FS720 Fire detection system – Data sheet A6V10227649
FS720
Cerberus TM PRO
Fire detection system
IP5
 Control panel family with 4 station types
– Microprocessor-controlled fire detection system
– Compact fire control panels for 252 to 1512 addresses
– PC-based operation (Cerberus-Remote) via Fast-Ethernet
– Free control logic
– Phased evacuation
 Network cluster (C-WEB/SAFEDLINK)
– Redundant network nodes
– Failsafe loop topology
– Up to 16000 addresses and 32 stations (control panels, operating panels)
– Fast data transfer up to 312 kbps (can be adjusted to line quality)
 Hierarchical networks via Ethernet backbone (C-WEB/LAN)
– Multi-cluster network interconnected via Industrial Ethernet (fiber-optic)
– EN 54-compliant network
– System-wide redundancy
– Up to 14 clusters (with up to 16 stations per cluster)
– Up to 64 stations in entire network
Building Technologies
Fire Safety & Security Products
 High-performance peripherals
– From bus-powered sounders, floor repeater displays and floor repeater terminals
– All Cerberus PRO FD720 devices are supported
 Time-saving functions for installation, startup and service
– Ergonomic Cerberus-Engineering-Tool with familiar Windows mechanisms
– Auto configuration (self-addressing)
– Zones and customer texts can be assigned without reading in the hardware
– Remote transfer of diagnostic data (e.g. firmware versions)
General functional principle
The FD720 devices register signals, compare and evaluate them on the basis of stored
patterns. If a fire is detected, the data is transferred to the fire control panel, and released fire controls. The processor in this device triggers centralized and decentralized
control functions via input and output modules. It does not matter whether the network
has a ring structure and is therefore failsafe, is Ethernet or a combination of the two. In
case of malfunctions, the degrade function guarantees operation of the system components that are impaired by the malfunction. All signals are automatically displayed on
the operating panel based on their origin, or can be handle using operating functions. In
any event, the messages together with a timestamp are entered in the event memory
so that the locations where fire started can be ascertained subsequently.
System overview FS720
The FS720 fire detection system is the new global generation of Cerberus PRO fire
control panels. It combines the highest safety standards with international product innovations and cutting-edge technology.
The fire control panels, fire terminals and the shared C-WEB network are designed in
accordance with EN 54-2, EN 54-4 and other national supplementary requirements.
They represent the heart of the FS720 fire detection system. The highest levels of detection reliability and optimum adaptability to customers' existing systems are achieved
in conjunction with intelligent FD720 peripheral devices (C-NET).
 FC722 fire control panel
The size of this fire control panel makes it ideal for smaller applications (e.g.
workshops and hotels).
It is possible to connect a total of 2 (4) loops or 4 (8) stub lines with up to
252 addresses.
Its strength lies above all in its compactness that permits quick and efficient
installation.
 FC723 fire control panel
The FC723 is a modular fire control panel with integrated user interface and
processes signals from Cerberus PRO FD720.
A built in card cage with 2 plug-in position enables the application of:
– -C-NET line cards FCL2001-A1 (for additional lines)
– I/O-card FCI2008-A1 (with 12 programmable in-/outputs)
– SynoLOOP line cards
– Interactive and Interactive-Ex line cards
Die FC723 supports up to 756 addresses.
2
Building Technologies
Fire Safety & Security Products
 FC724 fire control panel
The FC724 fire control panel can have 4 (8) loops or 8 (16) stub lines with
up to 504 addresses.
This means they offer sufficient capacity for medium-sized fire detection
installations (e.g. regional banks and office complexes).
 FC726 fire control panel
The FC726 is a modular fire control panel with integrated user interface and
processes signals from Cerberus PRO FD720.
A built in card cage with 5 plug-in position enables the application of:
– C-NET line cards FCL2001-A1 (for additional lines)
– I/O-card FCI2008-A1 (with 12 programmable in-/outputs)
– SynoLOOP line cards
– Interactive and Interactive-Ex line cards
The FC726 supports up to 1512 addresses
 FT724 fire terminal
All fire control panels have an integrated user interface.
However, the FT724 fire terminal is available for remote operating panels.
The view shown on this compact person machine interface can be freely
allocated between fire control panels. Max. 5 fire terminals with system wide
view programmable.
 Floor repeater terminals and floor repeater display
Messages from relatively small monitoring areas (e.g. hospital wards) can
be detected by FT2011 floor repeater displays and operator intervention is
even possible as well using FT2010 floor repeater terminals. These devices
are C-NET participant.
National supplements
Fire brigade person machine interfaces
Evacuation person machine interfaces
 Germany
 France
 Netherlands
3
Building Technologies
Fire Safety & Security Products
FS720 Networks
Interfaces
C-NET
Cluster (C-WEB/SAFEDLINK)
Backbone (C-WEB/Ethernet)
Ethernet
Network for connecting Cerberus PRO FD720 devices
Network for creating a cluster of up to 32 stations
(without connection to a Danger Management System)
Network for connecting multiple clusters via a fiber-optic Industrial Ethernet
(max. 64 stations)
Connection to Siemens Danger Management System

