J200UC3 E Engine JOHN DEERE ,... Alternator LEROY SOMER , LSA462M5

Transcription

J200UC3 E Engine JOHN DEERE ,... Alternator LEROY SOMER , LSA462M5
J200UC3
E
Engine JOHN DEERE , 6068HFS89, EPA/CARB Tier 3
Alternator LEROY SOMER , LSA462M5
200 KW JOHN DEERE GENERATOR
200 KW / 250 KVA DIESEL GENERATOR SET, FULLY PACKAGED:
 JOHN DEERE Heavy duty diesel engine, 4 stroke, 1800rpm, Turbo, EPA
 LEROY SOMER brushless alternator. IP23 protection, Insulation class H
 SCHNEIDER, Main line circuit breaker, wired, maximum output rated
 EPA Tier 3 compliant engine per U.S. Environmental Protection Agency
 Digital auto-start control panel. CE and UL compliant
 Incorporated metallic fuel tank for day use
 Auto Start control feature included for interoperation with ATS/AMF
 12V charging alternator and 12V DC electric starter motor
 12V charged DC starting battery with electrolyte and cables
 Dry type air filter, fuel filter and oil filter elements installed
 Mechanically welded chassis with vibration isolators
 Each unit prototype and individually factory load bank tested
 The generator accepts 100% rated load in one step as per NFPA110
and meets ISO8528-5 class G-3 for transient response
 Compliant with ISO3046, ISO8528, BS4999, BS5514, BS5000PT99,
AS1359, IEC34, UTE5100, VDE0530 and ISO9001:2000
AVAILABLE ACCESSORIES AND OPTIONS:
 Steel or Aluminum weather proof, sound attenuated enclosures
 UL142 listed, double wall fuel tanks from 50 to 10,000 Gal
 UL1008 listed, automatic transfer switches from 50 to 3000 Amp
 D.O.T. compliant heavy duty road trailers from 3000 to 30000 Lbs
 Automatic battery chargers, Engine preheaters, Remote annunciators
and many more
Voltage
480/277
460/265
440/254
240/139
230/133
220/127
208/120
Power ESP
kWe/kVA
200 / 250
200 / 250
200 / 250
190 / 238
185 / 231
200 / 250
190 / 238
Power PRP
kWe/kVA
182 / 227
182 / 227
182 / 227
173 / 216
168 / 210
182 / 227
173 / 216
Standby Amps
301
314
328
573
580
656
661
Dimensions - Open
Weight - Open
Length: 2370mm [93in]
Width: 1114mm [44in]
Height: 1503mm [59in]
1850kg [4079lbs] Net
2210kg [4872lbs] Gross
POWER DEFINITION
PRP : Prime Power is available for an unlimited number of annual operating hours in variable load applications, in accordance with ISO
8528-1.
ESP : The standby power rating is applicable for supplying emergency power in variable load applications in accordance with ISO 85281. Overload is not allowed.
TERM OF USE
Standard reference conditions ESP/PRP 25 C°/25 C° Air Intlet Temp, 1000 m/1000 m m A.S.L. 60 % relative humidity.
WEATHER / SOUND PROOF ENCLOSURES
Model
M226
dB(A)@3ft
80
dB(A)@23ft
70
Dimensions - Enclosed
Weight - Enclosed
Length: 3508mm [138in]
Width: 1200mm [47in]
Height: 1830mm [72in]
2460kg [5423lbs]
2820kg [6217lbs]
Tank
340 L
90 Gal
Parts Supply, Inc.
1348 NW 78th Avenue, Miami, FL 33126 USA
Tel: 786-863-8100/ Fax: 305-675-8482
sales@industrialdieselgenerators.com
ENGINE SPECIFICATIONS
Engine model
Cylinder arrangement
Displacement (C.I.)
