Constant Speed Gator
Transcription
Constant Speed Gator
Bulletin: Effective: Supersedes: 29-510 3-12-03 6-7-98 SYNCROFLO GATOR IRRIGATION PUMPING STATION OPERATOR’S GUIDE Table of Contents INTRODUCTION .......................................................................................................................................................1 STATION OPERATION ............................................................................................................................................1 Pressure/flow sequencing .......................................................................................................................................1 Time clock start sequencing ...................................................................................................................................2 Remote start sequencing.........................................................................................................................................2 DOOR MOUNTED CONTROLS AND INDICATORS..........................................................................................2 Pump Selector Switch ............................................................................................................................................2 Low system pressure alarm light ............................................................................................................................3 High system pressure alarm light (optional)...........................................................................................................3 Irregular power alarm light (optional)....................................................................................................................4 High temperature alarm light..................................................................................................................................4 Reset Button ...........................................................................................................................................................5 THE PLC (PROGRAMMABLE LOGIC CONTROLLER)...................................................................................5 Maintenance ...........................................................................................................................................................5 PLC Failure ............................................................................................................................................................5 Status Indicators .....................................................................................................................................................5 PLC Switch Settings...............................................................................................................................................6 EXTERNAL STATION FEATURES........................................................................................................................6 Main Disconnect Switch ........................................................................................................................................6 Ventilation Fan .......................................................................................................................................................6 INTRODUCTION This document explains how your station works. Station operation, alarms, basic troubleshooting, settings, and components are all explained in detail. It is the most important part of your owners manual because it is the key to understanding what your station can do and how to operate it properly. In addition, the answers to the most commonly asked questions about the Gator can usually be found right here. Use the table of contents as a guide to finding what you are interested in. Please read on! It will be worth the time you spend. STATION OPERATION Pressure/flow sequencing This mode of operation for the station allows the pump to start on pressure and stop on a “no flow” condition. The pressure sequencing setpoint is controlled by the low system pressure switch located adjacent to the motor control panel. The low system pressure switch should be set 10 to 15 psi below system pressure. The flow sequencing setpoint is controlled by the flow switch located in the discharge manifold of the station. It should be adjusted to detect flow at 5 to 10 gpm. Pressure sequencing should immediately start a pump if the system pressure drops enough to trip the pressure switch. Once the pump has started, it is latched on until the system pressure is satisfied, the flow switch detects a “no flow” condition and the minimum run timer for the pump has expired. When the off conditions are met, the pump can then shut down following the expiration of its stop delay. Flow sequencing (flow anticipation) will also start the pump. This occurs if there is enough flow through the discharge manifold to cause the flow switch to open, bringing the system out of a “no flow” condition. Again, once the pump has started, it is latched on until the system pressure is satisfied, the flow switch detects a “no flow” condition and the minimum run timer for the pump has expired. Time clock start sequencing This mode of operation is controlled by a time clock located on the face of the motor control panel. It can be set to bring the pump on and turn it back off at the desired times. The time clock is a 24 hour, 7 day clock and can be programmed to operate in a number of different time cycles. See the time clock operators guide for further instructions on operating and programming the time cycles. Remote start sequencing This mode of operation is controlled by a remote signal provided by a remote timer or an irrigation controller. This mode can be used to bring the pump on and turn it back off at the desired times, as with the time clock sequencing described in the section above. NOTE: Please see the station data sheet for further clarification on the type of pump sequencing and options provided with your station. DOOR MOUNTED CONTROLS AND INDICATORS Pump Selector Switch This switch has a green lens, and is labeled “NO.1 PUMP”. This switch is also referred to as “H-O-A” switches. HAND: Use this position for temporary manual operation, or to test a pump. The station should be supervised when pump is running “in hand", since all pump sequencing functions are bypassed. The pump and the irrigation system is still protected by all alarms when the pump is run “in hand". If the PLC fails, the pumps can still be run “in hand", but all pump sequencing controls, and the alarms will not function. OFF: Use this position when restarting the station, or when a pump is down for service AUTO: Use this position for normal automatic operation of each pump and the station as a whole. The PLC has full control over all pump operations in this position including: all pump sequencing functions, and all alarms. Run Light: The pump is indicated as running by a light which is inside its selector switch handle. Bulletin 29-510 Page: 2 SyncroFlo Gator Low system pressure alarm light This light is red, and is labeled “LOW SYSTEM PRESSURE. This alarm detects low system pressure in the discharge header with the low system pressure switch located adjacent to the control panel. This alarm could be caused by any of the following: 1. Low system pressure switch setting too high. 2. Misadjusted main and/or bypass control valve settings. 3. Flow rate greater than station capacity (too many sprinklers on). 4. Low system pressure switch sensing line valved off or clogged. 