Cluster (C-WEB/SAFEDLINK)
Up to 32 fire control panels und fire control terminals can be connected in a single cluster
(C-WEB/SAFEDLINK) or up to 16 stations when the
cluster is connected to a danger management system. The innovative redundant network nodes not
only set new standards in terms of failsafe characteristics but also for high-speed data transfer. It is
also possible to extend the distance between panels
by the use of a repeater.

Backbone (C-WEB/LAN )
Using a fiber-optic Backbone (C-WEB/LAN) up to
14 of the above mentioned clusters (with up to 16
stations each) can be networked. This topology
enables the construction of an EN 54-compliant
network with up to 64 panels and fire terminals.

Management station
A danger management station can be connected
directly to any network type: standalone panel, cluster (C-WEB/SAFEDLINK) or hierarchical network
(C-WEB/LAN). When such connections should be
made via a customer network, then a Security module shall be used to provide Firewall protection (and
a VPN connection if the management station is not
within the customer network itself).
4
Building Technologies
Fire Safety & Security Products
C-NET overview
Transmission of fault
and alarm signals
FC724/FC726
Service
FDA221/
FDA241
FT2011
Fire control panel
collective 2...24 zones
Alarm
Fault
Floor repeater display
FC10
FDCI
OH
2 (8)
conventional
horn lines
OP
OP
ASD
FDCIO
4 inputs
FDS
FDCL
C-NET
4 (8) loops
FDM223-Ex
OOH740-A9-Ex
Explosionhazard area
FT2010
Floor repeater
terminal
HI
OH
DBS
OP
FDCIO Extinguishing
control panel
collective
stub line
XC10
1 output
FDCIO
4 outputs
FDF
FDCW
FDM
FDCL221-Ex
FDL
FDS
Mimic display
FT2001-A1
1 input
FDCI
4 inputs
FDCIO
1 input
FDCIO
FDOOT
1 Extinguishing sector
FDM273
Radio detectors
Characteristics
Optimum use of customers' resources
 Integration of intranet.
 Operation of individual control panels or a network from the customer's PC using the
Cerberus-Remote Software.
 Replacement of redundant cabling by redundant network nodes
 Operation of floor repeater displays and terminals on the field data bus (C-NET)
High availability
 Remote control via Internet
 Efficient troubleshooting via remote diagnostic data transfer
 Highest levels of reliability and secure detection
 Primary site protection through auto configuration
Simple handling
 Straightforward and time-saving operation by user-friendly, self-explanatory menu
structure.
 Prefabricated control panels for efficient installation
 Remote access to all stations in the system via one network station
 Topology upload (periphery and installation) into the tool
5
Building Technologies
Fire Safety & Security Products
 Little training required because of a consistent operating and hardware concept with
one engineering tool (Cerberus-Engineering-Tool) for the entire system
High speed
 Rapid data transfer at 312 kbps in the failsafe network and 100 Mbit/s in the Ethernet
network
 Short download and upload times
 Preparation of logical configuration data before installation of the system
Station types in C-WEB
Housing with integrated
FC722
FC722
FC723
FC724
Standard
430 x 398 x 160
Comfort
430 x 796 x 160
Comfort
430 x 796 x 160
4 (8)
FC726
FT724
operating unit
Housing type
Dimensions (W x H x D) mm
Number of loops
(with loop extension) or
number of stub lines
Plug in positions
(C-NET and I/O cards)
2 (4)
Comfort
430 x 796 x 160
2(4)
4 (8)
4(8)
8 (16)
–
2
–
5
–
Max. number of addresses
252
756
504
1512
–
1
1
1
1
1
1
1
1
–
1
1
1
1
1
1
1
1
–
1 (4)
1(4)
2 (8)
2(8)
–
8
12
12
12
–
Outputs for alarm
– Monitored control output
– Potential-free changeover contact
Outputs for fault
– Monitored control output
– Potential-free changeover contact
Outputs for conventional horn lines, monitored (with sounder module)
Free programmable inputs/outputs 24 V
Free programmable inputs/outputs with a
max. of 5 additional I/O cards
Battery capacity (internal)
2 x 12 V, 12 Ah
2 x 12 V, 26 Ah
Modular
Eco
430 x 796 x 260 430 x 398 x 80
4 (8)
–
8 (16)
–
–
60
–
2 x 12 V, 26 Ah
2 x 12 V, 26 Ah
2 x 12 V, 45 Ah
Ethernet connection




