Heat Pump Hot Water System Installation Manual
Transcription
Heat Pump Hot Water System Installation Manual
Heat Pump Hot Water System Installation Manual Congratulations Contents Congratulations and thank you for choosing our heat pump hot water system. Before you install the hot water system, we recommend that you read through the entire installation manual, which provides instructions on the safe installation of the hot water system. Important safety instructions......................................................... 3 To avoid the risks that are always present when you install a hot water system, it is important that you read the safety instructions carefully to ensure that the hot water system is installed correctly and safely. After unpacking the hot water system please check that it is not damaged. If in doubt, do not install the hot water system but contact your local Electrolux Customer Care Centre. Heat pump specifications................................................................. 4 Storage tank specifications ............................................................ 5 Components .......................................................................................... 6 Installation ............................................................................................. 8 Installation diagram ......................................................................... 12 Electrical connection ....................................................................... 14 Temperature sensor connection ................................................. 16 Commissioning.................................................................................... 17 Meanings of symbols used in this manual are shown below: warning Warranty ............................................................................................... 19 This symbol indicates information concerning your personal safety caution This symbol indicates information on how to avoid damaging the hot water system environmental tips This symbol indicates tips and information about economical and ecological use of the hot water system warning • Contact an authorised installer for installation of this hot water system. • Contact an authorised service technician for repair or maintenance of this hot water system. • Installation work must be performed in accordance with the national standards by authorised personnel only. Wrong connection can cause over heating or fire. •This hot water system should be installed in accordance with AS/NZS3000 and your local electrical wiring rules. environmental tips Information on disposal for installers • Most of the packing materials are recyclable. Please dispose of those materials through your local recycling depot or by placing them in appropriate collection containers. • If you wish to dispose of an old hot water system, please contact your local authorities and ask for the correct method of disposal. 2 contents Kelvinator heat pump hot water system Conditions of use This appliance is intended to be used in household and similar applications such as : • staff kitchen areas in shops, offices and other working environments. • farm houses. • by clients in hotels, motels and other residential type environments. • bed and breakfast type environments Important safety instructions This Installation Manual has been prepared for Installers and Service Technicians of the equipment. Please keep it in a safe place for future reference. • In order to avoid injury, do not remove the fan guard of the heat pump. For the installer • Never use a flammable spray such as hair spray, lacquer paint near the hot water system as it may cause a fire. The installation must be completed by suitably licensed installers in accordance with the information supplied in this Installation Manual. All other relevant National, State or Local regulations must also be conformed with and these include (but are not limited to): • Australian Standard AS/NZS3500.1 - Water Supply • Australian Standard AS/NZS3500.4 - Hot Water Supply • Australian Standard AS/NZS3000 - Electrical Installation • Do not touch the heat exchanger fins on the heat pump. These fins are sharp and could result in cutting injuries. • This hot water system delivers water above 50°C and a tempering valve (supplied) must be installed in accordance with AS3498 to avoid scalding. • The operation of the thermal cut-out (located on the storage tank thermostat) indicates a possibly dangerous situation. Do not reset the thermal cut-out until the hot water system has been serviced by a qualified person. caution If you do not follow these instructions exactly, a fire or explosion may occur, resulting in property damage, personal injury or loss of life. Ensure the following safety instructions are read and understood before commencing installation. warning • For continued safety of this appliance it must be installed, operated and maintained in accordance with the manufacturers instructions. • This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance. • In order to avoid electric shock, fire or injury, if any abnormality is detected, such as the smell of smoke coming from the hot water system, isolate the power at the main switchboard then contact your local Electrolux Customer Care Centre. • Ensure that the hot water system and pipe work are adequately earthed to avoid an electric shock. • Never install a circuit breaker or power cable with the wrong current rating as this may cause a fire hazard or the circuit breaker to trip incorrectly. • Do not insert fingers, rods or other objects into the air inlet or outlet of the heat pump. When the fan is rotating at high speed, it will cause injury. • Do not use the hot water system for other purposes besides water heating for normal domestic use. • Do not place items around the hot water system which may be damaged by water leaking or draining from the hot water system. • Ensure that any water drained during installation does not cause damage to the building or property. • The minimum inlet water pressure must