SI INTERCEPTOR Instruction Manual ERITECH SI INTERCEPTOR - I N ST R U CT I O N M A N UA L ERITECH SI INTERCEPTOR Instruction Manual www.erico.com 1 ERITECH SI INTERCEPTOR - I N ST R U CT I O N M A N UA L Installation Guidelines ➜ For full details on installing your SI INTERCEPTOR, please refer to ERICO’s technical notes and the French national standard NFC17-102. It is also recommended to adhere to local standards for relevant local down conductor and grounding requirements. This manual is a guide to the Installation, Operation and Maintenance of the ERITECH® SI INTERCEPTOR Lightning Protection System. It assumes that the system to be installed has been designed by an authorized ERICO representative. The system design will include: • Grounding systems design – a configuration should be designed as a result of soil resistivity analysis. Certification The certification of the ERITECH SI INTERCEPTOR installation must be performed by an authorised ERICO representative. This is done in conjunction with issuing of a Certificate of Compliance, which is available from your nearest ERICO office. When this certificate has been completed and signed, a copy must be either taken by the ERICO representative or sent to the nearest ERICO office. During the process of certification, the following will be checked: • Downconductor routes - chosen to avoid other services, maintain minimum bending radii and minimize down conductor run length. • Downconductor securing requirements. • LPSD - CAD analysis design software which determines terminal placement, mast & height requirements as well as protection level calculation. All of the above are recommended for a successful installation. If there is any doubt about any of the points mentioned, please contact ERICO or its nearest representative for clarification. • Installation matches the Benji design. • The integrity of the mast and any associated brackets and fastenings. Warning - Only attempt to install the ERITECH® SI INTERCEPTOR during storm-free periods. • Guying, anchor points and fastenings. • Downconductor routing, securing and seals. • Ground termination of down-conductor. ➜ The SI INTERCEPTOR must be at least 2 meters higher than any other point on the structure it is intended to protect. • Grounding System. • Labelling. ➜ The resistance of the lightning protection grounding system must be less than 10 ohms. This should be measured without downconductor(s) connected and without interconnection to other grounding systems. • Certificate of Compliance and Warranty Card completed and returned. • General mechanical check of all fastenings. 2 www.erico.com ERITECH SI INTERCEPTOR - I N ST R U CT I O N M A N UA L Operation and Maintenance to the structure. Check that the guys are secure and undamaged. Replace if necessary. Check that all fastenings are secure and tight. The ERITECH® SI INTERCEPTOR lightning protection system requires no user operation and is completely automatic in operation. 5. Look for signs of damage to the downconductor (whether by lightning, careless handling, vandalism or other causes). • The SI becomes active only during storm activity. • The system does not require any external power requirements or replacement components for normal operation. 6. Check that the Lightning Event Counter is secure, if the display is registering a reading, then record the reading and date. • It is essential that the ERITECH® SI INTERCEPTOR Lightning Protection System be regularly maintained. Maintenance should be undertaken: 7. Ensure the grounding resistance is less than 10 . 8. Check the continuity of all bonding conductors 1. After each known strike to the SI INTERCEPTOR or at least once per year. 2. If any changes have been made to the structure, whether they be structural, antennae or Building Maintenance Unit additions, etc. Installation Instructions The recommended order of installation is as follows: Maintenance should be undertaken as follows: 1. Full installation of the grounding system. 