Using Lithium-Ion and Advanced Batteries with
the Conext™ Series of Inverter/Chargers and
MPPT Solar Charge Controllers - Introduction
Li-ion and other advanced chemistry batteries are now selected more often for use in battery
hybrid systems because they provide significant performance improvements over traditional
lead-acid batteries.
Some of these performance improvements include one or more of the following:
1. Higher density - three times the watt-hours per kilogram and half the volume.
2. Higher charge cycles - about six times that of traditional lead-acid batteries.
3. Low self-discharge rate such as 2-3% per month.
4. Low internal resistance - one-fourth of lead-acid resulting in lower heat loss and
better efficiency as well as voltage regulation.
5. No degradation of overall battery life when operated at partial state-of charge
(SOC) for an extended period.
6. Cell balancing circuits which mitigates cell divergence, thereby maintaining
capacity over lifetime.
7. Safety protections which are suitable for unattended applications.
8. Ability to operate under extended temperature ranges
Li-ion and advanced chemistry batteries pose few challenges when compared to
conventional lead-acid, such as:
1. Batteries with a Battery Management System (BMS) can trigger protection and
disconnect the battery from inverter/chargers thus removing power. This means that
the batteries are no longer dependent on the inverter/charger for their protection.
2. The life cycle of batteries is highly affected by charging profile over age, temperature,
and depth of discharge, and sometimes they require a frequent change of
configuration settings rather than a one-time configuration set-up.
solar.schneider-electric.com
3. Some batteries have a very wide voltage operating range (such as sodium-ion) or very
narrow voltage operating range (such as iFePO4) from 100% to 20% SOC.
4. Different types of Li-ion and advanced batteries, and their BMS in the market today,
pose a dilemma for the system designer. The main challenge is determining the
method of integration between the battery pack and power conversion equipment to
achieve optimum performance and battery life span while still ensuring the system is
safe.
We want to ensure you are completely satisfied with your system installation. Before
purchasing Lithium-Ion batteries we suggest you contact us for additional information and ask
for the detailed application guide for Lithium-Ion and Advanced Batteries (976-0319-01-01
Revision A).
Conext Family of Battery Based Power Conversion Products
solar.schneider-electric.com

Similar documents

Latest Report - Lead-acid Battery Market Size, Growth Trends, 2019: Radiant Insights, Inc

Latest Report - Lead-acid Battery Market Size, Growth Trends, 2019: Radiant Insights, Inc Lead-acid batteries are rechargeable devices that are comprised of lead electrodes submerged in diluted sulfuric acid. The global market for lead-acid batteries is estimated to show steady growth during the forecast period and factors like the rising use of lead-acid batteries by various end-user segments and other motive applications such as forklifts, railroad, and mining vehicles are expected to foster market growth during the forecast period. These factors promote the prospects for growth in this market and results in its steady CAGR of almost 7.5% by 2019. Browse Ongoing Reports http://www.radiantinsights.com/research/global-lead-acid-battery-market-2015-2019

More information