Air Circuit Breaker

Transcription

Air Circuit Breaker
U-Series
Air Circuit Breaker
LV &
MV
Circ
uit B
reak
ers
Leader of Technology
Hyundai Heavy Industries' state-of-the-art technologies
have created circuit breakers and contactors
for electrical systems that are genuine masterpieces.
CONTENTS
04 Features
•
74 Dimensions
11 Structure
•
•
13 Ratings
92 Ordering Codes
•
•
14 Protection Trip Relay (OCR) • 30 Accessories • 72 Circuit Diagrams
96 Technical Data
•
105 Operating Conditions
•
106 Ordering Sheet
U-Series
Air Circuit Breaker
HYUNDAI ACB meets your demands for high
breaking capacity, full line-up, and optimized
panel size. Various accessories and connection
methods realize user-friendly handling.
U-Series
/ Air Circuit Breaker
Features
| Full line-up |
460mm
•U-Series ACB maximize your choice and satisfaction with compact size and dual (UAN/UAS) model.
766mm
624mm
8m
36
399mm
m
328mm
B frame
[100kA]
A frame
[85kA]
•630-2,000A(UAN)
•630-1,600A(UAS)
C frame
[100kA]
D frame1)
[150kA]
•4,000-6,300A(UAN)
•4,000-5,000A(UAN)
•2,000-4,000A(UAN)
•2,000-3,200A(UAS)
※ - Breaking capacity is at AC500V.
1) D frame will be available from October 2013.
| Applications |
•U-Series ACB offering high breaking capacity and advanced protection trip relay is suitable to cover various applications
including buildings, data centers, industrials and so on. U-Series ACB protects these facilities from harmonic frequency by
100% capacity of N phase.
Buildings
Industrials
Electric power facilities
•Multipurpose buildings
•Broadcasting stations
•Steel/Metal
•Electric power stations
•Hospitals
•IT/Telecommunications
•Gas/Chemical
•Electric power substations
•Pulp/Paper
•Dispersed power generators
•Commercial buildings
•Hotels
4
Data centers & Networks
•Renewable energy facilities
ACB
| Compliance with standards |
 Standard
•IEC 60947-1,2
International Electrotechnical Commission
•EN 60947-2
European Standard
•GB
China National Standard (Guojia Biaozhun)
•GOST R 50030.2-99 9
Government Standard of Russia
•GOST R 50030.1-2000
Government Standard of Russia
•KS C 4620
Korean Standards Association
 Approval
•ISO 18001, 14001, 9001
•KS/KOREA
Korea Quality Certificate Standard Association
•CE
Community European
•GOST-R/RUSSIA
Government Standard of Russia
•CCC/CHINA
China Compulsory Certification
•KR/KOREA
Korean Register of Shipping
•GL/GERMANY
Germanischer Lloyd
•LR/U.K
Lloyd's Register of Shipping
•ABS/U.S.A
American Bureau of Shipping
•BV/FRANCE
Bureau Veritas
•NK/JAPAN
Nippon Kaiji Kyokai
 CB type test
•DEKRA
Formerly KEMA Quality Registered
•KERI
Korea Electrotechnology Research Institute
U-Series Air Circuit Breaker_ 5
U-Series
/ Air Circuit Breaker
Features
| Various accessories |
[ Body side ]
❶
❷
❸
❹
❺
❻
❼
❽
❾
❿











❶ Motor
❷ Closing coil
❸ Trip coil
❹ Double trip coil
❺ Trip supervision coil
❻ Under voltage trip coil
6
❼ Auxiliary switch
❽ Condenser trip device
❾ Lifting lug
❿ Mechanical interlock kit
 Phase insulation barrier
 ON/OFF button cover

 OCR portable checker
 Key lock device
 Wrong insertion preventer
 Fixing block
 Counter
O
CR & Alarm switch reset device

 Test jumper
 Draw-in/out handle
 Draw-in/out and
position lock device
 Door flange
 Dust cover
ACB
[ Cradle side ]
❶
❷
❸
❹
❺
❻
❼
❽
❾
❿


❶ UVT time delay controller
❷ Remote operation module
❸ Temperature detection module
❹ Short “b”contact
❺ Position switch
❻ Mechanical interlock kit
❼ Phase insulation barrier
❽ Mechanical operated cell (MOC) switch
❾ Dummy ACB
❿ Wrong insertion preventer

 Safety shutter
 Arc shield
 Control terminal protection cover
U-Series Air Circuit Breaker_ 7
U-Series
/ Air Circuit Breaker
Features
| High performance protection trip relay (OCR) |
•The protection trip relay (OCR) of U-Series ACB supports stable power supply with temperature alarm, fault recording, and
others in addition to main protection functions.
Type
UPR-1L-GL
UPR-2L-GS
UPR-1D-GT
UPR-2L-GM
Ordering 50Hz
code
60Hz
33
35
36
37
43
45
46
47
•L/S/I/G
•Self-power
•Failsafe
•Pre-trip alarm
•Integrated
instantaneous output
contact
•L/S/I/G
•Self-power
•AC, DC100-250V
•Failsafe
•Pre-trip alarm
•Individual continuous
output contact
•Fault event
•Temperature alarm
Externals
Main function
8
•L/S/I/G
•Self-power
•AC, DC100-250V
•Failsafe
•Pre-trip alarm
•Individual output
contact
•Fault event
•Temperature alarm
•Earth leakage trip
•Communication
(Modbus)
•L/S/I/G
•Self-power
•AC, DC100-250V
•Failsafe
•Pre-trip alarm
•Individual output
contact
•Fault event
•Temperature alarm
ACB
| Multiple terminal busbar connections |
•Increases the user's convenience by diversified terminal connection methods according to busbar's type.
•Simply turn a horizontal connector 90˚ to make it a vertical connector (The opposite case is same).
 Standard connection
Vertical
Horizontal
Front
Vertical/Horizontal
Horizontal/Vertical
Vertical/Front
Horizontal/Front
Front/Vertical
Front/Horizontal
 Mixed connection (Top/Bottom)
※ - Changing connector is available only for UAN/UAS A frame 630-1,600A, UAN/UAS B frame 2,000-3,200A.
- Front connection type is suitable the panel requirement for limited installation space.
- Changing connection above 4,000A needs additional component, please contact us.
U-Series Air Circuit Breaker_ 9
U-Series
/ Air Circuit Breaker
Features
| Easy-to-install |
 Fixed type
•Installed in a switchboard directly.
 Draw-out type
•Consists of ACB and cradle.
•Cradle is fixed to a switchboard.
•ACB may be in the position of CONNECTED, TEST, ISOLATED,
and REMOVED.
•Switchboard door may be closed in ISOLATED position.
[ Draw-in/out guide rail ]
접속위치(Connected Position)
Connected position
- Main and control circuit are all connected.
- Normal condition of use
Isolated position
- Main and control circuit are all isolated.
- Switchboard door may be closed in isolated position.
10
Test position
- Main circuit is isolated, control circuit is connected.
- Control test is possible when switchboard’s door is closed.
Removed position
- ACB is totally drawn out from the cradle.
ACB
Structure
| Externals |
[ Front ]
❶
❶

❷

❸

❹
❺

❻

❷


❸

❹
❺

❻
❼
❽
❾
❿
[ Fixed type ]


[ Draw-out type ]
[ Cradle ]


[ Inside ]
❶ Control terminal
❷ Front cover
❸ Close/Open indicator
❹ Close button
❺ Protection trip relay (OCR)
❻ Open button
[ Rear ]
❼ Position lock device
❽ Position lock release button
❾ Draw-in/out handle insertion hole
❿ Position indicator
 Counter
 Charged/Discharged indicator
 Manual charging handle
 Name plate
 Arc shield
 Terminal busbar
 OCR & Alarm switch reset button
 Draw-in/out guide rail
U-Series Air Circuit Breaker_ 11
U-Series
/ Air Circuit Breaker
Structure
| Internals |
❶
❷
❸
❹
❺
❻
❼
❽
❾
❿


❶


❻

❹



❽

❾




❿
❶ Arc chamber
❷ Frame
❸ Counter
❹ Auxiliary switch
❺ Motor
❻ Closing/Trip/UVT coil
12
❼ MHT device
❽ Protection trip telay (OCR)
❾ Mechanism
❿ Draw-in/out device
 Front cover
 Control terminal protection cover
 Control terminal
 Manual charging handle
 Closing spring
 Moving contact
 Fixed contact
T
erminal busbar
 Current transformer
 Terminal clip
 Cradle
ACB
Ratings
Frame
A frame
B frame
06 : 630
08 : 800
10 : 1,000
12 : 1,250
16 : 1,600
20 : 2,000
06 : 630
08 : 800
10 : 1,000
12 : 1,250
16 : 1,600
20 : 2,000
25 : 2,500
32 : 3,200
40 : 4,000
Model
Rated operating voltage (Ue) (V)
Rated insulation voltage (Ui) (V)
Frequency (Hz)
Number of poles
Current setting range (….. x In max)
Rated current of neutral pole (…..% x In)
UAS
20 : 2,000
25 : 2,500
32 : 3,200
20,000
10,000
20,000
15,000
2,000
2,000
30,000
20,000
Without maintenance
5,000
06-20 : 10,000
25-40 : 5,000
2,000
5,000
5,000
With maintenance
10,000
06-20 : 15,000
25-40 : 10,000
5,000
10,000
10,000
65
85
85
143
187
187
65
60
50
Electrical
AC 690
AC 1,000
50/60
3, 4
0.4-1.0
100%
85
100
100
55
65
65
187
220
220
85
75
65
121
143
143
55
45
36
70
85
85
100%
154
187
187
70
65
55
12
40
10
40
Draw-out type
63
06-32 : 87
40 : 107
145
63
87
Fixed type
34
06-32 : 44
40 : 61
76
34
44
Draw-out type
280
06-32 : 130
40 : 61
173
74
103
Fixed type
44
06-32 : 55
40 : 81
81
44
55
399 x 460 x 368
3 pole
Weight (kg)
4 pole
4 pole
06 : 630
08 : 800
10 : 1,000
12 : 1,250
16 : 1,600
30,000
IEC 60947-2 AC 690/600/550V
category “B” AC 500/480/460V
KS C 4620 AC 415/380/230/220V
Rated service breaking capacity (…..% x Icu)
Rated making capacity
IEC 60947-2 AC 690/600/550V
(Icm)
category “B” AC 500/480/460V
(kA peak)
KS C 4620 AC 415/380/230/220V
1 sec
Rated short-time capacity
(Icw)
2 sec
(kA, without Inst.)
3 sec
Rated impulse withstand voltage (Uimp) (kV)
Maximum total breaking time (ms)
Motor charging time (sec) max.
Closing operating time
Closing time (ms) max.
Without maintenance
Mechanical
With maintenance
3 pole
32 : 3,200
40 : 4,000
50 : 5,000
B frame
AC 690
AC 1,000
50/60
3, 4
0.4-1.0
100%
85
100
100
100%
187
220
220
85
75
65
12
40
10
40
15,000
Rated breaking capacity
(Icu)
(kA sym)
External dimension (mm)
(WxHxD, except busbar)
A frame
UAN
Recognition order code:
Rated current (In max at 40˚C) (A)
Life cycle (times)
C frame
Draw-out type
Fixed type
Draw-out type
Fixed type
399 x 460 x 368
624 x 460 x 368
328 x 460 x 368
337 x 404 x 296
408 x 404 x 296
633 x 404 x 296
337 x 404 x 296
408 x 404 x 296
413 x 460 x 368
514 x 460 x 368
794 x 460 x 368
413 x 460 x 368
514 x 460 x 368
422 x 404 x 296
523 x 404 x 296
803 x 404 x 296
422 x 404 x 296
523 x 404 x 296
Draw-out type
H
H
Fixed type
328 x 460 x 368
W
D
W
D
U-Series Air Circuit Breaker_ 13
U-Series
/ Air Circuit Breaker
Protection Trip Relay (OCR)
| Overview |
❶ LCD display window
❷ Fault indication LED
❷
❶
❺
❸
PTA: Pre-trip alarm
LTD: Long time delay
STD/INST: Short time or instantaneous tripping
GFT/ELT: Ground fault trip or earth-leakage trip
TAL: Temperature alarm
❸ Overload indication LED
❹ Function key
❹
❽
❻
❼
❾

❿



14
Reset: Fault reset
Hi/Low: Field test function
(Hi: STD/INST, Low: LTD)
Move
List: Secondary menu
Enter: Setting input
❺ Phase indication Iine
❻ Ir: Long time current setting knob
Tr: Long time tripping delay setting knob
❼ Isd: Short time current setting knob
Tsd: Short time tripping delay setting knob
❽ Ii: Instantaneous current setting knob
❾ GFT/STD, MCR setting knob
❿ Ip: Pre-trip alarm current setting knob
Tp: Pre-trip alarm delay setting knob
 Ig: Ground fault current setting knob
Tg: Ground fault tripping delay setting knob
 Rated current setting knob
 Test jack
 Earth leakage pick-up and
tripping delay setting knob
ACB
General feeder
Application
Generator
UPR-1L-GL
UPR-2L-GS
UPR-1D-GT
UPR-2L-GM
UPR-1S-AL
UPR-2S-AS
Control power
Self power
Long time delay (LTD)
Short time delay (STD)
Instantaneous trip (INST)
Pre trip alarm
Ground fault trip
Field test
Failsafe
True RMS detection
Fault indication LED
Overload indication LED
Display window







-













































-












Integrated instantaneous
contact (1a)

-
-

PTA: 1a
L/S/I/G: 2a

-
Individual continuous
contact (4a)
-



PTA: 1a
L/S/I/G: 2a
-
MCR
Temperature detection
Event/Fault recording
Earth leakage trip (ELT)
Communication

-


-







-

-
Externals
Power supply
Protection
Indication
Output contact
Optional
function
※ : Standard

LTD: 1a
S/I: 1a
PTA:1a



-
: Option
O
rdering codes
Model
UPR-1L-GL
UPR-2L-GS
UPR-1D-GT
UPR-2L-GM
UPR-1S-AL
UPR-2S-AS
UPR-1L-GL
UPR-2L-GS
UPR-1D-GT
UPR-2L-GM
UPR-1S-AL
UPR-2S-AS
Ordering codes
Frequency Complete parts
Spare part
of ACB/Cradle
50Hz
60Hz
33
35
36
37
38
39
43
45
46
47
48
49
UANS OCR33A/33J
UANS OCR35A/35J
UANS OCR36A/36J
UANS OCR37A/37J
UANS OCR38A/38J
UANS OCR39A/39J
UANS OCR43A/43J
UANS OCR45A/45J
UANS OCR46A/46J
UANS OCR47A/47J
UANS OCR48A/48J
UANS OCR49A/49J
Application
Specifications
for auto connection/manual connection type
for auto connection/manual connection type
for auto connection/manual connection type
for auto connection/manual connection type
for auto connection/manual connection type
for auto connection/manual connection type
for auto connection/manual connection type
for auto connection/manual connection type
for auto connection/manual connection type
for auto connection/manual connection type
for auto connection/manual connection type
for auto connection/manual connection type
UAN UAS












