Adaptive ventilation for climate control in a medieval church
Transcription
Adaptive ventilation for climate control in a medieval church
International Journal of Ventilation ISSN: 1473-3315 (Print) 2044-4044 (Online) Journal homepage: http://www.tandfonline.com/loi/tjov20 Adaptive ventilation for climate control in a medieval church in cold climate Margus Napp, Magnus Wessberg, Targo Kalamees & Tor Broström To cite this article: Margus Napp, Magnus Wessberg, Targo Kalamees & Tor Broström (2016) Adaptive ventilation for climate control in a medieval church in cold climate, International Journal of Ventilation, 15:1, 1-14 To link to this article: http://dx.doi.org/10.1080/14733315.2016.1173289 Published online: 18 May 2016. Submit your article to this journal View related articles View Crossmark data Full Terms & Conditions of access and use can be found at http://www.tandfonline.com/action/journalInformation?journalCode=tjov20 Download by: [Tallinn University of Technology] Date: 18 May 2016, At: 04:36 INTERNATIONAL JOURNAL OF VENTILATION, 2016 VOL. 15, NO. 1, 1 14 http://dx.doi.org/10.1080/14733315.2016.1173289 Adaptive ventilation for climate control in a medieval church in cold climate €mb Margus Nappa, Magnus Wessbergb, Targo Kalameesa and Tor Brostro Downloaded by [Tallinn University of Technology] at 04:36 18 May 2016 a Chair of Building Physics and Energy Efficiency, Tallinn University of Technology, Tallinn, Estonia; bDepartment of Art History, Conservation, Campus Gotland, Uppsala University, Uppsala, Sweden ABSTRACT ARTICLE HISTORY Old medieval churches hold objects of great historical and cultural value: organs, altars, paintings. But they have no systems for indoor climate control or the church may be heated only at services. These conditions are inadequate for the preservation of cultural heritage. The objective of this paper is to assess an adaptive ventilation (AV) solution in a church for reduction of the relative humidity (RH) in an unheated church to prevent mould growth and disintegration of wooden parts. The operation principle of the system is to ensure ventilation in the church when water vapour content in the outdoor air is lower than that indoors, to lower the RH in the church. A case study in Hangvar Church in Gotland, Sweden, was conducted to test the performance of AV to reduce the RH in the church. Field measurements showed that AV has a positive impact on the indoor RH of the church. During the measurement period without climate control, the RH in the church was higher than 70% of 98% of the time; with AV, the indoor RH was higher than 70% only 78% of the time. Building simulation was carried out to test the performance and energy consumption of AV under different conditions. The simulations showed that auxiliary heating and airflow rate both have high impact on the system performance. The higher the heating power, the more effective the system is; thus, lower airflow rates are needed. Infiltration has also high impact on the system performance: the lower the infiltration rate, the better the AV performance is. Received 15 November 2015 Accepted 1 March 2016 KEYWORDS Adaptive ventilation; indoor climate; climate control; energy performance; historic building; church 1. Introduction 1.1. Climate control in historic churches The indoor climate is one of the most important factors in the preservation of medieval churches and their interior. Most rural churches have no climate control or very simple systems when heated only at services. In between services, the building is left unheated or at a background temperature. Thus, the indoor climate challenge for these churches is twofold: to provide comfort for visitors during services and to maintain a good preservation climate when the church is not in use. This paper deals mainly with the latter. With none or very low heating between services, the indoor climate in medieval churches is dictated by the outdoor climate and the hygrothermal inertia of the massive structures. As a result, the indoor climate is generally quite stable with slow seasonal changes in temperature and humidity. CONTACT Targo Kalamees targo.kalamees@ttu.ee © 2016 Informa UK Limited, trading as Taylor & Francis Group 2 M. NAPP ET AL. Downloaded by [Tallinn University of Technology] at 04:36 18 May 2016 During winter, the relatively low thermal resistance of the building envelope causes low wall surface temperatures (which increases relative humidity (RH)) and high energy costs for heating. Moisture transport into the building from driving rain and ground sources often results in a considerably higher moisture ratio (MR, g/kg) inside. Many churches face problems related to high RH, increasing risk of damages of fungi, mould and rot and insects (Kalamees et al., 2015; Scheiding, Plaschkies, & Weiß, 2008). Strong RH fluctuations may cause flaking of paint and wood cracking (Mecklenburg, Tumosa, & Erhardt, 1998). The conventional way to reduce RH is through conservation heating or dehumidification €m & Larsen, 2012), (Kurabuchi, Ogasawara, Ochiai, & Lee, 2013). However, these solutions are (Brostro quite costly both in terms of investments and energy demand. A cost-efficient method for climate control is needed to lower the humidity in the church for reduction of biological activity and condensation on the surfaces. 