Energy Meters All our know-how - is now yours
Transcription
Energy Meters All our know-how - is now yours
MAKING MODERN LIVING POSSIBLE Your Personal Catalog Energy Meters All our know-how - is now yours Index 3 Sonometer™2100 20 Infocal 8 32 SONO 1500 CT 40 Sonometer™1100 Data sheet SONOMETERTM2100 Ultrasonic energy meter Description/Application - Insensitive against magnetite - Installation in any position - Free selectable pulse values from 1 ml MID examination certificate no.: DE-10-MI004-PTB008 and DE-09-MI004-PTB011 The SONOMETERTM2100 is an ultrasonic energy meter especially designed for heating, cooling or combined heating/cooling application in local and district heating systems. The SONOMETERTM2100 consists of: - Ultrasonic flow sensor, type SONO 1500 CT; - Energy calculator, type INFOCAL 8; - Pairs of temperature sensors. The SONOMETERTM2100 has been approved according to MID. Features of SONO 1500 CT - 1st approval in Europe for ultrasonic flow sensor with dynamic range of qi/qp 1:250 in class 2 (qp 1.5 / 2.5 / 6 / 10 / 15 / 25 / 40 / 60 m³/h) - Complete dynamic range: ≥ 1:1500 - Lithium battery with a lifetime of 11 years or external supply - Temperature range: 5 - 90 °C / 130 °C / 150 °C - Overload temperature up to 150 °C (sizes qp 0.6 up to 2.5 m³/h) - Available in nominal sizes: qp 0.6 / 1.0 / 1.5 / 2.5 / 3.5 / 6 / 10 / 15 / 25 / 40 / 60 m³/h - Unique free-beam principle - Swirl-free flow around reflector - Robust stainless steel reflector - All sizes also available in PN 25 - No calming sections necessary in the inlet and/ or outlet (standard installation) - NOWA test capability - Connection to calculator with pulse defined values DEN-SMT/PL VD.SH.L2.02 © Danfoss 08/2011 Features of INFOCAL 8 - Lithium battery with lifetime typical 11 years or 16 years optional (depending on selected functionality and connected flow sensor) - Temperature range: –20 to +190 °C - Power save mode - NOWA test capability - Connection possibility of 2- and 4-wire temperature sensor pairs - Remote reading via M-Bus, L-Bus, RS 232, RS 485, Radio or optical interface - Integrated Radio (868 or 434 Hz), Real Data or Open Metering Standard (OMS) - Individual remote reading (Automatic Meter Reading) with add on modules Plug&Play - 2 communication ports (e.g. M-Bus + M-Bus) - Improved radio performance - Individual tariff functions - History memory for 24 months - Extensive diagnostic displays - IZAR@SET parameterization software on Windows basis guarantees optimum adaptation to the user’s specific needs 1 Data Sheet SONOMETERTM2100 – Ultrasonic energy meter Description/Application, continued The SONOMETERTM2100 is able to handle 3 types of applications: DEN-SMT/PL District heating/boiler application Combined heating/cooling application Chilled water application VD.SH.L2.02 © Danfoss 08/2011 2 SONOMETERTM2100 – Ultrasonic energy meter Data Sheet Ordering: The ordering code no. consists of both dummy code and ordering code. Dummy code: 087G6012 Ordering code AAA BB - C D E F G H P AAA - application only temperature sensors 4 energy meter for heating energy meter for cooling 1,2 energy meter for heating / cooling 1,2,3 only flow sensor for heating only flow sensor for cooling 1,3 1 I J K - - 4TS 2HE 2CO 2HC 15H 15C 0 1 4 00 AT BA BG CN DK CZ DE GB HR IE IT KZ LV MD PL RO RU CS SK SI TR UA 00 1A 1B 1C 1D 1E 1F 1G 1H 1I 1J 1K 1L 1M 1N 2A 2B 2C 2D 2E 2F 2G 2H 2I 2J 2K 2L 2M 0 1 2 3 4 only PN 25 possible flow sensors for external power supply C - pressure not relevant PN 16 PN 251 0 C D 1 flange versions must be PN 25 D - flow sensor cable not relevant 2.5 m 5m 10 m 0 A B C E - installation not relevant low temperature high temperature 0 L H F - power supply not relevant / with external power supply 1 battery 3.6 V DC (A-cell) battery 3.6 V DC (D-cell) 2 mains unit 230 V AC mains unit 24 V AC 0 1 2 3 4 1 2 GH - interface modules modules slot 1 no module in slot 1 Analogue output module (4-20 mA) 1 Combined module (2 pulse inputs / 1 pulse output) Pulse input module (2 inputs) M-Bus module L-Bus module (use for external radio) RS232 module RS485 module modules slot 2 no module in slot 2 Pulse output module 2 Combined module (2 pulse inputs / 1 pulse output) 2 Pulse input module (2 inputs) 2 M-Bus module 2 L-Bus module (use for external radio) 2 RS232 module 2 RS485 module 2 2 P - version of communication without integrated radio (standard) Radio 868 MHz Real Data Radio 434 MHz Real Data Radio 868 MHz Open Metering Standard Radio 434 MHz Open Metering Standard only for flow sensor for integrated radio 1 2 3 4 0 A B C D E F G 0 A B C D E F G 1 only one module possible integrated radio is not available 0 1 2 3 4 VD.SH.L2.02 © Danfoss 08/2011 test reports on request NN - country code Neutral code with docs in English (standard) Austria Bosnia Bulgaria China Denmark Czech Republic Germany United Kingdom Croatia Ireland Italy Kazakhstan Latvia Moldova Poland Romania Russia Serbia Slovak Republic Slovenia Turkey Ukraine M - connections (sets) without screwing set R ½” x G ¾ B screwing set R ¾” x G 1 B screwing set R 1” x G 1¼ B screwing set R 1½” x G 2 B screwing sets are packaged in an extra box L - accessories / pocket 0 without for ø 5.2 mm temperature sensors (pair1) F brass-pockets, 35 mm, MID 2 DN 15-32 G brass-pockets, 52 mm, MID DN 40-65 H brass-pockets, 85 mm, MID DN 80-125 I brass-pockets, 120 mm, MID DN 150-200 3 stainless steel-pockets, 85 mm, MID DN 80-125 4 stainless steel-pockets, 120 mm, MID DN 150-200 5 stainless steel-pockets, 155 mm, MID DN 200-250 6 stainless steel-pockets, 210 mm, MID DN 300 1 versions with one sensor pocket on request 2 max temperature: 105°C temperature sensor pockets are packaged in an extra box for ø 6.0 mm temperature sensors (pair) V brass-pockets, 40 mm MID DN 25-65 W brass-pockets, 85 mm MID DN 80-125 X brass-pockets, 120 mm MID DN 150-200 Y stainless steel-pockets, 85 mm MID DN 80-125 Z stainless steel-pockets, 120 mm MID DN 150-200 1 stainless steel-pockets, 155 mm MID DN 200-250 2 stainless steel-pockets, 210 mm MID DN 300 temperature sensor pockets are packaged in an extra box Accessories (1 piece) 3 R ball valve DN 15 - ½” for direct sensor S ball valve DN 20 - ¾” for direct sensor T ball valve DN 25 - 1” for direct sensor U adapter for mounting direct sensor R½” M 10x1 3 not possible for ø 6.0 mm sensors ball valves packaged in an extra box 1 2 O - verification without approval mark, no test reports compliant according to national regulations PTB K 7.2 for cooling compliant to MID. With letter of conformity 1 1 includes potting and special temperature sensors for cooling or heating/cooling application 2 meter without type approval 3 120° maximum operation temperature 4 prices in the accessories list valid BB - (for) flow sensor (type SONO 1500 CT) not relevant / no flow sensor qp 0.6 m³/h / 110 mm thread / DN 15 / G¾B / 1 litre / pulse 2 qp 0.6 m³/h / 130 mm thread / DN 20 / G1B / 1 litre / pulse 2 qp 0.6 m³/h / 190 mm thread / DN 20 / G1B / 1 litre / pulse 2 qp 1.0 m³/h / 110 mm thread / DN 15 / G¾B / 1 litre / pulse 2 qp 1.0 m³/h / 130 mm thread / DN 20 / G1B / 1 litre / pulse 2 qp 1.0 m³/h / 190 mm thread / DN 20 / G1B / 1 litre / pulse 2 qp 1.5 m³/h / 110 mm thread / DN 15 / G¾B / 1 litre / pulse 2 qp 1.5 m³/h / 130 mm thread / DN 20 / G1B / 1 litre / pulse 2 qp 1.5 m³/h / 190 mm thread / DN 20 / G1B / 1 litre / pulse 2 qp 2.5 m³/h / 130 mm thread / DN 20 / G1B / 1 litre / pulse 2 qp 2.5 m³/h / 190 mm thread / DN 20 / G1B / 1 litre / pulse 2 qp 3.5 m³/h / 260 mm thread / DN 25 / G1¼B / 10 litre / pulse 2 qp 6 m³/h / 260 mm thread / DN 25 / G1¼B / 10 litre / pulse 2 qp 10 m³/h / 300 mm thread / DN 40 / G2B 2 qp 0.6 m³/h / 190 mm flange DN 20 / 1 litre / pulse 1,2 qp 1.0 m³/h / 190 mm flange DN 20 / 1 litre / pulse 1,2 qp 1.5 m³/h / 190 mm flange DN 20 / 1 litre / pulse 1,2 qp 2.5 m³/h / 190 mm flange DN 20 / 1 litre / pulse 1,2 qp 3.5 m³/h / 260 mm flange DN 25 / 10 litre / pulse 1,2 qp 3.5 m³/h / 260 mm flange DN 32 / 10 litre / pulse 1,2 qp 6 m³/h / 260 mm flange DN 25 / 10 litre / pulse 1,2 qp 6 m³/h / 260 mm flange DN 32 / 10 litre / pulse 1,2 qp 10 m³/h / 300 mm flange / DN 401 / 10 litre / pulse 1,2 qp 15 m³/h / 270 mm flange / DN 501 / 10 litre / pulse 1,2 qp 25 m³/h / 300 mm flange / DN 651 / 10 litre / pulse 1,2 qp 40 m³/h / 300 mm flange / DN 801 / 100 litre / pulse 1,2 qp 60 m³/h / 360 mm flange / DN 1001 / 100 litre / pulse 1,2 3 L M - NN O N O P Q T U V W A B C D E F G H I J K L M K - temperature sensor mounting Direct sensor mounting (qp 0.6 - qp 2.5) 1 (standard) Direct sensor mounting (qp 3.5 - qp 15) 1 Pocket sensor mounting (2 free sensors) (qp 0.6 - qp 2.5) 2 Pocket sensor mounting (2 free sensors) (qp 3.5 - qp 60) (standard) 1 one temperature sensor mounted in the body 2 2 free sensors, temperature sensor drill in the body closed J - temperature sensors (pair) Pt 500 / ø 5.2 mm / 2 m cable, MID and 22.77/08.04 (standard) Pt 500 / ø 5.2 mm / 3 m cable, MID and 22.77/08.04 Pt 500 / ø 5.2 mm / 5 m cable, MID and 22.77/08.04 Pt 500 / ø 5.2 mm / 10 m cable, MID and 22.77/08.04 1 Pt 500 / ø 6.0 mm / 2 m cable, MID 2 Pt 500 / ø 6.0 mm / 3 m cable, MID 2 Pt 500 / ø 6.0 mm / 5 m cable, MID 2 Pt 500 / ø 6.0 mm / 10 m cable, MID 1, 2 1 only available as an accessory 2 not available for Heating/Cooling and Cooling I - energy units kWh (without digit after comma) MWh (with 1 digit after comma) MWh (with 2 digit after comma) MWh (with 3 digit after comma) GJ (with 1 digit after comma) GJ (with 2 digit after comma) GJ (with 3 digit after comma) Gcal (with 1 digit after comma) 1 Gcal (with 2 digit after comma) 1 Gcal (with 3 digit after comma) 1 MBtu (with 1 digit after comma) 1 MBtu (with 2 digit after comma) 1 MBtu (with 3 digit after comma) 1 1 not applicable for MID approved meters DEN-SMT/PL Data Sheet SONOMETERTM2100 – Ultrasonic energy meter Ordering continued Modules Communication Function Supply voltage Code No. 087G6027 087G6035 087G6029 087G6032 087G6034 087G6041 087G6037 087G6039 087G6020 087G6022 087G6024 087G6025 Designation M-Bus module L-Bus module (use for external radio) RS232 module RS485 module Analogue output module (4-20mA) Combined module (2 pulse inputs/ 1 pulse output) Pulse input module (2 inputs) Pulse output module (2 outputs) battery 3.6 V DC (A-cell) battery 3.6 V DC (D-cell) mains unit 230 V AC mains unit 24 V AC Accessories Temperature