be 150kPa. • If the hot water system supply pressure exceeds 600kPa, a pressure limiting valve must be fitted to limit the pressure to 600kPa. A 700kPa cold water expansion control valve (not supplied) may also need to be installed at the water inlet to the storage tank according to local regulations. • A 99°C/850kPa temperature and pressure relief valve (supplied) must be installed in the relief valve connection near the top of the storage tank. • Operate the relief valve easing gear at least every 6 months in order to remove lime deposits, confirm correct operation and to verify it's not blocked. warning Failure to operate the valve easing gear at least once every 6 months may result in the water heater failing, or in extreme cases exploding. Continous leakage of water from the valve may indicate a problem with the water heater. • Water may leak from the discharge pipe of the relief valve(s). Ensure that the discharge pipes are left open to the atmosphere at all times and are installed in a continuously downward direction. • If any power cables are damaged during installation, they must be replaced by a qualified person in order to avoid damage or injury. • The temperature settings for the heat pump and auxiliary boost heater are factory pre-set to ensure optimum energy efficiency whilst providing Legionella bacteria protection. The temperature settings are therefore not adjustable by the customer or installer. Kelvinator heat pump hot water system important safety instructions 3 Heat pump specifications auxiliary heater boost button air bleed valve circulating water outlet circulating water inlet power cable entry air outlet mesh enclosure KSE362HPCB Heat pump Dimensions ( w x h x d) in mm Heating capacity (kW) 790 x 765 x 275 Condition 1* Standard power (kW) Heating capacity (kW) Condition 2* Standard power (kW) 4.30 1.25 4.70 1.39 Heat pump circuit power rating (kW) 1.95 Maximum power rating including tank element operation (kW) 3.60 Power supply 220V-240V ~ 50 Hz Refrigerant R410A (1200g) Maximum water pressure (kPa) 850 Outdoor protection rating IP24 Circulating water inlet and outlet connections (mm) Air side heat exchanger Fan motor power (kW) Air outflow mode 20 (3/4") 0.08 Air flow from rear Net weight (kg) 62 Full weight (kg) 65 NOTE: Condition 1*: Outdoor ambient temperature is DB/WB 7°C/ 6°C, water inlet temperature of the units is 30°C , water outlet temperature is 35°C. For more specific heat pump dimensions and safe installation distances refer to page 8 of this manual. 4 heat pump specifications Kelvinator heat pump hot water system Condition 2*: Outdoor ambient temperature is DB/WB 20°C/ 15°C, water inlet temperature of the units is 15°C , water outlet temperature is 55°C. Storage tank specifications Model number KCT27036A KCT27036B KCT34036A KCT34036B KCT42536B Diameter (mm) - A 650 600 650 700 700 Height (mm) - B 1390 1675 1690 1520 1785 Electrical connection height (mm) - C 580 750 680 700 850 Cold inlet and flow connection height (mm) - D 80 240 80 280 280 Return connection height (mm) - E 580 775 580 725 875 Hot outlet and relief valve connection height (mm) - F 1165 1415 1475 1250 1515 Tank capacity (L) 270 270 340 340 425 Net weight (kg) 95 95 110 110 135 Tank wall thickness (mm) 2.5 2.5 3 3 3 Element rating (kW) 3.6 3.6 3.6 3.6 3.6 T/P relief valve pressure limit (kPa) 850 850 850 850 850 T/P relief valve temperature limit (°C) 99 99 99 99 99 T/P relief valve energy release rate (kW) Full weight (kg) 10 10 10 10 10 365 365 450 450 560 Kelvinator heat pump hot water system storage tank specifications 5 Components Supplied with tank: KCT27036A, KCT27036B, KCT34036A, KCT34036B, KCT42536B Item No. Quantity Image Description KCT27036A - 270L tank with 3.6kW element KCT27036B - 270L tank with 3.6kW element 1 1 of KCT34036A - 340L tank with 3.6kW element KCT34036B - 340L tank with 3.6kW element KCT42536B - 425L tank with 3.6kW element 2 1 Bush 3/4" Male to 1/2" Female 3 1 Temperature and Pressure relief valve 1/2" Male Note: The item numbers used in the table refer to the numbers used in the installation diagram located in the middle of this manual (pages 12 and 13) 6 components Kelvinator heat pump hot water system Components Supplied with Heat Pump: KSE362HPCA Item No. Quantity Image Description 4 1 KSE362HPCA - Heat Pump module 5 1 Sensor wire 6m 6 1 Sensor pocket assembly 7 4 Rubber mounting feet 8 1 Rubber seal for drain spigot 9 1 Drain spigot Supplied with Heat Pump connection kit: KSEHPKA 11 3 Nipple 3/4" to 3/4" male 12 1 Tee piece 3/4" female 13 4 Elbow 3/4" male to 3/4" female 14 2 Flexible hose 1m 3/4" female, with fibre sealing washers 15 1 High performance tempering valve 50°C Note: The item numbers used in the table refer to the numbers used in the installation diagram located in the middle of this manual (pages 12 and 13) Kelvinator heat pump hot water system components 7 Installation Installation of the heat pump hot water system shall be completed in accordance with the AS/NZS 3500.1 and AS/ NZS 3500.4 plumbing codes regarding water and hot water supply as well as local authority regulations and any other applicable Australian standards. If the heat pump hot water system cannot be installed correctly to the Australian standards do not place it into service. If any problems or questions arise during the installation that cannot be answered in this installation manual please call the relevant local authorities or the Electrolux service centre (number located in the warranty section of this manual). The heat pump has been charged with refrigerant and does not require any on-site installation of refrigeration components. caution Installing the hot water system in any of the following places may lead to malfunction of the system. • Sites containing mineral oils such as cutting lubricant. • Locations beside the sea where salt air can cause corrosion. • Locations near hot springs where corrosive gases exist, e.g., sulfide gas. • Factories where the supply voltage fluctuates markedly. • Inside a cabin or caravan. • Kitchens where oil permeates the air. • Places where strong electromagnetic radiation exists. Choosing a suitable installation location The hot water storage tank can be installed either indoors or outdoors however the heat pump must be installed outdoors only. The heat pump is designed to operate within the temperature range of -7°C to 50°C, ensure the site chosen is within this ambient temperature range. Please ensure the following: 1. Enough space for installation and maintenance is available around the hot water system. 