6000 InSitu Analyser System
Transcription
6000 InSitu Analyser System
C O M T E C® 6000 O2 / COe* InSitu Analyser System Installation & Operating Manual Version No. 05 Valid for Software Version 3.00.15 Revision Date: 08 November 2010 O2 CO * 2,6 % 17 ppm COe is the short hand for CO equivalent . For more information please contact ENOTEC. O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 1 of 80 O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 2 of 80 Table of Contents 1 General User Information 6 1.1 Preface 6 1.2 Warranty 7 1.3 Declaration of EC-Conformity 8 1.4 System Overview 9 1.5 Package List for a COMTEC® 6000 InSitu Analyser System 10 1.6 Information on the CE-Certification 11 1.7 Notes on this Manual 11 1.8 Symbols used in this Manual 12 1.9 Intended Use 12 1.10 General Safety Instructions 13 1.11 Corrosion 13 1.12 Safety Hazards 13 COMTEC® 6000 Installation Information 14 Installation of the Electronic Unit and Electrical and Pneumatic Cables 14 Requirements at the Mounting Place of the Electronic Unit 14 Requirements for the Probe Signal Cable FEP0007/8 15 2.4 Requirements for the Pneumatic Cable FEP-0002 15 2.5 Installation of the Electronic Unit 16 2 2.1 2.2 2.3 2.5.1 Access to the terminals 16 2.5.2 Wiring Diagram of the Electronic Unit 17 2.5.3 Function of the relay contacts 18 ® 2.5.4 Wiring Diagram of the COMTEC 6000 Analyser System 2.6 2.7 Preparation and Connection of the Pneumatic Cable FEP-0002 at the Electronic Unit 19 20 2.6.1 Preparation of the Pneumatic Cable 20 2.6.2 Connection of the Pneumatic Cable 21 Installation of the probe with all electrical and pneumatic connections O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 22 Page 3 of 80 2.8 Requirements at the Mounting Place of the Probe 22 2.9 Mounting of the Mating Flange at the Duct 23 2.10 Adjustment of the Probe Filter Head 2.11 Mounting of the Probe Protection Tube at the Mounting Flange 24 Connection of the Probe Signal Cable FEP-0007/8 and Pneumatic Cable FEP-0002 at the Measuring Probe 25 2.12 2.13 3 V-Shield 23 2.12.1 Electrical Connections 25 2.12.2 Pneumatic Connections 26 Insulation of the Protection Tube outside the Duct System Start Up and Calibration 26 27 Description of the Electronic Unit for COMTEC® 6000 InSitu Analyser Systems 27 3.2 General Description of the Function 27 3.3 General operating instructions 28 3.4 Start-up of the COMTEC® 6000 InSitu Analyser System 29 3.5 COMTEC® 6000 Probe heating phase 29 3.6 Amounts and Adjusting of Test gas and Reference air 30 3.1 3.6.1 Reference air 30 3.6.2 Test gas 31 3.7 Main Window 32 3.8 Values (Actual Value Menu) 33 3.9 Parameter Menu 35 3.10 3.9.1 Altering a Parameter by the Example of the O2 Measuring Ranges 38 3.9.2 Altering a Parameter by the Example of a Limit Alarm Value 38 3.9.3 O2 Correction ‘wet’ or ‘dry’ value 40 Menu / Cal. 41 3.10.1 First Steps for Calibration 43 3.10.2 Two point System test + Calibration for O2 and COe 44 3.10.3 O2 Output Settings 47 3.10.4 COe Output Settings 48 3.10.5 Common … Settings 48 O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 4 of 80 3.10.6 COe … Measurement OFF 4 Service and Maintenance 4.1 51 Service and maintenance of the COMTEC® probes 51 4.1.1 Replacing filter element 51 4.1.2 Replacing filter head 52 4.1.3 Exchange of probe inner part 53 4.1.4 Exchange of ZrO2 sensor 54 4.1.5 Exchange of the COe sensor 55 4.2 Status messages/Error messages 57 4.3 Troubleshooting 61 4.4 5 4.3.1 Unsteady, widely varying Measuring Value (O2) 61 4.3.2 No COe-Measuring Value; Arrow instead of a value 61 4.3.3 No Measuring Value for O2; empty Bar Graph 61 4.3.4 O2 reads higher than expected, and COe reads lower than expected 62 4.3.5 O2 Display remains at the End of the Measuring Range or is higher than expected 62 Exchange Fuses and change of Voltage 63 Technical Datas and Drawings 64 5.1 Requirements of the Gas Supply 64 5.2 Probe 65 5.2.1 Dimensional drawing of probe KES600x 66 5.2.2 Protection tube flange 66 5.2.3 Adapter plate ADP-6000 67 5.2.4 Adapter plate ADP-6000-S01 67 5.2.5 Probe components 68 5.3 Electronic Technical Data & Dimensions 69 5.4 Gas plan SME-5 Instrument air (Version A) 71 5.5 Gas plan SME-5 Instrument air (Version 1) 72 5.6 Gas plan SME-5 with O2 Reference air pump 73 6 7 50 Electronic Assembly Overview 74 6.1 Mounting plates of Field housing 74 6.2 Mounting plates of 19”Rack 76 Table of figures O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 78 Page 5 of 80 1 General User Information 1.1 Preface Dear customer, Thank you for selecting our COMTEC® 6000 as your InSitu Flue Gas Oxygen/Combustibles (COe*) measuring system. ENOTEC has been producing its world famous OXITEC® Oxygen Analysers for more than 30 years, and now our COMTEC® Oxygen/Combustibles (COe) measuring system enhances our product line. ENOTEC are committed to total quality and performance and we have continuously enhanced our products to integrate various additional features and functions. In this package, the electronic unit uses the very latest Microprocessor Technology, making the SME5 electronic unit one of the most advanced and up-to-date monitoring units permitting you to reduce your maintenance & fuel costs to achieve an increased measuring accuracy with more operational reliability due to new monitoring functions. In our COMTEC® 6000 probes you will find the Zirconium Oxide measuring sensor which is gas-tight sealed in place using a special process and technique developed by our company. This leads to a considerably increased service life as compared to "glued or cemented" measuring sensor that has a tendency to leak or crack during operation. The O2 sensor is a proven gastight design providing greater measuring accuracy, durability and longer working life with the experience of more than 30,000 installations. For COe measurement, we have integrated a high temperature MXP- sensor. All ENOTEC instruments are thoroughly tested in the factory and are subject to a strict ISO 9001 Quality Assurance procedure. Therefore, with the correct installation, the operation of the COMTEC® 6000 InSitu Analyser System is very easy to use and user friendly. It will provide you with many years of operation with perfect measuring results. Please read this manual carefully and follow the instructions as directed. If you have any questions, or you are unclear about any aspect of the installation or operation, our Service Department, regional sales offices or approved distributors will be pleased to assist. The factory contact points are Tel: +49 2264-45780 or Fax: +49 2264 457831. You may also visit us at our website http://www.enotec.de or http://www.enotec.com or contact us by e-mail: info@enotec.de. Marienheide, January 2010 Dipl.-Ing. Fred Gumprecht Managing Director ENOTEC GmbH * COe is the short hand for COequivalent O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 6 of 80 1.2 Warranty ENOTEC 2 YEAR WARRANTY ENOTEC warrants that the equipment manufactured and sold by it will, upon shipment, be free of defects in workmanship or material. Should any failure to conform to this warranty become apparent during a period of two years after the date of shipment, ENOTEC shall upon prompt written notice from the purchaser, correct such nonconformity by repair or replacement of the defective part or parts. The purchaser is not entitled to claim any other legal remedies on the basis of this warranty. Please refer to the complete ENOTEC warranty policy for details. ENOTEC does not warrant equipment supplied by it against normal deterioration. Corrosive gases and solid particles may cause damages and make a repair or a replacement necessary as a consequence of normal wear and tear during the warranty period. The COe sensor is such a product, with a guarantee limited to one year. All ENOTEC products and systems which do incorporate a heated sensor must be operated under continuous conditions. If the heater power is switched off and on regularly, more thermal stress for the probe heater, the probe thermocouple and the ZrO2 cell will cause shorter life time. If it is not possible to operate the heated equipment continuously for a longer period of time, please contact ENOTEC for technical advice. Note: When installing the equipment, the customer must ensure that all necessary supply lines are connected and the operating temperature of the probe is reached. Experience has shown that products installed but not put into operation may be damaged by the process or by external influence. ENOTEC will not accept any responsibility for such damages. ENOTEC does not warranty ENOTEC products and systems which have been combined with products or components from suppliers not approved by ENOTEC (e.g. probe signal cable, probe flange gaskets). When installing and commissioning ENOTEC products and systems, you have to use proper tools. If there is any damage due to the use of wrong tools, ENOTEC will not accept any responsibility for damages. MANUFACTURER: ENOTEC GmbH Höher Birken 6 D-51709 Marienheide, Germany TEL: +49 (0) 2264 / 45780 FAX: +49 (0) 2264 / 457831 Email: info@enotec.de O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 7 of 80 1.3 Declaration of EC-Conformity ENOTEC GmbH Höher Birken 6 51709 Marienheide/Rodt Germany CE Mark - Conformity to EC Directive Electromagnetic Compatibility 2004/108/EG ® We declare that the COMTEC 6000 InSitu Analyser System as detailed below due to its design and construction as well as the type sold by us complies with the relevant basic safety and health requirements of the EC Directive. This declaration becomes invalid if the appliance is modified without our prior consent. Identifier: Evaluation electronics Type: Relevant EC-directives: ® COMTEC 6000 InSitu Analyser System ...................................................................................... SME 5 ...................................................................................... EC Low-voltage Directive (73/23/EEC) EC Directive Electromagnetic Compatibility (89/336/EEC) EC Directive Product Liability (85/374/EEC) Applied harmonised generic standards: Applied standards and technical specification, in particular: EN 55011 Kl.A:2007 Emission EN 61000-6-2:2005 Resistance to interference EN 61000-3-2:2006 Current harmonics EN 61000-3-3:1995 + A1,A2 Flicker EN 61000-4-2:2001 EN 61000-4-3:2006 ESD Irradiation E-field EN 61000-4-4:2005 Burst EN 61000-4-5:2001 Surge EN 61000-4-6:2001 Inflow E-field EN 61000-4-11:2005 Voltage dip EN 61000-3-2 Current harmonics EN 61000-3-3 Flicker CISPR 16-1 Interference voltage Kl.A CISPR 16-1 Radiation E-field Kl.B Date / Manufacturer’s signature: 1st August 2008 signed Fred Gumprecht ..................................................................................... Position: Managing Director ..................................................................................... O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 8 of 80 1.4 System Overview 8 O2 2,6 % CO 23 ppm 1 a b c d e 2 3 4 6 7 5 Figure 1 System overview System components Electronic unit SME5 Probe signal cable FEP-0007/8 Pneumatic cable FEP-0002 O2/COe-Probe Protection tube Mating flange O2/COe COMTEC 6000 InSitu Analyser System Customer components Processing room Test gas 2 Instrument air/Reference air (with pump) Power supply Output signals (analog and digital) Test gas 1 (only instrument version A and version with pump) Process gas Version 05.300.15 Page 9 of 80 1.5 Package List for a COMTEC® 6000 InSitu Analyser System • • • • Probe with protection tube and gaskets Probe Signal Cable (if ordered) Probe Pneumatic Cable (if ordered) Electronic unit with the product manual and parts kit: Quantity Part No. Description 6 0-L-000033 ferrite sleeves 1 0-F-000069 fuse 6.3 A semi time-lag (spare part) 1 0-F-000083 fuse 4.0 A semi time-lag (spare part) 1 0-F-000084 fuse 1.0 A semi time-lag (spare part) 1 0-F-000113 Fuse 1.0 A fast acting (spare part) 9 0-P-000092 support sleeves for Parker ¼’’ pneumatic connection to link the FEP-0002 at the probe terminal box 1 0-R-000055 clamp ring for Parker ¼’’ pneumatic connection to link the FEP-0002 at the probe terminal box (spare part) 1 0-R-000056 nut for Parker ¼’’ pneumatic connection to link the FEP-0002 at the probe terminal box (spare part) 1 0-R-001960 Closure to cover the COe sensor guiding tube inside the probe terminal box. Please use also a gasket-set. 1 0-P-000992 Gasket set O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 10 of 80 1.6 Information on the CE-Certification After having completed and successfully passed EMC-tests, the complete ENOTEC InSitu Analyser System - consisting of measuring probe, electronic unit and probe signal cable - has a conformity certificate. If parts of this system are operated with products not supplied or approved by ENOTEC, the CE-conformity is no longer valid. Likewise, all warranties are void if the system is operated in a configuration not authorized by ENOTEC! Note The enclosed ferrite sleeves must be placed over the terminal leads of the cable (see wiring chapter 2.5.2). The CEconformity is void if these ferrite sleeves are not fitted! Note The ground (Earth) connection must be installed thoroughly using the correct cable of at least 1,5 mm² minimum. It is very important that the equipotent bonding is installed correctly. Please note that some electrical devices (e.g. frequency converter etc.) close to the system can create considerable electrical disturbance and instability. So for normal function of the COMTEC® 6000 InSitu Analyser System it is important that these devices be installed away from the system and in accordance with the manufacturer’s installation notes and guidelines. Please do not run the probe cable near power supply cables, or near motors and their cables, as frequency converters control them because this could cause interference effects. If possible, do not cross the cables because this could interference effects. However, if this is unavoidable please make sure that these cables are only crossed at right angles. 