PADMOUNT SOLID DIELECTRIC SWITCHGEAR CATALOG

Transcription

PADMOUNT SOLID DIELECTRIC SWITCHGEAR CATALOG
Padmount Solid Dielectric Switchgear Catalog
p G&W headquarters in Bolingbrook, IL USA
Company Profile
Since 1905, G&W Electric has helped energize the world with innovative power system solutions. With the introduction of
the first disconnecting cable terminating device, G&W began to build a reputation for engineering custom solutions to meet
the needs of system designers. Solutions which today have extended far beyond cable accessory products and into the
latest in load and fault interrupting switchgear, reclosers, system protection equipment and distribution automation.
Headquarters
G&W headquarters is located in Bolingbrook, IL, USA, a suburb of Chicago. G&W also has manufacturing facilities or
sales offices in China, Mexico, Canada, India, Singapore and Brazil. G&W covers the globe with product installations
and sales representation in over 100 countries and all seven continents.
G&W Electric Facilities:
G&W Electric Co. Headquarters
(Bolingbrook, IL, USA)
G&W China (Shanghai)
G&W Canada
(Mississauga, Ontario)
G&W Mexico (San Luis Potosí)
G&W do Brasil (Salvador)
G&W sales office (Dubai)
G&W sales office (Delhi, India)
G&W ELECTRIC
G&W Manufacturing Facility
G&W sales office (Singapore)
G&W Sales Office
Manufacturer’s Brass and
Aluminum Foundry
(Blue Island, IL, USA)
PA G E 2
Over 110 Years Serving
our
Markets
G&W Product Overview
Single and Three Phase
Solid Dielectric Reclosers
Solid Dielectric Underground
Distribution Switchgear
SF6 Underground
Distribution Switchgear
System Automation and
Smart Grid Solutions
System Protection
Equipment
Transmission and
Distribution Cable
Accessories
G&W ELECTRIC
PA G E 3
Table of Contents
Technology
Solid Dielectric Insulation......................................................................................................... 5
Trident with SafeVu................................................................................................................. 5
Multi-way Trident Solid Dielectric Switch Overview................................................................... 8
Multi-way Three Phase Front Access
Three Phase Load Break and Three Phase Tripping (PLS-FA)...................................................10
Three Phase Load Break Ways and Fault Interrupter Ways with Single Phase Tripping (PLT-FA)..........12
Multi-way Three Phase Front/Back Access
Three Phase Load Break and Three Phase Tripping (PLS-FB)...................................................14
Three Phase Load Break and Single Phase Tripping (PLT-FB)...................................................15
Two-way Trident Solid Dielectric Switch Overview....................................................................16
Two-way Three Phase Front Access...........................................................................................18
Two-way Three Phase Front/Back Access..................................................................................19
Components for Three Phase Switches.....................................................................................20
Overcurrent Protection Options..................................................................................................21
Single Phase
Single Phase Load Break and Fault Interrupting........................................................................22
G&W ELECTRIC
PA G E 4
Technology
What is solid dielectric insulation?
G&W’s solid dielectric insulation is a field proven epoxy
which is used to insulate the high voltage connections of
a vacuum switch. The load break and fault interrupting
vacuum bottle and bushing conductors are fully over molded creating a single phase module. Each module is then
coated with a semi-conductive paint creating a continuous
grounding surface for a truly dead front design. For three
phase switches, three modules are combined together to
create one way of the switch.
Drive rod
Each module can also include an integral current transformer fully protected by the solid dielectric epoxy. This
ensures that the transformer is impervious to environmental conditions and insulated from extreme temperatures.
Encapsulated
current
transformer
G&W’s molding expertise allows for various options including 200A bushing wells or 600A apparatus bushings. The
rugged epoxy surface minimizes the force required for removing elbow connections compared to rubber-to-rubber
junctions. Different module orientations are available which
permit cable entry from the front, back, or bottom of the unit.
Vacuum bottle
The solid dielectric insulations and vacuum bottle combination make the Trident switchgear suitable for wet and
corrosive environments, vertical or horizontal mounting
and use in any altitude.
When
you need visible break ...
Trident
with
SafeVu™
Trident switches are
available with the
SafeVu™ option. These
switches include an
innovative
visible
break feature built
into the switch, which
eliminates the need to
remove elbows or use
externally
mounted
components
to
provide a visible open. p Close up of integrated visible The SafeVu operating
break in the open position
handle is operable via
hook stick or rope rigging, making it ideal for subsurface
applications where space or safety practices prevent the
operator from entering the vault to create a visible break.
Description
The visible break is achieved with a blade type switch
incorporated within the solid dielectric module. The blade
is in series with the vacuum interrupter and provides a clear
visible open. The blade is easily visible through a viewing
window molded as an integral part of each module.
p Internal components are shown outside the module as reference.
G&W ELECTRIC
PA G E 5
Multi-way Trident Solid Dielectric Switches
Front Access
Front Access
Front Access Trident Switches provide a solution for environments where space or aesthetics are
critical factors:
• Single Side Entry – There are only doors on one side of the pad mount enclosure which means
the enclosure can be placed close to a structure
• Easy Access – All components, connections, and operators are located within one compartment
• Flexible Configurations – Switches can range from a two way (in and out) to 6 way and can include inverted designs (bushings towards the top) or bus-tie options.
G&W ELECTRIC
PA G E 6
Multi-way Trident Solid Dielectric Switches
Front/Back Access
Front/Back Access
Front/Back Access Trident Switches provide a compact foot print in a traditional switch design:
• Two Side Entry – With two entry points, one side of the switch can be designated Line (Source)
and the other Load to simplify operations
• Compact Foot print – The Front/Back switches can be designed to fit on existing or pre-manufactured pads to simplify installation
G&W ELECTRIC
PA G E 7
Multi-way Trident Solid Dielectric Switches
Trident solid dielectric insulated switches provide the total life
cycle cost and operational benefits of fuseless, electronically
controlled, resettable overcurrent protection, with the safety
and maintenance benefits of an environmentally friendly
dead-front design.
The Trident utilizes G&W’s time proven, submersible epoxy
insulation to fully encapsulate load and fault interrupting
vacuum interrupters. This solid dielectric insulation
eliminates the degradation of dielectric integrity commonly
associated with oil and air insulated switchgear.
PLS Switch Series
The Trident PLS Series is available in two through six way
configurations, in any combination of three phase load
break switch ways and three phase fault interrupter ways.
The fault interrupter utilizes a trip-free mechanism, which
provides interruption independent of the operating handle
when closing into a fault. Viewing windows provide visible
indication of the contact position.
PLT Switch Series
The Trident PLT Series is available in two through six way
configurations, in any combination of three phase load
break switch ways and single phase fault interrupter ways.
Each fault interrupting mechanism incorporates a tripfree design which permits interruption independent of the
operating handle if closing into a fault. Each phase of the
fault interrupting mechanism can be independently tripped
and reset, providing the ability to maintain energization of
the other phases in the case of a single phase fault. Viewing
windows permit visible indication of the contact position of
all phases.
Applications
Trident load and fault interrupting combination switches
provide a direct replacement for power fused air and
vacuum-in-oil switchgear. Some ideal applications include:
Transformer and Motor Protection — The three phase
trip feature and high continuous current make the PLS
switches ideal for protecting three phase motors and transformer loads.
Loop Switching — Standard 600A loop switching is
accomplished using field proven vacuum switching and
solid dielectric insulation. Switching through 630A provides
up to 12.5kA symmetric fault protection using resettable,
electronically controlled vacuum interrupters. The vacuum
interrupters also function as load break switches.
Residential and Fuse Replacement — The single phase
trip feature of the PLT switches makes them ideal for protecting single phase motors and transformer loads.
G&W ELECTRIC
PA G E 8
p Trident PLS Switch Series
p Trident PLT Switch Series
Access Options — Trident switches are available in a
Front Access design, with operating handles and bushings
on the same side of the switch, and a Front/Back Access
design, with operating handles and bushings on both sides
of the switch.
Additional Features
Visible Break — The load break and three phase fault
interrupter ways are available with G&W’s SafeVu feature,
which provides an integrated visible break disconnect
switch in series with the vacuum interrupter. This eliminates
the need to remove elbows or use externally mounted linkage systems to provide a visible open. Switches equipped
with the SafeVu feature incorporate redundant mechanical
interlocks to ensure the load break switch is open prior to
the operation of the visible break switch.
Testing
Trident switches are designed and tested to applicable standards including IEEE C37.74 (IEEE C37.71 and C37.72),
IEEE 386, IEC 60265, IEEE 592, and IEEE C57.12.28. All
fault interrupter devices have passed IEEE C37.60. Trident
switches are RUS accepted.
Fully encapsulated current transformers provide power and
sensing for G&W’s Vacuum Interrupter controls. The controls emulate the most common time current curves (TCC)
for power fuses, mechanical relays, and fuse links. Control
options include Ground Fault (Phase Imbalance), Time Delays, and Inrush Restraint (Cold Load Pickup).
Multi-way Trident Solid Dielectric Switches
Features and Benefits
Features
Benefits
No maintenance or monitoring system necessary, lowest total life
cycle costs
Epoxy Insulation
(No oil or SF6, and true dead-front design)
Dead-front design provides increased operator safety by
eliminating all exposed live parts
Epoxy is inert, environmentally friendly, with no EPA usage
restrictions
Resettable Vacuum Interrupter Mechanism
No fuses or fuse links to stock and replace
Integral self-powered overcurrent protection available
Integrated solution with fully encapsulated current transformers and
no external power source or PT required
Ratings
The switch is designed, tested and built per IEEE C37.74 for load break switching, IEEE C37.60 for fault interrupting, IEEE
386 for bushing specification, and IEC 60529 for environmental protection rating. Certified test reports are available.
Load Break Ratings
Fault Interrupting Ratings
Voltage Class
15kV 1,2
25kV 2
35kV 3
Voltage Class
15kV 1,2
25kV 2
35kV 3
Max System Voltage
15.5kV
27kV
38kV
Max System Voltage
15.5kV
27kV
38kV
BIL Impulse
110kV 4
125kV
150kV
BIL Impulse
110kV 4
125kV
150kV
Continuous Current
630A
630A
630A
Continuous Current
630A
630A
630A
Load Break Current
630A
630A
630A
AC Withstand, 1 minute
35kV
60kV
70kV
AC Withstand, 1 minute
35kV
60kV
70kV
AC Withstand,
Production, 1 minute
34kV
40kV
50kV
34kV
40kV
50kV
AC Withstand,
Production, 1 minute
53kV
78kV
103kV
53kV
78kV
103kV
12.5kA
12.5kA
12.5kA
20kA
20kA
20kA
Fault-Close 3-times,
asym
2,000
2,000
2,000
20kA
20kA
20kA
1 Second Current, sym
12.5kA
12.5kA
12.5kA
Load Break Switch
Mechanical Operations
2,000
2,000
2,000
DC Withstand,
15 minutes
Momentary Current,
RMS, asym
(1) Integrated visible break available on 15kV load break and three phase fault interrupters. (PLS-FA and PLS-FB
configurations.)
(2) 15kV and 25kV class available for single phase fault
interrupters (PLT-FA and PLT-FB configurations)
(3) 35kV class available for PLS-FB configurations.
(4) BIL impulse rating is 95kV when using integrated visible break feature.
