a quarius - Schiessl
Transcription
a quarius - Schiessl
High efficiency water cooled chillers, heat pumps and evaporating units with screw compressors and R134a refrigerant gas. Cooling capacity 380 – 1549 kW Heating capacity 427 – 1740 kW Cooling capacity condenserless version 350 – 1434 kW Conditioning your ambient, maximising your comfort. Technical specifications ......................................................................................... 4 Selection guide ..................................................................................................... 11 Performances and technical data ........................................................................ 12 Hydraulic data ....................................................................................................... 23 Working limits ...................................................................................................... 25 Corrections factors ............................................................................................. 26 Overall dimensions .............................................................................................. 28 INDICE Installation guide .................................................................................................. 34 TECHNICAL SPECIFICATIONS 1 General 2 Acoustic configurations and versions 3 Nameplate 4Testing 5 Compressors 6Evaporator 7Condensers 8 Partial and total heat recovery (optional) 9 Refrigerant circuit 10 Structure and casing 11 Electrical panel 12Control 13 Options, kits and special executions 13.1 Options 13.2 Kits 13.3 Special executions 14 Selection guide AQUARIUS Plus 2 1. General The Aquarius Plus 2 series of chillers and heat pumps with reversible facility on the hydraulic side are high efficiency water cooled packaged units (Eurovent A Class). The Aquarius Plus 2 series uses a dry expansion type single pass shell & tube evaporator with a refrigerant circuit for each compressor and a single water circuit, one or two semi-hermetic dual screw compressors and continuous control of cooling capacity serving independent refrigerant circuits, electronic expansion valves and R134a refrigerant. The condensers (one for each refrigerant circuit) are shell & tube type and are suitable to integrate partial or total heat recovery. Installation is usually indoors, although the units are also suitable for outdoor installation under a rain shelter (IP54). The units are managed by a microprocessor controller, through a simple user interface allows a fully independent control of all the main functions, including adjustments and alarms. All units are designed, built and checked in compliance with ISO 9001 and incorporate components sourced from premium manufacturers. The combinations of these solutions make it possible to enhance energy efficiency at partial loads, which account for the largest proportion of the working life of an air conditioning unit, thereby maximizing ESEER (*) seasonal performance values. The standard product, destined for EU and EFTA countries, is subject to the following directives: 42% - Electromagnetic Compatibility Directive 2004/108/EC; - Machinery Directive 2006/42/EC; - Pressure Equipment Directive 97/23/EC. - The electrical equipment is constructed in compliance with EN 60204-1. All data in this catalogue refer to standard units and nominal operating conditions (unless otherwise specified). (*) The ESEER (European Seasonal Energy Efficiency Ratio) index proposed and used in the European design context, characterize the average weighted efficiency of a chiller for air conditioning applications. Both indices express, far more accurately than EER, the ratio between the useful effect (energy removed from interior spaces) and energy expenditure (electrical energy consumed) of a chiller during an entire season of operation. In relation to the various different operating conditions and the frequency with which they occur, these indicators are calculated by assigning a different energy weight to the corresponding output values of the unit. For example ESEER = 6 means that during an entire season of operation 1 kWh of electrical power is required on average to remove 6 kWh of heat energy from the air conditioned spaces. 41% ESEER 37% ESEER 33% 23% 20% 3,0% 1,4% 25% 50% 75% ESEER operating time percentages 4 100% 25% 50% 75% ESEER energy weights 100% 2. Acoustic configurations and versions • CH – cooling only version; suitable for working with evaporator outlet water temperature from 0 °C up to 20 °C and condenser outlet water temperature up to 60 °C. • HP – heat pump version with reversible facility on the hydraulic side and outlet water temperature up to 60 °C in heating mode; in comparison with "CH" version, the condenser and discharge pipes are thermally insulated to prevent heat loss; the units are supplied with additional probes for temperature control in heating mode; the reverse cycle valves and installation of the probes are to be provided by the customer; the reversing cycle valves can be managed by electronic control through a digital input. Total heat recovery “R” option is not available with “HP” version. • LWT – low water temperature version; with this option units are able to provide water from +5 °C down to -8 °C and condenser outlet water temperature up to 55 °C; in comparison with "CH" version this units are fitted with an evaporator optimized for working with brine; the evaporator is supplied with an additional thermal insulation in order to avoid potential condensation problems; each compressor is equipped with liquid injection and capacity control can work down to 50%. Antifreeze additives must be used in adequate concentration. Basic acoustic configuration • ME – condenserless version: this units are supplied without condensers and refrigerant charge adding on each refrigerant circuit a liquid reciever and the shut-off valves on discharge and on liquid line. The compressor’s capacity control can work down to 50%. Total heat recovery “R” and partial heat recovery “D” options are not available with “LWT” version. Heat recovery: • R – partial heat recovery: this configuration allows the production of hot water while the unit is on cooling mode by a partial recovery of the condensation heat; the heat recovery exchanger is fully integrated in the condenser (see. chapter “Partial and total heat recovery”). • D – total heat recovery: this configuration allows the production of hot water while the unit is on cooling mode by a total recovery of the condensation heat; the heat recovery exchanger is fully integrated in the condenser (see. chapter “Partial and total heat recovery”). Acoustic configurations: • Basic acoustic configuration: compressors directly accessible from the outside. •Silent acoustic configuration: optimised for very low noise operation, it allows a reduced noise levels by approximately 6 db(A) compared to “Basic” version; the compressors are housed in a metal compartment insulated with a sound absorbing layer of open-cell expanded polyurethane and a sound deadening rubber sheet; this option is available for all the models and configurations. Silent acoustic configuration 3. Nameplate AQP2 XXX Y ZZZ Unit version “CH”, “LWT”, “HP", "ME"; Cooling circuits number “1”, “2”; Compressor nominal power, in HP; Aquarius Plus 2 4. Testing All units are tested in a test chamber in order to check correct operation. The main checks performed are as follows: •the correct instalment of all components and the lack of refrigerant leaks; •electrical safety tests as prescribed by EN60204-1; •correct operation of the microprocessor and correct values of all the operating parameters; •the temperature probes and pressure transducers. AQUARIUS Plus 2 The Aquarius Plus 2 range, in order to meet different installation requirements, are available with different versions and accessories: At the time of installation the units require exclusively electrical and hydraulic connection, thus maximising reliability levels. Installation of a filter on the unit inlet is mandatory. 5 5. Compressors The units of the Aquarius Plus 2 range are equipped with semihermetic dual screw compressors optimized for use with R134a refrigerant. The compressors operates on independent refrigerant circuits; this allows to deliver the exact cooling capacity required by the system achieving and high energy efficiency special at partial loads, which account for the largest portion of the working life of the air conditioning application. The compressors can deliver down to 25% of the nominal cooling capacity in the single circuit units and down to 12.5% in the units with two compressors. The new "Smart Stepless” software algorithm developed by MTA determines with greater precision the real position of the compressor capacity slide and therefore its cooling capacity, compared to the traditional capacity logics; current and average partialization percentage are also available on the display. In addition, even in situations of high variability in the thermal load, the electronic control independently adjusts the capacity speed according to the needs of the system in a manner that is transparent to the user, with consequent greater stability of the evaporator outlet water temperature. Lubrication of the mechanical parts is ensured by a high-efficiency separator that is built into the compressor that reduces the outflow of the oil towards the system and the presence of an appropriate sightglass that enables control of the oil level in the casing. Each compressor is equipped with two oil level sensors: the upper sensor has the function of pre-alarm and is activated for necessary and relevant operational logics for a better return of the oil to the compressor, while the lower sensor has a function of alarm and shutdown the unit in the event of intervention. The electric motor with star-delta starting (soft-starter optional) is two-pole type cooled by the intake gas; protection from possible overheating is ensured by an internal module that controls the temperature of the windings; the same module also controls the sequence of the phases to avoid the danger of reverse rotation and the compressor’s discharge temperature. Each compressor is equipped with a crankcase heater, a delivery shut-off valve and a check valve in delivery side in order to prevent liquid return. The compressors are easily accessible for normal routine maintenance and are mounted in the upper part of the machine on rubber vibration dampers. The unloading function allows starting of the system and the operation of the machine, even under conditions that are very different from the nominal ones. Smart Stepless Thermal load (%) 100% AQUARIUS Plus 2 75% 6 50% 25% t (s) Thermal load Smart Stepless Stepless Inverter Step 6. Evaporator The evaporator is of the dry expansion single pass shell and tube type with one or two independent refrigerant circuits and a single water circuit. The evaporators in the Aquarius Plus 2 series are specifically designed for use with R134a and are composed of a bundle of copper tubes mechanically expanded at the ends into a tube plate and housed inside a carbon steel shell. The refrigerant flows inside the copper tubes, which are ribbed to increase the exchange efficiency, whilst the water, which is oriented by baffles, flows over the outside of the tubes. Each evaporator is externally protected with thermal insulation material and anti-condensation cladding with black embossed finish, and protected from the risk of freezing potentially caused by low evaporation temperatures by antifreeze function incorporated in the electronic controller, which monitors the water outlet temperature. The “LWT” units are fitted with an evaporator optimized for working with brine; an additional thermal insulation is provided in order to avoid potential condensation problems. Each evaporator is equipped with a water differential pressure switch to protect it in conditions in which the water flow is absent or insufficient. The water connections are easily accessible from the exterior of the unit and are “Victaulic” type, supplied with stub pipe. All the evaporators comply with the “EC” pressure vessels directive and can handle antifreeze solutions and, in general, all other liquids that are compatible with the hydraulic circuit construction materials. 