1.2. Adaptive ventilation Ventilation may seem as an obvious and simple solution to reduce humidity levels. However, air exchange in a historic building through infiltration or ventilation has a complex effect on the indoor climate in general and on humidity in particular. Depending on the outdoor and indoor climate conditions, air exchange can either increase or decrease the RH in a building. A classic example is an unheated church where doors and windows are opened in the spring to warm the building up. Inside the building, the warm outside air is cooled off and the RH increases. Hygroscopic materials, such as plaster and wood, are saturated and condensation may occur on cold surfaces. On the other hand, when the outdoor climate is drier than that inside, ventilation can have a significant positive effect by decreasing the humidity level in a church. The controlling principle of adaptive ventilation (AV) is to ventilate only when the MR inside the building is higher than that outside. It is equally important not to ventilate when the MR outside is higher. Thus, both air tightness and ventilation must be controlled and adapted through the use of mechanical fans and dampers controlled by indoor and outdoor climate sensors. A recent development is adaptive or controlled ventilation, a potentially low-energy and low impact option, which has been tested in case studies. Adaptive ventilation was implemented in the Torhalle in Lorsch, Germany, where condensation on the wall paintings was avoided by mechanical fans controlled by indoor and outdoor climate sensors (Reiss & Kiessl, 1986). Its seasonal use was tested in the Antikentempel in Potsdam-Sanssouci Park to prevent mould growth on the walls and ceiling. From May to September, a fan mounted in the skylight provided AV (Brockmann, 2010). A €m, Hagentoft, & Wessberg, 2011), concase study in a historical house in Gotland, Sweden (Brostro firmed that AV is particularly useful when there are internal moisture sources in the building, resulting in absolute humidity levels higher than those outside and the system produced a significant drying effect. In addition, mould risk was kept at an acceptable level for most of the time. Antretter et al. (2013) have investigated AV by means of computer simulations. AV has been implemented and €m, 2013). assessed in a number of churches in Denmark and Sweden (Larsen, Wessberg, & Brostro In the cases above, the control systems were custom designed for each building. However, due to the covariance of temperature and absolute humidity in the outside air, the effect on RH inside a building is limited in a short term. In a typical diurnal cycle, the temperature will be lower outside when the moisture ratio (MR, g/kg) is higher inside and the fan is running. This means that the ventilation has a cooling effect that tends to increase RH, even though at the same time, moisture is removed from the building. In this paper, a commercial solution intended for cold attics and crawl spaces under houses (Hagentoft & Kalagasidis, 2010) is used to assess AV performance in Hangvar Church on the island of Gotland. In order to allow for parameter studies and to explore the potential, additional simulations were carried out to find out how different airflow rates, heating powers and infiltration affect AV performance in a medieval church. INTERNATIONAL JOURNAL OF VENTILATION 3 2. Methods 2.1. Hangvar Church Hangvar Church on North Gotland, Sweden (Figures 1 and 2), was built in the thirteenth century. The construction is typical of Gotland churches, with outer walls and vaults made of lime stone in lime mortar and a wooden roof construction with tiles. The total volume of the church is 1000 m3 and the total floor area 144 m2. The church is used on an average once a month, mainly for weddings and funerals. The church is intermittently heated for services and unheated in between. Downloaded by [Tallinn University of Technology] at 04:36 18 May 2016 2.2. Measurements RH and temperature were measured in the middle of the church hall (Figure 2) with a Testo data logger at a one-hour interval. Measurements were taken over two time periods: Period 1: one full year before installation of AV; from September 2010 to August 2011 Period 2: one full year with the AV system running; from September 2012 to August 2013 Outdoor temperature, RH and solar radiation for the same periods were obtained from the Swedish Meteorological and Hydrological Institute (SMHI) in Visby Airport. Infiltration measurements were conducted in the church (Mattsson, 2013) by the fan pressurisation method (EN 13829, 2000) and by the low pressure pulse technique (Cooper, Etheridge, & Smith, 2007). The AV system (see Figure 3) was installed in