Envicool Cyber Mate ( Data Center )

Transcription

Envicool Cyber Mate ( Data Center )
TM
Precision Cooling Unit for Data Center
Save paper the protection of forest resources
Envicool
CyberMateTM Precision Cooling Unit for Data Center
Company profile
Shenzhen Envicool Technology Co., Ltd. is a hi-tech enterprise which specializes in research and development (R&D), manufacturing,
marketing of environment control products and solutions for Data Center and Data Access Stations. The team masters the world class
cooling technology, precise control technology, mechanical design technology and has obtained series patents around temperature
control. Envicool various products have been widely used in China and oversea markets, including CRAC for data center, air conditioner
for telecom outdoor enclosure, free cooling unit (FCU), heat exchanger, battery cabinet and so on.
Envicool has obtained ISO9001, ISO14001 and OHSAS18001. The products are CCC, CE, UL and TUV certified. Envicool adopts
the Integrated Product Development (IPD) process to develop products and technologies, and utilizes the JIT and TQC supply chain
management modes to meet the customers’requirement efficiently.
As an associate member of China Communications Standard Association, Envicool takes an active part in the revision of relevant
industry standards.
R&D Center
Psychrometric AirConditioning
Performance Testing
Lab
Production Line and Warehouse
Certifications & Awards
1
Envicool
TM
CyberMateTM Precision Cooling Unit for Data Center
Date Center
The continual growing OPEX has become the bottleneck of the TCO control in data center.
Improving the energy efficiency and enhancing the management level are the key actions
to reduce the TCO of the data center. Low power consumption and easy manageability are
appreciated in the construction of data center.
The power consumption for cooling system is a significant part, while accounting as 30-40% of
the overall power consumption in a data center. Therefore, energy efficiency of CRAC unit will be
great attention.
With the popularity of the green data center concept, the energy efficiency standards for precision
cooling units keep increasing. More and more data centers are applying the CRAC units with high
energy efficiency and integration of free cooling function.
CyberMateTM Series Precision Cooling Unit:
With high AEER system design and team work function, CyberMateTM meets the cooling demand and reduce the PUE of the
data center.
AEER =
M M
Annual Energy Efficiency Ratio (AEER):
the heats removed from the room
CRAC cooling electricity consumption
(All year round)
Applications
„ Computer room and data center
„ Switch room and mobile center station in telecommunication
„ High-tech environment and lab
„ Industrial automation control room and precision manufacturing workshop
„ Standard test room and calibration center
„ UPS and battery room
„ Test room in hospital
„ Biochemical culture chamber
2
Envicool
CyberMateTM Precision Cooling Unit for Data Center
Configuration Nomenclature for CyberMateTM
Function
Code
Description
1
Series Name
2
Series Code
3
4
Cooling
Capacity
5
Function
6
Fan Type
7
Air Discharge
8
Power Supply
9
System Type
CyberMate
5
7
0
1
0~9
0~9
B
H
P
I
E
F
S
U
D
1
2
3
A
F
W
G
N
C
T
D
R
CyberMate CRAC
DX, single circuit
DX, dual circuit
CW, capacity < 100kW
CW, capacity ≥ 100kW
DX: 50-50kW.
CW: 50-50kW (series code is 0), 50-150kW (series code is 1)
Cooling
Cooling, Reheating
Cooling, Reheating, Humidifying
AC fan
EC fan
Downflow
Downflow, fan under floor
Upflow, plenum
Upflow, duct
380V 3Ph-50Hz
220V 1Ph-50Hz
Other Power Input
Air cooled
Dual cool: Air cooled+iFreecooling®
Water cooled
Glycol cooled
Integrated direct free cooling and humidification curtain
Chilled water: Single coil
Chilled water: Dual coil
Dual cool: Chilled water+Air cooled
Dual cool: Chilled water+Water cooled (Glycol)
10
Special
Requirements
X
SFA Included
EVO
controller
Efficient scroll
compressor
Efficient
EC fans
Ziehl-Abegg
owlet fan
with various
frequency fan
speed control
3
Envicool
TM
CyberMateTM Precision Cooling Unit for Data Center
CyberMateTM series of DX unit (26kW-100kW)
Highlights of DX Unit Design
Functions of EVO Control System
High Reliability
• High quality components with
strict certification
• Running test in factory before
delivery for each unit
High Energy Efficiency
• EVO controller ensure optimum cooling efficiency
• Efficient EC fan, continuous airflow adjustment,
optional EC fan under floor design
• Efficient and quiet flexible scroll compressor
