Copeland Electrical Handbook

Transcription

Copeland Electrical Handbook
For more Copeland literature please visit
www.HVACRinfo.com
Electrical Handbook
2008-2009 Edition
Note: This CD requires Adobe Acrobat Reader 7.0 or higher in order to display and search correctly.
You should see a search panel at right, and links should have a simple underline rather than
a box. If you are using an earlier version of Acrobat Reader, go to http://www.adobe.com/products/
acrobat/readstep2.html for a free download of the latest version.
FOREWORD
The progress of Emerson Climate Technologies, Inc., as well as that of refrigeration and air conditioning in general, has
been greatly aided by good field service. Everyone at Emerson Climate Technologies, Inc. recognizes and appreciates
the important contribution of the service engineer upon whose talents we and all refrigeration equipment manufacturers
depend to assure complete user satisfaction.
This booklet covers in detail electrical service information on welded compressors, Copelametic®, Copeland Scroll®, and
Copeland Screw™ compressors. In addition, electrical service information is provided for Copeland® Condensing Units.
The booklet is designed to assist the service engineer to better understand the function of such items as motors, relays,
starting capacitors, running capacitors and motor protectors. In addition to electrical information, a brief section dealing
with diagnosing the causes of compressor failures has been added.
TABLE OF CONTENTS
Motors and Electrical Components ..................................................................... A
• Single and Three Phase Motors
• Capacitors
• Measuring Motor Temperature
• Measuring Winding Resistance
Electrical Motor Protection ................................................................................... B
Fuse Selection ....................................................................................................... C
Compressor Nomenclature .................................................................................. D
• Welded Compressors
• HFC Welded Compressors
• A-Line
• CRKQ, CIKQ
• CR7, CR6, CRKF, CS, CF
• Coplematic®
• Copeland Discus™
• Refrigeration Copeland Scroll®
• A/C Copeland Scroll®
• Condensing Unit (All models except M-Line)
• M-Line Condensing Unit
• Copeland Screw™
Electrical Component Nomenclature and Data .................................................. E
• Potential Relay Nomenclature
• G.E. Numbering System
• Potential Relay Data
• Current Relay Data
• Start Capacitor Data
• Run Capacitor Data
Compressor Electrical Data.................................................................................. F
• A-Line .............................................................................................................. FA
• Welded Compressors .................................................................................... FB
• Copelametic® Air-Cooled .............................................................................. FC
• Copelametic® Small Refrigerant-Cooled ..................................................... FD
• Copelametic® Large Refrigerant-Cooled ..................................................... FE
• Copeland Scroll® ........................................................................................... FF
• Copeland Screw™ .......................................................................................... FG
Wiring Diagrams .................................................................................................... G
Electrical Troubleshooting Procedures............................................................... H
Identifying Compressors Failures ....................................................................... I
SECTION A
MOTORS AND ELECTRICAL COMPONENTS
TOPICS
Single Phase Motors ...................................................A2
Start Relays .................................................................A3
Start Capacitors ...........................................................A5
Run Capacitors ............................................................A7
Parallel and Series Capacitors ....................................A9
Measuring Motor Temperature ..................................A10
Measuring Winding Resistance ................................. A11
Resistance Measurements for
Single Voltage Motors................................................A13
Resistance Measurements
for Dual Voltage Motors .............................................A15
Section A.indd 1
2/6/2008 10:46:30 AM
SINGLE PHASE MOTORS
There are four basic types of single phase motors used
in hermetic and semi-hermetic compressors:
• Split Phase or Resistance start - Induction Run
(RSIR)
• Capacitor Start - Induction Run (CSIR)
• Capacitor Start - Capacitor Run (CSCR)
• Permanent Split Capacitor (PSC)
• Schematic diagrams of each type are shown in
Figures 1,2,3 and 6
Figure 1
A2
Section A.indd 2
2/6/2008 10:46:41 AM
START RELAYS
Current and potential relays are used to actuate components that provide the torque to start single phase
motors.
Figure 2
A3
Section A.indd 3
2/6/2008 10:46:41 AM
The Current Relay
Current relays are used on small fractional horsepower
compressor motors. The current relay contacts are
normally open when de-energized. Its coil is wound with
heavy wire and is placed in series with the incoming
power line (Figure 1). The connections to the current
relay are L, M, and S. Alternate connections are 1,5, and
2. When the compressor is energized inrush currents
pass through the current relay coil, and its contacts close
and connect the start winding to the motor circuit. The
start winding is wound with a higher resistance than the
run winding. This changes its phase current with respect
to the run winding and produces the torque required for
motor starting. The relay’s contacts open when current
drops as the compressor comes up to speed, and the
start winding is disconnected from the motor circuit.
The Potential Relay
The potential (voltage sensing) relay places the start
capacitor in series with the start winding. It does so by
sensing voltage across the start winding, rather than line
current as does the current relay.
The contacts of the potential relay are normally closed
(Figures 2, and 3), and the start capacitor is connected
to the start winding as soon as power is applied to the
compressor motor. The relay’s coil senses the voltage
developed across the start winding. It is designed to pick
up, open its contacts, and disconnect the start capacitor
from the start winding, when sufficient voltage is generated. Since the voltage or back-EMF generated by the
start winding is proportional to motor speed, the relay will
open only when the motor has started and is approaching normal running speed.
A4
Section A.indd 4
2/6/2008 10:46:41 AM
Figure 3
START CAPACITORS
Start capacitors are used on compressors where system
designs require high starting torque. Start capacitors are
designed for intermittent service only and have a high
microfarad (MFD) rating. Their construction is of the
electrolytic type in order to obtain high capacitance.
All standard Copeland® start capacitors are supplied with
bleed-resistors securely attached and soldered to their
terminals as shown in Figure 4.
A5
Section A.indd 5
2/6/2008 10:46:41 AM
Figure 4
The use of capacitors without these resistors will result
in sticking relay contacts and/or erratic relay operation
especially where short cycling is likely to occur. This is
due to the start capacitor discharging through the relay
contacts as they close, following a very short running
cycle. The resistor permits the capacitor charge to bleed
down at a much faster rate, preventing arcing and overheating of the relay contacts.
The use of capacitors supplied by Emerson Climate
Technologies, Inc. is recommended. In case of an emergency exchange, a 15,000-18,000 ohm, two watt resistor
should be soldered across the terminals of each start
capacitor. Care should be taken to prevent their shorting
to the case or other nearby metallic objects.
If sticking contacts are encountered on any start relay,
the first item to check is the start capacitor resistor. If
damaged, or not provided, install a new resistor, and
clean the relay contacts or replace the relay. Suitable
resistors can be obtained from any electronic parts
wholesaler or retailer.
A6
Section A.indd 6
2/6/2008 10:46:41 AM
RUN CAPACITORS
Run capacitors are used on compressors to improve efficiency, raise the motor’s power factor, and lower noise.
Run capacitors are continuously in the operating circuit
and are normally of the metallized film type. They are
manufactured in oval (Figure 5) or round cans.
Figure 5
THE PTC START ASSIST
The PTC (Positive Temperature Coefficient) resistor is
used for applications where high starting torque is not required. The PTC resistor is connected in parallel with the
run capacitor, placing it in series with the start winding
(Figure 6). The PTC has a low resistance when it is cold.
When the motor starts, the low resistance causes a large
current to flow through the resistor. The current drawn by
the resistor is out of phase with the current drawn by the
motor windings, and this provides the torque to start. As
soon as the resistor draws current, it begins to heat, and
the positive temperature effect of the resistor causes it
to rapidly increase its resistance. By the time the motor
reaches full speed, very little current is drawn by the reA7
Section A.indd 7
2/6/2008 10:46:42 AM
sistor. Although it remains connected to the motor circuit,
it has no significance in the operation of the compressor.
Figure 6
Capacitor Voltage
The voltage rating of a capacitor indicates the highest nominal voltage at which it is designed to operate.
Use of a capacitor at voltages below its rating will do no
harm. Run capacitors must not be subject to voltages
exceeding 10 percent of the nominal rating, and start
capacitors must not be subjected to voltages exceeding
30 percent of the nominal rating.
A8
Section A.indd 8
2/6/2008 10:46:42 AM
The voltage to which a capacitor is subjected is not line
voltage, but is a much higher potential (often called back
electromotive force or back EMF) which is generated in
the start winding. On a typical 230 volt motor, the generated voltage may be as high as 400 volts and is determined by the start winding characteristics, the compressor speed, and the applied voltage.
PARALLEL AND SERIES CAPACITORS
Capacitors, either start or run, can be connected in
series or parallel to provide the desired characteristics if
the voltage and MFD are properly selected. When two
capacitors having the same MFD rating are connected
in series, the resulting total capacitance will be one half
the rated capacitance of a single capacitor. The formula
for determining capacitance (MFD) when capacitors are
connected in a series is as follows:
1 = _____+
1
1
____
____
MFDt MFD1 MFD2
For example, if a 20 MFD and a 30 MFD capacitor are
connected in series, the resultant capacitance will be:
1
1
1
____=
_____+
____
MFDt
20
30
1
3
2
1
____=
_____+
____=
____
MFDt
60
60
12
MFDt = 12MFD
A9
Section A.indd 9
2/6/2008 10:46:42 AM
The voltage rating of similar capacitors connected in
series is equal to the sum of the voltage of the two
capacitors. However, since the voltage across individual
capacitors in series will vary with the rating of the capacitor, for emergency field replacements, it is recommended
that only capacitors of like voltage and capacitance be
connected in series to avoid the possibility of damage
due to voltage beyond the capacitor limits.
When capacitors are connected in parallel, their MFD
rating is equal to the sum of the individual capacitances.
The voltage rating is equal to the lowest voltage rating of
the individual capacitors.
It is possible to use any combination of single, series,
or parallel start capacitors, with single or parallel run
capacitors (run capacitors are seldom used in series).
MEASURING MOTOR TEMPERATURE
During system engineering development or in attempting
to evaluate the ability of a compressor motor to operate
under severe conditions, it is often desirable to measure
motor temperatures under extreme conditions. In the
laboratory during compressor development, temperature measurements of this type are made by means of
thermocouples embedded in the motor windings with the
leads brought out through gasketed surfaces. In evaluating a production compressor in a system, thermocouple
readings are not usually feasible, and the only means of
checking motor temperatures is by checking resistance
values.
The resistance through the motor windings varies in a
ratio to the change in winding temperature. By establishA10
Section A.indd 10
2/6/2008 10:46:42 AM
ing a base resistance value at a given base temperature
(normally room temperature after storage for a prolonged
period without operation) any change in the temperature
of the motor windings can be calculated by determining
the change in winding resistance. The resistance method, since it reads the overall resistance of the winding, is
an average reading and does not accurately reflect the
temperature that might exist at hot spots. In some cases,
there may be hot spots that can reach temperatures of
40°F or more above the average reading so resistance
readings must be evaluated very conservatively.
Motors may be wound with either copper or aluminum
wire, and it is necessary to know the motor construction
since the resistance change varies depending on the
type of wire. The basic formula for calculating winding
temperature is as follows:
Rh (T + K) - K
Th = ___
c
Rc
Th = Temperature hot
Tc = Temperature cold
Rh = Resistance hot (ohms)
Rc = Resistance cold (ohms)
Kcopper = 390.1 for °F, 234.5 for °C
Kaluminum = 365.8 for °F, 221.0 for °C
MEASURING WINDING RESISTANCE
DISCONNECT ALL SOURCES OF POWER TO THE
COMPRESSOR BEFORE MAKING ANY RESISTANCE MEASUREMENT
A11
Section A.indd 11
2/6/2008 10:46:42 AM
Compressor Wiring Diagrams
Compressor wiring diagrams with motor winding connections and numbering are often used as a reference for
compressor motor winding resistance measurements.
Electrical Handbook wiring diagrams show the compressor motor with its windings connected for its design voltages. The compressor motor windings are also shown
unwired and labeled so that if it is necessary, individual
winding resistances can be measured and compared
to each other.
The pages of Section G of the Electrical Handbook
that are headed Copelametic Wiring Diagrams and
Welded Compressors Wiring Diagrams list applicable
wiring diagrams. They are indexed by the portion of the
Copeland® compressor model number that references:
1. Compressor Model
2. The Compressor Electrical Characteristics: the type
of motor, type of overload protection, voltage and
phase.
A typical compressor model number 4DH3R22ME-TSK
indicates a 4D Compressor Model with TSK Compressor
Electrical Characteristics (see Section D of the Electrical
Handbook for further compressor model nomenclature).
Ohmmeter Resistance Measurements.
Electrical Handbook (See Section F) pages designated
Electrical Data-Copelametic Compressors, Electrical
Data-Copeland Scroll Compressors, and Electrical
Data-Welded Compressors have columns that are
headed Winding Resistance (Ohms).
A12
Section A.indd 12
2/6/2008 10:46:42 AM
The resistances shown are compressor motor resistances measured when the motor is connected for the voltage shown in the Electrical Data column headed Volts.
Measurements must be taken with all external connections removed from the winding terminal blocks,
but winding connection jumpers (if system voltage
has been selected) inplace. Resistance measurements
should be within plus or minus 10% of the listed resistance.
The most satisfactory instrument for all winding resistance measurements is a low range digital ohmmeter
since many of the winding resistances listed are in fractions of an ohm.
MEASURING RESISTANCES OF SINGLE VOLTAGE
RANGE MOTORS (Single Phase and Three Phase)
Measurements are straightforward for single phase
and three phase compressors that can only be wired
across the line for a single voltage.
A13
Section A.indd 13
2/6/2008 10:46:42 AM
1. Single phase motors have a Start Winding, a Run
Winding, and a Common connection between them.
Therefore, the measurements are listed as: Start
Winding: “C” (Common) to “S” (Start), and Run Winding: “C” (Common) to “R” (Run). See Figure 7.
Figure 7
2. On Three phase motors having a single voltage range
the resistance measured is actually twice that of an
individual winding since the centers of 3 lead, Wye
wound motors are internally connected and cannot be
reached for measurement. See Figure 8.
A14
Section A.indd 14
2/6/2008 10:46:42 AM
Figure 8
MEASURING RESISTANCES AND ELECTRICAL
CONNECTIONS OF DUAL VOLTAGE THREE PHASE
MOTORS (Single Contactor and Part-Winding or Two
Contactor)
The resistances listed in Section F, under the column
headed WINDING RESISTANCE IN OHMS, LINE TO
LINE are the values for a one contactor, across-theline start. When a six or nine lead motor is connected
for a two contactor part winding start or across-the-line
start, the phase-to- phase ohm value will be twice (x2)
the value listed. When a nine lead motor is connected
for high voltage, 460 volts, the phase-to-phase ohm
value will be four times (x4) the listed value of the 230
volt value. If individual resistance measurements are
needed, for a nine-lead motor, disconnect all jumpers
and refer to Figure 9.
A15
Section A.indd 15
2/6/2008 10:46:42 AM
There are three individual windings (1-4, 2-5, and 3-6)
and one wye-connected winding (7-8-9). The individual
winding resistances are equal to the compressor’s 230
volt connected resistance measurement of Section F.
The wye winding value is twice the 230 volt resistance
measurement of Section F.
Figure 9
Electrical connections are made through contactors
to the compressor motor terminals. Brass jumper bars
must be connected to the motor terminals to allow one
or two contactors to be used for either across-the-line or
part-winding starts. If the windings are connected out of
phase, in any application, or if the jumper bars are not
positioned correctly, motor overheating and failure will
occur.
A16
Section A.indd 16
2/6/2008 10:46:42 AM
Six-lead motors are single voltage motors such as 200
or 460 volts. Nine-lead motors are dual voltage motors
such as 208-230/460 volts.
Figure 10 shows the electrical connections for a six lead
200 or 460 volt single contactor application.
Figure 10
Figure 11 shows the electrical connections for a six lead
200 or 460 volt two contactor across-the-line or partwinding start application. The dotted lines mean power
connections are made electrically rather than by jumper
bars.
Figure 11
A17
Section A.indd 17
2/6/2008 10:46:43 AM
Figure 12
Figure 12 (top) shows the electrical connections for a
nine lead, 208-230/460 volt, single contactor application when connected to 208 or 230 volts. It also shows
(bottom) the electrical connections for a two contactor
application when connected to 208 or 230 volts for an
across-the-line or part- winding start.
A18
Section A.indd 18
2/6/2008 10:46:43 AM
Figure 13
Figure 13 shows the electrical connections for a ninelead 208-230/460 volt single contactor application when
connected to 460 volts.
Part-winding starts require a time delay relay. The time
delay relay used in a part-winding start application, for
either six- or nine-lead motors, must have a one second
A19
Section A.indd 19
2/6/2008 10:46:43 AM
delay and must be used between the pull in of the first
and second contactors. Part-winding contactors must be
sized based on the compressor motor Rated Load Amps
(RLA) and the Part Winding Start, Locked Rotor Amp
(LRA) rating. See Section F.
Measurements Using The Megohmeter or “MEGGER”
When using a megohmeter to evaluate the motor
insulation of compressors, it is important to understand
that they are not intended to be used for a single reading. They were developed to establish a trend. In other
words, “meggers” are best used as part of a regular
maintenance program where periodic readings can be
recorded and a long term insulation resistance trend
established.
There are many factors that affect megohm readings
including contaminated refrigerant, oil level, and current leakage through electrical fusites or terminal plates.
Before making a measurement, all external wiring should
be removed, and all electrical terminal bolts cleaned and
torqued to specifications.
Measurements Using The High Potential Or “Hi-Pot”
Tester
Ohmmeter readings usually determine if a motor is
shorted or open, but a motor that has passed ohmmeter
resistance checks may still have repeated overload or
short circuit protector trips.
The motor may have a weakened winding that shorts
to ground when the compressor is called on to run.
The winding breakdown can be caused because of the
system voltage applied to it, heat build up, or mechaniA20
Section A.indd 20
2/6/2008 10:46:43 AM
cal stresses. It may also have a terminal board that has
developed an insulation breakdown from a terminal to
ground or from a terminal to another terminal.
A “Hi-Pot” tester can be used in conjunction with an
ohmmeter to check for insulation failure on both welded
compressors and Copelametic compressors. The terminal board check can only be made on Copelametic
compressors.
A “Hi-Pot” tester develops a high voltage, low current
power source and is used to check for an insulation
breakdown that the ohmmeter with its low voltage
power source may miss. It measures winding insulation
resistance to ground and (where applicable) terminal
board resistance from terminal to ground and from terminal to terminal. To measure winding insulation resistance, all wiring is removed from the motor winding
terminals. To measure terminal board resistance, all
wiring is removed from the terminal board.
The “Hi-Pot tester” should never be:
1. Operated alone or by an inexperienced service person.
2. Set at a voltage of more than twice the compressor
operating voltage plus 1000 volts.
3. Be set for more than 5 milliamps without consulting
Emerson Climate Technologies, Inc.
4. Applied for more than the time it takes to obtain a
reading (no more than a few seconds).
5. Used as a phase-to-phase winding check.
6. Used on any other part of the compressor.
7. Used when the compressor (system) is in a vacuum.
A21
Section A.indd 21
2/6/2008 10:46:43 AM
SECTION B
ELECTRONIC MOTOR PROTECTION
Scroll Compressor Applications
All Emerson Climate Technologies, Inc. Electronic Motor
Protectors are manufactured by Kriwan Industries and
Texas Instruments.
Scroll Compressor Applications
In all applications using Copeland Scroll® compressors,
each protector monitors motor temperature, supply
power voltage.
In all applications, utilizing the Kriwan Module, the motor
temperature is monitored using 4 positive temperature
coefficient sensors (PTC) wired in series. Four sensors
are embedded in the motor and one is located inside
the scroll set and is used to monitor the discharge gas
temperature. The sensors have a positive temperature
coefficient, and their resistance increases as the internal
temperature of the compressor motor rises. The control
module will compare the sensor resistance to a predetermined safe level; and if the total sensor resistance is too
high, the module control contact opens and breaks the
circuit for the contactor coil control voltage, which then
opens the contactor and removes line voltage from the
compressor. After a trip, when the motor has cooled to
a level that allows for the sensor resistances to return to
safe levels, the module will reset and close the control
contacts, which will allow the motor to restart.
All motor protector modules monitor power supplied to
the module and will trip if the power supplied to T1-T2
terminals are too low.
B1
Section B.indd 1
2/6/2008 10:48:20 AM
In refrigeration applications using scroll compressors,
each protector additionally monitors 3 phase incoming power phase rotation and phase loss. The module
is continuously monitoring the phases by checking the
phase sequencing. If the phase drops below a level that
is detectable by the electronics, the module will detect a
phase loss and will trip. The module monitors the phase
angle differences between the phases.
The supply voltage can be 24VDC, 24VAC or
120/240VAC depending on the model of motor protector
module. Refer to AE Bulletin AE 4-1302 and AE 4-1318
for specifications.
Semi-Hermetic Compressor Applications
In all applications using Semi-Hermetic compressors,
each protector monitors motor temperature, supply
power voltage.
Each protector consists of three temperature sensors
(embedded in the compressor motor windings) connected to an electronic control module.
The sensors have a positive temperature coefficient,
and their resistance increases as the internal temperature of the compressor motor rises. The control module
compares the sensor resistance to a predetermined
safe level; and if any sensor resistance is too high, the
module control contact opens and breaks the circuit for
the contactor coil control voltage, which then opens the
contactor and removes line voltage from the compressor.
After a trip, when the motor has cooled to a level that
allows for the sensor resistances to return to safe levels,
the module will reset and close the control contacts,
which will allow the motor to restart.
B2
Section B.indd 2
2/6/2008 10:48:26 AM
All motor protector modules monitor power supplied to
the module and will trip (open the contacts between M1
and M2) if the power supplied to L1-L2 terminals are too
low. See AE Bulletin AE 10-1264 for specifications and
wiring diagrams.
Screw Compressor Applications
In all applications using Screw compressors, each module monitors motor temperature, phase sequence control
for direction of rotation, manual reset lock-out and oil
temperature protection by PTC sensor.
In all applications, the motor temperature is monitored
using nine sensors embedded into the motor windings
which are in series and connected to the module. The
sensors have a positive temperature coefficient and
their resistance increases as the internal temperature
of the compressor rises. The control module compares
the sensor resistance to a predetermined safe level and
if any sensor resistance is too high. The module control
contact opens and breaks the circuit for the contactor
coil control voltage, which then opens the contactor and
removes line voltage from the compressor. After a trip,
the module “must” be manually reset by interruption of
the supply voltage to the module for a minimum of 2
seconds.
The other features of the module are: Direction of Rotation / Phase Sequence. When the module senses incorrect rotation or a phase sequence fault the module will
immediately shutdown the compressor and lockout. After
the correction of the fault, the module must be manually
reset.
Oil protection by the PTC sensor. An oil sensor is installed in the oil sump of the compressor and pre-wired
B3
Section B.indd 3
2/6/2008 10:48:26 AM
to the module in series with the motor windings PTC’s.
If the temperature of the oil rises to an unsafe condition,
the compressor will shutdown.
The supply voltage can be 24VDC, 24VAC, 120volt or
220volt.
Refer to AE Bulletin AE4-1322 and/or Operating Instruction 2001-71 for specifications.
Type Of Protection The Motor Protector Provides:
Motor Over Temperature and Running Over Current
• It protects the compressor by opening it’s control
contact when it senses dangerous motor over temperatures and/or over currents, which convert to over
temperatures.
Primary Single Phasing
• The protector sensors detect the sharp rise of temperature in compressor motor windings caused by
the high current resulting from a transformer primary
single phase condition.
Voltage Unbalance
• The protector protects against dangerous over-currents caused by system voltage unbalance.
Low Voltage Protection
• The electronic motor protector is designed so that it
will not allow the compressor to start with low voltage
at the protector module. When running, if the module
voltage drops below operating minimums, the module
control contact will immediately open and a two-minute delay before a restart is attempted. If any of these
occurrences result in a dangerous motor temperature
rise, the protector will immediately open it’s control
contact.
B4
Section B.indd 4
2/6/2008 10:48:26 AM
Short Cycle Protection
• Since the electronic protector has been designed
to provide a two-minute time delay before restart
after a low voltage or no voltage condition, it can be
used as protection against compressor short cycling.
For short cycling protection, the compressor control
circuit must be designed so the temperature or pressure controller turns the electronic protector power
on and off, and the protector contact control the
compressor contactor. Each time protector power is
cycled, it provides a two-minute time delay before it’s
contact closes and restarts the compressor.
Phase Loss Protection
• The scroll refrigeration module and the screw module
will sense the correct phase sequence of L1, L2 and
L3 incoming power. The three phase power must be
wired in the correct 120 degree phase sequence that
will ensure the compressor will start and operate in
the correct clockwise rotation.
When the module trips on phase loss, a delay of 5
minutes is activated and then there is a new attempt
to restart. If all three phases are present, then the
compressor will continue to run. If not the module will
lock out. There can be 10 attempts to restart before
the module will lock out and then only can be reset
by reestablishing incoming power to the module.
ELECTRONIC PROTECTOR SPECIFICATIONS:
Low Voltage Protection
24 VAC Module (Texas Instruments)
Cut-Out Voltage is 16 volts plus or minus 1.5 volts at
normal ambients.
B5
Section B.indd 5
2/6/2008 10:48:26 AM
Cut-In Voltage is 2 volts higher than cut-out.
120 VAC Module
Cut-Out Voltage is 85 volts plus or minus 4.5 volts at
normal ambients.
Cut-In Voltage is 4 volts higher than cut-out.
240 VAC Module
Cut-Out Voltage is 170 volts plus or minus 8 volts at
normal ambients. Cut-In Voltage is 4 volts higher
than cut-out.
For all Modules, the low Voltage Response Delay is
.2 seconds plus or minus .15 seconds.
Off Cycle Timer
120 seconds plus or minus 15 percent at normal
ambients.
Contact Rating
The TI (15AA) and the Kriwan (INT369) have a
contact rating of 275VA for either 120 VAC or 240
VAC. The 24VAC module has a rating of 72VA.
Sensor Resistances
See individual protector check-out procedures.
B6
Section B.indd 6
2/6/2008 10:48:27 AM
B7
Section B.indd 7
2/6/2008 10:48:27 AM
B8
Section B.indd 8
2/6/2008 10:48:28 AM
B9
Section B.indd 9
2/6/2008 10:48:29 AM
B10
Section B.indd 10
2/6/2008 10:48:29 AM
B11
Section B.indd 11
2/6/2008 10:48:29 AM
B12
Section B.indd 12
2/6/2008 10:48:29 AM
SECTION C
FUSE SELECTION FOR WELDED COMPRESSORS
AND COPELAMETIC COMPRESSORS
Motor Running Overload Protection and Branch Circuit
Short Circuit Protection are required for every compressor electrical branch circuit. These are detailed in Articles
430 and 440 of The National Electrical Code (NEC). All
installations and fuse selections must conform to the
NEC and any specific local code requirements. In case
of questions, contact a qualified electrician.
The fuse selection procedures of the Electrical Handbook are based on time delay (dual element) sizes that
will meet the requirements of most compressor installations. The selections conform to the National Electrical
Code short circuit requirements for single motor protection.
The manufacturer of the compressor system should be
consulted in cases of multiple motor or group fusing,
extreme ambient temperatures, or unusual operating
conditions where a larger fuse size than recommended
may be required.
Each compressor nameplate lists compressor data that
is needed to size short circuit protection: The Phase of
the motor, Locked Rotor Amps (LRA), and Rated Load
Amps (RLA). (RLA is not provided on welded compressor nameplates.) This data is also available in Section F.
C1
Section C.indd 1
2/5/2008 8:00:59 AM
The Electrical Handbook Fuse Selection Charts adjust
this nameplate data so that all that is necessary for standard compressor short circuit time delay fuse protection
sizing is to answer the Selection Chart questions, determine a multiplier for RLA, and size the compressor fuse
accordingly.
FUSE SELECTION PROCEDURE CHART FOR
WELDED COMPRESSORS AND COPELAND SCROLL
COMPRESSORS
1. Determine Rated Load Amps (RLA) from nameplate
or Section F.
2. Determine Locked Rotor Amps (LRA) from nameplate or Section F.
3. Divide LRA/RLA for Inrush Ratio.
4. If fuse ambient temperature is greater than 120°F,
multiply Inrush Ratio by 1.08.
5. For Single Phase compressors, multiply RLA by:
1.6 if Inrush Ratio is 5 or less, or
1.7 if Inrush Ratio is more than 5.
6. For Three Phase compressors, multiply RLA by:
1.5 if Inrush Ratio is 4 or less, or
1.6 if Inrush Ratio is more than 4.
7. Use the next higher Time Delay fuse rating above
the adjusted RLA value calculated in step 5 or step
6.
NOTE: IN NO CASE MAY FUSE RATING EXCEED
225% OF COMPRESSOR RLA!
C2
Section C.indd 2
2/5/2008 8:01:07 AM
FUSE SELECTION PROCEDURE CHART FOR
COPELAMETIC COMPRESSORS
1. Determine Rated Load Amps (RLA) from nameplate
or Section F.
2. Determine Locked Rotor Amps(LRA) from nameplate
or Section F.
3. Divide LRA/RLA for Inrush Ratio.
4. If fuse ambient temperature is greater than 120°F,
multiply Inrush Ratio by 1.08.
5. For Single Phase compressors, multiply RLA by:
1.5 if Inrush Ratio is 5 or less, or
1.6 if Inrush Ratio is more than 5.
6. For Three Phase compressors, multiply RLA by:
1.4 if Inrush Ratio is 4 or less, or
1.5 if Inrush Ratio is more than 4.
7. Use the next higher Time Delay fuse rating above the
adjusted RLA value calculated in step 5 or step 6.
NOTE: IN NO CASE MAY FUSE RATING EXCEED
225% OF COMPRESSOR RLA!
C3
Section C.indd 3
2/5/2008 8:01:07 AM
SECTION D
COMPRESSOR NOMENCLATURE
TOPICS
Welded Compressors .................................................. D2
HFC Welded Compressors.......................................... D4
A-Line .......................................................................... D6
CRKQ, CIKQ ............................................................... D8
CR7, CR6, CRKF, CS, CF ......................................... D10
Copelametic® ............................................................. D12
Copeland Discus™ ..................................................... D14
Refrigeration Copeland Scroll® .................................. D16
A/C Copeland Scroll®................................................. D18
Condensing Unit (All models except M-Line) ............ D20
M-Line Condensing Unit ............................................ D22
Copeland Screw™ ...................................................... D24
This section contains current information on Copeland® brand products. Information on obsolete models can be obtained from your local
Emerson Climate Technologies, Inc. wholesaler.
For individual model designations, visit On-Line Product Information at
www.emersonclimatecustomer.com.
NOMENCLATURE • WELDED COMPRESSORS
Code
E
F
R
T
S
Description
= High Efficiency
= Low Temperature
= High Temperature
= Two Speed
= Medium Temperature
X X X X
-
XXXX
Comp. Motor Rating
Compressor
Family Series
Either a number or a letter
established for each product
model.
Displacement
A letter only, arbitrarily
assigned for each different
displacement within any one
family series.
Model Variation
A number only, assigned to
indicate different model types
within any one family series.
D2
Nominal
(HP)
Code
¼
1/3
½
½
¾
1
1
1-1/4
1-1/2
1-3/4
2
2-1/4
2-3/4
3
3-1/2
4
4-1/2
5
7-1/2
9
10
12
0025
0033
0050
0051
0075
0100
0100
0125
0150
0175
0200
0225
0275
0275
0350
0400
0450
0500
7500
0900
1000
1200
NOMENCLATURE • WELDED COMPRESSORS
Compressor Motor Protection
Compressor Motor Types
Phase
Description
Type Protection
Code
1
Capacitor Run - Capacitor Start
C
1
Induction Run - Capacitor Start
I
1
Capacitor Run - Permanent
Split Capacitor
P
3
Three Phase
T
- X X X
Code
External Inherent ProtectionOne Protector (Line Break)
Use with Contactor
A
Internal Thermal Protection –
Electronic Sensors; and
Control Module External
Use with Contactor
S
Internal Inherent Protection –
One Protector (Line Break)
F
-
X X X
Electrical Codes
60 HZ
115-1
230-1
208/230-3
460-3
575-3
265-1

208/230-1

200/230-3
50HZ
Code
200/240-1
200/220-3
380/420-3
500-3
220/240-1
380/420-3
200-1
220/240-1
200/240-3
A
B
C
D
E
J
M
V
Z
5
(Refer to model data or nameplate for
specific nominal voltage.)
Product Variations
Numbers will be assigned as
follows:
1. Number – 100 is standard compressor used in
Copeland brand Condensing units.
2. Number – 200 indicates a STANDARD Compressor and Component Parts B/M and Model
No.
3. Number – 700 and –900 series indicate OEM
and Wholesaler service B/M and model number.
4. Number – 201 and larger will be assigned for all
other variations of a given model.
D3
NOMENCLATURE • HFC WELDED COMPRESSORS
Code
R
S
F
T
V
Description
=High or Medium
Temperature,
Air Conditioning and
Heat Pump
=Medium Temperature
=Low Temperature
=Two Speed
=Variable Speed
Oil Identifier
“E” designates Polyol Ester.
No digit if Mineral Oil
X X X X X X X
Model Variation
A number or letter, assigned
to indicate different model
types within any one family
series.
Compressor Family Series
Either a number or a letter
established for each product
model.
Compressor nominal capacity
at rating conditions to two
significant digits.
D4
Capacity Multiplier
C = 100
K = 1000
NOMENCLATURE • HFC WELDED COMPRESSORS
Compressor Motor Types
-
Phase
Description
Code
1
1
1
3
Capacitor Run – Capacitor Start
Induction Run – Capacitor Start
Capacitor Run – Permanent
Capacitor Run – Split Capacitor
C
I
P
T
X X X
Bill of Material
Product Variations
-
X X X
Typical Electrical Codes
60 HZ
50HZ
Codes
115-1
230-1
208/230-3
460-3
575-3
265-1
208/230-1
200/230-3
200/240-1
200/230
380/420-3
550-3
220/240-1
220/240-3
380/420-3
200-1
220/240-1
200/240-3
A
B
C
D
E
J
R
M
V
Z
5
(Refer to model data or nameplate for specific
nominal voltage.)
Compressor Motor Protection
Type
Code
External Inherent ProtectionOne Protector (Line Break)
Use with Contactor
A
Internal Inherent ProtectionOne Protector (Line Break)
Use with Contactor
F
D5
NOMENCLATURE • A-LINE COMPRESSORS
Application Range
Code
Description
Rating Point
S
Medium & Extended
Temperature R-404A, R-22
Extended Medium R-134a, R-404A
High Temperature R-134a
-10/120
45/130
F
R
20/120
Compressor Shell Series
A S E 2 4 C 3 E
Compressor Family Series
Capacity
Compressor nominal capacity
at 60 Hertz rating condition to
two significant digits.
Capacity Multiplier
C: 100
K: 1,000
Model Series Variation
A number or letter arbitrarily
assigned to indicate different
model types within any one
family series.
Oil Identifier
“E” designates Polyol Ester.
D6
NOMENCLATURE • A-LINE COMPRESSORS
Compressor Motor Protection
Type Protection
Code
Internal Thermal Protection –
Electronic Sensors; and Control
Module External
S
Internal Inherent Protection –
One Protector (Line Break)
Use with Contactor
F
External Inherent Protection –
One Protector (Line Break)
Use with Contactor
A
Compressor Motor Types
Phase
1
1
1
Description
Capacitor Run – Capacitor Start
Induction Run – Capacitor Start
Capacitor Run – Permanent
Split Capacitor
Three Phase
Induction Run – Split Phase
3
1
- I
Product Variations
Three-digit Bill of Material number that indicates
compressor configuration and
may include accessories.
Code
A
C
I
P
T
S
A
–
2
0
1
Voltage Ranges (Typical)
Voltage
Family
C, R
A
All
All
All
All
C, R
A
C, R
A
All
C
60 Hertz Rating
50 Hertz Rating
Code
Rating
Min.
Max.
Rating
Min.
Max.
A
A
C
D
E
J
V
V
Z
Z
5
T
115-1
115-1
208/230-3
460-3
575-3
265-1
208/230-1
208/230-1
200/230-3
-
103
103
207
414
518
239
197
187
187
-
127
127
253
506
633
292
253
244
253
-
100
200/220-3
380/420-3
500-3
220/240-1
200-1
200-1
220/240-1
220-240-1
200-240-3
200/240-1
90
180
342
450
198
180
180
198
198
180
180
110
240
462
550
264
200
220
264
254
264
252
BTU Model Families
22
134a
404A
507
A
R
CRK6
CRKQ
CS
X
X
X
X
X
X
X
X
X
X
X
D7
NOMENCLATURE • CRKQ, CIKQ MODELS
Compressor Family Series
Letter “C” established for this
family of compressors.
Capacity
Compressor nominal 60
Hertz capacity at ARI rating
condition to two significant
digits.
X
Code
R
X
X
X
Indicates compressors with
polyol ester oil.
X
Application Range
Description
High and medium temp.
Model Series Variation
Letter “Q” assigned to indicate “Quiet Compressors.”
Capacity Multiplier
K = 1000
D8
X E
NOMENCLATURE • CRKQ, CIKQ MODELS
Compressor Motor Types
Phase
Description
Code
1
Capacitor Run
– Permanent Spilt
Capacitor
Three Phase
General3 Lead Single Voltage
6 Lead Part Winding
P
3
T
Product Variations
Three-digit Bill of Material number that indicates
compressor configuration and
accessories included.
-X X X - X X X X X
Typical Electrical Codes
50 HZ
200-1
200/240-1
220/240-1
380/420-3
200/240-3
60 HZ
208/230-1
460-3
200/230-3
Code
V
T
Z
D
5
External Variations
Optional alpha letters
that indicate external accessories.
Compressor Motor Protection
Type Protection
Internal inherent
protection –
One protector,
Use with contactor
(single or three phase)
Code
F
D9
NOMENCLATURE • CR7, CR6, CRKF, CS, CF MODELS
Compressor Family Series
Either a number or a letter
established for each product
model.
Compressor nominal capacity at rating conditions to two
significant digits.
Indicates compressors with
polyol ester oil.
X X X X X X E
Application Range
Code
Refrig.
R
R-22
S
R-404A
F
R-404A
Description
Model Variation
A number or letter, assigned
to indicate different model
types within any one family
series.
High Temp.
A/C & Heat Pump
Med. Temp.
Refrigeration
Low Temp.
Refrigeration
Capacity Multiplier
K = 1000
D10
NOMENCLATURE • CR7, CR6, CRKF, CS, CF MODELS
Compressor Motor Types
Phase
Description
Code
1
Capacitor Run – Permanent
Split Capacitor
P
3
Three Phase
General –
3 Lead Single Voltage
6 Lead Part Winding (575 Volt)
T
Product Variations
Numbers will be assigned as follows:
1. Number –230 indicates a standard compressor
B/M and model number.
2. Number –270 indicates a standard compressor
B/M with crankcase heater.
3. Number –500 series indicates international
standard compressor B/M and model number.
4. Number –730 indicates a standard OEM service
B/M and model number.
5. Number –700 and –900 series indicate standard
OEM and Wholesaler service B/M and model
number.
6. For B/M different from –230, -270, and –730,
contact Emerson Climate Technologies, Inc.
Sales and Service.
- X X X - X X X
Electrical Codes
60 Hz.
208/230-3
460-3
575-3
265-1
208/230-1
200/230-3
50 Hz.
Code
200/220-3
380/420-3
500-3
220/240-1
380/420-3
200-1
220/240-1
360/460-3
180/260-1
200/240-3
C
D
E
J
M
V
Z
1*
2*
5
* Wide voltage range for India produced
products
Compressor Motor Protection
Type Protection
Code
Internal Inherent Protection –
One Protector
(Single or three phase)
F
D11
NOMENCLATURE • COPELAMETIC MODELS
Air-Cooled
Code
Description
A
= Std. Air Cooled
Code
R
Code
W
Refrigerant-Cooled
Description
= Std. Refrig. Cooled
Water-Cooled
Description
= Std. Water Cooled
K A T A – 0 1 0 0
Compressor
Family Series
Either a number or a letter
established for each product
model.
Comp. Motor Rating
Displacement and
Valve Plate
A letter only, assigned for
each different displacement
valve plate combination
within any one family series.
Model Variation
A number assigned to indicate major variations within
any one family series.
D12
Nominal (HP)
Code
1/3
½
½
¾
1
1-1/2
2
2
3
3
3
4
5
20
25
30
35
40
0033
0050
0051
0075
0100
0150
0200
0210
0300
0310
0311
0400
0500
2000
2500
3000
3500
4000
NOMENCLATURE • COPELAMETIC MODELS
Compressor Motor Types
Phase
Description
Code
1
Capacitor Run – Capacitor Start
1
Induction Run – Capacitor Start
C
I
3
Three Phase
T
3
Wye (star) Delta
E
3
6 Lead Part Winding or Across
The Line – except 575V
F
Product Variations
Numbers will be assigned as follows:
1. Number –100 is standard compressor used in
Copeland brand Condensing Units.
2. Number –200 indicates a STANDARD Compressor
Parts B/M and Model No.
3. Number –201 and larger will be assigned for all
other variations of a given model.
4. Number –800 indicates a standard replacement
Compressor and Component Parts B/M and Model
No. –240 volt control.
5. Number –801 indicates a standard replacement
Compressor and Component Parts B/M and Model
No. –120 volt control.
- C A V - 2 0 1
Electrical Codes
Compressor Motor Protection
Type Protection
Code
External Inherent ProtectionOne Protector, (Line Break)
Use with Contactor
A
Internal Inherent ProtectionOne Protector (Line Break)
Use with Contactor
F
Internal Thermal ProtectorsElectronic Sensors; and Control
Module External
Use with Contactor
S
60 Hz.
115-1
230-1
208/230-3
460-3
575-3
208/230/460-3
230/460-3
200-3
208/230-1
200/220/380-3
50 Hz.
Code
200/220-3
380/420-3
550-3
200/380/400-3
210/240/380/420-3
380/420-3
200/400-3
200/220-1
220/240-1
200/380-3
A
B
C
D
E
K
L
M
N
U
V
Z
8
D13
NOMENCLATURE • COPELAND DISCUS MODELS
Primary Application Range
R = ARI High Temp, Rated @ 45/130
S = ARI Med Temp, Rated @ 20/120
F = ARI Low Temp, Rated @ -25/105
Compressor Cooling
Code
Description
A
D
R
T
W
Air cooled
Discus
Refrigerant cooled
Std. two stage
Water cooled
May also be
“0” (Mineral Oil)
“E” (POE Oil)
“L” (Less Oil)
Tandem Style Models
Indicated by the digit representing the
comp. model series connected
in tandem with a comp. of the model
series indicated by the first digit.
XXXX X
XXXX
Nominal Capacity at
Rating Condition
2 numeric characters
Compressor
Family Series
Either a number of a letter
extablished for each product
family.
Capacity Multiplier
K - 1,000
M - 10,000
Displacement and
Valve Plate
A letter only, arbitrarily
assigned for each different
displacement valve plate
combination within any one
family series
Model Variation
Either a number or a letter
assigned to indicate major
variations within any one
family series.
D14
NOMENCLATURE • COPELAND DISCUS MODELS
Compressor Motor Types
Single Phase Motors
Capacitor run - capacitor start
Induction run - capacitor start
Induction run - split phase
Induction run - capacitor start,
low torque
Three Phase Motors
General
3 Lead single voltage
6 Lead part winding (575 volt)
9 Lead dual voltage
Star (wye) delta
6 Lead motors
Part winding or across the line
Code
C
I
S
X
Product Variations
Numbers will be assigned as follows:
1. Numbers -001 through -199 are reserved for
sub-b/m numbers.
2. Numbers -200 indicates a standard compressor
and component parts b/m and model no.
3. Numbers -201 and larger will be assigned for all
other variations of a given model.
Code
T
E
F
- X X X
X X X
Electrical Codes
60 Hz.
* 50 Hz.
(Typical)
Code
Compressor Motor Protection
Type Protection
Code
External inherent protection-one
protector (line break) use with
contactor
A
Internal inherent protection-one
protector use with contactor
F
Internal thermostat(s); and ext.
supplementary protector(s) use
with contactor
H
Internal thermostat(s); and three
ext. supplementary protectors
use with contactor
L
Internal thermal protectorselectronic sensors; and control
module external. Use with
contactor.
S
Internal thermal protectors-electronic sensors; and control module external. Use with contactor
(For European use only)
W
115-1
230-1
208-230-3
460-3
575-3
--208-1
-208/230/460-3
--230/460-3
----200-3
208-230-1
-Misc. A.C. Ratings
--200-1
100-1
200-230-3
230-3
380
200/220/380
100-1
200-1
200/220-3
380/400-3
500-3
115-1
230-1
200-1
208/230-1
200/400-3
210/240/380-3
380/420-3
200/400-3
200/380-3
200/240-3
220-1
200-1
-200-1
200/220-3
X
500-3
220/240-1
200-1
100-1
--346
200/346
A
B
C
D
E
F
G
H
I
K
L
M
N
P
R
S
T
U
V
W
Y
Z
3
4
5
6
7
8
D15
NOMENCLATURE • REFRIGERATION SCROLL MODELS
Compressor Family Series
Either a number or a letter established for
each product model.
Z = Scroll
Compressor nominal capacity at rating conditions to two
significant digits
Type of Oil
G = PAG
E = POE
“blank” = Mineral Oil
X X X X X X X X X
Capacity Multiplier
M: 10,000
K:
1,000
C: SCFM
Application Range
Code
Description
B
High/Medium
Temperature
Medium Temp.
Low Temp. with
Injection port
Helium
Marinized
Gas Booster
Asia Condensing Unit
Heat Pump
S
F
C
M
N
X
H
Model Variation
A number or letter, assigned
to indicate different model
types within any one family
series.
Optional Modulation
Code
D
H
HV
D16
Description
Digital
Horizontal
Horizontal Variable Speed
NOMENCLATURE • REFRIGERATION SCROLL MODELS
Product Variations
Numbers will be assigned as follows:
1. 230/231 - Standard Compressor & Component
Parts w/ Flag Terminal
2. 250/251 - Standard Compressor & Component
Parts w/ Screw Terminal
3. 240/241 - Rotalock Compressor & Component
Parts w/ Flag Terminal
4. 261/265 - Rotalock Compressor & Component
Parts w/ Screw Terminal
5. 900 series indicates standard OEM and
wholesaler service.
6. Other numbers designate variations.
Compressor Motor Types
Phase
Description
Code
1
Capacitor Run – Permanent
Split Capacitor
P
3
General
3 Lead Single Voltage
6 Lead Part Winding (575 Volt)
T
- X X X - X X X
Voltage Ranges (Typical)
Voltage
Code
C
D
E
V
5
7
J
R
60 Hertz Rating
Rating
208/230-3
460-3
575-3
208/230-1
200/230-3
380-3
265-1
-
50 Hertz Rating
Min.
Max.
187
414
518
197
180
342
239
-
253
506
633
253
253
418
292
-
Rating
200-3
380/420-3
500-3
200-1
200/220-3
220/240-1
220/240-3
Min.
Max.
180
342
450
180
180
198
180
220
462
550
220
242
264
264
Compressor Motor Protection
Type Protection
Code
Internal Inherent
ProtectionOne Protector
Use with Contactor
(Single or Three Phase)
F
External Electronic
Protection
(Three Phase)
W
D17
NOMENCLATURE • A/C SCROLL MODELS
Compressor Family Series
Either a number or a letter established for
each product model.
Type of Oil
E – 3MA POE Oil
Compressor nominal capacity at
rating conditions 2 – 3 numeric
characters.
Modulation
D – Digital
DU – Digital Uneven Tandem
DT – Digital Even Tandem
H – Horizontal
I – Heating
J – Digital Heating
S – UltraTech
T – Even Tandem
U – Uneven Tandem
V – Velocity Variable
X X X X X X X X X
Application Range
Code
Refrig.
Capacity Multiplier
K: 1,000
M: 10,000
Description
P
R-410A
High Temperature
Ultra High Pressure
R
R-22/407C/134a
High Temperature
Model Variation
A number or a letter, assigned
to indicate different model
types within any one family
series.
D18
NOMENCLATURE • A/C SCROLL MODELS
Compressor Motor Types
Phase
Description
Code
1
Capacitor Run – Permanent
Split Capacitor
P
3
General
3 Lead Single Voltage
6 Lead Part Winding (575 Volt)
T
Product Variations
1. 130/135/160 - Molded Plug
2. 230/235/260 - Quick Terminals T-box
3. 250/265 - Screw Terminals T-box
4. 7xx/9xx - T-box Service
5. 8xx - Molded Plug Service
- X X X - X X X
Compressor Motor Protection
Electrical Codes
Type Protection
Code
60 Hz.
Internal Inherent ProtectionOne Protector
Use with Contactor
(Single or Three Phase)
F
External Electronic ProtectionKriwan Module
(Three Phase)
W
208/230-3
460-3
575-3
265-1
208/230-1
Misc.
200/230-3
380-3
50 Hz.
200-3
380/420-3
220/240-1
380-420-3
220/240-3
Misc.
200/220-3
220/240-1
Code
C
D
E
J
M
R
V
X
5
7
Z
D19
NOMENCLATURE • CONDENSING UNIT
Design Series and Refrigerant
Letters (Except K,L,M)
K, L
M
Numbers (Except 6 & 7)
6, 7
X, 9
R-12
R-22 LT
R-22 LT Discus
R-22/R-502
R-12/R-502
Special Design
All Models Except M-Line
(Different series type may indicate a major design
revision.
New HFC Refrigerant Indicator
Pressure Rating
Approved Refrigerants
Standard
Models
Medium
High and Medium
High
T
P
J
Special
Designs
R
N
E
X X X X - X X X X
Application Temperature*
Temperature Range
Condensing Unit
Family Series
Type of Design
Type
Code
Air Cooled
No condenser
Water cooled
Evaporating Pan Base
Discus
A
N
W
E
D
Typical Motor Rating
Code
Nominal (HP)
Code
High Temperature
45ºF Max.; 0ºF Min.
H
Medium Temperature
25ºF Max.; -5ºF Min.
M
Medium Temperature
25ºF Max.; -25ºF Min.
F
1/4
1/3
1/2
3/4
1
1-1/2
2
2-1/2
3
3-1/2
4
5
6
7-1/2
9
10
15
20
22
25
27
30
40
50
60
70
80
0025
0033
0050
0075
0100
0150
0200
0250
0300
0350
0400
0500
0600
0750
0900
1000
1500
2000
2200
2500
2700
3000
4000
5000
6000
7000
8000
Low Temperature
0ºF Max.; -40ºF Min.
L
Extra Low Temperature
-20ºF Max.; -40ºF Min.
E
Two Stage
0ºF Max.; -40ºF Min.
T
Two Stage (Extra Low)
-30ºF Max.; -80ºF Min.
U
Commercial Application
High & Med. Temperature
Single Refrigerant
C
Dual Application
R-22 HT, R-502 MT
D
Multiple Application
R-12 H/MT, R-502 LT
B
NOTE: Limited or extended range will be
shown in performance data tables.
D20
*NOTE: Left hand position
may contain a letter indicating
a revision (on units less than
10 HP).
Right hand position may contain
the letter “Z” indicating a Glacier™ scroll compressor.
NOMENCLATURE • CONDENSING UNIT
Compressor Motor Type
Single Phase Motors
Code
Capacitor Run-Capacitor Start
Induction Run-Capacitor Start
Induction Run-Split Phase
Induction Run-Capacitor Start, Low Torque
Capacitor Run-Permanent Split Capacitor
Bill of Material Product Variations
C
I
S
X
P
Three Phase Motors
Variation (B/M) Number
UL/CSA Eligibility
001 thru 099
Intended for UL Listing
and CSA Certified.
100 thru 299
Intended for UL Recognition and CSA Certified.
300 thru 399
Not Eligible for either UL
Listing, LU Recognition,
or CSA Certified.
Code
T
General
3 Lead Single Voltage
6 Lead Part Winding 575 V
9 Lead Dual Voltage
Star (Wye) Delta
6 Lead Motors
Part Winding or Across the Line
E
F
- X X X - X X X
Typical Electrical Codes
Compressor Motor Protection
Type Protection
Code
External Inherent
Protection –
One Protector,
(Line Break)
Use with Contactor
(single or three phase)
A
Internal Inherent
Protection –
One Protector, Use
with Contactor.
(single or three phase)
F
Internal Thermostat(s);
and External Supplementary Protector(s).
(Two for 3Ø, one for 1Ø.)
Use with Contactor.
H
Internal Thermostat(s);
and Three External
Supplementary
Protectors. Use with
Contactor.
L
Internal Thermal
Protectors –
Electronic Sensors;
and Control Module
External.
Use with Contactor.
S
Internal Thermal
Protectors – Electronic
sensors; and control
module external. Use
with contactor. (For
European use only).
W
60 Hz.
50 Hz.
Code
115-1
230-1
208/230-3
460-3
575-3
208-1
265-1
208/230/460-3
230/460-3
All D.C. Ratings
200-3
208/230-1
Misc. A.C. Ratings
200-1
100-1
200/230-3
230-3
100-1
200-1
200/220-3
380/400-3
500-3
115-1
230-1
200-1
208/230-1
220/240-1
200/400-3
210/240/380-3
380/420-3
200/400-3
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
R
S
T
U
V
W
X
Y
Z
3
4
5
6
200/380-3
200/240-3
220-1
200-1
200-1
200/220-3
200/220-3
220/240-1
200-1
100-1
-
*NOTE: When applicable, specific 50 Hz ratings (not
necessarily identical to typical shown above) will be shown
as alternate on 60 Hz rated models.
D21
NOMENCLATURE • M-LINE CONDENSING UNIT
Base Size
A – 13” x 17” Steel
B – 10” x 12” Steel
E – 14-1/4” x 16” Copevap
F – 12” x 17-1/2” Steel
G – 10” x 21” Steel
H – 6-1/2” x 15-1/2” Steel
K – 15-1/2” x 18” Steel
N – 10” x 12” Copevap
P – 11” x 20” Copevap
Y – 10-1/4” x 14” Steel
Indicates M-Line
Condensing Unit
Series
M A A H Temperature Application
H
High Temperature
M Medium Temperature
L
Low Temperature
CFC & HCFC Construction & Refrigerant Indicator
(All Model Codes Signify UL Recognized Units)
R-12
A
G
I
J
K
L
U
V
R-22
R-502
E
M
Y
D
P
Q
S
T
Construction Style
Power
Cord
Receiver
Fan Guard
BX
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
New HFC Refrigerant Indicator
No reference to Construction and UL or CSA
Pressure Rating of Approved Refrigerants
Medium
High and Medium
High
D22
M-Line
2
3
4
NOMENCLATURE • M-LINE CONDENSING UNIT
Common Bill of Material Variations
CFC & HCFC Models
010
100’s
200’s
Wholesale (Single Pack)
OEM (Single Pack)
OEM (Multi Pack)
HFC Models
Hot Gas Evaporator Tube
O
E
M
New HFC products have the same B.O.M.
structure as F-Line.
No Tube
Epoxy Coated Copper Tube
Monel Tube
- 0 033 - IAA - XXX
Nominal HP
M-Line
013
017
020 to 023
024 to 027
032 to 037
049 to 051
075
100
HP
1/8
1/6
1/5
1/4
1/3
1/2
3/4
1
Voltage (Start Torque)
IAA
SAA
PAA
IAV
CAV
IAS
IAZ
SAZ
115-1-60
115-1-60
115-1-60
208/230-1-60
208/230-1-60
220-1-50
220/240-1-50
220/240-1-50
(High)
(Low)
(Low)
(High)
(High)
(High)
(High)
(Low)
D23
NOMENCLATURE • COPELAND SCREW COMPRESSOR
Body Type
Code
C
H
D
Description
Lubricant
O = R22
E = HFC
Compact
Semi-hermetic
Open Drive
S C H 2 - 9 0 0 0
Copeland Screw
Compressor
Comp. Motor Rating
Temperature Application
H = High
M = Medium
L = Low
A = Optimized for R-134a
(COMPACT ONLY)
Model Variation
A number assigned to
indicate major variations
within any one family
series. A number assigned
to individual major variations within any one family
series, for screw compressors 1 or 2.
D24
Nominal (HP)
Code
20
25
30
35
40
50
60
70
75
80
80
90
90
110
125
140
160
180
210
240
280
300
200
250
300
350
400
500
600
700
750
800
801*
900
901*
11H
12H
14H
16H
18H
21H
24H
28H
30H
*801 and 901 Frame 2 SCA2 Only
NOMENCLATURE • COPELAND SCREW COMPRESSOR
Compressor Motor Types
Phase
Description
Code
3
6 Lead Part Winding or Across
The Line – except 575 V
F
3
Misc. 3 Phase
• Single voltage 3 lead
• Dual voltage 9 lead
• 575 V 60 H/500 V 50 HZ
20 H.P. & up 6 lead Part Winding
T
3
Star (WYE) Delta
E
Product Variations
Numbers will be assigned as follows:
1. Number –200 indicates a STANDARD Compressor and Component
Parts B/M and Model No.
2. Number – 800 indicates a standard
replacement compressors and
component parts and model no.
- F W D - 2 0 0
Compressor Motor Protection
Type Protection
Internal Thermal ProtectorsElectronic Sensors; and Control
Module External
Use with Contactor
Electrical Codes
Code
60 Hz.
50 Hz.
Code
W
208/230-3
460-3
575-3
208/230/460-3
200/220-3
380/420-3
550-3
200/380/400-3
C
D
E
K
D25
SECTION E
ELECTRICAL COMPONENT NOMENCLATURE
AND DATA
TOPICS
Potential Relay Nomenclature.....................................E1
G.E. Numbering System .............................................E1
Potential Relay Data ...................................................E2
Current Relay Data .....................................................E7
Start Capacitor Data..................................................E16
Run Capacitor Data...................................................E22
This section contains current information on Copeland® products. Information on obsolete models can be obtained from your local wholesaler
carrying Copeland brand products.
Section E TOC.indd 1
2/21/2008 7:40:03 AM
Potential Relay Nomenclature
General Electric has somewhat of a complicated numbering
system for potential relays. Without a complete catalog,
the numbering designations are not self-explanatory,
but a basic understanding of the nomenclature is helpful
in identifying potential replacements in an emergency
situation.
G.E. Numbering System
A typical General Electric potential relay number is as
follows: 3ARRA3CT6D5
3ARR3 CT 3 D 5
Mounting Position
Electrical Specifications
Coil Rating
Mounting Bracket & Terminal Connection
Relay Type
E1
Section E TOC.indd 2
2/21/2008 7:40:25 AM
Potential Relay Data
Wholesaler
P/N
940-0001-48
940-0001-53
940-0001-54
940-0001-55
940-0001-56
940-0001-59
940-0001-60
940-0001-62
940-0001-63
940-0001-64
940-0001-69
940-0001-71
940-0001-78
940-0001-79
940-0001-80
940-0001-82
940-0001-83
940-0001-84
940-0001-64
940-0001-88
Copeland®
Brand P/N
040-0001-48
040-0001-53
040-0001-54
040-0001-55
040-0001-56
040-0001-59
040-0001-60
040-0001-62
040-0001-63
040-0001-64
040-0001-69
040-0001-71
040-0001-78
040-0001-79
040-0001-80
040-0001-82
040-0001-83
040-0001-84
040-0001-85
040-0001-86
040-0001-87
040-0001-88
GE P/N
3ARR3KC7M5
3ARR3KC10A5
3ARR3KC10V5
3ARR3KC10S5
3ARR3KC3T5
3ARR3KC6W5
3ARR3KC24S5
3ARR3KC5M5
3ARR3KC10C5
3ARR3KC6A5
3ARR3KC4D5
3ARR3KC10B5
3ARR3KC10AS5
3ARR3KC3P5
3ARR3KC2L5
3ARR3KC3U5
3ARR3K6A5
3ARR3K6B5
3ARR3K4B5
3ARR3K4A5
3ARR3J6A5
Pick-up
Volts
150 - 160
260 - 280
240 - 260
190 - 200
200 - 220
210 - 230
190 - 200
150 - 160
300 - 320
260 - 280
320 - 340
280 - 300
190 - 200
170 - 180
140 - 150
220 - 240
260 - 280
280 - 300
280 - 300
260 - 280
260 - 280
220 - 240
Drop Out
Volts
15 - 45
50 - 110
60 - 121
40 - 105
40 - 90
60 - 125
55 - 115
35 - 77
50 - 110
60 - 121
60 - 135
50 - 110
40 - 105
40 - 90
20 - 45
40 - 90
60 - 121
60 - 121
60 - 135
60 - 135
60 - 121
60 - 121
Cont. Volt
Rating
130
375
375
375
332
420
383
253
375
420
500
375
338
332
168
332
420
420
500
500
420
420
Freq.
60
60
60
60
60
60
60
60
60
60
60
60
50
60
60
60
60
60
60
60
60
60
E2
Section E.indd 2
2/26/2008 11:02:10 AM
Potential Relay Data
Wholesaler
P/N
940-0007-00
940-0007-02
940-0007-04
940-0046-18
940-0046-19
940-0046-21
940-0046-22
940-0046-23
940-0140-00
940-0140-07
940-0140-00
940-0140-02
940-0140-03
940-0140-04
940-0140-05
940-0140-06
940-0140-07
940-0140-08
940-0001-48
940-0001-49
Copeland®
Brand P/N
GE P/N
040-0007-00
040-0007-02
040-0007-04
040-0046-18
040-0046-19
040-0046-20
040-0046-21
040-0046-22
040-0046-23
040-0046-24
040-0140-00
040-0140-07
040-0166-00
040-0166-01
040-0166-02
040-0166-03
040-0166-04
040-0166-05
040-0166-06
040-0166-07
040-0166-08
040-0166-09
3ARR3C7M2
3ARR3C5AA2
3ARR3C24E2
3ARR22J24E5
3ARR22J6D5
3ARR22J5P5
3ARR22J7M5
3ARR22J25AC5
3ARR22J10B5
3ARR22J4AD5
3ARR3KC6AC5
3ARR3T6AC5
3ARR3T4AA5
3ARR3T25S5
3ARR3T3S5
3ARR3T6AA5
3ARR3T10AT5
3ARR3T3AA5
3ARR3KC3L5
3ARR3T7M5
3ARR3T3E5
Pick-up
Volts
150 - 160
260 - 280
340 - 360
340 - 360
320 - 340
170 - 180
150 - 160
300 - 320
280 - 300
320 - 340
300 - 320
260 - 280
300 - 320
260 - 280
190 - 200
190 - 200
260 - 280
200 - 220
260 - 280
140 - 150
150 - 160
340 - 360
Drop Out
Volts
15 - 45
35 - 77
55 - 125
55 - 125
60 - 121
35 - 77
15 - 45
60 - 133
50 - 110
60 - 135
60 - 121
40 - 90
60 - 121
60 - 135
60 - 130
40 - 90
60 - 121
40 - 105
40 - 90
40 - 90
15 - 45
50 - 100
Cont. Volt
Rating
130
228
336
383
420
253
130
400
375
0
378
299
343
395
395
290
343
296
261
290
114
290
Freq.
60
50
60
60
60
60
60
50
60
50
50
50
50
60
60
50
50
50
60
60
60
E3
Section E.indd 3
2/26/2008 11:02:31 AM
Potential Relay Data
Wholesaler
P/N
940-0001-50
940-0001-51
940-0001-52
940-0001-53
940-0001-54
940-0001-55
940-0001-57
940-0001-59
940-0001-60
940-0001-61
940-0001-62
940-0001-63
940-0001-64
940-0001-65
940-0001-66
940-0001-68
940-0001-69
940-0001-70
940-0001-71
940-0001-72
940-0001-73
Copeland®
Brand P/N
GE P/N
040-0166-10
040-0166-11
040-0166-12
040-0166-13
040-0166-14
040-0166-15
040-0166-17
040-0166-18
040-0166-19
040-0166-20
040-0166-21
040-0166-22
040-0166-23
040-0166-24
040-0166-25
040-0166-26
040-0166-27
040-0166-28
040-0166-29
040-0166-30
040-0166-31
040-0166-32
3ARR3T24E5
3ARR3T5P5
3ARR3T25AC5
3ARR3T10A5
3ARR3T10V5
3ARR3T10S5
3ARR3T23AA5
3ARR3T6W5
3ARR3T24S5
3ARR3T6D5
3ARR3T5M5
3ARR3T10C5
3ARR3T6A5
3ARR3T10AA5
3ARR3T3C5
3ARR3T10AB5
3ARR3T6V5
3ARR3T4D5
3ARR3T3AV5
3ARR3T10B5
3ARR3T6AB5
3ARR3T3AU5
Pick-up
Volts
340 - 360
170 - 180
300 - 320
260 - 280
240 - 260
190 - 200
260 - 280
210 - 230
190 - 200
320 - 340
150 - 160
300 - 320
260 - 280
260 - 280
300 - 320
280 - 300
240 - 260
320 - 340
240 - 260
280 - 300
280 - 300
220 - 240
Drop Out
Volts
55 - 125
35 - 77
60 - 133
50 - 110
60 - 121
40 - 105
45 - 109
60 - 125
55 - 115
60 - 121
35 - 77
50 - 110
60 - 121
50 - 110
55 - 100
50 - 110
60 - 121
60 - 135
40 - 90
50 - 110
60 - 121
40 - 90
Cont. Volt
Rating
336
221
406
375
375
375
262
420
383
420
253
375
420
338
332
338
420
500
299
375
378
299
Freq.
60
60
50
60
60
60
50
60
60
60
60
60
60
50
60
50
60
60
50
60
50
50
E4
Section E.indd 4
2/26/2008 11:02:31 AM
Potential Relay Data
Wholesaler
P/N
940-0001-75
940-0001-77
940-0001-78
940-0001-79
940-0001-80
940-0001-82
940-0001-83
940-0001-84
940-0001-64
940-0001-88
Copeland®
Brand P/N
GE P/N
040-0166-33
040-0166-34
040-0166-35
040-0166-36
040-0166-37
040-0166-38
040-0166-39
040-0166-40
040-0166-41
040-0166-42
040-0166-43
040-0166-44
040-0166-45
3ARR3T7J5
3ARR3T7AL5
3ARR3T5V5
3ARR3T10AS5
3ARR3T3P5
3ARR3T2L5
3ARR3T3U5
3ARR3K6A5
3ARR3K6B5
3ARR3K4B5
3ARR3K4A5
3ARR3T6A5
3ARR3T6U5
Pick-up
Volts
120 - 130
140 - 150
240 - 260
190 - 200
170 - 180
140 - 150
220 - 240
260 - 280
280 - 300
280 - 300
260 - 280
260 - 280
220 - 240
Drop Out
Volts
15 - 40
15 - 40
35 - 77
40 - 105
40 - 90
20 - 45
40 - 90
60 - 121
60 - 121
60 - 135
60 - 135
60 - 121
60 - 121
Cont. Volt
Rating
130
117
253
338
332
168
332
420
420
500
500
420
420
Freq.
60
50
60
50
60
60
60
60
60
60
60
60
E5
Section E.indd 5
2/26/2008 11:02:31 AM
Current Relay Data
Wholesaler P/N
940-0088-00
940-0088-03
940-0088-04
940-0088-05
940-0088-06
940-0090-00
940-0090-04
940-0090-06
940-0098-01
940-0098-02
940-0102-02
940-0115-00
940-C411-49
940-C411-18
940-C411-38
Copeland®
Brand P/N
040-0088-00
040-0088-03
040-0088-04
040-0088-05
040-0088-06
040-0089-04
040-0089-06
040-0090-00
040-0090-01
040-0090-04
040-0090-05
040-0090-06
040-0090-07
040-0098-01
040-0098-02
040-0102-02
040-0115-00
040-0115-01
040-0115-02
040-0128-01
040-0141-00
040-0141-01
040-0141-02
GE P/N
Texas Inst. P/N
6409-26-196
6409-26-176
6409-26-935
6409-26-189
6409-26-900
3CR-203-171B
3CR-203-186B
3CR-206-174B
3CR-206-181B
3CR-206-191B
3CR-206-165B
3CR-206-189B
3CR206-154B
6409-40-935
6409-40-180
6409-51-176
3CR-111-269
3CR-111-239
3CR-111-272
3CR234-181B
Max. Pick-up
Amps
28.9
14.9
33.6
21.8
42
12.9
22.5
14.1
17.9
27.2
10.4
24.75
8.25
33.6
17.4
14.9
12.2
6.3
13.3
17.9
7.7
3.8
6.2
Min. Drop
Out Amps
23.7
12.6
27.8
17.9
36
10.8
18.7
11.9
15.1
22.7
8.6
20.45
6.9
27.8
14.3
12.6
10.2
5.25
11.1
15.1
6.5
3.25
5.25
E6
Section E.indd 6
2/26/2008 11:02:31 AM
Current Relay Data
Wholesaler P/N
940-C411-47
940-C411-58
940-C411-82
940-C411-52
940-C411-66
940-C411-72
940-C411-73
940-C411-79
940-C411-80
940-C411-83
940-C411-82
940-C411-82
940-C411-82
940-C411-66
940-C411-49
940-C411-45
940-C411-45
940-C411-58
940-C411-83
940-C411-83
940-C411-83
940-C411-13
940-C411-18
Copeland®
Brand P/N
040-0141-03
040-0141-04
040-0141-05
040-0141-10
040-0141-14
040-0141-17
040-0141-18
040-0141-20
040-0141-21
040-0141-22
040-0150-01
040-0150-01
040-0150-01
040-0150-02
040-0150-03
040-0150-04
040-0150-04
040-0150-05
040-0150-06
040-0150-06
040-0150-06
040-0150-07
040-0150-08
GE P/N
Texas Inst. P/N
9660A-467-1822
9660C-3018-182
9660A-467-183
9660C-3018-183
Max. Pick-up
Amps
7.45
9.15
17.8
8.2
11
13.2
13.4
16.5
16.7
18.2
17.8
17.8
17.8
11
7.7
7.1
7.1
9.15
18.2
18.2
18.2
3.25
3.8
Min. Drop
Out Amps
6.3
7.7
14.9
7
9.35
11.1
11.4
13.8
14
15.3
14.9
14.9
14.9
9.35
6.5
6
6
7.7
15.5
15.5
15.5
2.75
3.25
E7
Section E.indd 7
2/26/2008 11:02:31 AM
Current Relay Data
Wholesaler P/N
940-C411-35
940-C411-63
940-C411-89
940-C411-89
940-C411-89
940-C411-89
940-C411-91
940-C411-91
940-C411-91
940-C411-78
940-C411-47
940-C411-61
940-C411-52
940-C411-85
940-C411-85
940-C411-85
940-C411-73
940-C411-72
940-C411-71
940-C411-40
940-C411-38
940-0150-24
Copeland®
Brand P/N
040-0150-09
040-0150-10
040-0150-11
040-0150-11
040-0150-11
040-0150-11
040-0150-12
040-0150-12
040-0150-12
040-0150-13
040-0150-14
040-0150-15
040-0150-16
040-0150-17
040-0150-17
040-0150-17
040-0150-18
040-0150-19
040-0150-20
040-0150-21
040-0150-22
040-0150-23
040-0150-24
GE P/N
Texas Inst. P/N
9660-467-191
9660C-3018-191
9660A-467-185
9660C-3018-185
Max. Pick-up
Amps
5.8
10.3
21.9
21.9
21.9
21.9
24.4
24.4
24.4
15.8
7.45
9.75
8.2
19.2
19.2
19.2
13.35
13.2
12.7
6.5
6.2
21.9
15.8
Min. Drop
Out Amps
4.95
8.6
18.2
18.2
18.2
18.2
20.3
20.3
20.3
13.3
6.3
8.2
7
16.2
16.2
16.2
11.35
11.1
10.8
5.5
5.25
18.2
13.3
E8
Section E.indd 8
2/26/2008 11:02:31 AM
Current Relay Data
Wholesaler P/N
940-C411-55
940-0152-00
940-0152-03
940-C401-82
940-0102-02
940-C401-25
940-C401-35
940-C401-82
940-0152-05
940-C401-58
Copeland®
Brand P/N
040-0150-25
040-0150-31
040-0150-31
040-0150-32
040-0150-33
040-0150-34
040-0150-34
040-0150-35
040-0150-35
040-0150-36
040-0150-36
040-0150-37
040-0150-37
040-0152-00
040-0152-03
040-0152-13
040-0159-02
040-0162-00
040-0162-01
040-0162-02
040-0162-03
040-0162-04
040-0162-05
GE P/N
Texas Inst. P/N
Max. Pick-up
Amps
8.5
13.7
13.7
12.1
18.2
11
11
14
14
14.7
14.7
19.9
19.9
7.7
3.76
17.8
14.9
4.65
13.2
5.8
17.8
4.2
9.15
Min. Drop
Out Amps
7.15
11.5
11.5
10.3
15.5
9.35
9.35
11.9
11.9
12.5
12.5
16.6
16.6
6.5
3.15
14.9
12.6
3.95
11.1
4.95
14.9
3.55
7.7
E9
Section E.indd 9
2/26/2008 11:02:31 AM
Current Relay Data
Wholesaler P/N
940-C401-66
940-C401-40
940-0152-03
940-0152-01
940-0152-00
940-0152-04
940-0162-13
940-0162-14
940-0163-00
940-0163-01
940-C411-79
940-C411-70
940-C411-80
940-C411-89
940-C411-91
940-C411-85
940-C411-49
940-C411-83
940-C411-38
940-0088-00
940-0088-02
940-0088-03
940-0088-04
Copeland®
Brand P/N
040-0162-07
040-0162-08
040-0162-09
040-0162-10
040-0162-11
040-0162-12
040-0162-13
040-0162-14
040-0163-00
040-0163-01
040-0163-02
040-0163-03
040-0163-04
040-0163-05
040-0163-07
040-0163-08
040-0167-03
040-0167-06
040-0167-22
040-0168-00
040-0168-01
040-0168-02
040-0168-03
GE P/N
Texas Inst. P/N
Max. Pick-up
Amps
11
6.5
3.35
2.29
7.7
3.76
9.75
13.2
9.15
11
16.5
12.1
16.7
21.9
24.4
19.2
7.7
18.2
6.2
28.9
17.4
14.9
33.6
Min. Drop
Out Amps
9.35
5.5
2.85
1.96
6.5
3.15
8.2
11.1
7.7
9.35
13.8
10.3
14
18.2
20.3
16.2
6.5
15.5
5.25
23.7
14.3
12.6
27.8
E10
Section E.indd 10
2/26/2008 11:02:32 AM
Current Relay Data
Wholesaler P/N
940-0088-05
940-0088-07
940-0102-00
940-0102-02
940-0102-03
940-0102-07
940-0163-00
940-C411-83
940-C016-00
940-0102-04
940-C016-03
940-C016-03
940-C016-00
940-0152-01
940-0152-03
940-0152-05
940-C401-25
Copeland®
Brand P/N
040-0168-04
040-0168-06
040-0169-00
040-0169-01
040-0169-02
040-0169-03
040-0169-06
040-0171-00
040-0171-06
040-0172-00
040-0172-02
040-0172-03
040-0172-03
040-0172-04
040-0172-04
040-0172-05
040-0172-05
040-C016-00
040-C401-01
040-C401-11
040-C401-14
040-C401-21
040-C401-25
GE P/N
Texas Inst. P/N
3CR-763-188B
9660-040-101
9660-040-111
9660-040-114
9660-040-121
9660-040-125
Max. Pick-up
Amps
21.8
13.3
28.9
17.4
14.9
33.6
13.3
9.15
18.2
24
24.75
30.3
30.3
18.4
18.4
22.1
22.1
24
2.29
3
3.35
4.2
4.65
Min. Drop
Out Amps
17.9
11.1
23.7
14.3
12.6
27.8
11.1
7.7
15.5
19.8
20.45
25.1
25.1
15.4
15.4
18.4
18.4
19.8
1.96
2.56
2.85
3.55
3.95
E11
Section E.indd 11
2/26/2008 11:02:32 AM
Current Relay Data
Wholesaler P/N
940-C401-35
940-C401-40
940-0152-00
940-C401-58
940-C401-66
940-C401-72
940-C401-82
940-C411-13
940-C411-18
940-C411-35
940-C411-38
940-C411-45
940-C411-47
940-C411-49
940-C411-52
940-C411-61
940-C411-63
940-C411-66
940-C411-71
940-C411-73
940-C411-79
940-C411-82
Copeland®
Brand P/N
040-C401-35
040-C401-40
040-C401-49
040-C401-55
040-C401-58
040-C401-66
040-C401-72
040-C401-82
040-C411-13
040-C411-18
040-C411-35
040-C411-38
040-C411-45
040-C411-47
040-C411-49
040-C411-52
040-C411-61
040-C411-63
040-C411-66
040-C411-71
040-C411-73
040-C411-79
040-C411-82
GE P/N
Texas Inst. P/N
9660-040-135
9660-040-140
9660-040-149
9660-040-155
9660-040-158
9660-040-166
9660-040-172
9660-040-182
9660B-041-113
9660B-041-135
9660-041-138
9660A-041-145
9660-041-147
9660-041-149
9660-041-161
9660-041-163
9660-041-166
9660A-041-173
9660A-041-182
Max. Pick-up
Amps
Min. Drop
Out Amps
5.9
6.5
7.7
8.5
9.15
11
13.2
17.8
3.25
3.8
5.9
6.2
7
7.4
7.7
8.1
9.75
10.3
11
12.9
13.7
16.5
17.8
5
5.5
6.5
7.15
7.7
9.2
11.1
14.9
2.77
3.25
5
5.25
5.9
6.2
6.5
6.8
8.2
8.6
9.2
10.8
11.5
13.8
14.9
E12
Section E.indd 12
2/26/2008 11:02:32 AM
Current Relay Data
Wholesaler P/N
940-C411-83
940-C411-83
940-C411-91
940-C411-91
Copeland®
Brand P/N
040-C411-83
040-C411-83
040-C411-91
040-C411-91
GE P/N
Texas Inst. P/N
9660A-041-183
9660C-3027-183
9660A-041-191
9660C-3027-191
Max. Pick-up
Amps
18.2
18.2
24.4
24.4
Min. Drop
Out Amps
15.3
15.3
20.3
E13
Section E.indd 13
2/26/2008 11:02:32 AM
Start Capacitor Data
Wholesaler P/N Copeland® Brand P/N MFD-Low
914-0006-02
914-0006-03
914-0006-09
914-0006-10
914-0006-11
914-0006-12
914-0006-03
914-0006-09
914-0006-10
914-0006-11
014-0006-12
914-0008-48
914-0008-50
914-0008-51
914-0008-61
914-0008-62
914-0008-63
914-0008-64
914-0008-65
914-0008-66
914-0008-70
914-0008-71
014-0006-02
014-0006-03
014-0006-09
014-0006-10
014-0006-11
014-0006-12
014-0006-13
014-0006-14
014-0006-15
014-0006-16
014-0006-17
014-0008-47
014-0008-48
014-0008-50
014-0008-51
014-0008-61
014-0008-62
014-0008-63
014-0008-64
014-0008-65
014-0008-66
014-0008-68
014-0008-70
014-0008-71
88
189
216
270
145
175
189
216
270
145
175
460
124
161
145
88
53
540
43
64
108
88
43
189
MFD-High
106
227
259
324
174
216
227
259
324
174
216
552
149
193
174
106
64
648
52
77
130
106
52
227
Cap Volts
330
330
330
330
330
330
330
330
330
330
330
115
220
220
220
220
220
115
220
330
220
115
330
220
E14
Section E.indd 14
2/26/2008 11:02:32 AM
Start Capacitor Data
Wholesaler P/N Copeland® Brand P/N MFD-Low
914-0008-72
014-0008-72
64
914-0008-73
014-0008-73
43
914-0008-74
014-0008-74
72
914-0008-78
014-0008-78
108
914-0008-79
014-0008-79
270
914-0032-00
014-0032-00
233
914-0032-06
014-0032-06
233
014-0032-07
41
914-0036-00
014-0036-00
53
914-0036-01
014-0036-01
88
914-0036-03
014-0036-03
88
914-0036-04
014-0036-04
145
914-0036-05
014-0036-05
108
914-0036-07
014-0036-07
130
914-0036-11
014-0036-11
72
914-0036-13
014-0036-13
21
914-0036-00
014-0036-16
53
914-0036-01
014-0036-17
88
914-0036-02
014-0036-18
130
914-0036-03
014-0036-19
88
914-0036-04
014-0036-20
145
914-0036-05
014-0036-21
108
914-0036-07
014-0036-22
130
914-0036-08
014-0036-23
340
MFD-High
77
52
86
130
324
280
280
53
64
106
106
174
130
156
88
25
64
106
156
106
174
130
156
408
Cap Volts
250
250
330
250
165
110
125
250
330
250
330
250
330
330
220
330
330
250
250
330
250
330
330
110
E15
Section E.indd 15
2/26/2008 11:02:32 AM
Start Capacitor Data
Wholesaler P/N Copeland® Brand P/N MFD-Low
914-0036-09
014-0036-24
243
914-0036-11
014-0036-25
72
914-0036-12
014-0036-26
189
914-0036-15
014-0036-28
189
914-0053-00
014-0038-00
145
914-0053-01
014-0038-01
145
914-0053-02
014-0038-02
53
014-0038-03
43
914-0053-04
014-0038-04
189
914-0053-05
014-0038-05
88
914-0053-06
014-0038-06
50
914-0053-07
014-0038-07
43
914-0053-10
014-0038-10
145
914-0053-10
014-0038-17
145
914-0053-13
014-0053-13
64
914-0053-00
014-0053-18
145
914-0053-01
014-0053-19
145
914-0053-02
014-0053-20
53
914-0053-04
014-0053-21
189
914-0053-05
014-0053-22
88
914-0053-06
014-0053-23
50
914-0053-07
014-0053-24
43
914-0053-09
014-0053-25
189
914-0053-10
014-0053-26
145
MFD-High
292
88
227
227
175
175
64
52
227
106
60
53
174
174
77
175
175
64
227
106
60
52
227
174
Cap Volts
165
220
250
165
165
110
250
250
165
250
330
330
250
250
330
165
110
250
165
250
330
330
250
250
E16
Section E.indd 16
2/26/2008 11:02:32 AM
Start Capacitor Data
Wholesaler P/N Copeland® Brand P/N MFD-Low
914-0053-13
014-0053-29
64
914-0053-14
014-0053-30
88
014-0053-31
53
914-0053-16
014-0053-32
130
914-0006-03
014-0058-00
189
914-0006-09
014-0058-01
216
914-0006-10
014-0058-02
270
914-0006-11
014-0058-03
145
914-0006-12
014-0058-04
175
014-0058-05
460
914-0008-48
014-0058-06
124
914-0008-49
014-0058-07
400
914-0008-50
014-0058-08
161
914-0008-51
014-0058-09
145
914-0008-52
014-0058-10
430
914-0008-57
014-0058-11
243
914-0008-58
014-0058-12
324
914-0008-59
014-0058-13
590
914-0008-61
014-0058-14
88
014-0058-15
53
914-0008-63
014-0058-16
540
914-0008-64
014-0058-17
43
914-0008-65
014-0058-18
64
914-0008-66
014-0058-19
108
MFD-High
77
108
64
156
227
259
324
174
216
552
149
480
193
174
516
292
389
708
106
64
648
52
77
130
Cap Volts
330
330
330
330
330
330
330
330
330
110
220
110
220
220
125
110
110
110
220
220
110
220
330
220
E17
Section E.indd 17
2/26/2008 11:02:32 AM
Start Capacitor Data
Wholesaler P/N Copeland® Brand P/N MFD-Low
914-0008-69
014-0058-20
270
914-0008-70
014-0058-21
43
914-0008-71
014-0058-22
189
914-0008-72
014-0058-23
64
914-0008-73
014-0058-24
43
914-0008-74
014-0058-25
72
914-0008-78
014-0058-26
108
914-0008-79
014-0058-27
270
914-0036-00
014-0058-28
53
914-0036-01
014-0058-29
88
914-0036-02
014-0058-30
130
914-0036-03
014-0058-31
88
914-0036-04
014-0058-32
145
914-0036-05
014-0058-33
108
914-0036-07
014-0058-34
130
914-0036-08
014-0058-35
340
914-0036-09
014-0058-36
243
914-0036-11
014-0058-37
72
914-0036-12
014-0058-38
189
914-0036-15
014-0058-40
189
014-0058-41
340
014-0058-43
243
914-0053-00
014-0059-00
145
914-0053-01
014-0059-01
145
MFD-High
324
52
227
77
52
86
130
324
64
106
156
106
174
130
156
408
292
88
227
227
408
292
175
175
Cap Volts
110
330
220
250
250
330
250
165
330
250
250
330
250
330
330
110
165
220
250
165
165
250
165
110
E18
Section E.indd 18
2/26/2008 11:02:33 AM
Start Capacitor Data
Wholesaler P/N Copeland® Brand P/N MFD-Low
914-0053-02
014-0059-02
53
914-0053-04
014-0059-03
189
914-0053-05
014-0059-04
88
914-0053-06
014-0059-05
50
914-0053-07
014-0059-06
43
914-0053-09
014-0059-07
189
914-0053-10
014-0059-08
145
914-0053-11
014-0059-09
72
914-0053-13
014-0059-11
64
914-0053-14
014-0059-12
88
914-0053-15
014-0059-13
53
914-0053-16
014-0059-14
130
014-0059-18
130
014-0059-20
243
014-0061-00
460
914-0008-48
014-0061-01
124
914-0008-49
014-0061-02
400
914-0008-50
014-0061-03
161
914-0008-51
014-0061-04
145
914-0008-52
014-0061-05
430
914-0008-57
014-0061-06
243
914-0008-58
014-0061-07
324
914-0008-59
014-0061-08
590
914-0008-61
014-0061-09
88
MFD-High
64
227
106
60
52
227
174
88
77
106
64
156
156
292
552
149
480
193
174
516
292
389
708
106
Cap Volts
250
165
250
330
330
250
250
330
330
330
330
330
250
165
110
220
110
220
220
125
110
110
110
220
E19
Section E.indd 19
2/26/2008 11:02:33 AM
Start Capacitor Data
Wholesaler P/N Copeland® Brand P/N MFD-Low
014-0061-10
53
914-0008-63
014-0061-11
540
914-0008-64
014-0061-12
43
914-0008-65
014-0061-13
64
914-0008-66
014-0061-14
108
914-0008-69
014-0061-15
270
914-0008-70
014-0061-16
43
914-0008-72
014-0061-18
64
914-0008-73
014-0061-19
43
914-0008-74
014-0061-20
72
914-0008-78
014-0061-21
108
914-0008-79
014-0061-22
270
914-0037-07
014-0064-26
60
MFD-High
64
648
52
77
130
324
52
77
52
86
130
324
0
Cap Volts
220
110
220
330
220
110
330
250
250
330
250
165
370
E20
Section E.indd 20
2/26/2008 11:02:33 AM
Run Capacitor Data
Wholesaler
P/N
914-0037-04
914-0037-06
914-0037-07
914-0037-08
914-0037-09
914-0037-10
914-0037-11
914-0037-12
914-0037-13
914-0037-14
914-0037-16
914-0037-17
914-0037-18
914-0037-19
914-0037-22
914-0037-11
914-0037-36
914-0037-37
914-0037-38
914-0037-39
914-0037-40
Copeland®
Brand P/N
014-0011-01
014-0011-04
014-0037-04
014-0037-05
014-0037-06
014-0037-07
014-0037-08
014-0037-09
014-0037-10
014-0037-11
014-0037-12
014-0037-13
014-0037-14
014-0037-16
014-0037-17
014-0037-18
014-0037-19
014-0037-22
014-0037-28
014-0037-36
014-0037-37
014-0037-38
014-0037-39
014-0037-40
MFD
5
11
10
12.5
15
17.5
20
25
30
35
40
15
20
30
35
40
45
60
35
45
60
80
55
50
Cap
Volts
330
330
370
370
370
370
370
370
370
370
370
440
440
440
440
440
440
440
370
370
370
370
370
370
Wholesaler
P/N
914-0036-03
914-0037-04
Copeland®
Brand P/N
014-0041-00
014-0041-01
014-0048-12
014-0048-18
014-0048-20
014-0048-21
014-0048-22
014-0048-36
014-0048-37
014-0048-38
014-0048-39
014-0048-40
014-0048-51
014-0054-12
014-0054-18
014-0054-20
014-0054-36
014-0054-37
014-0054-39
014-0054-40
014-0057-00
014-0058-31
014-0064-00
014-0064-01
MFD
60
80
40
40
50
55
60
45
60
80
55
50
70
40
40
50
45
60
55
50
100
88
10
12.5
Cap
Volts
370
370
370
440
440
440
440
370
370
370
370
370
370
370
440
440
370
370
370
370
440
330
370
370
E21
Section E.indd 21
2/26/2008 11:02:33 AM
Run Capacitor Data
Wholesaler
P/N
914-0037-06
914-0037-07
914-0037-08
914-0037-09
914-0037-10
914-0037-11
914-0037-12
914-0037-13
914-0037-14
914-0037-15
914-0037-16
914-0037-17
914-0037-18
914-0037-19
914-0037-20
914-0037-21
914-0037-22
914-0037-23
914-0037-29
914-0037-30
914-0037-36
914-0037-37
914-0037-38
914-0037-39
Copeland®
Brand P/N
014-0064-02
014-0064-03
014-0064-04
014-0064-05
014-0064-06
014-0064-07
014-0064-08
014-0064-09
014-0064-10
014-0064-11
014-0064-12
014-0064-13
014-0064-14
014-0064-15
014-0064-16
014-0064-17
014-0064-18
014-0064-19
014-0064-23
014-0064-24
014-0064-25
014-0064-26
014-0064-27
014-0064-28
MFD
15
17.5
20
25
30
35
40
15
20
25
30
35
40
45
50
55
60
25
7.5
5
45
60
80
55
Cap
Volts
370
370
370
370
370
370
370
440
440
440
440
440
440
440
440
440
440
482
330
330
370
370
370
370
Wholesaler
P/N
914-0037-40
914-0037-46
914-0037-48
914-0037-49
914-0037-50
914-0037-51
914-0037-52
Copeland®
Brand P/N
014-0064-29
014-0064-30
014-0064-31
014-0064-32
014-0064-33
014-0064-34
014-0064-35
014-0064-36
MFD
50
80
15
20
17.5
70
80
10
Cap
Volts
370
370
440
440
440
370
440
440
E22
Section E.indd 22
2/26/2008 11:02:33 AM
SECTION F
COMPRESSOR ELECTRICAL DATA
TOPICS
Introduction .................................................................. F2
A-Line .......................................................................... FA
Welded Compressors .................................................. FB
Copelametic Air-Cooled ...............................................FC
Copelametic Small Refrigerant-Cooled .......................FD
Copelametic Large Refrigerant-Cooled ....................... FE
Copeland Scroll ........................................................... FF
Copeland Screw ..........................................................FG
This section contains current information on Copeland®
products.