sensors Temperature sensors (pair) Pt 500 / ø 5.2 mm / 10 m cable, MID Pt 500 / ø 6.0 mm / 10 m cable, MID Ball valves Adapter for mounting temperature sensors pair Code No. 1 087G6048 1 087G6052 Dimension (IG) G ½’’ G ¾’’ Set 12 pcs 12 pcs Code No. 087G6068 087G6069 G 1’’ 12 pcs 087G6070 Coupling thread Sensor thread Set Code No. R ½’’ M 10 x 1 32 pcs 087G6076 Tailpieces Threaded Software The IZAR@SET parameterization software on windows basis is a convenient tool for handling the energy meter. The IZAR@SET software is available on web site www.hydrometer.de. DEN-SMT/PL VD.SH.L2.02 © Danfoss 08/2011 Dimension (AGR x IG) R ½” x G ¾ B R ¾” x G 1 B R 1” x G 1¼ B Set Code No. 1 pc 1 pc 1 pc 087G6071 087G6072 087G6073 R 1½” x G 2 B 1 pc 087G6074 It is used for: - commissioning - reading out measured values - printing out energy meter logs - energy meter configuration - application analysis - print the meter protocol 4 SONOMETERTM2100 – Ultrasonic energy meter Data Sheet Technical data INFOCAL 8 Basic data Display indication Temperature Ambient class Protection class Display Units Total values Values displayed Ambient Storage Temperature sensors Sensor current Measuring cycle Input Max. temp. difference Min. temp. difference Starting temp. difference Absolute temp. measuring range Battery supply Mains supply EN 1434 class E1 +M1 IP 54 LCD, 8-digit MWh - kWh - GJ - Gcal - MBtu - gal - GMP - °C - °F - m³ - m³/h 99 999 999 - 9999 999.9 - 999 999.99 - 99 999.999 Power - energy - flow rate - temperature - volume 0 - 55 °C -25 - +70 Pt 500 with 2-wire leads Type < 10 m mA Pt 500 peak < 2; rms < 0.012 Mains unit supply: 2 T s A-cell battery: 16; D-cell battery: 4 177 ∆θmax K 3 ∆θmin K ∆θ K 0.125 θ °C -20...190 3.6 VDC, A cell, 11 years lifetime 3.6 VDC, D cell, 16 years lifetime 24 VAC, 230 VAC / 0.15 W SONO 1500 CT Flow rate Nominal Maximum Minimum Starting Nominal qp m3/h qs m3/h l/h q i l/h DN mm 0.6 1.2 6 1 1.0 / 1.5 2/3 10 / 6 2.5 2.5 5 10 4 20 Diameter 15 20 15 20 Operating Maximum PN bar 16 / 25 25 16 / 25 25 16 / 25 25 pressure Temperature range heating 5 ... 90 / 5 ... 105 1 battery supplied Temperature range heating - °C 5 ... 130 external supplied Temperature range cooling 5 ... 90 / 5 ... 105 1 Medium circulation water (pH: 7 - 10) Δp mbar 85 36 / 75 100 Pressure loss At qp 130 190 Overall length mm 110 130 190 110 130 190 Volume l/imp. 0.001...5000 (depend on qp) Pulse value Test ml/imp. 5 10 20 battery supply: 3.0 V DC Supply Operating UN external supply: 3.0..5.5 V DC 2 voltage Enviro. class EN 1434 class C / MID class E1 + M1 Basic data Protect. class IP 54 (heating) / IP 68 (cooling) 1 Only in rising or falling pipes or tilted installation. 2 For medium temperatures above 90 °C, the flow sensor must be equipped with an external supply. Pressure loss graph 5 3.5 7 35 7 25 6 12 24 7 32 16 / 25 25 25 32 16 / 25 25 5 ... 150 1 44 260 128 260 20 50 Measuring accuracy to EN 1434 Class 2 for SONO 1500 CT VD.SH.L2.02 © Danfoss 08/2011 DEN-SMT/PL Data Sheet SONOMETERTM2100 – Ultrasonic energy meter Technical data, continued SONO 1500 / CT Flow rate Diameter Operating pressure Temperature range heating battery supplied Temperature range heating external supplied Temperature range cooling Medium Pressure loss 3 Overall length Pulse value Nominal Maximum Minimum Starting Nominal Maximum qp m3/h qs m3/h l/h qi l/h DN mm PN bar 10 20 40 4/100 20 40 15 30 60 4/150 40 50 25 50 250 50 65 25 40 80 160 4/400 80 80 60 120 240 4/600 120 100 5 ... 90 / 5 ... 105 1 Flow sensor At qp Volume Test Supply voltage °C ∆p mbar mm l/imp. ml/imp UN 5 ... 150 1 95 300 100 5 ... 90 / 5 ... 105 1 circulation water (pH - value: 7 -10) 80 75 80 270 300 300 0.001...5000 (depend on qp) 150 250 250 battery supply: 3.0 V DC external supply: 3.0..5.5 V DC 2 EN 1434 class C / MID class E1 + M1 IP 54 (heating) / IP 68 (cooling) 75 360 500 Environmental class Protection class 1 Only in rising or falling pipes or tilted installation. 2 For medium temperatures above 90 °C, the flow sensor must be equipped with an external supply. 3 Acc. to EN 1434 6.17. 4 Only for horizontal installation. Basic data Temperature sensors (pair) Direct mounted (EN 1434) Pt 500, 2-wire (EN 60751) Type Element Pairing Medium temperature Medium °C °C Response time t 0.5 Pressure rating PN bar Protection class Pipe material Pocket sensor (EN 1434) Pt 500, 2-wire (EN 60751) 10, 80, 130 0...180 0...150 District heating water acc. to sensor pocket technical data Typically 0.8 s / 0.4 m/s table acc. to sensor pocket technical data 16 table IP 67 IP 65 W 2.4816 W 1.4303 Temperature sensor pockets Type Medium temperature Medium Brass °C Response time t 0.5 Pressure rating PN Material Adapter bar Stainless steel 0...180 District heating water Typically 9 s / 0.4 m/s Typically 13 s / 0.4 m/s Typically 5 s / 0.4 m/s with pasta Typically 5 s / 0.4 m/s with pasta 25 CuZn40Pb2 (Ms 58) W 1.4571 CuZn40Pb2 (Ms 58) Design and function The SONOMETERTM2100 is an ultrasonic energy meter especially designed for heating, cooling or combined heating/cooling application in local and district heating systems. DEN-SMT/PL VD.SH.L2.02 © Danfoss 08/2011 The SONOMETERTM2100 consists of: - Ultrasonic flow sensor, type SONO 1500 CT; - Thermal energy calculator, type INFOCAL 8; - Pairs of temperature sensors. 6 Data Sheet SONOMETERTM2100 – Ultrasonic energy meter INFOCAL 8 Calculator The calculator contains all the necessary circuits for recording the flow rate and temperature as well as for calculating, logging and displaying the data. The calculator housing can be mounted directly on the flow sensor or on the wall. At application with medium temperature above 90 °C or at temperatures Twater < Tenvironment the calculator has to be removed from the flow sensor. The calculator can be conveniently read from a single line 8-digit display with units and symbols. A push-button provides user-friendly control of the various display loops. All failures and faults are recorded automatically and shown on the LC display. To protect the reading data, all the relevant data are saved in a non-volatile memory (EEPROM). This memory saves the measured values, device parameters and types of error at regular intervals. Temperature Sensors Pairs of Pt 500 temperature sensors with 2-wire or 4-wire leads are used. Integrated Radio Integrated Radio is an interface for communication with radio receiver. - Frequency band: 868 or 434 MHz - Type of radio telegram: Real Data or Open Metering Standard (OMS) - Transmission data updating: Online - no time delay between value measurement and data transmission - Data transmission: Unidirectional - Sending interval: 12...20 s; depending on length of telegram (duty cycle) Interfaces - Optical: ZVEI interface as standard, for communication and testing, M-Bus protocol. - M-Bus: Configurable telegram, according to EN1434-3. Data reading and parametrization are via two wires with polarity reversal protection. - L-Bus: Adapter for external radio module; configurable telegram, according to EN1434-3. Data reading and parametrization are via two wires with polarity reversal protection. M-Bus protocol. - RS232: Serial interface for communication with external devices. A special data cable is required. M-Bus protocol. - RS485: Serial interface for communication with external devices. Power supply with 12V ± 5V. M-Bus protocol. - Pulse output: Module with 2 Open Collector pulse outputs (potential-free), 4 Hz (pulse width 125ms), 100 Hz (pulse width ≥5ms), ratio: pulse duration / pulse break ~ 1:1. Configurable via IZAR@SET software. Possible pulse output values are Energy, Volume, Tariff energy 1, Tariff energy 2, Tariff condition 1, Tariff condition 2, Energy error and Volume error. - Pulse input: Module with 2 pulse inputs, max. 20 Hz with minimum pulse duration of 10 msec, input resistance 2.2 M Ohms, terminal voltage 3 V DC, cable length up to maximum 10m. The pulse value and the unit is configurable for energy, water, gas or electrical meter by IZAR@ SET. Data can be transferred remotely. Also two accounting day’s are available for both inputs. 7 VD.SH.L2.02 © Danfoss 08/2011 - Combined pulse input / output: Module with 2 pulse inputs and 1 pulse output. Configurable via IZAR@SET software. - Analogue output: Module for 4...20 mA with 2 programmable passive outputs, programmable value in case of error. Output values can be power, flow rate, temperatures. Configurable via IZAR@SET software. Slot 1 - Analogue output module (4-20mA) - Combined module (2 pulse inputs / 1 pulse output) - Pulse input module (2 inputs) - M-Bus module - L-Bus module (use for external radio) - RS232 module - RS485 module Slot 2 - Pulse output module - Combined module (2 pulse inputs / 1 pulse output) - Pulse input module (2 inputs) - M-Bus module - L-Bus module (use for external radio) - RS232 module - RS485 module Event Memory Events such as changes and faults are stored in a non-volatile memory with a capacity of up to 127 entries. The following events are recorded: - Checksum error - Temperature measurement error - Start and end of test mode - Changing of the main configuration Monthly Memory The INFOCAL 8 has a history memory of 24 months. The following values are stored in the EEPROM on the programmable interval (daily, weekly, monthly): - Date/ Time - Cumulated energy - Tariff energy 1 - Tariff energy 2 - Tariff definition 1 - Tariff definition 2 - Cumulated volume - Error hour counter - Value of max. flow - Time max. flow - Date max. flow - Value of max. power - Time max. power - Date max. power - Pulse input counter 1 - Pulse input counter 2 - Pulse 1 definition - Pulse 2 definition - Operating days - Max. forward temperature - Time max. forward temperature - Date max. forward temperature - Max. return temperature - Time max. return temperature - Date max. return temperature DEN-SMT/PL Data Sheet SONOMETERTM2100 – Ultrasonic energy meter Design and function, continued Log Memory The large two log memory blocks are used to store consumption values. The storage frequency can be selected from various storage intervals (1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, 60 minutes or the default setting of 24 hours, Day in the month, Day of the week, (1024 seconds), 15th or end of month). The data saved in the log memory can be used for the following analyses: - Reading the calculator on a certain