• High efficiency with precision Electronic Expansion
Valve precision cooling control
• Efficient electrode humidifier to realize precise
humidity control
• Efficient dehumidification design to ensure absolute
humidity control
• High efficiency and variable frequency control for
condenser fan
• Integrated iFreecooling® indirect free cooling
technology
• Utilization of natural cold source by integrating the
direct free cooling option
EVO Display System
•
•
•
•
7-inch, 800×480 dot true color touch screen
Temperature and humidity curves
Graphical display of device running status
Multi-level password protection
EVO Storage System
• Multiple history alarms, expanded storage of history
alarms is provided
• The running data will be stored every 60 seconds,
and the history data can be maintained. The
relevant data can be read directly through the
computers
EVO Data Collection System
• Able to connect multiple temperature/humidity
sensors and detect the temperature/humidity of the
inlet/outlet air of racks
• Control mode selected according to the rack cooling
demand, precise air supply to realize energy saving
EVO Team Work Function
High Adaptability
• Various air discharge choices including Downflow and
Upflow and so on
• Multiple monitoring interface
• Suitable for various ambient temperature conditions
(Optional low temperature startup kits)
• Customized design available
Wide Range of Cooling Capacity
• 6kW~20kW, 26kW~100kW
• Single circuit indoor unit, dual circuit indoor unit
• Single circuit condenser, dual circuit condenser
• Group multiple units easily
• Shared temperature and humidity setting
• Team work mode: demand management, trend
management, rotation and standby (lead/lag),
realizing adaptive energy saving
EVO Monitoring System
• RS485 interface as standard
• Optional SNMP and TCP/IP interface
• Optional GPRS DTU, SMS for alarm and
maintenance remind
Various Cooling System Type
• Air cooled/Water cooled/Glycol cooled
• Dual Cool including: Chilled water+Air cooled, Chilled
water+Water cooled (Glycol)
• Dual Cool: Air cooled+iFreecooling®
• Dual Cool : Aircooled+Direct free cooling
4
Envicool
CyberMateTM Precision Cooling Unit for Data Center
Data Sheet of CyberMateTM DX Units (Air Cooled, Water Cooled,
Glycol Cooled)
Model
526
Power Supply
Air Discharge
Cooling Capacity : 24℃ / 50% RH
Total (kW)
26.8
EC Sensible (kW)
24.2
fan
FLA-A
28.3
Quantity of compressor(s)
1
Fan Section
Airflow (m3/h)
8000
Quantity of fan(s)
1
Reheat Section
Capacity (kW)
6
Humidifier Section
Capacity (kg/h)
6
Connection Sizes
Liquid pipe - OD (mm)
16
Gas pipe - OD (mm)
22
Inlet pipe of humidifier (female) 3/4"G
Drain Pipe - ID (mm)
25
Physical Data
Width (mm)
1050
Depth (mm)
890
Height (mm)
1990
Weight (kg)
355
Water / Glycol Cool Unit Parameters
Inlet / Outlet
35.0
Connection (mm)
Water Flow Rate (m3/h)
6.0
Pressure Drop (kPa)
86.0
Inlet / Outlet
35.0
Glycol Connection (mm)
3
(40%) Flow Rate (m /h)
7.1
Pressure Drop (kPa)
99.8
Breakers & Cables
Recommended Air 50
Indoor break Switch (A)
unit
2
Cables (mm )
10
Recommended Air 20
Outdoor break Switch (A)
unit
Cables (mm2)
1.5
530
535
540
546
740
746
755
765
770
780
790
799
30.9
27.8
31.3
1
35.9
32.6
38.7
1
40.3
36.4
41.2
1
46.9
42.2
48.0
1
40.7
36.8
43.6
2
47.6
42.9
48.0
2
55.6
50.2
51.3
2
65.8
59.3
58.5
2
71.6
64.5
62.9
2
80.2
72.7
69.3
2
92.6
83.6
82.5
2
100.2
90.6
84.3
2
8000
1
10000
1
10000
1
13000
2
10000
1
13000
2
14000
2
17000
2
18000
2
21500
3
23000
3
23000
3
6
9
9
9
9
9
9
9
9
9
9
9
6
6
6
10
6
10
10
10
10
10
10
10
16
22
3/4"G
25
16
22
3/4"G
25
16
22
3/4"G
25
19
22
3/4"G
25
16
19
3/4"G
25
16
19
3/4"G
25
16
22
3/4"G
25
16
22
3/4"G
25
16
22
3/4"G
25
16
22
3/4"G
25
19
22
3/4"G
25
19
22
3/4"G
25
1050
890
1990
360
1400
890
1990
450
1400
890
1990
460
1700
890
1990
480
1400
890
1990
580
1700
890
1990
620
1700
890
1990
620
2100
890
1990
670
2100
890
1990
730
2550
890
1990
820
2550
890
1990
860
2550
890
1990
900
42.0
42.0
42.0
54.0
42.0
54.0
54.0
54.0
63.0
63.0
70.0
70.0
7.0
99.2
8.2
76.0
9.2
83.1
10.7
94.7
9.2
82.8
10.8
95.4
12.5
75.1
14.9
85.6
16.4
93.1
18.3
71.0
21.0
77.6
22.8
82.5
42.0
42.0
54.0
54.0
42.0
54.0
54.0
54.0
63.0
63.0
70.0
70.0
8.3
76.6
9.6
86.0
10.8
95.8
12.6
75.3
10.8
95.4
12.7
112.9
14.7
84.8
17.6
99.3
19.3
73.3
21.6
79.1
24.7
88.2
26.8
95.0
50
63
63
80
63
80
80
100
100
125
125
125
10
10
16
16
16
16
16
16
16
25
25
25
380V 3Ph-50Hz
Upflow / Downflow
20
20
20
20
20
20
20
20
20
20
20
20
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
Remark:
ƒ Return air condition: 24℃ / 50% RH.
