Programmable Transmitter

Transcription

Programmable Transmitter
5131
Programmable
Transmitter
No. 5131V104-UK
From ser. no.: 040112001
DK
PR electronics A/S tilbyder et bredt program af analoge og digitale
signalbehandlingsmoduler til industriel automation. Programmet
består af Isolatorer, Displays, Ex-barrierer, Temperaturtransmittere,
Universaltransmittere mfl. Vi har modulerne, du kan stole på i selv
barske miljøer med elektrisk støj, vibrationer og temperaturudsving,
og alle produkter opfylder de strengeste internationale standarder.
Vores motto »Signals the Best« er indbegrebet af denne filosofi – og
din garanti for kvalitet.
UK
PR electronics A/S offers a wide range of analog and digital
signal conditioning devices for industrial automation. The product
range includes Isolators, Displays, Ex Interfaces, Temperature
Transmitters, and Universal Devices. You can trust our products in
the most extreme environments with electrical noise, vibrations and
temperature fluctuations, and all products comply with the most
exacting international standards. »Signals the Best« is the epitome
of our philosophy – and your guarantee for quality.
FR
PR electronics A/S offre une large gamme de produits pour le
traite­
ment des signaux analogiques et numériques dans tous
les domaines industriels. La gamme de produits s’étend des
transmetteurs de température aux afficheurs, des isolateurs aux
interfaces SI, jusqu’aux modules universels. Vous pouvez compter
sur nos produits même dans les conditions d’utilisation sévères,
p.ex. bruit électrique, vibrations et fluctuations de température.
Tous nos produits sont conformes aux normes internationales les
plus strictes. Notre devise »SIGNALS the BEST« c’est notre ligne
de conduite - et pour vous l’assurance de la meilleure qualité.
DE
PR electronics A/S verfügt über ein breites Produktprogramm
an analogen und digitalen Signalverarbeitungsgeräte für die in­
dustrielle Automatisierung. Dieses Programm umfasst Displays,
Temperaturtransmitter, Ex- und galvanische Signaltrenner, und
Universalgeräte. Sie können unsere Geräte auch unter extremen
Einsatzbedingungen wie elektrisches Rauschen, Erschütterungen
und Temperaturschwingungen vertrauen, und alle Produkte von
PR electronics werden in Überein­stimmung mit den strengsten
internationalen Normen produziert. »Signals the Best« ist Ihre
Garantie für Qualität!
1431
2-WIRE
PROGRAMMABLE TRANSMITTER
PRetrans type 5131
Contents
Warning........................................................................................................
Symbol identification.............................................................................
Safety instructions..................................................................................
How to demont system 5000............................................................
Application..................................................................................................
Technical characteristics.......................................................................
Input types.................................................................................................
Output..........................................................................................................
Sensor error detection...........................................................................
Configuration.............................................................................................
Electrical specifications........................................................................
Order.............................................................................................................
5131 connection to Loop Link...........................................................
Selection of input type: (5131A)......................................................
Blockdiagram.............................................................................................
2
3
3
5
6
6
6
7
7
7
8
12
13
13
14
5 131V1 0 4 - U K 1
Warning
GENERAL
This device is designed for connection to hazardous electric
voltages.
Ignoring this warning can result in severe personal injury or
mechanical damage.
To avoid the risk of electric shock and fire, the safety instructions
of this manual must be observed and the guidelines followed. The
specifications must not be exceeded, and the device must only be
applied as described in the following.
Prior to the commissioning of the device, this manual must be
examined carefully.
Only qualified personnel (technicians) should install this device.
If the equipment is used in a manner not specified by the
manufacturer, the protection provided by the equipment may be
impaired.
WARNING
HAZARDOUS
VOLTAGE
Until the device is fixed, do not connect hazardous voltages to
the device.
The following operations should only be carried out on a
disconnected device and under ESD safe conditions:
Dismantlement of the device for setting of dipswitches
and jumpers.
General mounting, connection and disconnection of wires.
Troubleshooting the device.
Repair of the device and replacement of circuit breakers must
be done by PR electronics A/S only.
WARNING
INSTALLATION
2
SYSTEM 5000 must be mounted on DIN rail according to DIN
46277.
The communication connector of SYSTEM 5000 is connected to
the input terminals on which dangerous voltages can occur, and it
must only be connected to the programming unit Loop Link by way
of the enclosed cable.
5131V104- U K
Symbol identification
Triangle with an exclamation mark: Warning / demand.
