“Grounding for ESD, EMI, and Personal Safety” by Larry Labayen

Transcription

“Grounding for ESD, EMI, and Personal Safety” by Larry Labayen
Grounding
ESD Technical Seminar in San Diego
April 23, 2013
Copyright © 2013
T O TA L
S I T E
S O L U T I O N
Information contained in this presentation shall not be copied, duplicated or used without the written consent from Lyncole XIT Grounding LLC, a VFC company.
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
What Is Grounding?
An electrical connection, whether intentional or
accidental between an electrical circuit or
equipment and the earth, or to some conducting
body that serves in place of the earth.
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Reasons For Grounding
– Personnel safety and equipment
protection by providing a path to safely
dissipate any unwanted charges or
potentials.
– Ensure equipment performance and
protection
– Satisfy manufacture’s warranty
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Electrical
Protection Pyramid
RF
AC Surge
Instrumentation
Telco Data
ESD
Lightning
Safety
GROUNDING
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Earth Resistance
The ohmic resistance between the grounding electrode and
a remote earth (remote grounding electrode).
1 ft.
10 ft.
40 ft.
80 ft.
200 ft.
> 200 ft.
12 Ω
20 Ω
22 Ω 23.8 Ω
24 Ω
Remote Earth
∞
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Typical Earth Resistance Requirements
Industry Standard
Target
Upper Target
NFPA 70 NEC
25 Ω
Two rods regardless of resistance
MIL-HDBK-419
10 Ω
IEEE Standard 142
Equipment Dependent
Equipment Dependent
IEEE Standard 1100
Equipment Dependent
Equipment Dependent
Motorola Standard R-56
5Ω
10 Ω
Telecommunications
5Ω
10 Ω
Emerson DeltaV
1Ω
3Ω
Essilor
3Ω
GE Medical Systems
2Ω
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Grounding System Components
Equipment
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Electrical Noise
Any unwanted electrical signal which produces
undesirable effects in the circuits of the control
system in which they occur.
Noise Sources
Natural
Example
- Lightning
- ESD
Incidental
-
Fault
Motors
Power switching devices
Dissimilar metals
Intentional
-
Two way radio (mobile, handheld)
Broadcast (AM, FM, Satellite)
Cellphone
WiFi
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
25 Grounding
Lightning
Strike
18,000A
Potential Rise will be
~450KV at the site
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
5 Grounding
Lightning
Strike
18,000A
Potential Rise will be
~90KV at the site
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Benefits of a Properly Designed
Grounding System
– Predictable Results
– Improved Personnel Safety
– Improved Equipment Reliability
– Protection from Lightning/Power Surges
– Improved Equipment Performance
– Less System Noise
– Less Stress on Equipment and Fewer Operating Errors
– Improved Power Quality
– Meet Mfr’s Warranty Requirements
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Soil Resistivity
Basics
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Soil Resistivity
Signal
Generator
~
1 Meter Square
Earth
The resistance of earth to current flow between
opposite faces of a cubic earth that is one cubic meter
in volume. Measured in Ohms-meter.
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Soil Resistivity
IS
IT
The key variable in system
design
Determines grounding system
resistance
Changing from site to site
Depends on:
a. Soil type
b. Moisture content
c. Electrolytes
d. Temperature
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Soil Resistivity Comparison
Soil Type
Resistivity (ohms-cm)
60
Lynconite II
Surface Soil
100
5,000
Clay
200
10,000
5,000
100,000
10,000
1,000,000
Limestone
500
400,000
Shales
500
10,000
2,000
200,000
Sand and Gravel
Surface Limestone
Sandstone
100,000
Granites, Basalts, etc
Decomposed Gneisses
5,000
50,000
Slates, etc
1,000
10,000
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Conditions Affecting Soil Resistivity
Moisture
Electrolytes
200000
Temperature
12000
80000
70000
160000
140000
120000
100000
80000
Resistivity (ohm-cm)
10000
Resistivity (ohm-cm)
Resistivity (ohm-cm)
180000
8000
6000
60000
50000
40000
30000
4000
60000
20000
40000
2000
10000
20000
0
0
1 2 3 4 5 6 7 8 9 101112
Moisture % by Weight
0
0
0.1
1
5
10
20
Added Salt % by Weight of Moisture
23 32 32 50 68 86 104 122
Temperature (deg F)
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Soil Resistivity
Testing
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
4-Pt. Wenner Method
C2
15 ft
P2
C1
P1
5 ft
10 ft
0 ft
A
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Soil Resistivity Testing
4-Pt. Wenner Method
Site Area
Direction of Test
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
4-Pt. Wenner Method
 = 1.915 AR
Probe Spacing
(Feet)
Meter Reading
(Ohms)
Calculated
Resistivity

