Engineering Specifications GeoSource Heat Pumps

Transcription

Engineering Specifications GeoSource Heat Pumps
GeoSource 2000 Models GV/GH 18 Thru 120,
GC 18 Thru 42, and GW 29 Thru 380
GeoSource DualTEK Models GV/GH 36 Thru 67
GeoSource Vara Models GV/GH 36 Thru 67
GeoSource Vara 2 Plus GV/GH 38 Thru 58
GeoSource Ultra GW 37 Thru 77
GeoSource Invision3 - Dual Circuit Models Q14 Thru Q18
GeoSource Heat Pumps
Engineering
Specifications
1
Engineering
Guide
Specifications
General:
The GeoSource heat pump system
and the earth loop field shall be one system and
include all interconnecting piping and controls to
provide an efficient, harmoniously-balanced
package.
Earth Loop: The earth loop field shall be
constructed of high-density polyethylene or polybutylene piping. Its layout shall be of parallel
circuits terminated at a reducing header of
reverse return design. All underground joints
shall be fusion-welded. The earth loop field shall
be designed to provide a 25oF water/antifreeze
mixture to the heat pumps during the month of
January. The antifreeze shall be GTF heat
transfer fluid mixed 50% by volume with water
of 100-PPM grain hardness or less. The heat
pumps shall work over extended-range earth-loop
temperature variations (15oF to 110oF). The
piping shall consist of sufficient pump capacity
with suction and discharge pressure ports.
Valves shall be incorporated for purging all
debris and air from the total system. All
backfilling and grouting shall be done in
accordance with IGSHPA guidelines. All heat
pumps shall be installed with P/T ports for
pressure and temperature measurement.
Cabinet:
The heat pump cabinet shall be
constructed of heavy-gauge Galvaneal corrosionresistant steel coated with a baked-on powder
epoxy finish. It shall incorporate a full-width
aluminum condensate pan and be insulated with
1/2" high-density fiberglass insulation. It shall be
oriented to allow complete component service
access from the front.
heat exchanger shall be either non-coaxial opencenter canister-type with enhanced heat
exchanger surface, or stainless steel brazed plate.
An optional domestic water desuperheater coil of
vented double copper construction for potable
water with over-temperature control shall be
employed. The air heat exchanger shall use highdensity technology and incorporate enhanced
aluminum fins bonded to rifled copper tubing not
less than three rows deep. The expansion device
shall be a bi-flow thermostatic metering valve.
The reversing valve shall be of copper
construction with 24VAC control with fail-toheating positioning. All heat pumps shall have a
receiver and a factory-installed filter/drier.
Fan Motor and Controls: The fan motor
shall be a high-efficiency multi-speed PSC motor
or a variable speed DC motor coupled directly to
the fan wheel and be easily removed from the
heat pump without duct disconnection. All units
shall incorporate both low- and high-pressure
switches and freeze protection with total
refrigerant lockout with manual reset upon
application. All units shall have random start and
be anti-short cycle protected.
Testing and Warranty: All heat pumps shall
be factory run-tested with ASHRAE test lab
standards at simulated design conditions for a
minimum of two hours to assure component and
system integrity. All units shall be tested by and
rated in accordance with ARI 330, CSA C446,
and CSA C22.2 test laboratory safety and
performance standards. All heat pumps shall
carry a 2/5 residential or a 1/5 commercial
warranty.
Refrigerant Circuit: Compressors shall be
hermetically-sealed high-efficiency compliant
scroll mounted on vibration isolators. The water
Legend for Tables
BTU/hr
CAP
COP
CFM
DB
DHW
dP
EER
EWT
FLA
Heating or cooling capacity
Capacity
Coefficient of performance (BTU/hr out ÷ BTU/hr in)
Cubic feet per minute
Dry-bulb entering air temperature
Domestic hot water
Pressure drop across heat pump (in feet of water and psi)
Energy efficiency ratio (BTU/hr out ÷ watts in)
Entering water temperature (in degrees Fahrenheit)
Full-load amperage
GPM
HE
HR
KW
LRA
MBTU/hr
RLA
VA
WB
Gallons per minute of water flow
Heat extracted
Heat rejected
Kilowatt input
Locked-rotor amperage
Btu/hr X 1000
Rated-load amperage
Volt-amperes
Wet-bulb entering air temperature
†GeoSource DualTEK units are licensed under U.S. Patent Number 4,856,578
All Pressure Drop Ratings are for Pure Water
Performance values are +/- 10%, and are subject to change without notice.
Key to Model Numbers
GV420–1–TOOO
GeoSource STYLE
V = Vertical (Forced Air)
H = Horizontal (Forced Air)
C = Console (Forced Air)
W = Water (Hydronic)
D = Domestic (Hot Water)
WATER COIL
O = Standard
N = Cupro Nickel Well Water Coil
P = Cupro Nickel Hydronic Coil
V = Cupro Nickel Well Water and
Hydronic Coil
NOMINAL COOLING CAPACITY
X 1,000 BTU/hr
UNIT TYPE
O = Standard
V = Variable Speed ECM Blower (DualTEK)
D = Demonstrator
H = Heat only (Hydronic)
S = Special
T = Staged Tandems
U = Staged Tandems Heat Only
M = Modulating Valve (DualTEK)
B = Variable Speed ECM Blower w/
Modulating Valve (DualTEK)
2 = Two-Step Compressor (Vara 2 Plus)
DESUPERHEATER OPTION
0 = None
1 = Part Time, 65% DHW
ELECTRICAL SUPPLY OPTION
1 = 208/230V Single Phase
2 = 208/230V Three Phase
3 = 460V Three Phase
4 = 220V 50 Hz Single Phase
5 = 277V Single Phase
6 = 208/230 Single Phase w/ EMS
7 = 208/230 Three Phase w/ EMS
8 = 460 Three Phase w/ EMS
9 = 277 Three Phase w/ EMS
AIR OPTION
O = Standard
R = Right Return Vertical
B = Bottom Discharge Right
Return Vertical
C = Front Right Discharge Horizontal
DESIGN
T = GeoSource 2000
D = GeoSource DualTEK†
V = GeoSource Vara, Vara 2 Plus
U = GeoSource Ultra
Q18kW6T–000
DESIGN
Q = GeoSource Invision3 - Dual Circuit
NOMINAL HEATING CAPACITY
@ 32oF Earth Loop
14kW = 44,500 BTU/hr
16kW = 54,500 BTU/hr
18kW = 60,800 BTU/hr
NOMINAL COOLING CAPACITY
@77oF Earth Loop
4T = Four Ton
5T = Five Ton
6T = Six Ton
HOT WATER OPTIONS
000 = Forced Air Only
2 Stages Heating
2 Stages Cooling
SUP = Supplemental Domestic Water Heating
(Desuperheater)
2 Stages Heating
2 Stages Cooling
DHW = Full Time Domestic Hot Water
2 Stages Heating
1 Stage Cooling
1 Stage Domestic Hot Water
DWR = Full Time Domestic Hot Water with
Extra Capacity
2 Stages Heating
1 Stage Cooling
1 Stage Domestic Hot Water
1
Performance Ratings
GeoSource 2000, GeoSource DualTEK†, GeoSource Vara, Forced Air Models
ARI/ISO 13256-1: Ground Source, Closed Loop
Rated according to ARI/ISO 13256-1,
which includes power consumption
for water pumping.
MODEL
CFM
GPM
GV/GH/GC/180/181
625
4
GV/GH/GC/230/231
750
6
GV/GH/GC/290/291
1,050
7
GV/GH/GC/360/361
1,100
8
GV/GH/GC/420/421
1,150
10
GV/GH/520/521
1,550
11
GV/GH/590/591
1,800
13
GV/GH/670/671
2,150
14
GH980
2,700
22
GH1200
3,150
26
HEATING
32oF EWT
BTU/hr COP
16,500
3.4
21,100
3.8
25,700
3.5
32,000
3.3
37,400
3.2
45,000
3.2
54,000
3.3
63,000
3.3
78,000
3.2
107,000
3.1
COOLING
77oF EWT
BTU/hr EER
16,900
14.1
25,000
16.9
29,000
14.5
35,500
14.6
39,500
13.2
48,000
13.0
59,000
13.1
64,000
11.7
79,000
12.1
110,000
12.6
NRTL/C
Groundwater Source, Open Loop
HEATING
50 F EWT
70oF EWT
BTU/hr COP BTU/hr COP
18,200
3.8
21,600
3.9
23,000
3.7
26,300
4.0
29,400
3.8
35,600
4.3
36,600
3.6
45,000
4.1
43,300
3.6
50,300
3.9
54,700
3.5
66,000
3.9
65,700
3.6
78,800
3.9
73,500
3.4
90,500
3.6
100,500
3.5
118,500
3.7
124,000
3.3
148,000
3.6
o
MODEL
GV/GH/GC/180/181
GV/GH/GC/230/231
GV/GH/GC/290/291
GV/GH/GC/360/361
GV/GH/GC/420/421
GV/GH/520/521
GV/GH/590/591
GV/GH/670/671
GH980
GH1200
CFM
625
750
1,050
1,100
1,150
1,550
1,800
2,150
2,700
3,150
GPM
2
3
4
4
5
6
9
10
16
18
COOLING
50 F EWT
70oF EWT
BTU/hr EER BTU/hr EER
19,000
16.9
18,700
14.9
25,600
17.6
26,600
15.3
30,500
17.6
30,300
14.4
37,000
18.4
36,400
14.4
39,100
17.2
36,000
14.2
53,300
17.4
44,300
12.7
58,000
15.5
55,000
13.9
65,400
13.5
63,400
11.5
103,500
17.5
95,500
13.1
128,000
16.6
119,000
12.6
o
Heating based on 68oF DB air temperature entering the unit.
Cooling based on 80.6oF DB and 66.2oF WB air temperature entering the unit.
GeoSource 2000, GeoSource DualTEK†, GeoSource Ultra Hydronic Models
MODEL
GW/290/291
GW/360/361
GW/370/371
GW/420/421
GW/470/471
GW/520/521
GW/570/571
GW/590/591
GW/670/671
GW/770/771
GW980
GW1200
GW3800
Hydronic Loop
GPM
GPM
4
7
5
8
5
8
6
10
7
11
7
11
9
13
9
13
11
14
12
15
15
22
18
26
54
78
HEATING
32oF EWT
o
115 F output
85oF output
BTU/hr COP BTU/hr COP
24,400
3.4
25,100
4.7
28,200
3.3
29,000
4.7
29,800
3.4
31,900
5.1
36,500
3.4
37,600
4.9
40,700
3.5
43,900
5.4
42,600
3.1
43,800
4.6
49,700
3.3
54,900
5.0
51,900
3.2
53,400
4.7
60,200
3.0
61,900
4.5
65,800
3.2
69,700
5.2
85,600
3.1
86,600
4.5
100,500
3.0
101,900
4.4
300,700
3.0
304,700
3.5
Rated outside the scope of the ARI Groundsource Closed-Loop Heat Pump Certification Program
2
COOLING
77oF EWT
45oF output
BTU/hr EER
25,400
15.2
31,600
16.8
36,000
17.1
36,000
15.4
49,100
17.3
46,600
16.5
55,400
16.4
54,400
15.4
60,800
14.2
65,900
15.3
85,600
14.5
102,200
14.0
305,500
11.9
GeoSource Invision3 - Dual Circuit Models
ARI/ISO 13256-1: Ground Source, Closed Loop
HEATING
COOLING
HEATING
COOLING
Model - Q14kW4T
32oF EWT
77oF EWT
41oF EWT
70oF EWT
Suffix
CFM GPM BTU/hr COP BTU/hr EER BTU/hr COP BTU/hr EER
-000, -SUP, -DHW 1st Stage 1,050
6
----23,000 4.6 26,500 19.8
2nd Stage 1,675 11
44,500 3.7 48,000* 15.5*
-----DWR**
1st Stage 1,050
6
----23,000 4.6 26,500 19.8
2nd Stage 1,675 13
53,800 3.4
--*
--*
----GPM GPM
Domestic Hot Water
DHW Loop BTU/hr COP
-SUP
4
6
5,750
--DHW
6
6
20,500 3.0
-DWR
6
8
27,300 3.0
HEATING
COOLING
HEATING
COOLING
32oF EWT
77oF EWT
41oF EWT
70oF EWT
Suffix
CFM GPM BTU/hr COP BTU/hr EER BTU/hr COP BTU/hr EER
-000, -SUP, -DHW 1st Stage 1,250
8
----33,000 4.0 38,100 19.2
2nd Stage 1,775 13
50,000 3.4 58,200* 14.2*
-----DWR**
1st Stage 1,250
8
----33,000 4.0 38,100 19.2
2nd Stage 1,775 14
59,600 3.2
--*
--*
----GPM GPM
Domestic Hot Water
DHW Loop BTU/hr COP
-SUP
4
8
6,600
--DHW
6
6
20,500 3.0
-DWR
6
8
27,300 3.0
Model - Q16kW5T
HEATING
COOLING
HEATING
COOLING
o
o
o
32 F EWT
77 F EWT
41 F EWT
70oF EWT
Suffix
CFM GPM BTU/hr COP BTU/hr EER BTU/hr COP BTU/hr EER
-000, -SUP, -DHW 1st Stage 1,600
9
----43,100 3.2 44,200 15.3
2nd Stage 1,920 14
60,800 3.1 65,500* 12.1*
-----DWR**
1st Stage 1,600
9
----43,100 3.2 44,200 15.3
2nd Stage 1,920 15
64,800 3.1
--*
--*
----GPM GPM
Domestic Hot Water
DHW Loop BTU/hr COP
-SUP
4
9
6,900
--DHW
6
6
20,500 3.0
-DWR
6
8
27,300 3.0
Model - Q18kW6T
* Note: 2nd Stage Cooling is not available if unit is ordered with –DHW or –DWR option.
** Note: -DWR units have ARI ratings of the corresponding –000, -SUP, -DHW units.
GeoSource Vara 2 Plus Models
ARI/ISO 13256-1: Ground Source, Closed Loop
Model
GV/GH/380/381
GV/GH/480/481
GV/GH/580/581
HEATING
32oF EWT
CFM GPM BTU/hr COP
1st Stage
910
6
--2nd Stage 1180
8
30,500 3.9
1st Stage 1,295
9
--2nd Stage 1,680 11
43,100 3.6
1st Stage 1,425 11
--2nd Stage 1,850 13
51,800 3.6
COOLING
77oF EWT
BTU/hr EER
--38,000 16.0
--48,000 14.1
--62,000 14.5
HEATING
41oF EWT
BTU/hr COP
23,600 4.3
--33,500 4.1
--39,500 4.0
---
COOLING
70oF EWT
BTU/hr EER
30,300 22.8
--38,700 19.0
--45,900 18.6
--3
Configuration Options – All Models
GeoSource 2000 Vertical Forced Air Models
Model Suffix
GVxx0-x-Txxx
GVxx1-x-Txxx
GVxxx-1-Txxx
GVxxx-2-Txxx
GVxxx-3-Txxx
GVxxx-4-Txxx
GVxxx-5-Txxx
GVxxx-x-T0xx
GVxxx-x-TRxx
GVxxx-x-TBxx
GVxxx-x-Txx0
GVxxx-x-TxxN
Description
Standard, No Desuperheater
Desuperheater
Standard, 208/230-1, 60 Hz
208/230-3, 60 Hz
460-3, 60 Hz
220/240-1, 50 Hz
277-1, 60 Hz
Standard, Left Side Air Return
Right Side Return
Bottom Discharge, Right Return
Standard Earth Loop Coil
Cupro-Nickel Well Water Coil
18
•
•
•
23
•
•
•
∗
∗
∗
∗
•
∗
∗
•
∗
29
•
•
•
∗
∗
∗
36
•
•
•
∗
∗
∗
42
•
•
•
∗
∗
∗
52
•
•
•
∗
∗
∗
59
•
•
•
∗
∗
67
•
•
•
∗
∗
•
∗
∗
•
∗
•
∗
∗
•
∗
•
∗
∗
•
∗
•
∗
∗
•1
∗
•
∗
•
∗
•1
∗
•1
∗
29
•
•
•
∗
∗
∗
36
•
•
•
∗
∗
∗
42
•
•
•
∗
∗
∗
52
•
•
•
∗
∗
∗
59
•
•
•
∗
∗
67
•
•
•
∗
∗
98
•
•
•
∗
∗
120
•
•
•
∗
∗
∗
•
∗
∗
23
•
•
•
∗
∗
∗
∗
∗
∗
∗
∗
•
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
•
∗
∗
•
∗
∗
•
∗
∗
•
∗
∗
•
∗
∗
•
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗1
∗
∗1
∗
∗1
∗
•
∗
∗
∗
∗1
∗
•
∗
∗
∗
∗1
∗
∗
•
•
∗
GeoSource 2000 Horizontal Forced Air Models
Model Suffix
GHxx0-x-Txxx
GHxx1-x-Txxx
GHxxx-1-Txxx
GHxxx-2-Txxx
GHxxx-3-Txxx
GHxxx-4-Txxx
GHxxx-5-Txxx
GHxxx-6-Txxx
GHxxx-7-Txxx
GHxxx-8-Txxx
GHxxx-9-Txxx
GHxxx-x-T0xx
GHxxx-x-TCxx
GHxxx-x-Tx0x
GHxxx-x-TxTx
GHxxx-x-Txx0
GHxxx-x-TxxN
Description
Standard, No Desuperheater
Desuperheater
Standard, 208/230-1, 60 Hz
208/230-3, 60 Hz
460-3, 60 Hz
220/440-1, 50 Hz
277-1, 60 Hz
208/230-1, 60 Hz w/ EMS
208/230-3, 60 Hz w/ EMS
460-3, 60 Hz w/ EMS
277-1, 60 Hz w/ EMS
Standard, End Right Discharge
Front Right Discharge
Standard Forced Air
Staged Tandem Compressors
Standard Earth Loop Coil
Cupro-Nickel Well Water Coil
18
•
•
•
∗
∗
GeoSource Vara, Vara 2 Plus Forced Air Models
Model Suffix
Gxxx0-x-Vxxx
Gxxx1-x-Vxxx
Gxxxx-1-Vxxx
Gxxxx-2-Vxxx
GVxxx-x-V0xx
GHxxx-x-V0xx
GHxxx-x-VCxx
Gxxxx-x-Vxx0
Gxxxx-x-VxxN
Gxxxx-x-Vx2x
Description
Standard, No Desuperheater
Desuperheater
Standard, 208/230-1, 60 Hz
208/230-3, 60 Hz
Standard, Vertical Left Side Air Return
Standard, Horizontal End Right Discharge
Horizontal, Front Right Discharge
Standard Earth Loop Coil
Cupro-Nickel Well Water Coil
Vara 2 Plus
36
∗
∗
•
∗
•
•
∗
•
∗
38
∗
•
•
48
∗
•
•
•
∗
∗
•1
∗
•
•
∗
∗
•1
*
•
52
∗
•
•
∗
•
•
∗
•1
∗
GeoSource 2000 Console Forced Air Models
Model Suffix
GCxx0-x-T00x
GCxx0-1-T00x
GCxx0-2-T00x
GCxx0-3-T00x
GCxx0-x-T000
GCxx0-x-T00N
Description
Standard
Standard, 208/230-1, 60 Hz
208/230-3, 60 Hz
460-3, 60 Hz
Standard Earth Loop Coil
Cupro-Nickel Well Water Coil
18
•
•
•
∗
1
4
23
•
•
∗
∗
•
∗
29
•
•
∗
∗
•
∗
36
•
•
∗
42
•
•
∗
•
∗
•
∗
Brazed Plate Earth Loop Heat Exchanger
• Standard
∗ Special Order
58
∗
•
•
•
∗
∗
•1
∗
•
59
∗
•
•
∗
•
•
∗
•1
∗
67
∗
•
•
∗
•
•
∗
•1
∗
GeoSource Invision3 - Dual Circuit Forced Air Models
Model Suffix
QxxkWxT-000
QxxkWxT-SUP
QxxkWxT-DHW
QxxkWxT-DWR
Description
2 Heat / 2 Cool, No Desuperheater
2 Heat / 2 Cool, Desuperheater
2 Heat / 1 Cool / 1 DHW
2 Heat / 1 Cool / 1 DHW w/ extra Capacity
Q14
∗
∗
∗
∗
Q16
∗
∗
∗
∗
Q18
∗
∗
∗
∗
Note: All Invision3 are 208/230 VAC, Single Phase, 60 Hz
GeoSource 2000 Hydronic Models
Model Suffix
GWxx0-x-Txxx
GWxx1-x-Txxx
GWxxx-1-Txxx
GWxxx-2-Txxx
GWxxx-3-Txxx
GWxxx-4-Txxx
GWxxx-x-Tx0x
GWxxx-x-TxHx
GWxxx-x-TxTx
GWxxx-x-TxUx
GWxxx-x-Txx0
GWxxx-x-TxxN
GWxxx-x-TxxP
GWxxx-x-TxxV
Description
Standard, No Desuperheater
Desuperheater
Standard, 208/230-1, 60 Hz
208/230-3, 60 Hz
460-3, 60 Hz
220/240-1, 50 Hz
Standard Hydronic
Heat Only Hydronic
Staged Tandem Compressors
Staged Tandem Heat Only
Standard Earth Loop Coil
Cupro-Nickel Well Water Coil
Cupro-Nickel Hydronic Coil
Cupro-Nickel Well Water and Hydronic Coil
29
•
•
•
∗
∗
∗
•
∗
36
•
•
•
∗
∗
∗
•
∗
42
•
•
•
∗
∗
∗
•
∗
52
•
•
•
∗
∗
∗
•
∗
59
•
•
•
∗
∗
•
∗
67
•
•
•
∗
∗
∗
•
∗
•
∗
∗
∗
•
∗
∗
∗
•
∗
∗
∗
•1
∗
∗1
∗
•1
∗
∗1
∗
•1
∗
∗1
∗
98
•
•
∗
∗
∗
120
•
•
∗
∗
∗
380
•
•
∗
∗
∗
∗
•1
∗
∗
∗
∗
•1
∗
∗
∗
∗
•1
∗
∗
GeoSource DualTEK† Forced Air/Hydronic Models
Model Suffix
Gxxx0-x-Dxxx
Gxxx1-x-Dxxx
Gxxxx-1-Dxxx
Gxxxx-2-Dxxx
GVxxx-x-D0xx
GHxxx-x-D0xx
GHxxx-x-DCxx
Gxxxx-x-DxVx
Gxxxx-x-DxMx
Gxxxx-x-DxBx
Gxxxx-x-Dxx0
Gxxxx-x-DxxN
Gxxxx-x-DxxP
Gxxxx-x-DxxV
Description
Standard, No Desuperheater
Desuperheater
Standard, 208/230-1, 60 Hz
208/230-3, 60 Hz
Standard, Vertical Left Side Air Return
Standard, Horizontal End Right Discharge
Horizontal, Front Right Discharge
Variable Speed ECM Blower
Water Modulating Valve
Var. Speed Blower W/ Water Mod. Valve
Standard Earth Loop Coil
Cupro-Nickel Well Water Coil
Cupro-Nickel Hydronic Coil
Cupro-Nickel Well Water and Hydronic Coil
36
∗
∗
•
∗
•
•
∗
*
*
*
•
∗
∗
∗
52
∗
•
•
∗
•
•
∗
*
*
*
•1
∗
∗1
∗
59
∗
•
•
∗
•
•
∗
*
*
*
•1
∗
∗1
∗
67
∗
•
•
∗
•
•
∗
*
*
*
•1
∗
∗1
∗
GeoSource 2000 Domestic Water Heater Model
Model Suffix
GDxx0-x-T000
GDxx0-1-T000
GDxx0-2-T000
GDxx0-3-T000
Description
Standard, No Desuperheater
Standard, 208/230-1, 60 Hz
208/230-3, 60 Hz
460-3, 60 Hz
36
•
•
∗
∗
59
•
•
∗
∗
GeoSource Ultra Hydronic Models
Model Suffix
GWxx0-x-Uxxx
GWxx1-x-Uxxx
GWxxx-1-Uxxx
GWxxx-x-Ux0x
GWxxx-x-UxHx
GWxxx-x-Uxx0
GWxxx-x-UxxN
GWxxx-x-UxxP
GWxxx-x-UxxV
1
Description
Standard, No Desuperheater
Desuperheater
Standard, 208/230-1, 60 Hz
Standard Hydronic
Heat Only Hydronic
Standard Earth Loop Coil
Cupro-Nickel Well Water Coil
Cupro-Nickel Hydronic Coil
Cupro-Nickel Well Water and Hydronic Coil
37
•
•
∗
∗
∗
•
∗
∗
∗
47
•
•
∗
∗
∗
•1
∗
∗
∗
57
•
•
∗
∗
∗
•1
∗
∗
∗
77
•
•
∗
∗
∗
•1
∗
∗
∗
Brazed Plate Earth Loop Heat Exchanger
• Standard
∗ Special Order
5
Performance Data, Forced Air Models – GeoSource 2000, GeoSource
DualTEK†, GeoSource Vara
GV/GH/GC 180/181 @ 625 cfm
EWT GPM
3
15
4
5
3
20
4
5
3
25
4
5
3
30
4
5
3
35
4
5
2
45
2
4
2
50
2
4
2
60
2
4
2
70
2
4
dP
ft
2
2
3
2
2
3
2
2
3
2
2
3
2
2
3
2
2
2
2
2
2
2
2
2
2
2
2
HEATING @ 70oF DB
dP
SUCT
psi MBTU/hr KW COP PRESS
0.9
10.7
1.2
2.6
25-31
0.9
11.0
1.2
2.7
25-31
1.3
11.3
1.2
2.7
26-32
0.9
12.3
1.3
2.9
29-35
0.9
12.6
1.3
2.9
29-35
1.3
13.0
1.3
3.0
30-36
0.9
14.6
1.3
3.2
33-39
0.9
14.9
1.4
3.2
33-39
1.3
15.4
1.4
3.3
