Wiring for Damper Actuators and Control Valves
Wiring for Damper Actuators and Control Valves July 2011 Wiring for Damper Actuators and Control Valves General Wiring Instructions Always read the controller manufacturer’s installation literature carefully before making any connections. Follow all CAUTION: It is good practice to power electronic or digital controllers from a separate power transformer than that used for actuators or other end devices. The power supply design in our actuators and other end devices use half wave rectification. Some controllers use full wave rectification. When these two different types of power supplies are connected to the same power transformer and the DC commons are connected together, a short circuit is created across one of the diodes in the full wave power supply, damaging the controller. Only use a single power transformer to power the controller and actuator if you know the controller power supply uses half wave rectification. instructions in this literature. If you have any questions, contact the controller manufacturer and/or Belimo. Multiple actuators, one transformer Transformer(s) Belimo actuators require a 24 VAC Class 2 transformer. The actuator enclosure cannot be opened in the field, there are no parts or components to be replaced or repaired. – EMC Directive: 2004/108/EC – Software Class A: Mode of Operation Type 1 – Low Voltage Directive: 2006/95/EC Example: 3 AF Actuators Supplied, 16 Ga. wire (refer to table on page 3) 350 ft. (allowable wire length) ÷ 3 actuators = 117 ft. maximum wire run Typical Transformer Sizing Actuator Series EFB, EFX AFB, AFX AF NFB, NFX LF TF GMB AMB / ARB NMB LMB / LRB CMB AHB LHB LUB AMQB NMQB LMQB AHQB LHQB GK / GKR NK AHK Voltage 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 800-543-9038 USA 2 Required VA Per Actuator 16 10 10 9 7 5 7 6 6 3 1.5 4.5 3 3 26 23 23 23 23 21 22 20 Multiple actuators may be powered from one transformer provided the following rules are followed: 1. The TOTAL current draw of the actuators (VA rating) is less than or equal to the rating of the transformer. 2. Polarity on the secondary of the transformer is strictly followed. This means that all No. 1 wires from all actuators are connected to the common leg on the transformer and all No. 2 wires from all actuators are connected to the hotleg. Mixing wire No. 1 & 2 on one leg of the transformer will result in erratic operation or failure of the actuator and/or controls. Multiple actuators, multiple transformers Multiple actuators positioned by the same control signal may be powered from multiple transformers provided the following rules are followed: 1. The transformers are properly sized. 2. All No. 1 wires from all actuators are tied together and tied to the negative leg of the control signal. See wiring diagram. Wire type and wire installation tips For most installations, 18 or 16 Ga. cable works well with Belimo actuators. Review job requirements and determine whether a plenum or appliance rated cable is appropriate. Use code-approved wire nuts, terminal strips or solderless connectors where wires are joined. It is good practice to run control wires unspliced from the actuator to the controller. If splices are unavoidable, make sure the splice can be reached for possible maintenance. Tape and/or wire-tie the splice to reduce the possibility of the splice being inadvertently pulled apart. Wire length for actuator installation Keep power wire runs below the lengths listed in the following tables. If more than one actuator is powered from the same wire run, divide the allowable wire length by the number of actuators to determine the maximum run to any single actuator. 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. WARNING: The wiring technician must be trained and experienced with electronic circuits. Disconnect power supply before attempting any wiring connections or changes. Make all connections in accordance with wiring diagrams and follow all applicable local and national codes. Provide disconnect and overload protection as required. Use copper, twisted pair, conductors only. If using electrical conduit, the attachment to the actuator must be made with flexible conduit. 24 VAC 110 VAC 800-543-9038 USA 866-805-7089 CANADA 6 7 7 6 7 GM… 1125 800 475 300 895 545 900 550 800 1125 900 1150 1125 800 500 310 575 200 500 12 350 14 345 125 375 16 325 325 220 80 200 6 7.5 AM… 1150 925 600 375 200 6.5 NM… 1150 925 600 375 200 7.5 AM… 1125 700 450 300 150 6.5 NM… 1125 800 500 325 175 1125 700 450 300 150 1125 800 500 325 175 MAX Distance between Actuator and Supply (feet) 9.5 1150 LF…US TF…US 1125 900 18 215 11 NF..UP 1150 800 175 120 18 AF…US 895 900 20 29 AF..UP EF wire gauge 1050 440 545 500 12 650 575 375 275 500 325 14 575 375 325 345 165 415 110 VA 7.5 6 MAX Distance between Actuator and Supply (feet) 6.5 16 215 11 GM… 1125 18 265 8.5 LF…US TF…US 420 175 21 NF..UP 440 800 20 wire gauge AF 1175 260 500 AF..UP 1125 275 160 105 EF 1000 1100 165 900 800 700 550 600 500 12 550 390 360 350 14 VA 7 NM… 5 LM/LR… 1.5 CM… 1125 700 450 250 4.5 LM… 1125 700 450 250 4.5 LM… 700 450 250 1500 1000 600 325 3.5 CM… 1150 1000 600 350 3.5 CM… 1200 1150 800 MAX Distance between Actuator and Supply (feet) 22 NKQ… GM/GR… AM/AR… 325 110 21 GK/ GKR… 225 450 5 TF…US 145 325 7 LF…US 16 250 9 NF 18 220 10 AF 175 16 EF 20 wire gauge VA 1175 1125 750 400 3 LU 1175 1125 750 400 3 LU 600 375 200 6 AH… 700 450 250 5 LH… 700 450 250 5 LU… 1400 1200 1100 1 TR… 500 300 200 125 70 18 AMQ… NMQ… LMQ… AHQ… LHQ… *Belimo actuators and auxiliary switches are designed as a IEC protection class II, double insulated, and do not require an independent ground wire to earth, unless otherwise indicated in this document 220 VAC N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. Wire Size vs. Length of Run for Damper Actuators and Control Valves 203-791-8396 LATIN AMERICA / CARIBBEAN 3 24 VAC 110 VAC 800-543-9038 USA 866-805-7089 CANADA 3 SY2 Amps 357 606 905 SY1 Amps 12 10 8 5051 7937 12821 19608 33333 49751 18 16 14 12 10 8 0.3 29851 20000 11765 7692 4762 3030 0.5 29851 20000 11765 7692 4762 3030 0.5 Amps SY3 5000 SY2 14925 8 5000 2941 1923 Amps 10000 10 2941 1923 SY1 5882 12 1190 758 1 Amps SY3 543 364 214 140 Amps 3846 14 1190 758 1 364 214 140 87 55 7463 2381 16 wire gauge 3 7463 1515 18 0.5 543 233 14 87 55 92 144 16 wire gauge SY3 Amps SY4 6 Amps SY5 6.5 Amps 1.5 Amps SY5 250 168 99 65 40 1.8 Amps SY6 3.2 Amps SY7 4 Amps SY8 3.2 Amps SY9 0.7 Amps SY5 4975 3333 1961 1282 794 505 0.8 Amps SY6 4146 2778 1634 1068 661 421 1.6 Amps SY7 2332 1563 919 601 372 237 2 Amps SY8 1866 1250 735 481 298 189 1.6 Amps SY9 2332 1563 919 601 372 237 24876 16667 9804 6410 3968 2525 21322 14286 8403 5495 3401 2165 18657 12500 7353 4808 2976 1894 9328 6250 3676 2404 1488 947 7463 5000 2941 1923 1190 758 9328 6250 3676 2404 1488 947 MAX Distance between Actuator and Supply (feet) 0.6 Amps SY4 5741 3846 2262 1479 916 583 MAX Distance between Actuator and Supply (feet) 1.3 Amps SY4 271 182 107 70 43 MAX Distance between Actuator and Supply (feet) 1.8 18 wire gauge SY2 Amps SY1 7463 5000 2941 1923 1190 758 2 Amps SY10 1866 1250 735 481 298 189 4 Amps SY10 9328 6250 3676 2404 1488 947 1.6 Amps SY11 2488 1667 980 641 397 253 3 Amps SY11 6784 4545 2674 1748 1082 689 2.2 Amps SY12 1866 1250 735 481 298 189 4 Amps SY12 203-791-8396 LATIN AMERICA / CARIBBEAN N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. The NEC mandates that 24 VAC over 100 VA power requires CLASS 1 wiring conduit. Local codes may vary. Do NOT mix CLASS 1 & CLASS 2 circuits in the same conduit. Generally, 24 VAC actuators over 100 VA should be changed to 120 VAC models. 220 VAC 4 Amps Wire Size vs. Length of Run for SY Series Actuators Wiring for Damper Actuators and Control Valves W236_11 On/Off, Spring Return, Electronic Fail-Safe, 24V Actuators: EFB24(-S) TF24(-S) US EFX24(-S) GKB24-3 AF24(-S) US GKX24-3 NFB24(-S) NKQB24-1 Hazard Identification Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. 2 Equipment damage! Actuators may be connected in parallel. Power consumption and input impedance must be observed. WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. On/Off LF24(-S) US INSTALLATION NOTES Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. CAUTION NFX24(-S) NKQX24-1 1 Provide overload protection and disconnect as required. 3 Actuators may also be powered by 24 VDC. 5 Actuators with plenum rated cable do not have numbers on wires; use color codes instead. A Actuators with appliance cables are numbered. APPLICATION NOTES Meets cULus requirements without the need of an electrical ground connection. On/Off 1 24 VAC Transformer 24 VAC Transformer 2 3 5 Blk (1) Common – Line Volts 5 3 Red (2) + Blk (1) Common Line Volts N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. a a open a closed Red (2) + Hot Wht (3) + The indication of direction is valid for switch position 1. 1 0 NKQ On/Off 1 24 VAC Transformer Line Volts 3 5 Blk (1) Common – a Red (2) + Hot Wht (3) + Y1 input GK Refer to page 26 for auxiliary switch (-S models) wiring. 800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN 5 Wiring for Damper Actuators and Control Valves W231_A_11 On/Off, Spring Return, 120, 230V and UP Actuators: EFB120(-S) NFBUP(-S) EFX120(-S) NFXUP(-S) AFBUP(-S) AFXUP(-S) AF120(-S) US/AF230(-S) US LF120(-S) US/LF230(-S) US TF120(-S) US Hazard Identification INSTALLATION NOTES Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. CAUTION 14 Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. 2 Equipment damage! Actuators may be connected in parallel. Power consumption and input impedance must be observed. TF120(-S) US can be supplied with both 120 VAC and 230 VAC. 19 UP models and TF120(-S) US uses “L” instead of “H” on #2 wire. 20 All 120 VAC, 230 VAC and UP actuators use appliance rated cables. UP Universal Power Supply (UP) models can be supplied with 24 VAC up to 240 VAC. WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. APPLICATION NOTES Meets cULus requirements without the need of an electrical ground connection. On/Off Line Volts 14 UP 2 20 19 Wht N Wht (1) Neutral Blk H Blk N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. 