Giunti e Terminali di Media Tensione CELLPACK

Transcription

Giunti e Terminali di Media Tensione CELLPACK
Medium Voltage
D813 | SAP.Nr. 198693 | 1112
Catalogue 2013
Data, values and illustrations given in this documentation are
correct and reliable according to the current state of
our knowledge. They represent however no obligatory
characteristic warranty. Such a warranty is made only by our
product standards. The user of this product must decide on his
own responsibility on its suitability for the intended application.
Our liability for these products exclusively depends on our
general trading conditions.
Changes in the sense of technical progress and misprint reserved.
© 2013, CELLPACK GmbH. All Rights Reserved.
Safe
connections
www.cellpack.com
2
www.cellpack.com
Medium Voltage 2013
Medium Voltage 2013
Page
Introduction |
Cellpack Technology
4
Cable accessories
for unscreened cables
24
Cable accessories
for screened cables
30
Cable accessories
for paper-insulated cables
70
Cable accessories
for screened cables
according to British Standard
90
Cable accessories for
the industries
102
Accessories
106
Index
136
www.cellpack.com
3
Introduction
Medium Voltage 2013
Cable accessories are indispensable components of a cable network which exert a direct influence
on its quality. The same level of operational safety must be guaranteed for the accessories as
for the cable itself. Due to high operational costs incurred by medium voltage networks, it is
necessary to avoid outages. The safe, quick and easy assembly of cable accessories is therefore
essential for network reliability. Exceptional innovative solutions are thus required to ensure that
excessive demands are not placed on the capabilities of assembly staff. We produce innovative,
high-performance cable accessories for medium voltage networks based on the stress control
system developed by Cellpack.
Cellpack Villmergen | Switzerland
Cellpack Tiengen | Germany
Cellpack Radeberg | Germany
We offer a full range of products for a wide variety of applications using heat shrink, silicone,
slip-on, plug-in and cast resin technologies which comply with the standard requirements for
energy suppliers and the set industrial norms. The system components of all of our cable accessories
are compatible so as to ensure safe and reliable functioning. As a result of intensive testing carried
out in our laboratories, as well as numerous type tests carried out in international test facilities,
we are able to guarantee an operationally reliable conductor connection, an adequate insulation
level and excellent resistance against all environmental influences for all our cable accessories. All
our medium voltage products are tested according to DIN VDE 0278, CENELEC HD 629.1, HD
629.2, IEC 60502-4 and comply with IEEE and BS requirements.
Cellpack Almere Buiten | Netherlands
Cellpack Warschau | Poland
Cellpack Ludres | France
Cellpack Barcelona | Spain
Cellpack Melaka | Malaysia
Cellpack Singapur | Far East
4
www.cellpack.com
Medium Voltage 2013
Removal of the cable insulation and the outer semi-conducting layer when connecting or
terminating medium voltage cables results in damage to the cable structure. In addition to this,
the electric field becomes strongly inhomogeneous at particular points. During this process the
electric field strength value greatly increases, resulting in a risk of partial discharge, breakdown
or spikes.
Stress control influences the strong inhomogeneous field distribution at the cable end so as to
reduce the high field strengths to a non-critical value.
Refractive stress control is the most suitable method for medium voltage cable accessories. It
offers the following significant advantages over other methods:
• Leaner stress control element design, enabling the development of compact solutions which
are very easy to assemble.
• Reduced sensitivity to incorrect positioning or incorrect cable preparation, allowing
compensation for errors made during assembly.
Refractive stress control
Refractive stress control influences the electric field by means of a combination of two insulation
materials having different dielectric strengths. The insulation material with the higher dielectric
constant is placed in the area at which the higher electrical field strength occurs. The use of the
term „refractive“ derives from the fact that the process deflects electric field lines which cross the
surface of these materials at an angle(see Figure 1).
(Fig. 1: Interruption of electric field lines at the point of transition between materials with different dielectric
constants)
www.cellpack.com
5
Cellpack Technologie
Stress control in MV cable accessories
Medium Voltage 2013
Cellpack Technologie
When using the above principle in medium voltage cable accessories, a thin stress control and
insulation layer is placed in the region above the strippable edge of the outer semi-conducting
layer (for cables with plastic insulation), or above the Hochstädter foil or lead sheath (for cables
with paper insulation), or above the core insulation when the cable insulation has been removed.
This layer has a considerably higher dielectric constant (εr) than the insulating material of the
cable itself. This results in a targeted reduction of the original field strength (see Fig. 2).
(Fig. 2: Comparison of lines of equipotentiality in a plastic-insulated cable with the insulation removed, with
and without refractive stress control).
Stress control element (FSE)
In addition to stress control itself, the positioning of the contact surfaces of cable insulation and
accessory during assembly is very significant. Trapped air can result in partial discharge even at
low voltages, particularly in the area of stress control, resulting in the breakdown of the cable
accessory.
In order to avoid these problems, we have developed a stress control element (FSE) made
from a special silicone rubber, manufactured using injection-moulding. This product owes its
uniqueness to its optimised design and to the specific properties of the HTV silicone rubber used.
The dimensions of the cylinder body have been carefully selected to ensure that a single stress
control element size is compatible with a wide range of medium voltage cable cross-sections. The
dimensions of the inner cylindrical area allow the positioning of the FSE on the smallest possible
cross-sectional area, where it expands to the correct size, thus exerting a permanent contact
ressure on the base.
The permanent high elasticity of the silicone ensures that a constant pressure is applied to the
contact surface under all operating conditions. The high gas permeability of the special material
constitutes a significant advantage. As a result of constant pressure on the contact surface,
pockets of air arising during assembly will completely diffuse through the stress control material
within a few minutes (Fig. 3). This protects the cable accessory against partial discharge under all
operating conditions.
(Fig. 3 Disappearance of an air bubble in the gap between the sleeve insulating body and the FSE)
6
www.cellpack.com
Medium Voltage 2013
Cellpack Technologie
Stress control elements can be slid over any cable safely, quickly and easily with the aid of the AH
slip-on auxiliary device patented by Cellpack.
The slip-on auxiliary device has been designed so as to prevent damage to the inner cylindrical
surface of the stress control element during assembly.
www.cellpack.com
7
Medium Voltage 2013
Cellpack Technologie
Hybrid technology
Hybrid technology is a modular system developed
by Cellpack which combines components made
from silicone rubber with high voltage resistant heat
shrink products. This renders our cable accessories
compatible with all existing medium voltage cable
cross-sections and ensures maximum operational
reliability. The full product range comprises plug-in
straight-through and transition joints, indoor and
outdoor terminations for single- and three-core
cables, which comply with the standard requirements
for energy suppliers and the set industrial norms. We
also offer products based on customer specifications.
Advantages
Our hybrid cable accessories offer a high level
of operational safety in addition to the following
advantages:
• Safe, quick and easy installation
• Compact and space-saving
• Unlimited shelf life
• Adaptability
8
www.cellpack.com
Medium Voltage 2013
The main insulation material used in hybrid plug-in straight-through and transition joints consists
of a combination of heat-shrink tubing supplied in telescoped form. The insulation materials are
manufactured from high-performance polymeric materials with appropriate additives. The
resulting joint system can be positioned and heat-shrunk onto the cable cores to be connected
from the park position during assembly safely, quickly and easily.
The dimensions of the tube are selected to ensure a defined insulation wall thickness for the
appropriate voltage level and cable cross-section. Stress control is achieved by slipping the silicone
rubber stress control elements onto the prepared cable end using the patented slip-on auxiliary
device. A special filling tape possessing exceptionally high dielectric strength and oil-resistant
properties is used to restrict the field strength around the connectors and to prevent air pockets.
Assembly is safe, quick and easy, due to the compatibility of all system components.
Diagram of type CHMSV straight-through joint:
Connector
1. 2. Field control tape
3. Joint insulation
4. Stress control element
5. Screen continuity
6. Outer sheath
Cable screen continuity for single-core cables is achieved in accordance with current standards by
means of a copper braid sleeve, which is connected to the copper wire and/or tape screen using
pressure springs. Other types of shielded connections are available upon request. A heat- shrink
tube with integrated hot-melt adhesive developed especially for the outer sheath and possessing
very high mechanical strength guarantees a reliable seal.
www.cellpack.com
9
Cellpack Technologie
Hybrid joint system
Medium Voltage 2013
Hybrid termination system
Cellpack Technologie
Stress control within cable terminations is achieved in the same
way as for the hybrid joint system- by simply slipping the tried
and tested silicone rubber stress control elements onto the cable
end, using the patented slip-on auxiliary device.
A sealing tape- another well-established product- is wrapped
around the cable shielding and the cable lug to provide a reliable
seal. A heat-shrink spreader cap with integrated heat-sealing
adhesive provides a reliable seal for the connector distributor
and the cable sheath in the distribution region of three-core
cables.
The main insulation material used in terminations is heatshrink tubing, which is manufactured from high-performance
tracking resistant polymeric materials. To establish the necessary
creepage distances, highly-elastic shields manufactured from
tracking resistant silicone rubber are installed on the tubing after
shrinking. Once again, the use of the patented slip-on auxiliary
device ensures safe, quick and easy assembly.
Diagram of type CHE termination:
1. Cable lug
2. Seal
3. Stress control element
4. Leakage current-resistant outer tube
5. Leakage current-resistant silicone shield
10
www.cellpack.com
Cellpack Technologie
Medium Voltage 2013
The exceptional hydrophobic properties,
resistance to leakage current and high
elasticity of silicone rubber guarantee
sustained operational safety. All materials
characterised by exceptionally high
resistance to ozone and UV radiation have
undergone decades of rigorous testing
under challenging climatic conditions and
have proven themselves in innumerable
installations all over the world. Standard
hybrid terminations are designed for
challenging climatic conditions and
comply with CENELEC and IEC 60816
requirements.
www.cellpack.com
11
Medium Voltage 2013
Contrax technology
Cellpack Technologie
All primary components of our Contrax technology system are integrated into a single-piece
insulating body. This reduces the number of cable accessory components, greatly simplifying
assembly. Its compact, optimised design reduces the associated assembly, storage and
transportation costs to the energy supplier.
Insulating bodies for joints and terminations are
manufactured from high-voltage resistant silicone
rubber using a controlled injection process. Rigorous
quality control as well as high-voltage component
testing during production ensures the technical
reliability of all our Contrax cable accessories.
Advantages
Our Contrax cable accessories offer a high level of operational safety in addition to the following
advantages:
12
•
•
•
•
•
www.cellpack.com
Safe, quick and easy installation
Systems available for all cross sections
Compact and space-saving
Unlimited shelf life
Adaptability
Medium Voltage 2013
The single-piece insulating body of Contrax plug-in straight-through joints consists of an
inner conductive electrode which acts as a Faraday cage around the connector with the main
insulating layer above it, and an outer semi-conducting layer. Each joint body comes equipped
with an integrated slip-on auxiliary device for easy assembly and the prevention of damage
during installation.
Diagram of CAM joint body:
1. Connector
2. Single-piece insulating body
3. Stress control element
4. Screen continuity
5. Outer sheath
Stress control at the cable end is achieved as above, by simply sliding our tried and tested silicone
rubber stress control element onto the prepared cable using the patented slip-on auxiliary device.
A special feature of the Contrax joint is that the stress control element is also used to control the
electric field on the inner semi-conducting layer of the insulating body at high voltage against the
outer semi-conducting layer of the joint body at earth potential.
Electric field strength and lines of equipotentiality of type CAM Contrax straight-through joints.
www.cellpack.com
13
Cellpack Technologie
Contrax joint system
Medium Voltage 2013
Cellpack Technologie
The resulting lean and compact design of the joint body has proven to be particularly suited
to use in three-core cables, as the joint body can be placed on the prepared core insulation in
park position in a safe and simple process. Cable screen continuity is achieved using a copper
braid sleeve which is easily connected to the copper wire and/or tape screen using highly-elastic
pressure springs. Other types of shielded connections are available to order.
Special outdoor protection systems for Contrax plug-in straight-through joints are based on cast
resin technology, thus ensuring a reliable seal and high mechanical strength.
14
www.cellpack.com
Medium Voltage 2013
Contrax terminations consist of a single-piece insulating body
manufactured from a creepage tracking resistant silicone rubber using
a quality-controlled injection moulding process. The stress control
element and necessary shields are also integrated into the insulating
body. The compact optimised design minimises assembly, storage and
transportation costs to energy suppliers.
The silicone rubber used is characterised by excellent resistance
against ozone and UV radiation, as well as exceptional hydrophobic
properties. Its unique design has undergone years of rigorous testing
under challenging climatic conditions. Contrax terminations are
designed for challenging climatic conditions and thus comply with
CENELEC and IEC 60815 requirements.
Diagram of type CAE termination:
1. Cable lug
2. Seal
3. Single-piece insulating body
with integrated stress control
element
Construction of Contrax terminations
Hydrophobic properties of the silicone used
www.cellpack.com
15
Cellpack Technologie
Contrax termination system
Medium Voltage 2013
Cellpack Technologie
Assembly is carried out in a single-step process, in which the single-piece body is safely, quickly
and easily slid onto the prepared cable end using the patented slip-on auxiliary device.
A silicone spreader cap using special cold-shrink
technology, patented by Cellpack, and silicone tubes
with an integrated slip-on auxiliary device are used in the
distribution region of three-core cable, ensuring simple
and accurate assembly. A special sealing tape provides a
reliable seal at the cable shielding and around the cable
lug.
16
www.cellpack.com
Medium Voltage 2013
Plug-in technology
Cellpack Technologie
Plug-in technology consists of four components- the conductor connection, main insulation, stress
control element and outdoor protection system- which are combined to form a single element.
This integrated system developed by Cellpack maximises the reduction of assembly, storage and
transportation costs to energy suppliers.
Compax and Cellplux plug-in connection technologies are the result of over 5 years of work in
product development and constitute a perfect connection system for medium-voltage networks.
• Can be installed safely, quickly and easily
• Systems available for all cross sections
• Integrated system components
• Compact and space-saving
• Unlimited shelf life
• Tested and approved in
accordance with
CENELEC HD 629.1
Comprehensive quality
control carried out in
accordance with ISO 9001 as
well as electrical component
checks during production
ensure the technical reliability
of all our plug-in cable
accessories.
www.cellpack.com
17
Medium Voltage 2013
Compax plug-in straight-through joint
Cellpack Technologie
This joint has been especially developed for connecting plastic-insulated medium voltage
single-core cables. All system components are compatible to ensure that assembly is extremely
safe, quick and easy.
This innovative integration concept allows
for much of the assembly process, previously
carried out on-site, to be performed under
controlled conditions and subjected to
electrical testing at the Cellpack factory. Only
a few assembly steps remain to be performed
on-site.
Advantages:
•
•
•
•
•
•
•
18
Safe, quick and easy assembly
Only standard tools required
Suitable for use in confined spaces
Products available for all cross sections
Robust design
Reduction in storage and transportation costs
Unlimited shelf-life
www.cellpack.com
Medium Voltage 2013
The insulation materials in the CKM joint are equipped with exceptional electrical and mechanical
properties and are manufactured from high voltage- resistant silicone rubber in a controlled
injection moulding process. Each individual material component has been subjected to years
of extensive electrical and mechanical testing and has proven its reliability over decades of
application.
7
6
1
2
3
4
5
Diagram of type CKM straight-through joint
1. Screw connector
2. Joint insulation
3. Insulating support
4. Stress control element
5. Screen continuity
6. Outer sheath
7. Seal
Integrated screw connector
A unique feature of the Compax connection system is that the insulating body of the joint comes
equipped with a tried and tested integrated screw connection system. This screw connector is
compatible with all cross-sections and has been designed to guarantee a reliable connection for
both copper and aluminium conductors. The optimised design of the contact screws allows the
use of a single standard tool for all cross-sections.
Integrated field control
The CKM joint insulation body comes equipped with the Cellpack refractive stress control system,
a device which has been used time and time again by our customers all over the world. This
permits the reduction of assembly errors due to poor cable preparation or incorrect positioning of
the joint body. Stress control in the connector screw openings is achieved geometrically.
www.cellpack.com
19
Cellpack Technologie
Insulation materials
Medium Voltage 2013
Cellplux plug-in connectors
Cellpack Technologie
Cellplux plug-in cable connection components have been especially developed to connect plasticinsulated medium voltage cables. All system components are compatible to ensure that assembly
is extremely safe, quick and easy.
This innovative integration concept allows for much of the assembly process, previously carried
out on-site, to be performed under controlled conditions and subjected to electrical testing at the
Cellpack factory. Only a few assembly steps remain to be performed on-site.
Advantages:
Cellplux plug-in cable connection components guarantee reliable operational safety and offer the
following advantages:
•
•
•
•
•
•
•
20
High level of operational safety
Safe, quick and easy assembly
Standard tools may be used
Suitable for use in confined spaces
Products available for all cross sections
Robust design
Unlimited shelf life
www.cellpack.com
Medium Voltage 2013
Insulation materials used in Cellplux plug-in cable components possess exceptional electrical and
mechanical properties and are manufactured from high voltage resistant EPDM using a controlled
injection moulding process. Stress control is achieved by means of the silicone stress control
element, offering all the above-mentioned advantages. Each individual material component has
been subjected to years of extensive electrical and mechanical testing and has proven its reliability
over decades of application.
1. 2. 3. 4. 5. 6. 7. 8. Silicone stress control element
Screw-in cable lug with shear bolt screw and integrated bracket
Contact bolts with shear bolt screw
Inner electrode
Main insulation
Shielding
Screw-in insulating supports with capacitive test point
Protective cap
www.cellpack.com
21
Cellpack Technologie
Insulating materials
Medium Voltage 2013
Cellpack Technologie
Screw-in cable lug and screw-in contact bolts
Cellplux plug-in cable components are equipped with a tried
and tested screw-in cable lug system, compatible with all
cross-sections, which has been designed to guarantee reliable
connection for both copper and aluminium conductors. The
optimised design of the contact bolts permits the use of a single
Monventional tool for assembly across the entire range of cross
sections. The shear bolt screw system is also used for CTS screwtype plug-in connection contact bolts connecting the cable
lug to the connecting terminal. This eliminates the possibilty of
errors during assembly.
Stress control
This system is also equipped with Cellpack’s integrated refractive stress control system, which has
a proven track record of reliability. This eliminates the possibility of incorrect cable preparation
and dramatically reduces the number of possible assembly errors.
Protection from exposed electrical parts
Cellplux plug-in cable component shieldingaa is made from conductive EPDM rubber over 3mm
thick. All products have successfully undergone tests for insulation failure detection.
22
www.cellpack.com
Medium Voltage 2013
Quality system
Cellpack Technologie
All production sites have been certified according to ISO 9001, 2008 revision and ISO 14001,
2004 revision.
www.cellpack.com
23
For pros
by pros
24
www.cellpack.com
Medium Voltage 2013
Medium Voltage 2013
Cable accessories for
unscreened cables
Page
Straight-through joints
26
Terminations
28
www.cellpack.com
25
Straight-through joints
Medium Voltage 2013
SMH3MS6
Three-core straight-through joint
for armoured 3-core polymeric cables without semi-conducting layer up to 7.2 kV
Type SMH3MS6 straight-through joints are suitable for three-core plastic-insulated
cables (PVC, PE, XLPE, EPR) with no outer semi-conducting layer. They allow the
connection of cables with different cross sections, conductive materials and structure.
Dimensions
Cable accessories for unscreened cables
L = Length
Characteristics
• Compact dimensions
• Wide cross-section range
• Quick, safe and easy assembly
• Ready for immediate operation
• High mechanical strength
L
mm
Type
Application
• Indoor
• Outdoor
• Underground
• Water
• Installation ducts
• Ductwork
Note
• Connectors not included
max. Ø of connector
mm
U0/U (Um) 3.6/6 (7.2)kV - 3.8/6.6 (7.2)kV
25-70 MS6
850
20
1000
25
SMH3 50-150 MS6
120-300 MS6
1200
40
Appropriate connectors must be ordered separately.
26
www.cellpack.com
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Thick wall heat-shrinkable outer tubing
with hot melt adhesive
• Inner jacket sleeve
• Copper braid tube
• Pressure spring
• Assembly instructions
max. connector length
mm
110
135
150
Nominal cross section
Art.-No.
mm²
25 - 70
50 - 150
120 - 300
145630
145633
145635
Straight-through joints
Medium Voltage 2013
M...MS6
Three-core straight-through joint
for armoured 3-core polymeric cables without semi-conducting layer up to 7.2 kV
Type M.MS6 straight-through joints are suitable for three-core plastic-insulated cables
(PVC, PE, XLPE, EPR) with no outer semi-conducting layer. They allow the connection
of cables with different cross sections, conductive materials and structure. They do
not contain any substances which inhibit paint wetting and are suitable for use in the
automotive industry.
Dimensions
Characteristics
• Quick, safe and easy assembly
• Resistant to chemical agents
• Longitudinally and transversely
watertight
• High mechanical strength
Type
U0/U (Um)
M4 MS6
M5 MS6
M6 MS6
Application
• Indoor
• Outdoor
• Underground
• Water
• Installation ducts
• Ductwork
Note
• Connectors not included
Nominal
L1
L2
D1
D2
D3
Cable-Ø cross section
mm mm mm mm mm
mm²
3.6/6 (7.2)kV - 3.8/6.6
432 384 29
52
550 503.2 40
62
660 600 50
78
(7.2)kV
90
29 - 55
110 42 - 65
145 50 - 78
25 - 70
95 - 120
150 - 240
Scope of delivery
• Distance sleeve
• Hydrolysis resistance PUR type EG
cast-resin, containing the correct
volume ready for mixing. Packed in
practical and easy-to-use two chamber
bags
• Transparent plastic moulds
• Copper braid tube
• Hose clamp
• Fill and air-release funnel
• PVC insulation tape
• Protective gloves
• Assembly instructions
concentric conductor
nominal cross section per conductor
mm²
Art.-No.
25/25 - 50/50
70/70 - 95/95
120/120 - 185/185
124318
124319
124320
Appropriate connectors must be ordered separately.
www.cellpack.com
27
Cable accessories for unscreened cables
L = Length
D = Diameter
Terminations
Medium Voltage 2013
SEEV
Three-core indoor termination
for armoured 3-core polymeric cables without semi-conducting layer up to 7.2 kV
Terminations Type SEEV for indoor applications are suitable to cover armoured
three-core polymeric cables (PVC, PE, XLPE, EPR) without semi-conducting layer.
Dimensions
Cable accessories for unscreened cables
L = Length
Characteristics
• Compact dimensions
• Wide conductor and
cross-section range
• High mechanical strength
• Quick, safe and easy assembly
Application
• Indoor
Note
• Cable lugs not included
L
mm
Type
U0/U (Um) 3.6/6 (7.2)kV - 3.8/6.6 (7.2)kV
16-50
280
70-120
280
SEEV
150-240
280
300-400
280
Appropriate cable lugs must be ordered separately.
28
www.cellpack.com
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Core insulating tubes
(tracking resistant)
• Spreader cap
• Filling tape
• Earthing accessories
• Sealing tape
• Assembly instructions
Nominal cross section
mm²
Art.-No.
16 - 50
70 - 120
150 - 240
300 - 400
145458
145461
145464
171791
Terminations
Medium Voltage 2013
SEEV-F
Three-core outdoor termination
for armoured 3-core polymeric cables without semi-conducting layer up to 7.2 kV
Dimensions
L = Length
Ø S = Diameter of cable shed
Characteristics
• Compact dimensions
• Wide conductor and
cross-section range
• High mechanical strength
• Quick, safe and easy assembly
Type
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Core insulating tubes
(tracking resistant)
• Filling tape
• Silicone sheds
• Earthing accessories
• Sealing tape
• Tracking resistant spreader cap
• Assembly instructions
Application
• Outdoor
Note
• Cable lugs not included
L
mm
U0/U (Um) 3.6/6 (7.2)kV - 3.8/6.6 (7.2)kV
16-50
400
400
SEEV-F 70-120
150-240
400
Appropriate cable lugs must be ordered separately.
Nominal cross section
mm²
ØS
mm
Art.-No.
16 - 50
70 - 120
150 - 240
80
85
85
148152
182390
148153
www.cellpack.com
29
Cable accessories for unscreened cables
Terminations Type SEEV -F for outdoor applications are suitable to cover armoured
three-core polymeric cables (PVC, PE, XLPE, EPR) without semi-conducting layer.
30
www.cellpack.com
Medium Voltage 2013
Medium Voltage 2013
Cable accessories for
screened cables
Page
Straight-through joints for
single-core cables
32
Termination for
single-core cables
37
Straight-through joints for
3-core cables
59
Termination for 3-core cables
63
Scaling the
heights safely
www.cellpack.com
31
Straight-through joints for single-core cables
Medium Voltage 2013
CHMSV
Single-core straight-through joint with screw connector
Cable accessories for screened cables
for all polymeric single-core cables
Type CHMSV straight-through joints are suitable for all three-core plastic-insulated
cables (PVC, PE, XLPE, EPR). They allow the connection of cables with different cross
sections, conductive materials, semi-conducting layers (graphite-coated, removable
or strippable) and screening (copper wire or tape). With screw connector.
