10 Controls
Transcription
10 Controls
10 -1 RS485 (Master) Webserver BMS-WB2561PWE Notes:Co-existence and interoperability of each product shall be referred to another documents. RS485 line monitoring TCC-LINK TCC-LINK Energy monitoring Relay I/F Digital I/O Relay I/F TCC-LINK TCC-LINK RS485 Digital I/O Relay I/F BMS-IFDD03E BMS-IFDDO3UL(U.S.) System Air-conditioning Management Compressor operation /system operation ratio(SMMS-i only) Master ON/OFF signal Error/operation output Power peak-out control signal Energy monitoring Relay I/F Digital I/O Relay I/F BMS-WB2561PWE Gateway RS485 BMS-WB2561PWE Gateway RS485 RS485 I/O Device Power Meter Mini-SMMS Master ON/OFF signal Batch drive, error output Schedule timer TCB-EXS21TLE TCC-LINK SMMS SMMS-i Wired remote controller with Weekly timer RBC-AMS41E TCB-KBOS1E for SDI4 only Wired remote controller RBC-AMT32(31)E Simple remote controller RBC-AS21E2 TCB-IFGSM1E GSM REMOTE CONTROL I/F TCB-PCNT30TLE2 TCC-Link Interface “1:1 model” connection External sw General Purpose I/F TCB-IFCG1TLE Remote Sensor TCB-TC21LE2 GSM Modem Cable for connector CN32(TCB-KBCN32VEE) CN60(TCB-KBCN60OPE) CN61(TCB-KBCN61HAE) CN70(TCB-KBCN70OAE) CN73(TCB-KBCN73DEE) CN80(TCB-KBCN80EXE) Cable for connector CN32(TCB-KBCN32VEE) CN60(TCB-KBCN60OPE) CN61(TCB-KBCN61HAE) CN70(TCB-KBCN70OAE) CN73(TCB-KBCN73DEE) CN80(TCB-KBCN80EXE) Digital Inverter Super Digital Inverter Sensors/switch/key/actuator Wireless remote controller Daiseikai 1.LonWorks : Registered trademark by Echelon corporation. 2.BACnet : ANSI/ASHRAE 135-1995,A data Communication Protocol for Building Automation and Control Network. 3.Modbus : Registered trademark by Schneider E. Compliant Manager BMS-CM1280TLE Side remote Master remote Remote ON/OFF TCB IFCB-4E2 Central remote controller TCB-SC642TLE2 Alarm Status output ON/OFF Command TCB-PCIN4E Error output control board Compressor operation /system operation ratio(SMMS-i only) Error output control board TCB-PCIN2E External master ON/OFF board TCB-PCMO2E ON-OFF controller TCB-CC163TLE2 I/O Device TCC-LINK Power peak-out control board TCB-PCDM2E BMS-LSV4E BMS-IFLSV4UL(U.S.) TCS-Net Relay Interface Energy monitoring Relay I/F BMS-IFWH5E Power Meter BMS-IFWH5UL(U.S.) Digital I/O Relay I/F Energy Relay I/F BMS-LSV6E RS485 BACnet Server TCB-IFMB640TLE RS485 TP TCB-IFLN642TLE/TCB-IFLN642UL DC TCC-LINK RS485 Compliant Manager BMS-CM1280FTLE Touch-screen Controller BMS-TP0641ACE BMS-TP5121ACE BMS-TP0641PWE BMS-TP5121PWE BACnet Modbus BMS-WB01GTE Master Server Intranet *Monitoring *Remote control *Schedule operation *Error code indication *Alarm list indication *Monthly report *Energy monitoring data etc. Open Op en System LONWORKS .LonWorks Analog I/F(DCvoltage) TCB-IFCB640TLE Air-conditioning Management System on site 10 SMMS-i Data book Controls 1. Outline of application Control 10 Controls 2. Applications for indoor remote controller Basic function System diagram Main remote controller 2-1 Individual control Air conditioner is individually operated at a distance. Model • Wired remote controller Wireless remote RBC-AMT32E controller RBC-AMT31E • Wired remote controller with weekly timer Indoor RBC-AMS41E unit • Simple wired remote controller RBC-AS21E2 Receiver unit • Wireless remote controller kit RBC-AX31U(W)-E Wireless RBC-AX31U(WS)-E remote RBC-AX22CE2 controller TCB-AX21E2 Indoor unit ((( Remote controller Max.8 indoor units 2-2 GROUP control One remote controller can control a group of up to a max. 8 