Outdoor Units

Transcription

Outdoor Units
SERVICE MANUAL
ON/OFF SERIES
ASF-60AN, ASC-60AN
External Appearance
External Appearance
Indoor Units
Super-slim 4-way Cassette
Ceiling & floor type
Outdoor Units
Double fan outdoor unit
1
Features
Features
High quality coils:
The coil is constructed of advanced inner grooved copper tube and aluminum fins.
Anti-rust, 500 hours salt spray test.
Low operation sound level: Well-known stable and quiet running fan motor.
Well-known compressor.
Compact design: Smaller dimension and larger stuffing capacity.
Universal outdoor unit design.
Optional air outlet grille: plastic type and wire type.
Wire type
Plastic type
Plastic type
Optional low temperature cooling module.
R410A environment friendly refrigerant.
2
Model
ASC-60AN
Power supply
(indoor )
V- Ph-Hz
220~240-1-50
Power supply
(outdoor )
V- Ph-Hz
380~415-3-50
Capacity
Cooling
Heating
Btu/h
51000
Input
W
6030
Current
A
10,41
EER
W/W
2,48
Capacity
Btu/h
58000
Input
W
6410
Current
A
11,07
W/W
2,65
COP
Model
WZDK124-38G
Qty
Indoor fan motor
Input
Capacitor
1
w
124(Output)
uF
/
r/min
770/610/540
Indoor air flow (Hi/Med/Lo)
m3/h
2100/1800/1600
Sound level (sound pressure)
dB(A)
55/50/47
Speed(hi/mi/lo)
Throttle type
Indoor unit
/
Dimension (W x Dx H)(body)
mm
840x840x287
Packing (W x Dx H)(body)
mm
900x900x292
Dimension (W x Dx H)(panel)
mm
950x950x55
Packing (W x Dx H)(panel)
mm
1035x1035x90
kg
28.3/32.5
Net/Gross weight(body)
kg
5/8
Design pressure
Net/Gross weight(panel)
MPa
4.2/1.5
Drainage water pipe dia.
mm
ODĭ32
Refrigerant piping
mm
ĭ9.52/ĭ19(3/8"/3/4")
Standard
Remote-RG51C/E
ഒ
17~30
ഒ
17~32
Liquid side/ Gas side
Controller
Operation temperature
Room temperature
Cooling
ഒ
Heating
Remarks:1.The above design and specifications are subject to change
0~30
Model
ASF-60AN
Power supply
(indoor )
V- Ph-Hz
220~240-1-50
Power supply
(outdoor )
V- Ph-Hz
380~415-3-50
Btu/h
52000
W
5370
Capacity
Cooling
Input
A
9.27
EER
W/W
2.84
Capacity
Btu/h
57100
Input
W
5400
Current
A
9.32
Current
Heating
COP
W/W
Model
Qty
Indoor fan motor
Input
Capacitor
Speed(Hi/Med/Lo)
2
W
90(Output)
uF
/
r/min
1320/1200/1120
3
Number of rows
Indoor coil
3.1
WZDK90-38GS-W
Tube pitch(a)x row pitch(b)
mm
21x13.37
Fin spacing
mm
1,3
Tube outside dia.and type
mm
Ɏ7,Inner grooved tube
Coil length x height x width
mm
1300x294x40.11
m3/h
dB(A)
2550/2150/1850
Fin type
Hydrophilic aluminium
8
Number of circuits
Indoor air flow(Hi/Med/Lo)
Indoor noise level (sound pressure)(Hi/Med/Lo)
55/52/50
/
Throttle type
Dimension (WxDxH)
mm
1650x675x235
Packing (WxDxH)
mm
1725x755x313
Net/Gross weight
kg
40/46
Design pressure
MPa
Drainage water pipe diameter
mm
4.2/1.5
ODĭ25
mm(inch)
ĭ9.52/ĭ19(3/8"/3/4")
Standard
Remote-RG51Q1/BGE
ഒ
17~30
ഒ
17~32
ഒ
Heating
Remarks:1.The above design and specifications are subject to change
0~30
Indoor unit
Refrigerant piping
Liquid side/Gas side
Controller
Operation temperature
Room temperature
Cooling
V-ph-Hz
ASF-60AN, ASC-60AN
OUTDOOR UNIT
380~415-3-50
Max. input consumption
W
7000
Max. input current
A
19
Model
Power supply
Model
C-SBN453H8D
Type
Scroll
Brand
Capacity
Compressor
Sanyo
Btu/h
55957
Input
W
5750
Rated current(RLA)
A
9,77
Locked rotor Amp(LRA)
A
Thermal protector position
Capacitor
ȝF
Refrigerant oil
ml
Model
Input
2
W
142/127
ȝF
5UF/450V
880/810
Tube pitch(a)* row pitch(b)
mm
22x19.05
Fin spacing
mm
Speed
1,6
Number of rows
Fin type
Tube outside dia.and type
mm
Ɏ7.94,inner grooved tube
Coil length * height * width
mm
995×1320×19.05+593x1320x19.05
m3/h
dB(A)
7500
Dimension(WxDxH)
mm
938x392x1369
Packing(WxDxH)
mm
1095x495x1505
Net/Gross weight
kg
111.1/125.4
Outdoor air flow (Max.)
Outdoor noise level (sound pressure)
10
Throttle type
Refrigerant type/Quantity
63
Capillary
Type
Charged volume
Design pressure
Liquid side/ Gas side
Refrigerant piping
1.5
Hydrophilic aluminium
Number of circuits
Outdoor unit
1700
r/min
Capacitor
Outdoor coil
/
YDK90-6D
Qty
Outdoor fan motor
67
Internal
R410A
kg
3.5
MPa
4.2/1.5
mm(inch)
ĭ9.52/ĭ19(3/8"/3/4")
Max. pipe length
m
50
Max. difference in level
m
25
18~43
ഒ
Cooling
ഒ
-7ᨺ24
Heating
Remarks:1.Theabovedesignandspecificationsaresubjecttochangewithoutpriornoticeforproductimprovement.
Ambient temperature
Indoor Units
Indoor Units
Super-slim Cassette Type ..................................................4
Ceiling & Floor Type ...........................................................17
3
Super-slim Cassette Type
Super-slim Cassette Type
1. Features ......................................................................5
2. Dimensions .................................................................9
3. Service Space .............................................................10
4. Wiring Diagrams .........................................................11
5. Electric Characteristics .............................................12
6. Sound Levels ..............................................................13
7. Accessories ................................................................14
8. The Specification of Power .......................................15
9. Field Wiring ................................................................. 16
4
Features
1. Features
1.1
¾
¾
¾
Overview
Compact design, super slim body size, less space requiring in installation
Each louver can be separately controlled, more comfort air blowing is possible.
Auto-lifting panel design, more convenient to clean and maintain the filter. (optional)
60K
Old Cassette
New Slim Cassette
Reduction
840*300*840
840*287*840
4%Ļ
1.2 Fresh air intake function
¾ Fresh air fulfills air quality more healthy and comfortable.
¾ Ventilation motor is optional to increase the effect of fresh air.
5
Features
New air-intake
1.3
¾
¾
Optional ionizer generator
Ionizer generator is optional to get refreshing air to your room.
Ionizer generator
connector
Ventilation motor
connector
Ionizer can be switched on or off by remote controller.
When pressing the Clean Air button on the remote controller, Ionizer will work and the indicator light on
display board will shine.
6
Features
1.4
¾
External air duct design
Reserve external
air duct, more flexible for the air supply.
Built-in draining pump
1.5
¾ Due to the improvement of structure, more convenient to repair or replace the draining pump.
Draining Pump
¾
Built-in draining pump to make sure condensed water drain out reliably.
7
Features
1.6
¾
Terminals for alarm lamp and long-distance on-off controller connection are
standard
Reserve terminals for the connection of alarm lamp and long-distance on-off controller, more human
control.
Alarm lamp
Long-distance on-off controller
1.7
¾
¾
Optional touch screen wired controller
Touch screen wired controller is optional, with error code indication function. Better
man-machine conversation interface.
Undated structure design, 4-way wire layout design, no raised part at backside, more convenient to
place the wires and install the device.
8
Dimensions
2. Dimensions
Model
ASC-60AN
A
287
H
>317
9
Service Space
>1000m m
>1000mm
>1000mm
3. Service Space
>1000mm
10
Wiring Diagrams
4. Wiring Diagrams
ASC-60AN
11
Field Wiring
5. Electric Characteristics
Model
ASC-60AN
Note:
MFA: Max. Fuse Amps. (A)
Indoor Unit
Power Supply
Hz
Voltage
Min
Max
MFA
50
220-240V
198V
254V
16
12
Sound Levels
6. Sound Levels
P
Microphone
Model
ASC-60AN
Noise level dB(A)
H
M
L
55
50
47
13
Field Wiring
7. Accessories
Name
INSTALLATION FITTINGS
Tubing & Fittings
Drainpipe Fittings
Remote controller & Its
Frame
Others
Installation accessory
(The product you have
might not be provided the
following accessories
Shape
Quantity
Installation paper board
1
Bolt M5
4
Soundproof / insulation sheath
2
Out-let pipe
1
Out-let pipe sheath
1
Out-let pipe clasp
1
Remote controller & Its Frame
1
Remote controller holder
1
Mounting screw(ST2.9×10-C-H)
2
Remote controller manual
1
Alkaline dry batteries (AM4)
2
Owner's manual
1
Installation manual
1
Network wires
1
Expansible hook
4
Installation hook
4
Orifice
1
14
The Specification of Power
8. The Specification of Power
Model
ASC-60AN
Phase
INDOOR UNIT POWER
1-phase
Frequency and Voltage
220-240V, 50Hz
POWER WIRING (mm2)
3×1.0
Circuit Breaker/ Fuse (A)
Phase
OUTDOOR UNIT POWER
20/16
3-phase
Frequency and Voltage
2
380-415V, 50Hz
POWER WIRING (mm )
5×2.5
Circuit Breaker/ Fuse (A)
Indoor/Outdoor Connecting Wiring
(Weak Electric Signal) (mm2)
Indoor/Outdoor Connecting Wiring
2
(Strong Electric Signal) (mm )
25/20
3×0.2
15
Field Wiring
9. Field Wiring
ASC-60AN
16
Ceiling & Floor Type
Ceiling & Floor Type
1. Features ...........................................................................18
2. Dimensions......................................................................19
3. Service Space ..................................................................20
4. Wiring Diagrams .............................................................21
5. Electric Characteristics ..................................................22
6. Sound Levels...................................................................22 7. Accessories .....................................................................23
8. The Specification of Power ............................................23
9. Field Wiring .....................................................................24
17
Features
1. Features
1.1. New design, more modern and elegant appearance.
1.2. Convenient installation
--The ceiling type can be easily installed into a corner of the ceiling even if the ceiling is very narrow
--It is especially useful when installation of an air conditioner in the center of the ceiling is impossible
due to a structure such as one lighting.
