7 AMI 70 en
Transcription
7 AMI 70 en
Neles Axiom On/Off Valve Controller with Proximity Switches Installation, Maintenance and Operating Instructions 7 AMI 70 en • 3/2010 2 7 AMI 70 en Table of Contents 1 2 3 4 5 6 7 GENERAL........................................................ 3 1.1 Introduction ............................................ 3 1.2 Markings ................................................ 3 1.3 Specifications......................................... 3 1.4 CE marking ............................................ 5 1.5 Recycling and disposal ......................... 5 1.6 Safety precautions ................................. 5 ASSEMBLY AND MOUNTING ........................ 5 SENSING AND COMMUNICATIONS MODULE SENSOR SETTING.......................................... 6 3.1 Bench testing ......................................... 6 3.2 Fault alerts for AMI96_D......................... 7 3.3 Additional features for AMI96_D ............ 8 EXPLODED VIEW ........................................... 9 DIMENSIONS................................................. 10 WIRING DIAGRAMS ..................................... 11 6.1 Type AMI33.......................................... 11 6.2 Type AMI44.......................................... 11 6.3 Type AMI96.......................................... 12 6.4 Type AMI96_D ..................................... 12 6.5 Type AMI97.......................................... 12 6.6 Type AMI93.......................................... 13 6.7 Type AMI94.......................................... 13 6.8 Installation Diagram for Explosive Atmospheres for Europe ...................... 14 6.9 Intrinsic Safety Hazardous Location Installation Diagram ............................. 15 6.10 Non-Incendive Field Wiring Apparatus Installation Drawing.............................. 16 6.11 Non-Incendive Safety Hazardous Location Installation Diagram .............. 17 6.12 Intrinsic Field Wiring Apparatus Installation Drawing.............................. 18 TYPE CODE................................................... 19 READ THESE INSTRUCTIONS FIRST! These instructions provide information about safe handling and operation of the on/off valve controller. If you require additional assistance, please contact the manufacturer or manufacturer's representative. Addresses and phone numbers are printed on the back cover. SAVE THESE INSTRUCTIONS! Subject to change without notice. All trademarks are property of their respective owners. 7 AMI 70 en 3 1 GENERAL AS-Interface VCT (96) 1.1 Introduction Configuration This manual provides essential information on the Neles Axiom on/off valve controller. The Neles Axiom is used for quarter-turn automated pneumatic on/off valves.. 1.2 Markings Model Serial 448387 The device has identification plate attached to the cover, see Fig. 1. Date Sensor Rating: NAMUR 7-24Vdc IS: Ui=16Vdc, Ii=25mA, Pi=1.0W, Ci=4.4nF, Li=0mH; Install per 105157 S olenoid Rating: 12Vdc, 0.5W; Press: 40 to 120 psi IS: Ui=28V, Ii=120mA, Pi=1.0W, Ci=0nF, Li=0mH Warning: 1) When used within a Zone 0 location, the aluminum enclosure shall be installed in such a manner as to prevent the possibility of sparks resulting from friction or impact. 2) To prevent the risk of electrostatic sparking, the equipment enclosures shall be cleaned only with a damp cloth. Ex ia IIC T5 Ta @ -18°C to +50°C IP67 II 1 G FM07ATEX0047X Manufactured by StoneL Patent Pending Fig. 1 1725 1.3 Identification plate Model Serial number Date Protection class information Type Temperature range CE and hazardous area marks Warning Manufacturer information Specifications Sensing and communication module SST Switching sensors (33) Configuration 2 Two-wire solid state switching outputs 1 or 2 solenoid power input(s) 1 Output Normally open (SPST) Max. current inrush 2.0 A Max. current continuous 0.25 A Min. on current 2.0 mA Max. leakage current 0.5 mA Voltage range 20 to 125 V DC / 125 V AC Max. voltage drop 7.0 V / 100 mA Short circuit protection Protected from direct application of up to 125 V DC / V AC Namur sensors (44) Configuration Output Current ratings Voltage range AS-Interface VCT (97) with extended addressing Configuration AS-I version Input voltage Devices per network 2 Namur Outputs 1 or 2 solenoid power input(s) 2 Conforms to DIN 19234 Target on I < 1.0 mA Target off I > 2.1 mA 5 to 25 V DC 2 Discrete inputs (Open and Closed) 2 Auxiliary discrete inputs 1 Discrete output (Drive solenoid) 4 2.1 26.5 to 31 V DC 62 FOUNDATION fieldbus VCT, bus powered (93) Configuration Fergus Falls, MN U.S.A. Identification plate markings: 1. 2. 3. 4. 5. 6. 7. 8. 9. AS-I version Input voltage Devices per network 2 Discrete inputs (Open and Closed) 2 Auxiliary discrete inputs 2 Discrete outputs (Drive solenoids)4 2.1 26.5 to 31 V DC 31 Current input Voltage range Other features 2 Discrete inputs (Open and Closed) 2 Discrete outputs (Drive Piezo) 3 16 mA quiescent 9 to 32 V DC Stores number of actuations Stores date of last service Predetermined output fail state FOUNDATION fieldbus VCT, bus powered (94) Configuration Signal current Input Signal voltage range External voltage input External current input Other Features 1 Solenoid option "H" Solenoid option "E" 3 Piezo option "A" 4 Solenoid option "D" 2 2 Discrete inputs (Open & Closed) 2 Externally Powered discrete outputs (Drive solenoids)4 16 mA quiescent 9 to 32 V DC 24 V DC Solenoid dependent Stores number of actuations Stores date of last service Predetermined output fail state 4 7 AMI 70 en PNEUMATIC VALVE SPECIFICATIONS Valve design Pilot operator