MegaTron BlueTrak Supplement
Transcription
MegaTron BlueTrak Supplement
Manual MegaTron Controller Supplemental BlueTrack Instructions Notice: This manual includes instructions for the BlueTrack that is not covered in the main MegaTron manual but will refer to items covered in the main manual. Advantage Controls P.O. Box 1472 Muskogee, OK 74402 Phone: 800-743-7431 Fax: 888-686-6212 www.advantagecontrols.com email: support@advantagecontrols.com 4/2010 MegaTron Controller BlueTrack Option “U” Manual Table of Contents Contents Page I. Introduction......................................................................................... 2 Description of Option “U”.................................................................... 3 Electrical Wiring.................................................................................. 3 II. Operation............................................................................................ 4 A. Customize................................................................................. 4 B. Configure.................................................................................. 4 C. Set Points................................................................................. 5 D. Calibration................................................................................ 6 Troubleshooting.................................................................................. 7 III. I. Introduction Advantage Controls’ BlueTrack controllers are designed to monitor and control the concentration of the BlueTrace organic colorant in a recirculating cooling water system. This colorant, available from ProChemTech, is blended with cooling water treatment chemicals at a very precise ratio. By measuring the amount of BlueTrace colorant, we are able to infer the amount of cooling water treatment present in a system. BlueTrack sensors use a custom LED and photoreceptor to measure the transmittance of light through a solution containing the BlueTrace colorant. The sensor outputs a variable 0-5 VDC signal based on the level of light that is transmitted through a solution. This 0-5 VDC signal is sent to a MegaTron or MegaTron SS controller equipped with option “U” (0-5 VDC input). There is an inverse relationship between BlueTrace concentration and BlueTrack voltage output. Higher concentrations of BlueTrace in a sample will decrease the amount of transmitted light and will yield a lower voltage output, while lower concentrations of BlueTrace will allow more light to pass through the solution and yield a higher voltage output. The following chart represents the relationship between BlueTrace concentration, absorbance (impedance to light transmittance), and voltage output: BlueTrace Concentration 0.0 ppm 1.0 ppm 2.0 ppm Absorbance 0.00 0.08 0.16 BlueTrack Voltage Output 5.00 V 4.17 V 3.38 V To simplify this inverse relationship, we invert the 0-5 VDC output scale so that higher levels of BlueTrace chemical correspond to a higher percent reading on the MegaTron. The controller displays 100-%T. You can convert % transmission to absorbance with the equation A = 2 - log10%T. % Transmittance Absorbance Description of Option “U” MegaTron controllers with option “U” may have one to eight 0-5 VDC inputs. The 0-5 VDC inputs will operate similarly to a 4-20mA input and use the same basic menu in the MegaTron. When used with a BlueTrack sensor, a 0-5 VDC input from the BlueTrak sensor can be used to activate a relay based on a set point for automatic feed of BlueTrace chemicals. Electrical Wiring If a BlueTrack sensor is ordered with a MegaTron it will be prewired to the 0-5 VDC input card using low voltage. MegaTron 0-5 VDC Card Non-Isolated GND GND GND GND GND GND GND Black & Green GND BlueTrack Probe White Red MegaTronSS 0-5 VDC Card Non-Isolated 0-5 VDC Input Card for SS MegaTron 0-5 VDC Input Non-Isolated J1 Input 1 J3 Input 2 IN-8 IN-7 IN-6 IN-5 IN-4 IN-3 IN-2 IN-1 +12V +12V +12V +12V +12V +12V +12V +12V J4 Input 3 Note: Use 22 AWG (.76 mm) twisted pair shielded wire for all of these low voltage signal connections. LED Ground Signal +12 VDC II. Operations The MegaTron’s BlueTrack control circuit is designed maintain a precise level of BlueTrace in the recirculating cooling tower water by monitoring the BlueTrace level and activating a relay output as the BlueTrace level falls. As such, the MegaTron is programmed with a “falling” setpoint. There are four MegaTron menus that relate to customizing, calibrating, and programming the BlueTrack sensor. Units with a 0-5 VDC input option “U” will have the following menus to program for