DC Withstand,
15 minutes
Fault Interrupting
Current, sym
Vacuum Interrupter
Mechanical Operations
IEEE C37.60 Fault Interrupting Duty
Percent of
Maximum
Interrupting
Rating
Approximate
Interrupting
Current, Amps
Number of
Fault
Interruptions
15-20%
45-55%
90-100%
2,000
6,000
12,500
44
56
16
Total number of Fault Interruptions: 116
G&W ELECTRIC
PA G E 9
Front Access
PLS-FA Switch Series
Model
One-line
Diagram
Voltage
(kv)
WIDTH
15
6
Width
Inches (mm)
Weight
lbs (kg)
PLS32-376-12-6FA
80 (2040)
2300 (1100)
PLS32-376-12-6FAVU*
103 (2620)
2500 (1200)
PLS32-386-12-6FA
80 (2040)
2300 (1100)
PLS31-376-12-7FA
80 (2040)
2300 (1100)
PLS31-376-12-7FAVU*
103 (2620)
2500 (1200)
PLS31-386-12-7FA
80 (2040)
2300 (1100)
PLS42-376-12-9FA
106 (2700)
2400 (1100)
PLS42-376-12-9FAVU*
132 (3360)
2800 (1300)
PLS42-386-12-9FA
106 (2700)
2400 (1100)
PL44-376-20-10FA
106 (2700)
2400 (1100)
PL44-376-20-10FAVU*
132 (3360)
2800 (1300)
PL44-386-20-10FA
106 (2700)
2400 (1100)
PLS43-376-12-11FA
106 (2700)
2400 (1100)
PLS43-376-12-11FAVU*
132 (3360)
2800 (1300)
PLS43-386-12-11FA
106 (2700)
2400 (1100)
PLS41-376-12-12FA
106 (2700)
2400 (1100)
PLS41-376-12-12FAVU*
132 (3360)
2800 (1300)
PLS41-386-12-12FA
106 (2700)
2400 (1100)
PL33-376-20-13FA
80 (2040)
2300 (1100)
PL33-376-20-13FAVU*
103 (2620)
2500 (1200)
PL33-386-20-13FA
80 (2040)
2300 (1100)
PS40-376-12-40FA
106 (2700)
2400 (1100)
PS40-376-12-40FAVU*
132 (3360)
2800 (1300)
PS40-386-12-40FA
106 (2700)
2400 (1100)
PS50-376-12-50FA
130 (3310)
2600 (1200)
PS50-376-12-50FAVU*
162 (4120)
3000 (1400)
PS50-386-12-50FA
130 (3310)
2600 (1200)
PLS51-376-12-51FA
130 (3310)
2600 (1200)
PLS51-376-12-51FAVU*
162 (4120)
3000 (1400)
PLS51-386-12-51FA
130 (3310)
2600 (1200)
PLS52-376-12-52FA
130 (3310)
2600 (1200)
PLS52-376-12-52FAVU*
162 (4120)
3000 (1400)
PLS52-386-12-52FA
130 (3310)
2600 (1200)
25
HEIGHT
59”
(1494mm)
15
7
25
FRONT
This drawing and the information the
2.19
[56]
SEE NOTES FOR LIMITATIONS
MAXIMUM DESIGN VOLTAGE
IMPULSE LEVEL 1 BIL
AC 1 MIN. WITHSTAND
DC 15 MIN. WITHSTAND
CURRENT CONTINUOUS
CURRENT INTERRUPTING
MOMENTARY CURRENT RMS ASYM.
MAKING CURRENT RMS ASYM.
1 SEC. RATING RMS SYM.
LE
RE
NG
15.5
110
34
53
630
630
20
20
12.5
ALL WAYS
KV
KV
KV
KV
AMP
AMP
KA
KA
KA
ELECTRONIC
CABLE OUTPUT
WAYS 3 & 4
(CABLE CUT
TO LENGTH)
NOTES:
DEPTH
ENCLOSURE
44”
MOUNTING
DETAIL "A"
(1118mm)
2.19
56MM
TYP.
44.00
[1118]
92.13
[2340]
37.8
[960]
ADJUSTABLE
ENCLOSURE
MOUNTING
SWITCH WEIGHT
15.5KV 630AMP 110KV BIL APPARATUS BUSHING **
15.5KV 200AMP 110KV BIL DEEPWELL BUSHING **
15.5KV 200AMP 110KV BIL DEEPWELL BUSHING **
8.27
[210]
PRINT IDENTIFICATION
DATE
25
G&W NO.
CUSTOMER
ORDER NO.
ITEM NO.
FOR RECORD
94.38
[2397]
2. UNFINISHED 304 STAINLESS STEEL MOUNTING PLATE WITH BOLTED
STAINLESS MECHANISM COVER FINISHED ASA 70 LIGHT GRAY.
4.00
[102]
CABLE TRAINING
OUTLINE
3. SWITCH ELECTRICAL RATINGS MAY BE REDUCED BY THE CHOICE
OF ENTRANCES.
10
101.59
[2580]
ENCLOSURE
MOUNTING
50.38
[1280]
4. GALVANIZED STEEL ENCLOSURE FINISHED MUNSELL 7GY3.29/1.5
PADMOUNT GREEN.
FOR APPROVAL-NO MORE WORK TO BE
DONE UNTIL APPROVAL
IS RECEIVED
3.00
[76]
ELECTRONICS
2.19
[56]
TYP.
WAY3:
8. SWITCH IS EQUIPPED WITH 2 FORM C AUXILIARY CONTACTS ON ALL WAYS.
BOTH FORM C CONTACTS FROM ALL 4 WAYS ARE TERMINATED INTO THE
NEMA 4X JUNCTION BOX FOR CUSTOMER USE.
TYPE 2
15-300A
WAY4:
25
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
PA13-SL1SL1S21S21
FOUR WAY SOLID DIELECTRIC SWITCH
G&W ELECTRIC Co.
CAT. NO.:
DRAWN BY:
APPR BY:
11
TYPE 2
15-300A
* ALL PRIMARY DIMENSIONS ARE IN INCHES.
ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
PLAN VIEW
SHOWING OVERALL DIMENSIONS
AND MAXIMUM DIMENSIONS
WHEN ENCLOSURE DOORS ARE OPEN
15
WAY2:
WAY1:
ALL DOORS EQUIPPED
WITH PENTA HEAD
BOLT AND THREE
POINT LATCHING
7. 200 AMP RATED DEEPWELL BUSHINGS WILL REDUCE THE ELECTRICAL
RATINGS TO 200 AMP CONTINUOUS AND 15 KA ASYM. FOR 10 CYCLES.
2200 LBS/ 1000 KG
15.5KV 630AMP 110KV BIL APPARATUS BUSHING **
2
** ELBOWS AND INSERTS PROVIDED BY OTHERS AND
MAY HAVE REDUCED ELECTRICAL RATINGS.
1. ALL SWITCHED WAYS EQUIPPED WITH INTERNAL SPRING OPERATOR
AND EXTERNAL PROVISIONS FOR PADLOCKING IN ALL POSITIONS
6. SWITCH IS EQUIPPED WITH NEMA 4X TYPE 2, 15-300 AMP ELECTRONIC
CONTROLS ON WAYS 3 & 4.
THREE LINE DIAGRAM
ENTRANCES
1
3
4
SEE ENCLOSURE
MOUNTING
DETAIL "A"
22.00
[559]
5. ENCLOSURE IS DESIGNED PER APPLICABLE SECTIONS OF ANSI/IEEE
C37.72 AND ANSI C57.12.28. DRAWING IS TYPICAL AND SHOWS
OVERALL DIMENSIONS ONLY. CONSTRUCTION DETAILS MAY VARY
FROM THOSE DEPICTED.
3D MODEL MC ERRORS 0
DRAWING MC ERRORS 0
3D MODEL LAST CHECKED Wed Nov 09 2011 18:25:06 GMT-0600 3_PHASE_TRID_S_SIDE_HANDLE_CUST
DRAWING LAST CHECKED Wed Nov 09 2011 20:14:59 GMT-0600 STANDARD
SHEET 1 of 2
BOTTOM VIEW
SHOWING ELECTRONIC CABLE OUTPUT
84.0
[2135]
ADJUSTABLE
ENCLOSURE
MOUNTING
1.50
38MM
MIN.
CONCRETE
PAD
9
10.86
[276]
ENCLOSURE
.25" STAINLESS STEEL
ANCHOR BRACKET
WITH .875" X 1.125" OVAL
SUPPLIED BY G&W
SWITCH ELECTRICAL INFORMATION
15
WAY
.625" DIA.
HARDWARE
(4)-SUPPLIED
BY USER
PA13-SL1SL1S21S21
N.A.
10.86
[276]
84.0
[2135]
ADJUSTABLE
ENCLOSURE
MOUNTING
WAY
15.5KV 630AMP 110KV BIL APPARATUS BUSHING **
2
15.5KV 630AMP 110KV BIL APPARATUS BUSHING **
3
15.5KV 200AMP 110KV BIL DEEPWELL BUSHING **
DATE:
DATE:
Nov-09-11
D97LL FF00 L00
SCALE:
15
** ELBOWS AND INSERTS PROVIDED BY OTHERS AND
MAY HAVE REDUCED ELECTRICAL RATINGS.
Depth= 42in (1067mm)
45in (1143mm) with SafeVu options
with standard 24” cable compartment
92.13
[2340]
8.27
[210]
PRINT IDENTIFICATION
DATE
G&W NO.
CUSTOMER
22.00
[559]
ITEM NO.
FOR APPROVAL-NO MORE WORK TO BE
DONE UNTIL APPROVAL
IS RECEIVED
3.00
[76]
WAY2:
Height = 59 in (1494 mm)
with standard 24” Bushing height.
2.19
[56]
TYP.
WAY3:
TYPE 2
15-300A
WAY4:
* ALL PRIMARY DIMENSIONS ARE IN INCHES.
ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
ALL DOORS EQUIPPED
WITH PENTA HEAD
BOLT AND THREE
POINT LATCHING
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
40
PA13-SL1SL1S21S21
FOUR WAY SOLID DIELECTRIC SWITCH
PLAN VIEW
SHOWING OVERALL DIMENSIONS
AND MAXIMUM DIMENSIONS
WHEN ENCLOSURE DOORS ARE OPEN
TYPE 2
15-300A
G&W ELECTRIC Co.
CAT. NO.:
PA13-SL1SL1S21S21
N.A.
DRAWN BY:
APPR BY:
DATE:
Nov-09-11
DATE:
D97LL FF00 L00
SCALE:
SHEET:
15
25
1 of 2
50
15
25
51
15
25
Visit gwelec.com/specs.html
for electronic versions of
guide specifications.
G&W ELECTRIC
PA G E 1 0
SHEET:
1 of 2
REV
DRAWING NO.
Dimensions are approximate.
Do not use for construction.
15
25
ELECTRONICS
WAY1:
101.59
[2580]
ENCLOSURE
MOUNTING
13
ORDER NO.
FOR RECORD
CABLE TRAINING
OUTLINE
15
25
15.5KV 200AMP 110KV BIL DEEPWELL BUSHING **
4
SEE ENCLOSURE
MOUNTING
DETAIL "A"
12
ENTRANCES
1
REV
DRAWING NO.
25
SIDE
Approximate
Catalog Number
52
15
25
*VU indicates the switch includes the SafeVu integrated visible break.
Front Access
PLS-FA Switch Series
Model
One-line
Diagram
Voltage
(kv)
WIDTH
15
53
Width
Inches (mm)
Weight
lbs (kg)
PLS53-376-12-53FA
130 (3310)
2600 (1200)
PLS53-376-12-53FAVU*
162 (4120)
3000 (1400)
PLS53-386-12-53FA
130 (3310)
2600 (1200)
PLS54-376-12-54FA
130 (3310)
2600 (1200)
PLS54-376-12-54FAVU*
162 (4120)
3000 (1400)
PLS54-386-12-54FA
130 (3310)
2600 (1200)
PL55-376-20-55FA
130 (3310)
2600 (1200)
PL55-376-20-55FAVU*
162 (4120)
3000 (1400)
PL55-386-20-55FA
130 (3310)
2600 (1200)
PS60-376-12-60FA
155 (3940)
2800 (1300)
PS60-376-12-60FAVU*
197 (5010)
3300 (1500)
PS60-386-12-60FA
155 (3940)
2800 (1300)
PLS61-376-12-61FA
155 (3940)
2800 (1300)
PLS61-376-12-61FAVU*
197 (5010)
3300 (1500)
PLS61-386-12-61FA
155 (3940)
2800 (1300)
PLS62-376-12-62FA
155 (3940)
2800 (1300)
PLS62-376-12-62FAVU*
197 (5010)
3300 (1500)
PLS62-386-12-62FA
155 (3940)
2800 (1300)
PLS63-376-12-63FA
155 (3940)
2800 (1300)
PLS63-376-12-63FAVU*
197 (5010)
3300 (1500)
PLS63-386-12-63FA
155 (3940)
2800 (1300)
PLS64-376-12-64FA
155 (3940)
2800 (1300)
PLS64-376-12-64FAVU*
197 (5010)
3300 (1500)
PLS64-386-12-64FA
155 (3940)
2800 (1300)
PLS65-376-12-65FA
155 (3940)
2800 (1300)
PLS65-376-12-65FAVU*
197 (5010)
3300 (1500)
PLS65-386-12-65FA
155 (3940)
2800 (1300)
PL66-376-20-66FA
155 (3940)
2800 (1300)
PL66-376-20-66FAVU*
197 (5010)
3300 (1500)
PL66-386-20-66FA
155 (3940)
2800 (1300)
25
HEIGHT
59”
(1494mm)
15
54
25
FRONT
This drawing and the information the
2.19
[56]
SEE NOTES FOR LIMITATIONS
MAXIMUM DESIGN VOLTAGE
IMPULSE LEVEL 1 BIL
AC 1 MIN. WITHSTAND
DC 15 MIN. WITHSTAND
CURRENT CONTINUOUS
CURRENT INTERRUPTING
MOMENTARY CURRENT RMS ASYM.