ƒ Water/glycol flow control valve: standard two-way valve, optional three-way valve.
ƒ EC fan configured as standard.
ƒ Electronic Expansion Valve as standard.
5
Envicool
TM
CyberMateTM Precision Cooling Unit for Data Center
Data Sheet of CyberMateTM Dual Cool Units (DX +CW)
Model
526
Power Supply
Air Discharge
Cooling Capacity : 24℃ / 50% RH
Total (kW)
26.8
DX
Sensible (kW)
24.2
FLA-A
28.9
Total (kW)
33.6
CW Sensible (kW)
29.2
Flow Rate (m3/h)
5.8
Quantity of compressor(s)
1
Fan Section
Airflow (m3/h)
8000
Quantity of fan(s)
1
Reheat Section
Capacity (kW)
6
Humidifier Section
Capacity (kg/h)
6
Connection Sizes
DX Liquid Pipe - OD (mm)
16
DX Hot Gas Pipe - OD (mm)
22
CW inlet/outlet
DN25
Inlet pipe of humidifier (female)
3/4"G
Drain Pipe - ID (mm)
25
Physical Data
Width (mm)
1050
Depth (mm)
890
Height (mm)
1990
Weight (kg)
385
Water / Glycol Cool Unit Parameters
Inlet / Outlet
35.0
Connection (mm)
Water
Flow Rate (m3/h)
6.0
Pressure Drop (kPa) 86.0
Inlet / Outlet
35.0
Connection (mm)
Glycol
3
Flow Rate (m /h)
7.1
(40%)
Pressure Drop (kPa) 99.8
Breakers & Cables
Recommended Air 50
Indoor
break Switch (A)
unit
2
Cables (mm )
10
Recommended Air 20
Outdoor break Switch (A)
unit
2
Cables (mm )
1.5
530
535
540
546
740
746
755
765
770
780
790
799
30.9
27.8
31.9
33.6
29.2
5.8
1
35.9
32.6
39.4
44.2
37.7
7.6
1
40.3
36.4
41.9
44.2
37.7
7.6
1
46.9
42.2
49.0
56.4
48.6
9.7
1
40.7
36.8
44.3
44.2
37.7
7.6
2
47.6
42.9
49.0
56.4
48.6
9.7
2
55.6
50.2
52.4
59.1
51.2
10.1
2
65.8
59.3
59.7
73.5
63.2
12.6
2
71.6
64.5
64.1
76.4
66.0
13.1
2
80.2
72.7
71.8
89.2
77.8
15.3
2
92.6
83.6
84.3
92.5
81.7
15.9
2
100.2
90.6
86.2
92.5
81.7
15.9
2
8000
1
10000
1
10000
1
13000
2
10000
1
13000
2
14000
2
17000
2
18000
2
21500
3
23000
3
23000
3
6
9
9
9
9
9
9
9
9
9
9
9
6
6
6
10
6
10
10
10
10
10
10
10
16
22
DN25
3/4"G
25
16
22
DN32
3/4"G
25
16
22
DN32
3/4"G
25
19
22
DN32
3/4"G
25
16
22
DN32
3/4"G
25
16
22
DN32
3/4"G
25
16
22
DN32
3/4"G
25
16
22
DN40
3/4"G
25
16
22
DN40
3/4"G
25
16
22
DN40
3/4"G
25
19
22
DN40
3/4"G
25
19
22
DN40
3/4"G
25
1050
890
1990
390
1400
890
1990
500
1400
890
1990
510
1700
890
1990
550
1400
890
1990
530
1700
890
1990
680
1700
890
1990
690
2100
890
1990
770
2100
890
1990
830
2550
890
1990
940
2550
890
1990
980
2550
890
1990
1000
42.0
42.0
54.0
54.0
42.0
54.0
54.0
54.0
63.0
63.0
70.0
70.0
7.0
99.2
8.2
76.0
9.2
83.1
10.7
94.7
9.2
82.8
10.8
95.4
12.5
75.1
14.9
85.6
16.4
93.1
18.3
71.0
21.0
77.6
22.8
82.5
42.0
42.0
54.0
54.0
42.0
54.0
54.0
54.0
63.0
63.0
70.0
70.0
8.3
76.6
9.6
86.0
10.8
95.8
12.6
75.3
10.8
95.4
12.7
112.9
14.7
84.8
17.6
99.3
19.3
73.3
21.6
79.1
24.7
88.2
26.8
95.0
50
63
63
80
63
80
80
100
100
125
125
125
10
16
16
16
16
16
16
16
16
25
25
25
20
20
20
20
20
20
20
20
20
20
20
20
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
380V 3Ph-50Hz
Upflow / Downflow
Remark:
ƒ Return air condition: 24℃ / 50% RH.