2. Full installation of the downconductor. Do not attempt maintenance during potential lightning periods. 3. Termination of the downconductor to the grounding system. 4. Terminate the top of the downconductor to the SI INTERCEPTOR mast. 1. Check that the building is the same physical shape and that no additional structures such as antennae, advertising signs, satellite dishes, Building Maintenance Units or similar have been installed within 2m (80in.) height of the SI INTERCPTOR. 5. Raise the mast into position and secure. 2. Inspect the SI INTERCEPTOR to ensure that it is not dented or physically damaged in any way. 3. Inspect the Finial Tip on top of the SI INTERCEPTOR to ensure that it is not excessively burnt, deformed or missing. 4. Check that the mast is securely attached www.erico.com 3 ERITECH SI INTERCEPTOR - I N ST R U CT I O N M A N UA L Typical MAST Installation Arrangement For Cantilevered Mast (range 2-4 metres) SI-125, SI-140 or SI-60 TERMINATION COUPLER supplied with ER1-1000-SS or ER1-2000-SS MAST (ER1-1000-SS) or (ER1-2000-SS) TMC-SS TMC-SS LPC580 CABTIE-SS MAST OPTIONS ER1-1000-SS ER1-2000-SS MAST (ER2-2000-SS) or (ER2-3000-SS) 1m ALOF-1-GS ER2-2000-SS ER2-3000-SS ER3-2000-SS ER3-3000-SS DOWNCONDUCTOR Refer to your local standard for downconductor requirements. 4 www.erico.com ERITECH SI INTERCEPTOR - I N ST R U CT I O N M A N UA L Typical MAST Installation Arrangement For Cantilevered Mast (range 4-6 metres) SI-125, SI-140 or SI-60 TERMINATION COUPLER supplied with ER1-1000-SS or ER1-2000-SS MAST (ER1-1000-SS) or (ER1-2000-SS) MAST (ER2-2000-SS) or (ER2-3000-SS) TMC-SS TMC-SS LPC580 CABTIE-SS MAST (ER3-2000-SS) or (ER3-3000-SS) MAST OPTIONS ER1-1000-SS ER1-2000-SS 1m MAST (ER2-2000-SS) or (ER2-3000-SS) ALOF-1-GS ER2-2000-SS ER2-3000-SS 1m ER3-2000-SS ER3-3000-SS DOWNCONDUCTOR Refer to your local standard for downconductor i t www.erico.com 5 ERITECH SI INTERCEPTOR - I N ST R U CT I O N M A N UA L Typical MAST Installation Arrangement For Guyed Mast (range 3-5 metres) S125, S140 or S160 MAST (ER1-1000-SS) or ER1-2000-SS) TERMINATION COUPLER suppiled with ER1-1000-SS or ER1-2000-SS Do not over-tension Guy Wires (Slightly sagging) TMC-SS TMC-SS LPC580 Guy Kit (GUY KIT 4) Anchor Points not supplied with GUYKIT 4 CABTIE-SS Mast (ER2-3000-SS or ER2-2000-SS) Support Base (ER2-BASE-SS) MAST OPTIONS Preferred Angle 45˚ - 60˚ 4 Holes, Ø12.5mm ER2-2000-SS ER2-3000-SS 229mm 178mm ER1-1000-SS ER1-2000-SS ER2-BASE-SS ER3-2000-SS ER3-3000-SS DOWNCONDUCTOR Refer to your local standard for downconductor requirements. ER3-BASE-SS 6 www.erico.com ERITECH SI INTERCEPTOR - I N ST R U CT I O N M A N UA L Typical MAST Installation Arrangement For Guyed Mast (range 5-8 metres) S125, S140 or S160 MAST (ER1-1000-SS) or ER1-2000-SS) TERMINATION COUPLER suppiled with ER1-1000-SS or ER1-2000-SS MAST (ER2-2000-SS) or ER2-3000-SS) Guy point midway on ER2 Series mast TMC-SS TMC-SS Do not over-tension Guy Wires (Slightly sagging) LPC580 Guy Kit (GUYKIT 7) CABTIE-SS Mast (ER3-2000-SS or ER3-3000-SS) Anchor Points not supplied with GUYKIT 7 Support Base (ER3-BASE-SS) MAST OPTIONS Preferred Angle 45˚ - 60˚ 4 Holes, Ø12.5mm ER2-2000-SS ER2-3000-SS 229mm 178mm ER1-1000-SS ER1-2000-SS ER2-BASE-SS ER3-2000-SS ER3-3000-SS DOWNCONDUCTOR Refer to your local standard for downconductor requirements. ER3-BASE-SS www.erico.com 7 ERITECH SI INTERCEPTOR - I N ST R U CT I O N M A N UA L Options De Support / Support Options / Opciones del Montaje Option : 1 Opción : 1 ERICORE Downconductor ERICORE Conducteur de descente INTERCEPTOR INTCPT-ADBUTT MAST BUTT ADAPTOR LOCKSCREW ERICORE UPPER TERMINATION FRP MAST P/No. INTCPT-ADBUTT (#702296) Option : 2 Opción : 2 Standard Downconductor Conducteur de descente INTERCEPTOR INTCPT-ADBUTT MAST BUTT ADAPTOR LOCKSCREW TERMLUGCOUP ERICO ALUMINIUM TUBULAR MAST P/No. TERMLUGCOUP (#701840) 8 www.erico.com