MAKING CURRENT RMS ASYM.
1 SEC. RATING RMS SYM.
15.5
110
34
53
630
630
20
20
12.5
ALL WAYS
KV
KV
KV
KV
AMP
AMP
KA
KA
KA
ELECTRONIC
CABLE OUTPUT
WAYS 3 & 4
(CABLE CUT
TO LENGTH)
NOTES:
DEPTH
ENCLOSURE
44”
MOUNTING
DETAIL "A"
(1118mm)
2.19
56MM
TYP.
44.00
[1118]
92.13
[2340]
37.8
[960]
ADJUSTABLE
ENCLOSURE
MOUNTING
4.00
[102]
CABLE TRAINING
OUTLINE
60
3. SWITCH ELECTRICAL RATINGS MAY BE REDUCED BY THE CHOICE
OF ENTRANCES.
101.59
[2580]
ENCLOSURE
MOUNTING
50.38
[1280]
4. GALVANIZED STEEL ENCLOSURE FINISHED MUNSELL 7GY3.29/1.5
PADMOUNT GREEN.
8.27
[210]
PRINT IDENTIFICATION
DATE
ORDER NO.
FOR APPROVAL-NO MORE WORK TO BE
DONE UNTIL APPROVAL
IS RECEIVED
3.00
[76]
ELECTRONICS
WAY3:
TYPE 2
15-300A
25
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
PA13-SL1SL1S21S21
FOUR WAY SOLID DIELECTRIC SWITCH
G&W ELECTRIC Co.
CAT. NO.:
DRAWN BY:
PA13-SL1SL1S21S21
N.A.
2.19
[56]
44.00
[1118]
37.8
[960]
ADJUSTABLE
ENCLOSURE
MOUNTING
10.86
[276]
84.0
[2135]
ADJUSTABLE
ENCLOSURE
MOUNTING
WAY
15.5KV 630AMP 110KV BIL APPARATUS BUSHING **
2
15.5KV 630AMP 110KV BIL APPARATUS BUSHING **
DATE:
Nov-09-11
D97LL FF00 L00
15
SCALE:
15.5KV 200AMP 110KV BIL DEEPWELL BUSHING **
4
8.27
[210]
PRINT IDENTIFICATION
DATE
G&W NO.
CUSTOMER
22.00
[559]
4.00
[102]
CABLE TRAINING
OUTLINE
2.19
[56]
TYP.
WAY2:
WAY3:
TYPE 2
15-300A
WAY4:
64
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
PA13-SL1SL1S21S21
FOUR WAY SOLID DIELECTRIC SWITCH
PLAN VIEW
SHOWING OVERALL DIMENSIONS
AND MAXIMUM DIMENSIONS
WHEN ENCLOSURE DOORS ARE OPEN
TYPE 2
15-300A
* ALL PRIMARY DIMENSIONS ARE IN INCHES.
ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
ALL DOORS EQUIPPED
WITH PENTA HEAD
BOLT AND THREE
POINT LATCHING
15
25
ELECTRONICS
Height = 59 in (1494 mm)
with standard 24” Bushing height.
101.59
[2580]
ENCLOSURE
MOUNTING
1 of 2
ITEM NO.
FOR APPROVAL-NO MORE WORK TO BE
DONE UNTIL APPROVAL
IS RECEIVED
3.00
[76]
WAY1:
50.38
[1280]
63
ORDER NO.
FOR RECORD
8
7]
SHEET:
** ELBOWS AND INSERTS PROVIDED BY OTHERS AND
MAY HAVE REDUCED ELECTRICAL RATINGS.
Depth= 42in (1067mm)
45in (1143mm) with SafeVu options
with standard 24” cable compartment
92.13
[2340]
15
25
15.5KV 200AMP 110KV BIL DEEPWELL BUSHING **
3
SEE ENCLOSURE
MOUNTING
DETAIL "A"
62
ENTRANCES
1
REV
DRAWING NO.
DATE:
25
SIDE
ITEM NO.
TYPE 2
15-300A
WAY4:
* ALL PRIMARY DIMENSIONS ARE IN INCHES.
ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
APPR BY:
61
15
WAY2:
WAY1:
2.19
[56]
TYP.
PLAN VIEW
SHOWING OVERALL DIMENSIONS
AND MAXIMUM DIMENSIONS
WHEN ENCLOSURE DOORS ARE OPEN
25
G&W NO.
CUSTOMER
ALL DOORS EQUIPPED
WITH PENTA HEAD
BOLT AND THREE
POINT LATCHING
8. SWITCH IS EQUIPPED WITH 2 FORM C AUXILIARY CONTACTS ON ALL WAYS.
BOTH FORM C CONTACTS FROM ALL 4 WAYS ARE TERMINATED INTO THE
NEMA 4X JUNCTION BOX FOR CUSTOMER USE.
2200 LBS/ 1000 KG
15.5KV 200AMP 110KV BIL DEEPWELL BUSHING **
15.5KV 200AMP 110KV BIL DEEPWELL BUSHING **
** ELBOWS AND INSERTS PROVIDED BY OTHERS AND
MAY HAVE REDUCED ELECTRICAL RATINGS.
FOR RECORD
94.38
[2397]
2. UNFINISHED 304 STAINLESS STEEL MOUNTING PLATE WITH BOLTED
STAINLESS MECHANISM COVER FINISHED ASA 70 LIGHT GRAY.
7. 200 AMP RATED DEEPWELL BUSHINGS WILL REDUCE THE ELECTRICAL
RATINGS TO 200 AMP CONTINUOUS AND 15 KA ASYM. FOR 10 CYCLES.
THREE LINE DIAGRAM
15.5KV 630AMP 110KV BIL APPARATUS BUSHING **
4
1. ALL SWITCHED WAYS EQUIPPED WITH INTERNAL SPRING OPERATOR
AND EXTERNAL PROVISIONS FOR PADLOCKING IN ALL POSITIONS
6. SWITCH IS EQUIPPED WITH NEMA 4X TYPE 2, 15-300 AMP ELECTRONIC
CONTROLS ON WAYS 3 & 4.
SWITCH WEIGHT
15.5KV 630AMP 110KV BIL APPARATUS BUSHING **
2
3
SEE ENCLOSURE
MOUNTING
DETAIL "A"
22.00
[559]
5. ENCLOSURE IS DESIGNED PER APPLICABLE SECTIONS OF ANSI/IEEE
C37.72 AND ANSI C57.12.28. DRAWING IS TYPICAL AND SHOWS
OVERALL DIMENSIONS ONLY. CONSTRUCTION DETAILS MAY VARY
FROM THOSE DEPICTED.
3D MODEL MC ERRORS 0
DRAWING MC ERRORS 0
3D MODEL LAST CHECKED Wed Nov 09 2011 18:25:06 GMT-0600 3_PHASE_TRID_S_SIDE_HANDLE_CUST
DRAWING LAST CHECKED Wed Nov 09 2011 20:14:59 GMT-0600 STANDARD
SHEET 1 of 2
BOTTOM VIEW
SHOWING ELECTRONIC CABLE OUTPUT
84.0
[2135]
ADJUSTABLE
ENCLOSURE
MOUNTING
ENTRANCES
1
1.50
38MM
MIN.
CONCRETE
PAD
55
10.86
[276]
ENCLOSURE
.25" STAINLESS STEEL
ANCHOR BRACKET
WITH .875" X 1.125" OVAL
SUPPLIED BY G&W
SWITCH ELECTRICAL INFORMATION
15
WAY
.625" DIA.
HARDWARE
(4)-SUPPLIED
BY USER
Approximate
Catalog Number
15
G&W ELECTRIC Co.
CAT. NO.:
PA13-SL1SL1S21S21
N.A.
Nov-09-11
Dimensions are approximate.
Do not use for construction.
DRAWN BY:
APPR BY:
DATE:
DATE:
D97LL FF00 L00
SCALE:
SHEET:
25
REV
DRAWING NO.
1 of 2
65
15
25
66
15
25
*VU indicates the switch includes the SafeVu integrated visible break.
Visit gwelec.com/specs.html
for electronic versions of
guide specifications.
G&W ELECTRIC
PA G E 1 1
Front Access
PLT-FA Switch Series
Model
One-line
Diagram
Voltage
(kv)
Approximate
Catalog Number
Width
Inches (mm)
Weight
lbs (kg)
DRAWING REVIEW TEAM
WIDTH
15
6
25
HEIGHT
59”
(1494mm)
15
7
25
15
9
FRONT
25
DEPTH
44”
(1118mm)
DRAWING REVIEW TEAM
REVISIONS
15
11
DATE
25
BOTTOM VIEW (WAY 1)
REVISIONS
DATE
PLT32-376-12-6FA
80 (2040)
2400 (1100)
PLT32-376-12-6FAVU*
103 (2620)
2600 (1200)
PLT32-386-12-6FA
80 (2040)
2400 (1100)
PLT31-376-12-7FA
80 (2040)
2500 (1200)
PLT31-376-12-7FAVU*
103 (2620)
2600 (1200)
PLT31-386-12-7FA
80 (2040)
2500 (1200)
PLT42-376-12-9FA
106 (2700)
2700 (1300)
PLT42-376-12-9FAVU*
132 (3360)
2800 (1300)
PLT42-386-12-9FA
106 (2700)
2700 (1300)
PLT43-376-12-11FA
106 (2700)
2500 (1200)
PLT43-376-12-11FAVU*
132 (3360)
2800 (1300)
PLT43-386-12-11FA
106 (2700)
2500 (1200)
PLT41-376-12-12FA
106 (2700)
2800 (1300)
SHOWING CABLE FEEDTHRU
SWITCH ELECTRICAL INFORMATION
SEE NOTES FOR LIMITATIONS
MAXIMUM DESIGN VOLTAGE
IMPULSE LEVEL 1 BIL
AC 1 MIN. WITHSTAND
DC 15 MIN. WITHSTAND
CURRENT CONTINUOUS
CURRENT INTERRUPTING
MOMENTARY CURRENT RMS ASYM.
MAKING CURRENT RMS ASYM.
1 SEC. RATING RMS SYM.
WAY 1
15.5
KV
110
KV
34
KV
53
KV
630
AMP
630
AMP
20
KA
25.6
KA
12.5
KA
WAYS 2 & 3
15.5
KV
110
KV
34
KV
53
KV
630
AMP
16
KA
BOTTOM VIEW (WAYS 2 & 3)
12
SHOWING CABLE FEEDTHRU
PLAN VIEW
25
SHOWING OVERALL DIMENSIONS AND MAXIMUM
DIMENSIONS WHEN ENCLOSURE DOORS ARE OPEN
1.50
38MM
MIN.
ENCLOSURE
MOUNTING
DETAIL "A"
40
2.19
56MM
TYP.
15
WAY
132 (3360)
ENTRANCES
PLT41-386-12-12FA
106 (2700)
FOR RECORD
2900 (1400)
FOR APPROVAL-NO MORE WORK TO BE
DONE UNTIL APPROVAL
IS RECEIVED
PT40-376-12-40FA
106 (2700)
* ALL PRIMARY DIMENSIONS ARE IN INCHES.
ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
ITEM NO.
2800 (1300)
2300 (1100)
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
PT40-376-12-40FAVU*
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
2
15.5KV 110KV BIL 200A BUSHING WELL PER IEEE 386 FIGURE 3
PA13-SL1T11T11
132 (3360)
THREE WAY SOLID DIELECTRIC SWITCH
PAD 0649A
2200 (1000)
G&W ELECTRIC Co.
CAT. NO.:
PA13-SL1T11T11
NMD
DRAWING NO.
