Start-Up, Operation and Maintenance Instructions
Transcription
Start-Up, Operation and Maintenance Instructions
23XRV Hermetic Screw Liquid Chillers with PIC III Controls 50/60 Hz HFC-134a Start-Up, Operation and Maintenance Instructions SAFETY CONSIDERATIONS Screw liquid chillers are designed to provide safe and reliable service when operated within design specifications. When operating this equipment, use good judgment and safety precautions to avoid damage to equipment and property or injury to personnel. Be sure you understand and follow the procedures and safety precautions contained in the chiller instructions, as well as those listed in this guide. DO NOT VENT refrigerant relief valves within a building. Outlet from rupture disc or relief valve must be vented outdoors in accordance with the latest edition of ANSI/ASHRAE 15 (American National Standards Institute, American Society of Heating, Refrigeration, and Air Conditioning Engineers), latest edition. The accumulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation. PROVIDE adequate ventilation in accordance with ANSI/ASHRAE 15, especially for enclosed and low overhead spaces. Inhalation of high concentrations of vapor is harmful and may cause heart irregularities, unconsciousness, or death. Misuse can be fatal. Vapor is heavier than air and reduces the amount of oxygen available for breathing. Product causes eye and skin irritation. Decomposition products are hazardous. DO NOT USE OXYGEN to purge lines or to pressurize a chiller for any purpose. Oxygen gas reacts violently with oil, grease, and other common substances. NEVER EXCEED specified test pressures. VERIFY the allowable test pressure by checking the instruction literature and the design pressures on the equipment nameplate. DO NOT USE air for leak testing. Use only refrigerant or dry nitrogen. DO NOT VALVE OFF any safety device. BE SURE that all pressure relief devices are properly installed and functioning before operating any chiller. RISK OF INJURY OR DEATH by electrocution. High voltage is present on motor leads even though the motor is not running. Open the power supply disconnect before touching motor leads or terminals. DO NOT WELD OR FLAMECUT any refrigerant line or vessel until all refrigerant (liquid and vapor) has been removed from chiller. Traces of vapor should be displaced with dry air or nitrogen and the work area should be well ventilated. Refrigerant in contact with an open flame produces toxic gases. DO NOT USE eyebolts or eyebolt holes to rig chiller sections or the entire assembly. DO NOT work on high-voltage equipment unless you are a qualified electrician. DO NOT WORK ON electrical components, including control centers, switches, starters, or oil heater until you are sure ALL POWER IS OFF and no residual voltage can leak from capacitors or solid-state components. LOCK OPEN AND TAG electrical circuits during servicing. IF WORK IS INTERRUPTED, confirm that all circuits are deenergized before resuming work. DO NOT syphon refrigerant. AVOID SPILLING liquid refrigerant on skin or getting it into the eyes. USE SAFETY GOGGLES. Wash any spills from the skin with soap and liquid. If liquid refrigerant enters the eyes, IMMEDIATELY FLUSH EYES with water and consult a physician. NEVER APPLY an open flame or live steam to a refrigerant cylinder. Dangerous over pressure can result. When it is necessary to heat refrigerant, use only warm (110 F [43 C]) water. DO NOT REUSE disposable (nonreturnable) cylinders or attempt to refill them. It is DANGEROUS AND ILLEGAL. When cylinder is emptied, evacuate remaining gas pressure, loosen the collar, and unscrew and discard the valve stem. DO NOT INCINERATE. CHECK THE REFRIGERANT TYPE before adding refrigerant to the chiller. The introduction of the wrong refrigerant can cause damage or malfunction to this chiller. Operation of this equipment with refrigerants other than those cited herein should comply with ANSI/ASHRAE 15 (latest edition). Contact Carrier for further information on use of this chiller with other refrigerants. DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while chiller is under pressure or while chiller is running. Be sure pressure is at 0 psig (0 kPa) before breaking any refrigerant connection. CAREFULLY INSPECT all relief devices, rupture discs, and other relief devices AT LEAST ONCE A YEAR. If chiller operates in a corrosive atmosphere, inspect the devices at more frequent intervals. DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief device when corrosion or build-up of foreign material (rust, dirt, scale, etc.) is found within the valve body or mechanism. Replace the device. DO NOT install relief devices in series or backwards. USE CARE when working near or in line with a compressed spring. Sudden release of the spring can cause it and objects in its path to act as projectiles. DO NOT STEP on refrigerant lines. Broken lines can whip about and release refrigerant, causing personal injury. DO NOT climb over a chiller. Use platform, catwalk, or staging. Follow safe practices when using ladders. USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or move inspection covers or other heavy components. Even if components are light, use mechanical equipment when there is a risk of slipping or losing your balance. BE AWARE that certain automatic start arrangements CAN ENGAGE THE COMPRESSOR, TOWER FAN, OR PUMPS. Open the disconnect ahead of the starter, tower fan, or pumps. Shut off the chiller or pump before servicing equipment. USE only repair or replacement parts that meet the code requirements of the original equipment. DO NOT VENT OR DRAIN waterboxes containing industrial brines, water, gases, or semisolids without the permission of your process control group. DO NOT LOOSEN waterbox cover bolts until the waterbox has been completely drained. DOUBLE-CHECK that coupling nut wrenches, dial indicators, or other items have been removed before rotating any shafts. DO NOT LOOSEN a packing gland nut before checking that the nut has a positive thread engagement. PERIODICALLY INSPECT all valves, fittings, and piping for corrosion, rust, leaks, or damage. PROVIDE A DRAIN connection in the vent line near each pressure relief device to prevent a build-up of condensate or rain water. Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 532-310 Printed in U.S.A. Form 23XRV-1SS Pg 1 9-06 Replaces: New Book 2 Tab 5e CONTENTS Page Vaporizer Temperature Control COMPRESSOR ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Oil Sump Temperature Control COMPRESSOR OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Oil Sump Temperature Control COMPRESSOR ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Remote Start/Stop Contacts . . . . . . . . . . . . . . . . . . . . . 38 Spare Safety and Spare Temperature Inputs. . . . . 38 Spare Alarm Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Refrigerant Leak Detector . . . . . . . . . . . . . . . . . . . . . . . 39 4 to 20 mA Kilowatt Output . . . . . . . . . . . . . . . . . . . . . . 39 Remote Reset of Alarms. . . . . . . . . . . . . . . . . . . . . . . . . 39 Condenser Pump Control . . . . . . . . . . . . . . . . . . . . . . . 39 Condenser Freeze Prevention . . . . . . . . . . . . . . . . . . . 39 Tower Fan Relay Low and High . . . . . . . . . . . . . . . . . . 39 Auto. Restart After Power Failure. . . . . . . . . . . . . . . . 40 Liquid/Brine Temperature Reset . . . . . . . . . . . . . . . . . 40 • RESET TYPE 1 • RESET TYPE 2 • RESET TYPE 3 Demand Limit Control Option . . . . . . . . . . . . . . . . . . . 40 Hot Gas Bypass (Optional) Algorithm . . . . . . . . . . . 40 Head Pressure Output Reference. . . . . . . . . . . . . . . . 41 Lead/Lag Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 • COMMON POINT SENSOR INSTALLATION • CHILLER COMMUNICATION WIRING • LEAD/LAG OPERATION • FAULTED CHILLER OPERATION • LOAD BALANCING • AUTO. RESTART AFTER POWER FAILURE Attach to Network Device Control . . . . . . . . . . . . . . . 44 • ATTACHING TO OTHER CCN MODULES Service Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 • TO ACCESS THE SERVICE SCREENS • TO LOG OUT OF DEVICE • HOLIDAY SCHEDULING START-UP/SHUTDOWN/RECYCLE SEQUENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46-48 Local Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Shutdown Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Automatic Soft Stop Amps Threshold . . . . . . . . . . . 47 Chilled Liquid Recycle Mode . . . . . . . . . . . . . . . . . . . . 47 Safety Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 BEFORE INITIAL START-UP . . . . . . . . . . . . . . . . . . 48-64 Job Data Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Equipment Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Using the Optional Storage Tank and Pumpout System . . . . . . . . . . . . . . . . . . . . . . . . . 48 Remove Shipping Packaging . . . . . . . . . . . . . . . . . . . . 48 Open Oil Circuit Valves . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Oil Charge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Tighten All Gasketed Joints . . . . . . . . . . . . . . . . . . . . . 48 Check Chiller Tightness . . . . . . . . . . . . . . . . . . . . . . . . . 49 Refrigerant Tracer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Leak Test Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Chiller Dehydration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Inspect Liquid Piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Check Optional Pumpout Compressor Liquid Piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Check Relief Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Identify the VFD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 • IDENTIFYING THE DRIVE BY PART NUMBER Check Starter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Input Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Checking the Installation . . . . . . . . . . . . . . . . . . . . . . . . 57 Inspect Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Ground Fault Troubleshooting. . . . . . . . . . . . . . . . . . . 58 Carrier Comfort Network® Interface . . . . . . . . . . . . . 58 Page SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 ABBREVIATIONS AND EXPLANATIONS . . . . . . . . . . 4 23XRV CHILLER FAMILIARIZATION. . . . . . . . . . . . . 4-8 Chiller Identification Nameplate . . . . . . . . . . . . . . . . . . 4 System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Motor-Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Muffler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Control Center. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Storage Vessel (Optional) . . . . . . . . . . . . . . . . . . . . . . . . 8 REFRIGERATION CYCLE . . . . . . . . . . . . . . . . . . . . . . 8-10 MOTOR COOLING CYCLE . . . . . . . . . . . . . . . . . . . . . . . 10 LUBRICATION CYCLE . . . . . . . . . . . . . . . . . . . . . . . . 10-12 Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Details. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Oil Reclaim System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Capacity Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 CONTROLS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-46 Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 • ANALOG SIGNAL • DIGITAL SIGNAL General Controls Overview . . . . . . . . . . . . . . . . . . . . . . 12 PIC III System Components . . . . . . . . . . . . . . . . . . . . . 12 • INTERNATIONAL CHILLER VISUAL CONTROLLER (ICVC) • CHILLER CONTROL MODULE (CCM) • VFD POWER MODULE • VFD GATEWAY MODULE • OIL HEATER CONTACTOR (1C) • OIL PUMP CONTACTOR (2C) • HOT GAS BYPASS CONTACTOR RELAY (3C) (Optional) • VFD REFRIGERANT COOLING SOLENOID VALVE (5C) • VAPORIZER HEATER CONTACTOR (6C) • CONTROL TRANSFORMERS (T1, T2) ICVC Operation and Menus. . . . . . . . . . . . . . . . . . . . . . 15 • GENERAL • ALARMS AND ALERTS • ICVC MENU ITEMS • BASIC ICVC OPERATIONS (Using the Softkeys) • TO VIEW STATUS • OVERRIDE OPERATIONS • TIME SCHEDULE OPERATION • TO VIEW AND CHANGE SET POINTS • SERVICE OPERATION PIC III System Functions . . . . . . . . . . . . . . . . . . . . . . . . 34 • CAPACITY CONTROL • FORCED • NORMAL CONDITIONS • CAPACITY INCREASE • CAPACITY DECREASE • ECL CONTROL OPTION • CHILLED LIQUID DEADBAND • PROPORTIONAL BANDS AND PROPORTIONAL GAIN • DEMAND LIMITING • CHILLER TIMERS • OCCUPANCY SCHEDULE Safety Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Shunt Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Default Screen Freeze . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Ramp Loading. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Capacity Override . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Compressor Minimum Speed Override . . . . . . . . . . 36 2 CONTENTS (cont) Page Chillers With Storage Tanks . . . . . . . . . . . . . . . . . . . . . 70 • TRANSFER REFRIGERANT FROM PUMPOUT STORAGE TANK TO CHILLER • TRANSFER REFRIGERANT FROM CHILLER TO PUMPOUT STORAGE TANK • CHILLERS WITH ISOLATION VALVES • DISTILLING THE REFRIGERANT GENERAL MAINTENANCE . . . . . . . . . . . . . . . . . . . .72,73 Refrigerant Properties . . . . . . . . . . . . . . . . . . . . . . . . . . 72 Adding Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 Removing Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 Adjusting the Refrigerant Charge . . . . . . . . . . . . . . . 72 Refrigerant Leak Testing . . . . . . . . . . . . . . . . . . . . . . . . 72 Refrigerant Leak Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 Test After Service, Repair, or Major Leak . . . . . . . . 72 • REFRIGERANT TRACER • TO PRESSURIZE WITH DRY NITROGEN Repair the Refrigerant Leak, Retest, and Apply Standing Vacuum Test . . . . . . . . . . . . . . . . . . . . . . . . 73 Trim Refrigerant Charge. . . . . . . . . . . . . . . . . . . . . . . . . 73 WEEKLY MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . 73 Check the Lubrication System . . . . . . . . . . . . . . . . . . 73 SCHEDULED MAINTENANCE . . . . . . . . . . . . . . . . 73-78 Service Ontime. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 Inspect the Control Center . . . . . . . . . . . . . . . . . . . . . . 73 Check Safety and Operating Controls Monthly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 Changing Oil and Oil Filter . . . . . . . . . . . . . . . . . . . . . . 73 Oil Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 Oil Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 Refrigerant Filter/Drier . . . . . . . . . . . . . . . . . . . . . . . . . . 74 Oil Strainers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 VFD Refrigerant Strainer . . . . . . . . . . . . . . . . . . . . . . . . 74 Vaporizer Refrigerant Return Line Orifice . . . . . . . 74 Compressor Inlet Bearing Oil Orifice . . . . . . . . . . . . 74 Inspect Condenser Refrigerant Float System. . . . 75 Inspect Relief Valves and Piping . . . . . . . . . . . . . . . . 77 Compressor Bearing Maintenance . . . . . . . . . . . . . . 77 Compressor Rotor Check . . . . . . . . . . . . . . . . . . . . . . . 77 Motor Insulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Inspect the Heat Exchanger Tubes . . . . . . . . . . . . . . 77 • COOLER • CONDENSER Water/Brine Leaks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Water/Brine Treatment . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Inspect the Control Center . . . . . . . . . . . . . . . . . . . . . . 77 Recalibrate Pressure Transducers . . . . . . . . . . . . . . 78 Optional Pumpout System Maintenance. . . . . . . . . 78 • OPTIONAL PUMPOUT COMPRESSOR OIL CHARGE • OPTIONAL PUMPOUT SAFETY CONTROL SETTINGS Ordering Replacement Chiller Parts . . . . . . . . . . . . . 78 TROUBLESHOOTING GUIDE . . . . . . . . . . . . . . . . 78-117 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 Checking the Display Messages. . . . . . . . . . . . . . . . . 79 Checking Temperature Sensors . . . . . . . . . . . . . . . . . 79 • RESISTANCE CHECK • VOLTAGE DROP • CHECK SENSOR ACCURACY • DUAL TEMPERATURE SENSORS Checking Pressure Transducers . . . . . . . . . . . . . . . . 79 • COOLER CONDENSER PRESSURE TRANSDUCER AND LIQUIDSIDE FLOW DEVICE CALIBRATION • TRANSDUCER REPLACEMENT Page Power Up the Controls and Check the Oil Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Software Configuration . . . . . . . . . . . . . . . . . . . . . . . . . 59 Input the Design Set Points . . . . . . . . . . . . . . . . . . . . . 59 Input the Local Occupancy Schedule (OCCPC01S) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Input Service Configurations. . . . . . . . . . . . . . . . . . . . 59 • PASSWORD • INPUT TIME AND DATE • CHANGE ICVC CONFIGURATION IF NECESSARY • TO CHANGE THE PASSWORD • TO CHANGE THE ICVC DISPLAY FROM ENGLISH TO METRIC UNITS • MODIFY CONTROLLER IDENTIFICATION IF NECESSARY • INPUT EQUIPMENT SERVICE PARAMETERS IF NECESSARY • MODIFY EQUIPMENT CONFIGURATION IF NECESSARY Perform a Control Test . . . . . . . . . . . . . . . . . . . . . . . . . . 61 Pressure Transducer and Optional Flow Device Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 • ZERO POINT CALIBRATION • HIGH END CALIBRATION Check Optional Pumpout System Controls and Compressor. . . . . . . . . . . . . . . . . . . . . 62 High Altitude Locations . . . . . . . . . . . . . . . . . . . . . . . . . 62 Charge Refrigerant Into Chiller . . . . . . . . . . . . . . . . . . 63 • CHILLER EQUALIZATION WITHOUT A PUMPOUT UNIT • CHILLER EQUALIZATION WITH PUMPOUT UNIT • TRIMMING REFRIGERANT CHARGE INITIAL START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64,65 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 Check Oil Pressure and Compressor Stop . . . . . . 65 To Prevent Accidental Start-Up. . . . . . . . . . . . . . . . . . 65 Check Chiller Operating Condition . . . . . . . . . . . . . . 65 Instruct the Customer Operator . . . . . . . . . . . . . . . . . 65 • COOLER-CONDENSER • OPTIONAL PUMPOUT STORAGE TANK AND PUMPOUT SYSTEM • COMPRESSOR ASSEMBLY • COMPRESSOR LUBRICATION SYSTEM • CONTROL SYSTEM • AUXILIARY EQUIPMENT • DESCRIBE CHILLER CYCLES • REVIEW MAINTENANCE • SAFETY DEVICES AND PROCEDURES • CHECK OPERATOR KNOWLEDGE • REVIEW THE START-UP, OPERATION AND MAINTENANCE MANUAL OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . 66-68 Operator Duties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Prepare the Chiller for Start-Up . . . . . . . . . . . . . . . . . 66 To Start The Chiller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Check the Running System . . . . . . . . . . . . . . . . . . . . . 66 To Stop the Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 • FAILURE TO STOP After Limited Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . 66 Preparation for Extended Shutdown . . . . . . . . . . . . 66 After Extended Shutdown . . . . . . . . . . . . . . . . . . . . . . . 67 Cold Weather Operation. . . . . . . . . . . . . . . . . . . . . . . . . 67 Refrigeration Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 PUMPOUT AND REFRIGERANT TRANSFER PROCEDURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69-72 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 Operating the Optional Pumpout Unit . . . . . . . . . . . 69 3 CONTENTS (cont) ABBREVIATIONS AND EXPLANATIONS Page Control Algorithms Checkout Procedure . . . . . . . . 80 Control Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 Control Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98 • RED LED (Labeled as STAT) • GREEN LED (Labeled as COM) Notes on Module Operation . . . . . . . . . . . . . . . . . . . . . 98 Chiller Control Module (CCM) . . . . . . . . . . . . . . . . . . . 98 • INPUTS • OUTPUTS Replacing Defective Processor Modules . . . . . . . 101 • INSTALLATION Gateway Status LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . 102 • DRIVE STATUS INDICATOR • MS STATUS INDICATOR • NET A STATUS INDICATOR • NET B STATUS INDICATOR Physical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103 APPENDIX A — ICVC PARAMETER INDEX . . 118-126 INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127 INITIAL START-UP CHECKLIST FOR 23XRV HERMETIC SCREW LIQUID CHILLER . . . . . . . . . . . . . . . . . . . .CL-1 to CL-12 Frequently used abbreviations in this manual include: CCM — Chiller Control Module CCN — Carrier Comfort Network CCW — Counterclockwise CSM — Chillervisor System Manager CW — Clockwise DPI — LF2 VFD Drive Peripheral Interface Board ECDL — Entering Condenser Liquid ECL — Entering Chilled Liquid EMS — Energy Management System HGBP — Hot Gas Bypass ICVC — International Chiller Visual Controller IGBT — Insulated Gate Bipolar Transistor I/O — Input/Output KAIC — Kiloamps Interrupt Capacity LCD — Liquid Crystal Display LCDL — Leaving Condenser Liquid LCL — Leaving Chilled Liquid LED — Light-Emitting Diode LEI — Local Equipment Interface Translator LF2 — Reliance LiquiFlo™ 2 VFD with Active Rectifier OIM — Reliance Operator Interface Module OLTA — Overload Trip Amps PIC III — Product Integrated Control III RLA — Rated Load Amps RS485 — Communications Type used by ICVC and CCM SCR — Silicon Controlled Rectifier SI — International System of Units SIO — Sensor Input/Output TB1 — Control Center Terminal Block 1 TB2 — Control Center Terminal Block 2 VFD — Variable Frequency Drive INTRODUCTION Prior to initial start-up of the 23XRV chiller, those involved in the start-up, operation, and maintenance should be thoroughly familiar with these instructions and other necessary job data. This book is outlined to familiarize those involved in the startup, operation and maintenance of the unit with the control system before performing start-up procedures. Procedures in this manual are arranged in the sequence required for proper chiller start-up and operation. Words printed in all capital letters or in italics may be viewed on the International Chiller Visual Controller (ICVC) (e.g., LOCAL, CCN, ALARM, etc.). Words printed in both all capital letters and italics can also be viewed on the ICVC and are parameters (e.g., CONTROL MODE, COMPRESSOR START RELAY, etc.) with associated values (e.g., modes, temperatures, percentages, pressures, on, off, etc.). Words printed in all capital letters and in a box represent softkeys on the ICVC control center (e.g., ENTER , EXIT , INCREASE , QUIT , etc.). This unit uses a microprocessor control system. Do not short or jumper between terminations on circuit boards or modules. Control or board failure may result. Be aware of electrostatic discharge (static electricity) when handling or making contact with circuit boards or module connections. Always touch a chassis (grounded) part to dissipate body electrostatic charge before working inside control center. Use extreme care when handling tools near circuit boards and when connecting or disconnecting terminal plugs. Circuit boards can be damaged easily. Always hold boards by the edges, and avoid touching components and connections. This equipment uses, and can radiate, radio frequency energy. If not installed and used in accordance with the instruction manual, it may interfere with radio communications. This equipment has been tested and found to comply with the limits for a Class A computing device pursuant to Subpart J of Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user, at his own expense, will be required to take whatever measures may be required to correct the interference. Always store and transport replacement or defective boards in an anti-static shipping bag. Factory-installed additional components are referred to as options in this manual; factory-supplied but field-installed additional components are referred to as accessories. The chiller software part number of the 23XRV unit is located on the back of the ICVC. 23XRV CHILLER FAMILIARIZATION (Fig. 1, 2, and 3) Chiller Identification Nameplate — The chiller identification nameplate is located on the right side of the chiller control center. System Components — The components include cooler and condenser, heat exchangers in separate vessels, motor-compressor, lubrication system, control center, and optional economizer. All connections from pressure vessels have threads, flanges, or victaulic grooves to enable each component to be pressure tested during factory assembly. 4 S – Special 23XRV – High Efficiency Variable Speed Screw Chiller Not Used Voltage Code 3 – 380-3-60 4 – 416-3-60 5 – 460-3-60 9 – 400-3-50 Cooler Size* 30-32 35-37 40-42 45-47 50-52 55-57 Drive Frame AA BA BB CC Condenser Size* 30-32 35-37 40-42 45-47 50-52 55-57 Motor Code P Q R S T U V Economizer Option E – With Economizer N – No Economizer R – Compressor Rectifier Max Input Amps† 440 520 520 608 Inverter Max Output Amps† 442 442 520 608 Max Motor Amps 265 283 306 334 368 421 440 a23-1533 *First number denotes frame size. †Maximum limits only. Additional application limits apply that may reduce these ampacities. Fig. 1 — Model Number Identification 1 2 4 3 21 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 5 20 6 7 8 12 10 11 9 13 19 a23-1548 16 18 15 14 17 — — — — — — — — — — — — — — — — — — — — — Motor Terminal Cover Plate Variable Frequency Drive International Chiller Visual Controller (ICVC) Discharge Pipe/Relief Valve Condenser Oil Reclaim Actuator Vaporizer Sight Glass Oil Filter Assembly (Hidden) Vaporizer Oil Sump Charging/Drain Valve Oil Sump Condenser Refrigerant Pumpout Valve Condenser Float Chamber Cooler Inlet Isolation Valve ASME Nameplate, Economizer (Hidden) Filter Drier Oil Sump Heater Condenser Supply/Return End Waterbox Cooler Supply/Return End Waterbox Motor Cooling Supply Line VFD Circuit Breaker/Disconnect Fig. 2 — Typical 23XRV Component Locations 5 22 23 24 25 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 26 41 40 39 38 37 36 35 34 33 a23-1549 42 43 27 28 32 31 44 30 — — — — — — — — — — — — — — — — — — — — Discharge Pipe Assembly Compressor Discharge Check Valve Access Cover Condenser Relief Valves with Three-Way Valve Refrigerant Charging Valves Cooler Relief Valve Tubesheet Mounting Brackets Typical Waterbox Drain Coupling ASME Nameplate, Condenser Oil Pump Oil Pump Inlet Strainer Strainer Housing Sight Glass Discharge Isolation Valve (Option or Accessory) Machine Electrical Data Nameplate Refrigeration Machine Nameplate Oil Sump Sight Glass Filter Drier Isolation Valve with Schrader Economizer Motor Cooling Sight Glass Filter/Drier Isolation Valve Vaporizer Drain Sight Glass 29 45 46 47 42 — VFD Cold Plate Refrigeration Inlet Connection (Outlet Hidden) 43 — VFD Refrigerant Cooling Solenoid Valve 44 — Compressor Nameplate 45 — Compressor Lubrication Block 46 — Economizer Muffler 47 — Vaporizer Condenser Gas Isolation Valve 48 — Hot Gas Bypass Isolation and Trim Valve 49 — VFD Cooling Refrigerant Strainer 50 — Cooler Refrigerant Pumpout Valve 51 — ASME Nameplate, Cooler 48 49 50 a23-1550 51 Fig. 2 — Typical 23XRV Component Locations (cont) 6 6 2 3 4 5 1 1 2 3 4 5 6 7 8 9 — — — — — — — — — Condenser Pressure Evaporator Pressure Compressor Discharge Temperature Compressor Discharge Pressure Compressor Discharge High Pressure Switch Compressor Motor Winding Temperature (Hidden) Evaporator Refrigerant Liquid Temperature (Hidden) Condenser Liquid Temperature Condenser Liquid Flow (Optional) 9 7 a23-1551 8 10 11 12 13 14 15 20 16 17 19 a23-1552 10 — Inductor Temperature Switch (Inside VFD Enclosure) 11 — VFD Rectifier Temperature (Inside Power Module) 12 — VFD Cold Plate Temperature (Inside VFD Enclosure) 13 — VFD Inverter Temperature (Inside Power Module) 14 — Humidity Sensor (Inside VFD Enclosure) 15 — Oil Pressure Leaving Filter (Hidden) 16 — Oil Sump Pressure (Hidden) 17 — Oil Sump Temperature (Hidden) 18 — Vaporizer Temperature 19 — Evaporator Liquid Temperature 20 — Evaporator Liquid Flow (Optional) 18 18 Fig. 3 — Typical 23XRV Sensor Locations 7 Cooler — The cooler (also known as the evaporator) is REFRIGERATION CYCLE maintained at low temperature/pressure so that evaporating refrigerant can remove heat from the liquid flowing through its internal tubes. The compressor continuously draws refrigerant vapor from the cooler. As the compressor suction reduces the pressure in the cooler, the remaining refrigerant boils at a fairly low temperature (typically 38 to 42 F [3 to 6 C]). The energy required for boiling is obtained from the liquid flowing through the cooler tubes. With heat energy removed, the liquid becomes cold enough for use in an air-conditioning circuit or process liquid cooling. After absorbing heat from the chilled liquid, the refrigerant vapor is compressed. Compression adds still more energy, and the refrigerant is quite warm (typically 90 to 130 F [32 to 54 C]) when it is discharged from compressor into condenser. Relatively cool (typically 65 to 85 F [18 to 29 C]) liquid flowing into the condenser tubes removes heat from the refrigerant and the vapor condenses to liquid, refrigerant. The liquid refrigerant in the condenser passes through orifices into the FLASC (Flash Subcooler) chamber (Fig. 6). Since the FLASC chamber is at a lower pressure, part of the liquid refrigerant flashes to vapor, thereby cooling the remaining liquid. The FLASC vapor is recondensed on the tubes which are cooled by entering condenser liquid. The liquid then passes through a float valve assembly which forms a liquid seal to keep FLASC chamber vapor from entering the cooler. An optional economizer can be installed between the condenser and cooler. In this case, an in-line orifice on the economizer drain flange meters the refrigerant liquid into the cooler. Pressure in this chamber is intermediate between condenser and cooler pressures. At this lower pressure, some of the liquid refrigerant flashes to gas, cooling the remaining liquid. The flash gas, having absorbed heat, is returned directly to the compressor at a point after suction cutoff (Fig. 7). Here it is mixed with gas from the suction cut-off point to produce an increase in the mass flow of refrigerant transported and compressed without either an increase in suction volume or a change in suction temperature. The cooled liquid refrigerant in the economizer is metered through an orifice into the cooler. Because pressure in the cooler is lower than economizer pressure, some of the liquid flashes and cools the remainder to evaporator (cooler) temperature. The cycle is now complete. Condenser — This vessel is located underneath the compressor. The condenser operates at a higher temperature/ pressure than the cooler and has liquid flowing through its internal tubes to remove heat from the refrigerant. Motor-Compressor — The motor-compressor maintains system temperature/pressure differences and moves the heat carrying refrigerant from the cooler to the condenser. See Fig. 4. Muffler — The muffler provides acoustical attenuation. A check valve just downstream of the muffler prevents reverse compressor rotation during shutdown. Control Center — The control center is the user interface for controlling the chiller and regulating the chiller’s capacity to maintain the proper chilled liquid temperature. See Fig. 5. The control center: • registers cooler, condenser, and lubricating system pressures • shows chiller operating condition and alarm shutdown conditions • records the total chiller operating hours, starts, and the number of hours the chiller has been currently running • sequences chiller start, stop, and recycle under microprocessor control • provides access to other Carrier Comfort Network® devices • provides machine protection Storage Vessel (Optional) — Two sizes of storage vessels are available. The vessels have double relief valves, a magnetically coupled dial-type refrigerant level gage, a 1-in. FPT drain valve, and a 1/2-in. male flare vapor connection for the pumpout unit. A 30-in.-0-400 psi (–101-0-2750 kPa) gage is also supplied with each unit. NOTE: If a storage vessel is not used at the jobsite, factoryinstalled optional isolation valves may be used to isolate the chiller charge in either the cooler or condenser. An optional pumpout compressor system is used to transfer refrigerant from vessel to vessel. DISCHARGE COMPRESSOR LUBRICATION BLOCK MOTOR TERMINAL ACCESS COVER MOTOR TERMINALS MOTOR COOLING INLET FLANGE MOTOR COOLING DRAIN a23-1619 Fig. 4 — Compressor 8 ECONOMIZER PORT STANDARD 65 KAIC CIRCUIT BREAKER OPTIONAL 100 KAIC CIRCUIT BREAKER (SHIPPED LOOSE INSIDE OF CONTROL CENTER FOR FIELD INSTALLATION) a23-1620 Fig. 5 — Standard and 100-KAIC Circuit Breaker Control Center COOLER REFRIGERANT ISOLATION VALVE (OPTIONAL) VFD REFRIGERANT COOLING ISOLATION VALVE HGBP ISOLATION VALVE (OPTIONAL) MOTOR VFD COLD PLATE VFD REFRIGERANT COOLING SOLENOID VALVE HGBP SOLENOID VALVE COMPRESSOR STRAINER VFD REFRIGERANT COOLING ISOLATION VALVE FILTER DRIER CONDENSER ISOLATION VALVE (OPTIONAL) FILTER DRIER ISOLATION VALVES CONDENSER FLOAT VALVE BUBBLER LINE a23-1621 Fig. 6 — Refrigerant Flow Schematic (Without Optional Flash Economizer) 9 COOLER HGBP ISOLATION VALVE (OPTIONAL) HGBP SOLENOID VALVE VFD REFRIGERANT COOLING ISOLATION VALVE ECONOMIZER MUFFLER MOTOR VFD REFRIGERANT COOLING VFD SOLENOID COLD VALVE PLATE VFD REFRIGERANT COOLING ISOLATION VALVE FLASH ECONOMIZER STRAINER COMPRESSOR FILTER DRIER ORIFICE FILTER DRIER ISOLATION VALVES FLOAT VALVE CONDENSER FLOAT VALVE BUBBLER LINE a23-1622 Fig. 7 — Refrigerant Flow Schematic (With Optional Flash Economizer) MOTOR COOLING CYCLE LUBRICATION CYCLE One half of the motor is cooled by suction gas while the other half is cooled by liquid refrigerant taken from the bottom of the condenser vessel. The flow of liquid refrigerant is maintained by the pressure differential that exists due to compressor operation. The refrigerant flows through an isolation valve, in-line filter/drier, and a sight glass/moisture indicator (dry-eye), into the motor through the motor spray nozzle. See Fig. 6 or 7. The motor spray nozzle is orificed to control refrigerant flow through the gaps between the rotor and stator. The refrigerant collects in the bottom of the motor casing and then drains into the cooler through the motor cooling drain line. The motor is protected by a temperature sensor and a temperature switch imbedded in the stator windings. COMP MOTOR WINDING TEMP temperatures above the COMP MOTOR TEMP OVERRIDE threshold (see Capacity Override section, page 36) will override the chilled liquid temperature capacity control to hold. If the motor temperature rises 10° F (5.5 C) above this threshold, the compressor will unload. If the COMP MOTOR WINDING TEMP rises above the 220 F (104.4 C) safety limit, the compressor will shut down. Summary — The 23XRV requires an oil pump. Oil flow is provided by a magnetically coupled, motor-driven oil pump. Oil flows through the oil filter into the compressor rotors and bearings. The cycle is referred to as a “high side” oil system. See Fig. 8. Details — The oil system: • lubricates the roller bearings which support the male and female rotors, and the ball bearings of the 23XRV compressor. • lubricates the male and female rotors Oil is charged into the system through a hand valve located on the bottom of the oil sump. Sight glasses on the oil sump permit oil level observation. When the compressor is shut down, an oil level should be visible in the oil sump sight glass. During operation, the oil level should always be visible in the strainer housing sight glass. Approximately 7.5 gal. (28.4 L) of oil is charged into the sump. Oil from the compressor bearing drain is drained directly into the oil sump. Refrigerant is driven from the oil as it flows around the oil sump heater and into the strainer housing. The oil pump draws the oil through a strainer and forces it through an oil filter. 10 The oil sump contains temperature and pressure sensors and a 530 W oil heater. The oil sump is vented to the compressor suction to minimize the amount of refrigerant absorbed by the oil. The OIL SUMP TEMPERATURE is measured and displayed on the ICVC default screen and the COMPRESS screen. The oil sump pressure is used to calculate the OIL PRESSURE DELTA P. Operating OIL PRESSURE DELTA P must be at least 18 psid (124 kPa) after the OIL PRESS VERIFY TIME has elapsed. Under normal full load conditions, oil pressure is typically 20 to 28 psid (138 to 193 kPa). If sufficient oil pressure is not established or maintained the chiller will shut down. An oil pressure delta P sensor fault will be declared if the OIL PRESSURE DELTA P is not less than 4 psid (27.6 kPa) prior to start-up. The filter housing is capable of being isolated by upstream and downstream valves to permit filter replacement. An oil pressure regulator valve directs excessive oil back into the oil sump. Oil supplied to the compressor is monitored by an oil pressure sensor. The OIL PRESSURE DELTA P is equal to the difference between the oil pressure leaving the filter and the oil sump pressure. It is read directly from the ICVC (International Chiller Visual Controller) default screen. Oil is supplied to the compressor through two separate inlets. One inlet leads to the suction bearings, the other leads to the discharge bearings. Most of the oil drains back into the sump while a small amount is used to lubricate the rotors. Rotor lubrication oil leaves the compressor mixed with the compressed discharge refrigerant vapor. OIL SUPPLY COMPRESSOR TO COMPRESSOR SUCTION COMPRESSOR OIL DRAIN CONDENSER ISOLATION VALVE COOLER MIST ELIMINATOR ACTUATED BALL VALVE VAPORIZER ORIFICE SIGHT GLASS EXTERNAL OIL HEATER SIGHT GLASS OIL HEATER OIL SUMP MIST ELIMINATOR OIL PUMP ISOLATION VALVE SIGHT GLASS FILTER ISOLATION SERVICE VALVE VALVE PRESSURE REGULATOR VALVE PUMP STRAINER a23-1623 OIL REFRIGERANT OIL FILTER ISOLATION VALVE OIL/REFRIGERANT MIXTURE Fig. 8 — Oil Flow Schematic 11 The PIC III controls respond to the difference between the CONTROL POINT and LEAVING CHILLED LIQUID temperatures when the ECL CONTROL OPTION is DISABLED. The PIC III controls respond to the difference between the CONTROL POINT and ENTERING CHILLED LIQUID temperatures when the ECL CONTROL OPTION is ENABLED. The chiller capacity is controlled by varying the TARGET VFD SPEED from 0% to 100%. The PIC III controls monitor the compressor oil properties and set a COMPRESSOR MINIMUM SPEED to ensure sufficient compressor bearing lubrication under all operating conditions. If the oil pressure falls below the values specified in Table 1 during start-up, the PIC III control will shut down the chiller. Table 1 — Oil Pressure Requirements TIME (SEC) Before Oil Pump On After Oil Press Verify Time During Start/Run MINIMUM START-UP OIL PRESSURE REQUIREMENT HFC-134a PSID kPaD <4 27.6 18 124 15 103 Oil Reclaim System — The oil reclaim system recovers oil from the cooler, removes the refrigerant, filters and returns the oil back to the compressor. One or more oil reclaim nozzles are positioned along the length of the cooler to draw the oil and refrigerant mixture from the surface of the refrigerant level. The mixture passes through an oil reclaim modulating valve and into the vaporizer. The flow of refrigerant and oil is regulated to prevent the vaporizer from becoming overloaded with liquid refrigerant. The modulating valve position is adjusted in accordance with the difference between the VAPORIZER TEMP and the EVAP REFRIG LIQUID TEMP. The 4 to 20 mA signal from CCM terminals J8-3 and J8-4 is converted into a 0 to 10V DC input to the oil reclaim modulating valve by a 500 ohm resistor connected between CCM terminals J8-3 and J8-4. The oil reclaim modulating valve closes when the chiller is shut down to prevent the vaporizer and oil sump from being flooded with refrigerant. Do not manually open the oil reclaim modulating valve when the chiller is shut down. Doing so will severely degrade the viscosity of the oil in the sump. Flow of refrigerant and oil from the cooler can be observed through a sight glass on top of the vaporizer. The viscosity of the compressor oil is significantly reduced when it absorbs refrigerant. A combination of heat and low pressure is used to vaporize the refrigerant that has been absorbed by the oil mixture reclaimed from the cooler. Condenser gas is used to warm the refrigerant and oil mixture in the vaporizer. Warm refrigerant is bled from the top of the condenser, directed through a row of tubes that line the bottom of the vaporizer, and discharged into the cooler. A 1500 W surface mounted electric heater provides supplemental heat to the vaporizer when the compressor is operating at lower loads. Refrigerant boiled out of the reclaimed mixture is vented to the compressor suction. The concentrated oil mixture drains out of the vaporizer, through a sightglass, past the vaporizer temperature sensor, and into the oil sump. A 530 W oil sump heater maintains the temperature of the reclaimed oil and the oil returned from the compressor at approximately 90 F (32.2 C) when the chiller is running and 140 F (60 C) when the chiller is off. The oil sump is also vented to compressor suction to increase oil viscosity by boiling off additional refrigerant. CONTROLS Definitions ANALOG SIGNAL — An analog signal varies in proportion to the monitored source. It quantifies values between operating limits. (Example: A temperature sensor is an analog device because its resistance changes in proportion to the temperature, generating many values.) DISCRETE SIGNAL — A discrete signal is a two-position representation of the value of a monitored source. (Example: A switch produces a discrete signal indicating whether a value is above or below a set point or boundary by generating an on/off, high/low, or open/closed signal.) General Controls Overview — The 23XRV hermetic screw liquid chiller contains a microprocessor-based control center that monitors and controls all operations of the chiller. The microprocessor control system matches the cooling capacity of the chiller to the cooling load while providing state-of-the-art chiller protection. The system controls cooling capacity within the set point plus the deadband by sensing the leaving chilled liquid or brine temperature (see Fig. 9 and 10) and regulating the compressor speed. Reducing the compressor speed decreases the volume flow rate of refrigerant through the compressor. Chiller protection is provided by the PIC III processor, which monitors the digital and analog inputs and executes capacity overrides or safety shutdowns, if required. PIC III System Components (Fig. 11-14) — The chiller control system is called PIC III (Product Integrated Control III). See Table 2. The PIC III controls the chiller by monitoring all operating conditions. The PIC III can diagnose a problem and let the operator know what the problem is and what to check. It promptly adjusts compressor speed to maintain leaving chilled liquid temperature. It can interface with auxiliary equipment such as pumps and cooling tower fans to turn them on when required. It continually checks all safeties to prevent any unsafe operating condition. It also regulates the oil heater and regulates the hot gas bypass valve, if installed. The PIC III controls provide critical protection for the compressor motor and control of the variable frequency drive. The PIC III can interface with the Carrier Comfort Network® (CCN) system if desired. It can communicate with other PIC I, PIC II or PIC III equipped chillers and other CCN devices, such as LEI (Local Equipment Interface). Capacity Control — The PIC III controls provide chilled liquid temperature control by modulating the frequency of the power delivered by the VFD to the compressor motor. The compressor speed is adjusted in response to the difference between the CONTROL POINT and the LEAVING CHILLED LIQUID or ENTERING CHILLED LIQUID temperatures. 12 INTERNATIONAL CHILLER VISUAL CONTROLLER (ICVC) — The ICVC is the “brain” of the PIC III. This module contains all the primary software needed to control the chiller. The ICVC is the input center for all local chiller set points, schedules, configurable functions, and options. The ICVC has a stop button, an alarm light, four buttons for logic inputs, and a backlight display. The backlight will automatically turn off after 15 minutes of non-use. The functions of the four buttons or “softkeys” are menu driven and are shown on the display directly above the softkeys. The ICVC is mounted on the Control Center door. See Fig. 2. To change the contrast of the display, access the adjustment on the back of the ICVC. See Fig. 11. CHILLER CONTROL MODULE (CCM) — This module is located on the control panel in the control center. The CCM provides the input and outputs necessary to control the chiller. This module monitors refrigerant pressure, entering and leaving liquid temperatures and pressures, and outputs control for the oil reclaim valve, oil heaters, and oil pump. The CCM is the connection point for optional demand limit, automatic chilled liquid reset, 4 to 20 mA kW output, remote temperature reset, and refrigerant leak sensor. VFD POWER MODULE — This module is located in the control center (see Fig. 12). The A/C line I/O assembly executes commands from the ICVC for functions such as starting and stopping the condenser and evaporator liquid pumps, tower fan and alarm contacts. The Standard I/O Option Assembly monitors inputs such as remote start contact, spare safety, and high condenser pressure switch and provides the 4-20 mA Head Pressure Reference Output. VFD GATEWAY MODULE — The VFD Gateway Module translates the protocols between the ICVC, CCM and VFD. This module also contains logic capable of an independent safety shutdown. It shuts down the chiller if communications with the ICVC are lost. See Fig. 13 for power module component locations. OIL HEATER CONTACTOR (1C) — This contactor is located on the control panel (Fig. 14) and operates the heater at 115 V. It is controlled by the PIC III to maintain oil temperature during chiller shutdown. OIL PUMP CONTACTOR (2C) — This contactor is located in the control panel (Fig. 14) and operates the oil pump. The oil pump is controlled by the PIC III to provide oil pressure during pre-lube when the chiller is starting or running. HOT GAS BYPASS CONTACTOR RELAY (3C) (Optional) — This relay, located in the power panel, controls the opening of the hot gas bypass valve. The PIC III energizes the relay based on hot gas bypass algorithm settings. VFD REFRIGERANT COOLING SOLENOID VALVE (5C) — This solenoid is located on the VFD cooling line. The VFD cooling solenoid regulates the amount of time refrigerant is allowed to flow through the VFD cold plate to keep its temperature within operating limits. VAPORIZER HEATER CONTACTOR (6C) — This contactor is located in the control panel (Fig. 14) and energizes the surface mounted heater on the bottom of the vaporizer. CONTROL TRANSFORMERS (T1, T2) — These transformers convert incoming control voltage to 24 vac power for the power panel contactor relays, CCM, ICVC, and 21 vac power for the optional DataLINK™ or DataPort™ modules. Circuit breakers CB-1A, CB-1B, CB-2A and CB-2B for the control transformers are located above the CCM. SHRINK WRAP STRAIN RELIEF 1/8” NPT THERMOWELL REMOVABLE TEMPERATURE SENSOR a23-1624 Fig. 9 — Control Sensors (Temperature) a19-957 Fig. 10 — Control Sensors (Pressure Transducers) CONTRAST ADJUSTMENT SCREW a23-1625 Fig. 11 — ICVC Contrast Adjustment The PIC III controls are housed inside the control center enclosure. See Fig. 14. The component names are listed below (also see Table 2): Table 2 — Major PIC III Components and Panel Locations PIC III COMPONENT International Chiller Visual Controller (ICVC) and Display VFD Power Module Chiller Control Module (CCM) Oil Heater Contactor (1C) Oil Pump Contactor (2C) Hot Gas Bypass Relay (3C) (Optional) Control Transformers (T1, T2) Control Transformer Circuit Breakers (CB-1A, CB-1B, CB-2A, CB-2B) Temperature Sensors Pressure Transducers Vaporizer Heater Contactor (6C) PANEL LOCATION Control Center Panel Door Inside Control Center Control Panel Control Panel Control Panel Control Panel Control Panel Control Panel See Fig. 3 and 9 See Fig. 3 and 10 Control Panel 13 10 21 11 20 1 2 9 8 13 5 8 22 FUSE REF FU1 FU2 FU3 FU4 FU5 FU6 FU7 FU8 FU9 FU10 FU11A&B A2–F1 19 18 17 a23-1626 1 2 3 4 5 6 7 8 9 10 11 — — — — — — — — — — — 16 16 8 14 12 15 3 Input Inductor Assembly Capacitor Bank Assembly Pre-Charge Resistor Assembly AC Contactor (3) Power Module Assembly Terminal Block, 10-Position (Extra low voltage) Power Module Assembly Fuse Block, 30A, 600V, Class CC Fuse, Class CC, 600V, 15A (2) Fuse, Class CC, 600V, 5A (1) Fuse, Class CC, 600V, 20A (3) 7 4 12 13 14 15 16 17 18 19 20 21 22 — — — — — — — — — — — FUSE DESCRIPTION Class CC, 1A/600V Class CC, 1A/600V Class CC, 1A/600V 150A/600V 150A/600V 150A/600V Class CC, 20A/600V Class CC, 20A/600V Class CC, 20A/600V Class CC, 5A/600V Class CC, 15A/600V 3AG SLO–BLO 6 Fuse, Class CC, 600V, 1A (3) Transformer, 3kVA Line Sync PC Board Assembly Line Sync Board Cover Fan, 115V (3) Control Power Circuit Breaker, 600V, 15A Circuit Breaker, 600V Lug, Ground, 2-600 MCM Inductor Overtemperature Switch (Hidden) Input Power Wiring Access Panel Terminal Block (Hazardous voltage) Fig. 12 — Control Center VFD Input Components 1 2 5 3 16 4 6 20 23 7 8 25 17 9 10 18 11 26 6 7 25 20 24 3 19 8 12 10 4 21 11 8 1 13 22 14 15 a23-1627 Door Closed Door Open 1 2 3 4 5 6 7 8 9 10 11 12 13 — — — — — — — — — — — — — Wire Harness Assembly, Gate Driver Current Feedback Device, 1000 A Wire Harness Assembly, Power Supply, Logic 80 W Power Supply Assembly Terminal Block, 2-Position Cable Assembly, 40-Pin Cable Assembly, 30-Pin Wire Harness Assembly, Power Supply, Upper Gate Inverter Power Interface Assembly Wire Harness Assembly, Power Supply, Lower Gate Insulation Sheet Rectifier Power Interface Assembly Wire Harness Assembly, Current Feedback Device 14 15 16 17 18 19 20 21 22 23 24 25 26 — — — — — — — — — — — — — Wire Harness Assembly, DC Bus Bleeder Resistors Wire Harness Assembly, Line Sync Inverter Control Assembly* Standard I/O Option, 24 V Assembly Rectifier Control Assembly* AC Line I/O Assembly Connector, Terminal Block, 32-Pin NTC Assembly Internal Fan DPI Communications Interface Assembly RS-485 Communications Assembly (VFD Gateway) Wire Harness Assembly, Control Sync Cable Assembly, 20-pin *The inverter control assembly (item 16) and rectifier control assembly (item 18) are physically similar but are loaded with different software. These boards are NOT interchangeable. Fig. 13 — Power Module Components 14 PRIMARY STATUS MESSAGE HAZARDOUS VOLTAGE FIELD WIRING TERMINAL BLOCK GROUND WIRE SECONDARY STATUS MESSAGE VAPORIZER HEATER CONTACTOR (6C) CONNECTOR CNB CONTINUOUSLY • BLINKS ON FOR AN ALARM BLINKS TO • CONFIRMONCE A STOP HOT GAS BYPASS CONTACTOR (3C) (OPTIONAL) OIL PUMP CONTACTOR (2C) 24V CONTROL TRANSFORMER (T1) OIL HEATER CONTACTOR (1C) CHL IN 58.4 CDL IN CDL OUT 76.1 85.2 OIL PRESS OILTEMP –0.5 STATUS 11-22-04 00:09 15.2 HOURS CHL OUT 59.3 130.6 SCHEDULE TIME SETPOINT EVAP REF 62.1 COND REF 84.4 % AMPS IN 0.0 SERVICE STOP BUTTON FOR ONE • HOLD SECOND TO STOP 20V CONTROL TRANSFORMER (T2) SOFT KEYS CONTROL TRANSFORMER CIRCUIT BREAKERS EACH KEY'S FUNCTION IS DEFINED BY THE MENU DESCRIPTION ON MENU LINE ABOVE a23-1600 MENU LINE Fig. 15 — ICVC Default Screen HIGH PRESSURE SWITCH CABLE CONNECTOR CN2 SERVICE 23XRPIC3 ALARM HISTORY ALERT HISTORY CONTROL TEST CONTROL ALGORITHM STATUS EQUIPMENT CONFIGURATION VFD CONFIG DATA EQUIPMENT SERVICE TIME AND DATE ATTACH TO NETWORK DEVICE LOG OUT OF DEVICE ICVC CONFIGURATION CONNECTOR CN3 a23-1628 DATE MANUALLY STOPPED - PRESS CCN OR LOCAL TO START ALARM LIGHT (ILLUMINATED WHEN POWER ON) CONNECTOR CN1A COMPRESSOR ON TIME LOW VOLTAGE FIELD WIRING TERMINAL BLOCK Fig. 14 — Control Panel ICVC Operation and Menus (Fig. 15-21) GENERAL • The ICVC display automatically reverts to the default screen after 15 minutes if no softkey activity takes place (Fig. 15). • If a screen other than the default screen is displayed on the ICVC, the name of that screen is in the upper right corner (Fig. 16). • The ICVC may be set to display either English or SI units. Use the ICVC CONFIGURATION screen (accessed from the SERVICE menu) to change the units. See the Service Operation section, page 45. • Local Operation — The PIC III can be placed in local operating mode by pressing the LOCAL softkey. The PIC III then accepts commands from the ICVC only and uses the Local Time Schedule to determine chiller start and stop times. • CCN Operation — The PIC III can be placed in the CCN operating mode by pressing the CCN softkey. The PIC III then accepts modifications from any CCN interface or module (with the proper authority), as well as from the ICVC. The PIC III uses the CCN Time Schedule to determine start and stop times. a23-1601 Fig. 16 — ICVC Service Screen ALARMS AND ALERTS — An alarm shuts down the compressor. An alert does not shut down the compressor, but it notifies the operator that an unusual condition has occurred. An alarm (*) or alert (!) is indicated in the STATUS column on the right side of the MAINSTAT display screen. See Fig. 17. Alarms are indicated when the control center alarm light (!) flashes. The primary alarm message is displayed on the default screen. An additional, secondary message and troubleshooting information are sent to the ALARM HISTORY screen. When an alarm is detected, the ICVC default screen will freeze (stop updating) at the time of alarm. The freeze enables the operator to view the chiller conditions at the time of alarm. Additional information is stored in the VFD_HIST screen. The STATUS tables will show the updated information. Once all alarms have been cleared (by pressing the RESET softkey), the default ICVC screen will return to normal operation. 15 23XRPIC3 MAINSTAT Control Mode Run Status Start Inhibit Timer Occupied? System Alert/Alarm Chiller Start/Stop Remote Start Contact Temperature Reset Control Point Chilled Liquid Temp • Press ENTER to leave the selected decision or field and save changes. • Press NEXT to scroll the cursor bar down in order to highlight a point or to view more points below the current screen. • Press PREVIOUS to scroll the cursor bar up in order to highlight a point or to view points above the current screen. • Press SELECT to view the next screen level (highlighted with the cursor bar), or to override (if allowable) the highlighted point value. • Press EXIT to return to the previous screen level. • Press INCREASE or DECREASE to change the highlighted point value. POINT STATUS Reset Tripout 0.0 min No Alarm Stop CONTRL Open C 0.0 ^F 50.0 °F 55.7 °F a23-1602 Fig. 17 — Example of MAINSTAT Screen ICVC MENU ITEMS — To perform any of the operations described below, the PIC III must be powered up and have successfully completed its self test. The self test takes place automatically, after power-up. Press the MENU softkey to view the list of menu structures: STATUS , SCHEDULE , SETPOINT , and SERVICE . • The STATUS menu allows viewing and limited calibration or modification of control points and sensors, relays and contacts, and the options board. • The SCHEDULE menu allows viewing and modification of the local and CCN Time Schedules. • The SETPOINT menu allows set point adjustments, such as the ENTERING CHILLED LIQUID and LEAVING CHILLED LIQUID set points. • The SERVICE menu can be used to view or modify information on the ALARM HISTORY, ALERT HISTORY, CONTROL TEST, CONTROL ALGORITHM STATUS, EQUIPMENT CONFIGURATION, VFD CONFIG DATA, EQUIPMENT SERVICE, TIME AND DATE, ATTACH TO NETWORK DEVICE, LOG OUT OF DEVICE, AND ICVC CONFIGURATION screens. For more information on the menu structures, refer to Fig. 18. Press the softkey that corresponds to the menu structure to be viewed: STATUS , SCHEDULE , SETPOINT , or SERVICE . To view or access parameters within any of these menu structures, use the NEXT and PREVIOUS softkeys to scroll to the desired item or table. Use the SELECT softkey to select that item. The softkey choices that then appear depend on the selected table or menu. The softkey choices and their functions are described below. TO VIEW STATUS (Fig. 17) — The MAINSTAT table shows the actual value of overall chiller status such as CONTROL MODE, RUN STATUS, AUTO CHILLED LIQ RESET, and REMOTE RESET SENSOR. 1. On the menu screen, press STATUS to view the list of point status tables. BASIC ICVC OPERATIONS (Using the Softkeys) — To perform any of the operations described below, the PIC III must be powered up and have successfully completed its self test. • Press QUIT to leave the selected decision or field without saving any changes. 16 For Discrete Points — Press YES select the desired state. 2. Press NEXT or PREVIOUS to highlight the desired status table. The list of tables is: • MAINSTAT — Overall chiller status • STARTUP — Status required to perform start-up of chiller • COMPRESS — Status of sensors related to the compressor • HEAT_EX — Status of sensors related to the heat exchangers • POWER — Status of motor input power • VFD_STAT — Status of the variable frequency drive • ICVC_PSWD — Service menu password forcing access screen YES NO or ENTER NO to EXIT For Analog Points — Press INCREASE DECREASE to select the desired value. or 3. Press ENTER to register the new value. 3. Press SELECT to view the desired point status table. NOTE: When overriding or changing metric values, it is necessary to hold down the softkey for a few seconds in order to see a value change, especially on kilopascal values. To Remove an Override 1. On the point status table press NEXT or to highlight the desired value. PREVIOUS 4. On the point status table, press NEXT or PREVIOUS until the desired point is displayed on the screen. 