120 VAC 230 VAC (2) Hot Refer to page 26 for auxiliary switch (-S models) wiring. 800-543-9038 USA 6 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN Wiring for Damper Actuators and Control Valves W232_11 Floating Point, Spring Return, 24V Actuators: LF24-3(-S) US TF24-3(-S) US LFC24-3...US Hazard Identification Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. INSTALLATION NOTES Equipment damage! Actuators may be connected in parallel. Power consumption and input impedance must be observed. Actuators with plenum rated cable do not have numbers on wires; use color codes instead. Actuators with appliance cables are numbered. Actuators Hot wire must be connected to the control board common. For triac sink the Common connection from the actuator must be connected to the Hot connection of the controller. The actuator must be connected to the control board common. 5 Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. 2 Actuators may also be powered by 24 VDC. 3 CAUTION 6 11 WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. APPLICATION NOTES Meets cULus requirements without the need of an electrical ground connection. † Actuator Wire Number 4 5 4 5 TF24-3 US TF24-3-S US LF24-3 US LF24-3-S US Floating Point Color Org Org Grn Wht Triac Source 24 VAC Transformer 3 24 VAC Transformer Blk (1) Common Line Volts N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. 5 Line Volts Red (2) + Hot a b Wht (3) + † 2 Hot + Com 5 Blk (1) Common Red (2) + Hot CW CCW Wht (3) + LF24-3(-S) US LFC24-3-R US LFC24-3-S US TF24-3(-S) US The indication of direction is valid for switch position CW. † + CW CCW LF24-3(-S) US TF24-3(-S) US The indication of direction is valid for switch position CW. Controller Triac Sink Triac Sink with Separate Transformer 24 VAC Transformer Line Volts 2 Hot Com 5 11 24 VAC Transformer Blk (1) Common Red (2) + Hot 24 VAC Transformer 6 Line Volts Wht (3) + † CW Line Volts 2 5 + CCW Blk (1) Common Hot LF24-3(-S) US TF24-3(-S) US Com Red (2) + Hot 6 Wht (3) + Controller The indication of direction is valid for switch position CW. † CW + CCW LF24-3(-S) US TF24-3(-S) US Controller The indication of direction is valid for switch position CW. Refer to page 26 for auxiliary switch (-S models) wiring. 800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN 7 Wiring for Damper Actuators and Control Valves Actuators: LMB24-3(-S) (-P5) (-P10) (-T) TR24-3(-T) US CMB24-3… NMB24-3 ARB24-3-5 AMB24-3(-S) GMB24-3… GRB24-3-5 LMX24-3(-T) NMX24-3(-T) GRB24-3-7 Hazard Identification Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. 2 Equipment damage! Actuators may be connected in parallel. Power consumption and input impedance must be observed. LRB24-3(-S) ARX24-3 ARB24-3(-S) LRX24-3 LRCB24-3(-S) INSTALLATION NOTES Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. CAUTION AMX24-3(-T) GMX24-3… GMB24-3-X1 3 Actuators may also be powered by 24 VDC. 5 Actuators with plenum rated cable do not have numbers on wires; use color codes instead. Actuators with appliance cables are numbered. 16 The TR24-3-T US actuators are provided with a numbered screw terminal strip instead of cable. 17 TR24-3 US actuators cannot be wired in parallel. WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. APPLICATION NOTES Meets cULus requirements without the need of an electrical ground connection. Floating Point On/Off 24 VAC Transformer 2 3 5 24 VAC Transformer Blk (1) Common Line Volts 3 5 Blk (1) Common Line Volts Red (2) + 2 Red (2) + a a open a closed Wht (3) + 1 0 The indication of direction is valid for switch position 1. Wht (3) + LMB(X)24-3... NMB(X)24-3... AMB(X)24-3... GMB(X)24-3... CMB24-3... LRB(X)24-3... ARB(X)24-3... Line Volts The indication of direction is valid for switch position 1. GMB(X)24-3... CMB24-3... LRB(X)24-3... ARB(X)24-3... 16 17 5 24 VAC Transformer Blk 1 Common 5 16 17 Blk 1 Common Line Volts Red 2 + Red 2 + Wht 3 + Note: TR24-3 (-T) US cannot be wired in parallel with any actuator. LMB(X)24-3... NMB(X)24-3... AMB(X)24-3... Floating Point On/Off – SPDT Switch 24 VAC Transformer 1 0 Wht 3 + Note: TR24-3 (-T) US cannot be wired in parallel with any actuator. TR24-3 (-T) US TR24-3 (-T) US Refer to page 26 for auxiliary switch (-S models) and -P5, -P10 potentiometer wiring. 800-543-9038 USA 8 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. W332_11 On/Off and Floating Point, Non-Spring Return, 24V Wiring for Damper Actuators and Control Valves W612_11 Floating Point, Electronic Fail-Safe, 24V Actuators: GKB24-3 Hazard Identification INSTALLATION NOTES Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. 2 Equipment damage! Actuators may be connected in parallel. Power consumption and input impedance must be observed. WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. 1 Provide overload protection and disconnect as required. 3 Actuators may also be powered by 24 VDC. 5 Control signal may be pulsed from either the Hot (source) or the Common (sink) 24 VAC line. 8 Contact closures A & B also can be triacs. A & B should both be closed for triac source and open for triac sink. 9 For triac sink the common connection from the actuator must be connected to the hot connection of the controller. APPLICATION NOTES Meets cULus requirements without the need of an electrical ground connection. N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. Floating Point GKB24-3 800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN 9 Wiring for Damper Actuators and Control Valves Actuators: LMX120-3 NMX120-3 AMX120-3 GMX120-3 LRX120-3 ARX120-3 CMB120-3 Hazard Identification INSTALLATION NOTES Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. 2 Equipment damage! Actuators may be connected in parallel. Power consumption and input impedance must be observed. 15 LMB(X), NMB(X), AMB(X), GMB(X), LRB(X), and ARB(X) can be supplied with either 120 VAC or 230 VAC. 19 All 120VAC and 230VAC actuators use appliance rated cables. A Actuators with appliance cables are numbered. WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. APPLICATION NOTES Meets cULus requirements without the need of an electrical ground connection. Floating Point On/Off 100 to 240 VAC 2 15 19 100 to 240 VAC 15 2 19 N L1 Blu (1) Common – N L1 Blk (1) Common H L2 Blk (2) + H L2 Red (2) + a open a closed a The indication of direction is valid for switch position 1. Wht (3) + 1 0 Wht (3) + The indication of direction is valid for switch position 1. 1 0 Refer to page 26 for auxiliary switch (-S models) wiring. 800-543-9038 USA 10 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. W364_11 On/Off and Floating Point, Non-Spring Return, 100 to 240V Wiring for Damper Actuators and Control Valves W233_A_11 Proportional, Spring Return, 24V Actuators: EFB24-SR(-S) NFB24-SR(-S) EFX24-SR(-S) NFX24-SR(-S) AFB24-SR(-S) AFX24-SR(-S) AF24-SR US LF24-SR(-S) US TF24-SR(-S) US AFA24-SR US Hazard Identification INSTALLATION NOTES Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. 4 Equipment damage! Up to four actuators may be connected in parallel if not mechanically linked. Power consumption and input impedance must be observed. WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. 3 Actuators may also be powered by 24 VDC. 5 Actuators with plenum rated cable do not have numbers on wires; use color codes instead. Actuators with appliance cables are numbered. 6 Only connect common to neg. (–) leg of control circuits. APPLICATION NOTES Meets cULus requirements without the need of an electrical ground connection. 7 A 500 Ω resistor converts the 4 to 20 mA control signal to 2 to 10 VDC. 8 The AFA24-SR US and TF24-SR(-S) US are supplied without position feedback. † Actuator 24 VAC Transformer Line 4 7 Blk (1) Common Volts N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. 3 Red (2) + Hot (–) Control Signal (+) VDC/mA Ω 500 Ω 2 to 10 VDC (–) Feedback Signal (+) 5 Wht (3) Y Input, 2 to 10 † Wire Number 5 5 5 5 5 5 5 5 5 EFB24-SR(-S) EFX24-SR(-S) AFB24-SR(-S) AFX24-SR(-S) AF24-SR US NFB24-SR(-S) NFX24-SR(-S) LF24-SR US LF24-SR-S US Color Org Org Org Org Wht Org Org Grn Wht (5) U Output, 2 to 10V 6 CW CCW EFB24-SR(-S) EFX24-SR(-S) AFB24-SR(-S) AFX24-SR(-S) AF24-SR US NFB24-SR(-S) NFX24-SR(-S) LF24-SR(-S) US 24 VAC Transformer Line 3 4 7 Blk (1) Common Volts (–) Control Signal (+) VDC/mA 6 Ω 500 Ω Red (2) + Hot 5 Wht (3) Y Input, 2 to 10V 8 AFA24-SR US TF24-SR(-S) US Refer to page 26 for auxiliary switch (-S models) wiring. 800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN 11 Wiring for Damper Actuators and Control Valves W333_11 Proportional, Non-Spring Return, Electronic Fail-Safe, 24V Actuators: LMB24-SR (-T) NMB24-SR LMX24-SR (-T) GMB24-SR AMX24-SR (-T) CMB24-SR-R GKB24-SR AMB24-SR CMB24-SR-L NMX24-SR (-T) GMX24-SR GKX24-SR Hazard Identification INSTALLATION NOTES Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. 3 Actuators may also be powered by 24 VDC. 5 Actuators with plenum rated cable do not have numbers on wires; use color codes instead. Actuators with appliance cables are numbered. 6 Only connect common to neg. (–) leg of control circuits. Terminal models (-T) have no-feedback. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. 