eritech si interceptor

Transcription

eritech si interceptor
SI INTERCEPTOR
Instruction Manual
ERITECH SI INTERCEPTOR
- I N ST R U CT I O N M A N UA L
ERITECH
SI INTERCEPTOR
Instruction Manual
www.erico.com
1
ERITECH SI INTERCEPTOR
- I N ST R U CT I O N M A N UA L
Installation Guidelines
➜ For full details on installing your SI
INTERCEPTOR, please refer to ERICO’s
technical notes and the French national
standard NFC17-102. It is also
recommended to adhere to local
standards for relevant local down
conductor and grounding requirements.
This manual is a guide to the Installation,
Operation and Maintenance of the
ERITECH® SI INTERCEPTOR Lightning
Protection System. It assumes that the
system to be installed has been designed by
an authorized ERICO representative. The
system design will include:
• Grounding systems design – a configuration should be designed as a result of
soil resistivity analysis.
Certification
The certification of the ERITECH SI
INTERCEPTOR installation must be
performed by an authorised ERICO
representative. This is done in conjunction
with issuing of a Certificate of Compliance,
which is available from your nearest ERICO
office. When this certificate has been
completed and signed, a copy must be
either taken by the ERICO representative or
sent to the nearest ERICO office. During the
process of certification, the following will
be checked:
• Downconductor routes - chosen to avoid
other services, maintain minimum
bending radii and minimize down
conductor run length.
• Downconductor securing requirements.
• LPSD - CAD analysis design software
which determines terminal placement,
mast & height requirements as well as
protection level calculation.
All of the above are recommended for a
successful installation. If there is any
doubt about any of the points
mentioned, please contact ERICO or its
nearest representative for clarification.
• Installation matches the Benji design.
• The integrity of the mast and any
associated brackets and fastenings.
Warning - Only attempt to
install the ERITECH® SI
INTERCEPTOR during
storm-free periods.
• Guying, anchor points and fastenings.
• Downconductor routing, securing and
seals.
• Ground termination of down-conductor.
➜ The SI INTERCEPTOR must be at least 2
meters higher than any other point on
the structure it is intended to protect.
• Grounding System.
• Labelling.
➜ The resistance of the lightning protection
grounding system must be less than 10
ohms. This should be measured without
downconductor(s) connected and without interconnection to other grounding
systems.
• Certificate of Compliance and Warranty
Card completed and returned.
• General mechanical check of all
fastenings.
2
www.erico.com
ERITECH SI INTERCEPTOR
- I N ST R U CT I O N M A N UA L
Operation and Maintenance
to the structure. Check that the guys are
secure and undamaged. Replace if
necessary. Check that all fastenings are
secure and tight.
The ERITECH® SI INTERCEPTOR lightning
protection system requires no user
operation and is completely automatic in
operation.
5. Look for signs of damage to the
downconductor (whether by lightning,
careless handling, vandalism or other
causes).
• The SI becomes active only during
storm activity.
• The system does not require any external
power requirements or replacement
components for normal operation.
6. Check that the Lightning Event Counter
is secure, if the display is registering a
reading, then record the reading and
date.
• It is essential that the ERITECH® SI
INTERCEPTOR Lightning Protection
System be regularly maintained.
Maintenance should be undertaken:
7. Ensure the grounding resistance is less
than 10 .
8. Check the continuity of all bonding
conductors
1. After each known strike to the SI
INTERCEPTOR or at least once per year.
2. If any changes have been made to the
structure, whether they be structural,
antennae or Building Maintenance Unit
additions, etc.
Installation Instructions
The recommended order of installation is as
follows:
Maintenance should be undertaken as
follows:
1. Full installation of the grounding system.
2. Full installation of the downconductor.
Do not attempt
maintenance during
potential lightning periods.
3. Termination of the downconductor to the
grounding system.
4. Terminate the top of the downconductor
to the SI INTERCEPTOR mast.
1. Check that the building is the same
physical shape and that no additional
structures such as antennae, advertising
signs, satellite dishes, Building
Maintenance Units or similar have been
installed within 2m (80in.) height of the
SI INTERCPTOR.
5. Raise the mast into position and secure.
2. Inspect the SI INTERCEPTOR to ensure
that it is not dented or physically
damaged in any way.
3. Inspect the Finial Tip on top of the SI
INTERCEPTOR to ensure that it is not
excessively burnt, deformed or missing.