7. Condensers The condensers, one for each refrigerant circuit, are of the shell and tube type and are optimised for the use of R134a refrigerant. The exchangers are composed of a bundle of copper tubes (inside which water flows), housed inside a carbon steel shell, in which condensation occurs. The cast iron headers of the shell carry the threaded connections for the hydraulic pipes and are removable in order to allow inspection and the internal cleaning of the tubes; the tubes are finned on the water side to enhance thermal exchange efficiency.Installers are required to fit a filter on the unit inlet line to intercept any debris. If the installation involves the use of water at the inlet to the condensers outside the values specified for the operating limits, pressure control valves must be fitted. All the condenser comply with the “EC” pressure vessels directive and can handle antifreeze solutions and, in general, all other liquids that are compatible with the hydraulic circuit construction materials. The user is responsible for interconnection on the water side of dual circuit units and, when the unit is to be used as a heat pump, positioning of the winter temperature control probe (always supplied pre-wired to the controller) in a socket on the condenser outlet pipe. 8. Partial and total heat recovery (optional) • D - partial heat recovery: by means of a specifically developed condenser, while the unit is on cooling mode, it is possible to recover part of the condensing energy for the production of hot water. Heat recovery takes place simply via activation of the flow of water in the relevant area of the exchanger. The interconnection, temperature probes and management of the pumps are at the customer charge. The use of partial recovery is not permitted in HP mode. configuration offers significant energy saving whenever the requested of hot water is high. Total recovery mode is activated by turning on the hydraulic pumps in the relevant area of the exchanger. With this solution the condenser and the delivery pipes are supplied thermally insulated, while the interconnection and the temperature probes are at customer charge. Management of the pumps and of the alarms is entrusted to the xDRIVE electronic control. This option is not compatible with the heat pump configuration (HP). • R - total heat recovery: by means of a specifically developed condenser, while the unit is on cooling mode, it is possible to fully recover the condensing energy for the production of hot water. This Each cooling circuit in the standard configuration is completed in the following manner: •electronic expansion valve that allows the improvement of cooling performance in a context that is much wider than mechanical thermostatic valve, a reduction of the fluctuations of the temperature of the water and a great precision during operation at partial loads; •filter-dryer; •sight-glass; •shut-off valve and check valve on the compressor delivery; •shut-off valve on the liquid line; •pressure switches for control of the maximum condensation pressure as provided by the European standards (EN378); •safety valves on the low and high pressure line (as envisaged by EN378); •low pressure transducer: for alarm management, read and display the evaporating pressure; •high pressure transducer: read and display the condensing pressure; alarms management; unloading function; for adjustment of the condensing pressure through servo-driven modulating valve (optional); •antifreeze oil and refrigerant charge. The refrigeration circuit of the LWT version includes a liquid injection system on the compressor; this consists of bleeding from the main liquid line of a small amount of refrigerant that is directly expanded within the compressor thus allowing control and limitation of the discharge temperature of the compressors. The entire brazing for connection of the various components is made with silver alloy and the cold pipes are coated with heat-insulation material to prevent the formation of condensation. 10. Structure and casing The Aquarius Plus 2 units are characterised by a self-supporting structure developed in order to allow the maximum accessibility to all the components for ordinary maintenance. The heat exchangers are painted and rigidly assembled and form an integral part of the structure and support the compressors and the electrical panel. The base, heat exchangers and the support structure of the compressors are black RAL 9005, while the electrical panel and the panelling of the silenced acoustic version (optional) are light grey RAL 7035 with orange-peel finish made from galvanised carbon steel plating. All of the components are subjected to a treatment of phosphor degreasing treatment and oven painting at 180 °C with polyester powder coating to provide a durable weatherproof finish. The units are equipped with eyebolts for lifting and movement via the 4-point sling bar. AQUARIUS Plus 2 9. Refrigerant circuit 7 11. Electrical panel The unit and the electrical cabinet are made in compliance with CEI EN60204-1 (Safety of machinery – Electrical equipment of machines – Safety Part 1: General rules); in particular, protection against the weather is ensured such as to allow outdoor installation of the chillers protected by a rain shelter. The IP54 protection is assured thanks to a seal and a fully welded cabinet, where the electrical devices are placed on a base plate; an easy access to all the device is ensured by a double door where there is the display of the electronic control which is protected by a transparent polycarbonate door. The electrical cabinet, with forced ventilation, is equipped with a main breaker with door lock device and contains the circuit breakers to protect the compressors and contactors for star-delta starting; the control section includes a transformer for the control circuits and the microprocessor board. The protection from the phase loss and from the phase reversal is assured by the phase monitor device. The units are also electrically prearranged for connection of a flow switch and the pump’s management is available for all the configurations. Available Volt-free contacts: •general alarm; •remote ON/OFF; •remote CH/HP; •flow-switch; •double set-point; •evaporator pump; •condensers and heat recovery (optional) pumps. 12. Control AQUARIUS Plus 2 Control and management of the unit are provided by a MTA's control system "xDRIVE" composed by microprocessor electronic controller connected to the semi graphic backlit user terminal; the latter has a 240x96 pixel screen, 8 unit programming buttons and buzzer. Thanks to the icons, multi-function keys with dynamic description and moving images, the displays and information are easy to interpret, by both trained personnel and the system operator even if not specifically trained on the use of the controller. The terminal is located on the door of the electrical cabinet and is protected by an openable polycarbonate cover. An USB port placed near the display allows the software update and the download of the alarms history. 8 The controller manages the following main functions independently: • “Smart Stepless”: Intelligent management of the speed of the compressor capacity control with self-adaptive logic depending on thermal load; • step capacity control (CH-HP versions: 4 steps for each compressor 25%÷50%÷75%÷100%; LWT and ME versions: 3 steps for each compressor 50%÷75%÷100%); • control of the 25% partialization step depending on the oil level, on the compressor’s operating range and on the compressor discharge temperature; • temperature control of water at the evaporator outlet, with neutral zone logic; • set-point management: - “ fixed” (standard); - “ dual” set by a digital signal; - “ variable in accordance with time bands” (4 time bands) programmable on the internal timer; - “ variable by analogue signal” 4÷20 mA; • unloading function that allows system starting and unit operation also with parameters that differ significantly from nominal conditions (by deactivating one or more steps); • modulating valves management; • display of the main working parameters of the electronic expansion valves; • automatic rotation of compressors start sequence to minimise the working time of each compressor; • on/off by daily and/or weekly time bands; • antifreeze control in accordance with the evaporator outlet temperature; • count of operating hours of the unit and individual compressors with notification when the programmed operating hours before maintenance are exceeded; • management of alarm messages, including: - low evaporating pressure; - high condensing pressure; - compressor thermal protection trip alarm; - pump failure alarm; - compressor oil level; - evaporator low flow rate alarm; - high and low temperature water inlet and outlet alarms; - antifreeze alarm; - phase sequence alarm; - low difference between condensing and evaporating pressure. In addition to alarms, the display can also present the following main information: • compressors partialization values; • current and average partialization values; • condensing and evaporation pressure values of each circuit; • inlet and outlet water temperature; • status of digital inputs and outputs of the electronic controller; • alarms history; • language selection (Italian, English, French, German, Spanish, Russian); • the main operating parameters of the machine can be change through a password-protected menu. In addition, the unit features a 24 Vac powered remote general alarm. The controller has a RS485 serial output with ModBUS communication protocol for the connection to applications developed by third party System Integrators, for local and remote control and an Ethernet port for connecting to a LAN network through which you can access to the internal site controller to display/modify the operating parameters of the machine. Several units (up to 10) can be connected in parallel via Ethernet connection with its dedicated kit (one unit as a "master" and the other as "slave"). The user can manage the group of units by means of the master unit terminal or by means of the replicated remote terminal (optional). N.B.: Expansions may be present to increase the number of inputs/ outputs available, depending on the plant configuration. 