4 LRB24-SR TR24-SR (-T) US ARB24-SR LRX24-SR ARX24-SR NKQB24-SR NKQX24-SR Equipment damage! Up to four actuators may be connected in parallel if not mechanically linked. Power consumption and input impedance must be observed. APPLICATION NOTES WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. Blk Line 7 Ω (–) 500 Ω Control Signal (+) VDC/mA 7 3 24 VAC Transformer 4 Line (1) Common 5 (–) Control Signal (+) VDC/mA Wht (3) Y Input 2 to 10V Ω 500 Ω Red (2) + Hot 5 Wht (3) Y Input, 2 to 10V Org (5) U Output, 2 to 10V 7 2 to 10 VDC (–) Feedback Signal (+) 6 4 Blk (1) Common Volts Red (2) + Hot Volts A 500 Ω resistor converts the 4 to 20 mA control signal to 2 to 10 VDC. TR24-SR (-T) US 6 1 0 LMB(X)24-SR... NMB(X)24-SR... AMB(X)24-SR... GMB(X)24-SR... LRB(X)24-SR... ARB(X)24-SR... LHB(X)24-SR... AHB(X)24-SR... LUB(X)24-SR CMB24-SR... GK... NK... 800-543-9038 USA 12 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. 3 24 VAC Transformer Meets cULus requirements without the need of an electrical ground connection. Wiring for Damper Actuators and Control Valves W365_11 Proportional, Non-Spring Return, 100 to 240V Actuators: LMX120-SR NMX120-SR AMX120-SR LRX120-SR ARX120-SR Hazard Identification INSTALLATION NOTES Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. CAUTION 15 LMB(X), NMB(X), AMB(X), GMB(X), LRB(X), and ARB(X) can be supplied with either 120 VAC or 230 VAC. 6 Only connect common to neg. (–) leg of control circuits. 19 All 120 VAC and 230 VAC actuators use appliance rated cables. A Actuators with appliance cables are numbered. Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. 2 Equipment damage! Actuators may be connected in parallel. Power consumption and input impedance must be observed. WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. 2 A 500 Ω resistor converts the 4 to 20 mA control signal to 2 to 10 VDC. 19 N L1 Wht (1) Neutral H L2 Blk (2) Hot + 6 7 Cable 2 15 Meets cULus requirements without the need of an electrical ground connection. Blk (1) Common 7 (–) Control Signal VDC/mA (+) 2 to 10 VDC (–) Feedback Signal (+) Red (2) Hot + 5 Wht (3) Y Input, 2 to 10V Org (5) U Output, 2 to 10V 1 800-543-9038 USA Cable 1 N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. 100 to 240 VAC APPLICATION NOTES 0 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN 13 Wiring for Damper Actuators and Control Valves W225_2_11 Phasecut Control Signal, Spring Return and Non-Spring Return, 24V Actuators: AF24-PC US NMX24-PC LMX24-PC GMX24-PC AMX24-PC ARX24-PC LRX24-PC Hazard Identification INSTALLATION NOTES Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. 3 Actuators may also be powered by 24 VDC. 5 Actuators with plenum rated cable do not have numbers on wires; use color codes instead. Actuators with appliance cables are numbered. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. 2 Equipment damage! Actuators may be connected in parallel. Power consumption and input impedance must be observed. APPLICATION NOTES WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. 2 Meets cULus requirements without the need of an electrical ground connection. 5 3 24 VAC Transformer N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. Blk (1) Common – Line Volts Red (2) Hot + Wht *(3) Y Input, 0 to 10V phasecut (–) Control Signal (+) 0 to 10 V Phasecut Org‡ (5) U Output, 2 to 10V …PC * White color wire for AF24-PC US, Pink color for all others. ‡ White color wire for AF24-PC US, Orange color for all others. 800-543-9038 USA 14 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN Wiring for Damper Actuators and Control Valves W604_11 Proportional, Spring Return, 24V, 3 kΩ or 10 kΩ Control Input Actuators: LF24-ECON-R03 US LF24-ECON-R10 US AF24-ECON-R03 US Hazard Identification INSTALLATION NOTES Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. 2 Equipment damage! Actuators may be connected in parallel. Power consumption and input impedance must be observed. Override Control 27 A relay or switch can spring return the actuator when the RTU fan de-energizes, or if low ambient temperature is sensed. A standard relay can be used to close the sensor circuit to engage economizer mode, e.g. outside air changeover device like a dry bulb or enthalpy limit switch. Honeywell ® logic module W7459A and enthalpy sensor C7400 also provide terminals for this switching. 29 A remote CO2 sensor or DDC controller can change the standard relay opening or closing the sensor circuit. This device can be a relay or a dry bulb/enthalpy limit switch. 30 Override control for Y2 only accepts 0 to 10 VDC override control. Application Drive closed (0%) Morning warm-up cycle 24 VAC W203 AF24-ECON LF24-ECON… position Y1 Common Drive open (100%) Smoke Purge Y1 Open wire Drive to min. position Mechanical cooling in use, RTU thermostat calls for heat. 0 VDC to 10 VDC Min. position of 0% to 100% B Line Volts Blk (1) Common Red (2) + Hot 27 Wht (3) Y1 A Override potentiometer via a remote C02 sensor/controller or DDC controller. Standard Economizer Mode Wiring 2 5 24 VAC Transformer Org (4) Y2 Min-pos, 0 to 10V Grn (5) U Output, 2 to 10V Default CW CCW A Override Closed (0%) B Override Open (100%) (–) Control Signal (+) 0 to 10 VDC 29 30 1 0 26 .8 .2 .4 .6 MIN AF24-ECON-R03 US LF24-ECON-R03 US LF24-ECON-R10 US W202 N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. Min-position is adjustable from 0 to 100% with a potentiometer on the actuator cover. Override Wire Input Signal Y2 26 28 WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. Y1 Actuators with plenum rated cable do not have numbers on wires; use color codes instead. Actuators with appliance cables are numbered. 5 CAUTION 2 5 24 VAC Transformer Line Volts Blk (1) Common Red (2) + Hot 27 Wht (3) Y1 3 kΩ NTC* MA thermistor setpoint 55∞F Org (4) Y2 Min-pos, 0 to 10 V Grn (5) U Output, 2 to 10V 28 Default CW CCW (–) Control Signal (+) 0 to 10 VDC 29 30 1 0 26 .8 .2 .4 .6 MIN AF24-ECON-R03 US LF24-ECON-R03 US LF24-ECON-R10 US *10 kΩ NTC thermistor for -R10 types. 800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN 15 Wiring for Damper Actuators and Control Valves Proportional, Spring Return, 24V, 2 to 10 VDC (or 4 to 20 mA) W605_11 Control Signal or Three-Position On/Off Control Actuators: LF24-SR-E US Hazard Identification INSTALLATION NOTES Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. Equipment damage! Actuators may be connected in parallel. Power consumption and input impedance must be observed. WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. Actuators may also be powered by 24 VDC. 5 Actuators with plenum rated cable do not have numbers on wires; use color codes instead. Actuators with appliance cables are numbered. 7 A 500 Ω resister converts the 4 to 20 mA control signal to 2 to 10 VDC. 26 Min-position is adjustable from 0 to 100% with a potentiometer on the actuator cover. 31 For three-position control set direction of rotation to CW (default). 32 Switch A, actuator spring returns when open (e.g., fan interlock). 21 24 VAC Transformer Blk (1) Red (2) x + Min-position 32 Wht (3) D Y Full Open Grn (5) 31 Three-Position Control Signals Switch A Wire 2-Red (x) Wire 3-White (D) Any Any Closed (via spring) 24 VAC Open Min-position* Closed Open 24 VAC Full Open* Closed 24 VAC 24 VAC Full Open* * Desired position achieved by driving actuator with motor. ** An example would be to interlock the actuator power supply with the fan motor starter. LF24-SR-E US 21 24 VAC Transformer W179 3 2 Line Blk (1) Common Volts 0 .2 MIN 3 5 Blk (1) Volts Line .4 Min-Position with Full Open Override (with a single contact closure) 2 to 10 VDC Control of LF24-SR-E US 5 .8 .6 26 Closed 24 VAC Transformer 1 Default CW CCW Position Open** 21 U Output, 2 to 10V Common Red (2) x + Min-position 32 24 VAC Wht (3) D Y Full Open Red (2) + Hot Ω Grn (5) (–) Control Signal (+) 2 to 10 VDC Wht (3) Y Input, 2 to 10V 7 31 Grn (5) U Output, 2 to 10V Default CW 1 CCW LF24-SR-E US 0 .8 .6 26 .8 .4 800-543-9038 USA 1 .6 26 16 U Output, 2 to 10V Default CW CCW LF24-SR-E US .4 0 .2 MIN .2 MIN 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. Provide overload protection and disconnect as required. 21 Common 24 VAC Volts Meets cULus requirements without the need of an electrical ground connection. 3 5 Line APPLICATION NOTES W176 Three-Position Control with a SPDT Switch or Two Contact Closures (e.g. fan, cooling Y) W176 2 3 Wiring for Control Valves W606_11 On/Off and Floating Point, Spring and Non-Spring Return, 24V Actuators: NV24-3 US NVD24-3 US NVFD24 (-E) US Hazard Identification Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. 2 WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. Equipment damage! Actuators may be connected in parallel. Power consumption and input impedance must be observed. APPLICATION NOTES Meets cULus requirements without the need of an electrical ground connection. Floating Point and On/Off Control (diagram shown with default position of S1.2: Off) 24 VAC Transformer Line 2 On/Off Control-using actuator to drive open/close, spring upon power loss. (diagram shown with default position of S3.2: 3-way Off, 2-way On) Blk (1) – Common Volts Wht (2) + 2 24 VAC Transformer extending Line Wht (3) + Blk (1) – Common Volts retracting Red (2) + Hot Wht (3) Y1 Input NV24-3 US NVD24-3 US NVFD24 US NVFD24-E US = actuator plunger extending = actuator plunger retracting N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. Triac Source Floating Point On/Off Control (diagram shown with default position of S1.2: Off) Line 24 VAC Transformer (AC only) Volts 24 VAC Transformer Line Volts 2 2 Hot Com Blk (1) – Common Wht (2) + extending Wht (3) + retracting Blk (1) – Common Wht (2) + Hot Wht (3) Y1 Input Controller NV24-3 US NVD24-3 US NV24-3 US NVD24-3 US Triac Sink Floating Point Line On/Off Control-using actuator to drive one direction and spring the opposite direction. NOTE: A bridge must be made inside the NVF between terminals 2 and 3 (diagram shown with default position of S3.2: 3-way Off, 2-way On) 24 VAC Transformer Line Volts Volts 2 Hot Com Blk (1) – Common Wht (2) + Hot 2 Controller Wht (3) Y1 Input Blk (1) – Common NV24-3 US NVD24-3 US Wht (2) + Hot Wht (3) Y1 Input NVFD24 US NVFD24-E US 800-543-9038 USA 24 VAC Transformer (AC only) SPRING RETURN ACTUATORS MODEL DESIGNATION 866-805-7089 CANADA retracting plunger (spring up) NVFD24 US NVFD24-MFT US NVF24-MFT US extending plunger (spring down) NVFD24-E US NVFD24-MFT-E US NVF24-MFT-E US 203-791-8396 LATIN AMERICA / CARIBBEAN 17 Wiring for Control Valves Actuators: NVF24-MFT (-E) US NVFD24-MFT (-E) US NV24-MFT US Hazard Identification INSTALLATION NOTES Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. 