Mounting position







Inside of ACB body



U-Series Air Circuit Breaker_ 15
U-Series
/ Air Circuit Breaker
Protection Trip Relay (OCR)
| UPR-1L-GL |
•Overload protection
- Long time delay
•Short circuit protection
- Short time delay, instantaneous trip
- I2t on/off optional (for STD)
•Ground fault protection
- I2t on/off optional
•Self power
•1a DO (Digital output)
Characteristic
Ir: Long time current setting
tr: Long time tripping delay setting
Ir
Isd: Short time current setting
tr
tsd: Short time tripping delay setting
Ii: Instantaneous current setting
Isd
Ig I2t on
tg
Ig: Ground fault current setting
tsd
Ii
I2t off
I2t off
tg: Ground fault tripping delay setting
I2t on
 Protection
Current setting (Ir)
Long time
Time delay (tr)
Accuracy: ±15%
or below 100ms
Current setting (Isd)
Short time
Instantaneous
Time delay (tsd)
at 10×Ir
Accuracy: ±20%
Current setting (Ii)
Trip time
In = Ict×…
(A)
0.5
0.63
0.7
0.8
0.9
1
Ir = In×…
(A)
0.8
0.83
0.85
0.88
0.9
0.93
0.95
0.98
1
Non
(sec) 10.4
(sec) 0.5
(sec) 0.35
26.1
41.7
52
104
208
312
417
521
626
1.25
0.86
2
1.38
2.5
1.73
5
3.45
10
6.9
15
10.4
20
13.8
25
17.3
30
20.7
1.5
0.1
2
0.2
2.5
0.3
3
0.4
4
0.5
6
8
10
Non
tr at (1.5×Ir)
tr at (6.0×Ir)
tr at (7.2×Ir)
Isd = In×…
tsd
I2t off
I2t on
Min. trip time (msec)
(I2t off)
Max. trip time (msec)
Ii = In×…
(A)
16
Time delay (tg)
at 1×In
Accuracy: ±20%
0.1
0.2
0.3
0.4
0.5
20
80
80
140
160
240
260
340
360
440
460
540
2
3
4
6
8
10
12
15
Non
0.7
0.8
1
below 50ms
Pick-up (Ig)
Accuracy: ±15% (Ig>0.4In) Ig = Ict×…
±20% (Ig≤0.4In)
Ground fault
1
(A)
(sec) 0.05
(sec) 0.05
tg
(I2t off)
I2t off
I2t on
0.1
0.2
0.3
0.4
0.5
0.6
(sec) 0.05
(sec) 0.05
0.1
0.2
0.3
0.4
0.5
0.1
0.2
0.3
0.4
0.5
(A)
Min. trip time (msec)
20
80
160
260
360
460
Max. trip time (msec)
80
140
240
340
440
540
Non
ACB
| UPR-2L-GS, UPR-2L-GM |
•Overload protection
•Event recording
- Long time delay
- Short time delay, instantaneous trip
- I2t on/off optional (for STD)
•Short circuit protection
- Short time delay, instantaneous trip
- I2t on/off optional (for STD)
•Pre-trip alarm
- Prevent unnecessary over load trip
according to rated current (In)
•Ground fault protection
•Field test
- I2t on/off optional
•Realization of protective
coordination by ZSI (Zone selective
interlocking)
- Simulation of long time, short time,
instantaneous delay
•4a(3a) DO (Digital output)
- 4a (UPR-2L-GS)
- 3a (UPR-2L-GM)
•Fault recording
- Records max. up to 10 fault information
about fault type, fault phase, fault
valve, occurrence time of fault
Characteristic
Ir: Long time current setting
tr: Long time tripping delay setting
Ir
IP
Isd: Short time current setting
tr
tsd: Short time tripping delay setting
Ii: Instantaneous current setting
Tp
I2t off
tg: Ground fault tripping delay setting
I2t on
Isd
Ig I2t on
tg
Ig: Ground fault current setting
tsd
tp: Pre-trip alarm delay setting
Ii
I2t off
Ip: Pre-trip alarm current setting
 Protection
Current setting (Ir)
Long time
Time delay (tr)
Accuracy: ±15%
or below 100ms
Current setting (Isd)
Short time
Instantaneous
Time delay (tsd)
at 10×Ir
Accuracy: ±15%
Current setting (Ii)
Trip time
Pick-up (Ig)
Ground fault
Time delay (tg)
at 1×In
Accuracy: ±15% (Ig>0.4In)
±20% (Ig≤0.4In)
Current setting (Ip)
Pre trip alarm Accuracy: ±15%
Time delay (tp)
In = Ict×…
(A)
0.5
0.63
0.7
0.8
0.9
1
Ir = In×…
(A)
0.8
0.83
0.85
0.88
0.9
0.93
0.95
0.98
1
Non
(sec) 10.4
(sec) 0.5
(sec) 0.35
26.1
41.7
52
104
208
312
417
521
626
1.25
0.86
2
1.38
2.5
1.73
5
3.45
10
6.9
15
10.4
20
13.8
25
17.3
30
20.7
1.5
0.1
2
0.2
2.5
0.3
3
0.4
4
0.5
6
8
10
Non
tr at (1.5×Ir)
tr at (6.0×Ir)
tr at (7.2×Ir)
Isd = In×…
tsd
I2t off
I2t on
1
(A)
(sec) 0.05
(sec) 0.05
Min. trip time (msec)
(I2t off)
Max. trip time (msec)
(A)
Ii = In×…
0.1
0.2
0.3
0.4
0.5
20
80
80
140
160
240
260
340
360
440
460
540
2
3
4
6
8
10
12
15
Non
0.3
0.2
0.4
0.3
0.5
0.4
0.6
0.5
0.7
0.8
1
Non
Non
below 50ms
In = Ict×…
I2t off
tg
I2t on
0.1
(sec) 0.05
(sec) 0.05
0.2
0.1
0.1
0.2
0.3
0.4
0.5
Min. trip time (msec)
(I2t off)
Max. trip time (msec)
20
80
80
140
160
240
260
340
360
440
460
540
Ip = In×…
0.6
0.65
0.7
0.75
0.8
0.85
0.9
0.95
1
5
10
15
20
40
60
80
120
160
tp
(A)
(sec)
U-Series Air Circuit Breaker_ 17
U-Series
/ Air Circuit Breaker
Protection Trip Relay (OCR)
| UPR-1D-GT |
•Overload protection
•Event recording
- Long time delay
- Records events of device related to
setting change, operation and state
change (Max. up to 10)
•Short circuit protection
- Short time delay, instantaneous trip
- I2t on/off optional (for STD)
•Pre trip alarm
- Prevent unnecessary over load trip
according to rated current (In)
•Ground fault protection
- I t on/off optional
2
•Realization of protective
coordination by ZSI (Zone selective
interlocking)
•Field test
•Fault recording
•4a DO (Digital output)
-R
ecords max. up to 10 fault information
about fault type, fault phase, fault
valve, occurrence time of fault
- Simulation of long time, short time,
instantaneous delay
•Communication: Modbus-RTU/RS-485
•Earth leakage trip (Optional)
Characteristic
Ir: Long time current setting
Ir
IP
tr: Long time tripping delay setting
Isd: Short time current setting
tr
tsd: Short time tripping delay setting
Tp
Ii: Instantaneous current setting
Isd
Ig I2t on
tg
I2t off
I2t on
tsd
tp: Pre-trip alarm delay setting
Ii
I2t off
tg: Ground fault tripping delay setting
Ig: Ground fault current setting
Ip: Pre-trip alarm current setting
 Protection
Current setting (Ir)
Long time
Time delay (tr)
Accuracy: ±15%
or below 100ms
Current setting (Isd)
Short time
Instantaneous
Ground fault
Time delay (tsd)
at 10×Ir
Accuracy: ±15%
Current setting (Ii)
Trip time
Pick-up (Ig)
Time delay (tg)
at 1×In
Accuracy: ±15%(Ig>0.4In)
±20%(Ig≤0.4In)
Current setting (Ip)
Pre trip alarm Time delay (Tp)
Accuracy: ±15%
Current setting (IΔn)
Earth leakage
Time delay (Δt)
(optional)
Accuracy: ±15% or below 40ms
18
In = Ict×…
Ir = In×…
tr at (1.5×Ir)
tr at (6.0×Ir)
tr at (7.2×Ir)
Isd = In×…
(A)
(A)
(sec)
(sec)
(sec)
(A)
(sec)
I2t off
tsd
(sec)
I2t on
Min. trip time (msec)
2
(I t off)
Max. trip time (msec)
Ii = In×…
(A)
Ig = Ict×…
I2t off
(sec)
tg
(sec)
I2t on
Min. trip time (msec)
2
(I t off)
Max. trip time (msec)
Ip = In×…
(A)
tp
(sec)
IΔn
Δt
Alarm time
Trip time
(A)
(msec)
(msec)
0.5 0.63
0.8 0.83
10.4 26.1
0.5 1.25
0.35 0.86
1
1.5
0.05 0.1
0.05 0.1
20
80
80
140
2
3
below 50ms
0.1
0.2
0.05 0.1
0.05 0.1
20
80
80
140
0.6 0.65
0.7
0.85
41.7
2
1.38
2
0.2
0.2
160
240
4
0.8
0.88
52
2.5
1.73
2.5
0.3
0.3
260
340
6
0.9
0.9
104
5
3.45
3
0.4
0.4
360
440
8
1
0.93
208
10
6.9
4
0.5
0.5
460
540
10
0.3
0.2
0.2
160
240
0.7
0.4
0.3
0.3
260
340
0.75
0.5
0.4
0.4
360
440
0.8
0.95
312
15
10.4
6
0.98
417
20
13.8
8
1
521
25
17.3
10
12
15
Non
0.6
0.5
0.5
460
540
0.85
0.7
0.8
1
Non
0.9
0.95
1
Non
5
10
15
20
40
60
80
120
160
0.5
140
60
1
230
140
2
350
230
3
800
350
5
950
800
10
80
20
120
30
160
Non
Non
626
30
20.7
Non
ACB
| UPR-1S-AL |
•Overload protection
- Long time delay
•Short circuit protection
- Short time delay, instantaneous trip
- I2t on/off optional (for STD)
•Ground fault protection
- I2t on/off optional (for STD)
•Self power
•1a DO (Digital output)
Characteristic
Ir: Long time current setting
tr: Long time tripping delay setting
Ir
Isd: Short time current setting
tr
tsd: Short time tripping delay setting
Ii: Instantaneous current setting
I2t on
Isd
tsd
Ii
I2t off
 Protection
Current setting (Ir)
Long time
Time delay (tr)
Accuracy: ±15%
or below 100ms
Current setting (Isd)
Short time
Instantaneous
Time delay (tsd)
at 10×Ir
Accuracy: ±15%
Current setting (Ii)
Trip time
In = Ict×…
Ir = In×…
(A)
1.1
1.15
1.2
1.25
50
60
70
80
100
120
(sec) 10
(sec) 0.99
15
1.49
20
1.99
25
2.48
30
2.98
35
3.48
40
3.97
50
4.97
60
5.96
1
(A)
(sec) 0.05
(sec) 0.05
1.5
0.1
2
0.2
2.5
0.3
3
0.4
3.5
0.5
4
4.5
5
12
15
Non
(sec)
tr at (1.2×Ir)
tr at (3×Ir)
Isd = In×…
tsd
I2t on
20
40
tr at (1.05×Ir)
I2t off
(0.5-1.0) x1% unit, or 1A unit
0.7
0.8
0.9
1
1.05
30
(A)
Min. trip time (msec)
(I2t off)
Max. trip time (msec)
Ii = In×…
(A)
0.1
0.2
0.3
0.4
0.5
20
80
80
140
160
240
260
340
360
440
460
540
2
3
4
6
8
10
Non
Non
below 50ms
U-Series Air Circuit Breaker_ 19
U-Series
/ Air Circuit Breaker
Protection Trip Relay (OCR)
| UPR-2S-AS |
•Overload protection
•Event recording
- Long time delay
- Records events of device related to
setting change, operation and state
change (Max. up to 10)
•Short circuit protection
- Short time delay, instantaneous trip
- I2t on/off optional (for STD)
•Realization of protective
coordination by ZSI (Zone selective
interlocking)
•Pre trip alarm
- Prevent unnecessary over load trip
according to rated current (In)
•Field test
- Simulation of long time, short time,
instantaneous delay
•Fault recording
-R
ecords max. up to 10 fault information
about fault type, fault phase, fault
valve, occurrence time of fault
•3a DO (Digital output)
Characteristic
Ir: Long time current setting
tr: Long time tripping delay setting
Ir
IP
Isd: Short time current setting
tr
tsd: Short time tripping delay setting
Ii: Instantaneous current setting
Tp
Isd
tp: Pre-trip alarm delay setting
I2t on
Ip: Pre-trip alarm current setting
tsd
Ii
I2t off
 Protection
Current setting (Ir)
Long time
Time delay (tr)
Accuracy: ±15%
or below 100ms
Current setting (Isd)
Short time
Instantaneous
Ground fault
20
Time delay (tsd)
at 10×Ir
Accuracy: ±20%
Current setting (Ii)
Trip time
In = Ict×…
Ir = In×…
(A)
1.1
1.15
1.2
1.25
50
60
70
80
100
120
(sec) 10
(sec) 0.99
15
1.49
20
1.99
25
2.48
30
2.98
35
3.48
40
3.97
50
4.97
60
5.96
1
(A)
(sec) 0.05
(sec) 0.05
1.5
0.1
2
0.2
2.5
0.3
3
0.4
3.5
0.5
4
4.5
5
(sec)
tr at (1.2×Ir)
tr at (3×Ir)
Isd = In×…
tsd
I2t on
20
40
tr at (1.05×Ir)
I2t off
(0.5-1.0) x1% unit, or 1A unit
0.7
0.8
0.9
1
1.05
30
(A)
Min. trip time (msec)
(I2t off)
Max. trip time (msec)
Ii = In×…
(A)
0.1
0.2
0.3
0.4
0.5
20
80
80
140
160
240
260
340
360
440
460
540
2
3
4
6
8
10
12
15
Non
Non
Non
below 50ms
Current setting (Ip)
Ip = In×…
Time delay (Tp)
Accuracy: ±15%
tp
(A)
(sec)
0.7
0.75
0.8
0.85
0.9
0.95
1
1.05
1.1
1
5
10
15
20
25
30
35
40
Non
ACB
| Operation characteristics |

Long time delay (LTD)
t
Ir
tr

t
Ir
I
tr
t t
Ig
Ir

Short time delay (STD)
tr
I
I2t on
I2t off
Isd
Tsd
I I
I2t on
t
t
Time delay setting
Ig2t on
•L type
- Standard operating time (sec) is based
the time of 600%×[Ir] with inverse time operation.
Ig2on
t off
- Setting range: 0.5, 1.25,Ig2, 2.5, 5, 10, 15, 20, 25, 30sec (10 modes)
- The breaker is tripped
t at ±15% of setting time.
Tg
•S type
I
- Standard operating time (sec) is based on the time of 120%×[Ir] with inverse time operation.
- Setting range: 10, 15, 20, 25, 30, 35, 40, 50, 60sec (9 modes)
- The breaker is tripped at ±15% of setting
Ig2t ontime.
t t
t
Standard current setting
•L type
- The scale is marked as magnification of [In].
- Setting range: (Non, 0.8, 0.83, 0.85, 0.88, 0.9, 0.93, 0.95, 0.98, 1.0)×In (10 modes)
- No protection in case of non setting of [Ir].
- The breaker is not tripped below 105% of [Ir], and tripped at 120%.
•S type
t
- Setting range: (Non, 0.7, 0.8, 0.9, 1.0, 1.05, 1.1, 1.15, 1.2, 1.25 )×In (8 modes)
- The breaker is tripped above 100% of [Ir].
Isd
Tsd
I2t off
I
I2t on
Isd
Tsd
Ig2t off
Standard current setting
•L type
Tg
- The scale is marked as magnification of [In]. I
Ig2t on
- Setting range: (Non, 1, 1.5, 2, 2.5, 3, 4, 6, 8, 10)×In (10 modes)
•S type
Ig2t off
I∆ n
Ig
- The scale is marked as magnification of [In].
- Setting range: (Non,
t 1, 1.5,T2,g 2.5, 3, 3.5, 4, 4.5, 5)×In (10 modes)
∆T
I I
 Time delay setting
•L type
- Standard operating time (msec) is based on the time of 120%×[Isd] with definite time operation.
- Setting range: 50, 100, 200, 300, 400, 500msec (6 modes)
t curveI∆applied
- 1000% of inverse time
in case of inverse time (I2t on) setting.
n
•S type
t
- Standard operating time (msec) is based on the time of 120%×[Isd] with definite time operation.
∆T
- The range of set time is 50, 100, 200, 300, 400, 500msec (6 step).
I
- 500% of inverse time curve applied in case of inverse time (I2t on) setting.
I2t off
I∆ n
Instantaneous trip (INST)
t

Ii I
Tp(S type)
Ip
Standard current setting ∆T
t as magnification of [In]. I
- The scale is marked
Tp
- Setting range: (Non, 2, 3, 4, 6, 8, 10, 12, 15)×In (9I modes)
- No protection in case of non setting of [Ii].
I

Time delay setting
Tp(S type)
- Total breaking time is below 50ms.
t
Ip
t
Ii
Tp
I
I
Tp(S type)
Ip
Ii
Tp
I
I
U-Series Air Circuit Breaker_ 21
U-Series
/ Air Circuit Breaker
Protection Trip Relay (OCR)
| Operation characteristics |

Ground fault trip (GFT)

Time delay setting
•L type
- Standard operating time (msec) is based on the time of 120%×[Ig] with definite time operation.
- Setting range: 50, 100, 200, 300, 400, 500msec (6 modes)
- Inverse time operated with 100% of [Ict] standard in case of [I2t on] setting.
- The breaker is tripped at ±15% of setting time.
t
Ig2t on
Ig2t off
Ig
t
Standard current setting
•L type
- The scale is marked as magnification of OCR rated primary current [ICT].
- Setting range: (Non, 0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 1.0)×[ICT] (10 modes)
Tg
I
Ig2t on
Ig2t off
tt Ig

Earth leakage trip (ELT)
Ig2t on
Ig2t off

I
Ig
t
I∆ n
Standard current setting
•L type
- The scale is marked as magnification of OCR rated primary current [ZCT].
- Setting range: (Non, 0.5, 1, 2, 3, 5, 10, 20, 30[A]) (9 modes)
Tg
T∆T
g
II
Time delay setting
•L type
- Settings within its alarm range will prevent its breaker from tripping but activating its alarm.
- Trip time: 60, 140, 230, 350, 800msec (5 modes)
- Alarm time: 140, 230, 350, 800, 950msec (5 modes)
I∆ n
t
t
∆T
I
I∆ n Tp(S type)
Ip
∆T
tPre-trip alarm (PTA)
I
Tp
I
Tp(S type)
t Ip
I
Tp(S type)
Ip
Tp
I
Standard current setting
•L type
- The scale is marked as magnification of [In] with definite time operation.
- Setting range: (Non, 0.6, 0.65, 0.7, 0.75, 0.8, 0.85, 0.9, 0.95, 1.0)×In (10 modes)
•S type
- The scale is marked as magnification of [In] with inverse time operation.
- Setting range: (Non, 0.7, 0.75, 0.8, 0.85, 0.9, 0.95, 1.0, 1.05, 1.1)×In (10 modes)

Tp
22

Time delay setting
•L type
- Standard operating time (sec) is based on the time of 100%×[Ip].
- Setting range: 5, 10, 15, 20, 40, 60, 80, 120, 160, 200sec (10 modes)
•S Type
- Standard operating time (sec) is based on the time of 120%×[Ip].
- Setting range: 1, 5, 10, 15, 20, 25, 30, 35, 40sec (9 modes)
ACB
| Circuit diagrams |
UPR-1L-GL
NCT
k ℓ
T
S
R
R
S
T
21
29 30
N L/S
I/G
NCT NCT
1
2
UPR-1L-GL
CT3
Rn Sn Tn Nn Ac
A
C TN T P
TP
CT2
MHT
CT1
TN
1a for MCR
Rn
Sn
22
Tn
UPR-2L-GS
AC,DC100-250V
S0 - S2
Source
NCT
k ℓ
S
R
T
R
S
T
N
+
21 23
29 30
19
L PT
NCT NCT
1
2
S2
-
UPR-2L-GS
CT3
Rn Sn Tn Nn Ac S/I G/E ZI
1
ZI
2
ZO ZO
2
1
A
C TN TP S 0
TP
CT2
MHT
CT1
TN
1a for MCR
Rn
Sn
Tn
22 24 26 31 32 33 34
+
In
ZSI
20
+ Out
U-Series Air Circuit Breaker_ 23
U-Series
/ Air Circuit Breaker
Protection Trip Relay (OCR)
| Circuit diagrams |
UPR-1D-GT
AC,DC100-250V
S0 - S2
Source
ZCT
NCT
k ℓ k ℓ
T
S
R
21 23
R
S
T
N
L P/T
+
-
27 28 29 30
19
ELT ELT NCT NCT
2
1
2 1
S2
UPR-1D-GT
CT3
ZI ZO
2
1
Rn Sn Tn Nn Ac S/I G/E ZI
1
ZO COM COM
2
A
C TN TP S 0
TP
CT2
MHT
CT1
TN
1a for
MCR
Rn
Sn
20
22 24 26 31 32 33 34 35 36
Tn
+
In
ZSI
+ - + Out Communication
UPR-2L-GM
AC,DC100-250V
S0 - S2
Source
NCT
k ℓ
S
R
T
R
S
T
+
21 23
29 30
19
N L/S PT
I/G
NCT NCT
1
2
S2
UPR-2L-GM
CT3
ZI
Rn Sn Tn Nn Ac1 Ac2 L/S
I/G 1
ZI
2
ZO ZO
2
1
A
C TN TP S 0
TP
CT2
MHT
CT1
TN
1a for MCR
Rn
Sn
Tn
22 24 26 31 32 33 34
+
24
In
ZSI
+ Out
20
-
ACB
UPR-1S-AL
T
S
R
21
R
S
T
L/
N SI
UPR-1S-AL
CT3
Rn Sn Tn Nn Ac
A
C TN T P
TP
CT2
MHT
CT1
TN
1a for MCR
Rn
Sn
22
Tn
UPR-2S-AS
AC,DC100-250V
S 0 - S2
Source
+
S
R
T
R
S
T
N
21 23
19
L PT
S2
-
UPR-2S-AS
CT3
Rn Sn Tn Nn Ac S/I ZI
1
ZI
2
ZO ZO
1 2
A
C TN TP S 0
TP
CT2
MHT
CT1
TN
1a for MCR
Rn
Sn
Tn
22 24 31 32 33 34
+
In
ZSI
20
+ Out
U-Series Air Circuit Breaker_ 25
U-Series
/ Air Circuit Breaker
Protection Trip Relay (OCR)
| Characteristic curves |
Hour
General feeder
4
3
❶
❹
2
1
50
40
30
❺
❷
Minute
20
10
8
6
5
4
3
❸
2
Operating time
1
50
40
30
20
10
8
6
5
4
3
Second
2
1
0.8
0.6
0.5
0.4
0.3
500ms
500ms
50ms
50ms
0.2
0.1
0.08
0.06
0.0
0.05
0.04
0.03
0.02
Percent for rated primary current of OCR [ICT]
❶ Long time delay current setting range
❷ Short time delay current setting range
26
2500
3000
2000
1500
600
700
800
900
1000
500
400
250
300
200
150
125
60
70
80
90
100
50
60
70
80
90
100
40
30
20
15
7
8
9
10
0.01
0.008
0.006
0.005
Percent for base current of OCR [Io]
❸ Instantaneous tripping current setting range
❹ Ground fault trip current setting range
❺ Pre-trip alarm current setting range
ACB
Hour
Generator
❶
4
3
2
1
50
40
30
❹
Minute
20
10
8
6
5
4
3
❷
2
Operating time
1
50
40
30
❸
20
10
8
6
5
4
3
Second
2
1
0.8
0.6
0.5
0.4
0.3
500ms
0.2
0.1
0.08
0.06
0.05
0.0
0.04
0.03
50ms
0.02
2500
3000
2000
1500
600
700
800
900
1000
500
400
250
300
200
150
125
50
60
70
80
90
100
40
30
20
15
7
8
9
10
0.01
0.008
0.006
0.005
Percent for base current of OCR [Io]
❶ Long time delay current setting range
❷ Short time delay current setting range
❸ Instantaneous tripping current setting range
❹ Pre-trip alarm current setting range
U-Series Air Circuit Breaker_ 27
U-Series
/ Air Circuit Breaker
Protection Trip Relay (OCR)
| Zone selective interlock function |
Zone selective interlocking drops delay time that eliminates faults for breakers.
It minimizes the shock that all kinds of electric machinery get under fault conditions.
 Example
 In case of that short time-delay or ground fault accident occurs at ZSI built in system, the breaker at accident site
sends ZSI signal to halt upstream breaker’s operation.
 To eliminate a breakdown, trip relay of ACB at accident site activates trip operation without time delay.
 The
upstream breaker that received ZSI signal adhere to pre-set short time-delay or ground fault time delay for
protective coordination in the system. However upstream breaker that did not receive its signal will trip instantaneously.
 For ordinary ZSI operation, it should arrange operation time accordingly so that downstream circuit breakers will
react before upstream ones under overcurrent/short time delay/ground fault situations.
 ZSI connecting line needs to be maximum 3m.
ACB 1
Out
Zone 1
In
ACB 2-1
ACB 2-2
Out
Zone 2
Fault A
In
ACB 3-1
Zone 3
ZSI connecting
28
ACB 3-2
ACB 3-N
Out
Out
In
In
Fault B
Out
In
ACB
| System diagram |
R
S
T
N
ACB trip
ACB
Display
(LCD, LED)
MHT
Rogowski
CT
Measurement
part
Trip
operation
Relay
selection
PTA contact
MCU
processing
LTD contact
External
contact
STD/INST contact
GFT contact
Power
CT
Self power
COMMON contact
Trip relay
ZSI
ZCT
110V - 220V
Earth
leakage
COMM.
SMPS
power
Test
terminal
ZSI output +
ZSI output ZSI input +
ZSI input -
RS-485 +
RS-485 -
| Communication function |
 Modbus-RTU / RS-485
•Operation mode: Differential
•Distance: Max.1.2km
•Cable: RS-485 shielded twist 2-pair cable
•Baud rate: 9,600, 19,200, 38,400 bps
•Transmission method: Half-duplex
•Termination: 150Ω
SCADA system
Modbus/RS-485
U-Series Air Circuit Breaker_ 29
U-Series
/ Air Circuit Breaker
Accessories
| Overview |
Ordering codes
Item
Motor
Spring charge switch
Closing coil
Trip coil
Double trip coil
Trip supervision
coil
UVT coil
(Instantaneous type)
30
Complete
parts of
ACB/Cradle
M1
Application
Specifications
Spare part
UAN UAS
UANS M1
AC/DC110V


M2
UANS M2
AC/DC220V


M3
UANS M3
AC380V


M4
UANS M4
AC440V


M7
UANS M7
DC24V


M8
UANS M8
DC48V


M9
UANS M9
DC125V


B6
UANS B6


C1
UANS C1
AC/DC110V


C2
UANS C2
AC/DC220V



C3
UANS C3
AC380V

C4
UANS C4
AC440V


C7
UANS C7
DC24V


C8
UANS C8
DC48V


C9
UANS C9
DC125V


S1
UANS S1
AC/DC110V


S2
UANS S2
AC/DC220V


S3
UANS S3
AC380V


S4
UANS S4
AC440V


S7
UANS S7
DC24V


S8
UANS S8
DC48V


S9
UANS S9
DC125V


S1
UANS SS1
AC/DC110V


S2
UANS SS2
AC/DC220V


S3
UANS SS3
AC380V


S4
UANS SS4
AC440V


S7
UANS SS7
DC24V


S8
UANS SS8
DC48V


S9
UANS SS9
DC125V


T1
UANS T1
AC/DC110V


T2
UANS T2
AC/DC220V
T3
UANS T3
AC380V

T4
UANS T4
AC440V

T7
UANS T7
DC24V

T8
UANS T8
DC48V

T9
UANS T9
DC125V

U1
UANS U1
AC/DC110V


U2
UANS U2
AC/DC220V


U3
UANS U3
AC380V


U4
UANS U4
AC440V


U7
UANS U7
DC24V


U8
UANS U8
DC48V


U9
UANS U9
DC125V


Mounting position
Page
Inside of ACB body
36
Inside of ACB body
36
Inside of ACB body
37
Inside of ACB body
38
Inside of ACB body
39
Inside of ACB body
40
Inside of ACB body
41
ACB
Ordering codes
Item
UVT time delay
controller
UVT time delay
controller
&
UVT coil
(Instantaneous type)
Auxiliary switch
Test jumper
Position switch
Application
Complete
parts of
ACB/Cradle
-
UANS UT1
AC/DC110V


