Planning information Amacan® submersible pumps in
Transcription
Planning information Amacan® submersible pumps in
KSB Know-how, Volume 6 Planning information Amacan® submersible pumps in discharge tubes Contents Introduction 1. The Amacan series 1.1 Impeller types and performance ranges 1.2 Calculation of operating points 1.3 Pump drive with frequency inverter 2. Pump station design 2.1 General 2.2 Pump installation planning 2.2.1 Open intake chambers 2.2.2 Open intake chambers with suction umbrella 2.2.3 Covered intake chambers 2.2.4 Details of intake chamber design 2.2.5 Examples of pump station planning 2.2.6 Amacan K: A special case 2.3 Pump sump design 2.4 Solutions for special cases 2.5 The necessity of model testing 2.6 The significance of CFD simulation 2.7 Screening equipment 3. Discharge tube design 3.1 Design variants 3.2 Details on discharge tube design 3.3 Cable connections 4. List of references and photos 1 2 Introduction In the fields of water and waste More and more operators are water technology, submersible being won over by these advan- pumps represent a viable eco- tages – KSB’s Amacan pumps nomic and technical alternative work in irrigation and drainage to conventional, dry-installed pumping systems, waterworks, pumps. In particular, they offer sewage treatment plants, power a number of handling advan- stations, industrial water supply, tages during maintenance and water pollution and flood control. installation work, a factor of They handle raw and clean water increasing importance in times (groundwater, storm water, river of general staff cutbacks by water) as well as waste water and operating companies. activated sludge. In the special case of submers- With discharge tube pumps the ible motor pumps in discharge construction and design of the tubes, there are significant periphery – the pump station as design advantages to be consid- a whole – are crucial in ensuring ered. For example, though they economical and reliable oper- have the same hydraulic capacity ation, more so than is the case as tubular casing pumps, sub- with other pumps. mersible motor pumps are a good deal more compact in dimension In addition to the selection of (no long shaft assemblies, no pump hydraulics, the structural additional bearing locations in requirements will also be exam- the discharge tube). This means ined in close detail in the follow- additional buildings to accom- ing pages, along with the plan- modate the electric motor are ning of the pump installation not required, as the submersible and the design of the pump sump. pump and integral motor are Finally, this brochure will con- installed in the discharge tube. sider relevant aspects of electrical equipment. The “Amacan ® Submersible Pumps in Discharge Tubes” brochure is primarily aimed at pump station designers and operators in the water and waste water engineering sectors. 3 1 1. The Amacan series 1.1 Impeller types and performance ranges of fluids – from grey water, size for the pumping task in ques- which is reasonably clean, right tion. When making a selection, it up to waste water or activated is not only important to be aware sludge. Selecting the right im- of which impeller type is the right Wherever higher flow rates have peller type for a particular ap- match for the pumped fluid, in to be handled, submersible pumps plication will depend upon the some cases additional requirements in discharge tube design have nature of the pumped fluid and in the design of the pump station proved their worth in a wide the pumping task. The following and the choice of the technical range of applications. These sub- selection charts provide infor- equipment must be observed for mersible motor pumps can be mation on the performance of certain impeller types. optionally fitted with three dif- the different impeller types and ferent impeller types enabling help designers to choose the them to deal with a wide variety right Amacan pump type and Channel impeller Mixed flow impeller Propeller Amacan K Amacan S Amacan P Fig. 1.1-a: Available impeller types for Amacan pumps 4 Fluids pumped Notes and Recommendations Waste water - Check the free passage through the impeller - Pre - cleaned via a sreen or weir River water - Pre - cleaned via sreen or shingle trap Storm water / waste water - Check the free passage through the impeller - Pre - cleaned via a sreen or weir - With a propeller a special casing wear ring may be necessary Activated sludge - Max. 1% dry solids content Seawater - Check possible material combinations or fit anodes with six-monthly check- ups 1.1 Impeller types and performance ranges H [m] ft 20 A4 1200-870 10 pol B4 600-350 4 pol B4 700-470 6 pol B4 1000-700 8 pol B4 1200-870 10 pol 50 B4 1500-1060 12 pol 40 B4 800-540 6 pol 10 A4 800-540 6 pol A4 600-350 4 pol 5 A4 500-270 4 pol 4 A4 1000-700 10 pol A4 700-470 8 pol G3 2100-1480 A4 1200-870 12 pol 10 A4 500-270 6 pol 2 30 A4 1500-1060 14 pol 20 A4 800-540 8 pol A4 600-350 6 pol 3 A4 700-470 6 pol A4 1500-1060 12 pol A4 1000-700 8 pol G3 2100-1480 5 4 1 200 300 400 100 500 1000 200 300 2 000 400 500 3 000 4 000 5 000 1000 10 000 2 000 20 000 3 000 4 000 5 000 30 000 40 000 50 000 Q [m 3 /h] 10 000 Q [l/s] Fig. 1.1-b: Selection chart Amacan P pumps (50 Hz) Fig. 1.1-c: Amacan P 5 1.1 Impeller types and performance ranges H [m] 60 Engineered Engineered programme 50 40 -620 n=960 min -1 30 20 10 -405 n=1450 min -1 -404 n=1450 min -1 -364 n=1450 min -1 -505 n=960 min -1 -365 n=1450 min -1 -600 n=960 min -1 -550 n=960 min -1 -550 n=725 min -1 -535 n=960 min -1 -615 n=960 min -1 -820 n=580 min -1 5 4 - 655 n = 725 min - 1 3 2 1.5 200 700 300 400 1000 500 2000 1000 1200 3000 1600 2000 4000 5000 Fig. 1.1-d: Selection chart Amacan S (50 Hz) Fig. 1.1-e: Amacan S 6 3000 10000 4000 5000 20000 8000 Q [l/s] 30000 Q [m 3 /h] 1.1 Impeller types and performance ranges H [m] ft 40 100 30 20 K1000 - 500 6p 50 40 K800 - 370 6p 10 K700 - 330 4p K1000 - 420 6p K1200-630 6p 30 K700 - 371 6p K800 - 400 6p K700 - 330 6p K700 - 324 6p 5 4 20 K1000 - 421 6p K1200 - 630 8p K700 - 371 8p 3 10 K700 - 324 8p K1200-630 10p 2 K800 - 400 8p 5 4 1 100 30 200 40 50 300 400 100 500 1000 200 300 2000 400 500 3000 4000 5000 6000 1000 Q [m 3 /h] Q [l/s] Fig. 1.1-f: Selection chart Amacan K (50 Hz) Fig. 1.1-g: Amacan K 7 1.1 Impeller types and performance ranges The design configuration of installation. In addition, build- on the on-site installation depth. modern submersible motor ings to accommodate electric This lifting equipment represents pumps installed in discharge motors or ventilation equipment a major investment even though tubes has a number of advan- are not required. The drive is it is only periodically used for re- tages over that of conventional an integral part of the submers- pair work or pump installation / tubular casing pumps. For ex- ible pump and hence is contained removal. In contrast, to carry ample, although these pumps in the discharge tube. out the same tasks the Amacan submersible motor pumps only have the same hydraulic capacity (impeller) they are consid- For assembly and maintenance require mobile cranes, which are erably more compactly dimen- work on conventional pumps it far more cost effective. In order sioned (no long shaft assem- is generally common practice to to fully exploit this advantage, blies, no additional bearing install large lifting equipment, appropriate access must be fac- locations in the discharge tube). the size of which will depend tored in at the planning stage. The handling of a submersible pump is significantly more straightforward, simplifying in particular maintenance and Fig. 1.1-i: Installation of submersible motor pump with a mobile crane Fig. 1.1-h: Conventional tubular casing pump 8 Fig. 1.1-j: Pump station with building 1.2 Calculation of operating points 1.2 Calculation of operating points As propeller pumps in particular in low-lift pump stations. often generate only a low head, During pump selection, these the loss of head at the pipe out- maximum water levels should let (a check valve is often in- not lead to unacceptably low or With Amacan pumps, the stalled!) must be considered in high discharge heads, as this manometric head required for the calculation. When establish- would mean the pump is oper- a certain flow rate will be cal- ing the static head component, ating to the left of Qmin or to culated using the same approach the maximum differences be- the right of Qmax . as with any centrifugal pump. tween the suction and discharge side liquid levels of the pump The documented pump charac- station are of interest, especially teristic curves already include the internal losses between the impeller inlet and 0.5 m behind tube losses before and after these points and head losses through flow deflection, fittings (valves etc.) and the outlet are Head H total the motor. Inlet and discharge System curve HA Dynamic component = H dyn to be taken into account as the Static component = H stat dynamic head component. The system curve is composed Q req Flow rate Q of the static head component (difference in water levels) and Fig. 1.2-a: Example of a system curve [H = f(Q)] the dynamic head component (friction loss in the pipes and m 11 10 fittings): ft Q min 8 20 6 H tot = H stat+ H dyn H stat max H stat min 4 17˚ 2 0 v2 v2 L H dyn = ∑ λi x i x i + ∑ ξi x i 2g 2g di i=n i=n i =1 i =1 0 0 1000 2000 3000 4000 5000 6000 m 3 /h Fig. 1.2-b: Ilustration of possible water levels i indicates the considered section of the pipe with the pipe length Li , the pipe diameter d i and the friction loss coefficient ξ i as well as the flow velocity v i in the pipe section. 