10 CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. 2 Equipment damage! Actuators may be connected in parallel. Power consumption and input impedance must be observed. WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. For triac sink the Common connection from the actuator must be connected to the Hot connection of the controller. Position feedback cannot be used with a triac sink controller. The actuator internal common reference is not compatible. APPLICATION NOTES Meets cULus requirements without the need of an electrical ground connection. 8 Control signal may be pulsed from either the Hot (Source) or Common (Sink) 24 VAC line. 12 IN4004 or IN4007 diode. (IN4007 supplied, Belimo part number 40155) Triac Source Floating Point 24 VAC Transformer (AC only) Floating Point Control. (diagram shown with default position of S3.2: 3-way Off, 2-way On.) Line Volts 2 Hot 2 24 VAC Transformer 12 Requires diode NVD24-MFT US COM Blk (1) Common Red (2) + Hot Line Blk Volts (1) – Common Wht (3) Y1 Input, 2 to 10V Red (2) + Hot Wht (5) U Output, 2 to 10V A Wht (3) Y1 Input CCW 2 to 10 VDC Feedback Signal CW 12 12 Wht (5) U Output, 2 to 10V B Controller Position Feedback NVF24-MFT US NVF24-MFT-E US NVFD24-MFT US NVFD24-MFT-E US NV24-MFT US NVD24-MFT US NVF24-MFT US NVF24-MFT-E US NVFD24-MFT US NVFD24-MFT-E US NV24-MFT US NVD24-MFT US Direction of rotation switch CCW CCW CW CW B 1 A A B 1 Pulse Width Modulation Control Wiring (diagram shown with default position of S3.2: 3-way Off, 2-way On) 12 2 24 VAC Transformer Line Blk Volts (1) – Common Triac Sink Floating Point Red (2) + Hot 24 VAC Transformer (AC only) 8 Line Volts Wht (3) Y Input (–) 2 to 10 VDC Feedback Signal (+) 10 Wht (5) U Output Hot NVF24-MFT US NVF24-MFT-E US NVFD24-MFT US NVFD24-MFT-E US NV24-MFT US NVD24-MFT US COM Red (2) + Hot Wht (3) Y1 Input, 2 to 10V Wht (5) U Output, 2 to 10V 12 MFT Typical 2 to 10 VDC or 4 to 20 mA Wiring (diagram shown with default position of S3.2: 3-way Off, 2-way On) 24 VAC Transformer Line (–) Control Signal VDC/mA (+) (–) 2 to 10 VDC (+) Feedback Signal Controller NVF24-MFT US NVF24-MFT-E US NVFD24-MFT US NVFD24-MFT-E US NV24-MFT US NVD24-MFT US 2 Blk Volts 2 Blk (1) Common (1) Common SPRING RETURN ACTUATORS MODEL DESIGNATION Red (2) + Hot Ω 500 Ω Wht (3) Y1 Input, 2 to 10V retracting plunger (spring up) NVFD24 US NVFD24-MFT US NVF24-MFT US extending plunger (spring down) NVFD24-E US NVFD24-MFT-E US NVF24-MFT-E US Wht (5) U Output, 2 to 10V NVF24-MFT US NVF24-MFT-E US NVFD24-MFT US NVFD24-MFT-E US NV24-MFT US NVD24-MFT US 800-543-9038 USA 18 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. W607_11 MFT, Spring and Non-Spring Return, 24V Wiring for Damper Actuators and Control Valves W228_A_11 MFT, Spring Return, 24V Actuators: TF24-MFT US LF24-MFT(-S) US Hazard Identification Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. INSTALLATION NOTES 3 Actuators may also be powered by 24 VDC. CAUTION 5 Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. Actuators with plenum rated cable do not have numbers on wires; use color codes instead. Actuators with appliance cables are numbered. 8 4 Equipment damage! Actuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed. WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. APPLICATION NOTES Meets cULus requirements without the need of an electrical ground connection. 7 A 500 Ω resistor converts the 4 to 20 mA control signal to 2 to 10 VDC. 9 Contact closures A & B also can be triacs. A & B should both be closed for triac source and open for triac sink. 12 4 Blk Line Volts 8 (–) 2 to 10 VDC Feedback Signal (+) IN4004 or IN4007 diode. (IN4007 supplied, Belimo part number 40155). (1) – Common Two Position Red (2) + Hot A N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. 5 10 For triac sink the Common connection from the actuator must be connected to the Hot connection of the controller. Position feedback cannot be used with a Triac sink controller. The actuator internal common reference is not compatible. 10 Floating Point 24 VAC Transformer Control signal may be pulsed from either the Hot (Source) or Common (Sink) 24 VAC line. Wht (3) Y1 Input 4 24 VAC/DC Transformer 3 5 B 9 12 † (5) U Output 2 to 10V Line Blk (1) Common Volts Red (2) Hot a CCW CW (–) Position Feedback VDC (+) Direction of rotation switch CCW CW CW A B Y Input † U Output (5) CCW CW CCW 5 Wht (3) B 5 A Override Control to min, mid, max, Positions PWM 5 24 VAC Transformer (AC only) 24 VAC Transformer (AC only) Blk (1) Common Line 5 4 Volts Line Blk (1) Common Red (2) + Hot Wht (3) Y Input 8 Volts (–) Position (+) Feedback VDC † (5) Red (2) + Hot A Ω (–) Control Signal 2-10 VDC or 4 to 20 mA (+) 7 U Output B C Wht (3) Y1 Input, 2 to 10V 500 Ω 1/4 watt A Min* Mid* Max* Normal** † Actuator TF24-MFT US LF24-MFT US Wire Number 5 5 800-543-9038 USA Color Org Wht B C Functions CCW CW 0% 50% 100% Control mode acc. to Y * Default selectable 0-100%. See Configuration Data Sheet. ** Customizable. See Configuration Data Sheet. Refer to page 26 for auxiliary switch (-S models) wiring. 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN 19 Wiring for Damper Actuators and Control Valves W400_A_11 MFT, Spring Return, Non-Spring Return, Electronic Fail-Safe, 24V Actuators: EFB24-MFT(-S) EFX24-MFT(-S) AFB24-MFT(-S) AFX24-MFT(-S) NFB24-MFT(-S) NFX24-MFT(-S) LMX LRX NMX AMX ARX GKX NKQ ARX24-MFT-5 ARB24-MFT-5 GRX24-MFT-5 GMX24-MFT-X1 GRB24-MFT-S GRB24-MFT-5 GRB24-MFT-7 Hazard Identification INSTALLATION NOTES Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. 3 CAUTION 5 Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. 8 Equipment damage! Actuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed. 10 WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. APPLICATION NOTES Meets cULus requirements without the need of an electrical ground connection. 7 A 500 Ω resistor converts the 4 to 20 mA control signal to 2 to 10 VDC. 9 Contact closures A & B also can be triacs. A & B should both be closed for triac source and open for triac sink. VDC/4-20 mA 4 24 VAC Transformer 3 For triac sink the Common connection from the actuator must be connected to the Hot connection of the controller. Position feedback cannot be used with a triac sink controller. The actuator internal common reference is not compatible. 5 Blk (1) Common Line Volts Two Position Red (2) + Hot 500 Ω Ω 1/4 watt (–) Control Signal (+) 4 to 20 mA or 2 to 10 VDC 24 VAC/DC Transformer Wht (3) Y1 Input, 2 to 10V 7 Pnk (4) Y2 Input 4 Blk (1) Common Line Grn (5) U Output, 2 to 10V 5 3 Volts Red (2) Hot a CCW CW Position Feedback VDC Wht (3) Y Input Pnk (4) Y2 Input Org (5) U Output (–) (+) Floating Point (except NKQ) 10 24 VAC Transformer 4 5 3 Blk (1) Common – Line Volts Red (2) Hot + A 8 Wht (3) Y1 Input Override Control to min, mid, max, Positions B (–) 2 to 10 VDC Feedback Signal (+) Pnk (4) Y2 Input 9 Org (5) U Output 2 to 10V 24 VAC Transformer (AC Only) CCW CW A B 5 Volts CCW Ω B 5 (–) Control Signal 2-10 VDC or 4 to 20 mA (+) Triac Source and Sink Diagrams (See page 21) Red (2) + Hot A CW A 7 B C Wht (3) Y1 Input, 2 to 10V Pnk (4) Y2 Input Org (5) 500 Ω 1/4 watt PWM (except NKQ) 24 VAC Transformer (AC only) 4 Functions 5 Min* Blk (1) Common Line Volts Position (–) Feedback VDC (+) 800-543-9038 USA 20 8 Red (2) + Hot Wht (3) Y Input Pnk (4) Y2 Input Org (5) U Output 866-805-7089 CANADA 5 Blk (1) Common Line Direction of rotation switch 3 Mid* Max* Normal** a b c 0% 50% 100% Control mode acc. to Y * Default selectable 0-100%. See Configuration Data Sheet. ** Customizable. See Configuration Data Sheet. 203-791-8396 LATIN AMERICA / CARIBBEAN N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. 4 Actuators may also be powered by 24 VDC. Actuators with plenum rated cable do not have numbers on wires; use color codes instead. Actuators with appliance cables are numbered. Control signal may be pulsed from either the Hot (Source) or Common (Sink) 24 VAC line. Wiring for Damper Actuators and Control Valves W402_11 MFT, Non-Spring Return, 24V Actuators: LMX ARB24-MFT-5 GRB24-MFT-7 LRX GMX24-MFT NMX AMX ARX GMX24-MFT-X1 GRX24-MFT-5 GRX24-MFT-7 Hazard Identification INSTALLATION NOTES Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. 4 Equipment damage! Actuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed. 5 Actuators with plenum rated cable do not have numbers on wires; use color codes instead. Actuators with appliance cables are numbered. 6 Only connect common neg (-) leg of control circuits. 11 WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. Triac Sink ARX24-MFT-5 GRB24-MFT-5 For triac sink with common connection from the actuator must be connected to the hot connection of the controller. The actuator must be connected to the control board common. APPLICATION NOTES Meets cULus requirements without the need of an electrical ground connection. Triac Sink with Separate Transformer 24 VAC Transformer 24 VAC Transformer Line Volts 24 VAC Transformer 11 N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. Hot Com 4 5 6 Blk (1) Common Volts Line 4 Volts Red (2) + Hot Wht (3) Y1 Input Line 5 Blk (1) Common Hot Pnk (4) Y2 Input Org (5) U Output 2 to 10 V Com Red (2) + Hot Wht (3) Y1 Input Pnk (4) Y2 Input Org (5) U Output 2 to 10 V Controller Controller Triac Source 24 VAC Transformer Line Volts 4 Hot Com 5 Blk (1) Common Red (2) + Hot Wht (3) Y1 Input Pnk (4) Y2 Input Org (5) U Output 2 to 10 V Controller 800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN 21 Wiring for Damper Actuators and Control Valves W234_A_11 Wiring Multiple MFT Actuators Control Type: PWM Hazard Identification INSTALLATION NOTES 3 Actuators may also be powered by 24 VDC. 5 Actuators with plenum rated cable do not have numbers on wires; use color codes instead. Actuators with appliance cables are numbered. 