13.1 Options The options must be specified at the time of the order because they are factory fitted: Compressors • soft starter: these devices reduces inrush current during startup of the compressors; the soft starter allows to preserve the compressors by mechanical stress, with a reduction of maintenance and downtime; units equipped with soft starter can operate up to a maximum ambient temperature of 40 °C, after which, the unit will enter in a safety mode, in order to preserving the operation of the machine; soft starter aren’t suitable combined with capacitive elements and power factor correction systems must not be operated simultaneously with them. For models 3301 and 6602, this option is available on request only (special execution); • capacitors for compressor power factor correction at cosϕ > 0.9 located in an electrical box installed on the rear side of the electrical panel; this option is not compatible with the soft starter devices. Heat recovery: • D - partial heat recovery (see relevant chapter); •R - total heat recovery (see relevant chapter); Acoustic configurations : • Silent acoustic configuration: optimised for very low noise operation, it allows a reduced noise levels by approximately 6 db(A) compared to “Basic” version. AQUARIUS Plus 2 13. Options, kits and special executions Soft Starter • compressor shut-off valves on suction line to help service task; for models 3001, 3301, 5602, 6002 and 6602, this option is available on request only (special execution); 9 13.2. Kits The kits are supplied separately, generally at the same time of the unit, and installed by the user. They can be supplied later as spare parts, modification kits, completion kits, etc.: • anti-vibration mounts; • Victaulic to flanges evaporator conversion kit; • threaded to flanges condenser/total heat recovery conversion kit; • threaded to Victaulic condenser/total heat recovery conversion kit; • condensing pressure control with: - 2-way pressostatic valve; - 2-way and 3-way modulating servo-controlled valves driven by a 0-10V signal supplied by the unit controller. The choice of valve is made on the basis of the water flow rate in each condenser and the maximum closing and adjustment pressure differentials, exclusively for modulating valves, using the "Pressure control valves" and "Modulating valves" tables. Each kit has a single valve for each condenser and includes threaded counter-flanges complete with seals. The user is responsible for installing the valves: installation of support brackets, connections and hydraulic unions (the diameter of the threaded connections may not correspond to the diameter of the condenser connections), refrigerant (pressure control valves) and electrical (modulating valves) connections. • simple remote control: composed of an ON/OFF switch, green run LED and red general alarm LED, mounted on a plastic wallmounting enclosure, plus 3 metres of cable for connection to the unit; • remote display: can be installed at a distance of up to 200 metres, it works as on board display and it shows the same information. It is equipped with special support for external fixation; • kit modularity: allows the connection of multiple units in parallel by means Ethernet connection to create a modular system; • supervision system xWEB300D, with the possibility of recording the operating parameters, graphics, alarms notification and remote control; • Gateway Trend: allows the connection of the unit and its supervision by a Trend network controls; 13.3 Special executions AQUARIUS Plus 2 This is a selection of the most popular special features, normally not described in detail in our catalogues; the feasibility of special designs must be assessed, confirmed, and priced on a case by case basis in communication with our sales offices before placing the order: 10 • very high energy efficiency versions; • 460 V / 3 ph / 60 Hz power supply; • condensers suitable for sea water. Selection guide 1) Observe the operational limits as indicated in the chart “Working limits”; 2) Verify that the cool water flow is between the minim and maximum values of water flow, which are described in the “Hydraulic data” table. A very low flow can cause laminar flow and thus danger of ice formation and poor unit control; a very high flow can cause great pressure drops and the possibility of tube failure inside the evaporator; 3) For working temperatures under 6 °C outlet water it is necessary to add ethylene glycol or any other antifreeze additives. Consult the chart “Solutions of water and glycol” to determine the necessary quantity of ethylene glycol, the reduction of cooling capacity, the increase of power absorbed by the compressors, the increase of evaporator pressure drop due to the presence of the ethylene glycol; 4) When the difference in temperature between water inlet and outlet is different from 5 °C, the cooling/heating capacity and the absorbed power must be corrected using the table “Corrective coefficients ΔT ≠ 5 °C”. AQUARIUS Plus 2 For a correct chiller selection it is necessary to: 11 PERFORMANCE AND TECHNICAL DATA GENERAL DATA Chiller (CH) - Heat Pump (HP) - Partial heat recovery (D) - Total heat recovery (R) CH - Cooling mode (1) Cooling capacity Total absorbed power EER Energy efficiency class ESEER Evaporator water flow rate Evaporator pressur drops Condenser water flow rate Condenser pressure drops HP - Heating mode (2) AQUARIUS Plus 2 Heating capacity Total absorbed power COP Energy efficiency class Condenser water flow rate Condenser pressure drops D - Partial heat recovery (3) Heating capacity Water flow rate Pressure drops R - Total heat recovery (4) Heating capacity Water flow rate Pressure drops 12 Power supply (5) Power Compressors Type Compressors / Cooling circuits Cooling capacity regulation Capacity control Refrigerant Sound levels Basic acoustic configuration (6) Silent acoustic configuration (6) Dimensions and weights (7) Width Depth Height Weight 1401 1601 1801 2001 2301 2601 3001 3301 kW kW m 3 /h kPa m 3 /h kPa 380 74 5,12 A 5,84 65 43 78 53 422 82 5,15 A 5,84 72 48 87 47 482 94 5,13 A 5,89 83 32 99 57 531 103 5,17 A 5,89 91 43 109 53 594 115 5,17 A 5,89 102 45 122 52 654 126 5,20 A 5,96 112 41 134 53 714 137 5,20 A 5,99 122 33 147 53 768 147 5,23 A 6,04 132 27 158 53 kW kW m 3 /h kPa 427 88 4,85 A 74 45 473 97 4,88 A 82 40 540 111 4,85 A 93 49 593 121 4,89 A 103 45 665 136 4,89 A 115 44 732 149 4,91 A 127 45 799 163 4,91 A 138 45 858 174 4,92 A 148 45 kW m 3 /h kPa 21,2 3,6 10 21,8 3,8 11 23,3 4,0 10 23,6 4,1 12 32,0 5,5 11 33,5 5,8 10 34,5 5,9 10 42,8 7,4 11 kW m 3 /h kPa 427 74 45 473 82 40 540 93 49 593 103 45 665 115 44 732 127 45 799 138 45 858 148 45 V/Ph/Hz 400 ± 10% / 3 - PE / 50 n° - Screw 1/1 Smart Stepless 25 ÷ 100 R134a dB(A) dB(A) 95 90 96 91 97 91 97 92 97 92 97 92 98 92 98 92 mm mm mm kg 1460 4344 1640 1993 1460 4344 1645 2137 1460 4326 1725 2472 1485 4326 1725 2513 1485 4326 1645 2554 1460 4326 1770 2791 1460 4335 1770 2936 1460 4335 1770 2987 Data declared according to UNI EN 14511:2013 (1) CH - Cooling only: evaporator IN/OUT: 12/7 °C; condenser IN/OUT: 30/35 °C; (2) HP - Heat pump: evaporator IN/OUT: 12/7 °C; condenser IN/OUT: 40/45 °C; (3) D - Partial heat recovery: evaporator IN/OUT: 12/7 °C; condenser IN/OUT: 30/35 °C; partial heat recovery IN/OUT: 40/45 °C; (4) R - Total heat recovery: evaporator IN/OUT: 12/7 °C; total heat recovery IN/OUT: 40/45 °C; (5) IP54 protection class; (6) Sound power: determined on the basis of measurements taken in accordance with the standard ISO 3744; (7) Dimensions and weights are referred to AQP2, without options and water content. CH - Cooling mode (1) Cooling capacity Total absorbed power EER Energy efficiency class ESEER Evaporator water flow rate Evaporator pressur drops Condenser water flow rate Condenser pressure drops HP - Heating mode (2) Heating capacity Total absorbed power COP Energy efficiency class Condenser water flow rate Condenser pressure drops D - Partial heat recovery (3) Heating capacity Water flow rate Pressure drops R - Total heat recovery (4) Heating capacity Water flow rate Pressure drops Power supply (5) Power Compressors Type Compressors / Cooling circuits Cooling capacity regulation Capacity control Refrigerant Sound levels Basic acoustic configuration (6) Silent acoustic configuration (6) Dimensions and weights (7) Width Depth Height Weight 2802 3202 3402 3602 4002 4302 4602 4902 5202 5602 6002 6602 kW kW m 3 /h kPa m 3 /h kPa 753 147 5,12 A 5,98 129 40 155 51 848 163 5,21 A 5,98 145 40 174 48 907 175 5,18 A 5,97 156 37 187 53 967 188 5,15 A 5,97 166 41 199 57 1061 204 5,21 A 5,99 182 37 218 53 1121 215 5,21 A 6,05 192 26 230 52 1195 229 5,22 A 6,01 205 32 245 53 1256 240 5,24 A 6,05 215 35 258 53 1305 250 5,21 A 6,05 224 37 268 53 1373 263 5,21 A 5,99 235 45 282 54 1440 275 5,24 A 6,04 247 48 296 53 1549 296 5,23 A 6,00 265 58 318 53 kW kW m 3 /h kPa 852 175 4,87 A 147 45 953 193 4,93 A 165 41 1019 208 4,90 A 176 45 1089 223 4,89 A 188 49 1188 242 4,91 A 205 45 1255 256 4,91 A 217 45 1337 272 4,92 A 231 45 1407 285 4,94 A 243 46 1466 298 4,93 A 253 46 1540 312 4,93 A 266 46 1618 326 4,96 A 280 45 1740 351 4,96 A 301 46 kW m 3 /h kPa 42,4 7,3 10 43,7 7,5 12 45,1 7,8 11 46,5 8,0 10 47,2 8,1 10 55,7 9,6 11 64,1 11,0 10 65,5 11,3 12 66,9 11,5 11 67,9 11,7 10 69,0 11,9 13 85,6 14,7 12 kW m 3 /h kPa 852 147 45 953 165 41 1019 176 45 1089 188 49 1188 205 45 1255 217 45 1337 231 45 1407 243 46 1466 253 46 1540 266 46 1618 280 45 1740 301 46 V/Ph/Hz 400 ± 10% / 3 - PE / 50 n° - Screw 2/2 Smart Stepless 12,5 ÷ 100 R134a dB(A) dB(A) 98 93 98 93 99 93 99 93 99 93 99 94 99 94 100 94 100 94 100 95 101 95 101 95 mm mm mm 1390 4920 1390 4920 1390 4920 1390 4920 1390 4920 1390 4920 1390 4920 1390 4920 1390 4920 1390 4970 1390 4970 1390 4970 2132 3873 2132 4153 2165 4465 2165 4769 2278 5090 2278 5124 2278 5160 2278 5232 2278 5305 2278 5490 2278 5634 2278 5737 kg Data declared according to UNI EN 14511:2013 (1) CH - Cooling only: evaporator IN/OUT: 12/7 °C; condenser IN/OUT: 30/35 °C; (2) HP - Heat pump: evaporator IN/OUT: 12/7 °C; condenser IN/OUT: 40/45 °C; (3) D - Partial heat recovery: evaporator IN/OUT: 12/7 °C; condenser IN/OUT: 30/35 °C; partial heat recovery IN/OUT: 40/45 °C; (4) R - Total heat recovery: evaporator IN/OUT: 12/7 °C; total heat recovery IN/OUT: 40/45 °C; (5) IP54 protection class; (6) Sound power: determined on the basis of measurements taken in accordance with the standard ISO 3744; (7) Dimensions and weights are referred to AQP2, without options and water content. AQUARIUS Plus 2 GENERAL DATA Chiller (CH) - Heat Pump (HP) - Partial heat recovery (D) - Total heat recovery (R) 13 SOUND LEVELS Basic acoustic configuration Octave bands (Hz) Model 1401 1601 1801 2001 2301 2601 3001 3301 2802 3202 3402 3602 4002 4302 4602 4902 5202 5602 6002 6602 63 125 250 500 1000 2000 4000 8000 86 88 89 88 89 90 91 91 92 92 93 94 93 93 94 94 95 94 96 96 72 69 72 73 73 75 75 76 76 75 76 77 79 79 78 79 78 80 81 81 57 61 60 62 61 64 66 67 66 67 67 68 69 70 72 74 73 74 75 76 Sound power level dB (A) 40 41 42 43 43 44 44 45 44 46 45 46 46 47 47 49 49 48 49 50 49 50 51 51 52 52 54 54 54 56 56 56 57 58 57 59 60 61 62 61 72 72 73 74 74 73 75 76 77 78 78 79 79 79 79 81 82 83 82 82 82 83 83 85 86 86 86 85 85 85 85 86 86 87 88 88 88 87 88 89 94 95 96 96 96 96 97 97 97 96 97 97 97 97 97 98 98 98 99 99 Sound power (1) Sound pressure (2) dB (A) dB (A)10m 95 96 97 97 97 97 98 98 98 98 99 99 99 99 99 100 100 100 101 101 67 68 69 69 69 69 70 70 70 70 71 71 71 71 71 72 72 72 73 73 Sound power (1) Sound pressure (2) dB (A) dB (A)10m 90 91 91 92 92 92 92 92 93 93 93 93 93 94 94 94 94 95 95 95 62 63 63 64 64 64 64 64 