Safewatch Pro 2000/Security Manager 2000/Entrepreneur 2000
Transcription
Safewatch Pro 2000/Security Manager 2000/Entrepreneur 2000
K5244 7/00 Safewatch Pro 2000/Security Manager 2000/Entrepreneur 2000 (Model: SAVS20ADT-1 or SAVS20ADTG or SAVS20ADTCN-1) System Installation Notes For full installation and programming information, please refer to the Installation & Setup Guide for this product. Mounting the Cabinet Mount the PC board(s) as shown below. HOLES FOR ANTENNAS AND GROUNDING LUGS BOARD SUPPORTING SLOTS CIRCUIT BOARD CABINET RECEIVER CIRCUIT BOARD (See Detail D) + + DETAIL A SIDE VIEW OF BOARD -SUPPORTING SLOTS SHORT MOUNTING CLIPS CONTROL CIRCUIT BOARD LONG MOUNTING CLIPS SCREW (2) GROUNDING LUG (2) ANTENNA (2) DETAIL B SIDE VIEW OF SHORT MOUNTING CLIPS CABINET DETAIL C SIDE VIEW OF LONG MOUNTING CLIPS RCVR BRD + + ANTENNA MOUNT (2 PLACES) DETAIL D ANTENNA AND GROUNDING LUG INSTALLATION Setting Up the 5881/5882 Wireless Receiver OFF 1 2 3 4 ON ON 1. Set the receiver's DIP switch for device address “0,” as described in its instructions (set all switches to the left, “off” position). 2. Mount the receiver. The RF receiver can detect signals from transmitters within a nominal range of 200 feet. Take this into consideration when determining mounting location. 3. Connect the receiver's wire harness to the control's touchpad terminals (4, 5, 6, and 7). Plug the connector at the other end of the harness into the receiver. 4. Refer to the installation instructions provided with the receiver for further installation procedures regarding antenna mounting, etc. Testing the Transmitters To be sure reception of the transmitter's signal at the proposed mounting location is adequate, perform a Go/No Go Test after programming the transmitters in the control panel. Go/No Go Test Mode The Go/No Go Tests will verify adequate RF signal strength from the proposed transmitter location, and allow you to reorient or relocate transmitters if necessary, before mounting the transmitters permanently. This mode is similar to the Transmitter Test mode, except that the wireless receiver gain is reduced. This will enable you to make sure that the RF signal from each transmitter is received with sufficient signal amplitude when the system is in the normal operating mode. 1. With at least one 2-line Custom English display touchpad (6139B) connected to the system, powerup the system temporarily. If you had previously connected the AC transformer to the control panel, you need only plug in the transformer (to 120VAC outlet) to power-up the system. 2. Enter [Installer code (6321)] + [#] + 4 from partition 1's touchpad. For multi-partition systems, make sure all partitions are disarmed before entering this mode. 3. After you have placed transmitters in their desired locations and the approximate length of wire to be run to sensors is connected to the transmitter's screw terminals (if used), fault each transmitter. Do not conduct this test with your hand wrapped around the transmitter, as this will cause inaccurate results. Note: On button-type transmitters whose buttons have been set to Arm Away, Arm Stay, or Disarm, pressing a button will take the system out of the Go/No Go Test mode and cause that action. a. The touchpad will beep three times to indicate signal reception and display the appropriate zone number. b. If the touchpad does not beep, you should reorient or move the transmitter to another location. Usually a few inches in either direction is all that is required. If each transmitter produces the proper touchpad response when it is faulted, you can then permanently mount each of the transmitters according to the instructions provided with them. 4. Exit the Go/No Go Test mode by entering: [Installer code (6321)] + OFF. UL Notes 1. This is a "Grade A" residential system. 2. Alarm Sounder plus Auxiliary Power currents must not exceed 600mA total for UL installations (Aux power 500mA max.). 3. The system must be configured as a single partition only. 4. 5816 and 5817 transmitter loop wiring must not exceed 3 feet (with no intervening barriers), since they do not supervise their loop wiring. 5. The 5802MN, 5802MN2, 5804, 5804BD, 5814, 5816TEMP, 5819, 5819S (WHS & BRS), 5827BD, and 5850 are not approved for use in UL installations. 6. RF Jam detection must be enabled for UL installations using wireless devices. Note: When RF jam detection is selected, an RF receiver will detect a condition that may impede proper RF reception (i.e., jamming or other RF interference). Such a condition will produce a message display, and a report will be sent to the central monitoring station (if trouble reporting is enabled). 7. Use only UL Listed sounding devices in UL installations. 8. Downloading is not permissible for UL installations unless a technician is on-site. 9. Use a 17.2AH battery only. 10. Do not program an automatic telephone dialer or similar device to call a police station number that has not been specifically assigned by that police station for such service. 11. The alarm current provided by zone 1 will support only one smoke detector in the alarmed state and 16 smoke detectors in standby mode. 12. An ADEMCO model 610-7 must be used as an end-of-line resistor at the last detector. 13. Powerline Carrier (X-10) devices and the 4300 transformer are not UL listed for fire or burglary functions and are intended for home automation. 14. For Residential Fire and/or Burglary installations, use the ADEMCO RES-UL cabinet. 