-
UANS UT2
AC/DC220V


-
UANS UT3
AC380V


-
UANS UT4
AC440V





Specifications
Spare part
UAN UAS
Page
Outside of ACB body
& cradle
42
-
UANS UT7
DC24V
-
UANS UT8
DC48V

-
UANS UT9
DC125V


V1
UANS V1
AC/DC110V


V2
UANS V2
AC/DC220V


V3
UANS V3
AC380V


V4
UANS V4
AC440V


V7
UANS V7
DC24V

V8
UANS V8
DC48V

 •UVT coil: inside of
ACB body

V9
UANS V9
DC125V

-
UANS A3A
Auto connection type, 3a+3b
-
UANS A3J
Manual connection type, 3a+3b
A5
UANS A5A
Auto connection type, 5a+5b


A5
UANS A5J
Manual connection type, 5a+5b


•Controller: outside of
ACB body & cradle
42



AA
UANS AA
Additional 1a1b (Max. 6a6b)


-
UANS AJ
for auto connection type


AQ
UANS AQ
Test 1C, Connected 1C


AR
UANS AR
Connected 2C


AS
UANS AS
Test 2C


AT
UANS AT
Isolated 1C, Inserted 1C


AU
UANS AU
Inserted 2C


AV
UANS AV
Isolated 2C


P4
UANS P4
Test 2C, Connected 2C


PS
UANS PS
Isolated 1C, Test 1C, Connected 2C


PQ
UANS PQ
Inserted 1C, Isolated 1C, Test 1C, Connected 1C


PR
UANS PR
Inserted 1C, Isolated 1C, Test 3C, Connected 3C


P8
UANS P8
Inserted 2C, Isolated 2C, Test 2C, Connected 2C


Condenser trip
device (CTD)
-
UANS CTD1
AC/DC110V


-
UANS CTD2
AC/DC220V


Lifting lug
-
UANS AL
2EA/SET (supplied as standard only for C frame)


-
UANS DUA3
A frame, 630-2,000A, 3P


-
UANS DUA4
A frame, 630-2,000A, 4P


Dummy ACB
Mounting position
-
UANS DUB3
B frame, 630-4,000A, 3P


-
UANS DUB4
B frame, 630-4,000A, 4P


-
UANS DUC3
C frame, 3,200-5,000A, 3P


-
UANS DUC4
C frame, 3,200-5,000A, 4P


Inside of ACB body
43
43
Right side of cradle
44
45
Outside of ACB body & cradle
46
Outside of ACB body
& cradle
46
U-Series Air Circuit Breaker_ 31
U-Series
/ Air Circuit Breaker
Accessories
| Overview |
Ordering codes
Item
Mechanical
interlock kit
Mechanical
interlock kit
& ACB internal
interlock part
Terminal busbar
Termanal busbar
for fixed type
Termanal busbar
for draw-out type
32
Complete
parts of
Spare part
ACB/Cradle
UANS DWB1
Application
Specifications
for Draw-out type, 2way interlock
UAN UAS
Mounting position
Page
Outside of ACB body
& cradle
47

-
UANS DWB2
for Draw-out type, 3way interlock

-
UANS FAWB1
for A/C frame, Fixed type, 2way interlock

-
UANS FAWB2
for A/C frame, Fixed type, 3way interlock

-
UANS FBWB1 for B frame, Fixed type, 2way interlock

-
UANS FBWB2 for B frame, Fixed type, 3way interlock

-
UANS DWB1A for A frame, Draw-out type, 2way interlock

-
UANS DWB2A for A frame, Draw-out type, 3way interlock

-
UANS DWB1B for B frame, Draw-out type, 2way interlock

-
UANS DWB2B for B frame, Draw-out type, 3way interlock

-
UANS DWB1C for C frame, Draw-out type, 2way interlock

-
UANS DWB2C for C frame, Draw-out type, 3way interlock

-
UANS FWB1A
for A frame, Fixed type, 2way interlock

-
UANS FWB2A
for A frame, Fixed type, 3way interlock

-
UANS FWB1B for B frame, Fixed type, 2way interlock

-
UANS FWB2B for B frame, Fixed type, Wire type, 3way interlock

-
UANS FWB1C
for C frame, Fixed type, Wire type, 2way interlock

-
UANS FWB2C
for C frame, Fixed type, Wire type, 3way interlock

-
UANS HVA3
Horizontal/Vertical type 6EA for A frame, 630-1,600A, 3P


-
UANS HVA4
Horizontal/Vertical type 8EA for A frame, 630-1,600A, 4P


-
UANS HVB3
Horizontal/Vertical type 6EA for B frame, 630-3,200A, 3P


-
UANS HVB4
Horizontal/Vertical type 8EA for B frame, 630-3,200A, 4P


-
UANS FRA3F
Front type 6EA for A frame, 630-1,600A, 3P


-
UANS FRA4F
Front type 8EA for A frame, 630-16,00A, 4P


-
UANS FRB3F
Front type 6EA for B frame, 2,000-3,200A, 3P


-
UANS FRB4F
Front type 8EA for B frame, 2,000-3,200A, 4P


-
UANS FHVA3F
Front type 3EA & horizontal/Vertical type 3EA
for A frame, 630-1,600A, 3P


-
UANS FHVA4F
Front type 4EA & horizontal/Vertical type 4EA
for A frame, 630-1,600A, 4P


-
UANS FHVB3F
Front type 3EA & horizontal/Vertical type 3EA
for B frame, 630-3,200A, 3P


-
UANS FHVB4F
Front type 4EA & horizontal/Vertical type 4EA
for B frame, 630-3,200A, 4P


-
UANS FRA3
Front type 6EA for A frame, 630-1,600A, 3P


-
UANS FRA4
Front type 8EA for A frame, 630-1,600A, 4P


•Interlock kit: outside
of ACB body or cradle
47
•Interlock part: inside
of ACB body
-
UANS FRB3
Front type 6EA for B frame, 2,000-3,200A, 3P


-
UANS FRB4
Front type 8EA for B frame, 2,000-3,200A, 4P


-
UANS FHVA3
Front type 3EA & horizontal/Vertical type 3EA
for A frame, 630-1,600A, 3P


-
UANS FHVA4
Front type 4EA & horizontal/Vertical type 4EA
for A frame, 630-1,600A, 4P


-
UANS FHVB3
Front type 3EA & horizontal/Vertical type 3EA
for B frame, 630-3,200A, 3P


-
UANS FHVB4
Front type 4EA & horizontal/Vertical type 4EA
for B frame, 630-3,200A, 4P


48
Outside of ACB body
& cradle
48
Outside of ACB body
& cradle
48
ACB
Ordering codes
Item
Phase insulation
barrier
Complete
parts of
Spare part
ACB/Cradle
UANS 3PBAR
-

Terminal side of ACB
body & cradle
ON/OFF button cover with padlock hole
Outside of ACB body & cradle
UANS AM
Key lock device
AB
UANS AB
Control terminal
49


UANS OC
Arc shield
Page

-
Control terminal
protection cover
Mounting position
for 4P
AM
Safety shutter lock
UAN UAS
for 3P
ON/OFF button lock
OCR &
Alarm switch reset
device
Specifications
UANS 4PBAR
OCR portable checker
Wrong insertion
preventer
Application
Key lock device
49






Inside of ACB body
51


Outside of ACB body
& cradle
52
Inside of ACB body
53
Inside of cradle
54
Control terminal of cradle
55
Upper side of cradle
55
50
AW
UANS AW
BR
UANS BR
for OCR manual reset only


BA
UANS BA
for OCR manual reset & alarm switch reset


BM
UANS BM
for OCR auto reset & alarm switch reset


UANS AEA3
for A frame, 630-2,000A, 3P


UANS AEA4
for A frame, 630-2,000A, 4P


UANS AEB3
for B frame, 630-4,000A, 3P


UANS AEB4
for B frame, 630-4,000A, 4P


UANS AEC3
for C frame, 3,200-5,000A, 3P


UANS AEC4
for C frame, 3,200-5,000A, 4P


UANS BC
for auto connection control terminal


UANS AXA3
for A frame, 630-2,000A, 3P


UANS AXA4
for A frame, 630-2,000A, 3P


UANS AXB3
for B frame, 630-4,000A, 3P


UANS AXB4
for B frame, 620-4,000A, 4P


UANS AXC3
for C frame, 3,200-5,000A, 3P


UANS AXC4
for C frame, 3,200-5,000A, 4P


A
UANS CJ
Auto connection terminal


J
UANS MJ
Manual connection terminal


Inside of ACB body
& cradle
56
AE
BC
AX
Short "b" contact
AK
UANS AK


Control terminal of cradle
56
Counter
-
UANS AD
Counter


Inside of ACB body
57
UANS AF
for ACB body and cradle


UANS AFB
for ACB body


57

Outside of ACB body &
cradle
Fixing block
AF
UANS AFC
for cradle

UANS RTU
Temperature detection module

-
UANS RTUN
Temperature detection module with
temperature sensor

-
UANS RCU
Remote operation module

-
UANS RCTU
Remote operation & temperature detection
module

-
UANS RCTUN
Remote operation & temperature detection
module with temparature sensor

Temperature sensor
-
UANS TSN
Temperature sensor

Draw-in/out &
position lock device
-
UANS DR
Draw-in/out
handle
-
UANS HANDLE
-
UANS LHANDLE
-
UANS UHANDLE Universal joint type
-
Remote operation
& temparature
detection module
•Module: outside of
ACB body or cradle
58
•Sensor: inside of
cradle


Standard type


Long type




Inside of cradle
59
Inside of ACB body
60
60
U-Series Air Circuit Breaker_ 33
U-Series
/ Air Circuit Breaker
Accessories
| Overview |
Ordering codes
Item
Neutral CT
Application
Specifications
UAN UAS
for A frame, 630A


-
UANS NCTAH
for A frame, 800A


-
UANS NCTAJ
for A frame, 1,000A


-
UANS NCTAK
for A frame, 1,250A


-
UANS NCTAL
for A frame, 1,600A


-
UANS NCTBM
for B frame, 2,000A


-
UANS NCTBN
for B frame, 2,500A


-
UANS NCTBP
for B frame, 3,200A


-
UANS NCTBQ
for B frame, 4,000A


-
UANS NCTCQ
for C frame, 4,000A


Mounting position
Page
61
-
UANS NCTCS
for C frame, 5,000A


Door flange
-
UANS AG
for IP30


Dust cover
-
UANS DC
for IP52

62
ATS controller
-
UANS ATS
Automatic transfer switch & controller

OCR MCR wire
B8
UANS MCR
Inside of ACB body
63
-
Motor controller
-
UANS MCU
Inside of ACB body
-
Inside of ACB body
-
Inside of ACB body
-
Motor unit
Current
transformer (CT)
34
Complete
parts of
Spare part
ACB/Cradle
UANS NCTAT


-
UANS M1U
AC/DC110V


-
UANS M2U
AC/DC220V


-
UANS M3U
AC380V


-
UANS M4U
AC440V




-
UANS M7U
DC24V
-
UANS M8U
DC48V


-
UANS M9U
DC125V


I
UANS CTAI
for A frame, 80A


B
UANS CTAB
for A frame, 160A


O
UANS CTAO
for A frame, 200A


V
UANS CTAV
for A frame, 320A


E
UANS CTAE
for A frame, 400A


T
UANS CTAT
for A frame, 630A


H
UANS CTAH
for A frame, 800A


J
UANS CTAJ
for A frame, 1,000A


K
UANS CTAK
for A frame, 1,250A


L
UANS CTAL
for A frame, 1,600A


M
UANS CTAM
for A frame, 2,000A


E
UANS CTBE
for B frame, 400A


T
UANS CTBT
for B frame, 630A


H
UANS CTBH
for B frame, 800A


J
UANS CTBJ
for B frame, 1,000A


K
UANS CTBK
for B frame, 1,250A


L
UANS CTBL
for B frame, 1,600A


M
UANS CTBM
for A frame, 2,000A


N
UANS CTBN
for B frame, 2,500A


P
UANS CTBP
for B frame, 3,200A


Q
UANS CTCQ
for C frame, 4,000A


S
UANS CTCS
for C frame, 5,000A


Q
UANS CTDQ
for D frame, 4,000A


Panel door
62
ACB
Ordering codes
Item
Current
transformer (CT)
Arc chamber
MHT device
Draw-in/out
connection
terminal
Terminal clip
MOC switch
Protection trip
relay (OCR)
Complete
parts of
Spare part
ACB/Cradle
S
UANS CTDS
Application
Specifications
UAN UAS
for D frame, 5,000A


X
UANS CTDX
for D frame, 6,300A


-
UANS DIA
for A frame, C frame


-
UANS DIB
for B frame


-
UANS MHTU
MHT (Magnetic holding trigger) unit


-
UANS MHT
MHT (Magnetic holding trigger) coil only


-
UANS CLA16
for A frame, 630-1,600A


-
UANS CLA20
for A frame, 2,000A / C frame, 3,200-5,000A


-
UANS CLAB20
for B frame, 630-2,500A



-
UANS CLAB32
for B frame, 3,200A

-
UANS CLAB40
for B frame, 4,000A


-
UANS ISOL
5 clip


-
UANS ISOL4
4 clip


MC
UANS MOC
Mechanical operated cell switch 10a10b

33
UANS
OCR33A/33J
50Hz, UPR-1L-GL, for auto connection
/manual connection type


35
UANS
OCR35A/35J
50Hz, UPR-2L-GS, for auto connection
/manual connection type


36
UANS
OCR36A/36J
50Hz, UPR-1D-GT, for auto connection
/manual connection type

37
UANS
OCR37A/37J
50Hz, UPR-2L-GM, for auto connection
/manual connection type


38
UANS
OCR38A/38J
50Hz, UPR-1S-AL, for auto connection
/manual connection type


39
UANS
OCR39A/39J
50Hz, UPR-2S-AS, for auto connection
/manual connection type


43
UANS
OCR43A/43J
60Hz, UPR-1L-GL, for auto connection
/manual connection type


45
UANS
OCR45A/45J
60Hz, UPR-2L-GS, for auto connection
/manual connection type


46
UANS
OCR46A/46J
60Hz, UPR-1D-GT, for auto connection
/manual connection type

47
UANS
OCR47A/47J
60Hz, UPR-2L-GM, for auto connection
/manual connection type


48
UANS
OCR48A/48J
60Hz, UPR-1S-AL, for auto connection
/manual connection type


49
UANS
OCR49A/49J
60Hz, UPR-2S-AS, for auto connection
/manual connection type


Mounting position
Page
Inside of ACB body
-
Inside of ACB body
-
Inside of ACB body
-
Inside of ACB body
-
Terminal side of ACB
body & cradle
-
Outside of ACB body & cradle
-
Inside of ACB body
-
U-Series Air Circuit Breaker_ 35
U-Series
/ Air Circuit Breaker
Accessories
| Motor |
•Manual charging method and geared motor charging
by external power source.
•Operating voltage range: 85-110%
R
atings
 Wire ratings
Rated voltage
Rated current (A)
Rated voltage
DC110V
DC220V
1.2
0.5
Starting pick-up (A)
5-6 times of rated current
Revolutions per minute (RPM)
16±3
Charging time (sec)
within 5sec1)
Torque (kgf)
1
300kgf x cm
100
Insulation voltage (V/min)
1
Insulation resistance (MΩ)
AWG
AWG
Insulation
level (V)
18
600
18
600
15
Spring
charge
off sw.
15
M
charge
off sw.
-15-60
Ordering code
M
2
Complete parts
of ACB/Cradle
M1
M2
M3
M4
M7
M8
M9
2
2
16
16
16 part
Spare
UANS M1
UANS M2
UANS M3
UANS M4
UANS M7
UANS M8
UANS M9
Application
Specification
AC/DC110V
AC/DC220V
AC380V
AC440V
DC24V
DC48V
DC125V
| Spring charge switch |
•These contacts (No.15,16) are for delivering spring charge status to outside.
•Optional device mounted on the body.
•Ordering code: B6, UANS B6 (Spare part)
36
1
M
O
rdering code
Motor
DC110/220V
Insulation
level (V)
100Spring
※ 1) Charging time is within 10sec of rated, in case of DC24/48V.
Item
Source
100
Spring
charge
off sw.
Ambient temperature (˚C)
2,00015
DC24/48V
Source
Source
Rated watt (W)
C
onnection diagram
UAN
UAS














Mounting position
Inside of ACB body
ACB
| Closing coil |
•A control device which closes a circuit breaker
remotely, when applying 85-110% of rated control
voltage over 150ms to coil terminals (3,4).
O
rdering code
Ordering code
Item
Application
Complete parts
of ACB/Cradle
Spare part
C1
UANS C1
C2
UANS C2
C3
Closing coil
Specification
UAN
UAS
AC/DC110V


AC/DC220V


UANS C3
AC380V


C4
UANS C4
AC440V


C7
UANS C7
DC24V


C8
UANS C8
DC48V


C9
UANS C9
DC125V


Mounting position
Inside of ACB body
Source
PB
(Close)
R
atings
C
onnection diagram
Power supply (Vn)
3
Power consumption (VA)
Operating limits
DC (V)
AC (V)
24
-
0.85-1.1Vn
100-130
100-130
0.85-1.1Vn
200-250
200-250
0.85-1.1Vn
Inrush
Steady-state
OpeningSource
time
(ms)
300
10
60
PB
(Close)
3
Source
PB
(Close)
3
CC
W
ire ratings
Rated voltage (Vn)
DC24
ADC110/220
CC
AWG
Insulation level (V)
AWG
Insulation
level (V)
4
18
600
18
600
4
CC
4
U-Series Air Circuit Breaker_ 37
U-Series
/ Air Circuit Breaker
Accessories
| Trip coil |
•A control device which trips a circuit breaker
remotely, when applying 70-110% of rated control
voltage over 150ms to coil terminals (7,8).
O
rdering code
Ordering code
Item
Application
Complete parts
of ACB/Cradle
Spare part
S1
UANS S1
S2
UANS S2
S3
Trip coil
Specification
UAN
UAS
AC/DC110V


AC/DC220V


UANS S3
AC380V


S4
UANS S4
AC440V


S7
UANS S7
DC24V


S8
UANS S8
DC48V


S9
UANS S9
DC125V


Inside of ACB body
C
onnection diagram
Power consumption (VA)
Operating limits
AC (V)
24
-
0.7-1.1Vn
100-130
100-130
0.7-1.1Vn
200-250
200-250
0.7-1.1Vn
Source
PB(Open)
Power supply (Vn)
DC (V)
7
Inrush
Steady-state
Opening time
(ms)
300
10
40
Source
PB(Open)
R
atings
Mounting position
7
Source
PB(Open)
W
ire ratings
Rated voltage (Vn)
DC24
7
ADC110/220
AWG
Insulation level (V)
AWG
20
300
20
TC
TC
Insulation level (V)
300
8
8
TC
38
8
ACB
| Double trip coil |
•A control device which trips a circuit breaker doubly
from the outside.
•Not available with UVT (Under-voltage trip) coil when
installing double trip coil.
•Rated control voltage range 70-110%, applying
voltage over 150ms to coil terminals (9,10).
O
rdering code
Ordering code
Item
Application
Complete parts
of ACB/Cradle
Spare part
S1
UANS SS1
S2
UANS SS2
S3
Double trip coil
Specification
UAN
UAS
AC/DC110V


AC/DC220V


UANS SS3
AC380V


S4
UANS SS4
AC440V


S7
UANS SS7
DC24V


S8
UANS SS8
DC48V


S9
UANS SS9
DC125V


Inside of ACB body
C
onnection diagram
0.7-1.1Vn
100-130
100-130
0.7-1.1Vn
Source
200-250
200-250
0.7-1.1Vn
Source
7
W
ire ratings
Steady-state
Opening time
(ms)
300
10
40
ADC110/220
Insulation level (V)
AWG
20
300
20
Insulation level (V)
TC
7
9
TC
TC
8
10
9
300
TC
TC
8
7
Source
PB(Open)
Rated voltage (Vn)
AWG
Source
9
Source
DC24
Source
PB(Open)
-
PB(Open)
24
Inrush
PB(Open)
Power consumption (VA)
Operating limits
AC (V)
PB(Open)
Power supply (Vn)
DC (V)
PB(Open)
R
atings
Mounting position
TC
10
U-Series Air Circuit Breaker_ 39
8
10
U-Series
/ Air Circuit Breaker
Accessories
| Trip supervision coil |
•To trip the circuit breaker, 70-110% of rated control
voltage should be applied to both terminals (7,8) over
150ms.
•Add your selection (S1-S9) to main body's ordering
code and mark T1-T9 in option list.
•When using trip coil supervision, aux. contact is 3a3b
(Not available aux. switch 43/44, 53/54).
•Output contact is No.59.
O
rdering code
Ordering code
Application
Specification
Complete parts
of ACB/Cradle
Spare part
T1
UANS T1
AC/DC110V

T2
UANS T2
AC/DC220V

T3
UANS T3
AC380V

T4
UANS T4
AC440V

T7
UANS T7
DC24V

T8
UANS T8
DC48V

T9
UANS T9
DC125V

Trip supervision
coil
UAN
Operating limits7
AC (V)
24
-
0.7-1.1Vn
100-130
100-130
0.7-1.1Vn
200-250
200-250
Power consumption (VA)
Supervision
59
Inrush
Source
300
7
0.7-1.1Vn
W
ire ratings
Mounting position
Inside of ACB body
C
onnection diagram
PB(Open)
Power supply (Vn)
DC (V)
PB(Open)
Source
R
atings
UAS
Steady-state
Opening time
(ms)
10
40
Supervision
59
Source
PB(Open)
Item
7
TC
Rated voltage (Vn)
DC24
ADC110/220
AWG
Insulation level (V)
AWG
Insulation
level (V)
8
20
300
20
300
TC
8
40
TC
8
Supervision
59
ACB
| UVT coil |
•If the voltage of the main or the control power is
under 70% of the standard, UVT breaks the circuit
automatically.
•Connect instantaneous type with both terminals
(9,10) and connect with time delay type in order to
present time delay controller.
•- The circuit breaker is opened with trip unit power
supply voltages below 70%.
- The circuit breaker is closed with unit power supply
voltage above 85%.
•Instantaneous type can not be used with double trip
coil.
O
rdering code
Ordering code
Application
Complete parts
of ACB/Cradle
Spare part
U1
UANS U1
U2
UANS U2
U3
UAN
UAS
AC/DC110V