1.3. Two direction auto swing (vertical & horizontal) and wide angle air flow,
--Air flow directional control minimizes the air resistance and produces wilder air flow to vertical
direction.
--The range of horizontal air discharge is widened which secures wider air flow distribution to provide
more comfortable air circulation no matter where the unit is set up
1.4. Three level fan speed, more humanism design, meets different air-supply requirement.
1.5. New foam drain pan with plastic-spraying inner surface
1.6. Easy operation.
1.7. Remote control and optional wired control method.
18
Dimensions
2. Dimensions
Capacity (Btu/h)
ASF-60AN
A
B
C
D
E
1650
675
235
1565
220
19
Service Space
3. Service Space
20
Wiring Diagrams
4. Wiring Diagrams
ASF-60AN
21
Electric Characteristics
5. Electric Characteristics
Indoor Units
Model
ASF-60AN
Remark:
MFA: Max. Fuse Amps. (A)
Power Supply
Hz
Voltage
Min.
Max.
MFA
50
220-240V
198V
254V
16
6. Sound Levels
1m
1m
Air outlet side
Microphone
1.5m
1m
Microphone
Ceiling
Model
ASF-60AN
Floor
Noise level dB(A)
H
M
L
56
53
51
22
Accessories
7. Accessories
Remote controller & Its
holder
Others
1. Remote controller
1
2. Remote controller holder
1
3. Mounting screw (ST2.9×10-C-H)
2
4. Alkaline dry batteries (AM4)
2
5. Owner's manual
1
6. Installation manual
1
7. Remote controller manual
1
8. The Specification of Power
Model
ASF-60AN
Phase
INDOOR UNIT POWER
1-phase
Frequency and Voltage
2
POWER WIRING (mm )
3×1.0
Circuit Breaker/ Fuse (A)
20/16
Phase
OUTDOOR UNIT POWER
220-240V, 50Hz
3-phase
Frequency and Voltage
2
380-415V, 50Hz
POWER WIRING (mm )
5×2.5
Circuit Breaker/ Fuse (A)
Indoor/Outdoor Connecting Wiring
(Weak Electric Signal) (mm2)
Indoor/Outdoor Connecting Wiring
2
(Strong Electric Signal) (mm )
25/20
3×0.2
23
Field Wiring
9. Field Wiring
ASF-60AN
24
Outdoor Units
Outdoor Units
1. Dimensions ................................................................................................26
2. Service Space ............................................................................................27
3. Piping Diagrams ........................................................................................28
4. Wiring Diagrams ........................................................................................29
5. Electric Characteristics .............................................................................30
6. Operation Limits ........................................................................................31
7. Sound Levels .............................................................................................32
25
Dimensions
1. Dimensions
Model
ASF-60AN, ASC-60AN
Unitφmm
A
B
C
D
E
F
H
938
633.5
404
448
370
392
1369
26
Service Space
2. Service Space
(Wall or obstacle)
Air inlet
More than 30cm
Air inlet
More than 30cm
More than 60cm
Maintain channel
More than 60cm
Air outlet
More than 200cm
27
Piping Diagrams
3. Piping Diagrams
ASF-60AN, ASC-60AN
INDOOR
OUTDOOR
LIQUID SIDE
CHECK VALVE
(Heating Model only)
2-WAY VALVE
T3 Condenser
temp. sensor
CAPILIARY TUBE
HEAT
EXCHANGE
(EVAPORATOR)
HEAT
EXCHANGE
(CONDENSER)
T4 Ambient
temp. sensor
T1 Room temp.
sensor
T2 Evaporator
temp. sensor
GAS SIDE
4-WAY VALVE
3-WAY VALVE
Accumulator
Low pressure
switch
Compressor
High pressure switch
COOLING
HEATING
28
Wiring Diagrams
4. Wiring Diagrams
ASF-60AN, ASC-60AN
29
Electric Characteristics
5. Electric Characteristics
Model
ASF-60AN,ASC-60AN
Outdoor Unit
Hz
Voltage
Min.
Max.
50
380~415V
342V
435V
30
Operation Limits
6. Operation Limits
Temperature
Cooling operation
Mode
Room temperature
17đЊ32đ
Outdoor temperature
18đЊ43đ
Heating operation
-7đЊ24đ
Cooling
STD
Heating
Outdoor temperature(ć DB)
Outdoor temperature(ć DB)
With Low
Ambient
Cooling
System
STD
Indoor temperature(ć WB)
Indoor temperature(ć WB)
31
Sound Levels
7. Sound Levels
Outdoor Unit
Microphone
H
1.0m
Note: H= 0.5 × height of outdoor unit
Model
ASF-60AN,ASC-60AN
Noise level dB(A)
63
32
Installation
Installation
1. Installation Procedure ...............................................................................34
2. Location selection .....................................................................................35
3. Indoor unit installation ..............................................................................36
4. Outdoor unit installation (Side Discharge Unit) ......................................43
5. Refrigerant pipe installation .....................................................................44
6. Drainage pipe installation .........................................................................45
7. Vacuum Drying and Leakage Checking ..................................................49
8. Additional refrigerant charge ...................................................................50
9. Engineering of insulation ......................................................................... 51
10. Engineering of electrical wiring.............................................................52
11. Test operation .........................................................................................52
33
Insulation Work
1. Installation Procedure
Indoor unit installation
location selection
Outdoor unit installation
location selection
Indoor unit installation
Outdoor unit installation
Refrigerant pipe
installation and insulation
Refrigerant pipe
installation and insulation
Drainage pipe installation
and insulation
Drainage pipe installation
and insulation
Vacuum drying and leakage checking
Additional refrigerant charge
Insulation the joint part of refrigerant pipe
Wiring connection and electric safety checking
Test operation
34
Location selection
2. Location selection
2.1 Indoor unit location selection
¾
¾
¾
¾
¾
¾
¾
¾
¾
¾
¾
¾
¾
The place shall easily support the indoor unit’s weight.
The place can ensure the indoor unit installation and inspection.
The place can ensure the indoor unit horizontally installed.
The place shall allow easy water drainage.
The place shall easily connect with the outdoor unit.
The place where air circulation in the room should be good.
There should not be any heat source or steam near the unit.
There should not be any oil gas near the unit
There should not be any corrosive gas near the unit
There should not be any salty air neat the unit
There should not be strong electromagnetic wave near the unit
There should not be inflammable materials or gas near the unit
There should not be strong voltage vibration.
2.2 Outdoor unit location selection
¾
¾
¾
¾
¾
¾
¾
¾
¾
¾
¾
The place shall easily support the outdoor unit’s weight.
Locate the outdoor unit as close to indoor unit as possible
The piping length and height drop can not exceed the allowable value.
The place where the noise, vibration and outlet air do not disturb the neighbors.
There is enough room for installation and maintenance.
The air outlet and the air inlet are not impeded, and not face the strong wind.
It is easy to install the connecting pipes and cables.
There is no danger of fire due to leakage of inflammable gas.
It should be a dry and well ventilation place
The support should be flat and horizontal
Do not install the outdoor unit in a dirty or severely polluted place, so as to avoid blockage of the heat
exchanger in the outdoor unit.
¾ If is built over the unit to prevent direct sunlight, rain exposure, direct strong wend, snow and other scraps
accumulation, make sure that heat radiation from the condenser is not restricted.
More than 30cm
More than 60cm
ᤢ
(Service space
More than 30cm
Fe
n
ob ce o
sta
r
cle
s
More than 60cm
More than 200cm
35
Indoor unit installation
3. Indoor unit inst
3.3 Super-slim cassette indoor unit installation
3.3.1 Service space for indoor unit
Model
ASC-60AN
A
287
H
>317
R410A
Remark
Cooling / Cooling & Heating
3.3.2 Bolt pitch
3.3.3 Install the pendant bolt
Select the position of installation hooks according to the hook holes positions showed in upper picture.
Drill four holes of Ø12mm, 45~50mm deep at the selected positions on the ceiling. Then embed the
expansible hooks (fittings).
36
Insulation Work
3.3.4 Install the main body
Make the 4 suspender through the 4 hanger of the main body to suspend it. Adjust the hexangular nuts on
the four installation hooks evenly, to ensure the balance of the body. Use a leveling instrument to make sure
the levelness of the main body is within f1e.
Adjust the position to ensure the gaps between the body and the four sides of ceiling are even. The body's
lower part should sink into the ceiling for 10~12 mm. In general, L is half of the screw length of the
installation hook.
Locate the air conditioner firmly by wrenching the nuts after having adjusted the body's position well.
37
Indoor unit installation
3.3.5 Install the panel
Remove the grille
Remove the 4 corner covers.
Hang the panel to the hooks on the mainbody. If the panel is with auto-lift grille, please watch the ropes lifing
the grille, DO NOT make the ropes enwinded or blocked.
38
Insulation Work
Tighten the screws under the panel hooks till the panel closely stick on the ceiling to avoid condensate
water.