options Configuration Single pilot Dual pilot Flow rating Porting Operating pressure Filtration requirements Operating temperature 2 Operating life Manual override Material of construction Spool Body O-ring spacers End caps & fasteners O-rings Pilot operated spool valve Solenoid coil or Piezo 1 5/2 (5-way, 2-position) spring return Shuttle piston, 5/2 (5-way, 2-position) 0.70 Cv (0.60 Kv) 1/4" NPT 2.7 to 7.5 bar 40 µm (Piezo, 30 µm) See pilot specifications below 1 million cycles Internal momentary Nickel plated aluminum Epoxy coated anodized aluminum Polysulphone Stainless steel Nitrile compound Piezo pilot Filtration requirements Operating temperature DC power Dried air / 30 µm -10° to +60 °C 2 mA / 6.5 V DC Dead band 3° from set point (Rotational distance from original set point where switch will de-energize.) Maximum rotational range120° Operating life Pneumatic valve 1 million cycles Approvals II 1G Ex ia IIC T5 II 3G Ex nA nC IIC T5 Hazardous area ratings Ex ia: Sensor: Ui = 16 V, Ii = 25 mA, Pi = 1.0 W, Ci = 4.4 nF, Li = 0 mH Solenoid: Ui = 28 V, Ii = 120 mA, Pi = 1.0 W, Ci = 0 nF, Li = 0 mH Ex nA nC: AMI33_: AMI44_: AMI93_, AMI94_: AMI96_, AMI97_: U ≤ 75 V DC U ≤ 24 V DC U ≤ 32 V DC U ≤ 31.6 V DC Enclosure protection IP67 Solenoid pilot Electrical ratings H option 0.6 W / 22 V DC min., up to 130 V AC max. E (IS) option 0.5 W, 12 to 15 V DC D option 0.5 W / 24 V DC AC current consumption 18 mA (H) Operating temperature2 -18° to 50 °C Actuator Axiom Pneumatic Valve 2 3 1 Piezo used for bus powered FOUNDATION fieldbus applications only. SR 2 Extended temperature option (-40° to +80 °C) available. Option -T at end of type code. General specifications and ratings Housing and mounting manifold Epoxy coated anodized aluminum Cover and visual indicator Lexan polycarbonate Fasteners and mounting adaptors Stainless steel Pneumatic valve See Pneumatic valve specifications below 1 5 Materials of construction Fig. 2 4 Spring return actuator with rebreather open Actuator Axiom Pneumatic Valve Temperature ratings (pneumatic valve dependent) 3 Piezo pilots (A) -10° to +60 °C Solenoid pilots (D, E, H) -18° to +50 °C Special solenoid pilot -40º to +70 °C available, option -T in type coding. DA 2 Position sensor system 5 Accuracy Repeatability Setting buffer Within 1° Within 1° 2° from set point (Rotational distance from original set point where switch will energize on return stroke.) Fig. 3 1 4 Double acting actuator with rebreather closed 7 AMI 70 en 1.4 CE marking The limit switch meets the requirements of the European Directives and has been marked according to the Directive. 1.5 Recycling and disposal Most limit switch parts can be recycled if sorted according to material. See the list below for materials. In addition, separate recycling and disposal instructions are available from us. A limit switch can also be returned to us for recycling and disposal against a fee. 1.6 Safety precautions CAUTION: Do not exceed the permitted values! Exceeding the permitted values marked on the limit switch may cause damage to the switch and to equipment attached to the switch and could lead to uncontrolled pressure release in the worst case. Damage to the equipment and personal injury may result. CAUTION: To prevent ignition of hazardous atmospheres, replace cover before energizing the electrical circuits. Keep cover tightly closed when in operation. 5 2 ASSEMBLY AND MOUNTING NOTE: To mount the Axiom requires a mounting kit specific to the actuator the Axiom is to be mounted to. Neles Axiom mounting kits are sold separately. 1. Refer to Axiom Assembly Drawing located in Section 4 when performing mounting and assembly procedures. 2. Remove Axiom unit from shipping container. Ensure all listed items are present. 3. With an M4 allen wrench, loosen the four captive Axiom Cover Screws (Item# 1), remove cover. 4. Determine if the actuator the Axiom is to be mounted on is double acting (DA) or spring return (SR). Flip the Axiom body (Item# 4) over and ensure the DA/SR Plug (Item# 5) is in the correct position. (See Detail A in Section 4). If the DA/SR Plug is in the incorrect position, gently remove plug with a pair of pliers and insert into the proper hole. 5. From the mounting kit package, locate the Air Manifold Plate (Item# 14). Place the Air Manifold Plate on the actuator. Using an M4 allen wrench, fasten down with the four Air Manifold Mounting Screws (Item# 11). Torque screws to 2.8 - 3.4 Nm. 6. Place Visual Indicator Drive Block (Item# 10) into slot on the actuator shaft. Place Visual Indicator Drum Coupler (Item# 8) onto the Visual Indicator Drive Block. Next, place the Visual Indicator Drum (Item# 7) onto the Visual Indicator Drum Coupler. Align the holes in all three items with the the threaded hole in the actuator shaft and fasten down with the Visual Indicator Drum Retaining Screw (Item# 9). Leave screw loose in order to facilitate indexing of the visual indicator. 7. With the actuator in the closed position, center the Visual Indicator Drum until the “OPEN” quadrant is centered between the “V.I INDEX” markings on the AIr Manifold Plate. (See Detail - B in Section 4). Tighten down with the Visual Indicator Drum Retaining Screw 1.7 - 2.3 Nm. NOTE: In high cycle or high vibration applications, blue Loctite® may be used on the Air Manifold Mounting Screws (Item# 11) and the Visual Indicator Drum Retaining Screw (Item# 9). 8. Verify Air Manifold Plate Orifice O-rings (Item# 12) and Visual Indicator Cover O-ring (13) are in place. 