Indoor Busbar Trunking Systems (32 A)

Transcription

Indoor Busbar Trunking Systems (32 A)
Indoor Busbar Trunking Systems (32 A)
E-LINEFL/FLD
CONTENTS
E-LINE FL
Overview
2
General Specifications
3
FL Busbar Design and Product Selection
4
Specifications and Safety
5
FL Busbar Colours and Texture Coating
6
FL Busbar Product Order Codes
FL Busbar Mounting
FL Busbar Area of Usage
7-10
11-12
13
E-LINE FLD
Overview
14
General Specifications
15
FLD Data Busbar Design and Product Selection
16
FLD Data Busbar Colours and Texture Coating
17
FLD Data Busbar Product Order Codes
FLD Data Busbar Mounting
18-22
23
FL / FLD Busbar Area of Usage
24-25
General Product Specifications
26
CE Declaration of Conformity
27
Certificate
28
ELINEFL
OVERVIEW
Aesthetic, safe, practical and flexible structure eliminating cable mess.
E-LINE FL Indoor Busbar Trunking Systems
FL Busbar system allows easy and safe power distribution in workplaces
- Offices
- Workshops
- Stores
- Hospitals
- Laboratories
- Airports
- Schools
Wherever power is needed without the need for additional cabling.
Eliminates trailing cables and fixed sockets for low power distribution.
E-LINE FL Indoor Busbar Trunking Systems can be mounted on any structure or surface using brackets. They can be used
separately for power or UPS sockets requirements when needed.
Stylish and special UPS sockets with LED illumination and various colours can be installed in any position spot without the need
for a hand tool.
2
ELINEFL
GENERAL SPECIFICATION
Power or UPS sockets; 16A, 250V (protected)
FL Busbar; 32A, 250V Operating voltage
IP2X Protection Class
Use of sockets in various colours for mains or UPS circuits
Single phase circuit (3 conductors); L+N+(PE) (65x28 mm)
FL
Aesthetic, safe, practical and flexible structure
Easy and fast mounting
Standard length is 1m and 2m.
Standard color is white (RAL 9003). Refer to page 6 for different color and texture coating selections.
3
ELINEFL
FL BUSBAR DESIGN and PRODUCT SELECTION
For design and product selection, select the numbered products and accessories shown below according to the layout of the
building as shown in the project example.
Note: Please consider the voltage drop and current rating by checking the length of the busbar and the number of sockets
proposed.
7
4
6
5
1-FL Busbar Feeder Unit, 32A, 250V, L/N/PE
3
2
4
2-FL Busbar; 32A, 250V, L/N/PE
8
3-FL Busbar Internal Corner Kit; 32A, 250V, L/N/PE
4-FL Busbar Joint Set; 32A, 250V, L/N/PE
1
5-FL Busbar External Corner Kit, 32A, 250V, L/N/PE
6-FL Power/UPS Plug; 16A, 250V (Protected)
7-FL Busbar End Cap, 32A, 250V, L/N/PE
8-FL Busbar Mounting Bracket Set
Note: Add 3 “FL Busbar Bracket Set” per 2m FL busbar length and 2 per 1m FL Busbar length.
Component List
Serial
No
Description
Pcs.
Order
Code
1
FL Busbar (2 m x 5)
10 m
3048938
2
FL Internal Corner Kit
1 pc
3048953
3
FL External Corner Kit
1 pc
3048956
4
FL Feeder Unit
1 pc
3048959
5
FL Power Socket 16A, 250V
4 pcs
3048941
6
FL Busbar Mounting Bracket Set
15
3048962
7
FL End Cap
1 pc
3048965
8
FL Joint Set
6 pc
3048962
: Yener Tekstil
Project
: Corlu Tesisleri
Project No
: 0120
Prepared by
Company
Name
: Volkan ZIMBA
Date
: 29 / 05 / 2014
Signature
:
Project sample
4
ELINEFL
SPECIFICATIONS
Rated Current
In
A
Busbar Code
32
032
Standard
IEC 61439-6 / IEC 61534-1 / IEC 60884-1
Rated Insulation Voltage
Ui
V
415
Rated Operating Voltage
Ue
V
250
f
Hz
50
Rated Frequency
3
Pollution Level
2X
IP
Rated Short Circuit Current (kA)
Icc
kA(rms)
(*)
R20
mW/m
3,2827
R
mW/m
3,7285
Xph
mW/m
~0
FL
FL
Protection Class
PHASE CONDUCTOR CHARACTERISTICS
Average Ohmic Resistance of In Current at 20 °C
Average Ohmic Resistance of In Current at 35 °C Ambient Temperature
Reactance (Temperature Independent)
(*) Short circuit current (kA) is determined according to the selected fuse type.