2. Press SELECT to access the highlighted value. OVERRIDE OPERATIONS To Override a Value or Status 1. From any point status screen, press NEXT PREVIOUS to highlight the desired value. or 3. Press RELEASE to remove the override and return the point to the PIC III’s automatic control. 2. Press SELECT to select the highlighted value. Then: Override Indication — An override value is indicated by “SUPVSR,” “SERVC,” or “BEST” flashing next to the point value on the STATUS table. 17 DEFAULT SCREEN LOCAL CCN RESET MENU (SOFTKEYS) Start Chiller In CCN Control Start Chiller in Local Control Clear Alarms Access Main Menu STATUS SCHEDULE SETPOINT 1 1 1 1 (ENTER A 4-DIGIT PASSWORD) List the Status Tables List the Service Tables Display The Setpoint Table • MAINSTAT • STARTUP • COMPRESS • HEAT_EX • POWER • VFD_STAT • ICVC_PWD Select a Status Table PREVIOUS NEXT Select a Modification Point PREVIOUS NEXT Modify a Discrete Point START STOP ON OFF Modify an Analog Point INCREASE DECREASE Modify Control Options DISABLE ENABLE SERVICE List the Schedules EXIT • Base Demand Limit • LCL Setpoint • ECL Setpoint • Ice Build Setpoint • Tower Fan High Setpoint Select the Setpoint SELECT PREVIOUS NEXT SELECT EXIT Modify the Setpoint INCREASE DECREASE RELEASE ENTER RELEASE ENTER QUIT ENTER SELECT QUIT EXIT ENTER • OCCPC01S – LOCAL TIME SCHEDULE • OCCPC02S – ICE BUILD TIME SCHEDULE • OCCPC03S – CCN TIME SCHEDULE Select a Schedule SELECT PREVIOUS EXIT NEXT 1 2 3 4 5 6 7 8 Override Select a Time Period/Override SELECT PREVIOUS NEXT EXIT Modify a Schedule Time INCREASE DECREASE ENTER EXIT (ANALOG VALUES) Add/Eliminate a Day ENABLE DISABLE ENTER EXIT (DISCRETE VALUES) NEXT ALARM HISTORY ALERT HISTORY CONTROL TEST CONTROL ALGORITHM STATUS EQUIPMENT CONFIGURATION VFD CONFIG DATA EQUIPMENT SERVICE TIME AND DATE ATTACH TO NETWORK DEVICE LOG OUT OF DEVICE ICVC CONFIGURATION SELECT PREVIOUS EXIT SEE FIGURE 19 a23-1603 Fig. 18 — 23XRV ICVC Menu Structure 18 SERVICE TABLE NEXT PREVIOUS SELECT EXIT ALARM HISTORY ALERT HISTORY ALERT HISTORY Display Alert History (The table holds up to 25 alerts with the most recent alert at the top of the screen.) Display Alarm History (The table holds up to 25 alarms and alerts with the most recent alarm at the top of the screen.) CONTROL TEST List the Control Tests • Thermistors • Pressure Transducers • Pumps • Discrete Outputs • Oil Reclaim Output • Head Pressure Output • Pumpdown/Lockout • Terminate Lockout CONTROL ALGORITHM STATUS List the Control Algorithm Status Tables • CAPACITY (Capacity Control) • OVERRIDE (Override Status) • LL_MAINT (Lead Lag Status) • VFD_HIST (VFD Alarm History) • CUR ALRM (Chiller Alarm History) • WSMCHLRE (Water System Manager) • OCCDEFCM (Time Schedule Status) Select a Table SELECT PREVIOUS NEXT Select a Test NEXT PREVIOUS SELECT EXIT EXIT OCCDEFM (Time Schedule Status) Data Select Table PREVIOUS NEXT SELECT • CAPACITY (Capacity Control Algorithm) • OVERRIDE (Override Status) • LL_MAINT (LEADLAG Status) • WSMDEFME (Water System Manager Control Status) EXIT OCCPC01S (Local Status) OCCPC02S (CCN, ICE BUILD Status) OCCPC03S (CCN Status) EQUIPMENT CONFIGURATION Maintenance Table Data List the Equipment Configuration Tables • NET_OPT • BRODEF • OCCEFCS • HOLIDAYS • CONSUME • RUNTIME Select a Table PREVIOUS NEXT EXIT Select a Parameter PREVIOUS NEXT SELECT EXIT Modify a Parameter INCREASE DECREASE QUIT ENTER (ANALOG VALUES) QUIT ENTER (DISCRETE VALUES) ENABLE CONTINUED ON NEXT PAGE SELECT DISABLE a23-1604 Fig. 19 — 23XRV Service Menu Structure 19 SERVICE MENU CONTINUED FROM PREVIOUS PAGE VFD CONFIG DATA EQUIPMENT SERVICE 4 4 4 4 (ENTER A 4-DIGIT PASSWORD) Service Tables: • OPTIONS • SETUP1 • SETUP2 • LEADLAG • RAMP_DEM • TEMP_CTL Select a Service Table PREVIOUS NEXT Service Tables: • VFD CONFIG P ASSWORD • VFD_CONF SELECT EXIT Select a Service Table Parameter SELECT PREVIOUS NEXT EXIT Modify a Service Table Parameter INCREASE DECREASE QUIT ENABLE DISABLE QUIT ENTER (ANALOG VALUES) ENTER (DISCRETE VALUES) TIME AND DATE Display Time and Date Table: • To Modify — Current Time — Current Date INCREASE DECREASE ENTER ATTACH TO NETWORK DEVICE List Network Devices • Device 6 • Local • Device 1 • Device 7 • Device 2 • Device 8 • Device 3 • Attach To Any Device • Device 4 • Device 5 Select a Device PREVIOUS NEXT SELECT YES NO ENTER — Day of Week — Holiday Today (ANALOG VALUES) EXIT EXIT (DISCRETE VALUES) ATTACH Modify Device Address INCREASE DECREASE ENTER EXIT • Use to attach ICVC to another CCN network or device • Attach to "LOCAL" to enter this machine • To upload new tables LOG OUT OF DEVICE Default Screen LOCAL CCN RESET MENU ICVC CONFIGURATION CCN ICVC — — IMP — VFD — PIC III — LEGEND Carrier Comfort Network® International Chiller Visual Controller Imperial Variable Frequency Drive Product Integrated Control III ICVC Configuration Table INCREASE DECREASE ENTER EXIT • To View — ICVC Software Version • To Modify — ICVC CCN Address (last 2 digits of part number — Baud Rate indicate software version) — English (US IMP) or S.I. Metric Units — Password a23-1605 — LID Language Fig. 19 — 23XRV Service Menu Structure (cont) 20 TIME SCHEDULE OPERATION (Fig. 20) 1. On the Menu screen, press SCHEDULE . b. Press ENABLE to select days in the day-of-week fields. Press DISABLE to eliminate days from the period. 2. Press NEXT or PREVIOUS to highlight the desired schedule. 7. Press ENTER to register the values and to move horizontally (left to right) within a period. OCCPC01S — LOCAL Time Schedule OCCPC02S — ICE Build Schedule OCCPC03S — CCN Time Schedule 8. Press EXIT to leave the period or override. 3. Press SELECT to view the desired time schedule. 9. Either return to Step 4 to select another period or override, or press EXIT again to leave the current time schedule screen and save the changes. 4. Press NEXT or PREVIOUS to highlight the desired period or override to change. 10. The Holiday Designation (HOLIDAYS table) may be found in the Service Operation section, page 45. The month, day, and duration for the holiday must be assigned. The TIME BROADCAST ENABLE function in the BRODEF screen also must be enabled for holiday periods to function. TO VIEW AND CHANGE SET POINTS (Fig. 21) 1. To view the SETPOINT table, from the MENU screen press SETPOINT . 5. Press SELECT to access the highlighted period or override. 6. a Press INCREASE or DECREASE to change the time values. Override values are in one-hour increments, up to 4 hours. 23XRPIC3 SETPOINT Base Demand Limit Control Point Source LCL Setpoint ECL Setpoint Ice Build Setpoint Tower Fan High Setpoint 23XRPIC3 SETPOINT SELECT 100% 50.0 °F 60.0 °F 40.0 °F 75 °F a23-1607 Fig. 21 — Example of Set Point Screen a23-1606 Fig. 20 — Example of Time Schedule Operation Screen 21 5. Press INCREASE or DECREASE to change the selected set point value. 2. There are 5 set points on this screen: BASE DEMAND LIMIT, LCL SETPOINT (leaving chilled liquid set point), ECL SETPOINT (entering chilled liquid set point), ICE BUILD SETPOINT and TOWER FAN HIGH SETPOINT. Only one of the CONTROL POINT SOURCES (LCL or ECL) can be active at one time. The control point source that is active is determined from the TEMP_CTL screen. See the Service Operation section, page 45. 3. Press NEXT or PREVIOUS to highlight the desired set point entry. 6. Press ENTER to save the changes and return to the previous screen. SERVICE OPERATION — To view the menu-driven programs available for Service Operation, see Service Operation section, page 45. For examples of ICVC display screens, see Table 3. 4. Press SELECT to modify the highlighted set point. Table 3 — ICVC Display Data by the CCN, BSI, LEI, and the ICVC. Capitalized Reference Point Names preceded by two asterisks can be changed only from the ICVC. Reference Point Names in lower case type can be viewed by CCN or BSI only by viewing the whole table. 7. Alarms and Alerts: An asterisk in the far right field of a ICVC status screen indicates that the chiller is in an alarm state; an exclamation point in the far right field of the ICVC screen indicates an alert state. The asterisk (or exclamation point) indicates that the value on that line has exceeded (or is approaching) a limit. For more information on alarms and alerts, see the Alarms and Alerts section, page 15. 8. Index of all ICVC Parameters is shown in Appendix A. IMPORTANT: The following notes apply to all Table 3 examples. 1. Only 12 lines of information appear on the ICVC screen at any one time. Press the NEXT or PREVIOUS softkey to highlight a point or to view items below or above the current screen. Double-click the NEXT softkey to page forward; double-click the PREVIOUS softkey to page back. 2. To access the information shown in Examples 9 through 23, enter your 4-digit password after pressing the SERVICE softkey. If no softkeys are pressed for 15 minutes, the ICVC automatically logs off (to prevent unrestricted access to PIC III controls) and reverts to the default screen. If this happens, you must re-enter your password to access the tables shown in Examples 9 through 23. 1CR CCN CHL CR CT I2T ICVC ECL HGBP LCL LRA mA P T VFD WSM °F ˆF 3. Terms in the Description column of these tables are listed as they appear on the ICVC screen. 4. The ICVC may be configured in English or Metric (SI) units using the ICVC CONFIGURATION screen. See the Service Operation section, page 45, for instructions on making this change. 5. The items in the Reference Point Name column do not appear on the ICVC screen. They are data or variable names used in CCN, Building Systems Interface (BSI) or Local Equipment Interface (LEI) Module software (optional). They are listed in these tables as a convenience to the operator if it is necessary to cross reference CCN/BSI documentation or use CCN/BSI programs. For more information, see the CCN literature. 6. Reference Point Names shown in these tables in all capital letters can be read by CCN and BSI software. Of these capitalized names, those preceded by a dagger can also be changed (that is, written to) — — — — — — — — — — — — — — — — — — LEGEND Control Relay Carrier Comfort Network® Chilled Liquid Control Relay Current Transformer Motor Overload International Chiller Visual Controller Entering Chilled Liquid Hot Gas Bypass Leaving Chilled Liquid Locked Rotor Amps Milliamps Pressure Temperature Variable Frequency Drive Liquid System Manager Temperature in Degrees Fahrenheit Temperature Difference in Degrees Fahrenheit EXAMPLE 1 — ICVC DEFAULT SCREEN The following data is displayed in the ICVC Default screen. DESCRIPTION (PRIMARY MESSAGE) (SECONDARY MESSAGE) (DATE AND TIME) Compressor Ontime Entering Chilled Liquid Leaving Chilled Liquid Evaporator Refrigerant Temperature* Entering Condenser Liquid Leaving Condenser Liquid Condenser Refrigerant Temperature Oil Pressure Delta P Oil Sump Temp Percent Line Current CCN LOCAL RESET RANGE 0-500000.0 –40-245 –40-245 –40-245 –40-245 –40-245 –40-245 –6.7-425 –40-245 0-999 0-1 0-1 0-1 UNITS HOURS °F (°C) °F (°C) °F (°C) °F (°C) °F (°C) °F (°C) PSI (kPa) °F (°C) % REFERENCE POINT NAME (ALARM HISTORY) C_HRS ECL LCL ERT_EST ECDL LCDL CRT OIL_PD OILT AMPS_P CCN LOCAL RESET *The Evaporator Refrigerant Temperature displayed is the smaller value of EVAP REFRIG LIQUID TEMP or CALC EVAP SAT TEMP. NOTE: The last three entries are used to indicate operating mode to the PIC III. These values may be forced by the ICVC only. 22 DISPLAY CHL IN CHL OUT EVAP REF CDL IN CDL OUT COND REF OILPRESS OIL TEMP % AMPS IN Table 3 — ICVC Display Data (cont) EXAMPLE 2 — MAINTSTAT DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press MENU . 2. Press STATUS ( MAINSTAT will be highlighted). 3. Press SELECT . DESCRIPTION Control Mode Run Status Start Inhibit Timer Occupied ? System Alert/Alarm *Chiller Start/Stop *Remote Start Contact Temperature Reset *Control Point Chilled Liquid Temp *Active Demand Limit Percent Line Current Percent Line Kilowatts Auto Demand Limit Input Auto Chilled Liq Reset Remote Reset Sensor †Total Compressor Starts Starts in 12 Hours †Compressor Ontime **Service Ontime Ice Build Contact Refrigerant Leak Sensor PPM Emergency Stop STATUS NOTE 2 NOTE 3 0-15 0/1 0-2 0/1 0/1 –30-30 10-65 –40-245 40-100 0.0-9999 0.0-9999 4-20 4-20 –40-245 0-99999 0-8 0-500000.0 0-32767.0 0/1 0.0-9999.0 0/1 UNITS NOTE 2 NOTE 3 min NO/YES NOTE 4 STOP/START OPEN/CLOSE ^ F (^ C) ° F (° C) ° F (° C) % % % mA mA ° F (°C) HOURS HOURS OPEN/CLOSE mA ENABLE/EMSTOP POINT MODE STATUS T_START OCC SYS_ALM CHIL_S_S REMCON T_RESET LCW_STPT CHL_TMP DEM_LIM LN AMPS_P LINE KW_P AUTODEM AUTORES R_RESET C_STARTS STARTS C_HRS S_HRS ICE_CON REF_LEAK EMSTOP NOTES: 1. Numbers in parentheses indicate the equivalent CCN BEST++™ programming LEI or BACnet™ Translator use. 2. Off (0), Local (1), CCN (2), Reset (3) 3. Timeout (0), Ready (1), Recycle (2), Startup (3), Running (4), Demand (5), Ramping (6), Auto Restart (7), Override (8), Tripout (9), Control Test (10), Lockout (11), Pumpdown (12), Prestart (13) 4. Normal (0), Alert (1), Alarm (2). 5. All variables with capital letter point names are available for CCN read operation. Those shown with (*) support write operations for all CCN and LEI devices. Those shown with (†) shall support one time write operations for the ICVC only when the value is initially zero. Those shown with (**) shall support write operations for the ICVC only. EXAMPLE 3 — STARTUP DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press MENU . 2. Press STATUS . 3. Scroll down to highlight STARTUP . 4. Press SELECT . DESCRIPTION **Chilled Liquid Pump Chilled Liquid Flow **Condenser Liquid Pump Condenser Liquid Flow Oil Pump Relay Oil Reclaim Output **Oil Pressure Delta P Oil Sump Temp Vaporizer Temp VFD Start Start Complete Stop Complete VFD Speed Output Comp Motor RPM Comp Motor Frequency Comp Maximum Speed Comp Minimum Speed **Tower Fan Relay Low **Tower Fan Relay High Spare Safety Input Shunt Trip Relay STATUS 0-1 0-1 0-1 0-1 0-1 0-100.0 –6.7-200 –40.0-245.0 –40.0-245.0 0-1 0-1 0-1 0.0-100.0 0-300000 0-10000 0-101 0-100 0-1 0-1 0-1 0-1 UNITS OFF/ON NO/YES OFF/ON NO/YES OFF/ON %(4 to 20mA) PSI (kPa) ° F (° C) ° F (° C) NO/YES FALSE/TRUE FALSE/TRUE % RPM Hz Hz % OFF/ON OFF/ON ALARM/NORMAL OFF/ON NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation. Those shown with (**) shall support write operations for the ICVC only. 23 POINT CHLP CHL_FLOW CDP CDL_FLOW OILR OIL_MA OILPD OILT VAP_TEMP VFDSTART START_OK STOP_OK VFD_OUT CPR_RPM VFD_FREQ MAXSPEED MINSPEED TFR_LOW TFR_HIGH SAFETY TRIPR Table 3 — ICVC Display Data (cont) EXAMPLE 4 — COMPRESS DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press MENU . 2. Press STATUS . 3. Scroll down to highlight COMPRESS . 4. Press SELECT . DESCRIPTION Actual VFD Speed Compressor Motor RPM Compressor Motor Frequency Compressor Maximum Speed Compressor Minimum Speed VFD Delta **Target VFD Speed VFD Speed Output Oil Pump Relay **Oil Pressure Delta P Oil Sump Temp Vaporizer Temperature Oil Heater Relay Vaporizer Heater Comp Motor Winding Temp Comp Discharge Temp Discharge Superheat Stall Protection Counts Spare Temperature 1 Spare Temperature 2 STATUS 0-115 0-300000 0-10000 0-101 0-100 –2-2 0-100 0-100 0/1 –6.7-420 –40-245 –40-245 0/1 0/1 –40-245 –40-245 –20-999 0-5 –40-245 –40-245 UNITS % RPM Hz Hz % % % % OFF/ON PSI (kPa) ° F (° C) ° F (° C) OFF/ON OFF/ON ° F (° C) ° F (° C) ^F (^C) ° F (° C) ° F (° C) POINT VFD_ACT CPR_RPM VFD_FREQ MAXSPEED MINSPEED VFDDELTA VFD_TRG VFD_OUT OILR OILPD OILT VAP_TEMP OILHEAT VAP_HEAT MTRW CMPD SUPRHEAT SPC SPARE_T1 SPARE_T2 NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation; those with (**) shall support write operations for ICVC only. EXAMPLE 5 — HEAT_EX DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press MENU . 2. Press STATUS . 3. Scroll down to highlight HEAT_EX . 4. Press SELECT . DESCRIPTION **Chilled Liquid Delta P Entering Chilled Liquid Leaving Chilled Liquid Chilled Liquid Delta T Chill Liq Pulldown/Min Calc Evap Sat Temp **Evaporator Pressure Evap Refrig Liquid Temp Evaporator Approach **Condenser Liquid Delta P Entering Cond Liquid Leaving Cond Liquid Condenser Refrig Temp **Condenser Pressure Condenser Approach Vaporizer Temp Reclaim Delta T Oil Reclaim Output VFD Coolant Flow Hot Gas Bypass Relay Active Delta P Active Delta T HGBP Delta T Head Pressure Reference STATUS –6.7-420 –40-245 –40-245 –40-245 –20-20 –40-245 –6.7-420 –40-245 0-99 –6.7-420 –40-245 –40-245 –40-245 –6.7-420 0-99 –40-245 –500-500 0-100 0-100 0/1 0-200 0-200 0-200 0-100 UNITS PSI (kPa) ° F (° C) ° F (° C) ^F (^C) ^F (^C) ° F (° C) PSI (kPa) ° F (° C) ^F (^C) PSI (kPa) ° F (° C) ° F (° C) ° F (° C) PSI (kPa) ^F (^C) ° F (° C) ^F (^C) % % OFF/ON PSI (kPa) ^F (^C) ^F (^C) % NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation; those with (**) shall support write operations for ICVC only. 24 POINT CHLPD ECL LCL CHL_DT CHL_PULL ERT ERP EST EVAP_APP CDLPD ECDL LCDL CRT CRP COND_APP VAP_TEMP R_DELTA OIL_MA VFD_FOUT HGBYPASS DP_A DT_A DT_C HPR Table 3 — ICVC Display Data (cont) EXAMPLE 6 — POWER DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press MENU . 2. Press STATUS . 3. Scroll down to highlight POWER . 4. Press SELECT . DESCRIPTION Percent Line Current Average Line Current Percent Line Voltage Average Line Voltage Line Power Factor Line Kilowatts Percent Line Kilowatts Percent Load Current Average Load Current Motor Power Factor Motor Kilowatts Percent Motor Kilowatts Motor Kilowatt-Hours Demand Kilowatts Line Current Phase 1 (R) Line Current Phase 2 (S) Line Current Phase 3 (T) Load Current Phase 1 (U) Load Current Phase 2 (V) Load Current Phase 3 (W) Line Voltage Phase 1 (RS) Line Voltage Phase 2 (ST) Line Voltage Phase 3 (TR) Ground Fault Current Line Frequency Rectifier Overload Inverter Overload Motor Overload Line Current Imbalance Motor Current Imbalance Line Voltage Imbalance Line Active Current Line Reactive Current Line Active Voltage Line Reactive Voltage DC Bus Voltage Reference DC Bus Voltage Flux Current Torque Current Inverter Temperature Rectifier Temperature VFD Enclosure Temperature VFD Cold Plate Temperature Humidity Sensor Input Relative Humidity VFD Coolant Flow Actual VFD Speed Comp Motor RPM Comp Motor Frequency Comp Maximum Speed Comp Minimum Speed STATUS 0-999 0-99999 0-999 0-99999 0.0-2.0 0-99999 0-99999 0-99999 0-99999 0.0-2.0 0-99999 0-99999 0-99999 0-99999 0-99999 0-99999 0-99999 0-99999 0-99999 0-99999 0-99999 0-99999 0-99999 0-999 0-99 0-100 0-100 0-100 0-100 0-100 0-100 0-99999 0-99999 0-99999 0-99999 0-99999 0-99999 0-99999 0-99999 0-300 0-300 0-300 0-300 0.0-5.0 0-100 0-100 0-100 0-300000 0-10000 0-101 0-100 UNITS % AMPS % VOLTS KW % % AMPS KW % KWH KW AMPS AMPS AMPS AMPS AMPS AMPS VOLTS VOLTS VOLTS AMPS HZ % % % % % % AMPS AMPS VOLTS VOLTS VOLTS VOLTS AMPS AMPS ° F (° C) ° F (° C) ° F (° C) ° F (° C) VOLTS % % % RPM Hz Hz % NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation. 25 POINT LNAMPS_P LNAMPS_A LNVOLT_P LNVOLT_A LINE_PF LINE_KW LINEKW_P LDAMPS_P LDAMPS_A MOTOR_PF MOTOR_KW MOTORKWP MOTORKWH DEM_KW LN_AMPS1 LN_AMPS2 LN_AMPS3 LD_AMPS1 LD_AMPS2 LD_AMPS3 LN_VOLT1 LN_VOLT2 LN_VOLT3 GF_AMPS LINEFREQ RECT_OV INV_OV MOTOR_OV LN_IMB_I MT_IMB_I LN_IMB_V AMPS_ACT AMPS_RE VOLT_ACT VOLT_RE BUS_REF BUS_VOLT FLUXAMPS TORQAMPS INV_TEMP REC_TEMP VFD_ENCL CP_TEMP HUMID_SR HUMIDITY VFD_FOUT VFD_ACT CPR_RPM VFD_FREQ MAXSPEED MINSPEED Table 3 — ICVC Display Data (cont) EXAMPLE 7 — VFD VFD_STAT SCREEN To access this display from the ICVC default screen: 1. Press MENU . 2. Press STATUS . 3. Scroll down to highlight VFD_STAT . 4. Press SELECT . DESCRIPTION VFD Fault Code Single Cycle Dropout Line Current Imbalance Line Voltage Imbalance Line Phase Reversal High Line Voltage Low Line Voltage High DC Bus Voltage Low DC Bus Voltage Motor Current Imbalance Motor Overload Rectifier Overcurrent Rectifier Overtemp Rectifier Power Fault Inverter Overcurrent Inverter Overtemp Inverter Power Fault Ground Fault Frequency Fault VFD Power on Reset Start Complete Stop Complete Condenser High Pressure Motor Amps Not Sensed Start Acceleration Fault Stop Fault VFD Start Inhibit VFD Checksum Error VFD Comm Fault VFD Fault VFD Gateway Version # VFD Inverter Version # VFD Rectifier Version # STATUS 0-272 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-255 0-1000 0-1000 UNITS NORMAL/ALARM NORMAL/ALARM NORMAL/ALARM NORMAL/ALARM NORMAL/ALARM NORMAL/ALARM NORMAL/ALARM NORMAL/ALARM NORMAL/ALARM NORMAL/ALARM NORMAL/ALARM NORMAL/ALARM NORMAL/ALARM NORMAL/ALARM NORMAL/ALARM NORMAL/ALARM NORMAL/ALARM NORMAL/ALARM NORMAL/ALARM FALSE/TRUE FALSE/TRUE NORMAL/ALARM NORMAL/ALARM NORMAL/ALARM NORMAL/ALARM NORMAL/ALARM NORMAL/ALARM NORMAL/ALARM NORMAL/ALARM POINT VFD_FLT CYCLE_1 LINEIM_I LINEIM_V PH_REV HI_VOLT LOW_VOLT HI_DCBUS LO_DCBUS MOTIM_I MOTOR_OV RECT_OI RECT_OT RECT_PU INV_OI INV_OT INV_PU GRND_FLT FREQFLT VFD_POR START_OK STOP_OK PRS_TRIP NO_AMPS ACCELFLT AMPSTOP STRT_INH CHECKSUM VFD_COMM VFDFAULT VFG_VER INV_VER REC_VER NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation. EXAMPLE 8 — ICVC PWD To access this display from the ICVC default screen: 1. Press MENU . 2. Press STATUS 3. Scroll down to highlight ICVC_PWD . DESCRIPTION Disable Service Password **Remote Reset Option Reset Alarm ? CCN Mode ? STATUS 0-1 0-1 0-1 0-1 UNITS DS/ENABLE DS/ENABLE NO/YES NO/YES POINT PSWD_DIS RESETOPT REMRESET REM_CCN NOTE: The Disable Service Password parameter supports the service tool password disable access. It will only allow forcing with the service tool for a one time bypass of both the service menu and the VFD config data table. Exit from the service menu reverts to normal password operation. Those with (**) shall support write operations for ICVC only. The Reset Alarm? and CCN mode? parameters support write operations from CCN and LEI devices when the Remote Reset Option is enabled. 26 Table 3 — ICVC Display Data (cont) EXAMPLE 9 — SETPOINT DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press MENU . 2. Press SETPOINT (Base Demand Limit will be highlighted). 3. Press SELECT . DESCRIPTION Base Demand Limit Control Point Source LCL Setpoint ECL Setpoint Ice Build Setpoint Tower Fan High Setpoint STATUS 40-100 UNITS % POINT DLM DEFAULT 100 10-60 F (-12.2-15.6 C) 15-65 F (-9.4-18.3 C) 15-60 F (-9.4-15.6 C) 55-105 F (13-41 C) ° F (° C) ° F (° C) ° F (° C) ° F (° C) lcl_sp ecl_sp ice_sp TFH_sp 50.0 F (10.0 C) 60.0 F (15.6 C) 40 F (4.4 C) 75 F (23.9 C) NOTE: No variables are available for CCN read operation; forcing shall not be supported on setpoint screens. EXAMPLE 10 — CAPACITY DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press MENU . 2. Press SERVICE . 3. Scroll down to highlight CONTROL ALGORITHM STATUS . 4. Press SELECT . 5. Scroll down to highlight CAPACITY . DESCRIPTION Entering Chilled Liquid Leaving Chilled Liquid Capacity Control Control Point Control Point Error ECL Delta T ECL Reset LCL Reset Total Error + Resets Cap Delta VFD Delta Target VFD Speed Actual VFD Speed Comp Motor RPM Comp Motor Frequency Comp Maximum Speed Comp Minimum Speed VFD Speed Output VFD Gain Demand Limit Inhibit Amps/kW Ramp STATUS –40-245 –40-245 UNITS ° F (°C) ° F (°C) POINT ECL LCL 10-65 –99-99 –99-99 –99-99 –99-99 –99-99 –2-2 –2-2 0-100 0-110 0-300000 0-10000 0-101 0-100 0-110 0.1-1.5 0.2-1 0-100 ° F (°C) ^F (^C) ^F (^C) ^F (^C) ^F (^C) ^F (^C) % % % % RPM Hz Hz % % ctrlpt cperr ecldt eclres lclres error capdelta vfddelta VFD_TRG VFD_ACT CPR_RPM VFD_FREQ MAXSPEED MINSPEED VFD_OUT vfd_gain DEM_INH RAMP_LMT % % NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation; forcing shall not be supported on maintenance screens. 27 Table 3 — ICVC Display Data (cont) EXAMPLE 11 — OVERRIDE DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press MENU . 2. Press SERVICE . 3. Scroll down to highlight CONTROL ALGORITHM STATUS . 4. Press SELECT . 5. Scroll down to highlight OVERRIDE . DESCRIPTION Comp Motor Winding Temp Comp Motor Temp Override Condenser Pressure Cond Press Override Calc Evap Sat Temp Evap Sat Override Temp Comp Discharge Temp Comp Discharge Alert Rectifier Temperature Rectifier Temp Override Inverter Temperature Inverter Temp Override Discharge Superheat Condenser Refrig Temp STATUS –40-245 150-200 –6.7-420 150-260 –40-245 2-45 –40-245 125-200 0-300 125-200 0-300 125-200 –20-999 –40-245 UNITS ° F (°C) ° F (°C) PSI (kPa) PSI (kPa) ° F (°C) ° F (°C) ° F (°C) ° F (°C) ° F (°C) ° F (°C) ° F (°C) ° F (°C) ^F (^C) ° F (°C) POINT MTRW MT_OVER CRP CP_OVER ERT ERT_OVER CMPD CD_ALERT RECT_TEMP REC_OVER INV_TEMP INV_OVER SUPRHEAT CRT NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation; forcing shall not be supported on maintenance screens. EXAMPLE 12 — LL_MAINT DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press MENU . 2. Press SERVICE . 3. Scroll down to highlight CONTROL ALGORITHM STATUS . 4. Press SELECT . 5. Scroll down to highlight LL_MAINT . DESCRIPTION Lead Lag Control LEADLAG: Configuration Current Mode Load Balance Option LAG Start Time LAG Stop Time Prestart Fault Time Pulldown Time Pulldown: Delta T/Min Satisfied ? LEAD CHILLER in Control LAG CHILLER: Mode Run Status Start/Stop Recovery Start Request STANDBY CHILLER: Mode Run Status Start/Stop Recovery Start Request Spare Temperature 1 Spare Temperature 2 STATUS NOTE 1 NOTE 1 NOTE 2 0/1 0-60 0-60 0-60 0.0-30.0 XX.X 0/1 0/1 NOTE 3 NOTE 4 NOTE 5 0/1 NOTE 3 NOTE 4 NOTE 5 0/1 –40-245 –40-245 UNITS DSABLE/ENABLE MIN MIN MIN MIN ^F (^C) NO/YES NO/YES NO/YES NO/YES ° F (°C) ° F (°C) POINT leadlag llmode loadbal lagstart lagstop preflt pulltime pull_dt pull_sat leadctrl lagmode lagstat lag_s_s lag_rec stdmode stdstat std_s_s std_rec SPARE_T1 SPARE_T2 NOTES: 1. DISABLE, LEAD, LAG, STANDBY, INVALID 2. DISABLE, LEAD, LAG, STANDBY, RECOVERY, CONFIG 3. Reset, Off, Local, CCN, Blank 4. Timeout, Ready, Recycle, Prestart, Startup, Ramping, Running, Demand, Override, Shutdown, Trippout, Pumpdown, Lockout, ‘Blank’ 5. Stop, Start, Retain, ‘Blank’ 6. All variables with CAPITAL LETTER point names are available for CCN read operation; forcing shall not be supported on maintenance screens. 28 Table 3 — ICVC Display Data (cont) EXAMPLE 13 — VFD_HIST DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press MENU . 2. Press SERVICE . 3. Scroll down to highlight CONTROL ALGORITHM STATUS . 4. Press SELECT . 5. Scroll down to highlight VFD_HIST . DESCRIPTION VFD FAULT HISTORY Values At Last Fault: Line Current Phase 1 (R) Line Current Phase 2 (S) Line Current Phase 3 (T) Load Current Phase 1 (U) Load Current Phase 2 (V) Load Current Phase 3 (W) Line Voltage Phase 1 (RS) Line Voltage Phase 2 (ST) Line Voltage Phase 3 (TR) Ground Fault Current Line Frequency Line Power Factor Line Current Imbalance Line Voltage Imbalance Motor Power Factor Motor Current Imbalance Motor Overload Line Active Current Line Reactive Current Line Active Voltage Line Reactive Voltage DC Bus Voltage DC Bus Voltage Reference Flux Current Torque Current Inverter Temperature Rectifier Temperature VFD Enclosure Temp VFD Cold Plate Temp Actual VFD Speed Comp Motor RPM Comp Motor Frequency Chiller Fault State VFD Fault Code STATUS UNITS 0-99999 0-99999 0-99999 0-99999 0-99999 0-99999 0-99999 0-99999 0-99999 0-999 0-99 0-2.0 0-100 0-100 0-2.0 0-100 0-100 0-99999 0-99999 0-99999 0-99999 0-99999 0-99999 AMPS AMPS AMPS AMPS AMPS AMPS VOLTS VOLTS VOLTS AMPS Hz % % % % AMPS AMPS VOLTS VOLTS VOLTS VOLTS 0-99999 0-99999 0-300 0-300 0-300 0-300 0-100 0-300000 0-10000 200-272 200-272 AMPS AMPS ° F (°C) ° F (°C) ° F (°C) ° F (°C) % RPM Hz POINT LNAMPS1H LNAMPS2H LNAMPS3H LDAMPS1H LDAMPS2H LDAMPS3H LNVOLT1H LNVOLT2H LNVOLT3H GF_AMPSH LINEFRQH LINE_PFH LN_IMBIH LN_IMBVH MOTORPFH MT_IMBIH MOTOROVH AMPSACTH AMPS_REH VOLTACTH VOLT_REH BUSVOLTH BUS_REFH FLUXAMPH TORQAMPH INVTEMPH RECTEMPH VFDENCLH CP_TEMPH VFD_ACTH CPR_RPMH VFDFREQH VFDSTATH VFD_FLTH NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation; forcing shall not be supported on maintenance screens. EXAMPLE 14 — LOADSHED DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press MENU . 2. Press SERVICE . 3. Scroll down to highlight CONTROL ALGORITHM STATUS . 4. Press SELECT . 5. Scroll down to highlight LOADSHED . DESCRIPTION LOADSHED FUNCTION Redline Loadshed Loadshed Timer STATUS UNITS 0-1 0-1 0-480 NO/YES NO/YES NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation; forcing shall not be supported on maintenance screens. 29 POINT REDLINE LOADSHED LOADTIME Table 3 — ICVC Display Data (cont) EXAMPLE 15 — WSMCHLRE DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press MENU . 2. Press SERVICE . 3. Scroll down to highlight CONTROL ALGORITHM STATUS . 4. Press SELECT . 5. Scroll down to highlight WSMDEFME . DESCRIPTION WSM Active? Chilled Water Temp Equipment Status Commanded State CHW Setpoint Reset Value Current CHW Set Point STATUS 0/1 0.0-99.9 0/1 UNITS NO/YES ° F (°C) OFF/ON TEXT ^ F (^C) ° F (°C) 0.0-25.0 0.0-99.9 POINT WSMSTAT CHWTEMP CHWRST CHWRENA CHWRVAL CHWSTPT NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation; forcing shall not be supported on maintenance screens. EXAMPLE 16 — NET_OPT DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press MENU . 2. 3. 4. 5. Press SERVICE . Scroll down to highlight EQUIPMENT CONFIGURATION . Press SELECT . Scroll down to highlight NET_OPT . DESCRIPTION Loadshed Function Group Number Demand Limit Decrease Maximum Loadshed Time CCN Occupancy Config: Schedule Number Broadcast Option Alarm Configuration Re-Alarm Time Alarm Routing STATUS UNITS POINT DEFAULT 1-16 0-60 30-480 % MIN LDSGRPN LDSDLTA MAXSHED 0 20 120 3-99 0-1 DSABLE/ENABLE OCC_NUM OCCBRCST 3 DSABLE RETIME ROUTING 30 10000000 0-1440 0-1 MIN NOTE: No variables are available for CCN read or write operation. 30 Table 3 — ICVC Display Data (cont) EXAMPLE 17 — VFD_CONF DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press MENU . 2. Press SERVICE . 3. Scroll down to highlight VFD CONFIG DATA . 4. Press SELECT . 5. Scroll down to highlight VFD_CONF . DESCRIPTION Motor Nameplate Voltage Compressor 100% Speed * Rated Line Voltage * Rated Line Amps * Rated Line Kilowatts *Motor Rated Load KW *Motor Rated Load Amps Motor Nameplate Amps Motor Nameplate RPM Motor Nameplate kW Inverter PWM Frequency (0=4 kHz, 1=2 kHz) Skip Frequency 1 Skip Frequency 2 Skip Frequency 3 Skip Frequency Band Line Voltage % Imbalance Line Voltage Imbal Time Line Current % Imbalance Line Current Imbal Time Motor Current % Imbalance Motor Current Imbal Time Increase Ramp Time Decrease Ramp Time Single Cycle Dropout STATUS 480-480 54-101 346-480 10-5000 0-999999 0-999999 10-5000 10-5000 1500-3030 0-999999 0/1 UNITS VOLTS Hz VOLTS AMPS KW KW AMPS AMPS 0-102 0-102 0-102 0-102 1-10 1-10 5-40 1-10 5-40 1-10 5-60 5-60 0/1 Hz Hz Hz Hz % SEC % SEC % SEC SEC SEC DSABLE/ENABLE KW POINT motor_nv comp_100 vfd_volt vfd_amps vfd_rlkw mot_rlkw mot_rla motorni motorpm motorkw pwm_freq DEFAULT 480 70 460 200 100 100 200 100 2672 100 0 skipfrq1 skipfrq2 skipfrq3 skipband v_umbal v_time lineim_i lineim_t motim_i motim_t ramp_inc ramp_dec cycdrop 102 102 102 0 10 10 40 10 40 10 30 30 DSABLE NOTE: Those parameters marked with a * shall not be downloaded to the VFD, but shall be used in other calculations and algorithms in the ICVC. EXAMPLE 18 — OPTIONS DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press MENU . 2. Press SERVICE . 3. Scroll down to highlight EQUIPMENT SERVICE . 4. Press SELECT . 5. Scroll down to highlight OPTIONS . DESCRIPTION Auto Restart Option Remote Contacts Option Soft Stop Amps Threshold Hot Gas Bypass HGBP Option Min. Load Point (T1,P1) HGBP Delta T1 HGBP Delta P1 Full Load Point (T2,P2) HGBP Delta T2 HGBP Delta P2 HGBP Deadband HGBP On Delta T HGBP Off Delta T Stall Protection Stall Delta % Amps Stall Time Period Ice Build Control Ice Build Option Ice Build Termination (0=TEMP, 1=Contact, 2=Both) Ice Build Recycle Refrigerant Leak Option PPM at 20mA Refrig Leak Alarm PPM Head Pressure Reference Delta P at 0% (4mA) Delta P at 100% (20mA) Minimum Output STATUS 0/1 0/1 40-100 UNITS DSABLE/ENABLE DSABLE/ENABLE % POINT astart r_contac softstop 0, 1, 2 0=DSABLE 1=HGBP 2=LOW LOAD HGBP Srg_hgbp DSABLE 0.5-20 (0.3-11.1) 10-170 (68.9-1172.2) ^F (^C) PSI (kPa) hgbp_dt1 hgbp_dp1 1.5 (0.8) 150 (1034.2) 0.5-20 (0.3-11.1) 30-250 (206.9-1724) 0.5-3 (0.3-1.7) 0.5-10.0 (0.3-5.6) 1.0-10.0 (0.6-5.6) ^F (^C) PSI (kPa) ^F (^C) ^F (^C) ^F (^C) hbgp_dt2 hgbp_dp2 hbgp_db hgb_ton hgb-toff 4 (2.2) 200 (1379) 1 (0.6) 2.0 (1.17) 4.0 (2.2) 5-20 7-10 % MIN stall_a stall_t 10 8 0/1 0-2 DSABLE/ENABLE ibopt ibterm DSABLE 0 0/1 0/1 0-99999 0-99999 DSABLE/ENABLE DSABLE/ENABLE ibrecyc LEAK_EN PPM_20 PPM_LIM DSABLE DSABLE 1000 500 20-85 (138-586) 20-85 (138-586) 0-100 PSI (kPa) PSI (kPa) % HPDP0 HPDP100 HPDPMIN% 25 (172) 50 (241) 0 NOTE: No variables are available for CCN read or write operation. 31 DEFAULT DSABLE DSABLE 100 Table 3 — ICVC Display Data (cont) EXAMPLE 19 — SETUP1 DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press MENU . 2. Press SERVICE . 3. Scroll down to highlight EQUIPMENT SERVICE . 4. Press SELECT . 5. Scroll down to highlight SETUP1 . DESCRIPTION Comp Motor Temp Override Cond Press Override Comp Discharge Alert Rectifier Temp Override Inverter Temp Override STATUS 150-200 (66-93) 145-166 (1000-1145) 125-160 (52-71) 155-170 (68-77) 155-170 (68-77) UNITS ° F (°C) PSI (kPa) ° F (°C) ° F (°C) ° F (°C) POINT MT_OVER CP_OVER CD_ALERT REC_OVER INV_OVER DEFAULT 200 (93) 145 (1000) 140 (60) 160 (71) 160 (71) Chilled Medium Chilled Liquid Deadband Evap Refrig Trippoint Refrig Override Delta T Evap Approach Alert Cond Approach Alert Condenser Freeze Point 0/1 0.5-2.0 (0.3-1.1) 10-40.0 (-12.2-4.4) 2.0-5.0 (1.1-2.8) 0.5-15 (0.3-8.3) 0.5-15 (0.3-8.3) –20 -35 ( -28.9-1.7) WATER/BRINE ^F (^C) ° F (°C) ^F (^C) ^F (^C) ^F (^C) ° F (°C) MEDIUM CLDB ERT_TRIP REF_OVER EVAP_AL CDAP_AL CDFREEZE WATER 1.0 (0.6) 33 (0.6) 3 (1.7) 5 (2.8) 6 (3.3) 34 (1.1) Flow Delta P Display Evap Flow Delta P Cutout Cond Flow Delta P Cutout Oil Press Verify Time Liquid Flow Verify Time 0/1 0.5 - 50.0 (3.45-344.7) 0.5 - 50.0 (3.45-344.7) 15-300 0.5-5 DS/ENABLE PSI (kPa) PSI (kPa) SEC MIN FLOWDISP EVAP_CUT COND_CUT oilpr_t LFLOW_T DSABLE 5.0 (34.5) 5.0 (34.5) 45 5 Recycle Control Restart Delta T Shutdown Delta T 2.0-10.0 (1.1-5.6) 0.5-4.0 (.28-2.2) ^F (^C) ^F (^C) rcycr_dt rcycs_dt 5 (2.8) 1 (0.6) sp1_en sp1_lim sp2_ en sp2_ lim 0 245 (118) 0 245 (118) Spare Alert/Alarm Enable Disable=0, Lo=1/3, Hi=2/4 Spare Temp #1 Enable Spare Temp #1 Limit Spare Temp #2 Enable Spare Temp #2 Limit 0-4 –40-245 (-40-118) 0-4 –40-245 (-40-118) ° F (°C) ° F (°C) NOTE: No variables are available for CCN read or write operation; forcing shall not be supported on service screens. EXAMPLE 20 — SETUP2 DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press MENU . 2. Press SERVICE . 3. Scroll down to highlight EQUIPMENT SERVICE . 4. Press SELECT . 5. Scroll down to highlight SETUP2 . DESCRIPTION Capacity Control Proportional Inc Band Proportional Dec Band Proportional ECL Gain VFD Speed Control VFD Gain VFD Minimum Speed VFD Maximum Speed Vaporizer Heater Mode 0=Normal, 1=Service STATUS UNITS 2-10 2-10 1-3 0.1-1.5 15-50 50-100 0/1 % % POINT DEFAULT vfd_inc vfd_dec vfd_ecl 6.5 6.0 2 vfd_gain vfd_min vfd_max vhtr_mode 0.75 20 100 0 NOTE: No variables are available for CCN read or write operation; forcing shall not be supported on service screens. 32 Table 3 — ICVC Display Data (cont) EXAMPLE 21 — LEAD/LAG DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press MENU . 2. Press SERVICE . 3. Scroll down to highlight EQUIPMENT SERVICE . 4. Press SELECT . 5. Scroll down to highlight LEADLAG . DESCRIPTION Lead Lag Control LEAD/LAG Configuration DSABLE=0, Lead=1 LAG=2, STANDBY=3 Load Balance Option Common Sensor Option LAG % Capacity LAG Address LAG START Timer LAG STOP Timer PRESTART FAULT Timer PULLDOWN Timer STANDBY Chiller Option STANDBY % Capacity STANDBY Address STATUS UNITS POINT 0-3 0/1 0/1 25-75 1-236 2-60 2-60 2-30 1-30 0/1 25-75 1-236 DSABLE/ENABLE DSABLE/ENABLE % MIN MIN MIN MIN DSABLE/ENABLE % DEFAULT leadlag 0 loadbal commsens lag_per lag_add lagstart lagstop preflt pulldown stnd_opt stnd_per stnd_add DSABLE DSABLE 50 92 10 10 5 2 DSABLE 50 93 NOTE: No variables are available for CCN read or write operation. EXAMPLE 22 — RAMP_DEM DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press MENU . 2. Press SERVICE . 3. Scroll down to highlight EQUIPMENT SERVICE . 4. Press SELECT . 5. Scroll down to highlight RAMP_DEM . DESCRIPTION Pulldown Ramp Type: Select: Temp=0, KW=1 Demand Limit and kW Ramp Demand Limit Source Select: Amps=0, kW=1 Amps or kW Ramp %/Min Demand Limit Prop Band Demand Limit At 20 mA 20 mA Demand Limit Opt Demand Watts Interval STATUS 0/1 UNITS 0/1 5-20 3-15 40-100 0/1 5-60 % % DSABLE/ENABLE MIN POINT ramp_opt DEFAULT 1 dem_src 0 kw_ramp dem_app dem_20ma dem_sel dw_int 10 10 40 DSABLE 15 NOTE: No variables are available for CCN read or write operation. EXAMPLE 23 — TEMP_CTL DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press MENU . 2. Press SERVICE . 3. Scroll down to highlight EQUIPMENT SERVICE . 4. Press SELECT . 5. Scroll down to highlight TEMP_CTL . DESCRIPTION Control Point Source ECL Control Option Temp Pulldown Ramp/Min Temperature Reset RESET TYPE 1 Degrees Reset At 20 mA RESET TYPE 2 Remote Temp –> No Reset Remote Temp –> Full Reset Degrees Reset RESET TYPE 3 CHL Delta T –> No Reset CHL Delta T –> Full Reset Degrees Reset Enable Reset Type STATUS UNITS POINT DEFAULT 0/1 2-10 (1.1-5.6) DSABLE/ENABLE ^F (^C) ecl_opt tmp_ramp DSABLE 3 (1.7) –30- 30 (-17-17) ^F (^C) deg_20ma 10 (6) –40-245 (-40-118) –40-245 (-40-118) –30-30 (-17-17) ° F (°C) ° F (°C) ^F (^C) res_rt1 res_rt2 deg_rt 85 (29) 65 (18) 10 (6) 0-15 (0-8) 0-15 (0-8) –30-30 (-17-17) ^F (^C) ^F (^C) ^F (^C) restd_1 restd_2 deg_res 10 (6) 0 (0) 5 (3) res_sel 0 0-3 33 PIC III System Functions Table 4 — Capacity Control Conditions NOTE: Words not part of paragraph headings and printed in all capital letters can be viewed on the ICVC (e.g., LOCAL, CCN, RUNNING, ALARM, etc.) Words printed in both all capital letters and italics can also be viewed on the ICVC and are parameters (CONTROL MODE ADDED EXAMPLES, etc.) with associated values (e.g., modes, temperatures, pressures, percentages, on, off, enable, disable, etc.).Words printed in all capital letters and in a box represent softkeys on the ICVC (e.g., ENTER and EXIT ). See Table 3 for examples of the type of information that can appear on the ICVC screens. Figures 15-21 give an overview of ICVC operations and menus. The sequence of screens that should be selected to view any parameter in the ICVC can be found in Appendix A. Capacity DELTA TARGET VFD Forced Increase X Decrease X VFD Speed = Min. VFD Speed = Max Increase X Increase Decrease Decrease • X VFD SPEED CHANGE TARGET VFD = Forced Value TARGET VFD = Forced Value TARGET VFD = TARGET VFD + (VFD Delta * VFD Gain) No Change No Change TARGET VFD = TARGET VFD + (VFD Delta * VFD Gain) VFD DELTA less than 0.2% will not cause the VFD SPEED OUTPUT to increase or decrease. • If the Capacity Decrease is in effect due to an override then the VFD SPEED OUTPUT decreases at a rate of 2.0% per 5 seconds until the decrease condition is satisfied. This will occur regardless of VFD DELTA value. • A VFD SPEED OUT OF RANGE fault will be declared if the ACTUAL VFD SPEED exceeds the VFD SPEED OUTPUT ±10% for 75 seconds when the chiller is running. • A COMP MIN SPEED LIMITED RUN CAPACITY OVERRIDE alert will be declared when the TARGET VFD SPEED is being limited by the COMPRESSOR MINIMUM SPEED. ECL CONTROL OPTION — If this option is enabled, the PIC III modulates the compressor speed in response to the entering chilled liquid temperature instead of the LEAVING CHILLED LIQUID temperature. The ECL CONTROL OPTION may be viewed on the TEMP_CTL screen, which is accessed from the EQUIPMENT SERVICE screen. CHILLED LIQUID DEADBAND — This is the tolerance range on the chilled liquid/brine temperature control point. If the liquid temperature goes outside the CHILLED LIQUID DEADBAND, the PIC III increases or decreases compressor speed until the temperature is within tolerance. The PIC III may be configured with a 0.5 to 2 F (0.3 to 1.1 C) deadband. CHILLED LIQUID DEADBAND may be viewed or modified on the SETUP1 screen, which is accessed from the EQUIPMENT SERVICE table. Example: A 1º F (0.6º C) CHILLED LIQUID DEADBAND setting controls the liquid temperature within ±0.5º F (0.3º C) of the CONTROL POINT. This may cause frequent changes in compressor speed if the cooling load fluctuates frequently. A value of 1º F (0.6º C) is the default setting. PROPORTIONAL BANDS AND PROPORTIONAL GAIN — The PIC III uses the PROPORTIONAL INC (Increase) BAND, PROPORTIONAL DEC (Decrease) BAND, and the PROPORTIONAL ECL (Entering Chilled Liquid) GAIN to determine how fast or slow to respond. Proportional band is the rate at which the compressor speed is changed in proportion to how far the chilled liquid/brine temperature is from the CONTROL POINT. Proportional gain determines how quickly the VFD reacts to how quickly the temperature is deviating from the CONTROL POINT. The proportional bands and proportional gain may be viewed or modified from the SETUP2 screen, which is accessed from the EQUIPMENT SERVICE table. The Proportional Band — The PIC III controls can be configured to respond differently to temperature deviations above the control point and to temperature deviations below the control point. CAPACITY CONTROL — The PIC III controls the chiller capacity by changing the compressor speed in response to chilled liquid temperature deviation away from the CONTROL POINT. The CONTROL POINT may be changed by a CCN network device or is calculated by the PIC III adding any active chilled liquid reset to the ECL or LCL SET POINT. The CONTROL POINT may be viewed or overridden from the MAINSTAT screen. See page 23. Changes to the chiller capacity and system overrides are achieved through the VFD SPEED OUTPUT. The VFD SPEED OUTPUT is controlled by varying the output from 0 to 100%. The TARGET VFD SPEED is forcible and allows the operator manual control of the VFD SPEED OUTPUT. The TARGET VFD SPEED will be allowed to change every five seconds unless TARGET VFD SPEED is forced. The TARGET VFD SPEED is controlled between the VFD MINIMUM SPEED and VFD MAXIMUM SPEED (refer to SETUP2 screen) based on the Capacity Control algorithm. The PIC III controls monitor the compressor oil properties and set a COMPRESSOR MINIMUM SPEED to ensure sufficient compressor bearing lubrication under all operating conditions. The TARGET VFD SPEED shall not be allowed to be forced below the COMP MINIMUM SPEED. A summary of all capacity control conditions and responses is shown in Table 4. Changes to the VFD SPEED are implemented by the following methods: FORCED — The TARGET VFD SPEED can be forced from the ICVC. The TARGET VFD SPEED is set to the forced value and remains there until the force is removed or the chiller is shut down. The forced value is limited between the VFD MINIMUM SPEED and VFD MAXIMUM SPEED. NORMAL CONDITIONS — VFD speed changes are based on the calculated change in VFD DELTA multiplied by the VFD GAIN. VFD DELTA is displayed in the COMPRESS screen. The VFD GAIN increases or decreases the commanded VFD speed change with respect to the VFD DELTA calculated by the ICVC. CAPACITY INCREASE — If the TARGET VFD SPEED is less than the VFD MAXIMUM SPEED, the TARGET VFD SPEED is increased by the VFD DELTA times the VFD GAIN. CAPACITY DECREASE — If the TARGET VFD SPEED is greater than the VFD MINIMUM SPEED, the TARGET VFD SPEED is decreased by the VFD DELTA times the VFD GAIN. 34 to START. For more information on forced starts, see Local Start-Up, page 46. The schedules also can be overridden to keep the chiller in an occupied state for up to 4 hours, on a one time basis. See the Time Schedule Operation section, page 21. Figure 20 shows a schedule for a typical office building with a 3-hour, off-peak, cool-down period from midnight to 3 a.m., following a weekend shutdown. Holiday periods are in an unoccupied state 24 hours per day. The building operates Monday through Friday, 7:00 a.m. to 6:00 p.m., and Saturdays from 6:00 a.m. to 1:00 p.m. This schedule also includes the Monday midnight to 3:00 a.m. weekend cool-down schedule. NOTE: This schedule is for illustration only and is not intended to be a recommended schedule for chiller operation. Whenever the chiller is in the LOCAL mode, it uses Occupancy Schedule 01 (OCCPC01S). The chiller uses Occupancy Schedule 02 (OCCPCO2S) when it is in ICE BUILD mode. When the chiller is in CCN mode, it uses Occupancy Schedule 03 (OCCPC03S). The CCN SCHEDULE NUMBER is configured on the NET_OPT display screen, accessed from the EQUIPMENT CONFIGURATION table. See Table 3, Example 16. SCHEDULE NUMBER can be changed to any value from 03 to 99. If this number is changed on the NET_OPT screen, the operator must go to the ATTACH TO NETWORK DEVICE screen to upload the new number into the SCHEDULE screen. See Fig. 19. The PIC III controls response to temperatures above the control point is affected by the PROPORTIONAL INC BAND. This parameter will slow or quicken the rate at which the compressor speed is changed in response to chilled liquid/brine temperatures above the control point plus 1/2 times the CHILLED LIQUID DEADBAND. The PROPORTIONAL INC BAND can be adjusted from a setting of 2 to 10; the default setting is 6.5. A smaller value of PROPORTIONAL INC BAND will increase the rate at which the compressor speed is increased. The response below the control point is called the PROPORTIONAL DEC BAND, this parameter will slow or quicken the rate at which the compressor speed is changed in response to chilled liquid temperatures below the CONTROL POINT minus 1/2 times the CHILLED LIQUID DEAD BAND. The PROPORTIONAL DEC BAND can be adjusted on the ICVC from a setting of 2 to 10. The default setting is 6.0. A smaller value of PROPORTIONAL DEC BAND will increase the rate at which the compressor speed is decreased. The PROPORTIONAL ECL GAIN changes the amount the compressor speed is changed each time the PIC III controls command an adjustment. The PROPORTIONAL ECL GAIN can be adjusted from 1 to 3. A larger value of PROPORTIONAL ECL GAIN will increase the amount the compressor speed changes each time the controls call for a change. DEMAND LIMITING — The PIC III responds to the ACTIVE DEMAND LIMIT set point by limiting the amps or kilowatts consumed by the chiller. It compares the ACTIVE DEMAND LIMIT set point to the DEMAND LIMIT SOURCE (either the actual AVERAGE LINE CURRENT or the actual MOTOR KW), depending on how the control is configured. DEMAND LIMIT SOURCE is on the RAMP_DEM screen. The default DEMAND LIMIT SOURCE is the compressor motor amps. CHILLER TIMERS — The PIC III maintains 2 runtime clocks, known as COMPRESSOR ONTIME and SERVICE ONTIME. COMPRESSOR ONTIME indicates the total life-time compressor run hours. This timer can register up to 500,000 hours before the clock turns back to zero. The SERVICE ONTIME is a resettable timer that can be used to indicate the hours since the last service visit or any other event. The time can be changed from the ICVC to whatever value is desired. The SERVICE ONTIME timer can register up to 32,767 hours before it rolls over to zero. The chiller also maintains a start-to-start timer and a stopto-start timer. These timers limit how soon the chiller can be started. START INHIBIT TIMER is displayed on the MAINSTAT screen. See the Start-Up/Shutdown/Recycle Sequence section, page 46, for more information on this topic. OCCUPANCY SCHEDULE — The chiller schedule, described in the Time Schedule Operation section (page 21), determines when the chiller can run. Each schedule consists of from 1 to 8 occupied or unoccupied time periods, set by the operator. The chiller can be started and run during an occupied time period (when YES is displayed next to OCCUPIED? on the MAINSTAT display screen). It cannot be started or run during an unoccupied time period (when NO is displayed next to OCCUPIED ? on the MAINSTAT display screen). These time periods can be set for each day of the week and for holidays. The day begins with 0000 hours and ends with 2400 hours. When any occupancy schedule is in a time period when the chiller is allowed to run, the parameter OCCUPIED? is YES. These schedules can be set up to follow a building’s occupancy schedule, or can be set to be occupied 100% of the time, if the operator wishes. In this case, the chiller is normally started and stopped manually using the CCN, LOCAL, and STOP buttons. The schedules also can be bypassed by forcing the CHILLER START/STOP parameter on the MAINSTAT screen Safety Controls — The PIC III monitors all safety control inputs and, if required, shuts down the chiller or limits the compressor speed to protect the chiller from possible damage from any of the following conditions: • high motor winding temperature • high discharge temperature • low oil pressure • low evaporator refrigerant temperature • condenser high pressure or low pressure • inadequate liquid/brine cooler and condenser flow • high, low, or loss of voltage • ground fault • voltage imbalance • current imbalance • excessive motor acceleration time • lack of motor current signal • excessive motor amps • motor stall • temperature sensor and transducer faults • VFD power faults • VFD over temperature • humidity surrounding the VFD coldplate • reverse compressor rotation VFD faults or protective devices within the VFD can shut down the chiller. If compressor motor overload or a motor ground fault occurs, check the motor for grounded or open phases before attempting a restart. If the PIC III control initiates a safety shutdown, it displays the reason for the shutdown (the fault code) on the ICVC display screen along with a primary and secondary message, and blinks the alarm light on the control center. The alarm is stored in memory and can be viewed on the ALARM HISTORY and VFD_HIST screens on the ICVC, along with a message for troubleshooting. If the safety shutdown was also initiated by a fault detected in the VFD, the conditions at the time of the fault will be stored in VFD_HIST. 35 2. Motor load ramp loading (AMPS OR KW RAMP %/ MIN) limits the percent per minute rate at which the compressor motor current or compressor motor load increases. The AMPS OR KW RAMP %/MIN rate is configured by the operator on the RAMP_DEM screen in amps or kilowatts. If kilowatts is selected for the DEMAND LIMIT SOURCE, the MOTOR RATED LOAD KILOWATTS must be entered (information found on the machine Electrical Data Nameplate) in the VFD_CONF screen. The TEMP PULLDOWN DEG/MIN may be viewed or modified on the TEMP_CTL screen which is accessed from the EQUIPMENT SERVICE screen. PULLDOWN RAMP TYPE, DEMAND LIMIT SOURCE, and MOTOR KW RAMP %/MIN may be viewed or modified on the RAMP_DEM screen. Capacity Override (Table 6) — Adjustable capacity overrides are available to prevent the chiller from exceeding some limits and going into an alarm state. Alert messages 120 through 127 are displayed on the ICVC when capacity overrides are in effect. Capacity overrides can prevent some safety shutdowns caused by exceeding the refrigerant low temperature safety limit, motor high temperature safety limit, and condenser high pressure limit, high VFD inverter rectifier temperature limit, and high VFD inverter temperature limit. To give more precise information or warnings on the chiller’s operating condition, the operator can define alert limits on various monitored inputs in the SETUP1 screen. Safety contact and alert limits are defined in Table 5. Alarm and alert messages are listed in the Troubleshooting Guide section, page 81. Shunt Trip — The function of the shunt trip on the PIC III is to act as a safety trip. The shunt trip is wired from the standard I/O board to a shunt trip equipped VFD circuit breaker. If the PIC III tries to shut down the compressor using a normal shutdown procedure but is unsuccessful for 20 seconds, the shunt trip output is energized and causes the circuit breaker to trip off. The ground fault trip also will energize the shunt trip to trip the circuit breaker. Protective devices in the VFD can also energize the shunt trip. The shunt trip feature can be tested using the Control Test feature in the DISCRETE OUTPUTS CONTROL TEST screen. Reset the circuit breaker immediately after performing this test. Default Screen Freeze — When the chiller is in an alarm state, the default ICVC display “freezes,” that is, it stops updating. The first line of the ICVC default screen displays a primary alarm message; the second line displays a secondary alarm message. The ICVC default screen freezes to enable the operator to see the conditions of the chiller at the time of the alarm. If the value in alarm is one normally displayed on the default screen, the value flashes between normal and reverse contrast. The ICVC default screen remains frozen until the condition that caused the alarm is remedied by the operator. Knowledge of the operating state of the chiller at the time an alarm occurs is useful when troubleshooting. Additional chiller information can be viewed on the status screens and the VFD_HIST screen. Troubleshooting information is recorded in the ALARM HISTORY table, which can be accessed from the SERVICE menu. To determine what caused the alarm, the operator should read both the primary and secondary default screen messages, as well as the alarm history. The primary message indicates the most recent alarm condition. The secondary message gives more detail on the alarm condition. Since there may be more than one alarm condition, another alarm message may appear after the first condition is cleared. Check the ALARM HISTORY screen for additional help in determining the reasons for the alarms. Once all existing alarms are cleared (by pressing the RESET softkey), the default ICVC display returns to normal operation. Ramp Loading — The ramp loading feature controls the rate at which the compressor loads up. This control can prevent the compressor from loading up too fast during the short period of time when the chiller is started and the chilled liquid loop has to be brought down to the CONTROL POINT. This helps reduce electrical demand charges by slowly bringing the chilled liquid to the CONTROL POINT. There are two methods of ramp loading with the PIC III. Ramp loading can be based on chilled liquid temperature or on motor load. The method of ramp loading is selected from the RAMP__DEM screen. 1. Temperature ramp loading (TEMP PULLDOWN DEG/ MIN) limits the degrees per minute rate at which either the leaving chilled liquid or the entering chilled liquid temperature decreases. This rate is configured by the operator on the TEMP_CTL screen. The lowest temperature ramp rate will be used if chiller power has been off for 3 hours or more (even if the motor kilowatts ramp loading is selected as the ramp loading method). Compressor Minimum Speed Override — This capacity override increases compressor speed if oil viscosity falls below acceptable levels or if conditions exist that will prevent sufficient refrigerant cooling to the VFD or motor. This override is not configurable, it is the only override that will increase chiller capacity to avoid a safety shutdown. Compressor minimum speed override is most likely to happen at evaporator temperatures of 50 degrees or more, combined with low speed, low lift, and less than 25% tons. The PIC III controls regulate the minimum allowable compressor speed based on oil sump temperature and pressure and on compressor head. The compressor bearings require higher oil viscosity when operating at low speed than they do when operating at high speeds. The controls increase compressor speed when the oil viscosity is too low to operate the compressor at the lower speed. The low compressor speed override is also enabled at low loads with high condensing pressure. Vaporizer Temperature Control COMPRESSOR ON — The vaporizer temperature control is regulated by the PIC III using the vaporizer heater relay and a flexible surface heater that is attached to the bottom of the vaporizer. The vaporizer heater relay is energized whenever the compressor is at low loads and requires additional heat to maintain a sufficient vaporizer temperature. The vaporizer heater is turned off when the additional heat is no longer required. The vaporizer heater is not energized when the chiller is not running. Oil Sump Temperature Control COMPRESSOR OFF — The OIL SUMP TEMP is regulated by the PIC III using the oil heater relay and an immersion heater in the oil sump. The oil heater relay is energized whenever the chiller compressor is off, and the OIL SUMP TEMP is less than 140 F (60 C) or whenever the OIL SUMP TEMP is less than the CALC EVAP SAT TEMP plus 53 F (29.4 C). The oil heater is then turned off when the OIL SUMP TEMP is: 1. More than 152 F (66.7 C) or 2. The OIL SUMP TEMP is more than 142 F (61.1 C) and also warmer than the CALC EVAP SAT TEMP plus 55 F (30.6 C). 