10 Controls

Transcription

10 Controls
10 -1
RS485
(Master)
Webserver
BMS-WB2561PWE
Notes:Co-existence
and
interoperability of each product
shall be referred to another
documents.
RS485
line
monitoring
TCC-LINK
TCC-LINK
Energy monitoring Relay I/F
Digital I/O Relay I/F
TCC-LINK
TCC-LINK
RS485
Digital I/O Relay I/F
BMS-IFDD03E
BMS-IFDDO3UL(U.S.)
System
Air-conditioning Management
Compressor operation /system
operation ratio(SMMS-i only)
Master ON/OFF signal
Error/operation output
Power peak-out control signal
Energy monitoring Relay I/F
Digital I/O Relay I/F
BMS-WB2561PWE Gateway
RS485
BMS-WB2561PWE Gateway
RS485
RS485
I/O
Device
Power Meter
Mini-SMMS
Master ON/OFF signal
Batch drive, error output
Schedule
timer
TCB-EXS21TLE
TCC-LINK
SMMS
SMMS-i
Wired remote controller
with Weekly timer
RBC-AMS41E
TCB-KBOS1E
for SDI4 only
Wired remote controller
RBC-AMT32(31)E
Simple remote controller
RBC-AS21E2
TCB-IFGSM1E
GSM REMOTE CONTROL I/F
TCB-PCNT30TLE2
TCC-Link Interface
“1:1 model” connection
External sw
General Purpose I/F
TCB-IFCG1TLE
Remote Sensor
TCB-TC21LE2
GSM Modem
Cable for connector
CN32(TCB-KBCN32VEE)
CN60(TCB-KBCN60OPE)
CN61(TCB-KBCN61HAE)
CN70(TCB-KBCN70OAE)
CN73(TCB-KBCN73DEE)
CN80(TCB-KBCN80EXE)
Cable for connector
CN32(TCB-KBCN32VEE)
CN60(TCB-KBCN60OPE)
CN61(TCB-KBCN61HAE)
CN70(TCB-KBCN70OAE)
CN73(TCB-KBCN73DEE)
CN80(TCB-KBCN80EXE)
Digital Inverter
Super Digital Inverter
Sensors/switch/key/actuator
Wireless remote
controller
Daiseikai
1.LonWorks : Registered trademark by Echelon corporation.
2.BACnet : ANSI/ASHRAE 135-1995,A data Communication Protocol for Building Automation and Control Network.
3.Modbus : Registered trademark by Schneider E.
Compliant Manager
BMS-CM1280TLE
Side remote Master remote
Remote ON/OFF
TCB IFCB-4E2
Central remote controller
TCB-SC642TLE2
Alarm Status output
ON/OFF Command
TCB-PCIN4E
Error output control board
Compressor operation /system operation ratio(SMMS-i only)
Error output control board
TCB-PCIN2E
External master ON/OFF board
TCB-PCMO2E
ON-OFF controller
TCB-CC163TLE2
I/O
Device
TCC-LINK
Power peak-out control
board TCB-PCDM2E
BMS-LSV4E
BMS-IFLSV4UL(U.S.)
TCS-Net Relay Interface
Energy monitoring Relay I/F
BMS-IFWH5E
Power Meter
BMS-IFWH5UL(U.S.)
Digital I/O Relay I/F
Energy
Relay I/F
BMS-LSV6E
RS485
BACnet Server
TCB-IFMB640TLE
RS485
TP
TCB-IFLN642TLE/TCB-IFLN642UL
DC
TCC-LINK
RS485
Compliant Manager
BMS-CM1280FTLE
Touch-screen Controller
BMS-TP0641ACE
BMS-TP5121ACE
BMS-TP0641PWE
BMS-TP5121PWE
BACnet
Modbus
BMS-WB01GTE Master Server
Intranet
*Monitoring
*Remote control
*Schedule
operation
*Error code indication
*Alarm list indication
*Monthly report
*Energy monitoring data etc.
Open
Op
en System
LONWORKS
.LonWorks
Analog I/F(DCvoltage)
TCB-IFCB640TLE
Air-conditioning Management System on site
10
SMMS-i Data book
Controls
1. Outline of application Control
10 Controls
2. Applications for indoor remote controller
Basic function
System diagram
Main remote
controller
2-1
Individual control
Air conditioner is
individually operated
at a distance.