Potentially lethal situations.
The CE mark proves the compliance of the device with the essential
requirements of the directives.
The double insulation symbol shows that the device is protected by
double or reinforced insulation.
Ex devices have been approved for use in connection with
installations in explosive areas.
Safety instructions
Definitions
Hazardous voltages have been defined as the ranges: 75 to 1500 Volt DC, and
50 to 1000 Volt AC.
Technicians are qualified persons educated or trained to mount, operate, and also
troubleshoot technically correct and in accordance with safety regulations.
Operators, being familiar with the contents of this manual, adjust and operate the
knobs or potentiometers during normal operation.
Receipt and unpacking
Unpack the device without damaging it. The packing should always follow the
device until this has been permanently mounted. Check at the receipt of the device
whether the type corresponds to the one ordered.
Environment
Avoid direct sunlight, dust, high temperatures, mechanical vibrations and shock, as
well as rain and heavy moisture. If necessary, heating in excess of the stated limits
for ambient temperatures should be avoided by way of ventilation.
All devices fall under Installation Category II, Pollution Degree 1, and Insulation
Class II.
Mounting
Only technicians who are familiar with the technical terms, warnings, and
instructions in the manual and who are able to follow these should connect the
device.
5 131V1 0 4 - U K 3
Should there be any doubt as to the correct handling of the device, please contact
your local distributor or, alternatively,
PR electronics A/S
www.prelectronics.com
Mounting and connection of the device should comply with national legislation for
mounting of electric materials, i.e. wire cross section, protective fuse, and location.
Descriptions of input / output and supply connections are shown in the block
diagram and side label.
The following apply to fixed hazardous voltages-connected devices:
The max. size of the protective fuse is 10 A and, together with a power
switch, it should be easily accessible and close to the device. The power
switch should be marked with a label telling it will switch off the voltage
to the device.
Production year can be taken from the first 2 digits of the serial number.
Calibration and Adjustment
During calibration and adjustment, the measuring and connection of external
voltages must be carried out according to the specifications of this manual. The
technician must use tools and instruments that are safe to use.
Normal operation
Operators are only allowed to adjust and operate devices that are safely fixed in
panels, etc., thus avoiding the danger of personal injury and damage. This means
there is no electrical shock hazard, and the device is easily accessible.
Cleaning
When disconnected, the device may be cleaned with a cloth moistened with
distilled water.
Liability
To the extent the instructions in this manual are not strictly observed, the customer
cannot advance a demand against PR electronics A/S that would otherwise exist
according to the concluded sales agreement.
4
5131V104- U K
How to demont system 5000
First, remember to demount the connectors with hazardous voltages. By lifting the
bottom lock, the device is detached from the DIN rail as shown in picture 1.
Then, by lifting the upper lock and pulling the front plate simultaneously the PCB
is removed as shown in picture 2.
Switches and jumpers can now be adjusted. By opening the front, the programming
connector is accessible as shown in picture 3.
Picture 1: Separation from DIN rail.
Picture 3: Access to programming connector.
Picture 2: Removal of PCB.
5 131V1 0 4 - U K 5
2-WIRE PROGRAMMABLE
TRANSMITTER 5131
•
•
•
•
•
•
Input for RTD, TC, mV, linear resistance, mA, and V
3.75 kVAC galvanic isolation
4...20 mA loop output
1- and 2-channel versions
ATEX Ex version
DIN rail mounting
Application
Electronic temperature measurement with resistance sensor or thermocouple
sensor. • Ex barrier for temperature sensors, potentiometers and current /
voltage signals. • Conversion of current signals from supplied transmitters to
2-wire 4...20 mA signals. • Amplification of mV signals. • Conversion of linear
resistance variation. • Galvanic isolation of analogue signals. • Measurement of
floating signals. • Linearisation of non-linear Ohm, mV, mA, or voltage signals.
• Separation of circuits in PELV/SELV installations.
Technical characteristics
The unit is based on a microprocessor core with an efficient program operation.
The basic calibration data and present set-up are stored in an EEPROM thereby
avoiding the loss or change of data at power off. The 2-channel version has a full
galvanic isolation between the channels. By way of a jumper on the PCB the input
in the standard version can be programmed either for a temperature or a current /
voltage input. This means that one channel can work as for instance a temperature
transmitter and the other can work as an isolation amplifier. Measurement range,
signal parameters, and output span are configured to the present task by way of a
PC and PR electronics A/S’ communications interface Loop Link.
