MANUAL ATEX GEOFILTER GFX UK
Transcription
MANUAL ATEX GEOFILTER GFX UK
Instruction manual GeoFilter GFX The filter is as a main rule to be placed outside. If the only option is to place the filter indoors, the explosion hatch on the filter must be placed with direct access to the outdoors. Contents 1.0 General safety precautions 1.1 Danger 1.2 Field of application 1.3 Technical data 1.4 Construction – table of dimensions 2.0 Installation 2.1 Installation overview 2.2 Test run – exact adjustment 3.0 User instruction – application 4.0 Maintenance 4.1 Replacement of filter cartridges 4.2 Trouble shooting 5.0 Liability 6.0 Declaration of conformity If the filter is to be used for filtration of wood dust, then the filter must be placed outdoors and with a distance of minimum 2,5 meters from the closest building. The explosion hatch is to be placed, so that the hatch opens into the open, in case of explosion. The hatch must not be blocked from the outside and it should be placed so that neighbours and people passing through is not harmed in case of explosion. 1.2 Field of application 1.0 General safety precautions IMPORTANT - Please study all the instructions before mounting and commissioning. Please keep these instructions in a safe place and instruct all users in the function and operation of the product. Maintenance, replacement of filter cartridges/ emptying of collection bucket, should only be done in accordance with guide in section 4. The GeoFilter GFX can because of the ATEX approval (explosion hatch etc.) be used for filtration of aluminium, flavour, wood dust and other media associated with explosion danger (zone 20, 21 & 22(D)). The filter can naturally also be applied from such as welding fumes, where there is no risk of explosion. Mixing of various types of process is not recommended since it might increase the risk of explosion. Power cables and pneumatic air hoses should be replaced at once, if they are damaged. This should only be done by trained electrician and a HVAC technician. Do not dismantle any factory-mounted parts, since it impedes the commissioning of the equipment. All electrical installations must be carried out by an authorised electrician. 1.1 Danger Explosion danger – because the GFX filter is ATEX approved, the filter has been designed to minimize the risk of explosion in the best possible manner. In order to further minimize the risk of explosion it is required that the installation, service and use of the filter must conform with this instruction manual, why this must be read carefully before installation and use, since there is a risk of death or severe personal injury by explosion. It is deadly dangerous to dismount any part on the filter while this is in use. Always switch off the current when mounting or doing service on the Filter or when servicing it. Always run an extra cleaning cycle before the power is cut. 21-04-2005 ver. 1.0 www.geovent.com Side 1/9 Instruction manual GeoFilter GFX The GeoFilter GFB is delivered with filter cartridges of pleated textile with ALU-coating (minimum filtration efficiency of 99,90% according to BIA-test. The filter cartridges are cleaned automatically by a shock wave send down through the filter cartridges, whereby the particles that are caught in the filter fabric will fall off and land in the collection bucket bellow. The filter should as a main rule be placed out doors in order to minimize the damaged in case of an explosion (When the application is wood dust the filter must be placed at least 2,5 meter from the closest building). 1.3 Technical data No. of filters Filter area [m²] No. of pulse valves GFX-3-1 3 30 1 GFX-6-2 6 60 2 GFX-9-3 9 90 3 GFX-12-4 12 120 4 Model Max. Air Flow (*) Noise level according ISO-3746-1979 GFX-3-1 1.800 m³/h 72 dBA GFX-6-2 3.600 m³/h 74 dBA GFX-9-3 5.400 m³/h 78 dBA Model 7.200 m³/h 78 dBA GFX-12-4 *The filter cartridges are of pleated textile with an ALU coating. Compressed air tank [Liter] Art.No. Collection bucket GFX-3-1 4 15-400 25 Liter GFX-6-2 8 15-401 25 Liter GFX-9-3 12 15-402 25 Liter GFX-12-4 16 15-403 25 Liter Model The filter is ATEX approved, partly due to the explosion hatch, that in case of explosion in the filter, will insure that the explosion pressure is led out of the filter and into the open atmosphere. Compressed air : 6,0 bar – clean & dry air Air consumption : 3,0 liter/min per. valve Power supply : 24VDC or 230 VAC Temperature : -12°C - +65°C Noise emission : < 68 dB(A) Corrosion class : lll Pipe tightness : class C Filter types Standard Filter efficiency 99,90% v/0,3my Filter type Antistatic Washable Filter area Used for Standard No No 10,0 m² Allround BIA-test Material Coating U.S.G.C Polyester ALU Temperature extracted air Temperature surroundings Max 150°C Max -10°C - +50°C Relative air humidity has to be: <90% The noise level depends on several factors. I.e. the placement of the filter (indoor/outdoor), the size of the room, the temperature in the surroundings, the ambience, and the pressure drop in the filter, are all factors that influence the noise level. 