Dimensions
Characteristics
• Reliable stress control due to flexible
silicone stress control elements
• For both copper and aluminium
conductors
• For all cables with copper wire or
tape screen
• Wide conductor and
cross-section range
• Quick, safe and easy assembly
• Ready for immediate operation
• Suitable for a wide range of
applications due to innovative
integrated screw connector
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Thick wall heat-shrinkable
insulation tubing
• Thick wall heat-shrinkable outer tubing
with hot melt adhesive
• Silicone stress-control elements
• Copper braid tube
• Pressure springs
• Innovative screw connector with
conductive sheath
• Stress control filling tape (blue)
• Assembly instructions
Tests
• CENELEC HD 629.1
(DIN VDE 0278, part 629-1)
L
mm
Type
Application
• Indoor
• Outdoor
• Underground
• Water
• Installation ducts
• Ductwork
Note
• Incl. Screw connectors
• Joints with a range of Um = 12 kV
must be used for cables of Um = 7.2 kV.
(Check minimum diameter over
conductor insulation).
min. Ø over
conductor insulation
after removal of outer
semi-conducting layer
mm
U0/U (Um) 6/10 (12)kV - 6.35/11 (12)kV
25-95
600
70-150
600
CHMSV 12kV
95-240
600
240-400
650
U0/U (Um) 8.7/15 (17.5)kV
25-95
600
70-150
600
CHMSV 17kV
95-240
600
240-400
700
U0/U (Um) 12/20 (24)kV - 12.7/22 (24)kV
16-95
600
50-150
600
CHMSV 24kV
95-240
600
240-400
700
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
50-150
600
95-240
600
CHMSV 36kV
240-400
700
12.6
14.7
17.3
23.1
Nominal cross section
mm²
12kV
www.cellpack.com
17.5kV
24kV
Art.-No.
36kV
258130
258131
258132
258133
25 - 95
70 - 150
95 - 240
240 - 400
14.7
18.0
19.9
24.0
14.7
17.3
19.9
27.3
20.9
24.2
32.0
Heat-shrinkable straight-through joints, larger cross section on request
32
L = Length
258135
258136
258137
258138
25 - 95
70 - 150
95 - 240
240 - 400
258140
258141
258142
258143
16 - 95
50 - 150
95 - 240
240 - 400
50 - 150
95 - 240
240 - 400
258144
258145
258146
Straight-through joints for single-core cables
Medium Voltage 2013
CHM
Single-core straight-through joint
for all polymeric single-core cables
Type CHM straight-through joints are suitable for all single-core plastic-insulated
cables (PVC, PE, XLPE, EPR). They allow the connection of cables with different cross
sections, conductive materials, semi-conducting layers (graphite-coated, removable or
strippable) and screening (copper wire or tape). Suitable for compression connectors.
Dimensions
Characteristics
• Reliable stress control due to flexible
silicone stress control elements
• For all cables with copper wire or
tape screen
• Wide conductor and
cross-section range
• Quick, safe and easy assembly
• Ready for immediate operation
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Thick wall heat-shrinkable
insulation tubing
• Thick wall heat-shrinkable outer tubing
with hot melt adhesive
• Silicone stress-control elements
• Copper braid tube
• Pressure springs
• Stress control filling tape (blue)
• Assembly instructions
Tests
• CENELEC HD 629.1
(DIN VDE 0278, part 629-1)
www.cellpack.com
33
Cable accessories for screened cables
Application
• Indoor
• Outdoor
• Underground
• Water
• Installation ducts
• Ductwork
Note
• Compression connectors not included
• Joints with a range of Um = 12 kV
must be used for cables of Um = 7.2 kV.
(Check minimum diameter over
conductor insulation).
L = Length
Straight-through joints for single-core cables
min. Ø over
conductor
max.
insulation
max. Ø of
L
connector
after removal connector
mm
length
of outer semimm
mm
conducting
layer mm
Cable accessories for screened cables
Type
U0/U (Um) 6/10 (12)kV - 6.35/11 (12)kV
10-25
650
9.9
35-95
650
12.6
95-240
650
17.3
CHM 12KV 150-300
700
19.9
300-400
700
23.1
500-800
850
27.3
800-1000 850
36.8
U0/U (Um) 8.7/15 (17.5)kV
35-95
650
12.6
70-240
650
17.3
CHM 17KV 240-400
700
23.1
400-630
850
27.3
630-1000 850
36.8
U0/U (Um) 12/20 (24)kV - 12.7/22 (24)kV
10-35
650
12.6
50-150
650
17.3
70-240
700
19.9
CHM 24KV
150-300
700
23.1
400-630
850
27.3
630-1000 850
36.8
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
35-70
650
19.9
50-150
700
23.1
700
27.3
CHM 36KV 150-300
300-500
700
27.3
500-800
850
36.8
16
25
32
40
40
60
60
90
135
145
200
200
360
360
25
32
40
60
60
135
145
200
360
360
20
25
32
40
60
60
100
135
145
200
360
360
20
25
38
45
60
110
135
200
200
360
Armour continuity kit must be ordered separately.
Appropriate compression connector must be ordered separately.
34
www.cellpack.com
Medium Voltage 2013
Nominal cross section
mm²
Art.-No.
12kV
17.5kV
24kV
36kV
194072
194073
194074
194075
194076
194077
194078
10 - 25
35 - 95
95 - 240
150 - 300
300 - 400
500 - 800
800 - 1000
194079
194080
194082
194083
194085
35 - 95
70 - 240
240 - 400
400 - 630
630 - 1000
193339
193370
194086
194087
194088
194089
10 - 35
50 - 150
70 - 240
150 - 300
400 - 630
630 - 1000
35 - 70
50 - 150
150 - 300
300 - 500
500 - 800
194090
194091
194092
194093
194094
Straight-through joints for single-core cables
Medium Voltage 2013
CAM-S
Single-core straight-through joint
for all polymeric single-core cables
Characteristics
• Reliable stress control due to flexible
silicone stress control elements
• Wide conductor and
cross-section range
• Ready for immediate operation
• Silicone slip-on components for quick,
safe and easy assembly
Application
• Indoor
• Outdoor
• Underground
• Water
• Installation ducts
• Ductwork
Note
• Compression connectors not included
• Joints with a range of Um = 12 kV
must be used for cables of
Um = 7.2 kV. (Check minimum
diameter over conductor insulation).
min. Ø over conductor
insulation after
Type
removal of outer semiconducting layer mm
U0/U (Um) 6/10 (12)kV - 6.35/11 (12)kV
25-95
700
12.6
CAM-S 12kV
50-240
700
14.7
150-400
700
19.9
U0/U (Um) 12/20 (24)kV - 12.7/22 (24)kV
16-120
700
14.7
CAM-S 24kV
70-240
700
19.9
L
mm
max.
connector
length
mm
160
160
160
Dimensions
L = Length
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Thick wall heat-shrinkable outer tubing
with hot melt adhesive
• Silicone stress-control elements
• Silicone joint body with integrated
semi-conducting layer
(individually tested)
• Copper braid tube
• Pressure springs
• Semi-conducting tape
• Assembly instructions
Tests
• CENELEC HD 629.1
(DIN VDE 0278, part 629-1)
Nominal cross section
mm²
12kV
201385
201386
201388
25 - 95
50 - 240
150 - 400
160
160
Art.-No.
24kV
16 - 120
70 - 240
201393
201395
Appropriate compression connector must be ordered separately.
www.cellpack.com
35
Cable accessories for screened cables
Type CAM-S straight-through joints are suitable for all single-core plastic-insulated
cables (PVC, PE, XLPE, EPR). They allow the connection of cables with different cross
sections, conductive materials, semi-conducting layers (graphite-coated, removable
or strippable) and screening (wire or tape screen). Suitable for compression
connectors.
Straight-through joints for single-core cables
Medium Voltage 2013
CKM
Single-core straight-through joint with screw connector
for all polymeric single-core cables
Type CKM straight-through joints are suitable for all single-core plastic-insulated
cables (PVC, PE, XLPE, EPR) with different types of semi-conducting layers
(graphite-coated, removable or strippable) and screening (wire or tape screen) up to a
maximum network voltage of 24kV. With screw connectors integrated.
Dimensions
Cable accessories for screened cables
L = Length
H = Heigth
B = Width
Characteristics
• Compact design
• Quick, safe and easy assembly
• With integrated screw connectors
• Ready for immediate operation
• Resistant to alkaline earth elements
• Moisture-resistant
• Corrosion-resistant
• Superior mechanical properties
L
mm
Type
Application
• Indoor
• Underground
• Installation ducts
B
mm
H
mm
U0/U (Um) 12/20 (24)kV - 12.7/22 (24)kV
50-150
470
71
85
CKM 24kV
95-240
470
71
85
36
www.cellpack.com
min. Ø over
conductor insulation
after removal of outer
semi-conducting layer
mm
15.1 - 28.5
19.9 - 32.6
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Double plug
• Joint body with integrated outer
housing, inner semi-conducting layer,
silicon stress-control element and
shear-bolt connector
• Pressure springs
• Padding tape
• Housing cover with integrated seal
• Protective sleeve with slide-on
applicator
• Assembly instructions
Tests
• CENELEC HD 629.1
(DIN VDE 0278, part 629-1)
Nominal cross section
mm²
12kV
17.5kV
24kV
70 - 150
120 - 240
70 - 150
120 - 240
50 - 150
95 - 240
Art.-No.
252101
251713
Termination for single-core cables
Medium Voltage 2013
CHE-I
Single-core indoor termination
for all polymeric single-core cables
Dimensions
Type CHE-I terminations are suitable for all single-core plastic-insulated cables (PVC,
PE, XLPE, EPR) with different types of semi-conducting layers (graphite-coated or
strippable) and screening (copper wire or tape).
L = Length
Ø S = Diameter of
cable sheds
Application
• Indoor
Note
• Cable lugs not included
• 12 kV terminations must be used for
7.2 kV cables (Check minimum
diameter over conductor insulation).
Each unit contains materials for one set
of three terminations.
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• 1 Set for 3 phases
• Tracking-resistant heat-shrink tubing
• Silicone stress-control elements
• Silicone sheds
• Sealing tape
• Assembly instructions
Tests
• CENELEC HD 629.1
(DIN VDE 0278, part 629-1)
www.cellpack.com
Cable accessories for screened cables
Characteristics
• Flexible silicone stress control elements
ensure reliable stress control under all
operating conditions
• Combination of slip-on and heat-shrink
components
• Wide cross-section range
• Quick, safe and easy assembly
• Ready for immediate operation
37
Cable accessories for screened cables
Termination for single-core cables
min. Ø
Number
over conductor
of
L
insulation after
ØS
Type
sheds
mm removal of outer
mm
per
semi-conducting
phase
layer mm
U0/U (Um) 6/10 (12)kV - 6.35/11 (12)kV
10-25
300
9.9
25-95
300
12.6
95-240
300
17.3
CHE-I 12kV 150-400
300
19.9
240-500
300
23.1
400-800
300
27.3
800-1000 300
36.8
U0/U (Um) 8.7/15 (17.5)kV
10-16
300
9.9
1
80
16-50
300
12.6
1
80
70-240
300
17.3
1
85
CHE-I 17kV 120-300
300
19.9
1
85
185-400
300
23.1
1
85
300-630
300
27.3
1
115
630-1000 300
36.8
1
123
U0/U (Um) 12/20 (24)kV - 12.7/22 (24)kV
10-35
300
12.6
1
85
25-150
300
17.3
1
85
70-240
300
19.9
1
85
CHE-I 24kV
120-300
300
23.1
1
85
240-500
300
27.3
1
115
630-1000 300
36.8
1
123
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
35-70
500
19.9
2
85
50-150
500
23.1
2
85
CHE-I 36kV
150-400
500
27.3
2
115
500-800
500
36.8
2
123
Medium Voltage 2013
Nominal cross section
mm²
12kV
www.cellpack.com
24kV
36kV
193414
193416
194017
194018
194019
194030
194031
10 - 25
25 - 95
95 - 240
150 - 400
240 - 500
400 - 800
800 - 1000
Appropriate cable lugs must be ordered separately.
Type EGA earthing kit for cables with tape screen must be ordered separately.
38
17.5kV
Art.-No.
194032
194033
194034
194035
194036
194037
194038
10 - 16
16 - 50
70 - 240
120 - 300
185 - 400
300 - 630
630 - 1000
194039
194040
194041
194042
194043
194044
10 - 35
25 - 150
70 - 240
120 - 300
240 - 500
630 - 1000
35 - 70
50 - 150
150 - 400
500 - 800
194045
194046
194047
194048
Termination for single-core cables
Medium Voltage 2013
CHE-F
Single-core outdoor termination
for all polymeric single-core cables
Dimensions
Type CHE-F terminations are suitable for all single-core plastic-insulated cables (PVC,
PE, XLPE, EPR) with different types of semi-conducting layers (graphite-coated or
strippable) and screening (copper wire or tape).
L = Length
Ø S = Diameter of
cable sheds
Application
• Outdoor
Note
• Cable lugs not included
• 12 kV terminations must be used for
7.2 kV cables (Check minimum
diameter over conductor insulation).
Each unit contains materials for one set
of three terminations.
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• 1 Set for 3 phases
• Tracking-resistant heat-shrink tubing
• Silicone stress-control elements
• Silicone sheds
• Sealing tape
• Assembly instructions
Tests
• CENELEC HD 629.1
(DIN VDE 0278, part 629-1)
www.cellpack.com
Cable accessories for screened cables
Characteristics
• Flexible silicone stress control elements
ensure reliable stress control under all
operating conditions
• Combination of slip-on and heat-shrink
components
• Wide cross-section range
• Quick, safe and easy assembly
• Ready for immediate operation
39
Cable accessories for screened cables
Termination for single-core cables
min. Ø
over conductor Number
L
insulation after of sheds Ø S
Type
mm removal of outer
per
mm
semi-conducting phase
layer mm
U0/U (Um) 6/10 (12)kV - 6.35/11 (12)kV
10-25
300
9.9
1
80
25-95
300
12.6
1
80
95-240
300
17.3
1
85
CHE-F 12kV 150-400
300
19.9
1
85
240-500
300
23.1
1
85
400-800
300
27.3
1
115
800-1000
300
36.8
1
123
U0/U (Um) 8.7/15 (17.5)kV
10-16
500
9.9
2
80
16-50
500
12.6
2
80
70-240
500
17.3
2
85
CHE-F 17kV 120-300
500
19.9
2
85
185-400
500
23.1
2
85
300-630
500
27.3
2
115
630-1000
500
36.8
2
123
U0/U (Um) 12/20 (24)kV - 12.7/22 (24)kV
10-35
500
12.6
3
85
25-150
500
17.3
3
85
70-240
500
19.9
3
85
CHE-F 24kV
120-300
500
23.1
3
85
240-500
500
27.3
3
115
630-1000
500
36.8
3
123
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
35-70
700
19.9
4
85
50-150
700
23.1
4
85
CHE-F 36kV
150-400
700
27.3
4
115
500-800
700
36.8
4
123
Medium Voltage 2013
Nominal cross section
mm²
12kV
www.cellpack.com
24KV
36kV
194049
194050
194051
194052
194053
194054
194055
10 - 25
25 - 95
95 - 240
150 - 400
240 - 500
400 - 8000
800 - 1000
Appropriate cable lugs must be ordered separately.
Type EGA earthing kit for cables with tape screen must be ordered separately.
40
17.5kV
Art.-No.
194056
194057
194058
194059
194061
194062
194063
10 - 16
16 - 50
70 - 240
120 - 300
185 - 400
300 - 630
630 - 1000
193372
193374
194064
194065
194066
194067
10 - 35
25 - 150
70 - 240
120 - 300
240 - 500
630 - 1000
35 - 70
50 - 150
150 - 400
500 - 800
194068
194069
194070
194071
Termination for single-core cables
Medium Voltage 2013
CAESK-I
Single-core indoor termination with screw cable lugs
for all polymeric single-core cables
Dimensions
Type CAESK-I terminations are suitable for all single-core plastic-insulated cables
(PVC, PE, XLPE, EPR) with different types of semi-conducting layers (graphite-coated
or strippable) and screening (wire or tape screen). With screw cable lug.
Characteristics
• Wide cross-section range
• Silicone slip-on components for quick,
safe and easy assembly
• Ready for immediate operation
Application
• Indoor
Note
• Incl. Screw cable lugs
• 12 kV terminations must be used for
7.2 kV cables (Check minimum
diameter over conductor insulation).
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• 3 one-piece slip-on silicone
terminations with integrated stress
control element
• Silicone tube
• Sealing tape
• Screw cable lug for main conductor
• Assembly instructions
Tests
• CENELEC HD 629.1
(DIN VDE 0278, part 629-1)
min. Ø
Nominal cross section
Number
over conductor
mm²
of
L
insulation after
ØS
Type
sheds
mm removal of outer
mm
per
semi-conducting
12kV
17.5kV
24kV
36kV
phase
layer mm
U0/U (Um) 6/10 (12)kV - 6.35/11 (12)kV
95-150
310
17.3
1
87 95 - 150
150-240 330
19.9
1
90 150 - 240
CAESK-I 12kV
300-400 340
26.6
1
93 300 - 400
500-630 360
32.3
1
97 500 - 630
U0/U (Um) 8.7/15 (17.5)kV
50-95
310
17.3
1
87
50 - 95
95-150
310
19.9
1
90
95 - 150
CAESK-I 17kV 150-240 330
23.1
1
93
150 - 240
240-400 340
27.3
1
97
240 - 400
400-500 360
32.3
1
97
400 - 500
U0/U (Um) 12/20 (24)kV - 12.7/22 (24)kV
35-95
310
17.3
1
87
35 - 95
70-150
310
19.9
1
90
70 - 150
CAESK-I 24kV 120-240 330
23.1
1
90
120 - 240
240-400 340
27.3
1
97
240 - 400
400-500 360
32.3
1
97
400 - 500
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
16-95
360
20.9
4
93
16 - 95
70-150
360
24.2
4
93
70 - 150
CAESK-I 36kV
120-240 380
28.6
4
97
120 - 240
240-300 390
32.3
4
97
240 - 300
Art.-No.
289945
289947
289948
289949
289950
289951
289952
289953
289954
289955
289956
289957
289958
289959
289960
289961
289962
289963
Type EGA earthing kit for cables with tape screen must be ordered separately.
www.cellpack.com
41
Cable accessories for screened cables
L = Length
Ø S = Diameter
of cable sheds
Termination for single-core cables
Medium Voltage 2013
CAE-I
Single-core indoor termination
for all polymeric single-core cables
Type CAE-I terminations are suitable for all single-core plastic-insulated cables (PVC,
PE, XLPE, EPR) with different types of semi-conducting layers (graphite-coated or
strippable) and screening (wire or tape screen). Suitable for compression cable lugs.
Dimensions
Cable accessories for screened cables
L = Length
Ø S = Diameter of
cable sheds
Characteristics
• Wide cross-section range
• Silicone slip-on components for quick,
safe and easy assembly
• Ready for immediate operation
Type
U0/U (Um)
CAE-I 12kV
U0/U (Um)
CAE-I 17kV
U0/U (Um)
CAE-I 24kV
U0/U (Um)
CAE-I 36kV
Application
• Indoor
Note
• Compression cable lugs not included
• 12 kV terminations must be used for
7.2 kV cables (Check minimum
diameter over conductor insulation).
min. Ø
over conductor
L
insulation after
mm
removal of outer
semi-conducting
layer mm
6/10 (12)kV - 6.35/11 (12)kV
95-240
270
17.3
150-400
270
19.9
240-500
270
23.1
300-800
270
27.3
8.7/15 (17.5)kV
50-185
270
17.3
95-240
270
19.9
150-400
270
23.1
240-630
270
27.3
12/20 (24)kV - 12.7/22 (24)kV
35-120
270
17.3
70-240
270
19.9
120-400
270
23.1
240-630
270
27.3
18/30 (36)kV - 19/33 (36)kV
16-95
325
19.9
50-240
325
23.1
120-400
325
27.3
Number
of
ØS
sheds
mm
per
phase
www.cellpack.com
Nominal cross section
mm²
12kV
1
1
1
1
87 95 - 240
90 150 - 400
93 240 - 500
97 300 - 800
1
1
1
1
87
90
93
97
1
1
1
1
87
90
93
97
4
4
4
90
93
97
Appropriate cable lugs must be ordered separately.
Accessories for cables with tape screen must be ordered separately.
42
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• 3 one-piece slip-on silicone
terminations with integrated stress
control element
• Sealing tape
• Assembly instructions
Tests
• CENELEC HD 629.1
(DIN VDE 0278, part 629-1)
17.5kV
24kV
Art.-No.
36kV
199151
199152
199154
199155
199157
199158
199159
199160
50 - 185
95 - 240
150 - 400
240 - 630
35 - 120
70 - 240
120 - 400
240 - 630
199162
199163
199164
199165
16 - 95 199166
50 - 240 199167
120 - 400 199168
Termination for single-core cables
Medium Voltage 2013
CAESK-F
Single-core outdoor termination with screw cable lugs
for all polymeric single-core cables
Type CAESK-F terminations are suitable for all single-core plastic-insulated cables
(PVC, PE, XLPE, EPR) with different types of semi-conducting layers (graphite-coated
or strippable) and screening (wire or tape screen). With screw cable lug.
Dimensions
Characteristics
• Wide cross-section range
• Silicone slip-on components for quick,
safe and easy assembly
• Ready for immediate operation
Application
• Outdoor
Note
• Incl. Screw cable lugs
• 12 kV terminations must be used for
7.2 kV cables (Check minimum
diameter over conductor insulation).
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• 3 one-piece slip-on silicone
terminations with integrated stress
control element
• Silicone tube
• Sealing tape
• Screw cable lug for main conductor
• Assembly instructions
Tests
• CENELEC HD 629.1
(DIN VDE 0278, part 629-1)
min. Ø
Nominal cross section
over conductor Number
mm²
insulation after
of
L
ØS
Type
removal of
sheds
mm
mm
outer semiper
12kV
17.5kV
24kV
36kV
conducting
phase
layer mm
U0/U (Um) 6/10 (12)kV - 6.35/11 (12)kV
95-150
360
17.3
4
87 95 - 150
150-240 390
19.9
4
90 150 - 240
CAESK-F 12kV
300-400 390
26.6
4
93 300 - 400
500-630 410
32.3
4
97 500 - 630
U0/U (Um) 8.7/15 (17.5)kV
50-95
360
17.3
4
87
50 - 95
95-150
360
19.9
4
90
95 - 150
CAESK-F 17kV 150-240 390
23.1
4
97
150 - 240
240-400 410
27.3
4
97
240 - 400
400-500 410
32.3
4
97
400 - 500
U0/U (Um) 12/20 (24)kV - 12.7/22 (24)kV
35-95
360
17.3
4
87
35 - 95
70-150
360
19.9
4
90
70 - 150
CAESK-F 24kV 120-240 390
23.1
4
93
120 - 240
240-400 410
27.3
4
97
240 - 400
400-500 410
32.3
4
97
400 - 500
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
70-150
470
24.2
5
93
70 - 150
28.6
5
97
120 - 240
CAESK-F 36kV 120-240 500
240-300 500
32.3
5
97
240 - 300
Art.-No.
289894
289897
289898
289899
289900
289901
289902
289903
289904
289905
289906
289907
289908
289909
289910
289911
289912
Type EGA earthing kit for cables with tape screen must be ordered separately.
www.cellpack.com
43
Cable accessories for screened cables
L = Length
Ø S = Diameter
of cable sheds
Termination for single-core cables
Medium Voltage 2013
CAE-F
Single-core outdoor termination
for all polymeric single-core cables
Dimensions
Type CAE-F terminations are suitable for all single-core plastic-insulated cables (PVC,
PE, XLPE, EPR) with different types of semi-conducting layers (graphite-coated or
strippable) and screening (wire or tape screen). Suitable for compression cable lugs.
Cable accessories for screened cables
L = Length
Ø S = Diameter
of cable sheds
Characteristics
• Wide cross-section range
• Silicone slip-on components for quick,
safe and easy assembly
• Ready for immediate operation
Application
• Outdoor
Note
• Compression cable lugs not included
• 12 kV terminations must be used for
7.2 kV cables (Check minimum
diameter over conductor insulation).
min. Ø over conductor Number
insulation after
of
L
ØS
removal of outer
sheds
mm
mm
semi-conducting
per
layer mm
phase
Type
U0/U (Um) 6/10 (12)kV - 6.35/11 (12)kV
95-240
325
17.3
150-400
325
19.9
CAE-F 12kV
240-500
325
23.1
300-800
325
27.3
U0/U (Um) 8.7/15 (17.5)kV
50-185
325
17.3
95-240
325
19.9
CAE-F 17kV
150-400
325
23.1
240-630
325
27.3
U0/U (Um) 12/20 (24)kV - 12.7/22 (24)kV
35-120
325
17.3
70-240
325
19.9
CAE-F 24kV
120-400
325
23.1
240-630
325
27.3
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
50-240
440
23.1
CAE-F 36kV
120-400
440
27.3
www.cellpack.com
Nominal cross section
mm²
12kV
4
4
4
4
87 95 - 240
90 150 - 400
93 240 - 500
97 300 - 800
4
4
4
4
87
90
93
97
4
4
4
4
87
90
93
97
5
5
93
97
Appropriate compression cable lugs must be ordered separately.
