Overhead Conductors
Transcription
Overhead Conductors
Electric Utility Overhead Conductors TransPowr® Bare Overhead Conductors for Transmission and Distribution General Cable manufactures an extensive line of bare aluminum overhead products for both distribution and transmission applications. General Cable’s TransPowr® bare overhead products are manufactured and tested in accordance with the latest applicable CSA and ASTM specifications. General Cable’s bare overhead conductors are available as A1 aluminum stranded conductors (ASC), A2 aluminum alloy stranded conductors (AASC), aluminum conductor steel-reinforced (ACSR or A1S1A), and aluminum conductor steel-supported (ACSS). A1 or ASC consists of 1350-H19 aluminum, is lightweight and corrosion-resistant and is commonly used in overhead line installations where higher strength or temperature ratings are not required. A2 or AASC consists of high-strength 6101 T81 aluminum alloy and is commonly used for overhead line installations adjacent to ocean coastlines where there can be a problem of corrosion in the steel of an ACSR construction. ACSR or A1S1A combines the light weight and good conductivity of 1350-H19 aluminum with the high tensile strength and ruggedness of steel. ACSR provides higher tension, less sag and longer span lengths than A1 (ASC) and A2 (AASC) overhead conductors. Standard ACSR designs are manufactured with regular-strength Class A galvanized steel (S1A). With more than 35 years of experience, General Cable applies the same “tried and true” process pioneered by Reynolds to offer TransPowr® ACSS conductors. With its unique ability to operate at higher temperatures and withstand harsh environmental factors, TransPowr® ACSS allows utilities to modernize and optimize the nation’s electrical grid with minimal capital investment. TransPowr® ACSS offers better performance over ACSR when it operates at high temperatures without detriment to its mechanical properties and with significantly less sag, allowing for much higher ampacity ratings. Standard ACSS designs are manufactured with 1350-O aluminum and regular-strength Class A zinc-5% aluminum mischmetal alloy coated steel (/MA2). With several steel core options such as mischmetal, aluminum-clad steel and galvanized steel, TransPowr® ACSS is easily customized to meet specific applications and performance levels. TransPowr® ACSS is an affordable, long-lasting conductor with improved performance and reliability, made from aluminum and steel components that have been used in transmission lines for more than a hundred years. With thousands of miles installed throughout North America, ACSS is a proven, trustworthy overhead conductor technology and remains the most accepted solution for high-temperature performance. See the following page for a complete list and description of the numerous options that are available for TransPowr® overhead products. For ACSR (A1S1A) and ACSS concentric round or trapezoidal conductors, a myriad of aluminum and steel stranding combinations are available. In addition, a variety of steel strengths and types of coatings or claddings is available. Trapezoidal AAC, ACSR and ACSS conductor designs are listed in separate catalog sections. Compact aluminum and ACSR stranded conductor information are also listed. While General Cable manufactures a complete range of bare overhead products, only the most popular designs are described in the following section. Details of other conductor sizes and designs are available upon request. General Cable provides technical assistance and advice on any challenges associated with conductor design, installation or application. Engineering services are available for specification review, specification development and conductor application inquiries. For more information, contact your General Cable sales representative or e-mail infoca@generalcable.com. Current Standards and Specifications: C49.2 Compact Aluminum Conductors Steel Reinforced (ACSR) C49.3 Aluminum Alloy 1350 Round Wire, For Electrical Purposes C49.5 Compact Round Concentric Lay Aluminum Stranded Conductors C49.8 Bare Overhead Aluminum Conductors for Distribution Applications • Replaced CEA WCWG 03 G12 Zinc Coated Steel Wire Strand CAN/CSA C60888: Zinc-Coated Steel Wires for Stranded Conductors • Replaced C49.6 CAN/CSA C60889: Hard-Drawn Aluminum Wire for Overhead Conductors • Replaced C49.7 48 CAN/CSA C60104: Aluminum-Magnesium-Silicon Alloy Wire for Overhead Line Conductors CAN/CSA C61089: Round Wire Concentric Lay Overhead Electric Stranded Conductors • Replaced C49.1 • Replaced C49.4 CAN/CSA C61232: Aluminum-Clad Steel Wires for Electrical Purposes C68.9 Covered Overhead Distribution Line Wire • Replaced CEA WCWG 06 3/2013 Electric Utility 4 TransPowr® Bare Overhead Options: •Non-Specular (NS) – Overhead aluminum electrical conductors, when installed, typically have a shiny surface appearance. This “reflective” or “specular” surface can make a transmission line more noticeable in appearance against the background landscape. A factory treatment process of the outer surface of the aluminum wires can render the surface finish into a dull, non-specular matte gray finish. This non reflective or “de-glared” surface finish allows the conductor to become less visible when observed from a distance and enables the transmission line to blend in with the skyline or landscape background. The “NS” surface finish option is available for all types of bare overhead conductors that have aluminum outer strand wires. •High-Conductivity Aluminum (HC) – The normal 1350 hard-drawn aluminum material used for an ACSR-type conductor has a minimum lot average conductivity value of 61.2% IACS (International Association Copper Standard). By carefully selecting the feed stock of the raw materials and manufacturing process used to refine the aluminum and convert it into rolled rod, a purer grade of 1350 aluminum can be manufactured. When this is done, the aluminum minimum lot average conductivity value is increased to 62.2%. The use of the higher conductivity metal means the overall electrical resistance of the conductor is lowered. Lowering the electrical resistance means there are lower line losses incurred in the transmission line. •“Mischmetal” Alloy-Coated Steel – Inside an ACSR and ACSS conductor, there is the stranded steel core. To provide corrosion protection for the steel, traditionally zinc has been used to coat (galvanize) the steel. In recent years, a zinc alloy material has also been used. This material, a 95% zinc/5% aluminum alloy, is available as an optional steel wire coating material. The alloy, known as zinc-5% aluminum “mischmetal” alloy, demonstrates improved corrosion resistance and high temperature exposure compatibility as compared to regular zinc. For ACSS conductors, “mischmetal” alloy-coated steel is recommended for applications where the conductor will see exposure to temperatures in excess of 200°C. IndexPage Bare Overhead Conductor A1 (ASC) 51-58 Compact (Smooth Body) ASC 59-62 AAC/TW63-68 A2 (AASC) 69-72 ACSR73-90 Compact (Smooth Body) ACSR 91-94 ACSR/TW95-102 ACSS103-112 ACSS/TW113-120 ACSR/SD121-126 Weatherproof Overhead Line Wire Weatherproof Overhead Line Wire127-130 Aluminum Tie Wire Aluminum Tie Wire 131 •Ultra-High-Strength Steel – In response to industry needs, there are new high strength carbon steel materials now available for ACSR and ACSS conductors. The higher strength steel overcomes some of the previous transmission line design limitations encountered with available conductor selection options. The availability of these new steel materials boosts the conductor rated strength and can enable enhanced sag and tension calculation results. General Cable identifies the new ultra-high-strength steel as GA5 (for zinc-coated steel) and MA5 (for the zinc-5% aluminum “mischmetal” alloy-coated steel) strength grade designations. General Cable participated in the creation of two new ASTM standards to introduce these new steel types (ASTM B957 for GA5 steel and ASTM B958 for MA5 steel). 3/2013 49 Electric Utility Overhead Conductors TransPowr ® Bare Overhead Options (cont’d.): •Aluminum-Clad Steel (20SA [AW]) – In Canada, the 20SA (ASTM “AW”) identifier is used for aluminum-clad steel. Elsewhere in the world, other designations are used. Aluminum-clad steel is chosen for coastal locations or applications where there are severe corrosion concerns for the steel core and a zinc or “mischmetal” coated steel will not last. Aluminum-clad steel also offers the advantage of having a higher conductivity than conventional galvanized steel wires. The higher conductivity will reduce the line loss parameters of the transmission line, saving energy and reducing the day-to-day operating cost. In an ACSS conductor, aluminum-clad steel can allow the conductor to be operated up to 250°C. Aluminum-clad steel core wires are manufactured in accordance with CAN/CSA C61232. •Compact (Smooth Body) Conductors – General Cable can supply compact AAC (to CSA 49.5) and compact ACSR (to CSA 49.2) “smooth body” type conductor products for distribution conductor sizes. Compact conductors reduce the overall diameter of the conductor, thus lowering the resultant wind and ice loads on the conductor. In heavy ice load locations, the compact conductor option may be an interesting design option to explore. Contact your General Cable sales representative for additional information. •Trapezoidal (TW) Conductors – For overhead transmission conductor applications, General Cable supplies TW compact-style conductors. The aluminum wires in a “round wire” stranded conductor leave approximately 25% of an air gap between .the aluminum strands. Compacting the aluminum strands into the trapezoidal (TW) shape allows you to significantly reduce this .empty air space and fill it with aluminum. By “compacting” the metal space, it allows you to build a conductor that either a) has t.he same cross-sectional area of aluminum and a reduced overall conductor diameter or b) has the same overall conductor diameter as before, but now squeezes in more aluminum cross-sectional area. Reducing the overall diameter of the conductor provides the .advantage of lowering the resultant ice and wind loading on the conductor. Maintaining the same diameter by increasing the aluminum metal content means you lower the power loss in the conductor for day-to-day operations, as well as having a higher overall conductor ampacity rating. With TW conductors, the growing trend is to utilize the same diameter/increased aluminum cross-sectional area option. •Aluminum Alloy Steel Reinforced Conductors (A2/SxA) – General Cable is capable of building ACSR conductors where the A1 (1350 H19) aluminum wires are replaced with the higher strength A2 (6101 T81) or A4 (6101 T83) aluminum alloy material. These type of super high strength conductors are used in river crossings or for long span applications where the traditional ACSR conductor will not work. Contact General Cable to find out more details about these customized conductor constructions and see how they might be of benefit to you and your line design application. TransPowr ® bare overhead conductors can be designed to meet special applications and requirements. For designs not found in these catalog pages, contact your General Cable sales representative. 50 3/2013 Electric Utility Overhead Conductors TransPowr A1 (ASC) Bare Overhead Conductor to CAN/CSA C61089 ® All-Aluminum 1350 Conductor Concentric-Lay-Stranded Product Construction: Complete Conductor: Bare all-aluminum 1350 (A1 or ASC) are concentric-lay-stranded conductors consisting of one or more layers of wire wrapped helically around a straight round central wire. Each successive layer has six wires more than the layer immediately beneath. Greater flexibility is provided by increasing the number of strands for a specific cross-sectional area. A1 or ASC conductors are manufactured in accordance with the requirements of the latest applicable issue of CAN/CSA C61089. A1 or ASC (Aluminum Stranded Conductor) conductors are CSA reference terms. The Canadian constructions are similar in design (strand component size and configuration) to the ASTM B231 specifications. Differences lie in the methods used to calculate the rated strength and dc resistance values. The commonly used strandings are 7, 19, 37, 61 and 91. The sizes and strandings listed on the following pages are common examples used in overhead lines. Metric (mm2) sizes are also available. Complete Conductor (cont’d.): Class AA strandings are used for bare overhead lines. The direction of lay of the outer layer is righthand and is normally reversed in successive layers. The temper is full hard drawn (H19). Class A strandings are used primarily for overhead conductors which are to be covered with weatherresistant materials. Greater flexibility is provided than Class AA. The outer layer is right-hand, and the temper is generally H19. Successive layers are normally reverse lay. Features and Benefits: Optimum economy is provided since the lighter weight means lower unit length costs, easier handling in installation and less complex fittings. All-aluminum conductors have an inherent high corrosion resistance due to their homogeneous construction. Applications: Stranded bare A1 or ASC 1350 all-aluminum conductors are used for overhead line installations where design parameters do not require the higher strength or temperature ratings provided by ACSR, ACSS or other type of bare conductor. Options: •Compact aluminum strands (CSA C49.5) •Trapezoidal-shaped aluminum strands (/TW) •High-Conductivity aluminum (/HC) (62.2% IACS) •Non-Specular surface finish (/NS) For more information, contact your General Cable sales representative or e-mail infoca@generalcable.com. 51 Overhead Conductors Electric Utility TransPowr A1 (ASC) Bare Overhead Conductor to CAN/CSA C61089 ® All-Aluminum 1350 Conductor Concentric-Lay-Stranded A1 (ASC), ALUMINUM CONDUCTOR, CONCENTRIC-LAY-STRANDED (MECHANICAL PROPERTIES) CODE WORD CONDUCTOR SIZE AWG OR kcmil mm2 STRANDING NO. X DIA. INCHES CLASS CROSSSECTIONAL AREA SQ. INCHES INCHES mm LB/kFT kg/km LB kN O.D. APPROX. WEIGHT RATED STRENGTH Peachbell 6 13.3 7x0.0612 A 0.0206 0.184 4.67 24.40 36.31 580 2.58 Rose 4 21.1 7x0.0772 A 0.0328 0.232 5.88 38.90 57.89 930 4.14 Iris 2 33.6 7x0.0974 A, AA 0.0522 0.292 7.42 61.80 91.97 1400 6.23 Pansy 1 42.4 7x0.1093 A, AA 0.0657 0.328 8.33 77.90 115.9 1670 7.43 Poppy 1/0 53.5 7x0.1228 A, AA 0.0829 0.368 9.36 98.30 146.3 2040 9.07 Aster 2/0 67.4 7x0.1379 A, AA 0.1045 0.414 10.5 123.9 184.4 2580 11.5 Phlox 3/0 85.0 7x0.1548 A, AA 0.1317 0.464 11.8 156.2 232.5 3150 14.0 Oxlip 4/0 107.2 7x0.1739 A, AA 0.1663 0.522 13.2 197.0 293.2 3980 17.7 Daisy 266.8 135.2 7x0.1953 AA 0.2095 0.586 14.9 248.0 369.1 5010 22.3 Laurel 266.8 135.2 19x0.1185 A 0.2095 0.592 15.0 250.0 372.1 5170 23.0 Peony 300.0 152.0 19x0.1257 A 0.2358 0.628 16.0 281.0 418.2 5810 25.8 Tulip 336.4 170.5 19x0.1331 A 0.2644 0.665 16.9 315.0 468.8 6520 29.0 Daffodil 350.0 177.3 19x0.1357 A 0.2748 0.679 17.2 327.0 486.6 6780 30.2 Canna 397.5 201.4 19x0.1447 A, AA 0.3120 0.723 18.4 372.0 553.6 7690 34.2 Cosmos 477.0 241.7 19x0.1584 AA 0.3747 0.792 20.1 446.0 663.7 8970 39.9 STANDARD PACKAGES (1) WT LENGTH REEL DESIG. kg M RW 48.24 NR 36.22 COIL RW 48.24 NR 36.22 COIL RW 48.24 NR 36.22 COIL RW 48.24 NR 36.22 COIL RW 48.24 NR 36.22 COIL RW 48.24 NR 36.22 RW 48.24 NR 36.22 RW 48.24 NR 36.22 RW 48.24 NR 36.22 RM 68.38 RW 66.36 RW 50.32 RW 48.24 RM 68.38 RW 60.32 RM 68.38 RW 66.36 RW 50.32 RW 48.24 RM 68.38 RW 66.36 RW 50.32 RW 48.24 RM 68.38 RW 66.36 RW 50.32 RW 48.24 RM 68.38 RW 66.36 RW 50.32 RW 48.24 (1) Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 52 635 318 91 633 318 91 635 318 91 635 318 91 633 318 91 635 318 635 318 635 318 635 318 1721 1721 860 574 1721 1032 1721 1721 862 574 1719 1719 860 574 1719 1719 860 574 1721 1721 860 574 17345 8673 2478 10884 5442 1554 6849 3424 978 5434 2717 777 4307 2153 616 3417 1708 2710 1355 2149 1074 1704 852 4624 4624 2312 1541 4115 2469 3667 3667 1833 1222 3523 3523 1762 1175 3103 3103 1551 1035 2588 2588 1294 863 Electric Utility Overhead Conductors TransPowr A1 (ASC) Bare Overhead Conductor to CAN/CSA C61089 ® All-Aluminum 1350 Conductor Concentric-Lay-Stranded A1 (ASC), ALUMINUM CONDUCTOR, CONCENTRIC-LAY-STRANDED (ELECTRICAL PROPERTIES) CODE WORD CONDUCTOR SIZE AWG OR kcmil mm2 CROSSO.D. STRANDING SECTIONAL NO. X DIA. AREA INCHES CLASS SQ. INCHES INCHES mm RESISTANCE (2) GEOMETRIC INDUCTIVE OHMS/1000 FT MEAN REACTANCE DC AC AC AMPACITY RADIUS OHM/1000 FT @ 20˚C @ 25˚C @ 75˚C 75˚C (3) FT (4) (4) CAPACITIVE REACTANCE MEGAOHM 1000 FT (4) Peachbell 6 13.3 7x0.0612 A 0.0206 0.184 4.67 0.656 0.670 0.802 95 0.0056 0.1194 0.7632 Rose 4 21.1 7x0.0772 A 0.0328 0.232 5.88 0.413 0.421 0.504 125 0.0070 0.1140 0.7269 Iris 2 33.6 7x0.0974 A, AA 0.0522 0.292 7.42 0.260 0.265 0.317 170 0.0088 0.1087 0.6906 Pansy 1 42.4 7x0.1093 A, AA 0.0657 0.328 8.33 0.206 0.210 0.251 195 0.0099 0.1060 0.6724 Poppy 1/0 53.5 7x0.1228 A, AA 0.0829 0.368 9.36 0.163 0.166 0.199 225 0.0111 0.1034 0.6542 Aster 2/0 67.4 7x0.1379 A, AA 0.1045 0.414 10.5 0.129 0.132 0.158 265 0.0125 0.1007 0.6361 Phlox 3/0 85.0 7x0.1548 A, AA 0.1317 0.464 11.8 0.103 0.105 0.125 305 0.0140 0.0980 0.6179 Oxlip 4/0 107.2 7x0.1739 A, AA 0.1663 0.522 13.2 0.0814 0.0832 0.0996 350 0.0158 0.0954 0.5998 Daisy 266.8 135.2 7x0.1953 AA 0.2095 0.586 14.9 0.0646 0.0660 0.0790 405 0.0177 0.0927 0.5816 Laurel 266.8 135.2 19x0.1185 A 0.2095 0.592 15.0 0.0649 0.0663 0.0794 405 0.0187 0.0914 0.5798 Peony 300.0 152.0 19x0.1257 A 0.2358 0.628 16.0 0.0577 0.0590 0.0706 435 0.0198 0.0901 0.5706 Tulip 336.4 170.5 19x0.1331 A 0.2644 0.665 16.9 0.0514 0.0527 0.0630 470 0.0210 0.0888 0.5616 Daffodil 350.0 177.3 19x0.1357 A 0.2748 0.679 17.2 0.0495 0.0507 0.0606 480 0.0214 0.0883 0.5585 Canna 397.5 201.4 19x0.1447 A, AA 0.3120 0.723 18.4 0.0435 0.0447 0.0534 520 0.0228 0.0869 0.5486 Cosmos 477.0 241.7 19x0.1584 AA 0.3747 0.792 20.1 0.0363 0.0373 0.0446 585 0.0250 0.0848 0.5343 (2)Based on a conductivity of 61.0% IACS at 20˚C. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by 3.281. (3)Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 32˚C ambient temperature, 1.98 ft/sec (0.6 m/s) crosswind (90˚ to conductor), 0.5 coefficient of emissivity, 0.5 coefficient of absorbtivity, 42˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 95.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (4)Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm). To convert the Geometric Mean Radius (GMR) to cm, divide the value by 0.03821. To convert inductive reactance to ohm/km, multiply the value by 3.281. To convert capacitive reactance to ohm/km, divide the value by 3.281. 53 Overhead Conductors Electric Utility TransPowr A1 (ASC) Bare Overhead Conductor to CAN/CSA C61089 ® All-Aluminum 1350 Conductor Concentric-Lay-Stranded A1 (ASC), ALUMINUM CONDUCTOR, CONCENTRIC-LAY-STRANDED (MECHANICAL PROPERTIES) CODE WORD CONDUCTOR SIZE AWG OR kcmil mm2 STRANDING NO. X DIA. INCHES CLASS CROSSSECTIONAL AREA SQ. INCHES INCHES mm LB/kFT kg/km LB kN O.D. APPROX. WEIGHT RATED STRENGTH Syringa 477.0 241.7 37x0.1135 A 0.3744 0.795 20.2 447.0 665.2 9500 42.3 Zinnia Hyacinth 500.0 500.0 253.4 253.4 19x0.1622 37x0.1162 AA A 0.3926 0.3926 0.811 0.814 20.6 20.7 468.0 469.0 696.5 698.0 9400 9970 41.8 44.3 Dahlia 556.5 282.0 19x0.1711 AA 0.4369 0.856 21.7 521.0 775.4 10500 46.7 Mistletoe 556.5 282.0 37x0.1226 A 0.4368 0.858 21.8 522.0 776.8 10800 48.0 Meadowsweet 600.0 304.0 37x0.1273 A, AA 0.4712 0.891 22.6 563.0 837.9 11600 51.6 Orchid 636.0 322.3 37x0.1311 A, AA 0.4995 0.918 23.3 596.0 887.0 12300 54.7 Violet 715.5 362.5 37x0.1391 AA 0.5622 0.973 24.7 671.0 998.6 13900 61.8 Nasturtium 715.5 362.5 61x0.1083 A 0.5619 0.975 24.8 672.0 1000 14300 63.6 Petunia 750.0 380.0 37x0.1424 AA 0.5892 0.997 25.3 703.0 1046 14500 64.5 Arbutus 795.0 402.8 37x0.1466 AA 0.6245 1.026 26.1 745.0 1109 15400 68.5 Lilac 795.0 402.8 61x0.1142 A 0.6247 1.027 26.1 747.0 1112 15900 70.7 Fuchsia 800.0 405.4 37x0.1470 AA 0.6283 1.029 26.1 750.0 1116 15500 68.9 Heliotrope 800.0 405.4 61x0.1145 A 0.6282 1.031 26.2 751.0 1118 15900 70.7 Anemone 874.5 443.1 37x0.1537 AA 0.6866 1.076 27.3 820.0 1220 16400 72.9 Crocus 874.5 443.1 61x0.1197 A 0.6865 1.078 27.4 821.0 1222 16900 75.2 STANDARD PACKAGES (1) WT LENGTH REEL DESIG. kg M RMT 84.45 RM 68.38 RW 66.36 RW 50.32 RM 68.38 RMT 84.45 RM 68.38 RM 68.38 RW 66.36 RW 50.32 RW 48.24 RMT 84.45 RM 68.38 RW 66.36 RW 50.32 RMT 84.45 RM 68.38 RMT 84.45 RM 68.38 RW 66.36 RW 50.32 RMT 84.45 RM 68.38 RW 66.36 RW 50.32 RMT 90.45 RM 68.38 RMT 84.45 RM 68.38 RW 50.32 RMT 84.45 RM 68.38 RW 66.36 RW 50.32 RMT 90.45 RM 68.38 RMT 84.45 RM 68.38 RMT 90.45 RM 68.38 RMT 84.45 RM 68.38 RW 66.36 RW 50.32 RMT 90.45 RM 68.38 (1) Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 54 3350 1676 1676 839 1721 3348 1674 1719 1719 860 574 3350 1676 1676 839 3350 1674 3352 1676 1676 839 3354 1676 1676 839 4420 2209 3352 1676 839 3354 1676 1676 839 4425 2211 3350 1676 4420 2175 3348 1674 1674 839 4418 2209 5038 2519 2519 1260 2469 4803 2402 2216 2216 1108 739 4319 2159 2159 1080 4005 2002 3779 1890 1890 945 3359 1679 1679 840 4429 2214 3203 1602 802 3023 1512 1512 756 3987 1993 3004 1503 3962 1949 2746 1373 1373 687 3624 1812 Electric Utility Overhead Conductors TransPowr A1 (ASC) Bare Overhead Conductor to CAN/CSA C61089 ® All-Aluminum 1350 Conductor Concentric-Lay-Stranded A1 (ASC), ALUMINUM CONDUCTOR, CONCENTRIC-LAY-STRANDED (ELECTRICAL PROPERTIES) CODE WORD CONDUCTOR SIZE AWG OR kcmil mm2 CROSSO.D. STRANDING SECTIONAL NO. X DIA. AREA INCHES CLASS SQ. INCHES INCHES mm RESISTANCE (2) GEOMETRIC INDUCTIVE OHMS/1000 FT MEAN REACTANCE DC AC AC AMPACITY RADIUS OHM/1000 FT @ 20˚C @ 25˚C @ 75˚C 75˚C (3) FT (4) (4) CAPACITIVE REACTANCE MEGAOHM 1000 FT (4) Syringa 477.0 241.7 37x0.1135 A 0.3744 0.795 20.2 0.0364 0.0374 0.0447 585 0.0254 0.0844 0.5338 Zinnia Hyacinth 500.0 500.0 253.4 253.4 19x0.1622 37x0.1162 AA A 0.3926 0.3926 0.811 0.814 20.6 20.7 0.0346 0.0347 0.0356 0.0357 0.0425 0.0426 600 600 0.0256 0.0260 0.0842 0.0838 0.5306 0.5301 Dahlia 556.5 282.0 19x0.1711 AA 0.4369 0.856 21.7 0.0311 0.0321 0.0383 645 0.0270 0.0830 0.5222 Mistletoe 556.5 282.0 37x0.1226 A 0.4368 0.858 21.8 0.0312 0.0321 0.0384 645 0.0275 0.0826 0.5217 Meadowsweet 600.0 304.0 37x0.1273 A, AA 0.4712 0.891 22.6 0.0289 0.0299 0.0356 675 0.0285 0.0817 0.5158 Orchid 636.0 322.3 37x0.1311 A, AA 0.4995 0.918 23.3 0.0273 0.0282 0.0337 700 0.0294 0.0811 0.5113 Violet 715.5 362.5 37x0.1391 AA 0.5622 0.973 24.7 0.0242 0.0252 0.0300 750 0.0311 0.0797 0.5020 Nasturtium 715.5 362.5 61x0.1083 A 0.5619 0.975 24.8 0.0243 0.0252 0.0300 750 0.0314 0.0796 0.5018 Petunia 750.0 380.0 37x0.1424 AA 0.5892 0.997 25.3 0.0231 0.0241 0.0286 775 0.0319 0.0792 0.4983 Arbutus 795.0 402.8 37x0.1466 AA 0.6245 1.026 26.1 0.0218 0.0227 0.0271 800 0.0328 0.0785 0.4938 Lilac 795.0 402.8 61x0.1142 A 0.6247 1.027 26.1 0.0219 0.0228 0.0271 800 0.0331 0.0784 0.4936 Fuchsia 800.0 405.4 37x0.1470 AA 0.6283 1.029 26.1 0.0217 0.0226 0.0269 805 0.0329 0.0784 0.4933 Heliotrope 800.0 405.4 61x0.1145 A 0.6282 1.031 26.2 0.0217 0.0226 0.0269 805 0.0332 0.0783 0.4931 Anemone 874.5 443.1 37x0.1537 AA 0.6866 1.076 27.3 0.0198 0.0208 0.0247 850 0.0344 0.0774 0.4863 Crocus 874.5 443.1 61x0.1197 A 0.6865 1.078 27.4 0.0199 0.0208 0.0247 850 0.0347 0.0773 0.4861 (2)Based on a conductivity of 61.0% IACS at 20˚C. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by 3.281. (3)Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 32˚C ambient temperature, 1.98 ft/sec (0.6 m/s) crosswind (90˚ to conductor), 0.5 coefficient of emissivity, 0.5 coefficient of absorbtivity, 42˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 95.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (4)Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm). To convert the Geometric Mean Radius (GMR) to cm, divide the value by 0.03821. To convert inductive reactance to ohm/km, multiply the value by 3.281. To convert capacitive reactance to ohm/km, divide the value by 3.281. 55 Overhead Conductors Electric Utility TransPowr A1 (ASC) Bare Overhead Conductor to CAN/CSA C61089 ® All-Aluminum 1350 Conductor Concentric-Lay-Stranded A1 (ASC), ALUMINUM CONDUCTOR, CONCENTRIC-LAY-STRANDED (MECHANICAL PROPERTIES) CODE WORD CONDUCTOR SIZE AWG OR kcmil mm2 STRANDING NO. X DIA. INCHES CLASS CROSSSECTIONAL AREA SQ. INCHES INCHES mm LB/kFT kg/km LB kN O.D. APPROX. WEIGHT RATED STRENGTH Magnolia 954.0 483.4 37x0.1606 AA 0.7495 1.124 28.5 895.0 1332 17900 79.6 Goldenrod 954.0 483.4 61x0.1251 A 0.7497 1.126 28.6 896.0 1333 18500 82.3 Camellia 1000.0 506.7 61x0.1280 A 0.7850 1.152 29.3 939.0 1397 19400 86.3 Bluebell 1033.5 523.7 37x0.1671 AA 0.8115 1.170 29.7 969.0 1442 19400 86.3 Larkspur 1033.5 523.7 61x0.1302 A 0.8121 1.171 29.8 970.0 1444 20000 89.0 Marigold 1113.0 564.0 61x0.1351 A, AA 0.8744 1.216 30.9 1045 1555 21600 96.1 Hawthorn 1192.5 604.2 61x0.1398 A, AA 0.9364 1.258 32.0 1120 1667 23100 103 Narcissus 1272.0 644.5 61x0.1444 A, AA 0.9990 1.300 33.0 1194 1777 24600 109 Columbine 1351.5 684.8 61x0.1488 A, AA 1.0616 1.340 34.0 1269 1889 25400 113 Carnation 1431.0 725.1 61x0.1532 A, AA 1.1243 1.378 35.0 1344 2000 26900 120 Gladiolus 1510.5 765.4 61x0.1574 A, AA 1.1868 1.416 36.0 1418 2110 28400 126 Coreopsis 1590.0 805.7 61x0.1614 AA 1.2489 1.453 36.9 1493 2222 29900 133 Jessamine Cowslip Sagebrush Pigweed Lupine Bitterroot Trillium Bluebonnet 1750.0 2000.0 2250.0 2300.0 2500.0 2750.0 3000.0 3500.0 886.7 1013.4 1140.1 1165.4 1266.8 1393.4 1520.1 1773.5 61x0.1694 91x0.1482 91x0.1572 61x0.1942 91x0.1657 91x0.1738 127x0.1537 127x0.1660 AA A A A A A A A 1.3747 1.5710 1.7666 1.8067 1.9637 2.1593 2.3563 2.7488 1.524 1.631 1.730 1.748 1.823 1.912 1.998 2.158 38.7 41.4 43.9 44.4 46.3 48.6 50.7 54.8 1643 1880 2115 2160 2350 2585 2820 3290 2445 2798 3148 3215 3497 3847 4197 4896 32900 37600 42300 43200 47000 51700 56400 65800 146 167 188 192 209 230 251 293 STANDARD PACKAGES (1) WT LENGTH REEL DESIG. kg M RMT 84.45 RM 68.38 RW 66.36 RW 50.32 RMT 90.45 RM 68.38 RMT 90.45 RM 68.38 RMT 84.45 RM 68.38 RW 66.36 RW 50.32 RMT 90.45 RM 68.38 RMT 90.45 RM 68.38 RMT 90.45 RM 68.38 RMT 90.45 RM 68.38 RMT 90.45 RM 68.38 RMT 90.45 RM 68.38 RMT 90.45 RM 68.38 RMT 90.45 RM 68.38 RMT 90.45 RMT 90.45 RMT 90.45 RMT 90.45 RMT 90.45 RMT 90.45 RMT 90.45 RMT 90.45 (1) Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 56 3352 1676 1676 837 4425 2211 4420 2209 3352 1676 1676 839 4423 2211 4423 2211 4733 2209 4418 2209 4416 2209 4425 2214 4418 2209 4418 2209 4423 4121 4121 4119 4119 4119 4316 4307 2518 1259 1259 629 3322 1661 3170 1585 2326 1163 1163 582 3066 1533 2847 1423 2847 1329 2490 1245 2344 1172 2216 1108 2097 1048 1993 997 1810 1478 1301 1271 1170 1064 1021 866 Electric Utility Overhead Conductors TransPowr A1 (ASC) Bare Overhead Conductor to CAN/CSA C61089 ® All-Aluminum 1350 Conductor Concentric-Lay-Stranded A1 (ASC), ALUMINUM CONDUCTOR, CONCENTRIC-LAY-STRANDED (ELECTRICAL PROPERTIES) CODE WORD CONDUCTOR SIZE AWG OR kcmil mm2 CROSSO.D. STRANDING SECTIONAL NO. X DIA. AREA INCHES CLASS SQ. INCHES INCHES mm RESISTANCE (2) GEOMETRIC INDUCTIVE OHMS/1000 FT MEAN REACTANCE DC AC AC AMPACITY RADIUS OHM/1000 FT @ 20˚C @ 25˚C @ 75˚C 75˚C (3) FT (4) (4) CAPACITIVE REACTANCE MEGAOHM 1000 FT (4) Magnolia 954.0 483.4 37x0.1606 AA 0.7495 1.124 28.5 0.0182 0.0191 0.0227 895 0.0360 0.0764 0.4795 Goldenrod 954.0 483.4 61x0.1251 A 0.7497 1.126 28.6 0.0182 0.0192 0.0227 895 0.0362 0.0763 0.4793 Camellia 1000.0 506.7 61x0.1280 A 0.7850 1.152 29.3 0.0174 0.0183 0.0217 920 0.0371 0.0757 0.4756 Bluebell 1033.5 523.7 37x0.1671 AA 0.8115 1.170 29.7 0.0168 0.0177 0.0210 940 0.0374 0.0755 0.4732 Larkspur 1033.5 523.7 61x0.1302 A 0.8121 1.171 29.8 0.0168 0.0178 0.0211 940 0.0377 0.0753 0.4730 Marigold 1113.0 564.0 61x0.1351 A, AA 0.8744 1.216 30.9 0.0156 0.0166 0.0196 980 0.0391 0.0745 0.4672 Hawthorn 1192.5 604.2 61x0.1398 A, AA 0.9364 1.258 32.0 0.0146 0.0156 0.0184 1025 0.0405 0.0737 0.4618 Narcissus 1272.0 644.5 61x0.1444 A, AA 0.9990 1.300 33.0 0.0137 0.0147 0.0173 1065 0.0418 0.0730 0.4568 Columbine 1351.5 684.8 61x0.1488 A, AA 1.0616 1.340 34.0 0.0129 0.0139 0.0164 1105 0.0431 0.0723 0.4520 Carnation 1431.0 725.1 61x0.1532 A, AA 1.1243 1.378 35.0 0.0121 0.0132 0.0155 1140 0.0443 0.0716 0.4475 Gladiolus 1510.5 765.4 61x0.1574 A, AA 1.1868 1.416 36.0 0.0115 0.0126 0.0148 1175 0.0456 0.0710 0.4433 Coreopsis 1590.0 805.7 61x0.1614 AA 1.2489 1.453 36.9 0.0109 0.0121 0.0141 1210 0.0468 0.0704 0.4393 Jessamine Cowslip Sagebrush Pigweed Lupine Bitterroot Trillium Bluebonnet 1750.0 2000.0 2250.0 2300.0 2500.0 2750.0 3000.0 3500.0 886.7 1013.4 1140.1 1165.4 1266.8 1393.4 1520.1 1773.5 61x0.1694 91x0.1482 91x0.1572 61x0.1942 91x0.1657 91x0.1738 127x0.1537 127x0.1660 AA A A A A A A A 1.3747 1.5710 1.7666 1.8067 1.9637 2.1593 2.3563 2.7488 1.524 1.631 1.730 1.748 1.823 1.912 1.998 2.158 38.7 41.4 43.9 44.4 46.3 48.6 50.7 54.8 0.00993 0.00870 0.00776 0.00755 0.00696 0.00632 0.00580 0.00497 0.0111 0.00999 0.00914 0.00895 0.00842 0.00787 0.00741 0.00670 0.0130 0.0116 0.0105 0.0103 0.00966 0.00897 0.00841 0.00754 1280 1380 1470 1490 1555 1635 1705 1840 0.0490 0.0526 0.0558 0.0562 0.0588 0.0617 0.0646 0.0697 0.0693 0.0677 0.0663 0.0662 0.0651 0.0640 0.0630 0.0612 0.4318 0.4212 0.4120 0.4104 0.4037 0.3963 0.3894 0.3773 (2)Based on a conductivity of 61.0% IACS at 20˚C. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by 3.281. (3)Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 32˚C ambient temperature, 1.98 ft/sec (0.6 m/s) crosswind (90˚ to conductor), 0.5 coefficient of emissivity, 0.5 coefficient of absorbtivity, 42˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 95.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (4)Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm). To convert the Geometric Mean Radius (GMR) to cm, divide the value by 0.03821. To convert inductive reactance to ohm/km, multiply the value by 3.281. To convert capacitive reactance to ohm/km, divide the value by 3.281. 57 Overhead Conductors Notes 58 Electric Utility Electric Utility Overhead Conductors TransPowr Compact (Smooth Body) ASC Bare Overhead Conductor to CSA C49.5 All-Aluminum Compact Stranded Conductor ® Product Construction: Complete Conductor: Smooth Body bare all-aluminum 1350 (A1 or ASC) are compact concentric-lay-stranded conductors consisting of one or more layers of wire wrapped helically around a straight round central wire. Smooth Body conductors are manufactured in accordance with the requirements of the latest applicable issue of CSA C49.5. A1 or ASC (Aluminum Stranded Conductor) are CSA reference terms. The Canadian constructions are similar in design (strand component size and configuration) to the ASTM B400 specification. Differences lie in the methods used to calculate the rated strength and dc resistance values. The commonly used strandings are 7, 18, and 19. The sizes and strandings listed on the following pages are common examples used in overhead lines. Metric (mm2) sizes are also available. Complete Conductor (cont’d.): Class AA strandings are used for bare overhead lines. The direction of lay of the outer layer is righthand and is reversed in successive layers. The temper is full hard drawn (H19). Class A strandings are used primarily for overhead conductors which are to be covered with weatherresistant materials. Greater flexibility is provided than Class AA. The direction of lay of the outer layers is right-hand and is reversed in successive layers. The temper is full hard drawn (H19). Features and Benefits: Applications: Stranded bare A1 or ASC 1350 all-aluminum conductors are used for overhead line installations where design parameters do not require the higher strength or temperature ratings provided by ACSR, ACSS or other type of bare conductor. Options: •High-Conductivity aluminum (/HC) (62.2% IACS) • Non-Specular surface finish (/NS) For more information, contact your General Cable sales representative or e-mail infoca@generalcable.com. The conductors are smaller in diameter and offer lower ice load/wind resistance profile factors. The conductors are lighter in weight than ACSR, which translates into lower unit length costs, easier handling in installation and less complex fittings. All-aluminum conductors have an inherent high corrosion resistance due to their homogeneous construction. 59 Overhead Conductors Electric Utility TransPowr Compact (Smooth Body) ASC Bare Overhead Conductor to CSA C49.5 All-Aluminum Compact Stranded Conductor ® ASC, ALUMINUM CONDUCTOR, COMPACT-LAY-STRANDED (MECHANICAL PROPERTIES) CODE WORD CONDUCTOR SIZE AWG OR kcmil mm2 STRANDING NO. X DIA. INCHES CLASS CROSSSECTIONAL AREA SQ. INCHES INCHES mm LB/kFT kg/km LB kN O.D. APPROX. WEIGHT RATED STRENGTH Toad 6 13.3 7x0.0612 A 0.0206 0.169 4.29 24.4 36.3 580 2.6 Dragon 4 21.1 7x0.0772 A 0.0328 0.232 5.88 38.9 57.9 930 4.1 Moloch 2 33.6 7x0.0974 AA 0.0520 0.268 6.81 61.7 91.8 1400 6.2 Monitor 1 42.4 7x0.1093 AA 0.0657 0.299 7.59 78.1 116.2 1670 7.4 Newt 1 42.4 18x0.0682 A 0.0657 0.299 7.59 78.3 116.5 1860 8.3 Tuatara 1/0 53.5 7x0.1228 AA 0.0829 0.336 8.53 98.3 146.3 2040 9.1 Skink 1/0 53.5 18X0.0766 A 0.0830 0.336 8.53 98.8 147.0 2350 10.5 Alligator 2/0 67.4 7x0.1379 AA 0.1044 0.376 9.55 123.8 184.2 2570 11.4 Gecko 2/0 67.4 18x0.0860 A 0.1044 0.376 9.55 124.4 185.1 2880 12.8 Crocodile 3/0 85.0 7x0.1548 AA 0.1318 0.423 10.7 156.2 232.5 3150 14.0 Anoli 3/0 85.0 18x0.0965 A 0.1318 0.423 10.7 156.9 233.5 3540 15.7 Salamander 4/0 107.2 7x0.1739 AA 0.1661 0.475 12.1 197.4 293.8 3970 17.7 Clayman 4/0 107.2 18x0.1084 A 0.1663 0.475 12.1 197.9 294.5 4220 18.8 Komodo 266.8 135.2 18x0.1217 A 0.2096 0.537 13.6 250 372.1 5170 23.0 STANDARD PACKAGES (1) WT LENGTH REEL DESIG. kg M NR 36.22 COIL RW 48.24 COIL RW 48.24 COIL RW 50.32 COIL RW 60.32 COIL RW 50.32 COIL RW 60.32 COIL RW 50.32 RW 48.24 RW 60.32 RW 50.32 RW 50.32 RW 48.24 RW 60.32 RW 50.32 RW 50.32 RW 48.24 RW 60.32 RW 50.32 RW 60.32 RW 50.32 (1) Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 60 381 91 635 91 952 91 955 91 1225 91 953 91 1224 91 953 476 1633 817 949 475 1630 975 952 476 1630 815 1633 816 10485 2499 10969 1567 10363 988 8217 780 10509 777 6512 620 8327 617 5171 2585 8820 4410 4084 2042 6980 4176 3255 1628 5547 2774 4389 2194 Electric Utility Overhead Conductors TransPowr Compact (Smooth Body) ASC Bare Overhead Conductor to CSA C49.5 All-Aluminum Compact Stranded Conductor ® ASC, ALUMINUM CONDUCTOR, COMPACT-LAY-STRANDED (ELECTRICAL PROPERTIES) CODE WORD CONDUCTOR SIZE AWG OR kcmil mm2 CROSSO.D. STRANDING SECTIONAL NO. X DIA. AREA INCHES CLASS SQ. INCHES INCHES mm RESISTANCE (2) GEOMETRIC INDUCTIVE OHMS/1000 FT MEAN REACTANCE DC AC AC AMPACITY RADIUS OHM/1000 FT @ 20˚C @ 25˚C @ 75˚C 75˚C (3) FT (4) (4) CAPACITIVE REACTANCE MEGAOHM 1000 FT (4) Toad 6 13.3 7x0.0612 A 0.0206 0.169 4.29 0.6562 0.6695 0.8017 95 0.0052 0.1210 0.7765 Dragon 4 21.1 7x0.0772 A 0.0328 0.232 5.88 0.4117 0.4200 0.503 125 0.0065 0.1156 0.7400 Moloch 2 33.6 7x0.0974 AA 0.0520 0.268 6.81 0.2598 0.2650 0.3174 165 0.0082 0.1103 0.7039 Monitor 1 42.4 7x0.1093 AA 0.0657 0.299 7.59 0.2058 0.2100 0.2515 190 0.0092 0.1078 0.6871 Newt 1 42.4 18x0.0682 A 0.0657 0.299 7.59 0.2068 0.2111 0.2527 190 0.0095 0.1071 0.6870 Tuatara 1/0 53.5 7x0.1228 AA 0.0829 0.336 8.53 0.1631 0.1665 0.1993 220 0.0103 0.1051 0.6688 Skink 1/0 53.5 18X0.0766 A 0.0830 0.336 8.53 0.1639 0.1673 0.2003 220 0.0107 0.1044 0.6688 Alligator 2/0 67.4 7x0.1379 AA 0.1044 0.376 9.55 0.1295 0.1322 0.1583 255 0.0116 0.1025 0.6511 Gecko 2/0 67.4 18x0.0860 A 0.1044 0.376 9.55 0.1301 0.1328 0.1590 255 0.0119 0.1018 0.6510 Crocodile 3/0 85.0 7x0.1548 AA 0.1318 0.423 10.7 0.1027 0.1049 0.1255 295 0.0130 0.0998 0.6326 Anoli 3/0 85.0 18x0.0965 A 0.1318 0.423 10.7 0.1032 0.1054 0.1261 295 0.0134 0.0991 0.6327 Salamander 4/0 107.2 7x0.1739 AA 0.1661 0.475 12.1 0.0814 0.0832 0.0996 345 0.0146 0.0971 0.6143 Clayman 4/0 107.2 18x0.1084 A 0.1663 0.475 12.1 0.081809 0.0836 0.1001 340 0.0151 0.0964 0.6143 Komodo 266.8 135.2 18x0.1217 A 0.2096 0.537 13.6 0.0794 395 0.0170 0.0936 0.5952 0.0649 0.0663 (2)Based on a conductivity of 61.0% IACS at 20˚C. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by 3.281. (3)Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 32˚C ambient temperature, 1.98 ft/sec (0.6 m/s) crosswind (90˚ to conductor), 0.5 coefficient of emissivity, 0.5 coefficient of absorbtivity, 42˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 95.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (4)Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm). To convert the Geometric Mean Radius (GMR) to cm, divide the value by 0.03821. To convert inductive reactance to ohm/km, multiply the value by 3.281. To convert capacitive reactance to ohm/km, divide the value by 3.281. 