CKD Pneumatic Valves

Transcription

CKD Pneumatic Valves
Discrete valve
Body porting
3GA1·2·3 /4GA1·2·3 Series
• Applicable cylinder bore size: 20 to 100 mm
Common specifications
CAD DATA AVAILABLE.
Electrical specifications
Descriptions
Descriptions
Working fluid
Compressed air
Valve and solenoid type
Min. working pressure
Rated voltage
MPa
Max. working pressure MPa
0.7
Holding current
Withstanding pressure
1.05
Note 3
Ambient temperature
°C
-5 to 55
Fluid temperature
°C
-5 to 55
Manual override
DC24V
0.023 (0.025)
A DC12V
0.046 (0.050)
Power consumption DC24V
0.55 (0.6)
W DC12V
0.55 (0.6)
Note 3
Apparent power VA AC100V
Main valve/pilot valve common exhaust type
Lubrication
Note 1
Not required
Heat proof class
Protection structure
Note 2
Dust proof
Temperature rise
50 or less/300 or less
Surge suppressor
m/s2
Vibration/impact
Working environment
0.010 (0.012)
AC100V
Non-locking/locking type
Pilot exhaust method
100
±10%
Rated voltage fluctuation
0.2 (2-position, 3-position)
MPa
12, 24
DC
V AC
Pilot operated soft spool valve
1.0 (1.2)
B
°C
50
Option
Indicator
Not to be subject to corrosive gas
Note 1. For lubrication, please use turbine oil Class 1ISOVG32.
Too much lubrication and intermittent lubrication may cause unstable operation.
Note 2. Not to be subject to water drip, oil etc.
For DIN terminal box specifications, IP65 (jet-proof type).
Cable O.D. and tightening torque conformable with the regulations should be observed.
Reference. Pressure unit is Mpa. Conversion ratio is 1MPa=10.1972kgf/cm2.
Indicator light (Option)
Note 3. The value in ( ) for indicator light.
Individual specifications
Descriptions
Port size
3GA1
Port P/R1/R2
3GA3
4GA1
4GA2
4GA3
M5
Rc1/8
Rc1/4
M5
Rc1/8
Rc1/4
M5
Rc1/8
Rc1/4
M5
Rc1/8
Rc1/4
3GA1
3GA2
3GA3
4GA1
4GA2
4GA3
P → A/B A/B → R1/R2 P → A/B A/B → R1/R2 P → A/B A/B → R1/R2 P → A/B A/B → R1/R2 P → A/B A/B → R1/R2 P → A/B A/B → R1/R2
Descriptions
Port size Port A/B
Effective
3GA2
Push in joint 4, 6 dia. Push in joint 4, 6, 8 dia. Push in joint 6, 8, 10 dia. Push in joint 4, 6 dia. Push in joint 4, 6, 8 dia. Push in joint 6, 8, 10 dia.
Port A/B
Push in joint 6 dia. Push in joint 8 dia. Push in joint 10 dia. Push in joint 6 dia. Push in joint 8 dia. Push in joint 10 dia.
3.8
4.5
11
12
18
19
3.8
4.5
11
12
18
19
-
-
-
-
-
-
3.8
4.5
10
10
17
17
ABR connection
-
-
-
-
-
-
3.8
4.5
10
12
17
19
PAB connection
-
-
-
-
-
-
4.0
4.5
13
10
19
17
sectional area 2-position
mm2 3-position All ports closed
3GA2
3GA1
Descriptions
3GA3
4GA1
4GA2
4GA3
When ON When OFF When ON When OFF When ON When OFF When ON When OFF When ON When OFF When ON When OFF
Response time 2-position Single
Double
ms
3-position ABR connection
12
12
19
19
25
28
12
12
19
19
25
-
-
-
-
-
-
9
-
18
-
24
-
-
-
-
-
-
-
8
15
17
30
23
45
28
The value of light, surge suppressor is shown. Response time is the value at supply pressure 0.5MPa, 20 °C and not lubricated. The value varies depending on pressure and oil quality.
Descriptions
Single
g
2-position
Mass
Grommet lead wire
E-connector
3GA1
3GA2
3GA3
4GA1
4GA2
4GA3
58 (44)
60 (46)
115 (85)
117 (87)
162 (120)
164 (122)
58 (44)
60 (46)
120 (90)
122 (92)
171 (129)
173 (131)
3-position
DIN terminal box
137 (107)
184 (142)
142 (112)
193
Double Grommet lead wire
73 (59)
135 (105)
187
E-connector
77 (63)