PT40-386-12-40FA
15
PT50-376-12-50FA
130 (3310)
3200 (1500)
25
PT50-386-12-50FA
130 (3310)
3200 (1500)
PLT51-376-12-51FA
130 (3310)
3000 (1400)
PLT51-376-12-51FAVU*
162 (4120)
3100 (1400)
PLT51-386-12-51FA
130 (3310)
3000 (1400)
PLT52-376-12-52FA
130 (3310)
3000 (1400)
PLT52-376-12-52FAVU*
162 (4120)
3100 (1400)
PLT52-386-12-52FA
130 (3310)
3000 (1400)
PLT53-376-12-53FA
130 (3310)
3000 (1400)
PLT53-376-12-53FAVU*
162 (4120)
3000 (1400)
PLT53-386-12-53FA
130 (3310)
3000 (1400)
DRAWN BY:
APPR BY:
106 (2700)
REV
25
15.5KV 110KV BIL 200A BUSHING WELL PER IEEE 386 FIGURE 3
DATE:
DATE:
9-26-14
2300 (1100)
D97LF F000 R00
SCALE:
SHEET:
1 of 2
50
Depth= 42in (1067mm)
45in (1143mm) with SafeVu options
with standard 24” cable compartment
Height = 59 in (1494 mm)
with 24” Bushing height.
51
15
25
PRINT IDENTIFICATION
DATE
G&W NO.
CUSTOMER
ORDER NO.
ITEM NO.
FOR RECORD
MENSIONS AND MAXIMUM
OSURE DOORS ARE OPEN
PLT41-376-12-12FAVU*
1
3
SIDE
AN VIEW
G&W NO.
CUSTOMER
ENCLOSURE
.25" STAINLESS STEEL
ANCHOR BRACKET
WITH .875" X 1.125"
SLOTTED HOLE
SUPPLIED BY G&W
2200 LBS/ 998 KG
PRINT IDENTIFICATION
DATE
ORDER NO.
.625" DIA.
HARDWARE
(4)-SUPPLIED
BY USER
CONCRETE
PAD
SWITCH WEIGHT
15
Dimensions are approximate.
Do not use for construction.
52
FOR APPROVAL-NO MORE WORK TO BE
DONE UNTIL APPROVAL
IS RECEIVED
15
25
* ALL PRIMARY DIMENSIONS ARE IN INCHES.
ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
PA13-SL1T11T11
ENTRANCES
THREE WAY SOLID DIELECTRIC SWITCH
PAD 0649A
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
G&W ELECTRIC Co.
15.5KV 110KV BIL 200A BUSHING WELL PER IEEE 386 FIGURE 3
CAT. NO.:
15.5KV 110KV BIL 200A BUSHING WELL PER IEEE 386 FIGURE 3
DRAWN BY:
APPR BY:
PA13-SL1T11T11
NMD
REV
DRAWING NO.
DATE:
9-26-14
DATE:
D97LF F000 R00
SCALE:
SHEET:
1 of 2
53
15
25
*VU indicates the switch includes the SafeVu integrated visible break.
Visit gwelec.com/specs.html
for electronic versions of
guide specifications.
G&W ELECTRIC
PA G E 1 2
Front Access
PLT-FA Switch Series
Model
One-line
Diagram
Voltage
(kv)
Approximate
Catalog Number
Width
Inches (mm)
Weight
lbs (kg)
DRAWING REVIEW TEAM
D97LF F000 R00
WIDTH
DWG. NO.:
&W.
expressed written consent of G
3000 (1400)
PLT54-376-12-54FAVU*
162 (4120)
3000 (1400)
25
PLT54-386-12-54FA
130 (3310)
3000 (1400)
15
PT60-376-12-60FA
155 (3940)
3400 (1600)
25
PT60-386-12-60FA
155 (3940)
3400 (1600)
PLT61-376-12-61FA
155 (3940)
3300 (1500)
PLT61-376-12-61FAVU*
197 (5010)
3400 (1600)
PLT61-386-12-61FA
155 (3940)
3300 (1500)
PLT62-376-12-62FA
155 (3940)
3200 (1500)
PLT62-376-12-62FAVU*
197 (5010)
3400 (1600)
PLT62-386-12-62FA
155 (3940)
3200 (1500)
PLT63-376-12-63FA
155 (3940)
3100 (1400)
15
property of G
61
reon are and remain the
FRONT
25
This drawing and the information the
DEPTH
44”
(1118mm)
DRAWING REVIEW TEAM
15
REVISIONS
62
DATE
25
BOTTOM VIEW (WAY 1)
SHEET 1 of 2
130 (3310)
60
&W and are not to be copied, reproduce
d or diclosed to others
without the
HEIGHT
59”
(1494mm)
SHOWING CABLE FEEDTHRU
SWITCH ELECTRICAL INFORMATION
WAY 1
15.5
KV
110
KV
34
KV
53
KV
630
AMP
630
AMP
20
KA
25.6
KA
12.5
KA
WAYS 2 & 3
15.5
KV
110
KV
34
KV
53
KV
630
AMP
16
KA
15
BOTTOM VIEW (WAYS 2 & 3)
SHOWING CABLE FEEDTHRU
.625" DIA.
HARDWARE
(4)-SUPPLIED
BY USER
63
PRINT IDENTIFICATION
DATE
G&W NO.
PLT63-376-12-63FAVU*
CUSTOMER
ORDER NO.
197 (5010)
PLAN VIEW
.25" STAINLESS STEEL
ANCHOR BRACKET
WITH .875" X 1.125"
SLOTTED HOLE
SUPPLIED BY G&W
25
SHOWING OVERALL DIMENSIONS AND MAXIMUM
DIMENSIONS WHEN ENCLOSURE DOORS ARE OPEN
PLT63-386-12-63FA
3400 (1600)
ITEM NO.
FOR RECORD
ENCLOSURE
155 (3940)
FOR APPROVAL-NO MORE WORK TO BE
DONE UNTIL APPROVAL
IS RECEIVED
* ALL PRIMARY DIMENSIONS ARE IN INCHES.
ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
1.50
38MM
MIN.
CONCRETE
PAD
PLT64-376-12-64FA
155 (3940)
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
3D MODEL MC ERRORS 0
DRAWING MC ERRORS 0
3D MODEL LAST CHECKED Fri Sep 26 2014 15:43:14 GMT-0600 STANDARD
DRAWING LAST CHECKED Fri Sep 26 2014 15:44:31 GMT-0600 STANDARD
SEE NOTES FOR LIMITATIONS
MAXIMUM DESIGN VOLTAGE
IMPULSE LEVEL 1 BIL
AC 1 MIN. WITHSTAND
DC 15 MIN. WITHSTAND
CURRENT CONTINUOUS
CURRENT INTERRUPTING
MOMENTARY CURRENT RMS ASYM.
MAKING CURRENT RMS ASYM.
1 SEC. RATING RMS SYM.
DATE
PLT54-376-12-54FA
15
54
REVISIONS
SWITCH WEIGHT
ENCLOSURE
MOUNTING
DETAIL "A"
2200 LBS/ 998 KG
WAY
64
2.19
56MM
TYP.
15
ENTRANCES
65
Depth= 42in (1067mm)
45in (1143mm) with SafeVu options
with standard 24” cable compartment
Height = 59 in (1494 mm)
with 24” Bushing height.
PLT64-376-12-64FAVU*
1
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
2
15.5KV 110KV BIL 200A BUSHING WELL PER IEEE 386 FIGURE 3
3
15.5KV 110KV BIL 200A BUSHING WELL PER IEEE 386 FIGURE 3
CAT. NO.:
25
SIDE
15
25
PA13-SL1T11T11
THREE WAY SOLID DIELECTRIC SWITCH
PAD 0649A
DRAWN BY:
PA13-SL1T11T11
NMD
APPR BY:
PLT64-386-12-64FA
197 (5010)
DATE:
DATE:
9-26-14
3100 (1400)
3000 (1400)
DRAWING NO.
3300 (1500)
SCALE:
SHEET:
G&W ELECTRIC Co.
REV
D97LF F000 R00
1 of 2
155 (3940)
3000 (1400)
PLT65-376-12-65FA
155 (3940)
2900 (1300)
PLT65-376-12-65FAVU*
197 (5010)
3300 (1500)
PLT65-386-12-65FA
155 (3940)
2900 (1300)
*VU indicates the switch includes the SafeVu integrated visible break.
PRINT IDENTIFICATION
DATE
G&W NO.
CUSTOMER
ORDER NO.
ITEM NO.
FOR RECORD
PLAN VIEW
NG OVERALL DIMENSIONS AND MAXIMUM
ONS WHEN ENCLOSURE DOORS ARE OPEN
Dimensions are approximate.
Do not use for construction.
FOR APPROVAL-NO MORE WORK TO BE
DONE UNTIL APPROVAL
IS RECEIVED
* ALL PRIMARY DIMENSIONS ARE IN INCHES.
ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
PA13-SL1T11T11
WAY
ENTRANCES
1
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
2
15.5KV 110KV BIL 200A BUSHING WELL PER IEEE 386 FIGURE 3
3
15.5KV 110KV BIL 200A BUSHING WELL PER IEEE 386 FIGURE 3
THREE WAY SOLID DIELECTRIC SWITCH
PAD 0649A
G&W ELECTRIC Co.
CAT. NO.:
DRAWN BY:
APPR BY:
PA13-SL1T11T11
NMD
REV
DRAWING NO.
DATE:
9-26-14
DATE:
D97LF F000 R00
SCALE:
SHEET:
1 of 2
Visit gwelec.com/specs.html
for electronic versions of
guide specifications.
G&W ELECTRIC
PA G E 1 3
Front/Back Access
D98LL FF00 BE0
PLS-FB Switch Series
Model
Voltage
(kv)
15
&W.
DWG. NO.:
WIDTH
72”
(1810mm)
One-line
Diagram
d or diclosed to others
&W and are not to be copied, reproduce
property of G
FRONT
reon are and remain the
This drawing and the information the
Weight
lbs (kg)
PLS32-376-12-6FB
77 (1960)
1500 (700)
92 (2340)
1900 (900)
PLS32-386-12-6FB
77 (1960)
1700 (800)
35
PLS32-396-12-6FB
77 (1960)
1700 (800)
PLS31-376-12-7FB
77 (1960)
1700 (800)
PLS31-376-12-7FBVU*
92 (2340)
1900 (900)
25
PLS31-386-12-7FB
77 (1960)
1700 (800)
35
PLS31-396-12-7FB
77 (1960)
1700 (800)
77 (1960)
1800 (900)
ENTRANCES
WAY
1
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
2
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
NOTES:
BACK
WAYS 1 & 2
15.5
110
34
53
630
630
20
20
12.5
15.5
110
34
53
630
12.5
DRAWING REVIEW TEAM
PLS42-376-12-9FBVU*
92 (2340)
2200 (1000)
PLS42-386-12-9FB
77 (1960)
1800 (900)
35
PLS42-396-12-9FB
77 (1960)
1800 (900)
PL44-376-20-10FB
77 (1960)
1800 (900)
15
PL44-376-20-10FBVU*
92 (2340)
2200 (1000)
25
PL44-386-20-10FB
77 (1960)
1800
(900)
BOTTOM VIEW
SHOWING
35
PL44-396-20-10FB
77 (1960)
(WAYS
3 & 4)
1800
(900)
PLS43-376-12-11FB
77 (1960)
1800 (900)
PLS43-376-12-11FBVU*
92 (2340)
25
PLS43-386-12-11FB
77 (1960)
35
PLS43-396-12-11FB
77 (1960)
SH
JQ
PLS41-376-12-12FB
77 (1960)
PLS41-376-12-12FBVU*
92 (2340)
25
PLS41-386-12-12FB
77 (1960)
35
PLS41-396-12-12FB
77 (1960)
PL33-376-20-13FB
77 (1960)
5. WHEN ELBOWS, INSERTS, AND ANY OTHER ACCESSORIES ARE CONNECTED TO THE SWITCH,
THE RATINGS OF EACH CONNECTED ASSEMBLY WILL BE THAT OF THE LOWEST RATED
COMPONENT OF THE ASSEMBLY.
6. MOUNTING INFORMATION: THE FRAME OF THE SWITCH MUST BE ANCHORED TO THE PAD.
THE FRAME IS EQUIPPED WITH 4 SLOTTED ANCHORING HOLES, EACH MEASURING
9/16" X 1". THE LOCATIONS OF THESE HOLES, REFERRED TO AS "FRAME MOUNTING"
ARE SHOWN IN THE FRONT VIEW AND RIGHT VIEW. THE PAD MOUNT ENCLOSURE SHOULD
BE SECURED TO THE PAD TO PROVIDE IT WITH ADDITIONAL STABILITY. EACH PAD MOUNT
ENCLOSURE IS SHIPPED WITH 4 SECURING BRACKETS THAT ARE TO BE USED FOR THIS
PURPOSE. THE SECURING BRACKETS CAN BE INSTALLED ANYWHERE ALONG THE INNER
EDGE OF THE ENCLOSURE. SEE ENCLOSURE MOUNTING DETAIL "A" AND THE PLAN VIEW
FOR MORE DETAILS ABOUT SECURING THE PAD MOUNT ENCLOSURE TO THE PAD.