9. Place the Visual Indicator Cover (Item# 6) over the Visual Indicator Drum assembly then set the Axiom Body (Item# 4) in place. With an M4 allen wrench, torque the Axiom Body Screws to 2.8 - 3.4 Nm. 10.After all wiring and sensor setting procedures have been completed, install Axiom Cover and torque Axiom Cover Screws to 1.7 - 2.3 Nm. 6 3 7 AMI 70 en SENSING AND COMMUNICATIONS MODULE SENSOR SETTING Type AMI 33, 96, 97, 93, 94 1. With the Sensor & Communication Module (CCM) wired to the control system and power applied, (Refer Wiring Diagram located in Section 6), operate actuator to the closed position. 2. Press and hold SET CLOSED button until CLOSED LED is lit (2 seconds). Release button. 3. Operate actuator to the open position. 4. Press and hold SET OPEN button until OPEN LED is lit (2 seconds). Release button. 5. Set points are retained even after power is removed. 6. Sensor & Communication Modules on Axiom units with a single solenoid have a SOLENOID POWER LED indicating when solenoid power is applied. Type AMI 44 1. With the Sensor & Communication Module (CCM) wired to the control system and power applied, (Refer Wiring Diagram located in Section 6), operate actuator to the closed position. 2. Press and hold SET CLOSED button until OPEN LED goes out (2 seconds). Release button. 3. Operate actuator to the open position. 4. Press and hold SET OPEN button until CLOSED LED goes out (2 seconds). Release button. 5. Both OPEN and CLOSED LEDs will be lit during midtravel. Set points are retained even after power is removed. 6. Sensor & Communication Modules on Axiom units with a single solenoid have a SOLENOID POWER LED indicating when solenoid power is applied. SET OPEN SET CLOSED OPEN CLOSED Setup Instructions: Operate Actuator to Closed Position and Push SET CLOSED for 2 seconds. Operate Actuator to Open Position and Push SET OPEN for 2 seconds SOLENOID POWER 3.1 Bench testing Type AMI33 Power must be applied to both sensors to ensure proper circuit operation. Use a 24 V DC power supply with series load resistor, (2 kΩ - 6 kΩ), connected to the 24 V DC +. Operate actuator to the closed position. Connect 24 V DC + to the “Closed C” (common) and “Open C” (common) terminals. Connect 24 V DC - to the “Closed NO” and “Open NO” terminals. Press and hold SET CLOSED button until CLOSED LED is lit (2 seconds). Release button. Operate actuator to the open position. Press and hold SET OPEN button until OPEN LED is lit (2 seconds). Release button. Set points are retained even after power is removed. To test solenoid, apply power to the “Sol Pwr IN” terminals only. See warning below. WARNING: Do not apply external power to the “Sol Out” terminals. This will cause permanent damage to the unit. CAUTION: A series load resistor must be used when bench testing in order to ensure proper module operation. NOTE: If using only one of the sensors for valve position feedback, the open sensor (green) must be used. Type AMI44 Power must be applied to both sensors to ensure proper circuit operation. Use a 24 V DC power supply. A series load resistor is not required when bench testing. Operate actuator to the closed position. Connect 24 V DC + to the “Closed +” and “Open +” terminals. Connect 24 V DC - to the “Closed -” and “Open -” terminals. Press and hold SET CLOSED button until OPEN LED goes out (2 seconds). Release button. Operate actuator to the open position. Press and hold SET OPEN button until CLOSED LED goes out (2 seconds). Release button. Both OPEN and CLOSED LEDs will be lit during mid-travel. Set points are retained even after power is removed. NOTE: If using only one of the sensors for valve position feedback, the open sensor (green) must be used. Type AMI96, 97 Fig. 4 Sensor and communication module (CCM) To test sensors, use a 24 V DC power supply. No series load resistor is required. Operate actuator to the closed position. Apply power across the “ASI+” and “ASI-” terminal points. Press and hold SET CLOSED button until CLOSED LED is lit (2 seconds). Release button. Operate actuator to the open position. Press and hold SET OPEN button until OPEN LED is lit (2 seconds). Release button. Set points are retained even after power is removed. A functioning AS-Interface network is required to test communications. WARNING: Do not apply external power to the output terminals. this will cause permanent damage to the unit. 7 AMI 70 en 7 Type AMI93, 94 To test sensors, use a 9-32 V DC power supply. No series load resistor is required. Operate actuator to the closed position. Apply power across the “FB+” and “FB-” terminal points. Press and hold SET CLOSED button until CLOSED LED is lit (2 seconds). Release button. Operate actuator to the open position. Press and hold SET OPEN button until OPEN LED is lit (2 seconds). Release button. Set points are retained even after power is removed. A functioning Foundation Fieldbus network is required to test communications. WARNING: Do not apply external power to the output terminals. this will cause permanent damage to the unit. Fault alerts for AMI96_D 1. The OPEN green LED is lit steady when the valve is in the open position and the open position sensor is ON. Input Bit 3 (DI2) will be set to “1”. If the valve is open and the LED is not lit, perform the sensor setting according to instructions located in Section 3. 2. The CLOSED red LED is lit steady when the valve is in the closed position and the closed position sensor is ON. Input Bit 4 (DI3) will be set to “1”. If the valve is closed and the LED is not lit, perform the sensor setting according to instructions located in Section 3. 