9 1.2 Calculation of operating points If some loss coefficients ξ i are In addition to the fluid level unknown when calculating the above the impeller (dependent dynamic head component, then on size) and the water level the literature given at the end of limit to prevent air-entraining the brochure may be of assist- vortices (dependent on flow ance (e. g. Selecting Centri- rate) – both are illustrated in fugal Pumps [1]). Fig. 1.2-c – the NSPH value of the pump at the operating point When selecting pumps installed is of importance for the required in discharge tubes particular water level t1. The condition to attention must be paid to the be fulfilled is as follows: difference in water levels, as the minimum water level Wlmin in NPSHavailable > NPSH required+ 1.0 m safety allowance the structure must not be lowered below the water level t1 required If this condition is not fulfilled, for the volume flow rate of the the value for t1 must be increased pump; this is the only way to by the value of the difference avoid surface vortices. The necessary depth tps of the pump tps = wl min – t1 station building can also be calculated using this water level. The minimum water level is a function of the volume flow rate wl min 1 2 3 4 5 6 7 required of the pump [t1 = f(Q)] and also of the intake chamber design (see sections 2.2.1 to Amacan P ... 500- 270 Amacan P ... 600- 350 Amacan P ... 700- 470 Amacan P ... 800- 540 Amacan P ... 1000- 700 Amacan P ... 1200- 870 Amacan P ... 1500-1060 t1 t ps Note: Compare t 1 tables in the type series booklets for the appropriate pump size, installation variant and volume flow rate. 2.2.3). t 1 [mm] 4000 7 6 3000 5 2500 4 2000 3 2 1600 1 1200 1000 800 600 500 400 0.1 0.2 0.3 0.4 0.6 0.8 1 1.5 2 2.5 3 4 5 6 8 Q [m 3 /s] Fig. 1.2-c: Calculation of the minimum water level t1 for Amacan P (for Amacan K and Amacan S refer to the appropriate type series booklet) 10 1.2 Calculation of operating points h V Kr [m] 1.0 20 0 0.8 0.6 25 0 0.5 110 0 120 0 130 0 14 0 150 0 16 0 0 0 900 10 0 0 800 70 0 600 50 0 400 2 0.2 DN –.–.–.– =3 50 30 0 0.3 DN 2 –.–.–.–.–.–.–.–.– 0.4 0.10 0.08 0.06 0.04 0.02 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 4 5 6 Q [m 3 /s] Fig. 1.2-d: Determining the pressure loss in a discharge elbow outlet Should the discharge tube be If there is no other data available, open at the top (free overflow then the overflow head h overfl from the tube, for instance) can be taken from the following then the overflow head h overfl diagram. must be taken into account when calculating the total pump head H tot. h ü [m] 2 D out h overfl 7° 1 Q D The overflow head h overfl depends on Q and the outlet diameter D out . The chart values are only applicable if the fluid overflow is undisturbed to all sides, (i.e. there are no obstructions) otherwise they can only be considered as approximate values. 0.8 0.6 0.5 0.4 0.3 DA =4 0.2 00 mm 60 0 0 00 10 0 0 12 0 0 00 14 0 0 18 0 0 00 2 20 16 2 80 0.1 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 4 5 6 Q [m 3 /s] Fig. 1.2-e: Establishing the overfl ow head hoverfl 11 1.2 Calculation of operating points After the system curve has been determined, this should always be plotted together with the pump characteristic curve in order to check the operating points (curve intersections). In this way, the designer can ensure that no operating conditions outside the permissible section of the characteristic curve arise. Fig. 1.2-f: Selection principle for Amacan pumps according to the type series booklet 12 1.3 Pump drive with frequency inverter 1.3 Pump drive with frequency inverter (a) the flow velocity in the dis- operate at the same speed. This charge tube must be adequate is to avoid the pumps blocking to assure the pumping of fibres each other in the low-flow and solids that might have to be operating range (with the nega- Basically all pump motors can handled (vmean > 2 m/s), and tive effects on impeller, shaft be used with frequency invert- (b) the circumferential speed on seal and bearings this can have). ers. The characteristic curves of the impeller’s outside diameter Amacan pumps installed in (not less than 15 m/s). When If checking the minimum flow discharge tubes can be calculated speed is changed, and taking velocity poses problems, under using the affinity laws, as is into account variable water some circumstances (depending also the case with centrifugal levels, it is vital that no operat- on the fluid pumped) it is pumps. ing point lies to the left of the possible to work with slightly permissible operating limit. reduced values. To ensure the This means: The limit speeds pumps are not clogged, an must be matched to comply automatic control can increase with the actual water levels. the speed for a short period and Q2 n2 = Q1 n1 () n H2 = 2 n1 H1 2 () n P2 = 2 n1 P1 3 n1 Original speed n 2 New or proposed speed at set time intervals to activate If two or more pumps with a flushing. After this procedure In principle, the aim of speed common discharge pipe are run the pumps’ speed can be control is to optimally match via frequency inverters, it is re- lowered, automatically again, to the pump’s operating point to commended that all pumps the original level. the actual system requirements. As mentioned above, three impeller types with different characteristics are available for this submersible motor pump ft m 11 Q min 10 8 type in discharge tube design. 20 6 For each of these impeller types 4 it is always important to check the control range. This includes establishing the system curve(s) with H stat,min and H stat,max. 2 n = 591 0 0 1000 2000 3000 4000 n = 690 n = 788 n = 985 0 5000 6000 m /h 3 The following must also be checked: n = 887 Fig 1.3-a: Amacan P 800 - 540 A 4 with speed curves 13 2.1 Pump station design 2. Pump station design 2.1 General pump(s) as well as the specifi- According to Prosser [6], the cation for the minimum spacing criteria for unsatisfactory pump between the pumps or, in some station design can be clearly The structural requirements of cases, the dimensions to be ob- defined and assessed. Poorly a pump station are largely deter- served for any necessary intake performing pump sumps can mined by how it is to be used. chambers. arise from the following: mechanical requirements, con- If the requirements regarding 1. Undersized control gates sideration must also be given to intake chamber dimensions, hydraulic (fluid dynamics) minimum water levels or the aspects in the planning and geometry of hydraulic areas execution of the construction within the pump station are not work. The first part of the met, i. e. deviations occur dur- flow areas (e.g. diffusers hydraulic areas to be designed ing the planning or construction with too large an angle of is the inlet upstream of the phase, proper functioning of divergence) pump station, followed by the the entire station can no longer 4. Steep slope intake chamber upstream of the be guaranteed. In such a case, it 5. Weirs with no provision for pump(s), parts of which may is irrelevant whether these prob- dissipating the energy of the require a special shape, and lems are caused by single or falling fluid finally the discharge pipe or multiple deviations. discharge system. The conditions for pump oper- Alongside purely structural and ation are not met due to these and valves 2. Abrupt changes in flow direction (e.g. sharp corners) 3. Submerged high velocity 6. Blunt pillars, piers and guide vanes 7. Any design, or mode of op- The pump manufacturer’s aim modifications or deviations and eration, which leads to is to specify in the product’s the problems arising as a result asymmetric distribution of technical documentation the are reflected in either the cen- the flow into the sump dimensions (e.g. geometry of trifugal pump’s operating be- 8. Inlet to the sump above the the building) required for the haviour or its performance. If installation of the centrifugal the pump manufacturer’s speci- pumps. The reference values fications on the hydraulic and Items 1, 2, 3, 6 and 7 may cause provided here are essential for mechanical design aspects of swirls at the pump’s inlet. Air- the planning process, in par- the pump station are taken into entraining surface and sub- ticular for establishing the main account in the overall layout merged vortices may form in dimensions of the pump station. early enough, malfunctions extreme cases. The successful planning of a such as not achieving the re- Items 4, 5 and 8 can produce pump station is a complex task quired performance data and aeration while items 3, 4 and 5 which encompasses questions operating troubles can be elim- may cause unsteady flow on how to design the area inated. conditions within the sump. between the intake and the 14 water level. 