21-04-2005 ver. 1.0 www.geovent.com Side 2/9 Instruction manual GeoFilter GFX Differential pressure for GFB-filter Typical pressure 1000-1500 Pa drop of running filter : Dimensions The pressure drop in the filter will vary depending on the load and how dirty the filter cartridges are. The filter cartridges must be replaced, when the pressure drop exceeds 2.000 Pa. The differential pressure may NOT increase above 3.000 Pa. 1.4 Construction Dimensions for GFX Model/Dimension [mm] A B øD GFX-3-1 775 325 ø250np GFX-6-2 808 625 ø315np GFX-9-3 850 925 ø400np GFX-12-4 900 1225 ø500np Outlet Free height Weight GFX-3-1 1x250np min. 800 90 kg GFX-6-2 2x250np min. 800 135 kg GFX-9-3 3x250np min. 800 180 kg Cabinet: Sturdy frame/cabinet, made of galvanised steel plate (corrosion class lll), with filter cone & directional plate in the inlet. GFX-12-4 4x250np min. 800 225 kg Filter medie: See filter table point 1.3. The filter should as a main rule be placed out doors in order to minimize the damaged in case of an explosion (When the application is wood dust the filter must be placed at least 2,5 meter from the closest building) Model/Dimension [mm] Compressed air tank: Epoxy coated Pulse valves: Anti static finish – Atex approved for zone 22D. Explosion Hatch: Brilex KER, Atex approved, i AISI 304 Automatic: Control panel with digital display, for adjustment of valve time, interval & after run cycle. Collection bucket: Galvanised – capacity up to 25L Extra equipment: As an option the filter can be supplied with a Rotor Lock and with extended legs in order to fit a container. The filter can also be delivered in a stainless steel version. 21-04-2005 ver. 1.0 2.0 Installation When the filter is placed out side, there should always be extracted clean & dry, 20°C hot air through the filter before use. This operation will minimize the damaged that can be caused by frost and humid air. The filter is delivered complete, fully mounted and pre-programmed from factory, ready to be connected to the ducting system and the mains. Before installing the filter, please make sure that the optimum installation area is selected. Is there room enough for the filter indoors? Is there space enough for carrying out satisfactory installation/service of the filter? What about optimum connection possibilities for piping and automatics? For outdoor mounting, any noise nuisances for neighbours should be taken into account and also ensure that the motor is kept out of heavy showers and cold weather. It is therefore recommended to build a small shed around the filter. www.geovent.com Side 3/9 Instruction manual GeoFilter GFX Recommended installation: Place the filter at least 2,5 meters from the building, with the explosion hatch pointing away from the building. Insure that random people passing by, can not be injured by the hatch or explosion pressure. should always be 2 meter above roof top, and keep an air velocity above at least 8 m/s. 7. It is also recommendable to build a protection roof above (and around) the filter in order to insure the filter the longest possible life and minimizes the risk of complications during operation. Connection of fan and filter to the mains: 8. Connection of the GFX filters electrical components should only be done by a professional electrician. If indoor installation is the only option, the filter must be placed so that the explosion hatch has direct access to the outdoors. Proper precautions, to insure that people passing by the explosion hatch is not harmed, must be taken. This can be done by a fence or proper shielding (visible signs). 9. Connect to the main via 220V + PE. 10. For possible combination/ connection possibilities please see the following diagrams & separate manual for GFX control panel. 2.1 Mounting overview The following installation should only be carried out by a trained fitter. Procedure: 1. The GFX filter has to be placed on a solid an even surface (i.e. a concrete floor). The free space above the filter has to be minimum 800 mm, to be able to change the filter cartridges. 2. The explosion hatch is lead through the wall and into the open (If installed indoors.) 3. The GFB filter has to be connected to circular spiral ventilation duct (SPIRO) on the clean & dust side (The lower connection side of the duct is always the dust side). Remember always to seal the assembly points with scotch seal and/or duct tape. 4. In some situations it can be necessary to install an automatic safety pressure release valve on the in/outlet side of the filter. 