Rota P51 - Paladin Ltd - Fire Detection and Emergency Lighting

Transcription

Rota P51 - Paladin Ltd - Fire Detection and Emergency Lighting
4 New products
8 Luminaires
58 Photometric data
60 Design guide
63 Self contained emergency
gear (conversion kits)
72 Low voltage
emergency lighting
75 Inverters for use
with central systems
78 Central systems
82 Addressable emergency
lighting systems
85 Digital self testing systems
86 Electronically controlled
emergency lighting
Rota
P51
87 Conditions of sale
Led exit signs
suitable for wall
or ceiling mounting
ORBIK Electronics Ltd has a policy of constant
product improvement, the right is therefore
reserved to modify product specifications
without prior notice.
All products sold in accordance with our
conditions of sale, copy on request.
p13 Chella
p17 Dyode
p21 Elled
P22 Geneva
P25 Idro
P2
P27
Concentrating their sales efforts on the lighting manufacturers in the UK, Orbik’s reputation for supplying quality BSI approved
emergency lighting control gear spread quickly.
Constant sales growth allowed the Company to expand and before long Orbik became a reputable name across Europe and the
Middle East for emergency lighting products, including a comprehensive range of emergency luminaires.
Continual luminaire development created increased demand for metal work and in 1993 Orbik acquired Metalforms
Engineering, a quality highly automated manufacturer of precision sheet metalwork with in-house powder coating facilities.
In 2001 SPEL was merged with Orbik Electronics to target the Electrical Wholesaler and specification markets with their own
brand of emergency lighting and fire safety equipment.
SPEL have grown rapidly and are now recognised as one of the most rapidly expanding emergency lighting suppliers in the UK.
I CIECLE LI C E L
INDUSTRYIN
INDUSTRY COMMITTEE
COMMITTEE
DUSTRY COMMITTEE
LIGHTINGLIGHTING
FOR EMERGENCY
FOR EMERGENCY
FOR EMERGENCY LIGHTING
FM09128
P49
Think quality.
Think Orbik.
Orbik’s purpose built four acre site is situated in the West
Midlands and now hosts 200 employees. Automated
production processes allow for an efficient flexible supply
of emergency lighting products to their global customers.
Encouraging sales in the Republic of Ireland has recently
led to Orbik joining forces with Dublin based Emergency
Lighting and Fire (E.L.F) who are now successfully
promoting the Orbik range of products across the
Emerald Isle with a local stockholding to ensure
their customers are provided with an excellent
service. Something that Orbik do naturally.
New Products and Designs
P26 Kalix
P27 Karis
P37 Monza
p43 Orbe
P49 Quarto
P53 Romney
P55 Savona Petite p73 50W Pack
P46 Petina
P47 Pico
P80 Mini Sine
p13 Chella
p17 Dyode
p14
Calabor
p15 Dart
p19 Eden
p17
Dyode
p19 Eden
p21 Elled
p22Geneva
Geneva
p22
p13 Chella
Stylish and versatile recessed polycarbonate luminaire or exit sign.
p14 Calabor
Fully recessed emergency luminaire for interior use
p15 Dart
Compact LED downlight range
p17 Dyode
Unique fully recessed LED emergency luminaire
p19 Eden
IP65 compact bulkhead with fresnel lens for improved light distribution with an led option
p21 Elled
Distinctive ceiling mounted led emergency luminaire
p46
p46Petina
Petina
p22 Geneva
Stylish Recessed Fluorescent and LED Luminaire
p46 Petina
Ultra-slim LED single and double-sided exit sign
p51 Rota
Led exit signs suitable for wall or ceiling mounting
p53 Romney
Flexible LED exit sign
p54 Savona
Edge-lit exit signs in single and double-sided versions
p55 Savona Petite
Compact suspended exit sign
p53
p51Romney
Rota
p53 Romney
p54
p55 Savona Petite
p55 Savona Petite
ok out for
o
L
08 | Luminaires
Arc
IP65 compact bulkhead with soft arc linear lens diffuser for
improved performance
Completely manufactured in the UK, Arc was the first luminaire on the market to feature a
Soft Arc Linear Lens Diffuser designed to provide maximum spacings between emergency
luminaires. Even today, very few products are able to meet Arc’s optical performance.
The lens also makes Arc an excellent mains lighting option with T5 or Compact
Fluorescent lamps.
Arc offers many other features with its compact polycarbonate enclosure.These
include a screw fixing diffuser located with brass threaded inserts, centre rear
besa entry and 20mm conduit knockouts at each end plus a hinged steel
gear tray for ease of installation. Making this product one of the
most flexible and best performing luminaires on the market.
The Arc can be fitted with a self adhesive legend SAL 1
kit to create an exit sign or with a semi-recessing
trim, suitable for use with suspended or plaster
board ceilings.
Arc with brass
semi-recessed trim
Arc surface
mounting luminaire
Mains Luminaires
Cat No.
Mode/Lamp
Lumens
Kg
AR 8
1 x 8W 300mm
-
0.90
AR 2x8
2 x 8W 300mm
-
0.90
AR 11 11 W TC-S
-
0.90
Emergency Luminaires
Cat No.
Mode/Lamp
AR8/NM3
NM3 8W 300mm
120S
180H
/E
Economy Output
/O
/S
Standard Output
/H
High Output
/HFHigh Frequency
Ballast
AR/BRBrass Finished
Semi-recess Trim
AR/CHChrome Finished
Semi-recess Trim
/SAL 1Self-adhesive
exit legend kit
/VRAnti-tamper
Screws
/HPFPower Factor
Corrected
/ES
Opal Diffuser
Electronic Start
/ADIntelligent
Addressable
Luminaire
(Non-Maintained
Only)
/STSelf Testing
Luminaire
(Non-Maintained
Only)
80E
1.45
120S
180H NM3 2x8W 300MM
Options Suffix:
AR/WHWhite Finished
Semi-recess Trim
M3 8W 300mm
Kg
1.20
AR2x8/NM3 Viewing distance 18 metres
80E
AR8/M3
SAL1 provides several options
for an exit legend.
Lumens*
150S
1.70
250H
Slave Luminaires
Cat No.
Mode/Lamp
AR8/#/D
8W Slave Luminaire
Lumens*
275
* Emergency Lumens
# Specify 24, 50, 110 or 230 Volts AC/DC System Voltage
* For other durations, specify the required time period e.g. /NM3 becomes /NM1 for 1 hour duration
Dimensions: Length 350mm x Width 108mm x Depth 80mm
Cut out dimensions: Length 330mm x Width 90mm
/TSPush to
Test Switch
KM31508
Kg
0.85
Luminaires | 09
Bakarrac
IP20 Steel and polycarbonate luminaire for interior use
Bakarrac is a high performance bulkhead for interior use featuring a white epoxy coated
sheet steel base fitted with a prismatic polycarbonate diffuser. The base is available in a
range of quality finishes including brass and chrome and an opal diffuser can be specified
if preferred. All models have a hinged gear tray and rear centre besa entry.
The Bakarrac can be supplied with a semi-recessing bezel, in a range of finishes,
is manufactured specifically for this purpose. Bakarrac has a high quality finish for
locations where appearance is important.
The SAL2 legend kit transforms the Bakarrac into an equally high quality
exit sign.
Bakarrac white surface
mounting luminaire
with opal diffuser
Mains Luminaires
Cat No.
Mode/Lamp
Lumens
BA1x8 1x8W 300mm -
1.90
BA2x8
2x8W 300mm
-
1.95
BA11
11W TC-S
-
1.95
BA2x11
2x11W TC-S
-
2.10
Bakarrac with white
semi-recessed trim
and clear diffuser
Kg
Emergency Luminaires
Cat No.
Mode/Lamp
BA8/NM3
NM3 8W 300mm
Lumens*
80E
120S
180H BA8/M3
M3 8W 300mm
80E
120S
180H
BA8/C3
C3 8W 300mm
80E
120S
180H
BA2x8/NM3
150S
NM3 2x8W 300mm
Kg
2.40
2.60
SAL2 provides several options
for an exit legend.
Options Suffix:
2.60
Slave Luminaires
Lumens*
Cat No.
Mode/Lamp
BA8/#/D
8W AC/DC Slave
275
1.90
BA8/#/H
8W Mains/Slave changeover
275
1.90
* Emergency Lumens
# Specify 24, 50, 110 or 230 Volts AC/DC System Voltage
* For other durations, specify the required time period e.g. /NM3 becomes /NM1 for 1 hour duration
Dimensions: Length 370mm x Width 150mm x Depth 100mm
Cut out dimensions: Length 375mm x Width 148mm
Viewing distance 22 metres
2.60
Kg
/HHigh Output
/O
/S
Standard Output
/E
Economy Output
/HFHigh Frequency
Ballast
BA/WHWhite Recessing
Flange
/SAL2Self-adhesive
exit legend kit
/VRAnti-tamper
Screws
/HPFPower Factor
Corrected
IP20
/ES
Opal diffuser
Electronic Start
/ADIntelligent
Addressable
Luminaire
/STSelf Testing
Luminaire
/TSPush to
Test Switch
10 | Luminaires
Bewdley
Robust IP65 bulkhead for exterior or interior use
Designed for use as either a mains bulkhead, or as a robust solution to emergency lighting
requirements, Bewdley has proven to be an outstanding performer.
Its tough all polycarbonate housing is combined with useful features including a hinged
steel gear tray, rear centre besa entry drill starts and 20mm end conduit entries.
Bewdley is supplied with a white base and opal diffuser as standard and a black
base, prismatic or fresnel diffuser are available as options.
An attractive metal base version sealed to IP65 is also available.
Bewdley semi-recessed
with prismatic diffuser
Bewdley with
opal diffuser
Mains Luminaires
Bewdley with
fresnel diffuser
Cat No.
Mode/Lamp
Lumens
Kg
BE1x8 1x8W 300mm -
1.20
BE2x8
2x8W 300mm
-
1.25
BE11
11W TC-S
-
1.25
BE2x11
2x11W TC-S
-
1.35
BE118
1x18W TC-L
-
1.50
Emergency Luminaires
Cat No.
Mode/Lamp
BE8/NM3
NM3 8W 300mm
120S
180H Options Suffix:
/S
Standard Output
/E
Economy Output
/H
High Output
BE/WHWhite Finished
Semi-recess Trim
BE/BRBrass
Semi-recess Trim
BE/CHChrome
Recessing Flange
SAL2Self-adhesive
exit legend
120S
180H
C3 8W 300mm
120S
180H
NM3 2x8W 300mm
/ES
Slave Luminaires
Electronic Start
/STSelf Testing
Luminaire
/TSPush to Test
Switch
/BKBlack Base
/PRPrismatic
Diffuser
/HPFPower Factor
Corrected
/M IP65 Metal Enclosure
/F
Fresnel Diffuser
80E
BE2x8/NM3
/ADIntelligent
Addressable
Luminaire
80E
/HFHigh Frequency
Ballast
/VRAnti-tamper
Screws
/PHDawn/Dusk
Photo cell
M3 8W 300mm
BE8/C3
Viewing distance 22 metres
80E
BE8/M3
SAL2 provides several options
for an exit legend.
Lumens*
150S
Kg
1.70
1.90
1.90
2.20
250H
Cat No.
Mode/Lamp
Lumens*
BE8/#/D
8W AC/DC Slave
275
1.00
BE8/#/H
8W Mains/Slave changeover
275
1.20
* Emergency Lumens
# Specify 24, 50, 110 or 230 Volts AC/DC System Voltage
* For other durations, specify the required time period e.g. /NM3 becomes /NM1 for 1 hour duration
Dimensions: Length 370mm x Width 140mm x Depth 105mm
Cut out dimensions: Length 365mm x Width 135mm
KM31508
Kg
Luminaires | 11
Cadiz
Practical emergency bulkhead for interior use with clip-fit diffuser
Cadiz is the perfect solution to emergency lighting needs in all interior applications where
a clip-fit diffuser is acceptable.
Cadiz is designed for rapid and easy installation with a hinged, clip-out steel gear
tray with pre-formed centre rear besa entry with fixing holes. The body of the
luminaire is injection moulded polycarbonate, along with the diffuser, which
incorporates etched areas to partially obscure the lamp from view.
Robust, low cost, fast to install, easy to clean and maintain,
Cadiz is an ideal product for offices, retail outlets and similar
premises, particularly where cost is critical but a reliable
and an efficient product is required.
The Cadiz semi-recessing trim provides a neat
surround to this product and is available in
white, brass or chrome.
Cadiz surface mounted
Cadiz semi-recessed
with white trim
Emergency Luminaires
Cat No.
Mode/Lamp
CAD8/NM3 NM3 8W 300mm
Lumens*
80E
120S
180H
CAD8/M3 M3 8W 300mm
80E
120S
180H
CAD2x8/NM3 150E
NM3 2x8W 300mm
Kg
1.20
1.45
SAL1 provides several options
for an exit legend.
1.75
Viewing distance 18 metres
240S
Slave Luminaires
Cat No.
Mode/Lamp
CAD8/#/D 8W Slave Luminaire
Lumens*
275
* Emergency Lumens
# Specify 24, 50, 110 or 230 Volts AC/DC System Voltage
* For other durations, specify the required time period e.g. /NM3 becomes /NM1 for 1 hour duration
Dimensions: Length 350mm x Width 108mm x Depth 80mm
Kg
1.00
Options Suffix:
/E
Economy Output
/S
Standard Output
/H
High Output
CAD/WHWhite Finished
Semi-recess Trim
CAD/BRBrass Finished
Semi-recess Trim
CAD/CHChrome Finished
Semi-recess Trim
/SAL1Self-adhesive
Exit Legend Kit
IP42
KM31508
/HPFPower Factor
Corrected
/HFHigh Frequency
Ballast
/ESElectronic Start
/TSPush to Test
Switch
/ADIntelligent
Addressable
Luminaire
(Non-Maintained
Only)
/STSelf Testing
Luminaire
(Non-Maintained
Only)
Orbik.
The best model for any location.
Luminaires | 13
Stylish and versatile recessed polycarbonate luminaire or exit sign.
Chella is an affordable recessed polycarbonate luminaire available with long life LED or 8w
Fluorescent versions.
Chella
Supplied in White as standard, the Chella ranges of luminaires are available in chrome or
brass versions to order.
Chella with
white trim
Chella luminaires all utilise a hinged gear tray for ease of installation and the
range of products includes mains, 3 hour maintained and non-maintained
emergency versions with slave, addressable and self-test
emergency options available.
Chella’s design allows all versions to be utilised as
a stylish edge-lit exit sign by specifying the
optional legend. The attention-to-detail
is illustrated with the effective
light-pipe design, which
enables the charge
LED indicator to be
clearly visible even
during maintained mode.
Other options available for
Chella include slave versions
for central battery or static
inverter systems and self test or
intelligent addressable gear.
Chella with
chrome trim
Mains Luminaires
Cat No.
Mode/Lamp
Lumens
Kg
CHE1X8
1X8W T5 300mm
-
1.00Kg
CHE2X8
2X8W T5 300mm
-
1.00Kg
CHE11
11W TC-S
-
1.00kg
Emergency Luminaires
Cat No.
Mode/Lamp
CHE8/NM3
NM3 8W T5 300mm
Lumens*
80E
120S
180H
CHE8/M3
M3 8W T5 300mm
80E
120S
180H
CHE2X8/NM3
NM3 2x8W T5 300mm
CHE/LED/M3
240S
Kg
1.50Kg
Chella with brass trim
and recessed legend
1.80Kg
1.55Kg
360H
White LED M3
-
1.80Kg
Slave Luminaires
Cat No.
Mode/Lamp
CHE8/#/D
8W AC/DC Slave
Lumens*
275
Kg
1.00Kg
Viewing distance 32 metres
* Emergency Lumens
# Specify 24, 50, 110 or 230 Volts AC/DC System Voltage
* For other durations, specify the required time period e.g. /NM3 becomes /NM1 for 1 hour duration
Dimensions: Length 380mm x Width 150mm
Edge-Lit Versions: Length 380mm x Width 150mm
Cut-Out: Length: Length 360 x Width 130 (70mm Min Ceiling Void)
Viewing Distances: 27 metres
Legend - Length 300 x Width 130mm
Options Suffix:
/H
High Output
/EEconomy Output
/SStandard Output
/BRBrass Finish
For all
Legend details
See Page 57
/CHChrome Finish
IP44
/HPFPower Factor
Corrected
/HFHigh Frequency
Ballast
/ES
Electronic Start
/ADIntelligent
Addressable
/STDigital Self-Test
/EXExit Version
14 | Luminaires
Calabor
Fully recessed emergency luminaire for interior use
Calabor is an attractive, fully recessed emergency luminaire available in white as standard
with brass and chrome as options. The Calabor features a robust galvanised body which
recesses fully into the ceiling and only requires a ceiling depth of 90mm. Within the fitting
a hinged, removable gear tray facilitates easy fixing and maintenance whilst the front trim
plate with a diffuser ensures a neat and attractive finish.
Standard models are supplied with a prismatic polycarbonate diffuser but can be
supplied in opal if preferred.
Calabor is available as a recessed edge-lit exit sign, with an exit fascia
manufactured from Plasi-Glas, a light conducting flame retardant plastic
almost impossible to distinguish from glass, but with the strength
of plastic. Calabor is also available with long life light emitting
diode (LED) light sources.
A version with 11 watt TC-S lamps is available for use
as a rectangular downlight mains luminaire.
Calabor in
white finish
Mains Luminaires
Calabor in
brass finish
Cat No.
Mode/Lamp
Lumens
CAL 1x8
8W 300mm
-
2.20
CAL11
11W TC-S
-
2.25
CAL2x11
2x11W TC-S
-
2.40
Emergency Luminaires
Cat No.
Mode/Lamp
CAL8/NM3
NM3 8W 300mm
Lumens*
80E
120S
180H
CAL2x8/NM3
NM3 2x8W 300mm
240S
CAL8/M3
Calabor in
chrome finish
with exit legend
Viewing distance 32 metres
High Output
/E
Economy Output
/S
Standard Output
/CAL/BRBrass Finish
Fascia
/CAL/CHChrome Finish
Fascia
/HPFPower Factor
Corrected
/OP
Opal diffuser
3.00
360H
M3 8W 300mm
80E
2.90
120S
180H
CAL11/8/C3
C3 11W TC-S + 8W
120S
2.90
CAL/LED/M3
White LED
-
2.20
Cat No.
Mode/Lamp
Lumens*
CAL8/#/D
8W AC/DC Slave
275
2.10
CAL11/#/H
11W Mains/Slave Changeover
650
2.10
* Emergency Lumens
/HFHigh Frequency
Ballast
/ES
Kg
2.70
Slave Luminaires
Options Suffix:
/H
Kg
Electronic Start
/ADIntelligent
Addressable
Luminaire
/STSelf Testing
Luminaire
/EXExit Version
# Specify 24, 50, 110 or 230 Volts AC/DC System Voltage
* For other durations, specify the required time period e.g. /NM3 becomes /NM1 for 1 hour duration
Dimensions: Length 410mm x Width 155mm x Depth 90mm
Calabor Exit Dimensions: Length 300mm x Width 160mm x Depth 150mm
Cut out dimensions: Length 325mm x Width 130mm Ceiling Void 85mm min
For all
Legend details
See Page 57
IP20
Kg
Dart
Compact LED downlight range
Dart is a discreet mains or emergency
downlight, designed to blend in with GU10
and GZ10 mains and low voltage luminaires.
Luminaires | 15
Dart in
white finish
Using the latest high output LED
technology, it is aesthetically attractive,
versatile and is virtually maintenancefree with a lamp life of approximately
50,000 hours.
The Dart packs feature high quality,
high temperature Nickel Cadmium
battery cells and a silicone
coated woven glass
fibre sleeving.
Dart is available in white
as standard but can also be
supplied in brass and
chrome finishes.
Dart in
brass finish
Dart emergency
pack
Luminaires
Cat No.
Mode/Lamp
Lumens
Kg
DAR/LED/WH
White 3 x 1W Luminaire
-
0.50
DAR/LED/BR
Brass 3 x 1W Luminaire
-
0.50
DAR/LED/CH
Chrome 3 x 1W Luminaire
-
0.50
Mains & Emergency Luminaires
Cat No.