2. The height difference between the water outlet of the heat pump and water inlet of the water tank will be less than 5 metres. 3. The air inlet and outlet of the heat pump will be free from obstacles and sheltered from strong winds. 4. The bearing surface is level, can bear the full weight of the hot water system, and is suitable for installing the heat pump without increasing noise or vibration. 5. The operational noise of the heat pump will not affect occupants and neighbours. 6. No flammable items stored near the installation site. • Places where flammable gases or materials exist. • Places where acid or alkali gases evaporate. If installing the heat pump in cyclonic areas or areas where high levels of wind exist, ensure the mounting solution and fixing is adequate. If possible, avoid installing the heat pump at elevated heights in these areas and instead place it in a more sheltered position at ground level. H 7. The location is convenient for piping and wiring. wall or obstacle air inlet A A maintain channel air inlet B A C air outlet B E D C 12×22mm mounting hole D fix with bolt A 563 B 295 C 100 D 790 E 275 Note: All measurements are in mm. A 300 B 600 C 1500 Note: All measurements are in mm. 8 installation Kelvinator heat pump hot water system D 600 For specific dimensions of the storage tank and its connections refer to page 5 of this manual. H 765 Installation Precautions before installing 1. Decide the correct way to transport the hot water system. 2. Transport the hot water system in its original packaging to avoid damage. 3. Ensure the heat pump is kept upright at all times, including during transportation. NOTE: Please confirm the mounting fixtures are strong enough and mounted firmly if the heat pump unit is to be installed on an external wall. If leakage of water from the hot water system has potential to cause property damage, a properly drained safe tray is to be installed under the heat pump and/or storage tank. Frost protection This hot water system can operate in frosty conditions down to -7C when the following important installation requirements are followed: Ensure adequate insulation is installed on all exposed connections, pipe work and hoses (minimum thickness 20mm). The heat pump must be installed on continuous only power supply so that power is available at all times in order for the frost protection mechanism to operate. The inlet valves and storage tank should be installed inside if possible. The relief valve piping must be installed in a frost free environment in order to remain open to atmosphere at all times. Electric heater tape is recommended to be installed underneath piping insulation in extreme frost areas. Water quality Water quality can vary in different locations and affect the performance and safe operation of the hot water system. If the water supply is not within the acceptable limits as indicated below, the hot water system should not be installed, and may not be covered by the Electrolux warranty. A suitable solution is to implement a water pre-treatment process to bring the water quality to within acceptable limits to support the installation. The saturation index (SI) is a measure of the corrosive or scaling properties of the water supply. Corrosive water (SI<1.0) can corrode copper components. In these conditions warranty will not apply. Scaling water (SI>0.5) can cause build up of CaCO3 (Calcium carbonate) which can impact to the correct operation of moving parts within the system, including the temperature and pressure relief valve. In these conditions warranty may not apply. Total Dissolved Solids (TDS) and water hardness can also impact the life of the hot water system, and warranty does not apply outside the following limits: • TDS exceeding 600 p.p.m • Electrical conductivity exceeding 850us/cm • Total hardness exceeding 200 p.p.m • Chloride exceeding 250 p.p.m • Magnesium exceeding 10 p.p.m • Sodium exceeding 150 p.p.m • Acidity/Alkalinity must also be within the limits of pH 6.5 - 8.5 If this hot water system is installed in a regional location where regular flushing is required due to sediment build up, then a drain cock for flushing must be fitted at the time of installation. If in doubt, consult your plumber. Placing of heat pump and storage tank The heat pump and storage tank must be installed on a level surface and checked with a spirit level. The storage tank in particular must be level to ensure the correct positioning of the anode inside the tank and to prevent premature breakage. Level installation will also ensure that hot water is drawn from the top of the tank and will assist air being dispelled during commissioning. Heat pump placement and fixing The heat pump may be installed mounted to a wall on a bracket or on the ground. It must be fixed securely in place and the rubber feet provided with the heat pump are to be placed on the heat pump’s footings to dampen vibration. Ensure that the mounting location is capable of handling the full weight of the system and its components when filled with water, refer specifications tables on pages 4 to 5 for full weight details. If installing in a cyclone prone area, ensure that the fixing methods are appropriate. under heat pump: drain assembly (viewed from back of unit) Water may leak from the heat pump due to condensation and this is part of normal operation. A drain elbow has been provided with the heat pump and shall be installed, along with a drain hose, if necessary. If the hot water system is positioned where leakage could cause property damage, install suitable drained safe-trays where