Input types
Temperature input - jumper in position 1:
Thermocouple input (TC) for standard thermocouples type B, E, J, K, L, N, R, S, T,
U, W3, W5, LR according to the norms IEC 584, DIN 43710, ASTM E988-90 and
GOST 3044-84.
6
5131V104- U K
The CJC can be selected in 3 different ways: internally in the terminal, externally
by way of a Pt100 / Ni100 sensor, or externally with a constant temperature. If
internal compensation is selected, a terminal with a built-in temperature sensor
must be ordered separately (PR type no. 5910 and 5913). Sensor error detection
is available.
RTD input for Pt100...Pt1000 according to the norm IEC 751 and Ni100...Ni1000
according to the norm DIN 43760. Automatic cable compensation at a 3- or
4-wire connection. At a 2-wire connection the cable resistance can be entered
or measured by the configuration program and sent to the device which then
compensates by the entered cable resistance. Sensor error detection is available.
Resistance input for resistance measurement with cable compensation as
described under the RTD input. Sensor error detection is available.
The mV input is programmable in the range -150...+150 mV.
Current / voltage input - jumper in position 2:
The current input is programmable in the range 0...100 mA, for instance 4...20 mA.
The voltage input is programmable in the range 0...250 VDC.
Output
Standard loop 4...20 mA current output. The output signal is proportional and linear
to the value of the input signal. Special set-ups can be selected in the configuration
program, for instance a customised linearisation, a reversed output, a limiter
according to the selected output span, and selection of an output value in case of
a sensor error. Maximum load on the current output is 1375 Ω.
Sensor error detection
The output can be set up at a RTD, thermocouple and linear resistance input to
go to max., to min., entered value, NAMUR NE43 Upscale or Downscale at sensor
error detection.
Configuration
The transmitter is configured to the present task by way of a and PR electronics
A/S’ communications interface Loop Link. The transmitter can be configured with
or without a connected supply voltage as the communications interface supplies
the necessary voltage to the set-up. The communications interface is galvanically
isolated to protect the PC port. Communication is 2-way to allow the retrieval of
the transmitter set-up into the PC and to allow the transmission of the PC set-up
to the transmitter. For users who do not wish to do the set-up themselves, the
5131 can be delivered con­fi­g­ured according to customer specifications: input type,
measurement range, sensor error detection, and output signal.
5 131V1 0 4 - U K 7
Electrical specifications
Specifications range:
-20°C to +60°C
Common specifications:
Supply voltage........................................................... 7.5...35 VDC
Fuse................................................................................ 50 mA SB / 250 VAC
Consumption during programming.................... 3...8 mA
Isolation voltage, test / operation..................... 3.75 kVAC / 250 VAC
Communications interface.................................... Loop Link
Signal / noise ratio................................................... Min. 60 dB (0...100 kHz)
Signal dynamics, input............................................ 22 bit
Signal dynamics, output........................................ 16 bit
Updating time:
Temperature input.............................................. 115 ms
mA / V / mV input............................................... 75 ms
Response time (0...90%, 100...10%), programmable:
Temperature input.............................................. 400 ms...60 s
mA / V / mV input............................................... 250 ms...60 s
Calibration temperature......................................... 20...28°C
Accuracy, the greater of the general and basic values:
General values
8
Input type
Absolute
accuracy
Temperature
coefficient
All
≤ ±0.05% of span
≤ ±0.01% of span / °C
5131V104- U K
Basic values
Input type
Basic
accuracy
Temperature
coefficient
mA
≤ ±4 µA
≤ ±0.4 µA / °C
Volt
≤ ±10 µV
≤ ±1 µV / °C
RTD
≤ ±0.2°C
≤ ±0.01°C / °C
Lin. resistance
≤ ±0.1 Ω
≤ ±10 mΩ / °C
TC type:
E, J, K, L, N, T, U
≤ ±1°C
≤ ±0.05°C / °C
TC type: B, R, S,
W3, W5, LR
≤ ±2°C
≤ ±0.2°C / °C
EMC immunity influence................................................... < ±0.5% of span
Extended EMC immunity:
NAMUR NE 21, A criterion, burst.................................. < ±1% of span
Effect of supply voltage change........................
Wire square (max.)....................................................
Screw terminal torque............................................
Relative humidity.....................................................
Dimensions (HxWxD)...............................................
DIN rail type................................................................
Protection degree.....................................................
Weight...........................................................................