2 x 12 V, 7 Ah
(optional)

Degrade mode and degrade supply





Emergency power supply
Organizational logic
Time functions
Standby operating time up to 72 h (depending on configuration)
The Alarm Verification Concept (AVC) permits the control panel organization to be freely adapted to the
customer's requirements.
During system tests or when detector groups are switched off, timeout functions make sure that these detector groups are reactivated.
Event memory
Up to 2000 events can be called up for each station according to various criteria.
Ground fault monitoring
All outgoing detector lines from the control panel are monitored for ground faults.
6
Building Technologies
Fire Safety & Security Products
Hardware expansion
Station
Network module (SAFEDLINK)
Redundancy module for networking
Repeater (SAFEDLINK)
Loop extension (C-NET)
FC722

FC723

FC724

FC726

FT724















Line cards (C-NET)
–
Line cards (SynoLOOP)
–
–

I/O cards (programmable)
Sounder module
RS232 module (isolated)
RS485 module (isolated)
Fire brigade periphery module (DE)
Event printer
Operating add-on



–
–



–
–
–

–





–














–







–
Refer to the following product data sheets for details about C-WEB stations:
FC722-xx
FC723-xx
FC724-xx
FC724-xx
FC726-xx
FT724-xx
A6V10206525
A6V10379246
A6V10207176
A6V10207176
A6V1263277
A6V10207898
Refer to the following data sheets for details about C-NET floor repeater terminals, floor
repeater displays, mimic display driver, conventional fire control unit FC10 and extinguishing control unit XC10:
FT2010-A1, FT2011-A1
009393
FT2001-A1
A6V10082691
FC10
A6V10277145, A6V10277147
XC10
008496
Refer to the corresponding product data sheets for details about the other peripheral devices.
7
Building Technologies
Fire Safety & Security Products
Peripheral devices in the C-NET
OP, OH, HI, FDF, FDL, FDM
– Latest generation devices with evaluation algorithms.
– Signal processing with detection algorithms and ASAtechnology™.
– Automatic address allocation during commissioning.
DBS, FDS
– Instead of complicated additional cabling, FD720 technology permits the
operation of sounder bases, alarm sounders and/or alarm sounder beacons on the detector bus, i.e. supply and communication are via the
C-NET.
LaserFocus VLF-250/-500
– The aspiration smoke detector is a very early warning smoke detector (As-
pirating Smoke Detector ASD) designed to protect small, business-critical
environments.
– The detector works by continually drawing air into sample holes in a pipe
network.
– The air is filtered and passed into a detection chamber where light scattering technology detects the presence of very small amounts of smoke.
SWING
– Wireless fire detection system can be fully integrated into the C-NET.
– Wireless transmission replaces complex or visible cable installation and is
therefore particularly interesting for museums, churches etc. The system
also offers the additional advantage that installation is possible without system interruption.
– The wireless gateway FDCW241 communicates with up to 30 wireless
detectors (smoke detectors and manual call points) and up to 16 Radio
gateways with crossover of radio cells.
FDA241, FDA221
–
–
The FDA241/221 series of detectors are a very early warning dual