5. Low system pressure switch failure. 6. Pump selector switch turned off. 7. Motor overload trip. 8. Motor starter coil or contact failure. 9. Main and/or bypass control valve failure. 10. Motor failure or reverse rotation. 11. Pump failure or loss of prime. 12. Pump check valve stuck closed or installed backwards. 13. A large break in the irrigation piping. 14. Low suction pressure, loss of prime, or supply water restriction. The low system pressure alarm can only activate when the system pressure is low, the PLC has already started or tried to start the pump, and no other alarms are activated. As soon as the low system pressure switch senses low pressure at the station discharge, the “low system pressure” alarm light will turn on. If the system pressure increases any time before the 5 minute delay expires, the alarm light will turn off and the pump will continue to operate normally. If the system pressure remains low for 5 minutes continuously, the pump will be stopped and the alarm light will latch on. To reset the alarm, push the station “reset” button. This alarm will always reset even if the system pressure is still low. NOTE: The low system pressure switch is also used to start the pump on stations with pressure/flow sequencing. (See STATION OPERATION section for details on pump starting) High system pressure alarm light (optional) This light is red, and is labeled “HIGH SYSTEM PRESSURE. This alarm detects high system pressure in the discharge header with the high system pressure switch located adjacent to the control panel. This alarm could be caused by any of the following: 1. High system pressure switch setting too low. 2. Misadjusted main and/or bypass control valve settings. 3. Sudden decrease in flow rate to no flow. 4. Pressure control valve hung open temporarily due to falling suction pressure or demand beyond available capacity. 5. Control valve failure. Bulletin 29-510 Page: 3 SyncroFlo Gator The high system pressure alarm will activate at any time when system pressure is high. As soon as the high system pressure switch senses high pressure at the station discharge, the “high system pressure” alarm light will turn on. If the system pressure decreases any time before the 10 second delay expires, the alarm light will turn off and the pump will continue to operate normally. If the system pressure remains high for 10 seconds continuously, the pump will be stopped and the alarm light will latch on. To reset the alarm, push the station “reset” button. Irregular power alarm light (optional) This light is amber, and is labeled “IRREGULAR POWER”. This alarm detects abnormal electric power conditions with a power monitor that is located inside the panel. Immediately after the power monitor senses something wrong on the power lines, the alarm latches on and the station is shutdown. If power conditions return to normal for 30 seconds, the alarm resets automatically and the station is allowed to run. Note: This alarm can be manually reset. You do not have to wait for an automatic reset. This alarm could be cause3d by any of the following: 1. 2. 3. 4. 5. 6. Incoming line voltage less than 90 percent of normal Power monitor voltage adjustment too high A reversal, shift, imbalance, or loss of line phase(s) Power lines not connected in phase with pump station Blown power monitor fuses Power monitor failure High temperature alarm light This light is red, and is labeled “HIGH TEMPERATURE”. This alarm detects high water temperature at the pump suction. This is a possible indication of a loss of water to the pump. The temperature switch is located at the pump suction. This alarm could be caused by any of the following: 7. Loss of suction prime or supply water restriction. 8. Temperature switch failure. 9. Pump failure. 10. Pump discharge isolation valve closed. 11. Pump check valve stuck closed or installed backwards. The high temperature alarm can activate when high temperature at the pump is indicated. As soon as the high temperature switch senses high temperature at the pump, the “high temperature” alarm light will turn on. If the the temperature drops below the switch trip point Bulletin 29-510 Page: 4 SyncroFlo Gator any time before the 30 second delay expires, the alarm light will turn off and the pump will continue to operate normally. If the temperature remains high for 30 seconds continuously, the pump will be stopped and the alarm light will latch on. To reset the alarm, push the station “reset” button. This alarm will only reset if the temperature has dropped below the switch trip point. Reset Button This button is red, and is labeled “RESET”. This button is used to perform several functions: see the following paragraphs. Push this button to reset an alarm and return to normal automatic operation. If the particular alarm indicating light does not turn off, the fault condition still exists. Check the alarm and try to correct the fault to be able to return the station to normal automatic operation. Pressing this button times out the minimum run timer and allows the pump to stop if it is no longer required to be running. The pump does not stop immediately since it has a stop delay that must expire first. The RESET button only releases the pump from its minimum run timer while it is running. This is a useful feature for testing or monitoring station operation. Hold this button in for 1 minute to test the PLC input failure alarm. The station will shutdown, but it will resume normal operation again once the button is released. The only time you need to hold the RESET button in that long, is when you want to test this feature. THE PLC (PROGRAMMABLE LOGIC CONTROLLER) Maintenance The PLC requires no routine maintenance. The PLC program cannot be lost due to a power failure, no matter how long power is off. An occasional check of the PLC's status indicators is sufficient to check for correct operation. PLC Failure It is unlikely that a problem will develop with the PLC. If there seems to be a problem, call the factory for assistance. If a problem does exist, a replacement PLC or program can be shipped to you. If the PLC does fail, the pumps can be run “in hand” until it is replaced. Status Indicators The operating status of the PLC can be determined by observing the red lights on the front of the PLC. To do this, the control panel must be open while the power is on. The function of each light is described below. The electrical schematic shows the physical layout of the PLC. POWER: Green power lights should be on unless control power is off or the PLC's internal power supply fuse has blown. RUN: This light is on if the PLC is operating normally. Bulletin 29-510 Page: 5 SyncroFlo Gator PROG-E / CPU-E: If this light is on continuously or flashing on the CPU, an error has been detected. If the error does not clear by turning power off and back on, call the factory for assistance. INPUT & OUTPUT: These numbered lights indicate which signals are coming into the PLC's inputs (X terminals) and which devices the PLC has turned on with its outputs (Y terminals), respectively. The electrical schematic shows which device is connected to each I/O point. PLC Switch Settings These switches are preset at the factory, so they should not need to be changed. If you want to check them, turn the power off first. CPU: The switch on the front right side of the PLC, under the communications door, should be set to the RUN position. This will allow the PLC to operate normal. PLC Time Settings (kept permanently inside the PC) Pump stop delay ................................................................................................... 