SAFETY
E-LINE FL BUSBAR is produced in accordance with ISO 9001 standards with a certified quality management system using the
world's latest manufacturing technologies. Units are designed and tested according to IEC 61439-6, IEC 61534-1 and IEC 60884-1.
The phase conductor structure is protected against finger contact and dust using a screen system along the length of the busbar.
In cases where the socket is live the socket is secured into position using a special locking system.
Sockets do not come off thanks to the clamping structure.
STEP 1
Mount socket in the
line
STEP 2
Turn the socket 90°
STEP 3
The socket is ready
for use
Caution: “ON” position must be
aligned to the top edge of FL Busbar.
5
ELINEFL
FL BUSBAR COLOURS and TEXTURE COATING
FL Busbar's Standard colour is white. However, colour selections below are produced according to the environment, walls and
floors when requested.
MAIN COLOURS
WHITE
RAL 9003
GREY
RAL 7040
LIGHT
BROWN
RAL 1001
FINISHING PATTERNS
OAK
WALNUT
CHERRY
BROWN
RAL 8004
SOCKET SURFACE FRAMES
They can be produced with or without LED in the colours
shown below when requested.
RED
BLUE
ORANGE
GREEN
There may be differences between colours and patterns in the catalogue and the actual product.
6
ELINEFL
FL BUSBAR PRODUCT ORDER CODES
FL Busbar
Order Code
Product Description
White
Grey
Light
Brown
Brown
Oak Texture Walnut Tex- Cherry TexCoating
ture Coating ture Coating
FL Busbar, 32A, 250V, L/N/PE (1m), PVC
3050404 3050403 3050405 3050402 3050708 3050744 3050777
FL Busbar, 32A, 250V, L/N/PE (2m), PVC
3048938 3048939 3049169 3048940 3050707 3050743 3050776
FL
28
9.5
57.3
65
55.8
1000mm
2000mm
7
ELINEFL
FL BUSBAR PRODUCT ORDER CODES
FL Power Socket
Order Code
Product Description
White
Grey
Light
Brown
Brown
Oak Texture Walnut Tex- Cherry TexCoating
ture Coating ture Coating
FL 16A 250V Power Socket, Red Frame, LED
3049157 3049161 3049174 3049165 3050719 3050753 3050786
FL 16A 250V Power Socket, Blue Frame, LED
3049158 3049162 3049175 3049166 3050721 3050755 3050788
FL 16A 250V Power Socket, Orange Frame, LED
3049159 3049163 3049176 3049167 3050723 3050757 3050790
FL 16A 250V Power Socket, Green Frame, LED
3049160 3049164 3049177 3049168 3050726 3050759 3050792
FL 16A 250V Power Socket, Red Frame, Without LED
3048941 3048945 3049170 3048949 3050709 3050745 3050778
FL 16A 250V Power Socket, Blue Frame, Without LED
3048942 3048946 3049171 3048950 3050712 3050747 3050780
FL 16A 250V Power Socket, Orange Frame, Without LED 3048943 3048947 3049172 3048951 3050715 3050749 3050782
FL 16A 250V Power Socket, Green Frame, Without LED
3048944 3048948 3049173 3048952 3050717 3050751 3050784
55.7
40.5
9
∅62.9
.