34-40
0.9
15.6
1.4
3.3
37-43
0.9
16.1
1.4
3.4
37-43
1.3
16.5
1.4
3.4
38-44
0.9
16.4
1.4
3.4
41-47
0.9
16.8
1.4
3.5
41-47
1.3
17.3
1.4
3.5
42-48
0.9
17.3
1.4
3.5
48-54
0.9
17.3
1.4
3.5
48-54
0.9
19.3
1.5
3.8
49-55
0.9
18.3
1.5
3.6
51-57
0.9
18.3
1.5
3.6
51-57
0.9
19.9
1.5
3.8
52-58
0.9
20.8
1.6
3.9
59-65
0.9
20.8
1.6
3.9
59-65
0.9
21.9
1.6
4.0
60-66
0.9
21.7
1.6
4.0
67-73
0.9
21.7
1.6
4.0
67-73
0.9
24.3
1.7
4.2
68-74
HEAD
PRESS EWT GPM
170-180
2
175-185
40
2
180-190
4
175-185
2
180-190
50
2
185-195
4
185-195
2
185-195
60
2
190-200
4
190-200
2
190-200
70
2
195-205
4
195-205
3
195-205
75
4
200-210
5
215-225
3
215-225
80
4
215-225
5
220-230
3
220-230
85
4
220-230
5
230-240
3
230-240
90
4
230-240
5
240-250
3
240-250
95
4
245-255
5
dP
ft
2
2
2
2
2
2
2
2
2
2
2
2
2
2
3
2
2
3
2
2
3
2
2
3
2
2
3
COOLING @ 80oF DB/67oF WB
dP
psi MBTU/hr KW EER
0.9
19.3
1.1
18.1
0.9
19.3
1.1
18.1
0.9
19.6
1.0
19.8
0.9
18.7
1.1
17.0
0.9
18.7
1.1
17.0
0.9
19.1
1.0
18.7
0.9
18.5
1.2
15.8
0.9
18.5
1.2
15.8
0.9
18.8
1.1
17.4
0.9
18.4
1.3
14.7
0.9
18.4
1.3
14.7
0.9
18.8
1.2
16.0
0.9
16.5
1.2
14.0
0.9
16.8
1.2
14.1
1.3
17.2
1.2
14.3
0.9
16.1
1.2
13.4
0.9
16.4
1.2
13.6
1.3
16.8
1.2
13.7
0.9
15.6
1.2
12.8
0.9
16.0
1.2
13.0
1.3
16.3
1.2
13.1
0.9
15.2
1.2
12.3
0.9
15.5
1.2
12.4
1.3
15.8
1.3
12.5
0.9
14.7
1.3
11.7
0.9
15.0
1.3
11.9
1.3
15.3
1.3
12.0
SUCT
PRESS
52-58
52-58
51-57
54-60
54-60
53-59
57-63
57-63
56-62
59-65
59-65
58-64
59-65
59-65
58-64
60-66
60-66
59-65
62-68
62-68
61-67
63-69
63-69
62-68
65-71
65-71
64-70
HEAD
PRESS
125-135
125-135
120-130
135-145
135-145
130-120
150-160
150-160
145-155
165-175
165-175
160-170
165-175
165-175
160-170
170-180
170-180
165-175
180-190
180-190
175-185
185-195
185-195
180-190
190-200
190-200
185-195
HEAD
PRESS EWT GPM
175-185
2
180-190
40
3
185-195
6
180-190
2
185-195
50
3
190-200
6
185-195
2
190-200
60
3
195-205
6
190-200
2
195-205
70
3
200-210
6
195-205
5
200-210
75
6
205-215
7
210-220
5
210-220
80
6
215-225
7
215-225
5
215-225
85
6
220-230
7
220-230
5
220-230
90
6
225-235
7
225-235
5
225-235
95
6
230-240
7
dP
ft
2
2
7
2
2
7
2
2
7
2
2
7
5
7
9
5
7
9
5
7
9
5
7
9
5
7
9
COOLING @ 80oF DB/67oF WB
dP
psi MBTU/hr KW EER
0.9
24.8
1.3
19.2
0.9
25.3
1.3
19.4
3.0
25.8
1.2
21.2
0.9
24.7
1.4
18.0
0.9
25.2
1.4
18.2
3.0
25.7
1.3
21.1
0.9
25.1
1.5
16.9
0.9
25.6
1.5
17.2
3.0
26.1
1.4
18.9
0.9
25.7
1.7
15.4
0.9
26.2
1.7
15.6
3.0
26.7
1.6
17.1
2.2
24.3
1.6
15.5
3.0
24.8
1.6
15.7
3.9
25.3
1.6
15.8
2.2
24.2
1.6
15.1
3.0
24.7
1.6
15.2
3.9
25.2
1.6
15.4
2.2
24.2
1.6
14.7
3.0
24.7
1.7
14.8
3.9
25.1
1.7
15.0
2.2
24.1
1.7
14.3
3.0
24.6
1.7
14.4
3.9
25.1
1.7
14.6
2.2
24.0
1.7
13.9
3.0
24.5
1.7
14.0
3.9
25.0
1.8
14.2
SUCT
PRESS
52-58
52-58
51-57
54-60
54-60
53-59
57-63
57-63
56-62
59-65
59-65
58-64
59-65
59-65
58-64
60-66
60-66
59-65
62-68
62-68
61-67
64-70
64-70
63-69
66-72
66-72
65-71
HEAD
PRESS
120-130
120-130
115-125
135-145
135-145
130-140
150-160
150-160
145-155
165-175
165-175
160-170
170-180
165-175
165-175
175-185
170-180
170-180
185-195
180-190
180-190
190-200
185-195
185-195
200-210
195-205
195-205
GV/GH/GC 230/231 @ 750 cfm
EWT GPM
5
15
6
7
5
20
6
7
5
25
6
7
5
30
6
7
5
35
6
7
3
45
4
6
2
50
3
6
2
60
3
6
2
70
3
6
6
dP
ft
5
7
9
5
7
9
5
7
9
5
7
9
5
7
9
2
3
7
2
2
7
2
2
7
2
2
7
HEATING @ 70oF DB
dP
SUCT
psi MBTU/hr KW COP PRESS
2.2
14.7
1.5
2.8
26-32
3.0
15.1
1.6
2.8
27-33
3.9
15.5
1.6
2.9
28-34
2.2
16.4
1.6
3.0
30-36
3.0
16.9
1.6
3.1
31-37
3.9
17.4
1.6
3.1
32-38
2.2
19.0
1.7
3.3
34-40
3.0
19.5
1.7
3.3
35-41
3.9
20.0
1.7
3.4
36-42
2.2
20.2
1.7
3.4
38-44
3.0
20.7
1.7
3.5
39-45
3.9
21.3
1.8
3.5
40-46
2.2
21.0
1.7
3.5
42-48
3.0
21.5
1.8
3.6
43-49
3.9
22.2
1.8
3.6
44-50
0.9
22.0
1.8
3.6
49-55
1.5
22.6
1.8
3.7
50-56
3.0
23.7
1.8
3.9
51-57
0.9
22.6
1.8
3.6
52-58
0.9
23.2
1.9
3.7
53-59
3.0
25.3
1.9
3.9
55-61
0.9
24.2
1.9
3.8
60-66
0.9
24.8
1.9
3.9
61-67
3.0
26.8
1.9
4.1
62-68
0.9
25.8
1.9
4.0
68-74
0.9
26.4
1.9
4.1
68-74
3.0
27.9
1.9
4.3
69-75
GV/GH/GC 290/291 @ 1050 cfm
EWT GPM
6
15
7
8
6
20
7
8
6
25
7
8
6
30
7
8
6
35
7
8
4
45
5
7
3
50
4
7
3
60
4
7
3
70
4
7
dP
ft
8
9
12
8
9
12
8
9
12
8
9
12
8
9
12
3
5
9
2
3
9
2
3
9
2
3
9
HEATING @ 70oF DB
dP
SUCT
psi MBTU/hr KW COP PRESS
3.5
19.4
1.9
3.0
24-30
3.9
19.9
1.9
3.1
25-31
5.2
20.5
1.9
3.1
26-32
3.5
21.1
2.0
3.2
28-34
3.9
21.6
2.0
3.2
29-35
5.2
22.3
2.0
3.2
30-36
3.5
22.6
2.0
3.3
32-38
3.9
23.1
2.0
3.4
33-39
5.2
23.8
2.0
3.4
34-40
3.5
24.4
2.1
3.4
36-42
3.9
25.0
2.1
3.4
37-43
5.2
25.8
2.1
3.5
38-44
3.5
25.8
2.1
3.5
40-46
3.9
26.4
2.2
3.5
41-47
5.2
27.2
2.2
3.6
42-48
1.5
27.3
2.2
3.6
48-54
2.2
28.0
2.2
3.7
48-54
3.9
29.0
2.2
3.9
49-55
0.9
28.9
2.3
3.7
51-57
1.5
29.6
2.3
3.8
52-58
3.9
31.2
2.3
4.0
53-59
0.9
31.9
2.4
4.0
59-65
1.5
32.7
2.4
4.0
60-66
3.9
35.3
2.4
4.3
61-67
0.9
35.0
2.4
4.2
67-73
1.5
35.8
2.5
4.3
68-74
3.9
37.2
2.5
4.4
69-75
dP
ft
11
13
15
11
13
15
11
13
15
11
13
15
11
13
15
3
4
13
2
3
13
2
3
13
2
3
13
HEATING @ 70oF DB
dP
SUCT
psi MBTU/hr KW COP PRESS
4.7
22.5
2.3
2.9
27-33
5.5
23.0
2.3
2.9
28-34
6.5
23.7
2.4
3.0
29-35
4.7
25.0
2.4
3.1
33-39
5.5
25.7
2.4
3.1
33-39
6.5
26.5
2.5
3.1
34-40
4.7
27.6
2.5
3.2
35-41
5.5
28.3
2.5
3.3
35-41
6.5
29.2
2.6
3.3
36-42
4.7
30.2
2.6
3.4
38-44
5.5
30.9
2.7
3.4
39-45
6.5
31.9
2.7
3.5
40-46
4.7
32.0
2.7
3.5
42-48
5.5
32.8
2.7
3.5
43-49
6.5
33.8
2.8
3.6
44-50
1.3
34.1
2.8
3.6
50-56
1.7
34.9
2.8
3.6
50-56
5.5
36.3
2.8
3.8
51-57
0.9
35.9
2.9
3.7
53-59
1.3
36.8
2.9
3.7
54-60
5.5
39.6
2.9
4.0
55-61
0.9
39.9
3.0
3.9
61-67
1.3
40.9
3.0
4.0
61-67
5.5
44.4
3.1
4.2
63-69
0.9
43.8
3.1
4.2
67-73
1.3
45.0
3.1
4.2
68-74
5.5
48.0
3.2
4.4
70-76
HEAD
PRESS EWT GPM
180-190
3
185-195
40
4
190-200
7
185-195
3
190-200
50
4
195-205
7
190-200
3
195-205
60
4
200-210
7
195-205
3
200-210
70
4
205-215
7
200-210
6
205-215
75
7
210-220
8
215-225
6
220-230
80
7
225-235
8
220-230
6
225-235
85
7
230-240
8
230-240
6
235-245
90
7
240-250
8
245-255
6
250-260
95
7
255-265
8
dP
ft
2
3
9
2
3
9
2
3
9
2
3
9
8
9
12
8
9
12
8
9
12
8
9
12
8
9
12
COOLING @ 80oF DB/67oF WB
dP
psi MBTU/hr KW EER
0.9
29.8
1.7
17.8
1.5
30.4
1.7
18.0
3.9
31.0
1.6
19.9
0.9
29.6
1.7
16.9
1.5
30.0
1.8
17.0
3.9
30.6
1.6
18.7
0.9
28.9
1.8
15.9
1.5
29.5
1.8
16.1
3.9
30.1
1.7
17.9
0.9
28.4
1.9
15.1
1.5
29.8
1.9
15.2
3.9
29.5
1.8
16.8
3.5
28.1
1.9
14.7
3.9
28.7
1.9
14.8
5.2
29.3
2.0
15.0
3.5
27.8
2.0
14.3
3.9
28.4
2.0
14.4
5.2
29.0
2.0
14.6
3.5
27.5
2.0
13.9
3.9
28.1
2.0
14.0
5.2
28.6
2.0
14.1
3.5
27.2
2.0
13.5
3.9
27.8
2.0
13.6
5.2
28.3
2.1
13.7
3.5
26.9
2.1
13.1
3.9
27.4
2.1
13.2
5.2
28.0
2.1
13.3
SUCT
PRESS
52-58
52-58
51-59
55-61
55-61
54-60
58-64
58-64
57-63
60-66
60-66
59-65
60-66
60-66
59-65
61-67
61-67
60-66
63-69
63-69
62-68
65-71
65-71
64-70
66-72
66-72
65-71
HEAD
PRESS
125-135
125-135
120-130
135-145
135-145
130-140
150-160
150-160
145-155
170-180
170-180
165-175
170-180
170-180
165-175
175-185
175-185
170-180
185-195
185-195
180-190
190-200
190-200
185-195
195-205
195-205
190-200
GV/GH/GC 360/361 @ 1100 cfm
EWT GPM
7
15
8
9
7
20
8
9
7
25
8
9
7
30
8
9
7
35
8
9
4
45
5
8
3
50
4
8
3
60
4
8
3
70
4
8
HEAD
PRESS EWT GPM
185-195
3
190-200
40
4
195-205
8
190-200
3
195-205
50
4
200-210
8
195-205
3
200-210
60
4
205-215
8
200-210
3
205-215
70
4
210-220
8
210-220
7
215-225
75
8
215-225
9
230-240
7
230-240
80
8
235-245
9
230-240
7
235-245
85
8
240-250
9
240-250
7
245-255
90
8
250-260
9
250-260
7
255-265
95
8
260-270
9
dP
ft
2
3
13
2
3
13
2
3
13
2
3
13
11
13
15
11
13
15
11
13
15
11
13
15
11
13
15
COOLING @ 80oF DB/67oF WB
dP
psi MBTU/hr KW EER
0.9
36.0
1.7
21.2
1.3
36.7
1.7
21.4
5.5
37.5
1.6
23.1
0.9
35.7
1.9
19.0
1.3
36.4
1.9
19.2
5.5
37.1
1.8
21.0
0.9
35.2
2.1
17.1
1.3
36.0
2.1
17.2
5.5
36.7
1.9
19.1
0.9
34.8
2.2
15.5
1.3
35.8
2.3
15.6
5.5
36.2
2.1
17.2
4.7
34.6
2.3
14.8
5.5
35.3
2.4
14.9
6.5
36.0
2.4
15.1
4.7
34.3
2.4
14.1
5.5
35.0
2.5
14.3
6.5
35.7
2.5
14.4
4.7
34.1
2.5
13.5
5.5
34.8
2.5
13.6
6.5
35.5
2.6
13.8
4.7
33.8
2.6
12.9
5.5
34.5
2.6
13.1
6.5
35.2
2.7
13.2
4.7
33.5
2.7
12.4
5.5
34.2
2.7
12.5
6.5
34.9
2.8
12.6
SUCT
PRESS
49-55
49-55
48-54
52-58
52-58
51-57
55-61
55-61
54-60
57-63
57-63
56-62
57-63
57-63
56-62
58-64
58-64
57-63
60-66
60-66
59-65
62-68
62-68
61-67
64-70
64-70
63-69
HEAD
PRESS
125-135
120-130
115-125
135-145
130-140
125-135
155-165
150-160
145-155
175-185
170-180
165-175
175-185
175-185
170-180
180-190
180-190
175-185
190-200
190-200
185-195
200-210
200-210
195-205
215-225
215-225
210-220
7
GV/GH/GC 420/421 @ 1150 cfm
EWT GPM
9
15
10
11
9
20
10
11
9
25
10
11
9
30
10
11
9
35
10
11
5
45
6
10
4
50
5
10
4
60
5
10
4
70
5
10
dP
ft
14
18
23
14
18
23
14
18
23
14
18
23
14
18
23
4
6
18
3
4
18
3
4
18
3
4
18
HEATING @ 70oF DB
dP
SUCT
psi MBTU/hr KW COP PRESS
6.0
26.2
2.6
3.0
25-31
7.8
26.9
2.6
3.0
26-32
10.0
27.7
2.6
3.1
26-32
6.0
29.3
2.7
3.2
29-35
7.8
30.0
2.7
3.2
30-36
10.0
30.9
2.7
3.3
30-36
6.0
32.3
2.8
3.4
33-39
7.8
33.1
2.8
3.4
34-40
10.0
34.1
2.9
3.5
34-40
6.0
35.3
2.9
3.6
37-43
7.8
36.2
3.0
3.6
38-44
10.0
37.3
3.0
3.7
38-44
6.0
37.5
3.0
3.6
40-46
7.8
38.5
3.1
3.7
41-47
10.0
39.7
3.1
3.7
42-48
1.7
39.6
3.1
3.7
48-54
2.8
41.4
3.2
3.8
48-54
7.8
43.6
3.2
4.0
49-55
1.3
42.4
3.4
3.7
51-57
1.7
43.5
3.4
3.7
52-58
7.8
47.8
3.5
4.0
53-59
1.3
45.8
3.5
3.9
57-63
1.7
47.0
3.5
3.9
58-64
7.8
51.6
3.6
4.2
60-66
1.3
49.2
3.6
4.0
63-69
1.7
50.5
3.6
4.1
64-70
7.8
53.0
3.7
4.2
66-72
HEAD
PRESS EWT GPM
195-205
4
195-205
40
5
200-210
10
200-210
4
200-210
50
5
205-215
10
205-215
4
205-215
60
5
210-220
10
210-220
4
210-220
70
5
215-225
10
215-225
9
215-225
75
10
220-230
11
235-245
9
235-245
80
10
245-255
11
240-250
9
245-255
85
10
250-260
11
250-260
9
255-265
90
10
260-270
11
260-270
9
265-275
95
10
270-280
11
dP
ft
3
4
18
3
4
18
3
4
18
3
4
18
14
18
23
14
18
23
14
18
23
14
18
23
14
18
23
COOLING @ 80oF DB/67oF WB
dP
psi MBTU/hr KW EER
1.3
38.0
1.9
20.0
1.7
38.8
1.9
20.3
7.8
39.6
1.8
22.0
1.3
37.7
2.1
18.1
1.7
38.5
2.1
18.3
7.8
39.3
2.0
20.1
1.3
37.4
2.2
17.0
1.7
38.2
2.1
17.6
7.8
39.2
2.0
19.5
1.3
37.1
2.4
15.5
1.7
37.9
2.4
15.8
7.8
39.1
2.2
17.5
6.0
38.2
2.5
15.0
7.8
39.0
2.6
15.2
10.0
39.7
2.6
15.4
6.0
38.1
2.6
14.5
7.8
38.9
2.7
14.6
10.0
39.6
2.7
14.8
6.0
37.9
2.7
13.9
7.8
38.6
2.7
14.1
10.0
39.4
2.8
14.2
6.0
37.6
2.8
13.4
7.8
38.4
2.8
13.5
10.0
39.2
2.9
13.7
6.0
37.4
2.9
12.9
7.8
38.2
2.9
13.0
10.0
38.9
3.0
13.1
SUCT
PRESS
42-48
42-48
40-46
45-51
45-51
43-49
46-52
46-52
45-51
48-54
48-54
47-53
48-54
48-54
47-53
49-55
49-55
48-54
50-56
50-56
49-55
51-57
51-57
50-56
52-58
52-58
51-57
HEAD
PRESS
130-140
125-135
120-130
140-150
135-145
130-140
155-165
150-160
145-155
175-185
170-180
160-170
175-185
170-180
170-180
185-195
180-190
180-190
195-205
190-200
190-200
205-215
200-210
200-210
215-225
210-220
210-220
SUCT
PRESS
47-53
47-53
46-52
49-55
49-55
47-53
52-58
51-57
50-56
54-60
53-59
52-58
53-59
53-59
52-58
54-60
54-60
53-59
55-61
55-61
54-60
56-62
56-62
55-61
57-63
57-63
56-62
HEAD
PRESS
120-130
120-130
115-125
135-145
130-140
125-135
155-165
155-165
150-160
180-190
175-185
170-180
175-185
175-185
170-180
185-195
180-190
175-185
195-205
190-200
190-200
205-215
200-210
200-210
215-225
210-220
210-220
GV/GH 520/521 @ 1550 cfm
EWT GPM
10
15
11
12
10
20
11
12
10
25
11
12
10
30
11
12
10
35
11
12
6
45
7
11
5
50
6
11
5
60
6
11
5
70
6
11
8
dP*
ft
10
12
15
10
12
15
10
12
15
10
12
15
10
12
15
4
6
12
3
4
12
3
4
12
3
4
12
HEATING @ 70oF DB
COOLING @ 80oF DB/67oF WB
dP*
SUCT
HEAD
dP* dP*
psi MBTU/hr KW COP PRESS PRESS EWT GPM
ft
psi MBTU/hr KW EER
4.4
31.6
3.4
2.7
26-32 190-200
5
3
1.2
52.9
2.7
19.7
5.2
32.4
3.4
2.8
27-33 195-205
40
6
4
1.6
54.0
2.7
19.9
6.4
33.4
3.5
2.8
27-33 195-205
11
12
5.2
55.1
2.5
21.7
4.4
35.2
3.6
2.9
30-36 195-205
5
3
1.2
51.5
2.9
17.9
5.2
36.1
3.6
2.9
31-37 200-210
50
6
4
1.6
52.5
2.9
18.1
6.4
37.2
3.7
3.0
31-37 205-215
11
12
5.2
53.6
2.7
20.0
4.4
38.8
3.7
3.1
34-40 205-215
5
3
1.2
47.6
2.9
16.2
5.2
39.8
3.8
3.1
35-41 205-215
60
6
4
1.6
48.6
3.0
16.4
6.4
41.0
3.8
3.1
35-41 210-220
11
12
5.2
49.6
2.8
18.0
4.4
42.4
3.9
3.2
38-44 210-220
5
3
1.2
46.6
3.1
15.0
5.2
43.5
3.9
3.2
39-45 210-220
70
6
4
1.6
47.5
3.1
15.3
6.4
44.8
4.0
3.3
39-45 215-225
11
12
5.2
48.5
2.9
16.7
4.4
45.5
4.0
3.3
41-47 215-225
10
10
4.4
46.5
3.3
14.0
5.2
46.7
4.1
3.3
42-48 215-225
75
11
11
5.2
47.4
3.4
14.1
6.4
48.1
4.1
3.4
43-49 220-230
12
12
6.4
48.4
3.4
14.2
1.6
49.3
4.2
3.4
49-55 235-245
10
10
4.4
45.3
3.4
13.2
2.4
50.2
4.2
3.5
50-56 235-245
80
11
11
5.2
46.2
3.5
13.4
5.2
54.3
4.3
3.7
52-58 245-255
12
12
6.4
47.2
3.5
13.5
1.2
53.6
4.4
3.5
52-58 240-250
10
10
4.4
44.1
3.5
12.5
1.6
55.0
4.5
3.6
53-59 240-250
85
11
11
5.2
45.0
3.5
12.7
5.2
59.6
4.6
3.8
55-61 250-260
12
12
6.4
45.9
3.6
12.8
1.2
59.0
4.6
3.8
57-63 245-255
10
10
4.4
42.8
3.6
11.0
1.6
60.5
4.6
3.8
58-64 245-255
90
11
11
5.2
43.7
3.6
12.0
5.2
65.7
4.7
4.1
61-67 255-265
12
12
6.4
44.6
3.7
12.1
1.2
64.4
4.7
4.0
64-70 255-265
10
10
4.4
41.6
3.7
11.2
1.6
66.0
4.8
4.0
65-71 255-265
95
11
11
5.2
42.4
3.7
11.4
5.2
68.8
4.8
4.2
66-72 265-275
12
12
6.4
43.3
3.8
11.5
* These pressure drops apply to standard water coils only. Cupro-nickel water coils have higher pressure drops.
GV/GH 590/591 @ 1800 cfm
EWT GPM
12
15
13
14
12
20
13
14
12
25
13
14
12
30
13
14
12
35
13
14
9
45
10
13
8
50
9
13
7
60
8
13
7
70
8
13
dP*
ft
11
14
17
11
14
17
11
14
17
11
14
17
11
14
17
7
9
14
6
7
14
5
6
14
5
6
14
HEATING @ 70oF DB
dP*
SUCT
psi MBTU/hr KW COP PRESS
4.8
40.8
4.3
2.8
25-31
6.0
41.8
4.3
2.8
26-32
7.5
43.1
4.4
2.9
26-32
4.8
44.7
4.4
3.0
29-35
6.0
45.8
4.4
3.0
30-36
7.5
47.2
4.5
3.1
31-37
4.8
48.6
4.4
3.2
33-39
6.0
49.9
4.5
3.3
34-40
7.5
51.4
4.6
3.3
35-41
4.8
52.5
4.5
3.4
38-44
6.0
53.9
4.6
3.5
38-44
7.5
55.5
4.6
3.5
39-45
4.8
55.8
4.6
3.5
42-48
6.0
57.3
4.7
3.6
42-48
7.5
59.0
4.8
3.6
43-49
3.1
61.9
4.9
3.7
49-55
3.8
62.8
4.9
3.8
50-56
6.0
65.4
4.9
3.9
51-57
2.5
66.0
5.2
3.7
52-58
3.1
68.2
5.2
3.8
53-59
6.0
74.3
5.3
4.0
55-61
2.0
70.2
5.4
3.8
60-66
2.5
72.0
5.4
3.9
60-66
6.0
76.9
5.5
4.1
62-68
2.0
76.1
5.6
4.0
67-73
2.5
78.0
5.7
4.0
67-73
6.0
85.1
5.8
4.3
70-76
HEAD
PRESS EWT GPM
190-200
8
190-200
40
9
195-205
13
200-210
8
200-210
50
9
205-215
13
205-215
7
205-215
60
8
210-220
13
210-220
7
210-220
70
8
215-225
13
215-225
12
215-225
75
13
220-230
14
240-250
12
240-250
80
13
245-255
14
240-250
12
245-255
85
13
250-260
14
255-265
12
255-265
90
13
260-270
14
265-275
12
265-275
95
13
270-280
14
dP*
ft
6
7
14
6
7
14
5
6
14
5
6
14
11
14
17
11
14
17
11
14
17
11
14
17
11
14
17
COOLING @ 80oF DB/67oF WB
dP*
psi MBTU/hr KW EER
2.5
57.2
3.1
18.5
3.1
57.6
3.0
19.2
6.0
58.3
2.8
19.4
2.5
57.0
3.5
16.3
3.1
57.4
3.4
16.8
6.0
58.1
3.2
17.1
2.0
55.8
3.5
15.5
2.5
56.8
3.6
15.8
6.0
57.8
3.3
16.5
2.0
55.6
3.7
15.0
2.5
56.6
3.7
15.3
6.0
57.7
3.4
16.0
4.8
56.3
4.4
12.9
6.0
57.5
4.4
13.0
7.5
58.6
4.5
13.1
4.8
56.0
4.6
12.2
6.0
57.3
4.6
12.5
7.5
58.4
4.7
12.5
4.8
55.8
4.8
11.6
6.0
57.1
4.8
11.9
7.5
58.1
4.9
11.9
4.8
55.6
5.0
11.1
6.0
56.9
5.0
11.4
7.5
57.9
5.1
11.4
4.8
55.4
5.1
10.8
6.0
56.6
5.2
10.9
7.5
57.7
5.3
10.9
SUCT
PRESS
43-49
43-49
42-48
47-53
46-52
45-51
51-57
50-56
49-55
53-59
52-58
51-57
53-59
53-59
52-58
55-61
55-61
54-60
56-62
56-62
55-61
57-63
57-63
56-62
58-64
58-64
57-63
HEAD
PRESS
120-130
120-130
115-125
135-145
135-145
130-140
155-165
155-165
150-160
175-185
175-185
170-180
175-185
175-185
170-180
185-195
185-195
180-190
195-205
190-200
190-200
205-215
200-210
200-210
215-225
210-220
210-220
GV/GH 670/671 @ 2150 cfm
EWT GPM
13
15
14
15
13
20
14
15
13
25
14
15
13
30
14
15
13
35
14
15
10
45
11
14
9
50
10
14
8
60
9
14
8
70
9
14
HEATING @ 70oF DB
COOLING @ 80oF DB/67oF WB
dP* dP*
SUCT
HEAD
dP* dP*
ft
psi MBTU/hr KW COP PRESS PRESS EWT GPM
ft
psi MBTU/hr KW EER
14
6.1
45.9
5.1
2.7
26-32 185-195
9
8
3.5
62.9
4.2
15.1
16
7.0
47.1
5.1
2.7
26-32 185-195
40
10
9
3.8
64.1
4.2
15.3
18
7.9
48.5
5.2
2.7
27-33 190-200
14
16
7.0
65.4
3.9
16.9
14
6.1
50.8
5.2
2.9
31-37 195-205
9
8
3.5
62.7
4.5
14.1
16
7.0
52.1
5.2
2.9
31-37 195-205
50
10
9
3.8
64.0
4.5
14.2
18
7.9
53.6
5.3
3.0
32-38 200-210
14
16
7.0
65.3
4.1
15.9
14
6.1
57.7
5.3
3.2
36-42 200-210
8
7
3.0
62.5
4.7
13.2
16
7.0
59.2
5.4
3.2
36-42 200-210
60
9
8
3.5
63.8
4.8
13.3
18
7.9
61.0
5.5
3.3
37-43 205-215
14
16
7.0
65.1
4.4
14.9
14
6.1
61.1
5.4
3.3
41-47 205-215
8
7
3.0
60.7
5.1
12.0
16
7.0
62.6
5.5
3.4
42-48 205-215
70
9
8
3.5
62.0
5.2
12.0
18
7.9
64.5
5.6
3.4
42-48 210-220
14
16
7.0
63.3
4.6
13.9
14
6.1
64.0
5.6
3.4
45-51 210-220
13
14
6.1
62.3
5.2
12.0
16
7.0
65.7
5.6
3.4
46-52 210-220
75
14
16
7.0
63.5
5.2
12.1
18
7.9
67.6
5.7
3.5
46-52 215-225
15
18
7.9
64.8
5.3
12.2
9
3.8
67.0
5.7
3.4
53-59 225-235
13
14
6.1
61.8
5.3
11.6
11
4.6
69.0
5.8
3.5
54-60 225-235
80
14
16
7.0
63.1
5.4
11.7
16
7.0
76.5
5.9
3.8
54-60 230-240
15
18
7.9
64.3
5.4
11.8
8
3.5
72.2
6.0
3.5
57-63 230-240
13
14
6.1
61.1
5.5
11.1
9
3.8
74.0
6.1
3.6
58-64 235-245
85
14
16
7.0
62.3
5.5
11.3
16
7.0
80.4
6.2
3.8
59-65 240-250
15
18
7.9
63.6
5.6
11.4
7
3.0
80.4
6.5
3.6
63-69 245-255
13
14
6.1
60.3
5.6
10.7
8
3.5
82.5
6.6
3.7
64-70 250-260
90
14
16
7.0
61.6
5.7
10.8
16
7.0
89.2
6.7
3.9
66-72 255-265
15
18
7.9
62.8
5.7
10.9
7
3.0
88.7
6.9
3.8
73-79 255-265
13
14
6.1
59.6
5.8
10.3
8
3.5
91.0
7.0
3.8
73-79 260-270
95
14
16
7.0
60.8
5.8
10.4
16
7.0
96.0
7.1
4.0
75-81 265-275
15
18
7.9
62.1
5.9
10.5
* These pressure drops apply to standard water coils only. Cupro-nickel water coils have higher pressure drops.