day. Example: If the day for reading is 01.10, the calculator reading is displayed for the period from 01.10 of the previous year to 30.09 of the current year. - Comparison of the last consumption period with the preceding period Extract of possible log memory settings Memory Storage block interval area 1 1 hour 24 area 2 hours area 1 1 hour area 2 24 hours Values Error status, overload time temperature, overload time flow rate, supply temperature, return temperature, date and time, energy, tariff energy 1, tariff energy 2, tariff definition 1, tariff definition 2, volume, error day counter Accounting date The calculator includes two independent memories in which the accumulated energy at two programmable dates is stored. - Last Accounting Date; - Last but one Accounting Date; - Values stored: - Energy; - Volume; - Tariff counter 1; - Tariff counter 2; - Pulse counter 1; - Pulse counter 2; - Date. Max. Actual Values Memories The calculator creates maximum values for power, flow rate and temperatures based on consumption time, which are stored in the EEPROM. The integration intervals are adjustable to 6, 15, 30 or 60 minutes, 24 hours (and 1024 seconds). Default setting is 60 minutes. Date block size example 16 byte Number of data records 556 Recording period 23 days 16 byte 299 299 days 8 byte 1113 46 days 8 byte 599 599 days Tariff Function The calculator offers four optional tariff memories for monitoring plant load states for limit tariffs. Here it concerns threshold value tariffs. Extensive tariff conditions make it possible to adapt the calculator individually to the required customer-specific applications. The tariffs are separately configurable and independent from each other. Energy or time can be measured alternatively per tariff register dependent on the tariff mode adjusted in each case. With the “time triggered tariff function” (type Z) the switch-on time and the switch-off time are adjustable independent from each other for each day of the week in steps of 15 minutes. The following limit types are possible: (This example applies to the display at 3 digit after volume comma) Type ∆T -∆T TR TF P Q Description LIMIT LIMIT resolution Temperature difference 1 ... 255 °C 1 °C Negative temperature difference 1 ... 255 °C 1 °C Low temperature (low) 1 ... 255 °C 1 °C High temperature (high) 1 ... 255 °C 1 °C Power 1 ... 255 kW 1 kW Flow 100 ... 25 500 l/h 100 l/h “Theoretically Supply Energy” with return FE temperature of 0 °C Z “Time triggered” counting energy E “External” counting energy More detailed description concerning tariff functions on request. Leakage Function - on request Display Control The readings are displayed on the calculator by a 8-digit LCD with units and symbols. DEN-SMT/PL VD.SH.L2.02 © Danfoss 08/2011 8 Data Sheet SONOMETERTM2100 – Ultrasonic energy meter Design and function, continued Loop Structure The INFOCAL 8 display has six loops. Some display windows consist of two (to maximum seven) displays that are shown alternately at 4-second intervals. Some pictures in loops or a complete loop can be deactivated separately. The main loop with the current data, e.g. for energy, volume and flow rate, is programmed as default setting. In the standard setting the loop no. 5 (tariff loop) is not activated. For quick visual guidance, the loops in the display are numbered from 1 to 6. Overview of Loops DEN-SMT/PL VD.SH.L2.02 © Danfoss 08/2011 9 SONOMETERTM2100 – Ultrasonic energy meter Data Sheet Informative Displays (Standard) Loop “1” Main loop Loop Sequence 1.1 1.2 1.3 1.4 2.8 Sequence 3.1 3.2 3.3 3.4 3.5 3.6 Window 1 Accumulated energy Volume Flow Power Forward / - return temperature Difference temperature Operating days Error status Display test Window 1 Accounting date 1 date Next accounting date 1 date Previous accounting date 1 date ,Accd 1' Accounting date 2 date Next accounting date 2 date Previous accounting date 2 date ,Accd 2' Window 1 Current date ,SEC_Adr' ,Pri_Adr 1' ,Pri_Adr 2' Installation position ,In0' 3.7 ,Port 1' 3.8 ,Port 2' 3.9 Status integrated radio 3.10 1.5 1.6 1.7 1.9 1.10 Sequence 2.1 2.2 2.3 “2” Accounting date loop 2.4 2.5 2.6 2.7 Loop “3“ Info loop Loop Sequence No. of error hours ,F01-001' (software version) Window 1 “4” Pulse input loop 4.1 ,In1' 4.2 ,In2' 3.11 Window 2 Window 3 Window 4 Window 2 Accounting date 1 energy Window 3 [off] Accounting date 1 volume Window 4 ,Accd 1A' Next accounting date 1 energy Next accounting date 1 volume ,Accd 1L' Previous accounting date 1 volume ,Accd 1' Accounting date 2 volume ,Accd 2A' Next accounting date 2 volume ,Accd 2L' Previous accounting date 2 volume ,Accd 2' Window 3 Window 4 Window 3 Window 4 Previous accounting date 1 energy Date of next accounting date 1 Accounting date 2 energy Next accounting date 2 energy Previous accounting date 2 energy Date of next accounting date 2 Window 2 Secondary address Primary address 1 Primary address 2 Configuration (pulse value) No. of the mounted module at port 1 No. of the mounted module at port 2 (Sequence will be shown only in meters with integrated radio) Checksum Window 2 Accumulated values pulse input 1 Accumulated values pulse input 2 ,PPI' pulse value 1 ,PPI' pulse value 2 [off] = not active 10 VD.SH.L2.02 © Danfoss 08/2011 DEN-SMT/PL SONOMETERTM2100 – Ultrasonic energy meter Data Sheet Loop “5” Tariff loop Sequence Window 1 Window 2 Window 3 Window 4 Window 5 Window 6 Window 7 Window 4 [off] Window 5 Window 6 Window 7 energy energy energy volume volume volume energy volume The tariff loop is switched off as a standard at the heat meter or meter for cooling. Loop Sequence Window 1 Window 2 “6” Monthly value loop 6.1 6.2 6.3 ... 6.24 ,LOG’ ,LOG’ ,LOG’ date last month date month - 1 date month - 2 ,LOG’ date month - 23 Window 3 [off] ... [off] = not active Simple operation A push-button mounted on the front of the calculator is used to switch to the various displays. The button can be pressed for a short or long time. A short press of the button ( < 3 seconds) switches to the next display within a loop and a long press ( > 3 seconds) switches to the next display loop. The “Energy” window (sequence 1.1) in the main loop is the basic display. DEN-SMT/PL VD.SH.L2.02 © Danfoss 08/2011 The calculator switches automatically to power save mode if the button is not pressed for approx. 4 minutes and returns to the basic display when the button is pressed again. The loop settings can be programmed to suit the customer’s individual requirements using the IZAR@SET software. 11 Data Sheet SONOMETERTM2100 – Ultrasonic energy meter SONO 1500 CT Power supply The standard version contains a 3.0 VDC lithium battery (max. 90 °C) with a lifetime of 11 years (depends on configuration). It’s also possible to use an external supply e.g. from a calculator. Characteristic for ext. power supply: - Power supply 3.0 ... 5.5 V DC; - Power consumption < 130 mAh per year; - Impulse current < 10 mA. Pulse output The flow sensor has two pulse output. - Volume pulse output; - Output for testing (high resolution pulse output for test laboratories, temporary limited) and for communication. The output for testing is a combined impulse output. That means the flow sensor can emit a high resolution test impulse or the flow sensor can communicate via the same output. By using an adapter the flow sensor can be read out via the IZAR@SET Software. The electrical information for the volume pulses of the model for heating is described as follows: The pulse output is by default not galvanic. A galvanic pulse output is as an option available. The flow sensor has, by default, a 4-pin impulse cable with a length of 2.5 m. The maximal length is 10 m. Specification of the pulse output: Volume impulse output Power Supply Contact load Output frequency Pulse description Pulse values Pulse duration Battery supply External supply No galvanic insulation Galvanic insulation (standard) 3.0 V DC battery UCE ≤ 30 V UCE ≤ 30 V IC ≤ 20 mA with residual IC ≤ 1 mA with residual voltage of ≤ 0.5 V voltage of ≤ 0.5 V ≤ 20 Hz * Open Collector 1 ml ... 5000 l * (depends on qp) 1 ... 250 ms ± 10% pulse * duration ≤ pulse pause No galvanic insulation 3.0 – 5.5 V DC external supply UCE ≤ 30 V IC ≤ 20 mA with residual voltage of ≤ 0.5 V ≤ 150 Hz 1 ml ... 5000 l (depends on qp) 1 ... 250 ms ± 10% pulse duration ≤ pulse pause Cable allocation White core + volume impulse Yellow core test impulse / communication Blue core GND Brown core reserved - volume impulse + power supply *depends on the average flow during the lifetime of the flow sensor, on the pulse duration and on the pulse value. 12 VD.SH.L2.02 © Danfoss 08/2011 DEN-SMT/PL Data Sheet Mounting SONO 1500 CT DEN-SMT/PL SONOMETERTM2100 – Ultrasonic energy meter The flow sensor is installed either in the high temperature pipe or low temperature pipe as indicated on the data plate. The flow sensor has to be installed so that the direction of flow corresponds to the direction of the arrow on the flow sensor housing. Ensure that the flow sensor is always filled with liquid after installation. Calming sections before and after the flow sensor are not necessary. The flow sensor can be installed in both horizontal and vertical pipe sections, but always so, that air bubbles cannot collect in the flow sensor. VD.SH.L2.02 © Danfoss 08/2011 Make sure the flow sensor is installed sufficiently far away from possible sources of electromagnetic interference (switches, electric motors, fluorescent lamps, etc.). It is recommended that stop valves are fitted before and after the flow sensor to simplify dismantling. The flow sensor should be installed in a convenient position for service and operating personnel. 