62
∅
FL UPS Socket
Order Code
Product Description
White
Grey
Light
Brown
Brown
Oak Texture Walnut Tex- Cherry TexCoating
ture Coating ture Coating
FL 16A 250V UPS Socket, Red Frame, LED
3050365 3050369 3050382 3050373 3050720 3050754 3050787
FL 16A 250V UPS Socket, Blue Frame, LED
3050366 3050370 3050383 3050374 3050722 3050756 3050789
FL 16A 250V UPS Socket, Orange Frame, LED
3050367 3050371 3050384 3050376 3050724 3050758 3050791
FL 16A 250V UPS Socket, Green Frame, LED
3050368 3050372 3050385 3050377 3050727 3050760 3050793
FL 16A 250V UPS Socket, Red Frame, Without LED
3050353 3050357 3050378 3050361 3050711 3050746 3050779
FL 16A 250V UPS Socket, Blue Frame, Without LED
3050354 3050358 3050379 3050362 3050714 3050748 3050781
FL 16A 250V UPS Socket, Orange Frame, Without LED 3050355 3050359 3050380 3050363 3050716 3050750 3050783
FL 16A 250V UPS Socket, Green Frame, Without LED
55.7
40.5
.9
∅62.9
62
∅
8
3050356 3050360 3050381 3050364 3050718 3050752 3050785
ELINEFL
FL BUSBAR PRODUCT ORDER CODES
FL Feeder Unit
Order Code
Product Description
White
Grey
Light
Brown
Brown
Oak Texture Walnut Tex- Cherry TexCoating
ture Coating ture Coating
3048959 3048960 3049180 3048961 3050730 3050763 3050796
FL 32A 250V, L/N/PE, Feeder Unit, PVC
28
65
154
Side View
FL
Front View
FL End Cap
Order Code
Product Definition (Description)
White
Grey
Light
Brown
Brown
Oak Texture Walnut Tex- Cherry TexCoating
ture Coating ture Coating
3048965 3048966 3049182 3048967 3050733 3050766 3050799
FL 32A 250V, L/N/PE, End Cap, PVC
40
40
28
65
20
Front View
Top View
FL Joint Unit
Order Code
Product Description
White
Grey
Light
Brown
Brown
Oak Texture Walnut Tex- Cherry TexCoating
ture Coating ture Coating
3048962 3048963 3049181 3048964 3050731 3050764 3050797
68.3
35.5
FL 32A 250V, L/N/PE, Joint Unit, PVC
16
60
Front View
29.6
Side View
9
ELINEFL
FL BUSBAR PRODUCT ORDER CODES
FL External Corner Kit
Order Code
Product Description
White
FL 32A 250V, L/N/PE, External Corner Kit, PVC
Grey
Light
Brown
Brown
Oak Texture Walnut Tex- Cherry TexCoating
ture Coating ture Coating
3048956 3048957 3049179 3048958 3050729 3050762 3050795
65
69.2
116.7
116.7
Top View
Side View
FL Internal Corner Kit
Order Code
Product Description
White
Grey
Light
Brown
Brown
Oak Texture Walnut Tex- Cherry TexCoating
ture Coating ture Coating
3048953 3048954 3049178 3048955 3050728 3050761 3050794
FL 32A 250V, L/N/PE, Internal Corner Kit, PVC
69.2
113.3
28
113.2
Top View
Side View
FL Mounting Bracket Set
Product Description
FL Mounting Bracket Set, PVC
10
Order Code
3048968
ELINEFL
FL BUSBAR MOUNTING
FL Busbar Feeder Unit Mounting
1
1-Busbar Feeder unit with cover.
2-Remove the cover of the feed unit
and mount the unit on the wall with 2
M6 dowels and screws.
6
3
4
3-Cut the cable cover hole on the
cover and remove.
4-Strip the end of the cable and insert
through the hole.
8
7
FL
5
2
CLICK
5-Fix the cable ends (L/N/PE) into the
corresponding terminals and tighten
the cable clamp.