Model
• Wired remote controller
Wireless remote
RBC-AMT32E
controller
RBC-AMT31E
• Wired remote controller with
weekly timer
Indoor
RBC-AMS41E
unit
• Simple wired remote controller
RBC-AS21E2
Receiver unit • Wireless remote controller kit
RBC-AX31U(W)-E
Wireless
RBC-AX31U(WS)-E
remote
RBC-AX22CE2
controller
TCB-AX21E2
Indoor
unit
(((
Remote
controller
Max.8 indoor units
2-2
GROUP control
One remote
controller can control
a group of up to a
max. 8 indoor units.
Operating on the
same setting.
Indoor
unit
Indoor
unit
Indoor
unit
Indoor
unit
Remote
controller
Wired & Wireless combination
control
(Either one of the two controllers
can be set as side control.)
Wired system
Indoor
unit
Indoor
unit
Remote
controller
Side
(
Remote
controller
Master
((
2-3
Two remote control
Air conditioner is
controlled by two
remote controllers in
two locations.
Remote
controller
Wireless system
Indoor
unit
((
(
(((
Wireless
remote
controller 1
Master
Wireless
remote
controller 2
Side
2-4
Wireless
remote
controller
When two wireless
remote controllers are
operated at the same
time, the communication
are not done by
interference of both
infrared rays.
Indoor
unit
Indoor
unit
SW setting at
schedule timer
is necessary.
TCC-LINK
Central
remote
controller
• Wired remote controller
RBC-AMT32E
RBC-AMT31E
• Wired remote controller with
weekly timer
RBC-AMS41E
• Simple wired remote controller
RBC-AS21E2
• Wireless remote controller kit
RBC-AX31U(W)-E
RBC-AX31U(WS)-E
RBC-AX22CE2
TCB-AX21E2
Weekly timer mode
Schedule timer mode
Control by
schedule timer
Schedule timer mode
and Weekly timer
mode
• Wired remote controller
RBC-AMT32E
RBC-AMT31E
• Wired remote controller with
weekly timer
RBC-AMS41E
• Simple wired remote controller
RBC-AS21E2
• Wireless remote controller kit
RBC-AX31U(W)-E
RBC-AX31U(WS)-E
RBC-AX22CE2
TCB-AX21E2
Schedule
timer
Wired
remote
controller
10 -2
Schedule
timer
• Wired remote controller
RBC-AMT32E
RBC-AMT31E
• Central remote controller
TCB-SC642TLE2
• Schedule timer
TCB-EXS21TLE
10 Controls
3. Application control for central remote controller
Basic function
System diagram
Model
Header
unit
Outdoor unit
U3, U4
Line-3
U5, U6
Zone
4
U1, U2
Header
unit
Indoor remote controller
Outdoor unit
U3, U4
U5, U6
Zone
3
Indoor unit
Line-2
Indoor unit
U1, U2
Zone
2
Indoor remote controller
Header
unit
U3, U4
Outdoor unit
Line-1
Zone
1
Indoor unit
U1, U2
Indoor remote controller
Power
Central
supply
remote controller
Single phase
220V
3-1
Central management
controllers for
64/128 units
Function of central remote controller
Controller for 64 units(TCB-SC642TLE2)
• Individual control up to 64 indoor units
• Individual control for max. 64 indoor units divided in to 4 zones
(Up to 16 indoor units for each zone)
• Up to 16 outdoor header units are connectable.
• Setting for one of 1 to 4 zones is available.
Controller for 128 units(BMS-CM1280TLE)
• Individual control of up to (64 indoor units) 2 TCC-LINK buses
• Individual control of up to (64 indoor units divided 1 to 64
zone) 2 TCC-LINK buses (Up to 64 indoor units for each zone)
• Up to 16 outdoor header units are connectable per 1 TCC-LINK
bus
• Setting for (one of 1 to 64 zones) 2ch is available.
• Setting for (one of 1 to 64 groups) 2ch is available.
• Return back setting
Common
• 4 types central control settings to restrict individual operation by
remote controller are selectable.