controlling with a BlueTrack sensor. A. Customize This menu allows the user to define the on-screen name of the unit plus the name of each system and relay. The user can also setup a 0-5 VDC input name and unit of measurement. >CUSTOMIZE< UNIT NAME RELAY NAMES NOTEPAD SYSTEM 1 NAME pH INDEX SYSTEM 2 NAME 0-5 IN RUN SCREEN Note: When entering values for custom names use the numerical keys for numbers and the up / down arrows to scroll through all the characters of a key board. Press the right arrow to advance the curser after setting a desired value. Press the Help button to place the last entered character into the new cursor space to speed up the process. The Help button will also jump advance through the characters. >0-5 INPUT 1 CUSTOMIZE< NAME UNITS NUMBER NAME - Customize the name of the input. UNITS - Set the units of measurement. MegaTron will display the BlueTrack reading in a 0-99.99% range, so the default units are set as “%”. NUMBER - Set the number range. Since the BlueTrack range will be 0-99.99%, the number format should be expressed as XX.XX. B. Configure Provides access to menus to set-up passwords, relay activation, temp scale, display contrast, flow switch, inputs, history time stamps, factory set-up and system information. User will need to go here to configure a relay to be activated by the 0-5 VDC input in the Relays sub menu of Configure. CONFIGURE RELAYS - This menu lets you choose a Main Action or function (timer 1, conductivity, alarms etc...) to activate a relay. >RELAY 1 SETUP< MAIN ACTION DISABLE 1 ACTIVATOR 2 DISABLE 2 ACTIVATOR 3 DISABLE 3 ACTIVATOR 4 DISABLE 4 DAILY MAX A pop-up screen appears with a list of all available activation functions to arrow through and the 0-5 VDC input will need to be selected as the main activator. The MAIN ACTION setting should be assigned to MA IN1 (or 0-5 VDC IN1 depending on firmware version) using the up and down arrow keys followed by the ENTER key. This tells the MegaTron that the relay will be activated by the BlueTrack sensor (0-5 VDC input). In the same way, ACTIVATOR 2-4 can be used to activate the same relay for advanced control schemes. Likewise, DISABLE 1-4 can be used to deactivate the BlueTrace relay output based on up to four different user-defined events (e.g., no flow, oxidizer feed, etc.). DAILY MAX ensures that the BlueTrack relay does not activate for more than XX hours in a single 24-hour day (beginning & ending at midnight). Note: A no flow disabler should be set if the sytem has a flow switch and you do not want to feed BlueTrack during a no flow condition. A disabler during biocide feed may also be desired. C. Set Points The setpoints menu is used to program the BlueTrack readings at which the corresponding relay output will be activated and deactivated along with any applicable alarm limits. SETPOINT - BlueTrack reading (00.00-99.99%) at which the relay output will activate. The setpoint should be set as a FALLING setpoint as indicated in the pop-up programming box. If it displays RISING, press the right arrow key to change. Next, use the number keys to enter the appropriate setpoint >0-5 INPUT 1 SETPOINT< SET POINT DIFFERENTIAL HIGH ALARM LOW ALARM LIMIT TIME DIFFERENTIAL (or deadband) - Increase in the BlueTrack reading above the setpoint that must occur before the relay output deactivates. For example, to maintain a BlueTrack control range of 15.00 to 15.50, set the setpoint at 15.00 and the differential at 00.50. HIGH ALARM and LOW ALARM - Independently adjustable settings for high and low alarm to provide an alert with the BlueTrack reading is above or below these boundaries. These alarms have no effect on the relay output unless they have been programmed as relay disablers. LIMIT TIME - Prevents the accidental over-feed of BlueTrace product by limiting the relay run time during a particular relay activation cycle. This setting is adjustable in hours & minutes (HH:MM). The limit time alarm will disable the relay output until the BlueTrack setpoint is satisfied, or until the limit timer is changed to a new value. For this reason, the limit timer should be programmed for a value that is significantly longer than the expected normal run time for the control relay to prevent premature deactivation. DO NOT SET THE LIMIT TIME TO A VALUE OF 00.00 OR ELSE THE RELAY WILL NOT ACTIVATE. D. 0-5 VDC Input Calibration The MegaTron’s CALIBRATION menu allows you to calibrate the 0VDC and 5VDC span points and program the corresponding BlueTrack readings for these upper and lower limits. THIS MENU IS ONLY USED TO SET THE FULL SCALE 0VDC AND 5VDC LEVELS AND SHOULD NOT BE USED TO CALIBRATE THE BLUETRACK SENSOR. 