C - Abacus Flame
Transcription
C - Abacus Flame
Appliance Technical Guide Service Engineer Edition Neta-tec Combi GA Range Duo-tec 2 Combi GA Range Megaflo 2 System GA Range Gas Fired Wall Mounted Condensing Combination & System Boilers © Baxi Heating UK Ltd 2012 Contents Appliance Technical Guide This Appliance Technical Guide contains information to enable diagnosis of faults, interpretation of error codes, identification of key componets and the performing of commissioining, calibration and combustion checking. Models covered:• Baxi Neta-tec Combi • Baxi Duo-tec 2 Combi • Baxi Megaflo 2 System Note: These buttons inactive on System models:If only the symbol is displayed on System models the boiler will not operate. Press the button until the symbol appears. 2 © Baxi Heating UK Ltd 2012 Page 1.0 Gas Adaptive System 3 2.0 Combi C.H. Sequence of Operation 4 3.0 Combi D.H.W Sequence of Operation 5 4.0 System C.H. Sequence of Operation 6 5.0 Commissioning Function 7 6.0 Service Due Function 9 7.0 Checking the Combustion 10 8.0 Combustion Re-calibration 11 9.0 Gas Type Selection 15 10.0 Information Menu 16 11.0 Error History 17 12.0 Errors & Sub-codes 19 13.0 P.C.B. & R.D.S. 21 14.0 Electronic Gas Valve 22 15.0 Hydraulics 23 16.0 Internal Wiring 26 17.0 Electrical Measurements 29 18.0 Parts Matrix 30 19.0 E133 Flow Chart 31 20.0 Commissiong Procedure & Errors 32 21.0 Additional Information 33 22.0 Pages for Notes 34 1.0 Gas Adaptive System The Gas Adaptive System The Baxi GA range of boilers are fully ‘Gas Adaptive’. This means the system automatically monitors the flame and adjusts the gas valve to achieve the correct combustion at all times. Explanation of Set Flames on GA The Set Flame is a value that is used to achieve the desired combustion and is set at either during manufacture or by an engineer on site. The value of this is different for each model because of fan speeds, mixers, nozzles, heat exchangers etc. hence each model has different Set Flames. This value relates to the ionization signal (e.g. 35 = 350 kOhms), and it simply tells the boiler what ionization it should achieve at that fan speed. If it is set incorrectly the boiler will always try to achieve that signal. It must be set correctly at manufacture, and by an engineer if any gas carrying parts or R.D.S. are changed, to achieve 9.0% +-0.2 CO2 on N.G. (10.5% +-0.2 CO2 on N.G. ) The adjustable Set Flames are at three fixed fan speeds:00 (min) IGN (ignition) Displayed as 33, 41 etc. It is a % of maximum fan speed or ‘power’. 100 (max) From these three points, a curve is drawn and the values for the entire RPM range are calculated. When the Set Flame is changed at one of the fan speeds above, the RPM will always stay the same, but the PCB will send a signal to the valve to open or close the solenoid to alter the gas flow so that the ionization signal matches the Set Flame value just inputted. As the ionization signal changes, so does the combustion. Boiler Cycle: From Factory to Installation Manufactured & Set on N.G. Boiler set automatically to achieve 9.0% CO2 Installed Boiler fitted by installer Commissioning Function Before use boiler must complete C.F. Service Due - 1 After 11 months ‘Sd’ shown on boiler display Service Due - 2 After 11 months ‘Sd’ shown on boiler display ‘SD’ function reset at annual service © Baxi Heating UK Ltd 2012 3 2.0 Combi C.H. Sequence of Operation Combi Models C.H. Demand Pump On Pump Check by Water Pressure - OK No E430 Yes Diverter Valve C.H. Position Fan On RPM Check - OK No E160 Yes Gas Valve Start Sequence Gas Valve Opens Spark Ignition No Ignition 5 Attempts Ignition Achieved No E133 Reset Yes Flame On Flame Stabilization 5 Seconds Stabilization Loss of Flame 12 Attempts Ignition Achieved Yes Full C.H. Rate 4 © Baxi Heating UK Ltd 2012 Boiler Operating No E128 Reset 3.0 Combi D.H.W. Sequence of Operation Combi Models D.H.W. Demand Pump On Pump Check by Water Pressure - OK No E430 Yes Diverter Valve D.H.W. Position Fan On RPM Check - OK No E160 Yes Gas Valve Start Sequence Gas Valve Opens Spark Ignition No Ignition 5 Attempts Ignition Achieved No E133 Reset Yes Flame On Flame Stabilization 5 Seconds Stabilization Loss of Flame 12 Attempts Ignition Achieved Yes Full D.H.W Rate © Baxi Heating UK Ltd 2012 Boiler Operating No E128 Reset 5 4.0 System C.H. Sequence of Operation System Models C.H. Demand Pump On Pump Check by Water Pressure - OK No E430 Yes Fan On RPM Check - OK No E160 Yes Gas Valve Start Sequence Gas Valve Opens Spark Ignition No Ignition 5 Attempts Ignition Achieved No E133 Reset Yes Flame On Flame Stabilization 5 Seconds Stabilization Loss of Flame 12 Attempts Ignition Achieved Yes Full Rate 6 © Baxi Heating UK Ltd 2012 Boiler Operating No E128 Reset The Commissioning Function (CF) - Description 5.0 Commissioning Function