AMPCONTROL BRAND GUIDELINES
Transcription
AMPCONTROL BRAND GUIDELINES
ELV – our next generation earth leakage relay AMPCONTROL BRAND GUIDELINES Ampcontrol’s ELV provides wide bandwidth earth leakage protection as per AS/NZS2081:2011. It is designed for use on earth fault limited systems, particularly coal and metal mining applications that may include Variable Speed Drives. The ELV relay provides a definite time operating characteristic with adjustable trip sensitivity and time delay. It latches when tripped and provides normally open and change-over relay contacts. The relay supports an external reset switch, and a 4-20mA interface allowing external monitoring. For security the ELV has provision to prevent unauthorised adjustment of the trip settings. DIN rail or panel mounted through a 69 x 39mm cut out. When panel mounted, the front of the ELV relay is designed to provide IP56 ingress protection. Features • AS/NZS 2081:2011 compliant • Wide operating bandwidth (5Hz to 10kHz) • Increased current range (down to 30mA) • Fail safe operation • Continual monitoring of the toroid • Adjustable trip level and time delay settings The user has the ability to switch the relay between wideband (up to 10kHz), narrowband (power frequency) and weighted frequency mode (up to 10kHz, high frequency corrected). The relay is housed in a stainless steel case and can be either For more information on Ampcontrol’s ELV visit ampcontrolgroup.com/ELV FEATURES The key differences between Ampcontrol’s VSDguard, ELD and ELV relays. VSDguard ELV ELD P 5Hz –10kHz (CT) 0Hz – 10kHz (Shunt) P 5Hz–10kHz x 10Hz–150Hz COMPLIANT TO AS/NZS 2081:2011 P P x EVENT LOGGING P x x CIRCUIT TRIP/TIME PROTECTION VALIDATION P x x P x x P x x P x x P x x P 50mA-5A P 30mA-2.5A P 100mA-2.5A P <50ms-500ms P <50ms-500ms P <50ms-500ms EXTERNAL COMMUNICATIONS P Ethernet x x ANALOGUE OUTPUT P Ethernet P 4-20mA P 4-20mA POWER SUPPLY 24VDC 24-110VAC, 50Hz 24-150VDC 32-110VAC, 50Hz 20-185VDC IP55 IP56 IP56 135x135 69x39 69x39 Panel Panel DIN Rail Panel DIN Rail · All low, medium and high voltage VSD systems · Protection system verification · Diagnostics and fault analysis All low, medium and high voltage VSD systems Simple outlet Earth Leakage Protection Password Protected Non-Tamper Front Panel Non-Tamper Front Panel 25mm, 60mm, 112mm, 203mm, 300mm 25mm, 60mm, 112mm, 203mm, 300mm 25mm, 60mm, 112mm, 203mm, 300mm P Loop Wire P P P See Whitepaper P See Whitepaper x $7,425 (Quantity of 1) $6,480 (Quantity of 3+) $1,775 $1,422 WIDE BANDWIDTH EARTH LEAKAGE PROTECTION RANGE OF PROTECTED FREQUENCIES EVENT RECORDING RECORD PHASE CURRENT RECORDING USING ALARM SET POINT RECORDING USING DIGITAL INPUT PERIODIC/INTERVAL RECORDING WEB BASED INTERFACE VIEW REAL-TIME CURRENT MEASUREMENTS · OSCILLOSCOPE, RMS AND FFT CURRENT GRAPHS VIEW DEVICE PARAMETERS VIEW DATA AND EVENT LOGS GRAPHICAL LCD DISPLAY VIEW REAL-TIME CURRENT MEASUREMENTS · OSCILLOSCOPE, RMS AND FFT CURRENT GRAPHS VIEW AND ACCESS DEVICE PARAMETERS VIEW DATA AND EVENT LOGS ON BOARD MEMORY 1000 Data logs, 50 Event logs ADJUSTABLE TRIP LEVEL SETTINGS ADJUSTABLE TRIP TIME SETTINGS INGRESS PROTECTION (PANEL MOUNTED) CUT OUT DIMENSIONS (MM) MOUNTING TARGET APPLICATION SETTINGS LOCK TOROID SIZES (I.D.) TOROID INTEGRITY CHECKING DC MEASUREMENT IN AC SYSTEMS PRICE ELV 16/3/15 For more information on Ampcontrol’s ELV visit ampcontrolgroup.com/ELV