July 2012. The system used is a control system mainly intended for ventilation of attics (Hagentoft & Kalagasidis, 2010), consisting of a ventilator set-up, a control unit and two sensors; an indoor sensor and an outdoor sensor for temperature and RH measurements. The system calculates and compares the moisture ratio both indoors and outdoors in real Figure 1. Hangvar Church, exterior (a) and interior (b). Downloaded by [Tallinn University of Technology] at 04:36 18 May 2016 4 M. NAPP ET AL. Figure 2. Plan of the church and positions of indoor climate sensors and loggers. time and activates the fan if the outdoor moisture ratio is 10% lower than the indoor value. The system is located in the tower staircase and the inlet air is taken from an opening in the tower wall. The inlet air is supplied to the church via the fan through a duct in a temporary tower door. From September 2012 to December 2012, the speed of the ventilator was set to run proportional to the difference between the indoor and the outdoor moisture ratio, starting at 50% of max speed. From January 2013, the speed of the ventilator was set to run at 100% any time the moisture ratio was 10% lower outdoors than indoors. Figure 3. Adaptive ventilation principle (left) and its installation in Hangvar Church (right). INTERNATIONAL JOURNAL OF VENTILATION 5 The system composed of two electric heaters with a total power of 1800 W is also equipped with photovoltaics (PV) panels (Figure 1a). Electricity collected in the daytime is sold to the grid and at night-time when the outdoor moisture content is usually lower than that indoors and the system is operational, the collected energy is bought back and used for the heaters. Mould risk is assessed in relation to the isopleth curve RHLIM I (Sedlebauer, 2001) which is the temperature-dependent lowest limit in RH where mould growth can occur on biological recyclable materials. Downloaded by [Tallinn University of Technology] at 04:36 18 May 2016 2.3. Simulation The envelope of the church has high hygrothermal inertia; therefore, it is essential to use dynamic computer simulation of heat, air and moisture of the whole building to calculate the church’s indoor €rsell et al., 1999; Sahlin, 1996) was used for indoor climate and energy usage. The software IDA-ICE (Bjo climate and energy analysis. This software has been meticulously validated (Achermann, 2000; Achermann & Zweifel, 2003; Kropf & Zweifel, 2001; Travesi, Maxwell, Klaassen & Holtz, 2001) and allows the modelling of a multi-zone building, internal and solar loads, outdoor climate, heating, ventilation and air conditioning (HVAC) systems, dynamic simulation of heat transfer and air flows. It is widely applied in energy performance and indoor climate calculations as well as in those of renovation of indoor climate, and energy performance of buildings (Alev et al., 2014; Arum€agi & Kalamees, 2014; Jokisalo et al., 2008; Kuusk, Kalamees & Maivel, 2014; Napp & Kalamees, 2015; Pavlovas, 2004; Woloszyn, Kalamees, Olivier Abadie, Steeman, & Sasic Kalagasidis, 2009). The indoor climate and energy simulation model for Hangvar Church enabled simulation of the performance of indoor temperature and humidity, energy use for heating and ventilation, flow of air, heat and moisture through the external walls and humidity generation indoors. The simulation model consists of six zones: hall, choir, sacristy, porch, tower and the well-ventilated attic. Thermal and hygric properties for heat, air and moisture (HAM) simulation are shown in Tables 1 and 2. In the simulation model of the church’s hall, for four external walls, the common thermal wall model was replaced with the hygrothermal (HamWall) model (Kurnitski & Vuolle, 2000) to calculate the moisture flow through the building envelope. The walls were divided into 18 layers (Table 3) to calculate the flow of moisture in the walls. The wooden interior parts, furniture and structures in the church were taken into account by an additional 100 m2 wooden surface. The simulation model was calibrated based on indoor and outdoor measurements between September 2012 and September 2013 (Figure 10). One-pane clear glazing was used with a solar factor of 0.85 and heat transmittance of 5.8 W/(m2K). 3. Results 3.1. Field measurements of AV performance Figure 4 shows the indoor climate during one-year periods before (left) and after (right) the installation of AV. A significant decrease in RH was achieved. The average RH decreased from 81% to 75%. See Table 4 for further details. Table 1. Structures, materials and their thermal properties. Materials (from inside Structure to outside) Thickness d (m) External wall Render 0.025 Lime stone masonry 1.45 Render 0.025 Render 0.025 Attic floor Limestone arch 0.4 Render 0.025 Floor Lime stone slab 0.25 Soil 1.0 Door and furniture Wood 0.05 Thermal conductivity λ (W/(m¢K)) 0.8 1.2 0.8 0.8 1.2 0.8 1.2 2.0 0.13 Specific heat c (J/(kg¢K)) 790 880 790 790 880 790 880 1000 1.0 Density r (kg/m3) 1800 2300 1800 1800 2300 1800 2300 2000 510 6 M. NAPP