1.7 Notes on this Manual This document describes the design, installation, commissioning, operation, maintenance and trouble-shooting of the COMTEC® 6000 InSitu Analyser System. Only authorized, qualified personnel may work on this equipment. These personnel must be familiar with all warnings, safety references and maintenance tasks in accordance with this instruction manual. The perfect and safe use of this equipment presupposes appropriate transport, professional storage and installation as well as careful operation and maintenance. O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 11 of 80 1.8 Symbols used in this Manual Important information as well as safety instructions are emphasised by the below-mentioned symbols. Please make sure that all safety advices and warnings are observed at all times. Note Advises important information, which should be pointed out particularly. Important Warns of the risk to damage parts or the complete system or to reduce its function. Warning Warns of dangers, which results from inappropriate handling and which can entail death, bodily harm and/or substantial property damage. Warning – Hot Surface Warns of the danger from burns, which result from hot system parts. 1.9 Intended Use Note The COMTEC® 6000 InSitu Analyser System is a system for measuring the oxygen concentration and the concentration of COe* in flue gases. For reasons of safety and the possible occurrence of accidents, unauthorized conversions and modifications of the system are prohibited. Warning The minimum concentration of O2 in flue gas should, under normal process conditions, not be less than 0.5%. The system must not be used for the determination of the O2/COe content of gases, whose lower explosion limit (LEL) can be exceeded. There is danger of explosion, since the measuring cell temperature of the O2 measuring cell is 840 °C (1544 °F). * COe is the short hand for COequivalent O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 12 of 80 1.10 General Safety Instructions The COMTEC® 6000 InSitu Analyser Systems may only be operated by authorized trained skilled persons. For reasons of immunity to interference, it must be ensured that the connection between measuring probe and electronic unit is only made with the ENOTEC probe signal cable and pneumatic tubing. The O2/COe measuring probes supplied by us may only be used with ENOTEC electronic units or with compatible electronic units approved by ENOTEC. Important Under no circumstance may the measuring probe be directly connected to the 230V main power, as this will immediately destroy the probe heater element! 1.11 Corrosion The probe may only be used in flue gases whose composition is uncritical regarding the corrosive effect on the materials used. With increased risk of corrosion, regular checks at suitably short intervals are necessary. 1.12 Safety Hazards Warning – Hot Surface During operation, the temperature of the probe filter head and of all parts exposed to flue gas is 150 °C – 500 °C (302 °F932 °F). Direct contact with the hot parts for dismantling or maintenance will cause severe burns! The probe may only be removed with heat-insulated gloves. Before removing the probe, always switch off the supply voltage to the electronic system. After removal, store the probe in a safe, protected place and wait until it has cooled downs below 35 °C (95 °F). O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 13 of 80 2 COMTEC® 6000 Installation Information 2.1 Installation of the Electronic Unit and Electrical and Pneumatic Cables Note Only qualified and authorized personnel may work on this instrument. These personnel must be familiar with all warnings, safety instructions and maintenance work in accordance with these operation instructions. The reliable and safe operation of this equipment requires careful transportation, professional storage, and installation and commissioning, as well as careful operation and maintenance. 2.2 Requirements at the Mounting Place of the Electronic Unit Keep the minimum distance to adjacent objects Install in eye height Avoid vibrations greater 2g Keep the protection class Ambient temperature with instrument air Min.: -20 °C/Max.: +55 °C Ambient temperature with pump Min.: -20 °C/Max.: +50 °C O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 14 of 80 2.3 Requirements for the Probe Signal Cable FEP-0007/8 Keep the maximum cable length (max.50m) Max. 50 m Note the minimum bending radius. FEP-0007Rmin=252 mm FEP-0008 Rmin=329 mm during installation during operation +50 °C Max. -5 °C Min. +90 °C Max. Note the temperature limits -40 °C Min. Cross the probe signal cable (FEP-0007/8) at right angle to the power supply cables 2.4 Requirements for the Pneumatic Cable FEP-0002 Note the minimum bending radius. FEP-0002Rmin=138 mm during installation during operation +50 °C Max. -5 °C Min. O2/COe COMTEC 6000 InSitu Analyser System +90 °C Max. -40 °C Min. Version 05.300.15 Note the temperature limits Page 15 of 80 2.5 Installation of the Electronic Unit Note You find dimensional drawings of the Electronic unit under the chapter 5.3. Drillings for the electronic unit Use suitable screws Electronic unit Figure 2 Installation of the Electronic unit 2.5.1 Access to the terminals Loosen the Phillips screws M4 and remove the terminal cover Terminals for power supply and the O2/COe Probe Figure 3 Access to the terminals Terminals for analog and digital signals To connect the wires with a small screwdriver, follow step 1 to 3. Figure 4 Instruction for the function of the terminals O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 16 of 80 2.5.2 Wiring Diagram of the Electronic Unit Figure 5 Wiring diagram of the electronic unit Ferrite sleeves (Enclosure) Power supply cable (provided by the customer) Analog output cable (provided by the customer) status signal cable (provided by the customer) Probe signal cable FEP-0007/8 Internal Power supply (115/230V 1 AC, 50/60Hz,max 1A) 4 L Phase 5 N neutral wire 6 PE grounding conductor Power supply (115/230V AC, 50/60Hz) 1 L phase 2 N neutral wire 3 PE grounding conductor Shielding Shield terminal Power supply probe heater (115V) 8 L black 9 N blue 10 PE green/yellow O2-sensor signal 12 + brown 13 brown/white Thermocouple (O2) 14 + green 15 white Probe solenoid valve 23B L Supply for probe 23B N solenoid valve (115VAC) 24A L grey 24B N grey/blue COe sensor 32A white 2 COe sensor in 32B white 1 33A red 4 COe heater out 33B red 3 Analog outputs (active 4-20mA) 17A + O2 17B O2 34A 34B + - COe COe Relay contacts for status signals 18 A/B Maintenance 19 A/B 20 A/B System Error Output A COe Maint./O2 MR 21 A/B O2 Limit Alarm 1 22 A/B O2 Limit Alarm 2 Measuring Range O2 (12..24V DC) 25A + 25B Calibration release (12..24V DC)) 27A + 27B - 1 The output voltage of this contacts(4…6) has always the same voltage as on the power supply input on contacts (1…3) O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 17 of 80 2.5.3 Function of the relay contacts Relay contact System error Contact closed No system error Maintenance System off or maintenance is active System off, maintenance or measuring range is active Output A COe maintenance or O2 measuring range O2 Limit Alarm 1 O2 Limit Alarm 2 O2/COe COMTEC 6000 InSitu Analyser System No O2 Limit Alarm 1 active No O2 Limit Alarm 2 active Version 05.300.15 Contact open System off, probe is heated or system error is active. (Details of error messages see chapter 4.2) No maintenance No maintenance or no measuring range is active System off or O2 Limit Alarm 1 active System off or O2 Limit Alarm 2 active Page 18 of 80 2.5.4 Wiring Diagram of the COMTEC® 6000 Analyser System Figure 6 Wiring and terminal connection diagram of COMTEC® 6000 O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 19 of 80 2.6 Preparation and Connection of the Pneumatic Cable FEP-0002 at the Electronic Unit 2.6.1 Preparation of the Pneumatic Cable Figure 7 Mounting instructions for pneumatic tubes Components for the pneumatic connections Pneumatic tubing of the pneumatic cable FEP-0002 Nut Clamp ring Support sleeve Both, the pneumatic tubing for the reference air (blue) and the test gas and (green) have to be prepared with support sleeves , clamp rings nuts. O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 20 of 80 2.6.2 Connection of the Pneumatic Cable 2.6.2.1 Field housing Cable glands M20 (for power supply cable) M25 (for FEP-0007/8 probe signal cable) M20 (Signal cable) M20 (Signal cable) Spare Pneumatic connections (¼”) Test gas 2 in Figure 8 Connections of the COMTEC® 6000 Field housing Test gas out (green tubing of FEP-0002) Instrument air in (system with Instrument air version) or Reference air in (system with pump version) Reference air out (blue tubing of FEP-0002) Test gas 1 in (only instrument version A and version with pump) 2.6.2.2 19” Rack 1 3 2 4 5 Figure 9 Gas connections of the COMTEC® 6000 in 19’’ rack Pneumatic connections (¼”) Test gas 1 in (only instrument version A and version with pump) Test gas out (green tubing of FEP-0002) Instrument air in (system with Instrument air version) or Reference air in (system with pump version) Reference air out (blue tubing of FEP-0002) Test gas 2 in O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 21 of 80 2.7 Installation of the probe with all electrical and pneumatic connections Note Only qualified and authorized personnel should work with this instrument. These personnel must be familiar with all warnings, safety instructions and maintenance work in accordance with these operating instructions. The fault free and safe operation of this equipment requires proper transportation, professional storage, set up and installation, as well as careful operation and maintenance. 2.8 Requirements at the Mounting Place of the Probe Flue gas temperature, pressure and all other process conditions must be in accordance with the specification. Leave enough space for insertion/removal of the probe and protection tube (if supplied) and ensure access to the measuring probe and/or connecting box. Before cutting the hole in the flue gas duct, make sure that the inside of the duct has enough space for probe installation, and that no soot is blown out nearby, or any obstacles are in the way. For probe lengths exceeding 2000 mm, a support must be mounted inside the duct (every 2 m) to prevent the probe and mounting tube from flexing or bending. +80 °C Max. max. 500°C -40 °C Min. Avoid vibrations greater 2g The ambient temperature at the connection box and the process temperature must not be exceeded. Keep the protections class of the connection box. O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 22 of 80 2.9 Mounting of the Mating Flange at the Duct The flange has to be mounted with an angle of 1° to 3° densed flue gas elements can flow back into the duct. , so that the con- 1° - 3° D A 3 Schnitt A-A A 1 2 Figure 10 Mounting of the mating flange at the duct Pitch of the mating flange The flange has to be welded gastight. Mating flange (supplied by customer) See dimensions in chapter 5.2.3 or 5.2.4 2.10 Adjustment of the Probe Filter Head V-Shield Note Find out the flow direction of the process gas at the installation place. Figure 11 Adjustment of the measuring probe in the flue gas O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Unscrew the retaining ring (clockwise) with a hook wrench Turn the filter head Vshield into the right position with a pin wrench Adjust the position of the shield against the flow direction Fix the retainer ring after adjusting the filter head Page 23 of 80 2.11 Mounting of the Probe Protection Tube at the Mounting Flange Note Use for the installation of the probe only new and undamaged gasket. Tighten the nuts firmly, to guarantee the density of the flange connection. Isolate the counter flange. Never leave the probe longer time unheated in the running process. Figure 12 Mounting of the protection tube at the mounting flange Adapter plate Protection tube Protection tube flange gasket Connection box O2/COe probe Probe flange gasket Probe flange O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 24 of 80 2.12 Connection of the Probe Signal Cable FEP0007/8 and Pneumatic Cable FEP-0002 at the Measuring Probe 2.12.1 Electrical Connections Note The Probe Signal Cable FEP-0007/8 has to be connected to the terminal board in the probe terminal box. Please do not fix the shield here. (Same terminals as in chapter 2.5.4) 1 2 3 4 6 7 8 ws/br wh/br braun grün weiss schw. blau gr.ge. brown green white black blue gr.ye. - + + - L N mV Messzelle cell mV Thermoelement thermocouple 9 10 11 12 13 14 2 1 grau gr.