appropriate. Connections and piping of the hot water system Connections on the heat pump and the storage tank are all 3/4”. Storage tank inlet connections An isolating and non return valve must be installed on the inlet to the hot water system. If the supply pressure may exceed 600kPa, a pressure limiting valve must also be installed on the inlet piping. A pressure relief valve may also need to be installed on the inlet to the hot water system under local plumbing requirements. inlet flow cold inlet isolating and non return valve pressure limiting valve (600kPa) cold water expansion control valve (700kPa) drain Kelvinator heat pump hot water system installation 9 Installation Storage tank outlet connections Heat pump connections This hot water system may deliver hot water between 47C to 60C during normal operation. Any pipes delivering hot water to the premises are to be installed with sufficient piping insulation to maintain the efficiency of the hot water system and to prevent heat loss. It is recommended that a heat trap be installed on the outlet piping of the storage tank to minimize convective heat loss. The supplied tempering valve must be installed in order to temper any water that travels to fixtures primarily used for the purposes of personal hygiene (e.g. bathroom or ensuite fixtures) down to 50°C as required by AS/NZS 3500.4. The heat pump can be installed up to 5 metres away from the storage tank (only 1 meter of hose is supplied). If the heat pump is to be installed further than 1m away, run hard copper piping from the tank to a point near the heat pump. Use the hoses supplied to connect from the heat pump to the hard plumbing in order to dampen vibrations on the circulating water piping from heat pump vibration. The hoses and any additional piping between the heat pump and storage tank must have 20mm thick insulation covering them to maintain the efficiency of the system. The hoses supplied in the heat pump connection kit KSEHPKA must be used and old hoses are not to be re-used. Under no circumstances should an isolation valve be installed on the hoses or connections between the heat pump and the storage tank. outlet The circulating water inlet connection to the heat pump is to be plumbed to the flow connection on the storage tank. The circulating water outlet connection on the heat pump must be plumbed to the return connection on the storage tank. uncontrolled hot water outlet (kitchen, laundry) outlet tempered (50°C) hot water outlet (bathrooms) inlet tempering valve Relief valve piping A 99°C/850kPa temperature and pressure relief valve comes supplied with the storage tank and must be installed on the relief valve connection near the top of the tank. The drainage piping from the relief valve (and the one on the inlet if installed) must have a constant downward fall and must be plumbed to an outside drain. The outlet of the drainage piping must be left open to the atmosphere at all times, and installed in a frost free environment. outlet relief valve 10 installation Kelvinator heat pump hot water system The 3/4" tee piece provided will need to be installed on the storage tank’s return connection to allow the sensor pocket to be installed and inserted into the storage tank along with the heat pump outlet connection. return Installation Filling with water and dispelling air from the system At this stage the wiring to the hot water system should either be disconnected at the switchboard or have the power isolated to it (off). Once all plumbing connections have been made to the hot water system, it will need to be filled with water and pressurized in order to check for leaks and to dispel air from the system. Activate the lever on the relief valve located on the storage tank. outlet relief valve activation lever Turn on the water supply to the premises and open the isolation valve located on the inlet piping to the storage tank. Water should begin flowing into the hot water system and air will be dispelled from the relief valve piping. When water begins flowing from the relief valve piping de-activate the lever and wait for the hot water system to pressurise. Check for any leaks in the hot water system and fix them as required. Open the air bleed valve located on the circulating water outlet connection of the heat pump. Wait until water is flowing freely out of the air bleed valve and then close it. The heat pump should now be primed with water. air bleed valve outlet inlet Open the nearest hot tap or fixture to the hot water system. Once water is flowing freely from the hot tap or fixture, indicating that all air has been dispelled from the hot water system, close the hot tap or fixture. Kelvinator heat pump hot water system installation 11 Installation diagram continuous wiring configuration off peak wiring configuration refer to the electrical section for more detail on wiring the heat pump 150mm Ø2.5mm continuous supply input continuous supply input storage tank storage tank heater output heater output off peak supply input refer to local electrical requirements to ascertain whether isolation switch is required uncontrolled hot water outlet (kitchen, laundry) sensor cable plugs in here 25mm diameter conduit tempered (50°C) hot water outlet (bathroom tempering valve outlet under heat pump (drain assembly viewed from back of unit) – discharge condensation drain hose to a suitable location 20mm diame condu 25mm diameter conduit inlet cold inlet All numbered items are supplied with the hot water system. Please refer to the Components list on pages 6 & 7 for details. Items which are not numbered are not supplied and need to be supplied by the installer in accordance with local plumbing requirements. Installation of this hot water system must be completed by an authorised and licensed person in accordance with all local regulations, including AS3500 plumbing and drainage requirements and AS3000 electrical wiring standards. 