65 65 65 65 65 66 66 66 66 67 67 67 Silent acoustic configuration Octave bands (Hz) AQUARIUS Plus 2 Model 1401 1601 1801 2001 2301 2601 3001 3301 2802 3202 3402 3602 4002 4302 4602 4902 5202 5602 6002 6602 63 125 250 500 1000 2000 4000 8000 80 82 82 82 83 84 84 84 86 86 86 87 86 87 88 87 88 88 89 89 62 59 62 63 63 65 65 66 66 65 66 67 69 69 68 69 68 70 71 71 49 53 51 54 53 56 57 58 58 59 58 59 60 62 64 65 64 66 66 67 Sound power level dB (A) 37 38 39 40 40 41 41 42 41 43 42 43 43 44 44 46 46 45 46 47 47 48 49 49 50 50 52 52 52 54 54 54 55 56 55 57 58 59 60 59 70 70 70 72 72 71 72 73 75 76 75 76 76 77 77 78 79 81 79 79 78 79 78 81 82 82 81 80 81 81 80 81 81 83 84 83 83 83 83 84 89 90 90 91 91 91 91 91 92 91 91 91 91 92 92 92 92 93 93 93 (1) Sound power: determined on the basis of measurements taken in accordance with the standard ISO 3744. (2) Sound pressure at 10 m: average value obtained in free field on a reflective surface at a distance of 10 m from the side of the condenser coils and at a height of 1.6 m from the unit support base. Distance KdB (1) L (m) 1 3 5 10 15 10 6 0 (1) To calculate a different distance of the sound pressure level, use the formula: dB(A)L=dB(A)10m+Kdb. 14 ELECTRICAL DATA Model FLI [KW] FLA [A] ICF [A] 1401 1601 1801 2001 2301 2601 3001 3301 2802 3202 3402 3602 4002 4302 4602 4902 5202 5602 6002 6602 126 140 160 174 196 215 236 253 252 279 300 321 349 371 392 411 430 451 472 506 209 234 269 291 319 357 382 410 418 469 503 537 582 610 637 676 714 739 765 820 262 328 422 422 493 602 717 807 471 562 656 691 713 784 812 921 959 1074 1099 1217 FLI: max power absorbed in the working limits condition (kW); FLA: max current absorbed in the working limits condition (A); ICF: start-up current at the start of the last compressor in the working limits condition. Compressors starting with soft starter: the soft starters allow a reduction of peak current during start-up of the compressors; these devices allow then to preserve the compressors by mechanical stress, with the consequent reduction of maintenance and machine downtime. The units equipped with a soft starter can operate up to a maximum ambient temperature of 40 °C, after which, the unit will enter in a safety mode, in order to preserving the operation of the machine; soft starters are't compatible with capacitive elements; power factor correction systems cannot operate simultaneously with the soft starter. This option is factory fitted and must be specified in the order. Model CH - HP - LWT kg D - Partial heat recovery kg R - Total heat recovery kg Compressors housing kg 1401 1601 1801 2001 2301 2601 3001 3301 2802 3202 3402 3602 4002 4302 4602 4902 5202 5602 6002 6602 2154 2363 2695 2738 2781 3143 3288 3338 4294 4572 4878 5185 5736 5767 5802 5881 5961 6143 6295 6399 2242 2451 2707 2750 2799 3160 3306 3596 4470 4748 4902 5209 5760 5795 5838 5916 5997 6178 6331 6915 2606 2838 3105 3171 3237 3618 3823 3893 5198 5518 5686 6007 6600 6657 6718 6819 6921 7166 7381 7521 260 260 260 260 260 260 260 260 540 540 540 540 540 540 540 540 540 540 540 540 AQUARIUS Plus 2 WORKING WEIGHTS Working weights includes water content. CH - only cooling version; HP - heat pump version; LWT - low water temperature version; D - partial heat recovery version; R - total heat recovery version. 15 PERFORMANCE DATA CHILLER (CH) - HEAT PUMP (HP) - TOTAL HEAT RECOVERY (R) Inlet / Outlet condenser water temperature [°C] 1401 25 / 30 Glycol tu Pf Pa Fw 20% *5 363 68 66 6 385 69 66 7 398 69 68 8 411 70 71 9 424 71 73 10 437 73 75 40 / 45 Pf Pa Fw 306 86 56 326 87 56 339 88 58 352 89 60 365 90 63 377 90 65 45 / 50 Pf Pa Fw 284 95 52 305 96 52 317 97 54 330 97 57 341 98 58 354 99 61 50 / 55 Pf Pa Fw 262 104 48 281 105 48 293 106 50 305 107 52 316 108 54 330 108 57 55 / 60 Pf Pa Fw 238 114 43 256 115 44 267 116 46 278 118 48 290 119 50 301 120 52 t max (**) 60 60 60 60 60 60 *5 6 7 8 9 10 402 427 443 457 472 486 75 76 77 78 79 80 73 73 76 78 81 83 382 406 422 437 451 465 80 81 82 83 84 85 69 70 72 75 77 80 361 384 400 414 429 444 87 88 89 90 90 91 66 66 68 71 74 76 339 95 362 96 376 97 390 98 405 99 419 100 62 62 64 67 69 72 315 338 351 366 378 393 104 106 106 107 108 109 57 58 60 63 65 67 290 311 325 338 351 367 115 116 117 118 119 119 53 53 56 58 60 63 264 284 296 309 322 335 125 127 128 129 131 132 48 49 51 53 55 57 60 60 60 60 60 60 20% *5 6 7 8 9 10 460 488 506 522 538 555 85 87 88 89 90 92 84 84 87 89 92 95 436 464 482 499 514 531 92 93 94 95 96 97 79 80 83 85 88 91 413 438 456 473 489 506 100 101 102 103 104 105 75 75 78 81 84 87 388 412 429 445 462 478 109 110 111 112 113 115 70 71 73 76 79 82 360 386 401 417 431 447 120 121 122 123 125 126 65 66 69 71 74 77 331 355 371 386 400 417 132 133 134 136 137 137 60 61 64 66 69 72 301 323 338 352 367 381 144 146 148 149 150 152 55 55 58 60 63 65 60 60 60 60 60 60 20% *5 6 7 8 9 10 506 93 92 480 538 95 92 511 557 96 95 531 575 97 99 550 594 99 102 568 612 100 105 586 100 87 101 88 103 91 104 94 105 97 106 100 454 483 502 521 539 558 109 110 111 112 113 115 82 83 86 89 92 96 426 455 472 491 509 527 119 120 121 122 124 125 77 78 81 84 87 90 396 424 441 460 475 493 131 132 133 134 136 137 72 73 76 79 81 85 364 391 408 425 441 460 143 145 146 148 149 150 66 67 70 73 76 79 331 356 372 389 404 420 157 159 161 162 164 165 60 61 64 67 69 72 60 60 60 60 60 60 20% *5 6 7 8 9 10 566 601 623 643 664 685 105 106 108 109 111 112 103 103 107 110 114 117 537 572 594 615 636 655 112 114 115 116 118 119 98 98 102 105 109 112 507 540 562 583 604 624 122 92 478 134 87 123 93 508 135 87 124 96 529 136 91 126 100 549 137 94 127 103 569 138 98 128 107 589 140 101 443 475 494 514 532 552 147 148 149 150 152 153 81 81 85 88 91 95 408 438 458 476 494 515 161 163 164 165 167 168 74 75 78 82 85 88 371 399 417 435 454 471 176 178 180 182 183 185 67 68 71 74 78 81 60 60 60 60 60 60 20% *5 6 7 8 9 10 624 662 684 707 729 751 114 116 118 119 121 123 113 113 117 121 125 129 592 630 654 675 698 720 123 124 126 127 129 130 108 108 112 116 120 123 561 596 620 642 665 685 134 135 136 138 139 141 102 102 106 110 114 118 527 561 583 606 627 649 146 148 149 150 152 153 96 96 100 104 108 111 490 525 546 567 586 609 161 89 451 162 90 483 164 94 504 165 97 526 167 101 545 168 104 568 176 178 180 182 183 184 82 83 86 90 94 97 410 441 460 480 501 520 193 196 198 199 201 203 75 76 79 82 86 89 60 60 60 60 60 60 20% *5 6 7 8 9 10 681 723 748 773 798 823 125 127 128 130 132 134 124 124 128 132 137 141 646 688 714 740 763 788 134 136 137 139 140 142 117 118 122 127 131 135 612 650 677 702 727 750 146 147 149 150 152 153 111 111 116 120 125 129 575 613 636 661 686 710 160 161 163 164 166 167 105 105 109 113 118 122 534 573 596 619 641 666 175 177 179 180 182 183 97 98 102 106 110 114 492 528 550 574 596 621 193 89 447 195 90 481 197 94 502 198 98 524 200 102 547 201 106 568 211 214 216 218 220 222 81 82 86 90 94 97 60 60 60 60 60 60 20% *5 6 7 8 9 10 733 778 806 832 859 886 133 136 137 139 141 143 133 133 138 143 147 152 695 740 768 796 821 848 143 145 147 148 150 152 126 127 132 136 141 145 658 699 728 755 781 809 156 158 159 161 162 164 120 120 125 129 134 139 618 658 684 711 737 763 171 173 174 176 177 179 112 113 117 122 126 131 574 615 640 666 689 715 188 190 192 193 195 196 104 105 110 114 118 123 529 567 591 616 640 667 206 209 211 212 214 215 226 87 229 89 231 92 233 96 235 101 238 105 60 60 60 60 60 60 1801 2001 2301 AQUARIUS Plus 2 35 / 40 Pf Pa Fw 325 79 59 346 80 59 360 80 62 373 81 64 386 82 66 398 83 68 20% 1601 2601 3001 3301 30 / 35 Pf Pa Fw 344 73 63 367 73 63 380 74 65 394 75 67 406 76 70 419 77 72 96 97 101 106 110 114 481 517 540 563 587 610 Data declared according to UNI EN 14511:2013 tu: evaporator outlet water temperature (°C); Pf: cooling capacity (kW); Pa: total absorbed power (kW); Fw: water flow rate with ΔT = 5 °C (m3 /h). (*): The performances have been calculated with 20% ethylene glycol in the water. (**): Condenser maximum outlet water temperature. When the condenser temperature is higher than the "t max" the unit doesn't stop but the "unloading" system capacity control is activated. The values in the table are inclusive of ethylene glycol percentage and are calculated with ∆T = 5 °C evaporator and condenser ∆T = 5 °C. To calculate performances at diferring water inlet/outlet ∆T levels, refer to the "∆T correction factors" table. Interpolation is allowed, extrapolation is not permitted. In the HP (heat pump) and R (total heat recovery) operating mode the heating capacity is detemined with the following formula: Heating capacity = Cooling capacity + Total absorbed power. 16 PERFORMANCE DATA CHILLER (CH) - HEAT PUMP (HP) - TOTAL HEAT RECOVERY (R) 2802 35 / 40 Pf Pa Fw 653 157 119 693 158 119 719 160 123 741 161 127 765 163 131 790 164 136 40 / 45 Pf Pa Fw 613 172 111 654 174 112 677 175 116 703 176 121 726 178 124 749 179 128 45 / 50 Pf Pa Fw 572 189 104 611 191 105 637 192 109 660 193 113 683 196 117 707 197 121 50 / 55 Pf Pa Fw 528 207 96 566 210 97 589 212 101 612 213 105 636 215 109 661 216 113 55 / 60 Pf Pa Fw 481 227 87 517 230 89 539 232 92 562 235 96 584 237 100 606 239 104 t max (**) 60 60 60 60 60 60 20% *5 6 7 8 9 10 811 858 888 917 947 977 148 150 152 154 156 159 147 147 152 157 162 167 772 820 848 877 906 934 159 161 163 165 166 168 140 141 145 150 155 160 732 778 807 837 863 891 173 175 177 178 180 182 133 133 138 143 148 153 688 734 759 790 818 845 190 192 193 195 197 198 125 126 130 135 140 145 640 685 712 739 767 795 209 211 212 214 216 218 116 117 122 127 132 136 590 633 661 687 713 738 229 232 234 236 237 240 107 108 113 118 122 127 537 577 603 629 656 681 251 255 257 259 261 264 98 99 103 108 112 117 60 60 60 60 60 60 20% *5 6 7 8 9 10 868 918 949 982 1013 1044 159 162 164 166 168 171 158 157 163 168 174 179 824 877 907 939 968 1000 171 173 175 177 179 181 150 150 156 161 166 172 782 831 862 892 923 952 186 188 190 192 194 196 142 142 148 153 158 163 734 783 811 843 874 902 204 206 208 210 212 214 133 134 139 145 150 155 683 731 761 790 819 848 224 227 229 230 232 234 124 125 130 135 140 146 630 675 704 733 761 791 246 249 251 254 255 257 114 116 121 126 131 136 573 616 643 671 698 726 270 274 276 279 281 284 104 106 110 115 120 124 60 60 60 60 60 60 20% *5 6 7 8 9 10 926 978 1011 1045 1078 1110 171 173 175 178 180 183 168 168 173 179 185 190 881 936 967 999 1030 1064 183 186 188 190 192 194 160 160 166 171 177 182 835 887 921 951 982 1013 200 202 204 206 208 210 152 152 158 163 168 174 784 836 866 900 932 960 219 221 223 225 227 229 143 143 148 154 160 165 731 781 813 846 874 905 240 243 245 246 249 251 133 134 139 145 150 155 674 722 752 784 813 847 264 267 269 271 274 275 123 124 129 134 139 145 614 659 688 717 745 776 289 293 296 298 301 304 112 113 118 123 128 133 60 60 60 60 60 60 20% *5 6 7 8 9 10 1013 1074 1109 1146 1182 1221 185 188 190 193 196 199 184 184 190 196 203 209 961 1023 1061 1096 1132 1167 199 202 204 206 208 211 175 175 182 188 194 200 910 969 1006 1043 1077 1112 217 219 221 223 225 228 165 166 172 179 185 191 857 912 946 984 1019 1055 238 240 242 244 246 248 156 156 162 169 175 181 796 853 886 924 955 989 261 264 266 267 270 273 145 146 152 158 164 170 733 786 819 854 886 918 286 290 292 295 297 300 133 135 140 146 152 157 667 717 749 780 814 845 314 318 321 324 327 330 121 123 128 134 140 145 60 60 60 60 60 60 20% *5 6 7 8 9 10 1070 1133 1174 1212 1251 1291 195 198 201 203 206 209 194 194 201 208 214 221 1015 1081 1121 1159 1196 1235 210 213 215 217 