Mode/Lamp
DAR/M3
M3 Emergency Pack
Lumens*
-
1.00
DAR/MAINS
Mains Pack
-
1.00
* Mains and emergency packs will operate up to two LED downlights
* For other durations, specify the required time period e.g. /NM3 becomes /NM1 for 1 hour duration
Dimensions: Ø 80mm x 40mm Depth
Dimensions Mains and Emergency Packs: Ø 75mm x 190mm
Cut out dimensions: Ø 75mm
IP20
Kg
Dart in
chrome finish
16 | Luminaires
Dalby
Low profile emergency surface/recessed luminaire/exit sign
Manufactured from Flame-Retardant Polycarbonate, this elegantly designed IP55 Luminaire
is suitable for almost any prestigious application.
Dalby can be used for surface or recessed mounting (when recessed only 25mm protrudes
below the ceiling) and with the addition of a Self-Adhesive Legend, a simple but attractive
Exit sign is created.
The Dalby design also offers an Edge-Lit Exit sign version which can be
confidently specified for projects including Hotels and Reception areas.
Dalby’s diffuser design incorporates a light-pipe ensuring the LED
charge indicator is visible in all modes.
Dalby recessed with
edge lit exit legend
Viewing distance
32 metres
Dalby surface
mounted
Mains Luminaires
Cat No.
Mode/Lamp
DAL8
8W 300mm Mains
Lumens
-
Kg
1.35
Emergency Luminaires
SAL2 provides several options
for an exit legend.
Viewing distance 22 metres
Cat No.
Mode/Lamp
DAL8/NM3
NM3 8W 300mm
Lumens*
80E
120S
180H
DAL2x8/NM3
240S
NM3 2x8W 300mm
DAL8/M3
Kg
1.80
3.00
360H
M3 8W 300mm
80E
120S
180H
2.00
Slave Luminaires
Cat No.
Mode/Lamp
DAL8/#/D
8W Slave Luminaires
Lumens*
275
* Emergency Lumens
Options Suffix:
/H
High Output
/EEconomy Output
/S
Standard Output
/SAL2Self-adhesive
Exit Legend Kit
/HPFPower Factor
Corrected
/HFHigh Frequency
Ballast
/ES
Electronic Start
/ADIntelligent
Addressable
Luminaires
# Specify 24, 50, 110 or 230 Volts AC/DC System Voltage
* For other durations, specify the required time period e.g. /NM3 but for 1 hour duration becomes /NM1
Dimensions: Length 355mm x Width 195mm x Depth 70mm
Dalby Exit Dimensions: Length 355mm x Width 195mm x Depth 220mm
Cut out dimensions: Length 335mm x Width 175mm
/STSelf Testing
Luminaires
/TSPush to Test
Switch
/EX/L+Edge-lit Exit Kit
/RRecessing Kit
For all
Legend details
See Page 57
IP55/IP20
Kg
1.10
Luminaires | 17
Dyode
Unique fully recessed LED emergency luminaire.
At just 50mm in diameter Dyode is one of the smallest recessed LED
based emergency luminaires currently available and the superbly
designed refractor lens assembly which is incorporated into a high
quality injection moulded housing offering an IP20 protection rating
accentuates the virtues of the high power white LED light source.
By utilizing a specially developed LED driver and advanced thermal
engineering techniques to dramatically reduce the LED
operating temperature the light output level from the LED
is guaranteed throughout the full emergency duration,
ensuring the life of the LED exceeds 50,000 hours.
Two versions of the advanced lens designs are
available. One specifically for corridor lighting offers an
elongated distribution pattern to efficiently illuminate
the centre line of escape route corridors and extends
the spacing distance between luminaires.
The second offers a more traditional cone distribution
pattern for use in open areas or for specific task
lighting. These unique features allow the emergency
lighting scheme designer the option of incorporating
Dyode into an existing mains only luminaire, to create
an unobtrusive low maintenance integrated
emergency luminaire.
Alternatively they can be used in standalone applications
for emergency lighting.
The control circuitry is housed in a robust metal assembly and along with
the Ni-MH battery pack is contained within a high quality flexible silicone
sleeve which can easily pass through the 40mm cut out required for Dyode
when mounted independently in a ceiling void.
All Dyode products are available with a self-test facility.
Dyode NM3
emergency
pack
Actual size
Options Suffix:
Emergency Luminaires
Cat No.
Mode/Lamp
DY/LED/NM3/OA
NM3 LED OPEN AREA
DY/LED/NM3/CR
NM3 LED CORRIDOR
Lumens*
Kg
75
0.1
75
0.1
DY/LED/NM3/OA/ST NM3 LED OPEN AREA SELF TEST
75
0.1
DY/LED/NM3/CR/ST
75
0.1
NM3 LED CORRIDOR SELF TEST
* Emergency Lumens
* For other durations, specify the required time period e.g. /NM3 but for 1 hour duration becomes /NM1
Dimensions: Ø 50mm x 32mm depth (22mm above ceiling)
Cut out dimensions: Ø 40mm
IP20
/BR
Brass finish
/CHChrome Finish
18 | Luminaires
Ecos
IP65 robust polycarbonate luminaire for interior and
exterior use
Over 1.4 kilograms of UV stabilised, flame retardant polycarbonate
is used in each Ecos body and its sheer toughness has been
illustrated by its successful use in police and magistrates cells,
military establishments, schools and public areas.
Ecos is sealed to IP65 as standard and has a choice
of a clear ‘Radial’ lens for enhanced photometric
performance and with a white base opal diffuser. It is
available with 2D lamps ranging from 28 to 55 watts
and 24w compact lamps. Versions up to 2 x 24w can
have integral emergency gear.
All versions have a hinged steel gear tray, and a white
base as standard. Ecos can also be recessed with an
optional white trim.
Ecos with white
base and clear diffuser
Mains Luminaires
Cat No.
Mode/Lamp
EC28
28W 2D
Lumens
-
2.80
Kg
EC38
38W 2D
-
2.80
EC55
55W 2D
-
2.80
EC24
1x24W TC-F
-
2.80
EC2x24
2x24W TC-F
-
2.90
EC40
40W T5 Circular
-
2.80
EC40/22
40W and 22W T5 Circular
-
2.80
Emergency Luminaires
Ecos with white semi-recessing
trim and opal diffuser
Options Suffix:
/ECR/WH White Recessing
Trim
/HF
High Frequency
Ballast
/BK
/ES
Electronic Start
Black base
/VRAnti-tamper
Screws
/HFHigh Frequency
Ballast
/HPF
Power Factor
Corrected
/ES
/ST
Self Testing
Luminaires
/O
Opal Diffuser
/PH
Dawn/Dusk
Photo Cell
Electronic Start
/ADIntelligent
Addressable
Luminaire
/TSPush to
Test Switch
Cat No.
Mode/Lamp
EC24/M3
M3 1x24W TC-F
Lumens*
120
3.10
Kg
EC2x24/M3 M3 2x24W TC-F
120
3.20
EC28/M3
M3 28W 2D
270
3.10
EC38/M3
M3 38W 2D
625
3.10
Cat No.
Mode/Lamp
Lumens*
EC28/#/H
28W 2D Mains/Slave
500
2.90
EC38/#/H
38W 2D Mains/Slave
500
2.90
Slave Luminaires
* Emergency Lumens
# Specify 24, 50, 110 or 230 Volts AC/DC System Voltage
* For other durations, specify the required time period e.g. /M3 becomes /M1 for 1 hour duration
Dimensions Standard: Ø 397mm x 132mm
Dimensions With Recess Trim: Ø 406mm x 86mm x 46mm into void
KM31508
Kg
Eden
IP65 compact bulkhead with fresnel lens for improved light
distribution with an led option
Eden is an attractive weatherproof IP65 luminaire available in both Non-Maintained and
Maintained emergency modes. It can be supplied with an 8W T5 fluorescent lamp or
alternatively using LED’s with a life of approximately 50,000 hours.
Luminaires | 19
The Eden body is manufactured in white flame retardant polycarbonate.
Eden’s polycarbonate diffuser incorporates a Fresnel lens, ensuring excellent
light distribution.
To aid rapid installation, Eden is fitted with a hinged geartray and
has side and rear entry points moulded into the base.
Eden is available with a number of options including
semi-recessing kits and self-adhesive exit legends.
Eden with white
semi-recessing trim
Emergency Luminaires
Cat No.
Mode/Lamp
Lumens*
ED8/NM3/E
8 Watt NM3 80
1.20
ED8/M3/E
8 Watt M3 80
1.45­
ED/LED/M3
LED NM/M3
-
1.20­
* Emergency Lumens
Dimensions: Length 350mm x Width 108mm x Depth 80mm
Dimensions (Semi-Recess Cut-Out): Length 330mm x Width 90mm­­­­
SAL1 provides several options
for an exit legend.
Kg
Viewing distance 18 metres
Options Suffix:
/ED/BR
Brass SemiRecess Kit
/ED/CHChrome SemiRecess Kit
/ED/WH White Semi
Recess Kit
/SAL1Self-Adhesive
Legend Kit
Sm
al
l is
n’
tj
us
tb
ea
ut
ifu
l
It’
sg
or
ge
ou
s
Elled
Distinctive ceiling mounted led emergency luminaire
Elled is a fully self contained, high power white LED light sourced emergency
lighting luminaire which has been designed to seamlessly blend into lighting
schemes by imitating the design ethics of fire detection and CCTV head units.
Amongst its many innovative features is the use of an advanced
design of LED driver, which provides a constant level of
illumination throughout the emergency duration and ensure
the LED operating temperature is at an optimum ensuring
an LED life in excess of 50,000 hours. The use of
Ni-MH cells and monitored charging combined with
RoHS compliant components and a polycarbonate
enclosure ensures a low in service environmental
impact and easy disposal at the end of life.
To provide the ultimate spacing between
luminaires on emergency exit corridor routes
and to ensure the requirements of EN1838 can
be easily met, the sophisticated photometrically
optimised refractor lens gives a type 1 light
distribution pattern, whereas, for open areas or
specific task illumination a second lens option can
be specified that provides the more traditional cone
of light.
Automatic self-testing versions can be specified which
conform to the requirements of BS EN62034:2006 and
conduct testing in accordance with BS EN50172:2004.
Self-testing versions provide both a visual and an audible test
failure indication and the results of the last test are displayed via
a multi-coloured LED indicator. A volt-free contact is made available
allowing a simple system fault monitoring facility to be incorporated
into the system.
Emergency Luminaires
Cat No.
Mode/Lamp
Lumens*
Kg
ELL/LED/NM3/OA
NM3 LED OPEN AREA
45
0.5
ELL/LED/NM3/CR
NM3 LED CORRIDOR
45
0.5
ELL/LED/NM3/OA/ST NM3 LED OPEN AREA SELF TEST
45
0.5
ELL/LED/NM3/CR/ST NM3 LED CORRIDOR SELF TEST
45
0.5
* Emergency Lumens
Dimensions: Ø 120mm x 67mm depth (35mm above ceiling)
Cut out dimensions: Ø 100mm
IP55
Luminaires | 21
design
22 | Luminaires
Geneva
Stylish recessed fluorescent and LED luminaire
Geneva is an impressive design of high quality recessed emergency lighting luminaires.
Available in white, chrome or brass finishes, Geneva is manufactured in steel with an epoxy
coating to create a robust, simplistic but unobtrusive and elegant luminaire, suitable for
almost any prestigious retail application. The Geneva range of emergency luminaires can be
specified as an 8W Fluorescent or LED Luminaire that offers long lamp life options of up to
50,000 hours. Its prismatic lens controller ensures optimised light distribution.
An optional exit legend is available for all versions transforming Geneva into
a beautiful edge-lit exit sign with impressive uniform light distribution,
which can be confidently specified for almost any prestigious
project including hotels, conference centres and retail
shopping centres.
Geneva finished
in white
Available in 3 hour emergency non-maintained
and maintained options, Geneva can
also be specified as a slave luminaire
for use on central battery and
static inverter systems.
Geneva LED Exit
finished in white
Viewing distance
32 metres
Emergency Luminaires
Silver-grey
Brass
Chrome
Options Suffix:
/BR
Brass Finish
/SGSilver Grey Finish
/CH
Chrome Finish
/EX
Edge-Lit Exit
Lumens*
Mode/Lamp
GN/LED/M3
M3 LED Luminaire
-
1.00
GN8/NM3
NM3 8W 300mm
120
1.20
GN8/M3
M3 8W 300mm
120
1.50
Slave Luminaires
Cat No.
Mode/Lamp
GN8/#/D
8W Slave Luminaire
Lumens*
275
* Emergency Lumens
For all
Legend details
See Page 57
Kg
Cat No.
# Specify 24, 50, 110 or 230 Volts AC/DC System Voltage
* For other durations, specify the required time period e.g. /NM3 becomes /NM1 for 1 hour duration
Dimensions: Length 360mm x Width 90mm. Requires minimum ceiling void of 80mm
Geneva Exit Dimensions: Length 360mm x Width 90mm x Depth 160mm
Cut out dimensions: 325mm x 80mm
IP20
Kg
1.20
Luminaires | 23
Holt
A rugged IP65 square luminaire
A robust IP65 luminaire suitable for interior and exterior applications supplied as standard
with rear besa and side conduit entries.
Captive screws secure the prismatic diffuser to the white base, with options for an
alternative opal diffuser, and black base.
Holt’s all polycarbonate housing is robust enough to be used in a wide range of
lighting applications and has the advantage of matching models with integral
emergency control gear.
Holt with black
base and opal
diffuser
Holt with white
base and clear
diffuser
Options Suffix:
Mains Luminaires
Cat No.
Mode/Lamp
Lumens
Kg
HT16A
16W 2D Size A
-
1.10
HT28B
28W 2D Size B
-
2.00
Emergency Luminaires
Cat No.
Mode/Lamp
Lumens*
Kg
HT16B/M3
16W M3 Size B
200
3.00
HT28B/M3
28W M3 Size B
270
3.00
HT28B/24/3S
28W Mains + 2x4W NM3 Size B
160
3.00
Slave Luminaires
Cat No.
Mode/Lamp
HT16A/#/D
16W 2D Size A
Lumens*
400
1.10
HT28B/#/D
28W 2D Size B
500
1.50
* Emergency Lumens
# Specify 24, 50, 110 or 230 Volts AC/DC System Voltage
* For other durations, specify the required time period e.g. /M3 becomes /M1 for 1 hour duration
Dimensions Size A: Length 210mm x Width 210mm x Depth 100mm
Dimensions Size B: Length 255mm x Width 255mm x Depth 90mm
IP65
Kg
/AD
Intelligent
Addressable
Luminaire
/HPF
Power Factor
Corrected
/ST
Self Testing
Luminaire
/O
Opal diffuser
/BK
Black Base
/PH
Dawn/Dusk
Photo Cell
/VR
Anti-tamper
Screws
/HF
High Frequency
Ballast
/ES
Electronic Start
Style and function
in perfect balance
Luminaires | 25
Idro
A robust and attractive circular aluminium diecast IP65
exterior bulkhead
Idro is a range of robust but versatile circular die-cast IP65 exterior bulkheads. Suitable for
wall and ceiling mounted applications, Idro luminaires can be specified with an
optional decorative guard, or with an effective and attractive anti-light
pollution eyelid or alternatively this luminaire can be selected for
use with its toughened polycarbonate opal diffuser alone.
Idro in black with
guard option
Supplied with vandal resistant screws as standard, Idro
is available in black (as standard) or silver-grey, and
can be used as a mains or 3 hour integral emergency
non-maintained and maintained luminaire.
Other options available to Idro are as a slave
luminaire for use with central battery or static
inverter systems, with self-test or addressable
emergency lighting gear.
Idro in silver-grey
Idro in silver-grey
with eyelid option
Mains Luminaires
Cat No.
Mode/Lamp
Lumens
Kg
IDR28
1x28W 2D Mains
-
6.0Kg
IDR38
1x38W 2D Mains
-
6.0Kg
Emergency Luminaires
Cat No.
Mode/Lamp
Lumens*
Kg
IDR28/M3
M3 28W 2D
270
7.0kg
IDR38/M3
M3 38W 2D
625
7.0kg
Cat No.
Mode/Lamp
Lumens*
IDR28/#/D
28W 2D AC/DC Slave
500
6.5Kg
IDR38/#/D
38W 2D AC/DC Slave
500
6.5kg
Slave Luminaires
* Emergency Lumens
Replace # with AC/DC system Voltage 24, 50, 110 or 230 Volts
* For other durations, specify the required time period e.g. /M3 becomes /M1 for 1 hour duration
Dimensions: 360mm x Depth 130mm
Depth 155mm With Optional Guard/Eyelid
IP65
Kg
Options Suffix:
/SG
Silver-Grey Finish
/ES Electronic Start
/EY
Eyelid Version
/GU
Guard
/AD Intelligent
Addressable
/HPF
Power Factor
Corrected
/ST Digital SelfTest
/HF
High Frequency
Ballast
26 | Luminaires
Kalix
Superbly designed wall light suitable for hotels
and commercial buildings
Kalix is an impressive and sleek range of elegantly profiled fluorescent luminaires which
utilises the latest energy saving high performance 14W T5 lamps.
Manufactured from sheet steel, Kalix is available in white
as standard and can also be supplied in silver-grey with a choice
of 2 diffusing fascias to accommodate the ambience of their
installation.
This unobtrusive but robust high quality high frequency
luminaire provides an impressive soft diffused illuminance
and its minimalistic low profile design creates a superb wall or
ceiling mounted luminaire.
Available in single and twin 14W high-frequency mains
versions, Kalix offers the option of integral 3 hour BSI
approved emergency control gear which on mains failure
ensures reliable emergency back up, achieving a Ballast
Lumens Factor (BLF) of 32%.
The Kalix range of Luminaires are suitable as Slave
Luminaires for use with central battery or static
inverter systems and can be specified for use with
self test or intelligent addressable emergency gear.
Kalix in white
Style A
Kalix in white
Style B
Options Suffix:
Mains Luminaires
/A
Kalix Style A
Cat No.
Mode/Lamp
/B
Kalix Style B
/AD
Intelligent
Addressable
KAL14
14W T5 HF Mains
-
2.60kg
KAL2X14
2X14W T5 HF Mains
-
2.70Kg
/ST
Digital SelfTest
Emergency Luminaires
/SG
Silver Grey
Cat No.
Mode/Lamp
KAL14/M3
14W T5 M3 Emergency
384
3.50Kg
KAL214/M3
2x14W T5 M3 Emergency
384
3.60Kg
Lumens
Lumens*
Kg
Kg
Slave Luminaires
Cat No.
Mode/Lamp
KAL14/#/D
14W T5 AC/DC Slave
Lumens*
500
* Emergency Lumens
Replace # with AC/DC system voltage 24, 50, 110 or 230 Volts
* For other durations, specify the required time period e.g. /M3 but for 1 hour duration becomes /M1
Dimensions: Length 585mm x Width 200mm x Depth 42mm
IP20
Kg
2.60Kg
Karis
Stylish and contemporary luminaire ideal for
prestigious applications
The Karis range of luminaires offer an elegant appearance
with a host of options which creates flexibility suitable for
most commercial applications.
Luminaires | 27
Karis is a decorative but robust high quality luminaire using
energy saving compact fluorescent lamps. Its steel base is
supplied in white as standard with silver-grey as an option,
with an elegant polycarbonate diffuser designed to evenly
diffuse its luminance.
Supplied as a mains and integral emergency luminaire, Karis
offers single and twin lamp versions as standard in mains mode
with 1 lamp being used for emergency versions.
This stylish luminaire is suitable for ceiling or wall mounted
applications and its facility to include an optional wire suspension
kit enables this range of luminaires to be confidently specified for
virtually all projects where matching mains and emergency
luminaires are required.
Karis can be supplied as a slave luminaire for use with central
battery systems or static inverters and can be supplied with self-test
emergency and intelligent addressable emergency systems
Karis finished
in white
Mains Luminaires
Cat No.