12 installation diagram Kelvinator heat pump hot water system isolating and non return valve pressure limiting valve (600kPa) may be required if pressure exceeds 600kPa cold water expansion control valve (700kPa) may be required refer to local plumbing guidelines relief valve outlet relief valve thermostat d ms) element g earth earth terminal m eter uit wiring terminal block neutral terminal conduit adaptor goes in here and locking ring holds it Note: terminal block may differ slightly depending on model. return active terminal return inlet flow flow be o g drain Kelvinator heat pump hot water system installation diagram 13 Electrical connection recommended size of the conduit to the heat pump is 25mm due to the number and size of the cables required to connect to the hot water system. A junction box or tee piece will need to be installed in order for one conduit to go to the heat pump and one to the storage tank. The storage tank has provision for a 20mm conduit adapter and a 25mm to 20mm reducer may need to be installed at the junction box or tee piece. It is recommended that an isolator be installed that can disconnect each power supply to the heat pump simultaneously, to assist in maintenance and shut down of the hot water system, this however, is not mandatory. Electrical wiring The heat pump hot water system must be installed in accordance with the AS/NZS 3000 wiring rules, the local electrical authority regulations and any other applicable standards. The pipe work, storage tank and heat pump are to be properly connected to the earthing system of the premises in accordance with AS/NZS 3000. The fixed wiring must be protected by insulating sleeving with the appropriate temperature rating and a means for disconnection must be incorporated into the wiring. The heat pump hot water system has the capability to be wired on a standard continuous power supply or with an additional off-peak supply if this is available at the premises. The heat pump requires a continuous power supply in both conditions in order to power the electronics that control the heat pump, to ensure it has freeze protection and to allow the auxiliary heating boost function to operate at any time of the day. The continuous supply cable must be capable of handling the current required to power the 3.6kW element in the storage tank. Depending on the wiring configuration, two or three cables will be wired to the heat pump. The power supply cable(s) will be run from the switchboard to the heat pump whilst the storage tank heater cable will be run between the storage tank and the heat pump. All cables will need to pass through a junction box, tee piece or isolator in order to branch off to their separate locations. If this heat pump hot water system is replacing an existing electric hot water system, a power supply cable may already be available for use. An additional active wire may need to be run from the switchboard as required in order to give the heat pump a continuous or an off-peak power supply. For safety reasons it is recommended that the wiring of the heat pump and storage tank be completed first before the cables are wired to the switchboard. If you are replacing an existing electric hot water system and re-using the existing cable, ensure that the power supply to this cable is isolated or disconnected at the switchboard. warning In order to avoid a hazard due to inadvertent resetting of the heat pump's protective cut-outs, the continuous supply must not be supplied through an external switching device such as a timer, or connected to a circuit that is regularly switched on and off by the utility. Wiring the heat pump If an off-peak power supply is connected to the heat pump, it will only operate its automatic heating function when the off-peak power supply becomes available. The heat pump has been designed to operate on extended off-peak which is available up to 18 hours of the day compared to the standard off-peak which is available only 8 hours. The off-peak power supply cable must be capable of handling the current required to operate the 1.95kW compressor circuit of the heat pump. All cables are to be passed through the cable clamp inside the terminal box and the clamp securely fastened so that if the conduit or cables are pulled, no stress is placed on the terminal connections. For safety reasons, all earths are to be connected first and wired to the G terminal. The continuous power supply input and the storage tank heater output cables must both be capable of handling the current draw of the 3.6kW element. The active wire of the continuous supply input must be wired to the “HL” terminal and the neutral wire to the HN terminal. Note: Please refer to the AS/NZS 3008 standard for the current carrying capacity of the cables to be used to ensure that they are capable of handling the current draw of the heat pump in the conditions that they are to be installed in. red blue white black red XP10 black The active wire of the storage tank heater output cable is to be wired to the L1 terminal and the neutral wire to the N1 terminal. When the cables are run externally, they are to be installed in conduit in order to provide mechanical protection. The XS10 T5 installation on continuous only * For phase, install jumper leads between compressor supply input and continuous supply input terminals as per diagram. XT2 temp sensor in water tank please connect with the attached T5 temp. sensor * * N2 compressor circuit supply input 220-240V~ 50Hz L2 G N1 L1 HN HL 14 electrical connection Kelvinator heat pump hot water systems system connect to off-peak or continuous supply common earth terminal heater line output continuous supply input 220-240V~ 50Hz Electrical connection Wiring the heat pump on a continuous power supply only: Ø2.5mm 150mm If the heat pump is to be wired to a continuous power supply only, the jumper leads supplied with the heat pump are to be installed. The red jumper lead is to be wired between terminals HL and L2. The black jumper lead is to be wired between terminals HN and N2. This will provide power to the compressor circuit of the heat pump and is shown in the diagram below. active (red) neutral (black) earth green/yellow continuous supply input storage tank heater output