INSTRUCTION FOR UNILET SEALING FITTINGS APPROVED FOR
Transcription
INSTRUCTION FOR UNILET SEALING FITTINGS APPROVED FOR
INSTRUCTION FOR UNILET SEALING FITTINGS APPROVED FOR USE WITH: APPLETON. wiko® A AND CROUSE-HINDS Chico® A SEALING CEMENT • The National Electrical Code in ArtJcle 50 1 Section 501.15 Class I. Division 1 and 2, requires that seals be installed in spec c locations. This is to prevent the passage of gases, vapors or flames th rough the conduit from one portion of the electricalmsta lion to another portion . • Appleton sealillg unilers are UL listed for use in hazardous locations with Appleton Kwiko A compound or Crouse Hinds Chico A compound onI These compounds, when properly mixed and poured, hardens into a dense and strong mass which is insoluble in water, i not a ed by petroleum products and is not softened by heal • The fOllowing sealing ~ series are UL listed for use with Appleton Kwiko A or Chiro A sealing co pounds: EYF, EYF-AL, EYM EYM·AL EYDM EYDM-AL, EYD, EYS, EYSF, EYSF-AL, EYSM, EYSM-AL, ESUF, ESUM WARNING: Failure to follow safety instructions may cause ignition of hazardous atmosphere resulting in serious personal injury and I or property damage. STEP 1 Install unilet and pull conductors through . • Remove plug(s) from sealing fitting and use fiber fille r to make dam (5) In hub(s). STEP 2. ,D APPLETON Kwiko A and CROUSE-HINDS Chico A CEMENT FOR GROUPS C AND D APPLICATIONS: Sealing com pound to be mixed ONLY at temperatures above 35° F (1.7° C) and ONLY po red into fittings that have been brought to a temperature above 35° F (1.7° C) . Seals must NOT be exposed to temperatures below 35° F (1 .7° C) for a least 8 hours . Compou nd must be allowed 8 hou rs to cu re to full strength before energizing system. FOR GROUPS A AND 8 APPL CATlO S: e3 I G:-~ ... CAUTION: TEMPERATURE/CURE TIME :::t condu tors and around each conductor. • These conductors must not touch eac other nor the sealin g fitting wall • Clean fiber shreds away from wa ll s 01· conductors to prevent them from causing flame and / or leakage of gases . Finish ed dam must be flush with conduit hub bushing. "A s b e s t 0 s Free" Seali ng r------C-A-U-T-I-O-N------, Cement Be sure to read the Refer to Table 1 to determine the mixing in stru c- maximum number and size of con tions on Sealing ductors allowed in a seal. (Page 4) cement can . STEP 3. Mlx.ing: Prepa,re se ling com pound using a completely clean mixing vessel in eac h batch . Sha e th e seali ng cement thoroughly in all di rections. Mix seahng cem ent wittl correct proportion of clean water a noted below. ) a'l lLV poure Into Ittlngs Itlal na e be€: ;"~ : a temperature above 40° F (4.4° C). Seals must NOT bi; exposed to temperature below 40° F (4 .40 C) for a least 72 hours . Compou nd must be allowed 72 hours to cure to full strength befo re energizing system . STEP 4 VERTICAL CONDUIT RUN. Po r seali ng cement mixture into the smal l pipe opening until the cement is level wi th the last thread of the opening. Replace and tigilten small pipe plug. HORIZONTAL CONDUIT RUN. Pour sealin g cem ent mixture 'OJgi" the large opening until two (2) to three into the Unl e 13) threads are .ered With the cement • Replace a a : _ .en In sequence the arge pipe pl ug or cover the small p pe p _ to t e unilet and the small pipe plug Into the cover. Damming and Pourmg: APPLETON Kwiko A and CROUSE-HINDS Chico A CEMENT. Add one (1) part water to two (2) parts ce ment by volume. Use Gold