ERITECH SI INTERCEPTOR - I N ST R U CT I O N M A N UA L Options De Support / Support Options / Opciones del Montaje Option : 3 Opción : 3 Standard Downconductor Standard Conducteur de descente INTERCEPTOR INTCPT3 OR INTCPT3SS INTCPT-ADM3/4UNC Note: INTCPTADM3/4UNC 3/4" UNC thread Option : 4 Opción : 4 CONDUCTIVE MAST P/No. INTCPT-ADM3/4UNC (#702299) Standard Downconductor Standard Conducteur de descente INTERCEPTOR INTCPT3 OR INTCPT3SS Note: INTCPT-ADF2BSPF 2" British Standard Pipe thread. INTCPT-ADF2NSP 2" (USA) National Standard Pipe thread. www.erico.com INTCPT-AMD2NPS OR INTCPT-ADMSBSPF 2" PIPE P/No. INTCPT-ADF2BSPF (#702297) P/No. INTCPT-ADF2NSP (#702298) 9 ERITECH SI INTERCEPTOR - I N ST R U CT I O N M A N UA L www.erico.com 5 YEAR LIMITED WARRANTY This product has a limited warranty to be free from defects in materials and workmanship for a period of ten (5) years from the date of dispatch from the Manufacturer. The Purchaser acknowledges that lightning is a natural event with statistical variation in behavior and energy levels which may exceed product ratings, and 100% protection is not offered and cannot be provided for. Therefore the Manufacturer's liability is limited to the repair or replacement of the product (at the Manufacturer's sole option) which in its judgement has not been abused, misused, interfered with by any person not authorized by the Manufacturer, or exposed to energy or transient levels exceeding the Manufacturer's specifications for the product. The product must be installed and earthed (where applicable) in strict accordance with the Manufacturer's specifications and all relevant national Electricity and Safety Standards. The Manufacturer and the Purchaser mutually acknowledge that the product by its nature may be subject to degradation as a consequence of the number and severity of surges and transients that it experiences in normal use and this warranty excludes such gradual or sudden degradation. This warranty does not indemnify the Purchaser of the product for any consequential claim for damages or loss of operations or service or profits. Customers should contact their nearest ERICO agent to obtain a Product Repair Authorization Number prior to making any claim under this warranty. This is only a summary of the warranty given by the Manufacturer. The full text of the warranty is set out in the Manufacturer's Conditions of Quotation and Sale. 10 www.erico.com ERITECH SI INTERCEPTOR - I N ST R U CT I O N M A N UA L WARNING: 1. These products shall be used only as illustrated and recommended in product instruction sheets (additional instruction sheets are available at www.erico.com). Misuse or misapplication may cause failure resulting in possible property damage or bodily injury. 2. These products must be used only in the manner depicted in the illustrations that accompany them. 3. Failure to observe these specifications may cause product malfunctions resulting in property damage or bodily injury. ERICO products at the time of shipment are warranted to conform to any applicable written description furnished to the Buyer by ERICO, and to be free from defects in material and workmanship. NO OTHER WARRANTY, WHETHER EXPRESSED OR IMPLIED, (INCLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS), SHALL EXIST IN CONNECTION WITH THE SALE OR USE OF ANY ERICO PRODUCT. 4. All instructions must be completely followed to ensure proper and safe operation. SAFETY WARNING: SAFETY INSTRUCTIONS: All governing codes and regulations and those required by the job site must be observed. Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.Wear gloves to avoid splinters and cuts. HAZARDOUS VOLTAGES EXIST INTERNAL TO THE SI INTERCEPTOR. THIS UNIT SHOULD BE INSTALLED AND SERVICED ONLY BY QUALIFIED PERSONNEL IN CONFORMANCE WITH ALL GOVERNING CODES. • The power supply to the SI INTERCEPTOR should always be turned (and locked) OFF before the unit is accessed for any reason. • Prior to installation, ensure that the SI INTERCEPTOR is of the correct voltage, current, phasing, frequency rating and is the type recommended by the manufacturer of the power distribution system. • All instructions must be followed to ensure proper and safe operation of the SI INTERCEPTOR. • Failure to follow instructions or warnings may result in bodily injury, equipment damage or ineffective protection. DANGER: Electrical shock or burn hazard. Installation of this SI INTERCEPTOR should only be made by qualified personnel. Failure to lockout electrical power during installation or maintenance can result in fatal electrocution or severe burns. Before making any connections to this electrical panel be sure that power has been removed from all associated wiring, electrical panels, and other electrical equipment. CAUTION: Check to make sure line voltage does not exceed SI INTERCEPTOR voltage requirement. CAUTION: This unit must be installed in conformance with all governing codes and must be installed on the load side of the main over-current protection. Diagrams are for reference only. Schematics are representative of typical applications and are only to be used for reference. www.erico.com 11 www.erico.com AUSTRALIA GERMANY POLAND 6 Chilvers Road P.O. Box 148 Thornleigh (Sydney) NSW 2120 Australia Phone 61-2-9479-8500 Fax 61-2-9484-9188 66851 Schwanenmuehle Germany Phone 49-6307-918-10 Fax 49-6307-918-150 ul. Krzemieniecka 17 54-156 Wroclaw Poland Phone 48-71-374-40-22 Fax 48-71-374-40-43 BELGIUM HONG KONG SINGAPORE Postbus 33 3110 Rotselaar Belgium Phone 32-14-69-96-88 Fax 32-14-69-96-90 Unit 1, 2nd Floor, Block A Po Yip Building 62-70 Texaco Road Tsuen Wan, New Territories Hong Kong Phone 852-2764-8808 Fax 852-2764-4486 16 Wan Lee Road Jurong Industrial Estate Singapore 627946 Phone 65-6-268-3433 Fax 65-6-268-1389 BRAZIL HUNGARY SPAIN R. Dom Pedro Henrique de Orleans e Braganca, 276 Vila Jaguara CEP 05117-000 São Paulo Brazil Phone 55-11-3621-4111 Fax 55-11-3621-4066 Ceglédi út 1-3 1107 Budapest Hungary Phone 36-1-431-3464 Fax 36-1-431-3471 C /Provenza 288, Pral. 08008 Barcelona Spain Phone 34-93-467-7726 Fax 34-93-467-7725 CANADA INDONESIA SWEDEN 34600 Solon Road Solon, Ohio 44139 U.S.A. Phone 1-800-677-9089 Fax 1-800-677-8131 Wisma Danamon Aetna Life 19th Floor Jalan Jend. Sudirman Kav. 45-46 Jakarta 12930 Indonesia Phone 62-21-575-0941 Fax 62-21-575-0942 Box 211 201 22 Malmö Sweden Phone 46-40-611-13-60 Fax 46-40-611-94-15 CHILE ITALY SWITZERLAND Alcantara 200, piso 6 Of. 17 Las Condes, Santiago Chile Phone 56-2-370-2908 Fax 56-2-370-2914 A&B Business Center Via Valla 16, nr. 17 20141 Milano Italy Phone 39-02-8474-2250 Fax 39-02-8474-2251 Postfach 54 3280 Murten Switzerland Phone 00-800-5000-1090 Fax 00-800-6000-1090 CHINA MEXICO THAILAND Room 1204 Tomson Commercial Building No. 710, Dongfang Road Pudong, Shanghai P.R. China 200122 Phone 86-21-5081-3900 Melchor Ocampo 193 Torre A piso 13 Col. Veronica Anzures 11300 Mexico D.F. Mexico Phone 52-55-5260-5991 Fax 52-55-5260-3310 163 Ocean Insurance Building, 16th Floor, Unit B Surawongse Road, Bangrak Bangkok 10500 Thailand Phone 66-2-634-1692 Fax 66-2-634-1694 DENMARK NETHERLANDS UNITED KINGDOM Box 211 201 22 Malmö Sweden Phone 46-40-611-13-60 Fax 46-40-611-94-15 Postbus 487 5000 AL Tilburg Netherlands Phone 31-13-58-35-400 Fax 31-13-58-35-499 52 Milford Road Reading, Berkshire RG1 8LJ United Kingdom Phone 44-118-958-8386 Fax 44-118-955-0925 FRANCE NORWAY UNITED STATES Rue Benoît Fourneyron Z.I. Sud Boîte Postale 31 42161 Andrezieux Cedex France Phone 33-4-77-36-56-56 Fax 33-4-77-55-37-89 Postboks 148 1366 Lysaker Norway Phone 47-67-53-12-00 Fax 47-67-12-42-68 34600 Solon Road Solon, Ohio 44139 U.S.A. Phone 1-440-248-0100 Fax 1-440-248-0723 Copyright ©2004 ERICO International Corporation. All rights reserved. CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation. E668LT03US FEP-LT04-8