Wiring the heat pump with an off-peak power supply: If the heat pump is to be wired with an off peak power supply, there are a number of ways that this can be achieved. The off peak power supply active wire is always to be wired to terminal L2, however the off peak power supply cable could be a single active wire, or have a neutral and an earth wire. The neutral wire, if available, would be wired to terminal N2 however in the case of the having a single active wire, the black jumper lead will need to be installed between terminals HN and N2. These two off peak wiring configurations are shown in the diagram. Off peak wiring configuration 1. Off peak wiring configuration 2. active (red) neutral (black) earth green/yellow continuous supply input storage tank heater output off peak supply input If the heat pump is replacing an electric hot water system that has an off peak power supply cable, another alternative is running a single active cable for the continuous power supply from the switchboard. In this case the black jumper lead will also be installed between terminals HN and N2 and the wiring configuration will look similar to the “off-peak wiring configuration 1" in the diagram. Since the continuous power supply would be using the off-peak supply cable’s neutral, it must be capable of handling the current drawn by the 3.6kW heating element. If in doubt, run a cable from the switchboard with an adequately sized active and a neutral. Note: The two operating modes of the heat pump, Automatic mode and Electric heating manual mode will never operate at the same time. Therefore if you are using a shared neutral for the continuous and off peak power supplies, the maximum current flowing through the neutral will be achieved when the heat pump is in Electric heating manual mode and powering the 3.6kW element in the storage tank. active (red) neutral (black) earth green/yellow continuous supply input storage tank heater output off peak supply input Kelvinator heat pump hot water system electrical connection 15 Electrical connection Heat pump fuse rating Wiring the hot water system to the switchboard: There is a 5A 250V T5AL 20mm glass cylinder type fuse located on the printed circuit board of the heat pump. The hot water system is required to be connected to the earthing system of the premises and to the earth stake. Each earth wire is to be wired to the earthing terminal inside the switchboard. The active wire of each power supply to the heat pump is required to be connected to an appropriately rated and labelled circuit breaker and the circuit breakers must be located next to each other. The neutral wires must be connected to the unprotected neutral bar. Wiring the hot water storage tank: The 20mm conduit adapter is to be inserted into the 20mm cut-out provided and the locking ring screwed down to hold the conduit firmly in place. The earth wire is to be wired to the earthing terminal on the bottom left hand side of the terminal block. The active is to be wired to terminal “A1” and the neutral to terminal “N” of the wiring terminal block. thermostat Electrical testing of the heat pump hot water system Once the hot water system has been filled with water, the following mandatory tests are required to be completed as per the AS/NZS 3000 Australian Standards: a) Continuity of the earthing system b) Insulation resistance c)Polarity d) Correct circuit connections e) Verification of impedance required for automatic disconnection of supply Note: The heat pump is required to be electrically disconnected during the insulation resistance testing to prevent damage to its electronics. element earth wiring terminal block neutral terminal earth terminal conduit adaptor goes in here and locking ring holds it active terminal 16 electrical connection Kelvinator heat pump hot water systems Refer to the AS/NZS 3000 Australian Standard for specific details on how to perform these tests and the acceptable readings that must be obtained. If the electrical installation fails a test, that test and any preceding tests that may have been influenced by the fault indicated shall be repeated after the fault has been rectified. Temperature sensor connection The heat pump requires feedback of the water temperature inside the storage tank in order to determine when it needs to operate. To achieve this the temperature sensor (supplied with the heat pump) is required to be run between the heat pump and the storage tank. It is recommended that the sensor cable be neatly cable tied to the conduit or pipe work that runs between the storage tank and heat pump. Any excess cable should be neatly tied in a loop and kept out of the way. However, if it is a possibility that the sensor cable could become damaged during the life of the hot water system, it is recommended that it be protected by installation in a conduit or similar protective means. Installing the temperature sensor in the storage tank The copper end of the sensor cable is the temperature sensing device and is to be installed in the sensor pocket located at the “return” connection on the storage tank. When inserting the sensor into the sensor pocket, ensure that it is inserted all the way into the pocket and reaches the end. Install the plug and fix the clamp to the sensor pocket using the screws provided. This will prevent the temperature sensor from being pulled out of the pocket and seals it from the outside environment. Connecting the sensor cable at the heat pump Inside the heat pump’s terminal box is a female plug socket that the male plug end of the sensor cable plugs into. Push the male plug into the female socket until it clicks into place. return Kelvinator heat pump hot water system temperature sensor connection 17 Commissioning Commissioning must only be commenced once the installation has been completed according to the relevant Australian standards and the instructions in this manual. Confirm the following before operation: • The heat pump has been installed correctly • Air inlet and outlet of heat pump are free of obstacles • Relief valve(s) installed correctly • Drainage piping installed correctly • Supplied tempering valve is installed correctly • All water connections are correct • Piping insulation has been installed • Inlet valve is fully open 3. Once the heat pump has stopped and the tank is up to temperature, drain some water off using a hot tap inside and then operate the auxiliary boost button. Monitor and confirm the operation of the tank element and thermostat. 