36 Table 5 — Protective Safety Limits and Control Settings ALARM OR ALERT STATE 260-271, 140,141 -40 deg F>Temperature>245 deg F for 3 seconds Pressure Transducers Out of Range High Compressor Discharge Temperature 262-272 231 162 103 0.06>Voltage Ratio>0.98 for 3 seconds COMP DISCHARGE TEMP > 180 deg F(82 deg C) COMP DISCHARGE TEMP > COMP DISCHARGE ALERT COMP DISCHARGE TEMP > COMP DISCHARGE ALERT - 10 deg F(5.6 deg C) High Motor Temperature 233 COMP MOTOR WINDING TEMP > 244 deg F(118 deg C) or < -5 deg F(-21 deg C) — Open Circuit COMP MOTOR WINDING TEMP > COMP MOTOR TEMP OVERRIDE - 10 deg F(5.6 deg C) MONITORED PARAMETER Temperature Sensors Out of Range 102 Low Evaporator Temperature (Freeze Protection) 243 232 104 LIMIT Chiller in RECYCLE SHUTDOWN and CALC EVAP SAT TEMP or EVAP REFRIG LIQUID TEMP < EVAP REFRIG TRIPPOINT + 1 deg F For water: EVAP REFRIG LIQUID TEMP or CALC EVAP SAT TEMP TEMP < 33 deg F and EVAPORATOR APPROACH < EVAP APPROACH ALERT For brine: EVAP REFRIG LIQUID TEMP or CALC EVAP SAT TEMP is between 0 deg F(-17.8C) and 40 deg F(4.4C)(brine) and EVAPORATOR APPROACH < EVAP APPROACH ALERT CALC EVAP SAT TEMP < 33 deg F + REFRIG OVERRIDE DELTA T (non-brine) CALC EVAP SAT TEMP < EVAP REFRIG TRIPPOINT (brine) + REFRIG OVERRIDE DELTA T Transducer Voltage Fault High Condenser Pressure - Control - Switch - Prestart Low Condenser Pressure (Freeze Protection) 239 TRANSDUCER VOLTAGE REF<4.5 VDC 235 207 106 CONDENSER PRESSURE > 166 PSI High Pressure Switch Open(165 +/-5 PSIG) & VFD START = YES CONDENSER PRESSURE > COND PRESS OVERRIDE - 25 PSI 244 Chiller in PUMPDOWN mode and CONDENSER REFRIG TEMP < CONDENSER FREEZE POINT Energizes condenser pump relay if CONDENSER REFRIG TEMP < CONDENSER FREEZE POINT. De-energizes condenser pump relay when CONDENSER REFRIG TEMP > CONDENSER FREEZE POINT + 5 deg F (2.8 deg C) and ENTERING COND LIQUID > CONDENSER FREEZE POINT 154 Oil - Low Pressure - Low Pressure - Low Pressure - High Oil Pressure - Pressure Sensor Fault - Low Temperature 234 228 142 164 227 105 COMMENTS Preset Alarm. See Temperature vs. Resistance/Voltage Drop in Table 13A and 13B Preset Alarm Voltage Ratio=Input Voltage/Voltage Reference(5 Volts) Preset Alarm, Configure DISCH TEMP ALERT in SETUP1 screen Configure COMP DISCH ALERT in SETUP1 screen Prestart Alert, Configure COMP DISCHARGE ALERT in SETUP1 screen Preset Alarm Prestart Alert, Configure COMP MOTOR TEMP OVERRIDE in SETUP1 screen Preset Alarm, Configure EVAP REFRIG TRIPPOINT in SETUP1 screen Preset Alarm, Configure EVAP APPROACH ALERT in SETUP1 screen Configure EVAP APPROACH ALERT and CHILLED MEDIUM in SETUP1 screen Prestart Alert, Configure REFRIG OVERRIDE DELTA T in SETUP1 screen Prestart Alert, Configure EVAP REFRIG TRIP POINT and CHILLED MEDIUM in SETUP1 screen Preset Alarm Preset Alarm Preset Alarm, Switch closes at 110 +/-7 PSIG Prestart Alert, Configure COND PRESS OVERRIDE in SETUP1 screen Preset Alarm, Configure CONDENSER FREEZE POINT in SETUP1 screen. Configure CONDENSER FREEZE POINT in SETUP1 screen OIL PRESSURE DELTA P < 18 PSID after OIL PUMP = ON, OIL PRESS VERIFY TIME exceeded, and STARTUP in progress OIL PRESSURE DELTA P < 15 PSID and VFD START = TRUE OIL PRESSURE DELTA P < 15 PSID and VFDSTART = TRUE Oil Pump ON and OIL PRESSURE DELTA P > 45 PSI OIL PRESSURE DELTA P > 4 PSI immediately before oil pump turned on OIL SUMP TEMP < 140 deg F and OIL SUMP TEMP < CALC EVAP SAT TEMP + 15 deg F (8.3 deg C) Preset Alarm, Configure OIL PRESS VERIFY TIME in SETUP1 screen Preset Alarm, condition must persist for 55 consecutive seconds Preset Alert, condition must persist for 10 consecutive seconds Preset Alert, condition must persist for 55 consecutive seconds Preset Alarm Preset Prestart Alert Line Voltage - High - High - Low - Low - Imbalance 211/145 108 212/146 107 216 Line voltage > limits are calculated by VFD (alert is declared if AUTORESTART is ENABLED) PERCENT LINE VOLTAGE > 115% Line voltage < limits calculated by VFD (alert is declared if AUTORESTART is ENABLED) PERCENT LINE VOLTAGE < 85% LINE VOLTAGE IMBALANCE > LINE VOLTAGE % IMBALANCE Preset Alarm/Autorestart Alert Preset Prestart Alert Preset Alarm/Autorestart Alert Preset Prestart Alert Configure LINE VOLTAGE % IMBALANCE and LINE VOLT IMBALANCE TIME in VFD_CONF screen Line Current - Dropout - Imbalance 210/144 209/143 Line Voltage on 2 Phases < 50% for 1 Cycle LINE CURRENT IMBALANCE>LINE CURRENT % IMBALANCE Preset Alarm/Autorestart Alert Configure LINE CURRENT % IMBALANCE and LINE CURRENT IMBALANCE TIME in VFD_CONF screen Power - Line Frequency Trip - Power Loss - Phase Reversal Motor - Stall 222 214/148 226 47 Hz < LINE FREQUENCY < 63 Hz DC BUS VOLTAGE<85% for Excessive Time Period Line power phases out of sequence Preset Alarm Preset Alarm/Autorestart Alert Preset Alarm 238 > 5 stall events within STALL TIME PERIOD - Current Imbalance 225 MOTOR CURRENT IMBALANCE>MOTOR CURRENT % IMBALANCE - Rotation Reversed - Overload Trip 221 217 DISCHARGE PRESSURE decreases more than 2 PSI after VFDSTART = TRUE Any LOAD CURRENT PHASE > 108% for Excessive Time Period - Excessive Amps - Acceleration Fault 208 203 PERCENT LOAD CURRENT > 110% for 30 sec. PERCENT LOAD CURRENT > 95% at startup and VFDSTART = TRUE for 5 to 40 sec - Amps not Sensed 202 PERCENT LOAD CURRENT < 5% and VFD START=TRUE for 20 sec - Starts Limit Exceeded Low Chilled Liquid Flow 100 229 Low Cond Liquid Flow 230 Preset Alarm, Configure STALL DELTA% AMPS and STALL TIME PERIOD in OPTIONS screen Configure MOTOR CURRENT % IMBALANCE and MOTOR CURRENT IMBAL TIME in VFD_CONF screen Preset Alarm, Must be outside -2 PSI limit for 5 consecutive samples Preset Alarm, Configure MOTOR LOAD ACTIVE DEMAND LIMIT in MAINSTAT screen Preset Alarm Preset Alarm, PERCENT LOAD CURRENT = AVERAGE LOAD CURRENT/MOTOR RATED LOAD AMPS Preset Alarm, PERCENT LOAD CURRENT = AVERAGE LOAD CURRENT/MOTOR RATED LOAD AMPS Preset Prestart Alert Configurable Alarm, Configure LIQUID FLOW VERIFY TIME in SETUP1 screen. EVAPORATOR APPROACH = LEAVING CHILLED LIQUID TEMP EVAP REFRIG LIQUID TEMP Configurable Alarm, Configure LIQUID FLOW VERIFY TIME in SETUP1 screen. CONDENSER APPROACH = CONDENSER REFRIG TEMP LEAVING COND LIQUID TEMP Configure EVAP APPROACH ALERT in SETUP1 screen EVAPORATOR APPROACH = LEAVING CHILLED LIQUID TEMP EVAP REFRIG LIQUID TEMP Configure COND APPROACH ALERT in SETUP1 screen. High Approach-Evaporator 160 More than 8 starts in 12 hours CHILLED LIQUID FLOW = FALSE after CHILLED LIQUID PUMP = ON & LIQUID FLOW VERIFY TIME elapsed. CHILLED LIQUID DELTA P < EVAP FLOW DELTA P CUTOUT or CALC EVAP SAT TEMP < EVAP REFRIG TRIPPOINT or EVAPORATOR APPROACH > EVAP APPROACH ALERT and EVAP REFRIG LIQUID TEMP < EVAP REFRIG TRIPPOINT +1 COND LIQUID FLOW = FALSE after COND LIQUID PUMP = ON & LIQUID FLOW VERIFY TIME elapsed. CONDENSER LIQUID DELTA P < COND FLOW DELTA P CUTOUT or CONDENSER APPROACH > CONDENSER APPROACH ALERT, or CONDENSER PRESSURE > COND PRESS OVERRIDE + 5 EVAPORATOR APPROACH > EVAP APPROACH ALERT and VFD START = TRUE - Condenser 161 CONDENSER APPROACH > COND APPROACH ALERT and VFD START = TRUE 245 204 ACTUAL VFD SPEED < VFD SPEED OUTPUT - 10% or ACTUAL VFD SPEED > VFD SPEED OUTPUT + 10% PERCENT LOAD CURRENT >15% and VFDSTART = NO for 20 sec VFD - Speed Out of Range - Failure to Stop - Communication Failure Rectifier - Overcurrent - High Temperature Inverter - Overcurrent - High Temperature High VFD Inductor Temperature DC Bus Voltage - High - Low Ground Fault Optional Limits - Spare Temperature Preset Alarm, Must be outside +/-10% range for 75 sec. Preset Alarm, PERCENT LOAD CURRENT = AVERAGE LOAD CURRENT/MOTOR RATED LOAD AMPS Preset Alarm 224 Communication with VFD lost for more than 10 sec 241 218 101 RECTIFIER OVERCURRENT exceeded limit determined by VFD RECTIFIER TEMPERATURE >exceeds limit calculated by VFD RECTIFIER TEMPERATURE > RECTIFIER TEMP OVERRIDE - 20 deg F(11.1 deg C) Preset Alarm Preset Alarm Prestart Alert, Configure RECTIFIER TEMP OVERRIDE in SETUP1 screen 246 219 109 INVERTER OVERCURRENT exceeded limit determined by VFD INVERTER TEMPERATURE >exceeds limit calculated by VFD INVERTER TEMPERATURE > INVERTER TEMP OVERRIDE - 20 deg F(11.1 deg C) 255 Inductor Temperature Switch Open Preset Alarm Preset Alarm Prestart Alert, Configure INVERTER TEMP OVERRIDE in SETUP1 screen Preset Alarm 205/150 215/149 220 DC BUS VOLTAGE Limit Exceeded, limit is calculated by VFD DC BUS VOLTAGE < approximately 407VDC @400/480V Line Side Voltage GROUND FAULT CURRENT > 7% of Drive Rated Amps Sensed Preset Alarm/Autorestart Alert Preset Alarm/Autorestart Alert Preset Alarm Optional Alarm, Configure SPARE TEMP ENABLE and SPARE TEMP LIMIT in SETUP1 screen Optional Alert, Configure SPARE TEMP ENABLE and SPARE TEMP LIMIT in SETUP1 screen Optional Alarm, configure PPM AT 20 MA and REFRIGERANT LEAK ALARM PPM in OPTIONS screen. 248,249 SPARE TEMPERATURE > SPARE TEMP LIMIT for 3 consecutive samples - Spare Temperature 158,159 SPARE TEMPERATURE > SPARE TEMP LIMIT for 3 consecutive samples - Refrigerant Leak Sensor 250 REFRIGERANT LEAK SENSOR PPM > REFRIG LEAK ALARM PPM 37 followed by the LOCAL or CCN softkey. This ensures that, if the automatic system is malfunctioning, the chiller will not repeatedly cycle on and off. If the AUTORESTART OPTION and the REMOTE CONTACT OPTION in the OPTIONS screen are enabled, the REMOTE CONTACTS must be closed in order for the chiller to restart following a power failure. If the automatic restart after a power failure option (AUTO RESTART OPTION on the OPTIONS screen) is not enabled when a power failure occurs, and if the remote contact is closed, the chiller will indicate an alarm because of the loss of voltage. Oil Sump Temperature Control COMPRESSOR ON — The oil heater relay is energized whenever the chiller compressor is on, and the OIL SUMP TEMP is less than 90 F (32.2 C) or OIL SUMP TEMP is less than the CALC EVAP SAT TEMP plus 35 F (19.4 C). The oil heater is then turned off when the OIL SUMP TEMP is: 1. More than 90 F (32.2 C). 2. The OIL SUMP TEMP is warmer than the CALC EVAP SAT TEMP plus 35 F (19.4 C). All oil filter isolation valves should always be left open, except when changing the oil or the oil filter as defined in Changing Oil and Oil Filter section, page 73. The contacts for remote start are wired into terminals 23 and 24 of the low voltage terminal strip in the control center cabinet. See the certified drawings for further details on contact ratings. The contacts must have 24 vac rating. Remote Start/Stop Contacts — A remote device, Spare Safety and Spare Temperature Inputs — Normally closed (NC) discrete inputs for additional fieldsupplied safeties may be wired to the spare protective limits input channel in place of the factory-installed jumper. (Wire multiple inputs in series.) The opening of any contact will result in a safety shutdown and a display on the ICVC. Refer to the certified drawings for safety contact ratings. Analog temperature sensors may also be added to the module (SPARE TEMPERATURE #1 and #2). The analog temperature sensors may be configured to cause an alert or alarm on the CCN network. The alert will not shut the chiller down. Configuring for alarm state will cause the chiller to shut down. The SPARE TEMP channels can be configured for low or high temperature limits in the SETUP1 screen. such as a timeclock that uses a set of contacts, may be used to start and stop the chiller. However, the device should not be programmed to start and stop the chiller in excess of 2 or 3 times every 12 hours. If more than 8 starts in 12 hours (the STARTS IN 12 HOURS parameter on the MAINSTAT screen) occur, an excessive starts prestart alert displays, preventing the chiller from starting. The operator must press the RESET softkey on the ICVC to override the starts counter and start the chiller. If the chiller records 12 starts (excluding recycle starts or auto restarts after power failure) in a sliding 12-hour period, it can be restarted only by pressing the RESET softkey Table 6 — Capacity Overrides OVERRIDE CAPACITY CONTROL High Condenser Pressure (COND PRESS OVERRIDE) FIRST STAGE SET POINT View/Modify on ICVC Screen SETUP1 Default Value Configurable Range SECOND STAGE SET POINT SECOND STAGE OVERRIDE TERMINATION Value Value CONDENSER PRESSURE > COND PRESS OVERRIDE 145 PSIG 145 to 166 PSIG + 2.4 PSIG(16.5 kPa) OR (1000 kPa) (1000 to 1145 kPa) CONDENSER PRESSURE > 163 PSIG (1124 kPa) CONDENSER PRESSURE < CONDENSER PRESS OVERRIDE - 1 PSI (6.9 kPa) SETUP1 3° F (1.7° C) 2 to 5° F (1.1 to 2.8° C) CALC EVAP SAT TEMP, or EVAP REFRIG LIQUID TEMP < EVAP SAT OVERRIDE TEMP - 1° F (.6° C) NOTE: EVAP SAT OVERRIDE TEMP = EVAP REFRIG TRIPPOINT + REFRIG OVERRIDE DELTA T High Motor Temperature SETUP1 (COMP MOTOR TEMP OVERRIDE) 200° F (93° C) 150 to 200° F (66 to 93° C) COMP MOTOR WINDING TEMP > COMP MOTOR TEMP OVERRIDE + 10° F (5.6° C) COMP MOTOR WINDING TEMP < COMP MOTOR TEMP OVERRIDE - 2° F (1.1° C) Low Evaporator Temperature (REFRIG OVERRIDE DELTA T) CALC EVAP SAT TEMP and EVAP REFRIG LIQUID TEMP > EVAP SAT OVERRIDE TEMP + 2° F (1.1° C) High Rectifier Temperature (RECTIFIER TEMP OVERRIDE) SETUP1 160° F (71° C) 155 to 170° F (68 to 77° C) RECTIFIER TEMP > RECTIFIER TEMP OVERRIDE + 10° F (5.6° C) RECTIFIER TEMP < RECTIFIER TEMP OVERRIDE - 5° F (2.8° C) High Inverter Temperature (INVERTER TEMP OVERRIDE) SETUP1 160° F (71° C) 155 to 170° F (68 to 77° C) INVERTER TEMP > INVERTER TEMP OVERRIDE + 10° F (5.6° C) INVERTER TEMP < INVERTER TEMP OVERRIDE - 5° F (2.8° C) 38 Spare Alarm Contacts — One normally open trip alarm contact is provided in the control center cabinet. The contact ratings are provided in the certified drawings. The contacts are located on terminals 9 and 10 of the hazardous voltage terminal strip in the control center cabinet. If the CONDENSER PRESSURE is greater than or equal to the COND PRESS OVERRIDE, the condenser pump will energize to try to decrease the pressure and Alert 151 will be generated. The pump will turn off when the condenser pressure is less than the COND PRESS OVERRIDE threshold. Refrigerant Leak Detector — A 4 to 20 mA / 0 to Condenser Freeze Prevention — This control algo- rithm helps prevent condenser tube freeze-up by energizing the condenser pump relay through terminals 3 and 4 of the hazardous voltage terminal strip (TB2) in the Control Center. The PIC III controls the pump and, by starting it, helps to prevent the liquid in the condenser from freezing. The PIC III can perform this function whenever the chiller is not running except when it is either actively in pumpdown or in pumpdown/ lockout with the freeze prevention disabled. When the CONDENSER REFRIG TEMP is less than or equal to the CONDENSER FREEZE POINT, the CONDENSER LIQUID PUMP is energized until the CONDENSER REFRIG TEMP is greater than the CONDENSER FREEZE POINT plus 5º F (2.7º C) and the ENTERING CONDENSER LIQUID TEMPERATURE is greater than or equal to the CONDENSER FREEZE POINT. An alarm (244) is generated if the chiller is in PUMPDOWN mode and the pump is energized. An alert (154) is generated if the chiller is not in PUMPDOWN mode and the pump is energized. If the chiller is in RECYCLE SHUTDOWN mode, the mode will transition to a non-recycle shutdown. 5 vdc input is available on the CCM module [terminal J5-5 (–) and J5-6 (+)] for a refrigerant leak detector. Enabling REFRIGERANT LEAK OPTION (OPTIONS screen) will allow the PIC III controls to go into an alarm state at a user configured level (REFRIG LEAK ALARM mA). The input is configured for 4 to 20 mA by setting CCM DIP switch 1 on SW2 at the ON position, or configured for 1 to 5 vdc by setting switch 1 at the OFF position. The output of the refrigerant leak detector is displayed as REFRIG LEAK SENSOR PPM on the MAINSTAT screen. For a 1 to 5 vdc input, 1 vdc input represents 4 mA displayed and 5 vdc input represents 20 mA displayed. 4 to 20 mA Kilowatt Output — An output is available on the CCM module [Terminal J8-1 (+) and J8-2 (–)] to represent the power consumption of the chiller. The 4 to 20 mA signal generated by the CCM module can be wired to the building automation or energy management system to monitor the chiller’s energy consumption. A 4 mA signal represents the chiller in an off state and a 20 mA signal represents the chiller operating at its rated peak kilowatt consumption. The rated peak kilowatt consumption is configured by the user in the VFD_CONF display screen by the setting the RATED LINE KILOWATTS from the Machine Electrical Data Nameplate. The kilowatt output is designed for use with non-grounded controllers with a maximum input impedance of 500 ohms. Tower Fan Relay Low and High — Low condenser liquid temperature can cause the chiller to shut down if it causes the condenser refrigerant temperature to be too low. The tower fan relays, located on terminals 5-8 on the hazardous voltage terminal strip (TB2) in the Control Center, are controlled by the PIC III to energize and deenergize as the pressure differential between cooler and condenser vessels changes. This prevents excessively low condenser liquid temperatures. The tower fan relay can only accomplish this if the relay has been added to the cooling tower temperature controller. The tower fan relay low is turned on whenever the condenser liquid pump is running, flow is verified, the difference between cooler and condenser pressure is more than 30 psid (207 kPad), and the ENTERING CONDENSER LIQUID temperature is greater than 65 F (18.3 C). The tower fan relay low is turned off when the CONDENSER LIQUID PUMP is deenergized, when CONDENSER LIQUID FLOW indication is lost, or under the following conditions: 1. CALC EVAP SAT TEMP is less than EVAP SAT OVERRIDE TEMP. 2. The difference between the CONDENSER PRESSURE and EVAPORATOR PRESSURE is less than 25 psi (172 kPa). The tower fan relay high is turned on whenever the condenser liquid pump is running, flow is verified and the difference between cooler and condenser pressure is more than 35 psid (241.3 kPa) for ENTERING COND LIQUID temperature greater than the TOWER FAN HIGH SETPOINT (SETPOINT menu, default 75 F [24 C]). The tower fan relay high is turned off when the condenser pump is off, flow is stopped, or the CALC EVAP SAT TEMP is less than the EVAP SAT OVERRIDE TEMP and ENTERING CONDENSER LIQUID is less than 70 F (21.1 C), The tower fan relay high is also turned off when the difference between CONDENSER PRESSURE and EVAPORATOR PRESSURE is less than 28 Psid (193 kPa), and ENTERING CONDENSER LIQUID temperature is less than TOWER FAN HIGH SETPOINT minus 3 F (1.6 C). Remote Reset of Alarms — A standard feature of the PIC III controls is the ability to reset certain faults on a chiller in a shutdown alarm state from a remote location. If the condition which caused the alarm has cleared the fault can be reset and the chiller can be placed back into a normal CCN operating mode when the REMOTE RESET OPTION (ICVC_PWD menu) is set to ENABLE. A variety of Carrier Comfort Network® software systems including ComfortVIEW™ or Network Service Tool® can access the PIC III controls and reset certain displayed alarms. Third party software from building automation systems (BAS) or energy management systems (EMS) can also access the PIC III controls through a Carrier DataLINK™, Dataport™, or LEI (Local Equipment Interface) module and reset certain faults displayed. All methods would access the ICVC_PWD screen and force the RESET ALARM? point to YES to reset the fault condition. If the PIC III controls have determined that it is safe to start the chiller the CCN MODE? point (ICVC_PWD screen) can be forced to YES to place the chiller back into normal CCN operating mode. The only exceptions are the following alarms that cannot be reset from a remote location: ALARM STATES #200, 201, 204, 206, 217, 218, 219, 220 and 236. To view alarm codes, refer to Troubleshooting Guide, Checking Display Messages, page 79. After the alarm has been reset the PIC II control will increment the Starts in 12 Hours counter by one upon restart. If the limit of 8 starts in a 12-hour period occurs Prestart Alert 100 must be manually reset at the local chiller control panel (ICVC). Condenser Pump Control — The chiller will moni- tor the condenser pressure (CONDENSER PRESSURE) and may turn on the condenser pump if the condenser pressure becomes too high while the compressor is shut down. The condenser pressure override (COND PRESS OVERRIDE) parameter is used to determine this pressure point. COND PRESS OVERRIDE is found in the SETUP1 display screen, which is accessed from the EQUIPMENT SERVICE table. The default value is 145 psig (543 kPa). 39 2 permits ±30 F (±17 C) of automatic reset to the ECL SETPOINT or LCL SETPOINT based on a temperature sensor wired to the CCM module (see wiring diagrams or certified drawings). The temperature sensor must be wired to CCM terminal J4-13 and J4-14. To configure Reset Type 2, enter the temperature of the remote sensor at the point where no temperature reset will occur (REMOTE TEMP -> NO RESET). Next, enter the temperature at which the full amount of reset will occur (REMOTE TEMP -> FULL RESET). Then, enter the maximum amount of reset required to operate the chiller (DEGREES RESET). Reset Type 2 can now be enabled. RESET TYPE 3 — Reset Type 3 is an automatic chilled liquid temperature reset based on the difference between ENTERING CHILLED LIQUID and LEAVING CHILLED LIQUID temperature. Reset Type 3 adds ±30 F (±17 C) based on the chilled liquid temperature difference. To configure Reset Type 3, enter the chilled liquid temperature difference (the difference between entering and leaving chilled liquid) at which no temperature reset occurs (CHL DELTA T -> NO RESET). This chilled liquid temperature difference is usually the full design load temperature difference. Next, enter the difference in chilled liquid temperature at which the full amount of reset occurs (CHL DELTA T -> FULL RESET). Finally, enter the amount of temperature reset (DEGREES RESET). Reset Type 3 can now be enabled. Demand Limit Control Option — The demand limit control option (20 mA DEMAND LIMIT OPT) is externally controlled by a 4 to 20 mA or 1 to 5 vdc signal from an energy management system (EMS). The option is set up on the RAMP_DEM screen. When enabled, 4 mA is the 100% demand set point with an operator-configured minimum demand at a 20 mA set point (DEMAND LIMIT AT 20 mA). The auto. demand limit is hardwired to terminals J5-1 (–) and J5-2 (+) on the CCM. Switch setting number 1 on CCM SW2 will determine the type of input signal. With the switch set at the ON position the input is configured for an externally powered 4 to 20 mA signal. With the switch in the OFF position the input is configured for an external 1 to 5 vdc signal. One of the following modifications are also required when using a 1 to 5 vdc DEMAND LIMIT signal: 1. Install a 25 ohm resistor in series with the (+) voltage lead connected to CCM terminal J5-2. 2. Modify the input voltage signal with an external controller software to calibrate the temperature interpreted by the CCM. The controller should provide 4.54 v at 100% of the controller’s output range and 0.91 v at 0% of the controller’s output range. The TOWER FAN RELAY LOW and HIGH parameters are accessed from the STARTUP screen. IMPORTANT: A field-supplied liquid temperature control system for condenser liquid should be installed. The system should maintain the leaving condenser liquid temperature at a temperature that is 20º F (11º C) above the leaving chilled liquid temperature. The tower fan relay control is not a substitute for a condenser liquid temperature control. When used with a liquid temperature control system, the tower fan relay control can be used to help prevent low condenser liquid temperatures. Auto. Restart After Power Failure — This option may be enabled or disabled and may be viewed or modified on the OPTIONS screen, which is accessed from the SERVICE table. If the AUTO. RESTART option is enabled, the chiller will start up automatically after a power failure has occurred (after a single cycle dropout; low, high, or loss of voltage; and the power is within ±10% of normal). The 15 and 3-minute inhibit timers are ignored during this type of start-up. When power is restored after the power failure, a power failure restart will be enabled and the control allowed to AUTORESTART the chiller, starting with the chilled liquid pump(s), if start-up conditions are met. If power to the ICVC module has been off for more than 3 hours or the timeclock has been set for the first time, the compressor will start with the slowest temperature-based ramp load rate possible in order to minimize oil foaming. Liquid/Brine Temperature Reset — Three types of chilled liquid or brine setpoint temperature reset are available and can be viewed or modified on the TEMP_CTL screen, which is accessed from the EQUIPMENT SERVICE table. The ICVC default screen indicates when the chilled liquid reset is active. TEMPERATURE RESET on the MAINSTAT screen indicates the amount of reset. The CONTROL POINT will be determined by adding the TEMPERATURE RESET to the ECL SETPOINT or LCL SETPOINT. To activate a reset type, access the TEMP_CTL screen and input all configuration information for that reset type. Then, input the reset type number (1, 2, or 3) in the SELECT/ ENABLE RESET TYPE input line. RESET TYPE 1: 4 to 20 mA (0 to 5 vdc) TEMPERATURE RESET — Reset Type 1 is an automatic chilled liquid temperature reset based on a remote temperature sensor input configured for either an externally powered 4 to 20 mA or a 0 to 5 vdc signal. Reset Type 1 permits up to ±30 F (±17 C) of automatic reset to the ECL SETPOINT or LCL SETPOINT. The auto, chilled liquid reset is hardwired to CCM terminals J5-3 (–) and J5-4 (+). Switch setting number 2 on SW2 will determine the type of input signal. With the switch set at the ON position the input is configured for an externally powered 4 to 20 mA signal. With the switch in the OFF position the input is configured for an external 0 to 5 vdc signal. One of the following modifications are also required when using a 1 to 5 vdc temperature reset signal: 1. Install a 25 ohm resistor in series with the (+) voltage lead connected to CCM terminal J5-4. 2. Modify the input voltage signal with an external controller software to calibrate the temperature interpreted by the CCM. The controller should provide 4.54 v at 100% of the controller’s output range and 0.91 v at 0% of the controller’s output range. RESET TYPE 2: REMOTE TEMPERATURE RESET — Reset Type 2 is an automatic chilled liquid temperature reset based on a remote temperature sensor input signal. Reset Type Hot Gas Bypass (Optional) Algorithm (See Fig. 22A, 22B, and 23) — If a hot gas bypass solenoid valve is present and the HGBP OPTION in the OPTIONS table is set to 1 or 2, this operator configurable feature can determine if load conditions are too low for the compressor and corrective action can be taken. When the HGBP OPTION = 0: the HGBP algorithm is disabled. When the HGBP OPTION = 1, the algorithm determines if corrective action is necessary by checking the chiller operating point against an operator configured threshold. The threshold is calculated from a combination of the difference between Entering and Leaving Chilled Liquid temperatures and the difference between CONDENSER PRESSURE and EVAPORATOR PRESSURE. The operator configured data points are the MIN LOAD POINT(T1/P1) and the FULL LOAD POINT (T2/P2). These points have default settings defined in the OPTIONS screen and on Table 3. A line is drawn between these points as shown in Fig. 22A and 22B. The default Load Points (to prevent compressor stall) are shown. Whenever the 40 ACTIVE DELTA T (actual temperature difference between the LEAVING CHILLED LIQUID and ENTERING CHILLED LIQUID) is on the left side of the line plotted in Fig. 22A and 22B, the algorithm will energize the hot gas bypass valve to falsely load the chiller. If the ACTIVE DELTA T falls to the right side of the line plotted in Fig 22A and 22B by more than the HGBP DEADBAND, the hot gas bypass valve is deenergized. The HGBP valve is also deenergized if the ACTIVE DELTA P (actual difference between CONDENSER PRESSURE and EVAPORATOR PRESSURE) falls to below HGBP DELTA P1. Instructions to configure the MIN LOAD POINT(T1/P1) and FULL LOAD POINT(T2/P2) are on page 60. When the HGBP OPTION = 2, the option energizes the Hot Gas Bypass relay solely based on the ACTIVE DELTA T (actual temperature difference between the LEAVING CHILLED LIQUID and ENTERING CHILLED LIQUID). Evaluation of the ACTIVE DELTA T begins at the completion of ramp loading. The hot gas bypass valve is energized if the ACTIVE DELTA T is less than the HGBP ON DELTA T. The hot gas bypass relay will be turned off when the ACTIVE DELTA T is greater than or equal to the sum of HGBP ON DELTA T plus HGBP OFF DELTA T. See Fig. 23. a23-1609 DEFAULT VALUES: LEGEND ΔP — ΔT ECL LCL HGBP Condenser PressureCooler Pressure — ECL-LCL — Entering Chilled Liquid Temperature — Leaving Chilled Liquid Temperature — Hot Gas Bypass POINT ΔT1 ΔP1 ΔT2 ΔP2 HFC-134a 0.8 1034 2.2 1379 Fig. 22B — 23XRV Hot Gas Bypass Option 1 (SI) Head Pressure Output Reference (See Fig. 24) — The PIC III control outputs a 4 to 20 mA signal HGBP OFF DELTA T for the configurable Delta P (CONDENSER PRESSURE – EVAPORATOR PRESSURE) reference curve shown in Fig. 24. The DELTA P AT 100% (default at 50 psi). DELTA P AT 0% (default at 25 psi) and MINIMUM OUTPUT are configurable in the EQUIPMENT SERVICE-OPTIONS table. When configuring this output, ensure that minimum requirements for proper condenser FLASC orifice performance are maintained. The 4 to 20 mA output from VFD TB1 terminals 17 and 18 can be used as a reference to control a tower bypass valve, tower speed control, or condenser pump speed control. The head pressure output is designed for use with non-grounded controllers with a maximum input impedence of 500 ohms. NOTE: It is up to the site design engineering agent to integrate this analog output with any external system device(s) to produce the desired effect. Carrier does not make any claim that this output is directly usable to control any specific piece of HGBP Off As ACTIVE DELTA T Decreases ΔP HGBP Off HGBP On HGBP On As ACTIVE DELTA T Increases HGBP ON DELTA T ΔT a23-1636 LEGEND ΔP ΔT HGBP — Condenser Pressure – Evaporator Pressure Entering Chilled Liquid – Leaving Chilled Liquid — Hot Gas Bypass — Fig. 23 — Hot Gas Bypass Option 2 DELTA P AT 100% DELTA P NON-ZERO EXAMPLE OF MINIMUM HEAD PRESSURE REFERENCE OUTPUT a23-1608 LEGEND ΔP — ΔT ECL — — LCL — HGBP — Condenser PressureCooler Pressure ECL-LCL Entering Chilled Liquid Temperature Leaving Chilled Liquid Temperature Hot Gas Bypass DELTA P AT 0% DEFAULT VALUES: POINT ΔT1 ΔP1 ΔT2 ΔP2 HFC-134a 1.5 150 4 200 0 mA 2 mA 4 mA (0%) a23-1610 Fig. 22A — 23XRV Hot Gas Bypass Option 1 (English) 4 T0 20 mA OUTPUT Fig. 24 — Head Pressure Output Reference Control 41 20 mA (100%) If return chilled liquid control is required on chillers piped in series, the common point return chilled liquid sensor should be installed. If this sensor is not installed, the return chilled liquid sensor of the downstream chiller must be relocated to the return chilled liquid pipe of the upstream chiller. To properly control the common supply point temperature sensor when chillers are piped in parallel, the liquid flow path through the shutdown chillers must be isolated so no liquid bypass around the operating chiller occurs. The common point sensor option must not be used if liquid bypass around the operating chiller is occurring. CHILLER COMMUNICATION WIRING — Refer to the chiller’s Installation Instructions, Carrier Comfort Network® Interface section for information on chiller communication wiring. LEAD/LAG OPERATION — The PIC III not only has the ability to operate 2 chillers in lead/lag, but it can also start a designated standby chiller when either the lead or lag chiller is faulted and capacity requirements are not met. The lead/lag option only operates when the chillers are in CCN mode. If any other chiller configured for lead/lag is set to the LOCAL or OFF modes, it will be unavailable for lead/lag operation. Lead/Lag Chiller Configuration and Operation • A chiller is designated the lead chiller when its LEAD/ LAG CONFIGURATION value on the LEADLAG screen is set to “1.” • A chiller is designated the lag chiller when its LEAD/ LAG CONFIGURATION value is set to “2.” • A chiller is designated as a standby chiller when its LEAD/LAG CONFIGURATION value is set to “3.” • A value of “0” disables the lead/lag designation of a chiller. To configure the LAG ADDRESS value on the LEADLAG screen, always enter the address of the other chiller on the system. For example, to configure chiller A, enter the address for chiller B as the lag address. To configure chiller B, enter the address for chiller A as the lag address. This makes it easier to rotate the lead and lag chillers. If the address assignments in the LAG ADDRESS and STANDBY ADDRESS parameters conflict, the lead/lag function is disabled and an alert (!) message displays. For example, if the LAG ADDRESS matches the lead chiller’s address, the lead/lag will be disabled and an alert (!) message displayed. The lead/lag maintenance screen (LL_MAINT) displays the message ‘INVALID CONFIG’ in the LEAD/LAG: CONFIGURATION and CURRENT MODE fields. Refer to Table 7. equipment (that is, without further control elements or signal conditioning), although it may be. The head pressure reference output will be on whenever the condenser pump is operating. It may also be manually operated in CONTROLS TEST. When the head pressure differential is less than the value entered for DELTA P AT 0%, the output will be maintained at 4 mA. The output is 2 mA when the chiller is not running. Lead/Lag Control — The lead/lag control system auto- matically starts and stops a lag or second chiller in a 2-chiller liquid system. A third chiller can be added to the lead/lag system as a standby chiller to start up in case the lead or lag chiller in the system has shut down during an alarm condition and additional cooling is required. Refer to Fig. 18 and 19 for menu, table, and screen selection information. The output is 2 mA when the chiller is not running. NOTE: The lead/lag function can be configured on the LEADLAG screen, which is accessed from the SERVICE menu and EQUIPMENT SERVICE table. See Table 3, Example 21. Lead/lag status during chiller operation can be viewed on the LL_MAINT display screen, which is accessed from the SERVICE menu and CONTROL ALGORITHM STATUS table. See Table 3, Example 12. Lead/Lag System Requirements: • all chillers in the system must have software capable of performing the lead/lag function • liquid pumps MUST be energized from the PIC III controls • liquid flows should be constant • the CCN time schedules for all chillers must be identical Operation Features: • 2 chiller lead/lag • addition of a third chiller for backup • manual rotation of lead chiller • load balancing if configured • staggered restart of the chillers after a power failure • chillers may be piped in parallel or in series chilled liquid flow COMMON POINT SENSOR INSTALLATION — In all cases lead/lag operation does not require a common point chilled liquid sensor. Common point sensors (Spare Temp #1 and #2) can be added to the CCM module, if desired. Spare Temp #1 and #2 are wired to plug J4 terminals 25-26 and 27-28 (J4 lower, respectively). See the Lead/Lag Control Wiring on page 116. NOTE: If the common point sensor option is chosen on a chilled liquid system, each chiller should have its own common point sensor installed. Each chiller uses its own common point sensor for control when that chiller is designated as the lead chiller. The PIC III cannot read the value of common point sensors installed on the other chillers in the chilled liquid system. If leaving chilled liquid control (ECL CONTROL OPTION is set to 0 [DSABLE], TEMP_CTL screen) and a common point sensor is desired (COMMON SENSOR OPTION in LEADLAG screen selected as 1) then the common point temperature sensor is wired in Spare Temp #1 position on the CCM. If the entering chilled liquid control option (ECL CONTROL OPTION) is enabled (configured in TEMP_CTL screen) and a common point sensor is desired (COMMON SENSOR OPTION in LEADLAG screen selected as 1) then the sensor is wired in Spare Temp #2 position on the CCM. When installing chillers in series, a common point sensor should be used. If a common point sensor is not used, the leaving chilled liquid sensor of the upstream chiller must be moved into the leaving chilled liquid pipe of the downstream chiller. Table 7 — Invalid Lead/Lag Addresses LEAD/LAG CONFIGURATION (In LEAD/LAG Screen) INVALID CONDITIONS Local Address (Lead) = Lag Address 1 (Lead) Standby Chiller Option = Enable and Local Address (Lead) = Standby Address Standby Chiller Option = Enable and Lag Address = Standby Address Local Address (Lead) = Lag Address 2 (Lag) Standby Chiller Option = Enable and Local Address (Lag) = Standby Address The lead chiller responds to normal start/stop controls such as the occupancy schedule, a forced start or stop, and remote start contact inputs. After completing start-up and ramp loading, the PIC III evaluates the need for additional capacity. If additional capacity is needed, the PIC III initiates the start-up of the chiller configured at the LAG ADDRESS. If the lag chiller is faulted (in alarm) or is in the OFF or LOCAL modes, 42 When all the above requirements have been met, the lag chiller is commanded to a STARTUP mode (SUPVSR flashing next to the point value on the STATUS table). The PIC III control then monitors the lag chiller for a successful start. If the lag chiller fails to start, the standby chiller, if configured is started. Lead/Lag Pulldown Timer Operation — Some lead/lag chiller applications with large chilled liquid loop volumes must accommodate intermittent slugs of warm ENTERING CHILLED LIQUID for short time periods. This type of transient condition can result when a control valve rapidly opens to allow flow through a previously isolated branch or zone within the chilled liquid system. A PULLDOWN TIMER can be configured to delay starting the lag chiller so it does not excessively cycle on and off for short time periods when intermittent slugs of warm ENTERING CHILLED LIQUID pass through the chillers. A larger PULLDOWN TIMER entry gives the warm slug of water more time to pass through the chillers before the lag chiller will start. The chiller CONTROL POINT can be configured to either LEAVING CHILLED LIQUID or ENTERING CHILLED LIQUID temperature. The PIC Controls monitor the temperature pulldown rate of the CHILLED LIQUID and display the result as CHILL LIQ PULLDOWN/MIN in the HEAT_EX screen. Samples of the CHILLED LIQUID temperature are taken once every 10 seconds and compared against the previous CHILLED LIQUID sample. A positive value of CHILL LIQ PULLDOWN/MIN indicates that the CHILLED LIQUID temperature is decreasing between successive samples. If CHILL LIQ PULLDOWN/MIN rate is a minimum of 0.5 degrees F per minute then the PULLDOWN: SATISFIED parameter in the LL_MAINT screen displays “YES”, otherwise, the PULLDOWN: SATISFIED parameter displays “NO”. If the lead chiller is unable to achieve the CONTROL POINT, the lag chiller will not start unless the lead chiller is unable to maintain a CHILL LIQ PULLDOWN/MIN rate of 0.5 degrees F per minute for a time period equal to the number of minutes entered in the PULLDOWN TIMER parameter. PULLDOWN TIME in the LL_MAINT screen displays the remaining delay left before the lag chiller is allowed to start based on the pulldown timer. PULLDOWN TIME will count down starting at the value entered in PULLDOWN TIMER when Ramp Loading is complete and when PULLDOWN: SATISIFIED = NO. The lag chiller pulldown start condition is met when PULLDOWN TIME lapses to 0.0 min. If PULLDOWN: SATISFIED changes to “YES” as the PULLDOWN TIME is counting down to zero, the PULLDOWN TIME will start to count back up provided that the CHILLED LIQUID temperature has not fallen to less than the CONTROL POINT plus one half of the CHILLED LIQUID DEADBAND. The PULLDOWN TIME will start to count back down again should PULLDOWN: SATISFIED change back to “NO”. The PULLDOWN TIME will be immediately reset to the value entered in the PULLDOWN TIMER parameter if the CHILLED LIQUID temperature decreases to less than the CONTROL POINT plus one half of the CHILLED LIQUID DEADBAND. Lag Chiller Shutdown Requirements — The following conditions must be met in order for the lag chiller to be stopped. 1. Lead chiller AVERAGE LINE CURRENT or PERCENT MOTOR KILOWATTS load value (on the MAINSTAT screen) is less than the Lead Chiller Percent Capacity. NOTE: Lead Chiller Percent Capacity = 105 – LAG % CAPACITY. The LAG % CAPACITY parameter is on the LEADLAG screen, which is accessed from the EQUIPMENT SERVICE table on the SERVICE menu. the chiller at the STANDBY ADDRESS (if configured) is requested to start. After the second chiller is started and is running, the lead chiller monitors conditions and evaluates whether the capacity has been reduced enough for the lead chiller to sustain the system alone. If the capacity is reduced enough for the lead chiller to sustain the CONTROL POINT temperature alone, then the operating lag chiller is stopped. If the lead chiller is stopped in CCN mode for any reason other than an alarm (*) condition, the lag and standby chillers are also stopped. If the configured lead chiller stops for an alarm condition, the configured lag chiller takes the lead chiller’s place as the lead chiller, and the standby chiller serves as the lag chiller. If the configured lead chiller does not complete the start-up before the PRESTART FAULT TIMER (configured in LEADLAG screen) elapses, then the lag chiller starts and the lead chiller shuts down. The lead chiller then monitors the start request from the acting lead chiller. The PRESTART FAULT TIMER is initiated at the time of a start request. The PRESTART FAULT TIMER provides a timeout if there is a prestart alert condition that prevents the acting lead chiller from starting in a timely manner. The PRESTART FAULT TIMER parameter is on the LEAD-LAG screen, which is accessed from the EQUIPMENT SERVICE table of the SERVICE menu. If the lag chiller does not achieve start-up before the PRESTART FAULT TIMER elapses, the lag chiller stops, and the standby chiller is requested to start, if configured and ready. Standby Chiller Configuration and Operation — A chiller is designated as a standby chiller when its LEAD/LAG CONFIGURATION value on the LEADLAG screen is set to “3.” The standby chiller can operate as a replacement for the lag chiller only if one of the other two chillers is in an alarm (*) condition (as shown on the ICVC panel). If both lead and lag chillers are in an alarm (*) condition, the standby chiller defaults to operate in CCN mode, based on its configured occupancy schedule and remote contacts input. Lag Chiller Start-Up Requirements — Before the lag chiller can be started, the following conditions must be met: 1. The lag chiller status indicates it is in CCN mode and is not in an alarm condition. If the current lag chiller is in an alarm condition, the standby chiller becomes the active lag chiller, if it is configured and available. 2. Lead chiller ramp loading must be complete. 3. The configured LAG START TIMER entry has elapsed. The LAG START TIMER starts when the lead chiller ramp loading is completed or when a lag chiller stops. The LAG START TIMER entry is on the LEADLAG screen, which is accessed from the EQUIPMENT SERVICE table of the SERVICE menu. 4. Lead chiller ACTIVE DEMAND LIMIT (see the MAINSTAT screen) value must be greater than 95% of full load amps. 5. Lead CHILLED LIQUID TEMP must be greater than the CONTROL POINT temperature (see the MAINSTAT screen) plus 1/2 the CHILLED LIQUID DEADBAND temperature (see the SETUP1 screen). NOTE: The chilled liquid temperature sensor may be the leaving chilled liquid sensor, the return liquid sensor, the common supply liquid sensor, or the common return liquid sensor, depending on which options are configured and enabled. 6. Lead chiller temperature pulldown rate (TEMP PULLDOWN DEG/MIN on the TEMP_CTL screen) of the chilled liquid temperature is less than 0.5º F (0.27º C) per minute for a cumulative duration greater than the PULLDOWN TIMER setting in the LEADLAG screen. 43 DEMAND LIMIT is set, the CONTROL POINT is assigned a value of 3º F (1.67º C) less than the lead chiller’s CONTROL POINT value to better match the lead chiller’s load level. If the LOAD BALANCE OPTION is disabled, the ACTIVE DEMAND LIMIT and the CONTROL POINT are forced to the same value as the lead chiller. AUTO RESTART AFTER POWER FAILURE — When an Auto restart condition occurs, each chiller may have a delay added to the start-up sequence, depending on its lead/lag configuration. The lead chiller does not have a delay. The lag chiller has a 45-second delay. The standby chiller has a 90-second delay. The delay time is added after the chiller liquid flow is verified. The delay must elapse before the oil pump is turned on. The Auto restart delay sequence occurs whether the chiller is in CCN or LOCAL mode and is intended to stagger the compressor motor starts. Preventing the motors from starting simultaneously helps reduce the inrush demands on the building power system. 2. The lead chiller CHILLED LIQUID TEMP is less than the CONTROL POINT temperature (see the MAINSTAT screen) plus on half of the CHILLED LIQUID DEADBAND temperature (see the SETUP1 screen). 3. The configured LAG STOP TIMER entry has elapsed. The LAG STOP TIMER starts when the lead chiller CHILLED LIQUID TEMP is less than the chilled liquid CONTROL POINT plus 1/2 of the CHILLED LIQUID DEADBAND and the lead chiller compressor motor load (PERCENT MOTOR KILOWATTS or AVERAGE LINE CURRENT on the MAINSTAT screen) is less than the lead chiller percent capacity. NOTE: The use of AVERAGE LINE CURRENT or PERCENT MOTOR KILOWATTS in the Lag chiller shutdown decision is based on the DEMAND LIMIT SOURCE configuration in the RAMP_DEM screen. If DEMAND LIMIT SOURCE = 0 then AVERAGE LINE CURRENT will be used. If DEMAND LIMIT SOURCE = 1 then PERCENT MOTOR KILOWATTS will be used. FAULTED CHILLER OPERATION — If the lead chiller shuts down because of an alarm (*) condition, it stops communicating to the lag and standby chillers. After 30 seconds, the lag chiller becomes the acting lead chiller and starts and stops the standby chiller, if necessary. If the lag chiller goes into alarm when the lead chiller is also in alarm, the standby chiller reverts, after 60 seconds, to a stand-alone CCN mode of operation. If the lead chiller is in an alarm (*) condition (as shown on the ICVC panel), press the RESET softkey to clear the alarm. The lead chiller is placed in CCN mode. The lead chiller communicates and monitors the RUN STATUS of the lag and standby chillers. If both the lag and standby chillers are running, the lead chiller does not attempt to start and does not assume the role of lead chiller until either the lag or standby chiller shuts down. If only one chiller is running, the lead chiller waits for a start request from the operating chiller. When the configured lead chiller starts, it resumes its role as lead chiller. Attach to Network Device Control — The Service menu includes the ATTACH TO NETWORK DEVICE screen. From this screen the operator can: • attach the ICVC to any CCN device, if the chiller has been connected to a CCN network. This may include other PIC-controlled chillers. • upgrade software Figure 25 shows the ATTACH TO NETWORK DEVICE screen. The LOCAL parameter is always the ICVC module address of the chiller on which it is mounted. Whenever the controller identification of the ICVC changes, the change is reflected automatically in the BUS and ADDRESS columns for the local device. See Fig. 19. Default address for local device is BUS 0 ADDRESS 1. When the ATTACH TO NETWORK DEVICE screen is accessed, information can not be read from the ICVC on any device until one of the devices listed on that screen is attached. The ICVC erases information about the module to which it was attached to make room for information on the new device. Therefore, a CCN module must be attached when this screen is entered. To attach any CCN device, highlight it using the SELECT softkey and press the ATTACH softkey. The message “UPLOADING TABLES, PLEASE WAIT” displays. The ICVC then uploads the highlighted device or module. If the module address cannot be found, the message “COMMUNICATION FAILURE” appears. The ICVC then reverts back to the ATTACH TO DEVICE screen. Try another device or check the address of the device that would not attach. The upload process time for each CCN module is different. In general, the uploading process takes 1 to 2 minutes. Before leaving the ATTACH TO NETWORK DEVICE screen, select the local device. Otherwise, the ICVC will be unable to display information on the local chiller. If the lag chiller is the only chiller running and the lead chiller is ready to resume its role as a lead chiller then the lag chiller will perform a RECOVERY START REQUEST (LL_MAINT screen). The lead chiller will start up when the following conditions are met. 1. Lag chiller ramp loading must be complete. 2. Lag CHILLED LIQUID TEMP (MAINSTAT screen) is greater than CONTROL POINT plus 1/2 the CHILLED LIQUID DEADBAND temperature. 3. Lag chiller ACTIVE DEMAND LIMIT value must be greater than 95% of full load amps. 4. Lag chiller temperature pulldown rate (TEMP PULLDOWN DEG/MIN) of the chilled liquid temperature is less than 0.5 F (0.27 C) per minute for a cumulative time duration greater than the PULLDOWN TIMER setting in the lag chiller’s LEADLAG screen. 5. The standby chiller is not running as a lag chiller. 6. The configured LAG START TIMER has elapsed. The LAG START TIMER is started when ramp loading is completed. LOAD BALANCING — When the LOAD BALANCE OPTION (see LEADLAG screen) is enabled, the lead chiller sets the ACTIVE DEMAND LIMIT in the lag chiller to the lead chiller’s AVERAGE LINE CURRENT or PERCENT MOTOR KILOWATTS value in the POWER screen. This value has limits of 40% to 100%. When the lag chiller ACTIVE a23-1611 Fig. 25 — Example of Attach to Network Device Screen 44 • • • • • • • • • • Alert History Control Test Control Algorithm Status Equipment Configuration VFD Config Data Equipment Service Time and Date Attach to Network Device Log Out of Device ICVC Configuration See Fig. 19 for additional screens and tables available from the SERVICE screens listed above. Use the EXIT softkey to return to the main MENU screen. ATTACHING TO OTHER CCN MODULES — If the chiller ICVC has been connected to a CCN Network or other PIC controlled chillers through CCN wiring, the ICVC can be used to view or change parameters on the other controllers. Other PIC III chillers can be viewed and set points changed (if the other unit is in CCN control), if desired, from this particular ICVC module. If the module number is not valid, the “COMMUNICATION FAILURE” message will show and a new address number must be entered or the wiring checked. If the module is communicating properly, the “UPLOAD IN PROGRESS” message will flash and the new module can now be viewed. Whenever there is a question regarding which module on the ICVC is currently being shown, check the device name descriptor on the upper left hand corner of the ICVC screen. See Fig. 25. When the CCN device has been viewed, the ATTACH TO NETWORK DEVICE table should be used to attach to the PIC that is on the chiller. Move to the ATTACH TO NETWORK DEVICE table (LOCAL should be highlighted) and press the ATTACH softkey to upload the LOCAL device. The ICVC for the 23XRV will be uploaded and default screen will display. NOTE: To prevent unauthorized persons from accessing the ICVC service screens, the ICVC automatically signs off and password-protects itself if a key has not been pressed for 15 minutes. The sequence is as follows. Fifteen minutes after the last key is pressed, the default screen displays, the ICVC screen light goes out (analogous to a screen saver), and the ICVC logs out of the password-protected SERVICE menu. The STATUS, SCHEDULE, and SETPOINT screens can be accessed without the password by pressing the appropriate softkey. TO LOG OUT OF DEVICE — To access this screen and log out of a network device, from the default ICVC screen, press the MENU and SERVICE softkeys. Enter the password and, from the SERVICE menu, highlight LOG OUT OF NETWORK DEVICE and press the SELECT softkey. The ICVC default screen will now be displayed. NOTE: The ICVC will not automatically reattach to the local module on the chiller. Press the ATTACH softkey to attach to the LOCAL device and view the local chiller operation. Service Operation — An overview of the tables and screens available for the SERVICE function is shown in Fig. 19. TO ACCESS THE SERVICE SCREENS — When the SERVICE screens are accessed, a password must be entered. 1. From the main MENU screen, press the SERVICE softkey. The softkeys now correspond to the numerals 1, 2, 3, 4. HOLIDAY SCHEDULING (Fig. 26) — The time schedules may be configured for special operation during a holiday period. When modifying a time period, the “H” in the far right column of the OCCPC01S, OCCPC02S or OCCPC03S time schedule screen signifies that the period is applicable to a holiday. (See Fig. 20.) The TIME BROADCAST ENABLE function must be activated for the holidays configured on the HOLIDAYS screen to work properly. Access the BRODEF screen from the EQUIPMENT CONFIGURATION table, highlight TIME BROADCAST ENABLE and select ENABLE to activate function. Note that when the chiller is connected to a CCN network, only one chiller or CCN device can be configured as the broadcast device. The controller that is configured as the broadcaster is the device responsible for transmitting holiday, time, and daylight-savings dates throughout the network. To access the BRODEF screen, see the SERVICE menu structure, Fig. 19. To view or change the holiday periods for up to 18 different holidays, perform the following operation: 1. At the Main Menu screen, press SERVICE to access the Service menu. 2. Press the four digits of the password, one at a time. An asterisk (*) appears as each digit is entered. NOTE: The initial factory-set password is 1-1-1-1. If the password is incorrect, an error message is displayed. If this occurs, return to Step 1 and try to access the SERVICE screens again. If the password is correct, the softkey labels change to: 2. If not logged on, follow the instructions for ATTACH TO NETWORK DEVICE CONTROL or To Log Out of Device. Once logged on, press NEXT until EQUIPMENT CONFIGURATION is highlighted. 3. Once EQUIPMENT CONFIGURATION is highlighted, press SELECT to access. NOTE: The SERVICE screen password can be changed by entering the ICVC CONFIGURATION screen under SERVICE menu. The password is located at the bottom of the menu. Contact Carrier Service to override the ICVC password if it is lost. The ICVC screen displays the following list of available SERVICE screens: • Alarm History 4. Press NEXT until HOLIDAYS is highlighted. This is the Holiday Definition table. 5. Press SELECT to enter the Data Table Select screen.This screen lists 18 holiday tables. 6. Press NEXT to highlight the holiday table that is to be viewed or changed. Each table is one holiday 45 softkey. This action returns the chiller to the start and stop times established by the schedule. The chiller may also be started by overriding the time schedule. From the default screen, press the MENU and SCHEDULE softkeys. Scroll down and select the current schedule. Scroll down and select OVERRIDE, and set the desired override time period. Another condition for start-up must be met for chillers that have the REMOTE CONTACTS OPTION on the EQUIPMENT SERVICE, OPTIONS screen set to ENABLE. For these chillers, the REMOTE START CONTACT parameter on the MAINSTAT screen must be CLOSED. From the ICVC default screen, press the MENU and STATUS softkeys. Scroll to high-light MAINSTAT and press the SELECT softkey. Scroll down the MAINSTAT screen to highlight REMOTE START CONTACT and press the SELECT softkey. Press the CLOSE softkey to initiate the override. To end the override, select REMOTE START CONTACT and press the RELEASE softkey. Once local start-up begins, the PIC III performs a series of pre-start tests to verify that all pre-start alerts and safeties are within the limits shown in Table 5. The RUN STATUS parameter on the MAINSTAT screen line now reads PRESTART. If a test is not successful, the start-up is delayed or aborted. Failure to verify any of the requirements up to this point will result in the PIC III aborting the start and displaying the applicable pre-start alert on the ICVC default screen. A pre-start alert does not advance the starts in 12 hours counter. If the tests are successful, the chilled liquid pump relay energizes, and the MAINSTAT screen line now reads STARTUP. Five seconds later, the condenser pump relay energizes. Thirty seconds later the PIC III monitors the chilled liquid and condenser liquid flow devices and waits until the LIQUID FLOW VERIFY TIME (operator-configured, default 5 minutes) expires to confirm flow. After flow is verified, the chilled liquid temperature is compared to CONTROL POINT plus 1/ CHILLED LIQUID DEADBAND. If the temperature is less 2 than or equal to this value, the PIC III turns off the condenser pump relay and goes into a RECYCLE mode. NOTE: The 23XRV chillers are not available with factoryinstalled external chilled liquid flow or condenser liquid flow devices. These are available as an accessory for use with the CCM control board. If the liquid temperature is high enough to require cooling, the start-up sequence continues. Tower fan control is enabled and the oil pump starts. Oil pressure is verified between 45 seconds and 5 minutes. The VFD is set to START following oil pressure verification and the controls verify that no faults exist. Proper compressor rotation is verified by monitoring the discharge pressure. The control center monitors load current to verify that the compressor is running then steps the compressor up to target speed. The start-to-start timer and Service On time timers are activated when compressor operation is confirmed. The controls will abort the start and display the applicable pre-start alert on the ICVC if any of the conditions above are not verified. Any fault after the startup process is complete results in a safety shutdown, advancing the STARTS IN 12 HOURS counter by one, and display of the applicable shutdown status on the ICVC display. Compressor ontime and service ontime timers start, and the compressor STARTS IN 12 HOURS counter in the MAINSTAT screen and the TOTAL COMPRESSOR STARTS counter advance by one. period, starting on a specific date, and lasting up to 99 days. 7. Press SELECT to access the holiday table. The Configuration Select table now shows the START MONTH, START DAY, and DURATION of the holiday period. 