-bl. ws/rt ws/rt grey gr.-bl. wh/rd wh/rd 3 4 rot rot red red L N RS RH 115 V ~ Sondenheizung probe heating 115 V ~ Magnetventil solenoid valve 0,5V 15V COe-Sensor COe-sensor COe-Sens. Heiz. COe-sens. heat. Figure 13 Electrical connections of the measuring probe O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 25 of 80 2.12.2 Pneumatic Connections Blue tubing (Ref. air) Green tubing (Test gas) Cable glands for probe signal cable (FEP-0007/8) 1 2 3 Figure 14 Connection of the pneumatic tubes at the measuring probe The two pneumatic tubes – blue and green have to be fixed at the probe terminal box. Please follow the colour code: connect the green tubing with the green ring and connect the blue tubing to the blue ring Note For mounting instructions of the pneumatic tube see chapter 2.6.1 2.13 Insulation of the Protection Tube outside the Duct Note If a cooling protection tube is used, the part of the protection tube outside the duct wall must be insulated or heated if necessary, to prevent flue gas temperature inside the probe below the dew point. Electrical heaters are available from ENOTEC as accessories. The bolts of the probe flange must remain accessible. The probe protection tube has to be insulated outside the duct to avoid temperatures below the acid dew point of the flue gas inside the probe. 1 Figure 15 Insulation of a probe protection tube O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 26 of 80 3 System Start Up and Calibration 3.1 3.2 Description of the Electronic Unit for COMTEC® 6000 InSitu Analyser Systems General Description of the Function The SME 5 electronic unit is designed for connection to one O2/COe measuring probe. The mV signal of the measuring sensors are amplified and then converted into a digital signal in the electronic unit (14 Bit converter). The µprocessor linearises and corrects the signal according to Nernst’s equation of the O2 measuring sensor. The O2 value is then displayed as a percent value and the mA output has an isolated 4 - 20 mA output. The COe measurement is achieved as a mV measurement of the heated COe sensor. The COe sensor temperature is controlled. The SME 5 microprocessor converts this voltage into a digital signal and displays ppm COe and drives the 4-20 mA output. As a standard, the electronic unit has two O2 measuring ranges and one COe measuring range. These measuring ranges can be freely defined in their initial and/or final value (within permissible system-related limits). The second O2 measuring range can be switched remotely 3.9.1 on page 38). The second O2 measuring range is signalled by a relay contact to the outside. The electronic unit is completely self-controlled. Any system errors occurring are displayed as clear text with an online help function for information. The COMTEC® user Interface permits intuitive operation by means of a selfexplanatory menu structure. Until the COMTEC® 6000 probe has reached its operating temperature, the System Error contact is open and the display shows that the probe is heating up. The progress of the heating phase is shown by a bar indicating the current probe temperature. During the heating phase, all system parameters, as well as (actual) values in the corresponding menus, can be selected on demand from the keypad. When the probe has reached its operating temperature and is stable within ± 0.1 °C, actual measurements are read, the System Error contact closes and the standard actual value display appears on the screen. The system is now ready for O2/COe measurement. O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 27 of 80 3.3 General operating instructions The electronic unit is operated by means of four soft keys and a numeric keypad. The functions of the soft keys always adapt to the current menu window. The numeric keypad serves only for entering numerical values. The ENOTEC user interface is designed for intuitive usage of the electronic unit. This means that as a rule there is no need to study the instruction manual during operation. Figure 16 Front panel of the COMTEC® 6000 electronic unit after the COe sensor is enabled By pressing the soft keys [menu/cal.], [values] or [parameter] the respective menus can be obtained. In each of these menus various options can be selected from a list using the soft keys [] and []. If there are more than 4 options, this is indicated by an arrow on the right hand side of the menu list. This arrow indicates that there are more options to follow. The option which can currently be selected has a black background and light letters and one can get access with the soft key [enter]. The main display provides the information about the actual O2 value in (Vol.) % and the COe (CO and other combustible gases) value in ppm. You will also get the information about the adjusted measuring range (on top of the bar graph: left number: minimum level of the adjusted measuring range; right number: maximum level of the adjusted measuring range. If the COe value is out of range, this status will be indicated by an arrow (see Figure. Figure 17 COe value out of range O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 28 of 80 3.4 Start-up of the COMTEC® 6000 InSitu Analyser System Important Before the COMTEC® 6000 InSitu analyser system is powered up make sure that the conditions comply with the following points: • Does the line voltage correspond with the voltage shown on the type label of your COMTEC® 6000? • Are all electrical connections made in accordance with the instructions in this manual? • Are all pneumatic connections made correctly and gastight to prevent the probe from ingress of ambient air? • Is the COMTEC® 6000 probe installed in a flue gas that corresponds with the probe specification? • Do the ambient conditions for the electronic correspond with the specifications for the electronic unit? 3.5 COMTEC® 6000 Probe heating phase After switching on the COMTEC® 6000 analyser system by fitting in the fuse F1 for the power supply, the COMTEC® logo appears on the display for a short time. During this time, all parameters relevant for a fault-free functioning and start-up are checked automatically. If during this check any system errors are found, the electronic unit will show them in clear text (press then the soft key [status]). You will find a detailed error and warning description in chapter 4.2 on page 57 and the following. When the O2 sensor temperature is stable within ± 1.0 °C/0.18 °F (this should be the case after approx. 20 to 60 minutes), O2 and COe measurement is released and the main window appears on the display. If the maximum heating-up time (default setting: 60 minutes) is exceeded or if such an excess is predictable due to the heat-up speed, then the heating is turned off and the error message "heating system don’t work" appears. During the O2 sensor heating phase, all actual values can be called up in the corresponding actual value menu window with the soft key [values]. You can also enter the menu/cal. and the parameter menu by pressing the corresponding soft keys. Please note that some functions will not be available during the heating phase (e.g. calibrations). If you try to start menu items like a calibration, you will get following information: “Function is being delayed until probe is heating up”. Note After switching on the COMTEC® 6000 InSitu analyser system, you have to wait 2 hours before any other activities are possible. After completion of the heating phase, the main window is shown in the display (see Figure 18). O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 29 of 80 Figure 18 Display after heating up (main window) Note Before you can trust the values, calibration is required. 3.6 Amounts and Adjusting of Test gas and Reference air 3.6.1 Reference air It is possible to adjust the reference air flow rate with the help of a screwdriver. (see Figure 19 or Figure 20) The flow rate of reference air can be read of in the values menu. Starting from the main window: [Values] > “O2 … actual values” > [Enter] > “O2 ref.-air flow rate” Flow rate: 30 l/h - 40 l/h + Figure 19 Adjusting ref. air flow rate at field housing + - Figure 20 Adjusting ref. air flow rate at 19”rack O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 30 of 80 3.6.2 Test gas Version A and with Pump (Two Test gas inputs) The flow rate of the test gas will be shown on the display as in chapter 3.10.2 described. To adjust the flow rate you need a test gas bottle with pressure reducer and a needle valve. Flow rate: Input pressure: 150 l/h - 180 l/h max. 3 bar Version 1 (One Test gas input) It is possible to adjust the flow rate of test gas 1 with the help of a screwdriver. (see Figure 21 or Figure 22) To adjust the flow rate of test gas 2 you need a test gas bottle with pressure reducer and a needle valve. Flow rate: Input pressure: 150 l/h - 180 l/h max. 3 bar + - Figure 21 Adjusting test gas 1 flow rate at field housing + Figure 22 Adjusting test gas 1 flow rate at field housing O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 31 of 80 3.7 Main Window In the main window the currently measured oxygen value and COe value is displayed. A bar graph shows current value relating to the measuring range of the output signals. Figure 23 Display: main window (example) after calibration This main window branches into four menus: Main window Status menu/cal. values parameter Menu Description Status resp. If the Measuring Range Switching is set to “local” and there is MR1/2 no error or alarm, the measuring range can be selected with this key. In this case the soft key is marked with "MR1/2". In the case of an error or alarm this soft key is labelled with "status" and with this soft key the errors and/or alarms can be called up. Calls up the system menu, in which you have access to calibraMenu/Cal. tion functions, system settings, system tests etc. Values Displays all actual values of the system. Calls the parameter menu, in which several parameters are Parameter shown. These parameters can also be altered. Table 1 Branching of the main window O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 32 of 80 3.8 Values (Actual Value Menu) Figure 24 Display: values menu In the value menu the following current actual values of the electronic unit can be called up: Result of last system test Result of last O2 calibration Result of last COe calibration O2 … Actual values Actual Values • O2 measured wet value [%] • O2 calculated dry value [%] • O2 mA output value [mA] • O2 sensor raw value [mV] • O2 sensor temperature [°C/°F] • O2 heater power [%] • O2 ref.-air flow rate [l/h] COe … Actual values • COe measured wet value [ppm] • COe mA output value [mA] • COe sensor voltage [mV] • COe sensor temperature [°C/°F] • COe heater voltage [mV] • COe heater current [mA] • COe heater resistance [Ω] • COe heater power [mW] • Version MXP-Board Common … Actual values • Cold junction temperature [°C/°F] O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 33 of 80 Categories Result of last system test Result of last O2 calibration Result of last COe calibration O2 Actual value Unit Comment Shows the O2 and COe values determined by the last system test. There is also shown the time passed by since the last system test has been performed. Attention: A system reset deletes the indication of the time passed by. Shows the O2 value determined by the last O2 calibration. There is also shown the time passed by since the last O2 calibration has been performed. Attention: A system reset deletes the indication of the time passed by. Shows the COe value determined by the last COe calibration. There is also shown the time passed by since the last O2 calibration has been performed. Attention: A system reset deletes the indication of the time passed by. O2 measured wet vol % This is the measured (wet) O2 value based on the senvalue sor voltage in wet flue gas. O2 calculated dry vol % At flue gas moisture correction of > 0% this is the calvalue culated (dry) value. This value is also displayed in the main window and given out by the mA output. O2 mA output value mA The O2 value current output depends on the O2 range. The O2 range can be changed in the parameter menu O2 sensor raw value mV Measured sensor voltage of the O2 Zirconium oxide sensor O2 sensor tempera- °C/°F Measured sensor temperature of the O2 Zirconium ture oxide sensor (Temperature unit can be changed to °F, see chapter 3.10.5.1) % Heater power in % of the O2 sensor heater O2 heater power O2 ref.