ET AL. Table 2. Hygric properties of materials. Water vapour transmission1 2 Material d0 (m /s) B 6.4 £ 10¡7 Limestone 1.89 £ 10¡7 3.8 £ 10¡6 Render 2.929 £ 10¡6 2.9 £ 10¡6 Wood 7.3 £ 10¡7 C 4.7 10 4.75 RH1 (%) 82 20 84 Sorption isotherm2 w1 (kg/m3) RH2 (%) 80 100 57 100 72 100 w2 (kg/m3) 100 82 100 Water vapour dv D d0 C B(RH/100)C, m2/s, where d0, m2/s, is if RH D 0%, B and C are constants and RH, %. Water vapour capacity relation to RH is given with three lines: start: w D 0kg/m3, RH D 0%, first breakpoint: w1; RH1, second breakpoint: w2; RH2 D 100% 1 2 Downloaded by [Tallinn University of Technology] at 04:36 18 May 2016 Table 3. Discretisation of the external wall. Number of layer Thickness (mm) C C Render 1 2 3 4 1 2 5 6 5 6 6 6 7 10 8 100 External wall Limestone 9 10 11 12 614 614 100 10 13 6 14 6 15 6 Render 16 17 5 2 P P 18 1500 18 1 The use of a ventilation system can increase RH fluctuations. Both Figures 4 and 5 indicate that the fluctuations have increased in Period 2 compared to Period 1. The standard deviation on the fluctuations has increased from 3.5 to 5.2. According to the European standard (EN 15757, 2010), fast RH fluctuations less than §10% RH from the 30-day running average are considered safe. Figure 4 shows that the number of events where RH is outside the §10% limits has increased in Period 2. Figure 4. Left, measurements from Period 1, September 2010 to August 2011, no climate control by AV. Right, measurements from Period 2, September 2012 to August 2013, with AV. In addition to hourly values also 30 days running average and §10% limits according to EN15757 (2010). Table 4. Field measurements statistics. Average moisture Average Percentage of time Average over 70% RH temperature ( C) ratio DMR (g/kg) RH (%) Max RH Min RH (%) Autumn: September, October, November Period 1 11.1 82 93 74 100 Period 2 11.3 1.19 77 90 63 89 Winter: December, January, February Period 1 3.4 80 91 66 93 Period 2 3.3 1.27 75 96 54 78 Spring: March, April, May Period 1 6.8 80 90 63 100 Period 2 5.3 1.09 73 99 54 68 Summer: June, July, August Period 1 17.0 83 93 68 100 Period 2 17.0 1.03 74 92 56 79 Annual average Period 1 9.6 81 96 63 98 Period 2 9.3 1.20 75 99 54 78 Percentage of time over RHLIM 52 19 1 0 0 1 68 19 31 8 INTERNATIONAL JOURNAL OF VENTILATION 7 Downloaded by [Tallinn University of Technology] at 04:36 18 May 2016 Figure 5. Mould risk without (left) and with (right) AV assessed with the isopleth curve LIM I (Sedlebauer, 2001). Figure 6. Duration graph of critical limit for mould growth RH/RHLIM I for Period 1 (red) and Period 2 (black), left. Seven-day running average of the difference between indoor MR and outdoor MR, right. Figure 5 shows that with AV, though significantly reduced, mould risk is not eliminated. The time over the critical limit was reduced from 31% to 8% of the time over one year. As can be seen from Figure 6, even a small reduction in RH can be important. Suppose the objective is to keep RH below RHLIM I, the duration graph shows that AV reduced operational time for an auxiliary active humidity control, i.e. a dehumidifier, from 3750 hours to 1450 hours. Figure 7. Occasions when RH is above the critical limit RH/RHLIM. Without (left) and with (right) climate control by AV. 8 M. NAPP ET AL. Downloaded by [Tallinn University of Technology] at 04:36 18 May 2016 Table 5. Infiltration measurements in the church. Q50 Q50/Aenvelope (l/s) (l/(s∙m2)) Fan pressurisation method, higher indoors 707 0.92 Fan pressurisation method, lower indoors 654 0.85 Low pressure pulse Combined Q4 Adaption-constant Adaption constant, Equivalent leakage (L/s) (L/(s∙Pan)) CL (n [-]) area (with 4 Pa) (m2) 143 59.7 0.632 139 59.2 0.614 131 0.051 54.4 0.648 RH must be over the critical limit for a number of days for mould to grow (Sedlebauer, 2001). Without climate control by AV, the average duration above the critical limit was 72 hours (3 days) and the longest period was 826 hours (34.4 days). With AV in operation, the average duration was 32 hours (1.3 days) and the longest period as 134 hours (5.6 days), see Figure 6. This is probably the most important effect of AV, see Figure 7. In addition to the measurable effects shown above, visitors and people working in the church felt that the indoor air quality had improved, mainly due to the elimination of bad smell. The infiltration measurements with the fan pressurisation method (EN 13829, 2000) and the low pressure pulse technique (Cooper et al., 2007) are presented in Table 5. The average q50 in the church is 0.89 l/(s∙m2) and the equivalent leakage area at 4 Pa is 0.051 m2. Figure 8 shows the moisture ratio inside and outside the building with and without AV. It can be seen that the moisture excess is reduced due to AV. The data in Table 4 show that the reduction of RH levels is mainly due to a reduction of MR since the difference in average temperature for the two periods is relatively small. The yearly average of MR sank from 6.5 g/kg to 5.9 g/kg, which is a reduction of moisture by 9%. During Period 