The CF is a one off forced function that is activated on the first power up of the boiler after it has left the factory. The boiler cannot be operated unless the CF has been completed and the CF can be activated only once. There are two stages to the CF - De-aeration of the system followed by a Gas Type Check. De-aeration This function operates the pump and the diverter valve moves from DHW to CH periodically to purge the system of air. It ensures maximum evacuation of air and prevents damage to the heat exchanger coils at initial fire up. This takes approximately 7 minutes to complete. Gas Type Check This automatically follows the de-aeration function and checks the flame signal to determine if the gas supply is NG or LPG. It is done by first running at IGN rate, then at full power for the final stage. From these two speeds two values are measured which are used to recognize the gas type being supplied. IMPORTANT: When checking at full power, the combustion can go higher than normal for a few seconds, therfore it is not advisable to insert the analyser probe into the flue sampling point to measure combustion, as saturation may occur and affect subsequent readings. This stage takes approximately 4 minutes to complete. The total time for the CF is between 10 and 12 minutes. Activation of Commissioning Function (CF) from initial Power On See page 32 for the flow diagram. Once power is supplied to the boiler the display will show ‘000’ which indicates that the CF needs to be activated. • Press and hold the ‘CH +ve’ and the ‘ip’ button, together for 6 seconds • ‘312’ should be displayed and the boiler is now performing the de-aeration cycle • After approx 7 minutes, the boiler will fire and the Gas Type check cycle will start • The boiler will remain at a reduced rate for approx 3 minutes, in the final minute it will ramp to ‘100’, during this time the boiler temp will be displayed. It is advised to open a DHW tap to dump the heat. • Once the Gas Type check has finished, the display will show what type of gas the boiler is connected to: • If it is natural gas, it will flash ‘NG’ for a few seconds and then be ready to operate • If it is LPG, it will flash ‘LPG’ and this will need to be confirmed by pressing the ip button for 6 seconds. All software values are automatically modified and the boiler is ready to use If the boiler display shows ‘LPG’ when NG is being supplied, it can be cancelled by pressing the ‘ip’ and reset ‘R’ button together for 4 seconds. When there is an error present (e.g. Low Water Pressure – E118) it must be rectified before the CF can be started or completed. If there is an interruption to CF it will start again. If de-aeration has been completed, it will start from gas type check. © Baxi Heating UK Ltd 2012 7 5.0 Commissioning Function (cont.) Commissioning Function (CF) Mini-Calibration if E133 in Commissioning Mode If during Commissioning Function the boiler fails to light and goes to E133 then a “mini-calibration” can be performed within the CF Function (assuming the gas supply has been checked). • With the display showing ‘000’ and before the Gas Type check, press and hold the reset ‘R’ and ‘CH -ve’ buttons for 6 seconds, followed by the ‘ip’ button. • The display should now show the ignition speed and calibrate. It will go to ‘100’ briefly then back to ‘000’ Commissioning. • To activate the Gas Type Check, press and hold the ‘ip’ and ‘CH +ve’, as normal and the boiler will now complete the Gas Type Check. IMPORTANT NOTE: IT IS NOT POSSIBLE TO CALIBRATE A NEW GAS VALVE WHILST IN COMMISSIONING MODE ! Manual De-aeration Function (312) This function can be activated manually, for example in instances when a radiator or heat exchanger has been changed and thus the system needs to be purged of air. • Press and hold the ‘ip’ and ‘CH -ve’ buttons for 6 seconds. • The display will show ‘312’ and the De-aeration function activated. • It will be active for 10 minutes. • To disable, either press and hold the ‘ip’ and ‘CH -ve’ for 6 seconds or isolate the power to the boiler. 8 © Baxi Heating UK Ltd 2012 Service Due Function (SD) - Description 6.0 Service Due Function When this function is activated ‘Sd’ is displayed after a pre-determined time (Factory Set at 11 months) informing the user that the 12 month service is due shortly. It is only active whilst there is power to the boiler. If power is interrupted the counter continues from where it stopped previously. The boiler continues to work as normal and the display flashes 'Sd' for 3 seconds, every 10 seconds. It can be reset, disabled and Service Time changed by alteration of parameters. ! IMPORTANT NOTE: DO NOT ADJUST ANY OTHER VALUES OR PARAMETERS AS IT WILL AFFECT THE OPERATION OF THE BOILER To reset the SD Function • Once the annual service is complete the SD Function must