6-Replace the feeder unit cover
ensuring that the cover is correctly
aligned with the end of the busbar.
7-Clip the cover into place ensuring
that all of the claws are located.
8-Finally check that the cable is not
loose and that the cover is fully
slotted.
FL Busbar Joint Set Mounting
1
1-Place the connector piece onto the
FL Busbar body and insert the
conductors between the contacts
ensure a secure fit.
2
2-In the same way offer up the next
piece of busbar inserting the
conductors into the joint connector
piece contacts ensure a secure fit.
3
3-Clip on the joint set cover piece
central to the joint.
4
4-Check that the joint cover is secure
and finish the mounting.
FL Busbar End Cap Mounting
1
1-FL Busbar End Cap.
2
3
2-Install the End Cap at the end of the 3-Make sure that the end cap is
busbar run by pushing the tags into
securely in position.
the busbar body moulding.
4
4-Complete the mounting of the end
cap using screws as shown above.
11
ELINEFL
FL BUSBAR MOUNTING
Bracket Set and FL Busbar Mounting
1
mm
00
7
0-
3
2
4
65
M6 Dowel
m
m
35
A
1-After determining the required
2-Insert the rawlplugs into the holes.
installation height for the FL busbar
drill two pairs of rawlplug holes for
each bracket at 35mm vertical centres
and 650-700mm horizontally.
5
5-Offer up the FL Busbar close to the
wall brackets.
9
3-Fix the wall brackets with screws as 4-Ensure that all of the wall brackets
shown above.
are correctly aligned.
8
7
6
6-First hook the lower clamps at the
7-Then hook the upper clamps at the
back of the busbar body onto the
back of the busbar body onto the top
sprung section of the wall bracket and of the wall bracket.
push upwards.
8-To complete the mounting of the FL
Busbar check that the clamps are
secure.
ON
10
OFF
OFF
ON
FL BUSBAR minimum offset return distance
is 20 cm. Order special modules by
submitting dimensions for off-set returns lower
than 20 cm.
9-Connect the internal and external
corners using the same method used
in fitting the connector piece and fix to
the wall using the rawlplugs and
screws.
12
10-Insert the FL socket into the
trunking and secure it by turning in the
specified direction.
Caution: The “ON” position must be
aligned to the top edge of the FL
Busbar.
ATTENTION: FL Busbar can be cut to length during
installation. A stand saw is recommended for this.
ELINEFL
FL BUSBAR AREA OF USAGE
FL
Workshops
Laboratories
13
ELINEFLD
OVERVIEW
Aesthetic, safe, practical and flexible structure eliminating cable mess.
E-LINE FLD Indoor Busbar Trunking Systems
FLD Data Busbar System;
- Offices
- Workshops
- Stores
- Hospitals
- Laboratories
- Airports
- Schools
Wherever power is needed without the need for additional cabling. Eliminates trailing cables and fixed sockets for low power
distribution.
E-LINE FLD Indoor Busbar Trunking Systems can be easily mounted on any structure or surface using brackets.
Also, when its compact structure is used with connectors, return modules and cable section, it offers a perfect structural cabling
infrastructure for data and phone requirements.
Specific power and UPS sockets can easily be installed with standard data, phone and TV sockets in modular structure. Stylish
and special UPS sockets with LED illumination and various colours can be installed in any position spot without the need for a
hand tool.
14
ELINEFLD
GENERAL SPECIFICATIONS
Power or UPS; 16A, 250V (protected)
FLD Data Busbar; 32A, 250V Operating voltage
IP2X Protection Class
Use of sockets in various colours for mains or UPS circuits
Single phase circuit (3 conductors); L+N+(PE) (65x28 mm))
FLD
Separate and compact section for structural cabling (Data&Phone)
Data, Phone, TV etc. socket mounting (without base)
Aesthetic, safe, practical and flexible structure
Easy and fast mounting
Standard length is 1m and 2m.
Standard colour is white (RAL 9003). Refer to page 17 for different colour and texture coating selections.