indoor units. Operating on the same setting. Indoor unit Indoor unit Indoor unit Indoor unit Remote controller Wired & Wireless combination control (Either one of the two controllers can be set as side control.) Wired system Indoor unit Indoor unit Remote controller Side ( Remote controller Master (( 2-3 Two remote control Air conditioner is controlled by two remote controllers in two locations. Remote controller Wireless system Indoor unit (( ( ((( Wireless remote controller 1 Master Wireless remote controller 2 Side 2-4 Wireless remote controller When two wireless remote controllers are operated at the same time, the communication are not done by interference of both infrared rays. Indoor unit Indoor unit SW setting at schedule timer is necessary. TCC-LINK Central remote controller • Wired remote controller RBC-AMT32E RBC-AMT31E • Wired remote controller with weekly timer RBC-AMS41E • Simple wired remote controller RBC-AS21E2 • Wireless remote controller kit RBC-AX31U(W)-E RBC-AX31U(WS)-E RBC-AX22CE2 TCB-AX21E2 Weekly timer mode Schedule timer mode Control by schedule timer Schedule timer mode and Weekly timer mode • Wired remote controller RBC-AMT32E RBC-AMT31E • Wired remote controller with weekly timer RBC-AMS41E • Simple wired remote controller RBC-AS21E2 • Wireless remote controller kit RBC-AX31U(W)-E RBC-AX31U(WS)-E RBC-AX22CE2 TCB-AX21E2 Schedule timer Wired remote controller 10 -2 Schedule timer • Wired remote controller RBC-AMT32E RBC-AMT31E • Central remote controller TCB-SC642TLE2 • Schedule timer TCB-EXS21TLE 10 Controls 3. Application control for central remote controller Basic function System diagram Model Header unit Outdoor unit U3, U4 Line-3 U5, U6 Zone 4 U1, U2 Header unit Indoor remote controller Outdoor unit U3, U4 U5, U6 Zone 3 Indoor unit Line-2 Indoor unit U1, U2 Zone 2 Indoor remote controller Header unit U3, U4 Outdoor unit Line-1 Zone 1 Indoor unit U1, U2 Indoor remote controller Power Central supply remote controller Single phase 220V 3-1 Central management controllers for 64/128 units Function of central remote controller Controller for 64 units(TCB-SC642TLE2) • Individual control up to 64 indoor units • Individual control for max. 64 indoor units divided in to 4 zones (Up to 16 indoor units for each zone) • Up to 16 outdoor header units are connectable. • Setting for one of 1 to 4 zones is available. Controller for 128 units(BMS-CM1280TLE) • Individual control of up to (64 indoor units) 2 TCC-LINK buses • Individual control of up to (64 indoor units divided 1 to 64 zone) 2 TCC-LINK buses (Up to 64 indoor units for each zone) • Up to 16 outdoor header units are connectable per 1 TCC-LINK bus • Setting for (one of 1 to 64 zones) 2ch is available. • Setting for (one of 1 to 64 groups) 2ch is available. • Return back setting Common • 4 types central control settings to restrict individual operation by remote controller are selectable. • Usable with other central control devices (Up to 10 central control devices in one control circuit) • Two control mode selectively Contral controller mode/Remote controller mode • Master/Sub setting possible 10 -3 • Central remote controller TCB-SC642TLE2 BMS-CM1280TLE Indoor remote controller • Wired remote controller RBC-AMT32E RBC-AMT31E • Wired remote controller with weekly timer RBC-AMS41E • Simple wired remote controller RBC-AS21E2 • Wireless remote controller kit 10 Controls Basic function System diagram U3, U4 Model Outdoor unit Indoor unit 3-2 Central remote