NS253 Termination of Wiring in Substation Protection and
Transcription
NS253 Termination of Wiring in Substation Protection and
Network Standard NETWORK NW000-S0038 NW000-S0038 Document No Amendment No Approved By Approval Date Review Date : : : : : NW000-S0038 0 Chief Engineer 26/06/2015 26/06/2018 NS253 TERMINATION OF WIRING IN SUBSTATION PROTECTION AND CONTROL EQUIPMENT UNCONTROLLED IF PRINTED Page 1 of 28 NS253 Termination of wiring in substation protection and control equipment Amendment No 0 ISSUE For issue to all Ausgrid and Accredited Service Providers’ staff involved with the termination of wiring in substation protection and control equipment, and is for reference by field, technical and engineering staff. Ausgrid maintains a copy of this and other Network Standards together with updates and amendments on www.ausgrid.com.au. Where this standard is issued as a controlled document replacing an earlier edition, remove and destroy the superseded document DISCLAIMER As Ausgrid’s standards are subject to ongoing review, the information contained in this document may be amended by Ausgrid at any time. It is possible that conflict may exist between standard documents. In this event, the most recent standard shall prevail. This document has been developed using information available from field and other sources and is suitable for most situations encountered in Ausgrid. Particular conditions, projects or localities may require special or different practices. It is the responsibility of the local manager, supervisor, assured quality contractor and the individuals involved to make sure that a safe system of work is employed and that statutory requirements are met. Ausgrid disclaims any and all liability to any person or persons for any procedure, process or any other thing done or not done, as a result of this Standard. All design work, and the associated supply of materials and equipment, must be undertaken in accordance with and consideration of relevant legislative and regulatory requirements, latest revision of Ausgrid’s Network Standards and specifications and Australian Standards. Designs submitted shall be declared as fit for purpose. Where the designer wishes to include a variation to a network standard or an alternative material or equipment to that currently approved the designer must obtain authorisation from the Network Standard owner before incorporating a variation to a Network Standard in a design. External designers including those authorised as Accredited Service Providers will seek approval through the approved process as outlined in NS181 Approval of Materials and Equipment and Network Standard Variations. Seeking approval will ensure Network Standards are appropriately updated and that a consistent interpretation of the legislative framework is employed. Notes: 1. Compliance with this Network Standard does not automatically satisfy the requirements of a Designer Safety Report. The designer must comply with the provisions of the Workplace Health and Safety Regulation 2011 (NSW - Part 6.2 Duties of designer of structure and person who commissions construction work) which requires the designer to provide a written safety report to the person who commissioned the design. This report must be provided to Ausgrid in all instances, including where the design was commissioned by or on behalf of a person who proposes to connect premises to Ausgrid’s network, and will form part of the Designer Safety Report which must also be presented to Ausgrid. Further information is provided in Network Standard (NS) 212 Integrated Support Requirements for Ausgrid Network Assets. 2. Where the procedural requirements of this document conflict with contestable project procedures, the contestable project procedures shall take precedent for the whole project or part thereof which is classified as contestable. Any external contact with Ausgrid for contestable works projects is to be made via the Ausgrid officer responsible for facilitating the contestable project. The Contestable Ausgrid officer will liaise with Ausgrid internal departments and specialists as necessary to fulfil the requirements of this standard. All other technical aspects of this document which are not procedural in nature shall apply to contestable works projects. INTERPRETATION In the event that any user of this Standard considers that any of its provisions is uncertain, ambiguous or otherwise in need of interpretation, the user should request Ausgrid to clarify the provision. Ausgrid’s interpretation shall then apply as though it was included in the Standard, and is final and binding. No correspondence will be entered into with any person disputing the meaning of the provision published in the Standard or the accuracy of Ausgrid’s interpretation. KEYPOINTS This standard has a summary of content labelled “KEYPOINTS FOR THIS STANDARD”. The inclusion or omission of items in this summary does not signify any specific importance or criticality to the items described. It is meant to simply provide the reader with a quick assessment of some of the major issues