30 seconds Pressure start delay .............................................................................................. 2 seconds Flow start delay .................................................................................................... 0 seconds Low system pressure alarm delay ........................................................................ 5 minutes High system pressure alarm delay ....................................................................... 10 seconds High temperature alarm delay .............................................................................. 30 seconds Input failure (PLC) alarm delay ........................................................................... 1 minute Irregular power alarm delay ................................................................................. 2 seconds Irregular power alarm reset delay ........................................................................ 30 seconds EXTERNAL STATION FEATURES Main Disconnect Switch A main disconnect switch is provided with each station. The switch is located outside the pump house and should be used to turn off all power to the pump station and isolate any main fuses from incoming power for servicing purposes. Ventilation Fan A pump house ventilation fan is provided with each Gator Station. It is used to cool the motor and control panel from the heat generated by the motor and the environment. It will run anytime the pump runs, venting the motor heat to the outside of the pump house. Bulletin 29-510 Page: 6 SyncroFlo Gator WARRANTY The components of each SyncroFlo water pressure booster system, when purchased as regular factory selections, are warranted against failure due to defects in design, material, or construction, from date of factory shipment within the periods and under the conditions noted below: PUMPS All SyncroFlo pumping assemblies are warranted against mechanical failure for a period of one (1) year. If any component of the pumping assembly fails within this period, SyncroFlo, Inc., will, at its option, repair or replace the pumps assembly on a no charge exchange basis FOB factory, Atlanta, Georgia. MOTORS Motors, when equipped with standard SyncroFlo over-temperature protection systems and maintained according to factory instructions, are warranted for one (1) year. SyncroFlo, Inc., will make, at its option, a no charge repair or replacement at the factory or at an authorized motor service station. PRESSURE REGULATING VALVES Pressure regulating valves are warranted for one (1) year. If any mechanical component of the regulating valve fails within this period, SyncroFlo, Inc., will, at its option, repair or replace regulating valve component parts on a no charge exchange basis FOB factory. COMPLETE SYSTEM The complete SyncroFlo system as a whole, including all accessories and components not mentioned above, is warranted functionally and mechanically for a period of one (1) year, when installed, operated, and maintained in accordance with the Company’s recommendations. SyncroFlo, Inc., is responsible only for repairing or replacing its products in accordance with the terms and conditions set forth above. There are no warranties, either expressed or implied, extending beyond those stated on the face hereof, and SyncroFlo, Inc., expressly disclaims all other warranties, including any implied warranties of mechanical ability or fitness for a particular purpose. SyncroFlo, Inc., also disclaims any liability whatsoever for incidental or consequential damages, including damages to property, damages for loss of use, loss of time, loss of profits, loss of income, or any other incidental or consequential damages. SyncroFlo, Inc., neither assumes nor authorizes any other person to furnish any warranties, or assume for it any liability in connection with the sale of its products. This warranty does not include mechanical seals, gauges, transportation, or labor costs for exchange or installation of repaired or replaced material. Final determination of warranty shall be made only by the factory upon return and inspection of returned material. No material is to be returned without a return material authority (RMA) tag which may be obtained by calling or writing the factory, advising what will be shipped and the reason for the return. 6700 Best Friend Road, Norcross, GA 30071 Phone: (770) 447-4443 Fax: (770) 447-0230 www.syncroflo.com BETTER CONTROL THROUGH SYSTEMS ENGINEERING 8 9 2 4 37" O.A.W. 6 3/8" 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 6 5 31" COMPONENTS 11" 5 7/8" 9 5/16" 48 7/8" CLOSE COUPLED END SUCTION PUMP DISCHARGE ISOLATION BALL VALVE 2" PRESSURE REGULATING VALVE 2" FLOW SWITCH SUCTION PRESSURE GAUGE SYSTEM PRESSURE GAUGE TEMPERATURE PROBE EXHAUST FAN DISCONNECT PANEL SYSTEM POWER AND CONTROL PANEL PUMP SUCTION CONNECTION 2" DISCHARGE CONNECTION 2" SYSTEM ENCLOSURE 51 3/8"O.A.L. PLAN VIEW 13 PROPRIETARY DRAWING THIS CONFIDENTIAL DOCUMENT IS THE PROPERTY OF 3 7 11 1 SYNCROFLO, INC. NORCROSS, GEORGIA NOT TO BE DUPLICATED WITHOUT WRITTEN PERMISSION OR USED IN ANY WAY DETRIMENTAL TO THE COMPANY. 10 12 NOTE: SEE DATA SHEET TO CONFIRM SYSTEM END CONNECTIONS. ALL DIMENSIONS +/- TOLERANCE OF 1/2" 31" LID CLOSED GATOR 2" x 2" 9 3/4"TYP. 9 1/2" DATE: 1998 DRAWN BY: PLH ENG. BY: JDB CHK. BY: SyncroFlo FRONT ELEVATION VIEW Pump i n g S y s t em S o l u t i o n s 6700 Best Friend Road - Norcross, GA 30071 - (770) 447-4443 - Fax (770) 447-0230 - WEB WWW.SYNCROFLO.COM 6" A970-2010-201A1 OWNERS MANUAL INSTALLATION AND OPERATING INSTRUCTIONS REPAIR PARTS LIST Close Coupled Motor Driven Centrifugal Pump 1134 0694 IMPORTANT For best possible performance and continuous, satisfactory operation, read these instructions before installing your new pump. Should service be required, this manual can be a valuable guide. It should be kept near the installation for ready reference. Record nameplate data from pump on blank nameplate inside this manual for future reference. Berkeley Pumps / 293 Wright Street / Delavan, WI 53115 F00634 (Rev. 7/21/09) Table of Contents Page • SAFETY .................................................................................................................................................................3 • INSTALLATION General Information ................................................................................................................................... 4, 5 Foundation ......................................................................................................................................................5 Suction Connection for Centrifugal Pump Installation..............................................................................4, 6-9 Suction Connection for Swimming Pool Installation.............................................................................4, 10-11 Discharge Connection..........................................................................................................................4, 12-13 Electrical Connection ................................................................................................................................4, 14 • START-UP General Information ......................................................................................................................................15 Check Pump Rotation .............................................................................................................................15, 16 Priming ....................................................................................................................................................15, 