13 SONOMETERTM2100 – Ultrasonic energy meter Data Sheet Dimensions SONO 1500 CT Nominal size L [mm] L1 [mm] L2 [mm] B [mm] H [mm] h [mm] AGZ qp = 0.6 m³/h qp = 3.5 m³/h qp = 2.5 m³/h 110 190 130 230 190 290 190 190 110 190 130 230 190 290 190 190 54.5 14.5 56.5 18 56.5 18 56.5 47.5 54.5 14.5 56.5 18 56.5 18 G¾B DN 15 G1B DN 20 G1B DN 20 FL DN 20 G¾B DN 15 G1B DN 20 R¾ 0.63 105 14 95 75 2.7 R½ 0.6 R¾ 0.61 AGV R½ R¾ D [mm] d [mm] F [mm] K [mm] Weight [kg] 0.6 0.61 FL - flanged connection DEN-SMT/PL qp = 1.0 / 1.5 m³/h qp = 6.0 m³/h 190 290 190 190 260 380 260 260 260 260 260 380 260 260 260 260 56.5 47.5 130 230 90 65.5 56.5 18 56.5 18 56.5 47.5 61 23 61 50 61 62.5 61 23 61 50 61 62.5 G1B DN 20 FL DN 20 G1B DN 20 G1B DN 20 FL DN 25 FL DN 32 G1¼B DN25 FL DN 25 FL DN 32 R¾ 0.63 105 14 95 75 2.7 R¾ 0.61 R¾ 0.63 114 14 100 85 3.35 139 18 125 100 4.65 R1 1.35 114 14 100 85 3.35 139 18 125 100 4.65 VD.SH.L2.02 © Danfoss 08/2011 FL G1¼B DN 20 DN 25 105 14 95 75 2.7 R1 1.35 14 SONOMETERTM2100 – Ultrasonic energy meter Data Sheet Dimensions, continued SONO 1500 CT Nominal size qp = 10 m³/h L [mm] 300 L1 [mm] 400 L2 [mm] B [mm] H [mm] 66.5 h [mm] 33 AGZ G2B DN40 AGV R1½ D [mm] d [mm] F [mm] K [mm] Weight [kg] 2.6 FL- flanged connection 300 300 qp = 15 m³/h qp = 25 m³/h qp = 40 m³/h qp = 60 m³/h 270 270 300 300 300 300 360 360 79 85 FL DN 65 184 18 170 145 9.45 86.5 92.5 FL DN80 200 19 185 160 11.1 96.5 108 FL DN100 235 22 216 190 16.9 90 65.5 66 69 FL DN 40 148 18 138 110 6.6 71.5 73.5 FL DN 50 163 18 147 125 7.45 Temperature sensors Designation Type Dimension D (mm) L (mm) Direct mounted Pt 500 ø 5.2 45 ø 5.2 45 ø 6.0 50 Pocket sensor Pt 500 Sensor pockets Type Sensor dimension Brass (mm) Stainless steel ø 5.2 ø 6.0 ø 6.0 L1 (mm) 47 60 93 128 47 92 128 98 133 168 223 L (mm) 35 52 85 120 40 85 120 85 120 155 210 Length 15 VD.SH.L2.02 © Danfoss 08/2011 DEN-SMT/PL Data Sheet SONOMETERTM2100 – Ultrasonic energy meter INFOCAL 8 16 VD.SH.L1.02 Produced by Danfoss A/S © 08/2011 Data sheet INFOCAL 8 Energy calculator Description/Application The INFOCAL 8 is an energy calculator e.g. for combination with SONO 1500 CT especially designed for heating, cooling or combined heating/cooling application in local and district energy systems. MID examination certificate no.: DE-10-MI004-PTB008 The INFOCAL 8 has been approved according to MID. Features - Lithium battery with lifetime typical 11 years or 16 years optional (depending on selected functionality and connected flow sensor) - Temperature range: –20 to +190 °C - Power save mode - NOWA test capability - connection possibility of 2- and 4-wire temperature sensor pairs - Remote reading via M-Bus, L-Bus, RS 232, RS 485, Radio or optical interface - Integrated Radio 868 MHz, Open Metering Standard (OMS) - Individual remote reading (Automatic Meter Reading) with add on modules Plug&Play - 2 communication ports (e.g. M-Bus + pulse input) - Improved radio performance - Individual tariff functions - History memory for 24 months - Extensive diagnostic displays - Dedicated district energy application telegram - Suitable for Danfoss ECL Comfort controller and ECL 310 internet portal connection - IZAR@SET parameterization software on Windows basis guarantees optimum adaptation to the user’s specific needs DEN-SMT/PL VDSHK202_INFOCAL_8-DS-1303-EN.indd 1 VD.SH.K2.02 © Danfoss 03/2013 1 2013-03-04 09:13:54 Data Sheet INFOCAL 8 – Energy calculator Description/Application, continued The INFOCAL 8 is able to handle 3 types of applications: DEN-SMT/PL VDSHK202_INFOCAL_8-DS-1303-EN.indd 2 District heating/boiler application Combined heating/cooling application Chilled water application VD.SH.K2.02 © Danfoss 03/2013 2 2013-03-04 09:13:55 INFOCAL 8 – Energy calculator Data Sheet Ordering: The standard codes are used for ordering. Heating application INFOCAL 8 standard codes 1⁾: Code no. Norminal flow rate range of flow sensor Pulse value Installation Module Energy unit Temperature sensor cable length 087G6220 qp 0.6 - 2.5 m³/h 1 liter / pulse low temperature Pulse output kWh (without digit after comma) 2m 087G6221 qp 3.5 - 25 m³/h 10 liter / pulse low temperature Pulse output MWh (with 2 digit after comma) 2m 087G6222 qp 40 - 60 m³/h 100 liter / pulse low temperature Pulse output MWh (with 1 digit after comma) 2m 087G1307 qp 60 – 200 m³/h 2.5 liter / pulse low temperature M-Bus MWh (with 1 digit after comma) 5m 087G1308 qp 150 - 800 m³/h 10 liter / pulse low temperature M-Bus MWh (with 1 digit after comma) 5m 087G1311 qp 560 -1900 m³/h 50 liter / pulse low temperature M-Bus MWh (with 1 digit after comma) 5m 087G1324 qp 1475 – 7600 m³/h 100 liter / pulse low temperature M-Bus MWh (with 1 digit after comma) 5m 1⁾These codes are EN version with A-cell battery. For more characteristics of each code, please contact Danfoss local sales company. More standard codes are available regarding cooling meter, combined heating/cooling meter, high temperature installation, power supply and modules. 3 VDSHK202_INFOCAL_8-DS-1303-EN.indd 3 VD.SH.K2.02 © Danfoss 03/2013 DEN-SMT/PL 2013-03-04 09:13:55 Data Sheet INFOCAL 8 – Energy calculator Ordering continued Modules Communication Function Supply voltage Code No. 087G6027 087G6035 087G6029 087G6032 087G6034 087G6041 087G6037 087G6039 087G6020 087G6022 087G6024 087G6025 Designation M-Bus module L-Bus module (use for external radio) RS232 module RS485 module Analogue output module (4-20 mA) Combined module (2 pulse inputs/ 1 pulse output) Pulse input module (2 inputs) Pulse output module (2 outputs) battery 3.6 V DC (A-cell) battery 3.6 V DC (D-cell) mains unit 230 V AC mains unit 24 V AC Accessories Temperature sensors Temperature sensors (pair) Pt 500 / ø 5.2 mm / 10 m cable, MID Ball valves Adapter for mounting temperature sensors Software The IZAR@SET parameterization software on windows basis is a convenient tool for handling the energy meter. DEN-SMT/PL VD.SH.K2.02 © Danfoss 03/2013 VDSHK202_INFOCAL_8-DS-1303-EN.indd 4 pair Code No. 1 087G6048 Dimension (IG) G ½’’ G ¾’’ Set 12 pcs 12 pcs Code No. 087G6068 087G6069 G 1’’ 12 pcs 087G6070 Coupling thread Sensor thread Set Code No. R ½’’ M 10 x 1 32 pcs 087G6076 It is used for: -commissioning - reading out measured values - printing out energy meter logs - energy meter configuration - application analysis - print the meter protocol 4 2013-03-04 09:13:56 INFOCAL 8 – Energy calculator Data Sheet Technical data INFOCAL 8 Basic data Display indication Temperature Ambient class Protection class Display Units Total values Values displayed Ambient Storage Temperature sensors Sensor current Input Measuring cycle Max. temp. difference Min. temp. difference Starting temp. difference Absolute temp. measuring range Battery supply Mains supply Design and function class E1 +M1 IP 54 LCD, 8-digit MWh - kWh - GJ - Gcal - MBtu - gal - GMP - °C - °F - m³ - m³/h 99 999 999 - 9999 999.9 - 999 999.99 - 99 999.999 Power - energy - flow rate - temperature - volume 0 - 55 °C -25 - +70 Pt 500 with 2-wire leads Type < 10 m mA Pt 500 peak < 2; rms < 0.012 Mains unit supply: 1 Ts A-cell battery: 16; D-cell battery: 4 ∆θmaxK 177 ∆θminK 3 ∆θK 0.125 θ°C -20...190 3.6 VDC, A cell, 11 years lifetime 3.6 VDC, D cell, 16 years lifetime 24 VAC, 230 VAC / 0.15 W The INFOCAL 8 is an ultrasonic energy meter especially designed for heating, cooling or combined heating/cooling application in local and district heating systems. Calculator The calculator contains all the necessary circuits for recording the flow rate and temperature as well as for calculating, logging and displaying the data. The calculator housing can be mounted directly on the volume measuring component or on the wall. At application with medium temperature above 90 °C or at temperatures Twater < Tenvironment the calculator has to be removed from the flowmeter. 5 VDSHK202_INFOCAL_8-DS-1303-EN.indd 5 VD.SH.K2.02 © Danfoss 03/2013 The calculator can be conveniently read from a single line 8-digit display with units and symbols. A push-button provides user-friendly control of the various display loops. All failures and faults are recorded automatically and shown on the LC display. To protect the reading data, all the relevant data are saved in a non-volatile memory (EEPROM). This memory saves the measured values, device parameters and types of error at regular intervals. DEN-SMT/PL 2013-03-04 09:13:56 Data Sheet INFOCAL 8 – Energy calculator Design and function, continued Temperature Sensors Pairs of Pt 500 ø5.2 mm temperature sensors with 2-wire or 4-wire leads are used. Cable length 2 m, 3 m, 5 m or 10 m are available. Integrated Radio Integrated Radio is an interface for communication with radio receiver. - Frequency band: 868 MHz - Type of radio telegram: Open Metering Standard (OMS) - Transmission data updating: Online - no time delay between value measurement and data transmission - Data transmission: Unidirectional - Sending interval: 12...20 s; depending on length of telegram (duty cycle) Interfaces - Optical: ZVEI interface as standard, for communication and testing, M-Bus protocol. - M-Bus: Configurable telegram, according to EN13757-3. Data reading and parametrization are via two wires with polarity reversal protection. - L-Bus: Adapter for external radio module; configurable telegram, according to EN13757-3. Data reading and parametrization are via two wires with polarity reversal protection. M-Bus protocol. - RS232: Serial interface for communication with external devices. A special data cable is required. M-Bus protocol. - RS485: Serial interface for communication with external devices. Power supply with 12V ± 5V. M-Bus protocol. - Pulse output: Module with 2 Open Collector pulse outputs (potential-free), 4 Hz (pulse width 125ms), 100 Hz (pulse width ≥5ms), ratio: pulse duration / pulse break ~ 1:1. Configurable via IZAR@SET software. Possible pulse output values are Energy, Volume, Tariff energy 1, Tariff energy 2, Tariff condition 1, Tariff condition 2, Energy error and Volume error. - Pulse input: Module with 2 pulse inputs, max. 20 Hz with minimum pulse duration of 10 msec, input resistance 2.2 M Ohms, terminal voltage 3V DC, cable length up to maximum 10m. The pulse value and the unit is configurable for energy, water, gas or electrical meter by IZAR@ SET. Data can be transferred remotely. Also two accounting day’s are available for both inputs. - Combined pulse input / output: Module with 2 pulse inputs and 1 pulse output. Configurable via IZAR@SET software. - Analogue output: Module for 4...20 mA with 2 programmable passive outputs, programmable value in case of error. Output values can be power, flow rate, temperatures. Configurable via IZAR@SET software. DEN-SMT/PL VDSHK202_INFOCAL_8-DS-1303-EN.indd 6 VD.SH.K2.02 © Danfoss 03/2013 Slot 1 -Analogue output module (4-20mA) - Combined module (2 pulse inputs / 1 pulse output) - Pulse input module (2 inputs) - M-Bus module - L-Bus module (use for external radio) - RS232 module - RS485 module Slot 2 - Pulse output module - Combined module (2 pulse inputs / 1 pulse output) - Pulse input module (2 inputs) - M-Bus