Hang the air-in grill to the panel, then connect the lead terminator of the swing motor and that of the control
box with corresponding terminators on the body respectively.
Install the 4 corner covers back.
Note: The panel shall be installed after the wiring connected.
39
Indoor unit installation
3.4 Ceiling & floor indoor unit installation
3.4.1 Service space for indoor unit
3.4.2 Bolt pitch
ķ Ceiling installation
Capacity (Btu/h)
ASF-60AN
D
E
1565
220
ĸ Wall-mounted installation
40
Insulation Work
3.4.3 Install the pendant bolt
ķ Ceiling installation
Select the position of installation hooks according to the hook holes positions showed in upper picture.
Drill four holes of Ø12mm, 45~50mm deep at the selected positions on the ceiling. Then embed the
expansible hooks (fittings).
ĸ Wall-mounted installation
Install the tapping screws onto the wall.(Refer to picture below)
3.4.4 Install the main body
ķ Ceiling installation (The only installation method for the unit with drain pump)
Remove the side board and the grille.
41
Indoor unit installation
Locate the hanging arm on the hanging screw bolt. Prepare the mounting bolts on the unit.
Put the side panels and grilles back.
ĸ Wall-mounted installation
Hang the indoor unit by insert the tapping screws into the hanging arms on the main unit. (The bottom of
body can touch with floor or suspended, but the body must install vertically.)
42
Insulation Work
4. Outdoor unit installation (Side Discharge Unit)
4.1 Service space for outdoor unit
4.2 Bolt pitch
Model
B
C
D
ASF-60AN, ASC-60AN
633.5
404
448
4.3 Install the Unit
Since the gravity center of the unit is not at its physical center, so please be careful when lifting it with a sling.
Never hold the inlet of the outdoor unit to prevent it from deforming.
43
Refrigerant pipe installation
Do not touch the fan with hands or other objects.
Do not lean it more than 45, and do not lay it sidelong.
Make concrete foundation according to the specifications of the outdoor units.
Fasten the feet of this unit with bolts firmly to prevent it from collapsing in case of earthquake or strong wind.
5. Refrigerant pipe installation
5.1 Maximum pipe length and height drop
Considering the allowable pipe length and height drop to decide the installation position. Make sure the
distance and height drop between indoor and outdoor unit not exceeded the date in the following table.
Model
Max. Length
Max. Elevation
45,000Btu/h~60,000Btu/h
50m
25m
5.2 The procedure of connecting pipes
90
o
5.2.1 Choose the pipe size according to the specification table.
5.2.2 Confirm the cross way of the pipes.
5.2.3 Measure the necessary pipe length.
5.2.4 Cut the selected pipe with pipe cutter
¾ Make the section flat and smooth.
Lean
Crude
Burr
5.2.5 Insulate the copper pipe
¾
Before test operation, the joint parts should not be heat insulated.
5.2.6 Flare the pipe
¾ Insert a flare nut into the pipe before flaring the pipe
¾ According to the following table to flare the pipe
44
Insulation Work
Flare dimension A (mm)
Pipe diameter
1/4" (6.35)
Flare shape
Min
Max
8.3
8.7
+- 4
90e
45°
3/8" (9.52)
12.0
12.4
1/2" (12.7)
15.4
15.8
5/8" (15.9)
18.6
19.1
3/4" (19)
22.9
23.3
A
R0.4~0.8
¾
After flared the pipe, the opening part must be seal by end cover or adhesive tape to avoid duct or
exogenous impurity come into the pipe.
5.2.7 Drill holes if the pipes need to pass the wall.
5.2.8 According to the field condition to bend the pipes so that it can pass the wall smoothly.
5.2.9 Bind and wrap the wire together with the insulated pipe if necessary.
5.2.10 Set the wall conduit
5.2.11 Set the supporter for the pipe.
5.2.12 Locate the pipe and fix it by supporter
¾ For horizontal refrigerant pipe, the distance between supporters should not be exceed 1m.
¾ For vertical refrigerant pipe, the distance between supporters should not be exceed 1.5m.
5.2.13 Connect the pipe to indoor unit and outdoor unit by using two spanners.
¾ Be sure to use two spanners and proper torque to fasten the nut, too large torque will damage the
bellmouthing, and too small torque may cause leakage. Refer the following table for different pipe
connection.
Torque
Sketch map
Pipe Diameter
(kgf.cm)
(N.cm)
1/4" (6.35)
144~176
1420~1720
3/8" (9.52)
333~407
3270~3990
1/2" (12.7)
504~616
4950~6030
5/8" (15.9)
630~770
6180~7540
3/4" (19)
990~1210
9270~11860
6. Drainage pipe installation
Install the drainage pipe as shown below and take measures against condensation. Improperly installation
could lead to leakage and eventually wet furniture and belongings.
6.1 Installation principle
¾
¾
¾
Ensure at least 1/100 slope of the drainage pipe
Adopt suitable pipe diameter
Adopt nearby condensate water discharge
6.2 Key points of drainage water pipe installation
6.2.1 Considering the pipeline route and elevation
¾ Before installing condensate water pipeline, determine its route and elevation to avoid intersection with
other pipelines and ensure slope is straight.
45
Drainage pipe installation
6.2.2 Drainage pipe selection
¾ The drainage pipe diameter shall not small than the drain hose of indoor unit
¾ According to the water flowrate and drainage pipe slope to choose the suitable pipe, the water flowrate
is decided by the capacity of indoor unit.
Relationship between water flowrate and capacity of indoor unit
Capacity (x1000Btu)
Water flowrate (l/h)
12
2.4
18
4
24
6
30
7
36
8
42
10
48
12
60
14
According to the above table to calculate the total water flowrate for the confluence pipe selection.
For horizontal drainage pipe (The following table is for reference)
PVC pipe
Reference value of inner
diameter of pipe (mm)
PVC25
PVC32
Allowable maximum water flowrate (l/h)
Slope 1/50
Slope 1/100
20
39
27
25
70
50
PVC40
31
125
88
PVC50
40
247
175
PVC63
51
473
334
Remark
For branch pipe
Could be used for confluence pipe
Attention: Adopt PVC40 or bigger pipe to be the main pipe.
For Vertical drainage pipe (The following table is for reference)
PVC25
Reference value of inner
diameter of pipe (mm)
20
PVC32
25
410
PVC40
31
730
PVC50
40
1440
PVC63
51
2760
PVC75
67
5710
PVC90
77
8280
PVC pipe
Allowable maximum water flowrate (l/h)
Remark
220
For branch pipe
Could be used for confluence pipe
Attention: Adopt PVC40 or bigger pipe to be the main pipe.
6.2.3 Individual design of drainage pipe system
¾ The drainage pipe of air conditioner shall be installed separately with other sewage pipe, rainwater pipe
and drainage pipe in building.
¾ The drainage pipe of the indoor unit with water pump should be apart from the one without water pump.
6.2.4 Supporter gap of drainage pipe
¾ In general, the supporter gap of the drainage pipe horizontal pipe and vertical pipe is respectively
1m~1.5m and 1.5m~2.0m.
¾ Each vertical pipe shall be equipped with not less than two hangers.
¾ Overlarge hanger gap for horizontal pipe shall create bending, thus leading to air block.
Too long distance
Gas bag
6.2.5 The horizontal pipe layout should avoid converse flow or bad flow
46
Insulation Work
Drainage pipe
Drainage pipe
Water flow
Water flow
Water flow
Drain tee
Drain tee
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Branch pipe
Drain tee
Drainage pipe
Gas
Gas
Water flow
Keep a certain degree
Main pipe
Main pipe
Branch pipe
¾
The correct installation will not cause converse water flow and the slope of the branch pipes can be
adjusted freely
¾ The false installation will cause converse water flow and the slope of the branch pipe can not be
adjusted.
6.2.6 Water storage pipe setting
¾ If the indoor unit has high extra static pressure and without water pump to elevate the condensate water,
such as high extra static pressure duct unit , the water storage pipe should be set to avoid converse flow
or blow water phenomena.
Indoor unit
More than 50mm
Plug
More than 25mm
Water storage pipe
6.2.7 Lifting pipe setting of indoor unit with water pump
¾ The length of lifting pipe should not exceed the pump head of indoor unit water pump.
Pump head of big four way cassette: 750mm
Pump head of compact four way cassette: 500mm
¾ The drainage pipe should be set down inclined after the lifting pipe immediately to avoid wrong
operation of water level switch.
¾ Refer the following picture for installation reference.
47
Drainage pipe installation
Hanger
A
Down incline pipe
A:Length of horizontal pipe İ150mm
B: Lift heightİthe pump head of water pump
B
Flexible pipe 300mm
6.2.8 Blowhole setting
¾ For the concentrated drainage pipe system, there should design a blowhole at the highest point of main
pipe to ensure the condensate water discharge smoothly.
¾ The air outlet shall face down to prevent dirt entering pipe.
¾ Each indoor unit of the system should be installed it.
¾ The installation should be considering the convenience for future cleaning.
Blowhole
Indoor unit
Plug
Indoor unit
Plug
6.2.9 The end of drainage pipe shall not contact with ground directly.
6.3 Drainage test
6.3.1 Water leakage test
After finishing the construction of drainage pipe system, fill the pipe with water and keep it for 24 hours to
check whether there is leakage at joint section.
6.3.2 Water discharge test
1. Natural drainage mode(the indoor unit with outdoor drainage pump)
Infuse above 600ml water through water test hole slowly into the water collector, observe whether the
water can discharge through the transparent hard pipe at drainage outlet.
2. Pump drainage mode
2.1 Disconnect the plug of water level switch, remove the cover of water test hole and slowly infuse about
2000ml water through the water test hole, be sure that the water will not touch the motor of drainage
pump.