addressed by the standard. To fully appreciate the content and the requirements of the standard it must be read in its entirety. AMENDMENTS TO THIS STANDARD Where there are changes to this standard from the previously approved version, any previous shading is removed and the newly affected paragraphs are shaded with a grey background. Where the document changes exceed 25% of the document content, any grey background in the document is to be removed and the following words should be shown below the title block on the right hand side of the page in bold and italic, for example, Supersedes – document details (for example, “Supersedes Document Type (Category) Document No. Amendment No.”). NW000-S0038 UNCONTROLLED IF PRINTED Page 2 of 28 KEY POINTS OF THIS STANDARD Scope and Risks Addressed Terminals Lugs and cable terminations This s This standard is limited to scope identified below and provides controls for associated risks as listed below: This section defines the terminal styles in use for different applications and includes review of terminals for: The lugs and cable terminations to be used within Ausgrid are defined in this section. The section includes: Terminals for Protection Relays, SCADA, Battery Links, Test Links, and Fuse Bases. Lugs and cable terminations. Crimping Techniques Protection SCADA Battery terminals Crimping This section identifies the type of crimping tool to be used for different types of terminations/lugs. Approved lug types Cable termination methodologies Where to for more information? Where to for more information? Where to for more information? Section 5.2 Section 5.3 Section 5.4 Where to for more information? Tools and Forms Tools and Forms Tools and Forms Section 1, 2 Annexure A – Lug stock codes Annexure C – Relay specific terminations Annexure B – Crimping tools Annexure D – Sample Compliance Checksheet NW000-S0038 UNCONTROLLED IF PRINTED Page 3 of 28 NS253 Termination of wiring in substation protection and control equipment Amendment No 0 Network Standard NS253 Termination of Wiring in Substations Protection and Control Equipment Contents 1.0 PURPOSE ............................................................................................................................................. 5 2.0 SCOPE .................................................................................................................................................. 5 3.0 REFERENCES ...................................................................................................................................... 5 3.1 Ausgrid documents .................................................................................................................... 5 3.2 Other standards and documents................................................................................................ 5 3.3 Acts and regulations................................................................................................................... 5 4.0 DEFINITIONS ........................................................................................................................................ 6 5.0 TERMINATION OF WIRING .................................................................................................................. 7 5.1 General ...................................................................................................................................... 7 5.2 Terminals ................................................................................................................................... 7 5.2.1 Protection ....................................................................................................................... 7 5.2.2 SCADA ........................................................................................................................... 7 5.2.3 Moulded battery or test links .......................................................................................... 8 5.2.4 Red spot back stud connected fuse holder .................................................................. 10 5.3 Lugs and cable terminations .................................................................................................... 11 5.3.1 Lugs .............................................................................................................................. 11 5.3.2 Cable terminations ....................................................................................................... 12 5.4 Crimping ................................................................................................................................... 13 6.0 RECORDKEEPING ............................................................................................................................. 14 7.0 AUTHORITIES AND RESPONSIBILITIES .......................................................................................... 14 8.0 DOCUMENT CONTROL...................................................................................................................... 