Cle Elum-Roslyn Indoor Air Quality Coalition
Transcription
Cle Elum-Roslyn Indoor Air Quality Coalition
Cle Elum-Roslyn Indoor Air Quality Coalition Final Report and Executive Summary Approved by the Cle Elum-Roslyn Indoor Air Quality Coalition: December 9, 2002 Submitted to: Cle Elum-Roslyn School Board Kittitas County Board of Health Washington State Board of Health Washington State Department of Health Final Report Writing Committee: Art Busch – Washington Education Association Jennifer Breyfogle – Cle Elum-Roslyn School Board Carolyn Booth – Kittitas County Board of Health Nancy Goodloe – Kittitas County Health Department Compiled by Nancy R. Goodloe Table of Contents Page Executive Summary …………………………………………………………………. i Final Report ………………………………………………………………………… Background …………………………………………………………………. Mission/Goals/Objectives…………………………………………………… Agencies/Resources…………………………………………………………. Assessment/Findings………………………………………………………… Remediation…………………………………………………………………. Post-Remediation Assessment………………………………………………. Recommendations…………………………………………………………… Bibliography.………………………………………………………………… 1 1 2 3 3 5 5 6 7 Appendix 1 ………………………………………………………………………….. Report #1 – Rich Prill Walkthrough Assessment April 30, 2002 8 Appendix 2 …………………………………………………………………………. 22 Report #1 – Microlab Northwest, Sampling & Testing June 13, 2002 Appendix 3 …………………………………………………………………………. 33 Report #1 – P&K Microbiological Services, Report June 28, 2002 Appendix 4 …………………………………………………………………………. 39 Results of the Student Health Assessment Washington State Department of Health, July 13, 2002 Appendix 5 …………………………………………………………………………. 59 Cle Elum-Roslyn School District Proposed 3-Phase Plan for Health & Safety June 2002 Appendices 6a & 6b ………………………………………………………………. 66 KJM Construction Management Services 6a – Remediation Documentation…………………………………………… 67 6b – Timeline for Remediation Work ……………………………………... 77 Appendices 7a & 7b ……………………………………………………………….. 78 Keathley Welsh, Inc. 7a – HVAC Assessment …………………………………………………… 79 August 15, 2002 7b – Retro-Commissioning Report ………………………………………… 82 August 28, 2002 Appendix 8 ………………………………………………………………………… 84 Report #2 Microlab Northwest Post-Remediation Testing & Sampling August 30, 2002 Appendix 9 ………………………………………………………………………… 92 Washington State Department of Health Walkthrough Inspection, WAC 246-366 September 3, 2002 Appendix 10……………………………………………………………………….. Rich Prill Post-Remediation Walkthrough Assessment October 1, 2002 96 Appendices 11a & 11b ……………………………………………………………. Cle Elum-Roslyn School District Phase 3 Plan 11a – Tracking & Monitoring …………………………………………….. 11b – Health & Safety Committee Appointment ………………………… 98 99 102 EXECUTIVE SUMMARY i Executive Summary During late 2001 and early 2002, in response to community concerns regarding the health issues of students and staff at Cle Elum-Roslyn High School, the Kittitas County Board of Health endorsed the formation of a representative coalition to address these consents. The Cle Elum-Roslyn Indoor Air Quality Coalition was formed and held its first meeting on April 2, 2002. Throughout the seven-month lifespan of the Coalition, several public and private agencies and significant human and financial resources supported an environmental assessment of the building, a health assessment of the student body, and extensive remediation work to address a “Sick Building Syndrome.” These agencies included the Washington State Department of Health (DOH), the Kittitas County Health Department, the Cle Elum-Roslyn School District, the state Office of Public Instruction, Washington State University, the Environmental Protection Agency, the Washington State Board of Health, and private environmental testing and sampling firms. Pre- and post-remediation environmental and microbiological assessments of the building were done. DOH personnel conducted a health assessment of the students in Cle Elum-Roslyn High School and compared results to a cohort of students at Ellensburg High School. The school district organized the findings and recommendations from the environmental and microbiological assessments into a three-phase plan for health and safety in the district {(1) assessment, (2) remediation and recommissioning, (3) evaluation and long-term monitoring}. They hired a special consultant from KJM Construction Management Services to oversee the remediation work on the building. The work was supported financially by the school district and a grant from the state Office of Public Instruction. The remediation work was extensive and exceeded the work that was recommended by the assessments (i.e., the building’s HVAC system was recommissioned.) Post-remediation environmental and microbiological assessments indicated the school district’s remediation efforts were thorough and successful in addressing the “sick building syndrome.” The recommissioning process confirmed the HVAC system was installed and was functioning as designed and specified and was performing within acceptable limits. The Coalition completed its work with a review of the school district’s long-term plan for maintenance and monitoring of the building and its environment. The Coalition made the following recommendations to the Cle Elum-Roslyn School Board: The Coalition makes the following recommendations to the Cle Elum-Roslyn School Board: 1. Educate/train students and staff so they can enhance the efforts of the custodial staff to maintain the air quality and general hygiene of the building. 2. Implement the Phase 3 plan for long term monitoring and evaluation of the health issues and building concerns of the district. 3. Maintain a dynamic Health and Safety Committee within the district. 4. Consider the budget for maintenance and upkeep of the buildings in the district as a priority item in the yearly budget planning process. ii 5. In light of the school nurse’s role in the monitoring of the health issues at all three levels of the district, future consideration could be given to making this position full-time. The Coalition makes the following recommendations to the staff and students of the Cle Elum-Roslyn School District: 1. Commit your time and energies to develop strong communication channels within the district. 2. Take advantage of the “Tools for Schools” training opportunities and get involved in helping monitor your building. 3. Work collaboratively with district administration and be proactive with problemsolving. The Coalition makes the following recommendations to the parents and citizens of the Cle Elum-Roslyn School District: 1. Continue to be concerned, involved parents/community members in the school environment and strive to build on the relationships and trust that has begun here. 2. Be committed to being informed about school issues. 3. Monitor the meetings of the district’s Health & Safety Committee. 4. Rely on clear and accurate information that has been verified. The Coalition finished its work on December 2, 2002. The final report with recommendations was forwarded to the Cle Elum-Roslyn School Board and the Kittitas County Board of Health. iii Cle Elum-Roslyn Indoor Air Quality Coalition April 1, 2002 – December 2, 2002 Final Report I Background Circa 1995 the Cle Elum-Roslyn School District undertook a major reconstruction project in the high school building. When students and staff returned to the newly renovated high school, health complaints emerged. Because of the persistent nature of these complaints, the Kittitas County Health Department formed a task force to address the situation and was instrumental in recruiting personnel from the National Institute for Occupational Safety and Health (NIOSH) to visit the campus and conduct a series of tests. The NIOSH report1 identified some problem areas in the building and made recommendations for remediation. The district followed with some remediation efforts. From 1995 to the spring of 2002 the concerns about the environment of the high school escalated. Staff from Kittitas County Health Department and the Washington State Department of Health visited the building on several occasions, performed smoke tests in the crawl space, and visually examined the building. Some additional testing was conducted. A clear nexus was never established between the reported illnesses and contamination of the building. However, certain patterns seemed to emerge, i.e., symptoms were better or worse depending on the season and those with symptoms experienced a lessening or disappearance of symptoms during vacations or holidays. During late 2001 and early 2002, community concerns escalated. In response to these persistent complaints, The Kittitas County Board of Health held its monthly meeting in Cle Elum on March 28, 2002 and received testimony from parents, students, and school officials. Subsequent to this meeting, a representative coalition was formed and held its first meeting on April 2, 2002. II Mission Statement/Goals and Objectives Mission The mission of the Cle Elum/Roslyn IAQ Coalition is to enhance the communication and foster a collaborative discussion between students, parents, teachers, school district personnel, citizens and the Department of Health to make short and long term recommendations that help ensure a safe and healthy learning environment in all facilities of the Cle Elum/Roslyn School District. Goal #1 and objectives By April 30, 2002 establish a balanced, community-based coalition (maximum number = 24) to study the IAQ issues in Cle Elum/Roslyn School District and make appropriate recommendation to these issues. a. Identify the following numbers of persons from each area: 1. 4 students, one from each class at the high school 1 2. 4 teachers – CEREA representatives 3. 3 persons from the administrative of the school district 4. 2 persons from PSE 5. 1 person from the school board 6. 2 persons from Clean Air Now 7. 8 members representing parents and concerned citizens b. Appoint representation from the Kittitas County Board of Health as consultants to the process. c. Schedule weekly meetings through June 2002 and then evaluate this time schedule. d. Elect appropriate coalition members to administrative roles as the process dictates. Goal #2 and objectives To find reliable/valid information that may establish a relationship between the indoor air quality of the school and the health concerns of students, teachers, staff and parents. a. Conduct a building walkthrough with Rich Prill, building specialist, by April 15. b. Review results and recommendations from Rich Prill, April 30. c. Collaborate with DOH personnel on a follow-up plan. d. Collaborate with DOH personnel to develop and administer a health assessment instrument at CE/R high school on May 9. e. Administer the health assessment to a cohort of students from a control group on May 16. f. Review preliminary findings of health assessment with DOH personnel by June 12. g. Evaluate health assessment results and make recommendations, if necessary. h. Review all data gathering efforts to date and evaluate the information in place. i. Discuss and/or recommend additional strategies that could produce additional information, if necessary. Goal #3 and objectives Enhance communication between the school district administration, teachers, students and the community on this issue. a. Conduct coalition meetings and invite interested persons to listen to the deliberations. b. Reproduce weekly Coalition minutes and make these available in the school and at various locations within the community. c. Coordinate with the upper county media to produce a weekly column in the Northern Kittitas County Tribune. d. Provide information to media at the Ellensburg Daily Record on a weekly basis. e. Coordinate with the school district in creating an information kiosk in the high school. f. Add to the Coalition agenda a monthly report on maintenance and repair activities at the school. 2 Goal #4 and objectives Assist the school district with infrastructure building activities that will create a long-term process for monitoring the building and any health or safety issues that might arise. a. Encourage the school district to make Indoor Air Quality a function of the school safety committee. b. Discuss and send recommendations pertaining to Indoor Air Quality to the School Board for policy consideration. Goals 1, 2, and 4 were met. Goal 3 was partially realized. III Agencies and Resources Several agencies supported the work of this Coalition with their time, fiscal and financial resources. Among these were: The Kittitas County Board of Health supported the involvement of the administrator of the county health department as a facilitator in the coalition process. This represented a significant investment of staff time and department resources. The Board heard monthly reports on the progress of the Coalition. A Board member served on the Coalition. The Cle Elum-Roslyn School Board provided membership on the Coalition and heard public testimony from concerned students, teachers, and community members at several of it meetings. The Board approved the district’s plan for health and safety and authorized additional expenditures (microbiological testing and consulting) that supported the remediation and recommissioning of the building and its systems. The Office of Public Instruction provided significant funding that enabled the remediation and recommissioning of the building ($55,000). Washington State University, through a grant from the Environmental Protection Agency, provided the services of an Indoor Air Quality specialist for consultation and a follow-up report after a walkthrough assessment of the building in April 2002. This report became the basis for the work of the Coalition. In addition, this specialist returned to the building in October 2002 for a second walkthrough after the district’s remediation efforts were completed. The Washington State Department of Health, Office of Environmental Health Assessment provided the resources to develop, implement and provide a final report to the coalition on a student health assessment. Staff from this office also provided significant technical support, consultation, and interpretation on the microbiological assessment of the tape lifts and bulk samples taken from the high school building. The Washington State Board of Health was supportive of the work of the Coalition facilitator and consistently heard testimony from community members at its monthly meetings. IV Assessment and Findings The Coalition, utilizing many resources, conducted a systematic and comprehensive investigation process that included assessments by an Indoor Air Quality specialist from Washington State University, a professional sampling and testing firm, and a student health assessment by staff from the Washington State Department of Health. Highlights of these processes are discussed below. Upon the recommendation of Dr. Harriet Amman, State Department of Health, Rich Prill, Building Specialist from Washington State University and the Environmental 3 Protection Agency was scheduled for a walkthrough of the high school on April 15, 2002 and presented his final report to the Coalition on April 30, 2002. His full report may be viewed in Appendix 1. Prill noted that the building had all of the symptoms of a “sick building syndrome”. He said there may be no single cause for this syndrome. Any attempt to address the problems associated with the syndrome had to be comprehensive. He made several recommendations containing suggestions for maintenance and remediation work as well as suggestions regarding testing and sampling in the building. Some of his more significant findings included: a. Depressurize the crawl space and provide monitors in key hallway areas so that everyone can monitor this depressurization on a daily basis. b. Clean or replace the carpet in the classrooms. c. Check potential for external wicking in noted areas Based on Prill’s recommendations for sampling and testing, the Coalition recommended and the school district hired Russ Crutcher of Microlab Northwest to conduct tape lift and bulk sampling on June 8, 2002. Crutcher took numerous tape lift and bulk samples from selected classrooms and exterior areas of the building (specific sites determined by input from teachers in the high school). Based on his understanding of the history of the concerns and upon the request of the Coalition facilitator, Crutcher recommended a selection of samples for testing and analysis in his lab as well as a microbiological testing and analysis of selected samples by P & K Laboratory in New Jersey. Crutcher presented his findings to the Coalition on June 13, 2002. His recommendations and findings are contained in Appendix 2. His findings included but were not limited to: a. Heavy particulate loading throughout the building. b. Extremely dirty carpets throughout the building. c. A limited fungal problem under one hallway tile near a drink machine. d. Potential wicking of moisture in certain areas on the outside of the building. e. One leaking heater in one of the classrooms. f. Absence of glass fibers in the environment. Crutcher’s remediation recommendations were to provide a thorough cleaning to the building, clean or get rid of the carpet, thoroughly examine the hallway area where the mold sample was identified and clean the area, and fix the leaky heater. He saw moisture wicking at certain exterior areas of the building but found no evidence of a fungal problem in these areas. A second set of samples was sent to P & K Laboratory in New Jersey for a microbiological analysis. Samples were tested based upon recommendation from Dr. Harriet Amman of the Department of Health. This analysis included microscopic dust characterization of selected tape lift and bulk samples and fungal/bacterial analysis (culture method) of selected bulk samples. Dr. Harriet Amman (via phone conference) provided an interpretation of these results for the Coalition on June 28, 2002. Dr. Amman found that the P&K results validated and supported the findings of Microlab Northwest. There was a limited fungal problem that was not a threat to health as well as heavy particulate matter present in the bulk and tape lift samples. Dr. Amman indicated that these findings supported Crutcher’s recommendation for remediation. (Appendix 3) Staff from the Washington State Department of Health, Office of Environmental Assessment, collaborated with Coalition members in the development of a health assessment survey instrument. The survey was administered to students in Cle Elum4 Roslyn High school on two Thursdays in May 2002 and to a cohort of students at Ellensburg High school on two Thursdays in May 2002. In general, symptoms were reported two to three times more frequently in Cle Elum than in Ellensburg with several symptoms being reported by a relatively large proportion of the students. The most frequently reported site of onset was at the entrance to the school. A relatively large number of students reported the location of symptom onset in classrooms and areas scattered throughout the school, and these reports did not cluster by wing or general area. These data can be used as baseline data to determine if reports of symptoms decline after building remediation work (Appendix 4). V Remediation The school district developed a three-phase plan for health and safety and presented the final draft to the Coalition in June 2002 (see Appendix 5). The plan provided for a (1) planning and assessment phase, (2) a remediation and HVAC recommissioning phase, and (3) an evaluation and long-term plan for maintenance and monitoring The district hired a consultant from KJM Construction Management Services in Seattle to organize and oversee the remediation work. This work evolved during July and August 2002. Details of this work are reported in Appendix 6 and include a checklist of all work that was done at the school, a timeline for task completion, and a final report of the work. The remediation checklist was extensive and work accomplished exceeded the recommendations of Rich Prill and Microlab Northwest. As an example, Keathley Welsh Associates conducted an assessment of the HVAC system and made several recommendations for recommissioning of this system (Appendix 7). These recommendations were added to the checklist, and all of these recommendations were completed as part of the remediation work. This recommissioning process confirmed that the HVAC system was installed and was functioning as designed and specified and was performing within acceptable parameters.2 The remediation project ended on October 1, 2002. VI Post-Remediation Assessment On August 30, 2002 Microlab Northwest conducted environmental sampling and testing, replicating several of the samples and tests that were done in June 2002. Air sampling was included in this post-remediation assessment. Results indicated: a. There was not a glass fiber problem in the rooms tested. b. There was not a general fungal problem in the rooms tested. c. The carpets had been thoroughly cleaned. d. Horizontal surfaces had not been cleaned at the time of sampling. e. Airborne dust loading outside the building varied dramatically and can be quite high. f. Airborne dust loading inside the building can be quite high even in an "at rest" condition. g. Discoloration of the blanket insulation in the overhead area was due to dust and not fungal growth. h. The exterior siding had some fungal growth on the wood but not on the waterbarrier board. The full report is available in Appendix 8. 