17 • MAINTENANCE General Information / Observational Maintenance / Pump Protection ..........................................................18 Packing ...................................................................................................................................................18, 19 Mechanical Shaft Seal .......................................................................................................................18, 20-21 • PUMP NOMENCLATURE General Information ......................................................................................................................................22 Parts Breakdown...........................................................................................................................................23 • TROUBLESHOOTING Chart .............................................................................................................................................................24 Page 2 F00634 Safety First READ AND FOLLOW SAFETY INSTRUCTIONS! This is the safety alert symbol. When you see this symbol on your pump or in this manual, look for one of the following signal words and be alert to the potential for personal injury: General Safety Do not allow pump, piping, or any other system component containing water to freeze. Freezing may damage system, leading to injury or flooding. Allowing pump or system components to freeze will void warranty. Pump approved liquids only with this pump. warns about hazards that will cause serious personal injury, death or major property damage if ignored. Periodically inspect pump and system components. warns about hazards that will or can cause serious personal injury, death or major property damage if ignored. Keep work area clean, uncluttered and properly lighted; store properly all unused tools and equipment. Wear safety glasses at all times when working on pumps. Keep visitors at a safe distance from the work areas. warns about hazards that will or can cause minor personal injury or property damage if ignored. The label NOTICE indicates special instructions which are important but not related to hazards. Carefully read and follow all safety instructions in this manual and on pump. Keep safety labels in good condition. Replace missing or damaged safety labels. Electrical Safety WARNING Wire motor for correct voltage. See “Electrical” section of this manual and motor nameplate. Ground motor before connecting to power supply. Hazardous voltage. Can shock, burn, or cause death. Ground pump before connecting to power supply. Meet National Electrical Code and local codes for all wiring. Follow wiring instructions in this manual when connecting motor to power lines. Make workshops childproof; use padlocks and master switches; remove starter keys. Swimming Pool and Spa Installation Safety Incorrectly installed or tested equipment may fail, causing severe injury or property damage. Read and follow instructions in owner's manual when installing and operating equipment. Have a trained pool professional perform all pressure tests. 1. Do not connect system to a high pressure or city water system. 2. Install pump with at least 2 hydraulically balanced main drains equipped with correctly installed, screw-fastened, anti-entrapment certified covers. See Page 11. 3. Trapped air in system can cause explosion. BE SURE all air is out of system before operating or testing equipment. Before pressure testing, make the following safety checks: • Check all clamps, bolts, lids, and system accessories before testing. • Release all air in system before testing. • Tighten Berkeley trap lids to 30 ft. lbs. (4.1 kg-cm) torque for testing. • Water pressure for test must be less than 25 PSI (172 kPa). • Water Temperature for test must be less than 100° F. (38° C). • Limit test to 24 hours. After test, visually check system to be sure it is ready for operation. Remove trap lid and retighten hand tight only. NOTICE: These parameters apply to Berkeley equipment only. For non-Berkeley equipment, consult manufacturer. F00634 Page 3 Installation General Information Proper Lifting Procedure Heavy weight crushing hazard. NEVER walk or reach under a suspended pump. DO NOT screw an eye bolt into the motor housing and attempt to lift assembly! The lifting point built into the motor case is not designed to support the combined weight of the motor and pump. The crane or hoist must have a capacity in excess of the combined weight of the motor and pump. Use a minimum of two chains or straps to lift motor/pump assembly. Each chain or strap must have a capacity in excess of the combined weight of the motor and pump. MOTOR / PUMP LIFTING PROCEDURE: Wrap the first chain or strap under the fan end of the motor up tight against the motor feet, and the second chain or strap under the pump bracket between the pump end and the motor. Raise motor/pump assembly slowly to ensure that the chains or straps will not slip when put under tension. Balance motor and pump with chains or straps to maintain proper weight distribution. If not balanced, release tension on the chains or straps and readjust. 2498 0497 Page 4 F00634 Installation General Information Pump Foundation LOCATION: Locate the pump as near the water source as practical. Make the pipe run as short and straight as possible, especially if a suction lift is required. Careful attention should be taken to assure that net positive suction head available (NPSHA) exceeds net positive suction head required (NPSHR) by the pump or reduced performance and severe pump damage may result. If in doubt, check with your nearest Berkeley professional dealer. Install pump in a clean, dry and drained location readily accessible for inspection and maintenance. Provide ample ventilation. 1/2" or thicker Sole Plate tapped for hold down bolts Pump or Motor Frame Anchor Bolts ge ina Dra Concrete Foundation FOUNDATION: Refer to illustrations at right. Heavy weights. Use care and proper equipment when handling pump for installation. Pump should be set on a concrete foundation which is sufficiently substantial to absorb vibration and which provides a permanent and rigid support. Pump or Motor Frame PIPING: System piping should be at least one commercial pipe size larger than pump connections and flow velocity should not exceed eight (8) feet per second. In pool installation, flow velocity should not exceed six (6) feet per second. NOTICE: Take care to align piping with pump case. Misalignment or excessive pipe strain can cause distortion of pump components resulting in rubbing, breakage and reduced pump life. Support pipe in such a way that no force is exerted on pump connections. Check alignment as follows: with the pump shut down and isolation valves closed, remove pipe flange bolts. If the mating flanges come apart or shift, misalignment is present and causing pressure on the connections. Adjust pipe supports until flanges mate without any force. This procedure can be done throughout piping system. Steel Channel Anchor Bolt Shims for alignment Wedges Various Heights Tack Weld Grout Grout Dam Dra Concrete Foundation inag e SUCTION PIPING: Refer to Pages 10 and 11 for installation instructions for swimming pool circulating pump applications. Refer to Pages 6 through 9 for recommended and not recommended practices in suction connections in centrifugal installations. DISCHARGE PIPING: Refer to illustrations on Page 12 and 13 for recommended and not recommended practices in discharge connections. ELECTRICAL CONNECTION: Hazardous voltage. Can shock, burn, or cause death. All wiring should be done by a qualified