Station ALS Multi 160

Transcription

Station ALS Multi 160
 Central Denmark Region (Region Midtylland)
FAO Project Department of the
New University Hospital (PA-DNU)
Hedeager 3
DK-8200 - Aarhus N, Denmark
Ne/-
Tilbudsfase:
04.03.2013
RFT 73086 - F2-12-00 - DNU - Rørpost
1 Response form, item 2.5
Dear Sir or Madam, We are pleased to participate and apply for tender of 73086 F2‐12‐00 ‐ DNU – Rørpost project. Kindly find hereafter data sheets of offered component  Station Type 4 – Auto‐unload to KBA (laboratory) according to description at 3.5.3 PTS statement of work. Yours faithfully
Günther Neudeck Sales Export Manager Ing. Sumetzberger GMBH. Leberstr. 108 A‐1110 Vienna Tel.: +43 1 74035 304 Fax: +43 1 74035 300 Mobile: +43 664 627 66 25 E‐mail: g.neudeck@sumetzberger.at Web: http://www.sumetzberger.at VAT No. ATU37204100 Commercial register No. FN 118934 Commercial court: Vienna Ing. Sumetzberger GMBH. A‐5020 Salzburg, Matzenkopfgasse 35 Tel.: 0662 43 03 93 0 Fax: 0662 43 03 93 20 UID.: ATU 37204100, Firmenbuch FN 118934 d. Handelsgericht Wien, DVR‐Nr.: 0608122
8
7
6
5
0
10
20
4
30
40
50
60
70
3
80
90
1
2
100
407
Multi Carrier Receive Tube
F
F
Multi Carrier Send Tube
E
system bend 160
E
427
lift 160
233 494
motor slide valve
394
system tube 160
944
D
1015
D
ejection bend right 160
800
Station ALS Multi
C
C
automatic opening
682
ALS slide
B
Änd.5:
Änd.4:
Änd.3:
Änd.2:
Änd.1:
gez.: 12.02.2013 f.parrer
Datum
Name
A
B
R
Rohrpostsysteme
A-1110 Wien, Leberstrasse 108, Tel.: +43/1/74035/0, Fax.: +43/1/74035/340
E-Mail: pt.technics@sumetzberger.at / Homepage: www.sumetzberger.at
Bemerkung
Aarhus University Hospital
Projekt:
Zeichnungstitel:
DIESE ZEICHNUNG IST GEISTIGES EIGENTUM DER Fa. SUMETZBERGER UND GESETZLICH GESCHÜTZT: JEDE
UNBEFUGTE BENÜTZUNG, VERVIELFÄLTIGUNG, ÜBERARBEITUNG UND WEITERGABE AN DRITTE IST VERBOTEN,
STRAFBAR UND VERPFLICHTET ÜBERDIES ZUM SCHADENERSATZ. KONSTRUKTIVE DETAILS SIND NICHT
VERBINDLICH! (URHEBERGESETZ BGBL. NR. 111/1936, 206/1949, 106/1953)
Artikelcode:
ALS-Multi Carrier
Material:
Laboratory
Normen:
8
7
6
5
DIN ISO 2768 T1 mittel
Oberfläche: Oberfläche/Farbe
File:
ALS-Multi.idw
Maßstab:
Format:
A3
PNEUMATIC TUBE SYSTEMS
Automatic Unloading Station
11
PNEUMATIC TUBE SYSTEMS
AUTOUNLOAD Station MCT-ALS
Advantages Automatic Carrier Unloading
• Fully automatic sample unloading
• Multi Carrier Transport for sending and
receiving
• No time consuming manual carrier
manipulation
• carriers always available at sending
stations because of immediate automatic
return
• Space required: 728 x 682 x 407 mm
(h x w x d) at example layout
14
PNEUMATIC TUBE SYSTEMS
AUTOUNLOAD Station MCT-ALS
15
PNEUMATIC TUBE SYSTEMS
AUTOMATIC UNLOADING
WKO “MERCUR ´12” Life Sciences Innovation Award
8
Station ALS Multi 160
Installation and operation manual
Version 1.0.5
Note:
Ing. Sumetzberger GMBH. reserves the right to do modifications on their products, which serve the
technical development of the products. These modifications are not necessarily recorded in each
particular case. This documentation and the contained information are recorded and arranged with the
necessary diligence, but Sumetzberger takes no guarantee for printing errors or other faults or resulting
damages. The brand and products named in this documentation are trademarks or registered trademarks of the particular title holder.