5 On September 3, 2002 Rich Ellis and Tim Hardin, State Department of Health, conducted an inspection of the high school per directions from WAC 246-366. Their report indicated that no facility issues were observed that would prevent the school from functioning normally during the school year (Appendix 9). On October 1, 2002 Rich Prill conducted a second walkthrough inspection of the building and indicated that all of his recommendations to address the “sick building syndrome” had been successfully addressed by the school district (Appendix 10). The district’s Phase 3 plan for long-term monitoring and maintenance will be presented at the same meeting this report is presented for approval. It will become Appendix 11 of this report. VII Recommendations The Coalition makes the following recommendations to the Cle Elum-Roslyn School Board: 1. Educate/train students and staff so they can enhance the efforts of the custodial staff to maintain the air quality and general hygiene of the building. 2. Implement the Phase 3 plan for long term monitoring and evaluation of the health issues and building concerns of the district. 3. Maintain a dynamic Health and Safety Committee within the district. 4. Consider the budget for maintenance and upkeep of the buildings in the district as a priority item in the yearly budget planning process. 5. In light of the school nurse’s role in the monitoring of the health issues at all three levels of the district, consider making this position full-time. The Coalition makes the following recommendations to the staff and students of the Cle Elum-Roslyn School District: 1. Commit your time and energies to develop strong communication channels within the district. 2. Take advantage of the “Tools for Schools” training opportunities and get involved in helping monitor your building. 3. Work collaboratively with district administration and be proactive with problemsolving. The Coalition makes the following recommendations to the parents and citizens of the Cle Elum-Roslyn School District: 1. Continue to be concerned, involved parents/community members in the school environment and strive to build on the relationships and trust that has begun here. 2. Be committed to being informed about school issues. 3. Monitor the meetings of the district Health & Safety Committee. 4. Make assumptions on clear and accurate information that has been verified. With the transmittal of this report, the Cle Elum-Roslyn Indoor Air Quality Coalition completes its work. 6 Bibliography 1. Daniels, W. & Martinez, K. Health Hazard Evaluation Report 97-0045. Cle Elum-Roslyn High School. Cle Elum, Washington, February 1998. Cincinnati, OH: NIOSH Publications Office, 4676 Columbia Parkway. 2. Clint Marsh, KJM Construction Management Services, Seattle, WA. November 6, 2002. 7 Appendix 1 Report #1 – Rich Prill Walkthrough Assessment April 30, 2002 8 Appendix 1 Final Report from Rich Prill Walkthrough #1 Summary of IAQ Walk-Around Findings Prepared by Rich Prill, WSU Cooperative Extension Energy Program Cle Elum – Roslyn High School School District 404 2692 SR 903 Swenson Date: 4/15/2002 IAQ Coordinator: Tom Cle Elum, WA 98922 Operator: Tom Swenson 509-649-2292 Principal: Lee Maras # Students: 317 Grades: 9 - 12 Year Built: 1967, remodel in mid 1990s ---------------------------------------------------------- Guiding principles for maintaining good indoor air quality: 1) Remove and exclude potential indoor air contaminants excluding pollutants from the building is clearly the most reliable and effective method to eliminate exposure. Identify contaminants and remove or contain them, develop policies and guidance to keep pollutants out in the future. 2) Control those pollutants you can’t exclude It isn’t possible to exclude or eliminate all potential indoor air pollutants from schools – occupants themselves contribute moisture, particles, volatile organic compounds (VOCs = personal care products, drycleaning compounds, etc), odors, carbon dioxide, and even mold spores. Classroom activities include use of materials that can cause problems: dryerase markers, glues, paper particles, chalk dust, laminators and photocopiers, art, science and shop materials, etc. To the extent possible, use pressure controls to keep shops, science, art areas “down wind” from other zones. Air should move from clean areas to dirty areas: examples include exhaust fans in paint booths, dark room, 9 science fume hood, and locker rooms, restrooms, kitchens, photocopy and laminator areas. Another important example of air moving from clean to dirty is a well-sealed crawlspace that is maintained at a slight “vacuum” compared to occupied zones (using a properly sized exhaust fan operated 24/7) effectively and reliably preventing crawlspace air and any contaminants from reaching the occupants. 3) Provide adequate ventilation Occupied buildings need to have adequate air exchange to remove and dilute those pollutants generated indoors from people, activities, equipment, custodial chemicals, etc. By controlling pollutants (see 1 & 2 above) standard building ventilation rates will be adequate. Current guidelines and standards specify 15 cubic feet per minute of outside per-person for classrooms, and 20 cubic feet per minute outside air per-person for offices & conference rooms. Ventilation rates can be easily and routinely checked using carbon dioxide measurements. 4) Keep the building dry and clean Moisture in buildings can lead to mold problems. Water incursion from rain and snow melt, ground water, leaky or sweating pipes, spills, over-saturation of carpets during cleaning, and high humidity from internal moisture generation, etc. all need to be controlled to prevent mold and moisture problems. The building must effectively shed water: roof, windows, doors, siding, driveways & sidewalks, storm drains, etc. Ensure proper flashing and drip caps are used, seals around windows, flashing, vents, etc. are maintained, and surfaces slope the right direction: if it can leak, it probably will. Adequate ventilation with outside air (see #3 above) will dry out the building from occupant breathing and other “normal” moisture sources even when it’s extremely wet outdoors. ---------------------------------------------------------History of IAQ problems at Cle Elum–Roslyn High School Remodel resulted in a variety of problems. These problems have been documented and various studies and assessments have been conducted. 10 Problems include, but are not limited to: • Water incursion due to ice dams • Water/moisture due to construction practices, flashing details, roof and site drainage, plumbing, fire sprinkler system. • Air handling equipment: ducts, fabrication, and installation. • On-going reports of building-related health symptoms/problems. ----------------------------------------------------Findings & observations from the IAQ Walk-Through 4/15/2002 • • • • • • • • • • Entry Areas, Hallways Walk off mats in place at entryways = OK Tile hallways = clean. Tile halls are recommended over carpet. Observed tiles in portions of the hallway are distorted – it was reported that the tiles are installed on particle-board flooring that has been subjected to excess moisture. Mechanical, Custodial, Storage Boiler room = equipment appeared to be in good condition and combustion air appeared adequate. No measurable carbon monoxide. Carbon dioxide OK. No evidence of combustion gas spillage or backdrafting at gas water heaters. Carbon monoxide detectors/alarms not present. Custodial areas = carpet vacuum equipment uses paper filter bags which is fairly standard in most schools. Did not observe dangerous materials stored in these areas. The air-handling units are located in the school attic space. These units appeared to be in very good condition, most are fitted with pleated filters, and the filters were clean and dated (April 2002). Air ducts are lined with typical fiberglass duct-lining material with an integral facing material covering the fiberglass. All air ducts are dirty to some degree – the ducts observed during this assessment were coated with dust and debris to varying degrees. Air handling unit # 14 was curious: it was equipped with return air dampers, but instead of a duct it had a sheet metal plate over the dampers (the design intent was unclear so perhaps this unit is OK ?). “Sawdust” was observed in the woodshop air handling unit and the duct system. 11 • • • • • • • • • Lined ducts are difficult to “clean” compared to hard-surface ducts with the insulation applied on the outside. Again, all ducts in buildings contain dust and debris to some extent. The interior of the ducts that bring outside air into the various air handling units was not accessible for inspection. Ventilation Most classrooms were equipped with operable windows = 5 rooms had at least one window open, while 12 rooms had all windows closed. All classrooms except auto shop building were equipped with mechanical ventilation system to provide fresh air. The mechanical ventilation systems were operating in all rooms visited. All rooms - except room # 200 - had carbon dioxide concentrations at or below 1,000 parts-per-million (ppm) as measured with a calibrated instrument. A summary of the carbon dioxide measurement results were provided at the end of the assessment visit. Room # 200 carbon dioxide was measured at 1,420 ppm in the breathing zone and 1,200 ppm out of the supply diffusers, indicating that some outside air was being allowed into the system. Outside air carbon dioxide measurements yielded 380 ppm at 9:50 am and 399 ppm at 2:15 pm. The Gym and the “Commons” areas are both equipped with carbon dioxide sensors designed to automatically control outside air based on occupancy rate in these zones. Apparently, these sensors are faulty and are being replaced. Classrooms and “Portable” Units • Classrooms were carpeted except for science, art, XXXXX • Classrooms equipped with dry-erase white boards and marking pens – a variety of pens were observed (some brands of pens have lower odor than others). • Home Ec (room # 302) was equipped with working exhaust for the cooking ranges. Air observed coming out of sink cabinet – unknown source of this air. • Most classrooms were under a slight negative pressure relative to the hallways and a slight positive pressure relative to the exterior of the building. • Proper airflow pattern was observed in the science classroom: air was flowing from the science classroom into the chemical storage area. 12 • • • • • • Science teacher explained that the science classroom fume hood works properly and is used appropriately. Large volumes of air into classrooms from the crawlspace were not observed. Room 104 cooking popcorn – odor was clearly noticeable down the hallway. The relief airflow in room 104 was minimal. Room 201 television monitor was covered with significant amount of dust, suggesting either a lack of housekeeping or a source of particulate matter. Room 300 contained a laminator – these produce VOCs when operated. Stained ceiling tiles were observed in some classrooms. Labs & Shops • Auto shop heated by a “residential-type” propane furnace with ducts located inside the conditioned space. No outside air is ducted to the furnace. • Auto shop paints and solvents are used either outside or near a window with a “box fan” used to assist with fume exhaust. No carbon monoxide detector/alarm installed. • Wood shop is equipped with a dust collection system connected to woodworking machines. The paint booth exhaust fan works fine. • Dark room is equipped with a revolving door and exhaust fan – works fine. • Art room has fume hood – works fine. Office, Staff & Workroom, Library, Counselor/Speech, • Library contains sofas (potential source of asthma triggers). • Recording room was operating at a slight negative pressure relative to library. Air was observed going into the recording room wall – unknown destination for this air (air into a wall is usually preferable to air coming out of a wall unless it is known where the air is coming from). • Credit Resources room contained a paper shredder (source of particles) and a cook range with working exhaust. Air was observed coming into the room from an interior wall. • Counselor’s office contained a portable air cleaner (filtration system). Counselor reported frequent odors from rooms 104 and Credit Resources. • Main office contains paper shredder (source of particles) and a portable air cleaner (filtration system). 13 • • • • • • • • • • • Nurse’s room contains two photocopiers (source of VOCs, particles, heat, ozone). An exhaust grill is located at the ceiling. Stained ceiling tiles were observed in some rooms. Crawlspaces A number of crawlspace locations were visited. Damp sand/soil was observed in a couple of areas near the exterior walls. This is typical of crawlspaces, especially after seasonal snow melt and rain events. No standing water or signs of excessive water intrusion was observed. No mold or signs of excess moisture was observed on structural materials, ducts, pipes, conduit, etc. The crawlspace did not smell unusually musty or moldy – it smelled like a “typical crawlspace”. Daylight was not observed at the perimeter of the crawlspace, indicating a minimum of outside air ventilation was being provided. Entry hatches to the crawlspace from the occupied areas of the school were not weather-stripped or air-sealed. However, for those hatches that were checked, air was observed flowing from the school into the crawlspace. A carbon dioxide measurement of 450 ppm was collected from crawlspace air exiting at an exterior perimeter crawlspace vent. This indicates school air is entering in the crawlspace. It was obvious that this is not a “typical” crawlspace: o All the ducts had been abandoned and lay on the crawlspace floor – with the exception of the Home Ec range hood exhaust duct system. o The crawlspace ceiling (underside of school floor) was thoroughly sealed with a layer of spray-on foam. o Additional foam sealant had been applied around ducts, plumbing pipes, electrical conduit, wiring, and other penetrations. o The vapor-retarding membrane (black plastic) on the ground had been “shredded” by the activities in the crawlspace – the membrane material was buried under a few inches of sand. o A “fog” machine (typical of theatrical smoke generator) was located in the crawlspace, and is used to check the integrity of 14 the air seal between the crawlspace and the occupied areas of the school above. • • • • • • • • • • Attics No indication of active or recent water leaks were observed. No indication of possible mold growth. Air handling equipment is located in the attics – an excellent practice (many schools have air handling equipment located on top of the roof exposed to the weather!). Exterior & Roofs Roof is composition shingles in good condition. Roof drainage creates splashing onto siding in some areas, and saturated soil in some areas. Questionable flashing and drip-cap details were observed in a couple of locations (example: roof at southeast corner at Home Ec room). Roof structure contains foam insulation between shingles and the roof decking (thus the attic is part of the conditioned space). Reports of ice-dams. General: No wet or moist materials were observed or measured in the school (suspect walls and ceiling tiles were tested with moisture meters). Relative humidity measurements in various locations suggest the building was between 25% and 30% relative humidity. • -------------------------------------------------------------------------------------- Recommendations Based on findings & observations from the IAQ Walk-Through 4/15/2002 Priority* To be determined by school district (and others) 1 2 3 4 Crawlspaces under the building contain open soil, moisture, documented mold spores in the past, and a variety of debris. Make use of the extraordinary (and relatively thorough) air sealing at the crawlspace ceiling 15 by installing exhaust fans and ducts to depressurize this area (“slight vacuum”) of approximately .10 to 25 inches water column) to effectively and continuously exclude crawlspace air entry to occupied areas of building. The exhaust fan(s) will control pressures and thus air flow direction: air should move from “clean” areas to “dirty” areas and ultimately out of the building through the exhaust stacks. Stacks should exhaust above roofline to prevent exposure to individuals at ground level or possible re-entrainment into open windows or doors. Locate exhausts a sufficient distance away from air intakes for the ventilation systems located at the roof! Install pressure gauges - readily visible to occupants - to monitor the crawlspace pressure to ensure continuous and adequate pressure control. Air should be moving from the occupied spaces to the crawlspace at all times. 1 2 3 4 Continue to use track off mats at all entrances. Trackoff systems help control entry of dust & moisture. These should be regularly maintained and not allowed to remain wet for more than a few days. 1 2 3 4 Suggest routine carbon dioxide measurements throughout the facility using calibrated instrumentation. Carbon dioxide is a convenient and relatively inexpensive method to monitor ventilation with outdoor air. Carbon dioxide concentrations should be maintained below about 1,000 ppm to help ensure proper air exchange (see CO2 handout for details). Only one room (# 200) appeared to be under-ventilated during the assessment. 1 2 3 4 The buildings contain gas appliances. Install carbon monoxide detectors/alarms with digital display and data recording capabilities in boiler room and in a general occupied area(s) so occupants can monitor the displayed values. Also install carbon monoxide detectors/alarms with digital display and data recording capabilities in the 16 auto shop, to monitor combustion gases from not only the furnace but also internal combustions engines. 1 2 3 4 Control potential asthma triggers in the school. Asthma triggers include volatile organic compounds (VOC), particles, smoke, mold, animal dander, combustion byproducts. Limit VOC exposure through the careful selection and use of cleaning chemicals, classroom materials including glues, paints, and the ubiquitous white board dry-erase marking pens (some brands are much less noxious than others), encourage perfume-free classrooms, etc. Keep carpets clean and use high efficiency vacuum equipment to prevent pulling allergens and asthma triggers out of carpets and spraying them into the air. 1 2 3 4 Routinely fill all drain traps to prevent sewer gas entry into school. Some schools add a layer with mineral oil on top of the water in the trap to retard evaporation. 1 2 3 4 Provide effective exhaust for containment (“dirty”) areas. Complete the evaluation and repair and/or upgrade of exhaust fans to provide sufficient flow in toilet, locker room, and custodial areas. Use exhaust fans to control pressures and thus air flow direction: air should move from “clean” areas to “dirty” areas and ultimately out of the building through the exhaust stacks. Fan controls and time clocks should be set to run exhaust fans as appropriate: science chemical storage, locker rooms, custodial closets, etc. should be kept under negative pressure 24/7. 