BG2 Range - MANUAL CALL POINT

Transcription

BG2 Range - MANUAL CALL POINT
BG2 Range - MANUAL CALL POINT
Ex de, Intrinsically Safe (Ex ia), Weatherproof
Features
4 Zone 0, Zone 1 and Zone 2 use.
4 Ex de, Ex ia or weatherproof.
4 ATEX approved– Ex II 1GD (Ex ia).
– Ex II 2G (Ex de).
4 BASEEFA certified.
4 IP66 and IP67.
4 Certified temperature: –40ºC to +70ºC*.
4 Corrosion resistant red painted GRP.
4 Retained stainless steel cover screws.
4 Optional lift flap.
4 Key operated test facility.
4 Lightweight and robust.
4 Breakglass hammer available.
(Contact sales office for details).
*Depending on version.
Introduction
This manual fire alarm call point has been designed for use in flammable
atmospheres and harsh environmental conditions. The GRP enclosure is
suitable for use offshore or onshore where lightweight combined with a
high level of corrosion resistance is required.
Head Office.
Unit B, Sutton Parkway, Oddicroft Lane, Sutton in Ashfield
NG17 5FB, UK.
Head Office (USA)
3413 North Sam Houston Parkway West,
Suite 212, Houston, TX 77086, USA
Sales Enq. UK: +44 (0)1623 444 445 Sales Enq. USA: +1 (713) 937- 9772 E-Mail: MEDCSales@Eaton.com Web: www.medc.com
22
Certification and Specification
ATEX Ex de:
ATEX Ex ia:
Cert. no. BAS02ATEX2105X. ATEX Approved Ex II 2G.
Certified to: EN60079-0, EN60079-1, EN60079-7.
Ex de IIC T6 Gb switch only.
Ex de mb IIC T4 Gb with resistors & diodes.
Cert no. Baseefa 03ATEX0084X. ATEX Approved Ex II 1GD.
Certified to: EN60079-0, EN60079-11.
Ex ia IIC T4 Ga, Ex ia IIIC T135ºC Da.
Material:
Anti static UV resistant Glass Reinforced Polyester.
Finish:
Painted Red.
Certified Temp:
-40ºC to +70ºC.
Voltage:
Up to 254V a.c. (Ex ia - Up to 28V d.c.).
Weight:
1.2Kg.
Ingress Protection:
IP66 & IP67.
Cable Entries:
2 x M20 bottom.
Terminals:
6 x 2.5mm².
Resistor Values:
Ex de - 100Ω minimum, 39KΩ maximum.
Ex ia - 470Ω minimum.
Switch ratings:
d.c. 0-30V 5A (resistive) or 3A (inductive).
30V-50V 1A resistive or inductive.
a.c. 0-254V 5A resistive or inductive.
1. Switch Only
2. End of Line
Resistor / Diode
R1/D1
1 2 3 4 5 6
1 2 3 4 5 6
ALL CIRCUITS SHOWN WITH GLASS INTACT
ALL DIMENSIONS IN MILLIMETERS
3. In Line
Resistor / Diode
R2/D2
4. In Line & End of Line
Resistor / Diode
R1/D1
R2/D2
1 2 3 4 5 6
1 2 3 4 5 6
Ordering Requirements
The MEDC BG Range of Manual Alarm
Call Points caters for numerous options such as variety of colours, LED
indication, earth continuity, double
switch, etc. See separate catalogue
sheet for details.
The following code is designed to help in selection of the correct unit. Build up the reference number
by inserting the code for each component into the appropriate box.
Model
Options
Flap
Finish
ModelCode
BG2W – a.c. or d.c. BG2WNN
BG2I – Up to 28V (I.S.) BG2INN
BG2E – d.c. BG2EDC
BG2E – a.c. BG2EAC
OptionsCode
Switch only 1
End of line resistor 2*
In line resistor 3*
In line and end of line resistor 4*
Diode (specify location & value)5
FlapCode
Fitted F*
Not Fitted N
FinishCode
Red Painted R
*Polycarbonate lift flap.
*Specify resistor values.
All specifications, dimensions, weights and tolerances are nominal (typical) and MEDC reserve the right to vary all data without prior notice.
No liability is accepted for any consequence of use.
6DS029/Q