Ing. Sumetzberger GMBH.
Leberstraße 108
A-1110 Vienna
Telephone
+43.(0)1.74035 0
Fax
+43.(0)1.74035 300
E-mail (Technical support)
pt.technics@sumetzberger.at
E-mail (Sales)
pt.sales@sumetzberger.at
Þ Homepage
© Copyright 2012 Ing. Sumetzberger GMBH.
www.sumetzberger.com
CONTENTS
Station ALS Multi 160
1
General
General description ................................................................................... 4
Technical data .......................................................................................... 6
Function description .................................................................................. 7
2
Data sheet
Data sheet - PHA2000 ............................................................................... 9
Data sheet - RFID 2000 ............................................................................. 10
Data sheet - Sensor MHT1-P122................................................................. 11
3
Installation
Necessary tools and materials .................................................................... 12
Appliance and mounting dimension ............................................................ 13
Mounting drills .......................................................................................... 16
Mounting – Carrier rack ............................................................................. 17
4
Cabling
General - System cable.............................................................................. 18
Station ALS Multi....................................................................................... 19
5
Spare parts
Station ALS Multi....................................................................................... 24
Station Lift 160 ......................................................................................... 26
Automatic opening .................................................................................... 27
6
General Safety Instructions
Label for devices ....................................................................................... 29
7
Maintenance Manual
Station ALS Multi....................................................................................... 30
General 1 - 4
15.11.2012
Station ALS Multi 160 - Version 1.0.5
General
General description
Model
Station ALS Multi
Manufacturer
Ing. Sumetzberger G.m.b.H
Leberstraße 108
A-1110 Vienna
General
Microprocessor-controlled pneumatic tube station for transport of samples
and other pharmaceutical products. The carrier is automatically opened and
emptied. Therefore only APA carriers can used.
Type of construction
Sending and Receiving Station
System
The carrier passes automatically the lift station above the Station ALS Multi.
Following the carrier stops at the two motor slide valves. Only after the carrier
is locked into the Station ALS Multi. There will be checked to what kind of
carrier it is. In the case of an APA carrier it is automatically opened, emptied
and re-sent. In the case of other carriers, they were sent back again without
emptying.
Station selection
The operation is done menu-controlled over a keyboard and a clear text display (individually programmable target numbers and addresses).
The keyboard offers the user a 5-digit target selection with an accompanying
16-digit user text.
Application Range
Lift station with automatical opening
Target information
Carrier returns after back to its programmed homestation.
Control
Microprocesser-controlled
Power failure
The system is built in a way that after a power failure it is self-examining and
if necessary self-repairing.
System diagnosis
A self-disturbance program, a control of the condition of the unit and the
course of operation make a safe operation possible
Mounting
Inndoor at the wall
Safety requirements
The station was tested according to office- and industry standards. (EMV etc.)
Accessories
Holding device for carriers
Errors and omissions excepted.
General 1 - 5
15.11.2012
Station ALS Multi 160 - Version 1.0.5
Carriers
Errors and omissions excepted.
Following carriers can be used:
• RP46004A (Loading dimension 265x110mm)
• RP46004C (Loading dimension 265x110 mm)
• RP46004I (Loading dimension 330x110 mm)
• RP46004J (Loading dimension 330x110 mm)
General 1 - 6
15.11.2012
Station ALS Multi 160 - Version 1.0.5
Technical data
Model
Station ALS Multi
Performance
The station is designed as a fully automatic dispatch and receiving unit
and can only be used as end station.