1 2 3 4 Regularly check exhaust function in science storage, science fume hood, dark room, clothes dryer exhaust, shops, etc. 1 2 3 4 Place photocopiers and laminator exhaust-only room, or equip these with an exhaust hood and fan. 17 1 2 3 4 The interior of the ducts that bring outside air into the various air handling units was not accessible for inspection – since these bring in raw outside air (unfiltered, wet/dry, etc.) inspection access doors or panels should be installed to allow routine inspection. 1 2 3 4 Carefully inspect the air handling system for wood shop and clean wood dust from equipment and ducts. Consider installing filters on the return (suction-side) grills in the wood shop to keep debris out of ducts and the equipment – teacher and students can visually inspect and notify facilities staff should these become prematurely loaded. Keep door to attic space and wood shop closed. 1 2 3 4 Redesign and install proper flashing and drip caps around the exterior of the building where improper design and construction of these details have allowed rain and snow melt to enter building envelope. Thoroughly inspect behind siding and inside of walls where rain/snow melt has entered the building envelope – look for structural damage and potential mold growth. 1 2 3 4 Add gutters, downspouts, and other measures (splash guards, etc) to prevent rain and snow melt from splashing onto building, run toward building, pool, or collect near buildings (includes auto shop building). Note that water can wick up behind siding or other materials, and is easily wicked by concrete. 1 2 3 4 Upgrade the filters in the air handlers where needed. Add spacers or gaskets to ensure filters fit tightly into air handling cabinets/ducts and there are no air bypasses around the filters. Clean heating coils where needed to ensure proper air-flow and to improve energy efficiency. 1 2 3 4 Air handling unit # 14 was curious: it was equipped with return air dampers, but instead of a duct it had a sheet metal plate over the dampers. The design intent should be checked and modifications performed as necessary. 18 1 2 3 4 Routine monitoring for radon gas should be conducted unless crawlspace is adequately depressurized 24/7 1 2 3 4 Consider removing carpet from the building. Many indoor air professionals highly recommend that carpet not be used in schools. However, this topic is hotly debated by proponents on both sides of the carpet/no-carpet issue. Until the carpet issue in this school is resolved, use high quality steam extraction to thoroughly clean the current carpet (avoid chemicals and detergents). Upgrade the vacuuming equipment to HEPA rated machines – the current equipment does not capture the small particles (asthma and allergy triggers) and these can remain suspended for hours and days. Recommendations for Further Investigation and/or Testing Based on findings & observations from the IAQ Walk-Through 4/15/2002 These are my suggestions only. Prior to conducting these investigations/tests it is recommended that detailed discussion occur with testing laboratories and consultants. Collection and handling of samples is necessary to ensure that the results obtained are as meaningful and helpful as possible in leading to some solutions. It should be stressed that sampling is only a tool, not a solution. The results of these investigations and/or samples may indicate additional sampling or investigation is warranted. 1. The carpeting in the school is the original carpet from the remodel in 1996. This carpet may contain dead and living mold or other allergens that can cause health symptoms/problems. a. Collect bulk samples of carpet: i. suspected problem areas ii. areas suspected to be OK. iii. 2 square inch samples or disks (check with lab) iv. also collect the debris from under the carpet 19 2. To help determine types of pollutants and particles present in the school, collect “tape lift” settled-duct samples from both suspected problem areas and some from areas suspected to be OK. a. 3 samples per room: i. teacher’s area: top of desk ii. general room area: top of chalk board, picture frame, etc. iii. student area: top of book case, cabinet, etc. 3. Most of the air ducts contain duct-lining material. These ducts (like all ducts) have some debris on the surface. Samples of this duct-lining material can be collected and analyzed. a. samples of duct material from the outside air duct(s). b. sample of duct material from ducts serving suspected problem areas. c. sample of duct material from ducts serving areas suspected to be OK . 4. Various locations at the exterior appear to allow rain and/or snow melt to enter the building shell due to improper flashing, failed sealants, or splash from sidewalks/ground. a. The siding or other materials should be removed from these areas and a thorough inspection of the building materials, wall cavities, and extent of moisture migration or damage determined. b. In the event that mold growth is discovered or is suspected, tape lift or bulk samples can be analyzed. 5. Test the textured (popcorn) ceiling material in the auto shop for asbestos. a. The space is currently occupied and it is good practice to identify areas with asbestos. b. Should the building be renovated, moved, or demolished, the presence (or absence) of asbestos will need to be determined. 6. Background samples should be taken at the same time as the above samples. a. Air samples of the outside air. 20 b. Air samples in suspected problem areas. c. Air sample in areas suspected to be OK. 21 Appendix 2 Report #1 – Microlab Northwest Sampling & Testing June 13, 2002 22 MICROLAB NORTHWEST 7609 140TH PL. NE REDMOND, WA 98052 PHONE: (425) 885-9419 LABORATORY REPORT TO: Nancy Goodloe REPORT #: 632-02 507 Nanum DATE: June 8, 2002 Ellensburg, WA 98926 PHONE: (FAX: (e-mail: ngoodloe@co.kittitas.wa.us) SUBJECT: Particle Identification SPECIMEN: Tapelifts From Rooms and Ventilation System, Flooring, and Siding Samples SUMMARY On June 1, 2002 a number of tapelift and material samples were collected from Cle Elum High School by E. R. Crutcher with the assistance of Nancy Goodloe, Tom Swenson, Jim Green, and Thelma Simon. All samples were collected in duplicate. Tapelifts were collected from rooms 100, 200, 201, 203, 300, 384, the Library, the Computer Lab, the Teacher's Lounge, and from the hallway outside Room 300. Five of these were analyzed for this report, rooms 100, 200, 300, the Library, and the Teacher's Lounge. Carpet samples were collected from rooms 100, 203, 300, 391, and the Library. The interior wall was opened and a section of the wallboard taken for examination from rooms 100, 201, 384, and from the hallway adjoining Room 300. Curled or cracked floor tile samples were collected outside room 100, 102, 300, and the Main Office. Exterior wall samples were collected outside Room 100, by the east building entry, and from outside the offices near the main entry. Three of the ventilation systems were sampled. Two of those were at intakes and one was a supply air system sample. The analysis shows the following: 1. There is not a glass fiber problem in the rooms tested. 2. There is not a general fungal problem in the rooms tested. 3. There is a water leakage problem with the univent heater units, specifically in Room 203. 4. There is a limited fungal problem in the hallway, under the floor tiles, outside Room 100. 5. Carpet cleanliness is an issue. Food debris in the carpets needs to be controlled. 6. Water splashing onto exterior panels or being directed down exterior panels is degrading the exterior and water is penetrating into the inside of the exterior walls at these locations. 7. A significant source of biological material in the classroom is track-in debris from outside. Additional observations are provided in the body of the report and in the conclusion. A list of recommendations is provided at the end of this report. Signed: ________________________________________ E. R. Crutcher, Consultant 23 INTRODUCTION On June 1, 2002, a number of tapelift and material samples were collected from Cle Elum High School. The samples were collected in response to a number of health complaints. The samples were collected by E. R. Crutcher of this laboratory with the assistance of Nancy Goodloe and Tom Swenson . All sampling was witnessed and documented by Jim Green and Thelma Simon of the "Clean Air Now" group and the IAQ Coalition. The original plan was to collect samples from five rooms, tile samples from the hall, exterior wall samples, and samples from the ventilation system. That plan was followed with tapelifts from an additional five rooms collected for future reference. All samples were collected in duplicate so that duplicate samples could be submitted to other laboratories as both a Quality Assurance technique and to add detail to the analysis. Photographs were taken to document the sample locations. The samples collected were as follows: Tapelifts Room 100, Window At Univent Heater Room 100, TV Center Room 100, Table by Teachers Desk Room 200, Teachers Desk Room 200, Top of Picture Frames Stacked on File Cabinet Room 200, Carpet Room 200, Top of Computer Table Room 200, Student Desks, 4 Contacts Room 201, By Computer on Desk Room 201, TV Table Room 201, Counter Against Wall Room 203, Univent Heater Room 203, Top of Speaker Room 203, Sub-flooring at Water Leak Room 300, Top of Computer Monitor, Front Desk Room 300, Top of File Cabinet Room 300, Shelf of Middle Bench Room 300, Air Handler Room 303, Top of Printer, Front Computer Desk Room 303, Book Shelf in Back of Room Room 303, Table in the Middle of the Room Room 384, Computer Lab, Large Jet Printer Computer Lab, Back Wall, Window Enclosure Hall, Outside Room 300 Library, Location of Old Desk Library, New Desk Location in Main Room Library, Bookshelf Near Wall, Under Broken Acoustic Tile Library, Shelf Near Network Room 24 Library, Table in the Middle of the Room Hall, Coke Machines Near Gym Teacher’s Lounge, Refrigerator Teacher’s Lounge, Microwave in Corner of Room Teacher’s Lounge, Monitor by Crawlspace Access (Only the samples from Rooms 100, 200, 300, the Library and the Teacher's Lounge were to be analyzed at this time.) Ventilation System Intake Access Panel 20’ From Exterior, Access From Shop Intake Access Panel Near Exterior, Access From Room 384 Supply Air, Filter Access Panel, Access Near Gym (These were collected as tapelifts from the duct liner) Carpet Room 100, Room 203, Univent Heater At Teacher’s Desk Room 300, Near Air Handler (Reported Water Exposure) Library, Near Entry to Network Room Room 391, Under Sink At Desk (All of the Carpet samples were collected at locations reported by Jim Green and Thelma Simon to have sustained water damage some time over the past five years with the exception of Room 391.) Floor Tile Hallway By Room 102 Hallway By Room 300 Hallway By Main Office Hallway By Coke Machine Outside Room 100 Interior Wall Room 201, Under Computer Counter, Near Reported Water Damage Mrs. Arnolds Room Room 100, Coke Machine on Opposite side of Wall Hallway Wall Between Coke Machines Outside Room 300 (All of the interior wall samples were collected at locations reported by Jim Green and Thelma Simon to have sustained water damage some time over the past five years.) Exterior Wall Room 100, Wood Paneling and Water Shield Board 25 Counselor’s and PE Coordinators Rooms, Wood Paneling and Water Shield Board Near East Entry, Wood Paneling and Water Shield Board (All of the exterior wall samples were collected at locations showing some indication of water damage. The tapelifts were placed on clean microscope slides and immersed in acetone for about two hours and then removed. The slides with the tapelifts were rinsed with clean acetone as they were removed from the immersion tank. The tapelifts were allowed to dry for ten minutes and then mounted using a synthetic resin (Eukitt). The completed mounts were analyzed using analytical light microscopy. The carpet samples were sectioned and examined under the stereoscopic microscope for any evidence of modification due to fungal or bacterial action as well as to characterize their cleanliness. Dust samples were collected by physically scrapping the folded carpet surface held above a collection sheet. The particles collected on the collection sheet were then examined microscopically and micro-chemically to establish their identity. The wall materials and tile sections were examined directly for any evidence of water damage or any associated evidence of local fungal activity. RESULTS One set of tapelift samples from rooms 100, 200, 300, the Library, and the Teacher's Lounge were sent to P&K Microbiological Services for particle analysis using their method P&K 115. One sample of the intake air particulate matter was also sent for particle analysis (P&K 115). Sections of all of the carpet samples were sent to P&K Microbiological Services for fungal and bacterial analysis using their method P&K 103. The carpet samples from Room 391 (where a water leak was detected), and room 203 along with a floor tile sample was sent for special Meso- and Thermophillic Actinomycetes testing; P&K 107. All of the samples listed above, with the exception of the tapelifts from rooms 201, 203, 303, 384, and the Computer Lab were analyzed by this laboratory. The results of those analyses are presented below. Tapelifts The tapelifts from Room 100 contained skin flakes, clothing fiber, paper fiber, natural minerals, lichen spores, pollens, soil, sawdust, charred wood, starch, cosmetics, phytoliths, shoe wear, aerosol droplets, glass fiber, food debris, insect parts, plant parts, spores, mycelium, blue spray paint spheres, perolite, pencil debris, weld spheres, cenospheres, bird feather barbules, and diatoms. Lichen spores are the most common airborne biological material in this sample. The dominant pollens are pine, cottonwood, cedar, and maple. Phytoliths are siliceous particles from decayed plants. The most common phytolith in these samples was from grass. The aerosol particle are predominantly from road spray of tires when the roads are wet. These particles are clusters of smaller particles typically held together by a droplet of water. When they land on a surface they form a tight cluster of particles. In this room these clusters often contain small tire wear particles, indicating the road as a source. The glass fiber was at a fairly low level and came from two sources, the ventilation system and the acoustic ceiling tile. The spores present were typical of an exterior environment though 26 Cladosporium was the most common single type. Cladosporium can grow indoors and has been associated with allergic type symptoms. The total spore population in this room did not indicate a fungal problem. The dust loading in this room indicates a significant exterior, unfiltered source of air. It also indicates a heavy track-in burden of particulate matter from the grass and soil outside the school. This track-in burden includes mycelium, rotted plant materials, and spores along with minerals, phytoliths, and other debris. The tapelifts from Room 200 contained skin flakes, clothing fiber, paper fiber, natural minerals, charred wood, soil, sawdust, toner, starch, pollens, phytoliths, shoe wear, glass fiber, food debris, insect parts, plant parts, spores, mycelium, blue spray paint spheres, cosmetics, tire wear, pencil debris, weld spheres, cenospheres, pink pearl erasure, lichen spores, bird feather barbules, and diatoms. The glass fiber was at a fairly low level and was predominantly from the ventilation system. The spores present were typical of an exterior environment though Cladosporium was again the most common single type. The total spore population in this room did not indicate a fungal problem. The dust loading in this room indicates a heavy track-in burden of particulate matter from the grass and soil outside the school. This track-in burden includes mycelium, rotted plant materials, and spores along with minerals, phytoliths, and other debris. The carpet in this room, as in many of the other rooms was spotted in many areas. One tapelift was taken of one of these spots. Sugar was present in the spot along with other food debris and adhering particles. The food debris evident in the carpets could account for the faint odor detected on entry into the unventilated room. The tapelifts from Room 300 contained skin flakes, clothing fiber, paper fiber, natural minerals, insect parts, plant parts, charred wood, soil, sawdust, toner, starch, pollens, lichen spores, phytoliths, shoe wear, mycelium, glass fiber, food debris, spores, cosmetics, tire wear, pencil debris, weld spheres, cenospheres, pink pearl erasure, bird feather barbules, and diatoms. Dermestid beetle larva hair was common among the insect parts in this set of samples. The Dermestid beetles are also known as carpet beetles. The type of carpet used in the classrooms at this school is not a source of food for these beetles but they will eat a variety of other foods. Dermestid beetles have been indicated as a potential cause of an allergic response. The dominant pollen in these samples was pine. The glass fiber was at a fairly low level and was predominantly from the acoustic ceiling tile. The spores present were typical of an exterior environment though Cladosporium was again the most common single type. The total spore population in this room did not indicate a fungal problem. The dust loading in this room indicates a heavy track-in burden of particulate matter from the soil outside the school. The track-in burden is higher in natural minerals in this room though track-in biologicals are still common. The tapelifts from the Library contained skin flakes, clothing fiber, paper fiber, natural minerals, insect parts, plant parts, charred wood, soil, sawdust, toner, starch, pollens, phytoliths, shoe wear, mycelium, bird feather barbules, glass fiber, spores, cosmetics, lichen spores, tire wear, pencil debris, weld spheres, cenospheres, pink pearl erasure, and diatoms. The dominant pollen in these samples was pine. The glass fiber was at a fairly low level and was predominantly from the acoustic ceiling tile. The spores 27 present were typical of an exterior environment though Cladosporium was again the most common single type. The total spore population in this room did not indicate a fungal problem. The dust loading in this room includes a significant track-in burden of particulate matter from the grass and soil outside the school. This track-in burden includes mycelium, rotted plant materials, and spores along with minerals, phytoliths, and other debris. The tapelifts from the Teacher's Lounge contained skin flakes, clothing fiber, paper fiber, natural minerals, food debris, charred wood, soil, sawdust, cosmetics, toner, insect parts, plant parts, starch, pollens, lichen spores, phytoliths, shoe wear, mycelium, ink, bird feather barbules, glass fiber, spores, tire wear, pencil debris, weld spheres, cenospheres, and diatoms. Dermestid beetle larva hair was common among the insect parts in this set of samples. The dominant pollen in these samples was pine. The glass fiber was at a fairly low level and was predominantly from the acoustic ceiling tile. The spores present were typical of an exterior environment though Cladosporium was again the most common single type. The total spore population in this room did not indicate a fungal problem. The dust loading in this room indicates a significant contribution of particulate matter from outside the school, both airborne and track-in. This track-in burden includes mycelium, rotted plant materials, and spores along with minerals, phytoliths, and other debris. Ventilation System The air intake samples contained natural minerals, charred wood, tire wear, pollens, spores, mycelium, insect parts, plant parts, phytoliths, cenospheres, and clothing fibers. The most common single fungal spore was Cladosporium, which suggests this spore may be high in the natural background in this area. There were a few particles in these samples, such as the clothing fiber, that suggest that the airflow is reversed at times. This is probably the result of natural drafting when the system is not in use. The supply air sample was dominated by classroom particles. This indicates that the make-up air volume is significantly less than the recycled volume. That is often the case and does not indicate a problem. There is nothing in the sample to indicate that the recycling loop is contributing anything detrimental. Carpet The carpet was a short pile synthetic fiber surface bonded to a solid, closed cell, plastic foam mat backing. The short pile facilitated cleaning and the solid closed cell backing mat