15. For Commercial Burglary installations, use the ADEMCO COM-UL cabinet.* *The Vista-ULKT Commercial Cabinet Accessory Kit provides all necessary parts and instructions to install this panel in Commercial applications. –2– NFPA Note You may only use hardwired zone 1 as a fire zone. However, any wireless zone can be used for fire. Compatible Devices 2-WIRE SMOKE DETECTORS Detector Type System Sensor Model No. Photoelectric w/heat sensor, direct wire 2300TB Photoelectric, direct wire 2400 Photoelectric w/heat sensor, direct wire 2400TH Photoelectric 2451 w/B401B base Photoelectric w/heat sensor 2451TH w/B401B base Ionization, direct wire 1400 Ionization 1451 w/B401B base Photoelectric duct detector 2451 w/DH400 base Ionization duct detector 1451D w/DH400 base H Low-profile, Photoelectric, w/135°F thermal 2100T Low-profile, Ionization type, direct wire 1100 SOUNDERS Ademco AB-12M 10” Motorized Bell & Box Ademco 1011BE12M 10” Motorized Bell & Box Ademco 702 Outdoor Siren Ademco 719 2-Channel Siren Ademco 747 Indoor Siren Ademco 747UL Indoor Siren Ademco 744 Siren Driver Ademco 745X3 Voice Siren Driver Ademco 705-820 5-inch Round Speaker Ademco 713 Speaker System Sensor PA400B (beige)/PA400R (red) Indoor Piezo Sounder Sounder Supervision (NFPA Requirement) This control contains a sounder (Bell) supervision option. To enable the Bell supervision option: 1. Cut the red Bell Supervision Jumper located above terminals 2 and 3 on the control board. 2. Connect a 2000 ohm resistor across the terminals of the last sounding device. Note: If the “Alarm Output” loop connected to the external sounder is opened or shorted, the message “Bell Failure” (Custom English Display touchpads) or “CHECK 70” (English Display touchpads) will be displayed, accompanied by a trouble sound. A report (Contact ID event code 321) will also be sent to the central station (if trouble reporting is enabled). –3– TROUBLESHOOTING GUIDE SYMPTOM POSSIBLE CAUSE 1. Low Battery message on touchpad. 2. “CHECK” and zone number 2–8 is displayed. 3. Digital communicator message not being received. “Bat” or “System Lo Bat” (no zone Nos.) “Bat” or “Lo Bat” + “00.” “Bat” or “Lo Bat” + “nn.” Control has sensed a high resistance condition on a loop in one of the hardwired zones (2–8). 1a. 1b. 1c. 2. System battery is low or missing. Remote RF touchpad battery is low. Transmitter for zone “nn” has a low-battery. Check the sensor or the loop wiring in the affected zone. The system will not arm until this condition is corrected (or the affected zone is bypassed). 3a. 3b. 3c. 3d. System is in Test mode. Telephone connection not secure. Digital communicator malfunctioning. Telephone number in program needs prefix or access code. Telephone call to central monitoring station requires operator assistance. 3a. 3b. 3c. 3d. 3e. Remove from Test mode. Check all connections. Check with a different control. Program prefix or access code into the control The system cannot work in this situation. 4a. “CC” or “MODEM COMM” displayed. 4a. System is in communication with downloader at central station. Wait until download session is finished. 4b. “d1” or “SYSTEM BUSY” displayed. 4b. System has just been powered and is in its 1minute initialization. To bypass this time, press '#' + '0'. 4c. “E4” or “E8” displayed. 4c. More zones have been programmed than the zone expansion modules can handle. Delete some zones or use a higher capability RF receiver. 4d. 4d. Touchpad address setting incorrect. Touchpads must be set for address 31 (nonaddressable mode). 5a. Transmitter or 5881/5882 not properly powered. 5a. 5b. 5c. 5b. 5c. 5d. Transmitter located too for from RF receiver. Metal shielding between transmitter and RF receiver. Transmitter malfunctioning. 5d. 5e. 5881/5882 malfunctioning. 5e. 5f. 5g. 5h. 5i. Transmitter No. (zone) not programmed. 5881/5882 address incorrect. Field ✱22 not set properly. 5800 RF receiver experiencing RF interference (displays “Rcvr Jam” or “CHECK 90”). 5f. 5g. 5h. 5i. Check or change transmitter's battery. Check control's AC power. Move transmitter or RF receiver. Check for large metal obstructions, then relocate transmitter if necessary. Verify by activating 5881/5882 with another, similar transmitter. If O.K. now, return defective transmitter. Verify by making sure other transmitters cannot activate 5881/5882. If defective, replace and return original 5881/5882. Verify programming. Set DIP switch on 5881/5882 for address “0.” Set field ✱22 for “2” or “4.” 5800 system set for RF Jam detection. Check for source of RF interference. If necessary, change location of receiver. 3e. 4. 5. System doesn't respond to keystrokes on touchpad. Transmitter signal not received at 5881/5882. REMEDY 1a. 1b. 1c. 2. Specifications 1. Physical: 12-1/2” W x 14-1/2” H x 3” D (318mm x 368mm x 76mm) 2. Electrical: VOLTAGE INPUT: 16.5VAC from plug-in 25VA transformer, Ademco No. 1321 (in U.S.A.) RECHARGEABLE BACKUP BATTERY: 12VDC, 4AH or greater (sealed lead acid type). Charging Voltage: 13.8VDC. See “Calculating the Battery Size Needed” in this document. ALARM SOUNDER: 12V, 2.0 Amp output can drive 12V BELLS or can drive one or two 702 (series connected) self-contained 20-watt sirens. Do not connect two 702s in parallel. AUXILIARY POWER OUTPUT: 12VDC, 500mA max. 3. FUSE: Battery (3A) No. 90–12 Communication: Line Seize: Double Pole 4. FCC Registration No.: AC 398U–68192–AL–E Maximum Zone Resistance: Zones 1–8 = 300 ohms excluding EOLR ADT Security Services, Inc. One Town Center Rd. Boca Raton, FL 33486 ¬.l K5244 7/00