Mechanical features:
• self-adjusting maintenance-free gaskets
• sturdy mechanism with “soft” drive by V-belts
• contactless dimensioned motor
Appliance dimensions
728 x 682 x 407 mm (h x b x t)
Packing dimensions
(h x b x t)
Weight
gross: 35,5 kg
Casing
steel cover RAL1013 white
Electric Supply
The station is supplied by the power supply unit with 30 V
Electricity uptake of the station when ready for operation 120 mA
Electricity uptake of the station when receiving or sending 1,2 - 1,5 A
Electricity limitation of the station 4 A
Type of drive / internal
Direct current gear motor over V-belt:
30 VDC
max 10 A (electricity limitation at 4 A)
2,5 NM
37 RPM/min
Noise level
Measurement at a distance of 1 meter:
Dispatch: max. 66 dbA
Receiving: max. 55 dbA
Type of control
Tableau, SCB 2000, clear text display with keyboard
Clock frequency
20 MHz
Dispatch and receipt
weigth
The carrier can maximally be loaded with a capacity of 0,5 kg.
Kind of protection
according to DIN40050
IP 53
Errors and omissions excepted.
Net: 37,5 kg
General 1 - 7
15.11.2012
Station ALS Multi 160 - Version 1.0.5
Function description
The two positions of the Station ALS Multi and their functions:
2%#%)6%
2%#%)6%
3%.$
3%.$
0OS
-
-
3ENSORFORMONITORINGTHE
DISCHARGEOFTHECARRIER
Errors and omissions excepted.
$ISCHARGEOF
FALSECARRIERS
-
General 1 - 8
15.11.2012
Station ALS Multi 160 - Version 1.0.5
2%#%)6%
2%#%)6%
3%.$
3%.$
0OS
0OS
-
-
!UTOMATICALOPENING
OFTHECARRIER
%*%#4)/.
Pos. 1
Arrival / Discharge position
Pos. 2
Eject / Dispatch position
Errors and omissions excepted.
-
Data sheet 2 - 9
15.11.2012
Station ALS Multi 160 - Version 1.0.5
Data sheet
Data sheet - PHA2000
Model
PHA2000
Manufacturer
Sumetzberger GmbH
Leberstraße 108;
1110 Vienna
Using
Expansion card: Secure Receive
Function
Secure carrier receive or pharmacy function:
Received carries are stored in the arrival station and they are not ejected
automatically. Because of this, sendings are secure from unauthorised
users. Authorise users are requested to put in a code or hold the smart
card to the control desk to receive the carrier.
Measurement
70 x 50 mm
Figure
Part
PLATINE PHA 2000-4 PHARMACY/SECURED
REC programmiert
QS
Errors and omissions excepted.
Order No.
RP44874-4
Remark
PHA2000 circuit board;
Extension for Secure Receive
Data sheet 2 - 10
15.11.2012
Station ALS Multi 160 - Version 1.0.5
Data sheet - RFID 2000
Model
RFID 2000
Manufacturer
Sumetzberger GmbH
Leberstraße 108;
1110 Vienna
Use
Extension card: Code Tag
Function
By equipping the carrier with passive transponder (no battery), called
code tags on both ends, all the carries can be receiving there own
identification number and so they can be assigned to a determinate
station. The consignment back to this “homestation” is possible without
entering the address.
Because of this only carriers which are registered to the system can be
used and not registered carriers cannot be infiltrated into the system.
Follow stations can be equipped: DRT110, DRT Front 110 E3S110,
MSS110/160, DST160, DST-END160.
Technical data
Sending frequency: 125 kHz
Exciting frequency: 125 kHz
Figure
Part
PLATINE RFID 2000 4-FACH/4-FOLD READER
QS
Errors and omissions excepted.
Order No.
RP44873C
Remark
RFID2000 Circuit board 4times
for MSS 160/6" (Extension Code
Data sheet 2 - 11
15.11.2012
Station ALS Multi 160 - Version 1.0.5
Data sheet - Sensor MHT1-P122
Model
MHT1-P122 Photoelectric proximity switch
Manufacturer
SICK GmbH
Technical data
Scanning distance typ. max.
Light source
Output current IA max.