139 (109)
191
DIN terminal box
179 (149)
231
75 (61)
147 (117)
196
All ports Grommet lead wire
E-connector
79
(65)
151
(121)
200
Block
DIN terminal box
191 (161)
240
For no piping adapter, refer to the value in ( ). The value of E-connector includes the value of socket assembly (lead wire 300mm).
For mass of EJ connector, add 16g/piece to mass of E-connector.
94
(151)
(141)
(145)
(185)
(154)
(158)
(198)
3GA1·2·3/4GA1·2·3 Series
Discrete valve: Body porting
4SA/B0
4SA/B1
4GA/B
MN4GA/B
4GA/B
(master)
MN3S0/
MN4S0
4TB
4L2-4/
LMF0
4KA/B
4F
PV5/
CMF
3MA/B0
3PA/B
P/M/B
NP/NAP/
NVP
4F**0E
HMV/
HSV
Uniwire
system
SKH
PCD/
FS/FD
Discrete
3, 5 port pilot operated valve
95
3GA1/4GA1 Series
Discrete valve: Body porting
Internal structure and part list
3GA110-C4
C6 -*
• 2-position single solenoid, N.C.
Grommet lead wire(Blank)
1
2
3
4
6
5
14
7
8
9
12
11
10
13
4(A)
5(R1)
1(P)
3 (R2)
3GA1110-C4
C6 -*
• 2-position single solenoid, N.O.
Grommet lead wire(Blank)
1
2
3
4
5
6
14
7
9
8
10
11
12
2 (B)
5(R1)
1(P)
3 (R2)
4GA110
• 2-position single
Grommet lead wire(Blank)
1
2
3
4
5
6
7
4(A)
8
9
2 (B)
11
5(R1)
96
1(P)
3 (R2)
10
11
12
13
13
3GA1/4GA1 Series
Discrete valve: Body porting
Internal structure and part list
4GA120
• 2-position double
Grommet lead wire(Blank)
4SA/B0
1
2
3
4
5
6
7
8
9
10
13
4SA/B1
2 (B)
4(A)
4GA/B
MN4GA/B
4GA/B
(master)
11
11
MN3S0/
MN4S0
4TB
5(R1)
1(P)
3 (R2)
4L2-4/
LMF0
3
4GA1 45 0
4KA/B
• 3-position
Grommet lead wire(Blank)
4F
PV5/
CMF
1
2
3
4
5
6
7
8
9
10
3MA/B0
13
2 (B)
4(A)
3PA/B
P/M/B
NP/NAP/
NVP
11
11
4F**0E
HMV/
HSV
5(R1)
1(P)
Uniwire
system
3 (R2)
SKH
Main part list
No.
Repair parts list
1
Coil assembly
-
2
Pilot exhaust check valve
Nitrile rubber
3
Piston D assembly
-
4
Manual override
Resin
5
Piston room
Resin
6
Protective cover of manual override
Resin
7
Cartridge type quick connector
-
8
Spool assembly
-
9
Joint adaptor
Resin
10
Body
Aluminum alloy die casting
11
Piston S assembly
-
12
Cap
Resin
13
Piping adapter
Aluminum alloy die casting
14
Plug cartridge
Aluminum
No.
Parts name
1
Coil assembly
PCD/
FS/FD
Model No.
4G-[Electric connection]- * - COIL- [Voltage]
Blank: Standard
A: Ozone proof
Discrete
Material
Blank: Grommet lead wire
7
4 dia. straight type 4G1-JOINT-C4
Cartridge type
quick connector 6 dia. straight type 4G1-JOINT-C6
and related parts
Plug cartridge
4G1-JOINT-CPG
97
3, 5 port pilot operated valve
Parts name
3GA2·3/4GA2·3 Series
Discrete valve: Body porting
Internal structure and part list
3GA210/3GA310
• 2-position single solenoid, N.C.
Grommet lead wire(Blank)
2
1
3
4
5
6
7
14
8
10
9
11
12
11
12
11
12
13
4(A)
5(R1)
1(P)
3 (R2)
3GA2110/3GA3110
• 2-position single solenoid, N.O.
Grommet lead wire(Blank)
1
2
3
4
5
6
14
7
8
9
10
13
2 (B)
5(R1)
1(P)
3 (R2)
4GA210/4GA310
• 2-position single
Grommet lead wire(Blank)
1
2
3
4
5
6
5(R1)
98
7
1(P)
8
9
3 (R2)
10
13
3GA2·3/4GA2·3 Series
Discrete valve: Body porting
Internal structure and part list
4GA220/4GA320
• 2-position double
Grommet lead wire(Blank)
4SA/B0
1
2
3
4
5
6
7
8
9
10
13
4SA/B1
4GA/B
MN4GA/B
4GA/B
(master)
MN3S0/
MN4S0
4TB
5(R1)
3
1(P)
3 (R2)
4L2-4/
LMF0
3
4GA2 45 0/4GA3 45 0
4KA/B
• 3-position
Grommet lead wire(Blank)
4F
PV5/
CMF
1
2
3
4
5
6
7
8
4(A)
9
10
13
3MA/B0
2 (B)
3PA/B
P/M/B
NP/NAP/
NVP
11
4F**0E
11
HMV/
HSV
5(R1)
1(P)
3 (R2)