8 Control signal may be pulsed from either the Hot or Common 24 VAC line. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. 4 Equipment damage! Actuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed. WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. Wiring multiple...MFT actuators to single shaft and/or on valves. All MFT actuators are wired in master-slave configuration. Pulse Width Modulation 5 24 VAC Transformer (AC Only) Master .1 to 25.5 sec Blk (1) Common Line Volts 8 Red (2) + Hot 3 Position Feedback VDC 0 to 5 VDC (–) Wht (3) Y Input (+) Org (5) U Output 2 to 10 VDC CCW CW MFT actuator configurations should also co-ordinate with each other. Meaning the master input = controllers output. Master output = slave input. Slave output = controller input. Slave Example 5 Blk (1) Common Controller Output Master Feedback Slave Input Slave Feedback Red (2) + Hot 0.1 to 25.5 sec 2 to 10 VDC 2 to 10 VDC 0 to 5 VDC Wht (3) Y Input 2 to 10 VDC Org (5) U Output Multiple Actuators Mounted to One Control Shaft Max. Qty Per Shaft Torque Generated EFB24-MFT(-S) EFX24-MFT(-S) Model 3 810 in-lb AFB24-MFT(-S) AFX24-MFT(-S) 3 432 in-lb GMX(B)24-MFT 2 640 in-lb GKX(B)24-MFT 2 640 in-lb 800-543-9038 USA 22 866-805-7089 CANADA CCW CW 4 203-791-8396 LATIN AMERICA / CARIBBEAN N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. Wiring for Damper Actuators and Control Valves Actuators: AFB24-MFT95 AFX24-MFT95 GMX24-MFT95 AMX24-MFT95 High Limit Control 22 23 24 25 Volts 22 Pnk (4) W W Series 90 Controller B R Red (2) + Hot R 5 = Gray 6 = Orange Series 90 Controller Volts Line W015 5 21 24 VAC Transformer Blk (1) Common Red (2) + Hot 23 A Pnk (4) W 135 Ω Wht (3) R B Gry (5) 21 Line Blk (1) Common Volts Red (2) + Hot 24 VAC Transformer Volts W Pnk (4) W R Wht (3) R B B 23 Shunting Resistor 24 24 22 Honeywell T675A Morning Warmup W Blk (1) Common Red (2) + Hot 23 Pnk (4) W No. of actuators Resistance 2 1300 Ω 3 910 Ω 4 768 Ω Resistor Kit No. ZG-R06 23 S963A Minimum Position Potentiometer 5 Red (2) + Hot B R R 22 B W 25 Pnk (4) W Wht (3) R Gry (5) B Org (6) ‘U5’ Output 2 to 10 VDC W 23 Gry (5) B Org (6) ‘U5’ Output 2 to 10 VDC To other actuators Used with the W973 and W7100 controllers Honeywell Q209A Minimum Position Potentiometer Line Blk (1) Common Volts Red (2) + Hot 22 23 Shunting Resistor W R R R B W Pnk (4) W W Wht (3) R W973, W7100 T775 Org (6) ‘U5’ Output 2 to 10 VDC Honeywell T675A Morning Warmup -MFT95 W 21 Line 21 21 5 Line Blk (1) Common Volts Line Volts Red (2) + Hot W W R B Pnk (4) W R Wht (3) R B Gry (5) B Series 90 low limit control 135 Ω for 0 to 50% control 280 Ω for 0 to 100% control 24 To other actuators 23 25 Wht (3) R 23 Pnk (4) W 25 Wht (3) R Gry (5) B Org (6) ‘U5’ Output 2 to 10 VDC 23 22 Pnk (4) W Blk (1) Common Red (2) + Hot Series 90 Controller Red (2) + Hot 22 22 Blk (1) Common 23 25 Gry (5) B B Volts 24 VAC Transformer -MFT95 -MFT95 R -MFT95 Low Limit Control 25 Wht (3) R -MFT95 H205 Change- Occupied over Controller Contact Org (6) ‘U5’ Output 2 to 10 VDC Controller R Volts 24 B Gry (5) B Occupied Contact Y Blk (1) Common A Line To other actuators Series 90 Controller -MFT95 B Pnk (4) W 25 Wht (3) R Gry (5) B Org (6) ‘U5’ Output 2 to 10 VDC Line Volts Org (6) ‘U5’ Output 2 to 10 VDC 24 VAC Transformer -MFT95 W Shunting Resistor 21 Wiring Multiple Actuators to a Series 90 Controller using a Minimum Position Potentiometer 21 B Gry (5) B 21 24 VAC Transformer 24 W016 N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. The direction of rotation switch is set so that the fail safe position and the position of the damper is closed with no signal at wire R. Volts Red (2) + Hot Damper Position Damper Closed Wht (3) R Line Blk (1) Common No. of actuators Resistance 2 140 Ω 3 71.5 Ω 4 47.5 Ω 5 37.5 Ω 6 28 Ω Resistor Kit No. ZG-R03 B 23 25 W973, W7100 Controller 23 21 Damper Open R -MFT95 Line Switch B W Pnk (4) W 24 Pnk (4) W 25 Wht (3) R Gry (5) B Org (6) ‘U5’ Output 2 to 10 VDC W W R Blk (1) Common Shunting Resistor R Org (6) ‘U5’ Output 2 to 10 VDC 5 24 VAC Transformer Volts B -MFT95 Wiring Multiple Actuators to a Series 90 Controller Override Switch A H205 Changeover Controller 22 Line Red (2) + Hot 22 Gry (5) B B W Series 90 high limit control - 280 Ω 24 3 = White 4 = Pink 24 Org (6) ‘U5’ Output 2 to 10 VDC Wire Colors 5 Blk (1) Common Volts Wht (3) R R B 1 = Black 2 = Red Line Red (2) + Hot 23 21 Q209A Minimum Position Potentiometer Blk (1) Common W018 21 Line LMX24-MFT95 Typical wiring diagrams for multiple actuators used with the W973, W7100 and T775 controllers 21 24 VAC Transformer W019 5 5 24 VAC Transformer 21 Actuators with plenum rated cable do not have numbers on wires; use color codes instead. Actuators with appliance cables are numbered. Provide overload protection and disconnect as required. Actuators and controller must have separate transformers. Consult controller instruction data for more detailed information. Resistor value depends on the type of controller and the number of actuators. No resistor is used for one actuator. Honeywell® resistor kits may also be used. To reverse control rotation, use the reversing switch. W017 INSTALLATION NOTES NMX24-MFT95 W020 Wnew60408_6 Spring Return and Non-Spring Return, 24V for use with Honeywell® Electronic Series 90, or a 0 to 135 Ω input Gry (5) B Org (6) ‘U5’ Output 2 to 10 VDC To other actuators -MFT95 -MFT95 Org (6) ‘U5’ Output 2 to 10 VDC 800-543-9038 USA -MFT95 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN 23 Wiring for Damper Actuators and Control Valves LF24-MFT-S-20 US 6 to 9 VDC Control of LF24-MFT (-S) -20 US Hazard Identification Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. 21 CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. 2 24 VAC Transformer Line Blk (1) Common Volts Red (2) + Hot Wht (3) Y Input, 6 to 9V Control Signal 6 to 9 VDC (+) Equipment damage! Actuators may be connected in parallel. Power consumption and input impedance must be observed. W027 Actuators: LF24-MFT-20 US 3 Wht (4) Output +20 VDC Wht (5) U Output 2 to 10V Power to Controller Wht (6) Common +20 VDC Controller Common (–) WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. CW CCW 2 Feedback 2-10 VDC LF24-MFT (-S) -20 US Multiple LF24-MFT (-S) -20 US Actuators from One Controller W029 W609_11 Proportional, Spring Return, 24V, 6 to 9 VDC Output Power Supply 20 VDC provides power to controllers 21 24 VAC Transformer INSTALLATION NOTES Line Blk (1) Common Volts Red (2) + Hot 3 Wht (3) Y Input, 6 to 9V Control Signal 6 to 9 VDC (+) Actuators may also be powered by 24 VDC 21 Provide overload protection and disconnect as required. Wht (4) Output +20 VDC Feedback 2-10 VDC Wht (5) U Output 2 to 10V Power to Controller Wht (6) Common +20 VDC Controller Common (–) CW 2 Typical Control Wiring for MP-52XX Series Actuators to Controllers Requiring External 20 VDC Power Supply LF24-MFT (-S) -20 US W215 CP-8102 TP-810X TP-8121 TP-8124 TP-8232 1 Vac Power Typical Controller +20 (Red) OP1 (Yellow) COM (Blue) 1 24 Vac: Black/Blue 120 Vac: White 240 Vac: White/Black Belimo modulating actuators are 24 VAC/DC, if 120 or 240 is available an external transformer is required. 2 Maximum of 2 3 MP-52XX-500 models include internal SPDT auxiliary switch. 21 24 VAC Transformer MP-52XX 2 Black Red Yellow Blue 3 Line Blk (1) Common Volts Red (2) + Hot 3 Wht (3) Y Input, 6 to 9V N.C. COM Brown Aux. Switch Orange Green Wht (4) Output, +20 VDC N.O. Wht (5) U Output 2 to 10V Wht (6) Common +20 VDC CW CCW 2 Wire cross reference MP-52XX Black/Blue, Power Black, Power Red, +20 Yellow, OP1 Blue, COM Brown, N.O. Orange, N.C. Green, Ground CCW Belimo (SR or MFT) 2, Hot 1, Com 4, +20 VDC 3, Signal 6, Com VDC S3, N.O. “-S” type S2, N.C. “-S” type Not used To other actuators LF24-MFT (-S) -20 US Refer to page 26 for auxiliary switch (-S models) wiring. 800-543-9038 USA 24 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. 3 Wiring for Damper Actuators and Control Valves W234_2_B_11 Wiring Multiple MFT Actuators Control Type: VDC or 4-20mA MFT95 VDC or 4-20mA Hazard Identification Red (2) + Hot 3 Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. 4 Blk (1) Common Line Volts CAUTION 5 Master 24 VAC Transformer Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. (–) Control Signal (+) 2 to 10 VDC or 4 to 20 mA Wht (3) Y Input, 2 to 10 V 500 Ω 1/4 watt Org (5) U Output 2 to 10 V Equipment damage! Actuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed. CCW CW WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. 5 Slave Blk (1) Common Red (2) + Hot Maximum 4 actuators per shaft. Wht (3) Y Input, 2 to 10 V Org (5) U CCW CW 4 INSTALLATION NOTES 3 Actuators may also be powered by 24 VDC. 5 Actuators with plenum rated cable do not have numbers on wires; use color codes instead. Actuators with appliance cables are numbered. Multiple Actuators Mounted to One Control Shaft N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. 21 21 Provide overload protection and disconnect as required. 23 Consult controller instruction data for more detailed information. 24 VAC Transformer Blk (1) Common Line Volts 3 W R 25 To reverse control rotation, use the reversing switch. 