Technical Guideline
Transcription
Technical Guideline
Technical Guideline A. Description 1. Definition and scope ISM Sismo is a permanent insulating shuttering kit for whole buildings (walls including basement walls, floors, roofs and their connections), to be filled on site with concrete (reinforced or not). The ISM Sismo module is composed of a tridimensional lattice made of galvanized steel wire, which is closed on both sides, inside and outside, with strips of insulating or non-insulating material. Alternatively, insulating panels can be added and fixed to the side of the module. (see figures 1 to 19) The choice for a certain type of module will depend on the required properties of the finished wall or floor as there are structural, thermal, hygrothermal, acoustic performance, fire resistance and reaction to fire. The shuttering kit is manufactured in the ISM Sism Production Station according to the specific requirements and assembled on the construction site. If applicable the necessary reinforcement to withstand the load to which the final ISM Sismo wall or floor will be subjected, are inserted in the tridimensional frame. Next the concrete is poured in the free space between the insulating strips. The stability of the final ISM Sismo wall is entirely assured by the concrete. The steel wire lattice and infill strips only provide stability during the provisional phase of pouring and maintaining fresh concrete. Furthermore the lattice acts as an armature and as an anchoring for the cladding or rendering. 2. Operating method Projects can either be directly designed in the ISM Sismo property software sisCAD™ or architectural drawings can be converted into production and site drawings using sisCAD™. The ISM Sismo layout plan is checked and approved by the customer before production After manufacturing, ISM Sismo modules and accessories are transported to and unloaded on the building site, keeping in mind to limit stress on the modules during handling. The acceptance of the goods is done at the delivery on site by the customer or his representative by checking the quality and quantities and their correspondence with the order. Assistance and technical training is carried out by technicians who master the ISM Sismo process. They train the customer or his subcontractor in all aspects related to the mounting of the ISM Sismo modules. 3. Material characteristics 3.1. Steel wire Hot galvanized steel wire. The Ø of the wires and the rings: 2,2 ± 0,03 mm The tensile strength of the wire: 680 - 830 N/mm², according to EN 10002-1 The identification of the steel wire: Type 1.0304 or C9D according EN 10016-1. Page 1 of 39 Chemical composition: C9D : C ≤ 0,10 % ; Mn ≤ 0.3 % ; Si ≤ 0,6 % ; P : 0.035 % max ; S : 0.035 % max. ; Cr : 0.25% max. ; Ni : 0.25% max. ; Mo : 0.08% max. ; Cu : 0.3 % max. Stainless steel: 1.4310 or X10CrNi18-8 austenitic steel according to EN 10088-1. Galvanization according to EN 10244 part 1 and 2: class D and the rendering cover of the wires is at least 5 mm. The shear strength of the welding: rupture > 1400 N (ISO 10287) When the concrete is hardened, the durability of the steel wire is necessary only in those applications where the adhesion of the finishing depend on it (in addition to the adhesion between concrete and insulation and between insulation and the rendering). Tolerances on the dimensions of the modules: ± 0,2 cm on the width, ± 0,5 cm on the height and ± 0.1 cm on the thickness of the modules. 3.2. Rings Rings are used to hold the panels together during installation phase, casting and curing of concrete, see figure 1. 3.3. Insulation strips and panels Expanded polystyrene (EPS): EN 13163 “Thermal insulation products for buildings - Factory made products of expanded polystyrene – Specification” Fiber cement board (FCB): EN 12467 “Fiber-cement flat sheets - Product specification and test methods.” Mineral wool (MW): EN 13162 “Thermal insulation products for buildings - Factory made mineral wool products – Specification” Wood based hardboard (HDF): EN 13986 : “Wood-based panels for use in construction Characteristics, evaluation of conformity and marking”; EN 622-1: “Fibreboards, Specifications - Part 1 General requirements”; EN 622-2 : “Fibreboards, Specifications - Part 2 Requirements for hardboards” Cardboard (CB): ASTM D 828 “Standard test method for tensile properties of paper and paperboard using constant-rate-of-elongation apparatus”; ASTM D 829 “Standard test methods for wet tensile breaking strength of paper and paper products”; EN ISO 534: “Paper and board - Determination of thickness, density and specific volume”; ISO 535: “Paper and board - Determination of water absorptiveness -- Cobb method”; EN ISO 12625-4: “Tissue paper and tissue products. Determination of tensile strength, stretch at break and tensile energy absorption”; EN ISO 12625-5: “Tissue paper and tissue products. Determination of wet tensile strength”. Minimum requirements can be found in tables 1 and 2. Table 1 Characteristics insulation strips Material characteristics Expanded polystyrene (EPS) Fiber cement board (FCB) Mineral wool (MW) Wood based hardboard (HDF) type HB.E Cardboard (CB) Dimensions : length x width x thickness (cm) 120,0 x 14,8 x 3,8 or 7,8 or 11,8 or 15.8 or 19.8 120,0 x 14,8 x 0,3 120,0 x 14,8 x 3,8 or 7,8 120,0 cm x 14,8 cm x 0,32 cm 120,0 x 14,8 x 0.52 Page 2 of 39 Tolerance (EN Tolerance: Tolerance (EN 822, EN 823) : l, w and t : -0.1 to + 0 cm 822, EN 823) : l, Tolerance (EN w and t : -0.1 to + 324-1) : l, w 0 cm and t: - 0,1 to + 0 cm l, w and t : - 0,1 to + 0 cm Squareness ≤ 3 mm / 500 mm (EN 824) ≤ 3 mm / 500 mm (EN 824) ≤ 3 mm / 500 mm (EN 3242) ≤ 3 mm / 500 mm Apparent density (kg/m³) Walls ≥ 20 to ≤ 30 / Floors ≥ 15 (EN 1602) 1300 (EN 12467) ≥ 100 (EN 1602) ≥ 800 (EN 323) ≥ 200 Compression strength (10% deformation) (N/mm²) Walls ≥ 0,1 / Floors ≥ 0,06 (EN 826) No performance determined (NPD) 0,02 (thickness< 50 mm) 0,04 (thickness ≥ 50 mm) (EN 826) NPD NPD Resistance to penetration of steel wires Passes Passes Passes Passes Passes Bending strength (N/mm²) Walls ≥ 0,15 / Floors ≥ 0.1 (EN 12089) 13 (EN 12467) ≥ 0,15 (EN 12089) ≥ 40 (EN 310) ≥ 0,10 Tensile strength (10% deformation) – Internal bond ≥ 0,080 (EN 1607) ≥ 0,080 (EN 1607) ≥ 0,700 (EN 319) ≥ 0,4 (ASTM D 829) Reaction to fire (Euroclass) E (EN 13501-1) A2-s2, d0 (EN 13501-1) A1 (EN 13501-1) NPD NPD Thermal conductivity (W/mK) (λ) Walls ≤ 0.033 / Floors ≤ 0.038 0,16 ≤ 0,045 (EN 12667) ≤ 0,14 (EN 12524) ≤ 0,14 Water vapour diffusion resistance index µ 30 to 70 ≤ 80 (EN 12572) ≈ 1,3 (EN 12524 or EN 12086) 10 (EN 12524 or EN 12086) NPD Water absorption ≤ 1,5% (EN 12087) ≤ 1,5% (EN 12087) 300 g/m² (EN 382-2) ≈ 1500 g/m² Dimensional stability ≤ 0,5 % (EN 1604) ≤ 0,5 % (EN 1604) 0.25 l. and 0.1 t (EN 318) NPD Swelling Not relevant ≤ 12% (EN 317) NPD NPD Length of strips varies from 20.5 cm till 120 cm in multiples of 10 cm so that they can be supported on both ends by 2D-lattices. Distance between 2 outer 2D-lattices of a standard module varies from 119.5 cm to 119.7 cm Table 2 Characteristics insulation panels Plus and interjoists Material characteristics Expanded polystyrene (EPS) Dimensions : length x width x Panels 120 x 45 x 4 or 8 or 12 or 16 or 20 / Interjoists 120 x 45 Page 3 of 39 thickness (cm) x 10 or 15 or 20 (EN 822, EN 823) Squareness ≤ 3 mm / 500 mm (EN 824) Apparent density (kg/m³) Panels ≥ 20 à ≤ 30 / Interjoists ≥ 15 (EN 1602) Compression strength (10% deformation) (N/mm²) Panels ≥ 0,1 / Interjoists ≥ 0,06 (EN 826) Resistance to penetration of steel wires Passes Bending strength (N/mm²) Panels ≥ 0,15 / Interjoists ≥ 0,1 (EN 12089) Tensile strength (10% deformation) – Internal bond ≥ 0,08 (EN 1607) Reaction to fire (Euroclass) E (EN 13501-1) Thermal conductivity (W/mK) (λ) Panels ≤ 0,033 / Interjoists ≤ 0,038 Water vapour diffusion resistance index µ 30 à 70 Water absorption ≤ 1,5% (EN 12087) Dimensional stability ≤ 0,5% (EN 1604) 3.4. Cast-in-place Concrete The consistence class of concrete for an ISM Sismo wall should be at least a slump class S4 according to EN 206-1, for ISM Sismo floors and roofs it should be at least a slump class S3. The most suitable concrete for an ISM Sismo wall is a self-compacting concrete with a slump flow class SF1 according to EN 206-9, for this type no extra measures are needed to ensure adequate compaction of the concrete. The compressive strength class is at least C20/25 for exposure class XC1, the thickness of the concrete shall be at least 10 cm. The size of the aggregates is function of the thickness of the concrete, the amount of reinforcement and the possible use of a pump device. The minimum size of the filler sections reported to the relevant properties of concrete is assumed to be in accordance with the following table: Table 3 Aggregate size and consistence class in function of the filling section Minimum dimension of the filling section Characteristics concrete according to EN 206-1 <12 cm Maximum aggregate size 8 mm, class of flow ≥ F5 12 cm ≤ section size < 14 cm Maximum aggregate size 16 mm, class of flow ≥ F4 (≥ F3 for slabs with open lattice ) ≥ 14 cm Maximum aggregate size 22 mm (32 mm for floor modules), class of flow ≥ F4 (≥ F2 for slabs with open lattice) Page 4 of 39 3.5. Type of modules Depending on the internal and external shuttering material one can divide ISM Sismo walls into 7 types (figures 5 to 11): Inside and outside insulation strips symmetrical and asymmetrical Inside board and outside insulation strips Inside and outside board strips Inside and outside insulation strips and outside Plus insulation panels Inside board and outside insulation strips and outside Plus insulation panels 2 ISM Sismo walls decoupled and insulated for an optimized acoustic performance, this type is typically used as separating wall between apartments and houses Module with insulation strips as core material ISM Sismo floors and roofs can be divided into 3 types: plain, one and two-way girder slabs. 4. Description of the components 4.1. Steel lattice The steel wire frame, framework of the ISM Sismo wall, is available in panels of different dimensions, see figures 2 to 4 : - Height: a multiple of 15 cm, with a maximum of 12 m - Length: a multiple of 10 cm, with a maximum of 1,2 m - Thickness: maximum 50 cm. Table 4 Dimensions of the module Dimensions of the module 4.2. Maximum (cm) Width Multiple of 10 cm 120 Height Multiple of 15 cm 1200 Thickness Depends on the type of wall, roof 50 Insulation strips, interjoists and panels See figures 1 to 19. The strips have 3 functions : Maintain fresh concrete during the provisional phase of pouring Thermal insulation in final phase Support of interior and exterior finishing The strips have fixed dimensions according to Table 1 and can be foreseen of a tongue and groove: 10 mm x 15 mm (h x w) for strips of 3.8 cm, 15 mm x 20 mm for EPS strips of 7.8 cm and 11.8 cm or bigger for EPS thicker than 11.8 cm. Page 5 of 39 The Plus panels have 2 functions: Thermal insulation in final phase Support of exterior finishing The panels have fixed dimensions (length 120 cm, width 45 cm). They are available in various thicknesses (up to 50 cm), plain or with a "waffle" structure (10 cm by 7.5 cm) where the groove has a depth of 1.5 cm and a width of 1 cm. The waffle structure ensures a good grip on the metal frame of the modules. The interjoists have 2 functions: Creation of ribs in order to create a one or two-way girder-slab floor Thermal insulation in final phase The interjoists have fixed dimensions (length 120 cm, width 45 cm) but can be cut in length to a multiple of 10 cm and width to a multiple of 15 cm. They are available in various thicknesses: 10 cm, 15 cm, 20 cm and 25 cm. They have a "waffle" structure (10 cm by 7.5 cm), the groove has a depth of 3 cm and a width of 1 cm. Their shape ensures a good grip on the metal frame of the floor modules. Schematic diagram of an ISM Sismo one way girder floor : The center to center distance between the ribs is a multiple of 15cm; The width of the ribs is 15cm or a multiple thereof. Schematic diagram of an ISM Sismo two-way girder-slab floor is shown below. The center to center distance between the ribs is a multiple of 15 cm; The width of the ribs is 15 cm or a multiple thereof; The center to center distance between the ribs is a multiple of 10 cm; The width of the ribs is 10 cm or a multiple thereof. 