REVISIONS
RD
REV.
CHANGE
DEPTH
DATE
15
12
PLAN VIEW SHOWING OVERALL
DIMENSIONS AND MAXIMUM
NOTES:
DIMENSIONS WHEN ENCLOSURE
DOORS ARE OPEN
1. ALL WAYS ARE EQUIPPED WITH INTERNAL SPRING OPERATORS AND EXTERNAL PROVISIONS
FOR PADLOCKING IN ALL POSITIONS.
BACK
2000 LBS / 909 KG
2. UNFINISHED 304/304L STAINLESS STEEL MOUNTING PLATE WITH BOLTED 304/304L
STAINLESS MECHANISM COVER PAINTED ASA 70 LIGHT GRAY. GALVANIZED STEEL
ENCLOSURE FINISHED MUNSELL 7GY3.29/1.5 PADMOUNT GREEN.
15
3. ENCLOSURE IS DESIGNED PER APPLICABLE SECTIONS OF ANSI/IEEE C37.74
& C57.12.28. ENCLOSURE IS TYPICAL AND SHOWS THE OVERALL DIMENSIONS
ONLY. CONSTRUCTION DETAILS MAY VARY FROM THOSE DEPICTED. ENCLOSURE
DOOR IS EQUIPPED WITH THREE POINT LATCH WITH PENTA HEAD BOLT AND
PROVISION FOR PADLOCK.
13
35
SIDE
DRAWN BY:
APPR BY:
G OPERATORS AND EXTERNAL PROVISIONS
BOTTOM VIEW SHOWING
Depth includes 24” cable compartments
FEEDTHRU LOCATIONS
(WAYS 3 & 4)
Dimensions are approximate.
Do not use for construction.
SSORIES ARE CONNECTED TO THE SWITCH,
WILL BE THAT OF THE LOWEST RATED
CUSTOMER
SWITCH MUST BE ANCHORED TO THE PAD.
ORING HOLES, EACH MEASURING
ERRED TO AS "FRAME MOUNTING"
W. THE PAD MOUNT ENCLOSURE SHOULD
DITIONAL STABILITY. EACH PAD MOUNT
KETS THAT ARE TO BE USED FOR THIS
ALLED ANYWHERE ALONG THE INNER
NTING DETAIL "A" AND THE PLAN VIEW
MOUNT ENCLOSURE TO THE PAD.
PRINT IDENTIFICATION
G&W NO.
ORDER NO.
FOR RECORD
ITEM NO.
FOR APPROVAL-NO MORE WORK TO BE
DONE UNTIL APPROVAL
IS RECEIVED
Visit gwelec.com/specs.html
for electronic versions of
guide specifications.
* ALL PRIMARY DIMENSIONS ARE IN INCHES.
ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
BA13-SL0SL0S10S10
FOUR WAY FRONT/ BACK PADMOUNT
SOLID DIELECTRIC SWITCH
CAT. NO.:
DRAWN BY:
APPR BY:
BA13-SL0SL0S10S10
SH
JQ
G&W ELECTRIC
G&W ELECTRIC Co.
REV
DRAWING NO.
DATE:
DATE:
Oct-16-14
Oct-16-14
D98LL FF00 BE0
SCALE:
PA G E 1 4
SHEET:
1 of 1
DATE:
BA13-SL0SL0S10S10
1800 (900)
FOUR WAY FRONT/ BACK PADMOUNT
SOLID DIELECTRIC SWITCH
BA13-SL0SL0S10S10
SH
JQ
1800 (900)
DATE:
Oct-16-14
Oct-16-14
1700 (800)
DATE:
PL33-396-20-13FB
77 (1960)
1700 (800)
77 (1960)
1800 (900)
PS40-376-12-40FBVU*
92 (2340)
2200 (1000)
PS40-386-12-40FB
77 (1960)
1800 (900)
PS40-396-12-40FB
77 (1960)
1800 (900)
ITEM NO.
G&W ELECTRIC Co.
REV
DRAWING NO.
DATE:
2200 (1000)
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
PS40-376-12-40FB
FOUR WAY FRONT/ BACK PADMOUNT
SOLID DIELECTRIC SWITCH
BA13-SL0SL0S10S10
SH
JQ
Oct-16-14
Oct-16-14
D98LL FF00 BE0
SCALE:
SHEET:
1 of 1
ITEM NO.
FOR APPROVAL-NO MORE WORK TO BE
DONE UNTIL APPROVAL
IS RECEIVED
*VU indicates the switch includes the SafeVu integrated visible break.
Height = 59 in (1494 mm)
with standard 24” Bushing height.
DATE
FOR RECORD
1900 (900)
BA13-SL0SL0S10S10
CAT. NO.:
1800 (900)
1800 (900)
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
PLAN VIEW SHOWING OVERALL
DIMENSIONS AND MAXIMUM
DIMENSIONS WHEN ENCLOSURE
DOORS ARE OPEN
RRENT TRANSFORMERS ON WAYS
UM INTERRUPTER CONTROL FOR
ONSIBLE FOR ENTERING PROTECTION
NG.
ORDER NO.
1800 (900)
1700 (800)
* ALL PRIMARY DIMENSIONS ARE IN INCHES.
ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
Width= 72 in (1810 mm)
G&W NO.
CUSTOMER
92 (2340)
FOR APPROVAL-NO MORE WORK TO BE
DONE UNTIL APPROVAL
IS RECEIVED
35
PRINT IDENTIFICATION
77 (1960)
FOR RECORD
25
APPR BY:
G&W NO.
ORDER NO.
40
CAT. NO.:
DRAWN BY:
PRINT IDENTIFICATION
15
6. MOUNTING INFORMATION: THE FRAME OF THE SWITCH MUST BE ANCHORED TO THE PAD.
THE FRAME IS EQUIPPED WITH 4 SLOTTED ANCHORING HOLES, EACH MEASURING
9/16" X 1". THE LOCATIONS OF THESE HOLES, REFERRED TO AS "FRAME MOUNTING"
ARE SHOWN IN THE FRONT VIEW AND RIGHT VIEW. THE PAD MOUNT ENCLOSURE SHOULD
BE SECURED TO THE PAD TO PROVIDE IT WITH ADDITIONAL STABILITY. EACH PAD MOUNT
ENCLOSURE IS SHIPPED WITH 4 SECURING BRACKETS THAT ARE TO BE USED FOR THIS
PURPOSE. THE SECURING BRACKETS CAN BE INSTALLED ANYWHERE ALONG THE INNER
EDGE OF THE ENCLOSURE. SEE ENCLOSURE MOUNTING DETAIL "A" AND THE PLAN VIEW
FOR MORE DETAILS ABOUT SECURING THE PAD MOUNT ENCLOSURE TO THE PAD.
DATE
2200 (1000)
DATE
PL33-386-20-13FB
CUSTOMER
CHANGE
FEEDTHRU LOCATIONS
PL33-376-20-13FBVU*
DATE
5. WHEN ELBOWS, INSERTS, AND ANY OTHER ACCESSORIES ARE CONNECTED TO THE SWITCH,
THE RATINGS OF EACH CONNECTED ASSEMBLY WILL BE THAT OF THE LOWEST RATED
COMPONENT OF THE ASSEMBLY.
REV.
* ALL PRIMARY DIMENSIONS ARE IN INCHES.
ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
BOTTOM VIEW SHOWING
FEEDTHRU LOCATIONS
(WAYS 3 & 4)
25
4. SWITCH IS EQUIPPED WITH INTERNAL 1000:1 CURRENT TRANSFORMERS ON WAYS
3 & 4. WAYS 3 & 4 EACH INCLUDE A TYPE 1 VACUUM INTERRUPTER CONTROL FOR
OVERCURRENT PROTECTION. CUSTOMER IS RESPONSIBLE FOR ENTERING PROTECTION
SETTINGS INTO THE CONTROL BEFORE ENERGIZING.
ING PLATE WITH BOLTED 304/304L
LIGHT GRAY. GALVANIZED STEEL
DMOUNT GREEN.
IONS OF ANSI/IEEE C37.74
S THE OVERALL DIMENSIONS
THOSE DEPICTED. ENCLOSURE
TH PENTA HEAD BOLT AND
DATE
4. SWITCH IS EQUIPPED WITH INTERNAL 1000:1 CURRENT TRANSFORMERS ON WAYS
3 & 4. WAYS 3 & 4 EACH INCLUDE A TYPE 1 VACUUM INTERRUPTER CONTROL FOR
OVERCURRENT PROTECTION. CUSTOMER IS RESPONSIBLE FOR ENTERING PROTECTION
SETTINGS INTO THE CONTROL BEFORE ENERGIZING.
11
BACK
FRONT
CHANGE
REVISIONS
RD
25
15
KV
KV
KV
KV
AMP
KA
FRONT
SWITCH WEIGHT
REV.
3. ENCLOSURE IS DESIGNED PER APPLICABLE SECTIONS OF ANSI/IEEE C37.74
& C57.12.28. ENCLOSURE IS TYPICAL AND SHOWS THE OVERALL DIMENSIONS
ONLY. CONSTRUCTION DETAILS MAY VARY FROM THOSE DEPICTED. ENCLOSURE
DOOR IS EQUIPPED WITH THREE POINT LATCH WITH PENTA HEAD BOLT AND
PROVISION FOR PADLOCK.
WAYS 3 & 4
KV
KV
KV
KV
AMP
AMP
KA
KA
KV
RD
2. UNFINISHED 304/304L STAINLESS STEEL MOUNTING PLATE WITH BOLTED 304/304L
STAINLESS MECHANISM COVER PAINTED ASA 70 LIGHT GRAY. GALVANIZED STEEL
ENCLOSURE FINISHED MUNSELL 7GY3.29/1.5 PADMOUNT GREEN.
SEE NOTES FOR LIMITATIONS
MAXIMUM DESIGN VOLTAGE
IMPULSE LEVEL (BIL)
AC 1 MIN. WITHSTAND
DC 15 MIN. WITHSTAND
CURRENT CONTINUOUS
CURRENT INTERRUPTING
MOMENTARY CURRENT RMS ASYM.
MAKING CURRENT RMS ASYM.
1 SEC. RATING RMS SYM.
SH
JQ
1. ALL WAYS ARE EQUIPPED WITH INTERNAL SPRING OPERATORS AND EXTERNAL PROVISIONS
FOR PADLOCKING IN ALL POSITIONS.
10
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
HEIGHT
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
59”
(1494mm)
SWITCH ELECTRICAL INFORMATION
3
REVISIONS
PLS42-376-12-9FB
15
9
SHEET 1 of 1
3D MODEL LAST CHECKED Wed Oct 15 2014 20:01:42 GMT-0600 3_PHASE_TRID_S_SIDE_HANDLE_CUST
DRAWING LAST CHECKED Thu Oct 16 2014 01:23:28 GMT-0600 STANDARD
Depth
Inches (mm)
DRAWING REVIEW TEAM
4
3D MODEL MC ERRORS 1
DRAWING MC ERRORS 2
Catalog Number
PLS32-376-12-6FBVU*
15
7
DRAWING REVIEW TEAM
SH
JQ
25
without the
expressed written consent of G
6
Approximate
G&W ELECTRIC Co.
REV
DRAWING NO.