AC/DC220V


UANS U3
AC380V


U4
UANS U4
AC440V


U7
UANS U7
DC24V


U8
UANS U8
DC48V


U9
UANS U9
DC125VT2


COM
a
b
T1
Source
U1
U2
UVT
Controller
UVT Coil
(Instantaneous type)
Specification
PB(Open)
Item
C1
Mounting position
Inside of ACB body
C2
9
C
onnection diagram
110 (100-130)
220 (200-250)
220 (200-250)
-
380
-
440
Steady-state
Opening time
U1
COM
(ms)
a
U2
UVT
Above 0.85Vn Below 0.35Vn
b
300
10
T2
T1
C1
C2
60
9
U1
COM
a
b
T2
T1
Source
110 (100-130)
Inrush
PB(Open)
-
Power consumption (VA)
Drop
Source
24
Pickup
UVT
Controller
AC (V)
PB(Open)
Power supply (Vn)
DC (V)
U2
UVT
Controller
R
atings
C1
C2
9
10
W
ire ratings
UVT
UVT
Rated voltage (Vn)
DC24
ADC110/220
AC380/440
AWG
Insulation level (V)
AWG
Insulation level (V)
AWG
Insulation level (V)
20
300
20
300
20
600
10
10
U-Series Air Circuit Breaker_ 41
U-Series
/ Air Circuit Breaker
Accessories
| UVT time delay controller |
•Use of UVT time delay controller is recommended to
prevent tripping when the power supply network for
the trip unit is subject to brief voltage drops or power
supply failures.
•This device is possible to delay as (0.5, 1.0, 1.5, 3 sec).
•It can be mounted at the left side of cradle or the DIN
rail.
•Controller is mounted at cradle (Draw-out type) or
outside of main body (Fixed type).
O
rdering code
Application
UVT time delay
controller
UVT time delay
controller
&
UVT coil
(Instantaneous type)
COM
a
b
T2
T1
C
onnection & Operating time
AC/DC110V
AC/DC220V
AC380V
AC440V
DC24V
DC48V
U1 DC125V
U2
AC/DC110V
C1 AC/DC220V
C2
AC380V
9
AC440V
DC24V
DC48V
DC125V
UVT
C
onnection diagram
UAN
UAS




























RATED VOLTAGE :
Remote
trip
DELAY
TIME(S)
0
Pick up
Output-Contact
DELAY
TIME(S)
0
1.0
T1
T2
a
b
COM
1
2
3
4
5
CAUTION
Rated
Voltage
10
1.5
3.0C1
6
T2
a
1
C2
2U1
3U2
7
8
9
UVT Trip
0.5 1.0 1.5
0
10
T1
CAUTION
UVT Trip
UVT
Coil
9
UVT
Coil
1.0
0.5
1.5
3.0
Voltage
9
0.5
V
V
Remote
Pick up
trip Rated
Output-Contact
b
COM
C1
C2
U1
U2
4
5
6
7
8
9
[ 0.5 - 1.0 - 1.5 - 3 (sec) ]
0
0.5 1.0 1.5
3.0
Sec
T2
T1
Source
U2
•UVT coil: inside of
ACB body
U1
T2
T1
U2
C1
C2
9
128
142
RATED VOLTAGE :
TYPE : UANS UT
TYPE : UANS UT
COM
a
b
0
0
U1
•Controller: outside
of ACB body &
cradle
COM
a
b
PB(Open)
10
UVT
Controller
V Source
PB(Open)
V Source
Outside of ACB body
& cradle
C
onnection diagram
120
102
ACB UVT
ACB UVT
CONTROLLER
CONTROLLER
Mounting position
UVT
Controller
UANS UT1
UANS UT2
UANS UT3
UANS UT4
UANS UT7
UANS UT8
UANS UT9
UANS V1
UANS V2
UANS V3
UANS V4
UANS V7
UANS V8
UANS V9
Source
V1
V2
V3
V4
V7
V8
V9
Specification
UVT
Controller
Spare part
PB(Open)
Complete parts
of ACB/Cradle
Source
Ordering code
Item
C1
C2
3.0
Sec
9
UVT
2-Ø4.2, M4*25L
UVT
10
42
10
ACB
| Auxiliary switch |
•A contact to monitor On/Off position of ACB remotely.
•3a3b is provided as standard for UAS type and 5a5b is
standard for UAN type.
•Applicable AUX switch is up to 6a6b. Add AA on your order.
•When working with monitoring contact for trip coil the
AUX switch will be 3a3b. When working with OCR’s MCR
function it will be 4a5b. When both monitoring contact and
MCR function working together it will be 3a4b.
•When ordering short “b”additionally it will be attached to
‘b’contacts 51, 52 when the product is out. The additional
short b which enclosed in the product is applicable as the
number of the b contact.
•5a5b is separate product and available. Add UANS AS on
extra order.
R
atings
C
onnection diagram
Inductor
Motor
Wire ratings
AC125V
5A
0.7A
4A
1.3A
AWG
Insulation level (V)
AC250V
5A
0.5A
4A
0.8A
20
300
41 43 45 47 49 51 53 55 57 59
Ordering code
Application
Specification
Spare part
UAN UAS
-
UANS A3A
Auto connection type, 3a+3b

-
UANS A3J
Manual connection type, 3a+3b

A5
UANS A5A
Auto connection type, 5a+5b


A5
UANS A5J
Manual connection type, 5a+5b


AA
UANS AA
Additional 1a1b (Max. 6a6b)


Used for SHT supervision (Option)
Mounting
position
Inside of ACB
body
42 44 46 48 50 52 54 56 58 60
•A connecting device to make the body of auto connection
type operate separately.
Used for SHT supervision (Option)
42 44 46 48 50 52 54 56 58 60
Used for short “b” contact (Option)
Used for MCR(Option)
41 43 45 47 49 51 53 55 57 59
Used for SHT supervision (Option)
Used for short “b” contact (Option)
| Test jumper |
41 43 45 47 49 51 53 55 57 59
Used for MCR(Option)
Auxiliary
switch
Complete parts
of ACB/Cradle
Used for SHT supervision (Option)
Item
Used for MCR(Option)
O
rdering code
Used for SHT supervision (Option)
Lamp
Used for short “b” contact (Option)
Resistance
Used for SHT supervision (Option)
Load
W
ire ratings
•Ordering code: UANS AJ (Spare part)
42 44 46 48 50 52 54 56 58 60
U-Series Air Circuit Breaker_ 43
U-Series
/ Air Circuit Breaker
Accessories
| Position switch |
•This switch is for indicating the position of ACB in the
cradle. It is mounted on the side of cradle.
•Indicating position Connected/Test/Isol/Insert.
•Only one switch is applicable.
R
atings
Load
Resistance
Lamp
Inductor
Motor
AC125V
10A
1.5A
6A
2A
DC30V
6A
3A
6A
3A
DC125V
0.6A
0.1A
0.6A
0.1A
DC250V
0.3A
0.05A
0.3A
0.05A
 Composition
Ordering code
Item
Application
Specification
Complete parts
Spare part
of ACB/Cradle
AQ
AR
AS
AT
AU
AV
P4
PS
PQ
Connect
PR
P8 Test
Position
switch
UANS AQ
UANS AR
UANS AS
UANS AT
UANS
AU
Insert
IsolUANSTest
AV
UANS P4
UANS PS
UANS PQ
UANS PR
UANS P8
Test 1C, Connected 1C
Connected 2C
Test 2C
Isolated 1C, Inserted 1C
Inserted 2C
Connect
Isolated 2C
Test 2C, Connected 2C
Isolated 1C, Test 1C, Connected 2C
Inserted 1C, Isolated 1C, Test 1C, Connected 1C
Inserted 1C, Isolated 1C, Test 3C, Connected 3C
Inserted 2C, Isolated 2C, Test 2C, Connected 2C
Isol
Insert
Isol
 Position switch
Insert operating sequence
Insert
Isol
Connect
Test
Insert
Isol
Connect
Test
UAN UAS
Test




61







62 63
Connect
61
64
71
74
61
-




64






65
66
6481
84
71
Connection
Position
71-72 a
71-73 b
74-75 a
74-76 b
77-78 a
77-79 b
Connect
Test
Test
Isol
Isol
Insert
Insert
44
61
64
Isolation
Position
81-82 a
81-83 b
Insert
Position
91-92 a
91-93 b
74
81
Connect
Test
Insert
Test
Position
61-62 a
61-63 b
64-65 a
64-66 b
67-68 a
67-69 b
Connected
(1C)
(2C)
-
84
(2C)
(1C)
(1C)
(2C)
86(3C)
71
74
Mounting
position
(1C)
(2C)
Right side
of cradle
(2C)
(2C)
(1C)
(2C)
(3C)
81
84
72 73 75
62 76
63 65826683 85
72 86
73 75 76
Connection
Isolation
Test
Connection
Position Position PositionPosition
71-72 a 61-62 a 81-82 a71-72 a
71-73 b 61-63 b 81-83 b71-73 b
74-75 a 64-65 a Insert 74-75 a
74-76 b 64-66 b Position74-76 b
77-78 a 67-68 a 91-92 a77-78 a
77-79 b 67-69 b 91-93 b77-79 b
Test
Position
61-62 a
61-63 b
64-65 a
64-66 b
67-68 a
67-69 b
82 83 85 86
Isolation
Position
81-82 a
81-83 b
Insert
Position
91-92 a
91-93 b
63.5
84
62 63 65 66
62 63 65 66
Test
E
xterior
Isol
Connect
-
(1C)
(1C)
71
74
81
(2C)
(2C)
(1C)
(1C) (1C)
(2C) (2C)
(1C)
72
73 75 76 (1C)
82 83 85
Test
Position
61-62 a
61-63 b
64-65 a
64-66 b
67-68 a
67-69 b
C
onnection diagram
Inserted Isolated
72 73 75 76
Connection
Position
71-72 a
71-73 b
74-75 a
74-76 b
77-78 a
77-79 b
82 83 85 86
Isolation
Position
81-82 a
81-83 b
Insert
Position
91-92 a
91-93 b
ACB
| Condenser trip device |
•In case of using AC/DC power for trip control, it gets a
circuit breaker tripped once electrically when power
supply is broken down.
O
rdering code
Ordering code
Item
Complete parts
of ACB/Cradle
Spare part
Condenser trip
device (CTD)
-
UANS CTD1
-
UANS CTD2
Application
Specification
UAN
UAS
AC/DC110V


AC/DC220V


C
TD operating sequence
C
onnection diagram
6
1
Ø6
2-
7
R1
72
22
SA
R2
V
CDT
P
R3
7
3 4
•AC Input power NO. 1, 2
•CTD Trip power NO. 7(+), 5(-)
U
SW C1 NL
2
80
90
Source
N
PB(Open)
130
72
CONDENSER TRIP DEVICE
WITH RECTIFIER
Mounting position
5
•DC Normal power NO. 6(+), 5(-)
•Delay contact
NO. 3, 4
YC
R
atings
Rated input voltage
AC110V
AC220V
Normal charging voltage
DC145V
DC290V
Normal current capacity
DC2A
Rated frequency
50/60Hz
Delay circuit time
within 1.5sec
Applicable standards
8
IEC 60694 / KSC 4611
U-Series Air Circuit Breaker_ 45
U-Series
/ Air Circuit Breaker
Accessories
| Lifting lug |
•A device to make an ACB easy to shift.
•Hang it to both handles of the arc shield, cradle, and ACB.
•When handling products, please be sure to use crane. In
case of products under 3,200A and handling cradle only,
please comply with safety regulation.
•Offered 2ea of 1set as a standard in 5,000AF "C" frame.
O
rdering code
Ordering code
Application
Item
Complete parts
of ACB/Cradle
Spare part
Lifting lug
-
UANS AL
Specification
2EA/SET (Supplied as standard only for C frame)
UAN
UAS


Mounting position
Outside of ACB body & cradle
| Dummy ACB |
•The dummy ACB which is a frame to apply electric current can conduct
ACB’s function temporarily when the maintenance work takes long due to
malfunction.
•When connecting the dummy ACB please check the primary power is out
since the CB is close.
•The early stage of each frame is maximum rated current.
O
rdering code
Ordering code
Item
Dummy ACB
46
Complete parts
of ACB/Cradle
Spare part
-
UANS DUA3
-
UANS DUA4
-
Application
Specification
UAN
UAS
A frame, 630-2,000A, 3P


A frame, 630-2,000A, 4P


UANS DUB3
B frame, 630-4,000A, 3P


-
UANS DUB4
B frame, 630-4,000A, 4P


-
UANS DUC3
C frame, 3,200-5,000A, 3P


-
UANS DUC4
C frame, 3,200-5,000A, 4P


Mounting position
Outside of ACB body
& cradle
ACB
| Mechanical interlock kit |
•It is used to interlock closing and trip between two or
three breakers mechanically so as to prevent unintended
operation at the same time.
•The MI is a safety gear installed in ACB for distribution line
and it creates a mechanical interlock between two or three
circuit-breakers through each CB’s open/close work.
•To operate the MI every component linked to the MI unit
and the MI must be combined before use.
•MI unit is separate product. After installing ACB it is
additionally attached.
•When ordering B0 all components linked to the MI unit
are provided.
•Order other separate kits when having purchased only
ACB without B0.
O
rdering code
Ordering code
Item
Mechanical
interlock kit
Mechanical
interlock kit
& ACB internal
interlock part
Complete parts
of ACB/Cradle
Spare part
Application
Specification
UAN
-
UANS DWB1
for draw-out type, 2way interlock

-
UANS DWB2
for draw-out type, 3way interlock

-
UANS FAWB1
for A/C frame, fixed type, 2way interlock

-
UANS FAWB2
for A/C frame, fixed type, 3way interlock

-
UANS FBWB1
for B frame, fixed type, 2way interlock

-
UANS FBWB2
for B frame, fixed type, 3way interlock

-
UANS DWB1A
for A frame, draw-out type, 2way interlock

-
UANS DWB2A
for A frame, draw-out type, 3way interlock

-
UANS DWB1B
for B frame, draw-out type, 2way interlock

-
UANS DWB2B
for B frame, draw-out type, 3way interlock

-
UANS DWB1C
for C frame, draw-out type, 2way interlock

-
UANS DWB2C
for C frame, draw-out type, 3way interlock

-
UANS FWB1A
for A frame, fixed type, 2way interlock

-
UANS FWB2A
for A frame, fixed type, 3way interlock

-
UANS FWB1B
for B frame, fixed type, 2way interlock

-
UANS FWB2B
for B frame, fixed type, wire type, 3way interlock

-
UANS FWB1C
for C frame, fixed type, wire type, 2way interlock

-
UANS FWB2C
for C frame, fixed type, wire type, 3way interlock

UAS
Mounting position
Outside of ACB body
& cradle
•Interlock kit:
outside of ACB body
or cradle
•Interlock part:
inside of ACB body
U-Series Air Circuit Breaker_ 47
U-Series
/ Air Circuit Breaker
Accessories
| Terminal busbar |
Standard connection
Vertical
Horizontal
•U-Series ACB have the following front types:
Vertical, horizontal, top vertical-bottom
horizontal and top horizontal-bottom vertical
type. There are also P-types which have no
terminal cradle and fixed body type. For these
models (P and fixed body type) separate
terminal is additionally supplied.
Front
•Separate terminal is applicable for only
A-frame 630-1,600[A] and B-frame
2,000- 3,200[A].
Mixed connection (Top/Bottom)
Vertical/Horizontal
Horizontal/Vertical
Vertical/Front
Horizontal/Front
Front/Vertical
Front/Horizontal
 Ordering code
Ordering code
Item
Terminal
busbar
Terminal
busbar
for fixed type
Terminal
busbar
for draw-out
type
48
Complete parts
of ACB/Cradle
Spare part
-
UANS HVA3
UANS HVA4
UANS HVB3
UANS HVB4
UANS FRA3F
UANS FRA4F
UANS FRB3F
UANS FRB4F
UANS FHVA3F
UANS FHVA4F
UANS FHVB3F
UANS FHVB4F
UANS FRA3
UANS FRA4
UANS FRB3
UANS FRB4
UANS FHVA3
UANS FHVA4
UANS FHVB3
UANS FHVB4
Application
Specification
Horizontal/Vertical type 6EA for A frame, 630-1,600A, 3P
Horizontal/Vertical type 8EA for A frame, 630-1,600A, 4P
Horizontal/Vertical type 6EA for B frame, 630-3,200A, 3P
Horizontal/Vertical type 8EA for B frame, 630-3,200A, 4P
Front type 6EA for A frame, 630-1,600A, 3P
Front type 8EA for A frame, 630-1,600A, 4P
Front type 6EA for B frame, 2,000-3,200A, 3P
Front type 8EA for B frame, 2,000-3,200A, 4P
Front type 3EA & Horizontal/Vertical type 3EA for A frame, 630-1,600A, 3P
Front type 4EA & Horizontal/Vertical type 4EA for A frame, 630-1,600A, 4P
Front type 3EA & Horizontal/Vertical type 3EA for B frame, 630-3,200A, 3P
Front type 4EA & Horizontal/Vertical type 4EA for B frame, 630-3,200A, 4P
Front type 6EA for A frame, 630-1,600A, 3P
Front type 8EA for A frame, 630-1,600A, 4P
Front type 6EA for B frame, 2,000-3,200A, 3P
Front type 8EA for B frame, 2,000-3,200A, 4P
Front type 3EA & Horizontal/Vertical type 3EA for A frame, 630-1,600A, 3P
Front type 4EA & Horizontal/Vertical type 4EA for A frame, 630-1,600A, 4P
Front type 3EA & Horizontal/Vertical type 3EA for B frame, 630-3,200A, 3P
Front type 4EA & Horizontal/Vertical type 4EA for B frame, 630-3,200A, 4P
UAN
UAS








































Mounting
position
Outside of
ACB body &
cradle
Outside of
ACB body &
cradle
Outside of
ACB body &
cradle
ACB
| Phase insulation barrier |
•Phase insulation barrier prevents the
arc which may arise and result in
short-circuit between phase in
advance.
O
rdering code
Ordering code
Item
Complete parts
of ACB/Cradle
Spare part
Phase insulation
barrier
-
UANS 3PBAR
-
UANS 4PBAR
Application
Specification
UAN
UAS
for 3P


for 4P


Mounting position
Terminal side of ACB body &
cradle
| ON/OFF button lock |
•Prevents manual operation of ACB's
closing/tripping button due to user's
wrong handling.
•It is not possible to handle on/off
operation under the "Button lock"
status.
•Padlock is in not included, key lock
size: 5-8
O
rdering code
Ordering code
Item
Complete parts
of ACB/Cradle
Spare part
ON/OFF button lock
AM
UANS AM
Application
Specification
ON/OFF button cover with padlock hole
UAN
UAS