acted as a barrier preventing moisture from accumulating in the carpet. Moisture can not penetrate the carpet from below as was well illustrated by the sample from Room 203. The carpet sample from Room 203 was collected next to the univent heater at the teacher's desk. The univent heater was leaking and the sub-flooring under the carpet at this location was saturated. The carpet itself was dry with the exception of a little moisture on the adhesive layer. There was no evidence of any alteration to the carpet as a result of the water exposure. The carpet in all rooms exhibited numerous stains. Many of these stains were food related and constituted a nutrient for bacteria and 28 fungus. No fungus was evident but a "vinegar" odor, suggesting bacterial action, was detected on entry to many of these rooms. The carpets were in need of at least spot cleaning. The particle contaminants on the carpet samples were all very much alike with the exception of the carpet from Room 300. All of the carpets with the exception of that in Room 300 were relatively clean outside the spotted areas. The main contaminants included natural minerals, carpet freshener (predominantly sodium bicarbonate), sawdust, insect parts, plant parts, plaster, and skin flakes. The carpet sample from Room 300 was collected in an area that was hard to reach with a vacuum cleaner. As a result it was heavily loaded with dust, about ten times more by volume than any of the other carpet samples. Natural minerals were the most common, followed by sawdust, wear metals, plaster, paint flakes, insect parts, plant parts, skin flakes, perolite, and carpet freshener. There was no evidence of water damage or staining under any of the carpet samples other than that in Room 203. The pattern of water damage on the sub-floor under the carpet in Room 203 was consistent with its source from the leaking univent piping. This type of carpet design is the easiest to maintain and forms a good moisture barrier. The short pile minimizes the potential for dust mites, is not a food for any insect, and eliminates the build-up of "deep" dust common to most carpet designs. The soiling of these carpets with food debris represents at least a potential health hazard. Spilled food and beverages or other "sticky" organic debris should be cleaned from the carpet with water and detergent. Ideally, eating spaces should not be carpeted. Floor Tile All of the floor tile samples were collected from locations where the tile had curled. The sample collected by the Coke Machine outside Room 100 had a number of pinheadsized fungal colonies. The floor in that area needs to be examined in more detail to determine the extent of the mold growth and to remediate the problem. None of the other floor tile samples exhibited any mold growth. Interior Wall None of the interior wall samples indicated any moisture problem inside the walls at these locations. That included the wall interior behind the Coke Machine outside Room 100 where fungal colonies had been found under the floor tile. Exterior Wall Two of the exterior walls examined were adjacent to concrete drip pads around drains. The concrete pad caused the water flowing from the roof to splash back upon the exterior paneling of the building. These concrete drip pads were located outside Room 100 and at the front of the school outside the PE Coordinator's Office. The paneling under the window outside the PE Coordinator's Office was water soaked and wood rot fungus was growing in the lower four inches of the panel. Water had soaked through the water barrier board and had stained the base plate inside the wall. 29 The exterior wall outside Room 100 showed some water checking but had not begun to decay. The water barrier board behind it was still in tact. The base plate inside the wall showed water staining as a result of water intrusion from the outside. The exterior wall at the east entry was exposed to water draining from the entry roof. Water draining down the roof ran onto the top of the lower eight foot by four foot panel at the edge of the roof. There was some checking of the outer-most first few plies of the plywood panel near the top of the panel. The back side of the ply board panel showed no indication of water streaking or water damage. The water barrier board did show some water streaking but it was not possible to determine when that had formed. The pattern consisted of several single streaks with no evidence of pooling until the water reached the bottom of the water barrier board. The concrete drip pads create a water problem for the exterior paneling. A splash guard should be added to the exterior wall at those locations to control the water exposure. The east entry roof should have some additional flashing added to reduce the amount of water flowing onto the exterior panels of the east side of the building. CONCLUSION The major sources of particles in these rooms are activities in the room, track-in debris, and the ventilation system. The overhead ventilation system is a minor source. The wall-mounted units may contribute much more to the total loading but that was not tested. The track-in debris is high in biological material including rotting leaves, various fungal mats, and humus, along with minerals and other debris. Food debris was a source of contamination in most of the rooms. Eating in the rooms is apparently common. The wall mounted heater units all collect exterior air near ground level. This may also contribute to the introduction of biologicals and other materials that are less common at more elevated sites. The chemicals in air fresheners and carpet fresheners can be an irritant for some individuals. These materials were in evidence in these rooms. There is no indication of a general fungal problem though there are a few specific areas of concern. The univent heater in Room 203 was leaking onto the floor. All of the univent systems should be inspected for leaks and repaired if any are found. An examination of the area around the leak in Room 203 did not indicate any fungal activity at this time. The floor tile in the hall outside room 100 is a problem. There is an active fungal colony under the floor tile in front of the Coke Machine. The flooring here should be removed and examined for any other growth and the Coke Machine should be checked for any release of moisture. Examination of the interior of the wall behind the Coke Machine did not indicate any fungal growth or water damage in the wall. There was no indication of fungal growth or water damage inside any of the interior walls inspected. The exterior walls exhibited some water damage and in one case, the paneling outside the PE Coordinator's Office, there was some wood rot fungus. There was no indication of a glass fiber problem. Glass fiber was present in all of the samples but at very low levels. Acoustic ceiling tile and ventilation duct liner were both 30 sources. At this time there is no evidence for a glass fiber problem in the areas tested. The type of acoustic ceiling tile used in these rooms can be a problem if disturbed. These tiles are easily damaged and can become a problem if they are manipulated. There is currently no evidence that they or the space above them is contributing significantly to the environment. Removing the tiles to clean them may cause more problems than it might solve. This is mentioned only because it had been overhear as a possible plan during the sampling. In some schools where this has been done the resulting glass fiber exposure was much worse than the original problem had been. The lack of a specific particulate irritant in these environments suggests that the cause of any building related health problem is either a total particle loading problem or a gas phase irritant not related to a particle source. A volumetric air sample collected when the rooms are occupied would give an indication of the total particle exposure. The rooms tend to be a bit cluttered, which inhibits thorough cleaning. There are ample sources of particles available for resuspension in these rooms that could significantly increase particle exposure if these surfaces were disturbed. The gas phase irritant could be as simple as a low room volume air exchange rate. Exchange of air with the crawlspace under some of the rooms could be a problem but there was no indication of a significant influx of spores that might be expected with that source. At this point a number of obvious potential causes of health problems have been ruled out for the rooms sampled. There are some clear action items that are listed below under RECOMMENDATIONS. The first three of these should be done regardless of any other action. The fourth item, the health assessment, is reportedly being completed now. Based on the outcome of the health assessment the final four items should be considered along with other more specific actions. Photodocumentation of the results presented here will be provided as a separate file. RECOMMENDATIONS 1. The extent of mold growth in the hallway outside Room 100 should be determined and remediated. The source of the moisture supporting the mold growth should be identified and controlled. 2. Splash guards and additional flashing should be installed to reduce the water exposure of exterior paneling. 3. A general thorough cleaning of the carpets and the rooms is needed. 4. A formal health assessment needs to be made in order to target specific potential agents in specific areas. 5. Airborne particle samples should be collected during a class session to quantify the total particle exposure. 6. Background airborne particle samples should be collected outside the building. 7. Carbon dioxide measurements should be taken in problem rooms toward the end of a class to assess the adequacy of the fresh air volume provided. 8. An attempt should be made to find better storage or to provide storage cabinets in order to reduce the clutter in the classrooms. 31 Thank you for this opportunity to be of service. If I can provide any further assistance please contact me. Signed: ________________________________________ E. R. Crutcher, Consultant 32 Appendix 3 P & K Microbiological Services Report June 28, 2002 33 34 35 36 37 38 Appendix 4 Results of the Student Health Assessment Washington State Department of Health July 13, 2002 39 Appendix 4 Washington State Department of Health Office of Epidemiology Summary of Data Collected on the Cle Elum – Roslyn High School Health Survey Prepared by Jim VanDerslice, PhD, Juliet VanEenwyk, PhD, and Harriet Ammann, PhD, DABT, Washington State Department of Health July 2002 For more information, contact Jim VanDerslice at (360) 236-3183 or jim.vanderslice@doh.wa.gov. 1. PURPOSE In response to requests from the Kittitas County Health District and the Cle Elum-Roslyn Indoor Air Quality Coalition, the Washington State Department of Health (WSDOH) conducted a survey of health symptoms among students at Cle Elum –Roslyn High School. The WSDOH stated that such a survey could provide information about the number and percent of students reporting symptoms and the places in the school where the symptoms occur. Additionally, the survey might be useful as a baseline to determine whether health improves after environmental remediation. The survey could not answer questions about what was causing the symptoms. 2. METHOD The survey was developed by the WSDOH in consultation with the Cle Elum – Roslyn Indoor Air Quality Coalition. WSDOH administered the survey on two Thursdays in May 2002. For comparison, WSDOH also administered the survey on two Thursdays in May at the Ellensburg High School. We used several different statistical tests to determine whether differences between Cle Elum and Ellensburg were statistically significant. While we do not report on the statistical significance in the data shown below, in general, differences were statistically significant. Additional detail on methods is available upon request. 40 3. SUMMARY OF MAJOR FINDING 3.1 Symptom onset in the previous three days In general, students at Cle Elum – Roslyn High School reported experiencing symptoms in the last three days two to three times more frequently than students in Ellensburg. Excluding those who also reported colds, the symptoms reported most often were abnormal tiredness (60% in Cle Elum versus 29% in Ellensburg), headache (59% versus 29%), and itchy eyes (44% versus 16%). The Cle Elum survey asked where the student was when the specific symptom began. About one-fifth of the time the student gave no specific location. When a location was provided, “when I entered the school” was the most common response. Classrooms in which at least 20 students reported symptom onset were scattered throughout the school and so symptom onset does not appear to cluster by wing or specific area. 3.2 Conditions with statewide comparison data 43% of students in Cle Elum reported depression in the last year compared to 22% in Ellensburg and 30% statewide. 20% of students in Cle Elum reported having ever been told by a doctor or other health care professional that they had asthma compared to 15% in Ellensburg and 21% statewide. 12% of students in Cle Elum reported having had an asthma attack or using asthma medication in the past year compared to 10% in Ellensburg and 15% statewide. 3.3 Other conditions 61% of students in Cle Elum reported menstrual irregularities in the last three months compared to 24% in Ellensburg. Differences persisted when adjusting for grade. There were no patterns in the specific type of irregularity. About twice as many students in Cle Elum reported unexplained bruising (24% in past three months) compared to Ellensburg (12%). 19% of students in Cle Elum reported lumps that developed since September and lasted for at least one month compared to 6% in Ellensburg. Fewer students in Cle Elum (35%) reported being told by a doctor or other health care professional they had allergies compared to Ellensburg (41%). 4 CONCLUSIONS In general, symptoms were reported two to three times more frequently in Cle Elum than in Ellensburg with several symptoms being reported by a relatively large proportion of the students. The most frequently reported site of onset was at the entrance to the school. A relatively large number of students reported the location of symptom onset in classrooms and areas scattered throughout the school, and these reports did not cluster by 41 wing or general area. These data can be used as baseline data to determine whether reports of symptoms decline after environmental remediation. 42 5. DETAIL The following section provides detailed information on most of the questions asked on the survey. The Washington State Department of Health can provide additional detail upon request. Who Responded? The completion rate measures the number of students who took the survey in relation to the number of students in the school. When completion rates are low, we are concerned that the data might not provide a good estimate of the true picture. For example, if a lot of students missed the survey because they were ill and not in school, we would likely underestimate the proportion of students experiencing different symptoms. For this type of survey, completion rates of 70% are generally considered adequate. Table 1 shows that completion rates were very high in both Cle Elum and Ellensburg (87% and 89% respectively) and consequently, if there are inaccuracies due to non-completion, they are most likely small. Table 1: Survey Response Cle Elum Enrollment* Completed surveys Completion rate Ellensburg 300 225 260 260/300=87% 201 201/225=89% 4 2 6 0 1 25 2 0 0 0 11 0 12 1 Refused Opt out by parents Absent, taking different test Absent, senior day/work out of school Absent, sick Absent, unknown Couldn’t code survey * This is the number of active students (i.e. not suspended) in the classes surveyed. For Cle Elum this also includes the students who were not enrolled in a history class. These students were surveyed on the makeup date. Table 2 shows that the proportion of female and male respondents was about the same in Cle Elum and Ellensburg. There were relatively more students in the older grades in Ellensburg than in Cle Elum. Because the frequency of some symptoms varied by grade, we analyzed each symptom reported in the last three days by grade. We did not find substantive differences in our conclusions when we analyzed these symptoms by grade and when we combined all grades. For this reason, we have reported only the analyses in which we combined all grades. Table 2: Gender and Grade of Respondents Cle Elum Ellensburg Gender Female Male 123 137 47% 52% 104 97 52% 48% Grade 9 10 11 12 72 52 74 62 28% 20% 28% 24% 12 22 86 81 6% 11% 43% 40% TOTAL 260 201 43 Summary of Reported Symptoms Table 3 summarizes the frequency of symptoms reported by students in Cle Elum and Ellensburg. Questions 4 – 16 asked about symptoms that started in school in the last three days (Monday through Wednesday). Some of these symptoms often occur when someone has a cold. We excluded those who reported the symptom and reported having a cold from Table 3. We did this because the most likely reason for these symptoms was that the student also had a cold. The results do not change substantively when we include students with colds. Questions 17 – 24 and question 27 asked about symptoms over different time periods. For these symptoms, a three-day period did not seem clinically meaningful. For the uestions on depression and asthma, we used questions from a statewide school-based health survey conducted in 1999 so that we had statewide comparison data. More information on this survey is available at http://www.doh.wa.gov/EHSPHL/Epidemiology/NICE/publications/YRBS99.PDF Students in Cle Elum reported most symptoms two to three times more frequently than students in Ellensburg. The most commonly reported symptoms are abnormal tiredness, headache and itchy eyes. We had not heard complaints about diarrhea and diarrhea is generally not associated with indoor air quality. We included it on the questionnaire as one way to assess whether students were over reporting symptoms (i.e., just answering “yes” to all symptoms without giving the question much thought). The fact that diarrhea was the least frequently reported symptom is an indication that the students were attempting to give thoughtful responses. Table 3: Summary of Reported Symptoms Cle Elum Ellensburg (n=260) (n=201) Symptom starting while at school during the last 3 days Trouble Thinking 112 43% 41 20% Dizziness 79 30% 26 13% Nausea 62 24% 19 9% Wheezing 63 24% 10 5% Rashes 32 12% 2 1% Nosebleeds 20 8% 9 4% Diarrhea 11 4% 3 1% Cold 86 33% 34 17% Symptom starting while at school during the last 3 days, excluding cold symptoms for those that had a cold (n=174) (n=167) Abnormal Tiredness 104 60% 48 29% Headache 102 59% 48 29% Itchy Eyes 77 44% 26 16% Stuffy Nose 66 38% 25 15% Cough 54 31% 8 5% Sore Throat 27 16% 6 4% Table 3: Summary of Reported Symptoms (continued) 44 Cle Elum Ellensburg (n=260) (n=201) Other symptoms Depression (2 straight weeks in past 12 months) 112 43% 44 22% Lumps under skin (1 month anytime since September) 48 19% 12 6% Ever diagnosed with asthma 52 20% 30 15% Asthma attack or taken asthma medication (past 12 months) 31 12% 19 10% Used inhaler (past month) 33 13% 13 6% Ever diagnosed with allergies 91 35% 83 41% Bruising for no apparent reason (the last 3 months) 62 24% 24 12% Menstrual irregularities (past 3 months) 75 (n=123) 61% 25 (n=104) 24% Table 4 shows the responses to question 26 that asked about symptoms in the last three days that began while the students were not in school. For five of the symptoms, an equal percent of students in Cle Elum and Ellensburg reported symptoms beginning outside of school. For other symptoms, some were reported more frequently in Cle Elum and some in Ellensburg. These findings may indicate that there were not large differences in the outdoor environments of Cle Elum and Ellensburg during the weeks the survey was administered that were related to the symptoms on the survey. For example, if pollen counts had been substantially higher in one location than in another, we would have expected that itchy eyes, stuffy nose, wheezing and cough to be consistently higher in one area than the other. Table 4:Summary of Reported Symptoms in Last 3 Days Developing Outside of School Symptom Cle Elum Ellensburg (n=260) (n=201) All students Trouble Thinking 34 13% 29 14% Dizziness 45 17% 25 