2.1 Pump station design The purpose of a pump sump is to provide liquid storage and good flow conditions to the pump; therefore, it is important to avoid the following undesirable hydraulic conditions: 1. Jets, or high-velocity flows, discharging into stagnant or slowly moving fluids (as these form large, unsteady eddies as downstream wakes) 2. Areas of separated flow 3. High-velocity flows Fig. 2.1-a: Vortices developing as a result of unacceptable approach flows into the chamber – jet directly impinging on discharge tube (v > 2 m/s) 4. Unsteady flow 5. Large surface waves 6. Free-falling fluids. Observing the above criteria at the planning and construction phase is an important step towards creating a smoothly functioning pump station. KSB’s intake chamber geometries compare favourably with those specified by other pump manufacturers and internationally recognised research institutions in their literature. The intake chamber geometries suggested by KSB in their type series booklets and software tools allow smaller pump stations to be built and therefore lower building costs. 15 2.2 Pump installation planning 2.2 Pump installation planning After all hydraulic aspects regarding the distribution of the volume flow have been consid- Fig. 2.2-a: Variants of discharge tube design with free discharge ered and the appropriate pump size chosen, the geometry of the intake chamber must be determined. Thanks to a flexible discharge tube design, Amacan pumps offer a vast range of installation options, making optimum pump station design possible. This gives system designers the flexibility to adapt the installation Fig. 2.2-b: Variants of discharge tube design with above-floor discharge nozzle to any station design and system condition. Some installation options are briefly presented here. Fig. 2.2-c: Variants of discharge tube design with underfloor discharge nozzle 16 Fig. 2.2-d: Discharge tube design variant with underfloor discharge nozzle, top floor suitable for vehicles 2.2 Pump installation planning The primary source of advice When determining the appro- Whether the pump station is on planning should be the pump priate intake chamber geom- equipped with one or several manfacturers’ documentation etry, the pump station designer pumps has no influence on the and internationally recognised must also consider any operat- intake chamber dimensions or standards (cf. References). ing conditions which will occur the discharge tube. when the pump station is being Once the pump station’s dimen- operated with a reduced num- sions have been roughly defined, ber of pumps. This may result detailed planning of the installa- in substantially different intake tion of the pump should be chamber flow conditions in carried out in close consultation terms of inflow velocity and in- with the manufacturers’ tech- flow direction (see section 2.3). nical literature (e.g. type series booklet or selection software), where detailed information on the exact dimensions required v b for each particular pump size can be found. It is vital that e1 Distance between pump and rear wall l these dimensions be observed to ensure problem-free pump b Approach channel width l Length of approach channel with uniform, straightened flow, where changes in flow direction do not occur v Mean flow velocity in approach channel operation. Information on permissible maximum inflow velocities and the direction of inflow for the Q Volume flow rate t1 t3 specific intake chamber geometries is also provided (see section 2.3). The dimensions essential for the intake chamber are its width and length as well as the distances between rear wall / floor and pump. The minimum water level has to be established on the basis of the pump’s volume flow in order to ensure smooth pump operation without air- t1 Minimum submergence t 3 Distance between floor and pump e1 Fig. 2.2-e: Important intake chamber data (for actual dimensions refer to the type series booklet or selection e1 Wandabstand zw. Pumpe und hinterer Schachtwand software) B Breite des Zulaufkanals L Länge des Zulaufkanals mit gleichförmiger gerichteter Strömung, wo keine Richtungswechsel stattfinden V mittlere Strömungsgeschwindigkeit im Zulaufkanal Q Volumenstrom t1 Mindestüberdeckung t3 Bodenabstand entraining surface vortices. 17 2.2 Pump installation planning 2.2.1 Open intake chambers If the water level in the pump sump is sufficiently high and the flow approaches the chamber directly from the front, Vent pipe with a tolerance of 10 degrees maximum, then this form of intake chamber design is the most cost-efficient variant. The flow velocity must not Minimum water level exceed 1 m/s within the intake chamber. Flow approaching the 10 degrees must be ruled out to t1 pump at an angle of more than t3 avoid flow separation and vortex formation. This also applies in the event of altered operating conditions. d8 b1 Flowstraightening vane b Inflow b1 e1 0 -10˚ Vmax = 1 m/s l Fig. 2.2.1-a: Open intake chamber without suction umbrella (see the type series booklet for the actual dimensions) 18 2.2 Pump installation planning 2.2.2 Open intake chambers with suction umbrella If a check of the minimum water level in the pump sump establishes that this is insuffi- Vent pipe cient, another chamber variant that provides sufficient submergence to prevent airentraining vortice should be chosen. One such option, involving a few changes, is the Minimum water level open intake chamber with a suction umbrella. This allows suction side minimum water t1 the pump to operate at a lower t3 level t1 with the same pump size and the same operating point. d8 d9 e1 Flowstraightening vane b Inflow 0-10˚ Vmax = 1 m/s l Bild 2.2.2-a: Open intake chamber with suction umbrella (see the type series booklet for the actual dimensions) 19 2.2 Pump installation planning 2.2.3 Covered intake chamber A special type of chamber is the covered intake chamber. It allows the lowest minimum water levels Vent pipe without the occurrence of airentraining surface vortices and can accommodate flows approaching at an angle of 0 to 90 degrees at 1 m/s max. However, this variant involves higher construction costs than Minimum water level the chamber types previously described. This type of chamber under unfavourable approach 45˚ t3 has more than proved its worth flow conditions and low water levels. d e2 b2 b Inflow b1 Flowstraightening vane 0-90˚ Vmax = 1 m/s l e1 Fig. 2.2.3-a: Covered intake chamber (see type series booklet or selection software for the actual dimensions) 20 2.2 Pump installation planning 2.2.4 Details of intake chamber design Mounting a flow-straightening vane under the pump inlet is important in all intake chamber designs for Amacan P and Unlike pumps from the Amacan Amacan S pumps as this device K series, Amacan P and Amacan prevents the occurrence of a S pumps have to be installed in submerged vortex which may dedicated compartments in the cause a drop in performance, intake chamber. An important among other things. This vane criterion for the chamber walls can either be a concrete or steel is a minimum height of 150 mm construction. above the maximum water level The precise vane dimensions in the pump sump. This is to are stipulated in the type series ensure that the shape of the booklet or selection software. chamber does not favour vortex formation even under maximum water level conditions. approx. 150 mm Cast flow-straightening vane Steel profile b2 H max b1 b1 H min hR hR Screwed to intake chamber floor Fig. 2.2.4 -a: Chamber wall height The walls in the intake section of the chamber should always Flow-straightening vane concentric to the pump centreline be rounded to rule out the pos- Discharge tube sibility of additional vortices forming if the flow to the chamber is skewed. This requirement is vital for both single-pump intake chambers with approach flows from the side and multiple- IR IR ≈ 2 x D h R = 0,4...0,6 x t 3 IR Fig. 2.2.4 -c: Sizing the flow-straightening vane pump chambers with central inlet flows. W 1 R≈ – W 2 Fig. 2.2.4 -b: Chamber intake design 21 2.2 Pump installation planning Experience gained over the past For this purpose, mounting The intake chamber surfaces as few years has shown that the devices for stop logs can be well as the wall around the costs for concrete formwork in integrated into the chamber wall pump sump should have rough the chambers can be reduced by or the chamber can be shut off concrete surfaces. If the areas in using straight contours. Concrete by appropriate flood gates. If contact with the pumped fluid fillings are, however, needed in these mounting devices are too smooth or even provided areas where dead water zones constrict the free flow cross with a paint coat, this may lead could occur. The intake chamber section, the distance be-tween to the reduction of the wall corners must then be filled with the pump and this point of flow shearing stress – and thus in- concrete up to a minimum height disturbance must be checked crease the risk of vortex forma- of 150 mm above the maximum and increased where necessary. tion (submerged vortices, and water level. possibly surface vortices). The Depending on the pump station roughness of surfaces in contact concept, the designers may allow with the fluid should range from for the possibility of shutting off 1 to 3 mm. and draining individual