Builder`s Manual for Ortal Fireplaces
Transcription
Builder`s Manual for Ortal Fireplaces
your life. your fire. Builder's Manual for Ortal Fireplaces [[ Table of Contents 1. Introduction 2 2. Checklist 3 3. Model Firebox Clearances 4 4. General Guidelines 5 5. Heat Release and Air Intake 7 A. Reveal 8 B. Louver 11 C. Sprinkler Clearances at Heat Release 13 6. Metal Framing 14 A. Shelf Details 21 B. TV Detail 22 i. Flush 22 ii. Recess 23 7. Wood Framing 24 A. TV Detail 30 i. Flush 30 ii. Recess 31 8. Finishing Details 32 A. Quartz 33 B. Wood paneling 34 C. Brick Veneer 35 D. Mantel Clearances 37 E. Stone Finish & Hearth 38 F. Wood Hearth Extensions 39 G. Inside Corner Clearances 40 H. Clearance to ceiling 42 9. Vent Pipe Clearances 43 10. Venting Diagrams 44 11. Sconce Cap Detail 47 [[ Introduction [[ Checklist Congratulations, your customer has entrusted you with building the world’s The heat produced by an Ortal fireplace requires particular attention to materials finest fireplace into your project. and details to assure a safe installation. Because the fireplace is the room’s focal point, your customer will expect a high level of craftsmanship. However, by Begin by reading this Builder’s Manual and shop drawings from Ortal, reviewing the putting your best craftsmen on the job and following these instructions, we are architect’s or designer’s drawings and specifications, and inspecting location where confident you will feel the same pride we do in every Ortal fireplace. fireplace will be installed. You will then be ready to coordinate the installation and We recommend that an Ortal dealer install the fireplace whenever practical. Installation must comply with the current edition of the Ortal Installation Manual and shop drawings provided by Ortal. It is up to you, however, to build the cavity that will enclose the fireplace. There are several methods for building the cavity: 1. Metal Framing – See page 14: Metal framing is also known as light-gage or cold-formed steel studs. 2. Wood Framing – See page 24: The interior of the cavity must be covered with gypsum board to protect combustible materials. 3. Non-Combustible: Cavities constructed of brick, concrete masonry units, or plaster on metal framing and lath should be based upon metal framing requirements. 2 [[ GAS TYPE (PROPANE OR NATURAL GAS) [[ MEDIA OPTIONS: • Ceramic Stones (large/small, white/grey) • Branch Set schedule with your Ortal dealer, the mechanical contractor, electrical contractor, drywall, AV home automation and other trades that will be involved. [[ FIREPLACE MODEL AND SIZE We look forward to working with you. ® your life. your fire. • Log Set • Glass [[ OPTIONAL FEATURES: [[ HEAT RELEASE – AIR RETURN TO ROOM: Size of heat release verified and located. See page 5. [[ AIR INTAKE (required for Double Glass models): Size of air intake verified and located. See page 5. [[ PLATFORM HEIGHT: This will determine the height of the viewable glass opening. Standard heights range from 12” up to 24”. See CAD drawing for unit dimensions. Note: The bottom of the glass will be from 8 3/8” to 10” above the platform depending on the unit. [[ POWER LOCATION: Provide a single gang 120v outlet in the same area as • Double Glass fan assisted (upgrade from screen barrier) valve behind access panel. The unit requires a 3v transformer supplied with • Power Vent system fireplace to run without batteries. • Reflective Interior Panel [[ TYPE X SHEETROCK IN CAVITY AREA: All combustible framing in chase • Wall Control Switch area must be completely covered with 5/8” Type X drywall. [[ FIREPLACE LOCATION AND VENTING: Make sure that adequate space is [[ NO MATERIAL ATTACHED TO FIREPLACE: No material may be attached provided to vent the fireplace from its desired location to the termination directly to the fireplace – no screws/glue/or nails should be used against the outside of the structure. fireplace. No weight on the firebox. [[ GAS SUPPLY LINE: Must run to fireplace valve location and include shutoff [[ NON-COMBUSTIBLE AREAS: Maintain 2” Clearance on sides and back of to allow for flex line to be attached to valve. Must have a manual shut off in firebox to type X drywall. the same room as the fireplace (within 4’ of fireplace). [[ FINAL WALL FINISH: Wall finish materials to be reviewed with your dealer to [[ ACCESS PANEL FOR CONTROL VALVE: See page 5. ensure clearances and materials conform to Ortal clearance requirements. 3 [[ Models and Clearances [[ General Guidelines AIRFLOWS This Builder’s Manual is based on installation of front-facing Ortal fireplaces; Clearances are to non-combustible materials or 5/8” Type X fire rated drywall. modify instructions to install other Ortal fireplace styles. Contact Ortal for additional information. Maintain clearances as shown below. 