12% Nausea 35 13% 25 12% Wheezing 33 13% 13 7% Rashes 15 6% 4 2% Diarrhea 14 6% 6 3% Excluding students with colds: (n=174) (n=167) Abnormal Tiredness 34 20% 37 22% Headache 60 34% 64 38% Itchy Eyes 30 17% 45 27% Stuffy Nose 49 28% 57 34% Cough 35 20% 12 7% Sore Throat 36 21% 33 20% 45 Number of symptoms reported Table 5 shows the number of symptoms beginning in school in the last 3 days reported by each student in answering questions 4 – 16. We wanted to assess the extent to which reports of these symptoms reflected many students reporting a few symptoms or a few students reporting many symptoms. About two-thirds of the students in Cle Elum reported four or fewer symptoms. In Table 5, those who only reported colds and cold symptoms are categorized as “none.” Table 5: Number of symptoms reported Number of symptoms reported Cle Elum number of students percent Ellensburg number of students percent None 33 13% 72 36% 1 43 17% 51 25% 2 38 15% 32 16% 3 37 14% 20 10% 4 18 7% 11 5% 5 31 12% 6 3% 6 20 8% 4 2% 7 12 5% 2 1% 8 11 4% 2 1% 9 6 2% 0 0% 10 8 3% 0 0% 11 3 1% 1 <1% Location in school where symptoms begin If students reported symptoms that started in school in the last three days, they were asked to describe where they were when the symptom started. Table 6 on the following page shows the locations reported by the students. If a student reported more than one symptom beginning in a particular location, that location was counted only once for that student. Thus, “number” in Table 6 is the number of students reporting symptom onset in a specific location. “Percent” shows that number as a proportion of the 260 respondents. Many students reported more than one location for each symptom. Some rooms were reported more frequently than others, but it is difficult to directly compare the number of reports because each room has a different number of students visiting it each day. For example, every student enters the school each day, but not every student spends time in each classroom. Without knowing how many students are in each room each day, we do not know what proportion of students in a classroom experience symptom onset in that room. Classrooms in which at least 20 students reported symptom onset were scattered throughout the school and so symptom onset does not appear to cluster by wing or specific area. 46 Table 6: Locations reported at least once by a student Location Number Percent ‘When I enter school’ 64 25% Miller 36 14% Basterrechea 35 13% Commons 33 13% Bender 32 12% Briggs 28 11% Gym 27 10% Nevills 25 10% Wilson 23 9% Other 21 8% Hill 20 8% Rusho 19 7% Hamel 16 6% Hutchins (Computer room) 14 5% Muzzall 14 5% Osborn 14 5% Norwood 13 5% Arnold 12 5% Aldrich 11 4% Cooke 11 4% Library 11 4% Gibson 9 3% O'Donnell, M 9 3% Randelman 7 3% Capps 6 2% Shop 6 2% O'Donnell, T 4 2% West wing 2 1% Music room 1 0% Senior wing 1 0% 47 Symptoms in the past month In addition to asking about symptoms starting in school in the last there days, questions 4 - 16 also asked about the frequency of the symptoms in the past month, when these symptoms usually went away and what types of medicine the student took for the symptom. The responses to these items are shown below. As with the reponses to the symptoms beginning in the past 3 days, reports of symptoms associated with colds are counted as “never” if the student also reported having colds. The order of the symptoms below is the same as the order in the survey. The pattern of more reporting of symptoms in Cle Elum than in Ellensburg that was evident for symptoms in the last three days was also apparent in the reports for the past month. As with symptoms occuring over the last three days, headache and abnormal tiredness were the symptoms most frequently reported over the past month. We urge members of the Cle Elum – Roslyn Indoor Air Quality Coalition to review the detailed information presented below to determine whether these results shed light on the questions the Coalition hopes to answer. We note that taking prescription medication is one indication that the student has seen a health care provider for the condition. Sore Throat (Those with colds counted as “never.”) Over the past month, how often have you had a sore throat that started in school? Cle Elum 1 Every school day 2 2 to 4 days per week 3 About 1 day per week 4 Rarely 5 Never 9 Don’t know No response When does this problem usually go away? 4 32 34 58 84 36 12 2% 12% 13% 22% 32% 14% 5% Cle Elum 1 Later during the school day 2 After school or during the night 3 Not until the weekend 4 Other (specify): _____________ 9 Don’t know Not Applicable or missing 17 63 19 7 18 136 13% 49% 15% 5% 14% Ellensburg 1 4 5 40 129 19 3 0% 2% 2% 20% 64% 9% 1% Ellensburg 8 18 4 14 5 152 16% 36% 8% 28% 10% In the last month, have you taken any prescription medication for a sore throat? Cle Elum 1 Yes, prescription medication 2 Yes, non-prescription (over the counter) medications 3 Yes, both prescription and non-prescription medications 4 No 9 Don’t know No response Ellensburg 10 4% 6 3% 35 13% 11 5% 8 190 6 11 3% 73% 2% 4% 5 174 2 3 2% 87% 1% 1% 48 Dry Cough (Those with colds counted as “never.”) Over the past month, how often have you had a dry cough that started in school? Cle Elum 1 Every school day 2 2 to 4 days per week 3 About 1 day per week 4 Rarely 5 Never 9 Don’t know No response 20 25 31 31 106 35 12 8% 10% 12% 12% 41% 13% 5% Ellensburg 2 5 2 28 143 14 6 1% 2% 1% 14% 71% 7% 3% When does this problem usually go away? Cle Elum 1 Later during the school day 2 After school or during the night 3 Not until the weekend 4 Other (specify): _____________ 9 Don’t know Not Applicable or missing 18 37 21 12 17 155 17% 35% 20% 11% 16% Ellensburg 8 8 2 8 9 165 22% 22% 5% 22% 24% In the last month, have you taken any prescription medication for dry cough? Cle Elum 1 Yes, prescription medication 2 Yes, non-prescription (over the counter) medications 3 Yes, both prescription and non-prescription medications 4 No 9 Don’t know No response Ellensburg 5 2% 5 2% 26 10% 3 1% 6 200 10 13 2% 77% 4% 5% 0 175 6 11 0% 87% 3% 5% Stuffy Nose (Those with colds counted as “never.”) Over the past month, how often have you had a stuffy nose that started in school? Cle Elum 1 Every school day 2 2 to 4 days per week 3 About 1 day per week 4 Rarely 5 Never 9 Don’t know No response 36 52 30 42 64 30 6 14% 20% 12% 16% 25% 12% 2% 49 Ellensburg 3 13 8 33 117 22 4 1% 6% 4% 16% 58% 11% 2% Stuffy Nose (continued) (Those with colds counted as “never.”) When does this problem usually go away? Cle Elum 1 Later during the school day 2 After school or during the night 3 Not until the weekend 4 Other (specify): _____________ 9 Don’t know Not Applicable or missing 20 75 20 20 18 107 13% 47% 13% 13% 11% Ellensburg 13 11 3 12 19 142 23% 19% 5% 21% 33% In the last month, have you taken any prescription medication for a stuffy nose? Cle Elum 1 Yes, prescription medication 2 Yes, non-prescription (over the counter) medications 3 Yes, both prescription and non-prescription medications 4 No 9 Don’t know No response Ellensburg 7 3% 11 5% 38 15% 12 6% 4 198 7 6 2% 76% 3% 2% 2 168 3 4 1% 84% 1% 2% Colds Over the past month, how often have you had colds that started in school? Cle Elum 1 Every school day 2 2 to 4 days per week 3 About 1 day per week 4 Rarely 5 Never 9 Don’t know No response 19 39 25 76 72 25 4 7% 15% 10% 29% 28% 10% 2% Ellensburg 7 10 8 61 97 13 5 3% 5% 4% 30% 48% 6% 2% In the last month, have you taken any prescription medication for a cold? Cle Elum 1 Yes, prescription medication 2 Yes, non-prescription (over the counter) medications 3 Yes, both prescription and non-prescription medications 4 No 9 Don’t know No response Ellensburg 8 3% 7 3% 56 22% 21 10% 9 175 5 7 3% 67% 2% 3% 3 163 2 5 1% 81% 1% 2% 50 Itchy Eyes (Those with colds counted as “never.”) Over the past month, how often have you had itchy eyes that started in school? Cle Elum 1 Every school day 2 2 to 4 days per week 3 About 1 day per week 4 Rarely 5 Never 9 Don’t know No response 37 47 27 37 86 16 10 14% 18% 10% 14% 33% 6% 4% Ellensburg 2 10 9 23 141 10 4 1% 5% 4% 11% 70% 5% 2% When does this problem usually go away? Cle Elum 1 Later during the school day 2 After school or during the night 3 Not until the weekend 4 Other (specify): _____________ 9 Don’t know Not Applicable or missing 27 69 11 14 20 119 18% 47% 7% 9% 14% Ellensburg 11 11 2 7 8 160 25% 25% 5% 16% 18% In the last month, have you taken any prescription medication for itchy eyes? Cle Elum 1 Yes, prescription medication 2 Yes, non-prescription (over the counter) medications 3 Yes, both prescription and non-prescription medications 4 No 9 Don’t know No response Ellensburg 5 2% 7 3% 30 12% 5 2% 1 209 4 11 0% 80% 2% 4% 1 178 4 4 0% 89% 2% 2% Headache (Those with colds counted as “never.”) Over the past month, how often have you had a headache that started in school? Cle Elum 1 Every school day 2 2 to 4 days per week 3 About 1 day per week 4 Rarely 5 Never 9 Don’t know No response 61 65 43 40 39 11 1 23% 25% 17% 15% 15% 4% 0% 51 Ellensburg 6 15 26 67 75 7 4 3% 7% 13% 33% 37% 3% 2% Headache (continued) (Those with colds counted as “never.”) When does this problem usually go away? Cle Elum 1 Later during the school day 2 After school or during the night 3 Not until the weekend 4 Other (specify): _____________ 9 Don’t know Not Applicable or missing 39 113 16 8 11 73 19% 54% 8% 4% 5% In the last month, have you taken any prescription medication for a headache? Cle Elum 1 Yes, prescription medication 2 Yes, non-prescription (over the counter) medications 3 Yes, both prescription and non-prescription medications 4 No 9 Don’t know No response Ellensburg 32 39 1 20 11 97 28% 34% 1% 18% 10% Ellensburg 7 3% 4 2% 111 43% 52 26% 6 124 8 4 2% 48% 3% 2% 3 133 3 5 1% 66% 1% 2% Nausea Over the past month, how often have you had nausea that started in school? Cle Elum 1 Every school day 2 2 to 4 days per week 3 About 1 day per week 4 Rarely 5 Never 9 Don’t know No response 10 18 27 47 126 22 10 4% 7% 10% 18% 48% 8% 4% Ellensburg 1 1 8 32 138 13 4 0% 0% 4% 16% 69% 6% 2% When does this problem usually go away? Cle Elum 1 Later during the school day 2 After school or during the night 3 Not until the weekend 4 Other (specify): _____________ 9 Don’t know Not Applicable or missing 25 40 8 11 16 160 25% 39% 8% 11% 16% 52 Ellensburg 12 10 1 6 10 158 29% 24% 2% 14% 24% Nausea (continued) In the last month, have you taken any prescription medication for nausea? Cle Elum 1 Yes, prescription medication 2 Yes, non-prescription (over the counter) medications 3 Yes, both prescription and non-prescription medications 4 No 9 Don’t know No response Ellensburg 4 2% 2 1% 15 6% 4 2% 0 218 11 12 0% 84% 4% 5% 1 183 3 4 0% 91% 1% 2% Diarrhea Over the past month, how often have you had diarrhea that started in school? Cle Elum 1 Every school day 2 2 to 4 days per week 3 About 1 day per week 4 Rarely 5 Never 9 Don’t know No response 6 2 4 15 205 14 14 2% 1% 2% 6% 79% 5% 5% Ellensburg 0 0 0 7 179 8 5 0% 0% 0% 3% 89% 4% 2% When does this problem usually go away? Cle Elum 1 Later during the school day 2 After school or during the night 3 Not until the weekend 4 Other (specify): _____________ 9 Don’t know Not Applicable or missing 3 9 1 8 13 226 11% 33% 4% 30% 48% Ellensburg 2 2 1 0 7 187 29% 29% 14% 0% 100% In the last month, have you taken any prescription medication for diarrhea? Cle Elum 1 Yes, prescription medication 2 Yes, non-prescription (over the counter) medications 3 Yes, both prescription and non-prescription medications 4 No 9 Don’t know No response Ellensburg 2 1% 0 0% 4 2% 1 0% 0 234 5 15 0% 90% 2% 6% 0 190 2 6 0% 95% 1% 3% 53 Wheezing or Other Difficulty Breathing Over the past month, how often have you had wheezing or other difficulty breathing that started in school? Cle Elum 1 Every school day 2 2 to 4 days per week 3 About 1 day per week 4 Rarely 5 Never 9 Don’t know No response 25 21 25 20 143 17 8 10% 8% 10% 8% 55% 7% 3% Ellensburg 3 0 3 8 168 14 3 1% 0% 1% 4% 84% 7% 1% When does this problem usually go away? Cle Elum 1 Later during the school day 2 After school or during the night 3 Not until the weekend 4 Other (specify): _____________ 9 Don’t know Not Applicable or missing 17 37 10 10 15 170 19% 41% 11% 11% 16% Ellensburg 4 2 0 5 5 183 29% 14% 0% 36% 36% In the last month, have you taken any prescription medication for wheezing or other difficulty breathing? Cle Elum 1 Yes, prescription medication 2 Yes, non-prescription (over the counter) medications 3 Yes, both prescription and non-prescription medications 4 No 9 Don’t know No response Ellensburg 16 6% 7 3% 9 3% 0 0% 2 216 8 8 1% 83% 3% 3% 0 184 3 5 0% 92% 1% 2% Abnormal Tiredness (Those with colds counted as “never.”) Over the past month, how often have you had episodes of feeling very tired at school even after having a good night’s sleep? Cle Elum 1 Every school day 2 2 to 4 days per week 3 About 1 day per week 4 Rarely 5 Never 9 Don’t know No response 76 69 30 16 56 7 5 29% 27% 12% 6% 22% 3% 2% 54 Ellensburg 9 33 19 30 99 8 3 4% 16% 9% 15% 49% 4% 1% Abnormal Tiredness (continued) (Those with colds counted as “never.”) When does this problem usually go away? Cle Elum Ellensburg 1 Later during the school day 26 14% 10 2 After school or during the night 77 40% 22 3 Not until the weekend 45 24% 12 4 Other (specify): _____________ 18 9% 23 9 Don’t know 12 6% 11 Not Applicable or missing 81 123 In the last month, have you taken any prescription medication for abnormal tiredness? Cle Elum 1 Yes, prescription medication 2 Yes, non-prescription (over the counter) medications 3 Yes, both prescription and non-prescription medications 4 No 9 Don’t know No response 11% 24% 13% 25% 12% Ellensburg 2 1% 0 0% 15 6% 4 2% 1 231 5 5 0% 89% 2% 2% 0 190 4 3 0% 95% 2% 1% Trouble Thinking Over the past month, how often have you had a time when you had trouble thinking that started in school? Cle Elum 1 Every school day 2 2 to 4 days per week 3 About 1 day per week 4 Rarely 5 Never 9 Don’t know No response 44 42 27 25 95 18 8 17% 16% 10% 10% 37% 7% 3% Ellensburg 14 9 14 19 126 14 4 7% 4% 7% 9% 63% 7% 2% When does this problem usually go away? Cle Elum 1 Later during the school day 2 After school or during the night 3 Not until the weekend 4 Other (specify): _____________ 9 Don’t know Not Applicable or missing 30 41 19 6 24 139 22% 30% 14% 4% 17% 55 Ellensburg 10 12 3 5 18 152 18% 21% 5% 9% 32% Trouble Thinking (continued) In the last month, have you taken any prescription medication for trouble thinking? Cle Elum 1 Yes, prescription medication 2 Yes, non-prescription (over the counter) medications 3 Yes, both prescription and non-prescription medications 4 No 9 Don’t know No response Ellensburg 2 1% 2 1% 7 3% 1 0% 0 236 6 8 0% 91% 2% 3% 0 188 5 4 0% 94% 2% 2% Dizziness Over the past month, how often have you had a time when you felt dizzy during school? Cle Elum 1 Every school day 2 2 to 4 days per week 3 About 1 day per week 4 Rarely 5 Never 9 Don’t know No response 15 30 33 42 118 14 7 6% 12% 13% 16% 45% 5% 3% Ellensburg 1 6 6 28 143 11 4 0% 3% 3% 14% 71% 5% 2% When does this problem usually go away? Cle Elum 1 Later during the school day 2 After school or during the night 3 Not until the weekend 4 Other (specify): _____________ 9 Don’t know Not Applicable or missing 45 41 3 10 19 141 38% 34% 3% 8% 16% In the last month, have you taken any prescription medication for dizziness? Cle Elum 1 Yes, prescription medication 2 Yes, non-prescription (over the counter) medications 3 Yes, both prescription and non-prescription medications 4 No 9 Don’t know No response Ellensburg 9 11 0 9 8 162 22% 27% 0% 22% 20% Ellensburg 0 0% 1 0% 9 3% 0 0% 0 236 5 9 0% 91% 2% 3% 0 190 4 4 0% 95% 2% 2% 56 Rashes Over the past month, how often have you had a rash that started in school? Cle Elum 1 Every school day 2 2 to 4 days per week 3 About 1 day per week 4 Rarely 5 Never 9 Don’t know No response 11 8 4 16 192 18 10 4% 3% 2% 6% 74% 7% 4% Ellensburg 0 0 2 2 184 8 4 0% 0% 1% 1% 92% 4% 2% When does this problem usually go away? Cle Elum 1 Later during the school day 2 After school or during the night 3 Not until the weekend 4 Other (specify): _____________ 9 Don’t know Not Applicable or missing 3 3 7 18 17 211 8% 8% 18% 46% 44% Ellensburg 0 2 0 5 5 188 0% 50% 0% 125% 125% In the last month, have you taken any prescription medication for a rash? Cle Elum 1 Yes, prescription medication 2 Yes, non-prescription (over the counter) medications 3 Yes, both prescription and non-prescription medications 4 No 9 Don’t know No response Ellensburg 5 2% 0 0% 8 3% 3 1% 1 232 4 9 0% 89% 2% 3% 0 187 3 7 0% 93% 1% 3% Summary of Additional Questions Other symptoms or health problems Question 25 asked students to report other health symptoms that were not included on the questionnaire. Not counting reports of menstrual irregularities that were asked about in question 27, 49 students in Cle Elum reported at least one other symptom, but eight of these students only reported symptoms that had been asked about previously. Eight students reported eye problems, such as watery eyes, burning or irritation. Five students reported body aches such as muscle, joint or back aches, or general soreness; five reported emotional problems, such as extreme anger or irritability; four reported skin problems, such as itching or dry skin; and four reported stomach aches or abdominal pain. Other symptoms were reported three or fewer times. 57 Menstrual irregularities There were no patterns in the students’ descriptions of their menstrual irregularities. In Cle Elum, approximately 30% of the students did not answer this question and another 23% stated that their menses were irregular, but did not provide specifics. Almost 22% indicated that they did not menstruate often enough and about 14% indicated they menstruated too frequently. Change in symptoms in the last 2 months Question 28 asked whether symptoms had gotten better or worse in the past 2 months. Approximately 50 students clearly stated that their symptoms had gotten worse, while about 15 clearly stated that their symptoms had gotten better. Other students reported that their symptoms did not change, left the question blank, stated that it did not apply to them or provided a comment that did not clearly indicate whether symptoms were better or worse. Cause of symptoms Question 29 asked whether the student knew the cause of their symptoms. We asked this question, because we thought it might be informative to exclude those with known causes from the analyses. Very few students reported known causes and so we did not analyze the data excluding these students from the analyses. Nine students reported reasons for headaches, including issues related to wearing glasses, not eating, stress and lighting and eight students reported respiratory symptoms being caused by colds, asthma, or allergies. Other comments Question 30 asked for additional comments. Most students did not give additional comments. Of the 44 students who made additional comments, most of them referred to the need to fix the school or gave additional detail on symptoms. Fewer than 10 students commented that they were fine, they thought the school was fine, they thought the survey was a waste of class time, or similar comments. 58 Appendix 5 Cle Elum-Roslyn School District Proposed 3 - Phase Plan for Health & Safety June 2002 59 60 61 62 63 64 65 Appendices 6a & 6b KJM Construction Management Services 6a – Remediation Work Documentation 6b – Timeline for Remediation Work 66 FINAL 10/1/2002 - Construction Management Status Report Cle Elum/Roslyn School District High School Modifications Situation The Cle Elum-Roslyn High School remediation of building deficiencies is a threephase plan to address health concerns and implement a long-term indoor air quality management plan. Goals Related To The Construction Management Portion Of The Plan 1. Completion and validation of indoor air quality remediation actions that satisfy community health concerns. 