61 Overhead Conductors Notes 62 Electric Utility Electric Utility Overhead Conductors Overhead Conductors TransPowr AAC/TW Bare Overhead Conductor to ASTM B778 ® Trapezoidal All-Aluminum 1350 Concentric-Lay-Stranded 17 Wire 2 Layer 34 Wire 3 Layer Product Construction: Complete Conductor: TransPowr ® AAC/TW is a trapezoidal 1350 H19 aluminum (AAC) concentric-lay-stranded conductor. The aluminum strands are trapezoidal in shape. The wedge-shaped aluminum strands enable a more compact alignment of the aluminum wires. Conductor designs that maintain the same circular mil cross-sectional area of aluminum as a conventional round conductor result in a TW conductor that is 10 to 15 percent smaller in overall diameter. Conductor designs that maintain the same overall diameter as a conventional round conductor result in a TW conductor that has 20 to 25 percent more aluminum cross-sectional area packed in. The AAC/TW conductors are manufactured in accordance with the requirements of the latest issue of ASTM B778. The conductor consists of two, three, four or five layers of aluminum 1350-H19 wires. The sizes and constructions listed on this and the following pages are examples used in overhead lines. 52 Wire 4 Layer Features and Benefits: TransPowr ® AAC /TW has a continuous operating temperature rating of 75°C. Operation of the conductor at elevated temperatures may increase the conductor sag properties and lower the rated tensile strength of the conductor. AAC/TW conductors constructed of equivalent aluminum circular mil cross-sectional area provide a conductor that is smaller in overall diameter than the equivalent conventional round wire AAC conductor. The reduced conductor diameter is advantageous in reducing the effects of ice and wind loading on the conductor. AAC/TW conductors constructed to equivalent overall diameter enable a greater circular mil cross-sectional area of aluminum within the conductor, allowing a significant increase in conductor current-carrying capacity. Electrical Parameters: The electrical parameters for the trapezoidal AAC equivalent circular mil area and equivalent overall diameter conductors may be found in the last table of this section. Options: •Compact aluminum strands •Trapezoidal-shaped aluminum strands (/TW) •High-Conductivity aluminum (/HC) (62.2% IACS) •Non-Specular surface finish (/NS) At the present time, CAN/CSA C61089 does not recognize TW conductor designs. The information provided on the following pages is from our US catalog. For more information, contact your General Cable sales representative or e-mail infoca@generalcable.com. Applications: Trapezoidal 1350 H19 aluminum conductors (AAC/TW) are used for overhead transmission lines where design parameters do not require the higher strength or temperature ratings provided by ACSR, ACSS, or other type conductors. 63 Overhead Conductors Electric Utility TransPowr AAC/TW Bare Overhead Conductor to ASTM B778 ® Trapezoidal All-Aluminum 1350 Concentric-Lay-Stranded AAC/TW CONDUCTORS (MECHANICAL PROPERTIES) – EQUIVALENT DIAMETER – CONDUCTORS SIZED TO HAVE EQUIVALENT CIRCULAR MIL AREA TO REGULAR AAC CODE WORD SIZE EQUIVALENT AWG NO. OF AL STRAND WIRE OR kcmil WIRES DIA. INCHES FILL FACTOR CROSS-SECTION SQ. O.D. INCHES INCHES APPROX. WEIGHT LB/1000 FT RATED STRENGTH LBS Tulip/AAC/TW 336.4 16 0.1453 89.8 0.2654 0.61 315 6050 Canna/AAC/TW 397.5 16 0.1579 91.0 0.3135 0.66 373 7000 Cosmos/AAC/TW 477.0 16 0.1730 91.1 0.3760 0.72 447 8390 Zinnia/AAC/TW 500.0 16 0.1771 92.3 0.3940 0.74 469 8790 Mistletoe/AAC/TW 556.5 16 0.1868 92.6 0.4387 0.78 522 9790 Meadowsweet/AAC/TW 600.0 16 0.1940 93.0 0.4729 0.80 562 10500 Orchid/AAC/TW 636.0 16 0.1996 93.4 0.5007 0.83 596 11200 Verbena/AAC/TW 700.0 16 0.2095 93.8 0.5514 0.86 656 12300 Nasturtium/AAC/TW 750.0 16 0.2168 94.0 0.5908 0.89 703 12900 Arbutus/AAC/TW 795.0 16 0.2231 94.1 0.6257 0.92 745 13600 Cockscomb/AAC/TW 900.0 16 0.2376 91.8 0.7092 0.99 844 15400 Magnolia/AAC/TW 954.0 31 0.1756 92.0 0.7509 1.02 894 16400 Hawkweed/AAC/TW 1000.0 31 0.1798 92.3 0.7868 1.04 937 17200 Bluebell/AAC/TW 1033.5 31 0.1827 92.5 0.8130 1.06 969 17700 Marigold/AAC/TW 1113.0 31 0.1897 92.8 0.8759 1.10 1043 19100 Hawthorn/AAC/TW 1192.5 31 0.1963 93.1 0.9382 1.13 1118 20500 Narcissus/AAC/TW 1272.0 31 0.2027 93.2 1.0006 1.17 1192 21800 Columbine/AAC/TW 1351.5 31 0.2090 93.6 1.0634 1.20 1267 23200 Carnation/AAC/TW 1431.0 31 0.2151 93.7 1.1260 1.24 1341 24000 Coreopsis/AAC/TW 1590.0 51 0.1767 91.9 1.2508 1.32 1490 27000 Jessamine/AAC/TW 1750.0 51 0.1853 92.3 1.3760 1.38 1640 29700 Cowslip/AAC/TW 2000.0 51 0.1981 92.8 1.5720 1.47 1875 33900 Lupine/AAC/TW 2500.0 71 0.1877 92.1 1.9655 1.65 2366 41900 Trillium/AAC/TW 3000.0 71 0.2056 92.7 2.3565 1.80 2839 50300 STANDARD PACKAGES (1) REEL WEIGHT LENGTH DESIGNATION LBS FT RMT 84.36 NR 60.28 RMT 84.36 NR 60.28 RMT 84.36 NR 60.28 RMT 84.36 NR 60.28 RMT 84.36 NR 60.28 RMT 84.36 NR 60.28 RMT 84.36 RM 68.38 RMT 84.36 NR 60.28 RMT 84.36 NR 60.28 RMT 84.36 NR 60.28 RMT 84.36 NR 60.28 RMT 96.60 RMT 84.36 RMT 96.60 RMT 84.36 RMT 96.60 RMT 84.36 RMT 96.60 RMT 84.36 RMT 96.60 RMT 84.36 RMT 96.60 RMT 84.36 RMT 96.60 RMT 84.36 RMT 96.60 RMT 84.36 RMT 96.60 RMT 90.45 RMT 96.60 RMT 90.45 RMT 96.60 RMT 90.45 RMT 108.74 RMT 96.60 RMT 108.74 RMT 96.60 4700 2360 4690 2350 4690 2370 4690 2340 4690 2350 4720 2360 4710 2320 4720 2360 4710 2390 4690 2380 4720 2360 9120 4560 9090 4590 9110 4550 9080 4590 9170 4580 9060 4530 9120 4560 9120 4560 9980 7450 10010 7550 10030 7570 19400 10410 20070 10320 (1) Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 64 14900 7500 12600 6300 10500 5300 10000 5000 9000 4500 8400 4200 7900 3900 7200 3600 6700 3400 6300 3200 5600 2800 10200 5100 9700 4900 9400 4700 8700 4400 8200 4100 7600 3800 7200 3600 6800 3400 6700 5000 6100 4600 5300 4000 8200 4400 7000 3600 Electric Utility Overhead Conductors TransPowr AAC/TW Bare Overhead Conductor to ASTM B778 ® Trapezoidal All-Aluminum 1350 Concentric-Lay-Stranded AAC/TW CONDUCTORS (ELECTRICAL PROPERTIES) – EQUIVALENT DIAMETER – CONDUCTORS SIZED TO HAVE EQUIVALENT CIRCULAR MIL AREA TO REGULAR AAC CODE WORD SIZE kcmil RESISTANCE (2) OHMS/1000 FT NO. EQUIVALENT CROSS-SECTION GEOMETRIC INDUCTIVE CAPACITIVE OF AL STRAND WIRE FILL SQ. O.D. DC AC AC AMPACITY MEAN REACTANCE REACTANCE MEGAOHM WIRES DIA. INCHES FACTOR INCHES INCHES @ 20˚C @ 25˚C @ 75˚C 75˚C (3) RADIUS FT OHM/1000 FT (4) 1000 FT (4) Tulip/AAC/TW 336.4 16 0.1453 89.8 0.2654 0.61 0.0514 0.0526 0.0630 500 0.0193 0.0907 0.5751 Canna/AAC/TW 397.5 16 0.1579 91.0 0.3135 0.66 0.0435 0.0446 0.0534 555 0.0209 0.0889 0.5630 Cosmos/AAC/TW 477.0 16 0.1730 91.1 0.3760 0.72 0.0362 0.0373 0.0445 625 0.0228 0.0869 0.5488 Zinnia/AAC/TW 500.0 16 0.1771 92.3 0.3940 0.74 0.0346 0.0356 0.0425 640 0.0232 0.0865 0.5461 Mistletoe/AAC/TW 556.5 16 0.1868 92.6 0.4387 0.78 0.0311 0.0320 0.0382 685 0.0245 0.0852 0.5380 Meadowsweet/AAC/TW 600.0 16 0.1940 93.0 0.4729 0.80 0.0288 0.0298 0.0355 715 0.0254 0.0844 0.5324 Orchid/AAC/TW 636.0 16 0.1996 93.4 0.5007 0.83 0.0272 0.0281 0.0335 745 0.0261 0.0838 0.5282 Verbena/AAC/TW 700.0 16 0.2095 93.8 0.5514 0.86 0.0247 0.0256 0.0305 790 0.0273 0.0827 0.5210 Nasturtium/AAC/TW 750.0 16 0.2168 94.0 0.5908 0.89 0.0230 0.0240 0.0286 820 0.0282 0.0820 0.5157 Arbutus/AAC/TW 795.0 16 0.2231 94.1 0.6257 0.92 0.0217 0.0227 0.0270 850 0.0291 0.0813 0.5112 Cockscomb/AAC/TW 900.0 16 0.2376 91.8 0.7092 0.99 0.0192 0.0201 0.0239 925 0.0313 0.0796 0.4997 Magnolia/AAC/TW 954.0 31 0.1756 92.0 0.7509 1.02 0.0181 0.0191 0.0226 955 0.0326 0.0787 0.4951 Hawkweed/AAC/TW 1000.0 31 0.1798 92.3 0.7868 1.04 0.0173 0.0182 0.0216 985 0.0333 0.0782 0.4917 Bluebell/AAC/TW 1033.5 31 0.1827 92.5 0.8130 1.06 0.0167 0.0177 0.0210 1005 0.0338 0.0778 0.4892 Marigold/AAC/TW 1113.0 31 0.1897 92.8 0.8759 1.10 0.0155 0.0165 0.0195 1050 0.0350 0.0770 0.4837 Hawthorn/AAC/TW 1192.5 31 0.1963 93.1 0.9382 1.13 0.0145 0.0155 0.0183 1095 0.0362 0.0763 0.4785 Narcissus/AAC/TW 1272.0 31 0.2027 93.2 1.0006 1.17 0.0136 0.0146 0.0173 1135 0.0374 0.0755 0.4736 Columbine/AAC/TW 1351.5 31 0.2090 93.6 1.0634 1.20 0.0128 0.0139 0.0163 1175 0.0384 0.0749 0.4691 Carnation/AAC/TW 1431.0 31 0.2151 93.7 1.1260 1.24 0.0121 0.0132 0.0155 1215 0.0395 0.0742 0.4647 Coreopsis/AAC/TW 1590.0 51 0.1767 91.9 1.2508 1.32 0.0109 0.0120 0.0141 1295 0.0423 0.0727 0.4549 Jessamine/AAC/TW 1750.0 51 0.1853 92.3 1.3760 1.38 0.00988 0.0111 0.0129 1370 0.0443 0.0716 0.4478 Cowslip/AAC/TW 2000.0 51 0.1981 92.8 1.5720 1.47 0.00864 0.00994 0.0115 1475 0.0472 0.0702 0.4377 Lupine/AAC/TW 2500.0 71 0.1877 92.1 1.9655 1.65 0.00698 0.00844 0.00969 1660 0.0531 0.0675 0.4196 Trillium/AAC/TW 3000.0 71 0.2056 92.7 2.3565 1.80 0.00582 0.00743 0.00843 1820 0.0580 0.0654 0.4059 (2)Based on a conductivity of 61.2% (minimum lot average) IACS at 20˚C. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by 3.281. (3)Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 25˚C ambient temperature, 2 ft/sec crosswind (90˚ to conductor), 0.5 coefficient of emissivity, 0.5 coefficient of absorbtivity, 30˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 96.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (4) Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius. 65 Overhead Conductors Electric Utility TransPowr AAC/TW Bare Overhead Conductor to ASTM B778 ® Trapezoidal All-Aluminum 1350 Concentric-Lay-Stranded AAC/TW CONDUCTORS (MECHANICAL PROPERTIES) – EQUIVALENT DIAMETER – CONDUCTORS SIZED TO HAVE EQUIVALENT CIRCULAR MIL AREA TO REGULAR AAC CODE WORD SIZE EQUIVALENT AWG NO. OF AL STRAND WIRE OR kcmil WIRES DIA. INCHES FILL FACTOR CROSS-SECTION SQ. O.D. INCHES INCHES APPROX. WEIGHT LB/1000 FT RATED STRENGTH LBS Logan/AAC/TW 322.5 16 0.1423 89.5 0.2546 0.60 302 5800 - none - 384.5 16 0.1553 91.0 0.3032 0.65 360 6700 Wheeler/AAC/TW 449.4 16 0.1679 91.7 0.3542 0.70 421 7900 - none - 521.7 16 0.1808 92.7 0.4108 0.75 489 9100 Robson/AAC/TW 595.8 16 0.1933 93.0 0.4693 0.80 558 10400 - none - 678.2 16 0.2062 93.8 0.5343 0.85 636 11900 McKinley/AAC/TW 761.5 16 0.2184 94.0 0.5995 0.90 714 13100 - none - 854.2 16 0.2314 94.6 0.6726 0.95 801 14700 Rainier/AAC/TW 918.8 31 0.1723 91.8 0.7227 1.00 861 15800 - none - 1020.0 31 0.1815 92.5 0.8023 1.05 956 17500 Helens/AAC/TW 1123.1 31 0.1905 92.8 0.8839 1.10 1053 19300 - none - 1234.2 31 0.1997 93.3 0.9707 1.15 1157 21200 Mazama/AAC/TW 1346.8 31 0.2085 93.5 1.0588 1.20 1262 23100 - none - 1467.9 31 0.2177 93.9 1.1542 1.25 1376 24700 Hood/AAC/TW 1583.2 31 0.2262 93.6 1.2457 1.30 1484 26600 - none - 1682.7 51 0.1817 92.3 1.3225 1.35 1577 28500 Whitney/AAC/TW 1812.7 51 0.1886 92.5 1.4243 1.40 1699 30800 - none - 1954.3 51 0.1959 92.9 1.5370 1.45 1832 33200 Powell/AAC/TW 2093.6 51 0.2027 93.0 1.6456 1.50 1982 35500 - none - 2245.4 51 0.2099 93.5 1.7653 1.55 2125 38100 Jefferson/AAC/TW 2388.1 51 0.2165 93.2 1.8782 1.60 2260 39700 - none - 2514.8 71 0.1883 92.4 1.9771 1.65 2380 42200 Shasta/AAC/TW 2667.2 71 0.1939 92.2 2.0957 1.70 2524 44700 - none - 2844.5 71 0.2003 92.9 2.2362 1.75 2692 47700 Adams/AAC/TW 3006.2 71 0.2058 92.7 2.3623 1.80 2873 50400 STANDARD PACKAGES (1) REEL WEIGHT LENGTH DESIGNATION LBS FT RMT 84.36 NR 60.28 RMT 84.36 NR 60.28 RMT 84.36 NR 60.28 RMT 84.36 NR 60.28 RMT 84.36 NR 60.28 RMT 84.36 NR 60.28 RMT 84.36 RM 68.38 RMT 84.36 NR 60.28 RMT 96.60 RMT 84.36 RMT 96.60 RMT 84.36 RMT 96.60 RMT 84.36 RMT 96.60 RMT 84.36 RMT 96.60 RMT 84.36 RMT 96.60 RMT 84.36 RMT 96.60 RMT 84.36 RMT 96.60 RMT 90.45 RMT 96.60 RMT 90.45 RMT 96.60 RMT 90.45 RMT 96.60 RMT 90.45 RMT 96.60 RMT 90.45 RMT 96.60 RMT 90.45 RMT 108.74 RMT 96.60 RMT 108.74 RMT 96.60 RMT 108.74 RMT 96.60 RMT 108.74 RMT 96.60 4720 2360 4720 2340 4720 2360 4690 2350 4690 2350 4700 2350 4710 2360 4720 2320 9130 4560 9080 4590 9160 4530 9140 4510 9090 4540 9080 4540 9050 4600 9940 7570 10020 7480 10070 7510 9910 7530 9990 7440 9950 7460 19520 10470 19690 10350 18850 10500 20110 10340 (1) Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 66 15600 7800 13100 6500 11200 5600 9600 4800 8400 4200 7400 3700 6600 3300 5900 2900 10600 5300 9500 4800 8700 4300 7900 3900 7200 3600 6600 3300 6100 3100 6300 4800 5900 4400 5500 4100 5000 3800 4700 3500 4400 3300 8200 4400 7800 4100 7000 3900 7000 3600 Electric Utility Overhead Conductors TransPowr AAC/TW Bare Overhead Conductor to ASTM B778 ® Trapezoidal All-Aluminum 1350 Concentric-Lay-Stranded AAC/TW CONDUCTORS (ELECTRICAL PROPERTIES) – EQUIVALENT DIAMETER – CONDUCTORS SIZED TO HAVE EQUIVALENT CIRCULAR MIL AREA TO REGULAR AAC CODE WORD RESISTANCE (2) OHMS/1000 FT SIZE NO. EQUIVALENT CROSS-SECTION GEOMETRIC INDUCTIVE CAPACITIVE AWG OF AL STRAND WIRE FILL SQ. O.D. DC AC AC AMPACITY MEAN REACTANCE REACTANCE MEGAOHM OR kcmil WIRES DIA. INCHES FACTOR INCHES INCHES @ 20˚C @ 25˚C @ 75˚C 75˚C (3) RADIUS FT OHM/1000 FT (4) 1000 FT (4) Logan/AAC/TW 322.5 16 0.1423 89.5 0.2546 0.60 0.0536 0.0549 0.0657 490 0.0189 0.0912 0.5782 - none - 384.5 16 0.1553 91.0 0.3032 0.65 0.0450 0.0461 0.0551 545 0.0205 0.0893 0.5656 Wheeler/AAC/TW 449.4 16 0.1679 91.7 0.3542 0.70 0.0385 0.0395 0.0472 600 0.0221 0.0876 0.5540 - none - 521.7 16 0.1808 92.7 0.4108 0.75 0.0331 0.0341 0.0408 660 0.0237 0.0860 0.5431 Robson/AAC/TW 595.8 16 0.1933 93.0 0.4693 0.80 0.0290 0.0300 0.0358 715 0.0253 0.0845 0.5330 - none - 678.2 16 0.2062 93.8 0.5343 0.85 0.0255 0.0264 0.0315 775 0.0269 0.0831 0.5234 McKinley/AAC/TW 761.5 16 0.2184 94.0 0.5995 0.90 0.0227 0.0236 0.0281 830 0.0285 0.0818 0.5145 - none - 854.2 16 0.2314 94.6 0.6726 0.95 0.0202 0.0212 0.0252 890 0.0300 0.0805 0.5060 Rainier/AAC/TW 918.8 31 0.1723 91.8 0.7227 1.00 0.0188 0.0198 0.0235 935 0.0320 0.0791 0.4979 - none - 1020.0 31 0.1815 92.5 0.8023 1.05 0.0169 0.0179 0.0212 995 0.0336 0.0780 0.4903 Helens/AAC/TW 1123.1 31 0.1905 92.8 0.8839 1.10 0.0154 0.0164 0.0194 1055 0.0352 0.0769 0.4830 - none - 1234.2 31 0.1997 93.3 0.9707 1.15 0.0140 0.0150 0.0177 1115 0.0368 0.0759 0.4760 Mazama/AAC/TW 1346.8 31 0.2085 93.5 1.0588 1.20 0.0128 0.0139 0.0164 1175 0.0384 0.0749 0.4693 - none - 1467.9 31 0.2177 93.9 1.1542 1.25 0.0118 0.0129 0.0151 1235 0.0400 0.0740 0.4629 Hood/AAC/TW 1583.2 31 0.2262 93.6 1.2457 1.30 0.0109 0.0121 0.0141 1290 0.0416 0.0731 0.4567 - none - 1682.7 51 0.1817 92.3 1.3225 1.35 0.0103 0.0115 0.0134 1340 0.0434 0.0721 0.4508 Whitney/AAC/TW 1812.7 51 0.1886 92.5 1.4243 1.40 0.00954 0.0108 0.0125 1395 0.0450 0.0712 0.4452 - none - 1954.3 51 0.1959 92.9 1.5370 1.45 0.00884 0.0101 0.0118 1455 0.0467 0.0704 0.4396 Powell/AAC/TW 2093.6 51 0.2027 93.0 1.6456 1.50 0.00834 0.00966 0.0112 1505 0.0483 0.0697 0.4343 - none - 2245.4 51 0.2099 93.5 1.7653 1.55 0.00777 0.00915 0.0106 1565 0.0498 0.0689 0.4292 Jefferson/AAC/TW 2388.1 51 0.2165 93.2 1.8782 1.60 0.00731 0.00873 0.0100 1615 0.0515 0.0682 0.4242 - none - 2514.8 71 0.1883 92.4 1.9771 1.65 0.00694 0.00841 0.00964 1665 0.0532 0.0674 0.4194 Shasta/AAC/TW 2667.2 71 0.1939 92.2 2.0957 1.70 0.00654 0.00806 0.00921 1715 0.0548 0.0667 0.4146 - none - 2844.5 71 0.2003 92.9 2.2362 1.75 0.00614 0.00770 0.00877 1770 0.0564 0.0661 0.4102 Adams/AAC/TW 3006.2 71 0.2058 92.7 2.3623 1.80 0.00586 0.00746 0.00848 1815 0.0581 0.0654 0.4057 (2)Based on a conductivity of 61.2% (minimum lot average) IACS at 20˚C. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by 3.281. (3)Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 25˚C ambient temperature, 2 ft/sec crosswind (90˚ to conductor), 0.5 coefficient of emissivity, 0.5 coefficient of absorbtivity, 30˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 96.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (4) Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius. 67 Overhead Conductors Notes 68 Electric Utility Electric Utility Overhead Conductors TransPowr A2 (AASC) Bare Overhead Conductor to CAN/CSA C61089 Aluminum Alloy Conductor Concentric-Lay-Stranded ® Product Construction: Complete Conductor: A2 conductors are high strength aluminum alloy, concentric-lay-stranded conductors. They are similar in construction and appearance to the A1 or AAC all-aluminum conductors. The conductors are manufactured in accordance with the requirements of the latest applicable issue of CAN/CSA C61089. A2 or AASC (Aluminum Alloy Stranded Conductor) are CSA reference terms. The A2/AASC conductors are manufactured from a heat-treated, magnesium-silicon high strength aluminum alloy. The aluminum strands consist of a concentric stranded cable of 7, 19, 37, or more wires. The sizes and strandings listed on the following pages are common examples used in overhead lines. Features and Benefits: Aluminum alloy conductors have a number of advantages over the use of the ACSR or all-aluminum conductors. •Lower power losses than for equivalent single aluminum layer ACSR conductors. (The inductive effect of the steel core in the ACSR is eliminated.) •Simpler fittings than those required for ACSR. •Excellent corrosion resistance in environments conducive to galvanic corrosion in ACSR. •Strength and sags approximately the same as for equivalent 6/1 and 26/7 ACSR conductors. •Outside diameters are the same as for standard ACSR conductors, permitting interchangeability of fittings. •Greater resistance to abrasion than that for 1350 wires in all-aluminum or ACSR conductors. Applications: A2 aluminum alloy conductors are extensively used for overhead distribution and transmission lines adjacent to ocean coastlines where there can be a problem of corrosion in the steel of an ACSR construction. The aluminum alloy conductors are used in place of single layer ACSR conductors (i.e., 6 AWG to 4/0 AWG) to reduce power losses in overhead distribution and transmission lines. The inductive effect of the ACSR’s steel core is eliminated, hence increasing the operating efficiency of the line. Option: •Non-Specular surface finish (/NS) For more information, contact your General Cable sales representative or e-mail infoca@generalcable.com. 69 Overhead Conductors Electric Utility TransPowr A2 (AASC) Bare Overhead Conductor to CAN/CSA C61089 Aluminum Alloy Conductor Concentric-Lay-Stranded ® A2 (AASC), ALUMINUM ALLOY CONDUCTOR, CONCENTRIC-LAY-STRANDED (MECHANICAL PROPERTIES) – CONDUCTOR SIZED TO HAVE DIAMETER EQUAL TO ACSR CODE WORD APPROX. CROSSCONDUCTOR SIZE EQUIVALENT EQUIVALENT STRANDING O.D. WEIGHT SECTIONAL AWG OR ACSR SIZE AAC SIZE NO. X DIA. AREA kcmil mm2 (1) (2) INCHES CLASS SQ. INCHES INCHES mm LB/kFT kg/km RATED STRENGTH LB kN -none- 8 9.6 8 8 7x0.0521 AA 0.0149 0.156 3.96 17.6 26.2 660 2.9 -none- 6 15.3 6 6 7x0.0657 AA 0.0237 0.197 5.01 28.0 41.7 1050 4.7 -none- 4 24.3 4 4 7x0.0828 AA 0.0377 0.248 6.31 44.4 66.1 1670 7.4 Halifax 2 38.7 2 2 7x0.1043 AA 0.0600 0.313 7.96 70.8 105.4 2660 11.8 -none- 1 48.8 1 1 7x0.1173 AA 0.0756 0.352 8.94 89.2 132.7 3350 14.9 Montreal 1/0 61.6 1/0 1/0 7x0.1318 AA 0.0955 0.395 10.04 112.6 167.6 4220 18.8 Winnipeg 2/0 77.6 2/0 2/0 7x0.1479 AA 0.1203 0.444 11.27 141.9 211.2 5320 23.7 Toronto 3/0 97.9 3/0 3/0 7x0.1661 AA 0.1518 0.498 12.66 179.0 266.4 6710 29.8 Vancouver 4/0 123.4 4/0 4/0 7x0.1865 AA 0.1914 0.560 14.21 225.6 335.7 8460 37.6 -none- 4/0 123.4 4/0 4/0 19x0.1132 AA 0.1912 0.566 14.38 226.7 337.4 8460 37.6 STANDARD PACKAGES (3) WT LENGTH REEL DESIG. kg M RW 48.24 NR 36.22 RW 48.24 NR 36.22 RW 48.24 NR 36.22 RW 60.32 RW 48.24 RW 60.32 RW 48.24 RW 60.32 RW 48.24 RW 60.32 RW 48.24 RW 60.32 RW 48.24 RW 60.32 RW 48.24 RW 66.36 RW 48.24 (1) Equivalent ACSR Size refers to an ACSR conductor size of equal diameter. (2)Equivalent AAC Size refers to an ASTM AAC 1350 conductor of approximate equivalent electrical resistance. (3)Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 70 479 239 476 238 755 378 954 477 953 476 952 476 952 476 953 477 952 635 1724 575 18287 9143 11429 5714 11429 5714 9053 4526 7176 3588 5684 2842 4510 2255 3578 1789 2837 1891 5111 1703 Electric Utility Overhead Conductors TransPowr A2 (AASC) Bare Overhead Conductor to CAN/CSA C61089 Aluminum Alloy Conductor Concentric-Lay-Stranded ® A2 (AASC), ALUMINUM ALLOY CONDUCTOR, CONCENTRIC-LAY-STRANDED (ELECTRICAL PROPERTIES) – CONDUCTOR SIZED TO HAVE DIAMETER EQUAL TO ACSR CODE WORD CONDUCTOR RESISTANCE (4) CROSSGEOMETRIC INDUCTIVE CAPACITIVE SIZE O.D. OHMS/1000 FT EQUIVALENT EQUIVALENT STRANDING SECTIONAL MEAN REACTANCE REACTANCE AWG OR ACSR SIZE AAC SIZE NO. X DIA. AREA DC AC AC AMPACITY RADIUS OHM/1000 FT MEGAOHM 2 kcmil mm (1) (2) INCHES CLASS SQ. INCHES INCHES mm @ 20˚C @ 25˚C @ 75˚C 75˚C (5) FT (6) 1000 FT (6) -none- 8 9.6 8 8 7x0.0521 AA 0.0149 0.156 3.96 1.0461 1.0644 1.2475 70 0.0047 0.1231 0.7887 -none- 6 15.3 6 6 7x0.0657 AA 0.0237 0.197 5.01 0.6564 0.6679 0.7828 95 0.0060 0.1177 0.7522 -none- 4 24.3 4 4 7x0.0828 AA 0.0377 0.248 6.31 0.4133 0.4205 0.4929 130 0.0075 0.1124 0.7160 Halifax 2 38.7 2 2 7x0.1045 AA 0.0600 0.313 7.96 0.2595 0.2641 0.3095 170 0.0095 0.1071 0.6796 -none- 1 48.8 1 1 7x0.1173 AA 0.0756 0.352 8.94 0.2058 0.2094 0.2455 200 0.0106 0.1044 0.6614 Montreal 1/0 61.6 1/0 1/0 7x0.1318 AA 0.0955 0.395 10.04 0.1630 0.1660 0.1945 235 0.0120 0.1017 0.6431 Winnipeg 2/0 77.6 2/0 2/0 7x0.1479 AA 0.1203 0.444 11.27 0.1294 0.1318 0.1544 270 0.0134 0.0991 0.6251 Toronto 3/0 97.9 3/0 3/0 7x0.1661 AA 0.1518 0.498 12.66 0.1026 0.1045 0.1224 315 0.0151 0.0964 0.6069 Vancouver 4/0 123.4 4/0 4/0 7x0.1865 AA 0.1914 0.560 14.21 0.0814 0.0829 0.0972 365 0.0169 0.0937 0.5887 -none- 4/0 123.4 4/0 4/0 19x0.1132 AA 0.1912 0.566 14.38 0.0818 0.0833 0.0976 360 0.0179 0.0925 0.5869 (4)Based on a conductivity of 53.0% IACS at 20˚C. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by 3.281. (5)Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 32˚C ambient temperature, 1.98 ft/sec (0.6 m/s) crosswind (90˚ to conductor), 0.5 coefficient of emissivity, 0.5 coefficient of absorbtivity, 42˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 95.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (6)Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm). To convert the Geometric Mean Radius (GMR) to cm, divide the value by 0.03821. To convert inductive reactance to ohm/km, multiply the value by 3.281. To convert capacitive reactance to ohm/km, divide the value by 3.281. 71 Overhead Conductors Notes 72 Electric Utility Electric Utility Overhead Conductors TransPowr ACSR Bare Overhead Conductor to CAN/CSA C61089 ® Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded Product Construction: Complete Conductor: Features and Benefits: ACSR conductors are recognized for their record of economy, dependability and favorable strength/ weight ratio. ACSR conductors combine the light weight and good conductivity of aluminum with the high tensile strength and ruggedness of steel. In line design, this can provide higher tensions, less sag, and longer span lengths than obtainable with most other types of overhead conductors. The steel strands are added as mechanical reinforcements. The cross-sections above illustrate some common strandings. ACSR is a composite concentric-lay-stranded conductor. The conductors are manufactured in accordance with the requirements of the latest applicable issue of CAN/CSA C61089. The steel strand or strands form the central core of the conductor, around which is stranded one or more layers of aluminum 1350-H19 wires. The steel core may consist of a single strand or a concentric stranded cable of 7, 19, 37, or more wires. Numerous combinations of aluminum and The steel core wires are protected from corrosion steel strands and layers are possible. The sizes and by galvanizing. The standard Class A zinc coating strandings listed on the following pages are common is usually adequate for ordinary environments. examples used in overhead lines. Metric (mm2) sizes For greater protection, Class B coating may be are also available. specified. High Strength (S2A) or Extra High The Canadian ACSR conductors are similar in Strength (S3A) steel core with Class A galvanizing design (strand component size and configuration) are also available. to the ACSR conductors designed to ASTM B232 specifications. Differences lie in the methods used The product is available with conductor corrosion to calculate the rated strength and dc resistance inhibitor treatment applied to the central steel values. component. CAN/CSA C61089 refers to ACSR as Type A1/S1A Applications: conductors, where the A1 refers to 1350 H19 Aluminum Conductors, Steel-Reinforced (ACSR) aluminum and the S1A as Class A galvanized, are extensively used for overhead distribution and regular strength steel. transmission lines. 12/12 Options: •High-Conductivity aluminum (/HC) (62.2% IACS) •CSA high-strength Class A galvanized steel core (S2A) •CSA extra-high-strength Class A galvanized steel core (S3A) •ASTM regular-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA2 to ASTM B802) •ASTM high-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA3 to ASTM B803) • Aluminum-clad steel core (20SA) •Non-Specular surface finish (/NS) •Aluminum Alloy Steel Reinforced Conductors (A2/SxA and A4/SxA) designs are available For more information, contact your General Cable sales representative or e-mail infoca@generalcable.com. 73 Overhead Conductors Electric Utility TransPowr ACSR Bare Overhead Conductor to CAN/CSA C61089 ® Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded ACSR, ALUMINUM CONDUCTOR, STEEL-REINFORCED, CONCENTRIC-LAY-STRANDED (MECHANICAL PROPERTIES) CODE WORD (1) CONDUCTOR SIZE AWG OR kcmil mm2 STRANDING NO. X DIA. INCHES AL STEEL CROSS-SECTION SQ. INCHES TOTAL AL APPROX. WEIGHT LB/1000 FT (2) O.D. INCHES mm TOTAL AL STEEL PERCENT BY MASS RATED STRENGTH AL LB kN STEEL Turkey 6 13.3 6x0.0661 1x0.0661 0.0240 0.0206 0.198 5.04 36.1 24.5 11.6 67.90 32.10 1160 5.16 Swan 4 21.1 6x0.0834 1x0.0834 0.0382 0.0328 0.250 6.36 57.4 38.9 18.4 67.89 32.11 1830 8.14 Swanate 4 21.1 7x0.0772 1x0.1029 0.0411 0.0328 0.257 6.54 67.0 38.9 28.0 58.13 41.87 2300 10.2 Sparrow 2 33.6 6x0.1052 1x0.1052 0.0608 0.0522 0.316 8.01 91.2 61.9 29.3 67.87 32.13 2800 12.5 Sparate 2 33.6 7x0.0974 1x0.1299 0.0654 0.0522 0.325 8.24 106.6 61.9 44.7 58.08 41.92 3510 15.6 Robin 1 42.4 6x0.1181 1x0.1181 0.0767 0.0657 0.354 9.00 115.0 78.1 36.9 67.88 32.12 3480 15.5 Raven 1/0 53.5 6x0.1327 1x0.1327 0.0968 0.0830 0.398 10.1 145.1 98.5 46.6 67.87 32.13 4250 18.9 Quail 2/0 67.4 6x0.1489 1x0.1489 0.1219 0.1045 0.447 11.3 182.9 124.2 58.7 67.89 32.11 5280 23.5 Pigeon 3/0 85.0 6x0.1672 1x0.1672 0.1537 0.1317 0.502 12.7 230.6 156.5 74.0 67.89 32.11 6660 29.6 Penguin 4/0 107.2 6x0.1878 1x0.1878 0.1939 0.1662 0.563 14.3 290.8 197.4 93.4 67.88 32.12 8400 37.4 Owl 266.8 135.2 6x0.2109 7x0.0703 0.2368 0.2096 0.633 16.1 341.0 249 92 73.01 26.99 9500 42.3 Waxwing 266.8 135.2 18x0.1217 1x0.1217 0.2210 0.2094 0.609 15.5 289.0 250 39 86.43 13.57 7000 31.1 Spoonbill 266.8 135.2 22x0.1101 7x0.0612 0.2300 0.2095 0.624 15.9 320.0 250 70 78.20 21.80 8800 39.1 Scaup 266.8 135.2 24x0.1054 7x0.0703 0.2366 0.2094 0.633 16.1 342.0 250 92 73.11 26.89 10100 44.9 Partridge 266.8 135.2 26x0.1013 7x0.0788 0.2437 0.2095 0.642 16.3 366.0 250 116 68.42 31.58 11300 50.3 STANDARD PACKAGES (3) WT LENGTH REEL DESIG. kg M NR 30.22 COIL NR 36.22 COIL RW 40.18 NR 30.22 COIL RW 48.24 NR 36.22 NR 30.22 COIL RW 48.24 NR 30.22 COIL RW 48.24 NR 36.22 NR 30.22 COIL RW 48.24 NR 36.22 NR 30.22 COIL RW 48.24 NR 36.22 NR 30.22 RW 48.24 NR 36.22 NR 30.22 RW 48.24 NR 36.22 NR 30.22 RM 68.38 RW 60.32 RW 48.24 RM 68.38 RW 66.36 RW 50.32 RM 68.38 RW 60.32 RW 50.32 RM 68.38 RW 66.36 RW 60.32 RW 60.32 268 88 401 100 544 272 109 803 401 268 100 544 272 109 801 401 268 100 803 401 268 100 803 401 268 801 401 268 803 401 268 2237 1118 559 1882 1882 941 1275 1275 851 1481 1481 989 1719 4980 1646 4700 1169 5459 2729 1091 5910 2955 1970 735 3429 1714 686 4681 2341 1560 582 3715 1858 1237 462 2947 1474 981 2338 1169 780 1853 927 617 4407 2204 1102 4377 4377 2188 2668 2668 1778 2902 2902 1935 3148 (1) Code words shown denote ACSR with regular-strength Class A galvanized steel core (S1A). See the Options section to find the appropriate code word modifier designation for alternative design options. (2)Due to rounding, total values may be slightly greater or slightly less than the sum of the component values. (3)Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 74 Electric Utility Overhead Conductors TransPowr ACSR Bare Overhead Conductor to CAN/CSA C61089 ® Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded ACSR, ALUMINUM CONDUCTOR, STEEL-REINFORCED, CONCENTRIC-LAY-STRANDED (ELECTRICAL PROPERTIES) CODE WORD (4) CONDUCTOR SIZE AWG OR kcmil mm2 STRANDING NO. X DIA. INCHES AL STEEL CROSS-SECTION SQ. INCHES TOTAL AL INCHES mm RESISTANCE (5) GEOMETRIC INDUCTIVE CAPACITIVE OHMS/1000 FT MEAN REACTANCE REACTANCE DC AC AC AMPACITY RADIUS OHM/1000 FT MEGAOHM @ 20˚C @ 25˚C @ 75˚C 75˚C (6) FT (7) 1000 FT (7) O.D. Turkey 6 13.3 6x0.0661 1x0.0661 0.0240 0.0206 0.198 5.04 0.658 0.671 0.804 95 0.0064 0.1163 0.7512 Swan 4 21.1 6x0.0834 1x0.0834 0.0382 0.0328 0.250 6.36 0.414 0.422 0.505 125 0.0080 0.1109 0.7148 Swanate 4 21.1 7x0.0772 1x0.1029 0.0411 0.0328 0.257 6.54 0.414 0.422 0.505 125 0.0085 0.1096 0.7104 Sparrow 2 33.6 6x0.1052 1x0.1052 0.0608 0.0522 0.316 8.01 0.260 0.265 0.318 165 0.0101 0.1056 0.6785 Sparate 2 33.6 7x0.0974 1x0.1299 0.0654 0.0522 0.325 8.24 0.260 0.265 0.318 165 0.0107 0.1043 0.6741 Robin 1 42.4 6x0.1181 1x0.1181 0.0767 0.0657 0.354 9.00 0.206 0.210 0.252 190 0.0113 0.1029 0.6603 Raven 1/0 53.5 6x0.1327 1x0.1327 0.0968 0.0830 0.398 10.1 0.163 0.167 0.200 220 0.0127 0.1003 0.6421 Quail 2/0 67.4 6x0.1489 1x0.1489 0.1219 0.1045 0.447 11.3 0.130 0.132 0.158 250 0.0143 0.0976 0.6240 Pigeon 3/0 85.0 6x0.1672 1x0.1672 0.1537 0.1317 0.502 12.7 0.103 0.105 0.126 285 0.0161 0.0950 0.6059 Penguin 4/0 107.2 6x0.1878 1x0.1878 0.1939 0.1662 0.563 14.3 0.0816 0.0833 0.100 325 0.0180 0.0923 0.5877 Owl 266.8 135.1876 6x0.2109 7x0.0703 0.2368 0.2096 0.633 16.1 0.0647 0.0661 0.0791 385 0.0202 0.0896 0.5695 Waxwing 266.8 135.2 18x0.1217 1x0.1217 0.2210 0.2094 0.609 15.5 0.0649 0.0664 0.0794 410 0.0197 0.0903 0.5756 Spoonbill 266.8 135.2 22x0.1101 7x0.0612 0.2300 0.2095 0.624 15.9 0.0650 0.0664 0.0795 410 0.0207 0.0891 0.5717 Scaup 266.8 135.2 24x0.1054 7x0.0703 0.2366 0.2094 0.633 16.1 0.0650 0.0664 0.0795 415 0.0212 0.0886 0.5695 Partridge 266.8 135.2 26x0.1013 7x0.0788 0.2437 0.2095 0.642 16.3 0.0651 0.0665 0.0796 415 0.0217 0.0880 0.5673 (4)Code words shown denote ACSR with regular-strength Class A galvanized steel core (S1A). See the Options section to find the appropriate code word modifier designation for alternative design options. (5)Based on a conductivity of 61.0% IACS at 20˚C for aluminum and ignores the effects of the steel core. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by 3.281. (6)Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 32˚C ambient temperature, 1.98 ft/sec (0.6 m/s) crosswind (90˚ to conductor), 0.5 coefficient of emissivity, 0.5 coefficient of absorbtivity, 42˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 95.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (7)Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm). To convert the Geometric Mean Radius (GMR) to cm, divide the value by 0.03821. To convert inductive reactance to ohm/km, multiply the value by 3.281. To convert capacitive reactance to ohm/km, divide the value by 3.281. 75 Overhead Conductors Electric Utility TransPowr ACSR Bare Overhead Conductor to CAN/CSA C61089 ® Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded ACSR, ALUMINUM CONDUCTOR, STEEL-REINFORCED, CONCENTRIC-LAY-STRANDED (MECHANICAL PROPERTIES) CODE WORD (1) CONDUCTOR SIZE AWG OR kcmil mm2 STRANDING NO. X DIA. INCHES AL STEEL CROSS-SECTION SQ. INCHES TOTAL AL APPROX. WEIGHT LB/1000 FT (2) O.D. INCHES mm TOTAL AL STEEL Junco 266.8 135.2 30x0.0943 7x0.0943 0.2584 0.2095 0.660 16.8 416.0 250 166 Phoebe 300.0 152.0 18x0.1291 1x0.1291 0.2487 0.2356 0.646 16.4 325.0 281 44 Piper 300.0 152.0 30x0.1000 7x0.1000 0.2906 0.2356 0.700 17.8 468.0 282 Ostrich Merlin 300.0 336.4 152.0 26x0.1074 7x0.0835 0.2739 0.2355 0.680 170.5 18x0.1367 1x0.1367 0.2789 0.2642 0.684 17.3 17.4 411.0 364.0 Woodcock 336.4 170.5 22x0.1237 7x0.0687 0.2903 0.2644 0.701 17.8 Widgeon 336.4 170.5 24x0.1184 7x0.0789 0.2985 0.2642 0.710 Linnet 336.4 Oriole PERCENT BY MASS RATED STRENGTH AL LB STEEL kN 60.20 39.80 13700 60.9 86.41 13.59 7900 35.1 186 60.20 39.80 15200 67.6 282 315 130 49 68.45 31.55 12700 86.42 13.58 8900 56.5 39.6 403.0 315 88 78.21 21.79 10900 48.5 18.0 431.0 315 116 73.13 26.87 12300 54.7 170.5 26x0.1137 7x0.0884 0.3072 0.2643 0.720 18.3 461.0 316 145 68.46 31.54 14000 62.3 336.4 170.5 30x0.1059 7x0.1059 0.3259 0.2642 0.741 18.8 525.0 316 209 60.20 39.80 17100 76.1 Chickadee 397.5 201.4 18x0.1486 1x0.1486 0.3295 0.3122 0.743 18.9 431.0 372 58 86.42 13.58 10200 45.4 Stork 397.5 201.4 22x0.1344 7x0.0747 0.3428 0.3121 0.762 19.3 477.0 373 104 78.20 21.80 12900 57.4 Brant 397.5 201.4 24x0.1287 7x0.0858 0.3527 0.3122 0.772 19.6 510.0 373 137 73.11 26.89 14600 64.9 Ibis 397.5 201.4 26x0.1236 7x0.0961 0.3630 0.3123 0.783 19.9 545.0 373 172 68.46 31.54 16100 71.6 Lark 397.5 201.4 30x0.1151 7x0.1151 0.3850 0.3121 0.806 20.5 620.0 373 247 60.21 39.79 20000 89.0 Pelican 477.0 241.7 18x0.1628 1x0.1628 0.3955 0.3747 0.814 20.7 517.0 447 70 86.42 13.58 12300 54.7 Toucan 477.0 241.7 22x0.1472 7x0.0818 0.4112 0.3744 0.834 21.2 572.0 447 125 78.21 21.79 15500 68.9 Flicker 477.0 241.7 24x0.1410 7x0.0940 0.4233 0.3747 0.846 21.5 612.0 447 165 73.11 26.89 17300 77.0 Hawk 477.0 241.7 26x0.1354 7x0.1053 0.4357 0.3747 0.858 21.8 654.0 448 206 68.45 31.55 19300 85.8 Hen 477.0 241.7 30x0.1261 7x0.1261 0.4621 0.3747 0.883 22.4 744.0 448 296 60.20 39.80 23200 103 Heron Osprey 500.0 556.5 253.4 30x0.1291 7x0.1291 0.4843 0.3927 0.904 282.0 18x0.1758 1x0.1758 0.4612 0.4369 0.879 23.0 22.3 780.0 603.0 469 521 310 82 60.20 39.80 24300 108.1 86.43 13.57 14300 63.6 STANDARD PACKAGES (3) WT LENGTH REEL DESIG. kg M RM 68.38 RW 66.36 RW 66.36 RW 60.32 RMT 84.36 RW 60.32 RW 60.32 RM 68.38 RW 66.36 RW 50.32 RMT 84.36 RW 60.32 RMT 84.36 RW 60.32 RMT 84.36 RW 60.32 RMT 84.36 RM 60.32 RM 68.38 RW 66.36 RW 50.32 RMT 84.36 RW 60.32 RMT 84.36 RW 60.32 RMT 84.36 RW 60.32 RM 68.38 RW 66.36 RM 68.38 RW 66.36 RW 50.32 RMT 84.36 RW 60.32 RMT 84.36 RW 60.32 RMT 84.36 RW 60.32 RM 68.38 RW 66.36 RM 68.38 RM 68.38 RW 66.36 RW 50.32 2254 2254 1887 943 3392 1696 1717 1885 1885 943 2549 1275 2971 1486 3438 1717 3383 1692 1882 1882 941 2542 1272 2964 1483 3436 1717 2252 2252 1882 1882 941 2549 1275 2964 1481 3429 1715 2250 2250 2250 1885 1885 941 3624 3624 3901 1951 4870 2435 2801 3472 3472 1736 4230 2115 4611 2306 4995 2498 4319 2159 2935 2935 1468 3575 1788 3898 1949 4227 2114 2432 2432 2447 2447 1224 2984 1492 3249 1625 3523 1762 2027 2027 1934 2100 2100 1050 (1) Code words shown denote ACSR with regular-strength Class A galvanized steel core (S1A). See the Options section to find the appropriate code word modifier designation for alternative design options. (2)Due to rounding, total values may be slightly greater or slightly less than the sum of the component values. (3)Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 76 Electric Utility Overhead Conductors TransPowr ACSR Bare Overhead Conductor to CAN/CSA C61089 ® Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded ACSR, ALUMINUM CONDUCTOR, STEEL-REINFORCED, CONCENTRIC-LAY-STRANDED (ELECTRICAL PROPERTIES) CODE WORD (4) CONDUCTOR SIZE AWG OR kcmil mm2 STRANDING NO. X DIA. INCHES AL STEEL CROSS-SECTION SQ. INCHES TOTAL AL INCHES mm RESISTANCE (5) GEOMETRIC INDUCTIVE CAPACITIVE OHMS/1000 FT MEAN REACTANCE REACTANCE DC AC AC AMPACITY RADIUS OHM/1000 FT MEGAOHM @ 20˚C @ 25˚C @ 75˚C 75˚C (6) FT (7) 1000 FT (7) O.D. Junco 266.8 135.2 30x0.0943 7x0.0943 0.2584 0.2095 0.660 16.8 0.0651 0.0665 0.0796 415 0.0227 0.0870 0.5629 Phoebe 300.0 152.0 18x0.1291 1x0.1291 0.2487 0.2356 0.646 16.4 0.0577 0.0591 0.0707 440 0.0209 0.0889 0.5664 Piper 300.0 152.0 30x0.1000 7x0.1000 0.2906 0.2356 0.700 17.8 0.0579 0.0591 0.0708 450 0.0241 0.0856 0.5537 Ostrich Merlin 300.0 336.4 152.0 170.5 26x0.1074 7x0.0835 0.2739 18x0.1367 1x0.1367 0.2789 0.2355 0.2642 0.680 0.684 17.3 17.4 0.0579 0.0515 0.0592 0.0527 0.0708 0.0631 445 475 0.0230 0.0221 0.0867 0.0876 0.5582 0.5574 Woodcock 336.4 170.5 22x0.1237 7x0.0687 0.2903 0.2644 0.701 17.8 0.0516 0.0527 0.0631 475 0.0232 0.0865 0.5535 Widgeon 336.4 170.5 24x0.1184 7x0.0789 0.2985 0.2642 0.710 18.0 0.0516 0.0527 0.0631 475 0.0238 0.0859 0.5514 Linnet 336.4 170.5 26x0.1137 7x0.0884 0.3072 0.2643 0.720 18.3 0.0516 0.0528 0.0632 480 0.0244 0.0854 0.5492 Oriole 336.4 170.5 30x0.1059 7x0.1059 0.3259 0.2642 0.741 18.8 0.0516 0.0528 0.0632 480 0.0255 0.0843 0.5447 Chickadee 397.5 201.4 18x0.1486 1x0.1486 0.3295 0.3122 0.743 18.9 0.0436 0.0447 0.0534 525 0.0240 0.0857 0.5443 Stork 397.5 201.4 22x0.1344 7x0.0747 0.3428 0.3121 0.762 19.3 0.0436 0.0447 0.0535 530 0.0252 0.0846 0.5404 Brant 397.5 201.4 24x0.1287 7x0.0858 0.3527 0.3122 0.772 19.6 0.0436 0.0447 0.0534 530 0.0259 0.0840 0.5383 Ibis 397.5 201.4 26x0.1236 7x0.0961 0.3630 0.3123 0.783 19.9 0.0437 0.0447 0.0535 530 0.0265 0.0835 0.5361 Lark 397.5 201.4 30x0.1151 7x0.1151 0.3850 0.3121 0.806 20.5 0.0437 0.0447 0.0535 535 0.0277 0.0824 0.5316 Pelican 477.0 241.7 18x0.1628 1x0.1628 0.3955 0.3747 0.814 20.7 0.0363 0.0373 0.0446 590 0.0263 0.0836 0.5301 Toucan 477.0 241.7 22x0.1472 7x0.0818 0.4112 0.3744 0.834 21.2 0.0364 0.0373 0.0446 590 0.0276 0.0825 0.5262 Flicker 477.0 241.7 24x0.1410 7x0.0940 0.4233 0.3747 0.846 21.5 0.0364 0.0373 0.0446 595 0.0283 0.0819 0.5240 Hawk 477.0 241.7 26x0.1354 7x0.1053 0.4357 0.3747 0.858 21.8 0.0364 0.0373 0.0446 595 0.0290 0.0814 0.5218 Hen 477.0 241.7 30x0.1261 7x0.1261 0.4621 0.3747 0.883 22.4 0.0364 0.0373 0.0446 600 0.0304 0.0803 0.5174 Heron Osprey 500.0 556.5 253.4 282.0 30x0.1291 7x0.1291 0.4843 18x0.1758 1x0.1758 0.4612 0.3927 0.4369 0.904 0.879 23.0 22.3 0.0347 0.0311 0.0356 0.0320 0.0425 0.0383 620 645 0.0311 0.0284 0.0797 0.0818 0.5137 0.5180 (4)Code words shown denote ACSR with regular-strength Class A galvanized steel core (S1A). See the Options section to find the appropriate code word modifier designation for alternative design options. (5)Based on a conductivity of 61.0% IACS at 20˚C for aluminum and ignores the effects of the steel core. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by 3.281. (6)Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 32˚C ambient temperature, 1.98 ft/sec (0.6 m/s) crosswind (90˚ to conductor), 0.5 coefficient of emissivity, 0.5 coefficient of absorbtivity, 42˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 95.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (7)Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm). To convert the Geometric Mean Radius (GMR) to cm, divide the value by 0.03821. To convert inductive reactance to ohm/km, multiply the value by 3.281. To convert capacitive reactance to ohm/km, divide the value by 3.281. 77 Overhead Conductors Electric Utility TransPowr ACSR Bare Overhead Conductor to CAN/CSA C61089 ® Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded ACSR, ALUMINUM CONDUCTOR, STEEL-REINFORCED, CONCENTRIC-LAY-STRANDED (MECHANICAL PROPERTIES) CODE WORD (1) CONDUCTOR SIZE AWG OR kcmil mm2 STRANDING NO. X DIA. INCHES AL STEEL CROSS-SECTION SQ. INCHES TOTAL AL APPROX. WEIGHT LB/1000 FT (2) O.D. INCHES mm TOTAL AL STEEL PERCENT BY MASS RATED STRENGTH AL LB STEEL kN Sapsucker 556.5 282.0 22x0.1590 7x0.0883 0.4800 0.4372 0.901 22.9 667.0 522 145 78.24 21.76 17700 78.7 Parakeet 556.5 282.0 24x0.1523 7x0.1015 0.4939 0.4372 0.914 23.2 714.0 522 192 73.12 26.88 19800 88.1 Dove 556.5 282.0 26x0.1463 7x0.1138 0.5083 0.4371 0.927 23.5 764.0 522 241 68.42 31.58 22500 100 Eagle 556.5 282.0 30x0.1362 7x0.1362 0.5391 0.4371 0.953 24.2 868.0 522 345 60.20 39.80 27000 120 -nonePeacock 605.0 605.0 306.6 22x0.1658 7x0.0921 0.5216 0.4750 0.940 306.6 24x0.1588 7x0.1059 0.5370 0.4753 0.953 23.9 24.2 725.0 776.0 567 567 158 209 78.22 21.78 19100 85.0 73.10 26.90 21600 96.1 Squab 605.0 306.6 26x0.1525 7x0.1186 0.5522 0.4749 0.966 24.5 830.0 568 262 68.44 31.56 24200 108 Wood Duck 605.0 306.6 30x0.1420 7x0.1420 0.5860 0.4751 0.994 25.2 943.0 568 375 60.20 39.80 29400 131 Duck 605.0 306.6 54x0.1058 7x0.1058 0.5366 0.4750 0.953 24.2 777.0 569 208 73.19 26.81 22600 101 Kingbird 636.0 322.3 18x0.1880 1x0.1880 0.5274 0.4997 0.940 23.9 689.0 596 94 86.42 13.58 16400 72.9 Goldfinch 636.0 322.3 22x0.1700 7x0.0944 0.5483 0.4994 0.963 24.5 762.0 596 166 78.23 21.77 20100 89.4 Rook 636.0 322.3 24x0.1628 7x0.1085 0.5643 0.4996 0.977 24.8 816.0 596 219 73.12 26.88 22700 101 Grosbeak 636.0 322.3 26x0.1564 7x0.1216 0.5808 0.4995 0.990 25.2 872.0 597 275 68.44 31.56 24900 111 Scoter 636.0 322.3 30x0.1456 7x0.1456 0.6160 0.4995 1.019 25.9 992.0 597 395 60.20 39.80 30900 137 Egret 636.0 322.3 30x0.1456 19x0.0874 0.6135 0.4995 1.019 25.9 987.0 601 387 60.83 39.17 31500 140 Goose 636.0 322.3 54x0.1085 7x0.1085 0.5640 0.4993 0.977 24.8 817.0 598 219 73.18 26.82 23400 104 Flamingo 666.6 337.8 24x0.1667 7x0.1111 0.5917 0.5238 1.000 25.4 855.0 625 230 73.12 26.88 23800 106 Gannet 666.6 337.8 26x0.1601 7x0.1245 0.6086 0.5234 1.014 25.8 914.0 626 289 68.44 31.56 26100 116 STANDARD PACKAGES (3) WT LENGTH REEL DESIG. kg M RMT 84.36 RW 60.32 RMT 84.36 RW 60.32 RMT 84.36 RW 60.32 RM 68.38 RW 66.36 RW 66.36 RMT 84.36 RW 60.32 RMT 84.36 RW 60.32 RM 68.38 RW 66.36 RMT 90.45 RM 68.38 RMT 84.36 RM 68.38 RW 66.36 RW 50.32 RMT 84.45 RMT 84.36 RW 60.32 RMT 84.45 RMT 84.36 RW 60.32 RMT 90.45 RMT 84.36 RW 60.32 RMT 96.60 RM 68.38 RMT 96.60 RMT 84.45 RM 68.38 RW 66.36 RMT 90.45 RM 68.38 RMT 84.45 RMT 84.36 RW 60.32 RMT 90.45 RMT 84.36 RW 60.32 2547 1272 2969 1483 3438 1719 2250 2250 1907 2971 1486 3438 1719 2250 2250 5017 2508 2835 1885 1885 941 3822 2547 1275 4452 2969 1483 5157 3438 1719 6772 2257 6697 4468 2234 2234 5020 2509 4461 2969 1486 5162 3445 1721 2557 1279 2786 1393 3020 1510 1737 1737 1768 2563 1282 2777 1388 1599 1599 4339 2169 2761 1835 1835 917 3356 2237 1119 3657 2438 1219 3965 2642 1321 4578 1525 4560 3042 1521 1521 4128 2063 3493 2326 1163 3782 2524 1262 (1) Code words shown denote ACSR with regular-strength Class A galvanized steel core (S1A). See the Options section to find the appropriate code word modifier designation for alternative design options. (2)Due to rounding, total values may be slightly greater or slightly less than the sum of the component values. (3)Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 78 Electric Utility Overhead Conductors TransPowr ACSR Bare Overhead Conductor to CAN/CSA C61089 ® Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded ACSR, ALUMINUM CONDUCTOR, STEEL-REINFORCED, CONCENTRIC-LAY-STRANDED (ELECTRICAL PROPERTIES) CODE WORD (4) CONDUCTOR SIZE AWG OR kcmil mm2 STRANDING NO. X DIA. INCHES AL STEEL CROSS-SECTION SQ. INCHES TOTAL AL INCHES mm RESISTANCE (5) GEOMETRIC INDUCTIVE CAPACITIVE OHMS/1000 FT MEAN REACTANCE REACTANCE DC AC AC AMPACITY RADIUS OHM/1000 FT MEGAOHM @ 20˚C @ 25˚C @ 75˚C 75˚C (6) FT (7) 1000 FT (7) O.D. Sapsucker 556.5 282.0 22x0.1590 7x0.0883 0.4800 0.4372 0.901 22.9 0.0312 0.0320 0.0383 650 0.0298 0.0807 0.5141 Parakeet 556.5 282.0 24x0.1523 7x0.1015 0.4939 0.4372 0.914 23.2 0.0312 0.0320 0.0383 655 0.0306 0.0801 0.5120 Dove 556.5 282.0 26x0.1463 7x0.1138 0.5083 0.4371 0.927 23.5 0.0312 0.0320 0.0383 655 0.0313 0.0796 0.5098 Eagle 556.5 282.0 30x0.1362 7x0.1362 0.5391 0.4371 0.953 24.2 0.0312 0.0320 0.0383 660 0.0328 0.0785 0.5053 -nonePeacock 605.0 605.0 306.6 306.6 22x0.1658 7x0.0921 0.5216 24x0.1588 7x0.1059 0.5370 0.4750 0.4753 0.940 0.953 23.9 24.2 0.0287 0.0287 0.0295 0.0295 0.0352 0.0352 685 690 0.0311 0.0319 0.0797 0.0792 0.5076 0.5054 Squab 605.0 306.6 26x0.1525 7x0.1186 0.5522 0.4749 0.966 24.5 0.0287 0.0295 0.0352 690 0.0327 0.0786 0.5032 Wood Duck 605.0 306.6 30x0.1420 7x0.1420 0.5860 0.4751 0.994 25.2 0.0287 0.0294 0.0352 695 0.0342 0.0776 0.4987 Duck 605.0 306.6 54x0.1058 7x0.1058 0.5366 0.4750 0.953 24.2 0.0288 0.0296 0.0353 690 0.0321 0.0790 0.5054 Kingbird 636.0 322.3 18x0.1880 1x0.1880 0.5274 0.4997 0.940 23.9 0.0272 0.0281 0.0335 705 0.0304 0.0803 0.5075 Goldfinch 636.0 322.3 22x0.1700 7x0.0944 0.5483 0.4994 0.963 24.5 0.0273 0.0281 0.0335 710 0.0319 0.0792 0.5036 Rook 636.0 322.3 24x0.1628 7x0.1085 0.5643 0.4996 0.977 24.8 0.0273 0.0281 0.0335 710 0.0327 0.0786 0.5015 Grosbeak 636.0 322.3 26x0.1564 7x0.1216 0.5808 0.4995 0.990 25.2 0.0273 0.0281 0.0335 715 0.0335 0.0781 0.4993 Scoter 636.0 322.3 30x0.1456 7x0.1456 0.6160 0.4995 1.019 25.9 0.0273 0.0280 0.0335 720 0.0351 0.0770 0.4948 Egret 636.0 322.3 30x0.1456 19x0.0874 0.6135 0.4995 1.019 25.9 0.0273 0.0280 0.0335 715 0.0351 0.0770 0.4948 Goose 636.0 322.3 54x0.1085 7x0.1085 0.5640 0.4993 0.977 24.8 0.0274 0.0281 0.0336 710 0.0330 0.0784 0.5015 Flamingo 666.6 337.8 24x0.1667 7x0.1111 0.5917 0.5238 1.000 25.4 0.0260 0.0268 0.0320 730 0.0335 0.0781 0.4978 Gannet 666.6 337.8 26x0.1601 7x0.1245 0.6086 0.5234 1.014 25.8 0.0261 0.0268 0.0320 735 0.0343 0.0775 0.4956 (4)Code words shown denote ACSR with regular-strength Class A galvanized steel core (S1A). See the Options section to find the appropriate code word modifier designation for alternative design options. (5)Based on a conductivity of 61.0% IACS at 20˚C for aluminum and ignores the effects of the steel core. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by 3.281. (6)Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 32˚C ambient temperature, 1.98 ft/sec (0.6 m/s) crosswind (90˚ to conductor), 0.5 coefficient of emissivity, 0.5 coefficient of absorbtivity, 42˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 95.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (7)Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm). To convert the Geometric Mean Radius (GMR) to cm, divide the value by 0.03821. To convert inductive reactance to ohm/km, multiply the value by 3.281. To convert capacitive reactance to ohm/km, divide the value by 3.281. 79 Overhead Conductors Electric Utility TransPowr ACSR Bare Overhead Conductor to CAN/CSA C61089 ® Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded ACSR, ALUMINUM CONDUCTOR, STEEL-REINFORCED, CONCENTRIC-LAY-STRANDED (MECHANICAL PROPERTIES) CODE WORD (1) CONDUCTOR SIZE AWG OR kcmil mm2 STRANDING NO. X DIA. INCHES AL STEEL CROSS-SECTION SQ. INCHES TOTAL AL APPROX. WEIGHT LB/1000 FT (2) O.D. INCHES mm TOTAL AL STEEL PERCENT BY MASS RATED STRENGTH AL LB STEEL kN -noneGull 666.6 666.6 337.8 42x0.1260 7x0.0700 0.5506 0.5237 0.966 337.8 54x0.1111 7x0.1111 0.5914 0.5235 1.000 24.5 717.0 25.4 857.0 626 627 91 230 87.28 12.72 17500 73.17 26.83 24500 78 109 Stilt 715.5 362.5 24x0.1727 7x0.1151 0.6350 0.5622 1.036 26.3 918.0 671 247 73.12 26.88 25500 113 Starling 715.5 362.5 26x0.1659 7x0.1290 0.6535 0.5620 1.051 26.7 982.0 672 310 68.43 31.57 28000 125 Redwing 715.5 362.5 30x0.1544 19x0.0926 0.6897 0.5617 1.081 27.5 1110 676 434 60.88 39.12 34600 154 -noneCrow 715.5 715.5 362.5 42x0.1305 7x0.0725 0.5907 0.5618 1.001 362.5 54x0.1151 7x0.1151 0.6347 0.5619 1.036 25.4 770.0 26.3 919.0 672 673 98 247 87.28 12.72 18800 73.17 26.83 26300 84 117 Macaw 795.0 402.8 42x0.1376 7x0.0764 0.6566 0.6245 1.055 26.8 855.0 746 109 87.29 12.71 20800 93 Tern 795.0 402.8 45x0.1329 7x0.0886 0.6674 0.6243 1.063 27.0 893.0 747 146 83.63 16.37 22700 101 Puffin 795.0 402.8 22x0.1901 7x0.1056 0.6857 0.6244 1.077 27.4 953.0 745 208 78.22 21.78 25100 112 Cuckoo 795.0 402.8 24x0.1820 7x0.1213 0.7053 0.6244 1.092 27.7 1019 745 274 73.13 26.87 27800 124 Condor 795.0 402.8 54x0.1213 7x0.1213 0.7050 0.6241 1.092 27.7 1022 748 274 73.18 26.82 28300 126 Drake 795.0 402.8 26x0.1749 7x0.1360 0.7263 0.6247 1.107 28.1 1091 746 344 68.43 31.57 31200 139 Mallard 795.0 402.8 30x0.1628 19x0.0977 0.7669 0.6245 1.140 28.9 1234 751 483 60.84 39.16 38400 171 -noneCrane 874.5 874.5 443.1 42x0.1443 7x0.0802 0.7222 0.6869 1.106 443.1 54x0.1273 7x0.1273 0.7760 0.6870 1.145 28.1 29.1 941 1124 821 822 120 302 87.27 12.73 22900 73.16 26.84 31200 102 139 -noneRuddy 900.0 900.0 456.0 42x0.1464 7x0.0813 0.7433 0.7070 1.122 456.0 45x0.1414 7x0.0943 0.7556 0.7067 1.131 28.5 28.7 971 1011 848 845 123 166 87.29 12.71 23600 83.62 16.38 25500 105 113 STANDARD PACKAGES (3) WT LENGTH REEL DESIG. kg M RMT 84.36 RMT 90.45 RM 68.38 RMT 84.45 RMT 84.36 RW 60.32 RMT 90.45 RMT 84.36 RW 60.32 RMT 96.60 RMT 84.45 RM 68.38 RW 66.36 RMT 84.36 RMT 90.45 RM 68.38 RMT 90.45 RM 68.38 RW 60.32 RMT 96.60 RMT 90.45 RM 68.38 RW 60.32 RMT 84.45 RMT 84.36 RW 60.32 RMT 84.45 RMT 84.36 RW 60.32 RMT 96.60 RMT 90.45 RMT 90.45 RMT 84.36 RW 60.32 RMT 96.60 RMT 84.45 RM 68.38 RMT 84.36 RMT 90.45 RM 68.38 RMT 84.36 RMT 96.60 RMT 90.45 RM 68.38 RW 60.32 3252 5015 2511 4454 2967 1483 5155 3441 1721 6691 4468 2234 2234 3276 5019 2509 4359 2180 1452 7307 4872 2436 1624 3819 2549 1275 4459 2969 1486 8677 5341 5155 3441 1721 6492 4466 2234 3276 5022 2511 3273 7301 4867 2434 1622 3048 3932 1969 3249 2164 1082 3520 2350 1175 4054 2706 1353 1353 2859 3670 1835 3414 1707 1137 5486 3657 1829 1219 2682 1789 895 2929 1951 975 5706 3511 3170 2115 1058 3536 2432 1216 2339 3002 1501 2265 4843 3228 1614 1076 (1) Code words shown denote ACSR with regular-strength Class A galvanized steel core (S1A). See the Options section to find the appropriate code word modifier designation for alternative design options. (2)Due to rounding, total values may be slightly greater or slightly less than the sum of the component values. (3)Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 80 Electric Utility Overhead Conductors TransPowr ACSR Bare Overhead Conductor to CAN/CSA C61089 ® Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded ACSR, ALUMINUM CONDUCTOR, STEEL-REINFORCED, CONCENTRIC-LAY-STRANDED (ELECTRICAL PROPERTIES) CODE WORD (4) CONDUCTOR SIZE AWG OR kcmil mm2 STRANDING NO. X DIA. INCHES AL STEEL CROSS-SECTION SQ. INCHES TOTAL AL INCHES mm RESISTANCE (5) GEOMETRIC INDUCTIVE CAPACITIVE OHMS/1000 FT MEAN REACTANCE REACTANCE DC AC AC AMPACITY RADIUS OHM/1000 FT MEGAOHM @ 20˚C @ 25˚C @ 75˚C 75˚C (6) FT (7) 1000 FT (7) O.D. -noneGull 666.6 666.6 337.8 337.8 42x0.1260 7x0.0700 0.5506 54x0.1111 7x0.1111 0.5914 0.5237 0.5235 0.966 1.000 24.5 25.4 0.0261 0.0261 0.0269 0.0269 0.0321 0.0321 725 730 0.0317 0.0337 0.0793 0.0779 0.5033 0.4978 Stilt 715.5 362.5 24x0.1727 7x0.1151 0.6350 0.5622 1.036 26.3 0.0242 0.0250 0.0298 765 0.0347 0.0773 0.4923 Starling 715.5 362.5 26x0.1659 7x0.1290 0.6535 0.5620 1.051 26.7 0.0243 0.0250 0.0299 765 0.0355 0.0767 0.4901 Redwing 715.5 362.5 30x0.1544 19x0.0926 0.6897 0.5617 1.081 27.5 0.0236 0.0243 0.0290 770 0.0369 0.0758 0.4856 -noneCrow 715.5 715.5 362.5 362.5 42x0.1305 7x0.0725 0.5907 54x0.1151 7x0.1151 0.6347 0.5618 0.5619 1.001 1.036 25.4 26.3 0.0243 0.0243 0.0251 0.0251 0.0299 0.0299 755 765 0.0329 0.0350 0.0785 0.0771 0.4977 0.4923 Macaw 795.0 402.8 42x0.1376 7x0.0764 0.6566 0.6245 1.055 26.8 0.0218 0.0227 0.0270 810 0.0346 0.0773 0.4895 Tern 795.0 402.8 45x0.1329 7x0.0886 0.6674 0.6243 1.063 27.0 0.0219 0.0227 0.0270 810 0.0352 0.0769 0.4882 Puffin 795.0 402.8 22x0.1901 7x0.1056 0.6857 0.6244 1.077 27.4 0.0218 0.0226 0.0269 815 0.0357 0.0766 0.4862 Cuckoo 795.0 402.8 24x0.1820 7x0.1213 0.7053 0.6244 1.092 27.7 0.0218 0.0225 0.0269 815 0.0366 0.0760 0.4840 Condor 795.0 402.8 54x0.1213 7x0.1213 0.7050 0.6241 1.092 27.7 0.0219 0.0226 0.0270 815 0.0368 0.0759 0.4840 Drake 795.0 402.8 26x0.1749 7x0.1360 0.7263 0.6247 1.107 28.1 0.0218 0.0225 0.0269 820 0.0375 0.0755 0.4818 Mallard 795.0 402.8 30x0.1628 19x0.0977 0.7669 0.6245 1.140 28.9 0.0218 0.0225 0.0269 825 0.0392 0.0744 0.4773 -noneCrane 874.5 874.5 443.1 443.1 42x0.1443 7x0.0802 0.7222 54x0.1273 7x0.1273 0.7760 0.6869 0.6870 1.106 1.145 28.1 29.1 0.0199 0.0199 0.0207 0.0206 0.0246 0.0246 855 865 0.0363 0.0386 0.0762 0.0748 0.4820 0.4766 -noneRuddy 900.0 900.0 456.0 456.0 42x0.1464 7x0.0813 0.7433 45x0.1414 7x0.0943 0.7556 0.7070 0.7067 1.122 1.131 28.5 28.7 0.0193 0.0193 0.0201 0.0201 0.0239 0.0239 870 875 0.0369 0.0374 0.0758 0.0755 0.4797 0.4785 (4)Code words shown denote ACSR with regular-strength Class A galvanized steel core (S1A). See the Options section to find the appropriate code word modifier designation for alternative design options. (5)Based on a conductivity of 61.0% IACS at 20˚C for aluminum and ignores the effects of the steel core. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by 3.281. (6)Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 32˚C ambient temperature, 1.98 ft/sec (0.6 m/s) crosswind (90˚ to conductor), 0.5 coefficient of emissivity, 0.5 coefficient of absorbtivity, 42˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 95.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (7)Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm). To convert the Geometric Mean Radius (GMR) to cm, divide the value by 0.03821. To convert inductive reactance to ohm/km, multiply the value by 3.281. To convert capacitive reactance to ohm/km, divide the value by 3.281. 81 Overhead Conductors Electric Utility TransPowr ACSR Bare Overhead Conductor to CAN/CSA C61089 ® Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded ACSR, ALUMINUM CONDUCTOR, STEEL-REINFORCED, CONCENTRIC-LAY-STRANDED (MECHANICAL PROPERTIES) CODE WORD (1) CONDUCTOR SIZE AWG OR kcmil mm2 STRANDING NO. X DIA. INCHES AL STEEL CROSS-SECTION SQ. INCHES TOTAL AL APPROX. WEIGHT LB/1000 FT (2) O.D. INCHES mm TOTAL AL STEEL PERCENT BY MASS RATED STRENGTH AL LB STEEL kN Canary 900.0 456.0 54x0.1291 7x0.1291 0.7985 0.7069 1.162 29.5 1157 846 310 73.17 26.83 32000 142 Phoenix 954.0 483.4 42x0.1507 7x0.0837 0.7877 0.7492 1.155 29.3 1026 896 130 87.29 12.71 24500 109 Rail 954.0 483.4 45x0.1456 7x0.0971 0.8011 0.7493 1.165 29.6 1072 896 176 83.62 16.38 27000 120 Towhee 954.0 483.4 48x0.1410 7x0.1097 0.8156 0.7495 1.175 29.8 1120 896 224 80.00 20.00 29400 131 Redbird 954.0 483.4 24x0.1994 7x0.1329 0.8466 0.7495 1.196 30.4 1223 895 329 73.12 26.88 33400 149 Cardinal 954.0 483.4 54x0.1329 7x0.1329 0.8462 0.7491 1.196 30.4 1226 897 329 73.18 26.82 34000 151 Snowbird 1033.5 523.7 42x0.1569 7x0.0872 0.8535 0.8117 1.203 30.5 1112 970 142 87.27 12.73 26500 118 Ortolan 1033.5 523.7 45x0.1515 7x0.1010 0.8677 0.8116 1.212 30.8 1161 971 190 83.64 16.36 28700 128 Whooper 1033.5 523.7 48x0.1467 7x0.1141 0.8830 0.8114 1.223 31.1 1213 971 242 80.02 19.98 31800 141 Curlew 1033.5 523.7 54x0.1383 7x0.1383 0.9167 0.8116 1.245 31.6 1328 972 356 73.18 26.82 36800 164 Beaumont (Avocet) 1113.0 564.0 42x0.1628 7x0.0904 0.9192 0.8742 1.248 31.7 1197 1045 152 87.29 12.71 28300 126 Bullfinch 1113.0 564.0 48x0.1523 7x0.1185 0.9516 0.8744 1.269 32.2 1307 1046 261 80.00 20.00 33700 150 Finch 1113.0 564.0 54x0.1436 19x0.0862 0.9851 0.8742 1.292 32.8 1423 1047 377 73.53 26.47 40400 180 Oxbird 1192.5 604.2 42x0.1685 7x0.0936 0.9847 0.9366 1.292 32.8 1283 1119 163 87.28 12.72 30400 135 Bunting 1192.5 604.2 45x0.1628 7x0.1085 1.0014 0.9367 1.302 33.1 1339 1120 219 83.64 16.36 33100 147 Cormorant 1192.5 604.2 48x0.1576 7x0.1226 1.0190 0.9364 1.313 33.4 1400 1120 280 80.01 19.99 35600 158 STANDARD PACKAGES (3) WT LENGTH REEL DESIG. kg M RMT 96.60 RMT 90.45 RMT 90.45 RM 68.38 RMT 96.60 RMT 90.45 RM 68.38 RW 60.32 RMT 96.60 RMT 90.45 RMT 84.36 RMT 84.45 RMT 84.36 RMT 96.60 RMT 90.45 RMT 90.45 RM 68.38 RMT 96.60 RMT 90.45 RM 68.38 RW 60.32 RMT 96.60 RMT 90.45 RMT 84.36 RMT 96.60 RMT 90.45 RMT 96.60 RMT 90.45 RM 68.38 RMT 96.60 RMT 90.45 RMT 84.36 RMT 96.60 RMT 90.45 RMT 96.60 RMT 90.45 RM 68.38 RMT 96.60 RMT 90.45 RM 68.38 RW 60.32 RMT 96.60 RMT 90.45 RMT 84.36 8689 5348 4355 2177 7307 4872 2436 1624 8151 5434 2717 4457 2969 8682 5343 4359 2180 7307 4869 2434 1622 8140 5430 2715 8682 5348 6536 4359 2180 8140 5432 2715 8634 5318 6534 4357 2180 7305 4869 2436 1622 8147 5430 2715 5041 3103 2847 1423 4572 3048 1524 1016 4877 3252 1626 2438 1625 4755 2926 2624 1312 4221 2813 1407 937 4502 3002 1501 4389 2703 3657 2438 1219 4176 2786 1393 4057 2499 3414 2277 1138 3657 2438 1219 812 3901 2600 1300 (1) Code words shown denote ACSR with regular-strength Class A galvanized steel core (S1A). See the Options section to find the appropriate code word modifier designation for alternative design options. (2)Due to rounding, total values may be slightly greater or slightly less than the sum of the component values. (3)Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 82 Electric Utility Overhead Conductors TransPowr ACSR Bare Overhead Conductor to CAN/CSA C61089 ® Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded ACSR, ALUMINUM CONDUCTOR, STEEL-REINFORCED, CONCENTRIC-LAY-STRANDED (ELECTRICAL PROPERTIES) CODE WORD (4) CONDUCTOR SIZE AWG OR kcmil mm2 STRANDING NO. X DIA. INCHES AL STEEL CROSS-SECTION SQ. INCHES TOTAL AL INCHES mm RESISTANCE (5) GEOMETRIC INDUCTIVE CAPACITIVE OHMS/1000 FT MEAN REACTANCE REACTANCE DC AC AC AMPACITY RADIUS OHM/1000 FT MEGAOHM @ 20˚C @ 25˚C @ 75˚C 75˚C (6) FT (7) 1000 FT (7) O.D. Canary 900.0 456.0 54x0.1291 7x0.1291 0.7985 0.7069 1.162 29.5 0.0193 0.0200 0.0239 880 0.0392 0.0744 0.4743 Phoenix 954.0 483.4 42x0.1507 7x0.0837 0.7877 0.7492 1.155 29.3 0.0182 0.0190 0.0226 905 0.0380 0.0752 0.4752 Rail 954.0 483.4 45x0.1456 7x0.0971 0.8011 0.7493 1.165 29.6 0.0182 0.0190 0.0226 905 0.0385 0.0748 0.4739 Towhee 954.0 483.4 48x0.1410 7x0.1097 0.8156 0.7495 1.175 29.8 0.0182 0.0190 0.0226 910 0.0391 0.0745 0.4726 Redbird 954.0 483.4 24x0.1994 7x0.1329 0.8466 0.7495 1.196 30.4 0.0182 0.0189 0.0225 915 0.0400 0.0739 0.4697 Cardinal 954.0 483.4 54x0.1329 7x0.1329 0.8462 0.7491 1.196 30.4 0.0182 0.0189 0.0226 915 0.0404 0.0738 0.4697 Snowbird 1033.5 523.7 42x0.1569 7x0.0872 0.8535 0.8117 1.203 30.5 0.0168 0.0176 0.0209 950 0.0395 0.0743 0.4689 Ortolan 1033.5 523.7 45x0.1515 7x0.1010 0.8677 0.8116 1.212 30.8 0.0168 0.0176 0.0209 950 0.0401 0.0739 0.4676 Whooper 1033.5 523.7 48x0.1467 7x0.1141 0.8830 0.8114 1.223 31.1 0.0168 0.0176 0.0209 955 0.0407 0.0736 0.4663 Curlew 1033.5 523.7 54x0.1383 7x0.1383 0.9167 0.8116 1.245 31.6 0.0168 0.0175 0.0209 960 0.0420 0.0728 0.4635 Beaumont (Avocet) 1113.0 564.0 42x0.1628 7x0.0904 0.9192 0.8742 1.248 31.7 0.0156 0.0164 0.0195 990 0.0410 0.0734 0.4631 Bullfinch 1113.0 564.0 48x0.1523 7x0.1185 0.9516 0.8744 1.269 32.2 0.0156 0.0164 0.0195 1000 0.0423 0.0727 0.4605 Finch 1113.0 564.0 54x0.1436 19x0.0862 0.9851 0.8742 1.292 32.8 0.0156 0.0163 0.0194 1005 0.0436 0.0720 0.4577 Oxbird 1192.5 604.2 42x0.1685 7x0.0936 0.9847 0.9366 1.292 32.8 0.0146 0.0154 0.0183 1035 0.0424 0.0726 0.4577 Bunting 1192.5 604.2 45x0.1628 7x0.1085 1.0014 0.9367 1.302 33.1 0.0146 0.0154 0.0182 1035 0.0431 0.0723 0.4564 Cormorant 1192.5 604.2 48x0.1576 7x0.1226 1.0190 0.9364 1.313 33.4 0.0146 0.0154 0.0182 1040 0.0437 0.0719 0.4551 (4)Code words shown denote ACSR with regular-strength Class A galvanized steel core (S1A). See the Options section to find the appropriate code word modifier designation for alternative design options. (5)Based on a conductivity of 61.0% IACS at 20˚C for aluminum and ignores the effects of the steel core. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by 3.281. (6)Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 32˚C ambient temperature, 1.98 ft/sec (0.6 m/s) crosswind (90˚ to conductor), 0.5 coefficient of emissivity, 0.5 coefficient of absorbtivity, 42˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 95.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (7)Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm). To convert the Geometric Mean Radius (GMR) to cm, divide the value by 0.03821. To convert inductive reactance to ohm/km, multiply the value by 3.281. To convert capacitive reactance to ohm/km, divide the value by 3.281. 83 Overhead Conductors Electric Utility TransPowr ACSR Bare Overhead Conductor to CAN/CSA C61089 ® Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded ACSR, ALUMINUM CONDUCTOR, STEEL-REINFORCED, CONCENTRIC-LAY-STRANDED (MECHANICAL PROPERTIES) CODE WORD (1) CONDUCTOR SIZE AWG OR kcmil mm2 STRANDING NO. X DIA. INCHES AL STEEL CROSS-SECTION SQ. INCHES TOTAL AL APPROX. WEIGHT LB/1000 FT (2) O.D. INCHES mm TOTAL AL STEEL PERCENT BY MASS RATED STRENGTH AL LB STEEL kN Grackle 1192.5 604.2 54x0.1486 19x0.0892 1.0553 0.9366 1.338 34.0 1525 1121 403 73.54 26.46 42600 189 Scissortail 1272.0 644.5 42x0.1740 7x0.0967 1.0502 0.9988 1.334 33.9 1368 1194 174 87.28 12.72 32400 144 Bittern 1272.0 644.5 45x0.1681 7x0.1121 1.0679 0.9988 1.345 34.2 1429 1195 234 83.63 16.37 35300 157 Diver 1272.0 644.5 48x0.1628 7x0.1266 1.0873 0.9991 1.357 34.5 1493 1195 298 80.02 19.98 38000 169 Pheasant 1272.0 644.5 54x0.1535 19x0.0921 1.1258 0.9993 1.381 35.1 1626 1196 430 73.55 26.45 44800 199 Ringdove 1351.5 684.8 42x0.1794 7x0.0997 1.1163 1.0616 1.375 34.9 1454 1269 185 87.27 12.73 34400 153 Dipper 1351.5 684.8 45x0.1733 7x0.1155 1.1348 1.0614 1.386 35.2 1518 1270 248 83.64 16.36 37500 167 -none- 1351.5 684.8 48x0.1678 7x0.1305 1.1551 1.0615 1.398 35.5 1587 1270 317 80.02 19.98 40300 179 Martin 1351.5 684.8 54x0.1582 19x0.0949 1.1958 1.0614 1.424 36.2 1728 1271 457 73.57 26.43 47600 212 Popinjay 1431.0 725.1 42x0.1846 7x0.1026 1.1820 1.1241 1.415 35.9 1539 1343 196 87.27 12.73 36500 162 Bobolink 1431.0 725.1 45x0.1783 7x0.1189 1.2014 1.1237 1.427 36.2 1608 1344 263 83.63 16.37 39700 177 Wagtail 1431.0 725.1 48x0.1727 7x0.1343 1.2235 1.1243 1.439 36.5 1680 1344 336 80.01 19.99 42700 190 Plover 1431.0 725.1 54x0.1628 19x0.0977 1.2665 1.1241 1.465 37.2 1830 1346 484 73.55 26.45 50500 225 -noneNuthatch 1510.5 1510.5 765.4 42x0.1896 7x0.1053 1.2472 1.1862 1.454 765.4 45x0.1832 7x0.1221 1.2682 1.1862 1.466 36.9 37.2 1624 1697 1418 1419 206 278 87.29 12.71 38500 83.64 16.36 41500 171 185 Parrot 1510.5 765.4 54x0.1672 19x0.1003 1.3362 1.1861 1.505 38.2 1930 1420 510 73.58 26.42 53200 237 STANDARD PACKAGES (3) WT LENGTH REEL DESIG. kg M RMT 96.60 RMT 90.45 RMT 96.60 RMT 90.45 RM 68.38 RMT 96.60 RMT 90.45 RM 68.38 RW 60.32 RMT 96.60 RMT 90.45 RMT 84.36 RMT 96.60 RMT 90.45 RMT 96.60 RMT 90.45 RM 68.38 RMT 96.60 RMT 90.45 RM 68.38 RW 60.32 RMT 96.60 RMT 90.45 RMT 84.36 RMT 96.60 RMT 90.45 RMT 96.60 RMT 90.45 RM 68.38 RMT 96.60 RMT 90.45 RM 68.38 RMT 96.60 RMT 90.45 RMT 84.36 RMT 96.60 RMT 90.45 RMT 84.45 RMT 96.60 RMT 90.45 RM 68.38 RMT 96.60 RMT 90.45 8630 5697 6534 4357 2177 7307 4872 2436 1624 8142 5430 2715 8630 5314 6539 4361 2180 7301 4867 2434 1624 8138 5427 2715 8625 5316 6534 4357 2177 7307 4869 2438 8142 5432 2715 8630 5314 4346 7305 4872 2436 8614 5309 3785 2499 3200 2133 1067 3429 2286 1143 762 3657 2438 1219 3551 2187 3011 2009 1004 3228 2152 1076 718 3441 2295 1148 3340 2059 2844 1896 948 3048 2031 1016 3249 2167 1084 3155 1943 1798 2889 1926 963 2987 1841 (1) Code words shown denote ACSR with regular-strength Class A galvanized steel core (S1A). See the Options section to find the appropriate code word modifier designation for alternative design options. (2)Due to rounding, total values may be slightly greater or slightly less than the sum of the component values. (3)Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 84 Electric Utility Overhead Conductors TransPowr ACSR Bare Overhead Conductor to CAN/CSA C61089 ® Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded ACSR, ALUMINUM CONDUCTOR, STEEL-REINFORCED, CONCENTRIC-LAY-STRANDED (ELECTRICAL PROPERTIES) CODE WORD (4) CONDUCTOR SIZE AWG OR kcmil mm2 STRANDING NO. X DIA. INCHES AL STEEL CROSS-SECTION SQ. INCHES TOTAL AL INCHES mm RESISTANCE (5) GEOMETRIC INDUCTIVE CAPACITIVE OHMS/1000 FT MEAN REACTANCE REACTANCE DC AC AC AMPACITY RADIUS OHM/1000 FT MEGAOHM @ 20˚C @ 25˚C @ 75˚C 75˚C (6) FT (7) 1000 FT (7) O.D. Grackle 1192.5 604.2 54x0.1486 19x0.0892 1.0553 0.9366 1.338 34.0 0.0146 0.0153 0.0182 1045 0.0451 0.0712 0.4523 Scissortail 1272.0 644.5 42x0.1740 7x0.0967 1.0502 0.9988 1.334 33.9 0.0137 0.0145 0.0172 1075 0.0438 0.0719 0.4526 Bittern 1272.0 644.5 45x0.1681 7x0.1121 1.0679 0.9988 1.345 34.2 0.0137 0.0145 0.0172 1080 0.0445 0.0715 0.4514 Diver 1272.0 644.5 48x0.1628 7x0.1266 1.0873 0.9991 1.357 34.5 0.0137 0.0145 0.0171 1080 0.0452 0.0712 0.4500 Pheasant 1272.0 644.5 54x0.1535 19x0.0921 1.1258 0.9993 1.381 35.1 0.0137 0.0144 0.0171 1090 0.0466 0.0705 0.4472 Ringdove 1351.5 684.8 42x0.1794 7x0.0997 1.1163 1.0616 1.375 34.9 0.0129 0.0137 0.0162 1115 0.0452 0.0712 0.4479 Dipper 1351.5 684.8 45x0.1733 7x0.1155 1.1348 1.0614 1.386 35.2 0.0129 0.0137 0.0162 1120 0.0459 0.0708 0.4466 -none- 1351.5 684.8 48x0.1678 7x0.1305 1.1551 1.0615 1.398 35.5 0.0129 0.0137 0.0162 1120 0.0466 0.0705 0.4453 Martin 1351.5 684.8 54x0.1582 19x0.0949 1.1958 1.0614 1.424 36.2 0.0129 0.0136 0.0161 1130 0.0480 0.0698 0.4425 Popinjay 1431.0 725.1 42x0.1846 7x0.1026 1.1820 1.1241 1.415 35.9 0.0121 0.0131 0.0154 1155 0.0465 0.0705 0.4434 Bobolink 1431.0 725.1 45x0.1783 7x0.1189 1.2014 1.1237 1.427 36.2 0.0121 0.0130 0.0154 1155 0.0472 0.0702 0.4422 Wagtail 1431.0 725.1 48x0.1727 7x0.1343 1.2235 1.1243 1.439 36.5 0.0121 0.0130 0.0153 1160 0.0479 0.0698 0.4408 Plover 1431.0 725.1 54x0.1628 19x0.0977 1.2665 1.1241 1.465 37.2 0.0122 0.0129 0.0153 1170 0.0494 0.0691 0.4380 -noneNuthatch 1510.5 1510.5 765.4 765.4 42x0.1896 7x0.1053 1.2472 45x0.1832 7x0.1221 1.2682 1.1862 1.1862 1.454 1.466 36.9 37.2 0.0115 0.0115 0.0124 0.0124 0.0146 0.0146 1190 1195 0.0478 0.0485 0.0699 0.0696 0.4392 0.4379 Parrot 1510.5 765.4 54x0.1672 19x0.1003 1.3362 1.1861 1.505 38.2 0.0115 0.0123 0.0145 1210 0.0508 0.0685 0.4338 (4)Code words shown denote ACSR with regular-strength Class A galvanized steel core (S1A). See the Options section to find the appropriate code word modifier designation for alternative design options. (5)Based on a conductivity of 61.0% IACS at 20˚C for aluminum and ignores the effects of the steel core. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by 3.281. (6)Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 32˚C ambient temperature, 1.98 ft/sec (0.6 m/s) crosswind (90˚ to conductor), 0.5 coefficient of emissivity, 0.5 coefficient of absorbtivity, 42˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 95.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (7)Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm). To convert the Geometric Mean Radius (GMR) to cm, divide the value by 0.03821. To convert inductive reactance to ohm/km, multiply the value by 3.281. To convert capacitive reactance to ohm/km, divide the value by 3.281. 85 Overhead Conductors Electric Utility TransPowr ACSR Bare Overhead Conductor to CAN/CSA C61089 ® Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded ACSR, ALUMINUM CONDUCTOR, STEEL-REINFORCED, CONCENTRIC-LAY-STRANDED (MECHANICAL PROPERTIES) CODE WORD (1) CONDUCTOR SIZE AWG OR kcmil mm2 STRANDING NO. X DIA. INCHES AL STEEL CROSS-SECTION SQ. INCHES TOTAL AL APPROX. WEIGHT LB/1000 FT (2) O.D. INCHES mm TOTAL AL STEEL PERCENT BY MASS RATED STRENGTH AL LB STEEL kN Ratite 1590.0 805.7 42x0.1946 7x0.1081 1.3133 1.2491 1.492 37.9 1710 1493 218 87.28 12.72 40500 180 Lapwing 1590.0 805.7 45x0.1880 7x0.1253 1.3354 1.2491 1.504 38.2 1786 1494 292 83.63 16.37 43700 194 Hornbill 1590.0 805.7 48x0.1820 7x0.1416 1.3590 1.2488 1.517 38.5 1867 1494 373 80.00 20.00 47500 211 Falcon 1590.0 805.7 54x0.1716 19x0.1030 1.4072 1.2489 1.544 39.2 2033 1495 538 73.54 26.46 56100 250 -noneChukar Seahawk Mockingbird Roadrunner Bluebird Kiwi Thrasher Joree 1590.0 1780.0 1869.0 2034.5 2057.5 2156.0 2167.0 2312.0 2515.0 37.7 40.7 40.7 42.7 43.2 44.8 44.1 45.8 47.7 1678 2062 1915 2147 2234 2497 2287 2510 2730 1495 1675 1757 1913 1935 2029 2037 2174 2365 183 387 158 234 299 468 249 336 365 89.10 81.22 91.75 89.10 86.61 81.25 89.10 86.61 86.61 173 239 190 221 238 282 235 268 291 805.7 901.9 947.0 1030.9 1042.5 1092.4 1098.0 1171.5 1274.4 72x0.1486 84x0.1456 68x0.1658 72x0.1681 76x0.1645 84x0.1602 72x0.1735 76x0.1744 76x0.1819 7x0.0991 19x0.0874 7x0.0921 7x0.1121 19x0.0768 19x0.0961 7x0.1157 19x0.0814 19x0.0849 1.3028 1.5118 1.5147 1.6671 1.7035 1.8309 1.7758 1.9145 2.0827 1.2488 1.3978 1.4681 1.5980 1.6155 1.6931 1.7022 1.8156 1.9751 1.486 1.601 1.603 1.681 1.700 1.762 1.735 1.802 1.880 10.90 18.78 8.25 10.90 13.39 18.75 10.90 13.39 13.39 38800 53800 42800 49700 53600 63300 52900 60200 65500 STANDARD PACKAGES (3) WT LENGTH REEL DESIG. kg M RMT 96.60 RMT 90.45 RM 68.38 RMT 96.60 RMT 90.45 RM 68.38 RMT 96.60 RMT 90.45 RMT 84.36 RMT 96.60 RMT 90.45 RMT 84.45 RMT 96.60 RMT 96.60 RMT 96.60 RMT 96.60 RMT 96.60 RMT 96.60 RMT 96.60 RMT 96.60 6534 4357 2177 7307 4872 2436 8147 5432 2715 8632 5316 3642 8650 7868 7310 7943 8530 7303 8011 7845 2560 1707 853 2743 1829 914 2926 1951 975 2841 1749 1458 2804 2743 2274 2377 2286 2133 2133 1920 (1) Code words shown denote ACSR with regular-strength Class A galvanized steel core (S1A). See the Options section to find the appropriate code word modifier designation for alternative design options. (2)Due to rounding, total values may be slightly greater or slightly less than the sum of the component values. (3)Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 86 Electric Utility Overhead Conductors TransPowr ACSR Bare Overhead Conductor to CAN/CSA C61089 ® Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded ACSR, ALUMINUM CONDUCTOR, STEEL-REINFORCED, CONCENTRIC-LAY-STRANDED (ELECTRICAL PROPERTIES) CODE WORD (4) CONDUCTOR SIZE AWG OR kcmil mm2 STRANDING NO. X DIA. INCHES AL STEEL CROSS-SECTION SQ. INCHES TOTAL AL INCHES mm RESISTANCE (5) GEOMETRIC INDUCTIVE CAPACITIVE OHMS/1000 FT MEAN REACTANCE REACTANCE DC AC AC AMPACITY RADIUS OHM/1000 FT MEGAOHM @ 20˚C @ 25˚C @ 75˚C 75˚C (6) FT (7) 1000 FT (7) O.D. Ratite 1590.0 805.7 42x0.1946 7x0.1081 1.3133 1.2491 1.492 37.9 0.0109 0.0119 0.0140 1230 0.0490 0.0693 0.4352 Lapwing 1590.0 805.7 45x0.1880 7x0.1253 1.3354 1.2491 1.504 38.2 0.0109 0.0118 0.0139 1230 0.0497 0.0690 0.4339 Hornbill 1590.0 805.7 48x0.1820 7x0.1416 1.3590 1.2488 1.517 38.5 0.0109 0.0118 0.0139 1235 0.0505 0.0686 0.4326 Falcon 1590.0 805.7 54x0.1716 19x0.1030 1.4072 1.2489 1.544 39.2 0.0109 0.0117 0.0138 1245 0.0521 0.0679 0.4297 -noneChukar Seahawk Mockingbird Roadrunner Bluebird Kiwi Thrasher Joree 1590.0 1780.0 1869.0 2034.5 2057.5 2156.0 2167.0 2312.0 2515.0 1.2488 1.3978 1.4681 1.5980 1.6155 1.6931 1.7022 1.8156 1.9751 1.486 1.601 1.603 1.681 1.700 1.762 1.735 1.802 1.880 37.7 40.7 40.7 42.7 43.2 44.8 44.1 45.8 47.7 0.0109 0.00978 0.00931 0.00855 0.00845 0.00807 0.00803 0.00752 0.00692 0.0119 0.0107 0.0104 0.00967 0.00953 0.00909 0.00918 0.00868 0.00813 0.0140 0.0126 0.0122 0.0113 0.0111 0.0106 0.0107 0.0101 0.00937 1225 1320 1340 1410 1425 1470 1460 1520 1590 0.0489 0.0534 0.0524 0.0553 0.0562 0.0588 0.0570 0.0595 0.0621 0.0694 0.0673 0.0678 0.0665 0.0662 0.0651 0.0658 0.0648 0.0639 0.4358 0.4241 0.4239 0.4165 0.4147 0.4091 0.4115 0.4055 0.3989 805.7 901.9 947.0 1030.9 1042.5 1092.4 1098.0 1171.5 1274.4 72x0.1486 84x0.1456 68x0.1658 72x0.1681 76x0.1645 84x0.1602 72x0.1735 76x0.1744 76x0.1819 7x0.0991 19x0.0874 7x0.0921 7x0.1121 19x0.0768 19x0.0961 7x0.1157 19x0.0814 19x0.0849 1.3028 1.5118 1.5147 1.6671 1.7035 1.8309 1.7758 1.9145 2.0827 (4)Code words shown denote ACSR with regular-strength Class A galvanized steel core (S1A). See the Options section to find the appropriate code word modifier designation for alternative design options. (5)Based on a conductivity of 61.0% IACS at 20˚C for aluminum and ignores the effects of the steel core. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by 3.281. (6)Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 32˚C ambient temperature, 1.98 ft/sec (0.6 m/s) crosswind (90˚ to conductor), 0.5 coefficient of emissivity, 0.5 coefficient of absorbtivity, 42˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 95.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (7)Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm). To convert the Geometric Mean Radius (GMR) to cm, divide the value by 0.03821. To convert inductive reactance to ohm/km, multiply the value by 3.281. To convert capacitive reactance to ohm/km, divide the value by 3.281. 