Information on obsolete models can be obtained from your local
Emerson Climate Technologies, Inc. wholesaler.
Section F TOC.indd 1
2/5/2008 10:00:51 AM
Introduction
The electrical data is listed as an aid to the serviceman
in determining compressor characteristics.
As required by U.L. requirements based on the National
Electric Code, the terms nameplate amperage and full
load amps have been replaced by the term “Rated Load
Amps” (RLA). The value shown on the compressor
nameplate is complicated by the fact that while normal
operating amperage draw can be determined on a complete system by test, a compressor could really have an
infinite number of operating conditions depending on its
application.
In order to provide a uniform basis of 71% of maximum
continuous current allowed by the motor protection system. This will allow the compressor to draw 140% of the
rated load amp value prior to the protector tripping.
Rated Load Amp values are not marked on new Copelametic, welded or scroll compressor nameplates unless otherwise specified by an equipment manufacturer.
Since one motor design may be used in a number of
different compressor models, using different refrigerants,
for different operating ranges, the Rated Load Amp value
shown in the handbook may vary from the value marked
on individual compressor nameplates. The handbook
value is usually selected as the highest nameplate
value used for a given motor, so it is always a conservative value which may be safely used in the event exact
nameplate values are not known.
If refrigerant application specific RLA is required, this
can be calculated from refrigerant application specific
Maximum Continuous Current (MCC) listed in Emerson
Climate Technologies, Inc. Online Product Information
(OPI).
F2
Section F TOC.indd 2
2/5/2008 10:00:56 AM
Explanation of Section F Electrical Data Notes
The following notes can be found in the headings
for the data tables which are found later in this section:
Copelametic compressors may have the ninth
digit changed to represent variations that do not
affect performance.
An “E” at the ninth digit means the compressor was
originally shipped with polyolester oil.
An “A” at the ninth digit means the compressor was
originally shipped with alkyl benzene oil.
A “number” at the ninth digit means the compressor was originally shipped with mineral oil.
An “L” at the ninth digit means the compressor was
originally shipped with no oil.
Information on Line to Line winding resistances
is found in Section A “Measuring Winding Resistance”.
Capacitor values are found in Section E.
Potential and Current relay values are found in
Section E.
*
RP = Relay Potential
*
RC = Relay Current
Large refrigerant cooled compressors whose
overload protectors are not listed have Emerson
Climate Technologies part numbers:
F3
Section F TOC.indd 3
2/5/2008 10:00:56 AM
071-0424-01
071-0424-00
071-0524-00
071-0464-01
071-0464-00
120V
240V
120V/240V
120V
240V
(Texas Instruments)
(Texas Instruments)
(Texas Instruments)
(Kriwan)
(Kriwan)
071-0441-01 120V
071-0441-00 240V
(Robertshaw)
(Robertshaw)
071-0520-03
071-0520-00
071-0520-01
071-0520-02
071-0520-04
071-0520-05
071-0550-00
071-0550-01
071-0582-00
071-0581-00
(Texas Instruments)
(Texas Instruments)
(Kriwan)
(Kriwan)
(Kriwan)
(Kriwan)
(Kriwan)
(Texas Instruments)
(Kriwan)
(Kriwan)
24V
120V/240V
230V
115V
24V
120V/240V
120V/240V
24V
120/240V
120/240V
F4
Section F TOC.indd 4
2/5/2008 10:00:56 AM
Electrical Data - A-Line
Model
AFB04C3E-SAA
AFB05C3E-IAA
AFB05C3E-SAA
AFB06C3E-IAA
AFB09C3E-IAA
AFB09C3E-IAB
AFE06C4E-IAA
AFE07C3E-IAA
AFE08C4E-IAA
AFE10C3E-IAA
AFE11C3E-IAA
AFE11C4E-IAA
AFE12C3E-IAA
AFE13C3E-IAA
AFE13C3E-IAV
AFE13C4E-IAA
AFE17C4E-CAA
AFE17C4E-IAA
AFJ23C1-IAA
AFJ23C2-IAA
AFJ31C1E-CFV
AFJ31C2E-CFV
AFJ37C1E-CFV
AFJ37C2E-CFV
AFT12C1-IAA
Max LRA
Volts PH RLA
115
115
115
115
115
230
115
115
115
115
115
115
115
115
208/230
115
115
115
115
115
208/230
208/230
208/230
208/230
115
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2.8
2.7
3.1
4.8
1.7
3.1
4.4
3.9
4.9
5.6
4.2
4.8
5.8
3.2
5.6
7.8
7.8
7.2
9.2
5.4
7.5
6.2
8
5
20
26.5
27.5
25
34.6
15
28.5
29
26.5
38
29
26.5
33
33
21.7
37.5
41.5
41.5
59
54
40
44
40
46
30
Resistance
Start or
Run
Line/Line
10.5
8.5
8.5
7.4
9
36
6.14
9
6.14
9
7.3
6.14
6.1
6.1
21.9
6.1
4.5
4.5
4.771
4.771
6
6
6
6
6.51
2.7
1.9
1.9
1.55
1.05
5.85
1.24
1.3
1.24
1.2
1.2
1.24
0.96
0.96
3.4
0.96
0.77
0.77
0.611
0.611
1.2
1.2
1.2
1.2
0.99
Start Cap
P/N
Run Cap
P/N
014-0053-21
014-0053-26
014-0053-26
014-0059-13
014-0053-18
014-0053-26
014-0053-18
014-0053-26
014-0053-18
014-0053-18
014-0053-21
014-0053-21
014-0059-13
014-0053-21
014-0036-28
014-0053-21
014-0036-24
014-0036-24
014-0053-18
014-0064-12
014-0064-10
014-0064-10
014-0064-10
014-0064-10
Relay
P/N
Part
Type*
Protector
P/N
040-0162-13
040-0150-05
040-0162-05
040-0150-02
040-0150-20
040-0150-03
040-0150-19
040-0150-01
040-0150-31
040-0150-11
040-0150-01
040-0150-19
040-0150-06
040-0150-06
040-0150-14
040-0150-06
040-0166-21
040-0150-11
040-0166-38
040-0166-38
040-0166-29
040-0166-29
040-0166-29
040-0166-29
040-0150-06
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RP
RC
RP
RP
RP
RP
RP
RP
RC
071-0561-13
071-0561-08
071-0561-08
071-0561-11
071-0561-15
071-0561-30
071-0561-29
071-0561-02
071-0561-23
071-0561-24
071-0561-16
071-0561-21
071-0561-28
071-0561-03
071-0561-04
071-0561-47
071-0561-48
071-0561-48
071-0605-03
071-0644-02
071-0603-14
* See Section F Introduction for more information.
FA1
Section_Fa.indd 1
3/4/2008 7:45:36 AM
Electrical Data - A-Line
Model
AFT12C1E-IAA
AFT12C1E-IAV
AFT18C1E-IAA
AFT18C1E-IAV
AFT22C1E-CFV
AFT22C1E-IAA
AFT26C1E-CFA
AFT26C1E-CFV
AFT29C1E-CFA
AFT29C1E-CFV
ARB10C3-SAA
ARB13C3-SAA
ARB13C3E-IAA
ARB13C3E-SAA
ARB17C3-SAA
ARB17C3E-IAA
ARB17C3E-SAA
ARB21C3-IAA
ARB26C3-IAA
ARB26C3-IAV
ARE25C3-SAA
ARE25C3E-IAA
ARE25C3E-SAA
ARE27C3-IAA
ARE27C3-SAA
Max LRA
Volts PH RLA
115
208/230
115
208/230
208/230
115
115
208/230
115
208/230
115
115
115
115
115
115
115
115
115
208/230
115
115
115
115
115
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
5.1
3.5
7.9
4.1
3.7
9.2
8.8
4.6
9.7
5
2.5
2.8
2.8
2.8
3.8
3.5
3.8
4.6
5
3.1
4.5
4.7
4.5
4.9
5
30
21.5
51
30
32.5
55
72
32.2
74
33
17
20
15.1
20
23
19.3
23
26.5
29
15.5
25
21.5
25
25
31
Resistance
Start or
Run
Line/Line
6.51
6.4
4.25
9
5.3
3.8
4.03
5.3
3.91
5.3
14.85
10.5
10.7
10.5
13.2
9.1
13.2
8
7.3
21.35
18.45
8.3
18.45
7.4
11.1
0.99
3.54
0.7
2.3
2.1
0.54
0.6
2.3
0.49
2.3
3.3
2.7
3
2.7
2.4
2.4
2.4
1.4
1.4
5.1
2
2
2
1.55
1.55
Start Cap
P/N
014-0053-21
014-0059-09
014-0053-26
014-0053-30
014-0058-31
014-0053-18
014-0058-32
014-0058-38
014-0058-31
014-0053-18
014-0053-18
014-0053-18
014-0059-14
014-0059-13
014-0053-18
014-0053-18
Run Cap
P/N
014-0064-09
014-0064-11
014-0064-09
014-0064-11
014-0064-09
Relay
P/N
Part
Type*
Protector
P/N
040-0163-08
040-0163-01
040-0163-07
040-0163-02
040-0166-39
040-0172-00
040-0166-37
040-0166-13
040-0166-37
040-0166-13
040-0162-08
040-0162-08
040-0150-16
040-0162-08
040-0162-11
040-0150-15
040-0162-11
040-0150-19
040-0150-24
040-0163-00
040-0162-01
040-0150-10
040-0162-01
040-0150-02
040-0162-07
RC
RC
RC
RC
RP
RC
RP
RP
RP
RP
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
071-0603-08
071-0603-01
071-0603-11
071-0603-03
071-0605-00
071-0561-18
071-0561-25
071-0561-25
071-0561-25
071-0561-09
071-0561-09
071-0561-09
071-0561-01
071-0561-26
071-0561-09
071-0561-23
071-0561-23
071-0561-23
071-0561-23
071-0561-23
* See Section F Introduction for more information.
FA2
Section_Fa.indd 2
3/4/2008 7:45:46 AM
Electrical Data - A-Line
Model
ARE27C3E-IAA
ARE27C3E-SAA
ARE29C4E-IAA
ARE34C4E-IAA
ARE35C3-IAA
ARE35C3-IAV
ARE36C3-IAA
ARE36C3-SAA
ARE37C3-IAA
ARE37C3-SAA
ARE37C3E-IAA
ARE37C3E-IAV
ARE37C3E-SAA
ARE40C4E-IAA
ARE41C3-IAA
ARE41C3-SAA
ARE41C3E-IAA
ARE41C3E-IAV
ARE43C3-IAA
ARE46C4E-IAA
ARE47C3-IAA
ARE47C3-IAV
ARE59C3-CAA
ARE59C3-CAV
ARJ10K1-CAV
Max LRA
Volts PH RLA
115
115
115
115
115
208/230
115
115
115
115
115
208/230
115
115
115
115
115
208/230
115
115
115
208/230
115
208/230
208/230
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4.9
5
3.9
4.6
7
3.6
6.7
6.5
7.2
7.2
7.2
3.4
7.2
7
7.5
4.7
7.5
3.9
7.1
9
7
4.5
8
4
7
25
31
28.5
37
34.6
18.2
29
34
29
35
29
17.3
35
37
37.5
41
37.5
23.8
29
40
38.5
25.8
36
25.9
37
Resistance
Start or
Run
Line/Line
7.4
11.1
6.14
6.1
9
25.6
7.3
13.55
7.3
13.65
7.3
21.4
13.65
6.1
10.6
8.8
10.6
21.25
7.3
5.5
5.62
21.86
7.5
10.45
7.6
1.55
1.55
1.24
0.96
1.05
4.7
1.2
1.4
1.2
1.2
1.2
4.8
1.2
0.96
1
1.1
1
3.4
1.2
0.86
0.85
2.92
1.2
3.05
1.8
Start Cap
P/N
Run Cap
P/N
Relay
P/N
Part
Type*
Protector
P/N
014-0064-10
014-0064-09
014-0064-10
040-0150-02
040-0162-07
040-0150-19
040-0150-06
040-0150-20
040-0150-25
040-0150-01
040-0162-03
040-0150-01
040-0162-03
040-0150-01
040-0150-04
040-0162-03
040-0150-33
040-0150-06
040-0162-14
040-0150-06
040-0150-18
040-0150-01
040-0150-11
040-0150-01
040-0150-13
040-0166-45
040-0166-30
040-0166-27
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RP
RP
RP
071-0561-23
071-0561-23
071-0561-21
071-0561-50
071-0561-03
071-0561-01
071-0561-16
071-0561-16
071-0561-16
071-0561-16
071-0561-16
071-0561-00
071-0561-16
071-0561-03
071-0561-32
071-0561-17
071-0561-32
071-0561-00
071-0561-17
071-0561-51
071-0561-17
071-0561-00
071-0561-07
071-0561-10
071-0563-00
014-0053-18
014-0053-18
014-0053-21
014-0053-18
014-0059-13
014-0059-01
014-0053-18
014-0053-21
014-0053-30
014-0053-25
014-0053-21
014-0053-21
014-0053-29
014-0053-18
014-0053-25
014-0053-26
014-0053-29
014-0058-37
014-0058-25
014-0058-31
* See Section F Introduction for more information.
FA3
Section_Fa.indd 3
3/4/2008 7:45:46 AM
Electrical Data - A-Line
Model
ARJ10K1-TFD
ARJ11K1-CAV
ARJ11K1E-CAV
ARJ11K1E-TFD
ARJ11K2-CAV
ARJ11K2E-CAV
ARJ13K1-CAB
ARJ84C1-IAA
ARJ84C1-IAV
ARJ84C1E-IAV
ARJ84C1E-TFD
ARJ84C2-IAA
ARJ84C2-IAV
ARJ84C2E-IAV
ART51C1-IAA
ART51C1E-IAA
ART51C1E-IAV
ART62C1-IAA
ART62C1E-IAA
ART62C1E-IAV
ART64C1E-IAA
ART64C1E-IAV
ART69C1-IAA
ART69C1-IAV
ART82C1-CAA
Max LRA
Volts PH RLA
440/480
208/230
208/230
440/480
208/230
208/230
230
115
208/230
208/230
440/480
115
208/230
208/230
115
115
208/230
115
115
208/230
115
208/230
115
208/230
115
3
1
1
3
1
1
1
1
1
1
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2.1
7.3
7.4
2.3
8.5
8.5
6
13.6
7.2
7.4
1.8
11.4
8
8
9.3
9.3
5
10.3
10.2
5.4
11
6
13
6.1
11.8
10
40
43
13
41
41
40
72
38
42
10
73
42
42
36
36
30
51
51
30
51
30
55
30
72
Resistance
Start or
Run
Line/Line
18.6
8.1
8.1
14.87
8.1
8.1
5.4
2.85
11.2
8.09
18.6
2.85
8.09
8.09
3.4
3.4
9
4.25
4.25
9
4.25
16
4.1
9
4.15
0
1.45
1.45
0
1.45
1.45
1.75
0.44
2
1.4
0
0.44
1.4
1.4
1.05
1.05
2.3
0.7
0.7
2.3
0.7
2.21
0.54
2.3
0.6
Start Cap
P/N
Run Cap
P/N
Relay
P/N
Part
Type*
Protector
P/N
014-0058-25
014-0058-25
014-0064-03
014-0064-33
040-0166-24
040-0166-24
RP
RP
071-0604-05
071-0604-04
014-0058-25
014-0058-25
014-0058-31
014-0036-23
014-0058-31
014-0058-31
014-0064-33
014-0064-33
014-0064-10
040-0166-24
040-0166-24
040-0166-05
040-0166-38
040-0172-02
040-0172-02
RP
RP
RP
RP
RC
RC
071-0604-11
071-0604-11
071-C100-10
071-0605-01
071-0604-03
071-0604-03
040-0166-38
040-0172-02
040-0172-02
040-0163-04
040-0163-04
040-0163-02
040-0163-05
040-0163-05
040-0163-02
040-0163-07
040-0163-02
040-0172-03
040-0163-02
040-0166-37
RP
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RP
071-0605-01
071-0604-11
071-0604-11
071-0603-02
071-0603-02
071-0603-09
071-0603-05
071-0603-05
071-0603-07
071-0603-10
071-0603-15
071-0605-05
071-0603-13
071-0605-03
014-0036-23
014-0058-31
014-0058-31
014-0053-21
014-0038-04
014-0058-18
014-0053-25
014-0053-25
014-0058-18
014-0053-25
014-0058-32
014-0053-30
014-0058-32
014-0064-13
* See Section F Introduction for more information.
FA4
Section_Fa.indd 4
3/4/2008 7:45:47 AM
Electrical Data - A-Line
Model
ART82C1-CAV
ART82C1-CFB
ART97C1-CAA
ART97C1-CAV
ART97C1-PAA
ART97C1-PAV
ASB12C3E-IAA
ASB14C3E-IAA
ASE19C3E-IAA
ASE19C4E-IAA
ASE20C4E-CAA
ASE20C4E-IAA
ASE21C3E-IAA
ASE24C3E-IAA
ASE24C3E-IAV
ASE26C4E-CAA
ASE26C4E-IAA
ASE32C3E-CAA
ASE32C3E-CAV
ASE35C4E-CAA
ASE35C4E-IAA
ASJ58C1E-CAV
AST40C1E-IAA
AST40C1E-IAV
AST45C1E-CAV
Max LRA
Volts PH RLA
208/230
230
115
208/230
115
208/230
115
115
115
115
115
115
115
115
208/230
115
115
115
208/230
115
115
208/230
115
208/230
208/230
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
5.9
30
5.1
31
14
71
7
34
11.2
50
5.6 31.5
5.2 26.5
6.8 29.75
8 34.6
5.6 26.5
5.5 30.5
5.2 26.5
7
29
6
29
4.2 16.8
7.5
38
7.5
38
9.2 33.6
4.9 24.8
12
51
12
51
8.4
34
13
55
6.9
30
6.5
30
Resistance
Start or
Run
Line/Line
9.06
11.6
3.944
9.68
6.28
2.94
2.5
0.461
1.97
0.58
8
7.3
9
6.14
6.14
6.14
7.3
7.3
7.48
6.1
6.1
7.3
11.6
5.2
5.2
7.6
3.8
16
9.06
1.4
1.2
1.05
1.24
1.24
1.24
1.2
1.2
4.55
0.96
0.96
1.2
3.2
0.67
0.67
1.8
0.54
2.21
2.94
Start Cap
P/N
Run Cap
P/N
Relay
P/N
Part
Type*
Protector
P/N
014-0058-21
014-0058-31
014-0058-38
014-0058-21
014-0036-13
014-0036-13
014-0053-26
014-0053-18
014-0053-18
014-0053-18
014-0058-32
014-0053-26
014-0053-26
014-0053-26
014-0059-09
014-0036-28
014-0053-21
014-0058-25
014-0058-31
014-0036-28
014-0053-21
014-0058-31
014-0058-32
014-0058-31
014-0058-21
014-0064-09
014-0064-09
014-0064-11
014-0064-09
014-0064-11
014-0064-10
040-0166-27
040-0166-04
040-0166-03
040-0166-27
040-0166-37
040-0166-27
040-0150-19
040-0150-01
040-0150-20
040-0150-32
040-0166-21
040-0150-19
040-0150-01
RP
RP
RP
RP
RP
RP
RC
RC
RC
RC
RP
RC
RC
071-0604-01
040-0150-04
040-0166-21
040-0163-04
040-0166-45
040-0166-13
040-0166-37
040-0150-11
040-0166-18
040-0172-03
040-0163-02
040-0166-27
RC
RP
RC
RP
RP
RP
RC
RP
RC
RC
RP
014-0064-10
014-0064-11
014-0064-10
014-0064-09
014-0064-12
014-0064-10
014-0064-09
071-0605-02
071-0604-08
071-0605-02
071-0604-06
071-0561-01
071-0561-26
071-0561-21
071-0561-21
071-0561-21
071-0561-21
071-0561-21
071-0561-07
071-0561-29
071-0561-03
071-0561-03
071-0561-07
071-0561-12
071-0561-49
071-0561-49
071-0563-00
071-0605-05
071-0603-13
071-0604-01
* See Section F Introduction for more information.
FA5
Section_Fa.indd 5
3/4/2008 7:45:47 AM
Electrical Data - A-Line
Model
AST45C1E-IAA
AST54C1E-CAA
AST54C1E-CAV
Max LRA
Volts PH RLA
115
115
208/230
1
1
1
15
15
5.8
55
71
34
Resistance
Start or
Run
Line/Line
4.1
3.944
9.68
0.54
0.461
1.97
Start Cap
P/N
Run Cap
P/N
Relay
P/N
Part
Type*
Protector
P/N
014-0058-32
014-0058-38
014-0058-21
014-0064-11
014-0064-09
040-0172-03
040-0166-03
040-0166-27
RC
RP
RP
071-0605-03
071-0605-04
071-0604-07
* See Section F Introduction for more information.
FA6
Section_Fa.indd 6
3/4/2008 7:45:48 AM
Electrical Data - Welded Compressors
Model
Volts
AFB04C3E-SAA
AFB05C3E-IAA
AFB05C3E-SAA
AFB06C3E-IAA
AFB09C3E-IAA
AFB09C3E-IAB
AFE06C4E-IAA
AFE07C3E-IAA
AFE08C4E-IAA
AFE10C3E-IAA
AFE11C3E-IAA
AFE11C4E-IAA
AFE12C3E-IAA
AFE13C3E-IAA
AFE13C3E-IAV
AFE13C4E-IAA
AFE17C4E-CAA
AFE17C4E-IAA
AFJ23C1-IAA
AFJ23C2-IAA
AFJ31C1E-CFV
AFJ31C2E-CFV
AFJ37C1E-CFV
AFJ37C2E-CFV
AFT12C1-IAA
AFT12C1E-IAA
115
115
115
115
115
230
115
115
115
115
115
115
115
115
208/230
115
115
115
115
115
208/230
208/230
208/230
208/230
115
115
Resistance
Max
PH RLA LRA
Start or
Run
Line/Line
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2.8
2.7
3.1
4.8
1.7
3.1
4.4
3.9
4.9
5.6
4.2
4.8
5.8
3.2
5.6
7.8
7.8
7.2
9.2
5.4
7.5
6.2
8
5
5.1
20
2.7
26.5
1.9
27.5
1.9
25 1.55
34.6 1.05
15 5.85
28.5 1.24
29
1.3
26.5 1.24
38
1.2
29
1.2
26.5 1.24
33 0.96
33 0.96
21.7
3.4
37.5 0.96
41.5 0.77
41.5 0.77
59 0.611
54 0.611
40
1.2
44
1.2
40
1.2
46
1.2
30 0.99
30 0.99
10.5
8.5
8.5
7.4
9
36
6.14
9
6.14
9
7.3
6.14
6.1
6.1
21.9
6.1
4.5
4.5
4.771
4.771
6
6
6
6
6.51
6.51
Start Cap
P/N
Run Cap
P/N
014-0053-21
014-0053-26
014-0053-26
014-0059-13
014-0053-18
014-0053-26
014-0053-18
014-0053-26
014-0053-18
014-0053-18
014-0053-21
014-0053-21
014-0059-13
014-0053-21
014-0036-28
014-0053-21
014-0036-24
014-0036-24
014-0053-18
014-0053-21
014-0064-12
014-0064-10
014-0064-10
014-0064-10
014-0064-10
Relay
P/N
Part
Type*
040-0162-13
040-0150-05
040-0162-05
040-0150-02
040-0150-20
040-0150-03
040-0150-19
040-0150-01
040-0150-31
040-0150-11
040-0150-01
040-0150-19
040-0150-06
040-0150-06
040-0150-14
040-0150-06
040-0166-21
040-0150-11
040-0166-38
040-0166-38
040-0166-29
040-0166-29
040-0166-29
040-0166-29
040-0150-06
040-0163-08
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RP
RC
RP
RP
RP
RP
RP
RP
RC
RC
Protector
P/N
071-0561-13
071-0561-08
071-0561-08
071-0561-11
071-0561-15
071-0561-30
071-0561-29
071-0561-02
071-0561-23
071-0561-24
071-0561-16
071-0561-21
071-0561-28
071-0561-03
071-0561-04
071-0561-47
071-0561-48
071-0561-48
071-0605-03
071-0644-02
071-0603-14
071-0603-08
* See Section F Introduction for more information.
FB1
Section_Fb.indd 1
3/4/2008 7:57:08 AM
Electrical Data - Welded Compressors
Model
Volts
AFT12C1E-IAV
AFT18C1E-IAA
AFT18C1E-IAV
AFT22C1E-CFV
AFT22C1E-IAA
AFT26C1E-CFA
AFT26C1E-CFV
AFT29C1E-CFA
AFT29C1E-CFV
ARB10C3-SAA
ARB13C3-SAA
ARB13C3E-IAA
ARB13C3E-SAA
ARB17C3-SAA
ARB17C3E-IAA
ARB17C3E-SAA
ARB21C3-IAA
ARB26C3-IAA
ARB26C3-IAV
ARE25C3-SAA
ARE25C3E-IAA
ARE25C3E-SAA
ARE27C3-IAA
ARE27C3-SAA
ARE27C3E-IAA
ARE27C3E-SAA
208/230
115
208/230
208/230
115
115
208/230
115
208/230
115
115
115
115
115
115
115
115
115
208/230
115
115
115
115
115
115
115
Resistance
Max
PH RLA LRA
Start or
Run
Line/Line
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3.5
7.9
4.1
3.7
9.2
8.8
4.6
9.7
5
2.5
2.8
2.8
2.8
3.8
3.5
3.8
4.6
5
3.1
4.5
4.7
4.5
4.9
5
4.9
5
21.5
51
30
32.5
55
72
32.2
74
33
17
20
15.1
20
23
19.3
23
26.5
29
15.5
25
21.5
25
25
31
25
31
3.54
0.7
2.3
2.1
0.54
0.6
2.3
0.49
2.3
3.3
2.7
3
2.7
2.4
2.4
2.4
1.4
1.4
5.1
2
2
2
1.55
1.55
1.55
1.55
6.4
4.25
9
5.3
3.8
4.03
5.3
3.91
5.3
14.85
10.5
10.7
10.5
13.2
9.1
13.2
8
7.3
21.35
18.45
8.3
18.45
7.4
11.1
7.4
11.1
Start Cap
P/N
014-0059-09
014-0053-26
014-0053-30
014-0058-31
014-0053-18
014-0058-32
014-0058-38
014-0058-31
014-0053-18
014-0053-18
014-0053-18
014-0059-14
014-0059-13
014-0053-18
014-0053-18
014-0053-18
Run Cap
P/N
014-0064-09
014-0064-11
014-0064-09
014-0064-11
014-0064-09
Relay
P/N
040-0163-01
040-0163-07
040-0163-02
040-0166-39
040-0172-00
040-0166-37
040-0166-13
040-0166-37
040-0166-13
040-0162-08
040-0162-08
040-0150-16
040-0162-08
040-0162-11
040-0150-15
040-0162-11
040-0150-19
040-0150-24
040-0163-00
040-0162-01
040-0150-10
040-0162-01
040-0150-02
040-0162-07
040-0150-02
040-0162-07
Part
Type*
RC
RC
RC
RP
RC
RP
RP
RP
RP
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
Protector
P/N
071-0603-01
071-0603-11
071-0603-03
071-0605-00
071-0561-18
071-0561-25
071-0561-25
071-0561-25
071-0561-09
071-0561-09
071-0561-09
071-0561-01
071-0561-26
071-0561-09
071-0561-23
071-0561-23
071-0561-23
071-0561-23
071-0561-23
071-0561-23
071-0561-23
* See Section F Introduction for more information.
FB2
Section_Fb.indd 2
3/4/2008 7:57:14 AM
Electrical Data - Welded Compressors
Model
Volts
ARE29C4E-IAA
ARE34C4E-IAA
ARE35C3-IAA
ARE35C3-IAV
ARE36C3-IAA
ARE36C3-SAA
ARE37C3-IAA
ARE37C3-SAA
ARE37C3E-IAA
ARE37C3E-IAV
ARE37C3E-SAA
ARE40C4E-IAA
ARE41C3-IAA
ARE41C3-SAA
ARE41C3E-IAA
ARE41C3E-IAV
ARE43C3-IAA
ARE46C4E-IAA
ARE47C3-IAA
ARE47C3-IAV
ARE59C3-CAA
ARE59C3-CAV
ARJ10K1-CAV
ARJ10K1-TFD
ARJ11K1-CAV
ARJ11K1E-CAV
115
115
115
208/230
115
115
115
115
115
208/230
115
115
115
115
115
208/230
115
115
115
208/230
115
208/230
208/230
440/480
208/230
208/230
Resistance
Max
PH RLA LRA
Start or
Run
Line/Line
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3
1
1
3.9
4.6
7
3.6
6.7
6.5
7.2
7.2
7.2
3.4
7.2
7
7.5
4.7
7.5
3.9
7.1
9
7
4.5
8
4
7
2.1
7.3
7.4
28.5
37
34.6
18.2
29
34
29
35
29
17.3
35
37
37.5
41
37.5
23.8
29
40
38.5
25.8
36
25.9
37
10
40
43
1.24
0.96
1.05
4.7
1.2
1.4
1.2
1.2
1.2
4.8
1.2
0.96
1
1.1
1
3.4
1.2
0.86
0.85
2.92
1.2
3.05
1.8
0
1.45
1.45
6.14
6.1
9
25.6
7.3
13.55
7.3
13.65
7.3
21.4
13.65
6.1
10.6
8.8
10.6
21.25
7.3
5.5
5.62
21.86
7.5
10.45
7.6
18.6
8.1
8.1
Start Cap
P/N
Run Cap
P/N
Relay
P/N
Part
Type*
014-0053-21
014-0053-29
014-0053-18
014-0053-25
014-0053-26
014-0053-29
014-0058-37
014-0058-25
014-0058-31
014-0064-10
014-0064-09
014-0064-10
040-0150-19
040-0150-06
040-0150-20
040-0150-25
040-0150-01
040-0162-03
040-0150-01
040-0162-03
040-0150-01
040-0150-04
040-0162-03
040-0150-33
040-0150-06
040-0162-14
040-0150-06
040-0150-18
040-0150-01
040-0150-11
040-0150-01
040-0150-13
040-0166-45
040-0166-30
040-0166-27
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RP
RP
RP
071-0561-21
071-0561-50
071-0561-03
071-0561-01
071-0561-16
071-0561-16
071-0561-16
071-0561-16
071-0561-16
071-0561-00
071-0561-16
071-0561-03
071-0561-32
071-0561-17
071-0561-32
071-0561-00
071-0561-17
071-0561-51
071-0561-17
071-0561-00
071-0561-07
071-0561-10
071-0563-00
014-0058-25
014-0058-25
014-0064-03
014-0064-33
040-0166-24
040-0166-24
RP
RP
071-0604-05
071-0604-04
014-0053-18
014-0053-21
014-0053-18
014-0059-13
014-0059-01
014-0053-18
014-0053-21
014-0053-30
014-0053-25
014-0053-21
Protector
P/N
* See Section F Introduction for more information.
FB3
Section_Fb.indd 3
3/4/2008 7:57:14 AM
Electrical Data - Welded Compressors
Model
Volts
ARJ11K1E-TFD
ARJ11K2-CAV
ARJ11K2E-CAV
ARJ13K1-CAB
ARJ84C1-IAA
ARJ84C1-IAV
ARJ84C1E-IAV
ARJ84C1E-TFD
ARJ84C2-IAA
ARJ84C2-IAV
ARJ84C2E-IAV
ART51C1-IAA
ART51C1E-IAA
ART51C1E-IAV
ART62C1-IAA
ART62C1E-IAA
ART62C1E-IAV
ART64C1E-IAA
ART64C1E-IAV
ART69C1-IAA
ART69C1-IAV
ART82C1-CAA
ART82C1-CAV
ART82C1-CFB
ART97C1-CAA
ART97C1-CAV
440/480
208/230
208/230
230
115
208/230
208/230
440/480
115
208/230
208/230
115
115
208/230
115
115
208/230
115
208/230
115
208/230
115
208/230
230
115
208/230
Resistance
Max
PH RLA LRA
Start or
Run
Line/Line
3
1
1
1
1
1
1
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2.3
8.5
8.5
6
13.6
7.2
7.4
1.8
11.4
8
8
9.3
9.3
5
10.3
10.2
5.4
11
6
13
6.1
11.8
5.9
5.1
14
7
13
0
41 1.45
41 1.45
40 1.75
72 0.44
38
2
42
1.4
10
0
73 0.44
42
1.4
42
1.4
36 1.05
36 1.05
30
2.3
51
0.7
51
0.7
30
2.3
51
0.7
30 2.21
55 0.54
30
2.3
72
0.6
30 2.94
31
2.5
71 0.461
34 1.97
14.87
8.1
8.1
5.4
2.85
11.2
8.09
18.6
2.85
8.09
8.09
3.4
3.4
9
4.25
4.25
9
4.25
16
4.1
9
4.15
9.06
11.6
3.944
9.68
Start Cap
P/N
014-0058-25
014-0058-25
014-0058-31
014-0036-23
014-0058-31
014-0058-31
Run Cap
P/N
014-0064-33
014-0064-33
014-0064-10
014-0036-23
014-0058-31
014-0058-31
014-0053-21
014-0038-04
014-0058-18
014-0053-25
014-0053-25
014-0058-18
014-0053-25
014-0058-32
014-0053-30
014-0058-32
014-0058-21
014-0058-31
014-0058-38
014-0058-21
014-0064-13
014-0064-09
014-0064-09
014-0064-11
014-0064-09
Relay
P/N
Part
Type*
Protector
P/N
040-0166-24
040-0166-24
040-0166-05
040-0166-38
040-0172-02
040-0172-02
RP
RP
RP
RP
RC
RC
071-0604-11
071-0604-11
071-C100-10
071-0605-01
071-0604-03
071-0604-03
040-0166-38
040-0172-02
040-0172-02
040-0163-04
040-0163-04
040-0163-02
040-0163-05
040-0163-05
040-0163-02
040-0163-07
040-0163-02
040-0172-03
040-0163-02
040-0166-37
040-0166-27
040-0166-04
040-0166-03
040-0166-27
RP
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RC
RP
RP
RP
RP
RP
071-0605-01
071-0604-11
071-0604-11
071-0603-02
071-0603-02
071-0603-09
071-0603-05
071-0603-05
071-0603-07
071-0603-10
071-0603-15
071-0605-05
071-0603-13
071-0605-03
071-0604-01
071-0605-02
071-0604-08
* See Section F Introduction for more information.
FB4
Section_Fb.indd 4
3/4/2008 7:57:15 AM
Electrical Data - Welded Compressors
Model
Volts
ART97C1-PAA
ASB12C3E-IAA
ASB14C3E-IAA
ASE19C3E-IAA
ASE19C4E-IAA
ASE20C4E-CAA
ASE20C4E-IAA
ASE21C3E-IAA
ASE24C3E-IAA
ASE24C3E-IAV
ASE26C4E-CAA
ASE26C4E-IAA
ASE32C3E-CAA
ASE32C3E-CAV
ASE35C4E-CAA
ASE35C4E-IAA
ASJ58C1E-CAV
AST40C1E-IAA
AST40C1E-IAV
AST45C1E-CAV
AST45C1E-IAA
AST54C1E-CAA
AST54C1E-CAV
CF04K6E-PFV
CF04K6E-TF5
CF04K6E-TFD
115
115
115
115
115
115
115
115
115
208/230
115
115
115
208/230
115
115
208/230
115
208/230
208/230
115
115
208/230
208/230
200/230
380/460
Resistance
Max
PH RLA LRA
Start or
Run
Line/Line
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3
3
11.2
5.2
6.8
8
5.6
5.5
5.2
7
6
4.2
7.5
7.5
9.2
4.9
12
12
8.4
13
6.9
6.5
15
15
5.8
9.6
6.8
3.3
50 0.58
26.5
1.4
29.75
1.2
34.6 1.05
26.5 1.24
30.5 1.24
26.5 1.24
29
1.2
29
1.2
16.8 4.55
38 0.96
38 0.96
33.6
1.2
24.8
3.2
51 0.67
51 0.67
34
1.8
55 0.54
30 2.21
30 2.94
55 0.54
71 0.461
34 1.97
59.2 1.107
52
0
26
0
6.28
8
7.3
9
6.14
6.14
6.14
7.3
7.3
7.48
6.1
6.1
7.3
11.6
5.2
5.2
7.6
3.8
16
9.06
4.1
3.944
9.68
3.044
1.71
7.4
Start Cap
P/N
Run Cap
P/N
Relay
P/N
Part
Type*
014-0036-13
014-0053-26
014-0053-18
014-0053-18
014-0053-18
014-0058-32
014-0053-26
014-0053-26
014-0053-26
014-0059-09
014-0036-28
014-0053-21
014-0058-25
014-0058-31
014-0036-28
014-0053-21
014-0058-31
014-0058-32
014-0058-31
014-0058-21
014-0058-32
014-0058-38
014-0058-21
014-0061-04
014-0064-11
040-0166-37
040-0150-19
040-0150-01
040-0150-20
040-0150-32
040-0166-21
040-0150-19
040-0150-01
RP
RC
RC
RC
RC
RP
RC
RC
040-0150-04
040-0166-21
040-0163-04
040-0166-45
040-0166-13
040-0166-37
040-0150-11
040-0166-18
040-0172-03
040-0163-02
040-0166-27
040-0172-03
040-0166-03
040-0166-27
040-0166-15
RC
RP
RC
RP
RP
RP
RC
RP
RC
RC
RP
RC
RP
RP
RP
014-0064-10
014-0064-11
014-0064-10
014-0064-09
014-0064-12
014-0064-10
014-0064-09
014-0064-11
014-0064-09
014-0064-06
Protector
P/N
071-0605-02
071-0561-01
071-0561-26
071-0561-21
071-0561-21
071-0561-21
071-0561-21
071-0561-21
071-0561-07
071-0561-29
071-0561-03
071-0561-03
071-0561-07
071-0561-12
071-0561-49
071-0561-49
071-0563-00
071-0605-05
071-0603-13
071-0604-01
071-0605-03
071-0605-04
071-0604-07
071-0508-38
071-0501-44
071-0496-27
* See Section F Introduction for more information.
FB5
Section_Fb.indd 5
3/4/2008 7:57:15 AM
Electrical Data - Welded Compressors
Model
CF06K6E-PFV
CF06K6E-TF5
CF06K6E-TFD
CF09K6E-PFV
CF09K6E-TF5
CF09K6E-TFD
CF12K6E-PFV
CF12K6E-TF5
CF12K6E-TFD
CF12K6E-TFE
CP25K8E-PFV
CR14K7-PFV
CR16K6-PFJ
CR16K6-PFV
CR16K7-PFV
CR16KQ-PFV
CR18K6-PFJ
CR18K6-PFV
CR18K7-PFV
CR18KQ-PFV
CR18KQ-TF5
CR18KQ-TFD
CR18KQE-PFV
CR18KQE-TF5
CR18KQE-TFD
CR19K7-PFV
Volts
208/230
200/230
380/460
208/230
200/230
380/460
208/230
200/230
380/460
575
208/230
208/230
265
208/230
208/230
208/230
265
208/230
208/230
208/230
200/230
380/460
208/230
200/230
380/460
208/230
Resistance
Max
PH RLA LRA
Start or
Run
Line/Line
1
3
3
1
3
3
1
3
3
3
1
1
1
1
1
1
1
1
1
1
3
3
1
3
3
1
11.4
7
3.7
16.7
10.2
5.5
20.5
12.3
6.6
5.4
11.3
6.9
9
9.6
8.4
7.9
9.1
10.4
8.6
9
6.1
3.1
9
6.1
3.1
10.2
59.2
52
25.4
87
72.2
35.8
105
85
42
35
51
35
44
49
39
38
44
49
40
41
49
23
41
49
23
43
1.107
0
0
0.715
0
0
0.553
0
0
0
2.1
1.85
1.741
1.268
1.647
2.214
1.741
1.268
1.592
2.092
0
0
2.092
0
0
1.491
3.044
1.71
7.4
2.82
1.256
4.95
1.979
0.945
3.78
5.99
1.04
2.392
3.619
3.661
2.538
5.084
3.619
3.661
2.519
4.215
1.9
7.437
4.215
1.9
7.437
2.698
Start Cap
P/N
Run Cap
P/N
Relay
P/N
Part
Type*
014-0061-04
014-0064-06
040-0166-15
RP
014-0058-32
014-0064-08
040-0166-15
RP
014-0058-00
014-0064-14
040-0166-19
RP
014-0061-04
014-0058-32
014-0058-31
014-0058-22
014-0058-32
014-0058-03
014-0058-31
014-0058-32
014-0058-32
014-0058-03
014-0064-06
014-0064-07
014-0064-05
014-0064-05
014-0064-07
014-0064-11
014-0064-11
014-0064-05
014-0064-07
014-0064-12
040-0166-19
040-0166-15
040-0166-15
040-0166-15
040-0166-15
040-0166-15
040-0166-15
040-0166-15
040-0166-15
040-0166-15
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
014-0058-03
014-0064-12
040-0166-15
RP
014-0061-04
014-0064-06
040-0166-19
RP
Protector
P/N
071-0508-38
071-0501-44
071-0501-46
071-0546-04
071-0501-45
071-0501-47
071-0546-08
071-0501-56
071-0496-20
071-0614-00
071-0546-25
071-0546-19
071-0508-34
071-0508-72
071-0546-10
071-0521-17
071-0508-34
071-0508-72
071-0546-20
071-0521-18
071-0501-60
071-0501-63
071-0521-18
071-0501-60
071-0501-63
071-0508-38
* See Section F Introduction for more information.
FB6
Section_Fb.indd 6
3/4/2008 7:57:15 AM
Electrical Data - Welded Compressors
Model
Volts
CR20K6-PFV
CR20KQ-PFV
CR20KQE-PFV
CR21K7-PFV
CR22K6-PFJ
CR22K6-PFV
CR22K6-TF5
CR22K6-TFD
CR22KQ-PFV
CR22KQE-PFV
CR23K7-PFV
CR24K6-PFJ
CR24K6-PFV
CR24K6-TF5
CR24K6-TFD
CR24K7-PFV
CR24KQ-PFV
CR24KQ-TF5
CR24KQ-TFD
CR24KQE-PFV
CR24KQE-TF5
CR24KQE-TFD
CR28K6-PFJ
CR28K6-PFV
CR28K6-TF5
CR28K6-TFD
208/230
208/230
208/230
208/230
265
208/230
200/230
380/460
208/230
208/230
208/230
265
208/230
200/230
380/460
208/230
208/230
200/230
380/460
208/230
200/230
380/460
265
208/230
200/230
460
Resistance
Max
PH RLA LRA
Start or
Run
Line/Line
1
1
1
1
1
1
3
3
1
1
1
1
1
3
3
1
1
3
3
1
3
3
1
1
3
3
10.6
10.4
10.4
11.3
9.9
10.9
7.5
3.9
11.1
11.1
10.8
10.9
12.4
7.7
4
12
13.6
7.5
3.7
13.6
7.5
3.7
13.9
15.3
10
4.8
50
54
54
51
55
50
51
25
51.5
51.5
49
58
61
55
28
60
70.5
51
25
70.5
51
25
73
75
68
34
1.268
1.529
1.529
1.322
1.332
1.268
0
0
1.626
1.626
1.251
1.346
0.999
0
0
1.163
0.862
0
0
0.862
0
0
0.986
0.74
0
0
3.661
4.003
4.003
2.538
3.807
3.661
1.77
7.4
3.424
3.424
2.026
2.646
2.594
1.609
6.386
2.101
3.337
1.97
7.4
3.337
1.97
7.4
3.649
2.3
1.3
5.43
Start Cap
P/N
Run Cap
P/N
Relay
P/N
Part
Type*
014-0061-04
014-0058-32
014-0058-32
014-0061-04
014-0058-34
014-0061-04
014-0064-06
014-0064-06
014-0064-06
014-0064-06
014-0064-06
014-0064-06
040-0166-19
040-0166-15
040-0166-15
040-0166-19
040-0166-15
040-0166-19
RP
RP
RP
RP
RP
RP
014-0058-03
014-0058-03
014-0058-00
014-0058-26
014-0058-03
014-0064-13
014-0064-13
014-0064-08
014-0064-13
014-0064-07
040-0166-44
040-0166-44
040-0166-15
040-0166-19
040-0166-15
RP
RP
RP
RP
RP
014-0058-00
014-0058-03
014-0064-08
014-0064-13
040-0166-15
040-0166-15
RP
RP
014-0058-03
014-0064-13
040-0166-15
RP
014-0036-18
014-0061-04
014-0064-13
014-0064-07
040-0166-15
040-0166-19
RP
RP
Protector
P/N
071-0508-72
071-0521-14
071-0521-14
071-0508-38
071-0508-50
071-0508-72
071-0501-01
071-0501-00
071-0521-16
071-0521-16
071-0546-12
071-0508-52
071-0508-35
071-0502-08
071-0502-00
071-0546-12
071-0521-20
071-0501-62
071-0501-00
071-0521-20
071-0501-62
071-0501-00
071-0508-48
071-0521-02
071-0501-05
071-0502-12
* See Section F Introduction for more information.
FB7
Section_Fb.indd 7
3/4/2008 7:57:16 AM
Electrical Data - Welded Compressors
Model
CR28K7-PFV
CR28K7-TF5
CR28KQ-PFV
CR28KQ-TF5
CR28KQ-TFD
CR28KQE-PFV
CR28KQE-TF5
CR28KQE-TFD
CR30K6-PFJ
CR30K6-PFV
CR30K6-TF5
CR30K6-TFD
CR30KQ-PFV
CR30KQ-TFD
CR30KQE-PFV
CR30KQE-TFD
CR31K7-PFV
CR31K7-TF5
CR32K6-PFJ
CR32K6-PFV
CR32K6-TF5
CR32K6-TFD
CR32K6-TFE
CR32KQ-PFV
CR32KQ-TF5
CR32KQ-TFD
Volts
208/230
200/230
208/230
200/230
380/460
208/230
200/230
380/460
265
208/230
200/230
460
208/230
380/460
208/230
380/460
208/230
200/230
265
208/230
200/230
460
575
208/230
200/230
380/460
Resistance
Max
PH RLA LRA
Start or
Run
Line/Line
1
3
1
3
3
1
3
3
1
1
3
3
1
3
1
3
1
3
1
1
3
3
3
1
3
3
13.6
10
15
8.9
4.4
15
8.9
4.4
13.6
16
10.4
4.9
15.4
4.7
15.4
4.7
16.1
9.1
15
16.1
10
5.1
3.8
17
9.9
5.1
73
65.5
70.5
60.5
30
70.5
60.5
30
64
82
65.5
33
78
32
78
32
82
66
83
82
70
33
27
83
63
32
0.847
0
0.862
0
0
0.862
0
0
1.096
0.715
0
0
0.82
0
0.82
0
0.715
0
0.91
0.751
0
0
0
0.721
0
0
2.131
1.256
3.337
1.28
5.05
3.337
1.28
5.05
3.02
2.82
1.256
4.95
3.045
4.96
3.045
4.96
2.82
1.256
2.955
3.2
1.133
4.3
7.48
2.775
1.24
4.99
Start Cap
P/N
Run Cap
P/N
Relay
P/N
Part
Type*
014-0058-32
014-0064-13
040-0166-15
RP
014-0058-03
014-0064-13
040-0166-15
RP
014-0058-03
014-0064-13
040-0166-15
RP
014-0058-32
014-0058-32
014-0064-14
014-0064-07
040-0166-15
040-0166-15
RP
RP
014-0058-03
014-0064-13
040-0166-15
RP
014-0058-03
014-0064-13
040-0166-15
RP
014-0058-32
014-0064-13
040-0166-15
RP
014-0058-32
014-0058-32
014-0064-13
014-0064-13
040-0166-14
040-0166-14
RP
RP
040-0166-15
RP
014-0058-32
Protector
P/N
071-0546-17
071-0477-06
071-0521-20
071-0501-62
071-0501-00
071-0521-20
071-0501-62
071-0501-00
071-0508-63
071-0508-31
071-0477-06
071-0501-25
071-0521-19
071-0501-26
071-0521-19
071-0501-26
071-0508-31
071-0501-68
071-0508-51
071-0492-02
071-0501-20
071-0501-25
071-0496-21
071-0521-11
071-0501-59
071-0501-64
* See Section F Introduction for more information.
FB8
Section_Fb.indd 8
3/4/2008 7:57:16 AM
Electrical Data - Welded Compressors
Model
Volts
CR32KQE-PFV
CR32KQE-TF5
CR32KQE-TFD
CR33KQ-PFV
CR33KQ-TF5
CR33KQ-TFD
CR33KQE-PFV
CR33KQE-TF5
CR33KQE-TFD
CR34K6-PFV
CR34KQ-PFV
CR34KQ-TF5
CR34KQ-TFD
CR34KQE-PFV
CR34KQE-TF5
CR34KQE-TFD
CR35K6-PFV
CR35K6-TF5
CR35K6-TFD
CR35K6-TFE
CR35K7-PFV
CR36KQ-PFV
CR36KQ-TF5
CR36KQ-TFD
CR36KQE-PFV
CR36KQE-TF5
208/230
200/230
380/460
208/230
200/230
460
208/230
200/230
460
208/230
208/230
200/230
460
208/230
200/230
460
208/230
200/230
460
575
208/230
208/230
200/230
460
208/230
200/230
Resistance
Max
PH RLA LRA
Start or
Run
Line/Line
1
3
3
1
3
3
1
3
3
1
1
3
3
1
3
3
1
3
3
3
1
1
3
3
1
3
17
9.9
5.1
16
10.6
4.7
16
10.6
4.7
16.6
16.7
11.8
5.4
16.7
11.8
5.4
18
11.4
4.8
4.1
18.2
17.6
12.4
5.5
17.6
12.4
83
63
32
75
69
31.6
75
69
31.6
96
84
67
29.2
84
67
29.2
96
75
40
31
89
93
68
34.5
93
68
0.721
0
0
0.865
0
0
0.865
0
0
0.639
0.74
0
0
0.74
0
0
0.623
0
0
0
0.61
0.711
0
0
0.711
0
2.775
1.24
4.99
3.626
1.28
5.05
3.626
1.28
5.05
1.911
3.352
1.24
5.85
3.352
1.24
5.85
2.333
1.058
4.11
6.5
2.08
3.152
1.13
4.43
3.152
1.13
Start Cap
P/N
Run Cap
P/N
014-0058-32
Relay
P/N
Part
Type*
040-0166-15
RP
014-0058-00
014-0064-14
040-0166-14
RP
014-0058-00
014-0064-14
040-0166-14
RP
014-0058-00
014-0058-00
014-0064-29
014-0064-14
040-0166-15
040-0166-14
RP
RP
014-0058-00
014-0064-14
040-0166-14
RP
014-0058-00
014-0064-08
040-0166-15
RP
014-0058-00
014-0058-00
014-0064-13
014-0064-14
040-0166-15
040-0166-14
RP
RP
014-0058-00
014-0064-14
040-0166-14
RP
Protector
P/N
071-0521-11
071-0501-59
071-0501-64
071-0508-77
071-0501-36
071-0501-35
071-0508-77
071-0501-36
071-0501-35
071-0508-30
071-0508-79
071-0501-16
071-0501-32
071-0508-79
071-0501-16
071-0501-32
071-0508-30
071-0501-13
071-0496-13
071-0477-15
071-0508-78
071-0508-78
071-0501-38
071-0501-37
071-0508-78
071-0501-38
* See Section F Introduction for more information.
FB9
Section_Fb.indd 9
3/4/2008 7:57:17 AM
Electrical Data - Welded Compressors
Model
CR36KQE-TFD
CR37KQ-PFV
CR37KQ-TF5
CR37KQ-TFD
CR37KQ-TFE
CR37KQE-PFV
CR37KQE-TF5
CR37KQE-TFD
CR38K6-PFV
CR38K6-TF5
CR38K6-TFD
CR38K6-TFE
CR41KQ-PFV
CR41KQ-TF5
CR41KQ-TFD
CR41KQE-PFV
CR41KQE-TF5
CR41KQE-TFD
CR42K6-PFV
CR42K6-TF5
CR42K6-TFD
CR42K6-TFE
CR47KQ-PFV
CR47KQ-TF5
CR47KQ-TFD
CR47KQ-TFE
Volts
460
208/230
200/230
380/460
575
208/230
200/230
380/460
208/230
200/230
380/460
575
208/230
200/230
380/460
208/230
200/230
380/460
208/230
200/230
460
575
208/230
200/230
380/460
575
Resistance
Max
PH RLA LRA
Start or
Run
Line/Line
3
1
3
3
3
1
3
3
1
3
3
3
1
3
3
1
3
3
1
3
3
3
1
3
3
3
5.5
18.6
11.1
5.6
4.8
18.6
11.1
5.6
19
11.9
5.9
4.8
19.4
13.1
5.9
19.4
13.1
5.9
20.4
14
6.4
5.2
24.6
16.1
8.2
5.6
34.5
100
85
39
34.39
100
85
39
105
85
42
34
109.6
80
42
109.6
80
42
102
91
42
39
132
97
50
38.6
0
0.664
0
0
0
0.664
0
0
0.553
0
0
0
0.601
0
0
0.601
0
0
0.585
0
0
0
0.457
0
0
0
4.43
2.431
1.07
3.693
5.99
2.431
1.07
3.693
1.979
0.945
3.78
5.9
2.324
1.04
4.06
2.324
1.04
4.06
2.37
0.875
3.45
5.315
2.148
0.82
3.22
5.026
Start Cap
P/N
Run Cap
P/N
Relay
P/N
Part
Type*
014-0058-00
014-0064-08
040-0166-19
RP
014-0058-00
014-0064-08
040-0166-19
RP
014-0058-00
014-0064-14
040-0166-19
RP
014-0058-00
014-0064-16
040-0166-27
RP
014-0058-00
014-0064-16
040-0166-27
RP
014-0058-00
014-0064-14
040-0166-27
RP
014-0058-00
014-0064-15
040-0166-18
RP
Protector
P/N
071-0501-37
071-0508-12
071-0501-31
071-0496-09
071-0614-02
071-0508-12
071-0501-31
071-0496-09
071-0508-42
071-0502-09
071-0496-20
071-0477-12
071-0508-12
071-0501-33
071-0501-29
071-0508-12
071-0501-33
071-0501-29
071-0508-19
071-0501-18
071-0477-09
071-0477-14
071-0546-07
071-0501-53
071-0501-57
071-0614-01
* See Section F Introduction for more information.
FB10
Section_Fb.indd 10
3/4/2008 7:57:17 AM
Electrical Data - Welded Compressors
Model
CR47KQE-PFV
CR47KQE-TF5
CR47KQE-TFD
CR53KQ-PFV
CR53KQ-TF5
CR53KQ-TFD
CR53KQ-TFE
CR53KQE-PFV
CR53KQE-TF5
CR53KQE-TFD
CR60K5-PFV
CR60K5-TF5
CR60K5-TFD
CR60KQ-PFV
CR60KQ-TFD
CRN5-0500-PFV
CRN5-0500-TF5
CRN5-0500-TFD
CRN5-0500-TFE
CRNQ-0500-PFV
CRNQ-0500-TF5
CRNQ-0500-TFD
CRNQ-0500-TFE
CRNQ-050E-TF5
CRNQ-050E-TFD
CRP5-0450-PFV
Volts
208/230
200/230
380/460
208/230
200/230
380/460
575
208/230
200/230
380/460
208/230
200/230
380/460
208/230
380/460
208/230
200/230
380/460
575
208/230
200/230
380/460
575
200/230
380/460
208/230
Resistance
Max
PH RLA LRA
Start or
Run
Line/Line
1
3
3
1
3
3
3
1
3
3
1
3
3
1
3
1
3
3
3
1
3
3
3
3
3
1
24.6 132 0.457
16.1
97
0
8.2
50
0
28.9 140 0.424
18.2 107
0
9.1
55
0
6 45.6
0
28.9 140 0.424
18.2 107
0
9.1
55
0
30.7 135 0.405
19.6 105
0
10.4
55
0
30.7 135 0.405
10.4
55
0
34.3 142 0.382
21.4 130
0
9.6
65
0
7.9
52
0
34.3 142 0.382
21.4 130
0
9.6
65
0
7.9
52
0
21.4 130
0
9.6
65
0
30.7 135 0.405
2.148
0.82
3.22
2.022
0.705
2.77
4.4
2.022
0.705
2.77
1.33
0.79
2.83
1.33
2.83
1.36
0.639
2.47
4.35
1.36
0.639
2.47
4.35
0.639
2.47
1.33
Start Cap
P/N
Run Cap
P/N
Relay
P/N
Part
Type*
014-0058-00
014-0064-15
040-0166-18
RP
014-0058-00
014-0064-18
040-0166-18
RP
014-0058-00
014-0064-18
040-0166-18
RP
014-0058-00
014-0064-15
040-0166-27
RP
014-0058-00
014-0064-15
040-0166-27
RP
014-0006-15
014-0064-17
040-0166-27
RP
014-0006-15
014-0064-17
040-0166-27
RP
014-0058-00
014-0064-15
040-0166-27
RP
Protector
P/N
071-0546-07
071-0501-53
071-0501-57
071-0509-02
071-0501-53
071-0501-48
071-0614-01
071-0509-02
071-0501-53
071-0501-48
071-0508-09
071-0428-07
071-0428-02
071-0508-09
071-0428-02
071-0483-00
071-0526-00
071-0526-01
071-0428-05
071-0483-00
071-0526-00
071-0526-01
071-0428-05
071-0526-00
071-0526-01
071-0508-09
* See Section F Introduction for more information.
FB11
Section_Fb.indd 11
3/4/2008 7:57:18 AM
Electrical Data - Welded Compressors
Model
Volts
CRP5-0450-TF5
CRP5-0450-TFD
CRP5-0450-TFE
CRPQ-0450-PFV
CRPQ-0450-TF5
CRPQ-0450-TFD
CRPQ-0450-TFE
CRT5-0450-PFV
CRT5-0450-TF5
CRT5-0450-TFD
CRT5-0450-TFE
CRTQ-0450-PFV
CRTQ-0450-TF5
CRTQ-0450-TFD
CRTQ-0450-TFE
CRTQ-045E-TF5
CRTQ-045E-TFD
CS08KQE-PFV
CS10K6E-PFJ
CS10K6E-PFV
CS10K6E-TF5
CS10K6E-TFD
CS12K6E-PFJ
CS12K6E-PFV
CS12K6E-TF5
CS13K6E-PFV
200/230
380/460
575
208/230
200/230
380/460
575
208/230
200/230
380/460
575
208/230
200/230
380/460
575
200/230
380/460
208/230
265
208/230
200/230
380/460
265
208/230
200/230
208/230
Resistance
Max
PH RLA LRA
Start or
Run
Line/Line
3
3
3
1
3
3
3
1
3
3
3
1
3
3
3
3
3
1
1
1
3
3
1
1
3
1
19.6
10.4
7
30.7
19.6
10.4
7
30.7
19.6
10.4
7
30.7
19.6
10.4
7
19.6
10.4
10.1
8.6
10.9
7.5
3.6
10.9
10.9
7.5
14.4
105
55
45
135
105
55
45
135
105
55
45
135
105
55
45
105
55
54
55
56
51
25
55
56
51
73
0
0
0
0.405
0
0
0
0.405
0
0
0
0.405
0
0
0
0
0
1.107
1.332
1.107
0
0
1.332
1.107
0
0.847
0.79
2.83
4.71
1.33
0.79
2.83
4.71
1.33
0.79
2.83
4.71
1.33
0.79
2.83
4.71
0.79
2.83
3.044
3.807
3.044
1.77
7.4
3.807
3.044
1.77
2.131
Start Cap
P/N
Run Cap
P/N
Relay
P/N
Part
Type*
014-0058-00
014-0064-15
040-0166-27
RP
014-0058-00
014-0064-15
040-0166-27
RP
014-0058-00
014-0064-15
040-0166-27
RP
014-0058-32
014-0036-18
014-0061-04
014-0064-06
014-0064-06
014-0064-06
040-0166-15
040-0166-15
040-0166-19
RP
RP
RP
014-0036-18
014-0061-04
014-0064-06
014-0064-06
040-0166-15
040-0166-19
RP
RP
014-0058-00
014-0064-13
040-0166-15
RP
Protector
P/N
071-0428-07
071-0428-02
071-0428-11
071-0508-09
071-0428-07
071-0428-02
071-0428-11
071-0508-09
071-0428-07
071-0428-02
071-0428-11
071-0508-09
071-0428-07
071-0428-02
071-0428-11
071-0428-07
071-0428-02
071-0508-38
071-0508-50
071-0508-38
071-0501-01
071-0501-00
071-0508-50
071-0508-38
071-0501-01
071-0546-17
* See Section F Introduction for more information.
FB12
Section_Fb.indd 12
3/4/2008 7:57:18 AM
Electrical Data - Welded Compressors
Model
Volts
CS13K6E-TF5
CS14K6E-PFJ
CS14K6E-PFV
CS14K6E-TF5
CS14K6E-TFD
CS16K6E-PFV
CS17K6E-PFV
CS18K6E-PFJ
CS18K6E-PFV
CS18K6E-TF5
CS18K6E-TFD
CS18K6E-TFE
CS20K6E-PFV
CS20K6E-TF5
CS20K6E-TFD
CS24K6E-PFV
CS24K6E-TF5
CS27K3E-TF5
CS27K3E-TFD
CS27K6E-PFV
CS27K6E-TF5
CS27K6E-TFD
CS33K3E-PFV
CS33K3E-TF5
CS33K3E-TFC
CS33K3E-TFD
200/230
265
208/230
200/230
380/460
208/230
208/230
265
208/230
200/230
460
575
208/230
200/230
460
208/230
200/230
200/230
380/460
208/230
200/230
460
208/230
200/230
208/230
380/460
Resistance
Max
PH RLA LRA
Start or
Run
Line/Line
3
1
1
3
3
1
1
1
1
3
3
3
1
3
3
1
3
3
3
1
3
3
1
3
3
3
9
66
0
12.5
58 1.346
12.5
61 0.999
9.1
55
0
4.7
28
0
15.5
73 0.847
16
82 0.727
13.6
64 1.096
16
82 0.715
8.8 65.5
0
4.7
33
0
4.4 25.4
0
18.6
96 0.623
11.4
75
0
5.1
40
0
23.9 121
0.5
14 105
0
15.6
82
0
8.4
41
0
23.9 121
0.5
13.4 105
0
8.4
52
0
30.7 125 0.44
20.7
90
0
20.7
90
0
9.9
45
0
1.256
2.646
2.594
1.609
6.386
2.131
2.367
3.02
2.82
1.256
4.95
7.48
2.333
1.058
4.11
2.302
0.853
0.994
3.96
2.302
0.853
3.413
2.1
0.853
0.853
3.413
Start Cap
P/N
Run Cap
P/N
Relay
P/N
Part
Type*
014-0061-04
014-0058-03
014-0064-13
014-0064-07
040-0166-19
040-0166-15
RP
RP
014-0061-16
014-0058-00
014-0058-32
014-0058-32
014-0064-13
014-0064-13
014-0064-14
014-0064-07
040-0166-14
040-0166-15
040-0166-15
RP
RP
RP
014-0058-00
014-0064-08
040-0166-15
RP
014-0058-00
014-0064-14
040-0166-23
RP
014-0058-00
014-0064-14
040-0166-23
RP
014-0058-00
014-0064-16
040-0166-27
RP
Protector
P/N
071-0501-68
071-0508-52
071-0508-35
071-0502-08
071-0502-00
071-0546-17
071-0521-03
071-0508-63
071-0508-31
071-0477-06
071-0501-26
071-0614-03
071-0508-30
071-0501-13
071-0496-13
071-0546-03
071-0501-49
071-0417-01
071-0417-06
071-0546-03
071-0501-49
071-0501-50
071-0508-37
071-0417-00
071-0417-00
071-0417-12
* See Section F Introduction for more information.
FB13
Section_Fb.indd 13
3/4/2008 7:57:18 AM
Electrical Data - Welded Compressors
Model
Volts
CS33K6E-PFV
CS33K6E-TF5
CS33K6E-TFD
CTH1-0275-CSV
CTH1-0275-TSC
CTL1-0350-CSV
CTL1-0350-TSC
CTM1-0400-CSV
CTM1-0400-TSC
CTN1-0500-TSC
CTN1-0501-CSV
REBQ-0150-PFJ
REBQ-0150-PFV
REKQ-0125-PFJ
REKQ-0125-PFV
RF18C1E-IAA
RF18C1E-IAV
RF18C2E-IAA
RF18C2E-IAV
RF40C1E-CAA
RF40C1E-CAV
RF41C1E-CAA
RF41C1E-CAV
RF41C5E-CAA
RF41C5E-CAV
RF42C1E-CAA
208/230
200/230
460
208/230
208/230
208/230
208/230
208/230
208/230
208/230
208/230
265
208/230
265
208/230
115
208/230
115
208/230
115
208/230
115
208/230
115
208/230
115
Resistance
Max
PH RLA LRA
Start or
Run
Line/Line
1
3
3
1
3
1
3
1
3
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
30.7
18.7
9.9
19.6
14.1
24.1
17.6
34.3
22.1
25.2
35.7
7.4
7.9
6.9
8.5
12.9
7.1
12.9
7.1
15.4
6.1
15.4
7.9
15.4
7.9
16
125 0.424
102
0
48
0
3.8
0
2.81
0
2.18
0
0
2.02
39.6 1.97
49.7 1.58
40 1.97
49.7 1.58
66.3 0.455
25 3.09
66.3 0.455
25 3.09
64 0.51
24.1
2.1
76.5 0.415
40 1.65
64 0.51
40 1.65
72.5 0.409
2.022
0.853
3.413
0.933
2.04
0.751
1.48
0.674
1.39
1.14
0.574
5.37
4.353
5.37
4.353
2.245
13.32
2.245
13.32
2.8
18.3
3.22
6.3
2.8
6.3
5.39
Start Cap
P/N
Run Cap
P/N
Relay
P/N
Part
Type*
014-0006-15
014-0064-17
040-0166-27
RP
014-0058-03
014-0064-13
040-0001-84
RP
014-0058-13
014-0064-15
040-0001-86
RP
014-0058-04
014-0064-16
040-0001-83
RP
014-0058-04
014-0036-17
014-0064-17
014-0064-12
014-0064-05
014-0064-12
014-0064-05
040-0001-85
040-0166-14
RP
RP
040-0166-14
RP
040-0168-03
040-0168-06
040-0168-03
040-0168-06
040-0166-14
040-0166-14
040-0166-15
040-0166-14
040-0166-14
040-0166-14
040-0166-19
RC
RC
RC
RC
RP
RP
RP
RP
RP
RP
RP
014-0036-17
014-0058-27
014-0058-27
014-0058-31
014-0058-17
014-0058-22
014-0058-19
014-0058-31
014-0058-19
014-0058-31
014-0064-08
014-0064-00
014-0064-07
014-0064-02
014-0064-08
014-0064-02
014-0064-05
Protector
P/N
071-0546-05
071-0496-28
071-0501-54
071-0582-00
071-0582-00
071-0582-00
071-0582-00
071-0582-00
071-0582-00
071-0582-00
071-0582-00
071-0512-12
071-0512-15
071-0512-12
071-0512-15
071-0127-06
071-0329-26
071-0127-06
071-0329-26
071-0518-03
071-0527-07
071-0518-09
071-0518-10
071-0518-03
071-0518-10
071-0127-46
* See Section F Introduction for more information.
FB14
Section_Fb.indd 14
3/4/2008 7:57:19 AM
Electrical Data - Welded Compressors
Model
Volts
RF42C1E-CAV
RFT12C1E-IAA
RFT12C1E-IAB
RFT22C1E-CAA
RFT22C1E-IAA
RFT26C1E-CAA
RFT26C1E-CAB
RFT26C1E-IAA
RFT26C1E-IAB
RFT29C1E-CAA
RFT29C1E-IAA
RFT32C1E-CAA
RFT32C1E-IAA
RR10K1E-CAA
RR10K1E-CAV
RR10K2-CAA
RR10K2-CAV
RR10K2E-CAA
RR10K2E-CAV
RR12K1-PFV
RR14K1-PFJ
RR14K1-PFV
RR16K1-PFJ
RR16K1-PFV
RR17K1-PFJ
RR17K1-PFV
208/230
115
230
115
115
115
230
115
230
115
115
115
115
115
208/230
115
208/230
115
208/230
208/230
265
208/230
265
208/230
265
208/230
Resistance
Max
PH RLA LRA
Start or
Run
Line/Line
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
8.4
6.1
2.5
7.9
7.9
10.8
5.7
10.8
5.7
13
13
15
15
15
7.3
16.9
8.3
16.9
8.3
7.1
6.9
8.5
8.4
9.5
8.2
10.4
46 1.36
33.7 0.72
15.8 2.71
54.5 0.43
54.5 0.43
66 0.04
26
2.3
66 0.04
26
2.3
66
0.4
66
0.4
56 0.34
56 0.34
78 0.412
40 1.65
78 0.412
40 1.65
78 0.412
40 1.65
35 1.96
35 2.84
40 2.09
36.1 2.44
43.3 1.52
44 2.16
48.2 1.54
4.45
4.11
13.8
2.66
2.66
2.6
8.8
2.6
8.8
2.6
2.6
2.59
2.59
4.83
6.3
4.83
6.3
4.83
6.3
4.89
5.25
4.87
4.77
4.39
4.06
3.82
Start Cap
P/N
Run Cap
P/N
Relay
P/N
Part
Type*
014-0058-00
014-0059-14
014-0059-09
014-0058-36
014-0058-36
014-0058-36
014-0058-31
014-0058-36
014-0053-30
014-0058-36
014-0058-36
014-0058-36
014-0058-36
014-0058-26
014-0058-19
014-0058-26
014-0058-19
014-0058-26
014-0058-19
014-0058-19
014-0058-31
014-0058-19
014-0036-16
014-0058-25
014-0058-25
014-0058-25
014-0064-10
040-0166-14
040-0150-37
040-0150-04
040-0166-21
040-0172-03
040-0166-21
040-0166-26
040-0172-03
040-0150-34
040-0166-21
040-0172-03
040-0166-37
040-0166-37
040-0166-14
040-0166-14
040-0166-14
040-0166-14
040-0166-14
040-0166-14
040-0166-19
040-0166-14
040-0166-19
040-0166-15
040-0166-19
040-0166-14
040-0166-37
RP
RC
RC
RP
RC
RP
RP
RC
RC
RP
RC
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
014-0064-13
014-0064-13
014-0064-09
014-0064-13
014-0064-13
014-0064-06
014-0064-02
014-0064-06
014-0064-02
014-0064-06
014-0064-02
014-0064-04
014-0064-05
014-0064-05
014-0064-11
014-0064-05
014-0064-12
014-0064-06
Protector
P/N
071-0127-37
071-0561-66
071-0561-64
071-0645-01
071-0645-00
071-0604-18
071-0647-09
071-0605-10
071-0561-28
071-0604-16
071-0605-05
071-0605-09
071-0605-08
071-0127-30
071-0127-05
071-0127-30
071-0127-05
071-0127-30
071-0127-05
071-0421-22
071-0512-09
071-0512-04
071-0432-16
071-0432-10
071-0512-13
071-0432-10
* See Section F Introduction for more information.
FB15
Section_Fb.indd 15
3/4/2008 7:57:19 AM
Electrical Data - Welded Compressors
Model
Volts
RR17K1-TFC
RR20K1-PFV
RR81C1E-IAA
RR81C1E-IAV
RR81C2-IAA
RR81C2-IAV
RR81C2E-IAA
RR81C2E-IAV
RRG4-0100-PAA
RRG4-0100-PAV
RRL4-0100-CAV
RRS4-0075-IAA
RRS4-0075-IAV
RRT62C1E-IAA
RRT62C1E-IAB
RRT64C1E-CAA
RRT64C1E-IAA
RRT73C1E-CAA
RRT73C1E-IAA
RS40C1E-IAA
RS40C1E-IAV
RS40C2-IAA
RS40C2-IAV
RS40C2E-IAA
RS40C2E-IAV
RS43C1E-CAA
208/230
208/230
115
208/230
115
208/230
115
208/230
115
208/230
208/230
115
208/230
115
230
115
115
115
115
115
208/230
115
208/230
115
208/230
115
Resistance
Max
PH RLA LRA
Start or
Run
Line/Line
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
6.5
12.1
13.3
7.9
15.2
9
15.2
9
13.2
6.7
7.3
13.3
6.5
9.5
4.5
11
11
11
11
9
4.9
10.1
5.6
10.1
5.6
10.1
41
65
66.3
33.5
66.3
33.5
66.3
33.5
60
33.5
40
66.3
33.5
44
21
45
45
54.5
54.5
51
24.1
51
24.1
51
24.1
51
0
0.955
0.416
1.55
0.416
1.55
0.416
1.55
0.551
1.55
1.65
0.416
1.55
0.6
2.7
0.51
0.51
0.43
0.43
0.687
2.1
0.687
2.1
0.687
2.1
0.59
2.4
4.085
3.15
7.92
3.15
7.92
3.15
7.92
4.8
7.92
6.3
3.15
7.92
4.3
12.7
2.62
2.62
2.66
2.66
4.07
18.3
4.07
18.3
4.07
18.3
4.08
Start Cap
P/N
014-0061-18
014-0058-22
014-0061-18
014-0058-22
014-0061-18
014-0058-22
014-0061-18
014-0058-06
014-0061-18
014-0058-19
014-0058-09
014-0061-18
014-0053-18
014-0036-24
014-0058-43
014-0058-43
014-0058-36
014-0058-36
014-0058-22
014-0058-17
014-0058-22
014-0058-17
014-0058-22
014-0058-17
014-0058-11
Run Cap
P/N
014-0064-05
014-0064-05
014-0064-02
014-0064-02
014-0037-17
014-0064-13
014-0064-02
Relay
P/N
040-0166-19
040-0168-03
040-0168-01
040-0168-03
040-0168-01
040-0168-03
040-0168-01
040-0166-19
040-0166-14
040-0166-14
040-0168-03
040-0168-01
040-0150-11
040-0150-04
040-0166-03
040-0172-04
040-0166-21
040-0172-03
040-0168-00
040-0168-02
040-0168-00
040-0168-02
040-0168-00
040-0168-02
040-0166-21
Part
Type*
RP
RC
RC
RC
RC
RC
RC
RP
RP
RP
RC
RC
RC
RC
RP
RC
RP
RC
RC
RC
RC
RC
RC
RC
RP
Protector
P/N
071-0481-01
071-0432-15
071-0127-18
071-0329-07
071-0127-18
071-0329-07
071-0127-18
071-0329-07
071-0127-40
071-0329-00
071-0127-05
071-0127-18
071-0329-07
071-0561-61
071-0647-11
071-0561-60
071-0647-04
071-0644-01
071-0605-01
071-0127-41
071-0329-11
071-0127-41
071-0329-11
071-0127-41
071-0329-11
071-0329-15
* See Section F Introduction for more information.
FB16
Section_Fb.indd 16
3/4/2008 7:57:20 AM
Electrical Data - Welded Compressors
Model
Volts
RS43C1E-CAV
RS43C1E-IAA
RS43C1E-IAV
RS43C2-CAA
RS43C2E-CAA
RS43C2E-CAV
RS43C2E-IAA
RS43C2E-IAV
RS43CAE-CAA
RS47C2-IAA
RS47C2-IAV
RS54C1E-IAA
RS54C1E-IAV
RS54C2-IAA
RS54C2-IAV
RS54C2E-IAA
RS54C2E-IAV
RS55C1E-CAV
RS55C1E-PAA
RS55C1E-PAV
RS55C2-CAA
RS55C2-CAV
RS55C2E-CAA
RS55C2E-CAV
RS64C1E-CAA
RS64C1E-CAV
208/230
115
208/230
115
115
208/230
115
208/230
115
115
208/230
115
208/230
115
208/230
115
208/230
208/230
115
208/230
115
208/230
115
208/230
115
208/230
Resistance
Max
PH RLA LRA
Start or
Run
Line/Line
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
5.4
10.1
5.7
10.1
10.1
5.4
10.1
5.7
10.1
14.3
7.1
11.8
6.8
11.8
6.8
11.8
6.8
6.7
13.2
6.7
13.2
6.1
13.2
6.1
15.1
7.7
24.1
51
24.1
51
51
24.1
51
24.1
51
66.3
35.5
66.3
33.5
66.3
33.5
66.3
33.5
33.5
60
33.5
60
40
60
40
59
37
2.1
0.59
2.1
0.59
0.59
2.1
0.59
2.1
0.59
0.416
1.55
0.455
1.55
0.455
1.55
0.455
1.55
1.55
0.551
1.55
0.66
3.09
0.66
3.09
0.573
1.55
18.3
4.08
18.3
4.08
4.08
18.3
4.08
18.3
4.08
3.15
7.92
2.245
7.92
2.245
7.92
2.245
7.92
7.92
4.8
7.92
4.2
3.82
4.2
3.82
5.68
7.92
Start Cap
P/N
Run Cap
P/N
Relay
P/N
Part
Type*
014-0058-17
014-0058-11
014-0058-17
014-0058-11
014-0058-11
014-0058-17
014-0058-11
014-0058-17
014-0058-11
014-0058-27
014-0058-19
014-0058-27
014-0058-18
014-0058-27
014-0058-18
014-0058-27
014-0058-18
014-0061-18
014-0058-06
014-0061-18
014-0058-00
014-0058-04
014-0058-00
014-0058-04
014-0058-25
014-0058-14
014-0064-00
040-0166-14
040-0168-00
040-0168-02
040-0166-21
040-0166-21
040-0166-14
040-0168-00
040-0168-02
040-0166-21
040-0168-03
040-0168-01
040-0168-03
040-0168-01
040-0168-03
040-0168-01
040-0168-03
040-0168-01
040-0166-14
040-0166-19
040-0166-14
040-0166-19
040-0166-14
040-0166-19
040-0166-14
040-0166-02
040-0166-14
RP
RC
RC
RP
RP
RP
RC
RC
RP
RC
RC
RC
RC
RC
RC
RC
RC
RP
RP
RP
RP
RP
RP
RP
RP
RP
014-0064-02
014-0064-02
014-0064-00
014-0064-02
014-0064-02
014-0064-05
014-0064-02
014-0064-05
014-0064-05
014-0064-05
014-0064-05
014-0064-12
014-0064-02
Protector
P/N
071-0329-10
071-0329-15
071-0329-11
071-0329-15
071-0329-15
071-0329-10
071-0329-15
071-0329-11
071-0329-15
071-0127-30
071-0370-29
071-0127-06
071-0329-04
071-0127-06
071-0329-04
071-0127-06
071-0329-04
071-0329-30
071-0127-40
071-0329-30
071-0518-02
071-0527-08
071-0518-02
071-0527-08
071-0127-43
071-0329-16
* See Section F Introduction for more information.
FB17
Section_Fb.indd 17
3/4/2008 7:57:20 AM
Electrical Data - Welded Compressors
Model
RS64C1E-IAV
RS64C1E-PAA
RS64C1E-PFA
RS64C2-CAA
RS64C2-CAV
RS64C2-IAV
RS64C2-PAA
RS64C2E-CAA
RS64C2E-CAV
RS64C2E-IAV
RS64C2E-PAA
RS70C1-PAA
RS70C1-PFJ
RS70C1-PFV
RS70C1-TFC
RS70C1-TFD
RS70C1E-PFJ
RS70C1E-PFV
RS70C1E-TFC
RS70C1E-TFD
RS73C1E-PFJ
RS80C1E-CAA
RS80C1E-CAV
RS80C1E-TF5
RS80C1E-TFD
RS80C2-CAA
Volts
208/230
115
115
115
208/230
208/230
115
115
208/230
208/230
115
115
265
208/230
208/230
460
265
208/230
208/230
460
265
115
208/230
200/230
460
115
Resistance
Max
PH RLA LRA
Start or
Run
Line/Line
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3
3
1
1
3
3
1
1
1
3
3
1
9.2
15.1
15.1
13.2
7.7
9.2
13.2
15.1
7.7
9.2
15.1
16.7
6
7
4.7
2.6
6
7
4.7
2.6
8.2
18.6
9.6
6.4
2.5
18.6
45
59
59
59
37
45
59
59
37
45
59
72.5
30
34.2
31
15
30
34.2
31
15
39.6
72.5
46
41
15
72.5
1.56
0.573
0.573
0.573
1.55
1.56
0.573
0.573
1.55
1.56
0.573
0.409
3.42
1.96
0
0
3.42
1.96
0
0
1.97
0.409
1.36
0
0
0.409
7.45
5.68
5.68
5.68
7.92
7.45
5.68
5.68
7.92
7.45
5.68
5.39
5.1
4.89
3.72
14.3
5.1
4.89
3.72
14.3
5.37
5.39
4.45
2.4
14.3
5.39
Start Cap
P/N
014-0058-19
014-0058-25
014-0058-25
014-0058-25
014-0058-14
014-0058-19
014-0058-25
014-0058-25
014-0058-14
014-0058-19
014-0058-25
014-0058-18
014-0036-17
014-0058-19
Run Cap
P/N
Relay
P/N
Part
Type*
014-0064-12
014-0064-06
014-0064-05
014-0064-05
040-0168-00
040-0166-02
040-0166-02
040-0166-02
040-0166-14
040-0168-00
040-0166-02
040-0166-02
040-0166-14
040-0168-00
040-0166-02
040-0166-19
040-0166-19
040-0166-19
RC
RP
RP
RP
RP
RC
RP
RP
RP
RC
RP
RP
RP
RP
014-0036-17
014-0058-19
014-0064-05
014-0064-05
040-0166-19
040-0166-19
RP
RP
014-0036-17
014-0058-31
014-0058-00
014-0064-12
014-0064-05
014-0064-10
040-0166-14
040-0166-19
040-0166-14
RP
RP
RP
014-0058-31
014-0064-05
040-0166-19
RP
014-0064-12
014-0064-12
014-0064-12
014-0064-02
014-0064-12
014-0064-12
014-0064-02
Protector
P/N
071-0127-37
071-0127-43
071-0546-13
071-0127-43
071-0329-16
071-0127-37
071-0127-43
071-0127-43
071-0329-16
071-0127-37
071-0127-43
071-0127-18
071-0432-11
071-0432-09
071-0481-00
071-0481-02
071-0432-11
071-0432-09
071-0481-00
071-0481-02
071-0512-12
071-0127-46
071-0127-37
071-0481-01
071-0481-02
071-0127-46
* See Section F Introduction for more information.
FB18
Section_Fb.indd 18
3/4/2008 7:57:20 AM
Electrical Data - Welded Compressors
Model
Volts
RS80C2-CAV
RS80C2-TF5
RS80C2-TFD
RS80C2E-CAA
RS80C2E-CAV
RS80C2E-TF5
RS80C2E-TFD
RS86C1E-PFJ
RS86C1E-PFV
RS86C2E-PFV
RS97C1E-CAA
RS97C1E-CAV
RS97C1E-TFC
RS97C2-CAA
RS97C2-CAV
RS97C2-TFC
RS97C2E-CAA
RS97C2E-CAV
RS97C2E-TFC
RSE4-0075-IAA
RSE4-0075-IAV
RSE4-0076-IAA
RSE4-0076-IAV
RSF5-0075-CAA
RSL2-0075-IAA
RSL2-0075-IAV
208/230
200/230
460
115
208/230
200/230
460
265
208/230
208/230
115
208/230
208/230
115
208/230
208/230
115
208/230
208/230
115
208/230
115
208/230
115
115
208/230
Resistance
Max
PH RLA LRA
Start or
Run
Line/Line
1
3
3
1
1
3
3
1
1
1
1
1
3
1
1
3
1
1
3
1
1
1
1
1
1
1
9.6
6.4
2.5
18.6
9.6
6.4
2.5
8.9
9.8
9.8
20.7
11
7
20.7
10.4
7
20.7
11
7
14.3
7.1
14.3
7.1
13.5
11.8
6.8
46
41
15
72.5
46
41
15
36.1
43.3
43.3
95
51
35
95
51
35
95
51
35
66.3
35.5
66.3
35.5
72.7
66.3
33.5
1.36
0
0
0.409
1.36
0
0
2.44
1.41
1.41
0.324
1.12
0
0.324
1.12
0
0.324
1.12
0
0.416
1.55
0.416
1.55
0.416
0.455
1.55
4.45
2.4
14.3
5.39
4.45
2.4
14.3
4.77
2.65
2.65
4.142
4.92
2.58
4.142
4.92
2.58
4.142
4.92
2.58
3.15
7.92
3.15
7.92
3.15
2.245
7.92
Start Cap
P/N
Run Cap
P/N
Relay
P/N
Part
Type*
014-0058-00
014-0064-10
040-0166-14
RP
014-0058-31
014-0058-00
014-0064-05
014-0064-10
040-0166-19
040-0166-14
RP
RP
014-0036-16
014-0058-25
014-0058-25
014-0061-04
014-0036-17
014-0064-11
014-0064-06
014-0064-06
014-0064-07
014-0064-11
040-0166-15
040-0166-19
040-0166-19
040-0166-18
040-0166-14
RP
RP
RP
RP
RP
014-0061-04
014-0036-17
014-0064-07
014-0064-11
040-0166-18
040-0166-14
RP
RP
014-0061-04
014-0036-17
014-0064-07
014-0064-11
040-0166-18
040-0166-14
RP
RP
040-0168-03
040-0168-01
040-0168-03
040-0168-01
040-0166-21
040-0168-03
040-0168-01
RC
RC
RC
RC
RP
RC
RC
014-0058-27
014-0058-19
014-0058-27
014-0058-19
014-0058-27
014-0058-27
014-0061-18
014-0064-17
Protector
P/N
071-0127-37
071-0481-01
071-0481-02
071-0127-46
071-0127-37
071-0481-01
071-0481-02
071-0432-16
071-0421-21
071-0546-01
071-0127-45
071-0127-24
071-0404-01
071-0127-45
071-0127-24
071-0404-01
071-0127-45
071-0127-24
071-0404-01
071-0127-30
071-0370-29
071-0127-30
071-0370-29
071-0506-00
071-0127-06
071-0329-04
* See Section F Introduction for more information.
FB19
Section_Fb.indd 19
3/4/2008 7:57:21 AM
Electrical Data - Welded Compressors
Model
Volts
RSL2-0100-CAA
RSL2-0100-CAV
RSL2-0101-CAA
RSL2-0101-CAV
RSL5-0100-CAV
RSL5-0100-TFC
RSL5-0101-CAV
RSL5-0101-TFC
RSN4-0050-IAA
RSN4-0050-IAV
RSN4-0075-CAV
RSN4-0075-IAA
RSN4-0075-IAV
RSN4-0075-PAA
RSN4-0100-CAV
RSN4-0100-PAA
RSN6-0075-CAA
RSN6-0075-IAA
RSN6-0075-IAV
RST40C1E-CAA
RST40C1E-CAB
RST40C1E-CAV
RST40C1E-IAA
RST40C1E-IAB
RST40C1E-IAV
RST45C1E-CAA
115
208/230
115
208/230
208/230
208/230
208/230
208/230
115
208/230
208/230
115
208/230
115
208/230
115
115
115
208/230
115
230
208/230
115
230
208/230
115
Resistance
Max
PH RLA LRA
Start or
Run
Line/Line
1
1
1
1
1
3
1
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
18
10.4
18
10.4
9.4
5.7
9.4
5.7
9
4.9
7.7
14.9
8.8
10.3
7.7
10.3
12.1
14.3
6.9
9
5.3
5.1
9
5.3
5.1
10.5
78
51
78
51
51
35
51
35
51
24.1
37
66.3
45
50
37
50
75
66.3
45
50
25
27
50
25
27
54.5
0.412
1.12
0.412
1.12
1.12
0
1.12
0
0.687
2.1
1.55
0.416
1.56
0.585
1.55
0.585
0.483
0.416
1.56
0.51
2.7
1.91
0.51
2.7
1.91
0.43
4.83
4.92
4.83
4.92
4.92
2.58
4.92
2.58
4.07
18.3
7.92
3.15
7.45
5.07
7.92
5.07
5.54
3.15
7.45
2.62
12.7
6.38
2.62
12.7
6.38
2.66
Start Cap
P/N
Run Cap
P/N
Relay
P/N
Part
Type*
014-0058-26
014-0036-17
014-0058-26
014-0036-17
014-0036-17
014-0064-06
014-0064-11
014-0064-06
014-0064-11
014-0064-11
040-0166-14
040-0166-14
040-0166-14
040-0166-14
040-0166-14
RP
RP
RP
RP
RP
014-0036-17
014-0064-11
040-0166-14
RP
040-0168-00
040-0168-02
040-0166-14
040-0168-03
040-0168-04
040-0166-19
040-0166-14
040-0166-19
040-0166-15
040-0168-03
040-0168-04
040-0166-03
040-0166-26
040-0166-18
040-0150-37
040-0150-14
040-0150-31
040-0166-21
RC
RC
RP
RC
RC
RP
RP
RP
RP
RC
RC
RP
RP
RP
RC
RC
RC
RP
014-0058-22
014-0058-17
014-0058-14
014-0058-27
014-0058-14
014-0058-06
014-0058-14
014-0058-06
014-0061-04
014-0058-27
014-0058-14
014-0036-24
014-0036-24
014-0058-31
014-0059-20
014-0059-09
014-0053-30
014-0036-24
014-0064-02
014-0064-05
014-0064-02
014-0064-05
014-0064-02
014-0064-13
014-0064-13
014-0064-33
014-0064-13
Protector
P/N
071-0127-30
071-0127-24
071-0127-30
071-0127-24
071-0127-24
071-0404-01
071-0127-24
071-0404-01
071-0127-34
071-0329-11
071-0329-16
071-0127-30
071-0127-05
071-0127-19
071-0329-16
071-0127-19
071-0127-42
071-0127-30
071-0127-05
071-0561-48
071-0561-57
071-0561-23
071-0561-56
071-0561-12
071-0561-65
071-0604-10
* See Section F Introduction for more information.