D98LL FF00 BE0
SCALE:
SHEET:
1 of 1
Front/Back Access
PLT-FB Switch Series
WIDTH
72”
(1810mm)
Model
6
One-line
Diagram
Voltage
(kv)
15
25
7
15
25
FRONT
9
15
25
10
HEIGHT
59”
(1494mm)
15
25
11
25
BACK
DEPTH
15
12
15
25
13
15
25
SIDE
Width= 72 in (1810 mm)
40
15
25
Approximate
Catalog Number
Depth
Inches (mm)
Weight
lbs (kg)
PLT32-376-12-6FB
77 (1960)
1700 (800)
PLT32-376-12-6FBVU*
92 (2340)
1900 (900)
PLT32-386-12-6FB
77 (1960)
2000 (900)
PLT31-376-12-7FB
77 (1960)
2000 (900)
PLT31-376-12-7FBVU*
92 (2340)
1900 (900)
PLT31-386-12-7FB
77 (1960)
2000 (900)
PLT42-376-12-9FB
77 (1960)
2300 (1100)
PLT42-376-12-9FBVU*
92 (2340)
2200 (1000)
PLT42-386-12-9FB
77 (1960)
2300 (1100)
PL44-376-20-10FB
77 (1960)
2300 (1100)
PL44-376-20-10FBVU*
92 (2340)
2200 (1000)
PL44-386-20-10FB
77 (1960)
2300 (1100)
PLT43-376-12-11FB
77 (1960)
2300 (1100)
PLT43-376-12-11FBVU*
92 (2340)
2200 (1000)
PLT43-386-12-11FB
77 (1960)
2300 (1100)
PLT41-376-12-12FB
77 (1960)
2300 (1100)
PLT41-376-12-12FBVU*
92 (2340)
2200 (1000)
PLT41-386-12-12FB
77 (1960)
2300 (1100)
PL33-376-20-13FB
77 (1956)
2000 (900)
PL33-376-20-13FBVU*
92 (2340)
1900 (900)
PL33-386-20-13FB
77 (1960)
2000 (900)
PT40-376-12-40FB
77 (1960)
2300 (1100)
PT40-376-12-40FBVU*
92 (2340)
2200 (1000)
PT40-386-12-40FB
77 (1960)
2300 (1100)
*VU indicates the switch includes the SafeVu integrated visible break.
Height = 59 in (1494 mm)
with standard 24” Bushing height.
Depth includes 24” cable compartments
Dimensions are approximate.
Do not use for construction.
Visit gwelec.com/specs.html
for electronic versions of
guide specifications.
G&W ELECTRIC
PA G E 1 5
Two-way Trident Solid Dielectric Switches
Front Access
Front Access
Front Access Trident Switches provide a solution for environments where space or aesthetics are
critical factors:
• Single Side Entry – There are only doors on one side of the pad mount enclosure which means
the enclosure can be placed close to a structure
• Easy Access – All components, connections, and operators are located within one compartment
• Flexible Configurations – Switches can range from a two way (in and out) to 6 way and can include inverted designs (bushings towards the top) or bus-tie options.
G&W ELECTRIC
PA G E 1 6
Two-way Trident Solid Dielectric Switches
Front/Back Access
Front/Back Access
Front/Back Access Trident Switches provide a compact foot print in a traditional switch design:
• Two Side Entry – With two entry points, one side of the switch can be designated Line (Source)
and the other Load to simplify operations
• Compact Foot print – The Front/Back switches can be designed to fit on existing or pre-manufactured pads to simplify installation
G&W ELECTRIC
PA G E 1 7
Two-way Trident Solid Dielectric Switches
Trident solid dielectric insulated switches provide
the total life cycle cost and operational benefits of
fuseless, electronically controlled, resettable overcurrent
protection, with the safety and maintenance benefits of
an environmentally friendly dead-front design.
The Trident utilizes G&W’s time proven, submersible
epoxy insulation to fully encapsulate load and fault
interrupting vacuum interrupters. This solid dielectric
insulation eliminates the degradation of dielectric
integrity commonly associated with oil and air insulated
switchgear.
Configurations
The two way Trident is available as a loadbreak switch or
a fault interrupter. The fault interrupter utilizes a trip-free
mechanism, which provides interruption independent of
the operating handle when closing into a fault. Viewing
windows provide visible indication of the contact position.
Applications
Trident load and fault interrupting switches provide a
direct replacement for power fused air and vacuum-in-oil
switchgear. Some ideal applications include:
Transformer and Motor Protection — The three phase
trip feature and high continuous current make the two
way Trident fault interrupters switches ideal for protecting three phase motors and transformer loads.
Access Options — Trident switches are available in a
Front Access design, with operating handles and bushings on the same side of the switch, and a low profile
Front/Back Access design, with bushings on both sides
of the switch.
Additional Features
Visible Break — The Front Access two way Trident is
available with G&W’s SafeVu feature, which provides
an integrated visible break disconnect switch in series
with the vacuum interrupter. This eliminates the need to
G&W ELECTRIC
PA G E 1 8
p Low Profile Front/Back Access Design
remove elbows or use externally mounted linkage systems to provide a visible open. Switches equipped with
the SafeVu feature incorporate redundant mechanical
interlocks to ensure the load break switch is open prior
to the operation of the visible break switch.
Testing
Trident switches are designed and tested to applicable
standards including IEEE C37.74 (IEEE C37.71 and
C37.72), IEEE 386, IEC 60265, IEEE 592, and IEEE
C57.12.28. All fault interrupter devices have passed
IEEE C37.60. Trident switches are RUS accepted.
Fully encapsulated current transformers provide power
and sensing for G&W’s Vacuum Interrupter controls. The
controls emulate the most common time current curves
(TCC) for power fuses, mechanical relays, and fuse links.
Control options include Ground Fault (Phase Imbalance),
Time Delays, and Inrush Restraint (Cold Load Pickup).
Two-way Trident Solid Dielectric Switches
Features and Benefits
Features
Benefits
No maintenance or monitoring system necessary, lowest total life
cycle costs
Epoxy Insulation
(No oil or SF6, and true dead-front design)
Dead-front design provides increased operator safety by
eliminating all exposed live parts
Epoxy is inert, environmentally friendly, with no EPA usage
restrictions
Resettable Vacuum Interrupter Mechanism
No fuses or fuse links to stock and replace
Integral self-powered overcurrent protection available
Integrated solution with fully encapsulated current transformers and
no external power source or PT required
Ratings
The switch is designed, tested and built per IEEE C37.74 for load break switching, IEEE C37.60 for fault interrupting, IEEE
386 for bushing specification, and IEC 60529 for environmental protection rating. Certified test reports are available.
Load Break Ratings
Fault Interrupting Ratings
Voltage Class
15kV 1
25kV
35kV
Voltage Class
15kV 1
25kV
35kV
Max System Voltage
15.5kV
27kV
38kV
Max System Voltage
15.5kV
27kV
38kV
BIL Impulse
110kV 2
125kV
150kV
BIL Impulse
110kV 2
125kV
150kV
Continuous Current
630A
630A
630A
Continuous Current
630A
630A
630A
Load Break Current
630A
630A
630A
AC Withstand, 1 minute
35kV
60kV
70kV
AC Withstand, 1 minute
35kV
60kV
70kV
AC Withstand,
Production, 1 minute
34kV
40kV
50kV
34kV
40kV
50kV
AC Withstand,
Production, 1 minute
53kV
78kV
103kV
53kV
78kV
103kV
12.5kA
12.5kA
12.5kA
20kA
20kA
20kA
Fault-Close 3-times,
asym
2,000
2,000
2,000
20kA
20kA
20kA
1 Second Current, sym
12.5kA
12.5kA
12.5kA
Load Break Switch
Mechanical Operations
2,000
2,000
2,000
DC Withstand,
15 minutes
Momentary Current,
RMS, asym
(1) Integrated visible break available on 15kV load break and three phase fault interrupters.
(2) BIL impulse rating is 95kV when using integrated visible break feature.
DC Withstand,
15 minutes
Fault Interrupting
Current, sym
Vacuum Interrupter
Mechanical Operations
IEEE C37.60 Fault Interrupting Duty
Percent of
Maximum
Interrupting
Rating
Approximate
Interrupting
Current, Amps
Number of
Fault
Interruptions
15-20%
45-55%
90-100%
2,000
6,000
12,500
44
56
16
Total number of Fault Interruptions: 116
G&W ELECTRIC
PA G E 1 9
Two-way Trident Solid Dielectric Switches
D9700 2FCR HR0
DWG. NO.:
PL21-376-20-3FA
25
PL21-386-20-3FA
35
PL21-396-20-3FA
15
PS20-376-12-4FA
25
PS20-386-12-4FA
35
PS20-396-12-4FA
6-5-14
25.00
[635]
ADJUSTABLE
ADJUSTABLE
ENCLOSURE
ENCLOSURE
MOUNTING
MOUNTING
UP TO UP TO
21.75 21.75
[552] [552]
4
3.00
[76]
3.00
[76]
26.00
[660]
26.00
[660]
53.75 53.75
[1365] [1365]
26.63 26.63
[676] [676]
ENCLOSURE
ENCLOSURE
MOUNTING
MOUNTING
PLAN VIEW
SHOWING
MAXIMUM
PLAN
VIEW SHOWING
MAXIMUM
DIMENSIONS
WHEN ENCLOSURE
DIMENSIONS
WHEN ENCLOSURE
DOOR ISDOOR
OPEN IS OPEN
SIDE
FRONT
.625" DIA. .625" DIA.
HARDWAREHARDWARE
(4)-SUPPLIED(4)-SUPPLIED
BY USER BY USER
ENCLOSUREENCLOSURE
MAXIMUMMAXIMUM
DESIGN VOLTAGE
DESIGN VOLTAGE
IMPULSE LEVEL
( BILLEVEL
) ( BIL )
IMPULSE
AC 1 MIN.AC
WITHSTAND
1 MIN. WITHSTAND
3D MODEL LAST CHECKED Tue Apr 15 2014 14:02:42 GMT-0600 3_PHASE_TRID_S_SIDE_HANDLE_CUST
DRAWING LAST CHECKED Tue Apr 22 2014 11:21:08 GMT-0600 STANDARD
15.5
110
34
53
630
12.5
DC 15 MIN.
DCWITHSTAND
15 MIN. WITHSTAND
CURRENTCURRENT
CONTINUOUS
CONTINUOUS
CURRENTCURRENT
INTERRUPTING
SYM.
INTERRUPTING
SYM.
15.5KV
110KV
34 KV
53 KV
630AMP
12.5KA
ENCLOSURE
ENCLOSURE
MOUNTING
MOUNTING
DETAIL
"A" "A"
DETAIL
KV
KV
KV
KV
AMP
KA
2.19
56MM
TYP.
1.50
38MM
MIN.
.25" STAINLESS
.25"STEEL
STAINLESS STEEL
ANCHOR BRACKET
ANCHOR BRACKET
WITH .875" XWITH
1.125"
.875" X 1.125"
SLOTTED HOLE
SLOTTED HOLE
SUPPLIED BYSUPPLIED
G&W BY G&W
1.50
38MM
MIN.
DWG. NO.:
&W.
15
DATE
204309
A CL 204309 CL6-5-14
WAY
WAY
2.19
56MM
TYP.
3D MODEL MC ERRORS 0
DRAWING MC ERRORS 1
SWITCH WEIGHT
SWITCH WEIGHT
15.5KV
110KV
BIL 600A
APPARATUSAPPARATUS
BUSHING PER
IEEE 386
FIGURE
11 FIGURE 11
15.5KV
110KVDEADBREAK
BIL 600A DEADBREAK
BUSHING
PER
IEEE 386
1
2
15.5KV
BIL 600A
APPARATUSAPPARATUS
BUSHING PER
IEEE 386
FIGURE
11 FIGURE 11
15.5KV
110KVDEADBREAK
BIL 600A DEADBREAK
BUSHING
PER
IEEE 386
2 110KV
PRINT IDENTIFICATION
PRINT IDENTIFICATION
BOTTOM
VIEW VIEW
BOTTOM
DATE
SHOWING
FEEDTHRU
LOCATION
SHOWING
FEEDTHRU
LOCATION
(MOUNTING
PLATE NOT
(MOUNTING
PLATE NOT
SHOWN SHOWN
FOR CLARITY)
FOR CLARITY)
Model
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
ORDER NO.
ORDER NO.
FOR RECORD
FOR RECORD
FOR APPROVAL-NO
MORE WORK
TOWORK
BE TO BE
FOR APPROVAL-NO
MORE
DONE UNTIL
APPROVAL
DONE
UNTIL APPROVAL
IS RECEIVED
IS RECEIVED
THREE LINE
DIAGRAM
THREE
LINE DIAGRAM
550 LBS / 550
250 LBS
KG / 250 KG
DWG. NO.:
One-line
Diagram
* ALL PRIMARY
DIMENSIONS
ARE IN INCHES.
* ALL PRIMARY
DIMENSIONS
ARE IN INCHES.
ALL SECONDARY
DIMENSIONS
ARE IN MILLIMETERS.
ALL SECONDARY
DIMENSIONS
ARE IN MILLIMETERS.
G&W NO.G&W NO.
DATE
CUSTOMER
CUSTOMER
ITEM NO. ITEM NO.
PA13-S206PA13-S206
THREE PHASE
THREE PHASE
SOLID DIELECTRIC
SWITCH SWITCH
SOLID DIELECTRIC
G&W ELECTRIC
Co.
G&W ELECTRIC
Co.