module - L-Bus module (use for external radio) - RS232 module - RS485 module Event Memory Events such as changes and faults are stored in a non-volatile memory with a capacity of up to 127 entries. The following events are recorded: - Checksum error - Temperature measurement error - Start and end of test mode - Changing of the main configuration Monthly Memory The INFOCAL 8 has a history memory of 24 months. The following values are stored in the EEPROM on the programmable interval (daily, weekly, monthly): - Date/ Time - Cumulated energy - Tariff energy 1 - Tariff energy 2 - Tariff definition 1 - Tariff definition 2 - Cumulated volume - Error hour counter - Value of max. flow - Time max. flow - Date max. flow - Value of max. power - Time max. power - Date max. power - Pulse input counter 1 - Pulse input counter 2 - Pulse 1 definition - Pulse 2 definition - Operating days - Max. forward temperature - Time max. forward temperature - Date max. forward temperature - Max. return temperature - Time max. return temperature - Date max. return temperature 6 2013-03-04 09:13:56 Data Sheet INFOCAL 8 – Energy calculator Design and function, continued Log Memory The large two log memory blocks are used to store consumption values. The storage frequency can be selected from various storage intervals (1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, 60 minutes or the default setting of 24 hours, Day in the month, Day of the week, (1024 seconds), 15th or end of month). The data saved in the log memory can be used for the following analyses: - Reading the calculator on a certain day. Example: If the day for reading is 01.10, the calculator reading is displayed for the period from 01.10 of the previous year to 30.09 of the current year. - Comparison of the last consumption period with the preceding period Extract of possible log memory settings Memory Storage block interval area 1 1 hour 24 area 2 hours area 1 1 hour area 2 24 hours Values Error status, overload time temperature, overload time flow rate, supply temperature, return temperature, date and time, energy, tariff energy 1, tariff energy 2, tariff definition 1, tariff definition 2, volume, error day counter Accounting date The calculator includes two independent memories in which the accumulated energy at two programmable dates is stored. - Last Accounting Date; - Last but one Accounting Date; - Values stored: - Energy; - Volume; - Tariff counter 1; - Tariff counter 2; - Pulse counter 1; - Pulse counter 2; - Date. Max. Actual Values Memories The calculator creates maximum values for power, flow rate and temperatures based on consumption time, which are stored in the EEPROM. The integration intervals are adjustable to 6, 15, 30 or 60 minutes, 24 hours (and 1024 seconds). Default setting is 60 minutes. Date block size example 16 byte Number of data records 556 Recording period 23 days 16 byte 299 299 days 8 byte 1113 46 days 8 byte 599 599 days Tariff Function The calculator offers four optional tariff memories for monitoring plant load states for limit tariffs. Here it concerns threshold value tariffs. Extensive tariff conditions make it possible to adapt the calculator individually to the required customer-specific applications. The tariffs are separately configurable and independent from each other. Energy or time can be measured alternatively per tariff register dependent on the tariff mode adjusted in each case. With the “time triggered tariff function” (type Z) the switch-on time and the switch-off time are adjustable independent from each other for each day of the week in steps of 15 minutes. The following limit types are possible: (This example applies to the display at 3 digit after volume comma) Type ∆T -∆T TR TF P Q Description LIMIT LIMIT resolution Temperature difference 1 ... 255 °C 1 °C Negative temperature difference 1 ... 255 °C 1 °C Low temperature (low) 1 ... 255 °C 1 °C High temperature (high) 1 ... 255 °C 1 °C Power 1 ... 255 kW 1 kW Flow 100 ... 25 500 l/h 100 l/h “Theoretically Supply Energy” with return FE temperature of 0 °C Z “Time triggered” counting energy E “External” counting energy More detailed description concerning tariff functions on request. Display Control The readings are displayed on the calculator by a 8-digit LCD with units and symbols. 7 VDSHK202_INFOCAL_8-DS-1303-EN.indd 7 VD.SH.K2.02 © Danfoss 03/2013 DEN-SMT/PL 2013-03-04 09:13:56 Data Sheet INFOCAL 8 – Energy calculator Design and function, continued Loop Structure The INFOCAL 8 display has six loops. Some display windows consist of two (to maximum seven) displays that are shown alternately at 4-second intervals. Some pictures in loops or a complete loop can be deactivated separately. The main loop with the current data, e.g. for energy, volume and flow rate, is programmed as default setting. In the standard setting the loop no. 5 (tariff loop) is not activated. For quick visual guidance, the loops in the display are numbered from 1 to 6. Overview of Loops DEN-SMT/PL VDSHK202_INFOCAL_8-DS-1303-EN.indd 8 VD.SH.K2.02 © Danfoss 03/2013 8 2013-03-04 09:13:57 INFOCAL 8 – Energy calculator Data Sheet Informative Displays (Standard) Loop “1” Main loop Loop Sequence 1.1 1.2 1.3 1.4 2.8 Sequence 3.1 3.2 3.3 3.4 3.5 3.6 Window 1 Accumulated energy Volume Flow Power Forward / - return temperature Difference temperature Operating days Error status Display test Window 1 Accounting date 1 date Next accounting date 1 date Previous accounting date 1 date ,Accd 1' Accounting date 2 date Next accounting date 2 date Previous accounting date 2 date ,Accd 2' Window 1 Current date ,SEC_Adr' ,Pri_Adr 1' ,Pri_Adr 2' Installation position ,In0' 3.7 ,Port 1' 3.8 ,Port 2' 3.9 Status integrated radio 3.10 3.11 Sequence No. of error hours software version Window 1 4.1 ,In1' 4.2 ,In2' 1.5 1.6 1.7 1.9 1.10 Sequence 2.1 2.2 2.3 “2” Accounting date loop 2.4 2.5 2.6 2.7 Loop “3“ Info loop Loop “4” Pulse input loop Window 2 Window 3 Window 4 Window 2 Accounting date 1 energy Window 3 [off] Accounting date 1 volume Window 4 ,Accd 1A' Next accounting date 1 energy Next accounting date 1 volume ,Accd 1L' Previous accounting date 1 volume ,Accd 1' Accounting date 2 volume ,Accd 2A' Next accounting date 2 volume ,Accd 2L' Previous accounting date 2 volume ,Accd 2' Window 3 Window 4 Window 3 Window 4 Previous accounting date 1 energy Date of next accounting date 1 Accounting date 2 energy Next accounting date 2 energy Previous accounting date 2 energy Date of next accounting date 2 Window 2 Secondary address Primary address 1 Primary address 2 Configuration (pulse value) No. of the mounted module at port 1 No. of the mounted module at port 2 (Sequence will be shown only in meters with integrated radio) Checksum Window 2 Accumulated values pulse input 1 Accumulated values pulse input 2 ,PPI' pulse value 1 ,PPI' pulse value 2 [off] = not active 9 VDSHK202_INFOCAL_8-DS-1303-EN.indd 9 VD.SH.K2.02 © Danfoss 03/2013 DEN-SMT/PL 2013-03-04 09:13:57 INFOCAL 8 – Energy calculator Data Sheet Loop “5” Tariff loop Sequence Window 1 Window 2 Window 3 Window 4 Window 5 Window 6 Window 7 Window 4 [off] Window 5 Window 6 Window 7 energy energy energy volume volume volume energy volume The tariff loop is switched off as a standard at the heat meter or meter for cooling. Loop Sequence Window 1 Window 2 “6” Monthly value loop 6.1 6.2 6.3 ... 6.24 ,LOG’ ,LOG’ ,LOG’ date last month date month - 1 date month - 2 ,LOG’ date month - 23 Window 3 [off] ... [off] = not active Simple operation A push-button mounted on the front of the calculator is used to switch to the various displays. The button can be pressed for a short or long time. A short press of the button ( < 3 seconds) switches to the next display within a loop and a long press ( > 3 seconds) switches to the next display loop. The “Energy” window (sequence 1.1) in the main loop is the basic display. DEN-SMT/PL VDSHK202_INFOCAL_8-DS-1303-EN.indd 10 VD.SH.K2.02 © Danfoss 03/2013 The calculator switches automatically to power save mode if the button is not pressed for approx. 4 minutes and returns to the basic display when the button is pressed again. The loop settings can be programmed to suit the customer’s individual requirements using the IZAR@SET software. 10 2013-03-04 09:13:57 Data Sheet INFOCAL 8 – Energy calculator Dimensions INFOCAL 8 Temperature sensors Designation Type Dimension D (mm) L (mm) Direct mounted Pt 500 ø 5.2 45 Pocket sensor Pt 500 ø 5.2 45 Sensor pockets Type Sensor dimension (mm) Brass Stainless steel ø 5.2 ø 5.2 L1 (mm) 47 60 93 128 98 133 168 223 L (mm) 35 52 85 120 85 120 155 210 Length 11 VDSHK202_INFOCAL_8-DS-1303-EN.indd 11 VD.SH.K2.02 © Danfoss 03/2013 DEN-SMT/PL 2013-03-04 09:13:57 Data Sheet INFOCAL 8 – Energy calculator 12 VD.SH.K2.02 © Danfoss 03/2013 VDSHK202_INFOCAL_8-DS-1303-EN.indd 12 Produced by Danfoss A/S © 03/2013 2013-03-04 09:14:01 Data sheet SONO 1500 CT Ultrasonic flow sensor Description/Application The SONO 1500 CT is an ultrasonic flow sensor especially designed for heating, cooling or combined heating/cooling application in local and district energy systems. The SONO 1500 CT has been approved according to MID in class 2 and 3. MID examination certificate no.: DE-09-MI004-PTB011 DEN-SMT/PL Features: -1st approval in Europe for ultrasonic flow sensor with dynamic range of qi/qp 1:250 in class 2 (qp 1.5 / 2.5 / 6 / 10 / 15 / 25 / 40 / 60 m³/h) - Complete dynamic range: ≥ 1:1500 - Lithium battery with a lifetime of 11 years or external supply - Temperature range: 5 - 90 °C / 130 °C / 150 °C - Overload temperature up to 150 °C (sizes qp 0.6 up to 2.5 m³/h) - Available in nominal sizes: qp 0.6 / 1.0 / 1.5 / 2.5 / 3.5 / 6 / 10 / 15 / 25 / 40 / 60 m³/h - Unique free-beam principle - Swirl-free flow around reflector - Robust stainless steel reflector - All sizes also available in PN 25 - No calming sections necessary in the inlet and/ or outlet (standard installation) - NOWA test capability - Connection to calculator with pulse defined values - Insensitive against magnetite - Installation in any position - Free selectable pulse values VD.SH.M1.02 © Danfoss 03/2013 1 Data Sheet SONO 1500 CT - Ultrasonic flow sensor Ordering: The standard codes are used for ordering. Heating application SONO 1500 CT standard codes 1⁾ : Code no. Flow sensor Nominal pressure Cable length of flow sensor 087G1350 qp 0.6 m³/h / 110mm thread / DN 15 / G¾B / 1 liter/pulse PN16 2.5m 087G1351 qp 1.5 m³/h / 110mm thread / DN 15 / G¾B / 1 liter/pulse PN16 2.5m 087G1352 qp 1.5 m³/h / 130mm thread / DN 20 / G1B / 1 liter/pulse PN16 2.5m 087G1353 qp 2.5 m³/h / 130mm thread / DN 20 / G1B / 1 liter/pulse PN16 2.5m 087G1354 qp 3.5 m³/h / 260mm thread / DN 25 / G1¼B / 10 liter/pulse PN16 2.5m 087G1355 qp 6 m³/h / 260mm thread / DN 25 / G1¼B / 10 liter/pulse PN16 2.5m 087G1356 qp 10 m³/h / 300mm thread / DN 40 / G2B / 10 liter/pulse PN16 2.5m 087G1357 qp 6 m³/h / 260mm flange DN 32 / 10 liter/pulse PN25 2.5m 087G1358 qp 10 m³/h / 300mm flange DN 40 / 10 liter/pulse PN25 2.5m 087G1359 qp 15 m³/h / 270mm flange DN 50 / 10 liter/pulse PN25 5m 087G1360 qp 25 m³/h / 300mm flange DN 65 / 10 liter/pulse PN25 5m 087G1361 qp 40 m³/h / 300mm flange DN 80 / 100 liter/pulse PN25 5m 087G1362 qp 60 m³/h / 360mm flange DN 100 / 100 liter/pulse PN25 5m 1⁾ These codes are EN version flow sensor with external power supply. For more characteristics of each code, please contact Danfoss local sales company. More standard codes are available regarding cooling application. DEN-SMT/PL VD.SH.M1.02 © Danfoss 03/2013 2 Data Sheet SONO 1500 CT - Ultrasonic flow sensor Technical data Flow rate Nominal Maximum Standard minimum Extended minimum 5⁾ Starting Nominal Diameter Operating Maximum pressure Temperature range heating battery supplied Temperature range heating external supplied Temperature range cooling Medium Pressure loss At qp Overall length Volume Pulse value Test Supply Operating voltage Enviromental class Protect.ion class Ambient temperature Flow rate Nominal Maximum Standard minimum Extended minimum 5⁾ Starting Nominal qpm3/h qsm3/h 0.6 1.2 1.5 3 2.5 5 3.5 7 6 12 qil/h 6 15 25 35 60 qi − 6 10 − 24 l/h l/h DNmm PNbar Pulse value Volume Test Supply Operating voltage Enviromental class 2.5 20 16 / 25 15 4 20 20 25 16 / 25 25 16 / 25 7 25 25 7 32 16 / 25 25 25 32 16 / 25 25 5 ... 90 / 5 ... 105 1⁾ °C Δpmbar mm l/imp. ml/imp. 5 ... 150 1⁾ 5 ... 130 110 85 130 190 110 5 UN °C 5 ... 90 / 5 ... 105 1⁾ circulation water (pH: 7 - 10) 75 100 130 190 130 190 0.001...5000 (depend on qp) 10 20 battery supply: 3.0 V DC external supply: 3.0..5.5 V DC 2⁾ EN 1434 class C / MID class E1 + M1 IP 54 (heating) / IP 65 (cooling) 5...55 44 260 128 260 20 50 qp m3/h qsm3/h 10 20 15 30 25 50 40 80 60 120 qil/h 100 150 250 400 600 qil/h 404⁾ / 100 604⁾ / 150 1004⁾ / 250 1604⁾ / 400 2404⁾ / 600 l/h DNmm 20 40 40 50 50 65 80 80 120 100 Diameter Operating Maximum PNbar pressure Temperature range heating battery supplied Temperature range heating - °C external supplied Temperature range cooling Medium Δpmbar Pressure loss At qp Overall length 1 15 25 5 ... 90 / 5 ... 105 1⁾ 5 ... 150 1⁾ 95 80 5 ... 90 / 5 ... 105 1⁾ circulation water (pH: 7 - 10) 75 mm 300 270 300 l/imp. ml/imp. 100 150 UN 0.001...5000 (depend on qp) 250 battery supply: 3.0 V DC external supply: 3.0..5.5 V DC 2⁾ EN 1434 class C / MID class E1 + M1 80 75 300 360 250 500 ⁾Only in rising or falling pipes or tilted installation. ⁾For medium temperatures above 90 °C, the flow sensor must be equipped with an external supply. ⁾Acc. to EN 1434 6.17. 4 ⁾Only for horizontal installation. ⁵⁾ Extended minimum flow rate for dynamic range of 1:250. Available on request. 1 2 3 3 VD.SH.M1.02 © Danfoss 03/2013 DEN-SMT/PL Data Sheet SONO 1500 CT - Ultrasonic flow sensor Pressure loss graph Function Measuring accuracy Class 2 Power supply The standard version contains a 3.0 VDC lithium battery (max. 90 °C) with a lifetime of 11 years (depends on configuration). It’s also possible to use an external supply e.g. from a calculator. Characteristic for ext. power supply: - Power supply 3.0 ... 5.5 V DC; - Power consumption < 130 mAh per year; - Impulse current < 10 mA. Pulse output The flow sensor has two pulse output. - Volume pulse output; - Output for testing (high resolution pulse output for test laboratories, temporary limited) and for communication. The output for testing is a combined impulse output. That means the flow sensor can emit a high resolution test impulse or the flow sensor can communicate via the same output. By using an adapter the flow sensor can be read out via the IZAR@SET Software. The electrical information for the volume pulses of the model for heating is described as follows: The pulse output is by default not galvanic. A galvanic pulse output is as an option available. The flow sensor has, by default, a 4-pin impulse cable with a length of 2.5 m. The maximal length is 10 m. Specification of the pulse output: Volume impulse output Power Supply Contact load Output frequency Pulse description Pulse values Pulse duration Battery supply External supply No galvanic insulation Galvanic insulation (standard) 3.0 V DC battery UCE ≤ 30 V UCE ≤ 30 V IC ≤ 20 mA with residual IC ≤ 1 mA with residual voltage of ≤ 0.5 V voltage of ≤ 0.5 V ≤ 20 Hz * Open Collector 1 ml ... 5000 l * (depends on qp) 1 ... 250 ms ± 10% pulse * duration ≤ pulse pause No galvanic insulation 3.0 – 5.5 V DC external supply UCE ≤ 30 V IC ≤ 20 mA with residual voltage of ≤ 0.5 V ≤ 150 Hz 1 ml ... 5000 l (depends on qp) 1 ... 250 ms ± 10% pulse duration ≤ pulse pause Cable allocation White core + volume impulse Yellow core test impulse / communication Blue core GND Brown core reserved - volume impulse + power supply *depends on the average flow during the lifetime of the flow sensor, on the pulse duration and on the pulse value. DEN-SMT/PL VD.SH.M1.02 © Danfoss 03/2013 4 Data Sheet SONO 1500 CT - Ultrasonic flow sensor Mounting The flow sensor is installed either in the high temperature pipe or low temperature pipe as indicated on the data plate. The flow sensor has to be installed so that the direction of flow corresponds to the direction of the arrow on the flow sensor housing. Ensure that the flow sensor is always filled with liquid after installation. Calming sections before and after the flow sensor are not necessary. The flow sensor can be installed in both horizontal and vertical pipe sections, but always so, that air bubbles cannot collect in the flow sensor. 5 VD.SH.M1.02 © Danfoss 03/2013 Make sure the flow sensor is installed sufficiently far away from possible sources of electromagnetic interference (switches, electric motors, fluorescent lamps, etc.). It is recommended that stop valves are fitted before and after the flow sensor to simplify dismantling. The flow sensor should be installed in a convenient position for service and operating personnel. DEN-SMT/PL Data Sheet SONO 1500 CT - Ultrasonic flow sensor Dimensions Nominal size qp = 0.6 m³/h qp = 1.5 m³/h L [mm] L1 [mm] L2 [mm] B [mm] H [mm] h [mm] 110 190 130 230 190 290 190 190 110 190 130 230 190 290 190 190 54.5 14.5 56.5 18 56.5 18 56.5 47.5 54.5 14.5 56.5 18 56.5 18 AGZ G¾B DN 15 G1B DN 20 G1B DN 20 FL DN 20 G¾B DN 15 G1B DN 20 R¾ 0.63 105 14 95 75 2.7 R½ 0.6 R¾ 0.61 AGV R½ R¾ D [mm] d [mm] F [mm] K [mm] Weight [kg] 0.6 0.61 FL - flanged connection DEN-SMT/PL qp = 3.5 m³/h qp = 2.5 m³/h qp = 6.0 m³/h 190 290 190 190 260 380 260 260 260 260 260 380 260 260 260 260 56.5 47.5 130 230 90 65.5 56.5 18 56.5 18 56.5 47.5 61 23 61 50 61 62.5 61 23 61 50 61 62.5 G1B DN 20 FL DN 20 G1B DN 20 G1B DN 20 FL DN 25 FL DN 32 G1¼B DN25 FL DN 25 FL DN 32 R¾ 0.63 105 14 95 75 2.7 R¾ 0.61 R¾ 0.63 114 14 100 85 3.35 139 18 125 100 4.65 R1 1.35 114 14 100 85 3.35 139 18 125 100 4.65 VD.SH.M1.02 © Danfoss 03/2013 FL G1¼B DN 20 DN 25 105 14 95 75 2.7 R1 1.35 6 Data Sheet SONO 1500 CT - Ultrasonic flow sensor Dimensions, continued 7 VD.SH.M1.02 © Danfoss 03/2013 DEN-SMT/PL Data Sheet 8 SONO 1500 CT - Ultrasonic flow sensor VD.SH.M1.02 Produced by Danfoss A/S © 03/2013 Data sheet SONOMETERTM1100 Ultrasonic compact energy meter Description/Application The SONOMETER™1100 is an ultrasonic static compact energy meter especially designed for heating, cooling or combined heating/cooling application in local and district energy systems. MID examination certificate no. : DE-10-MI004-PTB003 The SONOMETER™1100 as a compact energy meter consists of the following components: - Ultrasonic flow sensor; - Calculator with integral hardware and software for measuring flow rate, temperature and energy consumption; - Pair of temperature sensors. Features - 1st. approval in Europe for ultrasonic energy meter with dynamic range of qi/qp 1 : 250 in class 2 (qp 1.5 / 2.5 / 6 / 10 / 15 / 25 / 40 / 60 m³/h) - Complete dynamic range: ≥ 1 : 1500 - Lithium battery, 230 V AC or 24 V AC mains unit - Battery lifetime 11 years (16 years optional) - Unique free- beam principle - Improved service-friendly energy meter design - Housings with thread and flange (PN 16 / 25) - Can be configured for heating, cooling or combined heating/cooling application - Temperature range: 5 - 130 / 150 °C - Overload temperature up to 150 °C (qp= 0.6 - 2.5 m3/h) - Swirl-free flow around reflector - Lower pressure loss - Robust stainless steel reflector - Insensitive to dirt - Available in nominal sizes qp 0.6 / 1.0 / 1.5 / 2.5 / 3.5 / 6 / 10 / 15 / 25 / 40 / 60 m³/h Special Features - Power save mode - NOWA test capability - Remote reading via M-Bus, L-Bus, RS 232, RS 485, Radio or optical interface - Integrated Radio 868 MHz, Open Metering Standard (OMS) - Individual remote reading (Automatic Meter Reading) with add on modules Plug&Play - 2 communication ports (e.g. M-Bus + pulse input) - Improved radio performance - Individual tariff functions - History memory for 24 months - Extensive diagnostic displays - Dedicated district energy application telegram - Suitable for Danfoss ECL Comfort controller and ECL 310 internet portal connection - IZAR@SET parameterization software on Windows basis guarantees optimum adaptation to the user’s specific needs - Approved according to MID in class 2 and 3, and PTB K 7.2 for cooling - No calming sections necessary in the inlet and/or outlet (standard installation) DEN-SMT/PL VD.SH.J5.02 © Danfoss 03/2013 1 SONOMETERTM1100 – Ultrasonic energy meter Data Sheet Ordering: The standard codes are used for ordering. Heat meter standard codes 1⁾: Code no. Flow sensor Nominal pressure Cable length 2⁾ Module 087G1040 qp 0.6 m³/h / 110mm thread / DN 15 / G¾B PN16 1.5m M-Bus kWh (without digit after comma) 2m 087G1041 qp 1.5 m³/h / 110mm thread / DN 15 / G¾B PN16 1.5m M-Bus kWh (without digit after comma) 2m 087G1042 qp 1.5 m³/h / 130mm thread / DN 20 / G1B PN16 1.5m M-Bus kWh (without digit after comma) 2m 087G1043 qp 2.5 m³/h / 130mm thread / DN 20 / G1B PN16 1.5m M-Bus kWh (without digit after comma) 2m 087G1044 qp 3.5 m³/h / 260mm thread / DN 25 / G1¼B PN16 1.5m M-Bus kWh (without digit after comma) 2m 087G1045 qp 6 m³/h / 260mm thread / DN 25 / G1¼B PN16 1.5m M-Bus kWh (without digit after comma) 2m 087G1046 qp 10 m³/h / 300mm thread / DN 40 / G2B PN16 1.5m M-Bus MWh (with 3 digit after comma) 2m 087G1047 qp 6 m³/h / 260mm flange DN 32 PN25 1.5m M-Bus kWh (without digit after comma) 2m 087G1048 qp 10 m³/h / 300mm flange DN 40 PN25 1.5m M-Bus MWh (with 3 digit after comma) 2m 087G1049 qp 15 m³/h / 270mm flange DN 50 PN25 3m M-Bus MWh (with 3 digit after comma) 3m 087G1050 qp 25 m³/h / 300mm flange DN 65 PN25 3m M-Bus MWh (with 3 digit after comma) 3m 087G1051 qp 40 m³/h / 300mm flange DN 80 PN25 3m M-Bus MWh (with 2 digit after comma) 3m 087G1052 qp 60 m³/h / 360mm flange DN 100 PN25 3m M-Bus MWh (with 2 digit after comma) 3m 087G1118 qp 0.6 m³/h / 110mm thread / DN 15 / G¾B PN16 1.5m Radio OMS kWh (without digit after comma) 2m 087G1119 qp 1.5 m³/h / 110mm thread / DN 15 / G¾B PN16 1.5m Radio OMS kWh (without digit after comma) 2m 087G1120 qp 1.5 m³/h / 130mm thread / DN 20 / G1B PN16 1.5m Radio OMS kWh (without digit after comma) 2m 087G1121 qp 2.5 m³/h / 130mm thread / DN 20 / G1B PN16 1.5m Radio OMS kWh (without digit after comma) 2m 087G1122 qp 3.5 m³/h / 260mm thread / DN 25 / G1¼B PN16 1.5m Radio OMS kWh (without digit after comma) 2m 087G1123 qp 6 m³/h / 260mm thread / DN 25 / G1¼B PN16 1.5m Radio OMS kWh (without digit after comma) 2m 087G1124 qp 10 m³/h / 300mm thread / DN 40 / G2B PN16 1.5m Radio OMS MWh (with 3 digit after comma) 2m 087G1125 qp 6 m³/h / 260mm flange DN 32 PN25 1.5m Radio OMS kWh (without digit after comma) 2m 087G1126 qp 10 m³/h / 300mm flange DN 40 PN25 1.5m Radio OMS MWh (with 3 digit after comma) 2m 087G1127 qp 15 m³/h / 270mm flange DN 50 PN25 3m Radio OMS MWh (with 3 digit after comma) 3m 087G1128 qp 25 m³/h / 300mm flange DN 65 PN25 3m Radio OMS MWh (with 3 digit after comma) 3m 087G1129 qp 40 m³/h / 300mm flange DN 80 PN25 3m Radio OMS MWh (with 2 digit after comma) 3m 087G1130 qp 60 m³/h / 360mm flange DN 100 PN25 3m Radio OMS MWh (with 2 digit after comma) 3m Energy unit Cable length 3⁾ 1⁾ These codes are EN version Heat meter with A-cell battery and ‘low temperature’ installation. For more characteristics of each code, please contact Danfoss local sales company. 2⁾ Cable length between calculator and flow sensor. 3⁾ Cable lengh of temperature sensor. More standard codes are available regarding cooling meter, combined heating/cooling meter, high temperature installation, power supply and modules. DEN-SMT/PL VD.SH.J5.02 © Danfoss 03/2013 2 Data Sheet SONOMETERTM1100 – Ultrasonic energy meter Ordering continued Modules Communication Function Supply voltage Code No. 087G6027 087G6035 087G6029 087G6032 087G6034 087G6041 087G6037 087G6039 087G6020 087G6022 087G6024 087G6025 Designation M-Bus module L-Bus module (use for external radio) RS232 module RS485 module Analogue output module (4-20mA) Combined module (2 pulse inputs/ 1 pulse output) Pulse input module (2 inputs) Pulse output module (2 outputs) battery 3.6 V DC (A-cell) battery 3.6 V DC (D-cell) mains unit 230 V AC mains unit 24 V AC Accessories Temperature sensors Temperature sensors (pair) Pt 500 / ø 5.2 mm / 10 m cable, MID Ball valves Adapter for mounting temperature sensors pair Code No. 1 087G6048 Dimension (IG) G ½’’ G ¾’’ Set 12 pcs 12 pcs Code No. 087G6068 087G6069 G 1’’ 12 pcs 087G6070 Coupling thread Sensor thread Set Code No. R ½’’ M 10 x 1 32 pcs 087G6076 Tailpieces Threaded Software 3 The IZAR@SET parameterization software on windows basis is a convenient tool for handling the energy meter. VD.SH.J5.02 © Danfoss 03/2013 Dimension (AGR x IG) R 1/2” x G 3/4 B R 3/4” x G 1 B R 1” x G 11/4 B Set Code No. 1 pc 1 pc 1 pc 087G6071 087G6072 087G6073 R 11/2” x G 2 B 1 pc 087G6074 It is used for: -commissioning - reading out measured values - printing out energy meter logs - energy meter configuration - application analysis - print the meter protocol DEN-SMT/PL SONOMETERTM1100 – Ultrasonic energy meter Data Sheet Technical data Flow rate ranges Diameter Nominal qp m3/h 0.6 1.5 2.5 3.5 6 10 15 25 40 60 1.2 3 5 7 12 20 30 50 80 120 6 15 25 35 60 100 150 250 400 600 Maximum qs m3/h Standard minimum qi l/h Extended minimum 3⁾ qi l/h − 6 10 − 24 401) / 100 60 / 150 100 / 150 160 2401) /6002) / 1200 Starting l/h 1 2.5 4 7 7 20 40 50 80 120 Nominal DN mm 15 50 65 80 100 Connection AGZ G ¾B G 1B FL G ¾B G 1B FL G 1B FL G 1¼B FL G 1¼B FL FL FL FL FL Tailpiece AGV R½ R¾ - R½ R¾ - R¾ - R1 - R1 - - - - - 25 16 / 25 25 16 / 25 25 16 / 25 25 25 25 25 25 Operating Maximum pressure PN bar 20 16 / 25 15 25 16 / 25 Flow sensor heating Temp. cooling range heat. /cool. 20 20 25 25 5...90 5...105 Δp mbar mm 85 110 130 36 / 75 190 110 130 100 190 130 190 Sensor current mA Measuring cycle T s 44 128 95 80 75 80 75 260 260 300 270 300 300 360 Pt 500 with 2-wire leads Pt 500 peak < 2; rms < 0.012 Mains unit supply: 1 A-cell battery: 16; D-cell battery: 4 Max. Δθmax temperature K difference 177 Min. Δθmin temperature K difference 3 Starting Δθ temperature K difference 0.125 Absolute temperature θ measuring °C range 1...180 Operating voltage UN 3.6 V DC (Lithium-battery) / 230 V AC / 24 V AC class E1 + M1 calculator: IP 54 flow sensor: IP 54 (heating) / IP 68 (cooling) Ambient storage temperature -25...+ 60 °C Type Static energy meter Measuring process Ultrasonic volume measurement Display LCD, 8-digit Units Display indication Total values MWh - kWh - GJ - Gcal - MBtu - gal - GMP - °C - °F - m³ - m³/h 99 999 999 - 9999 999.9 - 999 999.99 - 99 999.999 Values displayed 1) - 5...105 Protection class 2) R 1½ FL 5...150 Ambient class Basic features 40 G 2B 5...90 Temperature Type sensors Supply voltage 32 1) circulation water (pH-value: 7 - 10) At qp Overall length Input 25 5...130 °C Medium Pressure loss 32 1) Power - energy - flow rate - temperature - volume Only for horizontal installation Only in rising or falling pipes or tilted installation 3⁾ Extended minmum flow rate for dynamic range of 1:250. Available on request. Pressure loss graph DEN-SMT/PL VD.SH.J5.02 © Danfoss 03/2013 Measuring accuracy Class 2 4 Data Sheet SONOMETERTM1100 – Ultrasonic energy meter Design and function The SONOMETER™1100 as a compact energy meter consists of the following components: - Ultrasonic flow sensor; - Calculator with integral hardware and software for measuring flow rate, temperature and energy consumption; - Pair of temperature sensors. The calculator contains all the necessary circuits for recording the flow rate and temperature and for calculating, logging and displaying the data. The calculator housing can be mounted directly on the flow sensor or on the wall. The energy meter can be conveniently read from a single-line 8-digit display with units and symbols. A push-button provides user-friendly control of the various display loops. All failures and faults are recorded automatically and shown on the LC display. To protect the reading data, all the relevant data are saved in a non-volatile memory (EEPROM). This memory saves the measured values, device parameters and types of error at regular intervals. Ultrasonic flow sensor The ultrasonic technology of the flow sensor permits very high measuring accuracy and can be used in the supply or return line. The flow sensor meets the requirements of MID in class 2 and 3. The standard cable length between the calculator and the flow sensor is 1.5 m or 3 m (optional 5 m). Supply voltage: - Lithium battery 3.6 V DC A-cell (11 years typical lifetime) - Lithium battery 3.6 V DC D-cell (16 years typical lifetime) - Mains unit 230 V AC or 24 V AC with changeable backup battery Temperature Sensors Pairs of Pt 500 ø5.2 mm temperature sensors with 2-wire leads are used. Cable length 2 m, 3 m, 5 m or 10 m are available. Integrated Radio Integrated Radio is an interface for communication with radio receiver. - Frequency band: 868 MHz - Type of radio telegram: Open Metering Standard (OMS) - Transmission data updating: Online - no time delay between value measurement and data transmission - Data transmission: Unidirectional - Sending interval: 12...20 s; depending on length of telegram (duty cycle) Interfaces - Optical: ZVEI interface as standard, for communication and testing, M-Bus protocol. - M-Bus: Configurable telegram, according to EN13757-3. Data reading and parametrization are via two wires with polarity reversal protection. - L-Bus: Adapter for external radio module; configurable telegram, according to EN13757-3. Data reading and parametrization are via two wires with polarity reversal protection. M-Bus protocol. - RS232: Serial interface for communication with external devices. A special data cable is required. M-Bus protocol. - RS485: Serial interface for communication with external devices. Power supply with 12V ± 5V. M-Bus protocol. - Pulse output: Module with 2 Open Collector pulse outputs (potential-free), 4 Hz (pulse width 125ms), 100 Hz (pulse width ≥5ms), ratio: pulse duration / pulse break ~ 1:1. Configurable via IZAR@SET software. Possible pulse output values are Energy, Volume, Tariff energy 1, Tariff energy 2, Tariff condition 1, Tariff condition 2, Energy error and Volume error. 