1. Direct vent exhaust system: This is the air inside the firebox and the [[ Locate 6-inches maximum from top of fireplace cavity exhaust gases (mostly carbon dioxide and water vapor) escape through This based on Manual front-facing Ortal ofoffront-facing modify instructions to modify other instructions Ortal totoinstall styles. other Maintain Ortal This Builder’s Builder’s Manual Manual is isThis based ThisBuilder’s Builder’s on installation installation Manualisof of isbased front-facing basedon oninstallation installation Ortal fireplaces; fireplaces; front-facing modifyOrtal instructions Ortalfireplaces; fireplaces; to install install modify other instructions Ortal fireplace fireplace install styles. other Maintain Ortalfireplace fireplacestyles. styles.Maintain Maintain clearances as shown below. clearances Clearances as shown are to below. non-combustible Clearances are materials to non-combustible or 5/8” Type X materials fire rated or drywall. 5/8” Type X fire rated drywall. clearances as shown below. clearances Clearances as shown are tobelow. non-combustible Clearances are materials to non-combustible or 5/8” Type Xmaterials fire ratedordrywall. 5/8” Type X fire rated drywall. Contact Contact information. Ortal Contact Ortal Ortal for for additional additional Contact information. Ortalfor foradditional additionalinformation. information. FRONT FRONT Heat Release: direct vent pipe. A direct vent pipe has an inner and outer channel. Hot Models Models Models and and Clearances Clearances Modelsand andClearances Clearances FRONT FRONT An Ortal fireplace requires two airflow paths: TUNNEL TUNNEL the inner channel. Fresh outdoor air (providing oxygen for the fire) is drawn in through the outer channel where it captures most of the heat escaping through the inner channel. 2. Heat release system and air intake: The cavity enclosing an Ortal TUNNEL TUNNEL fireplace must have a heat release outlet above the fireplace. This allows for heat building up within the fireplace cavity to be released back in the space which then helps keep your fireplace wall cool. Fireplaces with the double glass feature must have an air intake. Room Tunnel (See-thru) Front space creator air is drawn over the glass, between the interior wall and the frame of the fireplace, into the cavity and then is returned to the room through the heat release. These airflows, along with radiant heat from the LEFT LEFT SIDE SIDE OPEN OPEN (LS) (LS) LEFT LEFTSIDE SIDEOPEN OPEN(LS) (LS) RIGHT RIGHT SIDE SIDE OPEN OPEN (RS) (RS) front of the fireplace, maximize the heating performance of an Ortal RIGHT RIGHTSIDE SIDEOPEN OPEN (RS) (RS) Fireplace and contribute to its energy efficiency. Air Intake: [[ Can be a grille or louver or a gap between the top of cavity wall and ceiling. [[ Required for all built-in models. Size of Air Intake and of Heat Release: Minimum free area (net area after grille work or screens are subtracted) shall be: [[ Ortal Models 40 to 130: 124 sq.in. or more [[ Ortal Models 150 to 200: 200 sq.in. or more [[ Other Models: Check with Ortal. GAS VALVE ACCESS PANEL Gas valve should be installed below elevation of firebox. An access panel is recommended for easy servicing of gas valve. Panel should be 10 x 10 inches minimum; use larger size if required to conveniently reach valve. An appropriate sized air intake (see page 12) can be used as an access panel. [[ Ortal fireplaces with double-glass require an intake located below elevation of Ortal fireplace. Left side open (LS) THREE-SIDES 4 (TS) THREE-SIDES (TS) THREE-SIDES THREE-SIDES(TS) (TS) right side open (rS) SPACE SPACE CREATOR CREATOR SPACE SPACECREATOR CREATOR Three Sides (TS) [[ Air intake can be either a grille or louver or an opening on underside of cavity. 5 [[ SEISMIC BRACKETS [[ Heat Release as Reveal All built-in fireplaces come with legs and with seismic brackets at the top of [[ External surfaces of Ortal fireplace and areas exposed to radiant heat from the firebox. These are an additional way to secure the firebox in your cavity fire will get hot. Observe clearances between fireplace and combustible materials. while still maintaining the minimum air clearances provided here in this manual. You have the option to use these brackets or you may use a heavy duty steel bracket to mount the firebox to the back cavity wall while still maintaining the required 2” air clearance. If the seismic bracket does not extend all the way to your cavity wall, you may also extend metal studs to connect to your seismic bracket (as shown in several sections in this manual). FREESTANDING AND WALL-MOUNTED ORTAL FIREPLACES [[ Artwork and devices such as