Type EGA earthing kit for cables with tape screen must be ordered separately.
44
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• 3 one-piece slip-on silicone
terminations with integrated stress
control element
• Sealing tape
• Assembly instructions
Tests
• CENELEC HD 629.1
(DIN VDE 0278, part 629-1)
17.5kV
24kV
Art.-No.
36kV
199184
199185
199186
199187
199189
199190
199191
199192
50 - 185
95 - 240
150 - 400
240 - 630
35 - 120
70 - 240
120 - 400
240 - 630
199194
199195
199196
199197
50 - 240 199198
120 - 400 199199
Termination for single-core cables
Medium Voltage 2013
CWS 250A/M
Elbow separable cable connector with capacitive measuring point
for all polymeric single-core cables
Cellplux elbow separable cable connectors are suitable for the connection of all plastic-insulated single-core cables (PVC,PE,
XLPE, EPR) with different types of semi-conducting layers (graphite-coated, removable or strippable) and screening (wire or tape
screen) to switching equipment and transformers having plug-in connections for Type A outer cone system terminals
(in accordance with EN 50180, EN 50181 and DIN 47636) up to a maximum network voltage of 24 kV.
Dimensions
L = Length
H = Heigth
B = Width
Type
L
mm
Application
• Indoor
B
mm
U0/U (Um) 6/10 (12)kV - 12.7/22 (24)kV
16-95 M/EGA
176
80
CWS 250A 24kV
70-150 M/EGA
176
80
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Set of 3 separable cable connectors
• Silicone stress-control elements
• Earthing kit
• Assembly accessories
• Screw cable lug for main conductor
• Assembly instructions
Tests
• CENELEC HD 629.1
(DIN VDE 0278, part 629-1)
min. Ø over conductor
insulation after
H
removal of outer
mm
semi-conducting
layer mm
178
178
14.7
19.9
Nominal cross section
mm²
12kV
17.5kV
Cable accessories for screened cables
Characteristics
• with capacitive measuring point
• Individually tested
• Outer semi-conducting layer made of
semi-conductive EPDM provides
protection from exposed
electrical parts.
• Cable sheath insulation fault test may
be performed under voltage
• For both copper and aluminium
conductors
• Quick, safe and easy assembly
• Suitable for a wide range of
applications due to integrated screw
cable lug
Art.-No.
24kV
50 - 95 25 - 95 16 - 95 295167
120 - 150 95 - 150 70 - 150 293792
www.cellpack.com
45
Termination for single-core cables
Medium Voltage 2013
CGS 250A/M
Straight separable cable connector with capacitive measuring point
for all polymeric single-core cables
Cellplux straight separable cable connectors are suitable for the connection of all plastic-insulated single-core cables (PVC,PE,
XLPE, EPR) with different types of semi-conducting layers (graphite-coated or strippable) and screening (wire or tape screen) to
switching equipment and transformers having plug-in connections for Type A outer cone system terminals (in accordance with
EN 50180, EN 50181 and DIN 47636) up to a maximum network voltage of 24 kV.
Dimensions
Cable accessories for screened cables
L = Length
B = Width
Characteristics
• with capacitive measuring point
• Individually tested
• Outer semi-conducting layer made of
semi-conductive EPDM provides
protection from exposed electrical
parts.
• Cable sheath insulation fault test may
be performed under voltage
• For both copper and aluminium
conductors
• Quick, safe and easy assembly
• Suitable for a wide range of
applications due to integrated screw
cable lug
L
mm
Type
Application
• Indoor
B
mm
U0/U (Um) 6/10 (12)kV - 12.7/22 (24)kV
25-95 M/EGA
248
110
CGS 250A 24kV
70-150 M/EGA
248
110
46
www.cellpack.com
Storage conditions/Shelf life
• 12 months
• Unlimited shelf life
Scope of delivery
• Set of 3 separable cable connectors
• Silicone stress-control elements
• Earthing kit
• Assembly accessories
• Screw cable lug for main conductor
• Assembly instructions
Tests
• CENELEC HD 629.1
(DIN VDE 0278, part 629-1)
min. Ø over conductor
insulation after
removal of outer
semi-conducting
layer mm
14.7
19.9
Nominal cross section
mm²
12kV
17.5kV
24kV
50 - 95
120 - 150
25 - 95
95 - 150
25 - 95
70 - 150
Art.-No.
295283
293797
Termination for single-core cables
Medium Voltage 2013
CVS 250A
Connector element up to 24kV
for plug-in cable connector type CWS, CGS
The CVS plug-in connector element is suitable for the connection of two elbow and/or straight separable CWS 250A or CGS
250A connectors. Its dimensions correspond to Type A outer cone systems according to EN 50180, EN 50181 and DIN 47636.
Dimensions
L = Length
Ø = Diameter
Application
• Indoor
Type
U0/U (Um) 6/10 (12)kV - 12.7/22 (24)kV
CVS 24kV
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Set of 3 connectors
• Assembly accessories
• Assembly instructions
Cable accessories for screened cables
Characteristics
• Individually tested
• Easy assembly
• Safe and easy to handle
L
mm
ØD
mm
Art.-No.
136
100
225844
www.cellpack.com
47
Termination for single-core cables
Medium Voltage 2013
CWS 400A
Elbow separable cable connector
for all polymeric single-core cables
Cellplux elbow separable cable connectors are suitable for the connection of all plastic-insulated single-core cables (PVC,PE,
XLPE, EPR) with different types of semi-conducting layers (graphite-coated or strippable) and screening (wire or tape screen) to
switching equipment and transformers having plug-in connections for Type B outer cone system terminals (in accordance with
EN 50180, EN 50181 and DIN 47636) up to a maximum network voltage of 36 kV.
Dimensions
Cable accessories for screened cables
L = Length
H = Heigth
B = Width
Characteristics
• Outer semi-conducting layer made of
semi-conductive EPDM provides
protection from exposed electrical
parts.
• Cable sheath insulation fault test
may be performed under voltage
• For both copper and aluminium
conductors
• Quick, safe and easy assembly
• Suitable for a wide range of
applications due to integrated screw
cable lug
• With capacitive measurement
• Individually tested
Application
• Indoor
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Set of 3 separable cable connectors
• Silicone stress-control elements
• Earthing kit
• Assembly accessories
• Screw cable lug for main conductor
• Assembly instructions
Tests
• CENELEC HD 629.1
(DIN VDE 0278, part 629-1)
min. Ø over
Nominal cross section
conductor
mm²
L
B
H
insulation after
Type
mm mm mm removal of outer
semi-conducting
12kV
17.5kV
24kV
36kV
layer mm
U0/U (Um) 6/10 (12)kV - 12.7/22 (24)kV
25-70 EGA
215 107 250
14.7
50 - 95
25 - 95
25 - 70
CWS 400A 24kV
95-240 EGA
215 107 250
22.0
150 - 240 120 - 240 95 - 240
U0/U (Um) 12/20 (24)kV - 19/33 (36)kV
50-95 EGA
215 107 250
22.0
95 - 95
50 - 95
CWS 400A 36kV
150-240 EGA 215 107 250
30.8
240 - 240 150 - 240
Type EGA earthing kit for cables with tape screen must be ordered separately.
48
www.cellpack.com
Art.-No.
250720
246176
250726
247102
Termination for single-core cables
Medium Voltage 2013
CTS 630A
T-separable cable connector
for all polymeric single-core cables
CTS shear bolt Cellplux separable cable connectors are suitable for connecting all plastic-insulated single-core cables (PVC, PE,
XLPE, EPR) with different types of semi-conducting layers (graphite-coated or strippable) and screening (wire or tape) to
substations and transformers for a maximum system voltage of 36 kV, with plug-type connections for Type C Taper Male Plug
System complying with EN 50180 and EN 50181.
Dimensions
L = Length
H = Heigth
B = Width
Type
L
mm
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Set of 3 separable cable connectors
• Silicone stress-control elements
• Earthing kit
• Assembly accessories
• Screw cable lug for main conductor
• Assembly instructions
Tests
• CENELEC HD 629.1
(DIN VDE 0278, part 629-1)
Application
• Indoor
B
mm
U0/U (Um) 6/10 (12)kV - 12.7/22 (24)kV
25-70 EGA
194
85
194
85
CTS 630A 24kV 95-240 EGA
240-300 EGA
194
85
U0/U (Um) 12/20 (24)kV - 19/33 (36)kV
50-95 EGA
194
85
95-150 EGA
194
85
CTS 630A 36kV
150-240 EGA
194
85
240-400 EGA
194
85
H
mm
min. Ø
over conductor
insulation after
removal of outer
semi-conducting
layer mm
250
250
250
14.7
22
23.7
250
250
250
265
22
22
30.8
31.5
Cable accessories for screened cables
Characteristics
• Individually tested
• Outer semi-conducting layer made of
semi-conductive EPDM provides
protection from exposed electrical
parts.
• Cable sheath insulation fault test may
be performed under voltage
• For both copper and aluminium
conductors
• Quick, safe and easy assembly
• Suitable for a wide range of
applications due to integrated screw
cable lug
• With capacitive measurement
Nominal cross section
mm²
Art.-No.
12kV
17.5kV
24kV
36kV
50 - 95 25 - 95 25 - 70
150 - 240 120 - 240 95 - 240
240 - 400 240 - 300 240 - 300
95 - 95 50 - 95
95 - 240 95 - 150
240 - 240 150 - 240
300 - 400 240 - 400
250711
220775
302732
250715
256010
224826
256328
Type EGA earthing kit for cables with tape screen must be ordered separately.
More T-socket connexions on request
www.cellpack.com
49
Termination for single-core cables
Medium Voltage 2013
CTKS 630A
T-separable coupling connector
for all polymeric single-core cables
The CTKS coupling connectors are suitable for connecting all plastic-insulated single-core cables (PVC, PE, XLPE, EPR) with
different types of semi-conducting layers (graphite-coated or strippable) and screening (wire or tape), to the back of Cellplux
separable cable connectors, model CTS 630 A.
Dimensions
Cable accessories for screened cables
L = Length
B = Width
Characteristics
• Outer semi-conducting layer made of
semi-conductive EPDM provides
protection from exposed electrical
parts.
• Cable sheath insulation fault test may
be performed under voltage
• For both copper and aluminium
conductors
• Quick, safe and easy assembly
• Suitable for a wide range of
applications due to integrated screw
cable lug
• With capacitive measurement
• Individually tested
Application
• Indoor
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Set of 3 coupling elements
• Silicone stress-control elements
• Earthing kit
• Assembly accessories
• Screw cable lug for main conductor
• Assembly instructions
Tests
• CENELEC HD 629.1
(DIN VDE 0278, part 629-1)
min. Ø
Nominal cross section
over conductor
mm²
insulation after
L
B
H
Type
removal of outer
mm mm mm
semi-conducting
12kV
17.5kV
24kV
36kV
layer mm
mm
U0/U (Um) 6/10 (12)kV - 12.7/22 (24)kV
25-70 EGA
290 74 250
14.7
50 - 95 25 - 95 25 - 70
CTKS 630A 24kV
95-240 EGA
290 74 250
22
150 - 240 120 - 240 95 - 240
U0/U (Um) 12/20 (24)kV - 19/33 (36)kV
50-95
310 85 250
22
95 - 95 50 - 95
CTKS 630A 36kV
150-240
310 85 250
30.8
240 - 240 150 - 240
Type EGA earthing kit for cables with tape screen must be ordered separately.
50
www.cellpack.com
Art.-No.
256838
256839
257581
257582
Termination for single-core cables
Medium Voltage 2013
CTKSA
Coupling Surge Arrester
Class 1
The CTKSA Surge Arrester is designed for the protection of encapsulated medium voltage installations with a maximum
operating voltage of 24 kV. Its compact design allows direct connection to double-row CTS 630A screw plugs and complies
with International Standard IEC 60099-4.
Application
• Indoor
Note
• Each unit contains materials for one
set of three plugs
Scope of delivery
• Set of three surge arresters,
electrically tested
• Assembly accessories
• Secondary components
• Assembly instructions
Cable accessories for screened cables
Characteristics
• Individually tested
• Protection from exposed electrical
parts by EPDM outer protection
• Quick, safe and easy assembly
• Protection from exposed electrical
parts
• With capacitive measurement
Maximum ambient temperature: 60°C
System overvoltage
(per unit of MCOV)
(Per unit of Ur)
Time (seconds)
Art.-No.
Nominal leakage current I [kA]
Rated voltage Ur [kV]
Maximum Operating Voltage Uc [kV]
Partial discharge at Uc [pC]
Residual voltage [kV] at:
Steep current impulse 1/20 μs
Switching impulse current 125A
Switching impulse current 500A
Lightning impulse current 8/20 μs
CTKSA
12kV
CTKSA
17kV
CTKSA
19.5kV
CTKSA
24kV
262054
10
15
12.7
<5
262055
10
21
17
<5
262816
10
24
19.5
<5
262056
10
30
24
<5
41.8
28.2
30.1
37.6
58.5
39.4
42.2
52.6
66.9
45.1
48.2
60.2
83.5
56.5
60.3
75.5
www.cellpack.com
51
Termination for single-core cables
Medium Voltage 2013
CTKSA
Coupling Surge Arrester
Class 2
Characteristics
• Individually tested
• Protection from exposed electrical
parts by EPDM outer protection
• Quick, safe and easy assembly
• Protection from exposed electrical
parts
Application
• Indoor
Note
• Each unit contains materials for one
set of three plugs
Scope of delivery
• Set of three surge arresters,
electrically tested
• Assembly accessories
• Secondary components
• Assembly instructions
Maximum ambient temperature: 60°C
(Per unit of Ur)
System overvoltage
(per unit of Uc)
Cable accessories for screened cables
The CTKSA Surge Arrester is designed for the protection of encapsulated medium voltage installations with a maximum
operating voltage of 34 kV. Its compact design allows direct connection to double-row CTS 630A screw plugs and complies
with International Standard IEC 60099-4.
Time (seconds)
CTKSA
34kV
Art.-No.
Nominal leakage current I [kA]
Rated voltage Ur [kV]
Maximum Operating Voltage Uc [kV]
Partial discharge at Uc [pC]
Residual voltage [kV] at:
Steep current impulse 1/20 μs
Switching impulse current 250A
Switching impulse current 500A
Lightning impulse current 8/20 μs
52
www.cellpack.com
301492
10
42
34
<5
120.4
84
89.6
108.4
Termination for single-core cables
Medium Voltage 2013
CIK
Voltage-proof Insulating Cap
The CIK Voltage-proof Insulation Cap provides electrical insulation for Types A 250A and C 630A bushings in encapsulated
substations and transformers up to 36kV, in compliance with EN 50180 and EN 50181.
Note
• Each unit contains materials for one
set of three isulating caps
Scope of delivery
• 3 x Voltage-proof Insulating caps
• Assembly accessories
• Assembly instructions
Cable accessories for screened cables
Characteristics
• Submersible
• Easy assembly
• Protection from exposed
electrical parts
Type
Art.-No.
U0/U (Um) 6/10 (12)kV - 12.7/22 (24)kV
CIK
250A 24kV
U0/U (Um) 6/10 (12)kV - 19/33 (36)kV
CIK
630A 36kV
265023
265024
www.cellpack.com
53
Termination for single-core cables
Medium Voltage 2013
ZS-CTS
Accessory Kit for Type CTS 630A Cellplux separable cable Connectors
The ZS-CTS Accessory Kit is designed for the reinstallation of separable cable connectors in substations and transformers with
bushings for Type C outer cone systems complying with EN 50180, EN 50181. The inclusion of the tried and tested contact pin
with shear bolt in this kit eliminates the possibility of faulty assembly of cable systems.
Cable accessories for screened cables
Application
• Reinstallation of Type CTS
separable Cable Connector
Note
• Each unit contains materials for one
set of three shear bolts
Scope of delivery
• Set of 3 contact pins with shear bolt
• Assembly accessories
• Assembly instructions
Type
Art.-No.
ZS-CTS
257622
54
www.cellpack.com
Medium Voltage 2013
Termination for single-core cables
Mounting Ring
The Mounting Ring is designed to secure CWS 250A and CGS 250A Cellplux separable Cable Connectors to a special bushing
for Type A outer cone systems. The Mounting Ring is simply placed in the prefabricated groove in the cable connector. The two
components may then be mounted on the bushing together.
Scope of delivery
• 1 x Mounting Ring
Cable accessories for screened cables
Characteristics
• Easy assembly
• Secure connection to special
Type A bushing
Type
Art.-No.
Mounting Ring
264366
www.cellpack.com
55
Termination for single-core cables
Medium Voltage 2013
CKS 630A
Coupling connector up to 24kV
for separable cable connector type CTS
The CKS shear bolt coupling connector is intended for the connection of two CTS separable cable connectors up to 24 kV at up
to a rated current of 630 A. The dimensions of the longer outer cone correspond to Type C outer cone systems in accordance
with EN 50180, EN 50181.
Dimensions
L = Length
D = External diameter
Cable accessories for screened cables
Characteristics
• Individually tested
• Easy assembly
• Safe and easy to handle
Application
• Indoor
L
mm
Type
U0/U (Um) 6/10 (12)kV - 12.7/22 (24)kV
CKS 630A 24kV
196.5
56
www.cellpack.com
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Set of 3 coupling elements
• Assembly accessories
• Assembly instructions
L1
mm
L2
mm
D
mm
D1
mm
D2
mm
Art.-No.
61.5
91
70
56
46
224853
Termination for single-core cables
Medium Voltage 2013
CPES
Test and earthing Kit
The Test and Earthing Kit is designed for the establishment of galvanic connections between cable conductors and is compatible
with all Type CTS and CTKS Cellplux T-plugs.
Scope of delivery
• 1 x Test adapter
• 3 x Earthing adapter
• 1 x Case
• Assembly instructions
Cable accessories for screened cables
Application
• Cable testing
• Cable fault location
• Phase compensation
• Earthing for work
Type
Art.-No.
U0/U (Um) 6/10 (12)kV - 19/33 (36)kV
CPES
Test and Earthing Kit
259101
www.cellpack.com
57
Termination for single-core cables
Medium Voltage 2013
CPS
Test-Kit
The Test- Kit is designed for the establishment of galvanic connections between cable conductors and is compatible with all
Type CTS and CTKS Cellplux T-plugs.
Scope of delivery
• 3 x Test adapter
• 1 x Case
• Assembly instructions
Cable accessories for screened cables
Application
• Cable testing
• Cable fault location
• Phase compensation
Type
Art.-No.
U0/U (Um) 6/10 (12)kV - 19/33 (36)kV
CPS
Test-Kit
302227
58
www.cellpack.com
Straight-through joints for 3-core cables
Medium Voltage 2013
CHMSV3
Three-core straight-through joint with screw connector
for all 3-core polymeric cables
Type CHMSV 3 straight-through joints are suitable for connecting three-core
polymeric cable (PVC, PE, XLPE, EPR). They allow the connection of cables with
copper wire screen, with different cross sections, conductor materials,
semi-conducting layers (graphite-coated, removable or strippable). Screw
connectors included.
Dimensions
Characteristics
• Reliable stress control due to flexible
silicone stress control elements
• For both copper and aluminium
conductors
• For all cables with copper-wire screen
• Wide conductor and cross-section
range
• Quick, safe and easy assembly
• Ready for immediate operation
• Suitable for a wide range of
applications due to innovative
integrated screw connector
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Thick wall heat-shrinkable insulation
tubing
• Thick wall heat-shrinkable outer tubing
with hot melt adhesive
• Silicone stress-control element
• Copper braid tape
• Innovative screw connector with
conductive sheath
• Stress control filling tape (blue)
• Screw connector for
copper-wire screen
• Assembly instructions
Type
min. Ø over conductor
insulation after
L
removal of outer
mm
semi-conducting
layer mm
U0/U (Um) 6/10 (12)kV - 6.35/11 (12)kV
25-95
1050
12.6
70-150
1050
14.7
CHMSV 3 12kV
95-240
1100
17.3
240-400 1250
23.1
U0/U (Um) 8.7 /15 (17.5)kV
25-95
1050
14.7
70-150
1050
18
CHMSV 3 17kV
95-240
1100
19.9
240-400 1250
24
U0/U (Um) 12/20 (24)kV - 12.7/22 (24)kV
16-95
1050
14.7
50-150
1050
17.3
CHMSV 3 24kV
95-240
1100
19.9
240-400 1250
27.3
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
50-150
1050
20.9
CHMSV 3 36kV 95-240
1100
24.2
240-400 1250
32
Nominal cross section
mm²
Art.-No.
12kV
17.5kV
24kV
36kV
297348
297350
297260
297358
25 - 95
70 - 150
95 - 240
240 - 400
297349
297351
297310
297360
25 - 95
70 - 150
95 - 240
240 - 400
297433
297352
297104
297361
16 - 95
50 - 150
95 - 240
240 - 400
50 - 150
95 - 240
240 - 400
297353
297311
297362
www.cellpack.com
59
Cable accessories for screened cables
Application
• Indoor
• Outdoor
• Underground
• Water
• Installation ducts
• Ductwork
Note
• Incl. screw connectors
L = Length
Straight-through joints for 3-core cables Medium Voltage 2013
CHMSV3-1
Straight-through joint with screw connector
for connecting from three-core with single-core polymeric cable
Type CHMSV 3-1 straight-through joints are suitable for connecting three-core
polymeric cable with three single-core polymeric cable (PVC, PE, XLPE, EPR). They
allow the connection of cables with copper wire screen, with different cross
sections, conductor materials, semi-conducting layers (graphite-coated, removable
or strippable). Screw connectors included.
Dimensions
Cable accessories for screened cables
L = Length
Characteristics
• Reliable stress control due to flexible
silicone stress control elements
• For both copper and aluminium
conductors
• For all cables with copper-wire screen
• Wide conductor and cross-section
range
• Quick, safe and easy assembly
• Ready for immediate operation
• Suitable for a wide range of
applications due to innovative
integrated screw connector
L
mm
Type
Application
• Indoor
• Outdoor
• Underground
• Water
• Installation ducts
• Ductwork
Note
• Incl. screw connectors
min. Ø over conductor
insulation after
removal of outer
semi-conducting
layer mm
U0/U (Um) 6/10 (12)kV - 6.35/11 (12)kV
25-95
900
70-150
900
CHMSV 3-1 12kV
95-240
900
240-400
1000
U0/U (Um) 8.7/15 (17.5)kV
25-95
900
70-150
900
CHMSV 3-1 17kV
95-240
900
240-400
1000
U0/U (Um) 12/20 (24)kV - 12.7/22 (24)kV
16-95
900
50-150
900
CHMSV 3-1 24kV
95-240
900
240-400
1000
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
50-150
900
CHMSV 3-1 36kV 95-240
900
240-400
1000
60
www.cellpack.com
12.6
14.7
17.3
23.1
17.4
18
19.9
24
14.7
17.3
19.9
27.3
20.9
24.2
32
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Thick wall heat-shrinkable insulation
tubing
• Thick wall heat-shrinkable outer tubing
with hot melt adhesive
• Silicone stress-control element
• Copper braid tape
• Innovative screw connector with
conductive sheath
• Stress control filling tape (blue)
• Screw connector for copper-wire
screen
• Assembly instructions
Nominal cross section
mm²
12kV
17.5kV
24kV
Art.-No.
36kV
297449
297462
297442
297466
25 - 95
70 - 150
95 - 240
240 - 400
297460
297463
297443
297467
25 - 95
70 - 150
95 - 240
240 - 400
16 - 95
50 - 150
95 - 240
240 - 400
297461
297464
297441
297468
50 - 150 297465
95 - 240 297444
240 - 400 297469
Straight-through joints for 3-core cables
Medium Voltage 2013
CHM3
Three-core straight-through joint
for all 3-core polymeric cables
Type CHM3 straight-through joints are suitable for all three-core plastic-insulated
cables (PVC, PE, XLPE, EPR). They allow the connection of cables with different cross
sections, conductive materials, semi-conducting layers (graphite-coated, removable
or strippable) and screen (copper wire or tape). Suitable for compression
connectors.