FB20
Section_Fb.indd 20
3/4/2008 7:57:21 AM
Electrical Data - Welded Compressors
Model
Volts
RST45C1E-CAV
RST45C1E-IAA
RST45C1E-IAV
RST55C1E-CAA
RST55C1E-CAB
RST55C1E-IAA
RST55C1E-IAB
RST64C1E-CAV
RST64C1E-CFA
RST64C1E-IAV
RSU4-0050-CAA
RSU4-0050-IAA
RSU5-0050-IAA
RSU5-0050-IAV
208/230
115
208/230
115
230
115
230
208/230
115
208/230
115
115
115
208/230
Resistance
Max
PH RLA LRA
Start or
Run
Line/Line
1
1
1
1
1
1
1
1
1
1
1
1
1
1
5.1
10.5
5.1
15
7
15
7
8.9
14.6
8.9
9.6
9.6
9.6
5.4
26.5
54.5
26.5
70
37
70
37
43
77
43
51
51
51
24.1
1.69
0.43
1.69
0.4
1.75
0.4
1.75
1.18
0.36
1.18
0.59
0.59
0.59
2.1
6.49
2.66
6.49
2.6
10.1
2.6
10.1
5.94
2.39
5.94
4.08
4.08
4.08
18.3
Start Cap
P/N
Run Cap
P/N
Relay
P/N
Part
Type*
014-0058-25
014-0058-36
014-0059-09
014-0058-36
014-0036-18
014-0058-41
014-0059-18
014-0058-25
014-0058-43
014-0058-31
014-0058-27
014-0061-15
014-0061-15
014-0058-17
014-0064-09
040-0166-27
040-0172-03
040-0150-36
040-0166-21
040-0166-26
040-0172-03
040-0150-35
040-0166-30
040-0166-37
040-0172-05
040-0166-11
040-0168-03
040-0168-03
040-0168-02
RP
RC
RC
RP
RP
RC
RC
RP
RP
RC
RP
RC
RC
RC
014-0064-13
014-0064-33
014-0064-10
014-0064-14
014-0064-02
Protector
P/N
071-0561-28
071-0605-09
071-0561-16
071-0605-05
071-0647-02
071-0605-08
071-0561-55
071-0604-13
071-0604-14
071-0329-15
071-0329-15
071-0329-15
071-0329-11
* See Section F Introduction for more information.
FB21
Section_Fb.indd 21
3/4/2008 7:57:22 AM
Electrical Data - Copelametic - Air Cooled
Model
3AB1-0300-TAE
3AB1-0310-TAC
3AB1-0310-TAD
3AB1-0311-TAC
3AB1-0311-TAD
3AB1-031A-TAC
3AB1-031A-TAD
3AB2-0310-CAB
3AB2-031A-CAB
3ABA-031E-TAC
3ABA-031E-TAD
3ABA-031L-TAC
3ABB-032E-CAB
3ABB-032L-CAB
3AH1-0200-TAC
3AH1-0200-TAD
3AH1-0200-TAE
3AH1-020A-TAC
3AH1-020A-TAD
3AH2-0200-CAB
3AH2-0200-CAH
3AH2-020A-CAB
3AH2-020A-CAH
Volts PH
575
208/230
460
208/230
460
208/230
460
230
230
208/230
460
208/230
230
230
208/230
460
575
208/230
460
230
208
230
208
3
3
3
3
3
3
3
1
1
3
3
3
1
1
3
3
3
3
3
1
1
1
1
Max
LRA
RLA
4.4
8.2
5.5
10
5.1
10
5.1
14.7
14.7
10
5.1
10
14.7
14.7
6.6
3.7
2.3
6.6
3.7
9.3
12.4
9.3
12.4
30
82
41
82
41
82
41
86
86
82
41
82
86
86
46
23
20
46
23
58
57.2
58
57.2
Resistance
Run or
Start or
Line to WYE Line to Line
2.7
0.47
1.9
0.42
1.653
0.42
1.653
0.61
0.61
0.42
1.653
0.42
0.595
0.595
0.84
3.1
4.905
0.84
3.1
1.125
0.74
1.125
0.74
5.4
0.9
3.6
0.837
3.309
0.837
3.309
2.54
2.54
0.837
3.309
0.837
2.41
2.41
1.675
6
9.3
1.675
6
2.7
2.836
2.7
2.836
Start Cap Run Cap
P/N
P/N
Relay
P/N
Part Protector
Type*
P/N
014-0006-13 014-0064-12 040-0166-28
014-0006-13 014-0064-12 040-0166-28
RP
RP
014-0006-13 014-0064-14 040-0166-28
014-0006-13 014-0064-14 040-0166-28
RP
RP
014-0036-22
014-0036-22
014-0036-22
014-0036-22
RP
RP
RP
RP
014-0064-11
014-0064-11
014-0064-11
014-0064-11
040-0166-20
040-0166-20
040-0166-20
040-0166-20
071-0090-16
071-0090-01
071-0090-03
071-0090-37
071-0090-03
071-0090-37
071-0090-03
071-0119-01
071-0119-01
071-0090-37
071-0090-03
071-0090-37
071-0119-02
071-0119-02
071-0090-00
071-0090-08
071-0090-15
071-0090-00
071-0090-08
071-0092-18
071-0089-00
071-0092-18
071-0089-00
* See Section F Introduction for more information.
FC1
Section_Fc.indd 1
3/4/2008 7:59:55 AM
Electrical Data - Copelametic - Air Cooled
Model
3AJ1-0200-TAC
3AJ1-0200-TAD
3AJ1-0200-TAE
3AJ1-020A-TAC
3AJ1-020A-TAD
3AJ2-0200-CAB
3AJ2-0200-CAH
3AJ2-020A-CAB
3AJ2-0310-CAB
3AJA-0210-TAC
3AJA-021A-TAC
3AJA-021L-TAC
3AJB-0210-CAB
3AJB-021A-CAB
3WB1-0300-TAE
3WB1-0310-TAC
3WB1-0310-TAD
3WB1-0311-TAC
3WB1-031A-TAC
3WB2-0310-CAB
3WH1-0200-TAC
3WH1-0200-TAD
3WH1-0200-TAE
Volts PH
208/230
460
575
208/230
460
230
208
230
230
208/230
208/230
208/230
230
230
575
208/230
460
208/230
208/230
230
208/230
460
575
3
3
3
3
3
1
1
1
1
3
3
3
1
1
3
3
3
3
3
1
3
3
3
Max
LRA
RLA
5.6
3
2.3
5.6
3
9.5
12.4
9.5
12.6
9.2
9.2
9.2
14.4
14.4
4.4
8.2
5.5
10
10
14.7
6.6
3.7
2.3
46
23
20
46
23
58
57.2
58
86
82
82
82
86
86
30
82
41
82
82
86
46
23
20
Resistance
Run or
Start or
Line to WYE Line to Line
0.84
3.1
4.905
0.84
3.1
1.125
0.74
1.125
0.61
0.444
0.444
0.444
0.595
0.595
2.7
0.47
1.9
0.42
0.42
0.61
0.84
3.1
4.905
1.675
6
9.3
1.675
6
2.7
2.836
2.7
2.54
0.944
0.944
0.944
2.41
2.41
5.4
0.9
3.6
0.837
0.837
2.54
1.675
6
9.3
Start Cap Run Cap
P/N
P/N
014-0036-22 014-0064-11
014-0036-22 014-0064-11
014-0036-22 014-0064-11
014-0006-13 014-0064-12
Relay
P/N
Part Protector
Type*
P/N
040-0166-20
040-0166-20
040-0166-20
040-0166-28
RP
RP
RP
RP
014-0006-13 014-0064-12 040-0166-28
014-0006-13 014-0064-12 040-0166-28
RP
RP
014-0006-13 014-0064-12 040-0166-28
RP
071-0090-00
071-0090-08
071-0090-15
071-0090-00
071-0090-08
071-0092-18
071-0092-18
071-0092-18
071-0119-01
071-0090-44
071-0090-44
071-0090-44
071-0119-05
071-0119-05
071-0090-16
071-0090-01
071-0090-03
071-0090-37
071-0090-37
071-0119-01
071-0090-00
071-0090-08
071-0090-15
* See Section F Introduction for more information.
FC2
Section_Fc.indd 2
3/4/2008 8:00:01 AM
Electrical Data - Copelametic - Air Cooled
Model
3WH1-020A-TAD
3WH2-0200-CAB
3WH2-0200-CAH
3WJ1-0200-TAC
3WJ1-0200-TAD
3WJ1-0200-TAE
3WJ2-0200-CAB
3WJ2-0200-CAH
EAA1-0150-TAC
EAA1-0150-TAE
EAA1-015L-TAC
EAA2-0150-CAB
EAA2-0150-CAH
EAA2-015A-CAH
EAAA-015A-TAC
EAAB-015A-CAB
EAAB-015A-CAH
EAB1-0150-TAC
EAB1-0150-TAE
EAB1-015A-TAC
EAB2-0150-CAB
EAB2-0150-CAH
EAB2-015A-CAB
Volts PH
460
230
208
208/230
460
575
230
208
208/230
575
208/230
230
208
208
208/230
230
208
208/230
575
208/230
230
208
230
3
1
1
3
3
3
1
1
3
3
3
1
1
1
3
1
1
3
3
3
1
1
1
Max
LRA
RLA
3.7
9.3
12.4
5.6
3
2.3
9.5
12.4
5.9
2.2
5.9
8.9
8.3
8.3
5.9
8.9
8.3
5.8
2.2
5.8
6.4
5.6
6.4
23
58
57.2
46
23
20
58
57.2
38
14.3
38
41
44
44
38
41
44
38
14.3
38
41
44
41
Resistance
Run or
Start or
Line to WYE Line to Line
3.1
1.125
0.74
0.84
3.1
4.905
1.125
0.74
1.008
6.2
1.008
1.703
1.345
1.345
1.008
1.703
1.345
1.008
6.2
1.008
1.703
1.345
1.703
6
2.7
2.836
1.675
6
9.3
2.7
2.836
2.01
12.4
2.01
4.363
4.61
4.61
2.01
4.363
4.61
2.01
12.4
2.01
4.363
4.61
4.363
Start Cap Run Cap
P/N
P/N
Relay
P/N
Part Protector
Type*
P/N
014-0036-22
014-0036-22
014-0064-11 040-0166-20
014-0064-11 040-0166-20
RP
RP
014-0036-22
014-0036-22
014-0064-11 040-0166-20
014-0064-11 040-0166-20
RP
RP
014-0036-21 014-0064-10 040-0166-20
014-0036-21 014-0064-10 040-0166-30
014-0036-21 014-0064-10 040-0166-30
RP
RP
RP
014-0036-21 014-0064-10 040-0166-20
014-0036-21 014-0064-10 040-0166-30
RP
RP
014-0036-21 014-0064-10 040-0166-20
014-0036-21 014-0064-10 040-0166-30
014-0036-21 014-0064-10 040-0166-20
RP
RP
RP
071-0090-08
071-0092-18
071-0089-00
071-0090-00
071-0090-08
071-0090-15
071-0092-18
071-0092-18
071-0090-03
071-0090-21
071-0090-03
071-0092-18
071-0092-18
071-0092-18
071-0090-03
071-0092-16
071-0092-18
071-0090-03
071-0090-21
071-0090-03
071-0092-16
071-0092-16
071-0092-16
* See Section F Introduction for more information.
FC3
Section_Fc.indd 3
3/4/2008 8:00:01 AM
Electrical Data - Copelametic - Air Cooled
Model
EABA-0200-TAC
EABA-0200-TAD
EABA-0200-TAE
EABA-020A-TAC
EABB-0200-CAB
EABB-020A-CAB
EAC1-0150-TAC
EAC1-0150-TAE
EAC2-0150-CAB
EAC2-0150-CAH
EAC2-015A-CAB
EACA-0200-TAC
EACA-0200-TAD
EACA-0200-TAE
EACA-020A-TAC
EACA-020A-TAD
EACB-0200-CAB
EACB-0200-CAH
EAD1-0200-TAC
EAD1-0200-TAD
EAD1-0200-TAE
EAD1-020L-TAC
EAD1-0320-TAC
Volts PH
208/230
460
575
208/230
230
230
208/230
575
230
208
230
208/230
460
575
208/230
460
230
208
208/230
460
575
208/230
208/230
3
3
3
3
1
1
3
3
1
1
1
3
3
3
3
3
1
1
3
3
3
3
3
Max
LRA
RLA
6.8
3.6
2.3
6.8
8.4
8.4
6
2.2
7.1
6.4
7.1
6.6
3.5
2.3
6.6
3.5
8.4
11.9
NA
NA
NA
6.8
12.4
46
23
20
46
58
58
38
14.3
41
44
41
46
23
20
46
23
58
57.2
46
23
20
46
85
Resistance
Run or
Start or
Line to WYE Line to Line
0.84
3.346
4.905
0.84
1.125
1.125
1.008
6.2
1.703
1.345
1.703
0.84
3.346
4.905
0.84
3.346
1.125
0.74
0.84
3.346
4.905
0.84
0.419
1.675
6.692
9.3
1.675
2.7
2.7
2.01
12.4
4.363
4.61
4.363
1.675
6.692
9.3
1.675
6.692
2.7
2.836
1.675
6.692
9.3
1.675
0.838
Start Cap Run Cap
P/N
P/N
014-0036-22
014-0036-22
Relay
P/N
Part Protector
Type*
P/N
014-0064-11 040-0166-20
014-0064-11 040-0166-20
RP
RP
014-0036-21 014-0064-10 040-0166-20
014-0036-21 014-0064-10 040-0166-30
014-0036-21 014-0064-10 040-0166-20
RP
RP
RP
014-0036-22
014-0036-22
RP
RP
014-0064-11 040-0166-20
014-0064-11 040-0166-20
071-0090-00
071-0090-08
071-0090-15
071-0090-00
071-0092-18
071-0092-18
071-0090-03
071-0090-21
071-0092-16
071-0092-16
071-0092-16
071-0090-00
071-0090-08
071-0090-15
071-0090-00
071-0090-08
071-0092-18
071-0092-18
071-0090-00
071-0090-08
071-0090-15
071-0090-00
071-0090-38
* See Section F Introduction for more information.
FC4
Section_Fc.indd 4
3/4/2008 8:00:01 AM
Electrical Data - Copelametic - Air Cooled
Model
EAD1-0320-TAD
EAD1-032A-TAC
EAD1-032A-TAD
EAD1-032L-TAC
EAD1-032L-TAD
EAD2-0200-CAB
EAD2-0200-CAH
EAD2-020A-CAH
EAD2-020L-CAB
EAD2-0320-CAB
EADA-0200-TAC
EADA-0200-TAD
EADA-020A-TAC
EADA-020A-TAD
EADA-020E-TAC
EADA-020L-TAC
EADB-0200-CAB
EADB-020A-CAB
EADB-021E-CAB
EADB-021L-CAB
EAJ1-0150-TAC
EAJ1-0150-TAE
EAJ2-0150-CAB
Volts PH
460
208/230
460
208/230
460
230
208
208
230
230
208/230
460
208/230
460
208/230
208/230
230
230
230
230
208/230
575
230
3
3
3
3
3
1
1
1
1
1
3
3
3
3
3
3
1
1
1
1
3
3
1
Max
LRA
RLA
5.2
12.4
5.2
12.4
5.2
NA
NA
12.4
8.4
16
6.8
3.1
6.8
3.1
6.8
6.8
8.5
8.5
10
10
5.9
2.2
6.6
42
85
42
85
42
58
57.2
57.2
58
102
46
20.4
46
20.4
46
46
58
58
58
58
38
14.3
41
Resistance
Run or
Start or
Line to WYE Line to Line
1.641
0.419
1.641
0.419
1.641
1.125
0.74
0.74
1.125
0.519
0.84
0
0.84
0
0.84
0.84
1.125
1.125
1.125
1.125
1.008
6.2
1.703
3.282
0.838
3.282
0.838
3.282
2.7
2.836
2.836
2.7
2.435
1.675
6.765
1.675
6.765
1.675
1.675
2.7
2.7
2.7
2.7
2.01
12.4
4.363
Start Cap Run Cap
P/N
P/N
Relay
P/N
Part Protector
Type*
P/N
014-0036-22 014-0064-11
014-0036-22 014-0064-11
014-0036-22 014-0064-11
014-0036-22 014-0064-11
014-0006-13 014-0064-14
040-0166-20
040-0166-20
040-0166-20
040-0166-20
040-0166-28
RP
RP
RP
RP
RP
014-0036-22
014-0036-22
014-0036-22
014-0036-22
040-0166-20
040-0166-20
040-0166-20
040-0166-20
RP
RP
RP
RP
014-0036-21 014-0064-10 040-0166-20
RP
014-0064-11
014-0064-11
014-0064-11
014-0064-11
071-0090-03
071-0090-38
071-0090-03
071-0090-38
071-0090-03
071-0092-18
071-0092-18
071-0092-18
071-0092-18
071-0119-06
071-0090-00
071-0090-15
071-0090-00
071-0090-15
071-0090-00
071-0090-00
071-0092-18
071-0092-18
071-0099-03
071-0099-03
071-0090-03
071-0090-21
071-0092-16
* See Section F Introduction for more information.
FC5
Section_Fc.indd 5
3/4/2008 8:00:02 AM
Electrical Data - Copelametic - Air Cooled
Model
EAJ2-0150-CAH
EAJA-015A-TAC
EAJB-015A-CAB
EAJB-015A-CAH
EAL1-0200-TAC
EAL1-0200-TAD
EAL1-0200-TAE
EAL1-020A-TAD
EAL2-0200-CAB
EAL2-0200-CAH
EALA-020A-TAC
EALB-020A-CAB
EALB-020A-CAH
EAV1-0150-TAC
EAV1-0150-TAE
EAV1-015A-TAC
EAV1-0200-TA7
EAV1-0200-TAC
EAV1-0200-TAD
EAV1-0200-TAE
EAV1-0200-TAU
EAV1-020L-TAC
EAV1-020L-TAD
Volts PH
208
208/230
230
208
208/230
460
575
460
230
208
208/230
230
208
208/230
575
208/230
380
208/230
460
575
200
208/230
460
1
3
1
1
3
3
3
3
1
1
3
1
1
3
3
3
3
3
3
3
3
3
3
Max
LRA
RLA
5.9
5.9
6.6
5.9
NA
NA
NA
NA
NA
NA
7.1
8.7
12.9
5.6
2.2
5.6
NA
NA
NA
NA
NA
6.6
3.5
44
38
41
44
46
23
20
23
58
57.2
46
58
57.2
38
14.3
38
31.5
46
23
20
57.1
46
23
Resistance
Run or
Start or
Line to WYE Line to Line
1.345
1.008
1.703
1.345
0.84
3.346
4.905
3.346
1.125
0.74
0.84
1.125
0.74
1.008
6.2
1.008
0
0.84
3.346
4.905
0
0.84
3.346
4.61
2.01
4.363
4.61
1.675
6.692
9.3
6.692
2.7
2.836
1.675
2.7
2.836
2.01
12.4
2.01
3.38
1.675
6.692
9.3
0.994
1.675
6.692
Start Cap Run Cap
P/N
P/N
Relay
P/N
Part Protector
Type*
P/N
014-0036-21 014-0064-10 040-0166-30
RP
014-0036-21 014-0064-10 040-0166-20
014-0036-21 014-0064-10 040-0166-30
RP
RP
014-0036-22
014-0036-22
014-0064-11 040-0166-20
014-0064-11 040-0166-20
RP
RP
014-0036-22
014-0036-22
014-0064-11 040-0166-20
014-0064-11 040-0166-20
RP
RP
071-0092-16
071-0090-03
071-0092-16
071-0092-16
071-0090-00
071-0090-08
071-0090-15
071-0090-08
071-0092-18
071-0092-18
071-0090-00
071-0092-18
071-0092-18
071-0090-03
071-0090-21
071-0090-03
071-0090-03
071-0090-00
071-0090-08
071-0090-15
071-0090-17
071-0090-00
071-0090-08
* See Section F Introduction for more information.
FC6
Section_Fc.indd 6
3/4/2008 8:00:02 AM
Electrical Data - Copelametic - Air Cooled
Model
EAV2-0150-CAB
EAV2-0150-CAH
EAV2-015A-CAB
EAV2-0200-CAB
EAV2-0200-CAH
EAVA-0200-TAU
EAVA-020E-TA7
EAVA-020E-TAU
EAVA-020L-TA7
EAVA-020L-TAU
EAVA-0210-TAC
EAVA-0210-TAD
EAVA-021A-TAC
EAVA-021A-TAD
EAVA-021E-TAC
EAVA-021E-TAD
EAVA-021E-TAE
EAVA-021L-TAC
EAVA-021L-TAD
EAVB-015A-CAH
EAVB-020A-CAB
EAVB-020A-CAH
EAVB-0210-CAV
Volts PH
230
208
230
230
208
200
380
200
380
200
208/230
460
208/230
460
208/230
460
575
208/230
460
208
230
208
208/230
1
1
1
1
1
3
3
3
3
3
3
3
3
3
3
3
3
3
3
1
1
1
1
Max
LRA
RLA
6.4
5.5
6.4
NA
NA
9.7
4.7
9.7
4.7
9.7
7.4
3.9
7.4
3.9
7.4
3.9
3.1
7.4
3.9
5.5
9.6
12.4
14.7
41
44
41
58
57.2
57.1
31.5
57.1
31.5
57.1
50
26.6
50
26.6
50
26.6
20
50
26.6
44
58
57.2
102
Resistance
Run or
Start or
Line to WYE Line to Line
1.703
1.345
1.703
1.125
0.74
0
0
0
0
0
0
0
0
0
0
0
4.905
0
0
1.345
1.125
0.74
0.519
4.363
4.61
4.363
2.7
2.836
0.994
3.38
0.994
3.38
0.994
1.2
4.73
1.2
4.73
1.2
4.73
9.3
1.2
4.73
4.61
2.7
2.836
2.435
Start Cap Run Cap
P/N
P/N
Relay
P/N
Part Protector
Type*
P/N
014-0036-21 014-0064-10 040-0166-20
014-0036-21 014-0064-10 040-0166-30
014-0036-21 014-0064-10 040-0166-20
014-0036-22 014-0064-11 040-0166-20
014-0036-22 014-0064-11 040-0166-20
RP
RP
RP
RP
RP
014-0036-21 014-0064-10 040-0166-30
014-0036-22 014-0064-11 040-0166-20
014-0036-22 014-0064-11 040-0166-20
014-0006-13 014-0064-14 040-0166-28
RP
RP
RP
RP
071-0092-16
071-0092-16
071-0092-16
071-0099-01
071-0099-02
071-0090-17
071-0090-03
071-0090-17
071-0090-03
071-0090-17
071-0090-35
071-0090-13
071-0090-35
071-0090-13
071-0090-35
071-0090-13
071-0090-52
071-0090-35
071-0090-13
071-0092-16
071-0099-01
071-0099-02
071-0119-05
* See Section F Introduction for more information.
FC7
Section_Fc.indd 7
3/4/2008 8:00:03 AM
Electrical Data - Copelametic - Air Cooled
Model
EAVB-021A-CAV
EAVB-021E-CAV
EAVB-021L-CAV
EWA1-0150-TAC
EWA1-0150-TAE
EWA2-0150-CAB
EWA2-0150-CAH
EWB1-0150-TAC
EWB2-0150-CAB
EWBA-0200-TAC
EWBA-0200-TAD
EWBA-0200-TAE
EWBB-0200-CAB
EWC1-0150-TAC
EWCA-0200-TAC
EWCA-0200-TAD
EWCA-0200-TAE
EWCA-020A-TAC
EWCA-020A-TAD
EWCB-0200-CAB
EWCB-0200-CAH
EWD1-0200-TAC
EWD1-0200-TAD
Volts PH
208/230
208/230
208/230
208/230
575
230
208
208/230
230
208/230
460
575
230
208/230
208/230
460
575
208/230
460
230
208
208/230
460
1
1
1
3
3
1
1
3
1
3
3
3
1
3
3
3
3
3
3
1
1
3
3
Max
LRA
RLA
14.7
14.7
14.7
5.9
2.2
8.9
8.3
5.8
6.4
6.8
3.6
2.3
8.4
6
6.6
3.5
2.3
6.6
3.5
8.4
11.9
NA
3.4
102
102
102
38
14.3
41
44
38
41
46
23
20
58
38
46
23
20
46
23
58
57.2
46
23
Resistance
Run or
Start or
Line to WYE Line to Line
0.519
0.519
0.519
1.008
6.2
1.703
1.345
1.008
1.703
0.84
3.346
4.905
1.125
1.008
0.84
3.346
4.905
0.84
3.346
1.125
0.74
0.84
3.346
2.435
2.435
2.435
2.01
12.4
4.363
4.61
2.01
4.363
1.675
6.692
9.3
2.7
2.01
1.675
6.692
9.3
1.675
6.692
2.7
2.836
1.675
6.692
Start Cap Run Cap
P/N
P/N
Relay
P/N
Part Protector
Type*
P/N
014-0006-13 014-0064-14 040-0166-28
014-0006-13 014-0064-14 040-0166-28
014-0006-13 014-0064-14 040-0166-28
RP
RP
RP
014-0036-21 014-0064-10 040-0166-20
014-0036-21 014-0064-10 040-0166-30
RP
RP
014-0036-21 014-0064-10 040-0166-20
RP
014-0036-22
014-0064-11 040-0166-20
RP
014-0036-22
014-0036-22
014-0064-11 040-0166-20
014-0064-11 040-0166-20
RP
RP
071-0119-05
071-0119-05
071-0119-05
071-0090-03
071-0090-21
071-0092-18
071-0092-18
071-0090-03
071-0092-16
071-0090-00
071-0090-08
071-0090-15
071-0092-18
071-0090-03
071-0090-00
071-0090-08
071-0090-15
071-0090-00
071-0090-08
071-0092-18
071-0092-18
071-0090-00
071-0090-08
* See Section F Introduction for more information.
FC8
Section_Fc.indd 8
3/4/2008 8:00:03 AM
Electrical Data - Copelametic - Air Cooled
Model
EWDA-020A-TAC
EWJ1-0150-TAC
EWJ1-0150-TAE
EWJ2-0150-CAB
EWJ2-0150-CAH
EWL1-0200-TAC
EWL1-0200-TAD
EWL1-0200-TAE
EWL1-020A-TAC
EWL2-0200-CAB
EWL2-0200-CAH
EWV1-0150-TAC
EWV1-0200-TAC
EWV1-0200-TAD
EWV1-0200-TAE
EWV1-020A-TAC
EWV1-020A-TAD
EWV2-0150-CAB
EWV2-0150-CAH
EWV2-0200-CAB
EWV2-0200-CAH
EWVA-021E-TAC
EWVA-021E-TAD
Volts PH
208/230
208/230
575
230
208
208/230
460
575
208/230
230
208
208/230
208/230
460
575
208/230
460
230
208
230
208
208/230
460
3
3
3
1
1
3
3
3
3
1
1
3
3
3
3
3
3
1
1
1
1
3
3
Max
LRA
RLA
6.8
5.9
2.2
6.6
5.9
7.1
3.7
2.3
7.1
8.7
12.9
5.6
6.6
3.5
2.3
6.6
3.5
6.4
5.5
9.6
12.4
7.4
3.9
46
38
14.3
41
44
46
23
20
46
58
57.2
38
46
23
20
46
23
41
44
58
57.2
50
26.6
Resistance
Run or
Start or
Line to WYE Line to Line
0.84
1.008
6.2
1.703
1.345
0.84
3.346
4.905
0.84
1.125
0.74
1.008
0.84
3.346
4.905
0.84
3.346
1.703
1.345
1.125
0.74
0
0
1.675
2.01
12.4
4.363
4.61
1.675
6.692
9.3
1.675
2.7
2.836
2.01
1.675
6.692
9.3
1.675
6.692
4.363
4.61
2.7
2.836
1.2
4.73
Start Cap Run Cap
P/N
P/N
Relay
P/N
Part Protector
Type*
P/N
014-0036-21 014-0064-10 040-0166-20
014-0036-21 014-0064-10 040-0166-30
RP
RP
014-0036-22
014-0036-22
014-0064-11 040-0166-20
014-0064-11 040-0166-20
RP
RP
014-0036-21 014-0064-10 040-0166-20
014-0036-21 014-0064-10 040-0166-30
014-0036-22 014-0064-11 040-0166-20
014-0036-22 014-0064-11 040-0166-20
RP
RP
RP
RP
071-0090-00
071-0090-03
071-0090-21
071-0092-16
071-0092-16
071-0090-00
071-0090-08
071-0090-15
071-0090-00
071-0092-18
071-0092-18
071-0090-03
071-0090-00
071-0090-08
071-0090-15
071-0090-00
071-0090-08
071-0092-16
071-0092-16
071-0099-01
071-0099-02
071-0090-35
071-0090-13
* See Section F Introduction for more information.
FC9
Section_Fc.indd 9
3/4/2008 8:00:03 AM
Electrical Data - Copelametic - Air Cooled
Model
EWVB-021E-CAV
HAF2-0025-IAA
HAF2-0025-IAB
HAF2-0025-SAA
HAF2-0033-IAA
HAF2-0033-IAB
HAFB-0033-IAA
HAFB-0034-IAA
HAFB-003E-IAA
HAFB-003L-IAA
HAG1-0050-TAC
HAG1-005L-TAC
HAG2-0050-CAA
HAG2-0050-CAV
HAG2-005L-CAV
HAGA-005E-TAC
HAGA-005L-TAC
HAGB-005E-CAV
HAGB-005L-CAV
HAJ1-0050-TAC
HAJ1-005L-TAC
HAJ2-0025-IAA
HAJ2-0025-IAB
Volts PH
208/230
115
230
115
115
230
115
115
115
115
208/230
208/230
115
208/230
208/230
208/230
208/230
208/230
208/230
208/230
208/230
115
230
1
1
1
1
1
1
1
1
1
1
3
3
1
1
1
3
3
1
1
3
3
1
1
Max
LRA
RLA
14.7
3.9
2.3
3.9
5.4
2.5
5.4
5.9
5.4
5.4
2.4
2.4
8.6
4
4
2.4
2.4
4
4
2.2
2.2
4.1
2.1
102
23
12.2
22.5
31
12
31
43.5
31
31
13
13
44
22
22
13
13
22
22
13
13
23
12.2
Resistance
Run or
Start or
Line to WYE Line to Line
0.519
1.76
6.76
1.82
1.23
5.07
1.23
0.875
1.23
1.23
3.62
3.62
0.755
3
3
3.62
3.62
3
3
3.62
3.62
1.76
6.76
2.435
4.48
17.87
17.24
3.1
12.505
3.1
2.39
3.1
3.1
7.24
7.24
2.36
9.455
9.455
7.24
7.24
9.455
9.455
7.24
7.24
4.48
17.87
Start Cap Run Cap
P/N
P/N
Relay
P/N
Part Protector
Type*
P/N
014-0006-13 014-0064-14 040-0166-28
014-0061-06
040-0115-00
014-0061-13
040-0115-01
040-0115-00
014-0061-07
040-0166-08
014-0061-12
040-0166-19
014-0061-07
040-0166-08
014-0061-07
040-0166-08
014-0061-07
040-0166-08
014-0061-07
040-0166-08
RP
RC
RC
RC
RP
RP
RP
RP
RP
RP
014-0061-02 014-0064-00 040-0166-33
014-0036-21 014-0064-00 040-0166-09
014-0036-21 014-0064-00 040-0166-09
RP
RP
RP
014-0036-21 014-0064-00 040-0166-09
014-0036-21 014-0064-00 040-0166-09
RP
RP
014-0061-06
014-0061-13
RC
RC
040-0115-00
040-0115-01
071-0119-05
071-0092-37
071-0092-32
071-0092-37
071-0092-04
071-0092-31
071-0092-04
071-0092-35
071-0092-04
071-0092-04
071-0090-42
071-0090-42
071-0099-03
071-0092-27
071-0092-27
071-0090-42
071-0090-42
071-0092-27
071-0092-27
071-0090-42
071-0090-42
071-0092-37
071-0092-32
* See Section F Introduction for more information.
FC10
Section_Fc.indd 10
3/4/2008 8:00:04 AM
Electrical Data - Copelametic - Air Cooled
Model
HAJ2-0025-SAA
HAJ2-0033-IAA
HAJ2-0033-IAB
HAJ2-0050-CAA
HAJ2-0050-CAV
HAJ2-0050-IAA
HAJ2-005L-CAV
HAJA-005E-TAC
HAJA-005L-TAC
HAJB-003E-IAA
HAJB-003L-IAA
HAJB-005E-CAV
HAJB-005L-CAV
HAK2-0033-IAA
HAK2-0033-IAB
HAK2-0050-IAA
HAK2-0050-IAB
HAT2-0033-IAA
HAT2-0033-IAB
HAT2-0050-IAA
HAT2-0050-IAB
HATB-0051-CAA
HATB-005E-CAA
Volts PH
115
115
230
115
208/230
115
208/230
208/230
208/230
115
115
208/230
208/230
115
230
115
230
115
230
115
230
115
115
1
1
1
1
1
1
1
3
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Max
LRA
RLA
4.1
5.2
2.5
8.5
3.7
7.1
3.7
2.2
2.2
4.7
4.7
3.7
3.7
5
2.4
6.6
4
5.2
2.4
6.9
3.9
8.9
10.4
22.5
31
12
44
22
43.5
22
13
13
31
31
22
22
31
12
43.5
20.2
31
12
43.5
20.2
58
58
Resistance
Run or
Start or
Line to WYE Line to Line
1.82
1.23
5.07
0.755
3
0.875
3
3.62
3.62
1.23
1.23
3
3
1.23
5.07
0.875
3.48
1.23
5.07
0.875
3.48
0.509
0.509
17.24
3.1
12.505
2.36
9.455
2.39
9.455
7.24
7.24
3.1
3.1
9.455
9.455
3.1
12.505
2.39
9.6
3.1
12.505
2.39
9.6
2.155
2.155
Start Cap Run Cap
P/N
P/N
Relay
P/N
Part Protector
Type*
P/N
040-0115-00
014-0061-07
040-0166-08
014-0061-12
040-0166-19
014-0061-02 014-0064-00 040-0166-33
014-0036-21 014-0064-00 040-0166-09
014-0061-02
040-0166-08
014-0036-21 014-0064-00 040-0166-09
RC
RP
RP
RP
RP
RP
RP
014-0061-07
014-0061-07
014-0036-21
014-0036-21
014-0061-07
014-0061-12
014-0061-02
014-0061-09
014-0061-07
014-0061-12
014-0061-02
014-0061-09
014-0061-02
014-0061-02
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
014-0064-00
014-0064-00
014-0064-04
014-0064-04
040-0166-08
040-0166-08
040-0166-09
040-0166-09
040-0166-08
040-0166-19
040-0166-08
040-0166-09
040-0166-08
040-0166-19
040-0166-08
040-0166-09
040-0166-11
040-0166-11
071-0092-37
071-0092-04
071-0092-31
071-0099-03
071-0092-27
071-0092-35
071-0092-27
071-0090-42
071-0090-42
071-0092-04
071-0092-04
071-0092-27
071-0092-27
071-0092-04
071-0092-31
071-0092-35
071-0092-05
071-0092-04
071-0092-31
071-0092-35
071-0092-05
071-0099-03
071-0099-03
* See Section F Introduction for more information.
FC11
Section_Fc.indd 11
3/4/2008 8:00:04 AM
Electrical Data - Copelametic - Air Cooled
Model
HATB-005E-CAV
HATB-005L-CAA
HWF2-0025-IAA
HWF2-0025-IAB
HWF2-0033-IAA
HWF2-0033-IAB
HWFB-003E-IAA
HWG1-0050-TAC
HWG2-0050-CAA
HWG2-0050-CAV
HWGA-005E-TAC
HWGA-005L-TAC
HWGB-005E-CAV
HWGB-005L-CAV
HWJ1-0050-TAC
HWJ2-0025-IAA
HWJ2-0025-IAB
HWJ2-0033-IAA
HWJ2-0033-IAB
HWJ2-0050-CAA
HWJ2-0050-CAV
HWJA-005E-TAC
HWJA-005L-TAC
Volts PH
208/230
115
115
230
115
230
115
208/230
115
208/230
208/230
208/230
208/230
208/230
208/230
115
230
115
230
115
208/230
208/230
208/230
1
1
1
1
1
1
1
3
1
1
3
3
1
1
3
1
1
1
1
1
1
3
3
Max
LRA
RLA
3.3
10.4
3.9
2.3
5.4
2.5
5.4
2.4
8.6
4
2.4
2.4
4
4
2.2
4.1
2.1
5.2
2.5
8.5
3.7
2.2
2.2
22
58
23
12.2
31
12
31
13
44
22
13
13
22
22
13
23
12.2
31
12
44
22
13
13
Resistance
Run or
Start or
Line to WYE Line to Line
3
0.509
1.76
6.76
1.23
5.07
1.23
3.62
0.755
3
3.62
3.62
3
3
3.62
1.76
6.76
1.23
5.07
0.755
3
3.62
3.62
9.455
2.155
4.48
17.87
3.1
12.505
3.1
7.24
2.36
9.455
7.24
7.24
9.455
9.455
7.24
4.48
17.87
3.1
12.505
2.36
9.455
7.24
7.24
Start Cap Run Cap
P/N
P/N
Relay
P/N
Part Protector
Type*
P/N
014-0036-21 014-0064-00 040-0166-25
014-0061-02 014-0064-04 040-0166-11
014-0061-06
040-0115-00
014-0061-13
040-0115-01
014-0061-07
040-0166-08
014-0061-12
040-0166-19
014-0061-07
040-0166-08
RP
RP
RC
RC
RP
RP
RP
014-0061-02 014-0064-00 040-0166-33
014-0036-21 014-0064-00 040-0166-09
RP
RP
014-0036-21 014-0064-00 040-0166-09
014-0036-21 014-0064-00 040-0166-09
RP
RP
014-0061-06
040-0115-00
014-0061-13
040-0115-01
014-0061-07
040-0166-08
014-0061-12
040-0166-19
014-0061-02 014-0064-00 040-0166-33
014-0036-21 014-0064-00 040-0166-09
RC
RC
RP
RP
RP
RP
071-0092-27
071-0099-03
071-0092-37
071-0092-32
071-0092-04
071-0092-31
071-0092-04
071-0090-42
071-0099-03
071-0092-27
071-0090-42
071-0090-42
071-0092-27
071-0092-27
071-0090-42
071-0092-37
071-0092-32
071-0092-04
071-0092-31
071-0099-03
071-0092-27
071-0090-42
071-0090-42
* See Section F Introduction for more information.
FC12
Section_Fc.indd 12
3/4/2008 8:00:05 AM
Electrical Data - Copelametic - Air Cooled
Model
HWJB-005E-CAV
HWK2-0033-IAA
HWK2-0033-IAB
HWK2-0050-IAA
HWK2-0050-IAB
HWT2-0033-IAA
HWT2-0033-IAB
HWT2-0050-IAA
HWT2-0050-IAB
KAA1-0075-TAC
KAA1-007A-TAC
KAA2-0075-CAA
KAA2-0075-CAV
KAA2-0075-IAA
KAA2-0075-IAB
KAA2-0075-IAH
KAA2-0076-CAA
KAA2-007A-IAA
KAA2-007A-IAB
KAA2-007A-IAH
KAAB-0075-IAA
KAAB-007A-CAV
KAAB-007A-IAA
Volts PH
208/230
115
230
115
230
115
230
115
230
208/230
208/230
115
208/230
115
230
208
115
115
230
208
115
208/230
115
1
1
1
1
1
1
1
1
1
3
3
1
1
1
1
1
1
1
1
1
1
1
1
Max
LRA
RLA
3.7
5
2.4
6.6
4
5.2
2.4
6.9
3.9
2.6
2.6
NA
5.2
10.2
5.4
5.6
8.9
10.2
5.4
5.6
10.2
5.2
10.2
22
31
12
43.5
20.2
31
12
43.5
20.2
19.9
19.9
44
36
59.8
30.4
34.1
65
59.8
30.4
34.1
59.8
36
59.8
Resistance
Run or
Start or
Line to WYE Line to Line
3
1.23
5.07
0.875
3.48
1.23
5.07
0.875
3.48
2.28
2.28
0.57
1.9
0.59
2.34
2
0.519
0.59
2.34
2
0.59
1.9
0.59
9.455
3.1
12.505
2.39
9.6
3.1
12.505
2.39
9.6
4.551
4.551
7
4.24
1.4
5.53
5.15
1.266
1.4
5.53
5.15
1.4
4.24
1.4
Start Cap Run Cap
P/N
P/N
Relay
P/N
Part Protector
Type*
P/N
014-0036-21 014-0064-00 040-0166-09
014-0061-07
040-0166-08
014-0061-12
040-0166-19
014-0061-02
040-0166-08
014-0061-09
040-0166-09
014-0061-07
040-0166-08
014-0061-12
040-0166-19
014-0061-02
040-0166-08
014-0061-09
040-0166-09
RP
RP
RP
RP
RP
RP
RP
RP
RP
014-0061-14
014-0061-04
014-0061-11
014-0061-04
014-0061-04
014-0061-11
014-0061-11
014-0061-04
014-0061-04
014-0061-11
014-0061-04
014-0061-11
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
014-0064-02 040-0166-11
014-0064-00 040-0166-09
040-0166-08
040-0166-09
040-0166-09
014-0064-06 040-0166-33
040-0166-08
040-0166-09
040-0166-09
040-0166-08
014-0064-00 040-0166-09
040-0166-08
071-0092-27
071-0092-04
071-0092-31
071-0092-35
071-0092-05
071-0092-04
071-0092-31
071-0092-35
071-0092-05
071-0090-05
071-0090-05
071-0092-20
071-0092-29
071-0099-00
071-0092-27
071-0092-27
071-0092-38
071-0099-00
071-0092-27
071-0092-27
071-0099-00
071-0092-29
071-0099-00
* See Section F Introduction for more information.
FC13
Section_Fc.indd 13
3/4/2008 8:00:05 AM
Electrical Data - Copelametic - Air Cooled
Model
KAAB-007E-CAA
KAAB-007E-CAV
KAAB-007L-CAA
KAD1-0075-TAC
KAD2-0075-CAA
KAD2-0075-CAV
KAE1-0050-TAC
KAE1-0075-TAC
KAE1-007L-TAC
KAE2-0050-CAV
KAE2-0050-IAA
KAE2-0050-IAB
KAE2-0050-IAH
KAE2-005A-IAB
KAE2-005A-IAH
KAE2-0075-CAA
KAE2-0075-CAV
KAE2-007L-CAV
KAEA-005A-TAC
KAEA-0075-TAC
KAEA-007A-TAC
KAEA-007E-TAC
KAEA-007L-TAC
Volts PH
115
208/230
115
208/230
115
208/230
208/230
208/230
208/230
208/230
115
230
208
230
208
115
208/230
208/230
208/230
208/230
208/230
208/230
208/230
1
1
1
3
1
1
3
3
3
1
1
1
1
1
1
1
1
1
3
3
3
3
3
Max
LRA
RLA
10.2
5.8
10.2
2.4
9.9
5.1
1.9
3.4
3.4
3.4
7.8
4.1
4.1
4.1
4.1
10.9
5.4
5.4
1.9
3.4
3.4
3.4
3.4
59.8
36
59.8
19.9
65
36
13.2
19.9
19.9
24
45
22.5
25.5
22.5
25.5
65
36
36
13.2
19.9
19.9
19.9
19.9
Resistance
Run or
Start or
Line to WYE Line to Line
0.59
1.9
0.59
2.28
0.519
1.9
3.34
2.28
2.28
2.9
0.835
3.305
2.92
3.305
2.92
0.519
1.9
1.9
3.34
2.28
2.28
2.28
2.28
1.4
4.24
1.4
4.551
1.266
4.24
6.69
4.551
4.551
5.785
2.42
9.585
7.9
9.585
7.9
1.266
4.24
4.24
6.69
4.551
4.551
4.551
4.551
Start Cap Run Cap
P/N
P/N
Relay
P/N
Part Protector
Type*
P/N
014-0061-11 014-0064-11 040-0166-08
014-0061-04 014-0064-00 040-0166-09
014-0061-11 014-0064-11 040-0166-08
RP
RP
RP
014-0061-11 014-0064-06 040-0166-33
014-0061-04 014-0064-00 040-0166-09
RP
RP
014-0036-21
014-0061-02
014-0061-09
014-0061-09
014-0061-09
014-0061-09
014-0061-11
014-0061-04
014-0061-04
RP
RP
RP
RP
RP
RP
RP
RP
RP
014-0064-00 040-0166-09
040-0166-08
040-0166-09
040-0166-09
040-0166-09
040-0166-09
014-0064-06 040-0166-33
014-0064-00 040-0166-09
014-0064-00 040-0166-09
071-0099-00
071-0092-29
071-0099-00
071-0090-05
071-0099-07
071-0092-29
071-0090-06
071-0090-41
071-0090-41
071-0092-37
071-0092-06
071-0092-05
071-0092-05
071-0092-05
071-0092-05
071-0099-06
071-0092-29
071-0092-29
071-0090-06
071-0090-41
071-0090-41
071-0090-41
071-0090-41
* See Section F Introduction for more information.
FC14
Section_Fc.indd 14
3/4/2008 8:00:06 AM
Electrical Data - Copelametic - Air Cooled
Model
KAEB-005A-CAV
KAEB-005A-IAA
KAEB-007A-CAA
KAEB-007A-CAV
KAEB-007E-CAA
KAEB-007E-CAV
KAEB-007L-CAA
KAEB-007L-CAV
KAG1-0050-TAC
KAG1-005A-TAC
KAG1-0075-TAC
KAG1-0100-TAC
KAG1-0100-TAD
KAG2-0050-CAV
KAG2-0050-IAA
KAG2-0050-IAB
KAG2-0050-IAH
KAG2-005A-IAA
KAG2-0075-CAA
KAG2-0075-CAV
KAG2-0075-IAA
KAG2-0075-IAB
KAG2-0075-IAH
Volts PH
208/230
115
115
208/230
115
208/230
115
208/230
208/230
208/230
208/230
208/230
460
208/230
115
230
208
115
115
208/230
115
230
208
1
1
1
1
1
1
1
1
3
3
3
3
3
1
1
1
1
1
1
1
1
1
1
Max
LRA
RLA
3.4
7.8
10.9
5.4
10.9
5.4
10.9
5.4
1.9
1.9
2.6
4.1
1.6
3.6
7.8
4.1
4.1
7.8
NA
5.4
9.5
5.4
5.6
24
45
65
36
65
36
65
36
13.2
13.2
19.9
27
13.5
24
45
22.5
25.5
45
44
36
59.8
30.4
34.1
Resistance
Run or
Start or
Line to WYE Line to Line
2.9
0.835
0.519
1.9
0.519
1.9
0.519
1.9
3.34
3.34
2.28
1.59
6.24
2.9
0.835
3.305
2.92
0.835
0.57
1.9
0.59
2.34
2
5.785
2.42
1.266
4.24
1.266
4.24
1.266
4.24
6.69
6.69
4.551
3.179
12.48
5.785
2.42
9.585
7.9
2.42
7
4.24
1.4
5.53
5.15
Start Cap Run Cap
P/N
P/N
014-0036-21
014-0061-02
014-0061-11
014-0061-04
014-0061-11
014-0061-04
014-0061-11
014-0061-04
Relay
P/N
Part Protector
Type*
P/N
014-0064-00 040-0166-09
040-0166-08
014-0064-06 040-0166-33
014-0064-00 040-0166-09
014-0064-06 040-0166-33
014-0064-00 040-0166-09
014-0064-06 040-0166-33
014-0064-00 040-0166-09
RP
RP
RP
RP
RP
RP
RP
RP
014-0036-21 014-0064-00 040-0166-09
014-0061-02
040-0166-08
014-0061-09
040-0166-09
014-0061-09
040-0166-09
014-0061-02
040-0166-08
014-0061-14 014-0064-02 040-0166-11
014-0061-04 014-0064-00 040-0166-09
014-0061-11
040-0166-08
014-0061-04
040-0166-09
014-0061-04
040-0166-09
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
071-0092-37
071-0092-06
071-0099-06
071-0092-29
071-0099-06
071-0092-29
071-0099-06
071-0092-29
071-0090-06
071-0090-06
071-0090-05
071-0090-16
071-0090-07
071-0092-37
071-0092-06
071-0092-05
071-0092-05
071-0092-06
071-0092-20
071-0092-29
071-0099-00
071-0092-27
071-0092-27
* See Section F Introduction for more information.
FC15
Section_Fc.indd 15
3/4/2008 8:00:06 AM
Electrical Data - Copelametic - Air Cooled
Model
KAG2-0075-XAA
KAG2-0075-XAB
KAG2-007A-IAH
KAG2-0100-CAA
KAG2-0100-CAV
KAGA-007A-TAC
KAGA-008E-TAC
KAGA-010A-TAC
KAGA-010E-TAC
KAGA-010L-TAC
KAGA-011E-TAD
KAGA-011L-TAD
KAGA-0150-TAC
KAGA-0150-TAD
KAGA-015A-TAC
KAGA-015A-TAD
KAGA-015L-TAC
KAGA-015L-TAD
KAGB-0050-IAA
KAGB-005A-CAV
KAGB-005A-IAA
KAGB-005E-CAV
KAGB-005E-IAA
Volts PH
115
230
208
115
208/230
208/230
208/230
208/230
208/230
208/230
460
460
208/230
460
208/230
460
208/230
460
115
208/230
115
208/230
115
1
1
1
1
1
3
3
3
3
3
3
3
3
3
3
3
3
3
1
1
1
1
1
Max
LRA
RLA
9.3
5.4
5.6
11.9
6.4
2.6
3.6
4.3
4.3
4.3
2.1
2.1
5.5
2.5
5.5
2.5
5.5
2.5
7.8
4.1
7.8
4.1
7.8
43.9
23.2
34.1
85.5
40
19.9
23.1
27
27
27
15
15
35.5
18.2
35.5
18.2
35.5
18.2
45
24
45
24
45
Resistance
Run or
Start or
Line to WYE Line to Line
0.615
2.41
2
0.405
1.37
2.28
2.28
1.59
1.59
1.59
6.62
6.62
1.325
4.72
1.325
4.72
1.325
4.72
0.835
2.9
0.835
2.9
0.835
3.26
13.45
5.15
2.248
4.525
4.551
4.551
3.179
3.179
3.179
13.24
13.24
2.375
9.44
2.375
9.44
2.375
9.44
2.42
5.785
2.42
5.785
2.42
Start Cap Run Cap
P/N
P/N
Relay
P/N
Part Protector
Type*
P/N
014-0061-06
040-0166-33
014-0061-10
040-0166-35
014-0061-04
040-0166-09
014-0061-05 014-0064-08 040-0166-11
014-0061-04 014-0064-10 040-0166-10
RP
RP
RP
RP
RP
014-0061-02
040-0166-08
014-0036-21 014-0064-00 040-0166-09
014-0061-02
040-0166-08
014-0036-21 014-0064-00 040-0166-09
014-0061-02
040-0166-08
RP
RP
RP
RP
RP
071-0092-10
071-0092-15
071-0092-27
071-0092-40
071-0092-39
071-0090-05
071-0090-13
071-0090-50
071-0090-50
071-0090-50
071-0090-42
071-0090-42
071-0090-39
071-0090-27
071-0090-39
071-0090-27
071-0090-39
071-0090-27
071-0092-06
071-0092-37
071-0092-06
071-0092-37
071-0092-06
* See Section F Introduction for more information.
FC16
Section_Fc.indd 16
3/4/2008 8:00:06 AM
Electrical Data - Copelametic - Air Cooled
Model
KAGB-005L-IAA
KAGB-007A-CAV
KAGB-007A-IAA
KAGB-010E-CAV
KAGB-010L-CAV
KAGB-0150-CAV
KAGB-015A-CAV
KAGB-015L-CAV
KAJ1-0075-TAC
KAJ1-0100-TAC
KAJ1-0100-TAD
KAJ1-010L-TAC
KAJ1-010L-TAD
KAJ3-0075-CAV
KAJ3-0075-IAA
KAJ3-0075-IAB
KAJ3-0075-IAH
KAJ3-0075-XAA
KAJ3-0075-XAB
KAJ3-007A-IAB
KAJ3-0100-CAA
KAJ3-0100-CAB
KAJ3-0100-CAH
Volts PH
115
208/230
115
208/230
208/230
208/230
208/230
208/230
208/230
208/230
460
208/230
460
208/230
115
230
208
115
230
230
115
230
208
1
1
1
1
1
1
1
1
3
3
3
3
3
1
1
1
1
1
1
1
1
1
1
Max
LRA
RLA
7.8
5.4
9.5
7.5
7.5
9.6
9.6
9.6
2.7
NA
NA
3.4
2.1
5.1
9.1
5.4
5.9
8.9
5.2
5.4
NA
NA
NA
45
36
59.8
40
40
55
55
55
19.9
25
15
25
15
36
59.8
30.4
34.1
43.9
23.2
30.4
85.5
33.5
36.4
Resistance
Run or
Start or
Line to WYE Line to Line
0.835
1.9
0.59
1.37
1.37
0.94
0.94
0.94
2.28
2.145
6.62
2.145
6.62
1.9
0.59
2.34
2
0.615
2.41
2.34
0.405
2.27
1.885
2.42
4.24
1.4
4.525
4.525
3.45
3.45
3.45
4.551
4.29
13.24
4.29
13.24
4.24
1.4
5.53
5.15
3.26
13.45
5.53
2.248
4.935
4.59
Start Cap Run Cap
P/N
P/N
Relay
P/N
Part Protector
Type*
P/N
014-0061-02
014-0061-04
014-0061-11
014-0061-04
014-0061-04
014-0036-22
014-0036-22
014-0036-22
040-0166-08
014-0064-00 040-0166-09
040-0166-08
014-0064-14 040-0166-10
014-0064-14 040-0166-10
014-0064-19 040-0166-20
014-0064-19 040-0166-20
014-0064-19 040-0166-20
RP
RP
RP
RP
RP
RP
RP
RP
014-0061-04
014-0061-11
014-0061-04
014-0061-04
014-0061-06
014-0061-10
014-0061-04
014-0061-05
014-0061-04
014-0061-04
014-0064-00 040-0166-09
040-0166-08
040-0166-09
040-0166-09
040-0166-33
040-0166-35
040-0166-09
014-0064-08 040-0166-11
014-0064-00 040-0166-10
014-0064-00 040-0166-25
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
071-0092-06
071-0092-29
071-0099-00
071-0092-42
071-0092-42
071-0099-04
071-0099-04
071-0099-04
071-0090-05
071-0090-04
071-0090-07
071-0090-04
071-0090-07
071-0092-29
071-0099-00
071-0092-27
071-0092-27
071-0092-10
071-0092-15
071-0092-27
071-0092-23
071-0092-25
071-0092-14
* See Section F Introduction for more information.
FC17
Section_Fc.indd 17
3/4/2008 8:00:07 AM
Electrical Data - Copelametic - Air Cooled
Model
KAJ3-0100-CAV
KAJ3-010L-CAV
KAJ8-0075-TAC
KAJA-007A-TAC
KAJA-0100-TAC
KAJA-0101-TAC
KAJA-010A-TAC
KAJA-010L-TAC
KAJA-011A-TAC
KAJA-011A-TAD
KAJA-011E-TAC
KAJA-011E-TAD
KAJA-011L-TAC
KAJA-011L-TAD
KAJB-007A-CAV
KAJB-007A-IAA
KAJB-007E-IAA
KAJB-007L-IAA
KAJB-0100-CAA
KAJB-0100-CAV
KAJB-010A-CAA
KAJB-010A-CAV
KAJB-010E-CAV
Volts PH
208/230
208/230
208/230
208/230
208/230
208/230
208/230
208/230
208/230
460
208/230
460
208/230
460
208/230
115
115
115
115
208/230
115
208/230
208/230
1
1
3
3
3
3
3
3
3
3
3
3
3
3
1
1
1
1
1
1
1
1
1
Max
LRA
RLA
NA
6.9
2.7
2.7
NA
4.5
NA
3.4
4.6
2.1
4.6
2.1
4.6
2.1
5.1
10.4
10.4
10.4
NA
NA
NA
6.9
6.9
40
40
19.9
19.9
25
27
25
25
27
15
27
15
27
15
36
59.8
59.8
59.8
85.5
40
85.5
40
40
Resistance
Run or
Start or
Line to WYE Line to Line
1.37
1.37
2.28
2.28
2.145
1.59
2.145
2.145
1.59
6.62
1.59
6.62
1.59
6.62
1.9
0.59
0.59
0.59
0.405
1.37
0.405
1.37
1.37
4.525
4.525
4.551
4.551
4.29
3.179
4.29
4.29
3.179
13.24
3.179
13.24
3.179
13.24
4.24
1.4
1.4
1.4
2.248
4.525
2.248
4.525
4.525
Start Cap Run Cap
P/N
P/N
Relay
P/N
Part Protector
Type*
P/N
014-0061-04 014-0064-10 040-0166-10
014-0061-04 014-0064-10 040-0166-10
RP
RP
014-0061-04
014-0061-11
014-0061-11
014-0061-11
014-0061-05
014-0061-04
014-0061-05
014-0061-04
014-0061-04
RP
RP
RP
RP
RP
RP
RP
RP
RP
014-0064-00 040-0166-09
040-0166-08
040-0166-08
040-0166-08
014-0064-08 040-0166-11
014-0064-10 040-0166-10
014-0064-08 040-0166-11
014-0064-10 040-0166-10
014-0064-10 040-0166-10
071-0092-39
071-0092-39
071-0090-05
071-0090-05
071-0090-04
071-0090-16
071-0090-04
071-0090-04
071-0090-50
071-0090-42
071-0090-50
071-0090-42
071-0090-50
071-0090-42
071-0092-29
071-0099-00
071-0099-00
071-0099-00
071-0092-23
071-0092-39
071-0092-23
071-0092-39
071-0092-39
* See Section F Introduction for more information.
FC18
Section_Fc.indd 18
3/4/2008 8:00:07 AM
Electrical Data - Copelametic - Air Cooled
Model
KAJB-010L-CAV
KAJC-0100-TAC
KAJC-0101-TAC
KAJC-011L-TAC
KAK1-0100-TAC
KAK1-0100-TAD
KAK2-0100-CAA
KAK2-0100-CAB
KAK2-0100-CAH
KAK2-0100-CAV
KAK2-010A-CAA
KAK4-0075-CAV
KAK4-0075-IAA
KAK4-0075-IAB
KAK8-0100-TAC
KAKA-0100-TAC
KAKA-010A-TAC
KAKA-010A-TAD
KAKA-010L-TAC
KAKA-011E-TAD
KAKA-012E-TAC
KAKA-0150-TAU
KAKA-0200-TAC
Volts PH
208/230
208/230
208/230
208/230
208/230
460
115
230
208
208/230
115
208/230
115
230
208/230
208/230
208/230
460
208/230
460
208/230
200
208/230
1
3
3
3
3
3
1
1
1
1
1
1
1
1
3
3
3
3
3
3
3
3
3
Max
LRA
RLA
6.9
NA
4.5
4.6
NA
NA
NA
NA
NA
NA
11.4
NA
NA
NA
3.3
NA
3.3
NA
3.3
2.4
4.6
6.6
6.8
40
25
27
27
25
15
85.5
33.5
36.4
40
85.5
36
59.8
30.4
25
25
25
15
25
15
27
48.2
50
Resistance
Run or
Start or
Line to WYE Line to Line
1.37
2.145
1.59
1.59
2.145
6.62
0.405
2.27
1.885
1.37
0.405
1.9
0.59
2.34
2.145
2.145
2.145
6.62
2.145
6.62
1.59
0
0.795
4.525
4.29
3.179
3.179
4.29
13.24
2.248
4.935
4.59
4.525
2.248
4.24
1.4
5.53
4.29
4.29
4.29
13.24
4.29
13.24
3.179
1.463
1.589
Start Cap Run Cap
P/N
P/N
Relay
P/N
Part Protector
Type*
P/N
014-0061-04 014-0064-10 040-0166-10
RP
014-0061-05
014-0061-04
014-0061-04
014-0061-04
014-0061-05
014-0061-04
014-0061-11
014-0061-04
RP
RP
RP
RP
RP
RP
RP
RP
014-0064-08
014-0064-00
014-0064-00
014-0064-10
014-0064-08
014-0064-00
040-0166-11
040-0166-10
040-0166-25
040-0166-10
040-0166-11
040-0166-09
040-0166-08
040-0166-09
071-0092-39
071-0090-04
071-0090-16
071-0090-50
071-0090-04
071-0090-07
071-0092-23
071-0092-25
071-0092-14
071-0092-39
071-0092-23
071-0092-29
071-0099-00
071-0092-27
071-0090-04
071-0090-04
071-0090-04
071-0090-07
071-0090-04
071-0090-42
071-0090-03
071-0090-28
071-0090-35
* See Section F Introduction for more information.
FC19
Section_Fc.indd 19
3/4/2008 8:00:08 AM
Electrical Data - Copelametic - Air Cooled
Model
KAKA-0200-TAD
KAKA-020A-TAC
KAKA-020A-TAD
KAKA-020E-TAC
KAKA-020L-TAC
KAKA-020L-TAD
KAKA-022E-TAD
KAKB-011A-CAV
KAKB-011E-CAV
KAKB-011L-CAV
KAKB-012E-CAA
KAKB-0150-CAB
KAKB-0151-CAB
KAKB-015A-CAB
KAKB-0200-CAV
KAKB-020L-CAV
KAKB-021A-CAV
KAKB-021E-CAV
KAKB-021L-CAV
KAKC-0150-TAU
KAKC-0200-TAC
KAKC-020L-TAC
KAKD-011E-CAV
Volts PH
460
208/230
460
208/230
208/230
460
460
208/230
208/230
208/230
115
230
230
230
208/230
208/230
208/230
208/230
208/230
200
208/230
208/230
208/230
3
3
3
3
3
3
3
1
1
1
1
1
1
1
1
1
1
1
1
3
3
3
1
Max
LRA
RLA
3
6.8
3
6.8
6.5
3
3
7.9
7.9
7.9
11.4
7.5
8.5
7.5
9.1
9.1
9.1
10.6
10.1
6.6
6.8
6.5
7.9
25
50
25
50
50
25
25
40
40
40
85.5
44
44
44
55
55
55
55
55
48.2
50
50
40
Resistance
Run or
Start or
Line to WYE Line to Line
3.165
0.795
3.165
0.795
0.795
3.165
3.165
1.37
1.37
1.37
0.405
1.65
1.28
1.65
0.94
0.94
0.94
0.94
0.94
0
0.795
0.795
1.37
6.329
1.589
6.329
1.589
1.589
6.329
6.329
4.525
4.525
4.525
2.248
4.19
4.105
4.19
3.45
3.45
3.45
3.45
3.45
1.463
1.589
1.589
4.525
Start Cap Run Cap
P/N
P/N
014-0061-04
014-0061-04
014-0061-04
014-0061-05
014-0036-21
014-0036-21
014-0036-21
014-0036-22
014-0036-22
014-0036-22
014-0036-22
014-0036-22
014-0064-14
014-0064-14
014-0064-14
014-0064-08
014-0064-11
014-0064-19
014-0064-11
014-0064-19
014-0064-19
014-0064-19
014-0064-14
014-0064-14
Relay
P/N
Part Protector
Type*
P/N
040-0166-10
040-0166-10
040-0166-10
040-0166-11
040-0166-20
040-0166-20
040-0166-20
040-0166-20
040-0166-20
040-0166-20
040-0166-20
040-0166-20
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
014-0061-04 014-0064-14 040-0166-10
RP
071-0090-16
071-0090-35
071-0090-16
071-0090-35
071-0090-35
071-0090-16
071-0090-16
071-0092-42
071-0092-42
071-0092-42
071-0092-23
071-0092-29
071-0099-03
071-0092-29
071-0099-04
071-0099-04
071-0099-04
071-0099-04
071-0099-04
071-0090-28
071-0090-35
071-0090-35
071-0092-42
* See Section F Introduction for more information.
FC20
Section_Fc.indd 20
3/4/2008 8:00:08 AM
Electrical Data - Copelametic - Air Cooled
Model
KAL1-0100-TAC
KAL1-0100-TAD
KAL2-0100-CAA
KAL2-0100-CAB
KAL2-0100-CAH
KAL2-0100-CAV
KALA-0100-TAC
KALA-0100-TAD
KALA-010A-TAC
KALA-010A-TAD
KALA-0150-TAC
KALA-0150-TAD
KALA-0150-TAU
KALA-015A-TAC
KALA-015A-TAD
KALA-015L-TAC
KALA-015L-TAD
KALA-016E-TAC
KALA-016E-TAD
KALA-016L-TAC
KALA-016L-TAD
KALB-0100-CAA
KALB-0100-CAB
Volts PH
208/230
460
115
230
208
208/230
208/230
460
208/230
460
208/230
460
200
208/230
460
208/230
460
208/230
460
208/230
460
115
230
3
3
1
1
1
1
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
1
1
Max
LRA
RLA
NA
NA
NA
NA
NA
NA
3.3
1.8
3.3
1.8
NA
NA
NA
5.4
2.9
5.4
2.9
6.6
3.4
6.6
3.4
10.9
5.5
25
15
85.5
33.5
36.4
40
25
15
25
15
35.5
18.2
48.2
35.5
18.2
35.5
18.2
50
25
50
25
85.5
33.5
Resistance
Run or
Start or
Line to WYE Line to Line
2.145
6.62
0.405
2.27
1.885
1.37
2.145
6.62
2.145
6.62
1.325
4.72
0
1.325
4.72
1.325
4.72
0.795
3.165
0.795
3.165
0.405
2.27
4.29
13.24
2.248
4.935
4.59
4.525
4.29
13.24
4.29
13.24
2.375
9.44
1.463
2.375
9.44
2.375
9.44
1.589
6.329
1.589
6.329
2.248
4.935
Start Cap Run Cap
P/N
P/N
014-0061-05
014-0061-04
014-0061-04
014-0061-04
014-0064-08
014-0064-00
014-0064-00
014-0064-10
Relay
P/N
Part Protector
Type*
P/N
040-0166-11
040-0166-10
040-0166-25
040-0166-10
RP
RP
RP
RP
014-0061-05 014-0064-08 040-0166-11
014-0061-04 014-0064-00 040-0166-10
RP
RP
071-0090-04
071-0090-07
071-0092-23
071-0092-25
071-0092-14
071-0092-39
071-0090-04
071-0090-07
071-0090-04
071-0090-07
071-0090-03
071-0090-27
071-0090-28
071-0090-03
071-0090-27
071-0090-03
071-0090-27
071-0090-35
071-0090-16
071-0090-35
071-0090-16
071-0092-23
071-0092-25
* See Section F Introduction for more information.
FC21
Section_Fc.indd 21
3/4/2008 8:00:08 AM
Electrical Data - Copelametic - Air Cooled
Model
KALB-0100-CAH
KALB-0100-CAV
KALB-010A-CAA
KALB-010A-CAB
KALB-010A-CAV
KALB-010E-CAV
KALB-010L-CAV
KALB-0150-CAB
KALB-0150-CAH
KALB-0150-CAV
KALB-0151-CAB
KALB-015A-CAB
KALB-015A-CAH
KALB-015A-CAV
KALB-015E-CAV
KALB-015L-CAV
KALC-0150-TAU
KALC-016L-TAC
KAM1-0050-TAC
KAM1-0075-TAC
KAM1-0100-TAC
KAM1-0100-TAD
KAM1-010A-TAD
Volts PH
208
208/230
115
230
208/230
208/230
208/230
230
208
208/230
230
230
208
208/230
208/230
208/230
200
208/230
208/230
208/230
208/230
460
460
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3
3
3
3
3
3
3
Max
LRA
RLA
6.8
6.9
10.9
5.5
6.9
6.9
6.9
NA
NA
NA
8.9
5.6
8.1
9.9
9.9
9.9
NA
6.6
1.7
NA
4.5
2.2
2.2
36.4
40
85.5
33.5
40
40
40
44
45
55
44
44
45
55
55
55
48.2
50
13.2
19.9
27
13.5
13.5
Resistance
Run or
Start or
Line to WYE Line to Line
1.885
1.37
0.405
2.27
1.37
1.37
1.37
1.65
1.32
0.94
1.28
1.65
1.32
0.94
0.94
0.94
0
0.795
3.34
2.28
1.59
6.24
6.24
4.59
4.525
2.248
4.935
4.525
4.525
4.525
4.19
4.19
3.45
4.105
4.19
4.19
3.45
3.45
3.45
1.463
1.589
6.69
4.551
3.179
12.48
12.48
Start Cap Run Cap
P/N
P/N
014-0061-04
014-0061-04
014-0061-05
014-0061-04
014-0061-04
014-0061-04
014-0061-04
014-0036-21
014-0036-21
014-0036-22
014-0036-21
014-0036-21
014-0036-21
014-0036-22
014-0036-22
014-0036-22
014-0064-00
014-0064-10
014-0064-08
014-0064-00
014-0064-10
014-0064-10
014-0064-10
014-0064-10
014-0064-10
014-0064-19
014-0064-19
014-0064-10
014-0064-10
014-0064-19
014-0064-19
014-0064-19
Relay
P/N
040-0166-25
040-0166-10
040-0166-11
040-0166-10
040-0166-10
040-0166-10
040-0166-10
040-0166-20
040-0166-30
040-0166-20
040-0166-20
040-0166-20
040-0166-30
040-0166-20
040-0166-20
040-0166-20
Part Protector
Type*
P/N
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
071-0092-14
071-0092-39
071-0092-23
071-0092-25
071-0092-39
071-0092-39
071-0092-39
071-0092-16
071-0092-18
071-0099-04
071-0099-03
071-0092-16
071-0092-18
071-0099-04
071-0099-04
071-0099-04
071-0090-28
071-0090-35
071-0090-06
071-0090-05
071-0090-40
071-0090-43
071-0090-43
* See Section F Introduction for more information.
FC22
Section_Fc.indd 22
3/4/2008 8:00:09 AM
Electrical Data - Copelametic - Air Cooled
Model
KAM1-010L-TAC
KAM1-010L-TAD
KAM2-0050-CAV
KAM2-0050-IAA
KAM2-0050-IAB
KAM2-0050-IAH
KAM2-0075-CAV
KAM2-0075-IAA
KAM2-0075-IAB
KAM2-0075-IAH
KAM2-0075-XAA
KAM2-0075-XAB
KAM2-0100-CAA
KAM2-0100-CAV
KAM2-010A-CAA
KAM2-010L-CAV
KAMA-0050-TAC
KAMA-005A-TAC
KAMA-0075-TAC
KAMA-007A-TAC
KAMA-007E-TAC
KAMA-007L-TAC
KAMA-0100-TAC
Volts PH
208/230
460
208/230
115
230
208
208/230
115
230
208
115
230
115
208/230
115
208/230
208/230
208/230
208/230
208/230
208/230
208/230
208/230
3
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3
3
3
3
3
3
3
Max
LRA
RLA
4.5
2.2
3.7
7.2
3.8
3.8
5.6
NA
NA
6.1
8.9
6
15.5
7.5
15.5
7.5
1.7
1.7
NA
3.2
3.2
3.2
4.5
27
13.5
24
45
22.5
25.5
36
59.8
30.4
34.1
43.9
23.2
93
40
93
40
13.2
13.2
19.9
19.9
19.9
19.9
27
Resistance
Run or
Start or
Line to WYE Line to Line
1.59
6.24
2.9
0.835
3.305
2.92
1.9
0.59
2.34
2
0.615
2.41
0.376
1.37
0.376
1.37
3.34
3.34
2.28
2.28
2.28
2.28
1.59
3.179
12.48
5.785
2.42
9.585
7.9
4.24
1.4
5.53
5.15
3.26
13.45
1.837
4.525
1.837
4.525
6.69
6.69
4.551
4.551
4.551
4.551
3.179
Start Cap Run Cap
P/N
P/N
014-0036-21
014-0061-02
014-0061-09
014-0061-09
014-0061-04
014-0061-11
014-0061-04
014-0061-04
014-0061-06
014-0061-10
014-0061-05
014-0061-04
014-0061-05
014-0061-04
Relay
P/N
014-0064-00 040-0166-09
040-0166-08
040-0166-09
040-0166-09
014-0064-00 040-0166-09
040-0166-08
040-0166-09
040-0166-09
040-0166-33
040-0166-35
014-0064-08 040-0166-11
014-0064-10 040-0166-10
014-0064-08 040-0166-11
014-0064-10 040-0166-10
Part Protector
Type*
P/N
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
071-0090-40
071-0090-43
071-0092-37
071-0092-06
071-0092-05
071-0092-05
071-0092-29
071-0099-00
071-0092-27
071-0092-27
071-0092-10
071-0092-15
071-0099-05
071-0092-39
071-0099-05
071-0092-39
071-0090-06
071-0090-06
071-0090-41
071-0090-41
071-0090-41
071-0090-41
071-0090-40
* See Section F Introduction for more information.
FC23
Section_Fc.indd 23
3/4/2008 8:00:09 AM
Electrical Data - Copelametic - Air Cooled
Model
KAMA-010A-TAC
KAMB-0050-CAV
KAMB-0050-IAA
KAMB-0050-IAB
KAMB-0050-IAH
KAMB-005A-CAV
KAMB-005A-IAA
KAMB-005A-IAB
KAMB-005A-IAH
KAMB-0075-CAA
KAMB-0075-CAV
KAMB-0075-IAB
KAMB-0075-IAH
KAMB-007A-CAA
KAMB-007A-CAV
KAMB-007E-CAA
KAMB-007E-CAV
KAMB-007E-IAA
KAMB-007L-CAA
KAMB-007L-CAV
KAMB-010A-CAV
KAMC-0075-TAC
KAMD-007E-CAA
Volts PH
208/230
208/230
115
230
208
208/230
115
230
208
115
208/230
230
208
115
208/230
115
208/230
115
115
208/230
208/230
208/230
115
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3
1
Max
LRA
RLA
4.5
3.7
7.2
3.8
3.8
3.7
7.2
3.8
3.8
NA
NA
NA
NA
NA
5.6
10.9
5.6
10.1
10.9
5.6
7.5
NA
10.9
27
24
45
22.5
25.5
24
45
22.5
25.5
85.5
36
30.4
34.1
85.5
36
85.5
36
59.8
85.5
36
40
19.9
85.5
Resistance
Run or
Start or
Line to WYE Line to Line
1.59
2.9
0.835
3.305
2.92
2.9
0.835
3.305
2.92
0.405
1.9
2.34
2
0.405
1.9
0.405
1.9
0.59
0.405
1.9
1.37
2.28
0.405
3.179
5.785
2.42
9.585
7.9
5.785
2.42
9.585
7.9
2.248
4.24
5.53
5.15
2.248
4.24
2.248
4.24
1.4
2.248
4.24
4.525
4.551
2.248
Start Cap Run Cap
P/N
P/N
014-0036-21
014-0061-02
014-0061-09
014-0061-09
014-0036-21
014-0061-02
014-0061-09
014-0061-09
014-0061-05
014-0061-04
014-0061-04
014-0061-04
014-0061-05
014-0061-04
014-0061-05
014-0061-04
014-0061-11
014-0061-05
014-0061-04
014-0061-04
Relay
P/N
Part Protector
Type*
P/N
014-0064-00 040-0166-09
040-0166-08
040-0166-09
040-0166-09
014-0064-00 040-0166-09
040-0166-08
040-0166-09
040-0166-09
014-0064-08 040-0166-11
014-0064-00 040-0166-09
040-0166-09
040-0166-09
014-0064-08 040-0166-21
014-0064-00 040-0166-09
014-0064-08 040-0166-21
014-0064-00 040-0166-09
040-0166-08
014-0064-08 040-0166-21
014-0064-00 040-0166-09
014-0064-10 040-0166-10
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
014-0061-05 014-0064-08 040-0166-21
RP
071-0090-40
071-0092-37
071-0092-06
071-0092-05
071-0092-05
071-0092-37
071-0092-06
071-0092-05
071-0092-05
071-0092-40
071-0092-29
071-0092-27
071-0092-27
071-0092-40
071-0092-29
071-0092-40
071-0092-29
071-0099-00
071-0092-40
071-0092-29
071-0092-39
071-0090-41
071-0092-40
* See Section F Introduction for more information.
FC24
Section_Fc.indd 24
3/4/2008 8:00:10 AM
Electrical Data - Copelametic - Air Cooled
Model
KAMD-007E-CAV
KAN1-0050-TAC
KAN1-0075-TAC
KAN1-007L-TAC
KAN2-0050-CAV
KAN2-0050-IAA
KAN2-0050-IAB
KAN2-0050-IAH
KAN2-0075-CAA
KAN2-0075-CAV
KAN2-007A-CAA
KAN2-007L-CAV
KANA-006E-TAC
KANA-006L-TAC
KANA-0075-TAC
KANA-007E-TAC
KANB-0050-CAV
KANB-0050-IAA
KANB-005A-CAV
KANB-005A-IAA
KANB-005E-CAV
KANB-005E-IAA
KANB-005L-CAV
Volts PH
208/230
208/230
208/230
208/230
208/230
115
230
208
115
208/230
115
208/230
208/230
208/230
208/230
208/230
208/230
115
208/230
115
208/230
115
208/230
1
3
3
3
1
1
1
1
1
1
1
1
3
3
3
3
1
1
1
1
1
1
1
Max
LRA
RLA
5.6
2.1
3.5
3.5
3.6
8.1
4.2
4.2
11.7
6.1
11.7
6.1
2.2
2.2
3.5
3.5
3.6
NA
3.6
8
3.6
8
3.6
36
13.2
19.9
19.9
24
45
22.5
25.5
65
36
65
36
13.2
13.2
19.9
19.9
24
45
24
45
24
45
24
Resistance
Run or
Start or
Line to WYE Line to Line
1.9
3.34
2.28
2.28
2.9
0.835
3.305
2.92
0.519
1.9
0.519
1.9
3.34
3.34
2.28
2.28
2.9
0.835
2.9
0.835
2.9
0.835
2.9
4.24
6.69
4.551
4.551
5.785
2.42
9.585
7.9
1.266
4.24
1.266
4.24
6.69
6.69
4.551
4.551
5.785
2.42
5.785
2.42
5.785
2.42
5.785
Start Cap Run Cap
P/N
P/N
Relay
P/N
Part Protector
Type*
P/N
014-0061-04 014-0064-00 040-0166-09
RP
014-0036-21
014-0061-02
014-0061-09
014-0061-09
014-0061-11
014-0061-04
014-0061-11
014-0061-04
014-0064-00 040-0166-09
040-0166-08
040-0166-09
040-0166-09
014-0064-06 040-0166-33
014-0064-00 040-0166-09
014-0064-06 040-0166-33
014-0064-00 040-0166-09
RP
RP
RP
RP
RP
RP
RP
RP
014-0036-21
014-0061-02
014-0036-21
014-0061-02
014-0036-21
014-0061-02
014-0036-21
014-0064-00 040-0166-09
040-0166-08
014-0064-00 040-0166-09
040-0166-08
014-0064-00 040-0166-09
040-0166-08
014-0064-00 040-0166-09
RP
RP
RP
RP
RP
RP
RP
071-0092-29
071-0090-06
071-0090-41
071-0090-41
071-0092-37
071-0092-06
071-0092-05
071-0092-05
071-0099-06
071-0092-41
071-0099-06
071-0092-41
071-0090-21
071-0090-21
071-0090-41
071-0090-41
071-0092-37
071-0092-06
071-0092-37
071-0092-06
071-0092-37
071-0092-06
071-0092-37
* See Section F Introduction for more information.
FC25
Section_Fc.indd 25
3/4/2008 8:00:10 AM
Electrical Data - Copelametic - Air Cooled
Model
KANB-005L-IAA
KANB-007E-CAV
KAR1-0100-TAC
KAR1-0100-TAD
KAR1-010L-TAC
KAR1-010L-TAD
KAR2-0100-CAA
KAR2-0100-CAV
KAR2-010A-CAA
KAR2-010L-CAV
KARA-0100-TAC
KARA-010A-TAC
KARA-010E-TAC
KARA-010L-TAC
KARA-011A-TAD
KARA-011E-TAD
KARA-011L-TAD
KARB-010A-CAV
KARB-010E-CAV
KARB-010L-CAV
KAT4-0100-CAA
KAT4-0100-CAB
KAT4-0100-CAV
Volts PH
115
208/230
208/230
460
208/230
460
115
208/230
115
208/230
208/230
208/230
208/230
208/230
460
460
460
208/230
208/230
208/230
115
230
208/230
1
1
3
3
3
3
1
1
1
1
3
3
3
3
3
3
3
1
1
1
1
1
1
Max
LRA
RLA
8
NA
4.3
2.2
4.3
2.2
15.4
7.4
15.4
7.4
4.3
4.3
4.3
4.3
2
2
2
7.4
7.4
7.4
NA
NA
NA
45
36
27
13.5
27
13.5
93
40
93
40
27
27
27
27
15
15
15
40
40
40
85.5
33.5
40
Resistance
Run or
Start or
Line to WYE Line to Line
0.835
1.9
1.59
6.24
1.59
6.24
0.376
1.37
0.376
1.37
1.59
1.59
1.59
1.59
6.62
6.62
6.62
1.37
1.37
1.37
0.405
2.27
1.37
2.42
4.24
3.179
12.48
3.179
12.48
1.837
4.525
1.837
4.525
3.179
3.179
3.179
3.179
13.24
13.24
13.24
4.525
4.525
4.525
2.248
4.935
4.525
Start Cap Run Cap
P/N
P/N
Relay
P/N
Part Protector
Type*
P/N
014-0061-02
040-0166-08
014-0061-04 014-0064-00 040-0166-09
RP
RP
014-0061-05
014-0061-04
014-0061-05
014-0061-04
014-0064-08
014-0064-10
014-0064-08
014-0064-10
040-0166-11
040-0166-10
040-0166-11
040-0166-10
RP
RP
RP
RP
014-0061-04
014-0061-04
014-0061-04
014-0061-05
014-0061-04
014-0061-04
014-0064-10
014-0064-10
014-0064-10
014-0064-08
014-0064-00
014-0064-10
040-0166-10
040-0166-10
040-0166-10
040-0166-11
040-0166-10
040-0166-10
RP
RP
RP
RP
RP
RP
071-0092-06
071-0092-41
071-0090-40
071-0090-43
071-0090-40
071-0090-43
071-0099-05
071-0092-39
071-0099-05
071-0092-39
071-0090-40
071-0090-40
071-0090-40
071-0090-40
071-0090-42
071-0090-42
071-0090-42
071-0092-39
071-0092-39
071-0092-39
071-0092-23
071-0092-25
071-0092-39
* See Section F Introduction for more information.
FC26
Section_Fc.indd 26
3/4/2008 8:00:11 AM
Electrical Data - Copelametic - Air Cooled
Model
KATA-0100-TAC
KATA-0100-TAD
KATA-010A-TAC
KATA-010A-TAD
KATA-0150-TAC
KATA-0150-TAD
KATA-0151-TAC
KATA-015A-TAC
KATA-015A-TAD
KATA-015E-TAC
KATA-015E-TAD
KATA-015L-TAC
KATA-0200-TAU
KATA-020E-TAU
KATA-020L-TAU
KATB-0100-CAA
KATB-0100-CAB
KATB-0100-CAH
KATB-0100-CAV
KATB-010A-CAA
KATB-010A-CAB
KATB-010A-CAV
KATB-0150-CAB
Volts PH
208/230
460
208/230
460
208/230
460
208/230
208/230
460
208/230
460
208/230
200
200
200
115
230
208
208/230
115
230
208/230
230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
1
1
1
1
1
1
1
1
Max
LRA
RLA
3.9
2.1
3.9
2.1
NA
NA
6
5
2.9
5
2.9
5
6.4
6.4
6.4
12.4
5.5
7.3
7.2
12.4
5.5
7.2
NA
25
15
25
15
35.5
18.2
50
35.5
18.2
35.5
18.2
35.5
51
51
51
85.5
33.5
36.4
40
85.5
33.5
40
44
Resistance
Run or
Start or
Line to WYE Line to Line
2.145
6.62
2.145
6.62
1.325
4.72
0.795
1.325
4.72
1.325
4.72
1.325
0
0
0
0.405
2.27
1.885
1.37
0.405
2.27
1.37
1.65
4.29
13.24
4.29
13.24
2.375
9.44
1.589
2.375
9.44
2.375
9.44
2.375
1.44
1.44
1.44
2.248
4.935
4.59
4.525
2.248
4.935
4.525
4.19
Start Cap Run Cap
P/N
P/N
014-0061-05
014-0061-04
014-0061-04
014-0061-04
014-0061-05
014-0061-04
014-0061-04
014-0036-21
014-0064-08
014-0064-00
014-0064-00
014-0064-10
014-0064-08
014-0064-00
014-0064-10
014-0064-10
Relay
P/N
040-0166-11
040-0166-10
040-0166-25
040-0166-10
040-0166-11
040-0166-10
040-0166-10
040-0166-20
Part Protector
Type*
P/N
RP
RP
RP
RP
RP
RP
RP
RP
071-0090-04
071-0090-07
071-0090-04
071-0090-07
071-0090-03
071-0090-27
071-0090-22
071-0090-03
071-0090-27
071-0090-03
071-0090-27
071-0090-03
071-0090-31
071-0090-31
071-0090-31
071-0092-23
071-0092-25
071-0092-14
071-0092-39
071-0092-23
071-0092-25
071-0092-39
071-0092-18
* See Section F Introduction for more information.
FC27
Section_Fc.indd 27
3/4/2008 8:00:11 AM
Electrical Data - Copelametic - Air Cooled
Model
KATB-0150-CAH
KATB-0150-CAV
KATB-0151-CAB
KATB-015A-CAB
KATB-015A-CAH
KATB-015A-CAV
KATB-015E-CAV
KATB-015L-CAV
KATC-0150-TAC
KATC-0200-TAU
KATC-020E-TAD
KATC-020E-TAU
KATC-020L-TAU
KATD-015E-CAV
KWA1-0075-TAC
KWA2-0075-CAV
KWA2-0075-IAA
KWA2-0075-IAB
KWA2-0075-IAH
KWD1-0075-TAC
KWD2-0075-CAA
KWD2-0075-CAV
KWE1-0050-TAC
Volts PH
208
208/230
230
230
208
208/230
208/230
208/230
208/230
200
460
200
200
208/230
208/230
208/230
115
230
208
208/230
115
208/230
208/230
1
1
1
1
1
1
1
1
3
3
3
3
3
1
3
1
1
1
1
3
1
1
3
Max
LRA
RLA
7.8
NA
7.4
6.1
7.8
NA
9
9
NA
6.4
3.5
6.4
6.4
9
2.6
5.2
10.2
5.4
5.6
2.4
9.9
5.1
1.9
45
55
44
44
45
55
55
55
35.5
51
25
51
51
55
19.9
36
59.8
30.4
34.1
19.9
65
36
13.2
Resistance
Run or
Start or
Line to WYE Line to Line
1.32
0.94
1.28
1.65
1.32
0.94
0.94
0.94
1.325
0
3.165
0
0
0.94
2.28
1.9
0.59
2.34
2
2.28
0.519
1.9
3.34
4.19
3.45
4.105
4.19
4.19
3.45
3.45
3.45
2.375
1.44
6.329
1.44
1.44
3.45
4.551
4.24
1.4
5.53
5.15
4.551
1.266
4.24
6.69
Start Cap Run Cap
P/N
P/N
014-0036-21
014-0036-22
014-0036-21
014-0036-21
014-0036-21
014-0036-22
014-0036-22
014-0036-22
014-0064-10
014-0064-19
014-0064-19
014-0064-10
014-0064-10
014-0064-19
014-0064-19
014-0064-19
Relay
P/N
Part Protector
Type*
P/N
040-0166-30
040-0166-20
040-0166-20
040-0166-20
040-0166-30
040-0166-20
040-0166-20
040-0166-20
RP
RP
RP
RP
RP
RP
RP
RP
014-0036-22 014-0064-19 040-0166-20
RP
014-0061-04 014-0064-00 040-0166-09
014-0061-11
040-0166-08
014-0061-04
040-0166-09
014-0061-04
040-0166-09
RP
RP
RP
RP
014-0061-11 014-0064-06 040-0166-33
014-0061-04 014-0064-00 040-0166-09
RP
RP
071-0092-18
071-0099-04
071-0092-18
071-0092-18
071-0092-18
071-0099-04
071-0099-04
071-0099-04
071-0090-03
071-0090-31
071-0090-13
071-0090-31
071-0090-31
071-0099-04
071-0090-05
071-0092-29
071-0099-00
071-0092-27
071-0092-27
071-0090-05
071-0099-07
071-0092-29
071-0090-06
* See Section F Introduction for more information.