intake chambers, if required. b2 D e1 AK AR b1 v LS b Flow Straightening vane Ls = D x f 1.0 l AR AK f 0.5 Flow straighteners are required (consult KSB) Fig. 2.2.4 -e: Corner fillets 0 5 f [%] 10 Fig. 2.2.4 -f: Influence of cross-sectional constriction 22 2.2 Pump installation planning In some circumstances, it might These special options must be be necessary to adapt the intake sized to precisely match the structure to the specific require- project data, which should, ments of a project. It is conceiv- therefore, only be done after able, for instance, that an intake consultation with the respon- elbow might be employed in sible KSB Competence Center. place of a chamber. These elbows have properties comparable If special solutions are unavoid- with those of covered intake able for certain projects, these chambers, i.e. they straighten should be examined with ap- the flow and ensure an even propriate model tests and/or distribution of flow velocity CFD (Computational Fluid across the inlet cross section of Dynamics) simulations. As this the pump. means they are not standard Fig. 2.2.4 -i: Variant of a double elbow in a model test solutions (see sections 2.5 and 2.6) it is important to obtain prior assurance of the troublefree functioning of the system under these specific project conditions. l2 l2 LW r3 α2 r2 c2 d2 c1 α1 c1 a1 a1 L 5 d2 d1 r1 α1 d1 l3 1 b2 b1 2 b3 b4 b5 l4 α1 4 3 b6 b7 b8 b8 b 10 Fig. 2.2.4 -h: Variant of a segmental bend 23 2.2 Pump installation planning 2.2.5 Examples of pump station planning Variant 1 Variant 2 Given: Solution: Given: Using three pumps, the pump Each pump is to be provided The pump station consisting of station is to pump fluid from a with an intake chamber sized to three pumps is to convey fluid channel. The inflow to the match the respective pump (see from a pump sump which is fed pumps is described as being the type series booklet or selec- with fluid from an off-centre, even across the channel width. tion software). This ensures front pipe / channel. In addition, defined approach flow condi- the pumps are installed asym- tions and rules out any possi- metrically with regard to the bility of the pumps influencing inflow; intake chambers have each other during pumping. not been provided. v̄ v̄ Problem: As the distance between the discharge tubes and the rear wall is too big, vortices may develop behind the discharge tubes as a result of separated Problem: flow. The absence of intake The off-centre inflow into the chambers creates the risk of the pump sump causes an anti- pumps influencing each other clockwise rotation of the fluid and of undefined approach flow in the pump sump. The velocity conditions in the case of single in the inflow channel / pipe pump operation. determines the intensity of this rotation and, as a consequence, e1 L min that of the uneven approach flow. b v̄k < – 1 m/s e1 l min v̄ b min 5 x D >1.3xDi v̄k < – 1 m/s 24 Di 2.2 Pump installation planning Variant 3 Solution: Given: Solution: Each pump is to be provided The pump station consisting of A curtain wall with an opening with a complete intake chamber three pumps is to operate from towards the floor is installed sized to match the respective a pump sump which is fed with upstream of the intake chambers. pump (see the type series water from an off-centre, front This prevents rotation and booklet or selection software). pipe/channel. In addition, the ensures the intake chambers are This will rule out any possibil- pumps are installed asymmet- approached from the front ity of the pumps influencing rically with regard to the in- without pre-swirl occurring. each other during pumping. flow; intake chambers have not A curtain wall with an opening been provided. towards the floor is to be installed to ensure a uniform v̄ approach flow. This will help prevent the fluid from rotating. Problem: The off-centre inflow into the pump sump causes an anticlockwise rotation of the fluid in the pump sump. The velocity in the inflow channel / pipe determines the intensity of this rotation and, as a consequence, that of the uneven approach flow. e1 l min v̄ b Di min 5 x D >1.3xDi v̄k < – 1 m/s 25 2.2 Pump installation planning Variant 4.2 Variant 4.1 Given: Solution: Given: Using three pumps, the pump Each pump is provided with a Three pumps are installed to station is to pump fluid from a complete intake chamber sized pump fluid from one pump channel. The flow from the to match the respective pump sump. The flow approaches the channel approaches the pumps (see type series booklet or selec- sump in the centre. The pumps laterally. The pumps are separ- tion software). The intake are installed perpendicular to ated from each other through chambers should be installed on the flow direction and do not free standing baffles. the sump wall opposite the have intake chambers. inflow. A curtain wall should To reduce the velocity in the be installed across the entire sump the inlet channel has been width of the pump sump up- widened. Relative to the inflow, stream of the intake chambers. the distance between the pumps This prevents the pumps from and the rear wall is extremely influencing each other during large. v̄ the pumping process; the approach flow is even. Problem: The flow moving from the e1 l min α > 15˚ v̄ b channel into the sump is symmetrical with respect to the min 5 x D installation set-up of the pumps. v̄k < – 1 m/s Vortices may, however, form as v̄ Di >1.3xDi a result of flow separation; this Problem: leads to the risk of uneven Due to the fluid approach from velocity distribution among the the channel to the sump, vortices pumps. The absence of any in- caused by flow separation are take chambers means an un- likely, leading ultimately to the defined approach flow, with the risk of uneven velocity distribu- accompanying risk of the pumps tion upstream of the pumps. influencing each other. The angle of divergence is too wide and causes problems with vortices and velocity distribution as mentioned above. As intake chambers are not available, there is the risk of the pumps influencing each other and of undefined flow. 26 2.2 Pump installation planning Variant 5 Solution: Given: Solution: Each pump is provided with a The pump station consisting of Each pump is provided with a complete intake chamber sized three pumps is to pump fluid covered intake chamber. As a to match the respective pump from a channel. The pumps do result, perpendicular flows of (see type series booklet or selec- not have intake chambers and up to a maximum of 1 m/s can tion software). The intake the fluid flow approaches the be handled without any chambers are installed on the line of pumps perpendicularly. problems. The intake chambers are sized to match the actual sump wall opposite the inflow. pump size (see type series A curtain wall should be inv̄ stalled across the entire width booklet or selection software). of the pump sump upstream of The front edges of the intake the intake chambers. This chambers should be in line with prevents the pumps from influ- the channel wall to avoid encing each other during additional flow constrictions pumping; the flow is even. e1 Problem: and marked differences in flow The pump station consisting of velocities in the channel. three pumps is to pump fluid l min from a channel. The pumps do b not have intake chambers and α > 15˚ v̄ min 5 x D Di the fluid flow approaches the line of pumps perpendicularly. v̄k < – 1 m/s >1.3xDi v̄ < – 1 m/s 27 2.2 Pump installation planning Variant 6 Variant 7 Given: Given: Solution: The pump station consisting of The pump station consisting of Each pump is provided with a three pumps is to pump fluid three pumps is to pump fluid complete intake chamber sized from a channel. The pumps are from a channel. The flow is to match the respective pump installed in a series. The pumps described as being even across (see type series booklet / selec- are not separated from each other the entire channel width. The tion software). This will rule through chambers or baffles. pumps are separated from each out any possibility of the pumps other through profiled rear influencing each other. walls of the sump. Problem: The approach flow from the channel creates the risk of vortices caused by flow separation and uneven velocity distribution up- and downstream of the pumps. The absence of any intake chambers means an undefined approach flow, with the Problem: accompanying risk of the pumps The absence of any intake influencing each other. chambers means an undefined approach flow, with the accomv̄ < – 1 m/s panying risk of the pumps influencing each other. This results in unpredictable flow conditions particularly during operation with a reduced number of pumps. Solution: Each pump is to be provided e1 l min with a covered intake chamber sized to match the respective pump (see type series booklet or selection software). This will rule out any possibility of the pumps influencing each other, while the flow conditions are exactly defined. 