48
Insulation Work
2.2 Power on and let the air conditioner operate for cooling. Check operation status of drainage pump, and
then connect the plug of water level switch, check the operation sound of water pump and observe
whether the water can discharge through the transparent hard pipe at drainage outlet. (In light of the
length of drainage pipe, water shall be discharged about 1 minute delayed)
2.3 Stop the operation of air conditioner, power off the power supply and put the cover of water test hole
back to the original place.
a. After stopped the air conditioner 3 minutes, check whether there is anything abnormal. If drainage pipes
have not been distributed properly, over back-flow water shall cause the flashing of alarm indicator at
remote-controlled receiving board and even water shall run over the water collector.
b. Continuously infusing water until water level alarmed, check whether the drainage pump could
discharge water at once. If water level does not decline under warning water level 3 minutes later, it
shall cause shutdown of unit. When this situation happens, the normal startup only can be recovered by
turning down power supply and eliminating accumulated water.
Note: Drain plug at the main water-containing plate is used for eliminating accumulated water in
water-containing plate when maintaining air conditioner fault. During normal operation, the plug shall be
filled in to prevent leakage.
6.4 Insulation work of drainage pipe
Refer the introduction to the insulation engineering parts.
7. Vacuum Drying and Leakage Checking
7.1 Purpose of vacuum drying
¾
¾
Eliminating moisture in system to prevent the phenomena of ice-blockage and copper oxidation.
Ice-blockage shall cause abnormal operation of system, while copper oxide shall damage compressor.
Eliminating the non-condensable gas (air) in system to prevent the components oxidizing, pressure
fluctuation and bad heat exchange during the operation of system.
7.2 Selection of vacuum pump
¾
¾
The ultimate vacuum degree of vacuum pump shall be -756mmHg or above.
Precision of vacuum pump shall reach 0.02mmHg or above.
7.3 Operation procedure for vacuum drying
Due to different construction environment, two kinds of vacuum drying ways could be chosen, namely
ordinary vacuum drying and special vacuum drying.
7.3.1 Ordinary vacuum drying
49
Additional refrigerant charge
1.
2
3
4
When conduct first vacuum drying, connect pressure gauge to the infusing mouth of gas pipe and liquid
pipe, and keep vacuum pump running for 1hour (vacuum degree of vacuum pump shall be reached
-755mmHg).
If the vacuum degree of vacuum pump could not reach -755mmHg after 1 hour of drying, it indicates
that there is moisture or leakage in pipeline system and need to go on with drying for half an hour.
If the vacuum degree of vacuum pump still could not reach -755mmHg after 1.5 hours of drying, check
whether there is leakage source.
Leakage test: After the vacuum degree reaches -755mmHg, stop vacuum drying and keep the pressure
for 1 hour. If the indicator of vacuum gauge does not go up, it is qualified. If going up, it indicates that
there is moisture or leak source.
7.3.2 Special vacuum drying
The special vacuum drying method shall be adopted when:
1.
Finding moisture during flushing refrigerant pipe.
2.
Conducting construction on rainy day, because rain water might penetrated into pipeline.
3.
Construction period is long, and rain water might penetrated into pipeline.
4.
Rain water might penetrate into pipeline during construction.
Procedures of special vacuum drying are as follows:
1.
Vacuum drying for 1 hour.
2.
Vacuum damage, filling nitrogen to reach 0.5Kgf/cm2 .
Because nitrogen is dry gas, vacuum damage could achieve the effect of vacuum drying, but this
method could not achieve drying thoroughly when there is too much moisture. Therefore, special
attention shall be drawn to prevent the entering of water and the formation of condensate water.
3.
Vacuum drying again for half an hour.
If the pressure reached -755mmHg, start to pressure leakage test. If it cannot reached the value,
repeat vacuum damage and vacuum drying again for 1 hour.
4
Leakage test: After the vacuum degree reaches -755mmHg, stop vacuum drying and keep the pressure
for 1 hour. If the indicator of vacuum gauge does not go up, it is qualified. If going up, it indicates that
there is moisture or leak source.
8. Additional refrigerant charge
¾
¾
After the vacuum drying process is carried out, the additional refrigerant charge process need to be
performed.
The outdoor unit is factory charged with refrigerant. The additional refrigerant charge volume is decided
by the diameter and length of the liquid pipe between indoor and outdoor unit. Refer the following
formula to calculate the charge volume.
ĭ6.35
ĭ9.52
ĭ12.7
V=11g/m×(L-5)
V=30g/m×(L-5)
V=60g/m×(L-5)
Diameter of liquid pipe (mm)
Formula
V: Additional refrigerant charge volume (g).
L : The length of the liquid pipe (m).
Note:
¾ Refrigerant may only be charged after performed the vacuum drying process.
¾ Always use gloves and glasses to protect your hands and eyes during the charge work.
¾ Use electronic scale or fluid infusion apparatus to weight refrigerant to be recharged. Be sure to avoid
extra refrigerant charged, it may cause liquid hammer of the compressor or protections.
¾ Use supplementing flexible pipe to connect refrigerant cylinder, pressure gauge and outdoor unit. And
The refrigerant should be charged in liquid state. Before recharging, The air in the flexible pipe and
manifold gauge should be exhausted.
¾ After finished refrigerant recharge process, check whether there is refrigerant leakage at the connection
joint part.(Using gas leakage detector or soap water to detect).
50
Insulation Work
9. Engineering of insulation
9.1 Insulation of refrigerant pipe
9.1.1 Operational procedure of refrigerant pipe insulation
Cut the suitable pipe ĺ insulation (except joint section) ĺ flare the pipe ĺ piping layout and connectionĺ
vacuum drying ĺ insulate the joint parts
9.1.2 Purpose of refrigerant pipe insulation
¾ During operation, temperature of gas pipe and liquid pipe shall be over-heating or over-cooling
extremely. Therefore, it is necessary to carry out insulation; otherwise it shall debase the performance
of unit and burn compressor.
¾ Gas pipe temperature is very low during cooling. If insulation is not enough, it shall form dew and cause
leakage.
¾ Temperature of gas pipe is very high (generally 50-100ć) during heating. Insulation work must be
carried out to prevent hurt by carelessness touching.
9.1.3 Insulation material selection for refrigerant pipe
¾ The burning performance should over 120ć
¾ According to the local law to choose insulation materials
¾ The thickness of insulation layer shall be above 10mm.If in hot or wet environment place, the layer of
insulation should be thicker accordingly.
9.1.4 Installation highlights of insulation construction
¾ Gas pipe and liquid pipe shall be insulated separately, if the gas pipe and liquid pipe were insulated
together; it will decrease the performance of air conditioner.
Liquid pipe
¾
¾
¾
¾
¾
Insulation meterial
Gas pipe
The insulation material at the joint pipe shall be 5~10cm longer than the gap of the insulation material.
The insulation material at the joint pipe shall be inserted into the gap of the insulation material.
The insulation material at the joint pipe shall be banded to the gap pipe and liquid pipe tightly.
The linking part should be use glue to paste together
Be sure not bind the insulation material over-tight, it may extrude out the air in the material to cause bad
insulation and cause easy aging of the material.
9.2 Insulation of drainage pipe
9.2.1 Operational procedure of refrigerant pipe insulation
Select the suitable pipe ĺ insulation (except joint section) ĺ piping layout and connectionĺ drainage testĺ
insulate the joint parts
9.2.2 Purpose of drainage pipe insulation
The temperature of condensate drainage water is very low. If insulation is not enough, it shall form dew and
cause leakage to damage the house decoration.
51
Engineering of electrical wiring
9.2.3 Insulation material selection for drainage pipe
¾ The insulation material should be flame retardant material, the flame retardancy of the material should
be selected according to the local law.
¾ Thickness of insulation layer is usually above 10mm.
¾ Use specific glue to paste the seam of insulation material, and then bind with adhesive tape. The width
of tape shall not be less than 5cm. Make sure it is firm and avoid dew.
9.2.4 Installation and highlights of insulation construction
¾ The single pipe should be insulated before connecting to another pipe, the joint part should be insulated
after the drainage test.
¾ There should be no insulation gap between the insulation material.
10. Engineering of electrical wiring
10.1 Highlights of electrical wiring installation
¾
¾
¾
¾
¾
¾
¾
¾
¾
¾
¾
All field wiring construction should be finished by qualified electrician.
Air conditioning equipment should be grounded according to the local electrical regulations.
Current leakage protection switch should be installed.
Do not connect the power wire to the terminal of signal wire.
When power wire is parallel with signal wire, put wires to their own wire tube and remain at least 300mm
gap.
According to table in indoor part named “the specification of the power” to choose the wiring, make sure
the selected wiring not small than the date showing in the table.
Select different colors for different wire according to relevant regulations.
Do not use metal wire tube at the place with acid or alkali corrosion, adopt plastic wire tube to replace it.
There must be not wire connect joint in the wire tube If joint is a must, set a connection box at the place.
The wiring with different voltage should not be in one wire tube.
Ensure that the color of the wires of outdoor and the terminal No. are same as those of indoor unit
respectively.
11. Test operation
11.1 The test operation must be carried out after the entire installation has been
completed.
11.2 Please confirm the following points before the test operation.
¾
¾
¾
¾
¾
¾
¾
¾
¾
¾
The indoor unit and outdoor unit are installed properly.
Tubing and wiring are correctly completed.
The refrigerant pipe system is leakage-checked.
The drainage is unimpeded.
The ground wiring is connected correctly.
The length of the tubing and the added stow capacity of the refrigerant have been recorded.
The power voltage fits the rated voltage of the air conditioner.
There is no obstacle at the outlet and inlet of the outdoor and indoor units.
The gas-side and liquid-side stop values are both opened.
The air conditioner is pre-heated by turning on the power.
11.3 Test operation
Set the air conditioner under the mode of "COOLING" by remote controller, and check the following points.
Indoor unit
¾ Whether the switch on the remote controller works well.
¾ Whether the buttons on the remote controller works well.
¾ Whether the air flow louver moves normally.
¾ Whether the room temperature is adjusted well.