Dimensions
Characteristics
• Reliable stress control due to flexible
silicone stress control elements
• Wide conductor and cross-section
range
• Quick, safe and easy assembly
• Ready for immediate operation
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Thick wall heat-shrinkable insulation
tubing
• Thick wall heat-shrinkable outer tubing
with hot melt adhesive
• Silicone stress-control element
• Copper braid tube
• Pressure springs
• Stress control filling tape (blue)
• Assembly instructions
min. Ø
Nominal cross section
over conductor
max.
max.
mm²
insulation
Ø of
connector
L
Type
after removal
mm
connector length
of outer semimm
mm
12kV 17.5kV 24kV
36kV
conducting
layer mm
U0/U (Um) 6/10 (12)kV - 6.35/11 (12)kV
10-25
1200
9.9
16
90
10 - 25
35-95
1200
12.6
25
135
35 - 95
CHM3 12kV
95-240
1200
17.3
32
145
95 - 240
150-300
1200
19.9
40
200
150 - 300
U0/U (Um) 8.7/15 (17.5)kV
35-95
1200
12.6
25
135
35 - 95
70-240
1200
17.3
32
145
70 - 240
CHM3 17kV
120-300
1200
19.9
34
150
120 - 300
240-400
1200
23.1
40
200
240 - 400
U0/U (Um) 12/20 (24)kV - 12.7/22 (24)kV
10-35
1200
12.6
20
100
10 - 35
50-150
1200
17.3
25
135
50 - 150
CHM3 24kV
70-240
1200
19.9
32
145
70 - 240
150-300
1200
23.1
40
200
150 - 300
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
35-70
1200
19.9
20
110
35 - 70
1200
23.1
25
135
50 - 150
CHM3 36kV 50-150
150-300
1200
27.3
38
200
150 - 300
Art.-No.
194293
194294
194295
194296
194297
194298
194299
194300
194301
194302
194303
194304
194305
194306
194307
Appropriate compression connectors must be ordered separately.
Armour continuity kit for armoured cable available to order.
www.cellpack.com
61
Cable accessories for screened cables
Application
• Indoor
• Outdoor
• Underground
• Water
• Installation ducts
• Ductwork
Note
• Compression connectors not included
• Joints with a range of Um = 12 kV
must be used for cables of
Um = 7.2 kV. (Check minimum
diameter over conductor insulation).
L = Length
Straight-through joints for 3-core cables Medium Voltage 2013
CAM3-S
Three-core straight-through joint with heat-shrink outer protection
for all 3-core polymeric cables
Cable accessories for screened cables
Dimensions
Type CAM3-S straight-through joints are suitable for all three-core plastic-insulated
cables (PVC, PE, XLPE, EPR). They allow the connection of cables with different cross
sections, conductive materials, semi-conducting layers (graphite-coated, removable or
strippable) and screening (wire or tape screen). Suitable for compression connectors.
Characteristics
• Reliable stress control due to flexible
silicone stress control elements
• Wide conductor and
cross-section range
• Ready for immediate operation
• Quick, safe and easy assembly
Application
• Indoor
• Outdoor
• Underground
• Water
• Installation ducts
• Ductwork
Note
• Compression connectors not included
• Joints with a range of Um = 12 kV
must be used for cables of
Um = 7.2 kV. (Check minimum
diameter over conductor insulation).
L
mm
Type
min. Ø
over conductor
mm
U0/U (Um) 6/10 (12)kV - 12.7/22 (24)kV
16-120
1200
CAM3-S 24kV
70-240
1200
U0/U (Um) 6/10 (12)kV - 6.35/11 (12)kV
50-240
1200
CAM3-S 12kV
150-400
1200
U0/U (Um) 8.7/15 (17.5)kV
35-150
1200
CAM3-S 17kV
95-300
1200
14.7
19.9
160
160
14.7
19.9
160
160
14.7
19.9
160
160
Appropriate compression connectors must be ordered separately.
Armour continuity kit for armoured cable available to order.
62
www.cellpack.com
max.
connector
length
mm
L = Length
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Thick wall heat-shrinkable outer tubing
with hot melt adhesive
• Silicone joint body with integrated
semi-conducting layer
(individually tested)
• Copper braid tube
• Pressure spring
• Lubricant
• Protective gloves
• Silicone stress-control elements
• Assembly instructions
Nominal cross section
mm²
12kV
17.5kV
Art.-No.
24kV
16 - 120 201382
70 - 240 201374
201375
201377
50 - 240
150 - 400
35 - 150
95 - 300
201379
201381
Termination for 3-core cables
Medium Voltage 2013
CHE-3I(A)
Three-core indoor termination
for all 3-core polymeric cables
Type CHE-3I(A) terminations are suitable for all three-core plastic-insulated cables (PVC, PE, XLPE, EPR) with different types of
semi-conducting layers (graphite-coated or strippable) and screening (copper wire or tape).
Dimensions
Characteristics
• Flexible silicone stress control elements
ensure reliable stress control under all
operating conditions
• Combination of slip-on and heat-shrink
components
• Wide cross-section range
• Quick, safe and easy assembly
• Ready for immediate operation
Application
• Indoor
Note
• Cable lugs not included
• 12 kV terminations must be used for
7.2 kV cables (Check minimum
diameter over conductor insulation).
min. Ø over
conductor
L
insulation after
Type
mm
removal of outer
semi-conducting
layer mm
U0/U (Um) 6/10 (12)kV - 6.35/11 (12)kV
10-25
300
9.9
25-95
300
12.6
CHE-3I(A) 12kV
95-240
300
17.3
150-400 300
19.9
U0/U (Um) 8.7/15 (17.5)kV
16-50
300
12.6
70-240
300
17.3
CHE-3I(A) 17kV
150-300 300
19.9
185-400 300
23.1
U0/U (Um) 12/20 (24)kV - 12.7/22 (24)kV
10-35
300
12.6
25-95
300
17.3
CHE-3I(A) 24kV
70-240
300
19.9
120-300 300
23.1
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
35-70
500
19.9
500
23.1
CHE-3I(A) 36kV 50-150
150-400 500
27.3
Number
of
ØS
sheds
mm
per
phase
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Tracking-resistant heat-shrink tubing
• Heat-shrink tube
• Silicone stress-control elements
• Silicone sheds
• Pressure spring
• Silicone stress control element
• Assembly accessories
• Sealing tape
• Assembly instructions
Tests
• CENELEC HD 629.1
(DIN VDE 0278, part 629-1)
Nominal cross section
mm²
12kV
17.5kV
24kV
36kV
146228
146216
146217
146218
10 - 25
25 - 95
95 - 240
150 - 400
1
1
1
1
85
85
85
85
1
1
1
1
85
85
85
85
2
2
2
85
85
115
Art.-No.
195365
171761
171762
171763
16 - 50
70 - 240
150 - 300
185 - 400
10 - 35
25 - 95
70 - 240
120 - 300
146300
146302
146301
146297
35 - 70 146158
50 - 150 146159
150 - 400 146160
Appropriate cable lugs must be ordered separately.
Type EGA earthing kit for cables with tape screen and armouring must be ordered separately.
www.cellpack.com
63
Cable accessories for screened cables
L = Length
Ø S = Diameter of cable shed
Termination for 3-core cables
Medium Voltage 2013
CHE-3F(A)
Three-core outdoor termination
for all 3-core polymeric cables
Type CHE-3F(A) terminations are suitable for all three-core plastic-insulated cables (PVC, PE, XLPE, EPR) with different types of
semi-conducting layers (graphite-coated or strippable) and screening (copper wire or tape).
Dimensions
Cable accessories for screened cables
L = Length
Ø S = Diameter of cable shed
Characteristics
• Flexible silicone stress control elements
ensure reliable stress control under all
operating conditions
• Combination of slip-on and heat-shrink
components
• Wide cross-section range
• Quick, safe and easy assembly
• Ready for immediate operation
Application
• Outdoor
Note
• Cable lugs not included
• 12 kV terminations must be used for
7.2 kV cables (Check minimum
diameter over conductor insulation).
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Spreader cap
• Tracking-resistant heat-shrink tubing
• Silicone stress-control elements
• Silicone sheds
• Sealing tape
• Pressure spring
• Assembly accessories
• Assembly instructions
Tests
• CENELEC HD 629.1
(DIN VDE 0278, part 629-1)
min. Ø
Number
Nominal cross section
over conductor
of
mm²
L
insulation after
ØS
Type
sheds
mm removal of outer
mm
per
12kV 17.5kV 24kV
36kV
semi-conducting
phase
layer mm
U0/U (Um) 6/10 (12)kV - 6.35/11 (12)kV
10-25
300
9.9
1
80
10 - 25
25-95
300
12.6
1
85
25 - 95
CHE-3F(A) 12kV
95-240
300
17.3
1
85 95 - 240
150-400
300
19.9
1
85 150 - 400
U0/U (Um) 8.7/15 (17.5)kV
16-50
500
12.6
2
85
16 - 50
70-240
500
17.3
2
85
70 - 240
CHE-3F(A) 17kV
150-300
500
19.9
2
85
150 - 300
185-400
500
23.1
2
85
185 - 400
U0/U (Um) 12/20 (24)kV - 12.7/22 (24)kV
10-35
500
12.6
3
85
10 - 35
25-95
500
17.3
3
85
25 - 95
CHE-3F(A) 24kV
70-240
500
19.9
3
85
70 - 240
120-300
500
23.1
3
85
120 - 300
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
35-70
700
19.9
4
85
35 - 70
700
23.1
4
85
50 - 150
CHE-3F(A) 36kV 50-150
150-400
700
27.3
4
115
150 - 400
Appropriate cable lugs must be ordered separately.
Type EGA earthing kit for cables with tape screen and armouring must be ordered separately.
64
www.cellpack.com
Art.-No.
146226
146220
146222
146224
195366
171756
171757
146296
146303
146304
146306
146298
146234
146235
146242
Termination for 3-core cables
Medium Voltage 2013
CHE-3I(B)
Three-core indoor termination
for all 3-core polymeric cables
Type CHE-3I(B) terminations are suitable for all three-core plastic-insulated cables (PVC, PE, XLPE, EPR) with different types of
semi-conducting layers (graphite-coated or strippable) and screening (copper wire or tape).
Dimensions
Characteristics
• Flexible silicone stress control elements
ensure reliable stress control under all
operating conditions
• Combination of slip-on and heat-shrink
components
• Wide cross-section range
• Quick, safe and easy assembly
• Ready for immediate operation
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Tracking resistant spreader cap
• Tracking-resistant heat-shrink tubing
• Silicone stress-control elements
• Silicone sheds
• Pressure spring
• Assembly accessories
• Sealing tape
• Assembly instructions
Tests
• CENELEC HD 629.1
(DIN VDE 0278, part 629-1)
Application
• Indoor
Note
• Cable lugs not included
• 12 kV terminations must be used for
7.2 kV cables (Check minimum
diameter over conductor insulation).
min. Ø over
conductor
L
insulation after
Type
mm removal of outer
semi-conducting
layer mm
U0/U (Um) 6/10 (12)kV - 6.35/11 (12)kV
10-25
350
9.9
25-95
350
12.6
CHE-3I(B) 12kV
95-240
350
17.3
150-400
350
19.9
U0/U (Um) 8.7/15 (17.5)kV
25-50
400
12.6
70-240
400
17.3
CHE-3I(B) 17kV
150-300
400
19.9
185-400
400
23.1
U0/U (Um) 12/20 (24)kV - 12.7/22 (24)kV
10-35
500
12.6
25-95
500
17.3
CHE-3I(B) 24kV
70-240
500
19.9
120-400
500
23.1
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
35-70
650
19.9
650
23.1
CHE-3I(B) 36kV 50-150
150-400
650
27.3
Number
of
ØS
sheds
mm
per
phase
Nominal cross section
mm²
12kV
17.5kV
24kV
36kV
184796
173134
173132
180522
10 - 25
25 - 95
95 - 240
150 - 400
182731
182732
182733
182734
25 - 50
70 - 240
150 - 300
185 - 400
1
1
1
1
85
85
85
85
2
2
2
85
85
115
Art.-No.
10 - 35
25 - 95
70 - 240
120 - 400
184797
184798
184799
184800
35 - 70 184801
50 - 150 184802
150 - 400 184803
Appropriate cable lugs must be ordered separately.
Type EGA earthing kit for cables with tape screen must be ordered separately.
www.cellpack.com
65
Cable accessories for screened cables
L = Length
Ø S = Diameter of cable shed
Termination for 3-core cables
Medium Voltage 2013
CHE-3F(B)
Three-core outdoor termination
for all 3-core polymeric cables
Type CHE-3F(B) terminations are suitable for all three-core plastic-insulated cables (PVC, PE, XLPE, EPR) with different types of
semi-conducting layers (graphite-coated or strippable) and screening (copper wire or tape).
Dimensions
Cable accessories for screened cables
L = Length
Ø S = Diameter of cable shed
Characteristics
• Flexible silicone stress control elements
ensure reliable stress control under all
operating conditions
• Combination of slip-on and heat-shrink
components
• Wide cross-section range
• Quick, safe and easy assembly
• Ready for immediate operation
Application
• Outdoor
Note
• Cable lugs not included
• 12 kV terminations must be used for
7.2 kV cables (Check minimum
diameter over conductor insulation).
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Tracking-resistant heat-shrink tubing
• Silicone stress-control elements
• Silicone sheds
• Sealing tape
• Pressure spring
• Assembly accessories
• Tracking resistant spreader cap
• Assembly instructions
Tests
• CENELEC HD 629.1
(DIN VDE 0278, part 629-1)
min. Ø
Number
Nominal cross section
over conductor
of
mm²
L
insulation after
ØS
Type
sheds
mm removal of outer
mm
per
12kV
17.5kV
24kV
36kV
semi-conducting
phase
layer mm
U0/U (Um) 6/10 (12)kV - 6.35/11 (12)kV
10-25
700
9.9
1
80 10 - 25
25-95
700
12.6
1
85 25 - 95
CHE-3F(B) 12kV
95-240
700
17.3
1
85 95 - 240
150-400
700
19.9
1
85 150 - 400
U0/U (Um) 8.7/15 (17.5)kV
25-50
700
12.6
2
85
25 - 50
70-240
700
17.3
2
85
70 - 240
CHE-3F(B) 17kV
150-300
700
20.9
2
85
150 - 300
185-400
700
23.1
2
85
185 - 400
U0/U (Um) 12/20 (24)kV - 12.7/22 (24)kV
10-35
850
12.6
3
85
10 - 35
25-95
850
17.3
3
85
25 - 95
CHE-3F(B) 24kV
70-240
850
20.9
3
85
70 - 240
120-400
850
23.1
3
85
120 - 400
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
35-70
850
22.5
4
85
35 - 70
850
23.1
4
85
50 - 150
CHE-3F(B) 36kV 50-150
150-400
850
27.3
4
115
150 - 400
Appropriate cable lugs must be ordered separately.
Type EGA earthing kit for cables with tape screen must be ordered separately.
66
www.cellpack.com
Art.-No.
184805
184806
184807
184808
182735
182736
182737
182738
184472
184809
184811
184812
184813
184815
184816
Termination for 3-core cables
Medium Voltage 2013
CAE-3I
Three-core indoor termination
for all 3-core polymeric cables
Type CAE-3I terminations are suitable for all three-core plastic-insulated cables (PVC, PE, XLPE, EPR) with different types of
semi-conducting layers (graphite-coated or strippable) and screening (wire or tape screen). Suitable for compression cable lugs.
Dimensions
L = Length
Ø S = Diameter of cable shed
Application
• Indoor
Note
• Compression cable lugs not included
• 12 kV terminations must be used for
7.2 kV cables (Check minimum
diameter over conductor insulation).
min. Ø
over conductor
L
insulation after
Type
mm removal of outer
semi-conducting
layer mm
U0/U (Um) 6/10 (12)kV - 6.35/11 (12)kV
95-240
270
17.3
CAE-3I 12kV
150-400
270
19.9
U0/U (Um) 8.7/15 (17.5)kV
50-185
270
17.3
CAE-3I 17kV 95-240
270
19.9
150-400
270
23.1
U0/U (Um) 12/20 (24)kV - 12.7/22 (24)kV
35-120
270
17.3
CAE-3I 24kV 70-240
270
19.9
120-400
270
23.1
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
16-95
325
19.9
325
23.1
CAE-3I 36kV 50-240
120-400
325
27.3
Number
of
ØS
sheds
mm
per
phase
1
1
87
90
1
1
1
87
90
93
1
1
1
87
90
93
4
4
4
90
93
97
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• 3 one-piece slip-on silicone
terminations with integrated stress
control element
• Silicone tube
• Silicone cold-shrink spreader cap
• Assembly accessories
• Sealing tape
• Assembly instructions
Nominal cross section
mm²
12kV
17.5kV
24kV
Cable accessories for screened cables
Characteristics
• Wide cross-section range
• Silicone slip-on components for quick,
safe and easy assembly
• Ready for immediate operation
Art.-No.
36kV
199170
199171
95 - 240
150 - 400
199173
199174
199175
50 - 185
95 - 240
150 - 400
35 - 120
70 - 240
120 - 400
199177
199178
199179
16 - 95 199180
50 - 240 199182
120 - 400 199181
Appropriate compression cable lugs must be ordered separately.
Type EGA earthing kit for cables with tape screen must be ordered separately.
www.cellpack.com
67
Termination for 3-core cables
Medium Voltage 2013
CAE-3F
Three-core outdoor termination
for all 3-core polymeric cables
Type CAE-3F terminations are suitable for all three-core plastic-insulated cables (PVC, PE, XLPE, EPR) with different types of
semi-conducting layers (graphite-coated or strippable) and screening (wire or tape screen). Suitable for compression cable lugs.
Dimensions
Cable accessories for screened cables
L = Length
Ø S = Diameter of cable shed
Characteristics
• Wide cross-section range
• Silicone slip-on components for quick,
safe and easy assembly
• Ready for immediate operation
min. Ø
over conductor
L
insulation after
Type
mm removal of outer
semi-conducting
layer mm
U0/U (Um) 6/10 (12)kV - 6.35/11 (12)kV
95-240
325
17.3
CAE-3F 12kV
150-400
325
19.9
U0/U (Um) 8.7/15 (17.5)kV
50-185
325
17.3
CAE-3F 17kV 95-240
325
19.9
150-400
325
23.1
U0/U (Um) 12/20 (24)kV - 12.7/22 (24)kV
35-120
325
17.3
CAE-3F 24kV 70-240
325
19.9
120-400
325
23.1
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
50-240
440
23.1
CAE-3F 36kV
120-400
440
27.3
Number
of
ØS
sheds
mm
per
phase
Nominal cross section
mm²
12kV
4
4
87 95 - 240
90 150 - 400
4
4
4
87
87
93
4
4
4
87
90
93
5
5
93
97
Appropriate compression cable lugs must be ordered separately.
Type EGA earthing kit for cables with tape screen must be ordered separately.
68
www.cellpack.com
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• 3 one-piece slip-on silicone
terminations with integrated stress
control element
• Silicone tube
• Silicone cold-shrink spreader cap
• Assembly accessories
• Sealing tape
• Assembly instructions
Application
• Outdoor
Note
• Compression cable lugs not included
• 12 kV terminations must be used for
7.2 kV cables (Check minimum
diameter over conductor insulation).
17.5kV
24kV
Art.-No.
36kV
199201
199202
199204
199205
199206
50 - 185
95 - 240
150 - 400
35 - 120
70 - 240
120 - 400
199208
199209
199210
50 - 240 199211
120 - 400 199212
Termination for 3-core cables
Cable accessories for screened cables
Medium Voltage 2013
www.cellpack.com
69
Medium Voltage 2013
We help you
achieve the
highest standards
70
www.cellpack.com
Medium Voltage 2013
Page
Belted cables
Transition joints 72
Straight-through joints
76
Terminations 77
Cable accessories for
paper-insulated cables
Page
Hoechstaedterkabel
Transition joints 79
Straight-through joints
81
Terminations 82
Three-core single lead sheath cables
Transition joints
84
Straight-through joints 86
Terminations 87
www.cellpack.com
71
Transition joints
Medium Voltage 2013
M...MSPB6
Three-core transition joint
Cable accessories for paper-insulated cables
from belted cable to polymeric cable without external conductive layer
Type M.MSPB6 transition joints are suitable for transitions between paper-insulated
lead cables and three-core cables with plastic insulation (PVC, PE, XLPE, EPR) and no
outer semi-conducting layer. They allow the connection of cables with different cross
Type M.MSPB6 transition joints are suitable for transitions between paper-insulated lead
cables and three-core cables with plastic insulation (PVC, PE, XLPE, EPR) and no outer
semi-conducting layer. They allow the connection of cables with different cross sections,
conductive materials and structure. They do not contain any substances which inhibit
paint wetting and are suitable for use in the automotive industry.
Dimensions
Characteristics
• Quick, safe and easy assembly
• Resistant to chemical agents
• Longitudinally and transversely
watertight
• High mechanical strength
Scope of delivery
• Distance sleeve
• Hydrolysis-resistant PUR type EG
cast-resin, containing the correct
volume ready for mixing
• Transparent plastic moulds
• Spreader cap
• Armour continuity kit
• Fill and air-release funnel
• Heat-shrinkable tubing for sealing
• Assembly accessories
• Assembly instructions
Type
L1
mm
L2
mm
Application
• Indoor
• Outdoor
• Underground
• Water
• Installation ducts
• Ductwork
Note
• Connectors not included
D1
mm
D2
mm
U0/U (Um) 3.6/6 (7.2)kV - 3.8/6.6 (7.2)kV
M4MSPB6
432
384
28.9
52
M5MSPB6
550
503
41.6
62
Appropriate connectors must be ordered separately.
72
www.cellpack.com
L = Length
D = Diameter
D3
mm
Cable-Ø
mm
3x
Nominal cross section per conductor
Polymeric cable
mm²
Art.-No.
90
110
29 - 55
42 - 65
25 - 70
70 - 120
124334
124335
Transition joints
Medium Voltage 2013
CHMPRSV 3-1
Transition joint
with screw connectors, from belted cable to polymeric cables
Type CHMPRSV3-1 hybrid transition joints for transition to three single-core plasticinsulated cables are suitable for both paper-insulated lead cables and Hochstädter
cables up to 17.5 kV. With screw connectors.
Dimensions
Characteristics
• Reliable stress control due to flexible
silicone stress control elements
• Wide cross-section range
• Quick, safe and easy assembly
• Ready for immediate operation
• Suitable for a wide range of
applications due to innovative
integrated screw connector
Type
Application
• Indoor
• Outdoor
• Underground
• Water
• Installation ducts
• Ductwork
Note
• Incl. Screw connectors
min. Ø over conductor
L
insulation after removal of outer
mm
semi-conducting layer mm
U0/U (Um) 6/10 (12)kV - 8.7 /15 (17.5)kV
35-95
1200
70-150
1200
CHMPRSV3-1 17kV
95-240
1200
240-400
1200
12.6
17.3
17.3
23.1
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Spreader cap
• Thick wall heat-shrinkable outer tubing
with hot melt adhesive
• Oil barrier tubing
• Heat-shrink tubing
• Silicone stress-control elements
• Earthing wire
• Copper braid tape
• Pressure spring
• Assembly accessories
• Sealing tape
• Stress control filling tape (blue)
• Fire protection wrap
• Screw connector for copper-wire
screen
• Innovative screw connector with
conductive sheath
• Assembly instructions
Nominal cross section
mm²
12kV
17.5kV
50 - 95
95 - 150
95 - 240
240 - 400
35 - 95
70 - 150
95 - 240
240 - 400
Art.-No.
264988
265205
264769
265501
www.cellpack.com
73
Cable accessories for paper-insulated cables
L = Length
Transition joints
Medium Voltage 2013
CHMPR 3-1
Transition joint
from belted cable to polymeric cables
Type CHMPR3-1 hybrid transition joints for transition to three single-core plasticinsulated cables are suitable for both paper-insulated lead cables and Hochstädter
cables up to 17.5 kV. Padding kits for paper-insulated cables are available for
downwards enlargement of the operational area. Suitable for Compression connectors.
Dimensions
L = Length
Cable accessories for paper-insulated cables
Characteristics
• Reliable stress control due to flexible
silicone stress control elements
• Wide conductor and cross-section
range
• Wide cross-section range
• Quick, safe and easy assembly
• Ready for immediate operation
Application
• Indoor
• Outdoor
• Underground
• Water
• Installation ducts
• Ductwork
Note
• Compression connectors not included
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Spreader cap
• Thick wall heat-shrinkable outer tubing
with hot melt adhesive
• Oil barrier tubing
• Heat-shrink tubing
• Silicone stress-control elements
• Earthing wire
• Copper braid tape
• Pressure spring
• Assembly accessories
• Sealing tape
• Stress control filling tape (blue)
• Fire protection wrap
• Assembly instructions
min. Ø
12 kV
17.5 kV
over conductor
insulation after
L
max.
max.
Nominal
max.
max.
