Kingfisher RTUs — How to create multiple variables using Toolbox PLUS+

Transcription

Kingfisher RTUs — How to create multiple variables using Toolbox PLUS+
Kingfisher RTUs — How to create multiple
variables using Toolbox PLUS+ by Vishal Prakash
TECHNICAL
BRIEF
Did you know that, when using Toolbox PLUS+ with Kingfisher RTUs, it is very simple to create multiple
variables of different types, for different protocols, and to duplicate entire configurations?
So, how is this done? As to whether it is simple, I will allow you, the user, to decide!
The Kingfisher CP-30 and G-30 based RTUs include support for all six programming languages under the
IEC61131-3 standard via the ISaGRAF programming environment and support for a multitude of protocols
including Modbus, DNP3, SNMP, Kingfisher, DF1, and NTP, to name a few. Given this level of superior
functionality, it is important for the user to be able to program the RTUs on a simple and efficient manner.
It is assumed that the user has a basic understanding of Kingfisher concepts, industrial protocols, and the
configuration software, Toolbox PLUS+.
First, let’s look at how easy it is to create multiple variables. Take two of the most common industrial protocols,
Modbus and DNP3, each have several different types of objects — Holding Registers, Discrete, Coils, Binary Inputs,
and Analog Inputs etc. To create multiple objects of any type for either protocol, follow the steps listed below.
1. Open Toolbox PLUS+
2. Create a project
3. Create a RTU as desired
4. Right Click on the RTU name and go to properties, add the desired communication protocols (see Figure 1)
Figure 1: Enabling protocols in a CP-30 or G-30 RTU
www.servelec-semaphore.com
TECHNICAL BRIEF
5. Configure the communication ports and link the desired protocol to the port
6. Go to the “Dictionary” on the bottom left hand corner. Click on “New” in the workspace. A window will
appear. Click on the “Multiple” tab (see Figure 2)
Figure 2: Creating multiple protocol variables of different types
7. Now, simply select the Format (protocol), Type, and Range. As these parameters are being configured, the
“Description” changes dynamically informing the user what type of variables will be created.
8. Once all parameters have been configured, click on OK
9. That’s it! For the result, see Figure 3 below.
Figure 3: Creating the alarm condition to send the report to the SD Card
www.servelec-semaphore.com
TECHNICAL BRIEF
The user can now edit each variable, export to Excel®, make changes, import back into Toolbox PLUS+, or make
changes within the ISaGRAF interface.
Next, it is very simple to replicate an entire RTU configuration! To do this, create the Project and RTU. Populate
as required with the right I/O and communication modules, variables, protocols and ISaGRAF programs
(see Figure 4).
Figure 4: A fully configured RTU displaying list of ISaGRAF programs
To replicate this RTU, in full, simply select the RTU; press Ctrl+C on the keyboard, click anywhere in the project
tree space and press Ctrl+V on the key board! The same can be achieved by right-clicking on the RTU name,
select “Copy” and then right-click on the Project Name and select “Paste”.
That’s it! See the result below (Figure 5).
www.servelec-semaphore.com
U.S.A.
Semaphore Americas Inc.
280 Wekiva Springs Road
Suite 3030
Longwood, FL 32779
U.S.A.
P +1 (844) 475 8020
support.americas@servelec-semaphore.com
Australia
Semaphore
Unit 8, 3-5 Gilda Crt
Mulgrave, Victoria 3170
Australia
P+61 (03) 8544 8544
F +61 (03) 8544 8555
Info.kingfisher@servelec-semaphore.com
Europe
Semaphore Belgium
Waterloo Office Park — Building “M”
Dreve Richelle, 161
B-1410 Waterloo
Belgium
P+32 (2) 387 42 59
F +32 (2) 387 42 75
info.tbox@servelec-semaphore.com
© 2013 Semaphore. All rights reserved.
Kingfisher is a trademark of Semaphore.
All other marks may be trademarks of their
respective owners. 1361011 03/14
Figure 5: Duplicating entire configurations — in a single copy and paste action!
You will notice that the RTU address is automatically appended. This is because every RTU on a connected
telemetry network must have a unique address. RTU configurations can be copied across projects or groups.
For more information on the above, please refer to the online help in Toolbox PLUS+.
Please visit our website, www.servelec-semaphore.com/mykingfisher (must be a registered user) for the
latest versions of the Kingfisher manuals and Toolbox PLUS+ programming software. The portal also contains
other useful information such as example programs and firmware updates.