DETECT-A
Transcription
DETECT-A
DETECT-A-FIRE® Detection and Release Devices Detection and Release Devices Fenwal® and DETECT-A-FIRE® are registered trademarks of Kidde-Fenwal Incorporated, Ashland, Massachusetts, USA DETECT-A-FIRE® Detection and Release Devices FEATURES Repeatable - resets itself, nothing to replace, testable Rugged - withstands shock and vibration Versatile - available various temperature settings Durable - long lasting stainless steel shell Economical - wide spacing reduce installation costs Factory set internal contact area is hermetically sealed in stainless steel APPLICATIONS Protection of schools, factories, offices, libraries, etc. Power generation Gas station Paint spray booths Range hoods GENERAL DESCRIPTION DETECT-A-FIRE units are the “heart”of many Fire Protection Systems. These highly reliable devices have been a standard of the industry for over 45 years. Many thousands of these units are now in use controlling the release of extinguishants such as clean agents, CO2, water, or dry chemicals. In some systems the device is used as an ALARM device, to sense overheat or fire, and alert personnel. In other systems, it is used as a RELEASE device, to sense fire and actuate fire attack systems. DETECT-A-FIRE units have met with wide acceptance because they are designed with RATE COMPENSATION. This provides a unique advantage over both fixed temperature and rate-of-rise types of detectors because only the DETECT-A-FIRE unit accurately senses the surrounding air temperature regardless of the fire growth rate. At precisely the predetermined danger point, the system is activated. Fixed temperature detectors must be completely heated to alarm temperature and therefore a disastrous lag in time may occur with a fast rate fire. Rate-of-rise devices, on the other hand, are triggered by the rate of increase in ambient temperature and are subject to false alarms caused by harmless, transient thermal gradients such as the rush of warm air from process ovens. The secret of the unit’s sensitivlty is in the design (figure 1). The outer shell is made of a rapidly expanding alloy which closely follows changes in surrounding air temperature. The inner struts are made of a lower expanding alloy. Designed to resist thermal energy absorption and sealed inside the shell, the struts fol- low temperature changes more slowly. A slow rate fire (fIgure 2) will heat the shell and struts together. At the “set point”, the unit will trigger, actuating the alarm or releasing the extinguishant. A transient rush of warm air up to 40F°/min. may expand the shell, but not enough to trigger the unit. By ignoring transient warm air excursions, the DETECT-A-FIRE unit virtually eliminates false alarms prevalent with rate - of - rise devices. If a last rate fire (figure 3) starts, the shell will expand rapidly. The struts will close, actuating the alarm or releasing the agent. The faster the fire rate of growth, the sooner the DETECT-A-FIRE unit will react. This chart shows three categories of fire detection devices and their relative response levels for reaction to three different rate - of - rise conditions. Statistics indicate that 97% of all fires fall within these categories. RATE - OF - RISE Type of Under Between Over device 10°F/min. 10÷40°F/min 40°F/min Rate Second Compensated FIRST FIRST but at selected DETECT-A-FIRE protection level Unit Fixed SECOND SECOND THIRD Temperature Rate-of-Rise Will not operate Will not operate FIRST unless fixed unless fixed but may be a temperature temperature false alarm supplement supplement at 165°F is at 165°F is provided, then it provided, then it is THIRD in is THIRD in sequence sequence DETECT-A-FIRE® Detection and Release Devices by Terry Ferraris & C. Milano - Italy SPECIFICATION HORIZONTAL DETECT-A-FIRE UNITS HORIZONTAL DETECT-A-FIRE UNITS Horizontal detectors are designed for locations where appearance is a factor. The attractive, functional design lends physical protection of the unit while making it suitable for commerciaI, industriaI, mercantile and public buildings, institutions and ships in non-hazardous