4.3. Production of ISM Sismo modules The production of ISM Sismo modules happens in the ISM Sismo Production Station or SPS™ The main stages of production include: • The unwinding of steel wire reels • The cutting and straightening of steel wire • The assembly and welding of two-dimensional lattices • The assembly and welding of tri-dimensional lattices • The cutting of insulation strips, interjoists and panels • The insertion of the insulating strips into the tri-dimensional lattice at the lateral intervals intended for this purpose The fixing of Plus panels and placing of interjoists on respectively ISM Sismo walls and floors happens on site. Plus panels are installed according to the specifications of paragraph 12.5, after hardening of concrete. Page 6 of 39 The production happens according to an internal factory production control plan, which addresses the requirements of the European Technical Approval 01/0001 (ETA 01/0001). There is a permanent internal control of production. All the parts, requirements and provisions adopted by the manufacturer are documented in a systematic manner in the form of written policies and procedures. The FPC ensures that the product is in conformity with the ETA. The manufacturer only uses wires, EPS, MW, HDF, CB and FCB. Checking of incoming materials, includes control of the documents presented by suppliers (comparison with nominal values). Conformity checks are made on incoming materials, and at regular stages throughout the production sequence to ensure the conformity and fitness of the components. Only after control of the dimensions of the modules and the conformity of the welding points, the strips may be integrated. This inspection includes a continuous visual inspection, and a sampling program for measuring of the dimensions and the welding strength, according to the prescribed test plan. The results of the FPC are recorded and evaluated. The records include at least the following information: - Designation; - Type of control or testing; - Date of manufacture and date of testing; - Results of control and testing and, where appropriate, comparison with requirements; - Signature of person responsible for factory production control. 4.4. Accessories The accessories needed for the erection of ISM Sismo walls on construction site are as following: ISM Sismo specific accessories: o struts: to support ISM Sismo panels during installation and pouring of concrete (maximum distance of 2 m between 2 struts), see figure 20; o Hollow profiles: to support ISM Sismo panels during installation and pouring of concrete, see red hollow profiles in figure 23; o U-profiles:. to connect the hollow profiles with the horizontal steel wire for supporting the ISM Sismo panels during pouring of the concrete, see figures 20 to 24; o Stapler: to connect the ISM Sismo panels (7 rings per linear meter, on each side of the wall, back and front), see figure 25; o Rings: to connect the ISM Sismo panels (7 rings per linear meter, on each side of the wall, back and front), see figure 1; o Cutter: necessary to cut the steel wire at the openings (doors, ceiling, etc..) after hardening of the concrete, see figure 27; Loop ties and Tie Twister for securing the reinforcement bars to the metal frame, see figure 26; Boards 3cm/12cm: for properly alignment of the walls; Props for ISM Sismo floors, see figures 28 and 29; Shuttering boards (e.g. OSB, MDF, …) as support for ISM Sismo floors in order to spread the concentrated loads of the vertical props. The number of vertical props can be reduced by using load spreading beams, see figures 28 and 29; Page 7 of 39 Ladder with a height corresponding to at least the height of the module; Plumb rule of 2 meter length; Plummet for the alignment of the walls (powder); Trowel: to smooth the concrete at the top of the wall; Wheelbarrow Brace and a 12 mm bit for fixing struts into concrete Anchorage bolts for struts; 5. Hygiene, health and the environment The kit does not contain materials which use is restricted according to The Directive on Dangerous Substances. The materials of the kit are resistant to the growth of fungi and other microorganisms under the normal temperature and humidity conditions. As described in paragraph 6 the designer shall consider the relevant needs for ventilation, heating and insulation to avoid condensation in service, which may lead to unacceptable growth of microorganisms (long-term effects). Infestation by vermin is not encouraged as there are no voids within the system. 6. Hygrothermal performance The risk for surface and interstitial condensation can be minimized by doing one or more of the following : Obtain low vapour pressures by ventilation and/or reduced moisture input to the building Obtain high surface temperatures by providing more insulation and/or increasing the heat input Use less thermal resistance near to the warmer side of the construction Use higher vapour resistance near to the warmer side of the construction ISM Sismo modules have typically more external than internal insulation. One can deviate from this principle if calculation of the surface and interstitial condensation according to ISO 13788 shows there’s no risk. The occupation of buildings, with associated activities and processes, produces moisture. This needs to be removed to outside air by ventilation, to avoid high relative humidity that can result in problems of condensation and mold growth. From the point of view of controlling condensation, the ideal ventilation system will provide either: finely controllable background ventilation; and mechanical extraction of water vapour from moisture producing areas such as kitchens and bathrooms; or continuous ventilation either by use of passive stack ventilation or a mechanical ventilation system. Minimum ventilation rates depend on the region and can be found in local standards. Page 8 of 39 7. Resistance to fire The resistance to fire can be derived from the thickness of the concrete as described in standard EN 1992-1-2 and Annex C of European Technical Approval Guideline n°9, and assessed according to following table: Table 5 Resistance to fire classification of ISM Sismo walls Minimal thickness of concrete (mm) 100 110 120 150 180 230 Example ISM Sismo wall Resistance to fire load bearing wall Resistance non load bearing wall S20_4EPS_4EPS S20_FC_8EPS S30_4EPS_12EPS S25_4EPS_4EPS+8EPS S20_FC_FC S25_FC_FC REI 30 REI 60 REI 90 REI 120 REI 180 REI 240 EI 90 EI 90 EI 120 EI 180 EI 240 EI 240 8. Reaction to fire Depending on the application, the reaction to fire class of an ISM Sismo panel can be adjusted by changing either the infill material or using a protective screen. 