8. Press NEXT or PREVIOUS to highlight the START MONTH, START DAY, and DURATION. 9. Press SELECT to modify the month, day, or duration. 10. Press INCREASE or DECREASE to change the selected value. 11. Press ENTER to save the changes. 12. Press EXIT to return to the previous menu. 23XRPIC3 a23-1612 Fig. 26 — Example of Holiday Period Screen START-UP/SHUTDOWN/ RECYCLE SEQUENCE (Fig. 27) Local Start-Up — Local start-up (or a manual start-up) is initiated by pressing the LOCAL menu softkey on the default ICVC screen. Local start-up can proceed when the chiller schedule indicates that the current time and date have been established as a run time and date, and after the internal 15-minute start-to-start and the 1-minute stop-to-start inhibit timers have expired. These timers are represented in the START INHIBIT TIMER and can be viewed on the MAINSTAT screen and DEFAULT screen. The timer must expire before the chiller will start. If the timers have not expired the RUN STATUS parameter on the MAINSTAT screen now reads TIMEOUT. NOTE: The time schedule is said to be “occupied” if the OCCUPIED? parameter on the MAINSTAT screen is set to YES. For more information on occupancy schedules, see the sections on Time Schedule Operation (page 21), Occupancy Schedule (page 35), and To Prevent Accidental Start-Up (page 65), and Fig. 20. If the OCCUPIED? parameter on the MAINSTAT screen is set to NO, the chiller can be forced to start as follows. From the default ICVC screen, press the MENU and STATUS softkeys. Scroll to highlight MAINSTAT. Press the SELECT softkey. Highlight and select CHILLER START/STOP. Press the START softkey to override the schedule and start the chiller. NOTE: The chiller will continue to run until this forced start is released, regardless of the programmed schedule. To release the forced start, highlight and select CHILLER START/STOP from the MAINSTAT screen and press the RELEASE 46 When a stop signal occurs, the controls set TARGET VFD SPEED to 0. This will cause the compressor to reduce speed to the point where line amps equal the configured SOFT STOP AMPS THRESHOLD. (In a recycle shut down, the compressor will probably be at or below the soft stop threshold amps when the stop signal is received.) At that point, or one minute after the stop signal occurs (whichever is earlier), the VFD is set to STOP. If the STOP key is depressed a second time during the soft stop or within one minute of the stop signal occurring, the compressor is immediately stopped. When the VFD is set to STOP, the compressor is turned off. The compressor shut down is confirmed by monitoring load amps. When the compressor shut down is verified, the oil pump is turned off and VFD STOP is complete. After one minute, the chilled liquid pump is turned off, unless it is a recycle shut down. At this point, the compressor on-time and service on-time timers are turned off, and the stop-to-start timer is turned on. At this time the condenser liquid pump is also shut off, provided that the entering condenser liquid temperature is 115 F (6.1 C) or greater, and the condenser refrigerant temperature is greater than the condenser freeze point plus 5° F (3° C). Otherwise, it remains under the control of the Condenser Pump Control algorithm. If the shut down is due to low evaporator refrigerant temperature, the chilled liquid pump continues to run until the leaving chilled liquid temperature is greater than the control point, plus 5° F (3° C). Automatic Soft Stop Amps Threshold — When a non-recycle, non-alarm shutdown is called for, the soft stop feature unloads the compressor by reducing speed to the point where load amps equal the SOFT STOP AMPS THRESHOLD. The compressor is then turned off (see the above sequence). If the chiller enters an alarm state or if the compressor enters a RECYCLE mode, the compressor deenergizes immediately. To modify the soft stop amps threshold feature, scroll to the OPTIONS screen on the ICVC. Use the INCREASE or DECREASE softkey to set the SOFTSTOP AMPS THRESHOLD parameter to the percent of amps at which the motor will shut down. Setting SOFT STOP AMPS THRESHOLD to 100% de-activates this feature. The default setting is 100% amps (no soft stop). The range is 40 to 100%. a23-1613 A — START INITIATED: Pre-start checks are made; chilled liquid pump started B — Condenser liquid pump started (5 seconds after A) C — Liquid flows verified (30 sec to 5 minutes maximum after B) D — Chilled liquid temperature checked against control point; tower fan control enabled; oil pump on. E — Oil pressure verified (oil pressure verified 45-300 sec after D.) F — VFD starts; phase reversal conditions monitored; compressor ontime and service ontime start; 15-minute inhibit timer starts (VFD fault tests for 15 sec after “F”) G — Verify average current >5% within 15 sec after VFD start, ramp to VFD target speed. H — Compressor reaches target speed, chiller set to running status I — Ramp down until percent line current < soft stop amps threshold (0-60 sec after I) J — Shutdown initiated: Target VFD speed to 0%. All load currents <5%. K — Oil pump relay off (1-20 sec after J) L — Evaporator pump deenergized (60 sec after K); condenser pump and tower fan control may continue to operate if condenser pressure is high; evaporator pump may continue if in RECYCLE mode or freeze protection alarm declared. When the soft stop amps threshold feature is being applied, a status message, “SHUTDOWN IN PROGRESS, COMPRESSOR UNLOADING” displays on the ICVC. The soft stop amps threshold function can be terminated and the compressor motor deenergized immediately by depressing the STOP button twice. Chilled Liquid Recycle Mode — The chiller may cycle off and wait until the load increases to restart when the compressor is running in a lightly loaded condition. This cycling is normal and is known as “recycle.” A recycle shutdown is initiated when any of the following conditions are true: 1. ECL CONTROL OPTION is DISABLED (LCL control): The CONTROL POINT has not been increased by at least 1° F in the last 5 min. AND LEAVING CHILLED LIQUID temperature is less than the CONTROL POINT (MAINSTAT screen) minus 5° F. OR LEAVING CHILLED LIQUID temperature is less than the CONTROL POINT AND the difference between ENTERING CHILLED LIQUID — LEAVING CHILLED LIQUID is less than RECYCLE SHUTDOWN DELTA T and ice build is not active. O/A — Restart permitted (both inhibit timers expired) (minimum of 15 minutes after F; minimum of 1 minute after L) Fig. 27 — Control Sequence Shutdown Sequence — Chiller shutdown begins if any of the following occurs: • the STOP button is pressed for at least one second (the alarm light blinks once to confirm the stop command) • a recycle condition is present (see Chilled Liquid Recycle Mode section) • the time schedule has gone into unoccupied mode • the chiller protective limit has been exceeded and chiller is in alarm • the start/stop status is overridden to stop from the CCN network or the ICVC 47 2. ECL CONTROL OPTION is ENABLED AND ice build is not active (ECL control): The CONTROL POINT has not been increased by at least 1° F in the last 5 min. AND ENTERING CHILLED LIQUID temperature is less than the CONTROL POINT minus 5° F OR ENTERING CHILLED LIQUID temperature is less than the CONTROL POINT AND the difference between ENTERING CHILLED LIQUID — LEAVING CHILLED LIQUID is less than RECYCLE SHUTDOWN DELTA T. 3. The LEAVING CHILLED LIQUID temperature is less than the EVAP REFRIG TRIPPOINT plus 3° F. (NOTE: Refer to Refrigerant Low Temperature Override) Whenever recycle shutdown is active the RUN STATUS shall be “Recycle”. When the chiller is in RECYCLE mode, the chilled liquid pump relay remains energized so the chilled liquid temperature can be monitored for increasing load. The recycle control uses RECYCLE CONTROL RESTART DELTA T to check when the compressor should be restarted. This is an operator-configured function which defaults to 5º F (3º C). This value can be viewed or modified on the SETUP1 table. The compressor will restart when the chiller is: • in LCL CONTROL (ECL CONTROL OPTION DISABLED) and the LEAVING CHILLED LIQUID temperature is greater than the CONTROL POINT plus the RECYCLE CONTROL RESTART DELTA T. • in ECL CONTROL and the ENTERING CHILLED LIQUID temperature is greater than the CONTROL POINT plus the RECYCLE CONTROL RESTART DELTA T. Once these conditions are met, the compressor initiates a start-up with a normal start-up sequence. An alert condition may be generated if 5 or more recycle start-ups occur in less than 4 hours. Excessive recycling can reduce chiller life; therefore, compressor recycling due to extremely low loads should be reduced. To reduce compressor recycling, use the time schedule to shut the chiller down during known low load operation periods, or increase the chiller load by running the fan systems. If the hot gas bypass is installed, adjust the values to ensure that hot gas is energized during light load conditions. Increase the RECYCLE CONTROL RESTART DELTA T on the SETUP1 table to lengthen the time between restarts. The chiller should not be operated below design minimum load without a hot gas bypass installed. Equipment Required • • • • • • • • T30 hexalobular socket screw driver to remove control center door shipping brackets mechanic’s tools (refrigeration) digital volt-ohmmeter (DVM) clamp-on ammeter electronic leak detector absolute pressure manometer or wet-bulb vacuum indicator (Fig. 28) 500-v insulation tester (megohmmeter) for compressor motors with nameplate voltage of 600 v or less Reliance LCD OIM (operator interface module) (optional) Using the Optional Storage Tank and Pumpout System — Refer to Chillers with Storage Tanks sec- tion, page 70 for pumpout system preparation, refrigerant transfer, and chiller evacuation. Remove Shipping Packaging — Remove any packaging material from the control center, oil pump, VFD cooling solenoid, HGBP solenoid, oil reclaim actuator, oil heater terminal boxes, and relief valves. Open Oil Circuit Valves — Check to ensure the oil filter isolation valves (Fig. 8) are open by removing the valve cap and checking the valve stem. Oil Charge — The oil charge for the 23XRV chiller is split between the cooler and the oil vaporizer: Frame Size 3 4 5 Cooler Charge Oil Sump Charge Total 1 gal.(3.8 L) 6.5 gal.(24.6 L) 7.5 gal. (28.4 L) The chiller is shipped with its oil charge. The oil level in the vaporizer will initially be in the center of the oil sump sight glass. This level will vary depending on the amount of refrigerant that has been absorbed by the oil and the operating conditions of the chiller. Normal oil levels will vary from the top of the strainer housing sight glass to above the top of the oil sump sight glass. If oil is added, it must conform to Carrier’s specification for screw compressor use as described in the Oil Specification section. Charge the oil through the oil charging valve located near the bottom of the oil strainer housing. The oil must be pumped from the oil container through the charging valve due to the higher refrigerant pressure. The pumping device must be able to lift from 0 to 200 psig (1379 kPa) or above unit pressure. Oil should only be charged or removed when the chiller is shut down. Safety Shutdown — A safety shutdown is identical to a manual shutdown with the exception that, during a safety shutdown, the ICVC displays the reason for the shutdown, the alarm light blinks continuously, and the spare alarm contacts are energized. After a safety shutdown, the RESET softkey must be pressed to clear the alarm. If the alarm condition is still present, the alarm light continues to blink. Once the alarm is cleared, the operator must press the CCN or LOCAL softkeys to restart the chiller. Tighten All Gasketed Joints — Gaskets normally relax by the time the chiller arrives at the jobsite. Tighten all gasketed joints to ensure a leak-tight chiller. See Table 8 for waterbox torque specifications. Table 8 — Waterbox Bolt Torque COOLER or CONDENSER BEFORE INITIAL START-UP FRAME 3 Job Data Required • list of applicable design temperatures and pressures (product data submittal) • chiller certified prints • starting equipment details and wiring diagrams • diagrams and instructions for special controls or options • 23XRV Installation Instructions • pumpout unit instructions FRAME 4 FRAME 5 48 NOMINAL BOLT SIZE 5/ -11 8 3/ -10 4 5/ -11 8 3/ -10 4 7/ - 9 8 5/ -11 8 3/ -10 4 7/ - 9 8 TORQUE ft-lb 105-150 175-250 105-150 175-250 265-380 105-150 175-250 265-380 N-m 142-203 237-339 142-203 237-339 359-515 142-203 237-339 359-515 Never charge liquid refrigerant into the chiller if the pressure in the chiller is less than 35 psig (241 kPa). Charge as a gas only, with the cooler and condenser pumps running, until this pressure is reached, using PUMPDOWN and TERMINATE PUMPDOWN MODE on the ICVC. Flashing of liquid refrigerant at low pressures can cause tube freeze-up and considerable damage. 2. a19-658 Fig. 28 — Typical Wet-Bulb Type Vacuum Indicator Check Chiller Tightness — Figure 29 outlines the proper sequence and procedures for leak testing. 23XRV chillers are shipped with a full refrigerant and oil charge. Units may be ordered with the refrigerant shipped separately, and a 15 psig (103 kPa) nitrogen-holding charge in each vessel. To determine if there are any leaks, the chiller should be charged with a refrigerant tracer. Use an electronic leak detector to check all flanges and solder joints after the chiller is pressurized. If any leaks are detected, follow the leak test procedure. If the chiller is spring isolated, keep all springs blocked in both directions to prevent possible piping stress and damage during the transfer of refrigerant from vessel to vessel during the leak test process, or any time refrigerant is being transferred. Adjust the springs when the refrigerant is in operating condition and the liquid circuits are full. 3. 4. Refrigerant Tracer — Carrier recommends the use of an environmentally acceptable refrigerant tracer for leak testing with an electronic detector or halide torch. Ultrasonic leak detectors can also be used if the chiller is under pressure. 5. 6. Do not use air or oxygen as a means of pressurizing the chiller. Mixtures of HFC-134a and air can undergo combustion. Leak Test Chiller — Due to regulations regarding refrigerant emissions and the difficulties associated with separating contaminants from refrigerant, Carrier recommends the following leak test procedures. See Fig. 29 for an outline of the leak test procedures. Refer to Fig. 30-33 during pumpout procedures. See the Pumpout and Refrigerant Transfer Procedures Section on page 69. Refer to Tables 9A and 9B for temperature/pressure relationships for HFC-134a refrigerant. 1. If the pressure readings are normal for chiller condition: a. Evacuate the holding charge from the vessels, if present. b. Raise the chiller pressure, if necessary, by adding refrigerant until pressure is at equivalent saturated pressure for the surrounding temperature. 7. 49 c. Leak test chiller as outlined in Steps 3 - 7. If the pressure readings are abnormal for chiller condition: a. Prepare to leak test chillers shipped with refrigerant. If chiller is shipped with refrigerant, proceed to Step 3. b. Check for large leaks by connecting a nitrogen bottle and raising the pressure to 30 psig (207 kPa). Soap test all joints. If the test pressure holds for 30 minutes, prepare the test for small leaks (Steps 2g - h). c. Plainly mark any leaks which are found. d. Release the pressure in the system. e. Repair all leaks. f. Retest only those joints that were repaired. g. After successfully completing the test for large leaks, remove as much nitrogen, air, and moisture as possible, given the fact that small leaks may be present in the system. This can be accomplished by following the dehydration procedure, outlined in the Chiller Dehydration section, page 55. h. Slowly raise the system pressure to normal operating pressures for the refrigerant used in the chiller. Proceed with the test for small leaks (Steps 3-7). Check the chiller carefully with an electronic leak detector or halide torch. Leak Determination — If an electronic leak detector indicates a leak, use a soap bubble solution, if possible, to confirm. Total all leak rates for the entire chiller. Leakage at rates greater than 1 lb/year (0.45 kg/year) for the entire chiller must be repaired. Note total chiller leak rate on the start-up report. If no leak is found during initial start-up procedures, complete the transfer of refrigerant gas from the storage tank to the chiller. Retest for leaks. If no leak is found after a retest a. Transfer the refrigerant to the storage tank and perform a standing vacuum test as outlined in the Chiller Dehydration section, page 55. b. If the chiller fails this test, check for large leaks (Step 2b). c. Dehydrate the chiller if it passes the standing vacuum test. Follow the procedure in the Chiller Dehydration section. Charge chiller with refrigerant. If a leak is found, pump the refrigerant back into the storage tank, or if isolation valves are present, pump into the vessel that is not leaking. Transfer the refrigerant until chiller pressure is at least equal to the pressure specified by the EPA under 40 CFR Part 82. Repair the leak and repeat the procedure, beginning from Step 2h to ensure a leaktight repair. If chiller is opened to the atmosphere for an extended period, evacuate it before repeating leak test. a23-1614 50 Fig. 29 — 23XRV Leak Test Procedure 3/8" MALE FLARE RELIEF VALVE CONN. W LEVEL GAGE 0' - 9 " [229mm] TYPICAL 1/2" DIA. K.O. ELECTRICAL CONN. (PUMPOUT POWER) 0' - 5 1/2" [140mm] D E (2) 1" NPT RELIEF VALVE OUTLET (SEE FIELD INSTALLATION NOTES) PRESSURE GAGE R 1' - 7 " [483mm] T 0' - 5 7/8 " [149mm] a23-1541 B TOP VIEW 1/2" MALE FLARE VAPOR CONN. 3/4" NPT PUMPOUT CONDENSER WATER INLET CONN. NOTES: 1. 3/4" NPT PUMPOUT CONDENSER WATER OUTLET CONN. ELECTRICAL SERVICE ACCESS SPACE 20 3/4" X 8 3/4" X 4 1/2" (BOTH SIDES) Denotes center of gravity. 2. Dimensions in [ ] are in millimeters. 3. The weights and center of gravity values given are for an empty storage tank. 4. For additional information on the pumpout unit, see certified drawings. 5. Conduit knockout is located on the side of the control box. 6. 28 cubic ft storage tank weight: 2334 lb (1059 kg). 7. 52 cu ft storage tank weight: 3414 lb (1549 kg). VAPOR J L K F 1" NPT LIQUID CONN. V 0'- 9" [229mm] TYPICAL 0'- 9 7/8" [249mm] U N M G a23-1542 A FRONT VIEW DIMENSIONS 1'-0 3/4" [324mm] 0'- 7 15/16" [202mm] (FARSIDE) ENGLISH (ft-in.) 3/8" MALE FLARE RELIEF VALVE CONN. 0'- 2 3/4" [70mm] 1/2" DIA. K.O. ELECTRICAL CONN. (PUMPOUT POWER) (FAR SIDE) H C TANK SIZE 0428 D E F G 10- 5 4-41/4 2-43/4 1-23/8 3-11/4 6-43/16 3-113/ 0452 14-111/4 14- 41/2 4-81/4 2-81/2 1-41/4 3-41/2 7-21/4 A B 9-10 C H J K 8 3-47/8 2-99/16 4- 31/4 3-83/4 3-17/16 TANK SIZE 0428 L M N P R S T V W 3-45/8 0-31/2 4- 91/2 1-77/8 2-03/8 3-9 5-01/4 2-5 2-97/8 2-53/4 0452 3-81/2 0-33/8 6-115/8 1-83/4 2-05/8 4-1 5-01/2 2-51/4 2-101/8 2-6 U SI (mm) S P 0'- 10" [254mm] 0'- 3 1/4" [83mm] a23-1543 TANK SIZE 0428 0452 A B C D E F G H J K 3175 4553 2997 4381 1327 1429 730 826 365 413 946 1029 1935 2191 1203 1302 1038 1137 852 951 TANK SIZE 0428 0452 L M N P R S T U V W 1032 1130 89 86 1451 2124 505 527 619 625 1143 1225 1530 1537 737 742 860 867 756 762 LEFT SIDE VIEW Fig. 30 — Optional Pumpout Unit and Storage Tank 51 RATED DRY WEIGHT AND REFRIGERANT CAPACITY ENGLISH (lb) TANK SIZE TANK OD (in.) 0428 0452 24.00 27.25 DRY WEIGHT* (lb) 2334 3414 R-134a MAXIMUM REFRIGERANT CAPACITY (lb) ANSI/ASHRAE 15 UL 1963 1860 3563 1716 3286 SI (kg) TANK SIZE TANK OD (mm) 0428 0452 610 692 DRY WEIGHT* (kg) 1059 1549 R-134a MAXIMUM REFRIGERANT CAPACITY (kg) ANSI/ASHRAE 15 UL 1963 844 1616 778 1491 LEGEND ANSI — American National Standard Institute ASHRAE — American Society of Heating, Refrigeration, and Air Conditioning Engineers OD — Outside Diameter UL — Underwriters Laboratories *The above dry weight includes the pumpout condensing unit weight of 164 lb (75 kg). COOLER INLET ISOLATION VALVE 11 COOLER REFRIGERANT PUMPOUT VALVE 7 COOLER CHARGING VALVE 1b COOLER CONDENSER CHARGING VALVE 1a CONTROL CENTER SHIPPING BRACE (REMOVE PRIOR TO START-UP) DISCHARGE ISOLATION VALVE (OPTIONAL) PRESSURE RELIEF SAFETY VALVE 10 PUMPOUT COMPRESSOR = SERVICE VALVE ON CHILLER (FIELD SUPPLIED) = MAINTAIN AT LEAST 2 FT (610mm) CLEARANCE AROUND STORAGE TANK FOR SERVICE AND OPERATION WORK. = SERVICE VALVE ON PUMPOUT UNIT a23-1634 STORAGE TANK LIQUID VALVE OIL SEPARATOR PUMPOUT CONDENSER 2 3 4 5 PUMPOUT CONDENSER WATER SUPPLY AND RETURN 6 STORAGE TANK VAPOR VALVE Fig. 31 — Optional Pumpout System Piping Schematic with Storage Tank (Configured to Push Liquid into Storage Tank) 52 COOLER INLET ISOLATION VALVE 11 COOLER REFRIGERANT PUMPOUT VALVE 7 COOLER CHARGING VALVE 1b COOLER USE CONDENSER CHARGING VALVE TO ADD CHARGE 1a CONTROL CENTER DISCHARGE ISOLATION VALVE (OPTIONAL) SHIPPING BRACE (REMOVE PRIOR TO START-UP) PRESSURE RELIEF SAFETY VALVE 10 PUMPOUT COMPRESSOR = SERVICE VALVE ON CHILLER (FIELD SUPPLIED) = MAINTAIN AT LEAST 2 FT (610mm) CLEARANCE AROUND STORAGE TANK FOR SERVICE AND OPERATION WORK. = SERVICE VALVE ON PUMPOUT UNIT a23-1637 STORAGE TANK LIQUID VALVE OIL SEPARATOR PUMPOUT CONDENSER 2 3 4 5 PUMPOUT CONDENSER WATER SUPPLY AND RETURN 6 STORAGE TANK VAPOR VALVE Fig. 32 — Optional Pumpout System Piping Schematic with Storage Tank (Configured to Pull Vapor out of Chiller or to Charge Chiller from Storage Tank) COOLER INLET ISOLATION VALVE 11 COOLER REFRIGERANT PUMPOUT VALVE 7 COOLER CHARGING VALVE 1b COOLER CONDENSER CHARGING VALVE 1a CONTROL CENTER SHIPPING BRACE (REMOVE PRIOR TO START-UP) DISCHARGE ISOLATION VALVE (OPTIONAL) PRESSURE RELIEF SAFETY VALVE 1a SERVICE VALVE OIL SEPARATOR = SERVICE VALVE ON PUMPOUT UNIT = SERVICE VALVE ON CHILLER PUMPOUT CONDENSER PUMPOUT COMPRESSOR a23-1638 2 3 4 5 PUMPOUT CONDENSER WATER SUPPLY AND RETURN Fig. 33 — Optional Pumpout System Piping Schematic without Storage Tank (Configured to Store Refrigerant in Cooler or Condenser) 53 Table 9A — HFC-134a Pressure — Temperature (F) TEMPERATURE, F 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120 122 124 126 128 130 132 134 136 138 140 Table 9B — HFC-134a Pressure — Temperature (C) PRESSURE (psig) 6.50 7.52 8.60 9.66 10.79 11.96 13.17 14.42 15.72 17.06 18.45 19.88 21.37 22.90 24.48 26.11 27.80 29.53 31.32 33.17 35.08 37.04 39.06 41.14 43.28 45.48 47.74 50.07 52.47 54.93 57.46 60.06 62.73 65.47 68.29 71.18 74.14 77.18 80.30 83.49 86.17 90.13 93.57 97.09 100.70 104.40 108.18 112.06 116.02 120.08 124.23 128.47 132.81 137.25 141.79 146.43 151.17 156.01 160.96 166.01 171.17 176.45 181.83 187.32 192.93 198.66 204.50 210.47 216.55 222.76 229.09 TEMPERATURE, C -18.0 -16.7 -15.6 -14.4 -13.3 -12.2 -11.1 -10.0 -8.9 -7.8 -6.7 -5.6 -4.4 -3.3 -2.2 -1.1 0.0 1.1 2.2 3.3 4.4 5.0 5.6 6.1 6.7 7.2 7.8 8.3 8.9 9.4 10.0 11.1 12.2 13.3 14.4 15.6 16.7 17.8 18.9 20.0 21.1 22.2 23.3 24.4 25.6 26.7 27.8 28.9 30.0 31.1 32.2 33.3 34.4 35.6 36.7 37.8 38.9 40.0 41.1 42.2 43.3 44.4 45.6 46.7 47.8 48.9 50.0 51.1 52.2 53.3 54.4 55.6 56.7 57.8 58.9 60.0 54 PRESSURE (kPa) 44.8 51.9 59.3 66.6 74.4 82.5 90.8 99.4 108.0 118.0 127.0 137.0 147.0 158.0 169.0 180.0 192.0 204.0 216.0 229.0 242.0 248.0 255.0 261.0 269.0 276.0 284.0 290.0 298.0 305.0 314.0 329.0 345.0 362.0 379.0 396.0 414.0 433.0 451.0 471.0 491.0 511.0 532.0 554.0 576.0 598.0 621.0 645.0 669.0 694.0 720.0 746.0 773.0 800.0 828.0 857.0 886.0 916.0 946.0 978.0 1010.0 1042.0 1076.0 1110.0 1145.0 1180.0 1217.0 1254.0 1292.0 1330.0 1370.0 1410.0 1451.0 1493.0 1536.0 1580.0 8. If the reading continues to change after several attempts, perform a leak test up to the maximum 160 psig (1103 kPa) pressure. Locate and repair the leak, and repeat dehydration. Chiller Dehydration — Dehydration is recommended if the chiller has been open for a considerable period of time, if the chiller is known to contain moisture, or if there has been a complete loss of chiller holding charge or refrigerant pressure. Inspect Liquid Piping — Refer to piping diagrams provided in the certified drawings and the piping instructions in the 23XRV Installation Instructions manual. Inspect the piping to the cooler and condenser. Be sure that the flow directions are correct and that all piping specifications have been met. Piping systems must be properly vented with no stress on waterbox nozzles and covers. Liquid flows through the cooler and condenser must meet job requirements. Measure the pressure drop across the cooler and the condenser. Do not start or megohm-test the compressor motor, even for a rotation check, if the chiller is under dehydration vacuum. Insulation breakdown and severe damage may result. Dehydration can be done at room temperatures. Using a cold trap (Fig. 34) may substantially reduce the time required to complete the dehydration. The higher the room temperature, the faster dehydration takes place. At low room temperatures, a very deep vacuum is required to boil off any moisture. If low ambient temperatures are involved, contact a qualified service representative for the dehydration techniques required. Perform dehydration as follows: 1. Disconnect power from the VFD before placing the chiller under a vacuum. 2. Connect a high capacity vacuum pump (5 cfm [.002 m3/s] or larger is recommended) to the cooler or condenser charging valve (Fig. 2 and 3). Tubing from the pump to the chiller should be as short in length and as large in diameter as possible to provide least resistance to gas flow. 3. Use an absolute pressure manometer or a wet bulb vacuum indicator to measure the vacuum. Open the shutoff valve to the vacuum indicator only when taking a reading. Leave the valve open for 3 minutes to allow the indicator vacuum to equalize with the chiller vacuum. 4. If the entire chiller is to be dehydrated, open all isolation valves (if present). 5. With the chiller ambient temperature at 60 F (15.6 C) or higher, operate the vacuum pump until the manometer reads 29.8 in. Hg vacuum, referenced to 30 inches of mercury barometric pressure (0.1 psia) (–100.6 kPa) or a vacuum indicator reads 35 F (1.7 C). Operate the pump an additional 2 hours. Do not apply a greater vacuum than 29.82 in. Hg vac (757.4 mm Hg) or go below 33 F (.56 C) on the wet bulb vacuum indicator. At this temperature and pressure, isolated pockets of moisture can turn into ice. The slow rate of evaporation (sublimation) of ice at these low temperatures and pressures greatly increases dehydration time. 6. Valve off the vacuum pump, stop the pump, and record the instrument reading. 7. After a 2-hour wait, take another instrument reading. If the reading has not changed, dehydration is complete. If the reading indicates vacuum loss, repeat Steps 4 and 5. Liquid must be clean and treated to ensure proper chiller performance and to reduce the potential of tube damage due to corrosion, scaling, or erosion. Carrier assumes no responsibility for chiller damage resulting from untreated or improperly treated cooler or condenser liquid. Check Optional Pumpout Compressor Liquid Piping — If the optional pumpout storage tank and/or pumpout system are installed, check to ensure the pumpout condenser liquid has been piped in. Check for field-supplied shutoff valves and controls as specified in the job data. Check for refrigerant leaks on field-installed piping. See Fig. 30-33. Check Relief Valves — Be sure the relief valves have been piped to the outdoors in compliance with the latest edition of ANSI/ASHRAE Standard 15 and applicable local safety codes. Piping connections must allow for access to the valve mechanism for periodic inspection and leak testing. The 23XRV relief valves are set to relieve at the 185 psig (1276 kPa) chiller design pressure. Identify the VFD — The LiquiFlo™ 2.0 AC drive is a PWM (Pulse Width Modulated), liquid-cooled drive that provides vector and general purpose regulation for a wide range of applications. Identify the drive from the Drive Part Number on the drive’s nameplate and the model number matrix in Fig. 35 and 36. a23-1553 a19-661 Fig. 34 — Dehydration Cold Trap Fig. 35 — VFD Nameplate 55 LF20 0608CC R LF20 = LiquiFlo 2.0 Continuous Ampere Rating and Frame Size Coolant Method R = Refrigerant R134a a23-1629 Fig. 36 — Identifying the Drive Model Number The control center is designed to operate in the following environmental conditions: DC bus capacitors retain hazardous voltage after input power has been disconnected. After disconnecting input power, wait 5 minutes for the DC bus capacitors to discharge and then check the voltage with a voltmeter to ensure the DC capacitors are completely discharged before touching any internal components. Failure to observe this precaution could result in severe bodily injury or loss of life. CONDITION SPECIFICATION Ambient Temperature (outside NEMA 1 enclosure) 32 to 122 F (0° to 50 C) Storage Temperature (ambient) -40 to 149 F (-40 to 65 C) Humidity 5% to 95% (non-condensing) IDENTIFYING THE DRIVE BY PART NUMBER — Each AC drive can be identified by its assembly number. See Fig. 36. This number appears on the shipping label and on the drive’s nameplate. LiquiFlo 2.0 AC drives comprise an input components section and a power module section. Each LiquiFlo™ 2.0 AC power module can be identified by its model number. See Fig. 36. This number appears on the shipping label and on the power module’s nameplate. Power ratings are provided in Table 10. The drive can operate at and maintain zero speed. The user is responsible for assuring safe conditions for operating personnel by providing suitable guards, audible or visual alarms, or other devices to indicate that the drive is operating or may operate at zero speed. Failure to observe this precaution could result in severe bodily injury or loss of life. The drive contains ESD (Electrostatic Discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing, or repairing the drive. Erratic machine operation and damage to, or destruction of equipment can result if this procedure is not followed. Table 10 — Drive Assembly and Power Module Ratings PART NUMBER FRAME SIZE 23XRA2AA___________ AA 23XRA2BA___________ BA 23XRA2BB___________ BB 23XRA2CC___________ CC MAX OUTPUT CURRENT* AT 4 kHz (AMPS) ENCLOSURE RATING NAMEPLATE INPUT VOLTAGE (V) MAX INPUT CURRENT (AMPS) 440 442 NEMA 1 380, 400, 416, 460 ±10% 520 442 520 520 608 608 *110% output current capability for 1 minute. 150% output current capability for 5 sec. 56 9. Check that the incoming power is within ± 10% of chiller nameplate voltage. 10. All wiring should be installed in conformance with the applicable local, national, and international codes (for example, NEC/CEC). Verify that a properly sized ground wire is installed and a suitable earth ground is used. Check for and eliminate any grounds between the power leads. Verify that all ground leads are unbroken. Check Control Center BE AWARE that certain automatic start arrangements can engage the VFD. Open the disconnect ahead of the control center in addition to shutting off the chiller or pump. Inspect Wiring The main disconnect on the control center may not deenergize all internal circuits. Open all internal and remote disconnects before servicing the starter. Do not check the voltage supply without proper equipment and precautions. Serious injury may result. Follow power company recommendations. Input Power Wiring — All wiring should be installed in conformance with applicable local, national, and international codes. Use grommets, when hubs are not provided, to guard against wire chafing. Use the following steps to connect AC input power to the main input circuit breaker and ground leads to the ground lug. 1. Turn off, lockout, and tag the input power to the drive. 2. Remove the input power wiring panel from the top of the control center and drill the required number of openings in the input power wiring panel. Take care that metal chips do not enter the VFD enclosure. 3. Wire the AC input power leads and ground leads by routing them through the opening in the top of the control center to the main input circuit breaker. Do not apply any kind of test voltage, even for a rotation check, if the chiller is under a dehydration vacuum. Insulation breakdown and serious damage may result. 1. Examine the wiring for conformance to the job wiring diagrams and all applicable electrical codes. Confirm that there is at least a 6 in. clearance surrounding the control center louvers. Use an inspection mirror to visually inspect the top of the power module to confirm that no debris has fallen inside of it. 2. Connect a voltmeter across the power wires to the VFD and measure the phase to phase and phase to ground voltage. Compare this reading to the voltage rating on the compressor and starter nameplates. 3. Compare the ampere ratings on the Machine Electrical Data Nameplate. LOCKED ROTOR AMPS should be equal to RATED LINE AMPS. OVERLOAD TRIP AMPS should be equal to 1.08 X RATED LINE AMPS. 4. The control center must be wired to components and terminals required for PIC III refrigeration control. Check line side power and for control components shown on the Certified Prints. The control center must share control of cooler and condenser liquid pumps and cooling tower fans. 5. Check the phase to phase and phase to ground line voltage to the optional pumpout compressor. Compare voltages against nameplate values. Refer to Fig. 37. 6. Ensure that fused disconnects or circuit breakers have been supplied to the control center and optional pumpout unit. 7. Ensure all electrical equipment and controls are properly grounded in accordance with the job drawings, certified drawings, and all applicable electrical codes. 8. Ensure the customer's contractor has verified proper operation of the pumps, cooling tower fans, and associated auxiliary equipment. This includes ensuring motors are properly lubricated and have proper electrical supply and proper rotation. 9. Tighten all wiring connections on the high and low voltage terminal blocks in the control center enclosure above and below the control panel. 10. Inspect the control panel in the control center enclosure to ensure that the contractor has used the knockouts to feed the wires into the back of the control panel. Wiring through the top of the control center can cause debris to fall into the power module. Clean and inspect the interior of the control center if this has occurred. Contact Carrier Service before applying power if debris may have fallen inside of the power module. Do not route control wiring carrying 30 v or less within a conduit carrying 50 v or higher. Failure to observe this precaution could result in electromagnetic interference in the control wiring. 4. Connect the three-phase AC input power leads (per job specification) to the appropriate input terminals of the circuit breaker. 5. Tighten the AC input power terminals and lugs to the proper torque as specified on the input circuit breaker. 6. Connect and tighten the ground leads to the ground lug. Checking the Installation — Use the following instructions to verify the condition of the installation: 1. Turn off, lockout, and tag the input power to the drive. Wait a minimum of 5 minutes for the DC bus to discharge. 2. Verify that there is no voltage at the input terminals (L1, L2 and L3) of the power module or main circuit breaker. 3. Verify that the status LEDs on the DPI Communications Interface Board are not lit. The location of the DPI Communications Interface Board is shown in Fig. 13. 4. Remove any debris, such as metal shavings, from the enclosure. 5. Check that there is adequate clearance around the machine. 6. Verify that the wiring to the terminal strip and the AC input power terminals is correct. Verify that all of the VFD power module circuit board connectors are fully engaged and secured in place. 7. Check that the wire size is within terminal specifications and that the wires are tightened properly. 8. Check that specified branch circuit protection is installed and correctly rated. 57 b. Divide the 60-second resistance reading by the 10-second reading. The ratio, or polarization index, must be one or higher. Both the 10 and 60-second readings must be at least 50 megohms. c. If the readings are unsatisfactory, repeat the test with the motor leads disconnected from the motor. Satisfactory readings in this second test indicate the fault is in the power leads. Carrier Comfort Network® Interface — The Carrier Comfort Network (CCN) communication bus wiring is supplied and installed by the electrical contractor. It consists of shielded, 3-conductor cable with drain wire. The system elements are connected to the communication bus in a daisy chain arrangement. The positive pin of each system element communication connector must be wired to the positive pins of the system element on either side of it. The negative pins must be wired to the negative pins. The signal ground pins must be wired to the signal ground pins. See the 23XRV Installation Instructions. NOTE: Conductors and drain wire must be 20 AWG (American Wire Gage) minimum stranded, tinned copper. Individual conductors must be insulated with PVC, PVC/nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of –4 F to 140 F (–20 C to 60 C) is required. See table below for cables that meet the requirements. MANUFACTURER Alpha American Belden Columbia CABLE NO. 2413 or 5463 A22503 8772 02525 When connecting the CCN communication bus to a system element, a color code system for the entire network is recommended to simplify installation and checkout. The following color code is recommended: a23-1555 Fig. 37 — Machine Electrical Data Nameplate SIGNAL TYPE Do not apply power unless a qualified Carrier technician is present. Electrical shock could cause serious personal injury or death. 11. Apply power to the control center. Go to the ICVC and access the MENU>SERVICE>VFD CONFIG DATA>VFD_CONF screen. Confirm that the parameters entered in VFD_CONF match the information on the Machine Nameplate and Sales Requisition. Confirm that the serial numbers on the chiller, Machine Nameplate, and Sales Requisition are consistent. CCN BUS CONDUCTOR INSULATION COLOR ICVC PLUG J1 PIN NO. + Red 1 Ground White or Clear 2 – Black 3 Power Up the Controls and Check the Oil Heater — Ensure that an oil level is visible in the oil sump before energizing the controls. A separate 15A Control Power Circuit Breaker in the control center energizes the oil heater and the control circuit. When first powered, the ICVC should display the default screen within a short period of time. The oil heater is energized when power is applied to the control circuit. This should be done several hours before startup to minimize oil-refrigerant migration. The oil heater is controlled by the PIC III and is powered through a contactor on the power panel. This arrangement allows the heater to energize when the main motor circuit breaker is off for service work or extended shutdowns. The oil heater relay status (OIL HEATER RELAY) can be viewed on the COMPRESS table on the ICVC. Oil sump temperature can be viewed on the ICVC default screen. SOFTWARE VERSION — The software part number is labeled on the backside of the ICVC module. The software version also appears on the ICVC CONFIGURATION screen as the last two digits of the software part number. Ground Fault Troubleshooting — Use this proce- dure only if ground faults are declared: Disconnect the motor leads from the control center before a motor insulation test is performed. The voltage generated from the testing equipment will damage the VFD. Test the compressor motor and its power lead insulation resistance with a 500 V insulation tester such as a megohmmeter. With the tester connected to the motor leads, take 10 second and 60 second megaohm readings as follows: a. Tie terminals 1, 2, and 3 together and test between the grouped motor terminals and ground. 58 TO CHANGE THE PASSWORD — The password may be changed from the ICVC CONFIGURATION screen. 1. Press the MENU and SERVICE softkeys. Enter the current password and highlight ICVC CONFIGURATION. Press the SELECT softkey. Only the last 6 entries on the ICVC CONFIG screen can be changed: BUS #, ADDRESS #, BAUD RATE, US IMP/METRIC, PASSWORD, and LID LANGUAGE. Software Configuration Do not operate the chiller before the control configurations have been checked in the ICVC and a Control Test has been satisfactorily completed. Protection by safety controls cannot be assumed until all control configurations have been confirmed. 2. Use the ENTER softkey to scroll to PASSWORD. The first digit of the password is highlighted on the screen. As the 23XRV unit is configured, all configuration settings should be written down. A log, such as the one shown on pages CL-1 to CL-11, provides a convenient list for configuration values. It is recommended that all control configuration tables be uploaded via service tool and stored for reference when the software configuration is complete. 3. To change the digit, press the INCREASE or DECREASE softkey. When the desired digit is seen, press the ENTER softkey. 4. The next digit is highlighted. Change it, and the third and fourth digits in the same way the first was changed. Input the Design Set Points — Access the ICVC SET POINT screen and view/modify the BASE DEMAND LIMIT set point, and either the LCL SET POINT or the ECL SET POINT. The PIC III can control a set point to either the leaving or entering chilled liquid. This control method is set in the EQUIPMENT SERVICE (TEMP_CTL) table. The default setting of ECL CONTROL OPTION is DSABLE so the PIC III will control the leaving chilled liquid temperature. 5. After the last password digit is changed, the ICVC goes to the LID LANGUAGE parameter. Press the EXIT softkey to leave that screen and return to the SERVICE menu. Input the Local Occupancy Schedule (OCCPC01S) — Access the schedule OCCPC01S screen Be sure to remember the password. Retain a copy for future reference. Without the password, access to the SERVICE menu will not be possible unless the ICVC_PWD menu on the STATUS screen is accessed by a Carrier representative. on the ICVC and set up the occupied time schedule according to the customer’s requirements. If no schedule is available, the default is factory set for 24 hours occupied, 7 days per week including holidays. For more information about how to set up a time schedule, see the Time Schedule Operation section, page 21. The CCN Occupied Schedule (OCCPC03S) should be configured if a CCN system is being installed or if a secondary time schedule is needed. NOTE: The default CCN Occupied Schedule OCCPC03S is configured to be unoccupied. TO CHANGE THE ICVC DISPLAY FROM ENGLISH TO METRIC UNITS — By default, the ICVC displays information in English units. To change to metric units, access the ICVC CONFIGURATION screen: 1. Press the MENU and SERVICE softkeys. Enter the password and highlight ICVC CONFIGURATION. Press the SELECT softkey. Input Service Configurations — The following configurations require the ICVC screen to be in the SERVICE portion of the menu. • CONTROL TEST • EQUIPMENT CONFIGURATION • VFD CONFIG DATA • EQUIPMENT SERVICE • TIME AND DATE • ICVC CONFIGURATION (PASSWORD) PASSWORD — When accessing the SERVICE tables, a password must be entered. All ICVC are initially set for a password of 1-1-1-1. INPUT TIME AND DATE — Access the TIME AND DATE table on the SERVICE menu. Input the present time of day, date, and day of the week. The HOLIDAY parameter should only be configured to YES if the present day is a holiday. NOTE: Because a schedule is integral to the chiller control sequence, the chiller will not start until the time and date have been set. CHANGE ICVC CONFIGURATION IF NECESSARY — From the SERVICE table, access the ICVC CONFIGURATION screen. From there, view or modify the ICVC CCN address, change to US Imperial (English) or Metric (SI) units, LID Language, and change the password. If there is more than one chiller at the jobsite, change the ICVC CCN address on each chiller so that each chiller has its own address. Note and record the new address. Change the screen to Metric (SI) units as required, and change the ICVC password if desired. 2. Use the ENTER softkey to scroll to US imp or METRIC. 3. Press the softkey that corresponds to the units desired for display on the ICVC (e.g., US imp or METRIC). MODIFY CONTROLLER IDENTIFICATION IF NECESSARY — The ICVC module address can be changed from the ICVC CONFIGURATION screen. Change this address for each chiller if there is more than one chiller at the jobsite. Write the new address on the ICVC module for future reference. INPUT EQUIPMENT SERVICE PARAMETERS IF NECESSARY — The EQUIPMENT SERVICE table has six service tables: 1. OPTIONS 2. SETUP1 3. SETUP2 4. LEADLAG 5. RAMP_DEM 6. TEMP_CTL Check VFD_CONFIG TABLE — Enter the VFD_CONF screen on the ICVC by entering the following screen sequence: • MENU • SERVICE • Password (default 1111) • VFD CONFIG DATA • Password (default 4444) • VFD_CONF 59 Confirm that the following parameters in the VFD_CONF screen match the values on the Machine Electrical Data Nameplate (see Fig. 37): • Motor Nameplate Voltage — Voltage required to run at motor rating. • Compressor 100% Speed — Compressor speed required to run at chiller design point. • Rated Line Voltage — Nominal line voltage selected for the job site. • Rated Line Amps — Line current required for the chiller to run at the design point. • Rated Line Kilowatts — Line power required for the chiller to run at the design point. • Motor Rated Load kW — Power consumed by the motor when running at the chiller design point. • Motor Rated Load Amps — Motor current required for the chiller to run at the design point. • Motor Nameplate Amps — Motor nameplate full load amps. • Motor Nameplate RPM — Rated speed of the motor when running at motor nameplate rated frequency, rated current, and rated voltage. • Motor Nameplate kW — Motor nameplate rated power. • Inverter PWM Frequency — Sets the carrier frequency for the pulse width modulation output. NOTE: Other parameters on these screens are normally left at the default settings; however, they may be changed by the operator as required. The voltage and current imbalance level and imbalance persistence time on the VFD_CONF table can be adjusted to increase or decrease the sensitivity of these fault conditions. Increasing time or persistence decreases sensitivity. Decreasing time or persistence increases sensitivity to the fault condition. Modify Minimum and Maximum Load Points (HGBP DELTA T1/ HGBP DELTA P1, HGBP DELTA T2/ HGBP DELTA P2) If Necessary — The default settings of the stall prevention parameters in the OPTIONS screen are set so the optional HGBP will not be energized during normal operating conditions. In addition to stall prevention, hot gas bypass may be useful for preventing excessive recycle restarts and maintaining temperature control in response to rapid load changes at low compressor speed. The chiller needs only to close the optional hot gas bypass valve to increase capacity when the chiller is running at low load with hot gas bypass active. It takes a few minutes for the chiller to start if it has shut down in recycle restart mode. When HGBP option is set to 1, hot gas bypass operation can be adjusted for minimum chiller load and lift control. The HGBP DELTA T1/HGBP DELTA P1, HGBP DELTA T2/ HGBP DELTA P2 parameters in the OPTIONS screen determine when the optional hot gas bypass valve will open and close. These points should be set based on individual chiller operating conditions. An example of such a configuration is shown below. Refrigerant: HCFC-134a Estimated Minimum Load Conditions: 44 F (6.7 C) LCL 45.5 F (7.5 C) ECL 43 F (6.1 C) Suction Temperature 70 F (21.1 C) Condensing Temperature Estimated Maximum Load Conditions: 44 F (6.7 C) LCL 54 F (12.2 C) ECL 42 F (5.6 C) Suction Temperature 98 F (36.7 C) Condensing Temperature Calculate Maximum Load — To calculate the minimum load points, use data from the sales requisition or estimate the chilled liquid delta T based on a percentage of full load where the HGBP should be energized. The minimum condensing pressure can be based on the entering condenser liquid temperature available at minimum load. Use the proper saturated pressure and temperature for R-134a. Suction Temperature: 43 F (6.1 C) = 38 psig (262 kPa) saturated refrigerant pressure (R-134a) Condensing Temperature: 70 F (21.1 C) = 71 psig (490 kPa) saturated refrigerant pressure (R-134a) Minimum Load HGBP DELTA T1 (at 15% load): 0.15 X (54-44) = 1.5º F (0.15 X (12.2 – 6.7) = 0.8º C Minimum Load HGBP DELTA P1: 71 – 38 = 33 psid (490 – 262 = 228 kPad) Determine HGBP DELTA T2/HGBP DELTA P1: Set HGBP DELTA T2 equal to 0.1º F larger than HGBP DELTA T1: HGBP DELTA T2 = HGBP DELTA T1 + 0.1 = 1.6º F (0.8 + 0.06 = 0.9º C) Set HGBP DELTA P2 to a large value to create a steep slope (see Fig. 22 and 23) HGBP DELTA P2 = 200 psid (1379 kPa). If the hot gas bypass is energized too soon or too late: HGBP ENERGIZED TOO SOON Decrease HGBP DELTA T1 and HGBP DELTA T2 by 0.5° F (0.3° C) HGBP ENERGIZED TOO LATE Increase HGBP DETLA T1 and HGBP DELTA T2 by 0.5° F (0.3° C) If variable evaporator flow is applied, changes to DELTA T1 proportional to the reduction in evaporator liquid flow rate are required. The differential pressure (ΔP) and temperature (ΔT) can be monitored during chiller operation by viewing ACTIVE DELTA P and ACTIVE DELTA T (HEAT_EX screen). Comparing HGBP DELTA T to ACTIVE DELTA T will determine when the HGBP valve will open. The smaller the difference between the HGBP DELTA T and the ACTIVE DELTA T values, the closer to stall prevention or the point at which the HGBP will open. If the ACTIVE DELTA T is less than the HGBP DELTA T, the HGBP valve will be activated. The HGBP will be deactivated once the ACTIVE DELTA T is greater than the HGBP DELTA T plus the HGBP DEADBAND if the ACTIVE DELTA P is less than HGBP DELTA P1. When the HGBP option is set to 2, HGBP on DELTA T should be based on the estimated minimum load conditions as was HGBP DELTA T1 in the example above. HGBP OFF DELTA T functions similar to a deadband above the temperature entered in HGBP ON DELTA T as shown in Fig. 23. MODIFY EQUIPMENT CONFIGURATION IF NECESSARY — The EQUIPMENT SERVICE table has screens to select, view, or modify parameters. Carrier’s certified drawings have the configuration values required for the jobsite. Modify these values only if requested. SERVICE Screen Modifications — Change the values on these screens according to specific job data. See the certified drawings for the correct values. Modifications can include: • Chilled liquid reset • Entering chilled liquid control (Enable/Disable) • 4 to 20 mA demand limit • Auto restart option (Enable/Disable) • Remote contact option (Enable/Disable) Owner-Modified CCN Tables — The following EQUIPMENT CONFIGURATION screens are described for reference only. 60 OCCDEFCS — The OCCDEFCS screen contains the Local and CCN time schedules, which can be modified here or on the SCHEDULE screen as described previously. HOLIDAYS — From the HOLIDAYS screen, the days of the year that holidays are in effect can be configured. See the holiday paragraphs in the Controls section for more details. BRODEF — The BRODEF screen defines the start and end of daylight savings time. By default this feature is enabled. Enter the dates for the start and end of daylight savings if required for your location. Note that for DAY OF WEEK, 1 represents Monday. START WEEK and STOP WEEK refer to the instance of the selected DAY OF WEEK during the selected START MONTH and year. To disable the feature, change START ADVANCE and STOP BACK times to 0 (minutes). In the BRODEF table the user may also identify a chiller as the time broadcaster for a CCN network with TIME BROADCAST ENABLE. There should be only one device on a CCN network which is designated as the time broadcaster. ALARM ROUTING (Fig. 38) — ALARM ROUTING is in the table SERVICE/EQUIPMENT CONFIGURATION/ NET_OPT under the heading Alarm Configuration. ALARM ROUTING consists of an 8-bit binary number. Only bits 1, 2, and 4 (counting from the left) are used. The bits can be set by any device which can access and change configuration tables. If any of these 3 bits is set to 1, the ICVC will broadcast any alarms which occur. Bit 1: Indicates that the alarm should be read and processed by a front end device, such as a ComfortWORKS® device. Bit 2: Indicates that the alarm should be read and processed by a TeLINK or Autodial Gateway module. Bit 4: Indicates that the alarm should be read and processed by an alarm printer interface (an optional module), ServiceLink, or a DataLINK™ device. The RE-ALARM TIME is a time period after which, if a preexisting and previously broadcast alarm has not been cleared, it will be rebroadcast on the CCN network. Other Tables — The CONSUME, NET_OPT, and RUNTIME screens contain parameters used with a CCN system. See the applicable CCN manual for more information on these screens. These tables can only be defined from a CCN Building Supervisor. Perform a Control Test — Check the safety controls status by performing an automated control test. Access the CONTROL TEST table and select a test to be performed function (see Tables 11 and 12). The Automated Control Test checks all outputs and inputs for function. The compressor must be in the OFF mode to operate the controls test. The compressor can be put in OFF mode by pressing the STOP push-button on the ICVC. Each test asks the operator to confirm the operation is occurring and whether or not to continue. If an error occurs, the operator can try to address the problem as the test is being done or note the problem and proceed to the next test. When the control test is finished or the EXIT softkey is pressed, the test stops, and the CONTROL TEST menu displays. If a specific automated test procedure is not completed, access the particular control test to test the function when ready. The CONTROL TEST menu is described in Table 11. Table 11 — Control Tests CCM Thermistors Check of all thermistors. CCM Pressure Check of all transducers. Transducers Checks operation of pump outputs; pumps are activated. Pumps Also tests associated inputs such as flow or pressure. Discrete Outputs Activation of all on/off outputs individually. Oil Reclaim Checks CCM 4-20mA oil reclaim output with Output power removed from oil reclaim actuator. Head Pressure Manually varies the head pressure output Output from low voltage field wiring terminal strip. Pumpdown prevents the low refrigerant alarm during Pumpdown/ evacuation so refrigerant can be removed form the unit. Lockout Also locks the compressor off and starts the liquid pumps. Terminate To charge refrigerant and enable the chiller Lockout to run after pumpdown lockout. NOTE: During any of the tests, an out-of-range reading will have an asterisk (*) next to the reading and a message will be displayed. The EVAPORATOR PRESSURE, CONDENSER PRESSURE, DISCHARGE PRESSURE, and OIL PRESSURE DELTA P pressure transducers should be calibrated prior to start-up. If pressure transducers are installed on the waterbox nozzles, CHILLED LIQUID DELTA P and CONDENSER LIQUID DELTA P transducers should also be calibrated. Pressure Transducer and Optional Flow Device Calibration — Transducers measuring single ALARM CONTROL ALARM ROUTING pressure values (such as CONDENSER PRESSURE and EVAPORATOR PRESSURE) are calibrated individually, while a pair of transducers measuring a pressure differential (OIL PRESSURE DELTA P, CHILLED LIQUID DELTA P, or CONDENSER LIQUID DELTA P) are calibrated together as a differential. Transducers for sensing liquid side flow are not provided as standard. Oil pressure, refrigerant pressure and liquid delta P readings can be viewed and calibrated from the COMPRESS and HEAT_EX screens on the ICVC controller. Each transducer or transducer pair can be calibrated at two points: “zero” (0 psig or 0 kPa) and “high end” (between 25 and 250 psig, or between 173 and 1724 kPa). It is good practice to calibrate at initial start-up. Calibration is particularly important at high altitudes to ensure the proper refrigerant temperature-pressure relationship. ZERO POINT CALIBRATION — Shut down the compressor, and cooler and condenser pumps. There must be no water flow through the heat exchangers, but these systems must be filled. For differential pairs, leave the transducers installed. For single value transducers, disconnect the transducer’s electrical cable, remove the sensor from its Schrader fitting, then reconnect the cable. NOTE: If the cooler or condenser vessels are at 0 psig (0 kPa) or are open to atmospheric