ioSelect DC to Frequency Isolating Signal Conditioner
Transcription
ioSelect DC to Frequency Isolating Signal Conditioner
UniPak™ UP475 DC to Frequency Isolating Signal Conditioner • Selectable Current or Voltage Input Range • Input Sensor Supply (20 Vdc @20 mA) • Frequency Output from 0.5 pph to 10 kHz • Open Collector or Reed Relay Output • 3-Way Isolation −1500 Vac Input/ Power/ Output • AC or DC Power (19-40 Vdc or 19-28 Vac) • DIN Rail Mount (TS 35) • Removable Terminal Blocks • LED Status Indicator The UniPak™ UP475 converts a DC current or voltage signal to a proportional, linear frequency signal providing 1500 Vac isolation between the frequency source, the dc output and power to the UP475. A typical application is totalizing applications, where the total number of pulses counted in a given time period represents the time integral of the DC input. If, for example, the input represents a flow in gallons per hour, then the time integral of this flow signal (total count) will represent total gallons. The input of the UP475 can supply voltage for a 2-wire current loop, up to 20 V dc. There are two output choices, an npn open collector or a reed relay. The open collector provides 30 V dc, up to 300 mA. The relay is rated for 30 V ac or dc and 100 mA. The open collector output can be used to drive electronic counters or other high speed inputs. The relay can be used to drive electromechanical counters when connected to an external AC or DC power source. The unsurpassed flexibility means that one model can meet many application requirements. Signal Conditioning flexibility and use made simple from ioSelect, powered by Seneca (Z104). General Specifications Input Current 0-20 mA, 4-20 mA, active or passive Excitation 20 Vdc (stabilized) @ 20 mA Impedance 100 Ω/passive Voltage 0-5, 1-5, 0-10 or 2-10 Vdc Impedance 1 MΩ Overload 100 mA continuous Output NPN open collector 30 Vdc @ 300 mA maximum Reed Relay 30 Vdc, 100 mA maximum LED Status Presence of Power Offscale Input Power 19-40 Vdc or 19-28 Vac Power Consumption 2.5 W Ordering Information: 877 3 GET IOS (877.343.8467) IOS-UP-475 IOS-Z104 Performance Specifications Isolation: 3 way isolation 1500 Vac input/output/power Accuracy < 0.2% of Full Scale Linearity 0.05% Thermal Stability 0.02%/°C Response Time < 150 ms Humidity: 30-90% @ 40 °C (104 °F) Operating Temperature 0 to 50 °C (32 to 122 °F) Storage Temperature -40 to 80 °C (-40 to 176 °F) Dimensions 17.5 x 100 x 112 mm (w x h x d) (0.69 x 3.84 x 4.14 in) Weight 150 g (5.3 oz) DC to Frequency Isolating Signal Conditioner DC to Frequency Isolating Signal Conditioner www.ioselect.com Rev: 2/23/2011 UniPak™ UP475 / Z104 DC to Frequency Isolating Signal Conditioner Wiring Instructions Input Power Current using Internal Loop Power Supply 6 A 4 19 to 40 Vdc Externally Powered Current 6 2 Voltage 6 + or 19 to 28 Vac 3 Not Polarity Sensitive *Do not exceed upper limits of supply voltage V A + 1 1 Output ! Terminal Connections Reed Relay + NPN 9 7 - The reed-relay output can only be used with frequencies below 40 12 Hz. The reed-relay output is switched on by setting DIP switch 10 1 of the RANGE switch to ON. The transistor output is always on. Configuration 1. Input Common for Voltage and 2-wire and Configuration 2. Power 3. Power 4. Current Input Source 1 2 3 4 5 6 5. Configuration (+) 6. Input (+) 7. Relay Output (See Diagram) 8. No Connection 9. Relay Output (See Diagram) 7 8 9 10 11 12 10. NPN Output Common(See Diagram) 11. No Connection 12. NPN Output (+) (See Diagram) Set the output frequency: Requires a calibrated voltmeter. The meter is connected to terminals 5 (+) and 1 (-) and set to a 10 V scale. 10 × P × K The desired output is calculated by the formula: Vout = FS Where P = pulses /hour, K is the constant on the UP475 label & FS is the full scale of the range selected in the RANGE SWITCH table. Set the INPUT SWITCH to the “Configuration” switch INPUT SWITCH settings. Use the front mounted potentiometer to adjust Input 1 2 3 4 output to the desired level. 0-20 mA Once the output range is set the input is configured by setting the INPUT SWITCH and then wiring to the designated input terminals for the input used. Example: P = 90 p/h (pulses per hour). The voltage should be set to: (10 x 90 x 1.05) /137.33 = 6.881 V. KEY: RANGE SWITCH 5 6 Frequency (pph) 1 2 3 4 5 6 36 M - 8.4 M 4-20 mA 9 M - 2.1 M 0-5 V 2.25 M - 525 k 1-5 V 562.5 k - 131.25 k 0-10 V 140.625 k - 33 k 2-10 V 35.15625 k - 8.2 k Configuration 8.78906 k - 2.1 k Often the desired output is listed in Hz (pulses per second) or rpm (revolutions per minute). Use the following to convert to p/h (pph or pulses per hour). Pulse/rev will be dependent on application. pulse 60 sec 60 min pulse × × = Hz × 3600 = sec 1 min 1hour hour rev pulse 60 min pulse × × = min rev 1hour hour = ON 2.19727 k - 513 549.32 - 129 137.33 - 33 34.33 - 8 8.58 - 2 2.15 - 0.5 Installation The UniPak™ UP475 is designed to be mounted on 35 mm DIN rail. Adequate ventilation may be needed to ensure optimal operating conditions. Avoid mounting modules over devices that generate heat. If operating at the high end of the temperature specifications (near 50 °C/ 125 °F) it may be necessary to separate the modules by at least 5 mm (0.2 in). Other Conditions that may Contribute to High Operational Temperature: · High power voltage (> 30 Vdc / > 26 Vac) · Powering an input sensor and one output consistently at a high output level Power supply upper limits must not be exceeded. Excessive power level will result in damage to the module. EN50081-2 EN50082-2 EN61010-1 877 3 GET IOS (877.343.8467) www.ioselect.com Rev: 2/23/2011