BACnet Communication Interface (BCI-I)
Transcription
BACnet Communication Interface (BCI-I)
Integration Guide BACnet™ Communication Interface (BCI-I) for IntelliPak™ and Commercial Self-contained September 2009 ACC-SVP01B-EN Copyright © 2009 Trane All rights reserved This document and the information in it are the property of Trane and may not be used or reproduced in whole or in part, without the written permission of Trane. Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change. Trademarks IntelliPak, Tracer, Trane, and the Trane logo are trademarks of Trane in the United States and other countries. All trademarks referenced in this document are the trademarks of their respective owners. 2 ACC-SVP01B-EN • BCI0I Integration Guide Table of Contents Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Ordering Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 BACnet Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 BCI-I Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Starting a Session of Tracer TU and Direct Connection . . . . . . . . . . . . . . . . . 5 IP Units Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 BACnet Object Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Change Baud Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Change Device ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Stand-alone or BAS Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 IntelliPak Control Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . BAS Unit Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Periodic Update of BAS Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . BAS Communication Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 8 9 9 Input/Output Commands and Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 System Control Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Filter Timer Reset Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Diagnostics Reset Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Setpoint Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Timestamp Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 BCI IntelliPak Rotary Switches and LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Rotary Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 LEDs Description, Behavior, and Troubleshooting . . . . . . . . . . . . . . . . . . . . . 13 BACnet Data Points and Configuration Property Definitions . . . . . . . . . . . . . . . 17 BACnet Protocol Implementation Conformance Statement (PICS) . . . . . . . 17 Standardized Device Profile (Annex L) . . . . . . . . . . . . . . . . . . . . . . . . . . . Interoperability Building Blocks (Annex K) . . . . . . . . . . . . . . . . . . . . . . . . Segmentation Capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Object Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 17 18 19 BACnet Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Data Link Layer Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Device Address Binding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Networking Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Object Data Points and Diagnostic Data Points . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 ACC-SVP01B-EN • BCI-I Integration Guide 3 Overview The BACnet Communication Interface for IntelliPak (BCI-I) is comprised of a Tracer™ UC400 controller with interface software. It is a non-programmable communications module that allows heating, ventilation, and air-conditioning (HVAC) equipment to communicate on a BACnet communications network. This guide provides: • A list of ordering numbers • A brief overview of the BACnet™ protocol • BCI-I configuration information • A explanation of the BCI-I device rotary switches and LEDs • Data point configuration property definitions • Tables listing object data points • Additional resources • A glossary of terms Note: Users of this guide should have basic knowledge of BACnet protocol. For more detailed information about this protocol, visit the company web site listed under “Additional Resources,” p. 44. Ordering Numbers Order Number Description X13651544-010 IntelliPak I; for software and hardware C175218460010 IntelliPak I, II, and CSC; for field-installed kit BACnet Protocol The Building Automation and Control Network (BACnet and ANSI/ASHRAE Standard 135-2004) protocol is a standard that allows building automation systems or components from different manufacturers to share information and control functions. BACnet provides building owners the capability to connect various types of building control systems or subsystems together for a variety of reasons. In addition, multiple vendors can use this protocol to share information for monitoring and supervisory control between systems and devices in a multi-vendor interconnected system. The BACnet protocol identifies standard objects (data points) called BACnet objects. Each object has a defined list of properties that provide information about that object. BACnet also defines a number of standard application services that are used to access data and manipulate these objects and provides a client/server communication between devices. For more information on BACnet protocol, refer to “Additional Resources,” p. 44. BACnet Testing Laboratory (BTL) Certification The BCI-I supports the BACnet communication protocol and has been designed to meet the requirements of the application-specific control profile. For more details, refer to the BTL web site at www.bacnetassociation.org. 4 ACC-SVP01B-EN • BCI-I Integration Guide BCI-I Configuration BCI-I Configuration This section will provide the following information when configuring the BCI-I: • Overview • Starting a session of Tracer TU and direct connection • Resetting to factory default • Configuring IP units • Configuring BACnet objects • Changing baud rate and device ID • Input/output and equipment functions Overview The BCI-I device is designed as a self-configuring controller to accommodate the many possible equipment configuration options available in the IntelliPak line of equipment. This self-configuring device eliminates the need for the BAS technician having to create BACnet objects, minimizes the risk of object configuration errors, and allows the IntelliPak unit to be quickly installed in the BAS. The self-configuration process only creates objects that are appropriate for the feature set of the specific IntelliPak unit the BCI-I is connected to. Once this process is complete, the device exits factory mode and enters the normal mode of operation. At this point, the self-configuration process will not start when power is applied to the device. The set of objects listed in Table 3, p. 24 through Table 10, p. 31, are the super set of all possible objects supported by the IntelliPak line of equipment. The BAS technician should query the device for the list of actual objects that have been created in the device. Starting a Session of Tracer TU and Direct Connection Tracer TU is the service tool software that allows the technician to modify the operation of the device and to discover the BACnet objects present in the device. To modify the device or discover objects, the user must first connect to Tracer TU as follows: WARNING: Remove power from the HVAC equipment before opening electrical control panel. 1. Connect a USB cable directly between the laptop PC and the service port located on the front of the BCI-I device. When connecting to the controller for the first time, the Found New Hardware Wizard appears. Follow the wizard instructions to install the USB hardware driver. 2. Click either the Tracer TU desktop icon or the Tracer TU program item in the Tracer TU group on the Start menu. The Tracer TU splash screen appears briefly followed by the Connect dialog box. 3. Select the Direct Connection (Via USB cable) radio button if it is not already selected. 4. Click the Connect button and the Tracer TU main page will appear after successful connection. Note: The BCI-I may be powered via the USB cable or 24 Vac from the HVAC unit. Concurrent connection of unit power and the USB cable will not harm the BCI-I device. For more detailed information about direct connection to Tracer TU, refer to the Tracer™ TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083). ACC-SVP01B-EN • BCI-I Integration Guide 5 BCI-I Configuration Reset to Factory Default Factory default mode is the only mode the technician can use to set the units of measure for the device or to scan the IntelliPak unit to create BACnet objects. The process of putting the device in factory default mode must be run prior to executing units of measure configuration or the object self-configuration process. WARNING: Remove power from the HVAC equipment before opening electrical control panel. To reset the controller to factory default/unconfigured state: 1. Power down the unit. The IMC buss must not be active during reset. 2. Establish the connection between Tracer TU and the device. Follow the procedure, “Starting a Session of Tracer TU and Direct Connection,” p. 5. 3. From the Utilities menu, select Controller and then Controller Settings. The Controller Settings page appears. 4. On the controller settings page there is a gray bar at the bottom with Save/Cancel buttons. Move the cursor near the left edge of the bar, keeping the cursor inside the bar. Click on this area and a Clear Controller button will appear in the upper right portion of the page. 5. Click the Clear Controller button and a pop-up window will appear asking for confirmation to reset the device. Click Yes. 6. After a few seconds a pop-up will appear confirming that the controller has been reset and indicating that the controller will be rebooted. Click OK. After the controller boots up, it will be in factory default state. The units of measure is SI (metric), the MS/TP baud rate is 76,800, and there will be no BACnet objects present in the controller. The controller must be in this state prior to changing the units of measure or self-configuring the device. If using inch-pound units of measure, proceed to the next section, “IP Units Configuration, otherwise, proceed to “BACnet Object Configuration. IP Units Configuration The BCI-I supports both inch-pound and SI (metric) units of measure. The factory default units of measure is SI. The device allows only a change of units for all objects as a whole. Mixed units of measure is not allowed. If the controller is not in factory default state, follow the previous procedure, “Reset to Factory Default,” p. 6. To change the units of measure in the device: 1. Establish the connection between Tracer TU and the BCI-I. Follow the procedure,“Starting a Session of Tracer TU and Direct Connection,” p. 5. 2. From the Utilities drop-down menu, select Controller and then Controller Settings. The page contains four configuration frames that are minimized. Expand the Controller Units frame. 3. In the Device Units box of the frame, select IP units of measure radio button and then click Save button in the lower right corner of the window. A pop-up will display indicating that changes were saved to the controller. Select OK. 4. Exit Tracer TU and cycle power to the controller by disconnecting the USB plug and then reconnecting the plug. After the controller boots up, it will be in factory default state, the units of measure is IP, the MS/TP baud rate is 76,800, and there will be no BACnet objects present in the controller. 6 ACC-SVP01B-EN • BCI-I Integration Guide BCI-I Configuration BACnet Object Configuration Configuring BACnet objects is a self-configuring process. If the controller is not in factory default state, follow the previous procedure, “Reset to Factory Default,” p. 6. 1. Remove the USB cable plug from the device. 2. Apply power to the HVAC equipment. After the device boots up, the self-configuration process will begin. No further user action is required. Note: Do not remove power while the device is in self-configuration mode. This typically takes 2 to 4 minutes to complete. Once complete, the device enters normal operating mode. Change Baud Rate The BCI-I device supports four baud rates: 9600, 19200, 38400, and 76800 baud. The default baud rate is 76800 baud. The baud rate can be modified with Tracer TU. WARNING: Remove power from the HVAC equipment before opening electrical control panel. To change baud rate: 1. Establish the connection between Tracer TU and the BCI-I. Follow the procedure,“Starting a Session of Tracer TU and Direct Connection,” p. 5. 2. From the Utilities drop-down menu, select Controller and then Controller Settings. The page contains four configuration frames that are minimized. Expand the Protocol frame. 3. Click on the drop down arrow for the Baud Rate list and select the desired baud rate. 4. Click Save button in the lower right corner of the window. A pop-up will display indicating that changes were saved to the controller. Click OK. 5. Exit Tracer TU and disconnect the USB cable plug. 6. Apply power to the HVAC equipment. Change Device ID By default, the BCI-I device sets its device ID to the same value as the one defined by the rotary switches (MS/TP MAC address) on the front of the device. Refer to the section, “Rotary Switches,” p. 12. For simple networks, this is an easy method to guarantee unique device IDs across the link. The device also supports the full range of device ID values as specified by the BACnet Standard. Systems that require a more complex device ID convention are supported with Tracer TU, which has the ability to set the device ID via software configuration. WARNING: Remove power from the HVAC equipment before opening electrical control panel. The process for soft setting the device ID is as follows: 1. Establish the connection between Tracer TU and the BCI-I. Follow the procedure,“Starting a Session of Tracer TU and Direct Connection,” p. 5. 2. From the Utilities drop-down menu, select Controller and then Controller Settings. The page contains four configuration frames that are minimized. Expand the Protocol frame. 3. In the device ID box, select the check box next to Use Software Device ID to enable the functionality. The swipe-and-type box becomes available. 