electrician. Disconnect power to pump before servicing. Check voltage and phase stamped on pump motor nameplate before wiring. Be sure they agree with your electric current supply. They MUST be the same. If in doubt, check with your local power company. Refer to illustration on Page 14 for minimum recommended pumping panel components that help safeguard your pump during operation. F00634 Shims ge ina Dra Concrete Foundation 797 0394 • There are several types of permanent pump/ foundation installations in use. Those pictured above are typical. • If grout is used, top of concrete should be left rough to provide a good bonding surface. • Foundation should slope away from pump to prevent liquid from pooling. Page 5 Installation Centrifugal Pump Suction Connection Suction Lift See Pages 10 and 11 for Swimming Pool Installation requirements. Short length of straight pipe after reducer. ( 2 times pipe diameter minimum ) For Han-Dee Primer connection, see start-up. Suction Gauge Straight run, short as possible but at least 6 times pipe diameter ("D") after elbow to stabilize flow. 503 0194 Eccentric Reducer flat side up. See foundation section. Standard or long radius elbow. Support pipe as required Slope upward to pump. NOTICE: All connections must be air tight. As close as possible • Use pipe, tubing, or reinforced hose to make suction connection. Hose must have sufficient strength to resist collapse under the pressure differential that occurs while pump is running. • Suction pipe size should be at least one commercial pipe size larger than opening of pump inlet. Flow velocity should not exceed 8 ft./sec. Pipe diameter ("D") 4 x "D" minimum • Suction screen must screen out solids that could clog pump impeller. • Suction screen area must be at least four times suction pipe area. • Net Positive Suction Head Available (NPSHA) must exceed Net Positive Suction Head Required (NPSHR) by the pump or reduced performance and severe pump damage may result. 1 x "D" minimum from bottom • All suction piping must have continuous rise to the pump suction inlet. A 1/4 inch per foot minimum slope is recommended. Strainer prevents debris from entering pump suction and prevents entrapment hazard. Foot valve maintains pump prime after shutoff. Recommended Page 6 F00634 Installation Centrifugal Pump Suction Connection Suction Lift See Pages 10 and 11 for Swimming Pool Installation requirements. Do not use Concentric Reducer. 1152 0794 Concentric Reducer causes high spots along the suction line resulting in air pockets. Do not install valves in suction line. No support or uneven mounting not recommended. Unsupported pipe causes excessive stress on pump and fittings. Excess use of pipe fittings means potential air leaks. Elbow immediately in front of pump intake not recommended. • Suction pipe sloping downward to pump inlet will trap air which will reduce performance and may cause pump to lose prime. Long run not recommended Pipe diameter ("D") undersized reduces performance Vortex caused by insufficient submergence may cause pump to lose prime. • Suction piping that is undersized will create excess friction losses that may cause cavitation and a reduction in pump performance. • Excess fittings and bends in suction line results in trapped air, reduced performance, and high friction losses which may cause cavitation. Suction entrapment hazard if strainer is High suction lift should be avoided. Less than 4 x "D" No strainer may cause pump to clog. not used. Insufficient bottom clearance Not Recommended F00634 Page 7 Installation Centrifugal Pump Suction Connection When Flooded Suction Exists See Pages 10 and 11 for Swimming Pool Installation requirements. Short run of straight pipe after reducer (2 times pipe diameter). Water under pressure Maintain minimum liquid level to prevent vortexing. Eccentric Reducer flat side up. Suction Gauge 0294 Isolation Valve full open when pumping. Straight run, short as possible but at least 6 times pipe diameter after pipe fitting to stabilize flow. Slope upward to pump. Support pipe as required • Use pipe, tubing, or reinforced hose to make suction connection. Hose must have sufficient strength to resist collapse under the atmospheric pressure differential that may occur while pump is running. • It is important, even with a flooded suction condition, that proper pipe fittings are used so water is delivered to impeller eye with a smooth flow and consistent velocity. Standard or long radius elbow. • An isolation valve is used in a pressurized suction pipe to permit servicing pump. • Piping run and connection fittings should be properly aligned and independently supported to reduce strain on pump case. • If solids are present, a strainer should be used to protect the pump. • Suction pipe size should be at least one commercial pipe size larger than opening of pipe inlet. Flow velocity should not exceed 8 ft./sec. Recommended Page 8 F00634 Installation Centrifugal Pump Suction Connection When Flooded Suction Exists See Pages 10 and 11 for Swimming Pool Installation requirements. Inverted Eccentric Reducer may result in air pocket. Water under pressure Valve in upward position may trap air. Do not leave valve partially closed. 703 0294 Check Valve in suction pipe not needed. Concentric Reducer may cause air pockets. Unsupported pipe causes excessive stress on pump and fittings. Miter elbow or short radius elbow not recommended. • Suction piping that is undersized will create excess friction losses that may cause cavitation and a reduction in pump performance. Elbow immediately in front of pump intake not recommended. • Excess fittings and bends in suction line results in trapped air, reduced performance, and high friction losses which may cause cavitation. • If check valve is required for back flow prevention, locate on the discharge side of pump. Not Recommended F00634 Page 9 Installation Discharge Connection Expansion joint with tie rods where needed. Isolation Valve Use Concentric Reducer to mimimize friction losses. Discharge pipe diameter at least one nominal pipe size larger than discharge opening in pump. This view shows discharge fittings typical of pump with flooded suction. This fitting may be used to check shut-off head. 706 0294 Pressure Gauge Support piping as required Align piping to minimize flange stress. These two views show discharge fittings typical of pump with suction lift. Isolation valve to permit servicing of check valve or pump. • Use pipe, tubing or reinforced hose to make discharge connection. Material selected must have sufficient strength for operating pressures. • Discharge pipe should be sized so that flow velocity is below 8 feet per second. • Use ONLY non-slamming check valves to prevent hydraulic shock (water hammer). Non-Slam or spring loaded check valve. • Use gate, ball, or butterfly valve for isolation. Valve should be full open during operation. • Maintain proper pipe size throughout discharge system, using as few elbows and tees as possible to keep friction loss to a minimum. • Install pressure gauge after reducer as shown to check operating pressure or shut-off head. Discharge Priming Valve Recommended Page 12 F00634 Installation Discharge Connection Avoid check valves that cause hydraulic shock. 