pressure, the transducers can be calibrated for the zero point without removal. Alarm routing settings should be left at default settings and only be changed by technicians trained in CCN. These settings determine which CCN system elements will receive and process alarms sent by the ICVC. Input for the decision consists of eight digits, each of which can be set to either 0 or 1. Setting a digit to 1 specifies that alarms will be sent to the system element that corresponds to that digit. Setting all digits to 0 disables alarm processing. Digits in this decision correspond to CCN system elements in the following manner: Alarm Printer Interface Module Autodail Gateway Local Building Supervisors(s) or ComfortWORKS 1 1 0 1 0 0 a23-1627 0 0 unused NOTE: If your CCN does not contain ComfortWORKS® controls or a Building Supervisor, Autodial Gateway, or APIM to serve as an alarm acknowledger, set all digits in this decision to 0 in order to prevent unnecessary activity on the CCN Communication Bus. Allowable Entries 00000000 to 11111111 0 = Disabled, 1 = Enabled Default Value 10000000 Fig. 38 — Alarm Control and Alarm Routing 61 Access the HEAT_EX or COMPRESS screen under the STATUS menu, and view the particular transducer reading (OIL PRESSURE DELTA P is in the COMPRESS screen; all others are in the HEAT_EX screen). If the displayed reading is not 0 psi (0 kPa), press the SELECT key to highlight the associated line in the display, then the ENTER key. (For zero point calibration, the INCREASE and DECREASE keys have no effect.) The value should change to 0.0. If the ICVC fails to accept the zero point calibration, the value will not change to 0.0 and the display will show “Higher Force In Effect”. This indicates that the sensor voltage is out of the acceptable range. For each single value transducer there are 3 terminals at the CCM: 0 vdc (low) connected to the black wire, “sensor” voltage connected to the white or clear wire, and 5.00 vdc (high) connected to the red wire. With a base supply voltage of 5.00 volts, the acceptable range of voltage taken between the low (black wire) and sensor terminals (white or clear wire) for zero point calibration is 0.40 to 0.55 v. For each transducer differential pair there are two 3-terminal sets at the CCM. With a base supply voltage of 5.00 volts, the acceptable range of voltage taken between the sensor terminal (white or clear wire) for the higher pressure transducer (liquid inlet or oil pump discharge) and the sensor terminal (white or clear wire) for the lower pressure transducer (liquid outlet or oil sump) for zero point calibration is -0.065 to +0.085 v. If this occurs with a differential pair, one possible remedy is to swap the high end (e.g., inlet) and low end (e.g., outlet) transducers. In most cases this puts the voltage difference of the sensor pair within the acceptable range. HIGH END CALIBRATION — High end calibration can be performed between 25 and 250 psig (173 and 1724 kPa), comparing the pressure readings in the ICVC display to an accurate refrigeration gage. High end calibration may improve transducer accuracy over the full pressure range. High end calibration is not recommended for transducer differential pairs. Pressure can be provided by attaching a regulated 250 psig (1724 kPa) pressure source, such as from a nitrogen cylinder, to the transducer. It is good practice to perform the high end calibration near a pressure that the sensor will typically be exposed to. Access the HEAT_EX screen under the STATUS menu, and the CONDENSER PRESSURE or EVAPORATOR PRESSURE to the reference pressure gage. To change the displayed reading, press the SELECT key to highlight the associated line in the display, then the INCREASE or DECREASE key to set the new value, then the ENTER key. Generally, the value can be changed to any value within ±15% of a nominal value. NOTE: Prior calibrations may have shifted the present precalibration value from the center of this range. In this case, the limit of acceptable new values will be less than 15% in one direction. If the ICVC fails to accept the high end calibration, the value will not change and the display will show “Higher Force In Effect”. This indicates that the sensor voltage is out of the acceptable range for the entered value. In this case, the pressure transducer may need to be replaced. Each pressure transducer is supplied with 5 vdc power from the CCM through the red wire. Pressure transducer readings are derived from voltage ratio, not absolute voltage, which compensates for any reference voltage variation. If this power supply fails, a transducer voltage reference alarm (239) is generated. If transducer readings are suspected of being faulty, check the supply voltage, measured between the high and low (red wire and black wire) terminals of any transducer 3 terminal connection at the CCM. This is also displayed in CONTROL TEST under PRESSURE TRANSDUCERS. Check Optional Pumpout System Controls and Compressor — Controls include an on/off switch, a 0.5-amp fuse for the secondary side of the transformer, 0.25 amp fuses for the primary side of the transformer, the compressor overloads, an internal thermostat, a compressor contactor, refrigerant low pressure cut-out and a refrigerant high pressure cutout. The high pressure cutout is factory set to open at 185 psig (1276 kPa) and reset at 140 psig (965 kPa). The low pressure cutout is factory set to open at 7 psia (–15.7 in. HG) and close at 9 psia (–11.6 in. HG). Ensure the watercooled condenser has been connected. Ensure oil is visible in the compressor sight glass. Add oil if necessary. See the Pumpout and Refrigerant Transfer Procedures and Optional Pumpout System Maintenance sections, pages 69 and 78, for details on the transfer of refrigerant, oil specifications, etc. High Altitude Locations — Because the chiller is initially calibrated at sea level, it is necessary to recalibrate the pressure transducers if the chiller has been moved to a high altitude location. See the calibration procedure in the Troubleshooting Guide section. Table 12 — Control Test Menu Functions TESTS TO BE PERFORMED 1. Thermistors 2. Pressure Transducers 3. Pumps 4. Discrete Outputs 5. Oil Reclaim Output 6. Head Pressure Output 7. Pumpdown Lockout 8. Terminate Lockout 62 DEVICES TESTED Entering Chilled Liquid Leaving Chilled Liquid Entering Cond Liquid Leaving Cond Liquid Evap Refrig Liquid Temp Comp Discharge Temp Oil Sump Temp Vaporizer Temp Comp Motor Winding Temp Spare Temperature 1 Spare Temperature 2 Remote Reset Sensor Evaporator Pressure Condenser Pressure Discharge Pressure Oil Pressure Delta P Chilled Liquid Delta P Condenser Liquid Delta P Transducer Voltage Ref Humidity Sensor Input Relative Humidity Operates Pump, Displays Delta P and confirms flow for oil pump, chilled liquid pump and condenser liquid pump. Oil Heater Relay Vaporizer Heater Hot Gas Bypass Relay Tower Fan Relay Low Tower Fan Relay High Alarm Relay VFD Coolant Solenoid Shunt Trip Relay Percentage and mA (% and mA) Head Pressure Reference (4-20mA) (The output is 2 mA when the chiller is not running.) When using pumpdown/lockout, observe freeze up precautions when removing charge: Instructs operator which valves to close and when. Starts chilled liquid and condenser liquid pumps and requests flow confirmation. Monitors Evaporator pressure Condenser pressure Evaporator temperature during pumpout procedures Turns pumps off after pumpdown. Locks out compressor. Starts pumps and monitors flows. Instructs operator which valves to open and when. Monitors Evaporator pressure Condenser pressure Evaporator temperature during charging process Terminates compressor lockout. • Oil Pump Isolation Valve • Oil Pressure Regulator Valve Refer to Fig. 2 and 8 for isolation valve locations. Charge Refrigerant into Chiller The transfer, addition, or removal of refrigerant in spring isolated chillers may place severe stress on external piping if springs have not been blocked in both up and down directions. Failure to block springs in both up and down directions could result in severe personal injury and equipment damage. Whenever turning the discharge isolation valve, be sure that the spring-loaded lever lock fully engages within one of the latch plate detents. This will prevent the valve from opening or closing during service work or during chiller operation. CHILLER EQUALIZATION WITH PUMPOUT UNIT — The following steps describe how to equalize refrigerant pressure on an isolated 23XRV chiller using the pumpout unit. NOTE: The top valve tee on a unit mounted pumpout is connected to the condenser and the bottom valve tee is connected to the cooler. This is different from unit mounted installations on other Carrier chillers. 1. Access the TERMINATE LOCKOUT function on the CONTROL TEST screen. 2. IMPORTANT: Turn on the chilled liquid and condenser liquid pumps to prevent possible freezing. Always operate the condenser and chilled liquid pumps during charging operations to prevent freeze-ups. Damage may result to equipment if the condenser and chilled water pumps are not operated during pumpdown or charging. The standard 23XRV chiller is shipped with the refrigerant already charged in the vessels. However, the 23XRV may be ordered with a nitrogen holding charge of 15 psig (103 kPa). In this case, evacuate the nitrogen from the entire chiller, and charge the chiller from refrigerant cylinders. Chillers shipped with a factory charge should arrive with all isolation valves in the open position. Figures 2, 43, 44 and 45 show the location of the isolation valves listed in the Initial Start-Up Checklist. CHILLER EQUALIZATION WITHOUT A PUMPOUT UNIT 3. Refer to Fig. 33. Open valve 4 on the pumpout unit and open valves 1a and 1b on the chiller cooler and condenser, Fig. 30-33. Slowly open valve 2 on the pumpout unit to equalize the pressure. This process takes approximately 15 minutes. 4. Once the pressures have equalized, the following isolation valves should be opened: • Discharge Isolation Valve • Cooler Inlet Valve • Hot Gas Bypass Valve • Vaporizer Condenser Gas Valve • Oil Pump Valve • Oil Filter Valve • Oil Pressure Regulator Valve • Filter/Drier Valve (2 places) • VFD Cooling Inlet Valve • VFD Cooling Drain Valve Refer to pages 5, 6, 11 and 75 for isolation valve locations. When equalizing refrigerant pressure on the 23XRV chiller after service work or during the initial chiller start-up, do not use the discharge isolation valve to equalize. Either the motor cooling isolation valve or the charging hose (connected between the pumpout valves on top of the cooler and condenser) should be used as the equalization valve. To equalize the pressure differential on a refrigerant isolated 23XRV chiller, use the TERMINATE LOCKOUT function of the CONTROL TEST on the SERVICE menu. This helps to turn on pumps and advises the operator on proper procedures. The following steps describe how to equalize refrigerant pressure in an isolated 23XRV chiller without a pumpout unit. 1. Access TERMINATE LOCKOUT function on the CONTROL TEST screen. 2. IMPORTANT: Turn on the chilled liquid and condenser liquid pumps to prevent freezing. Whenever turning the discharge isolation valve, be sure that the spring-loaded lever lock fully engages within one of the latch plate detents. This will prevent the valve from opening or closing during service work or during chiller operation. The full refrigerant charge on the 23XRV will vary with chiller components and design conditions, as indicated on the job data specifications. An approximate charge may be determined by adding the condenser charge to the cooler charge as listed in Table 13. 3. Slowly open the motor cooling isolation valve. The chiller cooler and condenser pressures will gradually equalize. This process takes approximately 15 minutes. 4. Once the pressures have equalized, the following isolation valves should be opened: • Discharge Isolation Valve • Cooler Inlet Valve • HGBP Isolation Valve (optional) • Vaporizer Condenser Gas Valve • Filter/Drier Isolation Valve (2 places) • VFD Cooling Isolation Valves (2 places) • Oil Filter Isolation Valve Always operate the condenser and chilled liquid pumps whenever charging, transferring, or removing refrigerant from the chiller. 63 Table 13 — Refrigerant Charges FRAME SIZE COOLER LENGTH ft (m) 12 (3.6) 3 14 (4.3) 12 (3.6) 4 14 (4.3) 12 (3.6) 5 14 (4.3) COOLER CODE 30 31 32 35 36 37 40 41 42 45 46 47 50 51 52 55 56 57 CHARGE AMOUNT (R-134a) WITH ECONOMIZER WITHOUT ECONOMIZER lb (± 25 lb) kg (± 11 kg) lb (± 25 lb) kg (± 11 kg) 800 363 650 295 800 363 650 295 800 363 650 295 910 413 760 345 910 413 760 345 910 413 760 345 900 408 750 340 900 408 750 340 900 408 750 340 1015 460 865 392 1015 460 865 392 1015 460 865 392 1250 567 1100 499 1250 567 1100 499 1250 567 1100 499 1430 649 1280 581 1430 649 1280 581 1430 649 1280 581 The preferred location at which refrigerant should be added directly into the chiller is through the service valves on top of the cooler condenser. if these valves are not accessible due to presence of an attached pumpdown unit which does not have a storage tank, slowly add charge through the valve connected to the side of the condenser drain float sump. Adding charge through the cooler refrigerant pumpout valve at the base of the cooler (off the liquid line) may force debris into the condenser float valve and is not recommended. CHILLER SHIPPED WITH HOLDING CHARGE — Use the CONTROL TEST TERMINATE LOCKOUT function to monitor conditions and start the pumps. If the chiller has been shipped with a holding charge, the refrigerant is added through the refrigerant charging valve (Fig. 30-33, valves 1a and 1b) or to the pumpout charging connection. First evacuate the nitrogen holding charge from the chiller vessels. Charge the refrigerant as a gas until the system pressure exceeds 35 psig (141 kPa) for HFC-134a. After the chiller is beyond this pressure the refrigerant should be charged as a liquid until all the recommended refrigerant charge has been added. TRIMMING REFRIGERANT CHARGE — The 23XRV is shipped with the correct charge for the design duty of the chiller. The LTD (Leaving Temperature Difference) between the EVAP REFRIG LIQUID TEMP and LEAVING CHILLED LIQUID can be checked against the design conditions to confirm that the charge is correct. In the case where leaks have been found and corrected and the LTD is greater than about 4° F (2.2° C) above design, add refrigerant until the full load design LTD is approached. (A high cooler LTD can also be caused by dirty tubes, water box division plate bypass, a partially closed liquid isolation valve, or the float valve.) Trimming the charge can best be accomplished when the design load is available. The calibration of the EVAP REFRIG LIQUID TEMP and LEAVING CHILLED LIQUID temperature sensors should be confirmed prior to checking for proper cooler LTD. Compare the difference between EVAP REFRIG LIQUID TEMP and LEAVING CHILLED LIQUID temperatures to the chiller design conditions. Add or remove refrigerant, if necessary, to bring the cooler leaving temperature difference to design conditions or within minimum differential. Check for low load oil recovery after making adjustments to the refrigerant charge. The bubbling mixture of refrigerant and oil mixture should be visible through the vaporizer sight glass at low load when the oil reclaim valve is open. If a bubbling mixture is not observed when the oil reclaim valve is open, add refrigerant. INITIAL START-UP In order for the Reliance VFD to be eligible for the full warranty period, the following conditions must be met: 1. The chiller must be started by a technician that has completed Reliance LiquiFlo2 training. 2. The start-up technician must be registered with Reliance. 3. The start-up technician must register the chiller start-up on the Reliance web site. Preparation — Before starting the chiller, verify: 1. Power is on to the CB2 control power circuit breaker, oil pump relay, tower fan starter, oil heater relay, and the chiller control center. 2. The CB1 main control center circuit breaker is in the On position. 3. Cooling tower liquid is at proper level and at-or-below design entering temperature. Check cooling tower bypass valve. 4. Chiller is charged with refrigerant and all refrigerant and oil valves are in their proper operating positions. 5. Oil is at the proper level in the oil sump sight glass. 6. The Oil Sump Temperature must be above 140 F (60 C) or CALC EVAP SAT TEMP plus 15º F (8.3º C) before the controls will allow the chiller to start to ensure that a sufficient amount of refrigerant has been driven out of the oil. 7. All valves listed on page CL-2 of the Initial Start-Up Checklist are fully open. 8. The VFD cold plate refrigerant isolation valves are open. 64 To start the chiller the STOP override setting must first be removed. Access the MAINSTAT screen and using NEXT or PREVIOUS softkeys highlight CHILLER START/STOP. The 3 softkeys that appear represent 3 choices: SHIPPING BRACKET • • • START — forces the chiller ON STOP — forces the chiller OFF RELEASE — puts the chiller under remote or schedule control. To return the chiller to normal control, press the RELEASE softkey followed by the ENTER softkey. For more information, see Local Start-Up, page 46. The default ICVC screen message line indicates which command is in effect. Check Chiller Operating Condition — Check to be sure that chiller temperatures, pressures, liquid flows, and oil and refrigerant levels indicate the system is functioning properly. Instruct the Customer Operator — Ensure the operator(s) understands all operating and maintenance procedures. Point out the various chiller parts and explain their function as part of the complete system. COOLER-CONDENSER — Float chamber, relief valves, refrigerant charging valve, temperature sensor locations, pressure transducer locations, Schrader fittings, waterboxes and tubes, and vents and drains. OPTIONAL PUMPOUT STORAGE TANK AND PUMPOUT SYSTEM — Transfer valves and pumpout system, refrigerant charging and pumpdown procedure, and relief devices. COMPRESSOR ASSEMBLY — Motor cooling system, oil system, temperature and pressure sensors, sight glasses, motor temperature sensors, synthetic oil, and compressor serviceability. COMPRESSOR LUBRICATION SYSTEM — Concentrator, oil pump, oil filter, oil heaters, oil charge and specification, strainers, sight glasses, operating and shutdown oil level, temperature and pressure sensors, and oil charging connections. CONTROL SYSTEM — CCN and LOCAL start, reset, menu, softkey functions, ICVC operation, occupancy schedule, set points, safety controls, and auxiliary and optional controls. AUXILIARY EQUIPMENT — Disconnects, separate electrical sources, pumps, cooling tower, chilled liquid strainers, and condenser liquid strainers. DESCRIBE CHILLER CYCLES — Refrigerant, motor cooling, lubrication, and oil reclaim. REVIEW MAINTENANCE — Scheduled, routine, and extended shutdowns, importance of a log sheet, importance of liquid treatment and tube cleaning, and importance of maintaining a leak-free chiller. SAFETY DEVICES AND PROCEDURES — Electrical disconnects, relief device inspection, and handling refrigerant. CHECK OPERATOR KNOWLEDGE — Start, stop, and shutdown procedures, safety and operating controls, refrigerant and oil charging, and job safety. REVIEW THE START-UP, OPERATION AND MAINTENANCE MANUAL a23-1565 Fig. 39 — Control Center Shipping Brace 9. Remove the control center shipping brace (see Fig. 39). Operating the chiller with the shipping brace attached may result in excessive vibration and noise. The shipping brace should be removed to avoid possible equipment damage. Do not permit liquid or brine that is warmer than 110 F (43 C) to flow through the cooler or condenser. Refrigerant overpressure may discharge through the relief valves and result in the loss of refrigerant charge. 10. Access the CONTROL TEST screen. Scroll down on the TERMINATE LOCKOUT option. Press the SELECT (to enable the chiller to start) and answer YES to restore unit to operating mode. The chiller is locked out at the factory in order to prevent accidental start-up. Check Oil Pressure and Compressor Stop — Start the chiller and allow it to automatically ramp load. 1. Two minutes after start-up, note the OIL PRESSURE DELTA P reading on the ICVC default screen. The OIL PRESSURE DELTA P is the difference between the oil pressure leaving the oil filter and the oil sump pressure. The minimum OIL PRESSURE DELTA P is 18 psid (124 kPad) after OIL PRESSURE VERIFY TIME is exceeded. The OIL PRESSURE DELTA P is displayed on the COMPRESS, STARTUP, PRESSURE TRANSDUCERS, PUMPS, and DEFAULT screens. A normal full load reading is approximately 20 to 28 psid (138 to 193 kPad). 2. Press the STOP softkey and listen for any unusual sounds from the compressor as it coasts to a stop. To Prevent Accidental Start-Up — The chiller is shipped with the CHILLER START/STOP parameter in the MAINSTAT screen set to STOP. Once installed, a chiller STOP override setting may be entered to prevent accidental start-up during service or whenever necessary. Access the MAINSTAT screen and using the NEXT or PREVIOUS softkeys, highlight the CHILLER START/STOP parameter. Override the current START value by pressing the SELECT softkey. Press the STOP softkey followed by the ENTER softkey. The word SUPVSR! displays on the ICVC indicating the STOP override is in place. Manuals and notebooks should not be stored under the VFD power module, they will block air flow into the power module cooling fan and cause the VFD to overheat. 65 5. The condenser pressure and temperature varies with the chiller design conditions. Typically the pressure will range between 60 to 135 psig (329 to 780 kPa) with a corresponding temperature range of 60 to 105 F (15 to 41 C). The condenser entering liquid temperature may be controlled below the specified design entering liquid temperature to save on compressor kilowatt requirements but, not be below 55 F (12.8 C). 6. Cooler pressure and temperature also will vary with the design conditions. Typical pressure range will be between 30 to 40 psig (204 to 260 kPa) with temperature ranging between 34 and 45 F (1 and 8 C). 7. The compressor may operate at full capacity for a short time after the pulldown ramping has ended, even though the building load is small. The active electrical demand setting can be overridden to limit the compressor kW, or the pulldown rate can be decreased to avoid a high demand charge for the short period of high demand operation. Pulldown rate can be based on load rate or temperature rate by PULLDOWN RAMP TYPE in the RAMP_DEM screen. AMPS or KW RAMP%/MIN is accessed on the Equipment SERVICE screen, RAMP_DEM table (Table 3, Example 22). TEMP PULLDOWN RAMP/MIN is accessed on the TEMP_CTL screen. OPERATING INSTRUCTIONS Operator Duties 1. Become familiar with the chiller and related equipment before operating the chiller. 2. Prepare the system for start-up, start and stop the chiller, and place the system in a shutdown condition. 3. Maintain a log of operating conditions and document any abnormal readings. 4. Inspect the equipment, make routine adjustments, and perform a Control Test. Maintain the proper oil and refrigerant levels. 5. Protect the system from damage during shutdown periods. 6. Maintain the set point, time schedules, and other PIC III functions. Prepare the Chiller for Start-Up — Follow the steps described in the Initial Start-Up section, page 64. To Start the Chiller 1. Start the liquid pumps, if they are not automatic. 2. On the ICVC default screen, press the LOCAL or CCN softkey to start the system. If the chiller is in the OCCUPIED mode and the start timers have expired, the start sequence will start. Follow the procedure described in the Start-Up/Shutdown/Recycle Sequence section, page 46. To Stop the Chiller 1. The occupancy schedule starts and stops the chiller automatically once the time schedule is configured. 2. The STOP button must be pressed for one second before the alarm light blinks once to confirm the button has been pressed. The compressor will then follow the normal shutdown sequence as described in the Controls section. The chiller will not restart until the CCN or LOCAL softkey is pressed. The chiller is now in the OFF control mode. Check the Running System — After the compres- sor starts, the operator should monitor the ICVC display and observe the parameters for normal operating conditions: 1. The oil sump temperature will vary from 50 deg F to 140 deg F (10 deg C to 60 deg C) depending on the operating conditions. If the chiller has not been running for a few hours the OIL SUMP TEMP will be warmer than the CALC EVAP SAT TEMP. When the chiller is not running, the oil heater is energized whenever the OIL SUMP TEMP is less than the smaller of 140 (60 deg C) or 53 deg F (29.4 deg C) greater than the CALC EVAP SAT TEMP. The OIL SUMP TEMP generally decreases slowly following start-up and eventually stabilizes at a point lower than the temperature maintained during shut down. The OIL PRESS DELTA P increases above 18 psid (124 kPad) during start-up and generally does not vary by more than ± 2 psid (14 kPad). The level in the oil sump is generally very stable. Changes in the oil level occur very slowly. 2. When the compressor is running, the liquid level should be visible in the oil sump or the strainer housing sight glass. Low oil pressure alarms are imminent if the oil level drops below the bottom of the oil strainer housing sight glass. 3. The OIL PRESSURE DELTA P displayed on the ICVC default screen is equal to the difference between the oil pressure leaving the oil filter and the oil sump pressure transducer readings. Typically the reading will be between 20 and 28 psid (138 to 193 kPad) after the oil pressure ramp up is complete. 4. The moisture indicator (dry-eye) sight glass on the refrigerant motor cooling line should indicate refrigerant flow and a dry condition. FAILURE TO STOP — If the alarm light does not blink after pressing and holding the stop button for at least one second and the chiller fails to stop, the operator should open the main circuit breaker on the front of the control panel. IMPORTANT: Do not attempt to stop the chiller by opening an isolating knife switch. High intensity arcing may occur. Do not restart the chiller until the problem is diagnosed and corrected. After Limited Shutdown — No special preparations should be necessary. Follow the regular preliminary checks and starting procedures. Preparation for Extended Shutdown — The refrigerant should be transferred into the pumpout storage tank (if supplied; see Pumpout and Refrigerant Transfer Procedures) to reduce chiller pressure and the possibility of leaks. Maintain a holding charge of 5 to 10 psi (34 to 69 kPa) of refrigerant or nitrogen to prevent air from leaking into the chiller. If freezing temperatures are likely to occur in the chiller area, drain the chilled liquid, condenser liquid, and the pumpout condenser liquid circuits to avoid freeze-up. Keep the waterbox drains open. Leave the oil charge in the chiller with the oil heater and controls energized to maintain the minimum oil reservoir temperature. 66 After Extended Shutdown — Ensure the liquid sys- Cold Weather Operation — When the entering con- tem drains are closed. It may be advisable to flush the liquid circuits to remove any soft rust which may have formed. This is a good time to brush the tubes and inspect the Schrader fittings on the optional liquid side flow devices for fouling, if necessary. Check the cooler pressure on the ICVC default screen and compare it to the original holding charge that was left in the chiller. If (after adjusting for ambient temperature changes) any loss in pressure is indicated, check for refrigerant leaks. See Check Chiller Tightness section, page 49. Recharge the chiller by transferring refrigerant from the pumpout storage tank (if supplied). Follow the Pumpout and Refrigerant Transfer Procedures section, page 69. Observe freeze-up precautions. Carefully make all regular preliminary and running system checks. Perform a Control Test before start-up. If the oil level appears abnormally high, the oil may have absorbed refrigerant. A LOW OIL TEMPERATURE prestart alert will be declared if the oil temperature is not greater than the CALC EVAP SAT TEMP plus 15 F (8.3 C) or 140 F (60 C), whichever is lower. denser liquid drops very low (55 F [13 C] minimum), the operator or tower control should automatically cycle the cooling tower fans off to keep the temperature up. Piping may also be arranged to bypass the cooling tower. The PIC III controls have a Tower Fan Low control contact that can be used to assist in this control (terminals 5 and 6 on the TB2 hazardous voltage field wiring terminal strip). Refrigeration Log — A refrigeration log, such as the one shown in Fig. 40, provides a convenient checklist for routine inspection and maintenance, and provides a continuous record of chiller performance. It is an aid in scheduling routine maintenance and in diagnosing chiller problems. Keep a record of the chiller pressures, temperatures, and liquid levels on a sheet similar to that shown. Automatic recording of PIC III data is possible through the use of CCN devices such as the Data Collection module and a Building Supervisor. Contact your Carrier representative for more information. 67 68 Press. Temp Refrigerant Liquid Pressure In Out GPM COOLER Temp In Out Press. Temp Refrigerant MODEL NO. Liquid Pressure In Out GPM CONDENSER COMPRESSOR Line kW OPERVFD ATOR Avg. Rectifier Coolant INITIALS Load Inverter Temp Flow Current Temp VFD REFRIGERANT TYPE Oil Oil Oil Comp. Avg. Avg. Reclaim Reclaim Oil Temp Press Sump Disch. Line Line Delta T Output Level Delta P Temp Temp Current Voltage In Out CONCENTRATOR SERIAL NO. Fig. 40 — Refrigeration Log: Carrier 23XRV Hermetic Screw Refrigeration REMARKS: Indicate shutdowns on safety controls, repairs made, oil or refrigerant added or removed, operating hours, and start counts. Include amounts. TIME DATE: Plant REMARKS counterclockwise to open. Frontseating the valve closes the refrigerant line and opens the gage port to compressor pressure. 2. Ensure that the compressor holddown bolts have been loosened to allow free spring travel. 3. Open the refrigerant inlet valve on the pumpout compressor. 4. Oil should be visible in the pumpout unit compressor sight glass under all operating conditions and during shutdown. If oil is low, add oil as described under Optional Pumpout System Maintenance section, page 78. The pumpout unit control wiring schematic is detailed in Fig. 41. TO READ REFRIGERANT PRESSURES during pumpout or leak testing: 1. The ICVC display on the chiller control center is suitable for determining refrigerant-side pressures and low (soft) vacuum. To assure the desired range and accuracy when measuring evacuation and dehydration, use a quality vacuum indicator or manometer. This can be placed on the Schrader connections on each vessel by removing the evaporator or condenser pressure transducer (Fig. 3). 2. To determine pumpout storage tank pressure, a 30 in. Hg vacuum –0-400 psi (–101-0-2769 kPa) compound gage is attached to the storage tank. 3. Refer to Fig. 31-33, and 41 for valve locations and numbers. PUMPOUT AND REFRIGERANT TRANSFER PROCEDURES Preparation — The 23XRV chiller may come equipped with an optional pumpout storage tank, pumpout system, or pumpout compressor. The refrigerant can be pumped for service work to either the chiller compressor evaporator vessel or chiller condenser vessel by using the optional pumpout system. If a pumpout storage tank is supplied, the refrigerant can be isolated in the storage tank. The following procedures describe how to transfer refrigerant from vessel to vessel and perform chiller evacuations. Always run the chiller cooler and condenser liquid pumps and always charge or transfer refrigerant as a gas when the chiller pressure is less than 35 psig (241 kPa). Below these pressures, liquid refrigerant flashes into gas, resulting in extremely low temperatures in the cooler/condenser tubes and possibly causing tube freeze-up. During transfer of refrigerant into and out of the optional storage tank, carefully monitor the storage tank level gage. Do not fill the tank more than 90% of capacity to allow for refrigerant expansion. Overfilling may result in damage to the tank or personal injury. Transfer, addition, or removal of refrigerant in springisolated chillers may place severe stress on external piping if springs have not been blocked in both up and down directions. Do not mix refrigerants from chillers that use different compressor oils. Compressor damage can result. Operating the Optional Pumpout Unit 1. Be sure that the suction and the discharge service valves on the optional pumpout compressor are open (backseated) during operation. Rotate the valve stem fully C 2 OL C 2 OL C 2 OL L1 FIELD POWER SUPPLY L2 MTR-1 L3 GND L1 H4 CONTROL POWER TRANSFORMER X1 XFMR-1 69 VA 1 X2 X2 55-1 OFF AUTO ON 2 2 3 C FU GND HTR MTR NC OL SS 0.5A FU3 HIGH PRESSURE SAFETY NC OPEN > 185psig 2 CRANKCASE HEATER 240-600v 27-40 WATT 7 0.25A 0.25A FU2 FU1 H1 HTR-1 8 L2 PUMP OUT COMPRESSOR LOW PRESSURE CONTROL NC OPEN < 7 psia (-15.7 in. HG) CLOSE > 9 psia (-11.6 in. HG) — — — — — — — — LEGEND Contactor Fuse Ground Heater Motor Normally Closed Overload Selector Switch 6 4 C 5 X2 a23-1615 Fig. 41 — 23XRV Pumpout Unit Wiring Schematic 69 charging valve 10 to let liquid refrigerant drain into the chiller. Chillers with Storage Tanks — In the Valve/Condi- tion tables that accompany these instructions, the letter “C” indicates a closed valve. Figures 31-33 and 42 show the locations of the valves. VALVE CONDITION VALVE 2 VALVE CONDITION VALVE CONDITION VALVE 3 COMPRESSOR VALVE 5 a23-1546 LEAVING WATER CONDENSER OIL FILL FITTING OIL SEPARATOR VALVE CONDITION Fig. 42 — Optional Pumpout Unit During transfer of refrigerant into and out of the 23XRV storage tank, carefully monitor the storage tank level gage. Do not fill the tank more than 90% of capacity to allow for refrigerant expansion. Overfilling may result in damage to the tank and personal injury. VALVE CONDITION 1b 2 C 3 4 C 5 C 6 7 C 10 C 5 6 7 10 11 1a 1b 2 C 3 4 5 C 6 7 10 11 1a 1b 2 3 C 4 C 5 6 7 C 10 C 11 1a C 1b C 2 C 3 C 4 C 5 C 6 C 7 C 10 C 11 1a 1b 2 C 3 4 C 5 C 6 7 C 10 C 11 b. Slowly open valve 5 and refrigerant charging valves 7 and 10 to allow liquid refrigerant to drain by gravity into the storage tank. 1. Equalize refrigerant pressure. a. Turn on chiller water pumps and monitor chiller pressures. b. Close pumpout and storage tank valves 2, 4, 5, and 10, and close refrigerant charging valve 7; open chiller isolation valve 11 and any other chiller isolation valves, if present. c. Open pumpout and storage tank valves 3 and 6; open chiller valves 1a and 1b. 1a 4 C l. Turn off pumpout condenser water. TRANSFER THE REFRIGERANT FROM CHILLER TO PUMPOUT STORAGE TANK 1. Equalize refrigerant pressure. a. Valve positions: TRANSFER REFRIGERANT FROM PUMPOUT STORAGE TANK TO CHILLER VALVE CONDITION 3 h. Turn on pumpout condenser water. i. Run the pumpout compressor in manual mode until the storage tank pressure reaches 5 psig (34 kPa), 18 in. Hg vacuum (41 kPa absolute). j. Turn off the pumpout compressor. k. Close valves 1a, 1b, 2, 5, and 6. OIL HEATER ENTERING WATER 2 C b. Turn off the pumpout condenser water, and turn on the pumpout compressor in manual mode to push liquid refrigerant out of the storage tank. Monitor the storage tank level until the tank is empty. c. Close refrigerant charging valves 7 and 10. d. Turn off the pumpout compressor. e. Turn off the chiller water pumps. f. Close valves 3 and 4. g. Open valves 2 and 5. FRAME ASSEMBLY VALVE 4 1b 2. Transfer remaining refrigerant. a. Close valve 5 and open valve 4. Always run chiller cooler and condenser water pumps and always charge or transfer refrigerant as a gas when chiller vessel pressure is less than 35 psig (241 kPa). Below these pressures, liquid refrigerant flashes into gas, resulting in extremely low temperatures in the cooler/condenser tubes and possibly causing tube freeze-up. CONTROL PANEL 1a VALVE CONDITION 1a 1b 2 C 3 4 C 5 6 7 10 11 2. Transfer the remaining liquid. a. Turn off pumpout condenser water. Place valves in the following positions: VALVE CONDITION 1a 1b 2 3 C 4 C 5 6 7 10 11 b. Run the pumpout compressor in automatic mode until vacuum switch is satisfied and compressor stops. Close valves 7 and 10. 11 d. Gradually crack open valve 5 to increase chiller pressure to 35 psig (241 kPa). Slowly feed refrigerant to prevent freeze-up. e. Open valve 5 fully after the chiller pressure rises above the freezing point of the refrigerant. Let the storage tank and chiller pressure equalize. Open refrigerant charging valve 7 and storage tank VALVE CONDITION 1a 1b 2 3 C 4 C 5 6 c. Turn off the pumpout compressor. 3. Remove any remaining refrigerant. a. Turn on chiller water pumps. b. Turn on pumpout condenser water. 70 7 C 10 C 11 This operation can be done in Automatic or On mode. In Automatic mode, the compressor will stop automatically at approximately 15 in. Hg vacuum (51 kPa absolute). c. Place valves in the following positions: VALVE CONDITION 1a 1b 2 C 3 4 5 C 6 7 C 10 C 11 d. Close valve 1a. e. Turn off pumpout compressor. f. Close valves 1b, 3, and 4. d. Run the pumpout compressor until the chiller pressure reaches 35 psig (241 kPa); then, shut off the pumpout compressor. Warm chiller condenser water will boil off any entrapped liquid refrigerant and chiller pressure will rise. e. When chiller pressure rises to 40 psig (276 kPa), turn on the pumpout compressor until the pressure again reaches 35 psig (241 kPa), then, turn off the pumpout compressor. Repeat this process until the chiller pressure no longer rises; then, turn on the pumpout compressor and pump out until the chiller pressure reaches 18 in. Hg vacuum (41 kPa absolute). This can be done in On or Automatic mode. f. Close valves 1a, 1b, 3, 4, and 6. VALVE CONDITION 1a C 1b C 2 C 3 C 4 C 5 C 6 C 7 C 10 C VALVE CONDITION 11 VALVE CONDITION 1b 2 3 C 4 C 5 VALVE CONDITION 11 1a 1b 2 C 3 4 5 C 3 C 4 C 5 C 11 C 1a 1b 2 3 C 4 C 5 11 1a 1b 2 3 C 4 C 5 11 C c. Turn on pumpout condenser water. d. Run the pumpout compressor until the chiller condenser reaches 18 in. Hg vacuum (41 kPa absolute) in Manual or Automatic mode. Monitor pressure at the chiller control panel and refrigerant gages. e. Close valve 1b. f. Turn off pumpout compressor. g. Close valves 1a, 2, and 5. c. Equalize the refrigerant in the chiller cooler and condenser. d. Turn off chiller water pumps and pumpout condenser water supply. e. Turn on pumpout compressor to push liquid out of the chiller cooler vessel. f. When all liquid has been pushed into the chiller condenser vessel, close the cooler refrigerant isolation valve (11). g. Turn on the chiller water pumps. h. Turn off the pumpout compressor. 2. Evacuate gas from chiller cooler vessel. a. Close pumpout valves 2 and 5; open valves 3 and 4. VALVE CONDITION 2 C c. Equalize the refrigerant in the chiller cooler and condenser. d. Turn off chiller water pumps and pumpout condenser water. e. Turn on pumpout compressor to push refrigerant out of the chiller condenser. f. When all liquid is out of the chiller condenser, close valve 11 and any other liquid isolation valves on the chiller. g. Turn off the pumpout compressor. 2. Evacuate gas from chiller condenser vessel. a. Turn on chiller water pumps. b. Make sure that pumpout valves 3 and 4 are closed and valves 2 and 5 are open. Transfer All Refrigerant to Chiller Condenser Vessel 1. Push refrigerant into chiller condenser vessel. a. Turn on the chiller water pumps and monitor the chiller pressure. b. Valve positions: 1a 1b C g. Turn off pumpout condenser water. h. Turn off chiller water pumps and lock out chiller compressor. Transfer All Refrigerant to Chiller Cooler Vessel 1. Push refrigerant into the chiller cooler vessel. a. Turn on the chiller water pumps and monitor the chiller pressure. b. Valve positions: g. Turn off the pumpout condenser water. 4. Establish vacuum for service. To conserve refrigerant, operate the pumpout compressor as described in Step 3e until the chiller pressure is reduced to 18 in. Hg vacuum (41 kPa absolute). This operation can be done in Automatic or On mode. In Automatic mode, the compressor will stop automatically at approximately 15 in. Hg vacuum (51 kPa absolute). CHILLERS WITH ISOLATION VALVES — The valves referred to in the following instructions are shown in Fig. 31-33 and 41. Valve 7 remains closed. VALVE CONDITION 1a C VALVE CONDITION 1a C 1b C 2 C 3 C 4 C 5 C 11 C h. Turn off pumpout condenser water. i. Turn off chiller water pumps and lock out chiller compressor. Return Refrigerant to Normal Operating Conditions 1. Be sure that the chiller vessel that was opened has been evacuated. 2. Turn on chiller water pumps. 3. Open valves 1a, 1b, and 3. 11 C b. Turn on pumpout condenser water. c. Run pumpout compressor until the chiller cooler vessel pressure reaches 18 in. Hg vacuum (41 kPa absolute). Monitor pressures on the chiller control panel and on refrigerant gages. VALVE CONDITION 71 1a 1b 2 C 3 4 C 5 C 11 C Safety Data Sheet and the latest ASHRAE Safety Guide for Mechanical Refrigeration to learn more about safe handling of this refrigerant. 4. Crack open valve 5, gradually increasing pressure in the evacuated chiller vessel to 35 psig (241 kPa). Feed refrigerant slowly to prevent tube freeze-up. 5. Leak test to ensure chiller vessel integrity. 6. Open valve 5 fully. VALVE CONDITION 1a 1b 2 C 3 4 C 5 HFC-134a will dissolve oil and some non-metallic materials, dry the skin, and, in heavy concentrations, may displace enough oxygen to cause asphyxiation. In handling this refrigerant, protect the hands and eyes and avoid breathing fumes. 11 C 7. Close valves 1a, 1b, 3, and 5. 8. Open chiller isolation valve 11 and any other isolation valves, if present. VALVE CONDITION 1a C 1b C 2 C 3 C 4 C 5 C Adding Refrigerant — Follow the procedures described 11 in the Charge Refrigerant into Chiller section, page 63. 9. Turn off chiller water pumps. DISTILLING THE REFRIGERANT 1. Transfer the refrigerant from the chiller to the pumpout storage tank as described in the Transfer the Refrigerant from Chiller to Pumpout Storage Tank section. 2. Equalize the refrigerant pressure. a. Turn on chiller water pumps and monitor chiller pressures. b. Close pumpout and storage tank valves 2, 4, 5, and 10, and close chiller charging valve 7; open chiller isolation valve 11 and any other chiller isolation valves, if present. c. Open pumpout and storage tank valves 3 and 6; open chiller valves 1a and 1b. VALVE CONDITION 1a 1b 2 C 3 4 C 5 C 6 7 C 10 C Always use the compressor pumpdown function in the Control Test mode to turn on the evaporator pump and lock out the compressor when transferring refrigerant. Liquid refrigerant may flash into a gas and cause possible freezeup when the chiller pressure is below 35 psig (241 kPa). Removing Refrigerant — If the optional pumpout sys- tem is used, the 23XRV refrigerant charge may be transferred to a storage vessel or within the condenser or cooler if isolation valves are present. Follow procedures in the Pumpout and Refrigerant Transfer Procedures section when removing refrigerant from the storage tank to the chiller. Adjusting the Refrigerant Charge — If the addition or removal of refrigerant is required for improved chiller performance, follow the procedures given under the Trim Refrigerant Charge section, on this page. 11 d. Gradually crack open valve 5 to increase chiller pressure to 35 psig (241 kPa). Slowly feed refrigerant to prevent freeze-up. e. Open valve 5 fully after the chiller pressure rises above the freezing point of the refrigerant. Let the storage tank and chiller pressure equalize. 3. Transfer remaining refrigerant. a. Close valve 3. b. Open valve 2. VALVE CONDITION 1a 1b 2 3 C 4 C 5 6 7 C 10 C Refrigerant Leak Testing — Because HFC-134a is above atmospheric pressure at room temperature, leak testing can be performed with refrigerant in the chiller. Use an electronic leak detector, halide leak detector, soap bubble solution, or ultra-sonic leak detector. Be sure that the room is well ventilated and free from concentration of refrigerant to keep false readings to a minimum. Before making any necessary repairs to a leak, transfer all refrigerant from the leaking vessel. The chiller should be leak tested at least once per year. Refrigerant Leak Rate — ASHRAE recommends that chillers should be immediately taken off line and repaired if the refrigerant leakage rate for the entire chiller is more than 10% of the operating refrigerant charge per year. Additionally, Carrier recommends that leaks totalling less than the above rate but more than a rate of 1 lb (0.5 kg) per year should be repaired during annual maintenance or whenever the refrigerant is pumped over for other service work. 11 c. Turn on pumpout condenser water. d. Run the pumpout compressor until the storage tank pressure reaches 5 psig (34 kPa), 18 in. Hg vacuum (41 kPa absolute) in Manual or Automatic mode. e. Turn off the pumpout compressor. f. Close valves 1a, 1b, 2, 5, and 6. g. Turn off pumpout condenser water. VALVE CONDITION 1a C 1b C 2 C 3 C 4 C 5 C 6 C 7 C 10 C Test After Service, Repair, or Major Leak — If all refrigerant has been lost or if the chiller has been opened for service, the chiller or the affected vessels must be pressured and leak tested. Refer to the Leak Test Chiller section to perform a leak test. REFRIGERANT TRACER — Use an environmentally acceptable refrigerant as a tracer for leak test procedures. TO PRESSURIZE WITH DRY NITROGEN — Another method of leak testing is to pressure with nitrogen only and use soap bubble solution or an ultrasonic leak detector to determine if leaks are present. This should only be done if all refrigerant has been evacuated from the vessel. 1. Connect a copper tube from the pressure regulator on the cylinder to the refrigerant charging valve. Never apply full cylinder pressure to the pressurizing line. Follow the listed sequence. 11 4. Drain the contaminants from the bottom of the storage tank into a container. Dispose of contaminants safely. GENERAL MAINTENANCE Refrigerant Properties — HFC-134a is the standard refrigerant in the 23XRV chiller. At normal atmospheric pressure, HFC-134a will boil at –14 F (–25 C), and must, therefore, be kept in pressurized containers or storage tanks. The refrigerant is practically odorless when mixed with air. HFC-134a is non-combustible at atmospheric pressure. Read the Material 72 2. Open the charging valve fully. 3. Slowly open the cylinder regulating valve. 4. Observe the pressure gage on the chiller and close the regulating valve when the pressure reaches test level. Do not exceed 140 psig (965 kPa). 5. Close the charging valve on the chiller. Remove the copper tube if no longer required. SCHEDULED MAINTENANCE Establish a regular maintenance schedule based on the actual chiller requirements such as chiller load, run hours, and cooler and condenser liquid quality. The time intervals listed in this section are offered as guides to service only. Service Ontime — The ICVC will display a SERVICE ONTIME value on the MAINSTAT table. This value should be reset to zero by the service person or the operator each time major service work is completed so that time between service can be seen. Repair the Refrigerant Leak, Retest, and Apply Standing Vacuum Test — After pressurizing the chiller, test for leaks with a soap bubble solution, an electronic leak detector, a halide torch, or an ultrasonic leak detector. Bring the chiller back to atmospheric pressure, repair any leaks found, and retest. After retesting and finding no leaks, apply a standing vacuum test. Then dehydrate the chiller. Refer to the Chiller Dehydration in the Before Initial Start-Up section, page 55. Inspect the Control Center — Maintenance is generally limited to general cleaning and tightening of connections. Vacuum the control center enclosure to eliminate dust build-up. In the event of chiller control malfunctions, refer to the Troubleshooting Guide section for control checks and adjustments. Power connections on newly installed equipment may relax and loosen after a month of operation. Turn off power and re-tighten, check annually thereafter. Trim Refrigerant Charge — If it becomes necessary to adjust the refrigerant charge to obtain optimum chiller performance, operate the chiller at design load and then add or remove refrigerant slowly until the difference between LEAVING CHILLED LIQUID chilled liquid temperature and the EVAP REFRIG LIQUID TEMP reaches design conditions. Do not overcharge. For superheat information, see the Troubleshooting section on page 78. Refrigerant may be added either through the optional storage tank or directly into the chiller as described in the section entitled, Refrigerant Charging. To remove any excess refrigerant, follow the procedure in Transfer Refrigerant from Chiller to Pumpout Storage Tank section, Steps 1a, b on page 70. Be sure power to the control center is off when cleaning and tightening connections inside the control center. Check Safety and Operating Controls Monthly — To ensure chiller protection, the Automated Control Test in the service menu should be done at least once per month. See Table 5 for safety control settings. Do not manually open the oil reclaim isolation valve when the chiller is shut down. Doing so will flood the vaporizer with refrigerant and severely degrade the viscosity of the oil in the sump. WEEKLY MAINTENANCE Check the Lubrication System — Mark the oil level on the oil sump sight glasses and observe the level each week while the chiller is running. Check the moisture indicator on the motor cooling line. If the level goes below the bottom of the oil sump sight glass, the oil reclaim system will need to be checked for proper operation. The oil reclaim system is operating properly if the level in the oil sump increases after running the chiller near full load with a 95 F or higher CONDENSER TEMPERATURE for 1 hour. If additional oil is required, add it through the oil charging valve (Fig. 2 and 3). A hand pump is required for adding oil against refrigerant pressure. The oil charge for the 23XRV chiller is 7.5 gallons (28 L). The oil must meet Carrier’s specifications for the 23XRV chillers. Refer to Changing Oil and Oil Filter section. Any oil that is added should be logged by noting the amount and date in Fig. 40 on page 68. Any oil that is added due to oil loss not related to service will eventually return to the sump. Excess oil must be removed when the level is above the top of the oil sump sight glass. A 530-watt oil sump heater is controlled by the PIC III to maintain oil temperature above 140 F (60 C) or CALC EVAP SAT TEMP plus 53 F (29.4 C) when the compressor is off (see the Controls section on page 12). The ICVC StatusCOMPRESS table displays whether the heater is energized or not. If the PIC III shows that the sump heater is energized, but the sump is not heating up, the power to the oil sump heater may be off or the oil level may be too low. Check the oil level, the sump oil heater contactor voltage, and oil heater resistance. The PIC III will not permit compressor start-up if the oil temperature is less than 140 F (60 C) or CALC EVAP SAT TEMP plus 15 F (8.3 C), whichever is lower. The control will continue with start-up only after the temperature is within limits. Changing Oil and Oil Filter — If the OIL PRES- SURE DELTA P approaches the 18 psid (124 kPad) LOW OIL PRESSURE ALARM threshold, change oil filter as needed. Otherwise, change the oil filter on a yearly basis. Change the oil after the first year of operation. Then, change the oil at least every three years, or as needed. However, if a continuous oil monitoring system is present and/or a yearly oil analysis is performed, the time between oil changes may be extended. See Oil Specification section on page 74 for additional information. Compressor oil is hygroscopic. Containers should remain tightly sealed in a clean and dry environment to prevent moisture absorption from the air. The 23XRV oil pump and filter can be isolated to change the oil filter and oil while the refrigerant remains inside the chiller. Use the following procedure to change the oil and oil filter (if required): CHANGING OIL 1. Make sure the compressor is off and the CB1 main circuit breaker for the control center is open. 2. Open the CB2 control power and oil heater circuit breaker in order to turn off the power to the oil heater. 73 • Pour Point (maximum) . . . . . . . . . . . . . . . . . . . –6 F (–21 C) • Flash Point (minimum) . . . . . . . . . . . . . . . . . . 428 F (220 C) • Moisture Content (maximum). . . . . . . . . . . . . . . . . . .50 ppm • Acid Number (maximum) . . . . . . . . . . . 0.15 mg KOH/gram • Critical Solution Temperature with HFC-134a (maximum) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . –8 F(–22 C) 3. Record the oil level observed in the oil sump sight glass. Be sure the power to the oil heater is off when the oil sump is drained. If the oil heater remains energized when the sump is empty, it will overheat any residual oil on the heating element and become fouled. Overheating the elements will also significantly reduce their useful life. Compressor oil is hygroscopic. Containers should remain tightly sealed in a clean and dry environment to prevent moisture absorption from the air. 4. Connect an oil charging hose to the oil drain valve on the strainer housing. See Fig. 3. Place the other end of the oil charging hose in a clean container suitable for used oil. A portion of the oil drained from the sump should be used as an oil sample and should be sent to a laboratory for proper analysis. Do not contaminate this sample. 5. Slowly open the drain valve in order to drain the oil from the sump. This oil (part number PP23BZ110001 [6x1 gal cans] and PP23BZ110005 [1x5 gal can]) may be ordered from your local Carrier representative. Oil Heater — Inspect the oil heater for carbon build-up on the heating element if an adequate oil sump temperature cannot be maintained when the chiller is shut down. It may be necessary to temporarily install the heater element terminal cover to provide additional leverage while threading the oil heater into the sump. The sump oil heater elements must be positioned vertically to allow proper heat convection. See Fig. 43 and 44. The heater element must be installed with the word “TOP” on the threaded fitting facing upward. The oil sump is at high pressure. Relieve pressure slowly. 6. Charge new oil through the drain valve on the strainer housing. A hand pump or portable electric oil pump will be required to charge oil back into the oil sump against refrigerant pressure. 7. Add oil (approximately 7 gal [23 L]) until it returns to the level noted in Step 3. The oil sight glass will not fill completely since a small amount of gas will be trapped inside (even under vacuum conditions). 8. Apply power through the CB2 controls and oil heater circuit breaker. Changing Oil Filter 1. Make sure the compressor is off and the disconnect for the compressor starter is open. 2. Close both oil filter isolation valves. See Fig. 43. 3. Place a container underneath the oil filter assembly. 4. When a Schrader valve is provided, use it to relieve the pressure. Slowly open the drain plug, located on the bottom of the oil filter housing, to relieve pressure. Do not remove the plug. 5. Remove the filter canisters by unscrewing the retainer nut. The filter may now be removed and disposed of properly. 6. Install new oil filter. Install the new O-ring. Tighten the retainer nut. 7. If a Schrader valve is supplied, evacuate the oil filter by connecting the vacuum pump to the Schrader valve. 8. Slowly open the isolation valve located near the oil pump to equalize the pressure. Fully open both oil filter isolation valves. Refrigerant Filter/Drier — A refrigerant filter/drier, located on the motor cooling line, should be changed once per year, or as necessary, if the condition of the filter indicates a need for less or more frequent replacement (see Fig. 45). A moisture indicator (dry eye) sight glass is located beyond the filter/drier to indicate the concentration of moisture in the refrigerant. If the moisture indicator indicates moisture, locate the source of the liquid immediately by performing a thorough leak check. Close the isolation valves on either side of the filter drier. Use the Schrader valve to relieve pressure in the isolated filter/drier. Replace the filter/drier and evacuate the isolated section of tubing with a vacuum pump attached to the Schrader valve. Oil Strainers — The oil reclaim system has two strainers. One is installed in the VFD refrigerant cooling line between the cooler and condenser. The second strainer is located in the oil sump strainer housing (see Fig. 43). The oil sump strainer must be replaced or inspected with the refrigerant charge isolated in the condenser. Inspect the oil sump strainer for obstructions or damage every time the oil is changed. The strainer threads into the oil sump strainer housing. Install a new strainer o-ring if the entire strainer does not require replacement. VFD Refrigerant Strainer — A refrigerant strainer is located in the line that supplies refrigerant to the VFD. Three isolation valves in the refrigerant cooling lines must be closed before this strainer is changed. See Fig. 45. Vaporizer Refrigerant Return Line Orifice — There is a metering orifice where the refrigerant return line attaches to the vaporizer (see Fig. 43). This orifice can only be inspected by cutting the vaporizer refrigerant return line near the vaporizer. This orifice should be inspected if hot condenser gas flow through the vaporizer appears to be obstructed. Oil Specification — If oil is to be added, it must meet the following Carrier specifications: • Carrier Part Number. . . . . . . .PP23BZ110001 (6x1 gal cans) . . . . . . . . . . . . . . . . . . . . . . . . . . .PP23BZ110005 (1x5 gal cans) • Oil type . . . . . . . . . . . . . . . . . . . . .Inhibited polyolester-based synthetic compressor lubricant suitable for use in screw compressors where high viscosity and compatibility with HFC-134a refrigerants is required. • ISO Viscosity Grade. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220 • Specific Gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.981 • Viscosity, cSt at 40 C (104 F) . . . . . . . . . . . . . . . . 198 to 242 cSt at 100 C (212 F) . . . . . . . . . . . . . . . . . 18 to 21 SSU at 100 F (38 C) . . . . . . . . . . . . . . .1005 ± 100 SSU at 210 F (99 C) . . . . . . . . . . . . . . . . . . .91 ± 7 Compressor Inlet Bearing Oil Orifice — The oil line leading to the compressor lubrication block is connected to the inlet bearing oil orifice. The orifice is pressed into a standard reducer/expander fitting and protected by a 50 X 50 mesh screen (see Fig. 46). Compressor oil lines and fittings between the oil filter and compressor must be capped during disassembly to prevent contamination. Inspect the inlet bearing oil orifice whenever the oil line between the oil filter and compressor is disconnected. 74 4. Apply thread locking adhesive (P/N 24221 [10 ml] or 24231 [50 ml]) the 3/8-in. - 16 bolts that hold the float valve in place. See Fig. 47 for a view of the float valve design. Inspect the orientation of the float slide pin. It must be pointed toward the bubbler tube for proper operation. 5. Apply gasket sealant (P/N 19XL680-002) to both sides of new gasket when reinstalling cover. Inspect Condenser Refrigerant Float System — Perform this inspection when the condenser is opened for service. See Fig. 47. 1. Transfer the refrigerant into the cooler vessel or into a pumpout storage tank. 2. Remove the float access cover. 3. Clean the chamber and valve assembly thoroughly. Be sure the valve moves freely. Ensure that all openings are free of obstructions. OIL SUPPLY LINE (TO COMPRESSOR) OIL PRESSURE LEAVING FILTER SENSOR OIL RECLAIM ACTUATOR OIL PRESSURE REGULATOR LINE OIL FILTER SCHRADER VALVE OIL RECLAIM LINE ( FROM COOLER) VAPORIZER REFRIGERANT RETURN ORIFICE OIL SUMP PRESSURE SENSOR OIL SUMP STRAINER OIL FILTER ISOLATION VALVE OIL SUMP TEMPERATURE SENSOR OIL FILTER a23-1639 OIL PUMP ISOLATION VALVE OIL PUMP JUNCTION BOX Fig. 43 — Oil Sump Strainer and Filter CONDENSER GAS INLET VAPORIZER HEATER JUNCTION BOX OIL RETURN FROM COMPRESSOR OIL PRESSURE REGULATOR VALVE OIL SUMP TEMPERATURE SENSOR (ON FAR END OF OIL SUMP) a23-1630 OIL SUMP SIGHT GLASS VERTICALLY ORIENTED OIL HEATER ELEMENTS VAPORIZER TEMPERATURE SENSOR THERMOWELL OIL SUMP HEATER JUNCTION BOX Fig. 44 — Oil Reclaim Cross Section 75 VAPORIZER DRAIN SIGHT GLASS OIL PRESSURE REGULATOR ISOLATION VALVE FILTER DRIER ISOLATION VALVE MOISTURE INDICATOR VFD REFRIGERANT COOLING ISOLATION VALVES (2) VFD REFRIGERANT STRAINER REFRIGERANT FILTER/DRIER FILTER/DRIER ISOLATION VALVE a23-1616 Fig. 45 — Refrigerant Filter/Drier 1 ORIFICE SCREEN 2 3 4 a23-1631 5 Fig. 46 — Compressor Inlet Bearing Oil Orifice 6 7 a23-1632 1 2 3 4 5 6 7 8 — — — — — — — — 8 LEGEND Refrigerant Inlet from FLASC Chamber Linear Float Assembly Float Screen Bubbler Line Float Cover Bubble Line Connection Refrigerant Outlet to Cooler Gasket Fig. 47 — 23XRV Float Valve Design 76 Higher than normal condenser pressures, together with the inability to reach full refrigeration load, usually indicate dirty tubes or air in the chiller. If the refrigeration log indicates a rise above normal condenser pressures, check the condenser refrigerant temperature against the leaving condenser liquid temperature. If this reading is more than what the design difference is supposed to be, then the condenser tubes may be dirty or liquid flow may be incorrect. Because HFC-134a is a high-pressure refrigerant, air usually does not enter the chiller. During the tube cleaning process, use brushes especially designed to avoid scraping and scratching the tube wall. Contact your Carrier representative to obtain these brushes. Do not use wire brushes. Inspect Relief Valves and Piping — The relief valves on this chiller protect the system against the potentially dangerous effects of overpressure. To ensure against damage to the equipment and possible injury to personnel, these devices must be kept in peak operating condition. Inspect the relief valves in accordance with local codes. At a minimum, the following maintenance is required. 1. At least once a year, disconnect the vent piping at the valve outlet and carefully inspect the valve body and mechanism for any evidence of internal corrosion or rust, dirt, scale, leakage, etc. 2. If corrosion or foreign material is found, do not attempt to repair or recondition. Replace the valve. 3. If the chiller is installed in a corrosive atmosphere or the relief valves are vented into a corrosive atmosphere, make valve inspections at more frequent intervals. Hard scale may require chemical treatment for its prevention or removal. Consult a liquid treatment specialist for proper treatment. Failure to properly treat liquid could result in property damage or personal injury. Compressor Bearing Maintenance — The compressor bearings are designed to last for the life of the chiller. The key to good bearing maintenance is proper lubrication. Use the proper grade of oil, maintained at recommended level, temperature, and pressure. Inspect the lubrication system regularly and thoroughly. Excessive bearing wear can be detected through increased vibration. If this symptom appears, contact an experienced and responsible service organization to perform vibration analysis on the compressor. Water/Brine Leaks — Moisture in the refrigerant is in- dicated during chiller operation by the refrigerant moisture indicator on the refrigerant motor cooling line. See Fig. 2. Leaks should be repaired immediately. The chiller must be dehydrated after repair of liquid leaks. See Chiller Dehydration section, page 55. Failure to dehydrate the chiller after repair of liquid leaks could result in equipment damage or personal injury. Compressor Rotor Check — Use Carrier specified oil. Excessive compressor rotor wear is shown by a lack of performance. If a lack of performance is noted, have the compressor rotors inspected by a trained service person. The rotors can be visually inspected once every 5 to 10 years or as needed depending on chiller operating conditions. Water/Brine Treatment — Untreated or improperly treated water/brine may result in corrosion, scaling, erosion, or algae. The services of a qualified water/brine treatment specialist should be obtained to develop and monitor a treatment program. Motor Insulation — Periodic checks of the motor insulation are not necessary. A 500V megger test is recommended to assist troubleshooting if there are indications of problems including, but not limited to, moisture in the refrigerant, and chronic current imbalance or over current trips. See guidelines for megger test in the Before Initial Start-Up section on page 48. Water/brine must be within design flow limits, clean, and treated to ensure proper chiller performance and to reduce the potential of tubing damage due to corrosion, scaling, erosion, and algae. Carrier assumes no responsibility for chiller damage resulting from untreated or improperly treated water/brine. The motor leads must be disconnected from the VFD before an insulation test is performed. The voltage generated from the test equipment can damage the solid-state VFD components. Inspect the Control Center — Before working on any starter, shut off the chiller, open and tag all disconnects supplying power to the control center. Inspect the Heat Exchanger Tubes COOLER — Inspect and clean the cooler tubes at the end of the first operating season. Because these tubes have internal ridges, a rotary-type tube cleaning system is necessary to fully clean the tubes. Upon inspection, the tube condition will determine the scheduled frequency for cleaning, and will indicate whether liquid treatment is adequate in the chilled liquid/ brine circuit. Inspect the entering and leaving chilled liquid temperature sensors for signs of corrosion or scale. Replace the sensor if corroded or remove any scale if found. CONDENSER — Since this liquid circuit is usually an opentype system, the tubes may be subject to contamination and scale. Clean the condenser tubes with a rotary tube cleaning system at least once per year and more often if the liquid is contaminated. Inspect the entering and leaving condenser liquid sensors for signs of corrosion or scale. Replace the sensor if corroded or remove any scale if found. Before working on any VFD, shut off the chiller, open and tag all disconnects supplying power to the starter. After disconnecting input power to a VFD and before touching any internal components, wait 5 minutes for the DC bus capacitors to discharge, then check the voltage with a voltmeter. Failure to observe this warning could result in severe bodily injury or death. The disconnect on the front of the control center does not deenergize all internal circuits. Open all internal control power and remote disconnects before servicing the starter. 77 Relieve refrigerant pressure and add oil to the pumpout unit as follows: 1. Refer to Fig. 41. Close service valves 2 and 4. 2. Run the pumpout compressor in Automatic mode for one minute or until the vacuum switch is satisfied and compressor shuts off. 3. Move the pumpout selector switch to OFF. Pumpout compressor shell should now be under vacuum. 4. Oil can be added to the shell with a hand oil pump through the access valve in the compressor base. NOTE: Compressor access valve has a self-sealing fitting which will require a hose connection with a depressor to open. The motor leads must be disconnected from the VFD before an insulation test is performed. The voltage generated from the tester can damage the drive components. Never open isolating knife switches while equipment is operating. Electrical arcing can cause serious injury. Periodically vacuum or blow off accumulated debris on the internal parts with a high-velocity, low-pressure blower. Power connections on newly installed control centers may relax and loosen after a month of operation. Turn power off and retighten. Recheck annually thereafter. OPTIONAL PUMPOUT SAFETY CONTROL SETTINGS (Fig. 48) — The optional pumpout system high-pressure switch should open at 185 psig (1276 kPa) and closes automatically at 140 psig (965 kPa). Check the switch setting by operating the pumpout compressor and slowly throttling the pumpout condenser liquid. Ordering Replacement Chiller Parts — When ordering Carrier specified parts, the following information must accompany an order. • chiller model number and serial number • VFD model number and serial number (if applicable) • name, quantity, and part number of the part required • delivery address and method of shipment Loose power connections can cause voltage spikes, overheating, malfunctioning, or failures. Recalibrate Pressure Transducers — Once a year, the pressure transducers should be checked against a pressure gage reading. Check all transducers (up to 9): the oil pressure delta P transducers, discharge pressure transducer, the condenser pressure transducer, the cooler pressure transducer, and the optional liquidside pressure transducers (consisting of 4 optional flow devices: 2 cooler, 2 condenser). Note the evaporator and condenser pressure readings on the HEAT_EX screen (EVAPORATOR PRESSURE and CONDENSER PRESSURE). Attach an accurate set of refrigeration gages to the cooler and condenser Schrader fittings. Compare the two readings. If there is a difference in readings, the transducer can be calibrated as described in the Troubleshooting Guide section. Oil differential pressure (OIL PRESSURE DELTA P on the COMPRESS screen) should be close to zero whenever the compressor is off. The oil pressure delta P transducers indicate the difference between oil pressure leaving filter and oil sump pressure. CONTACTOR TERMINAL STRIP FUSES SWITCH Optional Pumpout System Maintenance — For pumpout unit compressor maintenance details, refer to the 19XR Positive Pressure Storage System Installation, Start-Up, and Service Instructions. OPTIONAL PUMPOUT COMPRESSOR OIL CHARGE — Use oil conforming to Carrier specifications for reciprocating compressor usage. Oil requirements are as follows: • HFC-134a ISO Viscosity . . . . . . . . . . . . . . . . .68 or 220 • Viscosity SSU 100 F (38 C) . . . . . . . . . . . . .300 or 1005 • Carrier Part Number . . PP23BZ-103 or PP23BZ110005 The total oil charge is 13 oz (0.5 L). a23-1569 TRANSFORMER CONTROL BOX (INTERIOR) Fig. 48 — Optional Pumpout System Controls TROUBLESHOOTING GUIDE Overview — The PIC III has many features to help the operator and technician troubleshoot a 23XRV chiller. • The ICVC shows the chiller’s actual operating conditions and can be viewed while the unit is running. • The ICVC default screen freezes when an alarm occurs. The freeze enables the operator to view the chiller conditions at the time of alarm. The STATUS screens continue to show current information. Once all alarms have been cleared (by correcting the problems and pressing the RESET softkey), the ICVC default screen returns to normal operation. Compressor oil is hygroscopic. Containers should remain tightly sealed in clean and dry environments to prevent moisture absorption from the air. Oil should be visible in the pumpout compressor sight glass both during operation and at shutdown. Always check the oil level before operating the pumpout compressor. Before adding or changing oil, relieve the refrigerant pressure through the access valves. 78 The resistance and corresponding temperature are listed in Table 17A or 17B. Check the resistance of both wires to ground. This resistance should be infinite. VOLTAGE DROP — The voltage drop across any energized sensor can be measured with a digital voltmeter while the control is energized. Table 17A or 17B lists the relationship between temperature and sensor voltage drop (volts dc measured across the energized sensor). Exercise care when measuring voltage to prevent damage to the sensor leads, connector plugs, and modules. Sensors should also be checked at the sensor plugs. Check the sensor wire at the sensor for 5 vdc if the control is powered on. CHECK SENSOR ACCURACY — Place the sensor in a medium of known temperature and compare that temperature to the measured reading. The thermometer used to determine the temperature of the medium should be of laboratory quality with 0.5º F (.25º C) graduations. The sensor in question should be accurate to within 2º F (1.2º C). See Fig. 3 for sensor locations. Temperature sensors are inserted into a thermowell in the refrigerant or liquid circuits. When installing a new sensor thermowell, apply a pipe sealant or thread sealant (RCD part number 56507) to the thermowell threads. Coat the temperature sensors with thermally conductive grease (RCD Part Number PP8024) before inserting into the thermowell. DUAL MOTOR TEMPERATURE SENSORS — For servicing convenience, there are 2 sensors on the motor temperature sensor. If one of the sensors is damaged, the other can be used by simply moving a wire. The number 2 terminal in the sensor terminal box is the common line. To use the second sensor, move the wire from the number 1 position to the number 3 position. • The CONTROL ALGORITHM STATUS screens (which include the CAPACITY, OVERRIDE, LL_MAINT, VFD_HIST, CUR_ALRM, LOADSHED, WSMDEFME, and OCCDEFCM screens) display information that helps to diagnose problems with chilled liquid temperature control, chilled liquid temperature control overrides, hot gas bypass, surge algorithm status, and time schedule operation. Refer to Table 14. • The CONTROL TEST screen under the SERVICE menu facilitates the proper operation and test of temperature sensors, pressure transducers, oil reclaim output, head pressure output, oil pump, liquid pumps, tower control, and other discrete on/off outputs while the compressor is stopped. It also has the ability to lock out the compressor and turn on liquid pumps for pumpout operation. The ICVC shows the temperatures and pressures required during these operations. • From other SERVICE tables, the operator or technician can access configured items, such as chilled liquid temperature resets, override set points, etc. • If an operating fault is detected, an alarm or alert message is generated and displayed on the ICVC default screen. A more detailed message — along with a diagnostic message — is also stored into the ALARM HISTORY and ALERT HISTORY tables. Refer to Tables 15 and 16. • Review the ALERT HISTORY table to view other less critical events and abnormal conditions which may have occurred. Compare timing of relevant alerts and alarms. Checking Display Messages — The first area to check when troubleshooting the 23XRV chiller is the ICVC display. If the alarm light is flashing, check the primary and secondary message lines on the ICVC default screen (Fig. 15). These messages will indicate where the fault is occurring. These messages contain the alarm message with a specified code. This code or state appears with each alarm and alert message. The ALARM and ALERT HISTORY tables on the ICVC SERVICE menu also contain a message to further expand on the fault condition. Note that the date format in these tables is MM/DD/YY. For a complete list of possible alarm messages, see Table 16. If the alarm light starts to flash while accessing a menu screen, press the EXIT softkey to return to the default screen to read the alarm message. The STATUS screen can also be accessed to determine where an alarm exists. A “C” to the right of a parameters value means there is a communications fault on that channel. Checking Pressure Transducers — There are as many as 9 pressure transducers on 23XRV chillers. They determine EVAPORATOR PRESSURE, CONDENSER PRESSURE, oil pressure leaving filter, oil sump pressure, DISCHARGE PRESSURE, and optional CHILLED LIQUID DELTA P and CONDENSER LIQUID DELTA P. The EVAPORATOR PRESSURE and CONDENSER PRESSURE transducers are also used by the PIC III to determine the refrigerant temperatures. The oil pressure delta P (oil pressure leaving filter – oil sump pressure) is calculated by the CCM. All pressure transducers should be calibrated prior to initial start-up. At high altitude locations, it is necessary to calibrate the transducers to ensure the proper refrigerant temperature/ pressure relationship. Each transducer is supplied with 5 vdc power from the CCM. If the power supply fails, a transducer voltage reference alarm (239) is declared. If the transducer reading is suspected of being faulty, check the TRANSDUCER VOLTAGE REF supply voltage. It should be 5 vdc ± .5 v displayed in CONTROL TEST under PRESSURE TRANSDUCERS. If the TRANSDUCER VOLTAGE REF. is correct, the transducer should be recalibrated or replaced. Also check that inputs on CCM J5-1 through J5-6 have not been grounded and are not receiving anything other than a 4 to 20 mA signal. Checking Temperature Sensors — Except for the motor temperature sensors, all temperature sensors are installed in thermowells. This eliminates the need to drain the refrigerant, oil, or liquid from the chiller to replace the sensor. All temperature sensors are thermistor-type sensors. This means that the resistance of the sensor varies with temperature. All sensors have the same resistance characteristics. RESISTANCE CHECK — Turn off the control power and, from the module, disconnect the terminal plug of the sensor in question. With a digital ohmmeter, measure sensor resistance between receptacles as designated by the wiring diagram. 79 softkey to finish the calibration. Pressures at high altitude locations must be compensated for, so the chiller temperature/pressure relationship is correct. COOLER CONDENSER PRESSURE TRANSDUCER AND OPTIONAL LIQUIDSIDE FLOW DEVICE CALIBRATION — Calibration can be checked by comparing the pressure readings from the transducer to an accurate refrigeration gage reading. These readings can be viewed or calibrated from the HEAT_EX screen on the ICVC. The transducer can be checked and calibrated at 2 pressure points. These calibration points are 0 psig (0 kPa) and between 25 and 250 psig (173 and 1724 kPa). To calibrate these transducers: 1. Shut down the compressor, cooler, and condenser pumps. NOTE: There should be no flow through the heat exchangers. 2. Disconnect the transducer in question from its Schrader fitting for cooler or condenser transducer calibration. For oil pressure delta P, the optional cooler and condenser liquid delta P, or flow device calibration, leave the transducer in place. NOTE: If the cooler or condenser vessels are at 0 psig (0 kPa) or are open to atmospheric pressure, the transducers can be calibrated for zero without removing the transducer from the vessel. 3. Access the HEAT_EX screen and view the particular transducer reading (the EVAPORATOR PRESSURE or CONDENSER PRESSURE parameter on the HEAT_EX screen). To calibrate oil pressure or liquidside flow device, view the particular reading (CHILLED LIQUID DELTA P and CONDENSER LIQUID DELTA P on the HEAT_EX screen, and OIL PRESSURE DELTA P on the COMPRESS screen). It should read 0 psi (0 kPa). If the reading is not 0 psi (0 kPa), but within ± 5 psi (35 kPa), the value may be set to zero by pressing the SELECT softkey while the appropriate transducer parameter is highlighted on the ICVC screen. Then press the ENTER softkey. The value will now go to zero. No high end calibration is necessary for OIL PRESSURE DELTA P, optional CHILLED LIQUID DELTA P or CONDENSER LIQUID DELTA P or for flow devices. The PIC III does not allow calibration if the transducer is too far out of calibration. In this case, a new transducer must be installed and re-calibrated. If calibration problems are encountered on the OIL PRESSURE DELTA P channel, sometimes swapping the oil pressure leaving filter and the oil sump pressure transducer locations will offset an adverse transducer tolerance stack up and allow the calibration to proceed. TRANSDUCER REPLACEMENT — Since the pressure transducers are mounted on Schrader-type fittings, there is no need to remove refrigerant from the vessel when replacing the transducers. Disconnect the transducer wiring by pulling up on the locking tab while pulling up on the weather-tight connecting plug from the end of the transducer. Do not pull on the transducer wires. Unscrew the transducer from the Schrader fitting. When installing a new transducer, do not use pipe sealer (which can plug the sensor). Put the plug connector back on the sensor and snap into place. Check for refrigerant leaks. Be sure to use a back-up wrench on the Schrader fitting whenever removing a transducer, since the Schrader fitting may back out with the transducer, causing a large leak and possible injury to personnel. Control Algorithms Checkout Procedure — One of the tables on the ICVC SERVICE menu is CONTROL ALGORITHM STATUS. The maintenance screens may be viewed from the CONTROL ALGORITHM STATUS table to see how a particular control algorithm is operating. These maintenance screens are very useful in helping to determine how the control temperature is calculated and for observing the reactions from load changes, control point overrides, hot gas bypass, surge prevention, etc. See Table 14. Table 14 — Control Algorithm Maintenance Screens If the transducer value is not within the calibration range, the transducer returns to the original reading. If the pressure is within the allowed range (noted above), check the voltage ratio of the transducer. To obtain the voltage ratio, divide the voltage (dc) input from the transducer (white wire to black wire) by the TRANSDUCER VOLTAGE REF supply voltage signal (displayed in CONTROL TEST menu in the PRESSURE TRANSDUCERS screen). The TRANSDUCER VOLTAGE REF can be measured across the positive (+ red) and negative (– black) leads of the transducer. For example, the condenser transducer reference voltage is measured at CCM terminals J2-4 (black) and J2-6 (red). The condenser transducer input voltage is measured at CCM terminals J2-4 (black) and J2-5 (clear or white). The input voltage to reference voltage ratio must be between 0.80 and 0.11 for the software to allow calibration. Pressurize the transducer until the ratio is within range, then attempt calibration again. 4. A high pressure point can also be calibrated between 25 and 250 psig (172.4 and 1723.7 kPa) by attaching a regulated 250 psig (1724 kPa) pressure (usually from a nitrogen cylinder). The high pressure point can be calibrated by accessing the appropriate transducer parameter on the HEAT_EX screen, highlighting the parameter, pressing the SELECT softkey, and then using the INCREASE or DECREASE softkeys to adjust the value to the exact pressure on the refrigerant gage. Press the ENTER SCREEN CAPACITY TITLE Capacity Control OVERRIDE Override Status LEAD/LAG Status VFD Alarm History Loadshed Status Current Alarm Status Liquid System Manager Status LL_MAINT VFD_HIST LOADSHED CUR_ALRM WSMDEFME OCCDEFCM Time Schedules Status HEAT_EX* HGBP Status DESCRIPTION This table shows all values used to calculate the chilled liquid control point. Details of all chilled liquid and VFD control override values. Indicates LEAD/LAG operation status. Displays VFD values at last fault. Displays Loadshed (Demand Limit) status. Displays current chiller alarms. The liquid system manager is a CCN module that can turn on the chiller and change the chilled liquid control point. This screen indicates the status of this system. The Local and CCN occupied schedules are displayed here to help the operator quickly determine whether the schedule is in the “occupied” mode or not. The hot gas bypass control algorithm status is viewed from this screen. All values related to this control are displayed. *The HEAT_EX screen is under the STATUS menu. 80 vessels are isolated. The Terminate Lockout feature ends the Pumpdown/Lockout after the pumpdown procedure is reversed and refrigerant is added. Control Test — The Control Test feature can check all the thermistor temperature sensors, pressure transducers, pumps and their associated flow devices, the oil reclaim output, the head pressure output, and other control outputs such as tower fans, VFD cooling solenoid, shut trip relay, oil heaters, alarm relay, and hot gas bypass. The tests can help to determine whether a switch is defective or if a pump relay is not operating, as well as other useful troubleshooting issues. During pumpdown operations, the pumps are energized to prevent freeze-up and the vessel pressures and temperatures are displayed. The Pumpdown/Lockout feature prevents compressor start-up when there is no refrigerant in the chiller or if the LEGEND FOR TABLES 15A-15J CCM CCN ICVC CHL PIC III VFD WSM — — — — — — — Chiller Control Module Carrier Comfort Network International Chiller Visual Controller Chilled Liquid Product Integrated Control III Variable Frequency Drive Water System Manager Table 15 — ICVC Primary and Secondary Messages and Custom Alarm/Alert Messages with Troubleshooting Guides A. MANUAL STOP PRIMARY MESSAGE MANUALLY STOPPED — PRESS TERMINATE PUMPDOWN MODE SECONDARY MESSAGE CCN OR LOCAL TO START TO SELECT CCN OR LOCAL SHUTDOWN IN PROGRESS SHUTDOWN IN PROGRESS COMPRESSOR UNLOADING COMPRESSOR DEENERGIZED ICE BUILD SHUTDOWN IN PROGRESS OPERATION COMPLETE RECYCLE RESTART PENDING B. READY TO START PRIMARY MESSAGE READY TO START IN XX MIN SECONDARY MESSAGE UNOCCUPIED MODE READY TO START IN XX MIN READY TO START IN XX MIN REMOTE CONTACTS OPEN STOP COMMAND IN EFFECT READY TO START IN XX MIN READY TO START IN XX MIN OCCUPIED MODE REMOTE CONTACTS CLOSED READY TO START IN XX MIN START COMMAND IN EFFECT READY TO START IN XX MIN READY TO START RECYCLE RESTART PENDING UNOCCUPIED MODE READY TO START REMOTE CONTACTS OPEN READY TO START STOP COMMAND IN EFFECT READY TO START READY TO START READY TO START OCCUPIED MODE REMOTE CONTACTS CLOSED START COMMAND IN EFFECT STARTUP INHIBITED LOADSHED IN EFFECT C. IN RECYCLE SHUTDOWN PRIMARY MESSAGE SECONDARY MESSAGE RECYCLE RESTART PENDING OCCUPIED MODE RECYCLE RESTART PENDING REMOTE CONTACTS CLOSED RECYCLE RESTART PENDING START COMMAND IN EFFECT RECYCLE RESTART PENDING ICE BUILD MODE PROBABLE CAUSE/REMEDY PIC III in OFF mode, press CCN or LOCAL softkey to start unit. Enter the CONTROL TEST table and select TERMINATE LOCKOUT to unlock compressor. Chiller unloading before shutdown due to soft/stop feature. Chiller compressor is being commanded to stop. Liquid pumps are deenergized within one minute. Chiller shutdown from Ice Build operation. Chiller is shutting down in recycle mode PROBABLE CAUSE/REMEDY Time schedule for PIC III is unoccupied. Chillers will start only when occupied. Remote contacts are open. Close contacts on Terminal Block TB1 to start. Chiller START/STOP on MAINSTAT manually forced to stop. Release force or send START force to start. Chiller timer counting down. Unit ready to start. Chiller timer counting down. Unit ready to start. Remote contact enabled and closed. The chiller will stop when the contacts are opened. Chiller START/STOP on MAINSTAT manually forced to start. Release force to start under normal control. Chiller in recycle mode. Time schedule for PIC III is unoccupied. Chiller will start when occupied. Make sure the time and date are correct. Change values in TIME AND DATE screen. Remote contacts have stopped the chiller. Close contact on Terminal Block TB1 to start. Chiller START/STOP on MAINSTAT manually forced to stop. Release point to start. Chiller timer count down complete, unit start will commence. Chiller timer count down complete. Unit ready for start. Chiller START/STOP on MAINSTAT has been manually forced to start. Chiller will start regardless of time schedule or remote contact status. CCN loadshed module commanding chiller to stop. PROBABLE CAUSE/REMEDY Unit in recycle mode, chilled liquid temperature is not sufficiently above set point to start. Unit in recycle mode, chilled liquid temperature is not sufficiently above set point to start. Chiller START/STOP on MAINSTAT manually forced to start, chilled liquid temperature is not sufficiently above set point to start. Chiller in ICE BUILD mode. Chilled liquid temperature is satisfied for ICE BUILD conditions. 81 Table 15 — ICVC Primary and Secondary Messages and Custom Alarm/Alert Messages with Troubleshooting Guides (cont) D. PRE-START ALERTS: These alerts are only declared after a start command is issued and only delay start-up. When alert is corrected, the start-up will continue. No reset is necessary. PRIMARY SECONDARY MESSAGE MESSAGE PRESTART STARTS LIMIT ALERT EXCEEDED ALARM MESSAGE PRIMARY CAUSE 100->Excessive compressor starts (8 in 12 hours) 101 PRESTART HIGH RECTIFIER ALERT TEMP 101->Rectifier Temperature [VALUE] exceeded limit of [LIMIT]*. 102 PRESTART HIGH MOTOR ALERT TEMPERATURE 102->Comp Motor Winding Temp [VALUE] exceeded limit of [LIMIT]*. 103 PRESTART HIGH DISCHARGE ALERT TEMP 103->Comp Discharge Temp [VALUE] exceeded limit of [LIMIT]*. 104 PRESTART LOW REFRIGERANT ALERT TEMP 104->Evaporator Refrig Temp [VALUE] exceeded limit of [LIMIT]*. 105 PRESTART LOW OIL ALERT TEMPERATURE 105->Oil Sump Temp [VALUE] exceeded limit of [LIMIT]*. 106 PRESTART HIGH CONDENSER ALERT PRESSURE 106->Condenser Pressure [VALUE] exceeded limit of [LIMIT]*. 107 PRESTART LOW LINE VOLTAGE ALERT 107->Percent Line Voltage [VALUE] exceeded limit of [LIMIT]*. 108 PRESTART HIGH LINE VOLTAGE ALERT 108->Percent Line Voltage [VALUE] exceeded limit of [LIMIT]*. 109 PRESTART HIGH INVERTER TEMP 109->Inverter Temperature ALERT [VALUE] exceeded limit of [LIMIT]*. STATE 100 ADDITIONAL CAUSE/REMEDY Depress the RESET softkey if additional start is required. Reassess start-up requirements. Check RECTIFIER TEMPERATURE in POWER screen. Check VFD refrigerant isolation valves. Check VFD power module cooling fan. Check RECTIFIER TEMP OVERRIDE in SETUP1 screen. See Table 5. Check COMP MOTOR WINDING TEMP in COMPRESS screen. Check motor temperature sensors for wiring and accuracy. Check motor cooling line for proper operation, or restrictions. Check for excessive starts within a short time span. Check MOTOR TEMP OVERRIDE in SETUP1 screen. See Table 5. Check COMP DISCHARGE TEMP in COMPRESS screen. Allow Compressor Discharge Sensor to cool. Check for Compressor Discharge sensor wiring and accuracy. Check for excessive starts. Check COMP DISCHARGE ALERT in SETUP1 screen. See Table 5. Check EVAPORATOR PRESSURE in HEATEX screen. Check Evaporator Pressure transducer wiring and accuracy. Check for low chilled fluid supply temperatures. Check refrigerant charge. Check REFRIG OVERRIDE DELTA T in SETUP1 screen. See Table 5. Check OIL SUMP TEMP in ICVC default screen. Check Oil Sump Temperature sensor wiring and accuracy. Check 1C oil heater contactor/relay and power. Check oil level and oil pump operation. Confirm that oil reclaim valve is closed when chiller is not running. See Table 5. Check oil heater element for carbon build-up. Check CONDENSER PRESSURE in HEATEX screen. Check Condenser Pressure transducer wiring and accuracy. Check for high condenser liquid temperatures. Check COND PRESS OVERRIDE in SETUP1 screen. See Table 5. Check Line Voltage in POWER screen Check voltage supply. Check voltage transformers. Consult power utility if voltage is low. Check FU1, FU2, and FU3 in the VFD. Check connectors on VFD Line Synch Printed Circuit Board. See Table 5. Check Line Voltage in POWER screen. Check voltage supply. Check power transformers. Consult power utility if voltage is high. See Table 5. Check INVERTER TEMPERATURE in POWER screen. Check VFD refrigerant isolation valves. Check VFD power module cooling fan. Check INVERTER TEMP OVERRIDE in SETUP1 screen. See Table 5. *[LIMIT] is shown on the ICVC as temperature, pressure, voltage, etc., predefined or selected by the operator as an override or an alert. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped. 82 Table 15 — ICVC Primary and Secondary Messages and Custom Alarm/Alert Messages with Troubleshooting Guides (cont) E. START-UP IN PROGRESS PRIMARY MESSAGE STARTUP IN PROGRESS SECONDARY MESSAGE OCCUPIED MODE REMOTE CONTACT CLOSED START COMMAND IN EFFECT CAUSE/REMEDY Chiller is starting. Time schedule is occupied (OCCUPIED? = YES). Chiller is starting. REMOTE CONTACTS OPTION is set to ENABLE. Remote contacts input on terminal block TB1 terminals 23 and 24 are closed. AUTORESTART IN PROGRESS OCCUPIED MODE AUTORESTART IN PROGRESS REMOTE CONTACT CLOSED AUTORESTART IN PROGRESS START COMMAND IN EFFECT Chiller is starting after power failure. Time schedule is occupied (OCCUPIED? = YES). Chiller is starting after power failure. REMOTE CONTACTS OPTION is set to ENABLE. Remote contacts input on terminal block TB1 terminals 23 and 24 are closed. Chiller is starting after power failure. CHILLER START/STOP on MAINSTAT manually forced to START. STARTUP IN PROGRESS STARTUP IN PROGRESS Chiller is starting. CHILLER START/STOP in MAINSTAT manually forced to START. F. NORMAL RUN PRIMARY MESSAGE SECONDARY MESSAGE CAUSE/REMEDY Auto chilled liquid reset active based on external input. ENABLE RESET TYPE =1. A non-zero temperature reset based on a 4-20 mA signal on RUNNING — RESET ACTIVE BY 4-20 mA SIGNAL CCM J5-3 and J5-4 is being added to the SETPOINT to determine the CONTROL POINT. See TEMP_CTL screen. Auto chilled liquid reset active based on external input. ENABLE RESET TYPE =2. A non-zero temperature reset based on the remote sensor signal on CCM J4-13 RUNNING — RESET ACTIVE REMOTE TEMP SENSOR and J4-14 is being added to the SETPOINT to determine the CONTROL POINT. See TEMP_CTL screen. Auto chilled liquid reset active based on cooler DT. ENABLE RESET TYPE =3. A non-zero temperature reset based on the difference between the ENTERING RUNNING — RESET ACTIVE CHL TEMP DIFFERENCE CHILLED LIQUID and LEAVING CHILLED LIQUID is being added to the SETPOINT to determine the CONTROL POINT. See TEMP_CTL screen. Default method of temperature control. ECL CONTROL OPTION = DSABLE. Chiller capacity is being controlled so the LEAVING CHILLED LIQUID temperature RUNNING — TEMP CONTROL LEAVING CHILLED LIQUID is being maintained within 1/2 of the CHILLED LIQUID DEADBAND on either side of the CONTROL POINT. See TEMP_CTL screen. Entering Chilled Liquid (ECL) control enabled. ECL CONTROL OPTION = ENABLE. Chiller capacity is being controlled so the ENTERING CHILLED RUNNING — TEMP CONTROL ENTERING CHILLED LIQUID LIQUID temperature is being maintained within 1/2 of the CHILLED LIQUID DEADBAND on either side of the CONTROL POINT. See TEMP_CTL screen. Ramp Loading based on LEAVING CHILLED LIQUID or ENTERING CHILLED TEMPERATURE RAMP LIQUID is in effect. PULLDOWN RAMP TYPE = 0. Capacity inhibit is in effect RUNNING — TEMP CONTROL LOADING because LEAVING CHILLED LIQUID or ENTERING CHILLED LIQUID has fallen below the ramping temperature pulldown setpoint. See RAMP_DEM screen. Ramp Loading based on PERCENT LINE CURRENT or PERCENT LINE BY DEMAND RAMP KILOWATTS is in effect. PULLDOWN RAMP TYPE = 0. Capacity inhibit is in RUNNING — DEMAND LIMITED LOADING effect because PERCENT LINE CURRENT or PERCENT LINE KILOWATTS has exceeded the ramping active demand limit. See RAMP_DEM screen. Actual demand has exceeded ACTIVE DEMAND LIMIT. 20mA DEMAND LIMIT BY LOCAL DEMAND OPTION is DISABLED. ACTIVE DEMAND LIMIT is set equal to BASED DEMAND RUNNING — DEMAND LIMITED SETPOINT LIMIT. PERCENT LINE CURRENT or PERCENT LINE KILOWATTS is greater than ACTIVE DEMAND LIMIT. Actual demand has exceeded ACTIVE DEMAND LIMIT. 20mA DEMAND LIMIT OPTION is ENABLED. ACTIVE DEMAND LIMIT is adjusted based on RUNNING — DEMAND LIMITED BY 4-20 mA SIGNAL 4-20 mA signal received on CCM J5-1 and J5-2. PERCENT LINE CURRENT or PERCENT LINE KILOWATTS is greater than ACTIVE DEMAND LIMIT. Actual demand has exceeded ACTIVE DEMAND LIMIT. Chiller CONTROL MODE = CCN. Value of ACTIVE DEMAND LIMIT is being forced by a CCN RUNNING — DEMAND LIMITED BY CCN SIGNAL device. PERCENT LINE CURRENT or PERCENT LINE KILOWATTS is greater than ACTIVE DEMAND LIMIT. Actual demand has exceeded ACTIVE DEMAND LIMIT. Chiller CONTROL MODE = CCN. Value of ACTIVE DEMAND LIMIT was set equal to PERCENT RUNNING — DEMAND LIMITED BY LOADSHED/REDLINE LINE CURRENT or PERCENT LINE KILOWATTS at the time a Redline command was received by the loadshed POC. PERCENT LINE CURRENT or PERCENT LINE KILOWATTS is greater than ACTIVE DEMAND LIMIT. See LOADSHED screen. RUNNING — TEMP CONTROL HOT GAS BYPASS HOT GAS BYPASS OPTION is set to ENABLE and HOT GAS BYPASS RELAY is ON. RUNNING — DEMAND LIMITED BY LOCAL SIGNAL ACTIVE DEMAND LIMIT has been manually forced on MAINSTAT screen. ICE BUILD OPTION is set to ENABLE and chiller is running under Ice Build RUNNING — TEMP CONTROL ICE BUILD MODE temperature control. Actual demand has exceeded ACTIVE DEMAND LIMIT. Capacity inhibit is active RUNNING — DEMAND LIMITED MOTOR LOAD CURRENT because PERCENT LOAD CURRENT is greater than 100%. Actual demand has exceeded ACTIVE DEMAND LIMIT. Capacity inhibit is active RUNNING — DEMAND LIMITED VFD LINE CURRENT because PERCENT LINE CURRENT exceeds 100%. 83 Table 15 — ICVC Primary and Secondary Messages and Custom Alarm/Alert Messages with Troubleshooting Guides (cont) G. NORMAL RUN WITH OVERRIDES STATE PRIMARY MESSAGE SECONDARY MESSAGE ALARM MESSAGE PRIMARY CAUSE 120 RUN CAPACITY LIMITED HIGH CONDENSER PRESSURE 120->Condenser Pressure [VALUE] exceeded limit of [LIMIT]*. 121 RUN CAPACITY LIMITED HIGH MOTOR TEMPERATURE 121->Comp Motor Winding Temp [VALUE] exceeded limit of [LIMIT]*. 122 RUN CAPACITY LIMITED LOW EVAP REFRIG TEMP 122->Evaporator Refrig Temp [VALUE] exceeded limit of [LIMIT]*. 123 RUN CAPACITY LIMITED HIGH RECTIFIER TEMP 123->Rectifier Temperature [VALUE] exceeded limit of [LIMIT]* 124 RUN CAPACITY LIMITED MANUAL SPEED CONTROL 125 RUN CAPACITY LIMITED HIGH INVERTER TEMP 126 RUN CAPACITY OVERRIDE COMP MIN SPEED IN EFFECT 127 RUN CAPACITY OVERRIDE COMP MAX SPEED LIMITED 125->Inverter Temperature [VALUE] exceeded limit of [LIMIT]* ADDITIONAL CAUSE/REMEDY Check for high condenser liquid temperatures. Check COND PRESS OVERRIDE setting in SETUP1. Check motor cooling lines. Check for closed valves. Check COMP MOTOR TEMP OVERRIDE setting in SETUP1. Check REFRIG OVERRIDE DELTA T setting in SETUP1 screen. Check refrigerant charge. Check for low entering cooler temperatures. Check VFD refrigerant isolation valves. Check VFD refrigerant cooling solenoid valve. Check RECTIFIER TEMP OVERRIDE in SETUP1 screen. TARGET VFD SPEED in COMPRESS screen is forced to a fixed value. Check VFD refrigerant isolation valves. Check VFD refrigerant cooling solenoid valve. Check INVERTER TEMP OVERRIDE in SETUP1 screen. TARGET VFD SPEED is clamped to COMP MINIMUM SPEED due to oil viscosity. TARGET VFD SPEED is clamped to VFD MAXIMUM SPEED. Check VFD MAXIMUM SPEED in SETUP2 screen. *[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control has recorded at the time of the fault condition. H. OUT-OF-RANGE SENSOR ALARMS STATE PRIMARY MESSAGE SECONDARY MESSAGE ALARM MESSAGE PRIMARY CAUSE 260 CHILLED SENSOR FAULT LEAVING LIQUID 260->Sensor Fault: Check Leaving Chilled Liquid Sensor 261 CHILLED SENSOR FAULT ENTERING LIQUID 261->Sensor Fault: Check Entering Chilled Liquid Sensor 262 SENSOR FAULT CONDENSER PRESSURE 262->Sensor Fault: Check Condenser Pressure Sensor 263 SENSOR FAULT EVAPORATOR PRESSURE 263->Sensor Fault: Check Evaporator Pressure Sensor 264 PRESS SENSOR SENSOR FAULT OIL FAULT 264->Sensor Fault: Check Oil Pressure Delta P Sensor 84 ADDITIONAL CAUSE/REMEDY Check sensor resistance or voltage drop against Table 17A or 17B. Check for proper wiring between Leaving Chilled Liquid Temperature sensor and CCM. Check for grounded sensor lead. See Table 5. Check sensor resistance or voltage drop against Table 17A or 17B. Check for proper wiring between Entering Chilled Liquid Sensor and CCM. Check for grounded sensor lead. See Table 5. Confirm that 5V Reference voltage is available on CCM. Check sensor voltage drop. Check for proper wiring between Condenser Pressure Sensor and CCM. Check for grounded sensor lead. Check for condensation inside of pressure sensor connector. See Table 5. Confirm that 5V Reference voltage is available on CCM. Check sensor voltage drop. Check for proper wiring between Evaporator Pressure Sensor and CCM. Check for grounded sensor lead. Check for condensation inside of pressure sensor connector. See Table 5. Confirm that 5V Reference voltage is available on CCM. Check sensor voltage drops. Check for proper wiring between Oil Sump Pressure and Oil Pressure Leaving Filter Sensors and CCM. Check for grounded sensor lead. Check for condensation inside of pressure sensor connectors. See Table 5. Table 15 — ICVC Primary and Secondary Messages and Custom Alarm/Alert Messages with Troubleshooting Guides (cont) H. OUT-OF-RANGE SENSOR ALARMS (cont) STATE PRIMARY MESSAGE SECONDARY MESSAGE ALARM MESSAGE PRIMARY CAUSE 266 SENSOR FAULT OIL SUMP TEMP 266->Sensor Fault: Check Oil Sump Temp Sensor 267 DISCHARGE SENSOR FAULT COMP TEMP 267->Sensor Fault: Check Comp Discharge Temp Sensor 268 SENSOR FAULT CHILLED LIQUID FLOW 268->Sensor Fault: Check Chilled Liquid Delta P Sensor 269 SENSOR FAULT COND LIQUID FLOW 269->Sensor Fault: Check Cond Liquid Delta P Sensor 270 REFRIG SENSOR FAULT EVAP LIQUID TEMP 270->Sensor Fault: Check Evap Refrig Liquid Temp Sensor 271 SENSOR FAULT VAPORIZER TEMP 271->Sensor Fault: Check Vaporizer Temp Sensor 272 SENSOR FAULT DISCHARGE PRESSURE 272->Sensor Fault: Check Discharge Pressure Sensor 85 ADDITIONAL CAUSE/REMEDY Check sensor resistance or voltage drop against Table 17A or 17B. Check for proper wiring between Oil Sump Pressure Sensor and CCM. Check for grounded sensor lead. See Table 5. Check sensor resistance or voltage drop against Table 17A or 17B. Check for proper wiring between sensor and CCM. Check for grounded sensor lead. See Table 5. Check for 4.3 kohm load resistor on J3-14 and J3-15. Check for jumper between J3-17 and J3-18. Confirm that 5V Reference voltage is available on CCM. See Table 5. Check sensor voltage drops. Check for proper wiring between optional Entering Chilled Liquid Pressure and Leaving Chilled Liquid Pressure Sensors and CCM. Check for grounded sensor lead. Check for condensation inside of optional pressure sensor connectors. J3-17 to J3-18 jumper must be replaced with a 4.3 kohm resistor if optional flow switch is installed, see Certified Prints. Check for 4.3 kohm load resistor on J3-20 and J3-21. Check for jumper between J3-23 and J3-24. Confirm that 5V Reference voltage is available on CCM. See Table 5. Check sensor voltage drops. Check for proper wiring between optional Entering Condenser Liquid Pressure and Leaving Condenser Liquid Pressure Sensors and CCM. Check for grounded sensor lead. Check for condensation inside of optional pressure sensor connectors. J3-17 to J3-18 jumper must be replaced with a 4.3 kohm resistor if optional flow switch is installed, see Certified Prints. Check sensor resistance or voltage drop against Table 17A or 17B. Check for proper wiring between Evaporator Refrigerant Liquid Temperature Sensor and CCM. Check for grounded sensor lead. See Table 5. Check sensor resistance or voltage drop against Table 17A or 17B. Check for proper wiring between Vaporizer Temperature Sensor and CCM. Check for grounded sensor lead. See Table 5. Confirm that 5V Reference voltage is available on CCM. Check sensor voltage drop. Check for proper wiring between Compressor Discharge Pressure Sensor and CCM. Check for grounded sensor lead. Check for condensation inside of pressure sensor connector. See Table 5. Table 15 — ICVC Primary and Secondary Messages and Custom Alarm/Alert Messages with Troubleshooting Guides (cont) I. CHILLER PROTECTIVE LIMIT FAULTS STATE PRIMARY MESSAGE SECONDARY MESSAGE RECTIFIER POWER FAULT INVERTER POWER FAULT ALARM MESSAGE PRIMARY CAUSE 200->Rectifier Power Fault: Check VFD Status 201->Inverter Power Fault: Check VFD Status 200 PROTECTIVE LIMIT 201 PROTECTIVE LIMIT 202 PROTECTIVE LIMIT MOTOR AMPS NOT SENSED 202->Motor Amps Not Sensed — Average Load Current [VALUE] 203 FAILURE TO START MOTOR ACCELERATION FAULT 203->Motor Acceleration Fault — Average Load Current [VALUE] 204 FAILURE TO STOP VFD SHUTDOWN FAULT 204->VFD Shutdown Fault: Check Inverter Power Unit 205 PROTECTIVE LIMIT HIGH DC BUS VOLTAGE 205->High DC Bus Voltage: [VALUE] exceeded limit of [LIMIT]* 206 PROTECTIVE LIMIT VFD FAULT 206->VFD Fault Code: [VALUE]; Check VFD Fault Code List 207 PROTECTIVE LIMIT HIGH CONDENSER PRESSURE 207->High Cond Pressure trip. [VALUE] exceeded Switch Trippoint. 208 PROTECTIVE LIMIT 208->Percent Load Current EXCESSIVE MOTOR [VALUE] exceeded limit of AMPS [LIMIT]*. 209 PROTECTIVE LIMIT LINE CURRENT IMBALANCE 209->Line Current Imbalance: Check VFD Fault History for Values. 210 PROTECTIVE LIMIT LINE VOLTAGE DROPOUT 210->Single Cycle Line Voltage Dropout 211 PROTECTIVE LIMIT HIGH LINE VOLTAGE 211->High Percent Line Voltage [VALUE] 212 PROTECTIVE LIMIT LOW LINE VOLTAGE 212->Low Percent Line Voltage [VALUE] 213 PROTECTIVE LIMIT VFD MODULE RESET 213->VFD Module Power-On Reset When Running 214 PROTECTIVE LIMIT POWER LOSS 214->Control Power Loss When Running ADDITIONAL CAUSE/REMEDY Check VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. Check VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. Check main circuit breaker for trip. Check VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. Check MOTOR RATED LOAD AMPS setting in VFD_CONF screen. See Table 5. Check starter for proper operation. Reduce Condenser pressure if possible. Check VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. Check MOTOR RATED LOAD AMPS setting in VFD_CONF screen. See Table 5. Check VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. See Table 5. Check DC BUS VOLTAGE and VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. Check DC BUS VOLTAGE and VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. Check for electrical continuity across High Pressure Switch. Check connections at VFD A33 Gate Kill Terminals. Check for high condenser water temperatures, low water flow, fouled tubes. Check for division plate/gasket bypass. Check for noncondensables in refrigerant. Check Condenser Pressure transducer wiring and accuracy. See Table 5. Check Load Currents in VFD_HIST screen. Check MOTOR RATED LOAD AMPS setting in VFD_CONF screen. Check condenser water flow. See Table 5. Check LINE CURRENTs and VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. Check LINE CURRENT IMBALANCE settings in VFD_CONF screen. Check power distribution bus. Consult power company. See Table 5. Check LINE VOLTAGE and VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. Check SINGLE CYCLE DROPOUT setting in VFD_CONF screen. See Table 5. Check LINE VOLTAGE and VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. See Table 5. Check distribution bus. Consult power company. Check LINE VOLTAGE and VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. See Table 5. Check distribution bus. Consult power company. Check LINE VOLTAGE and VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. Check LINE VOLTAGE in VFD_HIST screen. Check control power voltage on ICVC terminal J1. See Table 5. Check distribution bus. Consult power company. *[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped. 86 Table 15 — ICVC Primary and Secondary Messages and Custom Alarm/Alert Messages with Troubleshooting Guides (cont) I. CHILLER PROTECTIVE LIMIT FAULTS (cont) STATE PRIMARY MESSAGE SECONDARY MESSAGE ALARM MESSAGE PRIMARY CAUSE 215 PROTECTIVE LIMIT LOW DC BUS VOLTAGE 215->Low DC Bus Voltage: [VALUE] exceeded limit of [LIMIT]* 216 PROTECTIVE LIMIT LINE VOLTAGE IMBALANCE 216->Line Voltage Imbalance; Check VFD Fault History for Values. 217 PROTECTIVE LIMIT MOTOR OVERLOAD TRIP 217->Motor Overload Trip; Check VFD configurations 218 PROTECTIVE LIMIT VFD RECTIFIER OVERTEMP 218->VFD Rectifier Temp Exceeded: Check Cooling and VFD Config. 219 PROTECTIVE LIMIT VFD INVERTER OVERTEMP 219->VFD Inverter Temp Exceeded: Check Cooling and VFD Config. 220 PROTECTIVE LIMIT GROUND FAULT 220->Ground Fault Trip; Check Motor and Current Sensors 221 PROTECTIVE LIMIT MOTOR ROTATION REVERSED 221->Motor Rotation Reversed: Check Wiring from VFD to Motor 222 PROTECTIVE LIMIT LINE FREQUENCY TRIP 222->Line Frequency [VALUE]: Check Power Supply. 223 WITH VFD LOSS OF COMMUNICATION GATEWAY MODULE 224 PROTECTIVE LIMIT VFD COMMUNICATIONS FAULT 224->Loss of DPI Comm with VFD Gateway: Check VFG to VFD Comm. 225 PROTECTIVE LIMIT MOTOR CURRENT IMBALANCE 225->Motor Current Imbalance: Check VFD Fault History for Values. 226 PROTECTIVE LIMIT LINE PHASE REVERSAL 226->Line Phase Reversal: Check Line Phases 227 PROTECTIVE LIMIT OIL PRESS SENSOR FAULT 227->Oil Pressure Delta P [VALUE] (Pump Off): Check Pump/Transducers 223->Loss of SIO Comm with VFD Gateway: Check VFG Module and Power ADDITIONAL CAUSE/REMEDY Check DC BUS VOLTAGE and VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. See Table 5. Check LINE VOLTAGE and VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. See Table 5. Check power distribution bus. Check LINE VOLTAGE IMBALANCE settings in VFD_CONF screen. Check LOAD CURRENT and VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODEs in Table 16. Check MOTOR RATED LOAD AMPS in VFD_CONF screen. See Table 5. Check VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. See Table 5. Check VFD refrigerant isolation valves and solenoid valve. Check cooling fan on bottom of VFD power module. Configure RECTIFIER TEMP OVERRIDE in SETUP1 screen. Check VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. See Table 5. Check VFD refrigerant isolation valves and solenoid valve. Check cooling fan on bottom of VFD power module. Configure INVERTER TEMP OVERRIDE in SETUP1 screen. Check GROUND FAULT CURRENT and VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. See Table 5. Check if discharge pressure sensor is out of range in CONTROL TEST screen. See Table 5. Check resistor between CCM J3-7 and J3-8. Check LINE FREQUENCY and VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. See Table 5. Check SIO communication harness between the Gateway and the J7 CCM connector. Check status lights on CCM and Gateway per Fig. 50 and 52. Check ribbon cable and connectors between the Gateway and the VFD DPI Communications Interface Board per Fig. 50 and 52. Check LOAD CURRENT and VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. See Table 5. Check power distribution bus. Check MOTOR CURRENT IMBALANCE settings in VFD_CONF screen. Check VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. See Table 5. Select OIL PRESSURE DELTA P in COMPRESS screen to calibrate sensors. Check OIL SUMP PRESSURE and OIL PRESSURE LEAVING FILTER pressure transducer wiring and voltage drop. Check oil line isolation valves. *[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped. 87 Table 15 — ICVC Primary and Secondary Messages and Custom Alarm/Alert Messages with Troubleshooting Guides (cont) I. CHILLER PROTECTIVE LIMIT FAULTS (cont) STATE PRIMARY MESSAGE SECONDARY MESSAGE ALARM MESSAGE PRIMARY CAUSE 228 PROTECTIVE LIMIT LOW OIL PRESSURE 228->Low Operating Oil Pressure [VALUE]: Check Oil Pump and Filter 229 PROTECTIVE LIMIT LOW CHILLED LIQUID FLOW 229->Low Chilled Liquid Flow; Check Switch/Delta P Config & Calibration 230 PROTECTIVE LIMIT LOW CONDENSER LIQUID FLOW 230->Low Condenser Liquid Flow; Check Switch/Delta P Config & Calibration 231 PROTECTIVE LIMIT HIGH DISCHARGE TEMP 231->Comp Discharge Temp [VALUE] Exceeded Limit of [LIMIT]* 232 PROTECTIVE LIMIT LOW REFRIGERANT 232->Evaporator Refrig Temp [VALUE] exceeded limit of TEMP [LIMIT]*. 233 PROTECTIVE LIMIT HIGH MOTOR TEMPERATURE 233->Comp Motor Winding Temp VALUE] exceeded limit of [LIMIT]*. ADDITIONAL CAUSE/REMEDY Check oil level in Oil Sump sight glasses. Check OIL SUMP PRESSURE and OIL PRESSURE LEAVING FILTER transducer wiring and voltage drop. See Table 5. Check power supply to pump and pump operation. Look for oil flow through vaporizer drain sight glass when chiller is running. Check for partially closed isolation valves. Check oil filter. Check for foaming oil at start-up in oil sump. Check OIL PRESSURE DELTA P transducer calibration in COMPRESS screen. Check vaporizer and oil sump heaters and contactors. Perform Pump Control Test in CONTROLS TEST screen. Check EVAP REFRIG LIQUID TEMP and LEAVING CHILLER LIQUID sensor accuracy and wiring. See Table 5. Check chilled liquid valves, pumps, and strainers. Check EVAP REFRIG TRIPPOINT, EVAP APPROACH ALERT, and EVAP FLOW DELTA P CUTOUT, and LIQUID FLOW VERIFY TIME settings. Check optional liquid flow switches or liquid delta P transducer calibration. Perform Pump Control Test in CONTROLS TEST screen. See Table 5. Check CONDENSER PRESSURE and LEAVING COND LIQUID sensors accuracy and wiring. Check condenser liquid valves, pumps, and strainers. Check COND APPROACH ALERT, COND PRESS OVERRIDE, LIQUID FLOW VERIFY TIME, and COND FLOW DELTA P CUTOUT settings. Check optional liquid flow switches or liquid delta P transducer calibration. Check discharge isolation valve position. See Table 5. Check COMP DISCHARGE TEMP sensor resistance or voltage drop. Check for proper COMP DISCHARGE TEMP sensor wiring. Check for proper condenser flow and temperature. Check for fouled tubes, plugged liquid strainers or noncondensables in the system. Alarm declared when chiller is running, see Table 5. Check Cooler Refrig Liquid Line Isolation Valve Position. Check for proper refrigerant charge. Check Condenser Float Valve operation, check if CHILLED LIQUID APPROACH decreases when CONDENSER PRESSURE increases. Check EVAP APPROACH ALERT setting. Check for proper fluid flow and temperature against chiller design conditions. Check COMP MOTOR WINDING TEMP sensor wiring and accuracy. See Table 5. Check motor cooling line for proper operation, restrictions, and isolation valve position. Check motor cooling filter/drier and look for refrigerant flow through motor cooling sight glass. Check for excessive starts within a short time span. The high motor temperature switch in the windings or the motor temperature sensor circuit is open if COMP MOTOR WINDING TEMP = 245 F(118 C). *[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped. 88 Table 15 — ICVC Primary and Secondary Messages and Custom Alarm/Alert Messages with Troubleshooting Guides (cont) I. CHILLER PROTECTIVE LIMIT FAULTS (cont) STATE 234 235 236 237 238 239 240 241 242 243 244 PRIMARY MESSAGE SECONDARY MESSAGE ALARM MESSAGE PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY Check for low oil level in oil sump sight glass. See Table 5. Refrigerant has not been adequately removed LOW OIL 234->Low Prelube Oil Press [VALUE]: from the oil if bubbling can be observed through PROTECTIVE LIMIT PRESSURE Check Oil Pump & Filter oil sump sight glass. Check vaporizer and oil sump heaters and contactors. Check OIL PRESS VERIFY TIME. Check for high condenser liquid temperatures against chiller design conditions. See Table 5. Check Condenser Approach in HEATEX screen. Check for low liquid flow, plugged liquid strainers, 235->Condenser Pressure HIGH CONDENSER [VALUE] exceeded limit of and fouled tubes. Check for division plate/gasket PROTECTIVE LIMIT PRESSURE bypass. [LIMIT]*. Check for noncondensables in refrigerant. Check CONDENSER PRESSURE transducer wiring and accuracy. Configure COND PRESS OVERRIDE in SETUP1 screen. CCN has signaled the chiller to stop. EMERGENCY STOP in the MAINSTAT CCN OVERRIDE 236->CCN Emergency/Override screen has been set to EMSTOP. PROTECTIVE LIMIT STOP Stop Reset and restart when ready. If the signal was sent by the ICVC, release the stop signal on the STATUS01 table. Spare safety input has tripped or factory-installed SPARE SAFETY PROTECTIVE LIMIT 237->Spare Safety Device jumper is not present between terminals 19 and DEVICE 20 on the Low Voltage Field Wiring Terminal Strip. Check condenser liquid flow and temperatures against chiller design conditions. See Table 5. COMPRESSOR 238->Compressor Stall: PROTECTIVE LIMIT Check STALL TIME PERIOD and STALL % MOTOR STALL Check Compressor and Motor AMPs settings. Check for excessive refrigerant charge and oil loss. Check If CCM PRESSURE TRANSDUCER VOLTAGE REFERENCE is less than 4.5 V in CONTROLS TEST screen. Confirm PRESSURE TRANSDUCER VOLTAGE REFERENCE across a CCM Pressure Transducer 239->Transducer Voltage Ref (e.g., CCM J3-1 to J3-3). TRANSDUCER PROTECTIVE LIMIT [VALUE] exceeded limit of Confirm that none of the transducers have VOLTAGE FAULT [LIMIT]*. been shorted to ground. Look for changes in voltage if customer wiring to CCM J5-1 through J5-6 and J8-1 to J8-2 are temporarily removed. Check for 24 VAC across CCM terminals J1-1 and J1-2. ICVC and Gateway software compatibility numbers 240->VFD Gateway Compatibility do not match. See ICVC SOFTWARE PART # in COMPATIBILITY VFD GATEWAY Conflict: Check VFG/ICVC ICVC CONFIGURATION SCREEN. CONFLICT Versions See VFD GATEWAY VERSION # in VFD_STAT screen. Check LOAD CURRENT and VFD FAULT RECTIFIER 241->Rectifier Overcurrent Fault: PROTECTIVE LIMIT CODE in VFD_HIST screen. OVERCURRENT Check VFD Status See VFD FAULT CODES in Table 16. Check wiring and connectors between CCM terminal J6 and ICVC terminal J7. 