52
¾
¾
¾
¾
Insulation Work
Whether the indicator lights normally.
Whether the temporary buttons works well.
Whether the drainage is normal.
Whether there is vibration or abnormal noise during operation.
Outdoor unit
¾ Whether there is vibration or abnormal noise during operation.
¾ Whether the generated wind, noise, or condensed of by the air conditioner have influenced your
neighborhood.
¾ Whether any of the refrigerant is leaked.
53
Electrical Control
Electrical Control System
1. Electrical Control Function ...................................................................55
2. Troubleshooting ....................................................................................64
3. Controller ............................................................................................. 79
54
Electrical Control Function
1. Electrical Control Function
1.1 Definition
T1: Indoor room temperature
T2:
Coil temperature of evaporator
T3:
Coil temperature of condenser
T4:
Outdoor ambient temperature
T5:
Compressor discharge temperature
1.2 Main Protection
1.2.1 Time delay at restart for compressor.
1.2.2 Sensor protection at open circuit and breaking disconnection.
1.2.3 Phase check function
If the phase sequence is detected wrong or lack of 1 or 2 phase, the unit won’t start and there is error code
displayed on outdoor PCB.
1.2.4 Over-current protection
When compressor is running, if the current is over twice of the rated for 3 seconds, the compressor will stop
and an error code will be displayed on the outdoor PCB. If the current becomes normal, the indoor sends
signal to the outdoor, the outdoor will display normally.
1.2.5 Fan Speed is out of control
When Indoor fan speed keeps too low (less than 300RPM) for 50s, the unit will stop and the LED will display
the failure.
55
Electrical Control Function
1.3 Operation Modes and Functions
1.3.1 Fan mode
(1) Outdoor fan and compressor stop.
(2) Temperature setting function is disabled, and no setting temperature is displayed.
(3) Indoor fan can be set to high/(med)/low/auto.
(4) The louver operates same as in cooling mode.
(5) Auto fan:
T1
27
High
26
Medium
24
Low
1.3.2 Cooling Mode
1.3.2.1 Compressor running rules
Once the compressor starts up, it will follow the below rules:
When indoor room temp.T1 is lower than Ts, the compressor and outdoor fan will shut off. When T1 is higher
than Ts+1, the compressor and outdoor fan will start up.
T1
Ts+1
On
Ts
Off
1.3.2.2 Outdoor fan running rules
For double-fan outdoor units:
Fan(above): The outdoor fan runs all the time.
Fan(below):
T3
33
On
30
Off
56
Electrical Control Function
1.3.2.3 Indoor fan running rules
In cooling mode, indoor fan runs all the time and the speed can be selected as high, medium, low and auto.
The auto fan:
T1-Ts
4
High
3
Medium
1
Low
1.3.2.4 Low evaporator coil temperature T2 protection
For Duct:
T2
On
TE6
TE5
Off
When the evaporator coil temp.T2 keeps lower than TE5 for Time0, the compressor and outdoor fan will shut
off. When T2 is higher than TE6, the compressor and outdoor fan will restart up.
For Ceiling & Floor, super-slim cassette type:
AC will enter T2 protection if any of the following conditions is satisfied.
Condition 1:
T2
On
TE6
TE5
Off
When the evaporator coil temp.T2 keeps lower than TE5 for 30 minutes, the compressor and outdoor fan will
shut off. When T2 is higher than TE6, the compressor and outdoor fan will restart up.
57
Electrical Control Function
Condition 2:
T2
On
TE6
TE5-2
Off
When the evaporator coil temp.T2 keeps lower than TE5-2 for 20 minutes, the compressor and outdoor fan
will shut off. When T2 is higher than TE6, the compressor and outdoor fan will restart up.
Condition 3:
T2
On
TE6
TE5-4
Off
When the evaporator coil temp.T2 keeps lower than TE5-4 for 8 minutes, the compressor and outdoor fan
will shut off. When T2 is higher than TE6, the compressor and outdoor fan will restart up.
1.3.2.5 Condenser high temperature T3 protection
For Duct & super-slim cassette type:
T3
Off
TE12
TE13
On
When T3•TE12 for Time1, the compressor will shut off. When T3ψTE13,the compressor will restart.
58
Electrical Control Function
For Ceiling & Floor:
T3
Off
TE10
TE11
On
When T3•TE10, the compressor will shut off. When T3ψTE11,the compressor will restart.
1.3.3 Heating Mode
1.3.3.1 Compressor running rules:
For Duct & super-slim cassette type: Once the compressor starts up, it keeps running 7 minutes,
For Ceiling & Floor: Once the compressor starts up, it keeps running HEATFTIM minutes,
then it will follow the below rules:
When indoor room temp.T1 is higher than Tgap0, the compressor and outdoor fan will shut off. When T1 is
lower than Tgap0-1, the compressor and outdoor fan will start up.
T1-TS
Off
Tgap0
Tgap0-1
On
For Ceiling & Floor:Tgap0 = setting temperature-compensation.
1.3.3.2 Outdoor fan running rules:
Fan(below): The outdoor fan runs all the time.
Fan(above):
T4
18
Off
16
On
1.3.3.3 Indoor fan running rules:
When the compressor is on, the indoor fan can be set to high/med/low/auto. And the anti-cold wind function
has the priority.
59
Electrical Control Function
Auto fan action:
For Duct & super-slim cassette type:
For Ceiling & Floor: setting temperature-compensation.=4qC
T1-Ts
Low
3
2
1
Medium
High
For Ceiling & Floor: setting temperature-compensation.=1qC
T1-Ts
Low
0
Medium
-1
-2
High
1.3.3.4 Defrosting modeφ
z
Condition of defrosting:
AC will enter defrosting mode if any of the following items is satisfied.
A: T3< TE19 and the compressor keeps running over 45 minutes. Meanwhile T3ψTE17 for 3minutes.
B: After the last defrosting, the time that the outdoor fan is off but the compressor is on in high T2 protection
cumulates up to 90 minutes.
z
Condition of ending defrosting:
If any one of the following items is satisfied, the defrosting will terminate and the machine will turn to normal
heating mode.
A: T3 rises to be higher than TE18.
B: The machine has run for 10 minutes in defrosting.
C: Turn to other modes or off.
z
Defrosting actionφ
60
Electrical Control Function
Setting defrosting time
45S
45S
Compressor
4 way valve
40S
40S
Outdoor fan
Indoor fan
10S
1.3.3.5 High evaporator coil temp.T2 protection:
For Duct and Super-slim Cassette:
Compressor off Outdoor fan off
TE9
Compressor on
Outdoor fan off
TE8
TE10
Compressor on Outdoor fan on
TE11
For Ceiling & Floor:
TE7
TE8
Compressor off
Outdoor fan off
Compressor and
Outdoor fan on
Compressor and
Outdoor fan off
TE9
Compressor and
Outdoor fan on
1.3.4 Auto-mode
This mode can be chosen with remote controller and the setting temperature can be changed between
17~30đ.
In auto mode, the machine will choose cooling, heating or fan-only mode according to ǻT (ǻT =T1-Ts).
61
Electrical Control Function
For Duct and Super-slim Cassette:
ǻT=T1-Ts
Running mode
ǻTϊ2đ
Cooling
-1”ǻT”2đ
Fan-only
ǻT<-1đ
Heating
ǻT=T1-Ts
Running mode
ǻTϊ2đ
Cooling
-1<ǻT”2đ
Fan-only
ǻT”-1đ
Heating
For Ceiling & Floor:
Indoor fan will run at auto fan of the relevant mode.
The louver operates same as in relevant mode.
If the machine switches mode between heating and cooling, the compressor will keep stopping for 15
minutes and then choose mode according to T1-Ts.
If the setting temperature is modified, the machine will choose running function again.
1.3.5 Drying mode
1.3.5.1 The indoor fan will keep running at low speed.
1.3.5.2 All protections are active and the same as that in cooling mode.
1.3.5.3 The louver operates the same as in cooling mode.
1.3.6 Timer function
1.3.6.1 Timing range is 24 hours.
1.3.6.2 Timer on. The machine will turn on automatically when reaching the setting time.
1.3.6.3 Timer off. The machine will turn off automatically when reaching the setting time.
1.3.6.4 Timer on/off. The machine will turn on automatically when reaching the setting “on” time, and then
turn off automatically when reaching the setting “off” time.
1.3.6.5 Timer off/on. The machine will turn off automatically when reaching the setting “off” time, and then
turn on automatically when reaching the setting “on” time.
1.3.6.6 The timer function will not change the AC current operation mode. Suppose AC is off now, it will not
start up firstly after setting the “timer off” function. And when reaching the setting time, the timer LED will be
off and the AC running mode has not been changed.
1.3.6.7 The setting time is relative time.
1.3.7 Economy function
1.3.7.1 It is valid in cooling, heating and auto mode.
1.3.7.2. Turning off, changing mode or setting fan speed will cancel economy function.
1.3.7.3 Operation process in sleep mode is as follow:
62
Electrical Control Function
After pressing ECONOMIC or SLEEP button on the controller, the machine will go into economy mode.
When cooling, the setting temperature rises 1đ(be lower than 30đ) every hour, 2 hours later the setting
temperature stops rising.
For heat pump models, when they are in heating, the setting temperature reduces 1đ(be higher than 17đ)
every hour, 2 hours later the setting temperature stops reducing.
1.3.7.4 In this mode, the fan speed is forced into AUTO mode.
1.3.8 Auto-Restart function
The indoor unit is equipped with auto-restart function, which is carried out through an auto-restart module. In
case of a sudden power failure, the module memorizes the setting conditions before the power failure. The
unit will resume the previous operation setting (not including Swing function) automatically after 3 minutes
when power returns.
1.3.9 Drain pump control(For duct & cassete)
1.3.9.1 Water level check
The water lever will be checked every 5 seconds, if the feedback signal is abnormal, it will be considered as
drain water full by the control system.