Uniwire
system
SKH
Main part list
Repair parts list
Material
1
Coil assembly
-
2
Pilot exhaust check valve
Nitrile rubber
3
Piston D assembly
-
4
Manual override
Resin
5
Piston room
Resin
6
Protective cover of manual override Resin
7
Cartridge type quick connector
-
8
Spool assembly
-
9
Joint adaptor
Resin
10
Body
Aluminum alloy die casting
11
Piston S assembly
-
12
Cap
Resin
13
Piping adapter
Aluminum alloy die casting
14
Plug cartridge
Aluminum
No.
Parts name
1
Coil assembly
PCD/
FS/FD
Model No.
4G-[Electric connection]- * - COIL- [Voltage]
Blank: Standard
A: Ozone proof
Discrete
Parts name
Blank: Grommet lead wire
4 dia. straight type
7
4G2-JOINT-C4 (4GA2 only)
6 dia. straight type
4G2-JOINT-C6
Cartridge type
quick connector 8 dia. straight type 4G2-JOINT-C8
and related parts
10 dia. straight type 4G2-JOINT-C10 (4GA3 only)
Plug cartridge
4G2-JOINT-CPG
99
3, 5 port pilot operated valve
No.
3GA1·2·3/4GA1·2·3 Series
Discrete valve: Body porting
Internal structure and part list (Electric connection)
• E-connector type (E**)
2
1
• EJ-connector type (E**J)
3
1
• DIN terminal box type (B)
1
Main part list
4
Repair parts list
No.
Parts name
Material
1
Coil assembly
2
E-connector socket assembly
-
3
Socket with cover assembly
-
4
DIN terminal box assembly
-
No.
Parts name
1
Coil assembly
Model No.
4G-[Electric connection]- * - COIL- [Voltage]
Blank: Standard
A: Ozone proof
E* : E-connector type
E* J: Socket with cover type
B : DIN terminal box type
When B, DIN terminal box is included.
100
2
E-connector socket assembly
4G-SOCKET ASSY-E**-[Voltage]
3
Socket with cover assembly
4G-SOCKET ASSY-E**J
4
DIN terminal box assembly
4G-TERMINAL BOX-[Voltage]
3GA1 Series
Discrete valve: Body porting
Dimensions
3GA110
(File name: Page 239 or Ending 15)
• 2-position single solenoid, N.C. grommet lead wire
• M5 female thread type(M5)
102
• Mounting plate type(P)
3GA1 Series
Discrete valve: Body porting
Dimensions
• E-connector type(E)
4SA/B0
4SA/B1
4GA/B
MN4GA/B
Note. Dimensions of DC specifications are shown.
When AC100V, overall length of valve is
3.5mm longer.
4GA/B
(master)
MN3S0/
MN4S0
4TB
4L2-4/
LMF0
• EJ-connector type(E**J)
4KA/B
4F
PV5/
CMF
3MA/B0
3PA/B
P/M/B
NP/NAP/
NVP
4F**0E
HMV/
HSV
Uniwire
system
Note. Dimensions of DC specifications are shown.
When AC100V, overall length of valve is
3.5mm longer.
SKH
PCD/
FS/FD
Discrete
3, 5 port pilot operated valve
103
3GA1 Series
Discrete valve: Body porting
Dimensions
3GA1110
(File name: Page 239 or Ending 15)
• 2-position single solenoid, N.O. grommet lead wire
• M5 female thread type(M5)
104
• Mounting plate type(P)
3GA1 Series
Discrete valve: Body porting
Dimensions
• E-connector type(E)
4SA/B0
4SA/B1
4GA/B
Note. Dimensions of DC specifications are shown.
When AC100V, overall length of valve is
3.5mm longer.
MN4GA/B
4GA/B
(master)
MN3S0/
MN4S0
4TB
4L2-4/
LMF0
• EJ-connector type(E**J)
4KA/B
4F
PV5/
CMF
3MA/B0
3PA/B
P/M/B
NP/NAP/
NVP
4F**0E
HMV/
HSV
Uniwire
Note. Dimensions of DC specifications are shown. system
When AC100V, overall length of valve is
SKH
3.5mm longer.
PCD/
FS/FD
Discrete
3, 5 port pilot operated valve
105
3GA2 Series
Discrete valve: Body porting
Dimensions
3GA210
(File name: Page 239 or Ending 15)
• 2-position single solenoid, N.C. grommet lead wire
• Rc1/8 female thread type(06)