Type
removal of Nominal
mm
cross
Ø of
connector cross
Ø of
connector
outer semisection connector length
section connector length
conducting
mm²
mm
mm
mm²
mm
mm
layer mm
U0/U (Um) 6/10 (12)kV - 8.7 /15 (17.5)kV
35-50
1100
12.6
50 - 95
25
145
35 - 50
20
110
CHMPR3-1
70-240
1100
17.3
95 - 300
34
145
70 - 240
34
145
17kV
240-400 1100
23.1
300 - 400
42
170
240 - 400
42
170
Art.-No.
197603
197604
197606
Appropriate connectors must be ordered separately.
Padding kits must be ordered separately.
Padding kit PS(G+H)17/1 (Art.-No.197690) to be used with Art.-No. 197604 sur 35-50mm² (17.5kV) and 35-70mm² (12kV).
74
www.cellpack.com
Transition joints
Medium Voltage 2013
CHMPR 3
Transition joint
from belted cable to polymeric cables
Type CHMPR3 hybrid transition joints for transition to three-core plastic-insulated
cables are suitable for both paper-insulated lead cables and Hochstädter cables up to
17.5 kV. Padding kits for paper-insulated cables are available for downwards
enlargement of the operational area. Suitable for Compression connectors.
Dimensions
Characteristics
• Reliable stress control due to flexible
silicone stress control elements
• Quick, safe and easy assembly
• Ready for immediate operation
• Wide cross-section range
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Spreader cap
• Thick wall heat-shrinkable outer tubing
with hot melt adhesive
• Oil barrier tubing
• Heat-shrink tubing
• Silicone stress-control elements
• Earthing wire
• Copper braid tape
• Pressure spring
• Assembly accessories
• Sealing tape
• Stress control filling tape (blue)
• Fire protection wrap
• Assembly instructions
min. Ø
12 kV
17 kV
over conductor
insulation after
L
Nominal
max.
max. Nominal
max.
max.
Type
removal of
Art.-No.
mm
cross
Ø of
connector cross
Ø of
connector
outer semisection connector length section connector length
conducting
mm²
mm
mm
mm²
mm
mm
layer mm
U0/U (Um) 6/10 (12)kV - 8.7 /15 (17.5)kV
35-50
1400
12.6
50 - 95
25
145
35 - 50
20
110
197618
CHMPR3
70-240
1400
17.3
95 - 300
34
145
70 - 240
34
145
197619
17kV
240-400 1400
23.1
300 - 400
42
170
240 - 400
42
170
197620
Appropriate compression connectors must be ordered separately.
Padding kits must be ordered separately.
Padding kit PS(G+H)17/1 (Art.-No.197690) tob e used with Art.-No. 197619 sur 35-50mm² (17.5kV and resp. 35-70mm² (12kV).
www.cellpack.com
75
Cable accessories for paper-insulated cables
Application
• Indoor
• Outdoor
• Underground
• Water
• Installation ducts
• Ductwork
Note
• Compression connectors not included
L = Length
Straight-through joints
Medium Voltage 2013
CHMPPR3
Straight-through joint
for belted cables up to 17.5 kV (MIND)
Type CHMPPR3 hybrid transition joints are suitable for belted cables and
Hochstädter cables up to 17.5 kV. Suitable for compression connectors.
Dimensions
L = Length
Cable accessories for paper-insulated cables
Characteristics
• Quick, safe and easy assembly
• Ready for immediate operation
• Wide cross-section range
Application
• Indoor
• Outdoor
• Underground
• Water
• Installation ducts
• Ductwork
Note
• Compression connectors not included
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Spreader cap
• Thick wall heat-shrinkable outer tubing
with hot melt adhesive
• Oil barrier tubing
• Heat-shrink tubing
• Earthing wire
• Copper braid tape
• Pressure spring
• Assembly accessories
• Sealing tape
• Stress control filling tape (blue)
• Fire protection wrap
• Assembly instructions
min. Ø
12 kV
17.5kV
over conductor
insulation after
L
Nominal
max.
max.
Nominal
max.
max.
Type
removal of
mm
cross
Ø of
connector cross
Ø of
connector
outer semisection connector length
section connector length
conducting
mm²
mm
mm
mm²
mm
mm
layer mm
U0/U (Um) 6/10 (12)kV - 8.7 /15 (17.5)kV
35-50
1400
15.2
50 - 95
25
145
35 - 50
20
110
CHMPPR3
70-240 1400
17.9
95 - 300
34
145
70 - 240
34
145
17kV
240-400 1400
26.3
300 - 400
42
170
240 - 400
42
170
Appropriate compression connectors must be ordered separately.
76
www.cellpack.com
Art.-No.
197658
197659
197660
Terminations
Medium Voltage 2013
CHEP-3I
Indoor termination
for belted cables up to 17.5 kV (MIND)
Type CHEP-3I indoor terminations are suitable for belted cables up to 17.5 kV for MIND cables only. For cables with draining
compound please contact us.
Dimensions
L = Length
Type
Application
• Indoor
Note
• Cable lugs not included
L
mm
U0/U (Um) 6/10 (12)kV - 8.7 /15 (17.5)kV
16-50
500
25-240
500
CHEP-3I 12kV
95-300
500
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Tracking resistant spreader cap
• Tracking-resistant heat-shrink tubing
• Earthing kit
• Assembly accessories
• Sealing tape
• Assembly instructions
Nominal cross section
mm²
min. Ø
over conductor
mm
12 kV
17.5kV
9.9
13.2
16.5
70 - 240
120 - 400
16 - 50
25 - 240
95 - 300
Art.-No.
197515
197516
197517
Appropriate cable lugs must be ordered separately.
www.cellpack.com
77
Cable accessories for paper-insulated cables
Characteristics
• Wide cross-section range
• Quick, safe and easy assembly
• Ready for immediate operation
Terminations
Medium Voltage 2013
CHEP-3F
Outdoor termination
for belted cables up to 17.5 kV (MIND)
Type CHEP-3F outdoor terminations are suitable for belted cables up to 17.5 kV for MIND cables only. For cables with draining
compound please contact us.
Dimensions
L = Length
Ø S = Diameter of cable shed
Cable accessories for paper-insulated cables
Characteristics
• Wide cross-section range
• Quick, safe and easy assembly
• Ready for immediate operation
L
mm
Type
Application
• Outdoor
Note
• Cable lugs not included
min. Ø
over conductor
mm
U0/U (Um) 6/10 (12)kV - 8.7 /15 (17.5)kV
16-50
500
9.9
25-240
500
13.2
CHEP-3F 17kV
95-300
500
16.5
Appropriate cable lugs must be ordered separately.
78
www.cellpack.com
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Tracking resistant spreader cap
• Tracking-resistant heat-shrink tubing
• Silicone sheds
• Earthing kit
• Assembly accessories
• Sealing tape
• Assembly instructions
Number of
sheds per
phase
ØS
mm
2
2
2
80
85
85
Nominal cross section
mm²
12 kV
17.5kV
70 - 240
16 - 50
25 - 240
95 - 300
Art.-No.
197537
197538
197539
Transition joints
Medium Voltage 2013
CHMP(H) 3-1
Transition joint
for H-cables to polymeric cables
Type CHMP(H)3-1 hybrid transition joints for transition to three single-core plasticinsulated cables are suitable for Hochstädter cables up 24 to 36 kV. Padding kits for
paper-insulated cables are available for downwards enlargement of the operational
area. Suitable for compression connectors.
Dimensions
Characteristics
• Reliable stress control due to flexible
silicone stress control elements
• Wide conductor and cross-section
range
• Wide cross-section range
• Quick, safe and easy assembly
• Ready for immediate operation
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Spreader cap
• Thick wall heat-shrinkable outer tubing
with hot melt adhesive
• Oil barrier tubing
• Heat-shrink tubing
• Silicone stress-control elements
• Earthing wire
• Copper braid tape
• Pressure spring
• Assembly accessories
• Sealing tape
• Stress control filling tape (blue)
• Fire protection wrap
• Assembly instructions
min. Ø
Nominal cross section
over conductor
max.
max.
mm²
L
insulation after
Ø of
connector
Type
Art.-No.
mm
removal of outer connector length
24kV
36kV
semi-conducting
mm
mm
layer mm
U0/U (Um) 12/20 (24)kV - 12.7/22 (24)kV
16-35
1200
12.6
15
100
16 - 35
197607
35-70
1200
17.3
20
110
35 - 70
197608
CHMP(H)3-1 24 kV
95-240
1200
19.9
34
145
95 - 240
197609
185-300 1200
23.1
42
145
185 - 300
197610
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
35-50
1200
19.9
20
110
35 - 50
197614
1200
23.1
28
145
70 - 150
197616
CHMP(H)3-1 36 kV 70-150
150-300 1200
27.3
36
145
150 - 300 197617
Appropriate compression connectors must be ordered separately.
Padding kits must be ordered separately.
Padding kit PS(H)24/1 (Art.-No.197692) to be used with Art.-No. 197609 sur 35-70mm² (24kV) and 35-70mm² (24kV).
www.cellpack.com
79
Cable accessories for paper-insulated cables
Application
• Indoor
• Outdoor
• Underground
• Water
• Installation ducts
• Ductwork
Note
• Compression connectors not included
L = Length
Transition joints
Medium Voltage 2013
CHMP(H) 3
Transition joint
Cable accessories for paper-insulated cables
for H-cables to polymeric cables
Type CHMP(H)3 hybrid transition joints for transition to three-core plastic-insulated
cables are suitable for Hochstädter cables up 24 to 36 kV. Padding kits for
paper-insulated cables are available for downwards enlargement of the operational
area. Suitable for compression connectors.
Dimensions
Characteristics
• Reliable stress control due to flexible
silicone stress control elements
• Quick, safe and easy assembly
• Ready for immediate operation
• Wide cross-section range
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Spreader cap
• Thick wall heat-shrinkable outer tubing
with hot melt adhesive
• Oil barrier tubing
• Heat-shrink tubing
• Silicone stress-control elements
• Earthing wire
• Copper braid tape
• Pressure spring
• Assembly accessories
• Sealing tape
• Stress control filling tape (blue)
• Fire protection wrap
• Assembly instructions
Type
U0/U (Um) 12/20 (24)kV 16-35
35-70
CHMP(H)3 24kV
95-240
185-300
U0/U (Um) 18/30 (36)kV 35-50
70-150
CHMP(H)3 36kV
150-300
Application
• Indoor
• Outdoor
• Underground
• Water
• Installation ducts
• Ductwork
Note
• Compression connectors not included
min. Ø
over conductor
L
insulation after
mm removal of outer
semi-conducting
layer mm
12.7/22 (24)kV
1400
12.6
1400
17.3
1400
19.9
1400
23.1
19/33 (36)kV
1400
19.9
1400
23.1
1400
27.3
L = Length
max.
max.
Ø of
connector
connector
length
mm
mm
15
20
34
42
100
110
145
145
20
28
36
110
145
145
Nominal cross section
mm²
Art.-No.
24kV
36kV
197621
197622
197623
197624
16 - 35
35 - 70
95 - 240
185 - 300
35 - 50
70 - 150
150 - 300
197625
197626
197627
Appropriate compression connectors must be ordered separately.
Padding kits must be ordered separately.
Padding kit PS(H)24/1 (Art.-No.197692) to be used with Art.-No. 197623 sur 35-70mm² (24kV) and 35-70mm² (24kV).
80
www.cellpack.com
Straight-through joints
Medium Voltage 2013
CHMPP(H)3
Straight-through joint
for H-cables from 24 up to 36 kV
Type CHMPP(H)3 hybrid transition joints are suitable for Hochstädter cables up to
24 to 36 kV. Padding kits for paper-insulated cables are available for downwards
enlargement of the operational area. Suitable for compression connectors.
Dimensions
Characteristics
• Quick, safe and easy assembly
• Ready for immediate operation
• Wide cross-section range
Type
U0/U (Um) 12/20
CHMPP(H)3 24kV
U0/U (Um) 18/30
CHMPP(H)3 36kV
Application
• Indoor
• Outdoor
• Underground
• Water
• Installation ducts
• Ductwork
Note
• Compression connectors not included
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Spreader cap
• Thick wall heat-shrinkable outer tubing
with hot melt adhesive
• Oil barrier tubing
• Heat-shrink tubing
• Silicone stress-control elements
• Earthing wire
• Copper braid tape
• Pressure spring
• Assembly accessories
• Sealing tape
• Spacers
• Stress control filling tape (blue)
• Fire protection wrap
• Assembly instructions
min. Ø
over conductor
max.
max.
L
insulation after
Ø of
connector
mm removal of outer connector
length
semi-conducting
mm
mm
layer mm
(24)kV - 12.7/22 (24)kV
16-35
1400
16.5
15
100
35-70
1400
17.4
20
110
95-240
1400
21.6
34
145
185-300
1400
25.8
42
145
(36)kV - 19/33 (36)kV
35-50
1400
21.4
20
110
70-150
1400
24
28
145
150-300
1400
28.2
36
145
Nominal cross section
mm²
Art.-No.
24kV
36kV
197661
197662
197663
197664
16 - 35
35 - 70
95 - 240
185 - 300
35 - 50
70 - 150
150 - 300
197665
197666
197667
Appropriate compression connectors must be ordered separately.
www.cellpack.com
81
Cable accessories for paper-insulated cables
L = Length
Terminations
Medium Voltage 2013
CHEP(H)-3I
Indoor termination
for H-cables from 24 up to 36 kV
Type CHEP(H)-3F outdoor terminations are suitable for Hoechstaedter cables from 24 up to 36 kV for MIND cables only. For
cables with draining compound please contact us.
Dimensions
L = Length
Ø S = Diameter of cable shed
Cable accessories for paper-insulated cables
Characteristics
• Wide cross-section range
• Quick, safe and easy assembly
• Ready for immediate operation
L
mm
Type
min. Ø
over conductor
mm
U0/U (Um) 12/20 (24)kV - 12.7/22 (24)kV
16-35
500
12.6
50-150
500
17.3
CHEP(H)-3I 24kV
70-240
500
19.9
120-300
500
23.1
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
35-70
650
19.9
CHEP(H)-3I 36kV
50-240
650
23.1
Appropriate cable lugs must be ordered separately.
82
www.cellpack.com
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Tracking-resistant heat-shrink tubing
• Conductive spreader cap
• Conductive heat-shrink tubing
• Oil barrier tubing
• Filling tape
• Silicone sheds
• Earthing wire
• Pressure spring
• Assembly instructions
Application
• Indoor
Note
• Cable lugs not included
Number of
sheds per
phase
ØS
mm
1
1
1
1
80
85
85
85
2
2
85
85
Nominal cross section
mm²
24kV
Art.-No.
36kV
197531
197532
197533
197534
16 - 35
50 - 150
70 - 240
120 - 300
35 - 70
50 - 240
197535
197536
Terminations
Medium Voltage 2013
CHEP(H)-3F
Outdoor termination
for H-cables from 24 up to 36 kV
Type CHEP(H)-3F outdoor terminations are suitable for Hoechstaedter cables from 24 up to 36 kV for MIND cables only. For
cables with draining compound please contact us.
Dimensions
Characteristics
• Wide cross-section range
• Quick, safe and easy assembly
• Ready for immediate operation
Type
L
mm
Application
• Outdoor
Note
• Cable lugs not included
min. Ø
over conductor
mm
U0/U (Um) 12/20 (24)kV - 12.7/22 (24)kV
16-35
850
12.6
50-150
850
17.3
CHEP(H)-3F 24kV
70-240
850
19.9
120-300 850
23.1
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
35-70
850
19.9
CHEP(H)-3F 36kV
50-240
850
23.1
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Thick wall heat-shrinkable outer tubing
with hot melt adhesive
• Tracking-resistant heat-shrink tubing
• Conductive spreader cap
• Oil barrier tubing
• Filling tape
• Silicone sheds
• Earthing wire
• Pressure spring
• Sealing tape
• Oil-barrier stress control filling
tape (blue)
• Assembly instructions
Number of
sheds per
phase
ØS
mm
3
3
3
3
80
85
85
85
4
4
85
85
Nominal cross section
mm²
24kV
Art.-No.
36kV
197543
197544
197545
197546
16 - 35
50 - 150
70 - 240
120 - 300
35 - 70
50 - 240
197547
197548
Appropriate cable lugs must be ordered separately.
www.cellpack.com
83
Cable accessories for paper-insulated cables
L = Length
Ø S = Diameter of cable shed
Transition joints
Medium Voltage 2013
CHMP(3Pb) 3-1
Transition joint
for 3-core single lead sheath cables to polymeric cables
Type CHMP(3Pb)3-1 hybrid transition joints for transition to three single-core cables
are suitable for all three-core lead sheath cables up to 36 kV. Padding kits for
paper-insulated cables are available for downwards enlargement of the operational
area. Suitable for compression connectors.
Dimensions
L = Length
Cable accessories for paper-insulated cables
Characteristics
• Reliable stress control due to flexible
silicone stress control elements
• Wide conductor and cross-section
range
• Wide cross-section range
• Quick, safe and easy assembly
• Ready for immediate operation
Application
• Indoor
• Outdoor
• Underground
• Water
• Installation ducts
• Ductwork
Note
• Compression connectors not included
Scope of delivery
• Spreader cap
• Thick wall heat-shrinkable outer tubing
with hot melt adhesive
• Oil barrier tubing
• Heat-shrink tubing
• Silicone stress-control elements
• Earthing wire
• Copper braid tape
• Pressure spring
• Assembly accessories
• Sealing tape
• Stress control filling tape (blue)
• Fire protection wrap
• Assembly instructions
min. Ø over
12 kV
17 kV
conductor
L
insulation after Nominal max.
max. Nominal max.
max.
Type
Art.-No.
mm removal of outer cross
Ø of
connector cross
Ø of
connector
semi-conducting section connector length section connector length
layer mm
mm²
mm
mm
mm²
mm
mm
U0/U (Um) 6/10 (12)kV - 8.7 /15 (17.5)kV
25-50
1200
12.6
50 - 95
25
110
25 - 50
20
110
197628
17.3
95 - 185
32
140
70 - 150
25
140
198782
CHMP(3Pb)3-1 70-150 1200
17 kV
120-240 1200
19.9
150 - 300
36
150
120 - 240
34
150
197629
240-300 1200
23.1
300 - 400
40
170
240 - 300
40
150
197630
min. Ø over conductor
max.
insulation after
max. Ø of
L
connector
Type
removal of outer
connector
mm
length
semi-conducting
mm
mm
layer mm
U0/U (Um) 12/20 (24)kV - 12.7/22 (24)kV
16-25
1200
12.6
20
100
1200
17.3
25
110
CHMP3Pb3-1 35-95
24kV
95-240
1200
19.9
34
150
185-300 1200
23.1
40
150
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
35-50
1200
19.9
20
110
CHMP3Pb3-1
70-150
1200
23.1
25
150
36kV
150-300 1200
27.3
38
160
Nominal cross section
mm²
24kV
Art.-No.
36kV
197631
197632
197633
197634
16 - 25
35 - 95
95 - 240
185 - 300
35 - 50
70 - 150
150 - 300
197635
197636
197637
Appropriate compression connectors must be ordered separately.
Padding kits must be ordered separately.
Padding kit PS(3Pb+Pb), (Art.-No.197699) to be used with Art.-No. 197633 sur 35-70mm² (24kV).
Please use the padding kit PS(3Pb+Pb), (Art.-No.197701) for the following case: for Art.-No. 197636 sur 35-70mm² (36kV).
Please use the padding kit PS(3Pb+Pb), (Art.Nr.197702) for the following case: for Art.-No. 197637 sur 70-150mm² (36kV).
84
www.cellpack.com
Transition joints
Medium Voltage 2013
CHMP(3Pb) 3
Transition joint
for 3-core single lead sheath cables to polymeric cables
Type CHMPP(3Pb)3 hybrid transition joints are suitable for all three-core lead sheath Dimensions
cables up to 36 kV. Padding kits for paper-insulated cables are available for
downwards enlargement of the operational area. Suitable for compression connectors.
Characteristics
• Reliable stress control due to flexible
silicone stress control elements
• Wide cross-section range
• Quick, safe and easy assembly
• Ready for immediate operation
Application
• Indoor
• Outdoor
• Underground
• Water
• Installation ducts
• Ductwork
Note
• Compression connectors not included
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Spreader cap
• Thick wall heat-shrinkable outer tubing
with hot melt adhesive
• Oil barrier tubing
• Heat-shrink tubing
• Silicone stress-control elements
• Earthing wire
• Copper braid tape
• Pressure spring
• Assembly accessories
• Sealing tape
• Stress control filling tape (blue)
• Fire protection wrap
• Assembly instructions
min. Ø
12 kV
17.5 kV
over conductor
L
insulation after Nominal max.
max.
Nominal
max.
max.
Type
mm removal of outer cross
Ø of
connector cross
Ø of
connector
semi-conducting section connector length section connector length
layer mm
mm²
mm
mm
mm²
mm
mm
U0/U (Um) 6/10 (12)kV - 8.7 /15 (17.5)kV
25-50
1400
12.6
50 - 95
25
110
25 - 50
20
110
17.3
95 - 185
32
140
70 - 150
25
140
CHMP(3Pb)3 70-150 1400
17kV
120-240 1400
19.9
150 - 300
36
150
120 - 240
34
150
240-300 1400
23.1
300 - 400
40
170
240 - 300
40
150
min. Ø over conductor
max.
max.
insulation after
L
Ø of
connector
Type
removal of outer
mm
connector length
semi-conducting
mm
mm
layer mm
U0/U (Um) 12/20 (24)kV - 12.7/22 (24)kV
16-25
1400
12.6
20
100
1400
17.3
25
110
CHMP(3Pb)3 35-95
24kV
95-240
1400
19.9
34
150
185-300 1400
23.1
40
150
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
35-50
1400
19.9
20
110
CHMP(3Pb)3
70-150
1400
23.1
25
150
36kV
150-300 1400
27.3
38
160
Nominal cross section
mm²
24kV
Art.-No.
197638
198783
197639
197640
Art.-No.
36kV
197641
197642
197643
197644
16 - 25
35 - 95
95 - 240
185 - 300
35 - 50
70 - 150
150 - 300
197645
197646
197647
Appropriate compression connectors must be ordered separately.
Padding kits must be ordered separately.
Padding kit PS(3Pb+Pb), (Art.-No.197699) to be used with Art.-No. 197633 sur 35-70mm² (24kV).
Please use the padding kit PS(3Pb+Pb), (Art.-No.197701) for the following case: for Art.-No. 197636 sur 35-70mm² (36kV).
Please use the padding kit PS(3Pb+Pb), (Art.Nr.197702) for the following case: for Art.-No. 197637 sur 70-150mm² (36kV).
www.cellpack.com
85
Cable accessories for paper-insulated cables
L = Length
Straight-through joints
Medium Voltage 2013
CHMPP(3Pb)3
Straight-through joint
for 3-core single lead sheath cables
Type CHMPP(3Pb)3 hybrid transition joints are suitable for all three-core lead sheath
cables up to 36 kV. Suitable for compression connectors.
Dimensions
L = Length
Cable accessories for paper-insulated cables
Characteristics
• Quick, safe and easy assembly
• Ready for immediate operation
• Wide cross-section range
Application
• Indoor
• Outdoor
• Underground
• Water
• Installation ducts
• Ductwork
Note
• Compression connectors not included
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Spreader cap
• Thick wall heat-shrinkable outer tubing
with hot melt adhesive
• Oil barrier tubing
• Heat-shrink tubing
• Silicone stress-control elements
• Earthing wire
• Copper braid tape
• Pressure spring
• Assembly accessories
• Sealing tape
• Stress control filling tape (blue)
• Fire protection wrap
• Assembly instructions
12 kV
17.5 kV
min. Ø
max.
max.
Nominal
max.
max.
Nominal
L
over
Type
Art.-No.
cross
Ø
of
connector
cross
Ø
of
connector
mm conductor
section
connector
length
section
connector
length
mm
mm²
mm
mm
mm²
mm
mm
U0/U (Um) 6/10 (12)kV - 8.7 /15 (17.5)kV
25-50
1400
14.1
50 - 95
25
110
25 - 50
20
110
197668
17.6
95 - 185
32
140
70 - 150
25
140
198784
CHMPP(3Pb)3 70-150 1400
12kV
120-240 1400
20.5
150 - 300
36
150
120 - 240
34
150
197669
240-300 1400
25.6
300 - 400
40
170
240 - 300
40
150
197670
min. Ø
L
over conductor
mm
mm
Type
U0/U (Um) 12/20 (24)kV - 12.7/22 (24)kV
16-25
1400
15.4
1400
17.4
CHMPP(3Pb)3 35-95
24kV
95-240 1400
21.6
185-300 1400
25.8
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
35-50
1400
21.4
CHMPP(3Pb)3
70-150 1400
24
36kV
150-300 1400
28.2
max. Ø of
connector
mm
max.
connector
length
mm
20
25
34
40
100
110
150
150
20
25
36
110
150
160
Appropriate compression connector must be ordered separately.