2. The return of community focus on the quality of education and management of indoor air quality issues as an integral function of facility maintenance operations. Key Messages A safe and healthy environment is essential for quality education. A community partnership provides the best solutions. Everyone contributes to keep a building healthy. Purpose The purpose of the high school remediation plan is to bring the building’s mechanical systems and structural components to the highest possible levels of operating efficiency and structural integrity within budget parameters. This plan addresses the aspects of the building that contribute to creating and maintaining a safe and healthy environment for students and staff. Validation and Verification The progress of this plan is to be reviewed weekly by the school district and the coalition. The coalition will confirm the successful completion of the phases of this plan. The reviews may be less frequent if appropriate. Status Consistent With the Situation, Goals, Key Messages, Purpose, Validation and Verification 67 Phase 1 - Implement Recommended Actions - This phase implements the recommendations from the IAQ assessment by Richard Prill on April 15, 2002 along with the associated testing recommendations from E.R. Crutcher that followed the Rich Prill assessment. Action Items Process began July 18th, 2002. Clint Marsh, KJM Associates, has been contracted as the remediation project consultant. Tom Swenson, maintenance supervisor, is the remediation manager supervising the plan. Telephone conversation with James Green on July 23rd, 2002. July 24th, 2002 - Initial team meeting. Received the following reports: - Rich Prill Summary of IAQ Walk-Around Findings Report - Dated 4/15/2002. - Microlab Northwest – Report 632-02. - P&K Microbiology Services, Inc. – P&K Report No.:020610-029. July 25th, 2002 - Tour of building with Pete Keithly of Keithly Welsh and Tom Swenson. Received the following reports: - Final Report for Health Assessment from Kittitas County Health Department. - Public Information Request from James Green for M&O documents on July, 22nd, 2002. - District Response to PIR from Evelyn Nelson on July 24th, 2002. - Copy of James Green Summary Report of Rich Prill Walk-thru from James Green. July 29th, 2002 – Read all reports and edited into a checklist. Made the following contacts: - Merle Kirkley – Beresford Company – Soft and hard-surfaces floor-coverings. - Nancy Goodloe – Requesting Rich Prill “Power Point” Addendum for 4/15/02 Assessment. - Kit Burns – BLRB Architects – Confirmation of “splash/ice guard design.” - Tim Iwasaki – ATS Automation – Soliciting retro-commissioning assistance and information on the Aircuity web-based air monitoring system. - Dennis Turnbull – Collins & Aikman soft vinyl back floor covering representative July 31st, 2002 – Met with Tim Iwasaki & Tom Swenson. Received Aircuity demonstration. Established control requirements for digital display sensors and ventilation controls. Reviewed preliminary summary work checklist and associated work schedule with Tom. - Met with Jim Green of Clean Air Now. August 1st, 2002 – Edited work checklist incorporating Cructher and Prill recommendations. Generated Clean Air Now work request list from Jim Green meeting. Made the following contacts: - Pete Keithly – Keithly Welsh Associates – Received retro-commissioning proposal for SD. - Nancy Goodloe – Kittitas County Health – Requested & received CAN Three Page List. Sent work checklist, work schedule, and CAN work request list by e-mail. - Art Busch – Washington Education Association – Brief overall update. Sent work checklist, work schedule, and CAN work request list by e-mail. 68 - Joe Jimenez – Jimenez & Associates – Brief overall update. Sent work checklist, work schedule, and CAN work request list by e-mail. - Rich Ellis – Washington State Health Advisor – Brief overall update. - Dennis Turnbull & Merle Kirkley – Collins & Aikman/Beresford – Confirmed public meeting with Dennis Turnbull, Regional Sales Manager, Tom Ellis, General Manager Schools Program, and Merle Kirkley, Beresford Company Representative, at the high school on August 8th, 2002 @ 9:00 a.m. August 2nd, 2002 – Edited CAN Three Page List into CAN work request list. Made the following contacts: - Tim Iwasaki – ATS Automation – Confirmation of SD proposal for ventilation controls and sample Aircuity reports for distribution/discussion among team members. - Tim Holmes – ATS Automation – Confirmation of SD proposal for Aircuity demonstration. August 5th, 2002 – Meeting with Nancy Goodloe @ Kittitas County Health in Ellensburg and presented overall status update. - Met with Jack Stoner @ Northern Kittitas County TRIBUNE and presented upcoming key events and activities in process. - Received service support, controls, CO2 monitoring device installation, and computer relocation quote from ATS Automation. - Received Aircuity monitoring test and rent versus buy proposal from ATS Automation. - Received SAMPLE Aircuity Indoor Air Quality Evaluation Report. August 6th, 2002 – Made the following contacts: - Received “3 Remaining Issues” power-point slides that cover discussions that were not previously in the power point presentation to the Coalition (Jim Green request). These have been added to the work checklist. - Contacted Rich Prill. Brief overall update. Discussed his future scheduling availability. He is unable to do a follow-up on the initial assessment until approximately September 15th. He will review information and reports sent him from now until then. - Contacted Russ Crutcher. Brief overall update. Requested the last 3 slides in his power-point presentation made to the Coalition (Jim Green request). They will be incorporated as needed into the work checklist. - Sent e-mail request to ATS & Keithly Welsh for schedule queuing of Cle Elum-Roslyn High School for controls, sensor, and commissioning work. - Made copies of all materials for August 7th, 2002 meeting. August 7th, 2002 – Met with Mike Snow, Tom Swenson, Joe Jimenez, and Evelyn Nelson at the Cle Elum-Roslyn High School. - Formal approval of the following for District contracting and payment requested & approved: o ATS Automation – Controls & Sensor Proposal #1699521 - $5,684+WSST. o Keithly Welsh Associates, Inc. - Commissioning Proposal - $6,080. - Requested copy of signed KJM contract for corporate office files. - Handed out and went over Work Schedule and Phase I Checklist. - Confirmed Phase I Checklist work that is underway. o Materials and parts required for project Work have been ordered. 69 o Electrical contractor scheduled for on-call work when needed. o ATS Automation has scheduled their work for August 19th, 2002. August 8th, 2002 – Attended and participated in the following meetings: - 7:00 a.m. – Collins/Aikman Inc. & Beresford Company – Met with Tom Ellis (C&A Factory-Dalton, Georgia), Dennis Turnbull, Merle Kirkley, and Joe Jimenez. - 8:00 a.m. – Cle Elum-Roslyn School District, Collins/Aikman Inc. & Beresford Company - Met with Evelyn Nelson, Mike Snow, Tom Swenson, Tom Ellis, Dennis Turnbull, Merle Kirkley, and Joe Jimenez. - 9:00 a.m. - Public Meeting on soft floorcovering @ high school library. C&A/Beresford presented features/benefits information about the floorcovering. Question/answer exchange ensued. Walked building discussing restorative cleaning plan. Unanimous confirmation among those in attendance to proceed with restorative cleaning. Thelma Simon came after the presentation, question/answer period, and building walk-thru and expressed concern over the public decision to proceed with restorative cleaning. NOTE: Collins & Aikman is donating a floorcovering agitator to the school district. This will provide assistance with mechanized spot removal increasing quality and decreasing labor. - 2:30 p.m. – Met Lisa Messmer, Clean Air Now, doing a walk-thru of the building. She had been requested to attend the floorcovering presentation by Jim Green. Jim had not been told a specific time for the presentation, however, I had told him that it would be held “in the morning sometime, at the school, in the library.” - Confirmed Additional Phase I Checklist work that is underway. o Scheduled Keithly Welsh Associates for building commissioning August 26th, 2002. o Merle Kirkley contacted Servicemasters Inc. for floorcovering restorative cleaningschedule pending – Tentative schedule August 12th thru august 16th, 2002. o Tom Swenson has staff assigned appropriately for Work in process. o Scheduled coke machine floor exploratory for August 14th, 2002. Repair pending coalition being present for review prior to closure. o Schedule for exterior wall remediation and exterior splash/ice guard installation pending week of August 26th, 2002. Installation completion pending Coalition review prior to closure. th August 9 , 2002 – Updated status report, schedule, and Phase I Checklist. o Sent electronic copies to: Nancy Goodloe for Board of Health meeting. Rich Prill - ongoing update. Evelyn Nelson, Mike Snow, Tom Swenson, Joe Jimenez - ongoing update. th August 14 , 2002 – Attended the following meetings: o 9:30 - Tom Swenson – Tour of Work in process. Coke machine floor exploratory began. Repair pending Coalition review prior to closure. Evelyn Swenson & Mike Snow @ Cle Elum-Roslyn High School. • OSPI Emergency Funds confirmation of $55,000. 70 • o o Responded with confirmation of additional Work scope/within budget. Contacted Pete Keithly for Engineering & System Upgrade Services: • AHU#14-Damper & linkage confirmation & removal. • Ductwork as-built modification and upgrade. • Exhaust fans 15/16/17-Design confirmation and repair. • Ventilation “popcorn smell” in room 104. Larry Matlin of Servicemaster-Restorative cleaning process update. Follow-up with Doug Paulichug-Local Carpenters Union-Per Jim Green request. Carpenters not needed. 5:00 – Jim Green @ Pioneer Café. 6:00 – Coalition @ Comtronics Systems Inc. th August 15 , 2002 – Pete Keithly conducted field visit on requested items. August 19th, 2002 – Attended the following meetings: o 8:00 – Teachers day/question and answer Cle Elum-Roslyn H.S. Tour of Work status to date. Limited Work activity due to teacher preparation. Review schedule/budget/overall status with Tom Swenson. o 10:30 – Dennis Turnbull/C&A/question and answer-floor covering. o 12:30 – Mike Snow, Tom Swenson, Joe Jimenez, and Rich Ellis. o 2:30 – Dennis Turnbull, Joe Jimenez, and Rich Ellis. th August 20 , 2002 – Updated status report: o Confirmed Pete Keithly for August 27th & 28th Commissioning dates. o Confirmed Russ Crutcher for August 30th, Re-testing date. o Confirmed remaining schedule of Work activities with Tom Swenson. o Confirmed and revised Remediation Budget. Sent copies to Evelyn Nelson, Mike Snow, Tom Swenson, and Joe Jimenez. o Follow-up e-mail to Art Busch for Coalition monitors names and phone numbers, in addition to Jim Green per Art’s request last week. o Left message with Glenna Green for James Green that we are starting the remediation of the Coke machine floor and the exterior walls 8/22/2002. o Requested and confirmed Health Department participation for Coke machine floor replacement and for exterior wall inspection prior to close. Rich Ellis will be on site at 8:00 a.m., Friday, August 23rd, 2002. o Sent request to Dennis Randolph (membership) and Ken Price (certification) for WAMOA membership and certification applications for Tom Swenson. August 21st, 2002 – Received necessary Coalition contact information from Art Busch and Joe Jimenez. Made the following contacts requesting their attendance at the remediation of the Coke machine floor and the exterior walls beginning 8:00 a.m., Thursday, 8/22/2002: o Left voice message at Lisa Mesmer’s work. 71 o Left voice message at Thelma Simon’s work. Left message with Thelma’s husband Keith. o Left voice message at Jennifer Betlach’s home. Left voice message on Jennifer’s cell phone as well. o Received call from James Green confirming that he will be in attendance at 8:00 a.m. Friday morning prior to covering the openings. nd August 22 – Attended the following activities: o Floor under Coke machine and appropriate exterior walls were opened for inspection and left open for others to inspect. The following people were present: Jennifer Betlach Thelma Simon Keith Simon Lisa Messmer Tom Swenson Clint Marsh o Per Art Busch’s request I left voice messages for Mike Muzzal and Tom Wilson. Explained the Work in progress and that we were taking pictures with the Health Department @ 8:00 a.m., Friday, August 23rd, 2002. o Contacted Larry Matlin of ServiceMaster to let him know that Coalition members were concerned about cleaners being used on soft floor covering. rd August 23 – Attended the following activities: o Toured building and took pictures of the floor under the Coke machine and The exterior walls that were opened for inspection. The following people were present: James Green Joanie Minkee Nan Blaum Tom Swenson Rich Ellis Clint Marsh o Coke machine floor and exterior walls were left open for others to inspect. o Coke machine floor and exterior walls will be repaired Monday, August, 26th, 2002. o Splash/ice guards will be installed Tuesday, August, 27th, 2002. o Brought crawlspace ventilation system online. Phase I – Validation and Verification has begun - District remediation plan manager and contracted project manager inspect completed tasks. o Toured crawlspace to determine impact of crawlspace ventilation system. The following people were present: Tom Swenson 72 Mark & Tom-Maintenance/Custodial Staff Frank-Heating Ventilation Staff Brent Walley-ATS Installer Clint Marsh o Received MSDS Sheets for cleaners used in soft floor covering restorative cleaning process from Larry Matlin of ServiceMaster: SYON-5-Collins & Aikman soft floor covering cleaner. FiberFresh Water Solv-A restorative cleaning solvent for spot removal. SalvOII with Citrus-A restorative cleaning solvent for spot removal. Larry Matlin would like to answer any questions about these products. o Updated project status report. o Updated Work checklist. o Project remains on schedule. o Sent status reports and updated Work checklist to Nancy Goodloe, Rich Prill, Mike Snow, Tom Swenson, Evelyn Nelson, Joe Jimenez by e-mail. th August 27 , 2002 – Attended the following activities: o Tour of Work status to date. o Building commissioning with Keithly Welsh Associates. o Exterior wall repair and reconstruction. o Coke machine floor repair. o Met with Farley Walker, Business Manager, and went over Work budget. Phase II – Validation and Verification has begun – District remediation plan manager and contracted project manager inspect completed tasks. Facility recommissioning contractor confirms building systems are operating as designed and specified by manufacturer and appropriate IAQ standards. August 28th, 2002 – Will attend the following activities: o Building commissioning with Keithly Welsh Associates. o Status meeting with Mike Snow and Tom Swenson. o Exterior wall repair and reconstruction. o Met with John Wolpers, Kittitas County Environmental Health Director. Reviewed project report, Work checklist, schedule, school district remediation plan. Gave him copies of each. o Met with Rich Ellis, State of Washington Environmental Health Inspector. o Inundated with attorneys, construction managers, and industrial hygienist performing discovery activities for upcoming litigation. Work halted. Contacted public relations consultant for Superintendent notification. o 4:30 – Status update with James Green. o 6:00 – Status meeting with Coalition. August 29th, 2002 – Received Retro-Commissioning Issues Report from KWA. o Pete Keithly (KWA) and Brent Walley (ATS) working to rectify issues identified in KWA report dated August 28th, 2002. o Worked with Joe Jimenez to produce building floor plan location and codification of remediation activities for public information distribution. 73 Associated signage is being prepared by Joe Jimenez for identification of remediation activities within the building. o Copies of Keithly Welsh reports sent with August 29th, 2002 status report. KWA field visit report dated August 16th, 2002 (site visit 8/15). KWA retro-commissioning issues report dated August 28th, 2002. August 30th, 2002 – Phase I – Validation and Verification continues – E.R. Crutcher to conduct reassessments and inspections of implemented recommendations. Specific testing for specific reasons conducted. Phase III – Evaluation has begun - Starts before the 2002-2003 school year begins and continues until a long-term Indoor Air Quality Management Plan is implemented. Preliminary verifications will be conducted before school resumes in September 2002. o 9:00 – Met with the following people at the Cle Elum-Roslyn HS for re-testing: Russ & Pat Crutcher Thelma Simon Mike Snow Tom Swenson Clint Marsh • The Following was re-tested with tape lifts & air samples: • Classrooms 100, 200, & 203. • Home Economics. • Library. • Outside background air sample. • Spot by AHU#14 (Actually AHU#10) in mechanical space above woodshop. Requested by Nancy Goodloe. o Splash/ice guard installation began. o Supplied Tom Swenson with WAMOA (Washington Association of Maintenance and Operations Administrator) membership, certification, and conference registration information. September 3rd, 2002 - Phase II – Validation and Verification continues - District remediation plan manager and contracted project manager inspect completed tasks with health inspectors and school district nurse : o 10:00 a.m. – Meeting with Tom Swenson while health inspectors met with school district nurse: Mike Snow – CERSD Principal. Rose Murdock – CERSD Nurse. Rich Ellis – State Environmental Health Inspector. John Wolpers – Kittitas County Environmental Health Director. o 11:30 – Larry Matlin – ServiceMaster/floor-covering restorative cleaning update. o 12:30 p.m. – Health inspection and tour of facility: Rose Murdock – CERSD Nurse. Tim Hardin – State Environmental Health Inspector. Rich Ellis – State Environmental Health Inspector. John Wolpers – Kittitas County Environmental Health Director. Joe Jimenez – Management Consultant. Tom Swenson – CERSD Maintenance Supervisor. 