220 222 184 185 192 199 205 212 961 1021 1063 1102 1139 1177 229 232 234 236 238 240 175 175 182 189 195 202 903 963 999 1039 1076 1115 251 254 256 258 260 262 164 165 171 178 185 191 840 899 936 974 1006 1045 276 279 281 283 286 288 153 154 160 167 172 179 774 830 866 902 936 972 303 307 309 312 315 317 141 142 148 155 160 167 704 757 790 824 858 892 332 337 340 343 346 349 128 130 135 141 147 153 60 60 60 60 60 60 3202 3402 3602 4002 4302 30 / 35 Pf Pa Fw 688 144 125 728 146 125 753 147 129 779 149 134 804 150 138 828 152 142 Data declared according to UNI EN 14511:2013 tu: evaporator outlet water temperature (°C); Pf: cooling capacity (kW); Pa: total absorbed power (kW); Fw: water flow rate with ΔT = 5 °C (m3 /h). (*): The performances have been calculated with 20% ethylene glycol in the water. (**): Condenser maximum outlet water temperature. When the condenser temperature is higher than the "t max" the unit doesn't stop but the "unloading" system capacity control is activated. The values in the table are inclusive of ethylene glycol percentage and are calculated with ∆T = 5 °C evaporator and condenser ∆T = 5 °C. To calculate performances at diferring water inlet/outlet ∆T levels, refer to the "∆T correction factors" table. Interpolation is allowed, extrapolation is not permitted. In the HP (heat pump) and R (total heat recovery) operating mode the heating capacity is detemined with the following formula: Heating capacity = Cooling capacity + Total absorbed power. AQUARIUS Plus 2 Inlet / Outlet condenser water temperature [°C] 25 / 30 Glycol tu Pf Pa Fw 20% *5 721 134 131 6 762 135 130 7 789 137 135 8 814 139 140 9 837 141 143 10 860 142 147 17 PERFORMANCE DATA CHILLER (CH) - HEAT PUMP (HP) - TOTAL HEAT RECOVERY (R) Inlet / Outlet condenser water temperature [°C] 4602 Glycol tu 20% *5 6 7 8 9 10 40 / 45 Pf Pa Fw 964 267 175 1028 269 176 1065 272 183 1108 274 190 1148 276 197 1189 279 204 45 / 50 Pf Pa Fw 896 293 163 959 296 164 997 298 171 1035 301 177 1076 303 184 1115 306 191 50 / 55 Pf Pa Fw 825 322 150 885 325 152 925 328 158 961 331 165 998 334 171 1034 337 177 55 / 60 Pf Pa Fw 751 352 136 807 357 138 843 360 144 879 364 151 917 367 157 952 370 163 t max (**) 60 60 60 60 60 60 1200 1271 1314 1357 1402 1444 218 221 224 227 230 233 218 218 225 233 240 248 1140 1213 1256 1298 1340 1384 234 237 240 242 245 248 207 208 215 222 230 237 1080 1149 1193 1236 1277 1318 255 258 260 262 265 268 196 197 204 212 219 226 1015 1082 1122 1166 1208 1249 279 282 285 287 289 292 184 185 192 200 207 214 945 1011 1052 1093 1133 1174 307 310 313 315 318 321 172 173 180 187 194 201 871 933 974 1014 1052 1093 337 341 344 347 350 352 158 160 167 174 180 187 792 852 889 927 965 1004 369 374 378 381 385 388 144 146 152 159 166 172 60 60 60 60 60 60 20% *5 6 7 8 9 10 1250 1320 1366 1410 1457 1502 228 231 234 237 240 243 227 226 234 242 250 258 1189 1262 1305 1349 1393 1439 245 248 250 253 256 259 216 216 224 231 239 247 1125 1197 1242 1287 1327 1370 267 269 272 274 277 280 205 205 213 221 228 235 1057 1126 1169 1215 1258 1299 292 295 298 300 303 305 192 193 200 208 216 223 985 1053 1097 1141 1180 1222 321 324 327 329 332 335 179 180 188 196 202 210 909 973 1014 1058 1097 1143 352 357 360 363 366 367 165 167 174 181 188 196 827 889 928 967 1006 1047 386 391 395 399 402 406 150 152 159 166 172 180 60 60 60 60 60 60 20% *5 6 7 8 9 10 1312 1388 1435 1484 1531 1579 240 243 246 250 253 257 238 238 246 254 263 271 1248 1326 1373 1418 1465 1513 258 261 263 266 269 273 227 227 235 243 251 260 1181 1256 1304 1350 1397 1441 280 283 286 288 291 294 215 215 224 231 240 247 1110 1184 1227 1276 1323 1367 307 309 312 315 318 321 202 203 210 219 227 234 1034 1106 1151 1196 1240 1285 337 340 343 346 349 352 188 189 197 205 213 220 954 1022 1066 1110 1152 1193 370 374 377 381 384 387 173 175 183 190 198 205 868 933 974 1015 1058 1100 405 411 414 418 422 426 158 160 167 174 181 189 60 60 60 60 60 60 20% *5 6 7 8 9 10 1379 1457 1506 1558 1607 1656 250 254 257 260 264 268 251 250 258 267 276 284 1312 1394 1440 1489 1536 1588 269 272 275 278 281 284 239 239 247 255 263 272 1243 1322 1372 1418 1465 1512 293 296 298 301 304 307 226 226 235 243 251 259 1168 1244 1291 1342 1390 1434 321 323 326 329 332 335 212 213 221 230 238 246 1089 1164 1213 1262 1305 1351 352 356 358 360 364 368 198 199 208 216 224 232 1005 1077 1122 1170 1213 1256 386 391 394 397 401 404 183 185 192 201 208 215 916 984 1027 1070 1113 1159 423 429 433 437 441 445 166 169 176 183 191 199 60 60 60 60 60 60 20% *5 6 7 8 9 10 1483 1566 1619 1675 1728 1780 270 273 277 281 284 288 269 268 277 287 296 305 1412 1499 1549 1601 1652 1707 290 293 296 299 303 306 257 257 265 274 283 293 1335 1422 1475 1524 1575 1625 315 318 321 324 327 330 243 244 253 261 270 279 1257 1340 1389 1444 1495 1542 345 347 351 354 357 360 228 230 238 247 256 264 1172 1252 1304 1358 1403 1454 378 382 385 387 392 395 213 215 224 233 241 249 1082 1159 1208 1259 1305 1351 415 420 423 427 431 435 197 199 207 216 224 232 985 1059 1105 1152 1198 1247 454 460 465 469 473 478 179 181 189 197 205 214 60 60 60 60 60 60 5602 6002 AQUARIUS Plus 2 35 / 40 Pf Pa Fw 1026 243 186 1091 246 187 1133 248 194 1175 250 201 1216 253 209 1255 255 215 *5 6 7 8 9 10 5202 18 30 / 35 Pf Pa Fw 1082 224 197 1152 226 197 1195 229 205 1235 231 212 1276 234 219 1317 237 226 20% 4902 6602 25 / 30 Pf Pa Fw 1140 208 207 1210 211 207 1250 214 214 1292 217 222 1334 220 229 1375 223 236 Data declared according to UNI EN 14511:2013 tu: evaporator outlet water temperature (°C); Pf: cooling capacity (kW); Pa: total absorbed power (kW); Fw: water flow rate with ΔT = 5 °C (m3 /h). (*): The performances have been calculated with 20% ethylene glycol in the water. (**): Condenser maximum outlet water temperature. When the condenser temperature is higher than the "t max" the unit doesn't stop but the "unloading" system capacity control is activated. The values in the table are inclusive of ethylene glycol percentage and are calculated with ∆T = 5 °C evaporator and condenser ∆T = 5 °C. To calculate performances at diferring water inlet/outlet ∆T levels, refer to the "∆T correction factors" table. Interpolation is allowed, extrapolation is not permitted. In the HP (heat pump) and R (total heat recovery) operating mode the heating capacity is detemined with the following formula: Heating capacity = Cooling capacity + Total absorbed power. PERFORMANCE DATA LOW WATER TEMPERATURE (LWT) Fw 36 40 44 51 58 63 35 / 40 Pf Pa 172 72 203 73 225 75 264 76 303 78 329 80 Fw 33 37 42 48 55 60 40 / 45 Pf Pa 159 78 187 80 209 82 246 84 283 86 309 87 Fw 30 35 39 45 51 56 45 / 50 Pf Pa 145 85 172 88 192 89 227 92 263 94 287 95 Fw 28 32 35 41 48 52 50 / 55 Pf Pa 130 92 156 95 174 97 208 100 242 103 265 105 Fw 25 29 32 38 44 48 t max (*) Glycol 35% 25% 25% 20% 20% 20% tu -8 -5 -3 0 3 5 1601 35% 25% 25% 20% 20% 20% -8 -5 -3 0 3 5 223 256 283 330 374 405 66 68 69 72 74 76 43 47 52 60 68 74 208 240 266 311 356 384 73 74 75 77 80 81 40 44 49 57 65 70 192 224 249 292 336 364 80 81 83 84 87 88 37 41 46 53 61 66 177 207 231 272 314 342 87 89 90 92 95 96 34 38 43 49 57 62 162 94 190 97 212 99 252 101 291 104 318 105 31 35 39 46 53 58 146 172 193 230 268 293 102 105 107 111 113 115 28 32 36 42 49 53 55 55 55 55 55 55 1801 35% 25% 25% 20% 20% 20% -8 -5 -3 0 3 5 254 293 324 377 428 463 76 78 79 82 85 87 49 54 60 68 78 84 236 274 304 356 407 439 83 85 86 89 91 93 45 51 56 65 74 80 219 91 256 93 284 94 334 97 384 99 416 101 42 47 53 61 70 76 201 236 264 311 359 391 99 102 103 106 108 110 39 44 49 57 65 71 184 217 243 288 333 363 108 111 113 116 119 121 35 40 45 52 61 66 166 196 221 263 306 335 116 120 123 127 130 132 32 36 41 48 56 61 55 55 55 55 55 55 2001 35% 25% 25% 20% 20% 20% -8 -5 -3 0 3 5 281 324 357 416 472 511 82 84 86 89 92 94 54 60 66 76 86 93 262 90 303 92 336 94 392 96 447 99 485 101 50 56 62 71 81 88 243 282 314 368 423 459 99 101 103 105 108 110 47 52 58 67 77 83 224 261 291 343 395 431 108 111 113 115 118 120 43 48 54 62 72 78 204 239 268 317 367 400 118 121 123 126 129 131 39 44 50 58 67 73 184 217 243 290 337 369 127 131 134 138 142 144 35 40 45 53 61 67 55 55 55 55 55 55 2301 35% 25% 25% 20% 20% 20% -8 -5 -3 0 3 5 313 93 60 361 95 67 399 97 74 464 100 84 527 104 96 571 106 104 291 338 375 438 501 541 102 104 106 108 112 114 56 63 69 80 91 98 270 315 350 411 473 512 111 114 115 118 121 123 52 58 65 75 86 93 248 291 325 383 442 482 121 124 126 130 133 135 48 54 60 70 80 88 227 267 299 355 410 448 132 136 138 142 145 148 44 49 55 64 75 81 204 242 272 324 377 413 142 147 150 155 159 162 39 45 50 59 69 75 55 55 55 55 55 55 2601 35% 25% 25% 20% 20% 20% -8 -5 -3 0 3 5 348 400 441 512 582 630 101 67 104 74 106 82 109 93 113 106 116 114 324 375 415 484 553 597 111 62 114 69 115 77 118 88 122 101 124 109 300 349 388 455 521 566 122 58 124 65 126 72 129 83 132 95 135 103 276 323 360 424 488 533 133 136 138 142 145 147 53 60 67 77 89 97 252 296 331 392 453 495 145 149 151 155 159 162 48 55 61 71 82 90 228 269 301 359 417 456 156 161 165 170 174 177 44 50 56 65 76 83 55 55 55 55 55 55 3001 35% 25% 25% 20% 20% 20% -8 -5 -3 0 3 5 379 437 482 559 634 686 111 73 114 81 116 89 120 102 124 115 128 125 353 409 453 528 603 651 122 68 125 76 127 84 130 96 134 110 137 118 327 381 424 496 568 616 134 63 136 71 139 78 142 90 146 103 148 112 302 353 393 463 532 580 146 58 149 65 152 73 155 84 159 97 162 105 275 324 362 428 494 539 158 163 166 170 174 177 53 60 67 78 90 98 248 294 330 392 454 497 171 177 180 186 191 194 48 54 61 71 83 90 55 55 55 55 55 55 3301 35% 25% 25% 20% 20% 20% -8 -5 -3 0 3 5 408 470 519 601 683 739 119 78 122 87 124 96 128 109 133 124 136 134 380 441 488 568 649 701 130 73 133 81 135 90 139 103 143 118 146 127 352 410 456 533 612 663 143 68 146 76 148 84 152 97 156 111 158 121 324 380 423 498 572 624 156 62 160 70 162 78 166 90 170 104 173 113 296 348 389 460 531 580 170 57 174 64 178 72 182 84 187 97 190 105 266 316 354 421 488 534 183 189 193 199 204 208 51 58 65 77 89 97 55 55 55 55 55 55 1401 Fw 38 43 47 54 61 66 30 / 35 Pf Pa 186 66 218 67 241 68 281 70 321 72 347 74 55 55 55 55 55 55 Data declared according to UNI EN 14511:2013 tu: evaporator outlet water temperature (°C); Pf: cooling capacity (kW); Pa: total absorbed power (kW); Fw: water flow rate with ΔT = 5 °C (m 3 /h). (*): Condenser maximum outlet water temperature. When the condenser temperature is higher than the "t max" the unit doesn't stop but the "unloading" system capacity control is activated. The values in the table are inclusive of ethylene glycol percentage and are calculated with ∆T = 5 °C evaporator and condenser ∆T = 5 °C. To calculate performances at diferring water inlet/outlet ∆T levels, refer to the "∆T correction factors" table. Interpolation is allowed, extrapolation is not permitted. AQUARIUS Plus 2 Inlet / Outlet condenser water temperature [°C] 25 / 30 Pf Pa 200 60 232 61 256 63 297 65 338 67 366 69 In the R (total heat recovery) operating mode the heating capacity is detemined with the following formula: Heating capacity = Cooling capacity + Total absorbed power. 