9. Thermal insulation As an example thermal resistance for some configurations of ISM Sismo walls can be found in table 6. The thermal resistance of these walls has been calculated according to standard EN ISO 6946. Table 6 Thermal resistance for some finished ISM Sismo walls 1 ISM Sismo wall ISM Sismo wall R (m²K/W) R (m²K/W) S25_4EPS_4EPS+8EPS 4.73 S25_4EPS_4EPS+12EPS 6.01 S35_4EPS_12EPS 4.2 S25_4EPS_4EPS+16EPS 7.28 S40_4EPS_20EPS 6.12 S25_4EPS_4EPS+20EPS 8.56 10. Thermal inertia The values for the heat capacity of the concrete, expanded polystyrene and fibrocement are given in standard EN ISO 12524. In table 7 the inertia effect of some finished ISM Sismo walls is given and calculated according to EN ISO 13786. Table 7 Thermal inertia for some ISM Sismo walls Decrement delay 1 Included thermal insulation for interior rendering λ = 0.18 W/mK (gypsum insulating plaster, Table 3 ISO 10456), for exterior rendering λ = 1 W/mK (cement, sand, Table 3 ISO 10456), for concrete λ = 1.35 W/mK (medium weight, Table 3 ISO 10456). Thermal insulation λ taken for EPS = 0.031 W/mK and steel = 50 W/mK Page 9 of 39 S25_4EPS_4EPS+12EPS 9h 27 min S25_FC_4EPS+16EPS 9h 43 min S30_4EPS_4EPS+12EPS 10h 39 min 11. Sound insulation A ISM Sismo wall can be used to meet the regulations regarding sound insulation. As an example some values of the sound reduction index can be found in table 8. Table 8 Sound reduction index for some ISM Sismo walls Rw (C ; CTR) (dB) S25_4EPS_4EPS+8EPS 52 (-2, -5) S20_FC_4EPS 51 (-1 ;-4) S10_4MW_S10 62 (-1 ; -3) The module S10_4MW_S10 is composed of two ISM Sismo modules separated by a mineral wool layer, this type is typically used as separating wall, a schematic diagram can be found in annex. 12. Implementation 12.1. Handling, transportation and storage of ISM Sismo panels The panels delivered on site can have sharp points, handling on site shall be done with gloves and protective glasses. Loading and unloading of ISM Sismo modules can be done manually (stored sideways, standing) as well as by machine (stored flat, in horizontal position). ISM Sismo modules can be transported and stored sideways, standing or in horizontal position. When stored and transported in horizontal position extra attention should be taken to limit stress because bottom panels of a pile horizontal stacked ISM Sismo modules have a higher risk to deform. 12.2. Erection of ISM Sismo panels The ISM Sismo panels are placed on the foundation or on the floors. They are held together by rings (figure 1) longitudinally placed every 15 cm on both sides of the wall In an initial phase the panels are supported on one of their sides by struts (figure 20) specially developed for this purpose. They provide lateral support to the panels during the initial phase till hardening of the concrete. The maximum distance between lateral supports should not exceed 2 meters.. It is possible to transform the struts to scaffolding to allow access at the top of the casing to monitor the pouring of concrete, in this case local regulations and laws should be respected. The free end of panels (in case of openings, windows, ceiling or doors) is closed in the same manner as the common parts to ensure the holding of fresh concrete. The verticality of the wall is checked before and during casting. Page 10 of 39 The ISM Sismo floor module can temporally, till hardening of the concrete, be supported by shuttering panels, beams and props as shown in figure 28-29. An installation plan shows the layout used for each bay. When props are only calculated for supporting the weight of fresh concrete, use can be made of a circulation and concrete pouring platform. Explicit mention is then shown on the installation plan. 12.3. Installation of reinforcement The principle plan of reinforcement can be found in annex. For efficient placement of the reinforcement a few aspects have to be taken into account. The modulated dimensions of the ISM Sismo lattice, are steps of 10 cm horizontally and steps of 15 cm vertically, see figures 4 and 59 to 62. As the reinforcement is kept in place by the ISM Sismo lattice, the distance between the reinforcement should be multiples of these dimensions. The securing of the bars through the lattice, ensures a correct positioning of the reinforcement after pouring concrete. Stirrups, straight, L- and U-shaped bars (figures 47 to 50) can easily be introduced during the mounting of the modules. The ISM Sismo lattice cannot be combined with welded reinforcement meshes. Depending on the type of ISM Sismo module used, stirrups and U-shaped reinforcement bars should respect maximum diameters as listed in the table below to guarantee concrete covering of the reinforcement. Table 9 : Maximum diameters reinforcement bars (EPSX = X cm insulating strips, FC = board) FC x FC FC x 4EPS 4EPS x 4EPS FC x 8EPS 4EPS x 8EPS S6® - - - - - S10® 5 - - - - S15® 10 5 - - - S20® 15 10 6 6 - S25® 20 15 11 11 7 S30® 25 20 16 16 12 S35® 30 25 21 21 17 S40® 35 30 26 26 22 S45® 40 35 31 31 27 The placing of vertical bars is done through the top of panels and progresses together with the mounting of the ISM Sismo panels. Horizontal bars for the achievement of horizontal ties, lintels or required by calculation are inserted sideways and progresses together with the mounting of the ISM Sismo walls. It is sometimes required to remove the insulating strips used as formwork at the edge of the panels to be able to insert the horizontal reinforcement bars, and then slide them back into position.. The chronology of placing reinforcement bars is detailed in schematic diagrams in annex: Corner-connection, see figures 71 to 73: Page 11 of 39 1. U-shaped horizontal reinforcement bars; 2. U-shaped horizontal reinforcement bars in the second wall; 3. The common vertical reinforcement bars T-connection, see figures 65 to 70: 1. U-shaped horizontal reinforcement bars in the wall to join; 2. Installation of the wall in T-junction; 3. Horizontal reinforcement bars of a wall; 4. The common vertical reinforcement bar. Beam, see figures 74 to 77 1. Vertical stirrups; 2. Horizontal reinforcement bars. 12.4. Pouring of concrete The concrete filling is done with a pump device, or a tipper. It is vital to respect the following requirements: The concrete filling should be limited to a maximum speed of 100 cm per hour, in layers up to 50 cm for a concrete with a consistence class SF1 . There shall never be filled a height greater or equal to 6 m a day. If filling is done with a pump device, it is advisable to take measures to cut the dynamic pressure of the concrete. A special flexible rubber sleeve shall be secured with retaining rings to