2B
4A
106
• Mounting plate type(P)
3GA2 Series
Discrete valve: Body porting
Dimensions
• E-connector type(E)
4SA/B0
4SA/B1
4GA/B
Note. Dimensions of DC specifications are shown.
When AC100V, overall length of valve is
3.5mm longer.
MN4GA/B
4GA/B
(master)
MN3S0/
MN4S0
4TB
• EJ-connector type(E**J)
4L2-4/
LMF0
4KA/B
4F
PV5/
CMF
3MA/B0
3PA/B
P/M/B
NP/NAP/
NVP
Note. Dimensions of DC specifications are shown.
When AC100V, overall length of valve is
3.5mm longer.
4F**0E
HMV/
HSV
• DIN terminal box type(B)
Uniwire
system
SKH
DC
24
PCD/
FS/FD
Discrete
3, 5 port pilot operated valve
107
3GA2 Series
Discrete valve: Body porting
Dimensions
3GA2110
(File name: Page 239 or Ending 15)
• 2-position single solenoid, N.O. grommet lead wire
• Rc1/8 female thread type(06)
2B
4A
108
• Mounting plate type(P)
3GA2 Series
Discrete valve: Body porting
Dimensions
• E-connector type(E)
103: Connector axial
98: Connector radial
4SA/B0
50.5: Connector radial
45.5: Connector axial
4SA/B1
4GA/B
Note. Dimensions of DC specifications are shown.
When AC100V, overall length of valve is
3.5mm longer.
MN4GA/B
4GA/B
(master)
MN3S0/
MN4S0
• EJ-connector type(E**J)
4TB
4L2-4/
LMF0
4KA/B
4F
PV5/
CMF
3MA/B0
3PA/B
P/M/B
NP/NAP/
NVP
4F**0E
Note. Dimensions of DC specifications are shown.
When AC100V, overall length of valve is
HMV/
3.5mm longer.
HSV
Uniwire
system
• DIN terminal box type(B)
SKH
PCD/
FS/FD
Discrete
109
3, 5 port pilot operated valve
DC
24
3GA3 Series
Discrete valve: Body porting
Dimensions
3GA310
(File name: Page 239 or Ending 15)
• 2-position single solenoid, N.C. grommet lead wire
• Rc1/4 female thread type(08)
110
• Mounting plate type(P)
3GA3 Series
Discrete valve: Body porting
Dimensions
• E-connector type(E)
4SA/B0
4SA/B1
4GA/B
MN4GA/B
4GA/B
Note. Dimensions of DC specifications are shown. (master)
When AC100V, overall length of valve is
3.5mm longer.
MN3S0/
MN4S0
4TB
• EJ-connector type(E**J)
4L2-4/
LMF0
4KA/B
4F
PV5/
CMF
3MA/B0
3PA/B
P/M/B
NP/NAP/
NVP
4F**0E
HMV/
Note. Dimensions of DC specifications are shown. HSV
When AC100V, overall length of valve is
Uniwire
3.5mm longer.
system
SKH
• DIN terminal box type(B)
PCD/
FS/FD
Discrete
111
3, 5 port pilot operated valve
DC
24
3GA3 Series
Discrete valve: Body porting
Dimensions
3GA3110
(File name: Page 239 or Ending 15)
• 2-position single solenoid, N.O. grommet lead wire
• Rc1/4 female thread type(08)
112
• Mounting plate type(P)
3GA3 Series
Discrete valve: Body porting
Dimensions
• E-connector type(E)
4SA/B0
4SA/B1
4GA/B
MN4GA/B
4GA/B
Note. Dimensions of DC specifications are shown. (master)
When AC100V, overall length of valve is
MN3S0/
3.5mm longer.
MN4S0
4TB
• EJ-connector type(E**J)
4L2-4/
LMF0
4KA/B
4F
PV5/
CMF
3MA/B0
3PA/B
P/M/B
NP/NAP/
NVP
4F**0E
HMV/
Note. Dimensions of DC specifications are shown. HSV
When AC100V, overall length of valve is
Uniwire
3.5mm longer.
system
• DIN terminal box type(B)
SKH
PCD/
FS/FD
Discrete
113
3, 5 port pilot operated valve
DC
24
4GA1 Series
Discrete valve: Body porting
Dimensions
4GA110
(File name: Page 239 or Ending 15)
• 2-position single grommet lead wire(Blank)
• Mounting plate type(P)
49.9
(Manual override position)
12.8
19.6
1 P
10
2- 3.2 dia.
fixing hole
2- 3.2 dia.
21
5
1
3-M5
5(R1),1(P),3 (R2)Port
3
P
13.5
2.2
52
R1
R2
13.5
26