be reset so the next service can be indicated. • Press and hold the ‘CH -ve’ and ‘CH +ve’ buttons together for 6 seconds to enter the ‘TSP Menu’. P01 will be displayed. • Use ‘CH +ve’ to scroll to ‘P22’. • Press the ‘ip’ button to toggle into the ‘P’ value. • Change ‘00’ to ‘15’ (15 is the SD counter reset code). • Press the ‘ip’ button to toggle back to to lower parameter menu. • Press the reset button ‘R’ to exit the ‘TSP’ menu. The next SD message will be displayed in 11 months. To disable or change the SD Function Time Period • Press and hold the ‘CH –ve’ and ‘CH +ve’ buttons together for 6 seconds to enter the ‘TSP Menu’. P01 will be displayed. • Use ‘CH +ve’ to scroll to ‘P22’. • Press the ‘ip’ button to toggle into the ‘P’ value. • Change ‘00’ to ‘22’ (22 is the code to access the higher parameters - P41 and above). • Press the ‘ip’ button to toggle back to lower parameter menu. • Use ‘CH +ve’ to scroll to ‘P50’. • Press the ‘ip’ button to toggle into the value for ‘P50’. • The value range is 6….25:6….24 = months elapsed before ‘Sd’ is displayed. 25 = function disabled. • Choose the desired value and press the ‘ip’ button to confirm. • Press the reset button ‘R’ to exit the ‘TSP’ menu. © Baxi Heating UK Ltd 2012 9 Checking the Combustion - F304 7.0 Checking the Combustion At each service the combustion must be checked at three fan speeds:- ‘00’, ‘IGN’ and ‘100’. 00 = Minimum IGN = Ignition Speed (different for each model) 100 = Maximum Speed (D.H.W. power for Combi) To check the combustion at these 3 speeds Function 304 must be activated. To activate, press and hold the ‘ip’ and ‘CH +ve’ buttons together for 6 seconds. ‘304’ should be displayed and then the boiler will run at maximum when ‘100’ will be displayed. Allow a few moments for the boiler to stabilize then measure the combustion. To choose the next fan speed, press the ‘CH –ve’ button - the Ignition Speed will be displayed. To set at minimum press the ‘CH –ve’ again. ‘00’ will be displayed. To de-activate this function, press and hold ‘ip’ and ‘CH +ve’ for 6 seconds or isolate power to the boiler for several seconds. Note: If at ‘100’ the boiler temperature reaches 85°C, the burner will be extinguish and it will start again. To prevent this from happening, open one or two D.H.W. taps whilst in F304 and the boiler will automatically dump the heat through the D.H.W. circuit. In the case of System models it is recommended that any stored hot water is depleted prior to commencement. Limited Combustion Adjustment - F304 • A limited adjustment of the combustion can be performed whilst Function 304 is activated. • By pressing the ‘ip’ button at any of the three fan speeds above an adjustment value is accessed. This adjustment is limited in that a deviation of only -3 or +3 from the original value of 0 is permitted. The combustion can be altered by approximately +/- 0.6% in this mode. • Changing the value by 3 increases or decreases the CO2 value by approximately 0.6%. • Positive adjustment equates to richer combustion and negative adjustment results in weaker combustion. • Once the combustion has been changed, press the ‘ip’ button to toggle back to the fan speed and now, by pressing the ‘CH +ve’ or ‘CH -ve’, the fan speed can be changed. • Once completed press and hold the ‘ip’ and ‘CH +ve’ buttons for 6 seconds to de-activate Function 304. 10 © Baxi Heating UK Ltd 2012 8.0 Combustion Re-calibration Combustion Re-calibration Each boiler is calibrated during manufacture and set during F.F.T. (Final Function Testing). This sets the Fan and E.G.V. (Electronic Gas Valve) to the rest of the system. Combustion at F.F.T. is set at 9.0% +/- 0.2% on N.G. The system must be re-calibrated by the engineer to the procedure below if any of the following are changed:• Gas Valve • R.D.S. (Removable Data Stick) • Burner • Fan IT IS ESSENTIAL THAT THE CALIBRATION PROCESS IS STARTED WHEN THERE IS NO DEMAND ! Combined Analyser/Manometer Press the ‘CH -ve’ and reset ‘R’ buttons together for 6 seconds. ‘On’ will be displayed and within 2 seconds of this showing press the ‘ip’ button. If ‘303’ is displayed, the time window to press the ‘ip’ button has been missed. Power down at the fused spur and start again. DO NOT TURN ON THE ANALYSER PUMP WHILST THE BOILER IS CALIBRATING AS THE INTERNAL CELL MAY BECOME SATURATED ! To G.V. Inlet Test Point Remove the boiler front door and connect the manometer to the Inlet Test point on the Gas Valve. After the ‘ip’ button is pressed the Ignition Fan Speed (as % of maximum) will be displayed. Each model is different (e.g. 33GA is ‘41’). The boiler software will now search for the appropriate ignition curve to light with, usually curve 3 or 4. To G.V. Inlet Test Point After several seconds ‘100’ will be displayed, indicating that the fan is a maximum speed. It may