15
ELINEFLD
FLD DATA BUSBAR DESIGN and PRODUCT SELECTION
For design and product selection, select the numbered products and accessories shown below according to the layout of the
building as shown in the project example.
1
3
4
Feeder
Unit
End
Feeder
Unit
7
2
40
150
3
5
8
6
End Cap
Right.
1-FLD Data Busbar, Feeder Unit (32A, 250V, L/N/PE, 150x40mm)
FLD Data Busbar, End Feeder Unit (32A, 250V, L/N/PE, 150x40mm)
End Cap.
Left.
2-FLD Data Busbar (32A, 250V, L/N/PE, 150x40mx1000/2000m)
3-FLD Data Busbar, Internal Corner Kit (32A, 250V, L/N/PE, 150x40mm)
4-FLD Data Busbar, External Corner Kit (32A, 250V, L/N/PE, 150x40mm)
5-FLD Data Busbar, Joint Unit (150x40mm)
6-FLD Data Busbar Data Keystone Faceplate (22,5x45mm)
7-Busbar Data Keystone Faceplate, Straight Type, Angular Type (22,5x45mm)
8-FLD Data Busbar End Cap - Right/Left (150x40mm)
Component List
Serial
No
Description
1
2
3
4
FLD Data Busbar (32A, 250V, L/N/PE)
FLD Data Busbar Internal Corner Kit
FLD Data Busbar External Corner Kit
FLD Data Busbar, Loint Unit
5
6
7
8
FL Socket (16A, 250V, L/N/PE)
FLD Data Busbar End Cap; (Right)
FLD Data Busbar Feeder Unit
FLD Data Busbar Keystone Faceplate,
Straight Type, Angular Type
FLD Data Busbar Data Keystone Faceplate
Pcs.
Order
Code
9m
1 pc
1 pc
6 pcs
3050432
3050434
3050435
3048962
6 pcs
1 pc
1 pc
4 pcs
3048941
3050437
3048969
3050429
(32A, 250V, L/N/PE, 150x40mm)
9
Prepared by
Company:
AltındağMak
Project
Project No
4 pcs 3050417
: Edirne Facilities
: 0132
Name
: Furkan ALTINDAĞ
Date
: 16 / 07 / 2014
Signature
:
Project sample
16
ELINEFLD
FL DATA BUSBAR COLOURS and TEXTURE COATING
FLD Data Busbar's standard colour is white. However, colour selections below are produced according to the environment, walls
and floors when requested.
MAIN COLOURS
WHITE
RAL 9003
GREY
RAL 7040
LIGHT
BROWN
OAK
WALNUT
CHERRY
FLD
RAL 1001
FINISHING PATTERNS
BROWN
RAL 8004
SOCKET SURFACE FRAMES
They can be produced with or without LED in the colours
shown below when requested.
RED
BLUE
ORANGE
GREEN
There may be differences between colours and patterns in the catalogue and the actual product
17
ELINEFLD
FLD DATA BUSBAR PRODUCT ORDER CODES
FLD Data Busbar
Order Code
Product Description
White
Grey
Light
Brown
Brown
FLD Data Busbar 150x40x1000mm, PVC
3050432 3050422 3050438 3050411 3050734 3050767 3050800
FLD Data Busbar 150x40x2000mm, PVC
3050433 3050423 3050439 3050410 3050735 3050768 3050801
1000mm
150
9.5
38
44.8
51
150
40
65.6
20
40
Front View
Side View
2000mm
18
Oak Texture Walnut Tex- Cherry TexCoating
ture Coating ture Coating
ELINEFLD
FLD DATA BUSBAR PRODUCT ORDER CODES
FLD Data Busbar Feeder Unit (32A, 250V, L/N/PE, 150x40mm)
Order Code
Product Description
White
FLD Data Busbar, Feeder Unit
32A, 250V, L/N/PE, 150x40mm, PVC
Grey
Light
Brown
Brown
Oak Texture Walnut Tex- Cherry TexCoating
ture Coating ture Coating
3048969 3050420 3062953 3050448 3062955 3062957 3062959