• M5 female thread type(M5)
M5 4 (A) port
13.5
20.2
37.4
M5 2 (B) port
1 P
114
4 17.8
49.8 (when manual cover open)
11.4
7.9
34.9
39.3
41.8
71.6
48.1: Push in joint 6 dia.
47.6: Push in joint 4 dia.
Push in joint 4, 6 dia. (selection)
2 (B) port
0.7
73.8
Push in joint 4, 6 dia. (selection)
4 (A) port
4
30
22
10
12
Lead wire length 300
(AWG#26, O.D. 1.35)
4GA1 Series
Discrete valve: Body porting
Dimensions
• E-connector type(E)
4SA/B0
84.5: Connector axial
79.5: Connector radial
4SA/B1
46: Connector radial
41: Connector axial
4GA/B
1 P
Note. Dimensions of DC specifications are shown.
When AC100V, overall length of valve is
3.5mm longer.
MN4GA/B
4GA/B
(master)
MN3S0/
MN4S0
4TB
• EJ-connector type(E**J)
4L2-4/
LMF0
4KA/B
4F
110.5: Connector axial
79.5: Connector radial
PV5/
CMF
3MA/B0
72: Connector radial
41: Connector axial
3PA/B
P/M/B
NP/NAP/
NVP
1 P
Note. Dimensions of DC specifications are shown.
When AC100V, overall length of valve is
3.5mm longer.
4F**0E
HMV/
HSV
Uniwire
system
SKH
PCD/
FS/FD
Discrete
3, 5 port pilot operated valve
115
4GA1 Series
Discrete valve: Body porting
Dimensions
4GA120
(File name: Page 239 or Ending 15)
• 2-position double grommet lead wire(Blank)
• Mounting plate type(P)
22.3
47.9
(Manual override position)
12.8
39.8
Push in joint 4, 6 dia. (selection)
2 (B) port
Push in joint 4, 6 dia. (selection)
4 (A) port
4
30
22
10
12
Lead wire length 300
(AWG#26, O.D. 1.35)
4
17.8
2- 3.2 dia.
10
103.8
2- 3.2 dia.
fixing hole
48.1: Push in joint 6 dia.
47.6: Push in joint 4 dia.
49.8 (when manual cover open)
11.4
1 P
1 P
7.9
39.3
41.8
92.5
21
20.2
11.3
52
5
1
3
R1
P
13.5
R2
13.5
3-M5
5(R1),1(P),3 (R2)Port
46.3
• M5 female thread type(M5)
13.5
M5 4 (A) port
40.5
37.4
M5 2 (B) port
1 P
116
4GA1 Series
Discrete valve: Body porting
Dimensions
• E-connector type(E)
4SA/B0
118: Connector axial
4SA/B1
109: Connector radial
41: Connector axial
46: Connector radial
4GA/B
MN4GA/B
1 P
Note. Dimensions of DC specifications are shown.
When AC100V, overall length of valve is
7mm longer.
4GA/B
(master)
MN3S0/
MN4S0
4TB
4L2-4/
LMF0
• EJ-connector type(E**J)
4KA/B
4F
PV5/
CMF
170: Connector axial
109: Connector radial
3MA/B0
3PA/B
NP/NAP/
NVP
4F**0E
41: Connector axial
72: Connector radial
P/M/B
HMV/
HSV
1 P
Note. Dimensions of DC specifications are shown.
When AC100V, overall length of valve is
Uniwire
system
7mm longer.
SKH
PCD/
FS/FD
Discrete
3, 5 port pilot operated valve
117
4GA1 Series
Discrete valve: Body porting
Dimensions
3
4GA145 0
(File name: Page 239 or Ending 15)
• 3-position grommet lead wire(Blank)
• Mounting plate type(P)
55.9
(Manual override position)
12.8
12
30
22
47.8
10
Lead wire length 300
(AWG#26, O.D. 1.35)
22.3
(Manual override position)
17.8
2- 3.2 dia.
4
4
Push in joint 4, 6 dia. (selection)
2 (B) port
Push in joint 4, 6 dia. (selection)
4 (A) port
1 P
2- 3.2 dia.
fixing hole
10
111.8
49.8 (when manual cover open)
48.1: Push in joint 6 dia.
47.6: Push in joint 4 dia.
11.4
39.3
7.9
41.8
100.5
21
52
11.3
28.2
5
1
3-M5
5(R1), 1(P), 3(R2) Port
3
P
R1
13.5
R2
13.5
54.2
• M5 female thread type(M5)
11.6
M5 4(A)Port
48.5
37.4
M5 2 (B)Port
1 P
118
4GA1 Series
Discrete valve: Body porting
Dimensions
• E-connector type(E)
4SA/B0
126: Connector axial
117: Connector radial
4SA/B1
41: Connector axial
46: Connector radial