708 0294 Avoid undersized pipe diameter. Do not force alignment that can cause flange stresses. Do not leave pipe unsupported. Do not use Gate Valve to throttle flow. Avoid abrupt change in pipe size. • Avoid excess friction loss caused by numerous fittings, insufficient pipe diameter, and sharp turns in pipe run. • Swing type check valves can permit build-up of reverse velocity before closing causing hydraulic shock or “water hammer.” Not Recommended F00634 Page 13 Installation Electrical Connection Protect Your Investment Incoming Power 1 4 2 5 3 L1 AMP L2 L3 TIME AUTO STOP HAND START NEMA 3R Enclosure Minimum recommended components to protect your pump during operation. Check all local electrical codes prior to installation. ❶ Contactor ❷ Lightning Arrestor ❸ Loss of Prime Protection ❹ Fuseable Disconnect 884 0494 Page 14 ❺ Starter F00634 Start-up General Information CHECK ROTATION: Before pump is put into operation, rotational direction must be checked to assure proper performance of pump. Refer to illustration on Page 16. Hazardous voltage. Can shock, burn, or cause death. Disconnect power to pump before servicing. Do not attempt any wiring changes without first disconnecting power to pump. PRIMING: Pump priming is the displacement of air with water in the pump and suction piping. Pump MUST BE completely filled with water when operating. Refer to Page 17 for instruction on the following conditions: 1. Suction lift with priming pump (water source below pump). 2. Suction lift with foot valve (water source below pump). 3. Flooded suction (water source above pump, or incoming water pressure is greater than atmospheric pressure). SPECIAL CASE - HYDRAULIC BALANCED PUMPS: Hydraulic balanced pumps operate with a very low positive pressure across the stuffing box, permitting a much looser fit of the packing rings around the shaft sleeve to control the loss of water from the pump through the stuffing box. Because of the looser fit of the packing rings, air can be more easily drawn into the pump through the stuffing box when priming the pump with an air evacuation type primer. A grease fitting, communicating through the side of the stuffing box to a lantern ring in the packing set, is provided to grease-seal the stuffing box to prevent air leakage during priming. F00634 If pump cannot be primed due to air leakage through stuffing box, DO NOT tighten packing. Instead, pump grease into lantern ring until back pressure occurs forcing grease into the lantern ring, grease-sealing the stuffing box. After priming, when unit is put into operation, the grease will be flushed out through the packing by the water flowing outward through the stuffing box. Proceed with normal adjustment of the packing as described on Page 18. Note that the grease seal only is used for control of air leaking during priming, and that only the packing gland is used to control flow of water through the stuffing box during normal operation. When necessary to replenish the grease supply use an NLGI no. 4 Water Pump Grease. STARTING: Never run pump dry. Running pump without water will overheat pump and damage internal parts. Always make sure pump is primed prior to startup. NOTICE: Refer to maintenance section if pump has packing for adjustment prior to start-up. Prime pump by one of the above procedures. Turn on power to pump. Slowly open discharge valve until desired flow rate is achieved. Place the “Hand-Off-Auto” selector switch in the “Auto” position. The pump will be started automatically when the pilot device signals the motor starter. STOPPING: Pump will stop automatically when the pilot device deenergizes the motor starter. Turn the “Hand-Off-Auto” selector switch to “Off” position if you want to stop the pump while it is running. Page 15 Start-up ta ro Clock wis e Determine Pump Rotation tion 12 9 Viewed from this direction 3 6 As viewed Engage start switch momentarily (bump motor) to observe rotational direction. 1129 0694 Direction of Pump Rotation is determined by viewing liquid end of pump from the back or shaft side, and not from looking into the impeller eye or front of volute case. A rotation direction arrow is cast into the pump body and shows correct rotation. • Electric Motors: Single Phase: Refer to wiring information on the motor plate to obtain proper rotation. • Pump running backward - Centrifugal pumps will still pump liquids, however, GPM and head (discharge pressure) will be a fraction of the published performance. Three Phase: If pump runs backwards, reverse any two leads coming off incoming power (L1, L2, L3) until proper rotation is obtained. Reverse L1 and L2, or L2 and L3, or L1 and L3. Page 16 F00634 Maintenance General Information LUBRICATION: LIQUID END of pump requires no lubrication. Wear rings, packing rings, and models using a mechanical shaft seal, are lubricated by the liquid being pumped. Do not run dry! NOTE: Grease fitting in packing area is for priming only. See PRIMING in start-up section for instruction. MOTOR bearings are lubricated at the factory. Relubrication at intervals consistent with the amount of use will provide maximum bearing life. Refer to motor Instruction Manual for proper motor lubrication and maintenance instructions. PERFORMANCE CHECK: Periodically check the output of the pump. If performance is noticeably reduced, refer to Troubleshooting Chart. OBSERVATIONAL MAINTENANCE: When the pump and system operation have been stabilized, verify that pump unit is operating properly. Observe the following: VIBRATION: All rotating machines can be expected to produce some vibration, however, excessive vibration can reduce the life of the unit. If the vibration seems excessive, discontinue operation, determine cause of the excessive vibration, and correct. NOISE: When the unit is operating under load, listen closely for unusual sounds that might indicate that the unit is in distress. Determine the cause and correct. OPERATING TEMPERATURE: During operation, heat is dissipated from the pump and the driver. After a short period of time, the surface of the pump bracket will be quite warm (as high as 150°F), which is normal. If the surface temperature of the pump bracket or driver is excessive, discontinue operation, determine cause of the excessive temperature rise, and correct. Bearings will run hotter for a brief run-in period after packing which is normal. However, worn bearings will cause excessive temperatures and need to be replaced. The pump unit is cooled by the water flowing through it, and will normally be at the temperature of the water being pumped. STUFFING BOX: After a short period of operation, verify that the stuffing box area and gland are not hot. Page 18 If heating is detected, loosen the gland nuts evenly until water is just running out of stuffing box in a DROPLET form. Water must not be streaming or spraying out. Verify cool operation periodically. Adjust gland nuts EVENLY as necessary for lubrication and cooling of the packing. If packing has been tightened to the limit of the packing gland travel, additional packing is necessary. PACKING: Starting new pump. Before starting pump for the first time, loosen gland nuts and retighten finger tight. Proceed with pump start-up procedure. Allow packing to leak liberally for a few moments. Then tighten gland nuts one complete turn each until leakage is reduced to 40 to 60 drops per minute. REPACKING: Refer to Page 19. MECHANICAL SEAL: Adjustment or maintenance is normally not required. The seal is enclosed within the pump and is self adjusting. Seal is cooled and lubricated by the liquid being pumped. Refer to Pages 20 and 21 for removal and replacement. Do not run dry! PUMP PROTECTIONCOLD WEATHER/ WET WEATHER INSTALLATIONS: SYSTEM DRAINS: Provide drain valves to empty system, including pump case, to prevent freezing damage. SHELTER: If possible, provide shelter for unit to protect from weather. Allow adequate space around pump unit for service. When effectively sheltered, a small amount of heat will keep temperature above freezing. Provide adequate ventilation for unit when running. For severe weather problems, where other shelter is not practical, a totally enclosed fan-cooled enclosure can be considered for electric motors. CONDENSATION: When the temperature of metal parts is below dew point and the surrounding air is moist, water will condense on the metal surfaces and can cause corrosion damage. In severe situations, a space heater can be considered to warm the unit. F00634 Maintenance Packing Ring Replacement–All Models Removal 1 2 Packing Hooks Packing Gland Motor / Engine not shown for clarity. Motor / Engine not shown for clarity. 