87 Overhead Conductors Electric Utility TransPowr ACSR Bare Overhead Conductor to CAN/CSA C61089 ® Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded ACSR, ALUMINUM CONDUCTOR, STEEL-REINFORCED, CONCENTRIC-LAY-STRANDED HIGH-STRENGTH STRANDING (MECHANICAL PROPERTIES) CODE WORD (1) CONDUCTOR SIZE AWG OR kcmil mm2 Grouse Petrel Minorca Leghorn Guinea Dotterel Dorking Auk Brahma Cochin 80.0 101.8 110.8 134.6 159.0 176.9 190.8 203.0 203.2 211.3 40.5 51.6 56.1 68.2 80.6 89.6 96.7 102.9 103.0 107.1 STRANDING NO. X DIA. INCHES CROSS-SECTION SQ. INCHES APPROX. WEIGHT LB/1000 FT (2) O.D. PERCENT BY MASS RATED STRENGTH AL STEEL TOTAL AL INCHES mm TOTAL AL STEEL AL STEEL LB kN 8x0.1000 12x0.0921 12x0.0961 12x0.1059 12x0.1151 12x0.1214 12x0.1261 8x0.1593 16x0.1127 12x0.1327 1x0.1670 7x0.0921 7x0.0961 7x0.1059 7x0.1151 7x0.1214 7x0.1261 7x0.0886 19x0.0977 7x0.1327 0.0847 0.1266 0.1378 0.1674 0.1977 0.2199 0.2373 0.2026 0.3020 0.2628 0.0628 0.0799 0.0870 0.1057 0.1249 0.1389 0.1499 0.1594 0.1596 0.1660 0.367 0.461 0.480 0.530 0.576 0.607 0.630 0.584 0.714 0.663 9.32 11.7 12.2 13.5 14.6 15.4 16.0 14.8 18.1 16.9 148.5 253.5 276.0 335.2 395.9 440.5 475.2 335.5 674.6 526.2 74.6 95.6 104.0 126.4 149.3 166.1 179.1 189.4 191.4 198.4 73.9 157.9 171.9 208.8 246.7 274.4 296.1 146.1 483.2 327.9 50.26 37.70 37.69 37.70 37.70 37.71 37.70 56.45 28.37 37.70 49.74 62.30 62.31 62.30 62.30 62.29 62.30 43.55 71.63 62.30 5130 9860 10730 12950 15210 16350 17640 11140 27600 19540 22.8 43.9 47.7 57.6 67.7 72.7 78.5 49.6 123 86.9 STANDARD PACKAGES (3) WT LENGTH REEL DESIG. kg M NR 36.22 RW 50.32 RW 50.32 RW 50.32 RW 50.32 RW 50.32 RW 50.32 RW 50.32 RW 60.32 RW 50.32 513 1440 1438 1440 1440 1440 1440 964 1919 1440 2310 3810 3499 2880 2438 2193 2031 1931 1911 1835 ACSR, ALUMINUM CONDUCTOR, STEEL-REINFORCED, CONCENTRIC-LAY-STRANDED CANADIAN DIAMETER-BASED SIZES (MECHANICAL PROPERTIES) CODE WORD (1) Shelter Bay Chignecto Peace River Mica Grand Rapids Chutes Des Passes Les Boules Carillon Gatineau Seaway Bersfort Bersimis Nelson CONDUCTOR SIZE AWG OR kcmil mm2 STRANDING NO. X DIA. INCHES CROSS-SECTION SQ. INCHES AL STEEL TOTAL AL APPROX. WEIGHT LB/1000 FT (2) O.D. INCHES mm TOTAL 604.0 706.0 734.0 855.0 821.0 955.0 PERCENT BY MASS RATED STRENGTH AL STEEL AL STEEL LB kN STANDARD PACKAGES (3) WT LENGTH REEL DESIG. kg M 504.2 588.9 625.8 666.9 685.4 849.6 255.5 298.4 317.1 337.9 347.3 430.5 22x0.1514 22x0.1636 48x0.1141 24x0.1667 22x0.1765 45x0.1374 7x0.0841 7x0.0909 7x0.0886 7x0.1110 7x0.0980 7x0.0917 0.4349 0.5079 0.5347 0.5916 0.5911 0.7136 0.3961 0.4625 0.4916 0.5238 0.5383 0.6673 0.858 0.927 0.951 1.000 1.000 1.099 21.8 23.6 24.2 25.4 25.4 27.9 473 552 588 625 643 798 132 154 146 229 179 157 78.21 78.19 80.09 73.15 78.23 83.59 21.79 21.81 19.91 26.85 21.77 16.41 16100 18600 19800 23700 21600 24100 71.6 82.7 88.1 105 96.1 107 RW 66.36 RM 66.32 RM 68.38 RM 68.38 RM 66.32 RMT 84.45 1912 1913 2038 3393 1912 3660 2127 1821 1865 2667 1565 2575 864.9 1028.7 1168.1 1277.5 1354.8 1361.0 1840.0 438.2 521.2 591.9 647.3 686.5 689.6 932.3 42x0.1435 42x0.1565 48x0.1560 42x0.1744 48x0.1680 42x0.1800 72x0.1598 7x0.0797 7x0.0870 7x0.1213 7x0.0969 7x0.1307 7x0.1000 7x0.1063 0.7142 0.8496 0.9983 1.0549 1.1580 1.1238 1.5068 0.6793 0.8080 0.9174 1.0033 1.0640 1.0688 1.4447 1.100 1.200 1.300 1.337 1.400 1.380 1.598 27.9 930.0 812 30.5 1107 966 33.0 1371 1097 34.0 1374 1199 35.6 1591 1273 35.1 1464 1278 40.6 1940 1730 118 141 274 175 318 186 210 87.29 87.27 80.02 87.28 80.01 87.28 89.16 12.71 12.73 19.98 12.72 19.99 12.72 10.84 22700 26400 34900 32500 40400 34700 44800 101 117 155 145 180 154 199 RMT 84.36 RMT 84.36 RMT 84.45 RMT 84.36 RMT 84.45 RMT 84.36 RMT 96.60 3274 3276 4080 3272 4077 3274 5491 2365 1989 1999 1600 1722 1503 1902 (1) Code words shown denote ACSR with regular-strength Class A galvanized steel core (S1A). See the Options section to find the appropriate code word modifier designation for alternative design options. (2)Due to rounding, total values may be slightly greater or slightly less than the sum of the component values. (3)Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 88 Electric Utility Overhead Conductors TransPowr ACSR Bare Overhead Conductor to CAN/CSA C61089 ® Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded ACSR, ALUMINUM CONDUCTOR, STEEL-REINFORCED, CONCENTRIC-LAY-STRANDED HIGH-STRENGTH STRANDING (ELECTRICAL PROPERTIES) CODE WORD (4) Grouse Petrel Minorca Leghorn Guinea Dotterel Dorking Auk Brahma Cochin CONDUCTOR SIZE AWG OR kcmil mm2 80.0 101.8 110.8 134.6 159.0 176.9 190.8 203.0 203.2 211.3 40.5 51.6 56.1 68.2 80.6 89.6 96.7 102.9 103.0 107.1 STRANDING NO. X DIA. INCHES AL STEEL 8x0.1000 1x0.1670 12x0.0921 7x0.0921 12x0.0961 7x0.0961 12x0.1059 7x0.1059 12x0.1151 7x0.1151 12x0.1214 7x0.1214 12x0.1261 7x0.1261 8x0.1593 7x0.0886 16x0.1127 19x0.0977 12x0.1327 7x0.1327 CROSS-SECTION SQ. INCHES TOTAL AL INCHES mm RESISTANCE (5) GEOMETRIC INDUCTIVE CAPACITIVE OHMS/1000 FT MEAN REACTANCE REACTANCE DC AC AC AMPACITY RADIUS OHM/1000 FT MEGAOHM @ 20˚C @ 25˚C @ 75˚C 75˚C (6) FT (7) 1000 FT (7) 0.0847 0.1266 0.1378 0.1674 0.1977 0.2199 0.2373 0.2026 0.3020 0.2628 0.0628 0.0799 0.0870 0.1057 0.1249 0.1389 0.1499 0.1594 0.1596 0.1660 0.367 0.461 0.480 0.530 0.576 0.607 0.630 0.584 0.714 0.663 9.32 11.7 12.2 13.5 14.6 15.4 16.0 14.8 18.1 16.9 0.206 0.158 0.145 0.120 0.101 0.0911 0.0845 0.0850 0.0764 0.0763 O.D. 0.211 0.161 0.148 0.122 0.103 0.0929 0.0862 0.0868 0.0779 0.0778 0.252 0.193 0.177 0.146 0.124 0.111 0.103 0.104 0.093 0.093 185 220 230 255 280 300 310 320 330 330 0.0122 0.0163 0.0170 0.0187 0.0203 0.0214 0.0223 0.0197 0.0260 0.0234 0.1012 0.0947 0.0937 0.0914 0.0895 0.0883 0.0874 0.0903 0.0839 0.0863 0.6549 0.6193 0.6126 0.5974 0.5843 0.5760 0.5701 0.5820 0.5506 0.5621 ACSR, ALUMINUM CONDUCTOR, STEEL-REINFORCED, CONCENTRIC-LAY-STRANDED CANADIAN DIAMETER-BASED SIZES (ELECTRICAL PROPERTIES) CODE WORD (4) Shelter Bay Chignecto Peace River Mica Grand Rapids Chutes Des Passes Les Boules Carillon Gatineau Seaway Bersfort Bersimis Nelson CONDUCTOR SIZE AWG OR kcmil mm2 STRANDING NO. X DIA. INCHES CROSS-SECTION SQ. INCHES AL STEEL TOTAL AL INCHES mm RESISTANCE (5) GEOMETRIC INDUCTIVE CAPACITIVE OHMS/1000 FT MEAN REACTANCE REACTANCE DC AC AC AMPACITY RADIUS OHM/1000 FT MEGAOHM @ 20˚C @ 25˚C @ 75˚C 75˚C (6) FT (7) 1000 FT (7) O.D. 504.2 588.9 625.8 666.9 685.4 849.6 255.5 298.4 317.1 337.9 347.3 430.5 22x0.1514 22x0.1636 48x0.1141 24x0.1667 22x0.1765 45x0.1374 7x0.0841 7x0.0909 7x0.0886 7x0.1110 7x0.0980 7x0.0917 0.4349 0.5079 0.5347 0.5916 0.5911 0.7136 0.3961 0.4625 0.4916 0.5238 0.5383 0.6673 0.858 0.927 0.951 1.000 1.000 1.099 21.8 23.6 24.2 25.4 25.4 27.9 0.03441 0.02946 0.02778 0.02601 0.02531 0.02046 0.03531 0.03029 0.02860 0.02678 0.02610 0.02125 0.04221 0.03619 0.03415 0.03198 0.03115 0.02531 615 675 700 730 740 845 0.0284 0.0307 0.0317 0.0335 0.0331 0.0364 0.0818 0.0800 0.0793 0.0781 0.0783 0.0762 0.5218 0.5097 0.5056 0.4978 0.4978 0.4830 864.9 1028.7 1168.1 1277.5 1354.8 1361.0 1840.0 438.2 521.2 591.9 647.3 686.5 689.6 932.3 42x0.1435 42x0.1565 48x0.1560 42x0.1744 48x0.1680 42x0.1800 72x0.1598 7x0.0797 7x0.0870 7x0.1213 7x0.0969 7x0.1307 7x0.1000 7x0.1063 0.7142 0.8496 0.9983 1.0549 1.1580 1.1238 1.5068 0.6793 0.8080 0.9174 1.0033 1.0640 1.0688 1.4447 1.100 1.200 1.300 1.337 1.400 1.380 1.598 27.9 30.5 33.0 34.0 35.6 35.1 40.6 0.02008 0.01688 0.01488 0.01360 0.01283 0.01276 0.00945 0.02090 0.01771 0.01566 0.01447 0.01364 0.01366 0.01051 0.02488 0.02104 0.01858 0.01712 0.01614 0.01613 0.01229 850 945 1025 1080 1125 1120 1335 0.0361 0.0394 0.0433 0.0439 0.0466 0.0453 0.0525 0.0763 0.0743 0.0722 0.0718 0.0704 0.0711 0.0677 0.4829 0.4693 0.4567 0.4523 0.4451 0.4473 0.4243 (4)Code words shown denote ACSR with regular-strength Class A galvanized steel core (S1A). See the Options section to find the appropriate code word modifier designation for alternative design options. (5)Based on a conductivity of 61.0% IACS at 20˚C for aluminum and ignores the effects of the steel core. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by 3.281. (6)Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 32˚C ambient temperature, 1.98 ft/sec (0.6 m/s) crosswind (90˚ to conductor), 0.5 coefficient of emissivity, 0.5 coefficient of absorbtivity, 42˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 95.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (7)Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm). To convert the Geometric Mean Radius (GMR) to cm, divide the value by 0.03821. To convert inductive reactance to ohm/km, multiply the value by 3.281. To convert capacitive reactance to ohm/km, divide the value by 3.281. 89 Overhead Conductors Notes 90 Electric Utility Electric Utility Overhead Conductors TransPowr Compact (Smooth Body) ACSR Bare Overhead Conductor to CSA C49.2 Aluminum Conductor Steel-Reinforced Compact Stranded ® Product Construction: Complete Conductor: Smooth Body ACSR is a composite compactlay-stranded conductor. The conductors are manufactured in accordance with the requirements of the latest applicable issues of CSA C49.2. The steel strands form the central core of the conductor, around which is stranded a layer of aluminum 1350-H19 wires. The sizes listed on the following pages are common examples used in overhead lines. Metric (mm2) sizes are also available. The Canadian Smooth Body ACSR conductors are supplied in various tensile strength configurations, designated as Type 100, Type 150, and Type 200. For each conductor gauge size, the regular product is known as Type 100. Type 150 designates a conductor design with the same AWG size, but with 150% the rated strength of the Type 100. Type 200 follows accordingly, with twice the rated strength of the Type 100. Features and Benefits: ACSR conductors are recognized for their record of economy, dependability and favorable strength/ weight ratio. ACSR conductors combine the light weight and good conductivity of aluminum with the high tensile strength and ruggedness of steel. In line design, this can provide higher tensions, less sag, and longer span lengths than obtainable with most other types of overhead conductors. The steel strands are added as mechanical reinforcements. The cross-sections above illustrate some common strandings. The steel core wires are protected from corrosion by galvanizing. The standard Class A zinc coating is usually adequate for ordinary environments. For greater protection, Class B and C galvanized coatings may be specified. The product is available with conductor corrosionresistant inhibitor treatment applied to the central steel component. Options: •High-Conductivity aluminum (/HC) (62.2% IACS) •CSA high-strength Class A galvanized steel core (S2A) •CSA extra-high-strength Class A galvanized steel core (S3A) •ASTM regular-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA2 to ASTM B802) •ASTM high-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA3 to ASTM B803) •Aluminum-clad steel core (20SA) •Regular-strength Class C galvanized steel core (S1C) •Non-Specular surface finish (/NS) •CSA C68.8 for distribution utilities For more information, contact your General Cable sales representative or e-mail infoca@generalcable.com. Applications: Compact Aluminum Conductors, Steel-Reinforced (ACSR) are used for overhead distribution and transmission lines. The Type 100 compact ASCR conductor style is also used as the support conductor in the CSA Neutral Supported Service Entrance Cable as referenced in the CSA C22.2 No. 129 specification. 91 Overhead Conductors Electric Utility TransPowr Compact (Smooth Body) ACSR Bare Overhead Conductor to CSA C49.2 Aluminum Conductor Steel-Reinforced Compact Stranded ® ACSR, ALUMINUM CONDUCTOR, STEEL-REINFORCED, COMPACT-LAY-STRANDED (MECHANICAL PROPERTIES) STRANDING CROSS-SECTION APPROX. WEIGHT CONDUCTOR SIZE NO. X DIA. INCHES SQ. INCHES O.D. LB/1000 FT (2) CODE AWG OR WORD (1) kcmil mm2 AL STEEL TOTAL AL INCHES mm TOTAL AL STEEL PERCENT BY MASS RATED STRENGTH AL LB STEEL STANDARD PACKAGES (4) CONDUCTOR WT LENGTH kN TYPE (3) REEL DESIG. kg M Bass 6 13.3 6 1x0.0661 0.0240 0.0206 0.182 4.62 36.1 24.5 11.6 67.90 32.10 1160 5.16 100 Mullet 6 13.3 6 1x0.0937 0.0275 0.0206 0.193 4.90 47.7 24.5 23.3 51.29 48.71 1720 7.65 150 Herring 6 13.3 6 1x0.1182 0.0316 0.0206 0.208 5.28 61.5 24.5 37.0 39.82 60.18 2400 10.7 200 Pike 4 21.1 6 1x0.0834 0.0382 0.0328 0.228 5.79 57.4 38.9 18.4 67.89 32.11 1830 8.14 100 Pollock 4 21.1 6 1x0.1182 0.0438 0.0328 0.243 6.17 75.9 38.9 37.0 51.28 48.72 2720 12.1 150 Flounder 4 21.1 6 1x0.1490 0.0502 0.0328 0.264 6.71 97.7 38.9 58.8 39.84 60.16 3690 16.4 200 Carp 2 33.6 6 1x0.1052 0.0608 0.0522 0.289 7.34 91.2 61.9 29.3 67.87 32.13 2800 12.5 100 Haddock 2 33.6 6 1x0.1490 0.0696 0.0522 0.308 7.82 120.7 61.9 58.8 51.29 48.71 4140 18.4 150 Pickerel 2 33.6 6 1x0.1878 0.0799 0.0522 0.331 8.41 155.3 61.9 93.4 39.86 60.14 5780 25.7 200 Shad 1 42.4 6 1x0.1182 0.0767 0.0657 0.325 8.26 115.1 78.1 37.0 67.85 32.15 3480 15.5 100 Lamprey 1 42.4 6 1x0.1672 0.0877 0.0657 0.346 8.79 152.1 78.1 74.0 51.33 48.67 5170 23.0 150 Sole 1/0 53.5 6 1x0.1327 0.0968 0.0830 0.364 9.25 145.1 98.5 46.6 67.87 32.13 4250 18.9 100 Sculpin 1/0 53.5 6 1x0.1878 0.1107 0.0830 0.388 9.86 191.9 98.5 93.4 51.33 48.67 6470 28.8 150 Hake 2/0 67.4 6 1x0.1490 0.1219 0.1045 0.410 10.4 183.0 124.2 58.8 67.86 32.14 5280 23.5 100 Cusk 3/0 85 6 1x0.1672 0.1537 0.1317 0.460 11.7 230.6 156.5 74.0 67.89 32.11 6660 29.6 100 Scup 4/0 107.2 6 1x0.1878 0.1939 0.1662 0.516 13.1 290.8 197.4 93.4 67.88 32.12 8400 37.4 100 RW 40.18 COIL NR 36.22 COIL RW 48.24 NR 36.22 COIL RW 48.24 NR 36.22 COIL RW 48.24 NR 36.22 COIL RW 48.24 RW 40.18 COIL RW 50.32 NR 36.22 COIL RW 60.32 NR 36.22 COIL RW 60.32 RW 40.18 COIL RW 50.32 NR 36.22 COIL RW 60.32 NR 36.22 COIL RW 50.32 NR 36.22 COIL RW 60.32 NR 36.22 COIL RW 50.32 NR 36.22 COIL RW 50.32 NR 36.22 COIL RW 50.32 NR 36.22 COIL 565 90 371 90 1025 512 90 604 302 90 799 399 90 1028 514 90 1205 301 90 1595 399 90 2052 513 90 1205 301 90 1592 398 90 1203 301 90 1591 398 90 1205 301 90 1203 301 90 1203 301 90 10509 1675 5230 1268 11196 5596 983 7069 3535 1054 7069 3535 797 7069 3535 619 8877 2219 663 8877 2219 501 8877 2219 389 7033 1758 525 7033 1758 398 5570 1392 417 5570 1392 315 4424 1106 330 3505 876 262 2780 695 208 (1) Code words shown denote compact ACSR with regular-strength Class A galvanized steel core (S1A). See the Options section to find the appropriate code word modifier designation for alternative design options. (2)Due to rounding, total values may be slightly greater or slightly less than the sum of the component values. (3)A Type 150 construction has 150% of the rated strength of a Type 100 construction, and a Type 200 construction has 200% of the rated strength of a Type 100 construction. (4)Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 92 Electric Utility Overhead Conductors TransPowr Compact (Smooth Body) ACSR Bare Overhead Conductor to CSA C49.2 Aluminum Conductor Steel-Reinforced Compact Stranded ® ACSR, ALUMINUM CONDUCTOR, STEEL-REINFORCED, COMPACT-LAY-STRANDED (ELECTRICAL PROPERTIES) CODE WORD (1) CONDUCTOR SIZE AWG OR kcmil mm2 STRANDING NO. X DIA. INCHES AL STEEL CROSS-SECTION SQ. INCHES TOTAL AL INCHES mm RESISTANCE (5) GEOMETRIC INDUCTIVE CAPACITIVE OHMS/1000 FT MEAN REACTANCE REACTANCE DC AC AC AMPACITY RADIUS OHM/1000 FT MEGAOHM @ 20˚C @ 25˚C @ 75˚C 75˚C (6) FT (7) 1000 FT (7) O.D. Bass 6 13.3 6 1x0.0661 0.0240 0.0206 0.182 4.62 0.657 0.671 0.803 90 0.0059 0.1181 0.7651 Mullet 6 13.3 6 1x0.0937 0.0275 0.0206 0.193 4.90 0.657 0.671 0.803 90 0.0065 0.1158 0.7552 Herring 6 13.3 6 1x0.1182 0.0316 0.0206 0.208 5.28 0.657 0.671 0.803 95 0.0071 0.1138 0.7440 Pike 4 21.1 6 1x0.0834 0.0382 0.0328 0.228 5.79 0.4144 0.4228 0.5063 120 0.0074 0.1128 0.7292 Pollock 4 21.1 6 1x0.1182 0.0438 0.0328 0.243 6.17 0.414 0.423 0.506 120 0.0082 0.1105 0.7193 Flounder 4 21.1 6 1x0.1490 0.0502 0.0328 0.264 6.71 0.414 0.423 0.506 125 0.0090 0.1083 0.7063 Carp 2 33.6 6 1x0.1052 0.0608 0.0522 0.289 7.34 0.260 0.266 0.318 160 0.0094 0.1074 0.6922 Haddock 2 33.6 6 1x0.1490 0.0696 0.0522 0.308 7.82 0.260 0.265 0.318 160 0.0103 0.1051 0.6824 Pickerel 2 33.6 6 1x0.1878 0.0799 0.0522 0.331 8.41 0.260 0.265 0.318 160 0.0113 0.1031 0.6710 Shad 1 42.4 6 1x0.1182 0.0767 0.0657 0.325 8.26 0.206 0.210 0.252 185 0.0105 0.1047 0.6738 Lamprey 1 42.4 6 1x0.1672 0.0877 0.0657 0.346 8.79 0.206 0.210 0.252 185 0.0116 0.1024 0.6641 Sole 1/0 53.5 6 1x0.1327 0.0968 0.0830 0.364 9.25 0.163 0.167 0.200 210 0.0118 0.1021 0.6560 Sculpin 1/0 53.5 6 1x0.1878 0.1107 0.0830 0.388 9.86 0.163 0.167 0.200 210 0.0130 0.0998 0.6460 Hake 2/0 67.4 6 1x0.1490 0.1219 0.1045 0.410 10.4 0.130 0.132 0.159 245 0.0133 0.0994 0.6376 Cusk 3/0 85 6 1x0.1672 0.1537 0.1317 0.460 11.7 0.103 0.105 0.126 280 0.0149 0.0967 0.6192 Scup 4/0 107.2 6 1x0.1878 0.1939 0.1662 0.516 13.1 0.082 0.083 0.100 320 0.0167 0.0941 0.6015 (1) Code words shown denote ACSR with regular-strength Class A galvanized steel core (S1A). See the Options section to find the appropriate code word modifier designation for alternative design options. (5)Based on a conductivity of 61.0% IACS at 20˚C for aluminum and ignores the effects of the steel core. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by 3.281. (6)Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 32˚C ambient temperature, 1.98 ft/sec (0.6 m/s) crosswind (90˚ to conductor), 0.5 coefficient of emissivity, 0.5 coefficient of absorbtivity, 42˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 95.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (7)Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm). To convert the Geometric Mean Radius (GMR) to cm, divide the value by 0.03821. To convert inductive reactance to ohm/km, multiply the value by 3.281. To convert capacitive reactance to ohm/km, divide the value by 3.281. 93 Overhead Conductors Notes 94 Electric Utility Electric Utility Overhead Conductors TransPowr ACSR/TW Bare Overhead Conductor ® Trapezoidal Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded 18/7 20/7 36/19 21/7 38/19 Product Construction: Complete Conductor: TransPowr® ACSR/TW is a trapezoidal aluminum conductor steel-reinforced concentric-lay-stranded conductor. The aluminum strands are trapezoidal in shape. The wedge-shaped aluminum strands enable a more compact alignment of the aluminum wires. Conductor designs that maintain the same circular mil crosssectional area of aluminum as a conventional round conductor result in a TW conductor that is 10 to 15 percent smaller in overall diameter. Conductor designs that maintain the same overall diameter as a conventional round conductor result in a TW conductor that has 20 to 25 percent more aluminum cross-sectional area packed in. The ACSR/TW conductors are manufactured in accordance with the requirements of the latest issue of ASTM B779. The steel strands form the central core of the conductor, around which is stranded two, three or four layers of aluminum 1350-H19 wires. The steel core may consist of a concentric stranded cable of 7, 19 or more wires. Numerous combinations of aluminum and steel strands and layers are possible. The sizes and constructions listed on the following pages are common examples used in overhead lines. For ACSR/TW conductors, the standard Class A galvanized coating is usually adequate for ordinary environments. 22/7 39/19 36/7 64/19 Features and Benefits: TransPowr® ACSR/TW has a continuous operating temperature rating of 75°C. ACSR and ACSR/TW conductors have an “industry-accepted” shortduration maximum operating temperature rating of 100°C. Operation of the conductor at elevated temperatures may increase the conductor sag properties and lower the rated tensile strength of the conductor. TransPowr® ACSR/TW conductors are recognized for their record of economy, dependability and favorable strength-to-weight ratio. ACSR/TW conductors constructed of equivalent aluminum circular mil cross-sectional area provide a conductor that is smaller in overall diameter than the equivalent conventional round wire ACSR conductor. The reduced conductor diameter is advantageous in reducing the effects of ice and wind loading on the conductor. ACSR/TW conductors constructed to equivalent overall diameter enable a greater circular mil cross-sectional area of aluminum within the conductor, allowing a significant increase in conductor current-carrying capacity. Applications: Trapezoidal Aluminum Conductors Steel-Reinforced (ACSR/TW) are used for overhead transmission lines. Electrical Parameters: The electrical parameters for the trapezoidal ACSR equivalent circular mil area and equivalent overall diameter conductors may be found in the last table of this section. Options: • High-Conductivity aluminum (/HC) (62.2% IACS) • Regular-strength Class C galvanized steel core (/GC2) • High-strength Class A galvanized steel core (/GA3) • Extra-high-strength Class A galvanized steel core (/GA4) • Ultra-high-strength Class A galvanized steel core (/GA5) • Regular-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA2) • High-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA3) • Extra-high-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA4) • Ultra-high-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA5) • Aluminum-clad steel core (/AW) • Non-Specular surface finish (/NS) At the present time, CAN/CSA C61089 does not recognize TW conductor designs. The information provided on the following pages is from our US catalog. For other conductor sizes, designs and/or specific installation requirements not shown in the tables, contact your General Cable sales representative or e-mail infoca@generalcable.com. 95 Overhead Conductors Electric Utility TransPowr ACSR/TW Bare Overhead Conductor ® Trapezoidal Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded ACSR/TW (MECHANICAL PROPERTIES) – REDUCED DIAMETER CONDUCTORS SIZED TO HAVE EQUIVALENT CIRCULAR MIL AREA TO REGULAR ACSR APPROX. WEIGHT PERCENT RATED STRENGTH STEEL STEEL CROSS-SECTION SQ. INCHES LB/1000 FT (2) BY MASS LBS STANDARD PACKAGES (3) SIZE NO. EQUIVALENT CORE CORE CODE AWG OR AL FILL AL DIA. NO. X DIA. O.D. O.D. GA3 GA5 REEL WEIGHT LENGTH WORD (1) kcmil TYPE WIRES FACTOR INCHES INCHES INCHES TOTAL AL INCHES TOTAL AL STEEL AL STEEL GA2 (HS) (UHS) DESIGNATION LBS FEET Oriole/ ACSR/TW 336.4 23 17 88.7 0.1407 7x0.1059 0.3177 0.3258 0.2642 0.69 Flicker/ ACSR/TW 477.0 13 18 91.3 0.1628 7x0.0940 0.2820 0.4234 0.3748 0.78 Hawk/ ACSR/TW 477.0 16 18 91.3 0.1628 7x0.1053 0.3159 0.4355 0.3745 0.79 Hen/ ACSR/TW 477.0 23 16 88.7 0.1727 7x0.1261 0.3783 0.4620 0.3746 0.83 Parakeet/ ACSR/TW 556.5 13 18 92.0 0.1758 7x0.1015 0.3045 0.4938 0.4372 0.84 Dove/ ACSR/TW 556.5 16 20 91.8 0.1668 7x0.1138 0.3414 0.5083 0.4371 0.85 Rook/ ACSR/TW 636.0 13 18 92.6 0.1880 7x0.1085 0.3255 0.5641 0.4994 0.89 Grosbeak/ ACSR/TW 636.0 16 20 92.0 0.1783 7x0.1216 0.3648 0.5809 0.4996 0.91 Tern/ ACSR/TW 795.0 7 17 93.5 0.2163 7x0.0888 0.2664 0.6680 0.6247 0.96 Puffin/ ACSR/TW 795.0 11 21 93.5 0.1945 7x0.1108 0.3324 0.6916 0.6241 0.98 Condor/ ACSR/TW 795.0 13 21 93.0 0.1945 7x0.1213 0.3639 0.7051 0.6242 0.99 Drake/ ACSR/TW 795.0 16 20 93.1 0.1993 7x0.1360 0.4080 0.7259 0.6242 1.01 Mallard/ ACSR/TW 795.0 23 22 93.0 0.1901 19x0.0977 0.4885 0.7668 0.6244 1.046 Phoenix/ ACSR/TW 954.0 5 30 92.9 0.1784 7x0.0837 0.2511 0.7882 0.7497 1.04 Rail/ ACSR/TW 954.0 7 33 92.2 0.1700 7x0.0971 0.2913 0.8011 0.7493 1.06 Cardinal/ ACSR/TW 954.0 13 21 93.9 0.2131 7x0.1329 0.3987 0.8463 0.7492 1.08 Snowbird/ ACSR/TW 1033.5 5 30 92.5 0.1856 7x0.0871 0.2613 0.8532 0.8115 1.09 Ortolan/ ACSR/TW 1033.5 7 33 92.3 0.1769 7x0.1010 0.3030 0.8673 0.8112 1.10 Curlew/ ACSR/TW 1033.5 13 21 93.7 0.2219 7x0.1383 0.4149 0.9170 0.8118 1.13 Avocet/ ACSR/TW 1113.0 5 30 93.0 0.1926 7x0.0904 0.2712 0.9186 0.8737 1.13 Bluejay/ ACSR/TW 1113.0 7 33 92.7 0.1837 7x0.1049 0.3147 0.9351 0.8746 1.14 Finch/ ACSR/TW 1113.0 13 39 91.9 0.1689 19x0.0862 0.4310 0.9845 0.8737 1.18 Oxbird/ ACSR/TW 1192.5 5 30 93.2 0.1993 7x0.0936 0.2808 0.9843 0.9361 1.17 Bunting/ ACSR/TW 1192.5 7 33 93.0 0.1901 7x0.1086 0.3258 1.0016 0.9368 1.18 526 318 209 60.34 39.66 17100 18300 19500 RMT 84.36 NR 60.28 612 448 164 73.14 26.86 17200 18100 19000 RM 84.36 NR 60.28 655 448 206 68.47 31.53 19400 20500 21700 RMT 84.36 NR 60.28 746 450 296 60.34 39.66 23600 25300 27000 RM 68.38 NR 60.28 714 522 192 73.15 26.85 20000 21100 22200 RM 68.38 NR 60.28 764 523 241 68.45 31.55 22600 24000 25300 RMT 84.36 NR 60.28 816 597 219 73.15 26.85 22900 24100 25400 RM 68.38 NR 60.28 873 598 275 68.47 31.53 25400 27000 28600 RMT 84.36 NR 66.28 892 745 147 83.54 16.46 21900 22700 23500 RM 68.38 NR 60.28 974 746 229 76.55 23.45 26200 27500 28800 RMT 84.36 NR 60.28 1020 746 274 73.15 26.85 28200 29800 31300 RMT 84.36 NR 60.28 1091 747 344 68.45 31.55 31800 33800 35700 RMT 84.36 NR 60.28 1234 751 483 60.84 39.16 38700 41400 44000 RMT 84.36 NR 60.28 1028 898 130 87.32 12.68 23800 24500 25200 RMT 84.45 NR 66.28 1074 899 175 83.66 16.34 25900 26900 27900 RMT 84.45 RM 68.38 1224 895 329 73.15 26.85 33500 35400 37200 RMT 84.36 NR 60.28 1114 972 141 87.32 12.68 25700 26500 27300 RMT 84.45 RM 66.32 1163 973 190 83.68 16.32 28100 29100 30200 RMT 84.45 RM 68.38 1326 970 356 73.15 26.85 36300 38300 40300 RMT 84.36 NR 60.28 1199 1047 152 87.32 12.68 27500 28300 29200 RMT 84.36 RM 66.32 1253 1048 205 83.66 16.34 30300 31400 32600 RMT 84.45 RM 68.38 1427 1051 376 73.64 26.36 39100 41200 43200 RMT 90.45 RMT 84.36 1285 1122 163 87.31 12.69 29400 30400 31300 RMT 84.36 RM 66.32 1343 1123 220 83.65 16.35 32400 33700 34900 RMT 84.45 RM 68.38 7743 4276 6765 4506 7233 3620 7288 3648 6770 3385 8036 4018 6766 3387 8030 4015 5601 2801 7542 3771 7896 3948 8042 4016 9946 3973 9448 4729 10848 5424 7896 3942 9455 4722 10842 5421 7890 3952 9439 4726 10840 5426 14556 7278 9446 4717 10849 5425 (1) Code words shown denote ACSR/TW with regular-strength Class A galvanized steel core (/GA2). See the Options section to find the appropriate code word modifier designation for alternative design options. (2) Due to rounding, total values may not exactly equal the sum of the component values. (3) Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 96 14720 8130 11050 7360 11050 5530 9770 4890 9480 4740 10520 5260 8290 4150 9200 4600 6280 3140 7740 3870 7740 3870 7370 3680 8060 3220 9190 4600 10100 5050 6450 3220 8490 4240 9320 4660 5950 2980 7870 3940 8650 4330 10200 5100 7350 3670 8080 4040 Electric Utility Overhead Conductors TransPowr ACSR/TW Bare Overhead Conductor ® Trapezoidal Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded ACSR/TW (ELECTRICAL PROPERTIES) – REDUCED DIAMETER CONDUCTORS SIZED TO HAVE EQUIVALENT CIRCULAR MIL AREA TO REGULAR ACSR CODE WORD (1) CROSS-SECTION RESISTANCE (4) GEOMETRIC INDUCTIVE SQ. INCHES OHMS/1000 FT SIZE EQUIVALENT STEEL CORE STEEL MEAN REACTANCE AWG OR NO. AL FILL AL DIA. NO. X DIA. CORE O.D. O.D. DC AC AC AMPACITY RADIUS OHM/1000 FT kcmil TYPE WIRES FACTOR INCHES INCHES INCHES TOTAL AL INCHES @ 20˚C @ 25˚C @ 75˚C 75˚C (5) FT (6) CAPACITIVE REACTANCE MEGAOHM 1000 FT (6) Oriole/ ACSR/TW 336.4 23 17 88.7 0.1407 7x0.1059 0.3177 0.3258 0.2642 0.69 0.0502 0.0513 0.0613 525 0.0236 0.0861 0.5553 Flicker/ ACSR/TW 477.0 13 18 91.3 0.1628 7x0.0940 0.2820 0.4234 0.3748 0.78 0.0357 0.0366 0.0437 640 0.0259 0.0839 0.5375 Hawk/ ACSR/TW 477.0 16 18 91.3 0.1628 7x0.1053 0.3159 0.4355 0.3745 0.79 0.0356 0.0364 0.0435 645 0.0266 0.0834 0.5349 Hen/ ACSR/TW 477.0 23 16 88.7 0.1727 7x0.1261 0.3783 0.4620 0.3746 0.83 0.0354 0.0362 0.0433 655 0.0280 0.0822 0.5278 Parakeet/ ACSR/TW 556.5 13 18 92.0 0.1758 7x0.1015 0.3045 0.4938 0.4372 0.84 0.0306 0.0314 0.0375 705 0.0279 0.0822 0.5259 Dove/ ACSR/TW 556.5 16 20 91.8 0.1668 7x0.1138 0.3414 0.5083 0.4371 0.85 0.0305 0.0313 0.0374 710 0.0287 0.0816 0.5232 Rook/ ACSR/TW 636.0 13 18 92.6 0.1880 7x0.1085 0.3255 0.5641 0.4994 0.89 0.0268 0.0275 0.0329 765 0.0298 0.0808 0.5159 Grosbeak/ ACSR/TW 636.0 16 20 92.0 0.1783 7x0.1216 0.3648 0.5809 0.4996 0.91 0.0267 0.0274 0.0327 770 0.0307 0.0801 0.5129 Tern/ ACSR/TW 795.0 7 17 93.5 0.2163 7x0.0888 0.2664 0.6680 0.6247 0.96 0.0215 0.0223 0.0266 870 0.0315 0.0795 0.5042 Puffin/ ACSR/TW 795.0 11 21 93.5 0.1945 7x0.1108 0.3324 0.6916 0.6241 0.98 0.0215 0.0222 0.0264 875 0.0327 0.0786 0.5009 Condor/ ACSR/TW 795.0 13 21 93.0 0.1945 7x0.1213 0.3639 0.7051 0.6242 0.99 0.0214 0.0221 0.0264 880 0.0333 0.0782 0.4987 Drake/ ACSR/TW 795.0 16 20 93.1 0.1993 7x0.1360 0.4080 0.7259 0.6242 1.01 0.0213 0.0220 0.0262 885 0.0342 0.0776 0.4962 Mallard/ ACSR/TW 795.0 23 22 93.0 0.1901 19x0.0977 0.4885 0.7668 0.6244 1.046 0.0213 0.0219 0.0261 895 0.0360 0.0764 0.4907 Phoenix/ ACSR/TW 954.0 5 30 92.9 0.1784 7x0.0837 0.2511 0.7882 0.7497 1.04 0.0181 0.0190 0.0233 950 0.0343 0.0775 0.4910 Rail/ ACSR/TW 954.0 7 33 92.2 0.1700 7x0.0971 0.2913 0.8011 0.7493 1.06 0.0180 0.0189 0.0232 955 0.0350 0.0771 0.4889 Cardinal/ ACSR/TW 954.0 13 21 93.9 0.2131 7x0.1329 0.3987 0.8463 0.7492 1.08 0.0178 0.0185 0.0221 985 0.0364 0.0762 0.4851 Snowbird/ ACSR/TW 1033.5 5 30 92.5 0.1856 7x0.0871 0.2613 0.8532 0.8115 1.09 0.0167 0.0176 0.0215 995 0.0357 0.0766 0.4844 Ortolan/ ACSR/TW 1033.5 7 33 92.3 0.1769 7x0.1010 0.3030 0.8673 0.8112 1.10 0.0167 0.0175 0.0215 1000 0.0364 0.0762 0.4827 Curlew/ ACSR/TW 1033.5 13 21 93.7 0.2219 7x0.1383 0.4149 0.9170 0.8118 1.13 0.0165 0.0171 0.0204 1035 0.0379 0.0752 0.4787 Avocet/ ACSR/TW 1113.0 5 30 93.0 0.1926 7x0.0904 0.2712 0.9186 0.8737 1.13 0.0155 0.0164 0.0200 1045 0.0370 0.0758 0.4790 Bluejay/ ACSR/TW 1113.0 7 33 92.7 0.1837 7x0.1049 0.3147 0.9351 0.8746 1.14 0.0155 0.0163 0.0200 1050 0.0377 0.0753 0.4772 Finch/ ACSR/TW 1113.0 13 39 91.9 0.1689 19x0.0862 0.4310 0.9845 0.8737 1.18 0.0154 0.0162 0.0198 1065 0.0399 0.0740 0.4716 Oxbird/ ACSR/TW 1192.5 5 30 93.2 0.1993 7x0.0936 0.2808 0.9843 0.9361 1.17 0.0145 0.0154 0.0188 1090 0.0382 0.0750 0.4738 Bunting/ ACSR/TW 1192.5 7 33 93.0 0.1901 7x0.1086 0.3258 1.0016 0.9368 1.18 0.0144 0.0153 0.0187 1095 0.0390 0.0746 0.4720 (1) Code words shown denote ACSR/TW with regular-strength Class A galvanized steel core (/GA2). See the Options section to find the appropriate code word modifier designation for alternative design options. (4) Based on a conductivity of 61.2% (minimum lot average) IACS at 20˚C for aluminum and 8% IACS at 20˚C for the steel core. AC resistance for single-layer and three-layer designs approximates the effects of core magnetization. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by 3.281. (5) Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 25˚C ambient temperature, 2 ft/sec crosswind (90˚ to conductor), 0.5 coefficient of emissivity, 0.5 coefficient of absorbtivity, 30˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 96.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (6) Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm). To convert the Geometric Mean Radius (GMR) to cm, divide the value by 0.03821. To convert inductive reactance to ohm/km, multiply the value by 3.281. To convert capacitive reactance to ohm/km, divide the value by 3.281. 97 Overhead Conductors Electric Utility TransPowr ACSR/TW Bare Overhead Conductor ® Trapezoidal Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded ACSR/TW (MECHANICAL PROPERTIES) – REDUCED DIAMETER CONDUCTORS SIZED TO HAVE EQUIVALENT CIRCULAR MIL AREA TO REGULAR ACSR APPROX. WEIGHT PERCENT RATED STRENGTH STEEL STEEL CROSS-SECTION SQ. INCHES LB/1000 FT (2) BY MASS LBS STANDARD PACKAGES (3) SIZE NO. EQUIVALENT CORE CORE CODE AWG OR AL FILL AL DIA. NO. X DIA. O.D. O.D. GA3 GA5 REEL WEIGHT LENGTH WORD (1) kcmil TYPE WIRES FACTOR INCHES INCHES INCHES TOTAL AL INCHES TOTAL AL STEEL AL STEEL GA2 (HS) (UHS) DESIGNATION LBS FEET Grackle/ ACSR/TW 1192.5 13 39 92.3 Scissortail/ 1272.0 ACSR/TW 5 30 93.6 Bittern/ ACSR/TW 1272.0 7 33 93.3 Pheasant/ ACSR/TW 1272.0 13 39 93.0 Dipper/ ACSR/TW 1351.5 7 33 93.5 Martin/ ACSR/TW 1351.5 13 39 93.0 Bobolink/ ACSR/TW 1431.0 7 33 93.0 Plover/ ACSR/TW 1431.0 13 39 93.0 Lapwing/ ACSR/TW 1590.0 7 36 93.0 Falcon/ ACSR/TW 1590.0 13 42 93.5 Chukar/ ACSR/TW 1780.0 8 38 93.5 Bluebird/ ACSR/TW 2156.0 8 64 91.0 0.1749 19x0.0892 0.4460 1.0556 0.9369 1.22 1529 1126 403 73.65 26.35 41900 44100 46300 RMT 90.45 RM 72.36 0.2059 7x0.0967 0.2901 1.0508 0.9994 1.20 1371 1197 174 87.30 12.70 31400 32400 33400 RMT 84.36 RM 66.32 0.1964 7x0.1121 0.3363 1.0685 0.9994 1.22 1432 1198 234 83.67 16.33 34600 35900 37200 RMT 84.45 RM 68.38 0.1806 19x0.0921 0.4605 1.1252 0.9987 1.26 1630 1201 429 73.66 26.34 44100 46400 48800 RMT 90.45 RM 72.36 0.2024 7x0.1155 0.3465 1.1350 1.0616 1.25 1521 1273 248 83.68 16.32 36700 38100 39500 RMT 84.45 RM 68.38 0.1861 19x0.0949 0.4745 1.1954 1.0610 1.30 1732 1276 456 73.68 26.32 46800 49300 51800 RMT 90.45 RM 72.36 0.2083 7x0.1189 0.3567 1.2020 1.1243 1.29 1611 1348 263 83.67 16.33 38900 40400 41900 RMT 84.45 RM 68.38 0.1916 19x0.0977 0.4885 1.2666 1.1242 1.33 1834 1351 483 73.66 26.34 49600 52200 54900 RMT 90.45 RM 72.36 0.2102 7x0.1253 0.3759 1.3351 1.2488 1.36 1790 1498 292 83.67 16.33 42200 43900 45500 RMT 84.45 RM 68.38 0.1946 19x0.1030 0.5150 1.4066 1.2483 1.40 2038 1501 537 73.65 26.35 55100 58000 61000 RMT 90.45 RMT 84.36 0.2164 19x0.0874 0.4370 1.5122 1.3982 1.45 2061 1674 387 81.24 18.76 50700 52800 54900 RMT 90.45 RM 68.38 0.1835 19x0.0961 0.4805 1.8312 1.6934 1.61 2512 2045 467 81.39 18.61 61100 63700 66200 RMT 96.60 RMT 84.45 14569 7277 9460 4730 10854 5427 14559 7272 10847 5416 14548 7274 10842 5413 14565 7282 11831 5906 15674 7827 12859 6430 21629 10802 9530 4760 6900 3450 7580 3790 8930 4460 7130 3560 8400 4200 6730 3360 7940 3970 6610 3300 7690 3840 6240 3120 8610 4300 ACSR/TW (MECHANICAL PROPERTIES) – EQUIVALENT DIAMETER CONDUCTORS SIZED TO HAVE EQUIVALENT DIAMETER TO REGULAR ACSR APPROX. WEIGHT PERCENT RATED STRENGTH STEEL STEEL CROSS-SECTION SQ. INCHES LB/1000 FT (2) BY MASS LBS STANDARD PACKAGES (3) SIZE NO. EQUIVALENT CORE CORE CODE AWG OR AL FILL AL DIA. NO. X DIA. O.D. O.D. GA3 GA5 REEL WEIGHT LENGTH WORD (1) kcmil TYPE WIRES FACTOR INCHES INCHES INCHES TOTAL AL INCHES TOTAL AL STEEL AL STEEL GA2 (HS) (UHS) DESIGNATION LBS FEET Calument/ ACSR/TW 565.3 16 20 91.5 0.1681 7x0.1146 0.3438 0.5161 0.4438 0.86 Mohawk/ ACSR/TW 571.7 13 18 92.2 0.1782 7x0.1030 0.3090 0.5072 0.4489 0.85 Oswego/ ACSR/TW 664.8 16 20 92.3 0.1823 7x0.1244 0.3732 0.6073 0.5222 0.93 Mystic/ ACSR/TW 666.6 13 20 92.3 0.1826 7x0.1111 0.3333 0.5915 0.5236 0.91 Wabash/ ACSR/TW 762.8 16 20 92.9 0.1953 7x0.1331 0.3993 0.6963 0.5989 0.99 Maumee/ ACSR/TW 768.2 13 20 93.0 0.1960 7x0.1195 0.3585 0.6817 0.6032 0.98 Kettle/ ACSR/TW 957.2 7 33 92.2 0.1703 7x0.0973 0.2919 0.8038 0.7518 1.06 Suwanee/ ACSR/TW 959.6 16 22 93.4 0.2089 7x0.1493 0.4479 0.8764 0.7539 1.11 Columbia/ ACSR/TW 966.2 13 21 93.6 0.2145 7x0.1338 0.4014 0.8576 0.7591 1.09 776 531 244 68.48 31.52 22900 24300 25700 RMT 84.36 NR 60.28 734 537 197 73.10 26.90 20600 21700 22800 RM 66.38 NR 60.28 913 625 288 68.44 31.56 26600 28200 29900 RMT 84.36 NR 60.28 855 626 230 73.14 26.86 24000 25300 26600 RMT 84.36 NR 60.28 1046 717 330 68.49 31.51 30500 32400 34200 RMT 84.36 NR 60.28 987 721 266 73.07 26.93 27700 29200 30700 RMT 84.36 NR 60.28 1078 902 176 83.65 16.35 26000 27000 28000 RMT 84.45 RM 68.38 1317 902 415 68.49 31.51 37200 40100 42500 RMT 84.36 RM 66.32 1240 907 333 73.13 26.87 34000 35800 37700 RMT 84.36 RM 66.32 8027 4010 6768 3384 8032 4016 7519 3755 8026 4008 7520 3760 10843 5421 8834 4410 7899 3943 (1) Code words shown denote ACSR/TW with regular-strength Class A galvanized steel core (/GA2). See the Options section to find the appropriate code word modifier designation for alternative design options. (2) Due to rounding, total values may not exactly equal the sum of the component values. (3) Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 98 10350 5170 9220 4610 8800 4400 8790 4390 7670 3830 7620 3810 10060 5030 6710 3350 6370 3180 Electric Utility Overhead Conductors TransPowr ACSR/TW Bare Overhead Conductor ® Trapezoidal Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded ACSR/TW (ELECTRICAL PROPERTIES) – REDUCED DIAMETER CONDUCTORS SIZED TO HAVE EQUIVALENT CIRCULAR MIL AREA TO REGULAR ACSR CODE WORD (1) CROSS-SECTION RESISTANCE (4) GEOMETRIC INDUCTIVE SQ. INCHES OHMS/1000 FT SIZE EQUIVALENT STEEL CORE STEEL MEAN REACTANCE AWG OR NO. AL FILL AL DIA. NO. X DIA. CORE O.D. O.D. DC AC AC AMPACITY RADIUS OHM/1000 FT kcmil TYPE WIRES FACTOR INCHES INCHES INCHES TOTAL AL INCHES @ 20˚C @ 25˚C @ 75˚C 75˚C (5) FT (6) CAPACITIVE REACTANCE MEGAOHM 1000 FT (6) Grackle/ ACSR/TW 1192.5 13 39 92.3 0.1749 19x0.0892 0.4460 1.0556 0.9369 1.22 0.0144 0.0151 0.0185 1110 0.0412 0.0733 0.4665 Scissortail/ ACSR/TW 1272.0 5 30 93.6 0.2059 7x0.0967 0.2901 1.0508 0.9994 1.20 0.0135 0.0145 0.0176 1130 0.0394 0.0743 0.4690 Bittern/ ACSR/TW 1272.0 7 33 93.3 0.1964 7x0.1121 0.3363 1.0685 0.9994 1.22 0.0135 0.0144 0.0176 1135 0.0402 0.0739 0.4672 Pheasant/ ACSR/TW 1272.0 13 39 93.0 0.1806 19x0.0921 0.4605 1.1252 0.9987 1.26 0.0135 0.0142 0.0174 1155 0.0424 0.0726 0.4619 Dipper/ ACSR/TW 1351.5 7 33 93.5 0.2024 7x0.1155 0.3465 1.1350 1.0616 1.25 0.0127 0.0136 0.0166 1180 0.0414 0.0732 0.4626 Martin/ ACSR/TW 1351.5 13 39 93.0 0.1861 19x0.0949 0.4745 1.1954 1.0610 1.30 0.0127 0.0135 0.0164 1195 0.0437 0.0719 0.4572 Bobolink/ ACSR/TW 1431.0 7 33 93.0 0.2083 7x0.1189 0.3567 1.2020 1.1243 1.29 0.0120 0.0129 0.0157 1220 0.0427 0.0725 0.4578 Plover/ ACSR/TW 1431.0 13 39 93.0 0.1916 19x0.0977 0.4885 1.2666 1.1242 1.33 0.0120 0.0128 0.0155 1240 0.0450 0.0713 0.4527 Lapwing/ ACSR/TW 1590.0 7 36 93.0 0.2102 7x0.1253 0.3759 1.3351 1.2488 1.36 0.0108 0.0118 0.0142 1300 0.0450 0.0712 0.4495 Falcon/ ACSR/TW 1590.0 13 42 93.5 0.1946 19x0.1030 0.5150 1.4066 1.2483 1.40 0.0108 0.0116 0.0140 1320 0.0474 0.0701 0.4448 Chukar/ ACSR/TW 1780.0 8 38 93.5 0.2164 19x0.0874 0.4370 1.5122 1.3982 1.45 0.00964 0.0106 0.0127 1400 0.0482 0.0697 0.4398 Bluebird/ ACSR/TW 2156.0 8 64 91.0 0.1835 19x0.0961 0.4805 1.8312 1.6934 1.61 0.00802 0.00900 0.0105 1585 0.0538 0.0672 0.4229 ACSR/TW (ELECTRICAL PROPERTIES) – EQUIVALENT DIAMETER CONDUCTORS SIZED TO HAVE EQUIVALENT DIAMETER TO REGULAR ACSR CODE WORD (1) CROSS-SECTION RESISTANCE (4) GEOMETRIC INDUCTIVE SQ. INCHES OHMS/1000 FT SIZE EQUIVALENT STEEL CORE STEEL MEAN REACTANCE AWG OR NO. AL FILL AL DIA. NO. X DIA. CORE O.D. O.D. DC AC AC AMPACITY RADIUS OHM/1000 FT kcmil TYPE WIRES FACTOR INCHES INCHES INCHES TOTAL AL INCHES @ 20˚C @ 25˚C @ 75˚C 75˚C (5) FT (6) CAPACITIVE REACTANCE MEGAOHM 1000 FT (6) Calument/ ACSR/TW 565.3 16 20 91.5 0.1681 7x0.1146 0.3438 0.5161 0.4438 0.86 0.0300 0.0308 0.0368 715 0.0290 0.0814 0.5217 Mohawk/ ACSR/TW 571.7 13 18 92.2 0.1782 7x0.1030 0.3090 0.5072 0.4489 0.85 0.0298 0.0306 0.0365 715 0.0283 0.0820 0.5239 Oswego/ ACSR/TW 664.8 16 20 92.3 0.1823 7x0.1244 0.3732 0.6073 0.5222 0.93 0.0255 0.0262 0.0313 795 0.0313 0.0796 0.5096 Mystic/ ACSR/TW 666.6 13 20 92.3 0.1826 7x0.1111 0.3333 0.5915 0.5236 0.91 0.0255 0.0263 0.0314 790 0.0306 0.0801 0.5120 Wabash/ ACSR/TW 762.8 16 20 92.9 0.1953 7x0.1331 0.3993 0.6963 0.5989 0.99 0.0222 0.0229 0.0273 865 0.0335 0.0781 0.4993 Maumee/ ACSR/TW 768.2 13 20 93.0 0.1960 7x0.1195 0.3585 0.6817 0.6032 0.98 0.0222 0.0229 0.0273 860 0.0328 0.0786 0.5014 Kettle/ ACSR/TW 957.2 7 33 92.2 0.1703 7x0.0973 0.2919 0.8038 0.7518 1.06 0.0180 0.0189 0.0232 955 0.0350 0.0770 0.4886 Suwanee/ ACSR/TW 959.6 16 22 93.4 0.2089 7x0.1493 0.4479 0.8764 0.7539 1.11 0.0177 0.0183 0.0218 995 0.0376 0.0754 0.4817 Columbia/ ACSR/TW 966.2 13 21 93.6 0.2145 7x0.1338 0.4014 0.8576 0.7591 1.09 0.0176 0.0183 0.0218 995 0.0367 0.0760 0.4839 (1) Code words shown denote ACSR/TW with regular-strength Class A galvanized steel core (/GA2). See the Options section to find the appropriate code word modifier designation for alternative design options. (4) Based on a conductivity of 61.2% (minimum lot average) IACS at 20˚C for aluminum and 8% IACS at 20˚C for the steel core. AC resistance for single-layer and three-layer designs approximates the effects of core magnetization. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by 3.281. (5) Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 25˚C ambient temperature, 2 ft/sec crosswind (90˚ to conductor), 0.5 coefficient of emissivity, 0.5 coefficient of absorbtivity, 30˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 96.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (6) Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm). To convert the Geometric Mean Radius (GMR) to cm, divide the value by 0.03821. To convert inductive reactance to ohm/km, multiply the value by 3.281. To convert capacitive reactance to ohm/km, divide the value by 3.281. 99 Overhead Conductors Electric Utility TransPowr ACSR/TW Bare Overhead Conductor ® Trapezoidal Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded ACSR/TW (MECHANICAL PROPERTIES) – EQUIVALENT DIAMETER CONDUCTORS SIZED TO HAVE EQUIVALENT DIAMETER TO REGULAR ACSR CODE WORD (1) APPROX. WEIGHT PERCENT RATED STRENGTH SIZE STEEL STEEL CROSS-SECTION SQ. INCHES LB/1000 FT (2) BY MASS LBS STANDARD PACKAGES (3) AWG NO. EQUIVALENT CORE CORE OR AL FILL AL DIA. NO. X DIA. O.D. O.D. GA3 GA5 REEL WEIGHT LENGTH kcmil TYPE WIRES FACTOR INCHES INCHES INCHES TOTAL AL INCHES TOTAL AL STEEL AL STEEL GA2 (HS) (UHS) DESIGNATION LBS FEET Genesee/ ACSR/TW 1158.0 7 33 92.5 0.1873 Hudson/ ACSR/TW 1158.4 13 26 93.7 0.2111 Cheyenne/ 1168.1 ACSR/TW 5 30 92.9 0.1973 Yukon/ ACSR/TW 1233.6 13 39 91.0 0.1778 Nelson/ ACSR/TW 1257.1 7 35 92.4 0.1895 Catawba/ ACSR/TW 1272.0 5 30 93.3 0.2059 Thames/ ACSR/TW 1334.6 13 39 92.6 0.1850 Mackenzie/ 1359.7 ACSR/TW 7 36 92.9 0.1943 Truckee/ ACSR/TW 1372.5 5 30 93.6 0.2139 Merrimack/ 1433.6 ACSR/TW 13 39 92.1 0.1917 Miramichi/ ACSR/TW 1455.3 7 36 93.4 0.2010 St. Croix/ ACSR/TW 1467.8 5 30 93.4 0.2212 Rio Grande/ 1533.3 ACSR/TW 13 39 93.2 0.1983 Potomac/ ACSR/TW 1557.4 7 36 93.2 0.2080 Platte/ ACSR/TW 1569.0 5 33 93.7 0.2181 Pecos/ ACSR/TW 1622.0 13 39 93.1 0.2039 Schuylkill/ ACSR/TW 1657.4 7 36 93.5 0.2145 James/ ACSR/TW 1730.6 13 39 92.5 0.2107 Pee Dee/ ACSR/TW 1758.6 7 37 93.0 0.2180 Cumberland/ 1926.9 ACSR/TW 13 42 93.3 0.2142 Athabaska/ 1949.6 ACSR/TW 7 42 93.4 0.2155 Powder/ ACSR/TW 2153.8 8 64 92.2 0.1834 Santee/ ACSR/TW 2627.3 8 64 93.1 0.2027 7x0.1078 0.3234 0.9732 0.9094 1.16 1307 1091 216 83.45 16.55 31600 32900 34100 RMT 84.45 RM 68.38 7x0.1467 0.4401 1.0279 0.9096 1.20 1488 1087 401 73.08 26.92 39600 42500 44700 RMT 84.36 RM 66.32 7x0.0926 0.2778 0.9642 0.9170 1.16 1259 1099 160 87.32 12.68 28800 29700 30700 RMT 84.45 RM 66.32 19x0.0910 0.4550 1.0923 0.9688 1.25 1584 1165 419 73.53 26.47 42900 45200 47500 RMT 90.45 RMT 84.36 7x0.1115 0.3345 1.0558 0.9875 1.21 1415 1184 231 83.65 16.35 34200 35500 36800 RMT 84.45 RM 68.38 7x0.0967 0.2901 1.0507 0.9993 1.20 1371 1197 174 87.30 12.70 31400 32400 33400 RMT 84.36 RM 66.32 19x0.0944 0.4720 1.1808 1.0479 1.29 1711 1260 451 73.64 26.36 46300 48700 51200 RMT 90.45 RM 72.36 7x0.1159 0.3477 1.1413 1.0674 1.26 1531 1281 250 83.67 16.33 36900 38400 39800 RMT 84.45 RM 68.38 7x0.1004 0.3012 1.1337 1.0783 1.25 1479 1291 188 87.32 12.68 33400 34500 35500 RMT 84.36 RM 66.32 19x0.0978 0.4890 1.2682 1.1255 1.34 1838 1354 484 73.65 26.35 49700 52300 55000 RMT 90.45 RM 72.36 7x0.1200 0.3600 1.2219 1.1427 1.30 1639 1371 268 83.64 16.36 39200 40700 42200 RMT 84.45 RM 68.38 7x0.1041 0.3123 1.2127 1.1532 1.29 1583 1381 202 87.26 12.74 35800 36900 38100 RMT 84.36 RM 66.32 19x0.1012 0.5060 1.3574 1.2046 1.38 1966 1448 518 73.63 26.37 53200 56000 58900 RMT 90.45 RM 72.36 7x0.1241 0.3723 1.3084 1.2237 1.35 1754 1467 287 83.65 16.35 41900 43600 45200 RMT 84.45 RM 68.38 7x0.1074 0.3222 1.2962 1.2328 1.33 1691 1476 215 87.30 12.70 38200 39400 40600 RMT 84.45 RM 68.38 19x0.1064 0.5320 1.4425 1.2736 1.42 2105 1531 573 72.77 27.23 57500 60600 63800 RMT 90.45 RM 72.36 7x0.1280 0.3840 1.3912 1.3012 1.39 1866 1561 305 83.66 16.34 44000 45700 47500 RMT 84.45 RM 68.38 19x0.1075 0.5375 1.5322 1.3598 1.47 2219 1634 585 73.64 26.36 59400 62600 65800 RMT 90.45 RM 72.36 7x0.1319 0.3957 1.4764 1.3807 1.43 1980 1656 324 83.65 16.35 46700 48500 50400 RMT 90.45 RM 68.38 19x0.1133 0.5665 1.7044 1.5129 1.54 2469 1819 650 73.68 26.32 66000 69600 73100 RMT 90.45 RMT 84.36 7x0.1392 0.4176 1.6384 1.5318 1.50 2197 1836 361 83.58 16.42 51900 53900 56000 RMT 90.45 RM 72.36 19x0.0961 0.4805 1.8293 1.6915 1.60 2510 2042 467 81.37 18.63 61100 63600 66200 RMT 96.60 RMT 84.45 19x0.1062 0.5310 2.2328 2.0645 1.76 3062 2492 571 81.36 18.64 74500 77700 80800 RMT 96.60 RMT 84.45 (1) Code words shown denote ACSR/TW with regular-strength Class A galvanized steel core (/GA2). See the Options section to find the appropriate code word modifier designation for alternative design options. (2) Due to rounding, total values may not exactly equal the sum of the component values. (3) Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 100 10874 5437 9776 4880 9441 4720 14588 7286 11508 5747 5333 4716 14562 7273 11832 5909 9451 4718 14555 7278 11832 5916 10320 5160 14569 7275 11836 5909 10383 5192 14732 7366 11831 5915 14557 7278 12159 6079 15679 7827 13819 6898 21611 10793 21621 10810 8320 4160 6570 3280 7500 3750 9210 4600 8130 4060 3890 3440 8510 4250 7730 3860 6390 3190 7920 3960 7220 3610 6520 3260 7410 3700 6750 3370 6140 3070 7000 3500 6340 3170 6560 3280 6140 3070 6350 3170 6290 3140 8610 4300 7060 3530 Electric Utility Overhead Conductors TransPowr ACSR/TW Bare Overhead Conductor ® Trapezoidal Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded ACSR/TW (ELECTRICAL PROPERTIES) – EQUIVALENT DIAMETER CONDUCTORS SIZED TO HAVE EQUIVALENT DIAMETER TO REGULAR ACSR CODE WORD (1) CROSS-SECTION RESISTANCE (4) GEOMETRIC INDUCTIVE SQ. INCHES OHMS/1000 FT SIZE EQUIVALENT STEEL CORE STEEL MEAN REACTANCE AWG OR NO. AL FILL AL DIA. NO. X DIA. CORE O.D. O.D. DC AC AC AMPACITY RADIUS OHM/1000 FT kcmil TYPE WIRES FACTOR INCHES INCHES INCHES TOTAL AL INCHES @ 20˚C @ 25˚C @ 75˚C 75˚C (5) FT (6) CAPACITIVE REACTANCE MEGAOHM 1000 FT (6) Genesee/ ACSR/TW 1158.0 7 33 92.5 0.1873 7x0.1078 0.3234 0.9732 0.9094 1.16 0.0149 0.0157 0.0192 1075 0.0385 0.0748 0.4739 Hudson/ ACSR/TW 1158.4 13 26 93.7 0.2111 7x0.1467 0.4401 1.0279 0.9096 1.20 0.0147 0.0154 0.0183 1110 0.0402 0.0738 0.4697 Cheyenne/ ACSR/TW 1168.1 5 30 92.9 0.1973 7x0.0926 0.2778 0.9642 0.9170 1.16 0.0148 0.0157 0.0191 1075 0.0379 0.0752 0.4751 Yukon/ ACSR/TW 1233.6 13 39 91.0 0.1778 19x0.0910 0.4550 1.0923 0.9688 1.25 0.0139 0.0147 0.0179 1135 0.0422 0.0728 0.4628 Nelson/ ACSR/TW 1257.1 7 35 92.4 0.1895 7x0.1115 0.3345 1.0558 0.9875 1.21 0.0137 0.0146 0.0178 1130 0.0402 0.0739 0.4674 Catawba/ ACSR/TW 1272.0 5 30 93.3 0.2059 7x0.0967 0.2901 1.0507 0.9993 1.20 0.0135 0.0145 0.0176 1130 0.0395 0.0743 0.4688 Thames/ ACSR/TW 1334.6 13 39 92.6 0.1850 19x0.0944 0.4720 1.1808 1.0479 1.29 0.0128 0.0136 0.0166 1190 0.0435 0.0720 0.4579 Mackenzie/ ACSR/TW 1359.7 7 36 92.9 0.1943 7x0.1159 0.3477 1.1413 1.0674 1.26 0.0127 0.0136 0.0165 1185 0.0417 0.0730 0.4617 Truckee/ ACSR/TW 1372.5 5 30 93.6 0.2139 7x0.1004 0.3012 1.1337 1.0783 1.25 0.0126 0.0135 0.0164 1185 0.0409 0.0734 0.4631 Merrimack/ ACSR/TW 1433.6 13 39 92.1 0.1917 19x0.0978 0.4890 1.2682 1.1255 1.34 0.0119 0.0127 0.0155 1240 0.0452 0.0712 0.4519 Miramichi/ ACSR/TW 1455.3 7 36 93.4 0.2010 7x0.1200 0.3600 1.2219 1.1427 1.30 0.0118 0.0127 0.0155 1235 0.0430 0.0723 0.4568 St. Croix/ ACSR/TW 1467.8 5 30 93.4 0.2212 7x0.1041 0.3123 1.2127 1.1532 1.29 0.0117 0.0127 0.0154 1235 0.0424 0.0726 0.4576 Rio Grande/ ACSR/TW 1533.3 13 39 93.2 0.1983 19x0.1012 0.5060 1.3574 1.2046 1.38 0.0112 0.0120 0.0145 1295 0.0466 0.0705 0.4474 Potomac/ ACSR/TW 1557.4 7 36 93.2 0.2080 7x0.1241 0.3723 1.3084 1.2237 1.35 0.0111 0.0120 0.0145 1285 0.0445 0.0715 0.4513 Platte/ ACSR/TW 1569.0 5 33 93.7 0.2181 7x0.1074 0.3222 1.2962 1.2328 1.33 0.0110 0.0120 0.0145 1285 0.0438 0.0719 0.4527 Pecos/ ACSR/TW 1622.0 13 39 93.1 0.2039 19x0.1064 0.5320 1.4425 1.2736 1.42 0.0105 0.0113 0.0138 1340 0.0482 0.0697 0.4424 Schuylkill/ ACSR/TW 1657.4 7 36 93.5 0.2145 7x0.1280 0.3840 1.3912 1.3012 1.39 0.0104 0.0113 0.0137 1335 0.0459 0.0708 0.4467 James/ ACSR/TW 1730.6 13 39 92.5 0.2107 19x0.1075 0.5375 1.5322 1.3598 1.47 0.00989 0.0107 0.0130 1390 0.0496 0.0690 0.4374 Pee Dee/ ACSR/TW 1758.6 7 37 93.0 0.2180 7x0.1319 0.3957 1.4764 1.3807 1.43 0.00979 0.0108 0.0130 1380 0.0474 0.0701 0.4416 Cumberland/ 1926.9 13 ACSR/TW 42 93.3 0.2142 19x0.1133 0.5665 1.7044 1.5129 1.54 0.00889 0.00974 0.0117 1485 0.0522 0.0679 0.4296 Athabaska/ ACSR/TW 1949.6 7 42 93.4 0.2155 7x0.1392 0.4176 1.6384 1.5318 1.50 0.00883 0.00985 0.0118 1470 0.0499 0.0689 0.4338 Powder/ ACSR/TW 2153.8 8 64 92.2 0.1834 19x0.0961 0.4805 1.8293 1.6915 1.60 0.00803 0.00900 0.0105 1580 0.0535 0.0673 0.4239 Santee/ ACSR/TW 2627.3 8 64 93.1 0.2027 19x0.1062 0.5310 2.2328 2.0645 1.76 0.00658 0.00767 0.00886 1765 0.0589 0.0651 0.4090 (1) Code words shown denote ACSR/TW with regular-strength Class A galvanized steel core (/GA2). See the Options section to find the appropriate code word modifier designation for alternative design options. (4) Based on a conductivity of 61.2% (minimum lot average) IACS at 20˚C for aluminum and 8% IACS at 20˚C for the steel core. AC resistance for single-layer and three-layer designs approximates the effects of core magnetization. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by 3.281. (5) Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 25˚C ambient temperature, 2 ft/sec crosswind (90˚ to conductor), 0.5 coefficient of emissivity, 0.5 coefficient of absorbtivity, 30˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 96.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (6) Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm). To convert the Geometric Mean Radius (GMR) to cm, divide the value by 0.03821. To convert inductive reactance to ohm/km, multiply the value by 3.281. To convert capacitive reactance to ohm/km, divide the value by 3.281. 101 Overhead Conductors Notes 102 Electric Utility Electric Utility Overhead Conductors TransPowr ACSS Bare Overhead Conductor ® Aluminum Conductor Steel-Supported Concentric-Lay-Stranded 20/7 22/7 24/7 26/7 30/7 30/19 54/7 54/19 45/7 72/7 76/19 84/19 Product Construction: Complete Conductor: ACSS is a composite concentric-lay-stranded cable. ACSS conductors are manufactured in accordance with the latest issue of ASTM B856. The steel strands form the central core of the cable, around which is stranded one or more layers of aluminum 1350-O wires. The “O” temper of the aluminum, a fully annealed or soft temper, causes most or all of the mechanical load on ACSS to be carried by the steel. Standard ACSS designs are manufactured with regular-strength Class A zinc5% aluminum mischmetal alloy-coated steel core (/MA2). The steel core may consist of 7, 19, 37 or more wires. Features and Benefits: ACSS conductors are similar to conventional ACSR with some very important additional advantages. ACSS can operate continuously at high temperatures up to 250°C without damage, allowing for a significant increase in conductor current-carrying capacity. ACSS sags less under emergency electrical loadings than ACSR, it is self-damping, and its final sags are not affected by long-term creep of the aluminum. 3/2013 Applications: Aluminum Conductor Steel-Supported (ACSS) is used for overhead transmission lines. It is especially useful in reconductoring applications requiring increased current with existing tensions and clearances; new line applications where structures can be economized due to reduced sag; new line applications requiring high emergency loadings; and lines where aeolian vibration is a problem. At the present time, CAN/CSA C61089 does not recognize the ACSS conductor designs. The information provided on the following pages is from our US catalog. For other conductor sizes, designs and/or specific installation requirements not shown in the tables, contact your General Cable sales representative or e-mail infoca@generalcable.com. Options: • High-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA3) • Extra-high-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA4) • Ultra-high-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA5) • Aluminum-clad steel core (/AW) — see ACSS/AW catalog section • 250°C operating temperature rating utilizing either the zinc-5% aluminum mischmetal alloy-coated steel core wires or the aluminum-clad steel core wires • Trapezoidal-shaped aluminum strands (/TW) • Non-specular surface finish (/NS) 103 Overhead Conductors Electric Utility TransPowr ACSS Bare Overhead Conductor ® Aluminum Conductor Steel-Supported Concentric-Lay-Stranded ACSS, CONCENTRIC-LAY-STRANDED (MECHANICAL PROPERTIES) STRANDING NO. X DIA. INCHES CROSS-SECTION SQ. INCHES AL STEEL RATED STRENGTH LBS STANDARD PACKAGES (3) GA2 OR GA3 OR GA5 OR REEL WEIGHT LENGTH MA2 MA3 (HS) MA5 (UHS) DESIGNATION LBS FEET AL STEEL TOTAL AL 22x0.1101 24x0.1054 26x0.1013 30x0.0943 26x0.1074 20x0.1297 22x0.1237 7x0.0612 7x0.0703 7x0.0788 7x0.0943 7x0.0835 7x0.0576 7x0.0687 0.2300 0.2366 0.2437 0.2584 0.2739 0.2825 0.2903 0.2095 0.2095 0.2096 0.2095 0.2355 0.2642 0.2644 78.28 73.20 68.50 60.35 68.53 83.69 78.29 21.72 26.80 31.50 39.65 31.47 16.31 21.71 6030 7410 8880 11700 10000 5990 7610 6550 8090 9730 13000 10900 6440 8250 7580 9450 11440 15200 12800 7350 9550 317 116 73.22 26.78 9340 10200 11900 0.2640 0.720 462 317 145 68.54 31.46 11200 12300 14400 7x0.1059 0.3259 7x0.0627 0.3339 7x0.0747 0.3428 0.2642 0.741 526 0.3123 0.752 448 0.3121 0.762 478 318 374 374 209 60.34 39.66 73 83.65 16.35 104 78.28 21.72 14800 7090 8990 16300 7630 9760 19100 8710 11290 397.5 24x0.1287 7x0.0858 0.3527 0.3122 0.772 511 374 137 73.21 26.79 11000 12100 14100 Ibis/ACSS 397.5 26x0.1236 7x0.0961 0.3627 0.3120 0.783 546 374 172 68.53 31.47 13000 14200 16500 Lark/ACSS Tailorbird/ACSS Toucan/ACSS 397.5 30x0.1151 477.0 20x0.1544 477.0 22x0.1472 7x0.1151 0.3850 7x0.0686 0.4003 7x0.0818 0.4112 0.3121 0.806 622 0.3746 0.824 537 0.3744 0.834 574 375 449 449 247 60.35 39.65 88 83.69 16.31 125 78.30 21.70 17500 8490 10800 19300 9140 11700 22600 10430 13500 Flicker/ACSS 477.0 24x0.1410 7x0.0940 0.4233 0.3747 0.846 614 449 164 73.20 26.80 13000 14200 16400 Hawk/ACSS 477.0 26x0.1354 7x0.1053 0.4353 0.3744 0.858 656 449 206 68.52 31.48 15600 17100 19800 Hen/ACSS Heron/ACSS Tody/ACSS Sapsucker/ACSS 477.0 500.0 556.5 556.5 7x0.1261 7x0.1291 7x0.0741 7x0.0883 0.3747 0.3927 0.4370 0.4368 746 782 626 669 450 472 524 524 296 310 102 145 39.66 39.65 16.32 21.68 21000 22000 9900 12600 22700 23800 10700 13600 26700 27900 12200 15800 Parakeet/ACSS 556.5 24x0.1523 7x0.1015 0.4939 0.4372 0.914 716 524 192 73.22 26.78 15200 16600 19100 Dove/ACSS 556.5 26x0.1463 7x0.1138 0.5083 0.4371 0.927 765 524 241 68.50 31.50 18200 19900 23100 Eagle/ACSS Peacock/ACSS 556.5 30x0.1362 605.0 24x0.1588 7x0.1362 0.5391 7x0.1059 0.5370 0.4371 0.953 871 0.4753 0.953 779 525 570 345 60.35 39.65 209 73.19 26.81 24500 16500 26500 18100 31100 20800 Squab/ACSS 605.0 26x0.1525 7x0.1186 0.5522 0.4749 0.966 832 570 262 68.52 31.48 19700 21700 25100 Wood Duck/ACSS 605.0 30x0.1420 7x0.1420 0.5860 Teal/ACSS 605.0 30x0.1420 19x0.0852 0.5834 0.4751 0.994 947 0.4751 0.994 939 571 571 375 60.35 39.65 367 60.85 39.15 26000 26600 28300 29300 33300 34700 Turacos/ACSS 636.0 20x0.1783 7x0.0792 0.5339 0.4994 0.951 716 599 117 83.69 16.31 11300 12200 13900 Goldfinch/ACSS 636.0 22x0.1700 7x0.0944 0.5483 0.4994 0.963 765 599 166 78.32 21.68 14100 15300 17600 Rook/ACSS 636.0 24x0.1628 7x0.1085 0.5643 0.4996 0.977 818 599 219 73.22 26.78 17300 19000 21900 CODE WORD (1) SIZE AWG OR kcmil Spoonbill/ACSS Scaup/ACSS Partridge/ACSS Junco/ACSS Ostrich/ACSS Trogon/ACSS Woodcock/ACSS 266.8 266.8 266.8 266.8 300.0 336.4 336.4 Widgeon/ACSS 336.4 24x0.1184 Linnet/ACSS APPROX. WEIGHT LB/1000 FT (2) O.D. INCHES TOTAL AL STEEL 321 343 367 417 412 379 405 251 251 251 252 283 317 317 70 92 116 166 130 62 88 7x0.0789 0.2985 0.2642 0.710 433 336.4 26x0.1137 7x0.0884 0.3070 Oriole/ACSS Ptarmigan/ACSS Stork/ACSS 336.4 30x0.1059 397.5 20x0.1410 397.5 22x0.1344 Brant/ACSS 30x0.1261 30x0.1291 20x0.1668 22x0.1590 0.4621 0.4843 0.4672 0.4797 0.624 0.633 0.642 0.660 0.680 0.692 0.701 0.883 0.904 0.890 0.901 PERCENT BY MASS 60.34 60.35 83.68 78.32 RM 68.38 RM 68.38 RM 68.38 RM 68.38 RM 68.38 RM 68.38 RMT 84.36 RM 68.38 RMT 84.36 RM 68.38 RMT 84.36 RM 68.38 RM 68.38 RM 68.38 RMT 84.36 RM 68.38 RMT 84.36 RM 68.38 RMT 84.36 RM 68.38 RM 68.38 RM 68.38 RMT 84.36 RM 68.38 RMT 84.36 RM 68.38 RMT 84.36 RM 68.38 RM 68.38 RM 68.38 RM 68.38 RMT 84.36 RM 68.38 RMT 84.36 RM 68.38 RMT 84.36 RM 68.38 RM 68.38 RMT 84.36 RM 68.38 RMT 84.36 RM 68.38 RM 68.38 RMT 84.45 RM 68.38 RMT 84.36 RM 68.38 RMT 84.45 RMT 84.36 RM 68.38 RMT 84.45 RMT 84.36 RM 68.38 2810 3265 3790 4970 3785 4780 5620 2810 6550 3275 7570 3785 4970 4780 5605 2805 6535 3270 7575 3785 4965 4780 5620 2810 6535 3265 7570 3785 4960 4960 4770 5615 2805 6545 3270 7580 3790 4960 6550 3275 7580 3790 4960 9840 4920 7160 4775 8425 5615 2810 9815 6545 3270 8755 9520 10330 11890 9190 12610 13880 6940 15130 7565 16390 8195 9430 10670 11730 5865 12790 6395 13870 6935 7980 8900 9790 4895 10660 5330 11560 5780 6650 6345 7620 8390 4195 9140 4570 9910 4955 5700 8410 4205 9110 4555 5245 10490 5245 10000 6670 11010 7340 3670 12000 8000 4000 (1) Code words shown denote ACSS with regular-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA2). See the Options section to find the appropriate code word modifier designation for alternative design options. (2) Due to rounding, total values may be slightly greater or slightly less than the sum of the component values. (3) Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 104 3/2013 Electric Utility Overhead Conductors TransPowr ACSS Bare Overhead Conductor ® Aluminum Conductor Steel-Supported Concentric-Lay-Stranded ACSS, CONCENTRIC-LAY-STRANDED (ELECTRICAL PROPERTIES) CROSS-SECTION SQ. INCHES CODE WORD (1) SIZE AWG OR kcmil STRANDING NO. X DIA. INCHES DC @ 20˚C RESISTANCE (4) OHMS/1000 FT AC AC @ 25˚C @ 75˚C AC @ 200˚C 75˚C GEOMETRIC INDUCTIVE MEAN REACTANCE RADIUS OHM/1000 FT 200˚C FT (6) AL STEEL TOTAL AL O.D. INCHES Spoonbill/ACSS Scaup/ACSS Partridge/ACSS Junco/ACSS Ostrich/ACSS Trogon/ACSS Woodcock/ACSS 266.8 266.8 266.8 266.8 300.0 336.4 336.4 22x0.1101 24x0.1054 26x0.1013 30x0.0943 26x0.1074 20x0.1297 22x0.1237 7x0.0612 7x0.0703 7x0.0788 7x0.0943 7x0.0835 7x0.0576 7x0.0687 0.2300 0.2366 0.2437 0.2584 0.2739 0.2825 0.2903 0.2095 0.2095 0.2096 0.2095 0.2355 0.2642 0.2644 0.624 0.633 0.642 0.660 0.680 0.692 0.701 0.0624 0.0622 0.0619 0.0615 0.0551 0.0497 0.0495 0.0639 0.0636 0.0633 0.0629 0.0563 0.0509 0.0507 0.0768 0.0765 0.0761 0.0756 0.0677 0.0612 0.0609 0.1091 0.1086 0.1081 0.1073 0.0962 0.0869 0.0866 455 460 460 465 500 525 530 800 805 810 825 875 925 935 0.0206 0.0211 0.0216 0.0226 0.0229 0.0226 0.0231 0.0892 0.0887 0.0882 0.0871 0.0868 0.0871 0.0866 0.5716 0.5694 0.5672 0.5628 0.5581 0.5555 0.5534 Widgeon/ACSS 336.4 24x0.1184 7x0.0789 0.2985 0.2642 0.710 0.0493 0.0505 0.0607 0.0862 530 940 0.0237 0.0860 0.5513 Linnet/ACSS 336.4 26x0.1137 7x0.0884 0.3070 0.2640 0.720 0.0491 0.0503 0.0604 0.0858 535 945 0.0242 0.0855 0.5491 Oriole/ACSS Ptarmigan/ACSS Stork/ACSS 336.4 397.5 397.5 30x0.1059 20x0.1410 22x0.1344 7x0.1059 7x0.0627 7x0.0747 0.3259 0.3339 0.3428 0.2642 0.3123 0.3121 0.741 0.752 0.762 0.0488 0.0421 0.0419 0.0499 0.0431 0.0430 0.0600 0.0518 0.0516 0.0851 0.0736 0.0733 540 585 585 955 1035 1040 0.0253 0.0245 0.0251 0.0845 0.0852 0.0847 0.5446 0.5424 0.5404 Brant/ACSS 397.5 24x0.1287 7x0.0858 0.3527 0.3122 0.772 0.0417 0.0428 0.0514 0.0730 590 1045 0.0257 0.0841 0.5382 Ibis/ACSS 397.5 26x0.1236 7x0.0961 0.3627 0.3120 0.783 0.0416 0.0426 0.0512 0.0726 595 1055 0.0263 0.0836 0.5360 Lark/ACSS Tailorbird/ACSS Toucan/ACSS 397.5 477.0 477.0 30x0.1151 20x0.1544 22x0.1472 7x0.1151 7x0.0686 7x0.0818 0.3850 0.4003 0.4112 0.3121 0.3746 0.3744 0.806 0.824 0.834 0.0413 0.0351 0.0349 0.0423 0.0360 0.0359 0.0508 0.0433 0.0431 0.0721 0.0614 0.0611 600 655 660 1070 1165 1175 0.0275 0.0269 0.0275 0.0826 0.0831 0.0826 0.5316 0.5281 0.5261 Flicker/ACSS 477.0 24x0.1410 7x0.0940 0.4233 0.3747 0.846 0.0348 0.0357 0.0429 0.0608 660 1180 0.0282 0.0820 0.5240 Hawk/ACSS 477.0 26x0.1354 7x0.1053 0.4353 0.3744 0.858 0.0346 0.0355 0.0427 0.0605 665 1190 0.0288 0.0815 0.5218 Hen/ACSS Heron/ACSS Tody/ACSS Sapsucker/ACSS 477.0 500.0 556.5 556.5 30x0.1261 30x0.1291 20x0.1668 22x0.1590 7x0.1261 7x0.1291 7x0.0741 7x0.0883 0.4621 0.4843 0.4672 0.4797 0.3747 0.3927 0.4370 0.4368 0.883 0.904 0.890 0.901 0.0344 0.0328 0.0301 0.0299 0.0353 0.0337 0.0309 0.0308 0.0423 0.0404 0.0371 0.0370 0.0601 0.0573 0.0527 0.0524 675 695 720 725 1205 1240 1290 1295 0.0302 0.0309 0.0290 0.0297 0.0805 0.0799 0.0813 0.0808 0.5173 0.5136 0.5161 0.5140 Parakeet/ACSS 556.5 24x0.1523 7x0.1015 0.4939 0.4372 0.914 0.0298 0.0306 0.0368 0.0522 730 1305 0.0304 0.0803 0.5119 Dove/ACSS 556.5 26x0.1463 7x0.1138 0.5083 0.4371 0.927 0.0297 0.0305 0.0366 0.0519 735 1315 0.0311 0.0797 0.5097 Eagle/ACSS Peacock/ACSS 556.5 605.0 30x0.1362 24x0.1588 7x0.1362 7x0.1059 0.5391 0.5370 0.4371 0.4753 0.953 0.953 0.0295 0.0274 0.0303 0.0282 0.0363 0.0339 0.0515 0.0480 740 770 1330 1380 0.0326 0.0317 0.0787 0.0793 0.5052 0.5053 Squab/ACSS 605.0 26x0.1525 7x0.1186 0.5522 0.4749 0.966 0.0273 0.0281 0.0337 0.0478 775 1390 0.0325 0.0788 0.5031 Wood Duck/ACSS 605.0 Teal/ACSS 605.0 30x0.1420 30x0.1420 7x0.1420 19x0.0852 0.5860 0.5834 0.4751 0.4751 0.994 0.994 0.0271 0.0272 0.0279 0.0279 0.0334 0.0335 0.0474 0.0474 780 780 1405 1405 0.0340 0.0340 0.0777 0.0777 0.4987 0.4987 Turacos/ACSS 636.0 20x0.1783 7x0.0792 0.5339 0.4994 0.951 0.0263 0.0271 0.0325 0.0461 785 1405 0.0310 0.0798 0.5056 Goldfinch/ACSS 636.0 22x0.1700 7x0.0944 0.5483 0.4994 0.963 0.0262 0.0270 0.0324 0.0459 790 1415 0.0318 0.0793 0.5036 Rook/ACSS 636.0 24x0.1628 7x0.1085 0.5643 0.4996 0.977 0.0261 0.0269 0.0322 0.0457 790 1425 0.0325 0.0787 0.5014 AMPACITY (5) CAPACITIVE REACTANCE MEGAOHM 1000 FT (6) (1) Code words shown denote ACSS with regular-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA2). See the Options section to find the appropriate code word modifier designation for alternative design options. (4) Based on a conductivity of 61.2% (minimum lot average) IACS at 20˚C for aluminum and 8% IACS at 20˚C for the steel core. AC resistance for single-layer and three-layer designs approximates the effects of core magnetization. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by 3.281. (5) Based on the given conductor temperature at 60 Hz and the following conditions: 25˚C ambient temperature, 2 ft/sec crosswind (90˚ to conductor), 0.5 coefficient of emissivity, 0.5 coefficient of absorbtivity, 30˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 96.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (6) Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius. 3/2013 105 Overhead Conductors Electric Utility TransPowr ACSS Bare Overhead Conductor ® Aluminum Conductor Steel-Supported Concentric-Lay-Stranded ACSS, CONCENTRIC-LAY-STRANDED (MECHANICAL PROPERTIES) CODE WORD (1) SIZE AWG OR kcmil STRANDING NO. X DIA. INCHES CROSS-SECTION SQ. INCHES AL TOTAL STEEL AL APPROX. WEIGHT LB/1000 FT (2) O.D. INCHES TOTAL AL STEEL PERCENT BY MASS AL STEEL RATED STRENGTH LBS STANDARD PACKAGES (3) GA2 OR GA3 OR GA5 OR REEL WEIGHT LENGTH MA2 MA3 (HS) MA5 (UHS) DESIGNATION LBS FEET Grosbeak/ACSS 636.0 26x0.1564 7x0.1216 0.5808 0.4995 0.990 874 599 275 68.52 31.48 20700 22400 26000 Scoter/ACSS 636.0 30x0.1456 7x0.1456 0.6160 0.4995 1.019 995 601 395 60.35 39.65 27400 29700 35000 Egret/ACSS 636.0 30x0.1456 19x0.0874 0.6135 0.4995 1.019 987 601 387 60.83 39.17 28000 30900 36600 Flamingo/ACSS 666.6 24x0.1667 7x0.1111 0.5917 0.5238 1.000 858 628 230 73.21 26.79 18200 19900 22900 Gannet/ACSS 666.6 26x0.1601 7x0.1245 0.6086 0.5234 1.014 916 628 289 68.52 31.48 21700 23400 27300 Stilt/ACSS 715.5 24x0.1727 7x0.1151 0.6350 0.5622 1.036 921 674 247 73.21 26.79 19500 21300 24600 Starling/ACSS 715.5 26x0.1659 7x0.1290 0.6535 0.5620 1.051 984 674 310 68.51 31.49 23300 25200 29300 Redwing/ACSS 715.5 30x0.1544 19x0.0926 0.6897 0.5617 1.081 1110 676 434 60.88 39.12 30800 34000 39800 Macaw/ACSS 795.0 42x0.1376 7x0.0764 0.6567 0.6246 1.055 857 749 109 87.33 12.67 11800 12600 14200 Turbit/ACSS 795.0 20x0.1994 7x0.0886 0.6677 0.6246 1.063 895 749 146 83.67 16.33 14200 15200 17400 Tern/ACSS 795.0 45x0.1329 7x0.0886 0.6674 0.6242 1.063 895 749 146 83.67 16.33 14200 15200 17400 Puffin/ACSS 795.0 22x0.1901 7x0.1056 0.6857 0.6244 1.077 956 749 208 78.30 21.70 17700 19200 22000 Cuckoo/ACSS 795.0 24x0.1820 7x0.1213 0.7053 0.6244 1.092 1023 749 274 73.22 26.78 21700 23300 26900 Condor/ACSS 795.0 54x0.1213 7x0.1213 0.7049 0.6240 1.092 1023 749 274 73.22 26.78 21700 23300 26900 Drake/ACSS 795.0 26x0.1749 7x0.1360 0.7263 0.6246 1.107 1093 749 344 68.50 31.50 25900 28000 32600 Mallard/ACSS 795.0 30x0.1628 19x0.0977 0.7669 0.6245 1.140 1234 751 483 60.84 39.16 34300 37900 44300 Ruddy/ACSS 900.0 45x0.1414 7x0.0943 0.7555 0.7066 1.131 1013 848 166 83.66 16.34 15800 17000 19200 Canary/ACSS 900.0 54x0.1291 7x0.1291 0.7985 0.7069 1.162 1158 848 310 73.21 26.79 24600 26400 30500 Phoenix/ACSS 954.0 42x0.1507 7x0.0837 0.7877 0.7491 1.155 1029 899 130 87.33 12.67 14200 15200 17100 Corncrake/ACSS 954.0 20x0.2184 7x0.0971 0.8011 0.7492 1.165 1074 899 175 83.66 16.34 16700 18000 20400 RMT 90.45 RMT 84.36 RM 68.38 RMT 96.60 RM 68.38 RMT 96.60 RMT 84.45 RM 68.38 RMT 84.45 RMT 84.36 RM 68.38 RMT 90.45 RMT 84.36 RM 68.38 RMT 84.45 RMT 84.36 RM 68.38 RMT 90.45 RMT 84.36 RM 68.38 RMT 96.60 RMT 84.45 RM 68.38 RMT 90.45 RM 68.38 RMT 84.36 RM 68.38 RMT 96.60 RMT 90.45 RM 68.38 RMT 84.45 RMT 84.36 RM 68.38 RMT 84.45 RMT 84.36 RM 68.38 RMT 96.60 RMT 90.45 RMT 90.45 RMT 84.36 RM 68.38 RMT 96.60 RMT 84.45 RM 68.38 RMT 96.60 RMT 90.45 RM 68.38 RMT 96.60 RMT 90.45 RMT 90.45 RM 68.38 RMT 84.36 RM 68.38 11370 7580 3790 14945 4980 14765 9850 4925 9835 6545 3275 11380 7595 3795 9820 6540 3270 11365 7585 3795 14750 9850 4925 9610 4805 7160 4770 16110 10740 5370 8420 5620 2810 9830 6545 3275 19130 11040 11365 7585 3795 14770 9845 4925 16095 10730 5365 19155 11045 9600 4800 7170 4785 13010 8670 4335 15020 5005 14960 9980 4990 11460 7630 3815 12410 8280 4140 10660 7100 3550 11550 7710 3855 13300 8880 4440 11200 5600 8000 5330 18000 12000 6000 8800 5870 2935 9610 6400 3200 18720 10800 10400 6940 3470 11970 7980 3990 15890 10590 5295 16540 9540 9340 4670 6670 4450 (1) Code words shown denote ACSS with regular-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA2). See the Options section to find the appropriate code word modifier designation for alternative design options. (2) Due to rounding, total values may be slightly greater or slightly less than the sum of the component values. (3) Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 106 3/2013 Electric Utility Overhead Conductors TransPowr ACSS Bare Overhead Conductor ® Aluminum Conductor Steel-Supported Concentric-Lay-Stranded ACSS, CONCENTRIC-LAY-STRANDED (ELECTRICAL PROPERTIES) SIZE AWG OR kcmil STRANDING NO. X DIA. INCHES CROSS-SECTION SQ. INCHES DC @ 20˚C RESISTANCE (4) OHMS/1000 FT AC AC @ 25˚C @ 75˚C AC @ 200˚C 75˚C GEOMETRIC INDUCTIVE MEAN REACTANCE RADIUS OHM/1000 FT 200˚C FT (6) AL STEEL TOTAL AL O.D. INCHES Grosbeak/ACSS 636.0 26x0.1564 7x0.1216 0.5808 0.4995 0.990 0.0260 0.0267 0.0321 0.0455 795 1435 0.0333 0.0782 0.4992 Scoter/ACSS 636.0 30x0.1456 7x0.1456 0.6160 0.4995 1.019 0.0258 0.0265 0.0318 0.0451 805 1455 0.0348 0.0772 0.4948 Egret/ACSS 636.0 30x0.1456 19x0.0874 0.6135 0.4995 1.019 0.0258 0.0265 0.0318 0.0451 805 1455 0.0348 0.0772 0.4947 Flamingo/ACSS 666.6 24x0.1667 7x0.1111 0.5917 0.5238 1.000 0.0249 0.0257 0.0308 0.0436 815 1470 0.0333 0.0782 0.4977 Gannet/ACSS 666.6 26x0.1601 7x0.1245 0.6086 0.5234 1.014 0.0248 0.0255 0.0306 0.0434 820 1480 0.0341 0.0777 0.4956 Stilt/ACSS 715.5 24x0.1727 7x0.1151 0.6350 0.5622 1.036 0.0232 0.0239 0.0287 0.0406 855 1540 0.0345 0.0774 0.4922 Starling/ACSS 715.5 26x0.1659 7x0.1290 0.6535 0.5620 1.051 0.0231 0.0238 0.0286 0.0404 860 1550 0.0353 0.0768 0.4900 Redwing/ACSS 715.5 30x0.1544 19x0.0926 0.6897 0.5617 1.081 0.0230 0.0236 0.0283 0.0401 870 1570 0.0369 0.0758 0.4856 Macaw/ACSS 795.0 42x0.1376 7x0.0764 0.6567 0.6246 1.055 0.0211 0.0221 0.0273 0.0396 880 1570 0.0346 0.0773 0.4894 Turbit/ACSS 795.0 20x0.1994 7x0.0886 0.6677 0.6246 1.063 0.0210 0.0218 0.0261 0.0370 900 1630 0.0347 0.0772 0.4881 Tern/ACSS 795.0 45x0.1329 7x0.0886 0.6674 0.6242 1.063 0.0210 0.0220 0.0272 0.0395 880 1575 0.0351 0.0770 0.4881 Puffin/ACSS 795.0 22x0.1901 7x0.1056 0.6857 0.6244 1.077 0.0210 0.0217 0.0260 0.0368 905 1640 0.0355 0.0767 0.4861 Cuckoo/ACSS 795.0 24x0.1820 7x0.1213 0.7053 0.6244 1.092 0.0209 0.0216 0.0259 0.0366 910 1650 0.0364 0.0762 0.4840 Condor/ACSS 795.0 54x0.1213 7x0.1213 0.7049 0.6240 1.092 0.0209 0.0217 0.0270 0.0392 890 1595 0.0366 0.0760 0.4840 Drake/ACSS 795.0 26x0.1749 7x0.1360 0.7263 0.6246 1.107 0.0208 0.0215 0.0257 0.0364 915 1660 0.0372 0.0756 0.4818 Mallard/ACSS 795.0 30x0.1628 19x0.0977 0.7669 0.6245 1.140 0.0207 0.0213 0.0255 0.0362 925 1685 0.0389 0.0746 0.4773 Ruddy/ACSS 900.0 45x0.1414 7x0.0943 0.7555 0.7066 1.131 0.0186 0.0195 0.0241 0.0349 955 1710 0.0373 0.0756 0.4784 Canary/ACSS 900.0 54x0.1291 7x0.1291 0.7985 0.7069 1.162 0.0184 0.0193 0.0239 0.0346 965 1730 0.0390 0.0746 0.4742 Phoenix/ACSS 954.0 42x0.1507 7x0.0837 0.7877 0.7491 1.155 0.0176 0.0185 0.0228 0.0330 985 1770 0.0379 0.0752 0.4751 Corncrake/ACSS 954.0 20x0.2184 7x0.0971 0.8011 0.7492 1.165 0.0175 0.0183 0.0219 0.0309 1005 1835 0.0380 0.0751 0.4738 CODE WORD (1) AMPACITY (5) CAPACITIVE REACTANCE MEGAOHM 1000 FT (6) (1) Code words shown denote ACSS with regular-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA2). See the Options section to find the appropriate code word modifier designation for alternative design options. (4) Based on a conductivity of 61.2% (minimum lot average) IACS at 20˚C for aluminum and 8% IACS at 20˚C for the steel core. AC resistance for single-layer and three-layer designs approximates the effects of core magnetization. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by 3.281. (5) Based on the given conductor temperature at 60 Hz and the following conditions: 25˚C ambient temperature, 2 ft/sec crosswind (90˚ to conductor), 0.5 coefficient of emissivity, 0.5 coefficient of absorbtivity, 30˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 96.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (6) Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius. 3/2013 107 Overhead Conductors Electric Utility TransPowr ACSS Bare Overhead Conductor ® Aluminum Conductor Steel-Supported Concentric-Lay-Stranded ACSS, CONCENTRIC-LAY-STRANDED (MECHANICAL PROPERTIES) CODE WORD (1) SIZE AWG OR kcmil STRANDING NO. X DIA. INCHES CROSS-SECTION SQ. INCHES AL TOTAL STEEL AL APPROX. WEIGHT LB/1000 FT (2) O.D. INCHES TOTAL AL STEEL PERCENT BY MASS AL STEEL RATED STRENGTH LBS STANDARD PACKAGES (3) GA2 OR GA3 OR GA5 OR REEL WEIGHT LENGTH MA2 MA3 (HS) MA5 (UHS) DESIGNATION LBS FEET Rail/ACSS 954.0 45x0.1456 7x0.0971 0.8011 0.7492 1.165 1074 899 175 83.66 16.34 16700 18000 20400 Towhee/ACSS 954.0 48x0.1410 7x0.1097 0.8157 0.7495 1.175 1123 899 224 80.05 19.95 19700 21300 24300 Redbird/ACSS 954.0 24x0.1994 7x0.1329 0.8466 0.7495 1.196 1227 899 329 73.21 26.79 26000 28000 32300 Cardinal/ACSS 954.0 54x0.1329 7x0.1329 0.8462 0.7491 1.196 1227 899 329 73.21 26.79 26000 28000 32300 Canvasback/ ACSS 954.0 30x0.1783 19x0.1070 0.9201 0.7493 1.248 1480 901 580 60.85 39.15 41100 45400 53100 Snowbird/ACSS 1033.5 42x0.1569 7x0.0872 0.8539 0.8121 1.203 1115 973 142 87.31 12.69 15400 16400 18500 Ortolan/ACSS 1033.5 45x0.1515 7x0.1010 0.8681 0.8121 1.212 1163 973 190 83.68 16.32 18100 19500 22000 Whooper/ACSS 1033.5 48x0.1467 7x0.1141 0.8829 0.8113 1.223 1216 973 242 80.07 19.93 21300 23100 26300 Curlew/ACSS 1033.5 54x0.1383 7x0.1383 0.9164 0.8112 1.245 1329 973 356 73.22 26.78 28200 30300 35000 Avocet/ACSS 1113.0 42x0.1628 7x0.0904 0.9192 0.8743 1.248 1200 1048 152 87.33 12.67 16300 17500 19500 Bluejay/ACSS 1113.0 45x0.1573 7x0.1049 0.9350 0.8745 1.259 1253 1048 205 83.66 16.34 19500 21000 23800 Bullfinch/ACSS 1113.0 48x0.1523 7x0.1184 0.9516 0.8744 1.269 1310 1048 261 80.04 19.96 23000 24900 28400 Finch/ACSS 1113.0 54x0.1436 19x0.0861 0.9854 0.8746 1.293 1430 1053 376 73.69 26.31 30400 33200 38700 Oxbird/ACSS 1192.5 42x0.1685 7x0.0936 0.9847 0.9365 1.292 1286 1123 163 87.32 12.68 17500 18700 20900 Bunting/ACSS 1192.5 45x0.1628 7x0.1085 1.0014 0.9367 1.302 1342 1123 219 83.68 16.32 20900 22500 25400 Cormorant/ACSS 1192.5 48x0.1576 7x0.1226 1.0190 0.9364 1.313 1403 1123 280 80.06 19.94 24600 26200 30000 Grackle/ACSS 1192.5 54x0.1486 19x0.0892 1.0553 0.9365 1.338 1531 1129 403 73.70 26.30 32600 35500 41500 Scissortail/ACSS 1272.0 42x0.1740 7x0.0967 1.0501 0.9987 1.334 1372 1198 174 87.32 12.68 18700 20000 22300 Bittern/ACSS 1272.0 45x0.1681 7x0.1121 1.0678 0.9987 1.345 1432 1198 234 83.67 16.33 22300 24000 27100 RMT 96.60 RMT 90.45 RM 68.38 RMT 96.60 RMT 90.45 RMT 84.36 RMT 84.45 RMT 84.36 RMT 96.60 RMT 90.45 RMT 96.60 RMT 84.45 RM 68.38 RMT 90.45 RM 68.38 RMT 96.60 RMT 90.45 RM 68.38 RMT 96.60 RMT 90.45 RM 68.38 RMT 96.60 RMT 90.45 RMT 96.60 RMT 90.45 RM 68.38 RMT 96.60 RMT 90.45 RM 68.38 RMT 96.60 RMT 90.45 RMT 84.36 RMT 96.60 RMT 90.45 RMT 96.60 RMT 90.45 RM 68.38 RMT 96.60 RMT 90.45 RM 68.38 RMT 96.60 RMT 90.45 RMT 84.36 RMT 96.60 RMT 90.45 RMT 96.60 RMT 90.45 RM 68.38 RMT 96.60 RMT 90.45 RM 68.38 16125 10750 5375 17970 11980 5990 9825 6545 19140 11780 14780 9865 4930 9610 4805 16110 10735 5365 17945 11970 5985 19140 11045 14400 9600 4800 16120 10745 1610 17945 11975 5985 19035 10970 14405 9605 4805 16105 10735 5370 17960 11970 5985 19025 10970 14405 9605 4800 16110 10740 5370 15000 10000 5000 16000 10670 5335 8000 5330 15600 9600 9980 6660 3330 8610 4305 13850 9230 4615 14770 9850 4925 14400 8310 12000 8000 4000 12853 8570 1285 13700 9140 4570 13310 7670 11200 7470 3735 12000 8000 4000 12800 8530 4265 12420 7160 10500 7000 3500 11250 7500 3750 (1) Code words shown denote ACSS with regular-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA2). See the Options section to find the appropriate code word modifier designation for alternative design options. (2) Due to rounding, total values may be slightly greater or slightly less than the sum of the component values. (3) Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 108 3/2013 Electric Utility Overhead Conductors TransPowr ACSS Bare Overhead Conductor ® Aluminum Conductor Steel-Supported Concentric-Lay-Stranded ACSS, CONCENTRIC-LAY-STRANDED (ELECTRICAL PROPERTIES) SIZE AWG OR kcmil STRANDING NO. X DIA. INCHES CROSS-SECTION SQ. INCHES DC @ 20˚C RESISTANCE (4) OHMS/1000 FT AC AC @ 25˚C @ 75˚C AC @ 200˚C 75˚C GEOMETRIC INDUCTIVE MEAN REACTANCE RADIUS OHM/1000 FT 200˚C FT (6) AL STEEL TOTAL AL O.D. INCHES Rail/ACSS 954.0 45x0.1456 7x0.0971 0.8011 0.7492 1.165 0.0175 0.0185 0.0228 0.0329 990 1775 0.0384 0.0749 0.4738 Towhee/ACSS 954.0 48x0.1410 7x0.1097 0.8157 0.7495 1.175 0.0175 0.0184 0.0227 0.0328 990 1785 0.0390 0.0746 0.4725 Redbird/ACSS 954.0 24x0.1994 7x0.1329 0.8466 0.7495 1.196 0.0174 0.0181 0.0217 0.0306 1020 1860 0.0398 0.0741 0.4697 Cardinal/ACSS 954.0 54x0.1329 7x0.1329 0.8462 0.7491 1.196 0.0174 0.0182 0.0225 0.0326 1000 1800 0.0401 0.0739 0.4697 Canvasback/ ACSS 954.0 30x0.1783 19x0.1070 0.9201 0.7493 1.248 0.0172 0.0178 0.0214 0.0302 1040 1900 0.0427 0.0725 0.4630 Snowbird/ACSS 1033.5 42x0.1569 7x0.0872 0.8539 0.8121 1.203 0.0162 0.0172 0.0211 0.0305 1035 1865 0.0394 0.0743 0.4688 Ortolan/ACSS 1033.5 45x0.1515 7x0.1010 0.8681 0.8121 1.212 0.0162 0.0171 0.0211 0.0304 1040 1875 0.0400 0.0740 0.4676 Whooper/ACSS 1033.5 48x0.1467 7x0.1141 0.8829 0.8113 1.223 0.0161 0.0170 0.0210 0.0303 1040 1880 0.0406 0.0737 0.4662 Curlew/ACSS 1033.5 54x0.1383 7x0.1383 0.9164 0.8112 1.245 0.0161 0.0169 0.0208 0.0301 1050 1900 0.0418 0.0730 0.4634 Avocet/ACSS 1113.0 42x0.1628 7x0.0904 0.9192 0.8743 1.248 0.0151 0.0160 0.0197 0.0283 1080 1960 0.0409 0.0735 0.4630 Bluejay/ACSS 1113.0 45x0.1573 7x0.1049 0.9350 0.8745 1.259 0.0150 0.0159 0.0196 0.0282 1085 1970 0.0415 0.0731 0.4618 Bullfinch/ACSS 1113.0 48x0.1523 7x0.1184 0.9516 0.8744 1.269 0.0150 0.0159 0.0195 0.0281 1090 1975 0.0421 0.0728 0.4604 Finch/ACSS 1113.0 54x0.1436 19x0.0861 0.9854 0.8746 1.293 0.0150 0.0158 0.0195 0.0281 1100 1990 0.0434 0.0721 0.4576 Oxbird/ACSS 1192.5 42x0.1685 7x0.0936 0.9847 0.9365 1.292 0.0141 0.0150 0.0184 0.0264 1130 2050 0.0423 0.0727 0.4576 Bunting/ACSS 1192.5 45x0.1628 7x0.1085 1.0014 0.9367 1.302 0.0140 0.0150 0.0183 0.0263 1135 2060 0.0429 0.0723 0.4564 Cormorant/ACSS 1192.5 48x0.1576 7x0.1226 1.0190 0.9364 1.313 0.0140 0.0149 0.0183 0.0263 1140 2070 0.0436 0.0720 0.4550 Grackle/ACSS 1192.5 54x0.1486 19x0.0892 1.0553 0.9365 1.338 0.0140 0.0148 0.0182 0.0262 1145 2085 0.0449 0.0713 0.4522 Scissortail/ACSS 1272.0 42x0.1740 7x0.0967 1.0501 0.9987 1.334 0.0132 0.0142 0.0173 0.0248 1175 2140 0.0437 0.0719 0.4526 Bittern/ACSS 1272.0 45x0.1681 7x0.1121 1.0678 0.9987 1.345 0.0131 0.0141 0.0172 0.0247 1180 2150 0.0443 0.0716 0.4513 CODE WORD (1) AMPACITY (5) CAPACITIVE REACTANCE MEGAOHM 1000 FT (6) (1) Code words shown denote ACSS with regular-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA2). See the Options section to find the appropriate code word modifier designation for alternative design options. (4) Based on a conductivity of 61.2% (minimum lot average) IACS at 20˚C for aluminum and 8% IACS at 20˚C for the steel core. AC resistance for single-layer and three-layer designs approximates the effects of core magnetization. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by 3.281. (5) Based on the given conductor temperature at 60 Hz and the following conditions: 25˚C ambient temperature, 2 ft/sec crosswind (90˚ to conductor), 0.5 coefficient of emissivity, 0.5 coefficient of absorbtivity, 30˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 96.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (6) Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius. 3/2013 109 Overhead Conductors Electric Utility TransPowr ACSS Bare Overhead Conductor ® Aluminum Conductor Steel-Supported Concentric-Lay-Stranded ACSS, CONCENTRIC-LAY-STRANDED (MECHANICAL PROPERTIES) CODE WORD (1) SIZE AWG OR kcmil STRANDING NO. X DIA. INCHES CROSS-SECTION SQ. INCHES AL TOTAL STEEL AL APPROX. WEIGHT LB/1000 FT (2) O.D. INCHES TOTAL AL STEEL PERCENT BY MASS AL STEEL RATED STRENGTH LBS STANDARD PACKAGES (3) GA2 OR GA3 OR GA5 OR REEL WEIGHT LENGTH MA2 MA3 (HS) MA5 (UHS) DESIGNATION LBS FEET Diver/ACSS 1272.0 48x0.1628 7x0.1266 1.0873 0.9992 1.357 1496 1198 298 80.06 19.94 26200 28000 Pheasant/ACSS 1272.0 54x0.1535 19x0.0921 1.1259 0.9993 1.381 1633 1204 429 73.71 26.29 34100 37300 Ringdove/ACSS 1351.5 42x0.1794 7x0.0997 1.1163 1.0617 1.376 1458 1273 185 87.31 12.69 19900 21200 Dipper/ACSS 1351.5 45x0.1733 7x0.1155 1.1348 1.0614 1.386 1521 1273 248 83.68 16.32 23700 25500 -none- 1351.5 48x0.1678 7x0.1305 1.1551 1.0614 1.398 1590 1273 317 80.06 19.94 27900 29700 Martin/ACSS 1351.5 54x0.1582 19x0.0949 1.1958 1.0614 1.424 1735 1279 456 73.72 26.28 36200 39600 Popinjay/ACSS 1431.0 42x0.1846 7x0.1026 1.1820 1.1241 1.415 1544 1348 196 87.31 12.69 21000 22500 Bobolink/ACSS 1431.0 45x0.1783 7x0.1189 1.2013 1.1236 1.426 1611 1348 263 83.67 16.33 25100 27000 Wagtail/ACSS 1431.0 48x0.1727 7x0.1343 1.2235 1.1244 1.439 1684 1348 336 80.06 19.94 29500 31500 Plover/ACSS 1431.0 54x0.1628 19x0.0977 1.2665 1.1241 1.465 1838 1354 483 73.71 26.29 38400 41900 Nuthatch/ACSS 1510.5 45x0.1832 7x0.1221 1.2682 1.1862 1.466 1700 1423 277 83.68 16.32 26500 28100 Parrot/ACSS 1510.5 54x0.1672 19x0.1003 1.3358 1.1856 1.505 1939 1430 509 73.74 26.26 40500 44200 Ratite/ACSS 1590.0 42x0.1946 7x0.1081 1.3134 1.2492 1.492 1715 1498 218 87.32 12.68 23400 25000 Lapwing/ACSS 1590.0 45x0.1880 7x0.1253 1.3355 1.2492 1.504 1790 1498 292 83.67 16.33 27900 29600 Hornbill/ACSS 1590.0 48x0.1820 7x0.1416 1.3590 1.2487 1.517 1871 1498 373 80.05 19.95 32200 34400 Falcon/ACSS 1590.0 54x0.1716 19x0.1030 1.4072 1.2489 1.545 2042 1505 537 73.70 26.30 42600 46600 Chukar/ACSS Seahawk/ACSS Mockingbird/ACSS Roadrunner/ACSS Bluebird/ACSS Kiwi/ACSS Thrasher/ACSS Joree/ACSS 1780.0 1869.0 2034.5 2057.5 2156.0 2167.0 2312.0 2515.0 1.3986 1.4681 1.5979 1.6152 1.6931 1.7022 1.8155 1.9750 35300 21500 27200 31700 42100 29000 35600 38700 38200 22700 28900 33900 45500 30800 38100 41400 84x0.1456 68x0.1658 72x0.1681 76x0.1645 84x0.1602 72x0.1735 76x0.1744 76x0.1819 19x0.0874 7x0.0921 7x0.1121 19x0.0768 19x0.0961 7x0.1157 19x0.0814 19x0.0849 1.5126 1.5148 1.6670 1.7033 1.8310 1.7758 1.9144 2.0826 1.602 1.603 1.681 1.700 1.762 1.735 1.802 1.880 2071 1918 2160 2246 2508 2300 2524 2745 1685 1760 1926 1947 2041 2051 2188 2380 387 158 234 299 467 249 335 365 81.33 91.77 89.17 86.71 81.36 89.17 86.71 86.71 18.67 8.23 10.83 13.29 18.64 10.83 13.29 13.29 31900 RMT 96.60 RMT 90.45 RMT 84.36 43000 RMT 96.60 RMT 90.45 23700 RMT 96.60 RMT 90.45 RM 68.38 28800 RMT 96.60 RMT 90.45 RM 68.38 33900 RMT 96.60 RMT 90.45 RMT 84.36 45600 RMT 96.60 RMT 90.45 25100 RMT 96.60 RMT 90.45 RM 68.38 30500 RMT 96.60 RMT 90.45 RM 68.38 35900 RMT 96.60 RMT 90.45 RMT 84.36 48300 RMT 96.60 RMT 90.45 31800 RMT 96.60 RMT 90.45 RM 68.38 51000 RMT 96.60 RMT 90.45 27900 RMT 96.60 RMT 90.45 RM 68.38 33500 RMT 96.60 RMT 90.45 RM 68.38 39400 RMT 96.60 RMT 90.45 RMT 84.36 53700 RMT 96.60 RMT 90.45 43900 RMT 96.60 24800 RMT 96.60 32000 RMT 96.60 38300 RMT 96.60 51700 RMT 96.60 34100 RMT 96.60 43000 RMT 96.60 46800 RMT 96.60 17950 11970 5985 19025 10975 14435 9630 4815 16140 10760 5380 17985 11995 6000 19015 10965 14435 9620 4810 16140 10755 5385 17995 12000 6000 19025 10975 16115 10745 5370 18990 10950 14405 9605 4800 16110 10740 5370 17960 11975 5985 19030 10965 19060 17345 16115 17520 18805 16100 17660 17295 12000 8000 4000 11650 6720 9880 6590 3295 10590 7060 3530 11290 7530 3765 10960 6320 9330 6220 3110 10000 6665 3335 10660 7110 3555 10350 5970 9480 6320 3160 9800 5650 8400 5600 2800 9000 6000 3000 9600 6400 3200 9320 5370 9200 9000 7460 7800 7500 7000 7000 6300 (1) Code words shown denote ACSS with regular-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA2). See the Options section to find the appropriate code word modifier designation for alternative design options. (2) Due to rounding, total values may be slightly greater or slightly less than the sum of the component values. (3) Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 110 3/2013 Electric Utility Overhead Conductors TransPowr ACSS Bare Overhead Conductor ® Aluminum Conductor Steel-Supported Concentric-Lay-Stranded ACSS, CONCENTRIC-LAY-STRANDED (ELECTRICAL PROPERTIES) STRANDING NO. X DIA. INCHES CROSS-SECTION SQ. INCHES AL STEEL TOTAL AL O.D. INCHES DC @ 20˚C RESISTANCE (4) OHMS/1000 FT AC AC @ 25˚C @ 75˚C AC @ 200˚C 75˚C GEOMETRIC INDUCTIVE MEAN REACTANCE RADIUS OHM/1000 FT 200˚C FT (6) Diver/ACSS 1272.0 48x0.1628 7x0.1266 1.0873 0.9992 1.357 0.0131 0.0140 0.0172 0.0246 1185 2160 0.0450 0.0713 0.4500 Pheasant/ACSS 1272.0 54x0.1535 19x0.0921 1.1259 0.9993 1.381 0.0131 0.0139 0.0171 0.0246 1190 2175 0.0464 0.0706 0.4471 Ringdove/ACSS 1351.5 42x0.1794 7x0.0997 1.1163 1.0617 1.376 0.0124 0.0134 0.0163 0.0234 1220 2225 0.0451 0.0712 0.4478 Dipper/ACSS 1351.5 45x0.1733 7x0.1155 1.1348 1.0614 1.386 0.0124 0.0133 0.0163 0.0233 1225 2235 0.0457 0.0709 0.4466 -none- 1351.5 48x0.1678 7x0.1305 1.1551 1.0614 1.398 0.0123 0.0133 0.0162 0.0232 1230 2245 0.0464 0.0706 0.4452 Martin/ACSS 1351.5 54x0.1582 19x0.0949 1.1958 1.0614 1.424 0.0123 0.0132 0.0161 0.0231 1235 2260 0.0478 0.0699 0.4424 Popinjay/ACSS 1431.0 42x0.1846 7x0.1026 1.1820 1.1241 1.415 0.0117 0.0127 0.0155 0.0221 1260 2310 0.0464 0.0706 0.4434 Bobolink/ACSS 1431.0 45x0.1783 7x0.1189 1.2013 1.1236 1.426 0.0117 0.0127 0.0154 0.0220 1265 2320 0.0470 0.0703 0.4421 Wagtail/ACSS 1431.0 48x0.1727 7x0.1343 1.2235 1.1244 1.439 0.0117 0.0126 0.0153 0.0219 1270 2330 0.0477 0.0699 0.4408 Plover/ACSS 1431.0 54x0.1628 19x0.0977 1.2665 1.1241 1.465 0.0117 0.0125 0.0153 0.0219 1280 2350 0.0492 0.0692 0.4379 Nuthatch/ACSS 1510.5 45x0.1832 7x0.1221 1.2682 1.1862 1.466 0.0111 0.0121 0.0147 0.0209 1310 2405 0.0483 0.0696 0.4379 Parrot/ACSS 1510.5 54x0.1672 19x0.1003 1.3358 1.1856 1.505 0.0110 0.0119 0.0145 0.0207 1325 2435 0.0505 0.0686 0.4337 Ratite/ACSS 1590.0 42x0.1946 7x0.1081 1.3134 1.2492 1.492 0.0105 0.0116 0.0140 0.0199 1340 2475 0.0489 0.0694 0.4351 Lapwing/ACSS 1590.0 45x0.1880 7x0.1253 1.3355 1.2492 1.504 0.0105 0.0115 0.0140 0.0199 1350 2485 0.0496 0.0690 0.4338 Hornbill/ACSS 1590.0 48x0.1820 7x0.1416 1.3590 1.2487 1.517 0.0105 0.0114 0.0139 0.0198 1355 2500 0.0503 0.0687 0.4325 Falcon/ACSS 1590.0 54x0.1716 19x0.1030 1.4072 1.2489 1.545 0.0105 0.0114 0.0138 0.0197 1365 2520 0.0519 0.0680 0.4297 Chukar/ACSS Seahawk/ACSS Mockingbird/ACSS Roadrunner/ACSS Bluebird/ACSS Kiwi/ACSS Thrasher/ACSS Joree/ACSS 1780.0 1869.0 2034.5 2057.5 2156.0 2167.0 2312.0 2515.0 19x0.0874 7x0.0921 7x0.1121 19x0.0768 19x0.0961 7x0.1157 19x0.0814 19x0.0849 1.5126 1.5148 1.6670 1.7033 1.8310 1.7758 1.9144 2.0826 1.3986 1.4681 1.5979 1.6152 1.6931 1.7022 1.8155 1.9750 1.602 1.603 1.681 1.700 1.762 1.735 1.802 1.880 0.0094 0.0090 0.0083 0.0082 0.0078 0.0078 0.0073 0.0067 0.0104 0.0101 0.0094 0.0093 0.0088 0.0090 0.0085 0.0079 0.0122 0.0119 0.0110 0.0108 0.0103 0.0104 0.0098 0.0092 0.0169 0.0163 0.0151 0.0149 0.0141 0.0142 0.0134 0.0124 1465 1490 1565 1580 1640 1620 1690 1765 2750 2805 2960 2995 3105 3080 3220 3390 0.0532 0.0523 0.0551 0.0560 0.0586 0.0569 0.0594 0.0619 0.0674 0.0678 0.0666 0.0662 0.0652 0.0659 0.0649 0.0639 0.4240 0.4239 0.4164 0.4146 0.4090 0.4115 0.4055 0.3989 SIZE AWG OR kcmil CODE WORD (1) 84x0.1456 68x0.1658 72x0.1681 76x0.1645 84x0.1602 72x0.1735 76x0.1744 76x0.1819 AMPACITY (5) CAPACITIVE REACTANCE MEGAOHM 1000 FT (6) (1) Code words shown denote ACSS with regular-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA2). See the Options section to find the appropriate code word modifier designation for alternative design options. (4) Based on a conductivity of 61.2% (minimum lot average) IACS at 20˚C for aluminum and 8% IACS at 20˚C for the steel core. AC resistance for single-layer and three-layer designs approximates the effects of core magnetization. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by 3.281. (5) Based on the given conductor temperature at 60 Hz and the following conditions: 25˚C ambient temperature, 2 ft/sec crosswind (90˚ to conductor), 0.5 coefficient of emissivity, 0.5 coefficient of absorbtivity, 30˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 96.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (6) Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius. 3/2013 111 Overhead Conductors Notes 112 Electric Utility Electric Utility Overhead Conductors TransPowr ACSS/TW Bare Overhead Conductor ® Trapezoidal Aluminum Conductor Steel-Supported Concentric-Lay-Stranded 18/7 20/7 36/19 21/7 38/19 Product Construction: Complete Conductor: TransPowr® ACSS/TW is a trapezoidal aluminum conductor steel-supported concentric-lay-stranded conductor. The aluminum strands are trapezoidal in shape. The wedge-shaped aluminum strands enable a more compact alignment of the aluminum wires. Conductor designs that maintain the same circular mil cross-sectional area of aluminum as a conventional round conductor result in a TW conductor that is 10 to 15 percent smaller in overall diameter. Conductor designs that maintain the same overall diameter as a conventional round conductor result in a TW conductor that has 20 to 25 percent more aluminum cross-sectional area packed in. The ACSS/TW conductors are manufactured in accordance with the requirements of the latest issue of ASTM B857. The steel strands form the central core of the conductor, around which is stranded two, three or four layers of aluminum 1350 O temper (annealed) wires. The steel core may consist of a concentric stranded cable of 7, 19 or more wires. Numerous combinations of aluminum and steel strands and layers are possible. The sizes and constructions listed on the following pages are common examples used in overhead lines. Standard ACSS/TW designs are manufactured with regular-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA2). 3/2013 22/7 39/19 36/7 64/19 Features and Benefits: TransPowr® ACSS/TW conductors are similar to conventional ACSR/TW conductors but have some very important additional advantages. ACSS/TW conductors can operate continuously at high temperatures (up to 250°C) without damage. ACSS sags less than ACSR/TW under emergency electrical loadings, it has self-damping properties, and its final sags are not affected by long-term creep of the aluminum. ACSS/TW conductors constructed of equivalent aluminum circular mil cross-sectional area provide a conductor that is smaller in overall diameter than the equivalent conventional round wire ACSS conductor. The reduced conductor diameter is advantageous in reducing the effects of ice and wind loading on the conductor. ACSS/TW conductors constructed to equivalent overall diameter enable a greater circular mil cross-sectional area of aluminum within the conductor, allowing a significant increase in conductor current-carrying capacity. Applications: Trapezoidal Aluminum Conductors Steel-Supported (ACSS/TW) are used for overhead transmission lines. They are especially useful in reconductoring applications requiring increased current with existing tensions and clearances; new line applications where structures can be economized due to reduced sag; new line applications requiring high emergency loadings; and lines where aeolian vibration is a problem. Electrical Parameters: The electrical parameters for the trapezoidal ACSS equivalent circular mil area and equivalent overall diameter conductors may be found in the last table of this section. Options: • High-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA3 to ASTM B803) • Extra-high-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA4 to ASTM B958) • Ultra-high-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA5 to ASTM B958) • Aluminum-clad steel core (/AW) • 250°C operating temperature rating utilizing either the zinc-5% aluminum mischmetal alloycoated steel core wires or the aluminum-clad steel core wires • Non-specular surface finish (/NS) At the present time, CAN/CSA C61089 does not recognize ACSS/TW conductor designs. The information provided on the following pages is from our US catalog. For other conductor sizes, designs and/or specific installation requirements not shown in the tables, contact your General Cable sales representative or e-mail infoca@generalcable.com. 113 Overhead Conductors Electric Utility TransPowr ACSS/TW Bare Overhead Conductor ® Trapezoidal Aluminum Conductor Steel-Supported Concentric-Lay-Stranded ACSS/TW (MECHANICAL PROPERTIES) – REDUCED DIAMETER CONDUCTORS SIZED TO HAVE EQUIVALENT CIRCULAR MIL AREA TO REGULAR ACSS CODE WORD (1) CROSS-SECTION APPROX. WEIGHT PERCENT RATED STRENGTH SQ. INCHES LB/1000 FT (2) BY MASS LBS STANDARD PACKAGES (3) STEEL SIZE EQUIVALENT STEEL CORE CORE GA2 GA3 OR GA5 OR AWG OR NO. AL FILL AL DIA. NO. X DIA. O.D. O.D. OR MA3 MA5 REEL WEIGHT LENGTH kcmil TYPE WIRES FACTOR INCHES INCHES INCHES TOTAL AL INCHES TOTAL AL STEEL AL STEEL MA2 (HS) (UHS) DESIG. LBS FEET Oriole/ ACSS/TW 336.4 23 17 88.7 0.1407 7x0.1059 0.3177 0.3258 0.2642 0.69 Flicker/ ACSS/TW 477.0 13 18 91.3 0.1628 7x0.0940 0.2820 0.4234 0.3748 0.78 Hawk/ ACSS/TW 477.0 16 18 91.3 0.1628 7x0.1053 0.3159 0.4355 0.3745 0.79 Hen/ ACSS/TW 477.0 23 16 88.7 0.1727 7x0.1261 0.3783 0.4620 0.3746 0.83 Parakeet/ ACSS/TW 556.5 13 18 92.0 0.1758 7x0.1015 0.3045 0.4938 0.4372 0.84 Dove/ ACSS/TW 556.5 16 20 91.8 0.1668 7x0.1138 0.3414 0.5083 0.4371 0.85 Rook/ ACSS/TW 636.0 13 18 92.6 0.1880 7x0.1085 0.3255 0.5641 0.4994 0.89 Grosbeak/ ACSS/TW 636.0 16 20 92.0 0.1783 7x0.1216 0.3648 0.5809 0.4996 0.91 Tern/ ACSS/TW 795.0 7 17 93.5 0.2163 7x0.0888 0.2664 0.6680 0.6247 0.96 Puffin/ ACSS/TW 795.0 11 21 93.5 0.1945 7x0.1108 0.3324 0.6916 0.6241 0.98 Condor/ ACSS/TW 795.0 13 21 93.0 0.1945 7x0.1213 0.3639 0.7051 0.6242 0.99 Drake/ ACSS/TW 795.0 16 20 93.1 0.1993 7x0.1360 0.4080 0.7259 0.6242 1.01 Mallard/ ACSS/TW 795.0 23 22 93.0 0.1901 19x0.0977 0.4885 0.7668 0.6244 1.05 Phoenix/ ACSS/TW 954.0 5 30 92.9 0.1784 7x0.0837 0.2511 0.7882 0.7497 1.04 Rail/ ACSS/TW 954.0 7 33 92.2 0.1700 7x0.0971 0.2913 0.8011 0.7493 1.06 Cardinal/ ACSS/TW 954.0 13 21 93.9 0.2131 7x0.1329 0.3987 0.8463 0.7492 1.08 Snowbird/ ACSS/TW 1033.5 5 30 92.5 0.1856 7x0.0871 0.2613 0.8532 0.8115 1.09 Ortolan/ ACSS/TW 1033.5 7 33 92.3 0.1769 7x0.1010 0.3030 0.8673 0.8112 1.10 Curlew/ ACSS/TW 1033.5 13 21 93.7 0.2219 7x0.1383 0.4149 0.9170 0.8118 1.13 Avocet/ ACSS/TW 1113.0 5 30 93.0 0.1926 7x0.0904 0.2712 0.9186 0.8737 1.13 Bluejay/ ACSS/TW 1113.0 7 33 92.7 0.1837 7x0.1049 0.3147 0.9351 0.8746 1.14 Finch/ ACSS/TW 1113.0 13 39 91.9 0.1689 19x0.0862 0.4310 0.9845 0.8737 1.18 Oxbird/ ACSS/TW 1192.5 5 30 93.2 0.1993 7x0.0936 0.2808 0.9843 0.9361 1.17 526 318 209 60.34 39.66 14800 16300 19100 RMT 84.36 NR 60.28 612 448 164 73.14 26.86 13000 14200 16400 RM 84.36 NR 60.28 655 448 206 68.47 31.53 15600 17100 19800 RMT 84.36 NR 60.28 746 450 296 60.34 39.66 21000 22700 26700 RM 68.38 NR 60.28 714 522 192 73.15 26.85 15200 16600 19100 RM 68.38 NR 60.28 764 523 241 68.45 31.55 18200 19900 23100 RMT 84.36 NR 60.28 816 597 219 73.15 26.85 17300 19000 21900 RM 68.38 NR 60.28 873 598 275 68.47 31.53 20700 22400 26000 RMT 84.36 NR 66.28 892 745 147 83.54 16.46 14200 15300 17500 RM 68.38 NR 60.28 974 746 229 76.55 23.45 18900 20600 23700 RMT 84.36 NR 60.28 1020 746 274 73.15 26.85 21700 23300 26900 RMT 84.36 NR 60.28 1091 747 344 68.45 31.55 25900 28000 32500 RMT 84.36 NR 60.28 1234 751 483 60.84 39.16 34300 37900 44300 RMT 84.36 NR 60.28 1028 898 130 87.32 12.68 14200 15200 17100 RMT 84.45 NR 66.28 1074 899 175 83.66 16.34 16700 18000 20400 RMT 84.45 RM 68.38 1224 895 329 73.15 26.85 26000 28000 32300 RMT 84.36 NR 60.28 1114 972 141 87.32 12.68 15400 16400 18500 RMT 84.45 RM 66.32 1163 973 190 83.68 16.32 18100 19500 22000 RMT 84.45 RM 68.38 1326 970 356 73.15 26.85 28200 30300 35000 RMT 84.36 NR 60.28 1199 1047 152 87.32 12.68 16300 17500 19500 RMT 84.36 RM 66.32 1253 1048 205 83.66 16.34 19500 21100 23800 RMT 84.45 RM 68.38 1427 1051 376 73.64 26.36 30400 33200 38700 RMT 90.45 RMT 84.36 1285 1122 163 87.31 12.69 17500 18700 20900 RMT 84.36 RM 66.32 7743 4276 6765 4506 7233 3620 7288 3648 6770 3385 8036 4018 6766 3387 8030 4015 5601 2801 7542 3771 7896 3948 8042 4016 9946 3973 9448 4729 10848 5424 7896 3942 9455 4722 10842 5421 7890 3952 9439 4726 10840 5426 14556 7278 9446 4717 14720 8130 11050 7360 11050 5530 9770 4890 9480 4740 10520 5260 8290 4150 9200 4600 6280 3140 7740 3870 7740 3870 7370 3680 8060 3220 9190 4600 10100 5050 6450 3220 8490 4240 9320 4660 5950 2980 7870 3940 8650 4330 10200 5100 7350 3670 (1) Code words shown denote ACSS/TW with regular-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA2). See the Options section to find the appropriate code word modifier designation for alternative design options. (2) Due to rounding, total values may be slightly greater or slightly less than the sum of the component values. (3) Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 114 3/2013 Electric Utility Overhead Conductors TransPowr ACSS/TW Bare Overhead Conductor ® Trapezoidal Aluminum Conductor Steel-Supported Concentric-Lay-Stranded ACSS/TW (ELECTRICAL PROPERTIES) – REDUCED DIAMETER CONDUCTORS SIZED TO HAVE EQUIVALENT CIRCULAR MIL AREA TO REGULAR ACSS CODE WORD (1) CROSS-SECTION RESISTANCE (4) STEEL SQ. INCHES OHMS/1000 FT AMPACITY (5) GEOMETRIC INDUCTIVE CAPACITIVE SIZE EQUIVALENT STEEL CORE CORE MEAN REACTANCE REACTANCE AWG OR NO. AL FILL AL DIA. NO. X DIA. O.D. O.D. DC AC AC AC RADIUS OHM/1000 FT MEGAOHM kcmil TYPE WIRES FACTOR INCHES INCHES INCHES TOTAL AL INCHES @ 20˚C @ 25˚C @ 75˚C @ 200˚C 75˚C 200˚C FT (6) 1000 FT (6) Oriole/ ACSS/TW 336.4 23 17 88.7 0.1407 7x0.1059 0.3177 0.3258 0.2642 0.69 0.0488 0.0499 0.0600 0.0851 530 940 0.0236 0.0861 0.5552 Flicker/ ACSS/TW 477.0 13 18 91.3 0.1628 7x0.0940 0.2820 0.4234 0.3748 0.78 0.0347 0.0356 0.0427 0.0606 650 1150 0.0259 0.0839 0.5375 Hawk/ ACSS/TW 477.0 16 18 91.3 0.1628 7x0.1053 0.3159 0.4355 0.3745 0.79 0.0346 0.0354 0.0426 0.0604 650 1160 0.0266 0.0834 0.5349 Hen/ ACSS/TW 477.0 23 16 88.7 0.1727 7x0.1261 0.3783 0.4620 0.3746 0.83 0.0344 0.0352 0.0423 0.0601 660 1180 0.0280 0.0822 0.5278 Parakeet/ ACSS/TW 556.5 13 18 92.0 0.1758 7x0.1015 0.3045 0.4938 0.4372 0.84 0.0297 0.0305 0.0367 0.0520 715 1270 0.0279 0.0822 0.5259 Dove/ ACSS/TW 556.5 16 20 91.8 0.1668 7x0.1138 0.3414 0.5083 0.4371 0.85 0.0296 0.0304 0.0365 0.0518 720 1280 0.0287 0.0816 0.5232 Rook/ ACSS/TW 636.0 13 18 92.6 0.1880 7x0.1085 0.3255 0.5641 0.4994 0.89 0.0260 0.0268 0.0321 0.0455 775 1385 0.0298 0.0808 0.5159 Grosbeak/ ACSS/TW 636.0 16 20 92.0 0.1783 7x0.1216 0.3648 0.5809 0.4996 0.91 0.0259 0.0267 0.0320 0.0453 780 1400 0.0307 0.0801 0.5129 Tern/ ACSS/TW 795.0 7 17 93.5 0.2163 7x0.0888 0.2664 0.6680 0.6247 0.96 0.0209 0.0217 0.0260 0.0368 880 1580 0.0315 0.0795 0.5042 Puffin/ ACSS/TW 795.0 11 21 93.5 0.1945 7x0.1108 0.3324 0.6916 0.6241 0.98 0.0209 0.0216 0.0259 0.0366 885 1595 0.0327 0.0786 0.5009 Condor/ ACSS/TW 795.0 13 21 93.0 0.1945 7x0.1213 0.3639 0.7051 0.6242 0.99 0.0208 0.0215 0.0258 0.0365 890 1605 0.0333 0.0782 0.4987 Drake/ ACSS/TW 795.0 16 20 93.1 0.1993 7x0.1360 0.4080 0.7259 0.6242 1.01 0.0207 0.0214 0.0257 0.0363 895 1615 0.0342 0.0776 0.4962 Mallard/ ACSS/TW 795.0 23 22 93.0 0.1901 19x0.0977 0.4885 0.7668 0.6244 1.05 0.0207 0.0213 0.0255 0.0361 905 1640 0.0360 0.0764 0.4907 Phoenix/ ACSS/TW 954.0 5 30 92.9 0.1784 7x0.0837 0.2511 0.7882 0.7497 1.04 0.0176 0.0185 0.0228 0.0329 960 1715 0.0343 0.0775 0.4910 Rail/ ACSS/TW 954.0 7 33 92.2 0.1700 7x0.0971 0.2913 0.8011 0.7493 1.06 0.0175 0.0184 0.0227 0.0328 965 1725 0.0350 0.0771 0.4889 Cardinal/ ACSS/TW 954.0 13 21 93.9 0.2131 7x0.1329 0.3987 0.8463 0.7492 1.08 0.0173 0.0180 0.0216 0.0305 995 1805 0.0364 0.0762 0.4851 Snowbird/ ACSS/TW 1033.5 5 30 92.5 0.1856 7x0.0871 0.2613 0.8532 0.8115 1.09 0.0162 0.0171 0.0211 0.0304 1010 1810 0.0357 0.0766 0.4844 Ortolan/ ACSS/TW 1033.5 7 33 92.3 0.1769 7x0.1010 0.3030 0.8673 0.8112 1.10 0.0162 0.0171 0.0210 0.0303 1015 1820 0.0364 0.0762 0.4827 Curlew/ ACSS/TW 1033.5 13 21 93.7 0.2219 7x0.1383 0.4149 0.9170 0.8118 1.13 0.0160 0.0167 0.0199 0.0281 1045 1905 0.0379 0.0752 0.4787 Avocet/ ACSS/TW 1113.0 5 30 93.0 0.1926 7x0.0904 0.2712 0.9186 0.8737 1.13 0.0150 0.0160 0.0196 0.0282 1055 1900 0.0370 0.0758 0.4790 Bluejay/ ACSS/TW 1113.0 7 33 92.7 0.1837 7x0.1049 0.3147 0.9351 0.8746 1.14 0.0150 0.0159 0.0195 0.0282 1060 1910 0.0377 0.0753 0.4772 Finch/ ACSS/TW 1113.0 13 39 91.9 0.1689 19x0.0862 0.4310 0.9845 0.8737 1.18 0.0150 0.0157 0.0194 0.0279 1075 1935 0.0399 0.0740 0.4716 Oxbird/ ACSS/TW 1192.5 30 93.2 0.1993 0.0750 0.4738 5 7x0.0936 0.2808 0.9843 0.9361 1.17 0.0140 0.0150 0.0183 0.0263 1100 1985 0.0382 (1) Code words shown denote ACSS/TW with regular-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA2). See the Options section to find the appropriate code word modifier designation for alternative design options. (4) Based on a conductivity of 61.2% (minimum lot average) IACS at 20˚C for aluminum and 8% IACS at 20˚C for the steel core. AC resistance for single-layer and three-layer designs approximates the effects of core magnetization. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by 3.281. (5) Based on the given conductor temperature at 60 Hz and the following conditions: 25˚C ambient temperature, 2 ft/sec crosswind (90˚ to conductor), 0.5 coefficient of emissivity, 0.5 coefficient of absorbtivity, 30˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 96.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (6) Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm). To convert the Geometric Mean Radius (GMR) to cm, divide the value by 0.03821. To convert inductive reactance to ohm/km, multiply the value by 3.281. To convert capacitive reactance to ohm/km, divide the value by 3.281. 3/2013 115 Overhead Conductors Electric Utility TransPowr ACSS/TW Bare Overhead Conductor ® Trapezoidal Aluminum Conductor Steel-Supported Concentric-Lay-Stranded ACSS/TW (MECHANICAL PROPERTIES) – REDUCED DIAMETER CONDUCTORS SIZED TO HAVE EQUIVALENT CIRCULAR MIL AREA TO REGULAR ACSS CODE WORD (1) CROSS-SECTION APPROX. WEIGHT PERCENT RATED STRENGTH SQ. INCHES LB/1000 FT (2) BY MASS LBS STEEL SIZE EQUIVALENT STEEL CORE CORE GA2 GA3 OR GA5 OR AWG OR NO. AL FILL AL DIA. NO. X DIA. O.D. O.D. OR MA3 MA5 kcmil TYPE WIRES FACTOR INCHES INCHES INCHES TOTAL AL INCHES TOTAL AL STEEL AL STEEL MA2 (HS) (UHS) Bunting/ ACSS/TW 1192.5 7 33 93.0 0.1901 Grackle/ ACSS/TW 1192.5 13 39 92.3 0.1749 Scissortail/ ACSS/TW 1272.0 5 30 93.6 0.2059 Bittern/ ACSS/TW 1272.0 7 33 93.3 0.1964 Pheasant/ ACSS/TW 1272.0 13 39 93.0 0.1806 Dipper/ ACSS/TW 1351.5 7 33 93.5 0.2024 Martin/ ACSS/TW 1351.5 13 39 93.0 0.1861 Bobolink/ ACSS/TW 1431.0 7 33 93.0 0.2083 Plover/ ACSS/TW 1431.0 13 39 93.0 0.1916 Lapwing/ ACSS/TW 1590.0 7 36 93.0 0.2102 Falcon/ ACSS/TW 1590.0 13 42 93.5 0.1946 Chukar/ ACSS/TW 1780.0 8 38 93.5 0.2164 Bluebird/ ACSS/TW 2156.0 8 64 91.0 0.1835 STANDARD PACKAGES (3) REEL DESIG. 7x0.1086 0.3258 1.0016 0.9368 1.18 1343 1123 220 83.65 16.35 20900 22600 25500 RMT 84.45 RM 68.38 19x0.0892 0.4460 1.0556 0.9369 1.22 1529 1126 403 73.65 26.35 32600 35500 41500 RMT 90.45 RM 72.36 7x0.0967 0.2901 1.0508 0.9994 1.20 1371 1197 174 87.30 12.70 18700 20000 22300 RMT 84.36 RM 66.32 7x0.1121 0.3363 1.0685 0.9994 1.22 1432 1198 234 83.67 16.33 22300 24000 27200 RMT 84.45 RM 68.38 19x0.0921 0.4605 1.1252 0.9987 1.26 1630 1201 429 73.66 26.34 34100 37300 43000 RMT 90.45 RM 72.36 7x0.1155 0.3465 1.1350 1.0616 1.25 1521 1273 248 83.68 16.32 23700 25500 28800 RMT 84.45 RM 68.38 19x0.0949 0.4745 1.1954 1.0610 1.30 1732 1276 456 73.68 26.32 36200 39600 45600 RMT 90.45 RM 72.36 7x0.1189 0.3567 1.2020 1.1243 1.29 1611 1348 263 83.67 16.33 25100 27100 30500 RMT 84.45 RM 68.38 19x0.0977 0.4885 1.2666 1.1242 1.33 1834 1351 483 73.66 26.34 38400 41900 48300 RMT 90.45 RM 72.36 7x0.1253 0.3759 1.3351 1.2488 1.36 1790 1498 292 83.67 16.33 27900 29600 33500 RMT 84.45 RM 68.38 19x0.1030 0.5150 1.4066 1.2483 1.40 2038 1501 537 73.65 26.35 42600 46600 53700 RMT 90.45 RMT 84.36 19x0.0874 0.4370 1.5122 1.3982 1.45 2061 1674 387 81.24 18.76 35300 38200 43900 RMT 90.45 RM 68.38 19x0.0961 0.4805 1.8312 1.6934 1.61 2512 2045 467 81.39 18.61 42100 45500 51700 RMT 96.60 RMT 84.45 WEIGHT LENGTH LBS FEET 10849 5425 14569 7277 9460 4730 10854 5427 14559 7272 10847 5416 14548 7274 10842 5413 14565 7282 11831 5906 15674 7827 12859 6430 21629 10802 8080 4040 9530 4760 6900 3450 7580 3790 8930 4460 7130 3560 8400 4200 6730 3360 7940 3970 6610 3300 7690 3840 6240 3120 8610 4300 ACSS/TW (MECHANICAL PROPERTIES) – EQUIVALENT DIAMETER CONDUCTORS SIZED TO HAVE EQUIVALENT DIAMETER TO REGULAR ACSS CODE WORD (1) CROSS-SECTION APPROX. WEIGHT PERCENT RATED STRENGTH SQ. INCHES LB/1000 FT (2) BY MASS LBS STEEL SIZE EQUIVALENT STEEL CORE CORE GA2 GA3 OR GA5 OR AWG OR NO. AL FILL AL DIA. NO. X DIA. O.D. O.D. OR MA3 MA5 kcmil TYPE WIRES FACTOR INCHES INCHES INCHES TOTAL AL INCHES TOTAL AL STEEL AL STEEL MA2 (HS) (UHS) Calument/ ACSS/TW 565.3 16 20 91.5 0.1681 7x0.1146 0.3438 0.5161 0.4438 0.86 Mohawk/ ACSS/TW 571.7 13 18 92.2 0.1782 7x0.1030 0.3090 0.5072 0.4489 0.85 Oswego/ ACSS/TW 664.8 16 20 92.3 0.1823 7x0.1244 0.3732 0.6073 0.5222 0.93 Mystic/ ACSS/TW 666.6 13 20 92.3 0.1826 7x0.1111 0.3333 0.5915 0.5236 0.91 Wabash/ ACSS/TW 762.8 16 20 92.9 0.1953 7x0.1331 0.3993 0.6963 0.5989 0.99 Maumee/ ACSS/TW 768.2 13 20 93.0 0.1960 7x0.1195 0.3585 0.6817 0.6032 0.98 Kettle/ ACSS/TW 957.2 7 33 92.2 0.1703 7x0.0973 0.2919 0.8038 0.7518 1.06 Suwanee/ ACSS/TW 959.6 16 22 93.4 0.2089 7x0.1493 0.4479 0.8764 0.7539 1.11 STANDARD PACKAGES (3) REEL DESIG. 776 531 244 68.48 31.52 18400 20200 23500 RMT 84.36 NR 60.28 734 537 197 73.10 26.90 15600 17100 19700 RM 66.38 NR 60.28 913 625 288 68.44 31.56 21700 23400 27200 RMT 84.36 NR 60.28 855 626 230 73.14 26.86 18200 19900 22900 RMT 84.36 NR 60.28 1046 717 330 68.49 31.51 24900 26800 31200 RMT 84.36 NR 60.28 987 721 266 73.07 26.93 21000 23000 26500 RMT 84.36 NR 60.28 1078 902 176 83.65 16.35 16800 18100 20400 RMT 84.45 RM 68.38 1317 902 415 68.49 31.51 30700 33100 38600 RMT 84.36 RM 66.32 WEIGHT LENGTH LBS FEET 8027 10350 4010 5170 6768 9220 3384 4610 8032 8800 4016 4400 7519 8790 3755 4390 8026 7670 4008 3830 7520 7620 3760 3810 10843 10060 5421 5030 8834 6710 4410 3350 (1) Code words shown denote ACSS/TW with regular-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA2). See the Options section to find the appropriate code word modifier designation for alternative design options. (2) Due to rounding, total values may be slightly greater or slightly less than the sum of the component values. (3) Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 116 3/2013 Electric Utility Overhead Conductors TransPowr ACSS/TW Bare Overhead Conductor ® Trapezoidal Aluminum Conductor Steel-Supported Concentric-Lay-Stranded ACSS/TW (ELECTRICAL PROPERTIES) – REDUCED DIAMETER CONDUCTORS SIZED TO HAVE EQUIVALENT CIRCULAR MIL AREA TO REGULAR ACSS CODE WORD (1) CROSS-SECTION RESISTANCE (4) SQ. INCHES OHMS/1000 FT AMPACITY (5) GEOMETRIC INDUCTIVE CAPACITIVE STEEL SIZE EQUIVALENT STEEL CORE CORE MEAN REACTANCE REACTANCE AWG OR NO. AL FILL AL DIA. NO. X DIA. O.D. O.D. DC AC AC AC RADIUS OHM/1000 FT MEGAOHM kcmil TYPE WIRES FACTOR INCHES INCHES INCHES TOTAL AL INCHES @ 20˚C @ 25˚C @ 75˚C @ 200˚C 75˚C 200˚C FT (6) 1000 FT (6) Bunting/ ACSS/TW 1192.5 7 33 93.0 0.1901 7x0.1086 0.3258 1.0016 0.9368 1.18 0.0140 0.0149 0.0183 0.0263 1105 1995 0.0390 0.0746 0.4720 Grackle/ ACSS/TW 1192.5 13 39 92.3 0.1749 19x0.0892 0.4460 1.0556 0.9369 1.22 0.0140 0.0147 0.0181 0.0261 1120 2025 0.0412 0.0733 0.4665 Scissortail/ ACSS/TW 1272.0 5 30 93.6 0.2059 7x0.0967 0.2901 1.0508 0.9994 1.20 0.0132 0.0141 0.0172 0.0247 1145 2070 0.0394 0.0743 0.4690 Bittern/ ACSS/TW 1272.0 7 33 93.3 0.1964 7x0.1121 0.3363 1.0685 0.9994 1.22 0.0131 0.0141 0.0172 0.0247 1150 2080 0.0402 0.0739 0.4672 Pheasant/ ACSS/TW 1272.0 13 39 93.0 0.1806 19x0.0921 0.4605 1.1252 0.9987 1.26 0.0131 0.0139 0.0170 0.0245 1165 2115 0.0424 0.0726 0.4619 Dipper/ ACSS/TW 1351.5 7 33 93.5 0.2024 7x0.1155 0.3465 1.1350 1.0616 1.25 0.0124 0.0133 0.0162 0.0232 1190 2165 0.0414 0.0732 0.4626 Martin/ ACSS/TW 1351.5 13 39 93.0 0.1861 19x0.0949 0.4745 1.1954 1.0610 1.30 0.0123 0.0131 0.0160 0.0230 1210 2200 0.0437 0.0719 0.4572 Bobolink/ ACSS/TW 1431.0 7 33 93.0 0.2083 7x0.1189 0.3567 1.2020 1.1243 1.29 0.0117 0.0126 0.0154 0.0220 1235 2250 0.0427 0.0725 0.4578 Plover/ ACSS/TW 1431.0 13 39 93.0 0.1916 19x0.0977 0.4885 1.2666 1.1242 1.33 0.0116 0.0124 0.0152 0.0218 1255 2285 0.0450 0.0713 0.4527 Lapwing/ ACSS/TW 1590.0 7 36 93.0 0.2102 7x0.1253 0.3759 1.3351 1.2488 1.36 0.0105 0.0115 0.0139 0.0198 1315 2410 0.0450 0.0712 0.4495 Falcon/ ACSS/TW 1590.0 13 42 93.5 0.1946 19x0.1030 0.5150 1.4066 1.2483 1.40 0.0105 0.0113 0.0137 0.0196 1335 2445 0.0474 0.0701 0.4448 Chukar/ ACSS/TW 1780.0 8 38 93.5 0.2164 19x0.0874 0.4370 1.5122 1.3982 1.45 0.00937 0.0103 0.0125 0.0177 1415 2605 0.0482 0.0697 0.4398 Bluebird/ ACSS/TW 2156.0 8 64 91.0 0.1835 19x0.0961 0.4805 1.8312 1.6934 1.61 0.00780 0.00879 0.0103 0.0141 1600 3015 0.0538 0.0671 0.4229 ACSS/TW (ELECTRICAL PROPERTIES) – EQUIVALENT DIAMETER CONDUCTORS SIZED TO HAVE EQUIVALENT DIAMETER TO REGULAR ACSS CODE WORD (1) CROSS-SECTION RESISTANCE (4) SQ. INCHES OHMS/1000 FT AMPACITY (5) GEOMETRIC INDUCTIVE CAPACITIVE STEEL SIZE EQUIVALENT STEEL CORE CORE MEAN REACTANCE REACTANCE AWG OR NO. AL FILL AL DIA. NO. X DIA. O.D. O.D. DC AC AC AC RADIUS OHM/1000 FT MEGAOHM kcmil TYPE WIRES FACTOR INCHES INCHES INCHES TOTAL AL INCHES @ 20˚C @ 25˚C @ 75˚C @ 200˚C 75˚C 200˚C FT (6) 1000 FT (6) Calument/ ACSS/TW 565.3 16 20 91.5 0.1681 7x0.1146 0.3438 0.5161 0.4438 0.86 0.0292 0.0299 0.0359 0.0510 725 1295 0.0290 0.0814 0.5217 Mohawk/ ACSS/TW 571.7 13 18 92.2 0.1782 7x0.1030 0.3090 0.5072 0.4489 0.85 0.0289 0.0297 0.0357 0.0506 725 1295 0.0283 0.0820 0.5239 Oswego/ ACSS/TW 664.8 16 20 92.3 0.1823 7x0.1244 0.3732 0.6073 0.5222 0.93 0.0248 0.0255 0.0306 0.0434 800 1440 0.0313 0.0796 0.5096 Mystic/ ACSS/TW 666.6 13 20 92.3 0.1826 7x0.1111 0.3333 0.5915 0.5236 0.91 0.0248 0.0256 0.0307 0.0434 800 1430 0.0306 0.0801 0.5120 Wabash/ ACSS/TW 762.8 16 20 92.9 0.1953 7x0.1331 0.3993 0.6963 0.5989 0.99 0.0216 0.0223 0.0267 0.0378 875 1575 0.0335 0.0781 0.4993 Maumee/ ACSS/TW 768.2 13 20 93.0 0.1960 7x0.1195 0.3585 0.6817 0.6032 0.98 0.0215 0.0222 0.0267 0.0377 870 1570 0.0328 0.0786 0.5014 Kettle/ ACSS/TW 957.2 7 33 92.2 0.1703 7x0.0973 0.2919 0.8038 0.7518 1.06 0.0175 0.0184 0.0226 0.0327 965 1730 0.0350 0.0770 0.4886 Suwanee/ ACSS/TW 959.6 16 22 93.4 0.2089 7x0.1493 0.4479 0.8764 0.7539 1.11 0.0172 0.0178 0.0213 0.0301 1005 1825 0.0376 0.0754 0.4817 (1) Code words shown denote ACSS/TW with regular-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA2). See the Options section to find the appropriate code word modifier designation for alternative design options. (4) Based on a conductivity of 61.2% (minimum lot average) IACS at 20˚C for aluminum and 8% IACS at 20˚C for the steel core. AC resistance for single-layer and three-layer designs approximates the effects of core magnetization. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by 3.281. (5) Based on the given conductor temperature at 60 Hz and the following conditions: 25˚C ambient temperature, 2 ft/sec crosswind (90˚ to conductor), 0.5 coefficient of emissivity, 0.5 coefficient of absorbtivity, 30˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 96.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (6) Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm). To convert the Geometric Mean Radius (GMR) to cm, divide the value by 0.03821. To convert inductive reactance to ohm/km, multiply the value by 3.281. To convert capacitive reactance to ohm/km, divide the value by 3.281. 3/2013 117 Overhead Conductors Electric Utility TransPowr ACSS/TW Bare Overhead Conductor ® Trapezoidal Aluminum Conductor Steel-Supported Concentric-Lay-Stranded ACSS/TW (MECHANICAL PROPERTIES) – EQUIVALENT DIAMETER CONDUCTORS SIZED TO HAVE EQUIVALENT DIAMETER TO REGULAR ACSS CODE WORD (1) CROSS-SECTION APPROX. WEIGHT PERCENT RATED STRENGTH SQ. INCHES LB/1000 FT (2) BY MASS LBS STEEL SIZE EQUIVALENT STEEL CORE CORE GA2 GA3 OR GA5 OR AWG OR NO. AL FILL AL DIA. NO. X DIA. O.D. O.D. OR MA3 MA5 kcmil TYPE WIRES FACTOR INCHES INCHES INCHES TOTAL AL INCHES TOTAL AL STEEL AL STEEL MA2 (HS) (UHS) Columbia/ ACSS/TW 966.2 13 21 93.6 0.2145 Genesee/ ACSS/TW 1158.0 7 33 92.5 0.1873 Hudson/ ACSS/TW 1158.4 13 26 93.7 0.2111 Cheyenne/ ACSS/TW 1168.1 5 30 92.9 0.1973 Yukon/ ACSS/TW 1233.6 13 39 91.0 0.1778 Nelson/ ACSS/TW 1257.1 7 35 92.4 0.1895 Catawba/ ACSS/TW 1272.0 5 30 93.3 0.2059 Thames/ ACSS/TW 1334.6 13 39 92.6 0.1850 Mackenzie/ 1359.7 ACSS/TW 7 36 92.9 0.1943 Truckee/ ACSS/TW 5 30 93.6 0.2139 Merrimack/ 1433.6 13 ACSS/TW 39 92.1 0.1917 Miramichi/ ACSS/TW 1455.3 7 36 93.4 0.2010 St. Croix/ ACSS/TW 1467.8 5 30 93.4 0.2212 Rio Grande/ 1533.3 13 ACSS/TW 39 93.2 0.1983 Potomac/ ACSS/TW 1557.4 7 36 93.2 0.2080 Platte/ ACSS/TW 1569.0 5 33 93.7 0.2181 Pecos/ ACSS/TW 1622.0 13 39 93.0 0.2039 Schuylkill/ ACSS/TW 1657.4 7 36 93.5 0.2145 James/ ACSS/TW 1730.6 13 39 92.5 0.2107 Pee Dee/ ACSS/TW 1758.6 7 37 93.1 0.2180 Cumberland/ 1926.9 13 ACSS/TW 42 93.3 0.2142 Athabaska/ 1949.6 ACSS/TW 7 42 93.4 0.2155 Powder/ ACSS/TW 2153.8 8 64 92.2 0.1834 Santee/ ACSS/TW 2627.3 8 64 93.1 0.2027 1372.5 STANDARD PACKAGES (3) REEL DESIG. 