4GA/B
MN4GA/B
1 P
Note. Dimensions of DC specifications are shown.
When AC100V, overall length of valve is
7mm longer.
4GA/B
(master)
MN3S0/
MN4S0
4TB
• EJ-connector type(E**J)
4L2-4/
LMF0
4KA/B
4F
178: Connector axial
117: Connector radial
PV5/
CMF
3MA/B0
3PA/B
NP/NAP/
NVP
41: Connector axial
72: Connector radial
P/M/B
4F**0E
1 P
Note. Dimensions of DC specifications are shown. HMV/
HSV
When AC100V, overall length of valve is
7mm longer.
Uniwire
system
SKH
PCD/
FS/FD
Discrete
3, 5 port pilot operated valve
119
4GA2 Series
Discrete valve: Body porting
Dimensions
4GA210
(File name: Page 239 or Ending 15)
• 2-position single grommet lead wire(Blank)
• Mounting plate type(P)
67.5
(Manual override position)
14.6
26.7
Push in joint 4, 6, 8 dia. (selection)
4 (A) port
5
2-2
Push in joint 4, 6, 8 dia. (selection)
2 (B)Port
93.7
46.4
4
14
43.9
2- width 4.4 oval hole
65.1: Push in joint 4, 6, 8 dia. common
4.3
89.7
46.4
25
36
27
10
19.4
Lead wire length 300
(AWG#26, O.D. 1.35)
17
17
5.8
62.6
2.7
4
17
0.5
4- 3.2 dia.
fixing hole
3-Rc1/8
5(R1),1(P), 3(R2)Port
17
17
31.3
• Rc1/8 female thread type(06)
2B
Rc1/8 4 (A) port
16
26
Rc1/8 2 (B) port
49.9
4A
120
4GA2 Series
Discrete valve: Body porting
Dimensions
• E-connector type(E)
103: Connector axial
98: Connector radial
4SA/B0
50.5: Connector radial
45.5: Connector axial
4SA/B1
4GA/B
MN4GA/B
Note. Dimensions of DC specifications are shown.
When AC100V, overall length of valve is
3.5mm longer.
4GA/B
(master)
MN3S0/
MN4S0
4TB
• EJ-connector type(E**J)
4L2-4/
LMF0
4KA/B
4F
129: Connector axial
98: Connector radial
PV5/
CMF
3MA/B0
3PA/B
76.5: Connector radial
45.5: Connector axial
P/M/B
NP/NAP/
NVP
4F**0E
Note. Dimensions of DC specifications are shown. HMV/
HSV
When AC100V, overall length of valve is
3.5mm longer.
Uniwire
system
SKH
• DIN terminal box type(B)
PCD/
FS/FD
Discrete
121
3, 5 port pilot operated valve
DC
24
4GA2 Series
Discrete valve: Body porting
Dimensions
4GA220
(File name: Page 239 or Ending 15)
• 2-position double grommet lead wire(Blank)
• Mounting plate type(P)
22.2
67
(Manual override
(Manual override position)
position)
14.6
48.4
5
25
2-2
123.2
4
14
46.4
43.9
2- width 4.4 oval hole
65.1: Push in joint 4, 6, 8 dia. common
Push in joint 4, 6, 8 dia. (selection)
2 (B) port
111.4
47.9
Push in joint 4, 6, 8 dia. (selection)
4 (A) port
4.3
36
27
19.4
Lead wire length 300
(AWG#26, O.D. 1.35)
17
5.8
17
62.6
24.4
11.8
17
0.5
4- 3.2 dia.
fixing hole
3-Rc1/8
5(R1),1(P),3 (R2)Port
17
17
31.3
• Rc1/8 female thread type(06)
2B
4A
Rc1/8 4 (A) port
16
26
49.9
Rc1/8 2 (B) port
122
4GA2 Series
Discrete valve: Body porting
Dimensions
• E-connector type(E)
137: Connector axial
128: Connector radial
4SA/B0
4SA/B1
50.5: Connector radial
45.5: Connector axial
4GA/B
MN4GA/B
Note. Dimensions of DC specifications are shown. 4GA/B
(master)
When AC100V, overall length of valve is
7mm longer.
MN3S0/
MN4S0
4TB
4L2-4/
LMF0
• EJ-connector type(E**J)
4KA/B
4F
PV5/
CMF
189: Connector axial
128: Connector radial
3MA/B0
3PA/B
76.5: Connector radial
45.5: Connector axial
P/M/B
NP/NAP/
NVP
4F**0E
HMV/
HSV
Note. Dimensions of DC specifications are shown.
Uniwire
When AC100V, overall length of valve is
system
7mm longer.
SKH
• DIN terminal box type(B)
PCD/
FS/FD
Discrete
123
3, 5 port pilot operated valve