Mode/Lamp
KAR18
1 X 18W TC-D/E Mains
Lumens
-
1.90Kg
Kg
KAR2X18
2 X 18W TC-D/E Mains
-
1.90Kg
KAR26
1 X 26W TC-D/E Mains
-
1.90Kg
KAR2X26
2 x 26w TC-D/E Mains
-
1.90Kg
Emergency Luminaires
Cat No.
Mode/Lamp
Lumens*
Kg
KAR18/M3
1 X 18W TC-D/E M3
276
2.70Kg
KAR2X18/M3
2 X 18W TC-D/E M3
276
2.80Kg
KAR26/M3
1 X 26W TC-D/E M3
324
2.70Kg
KAR2X26/M3
2 x 26w TC-D/E M3
324
2.80Kg
Karis finished in
silver-grey with wire
suspension kit
Slave Luminaires
Cat No.
Mode/Lamp
Lumens*
KAR18/#D
1 X 18W TC-D/E Slave
420
1.90Kg
KAR2X18/#D
2 X 18W TC-D/E Slave
420
1.90Kg
Options Suffix:
KAR26/#D
1 X 26W TC-D/E Slave
540
1.90Kg
/SG
Silver Grey
KAR2X26/#D
2 x 26w TC-D/E Slave
540
1.90Kg
/HPF
Power Factor
Corrected
/HF High Frequency
Ballast
/AD Intelligent
Addressable
* Emergency Lumens
Replace # with AC/DC system Voltage 24, 50 , 110 or 230v Volts
* For other durations, specify the required time period e.g. /M3 becomes /M1 for 1 hour duration
Dimensions: Length 345mm x Width 345mm x Depth 100mm
IP20
Kg
/ST
Digital SelfTest
/WS1
Wire
Suspension Kit
/RS1
Rod
Suspension Kit
Kolour concepts
Kandel with white
reflective trim
Blue Backlight
Green Backlight
Red Backlight
Luminaires | 29
Circular surface or semi-recessed IP54 luminaire
An attractive range of circular IP54 white polycarbonate luminaires, Kandel can be specified
as a mains or emergency luminaire with integral emergency gear.
Kandel
Kandel brass
trim
Kandel can be surface mounted or semi-recessed and now has the option of a rod or
wire suspension kit enabling Kandel to be confidently specified for almost any interior
application.
An attractive range of high quality surface trims are available in white brass or chrome,
which transform Kandel into a stylish range of mains and emergency luminaires.
The optional choice of opal, green, red or blue halo effects for Kandel luminaires allows
them to be confidently specified for several applications where a certain colour theme
is required such as hotels, hospitals, restaurants
etc. This is particularly effective when
combined with the new wide
angled reflecting trim.
Kandel chrome
trim
Installation and
maintenance is
simplified due to
the design of the
twist-and-lock
diffuser, which
is supplied
in opal as
standard with
an alternative
prismatic
diffuser
available.
Kandel white
trim
Mains Luminaires
Cat No.
Mode/Lamp
KN16
16W 2D Mains
Lumens
-
0.50
Kg
KN28
28W 2D Mains
-
0.50
KN38
38W 2D Mains
-
0.50
Emergency Luminaires
Options Suffix:
Kg
/AD
Intelligent
Addressable
Luminaire
/RS2Rod Suspension
Kit (600mm)
/HF
High Frequency
/HPF
Power Factor
Correction
/ST
Self Testing
Luminaires
Cat No.
Mode/Lamp
Lumens*
KN16/NM3
16W 2D NM3
160
2.90
/ES
Electronic Start
KN16/M3
16W 2D M3
160
3.00
/R
Recessing Kit
KN28/NM3
28W 2D NM3
280
3.00
KN28/M3
28W 2D M3
280
3.00
KN28/24/3S
28W Mains + 2x4W NM3
160
2.70
/WS2Wire
Suspension Kit
Surface Trims Options Suffix:
KN/BRBrass Surface
Trim
Slave Luminaires
Cat No.
Mode/Lamp
Lumens*
KN16/#/D
16W 2D Slave Emergency
420
2.30
KN28/#/D
28W 2D Slave Emergency
650
2.30
KN38/#/D
38W 2D Slave Emergency
650
2.30
* Emergency Lumens
# Specify 24, 50, 110 or 230 Volts AC/DC System Voltage
* For other durations, specify the required time period e.g. /NM3 becomes /NM1 for 1 hour duration
Dimensions: Ø 360mm x Depth 85mm
Cut out dimensions: Ø 335mm x 50mm Minimum Ceiling Void
Kg
KN/CHChrome Surface
Trim
Reflecting Trims Options Suffix:
KRT/BRBrass
Reflecting Trim
KRT/WHWhite
Reflecting Trim
KRT/CHChrome
Reflecting Trim
Back Light Effect Options
(opal halo effect back light standard)
/BUBlue Halo Effect
IP54
KN/WHWhite Surface
Trim
/GNGreen Halo
/RDRed Halo Effect
30 | Luminaires
Kea
A stylish exit sign or wall luminaire for prestigious interior applications
Kea stylish appearance coupled with it’s distinctive symmetrical design makes it ideal for the
most prestigious applications.
Suitable as an exit sign or a high frequency mains/emergency luminaire, Kea is available in
white as standard with an attractive silver grey finish as an option.
Kea finished
in silver-grey
Kea finished in
white with exit legend
Viewing distance
30 metres
Options Suffix:
/AD
/EX
Intelligent
Addressable
Luminaire
Exit Fascia
Mains Luminaires
/STDigital
Self-Test
/SG
Silver Grey
Finish
Cat No.
Mode/Lamp
KE14
14W T5 HF Mains
Lumens
-
3.20
Kg
KE36
36W TC-L HF Mains
-
3.30
Emergency Luminaires
Cat No.
Mode/Lamp
KE14/M3
14W T5 M3 Emergency
Lumens*
384
4.20
Kg
KE36/M3
36W TC-L M3 Emergency
435
4.20
Slave Luminaires
Cat No.
Mode/Lamp
KE14/#D
14W T5 Slave Emergency
Lumens*
384
3.20
KE36/#D
36W TC-L Slave Emergency
435
3.30
* Emergency Lumens
Replace # with AC/DC 24, 50, 110 or 230 system Voltage
* For other durations, specify the required time period e.g. /M3 but for 1 hour duration becomes /M1
Dimensions: 610mm Length x 200mm Width x 105mm Depth
For all
Legend details
See Page 57
IP20
Kg
Luminaires | 31
Classically styled decorative luminaire for energy saving lamps
The Lavaine range of luminaires feature a classic styling consisting of a steel gallery finished
in either brass or chrome polished plate and an opal glass diffuser. The diffuser is held in
place by three knuckle screws finished to match the gallery.
Lavaine
Lavaine features mains, emergency and slave
luminaires available in two body sizes.
The elegant family is a popular
choice for many applications
where a prestigious, reliable
range of matching mains and
emergency luminaires are
required.
Lavaine with
chrome finish
Lavaine with
brass finish
Mains Luminaires
Options Suffix:
/HF
High Frequency
Ballast
Brass Finish
/HPF
Power Factor
Corrected
/CH
Chrome Finish
/ST
Digital Self Test
/ES
Electronic Start
Cat No.
Mode/Lamp
LV16B
16W 2D Mains Luminaire Size B
-
2.00
/ADIntelligent
Addressable
Luminaire
LV28B
28W 2D Mains Luminaire Size B
-
4.00
/BR
LV38B
38W 2D Mains Luminaire Size B
-
4.00
LV28C
28W 2D Mains Luminaire Size B
-
4.80
LV38C
38W 2D Mains Luminaire Size C
-
4.80
Lumens
Kg
Emergency Luminaires
Cat No.
Mode/Lamp
LV16/3NM
16W 2D NM3 Emergency Size B
Lumens*
200
3.00
Kg
LV16/3M
16W 2D M3 Emergency Size B
200
3.00
LV28/3NM
28W 2D NM3 Emergency Size C
280
4.60
LV28/3M
28W 2D M3 Emergency Size C
280
4.60
Slave Luminaires
Cat No. Mode/Lamp
Lumens*
Kg
LV16/#/D
16W 2D AC/DC Slave Luminaire Size B
400
1.80
LV28/#/D
28W 2D AC/DC Slave Luminaire Size C
500
3.80
LV38/#/D
38W 2D AC/DC Slave Luminaire Size C
500
3.80
* Emergency Lumens
# Specify 24, 50, 110 or 230 Volts AC/DC System Voltage
* For other durations, specify the required time period e.g. /NM3 becomes /NM1 for 1 hour duration
Dimensions Size B: Ø 360mm x depth 140mm
Dimensions Size C: Ø 390mm x depth 180mm
IP20
32 | Luminaires
Larino
Elegant circular lighting range
Designed for universal application within any lighting project, the Larino range of luminaires
are available in three diameters: 330mm, 430mm and 525mm.
Larino luminaires feature a spun metal base containing the control gear and energy saving
compact fluorescent lamps. Models can be either mains only operation or, in selected
versions, incorporate integral emergency gear.
Larino’s base is available in a range of
epoxy coated and plated finishes
and can be supplied with a
smooth, polished opal or
clear prismatic diffuser.
New options include wire
and rod suspension kits
for that added elegant
touch.
Larino is available as
standard with a white
base and opal diffuser.
Larino finished
in brass
Mains Luminaires
Larino finished
in chrome
Cat No.
Mode/Lamp
Lumens
Kg
LAR16
16W Size A
-
1.10
LAR28A
28W Size A
-
2.00
LAR28
28W Size B
-
2.10
LAR38
38W Size B
-
2.10
LAR226HF
2x26W Size C
-
2.60
LAR55
55W Size C
-
2.60
Emergency Luminaires
Cat No.
Mode/Lamp
LAR16/M3
16W M3 Size A
Lumens*
200
2.70
Kg
LAR28/M3
28W M3 Size B
270
3.00
LAR38/M3
38W M3 Size B
625
3.00
LAR226/M3
2x26W M3 Size C
324
3.70
LAR55/M3
55W M3 Size C
450
3.70
Slave Luminaires
Options Suffix:
/BR
Brass Finish
/CH
Chrome Finish
/PR
Prismatic
Diffuser
/HPF
Power Factor
Corrected
/HF
High Frequency
Ballast
/ES
Electronic Start
/AD
Intelligent
Addressable
Luminaire
/ST
Self Testing
Luminaire
/WS2Wire
Suspension Kit
/RS2Rod Suspension
Kit (600mm)
Cat No.
Mode/Lamp
Lumens*
LAR16/#/D
16W Size A
400
1.00
LAR28/#/D
28W Size B
500
2.00
LAR38/#/D
38W Size B
500
2.00
* Emergency Lumens
# Specify 24, 50, 110 or 230 Volts AC/DC System Voltage
* For other durations, specify the required time period e.g. /M3 becomes /M1 for 1 hour duration
Dimensions Size A Ø 330mm x 105mm
Dimensions Size B: Ø 430mm x 105mm
Dimensions Size C: Ø 525mm x 105mm
IP20
Kg
Simple elegance
34 | Luminaires
Lens
Contemporary circular luminaire with a halo effect back
light creating a touch of style to interior applications
Lens is a stylish range of circular polycarbonate luminaires available in mains and integral
emergency versions.
Supplied as standard with an opal base, white straight sided clip-on metal trim and an opal
diffuser. Lens luminaires offer a comprehensive range of options including a prismatic
diffuser, with alternative clip-on trims which can be specified as curved or straight sided in
white, brass, chrome or black chrome.
Lens with white
straight trim
The optional choice of blue, green or red halo effects allows
you to tailor this luminaire to meet your exacting
requirements where a specific colour theme is
required, enhancing any installation.
Lens is now available with a stylish broad
deluxe trim in all colour options.
Lens with
brass curved trim
Mains Luminaires
Cat No.
Mode/Lamp
LN28
28W 2D White Mains
Lumens
-
2.70
Kg
LN38
38W 2D White Mains
-
2.70
Emergency Luminaires
Cat No.
Mode/Lamp
Lumens*
Kg
LN28/M3
28W 2D M3 White Emergency
384
3.60
LN38/M3
38W 2D M3 White Emergency
625
3.60
Slave Luminaires
Cat No.
Mode/Lamp
Lumens*
LN28/#D
28W 2D Slave White Emergency
500
2.60
LN38/#D
38W 2D Slave White Emergency
500
2.60
* Emergency Lumens
# Specify 24, 50, 110 or 230 Volts AC/DC System Voltage
* For other durations, specify the required time period e.g. /M3 becomes /M1 for 1 hour duration
Curved Trim Version Dimensions: Ø 500mm x Depth 105mm
Straight Sided Trim Version Dimensions: Ø 490mm x Depth 105mm
Broad Deluxe Trim Version Dimensions: Ø 525mm x Depth 105mm
IP20
Kg
Luminaires | 35
Lens with black
chrome broad deluxe trim
Opal Backlight
Blue Backlight
Green Backlight
Lens with chrome
broad deluxe trim
Red Backlight
Metal Trim & Colour Finish Options
(white straight sided trim standard)
/S/BRBrass Finish
Straight Sided
Metal Trim
/C/GMBlack Chrome
Finish Curved
Metal Trim
/S/CHChrome Finish
Straight Sided
Metal Trim
/BD/WHWhite Finish
Broad Deluxe
Metal Trim
/S/GMBlack Chrome
Finish Straight
Sided Metal Trim
/BD/BRBrass Finish
Broad Deluxe
Metal Trim
/C/WHWhite Finish
Curved Metal
Trim
/BD/CHChrome Finish
Broad Deluxe
Metal Trim
/C/BRBrass Finish
Curved Metal
Trim
/BD/GMBlack Chrome
Broad Deluxe
Sided Metal Trim
/C/CHChrome Finish
Curved Metal
Trim
Back Light Effect Options
(opal halo effect back light standard)
/BUBlue Halo Effect
Back Light
/RDRed Halo Effect
Back Light*
/GNGreen Halo
Effect Back Light*
* Green and red back light
effect luminaires are
manufactured to order.
Options Suffix
/ADIntelligent
Addressable
Luminaire
/HPFPower Factor
Correction
/ES
/WSWire
Suspension Kit
Electronic Start
/HFHigh Frequency
Ballast
/ST
Digital Self-Test
/RSRod
Suspension Kit
36 | Luminaires
Mezzina
IP65 circular polycarbonate utility luminaire for interior and exterior use
Mezzina is available as a mains/emergency bulkhead luminaire designed specifically
for energy efficient compact fluorescent lamps to provide designers and installers with
maximum flexibility.
Mezzina is sealed to IP65 and has a screw fit diffuser sealed to the body with a
closed cell neoprene gasket for durability. Mezzina’s pleasing appearance
lends it to both exterior and interior applications.
The control gear is mounted on a removable steel gear tray and
the all polycarbonate white housing has drill starts for both
centre rear Besa entry or 20mm surface conduit entries. Three
surface conduit entries are provided. It comes as standard
with a clear diffuser and Techno Radial lens technology.
An opal diffuser and a black base can be supplied as
options and an attractive recessing trim available in white
finish, enables Mezzina to be confidently specified in a
wide range of applications.
Mezzina with white
recessing trim
Mezzina with
white base
Mains Luminaires
Mezzina with
black base
Cat No.
Mode/Lamp
MZ16
16W Mains Luminaire
Lumens
-
1.10
Kg
MZ28
28W Mains Luminaire
-
1.10
MZ38/HF
38W HF Mains Luminaire
-
1.10
Emergency Luminaires
Cat No.
Mode/Lamp
Lumens*
Kg
MZ16/M3
16W M3 Emergency Luminaire
200
2.70
MZ28/M3
28W M3 Emergency Luminaire
270
3.00
Slave Luminaires
Options Suffix:
/MZR/W White
Recessing Trim
/HF
High Frequency
Ballast
/BK
Black Base
/ES
Electronic Start
/O
Opal Diffuser
/VR
Anti-tamper
Screws
/AD
Intelligent
Addressable
Luminaire
/HPF
Power Factor
Corrected
/ST
Self Testing
Luminaire
/PH
Dawn/Dusk
Photo cell
Cat No.
Mode/Lamp
Lumens*
MZ16/#/D
16W 2D Slave Luminaire
400
1.10
MZ28/#/D
28W 2D Slave Luminaire
500
1.10
* Emergency Lumens
# Specify 24, 50, 110 or 230 Volts AC/DC System Voltage
* For other durations, specify the required time period e.g. /M3 becomes /M1 for 1 hour duration
Dimensions: Ø 290mm x 79mm
Dimensions (Below Ceiling) With Recess Trim: 345mm x 50mm
Cut out dimensions: Ø 295mm
IP65
Kg
Luminaires | 37
Monza
A range of miniature compact fluorescent downlights
A stylish range of affordable high quality recessed
downlighters; the Monza range has been
specifically designed to accommodate energy
saving compact fluorescent lamps as mains
luminaires.
Available as 13W or 18W TC-DE lamps (lamps
not included), the Monza downlighter range
offers a 3 hour emergency version for both
lamps.
Orbik’s BSI approved Kite Marked emergency
control gear and Nickel Cadmium battery
pack are contained in a silicone coated woven
glass Fibre sleeve which can be offered into
the ceiling via the cut out.
Monza with white trim
During emergency discharge, the high
ballast lumen factors (BLF) achieved (29%
for 13W, 17% for 18W) ensure reliable
emergency lighting even when low-mercury
lamps are in use.
The Monza range is available as standard
in White with brass or chrome options and
has optional attachments including dropglass which ensures the Monza’s range of
recessed down lighters can be confidently
specified in both mains and emergency
lighting for most indoor applications.
Monza with chrome trim
and drop glass
Monza with brass trim
and drop glass
Mains Luminaires
Cat No.
Mode/Lamp
MO13
13W TC-D/E Mains
Lumens
-
0.40
Kg
MO18
18W TC-D/E Mains
-
0.50
Emergency Luminaires
Cat No.
Mode/Lamp
MO13/M3
13W TC-D/E Downlight
Lumens*
260
1.30
Kg
MO18/M3
18W TC-D/E Downlight
200
1.40
* Emergency Lumens
Options Suffix:
# Specify 24, 50, 110 or 230 Volts AC/DC System Voltage
* For other durations, specify the required time period e.g. /M3 becomes /M1 for 1 hour duration
Dimensions: 13W: Ø 96mm x Depth 145mm 18W: Ø 96mm x Depth 160mm
Cut out dimensions: Ø 86mm
/BR
Brass Trim
/CH
Chrome Trim
IP20
/WH/DGWhite Trim
with Drop Glass
/BR/DGBrass Trim
with Drop Glass
/CH/DGChrome Trim
With Drop Glass
38 | Luminaires
Multia
A stylish range of compact fluorescent downlights
Multia is a comprehensive range of compact fluorescent downlighters offering a variety
of options for almost every application.
Available from 18 to 26W in both single and twin lamp
versions with 32 and 42W single lamp versions Multia
is supplied with a white bezel as standard with interchangeable brass or chrome options also available.
Options include an attractive floating glass,
IP44 opal polycarbonate cover and a range
of polycarbonate emergency drop legends.
Emergency versions (mounted in a remote
box) for all lamp options are available
using BSI approved Perferm™ control
gear, specifically designed for use with low
Mercury compact fluorescent lamps and high
temperature Nickel Cadmium cells.
Mains Luminaires
Options Suffix:
/ADIntelligent
Addressable
Luminaire
/OPCIP44 Opal
Polycarbonate
Cover
Cat No.
Mode/Lamp
MU18
18W Mains Downlighter
–
2.42
/ESElectronic Start
/DGClear Outer Ring
With Frosted
Centre Disc
Floating Glass
MU218
2 x 18W Mains Downlighter
–
3.25
MU26
26W Mains Downlighter
–
2.42
/L+Drop Legend
(Replace + with
Required Legend
Panel)
MU226
2 x 26W Mains Downlighter
–
3.25
MU32
32W HF Mains Downlighter
–
2.28
MU42
42W HF Mains Downlighter
–
2.36
/HF
High Frequency
/HPFPower Factor
Corrected
/ST
/BR
Digital Self-Test
Brass Trim
/CH
Chrome Trim
Lumens
Kg
Emergency Luminaires (Incorporating Perferm™ Technology)
Cat No.