TVs, audio speakers and light fixtures to be mounted on cavity on or recessed into wall of cavity must have a double wall of 5/8” Type X fire rated gypsum board with air space in between to prevent direct heat impact. If working with metal framing see pages 22 and 23. If working with wood framing see pages 30 and 31. [[ Protect fireplace against damage throughout construction. LEGEND Secure fireplace to wall and subfloor. If fireplace is located against a wall, the wall must be of noncombustible 5/8" Type X fire rate gypsum board material or covered with 5/8” Type X gypsum board. IT'S YOUR business [[ Offer to assist your customer and their architect or designer while the Section Cut Wood project is still in planning so you can better understand their needs and suggest for the best approach to installing the fireplace. Combustible material [[ Get to know your local Ortal dealers. They can be a good source of referrals for you. ADDITIONAL WORDS OF CAUTION [[ Know the building code and consult with authorities having jurisdiction before proceeding. This guide contains minimum requirements; modify 6 details to satisfy project requirements. Non-combustible material Wood Framing Metal Framing 7 [[ Heat Release and Air Intake (with reveal or gap openings) Width opening must allow for minimum square inches of free air space (see page 5) See Heat Release Note 2 on page 5 6 See See10A 9A See Air Intake Note 2 on page 5 6 See See10B 9B Width opening must allow for minimum square inches of free air space (see page 5) Detail 9A Detail 9B See heat release note 2 on page 5 See air intake note 2 on page 5 Heat Release as Reveal 8 Air Intake as Reveal/Toe-kick 9 [[ Heat Release as Louver [[ Heat Release and Air Intake (with louver or grille openings) See Heat Release Note 2 on page 5 See 12C See 12D See Air Intake Note 2 on page 5 recommended 10 11 [[ Sprinkler Clearance to Heat Release In a situation where a sprinkler head is in close proximity to the heat release, the detail below must be followed. The distance between the sprinkler head to the heat release opening cannot be less than 60 inches (linear length) from every point of the heat release opening. Detail Detail 12C 12C Detail Detail 12D 12D See heat See release heatnote release 2 on note page25on page 5 See air intake See air note intake 2 on note page25on page 5 Heat Release Heat Release as louver as louver Air Intake Airas Intake louver as louver [[ Check with your louver manufacturer regarding the percentage of free air space provided by 12 their products in order to verify you will be providing the minimum free air space required or more. 13 [[ Metal Framing (Recessed Installation) [[ A. Work inside cavity (Steps 1-3) 1. Walls and Ceiling A. Work inside cavity (Steps 1-3) 1. Walls and Ceiling Non-combustible Framing Non-combustible Framing The wall behind an Ortal fireplace (either at the back or side of the The walland behind Ortal fireplace at the backbe or non side ofcombustible the fireplace) fireplace) theanceiling above(either the unit must construction such as concrete, brick, concrete masonry units, such or as and the ceiling above the unit must be non combustible construction plaster on metal framing and lath. Penetrations in wall or ceiling, concrete, brick, concrete masonry units, or plaster on metal framing and lath. suchPenetrations as electrical boxes, must be removed and patched to assure in wall or ceiling, such as electrical boxes, must be removed and integrity of non-combustible enclosure. patched to assure integrity of non-combustible enclosure. Combustible Framing Combustible Framing Existing walls or ceilings built of combustible materials may be used Existing walls or ceilings built of combustible may be used if the wall if the wall or ceiling is covered with 5/8- materials inch thick Type X gypsum or ceiling is covered with 5/8inch walls thick Type X gypsum board. (Exception: board. (Exception: Where cavity do not extend all the way to the Where ceilingcavity and walls allow “gap” forallheat release, 1/2-inch doanot extend the way to the ceiling andthick allow aType “gap”Xfor gypsum board may be used to match the thickness of gypsum heat release, 1/2-inch thick Type X gypsum board may be used to match the board used of ongypsum the ceiling theceiling cavity.) thickness board outside used on the outside the cavity.) The gypsum board may be screwed directly to the existing wall or mounted on The gypsum board may be screwed directly to the existing wall or metal framing or furring. mounted on metal framing or furring. Floor 2. 