BIG-8 REFLECTIVE DUCT INSULATION
Transcription
BIG-8 REFLECTIVE DUCT INSULATION
TECHNICAL DATA SHEET BIG-8 REFLECTIVE DUCT INSULATION www.rFOIL.com Product Description: rFOIL™ Big-8 Reflective Duct Insulation consist of two layers of thick polyethylene bubble pack reflective insulation separated by 2-inch wide strips of bubble pack insulation. This product has on it a code certification strip that identifies the brand name and pertinent testing information for duct applications. This inspector friendly tape means no hassles at the jobsite and peace of mind for installers. The Big-8 Reflective Duct Insulation has been tested to an R-8 and is classified as Class 1/Class A in accordance with the ASTM E84-09 fire test standard. The product was mounted in accordance to ASTM-E2599-08. REFLECTIVE SURFACE BUBBLE BUBBLE REFLECTIVE SURFACE BUBBLE Stock Sizes Available (Rolls): Size Part No. 48" X 50' 2280-48-050 Features: - R-Value 8 - Approved vapor barrier protection - Inhibits condensation, mould and fungi growth - Improves HVAC system efficiency - No foam corner spacers needed - Thermal performance unaffected by moisture - Non-Toxic / Non-Carcinogenic Applications: - Duct Insulation without spacers (R-8) Physical Properties Test Value THERMAL RESISTANCE TEMPERATURE RANGE FIRE RATING EMISSIVITY REFLECTIVITY WATER VAPOR PERMEABILITY RESISTANCE TO FUNGI & BACTERIA BLEEDING and DELAMINATION PLIABILITY ASTM C335 ASTM C411 ASTM E84-09 ASTM C1371 ASTM E903 ASTM E96 ASTM C1338-08 ASTM C1224-03 ASTM C1224-03 TEMPERATURE and HUMIDITY RESISTANCE ASTM C1258 R-8 with BUBBLE SPACERS 250 +/- 25OF CLASS 1 / CLASS A 0.04 0.096 0.029 Perms DOES NOT PROMOTE GROWTH NO BLEEDING or DELAMINATION NO CRACKING Evidence of Delamination - NONE Evidence of Corrosion - NONE Loss of Metallaization - MINIMAL 279 Humberline Drive Etobicoke, ON M9W 5T6 In CANADA: 1-800-837-8961 In US: 1-888-887-3645 Local: 416-798-1340 Fax: 416-798-1342 Email: sales@rfoil.com Visit our Website: www.rfoil.com INSTALLATION SHEET BIG-8 DUCT INSULATION (Duct Insulation continued) INSTALLATION METHOD #1 - R-8 Insulation with Spacer Strips 1. 2. 3. 4. 5. Create spacers by attaching 2” wide strips of rFOIL Duct Insulation (spacers also sold separately). Spacers should be wrapped around the perimeter at approximately 2' intervals. Wrap rFOIL BIG-8 Insulation around the duct with spacers and pull hand-tight (for and R-8 value). Ensure that the printed Code Certification Strip, taped the entire length of the roll, is facing out. This information must be visible to inspectors. Tape all seams and joints using rFOIL Metalized Tape, specially formulated to adhere to rFOIL Duct Insulation. - Item Code 15212 (2” x 150') - Item Code 15213 (3” x 150') - Use of any tape other than the rFOIL items above will void the manufacturer's warranty. Properly installed, the spacers will provide a consistent airspace around the duct. Repeat the above steps for the entire length of the ductwork. www.rFOIL.com NEW! BIG 8 Reflective Tape Spacer Strip Big-8 Spacer Wrap for an R-8 Value (With Spacer Strips) INSTALLATION METHOD #2 - R-6 Insulation for Ducts - Direct Wrap 1. This method does not require spacer strips. However, it is recommended that the product be loosely wrapped around the duct. 2. Determine the exact perimeter around the duct. 3. Wrap rFOIL BIG-8 Insulation around the duct (without spacers for an R-6 value). 4. For optimal performance, wrap the duct with material length that is approximately 5% longer than the actual duct perimeter. Ensure that the printed Code Certification Strip, taped the entire length of the roll, is facing out. This information must be visible to inspectors. 5. Installed loosely, this will create small airspaces between the outer duct wall and the insulation. These pockets of air will enhance the thermal value of the system. 