7x0.1338 0.4014 0.8576 0.7591 1.09 1240 907 333 73.13 26.87 26400 28300 32800 RMT 84.36 RM 66.32 7x0.1078 0.3234 0.9732 0.9094 1.16 1307 1091 216 83.45 16.55 20500 22100 25000 RMT 84.45 RM 68.38 7x0.1467 0.4401 1.0279 0.9096 1.20 1488 1087 401 73.08 26.92 31100 33500 38800 RMT 84.36 RM 66.32 7x0.0926 0.2778 0.9642 0.9170 1.16 1259 1099 160 87.32 12.68 17100 18300 20400 RMT 84.45 RM 66.32 19x0.0910 0.4550 1.0923 0.9688 1.25 1584 1165 419 73.53 26.47 33200 36300 41900 RMT 90.45 RMT 84.36 7x0.1115 0.3345 1.0558 0.9875 1.21 1415 1184 231 83.65 16.35 22100 23800 26900 RMT 84.45 RM 68.38 7x0.0967 0.2901 1.0507 0.9993 1.20 1371 1197 174 87.30 12.70 18700 20000 22300 RMT 84.36 RM 66.32 19x0.0944 0.4720 1.1808 1.0479 1.29 1711 1260 451 73.64 26.36 35800 39100 45100 RMT 90.45 RM 72.36 7x0.1159 0.3477 1.1413 1.0674 1.26 1531 1281 250 83.67 16.33 23800 25700 29000 RMT 84.45 RM 68.38 7x0.1004 0.3012 1.1337 1.0783 1.25 1479 1291 188 87.32 12.68 20200 21500 24000 RMT 84.36 RM 66.32 19x0.0978 0.4890 1.2682 1.1255 1.34 1838 1354 484 73.65 26.35 38400 42000 48400 RMT 90.45 RM 72.36 7x0.1200 0.3600 1.2219 1.1427 1.30 1639 1371 268 83.64 16.36 25600 27100 30700 RMT 84.45 RM 68.38 7x0.1041 0.3123 1.2127 1.1532 1.29 1583 1381 202 87.26 12.74 21600 23100 25800 RMT 84.36 RM 66.32 19x0.1012 0.5060 1.3574 1.2046 1.38 1966 1448 518 73.63 26.37 41200 45000 51900 RMT 90.45 RM 72.36 7x0.1241 0.3723 1.3084 1.2237 1.35 1754 1467 287 83.65 16.35 27300 29000 32800 RMT 84.45 RM 68.38 7x0.1074 0.3222 1.2962 1.2328 1.33 1691 1476 215 87.30 12.70 23100 24600 27500 RMT 84.45 RM 68.38 19x0.1064 0.5320 1.4425 1.2736 1.42 2105 1531 573 72.77 27.23 45000 49200 56900 RMT 90.45 RM 72.36 7x0.1280 0.3840 1.3912 1.3012 1.39 1866 1561 305 83.66 16.34 29100 30900 34900 RMT 84.45 RM 68.38 19x0.1075 0.5375 1.5322 1.3598 1.47 2219 1634 585 73.64 26.36 46400 50800 58500 RMT 90.45 RM 72.36 7x0.1319 0.3957 1.4764 1.3807 1.43 1980 1656 324 83.65 16.35 30900 32800 37100 RMT 90.45 RM 68.38 19x0.1133 0.5665 1.7044 1.5129 1.54 2469 1819 650 73.68 26.32 51600 56400 65000 RMT 90.45 RMT 84.36 7x0.1392 0.4176 1.6384 1.5318 1.50 2197 1836 361 83.58 16.42 34300 36500 41300 RMT 90.45 RM 72.36 19x0.0961 0.4805 1.8293 1.6915 1.60 2510 2042 467 81.37 18.63 42100 45500 51700 RMT 96.60 RMT 84.45 19x0.1062 0.5310 2.2328 2.0645 1.76 3062 2492 571 81.36 18.64 51300 55600 63100 RMT 96.60 RMT 84.45 WEIGHT LENGTH LBS FEET 7899 3943 10874 5437 9776 4880 9441 4720 14588 7286 11508 5747 5333 4716 14562 7273 11832 5909 9451 4718 14555 7278 11832 5916 10320 5160 14569 7275 11836 5909 10383 5192 14732 7366 11831 5915 14557 7278 12159 6079 15679 7827 13819 6898 21611 10793 21621 10810 6370 3180 8320 4160 6570 3280 7500 3750 9210 4600 8130 4060 3890 3440 8510 4250 7730 3860 6390 3190 7920 3960 7220 3610 6520 3260 7410 3700 6750 3370 6140 3070 7000 3500 6340 3170 6560 3280 6140 3070 6350 3170 6290 3140 8610 4300 7060 3530 (1) Code words shown denote ACSS/TW with regular-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA2). See the Options section to find the appropriate code word modifier designation for alternative design options. (2) Due to rounding, total values may be slightly greater or slightly less than the sum of the component values. (3) Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 118 3/2013 Electric Utility Overhead Conductors TransPowr ACSS/TW Bare Overhead Conductor ® Trapezoidal Aluminum Conductor Steel-Supported Concentric-Lay-Stranded ACSS/TW (ELECTRICAL PROPERTIES) – EQUIVALENT DIAMETER CONDUCTORS SIZED TO HAVE EQUIVALENT DIAMETER TO REGULAR ACSS CODE WORD (1) Columbia/ ACSS/TW CROSS-SECTION SQ. INCHES STEEL SIZE EQUIVALENT STEEL CORE CORE AWG OR NO. AL FILL AL DIA. NO. X DIA. O.D. O.D. DC kcmil TYPE WIRES FACTOR INCHES INCHES INCHES TOTAL AL INCHES @ 20˚C 966.2 13 RESISTANCE (4) OHMS/1000 FT AC @ 25˚C AMPACITY (5) GEOMETRIC INDUCTIVE CAPACITIVE MEAN REACTANCE REACTANCE AC AC RADIUS OHM/1000 FT MEGAOHM @ 75˚C @ 200˚C 75˚C 200˚C FT (6) 1000 FT (6) 21 93.6 0.2145 7x0.1338 0.4014 0.8576 0.7591 1.09 0.0171 0.0178 0.0213 0.0301 1005 1820 0.0367 0.0760 0.4839 Genesee/ ACSS/TW 1158.0 7 33 92.5 0.1873 7x0.1078 0.3234 0.9732 0.9094 1.16 0.0144 0.0153 0.0188 0.0271 1085 1960 0.0385 0.0748 0.4739 Hudson/ ACSS/TW 1158.4 13 26 93.7 0.2111 7x0.1467 0.4401 1.0279 0.9096 1.20 0.0143 0.0150 0.0179 0.0252 1125 2050 0.0402 0.0738 0.4697 Cheyenne/ ACSS/TW 1168.1 5 30 92.9 0.1973 7x0.0926 0.2778 0.9642 0.9170 1.16 0.0143 0.0153 0.0187 0.0269 1085 1960 0.0379 0.0752 0.4751 Yukon/ ACSS/TW 1233.6 13 39 91.0 0.1778 19x0.0910 0.4550 1.0923 0.9688 1.25 0.0135 0.0143 0.0175 0.0252 1145 2075 0.0422 0.0727 0.4628 Nelson/ ACSS/TW 1257.1 7 35 92.4 0.1895 7x0.1115 0.3345 1.0558 0.9875 1.21 0.0133 0.0142 0.0174 0.0249 1140 2070 0.0402 0.0739 0.4674 Catawba/ ACSS/TW 1272.0 5 30 93.3 0.2059 7x0.0967 0.2901 1.0507 0.9993 1.20 0.0132 0.0141 0.0173 0.0247 1145 2070 0.0395 0.0743 0.4688 Thames/ ACSS/TW 1334.6 13 39 92.6 0.1850 19x0.0944 0.4720 1.1808 1.0479 1.29 0.0125 0.0133 0.0162 0.0233 1200 2180 0.0436 0.0720 0.4579 Mackenzie/ 1359.7 ACSS/TW 7 36 92.9 0.1943 7x0.1159 0.3477 1.1413 1.0674 1.26 0.0123 0.0132 0.0161 0.0231 1200 2175 0.0417 0.0730 0.4617 Truckee/ ACSS/TW 5 30 93.6 0.2139 7x0.1004 0.3012 1.1337 1.0783 1.25 0.0122 0.0132 0.0160 0.0229 1200 2175 0.0409 0.0734 0.4631 Merrimack/ 1433.6 13 ACSS/TW 39 92.1 0.1917 19x0.0978 0.4890 1.2682 1.1255 1.34 0.0116 0.0124 0.0152 0.0217 1255 2290 0.0452 0.0711 0.4519 Miramichi/ ACSS/TW 1455.3 7 36 93.4 0.2010 7x0.1200 0.3600 1.2219 1.1427 1.30 0.0115 0.0124 0.0151 0.0216 1245 2275 0.0430 0.0723 0.4568 St. Croix/ ACSS/TW 1467.8 5 30 93.4 0.2212 7x0.1041 0.3123 1.2127 1.1532 1.29 0.0114 0.0124 0.0151 0.0215 1250 2275 0.0424 0.0726 0.4576 Rio Grande/ 1533.3 13 ACSS/TW 39 93.2 0.1983 19x0.1012 0.5060 1.3574 1.2046 1.38 0.0109 0.0117 0.0142 0.0203 1305 2390 0.0466 0.0705 0.4474 Potomac/ ACSS/TW 1557.4 7 36 93.2 0.2080 7x0.1241 0.3723 1.3084 1.2237 1.35 0.0107 0.0117 0.0142 0.0202 1300 2375 0.0445 0.0715 0.4513 Platte/ ACSS/TW 1569.0 5 33 93.7 0.2181 7x0.1074 0.3222 1.2962 1.2328 1.33 0.0107 0.0117 0.0142 0.0201 1300 2375 0.0438 0.0719 0.4527 Pecos/ ACSS/TW 1622.0 13 39 93.0 0.2039 19x0.1064 0.5320 1.4425 1.2736 1.42 0.0103 0.0111 0.0135 0.0192 1355 2485 0.0482 0.0697 0.4424 Schuylkill/ ACSS/TW 1657.4 7 36 93.5 0.2145 7x0.1280 0.3840 1.3912 1.3012 1.39 0.0101 0.0111 0.0134 0.0190 1350 2475 0.0459 0.0708 0.4467 James/ ACSS/TW 1730.6 13 39 92.5 0.2107 19x0.1075 0.5375 1.5322 1.3598 1.47 0.00962 0.0105 0.0127 0.0181 1405 2590 0.0496 0.0690 0.4374 Pee Dee/ ACSS/TW 1758.6 7 37 93.1 0.2180 7x0.1319 0.3957 1.4764 1.3807 1.43 0.00951 0.0105 0.0127 0.0180 1395 2570 0.0474 0.0701 0.4416 Cumberland/ 1926.9 13 ACSS/TW 42 93.3 0.2142 19x0.1133 0.5665 1.7044 1.5129 1.54 0.00864 0.00951 0.0115 0.0163 1500 2770 0.0522 0.0678 0.4296 Athabaska/ 1949.6 ACSS/TW 7 42 93.4 0.2155 7x0.1392 0.4176 1.6384 1.5318 1.50 0.00858 0.00962 0.0116 0.0163 1485 2750 0.0499 0.0689 0.4338 Powder/ ACSS/TW 2153.8 8 64 92.2 0.1834 19x0.0961 0.4805 1.8293 1.6915 1.60 0.00780 0.00879 0.0103 0.0141 1600 3010 0.0535 0.0673 0.4239 Santee/ ACSS/TW 2627.3 8 64 93.1 0.2027 19x0.1062 0.5310 2.2328 2.0645 1.76 0.00640 0.00750 0.00869 0.0118 1785 3405 0.0589 0.0651 0.4090 1372.5 (1) Code words shown denote ACSS/TW with regular-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA2). See the Options section to find the appropriate code word modifier designation for alternative design options. (4) Based on a conductivity of 61.2% (minimum lot average) IACS at 20˚C for aluminum and 8% IACS at 20˚C for the steel core. AC resistance for single-layer and three-layer designs approximates the effects of core magnetization. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by 3.281. (5) Based on the given conductor temperature at 60 Hz and the following conditions: 25˚C ambient temperature, 2 ft/sec crosswind (90˚ to conductor), 0.5 coefficient of emissivity, 0.5 coefficient of absorbtivity, 30˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 96.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (6) Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm). To convert the Geometric Mean Radius (GMR) to cm, divide the value by 0.03821. To convert inductive reactance to ohm/km, multiply the value by 3.281. To convert capacitive reactance to ohm/km, divide the value by 3.281. 3/2013 119 Overhead Conductors Notes 120 Electric Utility Electric Utility Overhead Conductors TransPowr ACSR/SD Bare Overhead Conductor ® Self-Damping Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded 2-Layer SDC 3-Layer SDC Product Construction: Complete Conductor: ACSR/SD conductors are manufactured with two layers of 1350 H19 trapezoidal-shaped aluminum wires concentrically stranded around a steel core of round coated steel wires. On certain larger conductor constructions, the trapezoidal-shaped wires are surrounded by a layer of round 1350 H19 aluminum wires. The steel core and the two layers of trapezoidal-shaped aluminum wires are separated by a gap to provide the self-damping characteristics. Steel core wires are protected from corrosion by aluminum-clad, galvanized, or zinc-5% aluminum mischmetal alloy coating. Standard, high, extra- and ultra-high-strength steel is also available. The ACSR/SD conductors are manufactured in accordance with the requirements of the latest issue of ASTM B701. 3/2013 Features and Benefits: The steel core and the two layers of trapezoidalshaped aluminum wires in ACSR/SD are separated by a gap designed to provide self-damping characteristics to control Aeolian vibration— eliminating the need for vibration dampers. Additional advantages in using ASCR/SD include: shorter, more economical towers, increased reliability, lower overall line cost, reduced sag, reduced ice and wind loads as well as permitting longer spans. Applications: ACSR/SD conductors are used for overhead transmission lines to control Aeolian vibration. Options: •High-conductivity aluminum (/HC) (62.2% IACS) •Regular-strength Class C galvanized steel core (/GC2) •High-strength Class A galvanized steel core (/GA3 to ASTM B606) •Extra-high-strength Class A galvanized steel core (/GA4 to ASTM B957) •Ultra-high-strength Class A galvanized steel core (/GA5 to ASTM B957) •Regular-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA2 to ASTM B802) •High-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA3 to ASTM B803) •Extra-high-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA4 to ASTM B958) •Ultra-high-strength Class A zinc-5% aluminum mischmetal alloy-coated steel core (/MA5 to ASTM B958) •Aluminum-clad steel core (/AW) •Non-specular surface finish (/NS) For more information, or information on other conductor sizes, designs and/or specific installation requirements not shown in the tables, contact your General Cable sales representative or e-mail info@generalcable.com. 121 Overhead Conductors Electric Utility TransPowr ACSR/SD Bare Overhead Conductor ® Self-Damping Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded ACSR/SD CONCENTRIC-LAY-STRANDED (MECHANICAL PROPERTIES) APPROX. WEIGHT LB/1000 FT (2) SIZE AWG OR kcmil Titmouse/SD Eider/SD PERCENT BY WEIGHT AL STEEL RATED STRENGTH LBS 36 87.3 12.7 6920 49 83.7 16.3 7610 251 69 78.3 21.7 367 251 116 68.5 362 316 46 87.3 STANDARD PACKAGES (3) TYPE STEEL CORE O.D. INCHES O.D. INCHES TOTAL 266.8 5 0.117 0.593 287 251 266.8 7 0.136 0.601 299 251 Spoonbill/SD 266.8 10 0.162 0.610 320 Partridge/SD 266.8 16 0.236 0.645 Cowbird/SD 336.4 5 0.132 0.667 Hummingbird/SD 336.4 7 0.153 0.664 378 316 62 83.7 16.3 9130 RM 66.32 4532 12000 Woodcock/SD 336.4 10 0.206 0.688 405 317 88 78.3 21.7 11000 RM 66.32 4450 11000 Linnet/SD 326.4 16 0.265 0.716 462 317 145 68.5 31.5 14300 RM 68.38 6011 13000 Erne/SD 397.5 5 0.143 0.717 428 374 54 87.3 12.7 9740 RM 66.32 4277 10000 Longspur/SD 397.5 7 0.166 0.725 446 373 73 83.7 16.3 10600 RM 68.38 5799 13000 Stork/SD 397.5 10 0.224 0.750 478 374 104 78.3 21.7 12900 RM 68.38 5735 12000 Ibis/SD 397.5 16 0.288 0.771 547 375 172 68.5 31.5 16400 RM 68.38 6558 12000 Kestrel/SD 477.0 5 0.157 0.787 513 448 65 87.3 12.7 11700 RM 68.38 5646 11000 Jackdaw/SD 477.0 7 0.206 0.808 536 449 87 83.7 16.3 13300 RM 68.38 5894 11000 Toucan/SD 477.0 10 0.245 0.824 573 449 125 78.3 21.7 15300 RM 68.38 5734 10000 Flicker/SD 477.0 13 0.282 0.843 614 449 165 73.2 26.8 17200 RMT 84.36 7362 12000 Hawk/SD 477.0 16 0.316 0.860 656 449 206 68.5 31.5 19500 RMT 84.36 7214 11000 Blackbird/SD 556.5 5 0.169 0.843 599 523 76 87.3 12.7 13600 RM 68.38 5990 10000 Sunbird/SD 556.5 7 0.222 0.863 625 523 102 83.7 16.3 15500 RMT 84.36 6875 11000 Sapsucker/SD 556.5 10 0.265 0.882 669 524 145 78.3 21.7 17800 RMT 84.36 7359 11000 Parakeet/SD 556.5 13 0.305 0.901 716 524 192 73.2 26.8 20000 RMT 84.36 7160 10000 Dove/SD 556.5 16 0.341 0.919 765 524 241 68.5 31.5 22600 RMT 84.36 7650 10000 Pippit/SD 636.0 5 0.205 0.903 684 598 87 87.3 12.7 16100 RMT 84.36 7524 11000 Killdeer/SD 636.0 7 0.238 0.917 715 598 117 83.6 16.4 17700 RMT 84.36 7150 10000 Goldfinch/SD 636.0 10 0.284 0.935 765 599 166 78.3 21.7 20100 RMT 84.36 7650 10000 Rook/SD 636.0 13 0.326 0.955 818 599 219 73.2 26.8 22900 RMT 84.36 7362 9000 Grosbeak/SD 636.0 16 0.365 0.975 874 599 275 68.5 31.5 25400 RMT 84.36 7866 9000 Macaw/SD 795.0 5 0.229 0.999 856 747 109 87.3 12.7 19800 RMT 90.45 11984 14000 Tern/SD 795.0 7 0.266 1.013 893 747 146 83.6 16.4 21900 RMT 90.45 11609 13000 Puffin/SD 795.0 10 0.317 1.034 956 746 208 78.3 21.7 25100 RMT 90.45 12428 13000 Condor/SD 795.0 13 0.364 1.055 1023 749 274 73.2 26.8 28200 RMT 90.45 12276 12000 Drake/SD 795.0 16 0.408 1.077 1093 749 344 68.5 31.5 31800 RMT 90.45 12023 11000 Phoenix/SD 954.0 5 0.251 1.088 1027 897 130 87.3 12.7 23700 RMT 90.45 11297 11000 Rail/SD 954.0 7 0.291 1.103 1073 897 176 83.6 16.4 26100 RMT 90.45 11803 11000 Cardinal/SD 954.0 13 0.399 1.147 1227 898 329 73.2 26.8 33500 RMT 90.45 12270 10000 CODE WORD (1) AL STEEL REEL DESIGNATION WEIGHT POUNDS LENGTH FEET RM 66.32 4017 14000 RM 66.32 4192 14000 8450 RM 66.32 4480 14000 31.5 11350 RM 66.32 4771 13000 12.7 8500 RM 66.32 4343 12000 (1) Code words shown denote ACSR/SD with regular-strength Class A galvanized steel core (/GA2). See the Options section to find the appropriate code word modifier designation for alternative design options. (2) Due to rounding, total values may not exactly equal the sum of the component values. (3) Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 122 3/2013 Electric Utility Overhead Conductors TransPowr ACSR/SD Bare Overhead Conductor ® Self-Damping Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded ACSR/SD CONCENTRIC-LAY-STRANDED (ELECTRICAL PROPERTIES) TYPE STEEL CORE O.D. INCHES O.D. INCHES DC @ 20˚C RESISTANCE (4) OHMS/1000 FT AC @ 25˚C 266.8 5 0.117 0.593 0.0646 0.0660 0.0790 0.0195 0.0905 0.5797 266.8 7 0.136 0.601 0.0645 0.0658 0.0788 0.0199 0.0900 0.5776 Spoonbill/SD 266.8 10 0.162 0.610 0.0642 0.0656 0.0785 0.0203 0.0895 0.5755 Partridge/SD 266.8 16 0.236 0.645 0.0637 0.0650 0.0779 0.0220 0.0877 0.5665 Cowbird/SD 336.4 5 0.132 0.667 0.0512 0.0523 0.0626 0.0217 0.0880 0.5613 Hummingbird/SD 336.4 7 0.153 0.664 0.0510 0.0522 0.0625 0.0218 0.0880 0.5618 Woodcock/SD 336.4 10 0.206 0.688 0.0509 0.0520 0.0623 0.0230 0.0867 0.5565 Linnet/SD 326.4 16 0.265 0.716 0.0505 0.0516 0.0618 0.0245 0.0853 0.5502 Erne/SD 397.5 5 0.143 0.717 0.0433 0.0443 0.0530 0.0233 0.0864 0.5496 Longspur/SD 397.5 7 0.166 0.725 0.0432 0.0442 0.0529 0.0238 0.0859 0.5481 Stork/SD 397.5 10 0.224 0.750 0.0431 0.0441 0.0527 0.0249 0.0848 0.5428 Ibis/SD 397.5 16 0.288 0.771 0.0428 0.0437 0.0523 0.0261 0.0838 0.5386 Kestrel/SD 477.0 5 0.157 0.787 0.0361 0.0370 0.0442 0.0257 0.0842 0.5354 Jackdaw/SD 477.0 7 0.206 0.808 0.0360 0.0369 0.0441 0.0261 0.0838 0.5333 Toucan/SD 477.0 10 0.245 0.824 0.0359 0.0368 0.0440 0.0274 0.0827 0.5280 Flicker/SD 477.0 13 0.282 0.843 0.0358 0.0366 0.0438 0.0283 0.0819 0.5243 Hawk/SD 477.0 16 0.316 0.860 0.0356 0.0365 0.0437 0.0291 0.0813 0.5217 Blackbird/SD 556.5 5 0.169 0.843 0.0309 0.0317 0.0379 0.0274 0.0827 0.5243 Sunbird/SD 556.5 7 0.222 0.863 0.0309 0.0317 0.0379 0.0285 0.0818 0.5206 Sapsucker/SD 556.5 10 0.265 0.882 0.0308 0.0316 0.0377 0.0293 0.0811 0.5174 Parakeet/SD 556.5 13 0.305 0.901 0.0307 0.0314 0.0376 0.0302 0.0804 0.5143 Dove/SD 556.5 16 0.341 0.919 0.0305 0.0313 0.0374 0.0311 0.0798 0.5111 Pippit/SD 636.0 5 0.205 0.903 0.0271 0.0278 0.0333 0.0291 0.0813 0.5153 Killdeer/SD 636.0 7 0.238 0.917 0.0270 0.0277 0.0332 0.0302 0.0804 0.5111 Goldfinch/SD 636.0 10 0.284 0.935 0.0269 0.0276 0.0330 0.0311 0.0798 0.5085 Rook/SD 636.0 13 0.326 0.955 0.0268 0.0275 0.0329 0.0320 0.0791 0.5048 Grosbeak/SD 636.0 16 0.365 0.975 0.0267 0.0274 0.0328 0.0329 0.0784 0.5016 Macaw/SD 795.0 5 0.229 0.999 0.0217 0.0224 0.0267 0.0326 0.0787 0.4979 Tern/SD 795.0 7 0.266 1.013 0.0216 0.0223 0.0266 0.0333 0.0782 0.4958 Puffin/SD 795.0 10 0.317 1.034 0.0215 0.0222 0.0265 0.0343 0.0775 0.4926 Condor/SD 795.0 13 0.364 1.055 0.0215 0.0221 0.0264 0.0353 0.0769 0.4895 Drake/SD 795.0 16 0.408 1.077 0.0214 0.0220 0.0263 0.0364 0.0762 0.4863 Phoenix/SD 954.0 5 0.251 1.088 0.0180 0.0187 0.0223 0.0357 0.0766 0.4847 Rail/SD 954.0 7 0.291 1.103 0.0180 0.0187 0.0222 0.0364 0.0762 0.4826 Cardinal/SD 954.0 13 0.399 1.147 0.0179 0.0185 0.0220 0.0384 0.0749 0.4763 SIZE AWG OR kcmil Titmouse/SD Eider/SD CODE WORD (1) AC @ 75˚C GEOMETRIC MEAN RADIUS FT INDUCTIVE REACTANCE OHM / 1000 FT (5) CAPACITIVE REACTANCE MEGAOHM 1000 FT (5) (1) Code words shown denote ACSR/SD with regular-strength Class A galvanized steel core (/GA2). See the Options section to find the appropriate code word modifier designation for alternative design options. (4) Based on a conductivity of 61.0% IACS at 20˚C for aluminum and 8% IACS at 20˚C for the steel core. AC resistance for three-layer designs must be increased by 1.1%, 2.7%, 3.7%, and 4.3% for current densities of 200, 600, 1000, and 1400 amperes per 1000 kcmil of aluminum to allow for the magnetic losses in the steel core. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by 3.281. (5) Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius. 3/2013 123 Overhead Conductors Electric Utility TransPowr ACSR/SD Bare Overhead Conductor ® Self-Damping Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded ACSR/SD CONCENTRIC-LAY-STRANDED (MECHANICAL PROPERTIES) APPROX. WEIGHT LB/1000 FT (2) TYPE O.D. INCHES TOTAL AL 5 0.261 1.185 1115 974 STEEL AL STEEL RATED STRENGTH LBS 141 87.3 12.7 25900 STANDARD PACKAGES (3) SIZE AWG OR kcmil Snowbird/SD 1033.5 Ortolan/SD 1033.5 7 0.303 1.145 1161 971 190 83.6 16.4 28100 Curlew/SD 1033.5 13 0.415 1.191 1329 973 356 73.2 26.8 36300 Avocet/SD 1113.0 5 0.271 1.226 1200 1048 152 87.3 12.7 27500 Bluejay/SD 1113.0 7 0.315 1.242 1254 1049 205 83.7 16.3 30300 Finch/SD 1113.0 13 0.431 1.233 1424 1048 376 73.6 26.4 Oxbird/SD 1192.5 5 0.281 1.266 1286 1123 163 87.3 Bunting/SD 1192.5 7 0.326 1.284 1343 1124 219 83.7 Grackle/SD 1192.5 13 0.446 1.274 1526 1123 403 Scissortail/SD 1272.0 5 0.290 1.305 1372 1198 174 Bittern/SD 1272.0 7 0.336 1.323 1433 1199 234 83.7 16.3 34600 RMT 96.60 17196 12000 Pheasant/SD 1272.0 13 0.461 1.378 1631 1202 429 73.7 26.3 44100 RMT 96.60 19572 12000 Ringdove/SD 1351.5 5 0.299 1.344 1458 1273 185 87.3 12.7 33400 RMT 96.60 17496 12000 Dipper/SD 1351.5 7 0.347 1.361 1522 1274 248 83.7 16.3 36700 RMT 96.60 18264 12000 Frigate/SD 1351.5 10 0.413 1.389 1629 1276 353 78.3 21.7 41700 RMT 96.60 17919 11000 Martin/SD 1351.5 13 0.475 1.417 1733 1277 456 73.7 26.3 46800 RMT 96.60 19063 11000 Popinjay/SD 1431.0 5 0.308 1.381 1544 1348 196 87.3 12.7 35300 RMT 96.60 16984 11000 Bobolink/SD 1431.0 7 0.357 1.398 1612 1349 263 83.7 16.3 38900 RMT 96.60 17732 11000 Plover/SD 1431.0 13 0.489 1.448 1835 1352 483 73.7 26.3 49600 RMT 96.60 20185 11000 Ratite/SD 1590.0 5 0.325 1.447 1715 1498 218 87.3 12.7 39100 RMT 96.60 17150 10000 Lapwing/SD 1590.0 7 0.376 1.468 1791 1499 292 83.7 16.3 42600 RMT 96.60 17910 10000 Falcon/SD 1590.0 13 0.515 1.521 2039 1502 537 73.7 26.3 55100 RMT 96.60 18351 9000 Smew/SD 1780.0 5 0.343 1.531 1921 1677 244 87.3 12.7 43600 RMT 96.60 17289 9000 Chukar/SD 1780.0 8 0.437 1.565 2068 1681 387 81.3 18.7 51100 RMT 96.60 18612 9000 Cockatoo/SD 2156.0 5 0.378 1.731 2331 2036 295 87.3 12.7 52500 RMT 96.60 17483 7500 Bluebird/SD 2156.0 8 0.481 1.716 2504 2036 468 81.3 18.7 60700 RMT 96.60 18780 7500 Kiwi/SD 2167.0 4 0.347 1.725 2296 2047 249 89.2 10.8 50700 RMT 96.60 16072 7000 CODE WORD (1) STEEL CORE O.D. INCHES PERCENT BY WEIGHT REEL DESIGNATION WEIGHT POUNDS LENGTH FEET RMT 90.45 11150 10000 RMT 90.45 11610 10000 RMT 90.45 11961 9000 RMT 90.45 10800 9000 RMT 90.45 11286 9000 39100 RMT 90.45 12816 9000 12.7 29500 RMT 90.45 11574 9000 16.3 32400 RMT 90.45 10744 8000 73.6 26.4 41900 RMT 90.45 12208 8000 87.3 12.7 31400 RMT 96.60 16464 12000 (1) Code words shown denote ACSR/SD with regular-strength Class A galvanized steel core (/GA2). See the Options section to find the appropriate code word modifier designation for alternative design options. (2) Due to rounding, total values may not exactly equal the sum of the component values. (3) Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 124 3/2013 Electric Utility Overhead Conductors TransPowr ACSR/SD Bare Overhead Conductor ® Self-Damping Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded ACSR/SD CONCENTRIC-LAY-STRANDED (ELECTRICAL PROPERTIES) TYPE STEEL CORE O.D. INCHES O.D. INCHES DC @ 20˚C RESISTANCE (4) OHMS/1000 FT AC @ 25˚C 5 0.261 1.185 0.0167 0.0175 AC @ 75˚C GEOMETRIC MEAN RADIUS FT INDUCTIVE REACTANCE OHM / 1000 FT (5) CAPACITIVE REACTANCE MEGAOHM 1000 FT (5) 0.0208 0.0389 0.0746 0.4710 SIZE AWG OR kcmil Snowbird/SD 1033.5 Ortolan/SD 1033.5 7 0.303 1.145 0.0166 0.0174 0.0206 0.0378 0.0753 0.4768 Curlew/SD 1033.5 13 0.415 1.191 0.0165 0.0171 0.0204 0.0400 0.0740 0.4704 Avocet/SD 1113.0 5 0.271 1.226 0.0155 0.0163 0.0193 0.0402 0.0739 0.4657 Bluejay/SD 1113.0 7 0.315 1.242 0.0155 0.0162 0.0192 0.0410 0.0734 0.4636 Finch/SD 1113.0 13 0.431 1.233 0.0153 0.0159 0.0190 0.0414 0.0732 0.4652 Oxbird/SD 1192.5 5 0.281 1.266 0.0145 0.0153 0.0181 0.0415 0.0732 0.4609 Bunting/SD 1192.5 7 0.326 1.284 0.0144 0.0152 0.0180 0.0423 0.0727 0.4588 Grackle/SD 1192.5 13 0.446 1.274 0.0143 0.0149 0.0177 0.0428 0.0724 0.4599 Scissortail/SD 1272.0 5 0.290 1.305 0.0136 0.0144 0.0170 0.0427 0.0725 0.4562 Bittern/SD 1272.0 7 0.336 1.323 0.0135 0.0143 0.0170 0.0436 0.0720 0.4541 Pheasant/SD 1272.0 13 0.461 1.378 0.0134 0.0141 0.0167 0.0464 0.0705 0.4477 Ringdove/SD 1351.5 5 0.299 1.344 0.0128 0.0136 0.0180 0.0440 0.0718 0.4514 Dipper/SD 1351.5 7 0.347 1.361 0.0128 0.0135 0.0160 0.0449 0.0713 0.4493 Frigate/SD 1351.5 10 0.413 1.389 0.0127 0.0134 0.0159 0.0463 0.0706 0.4462 Martin/SD 1351.5 13 0.475 1.417 0.0126 0.0133 0.0158 0.0477 0.0699 0.4430 Popinjay/SD 1431.0 5 0.308 1.381 0.0121 0.0129 0.0152 0.0452 0.0711 0.4472 Bobolink/SD 1431.0 7 0.357 1.398 0.0120 0.0128 0.0152 0.0461 0.0707 0.4451 Plover/SD 1431.0 13 0.489 1.448 0.0120 0.0127 0.0150 0.0488 0.0694 0.4398 Ratite/SD 1590.0 5 0.325 1.447 0.0109 0.0118 0.0138 0.0477 0.0699 0.4382 Lapwing/SD 1590.0 7 0.376 1.468 0.0108 0.0116 0.0137 0.0484 0.0696 0.4377 Falcon/SD 1590.0 13 0.515 1.521 0.0108 0.0115 0.0136 0.0512 0.0683 0.4319 Smew/SD 1780.0 5 0.343 1.531 0.0097 0.0106 0.0125 0.0502 0.0688 0.4308 Chukar/SD 1780.0 8 0.437 1.565 0.0097 0.0105 0.0124 0.0519 0.0680 0.4277 Cockatoo/SD 2156.0 5 0.378 1.731 0.0080 0.0091 0.0105 0.0573 0.0657 0.4118 Bluebird/SD 2156.0 8 0.481 1.716 0.0080 0.0089 0.0104 0.0570 0.0658 0.4134 Kiwi/SD 2167.0 4 0.347 1.725 0.0080 0.0090 0.0105 0.0570 0.0659 0.4124 CODE WORD (1) (1) Code words shown denote ACSR/SD with regular-strength Class A galvanized steel core (/GA2). See the Options section to find the appropriate code word modifier designation for alternative design options. (4) Based on a conductivity of 61.0% IACS at 20˚C for aluminum and 8% IACS at 20˚C for the steel core. AC resistance for three-layer designs must be increased by 1.1%, 2.7%, 3.7%, and 4.3% for current densities of 200, 600, 1000, and 1400 amperes per 1000 kcmil of aluminum to allow for the magnetic losses in the steel core. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by 3.281. (5) Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius. 3/2013 125 Overhead Conductors Notes 126 Electric Utility Electric Utility Overhead Conductors TransPowr Weatherproof Overhead Line Wire ® Single Conductor LLDPE or XLPE Covered Line Wire to CSA C68.9 Product Construction: Complete Cable: Weatherproof line wire consists of single conductor covered with either Linear Low-Density Polyethylene (LLDPE) or Cross-linked Polyethylene (XLPE). Conductors may be compact or concentric strand of ACSR, A1 or A2 or solid, compact or concentric strand copper. Weatherproof line wire meets the requirements of CSA C68.9 and the ANSI/ICEA S-70-547 specification, as applicable. Conductors: Different conductor types are available. Solid or stranded MHD copper, compact or concentric HD aluminum, aluminum alloy, or ACSR are all options that are available. The conductors meet the requirements of CSA C49.2, CAN/CSA C61089, ASTM B3, B8, B231, B232, B400, or B496 as applicable. For aluminum and ACSR conductors, the direction of lay of the outer layer of the strand is right-hand. For copper conductors, the direction of lay of the outer layer of the strand is left-hand. For products manufactured with aluminum conductors, the product is available with conductor corrosion-resistant inhibitor treatment. Complete Cable (cont’d.): Covering: Black, Linear Low-Density Polyethylene (LLDPE) or black extruded Cross-linked Polyethylene (XLPE) coverings are available. There is no voltage rating. Features and Benefits: The covering provides mechanical protection to the conductor and is resistant to weathering and chemicals. If the conductors accidentally come into contact due to high winds, falling tree limbs, or other disturbances, the covering resists short circuits and the tendency for conductors to weld together. Applications: Weatherproof line wire is used for overhead transmission and distribution lines. Covered line wire is not an electrically insulated cable. Therefore, it should be installed on insulators, and users should treat line wire as bare conductor for personal safety. Options: •Medium-Density Polyethylene (MDPE) •High-Density Cross-linked Polyethylene (HDXLPE) •Annealed (soft drawn) copper for transformer drop and covered ground wire •Conductor corrosion-resistant inhibitor treatment •Sequential print marking For other conductor sizes, designs and/or specific installation requirements not shown in the tables, contact your General Cable sales representative or e-mail infoca@generalcable.com. 127 Overhead Conductors Electric Utility TransPowr Weatherproof Overhead Line Wire ® Single Conductor LLDPE or XLPE Covered Line Wire to CSA C68.9 COVERED ACSR ALUMINUM CONDUCTOR, STEEL-REINFORCED, COMPACT-LAY-STRANDED STRANDING CONDUCTOR SIZE NO. X DIA. INCHES CONDUCTOR O.D. CODE WORD (1) Gum Solah -noneTeak -none-noneEbony -none-noneLiana -noneBamboo -noneCorypha Mahogany Eucalyptus -none-none- COVER THKN. APPROX. WEIGHT LB/1000 FT TOTAL CABLE O.D. RATED STRENGTH AMPACITY AWG OR kcmil mm2 AL STEEL INCHES mm INCHES mm INCHES mm AL PE XLPE LBS kN 6 6 13.3 13.3 6 6 1x0.0661 1x0.0937 0.182 0.193 4.62 4.90 0.030 0.030 0.76 0.76 0.242 0.253 6.15 6.43 24.5 24.5 45.1 57.3 45.1 57.3 1170 1720 5.20 7.65 6 4 4 4 2 2 2 1 1 1/0 1/0 2/0 3/0 4/0 266.8 336.4 13.3 21.1 21.1 21.1 33.6 33.6 33.6 42.4 42.4 53.5 53.5 67.4 85.0 107.2 135.2 170.5 6 6 6 6 6 6 6 6 6 6 6 6 6 6 18 18 1x0.1181 1x0.0835 1x0.1181 1x0.1488 1x0.1052 1x0.1488 1x0.1878 1x0.1182 1x0.1673 1x0.1327 1x0.1878 1x0.1490 1x0.1672 1x0.1878 1x0.1217 1x0.1366 0.208 0.229 0.243 0.264 0.290 0.308 0.331 0.326 0.346 0.365 0.388 0.409 0.461 0.516 0.559 0.630 5.28 5.82 6.17 6.71 7.37 7.82 8.41 8.28 8.79 9.27 9.86 10.4 11.7 13.1 14.2 16.0 0.030 0.030 0.030 0.030 0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.060 0.060 0.060 0.060 0.76 0.76 0.76 0.76 1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 1.52 1.52 1.52 1.52 0.268 0.289 0.303 0.324 0.380 0.398 0.421 0.416 0.436 0.485 0.508 0.530 0.581 0.636 0.679 0.748 6.81 7.34 7.70 8.23 9.65 10.11 10.7 10.6 11.1 12.3 12.9 13.5 14.8 16.2 17.2 19.0 24.5 38.8 38.8 38.8 61.8 61.8 61.8 78.2 78.2 98.5 98.5 124.3 156.5 197.4 250 316 71.8 68.8 88.0 110.8 112.8 143.5 180.1 139.5 178.2 179.5 228.3 221.2 273.5 338.7 338 419 71.8 68.8 88.0 110.8 112.8 143.5 180.1 139.5 178.2 179.5 228.3 221.2 273.5 338.7 338 419 2400 1830 2710 3680 2800 4130 5780 3480 5180 4250 6470 5280 6660 8400 7020 8850 10.7 8.14 12.1 16.4 12.5 18.4 25.7 15.5 23.0 18.9 28.8 23.5 29.6 37.4 31.2 39.4 PE (2) XLPE (3) 95 95 100 125 130 130 160 170 175 185 195 210 225 240 275 310 385 445 110 115 120 145 155 160 190 205 210 220 240 250 275 290 330 375 425 550 COVERED ACSR ALUMINUM CONDUCTOR, STEEL-REINFORCED, CONCENTRIC-LAY-STRANDED CONDUCTOR SIZE CODE WORD (1) COVER THKN. CABLE O.D. APPROX. WEIGHT LB/1000 FT RATED STRENGTH AMPACITY TOTAL AWG OR kcmil mm2 NO. OF WIRES INCHES mm INCHES mm SIZE PE XLPE LBS kN PE (2) XLPE (3) Walnut Butternut 6 4 13.3 21.1 6/1 6/1 0.030 0.030 0.762 0.762 0.260 0.312 6.60 7.92 24.5 38.9 46.9 71.3 46.9 71.3 1130 1830 5.03 8.14 Hickory Pignut Chestnut Almond Pecan Filbert Buckeye Hackberry Redbud Mockernut Aspen 4 2 1 1/0 2/0 3/0 4/0 266.8 266.8 336.4 336.4 21.1 33.6 42.4 53.5 67.4 85.0 107.2 135.2 135.2 170.5 170.5 7/1 6/1 6/1 6/1 6/1 6/1 6/1 18/1 18/1 18/1 18/1 0.030 0.045 0.045 0.060 0.060 0.060 0.060 0.060 0.080 0.060 0.080 0.762 1.14 1.14 1.52 1.52 1.52 1.52 1.52 2.03 1.52 2.03 0.319 0.408 0.445 0.521 0.570 0.625 0.686 0.732 0.773 0.807 0.848 8.10 10.4 11.3 13.2 14.5 15.9 17.4 18.6 19.6 20.5 21.5 38.9 61.9 78.1 98.5 124.1 156.5 197.4 250 250 315 315 81.4 117.2 143.9 184.5 226.9 280.1 346.5 347 367 430 452 81.4 117.2 143.9 184.5 226.9 280.1 346.5 347 367 430 452 2300 2800 3480 4250 5280 6660 8400 7000 7000 8900 8900 10.2 12.5 15.5 18.9 23.5 29.6 37.4 31.1 31.1 39.6 39.6 105 140 140 180 190 235 270 335 370 435 435 505 500 120 160 160 210 225 275 315 385 440 505 505 585 580 (1) Code words shown are for PE products; add the suffix “XLP” to the code word for cross-linked products. Example: Walnut/XLP. (2) Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 25˚C ambient temperature, 2 ft/sec (0.61 m/s) crosswind (90˚ to conductor), 0.91 coefficient of emissivity, 0.95 coefficient of absorbtivity, 42˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 96.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (3) Based on a conductor temperature of 90˚C at 60 Hz and the following conditions: 25˚C ambient temperature, 2 ft/sec (0.61 m/s) crosswind (90˚ to conductor), 0.91 coefficient of emissivity, 0.95 coefficient of absorbtivity, 42˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 96.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 128 Electric Utility Overhead Conductors TransPowr Weatherproof Overhead Line Wire ® Single Conductor LLDPE or XLPE Covered Line Wire to CSA C68.9 COVERED ASC ALUMINUM CONDUCTOR, CONCENTRIC-LAY-STRANDED CONDUCTOR SIZE COVER THKN. CABLE O.D. APPROX. WEIGHT LB/1000 FT RATED STRENGTH AMPACITY TOTAL CODE WORD (1) AWG OR kcmil mm2 NO. OF WIRES INCHES mm INCHES mm AL PE XLPE LBS kN PE (2) XLPE (3) Apple Plum Pear Apricot Cherry Peach Nectarine Quince Orange Fig Olive Mulberry Silverbelt Anona Crabapple Chinquapin Ginkgo Molles Ash Huckleberry Paw Paw Breadfruit Persimmon Grapefruit Mango 6 6 4 4 2 2 1 1/0 2/0 3/0 4/0 266.8 266.8 336.4 336.4 350.0 350.0 397.5 400.0 477.0 556.5 636.0 795.0 1033.5 1590.0 13.3 13.3 21.1 21.1 33.6 33.6 42.4 53.5 67.4 85.0 107.2 135.2 135.2 170.5 170.5 177.3 177.3 201.4 202.7 241.7 282.0 322.3 402.8 523.7 805.7 1 7 1 7 1 7 7 7 7 7 7 19 19 19 19 19 19 19 19 37 37 61 61 61 61 0.030 0.030 0.030 0.030 0.045 0.045 0.045 0.060 0.060 0.060 0.060 0.060 0.080 0.060 0.080 0.060 0.080 0.080 0.080 0.080 0.080 0.095 0.095 0.095 0.110 0.762 0.762 0.762 0.762 1.14 1.14 1.14 1.52 1.52 1.52 1.52 1.52 2.03 1.52 2.03 1.52 2.03 2.03 2.03 2.03 2.03 2.41 2.41 2.41 2.79 0.224 0.245 0.266 0.293 0.350 0.384 0.420 0.491 0.537 0.587 0.645 0.715 0.756 0.788 0.829 0.802 0.843 0.887 0.889 0.959 1.022 1.113 1.222 1.366 1.679 5.69 6.22 6.76 7.44 8.89 9.75 10.67 12.47 13.6 14.9 16.4 18.2 19.2 20.0 21.1 20.4 21.4 22.5 22.6 24.4 26.0 28.3 31.0 34.7 42.6 24.6 24.6 39.1 39.1 62.2 62.2 78.4 99.0 124.8 157.3 198.3 250 250 315 315 328 328 373 375 447 522 596 745 969 1490 33.4 34.6 50.3 52.0 83.2 86.1 105.5 135.5 165.6 203.1 249.3 307 326 379 400 393 414 464 467 548 631 731 896 1142 1739 33.4 34.6 50.3 52.0 83.2 86.1 105.5 135.5 165.6 203.1 249.3 307 326 379 400 393 414 464 467 548 631 731 896 1142 1739 490 580 780 930 1210 1400 1670 2040 2580 3150 3980 5170 5170 6520 6520 6780 6780 7690 7750 9500 10800 13000 15900 20000 29900 2.18 2.58 3.47 4.14 5.38 6.23 7.43 9.07 11.5 14.0 17.7 23.0 23.0 29.0 29.0 30.2 30.2 34.2 34.5 42.3 48.0 57.8 70.7 89.0 133 105 105 140 140 185 185 200 245 290 325 375 430 430 500 495 510 510 545 550 610 675 725 830 890 1240 120 120 160 160 210 210 230 280 335 375 430 500 500 580 575 595 595 640 640 715 790 850 975 1055 1470 COVERED ASC ALUMINUM CONDUCTOR, COMPACT-LAY-STRANDED CONDUCTOR SIZE CODE WORD (1) AWG OR kcmil mm2 Bay Hop Sloe Alder Aspen Thorn Barwood Camwood Dogwood Oakwood -noneRedwood Corkwood Hornbeam Ironwood Beachwood Buttonwood -none- 6 4 2 1 1/0 2/0 3/0 3/0 4/0 4/0 250 266.8 266.8 300 336.4 397.5 477 500 13.3 21.1 33.6 42.4 53.5 67.4 85.0 85.0 107.2 107.2 126.7 135.2 135.2 152.0 170.5 201.4 241.7 253.4 CONDUCTOR O.D. NO. OF mm WIRES INCHES 7 7 7 7 7 7 7 18 7 18 7 7 18 18 18 18 18 18 0.169 0.213 0.268 0.299 0.336 0.376 0.421 0.421 0.476 0.476 0.520 0.535 0.535 0.571 0.602 0.657 0.720 0.736 4.29 5.41 6.81 7.59 8.53 9.55 10.7 10.7 12.1 12.1 13.2 13.6 13.6 14.5 15.3 16.7 18.3 18.7 COVER THKN. CABLE O.D. APPROX. WEIGHT LB/1000 FT TOTAL RATED STRENGTH AMPACITY INCHES mm INCHES mm AL PE XLPE LBS kN PE (2) XLPE (3) 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.060 0.060 0.060 0.060 0.060 0.060 0.060 0.060 0.060 0.080 0.080 1.14 1.14 1.14 1.14 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 2.03 2.03 0.259 0.303 0.358 0.389 0.456 0.496 0.543 0.543 0.595 0.595 0.640 0.657 0.657 0.690 0.723 0.779 0.882 0.896 6.58 7.70 9.09 9.88 11.6 12.6 13.8 13.8 15.1 15.1 16.3 16.7 16.7 17.5 18.4 19.8 22.4 22.8 24.4 38.9 61.7 77.9 98.3 123.8 156.2 157.3 197.4 197.9 232.7 248 250 419 315 373 447 469 37.5 55.1 81.8 100.3 130.1 159.2 195.7 196.4 241.2 242.2 281 296 297 331 367 429 531 554 37.5 55.1 81.8 100.3 130.1 159.2 195.7 196.4 241.2 242.2 281 296 297 331 367 429 531 554 580 930 1400 1670 2040 2570 3150 3540 3980 4220 4700 5010 5170 5810 6510 7470 8970 9390 2.58 4.14 6.23 7.43 9.07 11.4 14.0 15.7 17.7 18.8 20.9 22.3 23.0 25.8 29.0 33.2 39.9 41.8 105 135 180 205 240 280 315 315 365 365 370 385 385 410 485 490 540 555 115 155 205 240 275 325 365 365 425 425 440 460 460 495 565 590 655 675 (1) Code words shown are for PE products; add the suffix “XLP” to the code word for cross-linked products. Example: Walnut/XLP. (2) Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 25˚C ambient temperature, 2 ft/sec (0.61 m/s) crosswind (90˚ to conductor), 0.91 coefficient of emissivity, 0.95 coefficient of absorbtivity, 42˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 96.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (3) Based on a conductor temperature of 90˚C at 60 Hz and the following conditions: 25˚C ambient temperature, 2 ft/sec (0.61 m/s) crosswind (90˚ to conductor), 0.91 coefficient of emissivity, 0.95 coefficient of absorbtivity, 42˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 96.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 129 Overhead Conductors Electric Utility TransPowr Weatherproof Overhead Line Wire ® Single Conductor LLDPE or XLPE Covered Line Wire to CSA C68.9 COVERED COPPER CONDUCTOR, CONCENTRIC-LAY-STRANDED CONDUCTOR SIZE CODE WORD (1) AWG OR kcmil mm2 CONDUCTOR O.D. NO. OF WIRES INCHES COVER THKN. CABLE O.D. APPROX. WEIGHT LB/1000 FT RATED STRENGTH AMPACITY TOTAL mm INCHES mm INCHES mm AL PE XLPE LBS kN PE (2) XLPE (3) 165 215 285 330 440 190 250 335 385 515 MEDIUM HARD DRAWN COPPER -none-none- 4 2 21.1 33.6 7 7 0.232 0.292 5.89 7.42 0.030 0.045 0.76 1.14 0.292 0.382 7.42 9.70 128.9 204.9 141.4 228.3 141.4 228.3 1510 2380 6.7 10.6 -none-none-none- 1/0 2/0 4/0 53.5 67.4 107.2 7 19 19 0.368 0.418 0.528 9.35 10.6 13.4 0.060 0.060 0.060 1.52 1.52 1.52 0.488 0.538 0.648 12.40 13.67 16.46 326.0 410.9 653.3 361.6 451.2 704.2 361.6 451.2 704.2 3730 4800 7520 16.6 21.4 33.4 (1) Code words shown are for PE products; add the suffix “XLP” to the code word for cross-linked products. Example: Walnut/XLP. (2)Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 25˚C ambient temperature, 2 ft/sec (0.61 m/s) crosswind (90˚ to conductor), 0.91 coefficient of emissivity, 0.95 coefficient of absorbtivity, 42˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 96.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. (3)Based on a conductor temperature of 90˚C at 60 Hz and the following conditions: 25˚C ambient temperature, 2 ft/sec (0.61 m/s) crosswind (90˚ to conductor), 0.91 coefficient of emissivity, 0.95 coefficient of absorbtivity, 42˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting in 96.