DC
24
4GA2 Series
Discrete valve: Body porting
Dimensions
3
4GA2450
(File name: Page 239 or Ending 15)
• 3-position grommet lead wire(Blank)
• Mounting plate type(P)
78.7
(Manual override position)
Lead wire length 300
22.3
(Manual override
60.2
14.6
5
position)
25
2-2
17
17
5.8
62.6
36
27
4
17
4- 3.2 dia.
135
47.9
14
43.9
46.4
123.2
2- width 4.4 oval hole
65.1: Push in joint 4, 6, 8 dia. common
Push in joint 4, 6, 8 dia. (selection)
2 (B) port
Push in joint 4, 6, 8 dia. (selection)
4 (A) port
4.3
10
19.4
(AWG#26, O.D. 1.35)
36.2
17
3-Rc1/8
5(R2),1(P),3(R1)Port
17
31.3
• Rc1/8 female thread type(06)
2B
4A
Rc1/8 4 (A) port
16
26
49.9
Rc1/8 2 (B) port
124
11.8
0.5
fixing hole
4GA2 Series
Discrete valve: Body porting
Dimensions
• E-connector type(E)
Note. Dimensions of DC specifications are shown.
When AC100V, overall length of valve is
7mm longer.
149: Connector axial
140: Connector radial
4SA/B0
4SA/B1
4GA/B
4GA/B
45.5: Connector axial
50.5: Connector radial
MN4GA/B
(master)
MN3S0/
MN4S0
4TB
4L2-4/
LMF0
• EJ-connector type(E**J)
4KA/B
4F
Note. Dimensions of DC specifications are shown.
When AC100V, overall length of valve is
7mm longer.
201: Connector axial
140: Connector radial
PV5/
CMF
3MA/B0
3PA/B
P/M/B
4F**0E
HMV/
HSV
45.5: Connector axial
76.5: Connector radial
NP/NAP/
NVP
Uniwire
system
SKH
PCD/
FS/FD
24
82
DC
164.5 (DIN terminal box extrinsic direction)
Discrete
MAX10
161.2 (DIN terminal box intrinsic direction)
125
3, 5 port pilot operated valve
• DIN terminal box type(B)
4GA3 Series
Discrete valve: Body porting
Dimensions
4GA310
(File name: Page 239 or Ending 15)
• 2-position single grommet lead wire(Blank)
• Mounting plate type(P)
75.9
Lead wire length 300
(AWG#26, O.D. 1.35)
16.6
10
20.5
30.1
7.25
36.9
18.5
Push in joint 6, 8, 10 dia. (selection)
2 (B) port
Push in joint 6, 8, 10 dia. (selection)
4 (A) port
35.9
27.3
2-5
3-Rc1/4
5(R1),1(P),3 (R2)Port
20
3.7
6.3
20
37.9
• Rc1/4 female thread type(08)
19.8
28.5
Rc1/4 4 (A) port
58.7
Rc1/4 2 (B) port
126
2- width 4.5 oval hole
101.8
75.6: Push in joint 10 dia.
70.6: Push in joint 6, 8 dia. common
51.5
5.5
63
75.7
2- 4.5 dia.
fixing hole
17.8
48
50.6
4.3
98.2
4GA3 Series
Discrete valve: Body porting
Dimensions
• E-connector type(E)
111: Connector axial
106: Connector radial
4SA/B0
4GA/B
49.5: Connector axial
54.5: Connector radial
4SA/B1
Note. Dimensions of DC specifications are shown.
When AC100V, overall length of valve is
3.5mm longer.
MN4GA/B
4GA/B
(master)
MN3S0/
MN4S0
4TB
• EJ-connector type(E**J)
4L2-4/
LMF0
4KA/B
4F
137: Connector axial
106: Connector radial
PV5/
CMF
3PA/B
P/M/B
49.5: Connector axial
80.5: Connector radial
3MA/B0
Note. Dimensions of DC specifications are shown.
When AC100V, overall length of valve is
3.5mm longer.
NP/NAP/
NVP
4F**0E
HMV/
HSV
Uniwire
system
• DIN terminal box type(B)
SKH
PCD/
FS/FD
Discrete
127
3, 5 port pilot operated valve
DC
24
4GA3 Series
Discrete valve: Body porting
Dimensions
4GA320
(File name: Page 239 or Ending 15)
• 2-position double grommet lead wire(Blank)
75.2
22.3
(Manual override position)
16.6
(Manual override position)
51.6
7.25
36.9
2-5
Push in joint 6, 8, 10 dia. (selection)
4 (A) port
4.3
Push in joint 6, 8, 10 dia. (selection)
2 (B) port
75.7
20
3-Rc1/4
22
20
59.8
5(R1),1(P),3 (R2)Port