Mounting position
Outside of ACB body & cradle
U-Series Air Circuit Breaker_ 49
U-Series
/ Air Circuit Breaker
Accessories
| OCR portable checker |
•UAN portable checker tests for the operation of UAN OCR
(Long time/Short time delay/Instantaneous/Ground fault).
•It is possible to set current level, phases, and frequency for
OCR’s test.
•All testing factors are adjustable through front monitor and
you can check operating time.
•Battery equipped inside (Available without external power
source).
•Ordering code: UANS OC (Spare part)
C
onnection diagram
Item
Specifications
External power
Battery
Alkaline 9V: 3EA
Trip time measurement
Test output
K
ey Pad
Input: AC/DC100-200V, 50/60Hz
Output: DC24V, 2.5A
0-999,999sec
03Ict - 17Ict
Output precision
±20% (1Ict - 17Ict)
Size (H x W x D)
193mm x 111mm x 45mm
E
xternals
OCRTEST
❸
POWER S/W
❹
110.60
❶
HIPDS-D
❹
❸
UP
DOWN
START
FUNC.
ENTER
193.40
❶
❷
❷
STOP
❻
❺
Number Button
1
50
UP
Function
Move menu and increasing setpoint
Number
Button
1
LCD
2
DOWN Move menu and decrease setpoint
2
Key pad
3
FUNC
Move to the previous menu and return to the setup screen
3
Signal output terminal
4
ENTER Save the settings and move the number of digits of setting current
4
Power switch
5
START Waveform occurrence
5
Terminal
6
STOP
Waveform stop
44.60
❺
DC24V
Function
Menu, setting current, trip time
Move menu and setting
OCR connection terminals
On/Off
Control terminal of checker
ACB
| Key lock device |
•The key lock prevents the circuit breaker closing, it
maintains interlock condition (Mechanical prevention).
•When the key has been unlocked you can operate spring
changing/manual on or off, when the key is removed from
circuit breaker it becomes interlock. The key doesn’t turn
to lock position until user push the off button, when the
key is locked.
•Ordering code: AB, UANS AB (Spare part)
| Key interlock |
•Configure the system with three breaker mounted key lock device. Only two breakers are possible to input with 2EA key, and
the other breaker can supply stable load with interlocking.
ACB 3 is interlocked
Power 1
ACB 1
ACB 2 is interlocked
Power 2
ACB 2
Power 1
ACB 1
Power 2
ACB 2
Power 1
ACB 1
Bus-tie
ACB 3
Bus-tie
ACB 3
Load 1
ACB 1 is interlocked
Load 2
Load 1
Power 2
ACB 2
Bus-tie
ACB 3
Load 2
Load 1
Load 2
U-Series Air Circuit Breaker_ 51
U-Series
/ Air Circuit Breaker
Accessories
| Wrong insertion preventer |
•When the main body of ACB is inserted to the
cradle if the ratings of ACB do not match with
cradle it mechanically prevents ACB from
being inserted into cradle of ACB.
•Each part will have been installed on body or
cradle.
•This device is set by CT rated current.
•Ordering code: AW (Attachment)
UANS AW (Accessory only)
•Add each ordering cade to both body and
cradle code.
M
ounting position according to rated current
Mounting position
CT
Cradle
ACB
ADEG
236
0 = Without OCR
Mounting position
CT
K = 1,250A
ACB
ABCF
457
I = 80A
AEFG
234
L = 1,600A
ABCE
467
B = 160A
ADFG
235
M = 2,000A
ABCD
567
O = 200A
ADEF
237
N = 2,500A
BCDE
167
V = 320A
ABEF
347
P = 3,200A
BCDF
157
E = 400A
ABDG
356
Q = 4,000A
BCDG
156
T = 630A
ABDF
357
S = 5,000A
BCEF
147
H = 800A
ABDE
367
X = 6,300A
ABEG
346
J =1,000A
ABCG
456
1
1
A
2
3
D
E
6
7
B
C
4
5
F
G
1
1
1 3
3 5
5 7
7
2
2 4
4 6
6
A
A C
C E
E G
G
3
B
B D
D F
F
1
3
5
7
2
4
6
A
C
E
G
5
B
D
F
7
1
3
2
5
4
7
6
D
E
6
7
B
C
4
5
M
ounting position according to rated current
A
2
3
52
Cradle
F
G
2
A
4
C
6
E
G
A
C
E
G
B
B
D
D
F
F
1
3
5
7
2
4
6
A
C
E
G
B
D
F
ACB
| OCR & Alarm switch reset |
•When a circuit breaker tripped by fault current or over load
and only if the circuit breaker has been tripped by OCR, the
MRB operates interlock and resets the interlock to restore
electric lines after fault factors have been removed. -(BR)
•When the CB is tripped by OCR it provides functions of
interlocking above mechanism -(BR) and output contacts
(2a) which check operation of CB by OCR as well. The
output contact displays OCR operation by long time, short
time delay, instantaneous and ground fault. And resetting
above mechanism occurs. -(BA)
•Except above functions when emergent restoration of
electric load is needed it automatically reset itself to get
ready to open immediately after trip and reset only output
contacts. (BM)
•It will have been installed when the product is out. Add BR/
BA/BM on your order.
O
rdering code
Ordering code
Item
Complete parts
of ACB/Cradle
Spare part
OCR &
Alarm switch reset
device
BR
UANS BR
BA
UANS BA
BM
UANS BM
Application
Specification
UAN
UAS
for OCR manual reset only


for OCR manual reset & alarm switch reset


for OCR auto reset & alarm switch reset


Mounting position
Inside of ACB body
U-Series Air Circuit Breaker_ 53
U-Series
/ Air Circuit Breaker
Accessories
| Safety shutter lock |
•An automatic safety device to protect the connectors of
main circuit by cutting off dangerous contact from outside
while the breaker is drawn out.
•Shutter lock is a locking device which prevents safety
shutter from being opened when it is closed. (Key lock is
not included. Size is 5-8)
O
rdering code
Ordering code
Item
Safety shutter lock
54
Complete parts
of ACB/Cradle
Spare part
AE
UANS AEA3
UANS AEA4
UANS AEB3
UANS AEB4
UANS AEC3
UANS AEC4
Application
Specification
for A frame, 630-2,000A, 3P
for A frame, 630-2,000A, 4P
for B frame, 630-4,000A, 3P
for B frame, 630-4,000A, 4P
for C frame, 3,200-5,000A, 3P
for C frame, 3,200-5,000A, 4P
UAN
UAS












Mounting position
Inside of cradle
ACB
| Arc shield |
•Arc which may arise while breaking fault current is
extinguished first by arc chute in main body of circuit
breaker and then completely extinguished by arc cover.
O
rdering code
Ordering code
Item
Complete parts
of ACB/Cradle
Arc shield
AX
Application
Specification
Spare part
UAN
UAS
UANS AXA3
for A frame, 630-2,000A, 3P


UANS AXA4
for A frame, 630-2,000A, 3P


UANS AXB3
for B frame, 630-4,000A, 3P


UANS AXB4
for B frame, 620-4,000A, 4P


UANS AXC3
for C frame, 3,200-5,000A, 3P


UANS AXC4
for C frame, 3,200-5,000A, 4P


Mounting position
Upper side of
cradle
| Control terminal protection cover |
•Protects control terminals which are exposed to the
outside, and prevent damage from foreign substances.
•Ordering code: BC (In case of auto-connection mode)
O
rdering code
Ordering code
Item
Complete parts
of ACB/Cradle
Spare part
Control terminal protection cover
BC
UANS BC
Application
Specification
for auto connection control terminal
UAN UAS


Mounting position
Control terminal of cradle
U-Series Air Circuit Breaker_ 55
U-Series
/ Air Circuit Breaker
Accessories
| Control terminal |
•Two types of connecting control power. Auto connection
type which the body connected or isolated from control
power automatically and manual connection type which
the connector is inserted to the body manually.
•Fixed type is provided with manual control plug type as
standard.
•Draw-out type's ordering code: "A" for auto connection,
"J" for manual control plug type.
Manual connection
terminal
Auto connection
terminal
O
rdering code
Ordering code
Item
Control terminal
Application
Specification
Complete parts of
ACB/Cradle
Spare part
A
UANS CJ
Auto connection terminal


J
UANS MJ
Manual connection terminal


UAN
UAS
Mounting position
Inside of ACB body
& cradle
| Short “b” contact |
•A contact which keeps the external control circuit in
normal by auxiliary contact which disconnects AUX "b"
when ACB is moved from connected position to test
position.
•The number of "Shorting "b" contact" corresponds to the
number of AUX "b" (5b).
•Ordering code: AK, UANS AK (Spare part)
ACB operating
ACB position
Connected position
(Short “b” off)
Test position
(Short “b” on)
56
ACB close
(AUX “b” off)
ACB open
(AUX “b” on)
Off
On
AUX "b"
Short "b"
AUX "b"
Off
AUX "b"
Short "b"
On
Short "b"
AUX "b"
Short "b"
ACB
| Fixing block |
•The fixing block can reinforce safety gear to prevent
malfunction from vibration.
•Able to strengthen bodies, cradles, and panel supporter
together.
•It will have been installed when the product is out.
•Add AF on main body of ACB and cradle’s order
respectively.
O
rdering code
Ordering code
Item
Complete parts of
ACB/Cradle
Spare part
Fixing block
AF
UANS AF
UANS AFB
UANS AFC
Application
Specification
for ACB body and cradle
for ACB body
for cradle
UAN
UAS






Mounting position
Outside of ACB body
& cradle
| Counter |
•Displays the total number of on/off operation of ACB
•The counter displays the total number of on/off operation
of ACB.
•Extra order is unnecessary (It is a primary component of
UAN/UAS).
•Ordering code: UANS AD (Spare part)
U-Series Air Circuit Breaker_ 57
U-Series
/ Air Circuit Breaker
Accessories
| Remote operation & Temparature detection module |
•Installed on the cradle or inside of panel, and
communicates with Modbus/RS-485 basically.
•Needs to be purchased separately and can be operated
with temperature alarm unit at the same time.
•Please refer to page 59 for temperature sensor.
•Temperature alarm unit is a device to show the busbar's
temperature through a sensor inside of ACB.
•Temperature sensor can be installed up to 3 and alarm
can occur when it reaches the specified temperature.
•Display the maximum temperature on the segment LED
and transmits through a network.
•Communicates with modbus/RS-485 basically, and needs
to be purchased separately.
•Installed on the cradle or inside of panel, and can be
operated with remote closing & trip unit at the same time.
C
ontact specification
Division
ACB control
Range of application
Contact ratings
10A 240VAC, 30VDC
Max switching power
2,400VA, 300W
O
rdering code
Ordering code
Item
Remote operation
& temperature
detection module
58
Complete parts
of ACB/Cradle
Spare part
Application
Specification
UAN
-
UANS RTU
Temperature detection module

-
UANS RTUN
Temperature detection module with temperature sensor

-
UANS RCU
Remote operation module

-
UANS RCTU
Remote operation & temperature detection module

-
Remote operation & temperature detection
UANS RCTUN
module with temperature sensor

UAS
Mounting position
•Module: outside of
ACB body or cradle
•Sensor: inside of
cradle
ACB
| Temperature sensor |
•The RCTU is used with temperature sensor installed
inside of the ACB.
•The temperature sensor is installed in designated
position. However user can change the position to
applicable extra site.
O
rdering code
Ordering code
Item
Complete parts
of ACB/Cradle
Spare part
Temperature sensor
-
UANS TSN
Application
Specification
Temperature sensor
UAN

UAS
Mounting position
Inside of cradle
U-Series Air Circuit Breaker_ 59
U-Series
/ Air Circuit Breaker
Accessories
| Draw-in/out device unit & Position lock device |
•Draw-in/out device unit is mounted on the body of draw
type ACB as standard.
•Draw-in/out device unit consists of draw-in/out handle
storage space, push button, position indicator, pad lock.
•Position pad lock is a safety device as locking draw-in/out
function in connected/test/sol position.
•This device is offered as standard except key lock.
Available key lock size: 5-8
•Ordering code: UANS DR (Spare part)
| Draw-in/out handle |
•Draw-in/out handle is attached on the side of cradle as
standard.
•Ordering code: UANS L handle or UANS U handle
 UANS L handle
 UANS U handle
O
rdering code
Ordering code
Item
Draw-in/out
handle
60
Complete parts of
ACB/Cradle
Spare part
-
UANS HANDLE
-
UANS LHANDLE
-
UANS UHANDLE
Application
Specification
UAN
UAS
Standard type


Long type


Universal joint type


Mounting position
-
ACB
| Neutral CT |
•The NCT is additionally applied for 3-pole circuit breaker
when it is connected to distribution line (3 phases 4 lines).
•For distribution line (3 phases 4 lines) 3pole circuit
breaker can protect the ground fault however, we can not
classify unbalanced load and ground fault. To complement
this when only a ground fault occurs the NCT senses the
N phase load and operates the GFT.
•When connecting a relay or electric instrument checking
phase is mandatory. Please connect the designated
terminal.
•It is a separate product. Refer to the table below (Rated
current level) and check the item on your order.
O
rdering code
Ordering code
Application
Specification
Complete parts of
ACB/Cradle
Spare part
-
UANS NCTAT
-
UANS NCTAH
Neutral CT
UAN
UAS
for A frame, 630A


for A frame, 800A


UANS NCTAJ
for A frame, 1,000A


UANS NCTAK
for A frame, 1,250A


UANS NCTAL
for A frame, 1,600A


-
UANS NCTBM
for B frame, 2,000A


-
UANS NCTBN
for B frame, 2,500A


-
UANS NCTBP
for B frame, 3,200A


-
UANS NCTBQ
for B frame, 4,000A


-
UANS NCTCQ
for C frame, 4,000A


-
UANS NCTCS
for C frame, 5,000A


630-2,000A
150
2,500-4,000A
30
80
100
30
SUS 2T
Ø
4
300
Ø
0
20
300
240
5
13
Ø1
4
300
175
97
Sec. M5
30
17.5
4-
Ø1
25
107
75
-
4,000-5,000A
4-
K
0
Ø8
Mounting position
W
300
240
Item
240
300
40
30
240
300
40
10
U-Series Air Circuit Breaker_ 61
U-Series
/ Air Circuit Breaker
Accessories
| Door flange |
•Protects the protruding front of ACB and the cutting
side of panel door by attaching it to the panel door.
•Both fixed/draw-out type are the same size of the
panel cutting, even if the dust cover is installed.
•Refer to dimension for panel cutting size.
•Protection rating of IP30.
 Panel door cutting dimensions
292
100
103.5
R5
4-
115
Door flange
122.5
7.5
12
-Ø
4
Panel door
345
122.5
103.5
7.5
25.6
Bottom
O
rdering code
Ordering code
Item
Complete parts
of ACB/Cradle
Spare part
Door flange
-
UANS AG
Application
Specification
UAN
UAS


for IP30
Mounting position
Panel door
| Dust cover |
103.5
292
100
•A protective cover which completely protects the
front
panel
R5 of ACB from dust and moisture, with a
103.5
4protection rating of IP54.
122.5
•Locks the cover in the test or connected position.
Bottom
292
100
103.5
345
122.5
103.5
R5
4-
Ordering code
62
Item
Complete parts
of ACB/Cradle
Spare part
Dust cover
-
UANS DC
Bottom
Specification
for IP52
7.5
345
Application
UAN
25.6
7.5
12
-Ø
4
O
rdering code
122.5
115
122.5
7.5
25.6
7.5
12
-Ø
4
115
•Refer to dimension for panel cutting size.

UAS
Mounting position
-
ACB
| Automatic transfer switch & Controller |
 Features
4
•Stable transfer system
Provides definite protection for electric power system by
using Hyudai ACB which has the highest breaking capacity.
•An unmanned woking system
An unmanned automatically transfering system is realized
by installing auto power control device to the ACB with
mechanic interlock device.
•Various mode
Offers four selection modes for user's convenience.
ACB1
3
•Multi protection device
Multi protection device installed in ACB has various
protecting functions such as self-monitoring, simple set
up. Unlike existing ATS, it has overload protection to offer
stable use.
•Compact size · Light weight
ACB is more compact and lighter. It is easily installed in
switchgear and occupies less space.
ACB2
3
•ATS configuration and interlock
- ACB1: "Normal" power (First order side, UN)
- ACB2: "Stand-by" power (Power generator side, UR)
- 3 : Mechanical interlock device unit
- 4 : ATS unit
Each ACB should meet the following specifications.
- Mechanism of geared motor
- SHT
- LRC
- Overload or short protection device
•Interlock conditions
ACB1
ACB2
Open
Open
Close
Open
Open
Close
ACB1
ACB2
O
rdering code
Ordering code
Item
Complete parts
of ACB/Cradle
Spare part
ATS controller
-
UANS ATS
Application
Specification
Automatic transfer switch & controller
UAN