FC28
Section_Fc.indd 28
3/4/2008 8:00:11 AM
Electrical Data - Copelametic - Air Cooled
Model
KWE1-0075-TAC
KWE2-0050-CAV
KWE2-0050-IAA
KWE2-0050-IAB
KWE2-0050-IAH
KWE2-0075-CAA
KWE2-0075-CAV
KWG1-0050-TAC
KWG1-0075-TAC
KWG1-0100-TAC
KWG1-0100-TAD
KWG2-0050-CAV
KWG2-0050-IAA
KWG2-0050-IAB
KWG2-0050-IAH
KWG2-0075-CAV
KWG2-0075-IAA
KWG2-0075-IAB
KWG2-0075-IAH
KWG2-0100-CAA
KWG2-0100-CAV
KWGA-010E-TAC
KWGA-010L-TAC
Volts PH
208/230
208/230
115
230
208
115
208/230
208/230
208/230
208/230
460
208/230
115
230
208
208/230
115
230
208
115
208/230
208/230
208/230
3
1
1
1
1
1
1
3
3
3
3
1
1
1
1
1
1
1
1
1
1
3
3
Max
LRA
RLA
3.4
3.4
7.8
4.1
4.1
10.9
5.4
1.9
2.6
4.1
1.6
3.6
7.8
4.1
4.1
5.4
9.5
5.4
5.6
11.9
6.4
4.3
4.3
19.9
24
45
22.5
25.5
65
36
13.2
19.9
27
13.5
24
45
22.5
25.5
36
59.8
30.4
34.1
85.5
40
27
27
Resistance
Run or
Start or
Line to WYE Line to Line
2.28
2.9
0.835
3.305
2.92
0.519
1.9
3.34
2.28
1.59
6.24
2.9
0.835
3.305
2.92
1.9
0.59
2.34
2
0.405
1.37
1.59
1.59
4.551
5.785
2.42
9.585
7.9
1.266
4.24
6.69
4.551
3.179
12.48
5.785
2.42
9.585
7.9
4.24
1.4
5.53
5.15
2.248
4.525
3.179
3.179
Start Cap Run Cap
P/N
P/N
Relay
P/N
Part Protector
Type*
P/N
014-0036-21 014-0064-00 040-0166-09
014-0061-02
040-0166-08
014-0061-09
040-0166-09
014-0061-09
040-0166-09
014-0061-11 014-0064-06 040-0166-33
014-0061-04 014-0064-00 040-0166-09
RP
RP
RP
RP
RP
RP
014-0036-21
014-0061-02
014-0061-09
014-0061-09
014-0061-04
014-0061-11
014-0061-04
014-0061-04
014-0061-05
014-0061-04
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
014-0064-00 040-0166-09
040-0166-08
040-0166-09
040-0166-09
014-0064-00 040-0166-09
040-0166-08
040-0166-09
040-0166-09
014-0064-08 040-0166-11
014-0064-10 040-0166-10
071-0090-41
071-0092-37
071-0092-06
071-0092-05
071-0092-05
071-0099-06
071-0092-29
071-0090-06
071-0090-05
071-0090-16
071-0090-07
071-0092-37
071-0092-06
071-0092-05
071-0092-05
071-0092-29
071-0099-00
071-0092-27
071-0092-27
071-0092-40
071-0092-39
071-0090-50
071-0090-50
* See Section F Introduction for more information.
FC29
Section_Fc.indd 29
3/4/2008 8:00:12 AM
Electrical Data - Copelametic - Air Cooled
Model
KWGA-011E-TAD
KWGA-011L-TAD
KWGA-0150-TAC
KWGA-0150-TAD
KWGA-015A-TAC
KWGB-010E-CAV
KWGB-010L-CAV
KWGB-0150-CAV
KWJ1-0075-TAC
KWJ1-0100-TAC
KWJ1-0100-TAD
KWJ3-0075-CAV
KWJ3-0075-IAA
KWJ3-0075-IAB
KWJ3-0075-IAH
KWJ3-0100-CAA
KWJ3-0100-CAB
KWJ3-0100-CAH
KWJ3-0100-CAV
KWJA-0101-TAC
KWJA-010A-TAC
KWJA-011A-TAC
KWJA-011A-TAD
Volts PH
460
460
208/230
460
208/230
208/230
208/230
208/230
208/230
208/230
460
208/230
115
230
208
115
230
208
208/230
208/230
208/230
208/230
460
3
3
3
3
3
1
1
1
3
3
3
1
1
1
1
1
1
1
1
3
3
3
3
Max
LRA
RLA
2.1
2.1
5.5
2.5
5.5
7.5
7.5
9.6
2.7
3.4
2.1
5.1
9.1
5.4
5.9
12.4
5.4
6.9
6.9
4.5
NA
4.6
2
15
15
35.5
18.2
35.5
40
40
55
19.9
25
15
36
59.8
30.4
34.1
85.5
33.5
36.4
40
27
25
27
15
Resistance
Run or
Start or
Line to WYE Line to Line
6.62
6.62
1.325
4.72
1.325
1.37
1.37
0.94
2.28
2.145
6.62
1.9
0.59
2.34
2
0.405
2.27
1.885
1.37
1.59
2.145
1.59
6.62
13.24
13.24
2.375
9.44
2.375
4.525
4.525
3.45
4.551
4.29
13.24
4.24
1.4
5.53
5.15
2.248
4.935
4.59
4.525
3.179
4.29
3.179
13.24
Start Cap Run Cap
P/N
P/N
Relay
P/N
Part Protector
Type*
P/N
014-0061-04 014-0064-14 040-0166-10
014-0061-04 014-0064-14 040-0166-10
014-0036-22 014-0064-19 040-0166-20
RP
RP
RP
014-0061-04
014-0061-11
014-0061-04
014-0061-04
014-0061-05
014-0061-04
014-0061-04
014-0061-04
RP
RP
RP
RP
RP
RP
RP
RP
014-0064-00 040-0166-09
040-0166-08
040-0166-09
040-0166-09
014-0064-08 040-0166-11
014-0064-00 040-0166-10
014-0064-00 040-0166-25
014-0064-10 040-0166-10
071-0090-42
071-0090-42
071-0090-39
071-0090-27
071-0090-39
071-0092-42
071-0092-42
071-0099-04
071-0090-05
071-0090-04
071-0090-07
071-0092-29
071-0099-00
071-0092-27
071-0092-27
071-0092-23
071-0092-25
071-0092-14
071-0092-39
071-0090-16
071-0090-04
071-0090-50
071-0090-42
* See Section F Introduction for more information.
FC30
Section_Fc.indd 30
3/4/2008 8:00:12 AM
Electrical Data - Copelametic - Air Cooled
Model
KWJA-011E-TAC
KWJA-011E-TAD
KWJB-0100-CAV
KWJB-010E-CAV
KWJC-011E-TAC
KWK1-0100-TAC
KWK1-0100-TAD
KWK2-0100-CAA
KWK2-0100-CAB
KWK2-0100-CAH
KWK2-0100-CAV
KWKA-010A-TAC
KWKA-011E-TAD
KWKA-0200-TAC
KWKA-0200-TAD
KWKA-020A-TAC
KWKA-020A-TAD
KWKA-020E-TAC
KWKB-0150-CAB
KWKB-0200-CAV
KWKB-020A-CAV
KWKB-021E-CAV
KWL1-0100-TAC
Volts PH
208/230
460
208/230
208/230
208/230
208/230
460
115
230
208
208/230
208/230
460
208/230
460
208/230
460
208/230
230
208/230
208/230
208/230
208/230
3
3
1
1
3
3
3
1
1
1
1
3
3
3
3
3
3
3
1
1
1
1
3
Max
LRA
RLA
4.6
2.1
6.9
6.9
4.6
3.3
1.9
11.4
5.4
7
7.3
3.3
2.4
6.8
3
6.8
3
6.5
7.5
9.1
9.1
10.6
3.3
27
15
40
40
27
25
15
85.5
33.5
36.4
40
25
15
50
25
50
25
50
44
55
55
55
25
Resistance
Run or
Start or
Line to WYE Line to Line
1.59
6.62
1.37
1.37
1.59
2.145
6.62
0.405
2.27
1.885
1.37
2.145
6.62
0.795
3.165
0.795
3.165
0.795
1.65
0.94
0.94
0.94
2.145
3.179
13.24
4.525
4.525
3.179
4.29
13.24
2.248
4.935
4.59
4.525
4.29
13.24
1.589
6.329
1.589
6.329
1.589
4.19
3.45
3.45
3.45
4.29
Start Cap Run Cap
P/N
P/N
Relay
P/N
Part Protector
Type*
P/N
014-0061-04 014-0064-10 040-0166-10
014-0061-04 014-0064-10 040-0166-10
RP
RP
014-0061-05
014-0061-04
014-0061-04
014-0061-04
040-0166-11
040-0166-10
040-0166-25
040-0166-10
RP
RP
RP
RP
014-0036-21 014-0064-11 040-0166-20
014-0036-22 014-0064-19 040-0166-20
014-0036-22 014-0064-19 040-0166-20
014-0036-22 014-0064-14 040-0166-20
RP
RP
RP
RP
014-0064-08
014-0064-00
014-0064-00
014-0064-10
071-0090-50
071-0090-42
071-0092-39
071-0092-39
071-0090-50
071-0090-04
071-0090-07
071-0092-23
071-0092-25
071-0092-14
071-0092-39
071-0090-04
071-0090-42
071-0090-35
071-0090-16
071-0090-35
071-0090-16
071-0090-35
071-0092-29
071-0099-04
071-0099-04
071-0099-04
071-0090-04
* See Section F Introduction for more information.
FC31
Section_Fc.indd 31
3/4/2008 8:00:13 AM
Electrical Data - Copelametic - Air Cooled
Model
KWL1-0100-TAD
KWL2-0100-CAA
KWL2-0100-CAB
KWL2-0100-CAH
KWL2-0100-CAV
KWLA-0100-TAD
KWLA-010A-TAC
KWLA-010A-TAD
KWLA-0150-TAC
KWLA-0150-TAD
KWLA-0150-TAU
KWLA-015A-TAC
KWLA-015A-TAD
KWLA-016E-TAC
KWLA-016E-TAD
KWLB-0100-CAV
KWLB-0150-CAB
KWLB-0150-CAH
KWLB-0150-CAV
KWLB-015A-CAB
KWLB-015A-CAV
KWLB-015E-CAV
KWM1-0050-TAC
Volts PH
460
115
230
208
208/230
460
208/230
460
208/230
460
200
208/230
460
208/230
460
208/230
230
208
208/230
230
208/230
208/230
208/230
3
1
1
1
1
3
3
3
3
3
3
3
3
3
3
1
1
1
1
1
1
1
3
Max
LRA
RLA
1.8
10.9
5.5
6.8
6.9
1.8
3.3
1.8
5.4
2.9
6.6
5.4
2.9
6.6
3.4
6.9
5.6
8.1
9.9
5.6
9.9
9.9
1.7
15
85.5
33.5
36.4
40
15
25
15
35.5
18.2
48.2
35.5
18.2
50
25
40
44
45
55
44
55
55
13.2
Resistance
Run or
Start or
Line to WYE Line to Line
6.62
0.405
2.27
1.885
1.37
6.62
2.145
6.62
1.325
4.72
0
1.325
4.72
0.795
3.165
1.37
1.65
1.32
0.94
1.65
0.94
0.94
3.34
13.24
2.248
4.935
4.59
4.525
13.24
4.29
13.24
2.375
9.44
1.463
2.375
9.44
1.589
6.329
4.525
4.19
4.19
3.45
4.19
3.45
3.45
6.69
Start Cap Run Cap
P/N
P/N
Relay
P/N
Part Protector
Type*
P/N
014-0061-05
014-0061-04
014-0061-04
014-0061-04
014-0064-08
014-0064-00
014-0064-00
014-0064-10
040-0166-11
040-0166-10
040-0166-25
040-0166-10
RP
RP
RP
RP
014-0061-04
014-0036-21
014-0036-21
014-0036-22
014-0036-21
014-0036-22
014-0036-22
014-0064-10
014-0064-10
014-0064-10
014-0064-19
014-0064-10
014-0064-19
014-0064-19
040-0166-10
040-0166-20
040-0166-30
040-0166-20
040-0166-20
040-0166-20
040-0166-20
RP
RP
RP
RP
RP
RP
RP
071-0090-07
071-0092-23
071-0092-25
071-0092-14
071-0092-39
071-0090-07
071-0090-04
071-0090-07
071-0090-03
071-0090-27
071-0090-28
071-0090-03
071-0090-27
071-0090-35
071-0090-16
071-0092-39
071-0092-16
071-0092-18
071-0099-04
071-0092-16
071-0099-04
071-0099-04
071-0090-06
* See Section F Introduction for more information.
FC32
Section_Fc.indd 32
3/4/2008 8:00:13 AM
Electrical Data - Copelametic - Air Cooled
Model
KWM1-0075-TAC
KWM1-0100-TAC
KWM1-0100-TAD
KWM2-0050-CAV
KWM2-0050-IAA
KWM2-0050-IAB
KWM2-0050-IAH
KWM2-0075-CAV
KWM2-0075-IAA
KWM2-0075-IAB
KWM2-0075-IAH
KWM2-0100-CAA
KWM2-0100-CAV
KWMA-0075-TAC
KWMA-007E-TAC
KWMB-0075-CAA
KWMB-0075-CAV
KWMB-007E-CAA
KWMB-007E-CAV
KWMC-007E-TAC
KWN1-0050-TAC
KWN1-0075-TAC
KWN2-0050-CAV
Volts PH
208/230
208/230
460
208/230
115
230
208
208/230
115
230
208
115
208/230
208/230
208/230
115
208/230
115
208/230
208/230
208/230
208/230
208/230
3
3
3
1
1
1
1
1
1
1
1
1
1
3
3
1
1
1
1
3
3
3
1
Max
LRA
RLA
2.7
4.5
2.2
3.7
7.2
3.8
3.8
5.6
9.2
6
6.1
15.5
7.5
3.2
3.2
10.9
5.6
10.9
5.6
3.2
2.1
3.5
3.6
19.9
27
13.5
24
45
22.5
25.5
36
59.8
30.4
34.1
93
40
19.9
19.9
85.5
36
85.5
36
19.9
13.2
19.9
24
Resistance
Run or
Start or
Line to WYE Line to Line
2.28
1.59
6.24
2.9
0.835
3.305
2.92
1.9
0.59
2.34
2
0.376
1.37
2.28
2.28
0.405
1.9
0.405
1.9
2.28
3.34
2.28
2.9
4.551
3.179
12.48
5.785
2.42
9.585
7.9
4.24
1.4
5.53
5.15
1.837
4.525
4.551
4.551
2.248
4.24
2.248
4.24
4.551
6.69
4.551
5.785
Start Cap Run Cap
P/N
P/N
Relay
P/N
Part Protector
Type*
P/N
014-0036-21
014-0061-02
014-0061-09
014-0061-09
014-0061-04
014-0061-11
014-0061-04
014-0061-04
014-0061-05
014-0061-04
014-0064-00 040-0166-09
040-0166-08
040-0166-09
040-0166-09
014-0064-00 040-0166-09
040-0166-08
040-0166-09
040-0166-09
014-0064-08 040-0166-11
014-0064-10 040-0166-10
RP
RP
RP
RP
RP
RP
RP
RP
RP
RP
014-0061-05
014-0061-04
014-0061-05
014-0061-04
014-0064-08
014-0064-00
014-0064-08
014-0064-00
040-0166-11
040-0166-09
040-0166-21
040-0166-09
RP
RP
RP
RP
014-0036-21 014-0064-00 040-0166-09
RP
071-0090-05
071-0090-40
071-0090-43
071-0092-37
071-0092-06
071-0092-05
071-0092-05
071-0092-29
071-0099-00
071-0092-27
071-0092-27
071-0099-05
071-0092-39
071-0090-41
071-0090-41
071-0092-40
071-0092-29
071-0092-40
071-0092-29
071-0090-41
071-0090-06
071-0090-41
071-0092-37
* See Section F Introduction for more information.
FC33
Section_Fc.indd 33
3/4/2008 8:00:14 AM
Electrical Data - Copelametic - Air Cooled
Model
KWN2-0050-IAA
KWN2-0050-IAB
KWN2-0050-IAH
KWN2-0075-CAA
KWN2-0075-CAV
KWNA-006E-TAC
KWNA-007E-TAC
KWNB-0050-CAV
KWNB-0050-IAA
KWNB-005A-CAV
KWNB-005E-CAV
KWNB-005E-IAA
KWNB-007E-CAV
KWR1-0100-TAC
KWR1-0100-TAD
KWR2-0100-CAA
KWR2-0100-CAV
KWRA-010E-TAC
KWRA-011E-TAD
KWRA-011L-TAD
KWRB-010E-CAV
KWTA-0100-TAC
KWTA-0100-TAD
Volts PH
115
230
208
115
208/230
208/230
208/230
208/230
115
208/230
208/230
115
208/230
208/230
460
115
208/230
208/230
460
460
208/230
208/230
460
1
1
1
1
1
3
3
1
1
1
1
1
1
3
3
1
1
3
3
3
1
3
3
Max
LRA
RLA
8.1
4.2
4.2
11.7
6.1
2.2
3.5
3.6
8
3.6
3.6
8
NA
4.3
2.2
15.4
7.4
4.3
2
2
7.4
3.9
2.1
45
22.5
25.5
65
36
13.2
19.9
24
45
24
24
45
36
27
13.5
93
40
27
15
15
40
25
15
Resistance
Run or
Start or
Line to WYE Line to Line
0.835
3.305
2.92
0.519
1.9
3.34
2.28
2.9
0.835
2.9
2.9
0.835
1.9
1.59
6.24
0.376
1.37
1.59
6.62
6.62
1.37
2.145
6.62
2.42
9.585
7.9
1.266
4.24
6.69
4.551
5.785
2.42
5.785
5.785
2.42
4.24
3.179
12.48
1.837
4.525
3.179
13.24
13.24
4.525
4.29
13.24
Start Cap Run Cap
P/N
P/N
Relay
P/N
Part Protector
Type*
P/N
014-0061-02
040-0166-08
014-0061-09
040-0166-09
014-0061-09
040-0166-09
014-0061-11 014-0064-06 040-0166-33
014-0061-04 014-0064-00 040-0166-09
RP
RP
RP
RP
RP
014-0036-21
014-0061-02
014-0036-21
014-0036-21
014-0061-02
014-0061-04
014-0064-00 040-0166-09
040-0166-08
014-0064-00 040-0166-09
014-0064-00 040-0166-09
040-0166-08
014-0064-00 040-0166-09
RP
RP
RP
RP
RP
RP
014-0061-05 014-0064-08 040-0166-11
014-0061-04 014-0064-10 040-0166-10
RP
RP
014-0061-04 014-0064-10 040-0166-10
RP
071-0092-06
071-0092-05
071-0092-05
071-0099-06
071-0092-41
071-0090-21
071-0090-41
071-0092-37
071-0092-06
071-0092-37
071-0092-37
071-0092-06
071-0092-41
071-0090-40
071-0090-43
071-0099-05
071-0092-39
071-0090-40
071-0090-42
071-0090-42
071-0092-39
071-0090-04
071-0090-07
* See Section F Introduction for more information.
FC34
Section_Fc.indd 34
3/4/2008 8:00:14 AM
Electrical Data - Copelametic - Air Cooled
Model
KWTA-010A-TAC
KWTA-010A-TAD
KWTA-0150-TAC
KWTA-0150-TAD
KWTA-015A-TAC
KWTA-015A-TAD
KWTB-0100-CAA
KWTB-0100-CAB
KWTB-0100-CAH
KWTB-0100-CAV
KWTB-010A-CAH
KWTB-010A-CAV
KWTB-0150-CAB
KWTB-0150-CAH
KWTB-0150-CAV
LAC1-0300-TAE
LAC1-0310-CAB
LAC1-0310-TAC
LAC1-0310-TAD
LAC1-0310-TAU
LACA-031A-TAC
LACA-032A-TAD
LACA-032E-TAC
Volts PH
208/230
460
208/230
460
208/230
460
115
230
208
208/230
208
208/230
230
208
208/230
575
230
208/230
460
200
208/230
460
208/230
3
3
3
3
3
3
1
1
1
1
1
1
1
1
1
3
1
3
3
3
3
3
3
Max
LRA
RLA
3.9
2.1
5
2.9
5
2.9
12.4
5.5
7.3
7.2
7.3
7.2
6.1
7.8
9.6
NA
NA
NA
NA
NA
9.2
6
12.8
25
15
35.5
18.2
35.5
18.2
85.5
33.5
36.4
40
36.4
40
44
45
55
30
86
82
41
99.7
82
56
112
Resistance
Run or
Start or
Line to WYE Line to Line
2.145
6.62
1.325
4.72
1.325
4.72
0.405
2.27
1.885
1.37
1.885
1.37
1.65
1.32
0.94
2.7
0.61
0.47
1.9
0
0.47
1.145
0.291
4.29
13.24
2.375
9.44
2.375
9.44
2.248
4.935
4.59
4.525
4.59
4.525
4.19
4.19
3.45
5.4
2.54
0.9
3.6
0.056
0.9
2.29
0.581
Start Cap Run Cap
P/N
P/N
014-0061-05
014-0061-04
014-0061-04
014-0061-04
014-0061-04
014-0061-04
014-0036-21
014-0036-21
014-0036-22
014-0064-08
014-0064-00
014-0064-00
014-0064-10
014-0064-00
014-0064-10
014-0064-10
014-0064-10
014-0064-19
Relay
P/N
Part Protector
Type*
P/N
040-0166-11
040-0166-10
040-0166-25
040-0166-10
040-0166-25
040-0166-10
040-0166-20
040-0166-30
040-0166-20
RP
RP
RP
RP
RP
RP
RP
RP
RP
014-0006-13 014-0064-14 040-0166-28
RP
071-0090-04
071-0090-07
071-0090-03
071-0090-27
071-0090-03
071-0090-27
071-0092-23
071-0092-25
071-0092-14
071-0092-39
071-0092-14
071-0092-39
071-0092-18
071-0092-18
071-0099-04
071-0090-14
071-0119-01
071-0090-01
071-0090-03
071-0090-30
071-0090-01
071-0090-54
071-0090-47
* See Section F Introduction for more information.
FC35
Section_Fc.indd 35
3/4/2008 8:00:14 AM
Electrical Data - Copelametic - Air Cooled
Model
LACA-032E-TAD
LACA-032L-TAC
LACA-032L-TAD
LACB-031A-CAB
LACB-032E-CAB
LACB-032L-CAB
LAH1-0300-TAE
LAH1-0310-CAB
LAH1-0310-TA7
LAH1-0310-TAC
LAH1-0310-TAD
LAHA-0310-TAC
LAHA-0310-TAD
LAHA-031A-TAC
LAHA-031A-TAD
LAHA-031E-TAC
LAHA-031L-TAC
LAHA-031L-TAD
LAHA-0320-TA7
LAHA-0320-TAC
LAHA-0320-TAU
LAHA-032A-TAE
LAHA-032E-TAC
Volts PH
460
208/230
460
230
230
230
575
230
380
208/230
460
208/230
460
208/230
460
208/230
208/230
460
380
208/230
200
575
208/230
3
3
3
1
1
1
3
1
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Max
LRA
RLA
6
12.8
6
15.4
15.5
15.5
4
15.1
6.9
9.9
5.7
9.9
NA
8.5
5.1
8.5
8.5
5.1
6.1
12.8
12.8
4.1
12.8
56
112
56
86
105
105
30
86
46
82
41
82
41
82
41
82
82
41
56
112
112
30
112
Resistance
Run or
Start or
Line to WYE Line to Line
1.145
0.291
1.145
0.61
0.472
0.472
2.7
0.61
0
0.47
1.9
0.47
1.675
0.444
1.675
0.444
0.444
1.675
1.145
0.291
0.291
2.7
0.291
2.29
0.581
2.29
2.54
1.36
1.36
5.4
2.54
2.76
0.9
3.6
0.9
3.35
0.943
3.35
0.943
0.943
3.35
2.29
0.581
0.581
5.4
0.581
Start Cap Run Cap
P/N
P/N
Relay
P/N
Part Protector
Type*
P/N
014-0006-13 014-0064-14 040-0166-28
014-0006-13 014-0064-18 040-0166-28
014-0006-13 014-0064-18 040-0166-28
RP
RP
RP
014-0006-13 014-0064-12 040-0166-28
RP
071-0090-54
071-0090-47
071-0090-54
071-0119-01
071-0119-05
071-0119-05
071-0090-14
071-0119-01
071-0090-33
071-0090-19
071-0090-03
071-0090-19
071-0090-03
071-0090-19
071-0090-03
071-0090-19
071-0090-19
071-0090-03
071-0090-46
071-0090-47
071-0090-47
071-0090-14
071-0090-47
* See Section F Introduction for more information.
FC36
Section_Fc.indd 36
3/4/2008 8:00:15 AM
Electrical Data - Copelametic - Air Cooled
Model
LAHA-032E-TAD
LAHA-032E-TAE
LAHA-032L-TAC
LAHA-032L-TAD
LAHA-032L-TAE
LAHB-0311-CAB
LAHB-031A-CAB
LAHB-031E-CAB
LAHB-031L-CAB
LAHB-032E-CAB
LAHB-032L-CAB
LAL1-0300-TAE
LAL1-0310-CAB
LAL1-0310-TAC
LAL1-0310-TAD
LAL1-031L-TAC
LAL1-031L-TAD
LALA-031A-TAC
LALA-032E-FXX
LALA-032E-TAC
LALA-032E-TAD
LALA-032L-TAC
LALA-032L-TAD
Volts PH
460
575
208/230
460
575
230
230
230
230
230
230
575
230
208/230
460
208/230
460
208/230
55
208/230
460
208/230
460
3
3
3
3
3
1
1
1
1
1
1
3
1
3
3
3
3
3
3
3
3
3
3
Max
LRA
RLA
6
4.1
12.8
6
4.1
16.6
16.6
16.6
16.6
16.7
16.7
NA
NA
NA
NA
10.9
5
10.9
NA
12.6
6.2
12.6
6.2
56
30
112
56
30
93
93
93
93
105
105
30
86
82
41
82
41
82
320
112
56
112
56
Resistance
Run or
Start or
Line to WYE Line to Line
1.145
2.7
0.291
1.145
2.7
0.574
0.574
0.574
0.574
0.472
0.472
2.7
0.61
0.47
1.9
0.47
1.9
0.47
0
0.291
1.145
0.291
1.145
2.29
5.4
0.581
2.29
5.4
1.899
1.899
1.899
1.899
1.36
1.36
5.4
2.54
0.9
3.6
0.9
3.6
0.9
0.12
0.581
2.29
0.581
2.29
Start Cap Run Cap
P/N
P/N
014-0006-13
014-0006-13
014-0006-13
014-0006-13
014-0006-13
014-0006-13
014-0064-14
014-0064-14
014-0064-14
014-0064-14
014-0064-18
014-0064-18
Relay
P/N
Part Protector
Type*
P/N
040-0166-28
040-0166-28
040-0166-28
040-0166-28
040-0166-28
040-0166-28
RP
RP
RP
RP
RP
RP
014-0006-13 014-0064-14 040-0166-28
RP
071-0090-54
071-0090-14
071-0090-47
071-0090-54
071-0090-14
071-0119-05
071-0119-05
071-0119-05
071-0119-05
071-0119-05
071-0119-05
071-0090-14
071-0119-01
071-0090-18
071-0090-03
071-0090-18
071-0090-03
071-0090-18
071-0090-47
071-0090-46
071-0090-47
071-0090-46
* See Section F Introduction for more information.
FC37
Section_Fc.indd 37
3/4/2008 8:00:15 AM
Electrical Data - Copelametic - Air Cooled
Model
Volts PH
LALB-031A-CAB
230
LALB-032E-CAB
230
LALB-032L-CAB
230
LAM1-0300-TAE
575
LAM1-0310-CAB
230
LAM1-0310-TAC 208/230
LAM1-0310-TAD
460
LAMA-031A-TAC 208/230
LAMA-031A-TAD
460
LAMB-031A-CAB 230
1
1
1
3
1
3
3
3
3
1
Max
LRA
RLA
14.2
15
15
4
12.7
10
4.7
10
4.7
12.7
86
105
105
30
86
82
41
82
41
86
Resistance
Run or
Start or
Line to WYE Line to Line
0.61
0.472
0.472
2.7
0.61
0.47
1.9
0.47
1.9
0.61
2.54
1.36
1.36
5.4
2.54
0.9
3.6
0.9
3.6
2.54
Start Cap Run Cap
P/N
P/N
Relay
P/N
Part Protector
Type*
P/N
014-0006-13 014-0064-14 040-0166-28
014-0006-13 014-0064-18 040-0166-28
014-0006-13 014-0064-18 040-0166-28
RP
RP
RP
014-0006-13 014-0064-12 040-0166-28
RP
014-0006-13 014-0064-12 040-0166-28
RP
071-0119-01
071-0119-05
071-0119-05
071-0090-13
071-0119-01
071-0090-01
071-0090-03
071-0090-01
071-0090-03
071-0119-01
* See Section F Introduction for more information.
FC38
Section_Fc.indd 38
3/4/2008 8:00:16 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
2DA3-060E-TFE
2DA3F23K0-TFC
2DA3F23K0-TFD
2DA3F23K0-TFE
2DA3F23KE-TFC
2DA3F23KE-TFD
2DA3F23KE-TFE
2DA3F23KL-TFC
2DA3F23KL-TFD
2DA3F23KL-TFE
2DA3R58K0-TFC
2DA3R58K0-TFD
2DA3R89K0-TFC
2DA3R89K0-TFD
2DA3R89K0-TFE
2DA3R89KE-TFC
2DA3R89KE-TFD
2DA3R89KE-TFE
2DA3R89KL-TFC
2DA3R89KL-TFD
2DA3R89KL-TFE
2DA8F23KE-TFD
2DB3F25K0-TFC
Max LRA
Volts PH RLA
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
208/230
460
575
208/230
460
575
208/230
460
575
460
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
9.1
28.8
9.7
9.1
28.8
9.7
9.1
28.8
9.7
9.1
22.3
10.4
32
14.1
13.3
32
14.1
13.3
32
14.1
13.3
9.7
28.2
49
161
60
49
161
60
49
161
60
49
120
60
169
85
67
169
85
67
169
85
67
60
161
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
3.714
0.419
2.382
3.714
0.419
2.382
3.714
0.419
2.382
3.714
0.595
2.382
0.386
1.508
2.518
0.386
1.508
2.518
0.386
1.508
2.518
2.382
0.419
* See Section F Introduction for more information.
Section_Fd.indd 1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Relay
P/N
Part Protector
Type*
P/N
071-0429-18
071-0429-08
071-0429-10
071-0429-18
071-0429-08
071-0429-10
071-0429-18
071-0429-08
071-0429-10
071-0429-18
071-0429-02
071-0429-10
071-0429-08
071-0429-05
071-0429-25
071-0429-08
071-0429-05
071-0429-25
071-0429-08
071-0429-05
071-0429-25
071-0429-10
071-0429-08
FD1
3/4/2008 8:02:47 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
2DB3F25K0-TFD
2DB3F25K0-TFE
2DB3F25KE-TFC
2DB3F25KE-TFD
2DB3F25KE-TFE
2DB3F25KL-TFC
2DB3F25KL-TFD
2DB3F25KL-TFE
2DB3R61K0-TFC
2DB3R61K0-TFD
2DB8F25KE-TFD
2DC3-0500-TFD
2DC3-050E-TFC
2DC3-050E-TFD
2DC3R53K0-CFB
2DC3R53K0-TFC
2DC3R53K0-TFD
2DC3R53K0-TFE
2DC3R53KE-TFC
2DC3R53KE-TFD
2DC3R53KE-TFE
2DC3R53KL-CFB
2DC3R53KL-TFC
FD2
Max LRA
Volts PH RLA
460
575
208/230
460
575
208/230
460
575
208/230
460
460
460
208/230
460
230
208/230
460
575
208/230
460
575
230
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
1
3
3
3
3
3
3
1
3
13.3
9.6
28.2
13.3
9.6
28.2
13.3
9.6
19.1
10.2
13.3
10.4
22.3
10.4
30.2
22.3
10.4
7.7
22.3
10.4
7.7
30.2
22.3
80
63
161
80
63
161
80
63
120
60
80
60
120
60
125
120
60
49
120
60
49
125
120
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
1.674
2.614
0.419
1.674
2.614
0.419
1.674
2.614
0.595
2.382
1.674
2.382
0.595
2.382
1.4
0.595
2.382
3.714
0.595
2.382
3.714
1.4
0.595
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0.37
0
0
0
0
0
0
0.37
0
Relay
P/N
Part Protector
Type*
P/N
014-0006-14 014-0064-18 040-0166-23
RP
014-0006-14 014-0064-18 040-0166-23
RP
071-0429-05
071-0429-26
071-0429-08
071-0429-05
071-0429-26
071-0429-08
071-0429-05
071-0429-26
071-0429-02
071-0429-10
071-0429-05
071-0429-10
071-0429-13
071-0429-10
071-0476-01
071-0429-13
071-0429-10
071-0429-23
071-0429-13
071-0429-10
071-0429-23
071-0476-01
071-0429-13
* See Section F Introduction for more information.
Section_Fd.indd 2
3/4/2008 8:02:52 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
2DC3R53KL-TFD
2DC3R53KL-TFE
2DCJR53K0-TFC
2DD3-050E-TFD
2DD3R63K0-TFC
2DD3R63K0-TFD
2DD3R63K0-TFE
2DD3R63KE-TFC
2DD3R63KE-TFD
2DD3R63KE-TFE
2DD3R63KL-TFC
2DD3R63KL-TFD
2DD3R63KL-TFE
2DD8R63K0-TFC
2DF3-0300-CFB
2DF3-0300-TFC
2DF3-030E-CFB
2DF3-030E-TFC
2DF3F16K0-CFB
2DF3F16K0-TFC
2DF3F16K0-TFD
2DF3F16K0-TFE
2DF3F16KE-CFB
Max LRA
Volts PH RLA
460
575
208/230
460
208/230
460
575
208/230
460
575
208/230
460
575
208/230
230
208/230
230
208/230
230
208/230
460
575
230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
1
3
1
3
1
3
3
3
1
10.4
7.7
22.3
10.5
22.3
10.5
7.9
22.3
10.5
7.9
22.3
10.5
7.9
22.3
25.7
16.9
25.7
16.9
25.7
16.9
8.1
6.7
25.7
60
49
120
60
120
60
49
120
60
49
120
60
49
120
125
102
125
102
125
102
52
41
125
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
2.382
3.714
0.595
2.382
0.595
2.382
3.714
0.595
2.382
3.714
0.595
2.382
3.714
0.595
1.4
0.67
1.4
0.67
1.4
0.67
2.68
4.406
1.4
* See Section F Introduction for more information.
Section_Fd.indd 3
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0.37
0
0.37
0
0.37
0
0
0
0.37
Relay
P/N
Part Protector
Type*
P/N
014-0006-14 014-0064-18 040-0166-23
RP
014-0006-14 014-0064-18 040-0166-23
RP
014-0006-14 014-0064-18 040-0166-23
RP
014-0006-14 014-0064-18 040-0166-23
RP
071-0429-10
071-0429-23
071-0429-13
071-0429-10
071-0429-24
071-0429-10
071-0429-23
071-0429-24
071-0429-10
071-0429-23
071-0429-24
071-0429-10
071-0429-23
071-0429-24
071-0476-01
071-0429-22
071-0476-01
071-0429-22
071-0476-01
071-0429-22
071-0429-23
071-0429-27
071-0476-01
FD3
3/4/2008 8:02:52 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
2DF3F16KE-TFC
2DF3F16KE-TFD
2DF3F16KE-TFE
2DF3F16KL-TFC
2DF3F16KL-TFD
2DF3F16KL-TFE
2DL3-075E-TFC
2DL3F20K0-TFC
2DL3F20K0-TFD
2DL3F20K0-TFE
2DL3F20KE-TFC
2DL3F20KE-TFD
2DL3F20KE-TFE
2DL3F20KL-TFC
2DL3F20KL-TFD
2DL3F20KL-TFE
2DL3R78K0-TFC
2DL3R78K0-TFD
2DL3R78K0-TFE
2DL3R78KE-TFC
2DL3R78KE-TFD
2DL3R78KE-TFE
2DL3R78KL-TFC
FD4
Max LRA
Volts PH RLA
208/230
460
575
208/230
460
575
208/230
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
16.9
8.1
6.7
16.9
8.1
6.7
31.6
26.3
8.7
7.7
26.3
8.7
7.7
26.3
8.7
7.7
31.6
13.9
13.2
31.6
13.9
13.2
31.6
102
52
41
102
52
41
169
161
60
49
161
60
49
161
60
49
169
85
67
169
85
67
169
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
0.67
2.68
4.406
0.67
2.68
4.406
0.386
0.419
2.382
3.714
0.419
2.382
3.714
0.419
2.382
3.714
0.386
1.508
2.518
0.386
1.508
2.518
0.386
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Relay
P/N
Part Protector
Type*
P/N
071-0429-22
071-0429-23
071-0429-27
071-0429-22
071-0429-23
071-0429-27
071-0429-08
071-0429-08
071-0429-10
071-0429-23
071-0429-08
071-0429-10
071-0429-23
071-0429-08
071-0429-10
071-0429-23
071-0429-08
071-0429-05
071-0429-25
071-0429-08
071-0429-05
071-0429-25
071-0429-08
* See Section F Introduction for more information.
Section_Fd.indd 4
3/4/2008 8:02:52 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
2DL3R78KL-TFD
2DL3R78KL-TFE
3DA3A0500-TFC
3DA3A0500-TFD
3DA3A0500-TFE
3DA3A0600-TFC
3DA3A0600-TFD
3DA3A0600-TFE
3DA3A060E-TFC
3DA3A060E-TFD
3DA3A060E-TFE
3DA3A060L-TFC
3DA3A060L-TFD
3DA3A060L-TFE
3DA3A0750-TFC
3DA3A0750-TFD
3DA3A0750-TFE
3DA3A0750-TFU
3DA3A075E-TFC
3DA3A075E-TFD
3DA3A075E-TFE
3DA3A075L-TFC
3DA3A075L-TFD
Max LRA
Volts PH RLA
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
200
208/230
460
575
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
13.9
13.2
18.6
9.1
7.9
30.3
13.7
10.5
30.3
13.7
10.5
30.3
13.7
10.5
41
20
16.4
34.9
41
20
16.4
41
20
85
67
115
58
43
150
77
62
150
77
62
150
77
62
215
106
84
196
215
106
84
215
106
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
1.508
2.518
0.603
2.412
3.794
0.419
1.676
2.6
0.419
1.676
2.6
0.419
1.676
2.6
0.295
1.178
1.835
0.294
0.295
1.178
1.835
0.295
1.178
* See Section F Introduction for more information.
Section_Fd.indd 5
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Relay
P/N
Part Protector
Type*
P/N
071-0429-05
071-0429-25
071-0429-02
071-0429-03
071-0429-19
071-0429-08
071-0429-05
071-0429-03
071-0429-08
071-0429-05
071-0429-03
071-0429-08
071-0429-05
071-0429-03
071-0429-06
071-0429-17
071-0429-11
071-0429-04
071-0429-06
071-0429-17
071-0429-11
071-0429-06
071-0429-17
FD5
3/4/2008 8:02:53 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
3DA3A075L-TFE
3DA3F18K0-TFC
3DA3F18K0-TFD
3DA3F28K0-TFC
3DA3F28K0-TFD
3DA3F28K0-TFE
3DA3F28KE-TFC
3DA3F28KE-TFD
3DA3F28KE-TFE
3DA3F28KL-TFC
3DA3F28KL-TFD
3DA3F28KL-TFE
3DA3R10M0-TFC
3DA3R10M0-TFD
3DA3R10M0-TFE
3DA3R10M0-TFU
3DA3R10ME-TFC
3DA3R10ME-TFD
3DA3R10ME-TFE
3DA3R10ML-TFC
3DA3R10ML-TFD
3DA3R10ML-TFE
3DA8A0500-TFD
FD6
Max LRA
Volts PH RLA
575
208/230
460
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
200
208/230
460
575
208/230
460
575
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
16.4
18.6
9.1
30.3
13.7
10.5
30.3
13.7
10.5
30.3
13.7
10.5
41
20
16.4
34.9
41
20
16.4
41
20
16.4
9.1
84
115
58
150
77
62
150
77
62
150
77
62
215
106
84
196
215
106
84
215
106
84
58
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
1.835
0.603
2.412
0.419
1.676
2.6
0.419
1.676
2.6
0.419
1.676
2.6
0.295
1.178
1.835
0.294
0.295
1.178
1.835
0.295
1.178
1.835
2.412
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Relay
P/N
Part Protector
Type*
P/N
071-0429-11
071-0429-02
071-0429-03
071-0429-08
071-0429-05
071-0429-03
071-0429-08
071-0429-05
071-0429-03
071-0429-08
071-0429-05
071-0429-03
071-0429-06
071-0429-17
071-0429-11
071-0429-04
071-0429-06
071-0429-17
071-0429-11
071-0429-06
071-0429-17
071-0429-11
071-0429-03
* See Section F Introduction for more information.
Section_Fd.indd 6
3/4/2008 8:02:53 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
3DA8A0501-TFD
3DA8A051E-TFD
3DA8A060E-TFD
3DA8F28KE-TFD
3DB3A0500-TFC
3DB3A0500-TFD
3DB3A0500-TFE
3DB3A0750-TFC
3DB3A0750-TFD
3DB3A0750-TFE
3DB3A075E-TFC
3DB3A075E-TFD
3DB3A075E-TFE
3DB3A075L-TFC
3DB3A075L-TFD
3DB3A075L-TFE
3DB3A0900-TFU
3DB3A1000-TFC
3DB3A1000-TFD
3DB3A1000-TFE
3DB3A100E-TFC
3DB3A100E-TFD
3DB3A100E-TFE
Max LRA
Volts PH RLA
460
460
460
460
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
200
208/230
460
575
208/230
460
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
9.1
9.1
13.7
13.7
18
10.1
7.5
31.4
16.1
11
31.4
16.1
11
31.4
16.1
11
36.8
43.6
20
16.5
43.6
20
16.5
58
58
77
77
115
58
43
161
83
67
161
83
67
161
83
67
196
215
106
84
215
106
84
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
2.412
2.412
1.676
1.676
0.603
2.412
3.794
0.385
1.54
2.508
0.385
1.54
2.508
0.385
1.54
2.508
0.294
0.295
1.178
1.835
0.295
1.178
1.835
* See Section F Introduction for more information.
Section_Fd.indd 7
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Relay
P/N
Part Protector
Type*
P/N
071-0429-03
071-0429-03
071-0429-05
071-0429-05
071-0429-02
071-0429-03
071-0429-19
071-0429-04
071-0429-09
071-0429-03
071-0429-04
071-0429-09
071-0429-03
071-0429-04
071-0429-09
071-0429-03
071-0429-20
071-0429-06
071-0429-17
071-0429-11
071-0429-06
071-0429-17
071-0429-11
FD7
3/4/2008 8:02:53 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
3DB3A100L-TFC
3DB3A100L-TFD
3DB3A100L-TFE
3DB3F22K0-TFC
3DB3F22K0-TFD
3DB3F27K0-TFU
3DB3F33K0-TFC
3DB3F33K0-TFD
3DB3F33K0-TFE
3DB3F33KE-TFC
3DB3F33KE-TFD
3DB3F33KE-TFE
3DB3F33KL-TFC
3DB3F33KL-TFD
3DB3F33KL-TFE
3DB3R12M0-TFC
3DB3R12M0-TFD
3DB3R12M0-TFE
3DB3R12ME-TFC
3DB3R12ME-TFD
3DB3R12ME-TFE
3DB3R12ML-TFC
3DB3R12ML-TFD
FD8
Max LRA
Volts PH RLA
208/230
460
575
208/230
460
200
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
43.6
20
16.5
18
10.1
36.8
31.4
16.1
11
31.4
16.1
11
31.4
16.1
11
43.6
20
16.5
43.6
20
16.5
43.6
20
215
106
84
115
58
196
161
83
67
161
83
67
161
83
67
215
106
84
215
106
84
215
106
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
0.295
1.178
1.835
0.603
2.412
0.294
0.385
1.54
2.508
0.385
1.54
2.508
0.385
1.54
2.508
0.295
1.178
1.835
0.295
1.178
1.835
0.295
1.178
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Relay
P/N
Part Protector
Type*
P/N
071-0429-06
071-0429-17
071-0429-11
071-0429-02
071-0429-03
071-0429-20
071-0429-04
071-0429-09
071-0429-03
071-0429-04
071-0429-09
071-0429-03
071-0429-04
071-0429-09
071-0429-03
071-0429-06
071-0429-17
071-0429-11
071-0429-06
071-0429-17
071-0429-11
071-0429-06
071-0429-17
* See Section F Introduction for more information.
Section_Fd.indd 8
3/4/2008 8:02:53 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
3DB3R12ML-TFE
3DB4A1000-TFC
3DB4A1000-TFD
3DB4R12M0-TFC
3DB8A075E-TFD
3DB8F33KE-TFD
3DE3A0500-TFC
3DE3A0500-TFD
3DE3A0500-TFE
3DE3A0750-TFC
3DE3A0750-TFD
3DE3A0750-TFE
3DE3A0750-TFU
3DE3A075E-TFC
3DE3A075E-TFD
3DE3A075E-TFE
3DE3A075L-TFC
3DE3A075L-TFD
3DE3A075L-TFE
3DE3R10M0-TFC
3DE3R10M0-TFD
3DE3R10M0-TFE
3DE3R10ME-TFC
Max LRA
Volts PH RLA
575
208/230
460
208/230
460
460
208/230
460
575
208/230
460
575
200
208/230
460
575
208/230
460
575
208/230
460
575
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
16.5
43.6
20
43.6
16.1
16.1
18.6
11
7.9
41
20
16.4
34.9
41
20
16.4
41
20
16.4
41
20
16.4
41
84
215
106
215
83
83
115
58
43
215
106
84
196
215
106
84
215
106
84
215
106
84
215
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
1.835
0.295
1.178
0.295
1.54
1.54
0.603
2.412
3.794
0.295
1.178
1.835
0.294
0.295
1.178
1.835
0.295
1.178
1.835
0.295
1.178
1.835
0.295
* See Section F Introduction for more information.
Section_Fd.indd 9
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Relay
P/N
Part Protector
Type*
P/N
071-0429-11
071-0429-06
071-0429-17
071-0429-06
071-0429-09
071-0429-09
071-0429-02
071-0429-03
071-0429-19
071-0429-06
071-0429-17
071-0429-11
071-0429-04
071-0429-06
071-0429-17
071-0429-11
071-0429-06
071-0429-17
071-0429-11
071-0429-06
071-0429-17
071-0429-11
071-0429-06
FD9
3/4/2008 8:02:54 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
3DE3R10ME-TFD
3DE3R10ME-TFE
3DE3R10ML-TFC
3DE3R10ML-TFD
3DE3R10ML-TFE
3DE8A0500-TFC
3DE8A0500-TFD
3DE8A060E-TFD
3DE8A0750-TFD
3DEHA075E-TFC
3DEHA075E-TFD
3DEHA075E-TFE
3DEHA075L-TFC
3DEHA075L-TFD
3DEHA075L-TFE
3DEHR10ME-TFC
3DEHR10ME-TFD
3DEHR10ME-TFE
3DEHR10ML-TFC
3DEHR10ML-TFD
3DEHR10ML-TFE
3DETA050E-TFD
3DETR70KE-TFD
FD10
Max LRA
Volts PH RLA
460
575
208/230
460
575
208/230
460
460
460
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
460
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
20
16.4
41
20
16.4
18.6
11
13.7
20
41
20
16.4
41
20
16.4
41
20
16.4
41
20
16.4
11
11
106
84
215
106
84
115
58
77
106
215
106
84
215
106
84
215
106
84
215
106
84
58
58
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
1.178
1.835
0.295
1.178
1.835
0.603
2.412
1.676
1.178
0.295
1.178
1.835
0.295
1.178
1.835
0.295
1.178
1.835
0.295
1.178
1.835
2.412
2.412
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Relay
P/N
Part Protector
Type*
P/N
071-0429-17
071-0429-11
071-0429-06
071-0429-17
071-0429-11
071-0429-02
071-0429-03
071-0429-05
071-0429-17
071-0429-06
071-0429-17
071-0429-11
071-0429-06
071-0429-17
071-0429-11
071-0429-06
071-0429-17
071-0429-11
071-0429-06
071-0429-17
071-0429-11
071-0429-03
071-0429-03
* See Section F Introduction for more information.
Section_Fd.indd 10
3/4/2008 8:02:54 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
3DF3A0750-TFC
3DF3A0750-TFD
3DF3A0900-TFC
3DF3A0900-TFD
3DF3A0900-TFE
3DF3A090E-TFC
3DF3A090E-TFD
3DF3A090E-TFE
3DF3A090L-TFC
3DF3A090L-TFD
3DF3A090L-TFE
3DF3A1200-TFC
3DF3A1200-TFD
3DF3A120E-TFC
3DF3A120E-TFD
3DF3A120L-TFC
3DF3A120L-TFD
3DF3F26K0-TFC
3DF3F26K0-TFD
3DF3F40K0-TFC
3DF3F40K0-TFD
3DF3F40K0-TFE
3DF3F40KE-TFC
Max LRA
Volts PH RLA
208/230
460
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
208/230
460
208/230
460
208/230
460
208/230
460
575
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
30.7
15
39
16.9
16.4
39
16.9
16.4
39
16.9
16.4
48.1
23.6
48.1
23.6
48.1
23.6
30.7
15
39
16.9
16.4
39
161
83
215
106
84
215
106
84
215
106
84
275
138
275
138
275
138
161
83
215
106
84
215
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
0.385
1.54
0.295
1.178
1.835
0.295
1.178
1.835
0.295
1.178
1.835
0.229
0.908
0.229
0.908
0.229
0.908
0.385
1.54
0.295
1.178
1.835
0.295
* See Section F Introduction for more information.
Section_Fd.indd 11
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Relay
P/N
Part Protector
Type*
P/N
071-0429-04
071-0429-09
071-0429-00
071-0429-09
071-0429-11
071-0429-00
071-0429-09
071-0429-11
071-0429-00
071-0429-09
071-0429-11
071-0504-05
071-0504-02
071-0504-05
071-0504-02
071-0504-05
071-0504-02
071-0429-04
071-0429-09
071-0429-00
071-0429-09
071-0429-11
071-0429-00
FD11
3/4/2008 8:02:54 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
3DF3F40KE-TFD
3DF3F40KE-TFE
3DF3F40KL-TFC
3DF3F40KL-TFD
3DF3F40KL-TFE
3DF3R15M0-TFC
3DF3R15M0-TFD
3DF3R15ME-TFC
3DF3R15ME-TFD
3DF3R15ML-TFC
3DF3R15ML-TFD
3DF4A0900-TFC
3DF4A0900-TFD
3DF4A1200-TFC
3DF4A1200-TFD
3DF4A120E-TFC
3DF4A120E-TFD
3DF4A120L-TFC
3DF4A120L-TFD
3DF4R15M0-TFC
3DF4R15ME-TFC
3DF4R15ME-TFD
3DF4R15ML-TFC
FD12
Max LRA
Volts PH RLA
460
575
208/230
460
575
208/230
460
208/230
460
208/230
460
208/230
460
208/230
460
208/230
460
208/230
460
208/230
208/230
460
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
16.9
16.4
39
16.9
16.4
48.1
23.6
48.1
23.6
48.1
23.6
39
16.9
48.1
23.6
48.1
23.6
48.1
23.6
48.1
48.1
23.6
48.1
106
84
215
106
84
275
138
275
138
275
138
215
106
275
138
275
138
275
138
275
275
138
275
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
1.178
1.835
0.295
1.178
1.835
0.229
0.908
0.229
0.908
0.229
0.908
0.295
1.178
0.229
0.908
0.229
0.908
0.229
0.908
0.229
0.229
0.908
0.229
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Relay
P/N
Part Protector
Type*
P/N
071-0429-09
071-0429-11
071-0429-00
071-0429-09
071-0429-11
071-0504-05
071-0504-02
071-0504-05
071-0504-02
071-0504-05
071-0504-02
071-0429-00
071-0429-09
071-0504-05
071-0504-02
071-0504-05
071-0504-02
071-0504-05
071-0504-02
071-0504-05
071-0504-05
071-0504-02
071-0504-05
* See Section F Introduction for more information.
Section_Fd.indd 12
3/4/2008 8:02:54 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
3DF4R15ML-TFD
3DF4S11M0-TFC
3DF4S11M0-TFD
3DF4S11ME-TFC
3DF4S11ME-TFD
3DF4S11ML-TFC
3DF4S11ML-TFD
3DF8A0750-TFC
3DF8A0750-TFD
3DF8A0751-TFD
3DF8A075E-TFC
3DF8A076E-TFD
3DF8R98KE-TFC
3DFTA075E-TFD
3DG3A0900-TFC
3DG3A0900-TFD
3DG3A0900-TFE
3DG3A090E-TFC
3DG3A090E-TFD
3DG3A090E-TFE
3DG3A090L-TFC
3DG3A090L-TFD
3DG3A090L-TFE
Max LRA
Volts PH RLA
460
208/230
460
208/230
460
208/230
460
208/230
460
460
208/230
460
208/230
460
208/230
460
575
208/230
460
575
208/230
460
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
23.6
38.6
18.6
42.6
20.4
42.6
20.4
30.7
15
15
30.7
15
30.7
15
35.7
15.6
15.7
35.7
15.6
15.7
35.7
15.6
15.7
138
240
115
240
115
240
115
161
83
83
161
83
161
83
215
106
84
215
106
84
215
106
84
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
0.908
0.255
1.02
0.255
1.02
0.255
1.02
0.385
1.54
1.54
0.385
1.54
0.385
1.54
0.295
1.178
1.835
0.295
1.178
1.835
0.295
1.178
1.835
* See Section F Introduction for more information.
Section_Fd.indd 13
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Relay
P/N
Part Protector
Type*
P/N
071-0504-02
071-0429-35
071-0429-33
071-0429-35
071-0429-33
071-0429-35
071-0429-33
071-0429-04
071-0429-09
071-0429-09
071-0429-04
071-0429-09
071-0429-04
071-0429-09
071-0429-00
071-0429-09
071-0429-11
071-0429-00
071-0429-09
071-0429-11
071-0429-00
071-0429-09
071-0429-11
FD13
3/4/2008 8:02:55 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
3DG3F40K0-TFC
3DG3F40K0-TFD
3DG3F40K0-TFE
3DG3F40KE-TFC
3DG3F40KE-TFD
3DG3F40KE-TFE
3DG3F40KL-TFC
3DG3F40KL-TFD
3DG3F40KL-TFE
3DGHA090E-TFC
3DGHA090E-TFD
3DGHA090E-TFE
3DGHA090L-TFC
3DGHA090L-TFD
3DGHA090L-TFE
3DGHF40KE-TFC
3DGHF40KE-TFD
3DGHF40KE-TFE
3DGHF40KL-TFC
3DGHF40KL-TFD
3DGHF40KL-TFE
3DH3A0600-TFC
3DH3A0600-TFD
FD14
Max LRA
Volts PH RLA
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
35.7
15.6
15.7
35.7
15.6
15.7
35.7
15.6
15.7
37
16.7
15.7
37
16.7
15.7
37
16.7
15.7
37
16.7
15.7
30.3
13.7
215
106
84
215
106
84
215
106
84
215
106
84
215
106
84
215
106
84
215
106
84
150
77
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
0.295
1.178
1.835
0.295
1.178
1.835
0.295
1.178
1.835
0.295
1.178
1.835
0.295
1.178
1.835
0.295
1.178
1.835
0.295
1.178
1.835
0.419
1.676
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Relay
P/N
Part Protector
Type*
P/N
071-0429-00
071-0429-09
071-0429-11
071-0429-00
071-0429-09
071-0429-11
071-0429-00
071-0429-09
071-0429-11
071-0429-00
071-0429-09
071-0429-11
071-0429-00
071-0429-09
071-0429-11
071-0429-00
071-0429-09
071-0429-11
071-0429-00
071-0429-09
071-0429-11
071-0429-08
071-0429-05
* See Section F Introduction for more information.
Section_Fd.indd 14
3/4/2008 8:02:55 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
3DH3A0600-TFE
3DH3A060E-TFC
3DH3A060E-TFD
3DH3A060E-TFE
3DH3A060L-TFC
3DH3A060L-TFD
3DH3A060L-TFE
3DH3F28K0-TFC
3DH3F28K0-TFD
3DH3F28K0-TFE
3DH3F28KE-TFC
3DH3F28KE-TFD
3DH3F28KE-TFE
3DH3F28KL-TFC
3DH3F28KL-TFD
3DH3F28KL-TFE
3DHHA060E-TFC
3DHHA060E-TFD
3DHHA060E-TFE
3DHHA060L-TFC
3DHHA060L-TFD
3DHHA060L-TFE
3DHHF28KE-TFC
Max LRA
Volts PH RLA
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
10.5
30.3
13.7
10.5
30.3
13.7
10.5
30.3
13.7
10.5
30.3
13.7
10.5
30.3
13.7
10.5
26.8
12
10.5
26.8
12
10.5
26.8
62
150
77
62
150
77
62
150
77
62
150
77
62
150
77
62
150
77
62
150
77
62
150
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
2.6
0.419
1.676
2.6
0.419
1.676
2.6
0.419
1.676
2.6
0.419
1.676
2.6
0.419
1.676
2.6
0.419
1.676
2.6
0.419
1.676
2.6
0.419
* See Section F Introduction for more information.
Section_Fd.indd 15
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Relay
P/N
Part Protector
Type*
P/N
071-0429-03
071-0429-08
071-0429-05
071-0429-03
071-0429-08
071-0429-05
071-0429-03
071-0429-08
071-0429-05
071-0429-03
071-0429-08
071-0429-05
071-0429-03
071-0429-08
071-0429-05
071-0429-03
071-0429-08
071-0429-05
071-0429-03
071-0429-08
071-0429-05
071-0429-03
071-0429-08
FD15
3/4/2008 8:02:55 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
3DHHF28KE-TFD
3DHHF28KE-TFE
3DHHF28KL-TFC
3DHHF28KL-TFD
3DHHF28KL-TFE
3DJ3A0750-TFC
3DJ3A0750-TFD
3DJ3A0750-TFE
3DJ3A075E-TFC
3DJ3A075E-TFD
3DJ3A075E-TFE
3DJ3A075L-TFC
3DJ3A075L-TFD
3DJ3A075L-TFE
3DJ3A0900-TFU
3DJ3F33K0-TFC
3DJ3F33K0-TFD
3DJ3F33K0-TFE
3DJ3F33KE-TFC
3DJ3F33KE-TFD
3DJ3F33KE-TFE
3DJ3F33KL-TFC
3DJ3F33KL-TFD
FD16
Max LRA
Volts PH RLA
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
200
208/230
460
575
208/230
460
575
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
12
10.5
26.8
12
10.5
30.7
14.3
11
30.7
14.3
11
30.7
14.3
11
34.6
30.7
14.3
11
30.7
14.3
11
30.7
14.3
77
62
150
77
62
161
83
67
161
83
67
161
83
67
196
161
83
67
161
83
67
161
83
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
1.676
2.6
0.419
1.676
2.6
0.385
1.54
2.508
0.385
1.54
2.508
0.385
1.54
2.508
0.294
0.385
1.54
2.508
0.385
1.54
2.508
0.385
1.54
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Relay
P/N
Part Protector
Type*
P/N
071-0429-05
071-0429-03
071-0429-08
071-0429-05
071-0429-03
071-0429-04
071-0429-09
071-0429-03
071-0429-04
071-0429-09
071-0429-03
071-0429-04
071-0429-09
071-0429-03
071-0429-20
071-0429-04
071-0429-09
071-0429-03
071-0429-04
071-0429-09
071-0429-03
071-0429-04
071-0429-09
* See Section F Introduction for more information.
Section_Fd.indd 16
3/4/2008 8:02:55 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
3DJ3F33KL-TFE
3DJHA075E-TFC
3DJHA075E-TFD
3DJHA075E-TFE
3DJHA075L-TFC
3DJHA075L-TFD
3DJHA075L-TFE
3DJHF33KE-TFC
3DJHF33KE-TFD
3DJHF33KE-TFE
3DJHF33KL-TFC
3DJHF33KL-TFD
3DJHF33KL-TFE
3DK3A0750-TFC
3DK3A0750-TFD
3DK3A0900-TFC
3DK3A0900-TFD
3DK3A0900-TFE
3DK3A1200-TFC
3DK3A1200-TFD
3DK3A120E-TFC
3DK3A120E-TFD
3DK3A120L-TFC
Max LRA
Volts PH RLA
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
208/230
460
575
208/230
460
208/230
460
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
11
30.7
15.7
11
30.7
15.7
11
30.7
15.7
11
30.7
15.7
11
30.7
15
39
16.9
16.4
48.1
23.6
48.1
23.6
48.1
67
161
83
67
161
83
67
161
83
67
161
83
67
161
83
215
106
84
275
138
275
138
275
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
2.508
0.385
1.54
2.508
0.385
1.54
2.508
0.385
1.54
2.508
0.385
1.54
2.508
0.385
1.54
0.295
1.178
1.835
0.229
0.908
0.229
0.908
0.229
* See Section F Introduction for more information.
Section_Fd.indd 17
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Relay
P/N
Part Protector
Type*
P/N
071-0429-03
071-0429-04
071-0429-09
071-0429-03
071-0429-04
071-0429-09
071-0429-03
071-0429-04
071-0429-09
071-0429-03
071-0429-04
071-0429-09
071-0429-03
071-0429-04
071-0429-09
071-0429-00
071-0429-09
071-0429-11
071-0504-05
071-0504-02
071-0504-05
071-0504-02
071-0504-05
FD17
3/4/2008 8:02:56 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
3DK3A120L-TFD
3DK3R15M0-TFC
3DK3R15M0-TFD
3DK3R15ME-TFC
3DK3R15ME-TFD
3DK3R15ML-TFC
3DK3R15ML-TFD
3DK4A1200-TFD
3DK4A120L-TFC
3DK4A120L-TFD
3DK4S11M0-TFC
3DK4S11M0-TFD
3DK4S11ML-TFC
3DK4S11ML-TFD
3DK8A0750-TFC
3DK8A0750-TFD
3DK8A075E-TFD
3DKAA120L-TFC
3DKAA120L-TFD
3DKHA120E-TFC
3DKHA120E-TFD
3DKHA120L-TFC
3DKHA120L-TFD
FD18
Max LRA
Volts PH RLA
460
208/230
460
208/230
460
208/230
460
460
208/230
460
208/230
460
208/230
460
208/230
460
460
208/230
460
208/230
460
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
23.6
48.1
23.6
48.1
23.6
48.1
23.6
23.6
48.1
23.6
38.6
18.6
38.6
18.6
30.7
15
15
48.1
23.6
48.1
23.6
48.1
23.6
138
275
138
275
138
275
138
138
275
138
240
115
240
115
161
83
83
275
138
275
138
275
138
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
0.908
0.229
0.908
0.229
0.908
0.229
0.908
0.908
0.229
0.908
0.255
1.02
0.255
1.02
0.385
1.54
1.54
0.229
0.908
0.229
0.908
0.229
0.908
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Relay
P/N
Part Protector
Type*
P/N
071-0504-02
071-0504-05
071-0504-02
071-0504-05
071-0504-02
071-0504-05
071-0504-02
071-0504-02
071-0504-05
071-0504-02
071-0429-35
071-0429-33
071-0429-35
071-0429-33
071-0429-04
071-0429-09
071-0429-09
071-0504-05
071-0504-02
071-0504-05
071-0504-02
071-0504-05
071-0504-02
* See Section F Introduction for more information.
Section_Fd.indd 18
3/4/2008 8:02:56 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
3DKHR15ME-TFC
3DKHR15ME-TFD
3DKHR15ML-TFC
3DKHR15ML-TFD
3DKHS11ME-TFC
3DKHS11ME-TFD
3DKHS11ML-TFC
3DKHS11ML-TFD
3DP3A0500-TFC
3DP3A0500-TFD
3DP3A0500-TFE
3DP3A0750-TFC
3DP3A0750-TFD
3DP3A0750-TFE
3DP3A075E-TFD
3DP3A0900-TFU
3DP3A1000-TFC
3DP3A1000-TFD
3DP3A1000-TFE
3DP3A100E-TFC
3DP3A100E-TFD
3DP3A100E-TFE
3DP3A100L-TFC
Max LRA
Volts PH RLA
208/230
460
208/230
460
208/230
460
208/230
460
208/230
460
575
208/230
460
575
460
200
208/230
460
575
208/230
460
575
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
48.1
23.6
48.1
23.6
42.6
20.4
42.6
20.4
18
10.1
7.5
31.4
16.1
11
16.1
36.8
43.6
20
16.5
43.6
20
16.5
43.6
275
138
275
138
240
115
240
115
115
58
43
161
83
67
83
196
215
106
84
215
106
84
215
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
0.229
0.908
0.229
0.908
0.255
1.02
0.255
1.02
0.603
2.412
3.794
0.385
1.54
2.508
1.54
0.294
0.295
1.178
1.835
0.295
1.178
1.835
0.295
* See Section F Introduction for more information.
Section_Fd.indd 19
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Relay
P/N
Part Protector
Type*
P/N
071-0504-05
071-0504-02
071-0504-05
071-0504-02
071-0429-35
071-0429-33
071-0429-35
071-0429-33
071-0429-02
071-0429-03
071-0429-19
071-0429-04
071-0429-09
071-0429-03
071-0429-09
071-0429-20
071-0429-06
071-0429-17
071-0429-11
071-0429-06
071-0429-17
071-0429-11
071-0429-06
FD19
3/4/2008 8:02:56 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
3DP3A100L-TFD
3DP3A100L-TFE
3DP3R12M0-TFC
3DP3R12M0-TFD
3DP3R12M0-TFE
3DP3R12ME-TFC
3DP3R12ME-TFD
3DP3R12ME-TFE
3DP3R12ML-TFC
3DP3R12ML-TFD
3DP3R12ML-TFE
3DPHA100E-TFC
3DPHA100E-TFD
3DPHA100E-TFE
3DPHA100L-TFC
3DPHA100L-TFD
3DPHA100L-TFE
3DPHR12ME-TFC
3DPHR12ME-TFD
3DPHR12ME-TFE
3DPHR12ML-TFC
3DPHR12ML-TFD
3DPHR12ML-TFE
FD20
Max LRA
Volts PH RLA
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
20
16.5
43.6
20
16.5
43.6
20
16.5
43.6
20
16.5
43.6
20
16.5
43.6
20
16.5
43.6
20
16.5
43.6
20
16.5
106
84
215
106
84
215
106
84
215
106
84
215
106
84
215
106
84
215
106
84
215
106
84
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
1.178
1.835
0.295
1.178
1.835
0.295
1.178
1.835
0.295
1.178
1.835
0.295
1.178
1.835
0.295
1.178
1.835
0.295
1.178
1.835
0.295
1.178
1.835
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Relay
P/N
Part Protector
Type*
P/N
071-0429-17
071-0429-11
071-0429-06
071-0429-17
071-0429-11
071-0429-06
071-0429-17
071-0429-11
071-0429-06
071-0429-17
071-0429-11
071-0429-06
071-0429-17
071-0429-11
071-0429-06
071-0429-17
071-0429-11
071-0429-06
071-0429-17
071-0429-11
071-0429-06
071-0429-17
071-0429-11
* See Section F Introduction for more information.
Section_Fd.indd 20
3/4/2008 8:02:56 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
3DR3A1000-TFC
3DR3A1000-TFD
3DR3A1000-TFE
3DR3A100E-TFC
3DR3A100E-TFD
3DR3A100E-TFE
3DR3A100L-TFC
3DR3A100L-TFD
3DR3A100L-TFE
3DR3F46K0-TFC
3DR3F46K0-TFD
3DR3F46K0-TFE
3DR3F46KE-TFC
3DR3F46KE-TFD
3DR3F46KL-TFC
3DR3F46KL-TFD
3DR3F46KL-TFE
3DRHA100E-TFC
3DRHA100E-TFD
3DRHA100E-TFE
3DRHA100L-TFC
3DRHA100L-TFD
3DRHA100L-TFE
Max LRA
Volts PH RLA
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
208/230
460
575
208/230
460
575
208/230
460
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
41.4
18.6
15.4
41.4
18.6
15.4
41.4
18.6
15.4
41.4
18.6
15.4
41.4
18.6
41.4
18.6
15.4
41.4
18.6
16.2
41.4
18.6
16.2
215
106
84
215
106
84
215
106
84
215
106
84
215
106
215
106
84
215
106
84
215
106
84
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
0.295
1.178
1.835
0.295
1.178
1.835
0.295
1.178
1.835
0.295
1.178
1.835
0.295
1.178
0.295
1.178
1.835
0.295
1.178
1.835
0.295
1.178
1.835
* See Section F Introduction for more information.
Section_Fd.indd 21
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Relay
P/N
Part Protector
Type*
P/N
071-0429-00
071-0429-09
071-0429-11
071-0429-00
071-0429-09
071-0429-11
071-0429-00
071-0429-09
071-0429-11
071-0429-00
071-0429-09
071-0429-11
071-0429-00
071-0429-09
071-0429-00
071-0429-09
071-0429-11
071-0429-00
071-0429-09
071-0429-11
071-0429-00
071-0429-09
071-0429-11
FD21
3/4/2008 8:02:57 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
3DRHF46KE-TFC
3DRHF46KE-TFD
3DRHF46KE-TFE
3DRHF46KL-TFC
3DRHF46KL-TFD
3DRHF46KL-TFE
3DS3A0750-TFC
3DS3A0750-TFD
3DS3A0750-TFE
3DS3A1000-TFC
3DS3A1000-TFD
3DS3A1000-TFE
3DS3A100E-TFC
3DS3A100E-TFD
3DS3A100E-TFE
3DS3A100L-TFC
3DS3A100L-TFD
3DS3A100L-TFE
3DS3A1500-TFC
3DS3A1500-TFD
3DS3A1500-TFE
3DS3A150E-TFC
3DS3A150E-TFD
FD22
Max LRA
Volts PH RLA
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
41.4
18.6
16.2
41.4
18.6
16.2
32
16.4
11.5
42
18.6
16.8
42
18.6
16.8
42
18.6
16.8
59.6
29
23.6
59.6
29
215
106
84
215
106
84
161
83
67
215
106
84
215
106
84
215
106
84
275
138
110
275
138
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
0.295
1.178
1.835
0.295
1.178
1.835
0.385
1.54
2.508
0.295
1.178
1.835
0.295
1.178
1.835
0.295
1.178
1.835
0.229
0.908
1.433
0.229
0.908
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Relay
P/N
Part Protector
Type*
P/N
071-0429-00
071-0429-09
071-0429-11
071-0429-00
071-0429-09
071-0429-11
071-0429-04
071-0429-09
071-0429-03
071-0429-00
071-0429-09
071-0429-11
071-0429-00
071-0429-09
071-0429-11
071-0429-00
071-0429-09
071-0429-11
071-0504-04
071-0504-00
071-0504-01
071-0504-04
071-0504-00
* See Section F Introduction for more information.
Section_Fd.indd 22
3/4/2008 8:02:57 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
3DS3A150E-TFE
3DS3A150L-TFC
3DS3A150L-TFD
3DS3A150L-TFE
3DS3F30K0-TFC
3DS3F30K0-TFD
3DS3F46K0-TFC
3DS3F46K0-TFD
3DS3F46K0-TFE
3DS3F46KE-TFC
3DS3F46KE-TFD
3DS3F46KE-TFE
3DS3F46KL-TFC
3DS3F46KL-TFD
3DS3F46KL-TFE
3DS3R17M0-TFC
3DS3R17M0-TFD
3DS3R17M0-TFE
3DS3R17ME-TFC
3DS3R17ME-TFD
3DS3R17ME-TFE
3DS3R17ML-TFC
3DS3R17ML-TFD
Max LRA
Volts PH RLA
575
208/230
460
575
208/230
460
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
23.6
59.6
29
23.6
32
16.4
42
18.6
16.8
42
18.6
16.8
42
18.6
16.8
59.6
29
23.6
59.6
29
23.6
59.6
29
110
275
138
110
161
83
215
106
84
215
106
84
215
106
84
275
138
110
275
138
110
275
138
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
1.433
0.229
0.908
1.433
0.385
1.54
0.295
1.178
1.835
0.295
1.178
1.835
0.295
1.178
1.835
0.229
0.908
1.433
0.229
0.908
1.433
0.229
0.908
* See Section F Introduction for more information.
Section_Fd.indd 23
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Relay
P/N
Part Protector
Type*
P/N
071-0504-01
071-0504-04
071-0504-00
071-0504-01
071-0429-04
071-0429-09
071-0429-00
071-0429-09
071-0429-11
071-0429-00
071-0429-09
071-0429-11
071-0429-00
071-0429-09
071-0429-11
071-0504-04
071-0504-00
071-0504-01
071-0504-04
071-0504-00
071-0504-01
071-0504-04
071-0504-00
FD23
3/4/2008 8:02:57 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
3DS3R17ML-TFE
3DS4A0750-TFC
3DS4A0750-TFD
3DS4A1000-TFC
3DS4A1000-TFD
3DS4A1500-TFC
3DS4A1500-TFD
3DS4A1500-TFE
3DS4S12M0-TFC
3DS4S12M0-TFD
3DS4S12ME-TFC
3DS4S12ME-TFD
3DS4S12ML-TFC
3DS4S12ML-TFD
3DS8A0750-TFD
3DS8A0751-TFD
3DS8A076E-TFD
3DS8A1000-TFC
3DS8A100E-TFC
3DS8F30K1-TFD
3DS8R11ME-TFD
3DSTA075E-TFC
3DSTA075E-TFD
FD24
Max LRA
Volts PH RLA
575
208/230
460
208/230
460
208/230
460
575
208/230
460
208/230
460
208/230
460
460
460
460
208/230
208/230
460
460
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
23.6
32
16.4
42
18.6
59.6
29
23.6
41.9
21.3
47.1
22.8
47.1
22.8
16.4
16.4
16.4
42
42
16.4
16.4
32
16.4
110
161
83
215
106
275
138
110
280
136
280
136
280
136
83
83
83
215
215
83
83
161
83
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
1.433
0.385
1.54
0.295
1.178
0.229
0.908
1.433
0.22
0.823
0.22
0.823
0.22
0.823
1.54
1.54
1.54
0.295
0.295
1.54
1.54
0.385
1.54
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Relay
P/N
Part Protector
Type*
P/N
071-0504-01
071-0429-04
071-0429-09
071-0429-00
071-0429-09
071-0504-04
071-0504-00
071-0504-01
071-0504-08
071-0429-34
071-0504-08
071-0429-34
071-0504-08
071-0429-34
071-0429-09
071-0429-09
071-0429-09
071-0429-00
071-0429-00
071-0429-09
071-0429-09
071-0429-04
071-0429-09
* See Section F Introduction for more information.
Section_Fd.indd 24
3/4/2008 8:02:57 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
3DSTR11ME-TFD
3DT3A0750-TFC
3DT3A0750-TFD
3DT3A0750-TFE
3DT3A1000-TFC
3DT3A1000-TFD
3DT3A1000-TFE
3DT3A1500-TFC
3DT3A1500-TFD
3DT3A1500-TFE
3DT3A150E-TFC
3DT3A150E-TFD
3DT3A150E-TFE
3DT3A150L-TFC
3DT3A150L-TFD
3DT3A150L-TFE
3DT3R11M0-TFC
3DT3R11M0-TFD
3DT3R11M0-TFE
3DT3R17M0-TFC
3DT3R17M0-TFD
3DT3R17M0-TFE
3DT3R17ME-TFC
Max LRA
Volts PH RLA
460
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
16.4
32
16.4
11.5
42
18.6
16.8
59.6
29
23.6
59.6
29
23.6
59.6
29
23.6
42
18.6
16.8
59.6
29
23.6
59.6
83
161
83
67
215
106
84
275
138
110
275
138
110
275
138
110
215
106
84
275
138
110
275
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
1.54
0.385
1.54
2.508
0.295
1.178
1.835
0.229
0.908
1.433
0.229
0.908
1.433
0.229
0.908
1.433
0.295
1.178
1.835
0.229
0.908
1.433
0.229
* See Section F Introduction for more information.
Section_Fd.indd 25
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Relay
P/N
Part Protector
Type*
P/N
071-0429-09
071-0429-04
071-0429-09
071-0429-03
071-0429-00
071-0429-09
071-0429-11
071-0504-04
071-0504-00
071-0504-01
071-0504-04
071-0504-00
071-0504-01
071-0504-04
071-0504-00
071-0504-01
071-0429-00
071-0429-09
071-0429-11
071-0504-04
071-0504-00
071-0504-01
071-0504-04
FD25
3/4/2008 8:02:58 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
3DT3R17ME-TFD
3DT3R17ME-TFE
3DT3R17ML-TFC
3DT3R17ML-TFD
3DT3R17ML-TFE
3DT4S12M0-TFC
3DT4S12M0-TFD
3DT4S12ML-TFC
3DT4S12ML-TFD
3DT8A0750-TFD
3DT8A075E-TFD
3DT8R11ME-TFD
3DTHA100E-TFD
3DTHA150E-TFC
3DTHA150E-TFD
3DTHA150E-TFE
3DTHA150L-TFC
3DTHA150L-TFD
3DTHA150L-TFE
3DTHR11ME-TFD
3DTHR17ME-TFC
3DTHR17ME-TFD
3DTHR17ME-TFE
FD26
Max LRA
Volts PH RLA
460
575
208/230
460
575
208/230
460
208/230
460
460
460
460
460
208/230
460
575
208/230
460
575
460
208/230
460
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
29
23.6
59.6
29
23.6
41.9
21.3
41.9
21.3
16.4
16.4
16.4
18.6
59.6
29
23.6
59.6
29
23.6
18.6
59.6
29
23.6
138
110
275
138
110
280
136
280
136
83
83
83
106
275
138
110
275
138
110
106
275
138
110
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
0.908
1.433
0.229
0.908
1.433
0.22
0.823
0.22
0.823
1.54
1.54
1.54
1.178
0.229
0.908
1.433
0.229
0.908
1.433
1.178
0.229
0.908
1.433
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Relay
P/N
Part Protector
Type*
P/N
071-0504-00
071-0504-01
071-0504-04
071-0504-00
071-0504-01
071-0504-08
071-0429-34
071-0504-08
071-0429-34
071-0429-09
071-0429-09
071-0429-09
071-0429-09
071-0504-04
071-0504-00
071-0504-01
071-0504-04
071-0504-00
071-0504-01
071-0429-09
071-0504-04
071-0504-00
071-0504-01
* See Section F Introduction for more information.
Section_Fd.indd 26
3/4/2008 8:02:58 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
3DTHR17ML-TFC
3DTHR17ML-TFD
3DTHR17ML-TFE
3DTHS12ME-TFC
3DTHS12ME-TFD
3DTHS12ML-TFC
3DTHS12ML-TFD
3RA1-0310-TAC
3RA1-0310-TAD
3RA1-0310-TAU
3RA1-0311-TAC
3RA1-0311-TAD
3RA1-031A-TAC
3RA1-031A-TAD
3RA1-031L-TAC
3RA1-031L-TAD
3RA2-0310-CAB
3RA2-031A-CAB
3RA2-031L-CAB
3RAA-0310-TAU
3RAA-031E-TAC
3RAA-031E-TAD
3RAA-031L-TAC
Max LRA
Volts PH RLA
208/230
460
575
208/230
460
208/230
460
208/230
460
200
208/230
460
208/230
460
208/230
460
230
230
230
200
208/230
460
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
1
1
1
3
3
3
3
59.6
29
23.6
47.1
22.8
47.1
22.8
NA
NA
11.4
14.1
6.3
14.1
6.3
13.1
6.6
NA
NA
17.8
13.1
14.1
6.3
14.1
275
138
110
280
136
280
136
82
41
82
82
41
82
41
82
41
86
86
86
82
82
41
82
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
0.229
0.908
1.433
0.22
0.823
0.22
0.823
0.9
3.6
0.944
0.837
3.309
0.837
3.309
0.9
3.6
2.54
2.54
2.54
0.9
0.837
3.309
0.837
* See Section F Introduction for more information.
Section_Fd.indd 27
0
0
0
0
0
0
0
0.47
1.9
0.444
0.42
1.653
0.42
1.653
0.47
1.9
0.61
0.61
0.61
0.47
0.42
1.653
0.42
Relay
P/N
014-0036-22 014-0064-14 040-0166-28
014-0036-22 014-0064-14 040-0166-28
014-0036-22 014-0064-14 040-0166-28
Part Protector
Type*
P/N
RP
RP
RP
071-0504-04
071-0504-00
071-0504-01
071-0504-08
071-0429-34
071-0504-08
071-0429-34
071-0090-17
071-0090-22
071-0090-32
071-0090-32
071-0090-22
071-0090-32
071-0090-22
071-0090-17
071-0090-22
071-0119-02
071-0119-02
071-0119-02
071-0090-17
071-0090-32
071-0090-22
071-0090-32
FD27
3/4/2008 8:02:58 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
3RAA-031L-TAD
3RK1-0300-TAE
3RK1-0310-TAC
3RK1-0310-TAD
3RK1-031A-TAC
3RK1-031A-TAD
3RK2-0310-CAB
3RK2-031A-CAB
3RKA-031E-FXX
9RA1-0505-TFC
9RA1-0505-TFD
9RA1-0505-TFE
9RA1-0506-CFB
9RA1-050A-CFB
9RA1-050A-TFC
9RA1-050A-TFD
9RB1-0505-TFC
9RB1-0505-TFD
9RB1-0505-TFE
9RB1-050A-TFC
9RB1-050A-TFD
9RB1-0765-TFC
9RB1-0765-TFD
FD28
Max LRA
Volts PH RLA
460
575
208/230
460
208/230
460
230
230
55
208/230
460
575
230
230
208/230
460
208/230
460
575
208/230
460
208/230
460
3
3
3
3
3
3
1
1
3
3
3
3
1
1
3
3
3
3
3
3
3
3
3
6.3
5.1
11.8
5.2
11.8
5.2
19.6
19.6
NA
16.7
8.6
7.8
26.9
26.9
16.7
8.6
15.9
7.9
7.8
15.9
7.9
32.1
15.4
41
30
82
41
82
41
86
86
320
115
53
42
125
125
115
53
115
53
42
115
53
164
82
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
3.309
5.4
0.9
3.6
0.9
3.6
2.54
2.54
0.17
0.519
2.08
3.17
1.4
1.4
0.519
2.08
0.519
2.08
3.17
0.519
2.08
0.338
1.351
1.653
2.7
0.47
1.9
0.47
1.9
0.61
0.61
0
0.26
1.015
1.585
0.37
0.37
0.26
1.015
0.26
1.015
1.585
0.26
1.015
0.169
0.675
Relay
P/N
014-0036-22 014-0064-14 040-0166-28
014-0036-22 014-0064-14 040-0166-28
014-0006-14 014-0064-18 040-0166-23
014-0006-14 014-0064-18 040-0166-23
Part Protector
Type*
P/N
RP
RP
RP
RP
071-0090-22
071-0090-16
071-0090-02
071-0090-03
071-0090-02
071-0090-03
071-0119-00
071-0119-00
071-0086-09
071-0086-17
071-0086-29
071-0476-01
071-0476-01
071-0086-09
071-0086-17
071-0086-09
071-0086-17
071-0086-29
071-0086-09
071-0086-17
071-0086-22
071-0086-20
* See Section F Introduction for more information.
Section_Fd.indd 28
3/4/2008 8:02:59 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
9RB1-0765-TFE
9RB1-0765-TFU
9RB1-076A-TFC
9RB1-076A-TFD
9RB1-076L-TFC
9RB1-076L-TFD
9RB2-0765-TFC
9RB2-0765-TFD
9RB2-0765-TFE
9RB2-076A-TFC
9RB4-0505-TFC
9RB4-0505-TFD
9RB6-0505-TFC
9RC1-0765-TFC
9RC1-0765-TFD
9RC1-0765-TFE
9RC1-0765-TFU
9RC1-076A-TFC
9RC1-076A-TFD
9RC1-1015-TF7
9RC1-1015-TFC
9RC1-1015-TFD
9RC1-1015-TFE
Max LRA
Volts PH RLA
575
200
208/230
460
208/230
460
208/230
460
575
208/230
208/230
460
208/230
208/230
460
575
200
208/230
460
380
208/230
460
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
14
NA
32.1
15.4
32.1
15.4
32.1
15.4
14
32.1
15.9
7.9
15.9
32.9
15.8
14
NA
32.9
15.8
NA
44
20
17.5
63.8
141
164
82
164
82
164
82
63.8
164
115
53
115
164
82
63.8
141
164
82
110
208
110
88.2
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
2.16
0.3
0.338
1.351
0.338
1.351
0.338
1.351
2.16
0.338
0.519
2.08
0.519
0.338
1.351
2.16
0.3
0.338
1.351
0.878
0.219
0.878
1.48
* See Section F Introduction for more information.
Section_Fd.indd 29
1.08
0.151
0.169
0.675
0.169
0.675
0.169
0.675
1.08
0.169
0.26
1.015
0.26
0.169
0.675
1.08
0.151
0.169
0.675
0
0
0
0
Relay
P/N
Part Protector
Type*
P/N
071-0086-40
071-0086-43
071-0086-22
071-0086-20
071-0086-22
071-0086-20
071-0086-22
071-0086-20
071-0086-40
071-0086-22
071-0086-09
071-0086-17
071-0086-09
071-0086-22
071-0086-20
071-0086-40
071-0086-43
071-0086-22
071-0086-20
071-0429-17
071-0504-06
071-0429-17
071-0429-11
FD29
3/4/2008 8:02:59 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
9RC1-101A-TFC
9RC1-101A-TFD
9RC3-1015-TFD
9RC3-1015-TFE
9RC3-101L-TFD
9RJ1-0505-TFC
9RJ1-0505-TFD
9RJ1-0505-TFE
9RJ1-050A-TFC
9RJ1-0765-TFC
9RJ1-0765-TFD
9RJ1-0765-TFE
9RJ1-076A-TFC
9RJ1-076A-TFD
9RJ1-076L-TFC
9RJ1-076L-TFD
9RJ2-0765-TFC
9RJ2-0765-TFE
9RP2-0765-TFC
9RP2-0765-TFD
9RP2-0765-TFE
9RP2-1015-TFC
9RP2-1015-TFD
FD30
Max LRA
Volts PH RLA
208/230
460
460
575
460
208/230
460
575
208/230
208/230
460
575
208/230
460
208/230
460
208/230
575
208/230
460
575
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
44
20
20
17.5
20
15.9
7.9
7.8
15.9
31.7
14.7
10.7
31.7
14.7
31.7
14.7
31.7
10.7
32.9
14.1
14
44
20
208
110
110
88.2
110
115
53
42
115
164
82
63.8
164
82
164
82
164
63.8
164
82
63.8
208
110
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
0.219
0.878
0.878
1.48
0.878
0.519
2.08
3.17
0.519
0.338
1.351
2.16
0.338
1.351
0.338
1.351
0.338
2.16
0.338
1.351
2.16
0.219
0.878
0
0
0
0
0
0.26
1.015
1.585
0.26
0.169
0.675
1.08
0.169
0.675
0.169
0.675
0.169
1.08
0.169
0.675
1.08
0
0
Relay
P/N
Part Protector
Type*
P/N
071-0504-06
071-0429-17
071-0429-17
071-0429-11
071-0429-17
071-0086-09
071-0086-17
071-0086-29
071-0086-09
071-0086-21
071-0086-20
071-0086-40
071-0086-21
071-0086-20
071-0086-21
071-0086-20
071-0086-21
071-0086-40
071-0086-22
071-0086-20
071-0086-40
071-0504-06
071-0429-17
* See Section F Introduction for more information.
Section_Fd.indd 30
3/4/2008 8:02:59 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
9RP2-1015-TFE
9RP2-101A-TFC
9RP3-1015-TFD
9RP3-1015-TFE
9RS1-1015-TSU
9RS1-1505-TF7
9RS1-1505-TFD
9RS1-1505-TFE
9RS1-1505-TSC
9RS1-150A-TFD
9RS1-150A-TSC
9RS2-0765-TFC
9RS2-0765-TFD
9RS2-0765-TFE
9RS2-076A-TFC
9RS2-076A-TFD
9RS2-1015-TFD
9RS3-0765-TFC
9RS3-0765-TFD
9RS3-0765-TFE
9RS3-076A-TFC
9RS3-076A-TFD
9RS3-1015-TFC
Max LRA
Volts PH RLA
575
208/230
460
575
200
380
460
575
208/230
460
208/230
208/230
460
575
208/230
460
460
208/230
460
575
208/230
460
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
17.5
44
20
17.5
NA
NA
28.5
22.5
56.4
28.5
56.4
29.4
16.5
14
29.4
16.5
19
29.4
16.5
14
29.4
16.5
41
88.2
208
110
88.2
203
144
144
127
284
144
284
164
82
63.8
164
82
110
164
82
63.8
164
82
208
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
1.48
0.219
0.878
1.48
0.204
0.908
0.908
1.036
0.229
0.908
0.229
0.338
1.351
2.16
0.338
1.351
0.878
0.338
1.351
2.16
0.338
1.351
0.219
* See Section F Introduction for more information.