wavelength (blue & infra-red) smoke detectors designed to protect
2
small to medium, business-critical environments up to 800 m with the
2
FDA241 or 500 m with the FDA221).
The detector works by continually drawing air into sampling holes in a
pipe network. The air is passed into a uniquely designed detection
chamber where light scattering technology detects the presence of very
small amounts of smoke.
8
Building Technologies
Fire Safety & Security Products
FDCI, FDCIO
– Statuses can be monitored using the input module. (e.g. door monitoring,
ventilation checks or for sprinkler alarm triggering.)
– The input/output modules are used for decentralized activation of fire
doors, ventilation systems, etc., the input can be used for acknowledgement or also for status monitoring purposes, or else for activating the
standard interfaces extinguishing (SST) according to VdS.
– The transponder has 2 inputs/outputs and can parameterized
– for connection of collective fire detectors Siemens or Synova 300/600
(GMT/conventional line, GMT/conventional line with shunt-Zener-diode
barrier (SB3) for explosion-hazard areas)
– for monitored controls of alarm devices
FDCL221, FDCL221-M
– Line separators can be connected in between to ensure that several stub
lines will not fail if there is a short circuit.
– The line separator is used where several stubs are connected to the
C-NET at one point if there is no other FD720 device between the branches.
FT2011-A1, FT2010-A1
– Smaller areas of the fire detection system can be operated or displayed
using the FT2010 floor repeater terminals and FT2011 floor repeater displays operated in the C-NET.
– The personnel responsible at the customer's premises (e.g. ward sisters)
have access to a clearly structured user interface for customer-specific
plain texts to enable events to be localized unambiguously.
– The display type corresponds to the FT724 fire terminal.
FT2001-A1
– The mimic display driver operated in the C-NET has 2x24 outputs for LED
activation for mimic display panels.
– 2 control outputs for 'Local buzzer' and 'LED operation'
– 2 inputs for 'Switch-off buzzer' and 'Lamp test'
– Connection to LED via flat cable F50F410 (50-wire, 24 red LEDs, cable
length 1 m
FC10, XC10
– The conventional fire control panel FC10 and the extinguishing control
panel XC10 can integrated as autonomous control panels into the C-NET
(via in-/output module FDCIO).
– Relevant events are transferred to the connected fire control panel.
– Each line can be individually configured to AlgoRex collective or Synova™
conventional. This allows to connection to AlgoRex DS11collective, Synova
conventional detectors as well as special detectors like DF1191, FDF2x1-9
flame, DLO1191, FDL241-9 linear detectors.
9
Building Technologies
Fire Safety & Security Products
Siemens Switzerland Ltd
Industry Sector
Building Technologies Division
International Headquarters
Fire Safety & Security Products
Gubelstrasse 22
CH-6301 Zug
Tel. +41 41 724 24 24
www.siemens.com/buildingtechnologies
Document Nr.
A6V10227649_d_en_--
Edition
2014-04-28
© 2009 Copyright by
Siemens Switzerland Ltd
Data and design subject to change without notice.
Supply subject to availability.
Manual FS720
Register 1