ƒ Water/glycol flow control valve: standard two-way valve, optional three-way valve.
ƒ EC fan configured as standard.
ƒ Electronic Expansion Valve as standard.
6
Envicool
CyberMateTM Precision Cooling Unit for Data Center
iFreecooling ® Technology
„ Through to stop the compressor running in suitable seasons to greatly reduce the power consumption of the cooling system,
,
it s a realizing efficient cooling and will reduce PUE of data center by free cooling
„ To protect the temperature, humidity and cleanness of data center from outside and ensure its high reliability
®
„ When iFreecooling running in suitable seasons, the compressor energy saving rate will exceeding 96% and the whole
cooling system will exceeding 70%, overall energy consumption of data center reduction of 25%~35%
®
„ iFreecooling can running together with DX both in spring and autumn seasons to make best use of free cooling
®
„ One iFreecooling system can working together with multiple DX units
Power consumption
of condenser fan
Power consumption
of indoor unit fan
Power consumption
of iFreecooling system
Power consumption
of compressor
Power consumption
of general CRAC
Power consumption
of CyberMate
Power consumption
of CyberMate+
iFreecooling in
spring and autumn
seasons
Power consumption
of iFreecooling in
suitable seasons
Regions Effective for iFreecooling® System
Annual energy saving rate ≥ 35%
Annual energy saving rate ≥ 25%
Annual energy saving rate ≥ 15%
7
Envicool
TM
CyberMateTM Precision Cooling Unit for Data Center
Data Sheet of CyberMateTM Dual Cool Units (Air Cooled+
iFreecooling® )
Model
535
540
546
740
746
755
765
Power Supply
380V 3Ph-50Hz
Air Discharge
Upflow / Downflow
770
780
790
799
Cooling Capacity of DX Unit : 24℃ / 50% RH
Total (kW)
35.9
40.3
46.9
40.7
47.6
55.6
65.8
71.6
80.2
92.6
100.2
Sensible (kW)
32.6
36.4
42.2
36.8
42.9
50.2
59.3
64.5
72.7
83.6
90.6
FLA-A
38.7
41.2
48.0
43.6
48.0
51.3
58.5
62.9
69.3
82.5
84.3
Number of compressor(s)
1
1
1
2
2
2
2
2
2
2
2
10000
10000
13000
10000
13000
14000
17000
18000
21500
23000
23000
1
1
2
1
2
2
2
2
3
3
3
9
9
9
9
9
9
9
9
9
9
9
6
6
10
6
10
10
10
10
10
10
10
Liquid Pipe - OD (mm)
16
16
16
16
19
16
16
16
16
19
19
Gas Pipe - OD (mm)
22
22
22
19
19
22
22
22
22
22
22
3/4"G
3/4"G
3/4"G
3/4"G
3/4"G
3/4"G
3/4"G
3/4"G
3/4"G
3/4"G
3/4"G
25
25
25
25
25
25
25
25
25
25
25
1400
1400
1700
1400
1700
1700
2100
2100
2550
2550
2550
EC fan
Fan Section
Airflow (m3/h)
Quantity of fan(s)
Reheat Section
Capacity (kW)
Humidifier Section
Capacity (kg/h)
Connection Sizes
Inlet pipe of humidifier (female)
Drain Pipe - ID (mm)
Physical Data of DX Unit
Width (mm)
Depth (mm)
890
890
890
890
890
890
890
890
890
890
890
Height (mm)
1990
1990
1990
1990
1990
1990
1990
1990
1990
1990
1990
Weight (kg)
450
460
480
580
620
620
670
730
820
860
900
Liquid pipe - OD (mm)
16
16
16
16
16
16
19
19
19
19
19
Gas pipe - OD (mm)
22
22
22
22
22
22
28
28
28
28
28
Recommended Air-break Switch (A)
63
63
80
63
60
60
100
100
125
125
125
Cables (mm2)
16
16
16
16
16
16
16
16
25
25
25
20
20
20
20
20
20
20
20
20
20
20
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
Connection Sizes of iFreecooling®
Breakers & Cables
Indoor
unit
Outdoor Recommended Air-break Switch (A)
unit
Cables (mm2)
Remark:
ƒ Return air condition: 24℃ / 50% RH.
ƒ EC fan configured as standard.
ƒ Electronic Expansion Valve as standard.