(Ohm-Meter)
5
52.00
497.90
10
19.68
370.87
15
10.16
292.00
20
6.53
250.10
30
4.30
247.04
40
10.80
827.28
60
7.40
850.26
80
5.58
855.60
100
4.44
850.26
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Soil Model
100ft Vs 40ft Test
Apparent
Resistivity
(Ohm-meters)
Soil model based on a
100-ft. deep investigation
200
150
100
Soil model based on a
40-ft. deep investigation
50
0
0
50
100
150
Average Inter-Electrode Spacing
(feet)
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Characteristics
of
Ground Electrodes
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Spheres of influence
Radius [ R ] or Primary
Spheres
Concentric Shells
Rod Length ( L )

Electrode Depth
(Length) equals the
radius of the effective
sphere of influence R = L
(uniform soil resistivity)
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Spheres of influence
– Resistance due to sum of a series
of “shells” surrounding the
electrode
●●●
– Closest “shell” has the smallest
circumference. It has the least
cross sectional area resulting in
higher resistance
– Outer “shells” have larger
circumference. It has a larger
cross sectional area resulting in
lower resistance
– Lower the resistance of closest
“shell”, lower the overall
resistance
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Resistance vs. Electrode Length
(in a defined space)
300
𝑹=
Resistance (Ohms)
250
𝝆
𝟒𝑳
ln[
− 𝟏]
𝟐𝝅𝑳
𝒓
ρ = 100,000 ohm-cm
r = 7.94 cm
(5/8 in rod )
200
150
100
50
0
10
20
30
40
50
60 70 80 90 100 110 120 130 140 150 160
Electrode Length (Feet)
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Resistance vs. Number of Electrodes
(in a defined space)
100
80
60
40
20
0
1 Rod
2 Rods
+
3 Rods
+
4 Rods
+
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Types
of
Ground Electrodes
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Methods of Grounding and Their
Limitations
Driven Rods
– Copper-clad rods driven into the ground
Drawbacks:
– Easily affected by the environment, aging,
temperature, and moisture.
– Resistance increases steadily with age.
– Usually damaged during installation.
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
“Driven rods have always worked for
us...”
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Methods of Grounding and Their
Limitations
Water Pipes
– Large amount of underground metal
providing a “theoretically good ground.”
Drawbacks:
– Difficult to test / impossible to maintain.
– Plastic inserts destroy circuit integrity.
– Condensation and corrosion are accelerated.
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Methods of Grounding and Their
Limitations
Ground Plates
– Thin copper plates placed under poles or
supplementing counterpoises.
Drawbacks:
– Small sphere of influence, higher resistance
reading.
– Susceptible to environmental changes and
corrosion.
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Methods of Grounding and Their
Limitations
Building Steel
– Large metallic structure
– Disperses fault current equally over large
area
Drawbacks:
– May have little or no connection to earth
– May not be electrically continuous
– Carries large amounts of electrical noise
– Creates multiple “Ground Loops”
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Methods of Grounding and Their
Limitations
Ufer Grounds / Concrete Encased Electrodes
– Copper wire grid incorporated into building
concrete foundation.
Drawbacks:
– Impossible to test and maintain.
– Time and gradual removal of moisture can
cause change in foundation integrity.
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Electrolytic Rod: XIT Grounding System
Slotted box cover
Protective cover box
U-bolt test connection
Breather holes
Exothermic connection
4/0 copper conductor
Electrolytic ground rod
Backfill material
All copper
Non-hazardous earth salts
Weep holes
Electrolytic roots
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
The XIT Grounding System (Horizontal Shaft)
Slotted box cover
Protective cover box
U-bolt test connection
Breather holes
Exothermic connection
# 6 thru 1000 MCM copper conductor
3’
Electrolytic ground rod
Backfill material
All copper
Weep
holes
Electrolytic roots
10’
Non-hazardous
earth salts
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Resistance Variance Over a Year:
XIT Rod -v- Driven Rod
60
50
40
Driven Rod
XIT Rod
30
20
10
0
High
Low
Median
Study done by IAEI
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Grounding Calculations
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Earth Ground Resisitivity Nomograph
This example reflects a 5 ohm ground resistance with a soil resistivity of 1800
ohms/cm using 5/8 inch diameter copper clad steel rods buried to a 10 ft depth
D
Directions
1)
Select required
resistance on R scale
2)
Select apparent
resistivity on P scale
3)
Lay straightedge on R
and P scale, and allow
to intersect with K scale
4)
Mark K scale point
5)
Lay straightedge on K
scale point and DIA
scale and allow to
intersect with D scale
6)
R
Point on D scale will be
the depth required for
R=Ground Rod
resistance on R scale
Resistance-Ohms
K
DIA
P
P=Soil
Resistivity
(ohms-cm)
D=Rod
Depth
(feet)
DIA= Rod
Diameter
(in)
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Resistance of Single Rod
Green Book IEEE-142 (Table 13)
  4L 
R
 1
 ln
2L  a