SUCT
PRESS
45-51
44-50
43-49
48-54
47-53
46-52
51-57
51-57
50-56
53-59
53-59
52-58
54-60
54-60
53-59
55-61
55-61
54-60
57-63
57-63
56-62
58-64
58-64
57-63
60-66
60-66
59-65
HEAD
PRESS
120-130
120-130
115-125
130-140
130-140
125-135
145-155
145-155
140-150
170-180
170-180
165-175
185-195
180-190
180-190
190-200
185-195
185-195
200-210
195-205
195-205
210-220
205-215
205-215
220-230
215-225
215-225
9
GH 980 @ 2700 cfm
EWT GPM
20
15
22
24
20
20
22
24
20
25
22
24
20
30
22
24
20
35
22
24
16
45
18
22
14
50
16
22
14
60
16
22
14
70
16
22
dP*
ft
8
9
10
8
9
10
8
9
10
8
9
10
8
9
10
7
8
9
6
7
9
6
7
9
6
7
9
HEATING @ 70oF DB
dP*
SUCT
psi MBTU/hr KW COP PRESS
3.5
70.3
7.3
2.8
24-30
3.8
72.1
7.4
2.8
25-31
4.1
74.3
7.5
2.9
26-32
3.5
75.7
7.4
3.0
30-36
3.8
77.7
7.5
3.0
31-37
4.1
80.0
7.6
3.1
32-38
3.5
83.7
7.4
3.3
34-40
3.8
85.8
7.5
3.3
35-41
4.1
88.4
7.6
3.4
36-42
3.5
87.3
7.6
3.4
38-44
3.8
89.5
7.6
3.4
39-45
4.1
92.2
7.8
3.5
40-46
3.5
90.4
7.7
3.5
41-47
3.8
92.7
7.8
3.5
42-48
4.1
95.4
7.9
3.5
43-49
3.0
95.6
7.8
3.6
47-53
3.3
97.3
7.9
3.6
48-54
3.8
103.7
8.0
3.8
49-55
2.7
98.5
8.0
3.6
50-56
3.0
101.0
8.1
3.7
51-57
3.8
108.0
8.2
3.9
52-58
2.7
107.3
8.3
3.8
56-62
3.0
110.0
8.4
3.9
57-63
3.8
118.0
8.5
4.1
58-64
2.7
116.0
8.5
4.0
61-67
3.0
119.0
8.6
4.0
62-68
3.8
125.5
8.8
4.2
63-69
HEAD
PRESS EWT GPM
195-205
14
200-210
40
16
200-210
22
200-210
14
205-215
50
16
205-215
22
205-215
14
210-220
60
16
210-220
22
210-220
14
215-225
70
16
220-230
22
220-230
20
225-235
75
22
230-240
24
230-240
20
235-245
80
22
240-250
24
235-245
20
240-250
85
22
245-255
24
245-255
20
250-260
90
22
255-265
24
255-265
20
260-270
95
22
265-275
24
dP*
ft
6
7
9
6
7
9
6
7
9
6
7
9
8
9
10
8
9
10
8
9
10
8
9
10
8
9
10
COOLING @ 80oF DB/67oF WB
dP*
psi MBTU/hr KW EER
2.7
104.5
5.6
18.7
3.0
106.6
5.7
18.9
3.8
108.8
5.3
20.5
2.7
100.0
6.0
16.6
3.0
102.0
6.1
16.8
3.8
104.0
5.6
18.6
2.7
96.9
6.2
15.6
3.0
98.7
6.3
15.7
3.8
100.6
5.7
17.6
2.7
92.5
6.6
14.1
3.0
94.0
6.6
14.2
3.8
96.0
6.0
15.6
3.5
90.9
6.9
13.2
3.8
92.7
7.0
13.2
4.1
94.6
7.0
13.5
3.5
88.8
7.1
12.6
3.8
90.6
7.1
12.7
4.1
92.4
7.2
12.8
3.5
86.5
7.2
12.0
3.8
88.3
7.3
12.1
4.1
90.1
7.4
12.2
3.5
84.3
7.4
11.4
3.8
86.0
7.5
11.5
4.1
87.7
7.5
11.6
3.5
82.0
7.6
10.8
3.8
83.7
7.7
10.9
4.1
85.3
7.7
11.0
SUCT
PRESS
44-50
43-49
42-48
46-52
46-52
45-51
48-54
48-54
47-53
50-56
50-56
49-55
51-57
51-57
50-56
52-58
52-58
51-57
53-59
53-59
52-58
54-60
54-60
53-59
55-61
55-61
54-60
HEAD
PRESS
120-130
120-130
115-125
135-145
135-145
130-140
150-160
150-160
145-155
165-175
165-175
160-170
175-185
170-180
165-175
185-195
180-190
175-185
195-205
190-200
185-195
205-215
200-210
195-205
215-225
210-220
205-215
dP*
ft
7
8
10
7
8
10
7
8
10
7
8
10
9
10
11
9
10
11
9
10
11
9
10
11
9
10
11
COOLING @ 80oF DB/67oF WB
dP*
psi MBTU/hr KW EER
3.0
123.8
6.7
18.6
3.5
126.3
6.7
18.8
4.5
128.8
6.8
20.3
3.0
123.5
7.4
16.6
3.5
126.0
7.5
16.8
4.5
128.5
7.6
18.5
3.0
119.9
8.0
15.0
3.5
121.4
8.0
15.2
4.5
123.8
8.1
16.8
3.0
114.6
8.7
13.1
3.5
117.0
8.8
13.3
4.5
119.3
8.9
14.8
4.1
108.1
8.1
13.4
4.5
110.3
8.1
13.5
4.8
112.5
8.2
13.7
4.1
105.9
8.3
12.8
4.5
108.1
8.4
12.9
4.8
110.2
8.4
13.1
4.1
104.4
8.5
12.2
4.5
106.5
8.6
12.4
4.8
108.6
8.7
12.5
4.1
102.8
8.8
11.7
4.5
104.9
8.9
11.8
4.8
107.0
9.0
11.9
4.1
101.3
9.0
11.2
4.5
103.3
9.1
11.3
4.8
105.4
9.2
11.4
SUCT
PRESS
40-46
39-45
38-44
43-49
42-48
41-47
45-51
44-50
43-49
47-53
46-52
45-51
48-54
47-53
46-52
50-56
49-55
48-54
52-58
51-57
50-56
54-60
53-59
52-58
56-62
55-61
54-60
HEAD
PRESS
120-130
115-125
110-120
135-145
130-140
125-135
150-160
145-155
140-150
165-175
160-170
155-165
170-180
165-175
160-170
180-190
175-185
170-180
195-205
190-200
185-195
205-215
200-210
195-205
215-225
210-220
205-215
GH 1200 @ 3150 cfm
EWT GPM
24
15
26
28
24
20
26
28
24
25
26
28
24
30
26
28
24
35
26
28
18
45
20
26
16
50
18
26
16
60
18
26
16
70
18
26
dP*
ft
9
10
11
9
10
11
9
10
11
9
10
11
9
10
11
8
8
10
7
8
10
7
8
10
7
8
10
HEATING @ 70oF DB
dP*
SUCT
psi MBTU/hr KW COP PRESS
4.1
81.2
8.7
2.7
23-29
4.5
83.2
8.8
2.8
24-30
4.8
85.7
8.9
2.8
25-31
4.1
87.9
8.9
2.9
27-33
4.5
90.2
9.0
2.9
28-34
4.8
92.9
9.1
3.0
29-35
4.1
95.2
8.9
3.1
31-37
4.5
97.7
9.0
3.2
32-38
4.8
100.6
9.2
3.2
33-39
4.1
101.7
9.3
3.2
35-41
4.5
104.3
9.4
3.3
36-42
4.8
107.5
9.5
3.3
37-43
4.1
107.3
9.6
3.3
39-45
4.5
110.0
9.7
3.3
40-46
4.8
113.3
9.8
3.4
41-47
3.3
115.0
9.8
3.4
46-52
3.5
118.5
9.9
3.5
47-53
4.5
127.0
10.1
3.7
48-54
3.0
121.9
10.4
3.4
50-56
3.3
125.0
10.5
3.5
51-57
4.5
134.0
10.7
3.7
52-58
3.0
133.6
10.8
3.6
57-63
3.3
137.0
10.9
3.7
58-64
4.5
147.7
11.1
3.9
59-65
3.0
145.3
11.1
3.8
64-70
3.5
149.0
11.3
3.9
65-71
4.5
155.6
11.4
4.0
66-72
HEAD
PRESS EWT GPM
195-205
16
200-210
40
18
205-215
26
200-210
16
205-215
50
18
210-220
26
205-215
16
210-220
60
18
215-225
26
215-225
16
220-230
70
18
225-235
26
225-235
24
230-240
75
26
235-245
28
235-245
24
240-250
80
26
245-255
28
245-255
24
250-260
85
26
255-265
28
260-270
24
265-275
90
26
270-280
28
275-285
24
280-290
95
26
285-295
28
* These pressure drops apply to standard water coils only. Cupro-nickel water coils have higher pressure drops.
10
Preliminary Performance Data, Forced Air Models – GeoSource Vara 2 Plus
GV/GH 380/381
Loop
EWT
15
20
25
30
35
45
50
60
70
Loop
EWT
40
50
60
70
75
80
85
90
95
Loop
GPM
7
8
9
7
8
9
7
8
9
7
8
9
7
8
9
4
5
8
4
5
8
4
5
8
4
5
8
Loop
GPM
4
5
8
4
5
8
4
5
8
4
5
8
7
8
9
7
8
9
7
8
9
7
8
9
7
8
9
dP
ft
5.5
6.5
8.3
5.5
6.5
8.3
5.5
6.5
8.3
5.5
6.5
8.3
5.5
6.5
8.3
1.8
2.8
6.5
1.8
2.8
6.5
1.8
2.8
6.5
1.8
2.8
6.5
dP
ft
1.8
2.8
6.5
1.8
2.8
6.5
1.8
2.8
6.5
1.8
2.8
6.5
5.5
6.5
8.3
5.5
6.5
8.3
5.5
6.5
8.3
5.5
6.5
8.3
5.5
6.5
8.3
dP
psi
2.4
2.8
3.6
2.4
2.8
3.6
2.4
2.8
3.6
2.4
2.8
3.6
2.4
2.8
3.6
0.8
1.2
2.8
0.8
1.2
2.8
0.8
1.2
2.8
0.8
1.2
2.8
dP
psi
0.8
1.2
2.8
0.8
1.2
2.8
0.8
1.2
2.8
0.8
1.2
2.8
2.4
2.8
3.6
2.4
2.8
3.6
2.4
2.8
3.6
2.4
2.8
3.6
2.4
2.8
3.6
MBTU/hr
14.9
16.3
17.2
17.5
18.7
19.2
18.8
19.1
20.1
21.0
21.5
22.6
21.8
22.4
23.1
23.9
24.1
26.5
24.8
25.0
27.9
27.2
27.7
30.5
30.9
31.4
34.6
Heating @ 68oF EAT
First Stage @ 910 cfm
Suct
Head
KW
COP
Press
Press
1.3
3.4
60-70
245-265
1.4
3.5
61-71
245-265
1.4
3.6
62-72
250-270
1.4
3.6
67-77
255-275
1.5
3.7
68-88
255-275
1.5
3.8
70-80
260-280
1.4
3.9
77-87
265-285
1.4
4.0
78-88
265-285
1.5
4.0
79-89
270-290
1.5
4.1
84-94
270-290
1.5
4.2
85-95
275-295
1.6
4.2
88-98
275-295
1.5
4.3
94-104
280-300
1.5
4.3
96-106
285-305
1.6
4.3
98-108
285-305
1.6
4.4
105-115 285-305
1.6
4.4
108-118 290-310
1.7
4.5
117-127 300-320
1.6
4.5
119-129 295-315
1.6
4.6
122-132 300-320
1.7
4.8
127-137 310-330
1.7
4.7
133-143 310-330
1.7
4.8
137-147 315-335
1.8
5.0
142-152 330-350
1.8
5.0
161-171 330-350
1.8
5.1
164-174 335-355
1.9
5.3
170-180 350-370
MBTU/hr
32.1
32.5
33.2
31.6
31.9
32.5
30.9
31.2
31.8
29.7
30.1
31.0
28.6
29.1
29.9
27.5
28.2
28.7
26.4
27.0
27.6
25.9
26.5
27.1
25.2
25.8
26.3
COOLING @ 80oF DB/67oF WB
First Stage @ 910 cfm
Suct
Head
KW
EER
Press
Press
1.0
31.7
122-132 185-205
1.0
32.3
121-131 180-200
0.9
34.8
119-129 175-195
1.1
28.4
126-136 210-230
1.1
29.1
125-135 205-225
1.0
31.3
123-133 200-220
1.2
25.6
130-140 230-250
1.2
26.5
129-139 225-245
1.1
28.5
127-137 220-240
1.3
22.9
124-144 250-270
1.3
23.2
133-143 245-265
1.2
24.9
131-141 240-260
1.3
21.8
134-144 255-275
1.3
22.5
133-143 250-270
1.3
23.1
132-142 245-265
1.4
19.4
136-146 270-290
1.4
19.9
135-145 265-285
1.5
20.1
134-144 260-280
1.5
17.2
138-148 280-300
1.5
17.7
137-147 275-295
1.6
17.9
136-146 270-290
1.6
15.8
140-150 290-310
1.6
16.2
139-149 285-305
1.7
16.4
138-148 280-300
1.7
14.5
142-152 305-325
1.7
14.7
141-151 300-320
1.8
14.9
140-150 295-315
MBTU/hr
21.6
22.1
22.9
24.0
24.7
25.5
26.8
27.2
28.3
28.7
29.8
30.6
30.4
31.1
32.5
31.4
32.1
36.3
34.5
35.3
39.9
38.0
38.9
43.8
42.1
43.0
47.7
Second Stage @ 1180 cfm
Suct
KW
COP
Press
1.9
3.3
55-65
1.9
3.4
56-66
2.0
3.4
57-67
2.0
3.5
61-71
2.0
3.6
62-72
2.1
3.6
63-73
2.1
3.7
67-77
2.1
3.8
69-79
2.2
3.8
70-80
2.2
3.8
75-85
2.2
3.9
76-86
2.3
3.9
77-87
2.3
3.9
80-90
2.3
4.0
81-91
2.4
4.0
82-92
2.3
4.0
94-104
2.3
4.1
95-105
2.5
4.3
100-110
2.4
4.2
103-113
2.4
4.3
105-115
2.6
4.5
110-120
2.6
4.3
127-137
2.6
4.4
130-140
2.8
4.6
135-145
2.8
4.4
147-157
2.8
4.5
150-160
3.0
4.7
155-165
Head
Press
265-285
270-290
270-290
270-290
275-295
275-295
280-300
285-305
285-305
290-310
295-315
295-315
300-320
300-320
305-325
305-325
310-330
320-340
315-335
320-340
330-350
335-355
340-360
350-370
355-375
360-380
370-390
MBTU/hr
39.6
40.2
41.3
38.2
38.9
40.1
37.0
37.5
38.7
36.3
36.8
37.9
36.5
37.1
37.6
38.0
38.5
39.2
38.7
39.4
40.3
39.5
40.1
40.8
40.2
40.9
41.7
Second Stage @ 1180 cfm
Suct
KW
EER
Press
1.7
23.1
111-121
1.7
23.9
110-120
1.6
25.5
108-118
1.9
19.9
115-125
1.9
20.6
114-124
1.8
22.3
112-122
2.1
17.4
120-130
2.1
17.8
119-129
2.0
19.2
117-127
2.3
15.5
123-133
2.3
16.0
122-132
2.2
17.1
120-130
2.3
15.5
123-133
2.3
16.1
122-132
2.4
16.3
121-131
2.4
15.6
125-135
124-134
2.4
16.0
2.5
16.2
123-133
2.5
15.3
127-137
126-136
2.5
15.6
2.6
15.9
125-135
2.6
14.8
129-139
128-138
2.6
15.2
2.7
15.4
127-137
2.8
14.1
131-141
130-140
2.8
14.5
2.9
14.7
129-139
Head
Press
220-240
215-235
205-225
245-265
240-260
230-250
265-285
260-280
250-270
285-305
280-300
270-290
290-310
285-305
280-300
300-320
295-315
290-310
310-330
305-325
300-320
320-340
315-335
310-330
330-350
325-345
320-340
11
GV/GH 480/481
Loop
EWT
15
20
25
30
35
45
50
60
70
Loop
EWT
40
50
60
70
75
80
85
90
95
12
Loop
GPM
10
11
12
10
11
12
10
11
12
10
11
12
10
11
12
6
7
11
5
6
11
5
6
11
5
6
11
Loop
GPM
5
6
11
5
6
11
5
6
11
5
6
11
10
11
12
10
11
12
10
11
12
10
11
12
10
11
12
dP
ft
10
12
15
10
12
15
10
12
15
10
12
15
10
12
15
4
6
12
3
4
12
3
4
12
3
4
12
dP
ft
3
4
12
3
4
12
3
4
12
3
4
12
10
12
15
10
12
15
10
12
15
10
12
15
10
12
15
dP
psi
4.4
5.2
6.4
4.4
5.2
6.4
4.4
5.2
6.4
4.4
5.2
6.4
4.4
5.2
6.4
1.6
2.4
5.2
1.2
1.6
5.2
1.2
1.6
5.2
1.2
1.6
5.2
dP
psi
1.2
1.6
5.2
1.2
1.6
5.2
1.2
1.6
5.2
1.2
1.6
5.2
4.4
5.2
6.4
4.4
5.2
6.4
4.4
5.2
6.4
4.4
5.2
6.4
4.4
5.2
6.4
MBTU/hr
19.8
21.5
22.1
22.4
24.0
24.3
24.4
25.5
26.3
27.0
28.3
29.0
29.8
31.5
31.9
33.0
34.4
37.4
35.2
36.0
39.1
39.2
40.1
43.8
43.5
44.4
47.7
Heating @ 68oF EAT
First Stage @ 1295 cfm
Suct
Head
KW
COP
Press
Press
2.0
2.9
55-65
250-270
2.1
3.0
57-67
255-275
2.1
3.1
59-69
260-280
2.1
3.1
63-73
260-280
2.2
3.2
65-75
265-285
2.2
3.3
67-77
270-290
2.1
3.4
70-80
275-295
2.2
3.4
72-82
280-300
2.2
3.5
73-83
285-305
2.2
3.6
78-88
290-310
2.3
3.6
79-89
295-305
2.3
3.7
80-90
300-320
2.3
3.8
89-99
300-320
2.4
3.8
90-100
305-325
2.4
3.9
91-101
310-330
2.3
4.2
104-114 315-335
2.4
4.2
106-116 320-340
2.5
4.4
110-120 330-350
2.4
4.3
109-119 325-345
2.4
4.4
111-121 330-350
2.5
4.6
118-128 340-360
2.5
4.6
128-138 345-365
2.5
4.7
129-139 350-370
2.6
4.9
137-147 365-385
2.6
4.9
147-157 375-395
2.6
5.0
149-159 380-400
2.7
5.2
155-165 390-410
MBTU/hr
40.9
41.5
42.2
39.4
40.1
41.3
39.1
39.8
40.9
38.4
38.8
39.7
37.1
37.7
38.6
36.3
37.4
38.2
35.5
36.2
37.2
35.3
36.1
37.0
33.2
34.1
34.9
COOLING @ 80oF DB/67oF WB
First Stage @ 1295 cfm
Suct
Head
KW
EER
Press
Press
1.6
25.9
118-128 190-210
1.6
26.2
117-127 185-205
1.5
28.1
114-124 175-195
1.7
23.8
122-132 215-235
1.7
24.2
121-131 210-230
1.6
25.8
118-128 200-220
1.7
22.7
125-135 245-265
1.7
23.4
124-134 240-260
1.7
24.1
122-132 230-250
2.0
19.5
129-139 275-295
2.0
19.8
128-138 270-290
2.0
20.3
126-136 260-280
2.1
17.7
129-139 275-295
2.1
18.0
128-138 270-290
2.2
18.1
127-137 265-285
2.2
16.5
131-141 285-305
2.2
17.0
130-140 280-300
2.3
17.1
129-139 275-295
2.3
15.0
134-144 300-320
2.4
15.1
133-143 295-315
2.5
15.2
132-142 290-310
2.5
14.1
137-147 310-330
2.5
14.4
136-146 305-325
2.6
14.5
135-145 300-320
2.7
12.3
139-149 325-345
2.7
12.6
138-148 320-340
2.8
12.7
137-147 315-335
MBTU/hr
28.6
29.7
30.7
32.8
33.8
34.9
36.0
37.1
37.7
38.3
40.8
41.1
41.6
42.1
43.0
46.4
47.8
51.5
48.1
50.2
53.9
53.8
54.4
59.3
57.2
58.5
62.6
Second Stage @ 1680 cfm
Suct
KW
COP
Press
2.9
2.9
49-59
2.9
3.0
51-61
3.0
3.0
52-62
3.1
3.1
58-68
3.1
3.2
60-70
3.2
3.2
61-71
3.2
3.3
65-75
3.2
3.4
67-77
3.3
3.4
68-78
3.3
3.4
74-84
3.3
3.5
75-85
3.4
3.5
76-86
3.4
3.5
81-91
3.4
3.6
82-92
3.5
3.6
83-93
3.4
4.0
93-103
3.5
4.0
95-105
3.6
4.2
100-110
3.4
4.1
101-111
3.5
4.2
103-113
3.7
4.3
107-117
3.7
4.3
118-128
3.7
4.3
120-130
3.9
4.4
125-135
3.9
4.3
134-144
3.9
4.4
136-146
4.1
4.5
140-150
Head
Press
270-290
275-295
280-300
285-305
290-310
295-315
300-320
305-325
310-330
310-330
315-335
320-340
320-340
325-345
330-350
335-355
340-360
350-370
345-365
350-370
360-380
365-385
370-390
380-400
385-405
390-410
400-420
MBTU/hr
49.0
49.8
53.1
48.9
49.7
51.8
48.6
49.2
51.6
47.7
48.1
49.3
45.9
48.8
50.5
45.2
47.1
49.6
45.0
46.6
48.5
44.8
45.9
47.5
44.1
45.3
47.2
Second Stage @ 1680 cfm
Suct
KW
EER
Press
2.5
19.6
102-112
2.5
19.9
101-111
2.4
22.1
99-109
2.7
18.1
105-115
2.7
18.4
104-114
2.6
19.9
102-112
3.0
16.2
110-120
3.0
16.4
109-119
2.9
17.8
107-117
3.3
14.5
113-123
3.3
14.6
112-122
3.2
15.4
110-120
3.3
13.9
113-123
3.3
14.8
112-122
3.4
15.1
111-121
3.4
13.2
115-125
114-124
3.4
13.8
3.5
14.2
113-123
3.6
12.5
117-127
116-126
3.6
12.9
3.7
13.1
115-125
3.7
12.1
119-129
118-128
3.7
12.4
3.8
12.5
117-127
3.9
11.3
121-131
120-130
3.9
11.6
4.0
11.8
119-129
Head
Press
225-245
220-240
210-230
245-265
240-260
230-250
280-300
275-295
265-285
310-330
305-325
295-315
310-330
305-325
300-320
320-340
315-335
310-330
330-350
325-345
320-340
340-360
335-355
330-350
355-375
350-370
345-365
GV/GH 580/581
Loop
EWT
15
20
25
30
35
45
50
60
70
Loop
EWT
40
50
60
70
75
80
85
90
95
Loop
GPM
12
13
14
12
13
14
12
13
14
12
13
14
12
13
14
9
10
13
8
9
13
8
9
13
8
9
13
Loop
GPM
8
9
13
8
9
13
8
9
13
8
9
13
12
13
14
12
13
14
12
13
14
12
13
14
12
13
14
dP
ft
11.1
13.9
16.2
11.1
13.9
16.2
11.1
13.9
16.2
11.1
13.9
16.2
11.1
13.9
16.2
7.2
8.8
13.9
5.8
7.2
13.9
5.8
7.2
13.9
5.8
7.2
13.9
dP
ft
5.8
7.2
13.9
5.8
7.2
13.9
5.8
7.2
13.9
5.8
7.2
13.9
11.1
13.9
16.2
11.1
13.9
16.2
11.1
13.9
16.2
11.1
13.9
16.2
11.1
13.9
16.2
dP
psi
4.8
6.0
7.5
4.8
6.0
7.5
4.8
6.0
7.5
4.8
6.0
7.5
4.8
6.0
7.5
3.1
3.8
6.0
2.5
3.1
6.0
2.5
3.1
6.0
2.5
3.1
6.0
dP
psi
2.5
3.1
6.0
2.5
3.1
6.0
2.5
3.1
6.0
2.5
3.1
6.0
4.8
6.0
7.5
4.8
6.0
7.5
4.8
6.0
7.5
4.8
6.0
7.5
4.8
6.0
7.5
MBTU/hr
28.4
28.9
29.6
31.9
32.5
33.2
34.2
34.9
35.6
36.3
37.0
37.7
38.5
39.1
39.8
40.9
41.6
43.0
42.1
42.8
44.4
47.2
47.9
49.1
51.4
52.0
54.3
Heating @ 68oF EAT
First Stage @ 1425 cfm
Suct
Head
KW
COP
Press
Press
2.5
3.3
55-65
240-260
2.5
3.4
56-66
245-265
2.6
3.4
57-67
250-270
2.6
3.6
66-76
250-270
2.6
3.6
67-77
255-275
2.7
3.7
68-78
260-280
2.7
3.7
77-87
265-285
2.7
3.7
78-88
270-290
2.8
3.8
79-89
275-295
2.7
3.9
82-92
275-295
2.8
3.9
83-93
280-300
2.8
4.0
84-94
285-305
2.8
4.0
91-101
295-315
2.8
4.1
92-102
295-315
2.9
4.1
93-103
300-320
2.8
4.2
93-103
300-320
2.9
4.2
94-104
300-320
2.9
4.3
97-107
310-330
2.9
4.3
102-112 310-330
2.9
4.3
104-114 315-335
3.0
4.4
109-119 325-345
3.0
4.6
113-123 335-355
3.0
4.7
115-125 340-360
3.1
4.7
119-129 350-370
3.1
4.8
135-145 360-380
3.1
4.9
137-147 365-385
3.2
5.0
142-152 375-395
MBTU/hr
45.4
46.0
47.1
45.3
45.8
46.8
45.1
45.7
46.6
45.0
45.5
46.4
45.9
46.3
46.8
45.6
46.1
46.6
45.3
45.9
46.4
45.0
45.7
46.1
44.7
45.4
45.9
COOLING @ 80oF DB/67oF WB
First Stage @ 1425 cfm
Suct
Head
KW
EER
Press
Press
2.0
22.7
111-121 180-200
2.0
22.9
110-120 175-195
1.9
24.6
108-118 170-190
2.1
21.4
116-126 210-230
2.1
21.7
115-125 205-225
2.0
22.9
113-123 200-220
2.3
19.3
122-132 245-265
2.3
19.7
121-131 240-260
2.2
21.2
118-128 235-255
2.4
18.5
125-135 265-285
2.4
18.8
124-134 265-285
2.4
19.4
123-133 260-280
2.6
17.1
129-139 285-305
2.6
17.5
128-138 285-305
2.7
17.7
127-137 280-300
2.8
16.0
134-144 305-325
2.8
16.2
133-143 305-325
2.9
16.4
132-142 300-320
2.9
15.3
139-149 315-335
2.9
15.5
138-148 315-335
3.0
15.7
137-147 310-330
3.1
14.3
144-154 325-345
3.1
14.4
143-153 325-345
3.2
14.6
142-152 320-340
3.2
13.7
150-160 340-360
3.2
14.0
149-159 340-360
3.3
14.2
148-158 335-355
MBTU/hr
39.7
40.4
41.2
43.1
44.0
44.6
46.8
47.5
48.2
50.3
50.9
51.7
52.1
52.9
53.8
58.2
58.8
59.8
61.0
61.7
63.3
66.9
67.6
69.1
71.2
72.0
73.8
Second Stage @ 1850 cfm
Suct
KW
COP
Press
3.6
3.2
49-59
3.6
3.3
50-60
3.7
3.3
51-61
3.7
3.4
56-66
3.7
3.5