2. Floor Ortal fireplaces can be set on wood, concrete, metal, and other typical floor Ortal fireplaces can become set on concrete, metal, and other types. Ortal fireplaces withwood, legs that position the unit above the floor or typical floor types. platform on which they are installed. See shop drawings for height of legs. To further raise Ortal fireplace, build a stable platform to which unit can be secured. Ortal fireplaces come with legs that position the unit above the floor Services: This also the timeare to make sure power and gas lines are in place. or platform on iswhich they installed. See shop drawings for Provide a grounded duplex power outlet inside cavity for use by Ortal installer, height of legs. To further raise Ortal fireplace, build a stable platform toother which unitifcan be secured. and outlets required. 14 15 Services: This is also the time to make sure power and gas lines are 15 in place. Provide a grounded duplex power outlet inside cavity for use by Ortal installer, and other outlets if required. [[ B. Metal Framing (see Step 4) B. Metal Framing (see Step 4) 4. Install Metal Framing Install framing in accordance with building codes and project 4. Install Metal Framing specifications. We also recommend installation of studs at 16-inch Install framing in accordance with building codes and project specifications. on center maximum and compliance with American Iron and Steel We also recommendS220 installation of studs at 16-inch on center maximum Institute Publication “North American Specification for the and compliance with AmericanSteel Iron and Steel Institute Publication S220 “North Design of Cold-Formed Framing – Non-Structural American Specification for the Design of Cold-Formed Steel Framing – NonMembers”. 3. Installation of Ortal fireplace and vent Ortal fireplaces must be installed in accordance with Ortal installation and Operation Manual and applicable codes. Install the direct vent pipe, make gas and power connections, and provide fire stopping or thimble where direct vent pipe penetrates the wall or ceiling of cavity. Structural Members ”. and give particular attention to: Plan your work carefully • Required clearances. • Plan Blocking forcarefully securing direct vent pipes, your work andfireplace, give particular attention to: mantles, etc. [ Required clearances. • [Access panel for gas valve (see page XX). • [Heat release and Air fireplace, intake (see page [ Blocking for securing direct ventXX). pipes, mantles, etc. • Direct vent, direct vent strapping, and penetrations [through [ Access panel valve (see page 05). walls for andgas ceiling. • Recesses for TV, audio speakers, light fixtures, artwork, [[ Heat release and Air intake (see page 05). and other items built into cavity (if required). TIP - Do not allow delivery of Ortal fireplace to jobsite until building is enclosed and ready for installation. [[ Protect fireplace against damage throughout construction. [[ Notify authorities having jurisdiction to inspect work before cavity is enclosed (if required). [[ Installation must be performed by an Ortal Authorized Installer otherwise warranty is void [[ Direct vent, direct vent strapping, and penetrations through walls and ceiling. Install conduit, wiring, power outlets, and electrical boxes between framing members asaudio required. [[ Recesses for TV, speakers, light fixtures, artwork, and other items built into cavity (if required). Take a moment for a final visual inspection of the cavity interior and to remove any construction debris that may be inside cavity. Take a moment for a final visual inspection of the cavity interior and to remove and structural must bear on conduit, Ortal fireplace. ⚠ Building any construction debris thatloads may be insidenot cavity. Install wiring, power outlets, and electrical boxes between framing members as required. [[ Building and structural loads must not bear on Ortal fireplace. 16 17 17 [[ C. Enclose Cavity (See Step 5) C. Enclose Cavity (See Step 5) 5. Drywall 5.the Drywall Cover metal framing with 5/8-inch thick Type X gypsum board to exterior face of framing cavity. with (Exceed these Cover the metal 5/8-inch thickrequirements Type X gypsumwhere board to exterior fire-resistance-rated construction or other methods are required.) face of cavity. (Exceed these requirements where fire-resistance-rated construction or other methods are required.) Type X gypsum board must comply with ASTM C1396 Type X gypsum board mustBoard. comply(This with ASTM C1396replaces - Specification for Gypsum Specification for Gypsum standard ASTM C36 - Specification for Gypsum Wallboard.) Board. (This standard replaces ASTM C36 - Specification for Gypsum Wallboard.) Provide Level 1 or better finish in accordance with GA-214 - Recommended Provide Level 1 or better finish in accordance with GA-214 Levels of Gypsum Board Finish. Recommended