4. Type in the desired device ID. ACC-SVP01B-EN • BCI-I Integration Guide 7 BCI-I Configuration 5. Click the Save button in the lower right corner of the window. A pop-up will display indicating that changes were saved to the controller. Click OK. 6. Exit Tracer TU and disconnect the USB service plug. 7. Apply power to the HVAC equipment. Stand-alone or BAS Operation The control system on HVAC equipment has the ability to operate the unit as a stand-alone system or as part of a building automation system. The BCI-I (either factory or field installed), by default, is configured for stand-alone operation. This configuration enables the HVAC equipment to operate prior to the commissioning of the unit into the BAS. IntelliPak Control Configuration The IntelliPak control system must be configured at the human interface (HI) to support unit control from the BAS. The technician should set/verify the following configuration properties as illustrated below. The technician should also verify that the BAS Module Comm Failure diagnostic is not present. 1. Configuration Menu Configuration - Model Num Digit BAS Communication Module 34 Installed Software Revision Number: BAS Communications: BACnet 18.01 Human Interface Representation 2. Setup Menu Unit Control: BAS/NETWORK 3. Diagnostics Menu Active Diagnostic - - Auto Reset None BAS Unit Control The BCI-I provides a method for a BAS to control the operation of HVAC equipment. This method consists of BACnet objects that the BAS can access to control and monitor the status of equipment. There are two sets of objects: • Output objects; used by the BAS to provide command, setpoint, and sensor information to the IntelliPak unit. • Input objects; provide IntelliPak status information to the BAS. See tables 3 to 11 for the list of objects supported. The system allows the BAS technician to define the amount of control that the BAS system will apply to the unit. This is done by configuring the state of the Out of Service property of the output objects. If the property is set to True, the equipment will use a corresponding local value for control. If the property is set to False, the local value is ignored and the BAS-supplied value is used for control. The BAS value is provided to the IntelliPak by writing to the present value property of the corresponding output object. The factory default value for the Out of Service property of these objects is True. 8 ACC-SVP01B-EN • BCI-I Integration Guide BCI-I Configuration Periodic Update of BAS Values The BCI-I device requires the BAS system to provide a periodic update to the sensor values. This is required to protect against a loss of communication between the BAS and the BCI-I. By BACnet definition, the present value of the object will maintain the last value written to it, regardless of the amount of time that has elapsed since the last write. If communication is lost for several minutes or longer, the present value of BAS-supplied sensor objects may no longer represent the current state of environmental conditions. This may result in decreased occupant comfort and damage to building systems. BAS Communication Failure The BCI-I is designed to minimize communication failure mode. It does this by monitoring the length of time that has elapsed since the last write to the present value of the sensor object. If the length of time exceeds a predefined limit, the BCI-I will place the object into the fault state and revert to a unit-supplied sensor value for control. At power up, the sensor objects are set to a fault state and they will remain in this state until a write is detected. The minimum periodic refresh rate for the objects is defined in Table 3, p. 24. The following list is a set of sensor values that can be supplied by the BAS: • Space Static Pressure BAS • Space Air Temperature BAS • Discharge Air Temperature BAS • Duct Static Air Pressure BAS • Outdoor Air Temperature BAS • Outdoor Air Humidity BAS • Outdoor Airflow BAS • Space CO2 Concentration BAS • Space Humidity BAS Input/Output Commands and Calculations This section will provide the following information about certain inputs and outputs that perform unique control commands and calculations: • System control command • Filter timer and diagnostic reset commands • Setpoint calculations System Control Command Binary Output Object 1, has a special importance in the system. The object allows the BAS to command the unit to run in a local or BAS control mode. When the present value property of the object is set to Local Control, the IntelliPak unit will enter local control and ignore BAS supplied values. In this mode, the unit will use local sensor and setpoint values. When the object present value property is set to BAS Control, the IntelliPak unit will use the values supplied by the BAS system for unit control. Filter Timer Reset Command The BCI-I uses the Filter Runtime Hours object (AI 6) to generate a diagnostic when its present value is greater than the Filter Runtime Hours Setpoint, (AV 1) present value. The procedure for resetting the timer is as follows: ACC-SVP01B-EN • BCI-I Integration Guide 9 BCI-I Configuration The BAS will change the state of the Filter Timer Reset Command object (BO 13) to the active state. Upon the change to active state, the BCI-I will set the present value of the Filter Runtime Hours object to zero and then set the Reset Command object back to the inactive state. Diagnostics Reset Command The IntelliPak control system monitors the operation of the HVAC equipment. If an abnormal condition is detected, a diagnostic message is displayed on the human interface of the equipment control panel. In addition, the set of internal diagnostics is mapped to the set of BACnet binary input objects, as listed in Table 9, p. 31. The corresponding BI object will change state from inactive to active when the diagnostic is detected. The object has been configured to send a BACnet event message to external BACnet devices as defined by the protocol. The BAS has the ability to reset internal diagnostics by controlling the state of the Diagnostic Reset Command object (BO 14). The procedure for resetting diagnostics is as follows: The BAS will change the state of the Diagnostic Reset to the active state. Upon the change to active state, the IntelliPak control system will reset all internal diagnostics and set the state of all of the diagnostic objects to inactive. Upon completion of this action, the BCI-I will set the present value of the Diagnostic Reset Command object back to the inactive state. Setpoint Calculations The equipment has the ability to perform two basic control functions: • Space air temperature control • Discharge air temperature control When the unit is configured for discharge air control, it controls the temperature of the air leaving the unit to the discharge air temperature setpoint. When the unit is configured for space air temperature control, it controls the air temperature of the space that contains the space air temperature sensor. This value may be provided by wiring the sensor to the unit or via a sensor value provided by the BAS. The drawing below describes how the various temperature setpoints are calculated for space temperature control. When the unit is in an occupied mode the active space temperature setpoint is calculated based on the space temperature setpoint and the two setpoint offset values. In unoccupied mode, the unoccupied heating and cooling setpoints are used as the active setpoint. 10 ACC-SVP01B-EN • BCI-I Integration Guide BCI-I Configuration Timestamp Configuration The BCI-C device has a software-derived clock that maintains the time and date. The device requires the current time to enable it to record a timestamp when an event or a change in state is detected by a BACnet object. However, in the event of a power loss, the device does not maintain this time and date information. At powerup, the device time and date will default to 12:00 pm., Jan 1, 1970. To minimize the possibility that the unit timestamp is not representing the actual time, the BAS should be setup to periodically synchronize the device time clock with the BAS clock using the BACnet TimeSynchronization service. ACC-SVP01B-EN • BCI-I Integration Guide 11 BCI IntelliPak Rotary Switches and LEDs BCI IntelliPak Rotary Switches and LEDs This section provides information about the BCI-I rotary switches and LED displays. Rotary Switches There are three rotary switches on the front of the BCI-I device that are used to define a three-digit address when the BCI-I is installed on a BACnet communications network. The three-digit address setting is the BACnet MAC address. Note: All devices are MSTP masters with valid MAC addresses of 001 to 127 for BACnet. Figure 1. Setting rotary switches Before After ADDRESS 90 1 7 8 7 8 90 1 2 3 2 3 2 3 7 8 90 1 4 56 4 56 4 56 x100 x10 x1 Example of before and after setting addresses Each device on the BACnet/MSTP link must have a unique rotary switch setting, otherwise, communication problems will occur. 12 78 901 23 Use a 1/8 inch flathead screwdriver to set rotary switches. 456 Important: ACC-SVP01B-EN • BCI-I Integration Guide BCI IntelliPak Rotary Switches and LEDs LEDs Description, Behavior, and Troubleshooting There are 15 LEDs on the front of the BCI-I unit. However, LEDs BO1 through BO9 are not used for the BCI-I controller. Figure 2 shows the locations of each LED. The following table provides a description of each LED activity, an indication or troubleshooting tips for each, and any notes. Figure 2. LED locations Marquee LED LINK IMC TX RX SERVICE Table 1. LED Activities and Troubleshooting Tips LED Name Activities Shows solid green when the unit is powered and no problems exist Marquee LED Indication or Troubleshooting Tip (Denoted in Bullets) Shows solid red when the unit is powered, but represents low power or a malfunction • If low power; could be under voltage or the microprocessor has malfunction. Follow the troubleshoot procedure “24 Vac Measurement,” p. 15 to measure for the expected value range. • If malfunction; unpower and then repower unit to bring the device back up to normal operation. Shows blinking red when an a BACnet object is in a fault condition Alarm; when an alarm is triggered, for example, when a point goes into fault condition because of point failure or there is an indication of a custom alarm in TGP2 Shows blinking green when the device does not detect the IMC buss • Verify that the IPC wiring harness is connected to the IMC link terminals. • Verify the polarity of the IPC wiring harness at the unit terminals. LED not lit Notes Indicates normal operation Indicates power is OFF or there is a malfunction • OFF or malfunction; cycle the power. ACC-SVP01B-EN • BCI-I Integration Guide 13 BCI IntelliPak Rotary Switches and LEDs Table 1. LED Activities and Troubleshooting Tips LED Name Activities TX blinks green Link and IMC RX blinks yellow Blinks at the data transfer rate when the unit transfers data to other devices on the link Blinks at the data transfer rate when the unit receives data from other devices on the link Shows solid green Blinks green Notes TX LED: Regardless of connectivity or not, this LED will constantly blink as it continually looks for devices to communicate to. Indicates that the controller is not detecting communication LED not lit: Determine if, for example, a Tracer SC or BACnet device is trying to talk to the controller or if it is capable of talking to the controller. Also determine if the communication status shows down all of the time. • Not lit; cycle the power to reestablish communication Refer to “Ground Measurements,” p. 16 for a check-out procedure. Indicates someone is pressing this LED or the controller is not operating normally Press and hold during power up to place controller into boot code or press and hold for a count of approximately 10 seconds to clear the Device ID. • ON solid yellow; indicates there is reverse polarity LED not lit Service Indication or Troubleshooting Tip (Denoted in Bullets) Indicates controllers is not accessing application software What is Boot Code? When the UC400 is placed into boot code, the system will not run any applications such as Indicates controller is operating normally trending, scheduling, and TGP2 runtime. • Restore; using TU service tool LED not lit Binary 01 to Binary 09 14 Not Used ACC-SVP01B-EN • BCI-I Integration Guide BCI IntelliPak Rotary Switches and LEDs 24 Vac Measurement General Information Checkout Procedure Checking the voltage that is powering the UC400 is often a Step 1 necessary step when commissioning or troubleshooting. Operational issues and LED operation may result in a need to measure the input power. When troubleshooting, it is faster to take measurements while the load is in place. If Step 1 indicates an outof-specification voltage, disconnect Step 2 the UC400 and measure the AC voltage across the transformer. These measurements can direct the technician towards the problem source. ACC-SVP01B-EN • BCI-I Integration Guide Measurement Expected Value Measure AC voltage with the UC400 connected. Perform this measurement while the unit is under load. 20.0 Vac ≤ Vac ≤ 30.0 Vac Measure AC voltage with the UC400 unconnected. Perform this measurement while the unit is not under load. 20.0 Vac ≤ Vac ≤ 30.0 Vac 15 BCI IntelliPak Rotary Switches and LEDs Ground Measurements General Information and Checkout Procedure Measurement Expected Value Method 1: AC voltage between shield conductors and device chassis groundthe voltage difference between BACnet MS/TP device chassis ground connections should be close to zero. If the voltage difference is greater that 4.0 Vac, there will be marginal communication or intermittent communication problems. If the voltage difference is greater that 7.0 Vac, some devices will no longer communicate. Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground Vac ≤ 2.0 V Method 2: AC voltage between earth ground and device chassis ground- the chassis ground of the UC400 needs to be connected to earth ground by some route. Measure AC current across the current termination and confirm that only one end of the shield conductor is tied to the earth ground Vac ≤ 4.0 V (Must comply with National Electrical Code™and local electrical codes) Note: 16 Do not assume that the building frame is a valid earth ground. ACC-SVP01B-EN • BCI-I Integration Guide BACnet Data Points and Configuration Property Definitions BACnet Data Points and Configuration Property Definitions The BCI device allows an IntelliPak control system to communicate with BACnet systems and devices using BACnet MS/TP. This section includes information about: • BACnet protocol implementation conformance statement (PICS) • Object types: descriptions and configuration (refer to Table 2, p. 19) • BACnet protocol: data link layers, device address binding, networking options, and character sets • Object data points and configurations BACnet Protocol Implementation Conformance Statement (PICS) Standardized Device Profile (Annex L) Profile Description Supported Profile BACnet Advanced Application Controller (B-AAC) BACnet Application Specific Controller (B-ASC) 9 BACnet Building Controller (B-BC) BACnet Operator Workstation (B-OWS) BACnet Smart Actuator (B-SA) BACnet Smart Sensor (B-SS) Interoperability Building Blocks (Annex K) Data Sharing Description Supported BIBB Data Sharing-COV-B (DS-COV-B) Data Sharing-ReadProperty-A (DS-RP-A) 9 Data Sharing-ReadProperty-B (DS-RP-B) 9 Data Sharing-ReadPropertyMultiple-B (DS-RPM-B) 9 Data Sharing-WriteProperty-A (DS-WP-A) 9 Data Sharing-WriteProperty-B (DS-WP-B) 9 Data Sharing-WritePropertyMultiple-B (DS-WPM-B) 9 Alarm and Event Management Description Supported BIBB Alarm and Event-ACKI-B (AE-ACK-B) 9 Alarm and Event-Alarm Summary-B (AE-ASUM-B) 9 Alarm and Event-Enrollment Summary-B (AE-ESUM-B) 9 Alarm and Event-Information-B (AE-INFO-B) 9 Alarm and Event-Notification Internal-B (AE-N-I-B) 9 ACC-SVP01B-EN • BCI-I Integration Guide 17 BACnet Data Points and Configuration Property Definitions Trending Description Supported BIBB Trending-Automated Trend Retrieval-B (T-ATR-B) 9 Trending-viewing and Modifying Trends Internal-B (T-VMT-I-B) 9 Device Management Description Supported BIBB Device Management-Backup and Restore-B (DM-BR-B) 9 Device Management-Device Communication Control-B (DM-DCC-B) 9 Device Management-Dynamic Device Binding-A (DM-DDB-A) 9 Device Management-Dynamic Device Binding-B (DM-DDB-B) 9 Device Management-Dynamic Object Binding-B (DM-DOB-B) 9 Device Management-List Manipulation-B (DM-LM-B) 9 Device Management-Object Creation and Deletion-B (DM-OCD-B) 9 Device Management-Private Transfer-A (DM-PT-A) 9 Device Management-Private Transfer-B (DM-PT-B) 9 Device Management-Reinitialize Device-B (DM-RD-B) 9 Device Management-TimeSynchronization-B (DM-TS-B) 9 Segmentation Capability Segmentation Description Segmented Requests/ Window Size: 1 Segmented Responses/ Window Size: 1 18 Supported Segment 9 9 ACC-SVP01B-EN • BCI-I Integration Guide BACnet Data Points and Configuration Property Definitions Object Types Table 2. Object Type Descriptions and configurations Ability to Create Ability to Delete Required Properties Read Properties Written(a) Optional Properties Read Analog Input • • • • • • • • Object_Identifier Object_Name Object_Type Present_Value Status_Flags Event_State Out_Of_Service Units • • • • • • • • • • • • • • • • Object_Name Description Out_Of_Service Present_Value Reliability Min_Pres_Value Max_Pres_Value COV_Increment Time_Delay Notification_Class High_Limit Low_Limit Deadband Limit_Enable Event_Enable Notify_Type • • • • • • • • • • • • • • • Description Reliability Min_Pres_Value Max_Pres_Value COV_Increment Time_Delay Notification _Class High_Limit Low_Limit Deadband Limit_Enable Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps Yes Yes, only user created objects Analog Output • • • • • • • • • • Object_Identifier Object_Name Object_Type Present_Value Status_Flags Event_State Out_Of_Service Units Priority_Array Relinquish_Default • • • • • • • • • • • • • • • • • Object_Name Description Out_Of_Service Present_Value Reliability Min_Pres_Value Max_Pres_Value Relinquish_Default COV_Increment Time_Delay Notification_Class High_Limit Low_Limit Deadband Limit_Enable Event_Enable Notify_Type • • • • • • • • • • • • • • • Description Reliability Min_Pres-Value Max_Pres_Value COV_Increment Time_Delay Notification _Class High_Limit Low_Limit Deadband Limit_Enable Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps Yes Yes, only user created objects Analog Value • • • • • • • • Object_Identifier Object_Name Object_Type Present_Value Status_Flags Event_State Out_Of_Service Units • • • • • • • • • • • • • • • Object_Name Description Out_Of_Service Present_Value Reliability Relinquish_Default COV_Increment Time_Delay Notification_Class High_Limit Low_Limit Deadband Limit_Enable Event_Enable Notify_Type • • • • • • • • • • • • • • • Description Reliability Priority_Array Relinquish_Default COV_Increment Time_Delay Notification_Class High_Limit Low_Limit Deadband Limit_Enable Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps Yes Yes, only user created objects Binary Input • • • • • • • • Object_Identifier Object_Name Object_Type Present_Value Status_Flags Event_State Out_Of_Service Polarity • • • • • • • • • • • • • • • Object_Name Description Out_Of_Service Inactive_Text Active_Text Present_Value Reliability Change_Of_State_Count Elapsed_Active_Time Time_Delay Notification_Class Alarm_Value Event_Enable Acked_Transitions Notify_Type • • • • • • • • • • • • • • • • Description Inactive_Text Active_Text Change_Of_State_Time Change_Of_State_Count Time_Of_State_Count_Reset Elapsed_Active_Time Time_Of_Active_Time_Reset Time_Delay Notification_Class Alarm_Value Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps Reliability Yes Yes, only user created objects ACC-SVP01B-EN • BCI-I Integration Guide 19 BACnet Data Points and Configuration Property Definitions Table 2. Object Type Descriptions and configurations (continued) Ability to Create Ability to Delete Required Properties Read Properties Written(a) Optional Properties Read Binary Output • • • • • • • • • • Object_Identifier Object_Name Object_Type Present_Value Status_Flags Event_State Out_Of_Service Polarity Priority_Array Relinquish_Default • • • • • • • • • • • • • • • • • Object_Name Description Out_Of_Service Inactive_Text Active_Text Present_Value Reliability Change_Of_State_Count Elapsed_Active_Time Minimum_On_Time Minimum_Off_Time Relinquish_Default Time_Delay Notification_Class Event_Enable Acked_Transitions Notify_Type • • • • • • • • • • • • • • • • • • Description Inactive_Text Active_Text Change_Of_State_Time Change_Of_State_Count Time_Of_State_Count_Reset Elapsed_Active_Time Time_Of_Active_Time_Reset Minimum_On_Time Minimum_Off_Time Time_Delay Notification_Class Feedback_Value Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps Reliability Yes Yes, only user created objects Binary Value • • • • • • • Object_Identifier Object_Name Object_Type Present_Value Status_Flags Event_State Out_Of_Service • • • • • • • • • • • • • • • • • • Object_Name Description Out_Of_Service Inactive_Text Active_Text Present_Value Reliability Change_Of_State_Count Elapsed_Active_Time Minimum_On_Time Minimum_Off_Time Relinquish_Default Time_Delay Notification_Class Alarm_Value Event_Enable Acked_Transitions Notify_Type • • • • • • • • • • • • • • • • • • • • Description Inactive_Text Active_Text Change_Of_State_Time Change_Of_State_Count Time_Of_State_Count_Reset Elapsed_Active_Time Time_Of_Active_Time_Reset Priority_Array Relinquish_Default Minimum_On_Time Minimum_Off_Time Time_Delay Notification_Class Alarm_Value Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps Reliability Yes Yes, only user created objects Location Description Max_Segments_Accepted APDU_Segment_Timeout Max_Master Max_Info_Frames Local_Time Local_Date Configuration_Files Last_Restore_Time Backup_Failure_Timeout Active_COV_Subscriptions None None Yes Yes, only user created objects • Polarity Device • • • • • • • • • • • • • • • • • • • • Object_Identifier Object_Name Object_Type System_Status Vendor_Name Vendor_Identifier Model_Name Firmware_Revision Application_Software_Version Protocol_Version Protocol_Revision Protocol_Services_Supported Protocol_Object_Types_Supported Object_List Max_APDU_Length_Accepted Segmentation_Supported APDU_Timeout Number_Of_APDU_Retries Device_Address_Binding Database_Revision • • • • • • • Object_Name Location Description APDU_Segment_Timeout APDU_Timeout Number_Of_APDU_Retries Backup_Failure_Timeout • • • • • • • • • • • • Event Enrollment Object • • • • • • • • • • • • Object_Identifier Object_Name Object_Type Event_Type Notify_Type Event_Parameters Object_Property_Reference Event_State Event_Enable Acked_Transitions Notification_Class Event_Time_Stamps • • • • • • Object_Name Notify_Type Event_Parameters Object_Property_Reference Event_Enable Notification_Class • None 20 ACC-SVP01B-EN • BCI-I Integration Guide BACnet Data Points and Configuration Property Definitions Table 2. Descriptions and configurations (continued) Object Type Ability to Create Ability to Delete Required Properties Read Properties Written(a) Optional Properties Read Multistate Input • • • • • • • • Object_Identifier Object_Name Object_Type Present_Value Status_Flags Event_State Out_Of_Service Number_Of_States • • • • • • • • • • • • Object_Name Description State_Text Out_Of_Service Present_Value Reliability Time_Delay Notification_Class Alarm_Values Fault_Values Event_Enable Notify_Type • • • • • • • • • • State_Text Reliability Time_Delay Notification_Class Alarm_Values Fault_Values Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps Yes Yes, only user created objects Multistate Output • • • • • • • • • • Object_Identifier Object_Name Object_Type Present_Value Status_Flags Event_State Out_Of_Service Number_Of_States Priority_Array Relinquish Default • • • • • • • • • • Object_Name Description State_Text Out_Of_Service Present_Value Reliability Time_Delay Notification_Class Event_Enable Notify_Type • • • • • • • • • • State_Text Reliability Relinquish_Default Time_Delay Notification_Class Feedback_Values Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps Yes Yes, only user created objects Multistate Value • • • • • • • • Object_Identifier Object_Name Object_Type Present_Value Status_Flags Event_State Out_Of_Service Number_Of_States • • • • • • • • • • • • • • Object_Name Description State_Text Out_Of_Service Present_Value Reliability Priority_Array Relinquish_Default Time_Delay Notification_Class Alarm_Values Fault_Values Event_Enable Notify_Type • • • • • • • • • • • State_Text Reliability Relinquish_Default Time_Delay Notification_Class Alarm_Values Fault_Values Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps Yes Yes, only user created objects Notification Class • • • • • • • Object_Identifier Object_Name Object_Type Notification_Class Priority Ack_Required Recipient_List • • • • Object_Name Priority Ack_Required Recipient_List None Yes Yes, only user created objects Trend • • • • • • • • • • Object_Identifier Object_Name Object_Type Log_Enable Stop_When_Full Buffer_Size Log_Buffer Record_Count Total_Record_Count Event_State • • • • • • • • • • • • • • Object_Name Log_Enable Start_Time Stop_Time Log_DeviceObjectProperty Log_Interval Stop_When_Full Buffer_Size Log_Buffer Record_Count Notification_Threshold Notification_Class Event_Enable Notify_Type • • • • • • • • • • • • • Yes Yes, only user created objects Start_Time Stop_Time Log_DeviceObjectProperty Log_Interval Stop_When_Full Buffer_Size Notification_Threshold Records_Since_Notification Last_Notify_Record Notification_Class Event_Enable Acked_Transitions Event_Time_Stamps (a)Properties written for Present_Value and Reliability only if Out_of_Service is TRUE. ACC-SVP01B-EN • BCI-I Integration Guide 21 BACnet Data Points and Configuration Property Definitions BACnet Protocol Data Link Layer Options Supported Option Data Link Layer Description ANSI/ATA 878.1, 2.5 Mb ARCNET (Clause 8) ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), Baud Rate(s) BACnet IP, (Annex J) BACnet IP, (Annex J), Foreign Device ISO 8802-3, Ethernet (Clause 7)(10Base2, 10Base5, 10BaseT, Fiber) LonTalk, (Clause 11), Medium MS/TP Master (Clause 9), Baud Rate(s): 9600, 19200, 38400, 76800, and 115200 @1.5% Nominal Baud Rate 9 MS/TP Slave (Clause 9), Baud Rate(s) Other Point-to-Point, EIA 232 (Clause 10), Baud Rate(s): 9600, 19200, 38400 Point-to-Point, Modem (Clause 10), Baud Rate(s): 9600, 19200, 38400 Device Address Binding Device Address Binding Supported? Static Device Binding Supported 9 Networking Options Networking Descriptions Supported Option Annex H, BACnet Tunneling BACnet/IP Broadcast Management Device (BBMD) Does the BBMD Support Registrations by Foreign Devices? Router 22 ACC-SVP01B-EN • BCI-I Integration Guide BACnet Data Points and Configuration Property Definitions Character Sets Indicates support for multiple characters sets, but does not imply that all character sets are supported simultaneously. Maximum supported string length is 64 bytes (any character set). Character Set Descriptions ANSI X3.4 Supported 9 IBM/Microsoft DBCS ISO 10646 (UCS-4) ISO 10646 (UCS2) 9 ISO 8859-1 9 JIS C 6226 ACC-SVP01B-EN • BCI-I Integration Guide 23 Object Data Points and Diagnostic Data Points Object Data Points and Diagnostic Data Points For quick reference, the following tables are listed two different ways. Tables 2 through 9 are listed by input/output type and sorted by object identifier. These tables provide the user with the units type for each object type. Table 11, p. 34 and Table 12, p. 38 are sorted by object name and provide a complete list of object names, types, values/ranges, and descriptions. Not all points are available to the user. The available data points are defined during self-configuration and are dependent on the type of equipment. Table 3. Analog Output Object Identifier Object Name Description Refresh Rate (Sec.) Units Valid Range Percent (98) 0 to 100 NA Analog Output, 1 BAS supplied economizer Economizer Minimum Position Setpoint BAS position minimum setpoint value. Analog Output, 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints Degrees-Fahrenheit (64) in occupied and standby modes. 50.0 to 90.0 NA Analog Output, 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode. Degrees-Fahrenheit (64) 50.0 to 90.0 NA Analog Output, 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup Degrees-Fahrenheit (64) terminate temperature setpoint. 