-air flow rate l/h COe Common COe meas. wet value COe mA output value ppm This value shows the measured flow rate of the reference gas (air: 20.95% O2) used for the Zirconium oxide sensor. Required value: 5 – 60 l/h (typical 40l/h). Indication of the measured COe value mA The COe value current output dependent on the COe range. The COe range can be changed in the parameter menu COe sensor voltage mV This is the measured value of the COe sensor in dependence to the combustibles COe sensor tem°C/°F Measured sensor temperature of the COe sensor perature (Temperature unit can be changed to °F, see chapter 3.10.5.1) COe heater voltage mV This is the heater voltage of the COe sensor COe heater current mA This is the heater current of the COe sensor COe resistance Ω This is the controlled resistance value of the COe heater. The COe sensor temperature depends on the COe heater resistance COe heater power mW This is the heater power of the COe sensor heater Version MXP-Board Shows the version of the MXP-Board Cold Junction Tem- °C/°F Cold junction temperature of the thermocouple element perature (Temperature unit can be changed to °F) Table 2 Values menu O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 34 of 80 If instead of a value only underscores are shown, this means that presently no valid value for this parameter is available. 3.9 Parameter Menu Figure 25 Display: parameter menu In the first parameter menu window you can select between four items as shown. After having selected between the four possible parameter items and after having selected a parameter for the first time with the soft key [enter], a window appears requesting the entry of a code. If the maintenance code was not yet changed after the installation, then one confirms the inquiry through [enter] without any input of numbers. To change the system code or to reset to the factory code “0000” see chapter 3.10.5.4 on page 50 (change and reset). After having entered the valid system code, there appears a window where the corresponding value can be altered. Note The system code is factory-set to 0000 O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 35 of 80 Following parameters can be altered in the parameter menu: Test gas parameters • O2 test gas 1 (bottle) [%] • O2 test gas 2 (bottle) [%] • CO test gas 2 (bottle) [ppm] O2 sensor parameters and measuring ranges Parameter • Sensor constant [mV] • Sensor slope [mV/dec] • Measuring range 1 from [% O2] • Measuring range 1 to [% O2] • Measuring range 2 from [% O2] • Measuring range 2 to [% O2] • Limit 1 alarm [O2 min] • Limit 2 alarm [O2 min] • Correction flue gas [vol% moisture] COe sensor parameters and measuring ranges • Sensor Offset [mV] • Sensor slope [mV/0,1%] • Measuring range end [ppm CO Global system parameters • Probe type [KES/KEX 6 0 0 X] • Probe cable length [m] O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 36 of 80 Category Test gas parameters Parameter O2 test gas 1 (bottle) O2 test gas 2 (bottle) CO test gas 2 (bottle) O2 sensor parameters and measuring ranges Sensor constant COe sensor parameters and measuring ranges Unit Values % 20.950 % Comment O2 concentration of the test gas bottle 1 Default value: 20.950 % % 2.1 % O2 concentration of the test gas bottle 2 Default value: 2.1 % ppm 1000 ppm CO concentration of the test gas bottle 2 Default value: 1000ppm mV -20mV to 10mV O2 sensor constant Note: a successful O2 calibration will overwrite this constant. Sensor slope mV +35mV to /dec +55mV Measuring range 1 from Measuring range 1 to Measuring range 2 from Measuring range 2 to Limit 1 alarm % 0 % - 21 % % 0 % - 25 % % 0 % - 10 % % 0 % - 25 % % % 0 % - 25 % min or max Limit 2 alarm % 0 % - 25 % min or max Corr. flue gas (H2O correction) % 0 % - 50 % Sensor Offset mV 0mV – 50mV Sensor Beta Sensor Gamma Measuring range end O2 sensor slope Note: a successful O2 calibration will overwrite this slope. Start value of the O2 measuring range 1 (see chapter 3.9.1 ) Default value: 0% End value of the O2 measuring range 1 Default value: 21 % Start value of the O2 measuring range 2 Default value: 0% End value of the O2 measuring range 2 Default value :10 % Limit value 1 for O2 min (alarm is set when the O2 concentration falls below the limit value) or max (alarm is set when the O2 concentration rises above the limit value) alarm. Limit value 2 for O2 min (alarm is set when the O2 concentration falls below the limit value) or max (alarm is set when the O2 concentration rises above the limit value) alarm Moisture content in the flue gas for the calculation of O2 value which would be measured in dried process gas. Entry will change shown value on the display and mA output to a dry value. Default setting: 00.0% (no calculation) (see chapter 0) COe Sensor offset. Note: a successful COe calibration will overwrite this offset. COe Sensor Beta Note: a successful COe calibration will overwrite this point. COe Sensor Gamma ppm 100ppm 2000ppm Measuring range of COe Default value: 1000 ppm Table 3 Parameter menu O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 37 of 80 3.9.1 Altering a Parameter by the Example of the O2 Measuring Ranges The electronic unit possess two freely adjustable O2 measuring ranges. The measuring ranges of electronic unit can be determined freely. For example one changes the “O2 Measuring Range 1” as follows: To reach the menu option "O2 Measuring Range 1" please enter the parameter menu with [parameter] and select here the item “O2 sensor params and meas.ranges”. Please press now the downward arrow until the point "Meas.range 1 from" is reached. Then the point is to be accessed with [enter], and the system code has to be inputted and confirmed. In the menu option "Meas.range 1 from" the initial value of the measuring range can be indicated now. Note It should be noted that the initial value of the measuring range cannot be larger than the final value. Likewise the final value cannot be selected smaller than the initial value. Otherwise the electronic unit does not permit the entered values. After input of the initial value this value will be confirmed with [enter] and the final value of the measuring range can be keyed in the menu option "O2 meas. range 1 to". As soon as this value is also confirmed through [enter], the electronic unit updates with the new measuring range. Note If you try to enter a value outside the permitted limits, the corresponding limit value is selected. 3.9.2 Altering a Parameter by the Example of a Limit Alarm Value In this chapter the altering of a parameter will be explained using the example of value “limit 1 alarm”. For this purpose enter the parameter menu with [parameter], select here the item “O2 sensor params and meas.ranges” and select then with the downward arrow the item "Limit 1 alarm”. Then the point can be called up with [enter], and the system code has to be inputted and confirmed. Figure 26 Display: parameter input (example) O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 38 of 80 In the window “Parameter Input – O2 System Params”, the parameter to be altered is displayed in clear text with the current value. If special functions are assigned to this parameter (as like “min/max” as in this example), these are displayed, too. The numeric value can be altered using the numeric keypad. To correct, the cursor can be moved back with the [←] key. The sign can be selected independently of the cursor position with the [±] key. In this example, the secondary parameter “min/max” can be changed by the corresponding soft keys. Note If you try to enter a value outside the permitted limits, the corresponding limit value is selected. The altered value has to be confirmed with the soft key [enter]. Note When pressing the soft key [cancel], the altered value is cancelled and the old value maintained. O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 39 of 80 3.9.3 O2 Correction ‘wet’ or ‘dry’ value By design principle the COMTEC® 6000 measures the wet values. To calculate and show the values as dry values in the display and also on the mA-output, you have to enter the amount of moisture in the flue gas. For this enter the parameter menu with pressing the soft key [parameter]. Select the item “O2 sensor params and meas.ranges” with [enter] and then downwards to the item “Corr. flue gas” with [enter]. Now an information text will appear: “Important information: Moisture correction flue gas When a fixed value is entered (average vol.% water vapour content of the flue gas) the InSitu measured ‘wet’ value (real value) will be converted into a ‘dry’ value. The ‘dry’ value is always higher than the ‘wet’ value! A ‘dry’ value is designated by the ‘dry’ label at the top of the bar graph of the measured value in the main measurement display.” Accept this information with [continue]. Enter now the amount of moisture in the flue gas and accept the entry with [enter]. You will now see the measured O2 value in the main window with the remark ‘dry’. Figure 27 Display: O2 value is shown as a dry value O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 40 of 80 3.10 Menu / Cal. When selecting the menu with the corresponding soft key [menu/cal.], first a code enquiry appears, where the system code (factory-set to 0000) must be entered and confirmed with [enter]. Note The system code is factory-set to 0000. After entering the system code, the menu appears. Figure 28 Display: menu/cal. In this menu, the following functions can be selected: O2/CO System test/calibration O2 Output settings menu/cal CODE • Freezing of measured O2 value • O2 measuring range switching • O2 mA-output damping COe Output settings • Freezing of measured CO value • COe measured value damping Common Settings •Change temperature unit °C/°F • Automatic calibration • Relay output assignments • Change system code • Service • Software version COe Measurement OFF or ON O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 41 of 80 Category Menu Point Description / Remarks O2/COe ... System test / calibration System test /cal. with test air /gas O2/ Output settings Freezing of measured O2 value O2 measuring range switching O2 mA-output damping COe… Output settings Freezing of measured COe value COe measured value damping Common Settings Change temperature unit °C/°F Automatic calibration Relay output assignments Change system code Service Performs a system test with test air and test gas (two-point-calibration). After the successful system test the new calibrated values can be taken over as calibration values. "Freezes" the last measured value for O2 while calibration See chapter 3.10.3.1 on page 47 Sets the operation mode to either "local" or "remote" Allows to alteration (change) to the damping time of the mA output for O2 Maximum value: 55 sec "Freezes" the last measured value for COe while calibration See chapter 3.10.4.1 on page 48 Allows to alteration (change) to the damping time of the mA output for COe Maximum value 30 sec Select unit temperature: °C or °F See chapter 3.10.5.1 COe … Measurement OFF (or ON) Software version Disable COe measurement Performs an automatic calibration Possible assignments for Output A: COe maintenance / O2 measuring range Changes the code for the menu and the parameter menu Calls up the service menu (service code required) Shows the software version of the ® COMTEC 6000 firmware In this menu item the COe sensor can be disabled (if enabled before) or the COe sensor can be enabled (if disabled before). See chapter 3.10.6 on page 50 Table 4 Menu / Calibration O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 42 of 80 3.10.1 First Steps for Calibration Important Before you begin with the calibration make sure that the conditions comply with the following points: • You will need two test gas bottles for the system test and calibration: • Test gas 1 must contain 21% O2 in N2 and no combustibles like CO. Quality like synthetic air or instrument air • Test gas 2 should contain 500 to 1000ppm CO and 2.1% O2 in N2. Attention Both test gases may require SO2 in ppm. Please contact ENOTEC. Are all pneumatic connections made correctly and gastight to prevent the probe from ingress of ambient air? Please make sure, that the tubing you use to connect the test gas bottles to the electronic unit are adapted for this use (temperature-resistant, clean, undamaged). Both test gas bottles have to be connected: Connect the test gas 1 to test gas 1 connection and test gas 2 to test gas 2 connection. ( see chapter 2.6.2 ) The calibration starts from the main window. Note If the COMTEC® 6000 probe has only just heated up, please wait at least 2 hours before you calibrate the O2 sensor and before commissioning the COe sensor. Please wait at least 24 hours before you make the final system test calibration. Press the soft key [menu/cal.]