2, September 2012 to August 2013, 1100 kg of water was removed from the church. This means that in addition to the short-term effects discussed above, there is a possible long-term effect of drying out the massive building envelope. The energy needed to run the fan is marginal. During one year, the fan itself used only 250 kWh electricity. This gives a drying efficiency of 0.22 kWh per kg. Figure 9 shows the energy generated by the PV panels and the energy used by the inlet air heaters. During Period 2, the PV panels generated sufficient energy to preheat the inlet air 9 of the 12 months. When the fan was operating at full speed and solar energy was available, the heaters gave the inlet air a temperature increase of 11 C, which was generally sufficient to mitigate the cooling effect that can counteract the positive effect of removing moisture from the building. The total amount of energy used for preheating of the inlet air during Period 2 was 2066 kWh (Wessberg, €m, 2014). Larsen, & Brostro Figure 8. Seven-day moving average of both indoor and outdoor MR. Without AV to the left and with AV to the right. Downloaded by [Tallinn University of Technology] at 04:36 18 May 2016 INTERNATIONAL JOURNAL OF VENTILATION 9 Figure 9. Energy produced and consumed during the period with AV. The case study has shown that AV is potentially an energy-efficient method to reduce RH in unheated historic buildings. In order to facilitate proper design and operation of adaptive systems, it is necessary to know the capacity of the fan, air tightness of the building and how heat input affects the overall performance. This will be addressed by indoor climate and energy simulation. 3.2. Simulation 3.2.1. Calibration of the indoor climate and energy simulation model IDA-ICE simulation program was used for a parameter study to show the influence of different AV parameters on the indoor climate and energy performance. The simulation model of the indoor climate and energy performance of Hangvar Church was calibrated for the AV test period from September 2012 to August 2013. In general, good agreement was found between the measured and simulated climate for the period (Figure 10). The simulated temperature shows coincidence with the measured temperature. The higher peaks in the measured temperature resulted from an additional heater in the church, which was used during services, weddings and funerals. Also, the simulated moisture content shows high similarity with the measured moisture content. During the simulation, the heating unit added to the system was assumed to be in operation all the time when AV was working. In the AV simulation, the inlet air temperature was limited to <30 C to avoid too high inlet temperatures and excessive dryness of the inlet air. The higher the heating Figure 10. Comparison of measured and calculated temperature (left) and moisture ratio (right) in Hangvar Church with adaptive ventilation. 10 M. NAPP ET AL. Downloaded by [Tallinn University of Technology] at 04:36 18 May 2016 Figure 11. Left, efficiency of AV with different airflows and heating powers. Right, energy use of AV per year with different air flows and heating. power, the higher the effect of AV is. At the maximum tested heating power of 20 W/m2, the simulation showed the highest effect of drying the church (Figure 11, left). The efficiency of AV also depends on the airflows. With increasing airflows, the temperature of the inlet air decreases. At very low airflows, AV is not sufficient to ensure lower RH levels. With no heating or low heating power, AV is most effective in the range of 1.2 1.6 l/(s∙m2). Lower airflow rates are more efficient when more heating is applied. At a heat input of 10 W/m2, the most effective airflow rate is 0.8 l/(s∙m2) and for 20 W/m2 it is 0.7 l/(s∙m2). The highest heating power of 20 W/m2 (Figure 11, left) is most effective, as it decreases the RH most. In Figure 11 (right), the bottom axis shows the time in percentiles when the RH is higher than 70%. The most effective airflows are also the most energy consuming, as they use more power to heat up the church, thus decreasing the indoor RH. With a heating power of 20 W/m2, the most power consuming and effective airflow rate is 0.8 l/(s∙m2), at RH over 70% for 6.5% of the year (Figure 11, right). Figure 11 presents only the heating capacity for the AV. With the highest heating power of 20 W/m2 and airflow of 0.8 l/(s∙m2) and the fan SFP of 1.5 the energy needed for the fan operation would be 12% of the total heating consumption. The dependence of AV performance on infiltration is presented in Figure 12. Both an effective leakage area and an air leakage rate q50 are given. AV is very dependent on infiltration, especially Figure 12. Adaptive ventilation with different infiltration rates. INTERNATIONAL JOURNAL OF VENTILATION 11 near lower infiltration values. Thus, the AV performance can be improved by lowering the air infiltration rate. With AV, the fluctuation of temperature and RH tends to increase. With the system turned