0 - 50 mm
LED, infrared
50 mA
Response time
Type of connection
Enclosure rating
Ambient temperaure
< 2,5 ms
Cable 2 m
Housing IP40
Operation -25 ... +50 °C
Storage
-40 ... +70 °C
ABS
Housing material
Dimension
1
2
3
4
5
6
Connection cable 2 m, 3x 0,25 mm2
Optic axis sensor
Optic axis receiver
LED function indicator
Translucent rearside
Mounting slots
Part
OTS REFLEXIONS-LICHTTASTER MHT1-P122 50
MM MIT HGA PNP-OUT HELLS 1016051 QS
Errors and omissions excepted.
Order No.
RP45204
Remark
OTS switch
Installation 3 - 12
15.11.2012
Station ALS Multi 160 - Version 1.0.5
Installation
Necessary tools and materials
Following materials are required for installation and maintenance of the station:
Material (* pcs. or * m = Depending on the use of the station and the local situation)
1
1
pcs.
pcs.
Station ALS Multi
Base frame for Station ALS Multi
RP46684
RP46621
2
2
1
1
pcs.
pcs.
pcs.
pcs.
Platine RFID2000
Platine SCB2000
Platine PHA2000
Relay Box
RP44873C
RP45760
RP44874-4
RP46481
1
2
pcs.
pcs.
Station Lift NW160
Motor slide valve NW160
RP32521B
RP43838R
4
4
4
4
pcs.
pcs.
pcs.
pcs.
Stair bolt M10 x 100 mm
Hexagonal nut M10
Washer M10
Dowel Ø 12 mm
Q 145052
QM00M10
QS00M10
Q 060012
1
2
pcs.
pcs.
Sleeve NW160
Hose clamp 160
RP31134
RP31685
*
*
*
*
m
m
pcs.
pcs.
System cable
Tube NW160
Bend NW160, R800
Bend NW160, R1200
K S118
RP30512B
RP30341
RP30107
60
4
*
mm
pcs.
pcs.
Shrink hose
Wire end caps 2,5² blue
Adhesive Tangit PVC-U (125 g tube)
Adhesive Tangit PVC-U (1 kg box)
RP32513
Q 561005
RP32481
RP32482
Tools (+ = These tools are not provided by company Sumetzberger)
Tape measure
Drilling machine inclucluding drills
Screwdriver set
Hexagon screw driver set
Socket wrench boxes
Diagonal cutting nipper (flat cuts)
Pliers - Stoko
Pliers - Variocrimp (Wago)
Iron saw
Cable knife
Wire stripping pliers
Measuring instrument - Multimeter
Logic tester
Hot air dryer
Hole saw Ø40 mm
Cable tester
Errors and omissions excepted.
+
+
+
+
+
RP32148
RP32146
RP41804
+
+
+
+
RP43424
+
+
RP44138
Installation 3 - 13
15.11.2012
Station ALS Multi 160 - Version 1.0.5
Appliance and mounting dimension
Symbol Isometry
Station ALS Multi
407
682
240
530
394
728
630
394
51
n160
Part
STATION LAU 160x3,2 SCB2000 RAL1013
LINEAR-AUTOUNLOAD STATION
Errors and omissions excepted.
Order No.
RP46684
Remark
Station ALS Multi
Installation 3 - 14
15.11.2012
Station ALS Multi 160 - Version 1.0.5
Base frame for Station ALS Multi
30
161
153
30
670
30
50
30
50
670
620
Part
ALL 160x3,2 GRUNDGESTELL 670x378x153mm
St37-2 vzkt
378
25
620
670
Errors and omissions excepted.
328
328
50
328
50
25
328
50
Order No.
RP46621
Remark
Base frame
Installation 3 - 15
15.11.2012
Station ALS Multi 160 - Version 1.0.5
Motor slide valve 160
213,4
106,7
140
141
45
53
132,2
160
437,7
Ø160
Part
SHB 160 8PIN CONNECTOR MOTOR SLIDE
VALVE INKL.ANTENNE
Errors and omissions excepted.
Order No.
RP43838R
Remark
Motor Slide Valve incl. Antenna
Installation 3 - 16
15.11.2012
Station ALS Multi 160 - Version 1.0.5
Mounting drills
Following mounting drills are necessary for the installation of the station.