6. Tape all seams and joints using rFOIL Metalized Tape, specially formulated to adhere to rFOIL Duct Insulation. - Item Code 15212 (2” x 150') - Item Code 15213 (3” x 150') - Use of any tape other than the rFOIL items above will void the manufacturer's warranty. Repeat the above steps for the entire length of the ductwork. Big-8 Direct Wrap for an R-6 Value 7. Repeat the above steps for the entire length of the ductwork. BIG 8 (Without Spacer Strips) SUGGESTED PRODUCTS FOR THIS APPLICATION: rFOIL™ REFLECTIVE INSULATION rFOIL™ REFLECTIVE TAPE › 2280-48-050 › 15212 (2" x 150'), 15213 (3" x 150') TM * Check local building codes for compliance before installation. This installation sheet is intended solely to illustrate the proper location and placement of rFOIL Reflective Insulation products in specific constructions applications. They are not intended to illustrate proper construction methods (which is ultimately the TM responsibility of the builder or contractor). The installation instructions are only recommendations relating to the location and placement of rFOIL Reflective TM Insulation products, and rFOIL makes no claims that these construction systems are universally accurate. TM ** All warranties and performance estimates are void if rFOIL Reflective Insulation products are used in exterior applications, or in non-enclosed systems or buildings. TM *** Exercise caution when using rFOIL Reflective Insulation products near and around electrical wiring and devices. 279 Humberline Drive Etobicoke, ON M9W 5T6 In CANADA: 1-800-837-8961 In US: 1-888-887-3645 Local: 416-798-1340 Fax: 416-798-1342 Email: sales@rfoil.com Visit our Website: www.rfoil.com MATERIAL SAFETY DATA SHEET TM rFOIL BIG-8 Duct Insulation www.rFOIL.com SEPTEMBER 2009 SECTION 1: PRODUCT IDENTIFICATION NAME: rFOIL BIG-8 DUCT INSULATION REFLECTIVE DUCT INSULATION R-8 DESCRIPTION: MANUFACTURER: COVERTECH FABRICATING INC. ADDRESS: 279 HUMBERLINE DRIVE ETOBICOKE, ONTARIO, CANADA M9W 5T6 TELEPHONE: 800-837-8961 FAX: 416-798-1342 SECTION 2: HAZARDOUS INGREDIENTS THESE PRODUCTS ARE NOT CONSIDERED TO BE HAZARDOUS, AND ARE NOT CLASSIFIED AS 'CONTROLLED PRODUCTS'. THEY ARE COMPRISED PRINCIPALLY OF POLYETHYLENE AND METALIZED ALUMINUM THAT ARE NON HAZARDOUS. SECTION 3: PHYSICAL DATA BOILING POINT: TEMPERATURE RANGE: WATER VAPOUR PERM: APPEARANCE: ODOUR: NOT APPLICABLE 250 +/- 25OF < 0.029 PERMS FLEXIBLE SHEET NONE SECTION 4: FIRE & EXPLOSION DATA FLAME SPREAD: 0 (ASTM E84-09) SMOKE DEVELOPMENT: 50 (ASTM E84-09) EXTINGUISHING MEDIA: CO2, DRY CHEMICAL, WATER OR FOAM USUAL FIRE HAZARDS: BARRIER FOIL MATERIALS ARE NOT HIGHLY FLAMMABLE, BUT IN CONTACT WITH FLAME THEY WILL MELT AND BURN. SECTION 5: REACTIVITY DATA STABILITY: PRODUCTS ARE STABLE AND INERT TO MOST CHEMICALS. NONE CAUSE A VIOLENT REACTION. INCOMPATIBILITY: CONSULT WITH MANUFACTURER PRIOR TO USING AS A CONTAINMENT OR BARRIER FOR CHEMICALS OTHER THAN WATER. SECTION 6: HEALTH HAZARD DATA INHALATION: NONE EYES & SKIN: NONE INGESTION: PRODUCTS SHOULD NOT BE EATEN OR KEPT IN CONTACT WITH FOOD SECTION 7: SPECIAL PRECAUTION & HANDLING INFORMATION GENERALLY THE PRODUCTS REQUIRE NO SPECIAL PRECAUTIONS WHEN HANDLING. HOWEVER THE PRODUCTS MAY BECOME SLIPPERY WHEN WET, AND CARE SHOULD BE TAKEN WHEN WALKING ON THIS. SECTION 8: FIRST AID MEASURES NOT APPLICABLE NOTE: THE INFORMATION CONTAINED IN THIS SHEET IS DISCLOSED IN GOOD FAITH AND IS PROVIDED TO THE BEST KNOWLEDGE OF THE MANUFACTURER. NEVERTHELESS IT IS NOT A WARRANTY AND COVERTECH FABRICATING INC. ASSUMES NO RESPONSIBILITY FOR DAMAGES INCURRED FROM THE USE OR INABILITY TO USE THE PRODUCT 279 Humberline Drive Etobicoke, ON M9W 5T6 In CANADA: 1-800-837-8961 In US: 1-888-887-3645 Local: 416-798-1340 Fax: 416-798-1342 Email: sales@rfoil.com Visit our Website: www.rfoil.com