. Before you enter this menu, you are asked to put in the system code first. Figure 29 Display: code input Normally you have only to confirm the factory default code by pressing the soft key [enter]. This does only work, if the system code has not been changed. Otherwise put in the 4-digit system code using the keypad on the right side of the display panel, and then press the soft key [enter]. O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 43 of 80 3.10.2 Two point System test + Calibration for O2 and COe This menu item starts with a system test and after this system test you may decide if you want to take the results to calibrate the system. Note At any time you can cancel the procedure with the button [cancel]. Enter the menu by pressing the soft key [menu/cal.] and select the menu item “O2/COe system test/calibration” by pressing [enter]. The following display indicates that test gas 2 is being supplied to the probe. Press [continue].to reach the next level, or wait for a few seconds. The flow rate must be between |>…<|(150l/h – 180l/h.) To adjust the flow rate see chapter 3.6) Press [continue] to reach the next level, or wait for a few seconds. System test with test gas 2 starts automatically and you can see all relevant values on the display. After the test with test gas 2 has finished, the following display indicates that test gas 1 is being supplied to the probe. Press [continue] to reach the next level, or wait for a few seconds. Now you have to adjust the test gas flow rate. The flow rate must be between |>…….<| (150l/h – 180l/h.) Press [continue] to reach the next level, or wait for a few seconds. O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 44 of 80 Also the system test with test gas 1 starts automatically and you can see all relevant values on the display. After the system test has finished, you will get the results of this system test. You can also see all presettings which were relevant for this system test. By using [] you can see all information. Now you can decide if you want to take the values for a calibration. The window with the results of the last system test will disappear after 60 seconds. Now the results will be safe for 2 hours. During this time you can get the results back (starting from the main window): [values] > Results of last system test > [Enter]. Decide: Press [no calibr.] to cancel this procedure Press [calibr.] to perform a calibration Here you have to enter the test gas bottle value of test gas 1 for O2 (Take the values from the test certificate of the bottle!) Press [enter].to reach the next level. Enter the test gas bottle value of test gas 2 for O2 Press [enter].to reach the next level. O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 45 of 80 Enter the test gas bottle value of test gas 2 for COe Press [enter].to reach the next level. After entering the values you will see, how the measured values of O2 will be calibrated. Press [calibr.] to calibrate the O2 sensor or [no calibr.] to cancel the procedure. Now you see the calibration values of the COe sensor. Press [calibr.] to calibrate the COe sensor or [no calibr.] to cancel the procedure. After the calibration you get the results of the last calibration of O2. Press [continue] to get the results of the COe sensor or [return] to close the procedure. Here you see the results of the last calibration of the COe sensor. Press [return] to close the procedure. Note You will find the results of the last calibrations in the menu item [values]. Before you perform a second system test (as a verification of the calibration) you have to wait at least 1.5 hours. This time is necessary to achieve reproducible results with each system test. O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 46 of 80 3.10.3 O2 Output Settings 3.10.3.1 Freezing of Measured O2 Value Start with the main window: [menu/cal.] “O2 … output settings” with [enter] “Freezing of measured O2 value” with [enter] “Freezing of meas. O2 value … OFF” with [enter] and select the soft key [ON]. Under this menu item freezing of measuring O2 value memory can be switched ON during calibration. With the freezing of measured O2 value on, the last measured value before calibration is saved so that at the current output the measuring value, which changes because of the calibration, has no effect. The currently measured value is released again after an adjustable delay, when the calibration is completed. The default delay time is 3 minutes and can also be changed under this menu item (“Return to flue gas in”) within the limits of 1 to 10 minutes. 3.10.3.2 O2 Measuring Range Switching Start with the main window: [menu/cal.] “O2 … Output settings” with [enter] “O2 measuring range switching”. Preloaded adjustment is “remote”. You can change the adjustment to “local” by pressing []. Accept the change with [enter]. Return to the main window with [cancel]. The electronic unit has two measuring ranges. The switching mode of the ranges can be made manually from the instrument keypad, or by an external remote 12-24 voltage input signal. This microprocessor parameter location is used to determine which mode of range switching is required - local or remote. The factory preset default in the electronic unit is "remote" range switching. This means that in the case of an open digital input, the measuring range 1 is active. At the modus "local“, the measuring range can be changed in the main menu with the soft key MR1/2 by hand. Note In case of errors and alarms, the soft key MR1/2 in the main menu is occupied by status information. The status function has the highest priority, therefore this means in case of errors the measuring range cannot be changed manually (by hand). 3.10.3.3 Damping of O2 mA Output Start with the main window: [menu/cal.] “O2 … output settings” with [enter] “O2 mA-output damping” with [enter]. Preloaded adjustment is “00 sec”. Please enter the time in seconds by using the numeric keypad and accept the entry with [enter]. By pressing [cancel] you will come back to the main window. O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 47 of 80 The mA-output can be damped if required. There are optional settings from 0 sec. (without damping) to a maximum of 55 sec. are available. Damping is useful if the oxygen output signal of the electronic unit is spiky or rough due to sudden process condition changes. A smooth or damped output can be obtained with the attenuation setting feature. 3.10.4 COe Output Settings 3.10.4.1 Freezing of measured COe Value Start with the main window: [menu/cal.] “COe … output settings” with [enter] “Freezing of measured COe value” with [enter] “Freezing of meas.COe value … OFF” with [enter] and select the soft key [ON]. Under this menu item a freezing of the measured COe value can be switched ON during calibration. With the freezing of measuring COe value on, the last measured value before calibration is saved so that at the current output the measuring value, which changes because of the calibration, has no effect. The currently measured value is released again after an adjustable delay, when the calibration is completed. The default delay time is 20 minutes and can also be changed under this menu item (“Memory hold time”) within the limits of 1 to 180 minutes. 3.10.4.2 Damping of COe Measured Value Start with the main window: [menu/cal.] “COe … output settings” with [enter] “COe measured value damping” with [enter]. Preloaded adjustment is “1 sec”. Please enter the time in seconds by using the numeric keypad and accept the entry with [enter]. By pressing [return] you will come back to the main window. The measured value for COe can be damped if required. There are optional settings from 1 sec. (without damping) to a maximum of 30 sec. are available. Damping is useful if the measured value for COe is spiky or rough due to sudden process condition changes. A smooth or damped value can be obtained with the attenuation setting feature. 3.10.5 Common … Settings 3.10.5.1 Change temperature unit °C/°F Start with the main window: [menu/cal.] “Common … Settings” with [enter] “Change temperature unit °C/°F” with [enter]. Select the unit by pressing []. By pressing [cancel] you will come to the main window without any changing. O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 48 of 80 3.10.5.2 Automatic calibration Start with the main window: [menu/cal.] “Common … Settings” with [enter] “Automatic calibration” [enter]. COMTEC® 6000 offers the opportunity of automatically performing a calibration procedure at regular intervals. This procedure however requires the version with a fully automatic pneumatic unit. All settings required for an automatic calibration can be made in this menu. These are: Automatic Calibration ON/OFF As a standard, ACAL is off. In this item, ACAL can be activated. Release mode 1. Time+External release 2. External release 3. Time only Interval time (e.g. 90 days) Indication of the calibration cycle time in days. At a value of 0 days the calibration starts immediately upon release, this is important for a manual remote calibration. Remaining time xx days and xx hours The remaining time until the next calibration is indicated under this item. Note For automatic calibration it is essential to connect a probe with solenoid valve and to ensure that the test gas “air” is always available and under pressure (instrument air version) or a pneumatic unit with pumps must be installed. Important If the calibration time interval in the parameter menu is set to zero seconds for example - to make a remote calibration - it is very important that the release signal has a maximum time of 60 seconds. A release signal of more then 60 seconds could restart the calibration a second time. Please note that there is no "real time" clock in the electronic unit. It does not know time of day, month or year. Only a clock-pulse generator is used for automatic calibration purposes. 3.10.5.3 Relay output assignments Start with the main window: [menu/cal.] “Common … Settings” with [enter] “Relay output assignments” with [enter] “Output A assignment”. By pressing [] you can change the relay assignment from “COe maintenance” to “O2 meas. range”. Accept the change with [enter]. By pressing [cancel] you will come back to the main window. O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 49 of 80 3.10.5.4 Change System Code Start with the main window: [menu/cal.] “Common … Settings” with [enter] “Change system code” with [enter]. In this menu item, the system code can be changed. Please enter now the old code with the numeric keypad. Accept your entry with [enter]. Enter now the new code with the numeric keypad. Accept your entry with [enter]. Repeat the new code and accept with [enter]. Now you get the information, that the new code is accepted and this information has to be confirmed with [ok]. Note If the changed system code is lost, a reset of the whole system is needed. Please contact ENOTEC. 3.10.5.5 Service Start with the main window: [menu/cal.] “Common … Settings” with [enter] “Service” with [enter]. This menu item is reserved for ENOTEC service personnel only. It is factorycoded. 3.10.5.6 Software Version Start with the main window: [menu/cal.] “Common … Settings” with [enter] “Software version” with [enter]. You will get the information about the software version. By pressing [return] you will come back to the main window. This menu item provides information about the software status and the level. 3.10.6 COe … Measurement OFF Start with the main window: [menu/cal.] “COe … Measurement OFF” with [enter]. In this menu item the COe measurement can be disabled. The menu item “COe … Measurement OFF” appears only if the COe measurement is enabled. Otherwise the menu item “COe … Measurement ON” is shown instead. O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 50 of 80 4 Service and Maintenance 4.1 Service and maintenance of the COMTEC® probes 4.1.1 Replacing filter element Warning – Hot Surface The probe may only be removed with heat-insulated gloves. Before removing the probe, always switch off the supply voltage of the electronic system. After removal, store the probe in a safe, protected place and wait until it has cooled down below 35 °C. Procedure: with a hook wrench and a) Loosen the retaining ring at the filter head screw off the filter head from the probe with a pin wrench. 