28 b v̄k < – 1 m/s 2.2 Pump installation planning 2.2.6 Amacan K: A special case building structure as well as is a function of the volume flow inter-pump spacing, and the rate Q and documented in the distance e1 between the rear type series booklet. wall and the pumps’ centreline. Thanks to its channel impeller Fig. 2.2.6-a offers basic guid- ~ 1.6 to The lateral distance smin ~ this pump type is relatively ance for a pump installation 1.8 x D should be also observed. straightforward with regard to concept. the pump station design. For discharge tubes with a diam- Amacan K pumps can be in- The following conditions should eter of D = 700 a factor of 1.6 stalled into the discharge tubes be assumed as reference values and with D = 1400 a factor of with no need for any special for a preliminary concept: 1.8 must be applied. Other inter- intake chambers or separating walls between the pumps. To rule out any possibility of the mediate values must be estabObserving the rear wall ~ 0.6 x D is crucial. distance e1 ~ pumps influencing each other, lished through interpolation. Flow straighteners as used for Amacan P or Amacan S are not it is, however, important to ob- The required minimum water serve the required installation level t1 – as is also the case with distances: the lateral distance the other submersible pumps Where inflow angles differ and between the pump and the installed in discharge tubes – flow velocities are higher than required. 1 m/s, it is necessary to take e1 measures suited to deal with that specific intake situation (see section 2.3 “Pump sump design”). S1/2 min Recommended inflow 0-45˚ Vmax = 1 m/s S1 min S1 min Fig. 2.2.6 -a: Minimum dimensions 29 2.3 Pump sump design Wrong D 2.3 Pump sump design Vortex > 8˚ The fluid storage space or the pump sump connects the pump station intake with the submersible pump in the discharge tube. There are as many vari- Correct D ations in the design of this part approx. 4 to 5 D of the intake structure as there are pump installation options. Only a few examples can be max. 8˚ looked at in the following chapter; the dimensions in the drawings refer to these cases only. If project or modification Fig. 2.3-a: Shape of sump floor conditions deviate from the examples described here, we When the flow enters the pump recommend consulting KSB. station structure from a channel, either a diffuser-type enlarge- One feature of an optimum ment (number of pumps n + pump sump design is that there chamber width x n+ (n –1) x are no major steps or slopes wall thickness) or a so-called with an inclination of more curtain wall is required. Which than 8 degrees on the sump of these measures is appropriate floor. A distance of at least 4 to for the project in hand, must be 5 D (D = discharge tube diam- individually decided upon. eter) should be maintained from the last point of disturbance or floor alteration to the pump centreline. Higher steps or slopes (> 100 mm) should be v in = 1.2 m/s (max) Floor gradient 8˚ max. avoided at all costs in order to prevent submerged areas of flow 15˚ max 0.3 to 0.5 m/s max separation and floor vortices. Fig. 2.3-b: Maximum permissible divergence angle for flow cross section and permissible velocities according to HI [5] and SN [12] 30 2.3 Pump sump design While some sources give details If the direction of the flow in the direction specifically re- of installations where submers- (relative to the orientation of quired. The result is a symmet- ible pumps in discharge tube the pump intake chamber) dis- rical approach flow into the design do not have their own charged from the inlet channel pump chambers. If such a wall intake chambers, KSB, in con- changes, this must be corrected is not installed, the energy trast, believes that each pump by appropriate devices, so-called contained in the flow may cause should be provided with its “flow straighteners”. While one vortices; in addition, as shown own, fully shaped intake function of flow straighteners is in Fig. 2.3-c, the flow to the chamber (see sections “Open to dissipate the kinetic energy chambers is asymmetrical and intake chamber” to “Covered of the fluid entering the pump therefore detrimental to intake chamber”) in order to station, their opening towards trouble-free pump operation. rule out any possibility of the the floor ensures the flow moves pumps influencing each other. Actual inflow conditions are difficult to predict, as vortices may form even in the case of 1.3-1.4 x D z Dz low pump flow rates as a result of various influences in the intake structure or the pump stations’s mode of operation, 0.1 x D z 0.45 ... 0.6 x D z with the accompanying negative effects on the pumps. l min e1 D According to KSB, flow velocities of no higher than 1 m/s are b permitted for the intake chamber geometries specified in the type series booklets. Therefore, with a view to reducing the intake building structure, it is necessary that the conditions > _ 3.5 x D around the pump are optimally designed to avoid problems. > _5xD Fig. 2.3-c: Example of a pump station with cross flow and curtain wall 31 2.3 Pump sump design If the difference in height between the inlet structure and the pump sump is large it may D be necessary to eliminate the risk of aeration by incorporat- H min ing a weir-type structure. A 150 mm difference in height of more than 0.3 m [7] already provides sufficient reason to take appropriate measures. The adjacent illustration shows a pump station with a considera- D ble difference in height between Entrained air bubbles the inlet channel and the pump sump and how this problem has been solved by fitting appropriate structures in the sump. Changes in flow direction can also be expected if only a few pumps are operating in a mul- Fig. 2.3-e: Pump station with weir-type structure tiple-pump system. Here preliminary assessment of the If a divergence angle of more than situation could help to decide 15 degrees is planned in the build- whether a covered intake cham- ing to reduce inflow velocity vi , ber should be preferred to an additional steps such as the in- open one. stallation of flow distributors and/or baffles are necessary to prevent vortices caused by flow separation. The feasibility of these measures depends on the nature of the fluid pumped. Flow distributors 20 On Baffle columns On v v v On Off v < 0.5 m /s Fig. 2.3-d: Flow pattern developing with variable pump operation 32 α > 15˚ Fig. 2.3-f: Flow optimisation α > 15˚ 2.3 Pump sump design The intake situation from a If the fluid is taken from stag- channel is comparable with the nant waters, then cross flow is abstraction of water from a irrelevant. If the fluid level river. Depending on the flow above the pumps is sufficient velocity, areas of flow separa- for the respective volume flow, tion can be expected where the i. e. a minimum water level t1 water flows into the intake between the lowest water level chamber area. If it is not pos- in the water body and the in- sible to provide a covered intake take chamber floor can be chamber, then it is important to assured (see type series book- markedly extend the chamber lets), it is no problem to use walls. As a reference value the open intake chambers. pump station designer can as- Depending on the design of the sume a factor 3 relative to the pump station’s lateral walls, it dimension L min given in the may be possible to make them technical literature. slightly longer than the intake chamber wall in order to reduce the influence of flow deflection on the outside intake chambers. Fig. 2.3-g: Pump station with open chamber for water abstraction from a river Fig. 2.3-h: Pump station with open chamber for water abstraction from stagnant waters 33 2.4 Solutions for special cases 2.4 Solutions for special cases To define these special cases The extent to which such more clearly, a few criteria, like measures are to be verified by for instance the maximum vel- model tests or CFD (Compu- ocity in the approach zone of tational Fluid Dynamics) If standard intake structures v > 1m/s and the large cross simulations should be indi- cannot be realised or the con- flows potentially associated vidually determined. ditions in the pump station do with them must be mentioned. not correspond with the above In such cases precisely dimen- mentioned layouts, KSB’s sioned baffling and specially expertise should be utilised to dimensioned intake chambers find specific design solutions. could possibly help to optimise The sooner advice is sought in the approach flow to the pump. such special cases, the better – The nature of the fluid pumped and the higher the chance of is here again crucial, thus under- identifying potential problems scoring the need for an indi- and of taking appropriate vidually engineered solution. measures to find a practical KSB has numerous successful solution. designs in this field to its credit. Fig. 2.4 -a: Specially dimensioned intake chamber for cross flows of v = 1,8 m/s 34 2.5 The necessity of model testing 2.5 The necessity of model testing The object of these tests is to The dimensionless numbers REYNOLDS number Re = FROUDE number Fr = It helps identify precisely where problematic conditions (vortex station building deviates from proven layouts as regards simulate the flow of a planned pump station in a scale model. - The concept of the pump applied here are as follows: WEBER number action, uneven velocity distri- vd ν v √g.d ρ .v 2 . d We = σ bution, etc.) might arise and how to then influence these positively, where