• Usable with other central control devices (Up to 10 central
control devices in one control circuit)
• Two control mode selectively Contral controller mode/Remote
controller mode
• Master/Sub setting possible
10 -3
• Central remote
controller
TCB-SC642TLE2
BMS-CM1280TLE
Indoor remote
controller
• Wired remote controller
RBC-AMT32E
RBC-AMT31E
• Wired remote controller
with weekly timer
RBC-AMS41E
• Simple wired remote
controller
RBC-AS21E2
• Wireless remote
controller kit
10 Controls
Basic function
System diagram
U3, U4
Model
Outdoor unit
Indoor unit
3-2
Central remote controller
+
Schedule timer
Weekly operation
schedule can be set
by connecting a
schedule timer to
the central remote
controller
U1, U2
Indoor remote
controller
• Wired remote controller
RBC-AMT32E
RBC-AMT31E
• Wired remote controller
with weekly timer
RBC-AMS41E
• Simple wired remote
controller
RBC-AS21E2
• Wireless remote
controller kit
Indoor remote controller
Single phase
220V
Power
supply
Schedule timer
Central
remote controller
U3, U4
• Central remote
controller
TCB-SC642TLE
RBC-CM1280TLE
+
• Schedule timer
TBC-EXS21TLE
Outdoor unit
U1, U2
Power
supply
Indoor unit
Central remote controller
Single phase
220V
Even when grouping operation is performed by
connecting multiple indoor units to 1 line, the
indoor remote controller is required.
Example of grouping operation
U3, U4
3-3
Either one of the two
controllers can be set as
side control without indoor
remote controller.
Outdoor unit
U1, U2
Power
supply
Single phase
220V
(Group)
Indoor remote controller is
required
Central remote controller
U3, U4
Available
Outdoor unit
U1, U2
Power
supply
Single phase
220V
(Group)
Available
Central remote controller
10 -4
• Central remote
controller
TCB-SC642TLE2
Indoor remote
controller
• Wired remote controller
RBC-AMT32E
RBC-AMT31E
• Wired remote controller
with weekly timer
RBC-AMS41E
• Wireless remote
controller kit
10 Controls
Basic function
System diagram
Power
supply
Model
Central remote controller
U3, U4
Header unit
Super MMS
U1, U2
3-4
Indoor unit
Central management
control with ‘‘1 : 1 model’’
*1
“1 : 1 model”
connection
interface
Indoor remote controller
* TOSHIBA Digital Inverter System and Super Digital Inverter
System
10 -5
• Central remote
controller
TCB-SC642TLE2
BMS-CM1280TLE
• ‘‘1 : 1 model’’
connection interface
TCB-PCNT30TLE2
High-wall type for
SDI/DI is not
necessary this.
4-way and compact
4-way cassette type
for SDI/DI need the
metal fitting kit
(TCB-PX30MUE).
Indoor remote
controller
• Wired remote controller
RBC-AMT32E
RBC-AMT31E
• Wired remote controller
with weekly timer
RBC-AMS41E
• Simple wired remote
controller
RBC-AS21E2
• Wireless remote
controller kit
10 Controls
4. Application control for network
Basic function
System diagram
Model
LON center
LON WORKS
LN Interface
TCB-
TCBTCBIFLN060 • • •
Super MMS
4-1-1
*1
LONWORKS
Remote controller
“1:1 model”
connection interface
*1TOSHIBA Digital Inverter System and Super Digital Inverter
System
• LN Interface
TCB-IFLN640TLE
• ‘‘1 : 1 model’’ connection
interface
TCB-PCNT30TLE2
High-wall type for SDI/DI is
not necessary this.
4-way and compact 4-way
cassette type for SDI/DI need
the metal fitting kit (TCBPX30MUE).
The LONWORKS interface should be connected between a
building management computer and a Super MMS air
conditioning system.
BACnet center
Intelligent
server
TCB-
■ BACnet server software
TCS-Net
Relay Interface
Super MMS
4-1-2
*1
BACnet
Remote controller
“1:1 model”
connection interface
*1TOSHIBA Digital Inverter System and Super Digital Inverter
System
• Intelligent server
BMS-LSV6E
• BACnet server software
BMS-STBN08E
• TCS-Net Relay Interface
BMS-IFLSV3E
• ‘‘1 : 1 model’’ connection
interface
TCB-PCNT30TLE2
High-wall type for SDI/DI is
not necessary this.