DRAWING REVIEW TEAM
CAT. NO.:
DRAWN BY:
APPR BY:
3
WIDTH
39”
(991mm)
expressed written consent of G
&W.
ENTRANCESENTRANCES
1
PA13-S206
CAT. NO.:
PA13-S206
IMN
DRAWN BY:
IMN
RYL
APPR BY:
RYL
SH
DATE:
DATE:
VX
REV. NO.
DRAWING
CHANGE
D9700D9700
2FCR
HR0 BSNHR0
A
187586
2FCR
Apr-15-14
DATE:
Apr-15-14
JQ
Apr-15-14
DATE:
Apr-15-14
SCALE:
B
C
SHEET: JXU
189834
1 ofSHEET:
1
195152 SH
SCALE:
REVDATE
REV
A
1-15-14
1 of 12-13-14
3-20-14
A
SH
JQ
VX
REV.
Catalog Number
REVISIONS
CHANGE
A
B
C
187586 BSN
189834 JXU
195152 SH
DATE
1-15-14
2-13-14
3-20-14
PL21-376-20-3FAVU
SWITCH ELECTRICAL INFORMATION
SWITCH ELECTRICAL INFORMATION
SEE NOTES FOR LIMITATIONS
SEE NOTES FOR LIMITATIONS
15.5
95
34
53
630
630
20
20
12.5
MAXIMUM DESIGN VOLTAGE
IMPULSE LEVEL ( BIL )
AC 1 MIN. WITHSTAND
DC 15 MIN. WITHSTAND
CURRENT CONTINUOUS
CURRENT INTERRUPTING SYM.
MOMENTARY CURRENT RMS ASYM.
MAKING CURRENT RMS ASYM.
1 SEC. RATING RMS SYM.
Voltage
(kv)
DRAWING REVIEW TEAM
REVISIONS
DRAWING NO.
KV MAXIMUM DESIGN VOLTAGE
KV IMPULSE LEVEL ( BIL )
KV AC 1 MIN. WITHSTAND
KV DC 15 MIN. WITHSTAND
AMP CURRENT CONTINUOUS
AMP CURRENT INTERRUPTING SYM.
KA MOMENTARY CURRENT RMS ASYM.
KA MAKING CURRENT RMS ASYM.
KA 1 SEC. RATING RMS SYM.
15
15.5
95
34
53
630
630
20
20
12.5
KV
KV
KV
KV
AMP
AMP
KA
KA
KA
d or diclosed to others
without the
4
PS20-376-12-4FAVU
THREE LINE DIAGRAM
THREE LINE DIAGRAM
SWITCH
WEIGHT
750
LBS / 340
KG
SWITCH WEIGHT
&W and are not to be copied, reproduce
HEIGHT
59”
(1499mm)
ENTRANCES
WAY
750 LBS / 340 KG
ENTRANCES
WAY
1
15.5KV 95KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
15.5KV 95KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 3861FIGURE 11
2
15.5KV 95KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
15.5KV 95KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 3862FIGURE 11
61.26
[1556]
61.26
[1556]
39.00
[991]
reon are and remain the
property of G
39.00
[991]
3.81
[97]
3.81
[97]
33.00
[838]
This drawing and the information the
33.00
[838]
SHEET 1 of 1
DEPTH
48”
(1219mm)
3.00
[76]
TYP.
3.00
[76]
TYP.
2.19
[56]
TYP.
2.19
[56]
TYP.
34.63
[879]
ENCLOSURE
MOUNTING
34.00
[864]
CUSTOMER
CUSTOMER
ORDER NO.
ORDER NO.
FOR RECORD
FOR APPROVAL-NO MORE WORK TO BE
DONE UNTIL APPROVAL
IS RECEIVED
Depth includes 24” cable compartment
Dimensions are approximate.
Do not use for construction.
G&W ELECTRIC
PA G E 2 0
34.00
[864]
PLAN VIEW
PLAN VIEW
G&W NO. DATE
34.63
[879]
ENCLOSURE
MOUNTING
SHOWING MAXIMUM DIMENSIONS
WHEN ENCLOSURE DOOR IS OPEN
SHOWING MAXIMUM DIMENSIONS
WHEN ENCLOSURE DOOR IS OPEN
G&W NO.
* ALL PRIMARY DIMENSIONS ARE IN INCHES.
ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
* ALL PRIMARY DIMENSIONS ARE IN INCHES.
ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
PRINT IDENTIFICATION
PRINT IDENTIFICATION
DATE
TRIDENT BOTTOM VIEW
82.00
[2083]
82.00
[2083]
SIDE
FRONT
DRAWING LAST CHECKED Thu Feb 13 2014 02:21:51 GMT-0600 STANDARD
DRAWING MC ERRORS 0
Catalog Number
31.00
[787]
25.00
[635]
Front Access with SafeVu Switch Series
W
REVISIONS
DATE
CHANGE
Voltage
(kv)
&W.
expressed written consent of G
expressed written consent of G
without the
without the
d or diclosed to others
d or diclosed to others
31.00
[787]
&W and are not to be copied, reproduce
&W and are not to be copied, reproduce
3
SEE NOTESSEE
FOR
LIMITATIONS
NOTES
FOR LIMITATIONS
3D MODEL LAST CHECKED Tue Apr 15 2014 14:02:42 GMT-0600 3_PHASE_TRID_S_SIDE_HANDLE_CUST
DRAWING LAST CHECKED Tue Apr 22 2014 11:21:08 GMT-0600 STANDARD
CHANGE
REV.
A
SWITCH
ELECTRICAL
INFORMATION
SWITCH
ELECTRICAL
INFORMATION
3D MODEL MC ERRORS 0
DRAWING MC ERRORS 1
REVISIONS
REV.
property of G
property of G
DRAWING REVIEW TEAM
DRAWING REVIEW TEAM
reon are and remain the
reon are and remain the
DEPTH
36”
(705mm)
HEIGHT
58”
(1458mm)
This drawing and the information the
This drawing and the information the
SHEET 1 OF 1
WIDTH
31”
(787mm)
CONCRETE CONCRETE
PAD
PAD
D9700 8LCR B00
One-line
Diagram
Model
SHEET 1 OF 1
D9700 2FCR HR0
Front Access Switch Series
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
PA13-SVL06
PA13-SVL06
ITEM NO. FOR RECORD
FOR APPROVAL-NO MORE WORK TO BE
PA13-SVL06
DONE UNTIL APPROVALCAT. NO.:
IS RECEIVED
DRAWN BY:
WMJ
APPR BY:
RYL
PADMOUNT TRIDENT WITH SAFEVU
WITH 600A BUSHINGS
PADMOUNT TRIDENT WITH SAFEVU
ITEM NO. WITH 600A BUSHINGS
CAT. NO.:
DATE:
DATE:
9-28-13
9-28-13
G&W ELECTRIC Co.
G&W ELECTRIC Co.
DRAWN BY:
APPR BY:
PA13-SVL06
DRAWING NO.
D9700
8LCR B00
WMJ
RYL
SCALE:
SHEET:
REV
DATE:
9-28-13 C
DATE:
1 of
1 9-28-13
REV
DRAWING NO.
D9700 8LCR B00
SCALE:
SHEET:
C
1 of 1
Two-way Trident Solid Dielectric Switches
Front/Back Switch Series
One-line
Diagram
Model
Voltage
(kv)
Catalog Number
15
PL21-376-20-3FB
25
PL21-386-20-3FB
35
PL21-396-20-3FB
15
PS20-376-12-4FB
25
PS20-386-12-4FB
35
PS20-396-12-4FB
3
HEIGHT
42”
(1067mm)
4
FRONT
.625" DIA.
HARDWARE
(4)-SUPPLIED
BY USER
39.21
[996]
27.00
[686]
TYP.
ENCLOSURE
.25" STAINLESS STEEL
ANCHOR BRACKET
WITH .875" X 1.125"
SLOTTED HOLE
SUPPLIED BY G&W
DEPTH
41”
(1042mm)
6.08
[155]
TYP.
BACK
ENCLOSURE
MOUNTING
DETAIL "A"
106.87
[2715]
CABLE
TRAINING
OUTLINES
72.66
[1846]
34.83
[885]
ENCLOSURE
MOUNTING
1.50
38MM
MIN.
CONCRETE
PAD
WAY
2.19
[56]
TYP.
2.19
56MM
TYP.
ENTRANCES
1
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
2
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
FRONT
* ALL PRIMARY DIMENSIONS ARE IN INCHES.
ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
BA13-SL06
W
THREE PHASE SOLID DIELECTRIC SWITCH
G&W ELECTRIC Co.
IMENSIONS
MENSIONS
ARE OPEN.
CAT. NO.:
DRAWN BY:
APPR BY:
BA13-SL06
SH
JQ
DRAWING NO.
DATE:
DATE:
Dec-24-14
Dec-24-14
REV
D9700 2LCR AZ0
SCALE:
SHEET:
1 of 1
SIDE
1. SWITCHED WAY EQUIPPED WITH INTERNAL SPRING OPERATOR
AND EXTERNAL PROVISIONS FOR PADLOCKING IN ALL POSITIONS.
.625" DIA.
HARDWARE
(4)-SUPPLIED
BY USER
39.21
[996]
34.21
[869]
TYP.
27.00
[686]
TYP.
ENCLOSURE
.25" STAINLESS STEEL
ANCHOR BRACKET
WITH .875" X 1.125"
SLOTTED HOLE
SUPPLIED BY G&W
6.08
[155]
TYP.
BACK
CONCRETE
PAD
1.50
38MM
MIN.
D9700 2LCR AZ0
DWG. NO.:
TYP.
8.00
[203]
2. UNFINISHED 304/304L STAINLESS STEEL MOUNTING PLATE WITH BOLTED
304/304L STAINLESS MECHANISM COVER PAINTED ASA 70 LIGHT GRAY.
304 STAINLESS STEEL ENCLOSURE FINISHED PADMOUNT GREEN MUNSELL
7GY3.29/1.5.
&W.
ADJUSTABLE
ENCLOSURE
MOUNTING
UP TO
32.46
[824]
expressed written consent of G
3. ENCLOSURE IS DESIGNED PER APPLICABLE SECTIONS OF
ANSI/IEEE C37.74 & C57.12.29. ENCLOSURE IS TYPICAL AND
SHOWS THE OVERALL DIMENSIONS ONLY, CONSTRUCTION DETAILS
MAY VARY FROM THOSE DEPICTED. ENCLOSURE DOOR IS
EQUIPPED WITH THREE POINT LATCH WITH PENTA HEAD BOLT
AND PROVISION FOR PADLOCK.
11.00
[279]
72.66
[1846]
without the
4. WHEN ELBOWS, INSERTS, AND ANY OTHER ACCESSORIES ARE CONNECTED TO
THE SWITCH, THE RATINGS OF EACH CONNECTED ASSEMBLY WILL BE THAT OF
THE LOWEST RATED COMPONENT OF THE ASSEMBLY
34.83
[885]
ENCLOSURE
MOUNTING
3.00
[76]
TYP.
5. MOUNTING INFORMATION: THE FRAME OF THE SWITCH MUST BE ANCHORED TO THE PAD.
THE FRAME IS EQUIPPED WITH 4 SLOTTED ANCHORING HOLES, EACH MEASURING
9/16" X 1". THE LOCATIONS OF THESE HOLES, REFERRED TO AS "FRAME MOUNTING"
ARE SHOWN IN THE BACK VIEW AND LEFT VIEW. THE PAD MOUNT ENCLOSURE SHOULD
BE SECURED TO THE PAD TO PROVIDE IT WITH ADDITIONAL STABILITY. EACH
PAD MOUNT ENCLOSURE IS SHIPPED WITH 4 SECURING BRACKETS THAT ARE TO BE
USED FOR THIS PURPOSE. THE SECURING BRACKETS CAN BE INSTALLED ANYWHERE
ALONG THE INNER EDGE OF THE ENCLOSURE. SEE ENCLOSURE MOUNTING DETAIL "A"
AND THE PLAN VIEW FOR MORE DETAILS ABOUT SECURING THE PAD MOUNT ENCLOSURE
TO THE PAD.
ENCLOSURE
MOUNTING
DETAIL "A"
106.87
[2715]
CABLE
TRAINING
OUTLINES
2.19
[56]
TYP.
WAY
2.19
56MM
TYP.
ENTRANCES
1
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
2
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
d or diclosed to others
FRONT
* ALL PRIMARY DIMENSIONS ARE IN INCHES.
ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
&W and are not to be copied, reproduce
BA13-SL06
PLAN VIEW
SHOWING OVERALL DIMENSIONS
AND MAXIMUM DIMENSIONS
WHEN ENCLOSURE DOORS ARE OPEN.