locations (those classified as “ordinary” under the National Electric Code). Flush mounted units are designed to fit standard 4” octagonal electrical boxes and surface mounting units are designed to mount directly on ceilings or on 4” electrical junction boxes. Canadian Electrical Code requires mounting only to an electrical junction box. VERTICAL DETECT-A-FIRE UNITS Vertical detectors are designed for use in both “ordinary” or “hazardous” locations. For “ordinary” use, they may be mounted to any approved junction box with 7/8” diameter opening by using 1/2- 14 NPT mounting nuts. The device may be wired in or out of conduit, depending on local preference and codes. Four leadwires are provided on normally open vertical units (that close on temperature rise), per UL requirement, to facilitate supervision of system wiring. Instruments are Underwriters Laboratory and Underwriters Laboratory of Canada listed and Factory MutuaI approved for hazardous locations, when mounted in a suitable fitting. Dimensions in inch Contract Operation on Temp. Rise Approx. weight per unit Electrical Rating (resistive only) 12-X27020-000 Opens 284g 5.0 Amps 125 VAC listed fitting in accordance 12-X27020-001 (325°F Max ) 0.5 Amps 125 VDC 12 - X28020-003 with National Eletric Code 12 - X28021-005 and/or local authority 12-X27021-000 Closes 5.0 Amps 125 VAC Class I, groups, B ,C 12 - X27120-000 having jurisdiction 12-X27021-001 (325°F Max) and D; Class II 12 - X27121-000 Hazardous Location Detector type Fitting required for UL & ULC Listings and FM approval Class I, groups A, B 12 - X27120-022 Mount detector to a suitable C and D; Class II 12 - X27121-020 Groups E, F, and G Model no. 284g 0.5 Amps 125 VDC 2.0 Amps 24 VDC 1.0 Amps 48 VDC Groups E, F, and G CONSTRUCTION NOTE A: Spacings shown are distances between units on smooth ceiIings: the distances from partitions or walls would be half that shown. Authority having local jurisdiction should be consulted before installation. Stainless steel shell sensing element. Cold rolled steel mounting facility. Off-White finish. NOTE B: Temperature preset at factory only. Special settings avaiIable upon request. Consult factory or Fenwal Representative for additional information. HORIZONTAL DETECT-A-FIRE MODELS TEMPERATURE RATING Suggested setting a minimum of 100°F above ambient. Model number 27020*, 27021 °F °F Setting Tolerance UL ULc FM RTI Coding 140 + 7/- 8 50 50 20 Quick Black 160 + 7/- 8 25 25 20 Quick Black NOTE D: Up to 375°F - #18 AWG Teflon insulated wire used on units. Above 375°F - #16AWG TGGT insulated wire used on units. 190 + 7/- 8 50 50 25 Fast White 210 + 7/- 8 50 50 25 Fast White 225 + 7/- 8 25 50 25 Fast White Specifications subject to change without notice. - UL or Canada labelling avaiIable upon request. - AIthough incandescent Iamps are considered resistive, their inrush current is 10 - 15 times their steady current. Do not exceed ratings. 275 ± 10 25 50 25 Fast Blue 325 ± 10 50 50 25 Fast Red NOTE C: In appIications where corrosion is suspect, care should be taken to protect the DETECT-A-FIRE unit to realize optimum performance and maximum life. Consult factory for suggestions. Spacings (in feet) Color * 27120 is a normally-closed device and does not meet the requirements of NFPA-72 for use as an initiating device. DETECT-A-FIRE® Detection and Release Devices by Terry Ferraris & C. Milano - Italy VERTICAL DETECT-A-FIRE UNITS Model Number 27120*, 27121 °F °F Setting Tolerance 140 +7/-8 160 +7/-8 190 +7/-8 210 +7/-8 225 +7/-8 275 ±10 325 ±10 360 ±10 450 ±15 500 ±15 600 ±20 725 ±20 (Hexagonal head) Spacings (in feet) UL ULc FM 50 50 25 25 25 25 50 50 25 25 50 30 25 50 30 25 50 30 50 50 30 25 50 30 25 50 30 50 50 30 N/A 50 30 N/A 50 30 RTI Fast Fast Fast V-Fast V-Fast V-Fast V-Fast V-Fast V-Fast V-Fast V-Fast V-Fast Color Coding Black Black White White White Blue Red Red Green Orange Orange Orange * 27120 is a normally-closed device and does not meet the requirements of NFPA-72 for use as an initiating device. Dimensions in inch Model Number 28020, 28021 (Coupling head) °F °F Setting Tolerance 140 +7/- 8 160 +7/- 8 190 +7/- 8 210 +7/- 8 225 +7/- 8 275 ±10 325 ±10 360 ±10 450 ±15 500 ±15 600 ±20 725 ±20 Mounting Head Material Brass Type 300 Stainless Steel Brass Type 300 Stainless Steel 12X28020-003 Type 300 Stainless Steel 12-X28021-005 Type 300 Stainless Steel FM 30 30 30 30 30 30 30 30 30 30 30 30 RTI V-Fast V-Fast V-Fast V-Fast V-Fast V-Fast V-Fast V-Fast V-Fast V-Fast V-Fast V-Fast Color Coding Black Black White White White Blue Red Red Green Orange Orange Orange Note: For clean agents and C02 suppression systems, ceiling spacing 20ft. apart unless otherwise specified. * 28020 is a normally closed device and does not meet the requirements of NFPA-72 for use as an initiating device Dimensions in inch Model Number 12-X27120-000 12X27120-022 12-X27121-000 12-X27121-020 Spacings (in feet) UL ULc 50 50 25 25 50 50 25 50 25 50 25 50 50 50 25 50 25 50 50 50 N/A 50 N/A 50 Shell Material Type 300 Stainless Steel Contact Operation on Temperature Rise Opens (450°F Max) Closes Opens (450°F Max) Closes Electrical Rating (Resistive Only) 5,0 Amps 125 VAC 0,5 Amps 125 VDC 5,0 Amps 125 VAC 0,5 Amps 125 VDC 2,0 Amps 24 VDC 1,0 Amps 48 VDC 5,0 Amps 125 VAC 0,5 Amps 125 VDC 5,0 Amps 125 VAC 0,5 Amps 125 VDC 2,0 Amps 24 VDC 1,0 Amps 48 VDC Approx. Weight per unit 142g 142g 142g 142g MODIFICATIONS 12-992012-XXX, Fluorocarbon coating, available on 27120-022, 27121-020,28020-003,28021-005 models only (500°F max.). DETECT-A-FIRE® Detection and Release Devices by Terry Ferraris & C. Milano - Italy DETECT-A-FIRE in Ex-flameproof housing Specification Fire Detector Temperature Switches. Model: - 27100 Rate Compensated - 28000 Rate compensated Constructive Characteristics Ex d housing: aluminum ASTM B-179-82 Electrical connection: 3/4” NPT-F Operation: OPENS/CLOSES on temperature rise Construction Weatherproof: With degree of protection IP66 according to IEC 60529 Flameproof: According to valid standards harmonized with ATEX Directive, with certificate ICEPI11ATEX03C001 or to IECEx scheme for type of protection Ex d IIC T6/T5/T4/T3*, with certificate IECEx CES12.0015 With approval UL certificate QBCRr7.E10518 & CSA certificate 4418-02 013046-0-000 according to NEC standard Cl, I Div, 1 & 2 Groups A,B, C, D Cl, II Div, 1 Groups E, F, G EX classification II 2 GD II 2 GD II 2 GD II 2 GD II 2 G Ambient Class temperature temperature -20°C to 65°C T6 -20°C to 95°C T5 -20°C to 120°C T4 -20°C to 130°C T3 -20°C to 185°C T3 -40°C upon request Cable temperature 70°C 100°C 125°C 135°C 190°C For the two available cable inlets, the manufacturer shall supply: - 1 temporary plastic plug - 1 plug according to selected certification Materials accepted for plug: Brass, Carbon steel and SS316 Certification Housing Material IECEx/ATEX ALUMINUM ATEX SS316 ATEX CAST IRON CSA/UL ALUMINUM Agency listings DETECT-A-FIRE units are UL , ULc and FM listed. ATEX and IECEx approved as fire detection thermostats (close on temperature rise) and as releasing devices (open on temperature rise). Agency File Number Location UL S492 Ordinary UL E19310 Hazardous ULc CS341- E Ordinary and Hazardous FM J.I. 0V3H0.AE Hazardous FM 17302 Ordinary UL S2410 Ordinary (600&725°F) UL E89599 Hazardous (600&725°F) ICEPI 11ATEX 03C001 Hazardous IECEx CES12.0015 Ancillary equipments - Flameproof housing with window and LED for power detection - Flameproof housing with window and LED to detect which DAF is switched on - External test push button - Test kit to check the DAF setting without disassembling it from its installation DETECT-A-FIRE® Detection and Release Devices by Terry Ferraris & C. Milano - Italy Hazardous UL & CSA EX - Flameproof housing DAF Series: 27120 - xxx, 28120 - xxx Contacts open on temperature rise DAF Series: 27121 - xxx, 28121- xxx Contacts close on temperature rise Rating contacts: 2A @ 24Vac/dc Resistive load 1A @ 48Vac/dc Resistive load 0,5A @ 115Vac/dc Resistive load 5A @ 125Vac/dc Resistive load DETECT-A-FIRE® Detection and Release Devices by Terry Ferraris & C. Milano - Italy Atex & IECEx EX - Flameproof housing DAF Series: 27120 - xxx, 28020 - xxx Contacts open on temperature rise