1.3.9.2 Drain pump control
If there is no water full error, the drain pump will be on when the unit is in cooling mode (including
auto-cooling and forced cooling) and dry mode. It will be off when the unit is in heating mode, fan only mode
or off state (if the pump is on before the unit is off, it will delay 3 minutes to be off).
If there is a water full error, the drain pump will be on when the error occurs. Afterwards:
If the error disappears in 3 minutes, the drain pump will work as normal state. (if it is necessary to turn off the
pump, it will be off in 1 minute delay.)
If the error is still there in 3 minutes, the drain pump will be off as well as the AC unit. The error can be
cleared only when the power of the unit is cut off.
63
Troubleshooting
2. Troubleshooting
2.1 Display board
2.1.2 Icon explanation on indoor display board (Super-slim 4-way cassette).
2.1.4 Display board of G[ZUROLZOTMVGTKRUL]G_IGYYKZZK
2.1.5 Icon explanation on indoor display board(Ceiling & Floor)
64
Troubleshooting
2.2. Self-diagnosis
Indoor unit’s LED indication
For Super-slim 4-way Cassette
NO.
Malfunction
Running
lamp
Timer
lamp
Defrosting
lamp
Alarm
lamp
Display(digital
tube)
1
Communication malfunction between indoor
and outdoor units
ƿ
X
ƿ
X
E1
2
Open or short circuit of T1 temperature
sensor
X
ƿ
X
X
E2
3
Open or short circuit of T2 temperature
sensor
ƿ
X
X
X
E3
4
Open or short circuit of T3 temperature
sensor
X
X
ƿ
X
E4
5
Outdoor unit malfunction
ƿ
ƿ
ƿ
ƿ
E6
6
Indoor EEPROM malfunction
ƿ
ƿ
X
X
E7
7
Full-water malfunction
X
X
X
ƿ
E8
8
Indoor fan speed is out of control
X
ƿ
X
ƿ
Eb
9
Protection of low pressure
ƿ
ƿ
ƿ
X
Ed
10
Communication malfunction between main
PCB and up-down panel PCB
ƿ
X
ƿ
ƿ
F0
11
Up-down panel malfunction
X
ƿ
ƿ
ƿ
F1
12
Up-down panel is not closed
X
O
ƿ
ƿ
F2
O (on)
X(off)
ƿ(flash at 5Hz)
65
Troubleshooting
For Ceiling & Floor
NO.
Malfunction
Running
lamp
Timer
lamp
Defrosting
lamp
Alarm
lamp
1
Communication malfunction between indoor and outdoor
units
ƿ
X
ƿ
X
2
Open or short circuit of T1 temperature sensor
X
ƿ
X
X
3
Open or short circuit of T2 temperature sensor
ƿ
X
X
X
4
Open or short circuit of T3 temperature sensor
X
X
ƿ
X
5
Outdoor unit malfunction
ƿ
ƿ
ƿ
ƿ
6
Indoor EEPROM malfunction
ƿ
ƿ
X
X
7
Full-water malfunction
X
X
X
ƿ
8
Indoor fan speed is out of control
X
ƿ
X
ƿ
9
Protection of low pressure
ƿ
ƿ
ƿ
X
LEDs’ for the indication of outdoor trouble
Type
Contents
LED2(Green)
LED3(Yellow)
LED4(Red)
Normal
Normal running
O
X
X
Normal
Normal standby
X
O
X
Trouble
Phase sequence error
X
ƿ
X
Trouble
Lack of phase
X
X
ƿ
Trouble
Open-circuit and short-circuit trouble of T3
Trouble
Trouble
Open-circuit and short-circuit trouble of T4
Temperature protection of compressor
discharge
Protection of high pressure
Trouble
Protection of low pressure
Trouble
X
X
O
ƿ
X
X
O
X
O
ƿ
ƿ
X
ƿ
X
ƿ
Trouble
Overload of current
X
ƿ
O
Trouble
High temperature protection of condenser
ƿ
ƿ
O
Trouble
Fan selection error
ƿ
ƿ
ƿ
O(light)
X(off)
ƿ(flash at 1Hz)
Note:
1. T3: Outdoor condenser temperature sensor
2. T4: Outdoor ambient temperature sensor
66
Troubleshooting
2.3. Solving steps for typical malfunction
(1) For indoor unit
a. Communication malfunction between indoor and outdoor units(E1)
Power off, then turn on the unit 5
seconds later(reconnect the
power wire).Is the error still
displaying after several minutes?
Yes
Check if there’s any interference.
Such as too many lamps, power
transformers? Or the signal wire is
too long?
Yes
Remove interference.
Increase the capacity of antiinterference
No
Adopt shield cable/Shield
cable earthing.
No
Correct the connection.
Yes
Replace the signal wire.
No
Pull out and insert back.
No
Check whether the signal wire is
shield cable or whether the shield
cable is earthing?
Yes
Check whether the wire is correct
polarity? P to P, Q to Q, E to E?
Yes
Check whether the signal wire is
broken?
No
Check whether the signal wires
insert on PCB well?
Yes
Replace indoor PCB, is the error
distinguished?
No
Replace the outdoor PCB.
67
Troubleshooting
b. Open or short circuit of temperature sensorδE2θE3, E4ε
Check the connections
between temperature
sensor and PCB. Are
the connections good?
No
Correct the connections.
Yes
Check the resistance value
of the sensor via Appendix 1
Is it normal?
Yes
Replace indoor or outdoor PCB.
No
Replace the sensor
68
Troubleshooting
c. Outdoor unit malfunction(E6)
Outdoor unit malfunction
Whether the outdoor
main board has error
display
Yes
Refer to corresponding solving steps
No
Check whether the power is on
No
Connect the wiring well or
replace the communication wire
No
Whether the outdoor
unit is power on
Yes
Check whether the
communication wire
between the indoor and
outdoor unit is
connected correctly
Yes
Replace outdoor main
board
check if the errors
happen again?
No
Yes
Replace the indoor PCB
Trouble is solved
69
Troubleshooting
d. Indoor EEPROM malfunction(E7)
Shut off the power supply and
turn it on 5 seconds later. Is it
still displaying the error code?
Yes
If the EEPROM chip
is welded on PCB,
replace the PCB
directly. Otherwise,
check whether the
EEPROM chip
plugged in PCB well?
No
Insert the EEPROM well
Yes
Replace the indoor PCB.
e. Full-water malfunction(E8)
If the water-level switch
is inserted well?
No
Insert the water-level switch well
Yes
Replace the water-level switch
Yes
If the water-level switch
is broken?
No
If the water pump is
normal?
No
Replace the water pump
Yes
Check PCB board or replace the indoor main PCB
70
Troubleshooting
f. Indoor fan speed has been out of control(Eb)
71
Troubleshooting
Index 1:
1.Indoor DC fan motor(control chip is inside fan motor)
Measure the resistance value of each winding by using the tester. If any resistance value is zero, the fan
motor must have problems and need to be replaced.
NO.
1
2
3
4
5
6
Color
Red
--Black
White
Yellow
Blue
Index2:
1. DC fan motor(control chip is inside fan motor)
Power on and when the unit is in standby, measure the voltage of pin1-pin3, pin4-pin3 in fan motor
connector. If the value of the voltage is not in the range showing in below table, the PCB must have
problems and need to be replaced.
DC motor voltage input and output
Signal
Voltage
Red
Vs/Vm
140~380V
---
---
---
NO.
Color
1
2
3
Black
GND
0V
4
White
Vcc
13.5~16.5V
5
Yellow
Vsp
0~6.5V
6
Blue
FG
15V
72
Troubleshooting
For the super-slim cassette with up-down panel
a. Communication error between indoor unit and up-down panel
b. Up-down panel is defective
73
Troubleshooting
c Up-down panel is not closed
74
Troubleshooting
(2) For the outdoor unit
a. Phase sequence error:
Phase sequence error
Change the order of two of the wires to power supply.
Switch on the unit again.
If the problem cannot be solved, the outdoor PCB is defective
b. Lack of phase
Lack of phase
Check the power supply, is it 3 phase,
380-415V?
Yes
Check the connection between power supply and terminal,
is the voltage in outdoor terminal is 3 phase, 380-415V?
Yes
Outdoor PCB is defective
75
Troubleshooting
c. Overload of current
Overload of current
Check the current, normally
Is the current in rated range?
No
Yes
The outdoor PCB is defective
Possible reason
1. Outdoor fan is defective
2. The compressor is defective
3. Refrigerant is over charged
4. Air enter the refrigerant system
d. Protection of pressure or temp.
Protection of pressure or temp.
Yes
Is it K1 or K2 open ?
Is temp. protective switch K1 close
Yes
Possible reason
1. The wires is loose to K1
2. Air or other gas in the refrigerant.
3. Heat exchanger is dirty
4. Outdoor fan or fan blade is
defective
5. Outdoor unit is in bad ventilation
6. Refrigerant is leakage
Is pressure protective switch K2 close
Yes
Possible reason
1. The wires is loose to K2
2. Air or other gas in the refrigerant.
3. Heat exchanger is dirty
4. Outdoor motor or fan blade is
defective
5. Outdoor unit is in bad ventilation
6. Refrigerant is too much
76
Troubleshooting
e. High temperature protection of condenser
High temperature protection of condenser
Check the resistance of the temp. sensor
according to Appendix 1, is it normal?