4-way and compact 4-way
cassette type for SDI/DI need
the metal fitting kit (TCBPX30MUE).
The local server should be connected to the BACnet network,
and the Super MMS air conditioning system through the
interface.
Modbus
Modbus
Interface
4-1-3
Modbus
TCB-
Super MMS
*1
Remote controller
“1:1 model”
connection interface
*1TOSHIBA Digital Inverter System and Super Digital Inverter
System
10 -6
• Modbus Interface
TCB-IFMB640TLE
• ‘‘1 : 1 model’’ connection
interface
TCB-PCNT30TLE2
High-wall type for SDI/DI is
not necessary this.
4-way and compact 4-way
cassette type for SDI/DI need
the metal fitting kit (TCBPX30MUE).
10 Controls
Touch screen controller system
System diagram
Max 64/512 Indoors/groups
Touch Screen Controller
1:1model
TCC-link bus
Connection I/F
Relay I/F
RS-485
Digital I/O signal
Max
In3 /Out3
Max12
Ethernet
Fire alarm
Door key
etc
TCC-link bus
Relay I/F
Monthly report creation software
Energy monitoring Relay I/F
Max8
Power Meter
Pulse signal
Max8
4-2-1
Digital I/O Relay I/F
Digital I/O signal
Max8
Fire alarm
Door key
Error
Max In 8 /Out 4
Power meter:
Pulse width:50-1000ms
Pulse generator constants (kWh/pulse) 0.1-99.9
Model Name
Function
Devices
Touch Screen controller
Model Name
BMS-TP0641ACE
Specification
Max. 64 indoor units, without electrical bill calculation
BMS-TP5121ACE
Max. 512 indoor units, without electrical bill calculation
BMS-TP0641PWE
Max. 64 indoor units, with electrical bill calculation
BMS-TP5121PWE
Max. 512 indoor units, with electrical bill calculation
TCS-Net Relay Interface
BMS-IFLSV3E
I/F in between Touch Screen controller & Control wiring
Energy Monitoring Relay Interface
BMS-IFWH4E2
I/F for Power Meter
Digital I/O Relay Interface
BMS-IFDD02E2
I/F for I/O signal
(1) Monitoring air-conditioners
Operation status can be viewed according to a unit.
[Unit] All building, All tenants, Each tenant, Each area, Each air-conditioning system
[Monitoring contents] Operation and alarm status, Setting status for each air-conditioning system
(2) Operating of air-conditioners
Header/individual control can be performed according to a unit.
[Operating contents] ON/OFF, Operation setting (operation mode, air volume, louver position,
setting temp., restricted setting from remote location)
(3) Schedule operation
Air-conditioners are operated according to the set-up schedule/operation pattern.
Schedule operataion can be performed according to a unit.
[Operation pattern] Weekly pattern, special day pattern (4 pattern), Non-operation days pattern
(4) Alarm list display
The present alarm contents are list-displayed.
[Display contents] Alarm contents, Unit number, Generated time
(5) Alarm record display
The alarm history records are displayed.
[Display contents] Alarm contents, Unit number, Generated time
(6) Monthly report data extraction
Monthly report data is written to ‘‘Compact Flash’’. Monthly reports can be created according to a unit
using the monthly report software.
