Control Cabinet Type A31-P*-*****

Transcription

Control Cabinet Type A31-P*-*****
Control Cabinet
Type A31-P*-*****
Exepd GmbH
i_PARK TAUBERFRANKEN 23
97922 Lauda-Königshofen
Germany
Phone: ++49 (0) 9343 627055-0
Fax: ++49 (0) 9343 627055-99
Mail: info@exepd.de
Operation Manual
Control Cabinet
Type A31-P*-*****
1.
Product Description ....................................................................................... 3
2.
Normal Handling ........................................................................................... 3
3.
Used Standards ............................................................................................ 3
4.
Technical Data .............................................................................................. 4
5.
Electrical Data .............................................................................................. 5
6.
Components / Cable Glands............................................................................ 5
7.
Safety references .......................................................................................... 5
8.
Installation ................................................................................................... 6
Mounting ........................................................................................................ 6
Installation ...................................................................................................... 6
9.
Starting ....................................................................................................... 6
10.
Special conditions for safe use ........................................................................ 7
11.
Operation, Maintenance and Elimination of Disturbances .................................... 7
12.
Accessories and spare parts ........................................................................... 7
13.
Service address ............................................................................................ 7
A31-P0-B0001-Rev3 eng
09/04/2014
www.exepd.de
page 2 of 8
Operation Manual
Control Cabinet
Type A31-P*-*****
1.
Product Description
The control cabinet, type A31-P*-***** is a non-portable installed, explosion protected
electrical equipment for use in explosive areas by zone 1 or zone 21.
It is used for the installation of explosion proof components and/or non-explosion proof
components. The control cabinet basically consists of internal fixing plates at the internal
rear side for mounting components.
The control cabinet consists of the materials polyester, coated steel plate or stainless
steel. It contains in category 2G a separate certified monitoring system. The monitoring
system has the function of "Ex px" and "Ex t" in category 2D respectively.
The construction and functionality of the Control Cabinet for the use in the marked Ex
zones is tested and documented by Exepd GmbH piece by piece. The passed quality test
is shown by marking the Control Cabinet with the Ex type label.
2.
Normal Handling
The Control Cabinet A31-P*-***** is built for local installation in Ex zone 1 or zone 21. It
is not allowed to install the product in zone 0 or zone 20.
Inside the Control Cabinet there are explosion protected and/or not explosions protected
electrical and mechanical equipment and their accessories installed.
The individual type label shows all the electrical and for the installation in hazardous area
required data.
If there is no information about the ambient temperature on the type label, the Control
Cabinet can be used in the temperature range of -20°C up to 40°C.
It is prohibited to make any changes on the Control Cabinet without contacting the
manufacturer. This applies to the associated safety equipment, and the equipment
mounted on or in the Control cabinet.
To follow this manual help to prevent permanent deformation of the Control Cabinet by
an increased pressure and thus a hazard to people and equipment. The purge gas supply
shall not exceed the limits, this is necessary for the safety operation of the Control
Cabinet. If another purge gas is used as air, it must be ensured that the minimum
oxygen content in the ambient space is not exceeded. Maybe a separate purge gas
exhaust line needs to be placed outdoors.
3.
Used Standards
(Depending on the assembled components)
EN 60079-0:2009 / General requirements
EN 60079-2:2007 / Overpressure monitoring "p"
EN 61241-4:2007 / Dust protection „pD"
(EN 60079-31)
EN 60079-7
EN 60079-11
A31-P0-B0001-Rev3 eng
09/04/2014
www.exepd.de
page 3 of 8
Operation Manual
Control Cabinet
Type A31-P*-*****
4.
Technical Data
Cabinet material
Type
Type
Type
Type
A31-P1-*****
A31-P3-*****
A31-P4-*****
A31-P5-*****
Polyester
Stainless steel V2A
Stainless steel V4A
Sheet plate
Protection according to 60529/IEC 60529: IP 55 up to IP 66
Ambient temperature range:
(Please refer to type label for details)
Temperature class T3, T4, or T5
Temperature class T6
max. -40°C up to + 60°C
max. -20°C up to + 40°C
Maximum surface Temperature (II 2D)
80°C
Mechanical strength to DIN EN 60079-2
Minimum pressure: 80 Pa (0.8 mbar)
Maximum pressure: 2500 Pa (25.0 mbar)
Maximum test pressure: 3750 Pa (37,5 mbar)
Quality of purge gas
The quality of the purge gas must be in accordance with ISO 8573-1 Class 543
correspond to:
Residual dust: less than 40  m
Residual water dew point +3 ° C
Residual oil content: 1 mg / m³
maximum temperature: + 40 ° C
Explosion protection:
(Please refer to type label for details)
II 2(1) G Ex px [ia/ib] IIB/IIC T3/T4/T5/T6 Gb und/oder
II 2(1) G Ex e px [ia/ib] IIB/IIC T3/T4/T5/T6 Gb oder
II 2 D Ex pD 21 T 80°C Db
EC type examination certificate:
A31-P0-B0001-Rev3 eng
TPS 07 ATEX 61951 2X
09/04/2014
www.exepd.de
page 4 of 8
Operation Manual
Control Cabinet
Type A31-P*-*****
5.
Electrical Data
(Please refer to type label for details)
Maximum rated voltage:
Protective gas:
Maximum power loss:
1500 V AC/DC
air or inert gas (max. temperature +40°C)
1000 Watt (extension by request)
(For special applications, a safety device is installed to monitor the temperature which
interrupt the electrical power supply automatically, see the respective wiring diagram).