86
www.cellpack.com
Nominal cross section
mm²
24kV
Art.-No.
36kV
197671
197672
197673
197674
16 - 25
35 - 95
95 - 240
185 - 300
35 - 50
70 - 150
150 - 300
197675
197676
197677
Terminations
Medium Voltage 2013
CHEP(3Pb)-3I
Indoor termination
for 3-core single lead sheath cables
Type CHEP(3Pb)-3I indoor terminations are suitable for three-core single lead sheath cables from 24 up to 36 kV – for MIND
cables only. For cables with draining compound please contact us.
Dimensions
L = Length
Ø S = Diameter of cable shed
Type
Application
• Indoor
Note
• Cable lugs not included
L
mm
min. Ø
over conductor
mm
U0/U (Um) 12/20 (24)kV - 12.7/22 (24)kV
16-35
450
50-150
450
CHEP(3Pb)-3I 24kV
70-240
450
120-300
450
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
35-70
600
CHEP(3Pb)-3I 36kV
95-240
600
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Tracking-resistant heat-shrink tubing
• Oil barrier tubing
• Silicone sheds
• Sealing tape
• Oil-barrier stress control filling
tape (blue)
• Earthing wire
• Pressure spring
• Assembly instructions
Number of
sheds per
phase
ØS
mm
12.2
17.2
19.9
23.1
1
1
1
1
80
85
85
85
19.9
23.1
2
2
85
85
Nominal cross section
mm²
24kV
Art.-No.
36kV
197555
197556
197557
197558
16 - 35
50 - 150
70 - 240
120 - 300
35 - 70
95 - 240
197559
197560
Appropriate cable lugs must be ordered separately.
www.cellpack.com
87
Cable accessories for paper-insulated cables
Characteristics
• Combination of slip-on and
heat-shrink components
• Wide cross-section range
• Quick, safe and easy assembly
• Ready for immediate operation
Terminations
Medium Voltage 2013
CHEP(3Pb)-3F
Outdoor termination
for 3-core single lead sheath cables
Type CHEP(3Pb)-3F outdoor terminations are suitable for three-core single lead sheath cables from 24 up to 36 kV – for MIND
cables only. For cables with draining compound please contact us.
Dimensions
L = Length
Ø S = Diameter of cable shed
Cable accessories for paper-insulated cables
Characteristics
• Combination of slip-on and
heat-shrink components
• Wide cross-section range
• Quick, safe and easy assembly
• Ready for immediate operation
L
mm
Type
min. Ø
over conductor
mm
U0/U (Um) 12/20 (24)kV - 12.7/22 (24)kV
16-35
600
50-150
600
CHEP(3Pb)-3F 24kV
70-240
600
120-300
600
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
35-70
750
CHEP(3Pb)-3F 36kV
95-240
750
Number of
sheds per
phase
ØS
mm
12.2
17.2
19.9
23.1
3
3
3
3
80
85
85
85
19.9
23.1
4
4
85
85
Appropriate cable lugs must be ordered separately.
88
www.cellpack.com
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Weatherproof spreader cap
• Tracking-resistant heat-shrink tubing
• Oil barrier tubing
• Silicone sheds
• Sealing tape
• Oil-barrier stress control filling
tape (blue)
• Earthing wire
• Pressure spring
• Assembly instructions
Application
• Outdoor
Note
• Cable lugs not included
Nominal cross section
mm²
24kV
Art.-No.
36kV
197567
197568
197569
197570
16 - 35
50 - 150
70 - 240
120 - 300
35 - 70
95 - 240
197571
197572
Terminations
Cable accessories for paper-insulated cables
Medium Voltage 2013
www.cellpack.com
89
Complete
safety
90
www.cellpack.com
Medium Voltage 2013
Medium Voltage 2013
Page
Straight-through joints for
single-core cables
92
Straight-through joints for
3-core cables
93
Terminations for single-core cables
94
Terminations for 3-core cables
96
Accessories
98
Cable accessories for
screened cables according to
British Standard
www.cellpack.com
91
Straight-through joints for single-core cables
Medium Voltage 2013
CHM(BS)
Single-core straight-through joint
Cable accessories for screened
cables according to British Standard
for all polymeric single-core cables
Type CHM (BS) straight-through joints are suitable for all single-core plasticinsulated cables (PVC, PE, XLPE, EPR). They allow the connection of cables with
different cross sections, conductive materials, semi-conducting layers
(graphite-coated, removable or strippable) and screening (copper wire or tape).
Suitable for compression connectors.
Dimensions
Characteristics
• Reliable stress control due to flexible
silicone stress control elements
• Quick, safe and easy assembly
• Ready for immediate operation
• Wide cross-section range
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Thick wall heat-shrinkable insulation
tubing
• Thick wall heat-shrinkable outer tubing
with hot melt adhesive
• Silicone stress-control elements
• Copper braid tube
• Pressure springs
• Assembly accessories
• Steel cage
• Stress control filling tape (blue)
• Assembly instructions
Application
• Indoor
• Outdoor
• Underground
• Water
• Installation ducts
• Ductwork
Note
• Compression connectors not included
• Joints with a range of Um = 12 kV
must be used for cables of
Um = 7.2 kV. (Check minimum
diameter over conductor insulation).
L = Length
min. Ø
Nominal cross section
over conductor
max.
mm²
max. Ø of
L
insulation after
connector
Type
connector
Art.-No.
mm removal of outer
length
mm
semi-conducting
mm
12kV
36kV
layer mm
U0/U (Um) 6/10 (12)kV - 6.35/11 (12)kV
CHM(BS) 12kV
400-630
1100
27.3
60
360
400 - 630
253845
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
150-400
900
27.3
38
200
150 - 400 253844
CHM(BS) 36kV
500-800
1100
36.8
60
360
500 - 800 253843
Appropriate compression connectors must be ordered separately.
92
www.cellpack.com
Straight-through joints for 3-core cables
Medium Voltage 2013
CHM3(BS)
Three-core straight-through joint
for all 3-core polymeric cables
Type CHM3(BS) straight-through joints are suitable for all three-core plastic-insulated cables (PVC, PE, XLPE, EPR). They allow
the connection of cables with different cross sections, conductive materials, semi-conducting layers (graphite-coated, removable
or strippable) and screening (copper wire or tape). Suitable for compression connectors.
Dimensions
Characteristics
• Reliable stress control due to flexible
silicone stress control elements
• For all cables with copper wire or
tape screen
• Quick, safe and easy assembly
• Ready for immediate operation
• Wide cross-section range
Type
Application
• Indoor
• Outdoor
• Underground
• Water
• Installation ducts
• Ductwork
Note
• Compression connectors not included
• Joints with a range of Um = 12 kV
must be used for cables of
Um = 7.2 kV. (Check minimum
diameter over conductor insulation).
min. Ø
over conductor
max.
max.
insulation after
Ø of
connector
L
removal of
mm
connector length
outer semimm
mm
conducting
layer mm
U0/U (Um) 6/10 (12)kV - 6.35/11 (12)kV
35-95
1500
12.6
CHM3(BS)
95-240
1500
17.3
12kV
150-300 1500
19.9
U0/U (Um) 8.7/15 (17.5)kV
35-95
1500
12.6
CHM3(BS)
70-240
1500
17.3
17kV
120-300 1500
19.9
U0/U (Um) 12/20 (24)kV - 12.7/22 (24)kV
35-95
1500
17.3
CHM3(BS)
70-240
1500
19.9
24kV
150-300 1500
23.1
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
50-150
1500
23.1
CHM3(BS)
36kV
150-300 1500
27.3
19
29
32
90
125
125
19
29
32
90
125
125
19
29
32
90
125
125
23
32
105
125
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Thick wall heat-shrinkable insulation
tubing
• Thick wall heat-shrinkable outer tubing
with hot melt adhesive
• Silicone stress-control element
• Copper braid tube
• Pressure springs
• Stress control filling tape (blue)
• Assembly instructions
• Steel cage
• Assembly accessories
Nominal cross section
mm²
Art.-No.
12kV
17.5kV
24kV
36kV
248770
248718
248717
35 - 95
95 - 240
150 - 300
249471
249474
249476
35 - 95
70 - 240
120 - 300
35 - 95
70 - 240
150 - 300
253917
253911
253929
50 - 150 248716
150 - 300 248719
Appropriate compression connectors must be ordered separately.
www.cellpack.com
93
Cable accessories for screened
cables according to British Standard
L = Length
Terminations for single-core cables
Medium Voltage 2013
CHE-I (BS)
Single-core indoor termination
for all polymeric single-core cables
Dimensions
Cable accessories for screened
cables according to British Standard
Type CHE-I(BS) terminations are suitable for all single-core plastic-insulated cables
(PVC, PE, XLPE, EPR) with different types of semi-conducting layers (graphite-coated
or strippable) and screening (copper wire or tape).
L = Length
Ø S = Diameter of
cable shed
Characteristics
• Flexible silicone stress control elements
ensure reliable stress control under all
operating conditions
• Combination of slip-on and heat-shrink
components
• Compatible with all cable lugs
• Wide cross-section range
• Quick, safe and easy assembly
• Ready for immediate operation
L
mm
Type
Application
• Indoor
Note
• Cable lugs not included
• 12 kV terminations must be used for
7.2 kV cables (Check minimum
diameter over conductor insulation).
min. Ø over conductor
insulation after
removal of outer
semi-conducting
layer mm
U0/U (Um) 6/10 (12)kV - 6.35/11 (12)kV
CHE-I(BS) 12kV
400-630
400
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
CHE-I(BS) 36kV
150-400
600
www.cellpack.com
ØS
mm
27.3
27.3
Appropriate cable lugs must be ordered separately.
94
Number of
sheds per
phase
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• 1 Set for 3 phases
• Tracking-resistant heat-shrink tubing
• Silicone stress-control elements
• Silicone sheds
• Earthing kit
• Sealing tape
• Assembly instructions
Nominal cross section
mm²
12kV
36kV
253847
400 - 630
2
115
Art.-No.
150 - 400
253849
Terminations for single-core cables
Medium Voltage 2013
CHE-F(BS)
Single-core outdoor termination
for all polymeric single-core cables
L = Length
Ø S = Diameter
of cable shed
Characteristics
• Flexible silicone stress control elements
ensure reliable stress control under all
operating conditions
• Combination of slip-on and heat-shrink
components
• Wide cross-section range
• Quick, safe and easy assembly
• Ready for immediate operation
Type
Application
• Outdoor
Note
• Cable lugs not included
• 12 kV terminations must be used for
7.2 kV cables (Check minimum
diameter over conductor insulation).
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• 1 Set for 3 phases
• Tracking-resistant heat-shrink tubing
• Silicone stress-control elements
• Silicone sheds
• Earthing kit
• Sealing tape
• Assembly instructions
min. Ø over conductor
insulation after
Number of
ØS
L
removal of outer
sheds per
mm
mm
semi-conducting
phase
layer mm
U0/U (Um) 6/10 (12)kV - 6.35/11 (12)kV
CHE-F(BS) 12kV
400-630
400
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
CHE-F(BS) 36kV
150-400
800
27.3
1
115
27.3
4
115
Nominal cross section
mm²
12kV
Art.-No.
36kV
253848
400 - 630
150 - 400
253850
Appropriate cable lugs must be ordered separately.
www.cellpack.com
95
Cable accessories for screened
cables according to British Standard
Dimensions
Type CHE-F(BS) terminations are suitable for all single-core plastic-insulated cables
(PVC, PE, XLPE, EPR) with different types of semi-conducting layers (graphite-coated
or strippable) and screening (copper wire or tape).
Terminations for 3-core cables
Medium Voltage 2013
CHE-3I(BS)
Three-core indoor termination
for all 3-core polymeric cables
Type CHE-3I(BS) terminations are suitable for all three-core plastic-insulated cables (PVC, PE, XLPE, EPR) with different types of
semi-conducting layers (graphite-coated or strippable) and screening (copper wire or tape).
Cable accessories for screened
cables according to British Standard
Dimensions
L = Length
Ø S = Diameter of cable shed
Characteristics
• Flexible silicone stress control elements
ensure reliable stress control under all
operating conditions
• Combination of slip-on and heat-shrink
components
• Wide cross-section range
• Quick, safe and easy assembly
• Ready for immediate operation
Application
• Indoor
Note
• Cable lugs not included
• 12 kV terminations must be used for
7.2 kV cables (Check minimum
diameter over conductor insulation).
Each unit contains materials for one set
of three terminations.
min. Ø
over conductor
L
insulation after
Type
mm removal of outer
semi-conducting
layer mm
U0/U (Um) 6/10 (12)kV - 6.35/11 (12)kV
25-95
350
12.6
CHE-3I(BS) 12kV 95-240
350
17.3
150-400
350
19.9
U0/U (Um) 8.7/15 (17.5)kV
25-50
400
12.6
CHE-3I(BS) 17kV
150-300
400
19.9
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
50-150
650
23.1
CHE-3I(BS) 36kV
150-400
650
27.3
Appropriate cable lugs must be ordered separately.
96
www.cellpack.com
Number of
sheds per
phase
ØS
mm
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Tracking-resistant heat-shrink tubing
• Silicone stress-control elements
• Silicone sheds
• Earthing kit
• Sealing tape
• Tracking resistant spreader cap
• Assembly instructions
Nominal cross section
mm²
Art.-No.
12kV
17.5kV
249328
249331
249332
25 - 95
95 - 240
150 - 400
25 - 50
150 - 300
2
2
85
115
36kV
249468
249469
50 - 150 249333
150 - 400 249334
Terminations for 3-core cables
Medium Voltage 2013
CHE-3F(BS)
Three-core outdoor termination
for all 3-core polymeric cables
Type CHE-3F(BS) terminations are suitable for all three-core plastic-insulated cables (PVC, PE, XLPE, EPR) with different types of
semi-conducting layers (graphite-coated or strippable) and screening (copper wire or tape).
L = Length
Ø S = Diameter of cable shed
Characteristics
• Flexible silicone stress control elements
ensure reliable stress control under all
operating conditions
• Combination of slip-on and heat-shrink
components
• Wide cross-section range
• Quick, safe and easy assembly
• Ready for immediate operation
Type
L
mm
Application
• Outdoor
Note
• Cable lugs not included
• 12 kV terminations must be used for
7.2 kV cables (Check minimum
diameter over conductor insulation).
min. Ø
over conductor
insulation after
removal of outer
semi-conducting
layer mm
(12)kV
12.6
17.3
19.9
U0/U (Um) 6/10 (12)kV - 6.35/11
25-95
1200
CHE-3F(BS) 12kV 95-240
1200
150-400 1200
U0/U (Um) 8.7/15 (17.5)kV
25-50
1200
CHE-3F(BS) 17kV
150-300 1200
U0/U (Um) 18/30 (36)kV - 19/33 (36)kV
50-150
1200
CHE-3F(BS) 36kV
150-400 1200
Number of
ØS
sheds per
mm
phase
1
1
1
85
85
85
12.6
19.9
2
2
85
85
23.1
27.3
3
3
85
115
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Tracking-resistant heat-shrink tubing
• Silicone stress-control elements
• Silicone sheds
• Earthing kit
• Sealing tape
• Tracking resistant spreader cap
• Assembly instructions
Nominal cross section
mm²
Art.-No.
12kV
17.5kV
36kV
249191
249192
249193
25 - 95
95 - 240
150 - 400
25 - 50
150 - 300
249464
249466
50 - 150 249194
150 - 400 249195
Appropriate cable lugs must be ordered separately.
www.cellpack.com
97
Cable accessories for screened
cables according to British Standard
Dimensions
Accessories
Medium Voltage 2013
AUF(BS)
Armour continuity for three-core joints
Armour continuity for armoured three-core polymeric cables in accordance with British Standard.
Dimensions
Cable accessories for screened
cables according to British Standard
L = Length
Characteristics
• Quick, safe and easy assembly
• Superior electrical properties
• High mechanical strength
Type
AUF
98
1100/53
1100/73
1100/87
1100/97
1100/107
www.cellpack.com
Application
• Earthing continuity and earth contactor
• For cast resin, heat-shrink and slip-on
cable accessories
• Enables solder-free electrical
connection of metal cable components
(screen, armouring, metal sheath).
L
mm
Internal-Ø
mm
1100
1100
1100
1100
1100
53
73
87
97
107
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Hose clamp
• Steel cage
• Cloth tape
• Backup-ring
Nominal cross section
mm²
7.2 kV
12 kV
17.5 kV
24 kV
150
150 - 300
95
120 - 300
70
95 - 240
150 - 300
50
70 - 150
150 - 300
Art.-No.
36 kV
95
120 - 185
150 - 300
240 - 400
195369
195380
195381
195382
304089
Accessories
Medium Voltage 2013
EGA(BS)
Earthing accessories
for cables with tape screen and/or armouring for terminations
Characteristics
• Quick, safe and easy assembly
• Superior electrical properties
• High mechanical strength
• Suitable for indoor and outdoor use
Type
EGA3BS
(53)
(68)
(73)
(87)
(97)
(107)
Application
• Earth connection and contactor
• For cast resin, heat-shrink and slip-on
cable accessories
• Enables solder-free electrical
connection of metal cable components
(screen, armouring, metal sheath).
Note
• Incl. cable lug
Internal-Ø
mm
Nominal
cross section
Copper braid
mm²
53
68
73
87
97
107
25
25
25
35
35
35
Storage conditions/Shelf life
• Unlimited shelf life
Scope of delivery
• Heat-shrink tube
• Earthing wire
• Earthing accessories
• Pressure springs
• Hose clamp
• Backup-ring
Nominal cross section
mm²
7.2 kV
12 kV
Cable accessories for screened
cables according to British Standard
Type EGA(BS) earthing kit for three-core polymeric cables in accordance with British Standard.
17.5 kV
24 kV
Art.-No.
36 kV
150
95
70
50
150 - 240 120 - 240 95 - 185 70 - 150
50
240 - 300 185 - 300 150 - 240 120 - 185 70 - 95
185 - 300 185 - 300 120 - 185
185 - 300
400
185050
185051
185052
185053
185054
304092
www.cellpack.com
99
Accessories
Medium Voltage 2013
CG
Cable entry points for XLPE- and paper-insulated cables
Cable entry point for junction boxes for transformers and substations.
Dimensions
Cable accessories for screened
cables according to British Standard
CG A
CG B
Scope of delivery
• Heat-shrink tube
• 1 Cable entry point
• Assembly accessories
• Assembly instructions
Type
CGA
CGB
100
Ø mm²
under armouring paper-insulated cable
30 - 46
47 - 75
www.cellpack.com
under armouring of XLPE-cable
36 - 52
53 - 80
Art.-No.
183662
183661
Cable accessories for screened
cables according to British Standard
Medium Voltage 2013
Accessories
www.cellpack.com
101
Customised
solutions
102
www.cellpack.com
Medium Voltage 2013
Medium Voltage 2013
Cable accessories
for the industries
Page
Cable accessories for
industries
104
www.cellpack.com
103
Cable accessories for shipyard-industrie Medium Voltage 2013
Cellpack‘s product portfolio also includes special solutions for the oil and gas, mining and shipbuilding industries as well as for offshore applications.These cable accessories are exposed to rain,
salt, chemicals and extreme mechanical loads.
Cable accessories for the shipbuilding industry
The products especially designed for these applications comply with current international norms
such as IEC and Cenelec, and with industry specific accreditation requirements. More specific
information is available on request.
104
www.cellpack.com
Cable accessories for shipyard-industrie
Cable accessories for the shipbuilding industry
Medium Voltage 2013
www.cellpack.com
105
106
www.cellpack.com
Medium Voltage 2013
Medium Voltage 2013
We won‘t leave you
in the lurch!
Page
Heat-shrink tubing
106
Compression cable lugs and
Compression connectors
complying with DIN
112
Screw cable lugs
119
Earthing components
120
Tapes
123
Tools
127
Chemical products
131
Accessories
www.cellpack.com
107
Heat-shrink tubing
Medium Voltage 2013
SRBB
Heat-shrink tubing up to 36kV
protection for busbar systems and reduction of minimum clearance
Characteristics
• Medium-walled
• Stabilized against UV rays
• Halogen-free
• Tracking resistant
• Non-corrosive
• Resistant to bacteria and fungi
Recommended application range
round Ø
mm
Type
19-6
35-11
50-18
80-26
120-40
min.
6.5
13
18
28
45
max.
12
25
35
65
100
Colour(s)
• red brown
Material
• Cross-linked polyolefin
Recommended application range
Width (B) + Height (H)
rectangular
mm
min.
12
22
31
55
80
max.
18
36
60
95
150
Art.-No.
201942
201943
201944
201945
201946
Accessories
SRBB
Application
• Allows for clearance reduction between
busbars in medium voltage substations
up to 36kV.
• Corrosion protection
L
m
Typ
SRBB
SRBB
108
19-6
35-11
50-18
80-26
120-40
19-6
35-11
50-18
80-26
120-40
www.cellpack.com
1
1
1
1
1
30
30
30
30
30
Internal-Ø
before shrinkage
mm
19
35
50
80
120
19
35
50
80
120
after shrinkage
mm
6
11
18
26
40
6
11
18
26
40
Recovered
Packing unit
wall thickness
Art.-No.
piece x m
mm
2.3
2.5
2.7
2.8
3
2.3
2.5
2.7
2.8
3
1x1
1x1
1x1
1x1
1x1
1 x 30 (Roll)
1 x 30 (Roll)
1 x 30 (Roll)
1 x 30 (Roll)
1 x 30 (Roll)
237858
237859
237860
237861
237862
201942
201943
201944
201945
201946
Heat-shrink tubing
Medium Voltage 2013
Technical Data
Physical properties
Density
Hardness
Elongation at break
Tensile strength at break
Longitudinal shrinkage
Shrink ratio
Concentricity expanded
Concentricity recovered
Thermal properties
Operating temperature range
Shrinkage temperature
Burning behaviour
Flexibility at low temperatures
Electrical properties
Dielectric strength
Volume resistivity
Chemical properties
Corrosion
Water absorption
Resistance to fungus and decay
Value
Test
1.22 g/cm³
89 Shore A
500 %
16 N/mm²
+5 % / -10 %
3:1
50 %
85 %
IEC 60684-2
DIN 53 505
IEC 60684-2
IEC 60684-2
IEC 60684-2
IEC 60684-2
-40 °C up to 120 °C
> 125 °C
not self-extinguishing
-40 °C
IEC 60684-2
CP-PM-1004*
IEC 60684-2 mode C
IEC 60684-2
20 kV/mm
1012 Ω x cm
IEC 60684-2
IEC 60684-2
none
< 0.15 %
Ra. 1
IEC 60684-2
IEC 60684-2
IEC 60684-2
IEC 60684-2
Busbar (round shaped)
without isolation Ph/Ph and Ph/E
with isolation Ph/Ph
with isolation Ph/E
Busbar (rectangular shaped)
without isolation Ph/Ph and Ph/E
with isolation Ph/Ph
with isolation Ph/E
12kV
mm
17.5kV
mm
24kV
mm
36kV
mm
120
50
60
160
65
80
220
90
120
320
145
200
120
60
70
180
80
100
220
110
145
320
195
280
www.cellpack.com
Accessories
Minimum allowance between the busbars:
109
Heat-shrink tubing
Medium Voltage 2013
SRAT
Thick wall heat-shrink tubing
Shrinkage ratio 3:1
Characteristics
• Thick-walled
• Stabilized against UV rays
• Halogen-free
• Non-corrosive
• Infusible
• Highly resistant to electrical breakdown
• Tracking resistance in compliance
with IEC 112
• High tensile strength
• Resistant to cold flow (thermally stable)
Accessories
in 1m sections
19-6
29-9
38-12
48-15
SRAT
60-20
80-26
120-40
on rolls
19-6
29-9
38-12
SRAT
48-15
60-20
80-26
110
www.cellpack.com
Internal-Ø
Colour(s)
• red brown
Material
• Cross-linked polyolefin
• Free of lead and cadmium
before shrinkage
mm
after shrinkage
mm
Recovered
wall thickness
mm
1
1
1
1
1
1
1
19
29
38
48
60
80
120
6
9
12
15
20
26
40
3
3
3.1
3.1
3.1
3.1
3.1
1x1
1x1
1x1
1x1
1x1
1x1
1x1
144888
144892
144898
132464
144921
144935
144943
30
30
30
30
30
30
19
29
38
48
60
80
6
9
12
15
20
26
3
3
3.1
3.1
3.1
3.1
1 x 30 (Roll)
1 x 30 (Roll)
1 x 30 (Roll)
1 x 30 (Roll)
1 x 30 (Roll)
1 x 30 (Roll)
144884
144882
144880
144878
144886
144876
L
m
Type
Application
• Insulation tube for conductors in
terminations of 3.6 to 42 kV
• Corrosion protection
Packing unit
Art.-No.
piece x m
Heat-shrink tubing
Medium Voltage 2013
Physical properties
Density
Hardness
Elongation at break
Tensile strength at break
Longitudinal shrinkage
Shrink ratio
Concentricity expanded
Concentricity recovered
Thermal properties
Operating temperature range
Shrinkage temperature
Burning behaviour
Flexibility at low temperatures
Effect of thermal ageing (168h at 150°C)
on elongation at break
Electrical properties
Dielectric strength
Chemical properties
Water absorption
Resistance to fungus and decay
Value
Test
1.30 g/cm³
50 Shore D
350 %
13 N/mm²
+5% / -15%
> 3:1
50 %
85 %
DIN 53 479
DIN 53 505
DIN IEC 15C/590/CD
DIN IEC 15C/590/CD
DIN IEC 15C/590/CD
DIN IEC 15C/590/CD
-40 °C up to 120 °C
> 125 °C
not self-extinguishing
-40 °C
DIN IEC 15C/590/CD
CP-PM-1004*
DIN VDE 0304
DIN IEC 15C590/CD
DIN IEC 15C/590/CD
300 %
16 kV/mm
DIN VDE 0303 Part 2
< 0.15 %
Ra. 1
DIN IEC 15C/590/CD
Accessories
Technical Data
www.cellpack.com
111
Compression cable lugs and
Compression connectors complying with DIN
Medium Voltage 2013
DV-CU-V
Cu compression connector
complies with DIN 46267, without separator
Strain relief connector (hexagonally compressed) for copper conductor, suitable for joints.