50.0 to 87.0 NA Analog Output, 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value. Degrees-Fahrenheit (64) 40.0 to 90.0 NA Analog Output, 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value. Degrees-Fahrenheit (64) 40.0 to 180.0 NA Analog Output, 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value. Inches-of-water (58) 0.70 to 4.30 (Ipak I) 0.70 to 5.10 (Ipak II) NA Analog Output, 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value. Inches-of-water (58) 0.03 to 0.30 -0.02 to 0.30 (enhanced StatiTrac) NA Analog Output, 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value. Inches-of-water (58) -0.28 to 0.50 -0.67 to 0.67 (enhanced StatiTrac) 900 Analog Output, 11 Space Air Temperature BAS BAS supplied space air temperature sensor value. Degrees-Fahrenheit (64) -39.5 to 200.0 900 Analog Output, 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value. Degrees-Fahrenheit (64) -39.5 to 200.0 900 Analog Output, 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value. Inches-of-water (58) 0.0 to 5.0 (Ipak I) 0.0 to 7.9 (Ipak II) 900 Analog Output, 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value. Degrees-Fahrenheit (64) -39.5 to 200.0 900 Analog Output, 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value. Percent (98) 10.0 to 90.0 900 Analog Output, 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint. Cubic-feet-per-minute (84) 0 to 60,000 NA Analog Output, 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value. Cubic-feet-per-minute (84) 0 to 65,000 900 Analog Output, 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value. Parts-per-million 50 to 2,200 900 Analog Output, 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value. Percent (98) 0 to 100 NA Analog Output, 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value. Percent (98) 0 to 100 NA Analog Output, 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value. Percent (98) 40 to 65 NA Analog Output, 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value. Degrees-Fahrenheit (64) 45.0 to 75.0 NA Analog Output, 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value. Degrees-Fahrenheit (64) 65.0 to 80.0 NA 24 ACC-SVP01B-EN • BCI-I Integration Guide Object Data Points and Diagnostic Data Points Table 3. Analog Output (continued) Refresh Rate (Sec.) Object Identifier Object Name Description Units Valid Range Analog Output, 25 Space Humidity BAS BAS supplied space humidity sensor value. Percent (98) 10 to 90 900 Analog Output, 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value. Percent (98) 20 to 50 NA Analog Output, 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode. Degrees-Fahrenheit (64) 1.0 to 5.0 NA Analog Output, 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode. Degrees-Fahrenheit (64) 1.0 to 10.0 NA Analog Output, 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode. Degrees-Fahrenheit (64) 52.0 to 88.0 NA Analog Output, 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode. Degrees-Fahrenheit (64) 50.0 to 90.0 NA Table 4. Analog Input Object Identifier Object Name Description Units (Listed Are Defaults) Analog Input, 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized. Percent (98) Analog Input, 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized. Percent (98) Analog Input, 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized. Percent (98) Analog Input, 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized. Percent (98) Analog Input, 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter. Hours (71) Percent (98) Analog Input, 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed. Analog Input, 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed. Percent (98) Analog Input, 9 Exhaust Damper Position Status Indicates the unit exhaust damper position. Percent (98) Analog Input, 10 Return Fan Speed Command Indicates the unit commanded return fan speed. Percent (98) Analog Input, 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position. Percent (98) Analog Input, 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position. Percent (98) Analog Input, 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint. Degrees-Fahrenheit (64) Analog Input, 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized. Percent (98) Analog Input, 15 Space Temperature Active The space temperature currently used for unit control. Degrees-Fahrenheit (64) Analog Input, 16 Space Humidity Active The space humidity value from a unit-mounted control. Percent-relative-humidity (29) Analog Input, 17 Space Enthalpy The space enthalpy value from a unit-mounted control. BTUs-per-pound (117) Analog Input, 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control. Degrees-Fahrenheit (64) Analog Input, 19 Outdoor Air Temperature Local The outdoor air temperature value from a unitmounted sensor. Degrees-Fahrenheit (64) Analog Input, 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control. Percent-relative-humidity (29) Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor. Percent-relative-humidity (29) Analog Input, 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit. Degrees-Fahrenheit (64 Analog Input, 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit. BTUs-per-pound (117) Analog Input, 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control. Degrees-Fahrenheit (64) Analog Input, 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor. Degrees-Fahrenheit (64 Return Air Temperature The return air temperature value from a unit-mounted sensor. Degrees-Fahrenheit (64 Analog Input, 21 Analog Input, 26 ACC-SVP01B-EN • BCI-I Integration Guide 25 Object Data Points and Diagnostic Data Points Table 4. Analog Input (continued) Object Identifier Object Name Description Units (Listed Are Defaults) Analog Input, 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control. Analog Input, 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unitmounted sensor. Inches-of-water (58) Analog Input, 30 Return Fan Air Pressure Return fan air pressure value measured by a unitmounted sensor. Inches-of-water (58) Analog Input, 31 Space Static Air Pressure Active Space static air pressure value being used for unit control. Inches-of-water (58) Analog Input, 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control. Parts-per-million (96) Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit. Degrees-Fahrenheit (64) Analog Input, 34 Outdoor Air Flow Active Outdoor airflow utilitzed by the unit. Cubic-feet-per-minute (84) Analog Input, 35 Condenser Water Entering Temperature The temperature of the water entering the condenser. Degrees-Fahrenheit (64) Analog Input, 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1. Degrees-Fahrenheit (64) Analog Input, 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2. Degrees-Fahrenheit (64) Analog Input, 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1 Degrees-Fahrenheit (64) Analog Input, 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2. Degrees-Fahrenheit (64) Analog Input, 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3. Degrees-Fahrenheit (64) Analog Input, 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4. Degrees-Fahrenheit (64) Analog Input, 42 Indicates the saturated condenser temperature for Condensing Saturated Temperature Circuit 1 circuit 1. Degrees-Fahrenheit (64) Analog Input, 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2. Degrees-Fahrenheit (64) Analog Input, 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3. Degrees-Fahrenheit (64) Analog Input, 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4. Degrees-Fahrenheit (64) Analog Input, 46 Condenser water leaving temperature value used for Condenser Water Leaving Temperature Active unit control. Analog Input, 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unitmounted sensor. Degrees-Fahrenheit (64) Analog Input, 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control. Inches-of-water (58) Analog Input, 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control. Degrees-Fahrenheit (64) Analog Input, 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control. Degrees-Fahrenheit (64) Analog Input, 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode. Degrees-Fahrenheit (64) Analog Input, 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode. Degrees-Fahrenheit (64) Analog Input, 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize. Percent (98) Analog Input, 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit. Cubic-feet-per-minute (84) Analog Input, 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control. Percent (98) Analog Input, 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control. Degrees-Fahrenheit (64) Analog Input, 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint. Degrees-Fahrenheit (64) Space Humidification Setpoint Active Indicates the setpoint used during space humidification control. Percent (98) Analog Input, 33 Analog Input, 62 26 Inches-of-water (58) Degrees-Fahrenheit (64) ACC-SVP01B-EN • BCI-I Integration Guide Object Data Points and Diagnostic Data Points Table 4. Analog Input (continued) Object Identifier Object Name Description Analog Input, 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position. Percent (98) Analog Input, 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature. Degrees-Fahrenheit (64) Analog Input, 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position. Percent (98) Analog Input, 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint. Degrees-Fahrenheit (64) Analog Input, 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode. Degrees-Fahrenheit (64) Analog Input, 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used. Degrees-Fahrenheit (64) Analog Input, 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used. BTUs-per-pound (117) Analog Input, 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence. Percent (98) Analog Input, 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module. Degrees-Fahrenheit (64) Analog Input, 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module. Degrees-Fahrenheit (64) Analog Input, 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized. Percent (98) Analog Input, 78 Space Temperature Setpoint Local The local space temperature setpoint. Degrees-Fahrenheit (64) Analog Input, 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized. Percent (98) Analog Input, 80 Cabinet Style Describes the cabinet style of the unit. NA Analog Input, 81 Cool Type Describes the cooling type installed in the unit. NA Analog Input, 82 Preheat Type Describes the heating type installed in the unit. NA Analog Input, 83 Reheat Type Describes the reheat type installed in the unit. NA Analog Input, 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation. Parts-per-million (96) Analog Input, 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation. Parts-per-million (96) Analog Input, 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint. Percent (98) Analog Input, 87 Space Air Temperature Local The space air temperature measured by a unitmounted sensor. Degrees-Fahrenheit (64) Analog Input, 88 Unit Energy Demand Indicates the current heat/cool energy demand of the unit. Percent (98) Analog Input, 89 Supply Fan Type Describes the supply fan type installed in the unit. NA Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit. NA Analog Input, 90 Table 5. Units (Listed Are Defaults) Analog Value Object Identifier Analog Value, 1 Object Name Description Units Valid Range Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation. Hours (71) 0 to 10,000 ACC-SVP01B-EN • BCI-I Integration Guide 27 Object Data Points and Diagnostic Data Points Table 6. Multistate Output BCI-I Object Identifier Description Object States Economizer Airside Enable BAS Command the state of the airside economizer system. 1 = Disabled 2 = Enabled 3 = Auto Multi-State Output, 2 Emergency Override BAS 1 2 3 Command the unit into an emergency mode of operation. 4 5 6 Multi-State Output, 3 Economizer Waterside Enable BAS 1 = Disabled Command the state of the waterside economizer system. 2 = Enabled 3 = Auto Multi-State Output, 7 Occupancy Mode Request BAS Command the unit into an occupancy mode. 1 = Occupied 2= Unoccupied 3 = Occupied Bypass 4 = Occupied Standby Multi-State Output, 1 Object Name = = = = = = Normal Pressurize Depressurize Purge Shutdown Fire Multi-State Output, 8 Application Mode Request BAS Command the unit to a specific application mode. 1 = Auto 2 = Heat 3 = Morning Warmup 4 = Cool 5 = Night Purge 6 = Precool 7 = Off 8 = Test 9 = Emergency Heat 10 = Fan Only 11 = Free Cool 12 = Ice Making 13 = Max Heat 14 = Economy Mode 15 = Dehumidifying 16 = Calibrate Multi-State Output, 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication. 1 = Flow 2 = No Flow 3 = Auto Table 7. Multistate Input BCI-I Object Identifier Multi-State Input, 2 Object Name Trane Unit Type Description Object States General description of the equipment-type classification. 1 = 1 Heat/1 Cool 2 = Heat Pump 3 = Blower Coil 4 = Unit Ventilator 5 = Fan Coil 6 = Rooftop 7 = Air Handler 8 = Vertical Self Contained 9 = Unitary 10 = VAV Box 11 = Fan Coil Multi-State Input, 9 Economizer Type General description of the equipment economizer system. 1 = None 2 = 2 Position Ventilation 3 = Modulation Economizer 4 = 2 Position Ventilation/Waterside Economizer 5 = Waterside Economizer 6 = Airside/Waterside Economizer 7 = TRAQ Damper 8 = Airside Economizer and TRAQ Damper/Sensor 9 = Waterside Economizer and TRAQ Damper/Sensor 10 = Airside/Waterside Economizer and TRAQ Damper/Sensor Multi-State Input, 10 Condenser Type General description of the equipment condenser system. 1 2 3 4 Multi-State Input, 13 Indicates if the unit is in a ventilation Ventilation Override Status override mode of operation. 28 = = = = 1= 2= 3= 4= 5= 6= None Air Cooled Water Cooled Evaporative Inactive Mode A Active Mode B Active Mode C Active Mode D Active Mode E Active ACC-SVP01B-EN • BCI-I Integration Guide Object Data Points and Diagnostic Data Points Table 7. Multistate Input (continued) BCI-I Object Identifier Object Name Description Object States Multi-State Input, 15 Economizer Decision Method Unit method to determine when the economizer system is enabled. 1= 2= 3= 4= Multi-State Input, 17 Cooling Reset Type Status Indicates the type of cooling reset. 1= None 2= Outdoor Air 3= Zone Multi-State Input, 18 Heating Reset Type Status Indicates the type of heating reset. 1= None 2= Outdoor Air 3= Zone Absolute Temperature Relative Temperature Absolute Enthalpy Comparative Enthalpy Multi-State Input, 19 Application Mode Status Indicates the current application mode of the equipment. 1 = Auto 2 = Heat 3 = Morning Warm-up 4 = Cool 5 = Night Purge 6 = Pre Cool 7 = Off 8 = Test 9 = Emergency Heat 10 = Fan Only 11 = Free Cool 12 = Ice-Making 13 = Max Heat 14 = Economy Mode 15 = Dehumidifying 16 = Calibrate Multi-State Input, 20 Occupancy Mode Status Indicates the current occupancy mode of the unit. 1 2 3 4 Multi-State Input, 21 Unit Stop Source Source of the stop command that turned off the equipment. 