off, the maximum hourly temperature fluctuation was 0.5 Ch. With AV and 1.2 l/(s∙m2), the maximum hourly temperature fluctuation was 1.2 C∙h. Additional heating increases the temperature fluctuations even more. At 0.8 l/(s∙m2) and 10 W/m2, maximum hourly temperature fluctuation was 1.6 C∙h and at 0.8 l/(s∙m2) and 20 W/m2, it was 2.4 C∙h. The maximum hourly RH fluctuation without the system was 4.1% with AV, 1.2 l/(s∙m2) and with no heating, it was 6.5%. Additional heating of 20 W/m2 and 0.8 l/(s∙m2) increases the hourly RH fluctuation to 9.8%. Downloaded by [Tallinn University of Technology] at 04:36 18 May 2016 4. Discussion This case study shows that AV improved the indoor climate in the church. The time over the critical mould limit was reduced from 31% to 8% (Table 4) and the time needed for active climate control was reduced by 60%. Most importantly, the continuous time periods over the critical limit were reduced substantially. Even considering that measurements were made in different years and under different outdoor climate conditions, the improvements in the indoor climate are significant. During one year, around 1100 kg of water has been removed from the building, which indicates that, in addition to the diurnal effects, there may also be a long-term effect where the building envelope slowly dries out. Continued monitoring over several years is needed for further investigations. The case study shows that AV can be a low-cost and low-energy option as compared to other types of humidity control, such as humidification and conservation heating. However, in the case study, even AV combined with auxiliary heating was not sufficient to eliminate mould risk completely. The parameter study by use of simulations for AV showed a potential to enhance the performance by making the building more air tight and by controlling the airflow rate. The higher the heating unit, the better the AV performs; however, even a small heat input gives a significant improvement (Figure 11, left). The most effective airflow rate under heating not applied is 1.5 l/(s∙m2), under heating applied, the optimal airflow rates decrease (Figure 11). The reason is that with higher heating power applied, the system would start working more as a heater just to heat up the church and larger airflow rates would import too much cold outside air to the church. With the largest heating power, 20 W/m2, the optimal airflow rate is 0.7 l/(s∙m2). At higher airflow rates, the inlet air is not sufficiently heated. In terms of RH control, the most effective solutions are also the most energy consuming. Adaptive ventilation is also influenced highly by infiltration (Figure 12). The lower the infiltration rate, the better the AV performance is. With infiltration rates lower than 2.0 l/(s∙m2), the performance of AV is very highly influenced by small changes in infiltration rates. Infiltration field measurements with the fan pressurisation method (Table 5) show the infiltration of 0.89 l/(s∙m2) in the church which is low enough to see the results of the AV performance (Figure 12). However, even small improvements in the infiltration would increase AV performance. Both the case study and the simulations showed that the performance of AV has limitations. Mould risk levels can be reduced significantly, but even with an optimal design, they cannot be completely eliminated. The remaining load for climate control is small and of short duration. Since it is limited to the warmer part of the year, it can be managed with a small condensing dehumidifier. The study of AV in Hangvar Church, as well as the studies in two churches in Germany (Antretter et al., 2013) and in a church in Estonia (Napp & Kalamees, 2015), showed that the system can increase the fluctuation of temperature and RH in the church. Thus, in the AV design, it is necessary to take into account that the system may increase RH fluctuations. However, the RH fluctuations caused by the AV system are small as compared to the variation of RH during intermittent heating for services. 12 M. NAPP ET AL. Downloaded by [Tallinn University of Technology] at 04:36 18 May 2016 5. Conclusion The aim of the study was to improve the indoor climate in the unheated church by the use of an AV system. In the non-climate control period, our measurements showed high RH rates, which could damage the church artwork and valuables. We tested the AV starting from September 2012 until August 2013. The test period showed large improvements over the RH rates in the church, by lowering the annual average RH of 81% measured in the non-climate control period to 69% measured during the AV test period. In addition to the test in the church, simulations done with the IDA-ICE program for Hangvar Church showed that heating power and airflow have impact on the AV performance. The larger the heating unit, the better the AV performance is. The most efficient airflow rate at heating applied is 0.7 0.8 l/(s∙m2). The relatively low amount of used energy for preheating of the inlet air does not