water, warm wa er increases setting speed. Add water and stir immediately and thorough ly. • DO NOT mix more than c n be poured in 15 minutes after adding water. • These cemen ts are NOT INSULATING COMPOUNDS and MUST NOT be used for such purposes. VERTICAL CONDUIT EGS Electrical Group · ww.appletonelec.com· 800.621.1506 HORIZONTAL CONDUIT Rev. "H " 07/01 /09 SEALING UNILETS EXPLOSION PROOF, DUST IGNITION PROOF FOR USE IN VERTIC lOR HORIZO TAL C UIT R EYS, EYF AND EYM SERIES 1/211 TO 6 11 - COfIOlln tile Caller shOuld be lighten8li down with th small pipe plug ro?rna.oed lrem iL This will allow excess eamen l or air to escape out rath81 Ihan seep'llg Ihrough or puShi ng th e dam into the ondult. When the large cover has been tightened fully. replace pipe plug . Vertical conduit 1. Install Unllet and pull conductors through . 2. Remove the pipe plug where the cement will be poured through and the large pipe plug or cover with the small pipe plug for size 3-1/2"-6" at the center of the Unilet 3. Dam the lower hub with fiber filler. (Page 1, Steps 1 & 2.) 4. Replace the large pipe plug or cover with the small pipe plug for 3-1/2" thru 6" and tighten aJl threaded joints securely. 5. Mix Sealing Cement with the correct proportIon of water per Instructions prOVided with the cement. (Page 1, Step 3) 6. Pour Sealing Cement mixture inlo the small pipe plug opening until the cement is level with the last thread of the 6. Pour Sealing Cement mixture Into the flang ed cover ooenlng n the cement level IS equal to the last thread of he opening 7. Replace and tighten the small pipe plug . Horizontal Conduit 1. Install Unllet and pull conductors through . 2. Remove the flanged cover. 3. Dam both hub openings with fiber filler (Page 1. Steps 1 & 2). 4. MIx Sealing Cement with the correct proportion of water _. per instructions provided with the cement. (Page 1, Step 3). 5. Pour Sealing Cement mixture into tile Unilet opening until the cement level is equal to the bottom of the cover mount ing flange. Fi ll hole must be oriented in the upright position, 6. Replace the flanged cover, tighten the small pipe plug. EYD AND EYDM SERIES 1/211 TO 111 DRAIN AND SEALING UNILETS EXPLOSION-PROOF, DUST-IGNmON-PROOF FOR USE IN VERTICAL CONDUrT RUNS SEAUNG COMPOUNIJ Horizontal conduit 1. Install Unilet and pull conductors through . 2. Remove all pipe plugs and / or cover from the Unilet. 3. Dam both hubs with fiber filler (Page 1, Steps 1 & 2) 4. Mix Sealing Cement with the correct proportion of water per instructions provided with the cement. (Page 1. Step 3 . 5. Pour Sealing Cement mixture into the Unilel through the large opening until 2-3 threads are covered with the cement. Fill hole must be oriented In the upright position. 6. Replace and tighten in sequence th large pipe plug or cover, the small pipe plug into the Unllet and the small pipe plug Into the cover. ESUF AND ESUM SERIES 1/2" TO 111 \IlRTlCAl CONOUlT Vertical Conduit 1. Install Unilet and pull conduc to rs through . 2. Remove fl anged cover and the pipe plug from the Unilet. 3. Dam tile lower hub opening with fiber filler (Page 1, Steps 1 & 2). 4. Replace the flanged cover. 5. Mix Sealing Cement with the correct proportion of water per instru cti ons provided w i h til e cement (Page 1, Step 3). HORIZONTAL coNOtm EGS Electrical Group • www.appletonelec.com • 800.621.1506 AFTER POURING SEALING CEMENT READy FOR USE 1. Install Unilet and pull conductors through. 