Mode/Lamp
MU18/M3 18W M3 Downlighter Lumens*
276 2.42
MU218/M3 2 x 18W M3 Downlighter 276 3.25
MU26/M3 26W M3 Downlighter 324 2.42
MU226/M3 2 x 26W M3 Downlighter 324 3.25
MU32/M3
32W M3 HF Downlighter
480
2.28
MU42/M3
42W M3 HF Downlighter
416
2.36
* Emergency Lumens
# Specify 24, 50, 110 or 230 Volts AC/DC System Voltage
* For other durations, specify the required time period e.g. /M3 becomes /M1 for 1 hour duration
Dimensions: Ø 226mm x 198mm (Minimum Ceiling Void)
Cut-Out (All Versions): Ø 208mm
For all
Legend details
See Page 57
IP20/44
Kg
Brass trim IP44
Chrome trim /DG
Classic lines
Classic product
AWAITING PHOTOGRAPHY
Karis
P27
Stylish and contemporary
luminaire ideal for
prestigious applications
Luminaires | 41
Slim profile injection moulded polycarbonate exit sign
Napoli exit signs lead the market in aesthetic design, ease of installation and maintenance.
Napoli­­­
The use of an injection moulded body has enabled us to create an exit sign superior in style
to conventional versions but remains equally as competitively priced.
Napoli’s body and base is made from flame retardant polycarbonate,
features a threshold downlight and a screen-printed legend panel.
Utilising clip fixings the Napoli is probably the quickest exit
sign to install. IP44 protection makes Napoli suitable
for use in sheltered exterior locations
Viewing distance
40 metres
Emergency Luminaires
Options Suffix:
Cat No.
Mode/Lamp
Lumens*
Kg
NA8/NM3/E
8W NM3 Emergency Exit Sign
60
2.30
NA8/M3/E
8W M3 Emergency Exit Sign
60
2.60
NA8/NM3
8W NM3 Emergency Exit Sign
120
2.30
NA8/M3
8W M3 Emergency Exit Sign
120
2.60
Slave Luminaires
Cat No.
Mode/Lamp
NA8/#/D
8W Slave Exit Sign
Lumens*
275
* Emergency Lumens
# Specify 24, 50, 110 or 230 Volts AC/DC System Voltage
* For other durations, specify the required time period e.g. /NM3 becomes /NM1 for 1 hour duration
Dimensions: 420 mm x 221mm x 58mm
For all
Legend details
See Page 57
IP44
Kg
2.30
/AD
Intelligent
Addressable
Luminaire
/ST
Digital Self Test
42 | Luminaires
Odet
Emergency floodlighting unit
Odet emergency floodlights incorporate a British Standard Approved Constant Voltage
Charger. The chargers are fitted with thermal, current and short circuit protection devices.
A low voltage disconnect circuit to prevent the batteries entering a deep discharge state in
the event of prolonged power failure, maximising battery life.
Batteries are maintenance free, sealed lead acid types with a life
expectancy of five years under normal conditions. The robust but
stylish sheet steel enclosure is finished in a light grey epoxy coating.
Odet is also available with an IP65 polycarbonate enclosure, for
external requirements. We have extended the range to include a
2x55W NM3 version.
Odet is available as a deluxe version utilising 20 Watt and
50 Watt dichroic halogen lamps (not supplied). The various
beam angles enable the client to tailor the light distribution
to their specific requirements. The heads enable the lamps
to be adjusted both horizontally and vertically giving total
flexibility. Available as standard in silver grey finish, this
stylish emergency luminaire is a popular choice for shopping
malls and most interior applications.
An optional 15 minute timer enables Odet to continue to
operate in the emergency mode after the main supply has
been reinstated allowing discharge luminaires to re-ignite
and provide a suitable light output.
ODS 20/NM1/TH
ODS 55/NM3/TH
Odet IP65
ODS Deluxe
Emergency Luminaires
Options Suffix:
/ADIntelligent
Addressable
Luminaire
(not available in
deluxe version)
/STSelf Testing
Luminaire
/IP65Weatherproof
Enclosure
/T15 Minute
Timer Delay
Unit for use with
Discharge Lamp
Schemes
Cat No.
Mode/Lamp
Lumens
Kg
ODS20/NM1/TH
NM1 2x20W/TH
2x 340
5.88
ODS20/NM3/TH
NM3 2x20W/TH
2x 340
7.00
ODS21/NM1
NM1 2x21W
2x 280
5.88
ODS21/NM3
NM3 2x21W
2x 280
7.00
ODS55/NM1/TH
NM1 2x55W TH
2x 900
7.50
ODS55/NM3/TH†
NM3 2x55W TH
2x 900
16.00
ODS/DELUXE
20/50W* Dichroic
-
7.00
*Deluxe versions give 3 hours emergency duration when used with 20W lamps and a 1 hour emergency
duration when used with 50W lamps (lamps not supplied)
* Emergency Lumens
†
This product is supplied with the batteries packed separately
Dimensions: 20, 21 and 55W (NM1) Length 315mm x Height 310mm x Depth 110mm
55W NM3 Length 440mm x Height 315mm x Depth 110mm
Dimensions IP65 Version: Length 400mm x Height 400mm x Depth 135mm
Dimensions Deluxe Version: Length 315mm x Height 200mm x Depth 75mm
IP20/65
Orbe
Compact fluorescent low bay
The Orbe lobay is a robust, high quality luminaire utilising energy saving compact
fluorescent lamps.
Luminaires | 43
Supplied as standard with a choice of 4 x 55w TC-L or 4 x 80w TC-L compact fluorescent
lamps, instant high-efficiency lighting with high-output integral 3 hour emergency lighting
using 1 lamp enables the Orbe to be specified for applications which traditional highpressure discharge lobays do not have a solution.
Orbe is suitable for surface mounting or suspension and is supplied with 4 fixing points and
3 BESA box entries as standard.
Orbe’s high quality and intelligently designed reflector system provides precise and
controlled optical performance resulting in impressive and superior spacing data (see
photometric data), ideal for high mounting applications such as sports halls, warehouses,
factories.
Independent switching circuits enable the Orbe luminaire the option of
switching off 2 lamps when in mains operation enabling potential
power savings.
Optional wire guard and polycarbonate covers offer
added protection typically for sports halls
or where damage may occur to
the luminaire.
Orbe can be used as
a Slave Luminaire
operating from
a central battery
system or static inverter,
and can be specified
with self test emergency
and intelligent addressable
emergency lighting.
Mains Luminaires
Cat No.
Options Suffix:
Mode/Lamp
Lumens
Kg
OR455
4X55W TC-L
-
11.50
OR480
4X80W TC-L
-
11.50
Emergency Luminaires
Cat No.
Mode/Lamp
Lumens*
Kg
OR455/M3
4 X 55W TC-L M3
1034
17.00
OR480/M3
4 X 80W TC-L M3
1020
17.00
Slave Luminaires
Cat No.
Mode/Lamp
OR455/#/D
55W TC-L
Lumens*
1034
11.50
OR480/#/D
80W TC-L
1020
11.50
* Emergency Lumens
# Specify 24, 50, 110 or 230 Volts AC/DC System Voltage
* For other durations, specify the required time period e.g. /M3 becomes /M1 for 1 hour duration
Dimensions: Length 900 x Width 605 x Depth 100mm
IP20
Kg
/WG
Wire Guard
/CPClear
Polycarbonate
Diffuser
/ADIntelligent
Address
Luminaire
/STSelf Testing
Luminaire
44| Luminaires
Pescara
Fluorescent exit sign for internal and external use
The Pescara range of fluorescent single and double sided exit signs are manufactured from
sheet steel and finished in a choice of either white, black, brass or chrome. Pescara’s many
features include a hinged internal steel gear tray, rear centre Besa entry, keyhole mounting
slots and an opal threshold downlight panel to illuminate the area below the sign.
The double sided version of Pescara has a central top Besa entry for ease
of fixing. The double-sided sign is no deeper than the standard Pescara
exit sign and so co-ordinates with other Pescara models.
A special U shaped gear tray allows even illumination
of both legend panels and an opal downlight panel
ensures that illumination is also directed below the
sign to the escape route and the door threshold.
The Cinema version of Pescara exit sign is fitted with a
fret-cut legend panel to reduce light emission. They are
designed for use in Theatres, Cinemas, School Halls and
Discotheques.
The IP65 rated Pescara is of robust construction making it
suitable for external and internal use. It is suitable for car parks,
sports stadiums, livestock markets and many other applications.
Viewing distance
40 metres
Non-maintained, maintained and sustained (combined) models are
BSI approved to EN60598, and all models are CE and F marked.
The legend panel can be removed from either end of the sign via
removable endcaps making Pescara suitable for close fitting into
corners where necessary.
Mains Luminaires
Cat No.
Mode/Lamp
PES8
8W 300mm Single Sided
-
2.60
PED8
8W 300mm Double Sided
-
2.60
Cat No.
Mode/Lamp
PES8/NM3 NM3 8W 300mm Single Sided
120
2.75
PES8/M3
M3 8W 300mm Single Sided
120
3.00
C3 8W 300mm Single Sided
120
3.00
PED8/NM3
NM3 8W 300mm Double Sided
120
2.75
PED8/M3
M3 8W 300mm Double Sided
120
3.00
PES8/C3
Pescara with
fret cut legend
/BK
Black Finish
/BR
Brass Finish
/CHChrome Finish
/EEconomy Version
/IP65IP65 Version
(Does not have a
Downlight Panel)
/LPSingle sided
signs available
in low profile
Lumens*
Kg
Slave Luminaires
Options Suffix:
Fret Cut Legend
Kg
Emergency Luminaires
IP65 Pescara
/C
Lumens
/VRAnti-tamper
Screws
/HPFPower Factor
Corrected
/HFHigh Frequency
Ballast
/ESElectronic Start
/ADIntelligent
Addressable
Luminaire
/STSelf Testing
Luminaire
/TSPush to Test
Switch
Cat No.
Mode/Lamp
PES8/#/D
8W Slave Exit Sign Single Sided
Lumens*
275
2.50
PED8/#/D
8W Slave Exit Sign Double Sided
275
2.50
* Emergency Lumens
# Specify 24, 50, 110 or 230 Volts AC/DC System Voltage
* For other durations, specify the required time period e.g. /NM3 becomes /NM1 for 1 hour duration
Dimensions: Length 385mm x Width 200mm x Depth 95mm (Low Profile 65mm)
Dimensions IP65 Version:
Length 445mm x Width 225mm x Depth 95mm
For all
Legend details
See Page 57
IP20/65
KM31508
Kg
Luminaires | 45
Pescara-G
Large exit sign with a 90 metre
viewing distance
To compliment our Pescara range, we have
introduced a large exit sign Pescara-G
for applications where greater viewing
distances are required.
The Pescara-G is available in single and
double sided versions and incorporate many
of the features of the Pescara range.
The ’U’ channel geartray ensures even
illumination in both single and double sided
versions and the double downlight panel
illuminates directly below the sign to the
escape route and door threshold.
Available in white as standard and nonmaintained and maintained emergency
modes, the Pescara-G is ideal for
supermarkets, car parks and warehouses.
Viewing distance
90 metres
Emergency Exit Signs
Cat No.
Mode/Lamp
Lumens
Kg
PES18/NM3
18W T8 Single Sided NM3
320
9.30
PES18/M3
18W T8 Single Sided M3
320
9.40
PED18/NM3
18W T8 Double Sided NM3
320
9.30
PED18/M3
18W T8 Double Sided M3
320
9.40
Emergency Luminaires
Cat No.
Mode/Lamp
Lumens*
PES18/#D
18W T8 Single Sided Slave 320
9.30
PED18/#D
18W T8 Double Sided Slave 320
9.30
* Emergency Lumens
# Specify 24, 50, 110 or 230 Volts AC/DC System Voltage
* For other durations, specify the required time period e.g. /NM3 becomes /NM1 for 1 hour duration
Dimensions: Length 620mm x Width 455mm x Depth 155mm
For all
Legend details
See Page 57
IP20
Kg
Options Suffix:
/ADIntelligent
Addressable
Luminaire
/ES
Electronic Start
/HFHigh Frequency
/HPFPower Factor
Correction
/ST
Digital Self-Test
46 | Luminaires
Petina
Ultra-slim LED single and double-sided exit sign
At only 30mm the single sided version of Petina is one of the slimmest emergency
exit signs available on the market.
The Petina’s new clean square profile allows it to be considered as on of the most stylish
emergency luminaires available and with new wire-suspension kits and end-mounting
black brackets now available double-sided Petina can also be confidently considered
for almost any internal application as wall or ceiling mounted.
Viewing distance
35 metres
Beautifully designed, this elegantly styled LED emergency luminaire utilises
advanced optical design, which ensures its Light Conducting Legend receives
an even spread of illumination from its LEDs with a life of approximately
50,000 hours.
Suitable for non-maintained and maintained modes, this 3 hour
emergency luminaire is available in white, black, brass or chrome
and can now also be supplied as a double-sided version which
at 45mm is probably one of the slimmest double sided exit signs
ever designed.
This new edition to the range has the facility for right angled mounting and
wire suspension enabling the Petina to be confidently specified for most applications.
Petina double-sided
in Silver-Grey
Emergency single-sided Luminaires
White
Silver-Grey
Brass
Chrome
Black
Cat No.
Mode/Lamp
Kg
PE/M3/WH
NM/M3 White LED Sign Single Sided
2.00
PE/M3/BK
NM/M3 Black LED Sign Single Sided
2.00
PE/M3/SG
NM/M3 Silver Grey LED Sign Single Sided
2.00
PE/M3/BR
NM/M3 Brass LED Sign Single Sided
2.00
PE/M3/CH
NM/M3 Chrome LED Sign Single Sided
2.00
Emergency double-sided Luminaires
Cat No.
Mode/Lamp
Kg
Options Suffix:
PD/M3/WH
NM/M3 White LED Sign Double Sided
2.60
/WSWire
Suspension Kit
PD/M3/BK
NM/M3 Black LED Sign Double Sided
2.60
/RBRight angled
Mounting
Bracket
PD/M3/SG
NM/M3 Silver Grey LED Sign Double Sided
2.60
PD/M3/BR
NM/M3 Brass LED Sign Double Sided
2.60
PD/M3/CH
NM/M3 Chrome LED Sign Double Sided
2.60
Dimensions:
Single - Length 360mm x Width 235mm x Depth 30mm
Legend - 280mm x 155mm
Double - 377mm x 255mm x 45mm
* For other durations, specify the required time period e.g. /NM3 becomes /NM1 for 1 hour duration
For all
Legend details
See Page 57
IP20
Pico
Low profile single sided emergency exit box
The Pico range of low-profile single sided fluorescent
exit signs are manufactured from sheet steel and
are available in high quality white, brass or chrome
options.
This competitively priced high quality exit
luminaire is available as a mains option, with
3 hour non-maintained and maintained
emergency versions.
Luminaires | 47
Viewing distance
40 metres
Pico luminaires are only 65mm deep
and are supplied as standard with
a rear center BESA entry, keyhole
mounting slots and an opal
threshold downlight panel to
illuminate the area below
the sign.
Pico luminaires are
supplied with removable
end-caps, which enable the
legend to be removed via either
end of the luminaire allowing the Pico
to be suitable for cornered installations.
(For Double Sided Versions See Pescara on Page 44)
Mains Luminaires
Cat No.
Mode/Lamp
Lumens
PIC8
8W 300mm Single Sided
Kg
2.50
Emergency Luminaires
Cat No.
Mode/Lamp
PIC8/NM3
NM3 8W 300mm Single Sided
Lumens*
Kg
80E
2.60
120S
PIC8/M3
80E
M3 8w 300mm Single Sided
2.90
120S
Slave Luminaires
Cat No.
Mode/Lamp
PIC8/#/D
8W Slave Exit Sign Single Sided
Lumens*
275
* Emergency Lumens
# Specify 24, 50, 110 or 230 Volts AC/DC System Voltage
* For other durations, specify the required time period e.g. /NM3 becomes /NM1 for 1 hour duration
Dimensions: Length 385mm x Width 200mm x Depth 65mm
For all
Legend details
See Page 57
IP20
Kg
2.50
Options Suffix:
/EEconomy
Version
/HFHigh Frequency
Ballast
/SStandard
Version
/ESElectronic Start
/CHChrome Finish
/BR
Brass Finish
/HPFPower Factor
Corrected
/ADIntelligent
Addressable
Luminaire
Luminaires | 49
Robust 4 sided exit sign
Quarto is an impressively robust 4 sided white emergency exit sign manufactured from high
quality sheet steel which is suitable for either surface mounting or for large open tall
buildings such as railway stations and airports Quatro can be suspended
using rod suspension kits available (750mm and 1200mm
white rod lengths as standard).
Quarto
Optional blanking plates
are available for Quarto for
situations when less than four
legends are required
Its energy saving compact
fluorescent lamp ensures each
of the legends and downlight
panel receives an impressive
even illumination creating
a reliable and highly visible
exit sign.
Available as a mains or 3
hour non-maintained and
maintained emergency
luminaires, Quarto is also
available as a slave unit
operating from a Central
battery or Static Inverter
System.
Self Test and Intelligent
Addressable Emergency versions are
also available as options for this flexible
exit sign enabling it to be confidently specified
for the largest of projects.
Viewing distance
40 metres
Mains Luminaires
Options Suffix:
Cat No.
Mode/Lamp
Lumens
QU16
Mains 16W
-
Kg
6.40
Emergency Luminaires
Mode/Lamp
QU16/NM3
16W NM3
200
7.00
QU16/M3
16W M3
200
7.30
Lumens*
Kg
Slave Luminaires
Mode/Lamp
QU16/#/D
Slave 16W
Lumens*
400
* Emergency Lumens
# Specify 24, 50, 110 or 230 Volts AC/DC System Voltage
* For other durations, specify the required time period e.g. /NM3 becomes /NM1 for 1 hour duration
Dimensions: Length 420mm x Depth 420mm x Width 230mm
For all
Legend details
See Page 57
/HFHigh Frequency
Ballast
/ESElectronic Start
Cat No.
Cat No.
/HPFPower Factor
Corrected
IP20
Kg
6.40
/ADIntelligent
Addressable
Luminaire
/STDigital Self Test
/RS1Rod Suspension
Kit (600mm)
/RS2Rod Suspension
Kit (1.2m)
/BPWhite Blanking
Plate
50 | Luminaires
Retz
A decorative curved exit sign
A superbly styled low profile exit sign suitable for almost any prestigious application.
The elegant design of Retz utilises an attractive curved fascia which is supplied in white finish
as standard with silver grey, brass and chrome finishes providing a comprehensive range of
options.
An opal downlight panel is incorporated into Retz to illuminate the escape route and door
threshold.
Viewing distance
40 metres
Mains Luminaires
Brass
Chrome
Silver Grey
Cat No.
Mode/Lamp
RZ8
8W Mains
Lumens
-
Kg
1.60
Emergency Luminaires
Cat No.
Mode/Lamp
RZ8/NM3
8W NM3 Emergency
Lumens*
120
2.00
Kg
RZ8/M3
8W M3 Emergency
120
2.20
Slave Luminaires
Options Suffix:
/BR
Brass Finish
/CHChrome Finish
/SGSilver Grey Finish
/ES
Electronic Start
/HFHigh Frequency
Ballast
/ADIntelligent
Addressable
Luminaire
/HPFPower Factor
Correction
/ST
Digital Self-Test
Cat No.
Mode/Lamp
RZ8/#D
8W Slave Emergency
Lumens*
275
* Emergency Lumens
# Specify 24, 50, 110 or 230 Volts AC/DC System Voltage
* For other durations, specify the required time period e.g. /NM3 becomes /NM1 for 1 hour duration
Dimensions: Length 440mm x Height 220mm x Depth 65mm
For all
Legend details
See Page 57
IP20
Kg
2.00
Rota
Led exit signs suitable for wall or ceiling mounting
The Rota is a superbly designed range of LED Exit Signs, which
combines long-life LED Technology with High Quality engineering.