[Monthly report contents] The number of ON/OFF, Operating time, Results of energy monitoring
10 -7
10 Controls
Compliant Manager
System diagram
TCC-LINK LINE 1
Compliant Manager
TCC-LINK LINE 2
HUB
Local Supply (BMS-CM1280FTLE only)
4-2-2
Monitoring
Operation
Zone setting (64 zone x ~ 2)
Individual units operation (ON/OFF, Operation
mode, Setting temperature, Air volume, Filter
sign)
Operation restriction
Alarm display
Individual operation
Max. 128 indoor units
Return Back operation
Weekly Schedule Operation* (ON/OFF)
External control input
Status output
Fire alarm input
Alarm display
* accessory necessary
Web Application (WEB model only)
Network connection
Schedule operation (ON/OFF, Setting temperature, operation
mode and Remote control Permit/Prohibit)
Alarm history
Energy monitoring external connection*
* accessory necessary
• Compliant Manager
BMS-CM1280TLE
• Compliant Manager with WEB
BMS-CM1280FTLE
10 -8
10 Controls
WEB Based Controller
System diagram
System diagram for connecting 256FCUs or less
BMS-WB2561PWE
(Web Server)
TCS-Net Relay I/F
TCC-LINK
Ethernet
BMS-IFLSV3E
SMMS
SMMS
RS-485
HUB
TCS-Net Relay I/F
TCC-LINK
4-2-3
MiNi-SMMS
BMS-IFLSV3E
SMMS
I/F for Power Meter
(BMS-IFWH4E2)
Network, Intranet, connection
through LAN port
I/F for I/O signal
(BMS-IFDD02E2E)
Local Supply
WEB Based Controller
• Gateway Server
BMS-WB2561PWE
• TCS-Net Relay I/F
BMS-IFLSV3E
• Energy Monitoring Relay I/F
BMS-IFWH4E2
• Digital I/O Relay I/F
BMS-IFDD02E2
System diagram for connecting 257FCUs or more
TCS-Net
Relay I/F
BMS-WB01GTE
(Master Server)
TCC-LINK
SMMS
Ethernet
SMMS
BMS-WB2561PWE
(Gateway)
RS-485
TCS-Net
Relay I/F
TCC-LINK
SMMS
HUB
TCS-Net
Relay I/F
TCC-LINK
SMMS
4-2-4
MiNi-SMMS
SMMS
BMS-WB2561PWE
(Gateway)
RS-485
Network, Intranet, connection through LAN port
Enable to connector up to 2,048 FCUs
TCS-Net
Relay I/F
TCC-LINK
SMMS
I/F for Power Meter
(BMS-IFWH4E2)
Local Supply
I/F for I/O signal
(BMS-IFDD02E2E)
WEB Based Controller
• Master server
BMS-WB01GTE
• Gateway Server
BMS-WB2561PWE
• TCS-Net Relay I/F
BMS-IFLSV3E
• Energy Monitoring Relay I/F
BMS-IFWH4E2
• Digital I/O Relay I/F
BMS-IFDD02E2
10 -9
MiNi-SMMS
10 Controls
Application control of optional devices connectable to indoor units
[1] Remote location ON/OFF control box
Model
Name
Appearance
Features
TCB-IFCB-4E2
z Start and stop of the air conditioner is possible by a
external signal and indication of operation/alarm
externally.
Application
Function
• Monitoring
ON/OFF status (for indoor unit)
Alarm status (system & indoor unit stop)
• ON/OFF command
Air conditioner can be turned ON/OFF by
external signals.
The external ON/OFF signals will initiate the
signals shown below.
Operation
Interface
Display
Remote
Controller
Non-voltage
ON/OFF continious signal
ON/OFF
COM
[2] ‘‘1 : 1 model’’ connection interface
Model
Name
Appearance
Features
z Link adapter for ‘‘1 : 1 model’’ into super modular
multi network
1 : 1 model: Super digital inverter
Digital inverter
TCB-PCNT30TLE2
Connection of cables
Install optional P.C. board in Electrical parts box of
indoor unit.
ON-OFF
control
devices
Application
Central Remote
Controller
Wiring diagram of indoor P.C. board
Super MMS control wiring
1:1 model
connection
interface
Indoor units
Metal fitting kit (TCB-PX30MUE)
is necessary for 4-way and
Compact 4-way cassette type.
adoptor
Digital Inverter
Super Digital Inverter
Outdoor unit
10 -10
10 Controls
Application controls by optional P.C. board of outdoor unit
Application
TCB-PCMO4E
TCB-PCIN4E
Feature
[1] Power peak-cut Control
The upper limit capacity of the outdoor unit is restricted based on the power
peak cut request signal from outside.
TCB-PCDM4E
Model
name
* Install these optional
P.C.Board in the
inverter assembly of
the header outdoor
unit.
[2] Snowfall fan control
Outdoor fan is operated by a snowfall signal from outside.
[3] External master ON/OFF control
The outdoor unit starts or stops the system.
[4] Night operation (Sound reduction) control
Sound level can be reduced by restricting the compressor and fan speeds.
[5] Operation mode selection control
This control can restrict the selectable operation mode.
[6] Error/Operation output control
Error/operation are displayed and output.
[7] Compressor operation output control
Three compressor’s operation/stop output
[8] System operation output control
10 -11