57-67
3.8
3.5
58-68
3.8
3.6
64-74
3.9
3.6
65-75
3.9
3.7
66-76
4.0
3.7
70-80
4.0
3.7
71-81
4.1
3.7
72-82
4.1
3.7
74-84
4.1
3.8
75-85
4.2
3.8
76-86
4.2
4.1
98-108
4.2
4.1
99-109
4.3
4.2
102-112
4.3
4.2
108-118
4.3
4.2
109-119
4.4
4.3
113-123
4.5
4.3
119-129
4.5
4.4
120-130
4.6
4.4
123-133
4.6
4.5
142-152
4.7
4.5
143-153
4.8
4.5
147-157
Head
Press
270-290
270-290
275-295
280-300
280-300
285-305
290-310
290-310
295-315
305-325
305-325
310-330
315-335
315-335
320-340
335-355
340-360
350-370
350-370
355-375
365-385
370-390
375-395
385-405
400-420
405-425
415-435
MBTU/hr
55.4
56.2
66.7
56.1
57.0
65.8
56.9
57.8
64.6
57.4
58.6
63.5
59.7
62.8
64.1
59.0
61.3
63.6
58.5
60.7
63.0
57.9
60.1
62.3
57.2
59.4
61.6
Second Stage @ 1850 cfm
Suct
KW
EER
Press
2.9
18.8
95-105
3.0
19.1
94-104
3.4
19.7
92-102
3.2
17.7
101-116
3.2
18.0
100-110
3.5
18.5
98-108
3.4
16.5
107-117
3.4
16.8
106-116
3.7
17.3
104-114
3.8
15.3
109-119
3.8
15.5
110-120
4.0
15.9
108-118
4.0
14.9
114-124
4.1
15.3
114-124
4.1
15.6
113-123
4.1
14.3
116-126
116-126
4.2
14.6
4.3
14.8
115-125
4.2
13.9
120-130
119-129
4.3
14.1
4.4
14.3
118-128
4.4
13.2
124-134
123-133
4.5
13.4
4.6
13.6
122-132
4.5
12.7
129-139
137-137
4.6
12.9
4.7
13.2
125-135
Head
Press
225-245
220-240
215-235
250-270
245-265
235-255
280-300
275-295
265-285
295-315
295-315
290-310
305-325
305-325
300-320
310-330
310-330
305-325
330-350
330-350
325-345
345-365
345-365
340-360
360-380
360-380
355-375
13
Performance Data, Hydronic Models – GeoSource 2000, GeoSource DualTEK†
GW 290/291 @ 7 Loop GPM (3.9 PSI dP) and 4 Hyd GPM (1.5 PSI dP)
Open Loop Flow Rate – 4 GPM (1.5 PSI dP)**
HEATING
LOOP HYD TEMP
CAP
HE
SUCT
EWT LWT RISE MBTU/hr KW COP MBTU/hr PRESS
70
11.3
22.6
1.3
5.1
18.2
34-40
85
11.2
22.4
1.6
4.3
17.5
35-41
25
100
11.1
22.3
1.8
3.6
16.2
36-42
115
11.1
22.2
2.1
3.1
15.4
37-43
130
11.0
22.0
2.4
2.7
13.8
38-44
70
12.4
24.8
1.3
5.6
20.4
43-49
85
12.0
24.0
1.6
4.4
18.5
44-50
30
100
11.8
23.6
1.8
3.8
17.5
45-51
115
11.7
23.4
2.1
3.3
16.2
46-52
130
11.4
22.8
2.4
2.8
14.6
47-53
70
13.6
27.2
1.4
5.7
22.4
44-50
85
12.8
25.6
1.6
4.7
20.1
47-53
35
100
12.5
25.0
1.9
3.9
18.5
49-55
115
12.4
24.8
2.2
3.4
17.3
50-56
130
12.0
24.0
2.5
2.9
15.5
51-57
70
14.4
28.8
1.4
6.0
24.0
46-52
85
14.0
28.0
1.7
4.8
22.2
51-57
40
100
13.7
27.4
1.9
4.2
20.9
53-59
115
13.4
26.8
2.2
3.6
19.3
55-61
130
13.1
26.2
2.6
3.0
17.3
56-62
70
16.9
33.8
1.4
6.7
29.0
49-55
85
16.3
33.3
1.7
5.8
27.6
55-61
50
100
16.0
32.7
2.0
4.8
25.9
58-64
115
15.5
31.7
2.3
4.0
23.8
63-69
130
15.1
30.8
2.7
3.3
21.4
64-70
GW/GV/GH 360/361
COOLING
HEAD LOOP HYD TEMP
CAP
HR
SUCT
PRESS EWT LWT DROP MBTU/hr KW EER MBTU/hr PRESS
120-130
35
11.0
22.1
1.2 17.8
26.2
44-50
160-170
40
11.6
23.2
1.2 19.3
27.3
46-52
200-210
50
45
12.3
25.1
1.3 19.8
29.5
49-55
250-260
50
12.8
25.6
1.3 19.9
30.0
53-59
295-305
55
13.3
27.2
1.3 20.6
31.7
57-63
125-135
35
10.8
21.6
1.5 14.4
26.7
48-54
160-170
40
11.6
23.2
1.5 15.5
28.3
51-57
205-215
70
45
12.4
24.8
1.6 15.7
30.3
54-60
250-260
50
13.0
26.0
1.6 16.1
31.5
58-64
300-310
55
13.7
27.4
1.7 16.3
33.2
61-67
130-140
35
10.7
21.4
1.7 12.6
27.2
51-57
165-175
40
11.5
23.0
1.7 13.5
28.8
54-60
210-220
80
45
12.5
25.0
1.8 13.9
31.1
57-63
255-265
50
13.1
26.2
1.8 14.4
32.3
60-66
305-315
55
13.8
27.6
1.9 14.6
34.1
64-70
135-145
35
10.6
21.2
1.8 11.8
27.3
53-59
170-180
40
11.4
22.8
1.9 12.0
29.3
56-62
215-225
90
45
12.4
24.8
2.0 12.4
31.6
59-65
260-270
50
13.0
26.0
2.0 13.0
32.8
62-68
310-320
55
13.6
27.2
2.1 13.1
34.4
66-72
145-155
35
10.5
21.0
2.0 10.5
27.8
57-63
175-185
40
11.3
22.6
2.1 10.8
29.8
60-66
220-230 100
45
12.3
24.6
2.2 11.2
32.1
63-69
265-275
50
12.9
25.8
2.3 11.3
33.6
67-73
315-325
55
13.5
27.0
2.4 11.4
35.2
70-76
@ 8 Loop GPM (5.5 PSI dP) and 5 Hyd GPM (1.7 PSI dP)
Open Loop Flow Rate – 4 GPM (1.3 PSI dP)**
HEATING
COOLING
LOOP HYD TEMP
CAP
HE
SUCT
HEAD LOOP HYD TEMP
CAP
HR
SUCT
EWT LWT RISE MBTU/hr KW COP MBTU/hr PRESS PRESS EWT LWT DROP MBTU/hr KW EER MBTU/hr PRESS
70
10.7
26.8
1.4
5.4
22.0
34-40 125-135
35
11.0
27.5
1.4 19.7
32.3
45-51
85
10.6
26.5
1.7
4.6
20.7
35-41 160-170
40
11.7
29.3
1.4 20.9
34.1
48-54
25
100
10.5
26.3
1.9
4.1
19.8
36-42 200-210
50
45
12.5
31.3
1.4 21.6
36.2
51-57
115
10.4
26.0
2.3
3.3
18.2
37-43 240-250
50
13.0
32.5
1.5 21.9
37.6
55-61
130
10.2
25.5
2.8
2.7
15.9
38-44 290-300
55
13.5
33.8
1.5 22.7
38.9
60-66
70
11.6
29.0
1.5
5.6
23.9
36-42 130-140
35
10.8
27.0
1.8 15.0
33.1
51-57
85
11.2
28.0
1.7
4.8
22.2
38-44 160-170
40
11.7
29.3
1.8 16.2
35.4
54-60
30
100
11.0
27.5
2.0
4.2
20.7
39-45 205-215
70
45
12.5
31.3
1.9 16.5
37.8
57-63
115
10.9
27.3
2.4
3.5
19.1
41-47 245-255
50
13.1
32.8
1.9 17.3
39.3
59-65
130
10.6
26.5
2.9
2.8
16.6
42-48 295-305
55
13.6
34.0
2.0 17.5
40.8
62-68
70
12.4
31.0
1.5
6.1
25.9
39-45 130-140
35
10.6
26.5
1.9 14.0
33.0
54-60
85
11.7
29.3
1.8
5.0
23.2
41-47 165-175
40
11.5
28.8
2.0 14.4
35.6
57-63
35
100
11.5
28.8
2.0
4.4
22.0
43-49 205-215
80
45
12.4
31.0
2.1 14.8
38.2
60-66
115
11.4
28.5
2.4
3.7
20.3
45-51 250-260
50
13.0
32.5
2.1 15.5
39.7
63-69
130
10.9
27.3
2.9
3.0
17.4
46-52 300-310
55
13.5
33.8
2.2 15.7
41.3
65-71
70
13.2
33.0
1.6
6.4
27.5
42-48 135-145
35
10.5
26.3
2.1 12.5
33.5
57-63
85
12.9
32.3
1.8
5.3
26.2
45-51 170-180
40
11.4
28.5
2.2 12.6
36.0
60-66
40
100
12.6
31.5
2.1
4.6
24.3
47-53 210-220
90
45
12.3
30.8
2.3 13.4
38.6
63-69
115
12.4
31.0
2.5
3.9
22.5
48-64 255-265
50
12.9
32.3
2.4 13.5
40.5
65-71
130
12.0
31.0
3.0
3.1
19.8
50-56 305-315
55
13.3
33.3
2.5 13.6
41.8
68-74
70
14.9
38.0
1.6
7.0
32.6
47-53 140-150
35
10.4
26.0
2.3 11.3
33.8
61-67
85
15.3
38.9
1.9
6.1
32.6
54-60 175-185
40
11.3
28.3
2.4 11.8
36.5
64-70
50
100
15.0
38.3
2.2
5.1
30.7
57-63 215-225 100
45
12.1
30.3
2.5 12.1
38.8
67-73
115
14.5
37.1
2.6
4.2
28.2
62-68 260-270
50
12.7
31.8
2.6 12.2
40.7
70-76
130
14.1
36.0
3.1
3.4
25.5
63-70 310-320
55
13.7
32.8
2.7 12.4
42.0
73-79
** Water Flow Rate Correction Factors are listed on page 45.
Note: Head Loss = Pressure drop in PSI x 2.31
14
HEAD
PRESS
120-130
120-130
125-135
125-135
130-140
155-165
160-170
165-175
170-180
175-185
180-190
185-195
190-200
195-205
200-210
200-210
205-215
210-220
215-225
220-230
220-230
225-235
230-240
235-245
240-250
HEAD
PRESS
115-125
120-130
120-130
125-135
125-135
155-165
160-170
165-175
170-180
175-185
170-180
175-185
180-190
185-195
190-200
190-200
195-205
200-210
205-215
210-220
210-220
215-225
220-230
225-235
230-240
GW 420/421 @ 10 Loop GPM (7.8 PSI dP)* and 6 Hyd GPM (2.8 PSI dP)
Open Loop Flow Rate – 5 GPM (1.7 PSI dP)**
HEATING
LOOP HYD TEMP
CAP
EWT LWT RISE MBTU/hr KW
70
11.5
34.5
1.9
85
11.4
34.1
2.3
25
100
11.3
33.9
2.7
115
11.2
33.7
3.2
130
11.1
33.3
3.7
70
12.4
37.2
1.9
85
12.0
36.0
2.2
30
100
11.9
35.7
2.7
115
11.7
35.1
3.2
130
11.5
34.5
3.7
70
13.4
40.2
1.9
85
12.7
38.1
2.3
35
100
12.4
37.2
2.7
115
12.2
36.6
3.2
130
11.8
35.4
3.8
70
14.4
43.2
2.0
85
14.0
42.0
2.4
40
100
13.7
41.1
2.8
115
13.4
40.2
3.3
130
13.0
39.0
3.8
70
16.3
49.0
2.0
85
16.7
50.2
2.4
50
100
16.4
49.3
2.8
115
15.8
47.8
3.3
130
15.5
46.4
3.9
HE
SUCT
COP MBTU/hr PRESS
5.3
28.0
34-40
4.3
26.2
35-41
3.7
24.7
36-42
3.1
22.8
37-43
2.7
20.7
38-44
5.7
30.7
36-42
4.8
28.5
38-44
3.9
26.5
39-45
3.2
24.2
42-48
2.8
21.9
43-49
6.2
33.7
39-45
4.9
30.3
41-47
4.1
28.0
44-50
3.4
25.7
47-53
3.0
22.4
50-56
6.5
36.4
42-48
5.2
33.8
45-51
4.3
31.5
48-54
3.6
28.9
52-58
3.1
26.0
55-61
7.1
42.1
47-53
6.2
42.0
54-62
5.1
39.8
57-63
4.2
36.4
62-68
3.5
33.0
63-69
COOLING
HEAD LOOP HYD TEMP
CAP
HR
SUCT
PRESS EWT LWT DROP MBTU/hr KW EER MBTU/hr PRESS
125-135
35
10.5
31.4
1.7 18.0
37.3
44-50
160-170
40
11.2
33.6
1.7 19.8
39.7
46-52
200-210
50
45
11.9
35.6
1.8 20.0
41.7
49-55
250-260
50
12.5
37.5
1.8 20.4
43.6
52-58
290-300
55
12.8
38.5
1.8 20.8
44.8
57-63
130-140
35
10.3
30.9
2.1 14.7
38.1
49-55
160-170
40
11.2
33.6
2.1 16.0
40.8
52-58
205-215
70
45
12.0
36.0
2.2 16.4
43.5
55-61
250-260
50
12.6
37.8
2.2 17.2
45.3
57-63
295-305
55
12.9
38.7
2.3 17.3
46.5
60-66
135-145
35
10.2
30.6
2.3 13.3
38.4
52-58
165-175
40
11.1
33.3
2.3 14.5
41.1
55-61
210-220
80
45
11.9
35.7
2.4 14.9
43.9
58-64
255-265
50
12.6
37.8
2.4 15.7
46.0
60-66
300-310
55
13.0
39.0
2.5 15.9
47.5
63-69
140-150
35
10.1
30.3
2.4 12.6
38.5
55-61
170-180
40
10.9
32.7
2.5 13.1
41.2
58-64
215-225
90
45
11.8
35.4
2.6 13.6
44.3
61-67
260-270
50
12.4
37.2
2.6 14.3
46.1
64-70
305-315
55
12.8
38.4
2.7 14.5
47.6
67-73
145-155
35
10.0
30.0
2.6 11.5
38.9
58-64
175-185
40
10.8
32.4
2.7 12.0
41.6
61-67
220-230 100
45
11.6
34.8
2.8 12.4
44.4
64-70
265-275
50
12.3
36.9
2.9 12.7
46.8
67-73
315-325
55
12.6
37.8
3.0 12.8
48.0
70-76
HEAD
PRESS
120-130
120-130
125-135
125-135
125-135
160-170
160-170
165-175
165-175
170-180
180-190
185-195
185-195
190-200
195-205
195-205
200-210
205-215
210-220
215-225
215-225
220-230
225-235
230-240
235-245
GW/GV/GH 520/521 @ 11 Loop GPM (5.2 PSI dP)* and 7 Hyd GPM (4.8 PSI dP)
Open Loop Flow Rate – 6 GPM (1.6 PSI dP)**
HEATING
COOLING
LOOP HYD TEMP
CAP
HE
SUCT
HEAD LOOP HYD TEMP
CAP
HR
SUCT
HEAD
EWT LWT RISE MBTU/hr KW COP MBTU/hr PRESS PRESS EWT LWT DROP MBTU/hr KW EER MBTU/hr PRESS PRESS
70
11.6
40.6
2.3
5.2
32.8
33-39 125-135
35
11.6
40.6
2.1 19.3
47.8
40-46 120-130
85
11.4
39.8
2.9
4.1
30.1
35-41 160-170
40
12.3
43.1
2.1 20.5
50.2
42-48 120-130
25
100
11.3
39.6
3.3
3.5
28.3
36-42 200-210
50
45
13.2
46.1
2.2 21.5
53.5
45-51 125-135
115
11.2
39.4
4.0
2.9
25.6
37-43 250-260
50
13.7
48.0
2.2 21.8
55.5
49-55 125-135
130
11.0
38.5
4.5
2.5
23.1
39-45 290-300
55
14.2
49.8
2.2 22.3
57.4
53-59 125-135
70
12.7
44.5
2.3
5.7
36.7
36-42 130-140
35
11.6
40.6
2.5 16.3
49.1
44-50 160-170
85
12.2
42.7
2.8
4.5
33.1
38-44 160-170
40
12.3
43.1
2.6 16.6
52.0
47-53 165-175
30
100
12.0
42.0
3.3
3.7
30.7
39-45 205-215
70
45
13.3
46.6
2.7 17.2
55.8
50-56 170-180
115
11.9
41.7
4.0
3.1
28.1
41-47 250-260
50
13.8
48.3
2.7 17.9
57.5
53-59 175-185
130
11.4
39.9
4.5
2.6
24.5
43-49 295-305
55
14.4
50.4
2.8 18.1
60.0
56-62 180-190
70
13.7
48.0
2.3
6.1
40.2
39-45 135-145
35
11.5
40.3
2.7 14.9
49.5
46-52 180-190
85
13.0
45.5
2.8
4.8
35.9
41-47 165-175
40
12.4
43.4
2.8 15.5
53.0
48-54 185-195
35
100
12.7
44.5
3.3
3.9
33.2
43-49 210-220
80
45
13.3
46.6
2.9 16.1
56.5
52-58 190-200
115
12.6
44.1
4.0
3.2
30.5
45-51 255-265
50
13.9
48.7
2.9 16.8
58.6
55-61 195-205
130
11.9
41.7
4.6
2.7
26.0
47-53 300-310
55
14.5
50.8
3.0 17.0
61.0
58-64 200-210
70
14.6
51.1
2.4
6.3
42.9
42-48 140-150
35
11.4
39.9
2.9 13.8
49.8
48-54 200-210
85
14.2
49.7
2.9
5.1
39.8
45-51 170-180
40
12.3
43.1
3.0 14.4
53.3
51-57 205-215
40
100
13.9
48.7
3.4
4.2
37.1
48-54 215-225
90
45
13.1
45.9
3.1 14.8
56.5
54-60 210-220
115
13.7
48.0
4.0
3.5
34.4
51-57 260-270
50
13.8
48.3
3.2 15.1
59.2
57-63 215-225
130
13.1
45.9
4.6
3.0
30.2
53-59 305-315
55
14.3
50.1
3.3 15.2
61.4
60-66 220-230
70
16.4
57.3
2.4
6.9
49.1
47-53 145-155
35
11.2
39.2
3.1 12.6
49.8
51-57 220-230
85
16.8
58.8
2.8
6.0
49.1
54-60 175-185
40
12.2
42.7
3.2 13.3
53.6
54-60 225-235
50
100
16.5
57.8
3.4
5.0
46.3
57-63 220-230 100
45
13.0
45.5
3.3 13.9
56.8
57-63 230-240
115
16.0
56.0
4.0
4.1
42.3
62-68 265-275
50
13.6
47.6
3.4 14.0
59.2
60-66 235-245
130
15.5
54.4
4.7
3.4
38.2
63-69 315-325
55
14.1
49.4
3.5 14.1
61.3
63-69 240-250
** Water Flow Rate Correction Factors are listed on page 45.
*Earth Loop Pressure Drop for standard water coils only.
Note: Head Loss = Pressure drop in PSI x 2.31
Cupro-nickel water coils have higher pressure drops.
15
GW/GV/GH 590/591 @ 13 Loop GPM (6.0 PSI dP)* and 9 Hyd GPM (7.0 PSI dP)
Open Loop Flow Rate – 9 GPM (3.1 PSI dP)**
HEATING
LOOP HYD TEMP
CAP
EWT LWT RISE MBTU/hr KW
70
10.9
49.1
2.8
85
10.8
48.5
3.4
25
100
10.8
48.4
3.9
115
10.7
48.0
4.7
130
10.5
47.3
5.4
70
12.0
54.0
2.8
85
11.6
52.2
3.3
30
100
11.4
51.3
3.9
115
11.3
50.9
4.7
130
11.0
49.5
5.4
70
13.0
58.5
2.8
85
12.7
57.2
3.3
35
100
12.4
55.8
4.0
115
11.8
53.1
4.8
130
11.5
51.8
5.5
70
13.7
61.7
2.9
85
13.8
62.1
3.4
40
100
13.5
60.8
4.0
115
12.9
58.1
4.8
130
12.6
56.7
5.5
70
15.5
69.6
2.9
85
15.9
71.4
3.4
50
100
15.6
70.2
4.0
115
15.1
68.0
4.8
130
14.7
66.0
5.6
HE
SUCT
COP MBTU/hr PRESS
5.1
39.5
32-38
4.2
37.0
33-39
3.6
35.1
34-40
3.0
31.8
35-41
2.6
28.9
37-43
5.7
44.4
36-42
4.6
40.9
38-44
3.9
38.0
39-45
3.2
34.9
42-48
2.7
31.1
43-49
6.1
48.9
38-44
5.1
45.9
42-48
4.1
42.2
44-50
3.3
36.7
46-52
2.9
33.0
48-54
6.3
51.8
40-46
5.4
50.5
45-51
4.5
47.2
49-55
3.5
41.7
51-57
3.1
37.9
53-59
7.1
59.8
44-50
6.2
59.9
52-58
5.1
56.5
55-61
4.2
51.8
60-66
3.5
46.9
61-67
COOLING
HEAD LOOP HYD TEMP
CAP
HR
SUCT
PRESS EWT LWT DROP MBTU/hr KW EER MBTU/hr PRESS
130-140
35
10.5
47.4
2.6 18.0
56.4
39-45
170-180
40
11.2
50.4
2.6 19.4
59.3
41-47
205-215
50
45
12.0
53.9
2.7 20.0
63.0
44-50
245-255
50
12.4
55.8
2.7 20.6
65.0
48-54
290-300
55
12.9
58.2
2.8 20.8
67.7
52-58
135-145
35
10.4
46.8
3.2 14.6
57.7
43-49
170-180
40
11.4
51.3
3.3 15.5
62.3
46-52
205-215
70
45
12.1
54.5
3.4 16.0
66.1
49-55
245-255
50
12.5
56.3
3.4 16.5
67.9
52-58
295-305
55
13.1
59.0
3.5 16.8
70.9
55-61
140-150
35
10.3
46.4
3.4 13.6
58.0
45-51
175-185
40
11.3
50.9
3.5 14.5
62.8
48-54
210-220
80
45
11.9
53.6
3.6 14.9
65.9
51-57
250-260
50
12.3
55.4
3.7 15.0
68.0
54-60
300-310
55
13.3
59.9
3.8 15.8
72.9
57-63
145-155
35
10.2
45.9
3.6 12.8
58.2
47-53
175-185
40
11.2
50.4
3.7 13.6
63.0
50-56
215-225
90
45
11.8
53.1
3.8 14.0
66.1
53-59
255-265
50
12.2
54.9
3.9 14.1
67.9
56-62
305-315
55
13.2
59.4
4.0 14.9
73.0
59-65
150-160
35
10.1
45.5
3.8 12.0
58.5
50-56
180-190
40
10.9
49.1
3.9 12.6
62.4
53-59
220-230 100
45
11.6
52.2
4.0 13.1
65.8
56-62
260-270
50
12.1
54.5
4.1 13.3
68.5
59-65
310-320
55
13.0
58.5
4.2 13.9
72.8
62-68
HEAD
PRESS
120-130
120-130
125-135
125-135
125-135
155-165
160-170
165-175
170-180
175-185
175-185
180-190
185-195
190-200
195-205
200-210
205-215
210-220
215-225
220-230
225-235
230-240
235-245
240-250
245-255
GW/GV/GH 670/671 @ 14 Loop GPM (7.0 PSI dP)* and 11 Hyd GPM (11.7 PSI dP)
Open Loop Flow Rate – 10 GPM (3.8 PSI dP)**
HEATING
COOLING
LOOP HYD TEMP
CAP
HE
SUCT
HEAD LOOP HYD TEMP
CAP
HR
SUCT
EWT LWT RISE MBTU/hr KW COP MBTU/hr PRESS PRESS EWT LWT DROP MBTU/hr KW EER MBTU/hr PRESS
70
10.1
55.6
3.3
4.9
44.3
31-37 135-145
35
9.6
53.0
3.2 16.6
63.8
37-43
85
10.2
56.3
4.1
4.0
42.2
33-39 170-180
40
10.2
56.1
3.2 17.5
67.0
40-46
25
100
10.2
56.1
4.7
3.5
40.0
34-40 200-210
50
45
10.9
60.2
3.3 18.5
71.3
43-49
115
10.1
55.6
5.8
2.8
35.8
35-41 245-255
50
11.3
62.2
3.3 18.8
73.5
46-52
130
10.0
55.0
6.7
2.4
32.1
37-43 285-295
55
11.8
65.0
3.4 19.2
76.6
50-56
70
11.3
62.2
3.4
5.4
50.6
34-40 140-150
35
9.6
52.8
3.9 13.5
66.1
42-48
85
11.0
60.5
4.0
4.4
46.9
36-42 170-180
40
10.3
56.7
3.9 14.5
70.0
44-50
30
100
10.8
59.4
4.8
3.6
43.0
37-43 205-215
70
45
11.0
60.5
4.0 15.1
74.1
47-53
115
10.6
58.3
5.7
3.0
38.9
38-44 245-255
50
11.4
62.7
4.0 15.7
76.3
50-56
130
10.4
57.2
6.7
2.6
34.3
39-45 290-300
55
12.0
66.0
4.1 16.1
80.0
53-59
70
12.5
68.8
3.4
5.9
57.2
37-43 145-155
35
9.5
52.3
4.3 12.2
67.0
45-51
85
12.1
66.6
4.0
4.9
53.0
40-46 175-185
40
10.2
56.1
4.3 13.0
70.8
47-53
35
100
11.8
64.9
4.8
4.0
48.5
42-48 210-220
80
45
11.1
61.1
4.4 13.9
76.1
50-56
115
11.2
61.6
5.8
3.1
41.8
43-49 250-260
50
11.4
62.7
4.4 14.3
77.7
53-59
130
10.8
59.4
6.8
2.8
36.2
44-50 295-305
55
12.1
66.7
4.5 14.8
82.0
56-62
70
13.2
72.6
3.5
6.1
60.7
39-45 150-160
35
9.4
51.7
4.5 11.5
67.1
48-54
85
13.4
73.7
4.1
5.3
59.7
44-50 180-190
40
10.1
55.6
4.6 12.1
71.3
51-57
40
100
12.8
70.4
4.9
4.2
53.6
46-52 215-225
90
45
10.9
60.0
4.7 12.8
76.0
54-60
115
12.2
67.1
5.8
3.4
47.3
47-53 255-265
50
11.2
61.6
4.8 12.9
77.9
57-63
130
11.9
65.5
6.8
3.0
42.3
49-55 300-310
55
11.9
65.5
4.9 13.4
82.2
60-66
70
14.7
80.8
3.5
6.8
68.8
44-50 155-165
35
9.3
51.2
4.8 10.7
67.6
51-57
85
15.1
82.8
4.1
5.9
68.2
52-58 185-195
40
9.9
54.5
4.9 11.1
71.2
53-59
50
100
14.8
81.4
4.9
4.9
64.8
54-60 220-230 100
45
10.7
58.9
5.0 11.8
76.0
56-62
115
14.3
78.9
5.8
4.0
59.1
57-63 260-270
50
11.1
61.1
5.1 12.0
78.5
59-65
130
13.9
76.6
6.8
3.3
53.3
59-65 310-320
55
11.7
64.4
5.2 12.4
82.1
62-68
** Water Flow Rate Correction Factors are listed on page 45.
*Earth Loop Pressure Drop for standard water coils only.
Note: Head Loss = Pressure drop in PSI x 2.31
Cupro-nickel water coils have higher pressure drops.