5 Master B Red (2) + Hot 23 Wht (3) W Pnk (4) R Gry (5) B 25 Org (6) U Output, 2 to 10 V -MFT95 Wiring multiple...MFT actuators to single shaft and/or on valves. All MFT actuators are wired in master-slave configuration. Slave 5 Blk (1) Common MFT actuator configurations should also co-ordinate with each other. Meaning the master input = controllers output. Master output = slave input. Slave output = controller input. Red (2) + Hot 23 Wht (3) Y1 Input 25 Pnk (4) Y2 Input Org (6) U Output 2 to 10 V Example Controller Output Master Feedback Slave Input Slave Feedback 2 to 10 VDC 2 to 10 VDC 2 to 10 VDC 0 to 5 VDC CCW CW -MFT 4 Multiple Actuators Mounted to One Control Shaft Model Max. Qty Per Shaft Torque Generated 3 810 in-lb 3 432 in-lb 2 640 in-lb 2 640 in-lb EFB24-MFT(-S) EFX24-MFT(-S) AFB24-MFT(-S) AFX24-MFT(-S) GMX(B)24-MFT GKX(B)24-MFT 800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN 25 Wiring for Damper Actuators and Control Valves Actuators: EFB...-S EFX...-S AFB...-S AFX...-S AF...-S US AMB(X)...-S LMB(X)...-S ARB(X)...-S LRB(X)...-S NFB...-S S1A/S2A NFX...-S LF...-S US LMB(X)...(-P5)(-P10) TF...-S US INSTALLATION NOTES APPLICATION NOTES 1 One built-in auxiliary switch (1xSPDT), for end position indication, interlock control, fan startup, etc. Meets cULus requirements without the need of an electrical ground connection. 13 Two built-in auxiliary switches (2xSPDT), for end position indication, interlock control, fan startup, etc. WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. † Same voltage must be used for dual switch models. Either 24 VAC or line voltage, not both. Auxiliary Switch Wiring for LF…-S US, TF…-S, LMB(X)24-3-S, AMB(X)24-3-S, LRB(X)24-3-S, ARB(X)24-3-S 1 S1 NC S2 S3 Auxiliary Switch Wiring for EFB...-S, EFX...-S, AFB...-S, AFX...-S, NFB...-S, NFX...-S 13 † NC S3 NO 10° Auxiliary Switch Ratings Voltage Product S4 NC S5 S6 NO 10° to 90° 10° to 85° for EF... EFB…-S AFB…-S NFB…-S EFX…-S AFX…-S NFX…-S Auxiliary Switch Wiring for AF… -S US 13 S1 S2 NC S3 NO NC S5 NO Resistive Load Inductive Load EFB...-S, EFX...-S AFB...-S, AFX...-S 250 250 3.0 A 3.0 A 0.5 A 0.5 A AF...-S US NFB...-S, NFX...-S 250 250 7.0 A 3.0 A 2.5 A 0.5 A LF...-S US 250 3.0 A 0.5 A TF...-S US 250 3.0 A 0.5 A AMB(X)...-S 250 3.0 A 0.5 A LMB(X)...-S 250 3.0 A 0.5 A ARB(X)...-S 250 3.0 A 0.5 A LRB(X)...-S 250 3.0 A 0.5 A S1A, S2A 250 3.0 A 0.5 A 5° S4 S6 0° to 95° LF…-S US TF…-S US LMB(X)24-3-S AMB(X)24-3-S LRB(X)24-3-S ARB(X)24-3-S S1 S2 NO 25° to 85° Potentiometer and Auxiliary Switch Wiring for LMB(X)24-3(-S)(-P5)(-P10) AF…-S US Add on Auxiliary Switches S1A/S2A for GMB(X), AMB(X), NMB(X), LMB(X), GRB(X), ARB(X), NRB(X), LRB(X) S1 S1 NC NC S2 S2 5/10K Ω S3 S3 NO NO S4 S1A NC S5 Potentiometer S6 Auxiliary Switch NO S2A 800-543-9038 USA 26 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. W224_A_11 Auxiliary Switch Wiring Interface Wiring Detail SYx-MFT, 24V, 120/230V Actuators: SYx-MFT Notes: 1. Motor CAMS have been factory calibrated and should not be moved. 2. An adaption must be performed if any limit switch is adjusted. This will calibrate the beginning and end stopping points. Press the adaption button for 3 seconds and release. INSTALLATION NOTES CAUTION Control Signal + Control Signal FDBK + FDBK - MFT Connection 24V Direction of Rotation N H Control Signal + Control Signal FDBK + FDBK - Adaption N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. Adaption Direction of Rotation 800-543-9038 USA 866-805-7089 CANADA 120/230V 203-791-8396 LATIN AMERICA / CARIBBEAN 27 SYx-P Interface Wiring Detail LED Open LED Close N Power Supply (3) Sensitivity switch setting is position #3 for factory default. To widen deadband, select a higher number (up to 9). + Power Supply (4) Control Signal (5) Control Signal (6) Feedback (11) Feedback (12) Sensitivity VR1 VR2 CAUTION Dip Switch Settings Notes: 1. Do not change sensitivity or dip switch settings with power applied! 2. VR1 and VR2 are factory calibrated and should not be moved. 3. Motor CAMS have been factory calibrated and should not be moved. 8 7 6 5 4 3 2 1 OFF 8 7 6 5 4 3 2 1 OFF RESPONSE = DIRECT INPUT = 2-10 VDC ON ON 8 7 6 5 4 3 2 1 OFF 8 7 6 5 4 3 2 1 OFF RESPONSE = REVERSE INPUT = 4-20mA ON ON 8 7 6 5 4 3 2 1 OFF INPUT = 1-5 VDC 8 7 6 5 4 3 2 1 OFF ON LOSS OF SIGNAL = CLOSED (Direct Acting) LOSS OF SIGNAL = OPEN ON 8 7 6 5 4 3 2 1 OFF (Reverse Acting) 8 7 6 5 4 3 2 1 OFF ON LOSS OF SIGNAL = CLOSED ON 8 7 6 5 4 3 2 1 OFF LOSS OF SIGNAL = OPEN (Direct Acting) OUTPUT = 4-20mA (Reverse Acting) 8 7 6 5 4 3 2 1 OFF OUTPUT = 2-10 VDC ON LOSS OF SIGNAL = STOP ON WARNING Potentiometer (Factory Pre-set) *On modulating actuators DO NOT master/slave using optional potentiometer. 800-543-9038 USA 28 For 2-position actuators with 1k feedback option Potentiometer points 1, 2, 3 are wired to terminal blocks 8, 9, 10. When a valve is closed: 8, 9 1k Ω 9, 10 0k Ω When a valve is opened: 8, 9 0k Ω 9, 10 1k Ω For modulating actuators with 1k feedback option* Potentiometer points 1, 2, 3 are wired to terminal blocks 8, 9, 10. When a valve is closed: 8, 9 1k Ω 9, 10 0k Ω When a valve is opened: 8, 9 0k Ω 9, 10 1k Ω 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. INSTALLATION NOTES Wiring for Damper Actuators and Control Valves W546_11 On/Off, 24V, 120V or 230V SY Actuator Wiring Diagram, SY1…5-24V – On/Off SY1…12-120V or 230V On/Off Hazard Identification INSTALLATION NOTES Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. Observe class 1 and class 2 wiring restrictions. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. Transformer sizing = SY actuator draw X 1.25 (safety margin) (Ex. SY2-24 requires 3.0A x 1.25 = 3.75A, 3.75A X 24 VAC = 90VA Transformer). Indicates an action or condition that may cause irreversible damage to the actuator(s) or associated equipment. Equipment damage! Power consumption and input impedance must be observed. NOTES SY1…12-120V or 230V sCaution: Power Supply Voltage s)SOLATIONRELAYSMUSTBEUSEDINPARALLELCONNECTIONOFMULTIPLEACTUATORS using a common control signal input. s(,CANNOTBECONNECTEDTOTERMINALANDSIMULTANEOUSLY sRequired: 4ERMINALNEEDSTOBEFIELDWIREDTOENABLEHEATERCIRCUIT NOTES SY1…5-24 Each actuator should be powered by a single, isolated 33 control transformer. s)SOLATIONRELAYSMUSTBEUSEDINPARALLELCONNECTIONOFMULTIPLEACTUATORS using a common control signal input. s(CANNOTBECONNECTEDTOTERMINALANDSIMULTANEOUSLY sRequired: 4ERMINALNEEDSTOBEFIELDWIREDTOENABLEHEATERCIRCUIT 33 24V AC/DC Transformer N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. Line Volts G Open Close G G Ground 1 Common 3 Open 4 Closed 5 Connect to #1 for fully open indication 5 Connect to #1 for fully open indication 6 Connect to #1 for fully closed indication 6 Connect to #1 for fully closed indication 7 HTR 7 A 120V or 230V AC/DC N L1 Open H L2 Close HTR G Ground 1 Common 3 Open 4 Closed A LS3 A-C (Open Indication) A-C (Open Indication) C C D D LS4 LS4 E E F D-F (Closed Indication) Contact Rating: 5A 250 VAC Max. SY2…5-24 A LS3 B C E F A LS3 B B F D-F (Closed Indication) Contact Rating: 5A 250 VAC Max. SY2…12-120V or 230V LS3 B A-B (Open Indication) Contact Rating: 5A 125 VAC Max. 3A 250 VAC Max. LS4 A-E (Closed Indication) SY1-24 C A-B (Open Indication) Contact Rating: 5A 125 VAC Max. 3A 250 VAC Max. E F LS4 A-E (Closed Indication) SY1-110 (220) SY1 Contact Arrangements 800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN 29 Wiring for Damper Actuators and Control Valves W547_11 Proportional, 24V, 120V or 230V SY Actuator Wiring Diagram, SY1-24P and SY1-110P (220P) Hazard Identification INSTALLATION NOTES 7ARNINGSAND#AUTIONSAPPEARATAPPROPRIATESECTIONSTHROUGHOUT this manual. Read these carefully. /BSERVE#LASSAND#LASSWIRINGRESTRICTIONS CAUTION 4RANSFORMERSIZING39ACTUATORDRAW8SAFETYMARGIN %X39REQUIRES!X!!86!#6!4RANSFORMER )NDICATESAPOTENTIALLYHAZARDOUSSITUATIONWHICHIFNOTAVOIDED may result in minor or moderate injury. It may also be used to alert against unsafe practices. APPLICATION NOTES Indicates an action or condition that may cause irreversible damage to the actuator(s) or associated equipment. %QUIPMENTDAMAGE 0OWERCONSUMPTIONANDINPUTIMPEDANCEMUSTBEOBSERVED 34 Ground shielded wire at control panel chassis. Tape back ground at actuator. 36 Use of feedback is optional. NOTES SY1…110P (220P) NOTES SY1…24P sCaution:0OWERSUPPLYVOLTAGE Each actuator should be powered by a single, isolated 33 control transformer. s0OWERSUPPLY#OM.EUTRALAND#ONTROL3IGNAL "–" wiring to a common is prohibited. Terminals 4 and 6 need to be wired separately. s0OWERSUPPLY#OM.EUTRALAND#ONTROL3IGNAL "–" wiring to a common is prohibited. Terminals 4 and 6 need to be wired separately. s$ONOTCHANGESENSITIVITYORDIPSWITCHSETTINGSWITHPOWERAPPLIED 33 24V AC/DC Transformer G Line Voltage Control signal 34 G Ground 4 Power Supply Com 5 Power Supply Hot 6 Control Signal (-) 7 Control Signal (+) G Ground N L1 4 Power Supply Com H L2 5 Power Supply Hot 6 Control Signal (-) 7 Control Signal (+) 8 Internal Use Only 9 Internal Use Only G 120 or 230 VAC 8 Internal Use Only 9 Internal Use Only Control signal 34 10 Internal Use Only 10 Internal Use Only Feedback 11 Feedback (-) A LS3 12 Feedback (+) C E F A LS3 B B !"/PEN)NDICATION #ONTACT2ATING !6!#-AX !6!#-AX LS4 !%#LOSED)NDICATION SY1-24P 800-543-9038 USA 11 Feedback (-) 36 36 30 Feedback 12 Feedback (+) 866-805-7089 CANADA C E F !"/PEN)NDICATION #ONTACT2ATING !6!#-AX !6!#-AX LS4 !%#LOSED)NDICATION SY1 -110P (220P) 203-791-8396 LATIN AMERICA / CARIBBEAN N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. s$ONOTCHANGESENSITIVITYORDIPSWITCHSETTINGSWITHPOWERAPPLIED Wiring for Damper Actuators and Control Valves W547_2_11 Proportional, 24V, 120V or 230V Actuator: SY2…5-24MFT SY2...12-120MFT SY2...12-230MFT Hazard Identification INSTALLATION NOTES 7ARNINGSAND#AUTIONSAPPEARATAPPROPRIATESECTIONSTHROUGHOUT this manual. Read these carefully. /BSERVE#LASSAND#LASSWIRINGRESTRICTIONS CAUTION 4RANSFORMERSIZING39ACTUATORDRAW8SAFETYMARGIN %X39REQUIRES!X!!86!#6!4RANSFORMER Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. APPLICATION NOTES Indicates an action or condition that may cause irreversible damage to the actuator(s) or associated equipment. %QUIPMENTDAMAGE 0OWERCONSUMPTIONANDINPUTIMPEDANCEMUSTBEOBSERVED NOTES SY2...5-24MFT 34 Ground shielded wire at control panel chassis. Tape back ground at actuator. 