D-EL-317

Transcription

D-EL-317
1500-3000
LIGHTNING PROTECTION OF TOWER
NOT SHOWN HERE.
FOR LAMPS MAINTENANCE
LADDERS SHALL BE PROVIDED
WITH PROTECTIVE CAGE.
CAST LIGHT METAL HOUSING OMNIDIRECTIONAL,
REFLECTION WITH AVIATION RED GLASS DOME,
THERMAL AND SHOCK RESISTANT,CABLE ENTRY
AT BOTTOM THREADED,SHOCKPROOF PORCELAIN
LAMP HOLDER COMPLETE WITH EARTHING,
SCREW, SEALING GASKET AND FLAT BAR FOR
(SEE NOTE "7") MOUNTING, 100W LAMP, 220/250 VOLT.
D
D
D
JUNCTION
BOX
7
5
2
SEE FIXTURE
SUPPORT DETAIL
DETAIL "A"
D
EL.+30
1
WELD
2
D
MIDDLE
B
B
2
25mm.DIA.CONDUIT-8(1x2.5)mm .
MI CABLE
DETAIL "A"
FINISHED
GRADE
3
ELEVATION
No.
SHELL OR
1
3- STACKS LESS THAN 30 METERS HEIGHT FROM THE
GROUND LEVEL DO NOT REQUIRE AIRCRAFT WARNING
LIGHTS.
4- STACKS OF APPROXIMATE HEIGHT OF 30 METERS FROM
THE GROUND LEVEL SHOULD BE FITTED WITH THREE
WARNING LIGHTS SPACED AT 120° AROUND THE STACK,
DIRECTED UPWARDS, AND LOCATED SO THAT THE LIGHTS
CAN BE SEEN FROM ALL DIRECTIONS. THESE LIGHTS
SHALL BE LOCATED BETWEEN 1.5 METERS, AND 3 METERS
BELOW TOP OF THE STACK, AND SHALL BE ACCESSIBLE
FROM EITHER THE TOP LANDING PLATFORM, LADDER, OR
FROM A PAINTER TROLLEY.AS APPLICABLE.
5- ALL THE STACKS HIGHER THAN 30 METERS FROM THE
GROUND LEVEL SHALL HAVE TWO SETS OF AIRCRAFT
WARNING LIGHTS. THE ARRANGMENT OF THE LIGHTS
SHALL BE AS FOLLOWS:
a- ONE SET OF THREE WARNING LIGHTS SHALL BE
INSTALLED AROUND EACH STACK AT A HEIGHT OF 30m.
FROM THE GROUND LEVEL AND SHALL BE SEEN FROM
ALL DIRECTIONS. THE LIGHTS SHALL BE SPACED AT 120°
AROUND THE STACK AND SHALL BE DIRECTED UPWARD.
b- IN ADDITION, ANOTHER SET OF THREE SETS OF WARNING
LIGHTS SHALL BE INSTALLED AT THE TOP OF EACH
STACK, THESE LIGHTS SHALL BE LOCATED BETWEEN
1.5 METERS AND 3 METERS BELOW THE TOP OF THE
STACK, SPACED AT 120° AROUND THE STACK AND
DIRECTED UPWARDS. THE LIGHTS SHALL BE LOCATED
SUCH THAT THEY CAN BE SEEN FROM ALL DIRECTIONS
AND SHALL BE ACCESSIBLE FROM EITHER THE TOP
LANDING PLATFORM LADDER OR FROM A PAINTER
TROLLEY.
c- WHERE A LIGHT IS SHIELDED FROM ANY DIRECTION BY AN
ADJACENT OBJECT, ADDITIONAL LIGHT(S) SHALL BE
PROVIDED ON THE OBJECT IN SUCH A WAY AS TO RETAIN
THE GENERAL DEFINITION OF THE OBJECT TO BE LIGHTED.