2. Remove the pipe plug. 3. Dam the lower hub opening Wlth fiber filler (See page 1. Steps 1 and 2) 4. Insert rubber drain-hoi core through drain opening and washer (provided) high enough so inner end of core will-be above sealing compound in completed seal. Note: Washer (provided) must be inserted to last thread to form dam for sealing compound. 5. Be sure that the rubb er drain - hole - core does not touch any of the conductors . 6. Mix Sealing Cement with the correct proportion of water per instructions provided with the cement (Page. 1 Step 3.). 7. Pour Sealing Cement mi ture into the Unil et openin g until the cement is level with the last thread of the opening. 8. Replace and tighten pipe plug. 9. When c e m e nt has cure d (see p age 1."Ca ution : Temperature / Cure Time") remove drain - hole - core. 10. Thread ECDB drain - breather fitling into threaded hole and lighten securely. 500395-1 Rev. "H OJ 07/01/09 Page 3 SEALING UNILETS, EXPLOSION-PROOF, DUST-IGNITION-PROOF FOR USE IN VERTICAL CO UIT RU S. EYSF AND EYSM SERIES 1/211 TO 411 EYS 1/211 TO 1" SEALING COMPOUND 1. Install Unllel and pull conductors through, 2. Remove the large pipe plug T ighten the small pipe plug on side of 3 and 4" Unilet sizes . 3. Dam U1e lower hub openrng with Rbe r Rller (Page 1, Steps 1 & 2) 4. Mix sealing cement with the correct proportIOn of water per instructions provided with the cement (Page 1. Step "3). 5. Pour Sealing Cement mixture into the Unilet openi ng until the cement is level with the last thread. 6. Replace and tighten pipe plug. EYD SERIES 1-1/411 TO 411 EYDM SERIES 1-1/4" TO 4" DRAIN TUBE 1. Install Un' at a . p co ductors through. 2. Remo e t e large nreaded co sr from e Un e . 3. Dam rye lower b ope ng ber rller. (Page 1 S ep 2 , 4. Replace the large . eaded er so t a e '<;loaded e IS faCing downward. 5, Insert the tube and wire drain core illto the operuog of the large threaded cover so that the end being Inserted will be above the compound in a completed seal. (See illustration above) . 6. Be sure that the tube and wire drain core do not touch any of the cond C ors 01 en.\ se hIS ," e).J)OSB the cord or.; In the completed and hardef'led seal (See illustration above) 7. MIX Seali ng Cement with the correct proportIon 0' water per instructions provided with the cement. (Page 1, Step 3). 8. Pou r Seali ng Cem ent mixtu re mto the Unilet through the ope ning located above the large cover until the las1 thread is covered with cement. 9. After cement has cured, (See page 1, "Caution: Temperature / Cure Time ") pull out the old tube and wire drain core and discard. 10. Thread the small pipe plug into this opening and tighten . 11. Thread EC DB drai n-breath er fitting into large cover t readed hole and tighten secure. Page 2 500395-1 Rev. "H" 07/01/09 EGS Electrical Group • www.appletonelec.com • 800.621.1 506 THE MAXIMUM NUMBER OF CONDUCTORS THAT CAN BE SEALED IN A SEALfNG FITING TABLE 1 Example On How To Use Table 1 • The maximu m number of No.4 Type THHN Conductors (Col umn 8 ) in a 1· 1/2" size sealing 11 1I111t) I' • The six (6) No. 4 THHN conductors rep r~ se nt the maximum wire fill of 25% or loss for sealing 1i1l1l1q • Increasing the sealing fitting to a 2" trade size will provide space for the 40'%, wire fill, or nine (9) NO. 4 conductors. • ITrade Size The M aximum number of wires that can be sealed in a fitting arc as rollows: 1-1'2' CondUCI~" Type Max No. PennlHed For 25%Fill Max No, For 40~. RlllTrndB Size Se alin~ AUinlLNOOdild _ Na 4 THHN (Col B) 6 (9 12"i SilO p. erml!l~ In our example, lise an EYM I EYF200 for 2" size EYSF I ESUM, EYD, EYDM, - lib AWOli' Ifl'SeaI IIIIYM'TSIzel A 8 7 11 " 6 9 1. S 8113""') 6 20 16 151241 1'1 12 3 6(10'1") 5 ll na' n 10 B 6 4 1I2..;J14'] I I I 416'1., 213';1·, 1 I 4 2 I 1 " 8 12 10 18 16 1"Seal ftlNhII Slzel 8 Jl4" SeaI IIIIYItl'T SlzeI 7111/ 1") 4(fo1n 2jr\1 Ii li2' 1"1 ~ ... 