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. 130 Electric Utility Overhead Conductors Aluminum Tie Wire Soft Solid 1350 Aluminum Wire Product Construction: Description: SIZE AWG DIAMETER OF SOLID WIRE INCHES APPROX. WEIGHT LB/1000 FT NOMINAL BREAKING STRENGTH LBS (1) 6 0.162 24.1 175 4 0.204 38.4 280 2 0.258 61.0 440 (1) Based on annealed aluminum having a minimum tensile strength of 8500 psi. Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass. Aluminum tie wire is a soft solid aluminum wire that is used in overhead transmission and distribution line construction to mechanically secure components such as conductors to pin insulators. The wire is also used for above-ground grounding applications in line construction. Aluminum tie wire is a solid annealed (soft) aluminum wire manufactured to ASTM B609 “O” tensile grade and wire diameter dimension. Options: Tie wire may be supplied with a black weatherresistant covering. The nominal thickness of this extruded covering is 30 mils. Packaging: Aluminum tie wire is sold in coils. 131 Electric Utility BICC Brand Stock Program ® 5 General Cable BICC® Brand Products Electric Utility Stock Program As a service to our customers, General Cable maintains an inventory of factory stock for frequently purchased items of Medium-Voltage Power, Bare Overhead Distribution and Low-Voltage Overhead and Underground Service cables. These products are manufactured to industry standard specifications, and are available for immediate shipment from our manufacturing facilities and Regional Distribution Centers across North America. Terms and Conditions of Sale for Stock Products Standards: •Low-Voltage Insulated and Bare Aluminum stock products are manufactured and tested in accordance with the latest revisions of CSA. •Medium-Voltage Power cable stock products are manufactured and tested in accordance with the latest revisions of CSA. •Weights and dimensions shown are nominal and subject to standard industry tolerances. Pricing Policy: •Firm prices are available for items confirmed in stock for immediate buy and ship. •Adjustable prices are available and subject to metals escalation/de-escalation at the time of shipment. •Backorders or delayed shipments may be subject to price adjustment. •Stock prices and terms of sale are subject to change without notice. Packaging/Shipping Method: •Shipments will be made via common carrier. Special instructions must be stated at the time of order. Flatbed shipments (truckload quantities only) are subject to availability and extra freight charges depending upon geographic destinations. •Length tolerance +/-5% Inventory Holds: •No inventory holds will be accepted. •Stock shall be subject to prior sale. For a complete list of available stock products, contact your General Cable sales representative. 132 Electric Utility Handling Recommendations and Packaging Information 6 Recommended Reel Handling Procedures When off-loading reels from a truck, lower reels carefully using a hydraulic gate, hoist or forklift truck. Never drop reels. If reels must be rolled, roll in opposite direction of the cable wraps to keep cable from loosening on the reel. Don’t When using a hoist, install a mandrel through the reel arbor holes and attach a sling. Use a spreader bar approximately 6 inches longer than the overall reel width placed between the sling ends just above the reel flanges. This will prevent bending the reel flanges and mashing the cable. Do Don’t Do Don’t Don’t Don’t If a forklift is used, approach the reel from the flange side. Position the forks such that the reel is lifted by both reel flanges. Do not allow the lift forks to contact the cable. Care must be taken by the forklift operator not to make sudden turns or stops. Cable shipped on pallets should be stored indoors if possible. Cable shipped on wooden or metal reels may be stored outdoors. When selecting a storage site, consideration should be given to: • Traffic patterns during off-loading • Grade and condition of the soil or pavement • Protection from vehicle damage during the time in storage • Environmental conditions such as exposure to heat, corrosive chemicals, etc. Don’t Cable reels should be stored on hard surfaces resting on the flange’s edge (flanges vertical). Align reels flange to flange and, if possible, arrange so that first in is first out. Multiple reels stacked on top of each other (“Pancake” storage) or storing reels flat (flanges horizontal) is not recommended for bare conductor or medium-voltage cable. The weight of the stack can total thousands of pounds, creating an enormous load on the bottom reel. Also, damage to the reel and/or cable will likely occur when the reel is flipped for transit. A concentration of stress on the reel flange may cause it to break and subsequently damage the cable. 133 Electric Utility Handling Recommendations and Packaging Information Recommended Reel Handling Procedures If cable reels must be pancaked or stored in vertical racks, do not lift the reel by the top flange. Spacers placed under the bottom flange and between reels (two 2x4s placed wide side up) create a space to insert the forks and lift the reel without damaging the cable. If nails are used to secure the spacers, make sure the nails do not go through the flange and into the cable. Don’t For extended storage of bare or insulated cables (spare cable, etc.), reels should be stored cradled between railroad ties, power poles or crossarms. Size and spacing of the supports should raise the flange above the ground. End View of Spacers Do This helps keep the flanges from decaying and prevents the reels from rolling. At temporary storage sites where soil may be soft, preservativetreated plywood sheets may be used to keep reel flanges from sinking into the ground. When possible, the reel wrap or lagging supplied on the reels should be replaced to help protect the cable from inadvertent damage. Under extreme environmental conditions, other measures may be necessary. To prevent entrance of water, cable ends should be sealed with plastic end caps. Electrical tape does not offer a sufficient seal. When lengths are cut, cable ends should be immediately resealed and secured. Low temperatures are a cause for concern when installing cable. Cable should not be installed when the ambient temperatures are less than the cold bend temperature rating of the cable product plus 15°C (i.e., the minimum installation temperature = cold bend temperature rating + 15°C). When applicable, the cold bend temperature rating is indicated on the individual product page in this catalog. Polyethylene insulated jacketed low-voltage cables and polyethylene jacketed medium-voltage power cables are suitable for storage and operation at -40°C and should not be handled or installed when the temperature of the cable or the ambient temperature is below -25°C. For other cable designs, cold weather installation may be limited to higher ambient temperatures. For more information about a specific construction, please contact your General Cable sales representative. If installations are to be carried out where the cable and/or the ambient temperature is below the limit specified above, the cable should first be warmed for a minimum of 48 hours at room temperature (15°C) or higher prior to handling. Cable should be pulled more slowly and trained in place the same day it is removed from storage. Do not impact, drop, kink or bend cable sharply at low temperatures. 134 Electric Utility Handling Recommendations and Packaging Information Standard Package and Shipping Information Shipping Information – Bare Overhead / Individual Package (Reel or Coil) Unless otherwise agreed upon at time of quotation • Standard or special lengths are subject to a manufacturing length tolerance per shipping reel of plus or minus 5% from the specified shipping reel length. • An amount not exceeding 10% of the total quantity of any order may be shipped in random lengths, with no one length shorter than 50% of the specified shipping reel length. • When required, bare conductor may be furnished in matched sets, with the variation in the measured length within each group being no greater than 150 feet for sets of 6 or less, and 200 feet for sets of 9 and 12. In the case where a random length has been produced, the corresponding matched set group will be cut to within a 10 ft. tolerance. For matched set reel identification, on both flanges of the reel, a weatherproof tag is attached that has a Number/Letter identifier marked on it. The number is the numerical sequence from 1, 2, 3, 4, etc for the different sets of matched conductor reels, and the letters A, B, C, etc. identify the matched reels in each set. • For product shipped in coils, 90% of an order quantity shall be furnished in exact lengths as specified in General Cable catalog pages. Exact lengths are specified as having a minus 0% tolerance. Up to 10% of an total order quantity may be supplied in random lengths with no one length shorter than 50% of the specified coil length. • For bare overhead conductor shipped on wood or steel reels, a reel wrap covering is applied over the conductor. The default reel wrap material consists of a NEMA WC26 Level II (Weather Protector). Individual manufacturing plant preferences may utilize heavier grade level of reel wrap material. Shipping Information – Covered and Insulated Cable (Reel or Coil) Unless otherwise agreed upon at time of quotation • Standard or special lengths are subject to a manufacturing length tolerance per shipping reel of plus or minus 10% from the specified shipping reel length. • An amount not exceeding 10% of the total quantity of any order may be shipped in random lengths, with no one length shorter than 80% nor greater than 120% of the specified shipping reel length. • For product shipped in coils, 90% of an order quantity shall be furnished in exact lengths as specified in General Cable catalog pages. Exact lengths are specified as having a minus 0% tolerance. Up to 10% of a total order quantity may be supplied in random lengths, with no one length shorter than 90% of the specified coil length. • For multiplex service drop cable shipped in coils on pallets, the quantity of coils must be in full pallet load quantities. • With the exception of cable sold from stock, in support of the Green Initiative and reducing waste, reels are shipped without a reel wrap covering. 135 Electric ElectricUtility Utility Code Word Classifications 7 Application Type Code Word Overhead Bare Conductor 1350 AAC Flowers Overhead Bare Conductor, Trapezoidal (TW) 1350 AAC/TW Mountains Compact Bare Conductor, Smooth Body (SB) 1350 ASC/SB Reptiles Overhead Bare Conductor 6201 AAAC U.S. Cities Overhead Bare Conductor 6101 A2 and AASC Canadian Cities Overhead Bare Conductor ACSR Birds Overhead Bare Conductor, Trapezoidal (TW) ACSR/TW Birds Compact Bare Conductor, Smooth Body (SB) ACSR/SB Fish Overhead Covered Conductor 1350 AAC Trees Overhead Covered Conductor 6201 AAAC Trees Overhead Covered Conductor ACSS Birds Overhead Bare Conductor, Trapezoidal (TW) ACSS/TW Birds 136 Electric Utility Code Word Index CODE WORDpage CODE WORDpage CODE WORDpage CODE WORDpage A Bobolink/SD.................. 124, 125 Brahma............................ 88, 89 Brant................................. 76, 77 Brant/ACSS................... 104, 105 Breadfruit.............................. 129 Buckeye................................ 128 Bullfinch............................ 82, 83 Bullfinch/ACSS............. 108, 109 Bunting.............................. 82, 83 Bunting/ACSR/TW............ 96, 97 Bunting/ACSS............... 108, 109 Bunting/ACSS/TW........ 116, 117 Bunting/SD................... 124, 125 Butternut............................... 128 Buttonwood.......................... 129 Columbine......................... 56, 57 Columbine/AAC/TW......... 64, 65 Condor............................... 80, 81 Condor/ACSR/TW............. 96, 97 Condor/ACSS................ 106, 107 Condor/ACSS/TW......... 114, 115 Condor/SD.................... 122, 123 Coreopsis.......................... 56, 57 Coreopsis/AAC/TW.......... 64, 65 Corkwood.............................. 129 Cormorant......................... 82, 83 Cormorant/ACSS.......... 108, 109 Corncrake/ACSS........... 106, 107 Corypha................................. 128 Cosmos............................. 52, 53 Cosmos/AAC/TW............. 64, 65 Cowbird/SD.................. 122, 123 Cowslip............................. 56, 57 Cowslip/AAC/TW............. 64, 65 Crabapple.............................. 129 Crane................................. 80, 81 Crocodile........................... 60, 61 Crocus............................... 54, 55 Crow.................................. 80, 81 Cuckoo.............................. 80, 81 Cuckoo/ACSS................ 106, 107 Cumberland/ACSR/TW. 100, 101 Cumberland/ACSS/TW. 118, 119 Curlew............................... 82, 83 Curlew/ACSR/TW............. 96, 97 Curlew/ACSS................ 108, 109 Curlew/ACSS/TW.......... 114, 115 Curlew/SD..................... 124, 125 Cusk................................. 92, 93 Drake/ACSR/TW............... 96, 97 Drake/ACSS.................. 106, 107 Drake/ACSS/TW........... 114, 115 Drake/SD...................... 122, 123 Duck.................................. 78, 79 Adams/AAC/TW................ 66, 67 Alder...................................... 129 Alligator............................. 60, 61 Almond.................................. 128 Anemone........................... 54, 55 Anoli.................................. 60, 61 Anona.................................... 129 Apple..................................... 129 Apricot.................................. 129 Arbutus............................. 54, 55 Arbutus/AAC/TW............. 64, 65 Ash........................................ 129 Aspen............................ 128, 129 Aster.................................. 52, 53 Athabaska/ACSR/TW.... 100, 101 Athabaska/ACSS/TW.... 118, 119 Auk................................... 88, 89 Avocet/ACSR/TW.............. 96, 97 Avocet/ACSS................. 108, 109 Avocet/ACSS/TW.......... 114, 115 Avocet/SD..................... 124, 125 B Bamboo................................. 128 Barwood................................ 129 Bass................................. 92, 93 Bay........................................ 129 Beachwood........................... 129 Beaumont (Avocet)........... 82, 83 Bersfort............................ 88, 89 Bersimis........................... 88, 89 Bittern.............................. 84, 85 Bittern/ACSR/TW............. 98, 99 Bittern/ACSS................. 108, 109 Bittern/ACSS/TW.......... 116, 117 Bittern/SD..................... 124, 125 Bitterroot........................... 56, 57 Blackbird/SD................ 122, 123 Bluebell............................. 56, 57 Bluebell/AAC/TW............. 64, 65 Bluebird............................. 86, 87 Bluebird/................................. 99 Bluebird/ACSR/TW................. 98 Bluebird/ACSS.............. 110, 111 Bluebird/ACSS/TW....... 116, 117 Bluebird/SD.................. 124, 125 Bluebonnet........................ 56, 57 Bluejay/ACSR/TW............. 96, 97 Bluejay/ACSS................ 108, 109 Bluejay/ACSS/TW......... 114, 115 Bluejay/SD.................... 124, 125 Bobolink........................... 84, 85 Bobolink/ACSR/TW.......... 98, 99 Bobolink/ACSS.............. 110, 111 Bobolink/ACSS/TW....... 116, 117 C Calument/ACSR/TW........ 98, 99 Calument/ACSS/TW..... 116, 117 Camellia............................ 56, 57 Camwood.............................. 129 Canary............................... 82, 83 Canary/ACSS................ 106, 107 Canna................................ 52, 53 Canna/AAC/TW................ 64, 65 Canvasback/ACSS........ 108, 109 Cardinal............................. 82, 83 Cardinal/ACSR/TW........... 96, 97 Cardinal/ACSS.............. 108, 109 Cardinal/ACSS/TW....... 114, 115 Cardinal/SD.................. 122, 123 Carillon............................. 88, 89 Carnation.......................... 56, 57 Carnation/AAC/TW.......... 64, 65 Carp.................................. 92, 93 Catawba/ACSR/TW...... 100, 101 Catawba/ACSS/TW....... 118, 119 Cherry................................... 129 Chestnut................................ 128 Cheyenne/ACSR/TW..... 100, 101 Cheyenne/ACSS/TW..... 118, 119 Chickadee......................... 76, 77 Chignecto......................... 88, 89 Chinquapin............................ 129 Chukar............................... 86, 87 Chukar/ACSR/TW............ 98, 99 Chukar/ACSS................ 110, 111 Chukar/ACSS/TW......... 116, 117 Chukar/SD..................... 124, 125 Chutes Des Passes.......... 88, 89 Clayman............................ 60, 61 Cochin.............................. 88, 89 Cockatoo/SD................. 124, 125 Cockscomb/AAC/TW....... 64, 65 Columbia/ACSR/TW......... 98, 99 Columbia/ACSS/TW...... 118, 119 D Daffodil............................. 52, 53 Dahlia................................ 54, 55 Daisy................................. 52, 53 Dipper.............................. 84, 85 Dipper/ACSR/TW............. 98, 99 Dipper/ACSS................. 110, 111 Dipper/ACSS/TW.......... 116, 117 Dipper/SD..................... 124, 125 Diver................................. 84, 85 Diver/ACSS................... 110, 111 Dogwood............................... 129 Dorking............................ 88, 89 Dotterel............................ 88, 89 Dove.................................. 78, 79 Dove/ACSR/TW................. 96, 97 Dove/ACSS.................... 104, 105 Dove/ACSS/TW............. 114, 115 Dove/SD........................ 122, 123 Dragon.............................. 60, 61 Drake................................. 80, 81 E Eagle................................. 78, 79 Eagle/ACSS................... 104, 105 Ebony.................................... 128 Egret.................................. 78, 79 Egret/ACSS................... 106, 107 Eider/SD........................ 122, 123 Erne/SD......................... 122, 123 Eucalyptus............................ 128 F Falcon............................... 86, 87 Falcon/ACSR/TW............. 98, 99 Falcon/ACSS................. 110, 111 Falcon/ACSS/TW.......... 116, 117 Falcon/SD..................... 124, 125 Fig......................................... 129 Filbert.................................... 128 Finch................................. 82, 83 Finch/ACSR/TW................ 96, 97 Finch/ACSS................... 108, 109 Finch/ACSS/TW............ 114, 115 Finch/SD....................... 124, 125 Flamingo........................... 78, 79 Flamingo/ACSS............. 106, 107 Flicker............................... 76, 77 Flicker/ACSR/TW.............. 96, 97 Flicker/ACSS................. 104, 105 Flicker/ACSS/TW.......... 114, 115 Flicker/SD..................... 122, 123 Flounder........................... 92, 93 Frigate/SD..................... 124, 125 Fuchsia.............................. 54, 55 G Gannet............................... 78, 79 Gannet/ACSS................ 106, 107 Gatineau........................... 88, 89 Gecko................................ 60, 61 Genesee/ACSR/TW....... 100, 101 Genesee/ACSS/TW....... 118, 119 Ginkgo................................... 129 Gladiolus........................... 56, 57 Goldenrod......................... 56, 57 Goldfinch........................... 78, 79 Goldfinch/ACSS............ 104, 105 Goldfinch/SD................. 122, 123 Goose................................ 78, 79 Grackle............................. 84, 85 Grackle/ACSR/TW........... 98, 99 Grackle/ACSS............... 108, 109 137 Electric Utility Code Word Index CODE WORDpage CODE WORDpage CODE WORDpage CODE WORDpage Grackle/ACSS/TW........ 116, 117 Grackle/SD.................... 124, 125 Grand Rapids................... 88, 89 Grapefruit.............................. 129 Grosbeak........................... 78, 79 Grosbeak/ACSR/TW......... 96, 97 Grosbeak/ACSS............ 106, 107 Grosbeak/ACSS/TW..... 114, 115 Grosbeak/SD................. 122, 123 Grouse.............................. 88, 89 Guinea.............................. 88, 89 Gull.................................... 80, 81 Gum....................................... 128 James/ACSR/TW.......... 100, 101 James/ACSS/TW.......... 118, 119 Jefferson/AAC/TW........... 66, 67 Jessamine......................... 56, 57 Jessamine/AAC/TW........ 64, 65 Joree................................. 86, 87 Joree/ACSS................... 110, 111 Junco................................ 76, 77 Junco/ACSS.................. 104, 105 Mango................................... 129 Marigold............................ 56, 57 Marigold/AAC/TW............ 64, 65 Martin.............................. 84, 85 Martin/ACSR/TW............. 98, 99 Martin/ACSS................. 110, 111 Martin/ACSS/TW.......... 116, 117 Martin/SD..................... 124, 125 Maumee/ACSR/TW.......... 98, 99 Maumee/ACSS/TW....... 116, 117 Mazama/AAC/TW............. 66, 67 McKinley/AAC/TW............ 66, 67 Meadowsweet................... 54, 55 Meadowsweet/AAC/TW.. 64, 65 Merlin................................ 76, 77 Merrimack/ACSR/TW... 100, 101 Merrimack/ACSS/TW... 118, 119 Mica................................. 88, 89 Minorca............................ 88, 89 Miramichi/ACSR/TW..... 100, 101 Miramichi/ACSS/TW..... 118, 119 Mistletoe........................... 54, 55 Mistletoe/AAC/TW........... 64, 65 Mockernut............................. 128 Mockingbird...................... 86, 87 Mockingbird/ACSS....... 110, 111 Mohawk/ACSR/TW.......... 98, 99 Mohawk/ACSS/TW....... 116, 117 Molles................................... 129 Moloch.............................. 60, 61 Monitor.............................. 60, 61 Montreal............................ 70, 71 Mulberry............................... 129 Mullet............................... 92, 93 Mystic/ACSR/TW............. 98, 99 Mystic/ACSS/TW.......... 116, 117 Oriole................................. 76, 77 Oriole/ACSR/TW............... 96, 97 Oriole/ACSS.................. 104, 105 Oriole/ACSS/TW........... 114, 115 Ortolan.............................. 82, 83 Ortolan/ACSR/TW............. 96, 97 Ortolan/ACSS................ 108, 109 Ortolan/ACSS/TW......... 114, 115 Ortolan/SD.................... 124, 125 Osprey............................... 76, 77 Ostrich.............................. 76, 77 Ostrich/ACSS................ 104, 105 Oswego/ACSR/TW........... 98, 99 Oswego/ACSS/TW........ 116, 117 Owl.................................... 74, 75 Oxbird................................ 82, 83 Oxbird/ACSR/TW.............. 96, 97 Oxbird/ACSS................. 108, 109 Oxbird/ACSS/TW.......... 114, 115 Oxbird/SD..................... 124, 125 Oxlip.................................. 52, 53 H Hackberry............................. 128 Haddock........................... 92, 93 Hake................................. 92, 93 Halifax............................... 70, 71 Hawk................................. 76, 77 Hawk/ACSR/TW................ 96, 97 Hawk/ACSS................... 104, 105 Hawk/ACSS/TW............ 114, 115 Hawk/SD....................... 122, 123 Hawkweed/AAC/TW........ 64, 65 Hawthorn.......................... 56, 57 Hawthorn/AAC/TW.......... 64, 65 Helens/AAC/TW................ 66, 67 Heliotrope......................... 54, 55 Hen.................................... 76, 77 Hen/ACSR/TW.................. 96, 97 Hen/ACSS..................... 104, 105 Hen/ACSS/TW.............. 114, 115 Heron................................ 76, 77 Heron/ACSS.................. 104, 105 Herring............................. 92, 93 Hickory.................................. 128 Hood/AAC/TW................... 66, 67 Hop........................................ 129 Hornbeam............................. 129 Hornbill.............................. 86, 87 Hornbill/ACSS............... 110, 111 Huckleberry.......................... 129 Hudson/ACSR/TW........ 100, 101 Hudson/ACSS/TW......... 118, 119 Hummingbird/SD.......... 122, 123 Hyacinth............................ 54, 55 I Ibis.................................... 76, 77 Ibis/ACSS...................... 104, 105 Ibis/SD.......................... 122, 123 Iris..................................... 52, 53 Ironwood............................... 129 J Jackdaw/SD.................. 122, 123 138 K Kestrel/SD.................... 122, 123 Kettle/ACSR/TW.............. 98, 99 Kettle/ACSS/TW........... 116, 117 Killdeer/SD.................... 122, 123 Kingbird............................ 78, 79 Kiwi................................... 86, 87 Kiwi/ACSS..................... 110, 111 Kiwi/SD......................... 124, 125 Komodo............................. 60, 61 L Lamprey........................... 92, 93 Lapwing............................ 86, 87 Lapwing/ACSR/TW.......... 98, 99 Lapwing/ACSS.............. 110, 111 Lapwing/ACSS/TW....... 116, 117 Lapwing/SD.................. 124, 125 Lark................................... 76, 77 Lark/ACSS.................... 104, 105 Larkspur............................ 56, 57 Laurel................................ 52, 53 Leghorn............................ 88, 89 Les Boules....................... 88, 89 Liana..................................... 128 Lilac................................... 54, 55 Linnet................................ 76, 77 Linnet/ACSS.................. 104, 105 Linnet/SD...................... 122, 123 Logan/AAC/TW................. 66, 67 Longspur/SD................. 122, 123 Lupine............................... 56, 57 Lupine/AAC/TW............... 64, 65 M Macaw.............................. 80, 81 Macaw/ACSS................ 106, 107 Macaw/SD.................... 122, 123 Mackenzie/ACSR/TW... 100, 101 Mackenzie/ACSS/TW... 118, 119 Magnolia........................... 56, 57 Magnolia/AAC/TW........... 64, 65 Mahogany............................. 128 Mallard.............................. 80, 81 Mallard/ACSR/TW............ 96, 97 Mallard/ACSS............... 106, 107 Mallard/ACSS/TW......... 114, 115 N Narcissus.......................... 56, 57 Narcissus/AAC/TW.......... 64, 65 Nasturtium........................ 54, 55 Nasturtium/AAC/TW........ 64, 65 Nectarine.............................. 129 Nelson.............................. 88, 89 Nelson/ACSR/TW.......... 100, 101 Nelson/ACSS/TW.......... 118, 119 Newt.................................. 60, 61 Nuthatch.......................... 84, 85 Nuthatch/ACSS............. 110, 111 O Oakwood............................... 129 Olive...................................... 129 Orange.................................. 129 Orchid............................... 54, 55 Orchid/AAC/TW............... 64, 65 P Pansy................................ 52, 53 Parakeet............................ 78, 79 Parakeet/ACSR/TW.......... 96, 97 Parakeet/ACSS............. 104, 105 Parakeet/ACSS/TW...... 114, 115 Parakeet/SD................. 122, 123 Parrot............................... 84, 85 Parrot/ACSS.................. 110, 111 Partridge........................... 74, 75 Partridge/ACSS............. 104, 105 Partridge/SD................. 122, 123 Paw Paw............................... 129 Peace River...................... 88, 89 Peach.................................... 129 Peachbell.......................... 52, 53 Peacock............................ 78, 79 Peacock/ACSS.............. 104, 105 Pear....................................... 129 Pecan.................................... 128 Pecos/ACSR/TW........... 100, 101 Pecos/ACSS/TW........... 118, 119 Pee Dee/ACSR/TW........ 100, 101 Pee Dee/ACSS/TW........ 118, 119 Pelican.............................. 76, 77 Penguin............................. 74, 75 Peony................................ 52, 53 Persimmon............................ 129 Petrel................................ 88, 89 Petunia.............................. 54, 55 Pheasant.......................... 84, 85 Pheasant/ACSR/TW......... 98, 99 Pheasant/ACSS............ 110, 111 Pheasant/ACSS/TW...... 116, 117 Electric Utility Code Word Index CODE WORDpage CODE WORDpage CODE WORDpage CODE WORDpage Pheasant/SD................. 124, 125 Phlox................................. 52, 53 Phoebe.............................. 76, 77 Phoenix............................. 82, 83 Phoenix/ACSR/TW............ 96, 97 Phoenix/ACSS............... 106, 107 Phoenix/ACSS/TW........ 114, 115 Phoenix/SD................... 122, 123 Pickerel............................ 92, 93 Pigeon............................... 74, 75 Pignut.................................... 128 Pigweed............................ 56, 57 Pike.................................. 92, 93 Piper.................................. 76, 77 Pippit/SD....................... 122, 123 Platte/ACSR/TW........... 100, 101 Platte/ACSS/TW........... 118, 119 Plover............................... 84, 85 Plover/ACSR/TW.............. 98, 99 Plover/ACSS.................. 110, 111 Plover/ACSS/TW........... 116, 117 Plover/SD...................... 124, 125 Plum...................................... 129 Pollock............................. 92, 93 Popinjay........................... 84, 85 Popinjay/ACSS.............. 110, 111 Popinjay/SD.................. 124, 125 Poppy................................ 52, 53 Potomac/ACSR/TW....... 100, 101 Potomac/ACSS/TW....... 118, 119 Powder/ACSR/TW......... 100, 101 Powder/ACSS/TW......... 118, 119 Powell/AAC/TW................ 66, 67 Ptarmigan/ACSS........... 104, 105 Puffin................................ 80, 81 Puffin/ACSR/TW............... 96, 97 Puffin/ACSS.................. 106, 107 Puffin/ACSS/TW........... 114, 115 Puffin/SD...................... 122, 123 Redbird/ACSS............... 108, 109 Redbud.................................. 128 Redwing............................ 80, 81 Redwing/ACSS............. 106, 107 Redwood............................... 129 Ringdove.......................... 84, 85 Ringdove/ACSS............. 110, 111 Ringdove/SD................. 124, 125 Rio Grande/ACSR/TW... 100, 101 Rio Grande/ACSS/TW... 118, 119 Roadrunner....................... 86, 87 Roadrunner/ACSS......... 110, 111 Robin................................. 74, 75 Robson/AAC/TW............... 66, 67 Rook.................................. 78, 79 Rook/ACSR/TW................. 96, 97 Rook/ACSS................... 104, 105 Rook/ACSS/TW............. 114, 115 Rook/SD........................ 122, 123 Rose.................................. 52, 53 Ruddy................................ 80, 81 Ruddy/ACSS.................. 106, 107 Snowbird/ACSS............ 108, 109 Snowbird/ACSS/TW..... 114, 115 Snowbird/SD................. 124, 125 Solah..................................... 128 Sole.................................. 92, 93 Sparate............................. 74, 75 Sparrow............................ 74, 75 Spoonbill........................... 74, 75 Spoonbill/ACSS............. 104, 105 Spoonbill/SD................. 122, 123 Squab................................ 78, 79 Squab/ACSS................. 104, 105 Starling............................. 80, 81 Starling/ACSS............... 106, 107 St. Croix/ACSR/TW....... 100, 101 St. Croix/ACSS/TW....... 118, 119 Stilt.................................... 80, 81 Stilt/ACSS..................... 106, 107 Stork................................. 76, 77 Stork/ACSS................... 104, 105 Stork/SD....................... 122, 123 Sunbird/SD................... 122, 123 Suwanee/ACSR/TW......... 98, 99 Suwanee/ACSS/TW...... 116, 117 Swan................................. 74, 75 Swanate............................ 74, 75 Syringa.............................. 54, 55 Tuatara.............................. 60, 61 Tulip.................................. 52, 53 Tulip/AAC/TW.................. 64, 65 Turacos/ACSS............... 104, 105 Turbit/ACSS.................. 106, 107 Turkey............................... 74, 75 Q Quail.................................. 74, 75 Quince................................... 129 R Rail.................................... 82, 83 Rail/ACSR/TW................... 96, 97 Rail/ACSS...................... 108, 109 Rail/ACSS/TW............... 114, 115 Rail/SD.......................... 122, 123 Rainier/AAC/TW................ 66, 67 Ratite................................. 86, 87 Ratite/ACSS.................. 110, 111 Ratite/SD...................... 124, 125 Raven................................ 74, 75 Redbird............................. 82, 83 S Sagebrush......................... 56, 57 Salamander....................... 60, 61 Santee/ACSR/TW......... 100, 101 Santee/ACSS/TW......... 118, 119 Sapsucker......................... 78, 79 Sapsucker/ACSS........... 104, 105 Sapsucker/SD............... 122, 123 Scaup................................ 74, 75 Scaup/ACSS.................. 104, 105 Schuylkill/ACSR/TW..... 100, 101 Schuylkill/ACSS/TW..... 118, 119 Scissortail........................ 84, 85 Scissortail/ACSR/TW....... 98, 99 Scissortail/ACSS.......... 108, 109 Scissortail/ACSS/TW.... 116, 117 Scissortail/SD............... 124, 125 Scoter................................ 78, 79 Scoter/ACSS................. 106, 107 Sculpin............................. 92, 93 Scup................................. 92, 93 Seahawk........................... 86, 87 Seahawk/ACSS............. 110, 111 Seaway............................ 88, 89 Shad................................. 92, 93 Shasta/AAC/TW................ 66, 67 Shelter Bay...................... 88, 89 Silverbelt............................... 129 Skink................................. 60, 61 Sloe....................................... 129 Smew/SD...................... 124, 125 Snowbird........................... 82, 83 Snowbird/ACSR/TW......... 96, 97 T Tailorbird/ACSS............ 104, 105 Teak....................................... 128 Teal/ACSS..................... 104, 105 Tern................................... 80, 81 Tern/ACSR/TW.................. 96, 97 Tern/ACSS..................... 106, 107 Tern/ACSS/TW.............. 114, 115 Tern/SD......................... 122, 123 Thames/ACSR/TW........ 100, 101 Thames/ACSS/TW........ 118, 119 Thorn..................................... 129 Thrasher............................ 86, 87 Thrasher/ACSS............. 110, 111 Titmouse/SD................. 122, 123 Toad.................................. 60, 61 Tody/ACSS.................... 104, 105 Toronto.............................. 70, 71 Toucan.............................. 76, 77 Toucan/ACSS................ 104, 105 Toucan/SD.................... 122, 123 Towhee.............................. 82, 83 Towhee/ACSS............... 108, 109 Trilium/AAC/TW............... 64, 65 Trillium.............................. 56, 57 Trogon/ACSS................. 104, 105 Truckee/ACSR/TW........ 100, 101 Truckee/ACSS/TW........ 118, 119 V Vancouver......................... 70, 71 Verbena/AAC/TW............. 64, 65 Violet................................. 54, 55 W Wabash/ACSR/TW........... 98, 99 Wabash/ACSS/TW........ 116, 117 Wagtail............................. 84, 85 Wagtail/ACSS................ 110, 111 Walnut................................... 128 Waxwing........................... 74, 75 Wheeler/AAC/TW.............. 66, 67 Whitney/AAC/TW.............. 66, 67 Whooper............................ 82, 83 Whooper/ACSS............. 108, 109 Widgeon............................ 76, 77 Widgeon/ACSS.............. 104, 105 Winnipeg........................... 70, 71 Woodcock......................... 76, 77 Woodcock/ACSS........... 104, 105 Woodcock/SD............... 122, 123 Wood Duck........................ 78, 79 Wood Duck/ACSS......... 104, 105 Y Yukon/ACSR/TW........... 100, 101 Yukon/ACSS/TW........... 118, 119 Z Zinnia................................ 54, 55 Zinnia/AAC/TW................ 64, 65 139 Electric Utility Notes 140 Your Renewable Energy Partner. Yesterday, today and tomorrow. General Cable is your partner for… Powerful Products We have a broad range of wind and solar generation, transmission and distribution cables, linking green power sources to the grid and beyond. Geographic Reach We offer the power and stability of a longstanding global company with local support, servicing a variety of renewable energy partners from anywhere in the world. Leading Technology We develop the most reliable and advanced cabling solutions through experience, innovation and R&D, allowing us to respond to the world's changing energy needs. Other General Cable Products Offered COMMODORE® CATALOG MOR® POLYRAD® CATALOG MV-RIG® CATALOG General Cable 590 Barmac Drive North York, Ontario M9L 2X8 Canada infoca@generalcable.com Form No. UTY-0018-R0312 43641 CCW® CATALOG X-TRACT® ESP CATALOG Telephone(800) 561-0649 Fax (800) 565-2529 www.generalcable.com GEPCO® CATALOG SHEERWIRE™ CATALOG