5 VD.SH.J5.02 © Danfoss 03/2013 - Pulse input: Module with 2 pulse inputs, max. 20 Hz with minimum pulse duration of 10 msec, input resistance 2.2 M Ohms, terminal voltage 3V DC, cable length up to maximum 10m. The pulse value and the unit is configurable for energy, water, gas or electrical meter by IZAR@SET. Data can be transferred remotely. Also two accounting day’s are available for both inputs. - Combined pulse input / output: Module with 2 pulse inputs and 1 pulse output. Configurable via IZAR@SET software. - Analogue output: Module for 4...20 mA with 2 programmable passive outputs, programmable value in case of error. Output values can be power, flow rate, temperatures. Configurable via IZAR@SET software. Slot 1 - Analogue output module (4-20mA) - Combined module (2 pulse inputs / 1 pulse output) - Pulse input module (2 inputs) - M-Bus module - L-Bus module (use for external radio) - RS232 module - RS485 module Slot 2 - Pulse output module - Combined module (2 pulse inputs / 1 pulse output) - Pulse input module (2 inputs) - M-Bus module - L-Bus module (use for external radio) - RS232 module - RS485 module Event Memory Events such as changes and faults are stored in a nonvolatile memory with a capacity of up to 127 entries. The following events are recorded: - Checksum error - Temperature measurement error - Ultrasonic operating time measurement errors - Start and end of test mode - Changing of the main configuration Monthly Memory The SONOMETER™1100 has a history memory of 24 months. The following values are stored in the EEPROM on the programmable interval (daily, weekly, monthly): - Date/ Time - Cumulated energy - Tariff energy 1 - Tariff energy 2 - Tariff definition 1 - Tariff definition 2 - Cumulated volume - Error hour counter - Value of max. flow - Time max. flow - Date max. flow - Value of max. power - Time max. power - Date max. power - Pulse input counter 1 - Pulse input counter 2 - Pulse 1 definition - Pulse 2 definition - Operating days - Max. forward temperature - Time max. forward temperature - Date max. forward temperature - Max. return temperature - Time max. return temperature - Date max. return temperature DEN-SMT/PL Data Sheet SONOMETERTM1100 – Ultrasonic energy meter Design and function, continued Log Memory The large two log memory blocks are used to store consumption values. The storage frequency can be selected from various storage intervals (1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, 60 minutes or the default setting of 24 hours, Day in the month, Day of the week, (1024 seconds), 15th or end of month). The data saved in the log memory can be used for the following analyses: - Reading the calculator on a certain day. Example: If the day for reading is 01.10, the calculator reading is displayed for the period from 01.10 of the previous year to 30.09 of the current year. - Comparison of the last consumption period with the preceding period Extract of possible log memory settings Memory Storage Date block size Values block interval example area 1 1 hour Error status, overload time temperature, 16 byte 24 overload time flow rate, supply area 2 16 byte hours temperature, return temperature, date area 1 1 hour and time, energy, tariff energy 1, tariff 8 byte energy 2, tariff definition 1, tariff definition 24 area 2 2, volume, error day counter 8 byte hours Max. Actual Values Memories The calculator creates maximum values for power, flow rate and temperatures based on consumption time, which are stored in the EEPROM. The integration intervals are adjustable to 6, 15, 30 or 60 minutes, 24 hours (and 1024 seconds). Default setting is 60 minutes. Tariff Function The calculator offers four optional tariff memories for monitoring plant load states for limit tariffs. Extensive tariff conditions make it possible to adapt the energy meter individually to the required customer-specific applications. The following limit types are possible: (This example applies to the display with 3 decimal places) Type ∆T TR TF P Q Z LIMIT LIMIT resolution 1 ... 255 °C 1 °C 1 ... 255 °C 1 °C 1 ... 255 kW 1 kW 100 ... 25 500 l/h 100 l/h 15 minutes Number of data records 556 Recording period 23 days 299 299 days 1113 46 days 599 599 days Display Control The readings are displayed on the calculator by a 8-digit LCD with units and symbols. Loop Structure The SONOMETER™1100 display has six loops. Some display windows consist of two (to maximum seven) displays that are shown alternately at 4-second intervals. Some pictures in loops or a complete loop can be deactivated separately. For quick visual guidance, the loops in the display are numbered from 1 to 6. The main loop with the current data, e.g. for energy, volume and flow rate is programmed as default setting. According to above table the energy or the time (in hours) how long the tariff condition is fulfilled will be stored in the tariff memories. DEN-SMT/PL VD.SH.J5.02 © Danfoss 03/2013 6 Data Sheet SONOMETERTM1100 – Ultrasonic energy meter Overview of Loops 7 VD.SH.J5.02 © Danfoss 03/2013 DEN-SMT/PL SONOMETERTM1100 – Ultrasonic energy meter Data Sheet Informative Displays (Standard) Loop “1” Main loop Loop Sequence 1.1 1.2 1.3 1.4 2.8 Sequence 3.1 3.2 3.3 3.4 3.5 Window 1 Accumulated energy Volume Flow Power Forward / - return temperature Difference temperature Operating days Error status Display test Window 1 Accounting date 1 date Next accounting date 1 date Previous accounting date 1 date ,Accd 1' Accounting date 2 date Next accounting date 2 date Previous accounting date 2 date ,Accd 2' Window 1 Current date ,SEC_Adr' ,Pri_Adr 1' ,Pri_Adr 2' Installation position 3.6 ,Port 1' 3.7 ,Port 2' 3.8 Status integrated radio 3.9 3.10 Sequence No. of error hours software version Window 1 4.1 ,In1' 4.2 ,In2' 1.5 1.6 1.7 1.9 1.10 Sequence 2.1 2.2 2.3 “2” Accounting date loop 2.4 2.5 2.6 2.7 Loop “3“ Info loop Loop “4” Pulse input loop Window 2 Window 3 Window 4 Window 2 Accounting date 1 energy Window 3 [off] Accounting date 1 volume Window 4 ,Accd 1A' Next accounting date 1 energy Next accounting date 1 volume ,Accd 1L' Previous accounting date 1 volume ,Accd 1' Accounting date 2 volume ,Accd 2A' Next accounting date 2 volume ,Accd 2L' Previous accounting date 2 volume ,Accd 2' Window 3 Window 4 Window 3 Window 4 Previous accounting date 1 energy Date of next accounting date 1 Accounting date 2 energy Next accounting date 2 energy Previous accounting date 2 energy Date of next accounting date 2 Window 2 Secondary address Primary address 1 Primary address 2 No. of the mounted module at port 1 No. of the mounted module at port 2 (Sequence will be shown only in meters with integrated radio) Checksum Window 2 Accumulated values pulse input 1 Accumulated values pulse input 2 ,PPI' pulse value 1 ,PPI' pulse value 2 [off] = not active DEN-SMT/PL VD.SH.J5.02 © Danfoss 03/2013 8 SONOMETERTM1100 – Ultrasonic energy meter Data Sheet Loop “5” Tariff loop Sequence Window 1 Window 2 Window 3 Window 4 Window 5 Window 6 Window 7 Window 4 [off] Window 5 Window 6 Window 7 energy energy energy volume volume volume energy volume The tariff loop is switched off as a standard at the heat meter or meter for cooling. Loop Sequence Window 1 Window 2 “6” Monthly value loop 6.1 6.2 6.3 ... 6.24 ,LOG’ ,LOG’ ,LOG’ date last month date month - 1 date month - 2 ,LOG’ date month - 23 Window 3 [off] ... [off] = not active Simple operation A push-button mounted on the front of the calculator is used to switch to the various displays. The button can be pressed for a short or long time. A short press of the button ( < 3 seconds) switches to the next display within a loop and a long press ( > 3 seconds) switches to the next display loop. The “Energy” window (sequence 1.1) in the main loop is the basic display. 9 VD.SH.J5.02 © Danfoss 03/2013 The calculator switches automatically to power save mode if the button is not pressed for approx. 4 minutes and returns to the basic display when the button is pressed again. The loop settings can be programmed to suit the customer’s individual requirements using the IZAR@SET software. DEN-SMT/PL Data Sheet SONOMETERTM1100 – Ultrasonic energy meter Mounting Depending on the design, the energy meter is installed either in the low temperature or high temperature line as indicated on the type plate. The energy meter is to be installed so that the direction of flow corresponds to the direction of the arrow on the flow sensor. Ensure that the flow sensor is always filled with liquid on completion of installation. Straight inlet/outlet pipes (calming sections) are not required for the flow sensor. The energy meter can be installed in both horizontal and vertical pipe sections, but every time so that air bubbles cannot collect in the flow sensor. For low flow we recommend to mount the flow sensor tilted 90° into the pipe. Make sure the energy meter is installed sufficiently far away from possible sources of electromagnetic interference (switches, electric motors, fluorescent lamps, etc.). For cooling application and for medium temperatures more than 90° C, the calculator must be mounted on the wall at a sufficient distance away from heat sources using the holder supplied. It is recommended that stop valves be fitted before and after the energy meter to simplify dismantling the energy meter. The energy meter should be installed in a convenient position for service and operating personnel. For the further information pls. refer to the SONOMETER™1100’s instructions. DEN-SMT/PL VD.SH.J5.02 © Danfoss 03/2013 10 SONOMETERTM1100 – Ultrasonic energy meter Data Sheet Dimensions H R L2 AGZ h AGV L L1 B DN ØK ØD Ød L1 L1 Nominal size qp = 0.6 m³/h qp = 1.5 m³/h qp = 3.5 m³/h qp = 2.5 m³/h qp = 6 m³/h F qp = 10 m³/h qp = 15 m³/h qp = 25 m³/h qp = 40 m³/h qp = 60 m³/h L [mm] 110 130 190 190 110 130 190 190 130 190 190 260 260 260 260 260 260 300 300 270 300 300 360 L1 [mm] 190 230 290 190 190 230 290 190 230 290 190 380 260 260 380 260 260 440 300 270 300 300 360 L2 [mm] 150 150 150 B [mm] 100 100 100 R [mm] 54 54 54 H [mm] 82 84 84 84 82 84 84 84 84 84 84 88.5 88.5 88.5 88.5 88.5 88.5 94 94 99 106.5 114 119 h [mm] 14.5 18 18 47.5 14.5 18 18 47.5 18 18 47.5 23 50 62.5 23 50 62.5 33 39 73.5 85 92.5 108 G¾B DN 15 G1B DN 20 G1B DN 20 FL DN 20 G¾B DN 15 G1B DN 20 G1B DN 20 FL DN 20 FL DN 25 FL DN 32 G1¼B DN 25 FL DN 25 FL DN 32 G2B AGZ FL DN 40 FL DN 50 FL DN 65 FL DN 80 FL DN 100 AGV R½ R¾ R¾ - R½ R¾ R¾ - R¾ R¾ - R1 - - R1 - - R1½ - - - - - - - - 105 - - - 105 - - 105 - 114 139 - 114 139 - 148 163 184 200 235 D [mm] G1B G1B DN DN 20 20 FL G1¼B DN DN 20 25 d [mm] - - - 14 - - - 14 - - 14 - 14 18 - 14 18 - 18 18 18 19 22 F [mm] - - - 95 - - - 95 - - 95 - 100 125 - 100 125 - 138 147 170 185 216 K [mm] - - - 75 - - - 75 - - 75 - 85 100 - 85 100 - 110 125 145 160 190 Weight [kg] 0.76 0.85 1.5 3.5 4.8 1.5 3.5 4.8 3.1 6.4 7.0 8.9 10.9 16.4 11 0.96 2.75 0.76 0.85 0.96 2.75 0.85 0.96 2.75 VD.SH.J5.02 © Danfoss 03/2013 DEN-SMT/PL Data Sheet SONOMETERTM1100 – Ultrasonic energy meter Dimensions, continued Temperature sensors Designation Type Dimension D (mm) L (mm) Direct mounted Pt 500 ø 5.2 45 Pocket sensor Pt 500 ø 5.2 45 Sensor pockets Type Sensor (mm) dimension Brass Stainless steel ø 5.2 ø 5.2 L1 (mm) 47 60 93 128 98 133 168 223 L (mm) 35 52 85 120 85 120 155 210 Length 12 VD.SH.J5.02 Produced by Danfoss A/S © 03/2013