Rating contacts: 2A @ 24Vac/dc Resistive load DAF Series: 27121 - xxx, 28021 - xxx Contacts close on temperature rise 1A @ 48Vac/dc Resistive load 0,5A @ 115Vac/dc Resistive load DETECT-A-FIRE® Detection and Release Devices by Terry Ferraris & C. Milano - Italy Configuration list DETECT-A-FIRE 27000 & 28000 Series 2 7 0 1 1 2 8 0 0 0 0 2 2 0 2 2 0 0 1 0 0 1 Hexagonal Head Opens on temperature rise ......................................................... Closes on temperature rise ......................................................... Coupling Head Opens on temperature rise ........................................................ Closes on temperature rise ......................................................... Head material 0 0 Brass .............................................................................. 2 0 S.S. (only for type 27121) ................................................. 2 2 S.S. (only for type 27120) ................................................. 0 5 S.S. (only for type 28021) ................................................. 0 3 S.S. (only for type 28020) ................................................ Setting A 140°F .............................................................................. B 160°F .............................................................................. C 190°F ............................................................................. D 210°F .............................................................................. E 225°F .............................................................................. F 275°F ............................................................................. G 325°F ............................................................................. H 360°F .............................................................................. I 450°F ............................................................................ J 500°F (only for types 27121, 28021) ............................... K 600°F (only for types 27121, 28021) ............................... L 725°F (only for types 27121, 28021) ............................... Housing 0 Only Detect-A-Fire ....................................................... A IECEx/Atex certified for 3/4 NPT-F.(Aluminum)............. I IP65 3/4” NPT-F (Aluminum)*........................................ P IP65 1” GK (Aluminum)*................................................ C UL/CSA certified (Aluminum)........................................ S S.S 316 Atex certified.................................................... Accessories 0 No Plug ..................................................................... 1 Plug 3/4” brass ......................................................... 2 Plug 3/4” carbon steel .............................................. 3 Plug 3/4” s.s. 316 IECEx .......................................... 4 Plug 1” brass ............................................................ 5 Plug 1” carbon steel ................................................. 6 Plug 1” s.s. 316 IECEx ............................................. Finishing 0 Only Detect-a-Fire ................................................ 1 Original colour cast iron ........................................ 2 One-colour painting (outside) cast iron ................ 3 Two-colour painting (inside/outside) cast iron ..... 4 Stainless steel original colour ............................... 5 Original color aluminum 6 One-colour painting (outside) aluminum ............... 7 Two-colour painting (inside/outside) aluminum ... Terminals 0 Only Detect-A-Fire ............................................ 1 2 terminals ........................................................ 2 5 terminals (only for types 27121, 28021) ........ 3 Back Plate Threaded 6MA Holes 5-Terminal .... 4 Back Plate Threaded 6MA Holes 2-Terminal .... *Cast iron and S.S.316 available on request 6/2012 Other products LINEAR HEAT DETECTION DETECT-A-FIRE® Detection and Release Devices by Terry Ferraris & C. Milano - Italy www.terryferraris.it - info@terryferraris.it - Phone +39 025391005