THREE PHASE SOLID DIELECTRIC SWITCH
G&W ELECTRIC Co.
CAT. NO.:
DRAWN BY:
BA13-SL06
SH
JQ
DRAWING NO.
DATE:
DATE:
REV
D9700 2LCR AZ0
Dec-24-14
Dec-24-14
SCALE:
SHEET:
1 of 1
property of G
APPR BY:
This drawing and the information the
reon are and remain the
BACK
PRINT IDENTIFICATION
DATE
NOTES:
CUSTOMER
1. SWITCHED WAY EQUIPPED WITH INTERNAL SPRING OPERATOR
AND EXTERNAL PROVISIONS FOR PADLOCKING IN ALL POSITIONS.
SHEET 1 of 1
ORDER NO.
FOR RECORD
ITEM NO.
FOR APPROVAL-NO MORE WORK TO BE
DONE UNTIL APPROVAL
IS RECEIVED
SWITCH ELECTRICAL INFORMATION
3D MODEL MC ERRORS 1
DRAWING MC ERRORS 1
3D MODEL LAST CHECKED Wed Dec 24 2014 01:39:25 GMT-0600 CUSTOMER
DRAWING LAST CHECKED Wed Dec 24 2014 01:40:52 GMT-0600 STANDARD
SEE NOTES FOR LIMITATIONS
MAXIMUM DESIGN VOLTAGE
IMPULSE LEVEL ( BIL )
AC 1 MIN. WITHSTAND
DC 15 MIN. WITHSTAND
CURRENT CONTINUOUS
CURRENT INTERRUPTING SYM.
MOMENTARY CURRENT RMS ASYM.
MAKING CURRENT RMS ASYM.
1 SEC. RATING RMS SYM.
15.5
110
34
53
630
630
20
20
12.5
KV
KV
KV
KV
AMP
AMP
KA
KA
KA
2. UNFINISHED 304/304L STAINLESS STEEL MOUNTING PLATE WITH BOLTED
304/304L STAINLESS MECHANISM COVER PAINTED ASA 70 LIGHT GRAY.
304 STAINLESS STEEL ENCLOSURE FINISHED PADMOUNT GREEN MUNSELL
7GY3.29/1.5.
3. ENCLOSURE IS DESIGNED PER APPLICABLE SECTIONS OF
ANSI/IEEE C37.74 & C57.12.29. ENCLOSURE IS TYPICAL AND
SHOWS THE OVERALL DIMENSIONS ONLY, CONSTRUCTION DETAILS
MAY VARY FROM THOSE DEPICTED. ENCLOSURE DOOR IS
EQUIPPED WITH THREE POINT LATCH WITH PENTA HEAD BOLT
AND PROVISION FOR PADLOCK.
Depth includes 16” cable compartments
4. WHEN ELBOWS, INSERTS, AND ANY OTHER ACCESSORIES ARE CONNECTED TO
THE SWITCH, THE RATINGS OF EACH CONNECTED ASSEMBLY WILL BE THAT OF
THE LOWEST RATED COMPONENT OF THE ASSEMBLY
5. MOUNTING INFORMATION: THE FRAME OF THE SWITCH MUST BE ANCHORED TO THE PAD.
THE FRAME IS EQUIPPED WITH 4 SLOTTED ANCHORING HOLES, EACH MEASURING
9/16" X 1". THE LOCATIONS OF THESE HOLES, REFERRED TO AS "FRAME MOUNTING"
ARE SHOWN IN THE BACK VIEW AND LEFT VIEW. THE PAD MOUNT ENCLOSURE SHOULD
BE SECURED TO THE PAD TO PROVIDE IT WITH ADDITIONAL STABILITY. EACH
PAD MOUNT ENCLOSURE IS SHIPPED WITH 4 SECURING BRACKETS THAT ARE TO BE
USED FOR THIS PURPOSE. THE SECURING BRACKETS CAN BE INSTALLED ANYWHERE
ALONG THE INNER EDGE OF THE ENCLOSURE. SEE ENCLOSURE MOUNTING DETAIL "A"
AND THE PLAN VIEW FOR MORE DETAILS ABOUT SECURING THE PAD MOUNT ENCLOSURE
TO THE PAD.
Dimensions are approximate.
Do not use for construction.
THREE LINE DIAGRAM
SWITCH WEIGHT
600 LBS / 273 KG
.625" DIA.
HARDWARE
(4)-SUPPLIED
BY USER
39.21
[996]
34.21
[869]
TYP.
G&W NO.
27.00
[686]
TYP.
3.00
[76]
TYP.
BACK
CONCRETE
PAD
8.00
[203]
ADJUSTABLE
ENCLOSURE
MOUNTING
UP TO
32.46
[824]
72.66
[1846]
3.00
[76]
TYP.
34.83
[885]
ENCLOSURE
MOUNTING
2.19
[56]
TYP.
ENCLOSURE
MOUNTING
DETAIL "A"
106.87
[2715]
CABLE
TRAINING
OUTLINES
11.00
[279]
ENCLOSURE
.25" STAINLESS STEEL
ANCHOR BRACKET
WITH .875" X 1.125"
SLOTTED HOLE
SUPPLIED BY G&W
6.08
[155]
TYP.
1.50
38MM
MIN.
NOTES:
WIDTH
40”
3.00
(1016mm)
[76]
WAY
2.19
56MM
TYP.
ENTRANCES
1
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
2
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
FRONT
* ALL PRIMARY DIMENSIONS ARE IN INCHES.
ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
BA13-SL06
PLAN VIEW
SHOWING OVERALL DIMENSIONS
AND MAXIMUM DIMENSIONS
WHEN ENCLOSURE DOORS ARE OPEN.
THREE PHASE SOLID DIELECTRIC SWITCH
G&W ELECTRIC Co.
CAT. NO.:
DRAWN BY:
APPR BY:
BA13-SL06
SH
JQ
DRAWING NO.
DATE:
DATE:
Dec-24-14
Dec-24-14
REV
D9700 2LCR AZ0
SCALE:
SHEET:
G&W ELECTRIC
1 of 1
PA G E 2 1
Components for Three Phase Switches
Overcurrent Protection
Fault interrupters are equipped with an encapsulated
500:1 or 1000:1 current transformer and a G&W self
powered Vacuum Interrupter Control. Alternately, a wide
variety of protective relay packages are available, including relays from SEL and other leading relay suppliers.
External CTs
and External PTs
Metering or relaying accuracy current and potential
transformers are available for use with protective relay
packages.
Auxiliary Contacts
Auxiliary contacts are mounted internal to the mechanism
housing to provide remote indication of switch contact
position. One normally open and one normally closed
Form C contact is provided. A junction box is available
with terminal strip connections for up to four auxiliary
contacts.
Motor Actuator
Automation begins with the addition of motor actuators to
a manual switch. These actuators can be factory installed
for new equipment or retrofitted to switchgear installed in
the field. (Refer to the Motor Operator catalog, MO11, for
motor control options.)
p Example of integrated external transformer
Operating Handle
G&W will select the appropriate handle based on the
application. Handles are operable via hook stick or rope
rigging.
Key Interlocks
Key interlocks may be
used to ensure safe
coordination of equipment. All Trident ways
can be equipped
with provisions for
key interlocks. Key
interlocks can be provided, and factory
installed if required.
p Side mounted motor actuator
p Key interlock
G&W ELECTRIC
PA G E 2 2
Overcurrent Protection Options
Type
Trip
Selection
Enclosure
Rating
User
Interface
Settings
Available
Type 1.0
Single or Three
Phase
NEMA 4X*
Knobs
Phase Only
Type 2.0
Three Phase
NEMA 4X*
Knobs
Phase and
Ground
NEMA 4X*
Via
computer using a programming port, or
manually via
the pushbuttons on the
front panel
Phase and
Ground
Available as
EZset or Plus
Phase and
Ground
Available as
EZset or Plus
Notes
Type 3.1
Single or Three
Phase
Type 4.1
NEMA 4X
Single or Three
Phase
NEMA 4X
Computer
using a
Programming
Port
Type 4.1
IP68
Single or Three
Phase
IP68
(submerged in
20’ of water for
20 days)
Computer
using a
Programming
Port
Phase and
Ground
Available as
EZset or Plus
Type 7.1
Single or Three
Phase
IP68
(located within
the mechanism
housing)
Computer
using a
Programming
Port
Phase and
Ground
Available as
EZset or Plus
* Optional clear lid enclosure available (shown above on Type 2)
G&W ELECTRIC
PA G E 2 3
Single Phase
Trident solid dielectric insulated switches provide the total life
cycle cost and operational benefits of fuseless, electronically
controlled, resettable overcurrent protection, with the safety
and maintenance benefits of an environmentally friendly
dead-front design.
The Trident utilizes G&W’s time proven, submersible epoxy
insulation to fully encapsulate load and fault interrupting
vacuum interrupters. This solid dielectric insulation
eliminates the degradation of dielectric integrity commonly
associated with oil insulated switchgear.
Single Phase
Trident single phase, spring-assisted switchgear is available for load break or fault interrupting switching. The
compact units are ideal for switching residential loops
and for oil fuse cutout replacements. Fault protection
can be provided using vacuum interrupters with integral current transformers and a variety of overcurrent
controls.
The Single Phase Trident is available in a Front Access
design, with operating handles and bushings on the same
side of the switch, The switch can be mounted vertically (as
shown on the right) or horizontally (as shown on page 19)
to best meet the requirements of the application.
Testing
Trident switches are designed and tested to applicable standards including IEEE C37.74 (IEEE C37.71 and C37.72),
IEEE 386, IEC 60265, IEEE 592, and IEEE C57.12.28. All
fault interrupter devices have passed IEEE C37.60. Trident
switches are RUS accepted.
p Single phase Trident switch
Fully encapsulated current transformers provide power and
sensing for G&W’s solid state electronic controls. The controls emulate the most common time current curves (TCC)
for power fuses, mechanical relays, and fuse links.
Features and Benefits
Features
Benefits
No maintenance or monitoring system, lowest total life cycle costs
Epoxy Insulation
(No oil or SF6, and true dead-front design)
Dead-front design provides increased operator safety by
eliminating all exposed live parts
Epoxy is inert, environmentally friendly, with no EPA usage
restrictions
Resettable Vacuum Interrupter Mechanism
No fuses or fuse links to stock and replace
Integral self-powered overcurrent protection available
Integrated solution with fully encapsulated current transformers and
no external power source or PT required
G&W ELECTRIC
PA G E 2 4
Single Phase
Ratings
Load Break & Fault Interrupting Ratings
Voltage Class
15kV
25kV
Max System Voltage
15.5kV
27kV
BIL Impulse
110kV
125kV
Continuous Current
630A
630A
Load Break Current
630A
630A
AC Withstand, 1 minute
35kV
60kV
AC Withstand, Production,
1 minute
34kV
40kV
DC Withstand, 15 minutes
53kV
78kV
Momentary Current, RMS, asym
20kA
20kA
Fault-Close 3-times, asym
20kA
20kA
Fault Interrupting Current, asym
12.5kA
12.5kA
1 Second Current, sym
12.5kA
12.5kA
Load Break Switch
Mechanical Operations
2,000
2,000
24”
(610mm)
38”
(965mm)
FRONT
31”
(787mm)
Catalog Numbering
Model
30”
(762mm)
3
SIDE
Approximate Weight = 150 lbs. (68 kg)
4
One-line
Diagram
Voltage
(kv)
Catalog Number
15
PL21-176-20-3FA
25
PL21-186-20-3FA
15
PS20-176-12-4FA
25
PS20-186-12-4FA
Dimensions are approximate.
Do not use for construction.
G&W ELECTRIC
PA G E 2 5
G&W offers
Technical Support and Services:
Custom Engineering
Our engineers can tailor our products to
meet the needs of any application.
Custom Programming
Our automation engineers can provide tailored
relay programs to meet any specified needs.
Factory Acceptance Testing
G&W’s Factory Acceptance Testing ensures
customers’ automation solutions are certified
to operate properly and meet all requirements
prior to being installed in the field.
Training Services
G&W offers a range of training solutions at
both G&W facilities and on site.
24 Hour Technical Support
Technical support for G&W products is
available 24 hours a day, 7 days a week.
For more information: gwelec.com
General inquiries by email: info@gwelec.com
Find your local sales representative: gwelec.com
Tel 708.388.5010 Fax 708.388.0755
Catalog S-psd15