14 ANNEXURE A - LUG STOCK CODES ........................................................................................................... 15 ANNEXURE B - CRIMPING TOOLS ............................................................................................................... 16 ANNEXURE C - RELAY SPECIFIC TERMINATIONS .................................................................................... 18 ANNEXURE D – SAMPLE COMPLIANCE CHECKLIST ................................................................................ 27 NW000-S0038 UNCONTROLLED IF PRINTED Page 4 of 28 NS253 Termination of wiring in substation protection and control equipment 1.0 Amendment No 0 PURPOSE The purpose of this standard is to standardise the types of cable termination methods, lugs, and crimping tools used across the Ausgrid Network in the wiring of substation control and protection panels and other related substation equipment. 2.0 SCOPE The following is included: New work Secondary wiring lugs, terminals, links, fuse holders, and the associated crimping tools to be used The following is not included: The wiring in equipment supplied to Ausgrid covered by purchase orders or period contracts in which the method of wiring has been approved as part of the contract. 3.0 REFERENCES All work covered in this document shall conform to all relevant Legislation, Standards, Codes of Practice and Network Standards. Current Network Standards are available on Ausgrid’s Internet site at www.ausgrid.com.au. 3.1 Ausgrid documents 3.2 Company Form (Governance) - Network Document Endorsement and Approval Company Procedure (Governance) - Network Document Endorsement and Approval Company Procedure (Network) - Production / Review of Network Standards Electrical Safety Rules Electricity Network Safety Management System Manual NS181 Approval of Materials and Equipment and Network Standard Variations NS203 Telecommunications: Master Policy Document NS212 Integrated Support Requirements for Ausgrid Network Assets NS252 Requirements for wiring within panels NS261 Requirement for Design Compliance Framework for Network Standards Other standards and documents ENA Doc 001-2008 National Electricity Network Safety Code WSI302 Manufacture of Protection Panels 3.3 Acts and regulations Electricity Supply (General) Regulation 2014 (NSW) Electricity Supply (Safety and Network Management) Regulation 2014 Work Health and Safety Act 2011 and Regulation 2011 NW000-S0038 UNCONTROLLED IF PRINTED Page 5 of 28 NS253 Termination of wiring in substation protection and control equipment 4.0 Amendment No 0 DEFINITIONS Accredited Service Provider (ASP) An individual or entity accredited by the NSW Government Trade & Investment in accordance with the Electricity Supply (Safety and Network Management) Regulation 2014 (NSW). Business Management System (BMS) An Ausgrid internal integrated policy and procedure framework that contains the approved version of documents. Crimp An electrical connector that is compressed onto a conductor Document control Ausgrid employees who work with printed copies of document must check the BMS regularly to monitor version control. Documents are considered “UNCONTROLLED IF PRINTED”, as indicated in the footer. Lug A conducting fitting that can be connected to an electrical conductor Network Standard A document, including Network Planning Standards, that describes the Company's minimum requirements for planning, design, construction, maintenance, technical specification, environmental, property and metering activities on the distribution and transmission network. These documents are stored in the Network Category of the BMS repository. Panel The cubicle in/onto which protection and control equipment is mounted. Panel may also refer specifically to the front sheet metal to which relays are mounted and then fixed to the rest of the cubicle. Review date The review date displayed in the header of the document is the future date for review of a document. The default period is three years from the date of approval however a review may be mandated at any time where a need is identified. Potential needs for a review include changes in legislation, organisational changes, restructures, occurrence of an incident or changes in technology or work practice and/or identification of efficiency improvements. Terminal A point of connection for closing an electric circuit NW000-S0038 UNCONTROLLED IF PRINTED Page 6 of 28 NS253 Termination of wiring in substation protection and control equipment 5.0 TERMINATION OF WIRING 5.1 General Amendment No 0 A basic summary of the requirements in this document is as follows: Compression type solderless lugs shall be used at the terminations of all stranded wires. The termination of bare wire strands into terminals is not permitted. The lugs shall be manufactured from high conductivity seamless copper tube stock and the correct size lug shall be used to suit the wire size. All lugs shall be crimped with the correct compression crimping tool recommended by the lug manufacturer. The shank of the lug shall be protected by insulating tubing to prevent direct or accidental contact with adjacent terminations. Under no circumstances shall lugs be bent, filed, cut or modified in any way to fit a termination. The lug’s insulation shall not be removed. On completing all crimps a visual inspection and pull test should be carried out to ensure that there is no movement of the wire inside the ferrule within the crimped connection. All crimped indents shall be on the top of the lug and visible. 