826 0394 • Unfasten hardware holding Packing Gland in place and slide back on shaft to expose packing rings. A split Packing Gland is shown. • Remove packing rings from Stuffing box using two commercially available Packing Hooks as shown. • Slide Lantern Ring (if used) back to expose any remaining rings, including metallic. Remove them in the same manner. Installing New Rings Motor / Engine not shown for clarity. Typical Packing Arrangement Ring Joints 1147 0794 Packing Rings Metallic Ring Lantern Ring • Clean shaft sleeve and Packing Gland. • Inspect shaft sleeve for wear, replace if needed. • Install new packing rings in stuffing box by placing over shaft sleeve and pushing them in as far as they will go. • Rotate ring joint 90 degrees when installing each ring as shown. F00634 • Slide packing gland into position, then gently and evenly tighten nuts to force rings into place and seat (do not overtighten). Loosen nuts again to hand tight. • Start primed pump and allow packing to leak liberally. • Tighten gland nuts one complete turn each until leakage is reduced to 40 to 60 drops per minute. Page 19 Maintenance Mechanical Shaft Seal Models B4ZPBH, B5ZPBH, B6ZPBHH. All other models turn to Page 22. Removal 1 2 6059 0609 6060 0609 • Unfasten hardware holding volute to bracket. • Remove volute to expose impeller. • Peel off old gasket or O-Ring and discard. • Hold impeller stationary and remove impeller screw and associated hardware. 3 4 Shaft Sleeve Gear Puller Finger Behind Vane Note: A hexnut placed between the jackscrew and shaft end will prevent damage to the shaft and impeller screw threads. Gear Puller Finger Behind Vane Gear Puller Jackscrew 6062 0609 6061 0609 • Install a standard gear puller to shaft end and impeller, placing puller fingers behind impeller vanes as shown. • Rotate gear puller jackscrew until impeller clears shaft. Remove shaft key. • If a seal retaining ring is part of the assembly, remove it. • Pull seal plate out of bracket. Mechanical shaft seal will come off with seal plate. Stationary Seat 5 Rotating Seat Spring Spring Retainer 6063 0609 • Push stationary seal out of seal cavity from the back of seal plate. Stationary Seat 1189 0794 • Clean seal cavity in seal plate thoroughly. Procedure and parts will vary slightly depending on pump style. Page 20 F00634 Maintenance Mechanical Shaft Seal Models B4ZPBH, B5ZPBH, B6ZPBHH. All other models turn to Page 23. Installing New Seal 1 Cardboard washer (Supplied with seal) Polished Face 2 Do not scratch or chip polished ceramic face. Also . . .do not touch polished surface 6064 0609 6065 0609 • Place seal plate on a smooth, flat surface, pump side up. ceramic face with cardboard washer and press straight in using a piece of pipe or tubing. • Apply a small amount of mineral oil to O-Ring on stationary seal and press into seal cavity. Cover • Reinstall seal plate in bracket using extreme care not to scratch or chip ceramic face of seal with shaft. 3 4 Key 6067 0609 6066 0609 • Clean threads thoroughly. • Apply a small amount of mineral oil to inside diameter of rubber ring in rotating seat and outside of shaft sleeve. Slide rotating seat onto shaft, polished face first, until it is tight against ceramic face. • Apply non-permanent thread adhesive to impeller capscrew and shaft threads. • Install impeller washer, shakeproof lockwasher, and capscrew. • Compress seal spring and install retaining ring in shaft sleeve groove (if used). • Place impeller key in motor shaft keyway. Slide impeller on to shaft as far as possible. 5 • Install gasket and volute on bracket. Use a new gasket or O-Ring when reassembling to prevent leakage ( a coat of grease on gasket will aid in future disassembly and maintenance). • Apply anti-seizing compound to capscrews and tighten securely. 6068 0609 Procedure and parts will vary slightly depending on pump style. F00634 Page 21 Maintenance Mechanical Shaft Seal Removal 1 2 1135 0794 1137 0794 • Unfasten hardware holding volute to bracket. NOTE: For model B4EY, consult factory for special instructions. • Peel off old gasket or O-Ring and discard. • Hold impeller stationary and remove impeller screw and associated hardware. • Remove volute to expose impeller. Gear Puller Finger 3 4 Key Note: A hexnut placed between the jackscrew and shaft end will prevent damage to the shaft and impeller screw threads. 1139 0794 Shaft Sleeve 1138 0794 Gear Puller Jackscrew Gear Puller Finger • Remove capscrews holding bracket to motor. • Rotate gear puller jackscrew until impeller clears shaft. Mechanical shaft seal will come off with motor bracket. • Install a standard gear puller to shaft end and motor bracket placing puller fingers in the area shown. • If a seal retaining ring is part of the assembly, it will need to be replaced. Stationary Seat 5 Rotating Seat Spring Spring Retainer 1140 0794 • Push stationary seal out of seal cavity from the back of bracket. Stationary Seat 1189 0794 • Clean seal cavity in bracket thoroughly. Procedure and parts will vary slightly depending on pump style. Page 22 F00634 Mechanical Shaft Seal 1 Cardboard washer (Supplied with seal) If shaft is threaded, cover threads with tape to protect seal during installation. 2 Polished Face Do not scratch or chip polished ceramic face. Also . . .do not touch polished surface 11 3 079 11 2 079 • Place bracket on a smooth, flat surface, pump side up. ceramic face with cardboard washer and press straight in using a piece of pipe or tubing. • Apply a small amount of mineral oil to O-Ring on stationary seal and press into seal cavity. Cover • Reinstall bracket on motor using extreme care not to scratch or chip ceramic face of seal with shaft. 3 4 Key 11 11 5 079 079 • Clean threads thoroughly. • Apply a small amount of mineral oil to inside diameter of rubber ring in rotating seat and outside of shaft sleeve. Slide rotating seat onto shaft, polished face first, until it is tight against ceramic face. • Apply non-permanent thread adhesive to impeller capscrew and shaft threads. • Install impeller washer, shakeproof lockwasher, and capscrew. • Compress seal spring and install retaining ring in shaft sleeve groove (if used). • Place impeller key in motor shaft keyway. Slide impeller on to shaft as far as possible. 5 • Install gasket and volute on bracket. Use a new gasket or O-Ring when reassembling to prevent leakage ( a coat of grease on gasket will aid in future disassembly and maintenance). 