Levels of Gypsum Board Finish. Do not locate exposed gypsum board joints directly above fireplace. Do not locate exposed gypsum board joints directly above fireplace. If corner beads and other drywall trim are required, use metal products where non-combustible materials are required. If corner beads and other drywall trim are required, use metal products where non-combustible materials are required. DRYWALL: These instructions apply to all steps. We recommend the following as a minimum. Exceed these requirements where fire-resistance-rated construction is required. DRYWALL: These instructions apply to all steps. Use 5/8-inch thick Type X gypsum board. (Exception: Where cavity walls do not extend allfollowing the way toas theaceiling and allow a “gap” for requireheat release, We recommend the minimum. Exceed these thickfire-resistance-rated Type X gypsum boardconstruction may be used ifistorequired. match the thickness of ments1/2” where gypsum board used on the ceiling outside the cavity.) Use 5/8-inch thick Type X gypsum board. (Exception: Where cavity Type X gypsum board must comply with ASTM C1396 - Specification for walls do not extend all the way to the ceiling and allow a “gap” for heat Gypsum Board. (ThisXstandard ASTM - Specification release, 1/2” thick Type gypsumreplaces board may beC36 used if to match for the Gypsum Wallboard.) Gypsum joints shalloutside be staggered on opposite thickness of gypsum board usedboard on the ceiling the cavity.) sides of framing. Type X gypsum board must comply with ASTM C1396 - Specification Fasteners: Use 1-1/4” Type W drywall screws 12” o.c. or 6d coated nails, 1-7/8” for Gypsum Board. (This standard replaces ASTM C36 - Specification long, 0.0915” shank, 1/4” head at 7” o.c. along edges and interior studs. for Gypsum Wallboard.) 18 18 Gypsum board joints shall be staggered on opposite sides of framing. Fasteners: Use 1-1/4” Type W drywall screws 12” o.c. or 6d coated nails, 1-7/8” long, 0.0915” shank, 1/4” head at 7” o.c. along edges and interior studs. 19 [[ Shelf Detail 7. Finishes Almost done. Now is the time to apply decorative finishes to exterior of fireplace cavity (see page Below is a table defining the maximum surface area if incorporating a shelf detail in the fireplace design. 32). This is also time to install mantels, TV mounts, and other features (see page 22 for TV and 37 for mantels). [[ Observe clearances requirements for combustible materials. 8. Turn Over to Customer Your Ortal dealer will install interior design media, remove protective materials from and clean exposed surfaces of the Ortal fireplace and perform a start-up 6 6 inspection and burn-in the unit. The dealer will provide: [[ Ortal Installation and Operation Manual. The drawing is showing that a minimum 12 inch height must be provided from the top of the fireplace opening to the top of the shelf. Be sure to keep the top of the firebox clear from obstruction and maintain all clearances. MODEL Max Shelf surface area Series 75 A x B < 220 sq. in. Series 110/130 A x B < 340 sq. in. Series 150/170 A x B < 410 sq. in. Series 200 A x B < 520 sq. in. [[ Ortal Fireplace Owners Manual. [[ Executed Warranty [[ Operation Control(s) Demonstrate the operation of the Ortal fireplace to the customer. [[ Advise customer that furniture and other combustible materials must not be placed within the clearance zone shown on Drawings. This detail applies to all our built-in models (Front, Corner, Three- Sided, Tunnel and Space Creators). [[ A heat release on top of the shelf is only needed if the shelf surface area exceeds what is shown on the table above. [[ Send Ortal photos of installation and the completed project for a chance to be featured on our website and social media. Submit your project at info@ortalheat.com. [[ Ask customer for a letter of recommendation. You can use the letter (and 20 the photos) when you suggest an Ortal fireplace for your next project. 21 22 [[ TV Detail (flush) [[ TV Detail (recess) [[ Always respect the 1/4” clearance between the metal framing and fireplace front for heat expansion [[ Always respect the 1/4” clearance between the metal framing and fireplace front for heat expansion 23 [[ Wood Framing (Recessed Installation) [[ A. Work Inside Cavity (Steps 1-3) A. Work Inside Cavity (Steps 1-3) 1 Frame Cavity Front Wall: On most projects, you will want to postpone installation of the 1. Frame Cavity front wall of the cavity. This will allow access for installing drywall inside the cavity, positioning the Ortal fireplace and direct vent Front Wall: vent pipe, and making necessary connections. (See step 3) On most projects, you will want to postpone installation of the front wall of the cavity.framing This will allow access for installing drywall inside the cavity, positioning the Install in accordance with building codes and project Ortal fireplace and pipe,16 andinches makingon necessary specifications. All direct, studsvent placed center.connections.