MS-400AD Adressable Manual Stations Installation Sheet

Transcription

MS-400AD Adressable Manual Stations Installation Sheet
MS-400AD Adressable Manual Stations Installation Sheet
Mircom’s MS-400AD Series are single action manual alarm stations. The MS-400AD Manual stations are constructed of
durable aluminium and finished in red. An abrasion resistant label with large, raised letters provides clear legible
instructions. The model MS-402AD (two stage) is similar to the MS- 401AD (single stage) except it contains an additional
General Alarm (G.A.) N.O. switch. For safety reasons, the G.A. switch is only accessible after the handle has been pulled.
A special key is supplied with each unit.The model MS-405AD is similar to the MS-401AD except it has an additional N.O.
switch. The model MS-407AD is similar to the MS- 401AD except it has an additional N.C. switch. All manual stations can
be easily converted from single action to double action station by the addition of the MS-DA double action lever.
All manual fire alarm stations shall be installed as per the specific requirements outlined in the UL codes, as well as all
other applicable national or local codes. Final acceptance is subject to the local authority having jurisdiction.
Wiring
MS-401AD(U), MS-402AD, MS-405AD, MS-407AD(U)
}
FROM PREVIOUS STATION
} TO NEXT STATION OR
RED
BLK
END OF LINE DEVICE
~
RED
0-9
ADD.SW
BLK
- BLACK
+ RED
ADDRESSABLE MODULE
N.O.
SWITCH
YEL
10-99
ADD.SW
PUR
YELLOW
N.O.
SWITCH
}
FROM PREVIOUS STATION
RED
RED
BLK
BLK
Notes:
1. Wire as shown so that supervision of connections
is maintained.
2. Switches shown in the Station Closed position.
} TO NEXT STATION OR
END OF LINE DEVICE
3. Maximum Wire Size: No. 12 AWG.
4. Refer to Fire Alarm Control Panel manual for
addressable module setting.
Specifications & Dimensions
Switch Rating:
1 Amp @ 30VDC
0.1 Amp @ 12OVAC
Surface-Mount Backbox:
Models
MS-401AD(U):
MS-402AD:
MS-405AD:
MS-407AD(U):
MS-DA:
2" x 4" x 2 1/4"
Note:
• The suffix “U” denotes USA version.
Intelligent Addressable Single Stage Manual Station
Intelligent Addressable Dual Stage Manual Station
Intelligent Addressable Single Stage Manual Station with additional N.O. Switch
Intelligent Addressable Single Stage Manual Station with additional N.C. Switch
Double Action Lever Kit (converts any of the above to double action stations)
Canada
25 Interchange Way
Vaughan, ON L4K 5W3
Tel: (888) 660-4655
(905) 660-4655
Fax: (905) 660-4113
U.S.A
60 Industrial Parkway, PMB 278
Cheektowaga, New York 14227
Tel: (888) 660-4655
(905) 660-4655
Fax: (905) 660-4113
www.mircom.com
LT-583 Rev. 1 060607