5.2 Terminals 5.2.1 Protection For details of protection terminals see Ausgrid layout and wiring diagrams. In most instances, Utilux H3820 terminals are employed for protection wiring, including DC. Figure 1: H3820 Terminals 5.2.2 SCADA SCADA wiring is generally a smaller cross sectional area (CSA) than control and protection cabling and hence Utilux H3820 terminals are not used as terminals for SCADA. Weidmuller type terminals are generally used for termination of SCADA. Weidmuller terminals are used for SCADA wiring, examples of common types are listed below: SAKR – link terminal ASK1 – fuse terminal NW000-S0038 UNCONTROLLED IF PRINTED Page 7 of 28 NS253 Termination of wiring in substation protection and control equipment Amendment No 0 SAK 2.5 – terminal up to 2.5mm² wire SAK 4 – terminal up to 4mm² wire AKZ 4 – terminal up to 4mm² wire AKZ 4L – terminal up to 4mm² wire with solder tag EKZ 4 – earth terminal up to 4mm² wire Figure 2: SAKR Terminals 5.2.3 Moulded battery or test links Test links and battery links are to be mounted so if the sliding section is loosened, it will fall to the open position. Most protection panels use moulded battery or test links. The links shall be installed as shown in Figure 3. The links can be obtained from Ausgrid store, with the stock code shown in Annexure A. All terminations to moulded battery or test links shall use the nut/washer combination as outlined in Figure 4. NW000-S0038 UNCONTROLLED IF PRINTED Page 8 of 28 NS253 Termination of wiring in substation protection and control equipment Amendment No 0 Figure 3: Moulded type link assembly Figure 4: Connections on to a stud When terminated all connections must have at least 1 thread of the stud protruding from the end of the nut. All lug terminations nuts shall be torqued to 4nm utilising a torque wrench. All fixing such as washers and nuts are to be stainless steel S.S AISI 304, spring washers are to be stainless steel S.S AISI 316. The front of all links should be checked to ensure that all washers are present, nuts are free to move and sliding link will fall open. There have been instances of the stainless steel nuts locking onto the 6mm threads by the process of galling. The incorrect use of battery drills, that is using battery drills on high speed to attach nuts, will cause galling. The back panel link assembly holding nut is to be checked for tightness using a PE test spanner which is displayed in Figure 5. The tightness is to be checked only when the cable connections have been made. Figure 5: PE test spanner NW000-S0038 UNCONTROLLED IF PRINTED Page 9 of 28 NS253 Termination of wiring in substation protection and control equipment Amendment No 0 Figure 6: PE Test Spanner being used to check back panel holding nut Figure 7: PE Test Spanner being used to check back panel holding nut 5.2.4 Red spot back stud connected fuse holder Wiring connected to the 6 millimetre stud employing the same techniques as for the moulded test links. Red spot fuses are supplied with brass half nuts, these are to be replaced with full brass nuts. NW000-S0038 UNCONTROLLED IF PRINTED Page 10 of 28 Amendment No 0 NS253 Termination of wiring in substation protection and control equipment Figure 8: Red spot back stud connected fuse holder 5.3 Lugs and cable terminations 5.3.1 Lugs The lugs and terminals used throughout Ausgrid in particular for relays and terminal blocks require specific types of lugs to be used as outlined in Annexure A. Under no circumstances should lugs be modified in any way to fit a termination. This includes bending the lugs; all lugs used are to be pre – insulated. 5.3.1.1 Solid barrel lugs As a rule all protection cabling shall be terminated using solid barrel lugs , this type of lug used in Ausgrid is the Utilux heavy duty lug which is available in flat or 90 degree palm. H series lugs must be used when terminating to stud type terminal blocks and relays. In some cases this is not possible as Utilux and other manufacturers do not make a heavy duty pre-insulated straight lug with a 4.1mm hole therefore ring terminal lugs outlined in Figure 9 may be used. 5.3.1.2 Split lugs double grip Double grip Split lugs are permitted if constructed as in Figure 9 and are to be used on control wiring only, these lugs are manufactured by Utilux and Cabac and wire sizes are colour coded. RED = 1.5mm BLUE = 2.5mm YELLOW = 6mm These lugs are available in ring terminal, fork spade, lip blade, flat blade, pin blade and bootlace ferrules. NW000-S0038 UNCONTROLLED IF PRINTED Page 11 of 28 NS253 Termination of wiring in substation protection and control equipment Amendment No 0 5.3.1.3 Crimp links / in-line splice Under no circumstances will jointing or splicing of control or CT cables be allowed. Control and CT cables should be continuous from source to destination; however where continuous cables are not practicable connection shall be achieved via terminal blocks in a marshalling cubicle. 