36 Use of feedback is optional. NOTES SY2...12-120MFT (230MFT) Each actuator should be powered by a single, isolated 33 control transformer. sCaution:0OWERSUPPLYVOLTAGE s0OWERSUPPLY#OM.EUTRALAND#ONTROL3IGNAL "–" wiring to a common is prohibited. PC Tool Service Jack Control Signal Feedback N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. 36 34 Control Signal (+) Y Control Signal (-) ŏ1 Feedback Signal (+) U5 Feedback Signal (-) ŏ2 Not Used - C1 Not Used - C2 A Internal Use Only B Internal Use Only 1 Internal Use Only 2 Internal Use Only 3 Internal Use Only ŏ /- Power Supply Com ~/+ Power Supply Hot 8 Internal Use Only 9 Internal Use Only 10 Internal Use Only 24V AC/DC Address 33 Adaption Y2 SYx-24MFT Y1 PE G Power Supply Com – 120v (N) / 230v (L1) Power Supply Hot – 120v (H) / 230v (L2) N Control Signal Feedback 36 34 A L PC Tool Service Jack F Internal Use Only 1 Internal Use Only Y Control Signal (-) ŏ1 2 Internal Use Only Feedback Signal (+) U5 3 Internal Use Only Feedback Signal (-) ŏ2 Not Used - C1 Not Used - C2 8 Internal Use Only 9 Internal Use Only 10 Internal Use Only Adaption Address LS3 B E Internal Use Only B Control Signal (+) Y1 C A SYx-120MFT SYx-230MFT !"/PEN)NDICATION #ONTACT2ATING !6!#-AX !6!#-AX G Y2 PE LS4 !%#LOSED)NDICATION SY2...5-24MFT SY2...12-120MFT (230MFT) 800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN 31 Wiring for Damper Actuators and Control Valves W549_11 On/Off, 24V, 120 or 230V SY Actuator Wiring Diagram, SY1…5-24 – Multiple Wiring SY1…12-110 (220) – Multiple Wiring Hazard Identification INSTALLATION NOTES Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. Observe class 1 and class 2 wiring restrictions. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. Transformer sizing = SY actuator draw X 1.25 (safety margin) (Ex. SY2-24 requires 3.0A x 1.25 = 3.75A, 3.75A X 24 VAC = 90VA Transformer). Indicates an action or condition that may cause irreversible damage to the actuator(s) or associated equipment. Equipment damage! Power consumption and input impedance must be observed. Line Voltage G Open K1 * Close K1-B Actuator B G Ground 1 Common G 120 or 230 VAC N L1 Open 3 Open 4 5 6 Closed 7 A K1-B HTR 1 Common 3 Open 4 Closed 5 6 7 A LS3 B B A-C (Open Indication) C D LS4 E F * Actuator A Ground 1 Common Open 4 Closed 4 Closed 5 6 HTR D A-C (Open Indication) C E F A-B (Open Indication) Contact Rating: 5A 125 VAC Max. 3A 250 VAC Max. C D LS4 A-E (Closed Indication) SY1 -24 F LS3 A-C (Open Indication) LS4 E D-F (Closed Indication) Contact Rating: 5A 250 VAC Max. SY2…5-24 F D-F (Closed Indication) Contact Rating: 5A 250 VAC Max. SY2…12-110 (220) A-B (Open Indication) Contact Rating: 5A 125 VAC Max. 3A 250 VAC Max. E LS4 B HTR C E F 7 A LS3 C B Actuator A K1-A B B Ground 3 A LS3 G Common 7 A G Open 6 LS3 SY2…12-110 (220) 1 5 A LS4 D-F (Closed Indication) 3 K1-A * The isolation relays may not be needed. Dependent on signal LS3 A-C (Open Indication) Contact Rating: 5A 250 VAC Max. SY2…5-24 G HTR E D-F (Closed Indication) Contact Rating: 5A 250 VAC Max. G Actuator B C D F Ground K1 H L2 Close G LS4 A-E (Closed Indication) SY1-110 (220) SY1 Contact Arrangements 800-543-9038 USA 32 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. 24V AC Transformer NOTES sCaution: Power Supply Voltage. s)SOLATIONRELAYSMUSTBEUSEDINPARALLELCONNECTIONOFMULTIPLEACTUATORS using a common control signal input. s(,CANNOTBECONNECTEDTOTERMINALANDSIMULTANEOUSLY sRequired: 4ERMINALNEEDSTOBEFIELDWIREDTOENABLEHEATERCIRCUIT Wiring for Control Valves W550_11 Proportional, 24V SY Actuator Wiring Diagram, SY1-24P – Multiple Wiring Hazard Identification Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. 33 24V AC/DC Transformer G Line Voltage CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. 35 Indicates an action or condition that may cause irreversible damage to the actuator(s) or associated equipment. Actuator B G Ground 4 Power Supply Com 5 Power Supply Hot 6 Control Signal (-) 7 Control Signal (+) 8 Internal Use Only 9 Internal Use Only 10 Internal Use Only Feedback (B) Equipment damage! Power consumption and input impedance must be observed. 11 Feedback (-) 12 Feedback (+) 36 A LS3 B C A-B (Open Indication) Contact Rating: 5A 125 VAC Max. 3A 250 VAC Max. E INSTALLATION NOTES F Observe class 1 and class 2 wiring restrictions. Transformer sizing = SY actuator draw X 1.25 (safety margin) (Ex. SY2-24 requires 3.0A x 1.25 = 3.75A, 3.75A X 24 VAC = 90VA Transformer). N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. NOTES SY1-24P Each actuator should be powered by a single, isolated 33 control transformer. 33 24V AC/DC Transformer G Line Voltage 35 s$ONOTCHANGESENSITIVITYORDIPSWITCHSETTINGSWITH power applied. Actuator A G Ground 4 Power Supply Com 5 Power Supply Hot 6 Control Signal (-) 7 Control Signal (+) 8 Internal Use Only 9 Internal Use Only 10 Internal Use Only Control Signal APPLICATION NOTES Feedback (A) 11 Feedback (-) 12 Feedback (+) 36 A 36 A-E (Closed Indication) SY1 -24P sSY1-24P notes: Power supply Com/Neutral and Control Signal "–" wiring to a common is prohibited. Terminals 4 and 6 need to be wired separately otherwise irreversible damage will occur. 35 LS4 Recommended twisted shielded pair for control wiring. Ground shielded wire at control panel chassis. Tape back ground at actuator. LS3 B C E Use of feedback is optional. F A-B (Open Indication) Contact Rating: 5A 125 VAC Max. 3A 250 VAC Max. LS4 A-E (Closed Indication) SY1 -24P 800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN 33 Wiring for Control Valves Actuators: SY2...5-24MFT Hazard Identification INSTALLATION NOTES Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. Observe class 1 and class 2 wiring restrictions. CAUTION Transformer sizing = SY actuator draw X 1.25 (safety margin) (Ex. SY2-24 requires 3.0A x 1.25 = 3.75A, 3.75A X 24 VAC = 90VA Transformer). Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. NOTES SY2...5-24MFT Indicates an action or condition that may cause irreversible damage to the actuator(s) or associated equipment. Each actuator should be powered by a single, isolated 33 control transformer. Equipment damage! Power consumption and input impedance must be observed. APPLICATION NOTES 35 Recommended twisted shielded pair for control wiring. Ground shielded wire at control panel chassis. Tape back ground at actuator. 36 Use of feedback is optional. Actuator A PC Tool Service Jack Feedback 36 35 Feedback 36 35 Power Supply Com ~/+ Power Supply Hot 8 Internal Use Only Feedback Signal (+) U5 Feedback Signal (-) ŏ2 Not Used - C1 Not Used - C2 24V AC/DC Address 33 Adaption Control Signal (+) Y Control Signal (-) ŏ1 Feedback Signal (+) U5 Feedback Signal (-) ŏ2 SYx-24MFT Y2 9 Internal Use Only 10 Internal Use Only A Internal Use Only B Internal Use Only 1 Internal Use Only 2 Internal Use Only 3 Internal Use Only ŏ /- Power Supply Com Not Used - C1 Not Used - C2 ~/+ Power Supply Hot 8 Internal Use Only 9 Internal Use Only 10 Internal Use Only Address Y2 24V AC/DC 33 Adaption Y1 G Internal Use Only ŏ1 C LS4 Internal Use Only 3 PE Control Signal D 2 Control Signal (-) PC Tool Service Jack A-C (Open Indication) Internal Use Only ŏ /- Actuator B LS3 Internal Use Only 1 Y G A Internal Use Only B Control Signal (+) Y1 B A SYx-24MFT PE E D-F (Closed Indication) F Contact Rating: 5A 250 VAC Max. SY2…5-24MFT 800-543-9038 USA 34 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. W550_2_11 Proportional, Multiple Wiring, 24V Wiring for Control Valves W552_1_11 Proportional, 120 or 230V Actuators: SY1-110P SY1-220P G Actuator B G Ground N L1 4 Power Supply Com H L2 5 Power Supply Hot CAUTION 6 Control Signal (-) Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. 7 Control Signal (+) 8 Internal Use Only 9 Internal Use Only Hazard Identification Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. 120 or 230 VAC 35 10 Internal Use Only Indicates an action or condition that may cause irreversible damage to the actuator(s) or associated equipment. 11 Feedback (-) Feedback (B) 12 Feedback (+) 36 Equipment damage! Power consumption and input impedance must be observed. A LS3 B C A-B (Open Indication) Contact Rating: 5A 125 VAC Max. 3A 250 VAC Max. E F INSTALLATION NOTES LS4 A-E (Closed Indication) SY1 -110P (220P) Observe class 1 and class 2 wiring restrictions. G APPLICATION NOTES N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. 35 36 Recommended twisted shielded pair for control wiring. Ground shielded wire at control panel chassis. Tape back ground at actuator. Use of feedback is optional. Control Signal 35 NOTES SY1-110P (220P) Actuator A G Ground 4 Power Supply Com 5 Power Supply Hot 6 Control Signal (-) 7 Control Signal (+) 8 Internal Use Only 9 Internal Use Only 10 Internal Use Only sCaution: Power supply voltage. Feedback (A) s$ONOTCHANGESENSITIVITYORDIPSWITCHSETTINGSWITH power applied. 11 Feedback (-) 12 Feedback (+) 36 A LS3 B C E F A-B (Open Indication) Contact Rating: 5A 125 VAC Max. 3A 250 VAC Max. LS4 A-E (Closed Indication) SY1 -110P (220P) 800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN 35 Wiring for Control Valves W552_2 Proportional, Multiple Wiring, 120/230V Actuators: SY2...12-120MFT SY2...12-230MFT Hazard Identification INSTALLATION NOTES Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. Observe class 1 and class 2 wiring restrictions. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. APPLICATION NOTES 35 Indicates an action or condition that may cause irreversible damage to the actuator(s) or associated equipment. 