be necessary to put a D.H.W. demand on the system if the temperature exceeds 85°. Check the gas inlet pressure has not dropped below 16mb. The boiler will remain at ‘100’ until stabilization is achieved - up to 3 minutes. © Baxi Heating UK Ltd 2012 >16mb To G.V. Inlet Test Point 11 After stabilization at maximum (‘100’) the boiler will revert to ignition fan speed to stabilize at this rate as well, taking up to 3 minutes. To G.V. Inlet Test Point After stabilization at ignition fan speed minimum power will be automatically selected, ‘00’ being displayed. Stabilization at this speed will take up to 2 minutes. To G.V. Inlet Test Point Once calibration is complete the flame, tap & radiator icons will flash and the display alternate between ‘00’ and a value. This value is the ‘Set Flame Value’. The Set Flame controls the ionization signal and thus the combustion level. Each fan speed has an adjustment. The Set Flame determines what the boiler can achieve so it is essential to have correct combustion. To Flue Sampling Point INSERT THE ANALYSER PROBE INTO THE FLUE SAMPLING POINT Pressing the ‘CH -ve’ or ‘CH +ve’ buttons changes the Set Flame value. Increasing the value weakens combustion, decreasing it makes the combustion richer. 12 © Baxi Heating UK Ltd 2012 To Flue Sampling Point Once combustion is set to 9.0% press the ‘ip’ button. °C The display will alternate between the fan speed (‘00’ or minimum in this case) and the boiler temperature. To Flue Sampling Point To select the next fan speed press the ‘CH +ve’ button. ‘33’ will be displayed, indicating ignition speed. To Flue Sampling Point °C To view the Set Flame value at that fan speed press the ‘ip’ button. The display will alternate between the ignition fan speed (‘33’) and the Set Flame value (‘38’ in this example). To Flue Sampling Point Change the Set Flame value to achieve 9.0% CO2 by pressing ‘CH -ve’ or ‘CH +ve’. Press the ‘ip’ button followed by ‘CH +ve’ to change to maximum fan speed (‘100’). Press the ‘ip’ button to display the Set Flame value. The value can be changed by pressing ‘CH -ve’ or ‘CH +ve’ buttons to achieve 9.0% CO2. Once combustion has been checked, adjusted where necessary, and the readings recorded at each fan speed press reset ‘R’ button to escape the calibration function - ‘ESC’ will be displayed. © Baxi Heating UK Ltd 2012 To Flue Sampling Point 13 Remove the pressure tube from the Gas Valve Inlet Test Point. Tighten the screw. To Flue Sampling Point Replace the front door, ensuring it is secured by the screws previously removed. Insert the analyser probe in the Air Sampling Test Point. Replace the plug in the Flue Sampling Test Point. Press the ‘ip’ button and ‘CH +ve’ for 6 seconds. ‘304’ will be displayed and the boiler will operate at maximum fan speed. ‘100’ will be displayed, alternating with the boiler temperature. Pressing ‘CH -ve’ button will change the fan speed to Ignition, a further press selecting minimum speed. Check for recirculation at each fan speed:- ‘100’, ‘33’* & ‘00’. °C * ‘33’ is typical a value Once the recirculation check is complete, either press the ‘ip’ and ‘CH +ve’ buttons for 6 seconds or isolate the power at the used spur and then re-instate it. 14 © Baxi Heating UK Ltd 2012 To Flue Sampling Point Gas Type - L.P.G. & N.G. 9.0 Gas Type Selection By gaining access to the ‘TSP’ (Transparent Slave Parameters) Menu the Gas Type can be adjusted, for example from L.P.G. to N.G. in rural areas when mains N.G. is provided subsequent to installation. Note: If the boiler is to be installed on an L.P.G. supply from new consult the information on page 7. • Press and hold the ‘CH +ve’ and ‘CH -ve’ buttons together for 6 seconds • ‘P01’ will be displayed alternating with its value (‘0’). • Pressing the ‘CH +ve’ and ‘CH -ve’ buttons scrolls through the parameter list. • Press ‘CH +ve’ until ‘P02’ is displayed. • Press the ‘ip’ button to view the selected parameter. • Pressing the ‘CH +ve’ and ‘CH -ve’ buttons modifies the parameter. • P02 = 0 Boiler set for N.G. • P02 = 1 Boiler set for L.P.G. • Press the ‘ip’ button to safe the parameter value. • Press the reset ‘R’ button to leave the TSP menu. The boiler temperature will be displayed - the boiler is ready for use. Once parameter P02 is set to the gas type required no calibration is necessary. The boiler will operate normally with the new settings automatically adjusted. Combustion Level & Setting Tolerance N.G. = 9.0% CO2 +/-0.2% L.P.G. = 10.5% CO2 +/-0.2% Note: The tolerance of +/-0.2% is for setting puposes - a tolerance of +/-0.8% can be applied when checking. The combustion is the same at each fan speed. © Baxi Heating UK Ltd 2012 15 10.0 Information Menu Information Menu By gaining access to the Information Menu a number of values can be viewed. The information can be used to diagnose