11 6 079 • Apply anti-seizing compound to capscrews and tighten securely. Procedure and parts will vary slightly depending on pump style. F00634 Page 23 Pump Nomenclature General Information ORDERING REPLACEMENT PARTS: Locate the Berkeley nameplate on the pump; plate is normally on the motor bracket. Information found on this plate is shown below. To be sure of receiving correct parts, provide all nameplate data when ordering. The BM (Bill of Material) number is most important. Write your nameplate information on the blank nameplate below for future reference as nameplates can become worn or lost. Illustrations on the following page show typical components used in the assembly of motor drive centrifugal pumps. Both mechanical seal and packing styles are shown. Refer to these drawings when ordering any replacement parts. SAMPLE ONLY BERKELEY PUMPS MODEL S.N. OR DATE B3TPMS IMPELLER DIA. G100894 B.M. 6-1/8" B54598 788 0394 BERKELEY PUMPS MODEL S.N. OR DATE IMPELLER DIA. B.M. 344 1093 Record your nameplate data here. Page 24 F00634 Pump Nomenclature Electric Motor Drive—with removable seal plate Models B4ZPBH, B5ZPBH, B6ZPBHH Mechanical Seal Motor Bracket Seal Plate Seal Retaining Ring Impeller Impeller Washer Mechanical Seal Shakeproof Lockwasher Impeller Capscrew Volute Case Wear Ring • Electric motor not shown. Gasket or O-Ring • Drawing shows typical motor drive pump with packing or a mechanical shaft seal. Parts on some models will vary slightly. 6069 0609 Packing Packing Gland Lantern Ring Shaft Sleeve Packing Rings Metallic Ring Motor Bracket Grease Fitting Seal Plate Impeller Impeller Washer Shakeproof Lockwasher Impeller Capscrew Volute Case Wear Ring O-Ring or Gasket 6070 0609 F00634 Page 25 Pump Nomenclature Electric Motor Drive—with fixed seal plate Mechanical Seal Clack Weight Clack Washer Suction Cover Motor Bracket Impeller Impeller Lock Nut Case Gasket Seal Retaining Ring Pump Case (Volute) Impeller Mechanical Seal Impeller Washer Shakeproof Lockwasher Impeller Capscrew Shaft Sleeve Rubber Clack (Check Valve) Volute Case • Electric motor not shown. Wear Ring • Drawing shows typical motor drive pump with packing or a mechanical shaft seal. Parts on some models will vary slightly. Gasket or O-Ring 5530 1006 Packing Impeller Shakeproof Lockwasher Gasket or O-Ring Packing Gland Lantern Ring Packing Grease Cup or fitting Shaft Sleeve Impeller Impeller Washer Impeller Capscrew Packing Rings Metallic Ring Balance Ring Gasket Clack Weight Volute Case Clack Washer 5531 1006 Impeller Lock Nut Motor Bracket Case Gasket Pump Case (Volute) Balance Ring Suction Cover Rubber Clack (Check Valve) Page 26 F00634 Maintenance Troubleshooting PROBABLE CAUSE SYMPTOM A Pump runs, but no water delivered Not enough water delivered Not enough pressure Excessive vibration Abnormal noise Pump stops Overheating X B X X C GROUP I ELECTRICAL D E F X X X X X X X X G H I X X X X X X A X X X X X E F X X X GROUP III SYSTEM A B C X X X X X X X X X X X X X X X CAUSE GROUP II MECHANICAL B C D X X X X X X X X X X CORRECTIVE ACTION I. ELECTRICAL A. No voltage in power system Check phase-to-phase on line side of starter contactor. Check circuit breaker or fuses. B. No voltage on one phase (Three Phase Units) Check phase voltage on line side of starter contactor. Isolate open circuit (circuit breaker, fuse, broken connections, etc.) C. Low voltage at motor Running voltage across each leg of motor must be ±10% of nominal voltage shown on nameplate. D. Motor leads improperly grouped for voltage Refer to lead grouping diagram on motor nameplate. E. Control failure Check control device, starter contactor, H-O-A selector switch, etc., for malfunction. F. Thermal overload switch open Check phase-to-phase on line side of starter contactor. G. Installation failure Check motor or windings to ground with megohmmeter. H. Open windings Check leg-to-leg with ohmmeter. I. Frequency variation Check frequency of power system. Must be less than 5% variation from motor nameplate rating. II. MECHANICAL A. Flow through pump completely or partially obstructed Locate and remove obstruction. Refer to Repair Instructions for disassembly. B. Wrong direction of rotation Reverse rotation of three phase motor by interchanging any two leads. See manufacturer’s Instructions for reversing single phase motor. C. Pump not primed Reprime. Inspect suction system for air leaks. D. Internal leakage Check impeller for wear of controlled clearances (See Repair Instructions). E. Loose parts Inspect. Repair. F. Stuffing box not properly adjusted Adjust gland. III. SYSTEM A. Pressure required by system at design flow rate exceeds pressure rating of pump Compare pump pressure and flow rate against pump characteristic curve. Check for closed or partially closed valve in discharge piping system. Reduce system pressure requirement. Increase pressure capability of pump. B. Obstruction in suction piping Locate and remove obstruction. C. Pressure rating of pump exceeds pressure requirement of system at design flow rate Compare pump pressure and flow rate against pump characteristic curve. Inspect discharge piping system for breaks, leaks, open by-pass valves, etc. If necessary, reduce flow rate by partially closing discharge valve. F00634 Page 27 Berkeley Warranty LIMITED WARRANTY BERKELEY warrants to the original consumer purchaser (“Purchaser” or “You”) of the products listed below, that they will be free from defects in material and workmanship for the Warranty Period shown below. Product Warranty Period Water Systems: Water Systems Products — jet pumps, small centrifugal pumps, submersible pumps and related accessories whichever occurs first: 12 months from date of original installation, or 18 months from date of manufacture Pro-SourceTM Composite Tanks 5 years from date of original installation Pro-SourceTM Steel Pressure Tanks 5 years from date of original installation Pro-SourceTM Epoxy-Lined Tanks 3 years from date of original installation Sump/Sewage/Effluent Products 12 months from date of original installation, or 18 months from date of manufacture Agricultural/Commercial: Centrifugals – close-coupled motor drive, frame mount, SAE mount, engine drive, VMS, SSCX, SSHM Submersible Turbines, 6” diameter and larger 12 months from date of original installation, or 24 months from date of manufacture 12 months from date of original installation, or 24 months from date of manufacture Our limited warranty will not apply to any product that, in our sole judgement, has been subject to negligence, misapplication, improper installation, or improper maintenance. Without limiting the foregoing, operating a three phase motor with single phase power through a phase converter will void the warranty. Note also that three phase motors must be protected by three-leg, ambient compensated, extra-quick trip overload relays of the recommended size or the warranty is void. Your only remedy, and BERKELEY’s only duty, is that BERKELEY repair or replace defective products (at BERKELEY’s choice). You must pay all labor and shipping charges associated with this warranty and must request warranty service through the installing dealer as soon as a problem is discovered. No request for service will be accepted if received after the Warranty Period has expired. This warranty is not transferable. BERKELEY SHALL NOT BE LIABLE FOR ANY CONSEQUENTIAL, INCIDENTAL, OR CONTINGENT DAMAGES WHATSOEVER. THE FOREGOING LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER EXPRESS AND IMPLIED WARRANTIES, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. THE FOREGOING WARRANTIES SHALL NOT EXTEND BEYOND THE DURATION EXPRESSLY PROVIDED HEREIN. Some states do not allow the exclusion or limitation of incidental or consequential damages or limitations on the duration of an implied warranty, so the above limitations or exclusions may not apply to You. This warranty gives You specific legal rights and You may also have other rights which vary from state to state. This warranty supersedes and replaces all previous warranty publications. In the U.S.: BERKELEY, 293 Wright St., Delavan, WI 53115 In Canada: 269 Trillium Dr., Kitchener, Ontario N2G 4W5 Page 28 F00634