controller + Schedule timer Weekly operation schedule can be set by connecting a schedule timer to the central remote controller U1, U2 Indoor remote controller • Wired remote controller RBC-AMT32E RBC-AMT31E • Wired remote controller with weekly timer RBC-AMS41E • Simple wired remote controller RBC-AS21E2 • Wireless remote controller kit Indoor remote controller Single phase 220V Power supply Schedule timer Central remote controller U3, U4 • Central remote controller TCB-SC642TLE RBC-CM1280TLE + • Schedule timer TBC-EXS21TLE Outdoor unit U1, U2 Power supply Indoor unit Central remote controller Single phase 220V Even when grouping operation is performed by connecting multiple indoor units to 1 line, the indoor remote controller is required. Example of grouping operation U3, U4 3-3 Either one of the two controllers can be set as side control without indoor remote controller. Outdoor unit U1, U2 Power supply Single phase 220V (Group) Indoor remote controller is required Central remote controller U3, U4 Available Outdoor unit U1, U2 Power supply Single phase 220V (Group) Available Central remote controller 10 -4 • Central remote controller TCB-SC642TLE2 Indoor remote controller • Wired remote controller RBC-AMT32E RBC-AMT31E • Wired remote controller with weekly timer RBC-AMS41E • Wireless remote controller kit 10 Controls Basic function System diagram Power supply Model Central remote controller U3, U4 Header unit Super MMS U1, U2 3-4 Indoor unit Central management control with ‘‘1 : 1 model’’ *1 “1 : 1 model” connection interface Indoor remote controller * TOSHIBA Digital Inverter System and Super Digital Inverter System 10 -5 • Central remote controller TCB-SC642TLE2 BMS-CM1280TLE • ‘‘1 : 1 model’’ connection interface TCB-PCNT30TLE2 High-wall type for SDI/DI is not necessary this. 4-way and compact 4-way cassette type for SDI/DI need the metal fitting kit (TCB-PX30MUE). Indoor remote controller • Wired remote controller RBC-AMT32E RBC-AMT31E • Wired remote controller with weekly timer RBC-AMS41E • Simple wired remote controller RBC-AS21E2 • Wireless remote controller kit 10 Controls 4. Application control for network Basic function System diagram Model LON center LON WORKS LN Interface TCB- TCBTCBIFLN060 • • • Super MMS 4-1-1 *1 LONWORKS Remote controller “1:1 model” connection interface *1TOSHIBA Digital Inverter System and Super Digital Inverter System • LN Interface TCB-IFLN640TLE • ‘‘1 : 1 model’’ connection interface TCB-PCNT30TLE2 High-wall type for SDI/DI is not necessary this. 4-way and compact 4-way cassette type for SDI/DI need the metal fitting kit (TCBPX30MUE). The LONWORKS interface should be connected between a building management computer and a Super MMS air conditioning system. BACnet center Intelligent server TCB- ■ BACnet server software TCS-Net Relay Interface Super MMS 4-1-2 *1 BACnet Remote controller “1:1 model” connection interface *1TOSHIBA Digital Inverter System and Super Digital Inverter System • Intelligent server BMS-LSV6E • BACnet server software BMS-STBN08E • TCS-Net Relay Interface BMS-IFLSV3E • ‘‘1 : 1 model’’ connection interface TCB-PCNT30TLE2 High-wall type for SDI/DI is not necessary this. 4-way and compact 4-way cassette type for SDI/DI need the metal fitting kit (TCBPX30MUE). The local server should be connected to the BACnet network, and the Super MMS air conditioning system through the interface. Modbus Modbus Interface 4-1-3 Modbus TCB- Super MMS *1 Remote controller “1:1 model” connection interface *1TOSHIBA Digital Inverter System and Super Digital Inverter System 10 -6 • Modbus Interface TCB-IFMB640TLE • ‘‘1 : 1 model’’ connection interface TCB-PCNT30TLE2 High-wall type for SDI/DI is not necessary this. 4-way and compact 4-way cassette type for SDI/DI need the metal fitting kit (TCBPX30MUE). 