74 Clint Marsh – Construction Management Consultant. o 4:30 p.m. – Crawlspace inspection: James Green – Clean Air Now Representative. Rich Ellis – State Environmental Health Inspector. Clint Marsh – Construction Management Consultant. • Due to time constraints James Green was unable to inspect the crawlspace under the gymnasium. He will set a time with Tom Swenson for his inspection. Note: Tom Swenson-CERSD, Brent Walley-ATS, Clint Marsh KJM, previously inspected the gymnasium crawlspace. th September 30 , 2002 – Confirmed completion of the Work and performed final building inspection. o Reviewed the following work for completion status: Splash/ice guard installation. Crawlspace vent blocking per discussions with Keithly Welsh Associates and ATS Automation. Crawlspace access hatch seals. Fresh air intake duct access panels. Flashings & caulks at various exterior locations. Outside air duct to “residential-type” furnace in maintenance facility. o Toured building for final inspection with the following people: Rich Prill - Building Science and Indoor Air Quality Specialist/WSU. Nancy Goodloe-Administrator Kittitas County Health Department. John Wolpers-Kittitas County Environmental Health Director. Rich Ellis – State Environmental Health Inspector. o Keith Simon-Coalition Member. Thelma Simon-Coalition Member. Lisa Messmer-Clean Air Now. Joe Jimenez – Management Consultant. Tom Swenson – CERSD Maintenance Supervisor. Clint Marsh – Construction Management Consultant. Attended wrap-up meeting of attendees. All parties concurred that the defined Work was satisfactorily completed within the spirit and intent of the initial findings and recommendations. Summary 75 Construction Management Remediation Project Complete o Phase I – Construction Management Work Checklist - Complete o Phase II – Construction Work Validation and Verification – Complete 76 77 Appendices 7a & 7b Keathley Welsh, Inc. 7a – HVAC Assessment 7b – Retro-Commissioning Report 78 August 16, 2002 Site Visit Report Cle Elum – Roslyn H.S. Visit date: 8/15/02 Overview: KWA was contracted to provide a site review and recommendations in response to several issues related to HVAC systems design and performance at the Cle Elum – Roslyn High School. Below please find a list of these issues, a summary of our findings and recommendations for further action. Issue #1: During an earlier survey of the HVAC systems conducted in the Spring of 2002, it was noted that occupied CO2 levels in Room 203 were somewhat higher than other classrooms, and somewhat higher than the ASHRAE recommended limit of 1000 PPM. This room is served by a unitary wall mounted fan-coil, with a heating coil and full economizer (motorized return air / outside air dampers) fresh air capability. In addition, the excess air introduced into the room is relieved through a central relief air ductwork to a remote outside wall louver. A backdraft damper was noted to be installed in this relief air ductwork, just at the point of leaving the room. Upon a recent investigation by the school district maintenance staff, it was noted that the return air ductwork for AHU-3 is connected to this relief air ductwork, very near the point of exit with the building. For the record, AHU-3 serves an unrelated commons hall and interior classroom. It should also be noted that this ductwork connection (AHU-3 return to the relief air duct) was not shown on the “As Built” version of the most recent ductwork design plans. Based on our review of this situation, we are inclined to believe that in some (if not all) situations, the AHU-3 return air duct may be actually introducing a negative pressure into the relief air duct, relative to the outside air. This would then cause the outside air to actually migrate back into the relief air ductwork en route to the AHU-3 return air ductwork. While this in of itself in not of major concern, it should be noted that an exhaust fan (EF-5) also is ducted to this common relief plenum, near the point of exit with the building. Therefore, it is quite possible (likely) that under some conditions, this exhaust air could be reintroduced back into the building through the AHU-3 return. We would recommend that this union between the AHU-3 return air ductwork and the relief air ductwork be dismantled and capped on the relief ductwork end. The return air ductwork could either be left open (a balancing damper should be installed) to return air from the surrounding ceiling plenum, or could be extended to return air from the space actually served by AHU-3. And finally, it would be appropriate to install a backdraft damper in the relief ductwork, prior to the point where the exhaust fan (EF-5) ductwork is introduced. This would insure that exhaust air cannot migrate back into the building 79 through the relief ductwork, and would provide additional protection against cold-air infiltration while the building is not occupied, during cold weather situations. KWA does not believe that the high CO2 levels noted in room 203 would have likely been related to the above issue. If the minimum outside air setting for the economisers on the fan-coil unit serving this area was adequate (approximately 15 CFM per person), the amount of fresh air introduced into the classroom should have been enough to maintain CO2 levels below the 1000 PPM threshold. KWA would suggest verification of this ventilation rate, and re-adjustment of the minimum occupied fresh air setting may be appropriate. KWA would further suggest that a more effective ventilation method would be through the use of CO2 monitoring sensors tied to the existing Alerton control system. This would allow for automatic reset of these minimum fresh air setpoints based on actual occupant demand. Issue #2: The CERSD Maintenance Staff also reported an on-going problem with several exhaust fans serving the locker rooms. These fans had been tripping off on high amperage draw. When we further investigated, it was found that these fans were rotating in the wrong direction. When the rotation was corrected, the fans operated normally with the full load amps slightly (1 amp) above the normal FLA rating. KWA would suggest the drive sheaves (pulley) for these fans be reduced to the next smaller diameter as necessary to reduce the amperage draw to within the FLA rating of the motors. Adequate CFM will be verified during the upcoming commissioning routines. Issue #3 It had been noted by the High School staff that the smell of roasting popcorn in one of the classrooms was noticed in the office area immediately after the cooking had begun. KWA and the district staff investigated this issue and could find no cross connection or potential leaks in the ductwork serving this room. It was noted however that the relief for this room discharged directly outside through a relief louver located in fairly near proximity to the outside air intake grille for the Office air handling unit. Upon closer inspection, it appears that the warm relief air is rising up under the roof eaves and then migrating the short distance to the intake for the AHU outside air intake. While this mixing of some relief air with fresh air poses no real serious health concerns, the transfer of odours may be occasionally objectionable. KWA would suggest that a short baffle could be constructed to force the relief air to travel up and over the roof edge, and thus the relief air would not likely be pulled into the fresh air intake of the Office AHU. (Note: there are two relief louvers located in this area that would need to be baffled) Issue #4: The CERSD M&O staff also asked KWA to review the outside air / return air damper linkage for AHU-14 (serves several small rooms in the Wood Shop area). Apparently, this unit had been designated to provide 100% fresh air to these areas, as the return air ductwork was totally sealed shut just outside the AHU. The damper linkage to the return 80 air damper was still functioning. While this unit is most likely programmed to go to and stay in the 100% outside air position prior to starting the fan, KWA would suggest this operation be reviewed during the upcoming commissioning routines and confirmed as appropriate. Also, it would not hurt to permanently disconnect the return air damper linkage to avoid any future confusion as to the intended operation of this AHU. Issue #5: KWA was also asked to review the location of the stove exhaust vent for the Home Economics room. This exhaust is vented through a recessed sidewalk louver located outside the exterior wall. KWA would suggest a hooded ductwork extension be fashioned for this louver to provide for better discharge of kitchen exhaust, and to avoid this exhaust route getting restricted by snow. This should also help direct the odours away from the building, and will eliminate the condensation occurring on the building siding. Issue #6: The CERSD M&O staff also asked KWA to review the location of a new exhaust fan designed to ventilate the crawl space where the abandoned ductwork is located. KWA believes these exhaust fans will provide for adequate ventilation of these spaces, and should prevent any possible air migration from the crawl space to the classrooms above. It should be noted that in cold weather, the make-up air for these fans may cause freezing concerns in the crawlspace. The CERSD M&O staff may want to consider sealing off all leaks to the outside from this crawlspace and providing make-up air from the conditioned space above. This would actually improve the negative to positive pressure differential from the crawl space to the classrooms above, and would help to avoid freezing concerns in the crawlspace. Summary: The majority of the above recommendations can be implemented fairly easily with no actual engineering design work necessary. At the Owner’s discretion, KWA can provide some additional details regarding our recommendations, and/or we can also assist in the development of a written scope of work to be used in the soliciting of an appropriate contractor to complete the work. Pete Keithly Keithly Welsh Associates Inc. 81 August 28, 2002 Retro-Commissioning Issues Report Cle Elum - Roslyn H.S. The following issues were discovered as a result of retro-commissioning procedures conducted on the HVAC related systems at the Cle Elum - Roslyn High School on 8/27 and 8/28, 2002. After each issue description, please find our related recommendations, our assignment of the most appropriate responsible party, and the current status of the issue. Note; these issues have not been prioritized in any particular order. # 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. ISSUE DESCRIPTION and RECOMMENDATIONS ASSIGNED TO STATUS 8/28/02: Some operating schedules for HVAC equipment may not be appropriate. Suggest review of all current operating schedules and equipment assigned to those schedules to determine if schedules and associated equipment are appropriate. Make changes as necessary with input from school district staff. 8/28/02: Multiple trend logs in system. Suggest reviewing all trend logs and deleting those that are not currently being used. 8/28/02: Sequence of Operation as provided in the ATS Automation “As-Built” drawings does not describe the operating sequences for all equipment, nor does it provide adequate detail describing the various control sequences currently operating. Suggest these operational sequences be reviewed, updated and expanded as appropriate. 8/28/02: The new smoke/fire damper installed on the new AHU-3 return duct from the lobby must be supplied with power. The school district M&O staff are aware of this issue. 8/28/02: The exhaust fan in the Health Room is quite noisy. Suggest this exhaust fan be replaced with a quieter model, or the fan should be remotely mounted. 8/28/02: Room temperature sensor in Work Room (for AHU1 Zone 2) is mounted on wall nearly behind a refrigerator. The heat from this refrigerator will cause the sensor to read abnormally high whenever the refrigerator compressor is running. Suggest this sensor be moved to a better location within this zone. 8/28/02: Many of the “Optimum Start/Stop” parameters were set up wrong in the Alerton controllers. Function was disabled until appropriate changes can be made by controls contractor. 8/28/02: The discharge air low-limit appeared to kick-in during the test of AHU-4, while the unit was in mechanical cooling. Suggest the low limit be adjusted or disabled during mechanical cooling. 8/28/02: Is AHU4 allowed to run 24/7/365? This AHU services a computer lab. Check schedule. 8/28/02: During the full heating mode test, the discharge air for AHU1 zones 1 and 2 never got above 80 degrees. Suggest the operation and performance of these duct coils be further investigated. 8/28/02: It is not clear what triggers the “Building Heat Required” point. Suggest all details of boiler control be provided in Sequence of Operation description. 8/28/02: The Micro-Set sensor for the kitchen is located too near the dishwasher. Suggest relocating to a more appropriate spot. 8/28/02: UV-9 only put out 69 degree air in full call for heat. Found isolation valves closed. ATS Open ATS Open ATS Open CRSD M&O Open CRSD M&O Open ATS Open ATS Open ATS Open ATS Open ATS Open ATS Open KWA Closed ATS Open ATS Open 14. 8/28/02: UV-9 heating valve responds very slowly to a call for heat. Suggest control loop for this valve be reviewed. 15. 8/28/02: AHU-2 had a supply air temperature of 65 degrees when in a 100% OSA mode and full call for cooling, with OSA temperature of 52 degrees. Heating valve may be leaking by. Suggest performance of this AHU be further investigated. 82 # ISSUE DESCRIPTION and RECOMMENDATIONS 16. 8/28/02: AHU-5 had a supply air temperature of 62 degrees when in a 100% OSA mode and full call for cooling, with OSA temperature of 52 degrees. Heating valve may be leaking by. Suggest performance of this AHU be further investigated. 17. 8/28/02: All controller economizer lock-out set points were set for 72 degrees. Without mechanical cooling, it may be better to simply allow the economizers to operate regardless of the OSA temperature. Also, this will provide better air quality. Suggest leaving lockout set point on all controllers (except AHU4) at 125 degrees. 18. 8/28/02: Found schedule for gym, lockers and restroom (schedule #5) HVAC was incorrectly keeping these units off on Tuesday and Weds. Corrected schedule. 19. 8/28/02: Whenever the space temperature goes above 2 degrees higher than the current cooling setpoint, an alarm is noted at the GUI. Since there is no mechanical cooling, suggest this range be increased, or the alarm be eliminated (or disabled when OSA is above 60 degrees? 20. 8/28/02: The “User Activity Log” indicated the last user logged in on 8/30/02. Today is only 8/28/02. Suggest ATS review this report. 21. 8/28/02: GUI indicates that the Gym and Commons have “CO” (Carbon Monoxide) controllers. This should be changed to “CO2” 22. 8/28/02: The new CO2 sensors are providing informational data only, and are not being used for demand ventilation purposes. Suggest that these units be programmed for demand ventilation sequence to determine if appropriate for all locations. 23. 8/28/02: When in the “Quick View” GUI window, some colors did not seem to match the temperature off-sets. Also, the alarms were not consistent. Suggest ATS review. 24. 8/28/02: CRSD M&O staff noticed the return air duct from AHU-3 was pulling air from the general relief air duct. This connection was severed and capped, and the return was run to the lobby area. Also, an anti-back-draft damper was installed near the point where the relief duct exits the building to avoid any possibility of contamination from an exhaust fan that discharges into a common plenum. 25. 8/28/02: Existing printer for the control system is old and slow. Suggest replacing with new color inkjet printer. 26. 8/28/02: Boiler controls were set up wrong. Adjusted to stage boiler in 4 stages from 190 (stage 1) to 175 (stage 4) with a 3 degree differential at each stage. 27. 8/28/02: Boiler #2 failed to start on one try. CRSD M&O staff is aware of a problem with the combustion air proof switch. Suggest this problem be resolved. 28. 8/28/02: GUI for boilers did not provide for manual run of boilers and pumps. This feature was on original graphic. ATS to reinstate. 29. 8/28/02: Hydronic heating sequences do not appear to be appropriate for the equipment and piping. Three-way valves won’t close below 50% when unit is running. Suggest ATS review with KWA and revise as appropriate. 83 ASSIGNED TO STATUS ATS Open KWA Closed KWA Closed ATS Open ATS Open ATS Open ATS Open ATS Open KWA Closed CRSD M&O KWA Closed CRSD M&O Open ATS Open ATS Open Appendix 8 Report #2 – Microlab Northwest Post-Remediation Testing and Sampling August 30, 2002 84 MICROLAB NORTHWEST 7609 140TH PL. NE REDMOND, WA 98052 PHONE: (425) 885-9419 LABORATORY REPORT TO: Clinton G. Marsh cc: Mike Snow, Principle REPORT #: 765-02 KJM Cle Elum/Roslyn High School DATE: Sept. 9, 2002 500 108th Ave. N.E., Suite 1000 2690 SR 903 Bellevue, WA 98004 Cle Elum, WA 98922 PHONE: (FAX: ( e-mail: cmarsh@kjmassoc.com, snowman@cleelum.wednet.edu SUBJECT: Particle Identification SPECIMEN: Tapelifts, Air Samples, and Insulation Samples, Cle Elum High School REFERENCE: Microlab Northwest Report #632-02 SUMMARY On August 30, 2002 a number of tapelift, air samples, and material samples were collected from Cle Elum High School by E. R. Crutcher with the assistance of Mike Snow, Clint Marsh, Tom Swenson, and Thelma Simon. Tapelifts were collected from rooms 100, 200, 203, 302, and the Library. Air samples were collected from these same rooms and from the exterior of the building outside the Counseling offices on the concrete drain pad (see table on page 5). Exterior wall samples were collected from the material that had been removed from the outside of Room 100. This material was in the back of a truck at the time of sampling. Two samples of discolored insulation were collected in the overhead space of the building near Air Handling Unit #10. The analysis shows the following: 8. There is not a glass fiber problem in the rooms tested. 9. There is not a general fungal problem in the rooms tested. 10. The carpets have been thoroughly cleaned. 11. Horizontal surfaces had not been cleaned at the time of sampling. 12. Airborne dust loading outside the building varies dramatically and can be quite high. 13. Airborne dust loading inside the building can be quite high even in an "at rest" condition. 14. Discoloration of the blanket insulation in the overhead area is due to dust and not fungal growth. 15. The exterior siding had some fungal growth on the wood but not on the water-barrier board. Additional observations are provided in the body of the report and in the conclusion. Signed: ________________________________________ E. R. Crutcher, Consultant 85 INTRODUCTION On August 30, 2002 a number of tapelift, air samples, and material samples were collected from Cle Elum High School by E. R. Crutcher with the assistance of Mike Snow, Clint Marsh, Tom Swenson, and Thelma Simon. Tapelifts were collected from rooms 100, 200, 203, 302, and the Library. Air samples were collected from these same rooms and from the exterior of the building near the Counseling offices on the concrete drain pad. The exterior air sample was collected every half-hour, starting at 10:00 AM and concluding at 12:10 PM. Exterior wall samples were collected from the material that had been removed from the outside of Room 100. This material was in the back of a truck at the time of sampling. Two samples of discolored insulation were collected in the overhead space of the building near Air Handling Unit #10. Photographs were take to document the sample locations. The samples collected were as follows: Tapelifts Room 100, Windowsill Room 100, Univent Heater Room 100, Teachers Desk, 2 Contacts Room 100, Computer Station, 2 Contacts Room 200, Windowsill Room 200, Equipment in Boxes Room 200, Teachers Desk, 3 Contacts Room 200, Top of Computer Monitor Room 201, By Computer on Desk Room 201, TV Table Room 201, Counter Against Wall Room 203, Windowsill Room 203, Top of Computer Monitor Room 302, Top of Refrigerator, Kitchen #1, 3 Contacts Room 302, Top of Monitor on Teacher's Desk, 2 Contacts Room 302, Top of Monitor next to Wall Room 302, Over Oven, Kitchen #3 Library, Location of Old Desk Library, Career Center Teacher's Desk Monitor, 2 Contacts Library, Checkout Desk Library, File Cabinet Overhead Ventilation Space Open Discolored Insulation near AHU #10 Discolored Insulation Covered with Plastic Sheet near AHU #10 Exterior Wall Room 100, Dark Discoloration on Wood Paneling Room 100, White Discoloration on Water Shield Board (All of the exterior wall samples were collected from material in the back of a truck) 86 The tapelifts were placed on clean microscope slides and immersed in acetone for about two hours and then removed. The slides with the tapelifts were rinsed with clean acetone as they were removed from the immersion tank. The tapelifts were allowed to dry for ten minutes and then mounted using a synthetic resin (Eukitt). The completed mounts were analyzed using analytical light microscopy. The discolored insulation samples were mounted directly in resin. The discoloration on the sheet materials was tapelifted and processed as a standard tapelift. RESULTS The tapelifts from Room 100 contained skin flakes, natural minerals, clothing fiber, paper fiber, soil, phytoliths, pollens, cleaning debris, lichen spores, sawdust, charred wood, starch, cosmetics, shoe wear, aerosol droplets, insect parts, plant parts, glass fiber, food debris, spores, mycelium, blue spray paint spheres, perolite, pencil debris, weld spheres, cenospheres, bird feather barbules, and diatoms. The materials present had changed as a result of the introduction of additional particles from outside (natural minerals, soil, phytoliths, pollens, spores, plant parts, etc) and cleaning debris from the carpet cleaning. The carpet in the room was dramatically cleaner than when last seen on June 8, 2002. The ventilation system was on in the building at the time of testing. The horizontal surfaces on counters, shelves, equipment, cabinets, etc. had not been cleaned since prior to June 8, 2002. The dusts present on these surfaces was the same with the addition of dusts collected over the Summer. Air samples provided addition information on the quality of the environment during this test interval. The air sample collected in Room 100 contained skin flakes, natural minerals, paper fiber, soil, humus, plant parts, phytoliths, clothing fiber, hyphae, spores, insect parts, charred wood, sawdust, tire wear, and diatoms. The quality of the air is indicated by both the types of materials that are airborne and the quantity of those materials. The quantity is measured as the percent obscuration on the impaction plate sampler normalized to 150 liters of air. The percent obscuration is the amount of the collection surface covered by particles divided by the total surface available for collection, multiplied by 100 in order to express the value as a percentage. The obscuration for this sample, collected at 10:18 AM, was 10%. This was a bit elevated for a room at rest but with the ventilation system