the pipe of the pump device in order to limit the pressure of concrete by compressing the hose manually. As an alternative a bend can be put in the flexible rubber sleeve in order to cut the dynamic pressure. The gap to fill up with concrete will determine the plasticity of the fresh concrete and the maximum size of aggregates. The values are given in paragraph 3.4 To ensure the geometrical and mechanical characteristics of the finished wall, the following checks are carried out during the concrete filling: Control and possible correction of the verticality of the wall before hardening of the concrete Visual verification of the penetration of the cement laitance in the joints between the strips to be sure that all gaps are completely filled. Cores can be taken through the insulation at critical positions, such as below windows and at corners, to establish integrity of concrete. However this check is not required as tests realized to obtain the European Technical Approval have shown, when respecting prescriptions concerning consistency class and maximum size of aggregates, that the density of the steel wire frame allows a full satisfactory filling of the gaps. Roofs with pitches below and over 30° are constructed with respectively open and closed lattices. Insulating strips can be cleaned with a water jet or brushed after pouring of the concrete to remove light leakage of laitance. 12.5. Fixing of Plus panels The wall surface must be sound and free of dust, cleared of any non-adherent product The expanded polystyrene panels are fixed to their support by use of an adhesive. The Plus panels are available with a honeycomb structure which ensures a good grip on the 1 cm lattice which crosses the ISM Sismo panel, see figure 13. In this case there is no need for the use of Page 12 of 39 base profiles, mounting is only done by bonding on the substrate by means of an adhesive. The adhesive is applied in strokes on the Plus panel. Plus panels without honeycomb structure are used for ISM Sismo modules without external grip of 1 cm. For such an ISM Sismo module a base profile is set at least 15 cm above the highest point of the soil. A space of 2 to 3 mm is left between each profile to allow their thermal expansion. The first row of panels is mounted starting from the base profile An adhesive is applied using the so-called “beadpoint-method” i.e. around the edges in a strip and in the center of the panel in several hand palm-sized lumps Adjust the volume of adhesive applied and the base height according to the substrate tolerances such that an adhesive contact area of at least 40% to 60% (depending on the manufacturer’s prescriptions) is attained. The flatness is continuously verified by means of a 2 m rule. Always install the insulating panels with offset vertical joints, panel butts perfectly joined. Vary vertical joints accordingly for panel cuts. Cross joints are not permitted. Panel joints should also be minimized at extensions to the corners of façade openings (e.g. windows) to prevent cracks at these locations, "L"-cuts should be made to avoid aligned joints. It is recommended to cut and fit the panels after positioning and bonding. 12.6. Finishing 12.6.1. Rendering With the wide array of rendering options available it is essential to note that there are significant regional differences due to the availability of materials and local climate conditions. The recommendations of the manufacturer of the material should always be followed and good trade practice regarding installation and sealing should be observed. Renders should adhere to the specific background provided, be resistant to an acceptable level of impact, be frost proof (if applicable), preferably be weatherproof but moisture permeable and be able to resist thermal shock. Contact should be taken with local supplier to discuss which product in their range will be best suited for the finishing of the ISM Sismo modules. Below some general points to take into account. Both Lime- based and Cement based renders are suitable but generally Lime-based render systems have better reliability than cement-based systems with plasticizer. Polymer modified render systems with a fiber reinforcing mesh have good resistance to thermal shock and impact damage as the polymers have the ability to flex. Use pre-batched polymer modified render systems to ensure performance, site mixing is susceptible to incorrect proportions. Propriety and insulated render systems do not have the same track as traditional renders. However, evidence of the durability of these systems in use is increasing as time progresses. In Europe insulated renders have performed well over 40 years. Renders applied directly on top of insulation like on an ISM Sismo wall can be subjected to extreme temperature fluctuations referred to as ‘Thermal Shock’ therefore it is essential that they have a high mechanical resistance and elasticity to avoid the risk of micro cracks or surface crazing. For the hygrothermal cycles test, the freeze - thaw testing and the capillarity test, see Guideline for European Technical Approval, ETAG 004 ETICS "External Thermal Insulation Composite Systems with Rendering" 'Compatibility with internal and external finishings'. Page 13 of 39 The system is composed of modules of 120 cm, all external-rendering systems shall be used in accordance with provisions to bridge the network of joints between modules. The second layer of the base coat shall be reinforced with a fiber mesh to improve its mechanical strength. The thickness of the coating is at least: • 20 mm when the mesh protrudes the insulation by 1 cm, figure 40; • 10 mm for all other cases, e.g. on hard strips of wood fiber and cement, on expanded polystyrene for modules without protruding mesh of 1 cm, figure 41; • 5 mm on the Plus panels of expanded polystyrene, figure 42. The lattice must be at least covered with 5mm. The rendering should have a pH ≥ 11. Aggressive materials might cause corrosion of the ISM Sismo Lattice. The designer chooses the corrosion resistance according to the exposure requirements of the nonstructural steel products as used in internal and external mortar renderings. The ISM Sismo Lattice optimizes adhesion and impact resistance through the Mesh protruding the insulation by 1 cm and as such acting as an anchor and reinforcement for the rendering. The protruding ISM Sismo mesh of 1 cm can be eliminated when using a polymer