10 Controls Touch screen controller system System diagram Max 64/512 Indoors/groups Touch Screen Controller 1:1model TCC-link bus Connection I/F Relay I/F RS-485 Digital I/O signal Max In3 /Out3 Max12 Ethernet Fire alarm Door key etc TCC-link bus Relay I/F Monthly report creation software Energy monitoring Relay I/F Max8 Power Meter Pulse signal Max8 4-2-1 Digital I/O Relay I/F Digital I/O signal Max8 Fire alarm Door key Error Max In 8 /Out 4 Power meter: Pulse width:50-1000ms Pulse generator constants (kWh/pulse) 0.1-99.9 Model Name Function Devices Touch Screen controller Model Name BMS-TP0641ACE Specification Max. 64 indoor units, without electrical bill calculation BMS-TP5121ACE Max. 512 indoor units, without electrical bill calculation BMS-TP0641PWE Max. 64 indoor units, with electrical bill calculation BMS-TP5121PWE Max. 512 indoor units, with electrical bill calculation TCS-Net Relay Interface BMS-IFLSV3E I/F in between Touch Screen controller & Control wiring Energy Monitoring Relay Interface BMS-IFWH4E2 I/F for Power Meter Digital I/O Relay Interface BMS-IFDD02E2 I/F for I/O signal (1) Monitoring air-conditioners Operation status can be viewed according to a unit. [Unit] All building, All tenants, Each tenant, Each area, Each air-conditioning system [Monitoring contents] Operation and alarm status, Setting status for each air-conditioning system (2) Operating of air-conditioners Header/individual control can be performed according to a unit. [Operating contents] ON/OFF, Operation setting (operation mode, air volume, louver position, setting temp., restricted setting from remote location) (3) Schedule operation Air-conditioners are operated according to the set-up schedule/operation pattern. Schedule operataion can be performed according to a unit. [Operation pattern] Weekly pattern, special day pattern (4 pattern), Non-operation days pattern (4) Alarm list display The present alarm contents are list-displayed. [Display contents] Alarm contents, Unit number, Generated time (5) Alarm record display The alarm history records are displayed. [Display contents] Alarm contents, Unit number, Generated time (6) Monthly report data extraction Monthly report data is written to ‘‘Compact Flash’’. Monthly reports can be created according to a unit using the monthly report software. [Monthly report contents] The number of ON/OFF, Operating time, Results of energy monitoring 10 -7 10 Controls Compliant Manager System diagram TCC-LINK LINE 1 Compliant Manager TCC-LINK LINE 2 HUB Local Supply (BMS-CM1280FTLE only) 4-2-2 Monitoring Operation Zone setting (64 zone x ~ 2) Individual units operation (ON/OFF, Operation mode, Setting temperature, Air volume, Filter sign) Operation restriction Alarm display Individual operation Max. 128 indoor units Return Back operation Weekly Schedule Operation* (ON/OFF) External control input Status output Fire alarm input Alarm display * accessory necessary Web Application (WEB model only) Network connection Schedule operation (ON/OFF, Setting temperature, operation mode and Remote control Permit/Prohibit) Alarm history Energy monitoring external connection* * accessory necessary • Compliant Manager BMS-CM1280TLE • Compliant Manager with WEB BMS-CM1280FTLE 10 -8 10 Controls WEB Based Controller System diagram System diagram for connecting 256FCUs or less BMS-WB2561PWE (Web Server) TCS-Net Relay I/F TCC-LINK Ethernet BMS-IFLSV3E SMMS SMMS RS-485 HUB TCS-Net Relay I/F TCC-LINK 4-2-3 MiNi-SMMS BMS-IFLSV3E SMMS I/F for Power Meter (BMS-IFWH4E2) Network, Intranet, connection through LAN port I/F for I/O signal (BMS-IFDD02E2E) Local Supply WEB Based Controller • Gateway Server BMS-WB2561PWE • TCS-Net Relay I/F BMS-IFLSV3E • Energy Monitoring Relay I/F BMS-IFWH4E2 • Digital I/O Relay I/F BMS-IFDD02E2 System diagram for connecting 257FCUs or more TCS-Net Relay I/F BMS-WB01GTE (Master Server) TCC-LINK SMMS Ethernet SMMS BMS-WB2561PWE (Gateway) RS-485 TCS-Net Relay I/F TCC-LINK SMMS HUB TCS-Net Relay I/F TCC-LINK SMMS 4-2-4 MiNi-SMMS SMMS BMS-WB2561PWE (Gateway) RS-485 Network, Intranet, connection through LAN port Enable to connector up to 2,048 FCUs TCS-Net Relay I/F TCC-LINK SMMS I/F for Power Meter (BMS-IFWH4E2) Local Supply I/F for I/O signal (BMS-IFDD02E2E) WEB Based Controller • Master server BMS-WB01GTE • Gateway Server BMS-WB2561PWE • TCS-Net Relay I/F BMS-IFLSV3E • Energy Monitoring Relay I/F BMS-IFWH4E2 • Digital I/O Relay I/F BMS-IFDD02E2 10 -9 MiNi-SMMS 10 Controls Application control of optional devices connectable to indoor units [1] Remote location ON/OFF control box Model Name Appearance Features TCB-IFCB-4E2 z Start and stop of the air conditioner is possible by a external signal and indication of operation/alarm externally. Application Function • Monitoring ON/OFF status (for indoor unit) Alarm status (system & indoor unit stop) • ON/OFF command Air conditioner can be turned ON/OFF by external signals. The external ON/OFF signals will initiate the signals shown below. Operation Interface Display Remote Controller Non-voltage ON/OFF continious signal ON/OFF COM [2] ‘‘1 : 1 model’’ connection interface Model Name Appearance Features z Link adapter for ‘‘1 : 1 model’’ into super modular multi network 1 : 1 model: Super digital inverter Digital inverter TCB-PCNT30TLE2 Connection of cables Install optional P.C. board in Electrical parts box of indoor unit. ON-OFF control devices Application Central Remote Controller Wiring diagram of indoor P.C. board Super MMS control wiring 1:1 model connection interface Indoor units Metal fitting kit (TCB-PX30MUE) is necessary for 4-way and Compact 4-way cassette type. adoptor Digital Inverter Super Digital Inverter Outdoor unit 10 -10 10 Controls Application controls by optional P.C. board of outdoor unit Application TCB-PCMO4E TCB-PCIN4E Feature [1] Power peak-cut Control The upper limit capacity of the outdoor unit is restricted based on the power peak cut request signal from outside. TCB-PCDM4E Model name * Install these optional P.C.Board in the inverter assembly of the header outdoor unit. [2] Snowfall fan control Outdoor fan is operated by a snowfall signal from outside. [3] External master ON/OFF control The outdoor unit starts or stops the system. [4] Night operation (Sound reduction) control Sound level can be reduced by restricting the compressor and fan speeds. [5] Operation mode selection control This control can restrict the selectable operation mode. [6] Error/Operation output control Error/operation are displayed and output. [7] Compressor operation output control Three compressor’s operation/stop output [8] System operation output control 10 -11