“Regufloor HC” Control unit for surface heating and
Transcription
“Regufloor HC” Control unit for surface heating and
“Regufloor HC” Control unit for surface heating and cooling systems Technical information Das Qualitätsmanagementsystem von Oventrop ist gemäß DIN-EN-ISO 9001 zertifiziert. Tender specification: Control unit DN 25 for flow temperature control of surface heating systems with the option of surface cooling in combination with Oventrop stainless steel distributors/collectors. Consisting of: - Connection fittings - Three-way diverting valve - Check valve, angle pattern adapter - Electronically controlled pump Pre-assembled and leak tested. 6 bar 0.75 bar 90 °C 50 °C 4 up to 15 kW or up to 200 m² heating surface with a heat demand of 75 kW/m² Fluid: Non-aggressive fluids (e.g. water and suitable water and glycol mixtures according to VDI 2035). Not suitable for steam, oily and aggressive fluids. Pump Bracket Connecting cable Item no.: 1152100 1152000 Dimensions/Connection sizes: The installation depth of the control unit inside the cabinet amounts to approx. 145 mm from the leading edge of the pump head to the rear wall of the cabinet (fixing rails have been taken into account). This installation depth has to be taken into account when installing the cabinet (pull out frame accordingly). Installation advice: The correct direction of flow must be observed when connecting the control unit to the stainless steel distributors/collectors “Multidis SF” (see illustr.). The supply at the control station is always located at the top and the return at the bottom. The control station is supplied for left hand side connection. For right hand side connection, turn the pump accordingly. Angle pattern adapter Three-way valve Summary G1 G1 100 G1 316 200 Description and function: The control unit “Regufloor HC“ is used for flow temperature control of surface heating and cooling systems. The three-way valve has one inlet port and two outlet ports. Depending on the position of the valve disc, the direction of flow is diverted from one outlet port to the other or, in case of intermediate positions, it is divided between the outlet ports. The respective position of the valve disc at the three-way valve is initiated with the help of the electromotive actuator 24 V (0 – 10 v) which is part of the optional flow temperature control set (item no. 1152020) for weather guided heating and cooling. The actuator receives its signals from an electric controller heating/cooling. To avoid a vertical downward installation, the actuator is mounted onto the three-way valve with an angle pattern adapter. The automatic pump control steadily adjusts the pump output to the current hot water demand. G1 Models: (with high-efficiency pump Wilo-Yonos PARA) (with Wilo pump E15/1-5) “Regufloor HC” approx. 130 Technical data: Max. operating pressure ps: Max. differential pressure: Max. operating temperature ts: Primary side: Secondary side: kvs-value: Performance range: 134 ~ 145 Dimensions Supply Flow distributor Return Return collector Direction of flow 2014 Oventrop 1 “Regufloor HC” Control unit for surface heating and cooling systems Accessories (optional): Flow temperature control set item no. 1152020 The electromotive actuator of the flow temperature control set receives its signals from the electric controller heating/cooling. The flow temperature control set for outside temperature guided heating and cooling via the corresponding surface heating/cooling systems allows automatic switching from heating to cooling according to requirements. Condensation is avoided beforehand by an active dew point calculation which guarantees suitable flow temperatures. 1 5 2 6 3 7 4 8 Flow temperature control set (optional) 1 2 3 4 5 6 7 8 Climate controller heating/cooling Outdoor sensor Flow temperature sensor Room humidity measuring transducer Memory stick Electrothermal actuator Electromotive actuator Electric pipe contact safety switch Outer wall Rooms 1 Controller heating/cooling 2 Outdoor sensor 3 “Sensor GA FD” Dew point control 24 V 4 Flow temperature sensor 5 Room humidity measuring transducer 6 Room thermostat 7 Connection system for room thermostats and actuators 8 “Regufloor HC” Control unit 9 Electromotive actuator 10 Electrothermal actuator 11 Three-way mixing valve “Tri-M” System illustration “Regufloor HC” and flow temperature control set Gedruckt auf chlorfrei OVENTROP GmbH & Co. KG Paul-Oventrop-Straße 1 D-59939 Olsberg Germany Telephone +49(0) 2962 82-0 Fax +49(0) 2962 82-450 E-Mail mail@oventrop.de Internet www.oventrop.de gebleichtem Papier. For an overview of our global presence visit www.oventrop.de Subject to technical modifications. Product range 2 ti 174-0/10/MW Edition 2014 2 2014 Oventrop