8
Envicool
CyberMateTM Precision Cooling Unit for Data Center
Data sheet of CyberMateTM Dual Cool Units (DX+Direct free
cooling )
Model
526
530
535
540
546
740
746
755
765
770
780
790
799
Power Supply
380V 3Ph-50Hz
Air Discharge
Upflow / Downflow
Cooling Capacity of DX Unit:24℃ / 50%RH
Total (kW)
26.8
30.9
35.9
40.3
46.9
40.7
47.6
55.6
65.8
71.6
80.2
92.6
100.2
EC fan Sensible (kW)
24.2
27.8
32.6
36.4
42.2
36.8
42.9
50.2
59.3
64.5
72.7
83.6
90.6
FLA-A
28.3
31.3
38.7
41.2
48.0
43.6
48.0
51.3
58.5
62.9
69.3
82.5
84.3
Number of compressor(s)
1
1
1
1
1
2
2
2
2
2
2
2
2
Fan Section
Airflow (m3/h)
8000
8000 10000 10000 13000 10000 13000 14000 17000 18000 21500 23000 23000
Quantity of fan(s)
1
1
1
1
2
1
2
2
2
2
3
3
3
Reheat Section
Capacity (kW)
6
6
9
9
9
9
9
9
9
9
9
9
9
Humidifier Section
Capacity (kg/h)
6
6
6
6
10
6
10
10
10
10
10
10
10
Connection Sizes
Liquid pipe (mm)
16
16
16
16
19
16
16
16
16
16
16
19
19
Gas pipe (mm)
22
22
22
22
22
19
19
22
22
22
22
22
22
Inlet pipe of humidifier (female) 3/4"G 3/4"G 3/4"G 3/4"G 3/4"G 3/4"G 3/4"G 3/4"G 3/4"G 3/4"G 3/4"G 3/4"G
3/4"G
Drain pipe - ID (mm)
25
25
25
25
25
25
25
25
25
25
25
25
25
Physical Data of DX Unit
Width (mm)
1050
1050
1400
1400
1700
1400
1700
1700
2100
2100
2550
2550
2550
Depth (mm)
890
890
890
890
890
890
890
890
890
890
890
890
890
Height (mm)
1990
1990
1990
1990
1990
1990
1990
1990
1990
1990
1990
1990
1990
Weight (kg)
355
360
450
460
480
580
620
620
670
730
820
860
900
Free Cooling Inlet Unit Specfication
Model
FS1050 FS1050 FS1400 FS1400 FS1700 FS1400 FS1700 FS1700 FS2100 FS2100 FS2550 FS2550 FS2550
Airflow (m3/h)
7600
7600
9500
9500 12350 9500 12350 13300 16150 17100 20425 21850 21850
Sensible cooling capacity (kW) 25.7
25.7
38.9
38.9
45.7
38.9
45.7
53.6
64.0
68.6
77.9
97.2
97.2
Humidifying capacity (kg/h)
13.6
13.6
17.1
17.1
22.1
17.1
22.1
23.9
29.0
30.7
36.7
39.2
39.2
Width (mm)
1050
1050
1400
1400
1700
1400
1700
1700
2100
2100
2550
2550
2550
Depth (mm)
600
600
600
600
600
600
600
600
600
600
600
600
600
Height (mm)
1990
1990
1990
1990
1990
1990
1990
1990
1990
1990
1990
1990
1990
Weight (kg)
100
100
140
140
160
140
160
160
200
200
240
240
240
Free Cooling Outlet Unit Specification
Model
DCX050-C DCX050-C DCX050-C DCX050-C DCX150-C DCX050-C DCX150-C DCX150-C DCX150-C DCX150-C DCX150-C DCX150-C DCX150-C
Quantity
1
1
1
1
1
1
1
1
1
1
1
1
1
Airflow (m3/h)
5000
5000
5000
5000
11000
5000
11000 11000 11000 11000 11000 11000 11000
Width (mm)
500
500
500
500
1160
500
1160
1160
1160
1160
1160
1160
1160
Depth (mm)
375
375
375
375
405
375
405
405
405
405
405
405
405
Height (mm)
480
480
480
480
1035
480
1035
1035
1035
1035
1035
1035
1035
Weight (kg)
35
35
35
35
50
35
50
50
50
50
50
50
50
Breakers & Cables
Recommended Air50
50
63
63
80
63
80
80
100
100
125
125
125
Indoor
break Switch (A)
unit
Cables (mm2)
10
10
10
16
16
16
16
16
16
16
25
25
25
Recommended Air20
20
20
20
20
20
20
20
20
20
20
20
20
Outdoor break Switch (A)
unit
2
Cables (mm )
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
Remark:
ƒ Return air condition: 24℃ / 50% RH.
ƒ EC fan configured as standard.
ƒ Electronic Expansion Valve as standard.