16
HEAD
PRESS
120-130
120-130
125-135
125-135
125-135
150-160
155-165
160-170
160-170
165-175
170-180
175-185
180-190
180-190
185-195
190-200
195-205
200-210
205-215
210-220
215-225
220-230
225-235
230-240
235-245
GW 980 @ 22 Loop GPM (3.8 PSI dP) and 15 Hyd GPM (4.0 PSI dP)
Open Loop Flow Rate – 16 GPM (3.0 PSI dP)**
HEATING
LOOP HYD TEMP
CAP
EWT LWT RISE MBTU/hr KW
70
10.5
79.1
5.0
85
10.5
78..7
5.7
25
100
10.4
78.1
6.8
115
10.4
77.8
8.0
130
10.2
76.8
9.4
70
11.2
83.9
4.9
85
11.3
84.4
5.7
30
100
11.1
82.9
6.7
115
10.9
82.1
7.9
130
10.7
80.6
9.3
70
11.7
87.4
4.8
85
11.9
88.9
5.6
35
100
11.7
88.1
6.6
115
11.5
86.6
7.9
130
11.3
84.4
9.3
70
12.6
94.2
4.8
85
12.8
95.7
5.6
40
100
12.7
94.9
6.6
115
12.4
92.7
7.8
130
12.1
90.4
9.2
70
14.3
107.1
4.7
85
14.6
109.7
5.5
50
100
14.4
107.9
6.5
115
13.9
104.6
7.7
130
13.5
101.5
9.1
HE
SUCT
COP MBTU/hr PRESS
4.6
62.0
30-36
4.0
59.3
32-37
3.4
54.9
33-39
2.9
50.5
34-40
2.4
44.7
36-42
5.0
67.2
34-40
4.3
65.0
35-41
3.6
60.0
37-43
3.0
55.1
38-44
2.5
48.9
40-46
5.3
71.0
38-44
4.7
69.8
39-45
3.9
65.6
41-47
3.2
59.6
42-48
2.7
52.7
45-51
5.8
77.8
42-48
5.0
76.6
43-50
4.2
72.4
46-52
3.5
66.1
47-53
2.9
59.0
49-55
6.7
91.1
52-58
5.8
90.9
53-59
4.9
85.7
56-62
4.0
78.3
57-63
3.3
70.5
60-66
COOLING
HEAD LOOP HYD TEMP
CAP
HR
SUCT
PRESS EWT LWT DROP MBTU/hr KW EER MBTU/hr PRESS
125-135
35
9.9
74.0
4.3 17.2
88.7
39-45
160-170
40
10.5
78.6
4.4 17.9
93.6
42-48
195-205
50
45
11.2
84.2
4.5 18.6
99.6
45-51
240-250
50
11.6
86.7
4.6 18.8
102.4
49-55
285-295
55
12.1
90.9
4.7 10.9
106.9
53-59
130-140
35
9.9
74.1
5.4 13.7
92.5
42-48
165-175
40
10.6
79.4
5.5 14.4
98.2
45-51
205-215
70
45
11.3
84.6
5.6 15.1
103.7
49-55
250-260
50
11.8
88.4
5.7 15.5
107.8
53-59
290-300
55
12.3
92.1
5.8 15.9
111.9
57-63
135-145
35
9.8
73.4
6.0 12.2
93.9
46-52
170-180
40
10.7
80.1
6.1 13.1
100.9
49-55
210-220
80
45
11.4
85.4
6.2 13.8
106.6
53-59
260-270
50
11.9
89.1
6.3 14.1
110.6
57-63
295-305
55
12.5
93.6
6.4 14.6
115.4
61-67
140-150
35
9.7
72.6
6.5 11.2
94.8
48-54
175-185
40
10.4
77.9
6.6 11.8
100.4
52-58
215-225
90
45
11.2
83.9
6.7 12.5
106.8
56-62
265-275
50
11.7
87.6
6.8 12.9
110.8
60-66
300-310
55
12.2
91.4
6.9 13.2
114.9
64-70
145-155
35
9.6
71.9
7.0 10.3
95.8
52-58
180-190
40
10.2
76.4
7.1 10.8
100.6
56-62
220-230 100
45
11.0
82.4
7.2 11.4
107.0
60-66
270-280
50
11.5
86.1
7.3 11.8
111.0
64-70
310-320
55
12.0
89.9
7.4 12.1
115.1
68-74
HEAD
PRESS
115-125
115-125
120-130
120-130
125-135
160-170
165-175
170-180
175-185
180-190
175-185
180-190
185-195
190-200
195-205
195-205
200-210
205-215
210-220
215-225
215-225
220-230
225-235
230-240
235-245
GW 1200 @ 26 Loop GPM (4.5 PSI dP) and 18 Hyd GPM (4.5 PSI dP)
Open Loop Flow Rate – 18 GPM (3.5 PSI dP)**
HEATING
COOLING
LOOP HYD TEMP
CAP
HE
SUCT
HEAD LOOP HYD TEMP
CAP
HR
SUCT
EWT LWT RISE MBTU/hr KW COP MBTU/hr PRESS PRESS EWT LWT DROP MBTU/hr KW EER MBTU/hr PRESS
70
10.5
94.5
6.1
4.5
73.7
30-36 135-145
35
9.9
89.0
5.4 16.4
107.6
36-42
85
10.4
94.0
7.0
4.0
70.2
32-38 170-180
40
10.5
94.5
5.5 17.2
113.3
38-44
25
100
10.4
93.3
8.3
3.3
65.0
33-39 205-215
50
45
11.2
101.2
5.6 18.2
120.1
41-47
115
10.3
92.9
9.8
2.8
59.4
34-40 250-260
50
11.6
104.4
5.7 18.3
123.8
44-50
130
10.2
91.8
11.5 2.3
52.6
35-41 290-300
55
12.1
109.3
5.8 18.9
129.0
48-54
70
11.1
99.9
6.0
4.9
79.4
32-38 140-150
35
9.9
89.1
6.8 13.1
112.3
39-45
85
11.2
100.8
6.9
4.3
77.3
33-39 175-185
40
10.6
95.4
6.9 13.8
118.9
41-47
30
100
11.0
99.0
8.2
3.5
71.0
35-41 210-220
70
45
11.3
101.7
7.0 14.5
125.6
44-50
115
10.9
98.1
9.7
3.0
65.0
36-42 255-265
50
11.8
106.2
7.1 15.0
130.4
47-53
130
10.7
96.3
11.4 2.5
57.4
38-44 295-305
55
12.3
110.7
7.2 15.4
135.3
50-56
70
11.6
104.4
5.9
5.2
84.3
34-40 145-155
35
9.8
88.2
7.5 11.8
113.8
42-48
85
11.8
106.2
6.8
4.6
83.0
37-43 180-190
40
10.7
96.3
7.6 12.7
122.2
45-51
35
100
11.7
105.3
8.1
3.8
77.7
39-45 215-225
80
45
11.4
102.6
7.7 13.3
128.9
47-53
115
11.5
103.5
9.6
3.2
70.7
41-47 260-270
50
11.9
107.1
7.8 13.7
133.7
50-56
130
11.2
100.8
11.3 2.6
62.2
42-48 300-310
55
12.5
112.5
7.9 14.2
139.5
53-59
70
12.5
112.5
5.8
5.7
92.7
37-43 150-160
35
9.7
87.3
8.1 10.8
114.9
45-51
85
12.7
114.3
6.8
4.9
91.1
41-47 185-195
40
10.4
93.6
8.2 11.4
121.6
48-54
40
100
12.6
113.4
8.0
4.2
86.1
43-49 220-230
90
45
11.2
100.8
8.3 12.1
129.1
50-56
115
12.3
110.7
9.5
3.4
78.3
46-52 265-275
50
11.7
105.3
8.4 12.5
134.0
53-59
130
12.0
108.0
11.2 2.8
69.8
47-53 305-315
55
12.2
109.8
8.5 12.9
138.8
56-62
70
14.2
127.9
5.7
6.6
108.5
42-48 155-165
35
9.6
86.4
8.8
9.8
116.4
48-54
85
14.6
131.1
6.7
5.8
108.3
50-56 185-195
40
10.2
91.8
8.9 10.3
122.2
50-56
50
100
14.3
128.9
7.9
4.8
101.9
52-58 225-235 100
45
11.0
99.0
9.0 11.0
129.7
53-59
115
13.9
124.9
9.4
3.9
92.9
56-62 265-275
50
11.5
103.5
9.1 11.4
134.5
56-62
130
13.5
121.3
11.1 3.2
83.4
57-63 315-325
55
12.0
108.0
9.2 11.7
139.4
59-65
** Water Flow Rate Correction Factors are listed on page 45.
Note: Head Loss = Pressure drop in PSI x 2.31
HEAD
PRESS
120-130
120-130
125-135
125-135
130-140
165-175
170-180
175-185
180-190
185-195
180-190
185-195
190-200
195-205
200-210
200-210
205-215
210-220
215-225
220-230
220-230
225-235
230-240
235-245
240-250
17
GW 3800 @ 78 Loop GPM (6.0 PSI dP)
and 54 Hyd GPM (3.3 PSI dP)
HEATING
LOOP HYD TEMP
CAP
HE
SUCT
EWT LWT RISE MBTU/hr KW COP MBTU/hr PRESS
70
10.5
284.2
23.6 3.5
203.7
32-38
85
10.4
282.0
26.3 3.2
192.3
34-40
25
100
10.4
280.3
29.2 2.8
180.7
36-42
115
10.3
278.7
32.8 2.5
166.8
38-44
130
10.1
272.8
37.2 2.2
145.9
40-46
70
11.1
300.5
23.2 3.8
221.3
35-41
85
11.0
298.2
25.9 3.4
209.8
37-43
30
100
11.0
296.3
29.0 3.0
197.4
39-45
115
10.9
294.4
31.4 2.8
187.3
41-47
130
10.7
288.2
37.1 2.3
161.6
43-49
70
11.7
316.9
23.0 4.0
238.4
38-44
85
11.6
314.4
25.7 3.6
226.7
40-46
35
100
11.6
312.3
28.4 3.3
215.4
42-48
115
11.5
310.1
30.8 3.0
205.0
44-50
130
11.2
303.6
36.9 2.5
177.7
46-52
70
12.7
342.1
22.9 4.4
264.0
41-47
85
12.8
345.8
25.5 4.0
258.8
43-49
40
100
12.7
341.5
28.2 3.6
245.3
45-51
115
12.4
334.6
30.6 3.2
230.2
47-53
130
12.1
326.1
36.4 2.7
201.9
49-55
70
14.2
383.7
22.8 4.9
305.9
49-55
85
14.6
393.3
25.1 4.6
307.7
51-57
50
100
14.3
386.7
27.4 4.1
293.2
53-59
115
13.9
374.7
30.4 3.6
271.0
55-61
130
13.5
363.9
35.6 3.0
242.4
57-63
Water Flow Rate Correction Factors are listed on page 45
18
COOLING
HEAD LOOP HYD TEMP
CAP
HR
SUCT
PRESS EWT LWT DROP MBTU/hr KW EER MBTU/hr PRESS
100-110
35
9.9
267.0
21.7 12.3
341.0
45-51
125-135
40
10.6
285.3
22.1 12.9
360.7
47-53
155-165
50
45
11.2
303.6
22.5 13.5
380.4
50-56
190-200
50
11.7
315.8
22.9 13.8
393.9
53-59
230-240
55
12.1
327.9
23.4 14.0
407.7
56-62
110-120
35
9.8
265.0
24.5 10.8
348.6
49-55
135-145
40
10.6
287.4
24.6 11.7
371.3
52-58
165-175
70
45
11.3
305.3
24.9 12.3
390.3
55-61
200-210
50
11.9
321.1
25.3 12.7
407.4
58-64
240-250
55
12.4
335.0
25.6 13.1
422.3
61-67
120-130
35
9.8
263.7
26.0 10.1
352.4
51-57
145-155
40
10.6
287.0
26.1 11.0
376.1
54-60
175-185
80
45
11.3
305.8
26.4 11.6
395.9
57-63
210-220
50
12.0
323.0
26.7 12.1
414.1
60-66
250-260
55
12.5
338.2
27.1 12.5
430.7
63-69
130-140
35
9.7
261.9
27.3 9.6
355.0
53-59
155-165
40
10.5
283.5
27.4 10.3
377.0
56-62
185-195
90
45
11.2
302.4
27.6 11.0
396.6
59-65
220-230
50
11.9
321.3
27.8 11.6
416.2
62-68
260-270
55
12.4
334.8
28.1 11.9
430.7
65-71
140-150
35
9.6
259.2
28.2 9.2
355.4
55-61
165-175
40
10.4
280.8
28.3 9.9
377.4
58-64
195-205 100
45
11.1
299.7
28.5 10.5
396.9
61-67
230-240
50
11.8
318.6
28.6 11.1
416.2
64-70
275-285
55
12.3
332.1
28.8 11.5
430.4
67-73
Note: Head Loss = Pressure drop in PSI x 2.31
HEAD
PRESS
110-120
115-125
115-125
120-130
125-135
145-155
150-160
155-165
155-165
160-170
165-175
170-180
175-185
180-190
185-195
180-190
185-195
190-200
195-205
200-210
200-210
205-215
210-220
215-225
220-230
Preliminary Performance Data, Hydronic Models – GeoSource Ultra
GW 370/371 @ 8 Loop GPM (5.5 PSI dP) and 5 Hyd GPM (1.7 PSI dP)
Open Loop Flow Rate – 4 GPM (1.3 PSI dP)**
HEATING
LOOP HYD TEMP
CAP
EWT LWT RISE MBTU/hr KW
70
12.0
30.1
1.5
85
11.7
29.2
1.8
25
100
11.3
28.3
2.2
115
11.0
27.4
2.6
130
10.7
26.7
3.0
70
12.9
32.2
1.5
85
12.4
31.0
1.8
30
100
12.0
30.0
2.2
115
11.7
29.2
2.6
130
11.3
28.3
3.0
70
13.8
24.6
1.6
85
13.3
33.3
1.9
35
100
12.8
32.0
2.2
115
12.3
30.8
2.6
130
11.9
29.7
3.0
70
14.6
36.4
1.6
85
14.0
35.1
1.9
40
100
13.5
33.7
2.2
115
13.0
32.4
2.6
130
12.5
31.2
3.0
70
16.3
40.7
1.6
85
15.6
39.1
1.9
50
100
15.1
37.7
2.3
115
14.4
35.9
2.6
130
13.8
34.5
3.0
HE
COP MBTU/hr
5.9
26.0
4.8
24.0
3.8
21.6
3.1
19.2
2.7
17.2
6.3
28.0
5.1
25.6
4.0
23.2
3.3
21.2
2.9
18.8
6.5
30.0
5.2
27.6
4.3
25.2
3.5
22.8
3.1
20.4
6.8
31.6
5.4
29.2
4.5
26.8
3.7
24.4
3.2
22.0
7.5
35.6
6.1
33.2
4.8
30.8
4.1
28.0
3.4
25.6
SUCT
PRESS
58-68
62-72
65-75
68-78
71-81
65-75
68-78
71-81
74-84
77-87
71-81
74-84
76-86
79-89
82-92
77-87
80-90
83-93
85-95
88-98
90-100
92-102
94-104
96-106
99-109
COOLING
HEAD LOOP HYD TEMP
CAP
HR
SUCT
PRESS EWT LWT DROP MBTU/hr KW EER MBTU/hr PRESS
205-225
35
14.5
36.2
1.4 25.8
40.9
87-97
270-290
40
15.5
38.6
1.4 27.6
43.4
94-104
330-350
50
45
16.6
41.4
1.4 29.2
46.2
102-112
390-410
50
17.5
43.9
1.5 29.4
49.0
109-119
455-475
55
18.6
46.5
1.5 31.0
51.6
117-127
210-230
35
12.8
32.0
1.9 16.8
38.4
87-97
270-290
40
13.8
34.6
1.9 18.2
41.1
94-104
335-355
70
45
15.0
37.5
1.9 19.7
43.9
103-113
395-415
50
16.0
39.9
2.0 20.0
46.8
111-121
460-480
55
17.0
42.6
2.0 21.3
49.4
119-129
210-230
35
12.1
30.2
2.1 14.4
37.3
87-97
275-295
40
13.1
32.7
2.1 15.6
39.9
95-105
335-355
80
45
14.1
35.3
2.2 16.1
42.9
104-114
400-420
50
15.2
38.1
2.2 17.3
45.6
112-122
460-480
55
16.3
40.7
2.2 18.5
48.2
120-130
215-235
35
11.3
28.2
2.3 12.3
36.0
87-97
275-295
40
12.4
30.9
2.3 13.4
38.7
95-105
340-360
90
45
13.4
33.4
2.4 13.9
41.6
104-114
405-425
50
13.4
36.1
2.4 15.0
44.3
113-123
465-485
55
15.5
38.8
2.4 16.2
47.0
122-132
215-235
35
10.5
26.2
2.6 10.1
35.1
87-97
280-300
40
11.5
28.7
2.6 11.0
37.6
95-105
345-365 100
45
12.5
31.4
2.7 11.6
40.6
105-115
410-430
50
13.6
34.0
2.7 12.6
43.2
114-124
475-495
55
14.7
36.8
2.7 13.6
46.0
124-134
HEAD
PRESS
185-205
190-210
195-215
200-220
205-225
260-280
270-290
275-295
280-300
290-310
300-320
305-325
315-335
325-345
330-350
340-360
345-365
355-375
365-385
375-395
375-395
385-405
395-415
405-425
415-435
GW 470/471 @ 11 Loop GPM (5.2 PSI dP)* and 7 Hyd GPM (4.8 PSI dP)
Open Loop Flow Rate – 6 GPM (1.6 PSI dP)**
HEATING
COOLING
LOOP HYD TEMP
CAP
HE
SUCT
HEAD LOOP HYD TEMP
CAP
HR
SUCT
EWT LWT RISE MBTU/hr KW COP MBTU/hr PRESS PRESS EWT LWT DROP MBTU/hr KW EER MBTU/hr PRESS
70
11.9
41.7
1.9
6.4
35.2
62-72 180-200
35
13.0
45.6
2.3 19.8
53.4
77-87
85
11.5
40.3
2.4
4.9
32.1
63-73 240-260
40
14.2
49.6
2.3 21.6
57.4
85-95
25
100
11.1
38.8
2.9
3.9
28.9
64-74 300-320
50
45
15.4
53.9
2.3 23.4
61.7
93-103
115
10.7
37.4
3.4
3.2
25.8
65-75 360-380
50
16.6
57.9
2.3 25.2
65.8
101-111
130
10.3
35.9
3.9
2.7
22.6
66-76 420-440
55
17.8
62.4
2.3 27.1
70.2
109-119
70
12.7
44.4
1.9
6.9
38.0
67-77 180-200
35
12.6
44.0
2.7 16.3
53.2
86-96
85
12.2
42.8
2.4
5.2
34.6
69-79 240-260
40
13.5
47.2
2.7 17.5
56.5
92-102
30
100
11.7
41.1
2.9
4.2
31.2
70-80 300-320
70
45
14.4
50.5
2.7 18.7
59.7
99-109
115
11.3
39.7
2.4
3.4
28.1
71-81 365-385
50
15.2
53.2
2.7 19.7
62.5
105-115
130
10.9
38.0
2.9
2.9
24.7
73-83 425-445
55
16.1
56.5
2.7 20.9
65.7
112-122
70
13.5
47.3
1.9
7.2
40.8
74-84 180-200
35
12.5
43.6
2.9 15.1
53.5
90-100
85
13.0
45.6
2.4
5.6
37.5
75-85 240-260
40
13.1
45.9
2.9 15.8
55.8
96-106
35
100
12.5
43.7
2.9
4.4
33.8
76-86 305-325
80
45
13.9
48.5
2.9 16.7
58.4
102-112
115
12.1
42.2
3.5
3.5
30.3
78-88 365-385
50
14.4
50.5
3.0 17.0
60.7
107-117
130
11.5
40.2
4.0
3.0
26.6
79-89 430-450
55
15.7
53.1
3.0 17.7
63.3
113-123
70
14.2
49.8
2.0
7.4
43.0
77-87 180-200
35
12.2
42.7
3.1 13.8
53.3
95-105
85
13.8
48.1
2.5
5.7
39.6
80-90 245-265
40
13.6
47.5
3.1 14.5
58.0
100-110
40
100
13.3
46.6
3.0
4.6
36.4
82-92 305-325
90
45
13.3
46.4
3.1 15.0
57.0
105-115
115
12.8
44.7
3.5
3.7
32.8
85-95 370-390
50
13.8
48.4
3.2 15.2
59.3
110-120
130
12.3
43.0
4.0
3.2
29.4
87-97 435-455
55
14.3
50.1
3.2 15.6
60.1
115-125
70
15.6
54.5
2.1
7.6
47.3
88-98 190-210
35
12.1
42.3
3.3 12.8
53.6
100-110
85
15.2
53.3
2.5
6.3
44.8
92-102 250-270
40
12.4
43.6
3.3 13.3
54.8
104-114
50
100
14.9
52.1
3.0
5.1
41.9
95-105 310-330 100
45
12.7
44.5
3.4 13.5
56.1
108-118
115
14.6
51.1
3.5
4.3
39.1
99-109 370-390
50
13.0
45.5
3.4 13.7
57.2
112-122
130
14.3
50.1
4.0
3.7
36.5
103-113 435-455
55
13.4
47.1
3.4 14.1
58.7
116-126
** Water Flow Rate Correction Factors are listed on page 45
Note: Head Loss = Pressure drop in PSI x 2.31
*Earth Loop Pressure Drop for standard water coils only. Cupro-nickel water coils have higher pressure drops.
HEAD
PRESS
190-210
190-210
190-210
195-215
195-215
265-285
270-290
275-295
275-295
280-300
305-325
310-330
315-335
315-335
320-340
345-365
350-370
355-375
360-380
365-385
385-405
390-410
395-415
400-420
405-425
19
GW 570/571 @ 13 Loop GPM (6.0 PSI dP)* and 9 Hyd GPM (7.0 PSI dP)
Open Loop Flow Rate – 9 GPM (3.1 PSI dP)**
HEATING
LOOP HYD TEMP
CAP
HE
SUCT
EWT LWT RISE MBTU/hr KW COP MBTU/hr PRESS
70
11.5
51.8
2.8
5.4
42.2
60-70
85
11.2
50.5
3.2
4.6
39.6
60-70
25
100
10.7
48.0
3.6
3.9
35.7
65-75
115
10.0
44.8
4.4
3.0
29.8
65-75
130
9.6
43.1
5.1
2.5
25.7
70-80
70
12.3
55.2
2.8
5.8
45.6
65-75
85
11.9
53.6
3.2
4.9
42.7
65-75
30
100
11.4
51.5
3.7
4.1
38.9
70-80
115
10.7
48.3
4.4
3.2
33.3
70-80
130
10.3
46.4
5.2
2.6
28.7
75-85
70
13.0
58.5
2.8
6.1
48.9
70-80
85
12.7
57.0
3.2
5.2
46.1
70-80
35
100
12.3
55.2
3.7
4.4
40.2
75-85
115
11.5
51.7
4.4
3.4
36.7
75-85
130
11.1
49.9
5.2
2.8
32.2
80-90
70
13.8
61.9
2.8
6.5
52.3
75-85
85
13.4
60.4
3.2
5.5
49.5
80-90
40
100
13.0
58.5
3.8
4.5
45.5
80-90
115
12.3
55.5
4.5
3.6
40.1
85-95
130
11.7
53.7
5.3
3.0
35.6
90-100
70
15.1
68.0
2.8
7.1
58.4
90-100
85
14.9
67.0
3.2
6.1
56.1
90-100
50
100
14.5
65.4
3.8
5.0
52.4
95-105
115
13.9
62.7
4.5
4.1
47.3
100-110
130
13.4
60.5
5.3
3.3
42.4
105-115
COOLING
HEAD LOOP HYD TEMP
CAP
HR
SUCT
PRESS EWT LWT DROP MBTU/hr KW EER MBTU/hr PRESS
230-250
35
13.5
60.8
2.3 26.4
68.6
80-90
275-295
40
13.8
61.9
2.3 26.9
69.7
80-90
325-345
50
45
14.1
63.5
2.4 27.0
71.7
85-95
385-405
50
14.3
64.4
2.4 27.1
72.6
90-100
445-465
55
14.6
65.9
2.5 27.2
78.0
95-105
235-255
35
12.1
54.5
3.0 18.2
64.7
80-90
280-300
40
12.6
56.7
3.1 18.3
67.3
85-95
330-350
70
45
12.9
58.1
3.1 18.7
68.7
90-100
390-410
50
13.3
59.9
3.2 18.8
70.8
95-105
450-470
55
13.5
60.6
3.2 19.0
71.5
100-110
235-255
35
11.4
51.2
3.4 15.1
62.8
85-95
280-300
40
11.7
52.7
3.4 15.4
64.3
85-95
330-350
80
45
12.1
54.3
3.5 15.5
66.2
90-100
390-410
50
12.4
55.8
3.5 16.0
67.7
95-105
450-470
55
12.9
57.9
3.6 16.1
70.2
100-110
240-260
35
10.6
47.5
3.7 12.8
60.1
85-95
285-305
40
10.9
48.9
3.8 12.9
61.9
90-100
335-355
90
45
11.2
50.5
3.8 13.3
63.5
95-105
395-415
50
11.7
52.8
3.9 13.5
66.1
100-110
455-475
55
12.2
55.0
3.9 14.1
68.3
105-115
240-260
35
9.6
43.0
4.1 10.5
57.0
90-100
285-305
40
10.0
45.2
4.1 11.0
59.2
90-100
335-355 100
45
10.5
47.1
4.2 11.2
61.4
95-105
400-420
50
11.0
49.6
4.3 11.5
64.3
100-110
460-480
55
11.6
52.2
4.3 12.1
66.9
105-115
HEAD
PRESS
175-195
180-200
180-200
185-205
190-210
260-280
260-280
265-285
270-290
275-295
290-310
295-315
300-320
305-325
310-330
330-340
335-355
340-360
345-365
350-370
370-390
375-395
380-400
385-405
390-410
GW 770/771 @ 15 Loop GPM (7.9 PSI dP)* and 12 Hyd GPM (14.7 PSI dP)
Open Loop Flow Rate – 11 GPM (4.6 PSI dP)**
HEATING
COOLING
LOOP HYD TEMP
CAP
HE
SUCT
HEAD LOOP HYD TEMP
CAP
HR
SUCT
EWT LWT RISE MBTU/hr KW COP MBTU/hr PRESS PRESS EWT LWT DROP MBTU/hr KW EER MBTU/hr PRESS
70
10.8
64.5
3.1
6.1
53.9
60-70 195-215
35
10.0
59.9
2.9 20.7
69.8
70-80
85
10.5
63.0
3.9
4.7
50.1
60-70 365-385
40
10.7
64.2
2.9 22.1
74.1
75-85
25
100
10.1
60.9
4.9
3.6
42.9
65-75 330-350
50
45
11.5
68.9
3.0 23.0
79.1
80-90
115
10.0
59.7
5.9
3.0
37.7
65-75 400-420
50
12.2
73.2
3.0 24.4
83.4
90-100
130
9.7
58.2
6.9
2.5
31.9
70-80 465-485
55
12.9
77.3
3.1 25.0
87.9
95-105
70
11.6
69.6
3.1
6.6
59.0
65-75 200-220
35
10.1
60.4
3.8 15.9
73.4
75-85
85
11.3
67.8
3.9
5.1
55.3
70-80 265-275
40
10.7
64.0
3.9 16.4
77.3
80-90
30
100
11.0
65.7
4.9
3.9
48.8
70-80 335-345
70
45
11.4
68.3
3.9 17.5
81.6
85-95
115
10.7
64.1
6.0
3.1
42.9
75-85 405-425
50
12.0
72.2
4.0 18.0
85.8
90-100
130
10.3
62.0
7.0
2.6
36.4
75-85 470-490
55
12.7
76.3
4.1 18.6
90.3
100-110
70
12.5
74.7
3.2
6.8
63.8
75-85 200-220
35
9.6
57.3
4.3 13.3
72.0
75-85
85
12.1
72.6
4.0
5.3
59.0
75-85 270-290
40
10.2
61.2
4.4 13.9
76.2
80-90
35
100
11.7
70.4
5.0
4.1
54.0
75-85 340-360
80
45
10.8
64.9
4.4 14.8
79.9
85-95
115
11.4
68.3
6.0
3.3
47.5
80-90 410-430
50
11.5
68.7
4.5 15.3
84.1
95-105
130
11.0
66.1
7.1
2.7
41.0
80-90 480-500
55
12.1
72.3
4.6 15.7
88.0
100-110
70
13.3
79.8
3.3
7.1
68.5
80-90 200-220
35
9.1
54.5
4.8 11.4
70.9
75-85
85
12.9
77.6
4.1
5.5
63.6
80-90 270-290
40
9.7
58.0
4.9 11.9
74.8
85-95
40
100
12.5
75.2
5.0
4.4
59.2
85-95 345-365
90
45
10.2
61.5
4.9 12.6
78.2
90-100
115
12.1
72.8
6.1
3.5
52.7
85-95 415-435
50
10.8
65.0
5.0 13.0
82.1
95-105
130
11.7
70.1
7.1
2.9
45.5
90-100 485-505
55
11.4
68.6
5.1 13.5
86.0
100-110
70
15.1
90.6
3.4
7.8
79.0
90-100 200-220
35
8.8
53.0
5.3 10.0
71.1
80-90
85
14.5
87.2
4.2
6.1
72.9
95-105 275-295
40
9.4
56.3
5.4 10.4
74.7
85-95
50
100
14.0
84.1
5.1
4.8
68.9
95-105 350-370 100
45
10.0
59.9
5.5 10.9
78.6
90-100
115
13.5
81.1
6.2
3.8
61.8
100-110 430-450
50
10.6
63.3
5.5 11.5
82.1
95-105
130
12.9
77.7
7.3
3.1
54.0
100-110 508-575
55
11.1
66.9
5.6 11.9
86.8
100-110
** Water Flow Rate Correction Factors are listed on page 45
Note: Head Loss = Pressure drop in PSI x 2.31
*Earth Loop Pressure Drop for standard water coils only. Cupro-nickel water coils have higher pressure drops.