justify the investment of PV panels (Wessberg, 2014). As AV is largely influenced by the infiltration rate, the performance of AV depends on air tightness, which in turn can be improved to some extent for most churches. Acknowledgments This study utilises the measurements collected in the project ‘Sustainable Management of Historic Rural Churches in the Baltic Sea Region’ financed by the Central Baltic Interreg IV A and simulations made in the project IUT1¡15 ‘Nearly-zero energy solutions and their implementation on deep renovation of buildings’ financed by the Estonian Ministry of Education and Research. Disclosure statement No potential conflict of interest was reported by the authors. Funding This work was supported by Central Baltic Interreg IV A [grant Sustainable Management of Historic Rural Churches in the Baltic Sea Region], Estonian Centre of Excellence in Zero Energy and Resource Efficient Smart Buildings and Districts, ZEBE [grant number TK146] funded by the European Regional Development Fund, and by the Estonian Research Council, with Institutional research funding [grant number IUT1-15]. Notes on contributors Margus Napp is a researcher in Chair of Building Physics and Energy Efficiency, Tallinn University of Technology, Tallinn, € His research focuses on energy efficiency in providing indoor cliEstonia and an engineer in design agency IB Aksiaal OU. mate of historically buildings. Magnus Wessberg is a lecturer at Department of Art History, Conservation at Uppsala University, Campus Gotland, Sweden. With a background in engineering, his research focuses on energy efficient way to control temperature and humidity to create a good indoor climate for preservation of historically important buildings. Targo Kalamees is a professor of Building Physics and head of Chair of Building Physics and Energy Efficiency, Tallinn University of Technology, Tallinn, Estonia. His research focuses on building physics, renovation of buildings, energy performance and indoor climate of buildings. Tor Brostr€ om is a professor in Conservation at Uppsala University, Campus Gotland, Sweden. With a background in engineering, his research focuses on indoor climate and energy conservation in historic buildings. He is coordinator of the Swedish national research programme on energy efficiency in historic buildings. INTERNATIONAL JOURNAL OF VENTILATION 13 Downloaded by [Tallinn University of Technology] at 04:36 18 May 2016 References Achermann, M. (2000). Validation of IDA ICE, Version 2.11.06 With IEA Task 12 Envelope BESTEST. Hochschule Technik C Architektur Luzern. HLK Engineering. Achermann, M., & Zweifel, G. (2003). RADTEST Radiant heating and cooling test cases. A report of Task 22, Subtask C. Building Energy Analysis Tools. Lucerne School of Engineering and Architecture. € Eskola, L., Arum€agi, E., Jokisalo, J., Donarelli, A., Siren, K., … Kalamees, T. (2014). Renovation alternatives to Alev, U., improve energy performance of historic rural houses in the Baltic Sea region. Energy and Buildings, 77, 58 66. Antretter, F., Kosmann, S., Kilian, R., Holm, A., Ritter, F., & Wehle, B. (2013). Hygrothermal behavior, building pathology and durability. In Building pathology and rehabilitation (Vol. 1, pp. 93 111). Berlin Heidelberg: Springer Berlin Heidelberg. doi:10.1007/978-3-642-31158-1 Arum€agi, E., & Kalamees, T. (2014). Analysis of energy economic renovation for historic wooden apartment buildings in cold climates. Applied Energy, 115, 540 548. Bj€ orsell, N., Bring, A., Eriksson, L., Grozman, P., Lindgren, M., & Sahlin, P. (1999). IDA indoor climate and energy. Proceedings of the IBPSA Building Simulation ’99 Conference, Kyoto. Brockmann, T. (2010). Langzeiterfahrungen mit dezentralen Kleinanlagen zur Feuchtegesteuerten Zwangsl€ uftung [Longterm experience with decentralized small plants for humidity-controlled mechanical ventilation]. Klima und Klimastabilit€ at in historichen Bauwerken, Wissenschaftlich-Techniche Arbeitsgemeinschaft f€ ur Bauwerkserhaltung e.V. Arbeitsgruppe 6.11 [Climate and climate stability in historic buildings, Scientific Technical Association for Building Preservation e.v. working group 6.11], pp. 59 76. Brostr€ om, T., Hagentoft, C.-E., & Wessberg, M. (2011). Humidity control in historic buildings through adaptive ventilation: A case study. Proceedings of the 9th Nordic Symposium on Building Physics, Tampere. Brostr€ om, T., & Larsen, P. (2012). Climate control strategies for occasionally used churches. Heat, dehumidify, ventilate or do nothing. In E. Dahlin (Ed.), Proceedings of the 2nd European Workshop on Cultural Heritage Preservation (EWCHP) (pp. 124 130). Kjeller: Norwegian Institute for Air Research (NILU). Cooper, E.W., Etheridge, D.W, & Smith, S. (2007). Determining the adventitious leakage of buildings at low pressure. Part 2: Pulse technique. Building Services Engineering Research and Technology, 28, 81 96. EN 13829. (2000). Thermal performance of buildings Determination of air permeability of buildings Fan pressurization method. Bruxelles: European Committee for Standardization CEN. EN 15757. (2010). Conservation of cultural property Specifications for temperature and relative humidity to limit climateinduced mechanical damage in organic hygroscopic materials. Bruxelles: European Committee for Standardization CEN. Hagentoft, C.