Luminaires | 51
The versatile design of the Rota allows wall or ceiling mounting
with a range of high quality finishes including white,
brass, chrome, black or silver-grey (RAL-9006)
Suitable for non-maintained and maintained modes
this 3 hour exit sign also includes a new recessed
version suitable for almost any prestigious project.
Both the surface and recessed versions utilise the
unique high quality plasi-glas legends with flame
polished edges which ensure that the light distribution
is effectively and evenly diffused across the legend
resulting in a high performance, impressive and
reliable emergency luminaire.
Can be used with single and double-sided legends
(please specify when ordering)
Rota recessed
finished
in white
Rota finished in chrome
Viewing distance
32 metres
Emergency Luminaires
Cat No.
Mode/Lamp
RO/LED/M3/WH
M3 White LED Exit Sign
Lumens
-
2.00
RO/LED/M3/BR
M3 Brass LED Exit Sign
-
2.00
RO/LED/M3/CH
M3 Chrome LED Exit Sign
-
2.00
RO/LED/M3/BK
M3 Black LED Exit Sign
-
2.00
RO/LED/M3/SG
M3 Silver Grey LED Exit Sign
-
2.00
* For other durations, specify the required time period e.g. /NM3 becomes /NM1 for 1 hour duration
Dimensions: Length 310mm x Height 240mm x Depth 40mm
Cut out dimensions: Length 310mm x Height 60mm x Depth 35mm
Kg
White
Brass
Silver-Grey
Black
Options Suffix:
/RRecessed Version
For all
Legend details
See Page 57
IP20
Chrome
Romney.
The ultimate solution.
Right angle mount
Wall mount
Wire suspension
Luminaires | 53
Romney
Flexible LED exit sign
Romney is an affordable, robust flexible exit sign featuring LED’s with a 50,000-hour
lamp-life. This economically designed 3 hour emergency luminaire has been specifically
engineered to ensure Romney benefits from the latest LED technology.
Romney is available in white and has the choice of two legend sizes (135mm as standard
and an optional 180mm version) with optional wire mounting suspension kits for high-ceiling
applications.
Additional end or wall mounting kits can be specified to enable Romney to be used as a
single or double-sided exit sign emphasising the wide range of variations.
Viewing distance 20 metres
(135mm legend)
Viewing distance 30 metres
(180mm legend)
Romney with optional
wire suspension kit
Emergency Luminaires
Cat No.
Mode/Lamp
ROM/LED/M3
M3 LED Exit Sign
Lumens*
-
* For other durations, specify the required time period e.g. /M3 becomes /M1 for 1 hour duration
Dimensions: Length 300mm x Width 195mm x Depth 40mm (135mm Legend)
Length 300mm x Width 240mm x Depth 40mm (180mm Legend)
For all
Legend details
See Page 57
IP20
Kg
1.60
Options Suffix:
/RABRight Angled
Mounting
Bracket
/WMBWall Mounting
Bracket
/WSWire
Suspension Kit
Savona
Edge-lit exit signs in single and double-sided versions
Savona is an edge-lit exit sign available in a range of high quality finishes. The smooth
lines of the new Savona create a product of contemporary design which lends itself for
use in many prestigious installations.
Models featuring both fluorescent and high output white light emitting diodes (LED)
are available. LED’s have the advantage of a long life combined with a very low
maintenance requirement. Whichever light source you choose, Savona offers an
elegant exit sign with superb performance.
Savona with
chrome finish
The flame retardant Plasi-Glas legend panel suspends below the lamp and its
light conducting properties ensure even and clear illumination of the panel.
The Savona body is supplied separately from the legend which is assembled
with just two screws. This makes ordering single or double-sided signs very
simple. If you require a single sided sign simply add the relevant legend
number to the product code e.g.. SAV8/NM3/L19. If you require a double-sided
sign the product code would be SAV8/NM3/L19/D.
There are 2 Legend depths available - 270mm (standard) or 135mm for areas
where height is restricted.
Savona recessed
with brass finish
Viewing distances 27 metres
(135mm legend)
Viewing distances 40 metres
(270mm legend)
Options Suffix:
/R
Recessed Trim
/CH
Chrome Finish
/WH
White Finish
/BR
Brass Finish
/ADIntelligent
Addressable
Luminaire
/STDigital Self Test
Mains Luminaires
Cat No.
Mode/Lamp
Lumens
SAV8
8W 300mm
-
Kg
2.90
Emergency Luminaires
Cat No.
Mode/Lamp
Lumens*
Kg
SAV8/NM3
NM3 8W 300mm
120
3.00
SAV8/M3
M3 8W 300mm
120
3.20
Emergency LED Luminaires
Cat No.
Mode/Lamp
SAV/LED/M3
M3 LED
Lumens*
-
Kg
3.20
Slave Luminaires
Cat No.
Mode/Lamp
SAV8/#/D
8W 300mm Slave Sign
Lumens*
275
* Emergency Lumens
# Specify 24, 50, 110 or 230 Volts AC/DC System Voltage
* For other durations, specify the required time period e.g. /NM3 becomes /NM1 for 1 hour duration
Dimensions: Length 445mm x Width 90mm x Depth 340mm
Recess Version Dimensions: Length 502mm x Width 152mm
Recess Version Dimensions Cut Out: Length 428mm x Width 135mm x Depth 85mm
For all
Legend details
See Page 57
IP20
Kg
2.90
Luminaires | 55
Savona
Petite
Compact suspended exit sign
Savona Petite is a compact suspended
emergency exit sign, which utilises the
latest LED technology to ensure a long
lamp-life of up to 50,000 hours.
Extensive thermal engineering has enabled
the Savona Petite to be suitable as
a 3 hour non-maintained/maintained
emergency luminaire.
Available in white as standard with optional
brass or chrome high quality finishes, this
exceptionally luxurious suspended exit sign
can be confidently specified as a single or
double-sided emergency luminaire with
additional options including an endmounting wall bracket, creating a reliable
universal LED exit sign.
Viewing distances
32 metres
Emergency Luminaires
Cat No.
Mode/Lamp
SP/LED/M3
M3 LED Exit Sign
Lumens*
-
* For other durations, specify the required time period e.g. /M3 becomes /M1 for 1 hour duration
Dimensions: Length 340mm x Depth 275mm x Width 85mm including legend
Ceiling Bar: Length 325mm x Depth 20mm x Width 63mm
For all
Legend details
See Page 57
IP20
Kg
2.70
Brass
Chrome
Options Suffix:
/CH
Chrome Finish
/BR
Brass Finish
56 | Luminaires
Tiel
IP65 single or double sided exit sign
Tiel is a robust IP65 ceiling mounted single or double sided white polycarbonate exit sign.
Suitable for surface or semi-recessed installations.
Its IP65 rating and optional tamper resistant screws, make the Tiel a unique single or double
sided sign for all public areas.
Tiel is supplied complete with two self-adhesive legends as standard (please
specify) so that the installer can make up either a single sided or
double sided sign.
Tiel recessed
Viewing distances
28 metres
Options Suffix:
/E
Economy Output
/S
/H
Standard Output
High Output
/TI/WHWhite Finished
Semi-recess Trim
/TI/BRBrass Finished
Semi-recess Trim
/TI/CHChrome Finished
Semi-recess Trim
/VRAnti-tamper
Screws
/HPFPower Factor
Corrected
Mains Luminaires
/HFHigh Frequency
Ballast
Cat No.
Mode/Lamp
TI8
1x8W 300mm
-
0.90
/ADIntelligent
Addressable
Luminaire
(Non-Maintained
Only)
TI2x8
2x8W 300mm
-
0.90
TI11
11W TC-S
-
0.90
/STDigital Self Test
(Non-Maintained
Only)
Cat No.
Mode/Lamp
TI8/NM3
NM3 8W 300mm
/TSPush to
Test Switch
120S
180H
/ES
Electronic Start
Lumens
Kg
Emergency Luminaires
TI8/M3
Lumens*
M3 8W 300mm
80E
80E
120S
180H
TI2X8/NM3
NM3 2X8W 300mm
150S
Kg
1.20
1.45
1.70
250H
Slave Luminaires
Cat No.
Mode/Lamp
Lumens*
TI8/#/D
8W Slave Luminaire
275
* Emergency Lumens
# Specify 24, 50, 110 or 230 Volts AC/DC System Voltage
* For other durations, specify the required time period e.g. /NM3 becomes /NM1 for 1 hour duration
Dimensions: Length 350mm x Width 108mm x Depth 204mm
Cut out dimensions: Length 330mm x Width 90mm
For all
Legend details
See Page 57
IP65
Kg
0.85
Luminaires | 57
Savona
P54
Edge-lit exit sign
in single and
double-sided versions
Legends
L16
L17
L18
L19
L20
L22
L21
L23
58 | Photometric data
Mounting
CAT Number
height (m)
Transverse to wall Transverse spacing
Axial to wall
0.2
0.5
1.0
0.2
0.5
1.0
0.2
0.5
1.0
CAD8/NM3/E (M3) 2.5
4.17
2.45
1.63
10.92
7.94
5.29
3.28
2.01
1.34
AR8/NM3/E (M3)
4.0
4.18
N/A
N/A
12.01
5.60
3.73
3.48
N/A
N/A
ED8/NM3/E (M3)
6.0
3.34
N/A
N/A
11.73
N/A
N/A
2.69
N/A
N/A
CAD8/NM3/S (M3) 2.5
4.80
3.20
2.10
12.40
8.60
6.30
3.70
2.60
1.80
AR8/NM3/S (M3)
4.0
5.00
2.80
N/A
13.70
8.70
5.40
4.10
2.40
N/A
6.0
4.50
N/A
N/A
14.00
7.10
N/A
3.80
N/A
N/A
CAD8/NM3 (M3)/H 2.5
5.90
4.10
3.00
15.20
10.70
8.10
4.40
3.20
2.40
AR8/NM3 (M3)/H
4.0
6.50
4.10
1.30
17.00
11.50
8.00
5.10
3.40
2.00
6.0
6.50
3.00
N/A
18.20
11.10
7.30
5.40
2.50
N/A
DAL8/NM3
2.5
5.30
3.80
2.90
13.30
9.70
7.50
5.00
3.60
2.80
DAL8/M3
4.0
6.00
3.90
1.30
15.30
10.80
7.80
5.70
3.80
1.50
6.0
6.20
N/A
N/A
16.80
10.50
N/A
6.00
N/A
N/A
BE8/NM3+BA/NM3 2.5
4.00
2.70
1.70
10.10
7.40
5.30
3.50
2.40
1.50
BE8/M3+BA/M3
4.0
4.20
1.90
N/A
11.40
7.30
4.00
3.90
1.60
N/A
BE8/C3+BA/C3
6.0
3.40
N/A
N/A
11.50
4.60
N/A
3.10
N/A
N/A
CAL8/NM3/M3
2.5
3.90
3.10
2.70
8.90
7.10
7.20
2.90
2.70
1.40
GN8/NM3/M3
4.0
4.90
3.80
1.40
12.20
10.10
4.90
3.20
2.90
0.50
CHE8/NM3/M3
6.0
4.70
2.00
0.50
11.80
8.80
2.90
3.00
1.50
N/A
MZ28/M3
2.5
5.40
4.00
3.10
13.40
10.00
7.80
5.40
4.00
3.10
EC28/M3
4.0
6.30
4.40
3.00
15.90
11.50
8.60
6.30
4.40
3.00
6.0
6.70
4.40
2.50
17.00
12.10
8.60
6.70
4.40
2.50
EC38/M3
2.5
4.0
6.0
5.60
6.60
7.60
4.20
4.50
5.20
3.20
3.10
3.40
13.80
16.50
19.10
10.40
11.90
13.80
8.20
8.90
10.20
5.60
6.60
7.60
4.20
4.50
5.20
3.20
3.10
3.40
MZ16/M3 2.5
LA16/M3
4.0
LV16/M3 + HT16/M3 6.0
4.30
4.60
4.40
3.00
2.70
N/A
2.20
N/A
N/A
10.60
12.30
13.00
7.80
8.30
7.00
5.90
5.30
N/A
4.30
4.70
4.30
3.00
2.70
N/A
2.20
N/A
N/A
HT28/M3 + LN28/M32.5
LV28/M3 + KN28/M3 4.0
IDR28/M3
6.0
4.40
4.80
4.40
3.20
2.80
N/A
2.30
N/A
N/A
11.10
12.80
13.60
8.10
8.60
7.40
6.10
5.50
N/A
4.50
4.80
4.40
3.10
2.80
N/A
2.10
N/A
N/A
LA38/M3
IDR38/M3
2.5
4.0
6.0
5.60
6.60
6.90
4.20
4.50
4.50
3.00
3.30
N/A
13.80
16.50
17.70
10.40
11.90
12.50
7.50
8.40
9.00
5.60
6.60
6.90
4.20
4.50
4.50
3.00
3.30
N/A
DAR/LED/M3
2.5
4.0
6.0
3.20
3.50
3.60
2.20
2.80
2.70
1.80
2.10
2.40
8.20
8.50
9.90
5.80
6.80
6.10
4.90
5.20
5.40
3.20
3.50
3.60
2.20
2.80
2.70
1.80
2.10
2.40
ED/LED/M3
2.5
4.0
6.0
3.70
4.70
5.60
2.90
3.10
N/A
2.50
N/A
N/A
10.00
10.90
13.50
7.10
7.70
5.80
5.80
5.10
N/A
3.10
3.20
3.00
2.20
2.40
N/A
1.40
N/A
N/A
GN/LED/M3
CHE/LED/M3
2.5
4.0
6.0
3.90
4.70
4.50
2.80
2.10
N/A
1.80
0.50
N/A
8.90
11.30
11.10
5.70
7.70
N/A
6.10
3.00
N/A
2.70
2.80
2.00
2.40
1.60
N/A
1.00
N/A
N/A
MULTIA18W
2.5
4.0
6.0
4.60
5.60
6.30
3.70
4.20
4.30
3.00
3.20
2.20
9.40
12.40
14.70
7.70
9.50
10.60
7.00
7.40
7.60
4.60
5.60
6.30
3.70
4.20
4.30
3.00
3.20
2.20
MULTIA26W
2.5
4.0
6.0
5.00
6.00
7.20
4.10
4.70
5.70
3.40
3.80::
3.50
10.00
13.00
16.80
6.90
9.80
10.30
7.20
8.90
7.30
5.00
6.00
7.20
4.10
4.70
5.70
3.40
3.80
3.50
MULTIA32W
2.5
4.0
6.0
3.70
5.40
7.40
2.40
3.30
3.90
3.20
3.80
3.60
8.20
11.80
16.30
7.30
10.40
13.80
7.10
9.60
11.20
3.70
5.40
7.40
2.40
3.30
3.90
3.20
3.80
3.60
MULTIA42W
2.5
4.0
6.0
4.20
6.10
9.10
2.90
3.90
5.30
4.10
4.90
5.90
9.10
12.90
17.90
7.90
11.40
16.10
7.80
10.70
14.30
4.20
6.10
9.10
2.90
3.90
5.30
4.10
4.90
5.90
OR455/M3
OR480/M3
4.0
6.0
8.0
9.30
10.80
11.80
7.00
7.90
8.20
5.50
5.80
5.40
22.30
26.60
29.70
17.20
19.90
21.70
13.80
15.60
16.20
6.50
8.60
10.30
5.60
7.20
8.30
4.90
6.00
6.60
DY/LED/OA
2.5
3.0
4.0
4.10
3.70
2.10
1.40
-
-
0.60
-
-
11.90
12.00
10.80
6.80
6.00
1.40
4.20
-
-
4.10
3.70
2.10
1.40
-
-
0.60
-
-
DY/LED/CR
2.5
3.0
4.0
4.10
4.30
0.70
0.50
-
-
1.30
-
-
16.00
14.70
11.60
7.30
5.10
-
5.10
-
-
3.40
2.50
0.80
0.80
-
-
0.60
-
-
ELL/LED/OA
2.5
3.0
3.5
4.10
4.00
3.70
2.20
1.30
-
-
-
-
10.40
11.00
11.30
7.20
6.80
5.90
4.10
2.40
-
4.10
4.00
3.70
2.20
1.30
-
-
-
-
ELL/LED/CR
2.5
3.0
3.5
4.80
4.90
4.90
2.90
2.50
-
0.90
-
-
11.70
12.70
13.30
8.60
8.70
8.20
5.70
4.60
2.50
3.80
3.80
3.70
2.30
1.90
1.30
0.90
-
-
Photometric data | 59
Axial spacing
0.2
0.5
1.0
8.23
6.62
4.41
9.57
4.56
3.04
9.77
N/A
N/A
Transverse to axial spacing
0.2
0.5
1.0
9.59
7.28
4.85
10.73
5.07
3.38
10.76
N/A
N/A
8.90
10.60
11.50
6.70
7.20
5.80
5.10
4.60
N/A
8.50
9.10
8.30
5.80
5.20
N/A
3.90
N/A
N/A
Notes: These tables are based on
the following factors:
10.30
12.70
14.50
8.00
9.30
9.30
6.30
6.70
4.20
9.70
10.80
10.70
6.90
6.80
3.90
4.90
3.50
N/A
Light output ratios measured to BS5225 and
lamp lumen outputs are from GE Lighting Warm
white lamps.
13.00
14.90
16.50
9.40
10.60
10.40
7.50
7.60
N/A
12.60
14.40
16.00
9.00
10.40
10.50
7.30
7.50
N/A
Requirements from BS5266/EN1838
8.80
10.10
10.40
6.50
6.50
4.00
4.90
3.30
N/A
9.40
10.80
11.00
7.00
6.90
4.30
5.00
3.70
N/A
7.40
8.10
7.90
6.40
6.90
6.70
4.50
3.10
2.00
8.10
10.70
10.80
6.80
7.30
6.10
5.70
4.30
N/A
13.40
15.90
17.00
10.00
11.50
12.10
7.80
8.60
8.60
13.40
15.90
17.00
10.00
11.50
12.10
7.80
8.60
8.60
13.80
16.50
19.10
10.40
11.90
13.80
8.20
8.90
10.20
13.80
16.50
19.10
10.40
11.90
13.80
8.20
8.90
10.20
10.70
12.30
13.00
7.80
8.90
7.00
5.90
5.30
N/A
10.70
12.40
13.00
7.80
8.40
7.00
5.90
5.30
N/A
11.10
12.70
13.60
8.10
8.60
7.40
6.10
5.50
N/A
11.00
12.70
13.60
8.00
8.60
7.40
6.00
5.50
N/A
13.80
16.50
17.70
10.40
11.90
12.50
7.50
8.40
9.00
13.80
16.50
17.70
10.40
11.90
12.50
7.50
8.40
9.00
8.20
8.50
9.90
5.80
6.80
6.10
4.90
5.20
5.40
8.20
8.50
9.90
5.80
6.80
6.10
4.90
5.20
5.40
9.00
9.80
11.00
6.20
6.60
4.00
4.80
3.50
N/A
8.10
8.80
8.60
6.90
7.20
5.30
3.90
3.40
N/A
6.90
7.80
6.80
5.50
6.20
N/A
3.80
2.00
N/A
8.10
10.10
10.30
5.60
N/A
N/A
5.00
N/A
N/A
9.40
12.40
14.70
7.70
9.50
10.60
7.00
7.40
7.60
9.40
12.40
14.70
7.70
9.50
10.60
7.00
7.40
7.60
10.00
13.00
16.80
6.90
9.80
10.30
7.20
8.90
7.30
10.00
13.00
16.80
6.90
9.80
10.30
7.20
8.90
7.30
8.20
11.80
16.30
7.30
10.40
13.80
7.10
9.60
11.20
8.20
11.80
16.30
7.30
10.40
13.80
7.10
9.60
11.20
9.10
12.90
17.90
7.90
11.40
16.10
7.80
10.70
14.30
9.10
12.90
17.90
7.90
11.40
16.10
7.80
10.70
14.30
13.80
18.90
23.10
12.40
16.40
19.40
11.10
14.20
16.50
17.40
22.00
25.80
14.30
17.80
20.30
12.20
14.70
16.10
11.90
12.00
10.80
6.80
6.00
1.40
4.20
-
-
11.30
12.00
10.80
6.80
6.00
-
4.20
-
8.20
8.80
7.50
4.80
3.10
-
2.60
-
-
12.10
9.80
8.00
5.10
3.20
-
3.2
-
10.40
11.00
11.30
7.20
6.80
5.90
4.10
2.40
-
10.40
11.00
11.30
7.20
6.80
5.90
4.10
2.40
-
9.30
10.00
10.40
6.60
6.60
6.30
4.40
3.70
2.40
10.50
11.30
11.80
7.60
7.60
7.20
5.10
3.80
2.30
Permanently unobstructed
escape routes:
Require minimum 0.2 lux along the centre line
of the escape route, where there is a possibility
of an obstruction occuring along the route 1 lux
minimum is required.