4. Check that the mast is securely attached
www.erico.com
3
ERITECH SI INTERCEPTOR
- I N ST R U CT I O N M A N UA L
Typical MAST Installation Arrangement
For Cantilevered Mast
(range 2-4 metres)
SI-125, SI-140 or SI-60
TERMINATION
COUPLER
supplied with
ER1-1000-SS
or ER1-2000-SS
MAST
(ER1-1000-SS)
or (ER1-2000-SS)
TMC-SS
TMC-SS
LPC580
CABTIE-SS
MAST
OPTIONS
ER1-1000-SS
ER1-2000-SS
MAST
(ER2-2000-SS)
or (ER2-3000-SS)
1m
ALOF-1-GS
ER2-2000-SS
ER2-3000-SS
ER3-2000-SS
ER3-3000-SS
DOWNCONDUCTOR
Refer to your local
standard for downconductor
requirements.
4
www.erico.com
ERITECH SI INTERCEPTOR
- I N ST R U CT I O N M A N UA L
Typical MAST Installation Arrangement
For Cantilevered Mast
(range 4-6 metres)
SI-125, SI-140 or SI-60
TERMINATION
COUPLER
supplied with
ER1-1000-SS
or ER1-2000-SS
MAST
(ER1-1000-SS)
or (ER1-2000-SS)
MAST
(ER2-2000-SS)
or (ER2-3000-SS)
TMC-SS
TMC-SS
LPC580
CABTIE-SS
MAST
(ER3-2000-SS)
or (ER3-3000-SS)
MAST
OPTIONS
ER1-1000-SS
ER1-2000-SS
1m
MAST
(ER2-2000-SS)
or (ER2-3000-SS)
ALOF-1-GS
ER2-2000-SS
ER2-3000-SS
1m
ER3-2000-SS
ER3-3000-SS
DOWNCONDUCTOR
Refer to your local
standard for downconductor
i
t
www.erico.com
5
ERITECH SI INTERCEPTOR
- I N ST R U CT I O N M A N UA L
Typical MAST Installation Arrangement
For Guyed Mast
(range 3-5 metres)
S125, S140 or S160
MAST
(ER1-1000-SS)
or ER1-2000-SS)
TERMINATION
COUPLER
suppiled with
ER1-1000-SS
or ER1-2000-SS
Do not over-tension
Guy Wires
(Slightly sagging)
TMC-SS
TMC-SS
LPC580
Guy Kit
(GUY KIT 4)
Anchor Points
not supplied with
GUYKIT 4
CABTIE-SS
Mast
(ER2-3000-SS
or ER2-2000-SS)
Support Base
(ER2-BASE-SS)
MAST
OPTIONS
Preferred
Angle
45˚ - 60˚
4 Holes, Ø12.5mm
ER2-2000-SS
ER2-3000-SS
229mm
178mm
ER1-1000-SS
ER1-2000-SS
ER2-BASE-SS
ER3-2000-SS
ER3-3000-SS
DOWNCONDUCTOR
Refer to your local
standard for downconductor
requirements.
ER3-BASE-SS
6
www.erico.com
ERITECH SI INTERCEPTOR
- I N ST R U CT I O N M A N UA L
Typical MAST Installation Arrangement
For Guyed Mast
(range 5-8 metres)
S125, S140 or S160
MAST
(ER1-1000-SS)
or ER1-2000-SS)
TERMINATION
COUPLER
suppiled with
ER1-1000-SS
or ER1-2000-SS
MAST
(ER2-2000-SS)
or ER2-3000-SS)
Guy point
midway on
ER2 Series
mast
TMC-SS
TMC-SS
Do not over-tension
Guy Wires
(Slightly sagging)
LPC580
Guy Kit
(GUYKIT 7)
CABTIE-SS
Mast
(ER3-2000-SS
or ER3-3000-SS)
Anchor Points
not supplied with
GUYKIT 7
Support Base
(ER3-BASE-SS)
MAST
OPTIONS
Preferred
Angle
45˚ - 60˚
4 Holes, Ø12.5mm
ER2-2000-SS
ER2-3000-SS
229mm
178mm
ER1-1000-SS
ER1-2000-SS
ER2-BASE-SS
ER3-2000-SS
ER3-3000-SS
DOWNCONDUCTOR
Refer to your local
standard for downconductor
requirements.