19 PERFORMANCE DATA LOW WATER TEMPERATURE (LWT) Inlet / Outlet condenser water temperature [°C] Glycol 35% 25% 25% 20% 20% 20% tu -8 -5 -3 0 3 5 3202 35% 25% 25% 20% 20% 20% -8 -5 -3 0 3 5 456 523 576 667 758 819 132 135 138 142 146 150 88 97 106 121 138 149 426 491 542 631 719 779 145 148 150 154 158 161 82 91 100 115 131 142 395 458 507 594 682 737 159 76 162 85 164 94 168 108 172 124 175 134 364 424 471 554 638 695 174 70 178 78 180 87 184 101 188 116 191 126 332 389 434 513 593 647 189 64 194 72 197 80 202 93 207 108 210 118 300 353 395 470 545 597 204 58 211 65 215 73 221 85 227 99 230 109 55 55 55 55 55 55 3402 35% 25% 25% 20% 20% 20% -8 -5 -3 0 3 5 481 555 613 713 809 876 141 144 147 152 157 160 92 103 113 130 147 159 449 520 577 674 770 834 155 158 161 165 169 172 86 96 107 122 140 151 416 485 540 633 727 789 170 173 176 180 184 187 80 90 100 115 132 143 383 449 501 591 681 742 186 74 190 83 193 93 197 107 202 124 205 135 349 412 462 547 633 692 202 67 207 76 211 85 217 99 222 115 225 126 315 374 420 501 582 637 218 61 225 69 230 78 237 91 243 106 247 116 55 55 55 55 55 55 3602 35% 25% 25% 20% 20% 20% -8 -5 -3 0 3 5 512 591 653 760 864 935 151 154 157 162 168 172 98 109 121 138 157 170 477 554 615 719 823 890 165 169 172 176 181 185 92 102 114 131 150 162 443 517 575 676 776 843 181 185 188 193 197 200 85 96 106 123 141 153 408 479 535 632 728 792 198 78 203 89 206 99 211 115 216 132 220 144 372 439 493 585 677 739 215 72 222 81 226 91 232 106 237 123 241 134 336 398 448 536 623 682 233 64 241 74 246 83 253 97 260 113 265 124 55 55 55 55 55 55 4002 35% 25% 25% 20% 20% 20% -8 -5 -3 0 3 5 566 650 717 831 944 1021 165 169 172 177 183 188 109 120 133 151 172 186 528 610 674 786 898 972 181 184 187 192 197 201 102 113 125 143 163 177 490 569 631 739 849 921 198 202 205 210 215 219 94 105 117 134 154 167 451 526 586 689 793 865 216 222 225 230 235 239 87 97 108 125 144 157 412 483 539 638 737 804 235 242 246 252 258 262 79 89 100 116 134 146 372 438 491 584 678 742 254 71 263 81 268 91 276 106 283 123 288 135 55 55 55 55 55 55 4302 35% 25% 25% 20% 20% 20% -8 -5 -3 0 3 5 594 689 758 878 996 1077 175 179 183 189 195 200 114 554 127 646 140 713 160 829 181 946 196 1023 192 196 199 204 210 214 106 120 132 151 172 186 513 602 667 780 894 969 210 215 218 223 229 233 99 111 123 142 162 176 472 558 619 727 836 911 229 235 239 245 250 254 91 103 115 132 152 166 431 511 570 673 777 848 249 257 261 268 274 279 83 95 105 122 141 154 388 464 519 616 715 782 269 75 279 86 284 96 293 112 300 130 306 142 55 55 55 55 55 55 AQUARIUS Plus 2 2802 20 30 / 35 Pf Pa Fw 371 130 71 431 133 80 478 135 88 560 139 102 643 142 117 694 145 126 35 / 40 Pf Pa Fw 345 143 66 403 146 75 448 148 83 527 152 96 606 155 110 658 158 120 40 / 45 Pf Pa Fw 318 156 61 372 160 69 417 162 77 493 166 90 569 170 103 619 173 113 45 / 50 Pf Pa Fw 291 170 56 342 175 63 384 178 71 457 182 83 530 187 96 578 190 105 50 / 55 Pf Pa 263 183 311 190 350 194 419 199 488 205 534 208 t max (*) 25 / 30 Pf Pa Fw 398 119 76 460 122 85 508 124 94 592 128 108 674 132 122 727 135 132 Fw 50 57 65 76 89 97 55 55 55 55 55 55 Data declared according to UNI EN 14511:2013 tu: evaporator outlet water temperature (°C); Pf: cooling capacity (kW); Pa: total absorbed power (kW); Fw: water flow rate with ΔT = 5 °C (m 3 /h). (*): Condenser maximum outlet water temperature. When the condenser temperature is higher than the "t max" the unit doesn't stop but the "unloading" system capacity control is activated. The values in the table are inclusive of ethylene glycol percentage and are calculated with ∆T = 5 °C evaporator and condenser ∆T = 5 °C. To calculate performances at diferring water inlet/outlet ∆T levels, refer to the "∆T correction factors" table. Interpolation is allowed, extrapolation is not permitted. In the R (total heat recovery) operating mode the heating capacity is detemined with the following formula: Heating capacity = Cooling capacity + Total absorbed power. PERFORMANCE DATA LOW WATER TEMPERATURE (LWT) tu -8 -5 -3 0 3 5 4902 35% 25% 25% 20% 20% 20% -8 -5 -3 0 3 5 661 771 850 987 1119 1211 193 198 202 208 215 220 127 617 212 143 723 217 157 800 220 179 932 226 203 1064 232 220 1152 236 118 571 232 134 674 238 148 749 241 169 877 247 193 1006 253 209 1090 257 110 526 125 624 138 695 159 818 183 942 198 1025 254 261 265 271 277 281 101 115 129 149 171 186 480 573 640 757 875 955 276 284 289 297 304 309 92 106 118 138 159 174 432 520 583 693 805 881 298 309 315 325 333 339 83 96 108 126 146 160 55 55 55 55 55 55 5202 35% 25% 25% 20% 20% 20% -8 -5 -3 0 3 5 700 804 886 1027 1165 1260 203 207 211 218 225 230 135 653 222 149 755 227 164 834 230 187 972 236 212 1110 242 229 1200 247 126 606 244 140 704 249 154 781 252 177 914 258 202 1047 264 218 1136 269 117 558 130 652 144 726 166 854 190 982 206 1068 266 272 277 283 289 294 107 121 134 155 178 194 510 598 668 790 913 996 289 297 303 310 318 323 98 111 124 144 166 181 460 543 609 724 840 919 313 323 330 339 348 354 88 100 113 132 153 167 55 55 55 55 55 55 5602 35% 25% 25% 20% 20% 20% -8 -5 -3 0 3 5 734 845 931 1079 1223 1323 213 218 222 229 237 243 141 684 233 132 635 255 156 792 238 147 739 261 172 877 242 162 820 265 196 1021 248 185 960 271 222 1164 255 211 1100 278 240 1259 260 229 1192 282 112 534 127 628 141 702 163 830 187 958 204 1045 303 312 317 326 333 339 103 116 130 151 174 190 481 570 639 760 881 964 327 339 346 356 365 372 93 105 118 138 160 175 55 55 55 55 55 55 6002 35% 25% 25% 20% 20% 20% -8 -5 -3 0 3 5 767 884 975 1132 1285 1390 222 228 232 239 247 254 147 716 244 138 664 267 128 612 292 163 829 249 153 774 273 143 717 299 180 919 253 170 860 277 159 800 303 206 1071 259 195 1008 283 183 942 311 234 1224 267 223 1156 290 210 1084 318 253 1324 272 241 1254 295 228 1180 323 107 504 122 597 136 671 159 799 183 929 200 1017 342 354 361 372 382 388 97 110 124 145 169 185 55 55 55 55 55 55 6602 35% 25% 25% 20% 20% 20% -8 -5 -3 0 3 5 825 952 1051 1220 1385 1498 237 243 248 255 264 270 159 770 261 148 715 286 137 659 312 127 602 340 176 893 266 165 834 292 154 772 320 143 709 349 194 990 270 183 927 296 171 862 325 159 794 355 222 1155 277 210 1087 303 198 1015 332 185 941 364 252 1319 284 240 1246 310 226 1169 340 212 1087 373 272 1427 290 259 1353 315 246 1271 345 231 1186 379 116 544 367 131 644 379 147 724 387 171 862 399 198 1001 409 216 1095 416 104 119 134 157 182 199 55 55 55 55 55 55 122 585 279 137 684 286 152 762 290 174 896 297 200 1030 304 217 1121 309 45 / 50 Pf Pa Fw 466 264 90 546 272 101 610 276 113 719 283 131 830 290 151 906 294 165 50 / 55 Pf Pa Fw 420 286 81 495 295 92 555 301 103 658 310 120 763 318 139 835 323 152 t max (*) Glycol 35% 25% 25% 20% 20% 20% 4602 40 / 45 Pf Pa Fw 510 243 98 595 249 110 662 252 122 778 258 141 894 264 162 974 268 177 118 559 317 133 658 326 148 737 332 171 873 340 197 1009 348 214 1101 354 55 55 55 55 55 55 Data declared according to UNI EN 14511:2013 tu: evaporator outlet water temperature (°C); Pf: cooling capacity (kW); Pa: total absorbed power (kW); Fw: water flow rate with ΔT = 5 °C (m 3 /h). (*): Condenser maximum outlet water temperature. When the condenser temperature is higher than the "t max" the unit doesn't stop but the "unloading" system capacity control is activated. The values in the table are inclusive of ethylene glycol percentage and are calculated with ∆T = 5 °C evaporator and condenser ∆T = 5 °C. To calculate performances at diferring water inlet/outlet ∆T levels, refer to the "∆T correction factors" table. Interpolation is allowed, extrapolation is not permitted. In the R (total heat recovery) operating mode the heating capacity is detemined with the following formula: Heating capacity = Cooling capacity + Total absorbed power. AQUARIUS Plus 2 Inlet / Outlet condenser water temperature [°C] 25 / 30 30 / 35 35 / 40 Pf Pa Fw Pf Pa Fw Pf Pa Fw 641 185 123 598 203 115 554 222 107 736 189 136 690 207 128 643 227 119 811 193 150 762 210 141 713 230 132 940 199 171 887 215 161 833 235 151 1064 205 193 1010 221 184 956 241 174 1151 210 209 1095 225 199 1034 245 188 21 PERFORMANCE DATA PARTIAL HEAT RECOVERY (D) Partial heat recovery inlet / outlet water temperature [°C] 1401 1601 1801 2001 2301 2601 3001 3301 2802 3202 3402 3602 4002 4302 4602 4902 5202 5602 6002 6602 30 / 35 Pd Fw 27,6 4,7 28,4 4,9 30,2 5,2 30,7 5,3 41,7 7,2 43,5 7,5 44,8 7,7 55,7 9,6 55,1 9,5 56,8 9,8 58,6 10,1 60,5 10,4 61,4 10,6 72,4 12,4 83,3 14,3 85,2 14,6 87,0 15,0 88,3 15,2 89,7 15,4 111,3 19,1 35 / 40 Pd Fw 25,4 4,4 26,2 4,5 27,9 4,8 28,3 4,9 38,5 6,6 40,2 6,9 41,4 7,1 51,4 8,8 50,9 8,8 52,4 9,0 54,1 9,3 55,8 9,6 56,7 9,7 66,8 11,5 76,9 13,2 78,6 13,5 80,3 13,8 81,5 14,0 82,8 14,2 102,7 17,7 40 / 45 Pd 21,2 21,8 23,3 23,6 32,0 33,5 34,5 42,8 42,4 43,7 45,1 46,5 47,2 55,7 64,1 65,5 66,9 67,9 69,0 85,6 Fw 3,6 3,8 4,0 4,1 5,5 5,8 5,9 7,4 7,3 7,5 7,8 8,0 8,1 9,6 11,0 11,3 11,5 11,7 11,9 14,7 Pd: heating capacity supplied by the partial heat recovery (kW); Fw: water flow rate with ΔT = 5 °C (m 3 /h). Performance data are referred to the following conditions: - evaporator IN/OUT: 12/7 °C; - condenser IN/OUT: 30/35 °C. AQUARIUS Plus 2 PERFORMANCE DATA TOTAL HEAT RECOVERY (R) Total heat recovery inlet / outlet water temperature [°C] 1401 1601 1801 2001 2301 2601 3001 3301 2802 3202 3402 3602 4002 4302 4602 4902 5202 5602 6002 6602 25 / 30 Pd Fw 468 80 519 89 593 102 653 112 731 126 802 138 876 151 944 162 926 159 1040 179 1113 191 1186 204 1300 224 1375 236 1464 252 1538 264 1600 275 1681 289 1763 303 1896 326 30 / 35 Pd Fw 455 78 504 87 576 99 633 109 708 122 780 134 851 146 915 157 900 155 1011 174 1083 186 1154 199 1265 218 1336 230 1424 245 1495 257 1556 268 1636 281 1715 295 1845 317 35 / 40 Pd Fw 441 76 488 84 558 96 614 106 687 118 756 130 825 142 887 153 879 151 984 169 1053 181 1124 193 1227 211 1296 223 1381 238 1453 250 1514 260 1590 273 1670 287 1796 309 Pt: heating capacity supplied by the total heat recovery (kW); Fw: water flow rate with ΔT = 5 °C (m 3 /h). Performance data are referred to the following conditions: - evaporator IN/OUT: 12/7 °C. * LWT version: the maximum outlet water temperature is 55 °C; ** CH versions: the maximum outlet water temperature is 60 °C. 22 40 / 45 Pd Fw 427 73 473 81 540 93 593 102 665 114 732 126 799 137 858 148 852 147 953 164 1019 175 1089 187 1188 204 1255 216 1337 230 1407 242 1466 252 1540 265 1618 278 1740 299 45 / 50 Pd Fw 413 71 458 79 523 90 575 99 644 111 709 122 774 133 831 143 829 143 925 159 989 170 1058 182 1152 198 1217 209 1296 223 1365 235 1424 245 1494 257 1571 270 1690 291 50 / 55* Pd Fw 400 69 442 76 506 87 555 95 622 107 684 118 747 128 802 138 801 138 895 154 956 164 1022 176 1112 191 1175 202 1253 215 1318 227 1374 236 1444 248 1516 261 1631 281 55 / 60** Pd Fw 383 66 425 73 485 83 532 92 597 103 658 113 718 124 771 133 772 133 860 148 919 158 984 169 1070 184 1130 194 1203 207 1267 218 1323 228 1388 239 1460 251 1570 270 HYDRAULIC DATA Evaporator - CH -HP - ME Type Water flow rate (1) m 3 /h Pressure drop (2) kPa Water content l Water connections in Evaporator - LWT Type Water flow rate (1) Pressure drop (2) Water content Water connections Condenser Type Number Water flow rate (1) m 3 /h kPa l in n° m3/h 1401 1601 1801 24 / 104 8 / 118 113 DN100 (4") 23 / 97 7 / 92 170 DN125 (5") 34 / 146 7 / 103 164 DN125 (5") 18 / 74 11 / 159 113 DN100 (4") 18 / 72 11 / 146 170 DN125 (5") 25 / 99 11 / 154 164 DN125 (5") 1 1 1 1 2301 2601 3001 3301 Shell and tube 34 / 146 45 / 196 8 / 115 11 / 172 158 152 DN125 (5") DN125 (5") 34 / 146 5 / 75 270 DN150 (6") 42 / 182 5 / 76 262 DN150 (6") 57 / 243 7 / 92 255 DN150 (6") Shell and tube 30 / 119 30 / 119 12 / 157 12 / 180 158 152 DN125 (5") DN125 (5") 31 / 124 9 / 121 270 DN150 (6") 31 / 124 10 / 141 262 DN150 (6") 38 / 149 10 / 139 255 DN150 (6") 1 1 1 1 36 / 118 9 / 100 56 G 4" 37 / 128 9 / 109 59 