Section_Fd.indd 31
0
0
0
0
0
0
0
0
0
0
0
0.169
0.675
1.08
0.169
0.675
0
0.169
0.675
1.08
0.169
0.675
0
Relay
P/N
Part Protector
Type*
P/N
071-0429-11
071-0504-06
071-0429-17
071-0429-11
071-0581-02
071-0504-00
071-0504-00
071-0504-01
071-0581-02
071-0504-00
071-0581-02
071-0086-23
071-0086-20
071-0086-26
071-0086-23
071-0086-20
071-0429-17
071-0086-23
071-0086-20
071-0086-26
071-0086-23
071-0086-20
071-0504-06
FD31
3/4/2008 8:02:59 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
9RS3-1015-TFD
9RS3-1015-TFE
9RS3-1015-TSU
9RS5-0765-TFC
9RS7-0765-TFC
9RS7-0765-TFD
9RSB-076A-TFC
9RSC-0765-TFC
9RSC-0765-TFD
9RSD-0765-TFC
9RSD-0765-TFD
9RT1-1505-TFD
9RT1-1505-TFE
9RT1-1505-TSC
9RT1-150A-TFD
9RZ1-0765-TFU
9TH1-1015-TFC
9TH1-1015-TFD
9TH1-101A-TFC
9TH1-101A-TFD
9TH2-101E-TFC
9TH2-101E-TFD
9TK1-0505-TFC
FD32
Max LRA
Volts PH RLA
460
575
200
208/230
208/230
460
208/230
208/230
460
208/230
460
460
575
208/230
460
200
208/230
460
208/230
460
208/230
460
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
19 110
15.5 88.2
NA 203
29.4 164
29.4 164
16.5
82
29.4 164
29.4 164
16.5
82
29.4 164
16.5
82
28.5 144
22.5 127
56.4 284
28.5 144
NA 141
37.4 208
17.5 110
37.4 208
17.5 110
40.7 220
17.9 110
19.6 115
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
0.878
1.48
0.204
0.338
0.338
1.351
0.338
0.338
1.351
0.338
1.351
0.908
1.036
0.229
0.908
0.3
0.219
0.878
0.219
0.878
0.219
0.878
0.519
0
0
0
0.169
0.169
0.675
0.169
0.169
0.675
0.169
0.675
0
0
0
0
0.151
0
0
0
0
0
0
0.26
Relay
P/N
Part Protector
Type*
P/N
071-0429-17
071-0429-11
071-0581-02
071-0086-23
071-0086-23
071-0086-20
071-0086-23
071-0086-23
071-0086-20
071-0086-23
071-0086-20
071-0504-00
071-0504-01
071-0581-02
071-0504-00
071-0086-43
071-0504-06
071-0429-17
071-0504-06
071-0429-17
071-0504-06
071-0429-17
071-0086-38
* See Section F Introduction for more information.
Section_Fd.indd 32
3/4/2008 8:03:00 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
9TK1-0505-TFD
9TK1-0505-TFE
9TK1-050A-TFC
9TK1-050A-TFD
9TK2-050E-TFC
9TK2-050E-TFD
9TL1-0765-TFC
9TL1-0765-TFE
9TL1-076A-TFC
9TL1-076A-TFD
9TL2-076E-TFC
9TL2-076E-TFD
ERA1-0200-TAC
ERA1-0200-TAD
ERA1-0200-TAE
ERA1-020A-TAD
ERA2-0200-CAB
ERA2-020A-CAB
ERC1-0200-TAC
ERC1-0200-TAD
ERC1-0200-TAE
ERC1-020L-TAC
ERC1-020L-TAD
Max LRA
Volts PH RLA
460
575
208/230
460
208/230
460
208/230
575
208/230
460
208/230
460
208/230
460
575
460
230
230
208/230
460
575
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
1
1
3
3
3
3
3
8.3
53
7.8
42
19.6 115
8.3
53
20.3 115
8.3
53
30 164
9.7 63.8
30 164
14.5
82
28.9 164
13.1
82
6.6
46
3.5
23
3.5
20
3.5
23
10.4
58
10.4
58
6.8
46
3.6
23
NA
20
6.8
46
3.6
23
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
2.08
3.17
0.519
2.08
0.519
2.08
0.338
2.16
0.338
1.351
0.338
1.351
1.675
6.692
9.3
6.692
2.7
2.7
1.675
6.692
9.3
1.675
6.692
* See Section F Introduction for more information.
Section_Fd.indd 33
1.015
1.585
0.26
1.015
0.26
1.015
0.169
1.08
0.169
0.675
0.169
0.675
0.84
3.346
4.905
3.346
1.125
1.125
0.84
3.346
4.905
0.84
3.346
Relay
P/N
014-0036-22 014-0064-11 040-0166-20
014-0036-22 014-0064-11 040-0166-20
Part Protector
Type*
P/N
RP
RP
071-0086-17
071-0086-29
071-0086-38
071-0086-17
071-0086-38
071-0429-31
071-0086-22
071-0086-40
071-0086-22
071-0086-20
071-0086-22
071-0086-20
071-0090-00
071-0090-08
071-0090-15
071-0090-08
071-0103-02
071-0103-02
071-0090-00
071-0090-08
071-0090-15
071-0090-00
071-0090-08
FD33
3/4/2008 8:03:00 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
ERC2-0200-CAB
ERC2-020A-CAB
ERC2-020L-CAB
ERCA-020A-TAC
ERCA-020E-TAD
ERCA-020E-TAE
ERCA-020L-TAD
ERCA-020L-TAE
ERCA-021E-TAC
ERCA-021L-TAC
ERF1-0300-TAE
ERF1-0310-FXX
ERF1-0310-TAC
ERF1-0310-TAD
ERF1-0311-TAC
ERF1-0311-TAD
ERF1-031L-TAC
ERF1-031L-TAD
ERF2-0310-CAB
ERF2-031L-CAB
ERFA-0311-TAD
ERFA-031E-TAC
ERFA-031E-TAD
FD34
Max LRA
Volts PH RLA
230
230
230
208/230
460
575
460
575
208/230
208/230
575
55
208/230
460
208/230
460
208/230
460
230
230
460
208/230
460
1
1
1
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
1
1
3
3
3
10.9
10.9
10.9
6.8
3.5
3.1
3.5
3.1
8.8
8.8
5.2
NA
11.7
6.4
12.4
5.8
11.7
6.4
18.3
18.3
5.8
12.4
5.8
58
58
58
46
23
20
23
20
46
46
30
320
82
41
82
41
82
41
86
86
41
82
41
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
2.7
2.7
2.7
1.675
6.692
9.3
6.692
9.3
1.675
1.675
5.4
0.17
0.9
3.6
0.837
3.309
0.9
3.6
2.54
2.54
3.309
0.837
3.309
1.125
1.125
1.125
0.84
3.346
4.905
3.346
4.905
0.84
0.84
2.7
0
0.47
1.9
0.42
1.653
0.47
1.9
0.61
0.61
1.653
0.42
1.653
Relay
P/N
014-0036-22 014-0064-11 040-0166-20
014-0036-22 014-0064-11 040-0166-20
014-0036-22 014-0064-11 040-0166-20
014-0036-22 014-0064-14 040-0166-28
014-0036-22 014-0064-14 040-0166-28
Part Protector
Type*
P/N
RP
RP
RP
RP
RP
071-0099-01
071-0099-01
071-0099-01
071-0090-00
071-0090-08
071-0090-15
071-0090-08
071-0090-15
071-0090-49
071-0090-49
071-0090-16
071-0090-02
071-0090-10
071-0090-36
071-0090-10
071-0090-02
071-0090-10
071-0119-00
071-0119-00
071-0090-10
071-0090-36
071-0090-10
* See Section F Introduction for more information.
Section_Fd.indd 34
3/4/2008 8:03:00 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
ERFA-031E-TAE
ERFA-031L-TAC
ERFA-031L-TAD
ERFB-031E-CAB
ERFB-031L-CAB
ERJ1-0200-TAC
ERJ1-0200-TAD
ERJ1-0200-TAE
ERJ1-020A-TAC
ERJ1-020A-TAD
ERJ2-0200-CAB
ERJ2-0200-CAH
ERJ2-020A-CAB
MRA2-0500-TFC
MRA2-0500-TFD
MRA2-0500-TFE
MRA2-0500-TFU
MRA2-0506-CFB
MRA2-050A-CFB
MRA2-050A-TFC
MRA2-050A-TFD
MRA2-050L-TFC
MRA2-050L-TFD
Max LRA
Volts PH RLA
575
208/230
460
230
230
208/230
460
575
208/230
460
230
208
230
208/230
460
575
200
230
230
208/230
460
208/230
460
3
3
3
1
1
3
3
3
3
3
1
1
1
3
3
3
3
1
1
3
3
3
3
5.2
30
12.4
82
5.8
41
17
86
17
86
6.3
46
3.4
23
3.5
20
6.3
46
3.4
23
10.1
58
13.4 57.2
10.1
58
NA 115
NA
53
NA
42
NA 110
NA 125
27.5 125
22 115
8.6
53
22 115
8.6
53
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
5.4
0.837
3.309
2.41
2.41
1.675
6.692
9.3
1.675
6.692
2.7
2.836
2.7
0.519
2.08
3.17
0.415
1.4
1.4
0.519
2.08
0.519
2.08
* See Section F Introduction for more information.
Section_Fd.indd 35
2.7
0.42
1.653
0.595
0.595
0.84
3.346
4.905
0.84
3.346
1.125
0.74
1.125
0.26
1.015
1.585
0.207
0.37
0.37
0.26
1.015
0.26
1.015
Relay
P/N
Part Protector
Type*
P/N
014-0036-22 014-0064-14 040-0166-28
014-0036-22 014-0064-14 040-0166-28
RP
RP
014-0036-22 014-0064-11 040-0166-20
014-0036-22 014-0064-11 040-0166-20
014-0036-22 014-0064-11 040-0166-20
RP
RP
RP
014-0006-14 014-0064-18 040-0166-23
014-0006-14 014-0064-18 040-0166-23
RP
RP
071-0090-16
071-0090-36
071-0090-10
071-0119-00
071-0119-00
071-0090-00
071-0090-08
071-0090-15
071-0090-00
071-0090-08
071-0103-02
071-0099-02
071-0103-02
071-0086-38
071-0086-17
071-0086-29
071-0086-42
071-0476-01
071-0476-01
071-0086-38
071-0086-17
071-0086-38
071-0086-17
FD35
3/4/2008 8:03:00 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
MRA8-0500-TFC
MRA8-0500-TFD
MRB1-0500-TFC
MRB1-0500-TFD
MRB1-0500-TFE
MRB1-050A-TFC
MRB1-050A-TFD
MRC1-0500-TFC
MRC1-0500-TFD
MRC8-0500-TFC
MRC8-0500-TFD
MRF2-0500-TFC
MRF2-0500-TFD
MRF2-0500-TFE
MRF2-0506-CFB
MRF2-050A-CFB
MRF2-050A-TFC
MRF2-050A-TFD
MRF8-0500-TFC
MRH4-0760-FSC
MRH4-0760-TF7
MRH4-0760-TFC
MRH4-0760-TFD
FD36
Max LRA
Volts PH RLA
208/230
460
208/230
460
575
208/230
460
208/230
460
208/230
460
208/230
460
575
230
230
208/230
460
208/230
230
380
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
1
1
3
3
3
3
3
3
3
NA
NA
21.2
12.1
NA
21.2
12.1
18.4
9.2
18.4
9.2
21
8.6
7.8
25.2
25.2
21
8.6
21
NA
NA
NA
NA
115
53
115
53
42
115
53
115
53
115
53
115
53
42
125
125
115
53
115
130
82
164
82
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
0.519
2.08
0.519
2.08
3.17
0.519
2.08
0.519
2.08
0.519
2.08
0.519
2.08
3.17
1.4
1.4
0.519
2.08
0.519
0.82
1.208
0.338
1.351
0.26
1.015
0.26
1.015
1.585
0.26
1.015
0.26
1.015
0.26
1.015
0.26
1.015
1.585
0.37
0.37
0.26
1.015
0.26
0.41
0.604
0.169
0.675
Relay
P/N
014-0006-14 014-0064-18 040-0166-23
014-0006-14 014-0064-18 040-0166-23
Part Protector
Type*
P/N
RP
RP
071-0086-38
071-0086-17
071-0086-38
071-0086-35
071-0086-36
071-0086-38
071-0086-35
071-0086-38
071-0086-35
071-0086-38
071-0086-35
071-0086-38
071-0086-17
071-0086-29
071-0476-01
071-0476-01
071-0086-38
071-0086-17
071-0086-38
071-0581-02
071-0086-20
071-0086-21
071-0086-20
* See Section F Introduction for more information.
Section_Fd.indd 36
3/4/2008 8:03:01 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
MRH4-0760-TFE
MRH4-076A-TFC
MRH4-076A-TFD
MRH4-076L-TFC
MRH4-076L-TFD
MRJ1-0500-TFU
NRA2-0310-TFU
NRA2-0500-TF7
NRA2-0500-TFC
NRA2-0500-TFD
NRA2-0500-TFE
NRA2-050A-TFC
NRA2-050A-TFD
NRA3-0500-TFC
NRA3-0500-TFD
NRA3-050L-TFC
NRA3-050L-TFD
NRB2-0310-TFC
NRB2-0310-TFD
NRB2-031A-TFC
NRB2-031A-TFD
NRB2-0400-TFC
NRB2-0400-TFD
Max LRA
Volts PH RLA
575
208/230
460
208/230
460
200
200
380
208/230
460
575
208/230
460
208/230
460
208/230
460
208/230
460
208/230
460
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
NA
30.3
13.5
30.3
13.5
NA
NA
NA
NA
NA
NA
19.2
9.6
NA
NA
19.2
9.6
12.9
6.4
12.9
6.4
21.9
11.3
63.8
164
82
164
82
110
79.6
62.5
141
62.5
53.4
141
62.5
141
62.5
141
62.5
82
41
82
41
141
62.5
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
2.16
0.338
1.351
0.338
1.351
0.415
0.721
2.14
0.546
2.14
3.23
0.546
2.14
0.546
2.14
0.546
2.14
0.9
3.6
0.9
3.6
0.514
1.987
* See Section F Introduction for more information.
Section_Fd.indd 37
1.08
0.169
0.675
0.169
0.675
0.207
0.384
1.07
0.273
1.07
1.615
0.273
1.07
0.273
1.07
0.273
1.07
0.47
1.9
0.47
1.9
0.257
0.99
Relay
P/N
Part Protector
Type*
P/N
071-0086-40
071-0086-21
071-0086-20
071-0086-21
071-0086-20
071-0086-42
071-0086-41
071-0086-14
071-0086-39
071-0086-14
071-0086-17
071-0086-39
071-0086-14
071-0086-39
071-0086-14
071-0086-39
071-0086-14
071-0086-11
071-0086-37
071-0086-11
071-0086-37
071-0086-39
071-0086-14
FD37
3/4/2008 8:03:01 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
NRB2-0400-TFE
NRB2-040A-TFC
NRB2-040A-TFD
NRB2-040E-TFC
NRB2-040E-TFD
NRB2-040L-TFC
NRB2-040L-TFD
NRB3-0400-TFC
NRB3-0400-TFD
NRB3-040L-TFC
NRB3-040L-TFD
NRD1-0310-TFC
NRD1-0310-TFD
NRD1-0310-TFU
NRD1-031A-TFC
NRD1-031A-TFD
NRD1-032E-TFC
NRD1-032E-TFD
NRD1-032L-TFC
NRD1-032L-TFD
NRD1-0406-CFB
NRD1-040A-CFB
NRD1-040E-CFB
FD38
Max LRA
Volts PH RLA
575
208/230
460
208/230
460
208/230
460
208/230
460
208/230
460
208/230
460
200
208/230
460
208/230
460
208/230
460
230
230
230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
1
1
1
9.2
21.9
11.3
21.9
9
21.9
9
21.9
11.3
21.9
11.3
NA
NA
NA
NA
7.3
16.3
8.4
16.3
8.4
23.6
23.6
27.7
53.4
141
62.5
141
62.5
141
62.5
141
62.5
141
62.5
82
41
79.6
82
41
82
41
82
41
115
115
115
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
3.23
0.514
1.987
0.546
1.987
0.546
1.987
0.514
1.987
0.514
1.987
0.9
3.6
0.721
0.9
3.6
0.9
3.6
0.9
3.6
2.32
2.32
2.32
1.615
0.257
0.99
0.273
0.99
0.273
0.99
0.257
0.99
0.257
0.99
0.47
1.9
0.384
0.47
1.9
0.47
1.9
0.47
1.9
0.417
0.417
0.417
Relay
P/N
014-0006-14 014-0064-14 040-0166-28
014-0006-14 014-0064-14 040-0166-28
014-0006-14 014-0064-14 040-0166-28
Part Protector
Type*
P/N
RP
RP
RP
071-0086-17
071-0086-39
071-0086-14
071-0086-39
071-0429-18
071-0086-39
071-0429-18
071-0086-39
071-0086-14
071-0086-39
071-0086-14
071-0086-11
071-0086-37
071-0086-41
071-0086-11
071-0086-37
071-0429-30
071-0429-31
071-0429-30
071-0429-31
071-0476-01
071-0476-01
071-0476-01
* See Section F Introduction for more information.
Section_Fd.indd 38
3/4/2008 8:03:01 AM
Electrical Data - Copelametic Small Refrigerant-Cooled Compressors
Model
NRD1-040L-CFB
NRD2-032E-TFC
NRD2-032E-TFD
NRM1-0500-TFC
NRM1-0500-TFD
NRM1-0500-TFE
NRM1-050A-TFC
NRM1-050A-TFD
NRM1-050L-TFC
NRM1-050L-TFD
NRN2-0310-TFC
NRN2-0310-TFD
NRN2-031A-TFC
NRN2-031A-TFD
Max LRA
Volts PH RLA
230
208/230
460
208/230
460
575
208/230
460
208/230
460
208/230
460
208/230
460
1
3
3
3
3
3
3
3
3
3
3
3
3
3
27.7
16.3
8.4
24.3
12.1
9.2
24.3
12.1
24.3
12.1
13
6.5
13
6.4
115
82
41
141
62.5
53.4
141
62.5
141
62.5
82
41
82
41
Resistance
Start Cap Run Cap
Start or
Run or
P/N
P/N
Line to Line Line to WYE
2.32
0.9
3.6
0.546
2.14
3.23
0.546
2.14
0.546
2.14
0.9
3.6
0.9
3.6
* See Section F Introduction for more information.
Section_Fd.indd 39
0.417
0.47
1.9
0.273
1.07
1.615
0.273
1.07
0.273
1.07
0.47
1.9
0.47
1.9
Relay
P/N
014-0006-14 014-0064-14 040-0166-28
Part Protector
Type*
P/N
RP
071-0476-01
071-0429-30
071-0429-31
071-0086-39
071-0086-14
071-0086-17
071-0086-39
071-0086-14
071-0086-39
071-0086-14
071-0086-11
071-0086-37
071-0086-11
071-0086-37
FD39
3/4/2008 8:03:01 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
3DA3A0710-ESX
3DA3A0710-ESX
3DA3A071E-ESX
3DA3A071E-ESX
3DA3A071L-ESX
3DA3A071L-ESX
3DB3A0750-ES8
3DB3A0750-ES8
3DB3A0910-ESX
3DB3A0910-ESX
3DB3A091E-ESX
3DB3A091E-ESX
3DB3A1000-ES8
3DB3A1000-ES8
3DB3F33K0-ES8
3DB3F33K0-ES8
3DB3R12M0-ES8
3DB3R12M0-ES8
3DP3A1000-ES8
3DP3A1000-ES8
3DP3R12M0-ES8
3DP3R12M0-ES8
200/220
380
200/220
380
200/220
380
200/220
380
220
380
220
380
200/220
380
200/220
380
200/220
380
200/220
380
200/220
380
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
25.7
15.6
31.8
18.9
31.8
18.9
29.2
16.4
38.1
20.4
47.4
27.7
48
27.4
29.2
16.4
48
27.4
48
27.4
48
27.4
167
96
167
96
167
96
167
96
228
132
228
132
228
132
167
96
228
132
228
132
228
132
Part Winding Start
Max RLA
LRA
58
58
58
58
74
74
74
58
74
74
74
Winding Resistance
Line to Line (Ohms)
0.36
1.08
0.36
1.08
0.36
1.08
0.36
1.08
0.279
0.837
0.279
0.837
0.279
0.837
0.36
1.08
0.279
0.837
0.279
0.837
0.279
0.837
See Section F Introduction for more information.
FE1
Section_Fe.indd 1
3/4/2008 8:06:37 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
3DR3A1000-ES8
3DR3A1000-ES8
3DS3A1000-ES8
3DS3A1000-ES8
3DS3A1210-ESX
3DS3A1210-ESX
3DS3A121E-ESX
3DS3A121E-ESX
3DS3A1500-ES8
3DS3A1500-ES8
3DS3F46K0-ES8
3DS3F46K0-ES8
3DS3R17M0-ES8
3DS3R17M0-ES8
3DT3A1000-ES8
3DT3A1000-ES8
3DT3A1500-ES8
3DT3A1500-ES8
3DT3R17M0-ES8
3DT3R17M0-ES8
4DA1A1000-FSD
4DA1A1000-TSE
200/220
380
200/220
380
220
380
220
380
200/220
380
200/220
380
200/220
380
200/220
380
200/220
380
200/220
380
460
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
41.7
24.1
47.1
25.7
42.1
24.1
53.4
31.2
57.6
32.9
47.1
25.7
57.6
32.9
47.1
25.7
57.6
32.9
57.6
32.9
25.7
20
228
132
228
132
228
132
228
132
316
180
228
132
316
180
228
132
316
180
316
180
110
106
Part Winding Start
Max RLA
LRA
74
74
74
74
108
74
108
74
108
108
12.9
66
Winding Resistance
Line to Line (Ohms)
0.279
0.837
0.279
0.837
0.279
0.837
0.279
0.837
0.191
0.573
0.279
0.837
0.191
0.573
0.279
0.837
0.191
0.573
0.191
0.573
1.02
1.6
See Section F Introduction for more information.
FE2
Section_Fe.indd 2
3/4/2008 8:06:41 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DA1A1000-TSK
4DA1A1000-TSK
4DA1A2000-FSD
4DA1A2000-TSE
4DA1A2000-TSK
4DA1A2000-TSK
4DA1A2000-TXK
4DA1A2000-TXK
4DA1R18M0-TSK
4DA1R18M0-TSK
4DA3A1000-FSD
4DA3A1000-TSE
4DA3A1000-TSK
4DA3A1000-TSK
4DA3A100E-FSD
4DA3A100E-TSE
4DA3A100E-TSK
4DA3A100E-TSK
4DA3A100L-FSD
4DA3A100L-TSE
4DA3A100L-TSK
4DA3A100L-TSK
208/230
460
460
575
208/230
460
208/230
460
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
53.6
26.8
32.1
28.6
70
35
NA
NA
70
35
20
17.4
42
21
20
17.4
42
21
20
17.4
42
21
240
120
140
135
308
154
308
154
308
154
115
106
240
120
115
106
240
120
115
106
240
120
Part Winding Start
Max RLA
LRA
26.8
140
16.1
14.3
35
84
81
188
35
188
35
188
10
70
21
140
10
70
21
140
10
70
21
140
Winding Resistance
Line to Line (Ohms)
0.259
1.036
0.757
2.2
0.174
0.696
0.174
0.696
0.174
0.696
1.012
1.6
0.259
1.036
1.012
1.6
0.259
1.036
1.012
1.6
0.259
1.036
See Section F Introduction for more information.
FE3
Section_Fe.indd 3
3/4/2008 8:06:41 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DA3A1010-TSE
4DA3A1010-TSK
4DA3A1010-TSK
4DA3A101E-TSE
4DA3A101E-TSK
4DA3A101E-TSK
4DA3A101L-TSE
4DA3A101L-TSK
4DA3A101L-TSK
4DA3A2000-FSD
4DA3A2000-FXD
4DA3A2000-TSE
4DA3A2000-TSK
4DA3A2000-TSK
4DA3A2000-TXE
4DA3A2000-TXK
4DA3A2000-TXK
4DA3A200E-FSD
4DA3A200E-TSE
4DA3A200E-TSK
4DA3A200E-TSK
4DA3A200L-FSD
575
208/230
460
575
208/230
460
575
208/230
460
460
460
575
208/230
460
575
208/230
460
460
575
208/230
460
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
17.4
42
21
17.4
45.6
22.8
17.4
45.6
22.8
33.6
NA
24.7
66.6
33.3
NA
NA
NA
33.6
24.7
82.9
41.4
33.6
106
220
110
106
220
110
106
220
110
173
173
135
308
154
135
308
154
173
135
308
154
173
Part Winding Start
Max RLA
LRA
22.6
134
22.6
134
22.6
134
16.8
12.4
33
104
104
81
188
33
81
188
16.8
12.4
33
104
81
188
16.8
104
Winding Resistance
Line to Line (Ohms)
1.6
0.244
0.976
1.6
0.244
0.976
1.6
0.244
0.976
0.603
0.603
2.2
0.174
0.696
1.1
0.174
0.696
0.603
2.2
0.174
0.696
0.603
See Section F Introduction for more information.
FE4
Section_Fe.indd 4
3/4/2008 8:06:42 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DA3A200L-TSE
4DA3A200L-TSK
4DA3A200L-TSK
4DA3F47K0-TSE
4DA3F47K0-TSK
4DA3F47K0-TSK
4DA3F47KE-TSE
4DA3F47KE-TSK
4DA3F47KE-TSK
4DA3F47KL-TSE
4DA3F47KL-TSK
4DA3F47KL-TSK
4DA3R12M0-FSD
4DA3R12ME-FSD
4DA3R12ME-TSK
4DA3R12ME-TSK
4DA3R18M0-FSD
4DA3R18M0-TSE
4DA3R18M0-TSK
4DA3R18M0-TSK
4DA3R18ME-FSD
4DA3R18ME-TSE
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
460
460
208/230
460
460
575
208/230
460
460
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
24.7
82.9
41.4
17.4
42
21
17.4
45.6
22.8
17.4
45.6
22.8
20
20
42
21
33.6
24.7
66.6
33.3
33.6
24.7
135
308
154
106
220
110
106
220
110
106
220
110
115
115
240
120
173
135
308
154
173
135
Part Winding Start
Max RLA
LRA
12.4
33
81
188
22.6
134
22.6
134
22.6
134
10
10
21
70
70
140
16.8
12.4
33
104
81
188
16.8
12.4
104
81
Winding Resistance
Line to Line (Ohms)
2.2
0.174
0.696
1.6
0.244
0.976
1.6
0.244
0.976
1.6
0.244
0.976
1.012
1.012
0.259
1.036
0.603
2.2
0.174
0.696
0.603
2.2
See Section F Introduction for more information.
FE5
Section_Fe.indd 5
3/4/2008 8:06:42 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DA3R18ME-TSK
4DA3R18ME-TSK
4DA3R18ML-FSD
4DA3R18ML-TSE
4DA3R18ML-TSK
4DA3R18ML-TSK
4DA3S13ME-TSK
4DA3S13ME-TSK
4DA3S13ML-TSK
4DA3S13ML-TSK
4DA5A1000-TSK
4DA5A1000-TSK
4DAGA1010-TSK
4DAGA1010-TSK
4DAJA2000-TSK
4DAJA2000-TSK
4DB3A2200-FSD
4DB3A2200-TSE
4DB3A2200-TSK
4DB3A2200-TSK
4DB3A220E-FSD
4DB3A220E-TSE
208/230
460
460
575
208/230
460
208/230
460
208/230
460
208/230
460
208/230
460
208/230
460
460
575
208/230
460
460
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
82.9
41.4
33.6
24.7
82.9
41.4
57.1
27.1
57.1
27.1
53.6
26.8
42
21
66.6
33.3
32.5
26.5
65.6
32.8
32.5
31.4
308
154
173
135
308
154
278
139
278
139
240
120
220
110
308
154
180
135
374
187
180
135
Part Winding Start
Max RLA
LRA
33
188
16.8
12.4
33
104
81
188
26.8
140
22.6
134
33
188
16.3
13.3
32.8
108
81
222
16.3
13.3
108
81
Winding Resistance
Line to Line (Ohms)
0.174
0.696
0.603
2.2
0.174
0.696
0
0.204
0
0.204
0.259
1.036
0.244
0.976
0.174
0.696
0.558
1.94
0.14
0.56
0.558
1.94
See Section F Introduction for more information.
FE6
Section_Fe.indd 6
3/4/2008 8:06:43 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DB3A220E-TSK
4DB3A220E-TSK
4DB3A220L-FSD
4DB3A220L-TSE
4DB3A220L-TSK
4DB3A220L-TSK
4DB3R20M0-FSD
4DB3R20M0-TSE
4DB3R20M0-TSK
4DB3R20M0-TSK
4DB3R20ME-FSD
4DB3R20ME-TSE
4DB3R20ME-TSK
4DB3R20ME-TSK
4DB3R20ML-FSD
4DB3R20ML-TSE
4DB3R20ML-TSK
4DB3R20ML-TSK
4DC3A2200-FSD
4DC3A2200-TSE
4DC3A2200-TSK
4DC3A2200-TSK
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
92.9
46.4
32.5
31.4
92.9
46.4
32.5
26.5
65.6
32.8
32.5
31.4
92.9
46.4
32.5
31.4
92.9
46.4
32.5
26.5
65.6
32.8
374
187
180
135
374
187
180
135
374
187
180
135
374
187
180
135
374
187
180
135
374
187
Part Winding Start
Max RLA
LRA
32.8
222
16.3
13.3
32.8
108
81
222
16.3
13.3
32.8
108
81
222
16.3
13.3
32.8
108
81
222
16.3
13.3
32.8
108
81
222
16.3
13.3
32.8
108
81
222
Winding Resistance
Line to Line (Ohms)
0.14
0.56
0.558
1.94
0.14
0.56
0.558
1.94
0.14
0.56
0.558
1.94
0.14
0.56
0.558
1.94
0.14
0.56
0.558
1.94
0.14
0.56
See Section F Introduction for more information.
FE7
Section_Fe.indd 7
3/4/2008 8:06:43 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DC3A220E-FSD
4DC3A220E-TSE
4DC3A220E-TSK
4DC3A220E-TSK
4DC3A220L-FSD
4DC3A220L-TSE
4DC3A220L-TSK
4DC3A220L-TSK
4DC3R20M0-FSD
4DC3R20M0-TSE
4DC3R20M0-TSK
4DC3R20M0-TSK
4DC3R20ME-FSD
4DC3R20ME-TSE
4DC3R20ME-TSK
4DC3R20ME-TSK
4DC3R20ML-FSD
4DC3R20ML-TSE
4DC3R20ML-TSK
4DC3R20ML-TSK
4DE1A1000-TSE
4DE1A1000-TSK
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
575
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
32.5
31.4
92.9
46.4
32.5
31.4
92.9
46.4
32.5
26.5
65.6
32.8
32.5
31.4
92.9
46.4
32.5
31.4
92.9
46.4
20
53.6
180
135
374
187
180
135
374
187
180
135
374
187
180
135
374
187
180
135
374
187
106
240
Part Winding Start
Max RLA
LRA
16.3
13.3
32.8
108
81
222
16.3
13.3
32.8
108
81
222
16.3
13.3
32.8
108
81
222
16.3
13.3
32.8
108
81
222
16.3
13.3
32.8
108
81
222
26.8
140
Winding Resistance
Line to Line (Ohms)
0.558
1.94
0.14
0.56
0.558
1.94
0.14
0.56
0.558
1.94
0.14
0.56
0.558
1.94
0.14
0.56
0.558
1.94
0.14
0.56
1.6
0.259
See Section F Introduction for more information.
FE8
Section_Fe.indd 8
3/4/2008 8:06:43 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DE1A1000-TSK
4DE1A2000-FSD
4DE1A2000-TSE
4DE1A2000-TSK
4DE1A2000-TSK
4DE1A2000-TXK
4DE1A2000-TXK
4DE1R18M0-FSD
4DE1R18M0-TSK
4DE1R18M0-TSK
4DE3A100E-TSK
4DE3A100E-TSK
4DE3A100L-TSK
4DE3A100L-TSK
4DE3A2000-FSD
4DE3A2000-FXD
4DE3A2000-TSE
4DE3A2000-TSK
4DE3A2000-TSK
4DE3A2000-TXE
4DE3A2000-TXK
4DE3A2000-TXK
460
460
575
208/230
460
208/230
460
460
208/230
460
208/230
460
208/230
460
460
460
575
208/230
460
575
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
26.8
32.1
28.6
70
35
NA
NA
32.1
70
35
42
21
42
21
33.6
NA
24.7
66.6
33.3
NA
NA
NA
120
140
135
308
154
308
154
140
308
154
240
120
240
120
173
173
135
308
154
135
308
154
Part Winding Start
Max RLA
LRA
16.1
14.3
35
84
81
188
35
188
16.1
35
84
188
21
140
21
140
16.8
12.4
33
104
104
81
188
33
81
188
Winding Resistance
Line to Line (Ohms)
1.036
0.757
2.2
0.174
0.696
0.174
0.696
0.757
0.174
0.696
0.259
1.036
0.259
1.036
0.603
0.603
2.2
0.174
0.696
1.1
0.174
0.696
See Section F Introduction for more information.
FE9
Section_Fe.indd 9
3/4/2008 8:06:44 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DE3A200E-FSD
4DE3A200E-TSE
4DE3A200E-TSK
4DE3A200E-TSK
4DE3A200L-FSD
4DE3A200L-TSE
4DE3A200L-TSK
4DE3A200L-TSK
4DE3R12ME-TSK
4DE3R12ME-TSK
4DE3R12ML-TSK
4DE3R12ML-TSK
4DE3R18M0-FSD
4DE3R18M0-TSE
4DE3R18M0-TSK
4DE3R18M0-TSK
4DE3R18ME-FSD
4DE3R18ME-TSE
4DE3R18ME-TSK
4DE3R18ME-TSK
4DE3R18ML-FSD
4DE3R18ML-TSE
460
575
208/230
460
460
575
208/230
460
208/230
460
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
33.6
24.7
82.9
41.4
33.6
24.7
82.9
41.4
42
21
42
21
33.6
24.7
66.6
33.3
33.6
24.7
82.9
41.4
33.6
24.7
173
135
308
154
173
135
308
154
240
120
240
120
173
135
308
154
173
135
308
154
173
135
Part Winding Start
Max RLA
LRA
16.8
12.4
33
104
81
188
16.8
12.4
33
104
81
188
21
140
21
140
16.8
12.4
33
104
81
188
16.8
12.4
33
104
81
188
16.8
12.4
104
81
Winding Resistance
Line to Line (Ohms)
0.603
2.2
0.174
0.696
0.603
2.2
0.174
0.696
0.259
1.036
0.259
1.036
0.603
2.2
0.174
0.696
0.603
2.2
0.174
0.696
0.603
2.2
See Section F Introduction for more information.
FE10
Section_Fe.indd 10
3/4/2008 8:06:44 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DE3R18ML-TSK
4DE3R18ML-TSK
4DE3S13ME-TSK
4DE3S13ME-TSK
4DE3S13ML-TSK
4DE3S13ML-TSK
4DE5A2000-TSK
4DE5A2000-TSK
4DE8A101E-TSK
4DE8A101E-TSK
4DE8A2000-FSD
4DE8A200E-TSK
4DE8A200E-TSK
4DE8F47KE-TSK
4DE8F47KE-TSK
4DH1A1500-FSD
4DH1A1500-TSE
4DH1A1500-TSK
4DH1A1500-TSK
4DH1A2500-ES8
4DH1A2500-ES8
4DH1A2500-FSD
208/230
460
208/230
460
208/230
460
208/230
460
208/230
460
460
208/230
460
208/230
460
460
575
208/230
460
200/220
380
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
82.9
41.4
57.1
27.1
57.1
27.1
70
35
45.6
22.8
33.6
58.7
29.4
45.6
22.8
32.9
24.3
61.4
30.7
99.3
58.6
46.4
308
154
278
139
278
139
308
154
220
110
173
308
154
220
110
136
113
278
139
438
251
195
Part Winding Start
Max RLA
LRA
33
188
35
188
22.6
134
16.8
33
104
188
22.6
134
16.5
81.6
30.7
170
142
23.2
117
Winding Resistance
Line to Line (Ohms)
0.174
0.696
0
0.204
0
0.204
0.174
0.696
0.244
0.976
0.603
0.174
0.696
0.244
0.976
0.84
0.97
0.208
0.832
0.345
0.115
0.575
See Section F Introduction for more information.
FE11
Section_Fe.indd 11
3/4/2008 8:06:44 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DH1A2500-FXD
4DH1A2500-TSE
4DH1A2500-TSK
4DH1A2500-TSK
4DH1A2500-TXE
4DH1A2500-TXK
4DH1A2500-TXK
4DH1R22M0-ES8
4DH1R22M0-ES8
4DH1R22M0-FSD
4DH1R22M0-TSK
4DH1R22M0-TSK
4DH3A150E-TSE
4DH3A150E-TSK
4DH3A150E-TSK
4DH3A150L-TSE
4DH3A150L-TSK
4DH3A150L-TSK
4DH3A2500-ES8
4DH3A2500-ES8
4DH3A2500-FSD
4DH3A2500-FXD
460
575
208/230
460
575
208/230
460
200/220
380
460
208/230
460
575
208/230
460
575
208/230
460
200/220
380
460
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
NA
34.3
85.7
42.9
NA
NA
NA
99.3
58.6
46.4
85.7
42.9
24.3
57.9
28.9
24.3
57.9
28.9
NA
NA
40.6
NA
195
172
428
214
172
428
214
438
251
195
428
214
113
278
139
113
278
139
438
251
206
206
Part Winding Start
Max RLA
LRA
17.2
42.9
117
103
250
103
250
142
23.2
42.9
117
250
29
170
29
170
142
20.3
132
132
Winding Resistance
Line to Line (Ohms)
0.575
1.538
0.132
0.528
0.769
0.132
0.528
0.345
0.115
0.575
0.132
0.528
1.28
0.208
0.832
1.28
0.208
0.832
0.345
0.115
0.524
0.524
See Section F Introduction for more information.
FE12
Section_Fe.indd 12
3/4/2008 8:06:45 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DH3A2500-TSE
4DH3A2500-TSK
4DH3A2500-TSK
4DH3A2500-TXE
4DH3A2500-TXK
4DH3A2500-TXK
4DH3A250E-ES8
4DH3A250E-ES8
4DH3A250E-FSD
4DH3A250E-TSE
4DH3A250E-TSK
4DH3A250E-TSK
4DH3A250L-ES8
4DH3A250L-ES8
4DH3A250L-FSD
4DH3A250L-TSE
4DH3A250L-TSK
4DH3A250L-TSK
4DH3R16ME-TSK
4DH3R16ME-TSK
4DH3R16ML-TSK
4DH3R16ML-TSK
575
208/230
460
575
208/230
460
200/220
380
460
575
208/230
460
200/220
380
460
575
208/230
460
208/230
460
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
34.4
82.1
41.1
NA
NA
NA
NA
NA
40.6
34.4
82.1
52.9
NA
NA
40.6
34.4
82.1
52.9
57.9
28.9
57.9
28.9
172
428
214
172
428
214
438
251
206
172
428
214
438
251
206
172
428
214
278
139
278
139
Part Winding Start
Max RLA
LRA
17.2
41.1
103
250
103
250
142
20.3
17.2
41.1
132
103
250
142
20.3
17.2
41.1
132
103
250
29
170
29
170
Winding Resistance
Line to Line (Ohms)
1.538
0.132
0.528
0.769
0.132
0.528
0.345
0.115
0.524
1.538
0.132
0.528
0.345
0.115
0.524
1.538
0.132
0.528
0.208
0.832
0.208
0.832
See Section F Introduction for more information.
FE13
Section_Fe.indd 13
3/4/2008 8:06:45 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DH3R22M0-ES8
4DH3R22M0-ES8
4DH3R22M0-FSD
4DH3R22M0-TSE
4DH3R22M0-TSK
4DH3R22M0-TSK
4DH3R22M0-TXE
4DH3R22ME-FSD
4DH3R22ME-TSE
4DH3R22ME-TSK
4DH3R22ME-TSK
4DH3R22ML-FSD
4DH3R22ML-TSE
4DH3R22ML-TSK
4DH3R22ML-TSK
4DH3S16ME-TSK
4DH3S16ME-TSK
4DH3S16ML-TSK
4DH3S16ML-TSK
4DJ1A2000-FSD
4DJ1A2000-TSE
4DJ1A2000-TSK
200/220
380
460
575
208/230
460
575
460
575
208/230
460
460
575
208/230
460
208/230
460
208/230
460
460
575
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
NA
NA
40.6
34.4
82.1
41.1
NA
40.6
34.4
82.1
52.9
40.6
34.4
82.1
52.9
65.7
32.1
NA
NA
32.9
30
71.4
438
251
206
172
428
214
172
206
172
428
214
206
172
428
214
308
154
308
154
173
135
346
Part Winding Start
Max RLA
LRA
142
20.3
17.2
41.1
132
103
250
20.3
17.2
41.1
103
132
103
250
20.3
17.2
41.1
132
103
250
16.5
15
35.7
104
81
208
Winding Resistance
Line to Line (Ohms)
0.345
0.115
0.524
1.538
0.132
0.528
0.769
0.524
1.538
0.132
0.528
0.524
1.538
0.132
0.528
0
0.179
0
0.179
0.603
1.94
0.142
See Section F Introduction for more information.
FE14
Section_Fe.indd 14
3/4/2008 8:06:46 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DJ1A2000-TSK
4DJ1A3000-ES8
4DJ1A3000-ES8
4DJ1A3000-FSD
4DJ1A3000-TSE
4DJ1A3000-TSK
4DJ1A3000-TSK
4DJ1A3000-TXE
4DJ1A3000-TXK
4DJ1A3000-TXK
4DJ1R28M0-TSK
4DJ1R28M0-TSK
4DJ2A2000-TSK
4DJ2A2000-TSK
4DJ2A3000-TSK
4DJ2A3000-TSK
4DJ2R28M0-TSK
4DJ2R28M0-TSK
4DJ3A200E-TSE
4DJ3A200E-TSK
4DJ3A200E-TSK
4DJ3A200L-TSE
460
200/220
380
460
575
208/230
460
575
208/230
460
208/230
460
208/230
460
208/230
460
208/230
460
575
208/230
460
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
35.7
123.6
71.4
59
42.9
117.9
58.9
NA
NA
NA
117.9
58.9
71.4
35.7
117.9
58.9
117.9
58.9
30
66
33
30
173
500
289
235
200
470
235
200
470
235
470
235
346
173
470
235
470
235
135
346
173
135
Part Winding Start
Max RLA
LRA
164
29.5
21.5
59
141
130
292
130
292
59
292
35.7
208
59
292
59
292
15
33
81
208
15
81
Winding Resistance
Line to Line (Ohms)
0.568
0.294
0.098
0.45
1.46
0.111
0.444
0.731
0.111
0.444
0.111
0.444
0.142
0.568
0.111
0.444
0.111
0.444
1.94
0.142
0.568
1.94
See Section F Introduction for more information.
FE15
Section_Fe.indd 15
3/4/2008 8:06:46 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DJ3A200L-TSK
4DJ3A200L-TSK
4DJ3A270E-TSK
4DJ3A270E-TSK
4DJ3A270L-TSK
4DJ3A270L-TSK
4DJ3A3000-FSD
4DJ3A3000-FXD
4DJ3A3000-TSE
4DJ3A3000-TSK
4DJ3A3000-TSK
4DJ3A3000-TXE
4DJ3A3000-TXK
4DJ3A3000-TXK
4DJ3A300E-FSD
4DJ3A300E-TSE
4DJ3A300E-TSK
4DJ3A300E-TSK
4DJ3A300L-FSD
4DJ3A300L-TSE
4DJ3A300L-TSK
4DJ3A300L-TSK
208/230
460
208/230
460
208/230
460
460
460
575
208/230
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
66
33
94
55
94
55
45
NA
39.3
94
47
NA
NA
NA
45
39.3
94
55
45
39.3
94
55
346
173
470
235
470
235
235
235
200
470
235
200
470
235
235
200
470
235
235
200
470
235
Part Winding Start
Max RLA
LRA
33
208
47
292
47
292
22.5
141
141
130
292
19.7
47
130
292
22.5
19.7
47
141
130
292
22.5
19.7
47
141
130
292
Winding Resistance
Line to Line (Ohms)
0.142
0.568
0.111
0.444
0.111
0.444
0.45
0.45
1.46
0.111
0.444
0.731
0.111
0.444
0.45
1.46
0.111
0.444
0.45
1.46
0.111
0.444
See Section F Introduction for more information.
FE16
Section_Fe.indd 16
3/4/2008 8:06:46 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DJ3R19ME-TSK
4DJ3R19ME-TSK
4DJ3R19ML-TSK
4DJ3R19ML-TSK
4DJ3R28M0-FSD
4DJ3R28M0-TSE
4DJ3R28M0-TSK
4DJ3R28M0-TSK
4DJ3R28ME-FSD
4DJ3R28ME-TSE
4DJ3R28ME-TSK
4DJ3R28ME-TSK
4DJ3R28ML-FSD
4DJ3R28ML-TSE
4DJ3R28ML-TSK
4DJ3R28ML-TSK
4DJ8A3000-TSK
4DJ8A3000-TSK
4DK1A1500-TSK
4DK1A1500-TSK
4DK1A2500-ES8
4DK1A2500-ES8
208/230
460
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
208/230
460
208/230
460
200/220
380
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
66
33
66
33
45
39.3
94
47
45
39.3
94
55
45
39.3
94
55
94
47
61.4
30.7
99.3
58.6
346
173
346
173
235
200
470
235
235
200
470
235
235
200
470
235
470
235
278
139
438
251
Part Winding Start
Max RLA
LRA
33
208
33
208
22.5
19.7
47
141
130
292
22.5
19.7
47
141
130
292
22.5
19.7
47
141
130
292
47
292
30.7
170
142
Winding Resistance
Line to Line (Ohms)
0.142
0.568
0.142
0.568
0.45
1.46
0.111
0.444
0.45
1.46
0.111
0.444
0.45
1.46
0.111
0.444
0.111
0.444
0.208
0.832
0.345
0.115
See Section F Introduction for more information.
FE17
Section_Fe.indd 17
3/4/2008 8:06:47 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DK1A2500-FSD
4DK1A2500-FXD
4DK1A2500-TSE
4DK1A2500-TSK
4DK1A2500-TSK
4DK1A2500-TXE
4DK1A2500-TXK
4DK1A2500-TXK
4DK1R22M0-FSD
4DK1R22M0-TSE
4DK1R22M0-TSK
4DK1R22M0-TSK
4DK3A150E-TSE
4DK3A150E-TSK
4DK3A150E-TSK
4DK3A150L-TSE
4DK3A150L-TSK
4DK3A150L-TSK
4DK3A2500-ES8
4DK3A2500-ES8
4DK3A2500-FSD
4DK3A2500-FXD
460
460
575
208/230
460
575
208/230
460
460
575
208/230
460
575
208/230
460
575
208/230
460
200/220
380
460
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
46.4
NA
34.3
85.7
42.9
NA
NA
NA
46.4
34.3
85.7
42.9
24.3
57.9
28.9
24.3
57.9
28.9
NA
NA
40.6
NA
195
195
172
428
214
172
428
214
195
172
428
214
113
278
139
113
278
139
438
251
206
206
Part Winding Start
Max RLA
LRA
23.2
17.2
42.9
117
117
103
250
103
250
23.2
17.2
42.9
117
103
250
29
170
29
170
142
20.3
132
132
Winding Resistance
Line to Line (Ohms)
0.575
0.575
1.538
0.132
0.528
0.769
0.132
0.528
0.575
1.538
0.132
0.528
1.28
0.208
0.832
1.28
0.208
0.832
0.345
0.115
0.524
0.524
See Section F Introduction for more information.
FE18
Section_Fe.indd 18
3/4/2008 8:06:47 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DK3A2500-TSE
4DK3A2500-TSK
4DK3A2500-TSK
4DK3A2500-TXE
4DK3A2500-TXK
4DK3A2500-TXK
4DK3A250E-ES8
4DK3A250E-ES8
4DK3A250E-FSD
4DK3A250E-TSE
4DK3A250E-TSK
4DK3A250E-TSK
4DK3A250L-ES8
4DK3A250L-ES8
4DK3A250L-FSD
4DK3A250L-TSE
4DK3A250L-TSK
4DK3A250L-TSK
4DK3R16ME-TSK
4DK3R16ME-TSK
4DK3R22M0-ES8
4DK3R22M0-ES8
575
208/230
460
575
208/230
460
200/220
380
460
575
208/230
460
200/220
380
460
575
208/230
460
208/230
460
200/220
380
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
34.4
82.1
41.1
NA
NA
NA
NA
NA
40.6
34.4
82.1
52.9
NA
NA
40.6
34.4
82.1
52.9
57.9
28.9
NA
NA
172
428
214
172
428
214
438
251
206
172
428
214
438
251
206
172
428
214
278
139
438
251
Part Winding Start
Max RLA
LRA
17.2
41.1
103
250
103
250
142
20.3
17.2
41.1
132
103
250
142
20.3
17.2
41.1
132
103
250
29
170
142
Winding Resistance
Line to Line (Ohms)
1.538
0.132
0.528
0.769
0.132
0.528
0.345
0.115
0.524
1.538
0.132
0.528
0.345
0.115
0.524
1.538
0.132
0.528
0.208
0.832
0.345
0.115
See Section F Introduction for more information.
FE19
Section_Fe.indd 19
3/4/2008 8:06:48 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DK3R22M0-FSD
4DK3R22M0-TSE
4DK3R22M0-TSK
4DK3R22M0-TSK
4DK3R22ME-FSD
4DK3R22ME-TSE
4DK3R22ME-TSK
4DK3R22ME-TSK
4DK3R22ML-FSD
4DK3R22ML-TSE
4DK3R22ML-TSK
4DK3R22ML-TSK
4DK3S16ME-TSK
4DK3S16ME-TSK
4DK3S16ML-TSK
4DK3S16ML-TSK
4DL1A1500-ES8
4DL1A1500-ES8
4DL1A1500-FSD
4DL1A1500-TSE
4DL1A1500-TSK
4DL1A1500-TSK
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
208/230
460
208/230
460
200/220
380
460
575
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
40.6
34.4
82.1
41.1
40.6
34.4
82.1
52.9
40.6
34.4
82.1
52.9
65.7
32.1
NA
NA
NA
NA
28.6
22.8
60
30
206
172
428
214
206
172
428
214
206
172
428
214
308
154
308
154
295
175
136
113
278
139
Part Winding Start
Max RLA
LRA
20.3
17.2
41.1
132
103
250
20.3
17.2
41.1
132
103
250
20.3
17.2
41.1
132
103
250
107
14.3
81.6
30
170
Winding Resistance
Line to Line (Ohms)
0.524
1.538
0.132
0.528
0.524
1.538
0.132
0.528
0.524
1.538
0.132
0.528
0
0.179
0
0.179
0.546
0.182
0.84
1.28
0.208
0.832
See Section F Introduction for more information.
FE20
Section_Fe.indd 20
3/4/2008 8:06:48 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DL1F63K0-FSD
4DL1F63K0-TSK
4DL1F63K0-TSK
4DL3A1500-ES8
4DL3A1500-ES8
4DL3A1500-FSD
4DL3A1500-TSE
4DL3A1500-TSK
4DL3A1500-TSK
4DL3A150E-FSD
4DL3A150E-TSE
4DL3A150E-TSK
4DL3A150E-TSK
4DL3A150L-FSD
4DL3A150L-TSE
4DL3A150L-TSK
4DL3A150L-TSK
4DL3F63K0-ES8
4DL3F63K0-ES8
4DL3F63K0-FSD
4DL3F63K0-TSE
4DL3F63K0-TSK
460
208/230
460
200/220
380
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
200/220
380
460
575
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
28.6
60
30
NA
NA
24.5
20.9
52.6
26.3
24.5
20.9
52.6
26.3
24.5
20.9
52.6
26.3
NA
NA
24.5
20.9
52.6
136
278
139
295
175
136
113
278
139
136
113
278
139
136
113
278
139
295
175
136
113
278
Part Winding Start
Max RLA
LRA
14.3
30
81.6
170
107
12.3
81.6
26.3
170
12.3
81.6
26.3
170
12.3
81.6
26.3
170
107
12.3
81.6
26.3
170
Winding Resistance
Line to Line (Ohms)
0.84
0.208
0.832
0.546
0.182
0.84
1.28
0.208
0.832
0.84
1.28
0.208
0.832
0.84
1.28
0.208
0.832
0.546
0.182
0.84
1.28
0.208
See Section F Introduction for more information.
FE21
Section_Fe.indd 21
3/4/2008 8:06:48 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DL3F63K0-TSK
4DL3F63KE-FSD
4DL3F63KE-TSE
4DL3F63KE-TSK
4DL3F63KE-TSK
4DL3F63KL-FSD
4DL3F63KL-TSE
4DL3F63KL-TSK
4DL3F63KL-TSK
4DL8A1500-TSK
4DL8A1500-TSK
4DN1A1000-FSD
4DN1A1000-TSE
4DN1A1000-TSK
4DN1A1000-TSK
4DN3A1000-FSD
4DN3A1000-TSE
4DN3A1000-TSK
4DN3A1000-TSK
4DN3A100E-FSD
4DN3A100E-TSE
4DN3A100L-FSD
460
460
575
208/230
460
460
575
208/230
460
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
26.3
24.5
20.9
52.6
26.3
24.5
20.9
52.6
26.3
52.6
26.3
25.7
20
53.6
26.8
20
17.4
42
21
20
17.4
20
139
136
113
278
139
136
113
278
139
278
139
110
106
240
120
115
106
240
120
115
106
115
Part Winding Start
Max RLA
LRA
12.3
81.6
26.3
170
12.3
81.6
26.3
170
26.3
170
12.9
66
26.8
140
10
70
21
140
10
70
10
70
Winding Resistance
Line to Line (Ohms)
0.832
0.84
1.28
0.208
0.832
0.84
1.28
0.208
0.832
0.208
0.832
1.02
1.6
0.259
1.036
1.012
1.6
0.259
1.036
1.012
1.6
1.012
See Section F Introduction for more information.
FE22
Section_Fe.indd 22
3/4/2008 8:06:49 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DN3A100L-TSE
4DN3A1010-TSE
4DN3A1010-TSK
4DN3A1010-TSK
4DN3A101E-TSE
4DN3A101E-TSK
4DN3A101E-TSK
4DN3A101L-TSE
4DN3A101L-TSK
4DN3A101L-TSK
4DN3F47K0-TSE
4DN3F47K0-TSK
4DN3F47K0-TSK
4DN3F47KE-TSE
4DN3F47KE-TSK
4DN3F47KE-TSK
4DN3F47KL-TSE
4DN3F47KL-TSK
4DN3F47KL-TSK
4DP1A1500-ES8
4DP1A1500-ES8
4DP1A1500-FSD
575
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
200/220
380
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
17.4
17.4
42
21
17.4
45.6
22.8
17.4
45.6
22.8
17.4
42
21
17.4
45.6
22.8
17.4
45.6
22.8
NA
NA
28.6
106
106
220
110
106
220
110
106
220
110
106
220
110
106
220
110
106
220
110
295
175
136
Part Winding Start
Max RLA
LRA
22.6
134
22.6
134
22.6
134
22.6
134
22.6
134
22.6
134
107
14.3
81.6
Winding Resistance
Line to Line (Ohms)
1.6
1.6
0.244
0.976
1.6
0.244
0.976
1.6
0.244
0.976
1.6
0.244
0.976
1.6
0.244
0.976
1.6
0.244
0.976
0.546
0.182
0.84
See Section F Introduction for more information.
FE23
Section_Fe.indd 23
3/4/2008 8:06:49 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DP1A1500-TSK
4DP1A1500-TSK
4DP3A1500-FSD
4DP3A1500-TSE
4DP3A1500-TSK
4DP3A1500-TSK
4DP3A150E-FSD
4DP3A150E-TSE
4DP3A150E-TSK
4DP3A150E-TSK
4DP3A150L-FSD
4DP3A150L-TSE
4DP3A150L-TSK
4DP3A150L-TSK
4DP3F63K0-FSD
4DP3F63K0-TSE
4DP3F63K0-TSK
4DP3F63K0-TSK
4DP3F63KE-FSD
4DP3F63KE-TSE
4DP3F63KE-TSK
4DP3F63KE-TSK
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
60
30
24.5
20.9
52.6
26.3
24.5
20.9
52.6
26.3
24.5
20.9
52.6
26.3
24.5
20.9
52.6
26.3
24.5
20.9
52.6
26.3
278
139
136
113
278
139
136
113
278
139
136
113
278
139
136
113
278
139
136
113
278
139
Part Winding Start
Max RLA
LRA
30
170
12.3
81.6
26.3
170
12.3
81.6
26.3
170
12.3
81.6
26.3
170
12.3
81.6
26.3
170
12.3
81.6
26.3
170
Winding Resistance
Line to Line (Ohms)
0.208
0.832
0.84
1.28
0.208
0.832
0.84
1.28
0.208
0.832
0.84
1.28
0.208
0.832
0.84
1.28
0.208
0.832
0.84
1.28
0.208
0.832
See Section F Introduction for more information.
FE24
Section_Fe.indd 24
3/4/2008 8:06:50 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DP3F63KL-FSD
4DP3F63KL-TSE
4DP3F63KL-TSK
4DP3F63KL-TSK
4DP8A1500-TSK
4DP8A1500-TSK
4DP8A150E-TSK
4DP8A150E-TSK
4DP8A150L-TSK
4DP8A150L-TSK
4DP8F63KE-TSK
4DP8F63KE-TSK
4DR1A2000-TSE
4DR1A2000-TSK
4DR1A2000-TSK
4DR1A3000-ES8
4DR1A3000-ES8
4DR1A3000-FSD
4DR1A3000-FXD
4DR1A3000-TSE
4DR1A3000-TSK
4DR1A3000-TSK
460
575
208/230
460
208/230
460
208/230
460
208/230
460
208/230
460
575
208/230
460
200/220
380
460
460
575
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
24.5
20.9
52.6
26.3
52.6
26.3
52.6
26.3
52.6
26.3
52.6
26.3
30
71.4
35.7
123.6
71.4
59
NA
42.9
117.9
58.9
136
113
278
139
278
139
278
139
278
139
278
139
135
346
173
500
289
235
235
200
470
235
Part Winding Start
Max RLA
LRA
12.3
81.6
26.3
170
26.3
170
26.3
170
26.3
170
26.3
170
15
35.7
81
208
164
29.5
21.5
59
141
141
130
292
Winding Resistance
Line to Line (Ohms)
0.84
1.28
0.208
0.832
0.208
0.832
0.208
0.832
0.208
0.832
0.208
0.832
1.94
0.142
0.568
0.294
0.098
0.45
0.45
1.46
0.111
0.444
See Section F Introduction for more information.
FE25
Section_Fe.indd 25
3/4/2008 8:06:50 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DR1A3000-TXE
4DR1A3000-TXK
4DR1A3000-TXK
4DR1R28M0-FSD
4DR1R28M0-TSE
4DR1R28M0-TSK
4DR1R28M0-TSK
4DR3A200E-TSE
4DR3A200E-TSK
4DR3A200E-TSK
4DR3A200L-TSE
4DR3A200L-TSK
4DR3A200L-TSK
4DR3A270E-TSK
4DR3A270E-TSK
4DR3A270L-TSK
4DR3A270L-TSK
4DR3A3000-ES8
4DR3A3000-FSD
4DR3A3000-FXD
4DR3A3000-TSE
4DR3A3000-TSK
575
208/230
460
460
575
208/230
460
575
208/230
460
575
208/230
460
208/230
460
208/230
460
380
460
460
575
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
NA
NA
NA
59
42.9
117.9
58.9
30
66
33
30
66
33
94
55
94
55
71.4
45
NA
39.3
94
200
470
235
235
200
470
235
135
346
173
135
346
173
470
235
470
235
289
235
235
200
470
Part Winding Start
Max RLA
LRA
130
292
29.5
21.5
59
141
130
292
15
33
81
208
15
33
81
208
47
292
47
292
22.5
141
141
130
292
19.7
47
Winding Resistance
Line to Line (Ohms)
0.731
0.111
0.444
0.45
1.46
0.111
0.444
1.94
0.142
0.568
1.94
0.142
0.568
0.111
0.444
0.111
0.444
0.098
0.45
0.45
1.46
0.111
See Section F Introduction for more information.
FE26
Section_Fe.indd 26
3/4/2008 8:06:50 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DR3A3000-TSK
4DR3A3000-TXE
4DR3A3000-TXK
4DR3A3000-TXK
4DR3A300E-FSD
4DR3A300E-TSE
4DR3A300E-TSK
4DR3A300E-TSK
4DR3A300L-FSD
4DR3A300L-TSE
4DR3A300L-TSK
4DR3A300L-TSK
4DR3R19ME-TSK
4DR3R19ME-TSK
4DR3R28M0-ES8
4DR3R28M0-FSD
4DR3R28M0-TSE
4DR3R28M0-TSK
4DR3R28M0-TSK
4DR3R28ME-FSD
4DR3R28ME-TSE
4DR3R28ME-TSK
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
208/230
460
380
460
575
208/230
460
460
575
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
47
NA
NA
NA
45
39.3
94
55
45
39.3
94
55
66
33
71.4
45
39.3
94
47
45
39.3
94
235
200
470
235
235
200
470
235
235
200
470
235
346
173
289
235
200
470
235
235
200
470
Part Winding Start
Max RLA
LRA
130
292
22.5
19.7
47
141
130
292
22.5
19.7
47
141
130
292
33
208
22.5
19.7
47
141
130
292
22.5
19.7
47
141
130
292
Winding Resistance
Line to Line (Ohms)
0.444
0.731
0.111
0.444
0.45
1.46
0.111
0.444
0.45
1.46
0.111
0.444
0.142
0.568
0.098
0.45
1.46
0.111
0.444
0.45
1.46
0.111
See Section F Introduction for more information.
FE27
Section_Fe.indd 27
3/4/2008 8:06:51 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DR3R28ME-TSK
4DR3R28ML-FSD
4DR3R28ML-TSE
4DR3R28ML-TSK
4DR3R28ML-TSK
4DR8A200E-TSK
4DR8A200E-TSK
4DS1A2200-FSD
4DS1A2200-TSE
4DS1A2200-TSK
4DS1A2200-TSK
4DS3A2200-ES8
4DS3A2200-ES8
4DS3A2200-FSD
4DS3A2200-TSE
4DS3A2200-TSK
4DS3A2200-TSK
4DS3A220E-FSD
4DS3A220E-TSE
4DS3A220E-TSK
4DS3A220E-TSK
4DS3A220L-FSD
460
460
575
208/230
460
208/230
460
460
575
208/230
460
200/220
380
460
575
208/230
460
460
575
208/230
460
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
55
45
39.3
94
55
66
33
32.9
28.6
71.4
35.7
68.9
40
33.9
24.1
66
33
33.9
24.1
66
33
33.9
235
235
200
470
235
346
173
180
135
374
187
405
235
180
135
374
187
180
135
374
187
180
Part Winding Start
Max RLA
LRA
22.5
19.7
47
141
130
292
33
208
16.5
14.3
35.7
108
81
222
134
17
12.1
33
108
81
222
17
12.1
33
108
81
222
17
108
Winding Resistance
Line to Line (Ohms)
0.444
0.45
1.46
0.111
0.444
0.142
0.568
0.558
1.94
0.14
0.56
0.375
0.125
0.558
1.94
0.14
0.56
0.558
1.94
0.14
0.56
0.558
See Section F Introduction for more information.
FE28
Section_Fe.indd 28
3/4/2008 8:06:51 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DS3A220L-TSE
4DS3A220L-TSK
4DS3A220L-TSK
4DS3F76K0-FSD
4DS3F76K0-TSE
4DS3F76K0-TSK
4DS3F76K0-TSK
4DS3F76KE-FSD
4DS3F76KE-TSE
4DS3F76KE-TSK
4DS3F76KE-TSK
4DS3F76KL-FSD
4DS3F76KL-TSE
4DS3F76KL-TSK
4DS3F76KL-TSK
4DT1A2200-FSD
4DT1A2200-TSE
4DT1A2200-TSK
4DT1A2200-TSK
4DT1F76K0-TSK
4DT1F76K0-TSK
4DT3A2200-ES8
575
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
208/230
460
200/220
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
24.1
66
33
33.9
24.1
66
33
33.9
24.1
66
33
33.9
24.1
66
33
32.9
28.6
71.4
35.7
71.4
35.7
68.9
135
374
187
180
135
374
187
180
135
374
187
180
135
374
187
180
135
374
187
374
187
405
Part Winding Start
Max RLA
LRA
12.1
33
81
222
17
12.1
33
108
81
222
17
12.1
33
108
81
222
17
12.1
33
108
81
222
16.5
14.3
35.7
108
81
222
35.7
222
134
Winding Resistance
Line to Line (Ohms)
1.94
0.14
0.56
0.558
1.94
0.14
0.56
0.558
1.94
0.14
0.56
0.558
1.94
0.14
0.56
0.558
1.94
0.14
0.56
0.14
0.56
0.375
See Section F Introduction for more information.
FE29
Section_Fe.indd 29
3/4/2008 8:06:51 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DT3A2200-ES8
4DT3A2200-FSD
4DT3A2200-TSE
4DT3A2200-TSK
4DT3A2200-TSK
4DT3A220E-FSD
4DT3A220E-TSE
4DT3A220E-TSK
4DT3A220E-TSK
4DT3A220L-FSD
4DT3A220L-TSE
4DT3A220L-TSK
4DT3A220L-TSK
4DT3A2510-ESX
4DT3A2510-ESX
4DT3A251E-ESX
4DT3A251E-ESX
4DT3A251L-ESX
4DT3A251L-ESX
4DT3F76K0-ES8
4DT3F76K0-ES8
4DT3F76K0-FSD
380
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
220
380
220
380
220
380
200/220
380
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
40
33.9
24.1
66
33
33.9
24.1
66
33
33.9
24.1
66
33
72.1
41.9
89.3
49.6
89.3
49.6
68.9
40
33.9
235
180
135
374
187
180
135
374
187
180
135
374
187
405
235
405
235
405
235
405
235
180
Part Winding Start
Max RLA
LRA
17
12.1
33
108
81
222
17
12.1
33
108
81
222
17
12.1
33
108
81
222
134
134
134
134
17
108
Winding Resistance
Line to Line (Ohms)
0.125
0.558
1.94
0.14
0.56
0.558
1.94
0.14
0.56
0.558
1.94
0.14
0.56
0.375
0.125
0.375
0.125
0.375
0.125
0.375
0.125
0.558
See Section F Introduction for more information.
FE30
Section_Fe.indd 30
3/4/2008 8:06:52 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4DT3F76K0-TSE
4DT3F76K0-TSK
4DT3F76K0-TSK
4DT3F76KE-FSD
4DT3F76KE-TSE
4DT3F76KE-TSK
4DT3F76KE-TSK
4DT3F76KL-FSD
4DT3F76KL-TSE
4DT3F76KL-TSK
4DT3F76KL-TSK
4DT8A220E-TSE
4RA3-1000-TSE
4RA3-1000-TSK
4RA3-1000-TSK
4RA3-100A-TSK
4RA3-100A-TSK
4RA3-100L-TSK
4RA3-100L-TSK
4RA3-2000-ES8
4RA3-2000-ES8
4RA3-2000-FSD
575
208/230
460
460
575
208/230
460
460
575
208/230
460
575
575
208/230
460
208/230
460
208/230
460
200/220
380
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
24.1
66
33
33.9
24.1
66
33
33.9
24.1
66
33
24.1
19.8
54.9
27.4
54.9
27.4
54.9
27.4
68.4
38.9
32.4
135
374
187
180
135
374
187
180
135
374
187
135
106
240
120
240
120
240
120
335
189
135
Part Winding Start
Max RLA
LRA
12.1
33
81
222
17
12.1
33
108
81
222
17
12.1
33
108
81
222
12.1
81
27.4
140
27.4
140
27.4
140
113
16.2
82
Winding Resistance
Line to Line (Ohms)
1.94
0.14
0.56
0.558
1.94
0.14
0.56
0.558
1.94
0.14
0.56
1.94
1.6
0.259
1.036
0.259
1.036
0.259
1.036
0.483
0.161
0.757
See Section F Introduction for more information.
FE31
Section_Fe.indd 31
3/4/2008 8:06:52 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
4RA3-2000-TSE
4RA3-2000-TSK
4RA3-2000-TSK
4RA3-200A-TSK
4RA3-200A-TSK
4RA4-1000-TSE
4RA4-1000-TSK
4RA4-1000-TSK
4RA4-2000-TSE
4RA4-2000-TSK
4RA4-2000-TSK
4RA4-200A-TSK
4RA4-200A-TSK
4RA4-200L-TSK
4RA4-200L-TSK
4RE2-1000-TSE
4RE2-1000-TSK
4RE2-1000-TSK
4RE2-2000-ES8
4RE2-2000-ES8
4RE2-2000-FSD
4RE2-2000-TSE
Volts
PH
575
208/230
460
208/230
460
575
208/230
460
575
208/230
460
208/230
460
208/230
460
575
208/230
460
200/220
380
460
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
29.2
71.4
35.7
71.4
35.7
19.8
54.9
27.4
29.2
71.4
35.7
71.4
35.7
71.4
35.7
19.8
54.9
27.4
68.4
38.9
32.4
29.2
135
308
154
308
154
106
240
120
135
308
154
308
154
308
154
106
240
120
335
189
135
135
Part Winding Start
Max RLA
LRA
14.6
35.7
74
188
35.7
188
27.4
140
14.6
35.7
74
188
35.7
188
35.7
188
27.4
140
113
16.2
14.6
82
74
Winding Resistance
Line to Line (Ohms)
2.2
0.173
0.69
0.173
0.69
1.6
0.259
1.036
2.2
0.173
0.69
0.173
0.69
0.173
0.69
1.6
0.259
1.036
0.483
0.161
0.757
2.2
See Section F Introduction for more information.
FE32
Section_Fe.indd 32
3/4/2008 8:06:53 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4RE2-2000-TSK
4RE2-2000-TSK
4RE2-200A-FSD
4RE2-200A-TSK
4RE2-200A-TSK
4RE4-2000-TSK
4RE4-2000-TSK
4RE5-2000-TSK
4RE5-2000-TSK
4RH1-1500-TSE
4RH1-1500-TSK
4RH1-1500-TSK
4RH1-150A-TSK
4RH1-150A-TSK
4RH1-2500-ES8
4RH1-2500-ES8
4RH1-2500-FSD
4RH1-2500-TSE
4RH1-2500-TSK
4RH1-2500-TSK
4RH1-250A-FSD
4RH1-250A-TSK
208/230
460
460
208/230
460
208/230
460
208/230
460
575
208/230
460
208/230
460
200/220
380
460
575
208/230
460
460
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
71.4
35.7
32.4
71.4
35.7
71.4
35.7
71.4
35.7
24.1
63
31.5
63
31.5
99.1
59.9
45
34.9
88.6
44.3
45
88.6
308
154
135
308
154
308
154
308
154
113
278
139
278
139
438
251
165
160
428
214
165
428
Part Winding Start
Max RLA
LRA
35.7
188
16.2
35.7
82
188
35.7
188
35.7
188
31.5
170
31.5
170
142
22.5
17.4
44.3
100
113
250
22.5
44.3
100
250
Winding Resistance
Line to Line (Ohms)
0.173
0.69
0.757
0.173
0.69
0.173
0.69
0.173
0.69
1.255
0.208
0.832
0.208
0.832
0.345
0.115
0.575
1.76
0.132
0.528
0.575
0.132
See Section F Introduction for more information.
FE33
Section_Fe.indd 33
3/4/2008 8:06:53 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4RH1-250A-TSK
4RH1-250L-TSK
4RH1-250L-TSK
4RH2-1500-TSK
4RH2-1500-TSK
4RH5-1500-TSK
4RH5-1500-TSK
4RJ1-3000-ES8
4RJ1-3000-ES8
4RJ1-3000-FSD
4RJ1-3000-TSE
4RJ1-3000-TSK
4RJ1-3000-TSK
4RJ1-300A-FSD
4RJ1-300A-TSK
4RJ1-300A-TSK
4RJ2-3000-ES8
4RJ2-3000-ES8
4RJ2-3000-FSD
4RJ2-3000-TSE
4RJ2-3000-TSK
4RJ2-3000-TSK
460
208/230
460
208/230
460
208/230
460
200/220
380
460
575
208/230
460
460
208/230
460
200/220
380
460
575
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
44.3
88.6
44.3
63
31.5
63
31.5
119.3
68.4
59
42.1
96.4
50.7
59
96.4
50.7
119.3
68.4
59
42.1
96.4
50.7
214
428
214
278
139
278
139
500
289
200
200
470
235
200
470
235
500
289
200
200
470
235
Part Winding Start
Max RLA
LRA
44.3
250
31.5
170
31.5
170
164
29.5
21.1
51
121
130
292
29.5
51
121
292
164
29.5
21.1
51
121
130
292
Winding Resistance
Line to Line (Ohms)
0.528
0.132
0.528
0.208
0.832
0.208
0.832
0.294
0.098
0.475
1.46
0.108
0.43
0.475
0.108
0.43
0.294
0.098
0.475
1.46
0.108
0.43
See Section F Introduction for more information.
FE34
Section_Fe.indd 34
3/4/2008 8:06:53 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4RJ2-300A-TSK
4RJ2-300A-TSK
4RK2-1500-TSE
4RK2-1500-TSK
4RK2-1500-TSK
4RK2-2500-ES8
4RK2-2500-ES8
4RK2-2500-FSD
4RK2-2500-TSE
4RK2-2500-TSK
4RK2-2500-TSK
4RK2-250A-FSD
4RK2-250A-TSE
4RK2-250A-TSK
4RK2-250A-TSK
4RK5-2500-TSK
4RK5-2500-TSK
4RL1-1500-TSE
4RL1-1500-TSK
4RL1-1500-TSK
4RL1-150A-TSK
4RL1-150A-TSK
208/230
460
575
208/230
460
200/220
380
460
575
208/230
460
460
575
208/230
460
208/230
460
575
208/230
460
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
96.4
50.7
24.1
63
31.5
102.5
59.9
45
34.9
88.6
44.3
45
34.9
88.6
44.3
88.6
44.3
24.1
62.6
31.4
62.6
31.4
470
235
113
278
139
438
251
165
160
428
214
165
160
428
214
428
214
113
278
139
278
139
Part Winding Start
Max RLA
LRA
51
292
31.5
170
142
22.5
17.4
44.3
100
113
250
22.5
17.4
44.3
100
113
250
44.3
250
31.3
170
31.3
170
Winding Resistance
Line to Line (Ohms)
0.108
0.43
1.255
0.208
0.832
0.345
0.115
0.575
1.76
0.132
0.528
0.575
1.76
0.132
0.528
0.132
0.528
1.255
0.208
0.832
0.208
0.832
See Section F Introduction for more information.
FE35
Section_Fe.indd 35
3/4/2008 8:06:54 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4RL1-1900-TSU
4RL2-1500-TSE
4RL2-1500-TSK
4RL2-1500-TSK
4RL2-150A-TSK
4RL2-150A-TSK
4RL5-1900-TSU
4RR1-3000-ES8
4RR1-3000-ES8
4RR1-3000-FSD
4RR1-3000-TSE
4RR1-3000-TSK
4RR1-3000-TSK
4RR1-300A-FSD
4RR1-300A-TSK
4RR1-300A-TSK
4RR2-3000-ES8
4RR2-3000-ES8
4RR2-3000-FSD
4RR2-3000-TSE
4RR2-3000-TSK
4RR2-3000-TSK
200
575
208/230
460
208/230
460
200
200/220
380
460
575
208/230
460
460
208/230
460
200/220
380
460
575
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
NA
24.1
62.6
31.4
62.6
31.4
NA
119.3
68.4
59
42.1
101.4
50.7
59
101.4
50.7
119.3
68.4
59
42.1
101.4
50.7
350
113
278
139
278
139
350
500
289
200
200
470
235
200
470
235
500
289
200
200
470
235
Part Winding Start
Max RLA
LRA
32.5
205
31.3
170
31.3
170
32.5
205
164
29.5
21.1
51
121
130
292
29.5
51
121
292
164
29.5
21.1
51
121
130
292
Winding Resistance
Line to Line (Ohms)
0.133
1.255
0.208
0.832
0.208
0.832
0.133
0.294
0.098
0.475
1.46
0.108
0.43
0.475
0.108
0.43
0.294
0.098
0.475
1.46
0.108
0.43
See Section F Introduction for more information.
FE36
Section_Fe.indd 36
3/4/2008 8:06:54 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
4RR2-300A-TSK
4RR2-300A-TSK
6DB3A3000-FSD
6DB3A3000-TSE
6DB3A3000-TSK
6DB3A3000-TSK
6DB3A300E-FSD
6DB3A300E-TSE
6DB3A300E-TSK
6DB3A300E-TSK
6DB3A300L-FSD
6DB3A300L-TSE
6DB3A300L-TSK
6DB3A300L-TSK
6DB3R32M0-FSD
6DB3R32M0-TSE
6DB3R32M0-TSK
6DB3R32M0-TSK
6DB3R32ME-FSD
6DB3R32ME-TSE
6DB3R32ME-TSK
6DB3R32ME-TSK
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
101.4
50.7
50
40
105
52.5
50
40
134.3
67.1
50
40
134.3
67.1
50
40
105
52.5
50
40
134.3
67.1
470
235
260
230
565
283
260
230
565
283
260
230
565
283
260
230
565
283
260
230
565
283
Part Winding Start
Max RLA
LRA
51
292
25
20
52.5
156
138
340
25
20
52.5
156
138
340
25
20
52.5
156
138
340
25
20
52.5
156
138
340
25
20
52.5
156
138
340
Winding Resistance
Line to Line (Ohms)
0.108
0.43
0.39
1.16
0.087
0.348
0.39
1.16
0.087
0.348
0.39
1.16
0.087
0.348
0.39
1.16
0.087
0.348
0.39
1.16
0.087
0.348
See Section F Introduction for more information.
FE37
Section_Fe.indd 37
3/4/2008 8:06:54 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DB3R32ML-FSD
6DB3R32ML-TSE
6DB3R32ML-TSK
6DB3R32ML-TSK
6DC1A2700-TSE
6DC1A2700-TSK
6DC1A2700-TSK
6DC3A2700-ES8
6DC3A2700-ES8
6DC3A2700-FSD
6DC3A2700-TSE
6DC3A2700-TSK
6DC3A2700-TSK
6DC3A270E-FSD
6DC3A270E-TSE
6DC3A270E-TSK
6DC3A270E-TSK
6DC3A270L-FSD
6DC3A270L-TSE
6DC3A270L-TSK
6DC3A270L-TSK
6DC3F93K0-FSD
460
575
208/230
460
575
208/230
460
200/220
380
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
50
40
134.3
67.1
35
89.3
44.6
82.5
47.9
41.6
32.5
80.7
40.4
41.6
32.5
80.7
40.4
41.6
32.5
80.7
40.4
41.6
260
230
565
283
172
450
225
445
260
218
172
450
225
218
172
450
225
218
172
450
225
218
Part Winding Start
Max RLA
LRA
25
20
52.5
156
138
340
17.5
44.7
103
263
141
20.8
16.3
40.4
131
103
263
20.8
16.3
40.4
131
103
263
20.8
16.3
40.4
131
103
263
20.8
131
Winding Resistance
Line to Line (Ohms)
0.39
1.16
0.087
0.348
1.538
0.114
0.456
0.336
0.112
0.457
1.538
0.114
0.456
0.457
1.538
0.114
0.456
0.457
1.538
0.114
0.456
0.457
See Section F Introduction for more information.
FE38
Section_Fe.indd 38
3/4/2008 8:06:55 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DC3F93K0-TSE
6DC3F93K0-TSK
6DC3F93K0-TSK
6DC3F93KE-FSD
6DC3F93KE-TSE
6DC3F93KE-TSK
6DC3F93KE-TSK
6DC3F93KL-FSD
6DC3F93KL-TSE
6DC3F93KL-TSK
6DC3F93KL-TSK
6DD1A2700-FSD
6DD1A2700-TSK
6DD1A2700-TSK
6DD3A2700-ES8
6DD3A2700-ES8
6DD3A2700-FSD
6DD3A2700-TSE
6DD3A2700-TSK
6DD3A2700-TSK
6DD3A270E-FSD
6DD3A270E-TSE
575
208/230
460
460
575
208/230
460
460
575
208/230
460
460
208/230
460
200/220
380
460
575
208/230
460
460
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
32.5
80.7
40.4
41.6
32.5
80.7
40.4
41.6
32.5
80.7
40.4
42.9
89.3
44.6
82.5
47.9
41.6
32.5
80.7
40.4
41.6
32.5
172
450
225
218
172
450
225
218
172
450
225
218
450
225
445
260
218
172
450
225
218
172
Part Winding Start
Max RLA
LRA
16.3
40.4
103
263
20.8
16.3
40.4
131
103
263
20.8
16.3
40.4
131
103
263
21.5
44.7
131
263
141
20.8
16.3
40.4
131
103
263
20.8
16.3
131
103
Winding Resistance
Line to Line (Ohms)
1.538
0.114
0.456
0.457
1.538
0.114
0.456
0.457
1.538
0.114
0.456
0.457
0.114
0.456
0.336
0.112
0.457
1.538
0.114
0.456
0.457
1.538
See Section F Introduction for more information.
FE39
Section_Fe.indd 39
3/4/2008 8:06:55 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DD3A270E-TSK
6DD3A270E-TSK
6DD3A270L-FSD
6DD3A270L-TSE
6DD3A270L-TSK
6DD3A270L-TSK
6DD3F93K0-FSD
6DD3F93K0-TSE
6DD3F93K0-TSK
6DD3F93K0-TSK
6DD3F93KE-FSD
6DD3F93KE-TSE
6DD3F93KE-TSK
6DD3F93KE-TSK
6DD3F93KL-FSD
6DD3F93KL-TSE
6DD3F93KL-TSK
6DD3F93KL-TSK
6DE1A3000-ES8
6DE1A3000-ES8
6DE1A3000-TSK
6DE1A3000-TSK
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
200/220
380
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
80.7
40.4
41.6
32.5
80.7
40.4
41.6
32.5
80.7
40.4
41.6
32.5
80.7
40.4
41.6
32.5
80.7
40.4
95.9
55.6
110.9
55.5
450
225
218
172
450
225
218
172
450
225
218
172
450
225
218
172
450
225
500
289
470
235
Part Winding Start
Max RLA
LRA
40.4
263
20.8
16.3
40.4
131
103
263
20.8
16.3
40.4
131
103
263
20.8
16.3
40.4
131
103
263
20.8
16.3
40.4
131
103
263
164
55.5
292
Winding Resistance
Line to Line (Ohms)
0.114
0.456
0.457
1.538
0.114
0.456
0.457
1.538
0.114
0.456
0.457
1.538
0.114
0.456
0.457
1.538
0.114
0.456
0.294
0.098
0.111
0.444
See Section F Introduction for more information.
FE40
Section_Fe.indd 40
3/4/2008 8:06:56 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DE3A3000-FSD
6DE3A3000-TSE
6DE3A3000-TSK
6DE3A3000-TSK
6DE3A300E-FSD
6DE3A300E-TSE
6DE3A300E-TSK
6DE3A300E-TSK
6DE3A300L-FSD
6DE3A300L-TSE
6DE3A300L-TSK
6DE3A300L-TSK
6DE3F11M0-FSD
6DE3F11M0-TSE
6DE3F11M0-TSK
6DE3F11M0-TSK
6DE3F11ME-FSD
6DE3F11ME-TSE
6DE3F11ME-TSK
6DE3F11ME-TSK
6DE3F11ML-FSD
6DE3F11ML-TSE
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
42.9
39.6
95.6
47.8
42.9
39.6
95.6
47.8
42.9
39.6
95.6
47.8
42.9
39.6
95.6
47.8
42.9
39.6
95.6
47.8
42.9
39.6
235
200
470
235
235
200
470
235
235
200
470
235
235
200
470
235
235
200
470
235
235
200
Part Winding Start
Max RLA
LRA
21.4
19.8
47.8
141
130
292
21.4
19.8
47.8
141
130
292
21.4
19.8
47.8
141
130
292
21.4
19.8
47.8
141
130
292
21.4
19.8
47.8
141
130
292
21.4
19.8
141
130
Winding Resistance
Line to Line (Ohms)
0.45
1.46
0.111
0.444
0.45
1.46
0.111
0.444
0.45
1.46
0.111
0.444
0.45
1.46
0.111
0.444
0.45
1.46
0.111
0.444
0.45
1.46
See Section F Introduction for more information.
FE41
Section_Fe.indd 41
3/4/2008 8:06:56 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DE3F11ML-TSK
6DE3F11ML-TSK
6DF1A3000-ES8
6DF1A3000-ES8
6DF1A3000-FSD
6DF1A3000-TSK
6DF1A3000-TSK
6DF3A3000-FSD
6DF3A3000-TSE
6DF3A3000-TSK
6DF3A3000-TSK
6DF3A300E-FSD
6DF3A300E-TSE
6DF3A300E-TSK
6DF3A300E-TSK
6DF3A300L-FSD
6DF3A300L-TSE
6DF3A300L-TSK
6DF3A300L-TSK
6DF3F11M0-FSD
6DF3F11M0-TSE
6DF3F11M0-TSK
208/230
460
200/220
380
460
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
95.6
47.8
95.9
55.6
53.6
110.9
55.5
42.9
39.6
95.6
47.8
42.9
39.6
95.6
47.8
42.9
39.6
95.6
47.8
42.9
39.6
95.6
470
235
500
289
235
470
235
235
200
470
235
235
200
470
235
235
200
470
235
235
200
470
Part Winding Start
Max RLA
LRA
47.8
292
164
26.8
55.5
141
292
21.4
19.8
47.8
141
130
292
21.4
19.8
47.8
141
130
292
21.4
19.8
47.8
141
130
292
21.4
19.8
47.8
141
130
292
Winding Resistance
Line to Line (Ohms)
0.111
0.444
0.294
0.098
0.45
0.111
0.444
0.45
1.46
0.111
0.444
0.45
1.46
0.111
0.444
0.45
1.46
0.111
0.444
0.45
1.46
0.111
See Section F Introduction for more information.
FE42
Section_Fe.indd 42
3/4/2008 8:06:56 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DF3F11M0-TSK
6DF3F11ME-FSD
6DF3F11ME-TSE
6DF3F11ME-TSK
6DF3F11ME-TSK
6DF3F11ML-FSD
6DF3F11ML-TSE
6DF3F11ML-TSK
6DF3F11ML-TSK
6DG3A3500-ES8
6DG3A3500-ES8
6DG3A3500-FSD
6DG3A3500-FSU
6DG3A3500-FXD
6DG3A3500-FXU
6DG3A3500-TSE
6DG3A3500-TSN
6DG3A3500-TSN
6DG3A3500-TXE
6DG3A3500-TXN
6DG3A3500-TXN
6DG3A350E-FSD
460
460
575
208/230
460
460
575
208/230
460
200/220
380
460
200
460
200
575
230
460
575
230
460
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
47.8
42.9
39.6
95.6
47.8
42.9
39.6
95.6
47.8
NA
NA
66
135
NA
NA
46
125
62.5
NA
NA
NA
66
235
235
200
470
235
235
200
470
235
633
365
315
650
315
650
245
594
297
245
594
297
315
Part Winding Start
Max RLA
LRA
21.4
19.8
47.8
141
130
292
21.4
19.8
47.8
141
130
292
212
33
67.5
23
62.5
195
400
195
400
152
340
152
340
33
195
Winding Resistance
Line to Line (Ohms)
0.444
0.45
1.46
0.111
0.444
0.45
1.46
0.111
0.444
0.225
0.075
0.32
0.069
0.32
0.069
1.016
0.085
0.34
0.508
0.085
0.34
0.32
See Section F Introduction for more information.
FE43
Section_Fe.indd 43
3/4/2008 8:06:57 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DG3A350E-FSU
6DG3A350E-TSE
6DG3A350E-TSN
6DG3A350E-TSN
6DG3A350L-FSD
6DG3A350L-FSU
6DG3A350L-TSE
6DG3A350L-TSN
6DG3A350L-TSN
6DG3R37M0-ES8
6DG3R37M0-ES8
6DG3R37M0-FSD
6DG3R37M0-FSU
6DG3R37M0-TSE
6DG3R37M0-TSN
6DG3R37M0-TSN
6DG3R37ME-FSD
6DG3R37ME-FSU
6DG3R37ME-TSE
6DG3R37ME-TSN
6DG3R37ME-TSN
6DG3R37ML-FSD
200
575
230
460
460
200
575
230
460
200/220
380
460
200
575
230
460
460
200
575
230
460
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
135
46
168.6
84.3
66
135
46
168.6
84.3
NA
NA
66
135
46
125
62.5
66
135
46
168.6
84.3
66
650
245
594
297
315
650
245
594
297
633
365
315
650
245
594
297
315
650
245
594
297
315
Part Winding Start
Max RLA
LRA
67.5
23
62.5
400
152
340
33
67.5
23
62.5
195
400
152
340
212
33
67.5
23
62.5
195
400
152
340
33
67.5
23
62.5
195
400
152
340
33
195
Winding Resistance
Line to Line (Ohms)
0.069
1.016
0.085
0.34
0.32
0.069
1.016
0.085
0.34
0.225
0.075
0.32
0.069
1.016
0.085
0.34
0.32
0.069
1.016
0.085
0.34
0.32
See Section F Introduction for more information.