20
HEAD
PRESS
175-195
180-190
190-210
195-215
205-225
255-275
260-280
265-285
270-290
280-300
295-315
300-320
305-325
310-330
315-335
335-355
340-360
345-365
350-370
355-375
375-395
380-400
385-405
390-410
390-410
Performance Data – GeoSource Invision3 - Dual Circuit Models
QxxkWxT-DHW Domestic Hot Water Heating
Loop Loop
EWT GPM
6
20
6
6
6
25
6
6
6
30
6
6
6
35
6
6
6
45
6
6
6
50
6
6
6
60
6
6
6
70
6
6
6
75
6
6
6
80
6
6
dP
ft
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
dP DHW DHW
psi EWT GPM
2.1
50
6
2.1
80
6
2.1 110
6
2.1
50
6
2.1
80
6
2.1 110
6
2.1
50
6
2.1
80
6
2.1 110
6
2.1
50
6
2.1
80
6
2.1 110
6
2.1
50
6
2.1
80
6
2.1 110
6
2.1
50
6
2.1
80
6
2.1 110
6
2.1
50
6
2.1
80
6
2.1 110
6
2.1
50
6
2.1
80
6
2.1 110
6
2.1
50
6
2.1
80
6
2.1 110
6
2.1
50
6
2.1
80
6
2.1 110
6
dP
ft
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
dP
psi
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
Temp
Capacity
Rise MBTU/hr KW/hr
5.2
15.6
4.6
4.7
14.1
4.2
4.3
13.0
3.8
5.9
17.6
5.2
5.1
15.2
4.5
4.8
14.3
4.2
6.3
18.8
5.5
5.7
17.2
5.0
5.4
16.2
4.7
7.1
21.3
6.2
6.3
18.8
5.5
5.8
17.4
5.1
7.5
22.6
6.6
6.9
20.6
6.0
6.5
19.6
5.7
8.0
24.0
7.0
7.3
21.8
6.4
7.0
20.9
6.1
9.4
28.2
8.3
8.5
25.5
7.5
8.2
24.6
7.2
9.7
29.2
8.6
9.5
28.5
8.4
9.1
27.2
8.0
10.6
31.7
9.3
10.3
30.9
9.1
9.4
28.3
8.3
10.9
32.8
9.6
10.7
32.0
9.4
10.4
31.1
9.1
Compressor #2
Suct
Head
KW COP Press
Press
1.2 3.8 37-43 120-130
1.4 3.0 40-46 180-190
1.7 2.2 42-48 235-245
1.2 4.3 42-48 125-135
1.4 3.2 44-50 185-195
1.8 2.3 47-53 240-250
1.2 4.6 47-53 135-145
1.5 3.4 49-55 190-200
1.9 2.5 51-57 250-260
1.3 4.8 51-57 140-150
1.5 3.7 54-60 195-205
1.9 2.7 56-62 255-265
1.3 5.1 61-67 150-160
1.5 4.0 64-70 210-220
2.0 2.9 67-73 265-275
1.3 5.4 67-73 155-165
1.5 4.3 70-76 215-225
2.0 3.1 73-79 270-280
1.4 5.9 78-84 170-180
1.6 4.7 80-86 220-230
2.1 3.4 83-89 280-290
1.4 6.1 86-92 175-185
1.6 5.2 89-95 225-235
2.1 3.8 92-98 285-295
1.5 6.2 91-97 180-190
1.7 5.3 93-99 230-240
2.1 3.9 96-102 290-300
1.5 6.4 93-99 185-195
1.7 5.5 95-101 235-245
2.2 4.1 98-104 295-305
QxxkWxT-DWR Domestic Hot Water Heating
Loop Loop
EWT GPM
8
20
8
8
8
25
8
8
8
30
8
8
8
35
8
8
8
45
8
8
8
50
8
8
8
60
8
8
8
70
8
8
8
75
8
8
8
80
8
8
dP
ft
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
dP DWR DWR
psi EWT GPM
2.8
50
6
2.8
80
6
2.8 110
6
2.8
50
6
2.8
80
6
2.8 110
6
2.8
50
6
2.8
80
6
2.8 110
6
2.8
50
6
2.8
80
6
2.8 110
6
2.8
50
6
2.8
80
6
2.8 110
6
2.8
50
6
2.8
80
6
2.8 110
6
2.8
50
6
2.8
80
6
2.8 110
6
2.8
50
6
2.8
80
6
2.8 110
6
2.8
50
6
2.8
80
6
2.8 110
6
2.8
50
6
2.8
80
6
2.8 110
6
dP
ft
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
dP
psi
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
Temp
Capacity
Rise MBTU/hr KW/hr
8.0
24.0
7.0
7.2
21.5
6.3
6.6
19.9
5.8
9.0
27.0
7.9
7.9
23.8
7.0
7.7
23.0
6.7
10.2
30.5
8.9
8.8
26.5
7.8
8.6
25.7
7.5
10.6
31.9
9.3
9.6
28.8
8.4
9.2
27.6
8.1
12.3
36.8
10.8
11.5
34.5
10.1
11.0
32.9
9.6
13.2
39.6
11.6
12.6
37.8
11.1
12.0
36.0
10.6
15.3
45.9
13.5
14.4
43.1
12.6
13.8
41.5
12.2
16.7
50.2
14.7
16.1
48.2
14.1
15.3
45.9
13.5
17.7
53.1
15.6
16.7
50.2
14.7
15.8
47.4
13.9
18.0
54.0
15.9
17.3
51.9
15.2
16.8
50.3
14.7
Compressor #2
Suct
Head
KW COP Press
Press
1.8 3.9 31-37 140-150
2.2 2.9 32-38 195-205
2.6 2.2 34-40 255-265
1.8 4.4 35-41 150-160
2.2 3.2 37-43 205-215
2.7 2.5 39-45 265-275
1.9 4.7 39-45 155-165
2.3 3.4 41-47 200-210
2.7 2.8 43-49 270-280
1.9 4.9 44-50 165-175
2.3 3.7 46-52 215-225
2.8 2.9 48-54 275-285
2.0 5.4 54-60 175-185
2.5 4.0 56-62 225-235
2.8 3.4 58-64 285-295
2.0 5.8 59-65 185-195
2.5 4.4 62-68 230-240
2.9 3.6 64-70 290-300
2.1 6.4 72-78 200-210
2.5 5.0 75-81 245-255
3.0 4.1 78-84 305-315
2.1 7.0 81-87 210-220
2.6 5.4 84-90 255-265
3.0 4.5 87-93 315-325
2.2 7.1 83-89 215-225
2.6 5.7 88-94 260-270
3.1 4.5 91-97 320-330
2.2 7.2 85-91 220-230
2.6 5.9 92-98 265-275
3.2 4.6 96-102 325-335
21
Q14kW4T-000, -SUP, -DHW
Heating @ 70oF
First Stage @ 1050 cfm
Loop Loop
EWT GPM
6
15
7
8
6
20
7
8
6
25
7
8
6
30
7
8
6
35
7
8
5
45
6
7
5
50
6
7
5
60
6
7
5
70
6
7
dP
ft
5.1
5.8
6.7
5.1
5.8
6.7
5.1
5.8
6.7
5.1
5.8
6.7
5.1
5.8
6.7
4.4
5.1
5.8
4.4
5.1
5.8
4.4
5.1
5.8
4.4
5.1
5.8
dP
psi
2.2
2.5
2.9
2.2
2.5
2.9
2.2
2.5
2.9
2.2
2.5
2.9
2.2
2.5
2.9
1.9
2.2
2.5
1.9
2.2
2.5
1.9
2.2
2.5
1.9
2.2
2.5
Compressor #1
Suct
Head Loop dP
MBTU/hr KW COP Press
Press GPM ft
13.9
1.2 3.4 28-34 160-170 10
9.2
14.3
1.2 3.5 28-34 165-175 11 10.6
14.7
1.2 3.6 29-35 170-180 12 12.7
15.1
1.2 3.5 32-38 165-175 10
9.2
15.6
1.2 3.6 32-38 170-180 11 10.6
16.4
1.3 3.7 33-39 175-185 12 12.7
16.9
1.3 3.8 36-42 170-180 10
9.2
18.6
1.4 3.9 36-42 175-185 11 10.6
19.1
1.4 4.0 37-43 180-190 12 12.7
19.6
1.4 4.0 40-46 175-185 10
9.2
19.9
1.4 4.1 40-46 180-190 11 10.6
21.0
1.5 4.1 41-47 185-195 12 12.7
20.4
1.4 4.2 44-50 180-190 10
9.2
21.5
1.5 4.2 45-51 185-195 11 10.6
22.0
1.5 4.3 46-52 190-200 12 12.7
21.9
1.5 4.3 51-57 195-205
7
5.8
22.5
1.5 4.4 52-58 195-205
8
6.7
24.1
1.6 4.4 53-59 200-210 11 10.6
23.9
1.6 4.4 55-61 200-210
7
5.8
24.6
1.6 4.5 55-61 205-215
8
6.7
26.1
1.7 4.5 56-62 210-220 11 10.6
25.8
1.7 4.5 63-69 210-220
7
5.8
26.7
1.7 4.6 64-70 215-225
8
6.7
27.3
1.7 4.7 65-71 220-230 11 10.6
27.0
1.7 4.7 71-77 220-230
7
5.8
27.8
1.7 4.8 71-77 225-235
8
6.7
29.1
1.8 4.9 72-78 230-240 11 10.6
dP
psi
4.0
4.6
5.5
4.0
4.6
5.5
4.0
4.6
5.5
4.0
4.6
5.5
4.0
4.6
5.5
2.5
2.9
4.6
2.5
2.9
4.6
2.5
2.9
4.6
2.5
2.9
4.6
Second Stage @ 1675 cfm
Compressor #1
Suct
Head
MBTU/hr KW COP Press
Press
30.7
3.0 3.0 25-31 165-175
31.7
3.0 3.1 25-31 170-180
32.8
3.1 3.1 26-32 175-185
33.1
3.1 3.1 29-35 170-180
33.8
3.2 3.1 29-35 175-185
34.9
3.2 3.2 30-36 180-190
36.0
3.3 3.2 33-39 175-185
37.2
3.3 3.3 33-39 180-190
38.3
3.4 3.3 34-40 185-195
38.5
3.4 3.3 37-43 185-195
39.6
3.4 3.4 37-43 185-195
40.6
3.5 3.4 38-44 190-200
40.9
3.5 3.4 41-47 190-200
43.0
3.6 3.5 42-48 190-200
44.2
3.7 3.5 43-49 195-205
44.8
3.7 3.5 48-54 200-210
45.4
3.7 3.6 49-55 205-215
49.3
3.8 3.8 50-56 210-220
48.0
3.8 3.7 52-58 210-220
50.6
3.9 3.8 52-58 210-220
54.6
4.0 4.0 53-59 215-225
55.9
4.0 4.1 60-66 220-230
57.4
4.1 4.1 61-67 225-235
61.6
4.2 4.3 62-68 230-240
60.2
4.2 4.2 67-73 230-240
61.9
4.2 4.3 68-74 235-245
64.6
4.3 4.4 69-75 245-255
Compressor #2
Suct
Head
Press
Press
31-37 175-185
32-38 175-185
33-39 180-190
35-41 180-190
36-42 180-190
37-43 185-195
40-46 185-195
40-46 185-195
41-47 190-200
44-50 190-200
44-50 190-200
45-51 195-205
48-54 200-210
48-54 200-210
49-55 205-215
55-61 205-215
56-62 210-220
57-63 215-225
60-66 210-220
60-66 215-225
61-67 220-230
67-73 225-235
68-74 230-240
69-75 235-245
76-82 235-245
76-82 240-250
78-84 245-255
COOLING @ 80oF DB/67oF WB
First Stage @ 1050 cfm
Compressor #1
Loop Loop dP
dP
Suct
Head Loop dP
EWT GPM ft
psi MBTU/hr KW EER Press
Press GPM ft
5
4.4 1.9
27.1
1.1 24.6 53-59 125-135
7
5.8
40
6
5.1 2.2
27.9
1.1 25.4 53-59 125-135
8
6.7
7
5.8 2.5
28.8
1.0 28.4 52-58 120-130 11 10.6
5
4.4 1.9
26.5
1.2 22.1 55-61 140-150
7
5.8
50
6
5.1 2.2
27.4
1.2 22.8 55-61 140-150
8
6.7
7
5.8 2.5
28.0
1.1 25.4 54-60 135-145 11 10.6
5
4.4 1.9
26.1
1.3 20.1 58-64 155-165
7
5.8
60
6
5.1 2.2
26.8
1.3 20.6 58-64 155-165
8
6.7
7
5.8 2.5
27.5
1.2 21.1 57-63 150-160 11 10.6
5
4.4 1.9
25.7
1.4 18.4 60-66 170-180
7
5.8
70
6
5.1 2.2
26.3
1.4 18.8 60-66 170-180
8
6.7
7
5.8 2.5
26.8
1.4 19.1 59-65 165-175 11 10.6
6
5.1 2.2
25.2
1.4 18.0 61-67 175-185 10
9.2
75
7
5.8 2.5
25.9
1.4 18.5 61-67 170-180 11 10.6
8
6.7 2.9
26.3
1.4 18.8 60-66 170-180 12 12.7
6
5.1 2.2
24.5
1.5 16.3 62-68 180-190 10
9.2
80
7
5.8 2.5
25.1
1.5 16.7 62-68 175-185 11 10.6
8
6.7 2.9
25.7
1.5 17.1 61-67 175-185 12 12.7
6
5.1 2.2
24.0
1.5 15.4 64-70 190-200 10
9.2
85
7
5.8 2.5
24.4
1.6 15.9 63-69 185-195 11 10.6
8
6.7 2.9
25.0
1.6 16.2 62-68 185-195 12 12.7
6
5.1 2.2
23.4
1.6 14.2 65-71 195-205 10
9.2
90
7
5.8 2.5
23.9
1.6 14.9 64-70 190-200 11 10.6
8
6.7 2.9
24.5
1.7 15.3 63-69 190-200 12 12.7
6
5.1 2.2
22.8
1.7 13.4 67-73 205-215 10
9.2
95
7
5.8 2.5
23.3
1.7 13.7 66-72 200-210 11 10.6
8
6.7 2.9
24.9
1.7 14.6 65-71 200-210 12 12.7
* -DHW units do not have second stage cooling.
22
dP
psi
2.5
2.9
4.6
2.5
2.9
4.6
2.5
2.9
4.6
2.5
2.9
4.6
4.0
4.6
5.5
4.0
4.6
5.5
4.0
4.6
5.5
4.0
4.6
5.5
4.0
4.6
5.5
Second Stage @ 1675 cfm*
Compressor #1
Suct
Head
MBTU/hr KW EER Press
Press
53.1
2.4 22.1 49-55 115-125
54.4
2.4 22.7 49-55 115-125
56.5
2.3 23.9 48-54 110-120
51.4
2.6 19.8 51-57 130-140
52.7
2.6 20.3 51-57 130-140
54.3
2.5 21.5 50-56 125-135
48.3
2.8 17.3 56-62 145-155
49.6
2.8 17.7 55-61 140-150
51.1
2.7 18.9 54-60 135-145
46.7
3.0 15.6 58-64 160-170
48.1
3.0 16.0 57-63 160-170
49.8
2.9 17.2 56-62 155-165
47.8
3.1 15.4 59-65 165-175
48.8
3.2 15.7 59-65 165-175
49.9
3.2 16.0 58-64 160-170
46.3
3.2 14.3 60-66 170-180
47.5
3.3 14.5 60-66 170-180
48.4
3.3 14.7 59-65 165-175
45.1
3.3 13.5 61-67 180-190
46.7
3.4 13.7 61-67 175-185
47.5
3.4 14.0 60-66 175-185
43.9
3.4 12.9 63-69 190-200
45.0
3.5 12.9 62-68 185-195
45.8
3.6 13.0 61-67 185-195
42.8
3.5 12.0 64-70 200-210
43.7
3.6 12.2 64-70 195-205
44.9
3.7 12.5 62-68 190-200
Compressor #2
Suct
Head
Press
Press
53-59 130-140
53-59 130-140
52-58 125-135
55-61 145-155
54-60 140-150
53-59 135-145
58-64 155-165
57-63 155-165
56-62 150-160
60-66 170-180
60-66 170-180
59-65 165-175
62-68 175-185
61-67 175-185
61-67 170-180
63-69 180-190
62-68 180-190
62-68 175-185
64-70 190-200
63-69 190-200
63-69 185-195
66-72 200-210
65-71 200-210
64-70 195-205
68-74 215-225
68-74 210-220
67-73 205-215
Q14kW4T-DWR
Heating @ 70oF
First Stage @ 1050 cfm
Loop Loop
EWT GPM
6
15
7
8
6
20
7
8
6
25
7
8
6
30
7
8
6
35
7
8
5
45
6
7
5
50
6
7
5
60
6
7
5
70
6
7
dP
ft
5.1
5.8
6.7
5.1
5.8
6.7
5.1
5.8
6.7
5.1
5.8
6.7
5.1
5.8
6.7
4.4
5.1
5.8
4.4
5.1
5.8
4.4
5.1
5.8
4.4
5.1
5.8
dP
psi
2.2
2.5
2.9
2.2
2.5
2.9
2.2
2.5
2.9
2.2
2.5
2.9
2.2
2.5
2.9
1.9
2.2
2.5
1.9
2.2
2.5
1.9
2.2
2.5
1.9
2.2
2.5
Compressor #1
Suct
Head Loop dP
MBTU/hr KW COP Press
Press GPM ft
13.9
1.2 3.4 28-34 160-170 12 12.7
14.3
1.2 3.5 28-34 165-175 13 14.6
14.7
1.2 3.6 29-35 170-180 14 16.4
15.1
1.2 3.5 32-38 165-175 12 12.7
15.6
1.2 3.6 32-38 170-180 13 14.6
16.4
1.3 3.7 33-39 175-185 14 16.4
16.9
1.3 3.8 36-42 170-180 12 12.7
18.6
1.4 3.9 36-42 175-185 13 14.6
19.1
1.4 4.0 37-43 180-190 14 16.4
19.6
1.4 4.0 40-46 175-185 12 12.7
19.9
1.4 4.1 40-46 180-190 13 14.6
21.0
1.5 4.1 41-47 185-195 14 16.4
20.4
1.4 4.2 44-50 180-190 12 12.7
21.5
1.5 4.2 45-51 185-195 13 14.6
22.0
1.5 4.3 46-52 190-200 14 16.4
21.9
1.5 4.3 51-57 195-205
8
6.7
22.5
1.5 4.4 52-58 195-205
9
7.9
24.1
1.6 4.4 53-59 200-210 13 14.6
23.9
1.6 4.4 55-61 200-210
8
6.7
24.6
1.6 4.5 55-61 205-215
9
7.9
26.1
1.7 4.5 56-62 210-220 13 14.6
25.8
1.7 4.5 63-69 210-220
8
6.7
26.7
1.7 4.6 64-70 215-225
9
7.9
27.3
1.7 4.7 65-71 220-230 13 14.6
27.0
1.7 4.7 71-77 220-230
8
6.7
27.8
1.7 4.8 71-77 225-235
9
7.9
29.1
1.8 4.9 72-78 230-240 13 14.6
dP
psi
5.5
6.3
7.1
5.5
6.3
7.1
5.5
6.3
7.1
5.5
6.3
7.1
5.5
6.3
7.1
2.9
3.4
6.3
2.9
3.4
6.3
2.9
3.4
6.3
2.9
3.4
6.3
Second Stage @ 1675 cfm
Compressor #1
Suct
Head
MBTU/hr KW COP Press
Press
40.6
4.1 2.9 27-33 175-185
42.0
4.1 3.0 27-33 180-190
43.1
4.2 3.0 28-34 185-195
42.9
4.2 3.0 31-37 180-190
44.4
4.2 3.1 31-37 185-195
45.4
4.3 3.1 32-38 190-200
45.5
4.3 3.1 35-41 185-195
48.0
4.4 3.2 35-41 190-200
49.5
4.4 3.3 36-42 195-205
49.2
4.4 3.3 39-45 190-200
51.1
4.4 3.4 39-45 195-205
52.2
4.5 3.4 40-46 200-210
52.1
4.5 3.4 43-49 195-205
53.7
4.5 3.5 44-50 200-210
54.9
4.6 3.5 45-51 205-215
56.5
4.6 3.6 50-56 205-215
57.7
4.7 3.6 51-57 205-215
62.2
4.8 3.8 52-58 210-220
57.9
4.7 3.6 54-60 215-225
60.6
4.8 3.7 54-60 215-225
66.5
5.0 3.9 55-61 220-230
65.2
4.9 3.9 62-68 225-235
68.2
5.0 4.0 63-69 230-240
74.5
5.2 4.2 64-70 235-245
73.8
5.2 4.2 69-75 235-245
76.0
5.3 4.2 70-76 240-250
80.7
5.5 4.3 71-77 250-260
Compressor #2
Suct
Head
Press
Press
33-39 185-195
34-40 185-195
35-41 190-200
37-43 190-200
38-44 190-200
39-45 195-205
41-47 195-205
42-48 200-210
43-49 205-215
46-52 200-210
46-52 205-215
47-53 210-220
50-56 205-215
50-56 210-220
51-57 215-225
57-63 215-225
58-64 215-225
59-65 220-230
62-68 220-230
62-68 225-235
63-69 230-240
70-76 230-240
70-76 235-245
72-78 240-250
77-83 240-250
78-84 245-255
79-85 255-265
COOLING @ 80oF DB/67oF WB
First Stage @ 1050 cfm
Loop Loop
EWT GPM
5
40
6
7
5
50
6
7
5
60
6
7
5
70
6
7
6
75
7
8
6
80
7
8
6
85
7
8
6
90
7
8
6
95
7
8
dP
ft
4.4
5.1
5.8
4.4
5.1
5.8
4.4
5.1
5.8
4.4
5.1
5.8
5.1
5.8
6.7
5.1
5.8
6.7
5.1
5.8
6.7
5.1
5.8
6.7
5.1
5.8
6.7
dP
psi
1.9
2.2
2.5
1.9
2.2
2.5
1.9
2.2
2.5
1.9
2.2
2.5
2.2
2.5
2.9
2.2
2.5
2.9
2.2
2.5
2.9
2.2
2.5
2.9
2.2
2.5
2.9
Compressor #1
Suct
Head
MBTU/hr KW EER Press
Press
27.1
1.1 24.6 53-59 125-135
27.9
1.1 25.4 53-59 125-135
28.8
1.0 28.4 52-58 120-130
26.5
1.2 22.1 55-61 140-150
27.4
1.2 22.8 55-61 140-150
28.0
1.1 25.4 54-60 135-145
26.1
1.3 20.1 58-64 155-165
26.8
1.3 20.6 58-64 155-165
27.5
1.2 21.1 57-63 150-160
25.7
1.4 18.4 60-66 170-180
26.3
1.4 18.8 60-66 170-180
26.8
1.4 19.1 59-65 165-175
25.2
1.4 18.0 61-67 175-185
25.9
1.4 18.5 61-67 170-180
26.3
1.4 18.8 60-66 170-180
24.5
1.5 16.3 62-68 180-190
25.1
1.5 16.7 62-68 175-185
25.7
1.5 17.1 61-67 175-185
24.0
1.5 15.4 64-70 190-200
24.4
1.6 15.9 63-69 185-195
25.0
1.6 16.2 62-68 185-195
23.4
1.6 14.2 65-71 195-205
23.9
1.6 14.9 64-70 190-200
24.5
1.7 15.3 63-69 190-200
22.8
1.7 13.4 67-73 205-215
23.3
1.7 13.7 66-72 200-210
24.9
1.7 14.6 65-71 200-210
23
Q16kW5T-000, -SUP, -DHW
Heating @ 70oF
First Stage @ 1250 cfm
Loop Loop
EWT GPM
8
15
9
10
8
20
9
10
8
25
9
10
8
30
9
10
8
35
9
10
6
45
7
9
6
50
7
9
6
60
7
9
6
70
7
9
dP
ft
6.7
7.9
9.2
6.7
7.9
9.2
6.7
7.9
9.2
6.7
7.9
9.2
6.7
7.9
9.2
5.1
5.8
6.7
5.1
5.8
6.7
5.1
5.8
6.7
5.1
5.8
6.7
dP
psi
2.9
3.4
4.0
2.9
3.4
4.0
2.9
3.4
4.0
2.9
3.4
4.0
2.9
3.4
4.0
2.2
2.5
2.9
2.2
2.5
2.9
2.2
2.5
2.9
2.2
2.5
2.9
Compressor #1
Suct
Head Loop dP
MBTU/hr KW COP Press
Press GPM ft
21.8
2.0 3.2 30-36 170-180 12 12.7
22.5
2.0 3.3 31-37 175-185 13 14.6
24.4
2.1 3.4 32-38 180-190 14 16.4
25.1
2.1 3.5 34-40 175-185 12 12.7
25.8
2.1 3.6 35-41 180-190 13 14.6
27.0
2.2 3.6 36-42 185-195 14 16.4
27.7
2.2 3.7 38-44 180-190 12 12.7
28.5
2.2 3.8 39-45 185-195 13 14.6
29.8
2.3 3.8 40-46 190-200 14 16.4
30.6
2.3 3.9 43-49 185-195 12 12.7
32.8
2.4 4.0 44-50 190-200 13 14.6
33.8
2.4 4.0 45-51 195-205 14 16.4
33.2
2.4 4.0 47-53 195-205 12 12.7
34.0
2.4 4.1 48-54 200-210 13 14.6
35.0
2.5 4.1 49-55 200-210 14 16.4
35.0
2.5 4.1 55-61 210-220
8
6.7
35.8
2.5 4.2 55-61 210-220
9
7.9
37.3
2.6 4.2 56-62 215-225 13 14.6
36.1
2.5 4.2 59-65 215-225
8
6.7
38.1
2.6 4.3 59-65 215-225
9
7.9
39.2
2.6 4.4 60-66 220-230 13 14.6
38.2
2.6 4.3 67-73 225-235
8
6.7
39.0
2.7 4.4 67-73 225-235
9
7.9
44.0
2.8 4.6 68-74 230-240 13 14.6
40.5
2.7 4.4 74-80 235-245
8
6.7
43.0
2.8 4.5 75-81 235-245
9
7.9
48.1
3.0 4.7 76-82 240-250 13 14.6
dP
psi
5.5
6.3
7.1
5.5
6.3
7.1
5.5
6.3
7.1
5.5
6.3
7.1
5.5
6.3
7.1
2.9
3.4
6.3
2.9
3.4
6.3
2.9
3.4
6.3
2.9
3.4
6.3
Second Stage @ 1775 cfm
Compressor #1
Suct
Head
MBTU/hr KW COP Press
Press
39.6
4.0 2.9 27-33 165-175
40.6
4.1 2.9 27-33 170-180
42.0
4.1 3.0 28-34 175-185
43.4
4.1 3.1 31-37 170-180
44.4
4.2 3.1 31-37 175-185
45.9
4.2 3.2 32-38 180-190
47.3
4.2 3.3 35-41 175-185
48.7
4.2 3.4 35-41 180-190
50.0
4.3 3.4 36-42 185-195
51.4
4.3 3.5 40-46 180-190
53.0
4.3 3.6 40-46 185-195
54.1
4.4 3.6 41-47 190-200
55.7
4.5 3.6 44-50 190-200
57.1
4.5 3.7 44-50 195-205
58.2
4.6 3.7 45-51 195-205
59.3
4.7 3.7 51-57 205-215
62.0
4.8 3.8 51-57 205-215
65.5
4.8 4.0 52-58 210-220
64.8
5.0 3.8 54-60 210-220
66.1
5.1 3.8 55-61 210-220
72.8
5.2 4.1 56-62 215-225
69.2
5.2 3.9 62-68 220-230
71.0
5.2 4.0 63-69 220-230
76.0
5.3 4.2 64-70 225-235
73.7
5.4 4.0 70-76 230-240
77.0
5.5 4.1 71-77 230-240
84.1
5.6 4.4 72-78 235-245
Compressor #2
Suct
Head
Press
Press
35-41 190-200
36-42 195-205
37-43 200-210
40-46 200-210
41-47 205-215
42-48 210-220
44-50 205-215
45-51 210-220
46-52 215-225
48-54 210-220
49-55 215-225
50-56 220-230
52-58 215-225
53-59 220-230
54-60 225-235
61-67 230-240
61-67 230-240
63-69 235-245
67-73 240-250
67-73 240-250
69-75 245-255
79-85 250-260
80-86 255-265
81-87 260-270
91-97 270-280
92-98 270-280
93-99 275-285
COOLING @ 80oF DB/67oF WB
First Stage @ 1250 cfm
Compressor #1
Loop Loop dP
dP
Suct
Head Loop dP
EWT GPM ft
psi MBTU/hr KW EER Press
Press GPM ft
6
5.1 2.2
37.0
1.7 21.5 56-62 120-130
8
6.7
40
7
5.8 2.5
37.3
1.7 22.0 55-61 115-125
9
7.9
9
6.7 2.9
40.0
1.6 24.8 54-60 110-120 13 14.6
6
5.1 2.2
36.7
1.8 20.0 59-65 130-140
8
6.7
50
7
5.8 2.5
37.0
1.8 20.5 58-64 125-135
9
7.9
9
6.7 2.9
39.6
1.7 23.0 57-63 120-130 13 14.6
6
5.1 2.2
36.2
1.9 19.2 61-67 150-160
8
6.7
60
7
5.8 2.5
36.9
1.9 19.5 61-67 145-155
9
7.9
9
6.7 2.9
39.2
1.8 21.8 60-66 140-150 13 14.6
6
5.1 2.2
35.8
2.0 18.9 63-69 170-180
8
6.7
70
7
5.8 2.5
36.5
2.0 19.2 63-69 165-175
9
7.9
9
6.7 2.9
38.7
1.9 20.4 62-68 160-170 13 14.6
8
6.7 2.9
35.4
1.9 18.6 63-69 175-185 12 12.7
75
9
7.9 3.4
37.9
2.0 18.7 63-69 175-185 13 14.6
10
9.2 4.0
38.4
2.0 18.8 62-68 170-180 14 16.4
8
6.7 2.9
36.2
2.0 18.1 64-70 180-190 12 12.7
80
9
7.9 3.4
37.0
2.0 18.3 64-70 180-190 13 14.6
10
9.2 4.0
37.4
2.1 18.4 63-69 175-185 14 16.4
8
6.7 2.9
36.0
2.1 17.5 66-72 190-200 12 12.7
85
9
7.9 3.4
36.8
2.1 17.6 65-71 190-200 13 14.6
10
9.2 4.0
37.3
2.2 17.8 65-71 185-195 14 16.4
8
6.7 2.9
35.7
2.2 16.7 67-73 205-215 12 12.7
90
9
7.9 3.4
36.5
2.2 16.9 67-73 200-210 13 14.6
10
9.2 4.0
37.1
2.3 17.0 66-72 200-210 14 16.4
8
6.7 2.9
35.3
2.3 16.0 69-75 215-225 12 12.7
95
9
7.9 3.4
36.1
2.3 16.1 69-75 210-220 13 14.6
10
9.2 4.0
36.7
2.4 16.3 68-74 210-220 14 16.4
* –DHW units do not have second stage cooling.