2 1 Figure 30 Removing of the filter head If needed, a set of spanners for loosening the filter head can be ordered at ENOTEC. Part-No.: PST-0002 (for filter heads with retaining ring) Both sets of spanners contain additionally an Allen key for the loosening of the O2 sensor screws. Warning – Hot Surface Probe may be hot! O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 51 of 80 b) Clamp the filter head into a vice. c) Remove the old filter completely. Also, clean the grooves in the metal fixing. Figure 31 Dismantling of filter 2 3 1 + H2O 1a d) Insert the new filter with cement as follows: Mix cement thoroughly and coat both the grooves in the seat and the filter around the seat at the outside. Press the filter into the seat by turning it. Wipe the cement between filter and seat and remove excess material inside as well. Figure 32 Insert the new filteri Note The cement dries at room temperature within 24 hours. Using the cement supplied by ENOTEC, all types of ceramic filters of the ENOTEC product range can be inserted and fixed. 4.1.2 Replacing filter head Warning – Hot Surface The probe may only be removed with heat-insulated gloves. Before removing the probe, always switch off the supply voltage of the electronic system. After removal, store the probe in a safe, protected place and wait until it has cooled down below 35 °C. For the change of the filter head the retainer ring at the filter head is to be loosened (have a look at Figure 30 on page 51). The filter head can be unscrewed and taken out now. The new filter head is now screwed on the probe tube. Before the retainer ring is tightened again, the V-shield must be aligned to the flue gas flow. If needed, a set of spanners for loosening the filter head can be ordered at ENOTEC. Part-No.: PST-0002 The set contains additionally an allan key for the loosening of the O2 sensor screws. O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 52 of 80 4.1.3 Exchange of probe inner part Take the probe out of the protection tube and wait until it has cooled down. Warning – Hot Surface The probe may only be removed with heat-insulated gloves. Before removing the probe, always switch off the supply voltage of the electronic system. After removal, store the probe in a safe, protected place and wait until it has cooled down below 35 °C. If necessary, clean the probe from dirt and dust etc., after it is cooled down. 4 2 1 3 6 5 Figure 33 Exchange of probe inner part Disconnect all wires of the probe in the connection box , loosen the tubes and , and the two screws. Pull off the thin transparent reference air pipe from the screwed entry connection in the housing wall. Carefully pull out the probe inner part. (4 hole ceramic rod with signal measuring wire, thermocouple element and heater). Push in carefully the new inner part into the probe, (The inner part is pressed by the holding plate with spring pressure.) and connect all wires and pneumatic tubes. Connect the wires as follows: O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 53 of 80 Terminal 1 2 3 4 6 7 8 9 10 11 12 13 14 Colour white/brown orange green white black blue green/yellow grey grey white (no.1) white (no.2) red (no.3) red (no.4) Description Signal wire, O2 sensor signal wire, O2 sensor thermocouple element 1 thermocouple element 1 heating element O2 heating element O2 ground/earth solenoid valve solenoid valve COe-sensor measuring value COe-sensor measuring value COe-sensor heating element COe-sensor heating element Polarity + + - Unit mV mV mV mV Table 5 Connection of the probe inner part Install the probe and carry out an O2 calibration. 4.1.4 Exchange of ZrO2 sensor Take the probe out of the protection tube and wait until it has cooled down. Dismantle the probe inner part as in chapter 4.1.3 described. Then unscrew the filter head and dismantle the test gas distributor with guide tube , by loosening the two Allen® screws. Now remove the 4 Allen® screws at the Measuring cell flange and remove the measuring cell of the probe tube. Remove also carefully the old Measuring flange gasket 6 7 1 2 3 4 5 Figure 34 Mounting O2 sensor holder tube (for KES600x) O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 54 of 80 No. Description Probe tube with flange Measuring flange gasket Measuring cell holder with flange 4 Allen® screws (M5x12) Protection cap 2 Allen® screws (M5x12) Test gas distributor with guide tube ENOTEC – Part-No.: Z02-6001 Z02-6011 (MLT) 0-R-002100 Clean the flange at the probe tube with fine sandpaper. Tighten the new O2 sensor with a new sealing and four new screws at the O2 sensor flange of the probe tube. Insert the probe inner part and ensure, that the inner parts do not clamp in the probe tube. Press the holding plate against the spring, so that the inner parts are pressed against the O2 sensor with sufficient spring loading. Install the probe (see chapter 2.7) and carry out an O2 calibration (see chapter 3.10.1). 4.1.5 Exchange of the COe sensor Warning – Hot Surface In addition, the outside of the probe is hot (300 °C). Warning Before changing the COe-sensor please switch off the power supply by removing the external power supply fuse or by removing the fuse F1 at the electronic unit! 1. Disable the COe-Sensor via the software: [menu/cal.] (enter system code) “COe ... Measurement OFF” <yes>. Switch off the power supply 3. Disconnect the COe sensor wires at the terminal block no. 11-14. (Instruction for the function of the terminals see chapter 2.5.1) Figure 35 Connection of the COe sensor O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 55 of 80 4. Unscrew and remove the cap nut. 5. Unfix the clamping ring , the O-ring and the retainer ring . 4 2 3 6. Pull the COe-sensor out of the probe. Attention: Maybe hot 1 Figure 36 Pull out the COe sensor 7. Prepare the new COe sensor as follow: Take the clamping ring, the O-ring, retainer ring and the cap nut and cover them over the COe sensor. 2 1 Note: Mind the position of the bevel. Bevel must face O-ring! Figure 37 Prepare the new COe sensor 4. Insert the new COe-sensor into the probe. 5. Adjust the excess length of the COe-sensor. ca.1cm Figure 38 Insert the new COe sensor 6. Tighten the cap nut. Please tighten the cap nut once more after the system and the plant are in normal operation for two hours. Note Ensure a gas-tight connection using new sealing kit. 7. Connect the COe sensor wires at the terminal block no. 11-14. 8. Switch on the power supply. 9. Wait until the system is heated up to nominal temperature. The system is to be enabled now, please follow the instructions in Chapter 3.10.6 COMTEC® 6000 Electronic Unit. Note After the exchange of the COe sensor the values COe Offset etc. have to be entered into the parameter menu. You will find these values on the test protocol of the sensor. O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 56 of 80 4.2 Status messages/Error messages Status Messages / Error Messages / Troubleshooting Figure 39 Display: error messages If errors or alarms occur during operation, these are displayed as clear text in the status menu. All errors and alarms must be acknowledged and/or cleared with the soft key [enter] in this menu display. A help function for the status messages is available in this menu. Note If the electronic unit is put into operation without a probe connected, some system errors will occur. E.g. heating system does not work, error sensor signal out of range, error wire breakage thermo element. When the electronic unit is then connected to a probe, these errors will be shown again, because the microprocessor stores the errors as they occur in a permanent memory (EEPROM). After acknowledgement of each of these errors, the system operates normally. The following status messages are possible: O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 57 of 80 Message Possible reasons Heating system does not work The probe could not heat to the nominal tempera- During start up ture Possible reasons: Reference air flow rate is too high, blown fuses, insufficient power supply voltage, broken probe cable, broken heater wires, heater resistance failure of the probe heater (must be between 37.5 and 47.5 Ohms). Warning Make sure that the power is switched off when doing this test! As the result of a calibration check, the calculated During calibracell constant is outside the tolerance range pation rameters of the microprocessor settings. Therefore the electronic unit continues with the previous/former cell constant value. The microprocessor tolerance range is factory set to: -50mV to +10mV. O2 sensor constant out of tolerance Occurrence LED/Relay contact LED “Error” Relay”System error” contact open LED”Error” Relay”System error” contact open O2 sensor slope As the result of a calibration check, the calculated out of tolerance mV/Decade slope is outside the tolerance range. The electronic unit therefore continues with the previous/former slope value. Tolerance: 35mV to 55mV per decade Possible reasons: Test gas flow to low (⇒ Check the test gas tubes, if needed exchange of the test gas and reference gas tubes), solenoid valve not open, incorrect test gas concentration. During calibra- LED”Error” tion Relay”System error” contact open COe Beta-Factor Wrong Testgas, or COe sensor error out of range Check the Testgas, repeat the calibration, and if necessary change the COe sensor.(Contact ENOTEC for help ) During calibra- LED”Error” tion Relay”System error” contact open O2 sensor signal Test gas flow too high, Unstable test gas concen- During system LED”Error” unstable tration, unstable test gas pressure, wrong V-shield test Relay”System position, filter is broken or filter head is missing error” contact open COe sensor signal unstable Test gas flow too high, Unstable test gas concen- During system LED”Error” tration, unstable test gas pressure, wrong V-shield test Relay”System position, filter is broken or filter head is missing error” contact open Test gas flow too Insufficient instrument air supply, blown fuses, During calibra- LED”Error” high/low insufficient test gas supply, test gas tube blocked, tion and “Maint.” solenoid valve is not open or test gas bottle is not open/empty Timeout while test gas supply Unstable test gas concentration, unstable test gas During calibra- LED”ERROR” pressure, wrong V-shield position, filter is broken tion Relay”System or filter head is missing error” contact open Autom. calibration cancelled mV output value of the probe is unstable, cell con- During autostant or mV/Dec. slope outside of microprocessor matic calibratolerance/range (Note: the corresponding error is tion shown on the electronic unit display) At any time Reference air Insufficient instrument air supply, Reference air flow too high/low tube blocked, Dirt in the tubing and by this a possible damage of the needle valve Tolerance: min 5l/h, max 60l/h, min. 1bar/14.5psi O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 LED”Error” Relay”System error” contact open LED“Error” Page 58 of 80 Message Possible reasons Occurrence LED/Relay contact Thermocouple wire broken Connection failure or broken probe cable At any time LED”Error” Relay”System error” contact open O2 sensor signal O2 cell signal wire not connected, bad connection, At any time out of range push the probe inner part assembly, broken probe cable, faulty thermocouple, large amount of combustibles in the flue gas. Tolerance: 45mV to +265mV LED”Error” Relay”System error” contact open Temp. of electronic out of spec. The temperature of the electronic unit is outside At any time the allowed operating limits Possible reasons: Ambient air temperature is too high. The temperature of the electronic unit is outside the allowed operating limits Tolerance: -20 °C (-4 °F) to +70 °C (158 °F) within its housing LED”Error” Relay”System error” contact open Probe tempera- Flue gas temperature too high (see chapter 5.2), At any time ture too high failure thermocouple, failure heater, wrong connec(O2 sensor only) tion at terminal box. Tolerance: +20 °C / 68 °F of the preset probe temperature max. 890 °C LED”Error” Relay”System error” contact open Probe tempera- Reference air flow too high, blown fuses, heater At any time ture too low failure, broken probe cable, actual power supply (O2 sensor only) voltage to the electronic unit (230V/115V ±10%). Limit:-20 °C/68 °F of the preset probe temperature LED”Error” Relay”System error” contact open Alarm limit 1 Oxygen limit 1 out of range Alarm limit 2 Note: Not active, when measuring value memory is active Oxygen limit 2 out of range At any time LED”Alarm” Relay”O2 limit alarm 1” contact open At any time Note: Not active, when measuring value memory is active O2 value freezing The measuring value memory (freezing) is still At any time active active LED”Alarm” Relay”O2 limit alarm 2” contact open LED”Maint.” COe value freez- The measuring value memory (freezing) is still ing active active At any time LED”Maint.” COe sensor Blown fuse on the COe sensor board, unplugged board communi- connection cable between display board and COe cation error sensor