Centre line
tube station
300
294
530
47
605
Mounting material for Station
4 pcs. Dowel ∅ 12 mm
Order no.: Q 060012
4 pcs. Stair bolt 10x100 mm
Order no.: Q 145052
4 pcs. Hexagonal nut M10
Order no.: QM00M10
4 pcs. Washer M10
Order no.: QS00M10
2 pcs. Sleeve NW160
Order no.: RP31134
4 pcs. Hose clamp
Order no.: RP31685
Errors and omissions excepted.
Installation 3 - 17
15.11.2012
Station ALS Multi 160 - Version 1.0.5
Mounting – Carrier rack
Carrier Rack for 5 Carriers. Following measurements are given:
Part
BA 5x63-132 RAL7001 HÜLSENABLAGE
CARRIER RACK SILBERGRAU
BA 5x63-132/4" RAL1013 HÜLSENABLAGE
CARRIER RACK
QS
Errors and omissions excepted.
Order No.
RP30798
Remark
Carrier Rack grey(RAL7001)
RP30798W
Carrier Rack white(RAL1013)
Cabling 4 - 18
15.11.2012
Station ALS Multi 160 - Version 1.0.5
Cabling
General - System cable
When preparing the system cables of the station, please pay attention to the following:
•
Strip insulation of the outer cover of the system cable and the impact resistant sheet lying beneath to 150mm.
•
Strip the insulation of the outer cover of the system cable and the impact resistant sheet of the data cable
(0,22²) to 20mm. Remove the sheet screen. Wrist the screen wire and shrink it with a shrink hose 0,5-1mm
(Mat.No.RP32513) over the whole length. The wires of the bus cable (0,22²) are entered according to the color
code into the 5-pole Stoko-plug (Order no.RP32811). The plug is compressed with pliers. (Order no.:RP32146)
•
Afterwards the outstanding wires are precisely cut with a diagonal cutting nipper (Order no.:RP32148) at the
side edges of the plug. (Attention: the used diagonal cutting nipper has to have a flat cutting edge, since outstanding cables may cause errors.)
•
The two remaining power supply wires (2,5²) are shortened by 30mm, Strip their insulation on a length of
10mm.
•
The wire end caps with a collar of synthetic material in blue -2,5²- (Mat.No.Q561005) are put over the cable
ends and pressed with Variocrimp pliers 4 (WAGO). (Order No.: RP41804)
The above description applies to all system cables in the Sytem MP10.000
Errors and omissions excepted.
Cabling 4 - 19
15.11.2012
Station ALS Multi 160 - Version 1.0.5
Station ALS Multi
Schematic cabling Station ALS Multi
tube switch X5
to blower
Relay
box
Lift Station
tube switch X4
Motor slide valve
NW160
SCB
tube switch X6
Motor slide valve
NW160
SCB
tube switch X5
Basket full sensor
tube switch X5
Basket full sensor
Station ALS Multi
SCB
Reed X2
DCB
DISPATCH
Detail Station ALS Multi
Reed X1
RECEIVE
tube switch X6
Basket full sensor
Motor
tube switch X4
Swivel arm
Automatic opening
tube switch X6
Automatic opening
Swivel arm
tube switch X5
Basket full sensor
SCB
Reed X2
DCB
DISPATCH
Reed X1
RECEIVE
tube switch X6
Basket full sensor
Motor
tube switch X4
Automatic opening
tube switch X6
Automatic opening
Swivel arm
Errors and omissions excepted.
Swivel arm
Cabling 4 - 20
15.11.2012
Station ALS Multi 160 - Version 1.0.5
Cabling Station ALS Multi
For a secure operation of the station the system cable A (A=incoming cable) as in chapter 4 page 1 has to be
prepared. The connection of the cable must not be done under voltage.
Part 1 - Automatic opening, Swivel arm and Lift Station
PHA2000_1
Errors and omissions excepted.
Cabling 4 - 21
15.11.2012
Station ALS Multi 160 - Version 1.0.5
Part 2 - DCB, Tube switches and Reed sensor
Errors and omissions excepted.
Cabling 4 - 22
15.11.2012
Station ALS Multi 160 - Version 1.0.5
Cabling Seperator (Lift, Motor slide valve)
For a secure operation of the station the system cable A (A=incoming cable) as in chapter 4 page 1 has to be
prepared. The connection of the cable must not be done under voltage.