Dimensions
D
L
L = Length
D = Centric bore hole
Q = Cross section
K = Die code no.~outer diameter
Application
• For RM/SM copper conductors
complying with DIN VDE 0295
Accessories
Type
DV-CU-V
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
625
800
1000
L
mm
D
mm
Q
mm²
K
Art.-No.
30
30
50
50
50
56
56
70
70
80
85
90
100
150
160
160
200
200
3.8
4.5
5.5
7.0
8.2
10.0
11.5
13.5
15.5
17.0
19.0
21.5
24.5
27.5
31.0
34.5
40.0
44.0
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
625
800
1000
5
6
8
10
12
14
16
18
20
22
25
28
32
38
42
44
52
58
125895
125950
125951
125952
125953
125954
125955
125956
125957
125958
125959
125960
125961
125962
125967
125963
125964
125965
To be used with suitable compression tool with DIN dies.
Fixed price – no metal surcharge
112
www.cellpack.com
Material
• Copper tin-plated
Compression cable lugs and
Compression connectors complying with DIN
Medium Voltage 2013
DVZ-CU-V-LD
Cu compression connector
complies with DIN 46267, with separator
Strain relief connector (hexagonally compressed) with separator for copper conductor, suitable for joints.
Dimensions
D
L
L = Length
D = Centric bore hole
Q = Cross section
K = Die code no.~outer diameter
Type
L
m
6
30
10
30
16
50
25
50
35
50
50
56
DVZ-CU-V-LD
70
56
95
70
120
70
150
80
185
85
240
90
300
100
To be used with suitable compression tool with DIN dies.
Fixed price – no metal surcharge
Material
• Copper tin-plated
D
mm
Q
mm²
K
Art.-No.
3.8
4.5
5.5
7.0
8.2
10.0
11.5
13.5
15.5
17.0
19.0
21.5
24.5
6
10
16
25
35
50
70
95
120
150
185
240
300
6
6
8
10
12
14
16
18
20
22
25
28
32
166374
125966
125897
125898
125899
125900
125901
125902
125903
125904
125905
125906
125907
www.cellpack.com
113
Accessories
Application
• Especially for transition sleeves and
pot end joints
• For RM/SM copper conductors
complying with DIN VDE 0295
Compression cable lugs and
Compression connectors complying with DIN
Medium Voltage 2013
DV-AL
Al Compression connector
complies with DIN 46267, without separator
Strain relief connector (hexagonally compressed) without separator for aluminium conductor, suitable for joints.
Dimensions
D
L
Application
• RM/SM, SE and RE aluminium
conductors complying with
DIN VDE 0295
Note
• *does not comply with DIN Standards
Accessories
Type
DV-AL
16*
25
35
50
70
95
120
150
185
240
300
400
500
L
mm
D
mm
55
70
85
85
105
105
105
125
125
145
145
210
210
5.8
6.8
8.0
9.8
11.2
12.6
14.7
16.3
18.3
21.0
23.3
26.0
29.0
To be used with suitable compression tool with DIN dies.
Fixed price – no metal surcharge
114
www.cellpack.com
RM/SM
16
25
35
50
70
95
120
150
185
240
300
400
500
Q
mm²
SE
25
35
50
70
95
120
150
185
240
300
L = Length
D = Centric bore hole
Q = Cross section
RM = Multi-core stranded round
SM = Multi-core stranded sector shaped
SE = Sector shaped solid
RE = Round solid
K = Die code no.~outer diameter
Material
• Blank aluminium
RE
16
25
35
50
K
Art.-No.
12
12
14
16
18
22
22
25
28
32
34
38
44
195344
195345
195346
195347
125947
125948
125888
125889
125890
125891
125892
195348
195349
Compression cable lugs and
Compression connectors complying with DIN
Medium Voltage 2013
DVZ-AL-LD
Al Compression connector
complies with DIN 46267, with separator
Strain relief connector (hexagonally compressed) with separator for aluminium conductor.
Dimensions
D
L
L = Length
D = Centric bore hole
Q = Cross section
RM = Multi-core stranded round
SM = Multi-core stranded sector shaped
SE = Sector shaped solid
K = Die code no.~outer diameter
Application
• RM/SM, SE and RE aluminium
conductors complying with
DIN VDE 0295
• Especially for transition sleeves and
pot end joints
DVZ-AL-LD
16
25
35
50
70
95
120
150
185
240
300
L
mm
D
mm
75
75
90
90
110
110
110
130
130
150
155
5.4
6.8
8.0
9.8
11.2
13.2
14.7
16.3
18.3
21.0
23.3
Q
mm²
RM/SM
16
25
35
50
70
95
120
150
185
240
300
SE
25
35
50
70
95
120
150
185
240
300
K
Art.-No.
12
12
14
16
18
22
22
25
28
32
34
198217
198219
198220
198221
198222
198223
198225
198226
198228
198230
198232
To be used with suitable compression tool with DIN dies.
Fixed price – no metal surcharge
www.cellpack.com
115
Accessories
Type
Material
• Blank aluminium
Compression cable lugs and
Compression connectors complying with DIN
Medium Voltage 2013
DK-CU-V
Cu compression cable lug
complies with DIN 46235
Cable lugs (hexagonally compressed) for copper conductors, suitable for indoor terminations.
Dimensions
D
D1
B
L
L = Length
B = Width
D = Centric bore hole
D1 = Flat hole diameter
Q = Cross section
K = Die code no.~outer diameter
Application
• Cable lugs for RM/SM copper
conductors complying with
DIN VDE 0295
Note
• *does not comply with DIN Standards
L
mm
Accessories
Type
B
mm
6/6
24
8.5
10/8*
27
13.0
16/8
36
13.0
16/12*
36
18.0
25/10
38
17.0
25/12
38
19.0
35/10
42
19.0
35/12
42
21.0
50/10
52
22.0
50/12
52
24.0
70/10
55
24.0
70/12
55
24.0
95/12
65
28.0
95/16
65
32.0
DK-CU-V
120/12
70
32.0
120/16
70
32.0
150/12
78
34.0
150/16
78
34.0
185/12
82
37.0
185/16
82
37.0
240/12
92
42.0
240/16
92
42.0
300/14*
100
48.0
300/16
100
48.0
400/16
115
55.0
500/16*
125
60.0
625/16*
135
60.0
800/20
165
75.0
To be used with suitable compression tool with DIN dies.
Fixed price – no metal surcharge
116
www.cellpack.com
Material
• Copper tin-plated
Test standard
• DIN 46235, Cable lugs for
compression connections (lug mould
for copper conductor)
D
mm
D1
mm
Q
mm²
K
mm
Art.-No.
3.8
4.5
5.5
5.5
7.0
7.0
8.2
8.2
10.0
10.0
11.5
11.5
13.5
13.5
15.5
15.5
17.0
17.0
19.0
19.0
21.5
21.5
24.5
24.5
27.5
31.0
34.5
40.0
6.4
8.4
8.4
13.0
10.5
13.0
10.5
13.0
10.5
13.0
10.5
13.0
13.0
17.0
13.0
17.0
13.0
17.0
13.0
17.0
13.0
17.0
15.0
17.0
17.0
17.0
17.0
21.0
6
10
16
16
25
25
35
35
50
50
70
70
95
95
120
120
150
150
185
185
240
240
300
300
400
500
625
800
5
6
8
8
10
10
12
12
14
14
16
16
18
18
20
20
22
22
25
25
28
28
32
32
38
42
44
52
126040
126044
126046
126048
126051
126052
126054
126055
126059
126060
126064
126065
126070
126072
126074
126077
126080
126082
126085
126087
126089
126091
126093
126094
126096
126098
126099
126102
Compression cable lugs and
Compression connectors complying with DIN
Medium Voltage 2013
DK-CU-V-LD
Cu compression cable lug
complies with DIN 46235, blocked
Cable lugs Cu (hexagonal compression type) for copper conductors, designed for outdoor terminations.
Dimensions
D
D1
B
L
L = Length
B = Width
D = Centric bore hole
D1 = Flat hole diameter
Q = Cross section
K = Die code no.~outer diameter
Type
DK-CU-V-LD
16/12*
25/10
35/12
50/12
70/12
95/12
120/12
150/16
185/16
240/16
300/16
400/16
500/16*
Material
• Copper tin-plated
Test standard
• DIN 46235, Cable lugs for
compression connections (lug mould
for copper conductor)
L
mm
B
mm
D
mm
D1
mm
Q
mm²
K
mm
Art.-No.
36
38
42
52
55
65
70
78
82
92
100
115
125
18
17
21
24
24
28
32
34
37
42
46
54
60
5.5
7.0
8.2
10.0
11.5
13.5
15.5
17.0
19.0
21.5
24.5
27.5
31.0
13.0
10.5
13.0
13.0
13.0
13.0
13.0
17.0
17.0
17.0
17.0
17.0
17.0
16
25
35
50
70
95
120
150
185
240
300
400
500
8
10
12
14
16
18
20
22
25
28
32
38
42
159667
126134
159670
126135
148432
126136
195350
126137
195351
126138
176369
126105
126106
To be used with suitable compression tool with DIN dies.
Fixed price – no metal surcharge
www.cellpack.com
117
Accessories
Application
• Cable lugs for RM/SM copper
conductors complying with
DIN VDE 0295
Note
• *does not comply with DIN Standards
Compression cable lugs and
Compression connectors complying with DIN
Medium Voltage 2013
DK-AL-LD
Al compression cable lug
complies with DIN 46329, blocked
Cable lugs (hexagonally compressed) for aluminium conductors, suitable for indoor and outdoor terminations.
Dimensions
D
D1
B
L
Note
• *does not comply with DIN Standards
L = Length
B = Width
D = Centric bore hole
D1 = Flat hole diameter
Q = Cross section
RM = Multi-core stranded round
SM = Multi-core stranded sector shaped
SE = Sector shaped solid
RE = Round solid
K = Die code no.~outer diameter
Material
• Blank aluminium
Test standard
• DIN 46329, Cable lugs for compression
connections (circular mould for
aluminium conductor)
Accessories
Type
DK-AL-LD
16/10*
25/10
25/12
35/10
35/12
50/12
70/12
95/12
95/16*
120/12
120/16
150/12
150/16
185/12
185/16
240/16
300/16
400/20
500/20
L
mm
B
mm
D
mm
D1
mm
50
50
50
62
62
62
72
75
80
80
80
90
90
91
91
103
103
116
122
20
25
25
25
25
25
25
25
30
30
30
30
30
30
30
38
38
38
44
5.4
6.8
6.8
8.0
8.0
9.8
11.2
12.6
12.6
14.7
14.7
16.3
16.3
18.3
18.3
21.0
23.3
26.0
29.0
10.5
10.5
13.0
10.5
13.0
13.0
13.0
13.0
17.0
13.0
17.0
13.0
17.0
13.0
17.0
17.0
17.0
21.0
21.0
To be used with suitable compression tool with DIN dies.
Fixed price – no metal surcharge
118
www.cellpack.com
RM/SM
16
25
25
35
35
50
70
95
95
120
120
150
150
185
185
240
300
400
500
Q
mm²
RE
16
25
25
35
35
50
SE
25
35
35
50
50
70
95
120
120
150
150
185
185
240
240
300
K
mm
Art.-No.
12
12
12
14
14
16
18
22
22
22
22
25
25
28
28
32
34
38
44
194950
194949
194947
194945
194944
194943
194942
194941
194940
194939
194938
194937
194936
194935
194934
194933
194932
194930
194908
Screw cable lugs
Medium Voltage 2013
CSK
Screw cable lugs for Cu and AI
blocked, aluminium tin-plated with shear bolts
Screw cable lugs for RM, RE, SM, and SE aluminium and copper conductors, suitable for indoor and outdoor terminations.
Dimensions
Note
• *CSK 240-400 : RM/RE cross section
from 240 to 400 mm², SM/SE cross
section from 240 to 300mm².
• Cellpack counter bracket 255404
recommended for installation.
L = Length
L1 = Centric bore hole
D = Outer diameter
D1 = Flat hole diameter
D2 = Bore hole diameter
Q = Cross section
S = Number of bolts
Type
CSK
6-50
16-95
50-150
95-240
240-400*
L
mm
L1
mm
D
mm
D1
mm
D2
mm
Q
mm²
S
Art.-No.
65
65
80
110
135
30
30
35
60
75
22.0
22.0
26.0
33.0
40.0
13
13
13
13
17
9
13
16
20
26
6 - 50
16 - 95
50 - 150
95 - 240
240 - 400
1
1
1
2
2
255414
255415
255416
289968
255418
Other screw connectors available to order.
Fixed price – no metal surcharge
www.cellpack.com
119
Accessories
Material
• Aluminium, tin-plated
Test standard
• EN 61238-1
Earthing components
Medium Voltage 2013
EGA
Earthing accessories
for cables with tape screen and/or armouring for terminations
Type EGA earthing kits for terminations for single-core cables with copper braid or aluminium screen (Fig. 1), and for
unarmoured three-core cables (Fig. 3). Kit components: 3 flat-rolled copper wires and 3 pressure springs
Dimensions
1
Note
• 1) Single core cables with copper tape
or aluminium screens, non armoured.
• 2) Single core cables with copper tape
or aluminium screens, armoured:
Please order extra pressure spring ZR1.
• 3) Three core cables with copper tape
or aluminium screens, non armoured.
• 4) Three core cables with copper tape
or aluminium screens, armoured:
Please order extra pressure spring ZR2.
Scope of delivery
• Copper wire
• Pressure spring
3
4
LS = external semi-conducting layer
BS = Cu-Tape screen
KM = Cable sheath
RF = Type RF pressure spring
ES = Cu-Earthing wire, flat tin-plated
AR = Armouring
ZR = Additional type RF pressure spring
Accessories
Characteristics
• Quick, safe and easy assembly
• Superior electrical properties
• High mechanical strength
• Suitable for indoor and outdoor use
Application
• Earthing continuity and earth contactor
• For cast resin, heat-shrink and slip-on
cable accessories
• Enables solder-free electrical
connection of metal cable components
(screen, armouring, metal sheath).
2
Copper braid
L Pressure
mm spring
Type
EGA
16-2
16-3
25-3
25-4
35-4
35-5
500
500
500
500
500
500
RF 2
RF 3
RF 3
RF 4
RF 4
RF 5
Nominal
ZR1 ZR2 Art.-No.
Ø
cross
of hole
7.2 kV
12 kV
17.5 kV
24 kV
36 kV
section
mm
mm²
8.5
16
150
120
70
50
RF 3 RF 5 143502
8.5
16
150 - 240 120 - 240 95 - 185 70 - 150
120
RF 4 RF 5 143503
10.5
25
150 - 500 120 - 500 95 - 300 70 - 300 70 - 240 RF 4 RF 6 143505
10.5
25
150 - 300 RF 5 RF 6 143506
10.5
35
500 - 1000 500 - 1000 400 - 800 300 - 800 185 - 500 RF 5 RF 6 143508
10.5
35
800 - 1000 800 - 1000 500 - 1000 RF 6
143509
For armoured cables, please order the pressure springs separately.
120
www.cellpack.com
Nominal cross section
mm²
Earthing components
Medium Voltage 2013
AUF
Armour continuity for three-core joints
Armour continuity kit for armoured three-core polymeric cables.
Dimensions
L = Length
1. Pressure spring
2. Copper wire
3. Pressure spring
Type
AUF 5
AUF 6
L
mm
Pressure
spring
1200
1200
RF 5
RF 6
Application
Scope of delivery
• Earthing continuity and earth contactor • Copper wire
• For cast resin, heat-shrink and slip-on
• Pressure springs
cable accessories
• Enables solder-free electrical
connection of metal cable components
(screen, armouring, metal sheath).
Nominal cross section
mm²
Copper
braid
35
35
Art.-No.
7.2kV
12kV
17.5kV
24kV
36kV
300
400
240
300 - 400
240
300 - 400
150
185 - 300
70
95 - 300
195367
195368
For armoured cables, please order the pressure springs separately.
www.cellpack.com
121
Accessories
Characteristics
• Quick, safe and easy assembly
• Superior electrical properties
• High mechanical strength
Earthing components
Medium Voltage 2013
RF
Pressure spring
Accessories
Characteristics
• Corrosion-resistant
• Fatigue-proof
• Guarantees consistent radial contact
stress
Application
• For cast resin, heat-shrink and slip-on
cable accessories
• Enables solder-free electrical
connection of metal cable components
(screen, armouring, metal sheath) and
earthing materials (copper grounding
wire, cooper mesh sleeve)
Colour(s)
• brass
Material
• Special stainless steel
Type
Width
mm
External-Ø
mm
Cable-Ø
mm
Art.-No.
RF 2
RF 3
RF 4
RF 5
RF 6
16
16
16
20
20
17.5
21.5
29.0
37.8
51.3
17 - 28
24 - 37
33 - 49
44 - 70
55 - 92
126296
126297
126298
126299
126300
Pressure springs are no current-carrying parts.
122
www.cellpack.com
Tapes
Medium Voltage 2013
No. 60, No. 62
High-voltage insulation tape
self-amalgamating, pliable
Type
No. 60
No. 62
Application
• Sealing of casting moulds
• Padding of cable insulation
• Conductor insulation for
plastic-insulated cables up to 69 kV
• Repairing and connection of various
insulating and cable materials e.g.
PE, XLPE, EPR, PVC, butyl, neoprene
Colour(s)
• black
Material
• EPR-Base
Length
m
Width
mm
Thickness
mm
Art.-No.
10
10
5
10
19
19
38
38
0.5
0.75
0.75
0.75
125533
145908
125584
125589
Technical Data
Elongation at break
Tensile strength at break
Dielectric constant
Dissipation factor (50Hz)
Dielectric strength
Volume resistivity
Temperature range
Water absorption
Value
900 %
3 N/mm²
2.8
0.0060
42 kV/mm
1012 Ω x cm
-40 °C up to 100 °C
0.05 %
www.cellpack.com
123
Accessories
Characteristics
• Easy application
• Fuses to form a homogeneous,
cavity-free compound within a short
space of time.
• Fully removable
• Durable
• Ozone-resistant  
• No electrolytic corrosion
• Non tacky
• Extremely ductile
• Superior electrical properties
• Excellent adherence to a wide range of
substances
• Superior physical properties
• Weatherproof
Tapes
Medium Voltage 2013
No. 61
Conductive tape
highly elastic, self-amalgamating
Characteristics
• Printed „CAUTION-CONDUCTING
TAPE“ to eliminate danger of confusion
• Fuses to form a homogeneous,
cavity-free compound within a short
space of time.
• Durable
• Ozone-resistant  
• No electrolytic corrosion
• Self-fusing
• Highly flexible
• Superior physical properties
Type
Accessories
No. 61
Technical Data
Elongation at break
Tensile strength at break
Volume resistivity
Temperature range
124
www.cellpack.com
Application
• Repairing of semi-conducting layer
in medium voltage cables
• Electrical field smoothing
• For smoothing rough surfaces of
connectors and cable lugs
Colour(s)
• black
Material
• EPR-Base
Length
m
Width
mm
Thickness
mm
Art.-No.
9.1
4.6
19
19
0.76
0.76
125590
125604
Value
900 %
3 N/mm²
10 Ω x cm
-40 °C up to 100 °C
Tapes
Medium Voltage 2013
No. 63
Copper braid tape
tinned
Type
No. 63
25mm x 9.1m
25mm x 5m
60mm x 10m
60mm x 5m
Application
• Earthing continuity and earth contactor
• Electrostatic shielding continuity
• Semi-conducting continuity for
connectors
• Voltage grading continuity
Colour(s)
• silver
Material
• Braided tinned copper wires
Length
m
Width
mm
Thickness
mm
Art.-No.
9.1
5.0
10.0
5.0
25
25
60
60
0.5
0.5
0.5
0.5
126303
126313
126316
126315
www.cellpack.com
125
Accessories
Characteristics
• Wrinkle-free application to all contours
• High flexibility
• Break-proof
Tapes
Medium Voltage 2013
No. 72
Repair tape
Characteristics
• Self-fusing
• 100% waterproof
• Superior electrical properties
• High tensile strength
Type
Accessories
No. 72
126
www.cellpack.com
Application
• Repairing of damaged sheaths of all
plastic- and rubber-insulated cables
and conductors
Note
• The use of a repair joint such as MZ is
mandatory in case of damage
extending beyond the cable sheath to
the core insulation, screen or armour.
Colour(s)
• black
Length
m
Width
mm
Thickness
mm
Art.-No.
10
25
0.75
125587
Tools
Medium Voltage 2013
CPB
Heat-shrink torch kit
Application
• Suitable for thick wall adhesive-lined
heat-shrink tubing
• Shrinking of heat-shrinkable polyolefin
products using flame or hot air on
pre-extruded compound
Caution note
• Warning: liquid gas is heavier than air.
Adhere strictly to safety instructions
provided with heat-shrink torch kit.
Type
CPB 5 (Set) *
CPB 6 (Set) *
Handle CPB 5/6 with piezo ignition
Needle point burner
Heat-shrink torch
Hot-air torch
Gas tube HD 4.4 R 3/8 LH x R 3/8 LH
Anti-rupture device for tubing R 3/8” x 3/8” LH
Pressure balance R 3/8“ x 3/8“ LH
Pressure balance DIN/Kombi 21,8-14 LH x R 3/8 LH
Refill connector, DIN Kombi
Small gas bottle, refillable
Scope of delivery
• Wooden case with aluminium profile
• Handle
• Angulated hot-air torch
• Angulated heat-shrink torch
• Angulated needle point burner
• 3 x R 3 pressure control device, 8“ li
• Anti-rupture device for tubing
• Gas tube
• Open-end spanner SW 17/19
• Small gas bottle (0.4l content), incl.
tube connection valve and suspension
hook (CPB6)
• Refill connector for a small gas bottle
(CPB6)
• 3 x DIN Kombi pressure control device
(CPB5 8“ li)
Length
m
Content
ml
4
400
Art.-No.
146765
146766
146781
146782
146783
146784
146769
146770
146780
123960
146786
146785
Delivered in an aluminium side-faced wooden case. Components can also be ordered separately.
www.cellpack.com
127
Accessories
Characteristics
• User-friendly rotating tube connector
• Gas supply shuts off automatically if
burner head not installed
• Minimal risk of overheating
• Flame extinguished immediately upon
releasing push button
• Continuously adjustable flame
• Bayonet fitting facilitates substitution
of burner head
• Quick-starting piezo ignition
Tools
Medium Voltage 2013
Clamp tool
Assembly guide for CSV screw connectors and CSK screw cable lugs
Assembly guide for CSV screw connectors and CSK screw cable lug with a diameter 14-40mm.
Scope of delivery
• Clamp tool
• Tool for diameter reduction
Type
Art.-No.
CSV/CSK
Accessories
Clamp tool
128
www.cellpack.com
255404
Tools
Medium Voltage 2013
CP-FLM20
Multi tool
The CP-FLM20 is designed for the cutting and stripping of outer cable sheaths and conductor insulation, in addition to
cold-strippable semi-conducting layers.
Characteristics
• Suitable for cables with a diameter
of 15-50mm
• For cold-strippable conducting layer.
0.3/0.4mm or 0.7/0.8mm according
to thickness of material
• Adjustable stop and limiting bar
• Cut depth of the insulation and
external sheath up to 10mm
• Suitable for PVC/PE/XLPE insulation
• Adjustable feed motion
Application
• Cutting and stripping of outer sheath
• Controlled initial cutting of
cold-strippable semi-conducting layer
• Cutting and stripping of conductor
insulation
Scope of delivery
• Allen key
• Carrying case
• CP-FLM20 Multi-tool
Replacement cutter
Multitool
Art.-No.