3. The SOLENOID POWER yellow LED is lit steady when Output Bit 3 (DO2) is set to “1” to energize the solenoid. 4. The BAD SOLENOID COIL red LED will flash at a 2 Hz rate if the solenoid pilot valve coil windings are either open or shorted. The Peripheral Fault Bit will be set to “1”. Fault indication will clear when solenoid pilot valve is replaced. 5. The LOW AIR SUPPLY PRESSURE red LED will flash at a 2 Hz rate if the supply pressure drops below 2.8 bar. Input Bit 1 (DI 0) will be set to “1”. Fault indication will clear when supply pressure goes back above 2.8 bar. 6. The STUCK SPOOL/PILOT red LED will flash at a 2 Hz rate if after 5 seconds** of power being applied The Stroke Time Alarm circuit timing is manually adjustable from 1 to 60 seconds. When manually setting the Full Stroke Time, the secondary timing used in the STUCK SPOOL/PILOT and the STUCK PROCESS VALVE/ACTUATOR diagnostic functions is fixed to one half the time period of the Full Stroke Time. (For example: if Full Stroke Time is set to 30 seconds, the time out for the STUCK SPOOL/PILOT and the STUCK PROCESS VALVE/ACTUATOR diagnostic functions will be 15 seconds). See Section 3.3 for Stroke Time Alarm adjustment procedureure. SET OPEN Green Process valve is open Normal Operation LED will be continuously lit when process valve is open CLOSED Red Process valve is closed Normal Operation LED will be continuously lit when process valve is closed 3 SOLENOID POWER Yellow Solenoid valve is energized Normal Operation LED will be continuously lit when solenoid is energized 4 BAD SOLENOID COIL Red Solenoid coil is open or shorted Fault State LED will flash at a 2 Hz rate if solenoid coil is open or shorted 5 LOW AIR SUPPLY PRESSURE Red 6 STUCK SPOOL/ PILOT Red Solenoid valve will not shift Fault State LED will flash at a 2 Hz rate if solenoid valve does not shift 7 STUCK PROCESS VALVE/ACTUATOR Red Valve/Actuator will not turn Fault State LED will flash at a 2 Hz rate if valve/actuator does not turn 1 2 Fig. 5 Supply air pressure Fault State LED will flash at a 2 Hz rate if is low supply air pressure is <2.8 bar Diagnostic LED Indications Operate Actuator to Open Position and Push SET OPEN for 2 seconds SET CLOSED CLOSED 2 SOLENOID POWER 3 Diagnostics: Blinking LED indicates problem 4 BAD SOLENOID COIL 6 STUCK SPOOL/PILOT 5 LOW AIR SUPPLY PRESSURE 7 STUCK PROCESS VALVE/ACTUATOR (4) OPEN 1 Description ASI + Operational State (3) Function Description ASI - LED Color SOL OUT+ (2) LED Setup Instructions: Operate Actuator to Closed Position and Push SET CLOSED for 2 seconds. OPEN SOL OUT- (1) 3.2 to the coil, the internal porting pressure does not rise above 0.7 bar. Conversely, if after 5 seconds** of power being removed from the coil and the internal porting pressure does not drop below 2.1 bar, a STUCK SPOOL/PILOT fault will be indicated. For either condition, the Peripheral Fault Bit will be set to “1”. Fault indication will remain active until internal porting pressure requirements are met. 7. The STUCK PROCESS VALVE/ACTUATOR red LED will flash at a 2 Hz rate if after 5 seconds** of power being applied to or removed from the coil, the valve/ actuator does not move by a minimum of 10% of stroke, provided there is not a STUCK SPOOL/PILOT or LOW AIR SUPPLY PRESSURE fault already indicated. Input Bit 2 (DI 1) will be set to “1”. A STUCK PROCESS VALVE/ACTUATOR fault will also be indicated if the valve/actuator doe not reach the commanded position within 20 seconds** (Valve open position when solenoid coil is energized or valve closed position when solenoid coil is de-energized). This is also referred to as a “Stroke Time Alarm”. Input Bit 2 (DI 1) will be set to “1”. **NOTE: The Factory default time settings of the Stroke Time Alarm circuit is 20 seconds for valve Full Stroke Time and 5 seconds for the STUCK SPOOL/PILOT and the STUCK PROCESS VALVE/ACTUATOR diagnostic functions. 8 3.3 7 AMI 70 en Additional features for AMI96_D Stroke Time Alarm Adjustment Procedure CAUTION: Valve/Actuator will automatically stroke while performing this procedure. 1. Read all instructions prior to performing this procedure. The Stroke Time Alarm is adjustable from 1 to 60 seconds. AS-Interface communications is not needed to perform this procedure, however, a 24 V dc power source connected to the ASI+ and ASIand an air source of a minimum of 2.8 bar connected to the Axiom supply pressure port (Port 1) will be required. 2. Ensure the CLOSED and OPEN sensors have been set. If not, perform the sensor setting according to instructions located below. 3. With the valve/actuator in the closed position, verify there are no fault indications, then press and hold both the SET CLOSED and SET OPEN buttons until both the CLOSED and OPEN LED’s are lit (2 seconds). Release both buttons, the red CLOSED LED should be flashing. 4. Push the SET CLOSED button to start the Timer function. The valve/actuator will automatically open and the OPEN LED start to flash. 5. After the valve/actuator has fully opened, wait the desired time the Stroke Time Alarm is to be set to (1 to 60 seconds), then push the SET OPEN button. This will stop the Timer function and the valve/actuator will automatically go back to the closed position. 6. The unit is ready to resume normal operation. Remote Sensor Setting Feature The Axiom with Diagnostics provides the capability of setting the Closed and Open sensors remotely from the Control System or from the AS-Interface Gateway/Master. 1. AS-Interface communications are required in order to remotely set the sensors. The unit must be addressed and correctly configured to be recognized by the Control System or the AS-Interface Gateway/Master. 