5. After wards connect 6 Bar clean & dry compressed air to the top of the filter – is fasten by means of a pipe plier. 6. To insure that the extracted air is blended with the clean air, the duct on the outlet side 21-04-2005 ver. 1.0 2.1.1 Connection of filters in parallel If the need for a larger capacity should arise, several filters can be connected in parallel (see pictures above). The filters can in theory be www.geovent.com Side 4/9 Instruction manual GeoFilter GFX connected in parallel infinitely. As a main rule two filters connected in parallel will share the same control panel. 2.1.2 Guide to control panel 2.2 Test run – fine adjustment CR = external on/off button CF = Connected to the potential free fan switch. Thus the fan is turned off, the CF has to be closed. • CR = Open Æ Control panel off • CR = Closed Æ Control panel on • CF = Open Æ normal operation • CF = Closed Æ shut down cleaning cycle 21-04-2005 ver. 1.0 Before use, check the functionality of the filter and adjust the filter cleaning cycle so that it is suits the current system needs. Make sure that the pause interval’s for the cleaning system is optimized for the current air flow – adjust if necessary (see separate guide for GFB control panel). Check if there is noticeable shaking or odd noise coming from the filter when in use. Make sure that the complete system is air tight. If whistling noises appears locate the leak and seal with scotch seal. It is recommended to check whether the supplies the correct volume of air, for which equipment has been dimensioned. I.e. control volume of air and make sure that it does exceed the ampere capacity of the motor. www.geovent.com fan the the not Side 5/9 Instruction manual GeoFilter GFX 3.0 User instruction – application 4.1.1 Emptying of collection bucket When the filter is installed correctly and is ready for use, there will be no interaction between the operator and the filter. Obviously the operator must be aware if there isn’t a correct flow in the system – in this case, see point 4.0 maintenance. Emptying of the collection bucket should be done when it’s about 2/3 full, because more loads could damage the filter medias. 1. The collection bucket is removed by unleashing the quick coupling on the side of the bucket. Then carefully pull the bucket out from underneath the filter. The particles in the bucket shall be destructed in proper manner by the current regulations. 2. The bucket is again placed the filter and strapped on. 4.0 Maintenance At least once annually, the whole point extraction plant should be overhauled by an authorised serviceman. Periodic maintenance: • Once a year check all the electrical parts on the filter. • Check that the compressed air supply is clean & dry, so that the filter cartridges and the pulse valves are not damaged by condensation. • Check the pressure difference through the filter and replace filter cartridges if the pressure drop is above 3.000 Pa. • Check the clean side (the outlet side) of the filter with even periods, and change the filter cartridges if leakage occurs. At least each 3 month should the filter cartridges be checked for leaks and flakes. In these cases shall this be fixed immediately (i.e. replacement of filter cartridges). Alternatively there can be mounted an Geovent Airbox on the filter, which measuret the differential pressure in the filter and gives alarm if the differential pressure is to high or low. It can also give a signal to the control panel to start a cleaning cycle, when a certain differential pressure level is reached. Using the conditions filter under extreme 4.1.2. Replacement of the filter cartridges The filter cartridges should be replaced after approximately 4000-8000 hours of use or max. 4 years. This is naturally determined by the work load on the filter and dependent on if it’s used for welding or grinding applications etc. Procedure: 3. Before the top of the filter is dismounted it is very important that the service technician is wearing the correct personal safety equipment, that meets the requirements of the current regulations. This could be gloves, special cloths and respiratory equipment. 4. All power must be turned off and it should be made sure that it can not be switch back on during service. 