Undefined, Open areas:
The minimum level of illumination required
throughout the area is 0.5 lux excluding a half
metre border around the edge of the room
which can be at a lower level.
TWINSPOT SPACING DATA
(1 LUX AVERAGE)
Mounting
Height
Spacing
to Wall
Between
Units
2 x 21 Watt Tungsten Versions
2.5 metres
4 metres
6 metres
8 metres
3m
4m
3m
3m
9m
11m
12m
10m
2 x 20 Watt Tungsten Halogen Versions
2.5 metres
4 metres
6 metres
8 metres
5m
6m
5m
4m
15m
16m
16m
15m
2 x 55 Watt Tungsten Halogen Versions
8 metres
10 metres
8m
8m
20m
20m
These tables are to be used as a guide only.
Please refer to www.relux.biz for accurate
photometric planning
60 | Design guide
Design Guide
NON -MAINTAINED
MAINTAINED
The lighting only operates
when the normal mains
supply fails (emergency
lighting only).
FINAL EXIT
To provide illumination
of escape routes.
FINAL EXITS
Install externally within 2 metres
horizontal distance of any final exits.
Please note that sufficient light will be
needed to muster a roll call.
LIFTS
To provide emergency illuminations
in all lifts.
The lighting operates normally
and continues to operate when
the normal mains supply fails
(mains lighting and emergency
lighting).
JUNCTIONS
CORRIDORS
STAIRWAYS
Install within 2 metres of escape
route junctions.
Install within 2 metres horizontal
distance of a change of direction
in an escape route.
Install within 2 metres horizontal
distance of change in floor level or
stairs (each tread to receive direct
light).
ALARM AREAS
ESCALATORS
TOILETS
Should not be used as an escape
route, but requires the same
illumination to protect users on it
when the supply fails.
Install in all toilets exceeding 8m2
area or where natural light is not
present.
OPEN AREAS
HAZARDOUS AREAS
Fire alarms, first aid points and
fire-fighting equipment, install
within 2 metres horizontal distance.
CONTROL ROOMS
Motor generator, control and
plant rooms for essential and
safety services.
Open rooms either with a particular
hazard, an escape route passing
through or larger than 60m2 .
Areas of high risk should be
illuminated to 10% of normal
lighting or 15 lux, whichever
is greater.
Lighting requirements
When luminaires have been sited to cover the locations above, additional luminaires
may be required to ensure minimum lighting levels are achieved. We provide spacing
tables for this purpose. Spacing tables advise how far to locate the first luminaire,
then how far apart other luminaires should be located for a given mounting height.
Installation to the spacings will ensure the lighting levels will be achieved.
Escape route corridors etc: 1 lux minimum on the centre line of the escape route.
Open Areas: 0.5 lux minimum in the central core to within 0.5m of the walls.
Exit signs – Signs should apply to the European Signs Directive and be either
back illuminated or have an emergency luminaire within 2m of horizontal height.
Signs should be of the same format throughout the building.
Relux
Orbik is a fully registered member of Relux
Powered by Relux the full comprehensive range of ORBIK products is available free of charge
to be downloaded via our website www.orbik.co.uk or at www.relux.biz in a UK format.
Orbik are able to offer the most technical advanced and user friendly lighting design
software available in todays market. Our built in database has a full technical library
on all of our products, including photometric data and product data sheets.
A complete lighting design solution which is fast and simple to create, the Relux
express mode will guide you through the lighting calculation on an intuitive,
step by step basis.
Once the design is complete the results can be complied into an impressive
structured report, table results and 3D computer generated visualisations.
Designs can be competed to meet the requirements of the latest
European and British standards, using dedicated emergency
luminaires, converted mains lighting luminaires or a combination
of mains and emergency luminaires for a complete
design solution.
Design guide | 61
Power is nothing
without control
Self contained emergency gear (conversion kits) | 63
Revolutionary technology for low Mercury and Amalgam lamps
In recent years, as a direct result of environmental concerns, the Mercury content of
fluorescent lamps has been steadily reduced to lessen the impact on the environment when
the lamps reach their end of life and require recycling or safe disposal. The RoHS directive
imposes strict limits on the amount of potentially hazardous substances that can be used in
the manufacture of products and Mercury is one of the six hazardous substances identified
in this directive. Lamp manufacturers are required to comply with these limits and have
initiatives to remove all Mercury from fluorescent lamps in the near future.
Since its introduction five years ago, Orbik’s Perferm™ technology range
of emergency modules, which incorporate enhanced striking
technology and permanent heating of the lamp cathodes
in emergency mode, have gained favour with many
of the major emergency lighting companies
within Europe and the Middle and Far
Eastern countries. Perferm™ modules
operate with most standard Mercury, reduced
Mercury and Amalgam based fluorescent
lamp types and thus offer customers who supply
emergency lighting luminaires a safeguard against
potential compatibility problems when lamps are replaced
with lower Mercury level lamps, at a later date.
This is becoming more of an issue because as the Mercury levels
in fluorescent lamps continue to fall, conventional modules without
Perferm™ technology are already failing to provide correct emergency
operation, which at best dramatically reduces the lamp life and can lead to
poor colour rendition or ’pink limbs’ on some compact fluorescent lamps and in
some extreme instances, no light from the lamp in emergency conditions.
We now offer two alternative versions of the Perferm™ with the PH4000 and PL4000
series offering all the advantages of Perferm™ without the additional mains
ballast delay control relay found in the PLR5000 and PHR5000 Perferm™
Plus modules. These have been designed specifically for use with
multi-lamp or dimmable electronic ballasts where ‘lock out’
can be a problem (supply present but the ballast has shut
down because the emergency lamp has been temporarily
disconnected from the ballast during testing). This is the case
where a keyswitch is used to fail the permanent supply (to test
the emergency lighting), whilst the switched supply is still present
at the electronic ballast. The additional relay introduces a small time
delay before the power is reconnected to the electronic ballast, allowing it
time to reset correctly after the emergency test.
KM21518
M
64 | Self contained emergency gear (conversion kits)
Technical
Specification
Ballast lumen factors for control gear incorporating Perferm™ technology
(suitable for all lamps including low Mercury & Amalgam lamps)
T8/T12
Module Number
T5
Battery
Cells
18W 20W 30W 36W 40W 58W 70W100W 8W 14W 21W 24W 28W 35W 39W 49W 54W 80W
PH4003P3 PL4003P3 PLR5003P3
3 x 4Ah
12
12
9
9
9
24
PH4005P3 PL4005P3 PLR5005P3
4 x 4Ah
11
11
10
10
10
20
MT5414P3 4 x 4Ah
32
PH4007P3 PL4007P3 PLR5007P3
4 x 4Ah
10
PH4403P3 PL4403P3 PLR5403P3
4 x 4Ah
PH4418P3 PL4418P3 PLR5418P3
4 x 4Ah
25
25
PH4009P3 PL4009P3 PLR5009P3
5 x 4Ah
13
13
PH4506P3 PL4506P3 PLR5506P3
5 x 4Ah
PH4011P3 PL4011P3 PLR5011P3
5 x 4Ah
10
42
32
MT5528P3 5 x 4Ah
PHR5607P3
6 x 4Ah
18
18
28
25
26
7
28
25
26
18
PHR5608P3
6 x 4Ah
11
10
PHR5809P3
8 x 4Ah
15
14
9
27
24
20
17
MT5854P3 8 x 4Ah
27
24
20
17
PHR5108P3
10 x 4Ah
17
10
Ballast lumen factors for emergency control gear
(not suitable for low Mercury and Amalgam lamps)
Module Number
T5/T8
Battery
Cells
8W 18W 20W 30W 36W 40W 58W 70W
M2019/3(NM) MS2020/3(M3)
2 x 4Ah
26
M2001P3(NM) MS2001P3(M3)
3 x 4Ah
34
24
MS2001P3
3 x 4Ah
34
24
MS2003P3
3 x 4Ah
MS2007P3
4 x 4Ah
MS2011P3
5 x 4Ah
24
14
14
29
13
Fixing centres
Module
A
B
C
D
E
Kg
PH
154
42
35
144
138
0.33
PL
203
42
28
193
187
0.34
PLR
216
42
28
206
200
0.35
PHR
216
42
35
206
200
0.54
MT5
350
28
28
230
–
0.34
M/MS
154
42
35
144
138
0.33
14
12
10
13
10
9
10
Self contained emergency gear (conversion kits) | 65
Technical
Specification
T5 Circular
2D
TC-L
TC-S/E
TC-D/E
TC-T/E Amalgam
22W 40W 55W 16W 21W 28W 38W 55W 18W 24W 34W 36W 40W 55W 5W 7W 9W 11W 10W 13W 18W 26W 13W 18W 26W 32W 42W 57W
16
13
12
13
11
11
18
13
12
20
12
22
23
20
20
29
12
25
26
24
26
29
17
16
25
22
11
9
23
9
11
13
12
16
13
11
24
29
14
15
14
40
37
38
40
11
11
9
10
30
33
28
23
22
20
11
16
13
14
12
30
20
12
15
18
11
13
•
P erferm™ technology is an ongoing development involving the latest lamp technology and as such is subject to change as and when further
lamps/data become available.
•
e strongly recommend that modules incorporating Perferm™ technology are used in all emergency luminaires and conversions to provide the
W
ultimate future proofing against lamp evolution.
•
ost modules and PCB’s are tested and approved to BE/EN61347-2-7. They are EMC compliant to EN55015 and carry the British Standard
M
Kitemark and CE mark.
•
They incorporate over temperature and charger short circuit protection.
•
Mains supply 230V - 6% + 10% 50/60 Hz power consumption 8VA (other supply Voltages available on request).
•
Output circuitry uses a high efficiency sinusoidal inverter, with nominal operating current of 1 Amp.
•
Available as standard in 3 hour operation (other durations to order).
•
All modules have battery over discharge protection as standard (DDP) to prevent discharge below 1 Volt per cell.
•
Reverse battery polarity protected.
•
ll connections are via terminal blocks with a green light emitting diode (LED), to indicate correct charging conditions.
A
All products are supplied with LED indicators.
•
Operating temperature range module 0 to 70°C (centre side of case)
•
Printed circuit boards 0 to 90°C (coil/core of charging transformer)
•
All ballast lumen factors are shown as worst case.
•
All products listed above are for 3 hours duration.
•
All figures are based on an ambient temperature of 25°C.
KM21518
66 | Self contained emergency gear (conversion kits)
Joule range
Combined mains and emergency lighting ballasts for
single compact lamps
Features:
• Combined electronic ballast and emergency modules for compact lamps
•
Incorporating
our PERFERM™ technology to ensure optimum operation of low mercury
and amalgam construction lamps from both ‘cold start’ and warm start applications
•
he electronic ballast circuit has a lamp failure protection circuit to prevent damage
T
occurring to the ballast when a lamp falls
• Sine-wave output in emergency prevents unpleasant visual lamp effects and
ensures maximum lamp cathode life
•
Advanced battery charging circuit exploits energy absorption
charging technology which reduces power losses in the
unit, is reverse polarity protected and provides stable
charge conditions to maximise battery life
• Joule combined units have Deep Discharge
Protection to further help in preventing damaging
operating conditions for the battery pack and are
suitable for use with Ni-Cad and Ni-MH cells
• Designed to comply with the requirements of the European
product standards EN 60924, EN 60925, EN 60929, EN55015,
EN61000.3.2, EN 61547, EN61347-2-7 and EN 61347-2-3
• Produced in our UK manufacturing plant which is registered and audited
by BSI to BS EN ISO 9001:2000
Cat No.
Cells
MCP4100P3
3x4AH
MCP4097P3
MCP4099P3
16W 2D Single 18W TC-D 22W T5
36W TC-F
38W 2D
40W T5 C
-
-
-
-
-
-
-
12
-
-
-
-
18
-
-
-
-
21
17
-
15
-
-
-
-
-
-
-
10
13
12
15
-
-
3x4AH
-
19
4x4AH
21
-
MCP4098P3
4x4AH
-
MCP4101P3
5x4AH
-
Single 26W TC-D 28W 2D
*’Cold start’ deemed to be temperatures above 10°C
All modules supplied with green LED.
All of the products are for 3 hour duration, for other durations, specify the required time period e.g. P3 becomes
P1 for 1 hour duration
Dimensions: 180mm x 70mm x 35mm
Fixing Centres: 170mm
Weight: 0.54Kg
All modules
are BSI
Kitemarked.
KM21518
Self contained emergency gear (conversion kits) | 67
Emergency conversions within quality systems
ISO9001: 2000 and ICEL 1004 approved
Orbik manufacture a comprehensive range of BSI approved emergency control gear
within their ISO9001: 2000 approved factory in the UK.
One of the many added-value services ORBIK/ELF/SPEL offer to their customers
is the re-engineering of third party mains only luminaires into emergency versions.
This operation is carried out and tested by highly skilled personnel working within a
ISO9001:2000 quality environment and registered to ICEL and approved to its ICEL
1004 Luminaire re-engineering scheme.
Facilities on site include testing for thermal endurance and EMC compliance for
re-engineered luminaires so that customers can be confident that these luminaires
remain compliant with European product safety and performance standards and
comply with the CE regulations.
Orbiks BSI approved emergency control gear ensures the highest quality
products are used to convert free issued luminaires with a choice of integral
or remote solutions for most 4 pin fluorescent lamps and 12V halogen
dichroic lamps.
With reduced mercury lamps being standardised on by most
leading lamp manufacturers, Orbiks BSI approved Perferm
emergency modules are specified for these lamp types as
their in-house design ensures reliable striking of the
latest generation of 4 pin compact and linear
fluorescent lamps.
Emergency
Conversions
Lighting industry
for over 25 years...
Orbe
P43
Compact
fluorescent
lobay
Self contained emergency gear (conversion kits) | 69
A full range of pre-wired emergency control remote boxes
With the constant development of low-energy compact fluorescent lamps, luminaire
designers are now able to design smaller low profile luminaires. With the increasing
requirements of emergency lighting in Public Buildings, these smaller luminaires can present
problems where they are physically too small and hot to house integral emergency lighting
control gear and batteries. For such applications we offer a full range of pre-wired emergency
control remote boxes which can be mounted adjacent to the luminaire and simply connected
via a flexible 0.5 metre, flame retardant, loom. Constructed in a galvanised finish steel
enclosure without side panels for easy access.
Remote Emergency
Systems
If you require this service simply prefix the product with RB/ i.e. PL4003P3 = RB/PL4003P3.
Dimensions (mm)
Size
L
W
H
Upto 3 cell
290
95
40
Upto 5 cell
425
100
45
Upto 10 cell
430
150
50
Printed Circuit
Boards
PCB ranges are generally for self contained luminaires where price is a significant factor.
As with most of our products the printed circuit board range are approved to the British/
European Standard EN60924/60925.
PCB Suffix/T have fold over LED. Suffix/TL have an LED. terminal block
All of the above products are for 3 hour duration, for other durations, specify the required time
period e.g. P3 for 1 hour duration becomes P1
Dimensions (mm)
Printed Circuit boards
A
B
C
D
Height
Non-Maintained
123
40
114
31
30
Maintained with C/O Relay
123
40
114
31
30
13W TC-D 4 Pin
16W 2D 4 Pin
45
22
30
26
P226/3/TL
P232/3/TL*
3 x 4AH
45
33
33
37
PERFERM
P1028/3/TL
3 x 4AH
19
20
12
PERFERM
P1038/3/TL
5 x 4AH
* Only suitable for Switchstart circuits.
PCB suffix/T have a fold over LED. Suffix/TL have an LED terminal block. All PCBs supplied with a green LED.
All of the above products are for a three hour duration, for other durations specify the required time period e.g. for 1 hour duration change part number from /3 to /1.
BSI Approved
38W 2D 4 Pin
11W TC-S 4 Pin
2 x 4AH
28W 2D 4 Pin
10W TC-D 4 Pin
P404/3/TL*
P400/3/TL
18W TC-D 4 Pin
9W TC-S 4 Pin
20
8W 300mm
30
7W TC-S 4 Pin
24
6W 225mm
37
No. of Cells
4W 150mm
28
Maintained
PCB’s for
external gear
Circuits
Non-Maintained
PCB’s
13
70 | Self contained emergency gear (conversion kits)
Nickel Cadmium
Batteries
In today’s competitive environment it is often the hidden elements of a product where
“savings” are made. In the case of self contained emergency lighting luminaires, it is often
the Nickel Cadmium battery which is judged to be an item where money can be saved, often
to the detriment of product performance, life, maintenance, and ultimately safety of lives.
We have a policy of using quality, high temperature Nickel Cadmium
batteries manufactured by world class companies using premium
materials and graded to the demanding standards of IEC285, and
when installed and operated in accordance with EN60598.2-22 meet
the requirements for a 4 year life.
In addition to the many standard battery configurations illustrated in
this catalogue, we are able to offer special battery configurations to assist
in the layout of components within luminaires having restricted space.
Redesigned endcaps now allow for inline batteries to be dove-tailed together
creating dual-in-line packs.
Nickel Metal
Hydride
The Green Alternative
Anticipating the growing awareness for the need to care more for our environment, we have
had an “alternative” battery development program in place since 1996. Whilst the nickel
cadmium battery is still specified in the majority of our emergency lighting products, there
is no doubt that it is becoming expensive to dispose of both financially and environmentally
due to the heavy metals and other pollutants which form part of the chemistry of each cell.
We have been working closely with both sealed recombination lead acid battery
manufacturers and nickel metal hydride battery manufacturers to find the most economical
and practical alternative to nickel cadmium. Our experience with nickel metal hydride battery
packs used in self contained luminaires sited in locations with elevated temperatures, is
second to none and we are confident that these batteries, when used in the correct way, have
many advantages over other battery technologies.
These are supplied in 2 and 3 Cell variations to enable most Cell combinations to be easily
constructed.
•
iMh batteries are kinder to the environment than NiCd and are cheaper to dispose of
N
at the end of life.
•
iMh batteries have a better power density than NiCd and lead acid batteries from a
N
smaller size cell, so can be used in products where space is limited.
•
igh temperature NiMh batteries are particularly designed for emergency lighting
H
applications which some alternative battery technologies cannot provide.
•
iMh batteries have a lower cost and longer active life than Lithium batteries, which
N
means being environmentally friendly is not too costly.
•
iMh battery technology is advancing all the time and there is little doubt they will
N
become increasingly popular, so designing battery and product layouts using NiMh can
sizes is an investment in the future.
Whether the future of your next emergency lighting installation or the future of the World is
your prime consideration, NiMh batteries should feature high on your list of priorities.
Self contained emergency gear (conversion kits) | 71
Technical Details
For battery packs
Battery
Cat No.