G5" 43 / 140 9 / 100 67 G 5" 48 / 159 9 / 100 75 G 5" 52 / 172 9 / 100 82 G 5" 58 / 191 9 / 100 90 G 5" 62 / 204 9 / 100 96 G 5" 1 1 1 1 1 1 1 9 / 99 103 G 5" 36 / 118 9 / 100 120 G 5" 37 / 128 9 / 109 124 G 5" 43 / 140 9 / 100 140 G 5" 48 / 159 9 / 100 157 G 5" 52 / 172 9 / 100 169 G 5" 58 / 191 9 / 100 193 G 6" 62 / 204 9 / 100 205 G 6" 5 G 3/4" 5 G 3/4" 5 G 3/4" Shell and tube 5 7 G 3/4" G 3/4" 7 G 3/4" 7 G 3/4" 10 G 1 1/4" Shell and tube 30 / 99 Pressure drop (2) kPa 9 / 99 Water content l 48 Water connections in G 4" Condenser / Total heat recovery - R Type Number n° 1 Water flow rate (3) m3/h 30 / 99 Pressure drop (2) kPa Water content l Water connections in Partial heat recovery - D Type Water content l Water connections in 2001 Shell and tube (1) Minimum and maximum allowed water flow rate (m3 /h); (2) Pressure drops referred to min/max allowed flow rate (kPa); (3) Minimum and maximum water flow rate referred to condenser or heat recovery water circuit (m3 /h). Type Shell and tube Water flow rate (1) m 3 /h 38 / 150 46 / 180 58 / 226 58 / 226 53 / 211 53 / 211 66 / 264 Pressure drop (2) kPa 10 / 131 11 / 143 12 / 153 12 / 153 10 / 138 11 / 154 10 / 128 Water content l 325 307 298 298 512 501 492 Water connections in DN150 (6") DN150 (6") DN150 (6") DN150 (6") DN200 (8") DN200 (8") DN200 (8") Condenser Type Shell and tube Number n° 2 2 2 2 2 2 2 Water flow rate (1) m 3 /h 60 / 199 71 / 236 74 / 236 74 / 256 85 / 281 96 / 293 96 / 317 Pressure drop (2) kPa 9 / 99 9 / 100 9 / 96 9 / 109 9 / 100 10 / 97 9 / 100 Water content l 96 112 115 118 134 142 150 Water connections in G 4" G 4" G 5" G 5" G 5" G 5" G 5" Condenser / Total heat recovery - R Type Shell and tube Number n° 2 2 2 2 2 2 2 Water flow rate (3) m3/h 60 / 199 71 / 236 74 / 236 74 / 256 85 / 281 96 / 293 96 / 317 Pressure drop (2) kPa 9 / 99 9 / 100 9 / 96 9 / 109 9 / 100 10 / 97 9 / 100 Water content l 206 240 244 248 280 297 314 Water connections in G 5" G 5" G 5" G 5" G 5" G 5" G 5" Partial heat recovery - D Type Shell and tube Water content 10 10 10 10 10 12 14 l Water connections G 3/4" G 3/4" G 3/4" G 3/4" G 3/4" G 3/4" G 3/4" in 66 / 264 66 / 264 66 / 264 66 / 264 88 / 353 10 / 132 10 / 132 10 / 142 10 / 142 12 / 153 492 492 481 481 470 DN200 (8") DN200 (8") DN200 (8") DN200 (8") DN200 (8") 2 2 2 2 2 104 / 332 104 / 344 115 / 359 115 / 381 124 / 408 10 / 101 9 / 100 10 / 99 9 / 100 9 / 100 157 164 172 180 192 G 5" G 5" G 5" G 5" G 5" 2 2 2 2 2 104 / 332 104 / 344 115 / 359 115 / 381 124 / 408 10 / 101 9 / 100 10 / 99 9 / 100 9 / 100 326 338 362 386 410 G 5" G 5" G 6/5" G 6" G 6" 14 G 3/4" 14 G 3/4" 14 G 3/4" 14 G 3/4" AQUARIUS Plus 2 2802 3202 3402 3602 4002 4302 4602 4902 5202 5602 6002 6602 Evaporator - CH -HP - ME Type Shell and tube Water flow rate (1) m 3 /h 42 / 179 52 / 222 68 / 297 68 / 297 60 / 259 80 / 347 80 / 343 80 / 347 80 / 347 80 / 343 80 / 347 80 / 347 Pressure drop (2) kPa 6 / 84 7 / 97 9 / 138 9 / 138 6 / 80 6 / 87 7 / 91 7 / 93 7 / 93 7 / 98 7 / 100 8 / 107 Water content l 325 307 298 298 512 501 492 492 492 481 481 470 Water connections in DN150 (6") DN150 (6") DN150 (6") DN150 (6") DN200 (8") DN200 (8") DN200 (8") DN200 (8") DN200 (8") DN200 (8") DN200 (8") DN200 (8") Evaporator - LWT 20 G1 1/4" (1) Minimum and maximum allowed water flow rate (m3 /h); (2) Pressure drops referred to min/max allowed flow rate (kPa); (3) Minimum and maximum water flow rate referred to condenser or heat recovery water circuit (m3 /h). 23 PRESSURE DROPS pressure drops (kPa) EVAPORATOR PRESSURE DROPS - CH - HP 1 1: 1401 2: 1601 3: 1801 4: 2001 5: 2301 6: 2601 7: 3001 8: 3301 9: 2802 10: 3202 11: 3402 - 3602 12: 4002 13: 4302 14: 4602 - 4902 - 5202 15: 5602 - 6002 16: 6602 5 4 16 3 100 10 15 11 2 14 13 8 9 12 7 6 50 0 0 50 100 150 200 250 300 350 400 water flow FW (m 3 /h) pressure drops (kPa) EVAPORATOR PRESSURE DROPS - LWT 1: 1401 2: 1601 3: 1801 4: 2001 5: 2301 6: 2601 7: 3001 8: 3301 9: 2802 10: 3202 11: 3402 - 3602 12: 4002 13: 4302 14: 4602 - 4902 - 5202 15: 5602 - 6002 16: 6602 5 1 150 4 3 2 13 7 8 10 16 11 15 12 9 14 6 50 0 50 100 150 200 250 300 350 400 CONDENSER AND TOTAL HEAT RECOVERY PRESSURE DROPS 1: 1401 2: 1601 3: 1801 4: 2001 5: 2301 6: 2601 7: 3001 8: 3301 9: 2802 10: 3202 11: 3402 - 3602 12: 4002 13: 4302 14: 4602 - 4902 - 5202 15: 5602 - 6002 16: 6602 3 1 100 2 5 4 6 7 9 8 12 10 11 13 15 14 16 50 0 24 0 water flow FW (m 3 /h) pressure drops (kPa) AQUARIUS Plus 2 100 0 50 100 150 200 250 300 350 400 450 water flow FW (m 3 /h) WORKING LIMITS CH - HP - R - D External ambient temperature Evaporator inlet water temperature Evaporator outlet water temperatute Delta T of the water (2) Condenser inlet water temperature (3) Condenser outlet water temperature Condenser water Delta T (2) Pressure evaporator water side Pressure condenser water side °C °C °C °C °C °C °C bar bar LWT External ambient temperature (*) Evaporator inlet water temperature Evaporator outlet water temperature (1) Evaporator water delta T (2) Condenser inlet water temperature (3) Condenser outlet water temperature Condenser water delta T (2) Pressure evaporator water side Pressure condenser water side °C °C °C °C °C °C °C bar bar Min -10 3 (1) 0 (1) 3 23 27 4 0 0 Max 43 25 20 8 55 60 7 10 10 Min -10 -5 -8 3 20 24 4 0 0 Max 43 10 5 8 50 55 7 10 10 The values are referred to operation of the unit at full load. (*) For external air temperature lower than 0 °C you must add a suitable quantity of antifreeze solution. 1) For water outlet temperatures lower than 6 °C you must add a suitable quantity of antifreeze solution. 2) Comply with the exchanger minimum and maximum flow rate values. 3) The limits for the inlet temperature of the condenser are referred to operation without a pressure control valve. CH - HP - R - D VERSIONS 60 55 50 45 Antifreeze solutions 40 35 30 25 20 15 -5 0 5 10 15 20 25 Evaporator outlet water temperature °C AQUARIUS Plus 2 Condenser outlet water temperature °C 65 25 Condenser outlet water temperature °C LWT VERSION 60 55 50 45 40 Antifreeze solutions 35 30 25 20 15 -10 -8 -6 -2 -4 4 2 0 6 8 Evaporator outlet water temperature °C THERMAL INSULATION THICKNESS LIMITS Standard insulation thickness 10 mm (*) AQUARIUS Plus 2 Ambient temperature Water outlet temperature 20 °C 30 °C 35 °C +10 mm (*) 40 °C 45 °C 47 °C RH Max -5 °C 83% 72% 68% 65% 63% 61% 80% 0 °C 90% 80% 73% 70% 67% 65% 82% 7 °C 97% 87% 77% 75% 73% 68% 83% 15 °C 99% 95% 85% 82% 78% 75% 86% The values in the table refer to the thickness of the thermal insulation of the hydraulic circuit and they show the maximum relative humidity above which ambient moisture condenses (these values are ot the operation limits of the chillers). (*) Closed cell thermal insulation. CORRECTION FACTORS CORRECTION FACTORS ∆T ≠ 5 °C ∆T Evaporator Cooling capacity correction factor Absorbed power correction factor k1 Kp1 3 4 5 6 7 0,992 1,039 0,996 1,021 1,000 1,000 1,010 0,996 1,020 0,991 ∆T Condenser Tower water Cooling capacity correction factor Absorbed power correction factor k1 Kp1 4 5 6 7 8 1,002 1,016 1,000 1,000 0,996 1,001 0,992 1,002 0,988 1,003 Multiply the unit performance by the correction factors given in table (P* = P_ x K1, Pa* = Pa x Kp1 where P_= Ph o Pf ). The new water flow to the evaporator is calculated by means of the following equation Fw (l/h) = P* (kW) x 860 / ∆T where ∆T of the water through the evaporator (°C). SOLUTIONS OF WATER AND ETHYLENE GLYCOL Cooling capacity correction factor Absorbed power correction factor Water flow correction factor (1) Pressure drop correction factor 26 10 °C K2 Kp2 KFWE2 Kdp2 10 0,982 0,997 1,010 1,094 % Ethylene glycol by weight 20 30 40 0,976 0,968 0,957 0,997 0,997 0,997 1,030 1,066 1,091 1,250 1,375 1,563 50 0,943 0,996 1,115 1,721 Multiply the unit performance by the correction factors given in the table (es. Pf(new) = Pf x K2); (1) KFWE2 = correction factor (referred to the cooling capacity/heating capacity corrected by K2) to obtain the water flow with a 5 °C. FOULING FACTORS Evaporator fouling factors (m2 °C/W) Cooling capacity correction factor Absorbed power correction factor 0 1 1 k4 Kp4 0,000043 0,986 0,996 0,000086 0,973 0,992 0,000172 0,947 0,984 0,000344 0,903 0,970 Tower water condenser fouling factors (m2 °C/W) Cooling capacity correction factor Absorbed power correction factor 0 1 1 k4 Kp4 0,000043 0,996 1,006 0,000086 0,992 1,011 0,000172 0,984 1,023 0,000344 0,968 1,047 To determine the effect of fouling on the heat exchanger water/refrigerant, multiply the cooling capacity Pf by k4 and the absorbed power Pa by kp4. (ex. Pf(new) = Pf x k4, Pa(new) = Pa x kp4). SELECTION TABLES FOR PRESSURE CONTROL VALVES AND MODULATING VALVES inch 1”1/2 2” 2”1/2 3” 4” WVS 40 WVS 50 WVS 65 WVS 80 WVS 100 Flow rate kv Min m 3 /h 13 16 24 40 55 m 3 /h 21 32 45 80 125 Connections kv Max Flow rate inch 1”1/2 2” 2”1/2 3” 4” 5” m 3 /h 25 40 63 100 130 200 m 3 /h 22 36 56 89 116 179 available head pressure (kPa) 3FGB DN 40 3FGB DN 50 3FGB DN 65 3FGB DN 80 3FGB DN 100 3FGB DN 125 1 250 2 3 4 5 150 100 available head pressure (kPa) Modulating valves Max m 3 /h 19 29 40 72 112 Max. differential pressure Adjustment Closing bar bar 2 11,7 2 7,3 2 3,7 2 2,4 1,5 1,5 1 1 1 150 2 3 4 5 6 100 50 50 25 10 50 100 200 10 10 water flow FW (m 3 /h) 1: WVS 40 2: WVS 50 3: WVS 65 4: WVS 80 5: WVS 100 50 100 150 200 water flow FW (m 3 /h) 1: 3FGB DN 40 2: 3FGB DN 50 3: 3FGB DN 65 4: 3FGB DN 80 5: 3FGB DN 100 6: 3FGB DN 125 AQUARIUS Plus 2 Connections Pressure control valves The maximum flow rates are calculated allowing a pressure drop of 80 kPa with the valve fully open. When using modulating valves check the maximum control and closing differential pressure values; if these limits are not complied with, consult our sales department for an ad hoc selection. 