Yes
Possible reason
1. Air or other gas in the refrigerant.
2. Heat exchanger is dirty
3. Outdoor fan or fan blade is
defective
4. Outdoor unit is bad ventilation
5. Refrigerant is leakage
No
Replace the sensor
77
Troubleshooting
Appendix 1 Temperature Sensor Resistance Value Table
ć
20
K Ohm
12.6431
ć
60
K Ohm
2.35774
ć
100
K Ohm
0.62973
-19
115.266
108.146
21
12.0561
61
2.27249
101
0.61148
-18
101.517
22
11.5000
62
2.19073
102
0.59386
-17
96.3423
23
10.9731
63
2.11241
103
0.57683
-16
89.5865
24
10.4736
64
2.03732
104
0.56038
ć
-20
K Ohm
(ć--K)
-15
84.2190
25
10.000
65
1.96532
105
0.54448
-14
79.3110
26
9.55074
66
1.89627
106
0.52912
-13
74.5360
27
9.12445
67
1.83003
107
0.51426
-12
70.1698
28
8.71983
68
1.76647
108
0.49989
-11
66.0898
29
8.33566
69
1.70547
109
0.48600
-10
62.2756
30
7.97078
70
1.64691
110
0.47256
-9
58.7079
31
7.62411
71
1.59068
111
0.45957
-8
56.3694
32
7.29464
72
1.53668
112
0.44699
-7
52.2438
33
6.98142
73
1.48481
113
0.43482
-6
49.3161
34
6.68355
74
1.43498
114
0.42304
-5
46.5725
35
6.40021
75
1.38703
115
0.41164
-4
44.0000
36
6.13059
76
1.34105
116
0.40060
-3
41.5878
37
5.87359
77
1.29078
117
0.38991
-2
39.8239
38
5.62961
78
1.25423
118
0.37956
-1
37.1988
39
5.39689
79
1.21330
119
0.36954
0
35.2024
40
5.17519
80
1.17393
120
0.35982
1
33.3269
41
4.96392
81
1.13604
121
0.35042
2
31.5635
42
4.76253
82
1.09958
122
0.3413
3
29.9058
43
4.57050
83
1.06448
123
0.33246
4
28.3459
44
4.38736
84
1.03069
124
0.32390
5
26.8778
45
4.21263
85
0.99815
125
0.31559
6
25.4954
46
4.04589
86
0.96681
126
0.30754
7
24.1932
47
3.88673
87
0.93662
127
0.29974
8
22.5662
48
3.73476
88
0.90753
128
0.29216
9
21.8094
49
3.58962
89
0.87950
129
0.28482
10
20.7184
50
3.45097
90
0.85248
130
0.27770
11
19.6891
51
3.31847
91
0.82643
131
0.27078
12
18.7177
52
3.19183
92
0.80132
132
0.26408
13
17.8005
53
3.07075
93
0.77709
133
0.25757
14
16.9341
54
2.95896
94
0.75373
134
0.25125
15
16.1156
55
2.84421
95
0.73119
135
0.24512
16
15.3418
56
2.73823
96
0.70944
136
0.23916
17
14.6181
57
2.63682
97
0.68844
137
0.23338
18
13.9180
58
2.53973
98
0.66818
138
0.22776
19
13.2631
59
2.44677
99
0.64862
139
0.22231
78
Controller
3. Controller
3.1 Wireless Remote Controller
3.1.1 RG51Q1/BGE
The R51Q1/BGE wireless remote controller is standard for Four-way cassette type and the Ceiling& floor
type.
General Function for wireless remote controller:
Model
RG51Q1/BGE
Rated voltage
3.0V(2pieces of LR03 7ί batteries)
Min voltage for sending signal of CPU
2.4V
Effective receiving distance
8m~11m
Operation condition
-5~60ć
79
Controller
Buttons and functions
1. Adjust
: Decrease the set temp. Keeping pressing will decrease the temp with 1ć per 0.5s.
: Increase the set temp. Keeping pressing will increase the temp with 1ć per 0.5s.
2. Adjust
3. MODE: Once pressing, running mode will be selected in the following sequence:
AUTO
COOL
DRY
HEAT
FAN
NOTE: No heating mode for cool only type unit.
4. VERT SWING: Used to stop or start horizontal louver movement or set the desired up/down air flow
direction. The louver changes 6 degree in angle for each press. If keep pushing more than 2 seconds, the
louver will swing up and down automatically.
5. HORIZ SWING: Used to stop or start vertical louver movement.
6. AIR DIRECTION: Used to set the desired up/down air flow direction. The louver changes 6 degree in
angle for each press.
7. ON/OFF: For turning on or turning off the air conditioner.
8. FAN SPEED: Fan speed will be selected in following sequence once pressing this button:
AUTO
LOW
MED
HIGH
9. TIME ON: For time ON setting. Once pressing this button, the time will increase by 0.5 hour. When the set
time exceeds 10 hours, pressing the button will increase the time by 1 hour. Adjusting the figure to 0.00 will
cancel time ON setting.
10. ECO: Activate or turn off economic operation mode. It is suggested to turn on this function when sleeping.
(Only available when remote controller is used with corresponding unit.)
11. TIME OFF: For time OFF setting. Once pressing this button, the time will increase by 0.5 hour. When the
set time exceeds 10 hours, pressing the button will increase the time by 1 hour.
Adjust the figure to 0.00 will cancel time ON setting.
12. C/H (inner located): Press this button with a needle of 1mm to shift the mode between Cooling only and
Cooling & Heating according to the feature of the machine.
13.RESET (inner located): Press this button with a needle of 1mm to cancel the current setting and reset
remote controller.
80
Controller
3.1.2 RG51C/E
Remote Controller Specifications
Model
RG51C/E
Rated Voltage
3.0V
Lowest Voltage of CPU Emitting Signal
2.0V
Reaching Distance
8m (when using 3.0 voltage, it can get 11m)
Environment Temperature Range
-5ćЊ60ć
Introduction of Function Buttons on the Remote Controller
SET TEM PERATURE( C)
FAN
HIGH
MED
LOW
AU TO
COOL
DR Y
HE AT
ADJUST
Adju st
1
2
7
3
SWING
SWING
4
ECO
RESET LOC K
8
Fan speed se tt ing
9
TI MER ON
10
Econom ci ope rat oi n
11
TIME R OFF
12
L ock
13
Re s et
TIMER ON
TI MER OFF
5
AI R
DIRECTI ON
1. Adjust
ON/ OFF
ON/O FF FAN SPEED
MODE
Mod e sett in g
Adj ust
: Decrease the set temp. Keeping pressing will decrease the temp with 1ć per 0.5s.
2. Adjust
: Increase the set temp. Keeping pressing will increase the temp with 1ć per 0.5s.
3. MODE: Once pressing, running mode will be selected in the following sequence:
AUTO
COOL
DRY
HEAT
FAN
NOTE: No heating mode for cool only type unit.
4. VERT SWING: Used to stop or start horizontal louver movement. The louver will swing up and down
automatically if push this button.
AIR DIRECTION: Used to set the desired up/down air flow direction. The louver changes 6 degree in
angle for each press.
5. HORIZ SWING: Used to stop or start vertical louver movement.
6. FAN SPEED+ MODE: Press the Mode and Fan speed button simultaneously for 2 seconds. The remote
81
Controller
controls into faceplate setting state and the LCD shows F2.Press the TEMPUP( ) to control the faceplate
up and press the TEMP DOWN( ) to control the faceplate down. Press any button to exit the faceplate
setting state, then the LCD back to the normal display.
7. ON/OFF: For turning on or turning off the air conditioner.
8. FAN SPEED: Fan speed will be selected in following sequence once pressing this button:
AUTO
LOW
MED
HIGH
9. TIME ON: For time ON setting. Once pressing this button, the time will increase by 0.5 hour. When the set
time exceeds 10 hours, pressing the button will increase the time by 1 hour. Adjusting the figure to 0.00 will
cancel time ON setting.
10. ECO: Select this function during the sleeping time. It can maintain the most comfortable temperature
and save energy. This function is available on COOL, HEAT or AUTO mode only .
NOTE: While the unit is running under Energy-saving mode, it would be cancelled if press MODE, FAN
SPEED or ON/OFF button.
11. TIME OFF: For time OFF setting. Once pressing this button, the time will increase by 0.5 hour. When the
set time exceeds 10 hours, pressing the button will increase the time by 1 hour.
Adjust the figure to 0.00 will cancel time ON setting.
12. LOCK (inner located): Push this button to lock in all the current settings, and the remote controller will
not accept any operation except that of the LOCK. Use the LOCK mode when you want to prevent settings
from being changed accidentally. Press the LOCK button again to cancel the LOCK function. A lock symbol
will appear on the remote controller display when the lock function is activated.
13.RESET (inner located): Once the recessed RESET button is pressed, all of the current settings will be
cancelled and the controller will return to the initial settings..
82
Controller
3.2 Wired Remote Controller (OPTIONAL)
KJR-10B
Name and functions of buttons on the wire controller
1
mode selection button:
It is used to select mode, push the button one time, then the operation modes will change
In turn as follows:
AUTO
COOL
DRY
HEAT
FAN
Remark: no heating mode if wire controller is set as the cool only.
2
Timer on button:
Push the button to set TIMER ON, each time you push the button the time moves forward by o.5 hours.
When the set time is over 10 hours, each time you push the button the time moves forward by 1 hour. If
want to cancel the TIMER ON, then adjust the time of TIMER ON as 0.0
3
Timer off button:
Push the button to set TIMER OFF, each time you push the button the time moves forward by o.5 hours.
When the set time is over 10 hours, each time you push the button the time moves forward by 1 hour. If
want to cancel the TIMER OFF, then adjust the time of TIMER OFF as 0.0
4
CLOCK button:
Normally display the clock set currently (display 12:00 for the first electrifying or resetting). When push
the button for 4 seconds, the hour part on the clock display flashes every 0.5 seconds, then push button
and to adjust hour; push the button CLOCK again, the minute part flashes every 0.5 seconds, then push
and button to adjust minute. When set clock or alter clock setting, must push the confirm button to
complete the setting
83
Controller
Name and function of LCD on the wire controller
1
Mode select button (MODE):
Press MODE button to select “COOL”, “DRY” , "HEAT", or "FAN ONLY" mode.(HEAT is invalid for
COOL ONLY wire controller.)
AUTO
2
COOL
DRY
HEAT
FAN
Fan speed button (FAN SPEED)
Press FAN SPEED to select fan speed from "AUTO", "LOW"," MED" , and "HIGH”. NOTE: some air
conditioners have no MED fan speed, and then the MED is regarded as HIGH.