modified lightweight render that has sufficient adhesion to the insulation. Mineral based renders require the ISM Sismo mesh for adhesion. Many premature failures and early repair requirements are the result of poor installation. Applying renders is a skilled operation. Use of approved and specially trained contractors, particularly for proprietary and insulated render systems, reduces the risk of early repair costs. The substrate has to be controlled for loose parts, any part of the ISM Sismo module that is protruding or loose has to be removed. The substrate has to be clean. If necessary it has to be cleaned with a broom to remove all impurities. The ISM Sismo wall may be rinsed with water to obtain a dust free surface. The ISM Sismo walls should be adequately cured and stable before rendering. They have to be free of any movement caused by solicitations, shrinkage, settling, etc… Reinforcement fiber mesh should be increased at areas of stress concentration such as window and door openings. At outer corners and at boundaries of the rendering, all the necessary corner- and stop-moldings have to be placed. Always take into consideration the thickness of the finishing layer. In places where there are different settlements, it is always advisable to make a movement-joint. Movement joints are essential to control cracking. They should be at centers appropriate to the movements expected of the render and substrate. Although a single coat can be used; two coat work, an undercoat and finishing coat is generally required. In conditions of severe exposure three coat work is recommended, with the first coat relatively impervious to water and the others more porous. Allow adequate drying time between successive coats. Protect surface from sun, rain and wind. Shrinkage and drying out may take several days. Textured finishes are less likely to show cracks than smooth finishes. Water is more likely to "ride" over the cracks rather than be drawn into the render. Permeable mixes are more durable than impermeable mixes. If proper attention has been given to external details in designing the structure and the rendering materials and methods of application are in accordance with the recommendations, external rendered finishes should not require any maintenance over a long period of years. However, depending on the levels of airborne pollution and dirt, there could be a requirement for regular cleaning. Typical maintenance would include allowances for annual inspection, cleaning every five years after year 20 and an allowance for minor repairs at 10-year intervals. Page 14 of 39 12.6.2. Other types of finishing The ISM Sismo module gives the freedom to choose virtually any finish at all, see figures 43 to 46. As long as the recommendations of the manufacturer of the finishing material are followed and good trade practice regarding installation and sealing is observed, the widest variety of finishing techniques can be adopted, such as natural stone claddings, shingles, cladding panels, masonry, curtain walling, plastering, plasterboards, tiling, wood paneling and so on. 12.7. Imbedding of ducts The use of certain filling materials makes it possible to install conduits quickly and easily, see figure 30 . Self-extinguishing polystyrene, for example, makes it possible to melt a path for all conduits. When thin hard panels are used for the shuttering, conduits may either be surface mounted or inserted before the concrete is poured. Alternatively, polystyrene strips may be inserted, allowing the conduits to be installed at a later stage. This entails that the local reduction in the thickness of the concrete must be checked to ensure that it doesn't affect overall strength 12.8. Fixing of objects It is possible to fix objects up to 35 kg per fixing device (expanding plug) in the finishes and insulation strips; for other cases the fixing devices should be inserted in the concrete. For the type of fixing, advice should be sought at the local distributor 12.9. Other Details In attachment following schematic diagrams are displayed (figures 31 to 46): window connections, floor connections, roller shutting and (underground) finishing 13. Structural design 13.1. Strategy The strategy is to exploit concrete to the ultimate and to use standard solutions for traditional reinforcement where needed. Reinforcement, installed according to the specifications in paragraph 12.3, depends on the application and is determined by structural calculations performed according to the local standards and rules 13.2. Basic principles of designing plain concrete The optimal result is obtained when ISM Sismo walls are designed as braced construction elements whose horizontal loads are supported by other , bracing elements belonging to the same construction, e.g. shear walls. Page 15 of 39 Walls subjected to bending or axial load and bending, for the rest exclusively subjected to wind load parallel or perpendicular to the plane of the wall, can be designed without steel reinforcement , provided the following condition is met: md + mt,i ≤ mu md = the design value for the limit state of collapse, of the maximum bending moment per unit length, due to the loads liable to act on the structure mu = the ultimate bending moment per unit length occurring with the design value of the axial load applied at the center of gravity of the cross section mt,I = the design value for the limit state of collapse, of the accidental restraint moment Wall-to-floor tie-reinforcement When mt,i is too high to meet the above condition and there can be proven that a position equilibrium is possible for the limit state of serviceability, no reinforcement is needed if accepted by local standards and rules. This equilibrium exists if the rotation capacity of the wall near to the wall-floorconnection is sufficient to follow the rotation of the floor slab. If this equilibrium doesn’t exist wallto-floor tie-reinforcement will be needed. Wall-to-wall tie-reinforcement In bearing walls of houses and buildings where no special loads are to be considered , there shall be a continuous horizontal tie-reinforcement on every floor level . If not otherwise specified by local standards, the tie-reinforcement may be omitted when the difference between the upper floor level and the terrain does not exceed 6.5 m. Edge reinforcement in walls Vertical reinforcement shall be provided at the edges of bearing walls for houses and buildings where no special loads are to be considered. Reinforcement shall be provided around all door and windowopenings. If not otherwise specified by local standards, edge reinforcement in walls may be omitted when the difference between the upper floor and the terrain does not exceed 12.5 m Splitting reinforcement at beams Splitting reinforcement is needed when the design value of the bearing stress due to the concentrated load exceeds the design value of concrete strength Page 16 of 39 ANNEXE 1 Figures ISM Sismo Wall 2 4 3 5 1 External rendering 1 2 Outside insulation strip 3 Concrete 4 Inside insulation strip 5 Rings Figure 1 Page 17 of 39 ISM Sismo Lattice composition Steps of 15 cm Figure 2 Vertical cross section of ISM Sismo steel wire lattice. Right figure one side without 1 cm protruding lattice (so called single wire frame on one side). 