PHA2000_1
Pin 3
Pin 5
K E0419 red
K E0410 blue
Errors and omissions excepted.
K E0411 brown
K E0419 red
K E0419 red
K E0411 brown
K E0412 black
K E0412 black
K E0419 red
Pin 4
Pin 4
Pin 1
Pin 3
Pin 5
Pin 2
Pin 2
Pin 5
Pin 3
Pin 1
Pin 4
Cabling 4 - 23
15.11.2012
Station ALS Multi 160 - Version 1.0.5
Cabling SCB and Motor slide Valve
For a secure operation of the station the system cable A (A=incoming cable) as in chapter 4 page 1 has to be
prepared. The connection of the cable must not be done under voltage.
Errors and omissions excepted.
Spare parts 5 - 24
15.11.2012
Station ALS Multi 160 - Version 1.0.5
Spare parts
Station ALS Multi
3
1
2
4
5
6
7
8
8
8
9
Errors and omissions excepted.
8
Spare parts 5 - 25
15.11.2012
Station ALS Multi 160 - Version 1.0.5
No.
Part
Order No.
1 MOTOR 100.606,24VDC,2.5NM,37UM 10 WATT RP31166
TYPE (DRT,W3F)
QS
2 PLATINE DCB 2000/2 (DIVERTER CONTROLLER) RP45766
STEUERRECHNER MOT.IC/CIRCUIT BOARD QS
3 PLATINE PHA 2000-4 PHARMACY/SECURED REC RP44874-4
programmiert
4 KOPPELRELAIS 10A 24V DC 1W 40.31
V K535214
5
6
7
8
9
LIFT RITZEL LAGERBOLZEN 10,10,L=26mm
RP1417 PA6+25%GF;INKL:NACHARBEIT;
QS
SPANNSTIFT DIN1481 5X28 GEPR
BN876/132917
REEDSCHALTER SCHWARZ 59025-2-V-05A/0,22 HAMLIN
PRALLPOLSTER für RP-STATIONEN BG komplett
30x30mm M&
LAS FÜHRUNGSSCHIENE l=500mm
QS
Errors and omissions excepted.
Remark
Motor (DRT, W3F) 24VDC;
2.5Nm 37min-1 10W
circuit board 2000/2
Platine PHA2000
Coupling relay
RP32587
Lift pinion bearing pin
QL00528
Locking pin DIN1481 5x28
RP32767H
Reed switch black
RP45747B
cushion
RP46656H
slide rail
Spare parts 5 - 26
15.11.2012
Station ALS Multi 160 - Version 1.0.5
Station Lift 160
1
2
3
5
4
No.
Part
Order No.
Remark
RP45204
OTS switch
1 OTS REFLEXIONS-LICHTTASTER MHT1-P122 50
MM MIT HGA PNP-OUT HELLS 1016051 QS
RP32602
Lift construction grp. 2; belt
2 LIFT BAUGRUPPE 2 RIEMENTRIEB LINKS
RP1582 NW63-160
QS
drive left
3 LIFT BAUGRUPPE 3 RIEMENTRIEB RECHTS
RP32603
Lift construction group. 3; belt
RP1583 NW63-160
QS
drive right
4 LIFT BAUGRUPPE 4 160
RP32604-160 Lift CG 4 Ground plate + motor
GRUNDPLATTE+MOTOR RP2651
unit
5 AL 160x3,2 LIFT ZAHNSTANGE M-2 20x20mm
RP46620M
toothed rack l=300mm
l=300mm
Errors and omissions excepted.
Spare parts 5 - 27
15.11.2012
Station ALS Multi 160 - Version 1.0.5
Automatic opening
2
4
2
1
8
3
1
6
5
7
No.
1
2
3
4
5
6
7
8
Part
ADERNENDHÜLSE 0.5 weiss/ISOL. WIRE END
CAP Verp = 100Stk
ADERNENDHÜLSE 0.75 grau/Isoliert
Gesamtlänge=14mm Verp = 100Stk
ADERNENDHÜLSE 0,25 ISOL. 167/H WIRE END
CAP Verp = 100Stk
SENKSCHRAUBE DIN 965A M 4X12 VERZINKT
0048 4 12
Scheibe DIN 125 A M 4 VZKT Beilagscheibe M
4 VZKT E03462
APA 160 LADEROHR HEBELSTÜTZE
(RP43297A)
APA 160 FÜHRUNGSBLOCK
Order No.