UAS
Mounting position
-
U-Series Air Circuit Breaker_ 63
U-Series
/ Air Circuit Breaker
Accessories
| Automatic transfer switch & Controller |
 Description of mode
•Stop mode
This mode is for compulsory trip of ACB1 (Electric power
company) or ACB2 (Power station) when UN (Power supply of
electric power company) or UR (Power supply of power
station) is available.
Time delay
State display of controller
t1: 0.1-30sec
t2: 0.1-240sec
On, Off, Fault
220/240V
•Auto mode
This mode is for transferring a circuit breaker automatically
to available power supply of UN or UR.
N
R
t1
N
UR
On/I
On/I
Off/0
Off/0
t2
Fault
Stop
Reset
Fault
Auto
Manu
N
R
 Operation characteristic
UN or KT
UR
KR
QN
QR
0.1 - 30s
500
250
T1(ms)
•UN: Normal
•UR: Stand-by
•KT: Stand-by
64
0.1 - 240s
500
T2(ms)
•KR: Re-checking
•QN: Normal
•QR: Stand-by
2 4
8
1
0.5
15
0.1 30
UN=0
0.5s
•N mode
This mode is for compulsory closing of ACB1 when UN is
available.
•R mode
This mode is for compulsory closing of ACB2 during the use
of UR regardless of that UN is available or not.
50/60Hz
UN
•: On/Off
250
15 30
8
60
4
120
0.1 240
0.5s
UN=I
R
ACB
 System operation
Auto mode
Stop mode
N R
ACB1 / ACB2
Trip manually
Off
“Normal”
On
N mode
(Normal power ON compulsory)
4-position switch
(N, UN supplied)
I O
Auto mode
Reset
ACB2 Trip
UN loss above +1 or received
auto-switching command
ACB1 Trip
1sec
t>0.5s
ACB1 Input
t>0.5s
Reset end
“Standby” ON
ACB2 Input
ACB1 closed
NR
Operation stop
ACB2 Input
N R
I O
4-position switch
I O
UN exist during t > t2 or stop
auto-switching command
R mode
("Stand-by" ON compulsory)
ACB2 Trip
4-position switch
(N, UN supplied)
t>0.5s
ACB1 Input
ACB1 Input
ACB1 Trip
t>0.5s
ACB2 Input
ACB2 Input
N R
•ACB1: UAN(S) ACB1
“Normal”(UN)
•ACB2: UAN(S) ACB2
“Stand-by”(UR)
• UN : “Normal”
• UR : “Stand-by”
I O
4-position switch
U-Series Air Circuit Breaker_ 65
U-Series
/ Air Circuit Breaker
Accessories
| Automatic transfer switch & Controller |
 Description of mode [ UAN, UAS type ]
Circuit diagram of ATS auxilliary device
ACB1, “Normal” UN
5343
26
7
1
3
TC
M
CC
8
2
4
UR on
Auto
Mode Aux. Switch
1
2
7
3
54
26
53
43
5444
Spring
charge
“off”SW.
OCR Alarm SW.
UN on
1
2
3
4
5
Aux. SW.
Common
Stop
Control circuit terminal block
Aux. SW.
A1
1
2
3
4
5
6
7
8
1
2
7
3
54
26
53
43
A1
1
2
3
4
5
6
7
8
B1
Communication
Control circuit terminal block
UR on
Auto
Common
1
2
3
4
5
6
7
8
9
10
Control circuit terminal block
Stop
UN on
Control circuit terminal block
1
24
✽1 Standard model is equipped switch on the controller (Control terminal type is not standard model).
UR
1
3
7
19
20
26
24
45
46
47
48
55
56
57
58
T
R S T
R S T
UN
MCCB
UR
MCCB
Controller
IVE
N
R
1
3
7
19
20
26
24
45
46
47
48
55
56
57
58
UN ACB
UR ACB
66
ATS Terminal block
UN
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
ATS Terminal block
Wiring diagram of ATS with applied two ACBs
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
ACB
ACB2, “Stand-by” UR
26 24 OCR DO
43 44 Aux. switch a
26
7
1
Aux. SW.
A1
A1
B1
53 43
3
53 54 Aux. switch b
TC
Spring
Charge
“OFF”SW.
Voltage trip
7 8 Shunt trip power terminals
1 2 Spring charge power terminals
3 4 Close power terminals
54 44
M
CC
OCR Alarm SW.
Aux. SW.
TC
24
8
2
M
Charging motor
CC
Latch release (Close)
4
Wiring diagram of ATS panel remote
Stand-by
ACB
ATS controller UR
control voltage (AC220V)
1
3
7
19
20
26
24
45
46
47
48
55
56
57
58
1
3
7
19
20
26
24
45
46
47
48
55
56
57
58
PB(Close)
PB(Open)
ATS Terminal block
Normal
ACB
Do not supply power, ATS
controller is power ON.1)
OCR control
terminal
ACDC100-250
S0-S2
OCR+OCGR “1a”contact
Aux. SW.
PB(Close)
PB(Open)
ATS Terminal block
ATS controller UN
control voltage (AC220V)
N
R
2a-2b
Do not supply power, ATS
controller is power ON.1)
OCR control
ACDC100-250
terminal
OCR+OCGR “1a”contact
Aux. SW.
S0-S2
2a-2b
※ 1) Do not supply additional control power in case of operating remote, open/close power is supplied from ATS controller (Terminal No. “1”, “7”, “16”).
U-Series Air Circuit Breaker_ 67
U-Series
/ Air Circuit Breaker
Accessories
| Automatic transfer switch & Controller |
 Dimensions
(unit: mm)
UAN(S)06-16 A frame
[ UAN(S)06-16 A, Front ]
27.5
40
470
128 36 154
89
[ UAN(S)06-16 A, Horizontal type]
89
220
245
20.5
[ UAN(S)06-16 A, Vertical type ]
296
560
600
50
15
15
15
374.55
235
335
435
50
UAN20 A frame
128 36
154
[ UAN20 A, Vertical type ]
89
245
27.5
[ UAN20 A, Front ]
40
20.5
46.3
250
344.6
20.1
343
75 69.1 75
615
1440
395.9
1810
20.1
343
75 69.1 75
39.9 79
107
68
296
560
600
50
235
335
435
159.1
15
455.9
420.9
250
357.05
20.1
343
50 94.1 50
615
1440
107
159.1
343
50 94.1 50
39.9 79
20.1
1810
46.3
46.3
39.9 79
235
335
435
ACB
(unit: mm)
UAN(S)20-25 B frame
[ UAN(S)20-25 B, Front ]
40
20.5
128 36 154
[ UAN(S)20-25 B, Vertical type ]
[ UAN(S)20-25 B, Horizontal type ]
89
89
245
27.5
140
154.7
296
660
700
50
451.9
163.1
20 20
372.55
250
345.05
20.1
343
75 68.1 75
615
1440
396.9
20 20
75 68.1 75
343
20.1
1810
48.3
39.9 79
163.1
48.3
39.9 79
50
235
335
435
235
335
435
UAN32 B frame
40
20.5
[ UAN32 B, Front ]
128 36 154
[ UAN32 B, Vertical type ]
[ UAN32 B, Horizontal type ]
89
89
245
27.5
140
39.9 79
48.3
39.9 79
123.1
615
20
154.7
296
660
700
50
235
335
435
163.1
20
372.55
250
337.55
20.1
343
90 53.1 90
20
615
1440
381.9
1810
20.1
343
90 53.1 90
20
48.3
50
235
335
435
U-Series Air Circuit Breaker_ 69
U-Series
/ Air Circuit Breaker
Accessories
| Automatic transfer switch & Controller |
 Dimensions
(unit: mm)
UAN40 B frame
40
20.5
[ UAN40 B, Front ]
128 36 154
[ UAN40 B, Vertical type ]
[ UAN40 B, Horizontal type ]
89
89
245
27.5
140
64.3
15
407
15
125
15
297
295.05
362.55
15
125
40
15
15
68 125
615
343
20.1
250
70
15
68
343
20.1
1810
1440
154.7
296
660
700
50
235
335
435
40 128 40
15
79
125
39.9
128 40
90.3
39.9 79
50
235
335
435
ACB
(unit: mm)
UAN40-50 C frame, 3P
[ UAN40-50 C, 3P, Front ]
[ UAN40-50 C, 3P, Vertical type ]
[ UAN40-50 C, 3P, Horizontal type ]
240
89
128 36 154
89
245
27.5
40
20.5
415.2
UAN40-50 C frame, 4P
760
800
296
[ UAN40-50 C, 4P, Front ]
40
20.5
128 36 154
110 86.1 110
20
20
308.9
50
235
335
435
[ UAN40-50 C, 4P, Vertical type ]
89
235
335
435
[ UAN40-50 C, 4P, Horizontal type ]
89
245
27.5
440
50
110 86.1 110
20
20
20
20
301.1
250
294.5
20.1
343
125 69.1 125
615
1440
295.9
20
125 69.1 125
343
20.1
1810
66.3
39.9 79
66.3
20
39.9 79
20
20
20
20
308.9
295.9
20
20
20
20
301.1
250
294.5
20.1
343
125 69.1 125
615
1440
500.2
960
1000
296
50
235
335
435
110 86.1 110
66.3
125 69.1 125
343
20.1
1810
39.9 79
66.3
110 86.1 110
39.9 79
50
235
335
435
U-Series Air Circuit Breaker_ 71
U-Series
/ Air Circuit Breaker
Circuit Diagrams
Main circuit
Protection trip relay
Motor
Spring charge Closing
switch
coil
ZSI
NCT In Out
PB
(Close)
Spring
charge
off SW.
UPR-2L-GS
Protection trip relay
NCT In Out
ZSI
S
ymbol description
CT
Current transformer
1
2
Charging motor (M) source power
L
LTD (Long-time delay) terminal
3
4
Closing coil (CC) source power
PT
PTA (Pre-trip alarm) terminal
7
8
Open coil (TC) source power
G
10
UVT coil terminal
Ground fault terminal
9
S/I
STD (Short-time delay ) / INST (Instantaneous) terminal
15 16
Charge complete contact
Ac
Common terminal
19 20
OCR source power
Neutral current transformer
22 21
LTD (Long-time delay) contact
ZI
Zone selective input
22 23
PTA (Pre-trip alarm) / TEMP (Temperature) contact
ZO
Zone selective output
22 24
STD (Short-time delay) / INST (Instantaneous) contact
MCR input terminal
22 26
GFT (Ground-fault trip) / ELT (Earth-leakage trip) contact
MHT input source
29 30
NCT input terminal
M
Charging motor
31 ~ 34
ZSI (Zone selective input)
CC
Close coil (Close)
41 ~ 60
AUX contact
TC
Trip coil (Open)
61 ~ 93
Position switch
NCT
A/C
Tp / Tn
UVT
Under voltage trip coil
MHT
Magnetic hold trigger
S0 / S2
72
UPR protection relay source power
Manufacturer’s wiring
User’s wiring
Disconnecting device (Draw-out type)
ACB
Trip coil
Condensor
trip
Under voltage
trip
Auxiliary switch
Position switch
Used for TC supervision (Option)
Used for TC supervision (Option)
Used for short “b” contact (Option)
Used for MCR (Option)
Used for supervision (Option)
UVT controller
PB (Open)
PB (Open)
PB (Open)
C
ontrol terminal lay-out
OCR
Operating
Auxiliary switch
Protection trip relay
Operating
circuit
Auxiliary SW
OCR Contact
OCR
V input
- Protection trip relay Operating
- Operating circuit -
Auxiliary switch
- Auxiliary SW -
U-Series Air Circuit Breaker_ 73
U-Series
/ Air Circuit Breaker
Dimensions
| UAN06-20/UAS06-16 fixed type (A frame) |
(unit: mm)
Front
296
404.4
404.4
381
270
270
168.7
253.7
422.4
337.4
[ 3P ]
[ 4P ]
Vertical terminal connection
85
15
85
85
15
109
20
ø14
[ 2,000A ]
132
33
132
33
60
49
60
186.8
295.8
43.6
※ A frame 2,000A of UAN fixed type is applicable horizontal terminal only.
13
3-ø
50
75
330
144
25
50
144
15
50
330
35
13
2-ø
50
35
49
186.8
295.8
43.6
15
75
[ 630-1,600A ]
74
85
5
152.5
186.8
152.5
ø14
20
109
186.8
5
85
ACB
(unit: mm)
Horizontal terminal connection
85
85
85
85
85
85
5
186.8
ø14
20
109
152.5
5
152.5
186.8
ø14
20
109
85
50
50
13
35
25
15
33
15
132
330
129
144
50
15
2-ø
60
49
186.8
43. 6
295.8
Front terminal connection
85
85
186.8
152.5
186.8
152.5
50
5
50
5
85
ø14
109
20
109
20
ø14
13
2-ø
25
50
526
35
33
330
15
49
186.8
295.8
252.4
118
60
15
U-Series Air Circuit Breaker_ 75
U-Series
/ Air Circuit Breaker
Dimensions
| UAN06-20/UAS06-16 draw-out type (A frame) |
(unit: mm)
Front
438 (Manual control plug type)
278.3
460 (Auto connection type)
.1
.1
ø1 2
438 (Manual control plug type)
525
501
ø1 2
460 (Auto connection type)
440
416
270
270
164
164
164
249
413
328
[ 3P ]
[ 4P ]
Vertical terminal connection
85
15
85
368.4
ø1
4
4
59
210
210
250
328.8
75
132
ø13
33.1
50
15
15
33.1
ø13
352.8
39.6
381.6
421.2
※ A frame 2,000A of UAN fixed type is applicable horizontal terminal only.
76
50
250
328.8
352.8
39.6
381.6
421.2
15
50
465.8
75
144
Fixing block
(Option)
132
15
13
3-ø
15
75
35
6
50
465.8
50
144
119.3
50
330
Fixing block
(Option)
13
2-ø
Arc shield surface
(Option)
20.4
15
35
6
60
25
20.4
119.3
(Test) 26.5
(Isol) 11.5
Arc shield surface
(Option)
330
60
85
[ 2,000A ]
[ 630-1,600A ]
(Isol) 11.5
85
250
368.4
250
ø1
(Test) 26.5
85
15
28.8
28.8
85
ACB
(unit: mm)
Horizontal terminal connection
85
85
85
85
28.8
368.4
368.4
250
28.8
250
ø1
ø1
4
4
59
210
60
15
ø13
50
25
465.8
15
15
250
328.8
352.8
381.6
421.2
39.6
2-ø
15
129
15
330
Fixing block
(Option)
50
13
35
6
119.3
33.1
85
Arc shield surface
(Option)
20.4
144
(Isol) 11.5
210
132
(Test) 26.5
85
50
50
Front terminal connection
85
85
85
28.8
4
59
210
60
85
526
465.8
13
2-ø
25
50
35
6
Fixing block
(Option)
330
210
Arc shield surface
(Option)
20.4
119.3
85
ø1
4
(Test) 26.5
85
368.4
ø1
(Isol) 11.5
50
250
368.4
250
28.8
50
15
328.8
39.6
50
250
329.6
352.8
15
15
118
33.1
ø13
15
U-Series Air Circuit Breaker_ 77
U-Series
/ Air Circuit Breaker
Dimensions
| UAN06-32/UAS20-32 fixed type (B frame) |
(unit: mm)
Front
367
404.4
404.4
482
270
270
204.2
319.2
408.4
523.4
[ 3P ]
[ 4P ]
Vertical terminal connection
115
115
115
115
186.8
152.5
5
5
ø14
109
20
109
20
[ 3,200A ]
90
33
132
132
33
60
49
186.8
295.8
60
43. 6
49
186.8
295.8
13
3-ø
50
90
144
330
50
144
15
75
330
35
13
3-ø
75
75
35
43. 6
15
90
186.8
152.5
ø14
[ 630-2,500A ]
78
115
20
20
ACB
(unit: mm)
Horizontal terminal connection
115
115
115
115
A
Name
Detail “A”
UAN06-25
75
UAN32
90
186.8
152.5
186.8
152.5
5
5
A
115
ø14
109
109
20
20
ø14
[ 630~2,500A ]
[ 3,200A ]
13
20
144
330
132
90
50
3-ø
15
33
132
50
15
33
20
75
3-ø
144
330
35
13
35
60
49
60
186.8
43.6
295.8
49
186.8
43. 6
295.8
Front terminal connection
115
115
115
115
115
75
ø14
13
3-ø
15
33
330
644
50
75
35
152.5
5
109
109
20
ø14
20
186.8
186.8
152.5
5
75
49
186.8
295.8
257.4
118
60
20
U-Series Air Circuit Breaker_ 79
U-Series
/ Air Circuit Breaker
Dimensions
| UAN06-32/UAS20-32 draw-out type (B frame) |
(unit: mm)
602
278.3
460 (Auto connection type)
278.3
.1
.1
ø1 2
438 (Manual control plug type)
626
438 (Manual control plug type)
511
487
ø1 2
460 (Auto connection type)
Front
270
270
199.5
199.5
199.5
314.5
399
514
[ 3P ]
[ 4P ]
Vertical terminal connection
115
115
20
368.4
368.4
250
28.8
250
4
4
210
94.5
210
75
Fixing block
(Option)
80
39.6
50
250
328.8
352.8
383.6
423.2
132.5
15
15
ø13
33.1
250
328.8
352.8
383.6
423.2
132.5
75
39.6
50
15
15
33.1
ø13
13
3-ø
15
90
35
6
90
119.3
143
15
Arc shield surface
(Option)
20.4
90
143
465.8
75
13
3-ø
50
35
6
Fixing block
(Option)
330
(Isol) 11.5
60
50
Arc shield surface
(Option)
20.4
119.3
[ 3,200A ]
(Test) 26.5
330
60
115
465.8
[ 630-2,500A ]
(Isol) 11.5
115
ø1
ø1
(Test) 26.5
115
20
28.8
115
ACB
(unit: mm)
Horizontal terminal connection
115
115
115
115
A
ø1
94.5
210
[ 630-2,500A ]
33.1
15
250
328.8
352.8
383.6
423.2
ø13
50
250
328.8
352.8
383.6
423.2
39.6
15
50
90
20
Fixing block
(Option)
124
143
15
13
3-ø
15
20
132.5
465.8
124
143
15
35
6
50
75
20
ø13
119.3
20
132.5
330
Fixing block
(Option)
13
3-ø
Arc shield surface
(Option)
20.4
465.8
(Isol) 11.5
35
6
60
15
20.4
33.1
90
[ 3,200A ]
(Test) 26.5
Arc shield surface
(Option)
39.6
75
UAN32
115
330
60
50
UAN06-25
4
210
119.3
Detail “A”
ø1
4
(Isol) 11.5
Name
368. 4
250
368. 4
250
28.8
28.8
A
(Test) 26.5
115
Front terminal connection
115
115
28.8
ø1
4
94.5
210
35
6
328.8
33.1
ø13
50
250
329.6
352.8
13
3-ø
15
15
15
117.5
330
Fixing block
(Option)
39.6
115
50
75
119.3
210
Arc shield surface
(Option)
20.4
465.8
60
525.5
(Test) 26.5
115
ø1
4
(Isol) 11.5
115
75
250
368.4
250
28.8
75
368.4
115
20
U-Series Air Circuit Breaker_ 81
U-Series
/ Air Circuit Breaker
Dimensions
| UAN40 fixed type (B frame) |
(unit: mm)
Front
404.4
482
404.4
367
270
270
204.2
408.4
319.2
523.4
[ 3P ]
[ 4P ]
Vertical terminal connection
152.5
10
152.5
140
15
15
109
186.8
295.8
87
152.5
13
15
125
5-ø
25*4=100
125
44
49
119.5
57
125
169
330
33
60
20
186.8
5
186.8
152.5
109
20
ø14
35
82
10 15
5
15
ø14
140
140
ACB
(unit: mm)
Horizontal terminal connection
405
520
152.5
152.5
140
100
140
144
40
3
15
132
33
15
10
15
ø1
325*3=75
35
330
ø14
100
109
152.5
ø14
20
186.8
5
5
100
109
20
186.8
152.5
140
60
49
186.8
295.8
58.6
U-Series Air Circuit Breaker_ 83
U-Series
/ Air Circuit Breaker
Dimensions
| UAN40 draw-out type (B frame) |
(unit: mm)
278.3
278.3
.1
.1
ø1 2
460 (Auto connection type)
602
438 (Manual control plug type)
626
438 (Manual control plug type)
511
487
ø1 2
460 (Auto connection type)
Front
270
270
199.5
199.5
199.5
314.5
399
514
[ 3P ]
[ 4P ]
Vertical terminal connection
152.5
152.5
140
368.4
250
368.4
ø1
4
4
94.5
210
60
Arc shield surface
(Option)
20.4
35
25*4=100
6
84
50
250
328.8
352.8
425.6
465.2
107.5
15
15
33.1
ø13
465.8
68
125
330
Fixing block
(Option)
193
125
119.3
13
5-ø
15
125
(Isol) 11.5
39.6
140
28.8
28.8
250
ø1
(Test) 26.5
140
15 10 15
15 10 15
210
115
ACB
(unit: mm)
Horizontal terminal connection
405
152. 5
100
140
368.4
368.4
250
28.8
28.8
100
250
ø1
ø1
4
4
94.5
210
60
(Isol) 11.5
15
39.6
50
250
328.8
352.8
399.6
439.2
15
15
33.1
ø13
132.5
40
168
Fixing block
(Option)
465.8
15
10
6
3
ø1
3-
25*3=75
15
35
330
115
Arc shield surface
(Option)
20.4
119.3
210
100
(Test) 26.5
520
140
140
152. 5
U-Series Air Circuit Breaker_ 85
U-Series
/ Air Circuit Breaker
Dimensions
| UAN32-50 fixed type (C frame) |
(unit: mm)
Front
762
404.4
404.4
592
270
464.7
270
168.7
549.7
633.4
253.7
803.4
[ 3P ]
[ 4P ]
Vertical terminal connection
190.5
20 70 20
190.5
190.5
20 70 20
86
5
63.6
152.5
186.8
44.5
186.8
295.8
15
20
109
125
69
194
107
125
330
33
60 49
13
5-ø
125
152.5
20
35
25*4=100
186.8
109
5
148
190.5
190.5
148
ACB
(unit: mm)
Horizontal terminal connection
190.5
190.5
190.5
125
190.5
190.5
186.8
109
25*4=100
51
20
33
110
125
110
86
15
70
196
330
13
5-ø
106
20
35
152.5
5
148
20
152.5
20
109
186.8
5
148
60
49
186.8
295.8
63.6
U-Series Air Circuit Breaker_ 87
U-Series
/ Air Circuit Breaker
Dimensions
| UAN32-50 draw-out type (C frame) |
(unit: mm)
278.3
278.3
.1
.1
ø12
460 (Auto connection type)
882
438 (Manual control plug type)
906
712
438 (Manual control plug type)
736
ø12
460 (Auto connection type)
Front
270
460
270
164
545
624
249
794
Vertical terminal connection
190.5
190.5
190.5
148
190.5
20 70 20
190.5
148
24
20 70 20
164
545
260
345
Arc shield surface
(Option)
35
50
175
328.8
352.8
401.6
441.2
88
194
44.5
15
15
33.1
ø13
107
125
330
Fixing block
(Option)
465.8
125
6
69
119.3
13
5-ø
15
125
20.4
25*4=100
60
(Isol) 11.5
39.6
4
ø1
50
50
460
260
(Test) 26.5
368.4
4
ø1
175
368.4
175
103.8
103.8
6
12
249
345
ACB
(unit: mm)
Horizontal terminal connection
190.5
190.5
190.5
125
190.5
148
190.5
368.4
175
4
ø1
50
50
ø1
4
175
368.4
103.8
103.8
148
460
260
35
25*4=100
465.8
15
33.1
50
39.6
175
328.8
106
15
15
ø13
51
110
20
196
330
Fixing block
(Option)
86
70
110
6
13
5-ø
125
20.4
119.3
249
345
Arc shield surface
(Option)
60
20
(Test) 26.5
(Isol) 11.5
545
345
164
260
352.8
401.6
441.2
U-Series Air Circuit Breaker_ 89
B
345
C
Rear panel
(IP30)
7.5
33.1
25.6
32
31
12
Dimensions
7.5
122.5
115
/ Air Circuit Breaker
-Ø
4
U-Series
330
122.5
A
4
Panel door
(323)
(25)
| UAN/UAS fixed type, panel cutting size - fixed type |
Front
Side
Rear (IP30)
Operaing
panel center
ACB center
292
100
103.5
R5
A
4-
B
144
75
330
345
(95)
C
7.5
25.6
33
132
7.5
122.5
12
-Ø
4
115
122.5
103.5
(188)
Rear panel
(IP30)
Panel door
R
eal panel cutting size
Model
90
A
B
C
UAN06-20 / UAS06-16 / A frame, 3P
283
355
25
UAN06-20 / UAS06-16 / A frame, 4P
368
355
25
UAN06-40 / UAS20-32 / B frame, 3P
354
355
25
UAN06-40 / UAS20-32 / B frame, 4P
469
355
25
UAN32-50 / C frame, 3P
579
355
25
UAN32-50 / C frame, 4P
749
355
25
ACB
| Panel cutting size - draw-out type |
Front
Side
Operaing
panel center
103.5
60
20.4
R5
ACB center
4-
A
B
345
115
7.5
122.5
Rear panel
(IP30)
7.5
33.1
25.6
32
31
C
-Ø
4
12
330
122.5
103.5
292
100
(Test)26.5
(Isol)11.5
Rear (IP30)
4
Panel door
(323)
(25)
Operaing
panel center
100
103.5
ACB center
R5
A
4-
B
C
UAN06-20 / UAS06-16 / A frame, 3P
329
268
70
UAN06-20 / UAS06-16 / A frame, 4P
414
268
70
400
298
55
UAN06-40 / UAS20-32 / B frame, 4P
515
298
55
UAN32-50 / C frame, 3P
625
338
35
338
35
330
7.5
UAN32-50 / C frame,
4P
75
33
(95)
(188)
Panel door
132
345
115
7.5
122.5
25.6
12
-Ø
4
UAN06-40 / UAS20-32 / B frame, 3P
144
A
122.5
Model
795 Rear panel
B
103.5
C
292
R
size
eal panel cutting
(IP30)
U-Series Air Circuit Breaker_ 91
U-Series
/ Air Circuit Breaker
Ordering Codes
| UAN type |
 ACB body part
UAN
12
A
3
J
M2
Type
Rated current
Frame size &
pole arrangement
Pole
Terminal connection
Motor
UAN
06
630A
08
800A
10
1,000A
12
1,250A
16
1,600A
201)
2,000A
25
2,500A
32
3,200A
40
4,000A
50
5,000A
A
2,000AF, 630-2,000A
3P: RST, 4P: RSTN
W
2,000AF, 630-2,000A
4P: NRST
3
3 Pole
4
4 Pole
Draw-out type/
Control terminal connection
M0
Manual type
M1
AC/DC 110V
A
Auto connection
M2
AC/DC 220V
J
Manual connection
M3
AC380V
M4
AC440V
M5
DC24V
B
4,000AF, 630-4,000A
3P: RST, 4P: RSTN
X
4,000AF, 630-4,000A
4P: NRST
H
Horizontal type
M6
DC48V
V
Vertical type
M7
DC125V
C
5,000AF, 3,200-5,000A
3P: RST, 4P: RSTN
T
Line side: Horizontal
Load side: Vertical
L
Y
5,000AF, 3,200-5,000A
4P: NRST
Line side: Vertical
Load side: Horizontal
P2)
Front type or others
Fixed type/
Terminal busbar arrangement
 Cradle part for draw-out type ACB
DUN
12
A
3
A
H
AE
Type
Rated current
Frame size &
pole arrangement
Pole
Control terminal
connection
Terminal busbar
arrangement
Accessories
A
Auto
connection
H Horizontal type
AE Safe shutter lock
V Vertical type
AF Fixing block
J
Manual
connection
DUN
16
630-1,600A,
A frame
A 2,000AF, 630-2,000A
3P: RST, 4P: RSTN/NRST
20
2,000A,
A frame
B 4,000AF, 630-4,000A
3P: RST, 4P: RSTN/NRST
25
630-2,500A,
B frame
C 5,000AF, 3,200-5,000A
3P: RST, 4P: RSTN/NRST
32
3,200A,
B frame
3
3 pole
4
4 pole
T
Line side: Horizontal
Load side: Vertical
AK
Short "b" contact for auto
connection terminal
L
Line side: Vertical
Load side: Horizontal
AW
Wrong insertion
preventer
P
Front type or
others
AX Arc shield
BC
92
40
4,000A,
B frame
50
3,200-5,000A,
C frame
Auto connection
control terminal cover
SP Cradle only
ACB
C2
S2
45
K
AB
Closing coil
Trip coil
Protection trip relay
(OCR)
CT3)
Accessories
00
N/A
0
N/A
Instantaneous type (UVT coil)4)
General feeder, 50Hz
I
80A
U1
AC/DC 110V
S1
AC/DC 110V
UPR-1L-GL
B
160A
U2
AC/DC 220V
S2
AC/DC 220V
35
UPR-2L-GS
O
200A
U3
AC380V
S3
AC380V
36
UPR-1D-GT
V
320A
U4
AC440V
S4
AC440V
37
UPR-2L-GM
E
400A
U7
DC24V
S7
DC24V
T
630A
U8
DC48V
S8
DC48V
U9
DC125V
S9
DC125V
C0
N/A
S0
N/A
C1
AC/DC 110V
S1
AC/DC 110V
C2
AC/DC 220V
S2
AC/DC 220V
33
C3
AC380V
S3
AC380V
C4
AC440V
S4
AC440V
C7
DC24V
S7
DC24V
C8
DC48V
S8
DC48V
C9
DC125V
S9
DC125V
General feeder, 60Hz
Double trip coil4)
43
UPR-1L-GL
H
800A
45
UPR-2L-GS
J
1,000A
46
UPR-1D-GT
K
1,250A
47
UPR-2L-GM
L
1,600A
V1
AC/DC 110V
T1
AC/DC 110V
M
2,000A
V2
AC/DC 220V
T2
AC/DC 220V
Generator, 50Hz
N
2,500A
V3
AC380V
T3
AC380V
38
UPR-1S-AL
P
3,200A
V4
AC440V
T4
AC440V
39
UPR-2S-AS
Q
4,000A
V7
DC24V
T7
DC24V
Time delay type4)
(UVT coil with UVT controller)
Trip supervision coil5)
Generator, 60Hz
S
5,000A
V8
DC48V
T8
DC48V
48
UPR-1S-AL
X
6,300A
V9
DC125V
T9
DC125V
49
UPR-2S-AS
AF
Fixing block
AW Wrong insertion preventer
AQ Test 1C, Connected 1C
AM ON/OFF button cover
AR Connected 2C
AA
Additional 1a1b auxiliary
switch
AS Test 2C
AB
Key lock device
AT Isolated 1C, Inserted 1C
B8
OCR MCR function
AU Inserted 2C
BR
OCR manual reset device
AV Isolated 2C
BA
P4 Test 2C, Connected 2C
B07)
OCR manual reset &
alarm switch reset device
OCR auto reset &
alarm switch reset device
Internal part for
mechanical interlock
1C, Isolated 1C,
PQ Inserted
Test 1C, Connected 1C
B6
Spring charge switch