9
Envicool
TM
CyberMateTM Precision Cooling Unit for Data Center
CyberMateTM (>20kW) Air Cooled Condenser
„ Strengthen aluminum alloy enclosure and stainless steel connecting parts
„ Variable frequency fan speed control, efficient energy saving
„ Bionic-type fan, low noise
®
„ Integrated iFreecooling design
„ Adapting to various climate conditions
„ Single/dual circuit design
Data Sheet of CyberMateTM (>20kW) Air Cooled Condenser
Model
Quantity of fan (s)
Length (mm)
Height (mm)
Width (mm)
Weight (kg)
CS25
CS32
CS38
CS46
CS54
CS66
CS78
CS86
CD46
CD54
CD66
CD78
CD86
1
1
1
1
1
2
2
2
1
1
2
2
2
1310
1310
1610
1610
1910
1910
2410
2410
1610
2110
2110
2410
2410
987
987
987
1287
1287
1287
1287
1287
1287
1287
1287
1287
1287
645
645
645
652
652
645
652
652
652
652
645
652
652
110
115
130
140
150
160
200
240
140
160
170
200
220
Liquid Line-OD Hot Gas Line-OD
(mm)
(mm)
16
16
16
16
16
19
19
19
16
16
16
16
16
22
22
22
22
22
28
28
28
22
22
22
22
22
Data Sheet of CyberMateTM Air Cooled+iFreecooling® Integrated Condenser
Model
Quantity
of fan(s)
CS32F
CS38F
CS46F
CS54F
CS66F
CS78F
CS86F
1
1
1
2
2
2
2
Length
(mm)
1910
2110
2110
2110
2410
2410
2810
Height
(mm)
987
987
1287
1287
1287
1287
1287
Width
(mm)
645
652
652
652
652
652
652
Weight
(kg)
135
150
170
180
210
270
310
Liquid Line for
DX-OD (mm)
Hot Gas Line for
DX-OD (mm)
Liquid Line for
iF-OD (mm)
Hot Gas Line for
iF-OD (mm)
16
16
16
16
19
19
19
22
22
22
22
28
28
28
16
16
19
19
19
19
19
22
22
28
28
28
28
28
10
Envicool
CyberMateTM Precision Cooling Unit for Data Center
CyberMateTM Series of CW unit
Highlights of CW Unit Design
Function of EVO Control System
High Reliability
• High quality components with strict certification
certified
• Running test in factory before delivery for each unit
EVO Display System
•
•
•
•
7-inch, 800×480 dot true color touch screen
Temperature and humidity curves
Graphical display of device running status
Multi-level password protection
High Energy Efficiency
• Precise valve and variable airflow control, adjust
the cooling capacity output and airflow to suit the
temperature change of rack
• EVO controller to ensure optimum cooling efficiency
• Efficient EC fan, continuous airflow adjustment,
optional EC fan under floor design
• Efficient electrode humidifier to realize precise
humidity control
• Efficient dehumidification design to ensure absolute
humidity control
High Adaptability
• Various air discharge including Downflow and Upflow
and so on
• Multiple monitoring interface
• Customized design available
Wide Range of Cooling Capacity
• 35kW ~150kW
Single-coil and Dual-coil Unit
• Dual-coil unit can match the dual pipelined
chilled water system design to increase the
system reliability
11
EVO Storage System
• Multiple history alarms, expanded storage of history
alarms is provided
• The running data will be stored every 60 seconds,
and the history data can be maintained. The relevant
data can be read directly through the computers
EVO Data Collection System
• Able to connect multiple temperature/humidity
sensors and detect the temperature/humidity of the
inlet/outlet air of racks
• Control mode selected according to the rack cooling
demand, precise air supply to realize energy saving
EVO Team Work Function
• Group multiple units easily
• Shared temperature and humidity setting
• Team work mode: demand management, trend
management, rotation and standby (lead/lag),
realizing adaptive energy saving
EVO Monitoring System
• RS485 interface as standard
• Optional SNMP and TCP/IP interface
• Optional GPRS DTU, SMS for alarm and
maintenance remind
Envicool
TM
CyberMateTM Precision Cooling Unit for Data Center
Data Sheet of CyberMateTM CW (Single-coil) Units
Model
Power Supply
Air Discharge
Performance Specification
7℃ /12℃ IWT/OWT
EC
fan 10℃ /15℃ IWT/OWT
035
Total (kW)
Sensible (kW)
Total (kW)
Sensible (kW)