1 = position of insulation strips, 2 = position sheet strips Figure 3 Cross section, available up to 50 cm Steps of 10 cm Page 18 of 39 ISM Sismo Module types Figure 4 Modular dimensions ISM Sismo module Figure 5 Inside and outside insulation strips, symmetrical Figure 6 Inside and outside insulation strips, asymmetrical Figure 7 Inside and outside insulation strips and outside Plus insulation panel Figure 8 Inside board and outside insulation strips Figure 9 Inside and outside board strips Figure 10 2 ISM Sismo walls with outside board strips decoupled and insulated by mineral wool for acoustic performance Figure 11 Module with insulation as core Page 19 of 39 Insulation strips for infill Figure 12 Insulation strips either with or without tongue and groove ISM Sismo Plus insulation panels Figure 13 Page 20 of 39 ISM Sismo floor Figure 14 ISM Sismo module for a deck slab Figure 15 EPS-block for ISM Sismo floor module Figure 16 ISM Sismo floor module with EPS interjoist to create a girder-slab ISM Sismo floor Figure 17 One way girder-slab ISM Sismo floor Figure 18 One way girder-slab ISM Sismo floor Page 21 of 39 Figure 19 Two way girder-slab ISM Sismo floor Accessories Figure 22 Figure 23 Figure 20 ISM Sismo Struts Figure 24 Figure 21 1 set of ISM Sismo struts : 1 strut, 3 hollow profiles, 9 U-profiles Page 22 of 39 Accessories Tools : Figure 25 Stapler & Omega staples Figure 26 Loop ties & Tie Twister Figure 27 Wire cutter Floor props and shuttering boards Figure 28 Floor props supporting beams and shuttering boards Figure 29 Imbedding of ducts Figure 30 Ducts embedded into concrete and/or insulation strips, either before pouring concrete or afterwards in the insulation (cut or melt) Page 23 of 39 Window connections 1 L-Mechanical tie for fixing window profile 3 2 Sealant 4 3 Windowsill 2 1 5 Figure 31 Vertical section Figure 32 Horizontal section : center, front and back position of window Page 24 of 39 4 Insulation 5 Concrete Roller shutter housing Figure 33 Façade closed or open with integrated insulated roller shutting housing 1 Insulated roller shutting housing 2 Width window 3 Façade open 4 Multiple of 100 Page 25 of 39 Floor connections Figure 34 With ISM Sismo floor module Figure 36 With self-bearing element and compressed layer Figure 35 With ISM Sismo floor module Figure 37 With self-bearing element and compressed layer 1 Finishing 2 Screed 3 Slab A1 Module Height A2 Clear Headroom A3 Structural floor Page 26 of 39 Underground finishing 1 Top coat on base coat 2 Plinth 3 Waterproof coat 4 Soil 5 Base coat 6 Drainage material Figure 38 Finishing on ISM Sismo foundation 1 Top coat on base coat 2 Plinth 3 Waterproof insulation 4 Soil 5 Waterproof coat 6 Drainage material Figure 39 Finishing on existing foundation Page 27 of 39 Substrates for rendering, three alternatives Figure 40 With protruding lattice (double wire), ±20 mm Figure 41 Without protruding lattice (single wire), ±10 mm rendering rendering Figure 42 On a Plus panel , ±5 mm rendering Some examples of finishings Figure 43 Finishing board with the bead point method Page 28 of 39 Figure 44 Tiles on a cement base Figure 45 Mechanical anchors for natural stone or cladding Figure 46 Brick facade with wall ties ISM Sismo Principle reinforcement Figure 48 Straight reinforcement bar Figure 47 Stirrup Figure 49 L-shaped reinforcement bar Figure 50 U-shaped reinforcement bar Wall – floor connection : Figure 51 Figure 53 Page 29 of 39 Figure 52 Figure 54 Starter bars : Figure 55 or Figure 57 Figure 56 Figure 58 Page 30 of 39 Positioning of reinforcement bars : Figure 60 Vertical reinforcement bars Figure 59 Horizontal reinforcement bars Figure 61 Page 31 of 39 Figure 62 Figure 63 Figure 64 Page 32 of 39 Wall connection – T-connection: Figure 66 Figure 65 Figure 67 Step 1 Figure 69 Step 3 Page 33 of 39 Figure 68 Step 2 Figure 70 Step 4 Wall connection – Corner connection: Figure 72 Figure 71 Figure 73 Page 34 of 39 Lintel/Beam: Figure 74 Figure 75 Figure 76 Figure 77 Page 35 of 39 Floor: Figure 78 Ring beam Figure 79 Girder iron Figure 80 Girder anchor Figure 81 Shrinkage compensating reinforcement Figure 82 Floor reinforcement Page 36 of 39 ANNEXE 2 Experimental results Measurement of the sound reduction index of ISM Sismo walls according to standards EN ISO 10140-2: 2010 and EN ISO 717-1:1996 carried out by the accredited laboratory Blasco bvba - LARGE certified to standard EN ISO/IEC 17025 – Tests carried out in Belgium in 2013 Salt spray test conducted by Bekaert Technology Centre according to ISO 9227, DIN SS 50021 and ASTM B117 in 2008 Compression tests on concrete cores taken from an ISM Sismo wall filled with concrete under more severe conditions than specified in the ETA 01/0001 – Test carried out by the laboratory of Magnel of the University of Ghent, Belgium in 2006 (www.labomagnel.ugent.be) Plain concrete ISM Sismo walls, ISM Sismo Building Technology: plain concrete in high rise buildings – Theoretical and experimental study presented by the Civil Engineering Department of the University of Leuven, Belgium in 1994 Determination of the bending moment resisting capacity of wall-to-floor connections with ISM Sismo standard reinforcement, under vertical and horizontal load – Test carried out by the Civil Engineering Department at the University of Leuven, Belgium in 1993 and 1994. Buckling behavior of ISM Sismo walls and columns, ISM Sismo wall-to-wall connection in earthquake areas: shear strength – Tests carried out by the Civil Engineering Department at the University of Leuven, Belgium in 1992 and 1993 Determination of the