necessary. The high transparency of acrylic glass makes this material an excellent choice for the construction of suitable models. chamber dimensions, piping layout, wall spacing, considerable changes in flow direction between inflow into the building and the approach flow to the pump, etc. - The volume flow rate per where: v = flow velocity in m/s d = hydraulc diameter in m ν = kinematc viscosity in m 2 /s g = gravitational constant in m/s2 σ = surface tension in N/mm 2 pump is higher than 2.5 m3 /s or 6.3 m3 /s for the entire pump station - The inflow is asymmetrical and/or not uniform In order to be able to tranfer As these characteristics are to a - Alternating pump operation the flow conditions to the full- degree interdependent, it is im- in multiple-pump stations size structure, dimensionless possible to apply them at the involves significant changes in numbers are applied in the same time in a scaled model. flow direction design of the model. These It is therefore important to find characteristic coefficients de- a compromise which helps scribe the forces acting in the achieve the optimum for a given flow; they should be as identical application. - An existing pump station has already created problems. as possible for both the model and the full-size structure. The Model testing is absolutely ne- most relevant forces are gravity, cessary when one or more of as well as those resulting from the criteria listed below apply to dynamic viscosity, surface the intake structure or pump tension and the inertia of the sump: fluid in motion. 35 2.5 The necessity of model testing Test set-up Instead of an impeller a vorto- The surface vortices are classi- The geometry of the model meter is employed whose rota- fied according to Hecker in six must correspond with the tional speed provides information categories (1 = low, 6 = very high) original structure, taking into on the development of vortices and the submerged vortices in account the selected scale and in the intake. three or four categories according the characteristic coefficients to Tillack [16]. mentioned previously. This The flow velocities are meas- applies to the hydraulic part of ured at reference points across the building structure and the the model pump’s entire suction pumps. Both the structure of cross section via Pitot tube or the building and the pumps are laser. To judge vortex develop- constructed from transparent ment the fluid surface as well as material. A model of the the wall and floor areas are impeller is not required as the observed. Vortex intensity in a test aims to simulate only the given flow cross section is flow approaching the impeller. visualised by means of dyes while their size is measured by the swirl angle of the vortometer. The following equation is applicable: Θ = tan -1 Fig. 2.5-a: Acrylic model of an Amacan P pump station Type 1 Type 2 Type 3 Slight surface swirl Surface swirl with dimple Intense surface dimple whose core can be seen (dye) Type 4 Type 5 Type 6 Vortex dimple entraining contaminants below the water surface Vortex pulling air bubbles to the pump intake Full air core reaching to pump bellmouth Fig. 2.5-c: Classification of surface vortices according to Hecker (Types 1 to 6 ) (π°du n ) m where: d m = pipe diameter Type 1: Slight swirl at floor or wall Type 2: Vortex at floor or wall Type 3: Air-entraining vortex at floor or wall Type 4: Vortex at floor or wall with vapour core (here the pump´s suction pipe) n = rotations of vortometer u = axial flow velocity Fig. 2.5-b: Vortometer 36 Fig. 2.5-d: Classification of submerged vortices according to Tillack (Types 1 to 4 ) 2.5 The necessity of model testing If one were only to look at the Evaluation of results In general the following applies: diagrams, these vortex Before the design is finalised Occurrences that have a minor formations appear relatively the measurement results should effect in the model may be con- harmless. Vortex formation be confirmed by all parties siderably more significant in observed in model tests give an involved: pump station designer, the full-scale structure! idea of what could happen in a end user, pump manufacturer real structure. Unlike laboratory and the institution which con- The tests must be concluded situations a real pump station ducted the tests. with a detailed report on the operating conditions investi- rarely deals with clear water and it is difficult to identify Main criteria: and operating conditions ob- vortex action as the source of problem, especially when submerged vortices are involved. 1. The mean flow velocity at served (for the tested water the defined measurement levels in the building structure) points of the suction cross have to be documented on section should not deviate video tape and made available from the mean value by to the party commissioning the more than 10 %. tests. 2. The swirl angle should not Fig. 2.5-e: Laboratory photo of a surface vortex type 6 gated. The vortex formations KSB will support and co-ord- be higher than 5 degrees. inate project related model tests A swirl angle of 7 degrees upon request. can be tolerated if it has occurred during less than 10 % of the period of observation or if the pump manufacturer has defined other limits. 3. Surface vortices may only be accepted up to type 2 and submerged vortices up to Fig. 2.5-f: Laboratory photo of a surface vortex type 3 type 1 if they do not have an unacceptable influence on the measured velocity The criteria which apply to this profile. method of investigation may vary slightly depending on the type of pump or size of station. 37 2.6 The significance of CFD simulations 2.6 The significance of CFD simulation Methodology The mathematical description of fluid flows is based on the NAVIER-STOKES equations. Numerical flow simulation They describe the processes at (Computational Fluid each point of a flow by means Dynamics = CFD) is becoming of partial differential equations increasingly important. The for the mass, energy and mo- software specially developed for mentum. this purpose is an effective instrument allowing relatively precise predictions of the flow 1 ∂p ∂u ∂u ∂u ∂u +u +v +w +v = fx _ ρ ∂x ∂t ∂x ∂y ∂z [ ∂∂xu + ∂∂yu + ∂∂zu ] 1 ∂p ∂v ∂v ∂v ∂v +u +v +w +v = fy _ ρ ∂y ∂t ∂x ∂y ∂z [ ∂∂xv + ∂∂yv + ∂∂zv ] conditions. The time and cost of flow modelling depends on the - size of the flow area to be modelled 2 2 2 2 2 [ - computer performance The calculation of each spatial - form of presentation of point in a flow is not feasible as results (report) and scope of this would result in an infinite results. number of calculations. A grid is generated instead and its nodes are calculated. The grid model is then processed further to provide information on the pressure and velocity distribution, which can then be subjected to numerical and/or graphical analysis. In modelling, the distances between individual nodes 38 2 2 2 2 2 2 1 ∂p ∂w ∂w ∂w ∂w ∂ 2w ∂ 2w ∂ 2w +u +v +w +v + + = fz _ ρ ∂z ∂t ∂x ∂y ∂z ∂ x2 ∂ y2 ∂z2 - desired geometric resolution Fig. 2.6 -a: Flow patterns in Amacan intake chambers 2 may partly differ; they depend on the flow velocity gradients. ] 2.6 The significance of CFD simulation The calculated nodes lie closer Problems are more often caused together near walls and corners, by the fact that surface and which are considered as discon- submerged vortices and asym- tinuities from a fluid dynamics metrical inflows do not always point of view. In areas with low exhibit steady behaviour and velocity gradients it is not a are therefore difficult to predict problem to increase the dis- exactly. tances. In addition, assumptions on the distribution of turbulence are made at the nodes. The task of a CFD specialist is to choose the “correct” turbulence model. It takes a lot of experience to be able to create an adequate model and to be able to accurately interpret the Fig. 2.6-c: Simulation of pump station with several pumps results obtained. At KSB CFD simulation is a well-established engineering tool that has been used for years. The fact that CFD calculations have been proven to conform well with model testing in past investigations Fig. 2.6 -b: Simulation of approach flow to discharge tube allows more accurate predictions to be made today on potential flow situations and CFD simulation is perfectly enables pump stations to be suited to evaluating flows in more systematically optimised. intake structures and pump In complicated cases, however, sumps, especially as it can also physical model testing is to be be used to make a very exact preferred to CFD calculations analysis of the influence single for building structure pumps have on the flow pattern investigations. in multiple-pump systems. In the future the use of both CFD simulations and model testing will significantly reduce the overall costs of pump station investigations. 