Radiant Comfort™ Floor Panels
PRODUCT DESCRIPTION
Radiant Comfort™
ThermalStar® Radiant Comfort™ floor panels are precision molded from expanded
polystyrene with a distinct orange color. The insulation panels form a firm base for
water heated radiant floors. Benefits to using Radiant Comfort™ include:
No stapling required– the groove channels hold the tubing right in place
x No professional design or shop drawings needed
x Eliminate the hassle with using left, right, and straight panels– one panel is used for
the entire installation
x New construction panels interlock for a secure placement and to prevent concrete
from seeping through the joints in heated slab applications
x
Table 1 Physical Properties
FEEL THE HEAT BENEATH
YOUR FEET™
New Construction
Panels
Retrofit
Panels
Panel Size
3’ x 4’
2’ x 3’
Panel Thickness
2-5/8”
1”
Accommodates up to 5/8”
pipe
Accommodates 1/2” pipe
Pipe Size
Panel Design
ThermalStar Radiant Comfort panels are available in
two types: new construction and retrofit panels. The
new construction panels are designed to be installed
prior to pouring a heated concrete slab. The retrofit
floor panels are designed to be installed above the
subfloor, and below the flooring option (hardwood
floors, ceramic tiles, carpet, etc.) Since Radiant
Comfort is manufactured out of EPS, it provides both a
heating system template and insulation. Radiant
Comfort panels save on installation time and
eliminates the guesswork for professionals and homeowners alike.
ThermalStar Radiant Comfort floor panels are backed
by a limited lifetime warranty for both physical and
thermal performance. Please visit our website for
further information.
Interlocking Edges
Flush Edge
Compressive Strength (minimum psi) @10% Deformation
D1621**
25 psi
40 psi
Compressive Strength (minimum psi) @1% Deformation
D1621**
11 psi
15 psi
R-value per inch (minimum) at 75F mean temperature C518
11
4.2
R-value per inch (minimum) at 40F mean temperature C518
12.3
4.7
R-value per inch (minimum) at 25F mean temperature C518
12.8
4.9
Flexural Strength (minimum psi) C203
ASTM Classification C578
Water Absorption % by volume, maximum after 24 hour
immersion C272
Water Vapor Permeance (perms) Typical E96
Surface Burning - Flame Spread and Smoked Developed E84
Maximum Use Temperature
50
70
Type II
Type XIV
1.25
1.25
1
2
Flame Spread 20, Smoke Developed 400 (meets code)
Short Term (10-15 minutes) 180F, Long term 165F
Number of panels per 4’ pallet
17 (204 ft2)
88 (528ft2)
Weight of 4’ pallet
85 pounds
120 pounds
64
64
Number of pallets per 48’ trailer
Thermal Resistance: R means the resistance to heat flow. The higher the R-value, the greater the insulating power.
*Please allow 2-3 weeks for all Radiant Comfort shipments
**ThermalStar Radiant Comfort is elastic within 1-2% deformation. To prevent long term creep, 3:1 design safety factors
for static loads of the 10% deformation values are recommended, or use the tested 1% deformation values for design,
http://www.ThermalStarRadiantComfort.com/
http://AtlasEPS.com/
info@atlaseps.com
(800) 917-9138
®
®
CHEMICAL & PHYSICAL
PROPERTIES
Table 2 Chemical Compatibility of Radiant Comfort
Physical properties of each panel can be found in Table 1, while
chemical resistance is listed in Table 2.
MOLD RESISTANCE
ThermalStar Radiant Comfort has been tested against 4 week
exposure to various mold and fungi via ASTM G21, D3273, and
C1338 with no growth of spores on the product. Radiant Comfort
provides no nutritive value for mold. However, construction
practices greatly impact mold growth, and fungi have been known
to even grow on glass.
FREEZE/ THAW EXPOSURE
ThermalStar Radiant Comfort has been tested via ASTM C1512
Moisture & Temperature Cycling for Insulation with no loss of
physical or thermal performance. This test places the product
between a cold chamber and a high humidity chamber with
temperature cycling, measuring the effect on the insulation as
natural moisture drive occurs.
Inorganic Acids (Muriatic, Sulfuric, Boric Acid)
Excellent
Organic Acids (Carbolic, Citric, Acetic Acid)
Good
Bases (Sodium Hydroxide, Potassium Hydroxide, Ammonia)
Excellent
Alcohols (Methanol, Ethanol, Isopropyl Alcohol)
Good
Beer, Tea, Coffee, Carbonated Soda, Water, Fruit Juice
Excellent
Household Liquid Spray Insecticides (non-aqueous)
Poor
Cement
Excellent
MEK, Methylene Chloride, Acetone
Poor
Antifreeze (Ethylene Glycol - Green, Propylene Glycol - Orange)
Excellent
Hydrocarbons (Hexane, Gasoline, Diesel, Kerosene)
Poor
Mineral Oil
Excellent
Other Oils (Corn, Motor, Palm, Coconut Oil)
Good
Agricultural (Manure, Feed, Urine, Soil, Fertilizer)
Excellent
Formaldehyde, Turpentine, Chloroform, Naphtha
Poor
Salts (Ammonium, Ferrous, Sodium Chloride, Sulfur)
Excellent
MDI-based Adhesive (Gorilla Glue, Fast-Tac, Dow Great Stuff)
Good
Bleach, Detergents, Borax
Excellent
Cured Mastic, Construction Adhesive, Hardened Asphalt
Good
Wherever XPS insulation is used
Excellent
Excellent = No degradation, no effect from exposure
Good = some effect from exposure, but not significant for product performance
Poor = significant degradation affecting performance, up to completely dissolving product
This table is a guide only - consult Atlas Technical Services for specific chemical design questions
SAFETY
MSDS for this product available at www.atlaseps.com. Dust
generated from sanding or cutting ThermalStar Radiant Comfort
should be avoided using a dust mask as with other building materials.
Radiant Comfort is combustible and the product should be protected
from ignition sources such as open flames or welder’s torch.
ENVIRONMENTAL
ThermalStar Radiant Comfort Insulation uses air in the insulating cells,
emitting no gasses. Radiant Comfort insulation is readily accepted for
recycle. Based on extrapolation of pounds consumed and pounds
recycled, the EPS industry as a whole in North America exceeded 30%
rate of recycling in 2013. Atlas EPS is a responsible recycle partner,
visit www.epspackaging.org for a drop off location near you to continue
this success.
CODE COMPLIANCE
ThermalStar Radiant Comfort insulation complies with the model building codes when properly installed:
x
x
x
x
Surface Burning – UL BRYX.R16529
Cal Std Reg #CA472
International Energy Conservation Code
ASTM C578 – see product marking for Type
Physical Properties – UL QORW.R16529
International Residential Code (IRC) – UL ER16529.1, ESR-1962
International Building Code (IBC) – UL ER16529.1, ESR-1962
CAN/ULC S102.2, S701 – ULC BOZCC.R16529
ATLAS, the Globe Logo, Solutions. Delivered., the color Pale Creamy Orange, and ThermalStar are
registered trademarks of Atlas Roofing Corporation
Atlas EPS, a Division of Atlas Roofing Corporation
8240 Byron Center Ave SW, Byron Center, MI 49315
(800) 917-9138 www.atlaseps.com
LIT 1058 Rev 04-28-2015