5.3.2 Cable terminations Cables shall be terminated in the following way: Stranded conductors shall be terminated by means of approved pre-insulated crimpable circular lugs. The Conductive parts of all terminations shall comprise of copper material with tinned electroplating to avoid corrosion build up. Figure 9 shows the construction and various types of these terminations. With the exception of bootlace terminations, the remaining terminations shall be constructed from: Solid barrel heavy duty type such as the Utilux H series or A two stage crimpable copper material such as the Utilux or Cabac colour coded lugs. For the two stage crimpable copper material, the first stage comprising of a main conducting part, shall fit stranded conductor, and the second stage, comprising of a copper barrel sleeved over the main conducting barrel, shall fit the cable insulation to provide a strong grip to the cable end. Special application terminals such as pre-insulated right angle or L circular ring terminals used for Midos or similar protection range, and pre-insulated quick fork terminals are also acceptable. For dual cable connections, circular lugs may be used. Quick fork lugs may only be used when captive type screws are present on the clamping unit of terminal blocks. See Annexure A for the lug stock codes. The size of each termination shall be suitable for the size of the conductor required for the connection. The terminations shall be crimped with the correct crimping tool as per manufacturer’s recommendations. Washers and spring washers or other approved locking devices shall be used on all terminations. See Annexure C for the relay specific terminations and maximum number of connections per terminal. Cable insulation shall be stripped using the appropriate wire strippers (pliers and side cutters are not permitted to strip insulation). Each cable core shall have sufficient spare length to allow for replacement of the crimp lug if required. On completion all crimped terminations shall be subject to a pull test to check the integrity of the crimp. Refer to NS252 ‘Requirements for wiring within panels’ for standards on cabinet and panel wiring. NW000-S0038 UNCONTROLLED IF PRINTED Page 12 of 28 NS253 Termination of wiring in substation protection and control equipment Amendment No 0 Figure 9: Recommended crimpable pre-insulated cable terminations Figure 10: Recommended method of crimping pre insulated cable termination 5.4 Crimping All lugs shall be crimped with the correct crimping tool for the lug type and size intended to be used and recommended by the lug manufacturer or as approved for use by Ausgrid. Refer to Figure 10 for correct stripping procedure. A list of manufacturers approved crimpers and the lugs they’re designed for can be found in Annexure B. On solid lugs i.e. Utilux Heavy duty the crimp should be made in the middle of the top side of lug to ensure correct crimping is achieved. On completing all crimps a visual inspection and pull test shall be carried out to ensure that there is no movement of the wire inside the ferrule within the crimped connection. The lug shall then be marked with a marking pen to indicate that it has been checked. NW000-S0038 UNCONTROLLED IF PRINTED Page 13 of 28 Amendment No 0 NS253 Termination of wiring in substation protection and control equipment 6.0 RECORDKEEPING The table below identifies the types of records relating to the process, their storage location and retention period. Table 1 – Recordkeeping Type of Record Storage Location Retention Period* Approved copy of the network standard BMS Network sub process Standard – Company Unlimited Draft Copies of the network standard during amendment/creation TRIM Work Folder for Network Standards (Trim ref. 2014/21250/20) Unlimited Working documents (emails, memos, impact assessment reports, etc.) TRIM Work Folder for Network Standards (Trim ref. 2014/21250/20) Unlimited * The following retention periods are subject to change eg if the records are required for legal matters or legislative changes. Before disposal, retention periods should be checked and authorised by the Records Manager. 7.0 AUTHORITIES AND RESPONSIBILITIES For this network standard the authorities and responsibilities of Ausgrid employees and managers in relation to content, management and document control of this network standard can be obtained from the Company Procedure (Network) – Production/Review of Network Standards. The responsibilities of persons for the design or construction work detailed in this network standard are identified throughout this standard in the context of the requirements to which they apply. 