FE44
Section_Fe.indd 44
3/4/2008 8:06:57 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DG3R37ML-FSU
6DG3R37ML-TSE
6DG3R37ML-TSN
6DG3R37ML-TSN
6DG8A3500-TSE
6DG8A3500-TSN
6DG8A3500-TSN
6DH1A2000-FSD
6DH1A2000-TSE
6DH1A2000-TSK
6DH1A2000-TSK
6DH1A3500-ES8
6DH1A3500-ES8
6DH1A3500-FSD
6DH1A3500-FXD
6DH1A3500-TSE
6DH1A3500-TSK
6DH1A3500-TSK
6DH1A3500-TXE
6DH1A3500-TXK
6DH1A3500-TXK
6DH1R35M0-ES8
200
575
230
460
575
230
460
460
575
208/230
460
200/220
380
460
460
575
208/230
460
575
208/230
460
200/220
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
135
46
168.6
84.3
46
125
62.5
39.3
30
75
37.5
146.7
84.1
67.5
NA
50
125
62.5
NA
NA
NA
146.7
650
245
594
297
245
594
297
173
135
346
173
633
365
260
260
230
565
283
230
565
283
633
Part Winding Start
Max RLA
LRA
67.5
23
62.5
400
152
340
23
62.5
152
340
19.7
15
37.5
104
81
208
212
33.8
25
62.5
156
156
138
340
138
340
212
Winding Resistance
Line to Line (Ohms)
0.069
1.016
0.085
0.34
1.016
0.085
0.34
0.603
1.94
0.142
0.568
0.225
0.075
0.4
0.4
1.076
0.088
0.352
0.538
0.088
0.352
0.225
See Section F Introduction for more information.
FE45
Section_Fe.indd 45
3/4/2008 8:06:57 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DH1R35M0-ES8
6DH1R35M0-FSD
6DH1R35M0-TSK
6DH1R35M0-TSK
6DH3A200E-TSE
6DH3A200E-TSK
6DH3A200E-TSK
6DH3A200L-TSE
6DH3A200L-TSK
6DH3A200L-TSK
6DH3A3500-FSD
6DH3A3500-TSE
6DH3A3500-TSK
6DH3A3500-TSK
6DH3A350E-FSD
6DH3A350E-TSE
6DH3A350E-TSK
6DH3A350E-TSK
6DH3A350L-FSD
6DH3A350L-TSE
6DH3A350L-TSK
6DH3A350L-TSK
380
460
208/230
460
575
208/230
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
84.1
67.5
125
62.5
30
75
37.5
30
75
37.5
62.6
42.5
125.1
62.6
62.6
42.5
147.1
73.6
62.6
42.5
147.1
73.6
365
260
565
283
135
346
173
135
346
173
260
230
565
283
260
230
565
283
260
230
565
283
Part Winding Start
Max RLA
LRA
33.8
62.5
156
340
15
37.5
81
208
15
37.5
81
208
31.3
21.3
62.6
156
138
340
31.3
21.3
62.6
156
138
340
31.3
21.3
62.6
156
138
340
Winding Resistance
Line to Line (Ohms)
0.075
0.4
0.088
0.352
1.94
0.142
0.568
1.94
0.142
0.568
0.39
1.16
0.087
0.348
0.39
1.16
0.087
0.348
0.39
1.16
0.087
0.348
See Section F Introduction for more information.
FE46
Section_Fe.indd 46
3/4/2008 8:06:58 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DH3R23ME-TSK
6DH3R23ME-TSK
6DH3R23ML-TSK
6DH3R23ML-TSK
6DH3R35M0-FSD
6DH3R35M0-TSE
6DH3R35M0-TSK
6DH3R35M0-TSK
6DH3R35ME-FSD
6DH3R35ME-TSE
6DH3R35ME-TSK
6DH3R35ME-TSK
6DH3R35ML-FSD
6DH3R35ML-TSE
6DH3R35ML-TSK
6DH3R35ML-TSK
6DJ1A4000-ES8
6DJ1A4000-ES8
6DJ1A4000-FSD
6DJ1A4000-FSU
6DJ1A4000-FXU
6DJ1A4000-TSE
208/230
460
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
200/220
380
460
200
200
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
75
37.5
75
37.5
62.6
42.5
125.1
62.6
62.6
42.5
147.1
73.6
62.6
42.5
147.1
73.6
164.1
96.9
69.3
170
NA
57.1
346
173
346
173
260
230
565
283
260
230
565
283
260
230
565
283
633
365
300
660
660
235
Part Winding Start
Max RLA
LRA
37.5
208
37.5
208
31.3
21.3
62.6
156
138
340
31.3
21.3
62.6
156
138
340
31.3
21.3
62.6
156
138
340
212
34.7
85
28.6
170
400
400
135
Winding Resistance
Line to Line (Ohms)
0.142
0.568
0.142
0.568
0.39
1.16
0.087
0.348
0.39
1.16
0.087
0.348
0.39
1.16
0.087
0.348
0.225
0.075
0.352
0.067
0.067
1.14
See Section F Introduction for more information.
FE47
Section_Fe.indd 47
3/4/2008 8:06:58 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DJ1A4000-TSN
6DJ1A4000-TSN
6DJ1A4000-TXE
6DJ1A4000-TXN
6DJ1A4000-TXN
6DJ1R40M0-FSD
6DJ1R40M0-TSE
6DJ1R40M0-TSN
6DJ1R40M0-TSN
6DJ3A300E-TSE
6DJ3A300E-TSK
6DJ3A300E-TSK
6DJ3A300L-TSE
6DJ3A300L-TSK
6DJ3A300L-TSK
6DJ3A4000-FSD
6DJ3A4000-FSU
6DJ3A4000-FXD
6DJ3A4000-FXU
6DJ3A4000-TSE
6DJ3A4000-TSN
6DJ3A4000-TSN
230
460
575
230
460
460
575
230
460
575
208/230
460
575
208/230
460
460
200
460
200
575
230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
141.4
70.7
NA
NA
NA
69.3
57.1
141.4
70.7
40
100
50
40
100
50
70
150
NA
NA
53.5
141.4
70.7
594
297
235
594
297
300
235
594
297
200
470
235
200
470
235
315
754
315
754
245
594
297
Part Winding Start
Max RLA
LRA
70.5
340
135
340
34.7
28.6
70.5
170
135
340
20
50
130
292
20
50
130
292
35
75
195
463
195
463
152
340
26.75
71
Winding Resistance
Line to Line (Ohms)
0.085
0.34
0.569
0.085
0.34
0.352
1.14
0.085
0.34
1.46
0.111
0.444
1.46
0.111
0.444
0.32
0.059
0.32
0.059
1.016
0.085
0.34
See Section F Introduction for more information.
FE48
Section_Fe.indd 48
3/4/2008 8:06:59 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DJ3A4000-TXE
6DJ3A4000-TXN
6DJ3A4000-TXN
6DJ3A400E-FSD
6DJ3A400E-FSU
6DJ3A400E-TSE
6DJ3A400E-TSN
6DJ3A400E-TSN
6DJ3A400L-FSD
6DJ3A400L-FSU
6DJ3A400L-TSE
6DJ3A400L-TSN
6DJ3A400L-TSN
6DJ3R28ME-TSE
6DJ3R28ME-TSK
6DJ3R28ME-TSK
6DJ3R28ML-TSE
6DJ3R28ML-TSK
6DJ3R28ML-TSK
6DJ3R40M0-FSD
6DJ3R40M0-FSU
6DJ3R40M0-TSE
575
230
460
460
200
575
230
460
460
200
575
230
460
575
208/230
460
575
208/230
460
460
200
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
NA
NA
NA
86.4
150
53.5
141.4
70.7
86.4
150
53.5
141.4
70.7
40
100
50
40
100
50
70
150
53.5
245
594
297
315
754
245
594
297
315
754
245
594
297
200
470
235
200
470
235
315
754
245
Part Winding Start
Max RLA
LRA
152
340
35
75
26.75
71
195
463
152
340
35
75
26.75
71
195
463
152
340
20
50
130
292
20
50
130
292
35
75
26.75
195
463
152
Winding Resistance
Line to Line (Ohms)
0.508
0.085
0.34
0.32
0.059
1.016
0.085
0.34
0.32
0.059
1.016
0.085
0.34
1.46
0.111
0.444
1.46
0.111
0.444
0.32
0.059
1.016
See Section F Introduction for more information.
FE49
Section_Fe.indd 49
3/4/2008 8:06:59 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DJ3R40M0-TSN
6DJ3R40M0-TSN
6DJ3R40ME-FSD
6DJ3R40ME-FSU
6DJ3R40ME-TSE
6DJ3R40ME-TSN
6DJ3R40ME-TSN
6DJ3R40ML-FSD
6DJ3R40ML-FSU
6DJ3R40ML-TSE
6DJ3R40ML-TSN
6DJ3R40ML-TSN
6DJGA4000-FSU
6DK1A2000-TSK
6DK1A2000-TSK
6DK1A3500-ES8
6DK1A3500-ES8
6DK1A3500-FSD
6DK1A3500-TSE
6DK1A3500-TSK
6DK1A3500-TSK
6DK1A3500-TXE
230
460
460
200
575
230
460
460
200
575
230
460
200
208/230
460
200/220
380
460
575
208/230
460
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
141.4
70.7
86.4
150
53.5
141.4
70.7
86.4
150
53.5
141.4
70.7
150
75
37.5
146.7
84.1
67.5
50
125
62.5
NA
594
297
315
754
245
594
297
315
754
245
594
297
754
346
173
633
365
260
230
565
283
230
Part Winding Start
Max RLA
LRA
71
340
35
75
26.75
71
195
463
152
340
35
75
26.75
71
195
463
152
340
75
37.5
463
208
212
33.8
25
62.5
156
138
340
138
Winding Resistance
Line to Line (Ohms)
0.085
0.34
0.32
0.059
1.016
0.085
0.34
0.32
0.059
1.016
0.085
0.34
0.059
0.142
0.568
0.225
0.075
0.4
1.076
0.088
0.352
0.538
See Section F Introduction for more information.
FE50
Section_Fe.indd 50
3/4/2008 8:06:59 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DK1A3500-TXK
6DK1A3500-TXK
6DK1A350E-TSK
6DK1A350E-TSK
6DK1R35M0-ES8
6DK1R35M0-ES8
6DK1R35M0-FSD
6DK1R35M0-TSE
6DK1R35M0-TSK
6DK1R35M0-TSK
6DK3A200E-TSE
6DK3A200E-TSK
6DK3A200E-TSK
6DK3A200L-TSE
6DK3A200L-TSK
6DK3A200L-TSK
6DK3A3500-FSD
6DK3A3500-TSE
6DK3A3500-TSK
6DK3A3500-TSK
6DK3A350E-FSD
6DK3A350E-TSE
208/230
460
208/230
460
200/220
380
460
575
208/230
460
575
208/230
460
575
208/230
460
460
575
208/230
460
460
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
NA
NA
125
62.5
146.7
84.1
67.5
50
125
62.5
30
75
37.5
30
75
37.5
62.6
42.5
125.1
62.6
62.6
42.5
565
283
565
283
633
365
260
230
565
283
135
346
173
135
346
173
260
230
565
283
260
230
Part Winding Start
Max RLA
LRA
340
62.5
340
212
33.8
25
62.5
156
138
340
15
37.5
81
208
15
37.5
81
208
31.3
21.3
62.6
156
138
340
31.3
21.3
156
138
Winding Resistance
Line to Line (Ohms)
0.088
0.352
0.088
0.352
0.225
0.075
0.4
1.076
0.088
0.352
1.94
0.142
0.568
1.94
0.142
0.568
0.39
1.16
0.087
0.348
0.39
1.16
See Section F Introduction for more information.
FE51
Section_Fe.indd 51
3/4/2008 8:07:00 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DK3A350E-TSK
6DK3A350E-TSK
6DK3A350L-FSD
6DK3A350L-TSE
6DK3A350L-TSK
6DK3A350L-TSK
6DK3R23ME-TSK
6DK3R23ME-TSK
6DK3R35M0-FSD
6DK3R35M0-TSE
6DK3R35M0-TSK
6DK3R35M0-TSK
6DK3R35ME-FSD
6DK3R35ME-TSE
6DK3R35ME-TSK
6DK3R35ME-TSK
6DK3R35ML-FSD
6DK3R35ML-TSE
6DK3R35ML-TSK
6DK3R35ML-TSK
6DK8A3500-TSK
6DK8A3500-TSK
208/230
460
460
575
208/230
460
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
147.1
73.6
62.6
42.5
147.1
73.6
75
37.5
62.6
42.5
125.1
62.6
62.6
42.5
147.1
73.6
62.6
42.5
147.1
73.6
125.1
62.6
565
283
260
230
565
283
346
173
260
230
565
283
260
230
565
283
260
230
565
283
565
283
Part Winding Start
Max RLA
LRA
62.6
340
31.3
21.3
62.6
156
138
340
37.5
208
31.3
21.3
62.6
156
138
340
31.3
21.3
62.6
156
138
340
31.3
21.3
62.6
156
138
340
62.6
340
Winding Resistance
Line to Line (Ohms)
0.087
0.348
0.39
1.16
0.087
0.348
0.142
0.568
0.39
1.16
0.087
0.348
0.39
1.16
0.087
0.348
0.39
1.16
0.087
0.348
0.087
0.348
See Section F Introduction for more information.
FE52
Section_Fe.indd 52
3/4/2008 8:07:00 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DL1A2700-FSD
6DL1A2700-TSE
6DL1A2700-TSK
6DL1A2700-TSK
6DL3A2700-ES8
6DL3A2700-ES8
6DL3A2700-FSD
6DL3A2700-TSE
6DL3A2700-TSK
6DL3A2700-TSK
6DL3A270E-FSD
6DL3A270E-TSE
6DL3A270E-TSK
6DL3A270E-TSK
6DL3A270L-FSD
6DL3A270L-TSE
6DL3A270L-TSK
6DL3A270L-TSK
6DL3F93K0-ES8
6DL3F93K0-ES8
6DL3F93K0-FSD
6DL3F93K0-TSE
460
575
208/230
460
200/220
380
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
200/220
380
460
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
42.9
35
89.3
44.6
82.5
47.9
41.6
32.5
80.7
40.4
41.6
32.5
80.7
40.4
41.6
32.5
80.7
40.4
82.5
47.9
41.6
32.5
218
172
450
225
445
260
218
172
450
225
218
172
450
225
218
172
450
225
445
260
218
172
Part Winding Start
Max RLA
LRA
21.5
17.5
44.7
131
103
263
141
20.8
16.3
40.4
131
103
263
20.8
16.3
40.4
131
103
263
20.8
16.3
40.4
131
103
263
141
20.8
16.3
131
103
Winding Resistance
Line to Line (Ohms)
0.457
1.538
0.114
0.456
0.336
0.112
0.457
1.538
0.114
0.456
0.457
1.538
0.114
0.456
0.457
1.538
0.114
0.456
0.336
0.112
0.457
1.538
See Section F Introduction for more information.
FE53
Section_Fe.indd 53
3/4/2008 8:07:00 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DL3F93K0-TSK
6DL3F93K0-TSK
6DL3F93KE-FSD
6DL3F93KE-TSE
6DL3F93KE-TSK
6DL3F93KE-TSK
6DL3F93KL-FSD
6DL3F93KL-TSE
6DL3F93KL-TSK
6DL3F93KL-TSK
6DL8A2700-TSK
6DL8A2700-TSK
6DM3A3500-ES8
6DM3A3500-ES8
6DM3A3500-FSD
6DM3A3500-FSU
6DM3A3500-FXD
6DM3A3500-FXU
6DM3A3500-TSE
6DM3A3500-TSN
6DM3A3500-TSN
6DM3A3500-TXE
208/230
460
460
575
208/230
460
460
575
208/230
460
208/230
460
200/220
380
460
200
460
200
575
230
460
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
80.7
40.4
41.6
32.5
80.7
40.4
41.6
32.5
80.7
40.4
80.7
40.4
NA
NA
66
135
NA
NA
46
125
62.5
NA
450
225
218
172
450
225
218
172
450
225
450
225
633
365
315
650
315
650
245
594
297
245
Part Winding Start
Max RLA
LRA
40.4
263
20.8
16.3
40.4
131
103
263
20.8
16.3
40.4
131
103
263
40.4
263
212
33
67.5
23
62.5
195
400
195
400
152
340
152
Winding Resistance
Line to Line (Ohms)
0.114
0.456
0.457
1.538
0.114
0.456
0.457
1.538
0.114
0.456
0.114
0.456
0.225
0.075
0.32
0.069
0.32
0.069
1.016
0.085
0.34
0.508
See Section F Introduction for more information.
FE54
Section_Fe.indd 54
3/4/2008 8:07:01 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DM3A3500-TXN
6DM3A3500-TXN
6DM3A350E-ES8
6DM3A350E-ES8
6DM3A350E-FSD
6DM3A350E-FSU
6DM3A350E-TSE
6DM3A350E-TSN
6DM3A350E-TSN
6DM3A350L-FSD
6DM3A350L-FSU
6DM3A350L-TSE
6DM3A350L-TSN
6DM3A350L-TSN
6DM3R37M0-FSD
6DM3R37M0-FSU
6DM3R37M0-TSE
6DM3R37M0-TSN
6DM3R37M0-TSN
6DM3R37ME-FSD
6DM3R37ME-FSU
6DM3R37ME-TSE
230
460
200/220
380
460
200
575
230
460
460
200
575
230
460
460
200
575
230
460
460
200
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
NA
NA
NA
NA
66
135
46
168.6
84.3
66
135
46
168.6
84.3
66
135
46
125
62.5
66
135
46
594
297
633
365
315
650
245
594
297
315
650
245
594
297
315
650
245
594
297
315
650
245
Part Winding Start
Max RLA
LRA
340
212
33
67.5
23
62.5
195
400
152
340
33
67.5
23
62.5
195
400
152
340
33
67.5
23
62.5
195
400
152
340
33
67.5
23
195
400
152
Winding Resistance
Line to Line (Ohms)
0.085
0.34
0.225
0.075
0.32
0.069
1.016
0.085
0.34
0.32
0.069
1.016
0.085
0.34
0.32
0.069
1.016
0.085
0.34
0.32
0.069
1.016
See Section F Introduction for more information.
FE55
Section_Fe.indd 55
3/4/2008 8:07:01 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DM3R37ME-TSN
6DM3R37ME-TSN
6DM3R37ML-FSD
6DM3R37ML-FSU
6DM3R37ML-TSE
6DM3R37ML-TSN
6DM3R37ML-TSN
6DN3A3500-ES8
6DN3A3500-ES8
6DN3A3500-FSD
6DN3A3500-FSU
6DN3A3500-FXD
6DN3A3500-FXU
6DN3A3500-TSE
6DN3A3500-TSN
6DN3A3500-TSN
6DN3A3500-TXE
6DN3A3500-TXN
6DN3A3500-TXN
6DN3A350E-ES8
6DN3A350E-ES8
6DN3A350E-FSD
230
460
460
200
575
230
460
200/220
380
460
200
460
200
575
230
460
575
230
460
200/220
380
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
168.6
84.3
66
135
46
168.6
84.3
NA
NA
66
135
NA
NA
46
125
62.5
NA
NA
NA
NA
NA
66
594
297
315
650
245
594
297
633
365
315
650
315
650
245
594
297
245
594
297
633
365
315
Part Winding Start
Max RLA
LRA
62.5
340
33
67.5
23
62.5
195
400
152
340
212
33
67.5
23
62.5
195
400
195
400
152
340
152
340
212
33
195
Winding Resistance
Line to Line (Ohms)
0.085
0.34
0.32
0.069
1.016
0.085
0.34
0.225
0.075
0.32
0.069
0.32
0.069
1.016
0.085
0.34
0.508
0.085
0.34
0.225
0.075
0.32
See Section F Introduction for more information.
FE56
Section_Fe.indd 56
3/4/2008 8:07:02 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DN3A350E-FSU
6DN3A350E-TSE
6DN3A350E-TSN
6DN3A350E-TSN
6DN3A350L-FSD
6DN3A350L-FSU
6DN3A350L-TSE
6DN3A350L-TSN
6DN3A350L-TSN
6DN3R37M0-FSD
6DN3R37M0-FSU
6DN3R37M0-TSE
6DN3R37M0-TSN
6DN3R37M0-TSN
6DN3R37ME-FSD
6DN3R37ME-FSU
6DN3R37ME-TSE
6DN3R37ME-TSN
6DN3R37ME-TSN
6DN3R37ML-FSD
6DN3R37ML-FSU
6DN3R37ML-TSE
200
575
230
460
460
200
575
230
460
460
200
575
230
460
460
200
575
230
460
460
200
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
135
46
168.6
84.3
66
135
46
168.6
84.3
66
135
46
125
62.5
66
135
46
168.6
84.3
66
135
46
650
245
594
297
315
650
245
594
297
315
650
245
594
297
315
650
245
594
297
315
650
245
Part Winding Start
Max RLA
LRA
67.5
23
62.5
400
152
340
33
67.5
23
62.5
195
400
152
340
33
67.5
23
62.5
195
400
152
340
33
67.5
23
62.5
195
400
152
340
33
67.5
23
195
400
152
Winding Resistance
Line to Line (Ohms)
0.069
1.016
0.085
0.34
0.32
0.069
1.016
0.085
0.34
0.32
0.069
1.016
0.085
0.34
0.32
0.069
1.016
0.085
0.34
0.32
0.069
1.016
See Section F Introduction for more information.
FE57
Section_Fe.indd 57
3/4/2008 8:07:02 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DN3R37ML-TSN
6DN3R37ML-TSN
6DP1A2000-TSK
6DP1A2000-TSK
6DP1A3500-ES8
6DP1A3500-ES8
6DP1A3500-FSD
6DP1A3500-FXD
6DP1A3500-TSE
6DP1A3500-TSK
6DP1A3500-TSK
6DP1A3500-TXE
6DP1A3500-TXK
6DP1A3500-TXK
6DP1A350E-TSK
6DP1A350E-TSK
6DP1R35M0-ES8
6DP1R35M0-ES8
6DP1R35M0-FSD
6DP1R35M0-TSE
6DP1R35M0-TSK
6DP1R35M0-TSK
230
460
208/230
460
200/220
380
460
460
575
208/230
460
575
208/230
460
208/230
460
200/220
380
460
575
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
168.6
84.3
75
37.5
146.7
84.1
67.5
NA
50
125
62.5
NA
NA
NA
125
62.5
146.7
84.1
67.5
50
125
62.5
594
297
346
173
633
365
260
260
230
565
283
230
565
283
565
283
633
365
260
230
565
283
Part Winding Start
Max RLA
LRA
62.5
340
37.5
208
212
33.8
25
62.5
156
156
138
340
138
340
62.5
340
212
33.8
25
62.5
156
138
340
Winding Resistance
Line to Line (Ohms)
0.085
0.34
0.142
0.568
0.225
0.075
0.4
0.4
1.076
0.088
0.352
0.538
0.088
0.352
0.088
0.352
0.225
0.075
0.4
1.076
0.088
0.352
See Section F Introduction for more information.
FE58
Section_Fe.indd 58
3/4/2008 8:07:02 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DP3A200E-TSE
6DP3A200E-TSK
6DP3A200E-TSK
6DP3A200E-TXK
6DP3A200E-TXK
6DP3A200L-TSE
6DP3A200L-TSK
6DP3A200L-TSK
6DP3A3500-FSD
6DP3A3500-TSE
6DP3A3500-TSK
6DP3A3500-TSK
6DP3A350E-FSD
6DP3A350E-TSE
6DP3A350E-TSK
6DP3A350E-TSK
6DP3A350L-FSD
6DP3A350L-TSE
6DP3A350L-TSK
6DP3A350L-TSK
6DP3R23ME-TSK
6DP3R23ME-TSK
575
208/230
460
208/230
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
30
75
37.5
NA
NA
30
75
37.5
62.6
42.5
125.1
62.6
62.6
42.5
147.1
73.6
62.6
42.5
147.1
73.6
75
37.5
135
346
173
346
173
135
346
173
260
230
565
283
260
230
565
283
260
230
565
283
346
173
Part Winding Start
Max RLA
LRA
15
37.5
81
208
208
15
37.5
81
208
31.3
21.3
62.6
156
138
340
31.3
21.3
62.6
156
138
340
31.3
21.3
62.6
156
138
340
37.5
208
Winding Resistance
Line to Line (Ohms)
1.94
0.142
0.568
0.142
0.568
1.94
0.142
0.568
0.39
1.16
0.087
0.348
0.39
1.16
0.087
0.348
0.39
1.16
0.087
0.348
0.142
0.568
See Section F Introduction for more information.
FE59
Section_Fe.indd 59
3/4/2008 8:07:03 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DP3R23ME-TXK
6DP3R23ME-TXK
6DP3R35M0-FSD
6DP3R35M0-TSE
6DP3R35M0-TSK
6DP3R35M0-TSK
6DP3R35ME-FSD
6DP3R35ME-TSE
6DP3R35ME-TSK
6DP3R35ME-TSK
6DP3R35ML-FSD
6DP3R35ML-TSE
6DP3R35ML-TSK
6DP3R35ML-TSK
6DP5A3500-FSD
6DP5A3500-TSE
6DR1A4000-ES8
6DR1A4000-ES8
6DR1A4000-FSD
6DR1A4000-FSU
6DR1A4000-FXU
6DR1A4000-TSE
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
200/220
380
460
200
200
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
NA
NA
62.6
42.5
125.1
62.6
62.6
42.5
147.1
73.6
62.6
42.5
147.1
73.6
67.5
50
164.1
96.9
69.3
170
NA
57.1
346
173
260
230
565
283
260
230
565
283
260
230
565
283
260
230
633
365
300
660
660
235
Part Winding Start
Max RLA
LRA
208
31.3
21.3
62.6
156
138
340
31.3
21.3
62.6
156
138
340
31.3
21.3
62.6
156
138
340
33.8
25
156
138
212
34.7
85
170
400
400
135
28.6
Winding Resistance
Line to Line (Ohms)
0.142
0.568
0.39
1.16
0.087
0.348
0.39
1.16
0.087
0.348
0.39
1.16
0.087
0.348
0.4
1.076
0.225
0.075
0.352
0.067
0.067
1.14
See Section F Introduction for more information.
FE60
Section_Fe.indd 60
3/4/2008 8:07:03 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DR1A4000-TSN
6DR1A4000-TSN
6DR1A4000-TXE
6DR1A4000-TXN
6DR1A4000-TXN
6DR1A400E-ES8
6DR1A400E-ES8
6DR1R40M0-ES8
6DR1R40M0-ES8
6DR1R40M0-FSD
6DR1R40M0-TSN
6DR1R40M0-TSN
6DR3A300E-TSE
6DR3A300E-TSK
6DR3A300E-TSK
6DR3A300L-TSE
6DR3A300L-TSK
6DR3A300L-TSK
6DR3A4000-FSD
6DR3A4000-FSU
6DR3A4000-FXD
6DR3A4000-FXU
230
460
575
230
460
200/220
380
200/220
380
460
230
460
575
208/230
460
575
208/230
460
460
200
460
200
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
141.4
70.7
NA
NA
NA
164.1
96.9
164.1
96.9
69.3
141.4
70.7
40
100
50
40
100
50
70
150
NA
NA
594
297
235
594
297
633
365
633
365
300
594
297
200
470
235
200
470
235
315
754
315
754
Part Winding Start
Max RLA
LRA
70.5
340
135
340
212
212
34.7
70.5
170
340
20
50
130
292
20
50
130
292
35
75
195
463
195
463
Winding Resistance
Line to Line (Ohms)
0.085
0.34
0.569
0.085
0.34
0.225
0.075
0.225
0.075
0.352
0.085
0.34
1.46
0.111
0.444
1.46
0.111
0.444
0.32
0.059
0.32
0.059
See Section F Introduction for more information.
FE61
Section_Fe.indd 61
3/4/2008 8:07:03 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DR3A4000-TSE
6DR3A4000-TSN
6DR3A4000-TSN
6DR3A4000-TXE
6DR3A4000-TXN
6DR3A4000-TXN
6DR3A400E-FSD
6DR3A400E-FSU
6DR3A400E-TSE
6DR3A400E-TSN
6DR3A400E-TSN
6DR3A400L-FSD
6DR3A400L-FSU
6DR3A400L-TSE
6DR3A400L-TSN
6DR3A400L-TSN
6DR3R28ME-TSK
6DR3R28ME-TSK
6DR3R28ML-TSK
6DR3R28ML-TSK
6DR3R40M0-FSD
6DR3R40M0-FSU
575
230
460
575
230
460
460
200
575
230
460
460
200
575
230
460
208/230
460
208/230
460
460
200
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
53.5
141.4
70.7
NA
NA
NA
86.4
150
53.5
141.4
70.7
86.4
150
53.5
141.4
70.7
100
50
100
50
70
150
245
594
297
245
594
297
315
754
245
594
297
315
754
245
594
297
470
235
470
235
315
754
Part Winding Start
Max RLA
LRA
26.75
71
152
340
152
340
35
75
26.75
71
195
463
152
340
35
75
26.75
71
195
463
152
340
50
292
50
292
35
75
195
463
Winding Resistance
Line to Line (Ohms)
1.016
0.085
0.34
0.508
0.085
0.34
0.32
0.059
1.016
0.085
0.34
0.32
0.059
1.016
0.085
0.34
0.111
0.444
0.111
0.444
0.32
0.059
See Section F Introduction for more information.
FE62
Section_Fe.indd 62
3/4/2008 8:07:04 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DR3R40M0-TSE
6DR3R40M0-TSN
6DR3R40M0-TSN
6DR3R40ME-FSD
6DR3R40ME-FSU
6DR3R40ME-TSE
6DR3R40ME-TSN
6DR3R40ME-TSN
6DR3R40ML-FSD
6DR3R40ML-FSU
6DR3R40ML-TSE
6DR3R40ML-TSN
6DR3R40ML-TSN
6DRGA4000-FSU
6DS1A4000-ES8
6DS1A4000-ES8
6DS1A4000-FSD
6DS1A4000-FSU
6DS1A4000-FXU
6DS1A4000-TSE
6DS1A4000-TSN
6DS1A4000-TSN
575
230
460
460
200
575
230
460
460
200
575
230
460
200
200/220
380
460
200
200
575
230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
53.5
141.4
70.7
86.4
150
53.5
141.4
70.7
86.4
150
53.5
141.4
70.7
150
164.1
96.9
69.3
170
NA
57.1
141.4
70.7
245
594
297
315
754
245
594
297
315
754
245
594
297
754
633
365
300
660
660
235
594
297
Part Winding Start
Max RLA
LRA
26.75
71
152
340
35
75
26.75
71
195
463
152
340
35
75
26.75
71
195
463
152
340
75
463
212
34.7
85
170
400
400
135
340
28.6
70.5
Winding Resistance
Line to Line (Ohms)
1.016
0.085
0.34
0.32
0.059
1.016
0.085
0.34
0.32
0.059
1.016
0.085
0.34
0.059
0.225
0.075
0.352
0.067
0.067
1.14
0.085
0.34
See Section F Introduction for more information.
FE63
Section_Fe.indd 63
3/4/2008 8:07:04 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DS1A4000-TXE
6DS1A4000-TXN
6DS1A4000-TXN
6DS1R40M0-ES8
6DS1R40M0-ES8
6DS1R40M0-FSD
6DS1R40M0-FSU
6DS1R40M0-TSE
6DS1R40M0-TSN
6DS1R40M0-TSN
6DS3A300E-TSE
6DS3A300E-TSK
6DS3A300E-TSK
6DS3A300L-TSE
6DS3A300L-TSK
6DS3A300L-TSK
6DS3A4000-FSD
6DS3A4000-FSU
6DS3A4000-FXD
6DS3A4000-FXU
6DS3A4000-TSE
6DS3A4000-TSN
575
230
460
200/220
380
460
200
575
230
460
575
208/230
460
575
208/230
460
460
200
460
200
575
230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
NA
NA
NA
164.1
96.9
69.3
170
57.1
141.4
70.7
40
100
50
40
100
50
70
150
NA
NA
53.5
141.4
235
594
297
633
365
300
660
235
594
297
200
470
235
200
470
235
315
754
315
754
245
594
Part Winding Start
Max RLA
LRA
135
340
212
34.7
85
28.6
70.5
170
400
135
340
20
50
130
292
20
50
130
292
35
75
195
463
195
463
152
340
26.75
71
Winding Resistance
Line to Line (Ohms)
0.569
0.085
0.34
0.225
0.075
0.352
0.067
1.14
0.085
0.34
1.46
0.111
0.444
1.46
0.111
0.444
0.32
0.059
0.32
0.059
1.016
0.085
See Section F Introduction for more information.
FE64
Section_Fe.indd 64
3/4/2008 8:07:05 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DS3A4000-TSN
6DS3A4000-TXE
6DS3A4000-TXN
6DS3A4000-TXN
6DS3A400E-FSD
6DS3A400E-FSU
6DS3A400E-TSE
6DS3A400E-TSN
6DS3A400E-TSN
6DS3A400L-FSD
6DS3A400L-FSU
6DS3A400L-TSE
6DS3A400L-TSN
6DS3A400L-TSN
6DS3R28ME-TSE
6DS3R28ME-TSK
6DS3R28ME-TSK
6DS3R28ML-TSE
6DS3R28ML-TSK
6DS3R28ML-TSK
6DS3R40M0-FSD
6DS3R40M0-FSU
460
575
230
460
460
200
575
230
460
460
200
575
230
460
575
208/230
460
575
208/230
460
460
200
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
70.7
NA
NA
NA
86.4
150
53.5
141.4
70.7
86.4
150
53.5
141.4
70.7
40
100
50
40
100
50
70
150
297
245
594
297
315
754
245
594
297
315
754
245
594
297
200
470
235
200
470
235
315
754
Part Winding Start
Max RLA
LRA
152
340
35
75
26.75
71
195
463
152
340
35
75
26.75
71
195
463
152
340
20
50
130
292
20
50
130
292
35
75
195
463
Winding Resistance
Line to Line (Ohms)
0.34
0.508
0.085
0.34
0.32
0.059
1.016
0.085
0.34
0.32
0.059
1.016
0.085
0.34
1.46
0.111
0.444
1.46
0.111
0.444
0.32
0.059
See Section F Introduction for more information.
FE65
Section_Fe.indd 65
3/4/2008 8:07:05 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DS3R40M0-TSE
6DS3R40M0-TSN
6DS3R40M0-TSN
6DS3R40ME-FSD
6DS3R40ME-FSU
6DS3R40ME-TSE
6DS3R40ME-TSN
6DS3R40ME-TSN
6DS3R40ML-FSD
6DS3R40ML-FSU
6DS3R40ML-TSE
6DS3R40ML-TSN
6DS3R40ML-TSN
6DSGA4000-FSU
6DT1A3000-ES8
6DT1A3000-ES8
6DT1A3000-FSD
6DT1A3000-TSE
6DT1A3000-TSK
6DT1A3000-TSK
6DT1F11M0-ES8
6DT1F11M0-ES8
575
230
460
460
200
575
230
460
460
200
575
230
460
200
200/220
380
460
575
208/230
460
200/220
380
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
53.5
141.4
70.7
86.4
150
53.5
141.4
70.7
86.4
150
53.5
141.4
70.7
150
95.9
55.6
53.6
40
110.9
55.5
95.9
55.6
245
594
297
315
754
245
594
297
315
754
245
594
297
754
500
289
235
200
470
235
500
289
Part Winding Start
Max RLA
LRA
26.75
71
152
340
35
75
26.75
71
195
463
152
340
35
75
26.75
71
195
463
152
340
75
463
164
26.8
20
55.5
141
130
292
164
Winding Resistance
Line to Line (Ohms)
1.016
0.085
0.34
0.32
0.059
1.016
0.085
0.34
0.32
0.059
1.016
0.085
0.34
0.059
0.294
0.098
0.45
1.46
0.111
0.444
0.294
0.098
See Section F Introduction for more information.
FE66
Section_Fe.indd 66
3/4/2008 8:07:06 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DT1F11M0-FSD
6DT3A3000-FSD
6DT3A3000-TSE
6DT3A3000-TSK
6DT3A3000-TSK
6DT3A300E-FSD
6DT3A300E-TSE
6DT3A300E-TSK
6DT3A300E-TSK
6DT3A300L-FSD
6DT3A300L-TSE
6DT3A300L-TSK
6DT3A300L-TSK
6DT3A3010-ESX
6DT3A3010-ESX
6DT3A301E-ESX
6DT3A301E-ESX
6DT3A301L-ESX
6DT3A301L-ESX
6DT3F11M0-FSD
6DT3F11M0-TSE
6DT3F11M0-TSK
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
200/220
380
200/220
380
200/220
380
460
575
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
53.6
42.9
39.6
95.6
47.8
42.9
39.6
95.6
47.8
42.9
39.6
95.6
47.8
94.6
68.8
94.6
81.7
94.6
81.7
42.9
39.6
95.6
235
235
200
470
235
235
200
470
235
235
200
470
235
500
289
500
289
500
289
235
200
470
Part Winding Start
Max RLA
LRA
26.8
21.4
19.8
47.8
141
141
130
292
21.4
19.8
47.8
141
130
292
21.4
19.8
47.8
141
130
292
21.4
19.8
47.8
141
130
292
Winding Resistance
Line to Line (Ohms)
0.45
0.45
1.46
0.111
0.444
0.45
1.46
0.111
0.444
0.45
1.46
0.111
0.444
0.294
0.098
0.294
0.098
0.294
0.098
0.45
1.46
0.111
See Section F Introduction for more information.
FE67
Section_Fe.indd 67
3/4/2008 8:07:06 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DT3F11M0-TSK
6DT3F11ME-FSD
6DT3F11ME-TSE
6DT3F11ME-TSK
6DT3F11ME-TSK
6DT3F11ML-FSD
6DT3F11ML-TSE
6DT3F11ML-TSK
6DT3F11ML-TSK
6DW3A3000-FSD
6DW3A3000-TSE
6DW3A3000-TSK
6DW3A3000-TSK
6DW3A300E-FSD
6DW3A300E-TSE
6DW3A300E-TSK
6DW3A300E-TSK
6DW3A300L-FSD
6DW3A300L-TSE
6DW3A300L-TSK
6DW3A300L-TSK
6DW3R32M0-FSD
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
47.8
42.9
39.6
95.6
47.8
42.9
39.6
95.6
47.8
50
40
105
52.5
50
40
134.3
67.1
50
40
134.3
67.1
50
235
235
200
470
235
235
200
470
235
260
230
565
283
260
230
565
283
260
230
565
283
260
Part Winding Start
Max RLA
LRA
21.4
19.8
47.8
141
130
292
21.4
19.8
47.8
141
130
292
25
20
52.5
156
138
340
25
20
52.5
156
138
340
25
20
52.5
156
138
340
25
156
Winding Resistance
Line to Line (Ohms)
0.444
0.45
1.46
0.111
0.444
0.45
1.46
0.111
0.444
0.39
1.16
0.087
0.348
0.39
1.16
0.087
0.348
0.39
1.16
0.087
0.348
0.39
See Section F Introduction for more information.
FE68
Section_Fe.indd 68
3/4/2008 8:07:06 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DW3R32M0-TSE
6DW3R32M0-TSK
6DW3R32M0-TSK
6DW3R32ME-FSD
6DW3R32ME-TSE
6DW3R32ME-TSK
6DW3R32ME-TSK
6DW3R32ML-FSD
6DW3R32ML-TSE
6DW3R32ML-TSK
6DW3R32ML-TSK
6DY3A3000-FSD
6DY3A3000-TSE
6DY3A3000-TSK
6DY3A3000-TSK
6DY3A300E-FSD
6DY3A300E-TSE
6DY3A300E-TSK
6DY3A300E-TSK
6DY3A300L-FSD
6DY3A300L-TSE
6DY3A300L-TSK
575
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
40
105
52.5
50
40
134.3
67.1
50
40
134.3
67.1
50
40
105
52.5
50
40
134.3
67.1
50
40
134.3
230
565
283
260
230
565
283
260
230
565
283
260
230
565
283
260
230
565
283
260
230
565
Part Winding Start
Max RLA
LRA
20
52.5
138
340
25
20
52.5
156
138
340
25
20
52.5
156
138
340
25
20
52.5
156
138
340
25
20
52.5
156
138
340
25
20
52.5
156
138
340
Winding Resistance
Line to Line (Ohms)
1.16
0.087
0.348
0.39
1.16
0.087
0.348
0.39
1.16
0.087
0.348
0.39
1.16
0.087
0.348
0.39
1.16
0.087
0.348
0.39
1.16
0.087
See Section F Introduction for more information.
FE69
Section_Fe.indd 69
3/4/2008 8:07:07 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6DY3A300L-TSK
6DY3R32M0-FSD
6DY3R32M0-TSE
6DY3R32M0-TSK
6DY3R32M0-TSK
6DY3R32ME-FSD
6DY3R32ME-TSE
6DY3R32ME-TSK
6DY3R32ME-TSK
6DY3R32ML-FSD
6DY3R32ML-TSE
6DY3R32ML-TSK
6DY3R32ML-TSK
6RA4-1000-TSE
6RA4-1000-TSK
6RA4-1000-TSK
6RA4-100A-TSK
6RA4-100A-TSK
6RA4-2000-FSD
6RA4-2000-TSE
6RA4-2000-TSK
6RA4-2000-TSK
460
460
575
208/230
460
460
575
208/230
460
460
575
208/230
460
575
208/230
460
208/230
460
460
575
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
67.1
50
40
105
52.5
50
40
134.3
67.1
50
40
134.3
67.1
17.5
43.6
21.8
43.6
21.8
38.9
28.2
67.4
33.7
283
260
230
565
283
260
230
565
283
260
230
565
283
106
240
120
240
120
135
135
308
154
Part Winding Start
Max RLA
LRA
25
20
52.5
156
138
340
25
20
52.5
156
138
340
25
20
52.5
156
138
340
21.8
140
21.8
140
19.4
14.1
33.7
82
74
188
Winding Resistance
Line to Line (Ohms)
0.348
0.39
1.16
0.087
0.348
0.39
1.16
0.087
0.348
0.39
1.16
0.087
0.348
1.6
0.259
1.036
0.259
1.036
0.757
2.2
0.173
0.69
See Section F Introduction for more information.
FE70
Section_Fe.indd 70
3/4/2008 8:07:07 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
6RA4-200A-TSK
6RA4-200A-TSK
6RA4-200L-TSK
6RA4-200L-TSK
6RA4-3000-ESX
6RA4-3000-ESX
6RA4-3000-FSD
6RA4-3000-TSE
6RA4-3000-TSK
6RA4-3000-TSK
6RA4-300A-TSK
6RA4-300A-TSK
6RA4-300L-TSK
6RA4-300L-TSK
6RA5-1000-TSK
6RA5-1000-TSK
6RA5-2000-TSK
6RA5-2000-TSK
6RB2-1000-TSK
6RB2-1000-TSK
6RB2-2000-FSD
6RB2-2000-TSE
Volts
PH
208/230
460
208/230
460
220
380
460
575
208/230
460
208/230
460
208/230
460
208/230
460
208/230
460
208/230
460
460
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
67.4
33.7
67.4
33.7
NA
NA
50.6
42.9
104.3
52.1
104.3
52.1
104.3
52.1
43.6
21.8
67.4
33.7
43.3
21.6
28.9
25.4
308
154
308
154
432
249
200
200
470
235
470
235
470
235
240
120
308
154
240
120
135
135
Part Winding Start
Max RLA
LRA
33.7
188
33.7
188
25.3
21.5
52.5
121
130
292
52.5
292
52.5
292
21.8
140
33.7
188
21.7
140
14.5
12.7
82
74
Winding Resistance
Line to Line (Ohms)
0.173
0.69
0.173
0.69
0.108
0.324
0.475
1.46
0.108
0.43
0.108
0.43
0.108
0.43
0.259
1.036
0.173
0.69
0.259
1.036
0.757
2.2
See Section F Introduction for more information.
FE71
Section_Fe.indd 71
3/4/2008 8:07:08 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
6RB2-2000-TSK
6RB2-2000-TSK
6RB2-200A-TSK
6RB2-200A-TSK
6RE2-2000-FSD
6RE2-2000-TSE
6RE2-2000-TSK
6RE2-2000-TSK
6RE2-200A-TSK
6RE2-200A-TSK
6RE2-3000-ESX
6RE2-3000-ESX
6RE2-3000-FSD
6RE2-3000-TSE
6RE2-3000-TSK
6RE2-3000-TSK
6RE2-300A-TSK
6RE2-300A-TSK
6RF5-2000-FSD
6RF5-2000-TSE
6RH1-2000-TSE
6RH1-2000-TSK
Volts
PH
208/230
460
208/230
460
460
575
208/230
460
208/230
460
220
380
460
575
208/230
460
208/230
460
460
575
575
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
61.4
30.7
61.4
30.7
38.9
26.8
65.4
32.5
65.4
32.5
NA
NA
50
42.9
104.3
52.1
104.3
52.1
38.9
28.2
28.8
72
308
154
308
154
135
135
308
154
308
154
432
249
200
200
470
235
470
235
135
135
135
308
Part Winding Start
Max RLA
LRA
30.7
188
30.7
188
19.4
14.1
33.7
82
74
188
33.7
188
25.3
21.5
52.5
121
130
292
52.5
292
19.4
14.1
14.4
36
82
74
74
188
Winding Resistance
Line to Line (Ohms)
0.173
0.69
0.173
0.69
0.757
2.2
0.173
0.69
0.173
0.69
0.108
0.324
0.475
1.46
0.108
0.43
0.108
0.43
0.757
2.2
2.2
0.174
See Section F Introduction for more information.
FE72
Section_Fe.indd 72
3/4/2008 8:07:08 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6RH1-2000-TSK
6RH1-200A-TSK
6RH1-200A-TSK
6RH1-3500-ES8
6RH1-3500-ES8
6RH1-3500-FSD
6RH1-3500-TSE
6RH1-3500-TSK
6RH1-3500-TSK
6RH1-350A-FSD
6RH1-350A-TSK
6RH1-350A-TSK
6RH5-2000-TSK
6RH5-2000-TSK
6RH5-3500-FSD
6RH5-3500-TSE
6RJ1-3000-FSD
6RJ1-4000-ES8
6RJ1-4000-ES8
6RJ1-4000-FSD
6RJ1-4000-FSU
6RJ1-4000-TSE
460
208/230
460
200/220
380
460
575
208/230
460
460
208/230
460
208/230
460
460
575
460
200/220
380
460
200
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
36
72
36
145.9
85.9
67.5
50.2
134.3
67.1
67.5
134.3
67.1
72
36
67.5
50.2
57.5
160
89.6
64.3
170
53.6
154
308
154
633
365
225
230
565
283
225
565
283
308
154
225
230
200
633
365
239
625
225
Part Winding Start
Max RLA
LRA
36
188
212
33.8
25.1
67.5
150
138
340
33.8
67.5
150
340
36
188
33.8
25.1
28.8
150
138
121
212
32.2
85
26.8
147
388
140
Winding Resistance
Line to Line (Ohms)
0.696
0.174
0.696
0.225
0.075
0.4
1.16
0.087
0.348
0.4
0.087
0.348
0.174
0.696
0.4
1.16
0.475
0.225
0.075
0.375
0.066
1.14
See Section F Introduction for more information.
FE73
Section_Fe.indd 73
3/4/2008 8:07:08 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
6RJ1-4000-TSN
6RJ1-4000-TSN
6RJ1-400A-FSD
6RJ1-400A-FSU
6RJ1-400A-TSN
6RJ1-400A-TSN
6RK2-2000-TSE
6RK2-2000-TSK
6RK2-2000-TSK
6RK2-3500-ES8
6RK2-3500-ES8
6RK2-3500-FSD
6RK2-3500-TSE
6RK2-3500-TSK
6RK2-3500-TSK
6RK2-350A-TSK
6RK2-350A-TSK
6RK5-3500-FSD
6RK5-3500-TSK
6RK5-3500-TSK
6RL1-2500-ES8
6RL1-2500-ES8
Volts
PH
230
460
460
200
230
460
575
208/230
460
200/220
380
460
575
208/230
460
208/230
460
460
208/230
460
200/220
380
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
141.4
70.7
64.3
170
141.4
70.7
28.8
72
36
145.9
82.7
67.5
50.2
134.3
67.1
134.3
67.1
67.5
134.3
67.1
102.3
59.3
594
297
239
625
594
297
135
308
154
633
365
225
230
565
283
565
283
225
565
283
438
251
Part Winding Start
Max RLA
LRA
71
340
32.2
85
71
147
388
340
14.4
36
74
188
212
33.8
25.1
67.5
150
138
340
67.5
340
33.8
67.5
150
340
142
Winding Resistance
Line to Line (Ohms)
0.085
0.34
0.375
0.066
0.085
0.34
2.2
0.174
0.696
0.225
0.075
0.4
1.16
0.087
0.348
0.087
0.348
0.4
0.087
0.348
0.345
0.115
See Section F Introduction for more information.
FE74
Section_Fe.indd 74
3/4/2008 8:07:09 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6RL1-2500-TSE
6RL1-2500-TSK
6RL1-2500-TSK
6RL1-250A-TSK
6RL1-250A-TSK
6RL1-250L-TSK
6RL1-250L-TSK
6RL5-2500-TSE
6RN2-2000-FSD
6RN2-2000-TSE
6RN2-2000-TSK
6RN2-2000-TSK
6RN2-200A-TSK
6RN2-200A-TSK
6RN2-3000-ESX
6RN2-3000-ESX
6RN2-3000-FSD
6RN2-3000-TSE
6RN2-3000-TSK
6RN2-3000-TSK
6RN2-300A-TSK
6RN2-300A-TSK
575
208/230
460
208/230
460
208/230
460
575
460
575
208/230
460
208/230
460
220
380
460
575
208/230
460
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
34.9
96.9
48.5
96.9
48.5
96.9
48.5
34.9
38.9
26.8
65.4
32.7
65.4
32.7
NA
NA
50
42.9
104.3
52.1
104.3
52.1
160
428
214
428
214
428
214
160
135
135
308
154
308
154
432
249
200
200
470
235
470
235
Part Winding Start
Max RLA
LRA
17.4
48.5
113
250
48.5
250
48.5
250
17.4
19.4
14.1
33.7
113
82
74
188
33.7
188
25.3
21.5
52.5
121
130
292
52.5
292
Winding Resistance
Line to Line (Ohms)
1.76
0.132
0.528
0.132
0.528
0.132
0.528
1.76
0.757
2.2
0.173
0.69
0.173
0.69
0.108
0.324
0.475
1.46
0.108
0.43
0.108
0.43
See Section F Introduction for more information.
FE75
Section_Fe.indd 75
3/4/2008 8:07:09 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6RN5-3000-TSK
6RN5-3000-TSK
6RP2-2000-TSE
6RP2-2000-TSK
6RP2-2000-TSK
6RP2-200A-TSK
6RP2-200A-TSK
6RP2-3500-ES8
6RP2-3500-ES8
6RP2-3500-FSD
6RP2-3500-TSE
6RP2-3500-TSK
6RP2-3500-TSK
6RP2-350A-FSD
6RP2-350A-TSK
6RP2-350A-TSK
6RP5-3500-FSD
6RP5-3500-TSK
6RP5-3500-TSK
6RR2-4000-ES8
6RR2-4000-ES8
6RR2-4000-FSD
208/230
460
575
208/230
460
208/230
460
200/220
380
460
575
208/230
460
460
208/230
460
460
208/230
460
200/220
380
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
104.3
52.1
28.8
72
36
72
36
145.9
82.7
67.5
50.2
134.3
67.1
67.5
134.3
67.1
67.5
134.3
67.1
160
89.6
62
470
235
135
308
154
308
154
633
365
225
230
565
283
225
565
283
225
565
283
633
365
239
Part Winding Start
Max RLA
LRA
52.5
292
14.4
36
74
188
36
188
212
33.8
25.1
67.5
150
138
340
33.8
67.5
150
340
33.8
67.5
150
340
212
32.2
147
Winding Resistance
Line to Line (Ohms)
0.108
0.43
2.2
0.174
0.696
0.174
0.696
0.225
0.075
0.4
1.16
0.087
0.348
0.4
0.087
0.348
0.4
0.087
0.348
0.225
0.075
0.375
See Section F Introduction for more information.
FE76
Section_Fe.indd 76
3/4/2008 8:07:10 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6RR2-4000-FSU
6RR2-4000-TSE
6RR2-4000-TSN
6RR2-4000-TSN
6RR2-400A-FSD
6RR2-400A-FSU
6RR2-400A-TSN
6RR2-400A-TSN
6RS2-4000-ES8
6RS2-4000-ES8
6RS2-4000-FSD
6RS2-4000-FSU
6RS2-4000-TSE
6RS2-4000-TSN
6RS2-4000-TSN
6RS2-400A-FSD
6RS2-400A-FSU
6RS2-400A-TSN
6RS2-400A-TSN
6RT1-3000-FSD
6RT1-3000-TSE
6RT1-3000-TSK
200
575
230
460
460
200
230
460
200/220
380
460
200
575
230
460
460
200
230
460
460
575
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
170
53.6
141.4
70.7
62
170
141.4
70.7
160
89.6
62
170
53.6
141.4
70.7
62
170
141.4
70.7
60.6
40
110.9
625
225
594
297
239
625
594
297
633
365
239
625
225
594
297
239
625
594
297
200
200
470
Part Winding Start
Max RLA
LRA
85
26.8
71
388
140
340
32.2
85
71
147
388
340
212
32.2
85
26.8
71
147
388
140
340
32.2
85
71
147
388
340
30
20
55.5
121
130
292
Winding Resistance
Line to Line (Ohms)
0.066
1.14
0.085
0.34
0.375
0.066
0.085
0.34
0.225
0.075
0.375
0.066
1.14
0.085
0.34
0.375
0.066
0.085
0.34
0.475
1.46
0.108
See Section F Introduction for more information.
FE77
Section_Fe.indd 77
3/4/2008 8:07:10 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
6RT1-3000-TSK
6RT1-300A-TSK
6RT1-300A-TSK
6RT1-300L-TSK
6RT1-300L-TSK
6TM1-2000-TSE
6TM1-2000-TSK
6TM1-2000-TSK
8DP1R56M0-FSD
8DP1R56M0-TS7
8DP1R56M0-TSE
8DP1R56M0-TSK
8DP1R56M0-TSK
8DP3R56M0-FSD
8DP3R56M0-TSE
8DP3R56M0-TSK
8DP3R56M0-TSK
8DP3R56ME-FSD
8DP3R56ME-TSE
8DP3R56ME-TSK
8DP3R56ME-TSK
8DP3R56ML-FSD
460
208/230
460
208/230
460
575
208/230
460
460
380
575
208/230
460
460
575
208/230
460
460
575
208/230
460
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
55.5
110.9
55.5
110.9
55.5
28.2
65.7
32.9
90.7
114
75
180
90
90.7
75
180
90
90.7
75
180
90
90.7
235
470
235
470
235
135
308
154
510
740
405
1070
535
510
405
1070
535
510
405
1070
535
510
Part Winding Start
Max RLA
LRA
55.5
292
55.5
292
14.1
32.9
74
188
45.5
330
37.5
90
262
654
45.5
37.5
90
330
262
654
45.5
37.5
90
330
262
654
45.5
330
Winding Resistance
Line to Line (Ohms)
0.43
0.108
0.43
0.108
0.43
2.2
0.174
0.696
0.147
0
0.456
0.039
0.156
0.147
0.456
0.039
0.156
0.147
0.456
0.039
0.156
0.147
See Section F Introduction for more information.
FE78
Section_Fe.indd 78
3/4/2008 8:07:10 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
8DP3R56ML-TSE
8DP3R56ML-TSK
8DP3R56ML-TSK
8DS1R67M0-FSD
8DS1R67M0-TS7
8DS1R67M0-TSE
8DS1R67M0-TSK
8DS1R67M0-TSK
8DS3R67M0-FSD
8DS3R67M0-TS7
8DS3R67M0-TSE
8DS3R67M0-TSK
8DS3R67M0-TSK
8DS3R67ME-FSD
8DS3R67ME-TS7
8DS3R67ME-TSE
8DS3R67ME-TSK
8DS3R67ME-TSK
8DS3R67ML-FSD
8DS3R67ML-TSE
8DS3R67ML-TSK
8DS3R67ML-TSK
575
208/230
460
460
380
575
208/230
460
460
380
575
208/230
460
460
380
575
208/230
460
460
575
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Across the Line
Max RLA LRA
75
180
90
96.4
130
80
224.3
112.1
96.4
130
80
224.3
112.1
96.4
130
80
224.3
112.1
96.4
80
224.3
112.1
405
1070
535
510
740
405
1070
535
510
740
405
1070
535
510
740
405
1070
535
510
405
1070
535
Part Winding Start
Max RLA
LRA
37.5
90
262
654
48.3
330
40
112
262
654
48.3
330
40
112
262
654
48.3
330
40
112
262
654
48.3
40
112
330
262
654
Winding Resistance
Line to Line (Ohms)
0.456
0.039
0.156
0.147
0
0.456
0.039
0.156
0.147
0
0.456
0.039
0.156
0.147
0
0.456
0.039
0.156
0.147
0.456
0.039
0.156
See Section F Introduction for more information.
FE79
Section_Fe.indd 79
3/4/2008 8:07:11 AM
Electrical Data - Copelametic Large Refrigerant-Cooled Compressors
Model
Volts
PH
9RS1-1015-TSU
9RS1-1505-TSC
9RS1-150A-TSC
9RS3-1015-TSU
9RT1-1505-TSC
MRH4-0760-FSC
200
208/230
208/230
200
208/230
230
3
3
3
3
3
3
Across the Line
Max RLA LRA
NA
56.4
56.4
NA
56.4
NA
203
284
284
203
284
130
Part Winding Start
Max RLA
LRA
16.3
85
Winding Resistance
Line to Line (Ohms)
0
0
0
0
0
0.41
See Section F Introduction for more information.
FE80
Section_Fe.indd 80
3/4/2008 8:07:11 AM
Electrical Data - Copeland Scroll®
Model
ZB10KCE-PFJ
ZB10KCE-PFV
ZB114KCE-TFD
ZB114KCE-TW5
ZB114KCE-TW7
ZB114KCE-TWD
ZB114KCE-TWE
ZB114KQ-TFD
ZB114KQ-TW5
ZB114KQ-TW7
ZB114KQ-TWD
ZB114KQ-TWE
ZB114KQE-TFD
ZB114KQE-TW5
ZB114KQE-TW7
ZB114KQE-TWD
ZB114KQE-TWE
ZB11KCE-PFJ
ZB11KCE-PFV
ZB11MA-TW7
ZB11MA-TWC
ZB11MA-TWD
ZB11MA-TWE
ZB11MC-TW7
ZB11MC-TWC
ZB11MC-TWD
Volts
PH
Max
RLA
LRA
265
208/230
460
200/230
380
460
575
460
200/230
380
460
575
460
200/230
380
460
575
265
208/230
380
208/230
460
575
380
208/230
460
1
1
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
1
1
3
3
3
3
3
3
3
8.2
10
28.6
65
42.9
32.1
25.7
27.9
58.6
35.7
28.6
23.6
28.6
65
42.9
32.1
25.7
8.6
10
36.4
53.6
26.4
23.6
27.9
51.6
24.3
38
41
179
340
196
173
132
179
340
196
173
132
179
340
196
173
132
39
45
239
425
187
148
239
425
187
Winding Resistance
Start or Line/Line
Run
3.4
2.73
0.833
0.226
0.56
0.833
1.268
0.833
0.226
0.56
0.833
1.268
0.833
0.226
0.56
0.833
1.268
3.24
2.27
0.52
0.19
0.72
1.08
0.52
0.19
0.72
2.16
1.77
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1.81
1.81
0
0
0
0
0
0
0
Run Cap PN
014-0064-07
014-0064-06
014-0064-07
014-0064-07
See Section F Introduction for more information.
FF1
Section_Ff.indd 1
3/4/2008 8:09:50 AM
Electrical Data - Copeland Scroll®
Model
ZB11MC-TWE
ZB11MCE-TW7
ZB11MCE-TWC
ZB11MCE-TWD
ZB11MCE-TWE
ZB13KCE-PFJ
ZB13KCE-PFV
ZB14KCE-PFJ
ZB14KCE-PFV
ZB15KC-PFJ
ZB15KC-PFV
ZB15KC-TF5
ZB15KC-TFD
ZB15KCE-PFJ
ZB15KCE-PFV
ZB15KCE-TF5
ZB15KCE-TFD
ZB15KQ-PFJ
ZB15KQ-PFV
ZB15KQ-TF5
ZB15KQ-TF7
ZB15KQ-TFD
ZB15KQE-PFJ
ZB15KQE-PFV
ZB15KQE-TF5
ZB15KQE-TF7
Volts
PH
Max
RLA
LRA
575
380
208/230
460
575
265
208/230
265
208/230
265
208/230
200/230
460
265
208/230
200/230
460
265
208/230
200/230
380
460
265
208/230
200/230
380
3
3
3
3
3
1
1
1
1
1
1
3
3
1
1
3
3
1
1
3
3
3
1
1
3
3
19.4
32.5
60
28.2
22.5
10
12.9
11.1
13.6
11.4
13.6
8.9
4.3
13.2
15.7
8.9
5
11.4
13.6
8.9
5
4.3
13.2
15.7
8.9
5.1
148
239
425
187
148
55
54
52
63
58
61
55
27
58
61
55
27
58
61
55
23
27
58
61
55
27
Winding Resistance
Start or Line/Line
Run
1.08
0.52
0.19
0.72
1.08
2.75
2.67
2.86
2.45
3.34
2.28
1.79
7.1
3.34
2.28
1.79
7.1
3.34
2.28
1.79
7.1
7.1
3.34
2.28
1.79
7.1
0
0
0
0
0
1.81
1.31
1.5
1.17
1.26
1.01
0
0
1.26
1.01
0
0
1.26
1.01
0
0
0
1.26
1.01
0
0
Run Cap PN
014-0064-25
014-0064-07
014-0064-25
014-0064-07
014-0064-08
014-0064-08
014-0064-08
014-0064-08
014-0064-08
014-0064-08
014-0064-08
014-0064-08
See Section F Introduction for more information.
FF2
Section_Ff.indd 2
3/4/2008 8:09:54 AM
Electrical Data - Copeland Scroll®
Model
Volts
PH
Max
RLA
LRA
ZB15KQE-TFD
ZB19KC-PFJ
ZB19KC-PFV
ZB19KC-TF5
ZB19KC-TFD
ZB19KCE-PFJ
ZB19KCE-PFV
ZB19KCE-TF5
ZB19KCE-TFD
ZB19KQ-PFJ
ZB19KQ-PFV
ZB19KQ-TF5
ZB19KQ-TFD
ZB19KQE-PFJ
ZB19KQE-PFV
ZB19KQE-TF5
ZB19KQE-TFD
ZB21KC-PFJ
ZB21KC-PFV
ZB21KC-TF5
ZB21KC-TFD
ZB21KCE-PFJ
ZB21KCE-PFV
ZB21KCE-TF5
ZB21KCE-TFD
ZB21KQ-PFJ
460
265
208/230
200/230
460
265
208/230
200/230
460
265
208/230
200/230
460
265
208/230
200/230
460
265
208/230
200/230
460
265
208/230
200/230
460
265
3
1
1
3
3
1
1
3
3
1
1
3
3
1
1
3
3
1
1
3
3
1
1
3
3
1
5
12.9
15.7
8.2
4.3
13.2
17.9
8.2
5
12.9
15
10
4.3
14.6
17.1
10
5
16.4
17.9
11.4
5.7
16.4
20.7
12.1
6.1
16.4
27
61
73
63
31
61
73
63
31
61
72.5
63
31
61
72.5
63
31
83
100
77
39
83
100
77
39
83
Winding Resistance
Start or Line/Line
Run
7.1
2.23
2.71
1.46
5.94
2.23
2.71
1.46
5.94
2.23
1.72
1.46
5.94
2.23
1.72
1.46
5.94
1.84
2.82
1.234
4.83
1.84
2.82
1.234
4.83
1.84
0
1.2
0.908
0
0
1.2
0.908
0
0
1.2
0.905
0
0
1.2
0.905
0
0
0.887
0.64
0
0
0.887
0.64
0
0
0.887
Run Cap PN
014-0064-15
014-0064-25
014-0064-15
014-0064-25
014-0064-15
014-0064-25
014-0064-15
014-0064-25
014-0064-16
014-0064-29
014-0064-16
014-0064-29
014-0064-29
See Section F Introduction for more information.
FF3
Section_Ff.indd 3
3/4/2008 8:09:54 AM
Electrical Data - Copeland Scroll®
Model
Volts
PH
Max
RLA
LRA
ZB21KQ-PFV
ZB21KQ-TF5
ZB21KQ-TF7
ZB21KQ-TFD
ZB21KQE-PFJ
ZB21KQE-PFV
ZB21KQE-TF5
ZB21KQE-TF7
ZB21KQE-TFD
ZB26KC-PFJ
ZB26KC-PFV
ZB26KC-TF5
ZB26KC-TFD
ZB26KCE-PFJ
ZB26KCE-PFV
ZB26KCE-TF5
ZB26KCE-TFD
ZB26KQ-PFJ
ZB26KQ-PFV
ZB26KQ-TF5
ZB26KQ-TFD
ZB26KQE-PFJ
ZB26KQE-PFV
ZB26KQE-TF5
ZB26KQE-TFD
ZB29KQ-PFJ
208/230
200/230
380
460
265
208/230
200/230
380
460
265
208/230
200/230
460
265
208/230
200/230
460
265
208/230
200/230
460
265
208/230
200/230
460
265
1
3
3
3
1
1
3
3
3
1
1
3
3
1
1
3
3
1
1
3
3
1
1
3
3
1
18.4
11.4
7.5
5.7
16.4
20.7
12.1
7.4
7.4
17.1
20.7
13.9
7.1
18.9
23.6
13.9
7.1
17.1
20.4
13.9
7.1
18.9
23.6
13.2
6.4
19.3
95
77
39
39
83
95
77
39
39
98
127
88
44
98
127
88
44
98
109
88
44
98
109
88
44
113
Winding Resistance
Start or Line/Line
Run
1.39
1.234
4.83
4.83
1.84
1.39
1.234
4.83
4.83
1.65
2.15
0.995
4.03
1.65
2.15
0.995
4.03
1.65
1.28
0.995
4.03
1.65
1.28
0.995
4.03
1.67
0.65
0
0
0
0.887
0.65
0
0
0
0.691
0.506
0
0
0.691
0.506
0
0
0.691
0.54
0
0
0.691
0.54
0
0
0.586
Run Cap PN
014-0064-29
014-0064-29
014-0064-29
014-0064-18
014-0064-26
014-0064-18
014-0064-26
014-0064-18
014-0064-26
014-0064-18
014-0064-26
014-0064-18
See Section F Introduction for more information.
FF4
Section_Ff.indd 4
3/4/2008 8:09:55 AM
Electrical Data - Copeland Scroll®
Model
Volts
PH
Max
RLA
LRA
ZB29KQ-PFV
ZB29KQ-TF5
ZB29KQ-TF7
ZB29KQ-TFD
ZB29KQE-PFJ
ZB29KQE-PFV
ZB29KQE-TF5
ZB29KQE-TF7
ZB29KQE-TFD
ZB30KC-PFV
ZB30KC-TF5
ZB30KC-TF7
ZB30KC-TFD
ZB30KC-TFE
ZB30KCE-PFV
ZB30KCE-TF5
ZB30KCE-TF7
ZB30KCE-TFD
ZB30KCE-TFE
ZB30KQ-PFV
ZB30KQ-TF5
ZB30KQ-TFD
ZB30KQE-PFV
ZB30KQE-TF5
ZB30KQE-TFD
ZB38KC-PFV
208/230
200/230
380
460
265
208/230
200/230
380
460
208/230
200/230
380
460
575
208/230
200/230
380
460
575
208/230
200/230
460
208/230
200/230
460
208/230
1
3
3
3
1
1
3
3
3
1
3
3
3
3
1
3
3
3
3
1
3
3
1
3
3
1
22.1
16.4
9.3
7.9
20
25
17.1
9.6
7.9
25
15
8.6
7.4
6.4
26.8
15.7
8.8
7.5
6.4
25
15
7.4
26.8
15.7
8.6
30.1
137
91
54
50
113
137
91
54
50
132
115
57
47.5
40
132
115
57
47.5
40
132
115
47.5
132
115
47.5
175
Winding Resistance
Start or Line/Line
Run
1.34
0.994
2.76
3.88
1.67
1.34
0.994
2.76
3.88
2.089
0.808
2.77
3.58
5.72
2.089
0.808
2.77
3.58
5.72
2.089
0.808
3.65
2.089
0.808
3.65
1.204
0.46
0
0
0
0.586
0.46
0
0
0
0.454
0
0
0
0
0.454
0
0
0
0
0.454
0
0
0.454
0
0
0.327
Run Cap PN
014-0064-18
014-0064-18
014-0064-18
014-0064-26
014-0064-26
014-0064-26
014-0064-26
014-0064-27
See Section F Introduction for more information.
FF5
Section_Ff.indd 5
3/4/2008 8:09:55 AM
Electrical Data - Copeland Scroll®
Model
Volts
PH
Max
RLA
LRA
ZB38KC-TF5
ZB38KC-TF7
ZB38KC-TFD
ZB38KC-TFE
ZB38KCE-PFV
ZB38KCE-TF5
ZB38KCE-TF7
ZB38KCE-TFD
ZB38KCE-TFE
ZB38KQ-PFV
ZB38KQ-TF5
ZB38KQ-TF7
ZB38KQ-TFD
ZB38KQE-PFV
ZB38KQE-TF5
ZB38KQE-TF7
ZB38KQE-TFD
ZB42KC-PFJ
ZB42KC-PFV
ZB42KCE-PFJ
ZB42KCE-PFV
ZB45KC-TF5
ZB45KC-TFD
ZB45KC-TFE
ZB45KCE-TF5
ZB45KCE-TFD
200/230
380
460
575
208/230
200/230
380
460
575
208/230
200/230
380
460
208/230
200/230
380
460
265
208/230
265
208/230
200/230
460
575
200/230
460
3
3
3
3
1
3
3
3
3
1
3
3
3
1
3
3
3
1
1
1
1
3
3
3
3
3
20.7
10.4
8.9
7.1
31.1
22.1
10.4
9.6
7.1
30.1
20.7
10.7
9.6
30.8
24
12.4
10
28.2
27.9
31.4
31.4
20.7
11.5
7.9
22.5
11.5
115
64
63
50
175
115
64
63
50
144
128
64
63
144
128
64
63
160
129
160
129
156
70
54
156
70
Winding Resistance
Start or Line/Line
Run
0.671
2.3
2.65
4.31
1.204
0.671
2.3
2.65
4.31
1.328
0.726
2.3
2.72
1.328
0.726
2.3
2.72
1.921
0.779
1.921
0.779
0.562
2.27
3.56
0.562
2.27
0
0
0
0
0.327
0
0
0
0
0.383
0
0
0
0.383
0
0
0
0.415
0.432
0.415
0.432
0
0
0
0
0
Run Cap PN
014-0064-27
014-0064-27
014-0064-27
014-0064-16
014-0064-16
014-0064-16
014-0064-16
See Section F Introduction for more information.
FF6
Section_Ff.indd 6
3/4/2008 8:09:55 AM
Electrical Data - Copeland Scroll®
Model
Volts
PH
Max
RLA
LRA
ZB45KCE-TFE
ZB45KQ-TF5
ZB45KQ-TF7
ZB45KQ-TFD
ZB45KQE-TF5
ZB45KQE-TF7
ZB45KQE-TFD
ZB48KQ-TF5
ZB48KQ-TF7
ZB48KQ-TFD
ZB48KQE-TF5
ZB48KQE-TFD
ZB50KC-TF5
ZB50KC-TF7
ZB50KC-TFD
ZB50KC-TFE
ZB50KCE-TF5
ZB50KCE-TF7
ZB50KCE-TFD
ZB50KCE-TFE
ZB50KQ-TF5
ZB50KQ-TF7
ZB50KQ-TFD
ZB50KQ-TFE
ZB50KQE-TF5
ZB50KQE-TF7
575
200/230
380
460
200/230
380
460
200/230
380
460
200/230
460
200/230
380
460
575
200/230
380
460
575
200/230
380
460
575
200/230
380
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
7.9
20.7
10.7
11.5
23.1
12.6
10.1
25
12.1
12.1
26
13.6
28.6
15.7
14.3
9.6
28.6
18.2
15
9.6
28.6
15.7
14.3
9.6
28.6
18.2
54
156
70
75
156
70
75
164
100
100
164
100
196
135
100
90
196
135
100
90
196
135
100
90
196
135
Winding Resistance
Start or Line/Line
Run
3.56
0.562
1.92
2.27
0.562
1.92
2.27
0.501
1.79
1.79
0.501
1.79
0.44
1.174
1.764
2.989
0.44
1.174
1.764
2.989
0.44
1.174
1.764
2.989
0.44
1.174
Run Cap PN
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
See Section F Introduction for more information.
FF7
Section_Ff.indd 7
3/4/2008 8:09:56 AM
Electrical Data - Copeland Scroll®
Model
ZB50KQE-TFD
ZB50KQE-TFE
ZB56KA-TW7
ZB56KA-TWC
ZB56KA-TWD
ZB56KA-TWE
ZB56KC-TW7
ZB56KC-TWC
ZB56KC-TWD
ZB56KC-TWE
ZB56KCE-TW7
ZB56KCE-TWC
ZB56KCE-TWD
ZB56KCE-TWE
ZB58KC-TF5
ZB58KC-TF7
ZB58KC-TFD
ZB58KC-TFE
ZB58KCE-TF5
ZB58KCE-TF7
ZB58KCE-TFD
ZB58KCE-TFE
ZB58KQ-TF5
ZB58KQ-TF7
ZB58KQ-TFD
ZB58KQ-TFE
Volts
PH
Max
RLA
LRA
460
575
380
208/230
460
575
380
208/230
460
575
380
208/230
460
575
200/230
380
460
575
200/230
380
460
575
200/230
380
460
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
15
9.6
16.6
26.4
13.9
10.1
16
25.8
13.5
9.9
18.6
30
15.7
9.9
32.1
16.7
16.4
12
32.1
17.1
16.4
12.9
32.1
16.7
16.4
12
100
90
112
189
99
74
112
189
99
74
112
189
99
74
195
123
95
80
195
123
95
80
195
123
95
80
Winding Resistance
Start or Line/Line
Run
1.764
2.989
1.03
0.37
1.41
2.3
1.03
0.37
1.41
2.3
1.03
0.37
1.41
2.3
0.4
1.051
1.799
2.55
0.4
1.051
1.799
2.55
0.4
1.051
1.799
2.55
Run Cap PN
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
See Section F Introduction for more information.
FF8
Section_Ff.indd 8
3/4/2008 8:09:56 AM
Electrical Data - Copeland Scroll®
Model
Volts
PH
Max
RLA
LRA
ZB58KQE-TF5
ZB58KQE-TF7
ZB58KQE-TFD
ZB58KQE-TFE
ZB66KC-TF5
ZB66KC-TF7
ZB66KC-TFD
ZB66KC-TFE
ZB66KCE-TF5
ZB66KCE-TF7
ZB66KCE-TFD
ZB66KCE-TFE
ZB66KQ-TF5
ZB66KQ-TF7
ZB66KQ-TFD
ZB66KQ-TFE
ZB66KQE-TF5
ZB66KQE-TF7
ZB66KQE-TFD
ZB66KQE-TFE
ZB68KA-TW7
ZB68KA-TWC
ZB68KA-TWD
ZB68KA-TWE
ZB75KA-TW7
ZB75KA-TWC
200/230
380
460
575
200/230
380
460
575
200/230
380
460
575
200/230
380
460
575
200/230
380
460
575
380
208/230
460
575
380
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
32.1
17.1
16.4
12.9
33.6
18.6
17.3
13.5
33.6
20.7
17.5
13.5
33.6
18.6
17.3
13.5
33.6
20.7
17.5
13.5
20.7
33.3
17
12.9
25.4
37.4
195
123
95
80
225
140
114
80
225
140
114
80
225
140
114
80
225
140
114
80
144
232
125
100
151
278
Winding Resistance
Start or Line/Line
Run
0.4
1.051
1.799
2.55
0.347
0.93
1.36
2.55
0.347
0.93
1.36
2.55
0.347
0.93
1.36
2.55
0.347
0.93
1.36
2.55
0.78
0.29
1.11
1.86
0.72
0.26
Run Cap PN
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
See Section F Introduction for more information.
FF9
Section_Ff.indd 9
3/4/2008 8:09:56 AM
Electrical Data - Copeland Scroll®
Model
ZB75KA-TWD
ZB75KA-TWE
ZB75KC-TW7
ZB75KC-TWC
ZB75KC-TWD
ZB75KC-TWE
ZB75KCE-TW7
ZB75KCE-TWC
ZB75KCE-TWD
ZB75KCE-TWE
ZB76KC-TF5
ZB76KC-TF7
ZB76KC-TFD
ZB76KC-TFE
ZB76KCE-TF5
ZB76KCE-TF7
ZB76KCE-TFD
ZB76KCE-TFE
ZB76KQ-TF5
ZB76KQ-TF7
ZB76KQ-TFD
ZB76KQ-TFE
ZB76KQE-TF5
ZB76KQE-TF7
ZB76KQE-TFD
ZB76KQE-TFE
Volts
PH
Max
RLA
LRA
460
575
380
208/230
460
575
380
208/230
460
575
200/230
380
460
575
200/230
380
460
575
200/230
380
460
575
200/230
380
460
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
18.4
15.2
20.6
37.5
18.1
13.9
23.9
43.6
21.1
16.1
41.4
23.6
19.2
13.8
41.4
23.6
20
13.8
41.4
23.6
19.2
13.8
41.4
23.6
20
13.8
127
100
151
278
127
100
151
278
127
100
239
145
125
80
239
145
125
80
239
145
125
80
239
145
125
80
Winding Resistance
Start or Line/Line
Run
1.02
1.7
0.72
0.26
1.02
1.7
0.72
0.26
1.02
1.7
0.306
0.85
1.227
2.55
0.306
0.85
1.227
2.55
0.306
0.85
1.227
2.55
0.306
0.85
1.227
2.55
Run Cap PN
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
See Section F Introduction for more information.
FF10
Section_Ff.indd 10
3/4/2008 8:09:57 AM
Electrical Data - Copeland Scroll®
Model
ZB88KC-TF5
ZB88KC-TF7
ZB88KC-TFD
ZB88KC-TFE
ZB88KCE-TF5
ZB88KCE-TF7
ZB88KCE-TFD
ZB88KCE-TFE
ZB88KQ-TF5
ZB88KQ-TF7
ZB88KQ-TFD
ZB88KQ-TFE
ZB88KQE-TF5
ZB88KQE-TF7
ZB88KQE-TFD
ZB88KQE-TFE
ZB92KA-TW7
ZB92KA-TWC
ZB92KA-TWD
ZB92KA-TWE
ZB92KC-TW7
ZB92KC-TWC
ZB92KC-TWD
ZB92KC-TWE
ZB92KCE-TW7
ZB92KCE-TWC
Volts
PH
Max
RLA
LRA
200/230
380
460
575
200/230
380
460
575
200/230
380
460
575
200/230
380
460
575
380
208/230
460
575
380
208/230
460
575
380
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
47.1
24.4
19.6
15.9
47.1
24.4
20.7
15.9
47.1
24.4
20.7
15.9
47.1
24.4
20.7
15.9
27.9
45.7
24.3
19.3
24.3
45.4
21.5
17.2
28.2
52.9
245
145
125
100
245
145
125
100
245
145
125
100
245
145
125
100
195
350
158
125
195
350
158
125
195
350
Winding Resistance
Start or Line/Line
Run
0.282
0.85
1.227
1.87
0.282
0.85
1.227
1.87
0.282
0.85
1.227
1.87
0.282
0.85
1.227
1.87
0.57
0.22
0.83
1.28
0.57
0.22
0.83
1.28
0.57
0.22
Run Cap PN
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
See Section F Introduction for more information.
FF11
Section_Ff.indd 11
3/4/2008 8:09:57 AM
Electrical Data - Copeland Scroll®
Model
ZB92KCE-TWD
ZB92KCE-TWE
ZB95KCE-TFD
ZB95KCE-TW5
ZB95KCE-TW7
ZB95KCE-TWD
ZB95KCE-TWE
ZB95KQ-TFD
ZB95KQ-TW5
ZB95KQ-TW7
ZB95KQ-TWD
ZB95KQ-TWE
ZB95KQE-TFD
ZB95KQE-TW5
ZB95KQE-TW7
ZB95KQE-TWD
ZB95KQE-TWE
ZBD30KC-TF5
ZBD30KC-TF7
ZBD30KC-TFD
ZBD30KCE-TF5
ZBD30KCE-TFD
ZBD45KC-TF5
ZBD45KC-TF7
ZBD45KC-TFD
ZBD45KCE-TF5
Volts
PH
Max
RLA
LRA
460
575
460
200/230
380
460
575
460
200/230
380
460
575
460
200/230
380
460
575
200/230
380
460
200/230
460
200/230
380
460
200/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
25
20
26.4
61.4
35
31.4
22.9
25
53.6
28.6
24.3
20.7
26.4
61.4
35
31.4
22.9
15
8
7.4
15.7
7.4
20.7
12.5
10
22.5
158
125
150
300
139
150
109
150
300
139
150
109
150
300
139
150
109
99
57
47.5
99
47.5
156
70
70
156
Winding Resistance
Start or Line/Line
Run
0.83
1.28
1.1
0.227
0.853
1.108
1.518
1.1
0.227
0.853
1.108
1.518
1.1
0.227
0.853
1.108
1.518
0.911
2.78
3.64
0.911
3.64
0.562
1.92
2.27
0.562
Run Cap PN
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
See Section F Introduction for more information.
FF12
Section_Ff.indd 12
3/4/2008 8:09:58 AM
Electrical Data - Copeland Scroll®
Model
ZBD45KCE-TFD
ZBH30KJE-TF5
ZBH30KJE-TF7
ZBH30KJE-TFD
ZBH30KJE-TFE
ZBH38KJE-TF5
ZBH38KJE-TF7
ZBH38KJE-TFD
ZBH45KJE-TF5
ZBH45KJE-TF7
ZBH45KJE-TFD
ZC40C1G-TF5
ZC40C1G-TFD
ZC60C1G-TF5
ZC60C1G-TFD
ZCH22C1G-PFJ
ZCH22C1G-PFV
ZCH48C2G-TF5
ZCH48C2G-TFD
ZCH68C1G-TF5
ZCH68C1G-TFD
ZCH68C2G-TFD
ZCH72C2G-TF5
ZCH72C2G-TFD
ZCH81C2G-TF5
ZCH81C2G-TFD
Volts
PH
Max
RLA
LRA
460
200/230
380
460
575
200/230
380
460
200/230
380
460
200/230
460
200/230
460
265
208/230
200/230
460
200/230
460
460
200/230
460
200/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
1
1
3
3
3
3
3
3
3
3
3
10
15
8.2
8.2
6.4
21.4
11.4
9.6
23.9
12.9
9.3
12.9
6.9
21.4
8.9
10.7
12.9
16.4
7.9
24.3
10
10
22.9
10
23.6
13.6
70
99
57
49.5
40
123
64
62
156
70
70
108
47.5
156
70
47
47
91
50
164
75
75
156
75
164
100
Winding Resistance
Start or Line/Line
Run
2.27
0.911
0.911
3.64
5.72
0.686
0.686
2.75
0.501
2.27
2.27
0.803
3.65
0.501
2.27
2.85
2.06
0.994
3.88
0.501
2.27
2.27
0.501
2.27
0.501
1.79
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1.62
1.18
0
0
0
0
0
0
0
0
0
Run Cap PN
014-0064-14
014-0064-25
See Section F Introduction for more information.
FF13
Section_Ff.indd 13
3/4/2008 8:09:58 AM
Electrical Data - Copeland Scroll®
Model
ZCH94C1G-TF5
ZCH94C1G-TFD
ZF06K4-PFV
ZF06K4-TF5
ZF06K4-TFD
ZF06K4E-PFV
ZF06K4E-TF5
ZF06K4E-TFD
ZF08K4-PFV
ZF08K4-TF5
ZF08K4-TFD
ZF08K4E-PFV
ZF08K4E-TF5
ZF08K4E-TFD
ZF09K4-PFV
ZF09K4-TF5
ZF09K4-TFD
ZF09K4-TFE
ZF09K4E-PFV
ZF09K4E-TF5
ZF09K4E-TFD
ZF09K4E-TFE
ZF11K4-PFV
ZF11K4-TF5
ZF11K4-TFD
ZF11K4E-PFV
Volts
PH
Max
RLA
LRA
200/230
460
208/230
200/230
460
208/230
200/230
460
208/230
200/230
460
208/230
200/230
460
208/230
200/230
460
575
208/230
200/230
460
575
208/230
200/230
460
208/230
3
3
1
3
3
1
3
3
1
3
3
1
3
3
1
3
3
3
1
3
3
3
1
3
3
1
NA
NA
13.6
7.9
3.6
13.6
9.3
4.3
16.4
7.9
3.9
16.4
9.6
5
17.9
10
5
4.3
16.4
9.6
5.7
4.3
20.7
12.5
6.4
20.7
195
95
61
55
27
61
55
27
73
63
31
73
63
31
88
77
39
31
88
77
39
31
109
88
44
109
Winding Resistance
Start or Line/Line
Run
1.979
1.799
2.28
1.79
7.1
2.28
1.79
7.1
1.72
1.46
5.94
1.72
1.46
5.94
1.46
1.234
4.83
7.89
1.46
1.234
4.83
7.89
1.28
0.995
4.03
1.28
0.553
0
1.01
0
0
1.01
0
0
0.833
0
0
0.833
0
0
0.691
0
0
0
0.691
0
0
0
0.54
0
0
0.54
Run Cap PN
014-0064-08
014-0064-08
014-0064-25
014-0064-25
014-0064-29
014-0064-29
014-0064-26
014-0064-26
See Section F Introduction for more information.
FF14
Section_Ff.indd 14
3/4/2008 8:09:58 AM
Electrical Data - Copeland Scroll®
Model
Volts
PH
Max
RLA
LRA
ZF11K4E-TF5
ZF11K4E-TFD
ZF11K4E-TFE
ZF13K4-TF5
ZF13K4-TF7
ZF13K4-TFD
ZF13K4E-PFV
ZF13K4E-TF5
ZF13K4E-TF7
ZF13K4E-TFD
ZF13K4E-TFE
ZF13KVE-TF5
ZF13KVE-TF7
ZF13KVE-TFD
ZF13KVE-TFE
ZF15K4-TF5
ZF15K4-TF7
ZF15K4-TFD
ZF15K4E-PFV
ZF15K4E-TF5
ZF15K4E-TF7
ZF15K4E-TFD
ZF15K4E-TFE
ZF18K4-TF5
ZF18K4-TF7
ZF18K4-TFD
200/230
460
575
200/230
380
460
208/230
200/230
380
460
575
200/230
380
460
575
200/230
380
460
208/230
200/230
380
460
575
200/230
380
460
3
3
3
3
3
3
1
3
3
3
3
3
3
3
3
3
3
3
1
3
3
3
3
3
3
3
8.9
7.1
5
15
7.1
6.8
26.8
15
8.2
8.2
8.2
19.3
10.7
9.3
7.9
16.4
9.5
8.6
31.8
21.4
9.5
9.6
7.9
20
11.3
8.9
88
44
34
99
57
49.5
129
99
57
49.5
40
123
64
62
50
123
64
62
169
123
64
62
50
156
70
70
Winding Resistance
Start or Line/Line
Run
0.995
4.03
6.28
0.911
2.78
3.64
0.779
0.911
2.78
3.64
5.72
0.686
2.28
2.75
4.31
0.686
2.28
2.75
0.605
0.686
2.28
2.75
4.31
0.501
1.92
2.27
0
0
0
0
0
0
0.432
0
0
0
0
0
0
0
0
0
0
0
0.329
0
0
0
0
0
0
0
Run Cap PN
014-0064-26
014-0064-27
See Section F Introduction for more information.
FF15
Section_Ff.indd 15
3/4/2008 8:09:59 AM
Electrical Data - Copeland Scroll®
Model
ZF18K4-TFE
ZF18K4E-TF5
ZF18K4E-TF7
ZF18K4E-TFD
ZF18K4E-TFE
ZF18KVE-TF5
ZF18KVE-TF7
ZF18KVE-TFD
ZF18KVE-TFE
ZF24K4-TW7
ZF24K4-TWC
ZF24K4-TWD
ZF24K4-TWE
ZF24K4E-TW7
ZF24K4E-TWC
ZF24K4E-TWD
ZF24K4E-TWE
ZF24KVE-TW7
ZF24KVE-TWC
ZF24KVE-TWD
ZF24KVE-TWE
ZF33K4-TW7
ZF33K4-TWC
ZF33K4-TWD
ZF33K4-TWE
ZF33K4E-TW7
Volts
PH
Max
RLA
LRA
575
200/230
380
460
575
200/230
380
460
575
380
208/230
460
575
380
208/230
460
575
380
208/230
460
575
380
208/230
460
575
380
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
7.1
23.9
12.6
9.3
7.9
23.9
12.9
9.3
9.3
14.3
22.9
11.4
8.9
18.6
30
15.7
8.9
18.6
30
15.7
11.4
16.6
30.1
16.4
11.6
23.9
54
156
70
70
54
156
70
70
54
112
189
99
74
112
189
99
74
112
189
99
74
151
278
127
100
151
Winding Resistance
Start or Line/Line
Run
3.56
0.501
1.92
2.27
3.56
0.562
1.92
2.27
3.56
1.03
0.37
1.41
2.3
1.03
0.37
1.41
2.3
1.03
0.37
1.41
2.3
0.72
0.26
1.02
1.7
0.72
Run Cap PN
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
See Section F Introduction for more information.