faults, e.g. the value of a sensor to check if it is open circuit or closed circuit Press ‘ip’ for 1 second. The display will alternate between the ‘0’i code (e.g. i 02) and its value. To scroll down the list press the ‘ip’ button. i 00: Error Subcode See table on page 18 i 01: C.H. Temperature i 02: External Temperature (if present) i 03: D.H.W. Temperature i 04: D.H.W. Temperature i 05: Water Pressure i 06: Return Temperature i 07: Flue Temperature i 08: Heat Exchanger Temperature i 09: Not used i 10: Not used i 11: Not used i 12: Not used i 13: Not used i 14: Not used i 15: Not used i 16: Not used i 17: Fan Speed RPM i 18: num ic °C °C °C °C bar °C °C °C i 03 & i 04 are the same sensor RPM This function operates for 3 minutes, or can be cancelled by pressing the reset ‘R’ button. 16 © Baxi Heating UK Ltd 2012 Reading Errors via the TSP Menu 11.0 Error History The boiler records the most recent error codes, up to a maximum of 10. These can be viewed via the display. Whilst the parameter lines are P32 through to P41, the display only shows the ‘C’ codes. To gain access to the TSP menu:• Press and hold the ‘CH +ve’ and ‘CH -ve’ buttons together for 6 seconds • ‘P01’ will be displayed. • Pressing the ‘CH +ve’ to scroll through the parameter list. • Error codes P32....P38. These errors do not require resetting, for example low system pressure. When the fault is rectified the code automatically resets. • Error codes P39....P41. Errors that must be manually reset, for example safety thermostat activated. Once a parameter has been selected a series of numbers will be displayed. It is advisable to note them down as they alternate between each other. The order is:• Error Number • Error Code • Counter for the same Error • Days elapsed since Event • System Status • Phase Status • C.H. Flow during Event ‘Counter for the same Error’ Number of times the same error has occurred. ‘Days Elapsed’ Number of days. ‘45’ = 45 days since error. ‘System Status’ Operating Mode before the error. 0 Standby 1 D.H.W. Request 2 Controller Stop Function Active (F304) 3 C.H. Request 4 Preheat active 5 C.H. Frost Protection active 6 D.H.W. Frost Protection active 7 Pump Post circulation active 8 Overheating pump active ‘Phase Status’ Special Operating Mode before the error. 0 Standby 1 Pre-Purging Function active 03 Ignition Load purging between 1st and 2nd attempt 04 Ignition load 1st attempt 05 Operation Active 06 Lock Out 08 2nd Ignition Attempt 11 Ignition Load purging between 2nd and 3rd attempt 14 3rd Ignition attempt 15 Post Purging Function 16 Overheating Post Purging function © Baxi Heating UK Ltd 2012 17 11.0 Error History (cont.) Reading Errors via the TSP Menu (cont.) The display format is such that, for example, P32 will flash then the code, P32 again then the next code and so on. For example:- P32...C01...P32...E06...P32...02...P32...000...P32...03...P32...05...P32...75°C. The ‘C’ value is always the start of the sequence. Error Table for Engineers Table for recording errors:- Reset Errors Non-reset Errors Error Error Days System Counter Number Code Elapsed Status 18 © Baxi Heating UK Ltd 2012 P32 P33 P34 P35 P36 P37 P38 P39 P40 P41 C01 C09 E06 02 000 03 Phase Status C.H. Flow 05 75°C 12.0 Errors & Sub-codes List of Errors & Sub-codes Anomaly Code Internal Code Anomaly Action E09 Gas valve connection fault Check the cable P.C.B./gas valve and gas valve plug E10 External probe fault Check the sensor E12 Differential water flow switch fault (still open) Check the water flow switch E13 Differential water flow switch fault (still closed) Check the water flow switch E15 Gas valve comand fault Check the cable P.C.B./gas valve. Replace P.C.B. if necessary E18 Water refill activated Auto-Refill activated – motor energized E19 Maximum time of water refill Auto-Refill open too long to fill – check system E20 1 Central heating NTC sensor fault (s.c.) Check the sensor E20 2 Central heating NTC sensor fault (o.c.) Check the sensor E40 1 Return central heating NTC sensor fault (s.c.) Check the sensor E40 2 Return central heating NTC sensor fault (o.c.) Check the sensor E28 539 Flue NTC sensor fault (s.c.) Check the sensor E28 540 Flue NTC sensor fault (o.c.) Check the sensor E50 1 DHW NTC sensor fault (tank boiler) (s.c.) Check the sensor E50 2 DHW NTC sensor fault (tank boiler) (o.c.) Check the sensor E53 Incorrect calibration or obstruction in flue pipe Enable the Calibration Function and check flue for obstruction E55 PCB to be set by the “Calibration Function” Enable the Calibration Function E71 Fan parameter out of range in autocalibration Check the fan speed E72 Combustion test out of range in autocalibration Check the correct position and integrity of the sensing electrode and cable E77 Current out of range Check the correct position and integrity of the sensing