AMPCONTROL BRAND GUIDELINES

Transcription

AMPCONTROL BRAND GUIDELINES
ELV – our next generation
earth leakage relay
AMPCONTROL
BRAND GUIDELINES
Ampcontrol’s ELV provides wide bandwidth earth leakage
protection as per AS/NZS2081:2011. It is designed for use on
earth fault limited systems, particularly coal and metal mining
applications that may include Variable Speed Drives.
The ELV relay provides a definite time operating characteristic
with adjustable trip sensitivity and time delay. It latches when
tripped and provides normally open and change-over relay
contacts. The relay supports an external reset switch, and a
4-20mA interface allowing external monitoring. For security
the ELV has provision to prevent unauthorised adjustment of
the trip settings.
DIN rail or panel mounted through a 69 x 39mm cut out.
When panel mounted, the front of the ELV relay is designed to
provide IP56 ingress protection.
Features
• AS/NZS 2081:2011 compliant
• Wide operating bandwidth (5Hz to 10kHz)
• Increased current range (down to 30mA)
• Fail safe operation
• Continual monitoring of the toroid
• Adjustable trip level and time delay settings
The user has the ability to switch the relay between wideband
(up to 10kHz), narrowband (power frequency) and weighted
frequency mode (up to 10kHz, high frequency corrected).
The relay is housed in a stainless steel case and can be either
For more information on Ampcontrol’s ELV
visit ampcontrolgroup.com/ELV
FEATURES
The key differences between Ampcontrol’s VSDguard, ELD and ELV relays.
VSDguard
ELV
ELD
P
5Hz –10kHz (CT)
0Hz – 10kHz (Shunt)
P
5Hz–10kHz
x
10Hz–150Hz
COMPLIANT TO AS/NZS 2081:2011
P
P
x
EVENT LOGGING
P
x
x
CIRCUIT TRIP/TIME PROTECTION VALIDATION
P
x
x
P
x
x
P
x
x
P
x
x
P
x
x
P
50mA-5A
P
30mA-2.5A
P
100mA-2.5A
P
<50ms-500ms
P
<50ms-500ms
P
<50ms-500ms
EXTERNAL COMMUNICATIONS
P
Ethernet
x
x
ANALOGUE OUTPUT
P
Ethernet
P
4-20mA
P
4-20mA
POWER SUPPLY
24VDC
24-110VAC, 50Hz
24-150VDC
32-110VAC, 50Hz
20-185VDC
IP55
IP56
IP56
135x135
69x39
69x39
Panel
Panel
DIN Rail
Panel
DIN Rail
· All low, medium and high
voltage VSD systems
· Protection system verification
· Diagnostics and fault analysis
All low, medium and high
voltage VSD systems
Simple outlet Earth Leakage
Protection
Password Protected
Non-Tamper Front Panel
Non-Tamper Front Panel
25mm, 60mm, 112mm,
203mm, 300mm
25mm, 60mm, 112mm,
203mm, 300mm
25mm, 60mm, 112mm,
203mm, 300mm
P
Loop Wire
P
P
P
See Whitepaper
P
See Whitepaper
x
$7,425 (Quantity of 1)
$6,480 (Quantity of 3+)
$1,775
$1,422
WIDE BANDWIDTH EARTH LEAKAGE PROTECTION
RANGE OF PROTECTED FREQUENCIES
EVENT RECORDING
RECORD PHASE CURRENT
RECORDING USING ALARM SET POINT
RECORDING USING DIGITAL INPUT
PERIODIC/INTERVAL RECORDING
WEB BASED INTERFACE
VIEW REAL-TIME CURRENT MEASUREMENTS
· OSCILLOSCOPE, RMS AND FFT CURRENT GRAPHS
VIEW DEVICE PARAMETERS
VIEW DATA AND EVENT LOGS
GRAPHICAL LCD DISPLAY
VIEW REAL-TIME CURRENT MEASUREMENTS
· OSCILLOSCOPE, RMS AND FFT CURRENT GRAPHS
VIEW AND ACCESS DEVICE PARAMETERS
VIEW DATA AND EVENT LOGS
ON BOARD MEMORY
1000 Data logs, 50 Event logs
ADJUSTABLE TRIP LEVEL SETTINGS
ADJUSTABLE TRIP TIME SETTINGS
INGRESS PROTECTION (PANEL MOUNTED)
CUT OUT DIMENSIONS (MM)
MOUNTING
TARGET APPLICATION
SETTINGS LOCK
TOROID SIZES (I.D.)
TOROID INTEGRITY CHECKING
DC MEASUREMENT IN AC SYSTEMS
PRICE
ELV 16/3/15
For more information on Ampcontrol’s ELV
visit ampcontrolgroup.com/ELV