-E., & Kalagasidis, A.S. (2010). Mold growth control in cold attics through adaptive ventilation: Validation by field measurements. In Buildings XI: Thermal performance of exterior envelopes of whole buildings (p. 8). Florida, USA (CD-Rom). Jokisalo, J., Kalamees, T., Kurnitski, J., Eskola, L., Jokiranta, K., & Vinha, J. (2008). A comparison of measured and simulated air pressure conditions of a detached house in a cold climate. Journal of Building Physics, 32(1), 67 89. Kalamees, T., V€ali, A., Kurik, L., Napp, M., Arumagi, E., & Kallavus, U. (2015). The influence of indoor climate control on risk for damages in naturally ventilated historic churches in cold climate. International Journal of Architectural Heritage. Retrieved from http://dx.doi.org/10.1080/15583058.2014.1003623 Kropf, S., & Zweifel, G. (2001). Validation of the building simulation program IDA-ICE According to CEN 13791 „thermal performance of buildings - calculation of internal temperatures of a room in summer without mechanical cooling general criteria and validation procedures“. Hochschule TechnikCArchitektur Luzern. HLK Engineering. Kurabuchi, T., Ogasawara, T., Ochiai, H., & Lee, S. (2013). A study on the indoor environment of the main building of the National Museum of Western Art, in Japan, for the development of a retrofit scheme. International Journal of Ventilation, 12(2), 119 128. Kurnitski, J., & Vuolle, M. (2000). Simultaneous calculation of heat, moisture, and air transport in a modular simulation environment. Proceedings of the Estonian Academy of Sciences Engineering, 6(1), 25 47. Kuusk, K., Kalamees, T., & Maivel, M. (2014). Cost effectiveness of energy performance improvements in Estonian brick apartment buildings. Energy and Buildings, 77, 313 322. Larsen, P., Wessberg, T., Brostr€ om, T. (2013). Adaptive ventilation for occasionally used churches. In A. Troi & E. Lucchi (Eds.), Proceedings of the 3rd European Workshop on Cultural Heritage Preservation (EWCHP) (pp. 55 62). Bolzano: European Academy of Bozen/Bolzano (EURAC). Mattsson, M. (2013). Resultat av luftl€ackagem€atningar i Hangvar & Fide kyrkor. [Results of measurements in air leakage Hangvar & Fide churches]. Report. Sweden: University of G€avle, Academy of Technology and Environment. Mecklenburg, M.F., Tumosa, C.S., & Erhardt, D. (1998). Structural response of painted wood surfaces to changes in ambient relative humidity. In V. Dorge, F.C. Howlett (Eds.), Painted wood: History and conservation (Part 6: Scientific research) (pp. 464 483). Los Angeles: The Getty Conservation Institute. Napp, M., & Kalamees, T. (2015). Energy use and indoor climate of conservation heating, dehumidification and adaptive ventilation for the climate control of a medieval church in a cold climate. Energy and Buildings, 108(1), 61 71. Pavlovas, V. (2004). Demand controlled ventilation: A case study for existing Swedish multifamily buildings. Energy and Buildings, 36(10), 1029 1034. Downloaded by [Tallinn University of Technology] at 04:36 18 May 2016 14 M. NAPP ET AL. Reiss, J., & Kiessl, K. (1986). Feuchtetechnicshe Untersuchung an Aussenw€ ande der Torhalle Lorsch [Moisture investigation on outer walls of the gate hall Lorsch]. IBP-Bericht FtB-1/1986. Holzkirchen: Fraunhofer Institut f€ ur Bauphysik. Sahlin, P. (1996). Modelling and simulation methods for modular continuous system in buildings. Stockholm: KTH. Scheiding, W., Plaschkies, K., & Weiß, B. (2008). Mould on organs and cultural heritage objects. Investigations in eight churches in Saxony. In J. Gril (Ed.), Wood Science for Conservation of Cultural Heritage. International Conference held by COST Action IE0601. Braga: Firenze University Press. Sedlebauer, K. (2001). Prediction of mould manifestation on and in building parts (PhD thesis). University of Stuttgart, Stuttgart. Travesi, J., Maxwell, G., Klaassen, C., & Holtz, M. (2001). Empirical validation of Iowa energy resource station building energy analysis simulation models. International Energy Agency (IEA), Solar Energy & Cooling Programme. A report of task 22, subtask a building energy analysis tools project A.1 empirical validation, June 2001. Wessberg, M., Larsen, P.K., & Brostr€ om, T. (2014, June). Solar energy augmented adaptive ventilation in historic buildings. In J. Arfvidsson, L.-E. Harderup, A. Kumlin, & B. Rosencrantz (Eds.), Proceedings of the 10th Nordic Symposium on Building Physics (pp. 648 655). Lund, Sweden. Woloszyn, M., Kalamees, T., Olivier Abadie, M., Steeman, M., & Sasic Kalagasidis, A. (2009). The effect of combining a relative-humidity-sensitive ventilation system with the moisture-buffering capacity of materials on indoor climate and energy efficiency of buildings. Building and Environment, 44(3), 515 524.