39 2.7 Screening equipment 2.7 Screening equipment Under conditions of long-term account that a screen filled with operation, however, failure to trapped material creates flow fit the appropriate screening resistance resulting in different The installation of screening equipment upstream of a pump water levels up- and downstream equipment is required for station will lead to sand accu- of the screen. This means that trouble-free pump operation: mulation and considerable sedi- the water level downstream of Depending on the type and mentation in stagnation zones the screen must not fall below the origin of the fluid handled it is at and within the building, as permissible minimum water level desirable to install coarse well as in increased wear to t1 for the pump’s operating point. screens (the distance between centrifugal pumps. Also, mechan- bars should be between 5 and ical damage to the impeller and 30 cm) and/or fine screens (the other pump parts cannot be distance between bars should ruled out. be between 5 and 20 mm) as well as shingle traps, mounted Where the screens are to be upstream of the screens, if accommodated in the pump needed. The screens and traps station concept is the designer’s should be cleaned automatically decision. The screening equip- during pump operation using ment is either mounted upstream appropiate mechanical equip- of the pump station or sump to ment. In applications where prevent coarse material from surface water from rivers, lakes entering the building, or single and channels is pumped or in screens are directly integrated storm water pumping stations into the intake chamber design. the installation of screening Selecting the latter option may equipment is an absolute must. necessitate longer chambers due Fig. 2.7-b: Screens with automatic cleaning devices to the slightly reduced flow cross section which results from integrating the screen. Downstream of the screening equipment the velocity distribution developing across the flow cross section Fig. 2.7-a: Coarse screens upstream of an Amacan pump station (water abstraction from a river) Fig. 2.7-c: Shingle trap upstream of pump station should be even and therefore Half of the impeller free passage favourable for pump operation, should be used as a reference provided the screen is largely value to determine the permis- free from any trapped material sible maximum distance between (see Fig. 2.7-b). the screen bars. This value can be taken from the appropriate The fact that river water in particular contains shingle and When establishing the minimum pump curve (see the type series sediment is often overlooked. water level t1 in the pump sump, booklet or selection software). it is also necessary to take into 40 2.7 Screening equipment horizontal position, the correc- The following values can be tion factor for the cleaning applied for the following dif- method csc and the coefficient ferent bar shapes: ζsc. For a clean screen this correction factor is 1, with mechanical cleaning it ranges between Shape 1 2 3 4 5 6 7 ß sc 1 0.76 0.76 0.43 0.37 0.3 0.74 1.1 and 1.3 and with manual Fig. 2.7-d: Wood inside the diffuser casing of an Amacan pump cleaning between 1.5 and 2. The coefficient ζsc includes the shape of the screen bars and the area To evaluate the screen’s influence on the water level directly upstream of the pumps it is ad- ratios between the free flow area a– and the distance between – the bar centrelines b. visable to use Hager’s simplified calculation [10], if a detailed . screen selection procedure is . not being undertaken. –a . vo – b . . ΔH δ sc Fig. 2.7-e: Flow through screen, without lowered floor Fig. 2.7-f: Screen layout drawing Therefore, ξ sc = β sc x ζ sc x c sc x δ sc Applying this calculation will 1 result in the lowering of the 2 4 3 screen as expressed in the – L – 0,6 L water level downstream of the 6 5 7 – 0,3 L vo equation: – d v2 ΔH = ξ sc x 0 2g Here v0 is the flow velocity up- Fig. 2.7-g: Different shapes of screen bars stream of the screen. The total loss coefficient β sc is a function of the angle of inclination of the screen δ sc in relation to the 41 2.7 Screening equipment – L is the length of the sreen bar – profile and a the width. If the – – ratio of L / a is 5 and the condition b a > 0.5 is satisfied, For detailed screen selection, the take chamber area would then method according to Idelchik achieve a better defined and [11, p. 504 ff] is recommended: even approach flow condition This method is most appropriate for the pump and screen. the formula for ξ sc can be simplified and expressed as when the influence of oblique flow to the screen is also to be Cleaning of the screen should follows: taken into account or if the preferably take place automat- screen bars are markedly differ- ically. To activate the cleaning ent from what was illustrated in process it is possible to make Fig. 2.7-g. use of the difference in water ξ sc = 7 β x 3 sc 3 – 4 [ ab −1]x c sc x sin δ sc levels up- and downstream of In order to compensate for the the screen. This ensures that the losses ΔH occurring as the flow cleaning process is activated as passes the screen, the floor of required. Manual cleaning is the intake structure or channel unfavourable for pump systems is often lowered by the value Δz in continuous operation, as the downstream of the screen. water level has to be regularly checked and the screen cleaned ΔH = Δz Fig. 2.7-i: Pump station with automatic screens The values usually applied for Screens are often integrated in between approx. 5 cm for the direct vicinity of the intake mechanical cleaning to approx. chambers. This means every 10 cm for manual cleaning. pump is dedicated with its own screen. The distance between the screening equipment and the pump’s discharge tube should be at least 4xD (D being vo the discharge tube diameter). Δz If it is assumed that the flow might approach the screen from Fig. 2.7-h: Flow through screen with lowered floor the side and the influence on the water level downstream of the screen might be difficult to predict, preventive measures are then advisable. Extending the intake chamber wall and positioning the screen in the in- 42 controlled cleaning is also not sufficiently reliable. losses through screens range ΔH sc by the operating staff. Timer 3.1 Discharge tube designs 3. Discharge tube designs The design configuration of Amacan pumps allows a wide 3.1 Design variants For this variant it is necessary that at the upper building level variety of installation variants the discharge tube is appropri- to be chosen with practically ately sealed against the fluid no boundaries set on a designer’s pumped and supported to creativity. Discharge tubes are withstand the mechanical forces. not only made from metal ma- The upper discharge tube edge terials - they can also be con- has to be designed in accord- structed with concrete elements. ance with the run-off conditions No matter which installation of the discharged fluid and the variant is chosen, it is impor- H min tant that the pump’s support maximum flow velocities within the tube itself. area in the tube, shaped as a 45-degree slope, is executed accurately. Fig. 3.1-a: Installation type A The support ring is set in concrete in the intake chamber H min area, then the concrete tube elements are used to construct the discharge tube. Such a design variant may be suitable for use in simple drainage and Fig. 3.1-c: Installation type BU irrigation pump stations. This discharge tube variant can, of course, also be employed in conjunction with open intake chambers. The final decision on the intake chamber design is H min taken on the basis of the required minimum water level relative to the volume flow rate of the pump and the approach flow direction (see diagram t1 = f(Q) in the Fig. 3.1-b: Installation type BG type series booklet or selection software). This illustration shows a covered intake chamber. Here the discharge tube is, however, made from metal. 43 3.1 Discharge tube designs mounted, the installation area is closed with a cover suitable for vehicles. The electrical cables 3.2 Details on discharge tube design are routed under the floor to the H min power supply. The manufacturing quality of the discharge tube is important for the proper functioning of the pump or pump station. As the pump is centered and pos- Fig. 3.1-d: Installation type CG itioned in the discharge tube on The next type of installation a 45-degree bevel, resting on a presented here is the underfloor rubber ring provided at the installation. The horizontal H min pump casing (the pump is seat- discharge pipe outlet is situated ed by its own weight plus the below the upper building level. axial thrust developed during An additional, above-floor pumping), particular attention building structure, which is necessary in conventional pump Fig. 3.1-f: Installation type DU must be given to this area during manufacturing. Poor stations, is not required here, If some systems require the concentricity and surface finish resulting in a cost advantage. discharge flange to be connected may cause the pump to rest on above the floor, the installation some points but not all of the type illustrated in Fig. 3.1-f can inclined support area, resulting be chosen. A plate is mounted in inadequate sealing with some on the upper building level to flow passing back to the suction accommodate the discharge tube side. As a consequence, the forces. When deciding on the pump does not achieve the size of this plate it is important volume flow rate required for to consider the maximum forces the connected system. H min developing during pump operation (pump weight, piping