ER3-BASE-SS
www.erico.com
7
ERITECH SI INTERCEPTOR
- I N ST R U CT I O N M A N UA L
Options De Support / Support Options / Opciones del Montaje
Option : 1
Opción : 1
ERICORE Downconductor
ERICORE Conducteur de descente
INTERCEPTOR
INTCPT-ADBUTT
MAST BUTT
ADAPTOR
LOCKSCREW
ERICORE
UPPER
TERMINATION
FRP MAST
P/No. INTCPT-ADBUTT (#702296)
Option : 2
Opción : 2
Standard Downconductor
Conducteur de descente
INTERCEPTOR
INTCPT-ADBUTT
MAST BUTT
ADAPTOR
LOCKSCREW
TERMLUGCOUP
ERICO
ALUMINIUM
TUBULAR MAST
P/No. TERMLUGCOUP (#701840)
8
www.erico.com
ERITECH SI INTERCEPTOR
- I N ST R U CT I O N M A N UA L
Options De Support / Support Options / Opciones del Montaje
Option : 3
Opción : 3
Standard Downconductor
Standard Conducteur de descente
INTERCEPTOR
INTCPT3
OR
INTCPT3SS
INTCPT-ADM3/4UNC
Note:
INTCPTADM3/4UNC
3/4"
UNC thread
Option : 4
Opción : 4
CONDUCTIVE MAST
P/No. INTCPT-ADM3/4UNC (#702299)
Standard Downconductor
Standard Conducteur de descente
INTERCEPTOR
INTCPT3
OR
INTCPT3SS
Note:
INTCPT-ADF2BSPF
2" British
Standard Pipe
thread.
INTCPT-ADF2NSP
2" (USA) National
Standard Pipe
thread.
www.erico.com
INTCPT-AMD2NPS
OR
INTCPT-ADMSBSPF
2" PIPE
P/No. INTCPT-ADF2BSPF (#702297)
P/No. INTCPT-ADF2NSP (#702298)
9
ERITECH SI INTERCEPTOR
- I N ST R U CT I O N M A N UA L
www.erico.com
5 YEAR LIMITED WARRANTY
This product has a limited warranty to be free from defects in materials and workmanship for a period of ten (5) years from the date of dispatch from the Manufacturer.
The Purchaser acknowledges that lightning is a natural event with statistical variation
in behavior and energy levels which may exceed product ratings, and 100% protection is not offered and cannot be provided for. Therefore the Manufacturer's liability is
limited to the repair or replacement of the product (at the Manufacturer's sole option)
which in its judgement has not been abused, misused, interfered with by any person
not authorized by the Manufacturer, or exposed to energy or transient levels exceeding the Manufacturer's specifications for the product. The product must be installed
and earthed (where applicable) in strict accordance with the Manufacturer's specifications and all relevant national Electricity and Safety Standards. The Manufacturer
and the Purchaser mutually acknowledge that the product by its nature may be subject to degradation as a consequence of the number and severity of surges and transients that it experiences in normal use and this warranty excludes such gradual or
sudden degradation. This warranty does not indemnify the Purchaser of the product
for any consequential claim for damages or loss of operations or service or profits.
Customers should contact their nearest ERICO agent to obtain a Product Repair
Authorization Number prior to making any claim under this warranty. This is only a
summary of the warranty given by the Manufacturer. The full text of the warranty is set
out in the Manufacturer's Conditions of Quotation and Sale.
10
www.erico.com
ERITECH SI INTERCEPTOR
- I N ST R U CT I O N M A N UA L
WARNING:
1. These products shall be used only as illustrated and recommended in product instruction sheets (additional
instruction sheets are available at www.erico.com). Misuse or misapplication may cause failure resulting in
possible property damage or bodily injury.
2. These products must be used only in the manner depicted in the illustrations that accompany them.
3. Failure to observe these specifications may cause product malfunctions resulting in property damage or bodily
injury. ERICO products at the time of shipment are warranted to conform to any applicable written description
furnished to the Buyer by ERICO, and to be free from defects in material and workmanship. NO OTHER WARRANTY,
WHETHER EXPRESSED OR IMPLIED, (INCLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS), SHALL
EXIST IN CONNECTION WITH THE SALE OR USE OF ANY ERICO PRODUCT.
4. All instructions must be completely followed to ensure proper and safe operation.
SAFETY WARNING:
SAFETY INSTRUCTIONS: All governing codes and regulations and those required by the job site must be observed.
Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the
application.Wear gloves to avoid splinters and cuts.
HAZARDOUS VOLTAGES EXIST INTERNAL TO THE SI INTERCEPTOR. THIS UNIT SHOULD BE INSTALLED
AND SERVICED ONLY BY QUALIFIED PERSONNEL IN CONFORMANCE WITH ALL GOVERNING CODES.
• The power supply to the SI INTERCEPTOR should always be turned (and locked) OFF before the unit is accessed for
any reason.
• Prior to installation, ensure that the SI INTERCEPTOR is of the correct voltage, current, phasing, frequency rating
and is the type recommended by the manufacturer of the power distribution system.
• All instructions must be followed to ensure proper and safe operation of the SI INTERCEPTOR.
• Failure to follow instructions or warnings may result in bodily injury, equipment damage or ineffective protection.