24
dP
psi
2.9
3.4
6.3
2.9
3.4
6.3
2.9
3.4
6.3
2.9
3.4
6.3
5.5
6.3
7.1
5.5
6.3
7.1
5.5
6.3
7.1
5.5
6.3
7.1
5.5
6.3
7.1
Second Stage @ 1775 cfm*
Compressor #1
Suct
Head
MBTU/hr KW EER Press
Press
57.2
3.2 18.4 50-56 110-120
57.6
3.2 18.8 50-56 110-120
58.9
3.1 19.6 49-55 105-115
57.0
3.4 16.4 54-60 125-135
57.3
3.4 16.8 54-60 120-130
58.6
3.3 17.7 53-59 115-125
56.7
3.5 15.6 57-63 140-150
57.1
3.5 16.0 57-63 140-150
58.4
3.4 16.7 56-62 135-145
56.2
3.6 14.9 60-66 160-170
56.8
3.6 15.5 60-66 160-170
58.0
3.5 16.4 59-65 155-165
56.7
4.2 13.5 62-68 170-180
57.6
4.2 13.6 61-67 170-180
58.5
4.3 13.8 61-67 165-175
56.5
4.4 12.8 64-70 175-185
57.4
4.4 13.0 63-69 175-185
58.1
4.5 13.0 63-69 170-180
56.3
4.6 12.2 65-71 185-195
57.1
4.6 12.3 65-71 185-195
57.9
4.7 12.4 64-70 180-190
56.1
4.8 11.7 66-72 200-210
57.0
4.8 11.9 66-72 200-210
57.7
4.9 11.9 65-71 195-205
55.9
5.0 11.2 67-73 210-220
56.8
5.0 11.3 67-73 210-220
57.4
5.1 11.3 66-72 205-215
Compressor #2
Suct
Head
Press
Press
53-59 110-120
52-58 110-120
51-57 105-115
56-62 130-140
56-62 125-135
55-61 120-130
60-66 150-160
59-65 145-155
58-64 140-150
61-67 165-175
61-67 165-175
60-66 160-170
62-68 175-185
62-68 170-180
61-67 170-180
63-69 180-190
63-69 175-185
62-68 175-185
65-71 190-200
64-70 185-195
64-70 185-195
66-72 205-215
65-71 200-210
65-71 200-210
68-74 220-230
67-73 215-225
67-73 210-220
Q16kW5T-DWR
Heating @ 70oF
First Stage @ 1250 cfm
Loop Loop
EWT GPM
8
15
9
10
8
20
9
10
8
25
9
10
8
30
9
10
8
35
9
10
6
45
7
9
6
50
7
9
6
60
7
9
6
70
7
9
dP
ft
6.7
7.9
9.2
6.7
7.9
9.2
6.7
7.9
9.2
6.7
7.9
9.2
6.7
7.9
9.2
5.1
5.8
6.7
5.1
5.8
6.7
5.1
5.8
6.7
5.1
5.8
6.7
dP
psi
2.9
3.4
4.0
2.9
3.4
4.0
2.9
3.4
4.0
2.9
3.4
4.0
2.9
3.4
4.0
2.2
2.5
2.9
2.2
2.5
2.9
2.2
2.5
2.9
2.2
2.5
2.9
Compressor #1
Suct
Head Loop dP
MBTU/hr KW COP Press
Press GPM ft
21.8
2.0 3.2 30-36 170-180 13 14.6
22.5
2.0 3.3 31-37 175-185 14 16.4
24.4
2.1 3.4 32-38 180-190 15 18.5
25.1
2.1 3.5 34-40 175-185 13 14.6
25.8
2.1 3.6 35-41 180-190 14 16.4
27.0
2.2 3.6 36-42 185-195 15 18.5
27.7
2.2 3.7 38-44 180-190 13 14.6
28.5
2.2 3.8 39-45 185-195 14 16.4
29.8
2.3 3.8 40-46 190-200 15 18.5
30.6
2.3 3.9 43-49 185-195 13 14.6
32.8
2.4 4.0 44-50 190-200 14 16.4
33.8
2.4 4.0 45-51 195-205 15 18.5
33.2
2.4 4.0 47-53 195-205 13 14.6
34.0
2.4 4.1 48-54 200-210 14 16.4
35.0
2.5 4.1 49-55 200-210 15 18.5
35.0
2.5 4.1 55-61 210-220
9
7.9
35.8
2.5 4.2 55-61 210-220 10
9.2
37.3
2.6 4.2 56-62 215-225 14 10.6
36.1
2.5 4.2 59-65 215-225
9
7.9
38.1
2.6 4.3 59-65 215-225 10
9.2
39.2
2.6 4.4 60-66 220-230 14 10.6
38.2
2.6 4.3 67-73 225-235
9
7.9
39.0
2.7 4.4 67-73 225-235 10
9.2
44.0
2.8 4.6 68-74 230-240 14 10.6
40.5
2.7 4.4 74-80 235-245
9
7.9
43.0
2.8 4.5 75-81 235-245 10
9.2
48.1
3.0 4.7 76-82 240-250 14 10.6
dP
psi
6.3
7.1
8.0
6.3
7.1
8.0
6.3
7.1
8.0
6.3
7.1
8.0
6.3
7.1
8.0
3.4
4.0
4.6
3.4
4.0
4.6
3.4
4.0
4.6
3.4
4.0
4.6
Second Stage @ 1775 cfm
Compressor #1
Suct
Head
MBTU/hr KW COP Press
Press
48.1
4.9 2.9 30-36 175-185
49.7
4.9 3.0 30-36 180-190
50.9
5.0 3.0 31-37 185-195
52.8
5.0 3.1 33-39 180-190
53.9
5.1 3.1 34-40 185-195
55.1
5.1 3.2 35-41 190-200
57.8
5.1 3.3 37-43 185-195
59.1
5.2 3.3 38-44 190-200
60.7
5.3 3.4 39-45 195-205
60.8
5.2 3.4 42-48 190-200
62.2
5.3 3.4 42-48 195-205
63.9
5.4 3.5 43-49 200-210
63.9
5.4 3.5 46-52 205-215
65.8
5.4 3.6 46-52 205-215
67.4
5.5 3.6 47-53 210-220
66.9
5.5 3.6 54-60 215-225
68.8
5.6 3.6 54-60 215-225
74.4
5.7 3.8 55-61 220-230
72.0
5.7 3.7 58-64 220-230
75.2
5.8 3.8 58-64 220-230
79.8
6.0 3.9 59-65 225-235
79.1
6.1 3.8 65-71 230-240
80.4
6.2 3.8 66-72 230-240
87.3
6.4 4.0 67-73 235-245
86.5
6.5 3.9 73-79 240-250
90.1
6.6 4.0 74-80 240-250
93.7
6.7 4.1 75-81 245-255
Compressor #2
Suct
Head
Press
Press
34-40 190-200
35-41 190-200
36-42 195-205
39-45 200-210
40-46 205-215
41-47 210-220
43-49 205-215
44-50 210-220
45-51 215-225
47-53 215-225
48-54 215-225
49-55 220-230
51-57 220-230
52-58 225-235
53-59 225-235
60-66 235-245
60-66 235-245
61-67 240-250
65-71 240-250
65-71 245-255
66-72 250-260
71-77 250-260
72-78 255-265
73-79 260-270
80-86 265-275
81-87 270-280
82-88 275-285
COOLING @ 80oF DB/67oF WB
First Stage @ 1250 cfm
Loop Loop
EWT GPM
8
40
9
13
8
50
9
13
8
60
9
13
8
70
9
13
12
75
13
14
12
80
13
14
12
85
13
14
12
90
13
14
12
95
13
14
dP
ft
5.1
5.8
6.7
5.1
5.8
6.7
5.1
5.8
6.7
5.1
5.8
6.7
6.7
7.9
9.2
6.7
7.9
9.2
6.7
7.9
9.2
6.7
7.9
9.2
6.7
7.9
9.2
dP
psi
2.2
2.5
2.9
2.2
2.5
2.9
2.2
2.5
2.9
2.2
2.5
2.9
2.9
3.4
4.0
2.9
3.4
4.0
2.9
3.4
4.0
2.9
3.4
4.0
2.9
3.4
4.0
Compressor #1
Suct
Head
MBTU/hr KW EER Press
Press
37.0
1.7 21.5 56-62 120-130
37.3
1.7 22.0 55-61 115-125
40.0
1.6 24.8 54-60 110-120
36.7
1.8 20.0 59-65 130-140
37.0
1.8 20.5 58-64 125-135
39.6
1.7 23.0 57-63 120-130
36.2
1.9 19.2 61-67 150-160
36.9
1.9 19.5 61-67 145-155
39.2
1.8 21.8 60-66 140-150
35.8
2.0 18.9 63-69 170-180
36.5
2.0 19.2 63-69 165-175
38.7
1.9 20.4 62-68 160-170
35.4
1.9 18.6 63-69 175-185
37.9
2.0 18.7 63-69 175-185
38.4
2.0 18.8 62-68 170-180
36.2
2.0 18.1 64-70 180-190
37.0
2.0 18.3 64-70 180-190
37.4
2.1 18.4 63-69 175-185
36.0
2.1 17.5 66-72 190-200
36.8
2.1 17.6 65-71 190-200
37.3
2.2 17.8 65-71 185-195
35.7
2.2 16.7 67-73 205-215
36.5
2.2 16.9 67-73 200-210
37.1
2.3 17.0 66-72 200-210
35.3
2.3 16.0 69-75 215-225
36.1
2.3 16.1 69-75 210-220
36.7
2.4 16.3 68-74 210-220
25
Q18kW6T-000, -SUP, -DHW
Heating @ 70oF
First Stage @ 1600 cfm
Loop Loop
EWT GPM
9
15
10
11
9
20
10
11
9
25
10
11
9
30
10
11
9
35
10
11
7
45
8
10
7
50
8
10
7
60
8
10
7
70
8
10
dP
ft
7.4
8.8
10.2
7.4
8.8
10.2
7.4
8.8
10.2
7.4
8.8
10.2
7.4
8.8
10.2
5.5
6.5
8.8
5.5
6.5
8.8
5.5
6.5
8.8
5.5
6.5
8.8
dP
psi
3.2
3.8
4.4
3.2
3.8
4.4
3.2
3.8
4.4
3.2
3.8
4.4
3.2
3.8
4.4
2.4
2.8
3.8
2.4
2.8
3.8
2.4
2.8
3.8
2.4
2.8
3.8
Compressor #1
Suct
Head Loop dP
MBTU/hr KW COP Press
Press GPM ft
30.6
3.1 2.9 27-33 175-185 13 13.9
31.7
3.1 3.0 28-34 180-190 14 15.7
32.8
3.2 3.0 29-35 180-190 15 17.6
34.8
3.3 3.1 32-38 180-190 13 13.9
35.9
3.3 3.2 32-38 185-195 14 15.7
36.9
3.4 3.2 33-39 185-195 15 17.6
38.3
3.4 3.3 36-42 190-200 13 13.9
39.4
3.5 3.3 36-42 195-205 14 15.7
40.6
3.5 3.4 37-43 195-205 15 17.6
41.8
3.6 3.4 40-46 195-205 13 13.9
43.0
3.6 3.5 41-47 200-210 14 15.7
45.1
3.7 3.5 41-47 200-210 15 17.6
44.1
3.7 3.6 43-49 200-210 13 13.9
45.3
3.8 3.6 44-50 205-215 14 15.7
46.9
3.8 3.7 45-51 205-215 15 17.6
48.7
3.9 3.7 52-58 220-230
9
7.4
50.1
3.9 3.8 53-59 220-230 10
8.8
53.2
4.0 3.9 54-60 225-235 15 17.6
53.1
4.1 3.8 57-63 230-240
9
7.4
54.4
4.2 3.8 58-64 230-240 10
8.8
57.3
4.2 4.0 59-65 235-245 15 17.6
57.2
4.3 3.9 65-71 245-255
9
7.4
60.1
4.4 4.0 66-72 245-255 10
8.8
61.6
4.4 4.1 67-73 250-260 15 17.6
61.4
4.5 4.0 74-80 255-265
9
7.4
62.8
4.6 4.0 74-80 255-265 10
8.8
67.4
4.7 4.2 75-81 260-270 15 17.6
dP
psi
6.0
6.8
7.6
6.0
6.8
7.6
6.0
6.8
7.6
6.0
6.8
7.6
6.0
6.8
7.6
3.2
3.8
7.6
3.2
3.8
7.6
3.2
3.8
7.6
3.2
3.8
7.6
Second Stage @ 1920 cfm
Compressor #1
Suct
Head
MBTU/hr KW COP Press
Press
47.8
5.0 2.8 24-30 195-205
50.5
5.1 2.9 24-30 200-210
52.2
5.1 3.0 25-31 200-210
52.2
5.1 3.0 28-34 200-210
53.2
5.2 3.0 29-35 205-215
55.1
5.2 3.1 30-36 205-215
55.2
5.2 3.1 33-39 205-215
56.1
5.3 3.1 33-39 210-220
58.1
5.3 3.2 34-40 210-220
57.9
5.3 3.2 37-43 210-220
59.0
5.4 3.2 37-43 215-225
60.8
5.4 3.3 38-44 215-225
62.0
5.5 3.3 41-47 220-230
63.1
5.6 3.3 41-47 225-235
64.9
5.6 3.4 42-48 225-235
63.4
5.6 3.3 49-55 240-250
65.2
5.7 3.3 49-55 240-250
69.4
5.9 3.4 50-56 245-255
67.3
5.8 3.4 53-59 250-260
70.5
5.9 3.5 54-60 250-260
75.1
6.1 3.6 55-61 255-265
76.1
6.2 3.6 61-67 270-280
77.4
6.3 3.6 62-68 270-280
83.0
6.4 3.8 63-69 275-285
82.1
6.5 3.7 69-75 285-295
85.6
6.6 3.8 70-76 285-295
89.2
6.7 3.9 71-77 290-300
Compressor #2
Suct
Head
Press
Press
36-42 200-210
36-42 205-215
37-43 205-215
40-46 205-215
40-46 210-220
41-47 210-220
45-51 210-220
45-51 215-225
46-52 215-225
49-55 215-225
49-55 220-230
50-56 220-230
53-59 225-235
53-59 230-240
54-60 230-240
64-70 245-255
64-70 245-255
65-71 250-260
69-75 255-265
69-75 255-265
70-76 260-270
79-85 275-285
79-85 275-285
80-86 280-290
88-94 290-300
88-94 290-300
89-95 295-305
COOLING @ 80oF DB/67oF WB
First Stage @ 1600 cfm
Compressor #1
Loop Loop dP
dP
Suct
Head Loop dP
EWT GPM ft
psi MBTU/hr KW EER Press
Press GPM ft
7
5.5 2.4
50.8
2.5 20.3 46-52 110-120
9
7.4
40
8
6.5 2.8
52.7
2.5 21.1 46-52 110-120 10
8.8
10
8.8 3.8
54.0
2.4 22.5 45-51 105-115 15 17.6
7
5.5 2.4
48.6
2.6 18.7 48-54 125-135
9
7.4
50
8
6.5 2.8
50.4
2.6 19.4 48-54 125-135 10
8.8
10
8.8 3.8
51.1
2.5 20.4 47-53 120-130 15 17.6
7
5.5 2.4
47.6
2.7 17.8 49-55 145-155
9
7.4
60
8
6.5 2.8
48.7
2.7 18.3 49-55 140-150 10
8.8
10
8.8 3.8
49.2
2.6 19.3 48-54 135-145 15 17.6
7
5.5 2.4
46.3
2.8 16.6 51-57 165-175
9
7.4
70
8
6.5 2.8
47.2
2.8 17.2 51-57 160-170 10
8.8
10
8.8 3.8
48.3
2.7 18.1 50-56 155-165 15 17.6
9
7.4 3.2
43.8
2.9 15.1 52-58 170-180 13 13.9
75
10
8.8 3.8
45.6
3.0 15.8 52-58 165-175 14 15.7
11 10.2 4.4
47.2
3.0 16.7 51-57 165-175 15 17.6
9
7.4 3.2
42.5
3.1 13.7 53-59 180-190 13 13.9
80
10
8.8 3.8
44.5
3.1 14.4 53-59 175-185 14 15.7
11 10.2 4.4
46.6
3.2 15.2 52-58 175-185 15 17.6
9
7.4 3.2
41.7
3.3 12.6 54-60 190-200 13 13.9
85
10
8.8 3.8
43.1
3.3 13.2 54-60 185-195 14 15.7
11 10.2 4.4
45.2
3.4 13.9 53-59 185-195 15 17.6
9
7.4 3.2
39.3
3.5 11.4 55-61 200-210 13 13.9
90
10
8.8 3.8
42.4
3.5 12.3 55-61 195-205 14 15.7
11 10.2 4.4
44.2
3.6 12.7 54-60 195-205 15 17.6
9
7.4 3.2
38.9
3.6 11.2 56-62 210-220 13 13.9
95
10
8.8 3.8
41.3
3.6 11.5 56-62 205-215 14 15.7
11 10.2 4.4
43.8
3.7 11.9 55-61 205-215 15 17.6
* -DHW units do not have second stage cooling.
26
dP
psi
3.2
3.8
7.6
3.2
3.8
7.6
3.2
3.8
7.6
3.2
3.8
7.6
6.0
6.8
7.6
6.0
6.8
7.6
6.0
6.8
7.6
6.0
6.8
7.6
6.0
6.8
7.6
Second Stage @ 1920 cfm*
Compressor #1
Suct
Head
MBTU/hr KW EER Press
Press
66.5
4.2 15.8 42-48 100-110
68.3
4.2 16.3 42-48 100-110
70.9
4.1 17.3 41-47 95-105
66.2
4.5 14.7 45-51 115-125
67.7
4.5 15.1 45-51 115-125
70.4
4.4 16.0 44-50 110-120
65.2
4.9 13.3 47-53 135-145
67.1
4.9 13.7 47-53 130-140
70.0
4.7 14.9 46-52 130-140
62.0
5.0 12.4 49-55 155-165
63.5
5.0 12.7 49-55 150-160
67.2
4.9 13.8 48-54 150-160
64.3
5.1 12.6 50-56 165-175
64.7
5.1 12.7 50-56 160-170
66.5
5.2 12.8 49-55 160-170
63.4
5.2 12.2 51-57 175-185
64.0
5.2 12.3 51-57 170-180
65.7
5.3 12.4 50-56 170-180
61.8
5.3 11.5 53-59 185-195
63.2
5.4 11.7 53-59 180-190
64.9
5.5 11.8 52-58 180-190
61.0
5.5 11.1 54-60 195-205
61.8
5.5 11.2 54-60 190-200
63.8
5.6 11.4 53-59 190-200
60.4
5.7 10.6 55-61 205-215
61.3
5.7 10.8 55-61 200-210
63.2
5.8 10.9 54-60 200-210
Compressor #2
Suct
Head
Press
Press
49-55 105-115
48-54 105-115
47-53 100-110
51-57 120-130
50-56 120-130
49-55 115-125
53-59 140-150
53-59 140-150
52-58 135-145
56-62 160-170
56-62 155-165
55-61 155-165
57-63 170-180
57-63 165-175
56-62 165-175
58-64 180-190
58-64 175-185
57-63 175-185
60-66 195-205
60-66 190-200
59-65 190-200
61-67 205-215
61-67 200-210
60-66 200-210
63-69 215-225
63-69 215-225
62-68 210-220
Q18kW6T-DWR
Heating @ 70oF
First Stage @ 1600 cfm
Loop Loop
EWT GPM
9
15
10
11
9
20
10
11
9
25
10
11
9
30
10
11
9
35
10
11
7
45
8
10
7
50
8
10
7
60
8
10
7
70
8
10
dP
ft
7.4
8.8
10.2
7.4
8.8
10.2
7.4
8.8
10.2
7.4
8.8
10.2
7.4
8.8
10.2
5.5
6.5
8.8
5.5
6.5
8.8
5.5
6.5
8.8
5.5
6.5
8.8
dP
psi
3.2
3.8
4.4
3.2
3.8
4.4
3.2
3.8
4.4
3.2
3.8
4.4
3.2
3.8
4.4
2.4
2.8
3.8
2.4
2.8
3.8
2.4
2.8
3.8
2.4
2.8
3.8
Compressor #1
Suct
Head Loop dP
MBTU/hr KW COP Press
Press GPM ft
30.6
3.1 2.9 27-33 175-185 14 15.7
31.7
3.1 3.0 28-34 180-190 15 17.6
32.8
3.2 3.0 29-35 180-190 16 19.9
34.8
3.3 3.1 32-38 180-190 14 15.7
35.9
3.3 3.2 32-38 185-195 15 17.6
36.9
3.4 3.2 33-39 185-195 16 19.9
38.3
3.4 3.3 36-42 190-200 14 15.7
39.4
3.5 3.3 36-42 195-205 15 17.6
40.6
3.5 3.4 37-43 195-205 16 19.9
41.8
3.6 3.4 40-46 195-205 14 15.7
43.0
3.6 3.5 41-47 200-210 15 17.6
45.1
3.7 3.5 41-47 200-210 16 19.9
44.1
3.7 3.6 43-49 200-210 14 15.7
45.3
3.8 3.6 44-50 205-215 15 17.6
46.9
3.8 3.7 45-51 205-215 16 19.9
48.7
3.9 3.7 52-58 220-230 10
8.8
50.1
3.9 3.8 53-59 220-230 11 10.2
53.2
4.0 3.9 54-60 225-235 15 17.6
53.1
4.1 3.8 57-63 230-240 10
8.8
54.4
4.2 3.8 58-64 230-240 11 10.2
57.3
4.2 4.0 59-65 235-245 15 17.6
57.2
4.3 3.9 65-71 245-255 10
8.8
60.1
4.4 4.0 66-72 245-255 11 10.2
61.6
4.4 4.1 67-73 250-260 15 17.6
61.4
4.5 4.0 74-80 255-265 10
8.8
62.8
4.6 4.0 74-80 255-265 11 10.2
67.4
4.7 4.2 75-81 260-270 15 17.6
dP
psi
6.8
7.6
8.6
6.8
7.6
8.6
6.8
7.6
8.6
6.8
7.6
8.6
6.8
7.6
8.6
3.8
4.4
7.6
3.8
4.4
7.6
3.8
4.4
7.6
3.8
4.4
7.6
Second Stage @ 1920 cfm
Compressor #1
Suct
Head
MBTU/hr KW COP Press
Press
53.4
5.8 2.7 26-32 200-210
56.4
5.9 2.8 27-33 205-215
59.4
6.0 2.9 28-34 205-215
57.3
6.0 2.8 31-37 205-215
60.4
6.1 2.9 31-37 210-220
62.5
6.1 3.0 32-38 210-220
60.1
6.1 2.9 35-41 210-220
63.3
6.2 3.0 35-41 215-225
65.6
6.2 3.1 36-42 215-225
62.9
6.2 3.0 39-45 215-225
66.5
6.3 3.1 39-45 220-230
69.9
6.4 3.2 40-46 220-230
70.7
6.5 3.2 43-49 220-230
72.1
6.6 3.2 43-49 225-235
74.3
6.6 3.3 44-50 225-235
76.6
6.8 3.3 51-57 240-250
78.9
6.8 3.4 51-57 245-255
80.0
6.9 3.4 52-58 250-260
82.4
7.1 3.4 55-61 250-260
84.8
7.1 3.5 56-62 255-265
85.9
7.2 3.5 57-63 260-270
89.6
7.5 3.5 64-70 270-280
90.6
7.6 3.5 65-71 275-285
95.9
7.6 3.7 66-72 280-290
98.5
7.8 3.7 73-79 290-300
101.1
7.8 3.8 73-79 295-305
105.1
7.9 3.9 74-80 300-310
Compressor #2
Suct
Head
Press
Press
30-36 205-215
30-36 210-220
31-37 210-220
35-41 210-220
35-41 215-225
36-42 215-225
39-45 215-225
39-45 220-230
40-46 220-230
43-49 220-230
43-49 225-235
44-50 225-235
47-53 225-235
48-54 230-240
48-54 230-240
54-60 245-255
55-61 250-260
56-62 255-265
58-64 255-265
59-65 260-270
60-66 265-275
68-74 275-285
69-75 280-290
71-77 285-295
78-84 295-305
79-85 300-310
81-87 305-315
COOLING @ 80oF DB/67oF WB
First Stage @ 1600 cfm
Loop Loop
EWT GPM
7
40
8
10
7
50
8
10
7
60
8
10
7
70
8
10
9
75
10
11
9
80
10
11
9
85
10
11
9
90
10
11
9
95
10
11
dP
ft
5.5
6.5
8.8
5.5
6.5
8.8
5.5
6.5
8.8
5.5
6.5
8.8
7.4
8.8
10.2
7.4
8.8
10.2
7.4
8.8
10.2
7.4
8.8
10.2
7.4
8.8
10.2
dP
psi
2.4
2.8
3.8
2.4
2.8
3.8
2.4
2.8
3.8
2.4
2.8
3.8
3.2
3.8
4.4
3.2
3.8
4.4
3.2
3.8
4.4
3.2
3.8
4.4
3.2
3.8
4.4
Compressor #1
Suct
Head
MBTU/hr KW EER Press
Press
50.8
2.5 20.3 46-52 110-120
52.7
2.5 21.1 46-52 110-120
54.0
2.4 22.5 45-51 105-115
48.6
2.6 18.7 48-54 125-135
50.4
2.6 19.4 48-54 125-135
51.1
2.5 20.4 47-53 120-130
47.6
2.7 17.8 49-55 145-155
48.7
2.7 18.3 49-55 140-150
49.2
2.6 19.3 48-54 135-145
46.3
2.8 16.6 51-57 165-175
47.2
2.8 17.2 51-57 160-170
48.3
2.7 18.1 50-56 155-165
43.8
2.9 15.1 52-58 170-180
45.6
3.0 15.8 52-58 165-175
47.2
3.0 16.7 51-57 165-175
42.5
3.1 13.7 53-59 180-190
44.5
3.1 14.4 53-59 175-185
46.6
3.2 15.2 52-58 175-185
41.7
3.3 12.6 54-60 190-200
43.1
3.3 13.2 54-60 185-195
45.2
3.4 13.9 53-59 185-195
39.3
3.5 11.4 55-61 200-210
42.4
3.5 12.3 55-61 195-205
44.2
3.6 12.7 54-60 195-205
38.9
3.6 11.2 56-62 210-220
41.3
3.6 11.5 56-62 205-215
43.8
3.7 11.9 55-61 205-215
27
Fan Performance Data
GeoSource 2000, GeoSource DualTEK† (-Dx0x)
UNIT
SIZE
GV/GH/180/181
GV/GH/230/231
GV/GH/290/291
GV/GH/360/361
GV/GH/420/421
GV/GH/520/521
GV/GH/590/591
GV/GH/670/671
GH980
GH1200
FAN
SPEED
Low
Medium
High*
Low
Medium
High*
Low
Medium
High*
Low
Medium*
High
Low
Medium
High*
Low
Medium
High*
Low
Medium
High*
Low
Medium*
High
Low
Medium
High*
Low
Medium
High*
External Static Pressure - in WG
0.10
0.15
0.20
0.25
0.30
0.35
550
520
490
460
445
430
610
580
550
530
510
480
675
650
625
600
580
560
760
710
680
650
625
600
860
800
775
750
735
710
950
900
870
855
830
800
870
825
800
775
750
735
980
935
900
870
845
830
1090
1050
1000
965
940
920
1005
965
935
890
855
815
1140
1100
1065
1010
965
935
1210
1150
1110
1070
1030
985
1005
965
935
890
855
815
1140
1100
1065
1010
965
935
1210
1150
1110
1070
1030
985
1325
1275
1235
1200
1165
1135
1505
1450
1415
1375
1320
1275
1685
1625
1550
1500
1435
1405
1500
1450
1410
1360
1325
1310
1700
1645
1595
1555
1500
1480
1900
1850
1800
1740
1680
1625
1900
1850
1800
1750
1690
1660
2220
2185
2150
2110
2050
2000
2410
2370
2325
2250
2200
2150
2510
2390
2270
2200
2110
2070
2840
2720
2600
2520
2430
2380
3040
2920
2800
2730
2640
2590
3020
2940
2860
2780
2710
2650
3220
3140
3060
2970
2900
2890
3530
3430
3340
3260
3170
3100
*Denotes factory setting
0.40
410
460
525
580
650
760
710
800
865
805
915
960
805
915
960
1105
1245
1360
1250
1410
1590
1600
1960
2110
2030
2330
2550
2600
2800
3040
0.50
385
440
480
560
590
720
650
760
840
740
840
895
740
840
895
1055
1185
1305
1210
1380
1510
1560
1880
2030
1980
2280
2480
2550
2710
2960
GeoSource Vara, GeoSource Vara 2 Plus, GeoSource DualTEK† (-DxVx)
UNIT SIZE
GV/GH/360/361
GV/GH/480/481
GV/GH/520/521
GV/GH/580/581
GV/GH/590/591
GV/GH/670/671
Low (G)
485
740
680
815
790
845
Medium (Y, Y1)
1100
1295
1550
1425
1800
1920
Medium-High (Y2)
N/A
1680
N/A
1850
N/A
N/A
High (W1, W2, E)
1210
1800
1705
1920
1920
2000
GeoSource Invision3 - Dual Circuit
Fan Speed
Range
High
Fan
Medium
Fan
Low
Fan
Speed
Tap
A
B
C
D
A
B
C
D
A
B
C
D
CFM
1920
1850
1775
1675
1600
1450
1250
1050
950
800
650
500
Q14kW4T
Factory Humidistat
Setting
Added
Q16kW5T
Factory Humidistat
Setting
Added
Q18kW6T
Factory Humidistat
Setting
Added
Y2
Y2
Y2
Y1
Y1
Y1
Y2
Y2
Y2
Y1/G*
Y1/G*
G
Y1/G*
G
G
*To add Humidistat, manually move Low FAN CFM to indicated tap.