0-5 VDC inputs can be calibrated to insure that the input seen by the controller from the external device match. It also allows for setting the 0-5 VDC input into a number range that relates to the value being read. >CURRENT LOOP CALIBRATION< Select the Input to be calibrated INPUT 1 INPUT 2 >INPUT 1 CALIBRATION< 5VDC14500 0VDC 2900 MAX 200 MIN 0 >0-5 INPUT 1 CALIBRATION< INPUT 1 5VDC CAL 14500 A/D PUT 5VDC ON INPUT THEN PRESS ENTER 5VDC - Allows you to calibrate the 5VDC input level. This input is already calibrated at the factory, but if it ever needs to be recalibrated, a voltage simulator must be connected to circuit ground and the +VDC input on the 0-5 VDC card. Once the simulator is in place, adjust the simulator to generate a +5VDC signal. DO NOT ACCESS THIS MENU UNLESS DIRECTED TO DO SO BY TECHNICAL SUPPORT. 0VDC - Just like the 5VDC menu, except this setting allows you to adjust the 0VDC input level. The same calibration procedure can be followed, except using a simulated 0VDC signal to calibrate the input. DO NOT MAKE ANY ADJUSTMENTS TO THIS SETTING UNLESS DIRECTED TO DO SO BY TECHNICAL SUPPORT. MAX - Assigns the BlueTrack reading that corresponds to a 5VDC input. Recall from the overview that there is an inverse relationship between the BlueTrace reading and the BlueTrack sensor voltage output. Therefore, the MAX reading should be entered as 00.00. MIN - Sets the BlueTrack reading that corresponds to the 0VDC input. On a 0-100% scale, this should be programmed as 99.99. If calibration of the sensor is required, there is a calibration pot labeled R6 on the circuit board located behind the protective rubber cover on the sensor. To calibrate the sensor, simply adjust this calibration pot up or down so that the MegaTron’s BlueTrack display on the run screen corresponds to the desired percentage value. Sample Board Remember, the MegaTron is actually reading “100 - % transmittance”, so use the chart shown in the overview section to calibrate the MegaTron’s reading to match the corresponding absorbance value. For example, if a hand held test reveals absorbance of 0.10 (79% transmission), calibrate the sensor so that the display reads 21% (100-79). III. Troubleshooting BlueTrack controller not reacting to changes in chemical (dye) levels Before you try to check the DC voltage output with a voltmeter, make sure the following settings are correct: 1. CUSTOMIZE 0-5 IN NUMBER XX.XX (make sure number format is expressed as XX.XX – if not, use up or down arrows to change) 2. CALIBRATION 0-5VDC IN INPUT 1 MAX 00.00 3. CALIBRATION 0-5VDC IN INPUT 1 MIN 99.99 4. SETPOINTS 0-5VDC INPUT 1 SETPOINT make sure setpoint direction is set to FALLING (relay will activate as reading falls below the setpoint) If the problem persists after ensuring the settings are correct, disconnect the white and black wires from the 0-5VDC input card in the MegaTron SS (see page 3 in the attached manual) and check the DC voltage output with a voltmeter (white = positive, black = negative). The DC voltage should be between 0 and 5 VDC. Next, rotate the sensor calibration pot to increase or decrease the DC voltage output. The calibration pot is located on the sensor circuit board behind the grey rubber cover on the sensor housing (labeled R6 as shown on page 7 of the attached manual). If the voltage doesn’t change at all after rotating the pot a few turns in either direction, the sensor is faulty and needs to be replaced. If you do get a change in voltage while rotating the calibration pot, it’s possible that the sensor was far out of calibration and just needed to be brought back into range. To verify, reconnect the sensor wires and calibrate the sensor to the desired reading per the table on page 2 in the attached manual. It’s also possible that the 0-5VDC input card is bad if you can measure a voltage change from the sensor, but see no change on the MegaTron SS display when the wires are connected. Get the Advantage in Water Treatment Equipment Advantage Controls can give you the Advantage in products, knowledge and support on all of your water treatment equipment needs. Cooling Tower Controllers Boiler Blow Down Controllers Blow Down Valve Packages Solenoid Valves Water Meters Chemical Metering Pumps Corrosion Coupon Racks Chemical Solution Tanks Solid Feed Systems Feed Timers Filter Equipment Glycol Feed Systems Pre Fabricated Systems Get the Advantage
Similar documents
Data Sheet Blue Track - Water Control Services
dye in the recirculating stream. This level can be correlated to the level of treatment present in the system.
More information