242->Loss of Communication Check CCM status lights. WITH CCM LOSS OF COMMUNICATION With CCM: Check Comm. Check for 24V control power to CCM J1-1 MODULE Connectors and J1-2. Confirm that all CCM SW1 switches are in the “off” position. Alarm declared at power up and after chiller is shutdown, see Table 5. Check EVAPORATOR PRESSURE transducer. 243->Evaporator Refrig Temp EVAP PRESS/TEMP Check EVAP REFRIG TRIP POINT. POTENTIAL FREEZE-UP [VALUE] exceeded limit of TOO LOW Check for proper refrigerant charge. [LIMIT]*. Check float operation. Check for proper evaporator fluid flow and temperature. Alarm declared when chiller in shutdown, COND PRESS/TEMP 244->Condenser Refrig Temp see Table 5. POTENTIAL FREEZE-UP [VALUE] exceeded limit of TOO LOW Check CONDENSER PRESSURE transducer. [LIMIT]*. Check CONDENSER FREEZE POINT setting. *[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped. 89 Table 15 — ICVC Primary and Secondary Messages and Custom Alarm/Alert Messages with Troubleshooting Guides (cont) I. CHILLER PROTECTIVE LIMIT FAULTS (cont) PRIMARY MESSAGE SECONDARY MESSAGE 245 PROTECTIVE LIMIT VFD SPEED OUT OF RANGE 245->Actual VFD Speed exceeded limit of Target VFD Speed ± 10%]*. 246 PROTECTIVE LIMIT INVERTER OVERCURRENT 246->Inverter Overcurrent Fault: Check VFD Status 247 PROTECTIVE LIMIT VFD START INHIBIT 247->VFD Start Inhibit: Check VFD Diagnostic Parameters 212/214 STATE ALARM MESSAGE PRIMARY CAUSE 248 PROTECTIVE LIMIT SPARE TEMPERATURE #1 248->Spare Temperature #1 [VALUE] exceeded limit of [LIMIT]*. 249 PROTECTIVE LIMIT SPARE TEMPERATURE #2 249->Spare Temperature #2 [VALUE] exceeded limit of [LIMIT]*. 250 PROTECTIVE LIMIT REFRIGERANT LEAK SENSOR 250->Refrigerant Leak Sensor ppm [VALUE] exceeded Limit of [LIMIT]* 251 PROTECTIVE LIMIT VFD CONFIG CONFLICT 251->VFD Config Conflict; Verify & Save VFD Config Data to Reset 253 PROTECTIVE LIMIT VFD CHECKSUM ERROR 253->Checksum Error: Press Reset to Restore Configuration 254 PROTECTIVE LIMIT VFD DEW PREVENTION 254->VFD Dew Prevention - VFD Coolant too Cold, Check Solenoid and Cond T 255 PROTECTIVE LIMIT INDUCTOR OVERTEMP 255->Inductor Overtemp Trip - Check Temp Switch and Cooling Fans 256 VFD GATEWAY COMPATIBILITY CONFLICT 256->VFD Gateway Compatibility Conflict: Check VFG/VFD Versions ADDITIONAL CAUSE/REMEDY Check if ACTUAL VFD SPEED exceeds VFD SPEED OUTPUT ±10% in COMPRESS or CAPACITY screen. See Table 5. Check for VFD FAULT CODES in VFD_HIST screen. Check LINE CURRENTs and VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. Check VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. Check component that SPARE TEMPERATURE #1 is monitoring. See Table 5. Check SPARE TEMPERATURE #1 settings in SETUP1 screen. Check SPARE TEMPERATURE #1 sensor resistance or voltage drop on CCM terminals J4-25 and J4-26. Check SPARE TEMPERATURE #1 sensor wiring. Check component that SPARE TEMPERATURE #2 is monitoring. See Table 5. Check SPARE TEMPERATURE #2 settings in SETUP1 screen. Check SPARE TEMPERATURE #2 sensor resistance or voltage drop on CCM terminals J4-27 and J4-28. Check SPARE TEMPERATURE #2 sensor wiring. REFRIGERANT LEAK OPTION is enabled. The refrigerant leak detector output wired to CCM terminals J5-5 and J5-6 has reached the alarm threshold (PPM AT 20 MA). See Table 5. Check for leaks. Check leak detector. Check REFRIGERANT LEAK OPTION, REFRIG LEAK ALARM PPM and PPM AT 20 MA settings in OPTIONS screen. VFD Parameters stored in Gateway and ICVC are not consistent. Enter VFD_CONF screen and check settings stored in ICVC against Machine Electrical Data Nameplate. If parameter values are unacceptable, exit VFD_CONF by pressing cancel. Re-enter VFD_CONF screen and check settings uploaded from Gateway against Machine Electrical Data Nameplate. Press SAVE before exiting VFD_CONF. VFD inverter or rectifier checksum must be regenerated. Check VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 17. Press RESET softkey on ICVC to restore VFD configuration. Reducing VFD COOLANT FLOW to 0% did not adequately increase VFD COLDPLATE TEMP. Check HUMIDITY SENSOR INPUT on CCM J3-7, J3-9 and J4-10 and RELATIVE HUMIDITY in POWER or CONTROLS TEST screen. Check humidity sensor wiring on CCM. Check VFD refrigerant cooling solenoid operation. Increase Entering Condenser Liquid Temperature. Reduce humidity surrounding chiller. Check that VFD A34 NTC cold plate thermocouple is wired to VFD A12 AC LINE I/O card TB1-19 and TB1-20. Temperature switch in VFD inductor has opened. Middle Control Center door must be fully closed to properly route airflow around VFD inductors. Check wiring to inductor temperature switch. Check inductor cooling fan operation. Check for inductor cooling fan airflow obstructions. Check VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. VFD INVERTER VERSION # and/or VFD RECTIFIER VERSION # are not compatible with the GATEWAY VERSION #. Check software version numbers in VFD_STAT screen. *[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped. 90 Table 15 — ICVC Primary and Secondary Messages and Custom Alarm/Alert Messages with Troubleshooting Guides (cont) J. CHILLER ALERTS STATE PRIMARY MESSAGE SECONDARY MESSAGE ALARM MESSAGE PRIMARY CAUSE 140 SENSOR ALERT LEAVING COND LIQUID TEMP 140->Sensor Fault: Check Leaving Cond Liquid Sensor 141 SENSOR ALERT ENTERING COND LIQUID TEMP 141->Sensor Fault: Check Entering Cond Liquid Sensor 142 SENSOR ALERT LOW OIL PRESSURE 142->Oil Pressure Delta P [VALUE] Exceeded Limit of [LIMIT] 143 AUTORESTART PENDING LINE CURRENT IMBALANCE 143->Line Current Imbalance: Check VFD Fault History for Values 144 AUTORESTART PENDING LINE VOLTAGE DROP OUT 144->Single Cycle Line Voltage Dropout 145 AUTORESTART PENDING HIGH LINE VOLTAGE 145>High Percent Line voltage [VALUE] 146 AUTORESTART PENDING LOW LINE VOLTAGE 146->Low Percent Line voltage [VALUE] 147 AUTORESTART PENDING VFD MODULE RESET 147->VFD Module Power-On Reset When Running 148 AUTORESTART PENDING POWER LOSS 148->Control Power-Loss When Running 149 AUTORESTART PENDING LOW DC BUS VOLTAGE 149->Low DC Bus Voltage: [VALUE] Exceeded Limit of [LIMIT]* ADDITIONAL CAUSE/REMEDY Temperature sensor reading out of range. Check LEAVING COND LIQUID TEMP sensor resistance or voltage drop at CCM. Check for grounded sensor leads. Check for proper wiring. See Table 5. Temperature sensor reading out of range. Check ENTERING COND LIQUID TEMP sensor resistance or voltage drop at CCM. Check for grounded sensor leads. Check for proper wiring. See Table 5. Check for partially or closed oil line isolation valves. Check oil filter. Check oil level. Check Oil Pressure Leaving Filter and Oil Sump Pressure transducer wiring and OIL PRESSURE DELTA P accuracy. See Table 5. Chiller automatically restarting - AUTORESTART OPTION is enabled. Power loss has been detected in any phase. Check LINE CURRENTs and VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. Check LINE CURRENT IMBALANCE settings in VFD_CONF screen. See Table 5. Check power distribution bus. Consult power company. Chiller is automatically restarting AUTORESTART OPTION is enabled. A drop in line voltage has been detected within 2 voltage cycles. Check LINE VOLTAGE and VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. See Table 5. Check SINGLE CYCLE DROPOUT setting in VFD_CONF screen. Chiller is automatically restarting AUTORESTART OPTION is enabled. Check LINE VOLTAGE and VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. See Table 5. Check distribution bus. Consult power company. Chiller is automatically restarting AUTORESTART OPTION is enabled. Check LINE VOLTAGE and VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. See Table 5. Check distribution bus. Consult power company. Chiller is automatically restarting AUTORESTART OPTION is enabled. VFD Module has detected a hardware fault and has reset. Check LINE VOLTAGE and VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. Chiller is automatically restarting AUTORESTART OPTION is enabled. Check LINE VOLTAGE in VFD_HIST screen. Check 24 vac control power voltage on ICVC terminals J1-4 and J1-5. See Table 5. Check distribution bus. Consult power company. Chiller is automatically restarting AUTORESTART OPTION is enabled. Check DC BUS VOLTAGE and VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. See Table 5. *[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped. 91 Table 15 — ICVC Primary and Secondary Messages and Custom Alarm/Alert Messages with Troubleshooting Guides (cont) J. CHILLER ALERTS (cont) STATE PRIMARY MESSAGE SECONDARY MESSAGE ALARM MESSAGE PRIMARY CAUSE 150 AUTORESTART PENDING HIGH DC BUS VOLTAGE 150->High DC Bus Voltage: [VALUE] Exceeded Limit of [LIMIT]* 151 CONDENSER PRESSURE ALERT PUMP RELAY ENERGIZED 151->High Condenser Pressure [VALUE]: Pump Energized to Reduce Pressure. 152 RECYCLE ALERT EXCESSIVE RECYCLE STARTS 152->Excessive recycle starts. 153 no message: ALERT only no message; ALERT only 153->Lead/Lag Disabled: Duplicate Chiller Address; Check Configuration 154 POTENTIAL FREEZE-UP COND PRESS/TEMP TOO LOW 154->Condenser freeze up prevention 155 OPTION SENSOR FAULT REMOTE RESET SENSOR 155->Sensor Fault/Option Disabled: Remote Reset Sensor 156 OPTION SENSOR FAULT AUTO CHILLED LIQUID RESET 156->Sensor Fault/Option Disabled: Auto Chilled Liquid Reset 157 OPTION SENSOR FAULT AUTO DEMAND LIMIT INPUT 157->Sensor Fault/Option Disabled: Auto Demand Limit Input 158 SENSOR ALERT SPARE TEMPERATURE #1 158->Spare Temperature #1 [VALUE] exceeded limit of [LIMIT].* 159 SENSOR ALERT SPARE TEMPERATURE #2 159->Spare Temperature #2 [VALUE] exceeded limit of [LIMIT].* ADDITIONAL CAUSE/REMEDY Chiller is automatically restarting AUTORESTART OPTION is enabled. Check DC BUS VOLTAGE and VFD FAULT CODE in VFD_HIST screen. See VFD FAULT CODES in Table 16. See Table 5. Check input power for high voltage transients. Check COND PRESS OVERRIDE in SETUP1 screen. Check CONDENSER PRESSURE sensor wiring and accuracy. Check condenser liquid flow, strainers, and condenser liquid temperature. Check for fouled tubes. This alarm is not caused by the High Pressure Switch. Chiller load is too low to keep compressor on line and there has been more than 5 starts in 4 hours. Check HGBP Isolation valve position. Increase chiller load. Adjust hot gas bypass parameters in OPTIONS screen. Increase (RECYCLE CONTROL) RESTART DELTA T in SETUP1 Screen. Illegal chiller address configuration in Lead/Lag screen, see Table 7. Check chiller addresses in LEAD/LAG and ICVC CONFIGURATION screens. The chiller is not in pumpdown mode and the condenser pressure transducer is reading a pressure that could freeze the condenser tubes. Check CONDENSER FREEZE POINT setting. See Table 5. Check for condenser refrigerant leaks. Check condenser liquid temperature. Check CONDENSER PRESSURE sensor wiring and accuracy on CCM terminals J2-4, J2-5 and J2-6. Place the chiller in PUMPDOWN mode if the vessel is evacuated. Type 2 Temperature Reset is enabled and Remote Reset sensor on CCM J4-13 and J4-14 is out of range. Check Temperature Reset settings in TEMP_CNTL screen. Check REMOTE RESET sensor resistance or voltage drop. Check for proper REMOTE RESET sensor wiring. Type 1 Temperature Reset is enabled and Auto Chilled Water Reset input on CCM J5-3 and J5-4 is < 2 mA. Check Temperature Reset settings in TEMP_CNTL screen. Check that Auto Chilled Liquid Reset input is between 4 mA and 20 mA. 20 mA DEMAND LIMIT OPTION is enabled and Auto Demand Limit input on CCM J5-1 and J5-2 is < 2 mA. Check 20 mA DEMAND LIMIT setting in RAMP_DEM screen. Check that Auto Demand Limit input is between 4 mA and 20 mA. Check component that SPARE TEMPERATURE #1 is monitoring. Check SPARE TEMPERATURE #1 settings in SETUP1 screen. Check SPARE TEMPERATURE #1 sensor resistance or voltage drop on CCM J4-25 and J4-26. Check for proper SPARE TEMPERATURE #1 wiring. Check component that SPARE TEMPERATURE #2 is monitoring. Check SPARE TEMPERATURE #2 settings in SETUP1 screen. Check SPARE TEMPERATURE #2 sensor resistance or voltage drop on CCM J4-27 and J4-28. Check for proper SPARE TEMPERATURE #2 wiring. *[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped. 92 Table 15 — ICVC Primary and Secondary Messages and Custom Alarm/Alert Messages with Troubleshooting Guides (cont) J. CHILLER ALERTS (cont) STATE PRIMARY MESSAGE SECONDARY MESSAGE ALARM MESSAGE PRIMARY CAUSE 160 SENSOR ALERT EVAPORATOR APPROACH 160->Evaporator Approach [VALUE] Exceeded Limit of [LIMIT]* 161 SENSOR ALERT CONDENSER APPROACH 161->Condenser Approach [VALUE] Exceeded Limit of [LIMIT]* 162 SENSOR ALERT HIGH DISCHARGE TEMP 162->Comp Discharge Temp [VALUE] Exceeded Limit of [LIMIT]* 163 LOSS OF COMMUNICATION WITH WSM 163->WSM Cool Source - Loss of Communication 164 SYSTEM ALERT HIGH OIL PRESSURE 164->High Oil Pressure [VALUE], Check Oil Regulator and Valves 168 SENSOR ALERT HUMIDITY SENSOR INPUT 168->Sensor Fault: Check Humidity Sensor Input ADDITIONAL CAUSE/REMEDY Check position of refrigerant liquid line isolation valve. Check EVAP APPROACH ALERT setting in SETUP1 screen. Check Evaporator Liquid Flow. See Table 5. Check EVAP REFRIG LIQUID TEMP and CHILLED LIQUID TEMP sensor resistances or voltage drops. Check for proper EVAP REFRIG LIQUID TEMP and CHILLED LIQUID TEMP sensor wiring. Check for oil loss. Check for low refrigerant charge. Check float valve operation and for refrigerant stacking in the condenser. Check for evaporator division plate bypass. Check for fouled tubes. Check for air in water box. Check COND APPROACH ALERT setting in SETUP1 screen. Check Condenser Liquid flow. See Table 5. Check CONDENSER PRESSURE and LEAVING COND LIQUID temperature sensor resistances or voltage drops. Check for proper CONDENSER PRESSURE and LEAVING COND LIQUID temperature sensor wiring. Check condenser shell temperature against condenser pressure measured with refrigerant gage for evidence of non-condensables in refrigerant charge. Check for condenser division plate bypass. Check for fouled condenser tubes. Check for air in water box. Check position of condenser isolation valve. Check COMP DISCHARGE ALERT setting in SETUP1 screen. See Table 5. Check COMP DISCHARGE TEMP sensor resistance or voltage drop. Check for proper condenser liquid flow and temperature. Check for proper wiring. Check for fouled tubes, plugged strainers, or non-condensables in the refrigerant. Communications interrupted between supervisory component and equipment component of WSM (Water System Manager). Check settings in WSMDEFME screen. Check CCN communications link with WSM. Check supervisory part of WSM. See Table 5. Check oil pressure regulator isolation valve. Check oil pressure regulator. Check for bent oil lines. Check Oil Sump Pressure and Oil Pressure Leaving filter transducer resistances or voltage drops. Check OIL PRESSURE DELTA P wiring to CCM. Check for debris in Compressor Inlet Bearing Oil Orifice Strainers. Normal alert if chiller was charged and started within a few hours of pulling dehydration vacuum with oil heater on. See Table 5. Humidity Sensor Input voltage is outside of 0.5 V to 4.5 V range. Check Humidity Sensor wiring to CCM terminals J3-7, J3-9, and J4-10. Check Humidity Sensor Input in Controls Test screen. Check resistance 4.3 kohm load resistor between CCM J3-7 and J3-8. *[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped. 93 Table 16 — Fault Description and Corrective Actions FAULT FAULT CODE 2 Auxiliary Input 3 Power Loss TYPE DESCRIPTION 1 1, 3 Input is open. DC bus voltage remained below 85% of nominal for longer than Power Loss Time (185). Enable/disable with Fault Config 1 (238). DC bus voltage fell below the minimum value of 407V DC at 400/480V input. DC bus voltage exceeded maximum value. 4 UnderVoltage 1, 3 5 OverVoltage 1 7 Motor Overload 1, 3 8 Invtr Base Temp 1 9 Invtr IGBT Temp 1 12 HW OverCurrent 1 13 Ground Fault 1 24 Decel Inhibit 3 25 OverSpeed Limit 1 29 Analog In Loss 1, 3 33 Auto Rstrt Tries 3 35 Current Fbk Lost 4 36 SW OverCurrent 1 37 Motor I Imbalance 4 38 39 40 41 42 43 Phase U to Grnd Phase V to Grnd Phase W to Grnd Phase UV Short Phase VW Short Phase UW Short 4 4 4 4 4 4 ACTION Check remote wiring. Monitor the incoming AC line for low voltage or line power interruption. FAULT STATE 206 149 215 Monitor the incoming AC line for low voltage or power interruption. Monitor the AC line for high line voltage or transient conditions. Extend the decel time or check RATED LINE VOLTAGE setting. An excessive motor load exists. Reduce load so drive output current does not exceed the MOTOR NAMEPLATE AMPS setting. 149 215 150 205 1. Check operation of VFD cooling solenoid, VFD isolation valves, and humidity sensor. 2. Check for proper temperature and flow rate of coolant. Output transistors have exceeded their 1. Check operation of VFD cooling solenoid, VFD maximum operating temperature. isolation valves, and humidity sensor. 2. Check for proper temperature and flow rate of coolant. The drive output current has exceeded Check programming. Check for excess load. the hardware current limit. Contact Carrier Service. A current path to earth ground in excess Check the motor and external wiring to the drive of 7% of drive rated amps has been output terminals for a grounded condition. detected at one or more of the drive output terminals. The drive is not following a commanded 1. Verify input voltage is within drive specified deceleration because it is attempting to limits. limit bus voltage. 2. Verify system ground impedance follows proper grounding techniques. Functions such as slip compensation or Remove excessive load conditions. bus regulation have attempted to add an output frequency adjustment greater than that programmed in Overspeed Limit (83). An analog input is configured to fault on 1. Check parameters. signal loss. A signal loss has occurred. 2. Check for broken/loose connections at inputs. Configure with Anlg In 1, 2 Loss (324, 327). Drive unsuccessfully attempted to reset 1. Correct the cause of the fault and manually a fault. clear. 2. Check parameters in VFD_CONF screen The magnitude of motor current feed1. Verify connection of current feedback device back was less than 5% Motor NP FLA and motor terminals. (42) for the time configured in Imbalance 2. If fault repeats, replace current feedback Time (50). Detection of this fault is disdevices and/or power supply. abled when Imbalance Time (50) is set to 3. Check VFD_CONF screen parameters. the maximum value of 10.0 seconds. The drive output current has exceeded 1. Check for excess load. the software current. 1. Press ICVC RESET key to clear fault. Phase current displayed in Imbalance Display (221) > percentage set in Imbal- 2. Check motor leads and terminals. ance Limit (49) for time set in Imbalance Time (50). A phase-to-ground fault has been 1. Check the wiring between the drive and motor. detected between the drive and motor in 2. Check motor for grounded phase. this phase. 3. Contact Carrier Service. 219 Internal electronic overload is set to trip when the motor current equals 135% of Motor NP FLA(42) for 1.5 seconds or when PERCENT LOAD CURRENT is sustained above 108%. Base temperature exceeded limit. Excessive current has been detected between these two output terminals. Fault Type indicates if the fault is: 1 — Auto-resettable 2 — Non-resettable 3 — User-configurable 4 — Normal Fault resettable using Carrier ICVC “RESET” softkey 1. Check the motor and drive output terminal wiring for a shorted condition. 2. Contact Carrier Service, replace drive. 217 219 246 220 204 206 206 206 206 246 225 220 220 NOTE: VFD Troubleshooting should only be performed by a Reliance Certified LiquiFlo2 technician. 94 Table 16 — Fault Description and Corrective Actions (cont) FAULT CODE 48 FAULT TYPE DESCRIPTION ACTION Params Defaulted 4 The drive was commanded to write default values to EEPROM. 63 Shear Pin 3 64 Drive OverLoad 4 70 HW Fault 4 Port 1-5 Net Loss 4 77 IR Volts Range 4 78 FluxAmpsRef Rang 4 79 Excessive Load 4 80 AutoTune Aborted 4 81- 85 Port 1-5 DPI Loss 4 87 Ixo Voltage Range 4 100 Parameter Chksum 2 101 102 103 104 UserSet1 Chksum UserSet2 Chksum UserSet3 Chksum Pwr Brd Chksum1 2 2 2 4 Programmed Current Lmt Val (148) has been exceeded. Enabled/disable with Fault Config 1 (238). Drive rating of 102% for 1 minute or 150% for 5 seconds has been exceeded. Inverter section of power module detected an unexpected fault during power stage diagnostics. The network card connected to DPI port stopped communicating. The fault code indicates the offending port number (71 = port 1, 72 = port 2, etc.) The drive autotuning default is calculated, and the value calculated for IR Drop Volts is not in the range of acceptable values. The value for flux amps determined by the autotune procedure exceeds the programmed Motor NP FLA (42). Motor did not come up to speed in the allotted time. The autotune procedure was canceled by the user. DPI port stopped communicating. An attached peripheral with control capabilities via Local Mask (288) (or OIM control) was removed. The fault code indicates the offending port number (81 = port 1, etc.) Ixo voltage calculated from motor nameplate data is too high The checksum read from the board does not match the checksum calculated. The checksum read from the user set does not match the checksum calculated. 105 Pwr Brd Chksum2 2 106 Incompat MCB-PB 2 107 Replaced MCB-PB 2 120 121 I/O Board Mismatch I/O Board Comm Loss 4 2 The checksum read from the EEPROM does not match the checksum calculated from the EEPROM data. The checksum read from the board does not match the checksum calculated. Drive rating information stored on the power board is incompatible with the Main Control board. Main Control board was replaced and parameters were not programmed. Incorrect I/O board identified. Loss of communication to I/O board. 122 I/O Board Fail 4 Board failure. 200 Inverter Dsat U, V, W 4 High current was detected in an IGBT. 71- 75 201 202 Fault Type indicates if the fault is: 1 — Auto-resettable 2 — Non-resettable 3 — User-configurable 4 — Normal Fault resettable using Carrier ICVC “RESET” softkey 1. Press ICVC RESET key or cycle power to the VFD. 2. Program the drive parameters as needed. Check MOTOR RATED LOAD AMPS setting in VFD_CONF screen. FAULT STATE 206 206 Check RATED LINE AMPS and MOTOR RATED LOAD AMPS in VFD_CONF screen. 246 Contact Carrier Service 206 1. Check communication board for proper connection to external network. 2. Check external wiring to module on port. Check ribbon cables, connectors, and pins. 3. Verify external network fault. Check Motor Nameplate parameters in VFD_CONF screen. 206 Check MOTOR NAMEPLATE AMPS in VFD_CONF screen. 206 1. Check parameters in VFD_CONF screen. 2. Contact Carrier Service. Press ICVC RESET key to restart procedure. 203 1. If module was not intentionally disconnected, check ribbon cables, connectors, and pins. Replace wiring port expander, modules, Main Control Board or complete drive as required. 2. Check OIM connection if used. 206 1. Press ICVC RESET key. 2. Contact Carrier Service. 1. Press ICVC RESET key to restore defaults. 2. Cycle power to the VFD. 1. Press ICVC RESET key to restore defaults. 2. Cycle power to the VFD. 206 1. Press ICVC RESET key to restore defaults. 2. Cycle power to the VFD. 206 1. Cycle power to the VFD. 2. If problem persists, contact Carrier Service. Load compatible version files into drive. 206 206 Program parameters into VFD_CONF screen. 206 Program parameters into VFD_CONF screen. 1. Press ICVC RESET key. 2. Check VFD board ribbon cables and connector pins. 1. Press ICVC RESET key, cycle power to the VFD. 2. If fault repeats, replace I/O board. 1. Check for loose connection in IGBT wire harness. 2. Check IGBTs. 3. Check precharge resistors and fuses. 4. Check precharge contactor. 206 206 206 206 206 206 206 201 NOTE: VFD Troubleshooting should only be performed by a Reliance Certified LiquiFlo2 technician. 95 Table 16 — Fault Description and Corrective Actions (cont) FAULT CODE 203 204 205 207 FAULT TYPE DESCRIPTION ACTION FAULT STATE 246 Inverter OverCurrent U, V, W 4 High current was detected in an IGBT. Check parameters in VFD_CONF screen. Invtr Gate Kill 4 Inverter gate kill contact is open. 207 235 208 209 210 211 212 213 214 215 Rectifier Dsat R, S, T 4 High current was detected in an IGBT. 1. Check that condenser high pressure switch is wired to the VFD gate kill contact. 2. Check that high pressure switch is closed. 1. Press RESET key on ICVC. 2. Contact Carrier Service. Rectifier Over Cur R, S, T 4 Rectifier overcurrent Check parameters in VFD_CONF screen. 241 Reactor Temp Rctfr HW Unused 4 4 216 217 Rectifier Ground Fault Rectifier Base Temp 4 4 218 Rectifier IGBT Temp 4 219 Rectifier IT Overload 4 220 Rectifier I2T Overload 4 221 Ride Thru Abort 4 222 High AC Line 4 223 Low DC Bus 4 224 Rctfr Over Volt 4 225 Input Amp Imbalance 4 226 Input Volt Imbalance 4 227 AC Line Lost 4 228 Line Frequency 4 229 Rectifier Checksum 4 230 Invtr HW Unk 4 Temperature switch in reactor opened. Check for proper temperature and fan operation. Rectifier portion of power structure hard- 1. Verify connection between rectifier control ware reported unexpected fault board and rectifier power board. 2. If fault persists, replace rectifier power board. 3. If fault still persists, replace rectifier inverter control board. Excessive ground current measured. Check for grounded input wiring. Excessive rectifier temperature 1. Check VFD cooling solenoid, VFD refrigerant measured. strainer, and VFD isolation valves. 2. Check for proper temperature and flow rate of coolant. Excessive calculated IGBT temperature. 1. Check VFD cooling solenoid, VFD refrigerant strainer, and VFD isolation valves. 2. Check for proper temperature and flow rate of coolant. Short-term current rating of rectifier Low input voltage can result in increased current exceeded. load. Provide proper input voltage to the drive. Long-term current rating of rectifier Low input voltage can result in increased current exceeded. load. Provide proper input voltage to the drive. Input power loss timed out. 1. Verify input power and connections. 2. Check Line Sync board, connectors and pins. 3. Check AC Line I/O board, connectors, and pins. Input line voltage is too high. Reduce input voltage to meet RATED LINE VOLTAGE ±10%. The bus voltage is too low. 1. Verify proper input voltage. 2. Check control center and input power fuses. The bus voltage is too high. Monitor the AC line for high line voltage or transient conditions. Extend the decel time. Input phase current imbalance 1. Check for loose connection in input power exceeded limits. wiring. 2. Check precharge contactors. Input voltage imbalance exceeded limits. 1. Check for problem in input power distribution. 2. Check input wiring connections. Input power Lost 1. Verify proper input voltage. 2. Check line sync board and fuse. 3. Check AC line I/O board. 4. Verify connections between boards. Line frequency not in the range of Verify connection between AC Line Sync and AC 47-63 Hz. Line I/O boards. Confirm that connectors are fully engaged. The checksum read from the board does 1. Check all power module connectors and cycle not match the checksum calculated. power to the VFD. 2. Press ICVC RESET key to restore defaults. 3. Check parameters in VFD_CONF screen. Inverter section of power structure hard- 1. Verify connection between inverter control ware reported unexpected fault. board and inverter power board. 2. If fault persists, replace inverter power board. 3. If fault still persists, replace inverter control board. Fault Type indicates if the fault is: 1 — Auto-resettable 2 — Non-resettable 3 — User-configurable 4 — Normal Fault resettable using Carrier ICVC “RESET” softkey 200 255 206 220 218 218 146 212 146 212 146 147 212 213 145 211 149 215 150 205 143 209 216 144 210 222 253 206 NOTE: VFD Troubleshooting should only be performed by a Reliance Certified LiquiFlo2 technician. 96 Table 16 — Fault Description and Corrective Actions (cont) FAULT CODE 231 Rctfr HW Unk 4 232 Rctfr Not OK 4 233 Precharge closed 4 234 Precharge open 4 235 Rctfr Pwr Board 4 236 Rctfr I/O Board 4 237 Not at Voltage 4 238 Rectfr Not Logged In 4 239 Power Phased ACB 4 FAULT TYPE DESCRIPTION ACTION Rectifier portion of power structure hard- 1. Verify connection between rectifier control ware reported unexpected fault. board and rectifier power board. 2. If fault persists, replace rectifier power board 3. If fault still persists, replace rectifier control board. A fault was detected in the rectifier other Look at rectifier parameter 243 to see fault code. than one specifically decoded. Contact Carrier. Precharge was closed when it should be 1. Check AUX contacts on precharge. Check if open. precharge contactor is energized. 2. Check input bit 0 in rectifier parameter 216 to view status of input. 3. Check wiring. 4. Check precharge resistors and fuses. Precharge was open when it should be 1. Check AUX contacts on precharge. Check if closed. precharge contactor is de-energized. 2. Check input bit 0 in rectifier parameter 216 to view status of input. 3. Check wiring. 4. Check precharge resistors and fuses. Drive rating information stored on the Load compatible version files into drive. power board is incompatible with the 1. Cycle power to the VFD. Main Control board. 2. If problem persists, contact Carrier Service. The checksum read from the board does not match the checksum calculated. Loss of communication to I/O board. 1. Cycle power to the VFD. Board failure. 2. Check I/O board ribbon cables, connectors, and pins. 3. If fault repeats, replace I/O board. The rectifier did not regulate to the 1. Check all fuses and cabinet wiring. desired bus voltage within the defined 2. Replace line synch board. time. 3. Replace AC Line I/O board. 4. Replace rectifier control board and/or rectifier power board. Rectifier took too long to connect to 1. Check the cabling, connectors, and pins inverter. between the communications interface and the two control boards. 2. Verify the DPI Data Rate (270) is set to 500K. 3. Connect one DPI device at a time to determine if one of the DPI devices is causing the problem. 4. Replace the communications interface. 5. Replace the rectifier control board. 6. Swap 80W power supplies to determine if the fault follows the power supply. Replace the power supply if needed. Input Power is phased ACB rather than Switch two of the input power phases. ABC. Fault Type indicates if the fault is: 1 — Auto-resettable 2 — Non-resettable 3 — User-configurable 4 — Normal Fault resettable using Carrier ICVC “RESET” softkey FAULT STATE 206 200 206 206 206 206 149 215 206 226 NOTE: VFD Troubleshooting should only be performed by a Reliance Certified LiquiFlo2 technician. 97 2. If a green LED is on continuously, check the communication wiring. If a green LED is off, check the red LED operation. If the red LED is normal, check the SIO address switches (Fig. 49 and 50). Confirm all SW1 SIO address dip switches on the CCM are in the OFF position. All system operating intelligence resides in the ICVC. Some safety shutdown logic resides in the VFD Gateway in case communications are lost between the VFD and ICVC. Outputs are controlled by the CCM and VFD Gateway as well. 3. In the control center, a 3 KVA transformer steps down line power to 115 V. This supplies power to the oil pump, oil vaporizer heater, oil sump heater, and control power transformers. Power is supplied to the ICVC and CCM modules within the control center via the T1 24-VAC transformer. The control power transformers are located on the power panel. Transformer T1 supplies 24 V power to the ICVC and CCM. Transformer T2 provides 20 V power to optional DataPort™ or DataLINK™ modules. Power is connected to Plug J1 on the ICVC and CCM modules. Control Modules — Turn controller power off before servicing controls. This ensures safety and prevents damage to the controller. The ICVC and CCM modules perform continuous diagnostic evaluations of the hardware to determine its condition. Proper operation of all modules is indicated by LEDs (lightemitting diodes) located on the circuit board of the ICVC and CCM. There is one green LED located on the CCM board, and one red LED located on the ICVC and CCM boards. RED LED (Labeled as STAT) — If the red LED: • Blinks continuously at a 2-second interval — the module is operating properly • Is lit continuously — there is a problem that requires replacing the module • Is off continuously — the power should be checked • Blinks 3 times per second — a software error has been discovered and the module must be replaced If there is no input power, check the CB2 control power circuit breaker and control power transformer circuit breakers (CB1A and CB1B). If the breakers are good, check for a shorted 24 vac secondary of the T1 transformer or, if power is present to the module, replace the module. GREEN LED (Labeled as COM) — These LEDs indicate the communication status between different parts of the controller and the network modules and should blink continuously. Chiller Control Module (CCM) (Fig. 50) INPUTS — Each input channel has 2 or 3 terminals. Refer to individual chiller wiring diagrams for the correct terminal numbers for your application. OUTPUTS — CCM terminals J11 and J12 are discrete (on/ off) outputs that switch 24 volts. The 4 to 20 mA output channel on terminals J8-1 and J8-2 is designed for non-grounded controllers with a maximum input impedance of 500 ohms. J8-3 and J8-4 are used with a 500-ohm resistor to control the oil reclaim actuator. Notes on Module Operation 1. The chiller operator monitors and modifies configurations in the microprocessor by using the 4 softkeys and the ICVC. Communications between the ICVC and the CCM is accomplished through the SIO (Sensor Input/ Output) bus, which is a phone cable. The communication between the CCM and VFD is accomplished through a 3-wire SIO communication protocol cable. GROUND SIO COMMUNICATIONS (J7) POWER AND CCN (J1) RJ-14 SERVICE CONNECTION (J8) fa23-1640 Fig. 49 — Rear of ICVC (International Chiller Visual Controller) 98 Table 17A — Thermistor Temperature (F) vs Resistance/Voltage Drop TEMPERATURE (F) –25 –24 –23 –22 –21 –20 –19 –18 –17 –16 –15 –14 –13 –12 –11 –10 –9 –8 –7 –6 –5 –4 –3 –2 –1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 PIC III VOLTAGE DROP (V) 4.700 4.690 4.680 4.670 4.659 4.648 4.637 4.625 4.613 4.601 4.588 4.576 4.562 4.549 4.535 4.521 4.507 4.492 4.477 4.461 4.446 4.429 4.413 4.396 4.379 4.361 4.344 4.325 4.307 4.288 4.269 4.249 4.229 4.209 4.188 4.167 4.145 4.123 4.101 4.079 4.056 4.033 4.009 3.985 3.960 3.936 3.911 3.886 3.861 3.835 3.808 3.782 3.755 3.727 3.700 3.672 3.644 3.617 3.588 3.559 3.530 3.501 3.471 3.442 3.412 3.382 3.353 3.322 3.291 3.260 3.229 3.198 3.167 3.135 3.104 3.074 3.042 3.010 2.978 2.946 2.914 2.882 2.850 2.819 2.788 2.756 2.724 2.692 2.660 2.628 2.596 RESISTANCE (Ohms) TEMPERATURE (F) 97,706 94,549 91,474 88,480 85,568 82,737 79,988 77,320 74,734 72,229 69,806 67,465 65,205 63,027 60,930 58,915 56,981 55,129 53,358 51,669 50,062 48,536 47,007 45,528 44,098 42,715 41,380 40,089 38,843 37,639 36,476 35,354 34,270 33,224 32,214 31,239 30,298 29,389 28,511 27,663 26,844 26,052 25,285 24,544 23,826 23,130 22,455 21,800 21,163 20,556 19,967 19,396 18,843 18,307 17,787 17,284 16,797 16,325 15,868 15,426 14,997 14,582 14,181 13,791 13,415 13,050 12,696 12,353 12,021 11,699 11,386 11,082 10,787 10,500 10,221 9,949 9,689 9,436 9,190 8,951 8,719 8,494 8,275 8,062 7,855 7,655 7,460 7,271 7,088 6,909 6,736 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 PIC III VOLTAGE DROP (V) 2.565 2.533 2.503 2.472 2.440 2.409 2.378 2.347 2.317 2.287 2.256 2.227 2.197 2.167 2.137 2.108 2.079 2.050 2.021 1.993 1.965 1.937 1.909 1.881 1.854 1.827 1.800 1.773 1.747 1.721 1.695 1.670 1.644 1.619 1.595 1.570 1.546 1.523 1.499 1.476 1.453 1.430 1.408 1.386 1.364 1.343 1.321 1.300 1.279 1.259 1.239 1.219 1.200 1.180 1.161 1.143 1.124 1.106 1.088 1.070 1.053 1.036 1.019 1.002 0.986 0.969 0.953 0.938 0.922 0.907 0.893 0.878 0.864 0.849 0.835 0.821 0.808 0.795 0.782 0.769 0.756 0.744 0.731 0.719 0.707 0.696 0.684 0.673 0.662 0.651 0.640 99 RESISTANCE (Ohms) TEMPERATURE (F) 6,568 6,405 6,246 6,092 5,942 5,796 5,655 5,517 5,382 5,252 5,124 5,000 4,880 4,764 4,650 4,539 4,432 4,327 4,225 4,125 4,028 3,934 3,843 3,753 3,667 3,582 3,500 3,420 3,342 3,266 3,192 3,120 3,049 2,981 2,914 2,849 2,786 2,724 2,663 2,605 2,547 2,492 2,437 2,384 2,332 2,282 2,232 2,184 2,137 2,092 2,047 2,003 1,961 1,920 1,879 1,840 1,801 1,764 1,727 1,691 1,656 1,622 1,589 1,556 1,524 1,493 1,463 1,433 1,404 1,376 1,348 1,321 1,295 1,269 1,244 1,219 1,195 1,172 1,149 1,126 1,104 1,083 1,062 1,041 1,021 1,002 983 964 945 928 910 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 PIC III VOLTAGE DROP (V) 0.630 0.619 0.609 0.599 0.589 0.579 0.570 0.561 0.551 0.542 0.533 0.524 0.516 0.508 0.499 0.491 0.484 0.476 0.468 0.460 0.453 0.445 0.438 0.431 0.424 0.418 0.411 0.404 0.398 0.392 0.385 0.379 0.373 0.367 0.361 0.356 0.350 0.344 0.339 0.333 0.328 0.323 0.318 0.313 0.308 0.304 0.299 0.294 0.290 0.285 0.281 0.277 0.272 0.268 0.264 0.260 0.256 0.252 0.248 0.245 0.241 0.237 0.234 0.230 0.227 0.224 0.220 0.217 0.214 0.211 0.208 0.205 0.203 0.198 0.195 0.192 0.190 0.187 0.184 0.182 0.179 0.176 0.174 0.172 0.169 0.167 0.164 0.162 0.160 0.158 0.155 0.153 RESISTANCE (Ohms) 893 876 859 843 827 812 797 782 768 753 740 726 713 700 687 675 663 651 639 628 616 605 595 584 574 564 554 544 535 526 516 508 499 490 482 474 466 458 450 442 435 428 421 414 407 400 393 387 381 374 368 362 356 351 345 339 334 329 323 318 313 308 303 299 294 289 285 280 276 272 267 263 259 255 251 248 244 240 236 233 229 226 223 219 216 213 210 207 204 201 198 195 Table 17B — Thermistor Temperature (C) vs Resistance/Voltage Drop TEMPERATURE (C) –33 –32 –31 –30 –29 –28 –27 –26 –25 –24 –23 –22 –21 –20 –19 –18 –17 –16 –15 –14 –13 –12 –11 –10 –9 –8 –7 –6 –5 –4 –3 –2 –1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 PIC III VOLTAGE DROP (V) 4.722 4.706 4.688 4.670 4.650 4.630 4.608 4.586 4.562 4.538 4.512 4.486 4.458 4.429 4.399 4.368 4.336 4.303 4.269 4.233 4.196 4.158 4.119 4.079 4.037 3.994 3.951 3.906 3.861 3.814 3.765 3.716 3.667 3.617 3.565 3.512 3.459 3.406 3.353 3.298 3.242 3.185 3.129 3.074 3.016 2.959 2.901 2.844 2.788 2.730 2.672 2.615 2.559 2.503 2.447 2.391 2.335 2.280 2.227 2.173 2.120 2.067 2.015 1.965 1.914 1.865 1.816 1.768 1.721 1.675 1.629 1.585 1.542 1.499 1.457 1.417 1.377 RESISTANCE (Ohms) TEMPERATURE (C) 105 616 99 640 93 928 88 480 83 297 78 377 73 722 69 332 65 205 61 343 57 745 54 411 51 341 48 536 45 819 43 263 40 858 38 598 36 476 34 484 32 613 30 858 29 211 27 663 26 208 24 838 23 545 22 323 21 163 20 083 19 062 18 097 17 185 16 325 15 513 14 747 14 023 13 341 12 696 12 087 11 510 10 963 10 444 9 949 9 486 9 046 8 628 8 232 7 855 7 499 7 160 6 839 6 535 6 246 5 972 5 711 5 463 5 226 5 000 4 787 4 583 4 389 4 204 4 028 3 861 3 701 3 549 3 404 3 266 3 134 3 008 2 888 2 773 2 663 2 559 2 459 2 363 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 100 PIC III VOLTAGE DROP (V) 1.338 1.300 1.263 1.227 1.192 1.158 1.124 1.091 1.060 1.029 0.999 0.969 0.941 0.913 0.887 0.861 0.835 0.811 0.787 0.764 0.741 0.719 0.698 0.677 0.657 0.638 0.619 0.601 0.583 0.566 0.549 0.533 0.518 0.503 0.488 0.474 0.460 0.447 0.434 0.422 0.410 0.398 0.387 0.376 0.365 0.355 0.344 0.335 0.325 0.316 0.308 0.299 0.291 0.283 0.275 0.267 0.260 0.253 0.246 0.239 0.233 0.227 0.221 0.215 0.210 0.205 0.198 0.193 0.188 0.183 0.178 0.174 0.170 0.165 0.161 0.157 0.153 RESISTANCE (Ohms) 2 272 2 184 2 101 2 021 1 944 1 871 1 801 1 734 1 670 1 609 1 550 1 493 1 439 1 387 1 337 1 290 1 244 1 200 1 158 1 117 1 079 1 041 1 006 971 938 906 876 846 818 791 765 740 715 692 670 648 628 608 588 570 552 535 518 502 487 472 458 444 431 418 405 393 382 371 360 349 339 330 320 311 302 294 286 278 270 262 255 248 242 235 229 223 217 211 205 200 195 J11 DISCRETE OUTPUTS SW1 SIO ADDRESS DIPSWITCH SET ALL TO “OFF” J12 DISCRETE OUTPUTS J1 24 VAC ANALOG OUT J8 SIO J7 SIO J6 SW2 V/I INPUT CONFIGURATION V/I INPUTS J5 a23-1617 STAT COMM THERMISTORS J4 DIFF PRESSURE J3 PRESSURE J2 Fig. 50 — Chiller Control Module (CCM) Replacing Defective ICVC Modules — The mod- ule replacement part number is printed on a small label on the rear of the ICVC module. The chiller model and serial numbers are printed on the chiller nameplate located on the right side of the control center. The proper software is factoryinstalled by Carrier in the replacement module. When ordering a replacement international chiller visual controller (ICVC) module, specify the complete replacement part number, full chiller model number, and chiller serial number. The installer must configure the new module to the original chiller data. Follow the procedures described in the Software Configuration section on page 59. 3. Electrical shock can cause personal injury. Disconnect all electrical power before servicing. 4. 5. 6. INSTALLATION 1. Verify the existing ICVC module is defective by using the procedure described in the Troubleshooting Guide section, page 78, and the Control Modules section, on this page. Do not select the ATTACH TO NETWORK DEVICE table if the ICVC indicates a CCN communication failure. Doing so will probably lock up the ICVC because it will not be able to communicate with the CCN. 2. Any communication wires from other chillers or CCN modules should be disconnected prior to installation of a new module to prevent the new ICVC from uploading incorrect run hours into memory. Data regarding the ICVC configuration should have been recorded and saved. This data must be reconfigured into the new ICVC. If this data is not available, follow the procedures 7. 8. 101 described in the Software Configuration section. If the module to be replaced is functional, configurations may also be copied manually. The data sheets on pages CL-4 through CL-12 are provided for this purpose. Default values are shown so that only deviations from these need to be recorded. If a CCN Building Supervisor or Service Tool is available, the module configuration should have already been uploaded into memory. When the new module is installed, the configuration can be downloaded from the computer. To install this module, record values for the TOTAL COMPRESSOR STARTS, SERVICE ONTIME, and the COMPRESSOR ONTIME from the MAINSTAT screen on the ICVC. Power off the controls. Remove the old ICVC. Install the new ICVC module. Turn the control power back on. The ICVC now automatically attaches to the local network device. Set the current time and date in the SERVICE / TIME AND DATE screen. Set the CCN Bus and Address in the SERVICE / ICVC CONFIGURATION screen. Press the alarm RESET soft key (from the default screen). Upload via Service Tool or manually reenter all non-default configuration values. (Refer to pages CL-4 through CL-12). If the correct VFD_CONF values are displayed when that table is viewed, simply press EXIT then SAVE to reload all of them. Using Service Tool or manually reenter TOTAL COMPRESSOR STARTS, COMPRESSOR ONTIME, and SERVICE ONTIME. If forced using Service Tool, release the force on SERVICE ONTIME after the desired value has been set. TOTAL COMPRESSOR STARTS and TOTAL COMPRESSOR ONTIME can only be changed prior to the first completed start. If a start is completed and the COMPRESSOR STARTS or COMPRESSOR ON TIME are both incorrect, the ICVC software must be downloaded again before these settings can be changed. 9. Check and recalibrate pressure transducer readings (refer to page 79). Check that the CURRENT TIME and DATE in the TIME AND DATE screen are correct. DPI Communications Interface Board Status LEDs — VFD status can be determined from the status LEDs on the DPI Communications Interface Board shown in Fig. 51. The DPI Board is mounted on the front of the VFD power module in a vertical orientation. Table 19 — Gateway MS Status Indicator STATE Off CAUSE The Gateway is not powered. Flashing Recoverable Fault Red Condition Solid Red Flashing Green Solid Green Gateway Status LEDs — The RS485 VFD Gateway provides a communication link between the CCM and ICVC SIO bus to the VFD Drive Peripheral Interface (DPI) board. The SIO bus communicates with the Gateway through VFD connector A32. See Fig. 52. The Gateway has four status indicators on the top side of the module. DRIVE STATUS INDICATOR — The DRIVE status indicator is on the right side of the Gateway. See Table 18. The module has failed the hardware test. The Gateway is operational. No I/O data is being transferred. The Gateway is operational and transferring I/O data. CORRECTIVE ACTION • Securely connect the Gateway to the drive using the ribbon cable. • Apply power to the drive. Cycle power to the drive. If cycling power does not correct the problem, the firmware may need to be flashed into the module. • Cycle power to the drive • Replace the Gateway Normal behavior during SIO configuration initialization process. No action required. NET A STATUS INDICATOR — The NET A status indicator is the third LED from the right of the Gateway. See Table 20. Table 20 — Gateway NET A Status Indicator STATE Off CAUSE The module is not powered or is not properly connected to the network. First incoming network command not yet recognized. Flashing Network has timed out. Red Solid The Gateway has Red detected an error that has made it incapable of communication on the network. Flashing Online to network, but Green not producing or consuming I/O information. Solid The module is properly Green connected and communicating on the network. Table 18 — Gateway DRIVE Status Indicator STATE Off CAUSE The Gateway is not powered or is not connected properly to the drive. Flashing The Gateway is not Red receiving a ping message from the drive. Solid The drive has refused Red an I/O connection from the Gateway. CORRECTIVE ACTION • Securely connect the Gateway to the drive using the DPI ribbon cable. • Apply power to the drive. • Verify that cables are securely connected. • Cycle power to the drive. IMPORTANT: Cycle power after making the following correction: • Verify that all DPI cables on the drive are securely connected and not damaged. Replace cables if necessary. Orange The Gateway is con• Check wires leading to the nected to a product that A32 terminal block. does not support Rock- • Check that A32 terminal well Automation DPI block is fully engaged. communications. Flashing The Gateway is estab- Normal behavior. Green lishing an I/O connection to the drive or the I/O has been disabled. Solid The Gateway is propNo action required. Green erly connected and is communicating with the drive. CORRECTIVE ACTION • Securely connect the Gateway ribbon cable to the drive DPI board. • Attach the RS485 cable in Gateway to the connector. • Apply power to the drive. Cycle power to the drive. Check node address and data rate switch positions on the front of the Gateway. Cycle power to the drive. No action required. The LED will turn solid green when communication resumes. No action required. NET B STATUS INDICATOR — The NET B status indicator is the left LED on the Gateway. See Table 21. Table 21 — Gateway NET B Status Indicator STATE Off Solid or Blinking Green MS STATUS INDICATOR — The MS status indicator is the second LED from the right of the Gateway. See Table 19. 102 CAUSE Gateway not receiving data over the network. Gateway is transmitting data. CORRECTIVE ACTION • Check wires leading to A32 terminal block. • Check that A32 terminal block is fully engaged. No action required. DPI COMMUNICATIONS INTERFACE BOARD INVERTER LED RECTIFIER LED a19-1634 INVERTER STATUS LIGHT COLOR Green Yellow Red Red Inverter Green Rectifier STATE Flashing Steady Flashing Steady Flashing Steady DESCRIPTION Drive ready, but not running and no faults are present. Drive running, no faults are present. The drive is not ready. A VFD start inhibit is in effect. Normal condition when chiller not running because the ICVC has issued a stop command. An alarm condition exits. Check VFD FAULT CODE in ICVC VFD_STAT screen. A fault has occurred. Check VFD FAULT CODE in ICVC VFD_STAT screen. A non-resettable fault has occurred. Check VFD FAULT CODE in ICVC VFD_STAT screen. Steady VFD Gate Kill circuit has opened because the compressor high pressure switch has opened. RECTIFIER STATUS LIGHT COLOR Green Yellow Red Red Inverter Green Rectifier STATE Flashing Steady Flashing Steady Flashing Steady DESCRIPTION Rectifier ready, but not running and no faults are present. Rectifier running, no faults are present. Rectifier is not ready. A VFD start inhibit is in effect. This is a normal state if the inverter is not running and/or the precharge contacts are open. Rectifier alarm condition exits. Check VFD FAULT CODE in ICVC VFD_STAT screen. Rectifier fault has occurred. Check (VFD FAULT CODE in ICVC VFD_STAT screen. A non-resettable fault has occurred. Check VFD FAULT CODE in ICVC VFD_STAT screen. Steady VFD Gate Kill circuit has opened because the compressor high pressure switch has opened. INVERTER AND RECTIFIER CONTROL BOARD FAILURE STATUS LIGHT PATTERNS COLOR Red/Green Alternating Yellow/Green/Red Repeating Pattern DESCRIPTION Control board application firmware may be corrupt. Call Carrier Service. Control board RAM failure or control board firmware may be corrupt. Call Carrier Service. Fig. 51 — DPI Communications Interface Board Status LEDs Physical Data — Tables 22-28 and Fig. 53-57 provide additional information on component weights, physical and electrical data, and wiring schematics for the operator’s convenience during troubleshooting. DPI RIBBON CABLE CONNECTOR NODE ADDRESS TENS DIGIT = 0 (DO NOT CHANGE) Do not attempt to disconnect flanges while the machine is under pressure. Failure to relieve pressure can result in personal injury or damage to the unit. DATA RATE = PGM (DO NOT CHANGE) Before rigging the compressor, disconnect all wires entering the power panel. A32 TERMINAL BLOCK NODE ADDRESS ONES DIGIT = 1 (DO NOT CHANGE) NUMBER 1 2 3 4 STATUS INDICATOR DRIVE MS NET A NET B a23-1618 DESCRIPTION DPI Connection Status Module Status Serial Communication Status Serial Communication Traffic Status NOTE: If all status indicators are off, the Gateway is not receiving power. Fig. 52 — Gateway Status LEDs 103 Table 22 — 23XRV Heat Exchanger Weights English Dry Rigging Weight (lb)* CODE 30 31 32 35 36 37 40 41 42 45 46 47 50 51 52 55 56 57 Cooler Only Condenser Only 4148 4330 4522 4419 4627 4845 5008 5178 5326 5463 5659 5830 5827 6053 6196 6370 6631 6795 3617 3818 4023 4529 4758 4992 4962 5155 5347 5525 5747 5967 6013 6206 6387 6708 6930 7138 Metric (SI) Dry Rigging Weight (kg)* Machine Charge Refrigerant Weight (lb) With Without Economizer Economizer 800 650 800 650 800 650 910 760 910 760 910 760 900 750 900 750 900 750 1015 865 1015 865 1015 865 1250 1100 1250 1100 1250 1100 1430 1280 1430 1280 1430 1280 Liquid Weight (lb) Cooler Condenser 464 531 601 511 587 667 863 930 990 938 1014 1083 1101 1192 1248 1201 1304 1369 464 542 621 513 602 692 915 995 1074 998 1088 1179 1225 1304 1379 1339 1429 1514 Cooler Only Condenser Only 1877 1959 2046 2000 2094 2193 2675 2758 2832 2882 2976 3061 3182 3294 3364 3429 3556 3636 1676 1769 1860 2089 2195 2299 2746 2839 2932 3001 3108 3214 3304 3397 3485 3620 3726 3826 Machine Charge Refrigerant Weight (kg) With Without Economizer Economizer 363 295 363 295 363 295 413 345 413 345 413 345 408 340 408 340 408 340 460 392 460 392 460 392 567 499 567 499 567 499 649 581 649 581 649 581 Liquid Weight (kg) Cooler Condenser 210 241 273 232 266 303 391 422 449 425 460 491 499 541 566 545 591 621 210 246 282 233 273 314 415 451 487 453 494 535 556 591 626 607 648 687 *Rigging weights are for standard tubes of standard wall thickness (Turbo-B3 and Spikefin 2, 0.025-in. [0.635 mm] wall). NOTES: 1. Cooler includes the suction elbow and 1/2 the distribution piping weight. 2. Condenser includes float valve and sump, discharge elbow, and 1/2 the distribution piping weight. 3. For special tubes refer to the 23XRV Computer Selection Program. 