28
Physical Dimensions – GeoSource 2000 Vertical Models
Standard (Top-Discharge Left-Hand Return)
(-TOxx)
C
A
E
B
Air Filter is on righthand side on Right-Hand
Return Model (-TRxx)
(Top Loading)
F
7.0”
G
3.0”
Access Panels
0.88” Dia. Knockouts
H
In (from earth loop)
Condensate Drain
Out (to earth loop)
0.88” Dia. Knockout
Desuperheater Outlet
Desuperheater Inlet
D
W
Option B (Bottom-Discharge Right-Hand Return)
(-TBxx) – 23 Through 52 Series
26.1”
27.0”
Desuperheater Inlet
Desuperheater Outlet
Out (to earth loop)
Access Panels
53.1”
In (from earth loop)
Air Filter
20” x 25”
(Front Loading)
24.7”
0.88” Dia.
Knockouts
3.75”
2.31”
Condensate Drain
19.75”
10.3”
8.4”
Model
GV18x-x-T(O,R)xx
GV23x-x-T(O,R)xx
GV29x-x-T(O,R)xx
GV36x-x-T(O,R)xx
GV42x-x-T(O,R)xx
GV52x-x-T(O,R)xx
GV59x-x-T(O,R)xx
GV67x-x-T(O,R)xx
12.0”
Top-Discharge
Dimensions
H
W
D
38.2 19.0 24.0
46.1 21.0 26.1
46.1 21.0 26.1
46.1 21.0 26.1
46.1 21.0 26.1
46.1 21.0 26.1
53.1 21.0 26.1
53.1 21.0 26.1
7.1”
Blower
Opening
A
B
9.38 10.25
12.00 10.25
12.00 10.25
12.00 10.25
12.00 10.25
12.00 10.25
12.00 10.25
12.44 13.44
Inlets
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
Outlets
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
Cond.
Drain
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
Filter
Size
20 x 20
20 x 22
20 x 22
20 x 22
20 x 22
20 x 22
21 x 29
21 x 29
C
0.59
0.59
0.59
0.59
0.59
0.59
0.59
0.59
Other
Dimensions
E
F
19.88 0.88
19.88 0.75
19.88 0.75
19.88 0.75
19.88 0.75
19.88 0.75
21.88 2.19
21.88 2.19
G
18.0
22.0
22.0
22.0
22.0
22.0
27.56
27.56
29
Physical Dimensions – GeoSource 2000, GeoSource DualTEK†, GeoSource Vara,
GeoSource Vara 2 Plus Horizontal Models
Standard (Right-Hand Discharge Rear Return)
(-xOxx)
Air Filter
(Side Loading)
0.88” Dia.
Knockouts
E
D
Hydronic Outlet
(DualTEK)
Hydronic Inlet
(DualTEK)
In (from earth
Loop)
J
H
C
Out (to earth loop
I
K
B
Desuperheater
Outlet
Desuperheater
Inlet
L
W
A
0.88” Dia. Knockout
Option C (Front-Right Discharge Rear Return)
(-xCxx)
Air Filter
(Side Loading)
0.88” Dia.
Knockouts
D
Hydronic Outlet
(DualTEK)
W
H
J
Hydronic Inlet
(DualTEK
In (from earth
Loop)
I
Out (to earth loop
Desuperheater
Outlet
Desuperheater
Inlet
K
L
B
A
0.88” Dia. Knockout
F
Model
GH18x-x-xxxx
GH23x-x-xxxx
GH29x-x-xxxx
GH36x-x-xxxx
GH38x-x-Vx2x
GH42x-x-xxxx
GH48x-x-Vx2x
GH52x-x-xxxx
GH58x-x-Vx2x
GH59x-x-xxxx
GH67x-x-xxxx
GH980-x-xxxx
GH1200x-x-xxxx
Dimensions Blower Opening**
H* W
D
A
B
21.0 46.1 26.1
9.38
10.25
21.0 46.1 26.1
9.38
10.25
21.0 46.1 26.1
9.38
10.25
21.0 46.1 26.1 12.00
10.25
29.0 46.1 26.1 10.25
12.00
21.0 46.1 26.1 12.00
10.25
29.0 46.1 26.1 10.25
12.00
21.0 46.1 26.1 10.69
11.38
29.0 46.1 26.1 10.25
12.00
29.0 46.1 26.1 10.25
12.00
29.0 46.1 26.1 12.44
13.44
30.0 60.0 37.0 10.69
11.38
30.0 60.0 37.0 10.69
11.38
G
Inlets
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
1.25 FPT
1.25 FPT
Outlets
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
1.25 FPT
1.25 FPT
Cond.
Drain
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
Filter
Size
20 x 20
20 x 22
20 x 22
20 x 22
21 x 29
20 x 22
21 x 29
20 x 22
21 x 29
21 x 29
21 x 29
29 x 34
29 x 34
C
2.0
2.0
2.0
2.0
10.0
2.0
10.0
2.0
10.0
10.0
7.0
3.63
3.63
E
9.0
9.0
9.0
9.0
13.25
9.0
13.25
9.0
13.25
13.25
9.0
7.81
7.81
Other Dimensions
F
G
I
J
7.63 2.0 0.5 20.0
7.63 2.0 0.5 20.0
7.63 2.0 0.5 20.0
5.0 2.0 0.5 20.0
5.0 6.0 0.0 29.0
5.0 2.0 0.5 20.0
5.0 6.0 0.0 29.0
5.0 2.0 0.5 20.0
5.0 6.0 0.0 29.0
5.0 6.0 0.0 29.0
4.0 5.0 0.0 29.0
7.0 3.31 0.5 29.0
7.0 3.31 0.5 29.0
*GH180’s through GH670’s have a 1-1/2” support rail, GH980’s and GH1200’s have a 2” support rail. These heights are in addition to the listed height.
**GH980’s and GH1200’s have two blower openings
30
K
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
1.25
1.25
L
19.5
21.5
21.5
21.5
21.5
21.5
21.5
21.5
21.5
21.5
21.5
32.0
32.0
Physical Dimensions – GeoSource 2000 Console Models
GC 180-420
Supply Air
8”
48”
Mounting
Holes
Return Air,
Filter Access
20”
16”
39”
3.75”
20”
9”
19.75”
32”
3.25”
60”
Access
Panel
12”
10.75”
0.75”
1”
5.5”
Model
GC180-x-Txxx
GC230-x-Txxx
GC290-x-Txxx
GC360-x-Txxx
GC420-x-Txxx
Inlets
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
Outlets
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
Cond.
Drain
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
Filter
Size
20 x 20
20 x 20
20 x 20
20 x 20
20 x 20
Electrical Data – Console Units
Voltage Compressor
Model (60 Hz) RLA LRA
180
208/230-1 10.7 45.0
208/230-1 12.1 54.0
45.0
230
208/230-3 7.9
3.9
22.4
460-3
208/230-1 15.0 72.5
290
208/230-3 10.0 63.0
5.0
31.0
460-3
360
208/230-1 17.9 88.0
208/230-3 11.4 77.0
420
208/230-1 20.4 109.0
208/230-3 13.9 88.0
Fan
FLA LRA
3.4
-3.4
-0.6
-0.6
-3.4
-0.6
-0.6
-3.4
-0.6
-5.2
-1.2
--
Without PumpPAK
Total
Min. Max Fuse/
FLA Ampac. Ckt Bkr*
14.1
16.8
25
15.5
18.5
30
8.5
10.5
15
4.5
5.8
10
18.4
22.2
35
10.6
13.1
20
5.6
6.9
10
21.3
25.8
40
12.0
14.9
25
25.6
30.7
50
14.2
18.6
30
NOTE: 208/230V Console Units REQUIRE a Neutral Connection
31
Physical Dimensions – GeoSource 2000, GeoSource Ultra Hydronic Models
GW 23 Through 77 Series
21.0”
Out (to hydronic)
26.1”
In (from hydronic)
0.88” Dia. Knockouts
27.5”
In (from earth loop)
Out (to earth loop)
Desuperheater Outlet
Desuperheater Inlet
Access Panel
GW 980, 1200 Series
26.1”
21.0”
0.88” Dia. Knockouts
Out (to hydronic)
Out (to earth loop)
27.5”
In (from earth loop)
In (from hydronic)
Access Panel
GW 3800
30”
42”
Out (to hydronic)
Out (to earth loop)
0.88” Dia. Knockouts
In (from hydronic)
51”
In (from earth loop)
Access Panel
Model
GW(29-77)x-x-Txxx
GW(98-120)0-x-Txxx
GW3800-x-Txxx
32
Inlets
0.75 FPT
1.25 MPT
2.0 MPT
Outlets
0.75 FPT
1.25 MPT
2.0 MPT
Physical Dimensions – GeoSource Invision3 - Dual Circuit,
GeoSource DualTEK†, GeoSource Vara, GeoSource Vara 2 Plus Vertical Models
C
B
A
E
Air Filter
(Front Loading –
Invision3, Top
Loading –
DualTEK)
F
I
J
G
Access Panels
53.1”
In (from earth loop)
Hydronic,
DHW Inlet
Out (to earth loop)
Hydronic,
DHW Outlet
Desuperheater Outlet
Condensate
Drain
Desuperheater Inlet
0.88” Dia.
Knockouts
26.1”
27.0”
Blower Opening
A
B
12.0
10.25
12.0
10.25
12.0
10.25
12.0
10.25
12.0
12.25
12.0
10.25
12.0
10.25
12.0
10.25
12.0
10.25
12.0
10.25
12.44
13.44
Model
Q14kW4T-xxx
Q16kW5T-xxx
Q18kW6T-xxx
GV36x-x-(D,V)xxx
GV38x-x-Vx2x
GV48x-x-Vx2x
GV52x-x-(D,V)xxx
GV58x-x-Vx2x
GV59x-x-(D,V)xxx
GV67x-x-DxVx,Vxxx
GV67x-x-Dx0x
Inlets
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
Outlets
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
Cond.
Drain
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
0.75 FPT
Filter
Size
21 x 30
21 x 30
21 x 30
20 x 22
21 x 29
21 x 29
20 x 22
21 x 29
21 x 29
21 x 29
21 x 29
Other Dimensions
E
F
G
I
19.1 2.2 28.5 9.0
19.1 2.2 28.5 9.0
19.1 2.2 28.5 9.0
19.9 3.0 22.0 9.0
21.9 1.2 27.6 9.0
21.9 1.2 27.6 9.0
19.9 3.0 22.0 9.0
21.9 1.2 27.6 9.0
21.9 1.2 27.6 9.0
21.9 1.2 27.6 9.0
21.9 1.2 27.6 9.0
C
2.1
2.1
2.1
2.3
0.6
0.6
2.3
0.6
0.6
0.6
0.6
J
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.0
Physical Data
All Models
18
23
29
36
38
42
48
52
Compressor
Series
58
59
67
Compliant Scroll
120
380
Q14
Q16
Q18
Thermostatic
Expansion Device
High Density
Air Coil Type
4
No. of Air Coil Rows
5
5
9x7 9x7 9x7
Fan Wheel (dia. x width)
Vara
--
Fan Motor Type
Fan Motor (HP)
Vara
N/A
High Density
5
3
5
3
5
4
5
5
5
5
N/A
5
5
5
9x9
10x8
9x9
10x8
10x8
10x8
10x8
12x9
(10x8)x2
(10x8)x2
--
10x8
10x8
10x8
--
--
--
--
--- 10x8
---10x8
-10x8 10x8
--GeoSource 2000, GeoSource DualTEK† – PSC; GeoSource Vara, GeoSource Vara 2 Plus - ECM
--
ECM
1/6
1/6
1/4
1/3
3/4
1/3
3/4
1/2
3/4
3/4
1
(1/2)x2
(3/4)x2
--
3/4
3/4
3/4
--
--
--
3/4
--
--
--
3/4
--
3/4
3/4
--
--
--
--
--
--
1/150
Desuperheater Pump (HP)
N/A
1/150
N/A
DHW Pump (HP)
1/20
55 (DualTEK – 75)
Transformer (VA)
190 225 235
100
75
--
--
GW
--
--
220
225
--
260
--
305
--
325
345
495
495
1200
--
--
--
Invision3
--
--
--
--
--
--
--
--
--
--
--
--
--
--
520
520
525
GV/GH
Unit Weight (lbs)
98
270
330
275
340
315
355
345
360
625
645
--
--
33
Electrical Data
GeoSource 2000, GeoSource DualTEK† (-Dx0x) Forced Air Models (GV, GH)
Model
180/181
230/231
290/291
360/361
420/421
520/521
590/591
670/671
980
1200
Voltage
(60 Hz)
208/230-1
277-1
208/230-1
208/230-3
277-1
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
Compressor
RLA
LRA
10.7
45.0
8.6
-12.1
54.0
7.9
45.0
9.6
47.0
3.9
22.4
15.0
72.5
10.0
63.0
5.0
31.0
17.9
88.0
11.4
77.0
5.7
39.0
20.4
109.0
13.9
88.0
7.1
44.0
22.1
137.0
15.0
120.0
8.2
49.5
32.1
148.0
19.3
137.0
10.0
62.0
27.9
129.0
20.7
156.0
10.0
75.0
26.4x2
129x2
15.0x2
120.0x2
8.2x2
49.5x2
32.1x2
148x2
19.3x2
137.0x2
10.0x2
62.0x2
Fan
FLA
1.1
2.0
1.1
1.1
2.0
0.9
1.7
1.7
0.9
2.2
2.2
1.1
2.2
2.2
1.1
3.1
3.1
1.6
4.3
4.3
2.2
7.5
7.5
2.2
3.1x2
3.1x2
1.8x2
4.3x2
4.3x2
2.2x2
LRA
2.5
8.0
2.5
2.5
8.0
2.3
4.5
4.5
2.3
6.1
6.1
3.1
6.1
6.1
3.1
8.0
8.0
4.0
10.4
10.4
6.1
16.0
16.0
6.1
8.0x2
8.0x2
6.1x2
10.4x2
10.4x2
6.1x2
Without PumpPAK
Total
Min.
Max Fuse/
FLA
Ampac.
Ckt Bkr*
11.8
14.5
25
10.6
12.8
20
13.2
16.2
25
9.0
11.0
15
11.6
14.0
20
4.8
5.8
10
16.7
20.5
35
11.7
14.2
20
5.9
7.2
10
20.1
24.6
40
13.6
16.5
25
6.8
8.2
10
22.6
27.7
45
16.1
19.6
30
8.2
10.0
15
25.2
30.7
55
18.1
21.9
35
9.8
11.9
20
36.4
44.4
75
23.6
28.4
45
12.2
14.7
20
35.4
42.4
70
28.2
33.4
50
12.2
14.7
25
59.0
65.6
90
36.2
40.0
50
20.0
21.3
30
72.8
80.8
110
47.2
52.0
70
24.4
26.9
35
*HACR-type breaker per NEC
PumpPAK
FLA
LRA
1.8
---3.6
-------3.6
-----3.6
-----3.6
-----3.6
-----3.6
-----3.6
------------------
With PumpPAK
Total
Min.
FLA
Ampac.
13.6
16.3
--16.8
19.8
------20.3
24.1
----23.7
28.2
----26.2
31.3
----28.8
34.3
----40.0
48.0
----39.0
46.0
-----------------
Max Fuse/
Ckt Brk*
25
-30
---35
--45
--50
--55
--80
--70
---------
Without PumpPAK
Total
Min.
Max Fuse/
FLA
Ampac.
Ckt Bkr*
18.6
22.4
35
13.6
16.1
25
6.1
7.4
10
21.5
26.0
40
15.0
17.9
25
6.8
8.2
10
20.7
25.0
40
24.0
29.1
45
17.5
21.0
30
8.2
10.0
15
29.3
35.7
60
25.7
31.2
50
18.6
22.4
35
9.3
11.4
15
37.2
45.6
75
35.7
43.7
75
22.9
27.7
45
11.1
13.6
20
31.5
38.5
65
24.3
29.5
50
11.1
13.6
20
39.3
48.2
80
56.4
63.0
85
33.6
37.4
50
17.5
19.6
25
67.8
75.8
105
42.2
47.0
65
21.1
23.6
30
117.2
131.9
190
52.8
59.4
85
*HACR-type breaker per NEC
PumpPAK
FLA
LRA
3.6
-----3.6
-----3.6
-3.6
-----3.6
-3.6
-----3.6
-3.6
-----3.6
-----3.6
------------------
With PumpPAK
Total
Min.
FLA
Ampac.
22.2
26.0
----25.1
29.6
----24.3
28.6
27.6
32.7
----32.9
39.3
29.3
34.8
----40.8
49.2
39.3
47.3
----35.1
42.1
----42.9
51.8
-----------------
Max Fuse/
Ckt Brk*
40
--45
--45
50
--65
55
--80
75
--65
--80
---------
With PumpPAK
Total
Min.
FLA
Ampac.
28.3
32.8
--29.4
34.2
34.4
40.4
32.5
38.0
--36.4
42.9
42.5
50.5
--38.3
45.3
---
Max Fuse/
Ckt Brk*
50
-50
60
60
-65
80
-70
--
GeoSource 2000, GeoSource Ultra Hydronic Models (GW)
Model
290/291
360/361
370/371
420/421
470/471
520/521
570/571
590/591
670/671
770/771
980
1200
3800
Voltage
(60 Hz)
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-1
208/230-3
460-3
208/230-1
208/230-1
208/230-3
460-3
208/230-1
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-3
460-3
Compressor
RLA
LRA
15.0
72.5
10.0
63.0
5.0
31.0
17.9
88.0
11.4
77.0
5.7
39.0
17.1
83.0
20.4
109.0
13.9
88.0
7.1
44.0
25.7
134.0
22.1
137.0
15.0
120.0
8.2
49.5
33.6
158.0
32.1
148.0
19.3
137.0
10.0
62.0
27.9
129.0
20.7
156.0
10.0
75.0
35.7
148.0
26.4x2
129.0x2
15.0x2
120x2
8.2x2
49.5x2
32.1x2
169.0x2
19.3x2
137.0x2
10.0x2
62.0x2
58.6x2
425x2
26.4x2
187x2
1/3 HP Pump
FLA
LRA
3.6
-3.6
-1.1
4.0
3.6
-3.6
-1.1
4.0
3.6
-3.6
-3.6
-1.1
4.0
3.6
-3.6
-3.6
-1.1
4.0
3.6
-3.6
-3.6
-1.1
4.0
3.6
-3.6
-1.1
4.0
3.6
-3.6
-3.6
-1.1
4.0
3.6
-3.6
-1.1
4.0
-----
GeoSource Vara, GeoSource Vara 2 Plus, GeoSource DualTEK† (-DxVx) Forced Air Models
Model
360/361
380/381
480-481
520/521
580/581
590/591
670/671
Voltage
(60 Hz)
208/230-1
208/230-3
208/230-1
208/230-1
208/230-1
208/230-3
208/230-1
208/230-1
208/230-3
208/230-1
208/230-3
Compressor
RLA
LRA
17.9
88.0
11.4
77.0
19.0
82.0
24.0
96.0
22.1
137.0
15.0
120.0
26.0
118.0
32.1
148.0
19.3
137.0
27.9
129.0
20.7
156.0
Fan
FLA
6.8
6.8
6.8
6.8
6.8
6.8
6.8
6.8
6.8
6.8
6.8
LRA
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
GeoSource Invision3 - Dual Circuit Models
Model
Q14kW4T-000, SUP, DHW
Q14kW4T-DWR
Q16kW5T-000, SUP, DHW
Q16kW5T-DWR
Q18kW6T-000, SUP, DHW
Q18kW6T-DWR
34
Compressor #1
Compressor #2
RLA
LRA
RLA
LRA
12.1
54.0
12.1
54.0
12.1
54.0
17.9
88.0
17.9
88.0
12.1
54.0
17.9
88.0
17.9
88.0
22.1
137.0
12.1
54.0
22.1
137.0
17.9
88.0
3
All GeoSource Invision units are 208/230-Volt single phase.
Without PumpPAK
Total
Min.
Max Fuse/
FLA
Ampac.
Ckt Bkr*
24.7
29.2
45
18.2
21.1
30
25.8
30.6
45
30.8
36.8
60
28.9
34.4
55
21.8
25.6
40
32.8
39.3
65
38.9
46.9
75
26.1
30.9
50
34.7
41.7
65
27.5
32.7
50
*HACR-type breaker per NEC
Fan
FLA
6.8
6.8
6.8
6.8
6.8
6.8
Total
FLA
31.0
36.8
36.8
42.6
41.0
46.8
PumpPAK
FLA
LRA
3.6
---3.6
-3.6
-3.6
---3.6
-3.6
---3.6
----
Without PumpPAK
Min.
Max Fuse/
Ampac.
Ckt Bkr*
34.0
45
41.3
55
41.3
55
47.1
60
46.5
65
52.3
70
*HACR-type breaker per NEC
PumpPAK
FLA
LRA
3.6
-3.6
-3.6
-3.6
-3.6
-3.6
--
With PumpPAK
Total
Min.
FLA
Ampac.
34.6
37.6
40.4
44.9
40.4
44.9
46.2
50.7
44.6
50.1
50.4
55.9
Max Fuse/
Ckt Brk*
45
60
60
65
70
75
Wiring Diagram – GeoSource 2000 Forced Air Models [G(V,H)xxx-x-TxOx]
35
Wiring Diagram – GeoSource 2000 Forced Air Models [GH(98,120)x-x-TxTx]
36
Wiring Diagram – GeoSource 2000, GeoSource Ultra Hydronic Models [GWx-x-TxOx]
37
Wiring Diagram – GeoSource 2000 Hydronic Models [GW(98,120)x-x-TxTx]
38
Wiring Diagram – GeoSource DualTEK† Models [G(V,H)xxx-x-Dx0x]
39
Wiring Diagram – GeoSource DualTEK† Models [G(V,H)xxx-x-DxVx]
40
Wiring Diagram – GeoSource Invision3 2Ht-1Cl-1DHW [QxxkWxT(-DHW, -DWR)]
41
Wiring Diagram – GeoSource Invision3 2Ht-2Cl [QxxkWxT(-000, -SUP)]
42
Wiring Diagram – GeoSource Vara Forced Air Models [G(V,H)xxx-x-Vxxx]
43
Wiring Diagram – GeoSource Vara 2 Plus Forced Air Models [G(V,H)xxx-x-Vx2x]
44
Correction Factors
Entering Air Temperature
ENTERING
AIR TEMP
60oF DB
65oF DB
70oF DB
o
75 F DB/63oF WB
80oF DB/67oF WB
85oF DB/71oF WB
HEATING
BTU/hr
KW
1.04
0.96
1.02
0.98
1.00
1.00
0.97
1.03
0.93
1.07
---
Airflow
COOLING
BTU/hr
KW
--0.67
0.73
0.79
0.83
0.90
0.92
1.00
1.00
1.05
1.04
NOMINAL
CFM
80%
85%
90%
95%
100%
105%
110%
Hydronic Unit’s Earth Loop Flow Rates
NOMINAL
GPM
50%
55%
60%
65%
70%
80%
90%
100%
110%
120%
130%
140%
150%
HEATING
BTU/hr
KW
0.90
0.97
0.91
0.97
0.92
0.98
0.93
0.98
0.94
0.98
0.96
0.99
0.98
0.99
1.00
1.00
1.02
1.00
1.04
1.00
1.06
1.01
1.07
1.01
1.08
1.02
HEATING
BTU/hr
KW
0.92
1.04
0.95
1.03
0.97
1.02
0.99
1.01
1.00
1.00
1.01
0.99
1.02
0.98
COOLING
BTU/hr
KW
0.96
0.97
0.97
0.98
0.98
0.98
0.99
0.99
1.00
1.00
1.01
1.01
1.02
1.02
Hydronic Unit’s Load Side Flow Rates
COOLING
BTU/hr
KW
0.97
1.05
0.97
1.05
0.98
1.04
0.98
1.04
0.98
1.03
0.99
1.02
0.99
1.01
1.00
1.00
1.01
0.99
1.02
0.98
1.02
0.98
1.03
0.97
1.03
0.96
NOMINAL
GPM
100%
120%
140%
160%
180%
200%
HEATING
BTU/hr
KW
1.00
1.00
1.01
0.98
1.02
0.96
1.03
0.95
1.04
0.94
1.05
0.94
COOLING
BTU/hr
KW
1.00
1.00
1.03
1.01
1.06
1.02
1.08
1.03
1.09
1.04
1.10
1.05
Water Coil Pressure Drop Ratings (Pure Water)
GV/GH/
GW/GC 18
GV/GH/
GW/GC 23
Earth Loop
Flow
dP
GPM psi
2
0.9
3
0.9
4
0.9
5
1.3
6
1.9
2
3
4
5
6
7
8
0.9
0.9
1.5
2.2
3.0
3.9
5.2
2
3
4
5
6
7
8
9
0.9
0.9
1.5
2.2
3.5
3.9
5.2
6.5
Hyd. Loop
Flow
dP
GPM psi
GV/GH/
GW/GC 42
GV/GH 38*
GW 47*
GV/GH/
GW/GC 29
2
3
4
5
6
0.9
0.9
1.5
2.2
3.5
GV/GH 48*
GV/GH/
GW 52*
Earth Loop
Flow
dP
GPM psi
3
0.9
4
1.3
5
1.7
6
2.8
7
4.7
8
5.5
9
6.0
10
7.8
11
10.0
12
12.1
4
5
6
7
8
9
10
11
12
13
0.8
1.2
1.6
2.4
2.8
3.6
4.4
5.2
6.4
7.6
Hyd. Loop
Flow
dP
GPM psi
4
1.3
5
1.7
6
2.8
7
4.7
8
5.5
5
6
7
8
9
2.6
3.0
4.8
6.0
7.0
GV/GH/
GW 67*
GW 77*
GH 98*
GH 120*
GW 98
GW120
GW 3800
6
1.6
7
4.8
GW 57*
2
0.9
3
0.9
7
2.0
8
6.0
3
0.9
4
1.5
8
2.5
9
7.0
GV/GH 58*
4
1.3
5
1.7
9
3.1
10
10.0
5
1.7
6
2.8
10
3.8
11
11.7
GW 37
GV/GH/
6
2.8
7
4.7
11
4.3
GW 59*
7
4.7
12
4.8
8
5.5
13
6.0
9
6.5
14
7.5
10
7.8
15
9.4
*Earth Loop Pressure Drops apply to standard water coils only. Cupro-nickel water coils have higher pressure drops.
GV/GH/
GW/GC 36
Earth Loop
Flow
dP
GPM psi
8
3.0
9
3.5
10
3.8
11
4.6
12
5.3
13
6.1
14
7.0
15
7.9
16
9.0
Hyd. Loop
Flow
dP
GPM psi
9
7.0
10
10.0
11
11.7
12
14.7
13
17.0
14
16
18
20
22
24
26
28
30
2.7
3.0
3.3
3.5
3.8
4.1
4.5
4.8
5.2
14
16
18
20
22
3.9
4.2
4.5
4.9
5.3
75
80
85
90
95
100
5.6
6.4
6.9
7.4
8.0
8.7
50
55
60
65
70
75
80
85
90
95
100
2.9
3.4
3.9
4.6
5.4
6.3
7.3
8.5
9.8
11.2
12.7
45
ColdClimate Geothermal Heat Pumps
19230 Evans Street (Hwy 169)
Elk River, MN 55330
USA
1-800-4-ECONAR
www.econar.com
NRTL/C