4. Once the hot water system is up to temperature, check that hot water is available to all hot taps or fixtures in the house and there is sufficient flow or pressure. Ensure that any fixtures designed primarily for purposes of personal hygiene do not have hot water above 50°C coming from them and adjust the tempering valve as necessary. 5. Clean any filters that are installed in the water system of the premises or at the individual fixtures as they may have become blocked by debris during the installation and commissioning of the hot water system. • Water is not leaking from the hot water system • Air has been bled from the storage tank and heat pump • Temperature sensor installed correctly in sensor pocket • Electrical cables installed correctly • Wiring configuration is correct • Electrical testing has been completed and satisfactory result obtained • Power supply is either continuous or extended off peak The following steps are to be followed after the installation of the heat pump hot water system to ensure its safety and performance. If the hot water system cannot be setup to perform correctly as specified in this manual, please call the service centre for further instructions (number located in the warranty section of this manual). 1. Turn on the power supply to the hot water system. If it has been installed on an off peak power supply it may need to be temporarily wired to a continuous power supply for commissioning. 2. Allow the heat pump to run and monitor its operation until the water in the storage tank reaches the set point temperature and the heat pump shuts down. This may take a few hours depending on the size of the storage tank and the conditions at the time. Note: If the heap pump does not begin operating after a few minutes despite power being supplied to the heat pump and the tank water being cold, the auxillary heating boost button may have accidently been pressed during commissioning or installation whilst the heat pump was powered up. In this case, switch off the power supply (both if connected to seperate continuous and off peak 2 power supply) for 2 minutes, then switch power back on again to reset to normal heat pump operation. After a few minutes the heat pump should start to operate. To force the heat pump to operate, remove the lid on the heat pump and carefully press and hold the two buttons marked "force" and "query" on the printed circuit board. The circulating pump should start and after one minute the heat pump will begin to operate. 18 commissioning Kelvinator heat pump hot water system Now that commissioning has been completed and the heat pump hot water system has been set up to operate correctly, select the correct model number of the storage tank on page 5 of the user manual. Fill out your details, the serial numbers, installation date and any important notes for the customer. The user manual is then to be handed to the customer or left in a suitable location on the premises. If the customer is available they should be instructed on the safe and correct operation of the hot water system. Note: If the heat pump hot water system needs to be drained after commissioning please refer to the maintenance section in the user manual supplied with the heat pump for instructions. Warranty FOR SALES IN AUSTRALIA AND NEW ZEALAND APPLIANCE: HOT WATER SYSTEMS This document sets out the terms and conditions of the product warranties for Electrolux Appliances. It is an important document. Please keep it with your proof of purchase documents in a safe place for future reference should you require service for your Appliance. 1. In this warranty: (a) ‘acceptable quality’ as referred to in clause 10 of this warranty has the same meaning referred to in the ACL; (b) ‘ACL’ means Schedule 2 to the Competition and Consumer Act 2010; (c) ‘Appliance’ means any Electrolux product purchased by you accompanied by this document; (d) ‘ASC’ means Electrolux authorised service centres; (e) ‘Electrolux’ means Electrolux Home Products Pty Ltd of 163 O’Riordan Street, Mascot NSW 2020, ABN 51 004 762 341 in respect of Appliances purchased in Australia and Electrolux (NZ) Limited (collectively ‘Electrolux’) of 3-5 Niall Burgess Road, Mount Wellington, in respect of Appliances purchased in New Zealand; (f) ‘major failure’ as referred to in clause 10 of this warranty has the same meaning referred to in the ACL and includes a situation when an Appliance cannot be repaired or it is uneconomic for Electrolux, at its discretion, to repair an Appliance during the Warranty Period; (g) ‘Warranty Period’ means the Appliance is warranted against manufacturing defects in Australia and in New Zealand for the period of 1 year, following the date of original purchase of the Appliance. Specific components are warranted against manufacturing defects in Australia for the periods listed below if there is evidence provided to Electrolux that the Appliance was installed by a licensed plumber; and in New Zealand if there is evidence that the Appliance was installed according to the Electrolux installation guidelines which can be inspected on the Kelvinator website; • Hot water tank - cylinder 5 years , labour 3 years, parts 1 year • Continuous Gas - Heat Exchanger – parts 10 years, labour 3 years - all others components - parts 3 years, labour 3 years • Heat Pump Refrigerant Sealed System - 2 years parts and labour • Solar Collectors - parts 5 years, labour 3 years, 1 year for all other parts (mounting and connection sets) (h) ‘you’ means the purchaser of the Appliance not having purchased the Appliance for re-sale, and ‘your’ has a corresponding meaning. 