Pack
2x4 AH NMH
3x4 AH NMH
2x1.5 AH Nicad
BH164
Duration
(Hours)
Length
A
Width
B
Depth
C
3
140
20
20
Fixing Centre
Style
D
70
IN-LINE
Battery
Weight (Kgs)
0.14
BH167
3
210
20
20
70
IN-LINE
0.21
B163/215
1
125
27
25
113
IN-LINE
0.10
2x4 AH Nicad
B164/24
3
164
36
36
149
IN-LINE
0.29
2x4 AH Nicad
B161/2 x 4
3
65
72
36
-
SidexSide
0.28
3x1.5 AH Nicad
B165/315
1
167
27
25
155
IN-LINE
0.15
3x4 AH Nicad
B166/3x4
3
99
65
34
40x33
PLATE
0.47
3x4 AH Nicad
B167/34
3
226
36
36
214
IN-LINE
0.43
4x1.5 AH Nicad
B168/415
1
209
27
25
197
IN-LINE
0.20
4x4 AH Nicad
B169/4x4
3
130
65
34
40x65
PLATE
0.59
4x4 AH Nicad
B702/4x4
3
123
75
36
108
DUAL
0.58
4x4 AH Nicad
B170/44
3
285
36
36
270
IN-LINE
0.57
5x1.5 AH Nicad
B171/515
1
251
27
25
239
IN-LINE
0.25
5x4 AH Nicad
B172/5x4
3
163
65
34
40x97
PLATE
0.78
5x4 AH Nicad
B173/54
3
346
36
36
331
IN-LINE
0.70
6x1.5 AH Nicad
B174/615
1
293
27
25
281
IN-LINE
0.30
6x4 AH Nicad
B176/64
3
406
36
36
391
IN-LINE
0.83
6x4 AH Nicad
B701/6x4
3
182
75
36
167
DUAL
0.84
8x4 AH Nicad
B878/84
3
525
36
36
510
IN-LINE
1.00
8x4 AH Nicad
B879/8x4
3
242
75
36
227
DUAL
1.35
10x1.5 AH Nicad
B177/1015
1
451
54
25
239
DUAL
0.50
10x4 AH Nicad
B178/104
3
648
36
36
633
IN-LINE
1.40
10x4 AH Nicad
B179/10x4
3
300
75
36
285
DUAL
1.35
All dimensions in mm
Cells
1.5AH Nicad for 1 hour duration modules/PCB’s. 4AH Nicad + NMH for 3 hour duration
modules/PCB’s
Permitted cell temperature
Minimum 0°C. Maximum 54°C, to give the specified performance for an expected life of
4 years
Battery connections
Batteries are supplied with tag connections with the exception of dual in-line and plate
versions, which are fitted with a non-reversable plug. The appropriate connections are
supplied with the batteries.
Battery fixing
Batteries are supplied with plastic end caps or metal plates with screwserts with provision
for screw fixings.
72 | Low voltage emergency lighting
Emergency lighting kits to operate 12 volt tungsten halogen lamps in
the event of a power failure
Low Voltage
Emergency
Lighting
These are available in three modes:
C
Non-maintained (NM) where the lamp is only illuminated when power fails
•
emote Maintained where a separate transformer is used, ideal for dimming installations
R
or where matching mains operation characteristics are critical.
•
Maintained (M) where the unit is supplied with an integral transformer.
All units incorporate a BSI Approved Charger Circuit to maximise battery life and deep
discharge battery protection, essential for Lead Acid batteries. They are housed in a white
epoxy coated sheet steel enclosure, and are supplied with 5 year life sealed Lead Acid
batteries.
B
A
•
LOW-VOLTAGE EMERGENCY BOX - ECONOMY VERSION (BALLAST LUMEN FACTOR 20W - 6% 50W - 10%)
Cat No.
Mode
1 Hour
R931/50
Non-Maintained
2 x 20W
5 x 20W
D
R932/50
Maintained
with
1 x 50W
Maintaining Transformer
2 x 20W
C
R942/50
Maintained without
2 x 50W
Maintaining Transformer
5 x 20W
DurationDimensions (Size in mm)
2 Hours 3 Hours
A
B
C Fixing Centres
1 x 50W 1 x 50W
250
230
72
187
3 x 20W 2 x 20W 1 x 50W 1 x 50W
250
230
72
187
2 x 20W 2 x 20W
1 x 50W 1 x 50W
250
230
72
187
3 x 20W 2 x 20W
Kg
4.0
5.0
4.0
A
B
LOW-VOLTAGE EMERGENCY BOX - 12V VERSION (BALLAST LUMEN FACTOR = 100%)
DurationDimensions (Size in mm)
Cat No.
Mode
1 Hour
2 Hours 3 Hours
A
B
C Fixing Centres
R939/50 Non-Maintained
1 x 50W 1 x 20W 1 x 20W
250
230
72
187
2 x 20W
R940/50
Maintained with
1 x 50W 1 x 20W 1 x 20W
250
230
72
187
Maintaining Transformer 2 x 20W R943/50
Maintained without
1 x 50W 1 x 20W 1 x 20W
250
230
72
187
Maintaining Transformer
2 x 20W
R760/50
Non-Maintained
2 x 20W 1 x 20W 1 x 20W
315
270
110
120
1 x 50W
R759/50
Non-Maintained
5 x 20W 3 x 20W 2 x 20W
315
270
110
120
2 x 50W 1 x 50W 1 x 50W
R757/50
Maintained with
2 x 20W 2 x 20W 1 x 20W
315
270
110
120
Maintaining Transformer 1 x 50W R758/50
Maintained with
2 x 20W 2 x 20W 2 x 20W
315
270
110
120
Maintaining Transformer 1 x 50W 1 x 50W 1 x 50W
R700/50
Maintained with 2x 50W
5 x 20W
-
-
315
270
110
120
Maintaining Transformer 2 x 50W -
-
R835/50
Maintained without
2 x 20W 1 x 20W 1 x 20W
315
270
110
120
Maintaining Transformer 1 x 50W -
-
R836/50
Maintained without
5 x 20W 2 x 20W 2 x 20W
315
270
110
120
C
Maintaining Transformer 2 x 50W 1 x 50W 1 x 50W
6V & 12V dc Charger Pcb
Kg
5.2
6.7
5.5
5.2
10.7
6.7
12.2
13.5
5.2
10.9
B
A
Emergency lighting pcb’s to operate 12 volt tungsten halogen lamps in the event of a power failure
The 6V and 12V DC charger circuits incorporated into our tungsten lead acid remote boxes are also available as separate printed circuit boards to
give users full flexibility with their choice of housings, batteries and maintaining components. The facility of a 10A terminal block on each PCB offers
a greater degree of flexibility for installation within a remote box/twinspot/luminaire.
Dimensions
Cat No.
CB112
CB106
Dimensions in mm
Voltage
Battery Type
Mode
Lamp Range No. of Outlets
12V
VP Lead Acid Maintained or 10-100W
2
6V
Non Maintained
A
147
BSI Approved
B
68
C
135
D
50
Height
45
D
C
A
B
Low voltage emergency lighting | 73
A new train with each element housed
in a separate galvanised metal box
To compliment our low voltage emergency lighting product range, we have introduced a new
product in the form of a train where each element is housed in a separate galvanised
metal box. This will operate lamps up to 50W at 6 Volts in emergency mode,
giving a ballast lumen factor of 10% for a 50W and 6% for a 20W lamp.
The compact size allows it to fit through a 85mm cut-out and the
standard non-maintained (or maintained via an external transformer) is
in two sections. If required we can supply a maintaining transformer in
a third box. All units provide 3-hour duration in the emergency mode
from the valve regulated lead acid batteries.
Catalogue Numbers
Dimensions (millimetres)
Maintained: R959/50/M3,
Non-Maintained: R959/50/NM3
For shorter durations, specify
the required time period
e.g. /NM3 for 1 hour
duration becomes /NM1
Charger and LV transformer enclosure:
Length 230mm x Width 74mm x Height 60mm
Valve regulated lead acid battery enclosure:
Length 350mm x Width 74mm x Height 60mm
Nickel Cadmium Emergency Conversion Kits
for 12 Volt Lamps up to 50W 3 hours:
Our low voltage lighting train enables 12 volt Tungsten Halogen lamps to operate in the
event of a power failure. The ability to feed the lighting train through ceiling aperture cutouts of 60mm ensures easy installation.
The lighting train is available in Non-Maintained mode, where the lamp is only
illuminated when the power fails and also Maintained mode, which is
supplied with an integral transformer which operates the lamp in mains
healthy and in the event of a power failure.
Vrla Low Voltage
Lighting Train
NICAD
Low Voltage
Lighting Train
The low voltage lighting train features high quality, high
temperature Nickel Cadmium battery cells and a silicone
coated woven glass fibre sleeving ensuring the product
is manufactured to BS/EN60924. The lighting train also
allows dimming of the Halogen lamps if required.
Dimensions (millimetres)
Overall Length 800mm
Lighting Train can fit through Ceiling Cut-Outs of 60mm or above
Cat No.
Mode
Lamp
Duration (1x20W) Duration (1x50W)
Ballast Lumen Factor
R960/50/NM1 Non-Maintained
50/20W 12V
3 Hours
1 Hour
50W - 10% / 20W - 6%
R960/50/M1
Maintained (with transformer) 50/20W 12V
3 Hours
1 Hour
50W - 10% / 20W - 6%
R961/50/M1
Maintained (without transformer)
50/20W 12V
3 Hours
1 Hour
50W - 10% / 20W - 6%
R962/50/NM3 Non-Maintained
50/20W 12V
3 Hours
3 Hour
50W - 10% / 20W - 6%
R962/50/M3
Maintained (with transformer) 50/20W 12V
3 Hours
3 Hour
50W - 10% / 20W - 6%
R963/50/M3
Maintained (without transformer)
50/20W 12V
3 Hours
3 Hour
50W - 10% / 20W - 6%
74 | Low voltage emergency lighting
Led Combi Module
Lcp31051/3
We have introduced a range of products designed to exploit the
significant advantages that the new generation of high power white
light emitting diodes (LEDs) offer.
•
•
•
•
•
•
•
•
•
•
Led Power Driver
Lpd8
•
•
•
•
Change-over and
Sub-circuit Monitor
Relay - drm415ac
ombined electronic parallel LED driver and emergency module, suitable for nonC
maintained and maintained 3-hour operation.
Supplies into 6W of output power at 4 Volts D.C.
Can be used for Nickel Cadmium or Nickel Metal Hydride cells in a variety of capacities
dependant on the duration and load requirements.
Easy selection of charge outputs.
Load3-hour battery
1W 3 x 0.7Ah cells
3W 3 x 1.5Ah cells
5W 3 x 4Ah cells
Maintained output can be switched via a separate input terminal
Electronics are suitable for a wide operating temperature range of –40°C to +50°C. (not
including batteries).
Lightweight and compact size polycarbonate case provides designers with a large degree
of flexibility. Dimensions: L130mm x W50mm x H30mm. Fixing centres 120mm.
Short circuit and battery polarity protected.
All designed to comply with EN55015 and relevant clauses of EN60924.
igh output parallel LED driver supplying loads up to 8 Watts at 4 Volts a (limiting
H
resistor should be included with the LED array).
Suitable for 230V ±50% 50Hz (other supply voltages available to order).
Housed in a polycarbonate case with dimensions of L130mm x W50mm x H30mm.
Fixing centres at 120mm.
Designed to comply with EN55015.
The DRM415AC relay module is an enclosed change-over relay for use
with static inverter operated emergency lighting systems and is rated
at 1250VA.
The DRM415AC can be used with either maintained or non-maintained luminaires, powered
from a static inverter and provides local sub-circuit monitoring to comply with the European
Standard for centrally supplied emergency systems, EN50171.
For non-maintained operation, the static inverter supply is connected to
the DRM415AC together with the local lighting circuits un-switched
supply. Upon loss of the local supply, the relay changes over and the
luminaire is operated by the output from the static inverter.
For maintained operation, the switched supply is also
connected to the DRM415AC. This allows the luminaire to be
switched on and off as though it were a normal mains luminaire.
In the event of the local un-switched supply failing the luminaire
is operated from the static inverter supply, regardless of whether the
luminaire was being operated from the normal mains supply at the time.
A number of different options based upon the DRM415AC are available:
DRM415AC:
Static inverter changeover relay rated at 1250VA
DRM415AC/NR:As above, with neon indicator showing that the static inverter supply is
present and healthy.
DRM415AC/RB:Static inverter change over relay housed within a sheet metal box for
remote mounting.
DRM415AC/RB/NR:As above except with neon indicator showing that the static inverter
supply is present and healthy.
DRM415AC/ADD Addressable remote box incorporating OEL305.
All of the above products can be factory fitted within “free-issued” luminaires, please contact our sales
office for information.
Inverters for use with central systems | 75
Incorporating PERFERM™ Technology
We produce a range of inverter units suitable for operating fluorescent lamps from low
voltage AC or DC supplies, including central battery systems of 24 Volts, 50 Volts and 110
Volts and fluorescent lamps from 4 Watts to 100 Watts.
All PV range inverters incorporate our PERFERM™ technology to ensure good lamp life and
correct operation with low mercury fluorescent lamps and sine-wave output to prolong lamp
cathode life and prevent unpleasant visual lamp effects.
Inverters for
use with
Central Systems
They are designed to comply with the European product standards EN50172, EN55015,
EN 61547 and EN 61000.3.2 and are produced in our UK manufacturing plant which is
registered to BS EN ISO9001:2000 by BSI.
Two types of operation are normally encountered in low voltage systems being:
1. Slave inverters - where the lamp is operated only from the inverter
unit. Typical of this type of use is vehicles where there is no mains
supply or an emergency lighting system that is separate to the
normal lighting luminaires. An example of a slave inverter of this type
is our PV289.
2. Inverter units with an AC hold-off relay are used to convert normal mains
luminaires to emergency luminaires by switching the lamp from the normal
mains control gear to the inverter output when the un-switched monitored mains
supply fails. An example of this type of inverter unit is our PVR110.
Luminaire with Slave inverter
Low Voltage
AC or DC
Supply
Inverter Unit
Converted luminaire
Switched Supply
Mains ballast
Unswitched Supply
Inverter Unit
with AC hold-off
relay
Low Voltage
AC or DC
Maintained
Supply
Technical details for inverters
•
I nverters are designed to conform to EN60924/60925. They are EMC compliant and
carry the CE mark.
•
Output circuitry uses a high efficiency sinusoidal inverter.
•
Operating temperature range Inverter 0 to 70°C (centre side of case).
•
DC Inverter Supply Range
Nominal Supply - 16% + 25%
•
C/DC Inverter Supply Range
A
supply
Nominal Supply - 16% + 25% DC supply +/- 10% AC
Dimensions
Sizes
A
B
C
Fixing Centre
D
E
Kg
Lamps up to 20W
154
42
35
144
138
0.25
Inverters with relay
216 42
28
206
200
0.35
Open PCB versions 131
40
114
31
-
-
Inverter Dimensions (millimetres)
Technical Details
76 | inverters for use with central systems
Technical
Specification
Inverters For
Fluorescent Lamps
No Relay
24 Volt AC/DC
50 Volt AC/DC
110 Volt AC/DC
Canned Unit
PV288
PV289
PV290
PCB Version
19288
19289
19290
Power Input
BLF
Power Input
BLF
Power Input
BLF
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
4W (150mm)
11VA
4.3W
0.44
0.36
14VA
3.96W
0.56
0.34
15VA
4.6W
0.50
0.43
5W TC-S
12VA
4.7W
0.68
0.40
14VA
4.73W
0.46
0.34
1VA
5.2W
0.65
0.51
6W (225mm)
13VA
5.0W
0.56
0.41
16VA
5.2W
0.58
0.53
17VA
5.6W
0.85
0.71
7W TC-S
13VA
5.5W
0.39
0.38
16VA
5.2W
0.44
0.40
18VA
5.9W
0.62
0.49
8W (300mm)
15VA
6.3W
0.60
0.47
18VA
6.3W
0.80
0.60
20VA
6.9W
0.70
0.57
24 Volt AC/DC
50 Volt AC/DC
110 Volt AC/DC
Canned Unit
No Relay
PV190
PV191
PV192
PCB Version
19720
19721
19722
Power Input
BLF
Power Input
BLF
Power Input
BLF
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
9W TC-S
20VA
11W
0.60
0.40
23VA
11W
0.54
0.45
26VA
9W
0.51
0.42
11W TC-S
22VA
13W
0.40
0.31
29VA
14W
0.49
0.41
32VA
11W
0.49
0.41
13W TC-D, TC-T
21VA
13W
0.51
0.41
30VA
15W
0.54
0.44
31VA
11W
0.61
0.48
16W 2D
22VA
16W
0.42
0.32
32VA
16W
0.49
0.38
33VA
12W
0.49
0.35
14W T5
22VA
15W
0.50
0.45
31VA
16W
0.50
0.41
35VA
13W
0.49
0.39
18W TC-D, TC-L
20VA
13W
0.49
0.40
28VA
14W
0.37
0.31
32VA
12W
0.41
0.37
18/20W T8
21VA
14W
0.29
0.19
33VA
17W
0.35
0.29
35VA
13W
0.27
0.21
Inverters for use with central systems | 77
Incorporating
24 Volt AC/DC
50 Volt AC/DC
110 Volt AC/DC
mains holdoff PVR24
PVR50
PVR110
Relay
Power Input
BLF
Power Input
BLF
Power Input
BLF
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
7W TC-S
15VA
7W
0.38
0.28
18VA
7W
0.47
0.35
20VA
8W
0.53
0.40
8W T5
15VA
7W
0.45
0.56
19VA
8W
0.60
0.45
21VA
9W
0.57
0.43
9W TC-S
15VA
8W
0.42
0.35
19VA
8W
0.58
0.48
21VA
9W
0.58
0.46
11W TC-S
16VA
8W
0.40
0.29
20VA
8W
0.55
0.43
22VA
9W
0.61
0.49
13W T5
16VA
8W
0.62
0.48
20VA
8W
0.64
0.50
22VA
9W
0.58
0.46
14W T5
16VA
9W
0.36
0.27
21VA
9W
0.50
0.36
23VA
9W
0.42
0.33
16W 2D
17VA
9W
0.45
0.38
21VA
9W
0.60
0.46
23VA
9W
0.56
0.44
18W/20W T8
18VA
8W
0.20
0.14
21VA
8W
0.24
0.20
23VA
9W
0.24
0.18
18W TC-D
19VA
9W
0.31
0.24
23VA
10W
0.45
0.35
24VA
10W
0.42
0.32
21W T5
19VA
10W
0.32
0.24
24VA
11W
0.44
0.34
25VA
11W
0.40
0.32
22W T5 Circular
19VA
10W
0.28
0.25
26VA
11W
0.40
0.33
26VA
11W
0.38
0.30
24W TC-L
19VA
9W
0.25
0.20
21VA
9W
0.43
0.28
24VA
10W
0.36
0.25
26W TC-D
20VA
11W
0.24
0.18
27VA
11W
0.35
0.22
26VA
11W
0.30
0.25
28W 2D T5
19VA
9W
0.24
0.19
27VA
11W
0.36
0.27
25VA
11W
0.33
0.24
28W T5
22VA
12W
0.31
0.23
31VA
13W
0.46
0.35
30VA
13W
0.42
0.35
32W TC-T
21VA
12W
0.37
0.28
28VA
12W
0.51
0.40
29VA
12W
0.49
0.38
35W T5
25VA
14W
0.31
0.23
36VA
16W
0.45
0.33
34VA
15W
0.41
0.34
36W TC-L
22VA
11W
0.22
0.16
26VA
11W
0.30
0.25
29VA
12W
0.29
0.21
36W T8
21VA
11W
0.17
0.14
27VA
11W
0.27
0.20
28VA
11W
0.22
0.18
38W 2D T5
19VA
11W
0.16
0.13
27VA
11W
0.24
0.19
30VA
13W
0.23
0.17
39W T5
22VA
12W
0.15
0.12
30VA
13W
0.24
0.18
30VA
13W
0.22
0.17
40W T5 Circular
24VA
13W
0.30
0.23
33VA
14W
0.45
0.35
30VA
13W
0.43
0.34
40W TC-L
24VA
13W
0.29
0.21
30VA
13W
0.39
0.28
31VA
14W
0.36
0.28
42W TC-T
23VA
13W
0.23
0.13
32VA
14W
0.39
0.24
32VA
13W
0.36
0.24
49W T5
26VA
15W
0.29
0.22
37VA
17W
0.44
0.28
35VA
16W
0.33
0.26
54W T5
27VA
15W
0.18
0.14
36VA
16W
0.26
0.20
35VA
16W
0.24
0.20
55W T5 Circular
26VA
14W
0.25
0.20
35VA
15W
0.39
0.29
33VA
15W
0.33
0.27
55W 2D
23VA
12W
0.17
0.13
30VA
12W
0.26
0.19
30VA
13W
0.21
0.17
55W TC-L
26VA
14W
0.22
0.18
32VA
13W
0.31
0.24
33VA
15W
0.30
0.25
58W T8
24VA
13W
0.13
0.11
34VA
14W
0.29
0.22
33VA
14W
0.22
0.18
70W T8
27VA
15W
0.12
0.09
38VA
16W
0.10
0.08
36VA
17W
0.10
0.08
80W T5
30VA
17W
0.17
0.14
41VA
19W
0.28
0.22
39VA
19W
0.25
0.21
100W T12
27VA
14W
0.09
0.06
37VA
16W
0.15
0.10
35VA
16W
0.13
0.11
78 | Central systems
Central Battery
and Inverter
Systems
Low Power
DC Systems
We supply a wide range of AC/DC and AC/AC central systems
Designed to meet the requirements of specific applications. Central systems have advantages
over self-contained emergency luminaires as follows;
•
ains luminaires can be used in place of conventional emergency luminaires allowing
M
higher light levels to be obtained.