Bore (mm) X Stroke (mm)
Compression ratio
DATA
GENERAL DATA
1800
7.62
Maximum stand-by power at rated RPM (kW)
Frequency regulation (%)
BMEP (bar)
235
+/-0.5
21.2
485
Exhaust gas flow (L/s)
Max. exhaust back pressure (mm CE)
715
1000
Fuel consumption 75% (L/h)
Fuel consumption 50% (L/h)
Maximum fuel pump flow (L/hr)
Oil capacity (L)
OIL
THERMAL BALANCE
AIR INTAKE
Min. oil pressure (bar)
Max. oil pressure (bar)
Oil consumption 100% load (L/h)
Carter oil capacity (L)
EMISSIONS
58.59 [15.5gal/hr]
51.88 [13.7gal/hr]
30 [7.9gal/hr]
25.29 [6.7gal/hr]
92.59 [24.5gal/hr]
33
1.05
3.39
0.13
32
Heat rejection to exhaust (kW)
Radiated heat to ambiant (kW)
Haet rejection to coolant (kW)
177.68
28.66
95+57
AIR INTAKE_entree_max%
Intake air flow (L/s)
375
291.67
Radiator & Engine capacity (L)
Max water temperature (°C)
Outlet water temperature (°C)
Fan power (kW)
COOLANT SYSTEM
ELECTRONIC
Exhaust gas temperature (°C)
Fuel consumption 110% load (gal/hr)
Fuel consumption 100% load (gal/hr)
FUEL SYSTEM
6 X, U.S. EPA / CARB TIER 3 FLEX
L
6.72
106 X 127
19 : 1
Speed (RPM)
Pistons speed (m/s)
Governor type
EXHAUST SYSTEM
JOHN DEERE 6068HFS89 , 4-temps, TURBO , AIR/AIR
Fan air flow w/o restriction (m3/s)
Available restriction on air flow (mm CE)
Type of coolant
Thermostat (°C)
25.8
110
93
5.9
5.5
20
GENCOOL
82-95
Emissions PM (g/kWh)
Emission CO (g/kW.h)
Emissions HCNOx (g/kWh)
0.11
0.5
3.2
Emission HC (g/kW.h)
0.1
Parts Supply, Inc.
1348 NW 78th Avenue, Miami, FL 33126 USA
Tel: 786-863-8100/ Fax: 305-675-8482
sales@industrialdieselgenerators.com
ALTERNATOR SPECIFICATIONS
Alternator brand
DATA
GENERAL DATA
OTHER
DATA
LEROY SOMER
Alternator
Number of phase
Power factor (Cos Phi)
Altitude (m)
Overspeed (rpm)
Number of pole
Excitation system
Insulation class / Temperature class
Regulation
Total harmonics TGH/THC
LSA462M5
Wave form : NEMA=TIF-TGH/THC
Wave form : CEI=FHT-TGH/THC
Number of bearing
Coupling
<50
<2
1
DIRECT
Voltage regulation 0 to 100%
Recovery time (Delta U = 20% transitoire) (ms)
+/-0.5%
500
3
0.8
<1000
2250
4
SHUNT
H/H
R250
<2.5
Continuous Nominal Rating 40°C (kVA)
Standby Rating 27°C (kVA)
Efficiencies 4/4 load (%)
Air flow (cfm)
Short circuit ratio (Kcc)
Direct axis synchro reactance unsaturated (Xd) (%)
Quadra axis synchro reactance unsaturated (Xq) (%)
Open circuit time constant (T'do) (ms)
Direct axis transient reactance saturated (X'd) (%)
Short circuit transient time constant (T'd) (ms)
Direct axis subtransient reactance saturated (X''d) (%)
Subtransient time constant (T"d) (ms)
Quadra axis subtransient reactance saturated (X"q) (%)
Zero sequence reactance unsaturated (Xo) (%)
Negative sequence reactance saturated (X2) (%)
Armature time constant (Ta) (ms)
No load excitation current (io) (ms)
Full load excitation current (ic) (A)
Full load excitation voltage (uc) (A)
Recovery time (Delta U = 20% transitoire) (ms)
Motor start (Delta U = 20% perm. or 50% trans.) (ms)
Transient dip (4/4 charge) - PF : 0,8 AR (%)
No load losses (kW)
250
273
92.7
0.51
0.43
314
188
2042
15
100
9
10
11.4
0.5
10.3
15
1
3.8
32
500
469
15.8
4.5
Heat rejection (kW)
15.68
Parts Supply, Inc.