2. This warranty only applies to Appliances purchased and used in Australia or New Zealand and used in normal domestic applications and is in addition to (and does not exclude, restrict, or modify in any way) any non-excludable statutory warranties in Australia or New Zealand. 3. During the Warranty Period Electrolux or its ASC will, at no extra charge if your Appliance is readily accessible for service, without special equipment and subject to these terms and conditions, repair or replace any parts which it considers to be defective. Electrolux or its ASC may use remanufactured parts to repair your Appliance. You agree that any replaced Appliances or parts become the property of Electrolux. This warranty does not apply to light globes, batteries, filters or similar perishable parts. 4. Parts and Appliances not supplied by Electrolux are not covered by this warranty. 5. To the extent permitted by law, you will bear the cost of transportation, travel and delivery of the Appliance to and from Electrolux or its ASC. If you reside outside of the service area, you will bear the cost of: (a) travel of an authorised representative; (b) transportation and delivery of the Appliance to and from Electrolux or its ASC. In all instances, unless the Appliance is transported by Electrolux or an Electrolux authorised representative, the Appliance is transported at the owner’s cost and risk while in transit to and from Electrolux or its ASC. 6. Proof of purchase is required before you can make a claim under this warranty. 7. You may not make a claim under this warranty unless the defect claimed is due to faulty or defective parts or workmanship. Electrolux is not liable in the following situations (which are not exhaustive): (a) the Appliance is damaged by: (i) accident (ii) misuse or abuse, including failure to properly maintain or service (iii) normal wear and tear (iv) power surges, electrical storm damage, excessive water pressure, excessive inlet water temperature or incorrect power supply (v) incomplete or improper installation (vi) incorrect, improper or inappropriate operation (vii) insect or vermin infestation (viii) failure to comply with any additional instructions supplied with the Appliance; (ix) quality of water that is not in accordance with the “Water Quality” guidelines in the installation instructions; (b) the Appliance is modified without authority from Electrolux in writing; (c) the Appliance’s serial number or warranty seal has been removed or defaced; (d) the Appliance was serviced or repaired by anyone other than Electrolux, an authorised repairer or ASC. 8. This warranty, the contract to which it relates and the relationship between you and Electrolux are governed by the law applicable where the Appliance was purchased. Where the Appliance was purchased in New Zealand for commercial purposes the Consumer Guarantee Act does not apply. 9. To the extent permitted by law and subject to your non-excludable statutory rights and warranties, Electrolux excludes all warranties and liabilities (other than as contained in this document) including liability for any loss or damage whether direct or indirect arising from your purchase, use or non use of the Appliance. 10. For Appliances and services provided by Electrolux in Australia, the Appliances come with a guarantee that cannot be excluded under the ACL. You are entitled to a replacement or refund for a major failure and for compensation for any other reasonably foreseeable loss or damage. You are also entitled to have the Appliance repaired or replaced if the Appliance fails to be of acceptable quality and the failure does not amount to a major failure. The benefits to you given by this warranty are in addition to your other rights and remedies under a law in relation to the Appliances or services to which the warranty relates. 11. At all times during the Warranty Period, Electrolux shall, at its discretion, determine whether repair, replacement or refund will apply if an Appliance has a valid warranty claim applicable to it. 12. For Appliances and services provided by Electrolux in New Zealand, the Appliances come with a guarantee by Electrolux pursuant to the provisions of the Consumer Guarantees Act, the Sale of Goods Act and the Fair Trading Act. 13. To enquire about claiming under this warranty, please follow these steps: (a) carefully check the operating instructions, user manual and the terms of this warranty; (b) have the model and serial number of the Appliance available; (c) have the proof of purchase (e.g. an invoice) available; (d) telephone the numbers shown below. 14. You accept that if you make a warranty claim, Electrolux and its ASC may exchange information in relation to you to enable Electrolux to meet its obligations under this warranty. Important Notice Before calling for service, please ensure that the steps listed in clause 13 above have been followed. FOR SERVICE or to find the address of your nearest state service centre in Australia PlEASE CAll 13 62 26 For the cost of a local call (Australia only) FOR SERVICE or to find the address of your nearest authorised service centre in New Zealand FREE CAll 0800 10 66 10 (New Zealand only) KHWS_Warr_Aug13 SERVICE AUSTRAlIA ELECTROLUX HOME PRODUCTS www.electrolux.com.au SERVICE NEW ZEAlAND ELECTROLUX (NZ) Limited www.electrolux.co.nz FOR SPARE PARTS or to find the address of your nearest state spare parts centre in Australia PlEASE CAll 1300 666 019 For the cost of a local call (Australia only) FOR SPARE PARTS or to find the address of your nearest state spare parts centre in New Zealand FREE CAll 0800 10 66 20 (New Zealand only) Kelvinator heat pump hot water system warranty 19 If you’d like further information about Kelvinator appliances, please visit your retailer, phone or email our Customer Care team or visit our website. telephone: 13 62 26 fax: 1800 350 067 email:customercare@electrolux.com.au web:www.kelvinator.com.au Kelvinator. We are part of the Electrolux family. Share more of our thinking at www.electrolux.com.au P/No. KHWHPI/2 © 2014 Electrolux Home Products Pty Ltd ABN 51 004 762 341 KMAN_KHWHPIM_Sep14