CP-FLM 20-S1 (for cable sheath)
CP-FLM 20-S2 (for semiconductor-layer)
CP-FLM 20
250355
250358
250351
www.cellpack.com
129
Accessories
Type
Tools
Medium Voltage 2013
CP-P20
Peeling tool
For removal of the co-extruded semi-conducting layer of medium voltage cables.
Characteristics
• Minimum strip length ca.30mm
• Stripping depth adjustable from
0-1,2 mm in 0,1mm steps
• Maintains high quality of stripped
surface
• Hard metal peeling knife
• Operating range 10-50mm
• Predefined rounded corners
• Begin stripping at cable end
• Automatic working feed
Accessories
Type
Case assembly
Peeling tool
130
CP-P 20
www.cellpack.com
Application
• Cutting and stripping of solid extruded
semi-conducting layer.
Length
mm
Width
mm
Height
mm
200
300
90
Art.-No.
255897
250354
Chemical products
Medium Voltage 2013
UNIVERSAL CLEANER 121
Detergent
Type
Universal Cleaner
No.121
No.121
No.121
No.121
No.121
Application
Colour(s)
• Cleaning of semi-conducting layers
• clear
• Removal of semi-conductive residues
(such as graphite)
• Cleaning and degreasing of motors
and electrical equipment
• Cleaning of cables and conductors
Note
• Clean all parts thoroughly. Air dry or
wipe with a cloth. Repeat operation as
required. Always test a small area prior
to cleaning plastics or finished surfaces.
Content
l
Art.-No.
0.4
1
5
20
200
146404
124026
124027
146405
124029
Technical Data
Density
Vapour pressure (at 20°C)
Flash point
Ignition temperature
Lower explosion limit (Vol.-%)
Upper explosion limit Vol.-%
Value
0.62 g/cm3
200 hPa
-19 °C
260 °C
1.1
13.0
www.cellpack.com
131
Accessories
Characteristics
• For use with Neoprene, Polyethylene,
EPR, XLPE, PVC; Butyl rubber and
thermoplastic insulation
• Protection against accidental discharge
• Cleans and degreases without leaving
residue. Non-conductive
• Fast-acting, safe
• No degradation
Chemical products
Medium Voltage 2013
ZINC SPRAY 171
Anti-corrosion spray
Zinc spray No. 171 binds to steel and iron surfaces using an electrochemical application to build a flexible protection film.
This gives the parts an active cathodic corrosion protection.
Characteristics
• Smooth, fine porous film
• With hydrocarbon propellant
(flammable)
• Varnishable
• Can be spot-welded
• Dries quickly
• Unmarked in compliance with ARB
material regulations
• No hazard rating, in compliance with
VBF
• Weatherproof
• Electrically conductive
• Frost-resistant
Type
Accessories
Zinc spray
No.171
Application
• Long-lasting corrosion protection
• Repairing of damaged zinc layer
• Repairing of galvanised surfaces
• Substitute for red lead primer
• Primer for use in auto repair
• Sealing of cavities
• Cold galvanising
• Oxidation protection
• Rust prevention
• Underground protection
Colour(s)
• grey
Content
l
Art.-No.
0.4
124030
Zinc spray No. 171 is not approved according to the the food regulations and the construction material norms release 8/76
from the Institute for Construction Technology.
Technical Data
Density
Degree of zinc purity
132
www.cellpack.com
Value
0.95 g/cm3
99 %
Chemical products
Medium Voltage 2013
INDUSTRIE 3-36
Protective agent
Type
Industrie 3-36
Application
• Dissolves rust
• Corrosion protection
• Protection of ferrous and non-ferrous
metals during storage, processing, and
transport
• Release of tightly-sealed components
• Moisture protection
Farbe
• green
Content
l
Art.-No.
0.4
5
20
200
124014
124015
124016
124013
Technical Data
Density
Viscosity (cP)
Flash point
Dielectric strength
Value
0.81 g/cm3
30/40 °C
105 °C
180 kV/mm
www.cellpack.com
133
Accessories
Characteristics
• Forms a clear, transparent film
• Lubricates and permeates
Chemical products
Medium Voltage 2013
Easy Glide
Lubricant
Easy-Glide simplifies and accelerates the feeding of cables through electrical installation conduits and cable ducts.
Damage to the outer sheath is thus avoided.
Characteristics
• Available in light, practical 1050 ml
plastic bottle or in handy
5 litre-buckets
• Agreeable odour
• Harmless ingredients
• Biologically degradable
• Non-corrosive
• Superior lubricating properties
• Non-adherent and does not stain
• Does not cause skin irritation, easily
washable
• Nonflammable
Application
• Lubricant for feeding cables and wires
through electrical installation conduits
Drum
Content
l
Art.-No.
Plastic bottle
Bucket
1.05
5
219647
246993
Type
Accessories
Easy Glide
1050ml
5000ml
Easy-Glide can be used with bare hands. Apply evenly.
Technical Data
max. Heat resistance
134
www.cellpack.com
Value
80 °C
Chemical products
Medium Voltage 2013
Easy Clean
Hand wipes
Easy Clean combines a powerful cleaning solution with a microfiber cloth developed especially for thorough wiping. The
special Easy Clean cleaning solution dissolves grime but is gentle on hands. It removes heavy fat stains, grease, glue, oil, tar,
asphalt, ink, wax, carbon stains, graphite, grass stains and resin, amongst others.
Application
• To remove ingrained dirt apply the
darker side of the cloth. Leave to soak
in, then rub. If the stain has not come
out, leave to soak for longer
• Remove most of the dirt using the
darker textured side of the cloth, then
polish with the soft side to achieve a
completely clean residue-free finish
• Skin may feel slightly sticky after use
due to moisturising emulsion, as
absorption time varies according to
skin type
Note
• For external use only
• Avoid contact with eyes
• Keep dispenser away from heat sources
• Keep out of reach of children
Type
Easy Clean
Sales display
in plastic dispenser
Content
Piece
Art.-No.
40
72
265196
264705
www.cellpack.com
135
Accessories
Characteristics
• Heavy-duty one-step cleaning system
• Easily removes even the toughest stains
• Retains dirt without leaving traces
• Quick-drying cleaning solution with
moisturising effect
• Biodegradable wipes
• Antibacterial
• Free from harmful substances
• Non-toxic
• Nonirritant
• Contains moisturising substances
136
www.cellpack.com
Medium Voltage 2013
Medium Voltage 2013
Ahead through
groundbreaking
technology
Page
Type index
138
Catalogue number index
140
Index
www.cellpack.com
137
A
Accessory Kit for Type CTS 630A Cellplux Plug-In
Cable Connectors ...................................................54
Al compression cable lug ......................................118
Al Compression connector ............................114, 115
Anti-corrosion spray ..............................................132
Armour continuity for three-core joints ...........98, 121
Assembly guide for CSV screw connectors and CSK
screw cable lugs ...................................................128
AUF ......................................................................121
AUF(BS) ..................................................................98
Index
C
Cable entry points for XLPE- and paper-insulated
cables ...................................................................100
CAE-3F ...................................................................68
CAE-3I ....................................................................67
CAE-F .....................................................................44
CAE-I ......................................................................42
CAESK-F .................................................................43
CAESK-I ..................................................................41
CAM3-S ..................................................................62
CAM-S ....................................................................35
CG .......................................................................100
CGS 250A ..............................................................46
CHE-3F(A) ..............................................................64
CHE-3F(B) ...............................................................66
CHE-3F(BS) .............................................................97
CHE-3I(A) ...............................................................63
CHE-3I(B) ...............................................................65
CHE-3I(BS) .............................................................96
CHE-F .....................................................................39
CHE-F(BS) ...............................................................95
CHE-I ......................................................................37
CHE-I ......................................................................94
CHEP(3Pb)-3F .........................................................88
CHEP(3Pb)-3I .........................................................87
CHEP(H)-3F ............................................................83
CHEP(H)-3I .............................................................82
CHEP-3F .................................................................78
CHEP-3I ..................................................................77
CHM ......................................................................33
CHM(BS) ................................................................92
CHM3 ....................................................................61
CHM3(BS) ..............................................................93
CHMP(3Pb) 3 .........................................................85
CHMP(3Pb) 3-1 ......................................................84
CHMP(H) 3 .............................................................80
CHMP(H) 3-1 .........................................................79
CHMPP(3Pb)3 ........................................................86
CHMPP(H)3 ............................................................81
CHMPPR3 ...............................................................76
CHMPR 3 ................................................................75
CHMPR 3-1 ............................................................74
CHMPRSV 3-1 ........................................................73
CHMSV ..................................................................32
CHMSV3 ................................................................59
CHMSV3-1 .............................................................60
CIK .........................................................................53
CKM .......................................................................36
CKS 630A ...............................................................56
138
www.cellpack.com
Medium Voltage 2013
Clamp tool ...........................................................128
Conductive tape ...................................................124
Connector element up to 24kV ..............................47
Copper braid tape ................................................125
Coupling connector 630A up to 24kV .....................56
CPB ......................................................................127
CPES .......................................................................57
CP-FLM20 ............................................................129
CP-P20 .................................................................130
CPS ........................................................................58
CSK ......................................................................119
CTKS 630A .............................................................50
CTKSA ....................................................................51
CTKSA ....................................................................52
CTS 630A ...............................................................49
Cu compression cable lug .............................116, 117
Cu compression connector ...........................112, 113
CVS 250A ...............................................................47
CWS 250A ..............................................................45
CWS 400A ..............................................................48
D
Detergent .............................................................131
DK-AL-LD .............................................................118
DK-CU-V ...............................................................116
DK-CU-V-LD .........................................................117
DV-AL ...................................................................114
DV-CU-V ...............................................................112
DVZ-AL-LD ...........................................................115
DVZ-CU-V-LD .......................................................113
E
Earthing accessories ........................................99, 120
Easy Clean ............................................................135
Easy Glide .............................................................134
EGA ......................................................................120
EGA(BS) ..................................................................99
Elbow plug-in cable connector ...............................48
Elbow plug-in cable connector with capacitive
measurement .........................................................45
H
Hand wipes ..........................................................135
Heat-shrink torch kit .............................................127
Heat-shrink tubing up to 36kV ..............................108
High-voltage insulation tape .................................123
I
Indoor termination .....................................77, 82, 87
INDUSTRIE 3-36 ...................................................133
L
Lubricant ..............................................................134
M
M...MS6 .................................................................27
M...MSPB6 .............................................................72
Mounting Ring .......................................................55
Multi tool .............................................................129
Medium Voltage 2013
N
Z
No. 60, No. 62 .....................................................123
No. 61 ..................................................................124
No. 63 ..................................................................125
No. 72 ..................................................................126
ZINC SPRAY 171 ...................................................132
ZS-CTS ...................................................................54
O
Outdoor termination ..................................78, 83, 88
P
Peeling tool ..........................................................130
Plug- In Surge Arrester ......................................51, 52
Pressure spring .....................................................122
Protective agent ...................................................133
R
Repair tape ...........................................................126
RF .........................................................................122
S
Screw cable lugs for Cu and AI .............................119
SEEV .......................................................................28
SEEV-F ....................................................................29
Single-core indoor termination ...................37, 42, 94
Single-core indoor termination with
screw cable lugs .....................................................41
Single-core outdoor termination .................39, 44, 95
Single-core outdoor termination with
screw cable lugs .....................................................43
Single-core straight-through joint ...............33, 35, 92
Single-core straight-through joint with
screw connector ...............................................32, 36
SMH3MS6 ..............................................................26
SRAT .....................................................................110
SRBB .....................................................................108
Straight plug-in cable connector with
capacitive measurement .........................................46
Straight-through joint .................................76, 81, 86
Straight-through joint with screw connector ...........60
T
Index
Test and Earthing Kit ...............................................57
Test-Kit ...................................................................58
Thick wall heat-shrink tubing ................................110
Three-core indoor termination ........28, 63, 65, 67, 96
Three-core outdoor termination .....29, 64, 66, 68, 97
Three-core straight-through joint ..........26, 27, 61, 93
Three-core straight-through joint with
heat-shrink outer protection ...................................62
Three-core straight-through joint with
screw connector .....................................................59
Three-core transisition joint ....................................72
T-plug and socket connexion ..................................50
Transition joint 73, 74, 75, 79, 80, 84, 85
T-socket connexion .................................................49
U
UNIVERSAL CLEANER 121 .....................................131
V
Voltage-proof Insulating Cap ..................................53
www.cellpack.com
139
123...
126...
123960...........127
126040...........116
126044...........116
126046...........116
126048...........116
126051...........116
126052...........116
126054...........116
126055...........116
126059...........116
126060...........116
126064...........116
126065...........116
126070...........116
126072...........116
126074...........116
126077...........116
126080...........116
126082...........116
126085...........116
126087...........116
126089...........116
126091...........116
126093...........116
126094...........116
126096...........116
126098...........116
126099...........116
126102...........116
126105...........117
126106...........117
126134...........117
126135...........117
126136...........117
126137...........117
126138...........117
126296...........122
126297...........122
126298...........122
126299...........122
126300...........122
126303...........125
126313...........125
126315...........125
126316...........125
124...
124013...........133
124014...........133
124015...........133
124016...........133
124026...........131
124027...........131
124029...........131
124030...........132
124318.............27
124319.............27
124320.............27
124334.............72
124335.............72
Index
125...
125533...........123
125584...........123
125587...........126
125589...........123
125590...........124
125604...........124
125888...........114
125889...........114
125890...........114
125891...........114
125892...........114
125895...........112
125897...........113
125898...........113
125899...........113
125900...........113
125901...........113
125902...........113
125903...........113
125904...........113
125905...........113
125906...........113
125907...........113
125947...........114
125948...........114
125950...........112
125951...........112
125952...........112
125953...........112
125954...........112
125955...........112
125956...........112
125957...........112
125958...........112
125959...........112
125960...........112
125961...........112
125962...........112
125963...........112
125964...........112
125965...........112
125966...........113
125967...........112
140
www.cellpack.com
132...
132464...........110
143...
143502...........120
143503...........120
143505...........120
143506...........120
143508...........120
143509...........120
144...
144876...........110
144878...........110
144880...........110
144882...........110
144884...........110
144886...........110
144888...........110
144892...........110
144898...........110
144921...........110
144935...........110
144943...........110
145...
145458.............28
145461.............28
145464.............28
145630.............26
145633.............26
145635.............26
145908...........123
146...
146158.............63
146159.............63
146160.............63
146216.............63
146217.............63
146218.............63
146220.............64
146222.............64
146224.............64
146226.............64
146228.............63
146234.............64
146235.............64
146242.............64
146296.............64
146297.............63
146298.............64
146300.............63
146301.............63
146302.............63
146303.............64
146304.............64
146306.............64
146404...........131
146405...........131
146765...........127
146766...........127
146769...........127
146770...........127
146780...........127
146781...........127
146782...........127
146783...........127
146784...........127
146785...........127
146786...........127
148...
148152.............29
148153.............29
148432...........117
Medium Voltage 2013
159...
185...
159667...........117
159670...........117
166374...........113
185050.............99
185051.............99
185052.............99
185053.............99
185054.............99
171...
193...
171756.............64
171757.............64
171761.............63
171762.............63
171763.............63
171791.............28
193339.............34
193370.............34
193372.............40
193374.............40
193414.............38
193416.............38
173...
194...
173132.............65
173134.............65
194017.............38
194018.............38
194019.............38
194030.............38
194031.............38
194032.............38
194033.............38
194034.............38
194035.............38
194036.............38
194037.............38
194038.............38
194039.............38
194040.............38
194041.............38
194042.............38
194043.............38
194044.............38
194045.............38
194046.............38
194047.............38
194048.............38
194049.............40
194050.............40
194051.............40
194052.............40
194053.............40
194054.............40
194055.............40
194056.............40
194057.............40
194058.............40
194059.............40
194061.............40
194062.............40
194063.............40
194064.............40
194065.............40
194066.............40
194067.............40
194068.............40
194069.............40
194070.............40
194071.............40
194072.............34
194073.............34
166...
176...
176369...........117
180...
180522.............65
182...
182390.............29
182731.............65
182732.............65
182733.............65
182734.............65
182735.............66
182736.............66
182737.............66
182738.............66
183...
183661...........100
183662...........100
184...
184472.............66
184796.............65
184797.............65
184798.............65
184799.............65
184800.............65
184801.............65
184802.............65
184803.............65
184805.............66
184806.............66
184807.............66
184808.............66
184809.............66
184811.............66
184812.............66
184813.............66
184815.............66
184816.............66
Medium Voltage 2013
195...
195344...........114
195345...........114
195346...........114
195347...........114
195348...........114
195349...........114
195350...........117
195351...........117
195365.............63
195366.............64
195367...........121
195368...........121
195369.............98
195380.............98
195381.............98
195382.............98
197...
197515.............77
197516.............77
197517.............77
197531.............82
197532.............82
197533.............82
197534.............82
197535.............82
197536.............82
197537.............78
197538.............78
197539.............78
197543.............83
197544.............83
197545.............83
197546.............83
197547.............83
197548.............83
197555.............87
197556.............87
197557.............87
197558.............87
197559.............87
197560.............87
197567.............88
197568.............88
197569.............88
197570.............88
197571.............88
197572.............88
197603.............74
197604.............74
197606.............74
197607.............79
197608.............79
197609.............79
197610.............79
197614.............79
197616.............79
197617.............79
197618.............75
197619.............75
197620.............75
197621.............80
197622.............80
197623.............80
197624.............80
197625.............80
197626.............80
197627.............80
197628.............84
197629.............84
197630.............84
197631.............84
197632.............84
197633.............84
197634.............84
197635.............84
197636.............84
197637.............84
197638.............85
197639.............85
197640.............85
197641.............85
197642.............85
197643.............85
197644.............85
197645.............85
197646.............85
197647.............85
197658.............76
197659.............76
197660.............76
197661.............81
197662.............81
197663.............81
197664.............81
197665.............81
197666.............81
197667.............81
197668.............86
197669.............86
197670.............86
197671.............86
197672.............86
197673.............86
197674.............86
197675.............86
197676.............86
197677.............86
198...
198217...........115
198219...........115
198220...........115
198221...........115
198222...........115
198223...........115
198225...........115
198226...........115
198228...........115
198230...........115
198232...........115
198782.............84
198783.............85
198784.............86
199...
199151.............42
199152.............42
199154.............42
199155.............42
199157.............42
199158.............42
199159.............42
199160.............42
199162.............42
199163.............42
199164.............42
199165.............42
199166.............42
199167.............42
199168.............42
199170.............67
199171.............67
199173.............67
199174.............67
199175.............67
199177.............67
199178.............67
199179.............67
199180.............67
199181.............67
199182.............67
199184.............44
199185.............44
199186.............44
199187.............44
199189.............44
199190.............44
199191.............44
199192.............44
199194.............44
199195.............44
199196.............44
199197.............44
199198.............44
199199.............44
199201.............68
199202.............68
199204.............68
199205.............68
199206.............68
199208.............68
199209.............68
199210.............68
199211.............68
199212.............68
201...
201374.............62
201375.............62
201377.............62
201379.............62
201381.............62
201382.............62
201385.............35
201386.............35
201388.............35
201393.............35
201395.............35
201942...........108
201942...........108
201943...........108
201943...........108
201944...........108
201944...........108
201945...........108
201945...........108
201946...........108
201946...........108
219...
219647...........134
220...
220775.............49
224...
224826.............49
224853.............56
225...
225844.............47
237...
237858...........108
237859...........108
237860...........108
237861...........108
237862...........108
246...
246176.............48
246993...........134
247...
247102.............48
248...
248716.............93
248717.............93
248718.............93
248719.............93
248770.............93
249...
249191.............97
249192.............97
249193.............97
249194.............97
249195.............97
249328.............96
249331.............96
249332.............96
249333.............96
249334.............96
249464.............97
249466.............97
249468.............96
249469.............96
249471.............93
249474.............93
249476.............93
250...
250351...........129
www.cellpack.com
141
Index
194074.............34
194075.............34
194076.............34
194077.............34
194078.............34
194079.............34
194080.............34
194082.............34
194083.............34
194085.............34
194086.............34
194087.............34
194088.............34
194089.............34
194090.............34
194091.............34
194092.............34
194093.............34
194094.............34
194293.............61
194294.............61
194295.............61
194296.............61
194297.............61
194298.............61
194299.............61
194300.............61
194301.............61
194302.............61
194303.............61
194304.............61
194305.............61
194306.............61
194307.............61
194908...........118
194930...........118
194932...........118
194933...........118
194934...........118
194935...........118
194936...........118
194937...........118
194938...........118
194939...........118
194940...........118
194941...........118
194942...........118
194943...........118
194944...........118
194945...........118
194947...........118
194949...........118
194950...........118
250354...........130
250355...........129
250358...........129
250711.............49
250715.............49
250720.............48
250726.............48
251...
251713.............36
252...
252101.............36
253...
253843.............92
253844.............92
253845.............92
253847.............94
253848.............95
253849.............94
253850.............95
253911.............93
253917.............93
253929.............93
255...
255404...........128
255414...........119
255415...........119
255416...........119
255418...........119
255897...........130
256...
256010.............49
256328.............49
256838.............50
256839.............50
257...
257581.............50
257582.............50
257622.............54
Index
258...
258130.............32
258131.............32
258132.............32
258133.............32
258135.............32
258136.............32
258137.............32
258138.............32
258140.............32
258141.............32
258142.............32
258143.............32
258144.............32
258145.............32
258146.............32
259...
259101.............57
262...
262054.............51
262055.............51
262056.............51
262816.............51
264...
264366.............55
264705...........135
264769.............73
264988.............73
265...
265023.............53
265024.............53
265196...........135
265205.............73
265501.............73
289...
289894.............43
289897.............43
289898.............43
289899.............43
289900.............43
289901.............43
289902.............43
289903.............43
289904.............43
289905.............43
289906.............43
289907.............43
289908.............43
289909.............43
289910.............43
289911.............43
289912.............43
289945.............41
289947.............41
289948.............41
289949.............41
289950.............41
289951.............41
289952.............41
289953.............41
289954.............41
289955.............41
289956.............41
289957.............41
289958.............41
289959.............41
289960.............41
289961.............41
289962.............41
289963.............41
289968...........119
132...
293792.............45
142
www.cellpack.com
293797.............46
295...
295167.............45
295283.............46
297...
297104.............59
297260.............59
297310.............59
297311.............59
297348.............59
297349.............59
297350.............59
297351.............59
297352.............59
297353.............59
297358.............59
297360.............59
297361.............59
297362.............59
297433.............59
297441.............60
297442.............60
297443.............60
297444.............60
297449.............60
297460.............60
297461.............60
297462.............60
297463.............60
297464.............60
297465.............60
297466.............60
297467.............60
297468.............60
297469.............60
301...
301492.............52
302...
302227.............58
302732.............49
304...
304089.............98
304092.............99
Medium Voltage 2013
Index
Medium Voltage 2013
www.cellpack.com
143
Cellpack AG Electrical Products
Anglikerstrasse 99
5612 Villmergen
Schweiz
Tel. +41 56 618 12 34
Fax +41 56 618 12 45
verkauf.ep@cellpack.com
Cellpack Far East (PTE) LTD.
128 Joo Seng Road # 06 – 01
Singapore 368356
Tel. +65 6747 7024
Fax +65 6841 4554
info@cellpack.com.sg
Cellpack GmbH
Carl-Zeiss-Straße 20
79761 Waldshut-Tiengen
Deutschland
Tel. +49 7741 6007-0
Fax +49 7741 64989
electrical.products@cellpack.com
Behr Bircher Cellpack BBC Malaysia
Sdn. Bhd.
No. 8, Jalan TU 50
Taman Tasik Utama
Ayer Keroh
75450 Melaka
Malaysia
Tel. + 60 6 251 95 30
Fax + 60 6 251 95 31
info@cellpack.com.my
www.cellpack.com.my
Cellpack Benelux B.V.
Keersluisweg 13
1332 EE Almere Buiten
Nederland
Tel. +31 36 549 03 36
Fax +31 36 532 74 99
info@cellpack.nl
Behr Bircher Cellpack Ibérica, S.A.
C/.Mas Pujol, nr. 47 – Nave 4
Pol. Ind. Sector V
08520 – Les Franqueses del Vàllès
Barcelona – España
Tel. +34 93 846 63 76
Fax +34 93 849 12 06
comercial@cellpackiberica.com
Behr Bircher Cellpack BBC France s.à.r.l.
277, Boulevard des Technologies
54710 Ludres
France
Tel. +33 3 83 25 60 07
Fax +33 3 83 25 88 27
info@cellpack-ep.fr
Cellpack Polska Sp. z o.o.
ul. Matuszewska 14,
03-876 Warszawa
Polska
Tel. +48 022 853 53 54
Fax +48 022 853 53 56
biuro@cellpack.pl
www.cellpack.com