150
Front View
40
158
Top View
FLD Data Busbar, End Feeder Unit (32A, 250V, L/N/PE, 150x40mm)
Order Code
White
FLD Data Busbar, End Feeder Unit
32A, 250V, L/N/PE, 150x40mm, PVC
Grey
Light
Brown
Brown
Oak Texture Walnut Tex- Cherry TexCoating
ture Coating ture Coating
3050406 3050446 3062954 3062952 3062956 3062958 3062960
FLD
Product Description
150
Front View
40
158
Top View
19
ELINEFLD
FLD DATA BUSBAR PRODUCT ORDER CODES
FLD Data Busbar, Internal Corner Kit (32A, 250V, L/N/PE, 150x40mm)
Order Code
Product Description
White
FLD Data Busbar, Internal Corner Kit
32A, 250V, L/N/PE, 150x40mm, PVC
Grey
Light
Brown
Brown
Oak Texture Walnut Tex- Cherry TexCoating
ture Coating ture Coating
3050434 3050424 3050440 3050412 3050736 3050769 3050802
42
155
116
42
116
Top View
Side View
FLD Data Busbar, External Corner Kit (32A, 250V, L/N/PE, 150x40mm)
Order Code
Product Description
White
FLD Data Busbar, External Corner Kit
32A, 250V, L/N/PE, 150x40mm, PVC
Grey
Light
Brown
Brown
Oak Texture Walnut Tex- Cherry TexCoating
ture Coating ture Coating
3050435 3050425 3050441 3050413 3050737 3050770 3050803
42
154
108.5
42
111.4
Top View
Side View
FLD Busbar Joint Unit (32A, 250V, L/N/PE, 150x40mm)
Order Code
Product Description
White
FLD Data Busbar, Joint Unit
32A, 250V, L/N/PE, 150x40mm, PVC
42.5
155
30
Top View
20
Side View
Grey
Light
Brown
Brown
Oak Texture Walnut Tex- Cherry TexCoating
ture Coating ture Coating
3050436 3050426 3050442 3050414 3050738 3050771 3050804
ELINEFLD
FLD DATA BUSBAR PRODUCT ORDER CODES
FLD Data Busbar End Cap - Right (150x40mm)
Order Code
Product Description
White
FLD Data Busbar End Cap - Right
150x40mm, PVC
Grey
Light
Brown
Brown
Oak Texture Walnut Tex- Cherry TexCoating
ture Coating ture Coating
3050437 3050427 3050443 3050415 3050739 3050772 3050805
150
40
32
23
30
Top View
Side View
FLD Data Busbar End Cap - Left (150x40mm)
Order Code
White
FLD Data Busbar End Cap - Left
150x40mm, PVC
Grey
Light
Brown
Brown
Oak Texture Walnut Tex- Cherry TexCoating
ture Coating ture Coating
3050418 3050428 3050444 3050416 3050740 3050773 3050806
FLD
Product Description
150
40
32
23
30
Top View
Side View
21
ELINEFLD
FLD DATA BUSBAR PRODUCT ORDER CODES
FLD Data Busbar Data Keystone Faceplate, Straight Type(22,5x45mm)
Order Code
Product Description
FLD Data Busbar, Data Keystone Faceplate,
Straight Type, 22,5x45mm
3050417
36
45
23
Front View
Top View
FLD Data Busbar Data Keystone Faceplate, Angular Type(22,5x45mm)
Order Code
Product Description
White
FLD Data Busbar, Data Keystone Faceplate,
Angular Type, 22,5x45mm
25
Front View
22
45
53
40
Top View
Grey
Light
Brown
Brown
Oak Texture Walnut Tex- Cherry TexCoating
ture Coating ture Coating
3050429 3050703 3050705 3050704 3050741 3050774 3050807
ELINEFLD
FLD DATA BUSBAR MOUNTING
1
2
3
4
A
A
5
5-Secure FLD Data Busbar on
the wall using appropriate
washer and screw.