< 0.005% of span / VDC
1 x 2.5 mm2 stranded wire
0.5 Nm
< 95% RH (non-cond.)
109 x 23.5 x 130 mm
DIN 46277
IP20
195 g
5 131V1 0 4 - U K 9
Electrical specifications, temperature input:
TC input:
Type
Min.
temperature
Max.
temperature
Min.
span
Standard
B
E
J
K
L
N
R
S
T
U
W3
W5
LR
+400°C
-100°C
-100°C
-180°C
-100°C
-180°C
-50°C
-50°C
-200°C
-200°C
0°C
0°C
-200°C
+1820°C
+1000°C
+1200°C
+1372°C
+900°C
+1300°C
+1760°C
+1760°C
+400°C
+600°C
+2300°C
+2300°C
+800°C
200°C
50°C
50°C
50°C
50°C
100°C
200°C
200°C
50°C
75°C
200°C
200°C
50°C
IEC584
IEC584
IEC584
IEC584
DIN 43710
IEC584
IEC584
IEC584
IEC584
DIN 43710
ASTM E988-90
ASTM E988-90
GOST 3044-84
Max. offset..................................................................
Sensor error current.................................................
CJC...................................................................................
Sensor error detection............................................
50% of selec. max. value
Nom. 30 µA
≤ ±1°C
Yes
mV input:
Measurement range.................................................
Min. measurement range.......................................
Max. offset..................................................................
Input resistance........................................................
-150...+150 mV
5 mV
50% of selec. max. value
Nom. 10 MΩ
RTD and linear resistance input:
Type
Min. value
Max. value
Min. span
Standard
Pt100
Ni100
Lin. R
-200°C
-60°C
0Ω
+850°C
+250°C
5000 Ω
25°C
25°C
30 Ω
IEC 751
DIN 43760
-------
Max. offset..................................................................
Max. cable resistance per wire............................
Sensor current............................................................
Effect of sensor cable resistance
(3- / 4-wire).................................................................
Sensor error detection............................................
10
50% of selec. max. value
10 Ω
Nom. 0.2 mA
< 0.002 Ω / Ω
Yes
5131V104- U K
Electrical specifications, mA / V / mV input:
Current input:
Measurement range.................................................
Min. measurement range (span).........................
Max. offset..................................................................
Input resistance:
Supplied unit..............................................................
Non-supplied unit.....................................................
0...100 mA
4 mA
50% of selec. max. value
Nom. 10 Ω + PTC 10 Ω
RSHUNT = ∞, VDROP < 6 V
Voltage input:
Measurement range.................................................
Min. measurement range (span).........................
Max. offset..................................................................
Input resistance ≤ 2,5 VDC.................................
> 2,5 VDC.................................
0...250 VDC
5 mVDC
50% of selec. max. value
Nom. 10 MΩ
Nom. 5 MΩ
Electrical specifications - OUTPUT:
Signal range (span)..................................................
Min. signal range (span).........................................
Max. offset..................................................................
Load resistance.........................................................
Load stability..............................................................
Current limit................................................................
4...20 mA
10 mA
50% of selec. max. value
≤ (Vsupply-7.5) / 0.023 A) [Ω]
≤ 0.01% of span / 100 Ω
≤ 28 mA
Sensor error detection:
Programmable............................................................
NAMUR NE43 Upscale............................................
NAMUR NE43 Downscale......................................
No function.................................................................
3.5...23 mA
23 mA
3.5 mA
Not defined
EEx / I.S. approval (5131B):
DEMKO 99ATEX124572........................................
II (1) GD
[EEx ia] IIC
Applicable for............................................................. Zone 0, 1, 2, 20, 21 or 22
5 131V1 0 4 - U K 11
Ex / I.S. data:
Um...................................................................................
Uo....................................................................................
Io......................................................................................
Po.....................................................................................
Lo.....................................................................................
Co.....................................................................................
: 250 V
: 8.0 VDC
: 10 mADC
: 20 mW
: 200 mH
: 1.0 μF
GOST R approval:
VNIIM & VNIIFTRI, Cert. no................................... See www.prelectronics.com
Observed authority requirements:
EMC 2004/108/EC...................................................
LVD 2006/95/EC.......................................................
PELV/SELV...................................................................
ATEX 94/9/EC.............................................................