8.0 DOCUMENT CONTROL Content Coordinator : Manager - Secondary Systems Distribution Coordinator : Engineering Information and Services Manager NW000-S0038 UNCONTROLLED IF PRINTED Page 14 of 28 NS253 Termination of wiring in substation protection and control equipment Amendment No 0 Annexure A - Lug Stock codes Table A1 - Utilux Heavy duty Pre-insulated Terminal style Stock code 2.5 sq mm Flat blade 5.1mm hole 74773 2.5 sq mm Right angle narrow blade 4.1mm hole 180036 2.5 sq mm Right angle standard blade 4.1 mm hole 74856 M6 hole 74781 Table A2 - Ring terminals for M4 Relay Bases Terminal style Stock code Red 0.25mm – 1.65mm conductor 181397 Blue 1.04mm – 2.63mm conductor 181398 Table A3 - Battery Trip Links Terminal style Stock code Moulded Battery Trip Links NW000-S0038 78493 UNCONTROLLED IF PRINTED Page 15 of 28 NS253 Termination of wiring in substation protection and control equipment Amendment No 0 Annexure B - Crimping Tools B1 Usage of crimping tools The following table is a list of manufacturers approved crimpers for designed lugs. This is meant as a guide only. Table B1 - Approved usage of crimp tools Lug Crimping Tool Utilux Heavy Duty Lug Utilux 120/A1 (Figure B2) Utilux Split Colour Coded Lugs Utilux #120 or #102 Utilux Bootlace Ferrule Utilux #125 Cabac Bootlace Ferrule Cabac HNKE5 or HNKE4 Cabac Split Colour Coded Lugs Cabac KTC1 – HP3 or HP3/1 (Figure B1) B2-Cabac KTC1 crimping tool for colour coded lugs Figure B1 – Cabac KTC1 crimping tool NW000-S0038 UNCONTROLLED IF PRINTED Page 16 of 28 NS253 Termination of wiring in substation protection and control equipment Amendment No 0 B3 Utilux 120A/1 crimping tool Suitable for 1.5, 2.5,4 and 6mm pre-insulated heavy duty lugs Figure B2 – Utilux 120A/1 crimping tool NW000-S0038 UNCONTROLLED IF PRINTED Page 17 of 28 NS253 Termination of wiring in substation protection and control equipment Amendment No 0 Annexure C - Relay Specific Terminations C1 Table of relay terminals Manufacturer Relay Type Termination Type Lug Max No. Connections GE C70 Screw Screw and Plate 90° Ring/Blade Bootlace 2 2 GE L90 Screw Screw and Plate 90° Ring/Blade Bootlace 2 2 GE T60 Screw Screw and Plate 90° Ring/Blade Bootlace 2 2 RMS 2C63K12 Screw 90° Ring 2 RMS 2V164 Screw 90° Ring 2 RMS 3A32KXX Screw 90° Ring 2 RMS TR12 Screw 90° Ring 2 Schneider P142 Screw 90° Ring/Blade 2 Schneider P545 Screw 90° Ring/Blade 2 SEL SEL 241101 Screw Screw and Plate 90° Ring/Blade Bootlace 2 1 SEL SEL 2505 Screw and Plate Bootlace 2 SEL SEL 2506 Screw and Plate Bootlace 2 SEL SEL 25943C3XX Screw and Plate Bootlace 2 SEL SEL 259503C31X Screw and Plate Bootlace 2 SEL SEL 487E Screw and Plate Bootlace 2 SEL SEL 751 Screw Screw and Plate 90° Ring/Blade Bootlace 2 1 SEL SEL 787 Screw Screw and Plate 90° Ring/Blade Bootlace 2 1 Siemens 7SD610 Screw and Plate Bootlace 2 Tekron ITR D2-3K Screw and Plate Bootlace 1 Tekron TTM01-E T2-TL60NLA Screw and Plate Bootlace 1 NW000-S0038 UNCONTROLLED IF PRINTED Page 18 of 28 NS253 Termination of wiring in substation protection and control equipment Amendment No 0 C2 Common relay terminals Figure C1 Typical terminals of a Schneider relay Figure C2 Typical terminal connections of a Schneider relay NW000-S0038 UNCONTROLLED IF PRINTED Page 19 of 28 NS253 Termination of wiring in substation protection and control equipment Amendment No 0 Figure C3 Typical terminals of a GE relay Figure C4 Typical terminal connections of a GE relay NW000-S0038 UNCONTROLLED IF PRINTED Page 20 of 28 NS253 Termination of wiring in substation protection and control equipment Amendment No 0 Figure C5 Typical terminals of a Siemens relay Figure C6 Typical terminal connections of a Siemens relay NW000-S0038 UNCONTROLLED IF PRINTED Page 21 of 28 NS253 Termination of wiring in substation protection and control equipment Amendment No 0 Figure C7 Typical terminals of an SEL relay Figure C8 Typical terminal connections of a SEL relay NW000-S0038 UNCONTROLLED IF PRINTED Page 22 of 28 NS253 Termination of wiring in substation protection and control equipment Amendment No 0 Figure C9 Typical terminals of an RMS relay Figure c10 Typical terminal connections of an RMS relay NW000-S0038 UNCONTROLLED IF PRINTED Page 23 of 28 NS253 Termination of wiring in substation protection and control equipment Amendment No 0 Figure C11 Typical terminals of a Tekron relay . Figure C12 Typical terminal connections of a Tekron relay NW000-S0038 UNCONTROLLED IF PRINTED Page 24 of 28 NS253 Termination of wiring in substation protection and control equipment Amendment No 0 If two lugs need to be connected to the same terminal, they shall be connected in the following arrangements. Figure C13 Back-to-back Figure C14 On top same way (one straight one right angle) NW000-S0038 UNCONTROLLED IF PRINTED Page 25 of 28 NS253 Termination of wiring in substation protection and control equipment Amendment No 0 Figure C15 On top opposite way NW000-S0038 UNCONTROLLED IF PRINTED Page 26 of 28 NS253 Termination of wiring in substation protection and control equipment Amendment No 0 Annexure D – Sample Compliance Checklist NW000-S0038 UNCONTROLLED IF PRINTED Page 27 of 28 NS253 Termination of wiring in substation protection and control equipment NW000-S0038 UNCONTROLLED IF PRINTED Amendment No 0 Page 28 of 28