R = Resistance
L = Length of Rod
ρ = Resistivity
a = Radius of rod
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Influence of Resistivity
Example:
Soil Type: Clay
 = 1500 ohm-cm
5/8” x 10’ Driven Rod
R = 4.963 ohms
Soil Type: Sand
 = 50000 ohm-cm
5/8” x 10’ Driven Rod
R = 165.447 ohms
1500  1219.2 
 1
 ln
1915.11  0.794

R  0.78327.337  1
R
R  4.963
50000  1219.1 
 1
 ln
1915.11  0.794

R  26.1087.337  1
R
R  165.447
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Resistance of Two Rods
(Spacing Greater than Length)
  4L   
L2 2 L4 
1  2  4 ... 
R
 1 
 ln
4L  a
4

s
5s 

 3s
1500
 7.3367  1  0.19581  0.94167
3830.23
R  2.4814  0.18439
R  2.52122
R
ρ = Resistivity (1500 Ohm-cm)
L = Length of Rod (304.8cm or 10 ft.)
a = Radius of rod (0.794cm or 5/8in.)
s = Spacing between rods (609.6cm or 20 ft.)
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Resistance of Horizontal Wire
(100 Feet of 4/0 AWG Buried 30 Inches Deep)
(1500 ohm-cm soil)

  4L
4L
s
s2
s4
 ln
R
 ln
2


... 
2
4
4L  a
s
2 L 16 L 512 L 
1500
9.114  3.689  2  0.05  0.000625  0.000000195
19151.15
R  0.0783  10.852
R  0.8499
R
ρ = Resistivity (1500 ohm-cm)
2L = Length of Wire (3048cm or 100 ft.)
a = Radius of Wire (0.671cm or 0.264 in.)
s/2 = Depth of conductor (76.2cm or 30 in.)
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Grounding Design
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
ABC ENGINEERING
John Smith
Date:
November 30, 2008
RE:
Site #
Grounding Option
N/A
Address:
Project #:
Acct Mgr.:
080020
Zahid Mitha
Engineer:
Yellow Brick Road
#1 Main Street
Anywhere, USA
XYZ Communication
Julian Hristov
These options are conservative calculations of the grounding system, based on testing data
provided by ABC Engineering. These designs will provide a stable, system that will be
unsusceptible to environmental variables, such as changes in temperature and precipitation, and
may improve with time.
NUMBER OF
ELECTRODES
ELECTRODE
TYPE
TYPE AND SIZE
OF GRID
PLACEMENT
OF
ELECTRODES
CALCULATED
EARTH
RESISTANCE
Grounding Option