electrode and for flue recirculation. Enable the automatic calibration function before replacing components. E78 Minimum gas valve current Check the correct position and integrity of the sensing electrode and for flue recirculation. Enable the automatic calibration function before replacing components. E79 Maximum gas valve current Check the correct position and integrity of the sensing electrode and for flue recirculation. Enable the automatic calibration function before replacing components. No communication Check cable between room unit and P.C.B. or R.F. link. E92 Combustion test alarm during auto-setting Failed the self check test during Calibration Function. Check for re-circulation before changing Gas Valve E109 Precirculation alarm Check for correct circulation of water and pump E83/84/85/86/87 Note: (s.c.) = Short Circuit (o.c.) = Open Circuit © Baxi Heating UK Ltd 2012 19 12.0 Errors & Sub-codes (cont.) E110 437 Boiler max temperature exceeded for gradient (possible sticking pump or air in the circuit). Temperature rise too fast. Check correct circulation of the water and pump. E110 438 Boiler max temperature exceeded for overtemperature (possible sticking pump or air in the circuit). Temperature overshoots Set Point by 20C. Check correct circulation of the water and pump. Safety thermostat sensor tripped. Check the sensor. Water pressure HIGH (> 2.9 bar). Check the water pressure. Water pressure LOW (< 0.5 bar). Check the water pressure. E110 E117 566 E118 E125 500 Water circulation falut (overtemperature). Check correct circulation of the water and pump. E125 501 Water circulation fault – Temp not increased on the flow. Check correct circulation of the water and pump. E125 502 Water circulation fault. Check correct circulation of the water and pump E128 Safety error for frequent loss of flame (12 times). Check the sensing electrode and cable and for flue recirculation. Enable the automatic calibration function before replacing components. E129 Safety error for frequent loss of flame with max correction during the ignition during Calibration Function. Check the sensing electrode and cable and for flue recirculation. Enable the automatic calibration function before replacing components. Flue thermostat sensor tripped (lockout). Check the thermostat, correct circulation of water and pump. E133 Gas supply fault. Check the power supply, sensing electrode, spark electrode and cable. Check flue recirculation. Enable the automatic calibration function before replacing components. E134 Elapsed time gas valve open without gas (short request in a short period). Check the gas pressure, sensing electrode, spark electrode and cable. Replace the P.C.B. if necessary. E135 Internal error. Replace P.C.B. E154 Plausibility test (flow/return). Check correct circulation of the water and pump. Check the correct position of the sensors. E160 Fan fault. Check the fan and the cable. E270 Dry fire. Check the sensor and the correct circulation of the water and the pump. E317 Wrong power supply electrical frequency (Hz) Check the frequency (Hz) and the power supply. E130 528 E321 1 Domestic Hot Water NTC sensor fault (s.c.) Check the sensor. E321 2 Domestic Hot Water NTC sensor fault (o.c.) Check the sensor. E384 Fault flame (parasitic flame). Check the correct operation of the gas valve. E385 Under voltage. Check the power supply (V~). E430 557 Water pressure temporary test. Check the correct circulation of the water and the pump. E430 & flame 505 Water pressure test failed. Check the correct circulation of the water and the pump. E431 1 Aluminium sensor fault (s.c.). Check the sensor. E431 2 Aluminium sensor fault (o.c.). Check the sensor. Note: (s.c.) = Short Circuit (o.c.) = Open Circuit 20 © Baxi Heating UK Ltd 2012 13.0 P.C.B. & R.D.S. P.C.B. & R.D.S. (Removable Data Stick) The same P.C.B. is used for Combi and System models. The R.D.S. is a removable data stick that determines the model type and also gas valve settings for that particular boiler. The P.C.B. will not work without the R.D.S. and the display will be blank. The R.D.S. will store in its memory the Calibration settings for that particular boiler and also the boiler type and output. If changing a P.C.B., simply swap the existing R.D.S. over to the new P.C.B. If the R.D.S. is damaged and a new one fitted then a Calibration is required (go to page 11) to calibrate the system. P.C.B. Changed Calibration Not Required P.C.B. & R.D.S. Changed Calibration Required R.D.S. Changed © Baxi Heating UK Ltd 2012 21 Electronic Gas Valve 14.0 Electronic Gas Valve The Bertelli Electronic Gas Valve (E.G.V.) has no mechanical adjustment of the gas air ratio, however it does have inlet and burner pressure tapping points. It is 24vDC and the connection is to the P.C.B. via the front connection. If this connection