Standard:
EN 61326-1
EN 61010-1
IEC 364-4-41 and EN 60742
EN 50014, EN 50020 and
EN 50281-1-1
Of span = Of the presently selected range
Order
Type
5131
Version
Input
Channels
Standard
:A
RTD / TC / R / mA / V / mV
ATEX Ex
: B
RTD / TC / mV / R
: 1
mA / V / mV
: 2
Channel 1, RTD / TC / mV / R : 3
Channel 2, mA / V / mV
: -
Single
Double
:A
:B
Note! For TC inputs with internal CJC, remember to order CJC connectors type 5910 /
5910Ex (ch. 1) and 5913 / 5913Ex (ch. 2).
12
5131V104- U K
5131 connection to Loop Link
13
11
Receiving
Disconnect when "on line"
loop communication is used equipment
+Vsupp
Loop communication
Black
Or
Red
Yellow
Front communication can be used
with or without 5131 connected
to the receiving equipment
CH 2
4...20 mA
Input
Green
CH 1
5131
Language O ption
O utput C om m unication
File Product Input
PRetop 5331
D ate:
S erial no:
Tag no:
COM
08:30:00
1994-8-10
943201594
PRelectronics
Analog input
Loop Link
Analog output
4 - 20mA
U pscale
O utput type:
Pt100 D IN/IE C
Input type:
S ensor error:
0.00 - 50.00 C
Input range:
3-wire
C onnection:
p: -----C old junction com
1.00 sec
Response tim e:
Selection of input type: (5131A)
JP 1
JP 2
Temperature channel 1
Temperature channel 2
1
-
1
Current / voltage channel 1
Current / voltage channel 2
2
-
2
Input
5 131V1 0 4 - U K 13
RTD and lin. R
Conn. wire
3
4
2
-
+
5131V104- U K
-
mA
V <=
2.5
Input gnd.
+
V
-
+
!! If channel 1, use
terminal no. 44...41
V>
2.5
V
-
+
Input +
Input +,
> 2.5 V
*
TC
Channel 2 shown as a
current / voltage input:
!! If channel 2, use
terminal no. 54...51
-
mV
+
mV
CH 2
51
52
53
54
41
42
43
44
CH 1
Ex barrier, only 5131B
14
Ex barrier, only 5131B
Channel 1 shown as a
temperature input:
1
2
1
2
V+
JP 2
Analogue
switch
0,2 m A
PTC
A /D
EE PRO M
C PU
Front comm.
V+
EEPRO M
C PU
5131 Channel 2
A /D
Front comm.
5131 Channel 1
PGA
50 k
10 Ω
M UX
Analogue
switch
PGA
50 k
10 Ω
M UX
0,2 m A
PTC
5M
V+
JP 1
5M
V+
D /A
C om m .
4 mA
D /A
C om m .
4 mA
* Accessories: 5910 CJC connector CH 1, 5913 CJC connector CH 2.
21
0...16 m A
4...20 m A
A
4...20 m A
Supply -
A
Supply +
A
Supply -
22 Test
23
11
0...16 m A
A
Supply +
12 Test
13
Blockdiagram
Displays
Programmable displays with a wide selection of
inputs and outputs for display of temperature, volume and weight,
etc. Feature linearization, scaling, and difference measurement
functions for programming via PReset software.
Interfaces for analog and digital signals as well
Ex interfaces
as HART® signals between sensors / I/P converters / frequency
signals and control systems in Ex zone 0, 1 & 2 and for some
devices in zone 20, 21 & 22.
Galvanic isolators for analog and digital signals
Isolation
as well as HART® signals. A wide product range with both looppowered and universal isolators featuring linearization, inversion,
and scaling of output signals.
Temperature
A wide selection of transmitters for DIN form
B mounting and DIN rail devices with analog and digital bus
communication ranging from application-specific to universal
transmitters.
Universal
PC or front programmable devices with
universal options for input, output and supply. This range offers
a number of advanced features such as process calibration,
linearization and auto-diagnosis.
www.prelectronics.fr
sales-fr@prelectronics.com
www.prelectronics.de
sales-de@prelectronics.com
www.prelectronics.es
sales-es@prelectronics.com
www.prelectronics.it
sales-it@prelectronics.com
www.prelectronics.se
sales-se@prelectronics.com
www.prelectronics.co.uk
sales-uk@prelectronics.com
www.prelectronics.com
sales-us@prelectronics.com
www.prelectronics.cn
sales-cn@prelectronics.com
Head office
Denmarkwww.prelectronics.com
PR electronics A/S
Lerbakken 10
DK-8410 Rønde
sales-dk@prelectronics.com
tel. +45 86 37 26 77
fax +45 86 37 30 85