2C, Isolated 2C,
P8 Inserted
Test 2C, Connected 2C
B7
ATS controller
1C, Isolated 1C,
PR Inserted
Test 3C, Connected 3C
SP
ACB body only
6)
※ 1) Vertical type is the only applicable terminal busbar for A frame, 2,000A.
2) Code P is for user installation, and applicable for A frame, 630-1,600A & B frame
630-3,200A. Please refer to page 48.
3) CT Application
Frame A/W: 80-2,000A
Frame B/X: 400-4,000A
Frame C/Y: 3,200-5,000A
4) UVT coil and double trip coil cannot be installed at the same time.
5) Standard auxiliary switch of UAN type is 5a5b. Trip supervision coil use 1a1b of
standard auxiliary switch, and OCR MCR function use;1a.
6) Additional 1a1b auxiliary switch and mechanical interlock cannot be installed at
the same time.
7) Mechanical interlock kit can be ordered separately, please refer to page 47.
8) Only one type position switch is selectable.
Position switch8)
5)
BM
1C, Test 1C,
PS Isolated
Connected 2C
U-Series Air Circuit Breaker_ 93
U-Series
/ Air Circuit Breaker
Ordering Codes
| UAS type |
 ACB body part
UAS
12
A
3
J
M2
Type
Rated current
Frame size &
pole arrangement
Pole
Terminal connection
Motor
UAS
06
630A
08
800A
10
1,000A
12
1,250A
16
1,600A
201)
2,000A
25
2,500A
32
3,200A
A
2,000AF, 630-2,000A
3P: RST, 4P: RSTN
W
2,000AF, 630-2,000A
4P: NRST
B
4,000AF, 630-4,000A
3P: RST, 4P: RSTN
X
4,000AF, 630-4,000A
4P: NRST
3
3 Pole
4
4 Pole
Draw-out type/
Control terminal connection
M0
Manual type
M1
AC/DC 110V
A
Auto connection
M2
AC/DC 220V
J
Manual connection
M3
AC380V
M4
AC440V
M5
DC24V
Fixed type/
Terminal busbar arrangement
H
Horizontal type
M6
DC48V
V
Vertical type
M7
DC125V
T
Line side: Horizontal
Load side: Vertical
L
Line side: Vertical
Load side: Horizontal
P2)
Front type or others
 Cradle part for draw-out type ACB
DUN
12
A
3
A
H
AE
Type
Rated current
Frame size &
pole arrangement
Pole
Control terminal
connection
Terminal busbar
arrangement
Accessories
A
Auto
connection
H Horizontal type
AE Safe shutter lock
V Vertical type
AF Fixing block
J
Manual
connection
DUN
16
630-1,600A,
A frame
A 2,000AF, 630-2,000A
3P: RST, 4P: RSTN/NRST
20
2,000A,
A frame
B 4,000AF, 630-4,000A
3P: RST, 4P: RSTN/NRST
25
32
3
3 pole
4
4 pole
T
Line side: Horizontal
Load side: Vertical
AK
Short "b" contact for auto
connection terminal
630-2,500A,
B frame
L
Line side: Vertical
Load side: Horizontal
AW
Wrong insertion
preventer
3,200A,
B frame
P
Front type or
others
AX Arc shield
BC
40
94
4,000A,
B frame
Auto connection
control terminal cover
SP Cradle only
ACB
C2
S2
43
K
AB
Closing coil
Trip coil
Protection trip relay
(OCR)
CT3)
Accessories
00
N/A
0
N/A
Instantaneous type (UVT coil)4)
General feeder, 50Hz
I
80A
U1
AC/DC 110V
S1
AC/DC 110V
UPR-1L-GL
B
160A
U2
AC/DC 220V
S2
AC/DC 220V
35
UPR-2L-GS
O
200A
U3
AC380V
S3
AC380V
37
UPR-2L-GM
V
320A
U4
AC440V
S4
AC440V
E
400A
U7
DC24V
S7
DC24V
T
630A
U8
DC48V
S8
DC48V
UPR-2L-GS
H
800A
U9
DC125V
S9
DC125V
UPR-2L-GM
J
1,000A
K
1,250A
Generator, 50Hz
L
1,600A
V1
AC/DC 110V
AQ Test 1C, Connected 1C
38
UPR-1S-AL
M
2,000A
V2
AC/DC 220V
AR Connected 2C
39
UPR-2S-AS
N
2,500A
V3
AC380V
AS Test 2C
Generator, 60Hz
P
3,200A
V4
AC440V
AT Isolated 1C, Inserted 1C
48
UPR-1S-AL
Q
4,000A
V7
DC24V
AU Inserted 2C
49
UPR-2S-AS
S
5,000A
V8
DC48V
AV Isolated 2C
X
6,300A
V9
DC125V
P4 Test 2C, Connected 2C
C0
N/A
S0
N/A
C1
AC/DC 110V
S1
AC/DC 110V
C2
AC/DC 220V
S2
AC/DC 220V
33
C3
AC380V
S3
AC380V
C4
AC440V
S4
AC440V
C7
DC24V
S7
DC24V
C8
DC48V
S8
DC48V
43
UPR-1L-GL
C9
DC125V
S9
DC125V
45
47
General feeder, 60Hz
Time delay type4)
(UVT coil with UVT controller)
Double trip coil4)
Position switch8)
1C, Test 1C,
PS Isolated
Connected 2C
AF
Fixing block
1C, Isolated 1C,
PQ Inserted
Test 1C, Connected 1C
AW Wrong insertion preventer
2C, Isolated 2C,
P8 Inserted
Test 2C, Connected 2C
AM ON/OFF button cover
1C, Isolated 1C,
PR Inserted
Test 3C, Connected 3C
1a1b auxiliary
AA6) Additional
switch
※ 1) Vertical type is the only applicable terminal busbar for A frame, 2,000A.
2) Code P is for user installation, and applicable for A frame, 630-1,600A & B frame
630-3,200A. Please refer to page 48.
3) CT Application
Frame A/W: 80-2,000A
Frame B/X: 400-4,000A
Frame C/Y: 3,200-5,000A
4) UVT coil and double trip coil cannot be installed at the same time.
5) Standard auxiliary switch of UAN type is 5a5b. Trip supervision coil use 1a1b of
standard auxiliary switch, and OCR MCR function use;1a.
6) Additional 1a1b auxiliary switch and mechanical interlock cannot be installed at
the same time.
7) Mechanical interlock kit can be ordered separately, please refer to page 47.
8) Only one type position switch is selectable.
AB
Key lock device
B8
OCR MCR function
BR
OCR manual reset device
BA
B07)
OCR manual reset &
alarm switch reset device
OCR auto reset &
alarm switch reset device
Internal part for
mechanical interlock
B6
Spring charge switch
SP
ACB body only
5)
BM
U-Series Air Circuit Breaker_ 95
U-Series
/ Air Circuit Breaker
Technical Data
| Internal resistance and power consumption |
AF
Rated current(A)
UAN/UAS06-16 A frame
UAN20 A frame
UAN/UAS20-32 B frame
B frame UAN 40B
C frame UAN 40-50C
D frame UAN 40-63D
Fixed type
Draw-out type
Internal resistance(㏁) Power consumption (W/3Phase) Internal resistance(㏁) Power consumption (W/3Phase)
630
20
24
40
48
800
20
38
40
77
1,000
20
60
40
120
1,250
20
94
40
188
1,600
20
154
40
307
630
15
18
30
36
800
15
29
30
58
1,000
15
45
30
90
1,250
15
70
30
141
1,600
15
115
30
230
2,000
13
156
27
324
2,000
10
120
20
240
2,500
10
188
20
375
3,200
10
307
20
614
2,000
10
120
20
240
2,500
10
188
20
375
3,200
10
307
20
614
4,000
8
384
11
528
4,000
8
384
11
528
5,000
8
600
11
825
4,000
6
288
9
432
5,000
6
450
9
675
6,300
5
595
7
833
※ 1) Power consumption listed is maximum power consumption for each rated current, 50/60Hz, 3/4 pole.
2) This is inner resistance value per pole.
3) Power factor = 1.0
A
| Insulation distance |
 I nsulation distance from arc
ACB
A
B
Fixed type
120mm
50mm
Draw-out Without Arc shield
type
With Arc shield
120mm
50mm
0mm
50mm
M
inimum insulation distance at charging side
96
Insulating voltage
D
[V] ≤ 600V
8mm
600V < [V] ≤ 1,000V
14mm
B
B
B
B
D
ACB
| Rectification of rated current |
Frame
Rated Terminal busbar
current of ACB body
200A
400A
5t×50mm×1EA
630A
800A
A frame
15t×50mm×1EA
UAN/UAS06-16 1,000A
1,250A
1,600A
A frame
UAN20
2,000A 15t×75mm×1EA
630A
800A
1,000A
B frame
1,250A 20t×75mm×1EA
UAN/UAS06-16
1,600A
2,000A
2,500A
B frame
UAN32
B frame
UAN40
C frame
UAN32-50
C frame
UAN40-63
3,200A 20t×90mm×1EA
4,000A
Horizontal
4,000A
Vertical
3,200A
4,000A
5,000A
4,000A
5,000A
6,300A
Applicable
busbar size
15t×100mm×2EA
15t×125mm×2EA
20t×125mm×2EA
20t×125mm×2EA
5t×50mm×2EA
10t×60mm×1EA
6t×50mm×2EA
10t×60mm×1EA
8t×50mm×2EA
6t×75mm×2EA
8t×60mm×2EA
10t×50mm×2EA
6t×75mm×3EA
10t×60mm×2EA
8t×60mm×3EA
8t×75mm×3EA
10t×100mm×2EA
5t×50mm×2EA
10t×60mm×1EA
6t×50mm×2EA
10t×60mm×1EA
8t×50mm×2EA
6t×75mm×2EA
8t×60mm×2EA
10t×50mm×2EA
6t×75mm×3EA
10t×60mm×2EA
8t×60mm×3EA
8t×75mm×3EA
10t×100mm×2EA
10t×75mm×3EA
8t×75mm×4EA
10t×100mm×3EA
10t×75mm×4EA
10t×100mm×4EA
10t×125mm×3EA
10t×100mm×4EA
10t×125mm×3EA
10t×100mm×3EA
10t×100mm×4EA
10t×125mm×4EA
10t×100mm×4EA
10t×125mm×4EA
10t×150mm×4EA
40°C
200A
400A
Horizontal type
45°C
50°C
55°C
200A
200A
200A
400A
400A
400A
60°C
200A
400A
40°C
200A
400A
45°C
200A
400A
Vertical type
50°C
55°C
200A
200A
400A
400A
630A
630A
630A
630A
630A
630A
630A
630A
630A
630A
800A
800A
800A
800A
800A
800A
800A
800A
800A
800A
60°C
200A
400A
1,000A 1,000A 1,000A 1,000A 1,000A
1,000A 1,000A 1,000A 1,000A 1,000A
1250A
1250A
1250A
1250A
1250A
-
-
-
-
-
1,250A 1,250A 1,250A 1,250A 1,250A
1,600A 1,600A 1520A 1,480A 1,420A 1,600A 1,600A 1,580A 1,550A 1,550A
-
-
-
-
-
2,000A 2,000A 1,940A 1,860A 1,860A
630A
630A
630A
630A
630A
630A
630A
630A
630A
630A
800A
800A
800A
800A
800A
800A
800A
800A
800A
800A
1,000A 1,000A 1,000A 1,000A 1,000A
1,000A 1,000A 1,000A 1,000A 1,000A
1,250A 1,250A 1,250A 1,250A 1,250A
-
-
-
-
1,250A 1,250A 1,250A 1,250A 1,250A
-
1,600A 1,600A 1,600A 1,600A 1,600A 1,600A 1,600A 1,600A 1,600A 1,600A
2,000A 2,000A 2,000A 2,000A 2,000A
2,000A 2,000A 2,000A 2,000A 2,000A
2,500A 2,500A 2,500A 2,400A 2,300A 2,500A 2,500A 2,500A 2,500A 2,500A
3,200A 3,200A 3,120A 3,050A 3,050A
3,200A 3,200A 3,100A 3,000A 2,900A
4,000A 4,000A 3,900A 3,800A 3,640A
-
-
-
-
-
3,200A
4,000A
5,000A
4,000A
5,000A
6,300A
3,200A
4,000A
5,000A
4,000A
5,000A
6,300A
3,100A
3,920A
4,900A
4,000A
4,900A
6,170A
3,000A
3,860A
4,800A
4,000A
4,820A
6,040A
2,900A
3,800A
4,700A
4,000A
4,750A
5,900A
A
ltitude
Item
U-Series ACB is designed for operation at altitudes
under 2,000m. At altitudes higher than 2,000m,
change the ratings upon service condition.
Withstand voltage[V]
Average insulating voltage[V]
Max. operation voltage [V]
Rectificated rated current [A]
Altitude
-
-
-
-
-
4,000A 4,000A 3,950A 3,800A 3,800A
3,200A
4,000A
5,000A
4,000A
5,000A
6,300A
3,200A
4,000A
5,000A
4,000A
5,000A
6,300A
3,100A
3,960A
4,950A
4,000A
4,950A
6,220A
3,000A
3,900A
4,900A
4,000A
4,870A
6,160A
3,000A
3,900A
4,900A
4,000A
4,870A
6,160A
2,000m
3,000m
4,000m
5,000m
3,500
1,000
690
1×In
3,150
900
590
0.99×In
2,500
700
520
0.96×In
2,100
600
460
0.94×In
U-Series Air Circuit Breaker_ 97
U-Series
/ Air Circuit Breaker
Technical Data
| Derating table |
 A frame
Ambient temperature outside of the switchboard: Ta (IEC 60439-1)
4
3
2
1
Switchboard composition
connection type
Applicable ACB
Busbar dimensions (mm)
UAN/UAS06-08
2EA x 50 x 6
UAN/UAS10
2EA x 50 x 8
800↓
4
Ventilated switchboard (IP31)
Ta=35°C
800↓
800↓
800↓
800↓
800↓
800↓
800↓
800↓
3
2
1
800↓
800↓
H
Ta=45°C
D
W
D
W
800↓
800↓
800↓
800↓
800↓
800↓
800↓
800↓
3
2
1
800↓
800↓
Area of inlet vents: 350cm
Area of outlet vents: 350cm2
Ta=55°C
800↓
800↓
800↓
800↓
800↓
800↓
800↓
800↓
3
2
1
800↓
800↓
Ta=35°C
Ta=45°C
H
H
D
W
D
W
Ta=55°C
※ H: 2,300mm, W: 800mm, D: 900mm
98
800↓
800↓
800↓
800↓
800↓
800↓
800↓
800↓
800↓
800↓
800↓
800↓
800↓
800↓
800↓
800↓
800↓
800↓
800↓
800↓
800↓
800↓
800↓
800↓
3
2
1
800↓
4
800↓
800↓
3
2
1
800↓
4
800↓
800↓
3
2
1
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
800↓
4
Non ventilated switchboard
(IP41/54)
1,000
1,000
800↓
4
2
1,000
1,000
800↓
4
H
1,000
800↓
800↓
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1000
ACB
Ambient temperature outside of the switchboard: Ta (IEC 60439-1)
4
3
2
1
Switchboard composition
connection type
Applicable ACB
Busbar dimensions (mm)
UAN/UAS12
2EA x 75 x 6
UAN/UAS16
2EA x 60 x 10
4
Ventilated switchboard (IP31)
Ta=35°C
1,250
3
2
1
1,250
1,250
1,250
1,250
1,250
1,250
1,000
1,600
1,600
1,600
1,000
1,000
1,600
1,000
1,000
4
H
H
Ta=45°C
2
1
D
W
D
W
1,250
3
1,250
1,250
1,250
1,250
1,250
1,250
1,000
1,600
1,600
1,600
1,000
1,000
1,600
1,000
1,000
4
Area of inlet vents: 350cm
Area of outlet vents: 350cm2
2
Ta=55°C
1,250
3
2
1
1,250
1,250
1,250
1,250
1,250
1,250
1,000
1,500
1,600
1,470
1,000
1,000
1,600
1,000
1,000
4
Non ventilated switchboard
(IP41/54)
Ta=35°C
1,250
3
2
1
1,250
1,250
1,250
1,250
1,250
1,250
1,000
1,600
1,600
1,600
1,000
1,000
1,600
1,000
1,000
4
Ta=45°C
H
H
1,250
3
2
1
1,250
1,250
1,250
1,250
1,250
1,250
1,000
1,480
1,600
1,500
1,000
1,000
1,600
1,000
1,000
4
D
W
D
W
Ta=55°C
1,250
3
2
1
1,250
1,250
1,250
1,250
1,250
1,250
1,000
1,400
1,520
1,400
1,000
1,000
1,500
1,000
1,000
※ H: 2,300mm, W: 800mm, D: 900mm
U-Series Air Circuit Breaker_ 99
U-Series
/ Air Circuit Breaker
Technical Data
| Derating table |
 B frame
Ambient temperature outside of the switchboard: Ta (IEC 60439-1)
4
3
2
1
Switchboard composition
connection type
4
3
2
1
Applicable ACB
Busbar dimensions (mm)
UAN/UAS201)
2EA x 75 x 10
4
3
2
1
UAN/UAS25
3EA x 75 x 10
4
3
2
1
UAN/UAS32
4EA x 75 x 10
UAN40
4EA x 75 x 10
4
Ventilated switchboard (IP31)
Ta=35°C
3
2
2,000
2,000
2,000
2,000
2,400
2,500
3,100
3,200
3,400
3,750
2,300
2,400
2,900
3,100
3,200
3,550
2,200
2,300
2,700
2,900
3,000
3,300
2,115
2,275
2,650
2,850
3,040
3,320
2,000
2,150
2,550
2,700
2,880
3,120
1,900
2,020
2,370
2,530
2,720
2,960
1
4
H
H
Ta=45°C
3
2
2,000
2,000
2,000
2,000
1
D
W
D
W
4
Area of inlet vents: 350cm
Area of outlet vents: 350cm2
2
Ta=55°C
3
2
2,000
2,000
2,000
2,000
1
4
Non ventilated switchboard
(IP41/54)
Ta=35°C
3
2
2,000
2,000
2,000
2,000
1
4
Ta=45°C
H
H
3
2
1,900
1,900
1,960
1,960
1
4
D
W
D
W
Ta=55°C
3
2
1
※ - H: 2,300mm, W: 800mm, D: 900mm
1) UAN20 A frame type is also applicable.
100
1,780
1,800
1,920
1,920
ACB
 C/D frame
Ambient temperature outside of the switchboard: Ta (IEC 60439-1)
4
3
2
1
Switchboard composition
connection type
Applicable ACB
Busbar dimensions (mm)
4
3
2
1
4
3
2
1
4
3
2
1
UAN40 (C)
4EA x 100 x 10
UAN50 (C)
4EA x 125 x 10
UAN40 (D)
4EA x 100 x 10
2,900
4,000
4,750
4,800
4,000
3,850
3,900
4,350
4,650
3,800
3,850
4,200
3,800
3,900
3,650
3,550
4
3
2
1
UAN50 (D)
4EA x 125 x 10
UAN63 (D)
4EA x 150 x 10
4,000
4,750
5,000
5,850
6,300
4,000
4,000
4,450
4,850
5,670
5,850
4,400
4,000
4,000
4,200
4,600
5,350
5,670
4,200
4,550
4,000
4,000
4,400
4,650
5,350
5,000
3,800
3,950
4,250
4,000
4,000
4,100
4,400
5,040
5,350
3,650
3,700
4,050
3,900
3,950
3,850
4,150
4,730
5,040
4
Ventilated switchboard (IP31)
Ta=35°C
3
2
1
4
H
H
Ta=45°C
3
2
1
D
W
D
W
4
Area of inlet vents: 350cm
Area of outlet vents: 350cm2
2
Ta=55°C
3
2
1
4
Non ventilated switchboard
(IP41/54)
Ta=35°C
3
2
1
4
Ta=45°C
H
H
3
2
1
4
D
W
D
W
Ta=55°C
3
2
1
※ H: 2,300mm, W: 800mm, D: 900mm
U-Series Air Circuit Breaker_ 101
U-Series
/ Air Circuit Breaker
Technical Data
| Discrimination table |
•Breaking capacity: at AC380/415V
Downstream
Upstream
ACB
Recognition
category
UAN/UAS A frame
Model
HiBD63-NS
B, C curve
MCB
HiBD63-N
B, C, D curve
HiBD63H
B, C, D curve
※
102
Can be blocked all sectors.
UAN/UAS B frame
UAN C frame
630
800
Breaking
capacity [Icu]
(kA r.m.s)
85
85
85
85
85
85
100
100
100
100
100
100
1
4.5
T
T
T
T
T
T
T
T
T
T
T
T
2
4.5
T
T
T
T
T
T
T
T
T
T
T
T
5
4.5
T
T
T
T
T
T
T
T
T
T
T
T
6
4.5
T
T
T
T
T
T
T
T
T
T
T
T
10
4.5
T
T
T
T
T
T
T
T
T
T
T
T
16
4.5
T
T
T
T
T
T
T
T
T
T
T
T
20
4.5
T
T
T
T
T
T
T
T
T
T
T
T
25
4.5
T
T
T
T
T
T
T
T
T
T
T
T
32
4.5
T
T
T
T
T
T
T
T
T
T
T
T
40
4.5
T
T
T
T
T
T
T
T
T
T
T
T
1
6
T
T
T
T
T
T
T
T
T
T
T
T
2
6
T
T
T
T
T
T
T
T
T
T
T
T
3
6
T
T
T
T
T
T
T
T
T
T
T
T
4
6
T
T
T
T
T
T
T
T
T
T
T
T
5
6
T
T
T
T
T
T
T
T
T
T
T
T
Rated
current
(A)
1,000 1,200 1,250 1,600 2,000 2,500 3,200 4,000 4,000 5,000
6
6
T
T
T
T
T
T
T
T
T
T
T
T
10
6
T
T
T
T
T
T
T
T
T
T
T
T
13
6
T
T
T
T
T
T
T
T
T
T
T
T
15
6
T
T
T
T
T
T
T
T
T
T
T
T
16
6
T
T
T
T
T
T
T
T
T
T
T
T
20
6
T
T
T
T
T
T
T
T
T
T
T
T
25
6
T
T
T
T
T
T
T
T
T
T
T
T
32
6
T
T
T
T
T
T
T
T
T
T
T
T
40
6
T
T
T
T
T
T
T
T
T
T
T
T
50
6
T
T
T
T
T
T
T
T
T
T
T
T
63
6
T
T
T
T
T
T
T
T
T
T
T
T
1
10
T
T
T
T
T
T
T
T
T
T
T
T
2
10
T
T
T
T
T
T
T
T
T
T
T
T
3
10
T
T
T
T
T
T
T
T
T
T
T
T
4
10
T
T
T
T
T
T
T
T
T
T
T
T
5
10
T
T
T
T
T
T
T
T
T
T
T
T
6
10
T
T
T
T
T
T
T
T
T
T
T
T
10
10
T
T
T
T
T
T
T
T
T
T
T
T
13
10
T
T
T
T
T
T
T
T
T
T
T
T
15
10
T
T
T
T
T
T
T
T
T
T
T
T
16
10
T
T
T
T
T
T
T
T
T
T
T
T
20
10
T
T
T
T
T
T
T
T
T
T
T
T
Can not be blocked.
ACB
•Breaking capacity: at AC380/415V
Downstream
Upstream
ACB
Recognition
category
UAN/UAS A frame
Model
HiBD63h
B, C, D curve
MCB
HiBD125
B, C, D curve
UAB100
C, R, S
MCCB
UCB100
R, S, H, L
UCB250
R, S, N, H, L
※
Can be blocked all sectors.
UAN/UAS B frame
UAN C frame
630
800
Breaking
capacity [Icu]
(kA r.m.s)
85
85
85
85
85
85
100
100
100
100
100
100
25
10
T
T
T
T
T
T
T
T
T
T
T
T
32
10
T
T
T
T
T
T
T
T
T
T
T
T
40
10
T
T
T
T
T
T
T
T
T
T
T
T
50
10
T
T
T
T
T
T
T
T
T
T
T
T
63
10
T
T
T
T
T
T
T
T
T
T
T
T
63
10
T
T
T
T
T
T
T
T
T
T
T
T
Rated
current
(A)
1,000 1,200 1,250 1,600 2,000 2,500 3,200 4,000 4,000 5,000
80
10
T
T
T
T
T
T
T
T
T
T
T
T
100
10
T
T
T
T
T
T
T
T
T
T
T
T
125
10
T
T
T
T
T
T
T
T
T
T
T
T
5
30
T
T
T
T
T
T
T
T
T
T
T
T
10
30
T
T
T
T
T
T
T
T
T
T
T
T
15
30
T
T
T
T
T
T
T
T
T
T
T
T
20
30
T
T
T
T
T
T
T
T
T
T
T
T
30
30
T
T
T
T
T
T
T
T
T
T
T
T
40
30
T
T
T
T
T
T
T
T
T
T
T
T
50
30
T
T
T
T
T
T
T
T
T
T
T
T
60
30
T
T
T
T
T
T
T
T
T
T
T
T
75
30
T
T
T
T
T
T
T
T
T
T
T
T
100
30
T
T
T
T
T
T
T
T
T
T
T
T
15
50
T
T
T
T
T
T
T
T
T
T
T
T
20
50
T
T
T
T
T
T
T
T
T
T
T
T
30
50
T
T
T
T
T
T
T
T
T
T
T
T
40
50
T
T
T
T
T
T
T
T
T
T
T
T
50
50
T
T
T
T
T
T
T
T
T
T
T
T
60
50
T
T
T
T
T
T
T
T
T
T
T
T
75
50
T
T
T
T
T
T
T
T
T
T
T
T
100
50
T
T
T
T
T
T
T
T
T
T
T
T
125
50
T
T
T
T
T
T
T
T
T
T
T
T
100
50
T
T
T
T
T
T
T
T
T
T
T
T
125
50
T
T
T
T
T
T
T
T
T
T
T
T
150
50
T
T
T
T
T
T
T
T
T
T
T
T
175
50
T
T
T
T
T
T
T
T
T
T
T
T
200
50
T
T
T
T
T
T
T
T
T
T
T
T
225
50
T
T
T
T
T
T
T
T
T
T
T
T
250
50
T
T
T
T
T
T
T
T
T
T
T
T
Can not be blocked.
U-Series Air Circuit Breaker_ 103
U-Series
/ Air Circuit Breaker
Technical Data
| Discrimination table |
•Breaking capacity: at AC380/415V
Downstream
Upstream
ACB
Recognition
category
UAN/UAS A frame
Model
UCB400
R, S, N, H, L
UCB630
R, S, H, L
UCB800
R, S, H, L
UPB100
S, H, L, X
MCCB
UPB250
R, S, N, H, L
UPB400
S, H, L, X
UPB630
S, H, L, X
※
104
Can be blocked all sectors.
UAN/UAS B frame
UAN C frame
630
800
Breaking
capacity [Icu]
(kA r.m.s)
85
85
85
85
85
85
100
100
100
100
100
100
250
100
T
T
T
T
T
T
T
T
T
T
T
T
300
100
T
T
T
T
T
T
T
T
T
T
T
T
320
100
T
T
T
T
T
T
T
T
T
T
T
T
350
100
T
T
T
T
T
T
T
T
T
T
T
T
400
100
T
T
T
T
T
T
T
T
T
T
T
T
500
100
-
T
T
T
T
T
T
T
T
T
T
T
630
100
-
T
T
T
T
T
T
T
T
T
T
T
700
100
-
-
T
T
T
T
T
T
T
T
T
T
800
100
-
-
T
T
T
T
T
T
T
T
T
T
15
150
T
T
T
T
T
T
T
T
T
T
T
T
20
150
T
T
T
T
T
T
T
T
T
T
T
T
30
150
T
T
T
T
T
T
T
T
T
T
T
T
40
150
T
T
T
T
T
T
T
T
T
T
T
T
50
150
T
T
T
T
T
T
T
T
T
T
T
T
63
150
T
T
T
T
T
T
T
T
T
T
T
T
Rated
current
(A)
1,000 1,200 1,250 1,600 2,000 2,500 3,200 4,000 4,000 5,000
80
150
T
T
T
T
T
T
T
T
T
T
T
T
100
150
T
T
T
T
T
T
T
T
T
T
T
T
125
150
T
T
T
T
T
T
T
T
T
T
T
T
125
150
T
T
T
T
T
T
T
T
T
T
T
T
150
150
T
T
T
T
T
T
T
T
T
T
T
T
175
150
T
T
T
T
T
T
T
T
T
T
T
T
200
150
T
T
T
T
T
T
T
T
T
T
T
T
225
150
T
T
T
T
T
T
T
T
T
T
T
T
250
150
T
T
T
T
T
T
T
T
T
T
T
T
250
150
T
T
T
T
T
T
T
T
T
T
T
T
300
150
T
T
T
T
T
T
T
T
T
T
T
T
320
150
T
T
T
T
T
T
T
T
T
T
T
T
350
150
T
T
T
T
T
T
T
T
T
T
T
T
400
150
T
T
T
T
T
T
T
T
T
T
T
T
320
150
T
T
T
T
T
T
T
T
T
T
T
T
350
150
T
T
T
T
T
T
T
T
T
T
T
T
400
150
T
T
T
T
T
T
T
T
T
T
T
T
500
150
-
T
T
T
T
T
T
T
T
T
T
T
630
150
-
T
T
T
T
T
T
T
T
T
T
T
Can not be blocked.
ACB
Operating Conditions
| Ambient temperature |
| Relative humidity |
•Operating condition: -5˚C to 40˚C is recommended.
•Cradle is fixed to a switchboard.
•The average temperature for 24 hours should be within 35˚C.
•Reduce the continuous conducting current when the
temperature is over 45˚C (Refer to derating table, 98page).
•Relative humidity should be under 85%.
| Load (I/In) |
| Storage conditions |
Load
Using
24/24 Hours
I/In ≤ 80%
80 < I/In ≤ 90% 24/24 Hours
I/In = 100%
Effect
-
Installation
Normal condition (Recommend)
Periodic inspection
insulator
24/24 Hours Plastic
color changed
Exhaust added
•Device without its control unit: -25˚C to 85˚C
•Device with control unit: -15˚C to 70˚C
•The product with charging motor should be stored in
open position.
| Atmospheric conditions |
•Do not apply under corrosive or ammonia gas circumstances (H2S, SO2, NH3).
•Use in clean air condition.
| Altitude |
Item
2,000m (6,600 feet)
Altitude
2,600m (8,500 feet)
3,900m (13,000 feet)
1,000
690
1 x In
950
655.5
0.99 x In
800
552
0.96 x In
Isolation voltage [V]
Operating voltage [V]
Allowed current [A]
| Protection degree provided by enclosures (IP code)|
•Standard: IP30
•With dust cover: IP52
IP  
First characteristic numeral × (Numerals 0 to 6, or letter ×)
Second characteristic numeral × (Numerals 0 to 8, or letter ×)
Code letters (International protection)
Degree of protection
First characteristic numeral
Second characteristic numeral
0
1
2
3
4
5
6
Non-protected
Protected against solid foreign objects of 50mm ø and greater
Protected against solid foreign objects of 12.5mm ø and greater
Protected against solid foreign objects of 2.5mm ø and greater
Protected against solid foreign objects of 1.0mm ø and greater
Dust-protected (Ingress of dust is not totally prevented)
Dust-tight (No ingress of dust)
Non-protected (OPEN)
Protected against vertically falling water drops
Protected against vertically falling water drops when enclosure tilted up to 15˚
Protected against spraying water (at an angle up to 60)
Protected against spraying water (Splash proof)
Protected against spraying jets (Hose proof)
Protected against powerful water jets (Deckwater proof)
7
-
Protected against the effects of temporary immersion in water
(Under pressure and time)
8
-
Protected against the effects of continuous immersion in water
(Submersible)
U-Series Air Circuit Breaker_ 105
U-Series
/ Air Circuit Breaker
Ordering Sheet
•To indicate your choice, check the applicable boxes and enter the appropriate information corresponding to your choice.
ACB body
Type of ACB
UAS1)
UAN
AF
Frame size
A (630-2,000AF)2)
B (630-4,000AF)3)
C (3,200-5,000AF)
D (4,000-6,300AF)
Phase type
Standard type (R, S, T, N)
Reverse phase type (N, R, S, T)
Number of poles
3 pole
4 pole
Type of equipment
Draw-out type
Fixed type
Terminal
connection
(Draw-out type)
Manual connection
Auto connection
Terminal busbar
arrangement
(Fixed type)
Horizontal
Charging
Manual closing
Electrical closing
Vertical
Horizontal/Vertical (Line/Load)
AC/DC110V
AC/DC220V
• Motor operating voltage
Vertical/Horizontal (Line/Load)
DC125V
AC380V 5)
DC24V
AC440V 5)
DC48V
Closing voltage
AC/DC110V
DC125V
AC/DC220V
DC24V
DC48V
AC380V
AC440V
Trip voltage
AC/DC110V
DC125V
AC/DC220V
DC24V
DC48V
AC380V
AC440V
Protection trip
relay
NO
YES
33
43 UPR-1L-GS
-
Ground
Signal
fault
detection6)