27 OVERALL DIMENSIONS VERSIONS: CH - HP - LWT 1401 - 1601 - 1801 - 2001 - 2301 - 2601 - 3001 - 3301 OPTIONAL OPTIONAL 1401 2601 1601 3001 1801 3301 2001 OPTIONAL 2301 AQUARIUS Plus 2 OPTIONAL 28 CH - HP - LWT I L M N P R IN/OUT Condenser in B C D E F G 1401 4344 1640 1460 1137 2070 1137 1380 929 2486 929 340 343 837 340 DN100 (4”) G 4” 1601 4344 1645 1460 1452 1715 1177 1380 947 2450 947 340 322 856 340 DN125 (5”) G 4” Model H IN/OUT Evaporator in A mm 1801 4326 1721 1460 1498 1685 1143 1380 938 2450 938 340 329 846 340 DN125 (5”) G 5” 2001 4326 1721 1485 1388 1795 1143 1405 938 2450 938 340 354 846 340 DN125 (5”) G 5” 2301 4326 1645 1485 1438 1745 1143 1405 938 2450 938 340 354 846 340 DN125 (5”) G 5” 2601 4326 1770 1460 1473 1710 1143 1380 957 2412 957 385 287 893 415 DN150 (6”) G 5” 3001 4334 1819 1460 1421 1770 1143 1380 965 2412 957 385 287 893 415 DN150 (6”) G 5” 3301 4334 1819 1460 1414 1777 1143 1380 965 2412 957 385 282 893 415 DN150 (6”) G 5” : Evaporator water inlet : Condenser water inlet : Water discharge: Rp 1/2" : Evaporator water outlet : Condenser water outlet : Air vent: Rp 1/2" : Power supply 2802 - 3202 - 3402 - 3602 - 4002 - 4302 - 4602 - 4902 - 5202 - 5602 - 6002 - 6602 CH - HP - LWT H I L M N P R IN/OUT Evaporator in IN/OUT Condenser in A B C D E F G 2802 4906 2165 1133 2369 1404 1039 2962 905 835 - - - - - DN150 (6”) G 4” 3202 4906 2165 1133 2369 1404 1039 2962 905 835 - - - - - DN150 (6”) G 4” Model mm 3402 4919 2165 1407 2369 1503 1039 2962 918 835 - - - - - DN150 (6”) G 5” 3602 4919 2165 1035 2558 1326 1039 2962 918 835 - - - - - DN150 (6”) G 5” 4002 4922 2278 1146 2369 1407 1063 2910 949 899 - - - - - DN200 (8”) G 5” 4302 4922 2278 1146 2369 1407 1063 2910 949 899 - - - - - DN200 (8”) G 5” 4602 4922 2278 1146 2369 1407 1063 2910 949 899 - - - - - DN200 (8”) G 5” 4902 4922 2278 1126 2369 1427 1063 2910 949 899 - - - - - DN200 (8”) G 5” 5202 4922 2278 1146 2369 1407 1063 2910 949 899 - - - - - DN200 (8”) G 5” 5602 4970 2278 1120 2379 1470 1060 2910 1000 899 - - - - - DN200 (8”) G 5” 6002 4970 2278 1145 2369 1460 1060 2910 1000 899 - - - - - DN200 (8”) G 5” 6602 4972 2278 1146 2369 1457 1065 2910 997 899 - - - - - DN200 (8”) G 5” : Evaporator water inlet : Condenser water inlet : Water discharge: Rp 1/2" : Evaporator water outlet : Condenser water outlet : Air vent: Rp 1/2" AQUARIUS Plus 2 OPTIONAL : Power supply 29 OVERALL DIMENSIONS WITH PARTIAL HEAT RECOVERY (D) VERSIONS 1401 - 1601 - 1801 - 2001 - 2301 - 2601 - 3001 OPTIONAL OPTIONAL 1401 2601 1601 3001 1801 2001 OPTIONAL OPTIONAL 2301 AQUARIUS Plus 2 3301 30 OPTIONAL D - Partial Heat Recovery Model 1401 A B C D E F G H I L M N P R S T U IN/OUT Evaporator IN/OUT Condenser IN/OUT Partial heat recovery mm in in in 4330 1668 1460 1130 2070 1130 1380 922 2486 922 340 312 801 273 454 310 340 DN100 (4”) G 5” G 3/4” 1601 4331 1668 1460 1445 1715 1170 1380 940 2450 940 340 304 819 263 454 300 340 DN125 (5”) G 5” G 3/4” 1801 4331 1721 1460 1500 1685 1145 1380 940 2450 940 340 324 809 253 454 290 340 DN125 (5”) G 5” G 3/4” 2001 4330 1645 1485 1388 1795 1143 1405 940 2450 940 340 334 809 268 454 305 340 DN125 (5”) G 5” G 3/4” 2301 4330 1645 1485 1440 1745 1145 1405 940 2450 940 340 332 809 270 454 307 340 DN125 (5”) G 5” G 3/4” 2601 4331 1770 1460 1475 1710 1145 1380 959 2412 959 385 270 856 260 529 297 415 DN150 (6”) G 5” G 3/4” 3001 4337 1819 1460 1405 1770 1155 1380 959 2412 959 385 272 856 258 529 295 415 DN150 (6”) G 5” G 3/4” 3301 4398 1952 1460 1420 1777 1200 1380 993 2412 993 435 230 930 300 578 300 435 DN150 (6”) G 6” G 1 1/4” : Evaporator water inlet : Condenser water inlet : Water inlet heat recovery : Water discharge: Rp 1/2" : Evaporator water outlet : Condenser water outlet : Water outlet heat recovery : Air vent: Rp 1/2" : Power supply 2802 - 3202 - 3402 - 3602 - 4002 - 4302 - 4602 - 4902 - 5202 - 5602 - 6002 OPTIONAL OPTIONAL D - Partial Heat Recovery Model A B C D E F G H I L M N P R S T U mm IN/OUT Evaporatore in IN/OUT IN/OUT Condensatore Partial heat recovery in in 2802 4906 2165 1133 2369 1404 1039 2962 905 835 - - - - - - - - DN150 (6”) G 5” G 3/4” 3202 4906 2165 1133 2369 1404 1039 2962 905 835 - - - - - - - - DN150 (6”) G 5” G 3/4” 3402 4919 2165 1407 2369 1503 1039 2962 918 835 - - - - - - - - DN150 (6”) G 5” G 3/4” 3602 4919 2165 1035 2558 1326 1039 2962 918 835 - - - - - - - - DN150 (6”) G 5” G 3/4” 4002 4922 2278 1146 2369 1407 1063 2910 949 899 - - - - - - - - DN200 (8”) G 5” G 3/4” 4302 4922 2278 1146 2369 1407 1063 2910 949 899 - - - - - - - - DN200 (8”) G 5” G 3/4” 4602 4922 2278 1146 2369 1407 1063 2910 949 899 - - - - - - - - DN200 (8”) G 5” G 3/4” 4902 4922 2278 1126 2369 1427 1063 2910 949 899 - - - - - - - - DN200 (8”) G 5” G 3/4” 5202 4922 2278 1146 2369 1407 1063 2910 949 899 - - - - - - - - DN200 (8”) G 5” G 3/4” 5602 4971 2278 1120 2379 1470 1065 2910 997 899 - - - - - - - - DN200 (8”) G 5” G 3/4” 6002 4971 2278 1145 2369 1458 1065 2910 997 899 - - - - - - - - DN200 (8”) G 5” G 3/4” 6602 4972 2380 1145 2369 1458 1065 2910 997 1001 - - - - - - - - DN200 (8”) G 6” G 1 1/4” AQUARIUS Plus 2 6602 : Evaporator water inlet : Condenser water inlet : Water inlet heat recovery : Water discharge: Rp 1/2" : Evaporator water outlet : Condenser water outlet : Water outlet heat recovery : Air vent: Rp 1/2" : Power supply 31 OVERALL DIMENSIONS WITH TOTAL HEAT RECOVERY (R) VERSIONS 1401 - 1601 - 1801 - 2001 - 2301 - 2601 - 3001 - 3301 OPTIONAL 1401 1601 1801 2001 2301 OPTIONAL 2601 3001 3301 OPTIONAL AQUARIUS Plus 2 OPTIONAL 32 R - Total Heat Recovery Model A B C D E F G H I L M N P R S T U mm IN/OUT Evaporator in IN/OUT Condenser in IN/OUT Total heat recovery in 1401 4470 1768 1460 1200 2070 1200 1380 992 2486 992 440 265 775 420 415 220 415 DN100 (4”) G 5” G 5” 1601 4470 1763 1460 1485 1745 1240 1380 1010 2450 1010 435 247 793 420 415 220 415 DN125 (5”) G 5” G 5” 1801 4470 1816 1485 1495 1745 1230 1405 1010 2450 1010 435 262 783 440 415 240 415 DN125 (5”) G 5” G 5” 2001 4470 1816 1485 1440 1795 1235 1405 1010 2450 1010 435 262 783 440 415 240 415 DN125 (5”) G 5” G 5” 2301 4470 1816 1485 1482 1745 1243 1405 1010 2450 1010 435 262 783 440 415 240 415 DN125 (5”) G 5” G 5” 2601 4470 1848 1460 1485 1710 1275 1380 1029 2412 1029 385 210 830 420 415 220 415 DN150 (6”) G 5” G 5” 3001 4474 1992 1485 1460 1777 1237 1405 1031 2412 1031 475 222 827 436 479 184 479 DN150 (6”) G 6” G 6” 3301 4474 1992 1485 1380 1777 1317 1405 1031 2412 1031 475 222 827 436 479 184 479 DN150 (6”) G 6” G 6” : Evaporator water inlet : Condenser water inlet : Water inlet heat recovery : Water discharge: Rp 1/2" : Evaporator water outlet : Condenser water outlet : Water outlet heat recovery : Air vent: Rp 1/2" : Power supply 2802 - 3202 - 3402 - 3602 - 4002 - 4302 - 4602 - 4902 - 5202 OPTIONAL OPTIONAL R - Total Heat Recovery Model A B C D E F G H I L M N P R S T U mm IN/OUT Evaporator in IN/OUT Condenser in IN/OUT Total heat recovery in 2802 4906 2357 1133 2369 1404 1039 2963 904 1027 - - - - - - - - DN150 (6”) G 5” G 5” 3202 4906 2357 1133 2369 1404 1039 2963 904 1027 - - - - - - - - DN150 (6”) G 5” G 5” 3402 4919 2357 1407 2369 1503 1039 2963 917 1027 - - - - - - - - DN150 (6”) G 5” G 5” 3602 4919 2357 1035 2558 1326 1039 2963 917 1027 - - - - - - - - DN150 (6”) G 5” G 5” 4002 4922 2380 1146 2369 1407 1063 2910 949 1001 - - - - - - - - DN200 (8”) G 5” G 5” 4302 4922 2380 1146 2369 1407 1063 2910 949 1001 - - - - - - - - DN200 (8”) G 5” G 5” 4602 4922 2380 1146 2369 1407 1063 2910 949 1001 - - - - - - - - DN200 (8”) G 5” G 5” 4902 4922 2380 1146 2369 1407 1063 2910 949 1001 - - - - - - - - DN200 (8”) G 5” G 5” 5202 4922 2380 1146 2369 1407 1063 2910 949 1001 - - - - - - - - DN200 (8”) G 5” G 5” 5602 4971 2472 1145 2369 1458 1065 2910 997 1092 - - - - - - - - DN200 (8”) G 6” G 6” 6002 4971 2472 1145 2369 1458 1065 2910 997 1092 - - - - - - - - DN200 (8”) G 6” G 6” 6602 4972 2470 1145 2369 1458 1065 2910 997 1092 - - - - - - - - DN200 (8”) G 6” G 6” AQUARIUS Plus 2 5602 - 6002 - 6602 : Evaporator water inlet : Condenser water inlet : Water inlet heat recovery : Water discharge: Rp 1/2" : Evaporator water outlet : Condenser water outlet : Water outlet heat recovery : Air vent: Rp 1/2" : Power supply 33 INSTALLATION GUIDE Installation of the units described in this catalogue must be performed in observance of the following prescriptions: a) Install the unit in a perfectly horizontal position to ensure correct oil return to the compressors. b) Maintain the specified clearances around the unit. c) Where possible, install the machine in a way to minimise the effects of noise, vibration, etc. In particular, do not to install the machine in areas where the noise could cause nuisance as under windows or between two residences. The vibrations transmitted to the ground must be reduced by using anti-vibration mounts, flexible joints on the water pipelines and on the conduit containing the cable of the electrical supply. d) Electrical installation works must be carried out by a specialist in accordance with the wiring diagrams and in compliance with the current regulations in force in the country where the unit are installed. e) Make the hydraulic connections, installing the following: - flexible couplings; - shut-off valves; - bleed valves in the uppermost sections of the plant; - safety valve; - grain valves in the lowermost points of the plant; - pump and expansion tank; - flow switch; - metal mesh filter with the mesh size not exceeding 1 mm installed on water inlet side of the evaporator and condensers, in order to protect the heat exchanger from impurities present in the system. f) If the total volume of the hydraulic circuit is insufficient, install a water storage tack down-line from the user side exchanger; the storage tank serves to reduce the range of fluctuations of chilled water temperature while simultaneously optimising the energy efficiency of the unit. The following table shows the minimum water contents of the installation referred to nominal operating conditions, with the standard settings of the electronic controller parameters: Minimum volume [m 3] AQUARIUS Plus 2 Minimum volume [m 3] 34 Minimum volume [m 3] 1401 1601 1801 2001 2301 2601 3001 3301 4,7 5,3 6,0 6,6 7,5 8,2 9,0 9,7 2802 3202 3402 3602 4002 4302 4602 4902 4,7 5,3 5,7 6,0 6,6 7,0 7,5 7,8 5202 5602 6002 6602 8,2 8,6 9,0 9,7 g) In the case of cooling capacity requirements that are higher than the maximum capacities available with a single unit, the chillers can be connected in parallel on the hydraulic circuit, ideally selecting identical units in order to avoid situations of imbalance of water flow rates. h) If it is necessary to treat water flow rates that are higher than the maximum permissible flow rate associated with the unit, it is advisable to set up a by-pass between the chiller inlet and outlet. i) If it is necessary to treat water flow rates that are lower than the minimum permissible flow rate associated with the chiller, it is advisable to set up a by-pass between the chiller outlet and inlet. l) Carefully bleed all air from the hydraulic circuit because even a small amount of air the circuit can cause the evaporator to freeze. m) Always drain the hydraulic circuit during winter shutdowns; alternatively, ensure the circuit is filled with a suitable antifreeze solution. 09-14 The images of the products in the document are for illustrative purposes only and therefore do not have any contractual value. 5050EAQP2001AA M.T.A. S.p.A. Viale Spagna, 8 ZI 35020 Tribano (PD) Italy MTA France S.A. Tel: +33 04 7249 8989 www.mtafrance.fr Tel. +39 049 9588611 Fax +39 049 9588676 MTA Deutschland GmbH Tel: +49 (2157) 12402 - 0 www.mta.de info@mta-it.com www.mta-it.com Milan branch office Tel. +39 02 95738492 Novair-MTA, S.A. (España) Tel: +34 938 281 790 www.novair-mta.com SC MTA ROMÂNIA Srl Tel: +40 723 022023 www.mta-it.ro MTA is represented in over 80 countries worldwide. For information concerning your nearest MTA representative please contact M.T.A. S.p.A. The continuous improvement of MTA's products can cause some variations in the information herein even without prior notice. Reproduction in whole or in part is forbidden. MTA is ISO9001 certified, a sign of its commitment to complete customer satisfaction. MTA products comply with European safety directives, as recognised by the CE symbol. MTA USA, LLC Tel: +1 716 693 8651 www.mta-usa.com MTA Australasia Pty Ltd Tel: +61 1300 304 177 www.mta-au.com MTA partecipates in the E.C.C. programme for LCP-HP. Certified products are listed on: www.eurovent-certification.com. Eurovent Certification applied to the units: - Air/Water with cooling capacity up to 600 kW -Water/Water up to 1500 kW GOST Certification
Similar documents
WQL/WQH/ WQRC
protection to the corrosion. The painting is a polyester powder based type, coloured in RAL 9001. The units are suitable for indoor installation.
More informationlista de preturi 2013
Agregate pentru racirea apei (CHILLER) cu condensatoare racite cu aer MULTI-POWER (199-1.051 kW) Pompe de caldura aer/apa cu productie de apa calda menajera cu tehnologie AQUALOGIK seria MIDY LINE ...
More information