(See step 3) Plan your work carefully and give particular attention to: Install framing in accordance with building codes and project specifications. All • Required clearances. placed 16 inches on center. • studs Blocking for securing fireplace, direct vent pipes, mantles,etc. • Plan Access panel for valve (seeparticular page XX). your work carefully and give attention to: • Heat release and Air intake (see page XX). Required clearances. • [[ Direct vent, direct vent strapping, and penetrations through walls and ceiling. [[ Blocking for securing fireplace, direct vent pipes, mantles,etc. • Recesses for TV, audio speakers, light fixtures, artwork, other items built into [[ Accessand panel for valve (see page 05).cavity (if required). Install conduit, wiring, power outlets, and electrical boxes between [[ Heat release and Air intake (see page 05). framing members as required. [[ Direct vent, direct vent strapping, and penetrations through walls and ceiling. Take a moment for a final visual inspection of the cavity interior TV,construction audio speakers, light fixtures, art work, and other items and[[toRecesses removefor any debris that may be inside cavity. built into cavity (if required). ⚠ Building and structural loads must not bear on Ortal fireplace. Take a moment for a final visual inspection of the cavity interior and to remove any construction debris that may be inside cavity. Install conduit, wiring, power Floor: outlets, and electrical boxes framing members as required. Ortal fireplaces can be setbetween on wood, concrete, metal, and other typical floor and types. [[ Building structural loads must not bear on Ortal fireplace. 24 25 Ortal fireplaces come with legs that position the unit above the floor or platform on which it they are installed. See shop drawings for height. 25 [[ B. Wood Framing (Steps 4-6) B. Wood Framing (Steps 4-6) 4 Build Infill Panel Assemble infill panel flat on the floor. Orient so that the face that be inside the cavity is uppermost as it lays on subfloor. 4.will Build Infill Panel Floor: Remodeling Projects: Apply a layer of Type X gypsum board over existing Ortal fireplaces can be set on wood, concrete, metal, and other typical floor materials unless it is certain that the existing surfaces are 5/8-inch Type X types. Ortal fireplaces come with legs that position the unit above the floor or Assemble infill panel flat on the floor. Orient so that the face that will be inside the Be sure to provide headers or other devices required to cavity isinfill uppermost as it lays on subfloor. loads. support panel and superimposed gypsum board or acceptable non combustible material. Be sure to provide headers or other devices required to support infill panel and Give particular loads. attention to the details and clearances required superimposed for any recesses for TV or art. Provide blocking for anchorage Give particular attention to the details and clearances required for any recesses of TV or heavy artwork, and brace recess to prevent sagging. (See TV oron art.page#?) Provide blocking for anchorage of TV or heavy artwork, and brace TVfor detail platform on which it they are installed. See shop drawings for height. To further raise Ortal fireplace, build a stable platform to which unit can be secured. Services: This is also the time to make sure power and gas lines are in place. Provide a grounded duplex power outlet inside cavity for use by Ortal installer, and other outlets if required. 2. Drywall Cavity Interior Wood framing inside cavity must be covered with Type X gypsum board or constructed of a non-combustible material such as concrete, plaster, concrete masonry, or brick. 3. Installation of Ortal fireplace and vent Ortal fireplaces must be installed in accordance with Ortal installation and recess to prevent sagging. (See TV details on pages 30 and 31) Operation Manual and applicable codes. Install the direct vent pipe, make gas 5 Drywall Inside of Infill Panel and power connections, and provide fire stopping or thimble where direct vent pipe penetrates the wall or ceiling of cavity. 