3
Economical operation displays:
Press ECONOMICAL to display economical operation, if press ECONOMICAL again then the display
disappears
4
Lock display
Press LOCK to display the icon of LOCK. Press the button again then the icon of LOCK disappears. In
the mode of LOCK, all the buttons are invalid except for LOCK button.
5
CLOCK display.
Usually display the clock set currently. Press the button CLOCK for 4 seconds, the HOUR part will flash,
press button Ÿ and ź to adjust HOUR. Press the button CLOCK again, the minute part flash, press
buttonŸ orź to adjust MINUTE. After clock set or clock operation, it must press CONFIRM to complete
the set.
6
TIMER ON/OFF display:
Display ON at the state of TIMER ON adjustment or after only set the TIMER ON; Display OFF at the
state of TIMER OFF adjustment or after only set the TIMER OFF; Display ON/OFF if simultaneously set
the mode of TIMER ON and TIMER OFF.
7
Temperature display area:
Usually display the set temperature. Press the buttons of and to set temperature, at the mode of FAN,
there is no figure display in the area.
84
Controller
Remark:
The wired controller will reset to factory setting with auto mode, auto fan and 24đ setting temperature when
the air conditioner restarts after power failure.
And this may cause inconsistent displays on the wired controller and on the air conditioner. You need to
readjust the running status through the wired controller.
Installation
Installation Notice:
When the air conditioner needs the constant frequency wire Controller, be sure adding a Wire Joint with 5
terminal named A, B, C, D, E in indoor unit, and fixing a infrared emitter whose anode and cathode
connecting with A and B near the receiver in the Indoor Unit Switch Board, then connecting the terminal +5v,
GND, Run in the Switch Board to C,D,E respectively.
NOTE
Never turn screws too tightly, or else the cover would be dented or the Liquid Crystal breaks.
Please leave enough long cable for maintenance of the Wire Controller Board.
85
MODEL: ASC‐60AN intdoor
No
Description Part Code Actualization
Qty Price Code MODEL: ASC‐60AN intdoor
1
Panel assembly
201109990017
1
BG
1.1
Louver motor
202400100007
2
AM
1.2
Display box assembly
203342890005
1
AV
1.3
Panel assembly
P0000449603
1
AZ
1.3.1
Cover assembly of installation plate
P0000449698
4
AD
1.3.2
Air inlet grille assembly
1.3.2.1 Air filter
1.3.3
Transmission framework
1.3.3.1 Louver
P0000449689
1
AL
201109901903
1
AL
P0000449696
2
AF
P0000449731
2
AD
2
Cover
201142790001
1
AC
3
Foam tray assembly for condenser water
202242790002
1
BA
4
Evaporator fixing hanger
201242990039
2
AD
5
Evaporator assembly
201542990027
1
BS
5.1
Output pipe assembly
201642990041
1
AV
5.2
Copper nut
201600320004
1
AC
5.3
Input pipe assembly
201642990006
1
AT
Copper nut
201600320001
1
AC
5.3.1
6
Base foam assembly
202242990004
1
AU
7
Board assembly III
201242990035
1
AN
8
Board assembly I
201242990034
1
AM
9
Chassis assembly
201242590012
1
AX
10
Board assembly II
201242990037
1
AN
11
Board assembly Ⅳ
201242990036
1
AM
12
Evaporator fixing board
201242790011
1
AD
13
Pipe fixing board assembly
201142790002
1
AD
14
Asynchronous motor
202400300529
1
BF
15
Fan assembly
201100100846
1
AZ
16
Ventilation assembly
201142990003
1
AU
17
Electronic control box assembly
203342990019
1
BF
17.1
Electronic control box
201242590004
1
AG
17.2
Insulation plate
201142590002
1
AF
17.3
Main control board assembly
201342990007
1
BC
17.4
Wire joint
202301450125
1
AE
17.4
Wire joint
202301450116
1
AD
17.6
Ambient temperature sensor assembly
202440120100
1
AD
17.7
Reactance
202301000950
1
AR
18
Cover of electronic control box I
201242590023
1
AD
19
Remote controller
203355091508
1
AT
20
Pipe temperature sensor
202301300111
1
AD
21
Water level sensor assembly
202301310051
1
AM
22
Water Pump installation bracket assembly
201242990003
1
AF
23
Drain pump
202400600203
1
AZ
24
Pump rubber washer
202742000002
3
AC
25
Drain pipe
202856001093
1
AG
25
Drain pipe
202742590002
1
AG
26
Water pipe
201142500032
1
AD
The data are subject to change without notice.
Model: ASF-60AN indoor
No
Description Part Code Actualization
Qty Price Code 1
AK
MODEL: ASF‐60AN intdoor
1
1.1
Air inlet grille assembly II
201144790014
Air filter I
201144790023
1
AD
Air inlet grille assembly I
201144790015
2
AL
Air filter II
201144790024
1
AD
3
Top cover assembly
201244790048
1
AZ
4
Display installation box
201144790016
1
AP
5
Display board assembly
201344790040
1
AR
6
Evaporator assembly
201544790142
1
BS
6.1
Pipe temperature sensor assembly
202301300111
1
AD
6.2
Input pipe assembly
201644790189
1
AT
201600320001
1
AC
2
2.1
6.2.1 Copper nut
6.3
Output pipe assembly
201644790185
1
AV
6.4
Evaporator
201544790139
1
BQ
6.5
Copper nut
201600320004
1
AC
7
Water collector
202244790001
1
AY
7.1
Louver motor
202400200100
1
AH
8
Insulated axis
201132590888
2
AF
9
Volute shell (above)
201144690032
4
AK
10
Fan motor fixing board
201252490002
2
AD
11
Centrifugal fan
201144690083
4
AM
12
Fan motor axes clamp (right)
201280200006
2
AE
13
Fan motor axes clamp (left)
201280200005
2
AE
14
Asynchronous motor
202400300070
2
BE
15
Volute shell (below)
201144690033
4
AL
16
Right cover
201144790017
1
AN
17
Right hook
201244790033
2
AC
18
Supporter of louver
201144790018
2
AD
19
Louver
201144790006
1
AH
20
Louver motor
202400200162
1
AN
21
Left hook
201244790034
2
AC
22
Left cover
201144790019
1
AM
23
Remote controller
203355091492
1
AT
24
Cover of electronic control box
201244490048
1
AE
25
Electronic control box assembly
203344690026
1
BF
25.1 Electronic control box
201244790050
1
AK
25.2 Wire joint
202301450042
1
AD
25.2 Wire joint
202301450125
1
AE
25.3 Main control board assembly
201344690017
1
BD
25.5 Ambient temperature sensor assembly
202301310072
1
AD
25.7 Reactor
202301000950
1
AR
201244790047
1
AE
27
Pipe clamp board
28
Chassis assembly
201244690053
1
BD
29
Electronic control box assembly
203319900796
2
BC
29.1 Electronic control box
201270590340
1
AH
29.2 Inverter control board assembly
201319903060
1
BA
29.3 Radiator
202301900138
1
AQ
The data are subject to change without notice.
MODEL: ASC‐60AN, ASF‐60AN outdoor
No
Description Part Code MODEL: ASC‐60AN, ASF‐60AN outdoor
Actualization
Qty Price Code 1
Ambient temperature sensor assembly
202440220061
1
AD
2
Rear net
201175690001
1
AR
3
Condenser assembly
201575790151
1
CK
3.1
Condenser assembly
201575790152
1
BW
3.1
Condenser assembly
201575790153
1
BW
3.2
Input pipe assembly
201675890900
1
AV
3.3
Fluted pipe assembly
201675890890
1
AW
4
Pipe temperature sensor assembly
202450200331
1
AE
5
Big Handle assembly
201157390007
1
AF
6
Rear right clapboard assembly
201248700199
1
AZ
7
Handle
201148700009
2
AD
8
Water collector
201148790000
1
AE
9
Front clapboard assembly
201248700204
1
AZ
10
Valve plate
201248790014
1
AE
11
Chassis
201248700285
1
BA
12
Partition board assembly
201275690068
1
AW
13
Accumulator cylinder
201601000636
1
AY
14
Fix clamp of segregator
201248700067
1
AC
15
Left clapboard
201275690067
1
AL
16
Air outlet grille
201148100116
2
AP
17
Front panel
201248700201
1
AX
18
Axial flow fan
201100300045
2
AQ
19
Fan motor
202400401375
2
BB
20
Supporter assembly of fan motor
201248700197
1
AY
21
Support Board
201248300231
1
AD
22
Supporting
pp
g bar
201275690066
1
AF
23
Top cover assembly
201248300242
1
AT
24
Compressor C-SB453H8A
201400710560
1
CR
25
Discharge pipe assembly
201675890952
1
AW
25.1
Pressure switch
202301820020
1
AS
25.2
Muffler
201601000041
1
AK
BD
4-way valve assembly
201675790946
1
26.1
26
4-way valve
201600600166
1
BA
26.2
Gas valve
201600720425
1
AS
27
27.1
Liquid valve assembly
201675790987
1
AX
Liquid valve
201600740704
1
AR
28
Electronic control box assembly
2033757A0156
1
BE
28.1
Installation plate of electric parts
201248700194
1
AK
28.2
Main control board assembly
201348890013
1
AX
28.3
Wire joint
202301450003
1
AF
28.3
Wire joint
202301450121
1
AD
28.3
Wire joint
202301450117
3
AD
28.4
Fan motor capacitor
202401100505
2
AG
28.7
AC contactor
202300850045
1
AV
28.8
Transformer
202300900161
1
AK
29
Copper nut
201600320001
1
AC
30
Crankcase electric heater
202403101716
1
AR
31
Discharge temperature sensor assembly
202301610500
1
AH
32
Suction pipe assembly
201675790991
1
AU
Pressure switch
202301800118
1
AP
32.1
The data are subject to change without notice.