running, which creates turbulence, and the condition of the horizontal surfaces in the room this was not an unexpected value. Particles on surfaces are not dormant. In turbulent air some will loft from the surface and move through the air to another surface. That is one of the reasons it is important to keep horizontal surfaces clean. The tapelifts from Room 200 contained skin flakes, clothing fiber, paper fiber, natural minerals, soil, charred wood, sawdust, starch, pollens, phytoliths, insect parts, plant parts, spores, mycelium, glass fiber, tire wear, shoe wear, toner, food debris, blue spray paint spheres, cosmetics, pencil debris, weld spheres, cenospheres, pink pearl erasure, lichen spores, bird feather barbules, and diatoms. The glass fiber was at a fairly low levels with the exception of the sample from the Teacher's Desk. This area had much more glass fiber associated with yellow phenolic resin than it did in June 2002. Glass fiber of this 87 type is typical of blanket insulation and is the same type as that used in the ventilation system. Most of the glass fiber in this room appeared to come from the ventilation system. The spores present were typical of an exterior environment though Cladosporium was again the most common single type. The total spore population in this room did not indicate a fungal problem. The dust loading in this room, as with the other rooms, is the same for the most part with the addition of more particulate matter from outside the school and cleaning debris from cleaning the carpets. The air sample from Room 200 contained skin flakes, natural minerals, paper fiber, humus, soil, plant parts, phytoliths, clothing fiber, hyphae, spores, insect parts, charred wood, sawdust, tire wear, and diatoms. The obscuration for this sample, collected at 9:58 AM, was 18%. This was quite high for a room at rest. The types of particles and their relative proportions were not significantly different than the sample in Room 100. The tapelifts from Room 203 contained natural minerals, skin flakes, clothing fiber, paper fiber, soil, pollens, charred wood, sawdust, phytoliths, lichen spores, cleaning debris, insect parts, plant parts, spores, mycelium, tire wear, starch, shoe wear, glass fiber, bird feather barbules, toner, food debris, blue spray paint spheres, cosmetics, pencil debris, weld spheres, diatoms, cenospheres, and pink pearl erasure. The air sample from Room 203 contained skin flakes, natural minerals, paper fiber, soil, humus, plant parts, phytoliths, clothing fiber, hyphae, spores, insect parts, charred wood, sawdust, tire wear, and diatoms. The obscuration for this sample, collected at 10:35 AM, was 13%. This was quite high for a room at rest. The types of particles and their relative proportions were not significantly different than the sample in Room 100. The tapelifts from Room 302 contained natural minerals, paper fiber, pollens, soil, skin flakes, clothing fiber, insect parts, plant parts, charred wood, cleaning residues, sawdust, phytoliths, food debris, starch, lichen spores, shoe wear, mycelium, glass fiber, spores, cosmetics, tire wear, pencil debris, cenospheres, bird feather barbules, and diatoms. The dominant pollen in these samples was pine. The glass fiber was at a fairly low level and was predominantly from the acoustic ceiling tile. The spores present were typical of an exterior environment (grass Rusts) though Cladosporium was a common type. The total spore population in this room did not indicate a fungal problem. The air sample from Room 302 contained skin flakes, natural minerals, paper fiber, soil, humus, plant parts, phytoliths, clothing fiber, hyphae, spores, insect parts, charred wood, sawdust, tire wear, and diatoms. The obscuration for this sample, collected at 11:15 AM, was 8%. This was reasonable for a room at rest with the elevated levels outside the building (see Exterior Air Sample). The types of particles and their relative proportions were not significantly different than the sample in Room 100. The tapelifts from the Library contained paper fiber, skin flakes, cleaning residues, natural minerals, clothing fiber, insect parts, plant parts, charred wood, soil, sawdust, toner, starch, pollens, phytoliths, shoe wear, mycelium, bird feather barbules, glass fiber, spores, cosmetics, lichen spores, tire wear, pencil debris, cenospheres, and diatoms. The dominant pollen in these samples was pine. The glass fiber was at a fairly low level and 88 was predominantly from the acoustic ceiling tile. The spores present were typical of an exterior environment though Cladosporium was again the most common single type. The total spore population in this room did not indicate a fungal problem. The air sample from the Library contained skin flakes, natural minerals, paper fiber, soil, humus, plant parts, phytoliths, clothing fiber, hyphae, spores, insect parts, charred wood, sawdust, tire wear, and diatoms. The obscuration for this sample, collected at 11:51 AM, was 23%. This was quite high for a room at rest, even with the elevated exterior levels. The types of particles and their relative proportions were not significantly different than the sample in Room 100. Exterior Air Sample The exterior air samples contained natural minerals, soil, humus, plant parts, phytoliths, charred wood, tire wear, pollens, paper fiber, spores, mycelium, insect parts, glass fiber, sawdust, concrete dust, diatoms, flyash, cenospheres, and clothing fibers. The glass fiber was from blanket insulation and was probably part of the construction residue remaining from the work done on the exterior wall at this location. Samples had been collected at 10:00, 10:30, 11:00, 11:30, and 12:00. The respective obscurations were 6%, 9%, 36%, 24%, and 27%. The table below indicates the exterior dust loading at the time the air samples were collected in each room. The exterior samples were collected on the half-hour. The time the sample was started in each room is indicated in parentheses. All air samples were collected for ten minutes at a sampling rate of fifteen liters of air per minute. TIME Outside Room 100 Room 200 Room 203 Room 302 Library 10:00 6% 10:30 9% 10% (10:18) 11:00 36% 11:30 24% 12:00 27% 18% (9:58) 13% (10:35) 8% (11:15) 23% (11:51) Dust Loading by Time of Collection and Location There is relatively poor correlation between the dust loading in the rooms and the dust loading outside at the location of the exterior sample. When the sample in Room 200 was collected the outside loading was at 6% while the inside loading was at 18%. When the outside airborne loading increased to 36% the indoor sample (Room 302) was only 8%. The dramatic change in loading outside indicated by the 11:00 AM sample may be an actual change in airborne dust load generally or a change in wind direction that increased the loading locally. It is possible that the loading in the rooms is a function of wind direction relative to the position of the air intake for the ventilation system serving that room. The fact that the airborne dust in the rooms contained significant amounts of skin flakes indicates that the particles were not penetrating directly from the exterior. 89 They could be generated by lofting in the rooms due to turbulent air flow over contaminated surfaces or they could be from part of the ventilation system containing significant amounts of skin flakes (the recirculation loop in the system). Pressure pulses in the ventilation system due to wind loading on the intakes could be a contributing cause. Discolored Insulation in the Overhead Space Two areas of discolored glass fiber insulation blanket were sampled. One was openly exposed to the attic space and one was under a plastic sheet. Both were located near Air Handling Unit #10. The discoloration was due to particles attached to the glass fiber. These particles included natural minerals, sawdust, charred wood, paint spheres, and insect parts. The particles were very small (0.5 to 3 micrometers) for the most part. There was no evidence of mold growth in the insulation. Exterior Siding Deposits There were two exterior siding deposits of interest. One was a dark discoloration on the back side of the exterior wood paneling. The other was a white deposit on the black paper covering the water-barrier siding. The dark discoloration was predominantly natural minerals, soil, plant parts, insect parts, humus, mite debris, spores, pollen, charred wood, tire wear, and diatoms. The amount of fungal debris in this sample was low but the high mite population indicated that there had been more fungal growth than indicated by the tapelift. Fungus is one of the main food sources for the mites and there was more mite debris than could be explained based on the spores seen in this sample. The condition of the wood indicated some degradation but no excessive fungal growth at this time. The white deposit on the black paper was gypsum, calcium sulfate dihydrate. This was a water related deposit in that it was the result of water extracting gypsum from the board and the gypsum precipitating as the water ran down the barrier board. This deposit can not be reliably dated though the path of the water was consistent with the position of the board on the wall. There was no indication of any fungal growth. CONCLUSION The carpets in these rooms had been thoroughly cleaned and were in excellent condition. The section cut out of the carpet in room 203 had not been replaced but the carpet in that room was otherwise in excellent condition. The horizontal surfaces in these rooms had not been cleaned and the locations of the tapelift samples collected in June were still evident in many locations. Additional dusts had accumulated over the summer, including debris from the carpet cleaning and other activities that had taken place. Air sample were collected at this time to evaluate the "at rest" condition of the air in the rooms. The air smelled fresh in the rooms though the dust loading was quite high in room 200 and the Library and was a bit high in room 203. The types of particles present 90 in the air samples were the same regardless of loading. That indicates that a local room or specific ventilation system source was not responsible for the elevated loading. The dust loading outside the school was also very high at times. The exterior dust loading varied from 6% obscuration to 36% during the two hours sampled. The exterior loading was not directly reflected in the rooms sampled. The particles typically seen in the room samples included skin flakes and other particles generated inside the building. That indicates that the source of the particles was air turbulence over contaminated surfaces in the room itself or it came from the portion of the ventilation system that contained a high burden of skin flakes, the air recirculation system. The discoloration of the insulation blankets in the overhead space near Air Handler Unit #10 is due to dust loading on the glass fibers. There is no indication of any fungal growth at these locations or nearby. The discoloration on the lower edge of the exterior wood siding did indicate some fungal growth supporting a significant mite population. The amount of fungal growth on the siding was not excessive and the panel had been removed because it was known to have been exposed to water and to have some fungal growth detected during the investigation conducted in June. The white deposit on the water-barrier board was gypsum, calcium sulfate dihydrate, and not fungus. Thank you for this opportunity to be of service. If I can provide any further assistance please contact me. Signed: ________________________________________ E. R. Crutcher, Consultant 91 Appendix 9 Washington State Department of Health Walkthrough Inspection, WAC 246-306 September 3, 2002 92 Dr. Evelyn Nelson, Superintendent Cle Elum-Roslyn School District #404 2690 SR 903 Cle Elum, WA 98922-8704 Dear Superintendent Nelson: In accordance with WAC 246-366, an inspection of the Cle Elum-Roslyn High School was conducted on September 3, 2002 by Richard E. Ellis and Tim Hardin of the Washington State Department of Health, and John Wolpers of the Kittitas County Health Department. Also present during the inspection were the school nurse, Rose Murdock, the school maintenance supervisor, Tom Swenson, and Clint Marsh from the KJM construction management firm. Joe Jimenez, of Jimenez & Associates, the school district consultant, observed the inspection. This report is a summary of the inspection, based on measurements and notes taken at the site. A set of digital pictures documenting the observations is being sent to you along with this report. Summary: The Cle Elum-Roslyn High School has recently completed remediation recommendations to address indoor environment and air quality concerns reported by students and staff. This health inspection was made to determine whether the school building environment complied with existing state rules and the Health and Safety Guide of the Office of Superintendent of Public Instruction and the Washington State Board of Health. Areas of emphasis included heating, ventilation, and air conditioning equipment; general sanitation and safety of the facility; building condition; plumbing fixtures; and lighting. During this inspection, the completed remediation recommendations were specifically examined for compliance with health and safety statutes, codes, rules, and the OSPI-DOH Health and Safety Guide. In general, the building’s flooring, walls, ceilings and fixtures appeared reasonably clean and well maintained. With proper routine care and maintenance, this building and its operating systems would provide an acceptable indoor environment for the building’s occupants. There were no facilities issues observed which would prevent the school from functioning normally during the school year. 1. The HVAC systems appeared to be operating satisfactorily, with flow rates of 75-450 linear feet per minute recorded in all areas measured. Colored ribbons were used to verify airflow through high-ceiling air supply units. 2. The new pleated filters and filter trays were clean and well maintained, and ceilings were generally in good repair. 3. There did not appear to be significant physical safety hazards in classroom areas. 4. Although some construction dust was present on the air diffusers and dirt was observed near the boys’ locker room due to football practice, these issues were resolved by the 93 maintenance staff before the inspection was concluded. The dirt being tracked in by the locker area can be addressed by walk-off mats and other means. 5. Direct observations of the crawl space were made to confirm the condition of the ventilation depressurization system, which was operational at the time of inspection. 6. Observations of the new CO2 monitors and vacuum pressure gauges were made and photographed. The monitors and gauges are easily visible to building occupants and others who are charged with maintaining the facility. 7. An inspection of all air handling units and catwalks in the attic was made. The units were working in a satisfactory manner at the time of inspection. 8. Posted records of filter changes and other routine maintenance were verified. Food service, water supply and athletic field inspections were not performed during this inspection. Inspection Notes: 1. ServiceMaster of Bellevue performed carpet restoration throughout the building. There are several areas where pieces of the floor covering will need to be replaced due to permanent ink markers being used on it. 2. Carpet moisture measurements were taken in rooms in both wings of the school. All measurements were 6%, which is virtually as dry as seasoned wood. 3. The woodshop office supply air vent was deliberately, visibly blocked at the time of inspection. As of the date of this report, the vent has been unblocked as a result of school district management action. The air vent should kept unblocked at all times during use of the shop, since dust, vapor and fume issues can impact student and teacher health. 4. The microscope cabinet in the science room was moved, revealing a metallic stain on the floor that needs cleaning. It was noted during the inspection that storage of chemicals in or near this cabinet is not recommended since the return air for the room ventilation is located there. 5. The small computer area in the library had relatively low air circulation, even though overall ventilation needs for normal room occupancy were met for the library in general. The school district maintenance director and facility consultant from KJM arrived at a proposed solution to this problem (which could be addressed in a future facilities project) which would re-direct air flow to this area. 6. The roof flashing and exterior splash guard projects need to be completed prior to winter weather conditions. This is on the current facilities project schedule and will be verified in a subsequent inspection this fall. 7. Four large crawlspace vents were observed. These are vented through the roof and monitored with pressure gauges that are readily accessible to building occupants. 94 8. Chipmunks, mice and other rodents on the premises have caused damage to walls and classroom supplies. The district should review its pest control practices in the exterior perimeter surrounding the building to eliminate burrows and other harborage. 9. Light readings in classrooms throughout the building ranged from 35-100 Foot-candles, which is well above the minimum levels required by the regulations. 10. Exterior doors in classrooms should be kept closed during normal classroom operations in order for the HVAC systems to properly function and filter the air. There is no need to open exterior doors in the classrooms for comfortable temperature and air flow where room CO2 levels are maintained below 1,000 parts per million, and temperatures and relative humidity are maintained in the human comfort ranges specified by the Washington State K12 Health and Safety Guide and standards of the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE). 11. It was noted during the inspection that the school district is developing a long-range Indoor Environment Management Plan for IAQ issues. This plan should address the district’s policy on purchasing and use of custodial materials and classroom products containing chemicals, such as solvents and permanent markers. If you have any questions regarding this report, please feel free to contact me at (360) 236-3072. Sincerely, Richard E. Ellis, REHS, RS, MS, JD School Program Manager 95 Appendix 10 Rich Prill Post-Remediation Walkthrough Assessment October 1, 2002 96 October 1, 2002 Cle Elum-Roslyn School District Evelyn Nelson Superintendent 2690 SR 903 Cle Elum, Washington 98922 Dear Superintendent Nelson: Yesterday Mr. Tom Swenson conducted a final inspection tour of the Cle Elum-Roslyn High School with Mr. Rich Prill, Building Science and Indoor Air Quality Specialist from Washington State University. Also in attendance were Mr. Rich Ellis, State Environmental Health Inspector, Mr. John Wolpers, Kittitas County Environmental Health Inspector, Ms. Nancy Goodloe, Kittitas County Health Department Administrator, Mr. Joe Jimenez, contracted consultant, Ms. Lisa Messmer, Clean Air Now Representative, Keith and Thelma Simon, citizen coalition members. I am very happy to report that all parties concurred that the defined Work was satisfactorily completed within the spirit and intent of the initial findings and recommendations by both Mr. Rich Prill and Mr. E. R. Crutcher of Microlab Northwest. This brings Phase I and Phase II of the three-phase District remediation plan to address health concerns to completion, thereby completing the construction remediation project conducted by KJM. Current reports are attached and please call me if you have any questions or comments. We wish you the very best in the Phase III implementation of a long-term indoor air quality management plan and would like for you to think of us in the event that facilities/construction assistance is needed in that effort or in other future efforts. It has been a pleasure working with you, your staff, and members of your community. Sincerely, Clinton G. Marsh Northwest Region Educational Program Manager c: Karen Mask; Duane Mask 97 Appendices 11a & 11b Cle Elum-Roslyn School District Phase 3 Plan 11a – Tracking and Monitoring Health Complaints 11b – Health & Safety Committee Appointment December 2, 2002 98 99 100 101 102 103