1348 NW 78th Avenue, Miami, FL 33126 USA
Tel: 786-863-8100/ Fax: 305-675-8482
sales@industrialdieselgenerators.com
CONTROL PANELS
Standard
NEXYS
NEXYS
Specifications : Frequency meter, Ammeter, Voltmeter
Alarms and faults : Oil pressure, water temperature,
Overcrank, Overspeed ( >60 kVA), Min/max alternator, Low
fuel level, Emergency stop
Engine parameters : Hours counter, Engine speed, Battery
voltage, Fuel level, AIr preheating
Option
TELYS2
TELYS
Specifications : Frequency meter, Ammeter, Voltmeter
Alarms and faults : Oil pressure, water temperature, No startup, Overspeed, Min/max alternator, Min/max battery voltage,
Low fuel level, Emergency stop
Engine parameters : Hours counter, Oil pressure, Water
temperature, Engine speed, Battery voltage, Fuel level
Remote monitoring and control
ACCESSORIES AND OPTIONS
Option
50 to 3000 AMP Automatic Transfer Switches, UL1008 listed
With a Series 300 transfer switch, you get a product backed by
ASCO Power Technologies, the industry leader
●True double-throw operation: single solenoid design is inherently
interlocked & prevents contacts from stopping between sources
●Easy-to-read flush-mounted control and display panel provides
LED indicators for switch position and source availability
●Standard engine exerciser for weekly automatic testing with or
without load
●UL 1008 listed for Transfer Equipment and CSA C22.2 listed
●NFPA 110 for Emergency & Standby Power & the National
Electrical (NEC) Articles 700, 701 and 702
Option
50 to 10000 GAL Fuel Tanks, UL142 listed
●UL listed. Secondary containment tank meeting UL 142 tank
requirements
●NFPA compliant. Designed to comply with the installation
standards of NFPA 30 and NFPA 37
●Emergency pressure relief vents. Meets UL requirements; ensures
adequate venting of inner and outer tank under extreme pressure
and/or emergency conditions
●Electrical stub-up area with removable end channel
●Normal vent • Inner tank emergency vent sized to UL 142 specs
●Direct reading mechanical fuel gauge • Fuel in basin switch
●Satin black paint finish
Parts Supply, Inc.
1348 NW 78th Avenue, Miami, FL 33126 USA
Tel: 786-863-8100/ Fax: 305-675-8482
sales@industrialdieselgenerators.com
Weatherproof / Super Silent
Enclosure
M226
STANDARD FEATURES









They protect stationary and mobile generator against the bad weather, against the theft and enables the reduction of
the noise level.
Enclosures are of 12 gauge steel. Steel sheet are electro zinc coated before painting (inside and outside) with a
polyester powder rust inhibiting coat .
High corrosion resistance: stainless covered with zinc and made in dichromate, bolts and rivets, anodized aluminium
alloy hinges flexible seals between body sections.
Soundfoam between 20 and 50 mm (1 to 2 in) acoustical sound treatment
Lifting eye(s) on top of the enclosure fixed to the skid
Large doors allow easy access to the generator set for service and monitoring purposes
Window in “securit” glass mounted on enclosure door for control viewing .
A critical silencer is mounted inside the enclosure
Emergency stop button is accessible from outside enclosure.
Sound level
Dimensions
Weight
Tank
dB(A)@3ft
dB(A)@23ft
LWA
(in)
(lbs)
(Gal)
80
70
N/A
138 x 47 x 72
5423
90
Model
J200UC3
Parts Supply, Inc.
1348 NW 78th Avenue, Miami, FL 33126 USA
Tel: 786-863-8100/ Fax: 305-675-8482
sales@industrialdieselgenerators.com