FF16
Section_Ff.indd 16
3/4/2008 8:09:59 AM
Electrical Data - Copeland Scroll®
Model
ZF33K4E-TWC
ZF33K4E-TWD
ZF33K4E-TWE
ZF33KVE-TW7
ZF33KVE-TWC
ZF33KVE-TWD
ZF33KVE-TWE
ZF40K4-TW7
ZF40K4-TWC
ZF40K4-TWD
ZF40K4-TWE
ZF40K4E-TW7
ZF40K4E-TWC
ZF40K4E-TWD
ZF40K4E-TWE
ZF40KVE-TW7
ZF40KVE-TWC
ZF40KVE-TWD
ZF40KVE-TWE
ZF48K4-TW7
ZF48K4-TWC
ZF48K4-TWD
ZF48K4-TWE
ZF48K4E-TW7
ZF48K4E-TWC
ZF48K4E-TWD
Volts
PH
Max
RLA
LRA
208/230
460
575
380
208/230
460
575
380
208/230
460
575
380
208/230
460
575
380
208/230
460
575
380
208/230
460
575
380
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
43.6
21.1
16.1
23.9
43.6
21.1
16.1
22.9
40.7
20
15.4
28.2
52.9
25
20
28.2
52.9
25
20
25
48.2
22.1
17.9
32.5
60
28.2
278
127
100
151
278
127
100
195
350
158
125
195
350
158
125
195
350
158
125
239
425
187
148
239
425
187
Winding Resistance
Start or Line/Line
Run
0.26
1.02
1.7
0.72
0.26
1.02
1.7
0.57
0.22
0.83
1.28
0.57
0.22
0.83
1.28
0.57
0.22
0.83
1.28
0.52
0.19
0.72
1.1
0.52
0.19
0.72
Run Cap PN
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
See Section F Introduction for more information.
FF17
Section_Ff.indd 17
3/4/2008 8:10:00 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZF48K4E-TWE
575
ZF48KVE-TW7
380
ZF48KVE-TWC 208/230
ZF48KVE-TWD
460
ZF48KVE-TWE
575
ZFD18KVE-TF5 200/230
ZFD18KVE-TF7
380
ZFD18KVE-TFD
460
ZH09KVE-TFD
460
ZH11M4E-TWD
460
ZH13KVE-PFJ
265
ZH13KVE-TFD
460
ZH15K4E-PFJ
265
ZH15K4E-TFD
460
ZH18KVE-TF5 200/230
ZH18KVE-TFD
460
ZH19K4E-PFJ
265
ZH19K4E-TFD
460
ZH21K4E-PFJ
265
ZH21K4E-TFD
460
ZH24KVE-TWD
460
ZH26K4E-PFJ
265
ZH26K4E-TFD
460
ZH30K4E-PFJ
265
ZH30K4E-TFD
460
ZH33KVE-TWD
460
PH
Max
RLA
LRA
3
3
3
3
3
3
3
3
3
3
1
3
1
3
3
3
1
3
1
3
3
1
3
1
3
3
22.5
32.5
60
28.2
22.5
24.3
12.5
10.7
NA
30.7
NA
9.6
12.1
4.3
21.4
10.4
16.8
5
16.1
5.7
17.7
19.6
7.1
19.3
8.2
20.1
148
239
425
187
148
156
70
70
39
187
NA
62
58
27
156
100
76
31
75
35
99
98
44
110
49.5
127
Winding Resistance
Start or Line/Line
Run
1.1
0.52
0.19
0.72
1.1
0.501
1.92
2.27
4.83
0.72
1.224
2.75
3.34
7.1
0.562
1.79
1.89
5.94
2.07
2.74
1.394
1.65
1.85
1.947
3.64
1.002
0
0
0
0
0
0
0
0
0
0
0.417
0
1.26
0
0
0
0.981
0
0.937
0
0
0.691
0
0.599
0
0
Run Cap PN
014-0064-26
014-0064-14
014-0064-15
014-0064-16
014-0064-18
014-0064-15
See Section F Introduction for more information.
FF18
Section_Ff.indd 18
3/4/2008 8:10:00 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZH38K4E-TFD
460
ZH40KVE-TWD
460
ZH45K4E-TFD
460
ZH48KVE-TWD
460
ZH56K4E-TWD
460
ZH75K4E-TWD
460
ZH92K4E-TWD
460
ZM18K4E-TFD
460
ZMD18KVE-TFD 460
ZMD26KVE-TFD 460
ZNH13C2A-KXX
275
ZNH16C2A-KXX
275
ZNH22C2A-KXX
275
ZNH22C3A-KXX
275
ZNH28C2A-KXX
275
ZO104KCE-TFD
460
ZO34K3E-TFD
460
ZO45K3E-TFD
460
ZO58K3E-TFD
460
ZP103KCE-TF5 200/230
ZP103KCE-TFD
460
ZP103KCE-TFE
575
ZP120KCE-TF5 200/230
ZP120KCE-TF7
380
ZP120KCE-TFD
460
ZP120KCE-TFE
575
PH
Max
RLA
LRA
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
9.6
23.1
9.6
27.1
16.4
22.9
27.1
9.3
10.7
10.4
NA
NA
NA
NA
NA
NA
NA
NA
NA
33.6
18.6
13.6
37.1
26.4
20
14.3
62
158
70
198
94
127
158
70
70
75
125
125
125
110
125
NA
27
35
46
225
114
80
239
145
125
80
Winding Resistance
Start or Line/Line
Run
2.75
0.83
2.27
0.72
1.394
1.002
0.83
2.27
2.27
2.26
0.458
0.458
0.458
0.571
0.458
2.26
7.15
5.35
3.88
0.347
1.36
2.55
0.306
0.85
1.227
2.55
Run Cap PN
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
See Section F Introduction for more information.
FF19
Section_Ff.indd 19
3/4/2008 8:10:00 AM
Electrical Data - Copeland Scroll®
Model
ZP137KCE-TF5
ZP137KCE-TF7
ZP137KCE-TFD
ZP137KCE-TFE
ZP154KCE-TF7
ZP154KCE-TFD
ZP154KCE-TW5
ZP154KCE-TW7
ZP154KCE-TWD
ZP154KCE-TWE
ZP16K3E-PFV
ZP16K5E-PFJ
ZP16K5E-PFV
ZP180KCE-TW7
ZP180KCE-TWC
ZP180KCE-TWD
ZP180KCE-TWE
ZP182KCE-TFD
ZP182KCE-TW5
ZP182KCE-TW7
ZP182KCE-TWD
ZP182KCE-TWE
ZP20K3E-PFJ
ZP20K3E-PFV
ZP20K3E-TF5
ZP20K3E-TFD
Volts
PH
Max
RLA
LRA
200/230
380
460
575
380
460
200/230
380
460
575
208/230
265
208/230
380
208/230
460
575
460
200/230
380
460
575
265
208/230
200/230
460
3
3
3
3
3
3
3
3
3
3
1
1
1
3
3
3
3
3
3
3
3
3
1
1
3
3
53.6
26.4
20.7
16.4
27.1
25
57.1
30
25.7
22.1
11.4
7.9
10
40.1
59.1
26.4
26
29.3
62.1
37.9
30
26.4
12.1
14.3
8.6
4.4
245
145
125
100
138
150
300
139
150
109
51
43
48
239
425
187
148
179
340
196
173
132
58
60
55
22.4
Winding Resistance
Start or Line/Line
Run
0.282
0.85
1.227
1.87
0.845
1.1
0.227
0.853
1.108
1.518
1.87
1.79
2.303
0.52
0.19
0.72
1.1
0.833
0.226
0.56
0.833
1.268
3.34
1.856
1.79
8.64
0
0
0
0
0
0
0
0
0
0
1.32
1.79
1.53
0
0
0
0
0
0
0
0
0
1.26
1.073
0
0
Run Cap PN
014-0064-08
014-0064-07
014-0064-06
014-0064-08
014-0064-07
See Section F Introduction for more information.
FF20
Section_Ff.indd 20
3/4/2008 8:10:01 AM
Electrical Data - Copeland Scroll®
Model
ZP20K5E-PFJ
ZP20K5E-PFV
ZP21K5E-PFJ
ZP21K5E-PFV
ZP22KCE-PFV
ZP235KCE-TW5
ZP235KCE-TW7
ZP235KCE-TWC
ZP235KCE-TWD
ZP235KCE-TWE
ZP23K3E-PFJ
ZP23K3E-PFV
ZP23K3E-TF5
ZP23K3E-TFD
ZP24K5E-PFJ
ZP24K5E-PFV
ZP24K5E-TF5
ZP24K5E-TFD
ZP24K5E-TFE
ZP25K5E-PFJ
ZP25K5E-PFV
ZP25K5E-TF5
ZP25K5E-TFE
ZP26K3E-PFJ
ZP26K3E-PFV
ZP26K3E-TF5
Volts
PH
Max
RLA
LRA
265
208/230
265
208/230
208/230
200/230
380
230
460
575
265
208/230
200/230
460
265
208/230
200/230
460
575
265
208/230
200/230
575
265
208/230
200/230
1
1
1
1
1
3
3
3
3
3
1
1
3
3
1
1
3
3
3
1
1
3
3
1
1
3
10
15
10.7
14.3
15
82.4
42.6
82.4
33.9
27.4
12.1
15
9.3
5
12.1
14.3
9.3
5.7
3.7
12.5
15.7
9.9
3.9
13.9
16.4
11.6
54
58.3
54
58.3
61
505
290
505
225
180
58
61
63
27
60
64
58
28
22.5
60
73
58
24
61
72.5
63
Winding Resistance
Start or Line/Line
Run
Run Cap PN
2.17
1.47
2.17
1.47
2.28
0.14
0.44
0.14
0.63
0.97
3.34
2.28
1.46
7.1
2.6
1.57
1.48
1.23
1.48
1.23
1.01
0
0
0
0
0
1.26
1.01
0
0
1.33
1.12
014-0064-08
014-0064-07
014-0064-08
014-0064-08
014-0064-08
2.6
1.78
1.33
0.98
014-0064-08
014-0064-08
2.23
1.72
1.46
1.2
0.905
0
014-0064-15
014-0064-25
014-0064-14
014-0064-08
014-0064-08
014-0064-08
See Section F Introduction for more information.
FF21
Section_Ff.indd 21
3/4/2008 8:10:01 AM
Electrical Data - Copeland Scroll®
Model
ZP26KCE-PFV
ZP285KCE-TW5
ZP285KCE-TW7
ZP285KCE-TWC
ZP285KCE-TWD
ZP285KCE-TWE
ZP28K5E-PFV
ZP28K5E-TF5
ZP295KCE-TW7
ZP295KCE-TWC
ZP295KCE-TWD
ZP295KCE-TWE
ZP29K5E-PFJ
ZP29K5E-PFV
ZP29K5E-TF5
ZP29K5E-TFD
ZP29K5E-TFE
ZP31K5E-PFJ
ZP31K5E-PFV
ZP31K5E-TF5
ZP31K5E-TFD
ZP31K5E-TFE
ZP32K3E-PFJ
ZP32K3E-PFV
ZP32K3E-TF5
ZP32K3E-TFD
Volts
PH
Max
RLA
LRA
208/230
200/230
380
208/230
460
575
208/230
200/230
380
208/230
460
575
265
208/230
200/230
460
575
265
208/230
200/230
460
575
265
208/230
200/230
460
1
3
3
3
3
3
1
3
3
3
3
3
1
1
3
3
3
1
1
3
3
3
1
1
3
3
17.1
99.3
60.7
99.3
47.9
35.7
17.9
11.1
57.9
95
46.7
38.7
13.6
15.7
10
6.3
4.2
15
18.6
11.6
6.4
4.2
17.1
17.1
12.9
5.7
73
500
305
500
250
198
77
71
353
605
272
240
72
77
71
38
36.5
72
79
73
38
36.5
83
83
77
35
Winding Resistance
Start or Line/Line
Run
Run Cap PN
2.71
0.112
0.311
0.112
0.45
0.701
1.44
0.908
0
0
0
0
0
0.9
014-0064-13
0.36
0.12
0.51
0.805
1.22
1.44
0
0
0
0
1.15
0.9
014-0064-26
014-0064-25
1.22
1.465
1.15
0.869
014-0064-26
014-0064-25
1.84
1.69
1.38
5.35
0.887
0.722
0
0
014-0064-16
014-0064-25
014-0064-25
See Section F Introduction for more information.
FF22
Section_Ff.indd 22
3/4/2008 8:10:01 AM
Electrical Data - Copeland Scroll®
Model
ZP32K3E-TFE
ZP32KCE-PFV
ZP34K5E-PFV
ZP34K5E-TF5
ZP34K5E-TFD
ZP36K3E-PFJ
ZP36K3E-PFV
ZP36K3E-TF5
ZP36K3E-TFD
ZP36K3E-TFE
ZP36K5E-PFJ
ZP36K5E-PFV
ZP36K5E-TF5
ZP36K5E-TFD
ZP36K5E-TFE
ZP385KCE-TW5
ZP385KCE-TW7
ZP385KCE-TWC
ZP385KCE-TWD
ZP385KCE-TWE
ZP38K3E-PFV
ZP38K3E-TF5
ZP38K3E-TFD
ZP38K3E-TFE
ZP38K5E-PFV
ZP38K5E-TF5
Volts
PH
575
208/230
208/230
200/230
460
265
208/230
200/230
460
575
265
208/230
200/230
460
575
200/230
380
208/230
460
575
208/230
200/230
460
575
208/230
200/230
3
1
1
3
3
1
1
3
3
3
1
1
3
3
3
3
3
3
3
3
1
3
3
3
1
3
Max
RLA
LRA
4.8
20
20
14.7
6.6
20
20.7
15
7.1
5.7
17.9
20
15.1
6.6
5.5
122.1
77.1
122.1
60.7
55
21.4
15
7.9
5.6
22.1
15.1
31
100
112
88
44
98
105
88
39
34
87
112
88
44
34
599
358
599
310
239
104
88
46
34
109
83.1
Winding Resistance
Start or Line/Line
Run
7.89
2.82
1.253
0.995
4.03
1.65
1.36
0.995
4.83
6.28
1.167
1.253
0.995
4.03
6.28
0.096
0.244
0.096
0.349
0.555
1.38
0.995
3.88
6.28
1.215
1.034
0
0.64
0.556
0
0
0.691
0.605
0
0
0
0.719
0.556
0
0
0
0
0
0
0
0
0.57
0
0
0
0.552
0
Run Cap PN
014-0064-14
014-0064-25
014-0064-18
014-0064-28
014-0064-26
014-0064-25
014-0064-28
014-0064-25
See Section F Introduction for more information.
FF23
Section_Ff.indd 23
3/4/2008 8:10:02 AM
Electrical Data - Copeland Scroll®
Model
Volts
PH
Max
RLA
LRA
ZP38K5E-TFD
ZP38KCE-PFV
ZP39K5E-PFV
ZP39K5E-TF5
ZP39K5E-TFD
ZP41K3E-PFJ
ZP41K3E-PFV
ZP41K3E-TF5
ZP41K3E-TFD
ZP41K3E-TFE
ZP42K5E-PFJ
ZP42K5E-PFV
ZP42K5E-TF5
ZP42K5E-TFD
ZP44K3E-PFV
ZP44K3E-TF5
ZP44K3E-TFD
ZP44K3E-TFE
ZP44KCE-PFV
ZP50K3E-PFJ
ZP50K3E-PFV
ZP50K3E-TF5
ZP50K3E-TFD
ZP50K3E-TFE
ZP51K5E-PFV
ZP51K5E-TF5
460
208/230
208/230
200/230
460
265
208/230
200/230
460
575
265
208/230
200/230
460
208/230
200/230
460
575
208/230
265
208/230
200/230
460
575
208/230
200/230
3
1
1
3
3
1
1
3
3
3
1
1
3
3
1
3
3
3
1
1
1
3
3
3
1
3
6.8
22.1
22.1
14.6
6.8
20
22.9
16.2
7.9
5.7
18.1
24.3
15.3
6.9
25.7
17.9
7.9
6.2
27.1
23.6
30
19.6
10.7
6.8
29.4
17.8
41
131
109
83.1
41
98
109
91
46
34
98
117
83.1
41
134
91
46
37
131
133
145
123
62
40
134
110
Winding Resistance
Start or Line/Line
Run
4.17
1.78
1.215
1.034
4.17
1.65
1.28
0.994
3.88
6.28
0.885
0.817
1.034
4.17
1.45
0.994
3.88
6.21
1.85
0.76
0.593
0.686
2.8
5.72
0.792
0.68
0
0.525
0.552
0
0
0.691
0.54
0
0
0
0.701
0.517
0
0
0.49
0
0
0
0.475
0.49
0.398
0
0
0
0.453
0
Run Cap PN
014-0064-14
014-0064-25
014-0064-18
014-0064-26
014-0064-27
014-0064-34
014-0064-26
014-0064-29
014-0064-27
014-0064-27
014-0064-34
See Section F Introduction for more information.
FF24
Section_Ff.indd 24
3/4/2008 8:10:02 AM
Electrical Data - Copeland Scroll®
Model
ZP51K5E-TFD
ZP51K5E-TFE
ZP54K3E-PFV
ZP54K3E-TF5
ZP54K3E-TFD
ZP54K3E-TFE
ZP54K5E-PFV
ZP54K5E-TF5
ZP54K5E-TFD
ZP54K5E-TFE
ZP57K3E-PFJ
ZP57K3E-PFV
ZP57K3E-TF5
ZP57K3E-TFD
ZP57K3E-TFE
ZP57KCE-PFV
ZP61KCE-TF5
ZP61KCE-TFD
ZP61KCE-TFE
ZP67KCE-TF5
ZP67KCE-TFD
ZP67KCE-TFE
ZP70KWE-PFJ
ZP70KWE-PFV
ZP72KCE-TF5
ZP72KCE-TF7
Volts
PH
Max
RLA
LRA
460
575
208/230
200/230
460
575
208/230
200/230
460
575
265
208/230
200/230
460
575
208/230
200/230
460
575
200/230
460
575
265
208/230
200/230
380
3
3
1
3
3
3
1
3
3
3
1
1
3
3
3
1
3
3
3
3
3
3
1
1
3
3
8.6
6.4
30.7
20.2
10
7.6
29.3
17.4
8.6
6.5
27.3
33.6
22.9
10.7
8.5
33.6
21.2
10.9
8.3
25
11.8
8.6
34.6
35.7
25.9
13.6
52
38.9
158
137
62
50
134
110
52
38.9
157
158
155
75
54
172
123
62
50
149
75
54
170
148
164
73
Winding Resistance
Start or Line/Line
Run
3.199
5.4
0.553
0.612
2.8
4.31
0.792
0.68
3.199
5.4
1.17
0.553
0.58
2.27
3.56
0.58
0.686
2.8
4.31
0.562
2.27
3.56
0.667
0.667
0.501
1.96
0
0
0.37
0
0
0
0.453
0
0
0
0.4
0.37
0
0
0
0.34
0
0
0
0
0
0
0.362
0.362
0
0
Run Cap PN
014-0064-27
014-0064-27
014-0064-16
014-0064-27
014-0064-27
014-0064-35
014-0064-27
See Section F Introduction for more information.
FF25
Section_Ff.indd 25
3/4/2008 8:10:02 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZP72KCE-TFD
460
ZP83KCE-TF5 200/230
ZP83KCE-TF7
380
ZP83KCE-TFD
460
ZP83KCE-TFE
575
ZP83KWE-PFV 208/230
ZP90KCE-TF5 200/230
ZP90KCE-TF7
380
ZP90KCE-TFD
460
ZP90KCE-TFE
575
ZPD61KCE-TF5 200/230
ZPD61KCE-TF7
380
ZPD61KCE-TFD
460
ZPD72KCE-TF5 200/230
ZPD72KCE-TF7
380
ZPD72KCE-TFD
460
ZPD83KCE-TF7
380
ZPD83KCE-TFD
460
ZPDT14MCE-TF7 380
ZPDT14MCE-TFD 460
ZPDT16MCE-TFD 460
ZPDU13MCE-TFD 460
ZPS20K4E-PFV 208/230
ZPS26K4E-PFV 208/230
ZPS30K4E-PFV 208/230
ZPS30K4E-TF5 200/230
PH
3
3
3
3
3
1
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
1
1
1
3
Winding Resistance
Start or Line/Line
Run
Max
RLA
LRA
12.5
27.9
15.5
13.6
10
35.7
32.9
18.6
16.4
13.6
22.7
12.1
10.9
25.9
13.6
12.5
15.9
14.1
75
164
94.3
100
78
185
195
123
95
80
156
64
62
164
73
75
94.3
100
2.26
0.501
1.64
1.79
2.76
0.874
0.4
1.051
1.59
2.55
0.562
2.3
2.8
0.501
1.96
2.26
1.64
1.79
0
0
0
0
0
0.312
0
0
0
0
0
0
0
0
0
0
0
0
11.4
15.7
18.6
12.4
52
70
82
58
1.4
1.249
1.29
1.562
1.32
0.891
0.892
0
Run Cap PN
014-0064-35
014-0064-07
014-0064-08
014-0064-08
See Section F Introduction for more information.
FF26
Section_Ff.indd 26
3/4/2008 8:10:03 AM
Electrical Data - Copeland Scroll®
Model
ZPS30K4E-TFD
ZPS35K4E-PFV
ZPS35K4E-TF5
ZPS35K4E-TFD
ZPS40K4E-PFV
ZPS40K4E-TF5
ZPS40K4E-TFD
ZPS49K4E-PFV
ZPS49K4E-TF5
ZPS49K4E-TFD
ZPS51K4E-PFV
ZPS51K4E-TF5
ZPS51K4E-TFD
ZPS51K4E-TFE
ZPS60K4E-PFV
ZPT100K3E-TF5
ZPT100K3E-TF5
ZPT100K3E-TFD
ZPT100K3E-TFD
ZPT100K3E-TFE
ZPT100K3E-TFE
ZPT108K3E-TF5
ZPT108K3E-TF5
ZPT108K3E-TFD
ZPT108K3E-TFD
ZPT114K3E-PFV
Volts
PH
460
208/230
200/230
460
208/230
200/230
460
208/230
200/230
460
208/230
200/230
460
575
208/230
200/230
200/230
460
460
575
575
200/230
200/230
460
460
208/230
3
1
3
3
1
3
3
1
3
3
1
3
3
3
1
3
3
3
3
3
3
3
3
3
3
1
Max
RLA
LRA
5
18.6
15
6.8
23.6
15
7.1
25.6
19.6
10.3
28.6
19.6
10
8.2
30.4
29
96
88
44
96
88
41
118
123
62
118
123
62
50
150
Winding Resistance
Start or Line/Line
Run
6.02
1.547
0.995
4.03
1.52
0.995
4.17
0.601
0.686
2.8
0.601
0.686
2.8
4.31
0.533
0
0.621
0
0
0.635
0
0
0.49
0
0
0.49
0
0
0
0.37
Run Cap PN
014-0064-25
014-0064-25
014-0064-27
014-0064-27
014-0064-27
See Section F Introduction for more information.
FF27
Section_Ff.indd 27
3/4/2008 8:10:03 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZPT114K3E-TF5 200/230
ZPT114K3E-TF5 200/230
ZPT114K3E-TFD 460
ZPT114K3E-TFD 460
ZPT122KCE-TF5 200/230
ZPT122KCE-TF5 200/230
ZPT122KCE-TFD 460
ZPT122KCE-TFD 460
ZPT134KCE-TF5 200/230
ZPT134KCE-TF5 200/230
ZPT134KCE-TFD 460
ZPT134KCE-TFD 460
ZPT144KCE-TF5 200/230
ZPT144KCE-TF5 200/230
ZPT144KCE-TF7 380
ZPT144KCE-TF7 380
ZPT144KCE-TFD 460
ZPT144KCE-TFD 460
ZPT166KCE-TF5 200/230
ZPT166KCE-TF5 200/230
ZPT166KCE-TF7 380
ZPT166KCE-TF7 380
ZPT166KCE-TFD 460
ZPT166KCE-TFD 460
ZPT166KCE-TFE 575
ZPT166KCE-TFE 575
PH
Max
RLA
LRA
Winding Resistance
Start or Line/Line
Run
Run Cap PN
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
See Section F Introduction for more information.
FF28
Section_Ff.indd 28
3/4/2008 8:10:03 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZPT180KCE-TF5 200/230
ZPT180KCE-TF5 200/230
ZPT180KCE-TFD 460
ZPT180KCE-TFD 460
ZPT180KCE-TFE 575
ZPT180KCE-TFE 575
ZPT206KCE-TF5 200/230
ZPT206KCE-TF5 200/230
ZPT206KCE-TFD 460
ZPT206KCE-TFD 460
ZPT206KCE-TFE 575
ZPT206KCE-TFE 575
ZPT240KCE-TF5 200/230
ZPT240KCE-TF5 200/230
ZPT240KCE-TFD 460
ZPT240KCE-TFD 460
ZPT240KCE-TFE 575
ZPT240KCE-TFE 575
ZPT274KCE-TF5 200/230
ZPT274KCE-TF5 200/230
ZPT274KCE-TFD 460
ZPT274KCE-TFD 460
ZPT274KCE-TFE 575
ZPT274KCE-TFE 575
ZPT308KCE-TFD 460
ZPT308KCE-TW5200/230
PH
Max
RLA
LRA
Winding Resistance
Start or Line/Line
Run
Run Cap PN
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
See Section F Introduction for more information.
FF29
Section_Ff.indd 29
3/4/2008 8:10:04 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZPT308KCE-TWD 460
ZPT308KCE-TWE 575
ZPT360KCE-TW7 380
ZPT360KCE-TWC208/230
ZPT360KCE-TWD 460
ZPT360KCE-TWE 575
ZPT364KCE-TW5200/230
ZPT364KCE-TWD 460
ZPT364KCE-TWE 575
ZPT470KCE-TW7 380
ZPT470KCE-TWC 230
ZPT470KCE-TWD 460
ZPT470KCE-TWE 575
ZPT570KCE-TW5200/230
ZPT570KCE-TW7 380
ZPT570KCE-TWC208/230
ZPT570KCE-TWD 460
ZPT570KCE-TWE 575
ZPT590KCE-TW7 380
ZPT590KCE-TWC208/230
ZPT590KCE-TWD 460
ZPT590KCE-TWE 575
ZPT770KCE-TW5200/230
ZPT770KCE-TW5200/230
ZPT770KCE-TW7 380
ZPT770KCE-TW7 380
PH
Max
RLA
LRA
Winding Resistance
Start or Line/Line
Run
Run Cap PN
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
See Section F Introduction for more information.
FF30
Section_Ff.indd 30
3/4/2008 8:10:04 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZPT770KCE-TWC208/230
ZPT770KCE-TWC208/230
ZPT770KCE-TWD 460
ZPT770KCE-TWD 460
ZPT770KCE-TWE 575
ZPT770KCE-TWE 575
ZPU223KCE-TFD 460
ZPU240KCE-TFD 460
ZPU257KCE-TFD 460
ZPU272KCE-TFD 460
ZPU272KCE-TXD 460
ZPU272KCE-TXE 575
ZPU274KCE-TFD 460
ZPU274KCE-TX5 200/230
ZPU274KCE-TXD 460
ZPU274KCE-TXE 575
ZPU285KCE-TFD 460
ZPU285KCE-TX5 200/230
ZPU285KCE-TXD 460
ZPU285KCE-TXE 575
ZPU302KCE-TFD 460
ZPU302KCE-TX5 200/230
ZPU302KCE-TXD 460
ZPU302KCE-TXE 575
ZPU319KCE-TFD 460
ZPU319KCE-TX5 200/230
PH
Max
RLA
LRA
Winding Resistance
Start or Line/Line
Run
Run Cap PN
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
See Section F Introduction for more information.
FF31
Section_Ff.indd 31
3/4/2008 8:10:04 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZPU319KCE-TXD 460
ZPU319KCE-TXE 575
ZPU336KCE-TFD 460
ZPU336KCE-TW5200/230
ZPU336KCE-TW7 380
ZPU336KCE-TWD 460
ZPU336KCE-TWE 575
ZPU417KCE-TWC200/230
ZPU417KCE-TWC 230
ZPU417KCE-TWD 460
ZPU417KCE-TWE 575
ZPU520KCE-TWD 460
ZPU680KCE-TW7 380
ZPU680KCE-TWC208/230
ZPU680KCE-TWD 460
ZPU680KCE-TWE 575
ZPY115MCE-TW5200/230
ZPY115MCE-TW7 380
ZPY115MCE-TWC208/230
ZPY115MCE-TWD 460
ZPY115MCE-TWE 575
ZPY309KCE-TF5 200/230
ZPY309KCE-TFD 460
ZPY309KCE-TFE 575
ZPY360KCE-TF5 200/230
ZPY360KCE-TFD 460
PH
Max
RLA
LRA
Winding Resistance
Start or Line/Line
Run
Run Cap PN
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
See Section F Introduction for more information.
FF32
Section_Ff.indd 32
3/4/2008 8:10:05 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZPY360KCE-TFE 575
ZPY411KCE-TF5 200/230
ZPY411KCE-TFD 460
ZPY411KCE-TFE 575
ZPY462KCE-TFD 460
ZPY462KCE-TW5200/230
ZPY462KCE-TW7 380
ZPY462KCE-TWD 460
ZPY462KCE-TWE 575
ZPY546KCE-TFD 460
ZPY546KCE-TW5200/230
ZPY546KCE-TW7 380
ZPY546KCE-TWD 460
ZPY546KCE-TWE 575
ZPY705KCE-TW7 380
ZPY705KCE-TWC 230
ZPY705KCE-TWD 460
ZPY705KCE-TWE 575
ZPY855KCE-TW5200/230
ZPY855KCE-TW7 380
ZPY855KCE-TWC208/230
ZPY855KCE-TWD 460
ZPY855KCE-TWE 575
ZR108KC-TF5
200/230
ZR108KC-TF7
380
ZR108KC-TFD
460
PH
Max
RLA
LRA
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
33.6
18.6
17.3
225
140
114
Winding Resistance
Start or Line/Line
Run
0.347
0.93
1.36
Run Cap PN
0
0
0
See Section F Introduction for more information.
FF33
Section_Ff.indd 33
3/4/2008 8:10:05 AM
Electrical Data - Copeland Scroll®
Model
ZR108KC-TFE
ZR108KCE-TF5
ZR108KCE-TF7
ZR108KCE-TFD
ZR108KCE-TFE
ZR11M3-TW7
ZR11M3-TWC
ZR11M3-TWD
ZR11M3-TWE
ZR11M3E-TW7
ZR11M3E-TWC
ZR11M3E-TWD
ZR11M3E-TWE
ZR125KC-TF5
ZR125KC-TF7
ZR125KC-TFD
ZR125KC-TFE
ZR125KCE-TF5
ZR125KCE-TF7
ZR125KCE-TFD
ZR125KCE-TFE
ZR12M3-TW5
ZR12M3-TW7
ZR12M3-TWC
ZR12M3-TWD
ZR12M3-TWE
Volts
PH
Max
RLA
LRA
575
200/230
380
460
575
380
208/230
460
575
380
208/230
460
575
200/230
380
460
575
200/230
380
460
575
200/230
380
208/230
460
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
13.5
33.6
18.6
17.3
13.5
20.7
33.3
17
12.9
24.9
38.2
18.6
15.4
41.4
23.6
19.2
13.8
41.4
23.6
20
13.8
37.4
25.4
37.4
18.4
15.2
80
225
140
114
80
144
232
125
100
144
232
125
100
239
145
125
80
239
145
125
80
278
151
278
127
100
Winding Resistance
Start or Line/Line
Run
2.55
0.347
0.93
1.36
2.55
0.78
0.29
1.11
1.86
0.78
0.29
1.11
1.86
0.306
0.85
1.227
2.55
0.306
0.85
1.227
2.55
0.26
0.72
0.26
1.02
1.7
Run Cap PN
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
See Section F Introduction for more information.
FF34
Section_Ff.indd 34
3/4/2008 8:10:06 AM
Electrical Data - Copeland Scroll®
Model
ZR12M3E-TW5
ZR12M3E-TW7
ZR12M3E-TWC
ZR12M3E-TWD
ZR12M3E-TWE
ZR144KC-TF5
ZR144KC-TF7
ZR144KC-TFD
ZR144KC-TFE
ZR144KCE-TF5
ZR144KCE-TF7
ZR144KCE-TFD
ZR144KCE-TFE
ZR160KC-TF7
ZR160KC-TFD
ZR160KC-TW5
ZR160KC-TW7
ZR160KC-TWD
ZR160KC-TWE
ZR160KCE-TF7
ZR160KCE-TFD
ZR160KCE-TW5
ZR160KCE-TW7
ZR160KCE-TWD
ZR160KCE-TWE
ZR16K4-PFJ
Volts
PH
Max
RLA
LRA
200/230
380
208/230
460
575
200/230
380
460
575
200/230
380
460
575
380
460
200/230
380
460
575
380
460
200/230
380
460
575
265
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
1
41.1
30.3
41.1
22.1
18.3
47.1
24.4
19.6
15.9
47.1
24.6
20.7
15.9
27.1
25
53.6
28.6
24.3
20.7
27.1
25
55
30.7
25.7
21.4
8.6
278
151
278
127
100
245
145
125
100
245
145
125
100
138
150
300
139
150
109
138
150
300
139
150
109
38
Winding Resistance
Start or Line/Line
Run
0.26
0.72
0.26
1.02
1.7
0.282
0.85
1.227
1.87
0.282
0.85
1.227
1.87
0.845
1.1
0.227
0.853
1.108
1.518
0.845
1.1
0.227
0.853
1.108
1.518
3.4
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
2.16
Run Cap PN
014-0064-07
See Section F Introduction for more information.
FF35
Section_Ff.indd 35
3/4/2008 8:10:06 AM
Electrical Data - Copeland Scroll®
Model
ZR16K4-PFV
ZR16K4E-PFJ
ZR16K4E-PFV
ZR16KA-PFV
ZR16M3-TW5
ZR16M3-TW7
ZR16M3-TWC
ZR16M3-TWD
ZR16M3-TWE
ZR16M3E-TW5
ZR16M3E-TW7
ZR16M3E-TWC
ZR16M3E-TWD
ZR16M3E-TWE
ZR18K3-PFV
ZR18K3E-PFV
ZR18K4-PFJ
ZR18K4-PFV
ZR18K4E-PFJ
ZR18K4E-PFV
ZR18KC-PFV
ZR190KC-TFD
ZR190KC-TW5
ZR190KC-TW7
ZR190KC-TWD
ZR190KC-TWE
Volts
PH
Max
RLA
LRA
208/230
265
208/230
208/230
200/230
380
208/230
460
575
200/230
380
208/230
460
575
208/230
208/230
265
208/230
265
208/230
208/230
460
200/230
380
460
575
1
1
1
1
3
3
3
3
3
3
3
3
3
3
1
1
1
1
1
1
1
3
3
3
3
3
10
8.6
10
8.6
45.7
27.9
45.7
24.3
19.3
48.9
30
48.9
27.2
19.3
9.3
9.3
8.6
10.7
8.6
10.7
10.7
27.9
58.6
35.7
28.6
23.6
41
38
41
40.3
350
195
350
158
125
350
195
350
158
125
47
47
39
45
39
45
47
179
340
196
173
132
Winding Resistance
Start or Line/Line
Run
2.73
3.4
2.73
2.61
0.22
0.57
0.22
0.83
1.28
0.22
0.57
0.22
0.83
1.28
2.67
2.67
3.24
2.27
3.24
2.27
3.48
0.833
0.226
0.56
0.833
1.268
1.77
2.16
1.77
1.74
0
0
0
0
0
0
0
0
0
0
1.43
1.43
1.81
1.81
1.81
1.81
1.56
0
0
0
0
0
Run Cap PN
014-0064-06
014-0064-07
014-0064-06
014-0064-06
014-0064-06
014-0064-06
014-0064-13
014-0064-07
014-0064-13
014-0064-07
014-0064-06
See Section F Introduction for more information.
FF36
Section_Ff.indd 36
3/4/2008 8:10:06 AM
Electrical Data - Copeland Scroll®
Model
ZR190KCE-TFD
ZR190KCE-TW5
ZR190KCE-TW7
ZR190KCE-TWD
ZR190KCE-TWE
ZR19M3-TW5
ZR19M3-TW7
ZR19M3-TWC
ZR19M3-TWD
ZR19M3-TWE
ZR19M3E-TW5
ZR19M3E-TW7
ZR19M3E-TWC
ZR19M3E-TWD
ZR19M3E-TWE
ZR21KA-PFV
ZR22K3-PFJ
ZR22K3-PFV
ZR22K3-TF5
ZR22K3-TFD
ZR22K3E-PFJ
ZR22K3E-PFV
ZR22K3E-TF5
ZR22K3E-TFD
ZR22K4-PFJ
ZR22K4-PFV
Volts
PH
Max
RLA
LRA
460
200/230
380
460
575
200/230
380
208/230
460
575
200/230
380
208/230
460
575
208/230
265
208/230
200/230
460
265
208/230
200/230
460
265
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
1
1
1
3
3
1
1
3
3
1
1
27.9
60
37.1
31.4
25
53.6
36.4
53.6
26.4
23.6
55
37.1
55
32.1
25.7
11.6
9.6
11.4
7.9
3.9
9.6
11.4
7.9
3.9
10
12.1
179
340
196
173
132
425
239
425
187
148
425
239
425
187
148
54
47
56
45
22.4
47
56
45
22.4
55
54
Winding Resistance
Start or Line/Line
Run
0.833
0.226
0.56
0.833
1.268
0.19
0.52
0.19
0.72
1.1
0.19
0.52
0.19
0.72
1.1
2.14
2.85
2.06
2.15
8.64
2.85
2.06
2.15
8.64
2.75
2.67
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1.27
1.62
1.18
0
0
1.62
1.18
0
0
1.81
1.31
Run Cap PN
014-0064-07
014-0064-14
014-0064-25
014-0064-14
014-0064-25
014-0064-25
014-0064-07
See Section F Introduction for more information.
FF37
Section_Ff.indd 37
3/4/2008 8:10:07 AM
Electrical Data - Copeland Scroll®
Model
ZR22K4E-PFJ
ZR22K4E-PFV
ZR24K3-PFJ
ZR24K3-PFV
ZR24K3-TF5
ZR24K3-TFD
ZR24K3E-PFJ
ZR24K3E-PFV
ZR24K3E-TF5
ZR24K3E-TFD
ZR24K4-PFJ
ZR24K4-PFV
ZR24K4E-PFJ
ZR24K4E-PFV
ZR24KL-PFV
ZR250KC-TW5
ZR250KC-TW7
ZR250KC-TWC
ZR250KC-TWD
ZR250KC-TWE
ZR250KCE-TW5
ZR250KCE-TW7
ZR250KCE-TWC
ZR250KCE-TWD
ZR250KCE-TWE
ZR26K3-PFJ
Volts
PH
Max
RLA
LRA
265
208/230
265
208/230
200/230
460
265
208/230
200/230
460
265
208/230
265
208/230
208/230
200/230
380
208/230
460
575
200/230
380
208/230
460
575
265
1
1
1
1
3
3
1
1
3
3
1
1
1
1
1
3
3
3
3
3
3
3
3
3
3
1
10
12.1
11.4
13.6
8.6
4.3
11.4
13.6
8.6
4.3
10.4
13.6
10.4
13.6
13.6
81.4
42.1
81.4
33.6
27.1
81.4
42.1
81.4
37.9
32.1
12.1
55
54
58
61
55
27
58
61
55
27
52
63
52
63
61
505
280
505
225
180
505
280
505
225
180
58
Winding Resistance
Start or Line/Line
Run
2.75
2.67
3.34
2.28
1.79
7.1
3.34
2.28
1.79
7.1
2.86
2.45
2.86
2.45
2.28
0.14
0.44
0.14
0.63
0.97
0.14
0.44
0.14
0.63
0.97
2.94
1.81
1.31
1.26
1.01
0
0
1.26
1.01
0
0
1.5
1.17
1.5
1.17
1.01
0
0
0
0
0
0
0
0
0
0
1.23
Run Cap PN
014-0064-25
014-0064-07
014-0064-14
014-0064-08
014-0064-14
014-0064-08
014-0064-25
014-0064-07
014-0064-25
014-0064-07
014-0064-08
014-0064-14
See Section F Introduction for more information.
FF38
Section_Ff.indd 38
3/4/2008 8:10:07 AM
Electrical Data - Copeland Scroll®
Model
ZR26K3-PFV
ZR26K3-TF5
ZR26K3-TFD
ZR26K3E-PFJ
ZR26K3E-PFV
ZR26K3E-TF5
ZR26KA-PFV
ZR26KA-TF5
ZR26KC-PFV
ZR26KL-PFV
ZR28K3-PFJ
ZR28K3-PFV
ZR28K3-TF5
ZR28K3-TFD
ZR28K3E-PFJ
ZR28K3E-PFV
ZR28K3E-TF5
ZR28K3E-TFD
ZR28KA-PFV
ZR28KC-PFV
ZR300KC-TW5
ZR300KC-TW7
ZR300KC-TWC
ZR300KC-TWD
ZR300KC-TWE
ZR300KCE-TW5
Volts
PH
Max
RLA
LRA
208/230
200/230
460
265
208/230
200/230
208/230
200/230
208/230
208/230
265
208/230
200/230
460
265
208/230
200/230
460
208/230
208/230
208/230
380
208/230
460
575
208/230
1
3
3
1
1
3
1
3
1
1
1
1
3
3
1
1
3
3
1
1
3
3
3
3
3
3
13.6
8.6
4.3
12.1
13.6
8.6
15.7
8.6
15
13.6
12.9
15
10
5
12.9
15
10
5
15.7
15.7
87.9
54.3
87.9
42.9
34.3
81.4
67
55
27
58
67
55
68
58
73
67
61
72.5
63
31
61
72.5
63
31
68
73
500
305
500
250
198
500
Winding Resistance
Start or Line/Line
Run
1.96
1.79
7.1
2.94
1.96
1.79
1.34
0.94
0
0
1.23
0.94
0
0.92
3.16
1.96
2.23
1.72
1.46
5.94
2.23
1.72
1.46
5.94
1.34
2.71
0.112
0.311
0.112
0.45
0.701
0.112
0.99
0.94
1.2
0.905
0
0
1.2
0.905
0
0
0.92
0.908
0
0
0
0
0
0
Run Cap PN
014-0064-08
014-0064-14
014-0064-08
014-0064-25
014-0064-12
014-0064-08
014-0064-15
014-0064-25
014-0064-15
014-0064-25
014-0064-25
014-0064-13
See Section F Introduction for more information.
FF39
Section_Ff.indd 39
3/4/2008 8:10:07 AM
Electrical Data - Copeland Scroll®
Model
ZR300KCE-TW7
ZR300KCE-TWC
ZR300KCE-TWD
ZR300KCE-TWE
ZR30K3-PFJ
ZR30K3-PFV
ZR30K3-TF5
ZR30K3-TFD
ZR30K3-TFE
ZR30K3E-PFJ
ZR30K3E-PFV
ZR30K3E-TF5
ZR30K3E-TFD
ZR30K3E-TFE
ZR30KC-PFV
ZR30KS-TFD
ZR310KC-TW7
ZR310KC-TWC
ZR310KC-TWD
ZR310KCE-TW7
ZR310KCE-TWC
ZR310KCE-TWD
ZR32K3-PFJ
ZR32K3-PFV
ZR32K3-TF5
ZR32K3-TFD
Volts
PH
Max
RLA
LRA
380
208/230
460
575
265
208/230
200/230
460
575
265
208/230
200/230
460
575
208/230
460
380
208/230
460
380
208/230
460
265
208/230
200/230
460
3
3
3
3
1
1
3
3
3
1
1
3
3
3
1
3
3
3
3
3
3
3
1
1
3
3
61.4
81.4
48.6
36.4
14.3
15
10.7
5
4.3
14.3
15
10.7
5
4.3
16.4
5.7
55.7
93.6
41.4
55.7
87.1
43.6
14.3
16.4
10.7
5.4
305
500
250
198
76
73
63
31
24
76
73
63
31
24
84
44.4
353
605
272
353
605
272
76
83
77
35
Winding Resistance
Start or Line/Line
Run
0.311
0.112
0.45
0.701
1.89
1.72
1.46
5.94
9.2
1.89
1.72
1.46
5.94
9.2
2.51
0
0
0
0
0.981
0.833
0
0
0
0.981
0.833
0
0
0
0.787
0.36
0.12
0.51
0.36
0.12
0.51
1.89
1.69
1.38
5.35
0
0
0
0
0
0
0.981
0.722
0
0
Run Cap PN
014-0064-15
014-0064-25
014-0064-15
014-0064-25
014-0064-07
014-0064-15
014-0064-25
See Section F Introduction for more information.
FF40
Section_Ff.indd 40
3/4/2008 8:10:08 AM
Electrical Data - Copeland Scroll®
Model
Volts
PH
Max
RLA
LRA
ZR32K3-TFE
ZR32K3E-PFJ
ZR32K3E-PFV
ZR32K3E-TF5
ZR32K3E-TFD
ZR32K3E-TFE
ZR32KA-PFV
ZR32KA-TF5
ZR32KA-TFD
ZR32KA-TFE
ZR32KS-TFD
ZR34K3-PFJ
ZR34K3-PFV
ZR34K3-TF5
ZR34K3-TF7
ZR34K3-TFD
ZR34K3-TFE
ZR34K3E-PFJ
ZR34K3E-PFV
ZR34K3E-TF5
ZR34K3E-TF7
ZR34K3E-TFD
ZR34K3E-TFE
ZR34KA-PFV
ZR34KA-TF5
ZR34KA-TFD
575
265
208/230
200/230
460
575
208/230
200/230
460
575
460
265
208/230
200/230
380
460
575
265
208/230
200/230
380
460
575
208/230
200/230
460
3
1
1
3
3
3
1
3
3
3
3
1
1
3
3
3
3
1
1
3
3
3
3
1
3
3
3.9
14.3
16.4
10.7
5.4
3.9
16.1
10.7
6.4
4.5
5.7
14.3
17.9
11.4
6.8
5.7
4.7
14.3
17.9
11.4
6.8
5.7
4.7
16.4
12.1
6.4
28
76
83
77
35
28
77
73
38
28
44.4
75
88
77
39
39
31
75
88
77
39
39
31
77
73
38
Winding Resistance
Start or Line/Line
Run
8.38
1.89
1.69
1.38
5.35
8.38
1.07
0
0.981
0.722
0
0
0
0.839
2.07
1.46
1.234
4.83
4.83
7.89
2.07
1.46
1.234
4.83
4.83
7.89
1.07
0.937
0.691
0
0
0
0
0.937
0.691
0
0
0
0
0.839
Run Cap PN
014-0064-15
014-0064-25
014-0064-29
014-0064-16
014-0064-29
014-0064-16
014-0064-29
014-0064-26
See Section F Introduction for more information.
FF41
Section_Ff.indd 41
3/4/2008 8:10:08 AM
Electrical Data - Copeland Scroll®
Model
ZR34KA-TFE
ZR34KC-PFV
ZR34KH-PFJ
ZR34KH-TFD
ZR34KL-PFV
ZR34KL-TF5
ZR36K3-PFJ
ZR36K3-PFV
ZR36K3-TF5
ZR36K3-TFD
ZR36K3-TFE
ZR36K3E-PFJ
ZR36K3E-PFV
ZR36K3E-TF5
ZR36K3E-TFD
ZR36K3E-TFE
ZR36KC-PFV
ZR36KH-PFJ
ZR36KH-TFD
ZR380KC-TW5
ZR380KC-TW7
ZR380KC-TWC
ZR380KC-TWD
ZR380KC-TWE
ZR380KCE-TW5
ZR380KCE-TW7
Volts
PH
575
208/230
265
460
208/230
200/230
265
208/230
200/230
460
575
265
208/230
200/230
460
575
208/230
265
460
200/230
380
208/230
460
575
200/230
380
3
1
1
3
1
3
1
1
3
3
3
1
1
3
3
3
1
1
3
3
3
3
3
3
3
3
Max
RLA
LRA
3.9
15.7
17.1
7.1
17.9
11.4
16.4
18.4
11.4
5.7
4.7
16.4
18.4
11.4
5.7
4.7
17.9
17.1
6.4
111.4
63.6
111.4
54.3
43.6
121.4
68.6
36.5
93
102
39
88
77
83
95
77
39
31
83
95
77
39
31
100
96
39
599
358
599
310
239
599
358
Winding Resistance
Start or Line/Line
Run
1.9
1.81
4.83
1.46
1.234
1.84
1.39
1.234
4.83
7.89
1.84
1.39
1.234
4.83
7.89
2.82
1.81
4.83
0.096
0.244
0.096
0.349
0.555
0.096
0.244
0.74
0.753
0
0.691
0
0.887
0.65
0
0
0
0.887
0.65
0
0
0
0.64
0.753
0
0
0
0
0
0
0
0
Run Cap PN
014-0064-08
014-0064-17
014-0064-29
014-0064-16
014-0064-29
014-0064-16
014-0064-29
014-0064-14
014-0064-17
See Section F Introduction for more information.
FF42
Section_Ff.indd 42
3/4/2008 8:10:08 AM
Electrical Data - Copeland Scroll®
Model
ZR380KCE-TWC
ZR380KCE-TWD
ZR380KCE-TWE
ZR38KA-PFV
ZR38KA-TF5
ZR38KA-TFD
ZR38KA-TFE
ZR39KH-PFJ
ZR39KH-TFD
ZR40K3-PFJ
ZR40K3-PFV
ZR40K3-TF5
ZR40K3-TFD
ZR40K3-TFE
ZR40K3E-PFJ
ZR40K3E-PFV
ZR40K3E-TF5
ZR40K3E-TFD
ZR40K3E-TFE
ZR40KC-PFV
ZR42K3-PFJ
ZR42K3-PFV
ZR42K3-TF5
ZR42K3-TFD
ZR42K3-TFE
ZR42K3E-PFJ
Volts
PH
208/230
460
575
208/230
200/230
460
575
265
460
265
208/230
200/230
460
575
265
208/230
200/230
460
575
208/230
265
208/230
200/230
460
575
265
3
3
3
1
3
3
3
1
3
1
1
3
3
3
1
1
3
3
3
1
1
1
3
3
3
1
Max
RLA
LRA
121.4
59.3
47.1
21.4
13.6
6.4
4.6
22.9
7.9
17.1
20
13.9
6.4
5.4
17.1
20
13.9
6.4
5.4
20
17.1
20.4
13.9
7.1
5.4
17.1
599
310
239
104
88
44
33
113
44
96
104
88
44
34
96
104
88
44
34
103
98
109
88
44
34
98
Winding Resistance
Start or Line/Line
Run
0.096
0.349
0.555
1.38
0.995
4.03
6.32
1.67
4.03
1.81
1.38
0.995
4.03
6.28
1.81
1.38
0.995
4.03
6.28
2.94
1.65
1.28
0.995
4.03
6.28
1.65
0
0
0
0.57
0
0
0
0.586
0
0.753
0.57
0
0
0
0.753
0.57
0
0
0
0.598
0.691
0.54
0
0
0
0.691
Run Cap PN
014-0064-28
014-0064-18
014-0064-17
014-0064-28
014-0064-17
014-0064-28
014-0064-14
014-0064-18
014-0064-26
014-0064-18
See Section F Introduction for more information.
FF43
Section_Ff.indd 43
3/4/2008 8:10:09 AM
Electrical Data - Copeland Scroll®
Model
Volts
PH
Max
RLA
LRA
ZR42K3E-PFV
ZR42K3E-TF5
ZR42K3E-TFD
ZR42K3E-TFE
ZR42KA-PFV
ZR42KA-TF5
ZR42KA-TFD
ZR42KA-TFE
ZR42KC-PFV
ZR44KA-PFV
ZR44KA-TF5
ZR44KA-TFD
ZR44KA-TFE
ZR45K3-PFJ
ZR45K3-PFV
ZR45K3-TF5
ZR45K3-TFD
ZR45K3E-PFJ
ZR45K3E-PFV
ZR45KC-PFV
ZR45KC-TF5
ZR45KC-TFD
ZR45KC-TFE
ZR45KCE-TFD
ZR46K3-PFV
ZR46K3-TF5
208/230
200/230
460
575
208/230
200/230
460
575
208/230
208/230
200/230
460
575
265
208/230
200/230
460
265
208/230
208/230
200/230
460
575
460
208/230
200/230
1
3
3
3
1
3
3
3
1
1
3
3
3
1
1
3
3
1
1
1
3
3
3
3
1
3
20.4
13.9
7.1
5.4
21.4
13.6
6.4
5.1
20.7
22.5
13.6
6.8
4.6
19.3
23.6
15.4
7.9
19.3
23.6
24.3
14.3
7.1
5.7
7.1
26.4
15
109
88
44
34
97
88
44
37
127
137
83.1
41
33
113
137
91
46
113
137
131
91
46
37
46
129
120
Winding Resistance
Start or Line/Line
Run
1.28
0.995
4.03
6.28
1.374
0.995
4.03
6.21
2.15
1.34
1.034
4.17
6.32
1.67
1.34
0.994
3.88
1.67
1.34
1.85
0.994
3.88
6.21
3.88
0.765
0.797
0.54
0
0
0
0.595
0
0
0
0.506
0.46
0
0
0
0.586
0.46
0
0
0.586
0.46
0.475
0
0
0
0
0.475
0
Run Cap PN
014-0064-26
014-0064-28
014-0064-14
014-0064-26
014-0064-18
014-0064-18
014-0064-18
014-0064-18
014-0064-08
014-0064-26
See Section F Introduction for more information.
FF44
Section_Ff.indd 44
3/4/2008 8:10:09 AM
Electrical Data - Copeland Scroll®
Model
Volts
PH
Max
RLA
LRA
ZR46K3-TFD
ZR46K3-TFE
ZR46KC-TF5
ZR46KC-TF7
ZR46KC-TFD
ZR46KCE-TF5
ZR47K3-PFJ
ZR47K3-PFV
ZR47K3-TF5
ZR47K3-TFD
ZR47K3-TFE
ZR47K3E-PFJ
ZR47K3E-PFV
ZR47K3E-TF5
ZR47K3E-TFD
ZR47K3E-TFE
ZR47KC-PFV
ZR47KC-TF5
ZR47KC-TF7
ZR47KC-TFD
ZR47KC-TFE
ZR47KCE-TF5
ZR47KCE-TF7
ZR47KCE-TFD
ZR47KCE-TFE
ZR48K3-PFJ
460
575
200/230
380
460
200/230
265
208/230
200/230
460
575
265
208/230
200/230
460
575
208/230
200/230
380
380/460
575
200/230
380
380/460
575
265
3
3
3
3
3
3
1
1
3
3
3
1
1
3
3
3
1
3
3
3
3
3
3
3
3
1
8.2
6.4
15
8
7.4
16.1
19.3
21.4
16.4
7.9
5.7
19.3
21.4
16.4
7.9
5.7
24.3
14.3
9.3
7.1
5.7
14.3
9.3
7.1
5.7
19.3
49.5
40
108
57
47.5
115
113
137
91
50
37
113
137
91
50
37
131
91
54
46
37
91
54
46
37
113
Winding Resistance
Start or Line/Line
Run
3.64
5.72
0.803
2.77
3.58
0.808
1.67
1.34
0.994
3.88
6.21
1.67
1.34
0.994
3.88
6.21
1.85
0.994
2.76
3.88
6.21
0.994
2.76
3.88
6.21
1.67
0
0
0
0
0
0
0.586
0.46
0
0
0
0.586
0.46
0
0
0
0.475
0
0
0
0
0
0
0
0
0.586
Run Cap PN
014-0064-18
014-0064-18
014-0064-18
014-0064-18
014-0064-25
014-0064-18
See Section F Introduction for more information.
FF45
Section_Ff.indd 45
3/4/2008 8:10:09 AM
Electrical Data - Copeland Scroll®
Model
Volts
PH
Max
RLA
LRA
ZR48K3-PFV
ZR48K3-TF5
ZR48K3-TFD
ZR48K3-TFE
ZR48K3E-PFJ
ZR48K3E-PFV
ZR48K3E-TF5
ZR48K3E-TFD
ZR48K3E-TFE
ZR48KC-PFV
ZR48KC-TF5
ZR48KC-TF7
ZR48KC-TFD
ZR48KC-TFE
ZR48KCE-PFV
ZR48KCE-TF5
ZR48KCE-TF7
ZR48KCE-TFD
ZR48KCE-TFE
ZR49K3-PFV
ZR49K3-TF5
ZR49K3-TFD
ZR49K3-TFE
ZR49K3E-TFD
ZR49KC-PFV
ZR49KC-TF5
208/230
200/230
460
575
265
208/230
200/230
460
575
208/230
200/230
380
460
575
208/230
200/230
380
460
575
208/230
200/230
460
575
460
208/230
200/230
1
3
3
3
1
1
3
3
3
1
3
3
3
3
1
3
3
3
3
1
3
3
3
3
1
3
22.1
16.4
7.9
5.7
19.3
22.1
16.4
7.9
5.7
23.6
16.4
9.3
7.9
6.4
23.6
16.4
9.3
7.9
6.4
26.4
15
8.2
6.4
8.2
25
15
137
91
50
37
113
137
91
50
37
132
91
54
50
37
132
91
54
50
37
129
120
49.5
40
49.5
132
115
Winding Resistance
Start or Line/Line
Run
1.34
0.994
3.88
6.21
1.67
1.34
0.994
3.88
6.21
2.75
0.994
2.76
3.88
6.21
2.75
0.994
2.76
3.88
6.21
0.779
0.797
3.64
5.72
3.64
2.089
0.808
0.46
0
0
0
0.586
0.46
0
0
0
0.437
0
0
0
0
0.437
0
0
0
0
0.432
0
0
0
0
0.454
0
Run Cap PN
014-0064-18
014-0064-18
014-0064-18
014-0064-14
014-0064-14
014-0064-26
014-0064-15
See Section F Introduction for more information.
FF46
Section_Ff.indd 46
3/4/2008 8:10:10 AM
Electrical Data - Copeland Scroll®
Model
Volts
PH
Max
RLA
LRA
ZR49KC-TF7
ZR49KC-TFD
ZR49KC-TFE
ZR49KCE-PFV
ZR49KCE-TF5
ZR49KCE-TF7
ZR49KCE-TFD
ZR49KCE-TFE
ZR52K3-PFV
ZR52K3-TF5
ZR52K3-TFD
ZR52K3-TFE
ZR54K3-PFV
ZR54K3-TF5
ZR54K3-TFD
ZR54K3-TFE
ZR54K3E-TF5
ZR54K3E-TFD
ZR54K3E-TFE
ZR54KA-PFV
ZR54KA-TF5
ZR54KA-TFD
ZR54KA-TFE
ZR54KC-PFV
ZR54KC-TF5
ZR54KC-TF7
380
460
575
208/230
200/230
380
460
575
208/230
200/230
460
575
208/230
200/230
460
575
200/230
460
575
208/230
200/230
460
575
208/230
200/230
380
3
3
3
1
3
3
3
3
1
3
3
3
1
3
3
3
3
3
3
1
3
3
3
1
3
3
8.8
7.4
5.9
25
15
8.8
7.4
5.9
27.9
17.1
7.5
5.7
27.9
19.3
7.5
6.4
19.3
7.5
6.4
28.2
17.1
7.9
5.9
28.6
16.4
9.3
57
47.5
37.5
132
115
57
47.5
37.5
148
128
49.5
40
148
123
49.5
40
123
49.5
40
141
110
52
38.9
150
124
65.8
Winding Resistance
Start or Line/Line
Run
2.77
3.58
6.26
2.089
0.808
2.77
3.58
6.26
0.572
0.686
3.64
5.72
0.572
0.686
3.64
5.72
0.686
3.64
5.72
0.768
0.68
3.199
5.4
1.12
0.735
2.46
0
0
0
0.454
0
0
0
0
0.406
0
0
0
0.406
0
0
0
0
0
0
0.461
0
0
0
0.386
0
0
Run Cap PN
014-0064-15
014-0064-27
014-0064-27
014-0064-27
014-0064-26
See Section F Introduction for more information.
FF47
Section_Ff.indd 47
3/4/2008 8:10:10 AM
Electrical Data - Copeland Scroll®
Model
Volts
PH
Max
RLA
LRA
ZR54KC-TFD
ZR54KC-TFE
ZR54KCE-TF5
ZR54KCE-TF7
ZR54KCE-TFD
ZR54KCE-TFE
ZR54KS-TF5
ZR54KS-TF7
ZR54KS-TFD
ZR54KSE-TF5
ZR54KSE-TFD
ZR57K3-PFV
ZR57K3-TF5
ZR57K3-TFD
ZR57K3-TFE
ZR57K3E-TF5
ZR57K3E-TFD
ZR57K3E-TFE
ZR57KC-PFV
ZR57KC-TF5
ZR57KC-TF7
ZR57KC-TFD
ZR57KC-TFE
ZR57KCE-TF5
ZR57KCE-TFD
ZR57KCE-TFE
460
575
200/230
380
460
575
200/230
380
460
200/230
460
208/230
200/230
460
575
200/230
460
575
208/230
200/230
380
380/460
575
200/230
380/460
575
3
3
3
3
3
3
3
3
3
3
3
1
3
3
3
3
3
3
1
3
3
3
3
3
3
3
8.3
6.6
16.4
9.3
8.3
6.6
18.3
9.9
10
18.3
10
32.1
19.3
9.1
7.9
19.3
9.1
7.9
27.9
17.2
10.7
8.3
6.6
17.2
8.3
6.6
59.6
49.4
124
65.8
59.6
49.4
125
65
59
125
59
148
123
62
50
123
62
50
150
124
75
59.6
49.4
124
59.6
49.4
Winding Resistance
Start or Line/Line
Run
2.9
4.74
0.735
2.46
2.9
4.74
0.69
2.13
2.78
0.69
2.78
0.667
0.686
2.75
4.31
0.686
2.75
4.31
1.12
0.735
1.98
2.9
4.74
0.735
2.9
4.74
0
0
0
0
0
0
0
0
0
0
0
0.362
0
0
0
0
0
0
0.386
0
0
0
0
0
0
0
Run Cap PN
014-0064-27
014-0064-26
See Section F Introduction for more information.
FF48
Section_Ff.indd 48
3/4/2008 8:10:11 AM
Electrical Data - Copeland Scroll®
Model
Volts
PH
Max
RLA
LRA
ZR57KH-TFD
ZR57KS-TF5
ZR57KS-TF7
ZR57KS-TFD
ZR57KSE-TF5
ZR57KSE-TFD
ZR61K3-PFV
ZR61K3-TF5
ZR61K3-TFD
ZR61K3-TFE
ZR61K3E-PFV
ZR61K3E-TF5
ZR61K3E-TFD
ZR61K3E-TFE
ZR61KC-PFV
ZR61KC-TF5
ZR61KC-TF7
ZR61KC-TFD
ZR61KC-TFE
ZR61KCE-PFV
ZR61KCE-TF5
ZR61KCE-TF7
ZR61KCE-TFD
ZR61KCE-TFE
ZR61KH-TFD
ZR61KS-TF5
460
200/230
380
460
200/230
460
208/230
200/230
460
575
208/230
200/230
460
575
208/230
200/230
380
460
575
208/230
200/230
380
460
575
460
200/230
3
3
3
3
3
3
1
3
3
3
1
3
3
3
1
3
3
3
3
1
3
3
3
3
3
3
10
18
10.9
NA
18
NA
32.1
19.3
9.1
7.9
32.1
19.3
9.1
7.9
30.1
20.7
10.7
10
7.4
26.4
20.7
10.7
10
7.4
11.4
22.9
62
125
65
59
125
59
148
137
62
50
148
137
62
50
144
128
64
63
49
144
128
64
63
49
68
125
Winding Resistance
Start or Line/Line
Run
2.75
0.69
2.13
2.78
0.69
2.78
0.654
0.612
2.75
4.31
0.654
0.612
2.75
4.31
1.328
0.726
2.3
2.72
4.44
1.328
0.726
2.3
2.72
4.44
2.673
0.69
0
0
0
0
0
0
0.355
0
0
0
0.355
0
0
0
0.383
0
0
0
0
0.383
0
0
0
0
0
0
Run Cap PN
014-0064-27
014-0064-27
014-0064-34
014-0064-34
See Section F Introduction for more information.
FF49
Section_Ff.indd 49
3/4/2008 8:10:11 AM
Electrical Data - Copeland Scroll®
Model
Volts
PH
Max
RLA
LRA
ZR61KS-TF7
ZR61KS-TFD
ZR61KSE-TFD
ZR67KW-PFV
ZR68KC-PFJ
ZR68KC-PFV
ZR68KC-TF5
ZR68KC-TF7
ZR68KC-TFD
ZR68KC-TFE
ZR68KCE-PFJ
ZR68KCE-PFV
ZR68KCE-TF5
ZR68KCE-TF7
ZR68KCE-TFD
ZR68KCE-TFE
ZR72KC-TF5
ZR72KC-TF7
ZR72KC-TFD
ZR72KC-TFE
ZR72KCE-TF5
ZR72KCE-TF7
ZR72KCE-TFD
ZR72KCE-TFE
ZR72KS-TFD
ZR80KW-PFV
380
460
460
208/230
265
208/230
200/230
380
460
575
265
208/230
200/230
380
460
575
200/230
380
460
575
200/230
380
460
575
380/460
208/230
3
3
3
1
1
1
3
3
3
3
1
1
3
3
3
3
3
3
3
3
3
3
3
3
3
1
11.8
10
10
27.9
30.7
32.1
20.7
10.7
10
8.2
30.7
32.1
20.7
10.7
10
8.2
20.7
10.7
10
8.2
20.7
10.7
10
8.2
10
31.4
65
56
56
129
160
176
156
70
75
54
160
176
156
70
75
54
156
70
75
54
156
70
75
54
75
176
Winding Resistance
Start or Line/Line
Run
2.13
2.78
2.78
0.779
1.921
1.408
0.562
1.92
2.27
3.56
1.921
1.408
0.562
1.92
2.27
3.56
0.562
1.92
2.27
3.56
0.562
1.92
2.27
3.56
2.27
1.408
0
0
0
0.432
0.415
0.346
0
0
0
0
0.415
0.346
0
0
0
0
0
0
0
0
0
0
0
0
0
0.346
Run Cap PN
014-0064-26
014-0064-16
014-0064-35
014-0064-16
014-0064-35
014-0064-35
See Section F Introduction for more information.
FF50
Section_Ff.indd 50
3/4/2008 8:10:11 AM
Electrical Data - Copeland Scroll®
Model
ZR81KC-TF5
ZR81KC-TF7
ZR81KC-TFD
ZR81KC-TFE
ZR81KCE-TF5
ZR81KCE-TF7
ZR81KCE-TFD
ZR81KCE-TFE
ZR84KC-TF5
ZR84KC-TF7
ZR84KC-TFD
ZR84KC-TFE
ZR84KCE-TF5
ZR84KCE-TF7
ZR84KCE-TFD
ZR84KCE-TFE
ZR90K3-TW5
ZR90K3-TW7
ZR90K3-TWC
ZR90K3-TWD
ZR90K3-TWE
ZR90K3E-TW5
ZR90K3E-TW7
ZR90K3E-TWC
ZR90K3E-TWD
ZR90K3E-TWE
Volts
PH
Max
RLA
LRA
200/230
380
460
575
200/230
380
460
575
200/230
380
460
575
200/230
380
460
575
200/230
380
208/230
460
575
200/230
380
208/230
460
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
25
12.1
12.1
9.3
25
12.1
12.1
9.3
28.6
15.7
14.3
9.6
28.6
15.7
14.3
9.6
26.4
16.6
26.4
13.9
10.1
33.6
16.6
33.6
15.4
11.4
164
100
100
78
164
100
100
78
196
135
100
90
196
135
100
90
189
112
189
99
74
189
112
189
99
74
Winding Resistance
Start or Line/Line
Run
0.501
1.79
1.79
2.76
0.501
1.79
1.79
2.76
0.44
1.174
1.764
2.989
0.44
1.174
1.764
2.989
0.348
1.03
0.37
1.41
2.3
0.348
1.03
0.37
1.41
2.3
Run Cap PN
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
See Section F Introduction for more information.
FF51
Section_Ff.indd 51
3/4/2008 8:10:12 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZR94KC-TF5
200/230
ZR94KC-TF7
380
ZR94KC-TFD
460
ZR94KC-TFE
575
ZR94KCE-TF5 200/230
ZR94KCE-TF7
380
ZR94KCE-TFD
460
ZR94KCE-TFE
575
ZRD125KC-TF5 200/230
ZRD125KC-TF7
380
ZRD125KC-TFD
460
ZRD125KC-TFE
575
ZRD125KCE-TF5 200/230
ZRD125KCE-TF7 380
ZRD125KCE-TFD 460
ZRD125KCE-TFE 575
ZRD36KC-PFV 208/230
ZRD36KC-TF5 200/230
ZRD36KCE-PFV 208/230
ZRD36KCE-TF5 200/230
ZRD42KC-TFD
460
ZRD42KCE-PFJ
265
ZRD42KCE-TFD
460
ZRD48KC-PFV 208/230
ZRD48KC-TF5 200/230
ZRD48KC-TF7
380
PH
Max
RLA
LRA
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
1
3
1
3
3
1
3
1
3
3
32.1
16.7
16.4
12
32.1
17.1
16.4
12
41.4
23.6
19.2
13.8
41.4
23.6
19.2
13.8
18.6
12.1
18.6
11.4
7.1
19.3
7.1
22.9
17.1
9.3
195
123
95
80
195
123
95
80
239
145
125
80
239
145
125
80
95
77
95
77
44
98
44
137
110
54
Winding Resistance
Start or Line/Line
Run
0.4
1.051
1.799
2.55
0.4
1.051
1.799
2.55
0.306
0.85
1.227
2.55
0.306
0.85
1.227
2.55
1.39
1.234
1.39
1.234
4.03
1.65
4.03
1.339
0.432
2.76
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0.65
0
0.65
0
0
0.691
0
0.462
0
0
Run Cap PN
014-0064-29
014-0064-29
014-0064-18
014-0064-26
See Section F Introduction for more information.
FF52
Section_Ff.indd 52
3/4/2008 8:10:12 AM
Electrical Data - Copeland Scroll®
Model
ZRD48KC-TFD
ZRD48KCE-PFV
ZRD48KCE-TF5
ZRD48KCE-TF7
ZRD48KCE-TFD
ZRD49KC-PFV
ZRD49KC-TF5
ZRD49KC-TF7
ZRD49KC-TFD
ZRD49KCE-TF5
ZRD49KCE-TF7
ZRD49KCE-TFD
ZRD61KC-PFV
ZRD61KC-TF5
ZRD61KC-TF7
ZRD61KC-TFD
ZRD61KC-TFE
ZRD61KCE-PFV
ZRD61KCE-TF5
ZRD61KCE-TF7
ZRD61KCE-TFD
ZRD68KC-TFD
ZRD68KCE-TFD
ZRD72KC-TF5
ZRD72KC-TF7
ZRD72KC-TFD
Volts
PH
Max
RLA
LRA
460
208/230
200/230
380
460
208/230
200/230
380
460
200/230
380
460
208/230
200/230
380
460
575
208/230
200/230
380
460
460
460
200/230
380
460
3
1
3
3
3
1
3
3
3
3
3
3
1
3
3
3
3
1
3
3
3
3
3
3
3
3
7.9
22.9
17.1
9.3
7.9
26.4
15
8
7.4
15.7
8
7.4
32.1
20.7
10.7
10
7.1
32.1
20.7
10.7
9.1
11.1
11.1
20.7
12.5
10
46
137
110
54
46
129
115
57
47.5
115
57
47.5
148
137
64
62
53
148
137
64
62
75
75
156
70
70
Winding Resistance
Start or Line/Line
Run
3.88
1.339
0.432
2.76
3.88
0.779
0.911
2.78
3.64
0.911
2.78
3.64
0.667
0.612
2.3
2.8
4.333
0.667
0.612
2.3
2.8
2.27
2.27
0.562
1.92
2.27
0
0.462
0
0
0
0.432
0
0
0
0
0
0
0.362
0
0
0
0
0.362
0
0
0
0
0
0
0
0
Run Cap PN
014-0064-26
014-0064-26
014-0064-27
014-0064-27
See Section F Introduction for more information.
FF53
Section_Ff.indd 53
3/4/2008 8:10:12 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZRD72KCE-TF5 200/230
ZRD72KCE-TF7
380
ZRD72KCE-TFD
460
ZRD81KC-TF7
380
ZRD81KC-TFD
460
ZRD81KCE-TF7
380
ZRD81KCE-TFD
460
ZRD94KC-TF5 200/230
ZRD94KC-TF7
380
ZRD94KC-TFD
460
ZRD94KC-TFE
575
ZRD94KCE-TF5 200/230
ZRD94KCE-TF7
380
ZRD94KCE-TFD
460
ZRD94KCE-TFE
575
ZRDT12MC-TF5 200/230
ZRDT12MC-TF7
380
ZRDT12MC-TFD 460
ZRDT12MCE-TF5200/230
ZRDT12MCE-TF7 380
ZRDT12MCE-TFD 460
ZRDT14MC-TF5 200/230
ZRDT14MC-TF7
380
ZRDT14MC-TFD 460
ZRDT14MCE-TF5200/230
ZRDT14MCE-TF7 380
PH
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Max
RLA
LRA
20.7
12.5
10
14.3
12.1
14.3
12.1
32.1
16.7
16.4
12
32.1
16.7
16.4
12
156
70
70
78
100
78
100
195
123
95
80
195
123
95
80
Winding Resistance
Start or Line/Line
Run
0.562
1.92
2.27
1.79
1.79
1.79
1.79
0.4
1.051
1.799
2.55
0.4
1.051
1.799
2.55
Run Cap PN
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
See Section F Introduction for more information.
FF54
Section_Ff.indd 54
3/4/2008 8:10:13 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZRDT14MCE-TFD 460
ZRDT16MC-TF7
380
ZRDT16MC-TFD 460
ZRDT16MCE-TF7 380
ZRDT16MCE-TFD 460
ZRDT96KC-TF7
380
ZRDT96KC-TFD
460
ZRDT96KCE-TF7 380
ZRDT96KCE-TFD 460
ZRDU11MC-TF5 200/230
ZRDU11MC-TF5 200/230
ZRDU11MC-TF7
380
ZRDU11MC-TF7
380
ZRDU11MC-TFD 460
ZRDU11MC-TFD 460
ZRDU11MCE-TF5200/230
ZRDU11MCE-TF7 380
ZRDU11MCE-TFD 460
ZRDU13MC-TF5 200/230
ZRDU13MC-TF5 200/230
ZRDU13MC-TF7 380
ZRDU13MC-TF7 380
ZRDU13MC-TFD 460
ZRDU13MC-TFD 460
ZRDU13MCE-TF5200/230
ZRDU13MCE-TF5200/230
PH
Max
RLA
LRA
Winding Resistance
Start or Line/Line
Run
Run Cap PN
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
See Section F Introduction for more information.
FF55
Section_Ff.indd 55
3/4/2008 8:10:13 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZRDU13MCE-TF7 380
ZRDU13MCE-TF7 380
ZRDU13MCE-TFD 460
ZRDU13MCE-TFD 460
ZRH49KJE-TF5 200/230
ZRH49KJE-TF7
380
ZRH49KJE-TFD
460
ZRH49KJE-TFE
575
ZRH61KJE-TF5 200/230
ZRH61KJE-TF7
380
ZRH61KJE-TFD
460
ZRH72KJE-TF5 200/230
ZRH72KJE-TF7
380
ZRH72KJE-TFD
460
ZRI108KC-TF7
380
ZRI125KC-TF7
380
ZRI144KC-TF7
380
ZRI61KC-TFD
460
ZRJ61KC-TFD
460
ZRJ72KC-TFD
460
ZRJU13MC-TFD
460
ZRS43K4-PFV 208/230
ZRS43K4-TF5
200/230
ZRS43K4-TFD
460
ZRS52K4-PFV 208/230
ZRS52K4-TF5
200/230
PH
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
1
3
3
1
3
Winding Resistance
Start or Line/Line
Run
Max
RLA
LRA
15
8.6
8.2
6.4
21.4
11.4
9.6
23.9
12.9
9.3
19.6
23.9
24.3
10.4
10.7
12.5
99
57
49.5
40
123
64
62
156
70
70
140
145
145
62
62
100
0.911
0.911
3.64
5.72
0.686
0.686
2.75
0.501
2.27
2.27
0.93
0.85
0.85
2.75
2.75
1.79
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
23.9
14.3
6.8
24.6
18.9
116
91
46
118
123
1.227
0.994
3.88
0.601
0.686
0.517
0
0
0.49
0
Run Cap PN
014-0064-25
014-0064-27
See Section F Introduction for more information.
FF56
Section_Ff.indd 56
3/4/2008 8:10:13 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZRS52K4-TFD
460
ZRT108K3-PFV 208/230
ZRT108K3-PFV 208/230
ZRT108K3-TF5 200/230
ZRT108K3-TF5 200/230
ZRT108K3-TFD
460
ZRT108K3-TFD
460
ZRT108K3-TFE
575
ZRT108K3-TFE
575
ZRT108K3E-TFD 460
ZRT108K3E-TFD 460
ZRT108K3E-TFE 575
ZRT108K3E-TFE 575
ZRT108KC-TF7
380
ZRT108KC-TF7
380
ZRT108KS-TFD
460
ZRT108KSE-TFD 460
ZRT114K3-PFV 208/230
ZRT114K3-PFV 208/230
ZRT114K3-TF5 200/230
ZRT114K3-TF5 200/230
ZRT114K3-TFD
460
ZRT114K3-TFD
460
ZRT114K3-TFE
575
ZRT114K3-TFE
575
ZRT114KS-TFD
460
PH
3
1
1
3
3
3
3
3
3
3
3
3
3
3
3
3
3
1
1
3
3
3
3
3
3
3
Max
RLA
LRA
9.4
62
Winding Resistance
Start or Line/Line
Run
2.8
Run Cap PN
0
See Section F Introduction for more information.
FF57
Section_Ff.indd 57
3/4/2008 8:10:14 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZRT114KSE-TFD 460
ZRT122K3-PFV 208/230
ZRT122K3-PFV 208/230
ZRT122K3-TF5 200/230
ZRT122K3-TF5 200/230
ZRT122K3-TFD
460
ZRT122K3-TFD
460
ZRT122K3-TFE
575
ZRT122K3-TFE
575
ZRT122K3E-PFV 208/230
ZRT122K3E-PFV 208/230
ZRT122K3E-TF5 200/230
ZRT122K3E-TF5 200/230
ZRT122K3E-TFD 460
ZRT122K3E-TFD 460
ZRT122KCE-TFD 460
ZRT122KCE-TFD 460
ZRT122KS-TF5 200/230
ZRT122KS-TFD
460
ZRT122KSE-TF5 200/230
ZRT122KSE-TFD 460
ZRT136KC-TF5 200/230
ZRT136KC-TF5 200/230
ZRT136KC-TF7
380
ZRT136KC-TF7
380
ZRT136KC-TFD
460
PH
Max
RLA
LRA
Winding Resistance
Start or Line/Line
Run
Run Cap PN
3
1
1
3
3
3
3
3
3
1
1
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
See Section F Introduction for more information.
FF58
Section_Ff.indd 58
3/4/2008 8:10:14 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZRT136KC-TFD
460
ZRT136KC-TFE
575
ZRT136KC-TFE
575
ZRT136KCE-TF5 200/230
ZRT136KCE-TFD 460
ZRT136KCE-TFD 460
ZRT136KCE-TFE 575
ZRT136KCE-TFE 575
ZRT144KC-TF5 200/230
ZRT144KC-TF5 200/230
ZRT144KC-TF7
380
ZRT144KC-TF7
380
ZRT144KC-TFD
460
ZRT144KC-TFD
460
ZRT144KC-TFE
575
ZRT144KC-TFE
575
ZRT144KCE-TF5 200/230
ZRT144KCE-TF5 200/230
ZRT144KCE-TFD 460
ZRT144KCE-TFD 460
ZRT144KCE-TFE 575
ZRT144KCE-TFE 575
ZRT162KC-TF5 200/230
ZRT162KC-TF5 200/230
ZRT162KC-TF7
380
ZRT162KC-TFD
460
PH
Max
RLA
LRA
Winding Resistance
Start or Line/Line
Run
Run Cap PN
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
See Section F Introduction for more information.
FF59
Section_Ff.indd 59
3/4/2008 8:10:14 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZRT162KC-TFD
460
ZRT162KCE-TF5 200/230
ZRT162KCE-TF5 200/230
ZRT162KCE-TF7 380
ZRT162KCE-TF7 380
ZRT162KCE-TFD 460
ZRT162KCE-TFD 460
ZRT168KC-TF5 200/230
ZRT168KC-TF5 200/230
ZRT168KC-TF7
380
ZRT168KC-TF7
380
ZRT168KC-TFD
460
ZRT168KC-TFD
460
ZRT168KC-TFE
575
ZRT168KC-TFE
575
ZRT168KCE-TF5 200/230
ZRT168KCE-TF5 200/230
ZRT168KCE-TF7 380
ZRT168KCE-TF7 380
ZRT168KCE-TFD 460
ZRT168KCE-TFD 460
ZRT168KCE-TFE 575
ZRT168KCE-TFE 575
ZRT180K3-TW5 200/230
ZRT180K3-TW7
380
ZRT180K3-TWC 208/230
PH
Max
RLA
LRA
Winding Resistance
Start or Line/Line
Run
Run Cap PN
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
See Section F Introduction for more information.
FF60
Section_Ff.indd 60
3/4/2008 8:10:15 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZRT180K3-TWD
460
ZRT180K3-TWE
575
ZRT180K3E-TWC208/230
ZRT180K3E-TWD 460
ZRT180K3E-TWE 575
ZRT188KC-TF5 200/230
ZRT188KC-TF5 200/230
ZRT188KC-TF7
380
ZRT188KC-TF7
380
ZRT188KC-TFD
460
ZRT188KC-TFD
460
ZRT188KC-TFE
575
ZRT188KC-TFE
575
ZRT188KCE-TF5 200/230
ZRT188KCE-TF5 200/230
ZRT188KCE-TF7 380
ZRT188KCE-TF7 380
ZRT188KCE-TFD 460
ZRT188KCE-TFD 460
ZRT188KCE-TFE 575
ZRT188KCE-TFE 575
ZRT216KC-TF5 200/230
ZRT216KC-TF5 200/230
ZRT216KC-TF7
380
ZRT216KC-TF7
380
ZRT216KC-TFD
460
PH
Max
RLA
LRA
Winding Resistance
Start or Line/Line
Run
Run Cap PN
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
See Section F Introduction for more information.
FF61
Section_Ff.indd 61
3/4/2008 8:10:15 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZRT216KC-TFD
460
ZRT216KC-TFE
575
ZRT216KC-TFE
575
ZRT216KCE-TF5 200/230
ZRT216KCE-TF5 200/230
ZRT216KCE-TF7 380
ZRT216KCE-TF7 380
ZRT216KCE-TFD 460
ZRT216KCE-TFD 460
ZRT216KCE-TFE 575
ZRT216KCE-TFE 575
ZRT220K3-TW7
380
ZRT220K3-TWC 208/230
ZRT220K3-TWD
460
ZRT220K3-TWE
575
ZRT220K3E-TW7 380
ZRT220K3E-TWC208/230
ZRT220K3E-TWD 460
ZRT240K3-TW5 200/230
ZRT240K3-TW7
380
ZRT240K3-TWC 208/230
ZRT240K3-TWD
460
ZRT240K3-TWE
575
ZRT240K3E-TWC208/230
ZRT240K3E-TWD 460
ZRT240K3E-TWE 575
PH
Max
RLA
LRA
Winding Resistance
Start or Line/Line
Run
Run Cap PN
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
See Section F Introduction for more information.
FF62
Section_Ff.indd 62
3/4/2008 8:10:15 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZRT250KC-TF5 200/230
ZRT250KC-TF5 200/230
ZRT250KC-TF7
380
ZRT250KC-TF7
380
ZRT250KC-TFD
460
ZRT250KC-TFD
460
ZRT250KC-TFE
575
ZRT250KC-TFE
575
ZRT250KCE-TF5 200/230
ZRT250KCE-TF5 200/230
ZRT250KCE-TF7 380
ZRT250KCE-TF7 380
ZRT250KCE-TFD 460
ZRT250KCE-TFD 460
ZRT250KCE-TFE 575
ZRT250KCE-TFE 575
ZRT288KC-TF5 200/230
ZRT288KC-TF5 200/230
ZRT288KC-TF7
380
ZRT288KC-TF7
380
ZRT288KC-TFD
460
ZRT288KC-TFD
460
ZRT288KC-TFE
575
ZRT288KC-TFE
575
ZRT320K3-TW5 200/230
ZRT320K3-TW7
380
PH
Max
RLA
LRA
Winding Resistance
Start or Line/Line
Run
Run Cap PN
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
See Section F Introduction for more information.
FF63
Section_Ff.indd 63
3/4/2008 8:10:16 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZRT320K3-TWC 208/230
ZRT320K3-TWD
460
ZRT320K3-TWE
575
ZRT320K3E-TWC208/230
ZRT320K3E-TWD 460
ZRT320K3E-TWE 575
ZRT320KC-TFD
460
ZRT320KC-TW5 200/230
ZRT320KC-TW7
380
ZRT320KC-TWD 460
ZRT320KC-TWE 575
ZRT320KCE-TFD 460
ZRT320KCE-TW5200/230
ZRT320KCE-TW7 380
ZRT320KCE-TWD 460
ZRT320KCE-TWE 575
ZRT380K3-TW5 200/230
ZRT380K3-TW7
380
ZRT380K3-TWC 208/230
ZRT380K3-TWD
460
ZRT380K3-TWE
575
ZRT380K3E-TWC208/230
ZRT380K3E-TWD 460
ZRT380K3E-TWE 575
ZRT380KC-TFD
460
ZRT380KC-TW5 200/230
PH
Max
RLA
LRA
Winding Resistance
Start or Line/Line
Run
Run Cap PN
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
See Section F Introduction for more information.
FF64
Section_Ff.indd 64
3/4/2008 8:10:16 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZRT380KC-TW7
380
ZRT380KC-TWD 460
ZRT380KC-TWE 575
ZRT380KCE-TFD 460
ZRT380KCE-TW5200/230
ZRT380KCE-TW7 380
ZRT380KCE-TWD 460
ZRT380KCE-TWE 575
ZRT500KC-TW5 200/230
ZRT500KC-TW5 200/230
ZRT500KC-TW7
380
ZRT500KC-TW7
380
ZRT500KC-TWC 208/230
ZRT500KC-TWC 208/230
ZRT500KC-TWD 460
ZRT500KC-TWD 460
ZRT500KC-TWE 575
ZRT500KC-TWE 575
ZRT500KCE-TW5200/230
ZRT500KCE-TW5200/230
ZRT500KCE-TW7 380
ZRT500KCE-TW7 380
ZRT500KCE-TWC208/230
ZRT500KCE-TWC208/230
ZRT500KCE-TWD 460
ZRT500KCE-TWD 460
PH
Max
RLA
LRA
Winding Resistance
Start or Line/Line
Run
Run Cap PN
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
See Section F Introduction for more information.
FF65
Section_Ff.indd 65
3/4/2008 8:10:16 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZRT500KCE-TWE 575
ZRT500KCE-TWE 575
ZRT600KC-TW5 208/230
ZRT600KC-TW5 208/230
ZRT600KC-TW7
380
ZRT600KC-TW7
380
ZRT600KC-TWC 208/230
ZRT600KC-TWC 208/230
ZRT600KC-TWD 460
ZRT600KC-TWD 460
ZRT600KC-TWE 575
ZRT600KC-TWE 575
ZRT600KCE-TW5208/230
ZRT600KCE-TW5208/230
ZRT600KCE-TW7 380
ZRT600KCE-TW7 380
ZRT600KCE-TWC208/230
ZRT600KCE-TWC208/230
ZRT600KCE-TWD 460
ZRT600KCE-TWD 460
ZRT600KCE-TWE 575
ZRT600KCE-TWE 575
ZRT760KC-TW5 200/230
ZRT760KC-TW5 200/230
ZRT760KC-TW7
380
ZRT760KC-TW7
380
PH
Max
RLA
LRA
Winding Resistance
Start or Line/Line
Run
Run Cap PN
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
See Section F Introduction for more information.
FF66
Section_Ff.indd 66
3/4/2008 8:10:17 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZRT760KC-TWC 208/230
ZRT760KC-TWC 208/230
ZRT760KC-TWD 460
ZRT760KC-TWD 460
ZRT760KC-TWE 575
ZRT760KC-TWE 575
ZRT760KCE-TW5200/230
ZRT760KCE-TW5200/230
ZRT760KCE-TW7 380
ZRT760KCE-TW7 380
ZRT760KCE-TWC208/230
ZRT760KCE-TWC208/230
ZRT760KCE-TWD 460
ZRT760KCE-TWD 460
ZRT760KCE-TWE 575
ZRT760KCE-TWE 575
ZRT90K3-PFV 208/230
ZRT90K3-PFV 208/230
ZRT90K3-TF5
200/230
ZRT90K3-TF5
200/230
ZRT90K3-TFD
460
ZRT90K3-TFD
460
ZRT90K3E-PFV 208/230
ZRT90KC-PFV 208/230
ZRT90KC-PFV 208/230
ZRT90KC-TF5 200/230
PH
Max
RLA
LRA
Winding Resistance
Start or Line/Line
Run
Run Cap PN
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
1
1
3
3
3
3
1
1
1
3
See Section F Introduction for more information.