Q 561001
Remark
Wire end caps 0.5mm
Q 561002
Wire end caps 0.75mm
Q 561022
Wire end caps 0.25mm
Q230412
RP43067C
Countersunk screw DIN965
M4x12
Attaching disk DIN125A M4 zincplated
sley tube bracket
RP43067D
sley tube track
OTS REFLEXIONS-LICHTTASTER MHT1-P122 50
MM MIT HGA PNP-OUT HELLS 1016051 QS
RAU 160/6" ÖFFNUNGSMECHANIK
SENSORMECHANIK (ANKUNFT VON OBEN)
OTS REFLEXIONS-LICHTTASTER WTB140-P132
11x20x31mm PNP-OUT 10-30VDC 2-500mm
APA SPEICHER BG HEBEL KOMPLETT ÖffnungsAutomatik
RP45204
OTS switch
RP46044
opening mechanic
RP46027
OTS reflective switch
RP41052C
lever automatic opening
Errors and omissions excepted.
QS00M04
General Safety Instructions 6 - 28
15.11.2012
Station ALS Multi 160 - Version 1.0.5
General Safety Instructions
Before putting the pneumatic tube system into service, please read the users
manual carefully. The system may only be used by persons who are acquaint to
the system. Please keep the manual for a later use.
Don’t try to maintain or repair the system by your own. Opening Casings and
covers may lead to exposed voltage keeping or mechanical (mobile) parts of the
devices. Caution! Leave maintenance works to a qualified service department.
Never grasp into the tube openings of the station with your hands. Keep station
doors closed all the time. Caution: Risk of getting hurt.
Take care, not to get foreign objects into the pneumatic tube station. Avoid liquids
and moisture near the station.
If there is a undesired material or liquid in the station, please shut down the
system and inform your qualified service department.
Avoid magnetic fields in the stations area.
The system is exclusively designed for the sending of suitable Carriers. Please use
only Co. Sumetzberger carriers.
CAUTION: Electronic parts contain CMOS components. Don’t touch with your
fingers.
surrounding temperature: 0-50°C.
Errors and omissions excepted.
General Safety Instructions 6 - 29
15.11.2012
Station ALS Multi 160 - Version 1.0.5
Label for devices
CAUTION
Only to be used by trained and
authorized persons.
CAUTION
Risk of getting hurt.
Never grasp into the tube
openings of the station with
your hands.
If this label is needed, it can be ordered with the order number RP45222 from Sumetzberger.
Errors and omissions excepted.
Maintenance Manual 7 - 30
15.11.2012
Station ALS Multi 160 - Version 1.0.5
Maintenance Manual
Station ALS Multi
Preventive maintenance is a schedule of planned maintenance actions aimed at the prevention of breakdowns and
failures before it actually occurs and enhance equipment reliability by replacing worn components before they
actually fail.
ATTENTION
Preventive maintenance works have to be carried out
every three month !
Cleaning
•
Clean inside and outside of the station using synthetic cleaner "Exakt EXTRA".
CAUTION
Do not spray the cleaner on the circuit board or
connectors, because the circuit board will be destroyed!
Mechanical tests
•
Adjust slide valve position. Test function of slide valve
•
Check function and ease of steering of the revolving part inside the station disassembling and cleaning
•
Check positioning switches
•
Adjust positioning of station
•
Check contact and tight seat of every solder point, plug in connection and clamp
•
Check tight seat of the motor devices
•
Check V-belt (increase tension if necessary)
•
Check mounting, function and examine mechanical damages of the whole station
•
clean the whole station
•
Initiate self -test
Electrical tests
•
Operational check of the tube switch for changing direction (between sucking-blowing)
•
Check function of tube switch (LED lights green as soon as tube switch detects)
•
Check (measure) positioning switches
•
Check (measure) motor current
•
Check (measure) source voltage (idle motion and under load)
Errors and omissions excepted.