2. With the valve/actuator in the closed position, set Output Bit 1 (DO 0) to “1” for at least two seconds. This will set the Closed sensor to that valve/actuator position. Set Output Bit 1 (DO 0) back to “0” 3. With the valve/actuator in the open position, set Output Bit 2 (DO 1) to “1” for at least two seconds. This will set the Open sensor to that valve/actuator position. Set Output Bit 2 (DO 1) back to “0”. The “Wink” Feature The Axiom with Diagnostics provides the capability of setting the CLOSED and OPEN LED’s to simultaneously flash or “wink” . This feature aids in physically locating the unit on the network. 1. AS-Interface communications are required in order to set the “Wink” feature. The unit must be addressed and correctly configured to be recognized by the Control System or the AS-Interface Gateway/Master. 2. Set Output Bit 4 (DO 3) to “1” in the desired unit. Once the correct unit has been physically located on the network, indicated by the “winking” of the CLOSED and OPEN LED’s, set Output Bit 4 (DO 3) back to “0”. Performing this function will not change the Closed and Open sensor set points. 7 AMI 70 en 4 9 EXPLODED VIEW ITEM DESCRIPTION QTY 1 Axiom Cover Screws 4 2 Axiom Cover 1 3 Axiom Body Screws 4 4 Axiom Body 1 5 DA/SR Plug 1 6 Visual Indicator Cover 1 7 Visual Indicator Drum 1 8 Visual Indicator Drum Coupler 1 1 2 Item# 9 thru 14 are provided with the mounting kit. Mounting kits are sold separately 9 Visual Indicator Drum Retaining Screw 1 10 Visual Indicator Drive Block 1 11 Air Manifold Plate Mounting Screws 4 12 13 14 Air Manifold Plate Orifice O-rings Visual Indicator Cover O-ring Air Manifold Plate 3 1 1 3 4 DA/SR Plug Placement PLUG FOR SR PLUG FOR DA 6 7 8 6 5 9 8 7 RS ROF GULP AD ROF GULP Bottom side of Axiom Body 6 8 Detail - A 7 10 Visual Indicator Indexing SE V.I. INDEX D 7 OPEN 6 8 V.I. INDEX Detail - B 11 13 12 14 CL O 10 5 7 AMI 70 en DIMENSIONS E2 E3 S1 7 AMI 70 en 11 SET OPEN Setup Instructions: Operate Actuator to Closed Position and Push SET CLOSED for 2 seconds. Operate Actuator to Open Position and Push SET OPEN for 2 seconds (8) (5) Sol2 Pwr IN (4) Open NO Sol2 Pwr IN (3) Sol1 Pwr IN (1) Sol1 Pwr IN (2) (8) Closed C (6) Closed NO (7) Open C Open NO (5) Sol Pwr IN (4) Sol Pwr IN (3) (1) Sol Out - CLOSED SST SST Sol Out + (2) OPEN SET CLOSED SOLENOID POWER CLOSED Sol2 Out + (9) Setup Instructions: Operate Actuator to Closed Position and Push SET CLOSED for 2 seconds. Operate Actuator to Open Position and Push SET OPEN for 2 seconds Sol2 Out - (10) SET CLOSED Sol1 Out - (12) OPEN Sol1 Out + (11) SET OPEN Closed C Type AMI33 Closed NO (7) 6.1 (6) WIRING DIAGRAMS Open C 6 6-PIN MICRO-CONNECTOR 5-PIN MICRO-CONNECTOR 4 4 3 5 5 1 2 PIN SIGNAL 1 2 3 4 OPEN/CLOSED C CLOSED NO OPEN NO SOL PWR IN + 5 SOL PWR IN - MALE (PINS) 5-PIN MINI-CONNECTOR 3 4 3 6 1 2 MALE (PINS) 6-PIN MINI-CONNECTOR 3 2 4 2 5 1 PIN SIGNAL 1 OPEN/CLOSED C 2 CLOSED NO 3 OPEN NO 4 SOL1&SOL2 PWR IN 5 SOL1 PWR IN 6 SOL2 PWR IN 6 5 1 MALE (PINS) Type AMI44 SET OPEN (5) (6) (7) (8) Open - Closed + Closed - Setup Instructions: Operate Actuator to Closed Position and Push SET CLOSED for 2 seconds. Operate Actuator to Open Position and Push SET OPEN for 2 seconds Open + (8) Closed - Sol2 Pwr IN + (3) (7) Closed + 6-PIN MICRO-CONNECTOR Sol2 Pwr IN - (4) (6) Open - Sol1 Pwr IN + (1) (5) Open + Sol1 Pwr IN - (2) (4) Sol Pwr - (2) Sol Pwr + (3) (1) CLOSED NAMUR NAMUR Sol + OPEN SET CLOSED SOLENOID POWER CLOSED Sol2 Out + (9) Setup Instructions: Operate Actuator to Closed Position and Push SET CLOSED for 2 seconds. Operate Actuator to Open Position and Push SET OPEN for 2 seconds Sol2 Out - (10) SET CLOSED Sol1 Out - (12) OPEN Sol1 Out + (11) SET OPEN Sol - 6.2 MALE (PINS) 8-PIN MICRO-CONNECTOR 5 4 4 6 8 5 3 6 1 2 MALE (PINS) 6-PIN MINI-CONNECTOR 3 7 PIN SIGNAL 1 OPEN (+) 2 OPEN (-) 3 3 SIGNAL 1 Sol1 Pwr IN (+) 2 Sol1 Pwr IN (-) 3 CLOSED (+) SOL PWR (+) 4 CLOSED (-) 4 CLOSED (+) 5 Sol2 Pwr IN (+) 5 CLOSED (-) 6 SOL PWR (-) 1 2 MALE (PINS) 8-PIN MINI-CONNECTOR 8 4 2 5 5 1 6 4 3 2 6 1 7 MALE (PINS) PIN MALE (PINS) 6 Sol2 Pwr IN (-) 7 OPEN (+) 8 OPEN (-) 12 6.3 7 AMI 70 en Type AMI96 4-PIN MICRO-CONNECTOR SET OPEN Setup Instructions: Operate Actuator to Closed Position and Push SET CLOSED for 2 seconds. Operate Actuator to Open Position and Push SET OPEN for 2 seconds OPEN SET CLOSED 4 1 2 PIN MALE (PINS) SOLENOID POWER CLOSED 3 4-PIN MINI-CONNECTOR (10) (8) (9) 3 2 ASI+ 2 Not Used 3 ASI- 4 Not Used 4 ASI + Aux IN + MALE (PINS) ASI - Aux IN 1 - (7) Aux IN 2 - (6) 3 wire RTN (5) (3) (4) OUT 2 + (2) OUT 2 - OUT 1 - 6.4 OUT 1 + (1) 1 SIGNAL 1 Type AMI96_D SET OPEN Setup Instructions: Operate Actuator to Closed Position and Push SET CLOSED for 2 seconds. OPEN 4-PIN MICRO-CONNECTOR 4 3 Operate Actuator to Open Position and Push SET OPEN for 2 seconds CLOSED SET CLOSED SOLENOID POWER 1 2 PIN MALE (PINS) Diagnostics: Blinking LED indicates problem LOW AIR SUPPLY PRESSURE STUCK PROCESS VALVE/ACTUATOR 1 (4) ASI - 3 2 Not Used 3 ASI- 4 Not Used PIN SIGNAL 4 MALE (PINS) ASI + (3) 4-PIN MINI-CONNECTOR ASI+ 2 Type AMI97 4-PIN MICRO-CONNECTOR SET OPEN OPEN SET CLOSED Setup Instructions: Operate Actuator to Closed Position and Push SET CLOSED for 2 seconds. Operate Actuator to Open Position and Push SET OPEN for 2 seconds 4 1 2 MALE (PINS) SOLENOID POWER CLOSED 3 4-PIN MINI-CONNECTOR (9) (10) 3 2 4 ASI + MALE (PINS) ASI - (8) Aux IN + Aux IN 1 - (7) Aux IN 2 - (6) (4) 3 wire RTN (5) Not Used (3) (2) OUT 1 + Not Used (1) 1 OUT 1 - 6.5 SOL OUT+ (2) STUCK