•
he central system and battery cubicles, being centrally located, make maintenance,
T
control and monitoring easier.
•
ith a wide range of battery types and sizes the design life of the battery and duration
W
of discharge can be specifically designed around the parameters of the individual
application.
•
he luminaires being mounted remotely from their power source can be placed in
T
environments where a battery may not be capable of correct operation due to extreme
heat or cold.
We offer two ranges of lower power systems
Using sealed recombination lead acid batteries. The LPDC5 uses the 5-year design life
battery and the LPDC10 the-10 year design life battery. All Central Systems available with 10
year design life battery’s to order.
Tables below show the standard ranges but these can be augmented with alternative
batteries and durations if required.
Cabinet sizes (millimetres)
W1 - Height 455 x Width 405 x Depth 210; W2 - Height 555 x Width 750 x Depth 250
LPDC5 Range
Model*
LPDC5/12/15
LPDC5/24/6
LPDC5/24/15
LPDC5/24/24
LPDC5/24/38
LPDC5/24/48
LPDC5/24/65
High Power
DC Systems
Features:
• NM, M single or dual output
versions for optimum system
flexibility
• Lift off cubicle covers provide
easy access for maintenance
• Separate battery and gear
compartments for safer
operation
• Cubicles are manufactured
from sheet steel and are
epoxy powder coated for a
long life in RAL-7032
• Choice of Contactors to
BS5424 as standard, BS764
types available.
• A wide battery choice to give
optimum flexibility
• A range of pre-engineered options to allow complete
control and monitoring.
*Specify NM, M operation and duration required
(ie. NM3) e.g.. HPDC/24/30/NM1/VR = 24V 480 watts Non
maintained operation for 1 hour
To select a model in the HPDC range, insert either NM or M
describing the system operation and the system duration
1,2 or 3 hours. Options required should be specified using
the relevant suffix e.g. “/LE” = Low Electrolyte alarm, e.g.
HPDC/110/ 46/M3VR/LE is a 110V Maintained system
supplying 1350 watts for 3 hours via its Value Regulated,
lead acid battery and has a Low Electrolyte alarm facility
Power Rating
(W) for 1 hour
140
84
216
300
480
550
960
Power Rating
(W) for 3 hours
55
38
90
150
234
300
432
Nominal Output
Voltage
12
24
24
24
24
24
24
Cabinet Type
W1
W1
W1
W2
W2
W2
W2
Trouble free operation with a wide choice of batteries
Our high power systems are manufactured to the highest standards from the UK’s leading
systems supplier. They offer long trouble free operation with a wide choice of batteries and
options for specific applications.
HPDC - Valve regulated Lead Acid (VR) range
System
Model
Power Rating Power Rating Power Rating Battery
Normal Range Description (W) 1 Hour (W) 2 Hours (W) 3 Hours Capacity Ah
24 Volts HPDC/24/22/*VR
340
195
35
22
12 Cells
HPDC/24/30/*VR
480 280
190
30
HPDC/24/46/*VR
750 430
300
46
HPDC/24/68/*VR 1050 610
420
68
HPDC/24/84/*VR 1350 790
545
84
HPDC/24/98/*VR 1550 925
635
98
HPDC/24/120/*VR 1925 1120
780
120
50 Volts
HPDC/50/22/*VR
680 390
270
22
24 Cells
HPDC/50/30/*VR
960 560
380
30
HPDC/50/46/*VR 1500 860
600
46
HPDC/50/68/*VR 2100 1220
840
68
HPDC/50/84/*VR 2700 1580
1090
84
HPDC/50/98/*VR 3150 1850
1270
98
HPDC/50/120/*VR 3850 2250
1560
120
HPDC/50/152/*VR 4700 2800
1960
152
110 Volts
HPDC/110/22/*VR 1500 890
610
22
54 Cells
HPDC/110/30/*VR 2150 1250
870
30
HPDC/110/46/*VR 3350 1950
1350
46
HPDC/110/68/*VR 4800 2750
1900
68
HPDC/110/84/*VR 6100 3550
2450
84
HPDC/110/98/*VR 7150 4150
2850
98
HPDC/110/120/*VR 8700 5050
3500
120
* Specify mode and duration e.g. NM1, M3, etc.
Cabinet
Type
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F2
F2
F2
F3
F2
F2
F2
F3
F3
(2)F4
(2)F4
Central system | 79
With intelligent Datlog™ technology
Our range of static inverter systems are designed to provide emergency lighting (1 to 3 hours
as required) at 230VAC (or selected Voltage) at 50Hz and includes the latest version of the
acclaimed Datlog™ system monitoring and data logging software. The range is designed as
the safe option (AC output under emergency conditions).
Datlog™ will automatically monitor the load and the battery at a specified time and date
if required. Yearly, monthly or weekly testing if required ensures that all luminaires and the
battery are correctly functioning. The test results and alarms are stored in an internal nonvolatile memory. With the optional external printer, the events log can be printed out for
permanent record keeping.
Datlog™ also monitors the battery for continuity and provides temperature compensation
and deep discharge protection to ensure maximum life from the batteries. The user-interface
is easy to use with scroll buttons to read all operational parameters (available in different
languages). Additionally standard alarm outputs allow integration into most building
management systems.
Where price is an issue systems can be supplied without the Datlog™ facility.
Our range of high power static inverter central AC systems are active, off-line sine-wave
interters and provide the ultimate solution in emergency lighting for medium to large
premises. Producing a sinusoidal waveform with <5% harmonic distortion into a linear load,
the HPAC range is ideal for use with the latest high frequency ballasts and offers a no-break
option, for high-pressure discharge lighting schemes.
HPAC systems are active and offline and use a static switch to supply a by-passed supply
during normal conditions with a contactor for the non-maintained output. When there is a
power failure the contactor connects the non-maintained load to the inverter that continues
to supply the lead
As standard the HPAC range covers single and three-phase outputs, from 1.6kVA to 200kVA.
Single or three phase inputs with a single phase output are available up to 25kVA and three
phase inputs with three phase outputs are available from 10kVA to 200kVA.
It should be noted that in order to comply with EN60598.2-22, it is essential that luminaires
must not use glow starters or 2 pin lamps with integral starters, therefore electronic ballasts or
electronic starters are required.
Ordering Codes: High Power Systems
Low Power Systems
Cat No
Input
Phases
Watts
VA
Battery
Volts
Cat No
Max
VA
Max
Watts
HPAC3/1/#
Single
2400
192
LPAC/10/#
150
120
HPAC4/1/#
Single
3200
192
LPAC/20/#
300
240
HPAC6/1/#
Single
4800
264
LPAC/30/#
450
360
HPAC8/1/#
Single
6400
264
LPAC/40/#
600
480
HPAC10/1/#
Single
8000
264
LPAC/50/#
750
600
HPAC12/1/#
Single
9600
264
LPAC/60/#
950
750
HPAC15/3/#
Three
12000
480
LPAC/80/#
1250
1000
HPAC20/3/#
Three
16000
480
LPAC/100/#
1500
1200
HPAC25/3/#
Three
20000
480
HPAC30/3/#
Three
24000
480
HPAC40/3/#
Three
32000
480
HPAC60/3/#
Three
48000
480
AC Systems
80 | Central systems
Mini-Sine
A mini static inverter emergency lighting
unit for loads up to 150 watts
Orbik low power compact Mini Sine is a Mini Static inverter system designed to operated
loads upto 150W at 230V. This popular unit is available in 2 versions, either for 1 or 3 hour
duration on mains failure.
A purpose designed lead acid charger provides a float voltage of 27V within a tolerance of
1% with a sustainable charge current of 5A and over current protection. The charger is short
circuit and battery reversal protected with the addition of thermal shutdown protection.
Addition cooling for the charger during early charging stages is
provided by a quiet chassis mounted fan.
A high efficiency soft start modified sine wave
inverter provides the emergency back up
making it suitable for inductive loads. Output is
230V ± 10% 50Hz ± 1%. It is able to provide
continues loading up to 150W and includes
overload protection. The sine wave inverter
includes over temperature and short circuit
protection and is suitable for operation in an
ambient of up to 30°c.
The front panel provides a number of indictors
displaying healthy supply, power failure battery
disconnect/charger failure and over a charge
indicator that extinguishes when the charge
current falls below 1 Amp.
Additional fault monitoring is provided via a
set of volt free contacts allowing for remote
monitoring of the Mini Sine.
Mini Sine is supplied with Lead Acid Batteries
which are housed within its robust high quality
steel enclosure that is supplied in a white finish.
Mini Sine has advantages compared to selfcontained systems for emergency lighting which
include lower maintenance being a central unit,
mains luminaires can be used with higher light
outputs compared to conventional emergency
luminaires which typically produce lower ballast
lumen factors. Also with integral batteries the
Mini Sine can operate luminaires which maybe
placed in environments unsuitable for batteries
due to extreme heat or cold.
Mini Sine has also been successfully utilised to
operate with certain discharge luminaires. (Please
contact our technical department for assistance)
Ordering Codes
Cat No
Description
MS150/1
150W 1 Hour Static Inverter Emergency Lighting Unit
2x12V 12Ah
MS150/3
150W 3 Hour Static Inverter Emergency Lighting Unit
2x12V 25Ah
Dimensions: 375mm x 440mm x 160mm
Weight: 2
1Kg (MS150/1 including batteries)
30Kg (MS150/3 including batteries)
Batteries
Complete
reassurance
82 | Addressable emergency lighting systems
PALS™
Addressable Emergency Lighting
Regular testing and maintenance of emergency lighting systems is essential and is now a
legal requirement in many countries. It is possible to carry out testing manually but this can
be expensive and time consuming and accurate record keeping difficult to arrange. PALS is
a Programmable Addressable Lighting System that will automatically test and monitor the
emergency lighting system and produce accurate reports of test results and system events.
It ensures building owners and occupiers are informed promptly of any problems effecting
the emergency lighting system and as the system can be networked and remotely accessed,
off-site monitoring also becomes an option.
Key features include:
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
E ach PALS panel is fully expandable from 1 to 5 loops using plug-in line drivers
To allow for future expansion, specify 100 devices per driver (Maximum 126) can be
supported by each line driver card allowing one panel to monitor and test 360 devices
A total of 95 PALS panels can then be networked to allow a total system size of 58,850
devices
A range of interface units allow the system to operate with most types of emergency
luminaires including self-contained, central battery and static inverter systems
User friendly software with auto device learn and data loop status for trouble free
setting-up, commissioning and fault finding
Constant communication with luminaires to prove system integrity
Reports charger or mains supply failure within 60 seconds of the event
Loops, zones and luminaires can be disabled to carry out maintenance work
Carries out daily, weekly, quarterly and annual tests – fully automatically - or to
customers requirements
Full system and luminaires test can be manually activated at any time
Reports luminaire number, location and nature of the fault detected
On-board power supplies on the panel to maintain memory if power fails
Designed to fail safe whatever event occurs
Easy to use, tab style questions for programming and operating, On-board alpha numeric
keyboard for easy updates and modifications
External printer available
Multi panel networking, modem communications and PC report and control
Complies with the requirements of PR/EN62034
Specifications PALS™ Control Panel OEL-CA1
Dimensions:
Height 350 x width 340 x depth 115mm
Weight:
10 kg (ex. Batteries)
Mains Supply:
230V 50Hz AC – other voltages are available
Standby:Integral charger for 12V, 6Ah Sealed lead acid battery
(battery not included)
Warning output:
4 programmable short circuit protected monitored outputs
1 amp per output maximum, total current 2 amps
Auxiliary relay:
2 programmable volt free change over outputs
Contacts rated at 5 amps 250V max. per relay
Sensor circuit:
2 wire addressable loop
Loop protection:
Short circuit protection on-board (i.e. without isolators in loop).
Signalling Lines:
1 expandable to 5 via plug-in line driver circuits
Devices per Line:
up to 126 luminaires per line driver
Controls:
Alpha-numeric key pad
Indicators:
20 Test zone LED’s and audible buzzer
Display:
2 line by 40 characters backlit LCD
20 LED zone test indicators
20 LED zone fault indicators
10 LED system indicators
2 LED common fault indicators
Communications:
1 x RS485 serial port (OEL-485 plug in module required)
1 x on-board RS232 port (OEL-004 lead assembly required)
Recommended Cable: For signalling line circuits: Beldon 8762, 8760 or 8719 is recommended.
Addressable emergency lighting systems | 83
PALS™
Self-contained interface units
(OEL-302) monitor and test for:
•
Unswitched mains supply present at all times
•
Battery connected and charging
•
L ight output from the lamp in emergency operation (PALS monitors
the actual lamp light output as current monitoring can be unreliable)
•
Data loop integrity at all times
Central battery system interface units (OEL-307) monitor and test for:
•
Data loop integrity at all times
•
Light output from the lamp in emergency operation
Dimensions Depth 30 x width 50 x length 130 mm
Weight 80 grams
Fixing Centres 120mm
Cat No
Description
Function
OEL-CA1
PALS™ Control Panel
Each PALS™ panel requires at least one OEL-001 driver, with a maximum of 5
OEL-001
PALS™ Line Driver
To allow for future expansion, specify 100 devices per driver (Maximum 126)
OEL-003
9 Pin - 25 Pin D Type Cable
For serial printer connection
OEL-004
RS232 Cable and Gland
Internal cable and gland for local printer and RS232 panel communications
OEL-006
Modem Cabling Kit
Requires OEL-485 and OEL-009 (PC Net 002 software)
OEL-008
PC-Net 001 Upload Software
To allow easy on-site description and test changes via external computer
OEL-009
PC-Net 002 Light Logger Software
Allows full off-site system monitoring and testing facilities
OEL-010
RS232 Cable to Centronics
For parallel printer connection
OEL-108
RS232-RS485 Converter
Converter for use with local RS232 printers
OEL-301
240V AC Current Sensor Interface
Used to detect the current into mains luminaires
OEL-302
Lighting Interface
One required for each maintained/non-maintained luminaire, monitors charge,
mains and light
OEL-304/20
12 Volt 20W Tungsten Interface
Monitors the current in 10W and 20W non-maintained Tungsten luminaires
OEL-304/40
12 Volt 50W Tungsten Interface
Monitors the current in 20W and 50W non-maintained Tungsten luminaires
OEL-305
Central System Interface
One addressable relay required for each static inverter or central battery unit
OEL-307
Light Sensor Interface
Monitors only the lamp light output , one required for each luminaire on central
systems
OEL-485
RS485 Network Card
One required for each panel for local and modem networking of PALS™ panels
16-508
12 Volt 6Ah Sealed Lead Acid Battery Must be installed in each PALS™ control panel
LED-INT
Interface for 4 V LED circuits from 1
to 5 W and 6V 10W tungsten lamps.
84 | Addressable emergency lighting systems
PALS™
System schematic/PALS
Central Battery
or Static Inverter
Modem
RS485 Network
Key
From a singlesite to a global multi national,
PALS puts you in complete control of your
emergency lighting testing requirements.
Slave luminaires
Modem
Self contained
luminaires
(require 230 VAC)
Communication loop
Remote communication
Computer
Printer
Digital self testing systems | 85
A unique fully automatic self testing module
The Digital Self-Test Adapter, DST™, is a unique, fully automatic, independent, selftesting module that complies with the requirements of BS5266 and the forthcoming
International Standard for automatic testing devices, IEC62034 and unlike many is suitable
for incorporation into virtually any Nickel Cadmium, Nickel Metal Hydride VRLA. Battery
powered, self contained emergency lighting luminaire.
DST™
The DST™ is flexible and can be specified to be included in virtually all self contained
luminaires and conversion kits and is ideally suited to retrofitting.
The DST™ is thorough and carries out the monthly, six monthly and yearly test
regime contained within BS 5266 without need for manual intervention. When
the unit detects a fault condition it provides both a visual and an audible alarm
indication (if not required, the audible alarm can be simply disabled when the DST
is commissioned).
DST™ is reliable and even when it has failed its associated luminaire for
duration or light output discrepancies, it will still allow the luminaire to
operate to the best of its ability in its emergency mode.
Additionally, the DST™ has a non-volatile memory so if the power fails the
clock is suspended but the test sequence remains unaltered. When the mains
power is restored they simply carry on from the point at which power failed.
On initial power up the DST’s intelligence allows it to enter a battery preconditioning mode to ensure the batteries are in a suitable condition to supply
sufficient power for emergency operation. Testing, initiation and clock resetting
are carried out via a single discrete push button.
Performance
DST™ Standard Testing programme conforms to the requirements of BS5266-1
Monthly:
1 minute, functional test
6 Monthly:
1 hour, duration test
Annually:
3 hour, full rated duration test
DST™ LED Status Reports are made via a single tri-colour LED.
Continuous GREEN LED:
Mains, battery, charger and previous test correct
Continuous RED LED:
Test in progress
Flashing AMBER LED:
Test fail alarm *
(With optional sound alarm)
LED off: Mains failure or battery faulty
*If a fault is detected the sounder will enter a cycle where it emits an optional audible alarm,
it will then sound every 10 seconds until 4 hours have elapsed and if during this time it has
not been reset or the test reinitiated the sound alarm will repeat the alarm cycle. A single
bleep only will be emitted during manually initiated tests.
Ordering Codes
DST – 2 cell
Suitable for all modules using 2 Cell Batteries
DST – 3 cell
Suitable for all modules using 3 Cell Batteries
DST – 4 cell
Suitable for all modules using 4 Cell Batteries
DST – 5 cell
Suitable for all modules using 5 Cell Batteries
DST – 6 cell
Suitable for all modules using 6 Cell Batteries
DST – 8 cell
Suitable for all modules using 8 Cell Batteries
DST – 10 cell
Suitable for all modules using 10 Cell Batteries
DSTT – 12 V
Suitable for Tungsten Lamps using 12V VRLA Batteries
LED–INT
Interface for 4 volt LED circuits from 1 to 5 watts and 6V 10W
tungsten lamps.
Dimensions Height: 30mm x Length 130mm x Width 50mm,
Fixing centres: 120mm,
Weight: 80 grams.
86 | Electronically controlled emergency lighting
Test Switch
This innovative test switch enables manual testing
Simple to install and use, this innovative test switch enables manual testing of emergency
lighting to current UK and European standards.
There are requirements for all building occupiers and operators to test their emergency
lighting on a regular basis. The ELTS switch enables the short monthly test (10 minutes),
the six monthly 1 hour test and the annual 3 hour test to be carried out
by one person who, having operated the switch, is then free to inspect the
emergency lights for correct operation. At the end of the selected test period,
the mains is automatically re-instated.
ELTS is a cost effective solution for meeting testing requirements and is
installed in the unswitched supply to the emergency lights.
Ordering Codes
Pescara - G
P45
Large exit sign with
a 90 metre viewing
distance
Cat No
Description
ELTS
Emergency Lighting Test Switch
ELT/R5
5 Channel Relay Box
ELT/R10
10 Channel Relay Box
ELT/R15
15 Channel Relay Box
ELT/R20
20 Channel Relay Box