1= 2= 3= 4= 5= None Emergency Stop External Auto/Stop Local HI Remote HI Cooling Setpoint Source Indicates the source of the space cooling setpoint. 1= 2= 3= 4= 5= 6= RTM Zone Sensor Night Setback Panel Human Interface GBAS 0-5V BAS/Network GBAS 0-10V Multi-State Input, 23 Heating Setpoint Source Indicates the source of the space heating setpoint. 1= 2= 3= 4= 5= 6= RTM Zone Sensor Night Setback Panel Human Interface GBAS 0-5V BAS/Network GBAS 0-10V Multi-State Input, 24 Timed Override Status Timed override request or cancel from zone sensor. 1 = Idle 2 = On 3 = Cancel Multi-State Input, 25 Cool Output 1 Indicates the commanded state of cooling output 1. 1 = Off 2 = On 3 = Not Present Multi-State Input, 26 Cool Output 2 Indicates the commanded state of cooling output 2. 1 = Off 2 = On 3 = Not Present Multi-State Input, 27 Cool Output 3 Indicates the commanded state of cooling output 3. 1 = Off 2 = On 3 = Not Present Multi-State Input, 28 Cool Output 4 Indicates the commanded state of cooling output 4. 1 = Off| 2 = On 3 = Not Present Multi-State Input, 29 Heat Output 1 Indicates the commanded state of heating output 1. 1 = Off 2 = On 3 = Not Present Multi-State Input, 30 Heat Output 2 Indicates the commanded state of heating output 2. 1 = Off 2 = On 3 = Not Present Multi-State Input, 31 Heat Output 3 Indicates the commanded state of heating output 3. 1 = Off 2 = On 3 = Not Present Multi-State Input, 22 ACC-SVP01B-EN • BCI-I Integration Guide = = = = Occupied Unoccupied Occupied Bypass Occupied Standby 29 Object Data Points and Diagnostic Data Points Table 7. Multistate Input (continued) BCI-I Object Identifier Object Name Description Object States Multi-State Input, 32 Heat Output 4 Indicates the commanded state of heating output 4. 1 = Off 2 = On 3 = Not Present Multi-State Input, 33 Heat Output 5 Indicates the commanded state of heating output 5. 1 = Off 2 = On 3 = Not Present Multi-State Input, 34 Prefilter Status Indicates the prefilter media state. 1 = Clean 2 = Dirty 3 = Not Present Multi-State Input, 35 Primary Filter Status Indicates the primary filter media state. 1 = Clean 2 = Dirty 3 = Not Present Multi-State Input, 36 Final Filter Status Indicates the final filter media state. 1 = Clean 2 = Dirty 3 = Not Present Multi-State Input, 37 1= Off Supply Fan Proving Status Indicates the current state of the supply fan. 2= On 3= Not Present Multi-State Input, 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan. Multi-State Input, 39 Exhaust Fan Proving Status 1= Off Indicates if the unit exhaust fan is off or on. 2= On 3= Not Present Multi-State Input, 40 1= Off Return Fan Proving Status Indicates the current state of the return fan. 2= On 3= Not Present Multi-State Input, 41 Supply Fan Status Indicates the state of the supply fan. 1 = Off 2 = On 3 = Not Present Multi-State Input, 42 Return Fan Status Indicates the state of the return fan. 1 = Off 2 = On 3 = Not Present Multi-State Input, 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper. 1 = At or Below Minimum Position 2 = Above Minimum Position 3 = Not Present Multi-State Input, 44 Economizer System Status Indicates the operating state of the waterside economizer system. 1 = Disabled 2 = Enabled 3 = Not Present Table 8. 1 = Off 2 = On 3 = Not Present Binary Output Object Identifier Relinquish Default Object Name Description Binary Output, 1 System Control Command Command the unit to standaloneor BAS-controlled operation. Inactive Inactive = Standalone Control Active = BAS Control Binary Output, 5 Heat Lockout Command Command the unit to prevent heating operation. Inactive Inactive = Allow Heating Active = Heating Locked Out Binary Output, 6 Cool Lockout Command Command the unit to prevent cooling operation. Inactive Inactive = Allow Cooling Active = Cooling Locked Out Binary Output, 7 Economizer Minimum Position Command Command the unit to the minimum position operation. Inactive Inactive = Disabled Active = Enabled Binary Output, 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation. Inactive Inactive = Auto Active = On Binary Output, 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode. Inactive Inactive = Disabled Active = Enabled Binary Output, 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours. Inactive Inactive = Accumulating Active = Reset Binary Output, 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics. Inactive Inactive = Normal Active = Reset 30 Object States ACC-SVP01B-EN • BCI-I Integration Guide Object Data Points and Diagnostic Data Points Table 8. Binary Output Object Identifier Relinquish Default Object Name Description Binary Output, 15 Dehumidification Command Command the operating state of the dehumidification system. Active Inactive = Disabled Active = Auto Binary Output, 16 Humidification Command Command the operating state of the humidification system. Active Inactive = Disabled Active = Auto Object Name Description Object States Binary Input, 1 System Control Status Indicates the control system currently in command of the unit. Inactive = Standalone control Active = BAS control Binary Input, 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic. Inactive = Normal Active = Locked Out Binary Input, 3 Unit Status Indicates the current state of the unit. Inactive = Off Active = On Binary Input, 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open. Inactive = Auto Active = Open Binary Input, 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode Inactive = Inactive Active = Active Binary Input, 11 Service Test Mode Status Indicates if the unit is in service test mode. Inactive = Inactive Active = Active Binary Input, 15 Supply Fan Configuration Status Indicates the supply fan configuration. Inactive = Cycling Active = Continuous Binary Input, 22 Economizer Airside Enable Status Indicates the status of the airside economizer system. Inactive = Disabled Active = Enabled Binary Input, 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system. Inactive = Disabled Active = Enabled Binary Input, 24 Condenser Water Pump Status Indicates the status of the condenser water system pump. Inactive = Inactive Active = Active Binary Input, 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system. Inactive = No Flow Active = Flow Binary Input, 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function. Inactive = Inactive Active = Active Binary Input, 27 Energy Recovery Status Indicates the status of the energy recover system. Inactive = Inactive Active = Active Binary Input, 28 Energy Recovery Preheat Status Indicates the status of the energy recovery preheat function. Inactive = Inactive Active = Active Binary Input, 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1. Inactive = Inactive Active = Active Binary Input, 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2. Inactive = Inactive Active = Active Binary Input, 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3. Inactive = Inactive Active = Active Binary Input, 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4. Inactive = Inactive Active = Active Binary Input, 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit. Inactive = De-energized Active = Energized Binary Input, 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown. Inactive = Inactive Active = Active Binary Input, 243 Condenser Water Drain Status Indicates the status of the condenser water drain Inactive = Closed Active = Open Table 9. Object States Binary Input Object Identifier Table 10. Diagnostics, Binary Input Object Identifier(a) Object Name Binary Input, 29 Diagnostic: RTM Zone Temp Sensor Failure Diagnostic: RTM Zone Temp Sensor Failure Binary Input, 30 Diagnostic: Supply Air Temp Sensor Fail Diagnostic: Supply Air Temp Sensor Fail Diagnostic: RTM Aux Temp Sensor Failure Diagnostic: RTM Aux Temp Sensor Failure Diagnostic: SA Temp Sensor Fail Diagnostic: SA Temp Sensor Fail Binary Input, 31 (use Object Identifier for RT or CSC) Binary Input, 31 (use Object Identifier for FAU) ACC-SVP01B-EN • BCI-I Integration Guide Description 31 Object Data Points and Diagnostic Data Points Table 10. Diagnostics, Binary Input (continued) Object Identifier(a) Object Name Binary Input, 32 Diagnostic: OA Temperature Sensor Fail Diagnostic: OA Temperature Sensor Fail Binary Input, 33 Diagnostic: Mode Input Failure Diagnostic: Mode Input Failure Description Binary Input, 34 Diagnostic: Occ Zone Cool Setpoint Fail Diagnostic: Occ Zone Cool Setpoint Fail Binary Input, 35 Diagnostic: Occ Zone Heat Setpoint Fail Diagnostic: Occ Zone Heat Setpoint Fail Binary Input, 36 Diagnostic: Supply Air Press Sensor Fail Diagnostic: Supply Air Press Sensor Fail Binary Input, 37 Diagnostic: OA Humidity Sensor Failure Diagnostic: OA Humidity Sensor Failure Binary Input, 38 Diagnostic: Emergency Stop Diagnostic: Emergency Stop Binary Input, 39 Diagnostic: Supply Fan Failure Diagnostic: Supply Fan Failure Binary Input, 40 Diagnostic: Exhaust/Return Fan Failure Diagnostic: Exhaust/Return Fan Failure Binary Input, 41 Diagnostic: Lvg Evap Temp Sensor Fail - Ckt1 Diagnostic: Lvg Evap Temp Sensor Fail - Ckt1 Binary Input, 42 Diagnostic: Lvg Evap Temp Sensor Fail - Ckt2 Diagnostic: Lvg Evap Temp Sensor Fail - Ckt2 Binary Input, 43 Diagnostic: Low Pressure Ctl Open - Ckt1 Diagnostic: Low Pressure Ctl Open - Ckt1 Binary Input, 44 Diagnostic: Low Pressure Ctl Open - Ckt2 Diagnostic: Low Pressure Ctl Open - Ckt2 Binary Input, 45 Diagnostic: Cond Temp Sensor Fail - Ckt1 Diagnostic: Cond Temp Sensor Fail - Ckt1 Binary Input, 46 Diagnostic: Cond Temp Sensor Fail - Ckt2 Diagnostic: Cond Temp Sensor Fail - Ckt2 Binary Input, 47 Diagnostic: Compressor Trip - Ckt1 Diagnostic: Compressor Trip - Ckt1 Binary Input, 48 Diagnostic: Compressor Trip - Ckt2 Diagnostic: Compressor Trip - Ckt2 Binary Input, 49 Diagnostic: HEAT Aux Temp Sensor Fail Diagnostic: HEAT Aux Temp Sensor Fail Binary Input, 50 Diagnostic: Low Air Temp Limit Trip Diagnostic: Low Air Temp Limit Trip Binary Input, 51 Diagnostic: Heat Failure Diagnostic: Heat Failure Binary Input, 52 Diagnostic: Unocc Zone Cool Stpnt Fail Diagnostic: Unocc Zone Cool Stpnt Fail Binary Input, 53 Diagnostic: Unocc Zone Heat Stpnt Fail Diagnostic: Unocc Zone Heat Stpnt Fail Binary Input, 54 Diagnostic: SA Duct Press Setpoint Fail Diagnostic: SA Duct Press Setpoint Fail Binary Input, 55 Diagnostic: Space Pressure Setpoint Fail Diagnostic: Space Pressure Setpoint Fail Binary Input, 56 Diagnostic: Space Pressure Sensor Fail Diagnostic: Space Pressure Sensor Fail Binary Input, 57 Diagnostic: Return Air Temp Sensor Fail Diagnostic: Return Air Temp Sensor Fail Binary Input, 58 (use Object Identifier for RT or CSC) Diagnostic: Return Air RH Sensor Failure Diagnostic: Return Air RH Sensor Failure Diagnostic: Zone Humidity Sensor Failure Diagnostic: Zone Humidity Sensor Failure Binary Input, 58 (use Object Identifier for FAU) Binary Input, 59 Diagnostic: Auto - SA High Press Limit Diagnostic: Auto - SA High Press Limit Binary Input, 60 Diagnostic: Man - SA High Press Limit Diagnostic: Man - SA High Press Limit Binary Input, 61 Diagnostic: SCM Communications Failure Diagnostic: SCM Communications Failure Binary Input, 62 Diagnostic: MCM Communications Failure Diagnostic: MCM Communications Failure Binary Input, 63 Diagnostic: HEAT Communications Failure Diagnostic: HEAT Communications Failure Binary Input, 64 Diagnostic: ECEM Communications Failure Diagnostic: ECEM Communications Failure Binary Input, 65 Diagnostic: GBAS 0-5 VDC Comm Failure Diagnostic: GBAS 0-5 VDC Comm Failure Binary Input, 66 Diagnostic: BACnet Module Comm Fail Diagnostic: BACnet Module Comm Fail Binary Input, 67 Diagnostic: BAS/Network Comm Fail Diagnostic: BAS/Network Comm Fail Binary Input, 68 Diagnostic: NSB Panel Communication Fail Diagnostic: NSB Panel Communication Fail Binary Input, 69 Diagnostic: RTM EEPROM Failure Diagnostic: RTM EEPROM Failure Binary Input, 70 Diagnostic: Unit HI Communications Fail Diagnostic: Unit HI Communications Fail Binary Input, 71 Diagnostic: VOM Communications Failure Diagnostic: VOM Communications Failure Binary Input, 72 Diagnostic: Compressor Contact Fail-Ckt1 Diagnostic: Compressor Contact Fail-Ckt1 Binary Input, 73 Diagnostic: Compressor Contact Fail-Ckt2 Diagnostic: Compressor Contact Fail-Ckt2 Binary Input, 74 Diagnostic: SA Temp Cool Setpoint Fail Diagnostic: SA Temp Cool Setpoint Fail Binary Input, 75 Diagnostic: SA Temp Heat Setpoint Fail Diagnostic: SA Temp Heat Setpoint Fail Binary Input, 76 Diagnostic: Dirty Filter Diagnostic: Dirty Filter Binary Input, 77 Diagnostic: NSB Zone Temp Sensor Fail Diagnostic: NSB Zone Temp Sensor Fail 32 ACC-SVP01B-EN • BCI-I Integration Guide Object Data Points and Diagnostic Data Points Table 10. Diagnostics, Binary Input (continued) Object Identifier(a) Object Name Description Binary Input, 78 Diagnostic: VOM Mode A Active Diagnostic: VOM Mode A Active Binary Input, 79 Diagnostic: VOM Mode B Active Diagnostic: VOM Mode B Active Binary Input, 80 Diagnostic: VOM Mode C Active Diagnostic: VOM Mode C Active Binary Input, 81 Diagnostic: VOM Mode D Active Diagnostic: VOM Mode D Active Binary Input, 82 Diagnostic: VOM Mode E Active Diagnostic: VOM Mode E Active Binary Input, 83 Diagnostic: CO2 Sensor Failure Diagnostic: CO2 Sensor Failure Binary Input, 84 Diagnostic: VCM Aux Temp Sensor Failure Diagnostic: VCM Aux Temp Sensor Failure Binary Input, 85 Diagnostic: Blocked Air Return Diagnostic: Blocked Air Return Diagnostic: Velocity Press Sensor Fail Diagnostic: Velocity Press Sensor Fail Diagnostic: Vel Press Sensor (Rear) Diagnostic: Vel Press Sensor (Rear) Binary Input, 87 Diagnostic: VCM Communications Failure Diagnostic: VCM Communications Failure Binary Input, 88 Diagnostic: WSM Communications Failure Diagnostic: WSM Communications Failure Binary Input, 89 Diagnostic: Compressor Trip - Ckt 3 Diagnostic: Compressor Trip - Ckt 3 Binary Input, 86 (use Object Identifier for CSC, FAU, I-pak I, RT) Binary Input, 86 (use Object Identifier for RT, I-pak II) Binary Input, 90 Diagnostic: Compressor Trip - Ckt 4 Diagnostic: Compressor Trip - Ckt 4 Binary Input, 91 Diagnostic: Exh Fan VFD Bypass Enabled Diagnostic: Exh Fan VFD Bypass Enabled Binary Input, 92 Diagnostic: Cond Temp Sensor Fail - Ckt3 Diagnostic: Cond Temp Sensor Fail - Ckt3 Binary Input, 93 Diagnostic: Cond Temp Sensor Fail - Ckt4 Diagnostic: Cond Temp Sensor Fail - Ckt4 Binary Input, 94 Diagnostic: Ent Cond Wtr Tmp Sensor Fail Diagnostic: Ent Cond Wtr Tmp Sensor Fail Binary Input, 95 Diagnostic: WSM MA Temp Sensor Failure Diagnostic: WSM MA Temp Sensor Failure Binary Input, 96 Diagnostic: Enter Water Temp Sensor Fail Diagnostic: Enter Water Temp Sensor Fail Binary Input, 97 Diagnostic: Water Flow Failure Diagnostic: Water Flow Failure Binary Input, 98 Diagnostic: Supply Fan VFD Bypass Enable Diagnostic: Supply Fan VFD Bypass Enable Binary Input, 99 Diagnostic: High CO2 Level Diagnostic: High CO2 Level Binary Input, 100 Diagnostic: Low Pressure Ctl Open - Ckt4 Diagnostic: Low Pressure Ctl Open - Ckt4 Binary Input, 101 Diagnostic: Low Pressure Ctl Open - Ckt3 Diagnostic: Low Pressure Ctl Open - Ckt3 Binary Input, 102 Diagnostic: Compressor Contact Fail-Ckt4 Diagnostic: Compressor Contact Fail-Ckt4 Binary Input, 103 Diagnostic: Compressor Contact Fail-Ckt3 Diagnostic: Compressor Contact Fail-Ckt3 Binary Input, 104 Diagnostic: Evap Temp Sensor Fail - Ckt4 Diagnostic: Evap Temp Sensor Fail - Ckt4 Binary Input, 105 Diagnostic: Evap Temp Sensor Fail - Ckt3 Diagnostic: Evap Temp Sensor Fail - Ckt3 Binary Input, 106 Diagnostic: RTM Zone Humidity Sensor Fail Diagnostic: RTM Zone Humidity Sensor Fail Binary Input, 107 Diagnostic: Ent Evap Temp Sensor Fail-Ckt 1 Diagnostic: Ent Evap Temp Sensor Fail-Ckt 1 Binary Input, 108 Diagnostic: Ent Evap Temp Sensor Fail-Ckt 2 Diagnostic: Ent Evap Temp Sensor Fail-Ckt 2 Binary Input, 111 Diagnostic: Recovery Dirty Prefilter Diagnostic: Recovery Dirty Prefilter Binary Input, 112 Diagnostic: Recovery Lvg RA Sensor Fail Diagnostic: Recovery Lvg RA Sensor Fail Binary Input, 113 Diagnostic: Energy Recovery Wheel Fail Diagnostic: Energy Recovery Wheel Fail Binary Input, 114 Diagnostic: Cond Sump Max Level Fail Diagnostic: Cond Sump Max Level Fail Binary Input, 115 Diagnostic: Cond Sump Min Level Fail Diagnostic: Cond Sump Min Level Fail Binary Input, 116 Diagnostic: Cond Water Pump Fail (man) Diagnostic: Cond Water Pump Fail (man) Binary Input, 117 Diagnostic: Cond Water Pump Fail (auto) Diagnostic: Cond Water Pump Fail (auto) Binary Input, 118 Diagnostic: Cond Water Temp Sensor Fail Diagnostic: Cond Water Temp Sensor Fail Binary Input, 119 Diagnostic: Cond Sump Heater Fail (man) Diagnostic: Cond Sump Heater Fail (man) Binary Input, 120 Diagnostic: GBAS 0-10 VDC Comm Failure Diagnostic: GBAS 0-10 VDC Comm Failure Diagnostic: Reheat Head Press High Diagnostic: Reheat Head Press High Diagnostic: SA Drying Setpoint Failure Diagnostic: SA Drying Setpoint Failure Binary Input, 122 Diagnostic: Insufficient Airflow for Dehumid Diagnostic: Insufficient Airflow for Dehumid Binary Input, 123 Diagnostic: SA Reheat Setpoint Failure Diagnostic: SA Reheat Setpoint Failure Binary Input, 121 (use Object Identifier for RT) Binary Input, 121 (use Object Identifier for FAU) ACC-SVP01B-EN • BCI-I Integration Guide 33 Object Data Points and Diagnostic Data Points Table 10. Diagnostics, Binary Input (continued) Object Identifier(a) Object Name Description Binary Input, 124 Diagnostic: Unocc Dehumid Setpoint Fail Diagnostic: Unocc Dehumid Setpoint Fail Binary Input, 125 Diagnostic: Occ Dehumid Setpoint Failure Diagnostic: Occ Dehumid Setpoint Failure Binary Input, 126 Diagnostic: Unocc Humid Setpoint Fail Diagnostic: Unocc Humid Setpoint Fail Binary Input, 127 Diagnostic: Occ Humid Setpoint Failure Diagnostic: Occ Humid Setpoint Failure Binary Input, 128 Diagnostic: MDM Communications Failure Diagnostic: MDM Communications Failure Binary Input, 129 Diagnostic: Dirty Final Filter Diagnostic: Dirty Final Filter Binary Input, 130 Diagnostic: Vel Press Sensor (Front) Fail Diagnostic: Vel Press Sensor (Front) Fail Binary Input, 131 Diagnostic: High Superheat - Ckt 1 Diagnostic: High Superheat - Ckt 1 Binary Input, 132 Diagnostic: Low Refrigerant Charge - Ckt 1 Diagnostic: Low Refrigerant Charge - Ckt 1 Binary Input, 133 Diagnostic: High Superheat - Ckt 2 Diagnostic: High Superheat - Ckt 2 Binary Input, 134 Diagnostic: Low Refrigerant Charge - Ckt 2 Diagnostic: Low Refrigerant Charge - Ckt 2 Binary Input, 139 Diagnostic: MPM Communications Failure Diagnostic: MPM Communications Failure Binary Input, 140 Diagnostic: TPM Communications Failure Diagnostic: TPM Communications Failure Binary Input, 141 Diagnostic: Return Plenum Press Sensor Diagnostic: Return Plenum Press Sensor Binary Input, 142 Diagnostic: Return Press High Limit (Man) Diagnostic: Return Press High Limit (Man) Binary Input, 143 Diagnostic: Return Press High Limit (Auto) Diagnostic: Return Press High Limit (Auto) Binary Input, 144 Diagnostic: Cond Press Sensor Fail Ckt 2 Diagnostic: Cond Press Sensor Fail Ckt 2 Binary Input, 145 Diagnostic: Cond Press Sensor Fail Ckt 1 Diagnostic: Cond Press Sensor Fail Ckt 1 Binary Input, 146 Diagnostic: Invalid Unit Configuration Diagnostic: Invalid Unit Configuration Binary Input, 147 Diagnostic: Maintenance Required Diagnostic: Maintenance Required Binary Input, 148 Diagnostic: Unit Communications Failure Diagnostic: Unit Communications Failure Binary Input, 149 Diagnostic: Unit Stopped at Local HI Diagnostic: Unit Stopped at Local HI Binary Input, 150 Diagnostic: Unit Stopped at Remote HI Diagnostic: Unit Stopped at Remote HI Binary Input, 151 Diagnostic: RTM External Stop Diagnostic: RTM External Stop Binary Input, 166 Diagnostic: Stop Status Diagnostic: Stop Status Binary Input, 233 Diagnostic: Sump Min Level Cycling (man) Diagnostic: Sump Min Level Cycling (man) (a) Object States: Inactive = normal and Active = foreign language specific Table 11. All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) Object Identifier(a) Object Name Binary Input, 165 Alarm Relay Output Status Indicates the state of the alarm relay on the unit. Multi-State Output, 8 Application Mode Request BAS Command the unit to a specific application mode. Description Multi-State Input, 19 Application Mode Status Indicates the current application mode of the equipment. Analog Input, 80 Cabinet Style Describes the cabinet style of the unit. Binary Input, 2 Compressor Lockout Status One or more compressors are locked out with no diagnostic. Analog Input, 14 Condenser Capacity Status Indicates the unit condenser capacity being utilized. Multi-State Input, 10 Condenser Type General description of the equipment condenser system. Binary Input, 243 Condenser Water Drain Status Indicates the status of the condenser water drain Analog Input, 35 Condenser Water Entering Temperature The temperature of the water entering the condenser. Multi-State Output, 10 Condenser Water Flow BAS Command the unit to utilize a remote water flow indication. Binary Input, 25 Condenser Water Flow Status Indicates the flow status of water in the condenser system. Analog Input, 46 Condenser Water Leaving Temperature Active Condenser water leaving temperature value used for unit control. Analog Input, 47 Condenser Water Leaving Temperature Local Condenser water leaving temperature from a unit-mounted sensor. Binary Input, 24 Condenser Water Pump Status Indicates the status of the condenser water system pump. Analog Input, 42 Condensing Saturated Temperature Circuit 1 Indicates the saturated condenser temperature for circuit 1. 34 ACC-SVP01B-EN • BCI-I Integration Guide Object Data Points and Diagnostic Data Points Table 11. All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued) Object Identifier(a) Object Name Description Analog Input, 43 Condensing Saturated Temperature Circuit 2 Indicates the saturated condenser temperature for circuit 2. Analog Input, 44 Condensing Saturated Temperature Circuit 3 Indicates the saturated condenser temperature for circuit 3. Analog Input, 45 Condensing Saturated Temperature Circuit 4 Indicates the saturated condenser temperature for circuit 4. Analog Output, 19 Cool Capacity Enable Setpoint BAS BAS supplied cooling demand limit capacity setpoint value. Binary Output, 6 Cool Lockout Command Command the unit to prevent cooling operation. Multi-State Input, 25 Cool Output 1 Indicates the commanded state of cooling output 1. Multi-State Input, 26 Cool Output 2 Indicates the commanded state of cooling output 2. Multi-State Input, 27 Cool Output 3 Indicates the commanded state of cooling output 3. Multi-State Input, 28 Cool Output 4 Indicates the commanded state of cooling output 4. Analog Input, 81 Cool Type Describes the cooling type installed in the unit. Analog Input, 1 Cooling Capacity Status Indicates the unit cooling capacity being utilized. Multi-State Input, 17 Cooling Reset Type Status Indicates the type of cooling reset. Multi-State Input, 22 Cooling Setpoint Source Indicates the source of the space cooling setpoint. Analog Input, 55 Daytime Warmup Air Temperature Initiate Setpoint Active The air temperature setpoint used to start daytime warmup mode. Analog Input, 67 Daytime Warmup Initiate Temperature Setpoint Local The local daytime warmup initiate temperature setpoint. Analog Input, 68 Daytime Warmup Terminate Temperature Setpoint Temperature setpoint that will exit daytime warmup mode. Analog Output, 5 Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint. Analog Input, 79 Dehumidification Capacity Status Indicates the unit dehumidification capacity being utilized. Binary Output, 15 Dehumidification Command Command the operating state of the dehumidification system. Analog Input, 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control. Binary Input, 10 Demand Limit Status Indicates if the unit is in an energy-demand limit mode Binary Output, 14 Diagnostic Reset Command Command the unit to reset and clear diagnostics. Binary Input, 166 Diagnostic Stop Status Indicates if the unit diagnostic has caused the unit to shutdown. Analog Output, 6 Discharge Air Cooling Setpoint BAS BAS supplied discharge air temperature cooling setpoint value. Analog Output, 22 Discharge Air Dewpoint Setpoint BAS BAS supplied discharge air dewpoint setpoint value. Analog Input, 60 Discharge Air Dewpoint Temperature Setpoint Humidity setpoint value used during dehumidification control. Analog Output, 7 Discharge Air Heating Setpoint BAS BAS supplied discharge air temperature heating setpoint value. Analog Input, 61 Discharge Air Reheat Setpoint Active Indicates the active supply air reheat temperature setpoint. Analog Output, 23 Discharge Air Reheat Setpoint BAS BAS supplied discharge air reheat setpoint value. Analog Input, 24 Discharge Air Temperature Active The discharge air temperature currently used for unit control. Analog Output, 12 Discharge Air Temperature BAS BAS supplied discharge air temperature sensor value. Analog Input, 33 Discharge Air Temperature Dewpoint Discharge air temperature dewpoint being used by the unit. Analog Input, 52 Discharge Air Temperature Setpoint Active Discharge air temperature setpoint value being used for unit control. Analog Input, 28 Duct Static Air Pressure Active Duct static air pressure value currently being used for unit control. Analog Output, 13 Duct Static Air Pressure BAS BAS supplied duct static air pressure sensor value. Analog Input, 29 Duct Static Air Pressure Local Duct static air pressure value measured by a unit-mounted sensor. Analog Input, 48 Duct Static Air Pressure Setpoint Active Duct static pressure setpoint value being used for unit control. Analog Output, 8 Duct Static Air Pressure Setpoint BAS BAS supplied duct static air pressure setpoint value. Multi-State Output, 1 Economizer Airside Enable BAS Command the state of the airside economizer system. Multi-State Output, 1 Economizer Airside Enable BAS Command the state of the airside economizer system. Binary Input, 22 Economizer Airside Enable Status Indicates the status of the airside economizer system. Multi-State Input, 15 Economizer Decision Method Unit method to determine when the economizer system is enabled. Binary Output, 7 Economizer Minimum Position Command Command the unit to economizer minimum position operation. Analog Input, 56 Economizer Minimum Position Setpoint Active The minimum position value the economizer damper will utilize. Analog Output, 1 Economizer Minimum Position Setpoint BAS BAS supplied economizer position minimum setpoint value. Analog Input, 86 Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position setpoint. ACC-SVP01B-EN • BCI-I Integration Guide 35 Object Data Points and Diagnostic Data Points Table 11. All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued) Object Identifier(a) Object Name Description Multi-State Input, 44 Economizer System Status Indicates the operating state of the waterside economizer system. Multi-State Input, 9 Economizer Type General description of the equipment economizer system. Multi-State Output, 3 Economizer Waterside Enable BAS Command the state of the waterside economizer system. Analog Input, 70 Economizing Enthalpy Enable Setpoint Enthalpy setpoint below which economizing can be used. Analog Input, 69 Economizing Temperature Enable Setpoint Temperature setpoint below which economizing can be used. Multi-State Output, 2 Emergency Override BAS Command the unit into an emergency mode of operation. Analog Input, 64 Energy Recovery Exhaust Air Bypass Damper Position Energy recovery exhaust air bypass damper position. Binary Input, 26 Energy Recovery Frost Avoidance Status Status of the energy recovery system frost protection function. Analog Input, 65 Energy Recovery Leaving Exhaust Air Temperature Energy recovery leaving exhaust air temperature. Analog Input, 66 Energy Recovery Outdoor Air Bypass Damper Position Energy recovery outdoor air bypass damper position. Indicates the status of the energy recovery preheat function. Binary Input, 28 Energy Recovery Preheat Status Binary Input, 27 Energy Recovery Status Indicates the status of the energy recover system. Analog Input, 36 Evaporator Entering Temperature Circuit 1 Indicates the entering evaporator temperature for circuit 1. Analog Input, 37 Evaporator Entering Temperature Circuit 2 Indicates the entering evaporator temperature for circuit 2. Binary Input, 161 Evaporator Frost Protection Circuit 1 Status The status of evaporator frost protection function for circuit 1. Binary Input, 162 Evaporator Frost Protection Circuit 2 Status The status of evaporator frost protection function for circuit 2. Binary Input, 163 Evaporator Frost Protection Circuit 3 Status The status of evaporator frost protection function for circuit 3. Binary Input, 164 Evaporator Frost Protection Circuit 4 Status The status of evaporator frost protection function for circuit 4. Analog