5. Drywall Inside of Infill Panel Apply 5/8-inch thick Type X gypsum board to the “inside” Apply 5/8-inch thickpanel; Type Xthis gypsum board “inside” of the infill surface of the infill is the toptoofthe the panelsurface as it lays this is the top of the panel as it lays on the floor. onpanel; the floor. TIP - Do not allow delivery of Ortal fireplace to jobsite until building is enclosed and ready for installation. [[ Protect fireplace against damage throughout construction. DRYWALL: These instructions apply to all steps. [[ Notify authorities having jurisdiction to inspect work before cavity is We recommend the following as a minimum. Exceed these requirements enclosed (if required). where fire-resistance-rated construction is required. Use 5/8-inch thick Type X gypsum board. (Exception: Where cavity walls do not extend all the way to the ceiling and allow a “gap” for heat release, Install Infill Panel 6 6. Install Infill Panel Take a moment for a final visual inspection of the cavity interior and to remove any Take a moment forthat a final inspection of the cavity interior and construction debris mayvisual be inside cavity. to remove any construction debris that may be inside cavity. [[ Installation must be performed by an Ortal Authorized Installer otherwise warranty is void. Gather a few mates and give it the old heave-ho to lift or tilt the infill panel into position. Secure to cavity Gather a few mates andframing. give it the old heave-ho to lift or tilt the infill panel into position. Secure to cavity framing. 1/2” thick Type X gypsum board may be used if to match the thickness of gypsum board used on the ceiling outside the cavity.) Type X gypsum board must comply with ASTM C1396 - Specification for Gypsum Board. (This standard replaces ASTM C36 - Specification for Gypsum Wallboard.) Gypsum board joints shall be staggered on opposite sides of framing. Fasteners: Use 1-1/4” Type W drywall screws 12” o.c. or 6d coated nails, 1-7/8” long, 0.0915” shank, 1/4” head at 7” o.c. along edges and interior studs. 26 27 27 [[ C. Metal Surround and Enclosure (Steps 7-8) 7 Install Metal Surround C. Metal Surround and Enclosure (Steps 7-8) Assemble and install metal surround. Metal Surround Do 7. notInstall attach framing to Ortal fireplace. 9. Finishes Assemble and install metal surround. Almost done. Do not attach framing to Ortal fireplace. Now is the time to apply decorative finishes to exterior of fireplace cavity 8 Drywall Exterior of Cavity (see page 32). This is also time to install mantels, TV mounts, and other features (see page 30 for TV and 37 for mantels). 8. Drywall Exterior of Cavity Install wiring, power outlets, and other electrical boxes if Install wiring, power outlets, and other electrical boxes if required between required between framing members. [[ Observe clearances requirements for combustible materials. Apply 5/8” X gypsum gypsum board to exterior ofinfill cavity, Apply 5/8”Type Type X board to exterior face offace cavity, panel,infill and metal panel, and metal surround. Do not locate drywall panel joints surround. Do not locate drywall panel joints directly above fireplace. directly above fireplace. Your Ortal dealer will install interior design media, remove protective materials 10. Turn Over to Customer framing members. from and clean exposed surfaces of the Ortal fireplace and perform a start-up inspection and burn-in the unit. [[ If corner beads and other drywall trim are required, use metal products non-combustible materials are required. ⚠ Ifwhere corner beads and other drywall trim are required, use metal products where non-combustible materials are required. [[ Electrical boxes should not penetrate the drywall on the interior of the cavity. ⚠ Electrical boxes should not penetrate the drywall on the interior of the cavity. The dealer will provide: 6 [[ Ortal Installation and Operation Manual. [[ Ortal Fireplace Owners Manual. [[ Executed Warranty [[ Operation Control(s) Demonstrate the operation of the Ortal fireplace to the customer. [[ Advise customer that furniture and other combustible materials must not be placed within the clearance zone shown on Drawings. [[ Send Ortal photos of installation and the completed project for a chance to be featured on our website and social media. Submit your project at info@ortalheat.com [[ Ask customer for a letter of recommendation. You can use the letter (and the photos) when you suggest an Ortal fireplace for your next project. 