SPOOL/PILOT SOL OUT- (1) BAD SOLENOID COIL SIGNAL 1 1 ASI+ 2 Not Used 3 ASI- 4 Not Used 7 AMI 70 en 6.6 13 Type AMI93 4-PIN MICRO-CONNECTOR SET OPEN OPEN SET CLOSED Setup Instructions: Operate Actuator to Closed Position and Push SET CLOSED for 2 seconds. Operate Actuator to Open Position and Push SET OPEN for 2 seconds 4 1 2 PIN MALE (PINS) SOLENOID POWER CLOSED 3 4-PIN MINI-CONNECTOR (7) (8) 2 FB+ 3 Not Used 4 Not Used PIN SIGNAL 4 FB + MALE (PINS) FB - (6) (5) OUT 1 - OUT 1 + (3) (4) OUT 2 + OUT 2 - 3 FB- 2 Type AMI94 4-PIN MICRO-CONNECTOR SET OPEN OPEN Setup Instructions: Operate Actuator to Closed Position and Push SET CLOSED for 2 seconds. Operate Actuator to Open Position and Push SET OPEN for 2 seconds 4 3 1 2 MALE (PINS) SET CLOSED SOLENOID POWER CLOSED 4-PIN MINI-CONNECTOR (10) (9) 3 FB + 2 FB - (7) 24 VDC + (8) (6) OUT 1 + 24 VDC - (5) OUT 1 - (4) OUT 2 + (3) OUT 2 - SIM JMPR (2) 1 SIM JMPR (1) 6.7 SIM JMPR (2) SIM JMPR (1) 1 SIGNAL 1 4 MALE (PINS) 1 FB- 2 FB+ 3 24VDC+ 4 24VDC- 14 7 AMI 70 en 6.8 Installation Diagram for Explosive Atmospheres for Europe AMI44_E___* models approved for Intrinsic Safety Installations: (Ex ia IIC T5) * Any Conduit Entry/Connector option and Visual Indicator option is approved. HAZARDOUS (CLASSIFIED) LOCATION 2 1 Ex ia IIC T5 4 7 Individual Sensor and solenoid coil wiring to Axiom Models AMI44____ Intrinsic Safety Barriers (Associated Apparatus) 5 NON-HAZARDOUS (SAFE AREA) LOCATION 6 3 Control Equipment Solenoid Coil Barrier Solenoid Coil Barrier 10 Enclosure Top Sensor Namur Barrier Bottom Sensor Namur Barrier (8) Closed (7) Closed + (6) Open (5) Open + (4) Sol2 Pwr (3) Sol2 Pwr + (2) Sol1 Pwr (1) Sol1 Pwr + AMI44 Terminal Identifiers (If using quick connectors, see 6.2 for pin-out) 8 Shields 9 Intrinsically Safe Ground INSTALLATION NOTES for Intrinsic Safety Installations: (Ex ia IIC T5) Entity Parameters: AMI44_____: Ui = 16 Vdc; Ii = 25 mA ; Ci = 4.4 nF; Li = 0.0 mH; Pi = 1.0 W IS Coil : Ui = 28 Vdc; Ii = 120 mA ; Ci = 00 nF; Li = 0.0 mH; Pi = 1.0 W 1 2 3 4 5 6 7 8 9 10 1. Voc or Vt < Ui, Isc or It < Ii, Ca > Ci + Ccable, La > Li + Lcable. 2. Dust-tight conduit seal must be used when installed in Zone 20, Zone 21, and Zone 22 environments or where Ingress Protection of IP67 is required. 3. Control equipment connected to barrier must not use or generate more than 250 Vrms or Vdc. 4. Installation should be in accordance with appropriate local code or practice. 5. The configuration of associated apparatus for each sensor wiring pair or solenoid wiring pair must be approved. 6. Associated apparatus manufacturer's installation drawing must be followed when installing this equipment. 7. To maintain intrinsic safety, wiring associated with each sensor or solenoid coil wiring must be run in separate cables or separate shields connected to intrinsically safe (associated apparatus) ground. 8. Conduit Grounding - Upon installation verify electrical continuity between conduit and ground terminal. 9. Resistance between Intrinsic Safe Ground and earth ground must be less than one ohm. 10. Parts of the enclosure are non-conducting and may generate an ignition-capable level of electrostatic charge under certain extreme conditions. The user should ensure that the equipment is not installed in location where it may be subjected to external conditions (such as high-pressure steam) which might cause a build-up of electrostatic charge on non-conducting surfaces. Additionally, cleaning of the equipment should only be done with a damp cloth. 11. Substitution of components may impair hazardous location safety. Specific Conditions of Use: 1. When used within a Zone 0 location, the aluminum enclosure shall be installed in such manner as to prevent the possibility of sparks resulting from friction or impact. 2. To prevent the risk of electrostatic sparking, the equipment enclosure shall be cleaned only with a damp cloth. 7 AMI 70 en 6.9 15 Intrinsic Safety Hazardous Location Installation Diagram AMI44_E___* models approved for Intrinsic Safety Installations: IS Class I,II, and III; Division 1&2; Gas Groups A,B,C,D,E,F,G * Any Conduit Entry/Connector option and Visual Indicator option is approved. HAZARDOUS (CLASSIFIED) LOCATION 2 4 1 IS; Cl I,II,III Div 1&2, Groups A,B,C,D,E,F,G 7 Individual Sensor and solenoid coil wiring to Axiom Models AMI44____ Intrinsic Safety Barriers (Associated Apparatus) 5 NON-HAZARDOUS (SAFE AREA) LOCATION 6 3 Control Equipment Solenoid Coil Barrier Solenoid Coil Barrier 10 Enclosure Top Sensor Namur Barrier Bottom Sensor Namur Barrier (8) Closed (7) Closed + (6) Open (5) Open + (4) Sol2 Pwr (3) Sol2 Pwr + (2) Sol1 Pwr (1) Sol1 Pwr + AMI44 Terminal Identifiers (If using quick connectors, see 6.2 for pin-out) 8 Shields 9 Intrinsically Safe Ground INSTALLATION NOTES for Intrinsic Safety Installations: Entity Parameters: AMI44_____: Ui (Vmax) = 16 Vdc; Ii (Imax) = 25 mA ; Ci = 4.4 nF; Li = 0.0 mH; Pi = 1.0 W IS Coil : Ui (Vmax) = 28 Vdc; Ii (Imax) = 120 mA ; Ci = 00 nF; Li = 0.0 mH; Pi = 1.0 W 1 2 3 4 5 6 7 8 9 10 1. Voc or Vt < Ui (Vmax), Isc or It < Ii (Imax), Ca > Ci + Ccable, La > Li + Lcable. 2. Dust-tight conduit seal must be used when installed in Class II and Class III environments or where Ingress Protection of IP67 is required. 3. Control equipment connected to barrier must not use or generate more than 250 Vrms or Vdc. 4. Installation should be in accordance with ANSI/ISA RPA12.6.01 "Installation of Intrinsically Safe Systems for Hazardous (Classified) Locations" and the National Electrical Code (ANSI/NFPA 70) or in accordance with the Canadian Electric Code. 5. The configuration of associated apparatus for each sensor wiring pair or solenoid wiring pair must be approved. 