36 Equipment damage! Power consumption and input impedance must be observed. Recommended twisted shielded pair for control wiring. Ground shielded wire at control panel chassis. Tape back ground at actuator. Use of feedback is optional. NOTES SY2...12-120MFT (230MFT) sCaution: Power supply voltage. Power Supply Com – 120 VAC (N) / 230 VAC (L1) Power Supply Hot – 120 VAC (H) / 230 VAC (L2) N Internal Use Only 1 Internal Use Only Y Control Signal (-) ŏ1 2 Internal Use Only Feedback Signal (+) U5 3 Internal Use Only Feedback Signal (-) ŏ2 Not Used - C1 Not Used - C2 8 Internal Use Only 9 Internal Use Only 10 Internal Use Only Adaption Address Y1 PE G Internal Use Only B Control Signal (+) 36 35 A Y2 SYx-120MFT Actuator A SYx-230MFT Power Supply Com – 120 VAC (N) / 230 VAC (L1) Power Supply Hot – 120 VAC (H) / 230 VAC (L2) N Control Signal Feedback L PC Tool Service Jack A Internal Use Only B Internal Use Only 1 Internal Use Only Control Signal (+) Y Control Signal (-) ŏ1 2 Internal Use Only Feedback Signal (+) U5 3 Internal Use Only Feedback Signal (-) ŏ2 Not Used - C1 Not Used - C2 8 Internal Use Only 9 Internal Use Only 10 Internal Use Only 36 35 A LS3 Adaption Address B A-C (Open Indication) Y1 C G D PE Actuator B SYx-120MFT SYx-230MFT Y2 LS4 E F D-F (Closed Indication) Contact Rating: 5A 250 VAC Max. SY2...12-120MFT SY2...12-230MFT 800-543-9038 USA 36 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. Feedback L PC Tool Service Jack Wiring for Control Valves On/Off, 24V, 120V Actuators: ZONE 24NC ZONE120NC-S ZONE24NO ZONE24NC-S ZONE120NO-S ZONE24NO-S ZONE120NC ZONE120NO T-STAT L1(HOT) MOTOR L2 Motor Lead Color 24 120/230 Black Black Red Red TO AUXILIARY CIRCUIT N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. Built-in Auxiliary Switch (optional) (-S models) 800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN 37 W610_11 Wiring Diagrams for Fire and Smoke Damper Actuators Actuators: FSLF120(-S) US FSAF24(-S) US FSLF24(-S) US FSNF120(-S) US FSNF24(-S) US FSAF120(-S) US INSTALLATION NOTES Hazard Identification Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. 3 Actuators may also be powered by 24 VDC. CAUTION 13 Two built-in auxiliary switches (2xSPDT), for end position indication, interlock control, fan startup, etc. Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. 21 Provide overload protection and disconnect as required. 39 S4 makes to S6 when the actuator is powered open. 2 4 Equipment damage! Actuators may be connected in parallel. Power consumption and input impedance must be observed. Equipment damage! Actuators may be connected in parallel if not mechanically linked. Power consumption and input impedance must be observed. 40 Double insulated. 41 Two built-in auxiliary switches (2xSPST), for end position indication, interlock control, fan startup, etc. Wht APPLICATION NOTES 21 H 1 Neutral L1 2 Hot 3 Ground Meets cULus requirements without the need of an electrical ground connection. All on this page indicates temperature limit or relay. Blk 24V 120V N C No ground on 24 V models FSNF24 US FSNF120 US manual reset high 2 21 24V 120V C=Blk N=Wht 1 Common, Neutral Violet S1 H=Red L1=Blk 2 Hot Violet S2 41 NC 10° NO 85° 3 Ground No ground for 24V models FSLF24 US FSLF120 US 2 Gray S4 Gray S6 39 40 FSLF24-S US FSLF120-S US 24 VAC Transformer 21 Line Blk (1) Common Volts 21 Auxiliary Switch Wiring for FSNF24-S US, FSNF120-S US N N L1 H Red (2) + Hot 3 FSAF24 US 4 NC 5° 13 S3 NO S4 NC Blk (2) Hot 40 S5 S6 FSAF120 US 800-543-9038 USA S2 All White Tagged Wht (1) Neutral 120 VAC 38 S1 4 866-805-7089 CANADA 85° NO FSNF24-S FSNF120-S 203-791-8396 LATIN AMERICA / CARIBBEAN N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. Auxiliary Switch Wiring for FSLF24-S US, FSLF120-S US W611_11 Wiring Diagrams for Fire and Smoke Damper Actuators Actuators: FSAF24-BAL (-S) US FSAF24-SR US Auxiliary Switch Wiring for FSAF24-BAL-S US, FSAF24-SR-S US Hazard Identification Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. CAUTION S1 Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. S2 2 4 NC 10° 13 40 S3 NO Equipment damage! Actuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed. S4 Equipment damage! Actuators may be connected in parallel if not mechanically linked. Power consumption and input impedance must be observed. FSAF24-BAL-S US FSAF24-SR-S US NC S5 S6 30° to 90° NO Balancing Control Fire and Smoke APPLICATION NOTES 21 24 VAC Transformer Blk (1) Common Line Meets cULus or UL requirements without the need of an electrical ground connection. 2 (3) INSTALLATION NOTES N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. 37 3 Actuators may also be powered by 24 VDC. 6 Only connect common neg (-) leg of control circuits. 7 A 500 Ω resister converts the 4 to 20 mA control signal to 2 to 10 VDC. 13 Two built-in auxiliary switches (2xSPDT), for end position indication, interlock control, fan startup, etc. 21 Provide overload protection and disconnect as required. 37 Only connect Hot, Wire 2 to Wire 3 override controls. OVERRIDE CONTROL See technical documentation for typical methods. Override Open FSAF24-BAL 2 Proportional Control Fire and Smoke 21 24 VAC Transformer Blk (1) Common Line 40 3 Red (2) + Hot Volts 3 Red (2) + Hot Volts Wht (3) Y1 Input, 2 to 10V (–) Control Signal 2 to 10 VDC (+) Double Insulated All on this page indicates temperature limit or relay. Grn (5) U Output, 2 to 10V FSAF24-SR US manual reset high 21 2 24 VAC Transformer Auxiliary Switch Wiring for FSAF24-S US, FSAF120-S US Line Blk (1) Common Volts Violet Violet Ω S1 S2 NC (–) 41 4 to 20 mA Control Signal (+) 10° Gray S4 Gray S6 3 Red (2) + Hot 500 Ω Wht (3) Y1 Input, 2 to 10V 7 NC NO 30 to 90° FSAF24-S US FSAF120-S US 800-543-9038 USA (–) 2 to 10 VDC (+) Feedback Signal 6 Grn (5) U Output, 2 to 10V FSAF24-SR US 2 4 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN 39 N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. Notes 800-543-9038 USA 40 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. Notes 800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN 41 N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. Notes 800-543-9038 USA 42 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN G & O Thermal Supply 5435 N. Northwest Highway Chicago, IL 60630 Phone: 773-763-1300 With branches in IL Aireco Supply 9120 Washington Boulevard Savage, MD 20763-0414 Phone: 301-953-8800 With branches in MD, VA Industrial Controls Distributors LLC 1776 Bloomsbury Avenue Wanamassa, NJ 07712 Phone: 800-631-2112 With branches in GA, KY, IN, MA, ME, NC, NY, OH, PA, TN Amcon Controls, Inc. 11906 Warfield Street San Antonio,TX 78216 Phone: 210-349-6161 Houston, TX branch 713-464-7002 Mandeville, LA branch 985-624-3303 Applied Automation A Wilson Mohr Company 3186 South Washington Street, #230 Salt Lake City, UT 84115 Phone: 801-486-6454 Boston Aircontrols, Inc. 8 Blanchard Road Burlington, MA 01803 Phone: 781-272-5800 Charles D. Jones Co. 445 Bryant Street, Unit #1 Denver, CO 80204-4800 Phone: 800-777-0910 With branches in CO, MO, KS Climatic Control Div/ICD 5061 W. State Street Milwaukee, WI 53208 Phone: 800-242-1656 With branches in WI Cochrane Supply and Engineering, Inc. 30303 Stephenson Highway Madison Heights, MI 48071-1633 Phone: 800-482-4894 With branches in MI and Maumee, OH Columbus Temperature Control 1053 E. 5th Avenue Columbus, OH 43201 Phone: 800-837-1837 Controlco 985 3rd Street Oakland, CA 94607 Phone: 510-636-7900 With branches in CA, NV Control Products 9101 Jameel, Suite 130 Houston, TX 77447 Phone: 713-849-7200 Edward C. Smyers & Co. 223 Fort Pitt Boulevard Pittsburgh, PA 15222-1505 Phone: 412-471-3222 Engineered Control Systems 4805 N.W. 79th Avenue Suite 11 Miami, FL 33166 Phone: 305-418-8901 With branches in FL Interstate HVAC Controls 30 Vineland Street Brighton, MA 02135 Phone: 617-782-9000 Jackson Controls 1708 E. 10th Street Indianapolis, IN 46201 Phone: 317-231-2200 M & M Controls 9E West Aylesbury Road Timonium, MD 21093 Phone: 410-252-1221 With a branch in Alexandria, VA MICONTROLS, Inc. 6516 5th Place South Seattle, WA 98124 Phone: 800-877-8026 With branches in WA, OR Meier Supply 123 Brown Street Johnson City, NY 13790 Phone: 607-797-7700 With branches in NY, PA Minvalco, Inc. 3340 Gorham Avenue Minneapolis, MN 55426-4267 Phone: 952-920-0131 With branches in MN RSD/Refrigeration Supply Distribution 26021 Atlantic Ocean Drive Lake Forest, CA 92630 Phone: 949-380-7878 With branches in CA, NV, OR, AK, AZ, ID, UT, WA, MT Saint Louis Boiler Supply, Co. 617 Hanley Industrial Court St. Louis, MO 63144 Phone: 314-962-9242 South Side Control Supply, Co. 488 N. Milwaukee Avenue Chicago, IL 60610-3923 Phone: 312-226-4900 With branches in IL, IN Stromquist and Company 4620 Atlanta Road Smyrna, GA 30080 Phone: 404-794-3440 With a branch in Orlando, FL Temperature Control Systems 10315 Brockwood Road Dallas, TX 75238 Phone: 214-343-1444 With branches in OK, TX Tower Equipment Co., Inc. 1320 West Broad Street Stratford, CT 06615 Phone: 800-346-4647 Twinco Supply Corporation 55 Craven Street Huntington Station, NY 11746-2143 Phone: 800-794-3188 With branches in NY Wilson-Mohr, Inc. 12610 West Airport Blvd, Suite 100 Sugarland, TX 77478 Phone: 281-295-8850 CANADA ACR Supply Company Inc. 4040 S. Alston Avenue Durham, NC 27713 Phone: 919-765-8081 With branches in NC For a complete list of distributors in Canada, please visit our website: www.belimo.ca or call toll free: 866-805-7089 LATIN AMERICA AND THE CARIBBEAN USA Belimo Platinum Distributors For a complete list of distributors in Latin America and the Caribbean, please visit our website: www.belimo.us or call: 203-791-8396 Belimo worldwide: www.belimo.com BELIMO Americas USA Locations, 43 Old Ridgebury Road, Danbury, CT 06810 Tel. 800-543-9038, Fax 800-228-8283, marketing@us.belimo.com 1049 Fortunado Loop, Sparks, NV 89436 Tel. 800 987-9042, Fax 800-987-8875, marketing@us.belimo.com Canada Locations, 14/16 – 5716 Coopers Avenue, Mississauga, Ontario L4Z 2E8 Tel. 866-805-7089, Fax 905-712-3124, marketing@us.belimo.com Latin America and the Caribbean Customer Service, Tel. 203-791-8396, Fax 203-791-9139, marketing@us.belimo.com