• Rc1/4 female thread type(08)
Rc1/4 4 (A) port
19.8
49.9
58.7
Rc1/4 2 (B) port
128
132.2
75.6: Push in joint 10 dia.
70.6: Push in joint 6, 8 dia. common
2- width 4.5 oval hole
12.6
6.3
63
5.5
17.8
50.6
48
51.7
119.7
2- 4.5 dia.
fixing hole
18.5
35.9
27.3
10
20.5
Lead wire length 300
(AWG#26, O.D. 1.35)
• Mounting plate type(P)
4GA3 Series
Discrete valve: Body porting
Dimensions
• E-connector type(E)
145.5: Connector axial
136: Connector radial
4SA/B0
54.5: Connector radial
49.5: Connector axial
4SA/B1
4GA/B
Note. Dimensions of DC specifications are shown.
When AC100V, overall length of valve is
7mm longer.
MN4GA/B
4GA/B
(master)
MN3S0/
MN4S0
4TB
• EJ-connector type(E**J)
4L2-4/
LMF0
4KA/B
4F
PV5/
CMF
197.5: Connector axial
136: Connector radial
3MA/B0
3PA/B
80.5: Connector radial
49.5: Connector axial
P/M/B
NP/NAP/
NVP
4F**0E
Note. Dimensions of DC specifications are shown.
HMV/
When AC100V, overall length of valve is
HSV
7mm longer.
Uniwire
system
SKH
PCD/
FS/FD
Discrete
DC
24
129
3, 5 port pilot operated valve
• DIN terminal box type(B)
4GA3 Series
Discrete valve: Body porting
Dimensions
3
4GA3450
(File name: Page 239 or Ending 15)
• 3-position grommet lead wire(Blank)
• Mounting plate type(P)
87.2
(Manual override position)
16.6
Lead wire length 300
(AWG#26, O.D. 1.35)
22.3
(Manual override position)
63.6
7.25
36.9
4.3
Push in joint 6, 8, 10 dia. (selection)
2 (B) port
Push in joint 6, 8, 10 dia. (selection)
4 (A) port
18.5
35.9
27.3
10
20.5
2-5
2- width 4.5 oval hole
3-Rc1/4
20
5(R1),1(P),3 (R2)Port
34
20
37.9
• Rc1/4 female thread type(08)
Rc1/4 4 (A) port
19.8
61.9
58.7
Rc1/4 2 (B) port
130
144.3
12.6
6.3
75.6: Push in joint 10 dia.
70.6: Push in joint 6, 8 dia. common
51.7
63.1
75.7
2- 4.5 dia.
fixing hole
5.5
17.8
48
50.6
131.7
4GA3 Series
Discrete valve: Body porting
Dimensions
• E-connector type(E)
4SA/B0
157.5: Connector axial
148: Connector radial
4SA/B1
54.5: Connector radial
49.5: Connector axial
4GA/B
MN4GA/B
Note. Dimensions of DC specifications are shown.
When AC100V, overall length of valve is
7mm longer.
4GA/B
(master)
MN3S0/
MN4S0
4TB
• EJ-connector type(E**J)
4L2-4/
LMF0
4KA/B
4F
PV5/
CMF
209.5: Connector axial
148: Connector radial
3MA/B0
3PA/B
NP/NAP/
NVP
49.5: Connector axial
80.5: Connector radial
P/M/B
4F**0E
HMV/
Note. Dimensions of DC specifications are shown. HSV
When AC100V, overall length of valve is
Uniwire
7mm longer.
system
SKH
• DIN terminal box type(B)
PCD/
FS/FD
Discrete
24
131
3, 5 port pilot operated valve
DC

Similar documents

4G /MN4G Series

4G /MN4G Series Piston speed of cylinder

More information

MAGNETIC BUBBLE APPARATUS

MAGNETIC BUBBLE APPARATUS magnetizing field H is applied, magnetization occurrs by the growth of one domain at the xpense of the others. The intensity of light transmitted through FMG is proportional to the magnetization M,...

More information

CKD Pneumatic Valves

CKD Pneumatic Valves Air supply/exhaust air method Pilot exhaust Internal pilot External pilot air method Piping direction Working fluid Valve and solenoid type Min. working pressure MPa Max. working pressure MPa Withs...

More information

4F0/1/2/3Series - CKDPneumatic.com

4F0/1/2/3Series - CKDPneumatic.com Discrete valve: Body porting MN3E0 Internal structure and parts list MN4E0 4GA/B

More information