board, electronic failure of the COe sensor board At any time if COe measurement is enabled LED”Error” Relay”System error” contact open Short circuit COe Resistance of the COe sensor heater is out of tolsensor heater erance. Please measure the insulation resistance. (see wiring chapter 2.5.4) At any time if COe measurement is enabled LED”Error” Relay”System error” contact open Open circuit COe Resistance of the COe sensor heater is out of tolsensor heater erance or wire breakage Please measure the insulation resistance. (see wiring chapter 2.5.4), At any time if COe measurement is enabled LED”Error” Relay”System error” contact open O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 59 of 80 Message Possible reasons Occurrence LED/Relay contact Open circuit COe Connection failure or wire breakage sensor At any time if COe measurement is enabled LED”Error” Relay”System error” contact open Data memory error COe sensor electronic Electronic failure of the COe sensor board At any time if COe measurement is enabled LED”Error” Relay”System error” contact open ADC error COe sensor heater Electronic failure of the COe sensor board At any time if COe measurement is enabled LED”Error” Relay”System error” contact open ADC error COe sensor Electronic failure of the COe sensor board At any time if COe measurement is enabled LED”Error” Relay”System error” contact open Data fault EEprom A data error has occurred in the microprocessor and the electronic unit continues with factory default values. Please contact ENOTEC. During commissioning LED”Error” Relay”System error” contact open O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 60 of 80 4.3 Troubleshooting 4.3.1 Unsteady, widely varying Measuring Value (O2) Occurrence: At any time Possible reasons Intermittent contact caused by wire breakage Procedure Check the O2 sensor temperature (set value 840 °C/1544 °F or 800 °C/1472 °F for Ex systems) Intermittent contact inside the Measure the mV value on the terminals of probe - internal mV connection the power supply board Broken filter element Visual inspection by dismounting the probe Wrong installed V-shild Visual inspection by dismounting the probe Probe has been installed with- Visual inspection by dismounting the probe out filter head Intermittent contact inside the Check the spring tension probe – low spring tension for the O2 signal contact wire internally 4.3.2 No COe-Measuring Value; Arrow instead of a value Occurrence: At any time Possible reasons Procedure The physical measuring range Perform a O2/COe system test is exceeded An error of the COe sensor Check all electrical connections as well. exists 4.3.3 No Measuring Value for O2; empty Bar Graph Occurrence: At any time Possible reasons Procedure O2 value out of the coverage of Perform a O2/COe system test the electronic unit, for example caused by a low O2 concentration in connection with a high COe concentration O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 61 of 80 4.3.4 O2 reads higher than expected, and COe reads lower than expected Occurrence: At any time Possible reasons Procedure This may be due to a poor seal Tighten or replace the COe sensor coupling of the COe sensor coupling assembly. located in the terminal box housing. If the stainless steel nut is not tight enough the Oring seal allows ambient air to enter into the COe senor mounting tube and that of course influence the sensors readings. 4.3.5 O2 Display remains at the End of the Measuring Range or is higher than expected Occurrence: At any time Possible reasons Leakages at the measuring probe or at the O2 sensor flange seal. Solenoid valve does not close because solid particles (metal swarf or any other dust particles) are inside the solenoid valve O2/COe COMTEC 6000 InSitu Analyser System Procedure Check all flanges and screw connections for tightness. Exchange O2 sensor or replace O2 sensor flange seal. In case of a leakage in the area of the zirconium oxide O2 sensor, the O2 sensor must be exchanged. Check the test gas tubing inside the probe terminal box. Is there any dust visible in the opaque (white) test gas tube inside the probe terminal box? It is possible, that the instrument air used as test air is contaminated by dust or condensed solids out of the flue gas have settled there. It is also possible, that metal swarf (test gas tubing made out of copper or stainless steel) settles inside the solenoid valve during system test / calibration. Version 05.300.15 Page 62 of 80 4.4 Exchange Fuses and change of Voltage The electronic unit has five accessible fuses (see Figure 40): Figure 40 Position of the fuses and the switcher between 230 V and 115 V operation (SW1) Part Current Kind of Fuse Task F3 1A F4 1A F5 1A Protection of the electronic unit Protection of the electronic unit Protection of the solenoid valve SW1 switch F1 6.3 A F2 4A fast-acting 5x20 mm glass tube fuse fast-acting 5x20 mm glass tube fuse semi time-lag 5x20 mm glass tube fuse 115 V AC to 230 V AC semi time-lag 5x20 mm glass tube Protection of the entire sysfuse tem semi time-lag 5x20 mm glass tube Protection of the probe fuse heater Table 6 Fuses Important The fuses on the circuit board below the cover protect the electronic unit and should only be replaced by service personnel, because otherwise damage to the electronic unit cannot be excluded. O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 63 of 80 5 Technical Datas and Drawings 5.1 Requirements of the Gas Supply Instrument air for reference air supply Specification: According to ISO 8573-1 class 2 (Particle size max. 1µm, Particle density max. 1mg/m³, Oil content max. 0,1mg/m³, Pressure dew point max. -20 °C) Input pressure: 2-10 bar Input flow rate continuously maximum 40 l/h (for reference air supply), Test gas for calibration / system test Input pressure: max. 3 bar Specification test gas 1: 21% O2 in N2 (synthetic air) Specification test gas 2: 2.1 Vol.-% O2 and x ppm CO in N2 where 'x' must correspond to the selected maximum value of the COe measuring range (accuracy +/- 2%). That is: For a measuring range of 0 to 1000ppm please take test gas with about 800ppm CO (± 50ppm) in 2.1 Vol.% O2 (± 0,1Vol.% O2) and N2. For a measuring range of 0 to 500ppm please take test gas with 400ppm CO (± 50ppm) in 2.1 Vol.% O2 (± 0,1Vol.% O2) and N2 Input flow rate 1,1 +/- 0,1 bar max. 180 l/h in the 2. step of calibration and during the system test with test gas 2. Note The flow rate of the test gas bottle is set via the bottle pressure. O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 64 of 80 5.2 Probe Flue gas temperature: KES600x: up to 500 °C (932 °F) up to 1400 °C (2552 °F) with cooling protection tube Insertion length: KES-6001: KES-6002: KES-6003: KES-6004: KES-6005: Insertion length with cooling protection tube: 500/1000 mm (Other length contact ENOTEC) Measuring principle: Zirconium oxide for O2 MXP for COe Flue gas pressure: -50 to +50 mbar (-0.725 to +0.725 PSIG) Flow velocity: 0 to 50 m/s Ambient temperature: -40 °C to +80 °C (-40 °F to +176 °F) Response time (O2): 0,5 s (flue gas flowing at > 10m/second) T90 time (O2): 5 s (flue gas flowing at > 10m/second) Probe material: V4A (1.4571/316SS) 316L Stainless Steel Type of protection: IP65 Voltage supply: via electronic unit Dimension: see dimension sheet Probe mounting: Horizontal – Preferred Vertical Down – Possible Important Note: Vertical mounted probes will generally have slower response time because of the lower gas exchange dynamic O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 470 mm 930 mm 1850 mm 2770 mm (Contact ENOTEC) 3690 mm (Contact ENOTEC) Page 65 of 80 O 84 5.2.1 Dimensional drawing of probe KES600x 172 120 C Figure 41 Dimensional drawing of probe KES600x Probe type KES 6001 KES 6002 KES 6003 KES 6004 KES 6005 5.2.2 Protection tube flange Abmessungen Dimensions Flanschtyp type of flange 45° D b d2 holes k A (9,00) 12,5 190,5 19,0 (0,50) (7,50) (0,75) 8 ANSI 3" 300lbs 209,5 (8,25) 28,6 168,3 22,2 (1,13) (6,63) (0,87) 8 190,5 (7,50) 23,9 152,4 19,1 (0,94) (6,00) (0,75) 4 190,0 (7,48) 18,0 150,0 18,0 (0,71) (5,91) (0,71) 4 200,0 (7,87) 20,0 160,0 18,0 (0,79) (6,29) (0,71) 8 DIN2527 DN100/PN16 220,0 20,0 180,0 18,0 (0,79) (7,09) (0,71) 8 120,6 11,0 (4,75) (0,43) 8 186,0 11,0 (7,32) (0,43) 4 DIN2527 DN150/PN16 285,0 (11,22) R 22,0 240,0 22,0 (0,87) (9,45) (0,87) 8 228,6 (9,00) 12,5 190,5 19,1 (0,50) (7,50) (0,75) 8 ANSI 4" 150lbs FF eq. 228,6 Order code: Order code: F ANSI 3" 150lbs Order code: J DIN2527 DN80/PN6 Order code: K DIN2527 DN80/PN16 Order code: Order code: L M Servomex 700 eq Order code: N Servomex 790M eq Order code: P (8,66) 155,0 (6,10) 220,0 (8,66) Order code: ANSI 4" 150lbs RF Order code: Length C (mm) 470 930 1850 2770 3690 T All dimensions in mm (inch) d2 k D 90° d2 k D Mat.: 1.4571 b Figure 42 Dimensional drawing of the protection tube flanges for KES600X O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 66 of 80 Adapter plate ADP-6000 M 16 5.2.3 45 O 90 18 O 191 O 229 Figure 43 Dimensions of adapter plate ADP-6000 Adapter plate ADP-6000-S01 101,6 M16 5.2.4 O 95,6 45 250 O 191 O 229 Figure 44 Dimensions of adapter plate ADP-6000-S01 O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 67 of 80 5.2.5 Probe components 6 7 5 3 8 4 4a 9a 2a 9 2 1 Figure 45 Probe components with working cycles No. ENOTEC – Part-No.: ASK-0003 MSR-6001 FLD-1000 SIK-600x (x=1,2…5) ZO2-6011 MZD-0005 0-R-002311 KES60000x0000(x=1,2…5) KEF-200x BAF-200x SMF-200x KES60000D000 KES600000x00(x=1,2…5) (see table in chapter 5.2.1) KES600000x00(x=A, B…) (see table in chapter 5.2.2) Depending on flange type O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Description Connection box Probe tube Probe flange gasket Probe inner part complete O2 Measuring cell complete (MLT) Metal-O-ring seal Test gas distributor with insulation tube Filter head Ceramic filter with cement Basalt filter with cement Sintered metal filter with cement COe sensor Protection tube Protection tube flange Protection tube flange gasket Page 68 of 80 5.3 Electronic Technical Data & Dimensions Dimensions: see dimensional drawings for the different housings Main voltage 230 V / 50...60 Hz (± 10%) 115 V / 50...60 Hz (± 10%) Power consumption 400 VA during start up, 100 - 200 VA running Recommended fuse 10 A Ambient temperature Version with instrument air: -20 °C (-4 °F) to +55 °C (+131 °F) Version in 19” rack: 0 °C (+32 °F) to 60 °C (+140 °F) Other temperatures on request Relay outputs, potential-free 24 V / 1 A Max. relay output solenoid valve 230V ~ 1A: Analog input O2 sensor Re > 9 MΩ Ue: -45mV to +265mV for the active measuring range Resolution of the digitizers in the active measuring ranges 14 Bits + sign (O2), 10 Bits (COe) Analog input thermocouple Re: > 900 kΩ Temperature compensation located on the circuit board Signal output 4...20 mA max. load 500 Ω potential-free, active Reaction time of the mA output with a change of 100mV on the O2 sensor input <200 ms Display LC-Display, LED-lit 240 x 64 dots graphic display Measuring accuracy ±0.2% of actual measured value (O2) Protection class IP66 (electronic unit in field housing) IP20 (electronic unit in 19” rack) O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 69 of 80 300 240 400 420 440 4X O 8,5 260 132 (3HE) Figure 46 Dimensions of the electronic unit in field housing 308 482 Figure 47 Dimensions of the electronic unit in 19’’ rack O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 70 of 80 5.4 Gas plan SME-5 Instrument air (Version A) 1 3 2 1 4 2 3 2 5 3 1 6 7 8 9 10 11 12 13 14 Figure 48 Gas plan (instrument air version A) Electronic unit O2/COe Probe Flow meter 3/2-way solenoid valve (for test gas 2) 3/2-way solenoid valve (for test gas 1) Choke reference air Pressure reducer O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Instrument air in (2-10 bar, oil free, dry) Test gas 1 in (max. 3 bar) Test gas 2 in (max. 3 bar) Test gas out green tubing (150-180l/h) Reference air out blue tubing (5-60l/h; optimal:30-40l/h)) Probe reference air in blue tubing Probe test gas in green tubing Page 71 of 80 5.5 Gas plan SME-5 Instrument air (Version 1) 1 3 2 1 4 2 3 2 5 3 1 6 8 7 10 9 11 12 13 14 Figure 49 Gas plan (instrument air version 1) Electronic unit O2/COe Probe Flow meter 3/2-way solenoid valve (for test gas 2) 3/2-way solenoid valve (for test gas 1) Choke reference air Pressure reducer O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Choke for Test gas 1 Instrument air in (2-10 bar, oil free, dry) Test gas 2 in (max. 3 bar) Test gas out green tubing (150-180l/h) Reference air out blue tubing (5-60l/h; optimal:30-40l/h)) Probe reference air in blue tubing Probe test gas in green tubing Page 72 of 80 5.6 Gas plan SME-5 with O2 Reference air pump 1 3 2 1 4 2 3 2 6 5 3 1 7 8 10 9 11 12 13 14 Figure 50 Gas plan (with pump) Electronic unit O2/COe Probe Flow meter 3/2-way solenoid valve (for test gas 2) 3/2-way solenoid