6. Associated apparatus manufacturer's installation drawing must be followed when installing this equipment. 7. To maintain intrinsic safety, wiring associated with each sensor or solenoid coil wiring must be run in separate cables or separate shields connected to intrinsically safe (associated apparatus) ground. 8. Conduit Grounding - Upon installation verify electrical continuity between conduit and ground terminal. 9. Resistance between Intrinsic Safe Ground and earth ground must be less than one ohm. 10. Parts of the enclosure are non-conducting and may generate an ignition-capable level of electrostatic charge under certain extreme conditions. The user should ensure that the equipment is not installed in location where it may be subjected to external conditions (such as high-pressure steam) which might cause a build-up of electrostatic charge on non-conducting surfaces. Additionally, cleaning of the equipment should only be done with a damp cloth. 11. Substitution of components may impair hazardous location safety. 16 7 AMI 70 en 6.10 Non-Incendive Field Wiring Apparatus Installation Drawing AMI96_____* models approved as Non-Incendive Field Wiring Apparatus: * Any Conduit/Connector option and Visual Indicator option is approved. HAZARDOUS (CLASSIFIED) LOCATION NON-HAZARDOUS (SAFE AREA) LOCATION Nonincendive Field Wiring Apparatus NI; Cl I,II,III Div 2 Groups A,B,C,D,F,G 1 2 4 Power Limiting Associated Apparatus 6 Control Equipment 3 5 AMI96__ Enclosure ASI + OUT 1 (1) OUT 1 + (2) OUT 2 (3) OUT 2 + (4) 3 wire RTN (5) Aux IN2 - (6) Aux IN1 - (7) Aux IN + (8) ASI (9) ASI + (10) ASI - AMI96 Terminal Identifiers Quick Connector Pin-out indicated below (if used) 4-PIN MINI-CONNECTOR 1 3 2 4 4-PIN MICRO-CONNECTOR PIN SIGNAL 1 ASI+ 2 Not Used 3 ASI- 4 Not Used 4 1 MALE (PINS) INSTALLATION NOTES: Entity Parameters: AMI96_____: Ui = 37 Vdc; 1 2 3 4 5 6 3 2 PIN SIGNAL 1 ASI+ 2 Not Used 3 ASI- 4 Not Used MALE (PINS) Ii = 150 mA ; Ci = 0.0 nF; Li = 0.0 mH; Pi = 3.0 W 1. Installation shall be in accordance with ANSI/ISA RPA12.6.01, ANSI/NFPA 70, and the National Electrical Code. 2. Dust-tight conduit seal must be used when installed in Class II and Class III environments or where Ingress Protection of IP67 is required. 3. Control equipment must be FM approved to supply power in Class I, Division 2 Areas. 4. Power Limiting Associated Apparatus must satisfy the conditions: Voc or Vt < Vi, Isc or It < Ii, Ca > Ci + Ccable, La > Li + Lcable of the AMI96_______ Entity Parameters 5. Manufacturer's associated non-incendive field wiring apparatus installation drawing must be followed when installing this equipment. 6. Parts of the enclosure are non-conducting and may generate an ignition-capable level of electrostatic charge under certain extreme conditions. The user should ensure that the equipment is not installed in location where it may be subjected to external conditions (such as high-pressure steam) which might cause a build-up of electrostatic charge on non-conducting surfaces. Additionally, cleaning of the equipment should only be done with a damp cloth. 7. Substitution of components may impair hazardous location safety. 7 AMI 70 en 6.11 17 Non-Incendive Safety Hazardous Location Installation Diagram AMI97_____* models approved as Non-Incendive Field Wiring Apparatus: * Any Conduit/Connector option and Visual Indicator option is approved. HAZARDOUS (CLASSIFIED) LOCATION NON-HAZARDOUS (SAFE AREA) LOCATION Nonincendive Field Wiring Apparatus NI; Cl I,II,III Div 2 Groups A,B,C,D,F,G 1 2 4 Power Limiting Associated Apparatus Control Equipment 3 5 AMI97__ Enclosure 6 ASI + OUT 1 (1) OUT 1 + (2) Not Used (3) Not Used (4) 3 wire RTN (5) Aux IN2 - (6) Aux IN1 - (7) Aux IN + (8) ASI (9) ASI + (10) ASI - AMI97 Terminal Identifiers Quick Connector Pin-out indicated below (if used) 4-PIN MINI-CONNECTOR 1 3 2 4 4-PIN MICRO-CONNECTOR PIN SIGNAL 1 ASI+ 2 Not Used 3 ASI- 4 Not Used 1 2 3 4 5 6 3 1 MALE (PINS) INSTALLATION NOTES: Entity Parameters: AMI97_____: Ui = 37 Vdc; PIN 4 2 SIGNAL 1 ASI+ 2 Not Used 3 ASI- 4 Not Used MALE (PINS) Ii = 150 mA ; Ci = 0.0 nF; Li = 0.0 mH; Pi = 3.0 W 1. Installation shall be in accordance with ANSI/ISA RPA12.6.01, ANSI/NFPA 70, and the National Electrical Code. 2. Dust-tight conduit seal must be used when installed in Class II and Class III environments or where Ingress Protection of IP67 is required. 3. Control equipment must be FM approved to supply power in Class I, Division 2 Areas. 4. Power Limiting Associated Apparatus must satisfy the conditions: Voc or Vt < Vi, Isc or It < Ii, Ca > Ci + Ccable, La > Li + Lcable of the AMI97_______ Entity Parameters 5. Manufacturer's associated non-incendive field wiring apparatus installation drawing must be followed when installing this equipment. 6. Parts of the enclosure are non-conducting and may generate an ignition-capable level of electrostatic charge under certain extreme conditions. The user should ensure that the equipment is not installed in location where it may be subjected to external conditions (such as high-pressure steam) which might cause a build-up of electrostatic charge on non-conducting surfaces. Additionally, cleaning of the equipment should only be done with a damp cloth. 7. Substitution of components may impair hazardous location safety. 