6.
Components / Cable Glands
With the Control Cabinet only separate tested or certified components like terminals,
switches and Control and signal units are used. Not used holes for cable glands or
operators have to be closed by certified plugs.
Assembly and safety instruction of the component manufacturer must be considered.
All equipment built into the surface of the Control Cabinet or installation equipment is
according applicable European standards or if there are no harmonized European
standards present the equipment meets relevant DIN VDE/VDE standards or other
equivalent national or European standards.
The minimum degree of protection of IP 55 of the Control cabinet has not been reduced
by the installation.
All built-in equipment installed in the Control cabinet is firmly mounted on the mounting
plate of the Control cabinet according the device-specific documentation.
Each Control unit includes an electrical circuit/wiring diagram of the installed equipment
in addition to the parts list.
Please note: The creator of the electrical circuit/wiring diagram is liable for the proper
functioning of the installed equipment and interconnection, this is not part of the extesting! Equipment who are changed for the proper ex p function (e.g. installation of
holes for safe purging, limiting performance measures) are indicated on the devices by a
label. An exchange of these devices, even if they are the same type, requires the consent
of the Exepd GmbH.
7.
Safety references
Devices in hazardous area must be installed, supervised, maintained and kept in good
conditions by the owner of the plant. Part of this is an inspection after the transport to
identify possible damages caused during the transport.
Only qualified workers are allowed to install and dismount as well as doing maintenance
work on the Control Cabinet. All universally valid rules and laws and other binding
directives for the safety of people and environment must be kept.
A31-P0-B0001-Rev3 eng
09/04/2014
www.exepd.de
page 5 of 8
Operation Manual
Control Cabinet
Type A31-P*-*****
After the final test of the Control cabinet additional warning labels could be fixed on, e.g:
When the key switch is used the Ex-protection is out of order
Warning: Risk of electrostatic discharge
Attention: Do not open when energized.
Control cabinet contains intrinsically safe circuits
Caution: Hot Surface to 85 ° C possible
Warning choking hazard: nitrogen or inert gas is used.
Etc.
To observance the type and warning label is necessary for safe operation.
The Control Cabinet will be delivered pre-set and recorded in accordance with the
requirements. A change of the setting is not allowed. If the Control Cabinet cannot
operate properly, only the Exepd or a notified body is authorized to make changes to the
settings.
8.
Installation
Mounting
The Control Cabinet must be protected against aggressive and unusual environmental
conditions which could cause damages on the equipment. This could be e.g. acids or high
and low temperatures.
For installation, please refer to IEC / EN 60079-14 and other valid standards and
directivities on the place of erection.
Information on the type label must be kept!
If cable glands marked with and “X” are in use, please refer to the operation manual of
the gland supplier.
Installation
The wire connection must be made in such a manner, that the insulation material and the
cores itself will not be damaged. Regarding the maximum possible cross connection and
electrical data, please refer to the information written on the type label.
Metal enclosures, installed in hazardous area, must be connected to the general earth
system via a cable with minimum 4 mm² cross section.
If intrinsically safe circuit installed in one box together with increased safe or energy
limited circuits, the installation must protect the Ex i circuit from an increase of capacity,
voltage and inductivity.
The air and creeping distance between Ex e and Ex i circuits must be kept by the internal
installation.
9.
Starting
Before the Control Cabinet is put into operation, the qualification for the use in the
predominant hazardous area must be proofed according to the type label and the zone
declaration.
It is not allowed to exceed the written data on the type label and the test protocol
(declaration of conformity).
By using the equipment in hazardous area with combustible dust, dust layers > 5 mm
must be removed. To protect the equipment from these circumstances also the
installation of protection hoods are possible.
The functionality of the Control Cabinet itself, as well as its combination with the plant or
machine must be tested before the first use.
Only use the Control Cabinet in clean and intact condition.
A31-P0-B0001-Rev3 eng
09/04/2014
www.exepd.de
page 6 of 8
Operation Manual
Control Cabinet
Type A31-P*-*****
10. Special conditions for safe use
The pressurized system shall only be operation with the setting values which are given in
test protocol (declaration of conformity) and on the type label.
The assembling of the components and viewing glasses in the door or wall system should
only take place by Exepd.
Control Cabinets with pneumatic cooling systems must be declare with temperature class
T3 or T4.
It is not allowed to install retrospectively additional equipment into a control cabinet.
11. Operation, Maintenance and Elimination of
Disturbances
Devices in hazardous area must be installed, supervised, maintained and kept in good
conditions by the owner of the plant. For information, refer to IEC / EN 60079-17. Only
skilled workers are allowed to do maintenance and the elimination of disturbance work.
Before doing this work, the safety requirements must be kept!
For elimination of disturbances, only original spare parts after consulting with Exepd are
allowed to use. Before using the boxes again, the safety requirements must be kept!
12. Accessories and spare parts
Please refer to www.exepd.de
13. Service address
Exepd GmbH
i_PARK TAUBERFRANKEN 23
97922 Lauda-Königshofen
Germany
A31-P0-B0001-Rev3 eng
Phone: ++49 (0) 9343 627055-0
Fax: ++49 (0) 9343 627055-99
Mail: info@exepd.de
www.exepd.de
09/04/2014
www.exepd.de
page 7 of 8
Operation Manual
Control Cabinet
Type A31-P*-*****
A31-P0-B0001-Rev3 eng
09/04/2014
www.exepd.de
page 8 of 8