35 B 58 1-112" Seal 1"SooI 2-IR"ScIII IOIvItl'T Slzel A 8 4!l !11 IOtvlN'l Slzel J\h1tl'T Slzei ... 8 A B J1'J 1:l1 II ~ II!1 151 :Il ~7 I~ ICII 18 43iW2"l 41 25 "'I 24 r:fJi l '/.1 18 12'l' 1'/<' '! >aliW ?'I ,II '~"illW 3") 111 'CI 15 32(511 2, 21 43(7012') 711114/3") II 7 II 13 1 tI&' 1"., 6(!1' 1v.., 17 10· aI!!' 33 'll 1-114" Seal IIIIYItl'TSimI 1 /., ' 2 1 4{& "I., 2\411'1,-, ".1".' r.L"J·J 'I,'l 2Oi32I2; 17(1!I' 2"1 :'II 27 1'141 .1 m Ut' 111..11 ,1J17l'3'1 'II ~'h') ,', 3"SeaI JtlIy/I4'TSlzeI A 8 111i 4'SoIj 5" Seal ~'9Id 11lv~,fIr SII>lI ,OIvItl'TSlzuI B A !QIY~r~ A 8 3-112" Seal 1D!1I1tI'TSllf:1 8 A A 00 121 tit 7ij 103 1~. II 150 I (T1IJ..IITI 104 1(01161)'4"1 'f! 1.1' 1111 11'2 :0 56mw41 17 11I11""~' 1 tJ.I 1000:1'> '$:,r,/.'·'j JJ 41 [lIUi"! 41 173 1(~lil',~i 7 1'''' 411>' ~ 11 9 la ~r.·1 :r') 7111/21 HII 11 2!j IfJ ..1 rt' ~'hl llfil l'lJi G S ItO! I 10 ~~" J 1111 ~'i' ft 0(17'1 1(,'-&3'1 1:1 T, P\1fi13") .1/ ~IV J'l 94 157 13'T 61$'6'1 &1 £6 93 III ~'1 n 7J Cf/;l'''\ ~t'3'h') 11 Til ~1rr.'4 1 :!.4 ~ICTI ~") 31 37~6') 4gcn 61 $ 7? ~ Itl 1"~' 4") ~117.7I ~'1 ",4Ql'5"l 2!! 31 (51161 44 !Il ():" n ,1'i H ,~"" 4'1 1til llifIlI , ,, 24 3>(4:\' 6"1 3Ij 42 5.', 61 10 11 (1Il1'q 14 151;!;'~' 1~ 2IICJ?1 t.) 2) 31 ¢2 -\,1 11 11 nC'11',' 'Ii 'firm ~I 14 1'1 1:'7- II '1,1>\1 ~1 Ii lc'lll\.1["·1 8 11 5 ijl l ~11 !j+l IU IIln~ ~-j h, 11W ~-J " ~1121 ~, 19 16 13 37 32 'lJ :>:! 19 7!11! 1"1 II 2!! Z! 19 6 13 11 >4 11 ' I/' ~t'l 25 22 Ie 16 6i\¥ Iii 10 9 10(15' 61 gill' 61 1~! 13 15 a 8111161 6$1 Iii 61&' 61 5171 In " II C\ ~ H 8 7 S ~)'l""-I 3 1 J 1 2r;111 1141 3 311>21 ,I r Sf'>' r'I U(llo 3") II I 12 II" ' ~'I·' 2 1 I I I 1 I I lil' 1 '~', 1 l I 31:" I 2i3' 1'hl 3(4/ 2'i 3 ;; 4\71 C) 3iS! 2'1 '1I!V ~'JJ'I 111Tt:! 10 " , ""~:I"I 1' ~l'~'J 711:111'11' I h "tUI" !H'tj ., 'III, ~") I' ~r\'!"\ I ~i1,I' ,I, !Il'l - I ,~ lID 1 1 1 1 1 2m 3/D 4ID 250 :m :fill 400 !DI 1m 100 750 IDI 9W 1111l 1l!il 1!D1 1750 2IJl) • COL A I 1 I 1 1 I I 2!Y2"l l r211 W'1 1 1 I I t 1 I I 1 1 ,11/1 :n \U·31 2 I I I 1 210\1 2"1 I I I , 1 1 1 ?11 "1 1,2 ,,'1 1 lj:\' I I I 2(.l1 ~ 11312"1 , ' 1212' I 1 1 , •:n r!\l 3j .14 ;r') 3(oV ~'l-· 21h1 I ,1{7ll1.1 ~hl ~~ .~~ H'~ :, 2W~ ,I, lllV 41 ~rrr .1 ~ I '1~, 4"1 ~it"-Ir,., ~I'" 1! 1 ~ 3f 41 I 1(411"1 11;':,1:"1 1(l' 3'1.) I T[II' L I 1 I il'J J) I rL~ ::-1 1I11'.In. I 1 1 i ~'.' ,. ,i , 1 1 n'll3'", I I 1 ! I Ii?l3'JoIj I I 1 I I I I I 1 1 1 I I , _ .... =Wire Types : RFH-2 , RH, RHH, THW. TH, XHHW (AWG 14-6). COL B = FEP, THH N, THWN , TFN, PF, PGFF XHHW (AWG4-2000 MCM), FE IJBV (AWG 14-8). 1 I ~ ~151 f. ~171 ~-I 4 ~1lV ~, , 41'14', 1 , I I 1 3 2 2 1 I I I I I 1 I I 1 1 1 1 I 6 6 5 4 3 3 3 3 3 I I ' I I I I I I I I ,1 3 3 1 314'4'1 3",,5"1 ,1 61l>' bl 5fl151 4,;,r S") 6 3~51 6 3W J 5 5 ~1 3 .\ E 4 3 4 4 2 3 l 2 I 1 I I :\2 'll r. 19 13 8 7 7 7 6 l ti S 'I " 4 4 3 4 2 1 ~ J NOTE: for ., 11 f'J II Hilr conductor sizes and types, wire fill Is based on maxim um 40~Q ril l or less depl'"1t11l1) on conduit size and condUctor type per tile NEC Code . • For all ullwr conductor sizes and types, wire fi ll is based on maximum 25% fill or less I