FLA-A
Flow Rate (m3/h)
Fan Section
Airflow (m3/h)
Quantity o f fan(s)
Reheat Section
Capacity (kW)
Humidifier Section
Capacity (kg/h)
Connection Sizes
Inlet pipe of CW
Outlet pipe of CW
Inlet pipe of humidifier (female)
Drain Pipe - ID (mm)
Physical Data
Width (mm)
Depth (mm)
Height (mm)
Weight (kg)
Breakers & Cables
Recommended Air-break Switch (A)
Cables (mm2)
045
050
060
080
090
380V 3Ph-50Hz
Upflow / Downflow
100
110
120
140
150
Downflow
35.3
28.3
25.6
24.4
10.7
6.0
45.7
36.9
32.3
30.7
11.9
7.8
50.2
39.8
35.5
33.8
16.1
8.6
60.5
48.0
42.0
40.2
16.9
10.3
81.1
67.2
60.2
57.2
19.1
13.8
90.7
72.6
65.2
62.0
19.1
15.5
101.0
84.4
73.5
70.2
21.3
17.2
112.0
90.8
80.2
76.4
21.3
18.9
125.0
104.0
90.6
86.1
22.2
21.0
141.0
112.8
100.5
95.5
24.0
24.0
150.9
119.8
105.5
100.4
23.8
25.7
6500
1
8500
1
9000
1
10000
1
16500
2
16500
2
21000
2
21000
2
25500
3
25500
3
27000
3
6
6
9
9
9
9
9
9
9
9
9
6
6
6
6
10
10
10
10
10
10
10
DN25
DN25
3/4"G
25
DN32
DN32
3/4"G
25
DN32
DN32
3/4"G
25
DN40
DN40
3/4"G
25
DN40
DN40
3/4"G
25
DN40
DN40
3/4"G
25
DN40
DN40
3/4"G
25
DN50
DN50
3/4"G
25
DN50
DN50
3/4"G
25
DN50
DN50
3/4"G
25
DN50
DN50
3/4"G
25
1050
890
1990
310
1050
890
1990
320
1400
890
1990
340
1400
890
1990
350
1700
890
1990
510
1700
890
1990
530
2100
890
1990
550
2100
890
1990
580
2550
890
1990
720
2550
890
1990
760
2550
890
1990
820
20
4
20
4
32
6
32
6
32
6
32
6
32
6
32
6
40
10
40
10
40
10
Data Sheet of CyberMateTM CW (Dual-coil) Units
Model
Power Supply
Air Discharge
Performance Specification
EC
fan
7℃ /12℃ IWT/OWT
10℃ /15℃ IWT/OWT
FLA-A
Flow Rate (m3/h)
Fan Section
Airflow (m3/h)
Quantity of fan(s)
Reheat Section
Capacity (kW)
Humidifier Section
Capacity (kg/h)
Connection Sizes
Inlet pipe of CW
Outlet pipe of CW
Inlet pipe of humidifier (female)
Drain Pipe - ID (mm)
Physical Data
Width (mm)
Depth (mm)
Height (mm)
Weight (kg)
Breakers & Cables
Recommended Air-break Switch (A)
Cables (mm2 )
030
Total (kW)
Sensible (kW)
Total (kW)
Sensible (kW)
045
060
080
380V 3Ph-50Hz
Upflow / Downflow
095
100
Downflow
30.5
26.9
21.9
21.9
11.8
5.2
45.2
39.6
32.3
32.3
18.3
7.7
59.9
52.3
42.9
42.9
18.9
10.3
77.6
68.0
55.5
55.5
21.6
13.3
96.3
85.3
70.2
70.2
22.4
16.5
104.0
92.1
75.3
75.3
23.3
17.8
7500
1
11000
1
14500
2
19000
2
24000
3
26000
3
6
9
9
9
9
9
6
6
10
10
10
10
DN25
DN25
3/4"G
25
DN32
DN32
3/4"G
25
DN40
DN40
3/4"G
25
DN40
DN40
3/4"G
25
DN40
DN40
3/4"G
25
DN40
DN40
3/4"G
25
1050
890
1990
340
1400
890
1990
380
1700
890
1990
550
2100
890
1990
590
2550
890
1990
760
2550
890
1990
790
20
4
32
6
32
6
32
6
32
6
40
6
Remark:
ƒ Return air condition: 24℃ / 50% RH.
ƒ Water/glycol flow control valve: standard two-way valve, optional three-way valve.
ƒ EC fan configured as standard.
12
Envicool
CyberMateTM Precision Cooling Unit for Data Center
CyberMateTM DX (6kW~20kW) Units
Applications
„ IT Equipment Room
„ Small Data Center
„ Industrial Clean Room
„ Constant Temperature and Humidity Process Workshop
„ Laboratory
„ Electric Power Equipment Room
„ Railway/Subway Machine Room
„ Base Station and Small Telecom Switch Room
„ Medium & small telecom switch room
Features
„ Color and style design consistent with IT equipments
„ Intelligent constant control function for temperature and humidity
„ Design for the continuously 365X24 operation under full range of climate
„ Long lifetime design with low operating costs
„ Large airflow supply with high SHR and low power consumption
„ Uniformity of room temperature by long-distance supply air
„ Ensure room cleanness by high level air filter configuration and large air flow
circuit
„ Ultra-wide input power adaptability, automatic phase sequence switching
function, automatic re-start, delayed startup optional
„ Remote monitoring and control through dry-contact or RS485 communication
interface with open protocol
„ Menu-based large LCD display with multi-level password protection function