General feeder
Integrated instantaneous 1a

-
-

-
-
35
45 UPR-2L-GS

General feeder

Individual continuous 4a

-
-



36
46 UPR-1D-GT

General feeder

Individual continuous 4a






37
47 UPR-2L-GM

General feeder

Integrated continuous 3a8)

-
-



38
48 UPR-1S-AL
-
Generator
-
Integrated instantaneous 1a
-
-
-

-
-
39
49 UPR-2S-AS

Generator
-
Individual continuous 3a9)
-
-
-



50Hz 60Hz
Current transformer
Accessory
80A
Model
LCD/LED
Application
NCT
ELT Comm7) MCR Memory Adaptor
160A · · · ·
•UVT coil
(Instantaneous type)
AC/DC110V
AC/DC220V
DC125V
AC380V
DC24V
AC440V
DC48V
•Double trip coil10)
AC/DC110V
AC/DC220V
DC125V
AC380V
DC24V
AC440V
DC48V
•Trip supervision coil
AC/DC110V
AC/DC220V
DC125V
AC380V
DC24V
AC440V
DC48V
•Auxiliary switch
3a3b (Standard for UAS)
•OCR MCR wire
Complete parts of ACB/Cradle
Spare part
•OCR & Alarm switch
reset button
BR: OCR (Only for manual reset button)
BM: OCR (Auto reset)+Alarm switch
BA: OCR manual reset+Alarm switch
•Fixing block11)
Complete parts of ACB/Cradle
Spare part
•Wrong insertion preventer11)
Complete parts of ACB/Cradle
Spare part
•Key lock device
Complete parts of ACB/Cradle
Spare part
•ON/OFF button lock
Complete parts of ACB/Cradle
Spare part
•Mechanical interlock12)
Complete parts of ACB/Cradle
Spare part
•Spring charge switch
Complete parts of ACB/Cradle
Spare part
5a5b (Standard for UAN)
•Counter (Standard)
106
Front type or others4)
6a6b (Maximum)
ACB
Cradle
Control terminal
Manual connection
Terminal busbar
arrangement
Horizontal
Accessory
ACB accessory
Purchase
separately
Vertical
Horizontal/Vertical (Line/Load)
Vertical/Horizontal (Line/Load)
Front type or others4)
•Safety shutter lock13)
Complete parts of ACB/Cradle
Spare part
•Fixing block11)
Complete parts of ACB/Cradle
Spare part
•Wrong insertion preventor11)
Complete parts of ACB/Cradle
Spare part
•Arc shield
Complete parts of ACB/Cradle
Spare part
•Short “b” contact14)
Complete parts of ACB/Cradle
Spare part
•Control terminal protection cover15)
Complete parts of ACB/Cradle
Spare part
•Mechanical operated cell switch
Complete parts of ACB/Cradle
Spare part
•UVT time delay
controller16)
AC/DC 110V
AC/DC 220V
DC 24V
AC 440V
•Position switch16)
AQ=Test1C, Connected1C
AT=Inserted1C, Isolated1C
PQ=Inserted1C, Isolated1C,
Test1C, Connected1C
•Mechanical interlock
Wire type (2 terminals)
Wire type (3 terminals)
•Condenser trip device
AC110V
AC220V
•Phase insulation barrier
•Test jumper
•Draw-in/out handle
DC 125V
AC 380V
AR=Connected2C
AU=Inserted2C
P4=Test2C, Connected2C
DC 48V
AS=Test2C
AV=Isolated2C
P8=Inserted2C, Isolated2C,
Test2C, Connected2C
•OCR portable checker
Standard type
Long type
Universal type
•ATS Controller
•Automatic transfer switch & controller
•Lifting lug
•Dummy ACB
•Door flange
•Dust cover
•ZCT (Consultation)
•NCT (Consultation)
•Profibus-DP comm.
•Remote operation & temperature detection module
※ 1) In case of UAS, A frame size is in the range of 630-1,600AF and B frame size is in the range of 2,000-3,200AF.
2) In case of UAN 20A, only vertical type is available.
3) In case of UAN, B frame size of 630-1,600AF is possible.
4) Front type/User installation need to be ordered separately and attached by the customer. 630-1,600AF is available
for A frame and 2,000-3,200AF is available for B frame.
5) Motor of AC380/440V is available from June. 2013.
6) Standard function for general feeder: Ground fault detection.
7) Communication function is not available under no control voltage.
8) LTD/STD/INST/ELT (except. PTA)
9) LTD/STD/INST/PTA (except. GFT)
10) In case of ordering UVT, double trip coil is not available.
11) In case of ordering fixing block and wrong insertion preventer, mark on both ACB and cradle ordering sheet.
12) MI is separate purchasing item, only assembled parts interacting inside of the body are delivered.
13) In case of ordering safety shutter-attachment type, shutter lock is automatically implemented.
14) Fixing block and wrong insertion preventer have to be marked on both the body and cradle orders.
15) Control terminal protection cover is only available for automatic connection type.
16) UVT controller and position switch can be offered as mounted.
U-Series Air Circuit Breaker_ 107
HHIS-WC-LE-B74-00, 2013.2 Designed by JC Creative
www.hyundai-elec.com
Head Office
1000, Bangeojinsunhwan-doro, Dong-gu, Ulsan, Korea
Tel: 82-52-202-8101~8
Fax: 82-52-202-8100
Seoul
(Sales & Marketing)
75, Yulgok-ro, Jongno-gu, Seoul, Korea
Tel: 82-2-746-8519, 7492, 7620
Fax: 82-2-746-7441
Atlanta
6100 Atlantic Boulevard, Norcross, GA 30071, USA
Tel: 1-678-823-7839
Fax: 1-678-823-7553
London
2nd Floor, The Triangle, 5-17 Hammersmith Grove London, W6 0LG, UK
Tel: 44-20-8741-0501
Fax: 44-20-8741-5620
Moscow
World Trade Center, Ent. 3# 1902, Krasnopresnenskays Nab. 12, Moscow, 123610, Russia
Tel: 7-495-258-1381
Fax: 7-495-258-1382
Madrid
Paseo De La Castellana 216, Planta 0, 28046 Madrid, Spain
Tel: 34-91-732-0454, 733-6069
Fax: 34-91-733-2389
Tokyo
8th Floor, North Tower Yurakucho Denki Bldg., 1-7-1 Yuraku-cho, Chiyoda-ku, Tokyo 100-0006, Japan
Tel: 81-3-3211-4792
Fax: 81-3-3216-0728
Osaka
I-Room 5th Floor Nagahori Plaza Bldg. 2-4-8 Minami Senba, Chuo-ku, Osaka, 542-0081, Japan
Tel: 81-6-6261-5766~7 Fax: 81-6-6261-5818
Mumbai
5th Floor, East Quadrant, The IL & FS Financial Centre, Plot No. C-22, G-Block,
Bandra-kurla Complex, Bandra(E), Mumbai 400 051, India
Tel: 91-22-2653-3420~26 Fax: 91-22-2653-3429
Riyadh
Office No. 230, 2nd Floor, 4th Akariya Plaza Olaya Street, PO Box 8072, Riyadh 11485, Saudi Arabia
Tel: 966-1-464-4696 Fax: 966-1-462-2352
Dubai
Unit 205, Building 4, Emaar Square, Sheikh Zayed Road, Pobox 252458, Dubai, UAE
Tel: 971-4-425-7995
Fax: 971-4-425-7996
Kuwait
15th Floor, Al-Sour Tower, Al Sour Street, Al-Qiblah, Kuwait
Tel: 965-2291-5354
Fax: 965-2291-5355
Sofia
1271, Sofia 41, Rojen Blvd., Bulgaria
Tel: 359-2-803-3200, 3220
Montgomery
215 Folmar Parkway, Montgomery, AL 36105, USA
Tel: 1-334-481-2000
Fax: 1-334-481-2098
Vladivostok
15, str. Potemkina, Artem, Primorskiy Krai, 692760, Russia
Tel: 7-423-201-0110
Fax: 7-423-201-0110
Yangzhong
No.9 Xiandai Road, Xinba Scientific and Technologic Zone, Yangzhong, Jiangsu, P.R.C. Zip: 212212, China
Tel: 86-511-8842-0666, 0212
Fax: 86-511-8842-0668, 0231
Fax: 359-2-803-3203

Similar documents

RX8--Engine Specifications

RX8--Engine Specifications 1 Engine mount rubber (RH) 2 Engine mount bracket (RH) 3 Engine mount rubber (LH) 4 Engine mount bracket (LH) 5 Engine, transaxle 6 AT oil cooler pipe 16. Install in the reverse order of removal. ...

More information

ACB Protection Relays - Hoàng Trang Co.com.vn

ACB Protection Relays - Hoàng Trang Co.com.vn 04 - Qualified Standard & Approval 05 - Features

More information

DONG-A PRODUCTS GUIDE

DONG-A PRODUCTS GUIDE ·AC Controls DC exitation system for voltage dip ·Acquired overseas certificate (CE, VDE, CCC, TUV)

More information

Contactor 3 P ole

Contactor 3 P ole Contactors Type MC-9B/R MC-12B/R MC-18B/R MC-22B/R MC-32A/R MC-40A/R MC-50A/R MC-65A/R MC-75A/R MC-85A/R MC-100A/R

More information