Input, 38 Evaporator Leaving Temperature Circuit 1 Indicates the leaving evaporator temperature for circuit 1 Analog Input, 39 Evaporator Leaving Temperature Circuit 2 Indicates the leaving evaporator temperature for circuit 2. Analog Input, 40 Evaporator Leaving Temperature Circuit 3 Indicates the leaving evaporator temperature for circuit 3. Analog Input, 41 Evaporator Leaving Temperature Circuit 4 Indicates the leaving evaporator temperature for circuit 4. Analog Input, 9 Exhaust Damper Position Status Indicates the unit exhaust damper position. Analog Input, 71 Exhaust Enable Damper Position Setpoint Exhaust air damper minimum position to enable exhaust sequence. Multi-State Input, 39 Exhaust Fan Proving Status Indicates if the unit exhaust fan is off or on. Analog Input, 8 Exhaust Fan Speed Command Indicates the unit commanded exhaust fan speed. Multi-State Input, 38 Exhaust Fan Status Indicates the commanded state of the exhaust fan. Analog Input, 90 Exhaust or Return Fan Type Describes the exhaust or return fan type installed in the unit. Analog Input, 6 Filter Runtime Hours Indicates the number of hours air has flowed through the filter. Analog Value, 1 Filter Runtime Hours Setpoint The setpoint value used by the filter run hours calculation. Binary Output, 13 Filter Timer Reset Command Command the unit to reset the accumulated filter run hours. Multi-State Input, 36 Final Filter Status Indicates the final filter media state. Analog Input, 13 Frost Avoidance Temperature Setpoint Indicates the frost coil avoidance temperature setpoint. Analog Output, 20 Heat Capacity Enable Setpoint BAS BAS supplied heating demand limit capacity setpoint value. Binary Output, 5 Heat Lockout Command Command the unit to prevent heating operation. Binary Output, 12 Heat or Reheat Enable Command Enable the heating or reheating system during dehumidification mode. Indicates the commanded state of heating output 1. Multi-State Input, 29 Heat Output 1 Multi-State Input, 30 Heat Output 2 Indicates the commanded state of heating output 2. Multi-State Input, 31 Heat Output 3 Indicates the commanded state of heating output 3. Multi-State Input, 32 Heat Output 4 Indicates the commanded state of heating output 4. Multi-State Input, 33 Heat Output 5 Indicates the commanded state of heating output 5. Analog Input, 2 Heat Primary Capacity Status Indicates the unit primary heating capacity being utilized. Analog Input, 3 Heat Secondary Capacity Status Indicates the unit secondary heating capacity being utilized. Multi-State Input, 18 Heating Reset Type Status Indicates the type of heating reset. Multi-State Input, 23 Heating Setpoint Source Indicates the source of the space heating setpoint. Analog Input, 76 Humidification Capacity Status Indicates the unit humidification capacity being utilized. 36 ACC-SVP01B-EN • BCI-I Integration Guide Object Data Points and Diagnostic Data Points Table 11. All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued) Object Identifier(a) Object Name Description Binary Output, 16 Humidification Command Command the operating state of the humidification system. NC 3 HVAC-Advisory HVAC-Advisory NC 1 HVAC-Critical HVAC-Critical NC 4 HVAC-Information HVAC-Information NC 2 HVAC-Service Required HVAC-Service Required Analog Input, 25 Mixed Air Temperature The mixed air temperature value from a unit-mounted sensor. Analog Input, 54 Morning Warmup Air Temperature Setpoint Active The air temperature setpoint used during morning warmup mode. Analog Output, 4 Morning Warmup Setpoint BAS BAS supplied temperature setpoint used in morning warmup mode. Multi-State Output, 7 Occupancy Mode Request BAS Command the unit into an occupancy mode. Multi-State Input, 20 Occupancy Mode Status Indicates the current occupancy mode of the unit. Analog Output, 29 Occupied Temperature Offset BAS Offset used to calculate setpoints in occupied mode. Analog Input, 11 Outdoor Air Damper Position Status Indicates the unit outdoor air damper position. Multi-State Input, 43 Outdoor Air Damper Status Indicates the operating state of the outdoor damper. Analog Input, 22 Outdoor Air Dewpoint The outdoor air dewpoint value being utilized by the unit. Analog Input, 23 Outdoor Air Enthalpy The outdoor air enthalpy value being utilized by the unit. Analog Input, 34 Outdoor Air Flow Active Outdoor airflow utilized by the unit. Analog Output, 17 Outdoor Air Flow BAS BAS supplied outdoor airflow sensor value. Analog Input, 20 Outdoor Air Humidity Active The outdoor air humidity value used for unit control. Analog Output, 15 Outdoor Air Humidity BAS BAS supplied outdoor air humidity sensor value. Analog Input, 21 Outdoor Air Humidity Local The outdoor air humidity value from a unit-mounted sensor. Analog Input, 57 Outdoor Air Minimum Flow Setpoint Active The minimum outdoor airflow setpoint being utilized by the unit. Analog Output, 16 Outdoor Air Minimum Flow Setpoint BAS BAS supplied minimum outdoor airflow setpoint. Analog Input, 18 Outdoor Air Temperature Active The outdoor air temperature currently used for unit control. Analog Output, 14 Outdoor Air Temperature BAS BAS supplied outdoor air temperature sensor value. Analog Input, 19 Outdoor Air Temperature Local The outdoor air temperature value from a unit-mounted sensor. Multi-State Input, 34 Prefilter Status Indicates the prefilter media state. Analog Input, 82 Preheat Type Describes the heating type installed in the unit. Multi-State Input, 35 Primary Filter Status Indicates the primary filter media state. Analog Input, 5 Reheat Capacity Status Indicates the unit reheat heating capacity being utilized. Analog Input, 83 Reheat Type Describes the reheat type installed in the unit. Analog Input, 26 Return Air Temperature The return air temperature value from a unit-mounted sensor. Analog Input, 30 Return Fan Air Pressure Return fan air pressure value measured by a unit-mounted sensor. Multi-State Input, 40 Return Fan Proving Status Indicates the current state of the return fan. Analog Input, 10 Return Fan Speed Command Indicates the unit commanded return fan speed. Multi-State Input, 42 Return Fan Status Indicates the state of the return fan. Binary Input, 11 Service Test Mode Status Indicates if the unit is in service test mode. Analog Output, 11 Space Air Temperature BAS BAS supplied space air temperature sensor value. Analog Input, 87 Space Air Temperature Local The space air temperature measured by a unit-mounted sensor. Analog Input, 50 Space Air Temperature Setpoint Active Space temperature setpoint value being used for unit control. Analog Output, 2 Space Air Temperature Setpoint BAS Base value to calculate setpoints in occupied and standby modes. Analog Input, 32 Space CO2 Concentration Active Space CO2 concentration being used for unit control. Analog Output, 18 Space CO2 Concentration BAS BAS supplied space CO2 sensor value. Analog Input, 84 Space CO2 High Limit Setpoint Indicates the high limit space CO2 setpoint for ventilation. Analog Input, 85 Space CO2 Low Limit Setpoint Indicates the low limit space CO2 setpoint for ventilation. Analog Output, 21 Space Dehumidification Setpoint BAS BAS supplied space dehumidification setpoint value. Analog Input, 17 Space Enthalpy The space enthalpy value from a unit-mounted control. ACC-SVP01B-EN • BCI-I Integration Guide 37 Object Data Points and Diagnostic Data Points Table 11. All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued) Object Identifier(a) Object Name Description Analog Input, 62 Space Humidification Setpoint Active Indicates the setpoint used during space humidification control. Analog Output, 26 Space Humidification Setpoint BAS BAS supplied space humidification setpoint value. Analog Input, 16 Space Humidity Active The space humidity value from a unit-mounted control. Analog Output, 25 Space Humidity BAS BAS supplied space humidity sensor value. Analog Input, 31 Space Static Air Pressure Active Space static air pressure value being used for unit control. Analog Output, 10 Space Static Air Pressure BAS BAS supplied space static air pressure sensor value. Analog Output, 9 Space Static Air Pressure Setpoint BAS BAS supplied space static air pressure setpoint value. Analog Input, 15 Space Temperature Active The space temperature currently used for unit control. Analog Input, 74 Space Temperature Cooling Setpoint Input Cooling temperature setpoint from space sensor module. Analog Input, 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module. Analog Input, 78 Space Temperature Setpoint Local The local space temperature setpoint. Analog Output, 30 Standby Temperature Offset BAS Offset value used to calculate setpoints in standby mode. Binary Output, 8 Supply Fan Configuration Command Command the unit supply fan to cycling or continuous operation. Binary Input, 15 Supply Fan Configuration Status Indicates the supply fan configuration. Multi-State Input, 37 Supply Fan Proving Status Indicates the current state of the supply fan. Analog Input, 7 Supply Fan Speed Command Indicates the unit commanded supply fan speed. Multi-State Input, 41 Supply Fan Status Indicates the state of the supply fan. Analog Input, 89 Supply Fan Type Describes the supply fan type installed in the unit. Binary Output, 1 System Control Command Command the unit to standalone- or BAS-controlled operation. Binary Input, 1 System Control Status Indicates the control system currently in command of the unit. Multi-State Input, 24 Timed Override Status Timed override request or cancel from zone sensor. Multi-State Input, 2 Trane Unit Type General description of the equipment-type classification. Analog Input, 88 Unit Energy Demand Indicates the current heat/cool energy demand of the unit. Binary Input, 3 Unit Status Indicates the current state of the unit. Multi-State Input, 21 Unit Stop Source Source of the stop command that turned off the equipment. Analog Output, 31 Unoccupied Cooling Temperature Setpoint BAS Cooling temperature setpoint used for control in unoccupied mode. Analog Output, 32 Unoccupied Heating Temperature Setpoint BAS Heating temperature setpoint used for control in unoccupied mode. Binary Input, 9 VAV Box Command Indicates whether VAV boxes should be in control or wide open. Multi-State Input, 13 Ventilation Override Status Indicates if the unit is in a ventilation override mode of operation. Binary Input, 23 Waterside Economizer Enable Status Indicates the status of the waterside economizer system. Analog Input, 12 Waterside Economizer Valve Position Status Indicates the unit waterside economizer valve position. (a) AI=Analog Input, AO=Analog Output, AV=Analog Value, BI=Binary Input, BO=Binary Output, MI=Multistate Input, MO=Multistate Output Table 12. Diagnostic Objects Sorted by Object Name Object Identifier(a) Object Name Value/Range Description BI 59 Diagnostic: Auto - SA High Press Limit 0 = inactive 1 = active Diagnostic: Auto - SA High Press Limit BI 66 Diagnostic: BACnet Module Comm Fail 0 = inactive 1 = active Diagnostic: BACnet Module Comm Fail 38 ACC-SVP01B-EN • BCI-I Integration Guide Object Data Points and Diagnostic Data Points Table 12. Diagnostic Objects Sorted by Object Name (continued) Object Identifier(a) Object Name Value/Range Description BI 67 Diagnostic: BAS/Network Comm Fail 0 = inactive 1 = active Diagnostic: BAS/Network Comm Fail BI 85 Diagnostic: Blocked Air Return 0 = inactive 1 = active Diagnostic: Blocked Air Return BI 83 Diagnostic: CO2 Sensor Failure 0 = inactive 1 = active Diagnostic: CO2 Sensor Failure BI 72 Diagnostic: Compressor Contact Fail-Ckt1 0 = inactive 1 = active Diagnostic: Compressor Contact Fail-Ckt1 BI 73 Diagnostic: Compressor Contact Fail-Ckt2 0 = inactive 1 = active Diagnostic: Compressor Contact Fail-Ckt2 BI 103 Diagnostic: Compressor Contact Fail-Ckt3 0 = inactive 1 = active Diagnostic: Compressor Contact Fail-Ckt3 BI 102 Diagnostic: Compressor Contact Fail-Ckt4 0 = inactive 1 = active Diagnostic: Compressor Contact Fail-Ckt4 BI 89 Diagnostic: Compressor Trip - Ckt 3 0 = inactive 1 = active Diagnostic: Compressor Trip - Ckt 3 BI 90 Diagnostic: Compressor Trip - Ckt 4 0 = inactive 1 = active Diagnostic: Compressor Trip - Ckt 4 BI 47 Diagnostic: Compressor Trip - Ckt1 0 = inactive 1 = active Diagnostic: Compressor Trip - Ckt1 BI 48 Diagnostic: Compressor Trip - Ckt2 0 = inactive 1 = active Diagnostic: Compressor Trip - Ckt2 BI 114 Diagnostic: Cond Sump Max Level Fail 0 = inactive 1 = active Diagnostic: Cond Sump Max Level Fail BI 115 Diagnostic: Cond Sump Min Level Fail 0 = inactive 1 = active Diagnostic: Cond Sump Min Level Fail BI 45 Diagnostic: Cond Temp Sensor Fail - Ckt1 0 = inactive 1 = active Diagnostic: Cond Temp Sensor Fail - Ckt1 BI 46 Diagnostic: Cond Temp Sensor Fail - Ckt2 0 = inactive 1 = active Diagnostic: Cond Temp Sensor Fail - Ckt2 BI 92 Diagnostic: Cond Temp Sensor Fail - Ckt3 0 = inactive 1 = active Diagnostic: Cond Temp Sensor Fail - Ckt3 BI 93 Diagnostic: Cond Temp Sensor Fail - Ckt4 0 = inactive 1 = active Diagnostic: Cond Temp Sensor Fail - Ckt4 BI 117 Diagnostic: Cond Water Pump Fail (auto) 0 = inactive 1 = active Diagnostic: Cond Water Pump Fail (auto) BI 116 Diagnostic: Cond Water Pump Fail (man) 0 = inactive 1 = active Diagnostic: Cond Water Pump Fail (man) BI 118 Diagnostic: Cond Water Temp Sensor Fail 0 = inactive 1 = active Diagnostic: Cond Water Temp Sensor Fail BI 76 Diagnostic: Dirty Filter 0 = inactive 1 = active Diagnostic: Dirty Filter BI 129 Diagnostic: Dirty Final Filter 0 = inactive 1 = active Diagnostic: Dirty Final Filter BI 64 Diagnostic: ECEM Communications Failure 0 = inactive 1 = active Diagnostic: ECEM Communications Failure BI 38 Diagnostic: Emergency Stop 0 = inactive 1 = active Diagnostic: Emergency Stop BI 113 Diagnostic: Energy Recovery Wheel Fail 0 = inactive 1 = active Diagnostic: Energy Recovery Wheel Fail BI 94 Diagnostic: Ent Cond Wtr Tmp Sensor Fail 0 = inactive 1 = active Diagnostic: Ent Cond Wtr Tmp Sensor Fail BI 107 Diagnostic: Ent Evap Temp Sensor Fail-Ckt 1 0 = inactive 1 = active Diagnostic: Ent Evap Temp Sensor Fail-Ckt 1 BI 108 Diagnostic: Ent Evap Temp Sensor Fail-Ckt 2 0 = inactive 1 = active Diagnostic: Ent Evap Temp Sensor Fail-Ckt 2 BI 109 Diagnostic: Ent Evap Temp Sensor Fail-Ckt 3 0 = inactive 1 = active Diagnostic: Ent Evap Temp Sensor Fail-Ckt 3 ACC-SVP01B-EN • BCI-I Integration Guide 39 Object Data Points and Diagnostic Data Points Table 12. Diagnostic Objects Sorted by Object Name (continued) Object Identifier(a) Object Name