DANGER: Electrical shock or burn hazard. Installation of this SI INTERCEPTOR should only be made by qualified
personnel. Failure to lockout electrical power during installation or maintenance can result in fatal electrocution or
severe burns. Before making any connections to this electrical panel be sure that power has been removed from all
associated wiring, electrical panels, and other electrical equipment.
CAUTION: Check to make sure line voltage does not exceed SI INTERCEPTOR voltage requirement.
CAUTION: This unit must be installed in conformance with all governing codes and must be installed on the load side
of the main over-current protection.
Diagrams are for reference only. Schematics are representative of typical applications and are only to be used for
reference.
www.erico.com
11
www.erico.com
AUSTRALIA
GERMANY
POLAND
6 Chilvers Road
P.O. Box 148
Thornleigh (Sydney) NSW 2120
Australia
Phone 61-2-9479-8500
Fax 61-2-9484-9188
66851 Schwanenmuehle
Germany
Phone 49-6307-918-10
Fax 49-6307-918-150
ul. Krzemieniecka 17
54-156 Wroclaw
Poland
Phone 48-71-374-40-22
Fax 48-71-374-40-43
BELGIUM
HONG KONG
SINGAPORE
Postbus 33
3110 Rotselaar
Belgium
Phone 32-14-69-96-88
Fax 32-14-69-96-90
Unit 1, 2nd Floor, Block A
Po Yip Building
62-70 Texaco Road
Tsuen Wan, New Territories
Hong Kong
Phone 852-2764-8808
Fax 852-2764-4486
16 Wan Lee Road
Jurong Industrial Estate
Singapore 627946
Phone 65-6-268-3433
Fax 65-6-268-1389
BRAZIL
HUNGARY
SPAIN
R. Dom Pedro Henrique de Orleans
e Braganca, 276
Vila Jaguara CEP 05117-000
São Paulo
Brazil
Phone 55-11-3621-4111
Fax 55-11-3621-4066
Ceglédi út 1-3
1107 Budapest
Hungary
Phone 36-1-431-3464
Fax 36-1-431-3471
C /Provenza 288, Pral.
08008 Barcelona
Spain
Phone 34-93-467-7726
Fax 34-93-467-7725
CANADA
INDONESIA
SWEDEN
34600 Solon Road
Solon, Ohio 44139
U.S.A.
Phone 1-800-677-9089
Fax 1-800-677-8131
Wisma Danamon Aetna Life 19th
Floor
Jalan Jend. Sudirman Kav. 45-46
Jakarta 12930
Indonesia
Phone 62-21-575-0941
Fax 62-21-575-0942
Box 211
201 22 Malmö
Sweden
Phone 46-40-611-13-60
Fax 46-40-611-94-15
CHILE
ITALY
SWITZERLAND
Alcantara 200, piso 6 Of. 17
Las Condes, Santiago
Chile
Phone 56-2-370-2908
Fax 56-2-370-2914
A&B Business Center
Via Valla 16, nr. 17
20141 Milano
Italy
Phone 39-02-8474-2250
Fax 39-02-8474-2251
Postfach 54
3280 Murten
Switzerland
Phone 00-800-5000-1090
Fax 00-800-6000-1090
CHINA
MEXICO
THAILAND
Room 1204
Tomson Commercial Building
No. 710, Dongfang Road
Pudong, Shanghai
P.R. China 200122
Phone 86-21-5081-3900
Melchor Ocampo 193
Torre A piso 13
Col. Veronica Anzures
11300 Mexico D.F.
Mexico
Phone 52-55-5260-5991
Fax 52-55-5260-3310
163 Ocean Insurance Building,
16th Floor, Unit B
Surawongse Road, Bangrak
Bangkok 10500
Thailand
Phone 66-2-634-1692
Fax 66-2-634-1694
DENMARK
NETHERLANDS
UNITED KINGDOM
Box 211
201 22 Malmö
Sweden
Phone 46-40-611-13-60
Fax 46-40-611-94-15
Postbus 487
5000 AL Tilburg
Netherlands
Phone 31-13-58-35-400
Fax 31-13-58-35-499
52 Milford Road
Reading, Berkshire RG1 8LJ
United Kingdom
Phone 44-118-958-8386
Fax 44-118-955-0925
FRANCE
NORWAY
UNITED STATES
Rue Benoît Fourneyron Z.I. Sud
Boîte Postale 31
42161 Andrezieux Cedex
France
Phone 33-4-77-36-56-56
Fax 33-4-77-55-37-89
Postboks 148
1366 Lysaker
Norway
Phone 47-67-53-12-00
Fax 47-67-12-42-68
34600 Solon Road
Solon, Ohio 44139
U.S.A.
Phone 1-440-248-0100
Fax 1-440-248-0723
Copyright ©2004 ERICO International Corporation. All rights reserved.
CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.
E668LT03US
FEP-LT04-8