18 7 AMI 70 en 6.12 Intrinsic Field Wiring Apparatus Installation Drawing AMI93_A___* models approved for Intrinsic Safety (FISCO) Installations: IS (FISCO) Class I,II, and III; Division 1&2; Gas Groups A,B,C,D,E,F,G * Any Conduit/Connector option and Visual Indicator option is approved. HAZARDOUS (CLASSIFIED) LOCATION 1 2 SIM JMPR (1) SIM JMPR (2) OUT 2 - (3) OUT 2 + (4) OUT 1 - (5) OUT 1 + (6) FB (7) FB + (8) AMI93 Terminal Identifiers FISCO Approved Termination NON-HAZARDOUS (SAFE AREA) LOCATION IS (FISCO) Cl I,II,III Div 1, Groups A,B,C,D,E,F,G FISCO Approved Fieldbus Device “n” Axiom Enclosure 6 3 FISCO Approved Control Equipment 4 5 FISCO Approved Fieldbus Device #2 FB + FB Quick Connector Pin-out indicated below (if used) 4-PIN MICRO-CONNECTOR 4 3 1 2 MALE (PINS) 4-PIN MINI-CONNECTOR PIN SIGNAL 1 FB- 2 FB+ 3 Not Used 4 Not Used PIN 1 4 2 3 SIGNAL 1 FB- 2 FB+ 3 Not Used 4 Not Used MALE (PINS) INSTALLATION NOTES: AMI93__ Entity Parameters (FISCO): Ui(Vmax) = 30Vdc; Ii(Imax) = 380mA ; Ci = 0.0nF; Li = 0.0mH; Pi = 5.32 W Outputs: Uo = 7.14Vdc; Io = 47mA; Po = 0.1W 1 2 3 4 5 6 1. Installation shall be in accordance with ANSI/ISA RPA12.6.01, ANSI/NFPA 70, and the National Electrical Code or in accordance with the Canadian Electric Code. 2. Dust-tight conduit seal must be used when installed in Class II and Class III environments or where Ingress Protection of IP67 is required. 3. Control equipment must be FISCO Approved Associated Apparatus. 4. Control equipment connected to FISCO barrier must not use or generate more than 250Vrms or Vdc. 5. Resistance between FISCO Intrinsically Safe Ground and earth ground must be less than 1.0 Ohm. 6. Parts of the enclosure are non-conducting and may generate an ignition-capable level of electrostatic charge under certain extreme conditions. The user should ensure that the equipment is not installed in location where it may be subjected to external conditions (such as high-pressure steam) which might cause a build-up of electrostatic charge on non-conducting surfaces. Additionally, cleaning of the equipment should only be done with a damp cloth. 7. Substitution of components may impair hazardous location safety. 8. Approval Agency controlled Installation Diagram. No revision to diagram allowed without prior Factory Mutual or Approval Agency authority. 7 AMI 70 en 7 19 TYPE CODE Valve controller, Neles Axiom 1. AMI 1. AMI 2. 33 44 93 94 96 97 3. 1 3 2 4 4. H E D A 2. 33 3. 1 4. H 5. V PRODUCT GROUP Neles Axiom, On/off valve controller with proximity switches. SENSOR Sensor Module SST Sensor, 2 switches, NO, 16 - 125 V DC / 24 - 125 V AC. Applicable to 4. sign "H". Namur Sensor, 2 switches, 7 - 24 V DC; > 2.1 mA; < 1.0 mA, DIN EN 60947-5-6. Applicable to 4. sign "E". Valve Communication Terminals (VCT) FOUNDATION fieldbus, bus powered, 2 switches. Physical layer according to IEC 61158-2. Applicable to 4. sign "A". FOUNDATION fieldbus, externally powered, 2 switches. Physical layer according to IEC 61158-2. Applicable to 4. sign "D" AS-Interface, 2 switches. Applicable to 3. sign "1", "3" or "5" with 7. sign "S" or "D". Applicable to 3. sign "2", "4" or "6" with 7. sign "S". Applicable to 4. sign "D" AS-Interface, extended addressing, 2 switches. Applicable to 3. sign "1", "3" or "5". Applicable to 4. sign "D". PNEUMATIC FUNCTIONALITY Sensor Module No manual override. Manual override Latching manual override Sensor Module No manual override. Not applicable to 7. sign "D" Manual override. Not applicable to 7. sign "D". PNEUMATIC VALVE Solenoid Temperature range -18° to +50 °C 24 V DC / 120 V AC, 0.6 W. Applicable to 2. sign "33". 12 V DC, 0.5 W, intrinsically safe. Applicable to 2. sign "44". 24 V DC, 0.5 W. Applicable to 2. sign "94", "96" or "97". Piezo Temperature range -10° to +60 °C 6.5 V DC, 2 mA, intrinsically safe. Applicable to 2. sign "93". 6. 05 7. S 5. V L 6. 02 05 7. S D 8. R 9. N *) – ENCLOSURE Standard IP67 enclosure ATEX certifications: II 1 G Ex ia IIC T5, Ta = -40° to +80 °C Sensor: Ui = 16 V, Ii = 25 mA, Pi = 1.0 W, Ci = 4.4 nF, Li = 0 mH Solenoid: Ui = 28 V, Ii = 120 mA, Pi = 1.0 W, Ci = 0 nF, Li = 0 mH Applicable to 2. sign "44". II 3 G Ex nA nC IIC T5, Ta = -40° to +70 °C AMI33_: U ≤ 75 V DC; AMI44_: U ≤ 24 V DC; AMI93_, AMI94_: U ≤ 32 V DC; AMI96_, AMI97_: U ≤ 31.6 V DC. Applicable to all sensor options 2. sign. INMETRO certification: BR-EX nAnC IIC T5, Ta = -40° to +70 °C Applicable to 2. sign "33", "44" and "96". CONNECTIONS 2 pcs. 1/2" NPT 2 pcs. M20x1.5 DIAGNOSTICS CAPABILITIES Standard, without diagnostics. Diagnostics, with Local LED indicators and diagnostic messages via AS-Interface. Applicable to 2. sign "96". Applicable to 3. sign "1", "3" or "5". 8. R INDICATOR Red-Closed Green-Open. 9. N Neles 10. T 10. T LABEL OPTION Extended temperature range. Temperature range -40° to +80 °C Not applicable to 2. sign "93" and 3. sign "A". 20 7 AMI 70 en Metso Automation Inc. Europe, Levytie 6, P.O. Box 310, 00811 Helsinki, Finland. Tel. +358 20 483 150. Fax +358 20 483 151 North America, 44 Bowditch Drive, P.O. Box 8044, Shrewsbury, MA 01545, USA. Tel. +1 508 852 0200. Fax +1 508 852 8172 Latin America, Av. Independéncia, 2500-Iporanga, 18087-101, Sorocaba-São Paulo, Brazil. Tel. +55 15 3235 9700. Fax +55 15 3235 9748/49 Asia Pacific, 238A Thomson Road, #25-09 Novena Square Tower A, 307684 Singapore. Tel. +65 6511 1011. Fax +65 6250 0830 China, 19/F, the Exchange Beijing, No. 118, Jianguo Lu Yi, Chaoyang Dist, 100022 Beijing, China. Tel. +86-10-6566-6600. Fax +86-10-6566-2575 Middle East, Roundabout 8, Unit AB-07, P.O. Box 17175, Jebel Ali Freezone, Dubai, United Arab Emirates. Tel. +971 4 883 6974. Fax +971 4 883 6836 www.metso.com/automation