FF67
Section_Ff.indd 67
3/4/2008 8:10:17 AM
Electrical Data - Copeland Scroll®
Model
ZRT90KC-TF5
ZRT90KC-TFD
ZRT90KC-TFD
ZRT90KC-TFE
ZRT90KC-TFE
ZRT92K3-PFV
ZRT92K3-PFV
ZRT92K3-TF5
ZRT92K3-TF5
ZRT92K3-TFD
ZRT92K3-TFD
ZRT92K3-TFE
ZRT92K3-TFE
ZRT96K3-PFV
ZRT96K3-PFV
ZRT96K3-TF5
ZRT96K3-TF5
ZRT96K3-TFD
ZRT96K3-TFD
ZRT96K3-TFE
ZRT96K3E-PFV
ZRT96K3E-PFV
ZRT96K3E-TF5
ZRT96K3E-TF5
ZRT96K3E-TFD
Volts
PH
200/230
460
460
575
575
208/230
208/230
200/230
200/230
460
460
575
575
208/230
208/230
200/230
200/230
460
460
575
208/230
208/230
200/230
200/230
460
3
3
3
3
3
1
1
3
3
3
3
3
3
1
1
3
3
3
3
3
1
1
3
3
3
Max
RLA
LRA
Winding Resistance
Start or Line/Line
Run
Run Cap PN
See Section F Introduction for more information.
FF68
Section_Ff.indd 68
3/4/2008 8:10:17 AM
Electrical Data - Copeland Scroll®
Model
ZRT96K3E-TFD
ZRT96K3E-TFE
ZRT96KC-PFV
ZRT96KC-PFV
ZRT96KC-TF5
ZRT96KC-TF5
ZRT96KC-TFD
ZRT96KC-TFD
ZRT96KCE-TF5
ZRT96KCE-TF5
ZRT96KCE-TFD
ZRT96KCE-TFD
ZRT98K3-PFV
ZRT98K3-PFV
ZRT98K3-TF5
ZRT98K3-TF5
ZRT98K3-TFD
ZRT98K3-TFD
ZRT98K3-TFE
ZRT98K3-TFE
ZRU103K3-TF5
ZRU103K3-TF5
ZRU103K3-TFD
ZRU103K3-TFD
ZRU103K3-TFE
ZRU103K3-TFE
Volts
PH
460
575
208/230
208/230
200/230
200/230
460
460
200/230
200/230
460
460
208/230
208/230
200/230
200/230
460
460
575
575
200/230
200/230
460
460
575
575
3
3
1
1
3
3
3
3
3
3
3
3
1
1
3
3
3
3
3
3
3
3
3
3
3
3
Max
RLA
LRA
Winding Resistance
Start or Line/Line
Run
Run Cap PN
See Section F Introduction for more information.
FF69
Section_Ff.indd 69
3/4/2008 8:10:18 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZRU140KC-TF5 200/230
ZRU140KC-TF5 200/230
ZRU140KC-TF7
380
ZRU140KC-TF7
380
ZRU140KC-TFD
460
ZRU140KC-TFD
460
ZRU140KC-TFE
575
ZRU140KC-TFE
575
ZRU178KC-TF5 200/230
ZRU178KC-TF5 200/230
ZRU178KC-TF7
380
ZRU178KC-TF7
380
ZRU178KC-TFD
460
ZRU178KC-TFD
460
ZRU178KC-TFE
575
ZRU178KC-TFE
575
ZRU280K3-TW5 200/230
ZRU280K3-TW7
380
ZRU280K3-TWC 208/230
ZRU280K3-TWD 460
ZRU280K3-TWE
575
ZRU280K3E-TWC208/230
ZRU280K3E-TWD 460
ZRU280K3E-TWE 575
ZRU285KC-TFD
460
ZRU285KC-TX5 200/230
PH
Max
RLA
LRA
Winding Resistance
Start or Line/Line
Run
Run Cap PN
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
See Section F Introduction for more information.
FF70
Section_Ff.indd 70
3/4/2008 8:10:18 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZRU285KC-TX7
380
ZRU285KC-TXD
460
ZRU285KC-TXE
575
ZRU285KCE-TFD 460
ZRU285KCE-TX5 200/230
ZRU285KCE-TX7 380
ZRU285KCE-TXD 460
ZRU285KCE-TXE 575
ZRU310K3-TW5 200/230
ZRU310K3-TW7
380
ZRU310K3-TWC 208/230
ZRU310K3-TWD 460
ZRU310K3-TWE
575
ZRU310K3E-TWC208/230
ZRU310K3E-TWD 460
ZRU310K3E-TWE 575
ZRU315KC-TFD
460
ZRU315KC-TX5 200/230
ZRU315KC-TX7
380
ZRU315KC-TXD
460
ZRU315KC-TXE
575
ZRU315KCE-TFD 460
ZRU315KCE-TX5 200/230
ZRU315KCE-TX7 380
ZRU315KCE-TXD 460
ZRU315KCE-TXE 575
PH
Max
RLA
LRA
Winding Resistance
Start or Line/Line
Run
Run Cap PN
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
See Section F Introduction for more information.
FF71
Section_Ff.indd 71
3/4/2008 8:10:18 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZRU334KC-TFD
460
ZRU334KC-TX5 200/230
ZRU334KC-TX7
380
ZRU334KC-TXD
460
ZRU334KC-TXE
575
ZRU334KCE-TFD 460
ZRU334KCE-TX5 200/230
ZRU334KCE-TX7 380
ZRU334KCE-TXD 460
ZRU334KCE-TXE 575
ZRU350K3-TW5 200/230
ZRU350K3-TW7
380
ZRU350K3-TWC 208/230
ZRU350K3-TWD 460
ZRU350K3-TWE
575
ZRU350K3E-TWC208/230
ZRU350K3E-TWD 460
ZRU350K3E-TWE 575
ZRU350KC-TFD
460
ZRU350KC-TW5 200/230
ZRU350KC-TW7 380
ZRU350KC-TWD 460
ZRU350KC-TWE 575
ZRU350KCE-TFD 460
ZRU350KCE-TW5200/230
ZRU350KCE-TW7 380
PH
Max
RLA
LRA
Winding Resistance
Start or Line/Line
Run
Run Cap PN
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
See Section F Introduction for more information.
FF72
Section_Ff.indd 72
3/4/2008 8:10:19 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZRU350KCE-TWD 460
ZRU350KCE-TWE 575
ZRU440KC-TW7 380
ZRU440KC-TW7 380
ZRU440KC-TWC 208/230
ZRU440KC-TWC 208/230
ZRU440KC-TWD 460
ZRU440KC-TWD 460
ZRU440KC-TWE 575
ZRU440KC-TWE 575
ZRU440KCE-TWD 460
ZRU440KCE-TWE 575
ZRU550KC-TW5 200/230
ZRU550KC-TW5 208/230
ZRU550KC-TW7 380
ZRU550KC-TWC 208/230
ZRU550KC-TWD 460
ZRU550KC-TWE 575
ZRU550KCE-TW5200/230
ZRU550KCE-TW5208/230
ZRU550KCE-TW7 380
ZRU550KCE-TWC208/230
ZRU550KCE-TWD 460
ZRU550KCE-TWE 575
ZRY114MC-TWD 460
ZRY114MCE-TWD 460
PH
Max
RLA
LRA
Winding Resistance
Start or Line/Line
Run
Run Cap PN
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
See Section F Introduction for more information.
FF73
Section_Ff.indd 73
3/4/2008 8:10:19 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZRY324KC-TF5 200/230
ZRY324KC-TF7
380
ZRY324KC-TFD
460
ZRY324KC-TFE
575
ZRY324KCE-TF5 200/230
ZRY324KCE-TF7 380
ZRY324KCE-TFD 460
ZRY324KCE-TFE 575
ZRY375KC-TF5 200/230
ZRY375KC-TF7
380
ZRY375KC-TFD
460
ZRY375KC-TFE
575
ZRY375KCE-TF5 200/230
ZRY375KCE-TF7 380
ZRY375KCE-TFD 460
ZRY375KCE-TFE 575
ZRY432KC-TF5 200/230
ZRY432KC-TF7
380
ZRY432KC-TFD
460
ZRY432KC-TFE
575
ZRY432KCE-TF5 200/230
ZRY432KCE-TF7 380
ZRY432KCE-TFD 460
ZRY432KCE-TFE 575
ZRY480K3-TW5 200/230
ZRY480K3-TW7
380
PH
Max
RLA
LRA
Winding Resistance
Start or Line/Line
Run
Run Cap PN
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
See Section F Introduction for more information.
FF74
Section_Ff.indd 74
3/4/2008 8:10:19 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZRY480K3-TWC 208/230
ZRY480K3-TWD
460
ZRY480K3-TWE
575
ZRY480K3E-TW5 200/230
ZRY480K3E-TW7 380
ZRY480K3E-TWC208/230
ZRY480K3E-TWD 460
ZRY480K3E-TWE 575
ZRY480KC-TFD
460
ZRY480KC-TW5 200/230
ZRY480KC-TW7
380
ZRY480KC-TWD 460
ZRY480KC-TWE 575
ZRY480KCE-TFD 460
ZRY480KCE-TW5200/230
ZRY480KCE-TW7 380
ZRY480KCE-TWD 460
ZRY480KCE-TWE 575
ZRY570K3-TW5 200/230
ZRY570K3-TW7
380
ZRY570K3-TWC 208/230
ZRY570K3-TWD
460
ZRY570K3-TWE
575
ZRY570K3E-TW5 200/230
ZRY570K3E-TW7 380
ZRY570K3E-TWC208/230
PH
Max
RLA
LRA
Winding Resistance
Start or Line/Line
Run
Run Cap PN
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
See Section F Introduction for more information.
FF75
Section_Ff.indd 75
3/4/2008 8:10:20 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZRY570K3E-TWD 460
ZRY570KC-TFD
460
ZRY570KC-TW5 200/230
ZRY570KC-TW7
380
ZRY570KC-TWD 460
ZRY570KC-TWE 575
ZRY570KCE-TFD 460
ZRY570KCE-TW5200/230
ZRY570KCE-TW7 380
ZRY570KCE-TWD 460
ZRY570KCE-TWE 575
ZRY750KC-TW5 200/230
ZRY750KC-TW7
380
ZRY750KC-TWC 208/230
ZRY750KC-TWD 460
ZRY750KC-TWE 575
ZRY750KCE-TW5200/230
ZRY750KCE-TW7 380
ZRY750KCE-TWC208/230
ZRY750KCE-TWD 460
ZRY750KCE-TWE 575
ZRY900KC-TW5 208/230
ZRY900KC-TW7
380
ZRY900KC-TWC 208/230
ZRY900KC-TWD 460
ZRY900KC-TWE 575
PH
Max
RLA
LRA
Winding Resistance
Start or Line/Line
Run
Run Cap PN
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
See Section F Introduction for more information.
FF76
Section_Ff.indd 76
3/4/2008 8:10:20 AM
Electrical Data - Copeland Scroll®
Model
Volts
ZRY900KCE-TW5208/230
ZRY900KCE-TW7 380
ZRY900KCE-TWC208/230
ZRY900KCE-TWD 460
ZRY900KCE-TWE 575
ZRY930KC-TW7
380
ZRY930KC-TWC 208/230
ZRY930KC-TWD 460
ZRY930KCE-TW7 380
ZRY930KCE-TWC208/230
ZRY930KCE-TWD 460
ZS11M4-TW7
380
ZS11M4-TWC
208/230
ZS11M4-TWD
460
ZS11M4-TWE
575
ZS11M4E-TW7
380
ZS11M4E-TWC 208/230
ZS11M4E-TWD
460
ZS11M4E-TWE
575
ZS15K4-PFV
208/230
ZS15K4-TF5
200/230
ZS15K4-TFD
460
ZS15K4E-PFV 208/230
ZS15K4E-TF5
200/230
ZS15K4E-TFD
460
ZS19K4-PFV
208/230
PH
Max
RLA
LRA
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
1
3
3
1
3
3
1
25
48.2
22.1
17.9
32.5
60
28.2
22.5
13.6
7.9
3.6
13.6
9.3
4.3
16.4
239
425
187
148
239
425
187
148
61
55
27
61
55
27
73
Winding Resistance
Start or Line/Line
Run
0.52
0.19
0.72
1.1
0.52
0.19
0.72
1.1
2.28
1.79
7.1
2.28
1.79
7.1
1.72
0
0
0
0
0
0
0
0
1.01
0
0
1.01
0
0
0.833
Run Cap PN
014-0064-08
014-0064-08
014-0064-25
See Section F Introduction for more information.
FF77
Section_Ff.indd 77
3/4/2008 8:10:20 AM
Electrical Data - Copeland Scroll®
Model
Volts
PH
Max
RLA
LRA
ZS19K4-TF5
ZS19K4-TFD
ZS19K4E-PFV
ZS19K4E-TF5
ZS19K4E-TFD
ZS21K4-PFV
ZS21K4-TF5
ZS21K4-TFD
ZS21K4E-PFV
ZS21K4E-TF5
ZS21K4E-TFD
ZS21K4E-TFE
ZS26K4-PFV
ZS26K4-TF5
ZS26K4-TFD
ZS26K4E-PFV
ZS26K4E-TF5
ZS26K4E-TFD
ZS26K4E-TFE
ZS30K4-PFV
ZS30K4-TF5
ZS30K4-TFD
ZS30K4E-PFV
ZS30K4E-TF5
ZS30K4E-TF7
ZS30K4E-TFD
200/230
460
208/230
200/230
460
208/230
200/230
460
208/230
200/230
460
575
208/230
200/230
460
208/230
200/230
460
575
208/230
200/230
460
208/230
200/230
380
460
3
3
1
3
3
1
3
3
1
3
3
3
1
3
3
1
3
3
3
1
3
3
1
3
3
3
7.9
3.9
16.4
9.6
5
17.9
10
5
16.4
11.1
5.7
4.3
20.7
12.5
6.4
20.7
13.6
7.1
5
26.4
15
6.8
26.8
15
8.2
8.2
63
31
73
63
31
88
77
39
88
77
39
31
109
88
44
109
88
44
34
129
99
49.5
129
99
57
49.5
Winding Resistance
Start or Line/Line
Run
1.46
5.94
1.72
1.46
5.94
1.46
1.234
4.83
1.46
1.234
4.83
7.89
1.28
0.995
1.85
1.28
0.995
1.85
6.28
0.779
0.911
3.64
0.779
0.911
2.78
3.64
0
0
0.833
0
0
0.691
0
0
0.691
0
0
0
0.54
0
0
0.54
0
0
0
0.432
0
0
0.432
0
0
0
Run Cap PN
014-0064-25
014-0064-29
014-0064-29
014-0064-26
014-0064-26
014-0064-26
014-0064-26
See Section F Introduction for more information.
FF78
Section_Ff.indd 78
3/4/2008 8:10:21 AM
Electrical Data - Copeland Scroll®
Model
ZS30K4E-TFE
ZS38K4-PFJ
ZS38K4-TF5
ZS38K4-TFD
ZS38K4E-PFJ
ZS38K4E-PFV
ZS38K4E-TF5
ZS38K4E-TF7
ZS38K4E-TFD
ZS38K4E-TFE
ZS45K4-TF5
ZS45K4-TFD
ZS45K4E-TF5
ZS45K4E-TF7
ZS45K4E-TFD
ZS45K4E-TFE
ZS56K4-TW7
ZS56K4-TWC
ZS56K4-TWD
ZS56K4-TWE
ZS56K4E-TW7
ZS56K4E-TWC
ZS56K4E-TWD
ZS56K4E-TWE
ZS75K4-TW7
ZS75K4-TWC
Volts
PH
Max
RLA
LRA
575
265
200/230
460
265
208/230
200/230
380
460
575
200/230
460
200/230
380
460
575
380
208/230
460
575
380
208/230
460
575
380
208/230
3
1
3
3
1
1
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
8.2
22.9
16.4
8.6
26.4
31.8
21.4
11.4
9.6
7.9
20
8.9
23.9
12.6
9.3
7.9
14.3
22.9
11.4
8.9
18.6
30
15.7
8.9
16.6
30.1
40
160
123
62
160
169
123
64
62
50
156
70
156
70
70
54
112
189
99
74
112
189
99
74
151
278
Winding Resistance
Start or Line/Line
Run
5.72
1.224
0.686
2.75
1.224
0.605
0.686
2.28
2.75
4.31
0.501
2.27
0.501
1.92
2.27
3.56
1.03
0.37
1.41
2.3
1.03
0.37
1.41
2.3
0.72
0.26
0
0.417
0
0
0.417
0.329
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Run Cap PN
014-0064-26
014-0064-26
014-0064-27
See Section F Introduction for more information.
FF79
Section_Ff.indd 79
3/4/2008 8:10:21 AM
Electrical Data - Copeland Scroll®
Model
ZS75K4-TWD
ZS75K4-TWE
ZS75K4E-TW7
ZS75K4E-TWC
ZS75K4E-TWD
ZS75K4E-TWE
ZS92K4-TW7
ZS92K4-TWC
ZS92K4-TWD
ZS92K4-TWE
ZS92K4E-TW7
ZS92K4E-TWC
ZS92K4E-TWD
ZS92K4E-TWE
ZX15KC-TFD
ZX15KCE-TFD
ZX21KC-TFD
ZX21KCE-TFD
ZX30KC-TFD
ZX30KCE-TFD
ZX38KC-TFD
ZX38KCE-TFD
ZX45KC-TFD
ZX45KCE-TFD
ZX51KC-TFD
ZX51KCE-TFD
Volts
PH
Max
RLA
LRA
460
575
380
208/230
460
575
380
208/230
460
575
380
208/230
460
575
460
460
460
460
460
460
460
460
460
460
460
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
16.4
11.6
23.9
43.6
21.1
16.1
22.9
40.7
20
15.4
28.2
52.9
25
20
4.3
5
5.7
6.1
7.4
7.5
8.9
9.6
11.5
10.1
12.1
11.8
127
100
151
278
127
100
195
350
158
125
195
350
158
125
27
27
39
39
47.5
47.5
63
63
70
70
100
100
Winding Resistance
Start or Line/Line
Run
1.02
1.7
0.72
0.26
1.02
1.7
0.57
0.22
0.83
1.28
0.57
0.22
0.83
1.28
7.1
7.1
4.83
4.83
3.65
3.65
2.72
2.72
2.27
2.27
1.79
1.79
Run Cap PN
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
See Section F Introduction for more information.
FF80
Section_Ff.indd 80
3/4/2008 8:10:22 AM
Electrical Data - Copeland Scroll®
Model
ZXI09KC-TFD
ZXI09KCE-TFD
ZXI18KC-TFD
ZXI18KCE-TFD
Volts
PH
Max
RLA
LRA
460
460
460
460
3
3
3
3
5.7
6
11.1
11.1
41
41
70
70
Winding Resistance
Start or Line/Line
Run
2.26
2.26
Run Cap PN
0
0
See Section F Introduction for more information.
FF81
Section_Ff.indd 81
3/4/2008 8:10:22 AM
Electrical Data - Copeland Screw™
Model
Voltage
PH
Max RLA
LRA
SCA2-11HE-FWC
SCA2-11HE-FWD
SCA2-11HE-TWE
SCA2-12HE-FWC
SCA2-12HE-FWD
SCA2-12HE-TWE
SCA2-14HE-FWC
SCA2-14HE-FWD
SCA2-14HE-TWE
SCA2-16HE-EWD
SCA2-16HE-EWE
SCA2-18HE-EWD
SCA2-18HE-EWE
SCA2-21HE-EWD
SCA2-21HE-EWE
SCA2-24HE-EWD
SCA2-24HE-EWE
SCA2-350E-FWC
SCA2-350E-FWD
SCA2-350E-TWE
SCA2-400E-FWC
SCA2-400E-FWD
SCA2-400E-TWE
SCA2-500E-FWC
SCA2-500E-FWD
SCA2-500E-TWE
SCA2-600E-FWC
208/230
460
575
208/230
460
575
208/230
460
575
460
575
460
575
460
575
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
265
132.9
105.7
325
162.1
130
312.9
175.7
140
NA
NA
NA
NA
NA
NA
NA
NA
90
44.9
35.9
120
60
48
165
82.1
66
179.3
1807
814
648
2072
958
766
2336
1036
835
1364
1091
1442
1153
1853
1482
2029
1623
535
254
203
737
329
263
743
359
296
939
Half Wdg.RLA
224
Half Wdg.LRA
1250
563
449
1434
663
530
1612
716
577
786
628
831
664
1068
854
1169
935
286
136
108
394
176
141
466
226
186
559
FG1
Section_Fg.indd 1
3/4/2008 8:13:19 AM
Electrical Data - Copeland Screw™
Model
Voltage
PH
Max RLA
LRA
SCA2-600E-FWD
SCA2-600E-TWE
SCA2-700E-FWC
SCA2-700E-FWD
SCA2-700E-TWE
SCA2-800E-FWC
SCA2-800E-FWD
SCA2-800E-TWE
SCA2-801E-FWC
SCA2-801E-FWD
SCA2-801E-TWE
SCA2-900E-FWC
SCA2-900E-FWD
SCA2-900E-TWE
SCA2-901E-FWC
SCA2-901E-FWD
SCA2-901E-TWE
SCH1-5000-FWC
SCH1-5000-FWD
SCH1-5000-TWE
SCH1-6000-FWC
SCH1-6000-FWD
SCH1-6000-TWE
SCH1-7000-FWC
SCH1-7000-FWD
SCH1-7000-TWE
SCH1-8000-FWC
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
89.3
71.4
192.1
96.4
77.1
218.6
109.3
87.9
202.9
94.3
80
231.4
115.7
92.1
241.4
112.9
96.4
153.6
74
59.3
198.6
95
75.7
200
95.7
76.4
209.3
449
357
1021
485
412
1416
632
505
1386
556
483
1522
690
555
1506
703
603
743
355
281
939
449
322
1015
485
404
1224
Half Wdg.RLA
Half Wdg.LRA
267
212
669
303
259
966
433
346
845
339
295
1053
477
384
918
426
367
431
206
180
559
267
208
607
290
260
732
FG2
Section_Fg.indd 2
3/4/2008 8:13:25 AM
Electrical Data - Copeland Screw™
Model
Voltage
PH
Max RLA
LRA
SCH1-8000-FWD
SCH1-8000-TWE
SCH1-9000-FWC
SCH1-9000-FWD
SCH1-9000-TWE
SCH2-11H0-FWC
SCH2-11H0-FWD
SCH2-11H0-TWE
SCH2-11HE-FWC
SCH2-11HE-FWD
SCH2-11HE-TWE
SCH2-12H0-FWC
SCH2-12H0-FWD
SCH2-12H0-TWE
SCH2-12HE-FWC
SCH2-12HE-FWD
SCH2-12HE-TWE
SCH2-14H0-FWC
SCH2-14H0-FWD
SCH2-14H0-TWE
SCH2-14HE-FWC
SCH2-14HE-FWD
SCH2-14HE-TWE
SCH2-18H0-EWD
SCH2-18H0-EWE
SCH2-18HE-EWD
SCH2-18HE-EWE
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
460
575
460
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
100
80
243.6
116.4
92.9
284.3
142.1
113.6
272.9
136.4
109.3
317.1
158.6
127.1
302.1
151.4
120.7
359.3
179.3
143.6
330.7
165.7
132.1
NA
NA
NA
NA
585
433
1435
686
546
1988
895
713
1988
895
713
2279
1054
843
2279
1054
843
2569
1139
918
2569
1139
918
1546
1236
1546
1236
Half Wdg.RLA
Half Wdg.LRA
350
279
885
423
358
1375
619
494
1375
619
494
1577
729
583
1577
729
583
1773
788
635
1773
788
635
515
412
515
412
FG3
Section_Fg.indd 3
3/4/2008 8:13:25 AM
Electrical Data - Copeland Screw™
Model
Voltage
PH
Max RLA
LRA
SCH2-21H0-EWD
SCH2-21H0-EWE
SCH2-21HE-EWD
SCH2-21HE-EWE
SCH2-24H0-EWD
SCH2-24H0-EWE
SCH2-24HE-EWD
SCH2-24HE-EWE
SCH2-28H0-EWD
SCH2-28H0-EWE
SCH2-28HE-EWD
SCH2-28HE-EWE
SCH2-30H0-EWD
SCH2-30H0-EWE
SCH2-30HE-EWD
SCH2-30HE-EWE
SCH2-5000-FWC
SCH2-5000-FWD
SCH2-5000-TWE
SCH2-500E-FWC
SCH2-500E-FWD
SCH2-500E-TWE
SCH2-6000-FWC
SCH2-6000-FWD
SCH2-6000-TWE
SCH2-600E-FWC
SCH2-600E-FWD
460
575
460
575
460
575
460
575
460
575
460
575
460
575
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
115.7
57.9
46.4
137.1
68.6
55
164.3
82.1
65.7
164.3
82.1
1742
1393
1742
1393
2000
1600
2000
1600
2520
2016
2520
2016
2520
2016
2520
2016
939
411
329
939
411
329
1162
508
406
1162
508
Half Wdg.RLA
Half Wdg.LRA
584
467
584
467
667
534
667
534
805
644
805
644
805
644
805
644
498
218
174
498
218
174
616
269
215
616
269
FG4
Section_Fg.indd 4
3/4/2008 8:13:25 AM
Electrical Data - Copeland Screw™
Model
Voltage
PH
Max RLA
LRA
SCH2-600E-TWE
SCH2-7000-FWC
SCH2-7000-FWD
SCH2-7000-TWE
SCH2-700E-FWC
SCH2-700E-FWD
SCH2-700E-TWE
SCH2-8000-FWC
SCH2-8000-FWD
SCH2-8000-TWE
SCH2-800E-FWC
SCH2-800E-FWD
SCH2-800E-TWE
SCH2-9000-FWC
SCH2-9000-FWD
SCH2-9000-TWE
SCH2-900E-FWC
SCH2-900E-FWD
SCH2-900E-TWE
SHL1-12H0-FWC
SHL1-12H0-FWD
SHL1-12H0-TWE
SHL1-2000-TWE
SHL1-2000-TWK
SHL1-2000-TWK
SHL1-2500-TWE
SHL1-2500-TWK
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
575
208/230
460
575
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
65.7
200
95.7
76.4
188.6
90.7
72.9
209.3
100
80
225.7
108.6
87.1
243.6
116.4
92.9
250.7
120.7
97.1
NA
NA
NA
32.9
81.4
40.7
34.3
85.7
406
1015
485
404
1015
485
404
1224
585
433
1224
585
433
1435
686
546
1435
686
546
943
943
943
183
492
246
166
436
Half Wdg.RLA
Half Wdg.LRA
40.5
215
607
290
260
607
290
260
732
350
279
732
350
279
885
423
358
885
423
358
612
612
612
127
164
42.5
94
150
125.5
60
125.5
60
48
131.5
63
131.5
63
50.5
152.5
73
152.5
73
58
FG5
Section_Fg.indd 5
3/4/2008 8:13:26 AM
Electrical Data - Copeland Screw™
Model
Voltage
PH
Max RLA
LRA
SHL1-2500-TWK
SHL1-3000-TWE
SHL1-3000-TWK
SHL1-3000-TWK
SHL1-4000-FWC
SHL1-4000-FWD
SHL1-4000-TWE
SHL1-5000-FWC
SHL1-5000-FWD
SHL1-5000-TWE
SHL1-6000-FWC
SHL1-6000-FWD
SHL1-6000-TWE
SHL1-7000-FWC
SHL1-7000-FWD
SHL1-7000-TWE
SHL1-7500-FWC
SHL1-7500-FWD
SHL1-7500-TWE
SHL2-2000-TWE
SHL2-2000-TWK
SHL2-2000-TWK
SHL2-2500-FWD
SHL2-2500-TWE
SHL2-2500-TWK
SHL2-2500-TWK
SHL2-3000-TWE
460
575
208/230
460
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
575
208/230
460
460
575
208/230
460
575
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
42.9
41.4
84.3
52.1
162.9
77.9
62.1
171.4
82.1
70.7
176.4
91.4
84.3
213.6
82.9
80.7
224.3
95
85.7
32.9
81.4
40.7
42.9
34.3
85.7
42.9
41.4
218
204
532
266
655
313
222
743
355
281
939
449
322
1015
485
404
1224
585
433
183
492
246
218
166
436
218
204
Half Wdg.RLA
Half Wdg.LRA
52
131
184
40.5
391
187
147
431
206
180
559
267
208
607
290
260
732
350
279
127
164
42.5
94
150
131
FG6
Section_Fg.indd 6
3/4/2008 8:13:26 AM
Electrical Data - Copeland Screw™
Model
Voltage
PH
Max RLA
LRA
SHL2-3000-TWK
SHL2-3000-TWK
SHM1-11H0-FWC
SHM1-11H0-FWD
SHM1-11H0-TWE
SHM1-12H0-FWC
SHM1-12H0-FWD
SHM1-12H0-TWE
SHM1-14H0-FWC
SHM1-14H0-FWD
SHM1-14H0-TWE
SHM1-3000-TWE
SHM1-3000-TWK
SHM1-3000-TWK
SHM1-3500-TWE
SHM1-3500-TWK
SHM1-3500-TWK
SHM1-4000-TWE
SHM1-4000-TWK
SHM1-4000-TWK
SHM1-5000-FWC
SHM1-5000-FWD
SHM1-5000-TWE
SHM1-6000-FWC
SHM1-6000-FWD
SHM1-6000-TWE
SHM1-7000-FWC
208/230
460
208/230
460
575
208/230
460
575
208/230
460
575
575
208/230
460
575
208/230
460
575
208/230
460
208/230
460
575
208/230
460
575
208/230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
84.3
52.1
NA
NA
NA
NA
NA
NA
NA
NA
NA
37.1
92.9
46.4
48.6
98.6
60.7
52.1
130
65
184.3
88.6
70.7
238.6
95
91.4
210.7
532
266
801
801
801
943
943
943
1023
1023
1023
166
436
218
204
532
266
255
622
311
743
355
281
939
449
322
1015
Half Wdg.RLA
Half Wdg.LRA
52
184
46
520
520
520
612
612
612
665
665
665
94
150
60
131
184
65
166
218
431
206
180
559
267
208
607
FG7
Section_Fg.indd 7
3/4/2008 8:13:26 AM
Electrical Data - Copeland Screw™
Model
Voltage
PH
Max RLA
LRA
SHM1-7000-FWD
SHM1-7000-TWE
SHM1-8000-FWC
SHM1-8000-FWD
SHM1-8000-TWE
SHM1-9000-FWC
SHM1-9000-FWD
SHM1-9000-TWE
SHM2-3000-TWE
SHM2-3000-TWK
SHM2-3000-TWK
SHM2-3500-TWE
SHM2-3500-TWK
SHM2-3500-TWK
SHM2-4000-TWE
SHM2-4000-TWK
SHM2-4000-TWK
SHMS-4000-FWD
460
575
208/230
460
575
208/230
460
575
575
208/230
460
575
208/230
460
575
208/230
460
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
95.7
80.7
245
117.1
93.6
255.7
122.1
97.9
37.1
92.9
46.4
48.6
98.6
60.7
52.1
130
65
88.6
485
404
1224
585
433
1435
686
546
166
436
218
204
532
266
255
622
311
313
Half Wdg.RLA
Half Wdg.LRA
46
290
260
732
350
279
885
423
358
94
150
60
131
184
65
166
218
187
FG8
Section_Fg.indd 8
3/4/2008 8:13:26 AM
SECTION G
WIRING DIAGRAMS
The wiring diagram guide lists compressors by model designation. These are indexed against an Electrical Characteristics
code. (The third group of numbers in the model number.) The
third letter of third group of the model number may be missing.
It may be any one of a number of letters representing electrical
characteristics.
These diagrams represent typical wiring connections for the
compressors listed but may not be identical to the diagram in the
compressor terminal box.
Discontinued wiring diagrams listed in the back of this section
are for compressors that are no longer available by Emerson
Climate Technologies, Inc. The replacement wiring diagram is
not necessary the same as the old wiring diagram show in the
front of this section. Use caution when selecting the appropriate
wiring diagram.
This section contains current information on Copeland® brand products.
Information on obsolete models can be obtained from your local Emerson
Climate Technologies wholesaler.
G1
WELDED COMPRESSORS DIAGRAMS
MODEL
TF*
ES8
TS*
(5) 0770
(1,5) 005-1211-01
CT
1319
MODEL
IA*
0831/0832
0776/0777
0780
0769
A-LINE
0929
1223
(1)
(2)
(3)
(4)
(5)
(6)
1318
0865
(1) 005-0670
0768
0833
0778/0779
R
CSV
(1,5) 005-1211
(5) 0782
(1,3) 005-1210
(1,3) 005-1212
CR , CS
R
(2) PF*
SAA
0930
CA*
(2) PA*
0767
0818/0819
0820
0774/0775
0834
0781
0932
0932
CF*
TF*
0931
0980
DIAGRAM MOLDED IN COMPRESSOR TERMINAL BOX.
MAY REQUIRE PTC THERMISTOR
59 FRAME
70 FRAME
63 FRAME
4 PIN SENSOR CONNECTION
NOTE: ASTERISK AFTER FIRST TWO LETTERS INDICATES MAY
BE ANY LETTER DEPENDING ON ELECTRICAL
CHARACTERISTICS.
G2
SCROLL DIAGRAMS
MODEL
TF*
(2) PF*
ZB30-45K, ZF13-18K,
ZS30-45K, ZMD18K,
ZBD30-45K, ZBH30-45K
(REFR)
ZR46-81K, ZRD49-72K,
ZP54-57K
(AC)
(3) 0880
(1,3)
005-1213
ZF6-11K, ZS15-26K, ZB15-26K,
ZBH21K
(REFR)
ZR28-48K, ZP32-44K
(AC)
(1,4,5)
005-1270
(1,4,5)
005-1270
ZB50-88K (REFR)
ZR84-144K (AC)
(1) 005-1271
ZC40,60C
CRYO
(3) 0880
TW*
(1,3)
005-1213
ZR90K, ZR11-19M
ZP180K (AC)
1201
ZF24-48K, ZB,ZS56-92K,
ZB,ZS11M (REFR)
0906
ZB10-14K, ZBH11-14K
(REFR)
ZR16-24K, ZP16-23K
(AC)
(1,4,5)005-1270
(1,4,5) 005-1270
ZP235- ZP295K, ZR250,300K,
ZR310,380K
Large Commercial Scroll (LCS)
ZR22 - ZR 61, ZF09 - 11, ZX21,
ZS21-26, VR61
(1)
(2)
(3)
(4)
(5)
0953
1199
DIAGRAM MOLDED IN COMPRESSOR TERMINAL BOX.
MAY REQUIRE PTC THERMISTOR
70 FRAME
63 FRAME
FOR PROPER WIRING SEE SYSTEM WIRING DIAGRAM
NOTE: ASTERISK AFTER FIRST TWO LETTERS INDICATES MAY
BE ANY LETTER DEPENDING ON ELECTRICAL
CHARACTERISTICS.
G3
COPELAMETIC DIAGRAMS
MODEL
TF*
ES*
M
0803
N
0803
2D
0803
(5,6) 0897
3D
0803, 0816
(4) 0840
0837
(5,6) 0897
ESM
TS*
(6) 0900
4
(5,6) 0897
(6) 0900
(6) 2169
(7) 1851
6
(5,6) 0897
(6) 0900
(6) 2169
8
9
(6) 2169
0803
0837
(5,6) 0897
(6) 0900
MODEL
XAA
IA*
SAA
CAF/CAG
H
0809
0809
0809
(3) 0822
K
0809
0809
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(3) 0822
SIX LEAD MOTOR
THREE LEAD MOTOR
50 HERTZ APPLICATIONS
VDE GROUNDING
SMALLER VERSION OF 0899
DUAL VOLTAGE MODULE
24 VOLT MODULE
NOTE: ASTERISK AFTER FIRST TWO LETTERS INDICATES MAY
BE ANY LETTER DEPENDING ON ELECTRICAL
CHARACTERISTICS.
G4
COPELAMETIC DIAGRAMS
MODEL
CFB
(1) FS*
(1) TSE
(1) TSU
TA*
E
0807
0821
0806
H
0807
0810
K
0807
0810
L
0802
0805
M
0804
N
0804
2D
0804
3
(2)TSE (2) TS7
(2)TSU (2) TSC
(6) 2170
(5,6) 0914
(6) 2170
0807
0806
3D
(6) 2170
4
(6) 2170
(6) 0902
(7)1852
(6) 2167
6
(6) 2170
(6) 0902
(6) 2167
8
(6) 2170
(6) 2167
(6) 2170
(6) 2167
9
(1)
(2)
(3)
(4)
(5)
(6)
(7)
CA*
0804
SIX LEAD MOTOR
THREE LEAD MOTOR
50 HERTZ APPLICATIONS
VDE GROUNDING
SMALLER VERSION OF 0899
DUAL VOLTAGE MODULE
24 VOLT MODULE
NOTE: ASTERISK AFTER FIRST TWO LETTERS INDICATES MAY
BE ANY LETTER DEPENDING ON ELECTRICAL
CHARACTERISTICS.
G5
The following tables lists discontinued wiring diagrams and their
replacements.
MODEL
VOLTAGE
OLD
DIAGRAM
NEW
DIAGRAM
JR
IFA
0784
No Replacement
J,XH
IA*
005-0655
005-0697
No Replacement
J,XH
SAA
0813
No Replacement
J,XH
CA*
0820
No Replacement
J,XH
PA*
0781
No Replacement
BR/QR
ES*
0758
0875
BR/QR
TS*
0716
0875
BR/QR
EW8
0825
0875 (ES8)
BR/QR
TS*
0874
0948
BR/QR
ES8
0875
0949
BR/QR
TF*
005-0492
005-0922
BR/QR
TF*
005-0637
005-0922
BR/QR
ES*
0815
0875
BR/QR
TF*
005-0922
005-1043
BR/QR
TF*
005-1043
No Replacement
BR/QR
ES8
0883
No Replacement
BR/QR
TS*
0882
No Replacement
BR/QR
TS*
0948
No Replacement
CR
ES*
0757
0875
CR
EW8
0825
0875
CR
ES*
0876
0875
CR
EW8
0823
No Replacement
CR
ES*
0811
0875
G6
MODEL
VOLTAGE
OLD
DIAGRAM
NEW
DIAGRAM
CR
EW8
0824
0875
CR, CS
ES*
0801
No Replacement
CT
CSV
0751
0884
CT
TS*
0752
0885
CR 63FR
PF*
005-0678
005-0799
CR
PF*
005-0679
005-0799
CV
TF*
0770
No Replacement
CR
ES8
0875
0917
CT
CSV
0884
0918
CT
TS*
0885
0919
CR
ES8
0917
0949
CT
TS*
0919
1319
CT
CSV
0918
1318
ZF,ZS,ZB,
ZR,ZP,ZB
TF*
0826
0880
ASPEN
PF*
005-0838
No Replacement
ASPEN
TF*
1196
No Replacement
ASPEN
PF*
005-0706
No Replacement
ZF,ZS,ZB
PF*
005-0788
005-0837
ZF,ZS,ZB
PF*
005-0777
005-0819
ZF,ZS,ZB
PF*
005-0819
005-0840
ASPEN
PF*
0756
No Replacement
ZB
PF*
005-0788
005-0837
ZB
PF*
005-0837
005-0860
ZB,ZF
PF*
005-0777
005-0819
ZB,ZF,ZS
PF*
005-0819
005-0840
ZR (AC)
TW*
1825
1201
G7
MODEL
VOLTAGE
OLD
DIAGRAM
NEW
DIAGRAM
ZF,ZS,ZB
(REFR)
TW*
1825
0906
ZB
PF*
005-0840
005-1062
ZB,ZR
TF*
005-0868
005-0922
ZB,ZR
TF*
005-0922
005-1043
ZB, ZS, ZF,
ZRD, ZP
PF*
005-0860
005-1071
9
THC,TLC
0748
0853 (TSC)
9
THC,TLC
0748
0803 (TFC)
9
THD,TLD
0748
0803 (TFD)
9
THE,TLE
0748
0803 (TFE)
9
FS*
0856
0899, See note 2
9
ESM
0858
0900, See note 2
9
TS*
0853
0896, See note 2
9
TSE,TSU,TSC,TS7
0896
2167
9
FS*,TSE,TSU
0899
2170
4/6
TSE
0759
No Replacement
4/6
FS*,TSE, TSU
0841
0857
4/6
TSE,TSU, TS7
0760
0853, See note 1
4/6
ES*
0762
0854, See note 1
4/6
ESM
0848
0858, See note 1
4/6,8
TS*
0763
0855, See note 1
4/6,8
FS*
0765
0856, See note 1
G8
MODEL
VOLTAGE
4/6,8
TS*
4/6,8
4/6,8
OLD
DIAGRAM
NEW
DIAGRAM
0898
2169
TSE,TSU,TSC,TS7
0896
2167
FS*,TSE,TSU
0899
2170
4/6
TSE/TSU
0765
0856, See note 1
4DK6, 4DS6
FSD
0902
1299, See note 2
4DK6, 4DS6
FSD
1299
2177, See note 2
4,6
FS*
0857
0902, See note 2
4,6
TSE
0853
0896, See note 2
4,6
TS*
0855
0898,See note 2
4,6
ESM
0858
0900, See note 2
8
TS*
0855
0898, See note 2
8
TS7
0853
0896, See note 2
M
FSC
0849
0859, See Note 1
M
FS*
0856
0899, See note 2
M
FS*
0859
0914, See note 2
M
ES*
0854
0897, See note 2
2D
FS*
0856
0899, See note 2
2D
ES*
0854
0897, See note 2
3D
ES*
0854
0897, See note 2
Notes:
1. Models replaced with dual voltage 31aa module.
(Requires a jumper wire from L2 to LO for 120V and L2 to HI for
240V)
2. Models replaced with dual voltage 41aa module.
(Jumper wire not required)
G9
Wiring Diagram 005-0670
G10
Wiring Diagram 0767
G11
Wiring Diagram 0768
G12
Wiring Diagram 0769
G13
Wiring Diagram 0770
G14
Wiring Diagram 0774/0775
G15
Wiring Diagram 005-0776, 005-0821
G16
Wiring Diagram 0776/0777
G17
Wiring Diagram 0778/0779
G18
Wiring Diagram 0780
G19
Wiring Diagram 0781
G20
Wiring Diagram 0782
G21
Wiring Diagram 0802
G22
Wiring Diagram 0803
G23
Wiring Diagram 0804
G24
Wiring Diagram 0805
G25
Wiring Diagram 0806
G26
Wiring Diagram 0807
G27
Wiring Diagram 0809
G28
Wiring Diagram 0810
G29
Wiring Diagram 0816
G30
Wiring Diagram 0818/0819
G31
Wiring Diagram 0820
G32
Wiring Diagram 0821
G33
USE COPPER CONDUCTORS ONLY.
USE THIS EQUIPMENT ON A GROUNDED SYSTEM ONLY.
USE MINIMUM 75 C WIRE FOR AMPACITY DETERMINATION.
EXTERNAL MOTOR PROTECTION-ALLOW TIME FOR RESET.
CRANKCASE HEATER, WHEN APPLIED, MUST BE CONNECTED
ONLY TO ITS RATED VOLTAGE.
ON 115 VOLT, CONNECT NEUTRAL TO TERMINAL "1".
OVERCURRENT PROTECTION DEVICE RATING AND TYPE MUST BE
IN ACCORDANCE WITH REGULATORY AGENCY END PRODUCT
APPROVALS-SEE SYSTEM NAMEPLATE.
C
2
1
LINE
R
S
S
R
MOTOR WINDING
CONNECTIONS
START
CAPACITOR
RED
BLUE
BLACK
2
1
5
CURRENT
RELAY
C
YELLOW
RUN CAPACITOR
9-93
Wiring Diagram 0822
G34
052-0822-00
Wiring Diagram 0831/0832
G35
Wiring Diagram 0833
G36
Wiring Diagram 0834
G37
Wiring Diagram 0837
G38
Wiring Diagram 0840
G39
Wiring Diagram 0865
G40
Wiring Diagram 0880
G41
Wiring Diagram 0897 (Top)
G42
Wiring Diagram 0897 (Bottom)
G43
Wiring Diagram 0900 (Top)
G44
Wiring Diagram 0900 (Bottom)
G45
3
FOR USE WITH KRIWAN
SCY (PHASE SENSING)
MODULE ONLY
MOTOR WINDING
CONNECTIONS/
L2 BORNES DES
ENROULEMENTS DU
MOTEUR/
ANSCHLUSS
DER MOTORWICKLUNGEN
L1
INTERNAL THERMAL
SENSORS/
CAPTEURS THERMIQUES
INTERNES/
INTERNE
TEMPERATURSENSOREN
L1 L2 L3
L3
T2 T1 S2 S1 M2 M1
FOR USE WITH
KRIWAN SCY
(PHASE SENSING)
MODULE ONLY
3
1
2
L1
1
2
3
PROTECTOR MODULE VOLTAGE/TENSION DU MODULE DU DISPOSITIF
DE PROTECTION/ANSCHLUSSPANNUNG DES SCHUTZGERAETES
TO CONTROL CIRCUIT/VERS LE CIRCUIT DE
COMMANDE/ZUM STEUERSTROMKREIS
F0R KRIWAN SCY (PHASE SENSING) MODULES ONLY
TO MOTOR TERMINAL BLOCK/VERS BORNES DE
BRANCHMENT DES BOUNES MOTEUR/ZUR BELEGUNG
DER MOTOR KLEMMEN
NOTE:
SOLID STATE MODULE HAS 30 MINUTES
TIME DELAY BEFORE RESET IN EVENT
OF PROTECTOR TRIP.
NOTE:
EN CAS DE DECLENCHEMENT DU MODULE
DE PROTECTION, LE REARMEMENT EST RETARDE
A 30 MINUTES.
NOTIZ:
MOTORSCHUTZGERAET HAT EINE
ZEITVERZOEGERUNG VON 30 MINUTEN ZUM
RUECKSCHALTEN
L2
USE COPPER CONDUCTORS ONLY.
USE A TEMPERATURE OF 75C WHEN DETERMINING
CROSS SECTION OF LEAD FOR MAX CURRENT.
USE THIS EQUIPMENT ON A GROUNDED SYSTEM ONLY.
PRIMARY SINGLE PHASE FAILURE PROTECTION IS PROVIDED.
PROTECTOR MODULE AND OPTIONAL CRANKCASE HEATER MUST
BE CONNECTED ONLY TO THEIR RATED VOLTAGE.
OVERCURRENT PROTECTION DEVICE RATING AND TYPE MUST
BE IN ACCORDANCE WITH REGULATION AND PRODUCT APPROVALS
-SEE SYSTEM NAMEPLATE.
N'UTILISER QUE DES CONDUCTEURS EN CUIVRE.
UTILIER UNE TEMPERATURE ED 75C POUR DETERMINER
LA SECTION DES CABLES POUR LE COURANT MAXIMUM.
EMPLOYER CET EQUIPEMENT SEULEMENT SUR SYSTEME MIS A LA TERRE.
PROTECTION PRIMAIRE MONOPHASEE FOURNIE.
LE MODULE DU DISPOSITIF DE PROTECTION ET LE CHAUFFE-CARTER
FACULTATIF DOIVENT ETRE BRANCHES A LA TENSION NOMINALE
APPROPRIEE.
LE TYPE ET LES CARACTERISTIQUES NOMINALES DU DISPOSITIF DE
PROTECTION CONTRE LES SURINTENSITES DOIVENT ETRE CONFORMES AUX
EXIGENCES DES POUVOIRS DE REGLEMENTATION VISANT LE PRODUIT FINI
-VOIR LA PLAQUE SIGNALETIQUE.
NUR KUPFERLEITUNGEN VERWENDEN.
ZUR BESTIMMUNG DES LEITERQUERSCHNITTS MUESSEN KABEL VERWENDET WERDEN,
DIE FUER EINE BELASTUNG VON HUECHSTENS 75C ZUGELASSEN SIND.
ANLAGE NUR MIT ERDUNG VERWENDEN.
SCHUTZ BEI PHASENAUSFALL AUF DER PRIMAERSEITE IST GEWAEHRLEISTET.
SCHUTZGERAET UND KURBELGEHAEUSEHEIZER (FALLS VORHANDEN)
DUERFEN NUR MIT NENNSPANNUNG BETRIEBEN WERDEN.
NENNLEISTUNG UND TYP DES UEBERSTROMSCHUTZSCHALTERS MUESSEN
IN UEBEREINSTIMMUNG MIT ZUTREFFENDEN VORSCHRIFTEN SEIN
-BITTE TYPENSCHILD BEACHTEN.
Wiring Diagram 0906
G46
L3
6/99
(8525681)
052-0906-00
This page is left blank intentionally.
G47
Wiring Diagram 0914 (Top)
G48
Wiring Diagram 0914 (Bottom)
G49
Wiring Diagram 0929
G50
USE MINIMUM 75C COPPER
WIRE FOR AMPACITY
DETERMINATION. WHEN PROVIDED,
CRANKCASE HEATER AND FAN
MUST BE CONNECTED ONLY TO
THEIR RATED VOLTAGE.
SYSTEM OVERCURRENT
PROTECTION DEVICE RATING
AND TYPE MUST BE IN
ACCORDANCE WITH REGULATORY
AGENCY END PRODUCT
APPROVALS - SEE SYSTEM
NAMEPLATE. FAN LEADS
ARE FACTORY PROVIDED
ON CONDENSING UNITS.
LINE (230V)
NEUTRAL (115V)
CURRENT
RELAY
LINE
FAN
LINE GND
START CAPACITOR
052-0929-00
2
1
8-02
R
S
EXTERNAL
PROTECTOR
C BLK
Wiring Diagram 0930
G51
Wiring Diagram 0931
G52
USE MINIMUM 75C
INTERNAL PROTECTOR
LINE GND
COPPER WIRE FOR
BLK
C
LINE
AMPACITY
FAN
DETERMINATION.
5
LINE
RED
WHEN PROVIDED,
1
(230V) S
CRANKCASE HEATER
R
AND FAN MUST BE
NEUTRAL
2
CONNECTED ONLY TO
(115V)
START
THEIR RATED VOLTAGE.
BLU
CAPACITOR
SYSTEM OVERCURRENT PROTECTION
YEL (WHEN PROVIDED)
DEVICE RATING AND TYPE MUST
RUN CAPACITOR
BE IN ACCORDANCE WITH REGULATORY
(WHEN PROVIDED)
AGENCY END PRODUCT APPROVALS
POTENTIAL RELAY
-SEE SYSTEM NAMEPLATE.
(WHEN PROVIDED)
11-02
052-0931-00
Wiring Diagram 0932
G53
EXTERNAL
LINE GND
USE MINIMUM 75C COPPER
PROTECTOR
WIRE FOR AMPACITY
LINE
C
DETERMINATION.
BLK
WHEN PROVIDED, CRANKCASE
5
HEATER AND FAN MUST BE
1
RED
FAN
LINE S
CONNECTED ONLY
R
(230V)
TO THEIR RATED
2
NEUTRAL
VOLTAGE.
BLU
(115V)
SYSTEM OVERCURRENT
START CAPACITOR
PROTECTION DEVICE RATING
(WHEN PROVIDED)
AND TYPE MUST BE IN
YEL
RUN CAPACITOR
ACCORDANCE WITH REGULATORY
(WHEN PROVIDED)
AGENCY END
PRODUCT APPROVALS
POTENTIAL
RELAY
-SEE SYSTEM NAMEPLATE.
(WHEN
PROVIDED)
11-02
052-0932-00
Wiring Diagram 0953
G54
Wiring Diagram 0980
G55
Wiring Diagram 1199
G56
INTERNAL THERMAL
SENSORS/
CAPTEURS THERMIQUES
INTERNES/
INTERNE
TEMPERATURSENSOREN
T2
T1
1
S2
S1
M2
MOTOR WINDING
CONNECTIONS/
L2 BORNES DES
ENROULEMENTS DU
MOTEUR/
ANSCHLUSS
DER MOTORWICKLUNGEN
L1
L3
M1
2
L1
L3
L2
USE THIS EQUIPMENT ON A GROUNDED SYSTEM ONLY.
PRIMARY SINGLE PHASE FAILURE PROTECTION IS PROVIDED.
PROTECTOR MODULE AND OPTIONAL CRANKCASE HEATER MUST
BE CONNECTED ONLY TO THEIR RATED VOLTAGE.
OVERCURRENT PROTECTION DEVICE RATING AND TYPE MUST
BE IN ACCORDANCE WITH REGULATION AND PRODUCT APPROVALS
-SEE SYSTEM NAMEPLATE.
1
2
PROTECTOR MODULE VOLTAGE/TENSION DU MODULE DU DISPOSITIF
DE PROTECTION/ANSCHLUSSPANNUNG DES SCHUTZGER-TES
TO CONTROL CIRCUIT/VERS LE CIRCUIT DE
COMMANDE/ZUM STEUERSTROMKREIS
NOTE:
SOLID STATE MODULE HAS 30 MINUTES
TIME DELAY BEFORE RESET IN EVENT
OF PROTECTOR TRIP.
NOTE:
EN CAS DE DECLENCHEMENT DU MODULE
DE PROTECTION, LE REARMEMENT EST RETARDE
DE 30 MINUTES.
NOTIZ:
MOTORSCHUTZGER-T HAT EINE ZEITVERZ+GERUNG
VON 30 MINUTEN ZUM R_CKSCHALTEN
EMPLOYER CET EQUIPEMENT SEULEMENT SUR SYSTEME MIS A LA TERRE.
PROTECTION PRIMAIRE MONOPHASEE FOURNIE.
LE MODULE DU DISPOSITIF DE PROTECTION ET LE CHAUFFE-CARTER
FACULTATIF DOIVENT ETRE BRANCHES A LA TENSION NOMINALE
APPROPRIEE.
LE TYPE ET LES CARACTERISTIQUES NOMINALES DU DISPOSITIF DE
PROTECTION CONTRE LES SURINTENSITES DOIVENT ETRE CONFORMES AUX
EXIGENCES DES POUVOIRS DE REGLEMENTATION VISANT LE PRODUIT FINI
-VOIR LA PLAQUE SIGNALETIQUE.
ANLAGE NUR MIT ERDUNG VERWENDEN.
SCHUTZ BEI PHASENAUSFALL AUF DER PRIM-RSEITE IST
GEW-HRLEISTET.
SCHUTZGER-T UND KURBELGEH-USEHEIZER (FALLS VORHANDEN)
D_RFEN NUR MIT NENNSPANNUNG BETRIEBEN WERDEN.
NENNLEISTUNG UND TYP DES _BERSTROMSCHUTZSCHALTERS M_SSEN
IN _BEREINSTIMMUNG MIT ZUTREFFENDEN VORSCHRIFTEN SEIN
-BITTE TYPENSCHILD BEACHTEN.
052-1201-00
Wiring Diagram 1201
G57
CONNECTOR
CONNECTOR
BLOCK
BLOC
K
(WHEN REQD)
REQD)
1
2
3
MOTOR WINDING
WINDING
CONNECTIONS
CONNECTION
S
Wiring Diagram 005-1211-01
G58
8-06
T3
USE COPPER CONDUCTOR
CONDUCTORSS
ONLY..
ONLY
USE THIS EQUIPMENT ON A
GROUNDED SYSTEM ONLY.
ONLY.
FOR
R
USE MINIMUM 75 C WIRE FO
AMPACITY DETERMINATION.
DETERMINATION.
PRIMARY SINGLE PHASE FAILURE
FAILURE
PROTECTION IS PROVIDED.
PROVIDED.
INTERNAL MOTOR PROTECTION-ALLOW
PROTECTION-ALLOW
TIME FOR RESET.
RESET.
CRANKCASE HEATER, WHEN APPLIED,
APPLIED,
MUST BE CONNECTED ONLY TO ITS
ITS
RATED VOLTAGE.
VOLTAGE.
OVERCURRENT PROTECTION DEVICE
DEVICE
RATING AND TYPE MUST BE IN
IN
ACCORDANCE WITH REGULATORY AGENCY
AGENCY
END PRODUCT APPROVALS- SEE SYSTEM
SYSTEM
NAMEPLATE.
NAMEPLATE
.
005-1211-01
T2
T1
005-1213-00
8-06
Wiring Diagram 005-1213
G59
Wiring Diagram 1223
G60
8-02
052-1223-00
START CAPACITOR
NEUTRAL (115V)
USE MINIMUM 75C COPPER
LINE (230V)
CURRENT
WIRE FOR AMPACITY
FAN
RELAY
DETERMINATION.
WHEN PROVIDED, CRANKCASE
LINE
BLACK
HEATER AND FAN MUST BE
4
CONNECTED ONLY TO THEIR
RATED VOLTAGE.
EXTERNAL
SYSTEM OVERCURRENT
PROTECTOR
2 1
C
PROTECTION DEVICE RATING AND
BLACK
TYPE MUST BE IN ACCORDANCE
YELLOW
WITH REGULATORY AGENCY
S
R
RED
END PRODUCT APPROVALS
-SEE SYSTEM NAMEPLATE.
BLACK
LINE GND
BLA CK
005-1270-00
8-06
Wiring Diagram 005-1270
G61
Wiring Diagram 005-1271
G62
Wiring Diagram 1318
G63
Wiring Diagram 1319
G64
Wiring Diagram 1851
G65
Wiring Diagram 1852
G66
This page is left blank intentionally.
G67
Wiring Diagram 2167 (Left Side)
G68
Wiring Diagram 2167 (Right Side)
G69
Wiring Diagram 2169 (Top)
G70
Wiring Diagram 2169 (Bottom)
G71
Wiring Diagram 2170 (Top)
G72
Wiring Diagram 2170 (Bottom)
G73
Wiring Diagram 2177 (Left Side)
G74
Wiring Diagram 2177 (Right Side)
G75
Discontinued
Wiring Diagram 005-0492, 0637
G76
Discontinued
Wiring Diagram 005-0655, 0697
G77
Discontinued
Wiring Diagram 005-0678-00, 005-0679-00
G78
Discontinued
Wiring Diagram 005-0706
G79
Discontinued
Wiring Diagram 0716
G80
This page is left blank intentionally.
G81
Discontinued
Wiring Diagram 0748 (Left Side)
G82
Discontinued
Wiring Diagram 0748 (Right Side)
G83
Discontinued
Wiring Diagram 0751
G84
Discontinued
Wiring Diagram 0752
G85
Discontinued
Wiring Diagram 0756
G86
Discontinued
Wiring Diagram 0757
G87
Discontinued
Wiring Diagram 0758
G88
Discontinued
Wiring Diagram 0759
G89
Discontinued
Wiring Diagram 0760
G90
This page is left blank intentionally.
G91
Discontinued
Wiring Diagram 0762 (Left Side)
G92
Discontinued
Wiring Diagram 0762 (Right Side)
G93
Discontinued
Wiring Diagram 0763 (Left Side)
G94
Discontinued
Wiring Diagram 0763 (Right Side)
G95
Discontinued
Wiring Diagram 0765 (Left Side)
G96
Discontinued
Wiring Diagram 0765 (Right Side)
G97
Discontinued
Wiring Diagram 005-0777
G98
Discontinued
Wiring Diagram 0784
G99
Discontinued
Wiring Diagram 005-0788
G100
4-95
005-0799-00
Discontinued
Wiring Diagram 005-0799-00, 005-0800-00
G101
CONNECTOR
CONNECTOR
BLOCK
BLOC
K
(WHEN REQD)
REQD)
1
2
3
MOTOR WINDING
WINDING
CONNECTIONS
CONNECTION
S
Discontinued
Wiring Diagram 005-0800-01
G102
4-95
T3
USE COPPER CONDUCTOR
CONDUCTORSS
ONLY..
ONLY
USE THIS EQUIPMENT ON A
GROUNDED SYSTEM ONLY
ONLY.
.
FOR
R
USE MINIMUM 75 C WIRE FO
AMPACITY DETERMINATION.
DETERMINATION.
PRIMARY SINGLE PHASE FAILURE
FAILURE
PROTECTION IS PROVIDED.
PROVIDED.
INTERNAL MOTOR PROTECTION-ALLOW
PROTECTION-ALLOW
TIME FOR RESET.
RESET.
CRANKCASE HEATER, WHEN APPLIED,
APPLIED,
MUST BE CONNECTED ONLY TO ITS
ITS
RATED VOLTAGE
VOLTAGE.
.
OVERCURRENT PROTECTION DEVICE
DEVICE
RATING AND TYPE MUST BE IN
IN
ACCORDANCE WITH REGULATORY AGENCY
AGENCY
END PRODUCT APPROVALS- SEE SYSTEM
SYSTEM
NAMEPLATE.
NAMEPLATE
.
005-0800-01
T2
T1
Discontinued
Wiring Diagram 0801
G103
Discontinued
Wiring Diagram 0811
G104
U1
W3
V2
X4
RESISTANCE ACROSS MOTOR SENSORS SHOUL
SHOULD
BE APPROXIMATELY 1500 T0 7800 OHM
OHMS
WITH A MOTOR TEMPERATURE BELOW 60 C
C.
USE OHMMETER ONLY (6 VOLTS MAXIMUM) T
TO
CHECK SENSOR RESISTANCE. DO NOT SHOR
SHORT
ACROSS THE TERMINALS
TERMINALS.
WHEN CHECKING SOLID STATE MODULE:
MODULE
X S S1
LINE
M2 T1 T2
CONTROL
CIRCUIT
M1
PROTECTOR MODULE
MODUL
VOLTAGE
VOLTAG
MAI
MAIN
L1 L2 L3
DELTA CONNECTED
CONNECTE
TO CONTROL
CONTRO
CIRCUIT
CIRCUI
Z6
M1
X S S1
LINE
M2 T1 T2
CONTROL
CIRCUIT
U1
USE COPPER CONDUCTORS ONLY.
ONLY
USE MINIMUM 75 C WIRE FOR
FO
AMPACITY DETERMINATION.
DETERMINATION
USE THIS EQUIPMENT ON A GROUNDED
GROUNDE
SYSTEM ONLY.
ONLY
PRIMARY SINGLE PHASE FAILURE
FAILUR
PROTECTION IS PROVIDED.
PROVIDED
PROTECTOR MODULE AND OPTIONAL
OPTIONA
CRANKCASE HEATER MUST BE CONNECTED
CONNECTE
ONLY TO THEIR RATED VOLTAGE.
VOLTAGE
OVERCURRENT PROTECTION DEVICE
DEVIC
RATING AND TYPE MUST BE IN
I
ACCORDANCE WITH REGULATORY
REGULATOR
AGENCY END PRODUCT APPROVALSAPPROVALS
SEE SYSTEM NAMEPLATE.
NAMEPLATE
SENSORS
SENSOR
Y5
PROTECTOR MODUL
MODULE
VOLTAGE
VOLTAG
L1
W3
MAI
MAIN
L2 L3
1
3
5
Z6
4
6
X4
9-93
Y5
2
SENSORS
SENSOR
052-0811-00
052-0811-0
MOTOR WINDING
WINDIN
CONNECTIONS
CONNECTION
V2
STAR CONNECTED
CONNECTE
TO CONTROL
CONTRO
CIRCUIT
CIRCUI
Discontinued
Wiring Diagram 0813
G105
Discontinued
Wiring Diagram 0815
G106
Discontinued
Wiring Diagram 005-0819
G107
DELTA CONNECTED
PROTECTOR
MODULE
VOLTAGE
TO CONTROL
CIRCUIT
M1
M2
L1
L1
STAR CONNECTED
MAIN
L2 L3
TO CONTROL
CIRCUIT
L2
V2
U1
X4
Y5
M1
M2
S1
S2
L1
L1
MAIN
L2 L3
L2
V2
U1
PART No. 40AA300E
**
X
PROTECTOR
MODULE
VOLTAGE
Y5
PART No. 40AA300E
**
W3
Z6
X
SENSORS
120 OR 240 VOLT MODULE WIRING
WHEN CHECKING PROTECTOR
USE OHMMETER ONLY (6 VOLTS MAXIMUM)
TO CHECK SENSOR RESISTANCE. DO NOT
SHORT ACROSS THE TERMINALS.
RESISTANCE ACROSS MOTOR SENSORS SHOULD
BE APPROXIMATELY 750 OHMS WITH A MOTOR
TEMPERATURE BELOW 60 C.
**
THE 40AA300E MODULE HAS A FOUR MINUTE
TIME DELAY BEFORE RESET IN EVENT OF
PROTECTOR TRIP OR LOSS OF MODULE POWER.
THE 40AA100E MODULE IS NOT FURNISHED
WITH A TIME DELAY DEVICE.
S1
S2
Z6
W3
SENSORS
120 OR 240 VOLT MODULE WIRING
USE COPPER CONDUCTORS ONLY.
USE MINIMUM 75 C WIRE FOR
AMPACITY DETERMINATION.
U1
USE THIS EQUIPMENT ON A GROUNDED
SYSTEM ONLY.
PRIMARY SINGLE PHASE FAILURE
PROTECTION IS PROVIDED.
X4
Z6
PROTECTOR MODULE AND OPTIONAL
CRANKCASE HEATER MUST BE CONNECTED
ONLY TO THEIR RATED VOLTAGE.
OVERCURRENT PROTECTION DEVICE
RATING AND TYPE MUST BE IN
ACCORDANCE WITH REGULATORY
AGENCY END PRODUCT APPROVALSSEE SYSTEM NAMEPLATE.
Discontinued
Wiring Diagram 0823
Y5
V2
W3
MOTOR WINDING
CONNECTIONS
6-00
G108
X4
052-0883-00
Discontinued
Wiring Diagram 0824
G109
Discontinued
Wiring Diagram 0825
G110
Discontinued
Wiring Diagram 0826
G111
Discontinued
Wiring Diagram 005-0837
G112
Discontinued
Wiring Diagram 005-0838
G113
Discontinued
Wiring Diagram 005-0840
G114
This page is left blank intentionally.
G115
Discontinued
Wiring Diagram 0841 (Left Side)
G116
Discontinued
Wiring Diagram 0841 (Right Side)
G117
Discontinued
Wiring Diagram 0848
G118
Discontinued
Wiring Diagram 0849
G119
Discontinued
Wiring Diagram 0853 (Left Side)
G120
Discontinued
Wiring Diagram 0853 (Right Side)
G121
Discontinued
Wiring Diagram 0854 (Top)
G122
Discontinued
Wiring Diagram 0854 (Bottom)
G123
Discontinued
Wiring Diagram 0855
G124
This page is left blank intentionally.
G125
Discontinued
Wiring Diagram 0856 (Top)
G126
Discontinued
Wiring Diagram 0856 (Bottom)
G127
Discontinued
Wiring Diagram 0857 (Left Side)
G128
Discontinued
Wiring Diagram 0857 (Right Side)
G129
Discontinued
Wiring Diagram 0858 (Top)
G130
Discontinued
Wiring Diagram 0858 (Bottom)
G131
Discontinued
Wiring Diagram 0859 (Left Side)
G132
Discontinued
Wiring Diagram 0859 (Right Side)
G133
LINE
S
R
Discontinued
Wiring Diagram 005-0860
G134
XX
005-0860-00
C
3-96
USE COPPER CONDUCTORS ONLY. USE
THIS EQUIPMENT ON A GROUNDED
SYSTEM ONLY. USE MINIMUM 75C
WIRE FOR AMPACITY DETERMINATION.
INTERNAL MOTOR PROTECTIONALLOW TIME FOR RESET.
OVERCURRENT PROTECTION DEVICE
RATING AND TYPE MUST BE IN
ACCORDANCE WITH REGULATORY AGENCY
END PRODUCT APPROVALS-SEE SYSTEM
NAMEPLATE.
RUN CAPACITOR
LINE
Discontinued
Wiring Diagram 005-0868
G135
Discontinued
Wiring Diagram 0874
G136
Discontinued
Wiring Diagram 0875
G137
Discontinued
Wiring Diagram 0876
G138
Discontinued
Wiring Diagram 0882
G139
Discontinued
Wiring Diagram 0883
G140
Discontinued
Wiring Diagram 0884
G141
Discontinued
Wiring Diagram 0885
G142
This page is left blank intentionally.
G143
Discontinued
Wiring Diagram 0896 (Left Side)
G144
Discontinued
Wiring Diagram 0896 (Right Side)
G145
Discontinued
Wiring Diagram 0898 (Top)
G146
Discontinued
Wiring Diagram 0898 (Bottom)
G147
Discontinued
Wiring Diagram 0899 (Top)
G148
Discontinued
Wiring Diagram 0899 (Bottom)
G149
Discontinued
Wiring Diagram 0902 (Left Side)
G150
Discontinued
Wiring Diagram 0902 (Right Side)
G151
Discontinued
Wiring Diagram 0917
G152
TWO SPEED
SINGLE PHASE
LINE
LINE
T3
T8
T1
T7
T3
T8
T1
T2
LOW SPEED
T7
T2
HIGH SPEED
T2
T7
T8
T3
Part-No. XXXXXX
2 POLE START
MAIN WINDING
4 POLE START
EXTERNAL MAIN
T1
L1 L2 S1 S2 M1 M2
PROTECTOR
MODULE
VOLTAGE
MOTOR WINDING
CONNECTIONS
SENSORS
TO CONTROL
CIRCUIT
USE COPPER CONDUCTORS ONLY.
USE MINIMUM 75 C WIRE FOR AMPACITY DETERMINATION.
USE THIS EQUIPMENT ON A GROUNDED SYSTEM ONLY.
PROTECTOR MODULE AND OPTIONAL CRANKCASE HEATER MUST BE
CONNECTED ONLY TO THEIR RATED VOLTAGE.
OVERCURRENT PROTECTION DEVICE RATING AND TYPE MUST BE IN
ACCORDANCE WITH REGULATORY AGENCY END PRODUCT APPROVALS-SEE
SYSTEM NAMEPLATE.
SEE SYSTEM MANUFACTURER'S WIRING DIAGRAM FOR START
1-00 052-0918-00
COMPONENT CONNECTIONS.
Discontinued
Wiring Diagram 0918
G153
TWO SPEED
LINE
LOW SPEED
THREE PHASE
T4
LINE
HIGH SPEED
T1
T3
T2
T5
T1
T2
T4
T3
T5
T6
MOTOR WINDING
CONNECTIONS
T6
Part-No. XXXXXX
L1 L2 S1 S2 M1 M2
T4
T5
T1
T6
T2
T3
PROTECTOR
MODULE
VOLTAGE
SENSORS
USE COPPER CONDUCTORS ONLY.
USE MINIMUM 75 C WIRE FOR AMPACITY DETERMINATION.
USE THIS EQUIPMENT ON A GROUNDED SYSTEM ONLY.
PRIMARY SINGLE PHASE FAILURE PROTECTION IS PROVIDED.
PROTECTOR MODULE AND OPTIONAL CRANKCASE HEATER MUST
BE CONNECTED ONLY TO THEIR RATED VOLTAGE.
OVERCURRENT PROTECTION DEVICE RATING AND TYPE MUST BE
IN ACCORDANCE WITH REGULATORY AGENCY END PRODUCT
APPROVALS-SEE SYSTEM NAMEPLATE.
1-00 052-0919-00
Discontinued
Wiring Diagram 0919
G154
TO
CONTROL
CIRCUIT
Discontinued
Wiring Diagram 005-0922
G155
PROTECTOR
MODULE
VOLTAGE
TO CONTROL
CIRCUIT
L1
MAIN
L2
L3
2
1
2
M1
M2
L1
L2
3
1
PART No. 40AA300E
**
3
X
S1
S2
MOTOR WINDING
CONNECTIONS
SENSORS
120 OR 240 VOLT MODULE WIRING
WHEN CHECKING PROTECTOR
USE OHMMETER ONLY (6 VOLTS MAXIMUM) TO CHECK SENSOR
RESISTANCE. DO NOT SHORT ACROSS THE TERMINALS.
RESISTANCE ACROSS MOTOR SENSORS SHOULD BE
APPROXIMATELY 750 OHMS WITH A MOTOR TEMPERATURE
BELOW 60 C.
**
THE 40AA300E MODULE HAS A FOUR MINUTE TIME DELAY
BEFORE RESET IN EVENT OF PROTECTOR TRIP OR LOSS OF
MODULE POWER.
THE 40AA100E MODULE IS NOT FURNISHED WITH A TIME DELAY
DEVICE.
USE COPPER CONDUCTORS ONLY.
USE MINIMUM 75 C WIRE FOR AMPACITY DETERMINATION.
USE THIS EQUIPMENT ON A GROUNDED SYSTEM ONLY.
PRIMARY SINGLE PHASE FAILURE PROTECTION IS PROVIDED.
PROTECTOR MODULE AND OPTIONAL CRANKCASE HEATER MUST
BE CONNECTED ONLY TO THEIR RATED VOLTAGE.
OVERCURRENT PROTECTION DEVICE RATING AND TYPE MUST BE
IN ACCORDANCE WITH REGULATORY AGENCY END PRODUCT
APPROVALS-SEE SYSTEM NAMEPLATE.
6-00
Discontinued
Wiring Diagram 0948
G156
052-0948-00
DELTA CONNECTED
PROTECTOR
MODULE
VOLTAGE
TO CONTROL
CIRCUIT
M1
M2
L1
L1
STAR CONNECTED
MAIN
L2 L3
TO CONTROL
CIRCUIT
L2
M1
V2
U1
X4
S1
S2
L1
M2
L1
MAIN
L2 L3
L2
Y5
V2
U1
PART No. 40AA300E
**
X
PROTECTOR
MODULE
VOLTAGE
X4
Y5
PART No. 40AA300E
**
W3
Z6
X
S1
S2
W3
Z6
SENSORS
120 OR 240 VOLT MODULE WIRING
SENSORS
120 OR 240 VOLT MODULE WIRING
WHEN CHECKING PROTECTOR
USE OHMMETER ONLY (6 VOLTS MAXIMUM)
TO CHECK SENSOR RESISTANCE. DO NOT
SHORT ACROSS THE TERMINALS.
RESISTANCE ACROSS MOTOR SENSORS SHOULD
BE APPROXIMATELY 750 OHMS WITH A MOTOR
TEMPERATURE BELOW 60 C.
**
THE 40AA300E MODULE HAS A FOUR MINUTE
TIME DELAY BEFORE RESET IN EVENT OF
PROTECTOR TRIP OR LOSS OF MODULE POWER.
THE 40AA100E MODULE IS NOT FURNISHED
WITH A TIME DELAY DEVICE.
USE COPPER CONDUCTORS ONLY.
USE MINIMUM 75 C WIRE FOR
AMPACITY DETERMINATION.
USE THIS EQUIPMENT ON A GROUNDED
SYSTEM ONLY.
PRIMARY SINGLE PHASE FAILURE
PROTECTION IS PROVIDED.
PROTECTOR MODULE AND OPTIONAL
CRANKCASE HEATER MUST BE CONNECTED
ONLY TO THEIR RATED VOLTAGE.
OVERCURRENT PROTECTION DEVICE
RATING AND TYPE MUST BE IN
ACCORDANCE WITH REGULATORY
AGENCY END PRODUCT APPROVALSSEE SYSTEM NAMEPLATE.
U1
X4
Z6
Y5
V2
W3
MOTOR WINDING
CONNECTIONS
6-00
052-0949-00
Discontinued
Wiring Diagram 0949
G157
Discontinued
Wiring Diagram 005-1043
G158
Discontinued
Wiring Diagram 005-1062
G159
Discontinued
Wiring Diagram 005-1071
G160
Discontinued
Wiring Diagram 1196
G161
Discontinued
Wiring Diagram 1299 (Left Side)
G162
Discontinued
Wiring Diagram 1299 (Right Side)
G163
Discontinued
Wiring Diagram 1825, 0700-8503514
G164
SECTION H
ELECTRICAL TROUBLESHOOTING
PROCEDURES
TOPICS
If The Compressor Will Not Run ............................... H2
If The Compressor Starts But Trips Repeatedly ....... H5
If The Compressor Runs But Will Not Refrigerate .... H8
CAUTION
Before attempting any electrical trouble-shooting, make
sure all grounds are connected and secure and there is
ground continuity throughout the compressor system.
Also ensure the compressor system is correctly grounded
to the power supply. If you are not a qualifed service
person familiar with electrical troubleshooting techniques,
DO NOT PROCEED until a qualifed service person is
available.
IF THE COMPRESSOR WILL NOT RUN
If a compressor fails to start and run properly, it is important
that the compressor be tested to determine its condition.
It is possible that external electrical components may be
defective, the protector may be open, a safety device
may be tripped, or other conditions may be preventing
compressor operation. If the compressor is not the source
of the malfunction, replacing the compressor will only
result in the unnecessary expenditure of time and money
while the basic problem remains.
1. If there is no voltage at the compressor terminals,
follow the wiring diagram and check back from the
compressor to the power supply to find where the
circuit is interrupted.
Check the controls (low pressure, high pressure,
thermostat, oil pressure safety, etc.) to see if the
contact points are closed. If a contactor is used,
check to see if the contacts are closed. Check for
a blown fuse, open disconnect switch, or loose
connections.
2. If voltage is available at the compressor terminals
and it is below 90 percent of the nameplate voltage,
it is possible the motor may not develop sufficient
starting torque. Check to determine if wire sizes are
adequate, electrical connections are loose, the circuit
is overloaded, or if the power supply is adequate.
3. On units with single phase PSC motors, the suction
and discharge pressures must be equalized before
starting because of the low starting torque of the
motor. Any change in the refrigerant metering device,
H2
the addition of a drier, or other changes in the system
components may delay pressure equalization and
create difficulties. If PSC motor starting problems are
being encountered, the addition of a hard start kit is
recommended.
4. On single phase compressors, a defective start
capacitor or relay may prevent the compressor from
starting. If the compressor attempts to start, but is
unable to do so or if there is a humming sound, check
the relay to see if the relay contacts are damaged or
its coil opened. The relay contacts should be closed
during the initial starting cycle, but should open as
the compressor comes up to speed.
Remove the wires from the start relay and check
continuity through the relay coil. Replace the relay
if there is no continuity. Use an ohmmeter to check
across the relay contacts. Potential relay contacts
are normally closed when the relay is not energized,
while current relay contacts are normally open. If
either gives an incorrect reading, replace the relay.
Do not attempt to run a compressor that has a
capacitor that is bulging, leaking, or damaged. It must
be replaced.
Make sure capacitors are electrically discharged
before checking. Start capacitors should have bleed
resistors. Check for continuity between the capacitor
terminals and between the capacitor terminals
and the case. Continuity indicates a short, and the
capacitor should be replaced.
Substitute “a known to be good” start capacitor if
available. If the compressor then starts and runs
properly, replace the original start capacitor. On
H3
PSC motors, substitute a “a known to be good” run
capacitor if available. If the compressor then starts
and run properly, replace the original run capacitor.If
a capacitor tester is not available, an ohmmeter may
be used to check run and start capacitors for shorts
or open circuits. Use an ohmmeter set to its highest
resistance scale and connect probes to capacitor
terminals.
a. With a good capacitor, the indicator should first move
towards zero and then increase towards infinity.
b. If there is no movement of the ohmmeter indicator,
an open circuit is indicated.
c. If the ohmmeter indicator moves to zero and
remains there or on a low resistance reading, a short
circuit is indicated. Defective capacitors should be
replaced.
5. If the correct voltage is available at the compressor
terminals and no current is drawn, remove power.
Then remove all wires from the terminals and check for
continuity through the motor winding. On single phase
compressors, check for continuity from terminals C to
R, and C to S and R to S. On three phase compressors,
check for continuity between the terminals for
connections to phases 1 and 2, 2 and 3, and 1 and
3. On compressors with line break inherent (internal)
protectors, an open overload protector can cause a
lack of continuity. If the compressor is warm, it may
require consider-able time to cool down. If continuity
cannot be established through all motor winding, the
compressor should be replaced.
H4
Check the motor for ground by means of a continuity
check between the common terminal and the
compressor shell. If there is a ground, replace the
compressor.
6. If the compressor has an external protector, check
for continuity through the protector or protectors. All
external and internal inherent protectors on Copelametic
compressor can be replaced in the field. On larger
compressors with thermostats, thermotectors, or solid
state sensors in the motor windings; H,L,S protection
(see Section D for compressor nomenclature), the
internal protective devices cannot be replaced, and the
compressor must be changed if the internal protectors
are defective or damaged.
IF THE COMPRESSOR STARTS BUT TRIPS
REPEATEDLY ON THE OVERLOAD PROTECTOR
1. Check the compressor suction and discharge
pressures while the compressor is operating. Be sure
the refrigerant is compatible with the compressor
and the temperature range is within the limitations of
the compressor. If pressures are excessive, it may
be necessary to clean the condenser, remove noncondensables from the system, add a crankcase
pressure regulating valve, modify the system control,
or take such other action as may be necessary to avoid
excessive pressures. If the fan motor is three phase,
make sure it is running in the right direction.
An excessively low suction pressure may indicate a
loss of charge, and a suction gas cooled compressor
may not be getting enough refrigerant vapor across
the motor for proper cooling.
On units with no service gauge ports where pressures
can’t be checked, check the condenser to be sure it is
H5
clean and fan is running. Excessive temperatures on
suction and discharge lines may also indicate abnormal
operating conditions.
2. Check the line voltage at the motor terminals while
the compressor is operating. The voltage should be
within 10 percent of the nameplate voltage rating. If
outside those limits, the voltage supply must be brought
within the proper range, or a compressor with different
electrical characteristics must be used.
3. Check the amperage drawn while the compressor
is operating. The amperage drawn should be within
±10 percent of the published compressor curve data
for the given pressures the compressor is operating
under. High amperage can be caused by low voltage,
high head pressure, high suction pressure, high oil
level, mechanical compressor damage, defective run
capacitors, or a defective starting relay.
On three phase compressors, check amperage
in each line. One or two high amperage legs on a
three phase motor indicates an unbalanced voltage
supply, or a winding imbalance, which can cause
motor overheating. If all three legs are not drawing
approximately equal amperage, temporarily switch the
leads to the motor to determine if the high leg stays with
the line or stays with the terminal. If the high amperage
reading stays with the line, the problem is in the line
voltage supply. If the high amperage reading stays with
the terminal, the problem is in the motor.
If the amperage is sufficiently unbalanced to cause
a protector trip (approximately 10%) and the voltage
supply is unbalanced, check with the power company
to see if the condition can be corrected. If the voltage
supply is balanced, indicating a defective motor phase,
H6 the compressor should be replaced.
4. Check for a defective run capacitor or starting relay in
the same manner described in the previous section.
5. Check for wiring against the wiring diagram in the
terminal box. On dual voltage motors, check the
location of the terminal jumper bars to be sure phases
are properly connected.
6. Overheating of the cylinders and head can be caused
by a leaking valve plate or relief valve. To check,
front seat the suction service valve and briefly pump
the compressor into a vacuum. Stop the compressor
and open the suction valve to allow the pressure on
the suction gauge to build up to 0 psig. Again, close
the valve. If the pressure on the gauge continues to
increase steadily, the valve plate or relief valve is
leaking. Remove the head and check the valve plate.
Replace if necessary.
7. If all operating conditions are normal, the voltage
supply at the compressor terminals balanced and
within limits, the compressor crank-case temperature
within normal limits, the amperage drawn within the
specified range, the motor protector may be defective
and should be replaced.
If the operating conditions are normal and the
compressor is running excessively hot for no
observable reason, or if the amperage drawn is above
the normal range and sufficient to repeatedly trip the
protector, the compressor has internal damage and
should be replaced.
H7
IF THE COMPRESSOR RUNS BUT WILL NOT
REFRIGERATE
1. Check the refrigerant charge and the operating
pressures. Any abnormal operating conditions must
be corrected.
2. If the suction pressure is high and the evaporator
and condenser are functioning normally, check the
compressor amperage draw. An amperage draw within
±5 percent of published rating data, corrected for
actual measured voltage, indicates normal compressor
operation. An amperage draw considerably below
the published rating data indicates a possible broken
suction valve, discharge valve, broken connecting
rod blown gasket, or worn rings in the compressor.
Check the pistons and valve plate on an accessible
compressor. If no other reason for lack of capacity
and low amperage can be found, replace a welded
compressor.
An amperage draw considerably above published
rating data for the given operating pressures indicates
possible bearing damage, and the compressor should be
replaced.
Published compressor rating data for each model can
be obtained by your Emerson Climate Technologies
Wholesaler.
H8
SECTION I
IDENTIFYING COMPRESSOR FAILURES
Most compressors fail due to system malfunctions which must be corrected to prevent repeat
failures. After a compressor fails, field examination of the failed compressor often will reveal
symptoms of system problems. Proper corrections will help eliminate future failures.
Field examination does not affect warranty as long as all access plates and heads are reinstalled with all internal components put back inside the compressor.
REFRIGERANT FLOODBACK
This is a result of liquid refrigerant returning
to the compressor during the running cycle.
The oil is diluted with refrigerant to the point
it cannot properly lubricate the load bearing
surfaces.
• Air Cooled Compressors
• Worn pistons and cylinders
• No evidence of overheating
The liquid washes the oil off the pistons and
cylinder walls during the suction stroke causing them to wear during the compression
stroke.
I2
• Refrigerant Cooled Compressors
• Center and rear bearings worn or seized
• Dragging rotor, shorted stator
• Progressively scored crankshaft
• Worn or broken rods
The liquid dilutes the oil in the crankcase
and the refrigerant rich oil will be pumped
to the rods and the bearings through the
crankshaft.
As the refrigerant boils off, there will not be
enough oil for sufficient lubrication at bearings furthest from the oil pump.
The center and rear bearings may seize or
may wear enough to allow the rotor to drop
and drag on the stator causing a short.
• Corrections
1. Maintain proper evaporator and
compressor superheat.
2. Correct abnormal low load conditions.
3. Install accumulators to stop uncontrolled
liquid return.
I3
FLOODED STARTS
• Worn or scored rods or bearings
• Rods broken from seizure
• Erratic wear of crankshaft
This is the result of refrigerant migrating to the crankcase oil during the off cycle. When the compressor
starts, the diluted oil cannot properly lubricate the
load bearing surfaces causing an erratic wear or
seizure pattern.
• Corrections
1. Locate compressor in warm ambient or install
pump down.
2. Check crankcase heater operation.
SLUGGING
• Broken reeds, rods, or crankshaft
• Loose or broken backer bolts
• Blown head gaskets
This is the result of trying to compress liquid refrigerant and/or oil in the cylinders. Slugging is caused
by floodback on air cooled compressors and severe
flooded starts on refrigerant cooled compressors.
• Corrections
1. Maintain proper evaporator and compressor
superheat.
2. Correct abnormal low load conditions.
3. Install accumulators to stop uncontrolled liquid
return.
4. Locate compressor in warm ambient or install
pump down.
I4
HIGH DISCHARGE TEMPERATURE
• Discolored valve plate
• Burned valve reeds
• Worn pistons, rings, and cylinders
• Stator spot burn from metal debris
This is the result of temperatures in the compressor head and cylinders becoming so hot
that the oil loses its ability to lubricate properly.
This causes rings, pistons, and cylinders to
wear resulting in blow by, leaking valves, and
metal debris in the oil.
• Corrections
1. Correct abnormal low load conditions.
2. Correct high discharge pressure conditions.
3. Insulate suction lines.
4. Provide proper compressor cooling.
LOSS OF OIL
• All rods and bearings worn or scored.
• Crankshaft uniformly scored.
• Rods broken from seizure.
• Little or no oil in crankcase.
This is a result of insufficient oil in the crankcase
to properly lubricate the load bearing surfaces.
When there is not enough refrigerant mass flow
in the system to return oil to the compressor as
fast as it is pumped out, there will be a uniform
wearing or scoring of all load bearing surfaces.
I5
• Corrections
1. Check oil failure control operation if applicable.
2. Check system refrigerant charge.
3. Correct abnormally low load conditions or
short cycling.
4. Check for incorrect pipe sizes and/or oil
traps.
5. Check for inadequate defrosts.
ELECTRICAL
Many motors fail as a result of mechanical
failure. Others are true electrical failures.
GENERAL OR UNIFORM BURN
All windings are uniformly overheated or
burned.
• Corrections
1. Check for proper voltage.
2. Check for unbalanced voltage.
3. Check for inadequate motor cooling.
I6
SINGLE PHASE BURN
Two phases of a three phase motor are
overheated or burned.
This is the result of high current through two
of the three phases.
• Corrections
1. Replace contactors.
2. Check for proper motor protection.
HALF WINDING SINGLE PHASE BURN
Half of two phases of a three phase motor
overheated or burned due to one contactor
opening one of its contacts on a two contactor application.
• Correction
1. Replace contactors.
HALF WINDING BURN
Half of all phases of a two contactor three
phase motor are over heated or burned.
• Corrections
1. Replace contactors
2. Check for feedback circuit holding one
contactor closed
I7
PRIMARY SINGLE PHASE BURN
Only one phase of a three phase motor is
overheated or burned as the result of opening one phase on the primary side of a delta
to wye transformer.
• Correction
1. Check primary side of a delta to wye
mainpower transformer.
START WINDING BURN
Only the start winding of a single phase
motor is uniformly overheated or burned.
• Corrections
1. Check for proper wiring of compressor.
2. Check starting capacitor and/or starting
relay.
3. Check compressor overloading.
SPOT BURN
A localized burn within a winding, between
windings, or from windings to ground.
• Corrections
1. If not the result of mechanical problems,
check for spikes or surges of high current
flow.
I8
SHORTED TERMINALS
A breakdown of the insulation between
terminals and compressor body.
• Correction
1. Check for over torquing of terminals.
I9