valve (for test gas 1) Reference air pump Miniature filter O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Reference air in Test gas 1 in (max. 3 bar) Test gas 2 in (max. 3 bar) Test gas out green tubing (150-180l/h) Reference air out blue tubing (30-40l/h)) Probe reference air in blue tubing Probe test gas in green tubing Page 73 of 80 6 Electronic Assembly Overview 6.1 Mounting plates of Field housing Mounting plate 1 (with instrument air, Version A and Version 1) 1 ENOTECPart No. Description TRA-00017 Toroid transformer 2x115V;sec.115V/330VA Solenoid valve for test gas P01 Solenoid valve for test gas P02 Internal flow meter for reference air and test gas SME5 Pressure regulator with two chokes Version 1 (see chapter 5.5) Pressure regulator with one chocke Version A (see chapter 5.4) PGM-0001 PGM-0002 2 DFM-00001 3 4 0-P-000780 0-P-001369 5 Figure 51 Mounting plate 1(instrument air) Mounting plate 1 (with pump) 1 ENOTECPart No. Description TRA-00017 Toroid transformer 2x115V;sec.115V/330VA Solenoid valve for test gas P01 Solenoid valve for test gas P02 Internal flow meter for reference air and test gas SME5 Reference air pump 115V/50Hz; 30l/h PGM-0001 2 PGM-0002 DFM-00001 3 PLU-0025 4 5 Figure 52 Mounting plate 1(with pump) O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 74 of 80 Mounting plate 2 (with instrument air) 1 ENOTECPart No. Description 0-L-000100 0-L-000080 COe-Sensorboard Power board ENOTECPart No. Description 0-L-000100 0-L-000080 0-P-000658 COe-Sensorboard Power board Miniature filter 0,3µm 2 Figure 53 Mounting plate 2(instrument air) Mounting plate 2 (with pump) 1 2 3 Figure 54 Mounting plate 2 (with pump) O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 75 of 80 6.2 Mounting plates of 19”Rack Mounting plate (with instrument Version A and Version 1) 1 air, ENOTECPart No. Description 0-P-000780 Pressure regulator with two chokes Version 1 (see chapter 5.5) Pressure regulator with one chocke Version A (see chapter 5.4) Toroid transformer 2x115V;sec.115V/330VA Internal flow meter for reference air and test gas SME5 Solenoid valve for test gas P01 Power board COe-Sensorboard Solenoid valve for test gas P02 2 0-P-001369 3 4 5 6 TRA-00017 DFM-00001 PGM-0001 0-L-000080 0-L-000100 PGM-0002 7 Figure 55 Mounting plate (instrument air) Mounting plate (with pump) ENOTECPart No. Description PLF-0001 PLF-0002 TRA-00017 Test air / ref. air filter Spare filter element Toroid transformer 2x115V;sec.115V/330VA Internal flow meter for reference air and test gas SME5 Reference air pump COe-Sensorboard Power board Solenoid valve for test gas P01 Solenoid valve for test gas P02 1 2 3 4 5 DFM-00001 PLU-0025 0-L-000100 0-L-000080 PGM-0001 PGM-0002 6 7 8 Figure 56 Mounting plate (with pump) O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 76 of 80 ENOTECPart No. Description 0-L-000102 COMTEC 6000 front panel with electr. without RS232 interface option Figure 57 Display and microprocessor unit) O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 77 of 80 7 Table of figures Figure 1 System overview ..................................................................................................................................9 Figure 2 Installation of the Electronic unit.........................................................................................................16 Figure 3 Access to the terminals ......................................................................................................................16 Figure 4 Instruction for the function of the terminals ........................................................................................16 Figure 5 Wiring diagram of the electronic unit ..................................................................................................17 ® Figure 6 Wiring and terminal connection diagram of COMTEC 6000 ............................................................19 Figure 7 Mounting instructions for pneumatic tubes.........................................................................................20 ® Figure 8 Connections of the COMTEC 6000 Field housing............................................................................21 ® Figure 9 Gas connections of the COMTEC 6000 in 19’’ rack .........................................................................21 Figure 10 Mounting of the mating flange at the duct ........................................................................................23 Figure 11 Adjustment of the measuring probe in the flue gas..........................................................................23 Figure 12 Mounting of the protection tube at the mounting flange ...................................................................24 Figure 13 Electrical connections of the measuring probe ...............................................................................25 Figure 14 Connection of the pneumatic tubes at the measuring probe............................................................26 Figure 15 Insulation of a probe protection tube ................................................................................................26 ® Figure 16 Front panel of the COMTEC 6000 electronic unit after the COe sensor is enabled ......................28 Figure 17 COe value out of range ....................................................................................................................28 Figure 18 Display after heating up (main window) ...........................................................................................30 Figure 19 Adjusting ref. air flow rate at field housing .......................................................................................30 Figure 20 Adjusting ref. air flow rate at 19”rack................................................................................................30 Figure 21 Adjusting test gas 1 flow rate at field housing ..................................................................................31 Figure 22 Adjusting test gas 1 flow rate at field housing ..................................................................................31 Figure 23 Display: main window (example) after calibration ............................................................................32 Figure 24 Display: values menu .......................................................................................................................33 Figure 25 Display: parameter menu .................................................................................................................35 Figure 26 Display: parameter input (example) .................................................................................................38 Figure 27 Display: O2 value is shown as a dry value .......................................................................................40 Figure 28 Display: menu/cal. ............................................................................................................................41 Figure 29 Display: code input ...........................................................................................................................43 Figure 30 Removing of the filter head ..............................................................................................................51 Figure 31 Dismantling of filter ...........................................................................................................................52 Figure 32 Insert the new filteri ..........................................................................................................................52 Figure 33 Exchange of probe inner part ...........................................................................................................53 Figure 34 Mounting O2 sensor holder tube (for KES600x) ...............................................................................54 Figure 35 Connection of the COe sensor..........................................................................................................55 Figure 36 Pull out the COe sensor ...................................................................................................................56 Figure 37 Prepare the new COe sensor............................................................................................................56 Figure 38 Insert the new COe sensor ...............................................................................................................56 Figure 39 Display: error messages...................................................................................................................57 Figure 40 Position of the fuses and the switcher between 230 V and 115 V operation (SW1)........................63 Figure 41 Dimensional drawing of probe KES600x..........................................................................................66 Figure 42 Dimensional drawing of the protection tube flanges for KES600X ..................................................66 Figure 43 Dimensions of adapter plate ADP-6000 ...........................................................................................67 Figure 44 Dimensions of adapter plate ADP-6000-S01 ...................................................................................67 Figure 45 Probe components with working cycles ...........................................................................................68 Figure 46 Dimensions of the electronic unit in field housing ............................................................................70 Figure 47 Dimensions of the electronic unit in 19’’ rack ...................................................................................70 Figure 48 Gas plan (instrument air version A)..................................................................................................71 Figure 49 Gas plan (instrument air version 1) ..................................................................................................72 Figure 50 Gas plan (with pump) .......................................................................................................................73 Figure 51 Mounting plate 1(instrument air).......................................................................................................74 Figure 52 Mounting plate 1(with pump) ............................................................................................................74 Figure 53 Mounting plate 2(instrument air).......................................................................................................75 Figure 54 Mounting plate 2 (with pump) ...........................................................................................................75 Figure 55 Mounting plate (instrument air).........................................................................................................76 Figure 56 Mounting plate (with pump) ..............................................................................................................76 Figure 57 Display and microprocessor unit) .....................................................................................................77 O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 78 of 80 O2/COe COMTEC 6000 InSitu Analyser System Version 05.300.15 Page 79 of 80 Distribution & Service: ENOTEC GmbH Höher Birken 6 D-51709 Marienheide Germany Phone: +49 (0) 2264 / 4578-0 Fax: +49 (0) 2264/ 4578-31 E-Mail: info@enotec.de Internet: www.enotec.com ENOTEC National: Sales Office North/East Herr Dirk Jeworowski Broistedt Str. 26 D - 21423 Winsen Tel.: ++49 (0) 4171 6672 70 Fax: ++49 (0) 4171 7876 400 E-Mail: jeworowski@enotec.de Sales Office West Herr Thomas Bechstein Zum Stollen 4 D – 51674 Wiehl Tel.: ++49 (0) 2262 7527 97 Fax: ++49 (0) 2262 7528 01 E-Mail: bechstein@enotec.de Sales Office Middle Herr Dipl.-Ing. Dieter Rieß Oderstraße 44 D - 64546 Mörfelden-Walldorf Phone: ++49 (0) 6105 9462 38 Fax: ++49 (0) 6105 9462 85 E-Mail: riess@enotec.de Sales Office South Herr Dr. Claus Gumprecht Gössmannsreuth 1 D - 95326 Kulmbach Phone: ++49 (0) 9221 9050 20 Fax: ++49 (0) 9221 9050 41 E-Mail: sales@gumprecht.org ENOTEC International: ENOTEC UK Limited PO BOX 9026 DUMFRIES DG1 3YH United Kingdom ENOTEC Inc. 6206 Sandy Ridge Circle NW North Canton Ohio 44720 USA Phone: +44 8442470102 Fax: +44 8442470302 E-Mail: enotec.uk@enotec.com Phone: +1 330 498 0202 Fax: + 1 330 497 9802 E-Mail: enotec.inc@enotec.com ENOTEC ASIA PTE. Ltd. 151, Pasir Panjang Distripark Block 1 #02-19 Pasir Panjang Road Singapore 118480 Your Distribution: Phone: +65 6100 2188 Fax: +65 6399 2780 E-Mail: enotec.asia@enotec.com O2/COe COMTEC 6000 InSitu Analyser System Please contact: ENOTEC GmbH Phone: ++49 (0) 2264 / 4578-0 Fax: ++49 (0) 2264 / 4578-31 E-Mail: info@enotec.de Version 05.300.15 Page 80 of 80