9
9-Clip on the joint cover piece
central to the joint.
13
2-Check the horizontal level using a
spirit level and mark the location of
the rawlplug holes using a length of
FLD Data Busbar.
6
3-Drill the marked positions
using a hand drill and M6 bit.
7
7-At corner locations, place the FLD
6-Place FL Busbar in the
trunking securing the clamps in Data Busbar internal and external
corner units installation.
their places.
10
11
4-Place M6 rawlplugs in the
holes that are drilled.
8
8-At corner locations, install the FLD
Data Busbar FLD Data Busbar internal
and external corner unit covers
securing the clamps in their places.
12
10-Install FLD Data Busbar end 11-Mark areas on FLD Data
12-Extend Data and Phone
cap termination units securing Busbar where Data and Phone cables through these cut
socket will be installed and
them in the clamps.
sections approximately 50cm.
neatly cut the cover.
14
15
FLD
1-Determine the required
mounting height of FLD Data
Busbar and mark the position.
M6 Dowel
16
14-Place FLD Data Busbar
13-Have a qualified technician
15-Push FLD Data Busbar cover 16-Make sure FLD Data Busbar
Data&Phone Socket Base on the and tighten socket base.
drive the cables to RJ45 data
and all its accessories are
sockets and place the RJ45 data trunking.
complete and finish mounting.
sockets with the cables driven
on FLD Data Busbar Data &
Phone socket base.
FLD DATA BUSBAR minimum offset return distance is 20 cm. Order special
modules by submitting dimensions for off-set returns lower than 20 cm.
Caution: FLD Data Busbar and Cover can be cut during mounting; a stand saw is recommended for this.
23
ELINEFL/FLD
FL / FLD BUSBAR AREA OF USAGE
Airports and general spaces
90°
Hospitals
24
ELINEFL/FLD
FL / FLD BUSBAR AREA OF USAGE
Schools and courses
On
90°
90°
Off
Electronics stores
25
ELINEFL/FLD
GENERAL PRODUCT SPECIFICATION
FL BUSBAR and FLD DATA BUSBAR (32A) SYSTEM
GENERAL PRODUCT SPECIFICATIONS
FL and FLD Busbar;
1- Are manufactured according to IEC 61439-1,6 and IEC 61534-1 standards and sockets to be used in this system are manufactured according to IEC
60884-1 standard. Products have “type test” certificate from international test laboratories for 32A current level.
2- Indoor busbar trunking system and sockets to be used in this system are manufactured in facilities with ISO 9001 quality management system and ISO
14001 environment management system.
3- Nominal insulation voltage is 415 V.
4- Conductors are manufactured from tin plated electrolytic copper and tin with 32A current carrying capacity.
5- They are manufactured with 3 conductors, phase, neutral and earth (L/N/PE) structure.
6- They are manufactured in 1m and 2m standard lengths.
7- They are mounted on the wall with spring type special mounting brackets and they can also be installed in click-fit style in a special PVC data trunking
offering structural cabling (data and phone) ability suitable for physical structure and dimensions when requested.
8- Supply connectors, internal and external corner units used in Busbar trunking and data trunking are manufactured with same specifications and in the
same compact structure.
9- Connector member has tulip contact, click-fit structure connecting conductors on both sides. Contacts are silver coated and joints are covered with a
separate plate in compact structure.
10- Special power sockets of Busbar trunking system (Mains and/or UPS) are 32 A and 250 V and they can be mounted or dismounted to any place on the
indoor busbar trunking system. Thanks to its special lock mechanism and clamping structure, the cable is protected from coming off when it is plugged
and they are manufactured in different colors.
11- Protection class is IP 2XB at least and it is protected against finger contact. There is a dust protector on the entire power reception trunking on the
system and a special curtain with a rigid structure. This curtain has a flexible structure and it has resistance to -40/+80 °C operation temperature and
pressure.
The section it is placed on the profile is hard and the other end is soft.
12- Busbar and data trunking are manufactured in different colors with RAL codes suitable for the environment when requested.