Value/Range Description BI 110 0 = inactive Diagnostic: Ent Evap Temp Sensor Fail-Ckt 4 1 = active BI 96 Diagnostic: Enter Water Temp Sensor Fail 0 = inactive 1 = active Diagnostic: Enter Water Temp Sensor Fail BI 105 Diagnostic: Evap Temp Sensor Fail - Ckt3 0 = inactive 1 = active Diagnostic: Evap Temp Sensor Fail - Ckt3 BI 104 Diagnostic: Evap Temp Sensor Fail - Ckt4 0 = inactive 1 = active Diagnostic: Evap Temp Sensor Fail - Ckt4 BI 91 Diagnostic: Exh Fan VFD Bypass Enabled 0 = inactive 1 = active Diagnostic: Exh Fan VFD Bypass Enabled BI 40 Diagnostic: Exhaust/Return Fan Failure 0 = inactive 1 = active Diagnostic: Exhaust/Return Fan Failure BI 120 Diagnostic: GBAS 0-10 VDC Comm Failure 0 = inactive 1 = active Diagnostic: GBAS 0-10 VDC Comm Failure BI 65 Diagnostic: GBAS 0-5 VDC Comm Failure 0 = inactive 1 = active Diagnostic: GBAS 0-5 VDC Comm Failure BI 49 Diagnostic: HEAT Aux Temp Sensor Fail 0 = inactive 1 = active Diagnostic: HEAT Aux Temp Sensor Fail BI 63 Diagnostic: HEAT Communications Failure 0 = inactive 1 = active Diagnostic: HEAT Communications Failure BI 51 Diagnostic: Heat Failure 0 = inactive 1 = active Diagnostic: Heat Failure BI 99 Diagnostic: High CO2 Level 0 = inactive 1 = active Diagnostic: High CO2 Level BI 131 Diagnostic: High Superheat - Ckt 1 0 = inactive 1 = active Diagnostic: High Superheat - Ckt 1 BI 133 Diagnostic: High Superheat - Ckt 2 0 = inactive 1 = active Diagnostic: High Superheat - Ckt 2 BI 122 Diagnostic: Insufficient Airflow for Dehumid 0 = inactive 1 = active Diagnostic: Insufficient Airflow for Dehumid BI 146 Diagnostic: Invalid Unit Configuration 0 = inactive 1 = active Diagnostic: Invalid Unit Configuration BI 50 Diagnostic: Low Air Temp Limit Trip 0 = inactive 1 = active Diagnostic: Low Air Temp Limit Trip BI 43 Diagnostic: Low Pressure Ctl Open - Ckt1 0 = inactive 1 = active Diagnostic: Low Pressure Ctl Open - Ckt1 BI 44 Diagnostic: Low Pressure Ctl Open - Ckt2 0 = inactive 1 = active Diagnostic: Low Pressure Ctl Open - Ckt2 BI 101 Diagnostic: Low Pressure Ctl Open - Ckt3 0 = inactive 1 = active Diagnostic: Low Pressure Ctl Open - Ckt3 BI 100 Diagnostic: Low Pressure Ctl Open - Ckt4 0 = inactive 1 = active Diagnostic: Low Pressure Ctl Open - Ckt4 BI 132 Diagnostic: Low Refrigerant Charge - Ckt 1 0 = inactive 1 = active Diagnostic: Low Refrigerant Charge - Ckt 1 BI 134 Diagnostic: Low Refrigerant Charge - Ckt 2 0 = inactive 1 = active Diagnostic: Low Refrigerant Charge - Ckt 2 BI 41 Diagnostic: Lvg Evap Temp Sensor Fail - Ckt1 0 = inactive 1 = active Diagnostic: Lvg Evap Temp Sensor Fail - Ckt1 BI 42 Diagnostic: Lvg Evap Temp Sensor Fail - Ckt2 0 = inactive 1 = active Diagnostic: Lvg Evap Temp Sensor Fail - Ckt2 BI 147 Diagnostic: Maintenance Required 0 = inactive 1 = active Diagnostic: Maintenance Required BI 60 Diagnostic: Man - SA High Press Limit 0 = inactive 1 = active Diagnostic: Man - SA High Press Limit BI 62 Diagnostic: MCM Communications Failure 0 = inactive 1 = active Diagnostic: MCM Communications Failure BI 128 Diagnostic: MDM Communications Failure 0 = inactive 1 = active Diagnostic: MDM Communications Failure 40 Diagnostic: Ent Evap Temp Sensor Fail-Ckt 4 ACC-SVP01B-EN • BCI-I Integration Guide Object Data Points and Diagnostic Data Points Table 12. Diagnostic Objects Sorted by Object Name (continued) Object Identifier(a) Object Name Value/Range Description BI 33 Diagnostic: Mode Input Failure 0 = inactive 1 = active Diagnostic: Mode Input Failure BI 139 Diagnostic: MPM Communications Failure 0 = inactive 1 = active Diagnostic: MPM Communications Failure BI 68 Diagnostic: NSB Panel Communication Fail 0 = inactive 1 = active Diagnostic: NSB Panel Communication Fail BI 77 Diagnostic: NSB Zone Temp Sensor Fail 0 = inactive 1 = active Diagnostic: NSB Zone Temp Sensor Fail BI 37 Diagnostic: OA Humidity Sensor Failure 0 = inactive 1 = active Diagnostic: OA Humidity Sensor Failure BI 32 Diagnostic: OA Temperature Sensor Fail 0 = inactive 1 = active Diagnostic: OA Temperature Sensor Fail BI 125 Diagnostic: Occ Dehumid Setpoint Failure 0 = inactive 1 = active Diagnostic: Occ Dehumid Setpoint Failure BI 127 Diagnostic: Occ Humid Setpoint Failure 0 = inactive 1 = active Diagnostic: Occ Humid Setpoint Failure BI 34 Diagnostic: Occ Zone Cool Setpoint Fail 0 = inactive 1 = active Diagnostic: Occ Zone Cool Setpoint Fail BI 35 Diagnostic: Occ Zone Heat Setpoint Fail 0 = inactive 1 = active Diagnostic: Occ Zone Heat Setpoint Fail BI 111 Diagnostic: Recovery Dirty Prefilter 0 = inactive 1 = active Diagnostic: Recovery Dirty Prefilter BI 112 Diagnostic: Recovery Lvg RA Sensor Fail 0 = inactive 1 = active Diagnostic: Recovery Lvg RA Sensor Fail Diagnostic: Reheat Head Press High 0 = inactive 1 = active Diagnostic: Reheat Head Press High BI 119 Diagnostic: Reheat Sat Cond Temp Sensor 0 = inactive 1 = active Diagnostic: Reheat Sat Cond Temp Sensor BI 58 (use Object Identifier for RT or CSC) Diagnostic: Return Air RH Sensor Failure 0 = inactive 1 = active Diagnostic: Return Air RH Sensor Failure BI 57 Diagnostic: Return Air Temp Sensor Fail 0 = inactive 1 = active Diagnostic: Return Air Temp Sensor Fail BI 141 Diagnostic: Return Plenum Press Sensor 0 = inactive 1 = active Diagnostic: Return Plenum Press Sensor BI 143 Diagnostic: Return Press High Limit (Auto) 0 = inactive 1 = active Diagnostic: Return Press High Limit (Auto) BI 142 Diagnostic: Return Press High Limit (Man) 0 = inactive 1 = active Diagnostic: Return Press High Limit (Man) BI 31 (use Object Identifier for RT CSC) Diagnostic: RTM Aux Temp Sensor Failure 0 = inactive 1 = active Diagnostic: RTM Aux Temp Sensor Failure BI 69 Diagnostic: RTM EEPROM Failure 0 = inactive 1 = active Diagnostic: RTM EEPROM Failure BI 15 Diagnostic: RTM External Stop 0 = inactive 1 = active Diagnostic: RTM External Stop BI 151 Diagnostic: RTM External Stop 0 = inactive 1 = active Diagnostic: RTM External Stop BI 106 Diagnostic: RTM Zone Humidity Sensor Fail 0 = inactive 1 = active Diagnostic: RTM Zone Humidity Sensor Fail BI 29 Diagnostic: RTM Zone Temp Sensor Failure 0 = inactive 1 = active Diagnostic: RTM Zone Temp Sensor Failure Diagnostic: SA Drying Setpoint Failure 0 = inactive 1 = active Diagnostic: SA Drying Setpoint Failure Diagnostic: SA Drying Temp Sensor Fail 0 = inactive 1 = active Diagnostic: SA Drying Temp Sensor Fail BI 54 Diagnostic: SA Duct Press Setpoint Fail 0 = inactive 1 = active Diagnostic: SA Duct Press Setpoint Fail BI 123 Diagnostic: SA Reheat Setpoint Failure 0 = inactive 1 = active Diagnostic: SA Reheat Setpoint Failure BI 121 (use Object Identifier for RT) BI 121 (use Object Identifier for FAU) B1 31 (use Object Identifier for FAU) ACC-SVP01B-EN • BCI-I Integration Guide 41 Object Data Points and Diagnostic Data Points Table 12. Diagnostic Objects Sorted by Object Name (continued) Object Identifier(a) Object Name Value/Range Description BI 74 Diagnostic: SA Temp Cool Setpoint Fail 0 = inactive 1 = active Diagnostic: SA Temp Cool Setpoint Fail BI 75 Diagnostic: SA Temp Heat Setpoint Fail 0 = inactive 1 = active Diagnostic: SA Temp Heat Setpoint Fail BI 61 Diagnostic: SCM Communications Failure 0 = inactive 1 = active Diagnostic: SCM Communications Failure BI 56 Diagnostic: Space Pressure Sensor Fail 0 = inactive 1 = active Diagnostic: Space Pressure Sensor Fail BI 55 Diagnostic: Space Pressure Setpoint Fail 0 = inactive 1 = active Diagnostic: Space Pressure Setpoint Fail BI 233 Diagnostic: Sump Min Level Cycling (man) 0 = inactive 1 = active Diagnostic: Sump Min Level Cycling (man) BI 36 Diagnostic: Supply Air Press Sensor Fail 0 = inactive 1 = active Diagnostic: Supply Air Press Sensor Fail BI 30 Diagnostic: Supply Air Temp Sensor Fail 0 = inactive 1 = active Diagnostic: Supply Air Temp Sensor Fail BI 39 Diagnostic: Supply Fan Failure 0 = inactive 1 = active Diagnostic: Supply Fan Failure BI 98 Diagnostic: Supply Fan VFD Bypass Enable 0 = inactive 1 = active Diagnostic: Supply Fan VFD Bypass Enable BI 140 Diagnostic: TPM Communications Failure 0 = inactive 1 = active Diagnostic: TPM Communications Failure BI 148 Diagnostic: Unit Communications Failure 0 = inactive 1 = active Diagnostic: Unit Communications Failure BI 70 Diagnostic: Unit HI Communications Fail 0 = inactive 1 = active Diagnostic: Unit HI Communications Fail BI 149 Diagnostic: Unit Stopped at Local HI 0 = inactive 1 = active Diagnostic: Unit Stopped at Local HI BI 150 Diagnostic: Unit Stopped at Remote HI 0 = inactive 1 = active Diagnostic: Unit Stopped at Remote HI BI 124 Diagnostic: Unocc Dehumid Setpoint Fail 0 = inactive 1 = active Diagnostic: Unocc Dehumid Setpoint Fail BI 126 Diagnostic: Unocc Humid Setpoint Fail 0 = inactive 1 = active Diagnostic: Unocc Humid Setpoint Fail BI 52 Diagnostic: Unocc Zone Cool Stpnt Fail 0 = inactive 1 = active Diagnostic: Unocc Zone Cool Stpnt Fail BI 53 Diagnostic: Unocc Zone Heat Stpnt Fail 0 = inactive 1 = active Diagnostic: Unocc Zone Heat Stpnt Fail BI 84 Diagnostic: VCM Aux Temp Sensor Failure 0 = inactive 1 = active Diagnostic: VCM Aux Temp Sensor Failure BI 87 Diagnostic: VCM Communications Failure 0 = inactive 1 = active Diagnostic: VCM Communications Failure BI 130 Diagnostic: Vel Press Sensor (Front) Fail 0 = inactive 1 = active Diagnostic: Vel Press Sensor (Front) Fail BI 86 (use Object Identifier for Ipak II-RT) Diagnostic: Vel Press Sensor (Rear) 0 = inactive 1 = active Diagnostic: Vel Press Sensor (Rear) BI 86 (use Object Identifier for Ipak I-RT, CSC, FAU) Diagnostic: Velocity Press Sensor Fail 0 = inactive 1 = active Diagnostic: Velocity Press Sensor Fail BI 71 Diagnostic: VOM Communications Failure 0 = inactive 1 = active Diagnostic: VOM Communications Failure BI 78 Diagnostic: VOM Mode A Active 0 = inactive 1 = active Diagnostic: VOM Mode A Active BI 79 Diagnostic: VOM Mode B Active 0 = inactive 1 = active Diagnostic: VOM Mode B Active BI 80 Diagnostic: VOM Mode C Active 0 = inactive 1 = active Diagnostic: VOM Mode C Active BI 81 Diagnostic: VOM Mode D Active 0 = inactive 1 = active Diagnostic: VOM Mode D Active 42 ACC-SVP01B-EN • BCI-I Integration Guide Object Data Points and Diagnostic Data Points Table 12. Diagnostic Objects Sorted by Object Name (continued) Object Identifier(a) Object Name Value/Range Description BI 82 Diagnostic: VOM Mode E Active 0 = inactive 1 = active Diagnostic: VOM Mode E Active BI 97 Diagnostic: Water Flow Failure 0 = inactive 1 = active Diagnostic: Water Flow Failure BI 88 Diagnostic: WSM Communications Failure 0 = inactive 1 = active Diagnostic: WSM Communications Failure BI 95 Diagnostic: WSM MA Temp Sensor Failure 0 = inactive 1 = active Diagnostic: WSM MA Temp Sensor Failure BI 58 (use Object Identifier for FAU) Diagnostic: Zone Humidity Sensor Failure 0 = inactive 1 = active Diagnostic: Zone Humidity Sensor Failure (a) BI=Binary Input ACC-SVP01B-EN • BCI-I Integration Guide 43 Additional Resources Additional Resources Use the following documents and links as additional resources: • Product support online: • www.bacnet.org • www.bacnetassociation.org • www.ashrae.org • Tracer TU Help online • Tracer™ TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083) • Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control Programming Guide (current version of CTV-SVP02) Note: For further assistance, contact your local Trane sales office. 44 ACC-SVP01B-EN • BCI-I Integration Guide Glossary A ASHRAE See American Society of Heating, Refrigeration, and Airconditioning Engineers American Society of Heating, Refrigeration, and Airconditioning Engineers An international organization of 50,000 persons with chapters throughout the world. The Society is organized for the sole purpose of advancing the arts and sciences of heating, ventilation, air conditioning and refrigeration. It benefits the public with its research, standards writing, continuing education, and publications. advocates BACnet protocol for use in system-level control devices. device A device is a standard BACnet object as defined by ASHRAE Standard 135-2004.The Tracer UC800 contains the BACnet object. Device ID The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302. There cannot be more than one device using the same Device ID. Each of the sample applications operate as a device and requires its own device id which defaults to zero. B I BACnet™ See Building Automation Control network interoperability The ability to integrate equipment from different vendors into a comprehensive automation and control system. In addition, digital communications between products designed independently, but designed to the same communication standard. BACnet interoperability building blocks A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality. The BIBBs are grouped together into BACnet device profiles. P BACnet object An abstract representation of the physical point or points where data is input from or output to an I/O device. Each object may have several BACnet properties that describe the status of that object. protocol A set of rules (language) that governs the exchange of data over a digital communications system. baud rate The number of signaling elements that occur each second during electronic data transmission. At slow speeds, baud indicates the number of bits per second that are transmitted. For example, 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps). At higher speeds, multiple bits may be encoded with each electrical change. For example, 4,800 baud may allow 9,600 bits to be sent each second. Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud. For example, a 9,600 bps modem may operate at only 2,400 baud. stand-alone operation Equipment is running in a stand-alone mode when all control is provided by the equipment's electronic control system. The system controls the building environment to a local set of configuration and setpoint values. It monitors the environmental conditions via sensors that are physically wired to the unit's control system. S BIBB See BACnet interoperability building blocks Building Automation Control network (BACnet and ANSI/ASHRAE Standard 135-2004) An interoperable protocol developed specifically for the building controls industry. The American National Standards Institute named it as a standard and Trane ACC-SVP01B-EN • BCI-I Integration Guide 45 www.trane.com For more information, contact your local Trane office or e-mail us at comfort@trane.com Literature Order Number ACC-SVP01B-EN Date September 2009 Supersedes ACC-SVP01A-EN Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.