5. The compressed air connection shall be disconnected by means of a ball valve. If no ball valve is installed, turn off the compressor and empty the compressed air system for air. 6. Afterwards the compressed air supply hose is removed from the filter top by means of a pipe plier. weather Because of the changing weather conditions over the year, the daily operation of the filter might be influence by this. I.e. days with heavy rain or frost it is recommended to inspect the filter visually for leaks, and that the filter is running a cleaning cycle, before taking the filter in to use. This procedure is important in order to insure the longest possible living time. When servicing the filter, such as emptying the collection bucket or replacing the cartridges, it is ALWAYS required to wear antistatic outfit and garbage set. 21-04-2005 ver. 1.0 www.geovent.com Side 6/9 Instruction manual GeoFilter GFX 7. Unscrew all the screws that lock the top to the filter, with i.e. a 10 mm wrench. 8. Then remove the top of the filter. Take a firm grip in the mounted handles and be careful not to damage the compressed air system on the inside of the filter top. MAKE SURE NOT TO DAMAGE THE WIRERING TO THE PULSE VALVES (is not to be dismounted). The filter top (the lid) can be placed on the top of the filter or very close to. 9. 10. Then remove the plate, so that the cartridges are easy to pull up. 11. The contaminated filter cartridges is carefully lifted up and placed in a large disposal bag that is to be sealed properly. Afterwards remove the 10 mm bolts on the plate that keeps the filter cartridges to the filter with a wrench. 21-04-2005 ver. 1.0 www.geovent.com Side 7/9 Instruction manual GeoFilter GFX 12. The new filter cartridge is carefully placed in the filter (so the media isn’t damaged) and is fastened with the plate that holds the cartridges. 4.2 Trouble-shooting If a situation where problems with increase pressure drop or low air flow should occur, please see the following points. Dust is pushed back and dust is coming back out through outlets. The cleaning system has to “push” to much dust of the cartridges at a time, and the dust is pushed out into the duct. Chance the pause interval on the control panel so the time between each cleaning cycle is lowered until there is no dust coming out of the outlets (I.e. if the interval is set at 12 minutes, it can be lowered to 10 minutes. If this is not enough lower it further). 13. The top of the filter is cautiously placed on the filter again and tighten with the bolts that were removed earlier (remember to reconnect the power and the compressed air). Give the lit a small push so that it is placed correctly. The Pulse valves sounds like they are ”snoring”. Lower the shooting/pulse time with 0.25 sec. until the “snoring” sound disappears. The pressure drop/difference is rising when in use and the air flow is falling equivalently. The cleaning cycle can not keep up with the dust load. Lower the Pause interval until the pressure drop again is normal. The filter cartridges need to be changed if this does not work. 14. The used and contaminated filter cartridges are to be sent to destruction at the local garbage central. 15. Check the functionality of the filter and for leaks. 21-04-2005 ver. 1.0 www.geovent.com Side 8/9 Instruction manual GeoFilter GFX 5.0 Liability Warranty Geovent A/S grants a warranty for products, which are defective, when it can be proved that the defects are due to poor manufacture or materials on the part of Geovent. The warranty comprises remedial action (reparation or exchange) until one year after date of shipment. No claims can be made against Geovent A/S in relation to loss of earnings or consequential loss as a result of defects on products from Geovent. Wear on parts such as filter cartridges is not included in the warranty. User liability In order for Geovent to be capable of granting the declared warranty, the user/fitter must follow this Instruction Manual in all respects. Under no circumstances may the products be changed in any way, without prior written agreement with Geovent A/S. 6.0 Declaration of conformity The manufacturer: GEOVENT A/S HOVEDGADEN 86 DK-8831 LØGSTRUP hereby declares that: Product: Model: GeoFilter GFX GFX-3-1, GFX-6-2, GFX-9-3, GFX-12-4 has been manufactured in compliance with the directions of the Directive Council of 14 June 1989 in common approximation to the legislation of the member states regarding machine safety (89/392/EEC amended by the directive 91/368/EEC) with special reference to appendix 1 in the Directive regarding basic health and safety requirements in connection with the construction and manufacturing of machinery. Atex directive 94/9/EF materiel group II, Category 2D & may be used in zones classified as zone 20, 21 & 22. GEOVENT A/S • HOVEDGADEN 86 • DK-8831 LØGSTRUP Position: Name: Managing Director Steen Molsen Dato: 20/04/2005 Signature : ____________________________ ATEX Certificate Production data + Serial Number CE …. EX II1D st.1 21-04-2005 ver. 1.0 www.geovent.com Side 9/9