13- Busbar and data trunking are manufactured from PVC material in accordance with ROSH and REACH standards.
14- Busbar trunking cross section has two internal walls and there are tie pieces between inner and outer walls.
15- There are no manufacturing defects such as foreign objects, gaps, pores, cracks, continuous scratches in Busbar trunking profile.
16- It has flame retardant characteristics and manufactured in UL94 standard and V2 class at minimum.
17- It is manufactured with resistance to -5/+40 °C ambient temperature.
18- It is subjected to “Hot wire test” and can resist 960 °C heat according to the test results.
19- It is subjected to “Impact test” and it is in IK 07 class.
20- Lengthwise change of busbar trunking profiles that are subjected to 100°C for 1 hour is calculated and tested. According to test results, deflection is no
more than 2%.
21- Busbar trunking profiles are subjected to 120 °C for 30 minutes. Their surfaces are checked after they cooled down in room temperature and no grains,
peeling or surface defects were not observed.
22- Busbar trunking profile hardness is 77 (± 2) Shore D.
23- Lengthwise deflection on Busbar trunking profile is 1 mm/m maximum.
24- They are manufactured in accordance with “weight loading test” conditions stated in IEC 61439-1.
25- They are manufactured in accordance with “weight loading test” conditions stated in IEC 61439-1.
26- It is covered in protective film to prevent contamination before field mounting.
27- They are manufactured from unleaded raw material.
26
ELINEFL/FLD
Declaration
CE DECLARATION OF CONFORMITY
Product Line
E-LINE FL/FLD Indoor Busbar Trunking Systems
Manufacturer
EAE Elektrik Asansör End. İnşaat San. ve Tic. A.Ş.
Akçaburgaz Mahallesi, 119. Sokak,
No:10 34510
Esenyurt-İstanbul
We confirm that products or product group mentioned above manufactured in EAE Facilities conform to
standards and regulations listed below.
Standard :
IEC 61439-6
IEC 61534-1
IEC 60884-1
Low voltage switching and control gear equipment - Part 6: Equipment for power
distribution in general mains.
CE - Regulation
2006/95/AT “Regulation on electrical equipment” to be used in certain voltage limits”
Date
EAE Elektrik A.Ş.
17.11.2014
EAE Elektrik Asansör End. İnşaat San. ve Tic. A.Ş.
Akçaburgaz Mahallesi, 119. Sokak, No:10 34510 Esenyurt-İstanbul
Tel: +90 (212) 866 20 00
Fax: +90 (212) 886 24 20
http://www.eae.com.tr
27
ELINEFL
CERTIFICATE
28
S
IT
AL
ISO
9001
14001
MENT SYSTE
M
Y A N D EN V
MENTAL MAN
ON
E
AG
QU
IEC 61439-6
IEC 61534-1
IEC 60884-1
IR
EAE Elektrik A.S.
Akcaburgaz Mahallesi,
119. Sokak, No:10 34510
Esenyurt-Istanbul
Tel: +90 (212) 866 20 00
Fax: +90 (212) 886 24 20
www.eae.com.tr
Catalogue 24-Eng. / Rev 01 1.000 Ad. 23/02/2015
ATA LTD. / G.M./ 612 40 66
We reserve the right to make any kind of change in values given in the catalogue.
S
IT
AL
ISO
9001
14001
MENT SYSTE
M
Y A N D EN V
MENTAL MAN
ON
E
AG
QU
IEC 61439-6
IEC 61534-1
IEC 60884-1
IR
EAE Elektrik A.Ş.
Akcaburgaz Mahallesi,
119. Sokak, No:10 34510
Esenyurt-Istanbul
Tel: 0 (212) 866 20 00
Fax: 0 (212) 886 24 20
www.eae.com.tr
Catalogue 24-Tr. / Rev 00 1.000 Ad. 10/02/2015
ATA LTD. / G.M./ 612 40 66
We reserve the right to make any kind of change in values given in the catalogue.

Similar documents