is faulty E09 will be displayed. The EGV has two safety valves, the first is an ON/OFF solenoid and the second is used as safety but also to control the outlet gas flow depending upon the signal from the P.C.B. This second valve also controls the outlet gas pressure. The outputs on the connector both on the P.C.B. and E.G.V. are extremely difficult to measure with a multi-meter, so it is advisable not to measure this signal. Disconnecting the lead and checking the plug will result in an E09 error. If the boiler keeps going to E133 and you have checked all components and done a re-calibration, then it is possible the gas valve may not be fully opening upon Ignition. Change the Valve and do a re-calibration (page 11). Resistances for the two coils Pins 1 + 3 = 20 – 30 Ohms Pins 2 + 4 = 60 – 70 Ohms Ionization Gap The ionization electrode is unique to the GA system and it is important to maintain the correct distance from burner to the parallel section of the electrode. The distance should be 5mm +- 1mm. If it is out of this tolerance, the combustion may be compromised by the settings of the E.G.V. so install a new electrode and perform a re-calibration as described on page 11. 22 © Baxi Heating UK Ltd 2012 15.0 Hydraulics Neta-tec Combi GA Pressure Sensor D.H.W. Cartridge (Turbine Type) D.H.W. Sensor Diverter Valve Cartridge P.R.V. D.H.W. Hall Effect Sensor Pressure Gauge Connection (incorporates return filter) Diverter Valve Head The Neta-tec GA hydraulics are of a composite construction • The D.H.W. Flow Switch is a Turbine Type Design • There is a bypass built into the two bodies connected by a clip on the front. • Behind the Pressure Gauge there is an inline filter cage. • The pump is 2 speed operational. In D.H.W. it operates only at Max speed. In C.H. it switches between the two speeds depending upon temperature loadings to maintain the boiler in condensing mode. © Baxi Heating UK Ltd 2012 23 15.0 Hydraulics (cont.) Duo-tec 2 Combi GA Pressure Gauge Connection D.H.W. Hall Effect Sensor Pressure Sensor D.H.W. Cartridge (Turbine Type) The Duo-Tec 2 GA hydraulics are of brass construction similar to older products. • The D.H.W. Flow Switch is a Turbine Type • The Pressure Sensor measures the pressure and is not a switched type • The connection for the Pressure Sensor has an adaptor to take the clipped connection • The capillary pressure gauge connection is on the flow assembly above the D.H.W. sensor position • The Pressure Vessel connection is on the return assembly above the drain point • The bypass is integral and utilises the plate heat exchanger 24 © Baxi Heating UK Ltd 2012 Pressure Vessel Connection 15.0 Hydraulics (cont.) Megaflo 2 System GA Pressure Sensor Pressure Vessel Connection Bypass Pressure Gauge Connection The Megaflo 2 GA hydraulics are of a composite construction. Key components are the same as the Neta-tec Combi GA and the connection points for the pressure gauge and pressure vessel are the same. © Baxi Heating UK Ltd 2012 25 16.0 Internal Wiring Neta-tec Combi GA Gas Valve Hall Effect Sensor Fan M2 Low Voltage External Control Connection Flue Sensor Hydraulic Pressure Switch Safety Thermostat b b bk w br From X20 & X31 r g b g b b X3 bk br X23 b b br bk Terminal Strip r bk br X37 w g br b X36 g r b r g X22 X20 X24 X10 g/y b b br X13 b bk br To M2 Connection X31 bk bk b br br X11 br bk g/y gr X12 X1 X2 g/y g/y g/y Pump Diverter Valve Motor 26 © Baxi Heating UK Ltd 2012 Heating Flow Sensor DHW NTC Sensor bk b Heating Return Sensor Spark Ignition Electrode Flame Sensing Electrode 16.0 Internal Wiring (cont.) Duo-tec 2 Combi GA Gas Valve Fan Hall Effect Sensor M2 Low Voltage External Control Connection Flue Sensor Hydraulic Pressure Switch Safety Thermostat Heating Return Sensor b b bk w Heating Flow Sensor bk b br DHW NTC Sensor bk br From X20 & X31 b X3 bk br Terminal Strip r r b g br bk X23 b b b X37 g w g br X36 b g r b r g X22 X20 X24 X10 g/y b b br X13 bk r To M2 Connection b bk bk b br br X11 X31 br bk g/y gr X12 X1 X2 g/y g/y g/y Pump Spark Ignition Electrode Flame Sensing Electrode Diverter Valve Motor © Baxi Heating UK Ltd 2012 27 16.0 Internal Wiring (cont.) Megaflo 2 System GA Gas Valve Fan M2 Low Voltage External Control Connection Flue Sensor Hydraulic Pressure Switch Safety Thermostat Heating Return Sensor b b b w br bk X22 r br bk X20 bk b b g br bk X31 b X3 bk X23 b b X37 w g br g b X36 r b r X22 X20 X24 w Terminal Strip br X10 g/y b b To M2 Connection b br br br X13 X31 bk bk b br X11 bk g/y gr X12 X1 X2 g/y g/y g/y Pump 28 © Baxi Heating UK Ltd 2012 g/y Spark Ignition Electrode Flame Sensing Electrode Heating Flow Sensor 17.0 Electrical Measurements Useful Electrical Measurements All voltages for mains A.C. are taken from earth and the stated pin. Function PCB Conn. Voltage CH Demand X3 Pin 1 (Blue) Pump ON X13 Pin 2 (Brown) 230v X11 Pin 5 (Black) 225v Lo 260v Hi (Pump runs at ‘Hi’ speed only in DHW, both speeds in CH) Pressure Sensor X22 230v Between Pins 11 and 12 (red and white) 1 bar = 3v (approx) Diverter Valve (CH) X13 Diverter Valve (DHW) X13 Pin 4 (Black) 240v Pin 4 (Black) 0v Pin 5 (Brown) 0v Pin 5 (Brown) 240v Fan ON X11 X23 240v @ Pin 2 Full Power: Circa 8v DC between Black and Blue DHW Hall Sensor X22 ON between Pins 11 and 12 (Red + White) 1v OFF between Pins 11 and 12 (Red + White) 0v Between Pins 11 and 13 (Red + Blue) 5v constant It is not advisable to measure at the smaller P.C.B. connections such as the Electronic Gas Valve as the voltages need to be taken from the actual edge connector on the board and damage could easily occur. Water Temperature Sensors All the sensors use the same resistance/ temperature measurements. The graph below can be used to establish an approximate measurement, but the important point is to ensure the resistance reduces as temperature increases. Temperature Sensors & Resistance 120 Temperature (°C) 100 80 Heat Exchanger Sensor 60 Water Sensors 40 20 0 0 2 4 6 8 10 12 14 16 18 20 Resistance (Ohms) Both C.H. & D.H.W. sensors have the same resistance. The Heat Exchanger sensor has a different curve, but the temperature/resistance curve is the same. A further check can be made using the Information Menu as described on page 16. Even if the boiler is not operating the temperatures can still be read in the Information Menu making it possible to check if a sensor is reading correctly. © Baxi Heating UK Ltd 2012 29 18.0 Parts Matrix 30 © Baxi Heating UK Ltd 2012 © Baxi Heating UK Ltd 2012 E133 No Is ‘000’ displayed on first power up ? Yes Yes Check electrode gap, gas supply, etc. Any components changed prior to commissioning ? No E55 displayed Change R.D.S. to bypass Commissioning Function Calibrate (‘CH -ve’ & ‘Reset’, then ‘ip’) Page 11 Mini-Calibrate (‘CH -ve’ & ‘Reset’, then ‘ip’) Page 8 Check electrode gap, gas supply, etc. Check combustion levels whilst in Calibration Function (wait until finished) Calibrate (‘CH -ve’ & ‘Reset’, then ‘ip’) Page 11 When ‘000’ displayed start Commissioning (‘ip’ & ‘CH +ve’) Complete Change the Set Flame to achieve 9.0% CO2 at all fan speeds Complete 312 completed then Gas Check ? 19.0 E133 Flow Chart 31 32 © Baxi Heating UK Ltd 2012 Start Press ‘ip’ & ‘CH +ve’ for 6 seconds ‘312’ will be displayed for 7 minutes *It is referred to as Mini-Calibration when activated whilst still in commissioning mode. Only the ignition curve is set then ‘000’ displayed. See page 8 ‘000’ displayed Check electrode gap, gas supply, etc. E133 or other gas error displayed No Gas Type check starts Yes Yes Mini-Calibrate (‘CH -ve’ & ‘Reset’, then ‘ip’) Page 8 In 3 to 4 minutes ‘NG’ or ‘LPG’ is displayed No Boiler will find an ignition curve to ignite, briefly display ‘100’ then stop Mini-Calibration* Check electrode gap, gas supply, etc. Check boiler temp has not reached 85ºC When ‘000’ displayed restart commissioning (‘ip’ & ‘CH +ve’) Boiler commissioned 20.0 Commissioning Procedure & Errors 21.0 Additional Information Gas Recognition Fault If the boiler incorrectly identifies the gas type and it cannot be cleared:• Accept the incorrect gas type • Follow the procedure on page 15 • Select P02 (Gas Type) and change the type back to the correct one (‘00’ = N.G. & ‘01’ = L.P.G.) • Press reset ‘R’ to escape, power down the electrical supply to the boiler then power up to re-boot and the boiler will be set to work on the correct gas type Set Flame Reference Guide - Calibration Mode Use the values below to assist in setting the flame to the correct combustion leveles:- Model 24C 28C 33C 40C Set Flame Values Fan Speeds 00 IGN 48 38 36 38 37 49 30 35 100 37 32 35 25 18S 24S 28S 33S 60 50 48 34 44 37 40 30 40 40 40 36 These values will closely achieve 9.0% CO2 at all speeds, which is the recommended combustion setting. If the value differs by more than 10 from those above and the CO2 is not changing it is possible that re-circulation is occurring or there is an outside influence affecting the combustion. © Baxi Heating UK Ltd 2012 33 22.0 Notes 34 © Baxi Heating UK Ltd 2012 22.0 Notes © Baxi Heating UK Ltd 2012 35 All descriptions and illustrations provided in this leaflet have been carefully prepared but we reserve the right to make changes and improvements in our products which may affect the accuracy of the information contained in this leaflet. All goods are sold subject to our standard Conditions of Sale which are available on request. BAXI A Trading Division of Baxi Heating UK Ltd (3879156) Brooks House, Coventry Road, Warwick. CV34 4LL After Sales Service 0844 871 1525 Technical Enquiries 0844 871 1555 Website www.baxi.co.uk e&oe © Baxi Heating UK Ltd 2012 Comp No. 7210507-01 (5/12)