3
K2L-10CS
As illustrated
(Drawing 1)
As illustrated
(Drawing 1)
< 25 ohms
5
K2L-10CS
As illustrated
(Drawing 2)
As illustrated
(Drawing 2)
< 10 ohms
8
K2L-10CS
As illustrated
(Drawing 3)
As illustrated
(Drawing 3)
< 5 ohms
Note: Lyncole recommends that the copper conductor be covered with Lynconite II
or Lyncole Grounding Gravel™ to protect from corrosive action of the soil and to
promote conductivity.
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Grounding System
Resistance Testing
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Ground System Testing
– Why Test Grounds?
– Determine Baseline
– Validate Construction
– Confirm Design Spec
Satisfied
– Satisfy Warranty Reqs
– Ensure Equip Protection & Performance
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Testing Methods
− Two Test Methods
− Fall Of Potential Test (Three Point/62% Test)
− Clamp-On Test
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Fall of Potential Test
– Advantage
– Recognized As Accurate
– Most Commonly Utilized (IEEE 81)
– Disadvantages
– Results are Frequently Invalid
– Requires Isolated Ground System
– Requires Large Area; 10X rod length (ideal) or 5X rod length (min)
– Time Consuming
– Access To Soil
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Fall of Potential Test
25
50-100ft Spacing
20
15
Readings Not Impacted by Spheres
of Influence
10
05
Plateau
System
Resistance
Current
Probe
00
Spheres of
Influence
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Ground System Testing
Required Equipment
– 3 / 4 Pole Tester
– AVO / AEMC
– Test Kit
– Probes
– Conductor
– Tape Measure
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Fall-of-Potential Method
C1
P1
C2
Ground
Rod
Under
Test
P2 Auxiliary Voltage Electrode
1 ft
Remote
Current
Electrode
Earth
10%20% 30% 40% 50% 60%70%80% 90%
10 x depth of electrode
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Fall-of-Potential Test Results
P2
Distance
(%)
P2
Distance
(Feet)
Measured
Resistance
(ohms)
Resistance
Change
(ohms)
1
1
67.0
10
10
114.5
47.5
20
20
119.6
5.1
30
30
121.3
1.7
40
40
122.2
0.9
50
50
122.5
0.3
60
60
123.1
0.6
70
70
123.7
0.6
80
80
126.6
2.9
90
90
141.8
15.2
100
100
C2 probe
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Fall of Potential
– Why 10+ Samples?
– Single Point Could Be Misinterpreted
– Data must be plotted
– Visual Plateau
– Confirms Test Validity
Measured Resistance (ohms)
150
140
130
120
110
100
90
80
70
60
1
10
20
30
40
50
60
70
80
90
P2 Probe Distance (Feet)
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Ground Resistance Testing
Clamp-On Resistance Testing
AEMC 3711 Clamp-On Meter
– Convenient, Quick, Easy
– Does Not Require Disconnecting
Equipment
– Measures Current on the Ground
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Clamp -On Meter Operation
2 Control Xformers
Current Flow
R=E/I
??? ohms
Current Flow
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Clamp-On Resistance Testing Example
R
Rx
Rn-1
Rn
1
I
V
Rx
R1
R2
R3
Rn-1
Rn
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Clamp-On Meter Operation
Utility Neutral Line
Parallel Paths
NeutralGround
Bond
Grounding
Conductor
Series
Loop
Current Flow
R = ???
E/I
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Conclusion
− Grounding is the foundation for personnel safety and system
performance.
− Low impedance to earth minimizes potential rise in event of
lightning, fault or heavy load switching.
− A good grounding system implementation always starts at the
design phase.
− Soil resistivity testing is the key variable for grounding design.
− Effective, pragmatic and economically sound earth resistance
targets is engineered using computer aided grounding design
software.
− Test the system before commissioning.
− Monitor ground system to ensure system performance.
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com
Where Grounding Bonds With Science
®
3547 Voyager Street Suite 204 ● Torrance ● CA 90503 ● Tel: 800.962.2610 ● Email: info@Lyncole.com ● Web: www.Lyncole.com

Similar documents

Released courtesy of Areva Resources Canada and UEX

Released courtesy of Areva Resources Canada and UEX sandstone above the SLC but the TAMT inverted results are not as smoothly varying and the conductive halo not as wide. Within the basement, the TAMT inverted results place conductive material aroun...

More information