4. All weights for standard 2 pass NIH (nozzle-in-head) design with victaulic grooves. Table 23 — 23XRV Compressor Weights ENGLISH MOTOR SIZE* P,Q,R,S,T, U,V SI Compressor Weight† (lb) Stator Weight (lb) Rotor Weight (lb) Motor Terminal Cover (lb) 4866 441 229 46 Compressor Weight† (kg) Stator Weight (kg) Rotor Weight (kg) Motor Terminal Cover (kg) 2207 200 104 21 *Total compressor weight is the sum of the compressor components (compressor weight column), stator, and end bell weights. †Compressor size number is the first digit of the motor code. See Fig. 1. Table 24 — 23XRV Component Weights COMPONENT Isolation Valves Suction Elbow Discharge Pipe Assembly Control Center Vaporizer and Oil Sump Economizer FRAME 3 HEAT EXCHANGER lb kg 70 32 179 81 747 339 1650 749 700 318 542 246 104 FRAME 4 HEAT EXCHANGER lb kg 70 32 237 108 747 339 1650 749 700 318 542 246 FRAME 5 HEAT EXCHANGER lb kg 115 52 232 105 747 339 1650 749 700 318 542 246 Table 25A — 23XRV Waterbox Cover Weights — English (lb)* FRAMES 3, 4, AND 5 WATERBOX DESCRIPTION NIH,1 pass Cover 150 PSIG NIH,2 pass Cover 150 PSIG NIH,3 pass Cover 150 PSIG NIH Plain End, 150 PSIG MWB End Cover, 150 PSIG* NIH,1 pass Cover 300 PSIG NIH,2 pass Cover 300 PSIG NIH,3 pass Cover 300 PSIG NIH Plain End, 300 PSIG MWB End Cover, 300 PSIG* COOLER CONDENSER Frame 3 Frame 4 Frame 5 Frame 3 Frame 4 Frame 5 Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic Nozzles Flanged Nozzles Flanged Nozzles Flanged Nozzles Flanged Nozzles Flanged Nozzles Flanged 282 318 148 185 168 229 282 318 148 185 168 229 287 340 202 256 222 276 287 340 191 245 224 298 294 310 472 488 617 634 294 310 503 519 628 655 243 243 138 138 154 154 225 225 138 138 154 154 243/315 243/315 138/314 138/314 154/390 154/390 225/234 225/234 138/314 138/314 154/390 154/390 411 486 633 709 764 840 411 486 633 709 764 840 411 518 626 733 760 867 411 578 622 729 727 878 433 468 660 694 795 830 433 468 655 689 785 838 291 291 522 522 658 658 270 270 522 522 658 658 445/619 445/619 522/522 522/522 658/658 658/658 359/474 359/474 522/522 522/522 658/658 658/658 LEGEND MWB — Marine Waterbox NIH — Nozzle-In-Head *Rows with two entries list nozzle end weight/return end weights. NOTE: Weight for NIH 2-pass cover, 150 psig (1034 kPa), is included in the heat exchanger weights shown in Table 22. Table 25B — 23XRV Waterbox Cover Weights — SI (kg)* FRAMES 3, 4, AND 5 WATERBOX DESCRIPTION NIH,1 pass Cover 1034 kPa NIH,2 pass Cover 1034 kPa NIH,3 pass Cover 1034 kPa NIH Plain End, 1034 kPa MWB End Cover, 1034 kPa NIH,1 pass Cover 2068 kPa NIH,2 pass Cover 2068 kPa NIH,3 pass Cover 2068 kPa NIH Plain End, 2068 kPa MWB End Cover, 2068 kPa Frame 3 Victaulic Flanged Nozzles 128 144 130 154 133 141 110 110 110/143 110/143 186 220 186 235 196 212 132 132 202/281 202/281 COOLER Frame 4 Victaulic Flanged Nozzles 67 84 92 116 214 221 63 63 63/142 63/142 287 322 284 332 299 315 237 237 237/237 237/237 Frame 5 Victaulic Flanged Nozzles 76 104 101 125 280 288 70 70 70/177 70/177 347 381 344 393 361 376 298 298 298/298 298/298 Frame 3 Victaulic Flanged Nozzles 128 144 130 154 133 141 102 102 102/106 102/106 186 220 186 235 196 212 122 122 163/215 163/215 CONDENSER Frame 4 Victaulic Flanged Nozzles 67 84 87 111 228 235 63 63 63/142 63/142 287 322 282 331 297 313 237 237 237/237 237/237 LEGEND MWB — Marine Waterbox NIH — Nozzle-In-Head *Rows with two entries list nozzle end weight/return end weights. NOTE: Weight for NIH 2-pass cover, 150 psig (1034 kPa), is included in the heat exchanger weights shown in Table 22. Table 26 — Optional Storage Tank and/or Pumpout System Physical Data UNIT SIZE 28 52 TANK OUTSIDE DIAMETER in. 24.00 27.25 DRY WEIGHT mm 610 692 lb 2334 3414 kg 1059 1549 MAXIMUM REFRIGERANT CAPACITY ASHRAE/ANSI 15 VL-1963 HFC-134a HFC-134a lb kg lb kg 1860 844 1716 778 3563 1616 3286 1491 LEGEND ANSI — American National Standards Institute ARI — Air Conditioning and Refrigeration Institute ASHRAE — American Society of Heating, Refrigeration, and Air Conditioning Engineers NOTES: 1. ANSI/ASHRAE 15 — Safety Code for Mechanical Refrigeration 2. Dry weights include the pumpout condensing unit weight of 164 lb (75 kg). Table 27 — Optional Storage Tank and/or Pumpout System Electrical Data VOLTS-PH-HZ 208/230-3-50/60 460-3-60 400-3-50 LRA RLA MAX RLA 15.8 7.8 7.8 LEGEND — Locked Rotor Amps — Rated Load Amps 105 LRA 105.0 52.0 52.0 Frame 5 Victaulic Flanged Nozzles 76 104 102 135 285 297 70 70 70/177 70/177 346 381 330 398 356 380 298 298 298/298 298/298 Table 28 — 23XRV Compressor Torque Specification Chart PART NO. DESCRIPTION LOCATION/USAGE Hermetic Term, Outlet Casing Sub-ASS’Y Motor Side Seal Installation 8TR0116 M5 X 0.8 X 30LG SHCS GR 12.9 Inlet Seal Installation 8TR0117 M5 X 0.8 X 60LG SHCS GR 12.9 Inlet Seal Installation 8TR0303 M10 X 1.5 X 40LG SHCS GR 12.9 Bearing Cover Installation 8TR0304 M20 X 1.0 X 120LG SHCS GR 12.9 Outlet Casing Process Bolts Motor Terminal Cover Install 8TR0120 M12 X 1.75 X 50LG SHCS GR 12.9 and Lube Block Motor Housing and 8TR0122 M20 X 2.5 X 80LG SHCS GR 12.9 Bearing Cover Installation 8TR0381 M20 X 2.5 X 310LG HHCS GR 12.9 Discharge Flange 8TC0089C Set Screw M10 X 1.5 X 30 Motor Stator Sub-Assembly 1/ ″ NPTF Bearing Cover Lube Plug 8TC0290C 4 8TQ0189 M6 X 1.0 X 25LG SHCS GR 12.9 Rotor Caps & Male Axial Seal 3/ ″ SAE (9/ 8TC0107C Plug Installation 8 16 Thread) 3/ ″ SAE (9/ 8TR0106 Plug Installation 8 16 Thread) 3/ ″ SAE (11/ 8TC0109C Rotor Housing 4 16 Thread) 7/ ″ SAE (13/ Motor Housing Air Gap Check 8TR0128 8 16 Thread) HY85AA062 13/16″, Terminal Pin Body Motor Installation 5/ ″, Term Nut, Mtr Lead, Term Nut HY85AA062 Motor Installation 8 8TR0121 M16 X 2 X 70LG HHCS GR 10.9 Motor Rotor (Special) Lube Cover Plate Installation 8TC1044 M12 X 1.75 X 30LG SHCS GR 12.9 Valve Pad Installation 5/ ″ — 11UNC X 1.88″ LG HHCS GR 8 Economizer Cover 8TR0238 8 1/ -27 NPT (Brass) Orifice 8TR0357 Lube Block & Bearing Cover Plate 8 3/ ″ SAE (9/ Lube Block 8TR0358 8 16 Thread) Choke Orifice 7/ ″ 9 UNC X 2″ LG HHCS GR 8 8TR0363 Suction & Discharge Covers 8 8TR0115 GR HHCS LG SHCS UNC M5 X 0.8 X 16LG SHCS GR 12.9 — — — — — LEGEND Grade Hex Head Cap Screw Long Socket Head Cap Screw Unified Coarse Thread 106 TORQUE lb-ft Nm 5- 7 7- 9 5- 7 5- 7 50- 55 430-450 7- 9 7- 9 68- 75 583-610 90- 95 122-129 430-450 583-610 430-450 30- 35 20- 25 7- 9 17- 19 17- 19 83- 92 92-103 45- 55 40- 45 17- 22 583-610 41- 47 27- 34 9- 12 23- 26 23- 26 112-125 125-140 61- 75 54- 61 23- 30 87- 93 118-126 185-195 4- 6 17- 19 430-450 251-264 5- 8 23- 26 583-610 a23-1588 Fig. 53 — 23XRV Controls Schematic 107 a23-1589 Fig. 53 — 23XRV Controls Schematic (cont) 108 a23-1641 109 Fig. 53 — 23XRV Controls Schematic (cont) NOTES: 1. This feature is standard in the 23XR controls, but requires a controller with a non-grounded 4-20mA or 1-5Vdc output signal, not by Carrier. 2. This feature is standard in the 23XR controls, but requires an external controller with a non-grounded 4-20mA output signal, not by Carrier. 3. This feature is standard in the 23XR controls, but requires a sensor package option, by Carrier. (Item #3 see option listing.) 4. Pins shown for reference only. Actual pin layout not shown. 5. This feature is standard in the 23XR controls. Controllers monitoring this signal must have a non-grounded input with a maximum impedance of 500 ohms. 110 120A 118 116 114 K1A TS1 20A 600V 2 T1 T2 T3 A2 L1 L2 L3 A1 15 3 14 13 154 PRECHARGE CONTACTORS 1 32 PRECHARGE RESISTORS 10 , 600W 137A,B FU4 139 R4 12 8 FU7 127 13 6 4x 140J 2V FU5 FU6 150A 600V 129 119A 117 115 IND1 INPUT INDUCTOR MAIN CIRCUIT BREAKER CB1 GND 13 8 20A 600V 1uF 113 46uF ea 100k , 50W FILTER CAP ASSY a23-1633 1 4 R R5 131 FU8 130A 7 1 L1 155 A1 L3 L2 L1 13 5 L2 T1 14 A2 T3 T2 8 2 S 9 3 T K1B 15 6 6 L3 140 135 20A 600V 1 M3 M2 R6 134 FU9 2 1 2 1 FU3 FU2 FU1 152 157 A1 L3 L2 L1 13 124 123 126 125 1A/600V CLASS 'CC' 133 112 110 108 151 A2 T3 T2 T1 14 111 109 107 106 2 105 T2 L2 ST 103 T1 L1 104 CONTROL BREAKER (2 POLE, 15A) CB2 AC INPUT FIELD WIRING 158 K1C 141 ( M4 2 1 TB3 4 3 2 1 122 121 ) X2 X1 145 MECHANICAL JUMPER H1-H4: 380-415VAC H1-H5: 440-480VAC *T1 INPUT (50/60Hz) H* H1 (3.0kVA, 120V, 25A) CONTROL POWER TRANSFORMER T1 CLASS 'CC' 15A 5A FU10 FU11A FU11B 0.5A P1-10 F1 PILOT RELAY P1-9 P1-12 + (OPTIONAL) METERS W/SWITCH VM1 VOLTMETER A2 LINE SYNC PCB P1-14 P1-8 P1-7 P1-13 SW1 P2-3 I/O_ DGND +5V_I/O L2 B2 B1 A2 A1 L1 P2-18 P2-17 P2-14 P2-13 + AMMETER COIL_RETURN +24V_COIL AM1 OVER_TEMP_2 OVER_TEMP_1 14 13 12 11 8 9 10 +12VDC_I/O 7 6 5 4 I/O_AGND RECT_AC_LINE I/O_AGND -12VDC_I/O 3 2 1 P1 P2-8 L3 /BC>CA /AB>BC /CA>AB 150C 190 P2-9 P2-10 P2-7 P2-6 P2-5 P2-4 P2-1 P2-2 P1-5 101C P1-3 SIGNAL CONDITIONING AND ISOLATION P1-11 150D 101D P1-1 101A Fig. 54 — 23XRV VFD Schematic 120V SWITCHED 120V_N 142 150F 102C CLASS 'CC' 102B 15A 102A 187 TB1 A12 AC LINE I/O LOGIC COM LOGIC IN 1 LOGIC IN 2 LOGIC IN 3 LOGIC IN 4 DO NC5 DO COM5 DO NO5 DO NC6 DO COM6 DO NO6 AO I1AO I1+ EXV C2EXV C2+ DO NC1 DO COM1 DO NO1 DO NC2 DO COM2 DO NO2 DO NC3 DO COM3 DO NO3 DO NC4 DO COM4 DO NO4 AO V1AO V1+ EXT NTC EXT COM TB1 +24V LOGIC COM 24V COM DI1 DI2 DI3 DI4 DI5 DI6 DO NC1 DO COM1 DO NO1 DO NC2 DO COM2 DO NO2 AI I1AI I1+ AI I2AI I2+ -10V +10V AI V1AI V1+ AI V2AI V2+ Vref COM AO V1AO V1+ AO I1AO I1+ A1 VFD POWER MODULE L1 L2 L3 188 186 185 184 183 STANDARD I/O A22 150A 101B 150B 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 U V W 169 T3 6 GND M1 MOTOR 155 156 154 EXTERNAL- REF. ONLY T1 T2 COM 4 SHIELD B 5 A 2 TERM 174 173 17 5 17 7 3 1 170 1 2 3 4 5 6 7 8 9 10 15 16 17 18 19 20 21 22 23 24 O I L I NT / L OC K TB2 3 2 1 GND POS COM NEG CN3 EVAP PUMP EVAP PUMP COND PUMP COND PUMP TOWER FAN LOW TOWER FAN LOW TOWER FAN HIGH TOWER FAN HIGH TRIP ALARM TRIP ALARM RED BLK WHT HIGH PRESS SW HIGH PRESS SW 4-20mA PRESS REF4-20mA PRESS REF+ SPARE SAFETY SPARE SAFETY ICE BUILD ICE BUILD REMOTE START REMOTE START TB1 CN2 OIL INT/LOCK PE LL2 L L1 CN1A SH2 SH 1 CN1B NOTE: MOTOR OVERLOAD IS FACTORY PRE-SET. DO NOT ADJUST. 159 160 161 162 163 164 165 166 167 168 FOR TECHNICAL SUPPORT CALL 1-800-726-8112 A34 NTC A32 RS485 2 1 TB1 GATE-KILL A33 179 180 171 172 2 1 2 1 a23-1585 Fig. 55 — Typical Field Wiring Schematic 111 a23-1586 Fig. 55 — Typical Field Wiring Schematic (cont) 112 fig55-notes-chart Fig. 55 — Typical Field Wiring Schematic (cont) 113 NOTES FOR FIG. 55 GENERAL 1.0 Variable frequency drive (VFD) shall be designed and manufactured in accordance with Carrier engineering requirements. 1.1 All field-supplied conductors, devices and the fieldinstallation wiring, termination of conductors and devices, must be in compliance with all applicable codes and job specifications. 1.2 The routing of field-installed conduit and conductors and the location of field-installed devices, must not interfere with equipment access or the reading, adjusting or servicing of any component. 1.3 Equipment installation and all starting and control devices, must comply with details in equipment submittal drawings and literature. 1.4 Contacts and switches are shown in the position they would assume with the circuit de-energized and the chiller shutdown. 1.5 3.1 3.2 3.3 Ice build start/terminate device contacts, remote start/stop device contacts and spare safety device contacts, (devices not supplied by Carrier), must have 24 VAC rating. Max current is 60 mA, nominal current is 10 mA. Switches with gold plated bifurcated contacts are recommended. Remove jumper wire between TB1-19 and TB1-20 before connecting auxiliary safeties between these terminals. Each integrated contact output can control loads (VA) for evaporator pump, condenser pump, tower fan low, tower fan high, and alarm annunciator devices rated 5 amps at 115 VAC and up to 3 amps at 277 VAC. Control wiring required for Carrier to start pumps and tower fan motors and establish flows must be provided to assure machine protection. If primary pump, tower fan and flow control is by other means, also provide a parallel means for control by Carrier. Failure to do so could result in machine freeze-up or over-pressure. Do not use aluminum conductors. Contractor/installer assumes all liability resulting from the use of aluminum conductors within the VFD enclosure. 3.4 3.5 POWER WIRING TO VFD 2.0 Provide a means of disconnecting branch feeder power to VFD. Provide short circuit protection and interrupt capacity for branch feeder in compliance with all applicable codes. 2.1 If metal conduit is used for the power wires, the last 4 feet or greater should be flexible to avoid transmitting unit vibration into the power lines and to aid in serviceability. 2.2 Line side power conductor rating must meet VFD nameplate voltage and chiller minimum circuit ampacity. 2.3 Lug adapters may be required if installation conditions dictate that conductors be sized beyond the minimum ampacity required. Circuit breaker lugs will accommodate the quantity (#) and size cables (per phase) as shown in Table 29. 2.4 Compressor motor and controls must be grounded by using equipment grounding lug provided inside unit mounted VFD enclosure. CONTROL WIRING 3.0 Field-supplied control conductors to be at least 18 AWG or larger. 3.6 Do not use control transformers in the control center as the power source for external or field-supplied contactor coils, actuator motors or any other loads. Do not route control wiring carrying 30 V or less within a conduit or tray which has wires carrying 50 V or higher or along side wires carrying 50 V or higher. Spare 4-20 mA output signal is designed for controllers with a non-grounded 4-20 mA input signal and a maximum input impedance of 500 ohms. Flow devices to confirm evaporator or condenser pump flow are not required. However; if flow devices are used, wire as shown on drawing 23XRC1-1 (J3 lower). Remove jumper installed at these terminals and wire in a 4.3 K resistor in its place. CCM J3 (LOWER) a23-1587 The flow device and resistor must be installed in parallel at these terminals such that the resistor provides a signal when the flow device is open. Table 29 — Lug Capacity STANDARD 65K AIC LUG CAPACITY OPTIONAL 100K AIC LUG CAPACITY VFD (PER PHASE) (PER PHASE) MAX. INPUT AMPS. No. Conductors Conductor Range No. Conductors Conductor Range 225A 3 3/0 — 500MCM 2 3/0 — 250MCM 338A 3 3/0 — 500MCM 2 400 — 500MCM 440A 3 3/0 — 500MCM 2 400 — 500MCM 520A 3 3/0 — 500MCM 3 3/0 — 400MCM 608A 3 3/0 — 500MCM 3 3/0 — 400MCM NOTE: If larger lugs are required, they can be purchased from the manufacturer of the circuit breaker (Cutler-Hammer or Square D). 114 1 2 3 a23-1593 115 — — — Field Wiring DRAIN WIRE BLACK WHITE RED DRAIN WIRE NOTE: Field-supplied terminal strip must be located in control panel. 3 BLACK WHITE RED 2 Fig. 56 — CCN Communication Wiring For Multiple Chillers (Typical) GROUND LEGEND Carrier Comfort Network® (CCN) Interface Circuit Breakers Chiller Control Module (CCM) Factory Wiring BLACK RED WHITE 1 BLACK WHITE RED DRAIN WIRE BLACK WHITE RED DRAIN WIRE a23-1597 116 Fig. 57 — Lead/Lag Control Wiring a23-1598 117 Fig. 57 — Lead/Lag Control Wiring (cont) APPENDIX A — ICVC PARAMETER INDEX PARAMETER 1st Current Alarm State 20mA Demand Limit Opt (Demand Limit & KW Ramp) 2nd Current Alarm State 3rd Current Alarm State 4th Current Alarm State 5th Current Alarm State Active Delta P Active Delta T Active Demand Limit Actual VFD Speed Actual VFD Speed Actual VFD Speed Actual VFD Speed (At Last Fault) Address # Alarm Configuration ALARM HISTORY Alarm Relay Test Alarm Routing (Alarm Configuration) ALERT HISTORY Amps or KW Load Ramp %/Min (Demand Limit and KW Ramp) Amps/KW Ramp ATTACH TO NETWORK DEVICE Auto Chilled Liq Reset Auto Demand Limit Input Auto Restart Option Average Line Current Average Line Voltage Average Load Current Base Demand Limit Baud Rate Broadcast Option (CCN Occupancy Config) Bus # Calc Evap Sat Temp Calc Evap Sat Temp Cap Delta (Capacity Control) Capacity Control Capacity Control CCN CCN Mode ? CCN Occupancy Config CCN Time Schedule CCN Time Schedule(OCCPC03S) Chill Liq Pulldown/Min Chilled Liquid Deadband Chilled Liquid Delta P Chilled Liquid Delta P Chilled Liquid Delta P Chilled Liquid Delta T Chilled Liquid Flow Chilled Liquid Flow Chilled Liquid Pump Chilled Liquid Pump Chilled Liquid Temp Chilled Medium Chilled Water Temp Chiller Fault State (At Last Fault) Chiller Start/Stop CHL Delta T->Full Reset (Temperature Reset Type 3) CHL Delta T->No Reset (Temperature Reset Type 3)) CHW Setpt Reset Value Commanded State Common Sensor Option MENU SOFTKEY TABLE SERVICE CONTROL ALGORITHM STATUS SCREEN NAME CUR_ALRM CONFIGURABLE SERVICE EQUIPMENT SERVICE RAMP_DEM X SERVICE SERVICE SERVICE SERVICE STATUS STATUS STATUS SERVICE STATUS STATUS SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS X EQUIPMENT CONFIGURATION CUR_ALRM CUR_ALRM CUR_ALRM CUR_ALRM HEAT_EX HEAT_EX MAINSTAT CAPACITY COMPRESS POWER VFD_HIST ICVC CONFIGURATION NET_OPT CONTROL TEST EQUIPMENT CONFIGURATION DISCRETE OUTPUTS NET_OPT X X SERVICE EQUIPMENT SERVICE RAMP_DEM X SERVICE SERVICE STATUS STATUS SERVICE STATUS STATUS STATUS SETPOINT SERVICE SERVICE SERVICE STATUS SERVICE SERVICE SERVICE SERVICE CONTROL ALGORITHM STATUS CAPACITY STATUS SERVICE SCHEDULE SERVICE STATUS SERVICE STATUS SERVICE SERVICE STATUS SERVICE STATUS SERVICE STATUS STATUS SERVICE SERVICE SERVICE STATUS CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS EQUIPMENT SERVICE EQUIPMENT CONFIGURATION CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS EQUIPMENT SERVICE EQUIPMENT CONFIGURATION EQUIPMENT CONFIGURATION EQUIPMENT SERVICE CONTROL TEST CONTROL TEST CONTROL TEST CONTROL TEST EQUIPMENT SERVICE CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS MAINSTAT MAINSTAT OPTIONS POWER POWER POWER SETPOINT ICVC CONFIGURATION NET_OPT ICVC CONFIGURATION HEAT_EX OVERRIDE CAPACITY CAPACITY SETUP2 DEFAULT SCREEN ICVC_PWD NET_OPT OCCP03S OCCDEFCS HEAT_EX SETUP1 HEAT_EX PRESSURE TRANSDUCERS PUMPS HEAT_EX PUMPS STARTUP PUMPS STARTUP MAINSTAT SETUP1 WSMCHLRE VFD_HIST MAINSTAT X X X X X X X X X X X X X X X SERVICE EQUIPMENT SERVICE TEMP_CTL X SERVICE EQUIPMENT SERVICE TEMP_CTL X SERVICE SERVICE SERVICE CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS EQUIPMENT SERVICE WSMCHLRE WSMCHLRE LEADLAG X 118 APPENDIX A — ICVC PARAMETER INDEX (cont) PARAMETER Comp Discharge Alert Comp Discharge Alert Comp Discharge Temp Comp Discharge Temp Comp Discharge Temp Comp Maximum Speed Comp Maximum Speed Comp Maximum Speed Comp Maximum Speed Comp Minimum Speed Comp Minimum Speed Comp Minimum Speed Comp Minimum Speed Comp Motor Frequency Comp Motor Frequency Comp Motor Frequency Comp Motor Frequency Comp Motor Frequency (At Last Fault) Comp Motor RPM Comp Motor RPM Comp Motor RPM Comp Motor RPM Comp Motor RPM (At Last Fault) Comp Motor Temp Override Comp Motor Temp Override Comp Motor Winding Temp Comp Motor Winding Temp Comp Motor Winding Temp Compressor 100% Speed Compressor Ontime Compressor Ontime Cond Approach Alert Cond Flow Delta P Cutout Cond Press Override Cond Press Override Condenser Approach Condenser Freeze Point Condenser High Pressure Condenser Liquid Delta P Condenser Liquid Delta P Condenser Liquid Delta P Condenser Liquid Flow Condenser Liquid Flow Condenser Liquid Pump Condenser Liquid Pump Condenser Pressure Condenser Pressure Condenser Pressure Condenser Refrig Temp Condenser Refrig Temp Condenser Temperature CONSM01E Control Mode Control Point Control Point Error (Capacity Control) Control Point Source Control Point Source Control Point (Capacity Control) CONTROL TEST Current CHW Setpoint Current Date Current Mode (Lead/Lag) Current Time MENU SOFTKEY SERVICE SERVICE STATUS SERVICE SERVICE STATUS STATUS STATUS SERVICE SERVICE STATUS STATUS STATUS STATUS SERVICE STATUS STATUS SERVICE SERVICE STATUS STATUS STATUS SERVICE SERVICE SERVICE STATUS SERVICE SERVICE SERVICE STATUS SERVICE SERVICE SERVICE SERVICE STATUS SERVICE STATUS STATUS SERVICE SERVICE SERVICE STATUS SERVICE STATUS STATUS SERVICE SERVICE STATUS SERVICE SERVICE STATUS STATUS SERVICE SETPOINT SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE TABLE CONTROL ALGORITHM STATUS EQUIPMENT SERVICE CONTROL ALGORITHM STATUS CONTROL TEST CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS EQUIPMENT SERVICE CONTROL ALGORITHM STATUS CONTROL TEST VFD CONFIG DATA EQUIPMENT SERVICE EQUIPMENT SERVICE CONTROL ALGORITHM STATUS EQUIPMENT SERVICE EQUIPMENT SERVICE CONTROL TEST CONTROL TEST CONTROL TEST CONTROL TEST CONTROL ALGORITHM STATUS CONTROL TEST CONTROL ALGORITHM STATUS EQUIPMENT CONFIGURATION CONTROL ALGORITHM STATUS EQUIPMENT SERVICE CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS 119 SCREEN NAME OVERRIDE SETUP1 COMPRESS OVERRIDE THERMISTORS COMPRESS POWER STARTUP CAPACITY CAPACITY COMPRESS POWER STARTUP POWER CAPACITY COMPRESS STARTUP VFD_HIST CAPACITY COMPRESS POWER STARTUP VFD_HIST OVERRIDE SETUP1 COMPRESS OVERRIDE THERMISTORS VFD_CONF DEFAULT SCREEN MAINSTAT SETUP1 SETUP1 OVERRIDE SETUP1 HEAT_EX SETUP1 VFD_STAT HEAT_EX PRESSURE TRANSDUCERS PUMPS PUMPS STARTUP PUMPS STARTUP HEAT_EX OVERRIDE PRESSURE TRANSDUCERS HEAT_EX OVERRIDE DEFAULT SCREEN CONSM01E MAINSTAT MAINSTAT CAPACITY SETPOINT TEMP_CTL CAPACITY WSMCHLRE TIME AND DATE LL_MAINT TIME AND DATE CONFIGURABLE X X X X X X X X X X X X X X X X APPENDIX A — ICVC PARAMETER INDEX (cont) PARAMETER MENU SOFTKEY Date SERVICE Day of Week SERVICE Daylight Savings SERVICE DC Bus Voltage STATUS DC Bus Voltage Reference STATUS DC Bus Voltage Reference (At Last Fault) SERVICE DC Bus Voltage (At Last Fault) SERVICE Decrease Ramp Time SERVICE Degrees Reset at 20 mA SERVICE (Temperature Reset Type 1) Degrees Reset (Temperature Reset Type 2) SERVICE Degrees Reset (Temperature Reset Type 3) SERVICE Delta P at 0% (4 mA) (Head Pressure Reference) SERVICE Delta P at 100% (20 mA) SERVICE (Head Pressure Reference) Demand Kilowatts STATUS Demand Limit and KW Ramp SERVICE Demand Limit At 20 mA (Demand Limit & KW Ramp) SERVICE Demand Limit Decrease (Loadshed Function) SERVICE Demand Limit Inhibit SERVICE Demand Limit Prop Band SERVICE (Demand Limit & KW Ramp) Demand Limit Source SERVICE (Demand Limit & KW Ramp) Demand Watts Interval SERVICE Disable Service Password STATUS Discharge Pressure SERVICE Discharge Superheat STATUS Discharge Superheat SERVICE Discrete Outputs Control Test SERVICE ECL Control Option (Control Point) SERVICE ECL Delta T (Capacity Control) SERVICE ECL Reset (Capacity Control) SERVICE ECL Setpoint (Base Demand Limit Control Point) SETPOINT Emergency Stop STATUS Enable Reset Type (Temperature Reset) SERVICE Entering Chilled Liquid SERVICE Entering Chilled Liquid Entering Chilled Liquid STATUS Entering Chilled Liquid SERVICE Entering Cond Liquid STATUS Entering Cond Liquid SERVICE Entering Cond Liquid Equipment Status SERVICE Evap Approach Alert SERVICE Evap Flow Delta P Cutout SERVICE Evap Refrig Liquid Temp STATUS Evap Refrig Liquid Temp SERVICE Evap Refrig Trippoint SERVICE Evap Sat Override Temp SERVICE Evaporator Approach STATUS Evaporator Pressure STATUS Evaporator Pressure SERVICE Evaporator Temperature Flow Delta P Display SERVICE Flux Current STATUS Flux Current (At Last Fault) SERVICE Frequency Fault STATUS Full Load Point (T2,P2)(Hot Gas Bypass) SERVICE Ground Fault STATUS Ground Fault Current STATUS Ground Fault Current (At Last Fault) SERVICE Group Number (Loadshed Function) SERVICE TABLE CONFIGURABLE X X CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS VFD CONFIG DATA SCREEN NAME TIME AND DATE TIME AND DATE BRODEF POWER POWER VFD_HIST VFD_HIST VFD_CONF EQUIPMENT SERVICE TEMP_CTL X EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT SERVICE TEMP_CTL TEMP_CTL OPTIONS X X X EQUIPMENT SERVICE OPTIONS X EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT CONFIGURATION CONTROL ALGORITHM STATUS POWER RAMP_DEM RAMP_DEM NET_OPT CAPACITY EQUIPMENT SERVICE RAMP_DEM EQUIPMENT CONFIGURATION X X X X EQUIPMENT SERVICE RAMP_DEM X EQUIPMENT SERVICE RAMP_DEM ICVC_PWD PRESSURE TRANSDUCERS COMPRESS OVERRIDE CONTROL TEST TEMP_CTL CAPACITY CAPACITY SETPOINT MAINSTAT TEMP_CTL CAPACITY DEFAULT SCREEN HEAT_EX THERMISTORS HEAT_EX THERMISTORS DEFAULT SCREEN WSMCHLRE SETUP1 SETUP1 HEAT_EX THERMISTORS SETUP1 OVERRIDE HEAT_EX HEAT_EX PRESSURE TRANSDUCERS DEFAULT SCREEN SETUP1 POWER VFD_HIST VFD_STAT OPTIONS VFD_STAT POWER VFD_HIST NET_OPT X X CONTROL TEST CONTROL ALGORITHM STATUS EQUIPMENT SERVICE CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS EQUIPMENT SERVICE CONTROL ALGORITHM STATUS CONTROL TEST CONTROL TEST CONTROL ALGORITHM STATUS EQUIPMENT SERVICE EQUIPMENT SERVICE CONTROL TEST EQUIPMENT SERVICE CONTROL ALGORITHM STATUS CONTROL TEST EQUIPMENT SERVICE CONTROL ALGORITHM STATUS EQUIPMENT SERVICE CONTROL ALGORITHM STATUS EQUIPMENT CONFIGURATION 120 X X X X X X X X X APPENDIX A — ICVC PARAMETER INDEX (cont) PARAMETER Head Pressure Output Control Test Head Pressure Reference Head Pressure Reference Head Pressure Reference HGBP Deadband HGBP Delta P1(Min Load Point) HGBP Delta P2(Full Load Point) HGBP Delta T HGBP Delta T1(Min Load Point) HGBP Delta T2(Full Load Point) HGBP On Delta T HGBP Off Delta T High DC Bus Voltage High Line Voltage Holiday HOLIDAYS Hot Gas Bypass HGBP Option Hot Gas Bypass Relay Hot Gas Bypass Relay Test Humidity Sensor Input Humidity Sensor Input Ice Build Contact Ice Build Control Ice Build Option (Ice Build Control) Ice Build Recycle Ice Build Setpoint Ice Build Termination Ice Build Time Schedule Ice Build Time Schedule(OCCPC02S) ICVC Address # ICVC Baud Rate ICVC Bus # ICVC CONFIGURATION ICVC LID Language ICVC Model # ICVC Reference # ICVC Serial # ICVC Software Part # ICVC US IMP/Metric Increase Ramp Time Inverter Overcurrent Inverter Overload Inverter Overtemp Inverter Power Fault Inverter PWM Frequency Inverter Temp Override Inverter Temp Override Inverter Temperature Inverter Temperature Inverter Temperature (At Last Fault) LAG % Capacity LAG Address LAG CHILLER: Mode LAG START Time LAG START Timer LAG STOP Time LAG STOP Timer LCL Reset (Capacity Control) LCL Setpoint (Base Demand Limit Control Point) LEAD CHILLER in Control Lead Lag Control Lead Lag Control LEAD/LAG: Configuration LEAD/LAG: Configuration MENU SOFTKEY SERVICE SERVICE STATUS SERVICE SERVICE SERVICE SERVICE STATUS SERVICE SERVICE SERVICE SERVICE STATUS STATUS SERVICE SERVICE SERVICE SERVICE STATUS SERVICE STATUS SERVICE STATUS SERVICE SERVICE SERVICE SETPOINT SERVICE SCHEDULE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE STATUS STATUS STATUS STATUS SERVICE SERVICE SERVICE SERVICE STATUS SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SETPOINT SERVICE SERVICE SERVICE SERVICE SERVICE TABLE CONTROL TEST EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT CONFIGURATION EQUIPMENT SERVICE EQUIPMENT SERVICE CONTROL TEST CONTROL TEST EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT CONFIGURATION VFD CONFIG DATA VFD CONFIG DATA CONTROL ALGORITHM STATUS EQUIPMENT SERVICE CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS EQUIPMENT SERVICE EQUIPMENT SERVICE CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS EQUIPMENT SERVICE CONTROL ALGORITHM STATUS EQUIPMENT SERVICE CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS EQUIPMENT SERVICE CONTROL ALGORITHM STATUS EQUIPMENT SERVICE CONTROL ALGORITHM STATUS 121 SCREEN NAME CONTROL TEST HEAD PRESSURE OUTPUT HEAT_EX OPTIONS OPTIONS OPTIONS OPTIONS HEAT_EX OPTIONS OPTIONS OPTIONS OPTIONS VFD_STAT VFD_STAT TIME AND DATE HOLIDAYS OPTIONS OPTIONS HEAT_EX DISCRETE OUTPUTS POWER PRESSURE TRANSDUCERS MAINSTAT OPTIONS OPTIONS OPTIONS SETPOINT OPTIONS OCCP02S OCCDEFCS ICVC CONFIGURATION ICVC CONFIGURATION ICVC CONFIGURATION CONFIGURABLE X ICVC CONFIGURATION ICVC CONFIGURATION ICVC CONFIGURATION ICVC CONFIGURATION ICVC CONFIGURATION ICVC CONFIGURATION VFD_CONF VFD_STAT POWER VFD_STAT VFD_STAT VFD_CONF OVERRIDE SETUP1 OVERRIDE POWER VFD_HIST LEADLAG LEADLAG LL_MAINT LL_MAINT LEADLAG LL_MAINT LEADLAG CAPACITY SETPOINT LL_MAINT LEADLAG LL_MAINT LEADLAG LL_MAINT X X X X X X X X X X X X X X X X X X X X X X X X X X X X X APPENDIX A — ICVC PARAMETER INDEX (cont) PARAMETER Leaving Chilled Liquid Leaving Chilled Liquid Leaving Chilled Liquid Leaving Chilled Liquid Leaving Cond Liquid Leaving Cond Liquid Leaving Cond Liquid LID Language Line Active Current Line Active Current (At Last Fault) Line Active Voltage Line Active Voltage (At Last Fault) Line Current % Imbalance Line Current Imbal Time Line Current Imbalance Line Current Imbalance Line Current Imbalance (At Last Fault) Line Current Ph 1(R) Line Current Ph 1(R)(At Last Fault) Line Current Ph 2(S) Line Current Ph 2(S)(At Last Fault) Line Current Ph 3(T) Line Current Ph 3(T)(At Last Fault) Line Frequency Line Frequency (At Last Fault) Line Kilowatts Line Phase Reversal Line Power Factor Line Power Factor (At Last Fault) Line Reactive Current Line Reactive Current (At Last Fault) Line Reactive Voltage Line Reactive Voltage (At last Fault) Line Volt Imbalance Time Line Voltage % Imbalance Line Voltage Imbalance Line Voltage Imbalance Line Voltage Imbalance (At Last Fault) Line Voltage Ph 1(RS) Line Voltage Ph 1(RS)(At Last Fault) Line Voltage Ph 2(ST) Line Voltage Ph 2(ST)(At Last Fault) Line Voltage Ph 3(TR) Line Voltage Ph 3(TR)(at Last Fault) Liquid Flow Verify Time Load Balance Option Load Balance Option Load Current Ph 1(U) Load Current Ph 1(U)(At Last Fault) Load Current Ph 2(V) Load Current Ph 2(V)(At Last Fault) Load Current Ph 3(W) Load Current Ph 3(W)(At Last Fault) Loadshed Loadshed Function Loadshed Function Loadshed Timer LOCAL Local Network Device Local Time Schedule Local Time Schedule(OCCPC01S) LOG OUT OF DEVICE Low DC Bus Voltage Low Line Voltage MENU SOFTKEY TABLE SERVICE CONTROL ALGORITHM STATUS STATUS SERVICE STATUS SERVICE SERVICE STATUS SERVICE STATUS SERVICE SERVICE SERVICE STATUS STATUS SERVICE STATUS SERVICE STATUS SERVICE STATUS SERVICE STATUS SERVICE STATUS STATUS STATUS SERVICE STATUS SERVICE STATUS SERVICE SERVICE SERVICE STATUS STATUS SERVICE STATUS SERVICE STATUS SERVICE STATUS SERVICE SERVICE SERVICE SERVICE STATUS SERVICE STATUS SERVICE STATUS SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SCHEDULE SERVICE SERVICE STATUS STATUS CONTROL TEST CONTROL TEST CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS VFD CONFIG DATA VFD CONFIG DATA CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS VFD CONFIG DATA VFD CONFIG DATA CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS EQUIPMENT SERVICE EQUIPMENT SERVICE CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS EQUIPMENT CONFIGURATION CONTROL ALGORITHM STATUS EQUIPMENT CONFIGURATION SCREEN NAME CONFIGURABLE CAPACITY DEFAULT SCREEN HEAT_EX THERMISTORS HEAT_EX THERMISTORS DEFAULT SCREEN ICVC CONFIGURATION X POWER VFD_HIST POWER VFD_HIST VFD_CONF X VFD_CONF X POWER VFD_STAT VFD_HIST POWER VFD_HIST POWER VFD_HIST POWER VFD_HIST POWER VFD_HIST POWER VFD_STAT POWER VFD_HIST POWER VFD_HIST POWER VFD_HIST VFD_CONF X VFD_CONF X POWER VFD_STAT VFD_HIST POWER VFD_HIST POWER VFD_HIST POWER VFD_HIST SETUP1 X LEADLAG X LL_MAINT POWER VFD_HIST POWER VFD_HIST POWER VFD_HIST LOADSHED LOADSHED NET_OPT LOADSHED DEFAULT SCREEN X ATTACH TO NETWORK DEVICE X OCCP01S X OCCDEFCS X VFD_STAT VFD_STAT 122 APPENDIX A — ICVC PARAMETER INDEX (cont) PARAMETER Maximum Loadshed Time Min. Load Point (T1,P1)(Hot Gas ByPass) Minimum Output (Head Pressure Reference) Model # Motor Amps Not Sensed Motor Current Imbal Time Motor Current Imbalance Motor Current Imbalance Motor Current Imbalance (At Last Fault) Motor Current% Imbalance Motor Kilowatt Hours Motor Kilowatts Motor Nameplate Amps Motor Nameplate KW Motor Nameplate RPM Motor Nameplate Voltage Motor Overload Motor Overload Motor Overload (At Last Fault) Motor Power Factor Motor Power Factor (At Last Fault) Motor Rated Load Amps Motor Rated Load KW OCCP01S (Local Time Schedule) OCCP02S (Ice Build Time Schedule) OCCP03S (CCN Time Schedule) OCCPC01S(Local Time Schedule) OCCPC02S(Ice Build Time Schedule) OCCPC03S(CCN Time Schedule) Occupied? Oil Heater Relay Oil Heater Relay Test Oil Press Verify Time Oil Pressure Acceptable? Oil Pressure Delta P Oil Pressure Delta P Oil Pressure Delta P Oil Pressure Delta P Oil Pressure Delta P Oil Pump Relay Oil Pump Relay Oil Pump Relay Oil Reclaim Output Oil Reclaim Output Oil Reclaim Output Test Oil Sump Temp Oil Sump Temp Oil Sump Temp Oil Sump Temp Password (SERVICE) Password (VFD CONFIG DATA) Percent Line Current Percent Line Current Percent Line Current Percent Line Kilowatts Percent Line Kilowatts Percent Line Voltage Percent Load Current Percent Motor Kilowatts PPM at 20 mA (Refrigerant Leak Option) Pressure Transducers Control Test PRESTART FAULT Time PRESTART FAULT Timer PRIMARY MESSAGE MENU SOFTKEY TABLE SERVICE EQUIPMENT CONFIGURATION SERVICE EQUIPMENT SERVICE SERVICE EQUIPMENT SERVICE SERVICE STATUS SERVICE VFD CONFIG DATA STATUS STATUS SERVICE CONTROL ALGORITHM STATUS SERVICE VFD CONFIG DATA STATUS STATUS SERVICE VFD CONFIG DATA SERVICE VFD CONFIG DATA SERVICE VFD CONFIG DATA SERVICE VFD CONFIG DATA STATUS STATUS SERVICE CONTROL ALGORITHM STATUS STATUS SERVICE CONTROL ALGORITHM STATUS SERVICE VFD CONFIG DATA SERVICE VFD CONFIG DATA SCHEDULE SCHEDULE SCHEDULE SERVICE EQUIPMENT CONFIGURATION SERVICE EQUIPMENT CONFIGURATION SERVICE EQUIPMENT CONFIGURATION STATUS STATUS SERVICE CONTROL TEST SERVICE EQUIPMENT SERVICE SERVICE CONTROL TEST STATUS SERVICE SERVICE STATUS STATUS SERVICE STATUS STATUS STATUS SERVICE STATUS STATUS SERVICE SERVICE SERVICE STATUS STATUS STATUS STATUS STATUS STATUS STATUS SERVICE SERVICE SERVICE SERVICE CONTROL TEST CONTROL TEST CONTROL TEST CONTROL TEST CONTROL TEST EQUIPMENT SERVICE CONTROL ALGORITHM STATUS EQUIPMENT SERVICE 123 SCREEN NAME NET_OPT OPTIONS OPTIONS ICVC CONFIGURATION VFD_STAT VFD_CONF POWER VFD_STAT VFD_HIST VFD_CONF POWER POWER VFD_CONF VFD_CONF VFD_CONF VFD_CONF POWER VFD_STAT VFD_HIST POWER VFD_HIST VFD_CONF VFD_CONF OCCP01S OCCP02S OCCP03S OCCDEFCS OCCDEFCS OCCDEFCS MAINSTAT COMPRESS DISCRETE OUTPUTS SETUP1 PUMPS COMPRESS DEFAULT SCREEN PRESSURE TRANSDUCERS PUMPS STARTUP COMPRESS PUMPS STARTUP HEAT_EX STARTUP OIL RECLAIM OUTPUT COMPRESS DEFAULT SCREEN STARTUP THERMISTORS ICVC CONFIGURATION VFD CONFIG DATA DEFAULT SCREEN MAINSTAT POWER MAINSTAT POWER POWER POWER POWER OPTIONS CONTROL TEST LL_MAINT LEADLAG DEFAULT SCREEN CONFIGURABLE X X X X X X X X X X X X X X X X X X X X X X X X X APPENDIX A — ICVC PARAMETER INDEX (cont) PARAMETER Proportional Dec Band (Capacity Control) Proportional ECL Gain (Capacity Control) Proportional Inc Band (Capacity Control) Pulldown Ramp Type: PULLDOWN Time PULLDOWN Timer Pulldown: Delta T / Min Pumpdown/Lockout Control Test Pumpdown/Lockout Control Test Pumps Control Test Rated Line Amps Rated Line Kilowatts Rated Line Voltage Re-alarm Time (Alarm Configuration) Reclaim Delta T Recovery Start Request (Lag Chiller) Recovery Start Request (Standby Chiller) Rectifier Overcurrent Rectifier Overload Rectifier Overtemp Rectifier Power Fault Rectifier Temp Override Rectifier Temp Override Rectifier Temperature Rectifier Temperature Rectifier Temperature (At Last Fault) Recycle Control Redline (Loadshed Function) Reference # Refrig Leak Alarm PPM (Refrigerant Leak Option) Refrig Leak Sensor PPM Refrig Override Delta T Refrigerant Leak Option Relative Humidity Relative Humidity Remote Contacts Option Remote Reset Option Remote Reset Sensor Remote Reset Sensor Remote Start Contact Remote Temp->Full Reset (Temperature Reset Type 2) Remote Temp->No Reset (Temperature Reset Type 2) RESET Reset Alarm ? RESET TYPE 1(Temperature Reset) RESET TYPE 2(Temperature Reset) RESET TYPE 3(Temperature Reset) Restart Delta T (Recycle Control) Run Status Run Status (Lag Chiller) Run Status (Standby Chiller) RUNTM01E Satisfied? (Pulldown) Schedule Number (CCN Occupancy Config) SECONDARY MESSAGE Serial # Service Ontime SERVICE Password Setpoint - ECL (Base Demand Limit Control Point) Setpoint - LCL (Base Demand Limit Control Point) Shunt Trip Relay Shunt Trip Relay Test Shutdown Delta T (Recycle Control) MENU SOFTKEY SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE STATUS SERVICE SERVICE STATUS STATUS STATUS STATUS SERVICE SERVICE SERVICE STATUS SERVICE SERVICE SERVICE SERVICE SERVICE STATUS SERVICE SERVICE STATUS SERVICE SERVICE STATUS STATUS SERVICE STATUS TABLE EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT SERVICE CONTROL ALGORITHM STATUS EQUIPMENT SERVICE CONTROL ALGORITHM STATUS CONTROL TEST VFD CONFIG DATA VFD CONFIG DATA VFD CONFIG DATA EQUIPMENT CONFIGURATION CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS EQUIPMENT SERVICE CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS EQUIPMENT SERVICE CONTROL ALGORITHM STATUS EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT SERVICE CONTROL TEST EQUIPMENT SERVICE CONTROL TEST SCREEN NAME SETUP2 SETUP2 SETUP2 RAMP_DEM LL_MAINT LEADLAG LL_MAINT CONTROL TEST Pumpdown/Lockout CONTROL TEST VFD_CONF VFD_CONF VFD_CONF NET_OPT HEAT_EX LL_MAINT LL_MAINT VFD_STAT POWER VFD_STAT VFD_STAT OVERRIDE SETUP1 OVERRIDE POWER VFD_HIST SETUP1 LOADSHED ICVC CONFIGURATION OPTIONS MAINSTAT SETUP1 OPTIONS POWER PRESSURE TRANSDUCERS OPTIONS ICVC_PWD MAINSTAT THERMISTORS MAINSTAT CONFIGURABLE X X X X X X X X X X X X X X X X X SERVICE EQUIPMENT SERVICE TEMP_CTL X SERVICE EQUIPMENT SERVICE TEMP_CTL X DEFAULT SCREEN ICVC_PWD TEMP_CTL TEMP_CTL TEMP_CTL SETUP1 MAINSTAT LL_MAINT LL_MAINT RUNTM01E LL_MAINT NET_OPT DEFAULT SCREEN ICVC CONFIGURATION MAINSTAT ICVC CONFIGURATION SETPOINT SETPOINT STARTUP DISCRETE OUTPUTS SETUP1 X X STATUS SERVICE SERVICE SERVICE SERVICE STATUS SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE STATUS SERVICE SETPOINT SETPOINT STATUS SERVICE SERVICE EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT SERVICE CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS EQUIPMENT CONFIGURATION CONTROL ALGORITHM STATUS EQUIPMENT CONFIGURATION CONTROL TEST EQUIPMENT SERVICE 124 X X X X X X X X X APPENDIX A — ICVC PARAMETER INDEX (cont) PARAMETER Single Cycle Dropout Single Cycle Dropout Skip Frequency 1 Skip Frequency 2 Skip Frequency 3 Skip Frequency Band Soft Stop Amps Threshold Software Part # Spare Alert/Alarm Enable Spare Safety Input Spare Temp #1 Enable (Spare Alert/Alarm Enable) Spare Temp #1 Limit (Spare Alert/Alarm Enable) Spare Temp #2 Enable (Spare Alert/Alarm Enable) Spare Temp #2 Limit (Spare Alert/Alarm Enable) Spare Temperature 1 Spare Temperature 1 Spare Temperature 1 Spare Temperature 2 Spare Temperature 2 Spare Temperature 2 Stall Delta % Amps (Stall Protection) Stall Protection Stall Protection Counts Stall Time Period (Stall Protection) STANDBY % Capacity STANDBY Address STANDBY Chiller Option STANDBY CHILLER: Mode Start Acceleration Fault Start Advance (Daylight Savings) Start Complete Start Complete Start Day of Week (Daylight Savings) Start Inhibit Timer Start Month (Daylight Savings) Start Time (Daylight Savings) Start Week (Daylight Savings) Start/Stop (Lag Chiller) Start/Stop (Standby Chiller) Starts in 12 Hours Stop Back (Daylight Savings) Stop Complete Stop Complete Stop Day of Week (Daylight Savings) Stop Fault Stop Month (Daylight Savings) Stop Time (Daylight Savings) Stop Week (Daylight Savings) System Alert/Alarm Target VFD Speed Target VFD Speed Temp Pulldown Ramp/Min (Control Point) Temperature Reset Temperature Reset Terminate Lockout Thermistors Control Test TIME AND DATE Time Broadcast Enable Torque Current Torque Current (At Last Fault) Total Compressor Starts Total Error + Resets (Capacity Control) MENU SOFTKEY SERVICE STATUS SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE STATUS SERVICE SERVICE SERVICE SERVICE STATUS SERVICE SERVICE STATUS SERVICE SERVICE SERVICE SERVICE STATUS SERVICE SERVICE SERVICE SERVICE SERVICE STATUS SERVICE STATUS STATUS SERVICE STATUS SERVICE SERVICE SERVICE SERVICE SERVICE STATUS SERVICE STATUS STATUS SERVICE STATUS SERVICE SERVICE SERVICE STATUS SERVICE STATUS SERVICE STATUS SERVICE SERVICE SERVICE SERVICE SERVICE STATUS SERVICE STATUS SERVICE TABLE VFD CONFIG DATA VFD CONFIG DATA VFD CONFIG DATA VFD CONFIG DATA VFD CONFIG DATA EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT SERVICE CONTROL ALGORITHM STATUS CONTROL TEST CONTROL ALGORITHM STATUS CONTROL TEST EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT SERVICE CONTROL ALGORITHM STATUS EQUIPMENT CONFIGURATION EQUIPMENT CONFIGURATION EQUIPMENT CONFIGURATION EQUIPMENT CONFIGURATION EQUIPMENT CONFIGURATION CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS EQUIPMENT CONFIGURATION EQUIPMENT CONFIGURATION EQUIPMENT CONFIGURATION EQUIPMENT CONFIGURATION EQUIPMENT CONFIGURATION CONTROL ALGORITHM STATUS EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT CONFIGURATION CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS 125 SCREEN NAME VFD_CONF VFD_STAT VFD_CONF VFD_CONF VFD_CONF VFD_CONF OPTIONS ICVC CONFIGURATION SETUP1 STARTUP SETUP1 SETUP1 SETUP1 SETUP1 COMPRESS LL_MAINT THERMISTORS COMPRESS LL_MAINT THERMISTORS OPTIONS OPTIONS COMPRESS OPTIONS LEADLAG LEADLAG LEADLAG LL_MAINT VFD_STAT BRODEF STARTUP VFD_STAT BRODEF MAINSTAT BRODEF BRODEF BRODEF LL_MAINT LL_MAINT MAINSTAT BRODEF STARTUP VFD_STAT BRODEF VFD_STAT BRODEF BRODEF BRODEF MAINSTAT CAPACITY COMPRESS TEMP_CTL MAINSTAT TEMP_CTL TERMINATE LOCKOUT CONTROL TEST TIME AND DATE BRODEF POWER VFD_HIST MAINSTAT CAPACITY CONFIGURABLE X X X X X X X X X X X X X X X X X X X X X X X X X X X X APPENDIX A — ICVC PARAMETER INDEX (cont) PARAMETER Tower Fan High Setpoint Tower Fan Relay High Tower Fan Relay High Test Tower Fan Relay Low Tower Fan Relay Low Test Transducer Voltage Ref US IMP/Metric Values At Last Fault: Vaporizer Heater Vaporizer Heater Vaporizer Heater Mode Vaporizer Heater Test Vaporizer Temp Vaporizer Temp Vaporizer Temp VFD Checksum Error VFD Cold Plate Temp VFD Cold Plate Temp (At Last Fault) VFD Comm Fault VFD CONFIG DATA Password VFD Coolant Flow VFD Coolant Flow VFD Coolant Solenoid Test VFD Delta VFD Delta (Capacity Control) VFD Enclosure Temp VFD Enclosure Temp (At Last Fault) VFD Fault VFD Fault Code VFD Fault Code (At Last Fault) VFD FAULT HISTORY VFD Gain VFD Gain (VFD Control) VFD Gateway Version # VFD Inverter Version # VFD Maximum Speed (VFD Control) VFD Minimum Speed (VFD Control) VFD Power On Reset VFD Rectifier Version # VFD Speed Control VFD Speed Output VFD Speed Output VFD Speed Output VFD Start VFD Start Inhibit WSM Active? MENU SOFTKEY SETPOINT STATUS SERVICE STATUS SERVICE SERVICE SERVICE SERVICE STATUS STATUS SERVICE SERVICE STATUS STATUS STATUS STATUS STATUS SERVICE STATUS SERVICE STATUS STATUS SERVICE STATUS SERVICE STATUS SERVICE STATUS STATUS SERVICE SERVICE SERVICE SERVICE STATUS STATUS SERVICE SERVICE STATUS STATUS SERVICE SERVICE STATUS STATUS STATUS STATUS SERVICE TABLE CONTROL TEST CONTROL TEST CONTROL TEST CONTROL ALGORITHM STATUS EQUIPMENT SERVICE CONTROL TEST CONTROL ALGORITHM STATUS CONTROL TEST CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT SERVICE EQUIPMENT SERVICE CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS 126 SCREEN NAME SETPOINT STARTUP DISCRETE OUTPUTS STARTUP DISCRETE OUTPUTS PRESSURE TRANSDUCERS ICVC CONFIGURATION VFD_HIST COMPRESS COMPRESS SETUP2 DISCRETE OUTPUTS STARTUP COMPRESS HEAT_EX VFD_STAT POWER VFD_HIST VFD_STAT VFD CONFIG DATA HEAT_EX POWER DISCRETE OUTPUTS COMPRESS CAPACITY POWER VFD_HIST VFD_STAT VFD_STAT VFD_HIST VFD_HIST CAPACITY SETUP2 VFD_STAT VFD_STAT SETUP2 SETUP2 VFD_STAT VFD_STAT SETUP2 CAPACITY COMPRESS STARTUP STARTUP VFD_STAT WSMCHLRE CONFIGURABLE X X X X X X X X X X X X X INDEX Abbreviations and explanations 4 After limited shutdown 67 Attach to network device control 44 Automatic soft stop amps threshold 47 Auto. restart after power failure 40 Before initial start-up 48-64 Carrier Comfort Network® Interface 58 Capacity control 12 Capacity override 36 Chilled liquid recycle mode 47 Chiller control module (CCM) 98 Chiller dehydration 55 Chiller familiarization 4-8 Chiller identification nameplate 4 Chiller start-up (prepare for) 66 Chillers with storage tanks 70 Chiller tightness (check) 49 Cold weather operation 67 Compressor bearing maintenance 77 Compressor minimum speed override 36 Compressor rotor check 77 Condenser 8 Condenser freeze prevention 39 Condenser pump control 39 Control algorithms checkout procedure 80 Control center 8 Control center (inspect) 73, 77 Control modules 98 Controls 12-46 Controls (definitions) 12 Control test 61, 81 Cooler 8 ICVC operation and menus 15 ICVC parameter index 118-126 Default screen freeze 36 Defective processor modules (replacing) 101 Demand limit control option 40 Design set points (input) 59 Display messages (checking) 79 Equipment required 48 Extended shutdown (preparation for) 66 Extended shutdown (after) 67 Gateway status LEDs 102 General controls overview 12 General maintenance 72, 73 Ground fault troubleshooting 58 Head pressure output reference 41 Heat exchanger tubes (inspect) 77 High altitude locations 62 Hot gas bypass (optional) algorithm 40 Identify the VFD 55 Initial start-up 64, 65 Initial start-up (preparation) 64 Initial start-up checklist for 23XRV hermetic screw liquid chiller CL-1 to CL-12 Input power wiring 57 Inspect liquid piping 55 Inspect wiring 57 Instruct the customer operator 65 Introduction 4 Job data required 48 Lead/lag control 42 Leak test chiller 49 Liquid/brine temperature reset 40 Local occupied schedule (input) 59 Local start-up 46 Lubrication cycle 10-12 Lubrication cycle (details) 10 Lubrication cycle (summary) 10 Lubrication system (check) 73 Module operation (notes) 98 Motor-compressor 8 Motor cooling cycle 10 Motor insulation 77 Muffler 8 Oil and oil filter changes 73 Oil charge 48 Oil circuit valves (open) 48 Oil heater 74 Oil pressure and compressor stop (check) 65 Oil reclaim system 12 Oil specification 74 Oil strainers 74 Oil sump temperature control 36, 38 Operating instructions 66-68 Operating the optional pumpout unit 69 Operator duties 66 Optional pumpout compressor Liquid piping (check) 55 Optional storage tank and pumpout system (using) 48 Optional pumpout system controls and compressor (check) 62 Optional pumpout system maintenance 78 Ordering replacement chiller parts 78 Overview (troubleshooting guide) 78 Physical data 103 PIC III system components 12 PIC III system functions 34 Preparation (pumpout and refrigerant transfer procedures) 69 Pressure transducers 61, 79 Prevent accidental start-up 65 Pumpout and refrigerant transfer procedures 69-72 Ramp loading 36 Refrigerant (adding) 72 Refrigerant (adjusting the charge) 72 Refrigerant charge (trim) 73 Refrigerant filter/drier 74 Refrigerant float system (inspect) 75 Refrigerant into chiller (charge) 63 Refrigerant leak rate 72 Refrigerant leak testing 72 Refrigerant leak detector 39 Refrigerant properties 72 Refrigerant (removing) 72 Refrigerant tracer 49 Refrigeration cycle 8-10 Refrigeration log 67 Relief valves (check) 55 Relief valves and piping (inspect) 77 Remote start/stop contacts 38 Remote reset of alarms 39 Repair the leak retest and apply standing vacuum test 73 Running system (check) 66 Safety and operating controls (check monthly) 73 Safety considerations 1 Safety controls 35 Safety shutdown 48 Scheduled maintenance 73-78 Service configurations (input) 59 Service ontime 73 Service operation 45 Shipping packaging (remove) 48 Shunt trip 36 Shutdown sequence 47 Software configuration 59 Spare alarm contacts 39 Spare safety inputs 38 Start the chiller 66 Starter (check) 57 Start-up/shutdown/recycle sequence 46-48 Stop the chiller 66 Storage vessel (optional) 8 System components 4 Temperature sensors (checking) 79 Test after service repair or major leak 72 Tighten all gasketed joints 48 Tower fan relay low and high 39 Troubleshooting guide 78-117 Vaporizer temperature control 36 127 VFD refrigerant strainers 74 Water/brine leaks 77 Water/brine treatment 77 Weekly maintenance 73 Copyright 2006 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 532-310 Printed in U.S.A. Form 23XRV-1SS Pg 128 9-06 Replaces: New Book 2 Tab 5e INITIAL START-UP CHECKLIST FOR 23XRV HERMETIC SCREW LIQUID CHILLER (Remove and use for job file.) MACHINE INFORMATION: NAME ADDRESS CITY JOB NO. MODEL ZIP STATE S/N DESIGN CONDITIONS TONS (kW) BRINE FLOW RATE TEMPERATURE IN TEMPERATURE PRESSURE OUT DROP PASS SUCTION TEMPERATURE COOLER CONDENSER ****** From Chiller Nameplate: Line Voltage Rated Line Amps From VFD Nameplate: I.D. No.: Input Rating VFD Serial Number ___________________________________________ Mfd in _____________________________________ on _____________ REFRIGERANT: CONDENSER TEMPERATURE ****** Type: CARRIER OBLIGATIONS: Overload Trip Amps Charge Assemble. . . . . . . . . . . . . . . . . . . Leak Test . . . . . . . . . . . . . . . . . . . Dehydrate . . . . . . . . . . . . . . . . . . Charging . . . . . . . . . . . . . . . . . . . Operating Instructions Yes Yes Yes Yes No No No No Hrs. START-UP TO BE PERFORMED IN ACCORDANCE WITH APPROPRIATE MACHINE START-UP INSTRUCTIONS JOB DATA REQUIRED: 1. Machine Installation Instructions . . . . . . . . . . . . . . . . . . Yes No 2. Machine Assembly, Wiring and Piping Diagrams . . . . . . Yes No 3. Starting Equipment Details and Wiring Diagrams. . . . . . Yes No 4. Applicable Design Data (see above) . . . . . . . . . . . . . . . . Yes No 5. Diagrams and Instructions for Special Controls . . . . . . . Yes No INITIAL MACHINE PRESSURE: YES NO Was Machine Tight? If Not, Were Leaks Corrected? Was Machine Dehydrated After Repairs? CHECK OIL LEVEL AND RECORD: 3/4 1/2 Oil sump sight glass 1/4 ADD OIL: Amount: Yes No 3/4 1/2 Strainer housing sight glass 1/4 RECORD PRESSURE DROPS: CHARGE REFRIGERANT: Cooler Initial Charge Condenser Final Charge After Trim Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 2 Catalog No. 532-310 Printed in U.S.A. Form 23XRV-1SS Pg CL-1 9-06 Replaces: New Tab 5e Yes Yes No No Line Voltage: FIELD-DISASSEMBLED CHILLERS ONLY: Megger Test Motor if the VFD is removed from the chiller. Check continuity T1 to T1, etc. (Motor to starter, disconnect motor leads T1, T2, T3.) Do not megger VFD; disconnect leads to motor and megger the leads. MEGGER MOTOR “PHASE TO PHASE” T1-T2 T1-T3 T2-T3 “PHASE TO GROUND” T1-G T2-G T3-G 10-Second Readings: 60-Second Readings: Polarization Ratio: CONTROLS: SAFETY, OPERATING, ETC. Verify parameters in VFD_conf screen. Yes No Perform Controls Test Yes No PIC III CAUTION COMPRESSOR MOTOR AND CONTROL CENTER MUST BE PROPERLY AND INDIVIDUALLY CONNECTED BACK TO THE EARTH GROUND IN THE STARTER (IN ACCORDANCE WITH CERTIFIED DRAWINGS). Water/Brine Pump Control Can the Carrier controls independently start the pumps? Condenser Liquid Pump Chilled Liquid Pump Yes Yes No No INITIAL START: Check Position of all Valves: Isolation Valves (See Fig. 2, 43-45) VALVE Discharge Cooler Inlet Hot Gas Bypass Vaporizer Condenser Gas Oil Pump Oil Filter Oil Pressure Regulator Filter/Drier Filter/Drier VFD Refrigerant Cooling Inlet VFD Refrigerant Cooling Drain LOCATION Under Muffler Next to economizer or under cooler Between cooler and condenser Between cooler and condenser Next to oil pump inlet Downstream of oil filter Under oil sump next to oil pressure regulator Next to condenser float chamber Under condenser near filter/drier Under compressor discharge Between cooler and condenser OPEN ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ Fully Front Seated or Fully Back Seated Fully Front Seated or Fully Back Seated ________ ________ CLOSED On cooler relief valve tree Under cooler On condenser relief valve tree On condenser float valve chamber Under oil sump ________ ________ ________ ________ ________ Relief Valve Three-Way Valves Cooler (if installed) Condenser Service Valves Cooler Refrigerant Charging Valve Cooler Refrigerant Pumpout Valve Condenser Refrigerant Charging Valve Condenser Refrigerant Pumpout Valve Oil Sump Charging/Drain Valve CL-2 Yes - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE INSPECT WIRING AND RECORD ELECTRICAL DATA: Verify 6″ clearance surrounding all Control Center louvers Visually inspect down through top of power module for debris Start Liquid Pumps and Establish Liquid Flow Oil Level OK and Oil Temperature OK Oil Pressure Restart Compressor, Bring Up To Speed. Shut Down. Any Abnormal Coastdown Noise? Yes* *If yes, determine cause. START MACHINE AND OPERATE. COMPLETE THE FOLLOWING: A: Trim charge and record under Charge Refrigerant Into Chiller section on page 63. B: Complete any remaining control calibration and record under Controls section (pages 12-46). C: Take at least two sets of operational log readings and record. D: After machine has been successfully run and set up, shut down and mark shutdown oil levels. E: Give operating instructions to owner’s operating personnel. Hours Given: Hours F: Call your Carrier factory representative to report chiller start-up. G: Register LiquiFlo2 VFD start up on www.automation.rockwell.com/complete1/warp. H: Return a copy of this completed checklist to the local Carrier Service office. SIGNATURES: CARRIER TECHNICIAN CUSTOMER REPRESENTATIVE DATE DATE CL-3 No DESCRIPTION Base Demand Limit LCL Setpoint ECL Setpoint Ice Build Setpoint Tower Fan High Setpoint RANGE 40 to 100 10 to 60 (-12.2-15.6) 15 to 65 (-9.4-18.3) 15-60 (-9.4-15.6) 55 to 105 (-13-41) Upload all Control Configuration tables via Service Tool Yes UNITS % ° F (° C) ° F (° C) ° F (° C) ° F (° C) DEFAULT 100 50.0 (10.0) 60.0 (15.6) 40 (4.4) 75 (23.9) No ICVC Software Part # (See ICVC CONFIGURATION Screen): ICVC Controller Identification (See ICVC CONFIGURATION Screen): BUS: VFD Gateway Version # (See VFD_STAT Screen): VFD Inverter Version # (See VFD_STAT Screen): VFD Rectifier Version # (See VFD_STAT Screen): CL-4 ADDRESS: VALUE - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE 23XRV PIC III SETPOINT TABLE CONFIGURATION SHEET 23XRV PIC III LOCAL TIME SCHEDULE CONFIGURATION SHEET OCCPC01S Day Flag M T W T F S S H Occupied Time Unoccupied Time Period 1: Period 2: Period 3: Period 4: Period 5: Period 6: Period 7: Period 8: NOTE: Default setting is OCCUPIED 24 hours/day. ICE BUILD 23XRV PIC III TIME SCHEDULE CONFIGURATION SHEET OCCPC02S Day Flag M T W T F S S H Occupied Time Unoccupied Time Period 1: Period 2: Period 3: Period 4: Period 5: Period 6: Period 7: Period 8: NOTE: Default setting is UNOCCUPIED 24 hours/day. 23XRV PIC III CCN TIME SCHEDULE CONFIGURATION SHEET OCCPC03S Day Flag M T W T F S Period 1: Period 2: Period 3: Period 4: Period 5: Period 6: Period 7: Period 8: NOTE: Default setting is OCCUPIED 24 hours/day. CL-5 S H Occupied Time Unoccupied Time DESCRIPTION Motor Nameplate Voltage RANGE 480-480 UNITS VOLTS DEFAULT 480 Compressor 100% Speed 60.0-101 Hz 70 Rated Line Voltage 346-480 VOLTS 460 Rated Line Amps 10-5000 AMPS 200 Rated Line Kilowatts 0-999999 KW 100 Motor Rated Load KW 0-999999 KW 100 Motor Rated Load Amps 10-5000 AMPS 200 Motor Nameplate Amps 10-5000 AMPS 100 Motor Nameplate RPM 1500-3030 Motor Nameplate KW Inverter PWM Frequency (0=4 k Hz, 1=2 k Hz) Skip Frequency 1 0-999999 0.0-102 Hz 102 Skip Frequency 2 0.0-102 Hz 102 Skip Frequency 3 0.0-102 Hz 102 Skip Frequency Band 0.0-102 Hz 0 Line Voltage % Imbalance 1-10 % 10 Line Volt Imbalance Time 1-10 SEC 10 Line Current % Imbalance 5-40 % 40 Line Current Imbal Time 1-10 SEC 10 Motor Current % Imbalance 5-40 % 40 Motor Current Imbal Time 1-10 SEC 10 Increase Ramp Time 5-60 SEC 30 Decrease Ramp Time 5-60 SEC 30 Single Cycle Dropout 0/1 DSABLE/ENABLE DSABLE 2672 KW 0/1 100 0 CL-6 VALUE - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE 23XRV PIC III VFD_CONF TABLE CONFIGURATION SHEET 23XRV PIC III OPTIONS TABLE CONFIGURATION SHEET DESCRIPTION Auto Restart Option Remote Contacts Option Soft Stop Amps Threshold RANGE 0/1 0/1 40 to 100 UNITS DSABLE/ENABLE DSABLE/ENABLE % DEFAULT DSABLE DSABLE 100 Hot Gas Bypass HGBP Option 0,1,2 0=DSABLE 1=HGBP 2=LOW LOAD HGBP 0=DSABLE 0.5 to 20 (.3 to 11.1) 30 to 170 (206.9 to 1172.2) ˆF (ˆC) PSI (kPa) 1.5 (.8) 150 (1034.2) 0.5 to 20 (.3 to 11.1) 30 to 250 (206.9 to 1724) 0.5 to 3 (.3 to 1.7) 0.5-10 (0.3-5.6) 1.0-10 (0.6-5.6) ˆF (ˆC) PSI (kPa) ˆF (ˆC) ^F (^C) ^F (^C) 4 (2.2) 200 (1379) 1 (.6) 2.0 (1.1) 4.0 (2.2) 5 to 20 7 to 10 % MIN 10 8 0/1 0-2 DSABLE/ENABLE DSABLE 0 0/1 0/1 0-99999 0-99999 DSABLE/ENABLE DSABLE/ENABLE DSABLE DSABLE 1000 20 20-85 (138-586) 20-85 (138-586) 0 to 100 PSI (kPa) PSI (kPa) % 25 (172) 35 (241) 0 Min. Load Point (T1, P1) HGBP Delta T1 HGBP Delta P1 Full Load Point (T2, P2) HGBP Delta T2 HGBP Delta P2 HGBP Deadband HGBP On Delta T HGBP Off Delta T Stall Protection Stall Delta % Amps Stall Time Period Ice Build Control Ice Build Option Ice Build Termination (0=TEMP, 1=Contact, 2=Both) Ice Build Recycle Refrigerant Leak Option PPM at 20 mA Refrigerant Leak Alarm PPM Head Pressure Reference Delta P at 0% (4 mA) Delta P at 100% (20 mA) Minimum Output CL-7 VALUE DESCRIPTION Comp Motor Temp Override Cond Press Override Comp Discharge Alert Rectifier Temp Override Inverter Temp Override Chilled Medium Chilled Liquid Deadband. Evap Refrig Trippoint Refrig Override Delta T Evap Approach Alert Cond Approach Alert Condenser Freeze Point Flow Delta P Display Evap Flow Delta P Cutout Cond Flow Delta P Cutout Oil Press Verify Time Liquid Flow Verify Time RANGE 150 - 200 (66 - 93) 145 - 166 (1000 - 1145) 125 to 160 (52 to 71) 155 to 170 (68 to 77) 155 to 170 (68 to 77) UNITS °F (° C) PSI (kPa) °F (° C) °F (° C) °F (° C) DEFAULT 200 (93) 145 (1000) 140 (60) 160 (71) 160 (71) 0/1 0.5 to 2.0 (0.3 to 1.1) 10 to 40.0 (–12.2 to 4.4) 2.0 to 5.0 (1.1 to 2.8) 0.5 to 15 (0.3 to 8.3) 0.5 to 15 (0.3 to 8.3) –20 to 35 (–28.9 to 1.7) WATER/BRINE ˆF (ˆC) °F (° C) ˆF (ˆ C) ˆF (ˆC) ˆF (ˆC) °F (° C) WATER 1.0 (0.6) 33 (0.6) 3 (1.7) 5 (2.8) 6 (3.3) 34 (1.1) 0/1 0.5 to 50.0 (3.4 to 344.8) 0.5 to 50.0 (3.4 to 344.8) 15 to 300 0.5 to 5 DS/ENABLE PSI (kPa) PSI (kPa) SEC MIN DSABLE 5.0 (34.5) 5.0 (34.5) 45 5 2.0 to 10.0 (1.1 to 5.6) 0.5 to 4.0 (0.3 to 2.2) ˆF (ˆ C) ˆF (ˆ C) 5 (2.8) 1 (0.6) Recycle Control Restart Delta T Shutdown Delta T SPARE ALERT/ALARM ENABLE Disable=0, Lo=1/3, Hi=2/4 Spare Temp #1 Enable Spare Temp #1 Limit Spare Temp #2 Enable Spare Temp #2 Limit 0 to 4 –40 to 245 (–40 to 118) 0 to 4 –40 to 245 (–40 to 118) °F (° C) °F (° C) CL-8 0 245 (118) 0 245 (118) VALUE - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE 23XRV PIC III SETUP1 TABLE CONFIGURATION SHEET 23XRV PIC III SETUP2 TABLE CONFIGURATION SHEET DESCRIPTION Capacity Control Proportional Inc Band Proportional Dec Band Proportional ECL Gain VFD Control VFD Gain VFD Minimum Speed VFD Maximum Speed Vaporizer Heater Mode 0 = Normal, 1 = Service STATUS UNITS 2 to 10 2 to 10 1 to 3 0.1 to 1.5 15 to 50 15 to 100 0 to 1 DEFAULT 6.5 6.0 2.0 % % CL-9 0.75 20 100 0 VALUE DESDRIPTION Lead Lag Control LEAD/LAG Configuration DSABLE=0, LEAD=1, LAG=2, STANDBY=3 Load Balance Option Common Sensor Option LAG % Capacity LAG Address LAG START Timer LAG STOP Timer PRESTART FAULT Timer PULLDOWN Timer STANDBY Chiller Option STANDBY % Capacity STANDBY Address RANGE UNITS 0 to 3 0/1 0/1 25 to 75 1 to 236 2 to 60 2 to 60 2 to 30 1 to 30 0/1 25 to 75 1 to 236 DEFAULT 0 DSABLE/ENABLE DSABLE/ENABLE % MIN MIN MIN MIN DSABLE/ENABLE % CL-10 DSABLE DSABLE 50 92 10 10 5 2 DSABLE 50 93 VALUE - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE 23XRV PIC III LEADLAG TABLE CONFIGURATION SHEET 23XRV PIC III RAMP_DEM TABLE CONFIGURATION SHEET DESCRIPTION Pulldown Ramp Type: Select: Temp=0, kW=1 Demand Limit and kW Ramp Demand Limit Source Select: Amps=0, kW=1 Amps or kW Ramp % Min Demand Limit Prop Band Demand Limit At 20 mA 20 mA Demand Limit Opt Demand Watts Interval RANGE UNITS DEFAULT 0/1 1 0/1 0 5 to 20 3 to 15 40 to 100 0/1 5 to 60 % % DSABLE/ENABLE MIN VALUE 10 10 40 DSABLE 15 23XRV PIC III TEMP_CTL TABLE CONFIGURATION SHEET DESCRIPTION Control Point Source ECL Control Option Temp Pulldown Ramp/Min RANGE UNITS DEFAULT 0/1 2 to 10 (1.1 to 5.6) DSABLE/ENABLE ˆF (ˆC) DSABLE 3 (1.7) –30 to 30 (–17 to 17) ˆF (ˆC) 10 (6) –40 to 245 (–40 to 118) –40 to 245 (–40 to 118) –30 to 30 (–17 to 17) °F (° C) °F (° C) ˆF (ˆC) 85 (29) 65 (18) 10 (6) 0 to 15 (0 to 8) 0 to 15 (0 to 8) –30 to 30 (–17 to 17) ˆF (ˆC) ˆF (ˆC) ˆF (ˆC) 10 (6) 0 (0) 5 (3) Temperature Reset RESET TYPE 1 Degrees Reset At 20 mA RESET TYPE 2 Remote Temp (– > No Reset) Remote Temp (– > Full Reset) Degrees Reset RESET TYPE 3 CHL Delta T (– > No Reset) CHL Delta T (– > Full Reset) Degrees Reset Enable Reset Type 0 to 3 0 CL-11 VALUE DESCRIPTION Time Broadcast Enable Daylight Savings Start Month Start Day of Week Start Week Start Time Start Advance Stop Month Stop Day of Week Stop Week Stop Time Stop Back RANGE 0/1 1 to 12 1 to 7 1 to 5 00:00 to 24:00 0 to 360 1 to 12 1 to 7 1 to 5 00:00 to 24:00 0 to 360 UNITS DSABLE/ENABLE HH:MM MIN MIN DEFAULT DSABLE VALUE 4 7 1 02:00 0 10 7 5 02:00 0 Copyright 2006 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 532-310 Printed in U.S.A. Form 23XRV-1SS Pg CL-12 10-06A 9-06 Replaces: New Book 2 Tab 5e - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE 23XRV BROADCAST (BRODEF) CONFIGURATION SHEET