forces, torques resulting from Fig. 3.1-e: Installation type CS pump operation, etc.). If the area above the pump station is intended for vehicular traffic, the discharge tube can, if necessary, be fitted with support feet resting on the floor underneath the inlet. After the discharge tube has been set up and 44 Fig. 3.2-a: Support area of pump in discharge tube for Amacan K 3.2 Discharge tube designs For all discharge tubes closed low wall thicknesses the natural with a cover it is vital to provide frequency of the tubes may an adequate venting device. If quickly reach excitation fre- this is not provided, a cushion quency levels (owing to the of compressed air will develop working principle of the centri- in the upper discharge tube fugal pump). The result is res- section. This has an effect onance accompanied by extreme similar to that of a spring and vibration effects. prevents the pump from running steadily. In extreme cases, Foundation bolts at site affect the entire discharge tube. If the tube is a welded metal of the tube down to the sump, sheet construction, it is import- or the discharge tube cover is ant to ensure that the welded fitted with a venting and aer- seams in the 45-degree support ation device. If a vent pipe is to area are level and true. The be fitted, the additional space entire discharge tube should required must be taken into additionally be checked for account when planning the ac- concentricity. As thin metal cess openings. . Fig. 3.2-b: Discharge tube in sheet metal construction for Amacan P / S . vibrations may be caused which pipe is laid from the upper end . . . . As a remedial measure, a vent Adapt to site conditions ( ≈ 400) Fig. 3.2-d: Discharge tube bracing with turnbuckles sheets tend to be deformed by the welding process the metal sheet thickness should not be less than 8 mm. Alternatively, it is also possible to make this support area as a turned part and to weld it to the discharge tube at the top Fig. 3.2-c: Discharge tube fitted with valve for venting and aeration and bottom. Making long discharge tubes from individual If the installation depth of the segments bolted together at discharge tube is more than their respective flanges is rec- 4 metres the tube should be ommended to improve concen- centered and/or braced. This is tricity. These tubes are easy to particularly important in the install at site and the flanges case of stainless steel tubes provide additional mechanical which are used for their rela- stability in the radial direction. tively thin walls. Due to these 45 3.3 Cable connections 3.3 Cable connections This sealing principle is used the form of the discharge tube for both power and control and the system pressure. If the cables. When the pump is in- tube variant is one closed with The pumps of the Amacan series stalled in the discharge tube, it a cover, the cables must be are all equipped with an abso- is necessary to mechanically supported by a separate holder lutely watertight cable entry support the cables’ own weight underneath the cover to support system. This KSB patented and at the same time protect the cables’ own weight and pro- system protects against the them against flow turbulence. tect them against flow turbu- pumped fluid penetrating the For this purpose KSB has de- lence in the discharge tube, as motor space or terminal box of veloped a patented cable holder. described above. the pump if the cable insulation The cables (power and control has been damaged during cables) are attached to a stain- assembly or operation. The less steel carrier rope using insulation of the individual rubber profiles and a clip. The cable cores is stripped and the rope is then screwed to the dis- wire ends are tinned. This sec- charge tube cover or to a cross tion is fixed in the cable gland bar in the case of an open dis- system with spacers and then charge tube. This guarantees embedded in synthetic resin. A that the cables have a long ser- rubber gland provides additional vice life and the cable entry into sealing. the motor housing is absolutely tight. Fig. 3.3-c: Cable suspension and cable entry into discharge tube If the discharge tube is open, the 1 cables are routed vertically out 2 of the tube and are then attached to a cross bar. If Amacan pumps 3 4 1 Long rubber gland 2 Outer cable insulation 3 Individual cores are additionally cast in resin 4 Individual core insulation stripped, wire ends tinned and embedded in cast resin Fig. 3.3-a: Sectional drawing of an absolutely watertight cable entry system on a pump 46 Fig. 3.3-b: Example of a rope with cable holder for an installation depth of 50 m are installed at greater installation depths, then additional supports should be fitted to hold the cable carrier rope in position. The To ensure the cables are smoothly object of these supports is to re- routed through the discharge duce the influence of the turbu- tube cover either welded-in lent flow on the rope. These sleeves or shaped rubber gromets supports rest against the dis- are used. The choice of cable charge tube wall. passage depends in the main on 3.3 Cable connections If the components described above are not ordered along with the pump, other solutions may have a very negative influence on the pump’s functioning. Power and control cables are, for instance, very Fig. 3.3-d: Supports for cable guidance in the discharge tube often attached to the rope with simple cable straps; this, however, will lead to the destruction When ordering the pump it is of the cable insulation and/or necessary to specify the exact core breakage inside the cable installation depth so that the during pump operation. precise length of the cables and ropes as well as the number of supports can be determined. If the specifications of both planning and execution stages differ, the following two situations may arise: If the rope is too short, the pump will not be firmly seated in the discharge tube and the reaction moment Fig. 3.3-e: Cable attachment using simple cable straps of the pump may damage the cables during start-up. If the For installation depths greater cables are too long or not tight than 5 m the cable holder and enough, the flow may cause the carrier rope design becomes lifting rings of the cable assembly increasingly important for to hit against the discharge tube trouble-free pump operation. thereby damaging discharge tube, rope and cables. In order to determine the correct number of lifting rings on the rope, it is also important to know the lifting height of the davit, lifting frame or crane. 47 4 List of references and photographs 4. References [1] Dr.-Ing. K. Holtzenberger, KSB AG, Centrifugal Pump Design, 5th edition 2005, ISBN 3-00-004734-4 [2] KSB AG, Amacan P type series booklet, 1580.5/5 [3] KSB AG, Amacan S type series booklet, 1589.5/5 [4] KSB AG, Amacan K type series booklet, 1579.5/3 [5] Hydraulic Institute, American National Standard for Pump Intake Design, ANSI / HI 9.8-1998 [6] M. J. Prosser, The Hydraulic Design of Pump Sumps and Intakes, BHRA, July 1997 [7] Henry T. Falvey, Air-Water Flow in Hydraulic Structures, Engineering and Research Center Denver, Colorado 80225, December 1980 [8] Jost Knauss, Swirling Flow Problems at Intakes, IAHR+AIRH, ISBN 90 6191 643 7, Rotterdam 1987 [9] Christian Frey, Peer Springer, Dr. Sven Baumgarten, Bernd Kothe, Optimization of Waste Water Pumping Station Architecture Using CFD Analysis, Validated by Model Testing, Pump Users International Forum 2004, Section 5: Pumps for Waste Water, Karlsruhe, Germany [10] W.H. Hager, Abwasserhydraulik: Theorie und Praxis, Springer Verlag, ISBN 3-540-55347-9, 1994 [11] I.E. Idelchik, Handbook of Hydraulic Resistance, 3rd Edition, Research Institute for Gas Purification, Moscow 1994, ISBN 0-8493-9908-4 [12] Schweizer Norm SN CR 13930: Rotodynamic Pumps – Design of Pump Intakes – Recommendations for the Installation of Pumps, VSM 2000 [13] Charles E. Sweeney, Rex A. Elder, Duncan Hay, Pump Sump Design Experience: Summary, March 1982 [14] US Army Corps of Engineers, Pumping Station Inflow – Discharge Hydraulics, Generalized Pump Sump Research Study, Technical Report HL-88-2 [15] Robert Sanks, Pumping Station Design, 2nd Edition, Butterworth Heinemann, Boston · Oxford · Johannesburg · Melbourne · New Delhi · Singapore [16] P. Tillack, D.-H. Hellmann, A. Rüth, Description of surface vortices with regard to common design criteria of intake chambers, 2nd International Conference on Pumps and Fans, Beijing, China 1995 Photographs Pg. 15 Fig. 2.1-a : KaiserslauternTechnical University, Institute for Fluid Machinery Pg. 23 Fig. 2.2.4-i : Hydrotec Consultants Ltd., Leeds, UK Pg. 37 Fig. 2.5-e and 2.5-f : KaiserslauternTechnical University, Institute for Fluid Machinery Author Dipl.-Ing. Bernd Kothe, born in 1955, studied at the Otto von Guericke Technical University in Magdeburg. After completing his studies, he became a development engineer for power station pumps at the Pumpenwerke Halle (Saale) company. From 1993 to 1998 he was responsible for transient flow analysis and complex waste water calculations in the engineering department of KSB AG. Since 2002, he has held the position of Sales Support Manager of the Competence Center Waste Water in Halle (Saale), Germany. 48