„ Standby (master/slave) mode and rotating mode available
„ Self-diagnosis function, various system diagnosis, alarm, and protection
functions
„ Parameter and operation/alarm record auto-protection under power loss
„ 50 maximum storage for historic alarm record and 999 maximum counting for
single alarm
„ Lower noise level for condenser with compressor placed in indoor unit
„ Various options and SFA capability
13
Envicool
TM
CyberMateTM Precision Cooling Unit for Data Center
Data Sheet of DX CyberMateTM (6kW~20kW) Units
Return air condition: 24℃ / 50%RH
Model
Power supply
Air Discharge
Performance Specification
Total (kW)
AC Sensible (kW)
fan FLA-A (Cooling)
FLA-A (Cooling, Reheating, Humidifying)
Total (kW)
EC Sensible (kW)
fan FLA-A (Cooling)
FLA-A (Cooling, Reheating, Humidifying)
Quantity of Compressor(s)
Quantity of Fan(s)
Airflow (m3/h)
Reheating capacity (kW)
Humidifying capacity (kg/h)
Connection Sizes
Liquid pipe (mm)
Gas pipe (mm)
Inlet pipe of humidifier (female)
Drain Pipe - ID (mm)
Physical Data of Indoor Unit
Width (mm)
Depth (mm)
Height (mm)
Weight (kg)
Outdoor Unit parameters
Model
505
505
508
508
512
6.0
5.0
14.0
18.6
6.1
5.1
13.2
17.8
1
1
1500
3
2.8
7.5
6.9
17.3
44.6
1
1
2300
6
2.8
7.5
6.9
6.8
15.9
7.6
7.0
6.0
15.1
1
1
2300
6
2.8
9.52
12.7
3/4"G
19
9.52
12.7
3/4"G
19
9.52
12.7
3/4"G
19
600
550
1900
120
600
550
1900
120
600
550
1900
130
220V 1Ph50Hz
380V 3Ph50Hz
6.0
5.0
14.0
27.7
1
1
1500
3
2.8
220V 1Ph- 380V 3Ph- 380V 3Ph50Hz
50Hz
50Hz
Upflow / Downflow
516
520
380V 3Ph50Hz
380V 3Ph50Hz
12.5
11.3
12.8
21.9
12.6
11.5
10.9
19.9
1
1
2700
6
2.8
16.8
15.3
12.9
22.0
16.9
15.5
12.6
21.7
1
1
4500
6
6
20.2
18.3
17.9
27.0
20.4
18.5
17.3
26.4
1
1
5500
6
6
9.52
12.7
3/4"G
19
12.7
15.88
3/4"G
19
12.7
19
3/4"G
19
12.7
19
3/4"G
19
600
550
1900
130
600
550
1900
150
750
750
1950
280
750
750
1950
300
CyberMate CyberMate CyberMate CyberMate CyberMate CyberMate CyberMate
508E
508E
508E
508E
512E
516E
520E
800
800
800
800
800
1500
1500
360
360
360
360
360
360
360
790
790
790
790
1240
1240
1240
45
45
45
45
60
100
100
-15℃ ~ 45℃ -15℃ ~ 45℃ -15℃ ~ 45℃ -15℃ ~ 45℃ -15℃ ~ 45℃ -15℃ ~ 45℃ -15℃ ~ 45℃
Width (mm)
Depth (mm)
Height (mm)
Weight (kg)
Operating temperature range (standard)
Operating temperature range (with low-temperature -40℃ ~ 45℃ -40℃ ~ 45℃ -40℃ ~ 45℃ -40℃ ~ 45℃ -40℃ ~ 45℃ -40℃ ~ 45℃ -40℃ ~ 45℃
startup kits)
Breakers & Cables
Recommended Air-break Switch (A)
40
32
63
32
32
50
50
Outdoor unit power cable (mm2)
1.5
1.5
1.5
1.5
1.5
1.5
1.5
Main power cable (mm2) - Cooling
4
4
4
2.5
4
4
6
Main power cable (mm2) - Cooling, Reheating,
6
4
10
4
6
6
6
Humidifying
14
www.envicool.com
Professional·Value·Trust
Envicool Product Family
Outdoor Enclosure Cooling
Energy Saving Solutions
Customized Solutions
ƒ CyberMateTM series CRAC
ƒ DC series air conditioner
ƒ EC series indoor battery cooler
ƒ Outdoor LCD air conditioner
ƒ CyberMateTM series Modular CRAC
ƒ EC series air conditioner
ƒ ES series heat exchanger
ƒ Customized air conditioners
ƒ CyberMateTM series of high precision
environmental control system
ƒ HC series combo air conditioner
ƒ FX series BTS free cooling unit
ƒ EX series heat exchanger
ƒ FU series free cooling & humidifier
combination
Data Center Cooling
ƒ XRow ® series row-based cooling unit
ƒ XRack TM Micro Module Enclosure
ƒ EM series cabinet monitor
ƒ IFW series refrigerant pumping system
ƒ iFreecooling ® series indirect free
cooling system
ƒ SC series hybrid air conditioner
with free cooling
ƒ ERG series heat pipe
ƒ Cooling system for Container &
Modular Data Center
Shenzhen Envicool Technology Co., Ltd.
Address: Hongxin Industrial Park, Guanlan, Bao'an District, Shenzhen, China
Tel: +86 (755) 6683 3272
Http: www.envicool.com
Envicool reserves updating right without notice.
Fax: +86 (755) 2958 8895
Email: intlsales@envicool.com
P.C:518110