6- IN HAZARDOUS AREA, SPECIAL CONSIDERATION SHALL BE
GIVEN TO INSTALLATION OF AIR CRAFT WARNING LIGHT
PANEL
7- MAXIMUM SPACING (D) IS 1000mm.
4
STACK PLATE
WELD
NOTES
1- ALL DIMENSIONS ARE IN MILLIMETERS.
2- FOR TYPE OF LIGHTING FIXTURE, MOUNTING ELEVATION,
etc. SEE RELEVANT LIGHTING LAYOUT DRAWINGS.
1
WELD
CABLE SUPPORT (L-30x30x3)x200L
4
BOLT & NUT WITH 1-SPRING WASHER AND
2-FLAT WASHERS
SIZE:M8 x 60
6
MOUNTING PLATE (200x200x5)
5
SECTION "B-B"
6
FIXING HOLE
BOLTS
1-SET
FIXTURE SUPPORT (INP-100)
2
3
2
QTY.
DESCRIPTION
C
B
A
REV.
FLAT IRON 20mm. WIDTH 5mm. THICK
CABLE GLAND FOR MI CABLE
DESCRIPTION
IRANIAN PETROLEUM STANDARDS
FOUNDATION
DATE
NO REVISION PERMITTED UNLESS APPROVED BY STANDARD ORGANIZATION
TOP VIEW
REFERENCE DRAWING
LIGHTING INSTALLATION DETAILS
"CATEGORY 300"
FIXTURE SUPPORT DETAIL
AIRCRAFT WARNING LIGHT
DATE
(MOUNTED ON STACK)
DRAWING No.
IPS-D-EL-317
SHEET REV.
1
2
100W 230V AC. LIGHTING FIXTURES
NOTES
100W 230V AC. LIGHTING FIXTURES
1- ALL DIMENSIONS ARE IN MILLIMETERS.
2- WHEN MAIN LAMP FAILS RELAY 37 TRIPS AND RELATED
CONTACT CLOSES THE STANDBY LAMP CIRCUIT.
3- EVERY MONTH A CHECK SHOULD BE MADE TO ENSURE
THAT ALL THE WARNING LIGHTS ARE IN OPERATING
CONDITION.
FIRST LEVEL
FIXTURES
SECOND LEVEL
FIXTURES
2
25mm. DIA. CONDUIT -8(1x2.5)mm MI CABLE
100W 230V AC. LIGHTING FIXTURES
SEE NOTES "2"
MAIN LAMP
1
2
3
4
37
5
6
7
37
H2.1
8
9
10 11 12
37
H2.2
13 14 15
37
H2.3
16 17 18
37
H2.3
STANDBY
LAMP
37
H2.4
37
H2.5
37
H2
H1
16A
L
L
N
230V AC.
25mm. DIA. HOLE TO BE DRILLED IN PLATE FOR
FIXING OF INCOMING CABLE GLAND OR CONDUIT.
230V AC.
AIRCRAFT WARNING LIGHT PANEL
ONE LINE DIAGRAM
16A
TYPICAL WIRING DIAGRAM
FOR SINGLE PAIR OF LAMPS
5W 230V AC. INDICATING LAMP (RED COLOR)
UNDERCURRENT RELAY
MINIATURE CIRCUIT BREAKER
PROTECTIVE GROUND / EARTH
H1
PROTECTIVE GROUND / EARTH
H2
PROTECTIVE GROUND / EARTH
C
B
A
16A
N
LEGEND
SEE
NOTE "2"
REV.
DESCRIPTION
IRANIAN PETROLEUM STANDARDS
DATE
NO REVISION PERMITTED UNLESS APPROVED BY STANDARD ORGANIZATION
REFERENCE DRAWING
LIGHTING INSTALLATION DETAILS
"CATEGORY 300"
AIRCRAFT WARNING LIGHT
DATE
(TYPICAL PANEL)
DRAWING No.
IPS-D-EL-317
SHEET REV.
2
2