28 28 29 [[ Wood Framing - TV Detail (flush) 6 30 [[ Wood Framing - TV Detail (recess) 6 31 [[ Finishes [[ Finishes - Quartz [[ Quartz is not allowed to be installed on your hearth extension 32 [[ Always respect the 1/4” clearance between the metal framing and fireplace front for heat expansion 33 34 [[ Finishes - Wood Paneling [[ Finishes - Brick Veneer [[ Always respect the 1/4” clearance between the metal framing and fireplace front for heat expansion [[ Always respect the 1/4” clearance between the metal framing and fireplace front for heat expansion 35 [[ Mantel Details 36 [[ Always respect the 1/4” clearance between the metal framing and fireplace front for heat expansion 37 38 [[ Stone Finish & Hearth Extension [[ Wood Hearth Extension [[ The 1/8" clearance applies to the bottom/hearth extension as well. [[ Always respect the 1/4” clearance between the metal framing and fireplace front for heat expansion 39 [[ Inside Corner Clearances 40 41 [[ Clearances to Ceiling [[ Vent Pipe Clearances Vertical: [[ Maintain 1” clearance to combustibles on entire circumference. Horizontal: • Maintain 1” clearance to combustibles on bottom and sides • Maintain 3” clearance to combustibles on top • Maintain ¼” rise per foot MODEL A (minimum vertical off top of firebox before 90 elbow) Series 40-170 3 feet Series 200+ 6 feet In a situation where a 45 degree elbow is required off the top of the firebox, it must be followed with the minimum vertical run per above. 42 43 [[ Venting Diagram - Typical Horizontal Series 40 Series 75 Series 110/120/130 Series 150/170 [[ Venting Diagram - Typical Vertical Series 200 Series 40 V1 = minimum 3 feet Vertical (V) Horizontal (H) Vertical (V) Horizontal (H) Vertical (V) Horizontal (H) Vertical (V) Horizontal (H) Vertical (V) Horizontal (H) 3 ft 21 ft 3 ft 21 ft 3 ft 12 ft 3 ft 9 ft 6 ft 9 ft 6 ft 24 ft 6 ft 24 ft 6 ft 18 ft 6 ft 12 ft 9 ft 12 ft 9 ft 24 ft 9 ft 24 ft 9 ft 24 ft 9 ft 18 ft 12 ft 12 ft 12 ft 24 ft 12 ft 24 ft 12 ft 21 ft 12 ft 21 ft 15 ft 15 ft 15 ft 24 ft 15 ft 24 ft 15 ft 21 ft 15 ft 18 ft 18 ft 15 ft 18 ft 21 ft 18 ft 21 ft 18 ft 18 ft 18 ft 18 ft 21 ft 12 ft 21 ft 18 ft 21 ft 18 ft 21 ft 15 ft 21 ft 15 ft 24 ft 12 ft 24 ft 15 ft 24 ft 15 ft 24 ft 12 ft 24 ft 12 ft 27 ft 9 ft 27 ft 12 ft 27 ft 12 ft 27 ft 12 ft 27 ft 9 ft 30 ft 9 ft 30 ft 12 ft 30 ft 12Venting ft 30 ft 9 ft 33 ft 6 ft 33 ft 12 ft 33 ft 12 ft 30 ft - Typical12Horizontal ft Diagram 33 ft 12 ft V 44 Vertical Horizontal Series 110/120/130 9 ft Vertical Horizontal (V) (H) Series 75 Vertical Horizontal Series 200 V1 = minimum 3 feet Series 110/120/130 V1 = minimum 3 feet Series 150/170 Series 200 V1 = minimum 3 feet V1 = minimum 6 feet Vertical (V) Horizontal (H) Vertical (V) Horizontal (H) Vertical (V) Horizontal (H) Vertical (V) Horizontal (H) Vertical (V) Horizontal (H) 4 ft 15 ft 4 ft 15 ft 4 ft 6 ft 4 ft 6 ft 7 ft 3 ft 7 ft 18 ft 7 ft 18 ft 7 ft 15 ft 7 ft 12 ft 10 ft 12 ft 10 ft 18 ft 10 ft 18 ft 10 ft 18 ft 10 ft 15 ft 13 ft 12 ft 13 ft 18 ft 13 ft 18 ft 13 ft 15 ft 13 ft 12 ft 16 ft 12 ft 16 ft 18 ft 16 ft 18 ft 16 ft 15 ft 16 ft 12 ft 19 ft 12 ft 19 ft 15 ft 19 ft 15 ft 19 ft 12 ft 19 ft 12 ft 22 ft 12 ft 22 ft 12 ft 22 ft 12 ft 22 ft 9 ft 22 ft 12 ft 25 ft 12 ft 25 ft 9 ft 25 ft 9 ft 25 ft 6 ft 25 ft 9 ft 28 ft 12 ft 28 ft 6 ft 28 ft 6 ft 28 ft 6 ft 28 ft 9 ft 31 ft 9 ft Series 150/170 31 ft 6 ft 31 ft 6 ft 31 ft 6 ft 31 ft 6 ft 34 ft 9 ft Vertical Horizontal (V) (H) 34 ft 6 ft 34 ft 6 ft 34 ft 6 ft 34 ft 6 ft 3 ft 12 ft 3 ft 9 ft 6 ft 18 ft 6 ft 12 ft Notes: 9 ft 24 ft 9 ft 18 ft 12 ft 21or ft four 45 elbows. 12 ft 21 ft 1. Can use up to two 90 elbows 15 ft 21 ft 15 ft 18 ft 2. V minimum = 18 ft 18 ft 18 ft 18 ft a. 6 feet for Series 200 21 ft 15 ft 21 ft 15 ft 24 ft 12 ft 24 ft 12 ft b. 3 feet for Series 40-170 27 ft 12 ft 27 ft 9 ft [[ For venting runs that these 30exceed ft 12 ft maximums consider 30 ft Ortal’s 9 ftPower 33 ft Ortal12 ft 33 ft 9 ft Vent system. Contact your dealer for more information. H Series 40 33 ft Series 75 Venting Diagram - Typical Vertical Notes: V2 H1 Series 40 V1 = minimum 3 feet Vertical Horizontal (V) (H) Series 150/170 V1 = minimum 3 feet Vertical Horizontal (V) (H) 4 ft 4 ft 6 ft 6 ft 7 ft 15 ft 12 ft 10 ft 10 ft 18 ft 15 ft 2. V = V1 + V2 13 ft 13 ft 15 ft 12 ft 16 ft 16 ft 15 ft 12 ft [[ For venting runs that exceed19these maximums consider ft 19 ft Ortal’s 12 ft 12 ftPower 22 ft 22 ft 9 ft 12 ft Vent system. Contact your Ortal25dealer for more information. ft 25 ft 6 ft 9 ft 28 ft 28 ft 6 ft 9 ft 31 ft 31 ft 6 ft 6 ft 34 ft 34 ft 6 ft 6 ft 7 ft 1. Can use up to two 90 elbows V V1 Series 110/120/130 Series 75 Series 200 V1 = minimum 3 feet V1 = minimum 3 feet V1 = minimum 6 feet Vertical Horizontal Vertical Horizontal Vertical Horizontal 45 [[ Venting Diagram - Straight Vertical [[ Sconce Cap Detail (with small wall thimble) Venting Diagram - Straight Vertical V Model Max Vertical Series 40-200 42 feet Max Vertical Series 40-200[[ 46 MODEL For venting runs thatfeet exceed these maximums consider Ortal’s Power 42 Vent system. Contact your Ortal dealer for more information. 47 [[ notes 48 49 [[ notes 50 [[ notes 51 [[ notes 52 Tel: 1 (818) 238-7000 | Fax: 1 (818) 678-0541 www.ortalheat.com / info@ortalheat.com your life. your fire. © 2016 Ortal USA Issued date: 02/2016 For use by qualified design and construction professionals only.