attachment strength of resistance welds in two types of steel grids – Tests carried out by the Research Centre of the Belgian Welding Institute of the University of Ghent, Belgium in 1991 Plaster adhesion on ISM Sismo panels – Test carried out by the laboratory of building materials from the University of Liege, Belgium in 1991 Orientation tests concerning the fire resistance of load bearing ISM Sismo walls and floors – Tests carried out by the laboratory for Use of fuels and heat transfer from the University of Ghent, Belgium in 1985 and 1988 Longitudinal compression test on ISM Sismo panel – Tests carried out by the University of Leuven, Belgium in 1985 ANNEXE 3 List of reference documents ETAG 004 External Thermal Insulation Composite Systems with Rendering ETAG 009 Non load-bearing permanent shuttering kits/systems based on hollow blocks/panels of insulating materials and sometimes concrete EN ISO 140-3 Acoustics – Measurement of sound insulation in buildings and of building elements – Part 3 : Laboratory measurements of airborne sound insulation of building elements. EN 206-1 Concrete – Part 1: Specification, performance, production and conformity EN 206-9 Concrete – Part 9: Concrete. Additional rules for self-compacting concrete (SCC) EN 310 Wood-based panels - Determination of modulus of elasticity in bending and of bending strength EN 317 Particleboards and Fibreboards - Determination of swelling in thickness after immersion in water Page 37 of 39 EN 318 Fibreboards - Determination of dimensional changes associated with changes in relative humidity EN 319 Particleboards and Fibreboards -Determination of tensile strength perpendicular to the plane of the board EN 323 Wood-based panels - Determination of density EN 324-1 Wood-based panels - Determination of dimensions of the board – Part 1: determination of thickness, width and length. EN 324-2 Wood-based panels - Determination of dimensions of the board – Part 2: determination of squareness and edge straightness. EN 382-2 Fibreboards - Determination of surface absorption – Part 2: test methods on hardboards EN ISO 534: Paper and board - Determination of thickness, density and specific volume ISO 535: Paper and board - Determination of water absorptiveness -- Cobb method EN 622-1 Fibreboards, Specifications - Part 1 General requirements EN 622-2 Fibreboards, Specifications - Part 2 Requirements for hardboards EN 822 Thermal insulating products for building applications - Determination of length and width EN 823 Thermal insulating products for building applications - Determination of thickness EN 824 Thermal insulating products for building applications - Determination of squareness EN 826 Thermal insulating products for building applications - Determination of compression behaviour ASTM D 828 Standard test method for tensile properties of paper and paperboard using constant-rateof-elongation apparatus ASTM D 829 Standard test methods for wet tensile breaking strength of paper and paper products EN ISO 1463 Metallic and oxide coatings. Measurement of coating thickness. Microscopical method. EN 1602 Thermal insulating products for building applications - Determination of the apparent density EN 1604 Thermal insulating products for building applications - Dimensional stability test of the insulation EN 1607 Thermal insulating products for building applications - Determination of tensile strength perpendicular to faces EN 1991 Basis of design and actions on structures EN 1992-1-1 Design of concrete structures. Part 1-1: General rules and rules for buildings EN 1992-1-2 Design of concrete structures. Part 1-2: General rules - Structural fire design EN 1998-1 Design provisions for earthquake resistance of structures EN ISO 6946 Building components and building elements - Thermal resistance and thermal transmittance – Calculation method EN ISO 8990 Testing of building components by hot box -General method EN 10002-1 The tensile strength of the wire Page 38 of 39 EN 10016-1 Non-alloy steel rod for drawing and/or cold rolling - Part 1: general requirements EN 10088-1 Stainless steels – List of stainless steels EN 10244 - 1 Steel wire and wire products - Non-ferrous metallic coatings on steel wire - Part 1: General principles EN 10244 - 2 Steel wire and wire products - Non-ferrous metallic coatings on steel wire - Part 2: Zinc or zinc alloy coatings on steel wire ISO 10287 The shear strength of the welding EN ISO 10456 Thermal insulation - Building materials and products - Determination of declared and design values. EN 12086 Thermal insulating products for building applications - Determination of water vapour transmission properties EN 12087 Thermal insulating products for building applications - Determination of long term water absorption by immersion EN 12089 Thermal insulating products for building applications - Determination of bending behaviour EN 12467 Fiber-cement flat sheets - Product specification and test methods. EN 12524 Building materials and products - Hygrothermal properties - Tabulated design values EN ISO 12572 Hygrothermal performance of building materials and products - Determination of water vapour transmission properties EN ISO 12625-4: Tissue paper and tissue products. Determination of tensile strength, stretch at break and tensile energy absorption EN ISO 12625-5: Tissue paper and tissue products. Determination of wet tensile strength EN 12667 Thermal performance of building materials and products - Determination of thermal resistance by means of guarded hot plate and heat flow meter methods - Products of high and medium thermal resistance EN 13162 Thermal insulation products for buildings - Factory made mineral wool (MW) products Specification EN 13163 Thermal insulation products for buildings - Factory made products of expanded polystyrene – Specification EN 13501-1 Fire classification of construction products and building elements - Part 1: Classification using data from reaction to fire tests EN ISO 13786 Thermal performance of building components -- Dynamic thermal characteristics -Calculation methods EN ISO 13788 Hygrothermal performance of building components and building elements -Estimation on internal surface temperature to avoid critical surface humidity and calculation of interstitial condensation. EN 13986 Wood-based panels for use in construction - Characteristics, evaluation of conformity and marking The Directive on Dangerous Substances Page 39 of 39